Dimplex Water Heater Unvented Water Heater User Manual

Dimp-15278-SCx_Instructions 31/3/06 9:32 am Page 1  
DIMPLEX  
UNVENTED WATER HEATERS  
INSTALLATION MANUAL  
Marketing Department, Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF. Telephone: 0870 077 7117 Fax: 0870 727 0109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimp-15278-SCx_Instructions 31/3/06 9:32 am Page 5  
1 Element on IDH indirect models up to 305 litres and 80  
litre DH direct model  
CONNECTINGTHE WATER SUPPLY  
DRAINTAP  
STANDARD ENERGY LOSSES  
Pipework is not supplied  
A drain tap to drain the unit must be fitted to the cold-water inlet  
pipe somewhere between the SCx unit and the cold water  
valve assembly and at as low a level as possible, see fig. 1.  
The heat loss of each SCx Unvented Unit while maintaining  
the temperature of the stored water at 65 degrees Celsius.  
(See performance table below).  
2 Elements on DH direct models from 130 up to 305 litres.  
Additional elements from 215 to 305 litres are available on  
request.  
All pipework should be installed using good plumbing  
practice. We recommend 22mm mains cold water supply  
is used.  
1) Tests carried out by BBA. Slight variations may occur with  
changes to water mains supply pressure  
Install a Stop Cock Valve before the cold water inlet  
assembly on the incoming mains water supply so the unit  
can be isolated if required.  
Cold-water control valve comprising line strainer, check  
valve, pressure reducing valve set to 2.1 bar  
PIPEWORKTOTAPS  
Ideally a 22mm pipe run should supply the outlets throughout  
the property with short lengths (max 1 metre) runs of 15mm  
going to baths, showers, and basin taps. Smaller bore pipe  
can be used to suit taps.  
SCx Performance  
Expansion relief valve with non return valve set at 6 bar  
Tundish 15mm x 22mm F x F  
Nominal  
Heat up  
Heat up  
Reheat  
Reheat  
Heat loss in  
24 hrs  
Capacity Model IDH Model DH Model IDH Model DH  
Litres  
80  
Mins  
33  
28  
33  
27  
35  
42  
50  
Mins  
64  
Mins  
23  
21  
24  
24  
30  
35  
42  
Mins  
53  
kw/hr  
COLD WATERVALVE  
1.12  
1.50  
1.82  
2.10  
2.64  
2.73  
2.88  
Temperature / Pressure relief valve set at 90 degrees  
Celsius and 7 bar pressure relief (factory fitted)  
130  
150  
175  
215  
255  
305  
115  
138  
167  
212  
263  
313  
90  
The combined cold water valve (supplied) can be connected  
anywhere on the cold water mains prior to the unit. It can even  
be located at a point near to where the mains supply enters the  
premises if this is more convenient. When installing the cold water  
valve, ensure that the arrow is pointing in the same direction as  
the mains water supply flow when connecting, see fig 2.  
SECONDARY CIRCULATION  
104  
124  
153  
184  
220  
This is particularly easy to fit on the SCx units; a Swept Tee (not  
supplied) is needed for all indirect models if secondary  
circulation is required, see page 6 fig. 3 for fitting. A non-return  
valve (not supplied) must be fitted to prevent backflow. You  
will need a pump to circulate the hot water (not supplied). The  
return feed is in 15mm pipe and all work can be done on site.  
Motorised valve (indirect units only)  
Cylinder thermostat-factory fitted to cylinder, maximum  
setting 85 degrees Celsius (indirect units only)  
Thermal cut out set to operate at 87 degrees Celsius plus  
or minus 3 degrees (indirect units only)  
2) These figures relate to a 45 degree differential between  
the stored water and ambient temperature  
The cold water balancing port, on the valve, allows you to  
connect the cold water mains to the rest of the property thus  
giving balanced pressure throughout. If this facility is not  
required leave the cap on.  
Option – Expansion vessel with capacity as below: -  
WITH AN SCx UNVENTED CYLINDER THE  
FOLLOWING IS SUPPLIED AS STANDARD  
Typical Indirect Tank installation using external expansion vessel option  
Tank Size  
ExpansionTank Required  
12 Litres  
Before commencing installation check that all the  
components of your SCx Unit are contained in the kit.  
80 to 130 Litres  
150 to 215 Litres  
255 to 305 Litres  
WATER FLOW  
HOT WATER OUTLET  
1  
3KW Incoloy 825 heating element-incorporating  
thermostat to 70 degrees Celsius and resetable safety cut  
out set at 80 degrees Celsius  
18 Litres  
EXPANSION VESSEL  
7 BAR / 90 DEGREES  
(WALL MOUNTED)  
PRESSURE &  
25 Litres  
TEMPERATURE  
RELIEF VALVE.  
WATER FLOW  
TO COIL INLET  
PRIMARY FLOW  
TUNDISH  
WATER FLOW TO  
MANIFOLD VIA  
FLEXIBLE HOSE  
SCx UNVENTED INSTALLATION INSTRUCTIONS  
PRIMARY RETURN  
WATER FLOW  
FROM COIL INLET  
TWIN  
THERMOSTAT  
SECONDARY  
RETURN FLOW  
PRESSURE  
REDUCING VALVE  
SET AT 3 BAR  
6 BAR  
EXPANSION  
RELIEF  
WARNING: Under no circumstances must the factory fitted temperature pressure relief valve be removed. This will totally invalidate  
any guarantee or claim. The cold-water inlet valve assembly must be fitted or the SCx unit will not perform satisfactorily.  
VALVE  
WATER FLOW  
TO OVERFLOW  
IMMERSION  
HEATER  
DO NOT ATTEMPT TO VENT THE PRIMARY CIRCUIT THROUGH THE SCx UNIT.  
WATER INLET  
WATER FLOW  
INLET SIDE OF TANK  
All boilers should be installed to manufacturers instructions and the primary circuit through the SCx unit must be pumped.  
SWEPT TEE  
WATER FLOW  
FROM EXPANSION  
TANK TO 22MM  
FEMALE THREAD  
BEHIND COVER  
DRAIN  
COCK  
BLANKED  
PORT  
BALANCED  
COLD WATER  
OUTLET  
SITINGTHE SCx UNIT  
CHECK WATER PRESSURE & FLOW RATES  
Cold water inlet valve assembly  
We suggest 1.5 bar pressure & 15 litres / minute flow rate to  
be the minimum requirements for satisfactory operation. Less  
than this the unit will still operate but you will not be able to run  
two, or more, outlets at the same time. 85% of all U.K homes  
have more than 2-bar pressure.  
6 BAR  
EXPANSION  
RELIEF  
The unit can be placed anywhere convenient. Because it is  
connected directly to the mains water supply it is equally  
efficient on any floor – ground, first or second. Avoid areas  
that may be subject to frost. Try to keep pipe runs as short as  
possible for maximum economy, especially hot water  
discharge pipes running down from the SCx unit.  
VALVE  
PRESSURE REDUCING  
VALVE SET  
AT 3 BAR  
2  
The mains supply must not exceed 16 bar. If it does a special  
pressure-reducing valve will be required.  
WATER FLOW INLET SIDE OF TANK  
The unit can be fitted into a conventional airing cupboard  
and does not require any additional insulation.  
WATER FLOW FROM EXPANSION  
TANK TO 22MM FEMALE THREAD BEHIND  
COVER  
Important Note: - Stainless Steel Tectile push fit elbows are  
fitted as standard to all SCx Cylinders.  
BLANKED  
PORT  
ALL SCx UNITS MUST BE STORED VERTICALLY  
4
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimp-15278-SCx_Instructions 31/3/06 9:32 am Page 7  
2 PORT VALVE + 3 PORT MID POSITION  
VALVE (Y-PLAN) SYSTEM  
GUIDANCE LAYOUT ONLY  
SECONDARY CIRCULATION  
CONNECTION DIAGRAM  
Fig.5  
Fig.3  
As our heating element is Incoloy 825 and is fitted with a cut-  
WIRING  
3
/
4
out and thermostat for safety, a non-standard 1 " boss is fitted  
to the unit. Replacements can only be obtained from your  
authorised Dimplex Service Agent.  
All electrical wiring should be carried out by a registered electrical  
contractor and must conform to the latest IEE wiring regulations  
Do not switch the power on until the unit has been filled with  
water and all wiring has been earthed, see Fig. 4 and 5.  
All our heating elements have a built in manual reset cut-out.  
This will operate if the immersion heater thermostat fails.  
FITTING IMMERSION HEATERS  
WARNING: Ensure that the immersion heater thermostat is set  
at 60 degrees Celsius.  
These are supplied as standard  
2 * 2 PORT (S-PLAN) VALVE SYSTEM  
GUIDANCE LAYOUT ONLY  
E N L  
An ’O’ ring is supplied as the seal and must be fitted against  
the flange of the element. Take care not to cross thread and  
DO NOT USE any other type of seal.  
Fig.4  
FITTINGTHETHERMAL CUT-OUT &  
PRIMARY CONNECTIONS  
ROOM  
HTG  
ON  
DHW  
ON  
PROGRAMMER  
GY 1  
3
2
L
N
1
E
THERMOSTAT  
The motorised valve supplied and the thermal cut-out (Hi  
limit stat) must be fitted to the primary flow. Use  
compression fittings only.  
1
2
3
2 PORT MID  
POSITION VALVE  
Br BI  
G O GY  
4
Operation of the cut-out and motorised valve  
5
TWIN  
C
2 C  
1
2 GY  
THERMOSTAT  
To comply with BBA regulations and to prevent the  
temperature reaching 100 degrees Celsius the thermal  
cut-out supplied must be fitted.  
6
7
E
8
BOILER  
PUMP  
The thermal cut-out is wired in series to the cylinder  
thermostat. When the thermal cut-out senses an abnormal  
rise in temperature in the primary flow the electrical supply  
to the motorised valve will be cut, and the valve will be in  
the closed position thus cutting of the primary water from  
the boiler to the indirect coil in the cylinder. If this occurs it  
must be reset manually. If the thermal cut-out operates  
check the cylinder stat and / or boiler stat.  
L
L
N
N
E
E
9
L
N
10  
MOTOR ON/OFF  
VALVE  
Br BI G  
GY  
O
6
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimp-15278-SCx_Instructions 31/3/06 9:32 am Page 9  
standings, grassed areas etc. are acceptable providing  
that where children may play or otherwise come into  
contact with discharges a wire cage or similar guard is  
positioned to prevent contact, whilst maintaining visibility.  
TUNDISH  
DRAINING  
G3 REQUIREMENT  
The tundish supplied must be fitted visible to the occupier. The  
discharge pipe must be 22mm copper pipe. Regulations do  
not permit more than 3 x 90-degree bends between the SCx  
unit and the outflow. Between the temperature & pressure  
relief valve and the first 90-degree bend there must be a fall  
of at least 300mm. The fall of the pipework must be  
continuous and the pipe should terminate in the gully or be  
bent backwards onto an outside wall, in a place where  
discharge cannot be injurious to persons.  
Switch off electrical power to immersion heaters and/or shut  
‘…there shall be precautions…to ensure that the hot water  
discharged from safety devices is safely conveyed to where it is  
visible but will not cause danger to persons in or about the building.’  
down the boiler. Close the stopcock valve to isolate the SCx unit.  
Attach hosepipe to the drain cock having sufficient length to  
take water to a suitable discharge point.  
iii) discharges at high level; e.g into a metal hopper and  
metal down pipe with the end of the discharge pipe  
clearly visible (tundish visible or not) or onto a roof  
capable of withstanding high temperature discharges of  
water and 3m from any plastics guttering system that  
would collect such discharges (tundish visible.)  
G3 GUIDANCE SECTION 3.9  
Open drain cock  
The discharge pipe (D1) from the vessel up to and including  
tundish is generally supplied by the manufacturer of the hot  
water storage system. Where otherwise the installation should  
include the discharge pipe (s) (D1) from the safety device(s).  
In either case the tundish should be vertical located in the  
same space as the unvented hot water storage system and  
be fitted as close as possible and within 500mm of the safety  
device e.g the temperature relief valve.  
Open hot water tap nearest SCx unit.  
If water fails to drain from SCx unit, vent the system by  
If you need to site the SCx unit In the middle of the house your  
discharge pipe to the tundish can be as far away as 9m, which  
in most cases is enough to run the final discharge point. After 9m,  
increase the pipe size to a greater diameter than 22mm and  
accordingly for subsequent 9m lengths, see table 1 on page 10.  
opening the temperature pressure relief valve.  
iv) where a single pipe serves a number of discharges, such as  
in blocks of flats, the number served should be limited to not  
more than 6 systems so that any installation discharging can  
be traced reasonably easily. The single common discharge  
pipe should be at least one pipe size larger than the largest  
individual discharge pipe (D2) to be connected. If unvented  
hot water storage systems are installed where discharges  
from safety devices may not be apparent i.e. in dwellings  
occupied by blind, infirm or disabled people, consideration  
should be given to the installation of an electronically  
SCHEMATIC DISCHARGE  
PIPE ARRANGEMENT  
COMMISSIONINGTHE SCx UNIT  
The discharge pipe (D2) from the tundish should terminate in  
a safe place where there is no risk to persons in the vicinity of  
the discharge, preferably be of metal and:  
Switch on electricity to the immersion heater(s) (Direct system)  
or switch on the boiler (Indirect system). Refer to the boiler  
manufacturers instructions on commissioning.  
Fig.6  
a. be at least one pipe size larger than the nominal outlet size  
of the safety device unless it’s total equivalent hydraulic  
resistance exceeds that of a straight pipe 9m long ie.  
discharge pipes between 9m and 18m equivalent resistance  
length should be at least two sizes larger, than the nominal  
outlet size of the safety device between 18 and 27m, at least  
3 sizes larger and so on. Bends must be taken into account in  
calculating flow resistance. Refer to Table 1 overleaf and fig. 6.  
Bring the unit to its maximum temperature setting of approx.  
60 degrees Celsius. You should, on operating the water taps,  
have a good flow of hot and cold water assuming adequate  
water is supplied to the SCx unit.  
operated device to warn when discharge takes place.  
Note: The discharge will consist of scalding water and steam.  
Asphalt, roofing felt and non-metallic rainwater goods may be  
damaged by such discharges.  
Check the water does not discharge via the tundish pipework  
during heating.  
WORKED EXAMPLE OF DISCHARGE PIPE SIZING  
Recheck all fittings/joints for possible leaks.  
An alternative approach to sizing discharge pipes would  
be to follow BS 6700:1987 specification for design  
installation, testing and maintenance of services supplying  
water for domestic use within buildings and their curtilages,  
Appendix E, section E2 and table 21.  
The example below is for a G1/2 temperature relief valve with  
a discharge pipe (D2) having 4 No elbows and length of 7m  
from the tundish to the point of discharge.  
On completion of the installation, before turning on the mains  
water supply ensure that all residual materials are removed by  
means of flushing the system with a suitable cleaner.  
From table 1: (overleaf)  
EXTERNAL EXPANSIONVESSEL – OPTIONAL  
Maximum resistance allowed for a straight length of 22mm copper  
discharge pipe (D2) from G1/2 temperature relief valve is 9.0m  
b. have a vertical section of pipe at least 300mm long, below  
the tundish before any elbow or bends in the pipework.  
This smaller tank is connected to the cold-water inlet side of  
the vessel. Mount the tank according to separate manufacturers  
instructions provided with the External Expansion vessel.  
See fig 1 page 5.  
Subtract the resistance for 4 No 22mm elbows at  
0.8m each = 3.2m  
c. be installed with a continuous fall.  
DISCHARGE PIPEWORK  
Therefore the permitted length equates to 5.8m  
d. have discharges visible at both the tundish and the final  
point of discharge but where this is not possible or is  
practically difficult there should be clear visibility at one or  
other of these locations.  
It is a requirement of Building Regulations that any discharge  
from an unvented system is conveyed to where it is visible, but  
will not cause danger to persons in or about the building. The  
tundish and discharge pipes should be fitted in accordance  
with the requirements and guidance notes of Building  
Regulations. Building Regulation G3 Requirements and  
guidance section 3.9 reproduced in the following sections.  
5.8m is less than the actual length of 7m therefore calculate  
the next largest size.  
SCALE  
In hard water areas lower water temperatures can result in  
less scale being deposited.  
Maximum resistance allowed for a straight length of 28mm pipe  
(D2) from a G1/2 temperature relief valve equates to 18m  
If water softener is used it should be capable of flows of  
approx. 50 lt/min, this will maintain maximum performance  
of the SCx unit.  
Examples of acceptable discharge arrangements are:  
Subtract the resistance of 4 No 28mm elbows at  
1.0m each = 4.0m  
i) ideally below a fixed grating and above the water seal in  
a trapped gully.  
Therefore the maximum permitted length equates to 14m  
If no descaler or softener is used then the heating element(s)  
will need descaling periodically for maximum efficiency.  
Information Sheet No. 33 available from the British Board of  
Agreement gives further advice on discharge pipe installation.  
ii) downward discharges at low level; i.e. up to 100mm  
above the external surfaces such as car parks, hard  
As the actual length is 7m a 28mm (D2) copper pipe will  
be satisfactory.  
8
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimp-15278-SCx_Instructions 31/3/06 9:32 am Page 11  
TABLE 1 – SIZING OF COPPER DISCHARGE PIPE (D2) FOR COMMONT&P RELIEFVALVE SIZES  
MAINTENANCE  
Valve outlet Size  
Minimum size of  
discharge pipe D1  
Minimum size of  
discharge pipe D2  
from tundish  
Maximum resistance  
allowed, expressed as a  
length of straight pipe  
(i.e. no elbows or bends)  
Resistance created by  
each elbow or bend  
To keep the cylinder in good operating order the cylinder should be serviced once a year by a Dimplex service engineer.  
If water is seen dripping through the tundish, please contact your installer or Dimplex service agent.  
To receive the 25 year guarantee please complete and return the guarantee card within 30 days of purchase / install  
– please read Terms and Conditions on the guarantee card.  
G1/2  
G3/4  
G1  
15mm  
22mm  
28mm  
22mm  
28mm  
35mm  
28mm  
35mm  
42mm  
35mm  
42mm  
54mm  
up to 9m  
up to 18m  
up to 27m  
up to 9m  
up to 18m  
up to 27m  
up to 9m  
up to 18m  
up to 27m  
0.8m  
1.0m  
1.4m  
1.0m  
1.4m  
1.7m  
1.4m  
1.7m  
2.3m  
GUIDANCE INTHE EVENT OF A PROBLEM  
If you have a problem, in the first instance contact the plumber who fitted the unit. There after contact the plumber  
who carries out the annual servicing for you.  
Check current amps drawn by the heater, should be approx.  
15 amps. If heating element fails to operate, change the  
complete heating element assembly.  
PROBLEM SOLVING  
No water in tap from the SCx Unit  
Check that mains supply is on.  
Important. In the event of an over heat situation reset all  
thermal cutouts.  
Check that the line strainer is not blocked  
Check that the combination valve has been fitted so that the  
arrow on it faces in the direction of the water flow.  
If hot water discharges from Tundish  
If the water at the hot tap is cold  
WARNING: Do not turn the mains water supply off - switch off  
(1) power to immersion heaters (Direct) or (2) shut down  
heating boiler (Indirect)  
Boiler (indirect): Ensure that the boiler has been switched on  
and working correctly.  
If hot water discharges from the tundish on indirect models there  
could be a fault with the thermal cut out, cylinder thermostat or  
temperature pressure relief valve. On a direct model the fault  
could lie with the heating element thermostat. We recommend  
you call your installer or Dimplex Service Agent.  
Check that no air blocks have occurred in the primary system  
Check the following are all connected correctly  
Cylinder Stat  
Thermal cut out (Reset by pushing red button)  
Motorised valve  
SPARES  
Boiler thermostat (max setting 82 degrees Celsius)  
Boiler thermal cut out (if fitted)(Reset by pushing red button)  
Direct (Electric) Models  
When ordering replacement parts the serial number on the  
unit should be quoted.  
PART/COMPONENT REFERENCES  
WARNING: Isolate unit at main electric supply before opening  
heating element cover.  
Tundish 15mm to 22mm -  
Expansion Vessel Kit (12 Litre) -  
Expansion Vessel Kit (18 Litre) -  
Expansion Vessel Kit (25 Litre) -  
Motorised Valve -  
SC06006  
SC06001  
SC06002  
SC06003  
SC06007  
SC06009  
SC06005  
SC06008  
SC06004  
Ensure that power is available to the element from the electric  
mains and that the isolator is on. If there is power to the  
element and the element fails to operate check as follows:  
Check that the thermal cut out on the elements have not  
operated. If they have, reset by pressing the red button. If they  
cut out again as the water heats up the cylinder thermostat  
has failed and needs replacing. Fit a new thermostat and  
reset the thermal cut out.  
Immersion Heater -  
Temp/pressure Relief Valve -  
Twin Thermostat -  
Inlet valve assembly -  
WARNING: Should the factory fitted temperature and pressure  
relief valve be tampered with your guarantee will be  
invalidated. Neither the distributor nor manufacturer shall be  
responsible for any consequential damage howsoever caused.  
With power on and the thermal cut out reset check the output  
terminal on the thermostat. If the circuit cannot be  
completed, the thermostat and/or cut out needs replacing.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Coleman Camping Equipment 2000008491 User Manual
Continental Electric Toaster CE23551 User Manual
Crown Audio Microphone CM 311A User Manual
Crown Equipment Automobile SP 3500 Series User Manual
Cuisinart Fryer IB 9354A User Manual
Cypress Computer Hardware CY7C1006D User Manual
Dynex TV Mount DX TVM111 User Manual
Electro Voice Portable Speaker SL 15 2H User Manual
Gardena Water Pump T 380 User Manual
GE Dust Collector 1601 0149 A2 User Manual