17EX
Externally Geared Centrifugal Liquid Chillers
50/60 Hz
1500 to 2250 Nominal Tons (5280 to 7910 kW)
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design speci-
fications. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to equip-
ment and property or injury to personnel.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions
as well as those listed in this guide.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause dam-
age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply with ASHRAE-15 (latest edition). Con-
tact Carrier for further information on use of this chiller with other
refrigerants.
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while chiller
is under pressure or while chiller is running. Be sure pressure is at
0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in ac-
cordance with the latest edition of ASHRAE (American Society of
Heating, Refrigeration, and Air Conditioning Engineers) 15. The
accumulation of refrigerant in an enclosed space can displace oxy-
gen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregulari-
ties, unconsciousness, or death. Misuse can be fatal. Vapor is heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT install relief devices in series or backwards.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
RUN WATER PUMPS when removing, transferring, or charg-
ing refrigerant.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com-
ponents are light, use such equipment when there is a risk of slip-
ping or losing your balance.
DO NOT WELD OR FLAME CUT any refrigerant line or vessel
until all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali-
fied electrician.
DO NOT WORK ON electrical components, including control pan-
els, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-
state components.
BE AWARE that certain automatic start arrangements CAN EN-
GAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require-
ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without permission of your process con-
trol group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has
been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
LOCK OPENAND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized be-
fore resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
with soap and water. If any enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl-
inder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor-
rosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pres-
sure relief device to prevent a build-up of condensate or rain
water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 211
Catalog No. 531-721
Printed in U.S.A.
Form 17EX-1SS
Pg 1
7-97
Replaces: New
Tab 5d
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTENTS
Page
Page
Inspect Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Check Optional Pumpout Compressor Water
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Check Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Inspect Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
• CHECK INSULATION RESISTANCE
Prepare the Chiller for Start-Up . . . . . . . . . . . . . . . . . 62
Starting the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Check the Running System . . . . . . . . . . . . . . . . . . . . . 62
Stopping the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
After Limited Shutdown . . . . . . . . . . . . . . . . . . . . . . . . 63
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
After Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . 63
Cold Weather Operation . . . . . . . . . . . . . . . . . . . . . . . . 63
Manual Guide Vane Operation . . . . . . . . . . . . . . . . . . . 63
Refrigeration Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Motor Pre-Start Checks . . . . . . . . . . . . . . . . . . . . . . . . 51
External Gear Pre-Start Checks . . . . . . . . . . . . . . . . . 51
Carrier Comfort Network Interface . . . . . . . . . . . . . . . 53
Check Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
• MECHANICAL STARTERS
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63-67
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Operating the Optional Pumpout
• SOLID-STATE STARTERS
Compressor Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . 54
Power Up the Controls and
Check the Compressor Oil Heater . . . . . . . . . . . . . 54
• SOFTWARE VERSION
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
• READING REFRIGERANT PRESSURES
Set Up Chiller Control Configuration . . . . . . . . . . . . . 54
Input the Design Set Points . . . . . . . . . . . . . . . . . . . . . 54
Input the Local Occupied Schedule
Transferring Refrigerant into the
Economizer/Storage Vessel . . . . . . . . . . . . . . . . . . . 66
Transferring Refrigerant into
(OCCPC01S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Input Service Configurations . . . . . . . . . . . . . . . . . . . . 54
• PASSWORD
the Cooler/Condenser/Compressor Section . . . . . 67
Return Chiller to Normal Operating
Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• INPUT TIME AND DATE
GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . 67-75
Refrigerant Properties . . . . . . . . . . . . . . . . . . . . . . . . . 67
Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Removing Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . 67
Adjusting the Refrigerant Charge . . . . . . . . . . . . . . . . 67
Refrigerant Leak Testing . . . . . . . . . . . . . . . . . . . . . . . 67
Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Test After Service, Repair, or Major Leak . . . . . . . . . 67
• REFRIGERANT TRACER
• CHANGE LID CONFIGURATION IF NECESSARY
• MODIFY CONTROLLER IDENTIFICATION IF
NECESSARY
• INPUT EQUIPMENT SERVICE PARAMETERS IF
NECESSARY
• MODIFY EQUIPMENT CONFIGURATION IF
NECESSARY
• CHECK VOLTAGE SUPPLY
• PERFORM AN AUTOMATED CONTROL TEST
Check Pumpout System Controls and Optional
Pumpout Compressor . . . . . . . . . . . . . . . . . . . . . . . . 56
High Altitude Locations . . . . . . . . . . . . . . . . . . . . . . . . 57
Charge Refrigerant Into Chiller . . . . . . . . . . . . . . . . . . 57
• TRIMMING REFRIGERANT CHARGE
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test . . . . . . . . . . . . . . . . . . . . . . . 68
Checking Guide Vane Linkage . . . . . . . . . . . . . . . . . . 68
Contact Seal Maintenance . . . . . . . . . . . . . . . . . . . . . . 68
• SEAL DISASSEMBLY
INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . 57-62
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Manual Operation of the Guide Vanes . . . . . . . . . . . . 58
Dry Run to Test Start-Up Sequence . . . . . . . . . . . . . . 58
Check Motor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . 58
• INITIAL MOTOR START-UP
• SEAL REASSEMBLY
Chiller Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
• ALIGNMENT METHODS
• PRELIMINARY ALIGNMENT
• NEAR FINAL ALIGNMENT
• FINAL ALIGNMENT
Disc Coupling Installation and Alignment . . . . . . . . . 59
• IMPORTANT INFORMATION
• HOT ALIGNMENT CHECK
• DOWELING
Check Oil Pressure and Compressor Stop . . . . . . . . 61
Calibrate Motor Current Demand Setting . . . . . . . . . . 61
To Prevent Accidental Start-Up . . . . . . . . . . . . . . . . . . 61
Hot Alignment Check . . . . . . . . . . . . . . . . . . . . . . . . . 61
Doweling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Check Chiller Operating Condition . . . . . . . . . . . . . . . 61
Instruct the Operator . . . . . . . . . . . . . . . . . . . . . . . . . . 62
• COOLER-CONDENSER
WEEKLY MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . 76
Check the Lubrication System . . . . . . . . . . . . . . . . . . 76
SCHEDULED MAINTENANCE . . . . . . . . . . . . . . . . . . 76-83
Service Ontime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Inspect the Control Center . . . . . . . . . . . . . . . . . . . . . 76
Check Safety and Operating Controls Monthly . . . . . 76
Changing the Oil Filters . . . . . . . . . . . . . . . . . . . . . . . . 76
• COMPRESSOR OIL FILTER
• ECONOMIZER/STORAGE VESSEL
• PUMPOUT SYSTEM
• EXTERNAL GEAR OIL FILTER
• COMPRESSOR ASSEMBLY
Oil Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Oil Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
• COMPRESSOR OIL
• COMPRESSOR LUBRICATION SYSTEM
EXTERNAL GEAR LUBRICATION SYSTEM
• CONTROL SYSTEM
• EXTERNAL GEAR OIL
• MOTOR SLEEVE BEARING AND PUMPOUT
COMPRESSOR OIL
• AUXILIARY EQUIPMENT
• CHILLER CYCLES
• MAINTENANCE
Inspect Refrigerant Float System . . . . . . . . . . . . . . . . 78
Inspect Relief Valves and Piping . . . . . . . . . . . . . . . . 78
Coupling Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 78
Motor Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
• CLEANLINESS
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• THIS MANUAL
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . 62,63
Operator Duties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
• SLEEVE BEARINGS
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTENTS (cont)
Page
Page
Motor Handling/Rigging . . . . . . . . . . . . . . . . . . . . . . . . 81
Motor Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
External Gear Storage . . . . . . . . . . . . . . . . . . . . . . . . . 81
• SHORT-TERM STORAGE (Indoors)
Checking Pressure Transducers . . . . . . . . . . . . . . . . 84
• OIL DIFFERENTIAL PRESSURE/POWER SUPPLY
MODULE CALIBRATION
• TROUBLESHOOTING TRANSDUCERS
• TRANSDUCER REPLACEMENT
• LONG-TERM STORAGE (Indoors)
Control Algorithms Checkout Procedure . . . . . . . . . 85
Control Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
• RED LEDs
• EXTENDED DOWNTIME
Compressor Bearing Maintenance . . . . . . . . . . . . . . . 82
External Gear Maintenance . . . . . . . . . . . . . . . . . . . . . 82
Inspect the Heat Exchanger Tubes . . . . . . . . . . . . . . . 82
• COOLER
• GREEN LEDs
Notes on Module Operation . . . . . . . . . . . . . . . . . . . . 96
Processor/Sensor Input/Output Module (PSIO) . . . . 97
• INPUTS
• CONDENSER
Water Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Inspect the Starting Equipment . . . . . . . . . . . . . . . . . 83
Check Pressure Transducers . . . . . . . . . . . . . . . . . . . 83
Pumpout System Maintenance . . . . . . . . . . . . . . . . . . 83
• OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE
• PUMPOUT SAFETY CONTROL SETTINGS
Ordering Replacement Chiller Parts . . . . . . . . . . . . . . 83
• MOTOR REPLACEMENT PARTS
• OUTPUTS
Starter Management Module (SMM) . . . . . . . . . . . . . . 97
• INPUTS
• OUTPUTS
Options Modules (8-Input) . . . . . . . . . . . . . . . . . . . . . 98
Four-In/Two-Out Module . . . . . . . . . . . . . . . . . . . . . . . 98
• INPUTS
• OUTPUTS
• EXTERNAL GEAR REPLACEMENT PARTS
Replacing Defective Processor Modules . . . . . . . . . 98
• INSTALLATION OF NEW PSIO MODULE
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . 83-99
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Checking the Display Messages . . . . . . . . . . . . . . . . . 84
Checking Temperature Sensors . . . . . . . . . . . . . . . . . 84
• RESISTANCE CHECK
PHYSICAL DATA AND WIRING SCHEMATICS . . . . 99-114
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115-120
• VOLTAGE DROP
INITIAL START-UP CHECKLIST FOR 17EX
EXTERNALLY GEARED CENTRIFUGAL LIQUID
CHILLER . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1 to CL-12
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
4
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
17EX CHILLER FAMILIARIZATION
Chiller Identification Label (Fig. 1) — The iden-
tification label is located on the right side of the chiller con-
trol center panel. The label contains information on model
number, refrigerant charge, rated voltage, etc.
Before initial start-up of the 17EX unit, those involved in
the start-up, operation, and maintenance should be thor-
oughly familiar with these instructions and other necessary
job data. This book is outlined so that you may become fa-
miliar with the control system before performing start-up pro-
cedures. Procedures in this manual are arranged in the se-
quence required for proper chiller start-up and
operation.
System Components (Fig. 2) — The components
include the cooler and condenser heat exchangers in sepa-
rate vessels, compressor, compressor and gear lubrication pack-
ages, control center, speed increaser economizer/storage vessel,
motor, and starter. The compressor drive consists of an ex-
ternal gear (speed increaser) and an electric motor. All con-
nections from pressure vessels have external threads to en-
able each component to be pressure tested with a threaded
pipe cap during factory assembly.
This unit uses a microprocessor controlled system. Do
not short or jumper between terminations on circuit boards
or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or mod-
ule connections. Always touch a chassis (grounded) part
to dissipate body electrostatic charge before working in-
side the control center.
Cooler — This vessel (also known as the evaporator) is
located underneath the condenser, next to the economizer/
storage vessel. The cooler is maintained at lower tempera-
ture and pressure so that evaporating refrigerant can remove
heat from water flowing through its internal tubes.
Use extreme care when handling tools near boards and
when connecting or disconnecting terminal plugs.
Circuit boards can easily be damaged. Always hold boards
by the edges and avoid touching components and
connections.
Condenser — The condenser operates at a higher tem-
perature and pressure than the cooler and has water flowing
through its internal tubes in order to remove heat from the
refrigerant.
Compressor — This component maintains system tem-
perature and pressure differences and moves the heat-
carrying refrigerant from the cooler to the condenser.
This equipment uses, and can radiate, radio frequency
energy. If not installed and used in accordance with
the instruction manual, it may cause interference to
radio communications. It has been tested and found to
comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which
are designed to provide reasonable protection against such
interference when operated in a commercial environ-
ment. Operation of this equipment in a residential area
is likely to cause interference, in which case the user, at
his own expense, will be required to take whatever mea-
sures may be required to correct the interference.
Control Center — The control center is the user inter-
face for controlling the chiller and regulates the chiller ca-
pacity as required to maintain proper leaving chilled
water temperature. The control center:
• registers cooler, condenser, and lubricating system
pressures
• shows chiller operating and alarm shutdown conditions
• records the total chiller operating hours and how many hours
the chiller has been running
• sequences chiller start, stop, and recycle under micro-
processor control
• provides access to other CCN (Carrier Comfort Network)
devices
Always store and transport replacement or defective boards
in anti-static shipping bag.
ABBREVIATIONS
Motor Starter (Purchased Separately) — The starter
allows the proper start and disconnect of electrical energy
for the compressor-motor, oil pump, oil heater, and control
panels.
Frequently used abbreviations in this manual include:
CCN
— Carrier Comfort Network
CCW — Counterclockwise
CHW — Chilled Water
Economizer/Storage Vessel — During normal op-
eration, this vessel functions as an economizer, returning flash
gas to the second stage of the compressor and increasing the
efficiency of the refrigeration cycle. During periods of shut-
down and service, the economizer/storage vessel can serve
as a storage tank for the refrigerant.
CHWR — Chilled Water Return
CHWS — Chilled Water Supply
CW
— Clockwise
ECW — Entering Chilled Water
ECDW — Entering Condenser Water
EMS — Energy Management System
HGBP — Hot Gas Bypass
I/O — Input/Output
LCD — Liquid Crystal Display
LCDW — Leaving Condenser Water
LCW — Leaving Chilled Water
LED — Light-Emitting Diode
LID — Local Interface Device
OLTA — Overload Trip Amps
PIC — Product Integrated Control
PSIO — Processor Sensor Input/
Output Module
— Rated Load Amps
— Silicon Control Rectifier
SMM — Starter Management Module
TXV — Thermostatic Expansion Valve
REFRIGERATION CYCLE (Fig. 3)
The 17EX chiller can be used to chill either water or brine.
The data in this book applies to either application. Appli-
cations using corrosive brines may require using special tubes,
tubesheet, and waterbox materials which are special order
items.
RLA
SCR
5
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
NIH
—
Nozzle-In-Head
*Any available cooler size can be combined with any available condenser size.
NOTE: For details on motor size designations, see below.
ASME
‘U’ STAMP
ARI (Air Conditioning
and Refrigeration
Institute)
PERFORMANCE
CERTIFIED
(60 Hz Only)
Fig. 1 — Model Number Identification
6
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
40
39
38
37
36
35
15
33
34
27
20
19
31
30
28
25
29
23 22 21
18 17
32
26
24
16
LEGEND
1
2
—
Condenser
Cooler Suction Pipe
22
—
Oil Drain and Charging Valve
Oil Heater (Hidden)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
23
24
25
26
27
—
—
—
—
—
3
Compressor Suction Elbow
Guide Vane Actuator
Compressor Oil Pump
4
Compressor Oil Cooler/Filter
5
Condenser Discharge Pipe
Compressor Discharge Elbow
Two-Stage Compressor
Local Interface Display Control Panel
Cooler Relief Valves (Behind Compressor,
Hidden)
6
7
8
Economizer Gas Line to Compressor
Compressor Housing Access Cover
High-Speed Coupling (Hidden)
External Gear (Speed Increaser)
Low-Speed Coupling (Hidden)
Open-Drive Compressor Motor
Compressor Motor Terminal Box
Low-Side Float Box Cover
Gear Oil Pump
28
29
30
31
32
33
34
35
36
37
38
—
—
—
—
—
—
—
—
—
—
—
Economizer Storage Vessel
Economizer/Storage Vessel Relief Valves
Pumpout Unit
9
10
11
12
13
14
15
16
17
18
19
20
21
Cooler
High Side Float Box Cover
Cooler Waterbox Drain
Take-Apart Connections
Cooler Marine Waterbox
Cooler Waterbox Vent
Gear Oil Cooler/Filter
Condenser Waterbox Drain
Refrigerant Liquid Line to Economizer/
Storage Vessel
Condenser Marine Waterbox
Condenser Waterbox Vent
Refrigerant Charging/Service Valve
Refrigerant Liquid Line to Cooler
Power Panel
39
40
—
—
Oil Level Sight Glasses (2)
17EX WITH EXTERNAL GEAR (SPEED INCREASER)
Fig. 2 — Typical 17EX Chiller Components
7
Download from Www.Somanuals.com. All Manuals Search And Download.
The chiller compressor continuously draws large quanti-
ties of refrigerant vapor from the cooler at a rate determined
by the amount of guide vane opening. This compressor suc-
tion reduces the pressure within the cooler, allowing the liq-
uid refrigerant to boil vigorously at a fairly low temperature
(typically 38 to 42 F [3 to 6 C]).
The liquid refrigerant obtains the energy needed to va-
porize by removing heat from the water or brine in the cooler
tubes. The cold water or brine can then be used in air con-
ditioning and/or other processes.
After removing heat from the water or brine, the refrig-
erant vapor enters the first stage of the compressor, is
compressed, and flows into the compressor second stage. Here
it is mixed with flash-economizer gas and is further
compressed.
Compression raises the refrigerant temperature above
that of the water flowing through the condenser tubes.
When the warm (typically 98 to 102 F [37 to 40 C]) refrig-
erant vapor comes into contact with the condenser tubes, the
relatively cool condensing water (typically 85 to 95 F
[29 to 35 C]) removes some of the heat, and the vapor con-
denses into a liquid.
External Gear Oil Cooling — The external gear oil
is also water cooled. Water flow through the gear oil cooler
is manually adjusted by a plug valve to maintain an oper-
ating temperature of approximately 130 F (54 C). If so equipped,
an oil heater in the reservoir helps to maintain the oil tem-
perature under cold ambient operating conditions. The heater
is controlled by an internal thermostat.
LUBRICATION CYCLE
Compressor Lubrication Cycle (Refer to item
numbers shown in Fig. 4) — The compressor oil
pump and oil reservoir are contained in the compressor base.
Oil is pumped through an oil cooler and filter to remove heat
and any foreign particles. A portion of the oil is then di-
rected to the shaft-end bearing and the shaft seal. The bal-
ance of the oil lubricates the thrust and journal bearings and
the thrust end seal. The bearing and transmission oil returns
directly to the reservoir to complete the cycle. Contact-seal
oil leakage, however, is collected in an atmospheric float cham-
ber to be pumped back to the main reservoir as the oil
accumulates.
Oil may be charged into the compressor oil reservoir
(Item 8) through a charging valve (Item 6) which also func-
tions as an oil drain. If there is refrigerant in the chiller, how-
ever, a hand pump will be required for charging at this
connection.
An oil-charging elbow (Item 3) on the seal-oil return cham-
ber allows oil to be added without pumping. The seal-oil re-
turn pump (Item 4) automatically transfers the oil to the main
reservoir. Sight glasses (11) on the reservoir wall permit ob-
servation of the oil level.
A motor-driven oil pump (Item 10) discharges oil to an oil
cooler/filter (Item 16) at a rate and pressure controlled by an
oil regulator (Item 10). The differential oil pressure (bearing
supply versus oil reservoir) is registered on the control panel.
Water flow through the oil cooler is manually adjusted by
a plug valve (Item 17) to maintain the oil at an operating
temperature of approximately 145 F (63 C). During shut-
down, the oil temperature is also maintained at 150 to
160 F (65 to 71 C) by an immersion heater (Item 7) in order
to minimize absorption of refrigerant by the oil.
The liquid refrigerant passes through an orifice into the
FLASC chamber. The coolest condenser water flows through
the FLASC and allows a lower saturated temperature and
pressure. Part of the entering liquid refrigerant will flash to
vapor once it has passed through the FLASC orifice, thereby
cooling the remaining liquid. The vapor is then recondensed
by the condenser water flowing through the FLASC
chamber.
The subcooled liquid refrigerant drains into a high-side
valve chamber that meters the refrigerant liquid into a flash
economizer chamber. Pressure in this chamber is interme-
diate between condenser and cooler pressures. At this lower
pressure, some of the liquid refrigerant flashes to gas, fur-
ther cooling the remaining liquid. The flash gas, having ab-
sorbed heat, is returned directly to the compressor second
stage. Here it is mixed with discharge gas that is already com-
pressed by the first-stage impeller. Since the flash gas has to
pass through only half the compression cycle to reach con-
denser pressure, there is a savings in power.
The cooled liquid refrigerant in the economizer is me-
tered through the low-side valve chamber, reducing the re-
frigerant pressure. Pressure in the cooler is lower than in the
economizer. Some of the liquid flashes as it passes through
the low side float valve. The cycle is now complete.
Upon leaving the cooler section of the oil cooler/filter, the
oil is filtered (Item 15) and a portion is directed to the seal-
end bearing (Item 1) and the shaft seal (Item 2). The remain-
der lubricates thrust (Item 14) and journal bearings (Item 12).
Thrust bearing temperature is indicated on the PIC controls.
Oil from both circuits returns by gravity to the reservoir.
OIL COOLING CYCLE
The shaft seal of the open compressor drive must be kept
full of lubrication oil, even when the chiller is not operating,
to prevent loss of refrigerant.
If the chiller is not operating and the oil pump has not
operated during the last 12 hours, the control system auto-
matically runs the oil pump for one minute in order to keep
the contact seal filled with oil.
Compressor Oil Cooling — The compressor oil is
water cooled. Water flow through the oil cooler is manually
adjusted by a plug valve to maintain an operating tempera-
ture at the reservoir of approximately 145 F (63 C). An oil
heater in the reservoir helps to prevent oil from being di-
luted by the refrigerant. The heater is controlled by the PIC
(Product Integrated Control) and is energized when the oil
temperature is outside the operating temperature range of 150
to 160 F (66 to 71 C).
IMPORTANT: If the control power is to be deener-
gized for more than one day, the chiller refrigerant should
be pumped over to the economizer/storage vessel.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
TXV
—
Thermostatic Expansion Valve
Liquid
Liquid/Vapor
Vapor
*The FX compressor and the gear have a water cooled oil cooler.
Fig. 3 — Refrigeration, Cycle
Upon leaving the cooler section (Item 13) of the oil cooler/
filter, the oil is filtered (Item 11) and is directed to the pres-
sure control valve (Item 7). Before entering the pressure control
valve, the oil pressure (Item 16) and temperature (Item 8)
are monitored by the PIC.
A portion of the oil then lubricates the gear bearings
(Item 2). Another portion is directed through an orifice
(Item 5) to the gear mesh spray (Item 3) to lubricate the gear
mesh (Item 1) during operation. Oil from both circuits re-
turns by gravity to the reservoir.
External Gear Lubrication Cycle (Refer to Item
numbers shown in Fig. 5) — Oil reservoir is con-
tained in the gear base. The external gear oil pump is mounted
below the gear with the cooler/filter. Oil is pumped through
an oil cooler/filter to remove heat and any foreign particles.
A portion of the oil is directed to the gear bearings and gear
mesh spray. The remainder is bypassed to the sump. The bear-
ing and transmission oil returns directly to the reservoir to
complete the cycle.
Oil may be charged into the external gear oil reservoir as
described in the section, External Gear Pre-Start Checks,
page 51. Observe the oil level in the oil level glass (Item 4)
on the reservoir wall.
A motor driven oil pump (Item 10) discharges oil to the
oil cooler/filter (Item 12). The pump has an internal pressure
regulator to protect the pump in the event of an obstruction
downstream. Water flow through the oil cooler is manually
adjusted by a plug valve (Item 14) to maintain the oil at an
operating temperature of approximately 130 F (54 C).
STARTERS
All starters, whether supplied by Carrier or the customer,
must meet Carrier Starter Specification Z-375. This speci-
fication can be obtained from a Carrier Sales Representa-
tive. The purpose of this specification is to ensure the com-
patibility of the starter and the chiller. Many styles of compatible
starters are available, including solid-state , auto-transformer,
full-voltage, and, in the case of low-voltage main power sup-
ply, wye-delta closed transition.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
SHAFT DISPLACEMENT
& BRG TEMP. CUTOUT
CONNECTIONS
1
SEAL-END
BEARING
COAST DOWN
RESERVOIRS
13
COMPRESSOR OIL
PRESSURE LEAVING
FILTER LINE
2
12
SHAFT
SEAL
JOURNAL
BEARING
14
THRUST
BEARING
CHECK VALVE
15
OIL FILTER
16
OIL COOLER/
FILTER
TO PIC
CONTROLLER
17
3
8
PLUG VALVE
OIL CHARGING
ELBOW
MAIN OIL
RESERVOIR
4
11
PUMP, SEAL
OIL RETURN
SIGHT
GLASSES
TO POWER
PANEL
10
5
6
7
9
OIL
OIL
DRAIN &
CHARGING VALVE
COMPRESSOR OIL
SUCTION PRESSURE
OIL PUMP
& PRESS. REGULATOR
THERMISTOR
HEATER
Fig. 4 — 17EX Compressor Lubrication Cycle
10
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
3
4
5
6
—
—
—
—
—
—
Gear Mesh
8
9
10
11
12
13
14
—
—
—
—
—
—
—
Oil Supply Temperature Thermistor
Oil Pump Motor
Bearings
Gear Mesh Spray
Oil Level Glass
Orifice
Oil Supply Pressure
Transducer
Pressure Control Valve
Oil Pump and Pressure Regulator
Oil Filter
Oil Cooler/Filter
Oil Cooler
Plug Valve
7
—
NOTE: The oil reservoir is at the base of the gear box.
Fig. 5 — External Gear Oil Lubrication Cycle (Plan View)
CONTROLS General — The 17EX externally geared open-drive cen-
trifugal liquid chiller contains a microprocessor-based con-
trol center that monitors and controls all operations of the
chiller. The microprocessor control system matches the cool-
ing capacity of the chiller to the cooling load while provid-
ing state-of-the-art chiller protection. The system controls
cooling load within the set point plus the deadband by sens-
ing the leaving chilled water or brine temperature and regu-
lating the inlet guide vane via a mechanically linked actua-
tor motor. The guide vane is a variable flow prewhirl assembly
that controls the refrigeration effect in the cooler by regu-
lating the amount of refrigerant vapor flow into the com-
pressor. An increase in guide vane opening increases capac-
ity. Adecrease in guide vane opening decreases capacity. Chiller
protection is provided by the processor which monitors the
digital and analog inputs and executes capacity overrides or
safety shutdowns, if required.
Definitions
ANALOG SIGNAL — An analog signal varies in propor-
tion to the monitored source. It quantifies values between
operating limits. (Example: A temperature sensor is an ana-
log device because its resistance changes in proportion to
the temperature, generating many values.)
DIGITAL SIGNAL — A digital (discrete) signal is a 2-position
representation of the value of a monitored source.
(Example: A switch is a digital device because it only in-
dicates whether a value is above or below a set point or bound-
ary by generating an on/off, high/low, or open/closed signal.)
VOLATILE MEMORY — Volatile memory is memory in-
capable of being sustained if power is lost and subsequently
restored.
The memories of the PSIO and LID modules are vola-
tile. If the battery in a module is removed or damaged,
all programming will be lost.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
• power panel
PIC System Components — The Product Integrated
Control (PIC) is the control system on the chiller. See
Table 1. The PIC controls the operation of the chiller by moni-
toring all operating conditions. The PIC can diagnose a prob-
lem and let the operator know what the problem is and what
to check. It promptly positions the guide vanes to maintain
leaving chilled water temperature. It can interface with aux-
iliary equipment such as pumps and cooling tower fans to
turn them on only when required. It continually checks all
safeties to prevent any unsafe operating condition. It also
regulates the oil heater while the compressor is off and the
hot gas bypass valve, if installed. See Fig. 6-10 for the lo-
cations of sensors, transducers, and other devices controlled
and/or monitored by the PIC system.
— 115 v control voltage
— up to 600 v for oil pump power
• starter cabinet
— chiller power wiring (per job requirement)
Table 1 — Major PIC Components and
Panel Locations*
PANEL
PIC COMPONENT
LOCATION
Processor Sensor Input/Output Module
(PSIO)
Starter Management Module (SMM)
Local Interface Device (LID)
6-Pack Relay Board
8-Input Modules (Optional)
4-In/2-Out Module
Oil Differential Pressure/Power Supply
Module
Control Center
Starter Cabinet
Control Center
Control Center
Control Center
Power Panel
The PIC can be interfaced with the Carrier Comfort
Network (CCN) if desired. It can communicate with other
PIC-equipped chillers and other CCN devices.
Control Center
Oil Heater Contactor (1C)
Compressor Oil Pump Contactor (2C)
Gear Oil Pump Contactor (5C)
Hot Gas Bypass Relay (3C) (Optional)
Control Transformers (T1-T4)
Power Panel
Power Panel
Power Panel
Power Panel
Power Panel
The PIC consists of 4 modules housed inside one of 3 lo-
cations: the control center, the power panel, or the starter
cabinet. The component names and the control voltage of
each location are listed below (also see Table 1):
• control center
— all extra low-voltage wiring (24 v or less)
Control and Oil Heater Voltage Selector (S1) Power Panel
Temperature Sensors
Pressure Transducers
See Fig. 7
See Fig. 7
*See Fig. 6-10.
REAR
LEGEND
1
2
—
—
Gear Oil Pressure Sensor
6
—
Compressor Oil Cooler
11
12
—
—
Motor Water Cooling Leak Detector
Cable (TEWAC Motor Only)
Thrust Bearing Temperature and
Impeller Displacement Cable
Discharge Temperature Sensor
Guide Vane Conduit and Cable
High Pressure Cutout Switch
Solenoid Conduit
7
8
—
—
—
—
Oil Heater Conduit
Discharge Oil Pressure Sensor
3
4
5
—
—
—
Motor Space Heater Conduit
Gear Oil Temperature Sensor
Motor High Temperature Switch Cable
TEWAC — Totally Enclosed Water-to-Air Cooled
9
10
Fig. 6 — 17EX Controls and Sensor Locations
12
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
13
14
—
—
Condenser Pressure Transducer
Condenser Entering Water
Temperature Sensor
17
18
19
20
—
—
—
—
Oil Pump Conduit
Oil Pump Sensor
PIC Control Panel
15
16
—
—
Condenser Entering and Leaving Water
Temperature Cable
Condenser Leaving Water
Temperature Sensor
Gear Oil Cooler Solenoid Cond
Oil Suction Pressure Sensor
21
—
LEGEND
22
23
24
25
26
—
—
—
—
—
Cooler Temperature Cable
Cooler Leaving Water Temperature Sensor
Cooler Entering Water Temperature Sensor
Cooler Pressure Sensor
Refrigerant Charging Valve
Fig. 6 — 17EX Controls and Sensor Locations (cont)
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 6 — 17EX Controls and Sensor Locations (cont)
Fig. 7 — Control Sensors (Temperature)
Fig. 8 — Control Sensors
(Pressure Transducer, Typical)
LEGEND
LID
—
—
—
Local Interface Device
Product Integrated Controls
Processor Sensor Input/Output Module
PIC
PSIO
1
—
Optional 8-Input Module for Spare Inputs to Control
Interface (One of Two Available)
PSIO
2
3
4
5
6
7
—
—
—
—
—
—
LID Input/Output Interface Panel Display
Oil Differential Pressure/Power Supply Module (Hidden)
LID Light (Hidden)
6-Pack Relay Board
Circuit Breakers (4)
Fig. 9 — Control Center (Front View);
Shown with Options Module
14
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
EQUIP GND
GRD
—
Equipment Ground
—
—
—
Ground
M
Motor
TEWAC
Totally Enclosed Water-to-
Air Cooled
Fig. 10 — 17EX Chiller Power Panel and Controls Connections
Download from Www.Somanuals.com. All Manuals Search And Download.
PROCESSOR/SENSOR INPUT/OUTPUT MODULE (PSIO)
— This module contains all the operating software needed
to control the chiller. The 17EX uses 5 pressure transducers
and 8 thermistors to sense pressures and temperatures. These
inputs are connected to the PSIO module. The PSIO also
provides outputs to the guide vane actuator, compressor and
gear oil pumps, oil heater, hot gas bypass (optional), and alarm
contact. The PSIO communicates with the LID, the SMM,
and the optional 8-input modules for user interface and starter
management.
incoming control voltage to either 21 vac power for the PSIO
module and options modules, or 24 vac power for 3 power
panel contactor relays and a control solenoid valve.
CONTROL AND OIL HEATER VOLTAGE SELECTOR
(S1) — It is necessary to use 115 v incoming control power
in the power panel. The switch must be set to the 115-v
position.
OIL DIFFERENTIAL PRESSURE/POWER SUPPLY
MODULE — This module, which is located in the control
center, provides 5 vdc power for the transducers and LID
backlight. This module outputs the difference between two
pressure transducer input signals. The module subtracts oil
supply pressure from transmission sump pressure and out-
puts the difference as an oil differential pressure signal to the
PSIO. The PSIO converts this signal to differential oil pres-
sure. To calibrate this reading, refer to the Troubleshooting,
Checking Pressure Transducers section on page 84.
STARTER MANAGEMENT MODULE (SMM) — This mod-
ule is located within the starter cabinet. This module ini-
tiates PSIO commands for starter functions such as start/
stop of the compressor; start/stop of the condenser and chilled
water pumps; start/stop of the tower fan, spare alarm con-
tacts, and the shunt trip. The SMM monitors starter inputs
such as flow switches, line voltage, remote start contact, spare
safety, condenser high pressure, oil pump interlock, motor
current signal, starter 1M and run contacts, and the kW trans-
ducer input (optional). The SMM contains logic capable of
safely shutting down the chiller if communication with
the PSIO is lost.
LID Operation and Menus (Fig. 11-17)
GENERAL
• The LID display automatically reverts to the default screen
(Fig. 11) after 15 minutes if no softkey activity takes place
and if the chiller is not in PUMPDOWN mode
• When not displaying the default screen, the upper right-
hand corner of the LID displays the name of the screen
that you have entered (Fig. 12).
• The LID may be configured in English or SI units, through
the LID configuration screen.
• Local Operation — Pressing the LOCAL softkey places
LOCAL INTERFACE DEVICE (LID) — The LID is mounted
to the control center and allows the operator to interface with
the PSIO or other CCN devices. It is the input center for all
local chiller set points, schedules, set-up functions, and op-
tions. The LID has a STOP button, an alarm light, 4 buttons
for logic inputs, and a display. The function of the 4 buttons
or ‘‘softkeys’’ are menu driven and are shown on the display
directly above the key.
SIX-PACK RELAY BOARD (6-Pack Relay Board) — This
device is a cluster of 6 pilot relays located in the control
center. It is energized by the PSIO for the compressor oil
pump, oil heater, alarm, optional hot gas bypass relay, aux-
iliary oil pump.
the PIC in LOCAL operation mode, and the control ac-
cepts modification to programming from the LID only. The
PIC uses the Local Time Schedule to determine chiller start
and stop times.
• CCN Operation — Pressing the CCN softkey places the
EIGHT-INPUT (8-Input) MODULES — One optional mod-
ule is factory installed in the control center panel when or-
dered. There can be up to 2 of these modules per chiller with
8 spare inputs each. They are used whenever chilled water
reset, demand reset, or reading a spare sensor is required.
The sensors or 4 to 20 mA signals are field-installed.
PIC in the CCN operation mode, and the control accepts
modifications from any CCN interface or module (with the
proper authority), as well as the LID. The PIC uses the
CCN time schedule to determine start and stop times.
The spare temperature sensors must have the same
temperature/resistance curve as the other temperature sen-
sors on this unit. These sensors are rated 5,000 ohm at 75 F
(25 C).
FOUR-IN/TWO-OUT (4-IN/2-OUT) MODULE — This mod-
ule monitors and controls the external gear lubrication sys-
tem. It energizes the gear oil pump and is located in the power
panel.
OIL HEATER CONTACTOR (1C) — This contactor is lo-
cated in the power panel and operates the heater at 115 v. It
is controlled by the PIC to maintain oil temperature during
chiller shutdown.
COMPRESSOR OIL PUMP CONTACTOR (2C)AND GEAR
OIL PUMP CONTACTOR (5C) — These contactors are lo-
cated in the power panel. They operate all 200 to 575-v oil
pumps. The PIC energizes the contactor to turn on the oil
pumps as necessary.
HOT GAS BYPASS CONTACTOR RELAY (3C)
(Optional) — This relay, located in the power panel, con-
trols the opening of the hot gas bypass valve. The PIC en-
ergizes the relay during low load, high lift conditions.
OIL AUXILIARY RELAY (4C) — This relay opens the oil
cooler solenoid valve and interlocks the oil pump with the
compressor (special order).
CONTROL TRANSFORMERS (T1-T4) — These trans-
formers are located in the power panel and convert
Fig. 11 — LID Default Screen
ALARMS AND ALERTS — An alarm (*) or alert (!) status
is indicated on the default screen and the status tables. An
alarm (*) shuts down the compressor. An alert (!) notifies
the operator that an unusual condition has occurred. The chiller
continues to operate when an alert is shown.
Alarms are indicated when the control center alarm light
(!) flashes. The primary alarm message is viewed on the de-
fault screen and an additional, secondary, message and
troubleshooting information are sent to the ALARM HIS-
TORY table.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
• Press NEXT or PREVIOUS to highlight the desired
entry
NOTE: When an alarm is detected, the LID default screen
freezes (stops updating) at the time of alarm. The freeze en-
ables the operator to view the chiller conditions at the time
of the alarm. The status tables show the updated informa-
tion. Once all alarms have been cleared (by pressing the
RESET softkey), the default LID screen returns to normal
operation.
• PresStsig
• Press QUIT to leave the selected decision or field with-
out sving ny changes.
• Or, press ENTER to leave the selected decision or field
and save changes.
Fig. 12 — LID Service Screen
LID DEFAULT SCREEN MENU ITEMS — To perform
any of the operations described below, the PIC must be pow-
ered up and have successfully completed its self test.
TO VIEW OR CHANGE POINT STATUS (Fig. 13) — Point
Status is the actual value of all of the temperatures, pres-
sures, relays, and actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS to view the list of
Point Status tables.
The default screen menu selection offers four options
(STATUS, SCHEDULE, SETPOINT, and SERVICE). The
STATUS menu allows viewing and limited calibration/
modification of control points and sensors, relays and con-
tacts, and the options board. The SCHEDULE menu allows
viewing and modification of the Local Control, CCN Con-
trol, and Ice Build time schedules. Numerous set points in-
cluding Base Demand Limit, LCW, ECW, and Ice Build can
be adjusted under the SETPOINT menu. The SERVICE menu
can be used to revise alarm history, control test, control al-
gorithm status, equipment configuration, equipment service,
time and date, attach to network, log out of device, control-
ler identification, and LID configurations. Figures 15 and 16
provide additional information on the menu structure.
2. Press NEXT or PREVIOUS to highlight the desired
status table. The list of tables is:
• STATUS01 — Status of control points and sensors
• STATUS02 — Status of relays and contacts
• STATUS03 — Status of both optional 8-input modules
and sensors
Press the MENU softkey to select from the 4 options.
To view or change parameters within any menu structure,
use the SELECT softkey to choose the desired table or
• STATUS04 — Gear oil temperature and pressure
item. The softkey modification choices displayed will de-
pend on whether the selected item is a discrete point, ana-
log point, or an override point. Press the softkey that cor-
responds to your configuration selection or press the
QUIT softkey. If the QUIT softkey is depressed, the
configuration will not be modified. Use the following soft-
keys to access and select the desired section.
MENU STRUCTURE — To perform any of the operations
described below, the PIC must be powered up and have suc-
cessfully completed its self test.
• Press MENU to select from the four available options.
• Press the softkey that corresponds to the desired menu
structure.
Fig. 13 — Example of Point Status Screen
(Status01)
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Override Indication — An override value is indicated by
‘‘SUPVSR,’’‘‘SERVC,’’or ‘‘BEST’’flashing next to the point
value on the Status table.
3. Pre
TO VIEW OR CHANGE TIME SCHEDULE OPERATION
(Fig. 14)
4. On the Point Status table press NEXT or
PRIS isit
1. On the Menu screen, press SCHEDULE .
2. Press NEXT or PREVIOUS to highlight one of the
following schedules.
For Discrete Points — Press START or STOP ,
YES or NO , ON or OFF , etc. to select the desired
state.
OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03-99S — CCN Time Schedule (Actual
number is defined in CONFIG table.)
For Analog Points
—
Press INCREASE or
DECREASE to select the desired value.
3. Press SELECT to access and view the time schedule.
5. Press ENTER to register new value.
4. Press NEXT or PREVIOUS to highlight the de-
sir
OVERRIDE OPERATIONS
NOTE: When overriding or changing metric values, it is nec-
essary to hold the softkey down for a few seconds in order
to see a value change, especially on kilopascal values.
5. Press SELECT to access the highlighted period or
override.
To Remove an Override
1. On the Point Status table press NEXT or
PR
2. Preln
3. Press RELEASE to remove the override and return the
poio tPC’mttl
Fig. 14 — Example of Time Schedule
Operation Screen
18
Download from Www.Somanuals.com. All Manuals Search And Download.
DEFAULT SCREEN
LOCAL RESET
MENU
(SOFTKEYS)
CCN
Start Chiller In CCN Control
Start Chiller In Local Control
Clear Alarms
Access Main Menu
SCHEDULE
SETPOINT
STATUS
SERVICE
1 2
(ENTER A 4-DIGIT PASSWORD)
3
4
List the
Status Tables
List the Service Tables
Display the Setpoint Table
STATUS01
STATUS02
STATUS03
STATUS04
List the Schedules
•
•
•
•
Base Demand Limit
LCW Setpoint
ECW Setpoint
Ice Build Setpoint
SELECT
SELECT
(SELECT A TABLE)
PREVIOUS
PREVIOUS
EXIT
EXIT
NEXT
NEXT
(SELECT A POINT
ON THE TABLE)
Select the Setpoint
PREVIOUS
Modify the Setpoint
INCREASE
(MODIFY A
DISCRETE POINT) or
SELECT
QUIT
EXIT
START
ENTER
ENTER
ENTER
NEXT
STOP
RELEASE
RELEASE
RELEASE
(MODIFY AN
ANALOG POINT) or
INCREASE
DECREASE
DISABLE
ENTER
DECREASE
(MODIFY CONTROL
OPTIONS)
ENABLE
OCCPC01S - Local Time Schedule
OCCPC02S - Ice Build Time Schedule
OCCPC03S-99S - CCN Time Schedule
Select a Schedule
SELECT
PREVIOUS
EXIT
NEXT
1
2
3
4
5
6
7
8
Override
Select a Time Period/Override
SELECT
ENTER
ENTER
PREVIOUS
EXIT
EXIT
EXIT
NEXT
Modify a Schedule Time
INCREASE
DECREASE
(ANALOG VALUES)
(DISCRETE VALUES)
Add/Eliminate a Day
DISABLE
ENABLE
• ALARM HISTORY
• CONTROL TEST
• CONTROL ALGORITHM STATUS
• EQUIPMENT CONFIGURATION
• EQUIPMENT SERVICE
• TIME AND DATE
• ATTACH TO NETWORK DEVICE
• LOG OUT OF DEVICE
• CONTROLLER IDENTIFICATION
• LID CONFIGURATION
Select a Service Table
PREVIOUS
SELECT
EXIT
NEXT
SEE FIGURE 16
Fig. 15 — 17EX LID Menu Structure
19
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE TABLE
PREVIOUS
ALARM HISTORY
SELECT
EXIT
NEXT
Display Alarm History
(The table holds up to 25 alarms
and alerts with the last alarm at
the top of the screen.)
CONTROL TEST
List the Control Tests
• Automated Test
• PSIO Thermistors
• Options Thermistor
• Transducers
CONTROL ALGORITHM STATUS
• Guide Vane Actuator
• Pumps
List the Control Algorithm Status Tables
MAINT01 (Capacity Control)
MAINT02 (Override Status)
MAINT03 (Surge/HGBP Status)
MAINT04 (Lead/Lag Status)
WSMDEFME (Water System Manager Control Status)
OCCDEFM (Time Schedule Status)
• Discrete Outputs
• Pumpdown Lockout
• Terminated Lockout
• FX Gear Oil Pump I/O
Select a Test
NEXT
SELECT
PREVIOUS
EXIT
Select a Table:
SELECT
PREVIOUS
EXIT
NEXT
MAINT01 (Capacity Control Algorithm)
MAINT02 (Override Status)\
OCCDEFM (Time Schedule Status)
MAINT03 (Surge/HGBP Status)
MAINT04 (LEAD/LAG Status)
WSMDEFM2 (Water System Manager Control Status)
Data Select Table
PREVIOUS
SELECT
EXIT
NEXT
Maintenance Table Data
OCCPC01S (Local Status)
OCCPC02S (CCN, ICE BUILD Status)
OCCPC03S (CCN Status)
EQUIPMENT CONFIGURATION
List the Equipment Configuration Tables
• CONFIG
• LEAD/LAG
• OCCDEFCS
• HOLIDEF
• BRODEF
• WSMALMDF
• ALARMDEF
• CONS_DEF
• RUNT_DEF
Select a Table
SELECT
PREVIOUS
EXIT
NEXT
Select a Parameter
SELECT
PREVIOUS
EXIT
NEXT
Modify a Parameter
CONTINUED
ON NEXT PAGE
(ANALOG
VALUES)
(DISCRETE
VALUES)
(DISCRETE
VALUES)
INCREASE
ENTER
ENTER
ENTER
DECREASE
QUIT
QUIT
QUIT
DISABLE
NO
ENABLE
YES
Fig. 16 — 17EX Service Menu Structure
20
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE MENU CONTINUED
FROM PREVIOUS PAGE
EQUIPMENT SERVICE (See Table 2, Examples 8, 9, and 10)
Service Tables: (See Note)
• SERVICE1
• SERVICE2
• SERVICE3
Select a Service Table
SELECT
Select a Service Table Parameter
SELECT
PREVIOUS
EXIT
EXIT
NEXT
PREVIOUS
NEXT
Modify a Service Table Parameter
INCREASE
ENTER
ENTER
ENTER
(ANALOG VALUES)
(DISCRETE VALUES)
(DISCRETE VALUES)
DECREASE
DISABLE
YES
QUIT
QUIT
QUIT
ENABLE
NO
TIME AND DATE
Display Time and Date Table:
• To Modify — Time
— Day of Week
— Holiday Today
— Date
ATTACH TO NETWORK DEVICE
INCREASE
EXIT
DECREASE
ENTER
List Network Devices
• Local
• Device 6
• Device 1 • Device 7
• Device 2 • Device 8
• Device 3 • Device 9
• Device 4
• Device 5
Select a Device
SELECT
ENTER
ATTACH
EXIT
PREVIOUS
NEXT
Modify Device Address
INCREASE
DECREASE
• Use to attach LID to another CCN network or device
• Attach to "LOCAL" to enter this machine
• To upload new tables
LOG OUT OF DEVICE
Default Screen
LOCAL
RESET
MENU
CCN
CONTROLLER IDENTIFICATION
PSIO Controller
Identification Table
INCREASE
DECREASE
ENTER
EXIT
• To modify — PSIO CCN Address
• To View — PSIO Software Version
(last 2 digits on part number indicate software version)
LID CONFIGURATION
LID Configuration Table
INCREASE
DECREASE
ENTER
EXIT
• To View — LID Software Version
(last 2 digits of part number
indicate software version)
• To Modify — LID CCN Address
— English or S.I. Metric Units
— Password
LEGEND
CCN
HGBP
LID
—
—
—
Carrier Comfort Network
Hot Gas Bypass
Local Interface Device
NOTE: SERVICE TABLES:
SERVICE1:
—
—
—
—
—
—
—
—
—
—
—
—
—
Capacity Override
SERVICE2:
SERVICE3:
—
—
8-input Modules
Type of Chilled Medium
Alert Temperature
20 mA Power Source
Flow Verification
Deadband
Recycle Restart Time
Surge/HGBP Operation
Motor Voltage, RLA, and Frequency
Starter Type
—
—
—
—
Proportional Inc each Band
Proportional Dec each Band
Proportional ECW Gain
Maximum Guide Vane Opening
Condenser Freeze Safety
Soft Stop Configuration
Start to Stop Timer
Gear Oil Pump Configuration
Fig. 16 — 17EX Service Menu Structure (cont)
21
Download from Www.Somanuals.com. All Manuals Search And Download.
6. a. Press INCREASE or DECREASE to change the
4. Pre
time values. Override values are in one-hour incre-
5. Press INCREASE or DECREASE to change the se-
lecti
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE to eliminate days from the
6. Press ENTER to save the changes and return to the
previous sceen.
7. Press ENTER to register the values and to move
ho
8. Pr
9. Either return to Step 4 to select another period or
override, or press EXIT again to leave the cur-
re
10. Holiday Designation (HOLIDEF table) may be found in
the Service Operation section, page 42. You must assign
the month, day, and duration for the holiday. The Broad-
cast function in the BRODEF table also must be en-
abled for holiday periods to function.
Fig. 17 — Example of Set Point Screen
SERVICE OPERATION — To view the menu-driven pro-
grams available for Service Operation, see the Service Op-
eration section, page 42. For examples of LID display screens,
see Table 2.
TO VIEW AND CHANGE SET POINTS (Fig. 17)
1. To view the Set Point table, at the Menu screen press
SETPOINT .
LEGEND FOR TABLE 2 — LID DISPLAY DATA
CCN
CHWR
CHWS
Compr
Dec
Ecw
HGBP
Inc
LCW
mA
P
PIC
Refrig
T
Temp
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Carrier Comfort Network
Chilled Water Return
Chilled Water Supply
Compressor
2. There are 4 set points on this screen: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW
Set Point (entering chilled water set point); and ICE BUILD
set point. Only one of the chilled water set points can be
active at one time, and the type of set point is activated
in the Service menu. ICE BUILD is also activated and
configured in the Service menu.
Decrease
Entering Chilled Water
Hot Gas Bypass
Increase
Leaving Chilled Water
Milliamps
Pressure
Product Integrated Controls
Refrigerant
Temperature
Temperature
3. Press NEXT or PREVIOUS to highlight the desired
set ponenry.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data
NOTES:
5. The items in the Reference Point Name column do not appear on
the LID screen. They are data or variable names used in CCN or
Building Supervisor software. They are listed in these tables as a
convenience to the operator if it is necessary to cross reference
CCN/BS documentation or use CCN/BS programs. For more in-
formation, see the 17EX CCN literature.
IMPORTANT: The following notes apply to all Table
examples.
2
6. Reference Point Names shown in these tables in all capital letters
can be read by CCN and Building Supervisor software. Of these
capitalized names, those preceded by an asterisk can also be
changed (that is, written to) by the CCN, Building Supervisor soft-
ware and the LID. Capitalized Reference Point Names preceded
by two asterisks can be changed only from the LID. Reference
Point Names in lower case type can be viewed by CCN or Build-
ing Supervisor software only by viewing the whole table.
7. Alarms and Alerts: An asterisk in the far right field of a LID status
screen indicates that the chiller is in an alarm state; an exclama-
tion point in the far right field of the LID screen indicates an alert
state. The asterisk (or exclamation point) indicates that the value
on that line has exceeded (or is approaching) a limit. For more
information on alarms and alerts, see the Alarms and Alerts sec-
tion, page 16.
1. Only 12 lines of information appear on the LID screen at any one
time. Press the NEXT or PREVIOUS softkey to highlight a point
or to view items below or above the current screen. If you have a
chiller with a backlit LID, press the NEXT softkey twice to page
forward; press the PREVIOUS softkey twice to page back.
2. To access the information shown in Examples 6 through 14, enter
your 4-digit password after pressing the SERVICE softkey. If no
softkeys are pressed for 15 minutes, the LID automatically logs off
(to prevent unrestricted access to PIC controls) and reverts to the
default screen. If this happens, you must reenter your password
to access the tables shown in Examples 6 through 14.
3. Terms in the Description column of these tables are listed as they
appear on the LID screen.
4. The LID may be configured in English or Metric (SI) units using
the LID CONFIGURATION screen. See the Service Operation sec-
tion, page 42, for instructions on making this change.
EXAMPLE 1 — STATUS01 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS (STATUS01 will be highlighted).
3. Press SELECT .
REFERENCE POINT NAME
DESCRIPTION
RANGE
UNITS
(ALARM HISTORY)
Control Mode
Run Status
Reset.Off. Local. CCN
MODE
Timeout. Recycle. Startup.
Ramping. Running. Demand.
STATUS
Override. Shutdown. Abnormal.
Pumpdown
Occupied ?
Alarm State
No/Yes
OCC
ALM
CHIL
DLM
Normal/Alarm
Stop/Start
*Chiller Start/Stop
Base Demand Limit
*Active Demand Limit
Compressor Motor Load
Current
S
S
40-100
%
40-100
%
DEM LIM
0-999
%
%
CA
CA
CA
L
P
A
0-999
Amps
0-9999
AMPS
*Target Guide Vane Pos
Actual Guide Vane Pos
Water/Brine: Setpoint
0-100
%
%
GV TRG
GV ACT
SP
LCW STPT
ECW
LCW
0-100
10-120 (–12.2-48.9)
10-120 (–12.2-48.9)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
*
Control Point
Entering Chilled Water
Leaving Chilled Water
Entering Condenser Water
Leaving Condenser Water
Evaporator Refrig Temp
Evaporator Pressure
Condenser Refrig Temp
Condenser Pressure
Discharge Temperature
Bearing Temperature
Motor Winding Temp†
Motor Winding Hi
ECDW
LCDW
ERT
ERP
DEG F (DEG C)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
CRT
CRP
CMPD
MTRB
MTRW
Normal/Alarm
MTRW
Temp Cutout
Oil Sump Temperature
Oil Pressure Transducer†
Oil Pressure**
Line Voltage: Percent
Actual
*Remote Contacts Input
Total Compressor Starts
Starts in 12 Hours
–40-245 (–40-118)
–6.7-420 (–46-2896)
–6.7-420 (–46-2896)
0-999
DEG F (DEG C)
PSI (kPa)
PSID (kPad)
%
OILT
OILP
OILPD
V
V
P
A
0-9999
VOLTS
Off/On
REMCON
0-65535
c
starts
0-8
STARTS
Compressor Ontime
*Service Ontime
*Compressor Motor kW
0-500000.0
0-32767
HOURS
HOURS
kW
c
S
hrs
HRS
0-9999
CKW
†Information is applicable to hermetic chillers (19EX) only.
**Oil pressure is read directly from a differential pressure module on 17EX chillers.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 2 — STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS02.
4. Press SELECT .
POINT TYPE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
DESCRIPTION
INPUT
OUTPUT
Hot Gas Bypass Relay
*Chilled Water Pump
Chilled Water Flow
X
X
OFF/ON
HGBR
OFF/ON
CHWP
X
X
NO/YES
EVFL
*Condenser Water Pump
Condenser Water Flow
Compressor Start Relay
Compressor Start Contact
Compressor Run Contact
Starter Fault Contact
Pressure Trip Contact
Single Cycle Dropout
Oil Pump Relay
X
X
OFF/ON
CDP
NO/YES
CDFL
OFF/ON
CMPR
X
X
X
X
X
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
NORMAL/ALARM
OFF/ON
1CR AUX
RUN AUX
STR FLT
PRS TRIP
V1 CYCLE
OILR
X
X
X
X
X
X
X
Oil Heater Relay
OFF/ON
OILH
MTRC
Motor Cooling Relay†
Auxiliary Oil Pump Relay
*Tower Fan Relay
OFF/ON
OFF/ON
AUXOILR
TFR
OFF/ON
Compr. Shunt Trip Relay
Alarm Relay
Spare Prot Limit Input
OFF/ON
TRIPR
NORMAL/ALARM
ALARM/NORMAL
ALM
X
SPR PL
†Information is applicable to hermetic machines only.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
EXAMPLE 3 — STATUS03 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS03.
4. Press SELECT .
REFERENCE POINT NAME
(ALARM HISTORY)
DESCRIPTION
RANGE
UNITS
OPTIONS BOARD 1
*Demand Limit 4-20 mA
*Temp Reset 4-20 mA
4-20
4-20
mA
mA
DEM OPT
RES OPT
CHWS
*Common CHWS Sensor
*Common CHWR Sensor
*Remote Reset Sensor
*Temp Sensor — Spare 1
*Temp Sensor — Spare 2
*Temp Sensor — Spare 3
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
CHWR
R
RESET
SPARE1
SPARE2
SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 1
4-20
mA
SPARE1
SPARE2
SPARE4
SPARE5
SPARE6
SPARE7
SPARE8
SPARE9
M
M
*4-20 mA — Spare 2
4-20
mA
*Temp Sensor — Spare 4
*Temp Sensor — Spare 5
*Temp Sensor — Spare 6
*Temp Sensor — Spare 7
*Temp Sensor — Spare 8
*Temp Sensor — Spare 9
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 4 — STATUS04 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS04.
4. Press SELECT .
REFERENCE POINT NAME
(ALARM HISTORY)
DESCRIPTION
RANGE
UNITS
Main Gear Oil Pump
Auxiliary Gear Oil Pump
Gear Oil Pressure
OFF/ON
MAINPMP1
AUXPMP2
GEAROILP
GEAROILT
OFF/ON
−6.7 to 420 (−46 to 2896)
−40 to 245 (−40 to 118)
psi (kPa)
DEG F (DEG C)
Gear Oil Temperature
EXAMPLE 5 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SETPOINT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Base Demand Limit
LCW Setpoint
40-100
%
DLM
100
20-120 (–6.7-48.9)
20-120 (–6.7-48.9)
20- 60 (–6.7-15.6)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
lcw sp
ecw sp
ice sp
50.0 (10.0)
60.0 (15.6)
40.0 ( 4.4)
ECW Setpoint
ICE BUILD Setpoint
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE .
.
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight CONFIG.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA
–30-30 (–17-17)
DEG F (DEG C)
deg 20ma
10⌬(6⌬)
RESET TYPE 2
Remote Temp (No Reset)
Remote Temp (Full Reset)
Degrees Reset
–40-245 (–40-118)
–40-245 (–40-118)
–30-30 (–17-17)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
res rt1
res rt2
res rt
85 (29)
65 (18)
10⌬(6⌬)
RESET TYPE 3
CHW Delta T (No Reset)
CHW Delta T (Full Reset)
Degrees Reset
0-15 (0-8)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
restd
restd
1
2
10⌬(6⌬)
0⌬(0⌬)
5⌬(3⌬)
0-15 (0-8)
–30-30 (–17-17)
deg chw
Select/Enable Reset Type
0-3
res sel
0
ECW CONTROL OPTION
Demand Limit At 20 mA
20 mA Demand Limit Option
DISABLE/ENABLE
40-100
DISABLE/ENABLE
ecw opt
dem 20ma
dem sel
DISABLE
40
DISABLE
%
Auto Restart Option
DISABLE/ENABLE
DISABLE/ENABLE
astart
DISABLE
DISABLE
Remote Contacts Option
r
contact
Temp Pulldown Deg/Min
Load Pulldown %/Min
Select Ramp Type:
2-10
5-20
0/1
tmp ramp
kw ramp
ramp opt
3
10
1
Temp = 0, Load = 1
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
0-99
0-60
0-120
ldsgrp
ldsdelta
maxldstm
0
20
60
%
MIN
CCN Occupancy Config:
Schedule Number
Broadcast Option
3-99
occpcxxe
occbrcst
3
DISABLE/ENABLE
DISABLE
ICE BUILD Option
DISABLE/ENABLE
ibopt
DISABLE
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both
0-2
ibterm
0
ICE BUILD Recycle Option
DISABLE/ENABLE
ibrecyc
DISABLE
NOTE: ⌬ = delta degrees.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE .
.
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT .
LEAD/LAG CONFIGURATION SCREEN
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
0-3
leadlag
0
Load Balance Option
Common Sensor Option
LAG Percent Capacity
LAG Address
LAG START Timer
LAG STOP Timer
PRESTART FAULT Timer
STANDBY Chiller Option
STANDBY Percent Capacity
STANDBY Address
DISABLE/ENABLE
DISABLE/ENABLE
25-75
1-236
2-60
2-60
0-30
DISABLE/ENABLE
25-75
1-236
loadbal
DISABLE
DISABLE
50
92
10
10
5
DISABLE
50
93
commsens
lag per
lag add
lagstart
lagstop
preflt
stndopt
stnd per
stnd add
%
MIN
MIN
MIN
%
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 8 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE .
.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE1.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Motor Temp Override*
Cond Press Override
Refrig Override Delta T
Chilled Medium
150-200 (66-93)
90-200 (620-1379)
2-5 (1-3)
DEG F (DEG C)
PSI (kPa)
mt over
cp over
ref over
medium
200 (93)
125 (862)
3⌬ (1.6⌬)
WATER
33 (1)
DEG F (DEG C)
Water/Brine
Brine Refrig Trippoint
8-40 (–13.3-4)
DEG F (DEG C)
br trip
Compr Discharge Alert
Bearing Temp Alert
125-200 (52-93)
165-210 (74-99)
DEG F (DEG C)
DEG F (DEG C)
cd alert
tb alert
200 (93)
175 (79)
Water Flow Verify Time
Oil Press Verify Time
0.5-5
15-300
MIN
SEC
wflow
oilpr
t
5
15
t
Water/Brine Deadband
Recycle Restart Delta T
Recycle Shutdown Delta
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Min. Load Points (T1/P1)
Surge/HGBP Delta T2
Surge/HGBP Delta P2
Full Load Points (T2/P2)
Surge/HGBP Deadband
0.5-2.0 (0.3-1.1)
2.0-10.0 (1.1-5.6)
0.5-4.0 (.27-2.2)
0/1
DEG F (DEG C)
DEG F (DEG C)
cw db
rcycrdt
rcycsdt
1.0 (0.6)
5 (2.8)
1.0 (0.6)
0
srg hgbp
0.5-15 (0.3-8.3)
30-170 (207-1172)
DEG F (DEG C)
PSI (kPa)
hgb dt1
hgb dp1
1.5 (0.8)
50 (345)
0.5-15 (0.3-8.3)
30-170 (207-1172)
DEG F (DEG C)
PSI (kPa)
hgb dt2
hgb dp2
10 (5.6)
85 (586)
1-3 (0.6-1.6)
DEG F (DEG C)
hgb dp
1 (0.6)
Surge Delta Percent Amps
Surge Time Period
10-50
1-5
%
MIN
surge
surge
a
t
25
2
Demand Limit Source
Select: Amps=0, Load=1
Amps Correction Factor
Motor Rated Load Amps
Motor Rated Line Voltage
Meter Rated Line kW
0/1
dem src
0
1-8
corfact
3
1-9999
1-9999
1-9999
AMPS
VOLTS
kW
a
v
fs
fs
200
460
600
kw fs
Line Frequency
Select: 0=60 Hz, 1=50 Hz
0/1
HZ
freq
0
Compr Starter Type
REDUCE/FULL
–20-35 (–28.9-1.7)
40-100
starter
REDUCE
34 (1)
100
Condenser Freeze Point
Soft Stop Amps Threshold
DEG F (DEG C)
%
cdfreeze
softstop
Stop to Start Timer
3-50
MIN
stopmtr
20
External Gear Option
ENABLE/DSABLE
ENABLE/DSABLE
ENABLE/DSABLE
PSI (kPa)
exg opt
mech pmp
aux pmp
gearp al
geart al
ENABLE
DSABLE
DSABLE
15 (103)
130 (54)
Mechanical Gear Oil Pump
Auxiliary Gear Oil Pump
Gear Oil Pressure Alert
Gear Oil Temperature Alert
15-20 (103-138)
130-145 (54-63)
DEG F (DEG C)
*Information is applicable to hermetic machines (19EX) only.
NOTE: ⌬ = delta degrees.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 9 — SERVICE2 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE .
.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE2.
6. Press SELECT .
DESCRIPTION
OPTIONS BOARD 1
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME DEFAULT VALUE
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source
DEMAND 20 mA Power Source
0,1
0,1
res 20 ma
dem 20 ma
0
0
SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
CHWS Temp Enable
CHWS Temp Alert
CHWR Temp Enable
CHWR Temp Alert
Reset Temp Enable
Reset Temp Alert
Spare Temp 1 Enable
Spare Temp 1 Alert
Spare Temp 2 Enable
Spare Temp 2 Alert
Spare Temp 3 Enable
Spare Temp 3 Alert
0-4
chws en
0
–40-245 (–40-118)
DEG F (DEG C) chws al
chwr en
245 (118)
0-4
0
–40-245 (–40-118)
0-4
DEG F (DEG C) chwr al
rres en
245 (118)
0
–40-245 (–40-118)
0-4
DEG F (DEG C) rres al
spr1 en
245 (118)
0
–40-245 (–40-118)
0-4
DEG F (DEG C) spr1 al
spr2 en
245 (118)
0
–40-245 (–40-118)
0-4
DEG F (DEG C) spr2 al
spr3 en
245 (118)
0
–40-245 (–40-118)
DEG F (DEG C) spr3 al
245 (118)
OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 mA Power Source
SPARE 2 20 mA Power Source
0,1
0,1
sp1 20 ma
sp2 20 ma
0
0
SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
Spare Temp 4 Enable
Spare Temp 4 Alert
Spare Temp 5 Enable
Spare Temp 5 Alert
Spare Temp 6 Enable
Spare Temp 6 Alert
Spare Temp 7 Enable
Spare Temp 7 Alert
Spare Temp 8 Enable
Spare Temp 8 Alert
Spare Temp 9 Enable
Spare Temp 9 Alert
0-4
spr4 en
DEG F (DEG C) spr4 al
spr5 en
0
–40-245 (–40-118)
245 (118)
0-4
0
–40-245 (–40-118)
0-4
DEG F (DEG C) spr5 al
spr6 en
245 (118)
0
–40-245 (–40-118)
0-4
DEG F (DEG C) spr6 al
spr7 en
245 (118)
0
–40-245 (–40-118)
0-4
DEG F (DEG C) spr7 al
spr8 en
245 (118)
0
–40-245 (–0-118)
0-4
DEG F (DEG C) spr8 al
spr9 en
245 (118)
0
–40-245 (–40-118)
DEG F (DEG C) spr9 al
245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’ threshold for each point listed. If the ‘‘Enable’’
is set to 1, a value above the ‘‘Temp’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold
generates an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the ‘‘Enable’’ is set to 3, a value above the ‘‘Temp’’ threshold
generates an alarm. If the ‘‘Enable’’ is set to 4, a value below the ‘‘Temp’’ threshold generates an alarm.
EXAMPLE 10 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE3.
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Proportional Inc Band
Proportional Dec Band
Proportional ECW Gain
2-10
2-10
1-3
gv inc
gv de
gv ecw
6.5
6.0
2.0
Guide Vane Travel Limit
30-100
%
gv lim
50
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 11 — MAINTENANCE (MAINT01) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE .
.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT .
5. Scroll down to highlight MAINT01.
DESCRIPTION
RANGE/STATUS
UNITS
REFERENCE POINT NAME
CAPACITY CONTROL
Control Point
Leaving Chilled Water
Entering Chilled Water
Control Point Error
ECW Delta T
ECW Reset
LCW Reset
Total Error + Resets
Guide Vane Delta
Target Guide Vane Pos
Actual Guide Vane Pos
10-120 (–12.2-48.9)
–40-245 (–40-118)
–40-245 (–40-118)
–99-99 (–55-55)
–99-99 (–55-55)
–99-99 (–55-55)
–99-99 (–55-55)
–99-99 (–55-55)
–2-2
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
%
ctrlpt
LCW
ECW
cperr
ecwdt
ecwres
lcwres
error
gvd
0-100
%
GV
GV
TRG
ACT
0-100
%
Proportional Inc Band
Proportional Dec Band
Proportional ECW Gain
Water/Brine Deadband
2-10
gv inc
gv dec
gv ecw
cwdb
2-10
1-3
0.5-2 (0.3-1.1)
DEG F (DEG C)
NOTE: Overriding is not supported on this maintenance screen. Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
EXAMPLE 12 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT .
5. Scroll down to highlight MAINT02.
6. Press SELECT .
DESCRIPTION
RANGE/STATUS
UNITS
REFERENCE POINT NAME
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP†
Override Threshold
–40-245 (–40-118)
150-200 (66-93)
–6.7-420 (–42-2896)
90-245 (621-1689)
–40-245 (–40-118)
2-45 (1-7.2)
–40-245 (–40-118)
125-200 (52-93)
–40-245 (–40-118)
175-185 (79-85)
DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
MTRW
mt over
CRP
CONDENSER PRESSURE
Override Threshold
PSI (kPa)
cp over
ERT
EVAPORATOR REFRIG TEMP
Override Threshold
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
rt over
CMPD
DISCHARGE TEMPERATURE
Alert Threshold
cd alert
MTRB
BEARING TEMPERATURE
Alert Threshold
tb alert
†Information is applicable to hermetic machines (19EX) only.
NOTE: Overriding is not supported on this maintenance screen. Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — LID Display Data (cont)
EXAMPLE 13 — MAINTENANCE (MAINT03) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE .
.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT .
5. Scroll down to highlight MAINT03.
6. Press SELECT .
DESCRIPTION
RANGE/STATUS
UNITS
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
REFERENCE POINT NAME
SURGE/HGBP ACTIVE ?
NO/YES
Active Delta P
Active Delta T
Calculated Delta T
0-200 (0-1379)
0-200 (0-111)
0-200 (0-111)
dp
dt
a
a
dt
c
Surge Protection Counts
0-12
spc
NOTE: Override is not supported on this maintenance screen. Only values with capital letter reference point names are variables available for read
operation.
EXAMPLE 14 — MAINTENANCE (MAINT04) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE .
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT .
5. Scroll down to highlight MAINT04.
6. Press SELECT .
DESCRIPTION
RANGE/STATUS
UNITS
REFERENCE POINT NAME
LEAD/LAG: Configuration
Current Mode
DISABLE,LEAD,LAG,STANDBY, INVALID
leadlag
llmode
loadbal
lagstart
lagstop
preflt
pull dt
pull sat
leadctrl
lagmode
lagstat
DISABLE,LEAD,LAG,STANDBY, CONFIG
Load Balance Option
LAG Start Time
DISABLE/ENABLE
0-60
MIN
MIN
MIN
LAG Stop Time
0-60
Prestart Fault Time
Pulldown: Delta T/Min
Satisfied?
0-30
x.xx
⌬ DEG F (⌬ DEG C)
No/Yes
LEAD CHILLER in Control
LAG CHILLER: Mode
Run Status
No/Yes
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown
Stop,Start,Retain
Start/Stop
lag
s
s
s
Recovery Start Request
STANDBY CHILLER: Mode
Run Status
No/Yes
lag rec
stdmode
Reset,Off,Local,CCN
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown
Stop,Start,Retain
stdstat
Start/Stop
Recovery Start Request
std
s
No/Yes
std rec
NOTES:
1. Values on this screen cannot be ‘‘forced’’ (that is, changed by an operator, from the LID or from any other device [such as a CCN terminal]).
2. ⌬ = delta degrees.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
The PROPORTIONAL ECW GAIN can be adjusted at the LID
display from a setting of 1.0 to 3.0, with a default setting of
2.0. Increase this setting to increase guide vane response to
a change in entering chilled water temperature.
DEMAND LIMITING — The PIC responds to the ACTIVE
DEMAND LIMIT set point by limiting the opening of the
guide vanes. It compares the set point to either COMPRES-
SOR MOTOR LOAD or COMPRESSOR MOTOR LOAD CUR-
RENT (percentage), depending on how the control is con-
figured for the DEMAND LIMIT SOURCE which is accessed
on the SERVICE1 screen. The default setting is current
limiting. The ACTIVE DEMAND LIMIT may be viewed on
the STATUS01 screen.
PIC System Functions
NOTE: In the rest of this manual, words not part of para-
graph headings and printed in all capital letters can be viewed
on the LID (e.g., LOCAL, CCN, RUNNING, ALARM, etc.).
Words printed both in capital letters and italics can also be
viewed on the LID and are parameters (CONTROL MODE,
COOLING SETPOINT, OVERRIDE THRESHOLD, etc.) with
associated values (e.g., modes, temperatures, pressures, per-
centages, on, off, etc.). Words printed in all capital letters
and in a box represent softkeys on the LID control panel
(e.g., ENTER and EXIT ). See Table 2 for examples of
the information that can appear on the LID screens.
Figures 11-17 give an overview of LID operation and menus.
CHILLER TIMERS — The PIC maintains 2 runtime clocks,
known as COMPRESSOR ONTIME and SERVICE
ONTIME. COMPRESSOR ONTIME indicates the total life-
time compressor run hours. This timer can register up to
500,000 hours before the clock turns back to zero. The SERV-
ICE ONTIME is a resettable timer that can be used to indi-
cate the hours since the last service visit or any other event.
The time can be changed from the LID to whatever value is
desired. This timer can register up to 32,767 hours before it
rolls over to zero.
The chiller also maintains a start-to-start timer and a stop-
to-start timer. These timers limit how soon the chiller can be
started. See the Start-Up/Shutdown/Recycle Sequence sec-
tion, page 43, for operational information.
CAPACITY CONTROL — The PIC controls the chiller ca-
pacity by modulating the inlet guide vanes in response to
chilled water temperature changes away from the WATER/
BRINE CONTROL POINT. The WATER/BRINE CONTROL
POINT may be changed by a CCN network device or is de-
termined when the PIC adds any active chilled water reset to
the chilled water SET POINT. The PIC uses the PROPOR-
TIONAL INC (Increase) BAND, PROPORTIONAL DEC
(Decrease) BAND, and the PROPORTIONAL ECW (Enter-
ing Chilled Water) GAIN to determine how quickly or slowly
to respond. WATER/BRINE CONTROL POINT may be viewed/
overridden from the STATUS menu, STATUS01 screen.
ENTERING CHILLED WATER CONTROL — If this op-
tion is enabled, the PIC uses the ENTERING CHILLED WA-
TER temperature to modulate the vanes instead of the LEAVING
CHILLED WATER temperature. The ENTERING CHILLED
WATER control option may be viewed/modified from the
CONFIG screen, accessed from the EQUIPMENT CON-
FIGURATION table.
OCCUPANCY SCHEDULE — The chiller schedule, de-
scribed in the Time Schedule Operation section, page 18,
determines when the chiller can run. Each schedule consists
of 1 to 8 occupied/unoccupied time periods, set by the op-
erator. These time periods can be enabled (or not enabled)
on each day of the week and for holidays. The day begins
with 0000 hours and ends with 2400 hours. The chiller is in
an occupied state unless an unoccupied time period is in
effect.
DEADBAND — This is the tolerance on the chilled water/
brine temperature WATER/BRINE CONTROL POINT. If the
water temperature goes outside the WATER/BRINE DEAD-
BAND, the PIC opens or closes the guide vanes in response
until it is within tolerance. The PIC may be configured with
a 0.5° to 2° F (0.3° to 1.1° C) deadband. WATER/BRINE
DEADBAND may be viewed or modified from the
SERVICE1 screen, accessed from the EQUIPMENT
SERVICE table.
For example, a 1° F (0.6° C) deadband setting controls
the water temperature within ±0.5° F (0.3° C) of the control
point. This may cause frequent guide vane movement if the
chilled water load fluctuates frequently. A value of
1° F (0.6° C) is the default setting.
NOTE: To determine whether or not the chiller is in an oc-
cupied state and can be started, access the STATUS01 screen
and scroll to the OCCUPIED? parameter. If the value in the
right column is YES, the chiller is in an occupied state and
can turn on or can be started. If the value is NO, the chiller
is in an unoccupied state; that is, it can shut down or cannot
be started without performing an override.
The schedules can be set to follow the building schedule
or to be in an occupied state 100% of the time. The sched-
ules also can be bypassed by forcing the CHILLER START/
STOP parameter on the STATUS01 screen to START. For
more information on forced starts, see Local Start-Up,
page 43. The schedules also can be overridden to keep the
chiller in an occupied state for up to 4 hours, on a one-time
basis.
PROPORTIONAL BANDSAND GAIN — Proportional band
is the rate at which the guide vane position is corrected in
proportion to how far the chilled water/brine temperature is
from the control point. Proportional gain determines how
quickly the guide vanes react to how quickly the tempera-
ture is moving from WATER/BRINE CONTROL POINT. Pro-
portional bands and gain values can be viewed/modified from
the SERVICE3 screen (accessed from the EQUIPMENT CON-
FIGURATION table) and the MAINT01 screen (accessed from
the CONTROL ALGORITHM STATUS table).
NOTE: A parameter value can be ЉforcedЉ (changed by an
operator) from the LID screen or from another control de-
vice such as a CCN terminal. For example, if the CHILLER
START/STOP parameter is set to START, the operator can
go to the LID and change the value to STOP to ЉforceЉ the
chiller to stop.
Figure 14 shows a schedule for a typical office building
time schedule, with a 3-hour, off-peak cool down period from
midnight to 3 a.m., following a weekend shutdown. For ex-
ample, holiday periods are set to be unoccupied 24 hours per
day. The building operates Monday through Friday, 7:00 a.m.
to 6:00 p.m., with a Saturday schedule of 6:00 a.m. to
1:00 p.m., and includes the Monday midnight to 3:00 a.m.
weekend cool-down schedule.
The Proportional Band — There are two response modes,
one for temperature response above the control point, the
other for response below the control point.
The first type is called PROPORTIONAL INC BAND, and
it can slow or quicken vane response to chilled water/brine
temperature above the WATER/BRINE DEADBAND. It can
be adjusted from a setting of 2 to 10; the default setting is
6.5. PROPORTIONAL DEC BAND can slow or quicken vane
response to chilled water temperature below deadband plus
the control point. It can be adjusted on the LID from a set-
ting of 2 to 10, and the default setting is 6.0. Increasing ei-
ther of these settings causes the vanes to respond more slowly
than at a lower setting.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: This schedule is for illustration only, and is not in-
tended to be a recommended schedule for chiller operation.
Depending on its operating mode, the chiller uses the fol-
lowing occupancy schedules:
Default Screen Freeze — When the chiller is in an
alarm state, the default LID display freezes; that is, it stops
updating. The first line of the LID default screen displays a
primary alarm message; the second line displays a second-
ary alarm message. The LID default screen freezes to allow
the operator to see the condition of the chiller at the time of
the alarm. Knowledge of the operating state of the chiller at
the time an alarm occurs is useful when troubleshooting. Cur-
rent chiller information can be viewed on the STATUS screens
(see Table 2, Examples 1-4). Once all existing alarms are
• LOCAL mode — Occupancy Schedule 01(OCCPC01 on
the SCHEDULE screen).
• ICE BUILD mode — Occupancy Schedule 02 (OC-
CPC02 on the SCHEDULE screen).
• CCN mode — Occupancy Schedule 03-99 (OCCPC02-
OCCPC99 on the SCHEDULE screen).
cleared by pressing the RESET softkey, the default LID
screen returns to normal operation.
The CCN schedule number is specified on the CONFIG
screen, which is accessed from the EQUIPMENT CON-
FIGURATION table. The schedule number can be any value
from 03 to 99. If this schedule number is changed on the
CONFIG screen, the operator must use theATTACH TO NET-
WORK DEVICE screen to upload the new number into the
schedule screen. See Fig. 12.
Auxiliary Compressor Oil Pump Control — The
compressor oil pump (optional) is controlled by the PIC. If,
during start-up, the main oil pump cannot raise pressure to
18 psi (124 kPa), the auxiliary oil pump (optional) is ener-
gized. During compressor operation, the auxiliary oil pump
is energized if the oil pressure falls below the alert threshold
(18 psi [124 kPa]). Once the auxiliary compressor oil pump
is running, it stays on until the compressor is turned off and
is deenergized along with the main oil pump after the post-
lubrication period.
Safety Controls — The PIC monitors all safety control
inputs, and if required, shuts down the chiller or limits the
guide vanes to protect the chiller from possible damage from
several conditions, including:
• high bearing temperature
• high motor winding temperature
• high discharge temperature
• low compressor oil pressure
• low gear oil pressure
• high gear oil temperature
Auxiliary Gear Oil Pump Control — The optional
auxiliary gear oil pump is controlled by the PIC. During start-
up, if the main gear oil pump cannot raise the oil pressure at
least 20 psi (139 kPa), the auxiliary gear oil pump is ener-
gized. If, after 30 seconds, the required oil pressure has not
been established, the PIC initiates an alarm and does not al-
low the chiller to start. During operation, the auxiliary gear
oil pump is energized if the oil pressure falls below the alert
threshold (15 to 20 psi [103 to 139 kPa]). Once the auxiliary
gear oil pump is running, it stays on until the compressor is
turned off and is deenergized with the main gear oil pump
after the post-lubrication period.
• low cooler refrigerant temperature/pressure
• condenser high pressure or low pressure
• inadequate water/brine cooler and condenser flow
• high, low, or loss of voltage
• excessive motor acceleration time
• excessive starter transition time
• lack of motor current signal
• excessive motor amps
Shaft Seal Oil Control — For all open-drive chillers,
the shaft seal must be bathed in oil at all times, especially
when the chiller is not running. This ensures that refrigerant
will not leak past the seal. The PIC energizes the compressor
oil pump for one minute if the oil pump has not operated
during the past 12 hours.
• excessive compressor surge
• temperature and transducer faults
Starter faults or optional protective devices within the starter
can shut down the chiller. These devices depend on what
options have been purchased.
IMPORTANT: If control power is turned off for more
than 12 hours, the refrigerant charge must be pumped
into the economizer/storage vessel. Because the oil heater
is also turned off during this time, storing the refrig-
erant prevents refrigerant from migrating into the oil.
If a compressor motor overload or ground fault occurs,
check the motor for grounded or open phases before at-
tempting a restart.
If the PIC control initiates a safety shutdown, the control
displays a primary and secondary alarm message on the LID,
energizes an alarm relay in the starter, and blinks the alarm
light on the control panel. The alarm information is stored in
memory and can be viewed on the LID by accessing the
ALARM HISTORY table along with a troubleshooting
message.
To give a more specific operating condition warning, the
operator can also define alert limits on various monitored
inputs. Safety contact and alert limits are defined in Table 3.
Alarm and alert messages are listed in the Troubleshooting
Guide section, page 83.
Ramp Loading Control — Ramp loading control slows
down the rate at which the compressor loads up. It prevents
the compressor from loading up during the short time be-
tween chiller start-up and the time the chilled water loop has
to be brought down to normal design conditions. Ramp load-
ing helps to reduce electrical demand by slowly bringing the
chilled water temperature to the control point temperature.
The total power draw during this period stays almost
unchanged.
The PIC bases ramp loading on either the chilled water
temperature or on motor load. See the Table 2, Example 6
(CONFIG screen).
SHUNT TRIP — The PIC can include an optional shunt trip
function that acts as a safety trip. The shunt trip is wired
from an output on the SMM to the motor circuit breaker. If
the PIC tries to shut down the compressor using normal shut-
down procedures but is unsuccessful for 30 seconds, the shunt
trip output is energized and trips off the circuit breaker. If
ground fault protection has been applied to the starter, the
ground fault trip also energizes the shunt trip to trip the cir-
cuit breaker.
1. The temperature ramp loading rate is an operator-
configured value that limits the rate at which either the
leaving chilled water or entering chilled water tempera-
ture decreases (TEMP PULLDOWN DEG/MIN param-
eter on the CONFIG screen). The lowest temperature ramp
rate is used the first time the chiller is started (at com-
missioning). The lowest temperature ramp rate is also used
if chiller power has been off for 3 hours or more (even if
the motor ramp load control method has been selected).
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Protective Safety Limits and Control Settings
MONITORED PARAMETER
LIMIT
APPLICABLE COMMENTS
TEMPERATURE SENSORS
–40 to 245 F (–40 to 118.3 C)
0.08 to 0.98 Voltage Ratio
Must be outside range for 2 seconds
OUT OF RANGE
PRESSURE TRANSDUCERS
OUT OF RANGE
Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage Reference
COMPRESSOR DISCHARGE
TEMPERATURE
Ͼ220 F (104.4 C)
Preset, alert setting configurable
BEARING TEMPERATURE
Ͼ220 F (104.4 C)
Preset, alert setting configurable
Preset, configure chilled medium for water
(Service1 table)
Ͻ33 F (for water chilling) (0.6° C)
EVAPORATOR REFRIGERANT
TEMPERATURE
(Temp converted from Pressure
Reading)
Configure chilled medium for brine (Service1
table). Adjust brine refrigerant trippoint for
proper cutout
ϽBrine Refrigerant Trippoint (set point adjustable
from 0 to 40 F [–18 to 4 C] for brine chilling)
Preset (Read voltage at terminals 34 and 35
on PSIO module)
TRANSDUCER VOLTAGE
Ͻ4.5 vdc Ͼ 5.5 vdc
Ͼ218 ± 7 psig (1503 ± 48 kPa),
CONDENSER PRESSURE — SWITCH
— CONTROL
Preset
reset at 120 ± 10 (827 ± 69 kPa)
215 psig (1482 kPa)
Preset
COMPRESSOR OIL PRESSURE — SWITCH Cutout Ͻ11 psid (76 kPad) ± 1.5 psid (10.3 kPad)
Cut-in Ͼ16.5 psid (114 kPad) ± 4 psid (27.5 kPad)
Preset, no calibration needed
Cutout Ͻ15 psid (103 kPad)
— CONTROL
Preset
Alert Ͻ18 psid (124 kPad)
LINE VOLTAGE — HIGH
— LOW
Ͼ110% for one minute
Preset, based on transformed line voltage to
24 vac rated-input to the Starter Management
Module. Also monitored at PSIO power input.
Ͻ90% for one minute or р85% for 3 seconds
Ͻ50% for one cycle
— SINGLE-CYCLE
Ͼ110% for 30 seconds
Preset
Preset
Preset
COMPRESSOR MOTOR LOAD
(% Compressor Amps)
Ͻ10% with compressor running
Ͼ10% with compressor off
For chillers with reduced voltage mechanical
and solid-state starters
STARTER ACCELERATION TIME
(Determined by inrush current
going below 100% compressor
motor load)
Ͼ45 seconds
Ͼ10 seconds
For chillers with full voltage starters
(Configured on Service1 table)
STARTER TRANSITION
Ͼ75 seconds
Reduced voltage starters only
Energizes condenser pump relay if condenser refrigerant tem-
perature or condenser entering water temperature is below the CONDENSER FREEZE POINT configured in
CONDENSER FREEZE
PROTECTION
configured condenser freeze point temperature. Deenergizes
Service01 table with a default setting of
when the temperature is 5 F (3 C) above condenser freeze point 34 F (1 C).
temperature.
IMPELLER CLEARANCE
Displacement switch open
Thrust movement excessive
Water sensors are installed only on open-drive
motors that use water cooling. (Totally enclosed,
water-to-air cooled [TEWAC] motors)
MOTOR LEAK DETECTOR (TEWAC
MOTORS ONLY)
Water from motor cooling is leaking
GEAR OIL TEMPERATURE
— CONTROL
Cut-Out > 150 F (66 C)
Alert > 130-145 (54 - 63 C)
Preset
Adjustable
GEAR OIL PRESSURE
—CONTROL
Cut-out < 12 psi (83 kPa)
Alert < 15-20 psi (103 - 139 kPa)
Preset
Adjustable
FLOW SWITCHES (Field Supplied)
Operate water pumps with chiller off. Manually reduce water flow and observe
switch for proper cutout. Safety shutdown occurs when cutout time exceeds
3 seconds.
CUT-OFF
SETTING
ADJUSTMENT
SCREW
Carrier Part No. HK06ZC001
NOTE: Dimensions in parentheses are in
millimeters.
Carrier Part No. HK06ZC033
34
Download from Www.Somanuals.com. All Manuals Search And Download.
2. The motor load ramp loading rate is an operator-configured
value that limits the rate at which the compressor motor
current or compressor motor load increases. (LOAD PULL-
DOWN %/MIN on the CONFIG screen).
To select the ramp type, highlight the SELECT RAMP
TYPE parameter on the CONFIG screen and select either
0 (TEMP) or 1 (LOAD). Motor load (1) is the default ramp
loading control type.
High Discharge Temperature Control — If the dis-
charge temperature increases above 200 F (93 C), the guide
vanes are proportionally opened to increase gas flow through
the compressor. If the leaving chilled water temperature drops
5° F (2.8° C) below the control point temperature, chiller
enters the RECYCLE mode.
Oil Sump Temperature Control — The oil sump tem-
perature control is regulated by the PIC which uses the oil
heater relay when the chiller is shut down.
As part of the pre-start checks executed by the controls,
the PIC compares the oil sump temperature to the evapora-
tor refrigerant temperature. If the difference between these 2
temperatures is 50 F (27.8 C) or less, the start-up is delayed
until the oil temperature difference is 50 F (27.8 C) or more.
Once this temperature is confirmed, the start-up continues.
The oil heater relay is energized whenever the chiller com-
pressor is off and the oil sump temperature is less than
150 F (65.6 C) or the oil sump temperature is less than the
cooler refrigerant temperature plus 70° F (39° C). The oil
heater is turned off when the oil sump temperature is either
Capacity Override (See Table 4) — Capacity over-
rides can prevent some safety shutdowns caused by exceed-
ing the motor amperage limit, refrigerant low temperature
safety limit, motor high temperature safety limit, and con-
denser high pressure limit. In all of these cases, there are
2 stages of compressor vane control.
1. The guide vanes are kept from opening further, and the
status line on the LID displays the reason for the
override.
2. The guide vanes are closed until the condition decreases
below the first step set point. Then, the vanes are released
to normal capacity control.
• more than 160 F (71.1 C)
Whenever the motor current demand limit set point is reached,
it activates a capacity override, again using the 2-step pro-
cess. Exceeding 110% of the rated load amps for more than
30 seconds initiates a safety shutdown.
• or the oil sump temperature is more than 155 F (68.3 C)
and more than the cooler refrigerant temperature plus
75° F (41.6° C).
The oil heater is always off during start-up or when the
compressor is running.
The compressor high lift (surge prevention) set point causes
a capacity override as well. When the surge prevention set
point is reached, the PIC normally prevents the guide vanes
from opening. See the Surge Prevention Algorithm section,
page 37. If the chiller is equipped with the hot gas bypass
option, the PIC opens the hot gas bypass valve instead of
holding the guide vanes.
When a power failure to the PSIO module has occurred
for more than 3 hours (i.e., initial start-up), the compressor
guide vane opening is slowed down to prevent excessive oil
foaming that may result from refrigerant migration into the
oil sump during the power failure. The vane opening is slowed
via temperature ramp loading to a value of 2° F (1.1° C) per
minute.
Table 4 — Capacity Overrides
SECOND STAGE
SETPOINT
OVERRIDE
FIRST STAGE SETPOINT
Default Value
OVERRIDE
CAPACITY
CONTROL
TERMINATION
View/Modify
on LID Screen
Configurable Range
Value
Value
ϾOverride
Set Point
+ 4 psid (28 kPad)
HIGH CONDENSER
PRESSURE
Equipment
Service1
125 psig
(862 kPa)
90 to 200 psig
(620 to 1379 kPa)
ϽOverride
Set Point
LOW REFRIGERANT
TEMPERATURE
(Refrigerant Override
Delta Temperature)
рTrippoint
+ Override
⌬T –1° F
(0.56° C)
ϾTrippoint
+ Override
⌬T +2° F
(1.2° C)
Equipment
Service1
Ͻ3° F (1.6° C)
(Above Trippoint)
2° to 5° F
(1° to 3° C)
Min: T1 — 1.5° F
(0.8° C)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
Within
Lift Limits
Plus Surge/
HGBP
Deadband
Setting
P1 — 50 psid
(345 kPad)
HIGH COMPRESSOR
LIFT
(Surge Prevention)
Equipment
Service1
None
Max: T2 — 10° F
(5.6° C)
P2 — 85 psid
(586 kPad)
MANUAL
GUIDE VANE
TARGET
Control
Algorithm
Maint01
Release of
Manual
Automatic
100%
0 to 100%
None
Control
MOTOR LOAD —
ACTIVE
DEMAND LIMIT
2% Lower
Than
Set Point
у5% of
Set Point
Status01
40 to 100%
LEGEND
HGBP
P1
—
—
—
—
—
High Gas Bypass
Minimum Pressure Load
Maximum Pressure Load
Minimum Temperature Load
Maximum Temperature Load
P2
T1
T2
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Oil Cooler — The oil for the external gear and the com-
pressor must be cooled while the compressor is running. The
compressor oil cooler is a water-cooled, helical, tube-in-
shell type heat exchanger. A plug valve is manually set to
maintain proper temperatures. Set the valve to maintain a
145 F (63 C) oil sump temperature while the compressor is
running.
The gear oil cooler is a water-cooled, helical tube-in-shell
type heat exchanger. A plug valve is manually set to main-
tain proper temperatures. Set the valve to maintain the oil
temperature leaving the cooler at 130 F (54 C) while the com-
pressor is running.
Condenser Freeze Prevention — This control al-
gorithm helps prevent condenser tube freeze-up by energiz-
ing the condenser pump relay. If the pump is controlled by
the PIC, starting the pump helps prevent the water in the
condenser from freezing. Condenser freeze prevention can
occur whenever the chiller is not running except when it is
either actively in pumpdown or in pumpdown lockout with
the freeze prevention disabled.
When the condenser refrigerant temperature is less than
or equal to the condenser freeze point (CONDENSER FREEZE
POINT on the SERVICE1 screen), or the entering condenser
water temperature is less than or equal to the condenser freeze
point, then the condenser water pump (CONDENSER WA-
TER PUMP on the STATUS02 screen) is energized until the
condenser refrigerant temperature is greater than the con-
denser freeze point plus 5° F (2.7° C). If the chiller is in
PUMPDOWN mode and the pump is energized, the PIC ac-
tivates an alarm. If the chiller is not in PUMPDOWN mode
and the pump is energized, the PIC activates an alert. If the
chiller is in RECYCLE shutdown mode, the mode transi-
tions to SHUTDOWN (non-recycle shutdown).
Remote Start/Stop Controls — A remote device, such
as a time clock with a set of contacts, may be used to start
and stop the chiller. However, the device should not be pro-
grammed to start and stop the chiller more than 2 or 3 times
every 12 hours. If more than 8 starts in 12 hours occur, the
Excessive Starts alarm is displayed, and the chiller is pre-
vented from starting. The operator must reset the alarm at
the LID in order to override the starts counter and start the
chiller. If the automatic restart after a power failure (AUTO
RESTART OPTION ) is not activated (disabled) when a power
failure occurs and the remote contact is closed, the PIC con-
trol activates an alarm because of the loss of voltage.
Tower-Fan Relay — This control can be used to assist
the condenser water temperature control system (field sup-
plied). Low condenser water temperature can cause the chiller
to shut down on low refrigerant temperature. The tower fan
relay, located in the starter, is controlled by the PIC to en-
ergize and deenergize as the pressure differential between
cooler and condenser vessels changes. This function pre-
vents low condenser water temperature and maximizes chiller
efficiency. The tower-fan relay can only accomplish this if
the relay has been added to the cooling tower temperature
controller. The tower-fan relay (TOWER FAN RELAY on the
STATUS02 screen) is turned on whenever the condenser wa-
ter pump is running, flow is verified, and the difference be-
tween cooler and condenser pressure is more than 30 psid
(207 kPad) or entering condenser water temperature is greater
than 85 F (29 C). The tower-fan relay is deenergized when-
ever the condenser pump is off, flow is lost, the evaporator
refrigerant temperature is less than the override temperature,
or the differential pressure is less than 28 psid (193 kPad)
and entering condensing water is less than 80 F (27 C).
The contacts for remote starting are wired into the starter
at terminal strip TB5, terminals 8A and 8B. See the certified
drawings for further details on contact ratings. The contacts
must be dry (no power).
Spare Safety Inputs — Normally closed (NC) digital
inputs for additional field-supplied safeties may be wired to
the spare protective limits input channel in place of the factory-
installed jumper. (Wire multiple inputs in series.) Opening
any contact results in a safety shutdown and LID display.
Refer to the certified drawings for safety contact ratings.
Analog temperature sensors may also be added to the op-
tions modules, if installed. These may be programmed to ac-
tivate an alert on the CCN network, but not shut down the
chiller.
Spare Alarm Contacts — Two spare sets of alarm con-
tacts are provided in the starter. The contact ratings are pro-
vided in the certified drawings. The contacts are located on
terminal strip TB6, terminals 5A and 5B, and terminals 5C
and 5D.
IMPORTANT: A field-supplied water temperature con-
trol system for condenser water should be installed.
The system should maintain the leaving condenser wa-
ter temperature at 20° F (11° C) above the leaving chilled
water temperature.
Condenser Pump Control — The chiller monitors
the condenser pressure (CONDENSER PRESSURE param-
eter on the STATUS01 screen) and may turn on the con-
denser pump if the pressure becomes too high whenever the
compressor is shut down. The condenser pressure override
(COND PRESSURE OVERRIDE parameter on the
SERVICE1 screen) is the value that determines this pressure
point. Its default value is 125 psi (862 kPa). If the condenser
pressure is greater than or equal to the condenser pressure
override, and the entering condenser water temperature (EN-
TERING CONDENSER WATER parameter on the
STATUS01 screen) is less than 115 F (46 C), then the con-
denser pump energizes to try to decrease the pressure. The
pump turns off when the condenser pressure is 5psi (34 kPa)
less than the pressure override, or when the condenser re-
frigerant temperature (CONDENSER REFRIG TEMP on the
STATUS01 screen) is within 3° F (2° C) of the entering con-
denser water temperature.
The tower-fan relay control is not a substitute for a con-
denser water temperature control. When used with a wa-
ter temperature control system, the tower-fan relay con-
trol can be used to help prevent low condenser water
temperatures and associated problems.
Auto. Restart After Power Failure — This option,
which may be viewed or modified on the CONFIG screen
(the AUTO RESTART OPTION parameter), can be enabled
or disabled. If this option is enabled, the chiller starts up au-
tomatically after a single cycle dropout; low, high, or no volt-
age; and the power is within ±10% of normal. The
15-minute start-to-start timer and the stop-to-start timer are
ignored during this type of start-up.
When power is restored after a power failure, and if the
compressor had been running, the oil pump is energized for
one minute before the evaporator pump is energized. The
Auto. Restart function then continues like a normal start-up.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Water/Brine Reset — Three types of chilled water/
brine reset are available, Reset Type 1, Reset Type 2, and
Reset Type 3. They can be viewed or modified on the CON-
FIG screen (accessed from the EQUIPMENT CONFIGU-
RATION table). See Table 2, Example 6.
The LID default screen status message indicates when a
reset is active. The WATER/BRINE CONTROL POINT tem-
perature on the STATUS01 table indicates the chiller’s cur-
rent reset temperature.
Demand Limit Control Option (Requires
Optional 8-Input Module) — The demand limit may
be externally controlled with a 4 to 20 mA signal from an
Energy Management System (EMS). The option (20 mA DE-
MAND LIMIT OPTION) is enabled or disabled on the CON-
FIG screen (Table 2, Example 6). When enabled, the control
is set for 100% demand with 4 mA and an operator config-
ured minimum demand set point at 20 mA (DEMAND LIMIT
AT 20 mA) .
The EMS demand reset input is hardwired into the No. 1
8-input module. The signal may be internally powered by
the module or externally powered. If the signal is externally
powered, the signal is wired to terminals J1-1(+) and
J1-2(–). If the signal is internally powered, the signal is wired
to terminals J1-3(+) and J1-2(–). When enabled, the control
is set for 100% demand with 4 mA and an operator config-
ured minimum demand set point at 20 mA(DEMAND LIMIT
AT 20 mA).
To configure a reset type, input all configuration informa-
tion for that reset type on the CONFIG screen. Then activate
the reset type by entering the reset type number in the SELECT/
ENABLE RESET TYPE input line.
RESET TYPE 1 (Requires an optional 8-input module) —
Reset Type 1 is an automatic chilled water temperature reset
based on a 4 to 20 mA input signal. The value for Rest Type
1 is user configurable (DEGREES RESET AT 20 mA). It is
a temperature that corresponds to a 20 mA signal. (4 mA
corresponds to 0° F [0° C]; 20 mA corresponds to the tem-
perature entered by the operator.)
This reset type permits up to ±30° F (±16° C) of auto-
matic reset to the chilled water/brine temperature set point,
based on the input from a 4 to 20 mA signal. The signal is
hardwired into the No. 1 eight-input module.
If the 4 to 20 mA signal is externally powered from the
8-input module, the signal is wired to terminals J1-5(+) and
J1-6(–). If the signal is powered internally by the 8-input
module (for example, when using variable resistance), the
signal is wired to J1-7(+) and J1-6(–). The PIC must be
configured on the SERVICE2 screen to ensure that the
appropriate power source is identified. See Table 2,
Example 9, 20 mA POWER CONFIGURATION.
Surge Prevention Algorithm — Surge occurs when
lift conditions become so high that the gas flow across the
impeller reverses. This condition can eventually cause chiller
damage. Lift is defined as the difference between the pres-
sure at the impeller eye and the impeller discharge. The maxi-
mum lift that a particular impeller wheel can produce varies
with the gas flow across the impeller and the size of the
wheel.
The surge prevention algorithm is operator configurable
and can determine if lift conditions are too high for the com-
pressor. If they are, the PIC takes corrective action. The al-
gorithm also notifies the operator, via the LID, that chiller
operating conditions are marginal.
The surge prevention algorithm first determines if correc-
tive action is necessary. This is done by checking 2 sets of
operator configured data points: the minimum load points
(MIN. LOAD POINTS [T1/P1]) and the maximum load
points (FULL LOAD POINTS [T2/P2]). See the SERVICE1
screen or Table 2, Example 8. These points have default set-
tings. Information on how to modifiy the default minimum
and maximum load points can be found in the Input Service
Configurations section on page 54.
RESET TYPE 2 (Requires an optional 8-input module) —
Reset Type 2 is an automatic chilled water temperature reset
based on a remote temperature sensor input.
This reset type permits ±30° F (±16° C) of automatic re-
set to the set point based on a temperature sensor wired to
the No. 1 eight-input module (see wiring diagrams or cer-
tified drawings). The temperature sensor must be wired to
terminal J1-19 and J1-20.
Figures 18 and 19 graphically display these settings and
the algorithm function. The 2 sets of load points (default set-
tings) describe a line that the algorithm uses to determine
the maximum lift of the compressor. Whenever the actual
differential pressure between the cooler and condenser and
the temperature difference between the entering and leaving
chilled water are above the line on the graph (as defined by
the minimum and maximum load points) the algorithm goes
into a corrective action mode. If the actual values are below
the line, the algorithm takes no action.
Corrective action can be taken by making one of 2 choices.
If the optional hot gas bypass line is present, and the op-
erator selects the hot gas bypass option on the SERVICE1
screen (selects 1 for the SURGE LIMIT/HGBP OPTION),
then the hot gas bypass valve can be energized. If the hot gas
bypass option is not present, then the SURGE LIMIT/HGBP
OPTION is on the default setting (0), and the guide vanes
are held. (Also see Table 4, Capacity Overrides.) Both cor-
rective actions reduce the lift experienced by the compressor
and help to prevent a surge condition.
Configure Reset Type 2 on the CONFIG screen (Table 2,
Example 6). Enter the temperature of the remote sensor at
the point where no temperature reset will occur (REMOTE
TEMP [NO RESET]). Next, enter the temperature at which
the full amount of reset will occur (REMOTE TEMP [FULL
RESET]). Then, enter the maximum amount of reset re-
quired to operate the chiller (DEGREES RESET). Reset
Type 2 can now be activated.
RESET TYPE 3 — Reset Type 3 is an automatic chilled wa-
ter temperature reset based on cooler temperature differ-
ence. This reset adds ±30° F (±16° C) based on the tempera-
ture difference between entering and leaving chilled water.
Reset Type 3 is the only reset available without the need for
a No. 1 eight-input module. No wiring is required for Reset
Type 3, because it already uses the cooler water sensors.
Configure Reset Type 3 on the CONFIG screen (Table 2,
Example 6). Enter the chilled water temperature difference
(the difference between entering and leaving chilled water)
at which no temperature reset occurs (CHW DELTA T [NO
RESET]). This chilled water temperature difference is usu-
ally the full design load temperature difference. Enter the
difference in chilled water temperature at which the full
amount of reset occurs (CHW DELTA T [FULL RESET]).
Next, enter the amount of reset (DEGREES RESET). Reset
Type 3 can now be activated.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
parameter, Table 2, Example 13) can be monitored on the
MAINT03 screen. The SURGE TIME PERIOD parameter is
displayed and configured on the SERVICE1 screen. See
Table 2, Example 8. It has a default of 2 minutes.
Lead/Lag Control — Lead/lag is a control system pro-
cess that automatically starts and stops a lag or second chiller
in a 2-chiller system. Refer to Fig. 15 and 16 for menu, table,
and screen selection information. On chillers that have PSIO
software with lead/lag capability, it is possible to use the PIC
controls to perform the lead/lag function on 2 chillers. A third
chiller can be added to the lead/lag system as a standby chiller
to start up if the lead or lag chiller in the system has shut
down during an alarm condition and additional cooling is
required.
NOTE: Lead/lag parameters can be viewed and modified on
the LEAD/LAG CONFIGURATION screen, accessed from
the EQUIPMENT CONFIGURATION table. See Table 2,
Example 7. Lead/lag status during chiller operation is viewed
on the MAINT04 screen, accessed from the CONTROL
ALGORITHM STATUS table. See Table 2, Example 14.
LEGEND
⌬P = (Condenser psi) − (Cooler psi)
⌬T = (ECW) − (LCW)
Lead/Lag System Requirements:
ECW
HGBP
LCW
—
—
—
Entering Chilled Water
Hot Gas Bypass
Leaving Chilled Water
• all chillers must have PSIO software capable of perform-
ing the lead/lag function
• water pumps MUST be energized from the PIC controls
• water flows should be constant
Fig. 18 — 17EX Hot Gas Bypass/Surge
Prevention With Default Settings (English)
• CCN Time Schedules for all chillers must be identical
Operation Features:
• 2 chiller lead/lag
• addition of a third chiller for backup
• manual rotation of lead chiller
• load balancing if configured
• staggered restart of the chillers after a power failure
• chillers may be piped in parallel or in series chilled water
flow
COMMON POINT SENSOR INSTALLATION — Lead/
lag operation does not require a common chilled water point
sensor. Common point sensors can be added to the 8-input
option module, if desired. Refer to the certified drawings for
termination of sensor leads.
NOTE: If the common point sensor option is chosen on a
chilled water system, each chiller should have its own 8-input
option module and common point sensor installed. A chiller
uses its own common point sensor for control when that chiller
is designated as the lead chiller. The PIC cannot read the
value of common point sensors installed on other chillers in
the chilled water system.
When installing chillers in series, use a common point sen-
sor. If a common point sensor is not used, the leaving chilled
water sensor of the upstream chiller must be moved into the
leaving chilled water pipe of the downstream chiller.
If return chilled water control is required on chillers piped
in series, the common point return chilled water sensor should
be installed. If this sensor is not installed, the return chilled
water sensor of the downstream chiller must be relocated to
the return chilled water pipe of the upstream chiller.
LEGEND
⌬P = (Condenser kPa) − (Cooler kPa)
⌬T = (ECW) − (LCW)
ECW
HGBP
LCW
—
—
—
Entering Chilled Water
Hot Gas Bypass
Leaving Chilled Water
Fig. 19 — 17EX Hot Gas Bypass/Surge Prevention
With Default Settings (SI)
Surge Protection — Compressor surge can be de-
tected by the PIC based on operator configured settings. Surge
causes amperage fluctuations of the compressor motor. The
PIC monitors these amperage swings, and if the swing is
greater than the configured setting (SURGE DELTA
PERCENT AMPS) in one second, then one surge event has
occurred. The setting is displayed and configured on the
SERVICE1 screen. Its default setting is 25% amps.
A surge protection chiller shutdown occurs when the surge
protection counter reaches 12 within an operator specified
time period, known as the surge time period. The
surge protection count (SURGE PROTECTION COUNTS
To properly control the common supply point temperature
sensor when chillers are piped in parallel, the water flow through
the shutdown chiller(s) must be isolated so there is no water
bypass around the operating chiller. The common point sen-
sor option must not be used if water bypass around the op-
erating chiller is occurring.
CHILLER COMMUNICATION WIRING — Refer to the
chiller Installation Instructions and the Carrier Comfort Net-
work Interface section on page 53 of this manual for infor-
mation on chiller communication wiring.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
LEAD/LAG OPERATION — The PIC control has the ca-
pability to operate 2 chillers in the lead/lag mode. It also has
the additional capability to start a designated standby
chiller when either the lead or lag chiller is not operating
and capacity requirements are not being met. The lead/lag
option operates in CCN mode only. If any other chiller con-
figured for lead/lag is set to the LOCAL or OFF modes, it
will be unavailable for lead/lag operation.
NOTE: Lead/lag configuration is viewed and edited on the
LEAD/LAG screen, accessed from the EQUIPMENT CON-
FIGURATION table of the SERVICE menu. See Table 2,
Example 7. Lead/lag status during chiller operation is viewed
on the MAINT04 screen, accessed from the CONTROL AL-
GORITHM STATUS table. See Table 2, Example 14.
Standby Chiller Configuration and Operation — The con-
figured standby chiller is identified as such by having its LEAD/
LAG SELECT parameter assigned a value of 3. The standby
chiller can only operate as a replacement for the lag chiller
if one of the other two chillers is in an alarm (*) condition
(as indicated on the LID panel). If both lead and lag chillers
are in an alarm (*) condition, the standby chiller defaults to
operate in CCN mode based on its configured occupancy sched-
ule and remote contacts input.
Lag Chiller Start-Up Requirements — Before the lag chiller
can be started, the following conditions must be met.
1. Lead chiller ramp loading must be completed.
2. Lead chiller’s chilled water temperature must be
greater than the WATER/BRINE CONTROL POINT (STA-
TUS01 screen) plus half the WATER/BRINE DEAD-
BAND (SERVICE1 screen).
Lead/Lag Chiller Configuration and Operation — A chiller
is designated the lead chiller when the LEAD/LAG
SELECT parameter for that chiller is set to 1 on the LEAD/
LAG CONFIGURATION screen. A chiller is designated the
lag chiller when the LEAD/LAD SELECT parameter for that
chiller is set to 2. A chiller is designated the standby chiller
when the LEAD/LAG SELECT parameter for that chiller is
set to 3. Setting the LEAD/LAG SELECT parameter to 0 dis-
ables the lead/lag function in that chiller.
To configure the LAG ADDRESS parameter on the LEAD/
LAG CONFIGURATION screen, always use the address of
the other chiller on the system. Using this address makes it
easier to rotate the lead and lag chillers.
NOTE: The chilled water temperature sensor may be the
leaving chilled water sensor, the return water sensor, the
common supply water sensor, or the common return wa-
ter sensor, depending on which options are configured and
enabled.
3. Lead chiller ACTIVE DEMAND LIMIT (STATUS01
screen) value must be greater than 95% of full load amps.
4. Lead chiller temperature pulldown rate (TEMP PULL-
DOWN DEG/MIN on the CONFIG screen) of the chilled
water temperature is less than 0.5° F (0.27° C) per minute.
5. The lag chiller status indicates it is in CCN mode and is
not faulted. If the current lag chiller is in an alarm con-
dition, then the standby chiller becomes the active lag chiller,
if it is configured and available.
6. The configured time for the LAG START TIMER param-
eter has elapsed. The lag start timer starts when the lead
chiller ramp loading is completed. The LAG START TIMER
parameter is on the LEAD/LAG screen, which is ac-
cessed from the EQUIPMENT CONFIGURATION table.
See Table 2, Example 7.
If improper address assignments are entered for the LAG
ADDRESS and STANDBY ADDRESS parameters, the
lead/lag is disabled and an alert (!) message displays on the
LID. For example, if the lag chiller’s address matches the
lead chiller’s address, the lead/lag function is disabled and
an alert (!) message displays. The lead/lag maintenance screen
(MAINT04) displays the message INVALID CONFIG in the
LEAD/LAG CONFIGURATION and CURRENT MODE fields.
The lead chiller responds to normal start/stop controls such
as occupancy schedule, forced start/stop, and remote start
contact inputs. After completing start-up and ramp loading,
the PIC evaluates the need for additional capacity. If addi-
tional capacity is needed, the PIC initiates the start-up of the
chiller configured at the lag address. If the lag chiller is faulted
(in alarm) or is in the OFF or LOCAL modes, then the chiller
at the standby address (if configured) is requested to start.
After the second chiller is started and is running, the lead
chiller monitors conditions and evaluates whether the ca-
pacity has been reduced enough for the lead chiller to sus-
tain the system alone. If the capacity is reduced enough for
the lead chiller to sustain the control point temperatures alone,
then the operating lag chiller is stopped.
If the lead chiller is stopped in CCN mode for any reason
other than an alarm (*) condition, then the lag and standby
chillers are stopped. If the configured lead chiller stops for
an alarm condition, then the configured lag chiller takes the
lead chiller’s place as the lead chiller and the standby chiller
serves as the lag chiller.
If the configured lead chiller does not complete the start-up
before the PRESTART FAULT TIMER (a user configured pa-
rameter on the LEAD/LAG screen) elapses, then the lag chiller
is started and the lead chiller shuts down. The lead chiller
then monitors the request to start from the acting lead chiller.
The pre-start fault timer is initiated at the time of a start re-
quest. This timer’s function is to provide a time-out if there
is a pre-start alert condition that prevents the chiller from
starting in a timely manner.
When all the above requirements have been met, the lag
chiller is forced to a STARTUP mode. The PIC control then
monitors the lag chiller for a successful start. If the lag chiller
fails to start, the standby chiller, if configured, is started.
Lag Chiller Shutdown Requirements — The following con-
ditions must be met in order for the lag chiller to be stopped.
1. Lead chiller COMPRESSOR MOTOR LOAD (STA-
TUS01 screen) value is less than the lead chiller percent
capacity plus 15%. See STATUS01 screen or Table 2,
Example 1.
NOTE: Lead chiller percent capacity = 100 – LAG PER-
CENT CAPACITY.
The LAG PERCENT CAPACITY value is configured on
the LEAD/LAG CONFIGURATION screen.
2. The lead chiller chilled water temperature is less than
the WATER/BRINE CONTROL POINT plus 1/2 of the
WATER/BRINE DEADBAND. The WATER/BRINE DEAD-
BAND parameter is on the SERVICE1 screen. See
Table 2, Example 8.
3. The configured lag stop time (LAG STOP TIMER param-
eter on the LEAD/LAG CONFIGURATION screen) has
elapsed. The lag start time starts when the LEAVING
CHILLED WATER temperature is less than the WATER/
BRINE CONTROL POINT plus 1/2 of the WATER/
BRINE DEADBAND, and the lead chiller COMPRESSOR
MOTOR LOAD is less than the lead chiller percent ca-
pacity plus 15%. The lag stop timer is ignored if the chilled
water temperature reaches 3° F (1.67° C) below the WATER/
BRINE CONTROL POINT and the lead chiller COM-
PRESSOR MOTOR LOAD value is less than the lead chiller
percent capacity plus 15%.
If the lag chiller does not achieve start-up before the
pre-start fault time elapses, then the lag chiller is stopped
and the standby chiller is requested to start, if configured
and ready.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
FAULTED CHILLER OPERATION — If the lead chiller
shuts down because of an alarm (*) condition, it stops com-
municating with the lag and standby chillers. After 30 sec-
onds, the lag chiller becomes the acting lead chiller and starts
and stops the standby chiller, if necessary.
If the lag chiller faults when the lead chiller is also faulted,
the standby chiller reverts to a stand-alone CCN mode of
operation.
build period, the WATER/BRINE CONTROL POINT is set to
the ICE BUILD SETPOINT (SETPOINT screen) for tem-
perature control.
The ICE BUILD RECYCLE OPTION and ICE BUILD
TERMINATION parameters are on the CONFIG screen. The
ice build recycle option can be enabled or disabled from this
screen; the ice build termination value can be set to 0, 1, or
2, depending on the factor that determines termination (tem-
perature, contacts, or both). Ice build termination can occur
when:
• the ENTERING CHILLED WATER temperature is less than
the ICE BUILD SETPOINT
• the REMOTE CONTACTS INPUT (STATUS01 screen) is
opened based on input from an ice level indicator
• the end of the ice build time schedule has been reached.
If the lead chiller is in an alarm (*) condition (indicated
on the LID ), the RESET softkey is pressed to clear the
alarm, and the lead chiller is placed in CCN mode, the lead
chiller communicates and monitors the run status of the lag
and standby chillers. If both the lag and standby chillers are
running, the lead chiller does not attempt to start and does
not assume the role of lead chiller until either the lag or standby
chiller shuts down. If only one chiller is running, the lead
chiller waits for a start request from the operating chiller.
When the configured lead chiller starts, it assumes its role of
lead chiller.
LOAD BALANCING — When the LOAD BALANCE OP-
TION (LEAD/LAG screen) is enabled, the lead chiller sets
the ACTIVE DEMAND LIMIT in the lag chiller to the lead
chiller’s COMPRESSOR MOTOR LOAD value. This value
has limits of 40% to 100%. When setting the lag chiller AC-
TIVE DEMAND LIMIT, the WATER/BRINE CONTROL POINT
is modified to a value of 3° F (1.67° C) less than the lead
chiller’s WATER/BRINE CONTROL POINT value. If the LOAD
BALANCE OPTION is disabled, the ACTIVE DEMAND LIMIT
and the WATER/BRINE CONTROL POINT are forced to the
same value as the lead chiller.
ICE BUILD INITIATION — The ice build option is acti-
vated via the ice build time schedule on the OCCPC02S screen.
If the current time is set as an ice build time on the OCCPC02S
screen and the ICE BUILD OPTION on the CONFIG screen
is enabled, then the ice build option is active and the fol-
lowing events automatically take place (unless overridden
by a higher authority CCN device):
1. CHILLER START/STOP is forced to START.
2. The WATER/BRINE CONTROL POINT is forced to the
ICE BUILD SETPOINT.
3. Any force (Auto) on the ACTIVE DEMAND LIMIT is
removed.
NOTE: Items 1-3 (shown above) do not occur if the chiller
is configured and operating as a lag or standby chiller for
lead/lag operation and is actively controlled by a lead chiller.
The lead chiller communicates the ICE BUILD SETPOINT,
desired CHILLER START/STOP state, and ACTIVE DE-
MAND LIMIT to the lag or standby chiller as required for
ice build, if configured to do so.
AUTO. RESTART AFTER POWER FAILURE — When an
auto. restart condition occurs, each chiller may have a delay
added to the start-up sequence, depending on its lead/lag con-
figuration. The lead chiller does not have a delay. The lag
chiller has a 45-second delay. The standby chiller has a
90-second delay. The delay time is added after the chiller
water flow verification. The PIC controls ensure that the guide
vanes are closed. After the guide vane position is confirmed,
the delay for lag and standby chillers occurs before ener-
gizing the oil pump. The normal start-up sequence then con-
tinues. The auto. restart delay sequence occurs whether the
chiller is in CCN or LOCAL mode and is intended to stag-
ger the compressor motor start-up times. This helps reduce
the in-rush of demand on the building power system.
START-UP/RECYCLE OPERATION — If the chiller is not
running when ice build activates, then the PIC checks the
following parameters, based on the ICE BUILD
TERMINATION value, to avoid starting the compressor
unnecessarily:
• if the ICE BUILD TERMINATION parameter is set to 0
(temperature only), and the ENTERING CHILLED WA-
TER temperature is less than or equal to the ICE BUILD
SETPOINT;
Ice Build Control — Ice build control automatically sets
the chilled WATER/BRINE CONTROL POINT of the chiller
from a normal operation set point temperature to a tempera-
ture that allows an ice building operation for thermal
storage.
NOTE: For ice build control to operate properly, the PIC
controls must be placed in CCN mode.
• if the ICE BUILD TERMINATION parameter is set to 1
(contacts only) and the remote contacts are open;
• if the ICE BUILD TERMINATION parameter is set to 3
(both temperature and contacts), the ENTERING CHILLED
WATER temperature is less than or equal to the ICE BUILD
SETPOINT, and the remote contacts are open.
The ICE BUILD RECYCLE OPTION determines whether
or not the PIC goes into a RECYCLE mode. If the ICE BUILD
RECYCLE OPTION is set to DSABLE (disable) when the
ice build terminates, the PIC reverts to normal temperature
control duty. If the ICE BUILD RECYCLE OPTION is set to
ENABLE, when ice build terminates, the PIC goes into an
ice build recycle mode and the chilled water pump relay re-
mains energized to keep the chilled water flowing. If the EN-
TERING CHILLED WATER (brine) temperature increases above
the ICE BUILD SETPOINT plus the RECYCLE RESTART
DELTA T value, the compressor restarts and controls the chilled
water/brine temperature to the ICE BUILD SETPOINT.
The PIC can be configured for ice build operation by chang-
ing entries on the:
• CONFIG screen, accessed from the SERVICE menu
• OCCPC02S screen (ice build time schedule), accessed from
the SCHEDULE menu
• SETPOINT screen, accessed from the SETPOINT menu.
Figures 15 and 16 show how to access each screen.
The ice build time schedule defines the periods during which
the ice build option can be activated, if the ice build option
is enabled. If the ice build time schedule overlaps other sched-
ules, the ice build time schedule takes priority. During an ice
40
Download from Www.Somanuals.com. All Manuals Search And Download.
TEMPERATURE CONTROL DURING ICE BUILD
—During ice build, the capacity control algorithm uses the
WATER/BRINE CONTROL POINT minus 5 F (2.7 C) to con-
trol the LEAVING CHILLED WATER temperature. The ECW
CONTROL OPTION (see CONFIG screen), the 20 mA
DEMAND LIMIT, and any temperature reset option are ig-
nored during ice build.
Figure 20 shows the ATTACH TO NETWORK DEVICE
table as it appears on the LID. The LOCAL entry is always
the PSIO module address of the chiller the LID is mounted
on. Whenever the controller identification of the PSIO is
changed, this change is reflected on the bus and address for
the LOCAL DEVICE of the ATTACH TO DEVICE screen
automatically.
TERMINATION OF ICE BUILD — Ice build termination
occurs under the following conditions:
NAME DESCRIPTOR
1. Ice Build Time Schedule — The ice build function ter-
minates when the current time is not designated as an ice
build time period.
2. Entering Chilled Water Temperature — Compressor op-
eration terminates based on temperature if the ICE BUILD
TERMINATION parameter on the CONFIG screen is set
to 0 (temperature only) and the ENTERING CHILLED
WATER temperature is less than the ICE BUILD SET-
POINT. If the ICE BUILD RECYCLE OPTION is set to
ENABLE, a recycle shutdown occurs and recycle start-
up is based on a LEAVING CHILLED WATER tempera-
ture greater than the WATER/BRINE CONTROL POINT
plus RECYCLE RESTART DELTA T (see SERVICE1
screen).
3. Remote Contacts/Ice Level Input — Compressor opera-
tion terminates when the ICE BUILD TERMINATION pa-
rameter is set to 1 (contacts only) and the remote contacts
are open. In this case, the contacts are used for ice level
termination control. The remote contacts can still be opened
and closed to start and stop the chiller if the current time
is not a time designated as an ice build period. If the cur-
rent time is designated as an ice build period, the contacts
are used to stop the ice build function.
Fig. 20 — Example of Attach to Network
Device Screen
Whenever the ATTACH TO NETWORK DEVICE table
is accessed, no information can be read from the LID on any
device until you attach one of the devices listed on the dis-
play. As soon as this screen appears, the LID erases infor-
mation about the module to which it was attached to make
room for information on another device. Therefore, a CCN
module must be attached when this screen is entered.
To attach to a device listed on this screen, highlight it us-
ing the SELECT softkey. Then press the ATTACH soft-
key. The message, UPLOADING TABLES, PLEASE WAIT,
flashes. The LID then uploads the highlighted device or mod-
ule. If the device address cannot be found, the message, COM-
MUNICATION FAILURE, appears. The LID then reverts to
the ATTACH TO NETWORK DEVICE screen. Try another
device or check the address of the device that did not attach.
The upload process time for each CCN module is different.
In general, the uploading process takes 3 to 5 minutes.
4. Entering Chilled Water Temperature and Remote Con-
tacts — Compressor operation terminates when the ICE
BUILD TERMINATION parameter is set to 2 (both tem-
perature and contacts) and the previously described con-
ditions for ENTERING CHILLED WATER temperature and
remote contacts have occurred.
NOTE: Before leaving the ATTACH TO NETWORK DE-
VICE screen, select the LOCAL device. Otherwise, the LID
will be unable to display information on the local chiller.
NOTE: Overriding the CHILLER START/STOP, WATER/
BRINE CONTROL POINT, and ACTIVE DEMAND LIMIT
values by CCN devices (with a priority less than 4) during
the ice build period is not possible. However, overriding can
be accomplished with CCN during two-chiller lead/lag
operation.
ATTACHING TO OTHER CCN MODULES — If the chiller
PSIO has been connected to a CCN network or other PIC
controlled chillers through CCN wiring, the LID can be used
to view or change parameters on the other controllers. Other
PIC chillers can be viewed and set points changed (if the
other unit is in CCN control) if desired from this particular
LID module.
To view the other devices, access the ATTACH TO
NETWORK DEVICE table. Move the highlight bar to any
device number. Press the SELECT softkey to change to the
bus number and address of the module to be viewed. Press
the ENTER softkey. Press the EXIT softkey to return to
RETURN TO NON-ICE BUILD OPERATIONS — When
the ice build function terminates, the chiller returns to nor-
mal temperature control and start/stop schedule operation. If
the CHILLER START/STOP or WATER/BRINE CONTROL
POINT has been forced (with a priority less than 4), before
the start of ice build operation, then CHILLER START/STOP
and WATER/BRINE CONTROL POINT forces are removed;
that is, under these circumstances, the ice build operation
takes precedence over the force.
the ATTACH TO NETWORK DEVICE table. If the device
number is not valid, the message, COMMUNICATION FAIL-
URE, displays. Enter a new address number or check the
wiring. If the device is communicating properly, the mes-
sage, UPLOAD IN PROGRESS, displays and the new de-
vice can now be viewed.
Whenever there is a question regarding which CCN de-
vice the LID is currently showing, check the device name
descriptor on the upper left hand corner of the LID screen.
See Fig. 20.When the CCN device has been viewed, use the
ATTACH TO NETWORK DEVICE table to attach to the
PSIO that is on the chiller. From the ATTACH TO NET-
WORK DEVICE table , highlight LOCAL, and press the
Attach to Network Device Control — One of the
selections on the SERVICE menu is ATTACH TO NET-
WORK DEVICE. See Fig. 12. This table serves the follow-
ing purposes:
• uploads the occupancy schedule number (OCCPC03S), if
changed, as defined in the CONFIG screen (SCHEDULE
NUMBER).
• attaches the LID to any CCN device, if the chiller has been
connected to a CCN network. This may include other PIC
controlled chillers.
• uploads changes from a new PSIO or LID module or up-
graded software.
SELECT softkey. Then, press the ATTACH softkey to up-
load the LOCAL device. The PSIO will upload.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: The LID does not automatically re-attach to the PSIO
module on the chiller. Access the ATTACH TO NETWORK
DEVICE table, scroll to LOCAL, and press the
EF, EX, FA CHLR HOLDY01S CONF IGURATION SELECT
ATTACH softkey to upload the local device. The software
for the local chiller will now be uploaded.
Service Operation — Figure 16 shows an overview of
the service menu.
TO ACCESS THE SERVICE SCREENS
1. On the MENU screen, press the SERVICE softkey. The
softkeys now correspond to the numerals 1, 2, 3, and 4.
NOTE: The factory-set password is 1 - 1 - 1 - 1. See the
Input Service Configurations section, page 54, for informa-
tion on how to change a password.
2. Press the four digits of your password, one at a time. An
asterisk (*) appears as you enter each digit.
Fig. 21 — Example of Holiday Period Screen
If the password is incorrect, an error message is dis-
played. If this occurs, return to Step 1 and try to access
the SERVICE tables again. If the password is correct, the
To view or change the holiday periods for up to 18 dif-
ferent holidays, perform the following operation:
softkey labels change to NEXT
,
PREVIOUS
,
1. At the Menu screen, press SERVICE to access the
SERVICE menu.
SELECT , and EXIT , and the LID screen displays the
following SERVICE tables:
• Alarm History
• Control Test
• Control Algorithm Status
• Equipment Configuration
• Equipment Service
2. If not logged on, follow the instructions for entering your
password. See the section, To Access the Service Screens,
page 42. Once logged on, press NEXT until
• Time and Date
• Attach to Network Device
• Log Out of Device
• Controller Identification
• LID Configuration
EQUIPMENT CONFIGURATION is highlighted.
See Fig. 16 for additional screens and tables available form
the SERVICE tables listed above. Use the EXIT softkey to
return to the MENU screen.
3. Press the SELECT softkey to access the EQUIP-
MENT CONFIGURATION tables.
TO LOG OFF — Access the LOG OUT OF DEVICE table
from the SERVICE menu. The LID exits the SERVICE menu.
To re-enter the SERVICE menu, you must re-enter your pass-
word as described above.
NOTE: To prevent unauthorized persons from accessing the
LID service screens, the LID automatically signs off and
password-protects itself if a key has not been pressed for
15 minutes. The sequence is as follows. Fifteen minutes af-
ter the last key is pressed, the default screen displays, the
LID screen light goes out (analogous to a screen saver), and
the LID logs out of the password-protected SERVICE menu.
Other screens and menus, such as the STATUS screen can
be accessed without the password by pressing the appropri-
ate softkeys.
4. Press NEXT until HOLIDEF is highlighted. This is
the holiday definition table.
5. Press SELECT to access the HOLIDEF screen.
This screen lists 18 holiday tables.
HOLIDAY SCHEDULING (Fig. 21) — The time schedules
may be configured for special operation during holiday pe-
riods. When modifying a time period, an ‘‘H’’ at the end of
the days of the week field signifies that the period is appli-
cable to a holiday. (See Fig. 14.)
The broadcast function must be activated for the holidays
configured on the HOLIDEF screen to work properly. Ac-
cess the BRODEF screen from the EQUIPMENT CON-
FIGURATION table and set the parameter that activates the
BRODEF function to YES. Note that, when the chiller is
connected to a CCN network, only one chiller or CCN de-
vice can be configured to be the broadcast device. The con-
troller that is configured to be the broadcaster is the device
responsible for transmitting holiday, time, and daylight-
savings dates throughout the network.
6. Press NEXT to highlight the holiday table that you
wish to view or change. Each table is one holiday pe-
riod, starting on a specific date, and lasting up to 99 days.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
If the checks are successful, the chilled water/brine pump
relay is energized. Five seconds later, the condenser pump
relay is energized. One minute later the PIC monitors the
chilled water and condenser water flow switches, and waits
until the WATER FLOW VERIFY TIME (operator config-
ured, default 5 minutes) to confirm flow. See the SERVICE1
screen or Table 2, Example 8. After flow is verified, the chilled
water/brine temperature is compared to WATER/BRINE CON-
TROL POINT plus DEADBAND. If the temperature is less
than or equal to this value, the PIC turns off the condenser
pump relay and goes into a RECYCLE mode.
7. Press SELECT to access the holiday table. The LID
screen now shows the holiday start month and day, and
how many days the holiday period will last. See Fig. 24.
8. Press NEXT or PREVIOUS to highlight HOLIDAY
START MONTH, START DAY, or DURATION.
If the water/brine temperature is high enough, the start-up
sequence continues and checks the guide vane position. If
the guide vanes are more than 6% open, the start-up waits
until the PIC closes the vanes. If the vanes are closed, and
the oil pump pressure is less than 3 psid (21 kPad), the oil
pump relay is then energized. The PIC then waits a mini-
mum of 15 seconds (maximum 5 minutes) to verify that the
compressor oil pressure (OIL PRESSURE on the STA-
TUS01 screen) has reached 15 psid (103 kPad). At the same
time, the PIC waits up to 30 seconds to verify that the gear
oil pressure (GEAR OIL PRESSURE on the STATUS04
screen) has reached 24 psi (166 kPa). After the oil pressures
are verified, the PIC waits 10 seconds, and then the
compressor start relay (1CR) is energized to start the
compressor.
9. Press SELECT to modify the month, day, or
duration.
10. Press INCREASE or DECREASE to change the se-
lected value.
11. Press ENTER to save the changes.
12. Press EXIT to return to the previous menu.
LEGEND
START-UP/SHUTDOWN/
RECYCLE SEQUENCE (Fig. 22)
A
—
START INITIATED — Prestart checks made; chilled water
pump started.
Condenser water pump started (5 seconds after A).
Water flows verified (one minute to 5 minutes maximum
afterA). Chilled water temperature checked against control point.
Guide vanes checked for closure. Oil pumps started; tower fan
control enabled.
Oil pressure verified (for compressor, 15 seconds minimum,
300 seconds maximum, after C; for gear, within 30 seconds
after C).
Compressor motor starts, compressor ontime and service
ontime starts, 15-minute inhibit timer starts (10 seconds
after D). Start-in-12 hours counter advances by one.
SHUTDOWN INITIATED — Compressor motor stops, guide
vanes close, compressor ontime and service ontime stops, stop-
to-start inhibit timer starts.
B
C
—
—
Local Start-Up — Local start-up (or a manual start-up)
is initiated by pressing the LOCAL menu softkey which is
on the default LID screen. Local start-up can proceed if the
OCCUPIED ? parameter on the STATUS01 table is set to
YES and after the internal 15-minute start-to-start timer and
the stop-to-start inhibit timer have expired.
The CHILLER START/STOP parameter on the STA-
TUS01 screen may be overridden to start, regardless of the
time schedule, in order to start the chiller locally. Also, the
remote contacts may be enabled through the LID and closed
to initiate a start-up.
Whenever the chiller is in LOCAL control mode, the PIC
waits for the current time to coincide with an occupied time
period as configured in the local time schedule (OCCPC01S)
and for the remote contacts to close, if enabled. The PIC
then performs a series of pre-start checks to verify that all
pre-start alerts and safeties are within the limits shown in
Table 3. The RUN STATUS line on the STATUS01 screen
now reads STARTUP.
D
—
—
—
—
—
E
F
G
After the post-lube period, oil and evaporator pumps deener-
gized. Post-lube configurable to between one and 5 minutes
after Step F.
Restart permitted (both inhibit timers expired) (minimum of
15 minutes after E; minimum of 1 minute after F).
O/A
Fig. 22 — Control Sequence
43
Download from Www.Somanuals.com. All Manuals Search And Download.
If any of these requirements are not met, the PIC aborts
the start and displays the applicable pre-start mode of failure
on the LID default screen. A pre-start failure does not ad-
vance the STARTS IN 12 HOURS counter (STATUS01 screen).
Any failure after the 1CR relay has energized causes a safety
shutdown, advances the STARTS IN 12 HOURS counter by
one, and displays the applicable shutdown status on the LID
display.
When the automatic soft stop amps threshold is being ap-
plied, a status message, SHUTDOWN IN PROGRESS, COM-
PRESSOR UNLOADING, displays.
Chilled Water Recycle Mode — When the compres-
sor is running under light load conditions, the chiller
may cycle off and wait until the load increases to restart
again. This cycling is normal and is known as recycle. A
recycle shutdown is initiated when any of the following
occurs:
• when the chiller is operating under the control of the leav-
ing chilled water temperature (that is, when the ECW CON-
TROL OPTION on the CONFIG screen is disabled), the
difference between the LEAVING CHILLED WATER tem-
perature and ENTERING CHILLED WATER temperature
is less than the RECYCLE SHUTDOWN DELTA T (found
in the SERVICE1 table) and the LEAVING CHILLED WA-
TER TEMP is below the WATER/BRINE CONTROL POINT,
and the WATER/BRINE CONTROL POINT has not in-
creased in the last 5 minutes
• when the chiller is operating under the control of the en-
tering chilled water temperature (that is, the ECW CON-
TROL OPTION is enabled), the difference between the
ENTERING CHILLED WATER temperature and the LEAV-
ING CHILLED WATER temperature is less than the
RECYCLE SHUTDOWN DELTA T (found in the SERV-
ICE1 table) and the ENTERING CHILLED WATER tem-
perature is below the WATER/BRINE CONTROL POINT,
and the WATER/BRINE CONTROL POINT has not in-
creased in the last 5 minutes
Shutdown Sequence — The chiller shuts down if any
of the following occurs:
• the STOP button on the control panel is pressed for at least
one second. The alarm light blinks once to confirm the
stop command.
• a recycle condition is present (see Chilled Water Recycle
Mode section).
• the OCCUPIED ? parameter on the STATUS01 screen reads
NO; that is, the chiller is not scheduled to run at the cur-
rent time and date.
• the remote contact opens.
• the CHILLER START/STOP status is overridden to STOP
from the CCN network or the LID.
When a stop signal occurs, the shutdown sequence first
stops the compressor by deactivating the start relay. A status
message, SHUTDOWN IN PROGRESS, COMPRESSOR
DEENERGIZED, displays. The guide vanes are then brought
to the closed position. The oil pump relay and the chilled
water/brine pump relay are shut down 60 seconds after the
compressor stops. The condenser water pump shuts down
when the condenser refrigerant temperature is less than the
condenser pressure override minus 5 psi (34 kPa) or is less
than or equal to the entering condenser water temperature
plus 3° F (2° C). The stop-to-start timer now begins to count
down. If the value of the start-to-start timer is still greater
than the value of the start-to-stop timer, then the start-to-
start time is displayed on the LID.
There are certain conditions during shutdown that can change
this sequence:
• if the COMPRESSOR MOTOR LOAD (STATUS01 screen)
is greater than 10% after shutdown or the starter contacts
remain energized, the oil pump and chilled water pump
remain energized and the alarm is displayed
• when the LEAVING CHILLED WATER temperature is within
3° F (2° C) of the BRINE REFRIG TRIPPOINT.
(See the SERVICE1 screen.)
When the chiller is in RECYCLE mode, the chilled water
pump relay remains energized so that the chilled water tem-
perature can be monitored for increasing load. The recycle
control uses the RECYCLE RESTART DELTA T value
to check when the compressor should be restarted. This is an
operator-configured value that defaults to 5° F (3° C). The
value can be viewed/modified on the SERVICE1 screen. The
compressor restarts when:
• the chiller is operating under leaving chilled water tem-
perature control and the LEAVING CHILLED WATER
temperature is greater than the WATER/BRINE CON-
TROL POINT plus the RECYCLE RESTART DELTA T; or
• the chiller is operating under entering chilled water tem-
perature control and the ENTERING CHILLED WATER
temperature is greater than the WATER/BRINE CON-
TROL POINT plus the RECYCLE RESTART DELTA T.
Once these conditions are met, the compressor initiates a
start-up, with a normal start-up sequence.
An alert condition may be generated if 5 or more recycles
occur in less than 4 hours. Because excessive recycling can
reduce chiller life, compressor recycling caused by ex-
tremely low loads should be reduced. To accomplish this,
use the time schedule to shut the chiller down during periods
of known low load operation or increase the chiller load by
running the fan systems. If the hot gas bypass is installed,
adjust the values to ensure that hot gas is energized during
light load conditions. Increase the RECYCLE RESTART DELTA
T value on the SERVICE1 screen to lengthen the time be-
tween restarts.
• if the ENTERING CONDENSER WATER (STATUS01 screen)
temperature is greater than 115 F (46 C) at shutdown, the
condenser pump is deenergized after the 1CR compressor
start relay
• if the chiller shuts down due to low refrigerant tempera-
ture, the chilled water pump keeps running until the LEAV-
ING CHILLED WATER temperature is greater than the
WATER/BRINE CONTROL POINT plus 5° F (3° C).
Automatic Soft Stop Amps Threshold — The au-
tomatic soft stop amps threshold is an operator configured
value that closes the guide vanes of the compressor auto-
matically when a non-recycle, non-alarm stop signal occurs
before the compressor motor is deenergized.
If the STOP button on the control panel is pressed, the
guide vanes close to a preset amperage percent or until the
guide vane is less than 2% open. The compressor then shuts
off.
If the chiller enters an alarm state or if the compressor
enters a RECYCLE mode, the compressor is deenergized
immediately.
To activate the automatic soft stop amps threshold, access
the SERVICE1 screen. Set the SOFT STOP AMPS THRESH-
OLD parameter value to the percent of amps at which the
motor will shut down. The default setting is 100% amps (no
soft stop).
The chiller should not be operated below design mini-
mum load without a hot gas bypass installed on the
chiller.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Shutdown — A safety shutdown is identical to
a manual shutdown with the exception that the LID displays
the reason for the shutdown, the alarm light blinks continu-
ously, and the spare alarm contacts are energized. A safety
Remove Shipping Packaging — Remove any pack-
aging material from the control center, power panel, guide
vane actuator, motor and bearing temperature sensor covers,
and the factory-mounted starter.
shutdown requires that the RESET softkey be pressed in
order to clear the alarm. If the alarm continues, the alarm
light continues to blink. Once the alarm is cleared, the op-
MOTOR
erator must press the CCN or LOCAL softkeys to restart
the chiller.
The motor may be provided with a shipping brace or
shipping bolt (normally painted yellow) to prevent shaft
movement during transit. It must be removed prior to
operation. See Fig. 24.
Do not reset starter loads or any other starter safety for
30 seconds after the compressor has stopped. Voltage
output to the compressor start signal is maintained for
10 seconds to determine starter fault.
BEFORE INITIAL START-UP
Job Data Required
• list of applicable design temperatures and pressures (prod-
uct data submittal)
• certified drawings of the chiller
• starting equipment details and wiring diagrams
• diagrams and instructions for special controls or options
• installation instructions
• pumpout unit instructions
Equipment Required
Fig. 24 — Shipping Bolt on Open Drive Motor
• mechanic’s tools (refrigeration)
• digital volt-ohmmeter (DVM)
The motor should be inspected for any temporary, yellow
caution tags with legends that convey information concern-
ing actions necessary before the motor can be safely oper-
ated. Any slushing compound on the shaft or other parts must
be removed using a petroleum type solvent. Observe proper
safety precautions.
• clamp-on ammeter
• electronic leak detector
• absolute pressure manometer or wet-bulb vacuum indica-
tor (Fig. 23)
• 500 v insulation tester (megohmmeter) for compressor mo-
tors with nameplate voltage of 600 v or less, or a
5000 v insulation tester for compressor motor rated above
600 v
NOTE: If a shipping bolt was used to restrain the rotor, the
Westinghouse logo must be installed over the hole in the end-
cover. The logo, the gasket, and hardware can be found with
the parts that have been shipped loose. (Usually these are
packed inside the main power lead box.)
EXTERNAL GEAR — Remove any packaging material that
may be on the external gear. Be sure that the breather is in
place and free of any obstructions.
Motor Electrical Connection — All interconnect-
ing wiring for controls and grounding should be in strict com-
pliance with both the (NEC) National Electrical Code and
any local requirements.
The main lead box furnished with the motor has been sized
to provide adequate space for making up connections be-
tween the motor lead cables and the incoming power cables.
The bolted joints between the motor lead and the power cables
must be made and insulated in a workman-like manner fol-
lowing the best trade practices.
Fabricated motors are provided with 2 stainless steel ground-
ing pads drilled and tapped with the NEMA (National Elec-
trical Manufacturers Association) 2-hole pattern (two 1⁄2-13
tapped holes on 13⁄4 in. centers). Fan cooled cast frames are
provided with a special grounding bolt. The motor should be
grounded by a proper connection to the electrical system ground.
Fig. 23 — Typical Wet-Bulb Type
Vacuum Indicator
Using the Economizer/Storage Vessel and Pump-
out System — Refer to the Pumpout and Refrigerant Trans-
fer Procedures section, page 63 for: pumpout system prepa-
ration, refrigerant transfer, and chiller evacuation.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
The rotation direction of the motor is shown either on the
motor nameplate or on the certified drawing. Information on
the required phase rotation of the incoming power for this
motor may also be found on the nameplate or drawing. If
either is unknown, the correct sequence can be determined
as follows. While the motor is uncoupled from the load, start
the motor and observe the direction of rotation. Allow the
motor to achieve full speed before disconnecting it from the
power source. Refer to Motor Pre-Start Checks (page 51)
for information concerning initial start-up. If the resulting
rotation is incorrect, it can be reversed by interchanging any
2 incoming cables.
Do not use air or oxygen as a means of pressurizing the
chiller. Some mixtures of HFC-134a and air can un-
dergo combustion.
Leak Test the Chiller — Due to regulations regarding
refrigerant emissions and the difficulties associated with sepa-
rating contaminants from refrigerant, Carrier recommends
the following leak test procedures. See Fig. 25 for an outline
of the leak test procedures. Refer to Tables 5A and 5B for
refrigerant pressure/temperature values and to the Pumpout
and Refrigerant Transfer Procedures section, page 63.
Motor Auxiliary Devices — Auxiliary devices such
as resistance temperature detectors, thermocouples, thermo-
guards, etc., generally terminate on terminal blocks located
in the auxiliary terminal box on the motor. Other devices
may terminate on their own enclosures elsewhere on the mo-
tor. Such information can be obtained by referring to the cer-
tified drawing. Information regarding terminal designations
and the connection of auxiliary devices can be obtained from
the auxiliary drawings referenced by the outline drawing.
If the motor is provided with internal space heaters, to
ensure proper heater operation, the incoming voltage sup-
plied to them must be exactly as shown by either the name-
plate on the motor or the outline drawing. Exercise caution
any time contact is made with the incoming space heater cir-
cuit, because space heater voltage is often automatically ap-
plied when the motor is shut down.
1. If the pressure readings are normal for the chiller
condition:
a. Evacuate the nitrogen holding charge from the ves-
sels, if present.
b. Raise the chiller pressure, if necessary, by adding re-
frigerant until the pressure is at an equivalent satu-
rated pressure for the surrounding temperature. Follow
the pumpout procedures in the Pumpout and Refrig-
erant Transfer Procedures section, page 63.
Never charge liquid refrigerant into the chiller if the pres-
sure in the chiller is less than 35 psig (241 kPa). Charge
as a gas only, with the cooler and condenser pumps run-
ning, until this pressure is reached, using PUMPDOWN/
LOCKOUT and TERMINATE LOCKOUT mode on the
PIC. Flashing of liquid refrigerant at low pressures can
cause tube freeze-up and considerable damage.
Open Oil Circuit Valves — Check that the oil filter
isolation valves for both the compressor and external gear
are open by removing the valve cap and checking the valve
stem. (See Scheduled Maintenance, Changing the Oil Fil-
ters, page 76.)
Tighten All Gasketed Joints and Guide Vane
Run the chiller water pumps whenever transferring, re-
moving, or charging refrigerant.
Shaft Packing — Gaskets and packings normally relax
by the time the chiller arrives at the jobsite. Tighten all gas-
keted joints and the guide vane shaft packing to ensure a
leak-tight chiller.
NOTE: Check the chiller cold alignment. Refer to Chiller
Alignment in the General Maintenance section, page 71.
c. Leak test chiller as outlined in Steps 3 - 9.
2. If the pressure readings are abnormal for chiller
conditions:
a. Prepare to leak test chillers shipped with refrigerant
(Step 2h).
b. Check for large leaks by connecting a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap
test all joints. If the test pressure holds for 30 minutes,
prepare to test for small leaks (Steps 2g - h).
c. Plainly mark any leaks that are found.
d. Release the pressure in the system.
e. Repair all leaks.
Check Chiller Tightness — Figure 25 outlines the
proper sequence and procedures for leak testing.
17EX chillers may be shipped with the refrigerant con-
tained in the economizer/storage vessel and the oil charge
shipped in the compressor. The cooler/condenser vessels have
a 15 psig (103 kPa) refrigerant charge. Units may also be
ordered with the refrigerant shipped separately, along with a
15 psig (103 kPa) nitrogen-holding charge in each vessel.
To determine if there are any leaks, the chiller should be
charged with refrigerant. Use an electronic leak detector to
check all flanges and solder joints after the chiller is pres-
surized. If any leaks are detected, follow the leak test
procedure.
If the chiller is spring isolated, keep all springs blocked in
both directions in order to prevent possible piping stress and
damage during the transfer of refrigerant from vessel to ves-
sel during the leak test process or any time refrigerant is trans-
ferred. Adjust the springs when the refrigerant is in operat-
ing condition and when the water circuits are full.
f. Retest the joints that were repaired.
g. After successfully completing the test for large leaks,
remove as much nitrogen, air, and moisture as pos-
sible, given the fact that small leaks may be present in
the system. This can be accomplished by following
the dehydration procedure, outlined in the Chiller
Dehydration section, page 49.
h. Slowly raise the system pressure to the equivalent satu-
rated pressure for the surrounding temperature but no
less than 35 psig (241 kPa) by adding HFC-134a
refrigerant. Proceed with the test for small leaks
(Steps 3-9).
Refrigerant Tracer — Carrier recommends using an en-
vironmentally acceptable refrigerant tracer for leak testing
with an electronic detector.
3. Check the chiller carefully with an electronic leak detec-
tor, or soap bubble solution.
Ultrasonic leak detectors also can be used if the chiller is
under pressure.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 25 — 17EX Leak Test Procedures
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5A — HFC-134a Pressure — Temperature (F)
Table 5B — HFC-134a Pressure — Temperature (C)
TEMPERATURE (F)
PRESSURE (psi)
TEMPERATURE (C)
PRESSURE (kPa)
0
2
4
6
8
6.50
7.52
-18.0
-16.7
-15.6
-14.4
-13.3
44.8
51.9
59.3
66.6
74.4
8.60
9.66
10.79
10
12
14
16
18
11.96
13.17
14.42
15.72
17.06
-12.2
-11.1
-10.0
-8.9
82.5
90.8
99.4
108.0
118.0
-7.8
20
22
24
26
28
18.45
19.88
21.37
22.90
24.48
-6.7
-5.6
-4.4
-3.3
-2.2
127.0
137.0
147.0
158.0
169.0
30
32
34
36
38
26.11
27.80
29.53
31.32
33.17
-1.1
0.0
1.1
2.2
3.3
180.0
192.0
204.0
216.0
229.0
40
42
44
46
48
35.08
37.04
39.06
41.14
43.28
4.4
5.0
5.6
6.1
6.7
242.0
248.0
255.0
261.0
269.0
50
52
54
56
58
45.48
47.74
50.07
52.47
54.93
7.2
7.8
8.3
8.9
9.4
276.0
284.0
290.0
298.0
305.0
60
62
64
66
68
57.46
60.06
62.73
65.47
68.29
10.0
11.1
12.2
13.3
14.4
314.0
329.0
345.0
362.0
379.0
70
72
74
76
78
71.18
74.14
77.18
80.30
83.49
15.6
16.7
17.8
18.9
20.0
396.0
414.0
433.0
451.0
471.0
80
82
84
86
88
86.17
90.13
93.57
97.09
100.70
21.1
22.2
23.3
24.4
25.6
491.0
511.0
532.0
554.0
576.0
90
92
94
96
98
104.40
108.18
112.06
116.02
120.08
26.7
27.8
28.9
30.0
31.1
598.0
621.0
645.0
669.0
694.0
100
102
104
106
108
124.23
128.47
132.81
137.25
141.79
32.2
33.3
34.4
35.6
36.7
720.0
746.0
773.0
800.0
828.0
110
112
114
116
118
146.43
151.17
156.01
160.96
166.01
37.8
38.9
40.0
41.1
42.2
857.0
886.0
916.0
946.0
978.0
120
122
124
126
128
171.17
176.45
181.83
187.32
192.93
43.3
44.4
45.6
46.7
47.8
1010.0
1042.0
1076.0
1110.0
1145.0
130
132
134
136
138
140
198.66
204.50
210.47
216.55
222.76
229.09
48.9
50.0
51.1
52.2
53.3
54.4
55.6
56.7
57.8
58.9
60.0
1180.0
1217.0
1254.0
1292.0
1330.0
1370.0
1410.0
1451.0
1493.0
1536.0
1580.0
48
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Leak Determination — If an electronic leak detector in-
dicates a leak, use a soap bubble solution, if possible, to
confirm it. Total all leak rates for the entire chiller. Leak-
age for the entire chiller at rates greater than the EPA (En-
vironmental Protection Agency) guidelines or local codes
must be repaired. Note the total chiller leak rate on the
start-up report. This leak rate repair is only for new start-
ups. See page 67 in General Maintenance section for rec-
ommendations on checking leak rates and leak repairs for
operating chillers.
Do not start or megohm-test the compressor motor or
oil pump motor, even for a rotation check, if the chiller
is under dehydration vacuum. Insulation breakdown and
severe damage may result.
Dehydration is readily accomplished at room tempera-
tures. Using a cold trap (Fig. 26) may substantially reduce
the time required to complete the dehydration. The higher
the room temperature, the faster dehydration takes place. At
low room temperatures, a very deep vacuum is required for
boiling off any moisture. If low ambient temperatures are
involved, contact a qualified service representative for the
dehydration techniques required.
5. If no leak is found during the initial start-up procedures,
complete the transfer of refrigerant gas (see Pumpout and
Refrigerant Transfer Procedures section, page 63.)
6. If no leak is found after a retest:
a. Transfer the refrigerant to the economizer/storage ves-
sel or other storage tank and perform a standing vacuum
test as outlined in the Standing Vacuum Test section,
this page.
b. If the chiller fails this test, check for large leaks
(Step 2b).
c. Dehydrate the chiller if it passes the standing vacuum
test. Follow the procedure in the Chiller Dehydration
section, below. Charge chiller with refrigerant (see
Pumpout and Refrigerant Transfer Procedures section,
page 63).
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm
[0.002 m3/s] or larger is recommended) to the refrigerant
charging valve (Fig. 6). Tubing from the pump to the chiller
should be as short and as large in diameter as possible to
provide the least resistance to gas flow.
2. Use an absolute pressure manometer or a wet bulb vacuum
indicator to measure the vacuum. Open the shutoff valve
to the vacuum indicator only when taking a reading. Leave
the valve open for 3 minutes to allow the indicator vacuum
to equalize with the chiller vacuum.
3. Open all isolation valves (if present), if the entire chiller
is to be dehydrated.
4. With the chiller ambient temperature at 60 F (15.6 C) or
higher, operate the vacuum pump until the manometer reads
29.8 in. Hg vac, ref 30 in. bar. (0.1 psia)(–100.61 kPa) or
a vacuum indicator reads 35 F (1.7 C). Operate the pump
an additional 2 hours.
7. If a leak is found, pump the refrigerant back into the
economizer/storage vessel or other storage tank.
8. Transfer the refrigerant until the chiller pressure is
18 in. Hg (41 kPa absolute).
9. Repair the leak and repeat the procedure, beginning from
Step 2g to ensure a leak-tight repair. (If chiller is opened
to the atmosphere for an extended period, evacuate it be-
fore repeating the leak test.)
Do not apply a greater vacuum than 29.82 in. Hg vac
(757.4 mm Hg) or go below 33 F (0.56 C) on the wet
bulb vacuum indicator. At this temperature/pressure, iso-
lated pockets of moisture can turn into ice. The slow rate
of evaporation (sublimation) of ice at these low temperatures/
pressures greatly increases dehydration time.
Standing Vacuum Test — When performing the stand-
ing vacuum test or chiller dehydration, use a manometer or
a wet bulb indicator. Dial gages cannot indicate the small
amount of acceptable leakage during a short period of time.
1. Attach an absolute pressure manometer or wet bulb in-
dicator to the chiller.
2. Evacuate the vessel (see Pumpout and Refrigerant Trans-
fer Procedures section, page 63) to at least 18 in. Hg vac,
ref 30-in. bar (41 kPa), using a vacuum pump or the pump-
out unit.
5. Valve off the vacuum pump, stop the pump, and record
the instrument reading.
6. After a 2-hour wait, take another instrument reading. If
the reading has not changed, dehydration is complete. If
the reading indicates a vacuum loss, repeat Steps 4 and 5.
7. If the reading continues to change after several attempts,
perform a leak test up to the maximum 180 psig
(1241 kPa) pressure. Locate and repair the leak, and re-
peat dehydration.
3. Valve off the pump to hold the vacuum and record the
manometer or indicator reading.
4. a. If the leakage rate is less than 0.05 in. Hg (0.17 kPa)
in 24 hours, the chiller is sufficiently tight.
b. If the leakage rate exceeds 0.05 in. Hg (0.17 kPa) in
24 hours, repressurize the vessel and test for leaks. If
refrigerant is available in the other vessel, pressurize
by following Steps 2-10 of Return Chiller To Normal
Operating Conditions section, page 67. If not, use ni-
trogen and a refrigerant tracer. Raise the vessel pres-
sure in increments until the leak is detected. If refrig-
erant is used, the maximum gas pressure is approximately
70 psig (483 kPa) at normal ambient temperature.
5. Repair the leak, retest, and proceed with dehydration.
Chiller Dehydration — Dehydration is recommended
if the chiller has been open for a considerable period of time,
if the chiller is known to contain moisture, or if there has
been a complete loss of chiller holding charge or refrigerant
pressure.
Fig. 26 — Dehydration Cold Trap
49
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Check that all electrical equipment and controls are prop-
erly grounded in accordance with job drawings, certi-
fied drawings, and all applicable electrical codes.
7. Make sure that the customer’s contractor has verified
the proper operation of the pumps, cooling tower fans,
and associated auxiliary equipment. This includes en-
suring that motors are properly lubricated, have proper
electrical supply, and have proper rotation.
Inspect Water Piping — Refer to the piping diagrams
provided in the certified drawings and the piping instruc-
tions in the 17EX Installation Instructions manual. Inspect
the piping to the cooler and condenser. Be sure that flow
directions are correct and that all piping specifications have
been met.
Piping systems must be properly vented, with no stress on
the waterbox nozzles and covers. Water flows through the
cooler and condenser must meet job requirements. Measure
the pressure drop across the cooler and condenser.
8. Tighten all wiring connections to the plugs on the SMM,
8-input, and PSIO modules.
9. Ensure that the voltage selector switch inside the power
panel is switched to the incoming voltage rating, 115 v.
The 230 v alternative is not used.
10. On chillers with free-standing starters, inspect the power
panel to ensure that the contractor has fed the wires into
the bottom of the panel. Wiring into the top of the panel
can cause debris to fall into the contactors. Clean and
inspect the contactors if this has occurred.
Water must be within design limits, clean, and treated
to ensure proper chiller performance and reduce the po-
tential of tube damage due to corrosion, scaling, or ero-
sion. Carrier assumes no responsibility for chiller dam-
age resulting from untreated or improperly treated
water.
Check Optional Pumpout Compressor Water Pip-
ing — If the optional pumpout system is installed, check
to ensure that the pumpout condenser water has been piped
in. Check for field-supplied shutoff valves and controls as
specified in the job data. Check for refrigerant leaks on field-
installed piping.
Voltage to terminals LL1 and LL2 comes from a con-
trol transformer in a starter built to Carrier specifica-
tions. Do not connect an outside source of control power
to the compressor motor starter (terminals LL1 and LL2).
An outside power source will produce dangerous volt-
age at the line side of the starter, because supplying volt-
age at the transformer secondary terminals produces in-
put level voltage at the transformer primary terminals.
Check Relief Devices — Be sure that relief devices
have been piped to the outdoors in compliance with the lat-
est edition of ANSI/ASHRAE (American National Stan-
dards Institute/American Society of Heating, Refrigeration,
and Air Conditioning Engineers) Standard 15 and applicable
local safety codes. Piping connections must allow for access
to the valve mechanism for periodic inspection and leak
testing.
CHECK INSULATION RESISTANCE — Before applying
operating voltage to the motor, whether for checking rota-
tion direction or for actual operation, measure the resistance
of the stator winding insulation.
The test voltage, based on the motor operating voltage, is
as follows:
Relief valves are set to relieve at the 225 psig (1551 kPa)
chiller design pressure.
Operating Voltage
DC Test Voltage
Inspect Wiring
0- 900
901- 7000
7001-14500
500
1000
2500
Do not check voltage supply without proper equipment
and precautions. Serious injury may result. Follow power
company recommendations.
This is particularly important if the motor may have been
exposed to excessive dampness either during transit or while
in storage. A ‘‘megger’’ type instrument can be used to mea-
sure the insulation resistance. The test voltage should be ap-
plied between the entire winding (all winding leads connected
together) and ground for approximately one minute with the
winding at ambient temperature. The recommended mini-
mum insulation resistance is determined as follows:
Do not apply any kind of test voltage, including to check
compressor oil pump even for a rotation check, if the
chiller is under a dehydration vacuum. Insulation break-
down and serious damage may result.
RM =
Where
RM =
KV + 1
1. Examine wiring for conformance to job wiring dia-
grams and to all applicable electrical codes.
2. Compare the ampere rating on the starter nameplate with
the compressor nameplate. The overload trip amps must
be 108% to 120% of the rated load amps.
3. The starter for a centrifugal compressor motor must con-
tain the components and terminals required for PIC re-
frigeration control. Check the certified drawings.
4. Check the voltage to the following components and com-
pare to the nameplate values: compressor and gear oil
pump contactors, pumpout compressor starter, and power
panel.
Recommended minimum insulation resis-
tance in megohms at 104° F (40° C) of the
entire winding.
KV =
Rated motor terminal to terminal voltage in
kilovolts (1000 volts = 1 KV).
On a new winding, where the contaminant-causing low
insulation resistance is generally moisture, drying the wind-
ing through the proper application of heat normally in-
creases the insulation resistance to an acceptable level.
The following methods are acceptable for applying heat to
a winding:
5. Be sure that fused disconnects or circuit breakers have
been supplied for the compressor and gear oil pumps,
power panel, and pumpout unit.
1. If the motor is equipped with space heaters, energize the
heaters to heat the winding.
50
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Direct current (as from a welder) can be passed through
the winding. The total current should not exceed approxi-
mately 50% of the rated full load current. If the motor
has only 3 leads, 2 must be connected together to form
one circuit through the winding. In this case, one phase
carries the full applied current and each of the others car-
ries half of the applied current. If the motor has 6 leads
(3 mains and 3 neutrals), the 3 phases should be con-
nected into one series circuit.
3. Heated air can be blown either directly into the motor or
into a temporary enclosure surrounding the motor. The
source of heated air should preferably be electrical vs.
fueled (such as kerosene), since a malfunction of the fuel
burner could result in carbon entering the motor. Exer-
cise caution when heating the motor with any source of
heat other than self-contained space heaters. Raise the wind-
ing temperature at a gradual rate to allow any entrapped
moisture to vaporize and escape without rupturing the in-
sulation. The entire heating cycle should extend over 15
to 20 hours.
External Gear Pre-Start Checks
There are 2 service valves on the external gear oil lines.
See Fig. 27. Open both valves before starting the chiller.
External gears are shipped without oil. Before start-up,
the gear must be filled with the proper type and amount
of oil.
Before starting the external gear, check for any signs of
mechanical damage, such as damaged piping or accessories.
Then, follow the procedures listed below.
1. Fill the gear and auxiliary sump (if applicable) with oil
to the level indicated next to the sight glass. Fill the gear
to the proper level as follows. Make sure all external pip-
ing, gear oil cooler, and pumps are filled before confirm-
ing the final oil level. Fill to the oil level indicated next
to the glass sight gage.
Insulation resistance measurements can be made while the
winding is being heated. However, they must be corrected to
104 F (40 C) for evaluation since the actual insulation re-
sistance decreases with increasing temperature. For a new
winding, the insulation resistance approximately halves for
each 18° F (10° C) increase in insulation temperature above
the dew point.
Add oil through the gear inspection cover. The inspection
cover must be removed in order to add oil. Take care to
seal the cover when it is replaced.
Never attempt to add or replace oil while the ex-
ternal gear is running unless a vertical sight glass is
in use and the running oil level has been established
and marked on the sight glass. Do not fill beyond
the indicated oil level. Excess lubrication increases
the churning effect and may result in overheating and
subsequent thinning of oil and possible damage to
the rotating components.
Motor Pre-Start Checks — To prevent damage to the
motor, the following steps must be taken before initial start-
up:
1. Remove the shaft shipping brace (if supplied).
2. For sleeve bearing motors, the oil reservoir must be filled
with oil to the correct level. Use a rust and oxidation in-
hibited, turbine grade oil. The viscosity of the oil must be
32 ISO (150 SSU) at 100 F (37.7 C). Oil capacity in each
of the two bearings is 0.6 gal. (2.3 L) per bearing. Use of
Carrier Oil Specification PP16-0 is approved, Carrier Part
No. PP23BZ091 (Mobil DTE Light or Texaco Regal
R+O32).
3. If possible, the shaft should be turned over by hand to
ensure that there is free rotation. On sleeve bearing mo-
tors, the shaft should be moved to both extremes of its
end play while it is being rotated, and the oil rings should
be viewed through the viewing ports in the top of the bear-
ing housing to verify free ring rotation.
2. The viscosity of the oil must be 68 ISO. Use of Carrier
oil, specification PP16-2 is approved (Mobil DTE Heavy
Medium or Texaco Regal UR & 068; Carrier Part No.
PP23BB005).
3. Check that all electrical connections have been made and
are in working order. Check that all accessories are prop-
erly mounted.
4. Turn the gear shafts by hand with a spanner wrench to
confirm that there are no obstructions to rotation.
5. Check that all couplings are properly aligned, mounted,
and keyed on the shaft extension.
4. On fan-cooled motors, the area around the external fan
inlet should be checked for loose debris that could be drawn
into the fan during operation.
6. Check that the inspection cover is securely fastened. See
Table 7 for recommended torque values.
5. All external, factory-made, bolted joints should be checked
for any looseness that may have occurred in transit. Refer
to Table 6 for recommended bolt torques.
7. For units operating in cold ambient temperatures, op-
tional heaters must be turned on and the oil temperature
must be allowed to rise to at least 60 F (16 C) before
start-up.
8. Start the chiller under as light a load as possible. Check
for oil leaks, unusual sounds, excessive vibration, and ex-
cessive heat. If an operating problem develops, shut down
immediately and correct the problem before restarting.
Table 6 — Recommended Motor Fastener
Tightening Torques
1
3
1
5
3
7
Bolt size
Grade
⁄
4
؆
5⁄16؆
⁄
8؆
⁄
2؆
⁄
8؆
⁄4؆
⁄8
؆
1؆ 11⁄3
؆
11⁄2
؆
SAE GR 5
12 31 63 115 180 275 550
Ft-lbs
3.5
7
960
Torque*
.
N m
4.7 9.5 16 42 85 156 244 373 746 1302
Bolt size M4 M6 M8 M10 M12 M10 M12 M16
Grade
Ft-lbs
DIN 8.8
15
DIN 12.9
92
2
8
35
47
65
88
45
61
225
305
Torque*
.
N m
2.7 11
20
125
*Torque values based upon dry friction.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 27 — External Gear Lubrication System
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7 — Recommended Compressor and
External Gear Fastener Tightening Torques
Check Starter
FASTENER
DIAMETER (in.)
TORQUE*
•
Lb.-Ft. (N m)
BE AWARE that certain automatic start arrangements
can engage the starter. Open the disconnect ahead of
the starter in addition to shutting off the chiller and pump.
UNC
Minimum
Maximum
1
⁄
4
7
14
(9.5)
(19.0)
9
17
(12.2)
(23.1)
5⁄16
3
⁄
8
25
(33.9)
31
(42.0)
7⁄16
1
40
(54.2)
(81.4)
50
75
108
150
266
429
643
(67.8)
Use the instruction and service manual supplied by the
starter manufacturer to verify that the starter has been in-
stalled correctly.
⁄
2
60
(101.7)
(137.0)
(203.4)
(360.7)
(581.7)
(871.9)
9⁄16
5
87
(118.0)
(162.7)
(288.8)
(465.1)
(698.3)
(861.1)
⁄
⁄
⁄
8
4
8
120
213
343
515
635
3
7
1
11⁄8
11⁄4
13⁄8
11⁄2
13⁄4
2
793 (1075.3)
1120 (1518.7)
1468 (1990.6)
1950 (2644.2)
2286 (3099.8)
3437 (4660.6)
5027 (6816.6)
6875 (9322.5)
9323 (12,642.0)
The main disconnect on the starter front panel may not
deenergize all internal circuits. Open all internal and re-
mote disconnects before servicing the starter.
896 (1215.0)
1175 (1593.3)
1560 (2115.4)
1828 (2478.8)
2750 (3729.0)
4022 (5453.8)
5500 (7458.6)
7456 (10,110.3)
Whenever a starter safety trip device activates, wait at least
30 seconds before resetting the safety. The microprocessor
maintains its output to the 1CR relay for 10 seconds after
starter safety shutdown to determine the fault mode of
failure.
21⁄4
21⁄2
23⁄4
*Dry fastener.
NOTE: The torque values listed are to be used for end covers, seal
cages, shaft guards, inspection covers, and housing split line bolts,
unless otherwise specified on the drawing or assembly instructions.
MECHANICAL STARTERS
1. Check all field wiring connections for tightness, clear-
ance from moving parts, and correct connection.
Carrier Comfort Network Interface — The Carrier
Comfort Network (CCN) communication bus wiring is sup-
plied and installed by the electrical contractor. It consists of
shielded, 3-conductor cable with drain wire.
The system elements are connected to the communication
bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to
the positive pins of the system element on either side of it;
the negative pins must be wired to the negative pins; the sig-
nal ground pins must be wired to signal ground pins.
To attach the CCN communication bus wiring, refer to
the certified drawings and wiring diagrams. The wire is in-
serted into the CCN communications plug (COMM1) on the
PSIO module. This plug also is referred to as J5.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-
can Wire Gage) minimum stranded, tinned copper. Indi-
vidual conductors must be insulated with PVC, PVC/nylon,
vinyl, Teflon, or polyethylene. An aluminum/polyester 100%
foil shield and an outer jacket of PVC, PVC/nylon, chrome
vinyl, or Teflon with a minimum operating temperature range
of –20 C to 60 C is required. See table below for cables that
meet the requirements.
2. Check the contactor(s) to be sure they move freely. Check
the mechanical interlock between contactors to ensure that
the 1S and 2M contactors cannot be closed at the same
time. Check all other electro-mechanical devices, such as
relays and timers, for free movement. If the devices do
not move freely, contact the starter manufacturer for re-
placement components.
3. Some dashpot-type magnetic overload relays must be filled
with oil at the jobsite. If the starter is equipped with de-
vices of this type, remove the fluid cups from these mag-
netic overload relays. Add dashpot oil to the cups per in-
structions supplied with the starter. The oil is usually shipped
in a small container attached to the starter frame near the
relays. Use only dashpot oil supplied with the starter. Do
not substitute.
Factory-filled dashpot overload relays need no oil at start-
up, and solid-state overload relays do not have oil.
4. Reapply starter control power (not main chiller power) to
check the electrical functions. When using a reduced-
voltage starter (such as a wye-delta starter) check the tran-
sition timer for proper setting. The factory setting is
30 seconds (±5 seconds), timed closing. The timer is ad-
justable in a range between 0 and 60 seconds, and set-
tings other than the nominal 30 seconds may be chosen
as needed (typically 20 to 30 seconds).
MANUFACTURER
Alpha
CABLE NO.
2413 or 5463
A22503
American
Belden
When the timer has been set, check that the starter (with
relay 1CR closed) goes through a complete and proper
8772
Columbia
02525
start cycle.
When connecting the CCN communication bus to a sys-
tem element, a color code system for the entire network is
recommended to simplify installation and checkout. The fol-
lowing color code is recommended:
SOLID-STATE STARTERS
The solid-state starter is at line voltage when AC power
is connected. Pressing the Stop button does not remove
voltage. Use caution when adjusting the potentiometers
on the equipment.
SIGNAL CCN BUS CONDUCTOR
PSIO MODULE
TYPE
INSULATION COLOR COMM 1 PLUG (J5) PIN NO.
+
Ground
–
RED
WHITE
BLACK
1
2
3
53
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Check that all wiring connections are properly termi-
nated to the starter.
2. Verify that the ground wire to the starter is installed prop-
erly and is of sufficient size.
3. Verify that the motors are properly grounded to the starter.
4. Check that all the relays are properly seated in their
sockets.
5. Verify that the proper AC input voltage is brought into
the starter per the certified drawings.
6. Verify that the initial factory settings (i.e., starting torque,
ramp potentiometers, etc.) are set per the manufacturer’s
instructions.
Input the Design Set Points — To modify the set
points, access the SETPOINT menu. (Press the MENU and
SETPOINT softkeys.) From this menu, you can modify the
base demand limit and the leaving chilled water, entering
chilled water, and ice build set points. See Fig. 15 for the
SETPOINT menu structure.
The PIC can control a set point according to ether the leav-
ing or entering chilled water temperature. To change the type
of control, access the CONFIG screen. Scroll down to high-
light ECW CONTROL OPTION. To control the set point ac-
cording to the leaving chilled water, press the DISABLE
softkey; to control the set point according to the entering
chilled water, press the ENABLE softkey.
Compressor Oil Charge — If oil is added, it must
meet Carrier’s specification for centrifugal compressor use
as described in the Scheduled Maintenance, Oil Specifica-
tions section (page 77).
Oil may be added through the compressor oil drain and
charging valve (Fig. 2, Item 22) using a pump. The pump
must be able to lift from 0 to 150 psig (0 to 1034 kPa), or
above chiller pressure. However, an oil charging elbow on
the seal-oil return chamber (Fig. 4, Item 3) allows oil to be
added without pumping. The seal oil return pump automati-
cally transfers the oil to the main oil reservoir.
Input the Local Occupied Schedule (OCCPC01S)
— To set up the occupied time schedule according to the
site requirements, access the SCHEDULE screen on the LID.
(Press the MENU and SCHEDULE softkeys.) The de-
fault, factory-set schedule is 24 hours, occupied 7 days per
week including holidays. For more information about how
to set up a time schedule, see the Controls section, page 11.
If the ice build option is being used, configure the ice build
schedule (OCCPC02S).
If a CCN system is being installed or if a secondary time
schedule is required, configure the CCN occupancy sched-
ule (OCCPC03S to OCCPC99S). This task is normally done
using a CCN Building Supervisor terminal, but it can also
be done at the LID. For more information on CCN func-
tions, see 17EX CCN supplement. Also, in this manual, see
the section on Occupancy Schedule, page 32.
Oil should only be charged or removed when the chiller
is shut down. Maximum oil level is the middle of the upper
sight glass.
Power Up the Controls and Check the Com-
pressor Oil Heater — Be sure that an oil level is vis-
ible in the compressor before energizing the controls. Aseparate
disconnect energizes the oil heater and the control circuit.
When first powered, the LID should display the default screen
within a short period of time.
Input Service Configurations — The following con-
figurations are done from the SERVICE menu:
• password
• input time and date
• LID configuration
• controller identification
• service parameters
• equipment configuration
• automated control test
PASSWORD — You must enter a password whenever you
access the SERVICE screens. The default, factory-set pass-
word is 1 - 1 - 1 - 1. The password may be changed from the
LID CONFIGURATION screen. To change the password:
The oil heater is energized by powering the control cir-
cuit. This should be done several hours before start-up to
minimize oil-refrigerant dilution. The oil heater is con-
trolled by the PIC and is powered through a contactor in the
power panel. Starters contain a separate circuit breaker to
power the heater and the control circuit. This arrangement
allows the heater to energize when the main motor circuit
breaker is off for service work or extended shutdowns. The
oil heater relay status can be viewed on the STATUS02 screen
on the LID. Oil sump temperature can be viewed on the LID
default screen.
1. Press the MENU and SERVICE softkeys. Enter your
password and highlight LID CONFIGURATION. Press
the SELECT softkey. Only the last 5 entries on the LID
SOFTWARE VERSION — The software version is always
labeled on the PSIO module and on the back side
of the LID module. The software number also appears on
both the CONTROLLER IDENTIFICATION and LID CON-
FIGURATION tables. See Fig. 15.
CONFIGURATION screen can be changed: BUS #,
ADDRESS #, BAUD RATE, US IMP/METRIC, and
PASSWORD.
2. Use the ENTER softkey to scroll to PASSWORD. The
Set Up Chiller Control Configuration
first digit of the password is highlighted on the LID screen.
3. To change the digit, press the INCREASE or
DECREASE softkey. When you see the digit you want,
Do not operate the chiller before the control configu-
rations have been checked and a Control Test has been
satisfactorily completed. Protection by safety controls
cannot be assumed until all control configurations have
been confirmed.
press the ENTER softkey.
4. The next digit is highlighted. Change it and the third and
fourth digits in the same way you changed the first.
As you configure the 17EX chiller, write down all con-
figuration settings. A log, such as the one shown on pages
CL-1 to CL-12, is a convenient way to list configuration
values.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
5. After the last digit is changed, the LID goes to the
Modify Minimum and Maximum Load Points (⌬T1/P1;
⌬ T2/P2) If Necessary —These pairs of chiller load points,
located on the SERVICE1 table, determine when to limit guide
vane travel or to open the hot gas bypass valve when surge
prevention is needed. These points should be set based on
individual chiller operating conditions.
BUS # parameter. Press the EXIT softkey to leave the
screen, record your password change, and return to the
SERVICE menu.
If, after configuring a value for these points, surge pre-
vention is operating too soon or too late for conditions, these
parameters should be changed by the operator.
Example of configuration:
Chiller operating parameters:
Refrigerant used: HFC-134a
BE SURE TO REMEMBER YOUR PASSWORD.
Retain a copy of the password for future reference.
If you forget your password, you will not be able to
access the SERVICE menu unless you install and
download a new PSIO module.
Estimated Minimum Load Conditions:
44 F (6.7 C) LCW
45.5 F (7.5 C) ECW
43 F (6.1 C) Suction Temperature
70 F (21.1 C) Condensing Temperature
Estimated Maximum Load Conditions:
44 F (6.7 C) LCW
54 F (12.2 C) ECW
42 F (5.6 C) Suction Temperature
98 F (36.7 C) Condensing Temperature
INPUT TIME AND DATE — Access the Time and Date
table on the SERVICE menu. Input the present time of day,
date, and day of the week. HOLIDAY TODAY should only
be configured to YES if the present day is a holiday.
CHANGE THE LID CONFIGURATION IF NECESSARY
— From the LID CONFIGURATION screen, the LID CCN
address, units (English or SI), and password can be changed.
If there is more than one chiller at the jobsite, change the
LID address on each chiller so that each chiller has its own
address. Note and record the new address. Change the screen
to SI units as required, and change the password if desired.
To Change the LID Display From English to Metric Units
— By default, the LID displays information in English units.
To change to metric units:
1. Press the MENU and SERVICE softkeys. Enter your pass-
word and highlight LID CONFIGURATION. Press the
SELECT softkey.
Calculate Maximum Load — To calculate the maximum load
points, use the design load condition data. If the chiller full
load cooler temperature difference is more than 15° F
(8.3° C), estimate the refrigerant suction and condensing tem-
peratures at this difference. Use the proper saturated pres-
sure and temperature for the particular refrigerant used.
Suction Temperature:
2. Use the ENTER softkey to scroll to US IMP/METRIC.
3. Press the softkeys that correspond to the units you want
displayed on the LID (e.g., US or METRIC ).
42 F (5.6 C) = 37 psig (255 kPa) saturated
refrigerant pressure (HFC-134a)
Condensing Temperature:
98 F (36.7 C) = 120 psig (1827 kPa) saturated
MODIFY CONTROLLER IDENTIFICATION IF NECES-
SARY — The PSIO module address can be changed from
the CONTROLLER IDENTIFICATION screen. If there is
more than one chiller at the site, change the controller ad-
dress for each chiller. Write the new address on the PSIO
module for future reference.
refrigerant pressure (HFC-134a)
Maximum Load ⌬T2:
54 – 44 = 10° F (12.2 – 6.7 = 5.5° C)
Maximum Load ⌬P2:
120 – 37 = 83 psid (827 – 255 = 572 kPad)
To avoid unnecessary surge prevention, add about 10 psid
INPUT EQUIPMENT SERVICE PARAMETERS IF NEC-
ESSARY — The EQUIPMENT SERVICE table has 3 screens:
SERVICE1, SERVICE2, and SERVICE3.
(70 kPad) to ⌬P2 from these conditions:
⌬T2 = 10° F (5.5° C)
⌬P2 = 93 psid (642 kPad)
Configure SERVICE1 Table — Access the SERVICE1 table
to modify or view the following:
Calculate Minimum Load — To calculate the minimum load
conditions, estimate the temperature difference that the cooler
will have at 20% load, then estimate what the suction and
condensing temperatures will be at this point. Use the proper
saturated pressure and temperature for the particular refrig-
erant used.
Chilled Medium
Water or Brine?
Brine Refrigerant Trippoint Usually 3° F (1.7° C) below design
refrigerant temperature
Is HGBP installed?
Surge Limiting or
Hot Gas Bypass Option
Minimum Load Points
(T1/P1)
Per job data — See Modify Load
Points section
Suction Temperature:
43 F (6.1 C) = 38 psig (262 kPa) saturated
Full Load Points
(T2/P2)
Per job data — See Modify Load
Points section
refrigerant pressure (HFC-134a)
Motor Rated Load Amps
Per job data
Condensing Temperature:
Motor Rated Line Voltage Per job data
70 F (21.1 C) = 71 psig (490 kPa) saturated
Motor Rated Line kW
Line Frequency
Per job data (if kW meter installed)
50 or 60 Hz
refrigerant pressure (HFC-134a)
Compressor Starter Type
Stop-to-Start Timer
Reduced voltage or full?
Minimum Load ⌬T1 (at 20% Load):
2° F (1.1° C)
Follow motor vendor recommenda-
tion for time between starts. See
certified prints for correct value.
Minimum Load ⌬P1:
71 – 38 = 33 psid (490 – 262 = 228 kPad)
NOTE: Other values are left at the default values. These may be changed
by the operator as required. SERVICE2 and SERVICE3 tables can
be modified by the owner/operator as required.
Again, to avoid unnecessary surge prevention, add 20 psid
(140 kPad) at ⌬P1 from these conditions:
⌬T1 = 2° F (1.1° C)
⌬P1 = 53 psid (368 kPad)
55
Download from Www.Somanuals.com. All Manuals Search And Download.
If surge prevention occurs too soon or too late, make the
following adjustments:
PERFORM AN AUTOMATED CONTROL TEST — Check
the safety controls status by performing an automated con-
trols test. Access the CONTROL TEST table from the SERV-
ICE menu. This table has the following screens:
SURGE PREVENTION SURGE PREVENTION
LOAD
OCCURS TOO SOON OCCURS TOO LATE
At low loads
Increase P1 by
Decrease P1 by
Automated Test
As described above, a complete
control test.
Checks all PSIO thermistors only.
Checks all options board thermistors.
Checks all transducers.
Checks the guide vane operation.
Checks operation of pump output;
either all pumps can be
activated or individual pumps.
Also tests the associated input
such as flow or pressure.
Activates all on/off outputs, all
at once or individually.
Pumpdown prevents the low
refrigerant alarm during
evacuation so refrigerant
can be removed from the unit,
locks the compressor off. and
starts the water pumps.
(Ͻ50%)
10 psid (70 kPad)
10 psid (70 kPad)
At high loads
Increase P2 by
10 psid (70 kPad)
Decrease P2 by
10 psid (70 kPad)
PSIO Thermistors
Options Thermistors
Transducers
Guide Vane Actuator
Pumps
(Ͼ50%)
MODIFY EQUIPMENT CONFIGURATION IF NECES-
SARY — The EQUIPMENT CONFIGURATION table has
a number of screens to select, view, and/or modify. See
Fig. 16 for the menu structure of this table. Carrier provides
certified drawings that have the configuration values re-
quired for specific jobsites. Modify these values only if
requested.
Discrete Outputs
CONFIG Screen Modifications — Change the values on this
screen according to your job data. See certified drawings for
the correct values. Modifications can include:
Pumpdown/Lockout
• chilled water reset
• entering chilled water control (Enable/Disable)
• 4 to 20 mA demand limit
Terminate Lockout
Charges refrigerant and enables
the chiller to run after pumpdown
lockout.
• auto. restart option (Enable/Disable)
• remote contact option (Enable/Disable)
FX Gear Oil Pump I/O Activates external gear main oil pump
LEAD/LAG Screen Modifications — Change the values on
this screen according to your job data. See certified draw-
ings for specific values. Modifications can include:
and auxiliary oil pump (if supplied).
Automated Test — Before running this test, be sure that the
compressor is in the OFF mode and the 24-v input to the
SMM is in range (per line voltage percent on STATUS01
screen). Put the compressor in OFF mode by pressing the
STOP pushbutton on the LID.
The automated test starts with a check of the PSIO ther-
mistors and proceeds through the rest of the tests listed in
the table below. The test not only checks readings, such as
temperature and pressure readings, but also lets the operator
know if certain devices, such as pumps or relays, are on or
off and if all outputs and inputs are functioning. It also sets
the refrigerant type.
As each test is executed, the LID display shows which
test is running as well as other pertinent data. At the end of
each test, the LID displays, OK TO CONTINUE? If a test
indicates a problem, error, or device malfunction, the op-
erator can choose to address the problem as the test is being
done or note the problem and proceed to the next test.
• lead/lag selection
• load balance option
• common sensor option
• lag start/stop timers
• standby chiller option
Owner-Modified CCN Tables— The following tables are de-
scribed for reference only. For detailed information on CCN
operations, consult the CCN supplement for your chiller.
• OCCDEFCS Screen Modifications — This table contains
the local and CCN time schedules, which can be modified
here, or on the SCHEDULE screen as described
previously.
• HOLIDEF Screen Modifications — This table configures
the days of the year that holidays are in effect. See the
holiday paragraphs in the Controls section for more
details.
• BRODEF Screen Modifications — This table defines the
outside-air temperature sensor and humidity sensor if one
is to be installed. It also defines the start and end of day-
light savings time. Enter the dates for the start and end of
daylight savings, if required for your location. BRODEF
also activates the Broadcast function, which enables the
holiday periods defined on the LID to take effect.
• Other Tables — The ALARMDEF, CONS-DEF, RUNT-
DEF, and WSMALMDF screens contain information for
use with a CCN system. See the applicable CCN manual
for more information on these screens. These screens can
only be changed from a CCN Building Supervisor
terminal.
NOTE: If during the control test the guide vanes do not open,
check to see that the low pressure alarm is not active. (This
causes the guide vanes to close.)
NOTE: The oil pump test will not energize the oil pump if
cooler pressure is below –5 psig (–35 kPa).
When the test is finished, or the EXIT softkey is pressed,
the test stops and the CONTROL TEST menu is displayed.
If a specific automated test procedure is not completed, ac-
cess that test by scrolling to it and selecting it to test the
function when ready. The CONTROL TEST menu is de-
scribed in more detail in Table 8.
CHECK VOLTAGE SUPPLY —Access the STATUS 01 screen
and read the LINE VOLTAGE: ACTUAL value. This reading
should be equal to the incoming power to the starter. Use a
voltmeter to check incoming power at the starter power leads.
If the readings are not equal, an adjustment can be made by
selecting the LINE VOLTAGE: ACTUAL parameter and then
increasing or decreasing the value so that the value appear-
ing on the LID is calibrated to match the incoming power
voltage reading. Voltage can be calibrated only between 90
and 100% of the rated line voltage.
Check Pumpout System Controls and Optional
Pumpout Compressor — The pumpout system con-
trols include an on/off switch, a 3-amp fuse, the compressor
overloads, an internal thermostat, a compressor contactor, and
a refrigerant high pressure cutout. The high pressure cutout
is factory set to open at 161 psig (1110 kPa) and reset at
130 psig (896 kPa). Check that the water-cooled condenser
has been connected. Loosen the compressor holddown bolts
to allow free spring travel. Open the compressor suction and
discharge service valves. Check that oil is visible in the com-
pressor sight glass. Add oil if necessary.
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8 — Control Test Menu Functions
See the Pumpout and Refrigerant Transfer Procedures
(page 63) and Pumpout System Maintenance sections
(page 83) for details on transferring refrigerant, oil specifi-
cations, etc.
TESTS TO BE
PERFORMED
DEVICES TESTED
1. Automated Tests*
Operates the second through seventh
tests
High Altitude Locations — Because the chiller is ini-
tially calibrated at sea level, it is necessary to recalibrate the
pressure transducers if the chiller is to be operated at a high
altitude location. Please see the calibration procedure in the
Troubleshooting Guide section.
2. PSIO Thermistors
Entering chilled water
Leaving chilled water
Entering condenser water
Leaving condenser water
Discharge temperature
Bearing temperature
Motor winding temperature
Oil sump temperature
Charge Refrigerant into Chiller
3. Options Thermistors Common chilled water supply sensor
Common chilled water return sensor
Remote reset sensor
Temperature sensor — Spare 1
The transfer, addition, or removal of refrigerant in spring
isolated chillers may place severe stress on external pip-
ing if springs have not been blocked in both up and down
directions.
Spare 2
Spare 3
Spare 4
Spare 5
Spare 6
Spare 7
Spare 8
Spare 9
The 17EX chiller may have the refrigerant already charged
in the economizer/storage vessels. If chiller is not shipped
fully charged, refrigerant is shipped separately to conform
with transportation regulations. The 17EX may be ordered
with a nitrogen holding charge of 15 psig (103 kPa). Evacu-
ate the entire chiller, and charge chiller from refrigerant
cylinders.
The full refrigerant charge on the 17EX will vary with
chiller components and design conditions as indicated on the
job data specifications. An approximate charge may be found
in Physical Data and Wiring Schematics section, page 99.
The full chiller charge is printed on the chiller identification
label.
4. Transducers
Evaporator pressure
Condenser pressure
Oil pressure differential†
5. Guide Vane Actuator Open
Close
6. Pumps
All pumps or individual pumps may be
activated:
Oil pump — Confirm pressure
Chilled water pump — Confirm flow
Condenser water pump — Confirm flow
Auxiliary oil pump — confirm
pressure†
7. Discrete Outputs
All outputs or individual outputs may
be energized:
Always operate the condenser and chilled water pumps
during charging operations to prevent water in heat ex-
changer tubes from freezing.
Hot gas bypass relay
Oil heater relay
Motor cooling relay
Tower fan relay
Alarm relay
Shunt trip relay
Use the CONTROLS TEST terminate lockout function to
monitor conditions and start the pumps.
8. Pumpdown/Lockout When using pumpdown/lockout,
observe freeze up precautions when
removing charge.
If the chiller has been shipped with a holding charge, add
refrigerant through the refrigerant charging valve (Fig. 6) or
to the pumpout charging connection. First evacuate the ni-
trogen holding charge from the vessels. Charge the refrig-
erant as a gas until the system pressure exceeds 35 psig
(141 kPa). After the chiller is beyond this pressure, the re-
frigerant should be charged as a liquid until all the recom-
mended refrigerant charge has been added.
Instructs operator as to which valves
to close and when.
Starts chilled water and condenser wa-
ter pumps and confirms flows.
Monitors — Evaporator pressure
Condenser pressure
Evaporator temperature
during pumpout
TRIMMING REFRIGERANT CHARGE — The 17EX is
shipped with the correct charge for the design duty of the
chiller. Trimming the charge can best be accomplished when
the chiller is operating at design load. To trim, check the
temperature difference between the leaving chilled water tem-
perature and the cooler refrigerant temperature at full load
design conditions. If necessary, add or remove refrigerant to
bring the temperature difference to design conditions or a
minimum differential.
procedures
Turns pumps off after pumpdown.
Locks out compressor.
9. Terminate Lockout
Starts pumps and monitors flows.
Instructs operator as to which valves
to open and when.
Monitors — Evaporator pressure
Condenser pressure
Evaporator temperature
during charging process
Terminates compressor lockout.
10. FX Gear Oil
Pump I/O
Activates gear main oil pump; con-
firms pressure.
INITIAL START-UP
Activates optional gear auxiliary pump;
confirms pressure.
Preparation — Before starting the chiller, check that the:
1. Power is on to the main starter, oil pump relay (which
energizes both the compressor and gear oil pumps), tower
fan starter, oil heater relay, and the chiller control
center.
*During any of the tests that are not automated, an out-of-range read-
ing will have an asterisk (*) next to the reading and a message will
be displayed.
†On open-drive chillers, differential pressure is the only oil pressure
displayed.
2. Cooling tower water is at proper level and at or below
design entering temperature.
57
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Chiller is charged with refrigerant and all refrigerant and
all oil valves are in their proper operating position.
5. Check the main contactor for proper operation.
6. The PIC will activate an alarm for motor amps not sensed.
Reset this alarm and continue with the initial start-up.
4. Gear oil, compressor oil, and motor bearing oil are at the
proper levels in the reservoir sight glasses.
Check Motor Rotation
INITIAL MOTOR START-UP
5. Compressor oil reservoir temperature is above 140 F
(60 C) or refrigerant temperature plus 50° F (28° C).
Initial Uncoupled Start-Up — The initial start-up of the mo-
tor should be made with the motor uncoupled. Verify that oil
has been added to each bearing housing to the correct level.
6. Valves in the evaporator and condenser water circuits are
open.
NOTE: If the water pumps are not automatic, make sure
water is circulating properly.
1. If the motor is equipped with unidirectional fans (refer to
the certified drawing) and verification of rotation direc-
tion is required, do the following:
7. Check the starter to be sure it is ready to start and that all
safety circuits have been reset. Be sure to keep the starter
door closed.
a. Start the motor and observe the rotation direction. See
Fig. 28.
b. Allow the motor to achieve full speed before discon-
necting it from the power source.
c. If the rotation direction must be changed, refer to the
Before Initial Start-Up, Motor Electrical Connection
section, page 45. Otherwise, the motor can be re-
started immediately after it has coasted to a stop.
Do not permit water or brine that is warmer than 110 F
(43 C) to flow through the cooler or condenser. Refrig-
erant overpressure may discharge through the relief de-
vices and result in the loss of refrigerant charge.
8. To prevent accidental start-ups, the CHILLER START/
STOP parameter is set to STOP at the factory. Access the
STATUS01 screen and scroll to the CHILLER START/
STOP parameter. Press the RELEASE softkey to enable
the chiller to start.
Manual Operation of the Guide Vanes — Manual
operation of the guide vanes helps to establish a steady mo-
tor current when calibrating the motor amps value.
To manually operate the guide vanes, override the target
guide vane position (TARGET GUIDE VANE POS param-
eter on the STATUS01 screen). Manual control is also in-
dicated on the default screen on the run status line.
1. Access the STATUS01 screen and look at the TARGET
GUIDE VANE POS parameter. (Refer to Fig. 13). If the
compressor is off, the value reads zero.
2. Move the highlight bar to the TARGET GUIDE VANE
POS parameter and press the SELECT softkey.
Fig. 28 — Correct Motor Rotation
3. Press ENTER to override the automatic target. The screen
2. After the initial start-up, monitor the bearing tempera-
tures closely. Verify the free rotation of the oil rings on
the sleeve bearings by observing them through the view-
ing port in the top of the housing. The rate of rise in bear-
ing temperature is more indicative of impending trouble
than the actual temperature. If the rate of rise in tempera-
ture is excessive or if the motor exhibits excessive vi-
bration or noise, shut it down immediately and conduct a
thorough investigation to find the cause before operating
the motor again. If the bearing temperatures rise and mo-
tor operation appears to be normal, continue operating
the motor until the bearing temperatures stabilize.
reads a value of zero. The word SUPVSR! flashes to in-
dicate that manual control is in effect. The default screen
also indicates that the guide vanes are in manual control.
4. To return the guide vanes to automatic mode, press the
SELECT softkey; then press the RELEASE softkey.
After a few seconds, the word SUPVSR! disappears.
Dry Run to Test Start-Up Sequence
1. Disengage the main motor disconnect on the starter front
panel. This should only disconnect the motor power. Power
to the controls, oil pumps, and starter control circuit should
still be energized.
2. Look at the default screen on the LID. The status mes-
sage in the upper left corner should read, MANUALLY
The recommended limits on bearing temperature rise over
ambient temperature are listed below:
Temperature Rise
Sleeve Bearing Temperature
Over Ambient
STOPPED. Press the CCN or LOCAL softkey to start.
As Measured By
Temperature
If MANUALLY STOPPED is not on the default screen
access the SCHEDULE screen and override the schedule
or change the occupied time. Then, press the LOCAL
A permanently installed
72° F (40° C)
detector
A temporary detector on top
of the bearing sleeve near the
oil ring
softkey to begin the start-up sequence.
63° F (35° C)
3. Check that the chilled water and condenser water pumps
have energized.
4. Check that the oil pumps have started and have pressur-
ized the lubrication system. After the oil pumps have run
about 15 seconds, the starter energizes and goes through
its start-up sequence.
NOTE: When operating flood-lubricated sleeve bearings,
the bearing temperature must not be allowed to exceed
185 F (85 C) total temperature.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
Note that each start time an induction motor starts, it is
subjected to the full inrush of current along with heating of
the stator and rotor windings. Each acceleration and re-
peated start can produce more heat than is produced and dis-
sipated by the motor under full load. The starting duty for
which the motor is designed is shown on a nameplate mounted
on the motor. Do not exceed this amount if long motor life
is expected.
Abnormally low terminal voltage, excessive load torque,
and/or excessive load inertia during motor start-up can cause
lengthened acceleration times during which rotor ventilation
is reduced. This can cause rotor damage or can lead to short-
ened rotor life.
The temperature rating of the motor is shown on the main
nameplate as a temperature rise above an ambient tempera-
ture. If there is a service factor, it is also shown. If the motor
temperature switch opens, investigate the situation before at-
tempting to continue operation.
If the motor is a TEWAC (Totally Enclosed Water-to-Air
Cooled) design, the maximum inlet water temperature and
the water flow rate or gpm (gallons per minute) at the air
cooler must be as shown on the certified drawing. Other-
wise, the discharge air temperature from the cooler (actually
the ambient air for the motor as shown by the main name-
plate) could be too high for the motor to properly cool.
Under normal conditions, for the self-lubricating bear-
ing, the rate of temperature rise should be from 20°
to 25° F (11° to 14° C) during the first 10 minutes
after starting up and approximately 40° F (22° C)
over 30 minutes. The rate of bearing temperature rise
is a function of the natural ventilation and operating
conditions.
When the rate of bearing temperature rise is less than
2° F (1.1° C) per half-hour, the bearing temperature
is considered to be stabilized.
If the total bearing temperature exceeds 195 F
(91 C), the motor should be shut down immediately.
3. Any abnormal noise or vibration should be immediately
investigated and corrected. Increased vibration (with the
motor uncoupled from its load) can indicate a change in
balance due to a mechanical failure or loose rotor part, a
stator winding problem, a foundation problem, or a change
in motor alignment.
Disc Coupling Installation and Alignment — Be-
fore installing the disc coupling, inspect it for any signs of
damage during shipment. Check that all parts are available,
as ordered. Cradle or support the coupling components dur-
ing handling to avoid damage. Wrap the components for pro-
tection. Keep flanges free of nicks and burrs. Read all the
instructions and review this procedure before beginning the
actual installation. Some steps apply only to certain types of
couplings (e.g., high speed coupling).
4. Verify that the magnetic center indicator aligns with the
shaft.
Initial Coupled Start-Up — After initial uncoupled start-up,
take the following steps to ensure safe coupled operation:
1. Follow the procedure stated in the General Maintenance,
Chiller Alignment section to align the motor to the driven
chiller.
2. Prepare the coupling for operation according to the Disc
Coupling Installation andAlignment instructions, this page.
Note any match marks on the couplings and assemble ac-
cordingly. For sleeve bearing motors, verify that the cor-
rect limited end float coupling has been installed. The end
float limits can be found on the certified drawing.
Use only the bolts and nuts supplied by the coupling
manufacturer.
3. Ensure that all personnel are at a safe distance from ro-
tating parts. Start the motor in accordance with instruc-
tions supplied with the motor control.
1. Installing the Coupling Hubs (Keyed Mounting).
a. Check the hub bore and shaft for nicks and burrs; dress
if necessary.
4. If the motor rotor fails to start turning in a second or two,
shut off the power supply immediately. This can result
from:
b. For taper bores, check the fit of the bore to the shaft.
c. Fit keys precisely to the keyways in the shaft and hub.
Each key should have a tight fit on the sides with a
slight clearance on top. To maintain dynamic balance,
the keys should fill the keyways exactly and not be too
short or too long.
a. too low a voltage at the motor terminals
b. the load is too much for the rotor to accelerate
c. the load is frozen up mechanically
d. all required electrical connections are not made
e. single-phase power has been applied
f. any combination of the above.
d. Clean the hub bore and shaft.
e. Heat the hub to expand the bore. DO NOT allow the
hub temperature to exceed 600 F (300 C). DO NOT
apply an open flame to any part of the coupling. Car-
rier recommends using an oven to heat the hub.
Investigate thoroughly and take corrective action before
attempting a restart.
5. Carefully observe the vibration of the bearing housing and
any abnormal noise generator. Note that coupled motor
vibration may not be the same as uncoupled vibration
amounts. If coupled vibration is excessive, recheck the
mounting and alignment.
6. Carefully observe the bearing temperature rise and the
movement of the oil ring.
To avoid the risk of explosion, fire, or damage to
the coupling and equipment and/or injury to per-
sonnel, do not use an open flame or oil bath to ex-
pand the hub. If heat is used at anytime for instal-
lation, DO NOT ALLOW the hub temperature to
exceed 600 F (300 C).
If the bearing temperatures rise and motor operation ap-
pears normal, operation should continue until the bearing
temperatures stabilize.
f. Place the hub in the proper position on the shaft. Hold
the hub in place as it cools. For tapered bores, verify
the hub advance and install the shaft retaining nut.
7. If possible, check the motor line currents for balance.
59
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Offset and Angular Alignment — Reverse dial indication
or optical methods of alignment (such as lasers) are rec-
ommended. A cold alignment and a hot check (with cor-
rections, if necessary) are required. The hub flange OD
can be used to mount the alignment equipment and is ma-
chined to be concentric to the coupling bore. It can be
used as the reference diameter.
3. Final Assembly — The terminology used to identify parts
and the order of assembly may differ from one coupling
style to another. Follow the instructions that apply to the
coupling you are installing.
e. Place the disc pack nuts on the bolts. Tighten all nuts
evenly and in an alternating fashion to the torque speci-
fied in Table 9.
Low Speed Coupling (Close-Coupled Style):
a. Place the disc pack and adapter in position over the
hub body diameter. The reamed holes in the adapter
should be aligned with the large clearance holes in the
hub as in the upper portion of Fig. 30. The large clear-
ance holes in the adapter should be aligned with the
reamed holes in the hub as shown in the lower portion
of Fig. 30.
High Speed Coupling (Spacer Style):
DISK
PACK
ADAPTERS
a. Place the spacer in position between the hub flanges.
Place the disc packs between the flanges on both ends
of the coupling.
SPACING
WASHER
DISC
PACK
BOLT
b. Insert the disc pack bolt into the reamed hole of the
hub and through the disc pack bushing. See Fig. 29
(compressor side). The flat of the bolt head acts as a
bolt lock with the hub body. Make sure the spacer is
properly indexed for the large flange holes to receive
the bolt ends. Tap the bolts lightly for full engagement
until the heads rest on the hub flange surface. Repeat
for the other bolts.
DISC
PACK
NUT
HUB
MOTOR
SIDE
GEAR
SIDE
c. Place the spacing washers and disc pack nuts on the
bolts. Tighten all nuts evenly and in an alternating fash-
ion to the torque specified in Table 9.
SHAFT
PREPARATION
(0.19 IN.
[4.83 mm]
d. Place a spacing washer over a disc pack bolt. Insert
the bolt through the large hub flange hole and the disc
pack bushing. See Fig. 29 (gear side). Tap the bolts
lightly for full engagement. Repeat for the other bolts.
FLANGE BOLT
FLANGE NUT
NOTE: Motor rotor should be positioned on the mechanical center
and gear shaft should be on geometric center when coupling is po-
sitioned as shown.
Fig. 30 — Typical Low Speed Coupling for 17FX
Compressor/External Gear (Close Coupled)
b. Loosely assemble the disc pack bolts, nuts, and spac-
ing washers. Half of the bolts attach the adapter to the
disc pack. Refer to Fig. 30. These bolts are inter-
spersed by bolts that attach the disc pack to the hub.
c. Tighten all nuts evenly and in an alternating fashion to
the torque specified in Table 9.
d. Bring the driving and driven equipment together until
the flanges of the adapters just begin to touch. If there
is a gap between the flanges at any point, adjust the
axial position of the equipment until the amount of
gap is cut in half to minimize the amount of axial mis-
alignment.
e. Rotate the equipment shafts until the flange holes are
aligned.
f. Bolt the flanges together using the flange bolts and nuts.
See Fig. 30. Tighten all flange nuts evenly and in a
alternating fashion to the torque specified in Table 10.
NOTES:
1. Compressor shaft should be in the thrust position and gear shaft
should be on geometric center when coupling is positioned as shown.
2. The taper is 1 inch per side for the driven unit bore (compressor
side).
Fig. 29 — Typical High Speed Coupling for 17FX
Compressor/External Gear (Spacer Style)
Table 10 — Flange Nut Tightening Torques
(Low Speed Couplings Only)
Table 9 — Disc Pack Nut Tightening Torques
Torque
(dry)
Torque
(lubed)*
N-M
Coupling
Size
Nut
Tightening
ft-lb
Tightening
ft-lb
Torque
(dry)
Torque
(lubed)*
N-M
Coupling
Size
Nut
Tightening
ft-lb
Tightening
ft-lb
Size
N-m
Size
N-m
204
304
1/2-20
5/8-18
55
75
45
90
60
304
5/16-24
20
27
18
24
115
155
120
*Light machine oil.
*Light machine oil.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
4. General Recommendations
3. When a steady motor current value in the desired range
is reached, compare the MOTOR RATED LOAD AMPS
value on the STATUS01 screen to the actual amps shown
on the ammeter on the starter. Adjust the amps value on
the STATUS01 screen to match the actual value on the
a. Both disc couplings are designed to operate for ex-
tended periods without the need for lubrication or main-
tenance. Visual inspection of the disc packs is enough
to assess the operational condition of the coupling.
starter ammeter, if there is a difference. Highlight the amps
value; then, press the SELECT softkey. Press the
INCREASE or DECREASE softkey to bring the value
b. All machinery should be monitored to detect unusual
or changing vibration levels. Both couplings, under nor-
mal operating conditions, have no wearing parts and
retain their original balance quality. Any change in vi-
bration levels should be investigated, and remedial ac-
tion should be taken immediately.
to that indicated on the ammeter. Press ENTER when
the values are equal.
4. Release the target guide vane position to automatic mode.
See the section on Manual Operation of the Guide Vanes,
page 58, for instructions on how to do this.
5. Removal
a. Disassemble the coupling in the reverse order of the
applicable assembly procedure.
To Prevent Accidental Start-Up — The PIC can be
configured so that starting the unit is more difficult than just
b. Keyed couplings — Install a puller on the hub using
the tapped holes provided in the hub face. Pull the hub
off the shaft.
pressing the LOCAL or CCN softkeys during chiller serv-
ice or whenever necessary. Access the STATUS01
screen, and highlight the CHILLER START/STOP param-
IMPORTANT INFORMATION:
eter. Override the value by pressing SELECT and then the
STOP and ENTER softkeys. The word SUPVSR ap-
pears. When attempting to restart the chiller, remember to
release the override. Access the STATUS01 screen and high-
light CHILLER START/STOP. The 3 softkeys represent 3
choices:
• START - forces the chiller ON.
• STOP - forces the chiller OFF
• RELEASE - puts the chiller under remote or schedule
control.
To return the chiller to normal control, press the
RELEASE softkey; then, press the ENTER softkey. For
Coupling guards protect personnel. ALL COUPLINGS
MUST BE COVERED WITH A GUARD ACCORD-
ING TO OSHA (Occupational Safety and Health
Administration) REQUIREMENTS. Safety guards are
included with this product and must be installed at all
times.
1. Recheck alignment after all foundation bolts and me-
chanical connections are tightened.
2. Make sure all fasteners are properly installed and
tightened.
3. Take the time to double check your work.
additional information, see Local Start-Up, page 43.
The default LID screen message indicates which com-
mand is in effect.
4. Only authorized disc coupling manufacturer replacement
parts are to be used.
5. Call the disc coupling manufacturer for any clarifications
or questions.
Hot Alignment Check — The operating temperatures
of various chiller components can affect the alignment of the
compressor with the heat exchangers, gear, and driver. When
all the chiller components have reached operating tempera-
ture (after running at nearly full load for 4 to 8 hours), make
a hot alignment check.
The self-locking nuts on the disc pack bolts should
be replaced after they have been assembled and re-
moved from the bolts 5 times.
Using proper equipment and procedures, make the hot align-
ment check with either assembled or disassembled cou-
plings. The procedures are detailed in the General Mainte-
nance section, page 67.
A clamping tool, Part No. TS-170, is available for check-
ing alignment without disassembling the couplings. Check
with your local Carrier representative.
Check Oil Pressure and Compressor Stop
1. When the motor is up to full speed, note the differential
compressor oil pressure reading on the LID default screen.
It should be between 18 and 30 psid (124 to 206 kPad).
2. Press the Stop button and listen for any unusual sounds
from the compressor as it coasts to a stop.
Calibrate Motor Current Demand Setting
1. Make sure that the MOTOR RATED LOAD AMPS pa-
rameter on the SERVICE1 screen has been configured.
Place an ammeter on the line that passes through the mo-
tor load current transfer on the motor side of the power
factor correction capacitors (if provided).
2. Start the compressor and establish a steady motor current
value between 70% and 100% RLA by manually over-
riding the guide vane target value (TARGET GUIDE VANE
POS parameter on the STATUS01 screen) and setting the
chilled water set point (WATER/BRINE SETPOINT on the
STATUS01 screen) to a low value. Do not exceed 105%
of the nameplate RLA (rated load amps).
Never operate the compressor or drive with the cou-
pling guards removed. Serious injury can result from
contact with rotating equipment.
Doweling — The size, quantity, and location of dowels
vary considerably with type and arrangement of gear and
drive. Check your job data for specific doweling instruc-
tions. Typical doweling practices are described in the Gen-
eral Maintenance section.
Check Chiller Operating Condition — Check to
be sure that chiller temperatures, pressures, water flows, and
oil and refrigerant levels indicate that the system is func-
tioning properly.
61
Download from Www.Somanuals.com. All Manuals Search And Download.
2. On the LID default screen, press the LOCAL or
Instruct the Operator — Check to be sure that the op-
erator(s) understands all operating and maintenance proce-
dures. Point out the various chiller parts and explain their
function as part of the complete system.
COOLER-CONDENSER — Relief devices, temperature sen-
sor locations, pressure transducer locations, Schrader fit-
tings, waterboxes and tubes, and vents and drains.
CCN softkey to start the system. If the schedule indi-
cates that the current time and date have been established
as a run time and date (a condition referred to as ‘‘oc-
cupied’’) and the 3- and 15-minute start timers have ex-
pired, the start sequence will start. Follow the procedure
described in the Start-Up/Shutdown/Recycle Sequence
section, page 43.
ECONOMIZER/STORAGE VESSEL — Float chambers, re-
lief valves, charging valve.
Check the Running System — After the compres-
sor starts, monitor the LID display and observe the param-
eters for normal operating conditions:
1. The oil reservoir temperature should be above 150 F
(66 C) or refrigerant temperature plus 70° F (38° C) dur-
ing shutdown and above 125 F (52 C) during compressor
operation.
2. The bearing oil temperature (BEARING TEMPERA-
TURE on the STATUS01 screen) should be 150 to 200 F
(65 to 93 C). If the bearing oil temperature reads more
than 210 F (99 C) with the oil pump running, stop the
chiller and determine the cause of the high temperature.
Do not restart the chiller until corrected.
3. The oil level should be visible in the lower sight glass
when the compressor is running. At shutdown, oil level
should be halfway in the lower sight glass.
PUMPOUT SYSTEM — Transfer valves and pumpout sys-
tem, refrigerant charging and pumpdown procedure, lubri-
cation, and relief devices.
COMPRESSOR ASSEMBLY — Guide vane actuator, trans-
mission, oil cooling system, temperature and pressure sen-
sors, oil sight glasses, integral oil pump, isolatable oil filter,
extra oil and motor temperature sensors, synthetic oil, and
compressor serviceability.
COMPRESSOR LUBRICATION SYSTEM — Oil pump,
cooler filter, oil heater, oil charge and specification, operat-
ing and shutdown oil level, temperature and pressure, oil charg-
ing connections, and seal oil chambers.
EXTERNAL GEAR LUBRICATION SYSTEM — Oil pump,
cooler/filter, oil charge and specification, operating and shut-
down oil level, temperature and pressure, and oil charging
procedures.
4. The oil pressure should be between 18 and 30 psid (124
to 207 kPad) differential, as seen on the LID default
screen. Typically the reading will be 18 to 25 psid (124
to 172 kPad) at initial start-up.
CONTROL SYSTEM — CCN and local start, reset, menu,
softkey functions, LID operation, occupancy schedule, set
points, safety controls, and auxiliary and optional controls.
5. The condenser pressure and temperature vary with the chiller
design conditions. Typically the pressure ranges between
57 and 135 psig (393 and 930 kPa) with a corresponding
temperature range of 60 to 105 F (15 to 41 C) for R-134a.
The condenser entering water temperature should be con-
trolled to remain below the specified design entering wa-
ter temperature to save on compressor kilowatt require-
ments. The leaving condenser water temperature should
be at least 20° F (11° C) above leaving chilled water
temperature.
6. Cooler pressure and temperature also vary with the de-
sign conditions. Typical cooler pressure ranges between
30 and 40 psig (206 and 275 kPa); temperature ranges
between 34 and 45 F (1 and 8 C) for R-134a).
AUXILIARY EQUIPMENT — Starters and disconnects, sepa-
rate electrical sources, pumps, and cooling tower.
CHILLER CYCLES — Refrigerant, motor cooling, lubri-
cation, and oil reclaim cycles.
MAINTENANCE — Scheduled, routine, and extended shut-
downs; importance of a log sheet, water treatment, tube clean-
ing, and maintaining a leak-free chiller.
SAFETY DEVICES AND PROCEDURES — Electrical dis-
connects, relief device inspection, and handling refrigerant.
CHECK OPERATOR KNOWLEDGE — Start, stop, and shut-
down procedures, safety and operating controls, refrigerant
and oil charging, and job safety.
7. The compressor may operate at full capacity for a short
time after the pulldown ramping has ended, even though
the building load is small. The active electrical demand
setting can be overridden to limit the compressor IkW, or
the pulldown rate can be decreased to avoid a high de-
mand charge for the short period of high demand
operation. Pulldown rate can be based on kW rate (LOAD
PULLDOWN %/MIN) or temperature rate (TEMP PULL-
DOWN DEG/MIN) These parameters may be accessed
on the CONFIG screen (see Table 2, Example 6).
THIS MANUAL — Be sure that the operator is familiar with
the contents of this manual.
OPERATING INSTRUCTIONS
Operator Duties
1. Become familiar with chiller refrigeration and related equip-
ment before operating the chiller.
2. Prepare the system for start-up, start and stop the chiller,
and place the system in a shutdown condition.
3. Maintain a log of operating conditions and document any
abnormal readings.
8. The oil pump is energized once every 12 hours during
shutdown periods to ensure that the shaft seal is filled
with oil.
4. Inspect the equipment, make routine adjustments, and per-
form a controls test. Maintain the proper oil and refrig-
erant levels.
5. Protect the system from damage during shutdown
periods.
Stopping the Chiller
1. The occupancy schedule starts and stops the chiller au-
tomatically once the time schedule is set up.
2. Pressing the Stop button on the control panel for one sec-
ond causes the alarm light to blink once to confirm that
the button has been pressed. Then, the compressor fol-
lows the normal shutdown sequence as described in the
Controls section. The chiller is now in the OFF mode.
6. Maintain the set point, time schedules, and other PIC
functions.
Prepare the Chiller for Start-Up — Follow the steps
described in the Initial Start-Up section, page 57.
The chiller will not restart until the CCN or
LOCAL softkey is pressed.
Starting the Chiller
1. Start the water pumps if they are not automatic.
62
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: If the chiller fails to stop, in addition to action that
the PIC initiates, the operator should close the guide vanes
by overriding the guide vane target to zero (to reduce chiller
load) and then by opening the main disconnect. Do not at-
tempt to stop the chiller by opening an isolating knife switch.
High intensity arcing may occur. Do not restart the chiller
until the problem is diagnosed and corrected.
guide vane control and close the guide vanes, if necessary.
For descriptions of capacity overrides and set points, see the
Controls section.
Refrigeration Log — A refrigeration log, such as the
one shown in Fig. 31, is a convenient way to track routine
inspection and maintenance and provides a continuous record
of chiller performance. It is an aid in scheduling routine main-
tenance and in diagnosing chiller problems.
Keep a record of the chiller pressures, temperatures, and
liquid levels on a log similar to Fig. 31. It is possible to au-
tomatically record PIC data by using CCN devices such as
the Data Collection module and a Building Supervisor ter-
minal. Contact your Carrier representative for more
information.
After Limited Shutdown — No special preparations
should be necessary. Follow the regular preliminary checks
and starting procedures. Control power must be maintained
in order to keep the oil temperature hot and all control safe-
ties operational. The oil pump operates occasionally to keep
the contact seal filled with oil to prevent refrigerant loss.
Extended Shutdown — The refrigerant should be trans-
ferred into the economizer/storage vessel (see Pumpout and
Refrigerant Transfer Procedures, this page) in order to re-
duce chiller pressure and the possibility of leaks. Maintain
a holding charge of 5 to 10 lbs (2.27 to 4.5 kg) of refrigerant
within the cooler/condenser/compressor sections, to prevent
air from leaking into the chiller.
If freezing temperatures are likely to occur in the chiller
area, drain the chilled water, condenser water, and the pump-
out condenser water circuits to avoid freeze-up. Keep the
waterbox drains open.
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES
Preparation — The 17EX may come equipped with
an optional pumpout compressor. The refrigerant can be pumped
for service work to either the cooler/condenser/compressor
sections or the economizer/storage vessel by using the pump-
out system. The following procedures describe how to trans-
fer refrigerant from vessel to vessel and perform chiller
evacuations.
Leave the oil charge in the chiller with the oil heater and
controls energized to maintain the minimum oil reservoir
temperature.
To prevent tube freeze-up, always be sure that the con-
denser and cooler water pumps are operating whenever
charging, transferring, or removing refrigerant from the
chiller.
After Extended Shutdown — Be sure that the water
system drains are closed. It may be advisable to flush the
water circuits to remove any soft rust which may have formed.
This is a good time to brush the tubes if necessary.
Check the cooler pressure on the LID default screen, and
compare it to the original holding charge that was left in the
chiller. If (after adjusting for ambient temperature changes)
any loss in pressure is indicated, check for refrigerant leaks.
See the Check Chiller Tightness section, page 46.
If the chiller water pumps are controlled by the PIC, ac-
cess the CONTROL TEST table on the LID and use the
PUMPDOWN/LOCKOUT screen or TERMINATE LOCK-
OUT screen to perform the functions described below. If the
chiller water pumps are not controlled by the PIC, they must
be turned on and off manually.
Recharge the chiller by transferring refrigerant from
the economizer/storage vessel. Follow the Pumpout and Re-
frigerant Transfer Procedures section, this page. Observe
freeze-up precautions.
Carefully make all regular preliminary and running sys-
tem checks. Perform a controls test before start-up. If the
compressor oil level appears abnormally high, the oil may
have absorbed refrigerant. Make sure that the oil tempera-
ture is above 150 F (66 C) or above the cooler refrigerant
temperature plus 70° F (39° C).
When performing pumpout, do not leave the compres-
sor unattended for long periods of time or loss of com-
pressor oil may result. Periodically check oil level.
Operating the Optional Pumpout Compressor
1. Be sure that the suction and the discharge service valves
on the optional pumpout compressor are open (back seated)
during operation. Figure 32 shows the location of these
valves (valves 2, 3, 4, 5, and 8). Rotate the valve stem
fully counterclockwise to open. Front seating the valve
closes the refrigerant line and opens the gage port to com-
pressor pressure.
2. Make sure that the compressor holddown bolts have been
loosened to allow free spring travel.
3. Open the refrigerant inlet valve on the pumpout compressor.
Cold Weather Operation — When the entering con-
denser water temperature is very low, the PIC can automati-
cally cycle the cooling tower fans off to keep the tempera-
ture up. Provide a way to control the condenser water
temperature to the chiller either by arranging a tower bypass
piping system and/or adding a tower water temperature con-
trol system.
4. Oil should be visible in the compressor sight glass under
all operating conditions and during shutdown. If oil is
low, add oil as described under Pumpout System Main-
tenance section, page 83. The pumpout unit control wir-
ing schematic is detailed in Fig. 33. The Optional Pump-
out System is detailed in Fig. 34.
Manual Guide Vane Operation — It is possible to
operate the guide vane manually in order to check control
operations or control the guide vanes in an emergency. This
is done by overriding the target guide vane position. Access
the STATUS01 screen on the LID and highlight TARGET
GUIDE VANE POS. To control the position, enter the de-
sired percentage of guide vane opening. Zero percent is fully
READING REFRIGERANT PRESSURES during pumpout
or leak testing:
closed; 100% is fully open. To release the guide vanes to
automatic operation, press the RELEASE softkey.
1. The LID display on the chiller control center is suitable
for determining refrigerant-side pressures and low (soft)
vacuum. To measure evacuation or dehydration pres-
sures, use a quality vacuum indicator or manometer to
ensure the desired range and accuracy. This can be placed
on the Schrader connections on each vessel by removing
the pressure transducer.
NOTE: Manual guide vane control allows the operator to
manipulate the guide vane position and override the pull-
down rate during start-up. However, motor current above the
electrical demand setting, capacity overrides, and chilled wa-
ter temperature below the control point will override manual
63
Download from Www.Somanuals.com. All Manuals Search And Download.
REFRIGERATION LOG CARRIER 17EX EXTERNALLY GEARED CENTRIFUGAL CHILLER
Chiller Serial No.
Plant
Chiller Model No.
Refrigerant Type
REC. 1
REC. 2
REC. 3
REC. 4
REC. 5
REC. 6
REC. 7
REC. 8
REC. 9
TIME
DATE
OPERATOR INITIALS
COOLER
Refrigerant
Pressure
Temperature
Water
Pressure In
Pressure Out
Pressure GPM
Temperature In
Temperature Out
CONDENSER
Refrigerant
Pressure
Temperature
Water
Pressure In
Pressure Out
Pressure GPM
Temperature In
Temperature Out
COMPRESSOR
Bearing Temperature
Oil
Pressure Differential
Temperature (Reservoir)
Level
Motor
FLA
Amps (or Vane Position)
EXTERNAL GEAR
Bearing Temperature
Oil
Pressure Differential
Temperature (Reservoir)
Level
Motor
FLA
Aps (or Vane Position
REMARKS: On an attached sheet, Indicate shutdowns on safety controls, repairs made, and oil or refrigerant added or removed. Include amounts.
Include time, date, operator initials for each remark.
Fig. 31 — Refrigeration Log
64
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: Location of pumpout compressor may vary depending on ma-
chine arrangement.
9
10
CHILLER
CHARGER VALVE
COOLER
ISOLATION
VALVE
11
7
DRIVE END
COMPRESSOR END
REAR VIEW
Fig. 32 — Pumpout Unit Location and Valve Number Locations
65
Download from Www.Somanuals.com. All Manuals Search And Download.
COMPRESSOR MOTOR
LEGEND
Hz
50
Ph
3
Volts
400
298
230
460
375
Max. RLA
4.7
1
2
—
Compressor Motor
Circuit Disconnect
Control Circuit
3
10.9
9.5
—
3
Disconnect
Contactor
60
3
4.7
C
OL
RLA
T’stat
—
—
—
—
Compressor Overload
Rated Load Amps
Internal Thermostat
3
3.8
Compressor Terminal
Contactor Terminal
Overload Terminal
Pumpout Unit Terminal
Fig. 33 — Pumpout Unit Wiring Schematic
1. Isolate and push refrigerant into the economizer/storage
vessel with the pumpout compressor.
VENT VALVE
a. Valve positions: (Blank spaces indicate open valves).
VALVE
1
2
3
4
5
6
7
8
9
10 11
CONDITION
C
C
C
C
C
C
VALVES
b. Turn off the chiller water pumps and pumpout con-
denser water.
c. Turn on pumpout compressor to push liquid out of the
cooler/condenser/compressor section.
d. When all liquid has been pushed into the economizer/
storage vessel, close the cooler isolation valve 7.
e. Access the CONTROL TEST table on the LID. Select
the PUMPDOWN/LOCKOUT screen. From this screen,
turn on the chiller water pumps and view the chiller
pressures.
CONTROL BOX
(WIRING BY
VALVES
CONTRACTOR)
COMPRESSOR
f. Turn off pumpout compressor.
CONDENSER
WATER
CONNECTIONS
(FIELD PIPING)
2. Evacuate refrigerant gas from the cooler/condenser/
compressor vessel.
CONDENSER
DISCHARGE VALVE
a. Valve positions: close valves 2 and 5, open valves 3
and 4.
Fig. 34 — Optional Pumpout Compressor
VALVE
1
2
3
4
5
6
7
8
9
10 11
CONDITION
C
C
C
C
C
C
C
2. To determine economizer/storage vessel pressure, attach
a 30 in.-0-400 psi (-101-0-2760 kPa) gage to the vessel.
3. Refer to Fig. 32 for valve locations and numbers.
b. Turn on the pumpout condenser water.
c. Run the pumpout compressor until the suction reaches
15 in. Hg (50 kPa abs). Monitor pressures on the LID
and on the refrigerant gages.
d. Close valve 1.
e. Turn off pumpout compressor.
f. Close valves 3, 4, and 6. (All valves are now closed.)
g. Turn off pumpout condenser water.
Transfer, addition, or removal of refrigerant in spring-
isolated chillers may place severe stress on external pip-
ing if springs have not been blocked in both up and down
directions.
h. Use the PUMPDOWN LOCKOUT screen on the LID
to turn off the chiller water pumps and to lock out the
chiller compressor from operation.
Transferring Refrigerant into the Economizer/
Storage Vessel — These steps describe the method of
moving refrigerant from the cooler/condenser/compressor sec-
tions into the economizer/storage vessel. This is normally
done to prepare for service work on the cooler, condenser, or
the compressor components or for long-term chiller
shutdown.
66
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Continue to use the TERMINATE/LOCKOUT function
on the LID to turn off water pumps and enable the com-
pressor to operate.
Transferring Refrigerant into the Cooler/
Condenser/Compressor Section — These steps de-
scribe how to transfer refrigerant from the economizer/
storage vessel into the cooler/condenser/compressor section.
This is normally done to prepare for service work on the
economizer/storage vessel.
1. Isolate and push refrigerant into the cooler/condenser/
compressor section:
GENERAL MAINTENANCE
Refrigerant Properties — Refrigerant HFC-134a is
the standard refrigerant in the 17EX. At normal atmospheric
pressure, HFC-134a boils at −14 F (−25 C) and must, there-
fore, be kept in pressurized containers or storage tanks. The
refrigerant is practically odorless when mixed with air. This
refrigerant is non-combustible at atmospheric pressure. Read
the Material Safety Data Sheet (MSDS) and the latest ASHRAE
Safety Guide for Mechanical Refrigeration to learn more about
safe handling of this refrigerant.
a. Valve positions:
VALVE
1
2
3
4
5
6
7
8
9
10 11
CONDITION
C
C
C
C
C
C
b. Turn off chiller water pumps and pumpout condenser
water.
c. Turn on the pumpout compressor to push refrigerant
out of the economizer/storage vessel.
Refrigerant HFC-134a will dissolve oil and some non-
metallic materials, dry the skin, and, in heavy concen-
trations, may displace enough oxygen to cause asphyxi-
ation. When handling this refrigerant, protect the hands
and eyes and avoid breathing fumes.
d. When all liquid refrigerant is out of the economizer/
storage vessel, close the cooler isolation valve 7.
e. Turn off the pumpout compressor.
2. Evacuate refrigerant from the economizer/storage vessel.
a. Access the CONTROL TEST table on the LID. Select
the PUMPDOWN LOCKOUT screen. From this screen,
turn on the chiller water pumps and monitor vessel
pressures.
Adding Refrigerant — Follow the procedures de-
scribed in Charge Refrigerant into Chiller section, page 57.
b. Valve positions: Close valves 3 and 4, open valves 2
and 5.
Use the PUMPDOWN LOCKOUT function on the CON-
TROL TEST table to turn on the chiller water pumps
and lock out the compressor when transferring refrig-
erant. Liquid refrigerant may flash into a gas and cause
possible freeze-up when the chiller pressure is below
30 psig (207 kPa) for HFC-134a. If the water pumps are
not controlled by the PIC, they must be controlled
manually.
VALVE
1
2
3
4
5
6
7
8
9
10 11
CONDITION
C
C
C
C
C
C
C
c. Turn on the pumpout condenser water.
d. Run the pumpout compressor until the suction reaches
15 in. Hg (50 kPa abs). Monitor pressures on the LID
and on refrigerant gages.
e. Close valve 6.
f. Turn off the pumpout compressor.
Removing Refrigerant — When the optional pump-
out system is used, the 17EX refrigerant charge may be trans-
ferred into the economizer/storage vessel or another storage
vessel. Follow procedures in the Pumpout and Refrigerant
Transfer Procedures section when removing or transferring
refrigerant.
g. Close valves 1, 2, and 5 (all valves are now closed).
h. Turn off the pumpout condenser water.
i. From the CONTROL TEST table on the LID, turn off
the chiller water pumps and lock out the chiller com-
pressor from operation.
Return Chiller to Normal Operating Conditions
1. Be sure that the vessel that was opened has been evacu-
ated and dehydrated.
2. Access the CONTROL TEST table. From this table, se-
lect the TERMINATE LOCKOUT function to view the
vessel pressures and to turn on chiller water pumps.
3. Open valves 1, 3, and 6.
Adjusting the Refrigerant Charge — If it is nec-
essary to add or remove refrigerant to improve chiller per-
formance, follow the procedures under the Trimming Refrigerant
Charge section.
Refrigerant Leak Testing — Because HFC-134a is
above atmospheric pressure at room temperature, leak test-
ing can be performed with refrigerant in the chiller. Use an
electronic detector, soap bubble solution, or ultra-sonic leak
detector. To keep false readings to a minimum, be sure that
the room is well ventilated and free from concentration of
refrigerant. Before making any necessary repairs to a leak,
transfer all refrigerant from the leaking vessel.
VALVE
1
2
3
4
5
6
7
8
9
10 11
CONDITION
C
C
C
C
C
C
C
C
4. Slowly open valve 5, gradually increasing pressure
in the evacuated vessel to 35 psig (141 kPa)
for HFC-134a. Feed refrigerant slowly to prevent
freeze-up.
5. Perform a leak test at 35 psig (141 kPa).
6. Open valve 5 fully. Let the vessel pressures equalize.
Leak Rate — The ASHRAE recommendation is that chill-
ers should be immediately taken off line and repaired if the
refrigerant leak rate for the entire chiller is more than 10%
of the operating refrigerant charge per year.
VALVE
1
2
3
4
5
6
7
8
9
10 11
Additionally, Carrier recommends that leaks totalling less
than the above rate but more than a rate of 1 lb (0.5 kg) per
year should be repaired during annual maintenance or when-
ever the refrigerant is pumped over for other service work.
CONDITION
C
C
C
C
C
C
C
7. Open valves 9 and 10.
8. Open valve 7 to equalize liquid refrigerant levels.
9. Close valves 1, 3, 5, and 6.
Test After Service, Repair, or Major Leak — If
all refrigerant has been lost or if the chiller has been opened
for service, the chiller or the affected vessels must be pres-
sure and leak tested. Refer to the Leak Test Chiller section
(page 46) to perform a leak test.
VALVE
1
2
3
4
5
6
7
8
9
10 11
CONDITION
C
C
C
C
C
C
C
C
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant HFC-134a MUST NOT be mixed with air
or oxygen and pressurized for leak testing. In general,
this refrigerant should not be allowed to be present
with high concentrations of air or oxygen above atmo-
spheric pressures, because the mixture can undergo
combustion.
REFRIGERANT TRACER — Use an environmentally ac-
ceptable refrigerant as a tracer for leak test procedures.
TO PRESSURIZE WITH DRY NITROGEN — Another
method of leak testing is to pressurize with nitrogen only
and use a soap bubble solution or an ultrasonic leak detector
to determine if leaks are present. This should only be done
if all refrigerant has been evacuated from the vessel.
1. Connect a copper tube from the pressure regulator on the
cylinder to the refrigerant charging valve. Never apply
full cylinder pressure to the pressurizing line. Follow the
listed sequence.
2. Open the charging valve fully.
3. Slowly open the cylinder regulating valve.
Fig. 35 — Electronic Vane Actuator Linkage
4. Observe the pressure gage on the chiller and close the
regulating valve when the pressure reaches test level. Do
not exceed 140 psi (965 kPa).
5. Close the charging valve on the chiller. Remove the cop-
per tube if no longer required.
During shutdown, no refrigerant should be detected ex-
cept for minute outgassing from residual oil in the seal area.
There should be no oil seepage. If oil flow or the presence
of refrigerant is noted while the chiller is shut down, a seal
defect is indicated. Arrange for a seal assembly inspection
by a qualified serviceman to determine the cause of the leak-
age and make the necessary repairs.
Repair the Leak, Retest, and Apply Standing
Vacuum Test — After pressurizing the chiller, test for
leaks with an electronic leak detector, soap bubble solution,
or an ultrasonic leak detector. Bring the chiller back to at-
mospheric pressure, repair any leaks found, and retest.
After retesting and finding no leaks, apply a standing vacuum
test, and then dehydrate the chiller. Refer to the Standing
Vacuum Test and Chiller Dehydration in the Before Initial
Start-Up section, page 49.
SEAL DISASSEMBLY (Fig. 36) — Contact seal disassem-
bly and repair should be performed only by well qualified
compressor maintenance personnel. These disassembly in-
structions are included only as a convenient reference for
the authorized serviceman.
For ease of disassembly, refer to Fig. 36 while following
these instructions.
1. Remove refrigerant.
Checking Guide Vane Linkage — Refer to Fig. 35.
2. Remove compressor shaft coupling hub and coupling spacer
(if any).
If slack develops in the drive chain, eliminate backlash as
follows:
3. The snap ring (Item 16) used for seal assembly/disassembly
is clipped over three screws (Item 41) on the windage
baffle (Item 7). Remove the snap ring and put it aside
for now.
4. Remove the screws holding the windage baffle and the
shaft end labyrinth (Item 8).
1. With the chiller shut down (guide vanes closed), remove
the chain guard, loosen the actuator holddown bolts, and
remove the chain.
2. Loosen the vane sprocket set screw and rotate the sprocket
wheel until the set screw clears the existing spotting hole.
3. With the set screw still loose, replace the chain, and move
the vane actuator to the left until all the chain slack is
taken up.
4. Tighten the actuator holddown bolts and retighten the set
screw in the new position.
5. Remove the contact sleeve key (Item 11).
6. Using a snap ring tool, install the snap ring (Item 16) in
the groove on the end of the contact sleeve (Item 18), as
shown in Fig. 36.
7. Remove the tubing between the coupling (Item 20) and
the atmospheric oil chamber. Loosen the bolts (Item 6)
holding the coupling guard mounting ring (Item 4) and
the seal housing (Item 3). The spring contact sleeve
(Item 17) will push the housing out until the snap ring
(Item 16) contacts the seal housing (Item 3). To avoid
binding, loosen the bolts in a circular pattern until the
spring stops pushing out on the housing. Then, remove
2 bolts that are 180 degrees apart. Replace them with a
1/2-13 all-thread rod to support the housing while the
rest of the bolts are removed.
5. Realign the chain guard as required to clear the chain.
Contact Seal Maintenance (Refer to Fig. 36) —
During chiller operation, oil that lubricates the seal seeps through
the space between the contact sleeve (Item 18) and the lock
nut (Item 15). This oil slowly accumulates in an atmo-
spheric oil chamber and is automatically returned to the sys-
tem by a seal oil return pump.
Oil should never leak around the outer diameter of the
contact sleeve (Item 18). If oil is found in this area, O-ring
(Item 12) should be checked and replaced.
The oil passing through the shaft seal carries with it some
absorbed refrigerant. As the oil reaches the atmosphere, the
absorbed refrigerant is released from the oil as a vapor. For
this reason, a detector will indicate the presence of a slight
amount of refrigerant around the compressor shaft when-
ever the chiller is running.
8. Remove the rest of the bolts, and remove the seal
housing.
68
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: Adjust shims (Item 33) to main-
tain .525 ± .01 in. (13.3 ± .3 mm) dimen-
sion with shaft thrust toward drive and check
carbon for +.06 minimum travel.
LEGEND
1
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Lubricating Tube
O-Ring
2A
2B
3
O-Ring
Seal Housing
4
Coupling Guard Mounting Ring
1
5
Plain ⁄2-in. Washer (8 Required)
1
6
Hex Head Bolt,
Windage Baffle
⁄2-13 × 4 lg (8 Required)
7
8
Shaft End Labyrinth
1
3
9
Screw
⁄4
- 20 ×
⁄
4
lg (4 Required)
lg
1
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Screw, 10-24 ×
⁄
2
Key, Contact Sleeve
O-Ring
Compressor Shaft
O-Ring
Lock Nut
Snap Ring (Service tool only; must be removed for operation)
Spring Contact Sleeve
Contact Sleeve
Outer Carbon Ring
Coupling (Connection to atmospheric oil chamber)
Rotating Contact Ring
Diaphragm Retainer
Inner Seal Retaining Screw, 10-24 × 1 lg (14 Required)
Gasket
Diaphragm
Inner Carbon Ring
Inner Seal Spring
Inner Seal Retainer
Seal Gland Sleeve
Spacer
Journal Bearing Housing
Journal Bearing
Inner Seal Shim
Inner Carbon Guide Ring
O-Ring
Inner Carbon Key
Screw, 10-24 × 11⁄4 lg (2 Required)
Retaining Ring
Seal Shoulder
Compressor End Wall
1
Thread Cut Screw, 8-32 ×
⁄
4
lg (3 Required)
Screw, 5⁄16-18 × 13⁄4 lg (2 Required)
Fig. 36 — Contact Seal
69
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Place a clean, lint-free cloth on a smooth, sturdy work
surface. Place the seal housing assembly on the cloth
with the face of the contact sleeve in contact with the
cloth. While one person pushes down on the housing to
compress the spring, another person must remove the
snap ring. Then, slowly let the seal housing rise until
the spring is fully extended.
10. Remove Items 2B and 12 (O-rings).
11. Slide the outer carbon ring (Item 19) off the shaft.
12. Remove the lubricating tube (Item 1) and gasket
(Item 24).
13. Remove the inner carbon key (Item 36).
3. Place the diaphragm (Item 25) over the inner seal re-
tainer (Item 28). With the best lapped sealing face of the
carbon away from the diaphragm and the notch for the
key centered between two of the bolt holes in the dia-
phragm, gently push the inner carbon ring (Item 26) into
the inner carbon guide ring until it is tight against the
diaphragm. Make sure that the diaphragm is not wrinkled
or folded between the carbon and the retainer. Place the
spring (Item 27) over the back of the guide ring. Place
this assembly into the seal, and make sure that the car-
bon face can travel a minimum of 0.06 inches (1.5 mm)
in each direction from the outside edge of the seal gland
sleeve (Item 29).
4. Install the O-ring (Item 14). Slide the rotating contact
ring (Item 21) into position against the seal gland sleeve.
Install the lock nut (Item 15) and tighten it with a
spanner.
5. Gently rotate the inner seal assembly to line up the bolt
holes in the diaphragm with the bolt holes in the inner
seal retainer (Item 28). Place the diaphragm retainer over
the diaphragm with the beveled side toward the dia-
phragm. Install the 14 one-inch long screws (Item 23),
leaving the top 2 holes on either side of the notch in the
carbon open. Tighten to 2 ft-lb.
6. Install the inner carbon key (Item 36) using the 1-1/4-in.
screws (Item 37). Tighten to 2 ft-lb.
7. Install the lubricating tube (Item 1) and gasket (Item 24).
8. Lightly coat the outer carbon ring with compressor oil.
Then, slide the outer carbon ring (Item 19) into position
against the rotating contact ring.
14. Remove the inner seal retaining screws (Item 23) and
the diaphragm retainer (Item 22).
15. Using a spanner wrench, loosen the lock nut (Item 15).
The lock nut has a right-hand thread. Remove the lock
nut. The inner seal spring (Item 27) may push the con-
tact ring part way out as the lock nut is loosened.
16. Carefully slide the rotating contact ring (Item 21) off
the shaft. The ring slips onto the shaft with a very close
tolerance and is prone to sticking. Slide it slowly to avoid
a tight jam. To release, tap gently with a SOFT hammer.
17. Remove O-ring (Item 14). This O-ring will be crushed
into a triangular shape. Since it is not an ordinary O-ring
gland, this is normal. Always replace with a new O-ring.
18. The seal gland sleeve (Item 29) can be removed, but it
is generally not necessary to do so. If the seal gland is
removed, make sure it is reinstalled with the bevel (that
contains the O-ring) facing outward.
9. Install O-ring (Item 12).
19. The inner carbon ring (Item 26), the diaphragm
(Item 25), the inner carbon guide ring (Item 34), and the
inner seal spring (Item 27) can be removed as an as-
sembly. The carbon ring is held to the guide ring by raised
barbs on the guide ring. Carefully pull the carbon ring
from the guide ring. The diaphragm can now be re-
moved from the guide ring. Inspect the diaphragm for
wear.
20. To remove the inner seal retainer (Item 28) and O-ring
(Item 35), use 4 screws (Item 23) in the 4 threaded holes
spaced evenly around the seal retainer to jack the part
out of position.
If the inner seal shims are damaged, carefully measure them
so that a shim package of the same thickness can be in-
stalled. The thickness of the shim package should not be changed
unless the compressor shaft and/or thrust bearing are re-
placed. Replacing either of these items could affect the float
of the inner seal. This float is adjusted by varying the thick-
ness of the shim pack.
10. Place the contact sleeve (Item 18) face down on a clean,
lint-free cloth on a smooth, hard, work surface, and place
the contact sleeve spring over the sleeve. Lightly coat
the outside surface of the contact sleeve with compres-
sor oil. While one person places the seal housing
(Item 3) over the contact sleeve and presses the spring
down, another person must install the snap ring
(Item 16) in the groove around the small end of the con-
tact sleeve. Once the snap ring is firmly seated in the
groove, slowly let the seal housing rise until the snap
ring rests against the housing. Rotate the sleeve in the
seal housing until the key slot in the sleeve is in line
with the bolt hole for the contact sleeve key (Item 11).
11. Install the O-ring (Item 2B) into its groove, and place
the seal housing into position on the compressor. Guide
rods can help accomplish this task. Place the coupling
guard mounting ring (Item 4) over the seal housing, and
fasten both in place with 8 hex-head bolts (Item 6). Draw
in the housing against the seal spring by tightening the
bolts in steps in a crisscross pattern to draw the housing
evenly.
12. Once the bolts have been tightened, remove the snap
ring from the contact sleeve, and set it aside.
13. Install the contact sleeve key (Item 11).
14. Install the shaft end labyrinth (Item 8) and the windage
baffle using screws (Item 9). The split lines of the laby-
rinth and windage baffle should be located 90 degrees
apart.
15. Mount the snap ring (Item 16) on the screws (Item 41)
near the inside surface of the windage baffle.
This completes the disassembly of the seal.
Clean all parts to be reused with solvent, coat with oil and
place in a protected area until needed.
SEAL REASSEMBLY (Fig. 36) — Be sure that all gasket
surfaces are clean and that all holes, including oil holes, are
properly aligned between the gasket and mating flange. Coat
the gasket with oil-graphite mixture to prevent sticking.
1. Install the inner seal retainer (Item 28) and O-ring
(Item 35). Then, remove the bolts to allow installation
of the inner seal assembly.
2. Replace the seal gland sleeve (Item 29) if it has been
removed. Make sure that the plain side is against the
shaft shoulder and that the beveled side is facing
outward.
16. Reconnect the tubing from the atmospheric oil chamber
to the coupling (Item 20).
The reassembly of the seal is complete.
Run the oil pump to fill the seal, and rotate the shaft sev-
eral times by hand before leak testing.
NOTE: If the seal gland sleeve is oriented improperly,
refrigerant will leak under the contact ring.
70
Download from Www.Somanuals.com. All Manuals Search And Download.
Low Speed Coupling Alignment
Chiller Alignment
1. Move the motor with the coupling attached into align-
ment with the gear coupling. The motor must be in its
mechanical center and the gear must be centered between
the thrust collars when determining the motor position
relative to the gear. Adjust the jackscrews to reach close
alignment. Follow the procedure outlined in the Correct-
ing Angular Misalignment and Correcting Parallel Mis-
alignment sections.
2. Maintain the exact hub-to-hub distance as specified in
Fig. 30.
3. Where the shaft ends are very close, a taper gage may be
used in place of the dial indicator.
ALIGNMENT METHODS — There are several established
procedures for aligning shafts. The dial indicator method is
presented here since it is considered to be one of the most
accurate and reliable. Another faster and easier method for
alignment involves using laser alignment tools and comput-
ers. Follow the laser tool manufacturer’s guidelines when
using the laser technique.
Where job conditions such as close-spaced shafts prohibit
the use of dial indicators for coupling face readings, other
instruments such as a taper gage may be used. The same pro-
cedures described for the dial indicator may be used with the
taper gage.
Shafts placed in perfect alignment in the non-operating
(cold) condition will always move out of alignment to some
extent as the chiller warms to operating temperature. In most
cases, this shaft misalignment is acceptable for the initial run-in
period before hot check and alignment can be made (see Hot
Alignment Check section, page 61).
4. Get the motor alignment as close as possible by using the
jackscrew adjustment.
NOTE: The drive shaft end-float at final drive position must
not allow the coupling hub faces to make contact or the cou-
pling shroud to bind.
PRELIMINARY ALIGNMENT — To get within dial indi-
cator range, roughly align the equipment as shown in Fig. 37
and as described below.
Place a straight edge across the OD of one coupling to the
OD of the other. Measure the gap between the straight edge
and the OD of the second coupling with a feeler gage. Then,
by adding or removing shims at each corner, raise or lower
the equipment by the measured amount.
NOTE: The physical configuration of the 17FX compressor
makes the oil sump temperature a more significant factor in
alignment than the suction and discharge temperatures. There-
fore, warm the sump oil to operating temperature (approxi-
mately 140 F [60 C]), if possible, before beginning align-
ment procedures.
General
1. Final shaft alignment must be within .002-in. (.05-mm)
TIR (Total Indicated Runout) in parallel. Angular align-
ment must be within 0.00033 inches per inch of traverse
(0.00033 mm per mm of traverse) across the coupling face
(or inch of indicator swing diameter) at operating tem-
peratures. For example, if a bracket-mounted indicator
moves through a 10-in. diameter circle when measuring
angular misalignment, the allowable dial movement will
be 10 times 0.00033 for a total of 0.0033 in. (0.0033 mm).
In a similar manner, measure the shaft offset from side to
side and jack the equipment over as required to correct.
2. Follow the alignment sequence specified in the Near
Final Alignment section.
3. All alignment work is performed on gear and drive equip-
ment. Once the compressor is bolted in a perfectly level
position and is piped to the cooler and condenser, it must
not be moved prior to hot check.
4. All alignment checks must be made with the equipment
hold-down bolts tightened.
5. In setting dial indicators on zero and when taking read-
ings, both shafts should be tight against their respective
thrust bearings.
6. The space between coupling hub faces must be held to
the dimensions in Fig. 29 and 30.
Fig. 37 — Checking Preliminary Alignment
7. Accept only repeatable readings.
High Speed Coupling Alignment
NEAR FINAL ALIGNMENT — Once the chiller compo-
nents are within dial indicator range, the adjustments for mis-
alignment should be made in a specific sequence. The four
positions of alignment described below are arranged in the
recommended order.
1. Move the gear with the coupling attached into alignment
with the compressor coupling. The compressor must be
in the thrust position and the gear must be centered be-
tween the thrust collars when determining gear position
relative to the compressor. Adjust the jackscrews to reach
close alignment. Follow the procedures outlined in the
Correcting Angular Misalignment and Correcting Paral-
lel Misalignment sections.
1. Angular in elevation — This alignment is adjusted
with shims and is not readily lost in making the other
adjustments.
2. A 5-in. long spacer hub is supplied between the gear and
compressor. Maintain the exact hub-to-hub distance speci-
fied in Fig. 29.
3. Where the shaft ends are very close, a taper gage may be
used in place of the dial indicator.
4. Get the gear alignment as close as possible by using the
jackscrew adjustment.
71
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Parallel in elevation — This alignment is also made with
shims, but it cannot be made while there is angular mis-
alignment in elevation.
3. Angular in plan — This position can easily be lost if placed
ahead of the two adjustments in elevation.
4. Parallel in plan — This adjustment cannot be made while
there is still angular misalignment in plan and can easily be
lost if elevation adjustments are made.
Fig. 38 — Measuring Angular Misalignment
in Elevation
Correcting Angular Misalignment
Preparation — Shaft angular misalignment is measured on
the face of the coupling hubs or on brackets attached to each
shaft (see Fig. 38 and 39). Brackets are preferred since they
extend the diameter of the face readings.
Attach a dial indicator to one coupling hub or shaft and
place the indicator button against the face of the opposite
hub. Position the indicator so that the plunger is at approxi-
mately mid-position when the dial is set to zero. Both shafts
should be held tightly against their thrust bearings when the
dial is set and when readings are taken.
Fig. 39 — Measuring Angular Misalignment
in Elevation Using Brackets
Measurement — Occasionally, coupling faces may not be per-
fectly true or may have been damaged in handling. To com-
pensate for any such runout, determine the actual or ‘‘net’’
shaft misalignment as follows:
To be sure that the indicator linkage is tight and the button
is on securely, rotate the coupling exactly 360 degrees. The
dial reading should return to zero. Accept only repeatable
readings.
Check the opening at the top and at the bottom of the cou-
pling faces (or at each side when making plan adjustment).
Rotate both shafts exactly 180 degrees and recheck the open-
ings. Record the difference. (Example below is in inches.)
72
Download from Www.Somanuals.com. All Manuals Search And Download.
If the larger opening remains the same but changes from
side to side, the shafts are in perfect alignment. The change
in opening is due entirely to coupling runout, as above, or to
a burr or other damage to the coupling face.
Obtain:
D — coupling face diameter in inches (or indicator but-
ton circle)
L — distance between front and rear holddown bolts
(inches)
M — net misalignment in inches
And:
Divide L, the bolt distance, by D, the coupling diameter.
Multiply the result by M, the net misalignment.
L
D
S =
× M
Example: Face diameter 5 in. (D). Distance between front
and rear holddown bolts 30 in. (L). Net misalign-
ment in elevation .012 in. (M).
30 divided by 5 is 6
6 multiplied by .012 is .072 in.
S = .072 in.
If the larger opening between coupling faces is at the top,
place .072 in. of shim under each rear foot or remove
.072 in. from the front footings to bring the couplings into
angular alignment in elevation.
Tighten the holddown bolts and recheck the net
misalignment.
If the larger opening remains the same, and remains
on the same side, the amount is entirely shaft (net)
misalignment.
The height of the shaft above the footings and the dis-
tance the shaft extends beyond the equipment will not affect
the calculations.
Determine the angular adjustment in plan by the same method
of calculation. At this point, however, the procedure should
include a correction for the change in coupling gap which
always occurs in adjusting angular alignment (Fig. 40). By
selecting the proper pivot point (see Fig. 41), the coupling
gap can be kept at the dimension specified in the job data.
1. Pivot on the front bolt at the closed side of the couplings
to shorten the gap; pivot on the front bolt at the open side
to lengthen it. It may sometimes be advantageous to pivot
half the required amount on one front footing and half on
the other.
2. Place a dial indicator against the rear foot as indicated in
Fig. 41.
If the larger opening remains on the same side but changes
amount, misalignment and runout are present. Add the two
amounts and then divide by two to get the actual or net
misalignment.
3. Place a screw jack on the other rear foot to move the equip-
ment towards the indicator.
If the larger opening changes amount and also changes
from side to side, subtract the smaller amount from the larger
and divide by two to obtain the net misalignment.
Adjustment — Having obtained the net misalignment, the
amount by which the equipment must be moved can now be
calculated.
S
L
—
—
Thickness of Shim Required
Distance Between Front and
Rear Holddown Bolt in Inches
Diameter of Coupling in Inches
Net Misalignment in Inches
To determine:
D
M
—
—
S — amount of movement (in plan) or the thickness of
shim (in elevation) required.
Fig. 40 — Alignment Formula
73
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Loosen all holddown bolts except the pivot bolt. Turn the
screw jack until the rear end of the equipment moves against
the indicator by the desired amount.
5. Tighten the holddown bolts and recheck the indicator. If
the reading has changed, loosen the three bolts and re-
adjust. It may be necessary to over or undershoot the de-
sired reading to allow for the effect of bolt tightening.
Measurement — With dial set at zero in the top position,
rotate the shaft to which the indicator is attached 180 de-
grees. If the dial reading is plus, the shaft on which the but-
ton rests is low. If the reading is minus, the shaft on which
the button rests is high.
Never accept a single reading. Look for repeatability. Ro-
tate the shaft several times to see if the reading remains the
same. It is good practice to reverse the procedure and read
from zero at the bottom.
Always rotate the shafts in the same direction when tak-
ing readings. Backlash in the coupling teeth could cause some
differences.
Adjustment — Divide the total indicator reading by two to
obtain the exact amount of shaft offset. As illustrated in
Fig. 42, the indicator will read the total of A plus B but the
required shaft adjustment is only half of this as indicated
by C.
Add or remove identical amounts of shims at all footings
to bring the shaft to the proper elevation. Tighten all the hold-
down bolts and recheck the readings. Parallel alignment must
be within .002 TIR.
To correct parallel misalignment in plan, use a screw jack
and dial indicator as shown in Fig. 42. With a front hold-
down bolt as the pivot, move the rear of the equipment over.
Then, with the rear holddown bolt on the same side acting
as the pivot, move the front end of the equipment over by
the same amount.
FINAL ALIGNMENT — The procedures and tolerance re-
quirements for final alignment are the same as those de-
scribed in the Near Final Alignment section. Final alignment
is performed just prior to grouting and chiller hot check. All
piping, including water and steam, must be completed, but
the water and refrigerant charges need not be in place.
HOT ALIGNMENT CHECK
General — When all chiller components have reached op-
erating temperature (after running near full load for from 4
to 8 hours), a hot alignment check must be made. Hot align-
ment check may be made with couplings assembled or
disassembled.
Disassembled Couplings
1. Shut down chiller.
Fig. 41 — Adjusting Angular Misalignment in Plan
Correcting Parallel Misalignment
Preparation — Attach the dial indicator to one shaft or cou-
pling hub and place the indicator button on the outside di-
ameter of the other hub. The reach of the dial from one hub
to the other should be parallel to the shafts, and the dial but-
ton shaft should point directly through the center of the shaft
on which it rests. Compress the plunger to about mid-
position and set the dial at zero.
Check the tightness of the dial button and the indicator
linkage by rotating the shaft to which the indicator is at-
tached 360 degrees. The dial should return to zero. Check
for repeatability.
2. With chiller hot, quickly disassemble couplings.
3. Check angular and parallel alignment in plan and eleva-
tion as described in the Near Final Adjustment section.
Record the indicator readings (see page CL-12) and make
necessary adjustments to bring alignment within .002 in.
TIR and .00033 inches per in. of coupling face traverse
(or in. of indicator swing). Follow procedures described
in the Near Final Alignment section.
4. Reinstall couplings and run chiller until it again reaches
operating temperature.
5. Repeat steps 1 through 4 until alignment remains within
specified tolerances.
Check for runout by rotating the hub on which the dial
button rests 180 degrees. If the runout exceeds .001 total in-
dicator reading, the hub should be removed and the shaft
checked. Shaft runout must not exceed .001 TIR.
The effect of hub runout can be eliminated by locating a
position on the half coupling where two readings 180 de-
grees apart read zero. Rotate the coupling so that one zero
point is at the top and the other at the bottom when checking
for misalignment in elevation. Place the zero points side to
side in a similar manner when checking for misalignment in
plan.
Assembled Couplings — If there is room on the shaft be-
tween coupling and component to clamp a sturdy bracket,
the arrangement illustrated in Fig. 43 may be used. The clamps
must have room to rotate with the shaft.
This method is quicker because the couplings do not have
to be disassembled. In addition, eccentricity or coupling face
runout are not problems since both shafts rotate together.
74
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 43 — Alignment Check — Assembled Coupling
5. Recheck the alignment per steps 1 through 4 until it re-
mains within the specified tolerances.
Be sure that coupling guards are replaced after these checks.
DOWELING
Techniques — After a hot alignment check has been com-
pleted, the compressor, gear and drive must be doweled to
their sole plates. Doweling permits exact repositioning of com-
ponents if they have to be moved.
1. Doweling must be completed with equipment at maxi-
mum operating temperature (full load).
2. Use No. 8 taper dowels to dowel the compressor, gear,
and drive to the base. Use a 13⁄32-in. drill and No. 8 taper
reamer with straight flutes. Drill pilot hole and then ex-
pand the pilot hole to final dimension.
3. Fit dowel so that 1⁄16-in. of taper is left above the equip-
ment foot. If dowel holes are re-reamed as a result of re-
alignment, be sure dowels are tight and do not bottom.
4. Place dowels as nearly vertical as possible.
5. Coat the dowels with white lead or other lubricant to pre-
vent rusting.
6. Tap dowel lightly into position with a small machinist’s
hammer. A ringing sound will indicate proper seating.
Dowel the suction end of the compressor base, the two
feet at the high speed end of the gear, and the drive feet in
accordance with the drive manufacturer’s instructions. The
number of dowels used in the drive is usually four, but some
manufacturers require more.
Fig. 42 — Correcting Parallel Misalignment
When using brackets, the diameter in the alignment for-
mula (see Near Final Alignment, Connecting Angular Mis-
alignment section) will be that of the circle through which
the dial indicator rotates.
1. Shut down the chiller.
2. With chiller at operating temperature, quickly install
brackets.
3. Check that alignment is within .002 in. TIR and
.00033 in. per in. of traverse (0.00033 mm per mm of
traverse) across the diameter of measurement. Adjust align-
ment as required. (Refer to Near Final Alignment
section.)
4. Remove brackets and run chiller until operating tempera-
ture is again reached.
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Check the oil level in the motor bearings and observe the
level each week. If additional oil is required, add oil as de-
scribed in the Oil Changes section on page 77. The added oil
must meet Carrier specifications. (See Table 11.) Any addi-
tional oil added or removed should be logged by noting the
amount and date.
WEEKLY MAINTENANCE
Check the Lubrication System — Mark the oil level
on the compressor reservoir sight glass, and observe the level
each week while the chiller is shut down.
If the level goes below the lower sight glass, the oil re-
claim system will need to be checked for proper operation.
If additional oil is required, add oil as follows:
SCHEDULED MAINTENANCE
Establish a regular maintenance schedule based on the ac-
tual chiller requirements such as chiller load, run hours, and
water quality. The time intervals listed in this section are of-
fered as guides to service only.
Oil may be added through the oil drain and charging valve
(Fig. 2, Item 22) using a pump. However, an oil charging
elbow on the seal-oil return chamber (Fig. 4) allows oil to be
added without pumping. The seal oil return pump automati-
cally transfers the oil to the main oil reservoir. A pump is
required for adding oil against refrigerant pressure. The oil
charge is approximately 20 gallons (76 L) for FX (size 531-
599) style compressors. The added oil must meet Carrier’s
specifications. Refer to Changing the Oil Filters and Oil Changes
sections. Any additional oil that is added should be logged
by noting the amount and date. Any oil that is added due to
oil loss that is not related to service will eventually return to
the sump, and must be removed when the level is high.
An oil heater is controlled by the PIC to maintain oil tem-
perature above 150 F (65.5 C) or refrigerant temperature plus
70° F (38.9° C) (see the Controls section) when the com-
pressor is off. The LID STATUS02 screen displays whether
the heater is energized or not (OIL HEATER RELAY). If the
PIC shows that the heater is ON, but the sump is not heating
up, the power to the oil heater may be off or the oil level
may be too low. Check the oil level, the oil heater contactor
voltage, and oil heater resistance.
The PIC does not permit compressor start-up if the oil tem-
perature is too low. The PIC continues with start-up only
after the temperature is within limits.
After the initial start or a 3-hour power failure, the PIC
allows the chiller to start once the oil is up to proper tem-
perature, but uses a slow ramp load rate of 2° F (1.6° C) per
minute.
Be sure that the isolation valves on the oil line near the
filter(s) (Fig. 44) are fully open before operating the com-
pressor.
There are no lubrication requirements for the FX disc
coupling.
Service Ontime — The LID displays a SERVICE ON-
TIME value on the STATUS01 screen. This value should
be reset to zero by the service person or the operator each
time major service work is completed so that time span be-
tween service can be tracked and viewed.
Inspect the Control Center — Maintenance is lim-
ited to general cleaning and tightening of connections. Vacuum
the cabinet to eliminate dust build-up. If the chiller controls
malfunction, refer to the Troubleshooting Guide section for
control checks and adjustments.
Be sure power to the control center is off when
cleaning and tightening connections inside the control
center.
Check Safety and Operating Controls Monthly
— To ensure chiller protection, the automated control test
should be done at least once per month. See Table 3 for safety
control settings.
Changing the Oil Filters
COMPRESSOR OIL FILTER — Change this oil filter an-
nually or whenever the chiller is open for repairs. The 17FX
compressor has an isolatable filter so that the filter may be
changed without removing refrigerant from the chiller. Use
the following procedure.
1. Make sure the compressor is off and that the compressor
disconnect is open.
Check the oil level in the gear reservoir and observe the
level each week. If additional oil is required, add oil as de-
scribed in the Oil Changes section on page 77. The added oil
must meet Carrier specifications. (See Table 11.) Do not over-
fill the reservoir. Any additional oil added or removed should
be logged by noting the amount and date.
2. Disconnect the power to the oil heater and oil pump.
3. Close the valves to the filter.
4. Relieve the pressure from within the filter by using the
pressure connection on the oil feed line valve to the com-
pressor. Run a hose from the connection to a bucket to
catch the oil.
*Water out line is hidden behind oil out line.
Fig. 44 — Typical Compressor or Gear Oil Cooler/Filter
76
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Open the drain located on the shell of the cooler/filter.
Run a hose from the drain to a bucket to catch the oil.
7. Replace the drain fitting, using standard practices to en-
sure a leak-tight joint.
6. Once the pressure has been relieved and the oil drained,
loosen the bolts that hold the cover on the filter body.
Remove the old filter cartridges and replace with a new
filter cartridge. Assemble the filter assembly (filters, spacer,
and stopper assembly), and make sure that the spring is
centered against the filter assembly as shown in Fig. 44.
7. Replace the drain fitting, using standard practices to en-
sure a leak-tight joint. Evacuate the air from the cooler/
filter assembly.
8. Open the isolation valves.
9. Connect power to the oil heater, if equipped, and oil pump.
Operate the oil pump for 2 minutes. Add oil, if required,
to keep the level up in the sight glass.
Oil should be visible in the reservoir sight glass during all
operating and shutdown conditions.
Oil Specifications — If oil is to be added, it must meet
the Carrier specifications shown in Table 11.
8. Once the assembly has been evacuated, open the isola-
tion valves.
9. Connect power to the oil heater and oil pump. The oil
heater should turn on and warm the oil to 140 to 150 F
(60 to 66 C). Operate the oil pump for 2 minutes. Add oil,
if required, to keep the level up in the lower sight glass.
Oil Changes — Carrier recommends changing the oil
after the first year of operation and every three to five years
thereafter as a minimum. Carrier also recommends a yearly
oil analysis. However, if a continuous oil monitoring system
is functioning and a yearly oil analysis is performed, the time
between oil changes can be extended.
Oil should be visible in the reservoir sight glass during all
operating and shutdown conditions.
COMPRESSOR OIL
1. Open the control and oil heater circuit breaker.
2. Drain the oil reservoir by opening the oil charging valve,
(Fig. 2, Item 22). Slowly open the valve against refrig-
erant pressure.
3. Change the oil filter at this time. See the Changing the
Oil Filters section, page 76.
EXTERNAL GEAR OIL FILTER — Change the oil filter
annually or whenever the chiller is open for repairs. The 17EX
external gear lubrication system has an isolatable filter. Use
the following procedure.
1. Make sure that the compressor is off and the compressor
disconnect is open.
2. Disconnect the power to the oil heater, if equipped, and
to the oil pump.
3. Close the line valves to the filter.
4. Relieve any pressure from within the filter by using the
pressure connection on the oil feed line valve to the com-
pressor. Run a hose from the connection to a bucket to
catch the oil.
4. Charge the chiller with approximately 20 gallons (76 L)
of oil for FX (size 531-599) style compressors in order to
bring the level to the middle of the upper sight glass
(Fig. 2, Item 21). Turn on the power to the oil heater and
let the PIC warm it up to at least 140 F (60 C). Operate
the oil pump manually, through the control test, for 2 min-
utes. The oil level should be between the lower sight glass
and one-half full in the upper sight glass for shutdown
conditions.
EXTERNAL GEAR OIL — Proper lubrication is vital to
maintain gear drive performance. After 500 hours or 4 weeks
of initial operation, whichever is first, the external gear drive
should be thoroughly drained, flushed, and refilled with the
proper lubricant. Under normal operating conditions, the lu-
bricant should be changed every 2500 hours or 6 months,
whichever comes first. This change frequency can be ex-
tended if an oil sample analysis indicates a very limited deg-
radation or contamination.
5. Open the drain located on the shell of the cooler/filter.
Run a hose from the connection to a bucket to catch the
oil.
6. Once the pressure has been removed and the oil drained,
loosen the bolts that hold the cover on the filter body.
Remove the oil filter cartridges and replace with new car-
tridges. Assemble the filter assembly (filters, spacer, and
stopper assembly), and make sure that the spring is cen-
tered against the filter assembly, as shown in Fig. 44.
Table 11 — 17EX Chiller Oil Specifications
PUMPOUT
COMPRESSOR
AND OIL
MOTOR SLEEVE
BEARINGS
EXTERNAL
GEAR
SPECIFICATION
Oil Type*
COMPRESSOR
SEPARATOR
Inhitited Polyolester-Based Mineral-Based, Rust and
Rust and Oxidation
Inhibited Oil
Reciprocating
Compressor Oil
Synthetic Compressor Oil
Oxidation Inhibited Turbine
Grade Oil
Viscosity at
100 F (37 C)
ISO 68
(300 SSU)
ISO 32
(150 SSU)
ISO 68
(300 SSU)
ISO 68
(300 SSU)
Carrier Part Number PP23BZ107
Carrier Specification PP47-12
PP23BZ091
PP16-0
PP23BB005
PP16-2
PP23BZ103
PP47-31
Recommended
Manufacturer
ICI, Emkarate RL68H
Mobil, DTE Light
Mobil Oil, DTE Heavy Medium Castrol Icematic SW68
Texaco, Regal R & 0432
Sun Oil, Sunvis 932
Chevron, GST ISO 32
Texaco, Regal UR & 068
Chevron, OC #68
ICI Emkarate RL68HP
NOCO, Turbine T-68
Capacity
20 gal (76 L)
0.6 gal (2.3 L) per bearing
17 gal (41.6L)
Compressor:
4.5 pints (2.6 L)
Oil Separator:
1 pint (0.6 L)
LEGEND
Saybolt Universal Seconds
*Oil type specified for chillers using HFC-134a refrigerant.
SSU
—
77
Download from Www.Somanuals.com. All Manuals Search And Download.
The lubricant should be drained while the gear is at op-
erating temperature. The gear drive should be cleaned with
a flushing oil. Used lubricant and flushing oil should be com-
pletely removed from the system to avoid contaminating new
oil.
Inspect Relief Valves and Piping — The relief valves
on this chiller protect the system against the potentially dan-
gerous effects of overpressure. To ensure against damage to
the equipment and possible injury to personnel, these de-
vices must be kept in peak operating condition.
To change the oil in the external gear:
As a minimum, the following maintenance is required.
1. Make sure that the compressor is off and the disconnect
for the compressor is open.
2. Disconnect the power to the oil heater, if equipped, and
the oil pump.
1. At least once a year, disconnect the vent piping at the
valve outlet and carefully inspect the valve body and mecha-
nism for any evidence of internal corrosion or rust, dirt,
scale, leakage, etc.
2. If corrosion or foreign material is found, do not attempt
3. Open the drain located on the shell of the cooler/filter.
Run a hose from the drain to a bucket to catch the oil.
to repair or recondition. Replace the valve.
3. If the chiller is installed in a corrosive atmosphere or the
relief valves are vented into a corrosive atmosphere, make
valve inspections at more frequent intervals.
4. Once the pressure has been removed and the oil drained,
loosen the bolts that hold the cover on the filter body.
Remove the old filter cartridges. Assemble the filter as-
sembly (filters, spacer, and stopper assembly), and make
sure that the spring is centered against the filter assembly
as shown in Fig. 44.
5. Replace the drain fitting, using standard practices to en-
sure a leak-tight joint.
6. Open the isolation valves and add new oil. Refer to
Table 11 for oil specifications.
Coupling Maintenance — Proper coupling mainte-
nance is important since the coupling supports the outboard
end of the compressor high speed shaft. Clean and inspect
both couplings for wear yearly. Misalignment causes undue
noise and wear. Check alignment yearly, or more often if
vibration or heating occur. Refer to Chiller Alignment sec-
tion, page 71.
7. Connect power to the oil heater, if equipped, and the oil
pump. Operate the oil pump for 2 minutes. Add oil, if
required, to keep the level up in the sight glass.
Never operate the drive without the coupling guards in
place. Contact with a rotating shaft or coupling can cause
serious injury.
MOTOR SLEEVE BEARING AND PUMPOUT COM-
PRESSOR OIL — For instructions on changing the motor
sleeve bearing oil, refer to the section on Motor Mainte-
nance, this page.
For instructions on changing the optional pumpout com-
pressor and oil separator oil, refer to the section on Pumpout
System Maintenance, page 83.
Motor Maintenance — A carefully planned and ex-
ecuted program of inspection and maintenance will do much
to ensure maximum motor availability and minimum main-
tenance cost. If it becomes necessary to repair, recondition,
or rebuild the motor, it is recommended that the nearest West-
inghouse repair facility be consulted.
In addition to a daily observation of the appearance and
operation of the motor, it is recommended that a general in-
spection procedure be established to periodically check the
following items:
Inspect Refrigerant Float System — Inspect the
refrigerant float system once every 5 years or when the
economizer/storage vessel is opened for service. Transfer the
refrigerant into the cooler vessel or into a storage tank. There
are two floats on the 17EX, one on each side of the economizer/
storage vessel. Remove the float access covers. Clean the
chambers and valve assembly thoroughly. Be sure that the
valves move freely. Make sure that all openings are free of
obstructions. Examine the cover gaskets and replace if nec-
essary. See Fig. 45 for a view of both floats.
• cleanliness, both external and internal
• stator and rotor (squirrel-cage) windings
• bearings
Fig. 45 — Typical Float Valve Arrangement
78
Download from Www.Somanuals.com. All Manuals Search And Download.
CLEANLINESS — On open ventilated motors, screens and
louvers over the inlet air openings should not be allowed to
accumulate any build-up of dirt, lint, etc., that could restrict
free air movement. Screens and louvers should never be cleaned
or disturbed while the motor is in operation because any dis-
lodged dirt or debris can be drawn directly into the motor.
If the motor is equipped with air filters, they should be
replaced (disposable type) or cleaned and reconditioned (per-
manent type) at a frequency that is dictated by conditions. It
is better to replace or recondition filters too often than not
often enough.
Adequate ventilation must always be provided in any
area where solvents are being used to avoid the danger
of fire, explosion, or health hazards. In confined areas
(such as pits) each operator should be provided with an
air line respirator, a hose mask, or a self-contained breath-
ing apparatus. Operators should wear goggles, aprons,
and suitable gloves. Solvents and their vapors should
never be exposed to open flames or sparks and should
always be stored in approved safety containers.
SLEEVE BEARINGS
Oil Changing — The oil reservoirs of the self lubricated bear-
ings should be drained and refilled every 6 months. More
frequent changes may be needed if severe oil discoloration
or contamination occurs. In conditions where contamination
does occur, it may be advisable to flush the reservoir with
kerosene to remove any sediment before new oil is added.
Proper care must be taken to thoroughly drain the reservoir
of the flushing material before refilling it with the new oil.
Washing motors using a water spray is not recom-
mended. Manual or compressed air cleaning is pre-
ferred. If it becomes necessary to spray-wash a motor,
it should be done with extreme care. Do not aim high
pressure sprays directly at air inlet openings, conduit con-
nections, shaft seals, or gasketed surfaces to prevent the
possibility of forcing water inside the chiller.
Refill the reservoir to the center of the oil sight glass with
a rust and oxidation inhibited, turbine grade oil. The viscos-
ity of the oil must be 32 ISO (150 SSU) at 100 F (37.7 C).
Oil capacity in each of the 2 bearings is 0.6 gal. (2 l) per
bearing. Use of Carrier Oil Specification PP16-0 is ap-
proved (refer to Table 11).
The stator windings of motors with open ventilation sys-
tems can become contaminated with dirt and other sub-
stances brought into the motor by the ventilating air. Such
contaminants can impair cooling of the winding by clogging
the air passages in the winding end-turns and vent ducts through
the stator core and by reducing heat transfer from the wind-
ing insulation surfaces to the cooling air. Conducting con-
taminants can change or increase electrical stresses on the
insulation, and corrosive contaminants can chemically at-
tack and degrade the insulation. This may lead to shortened
insulation life and stator failure.
Disassembly — The bearing sleeve is spherically seated and
self-aligning. The opposite drive end bearing is normally in-
sulated for larger motors (or when specified). On some mo-
tors, the insulation is bonded to the spherical seat of the bearing
housing. Use extreme care when removing the sleeve from
the insulated support to avoid damaging this insulation.
Several satisfactory methods of cleaning stator windings
and stator cores are offered below:
Note that some bolts and tapped holes associated with the
bearing housings, bearing sleeves, and seals are metric.
Compressed Air — Low pressure (30 psi maximum), clean
(no oil) dry air can be used to dislodge loose dust and par-
ticles in inaccessible areas such as air vent ducts in the stator
core and vent passages in the winding end-turns. Excessive
air pressure can damage insulation and drive contaminants
into inaccessible cracks and crevices.
The following procedure is recommended for removing
the bearing sleeve.
1. Remove the oil drain plug in the housing bottom and
drain the oil sump.
2. Remove all instrumentation sensors that are in contact
with the bearing sleeve. These include resistance tem-
perature detectors, thermocouples, temperature relay bulbs,
thermometers, etc.
Vacuum — Vacuum cleaning can be used, both before and
after other methods of cleaning, to remove loose dirt and
debris. It is a very effective way to remove loose surface
contamination from the winding without scattering it. Vacuum
cleaning tools should be nonmetallic to avoid any damage to
the winding insulation.
3. Remove the end cover.
4. Remove the socket head bolts holding the bearing cap
and the inner air seal together at the horizontal split. The
front end cover plate must also be removed if the front
bearing is being disassembled. Remove the bearing cap
and top half of the inner air seal by lifting straight up to
avoid damaging the labyrinth seals. Place them on a clean,
dry surface to avoid damage to the parting surfaces.
5. Remove any split bolts that may be holding the two bear-
ing halves together. Remove the top half of the bearing
sleeve using suitable eyebolts in the tapped holes pro-
vided. Lift the bearing top straight up and avoid any con-
tact with the shoulders of the shaft journals that might
damage the thrust faces of the bearing. Place on a clean,
dry surface, taking care to prevent damage to either the
parting surfaces or the locating pins that are captive in
the top bearing half.
Wiping — Surface contamination on the winding can be re-
moved by wiping, using a soft, lint-free wiping material. If
the contamination is oily, the wiping material can be moist-
ened (not dripping wet) with a safety-type petroleum sol-
vent, such as Stoddard solvent. In hazardous locations, a solvent
such as inhibited methyl chloroform may be used, but must
be used sparingly and immediately removed. While this sol-
vent is non-flammable under ordinary conditions, it is toxic.
Proper health and safety precautions should be followed while
using it.
Solvents of any type should never be used on windings
provided with abrasion protection. Abrasion protection is a
grey, rubber-like coating applied to the winding end-turns.
6. Remove the 4 screws at the partings in the oil ring and
dismantle the ring by gently tapping the dowel pin ends
with a soft-faced mallet. Remove the ring halves and
immediately reassemble them to avoid any mixup in parts
or damage to the surfaces at the partings.
79
Download from Www.Somanuals.com. All Manuals Search And Download.
7. When removing the labyrinth seals, note the position of
the anti-rotation button located on the inside of the top
half of the seal. Pull up the garter spring surrounding
the floating labyrinth seal and carefully slip out the top
half. Rotate the garter spring until the lock is visible.
Twist counterclockwise to disengage the lock, remove
the garter spring, then rotate the lower half of the seal
out of the groove in the bearing housing while noting
the orientation of the oil drain holes. Note the condition
of these floating labyrinth seals. If they are cracked or
chipped, they must be replaced. Do not attempt to reuse
a damaged seal.
1. The interior of the bearing housing should be cleaned
and then flushed with clean oil or kerosene.
2. The bearing halves and the shaft journal should be wiped
clean using lint-free cloth soaked with clean oil.
3. All parts should be carefully inspected for nicks, scratches,
etc., in any contact surfaces. Such imperfections should
be removed by an appropriate method such as stoning,
scraping, filing, etc., followed by thorough cleaning.
4. Apply a few drops of oil to the journal and bearing saddles.
5. Roll the bottom half of the bearing into place and lower
the shaft.
8. To remove the bottom bearing half, the shaft must be
raised a slight amount to relieve pressure on the bear-
ing. On the rear end, this can be done by jacking or lift-
ing on the shaft extension. (Care must be taken to pro-
tect the shaft from damage.) On the front end, jacking
or lifting can be done using bolts threaded into the tapped
holes provided in the shaft end.
6. Before installing the floating labyrinth seal halves, ob-
serve their condition. Do not attempt to use a cracked or
chipped seal. The bottom half seal has a set of drilled
holes in its side face. These must be placed at the bot-
tom toward the inside of the bearing so that accumu-
lating oil may drain back into the housing.
7. Put a small bead of Curil-T around the bottom seal half
outside diameters on both sides adjacent to the garter
spring groove. This prevents oil from bypassing the seal
around its outside.
NOTE: Lift only enough to free the bearing; over-
lifting the shaft can cause difficulty in removing the
bearing.
9. Roll the bottom bearing half to the top of the shaft jour-
nal and then lift it using suitable eyebolts threaded into
the holes provided. Again, avoid any contact with the
shaft shoulders that could damage the bearing thrust faces.
Place the lower bearing half on a clean, dry surface to
protect the parting surfaces.
8. Place the bottom seal half on top of the shaft (ensuring
that the proper orientation of the drain holes is pro-
vided) and roll it into position. Install the top half of the
seal making sure that the anti-rotation button is located
in the proper position on the inboard side of the bearing.
Insert the garter spring pulling up on both ends to per-
mit engaging the lock. Run a small bead of Curil-T around
the outside diameters on both sides adjacent to the gar-
ter spring groove on this half also.
9. Carefully reassemble the two oil ring halves. Inspect the
dowel pins for burrs and straightness and make any cor-
rections required. Do not force the ring halves together.
Excessive force may alter the roundness or flatness of
the ring which can change its oil delivery performance.
Apply locking compound to the oil ring screws prior to
reassembly.
Use extreme care when rolling out the lower bear-
ing half. Keep the hands and fingers well clear of
any position where they might be caught by the bear-
ing half if it were accidentally released and rotated
back to its bottom position. Serious personal injury
could result.
10. Protect the shaft journal by wrapping it with clean, heavy
paper or cardboard.
10. Assemble the top half of the bearing liner making sure
that the match marks on the liner halves align with one
another. Failure to ensure alignment of match marks can
cause misalignment and possible damage to bearings and
journal surfaces. Reinstall any split bolts, if supplied,
between the bearing halves.
Reassembly — Bearing reassembly is basically a reversal of
the disassembly procedures outlined above, with the follow-
ing additional steps.
11. Some of the pipe plugs in the housing are metric thread
type and have a copper, lead, or similar material washer.
If these plugs are removed, be careful not to lose the
washers. Before reassembly, inspect the washers and re-
place them if required.
Curil-T is the only approved compound for use in the
assembly of the bearings on this motor. Other products
may harden and impede the operation.
12. Before installing the bearing cap, observe the position
of the floating labyrinth seal. The ‘‘tab’’ must be on top
to engage the pocket. Failure to position the seal prop-
erly will result in damage when the cap is assembled.
13. Carefully lower the bearing housing cap over the float-
ing seals. Keep the bearing cap level to avoid binding
and possibly damaging the seals. The bearing cap should
seat evenly on the bearing housing base.
During the reassembly of the bearing parts, a thin layer
of Curil-T should be applied to all gasketed and ma-
chined interface surfaces. This suggestion does not ap-
ply to the machined surfaces of the bearing liner halves.
When seating the bearing shell, apply a thin layer of
lubricating oil at the spherical surface of the liner. Slowly
roll the lower bearing liner into the bearing housing mak-
ing sure that the split surfaces of the liner and the hous-
ing are flush. Gradually lower the shaft onto the bear-
ing. The weight of the shaft will help rotate the bearing
liner so that the babbitt surface of the liner will match
the slope of the journal. Sometimes it is necessary to
use a rubber mallet to tap lightly on the bearing housing
while slowly rolling the shaft to help this seating
operation.
Do not force the bearing cap down. Damage could
occur to the labyrinth seals.
If the bearing cap does not seat completely, remove and
reset the floating labyrinth seal position. When install-
ing upper bearing cap, the floating labyrinth seals some-
times rotate and the anti-rotation ‘‘tab’’ does not seat in
its holder, thus preventing the bearing housing from seat-
ing properly. This procedure should be repeated until
the bearing cap seats properly.
80
Download from Www.Somanuals.com. All Manuals Search And Download.
14. Reinstall the bearing housing split bolts. Before torqu-
ing bearing housing cap bolts, rotate the shaft by hand
while bumping the bearing housing with a rubber or raw-
hide mallet in the horizontal and axial planes to allow
the bearings to align themselves to the shaft journals.
15. Torque the bearing housing cap bolts by following the
torque values as provided in Table 6 on page 51.
provide proper protection while the motor is being stored.
The motor should be stored under cover in a clean, dry lo-
cation and should be protected from rapid temperature changes.
Since moisture can be very detrimental to electrical com-
ponents, the motor temperature should be maintained at ap-
proximately 5° F (3° C) above the dew point temperature by
providing either external or internal heat. If the motor is
equipped with space heaters, they should be energized at the
voltage shown by the space heater nameplate attached to the
motor. Incandescent light bulbs can be placed within the mo-
tor to provide heat. However, if used, they must not be al-
lowed to come in contact with any parts of the motor because
of the concentrated hot spot that could result.
Motor Handling/Rigging — Each motor is provided
with lifting lugs, welded to the four corners of the motor
frame, for lifting the assembled chiller. The motor should
always be lifted by using the lifting lugs located on all four
corners of the motor frame. (See Fig. 46.)
This motor has been provided with a shaft shipping brace
or shipping bolt (normally painted yellow) to prevent shaft
movement during transit, it must be removed to allow shaft
rotation (refer to Before Initial Start-Up, Remove Shipping
Packaging section, page 45). It is very important that this
brace be reinstalled exactly as it was originally, before the
motor is moved from storage or any time when the motor is
being transported. This prevents axial rotor movement that
might damage the bearings.
Spreader bars of adequate capacity and number must be
used to avoid applying any pressure against the top air
housing with the lifting plugs.
Motors equipped with sleeve bearings are shipped from
the factory with the bearing oil reservoirs drained. In stor-
age, the oil reservoirs should be properly filled to the center
of the oil level gage with a good grade of rust inhibiting oil
(refer to the certified drawing for oil viscosity and any spe-
cial requirements). To keep the bearing journals well oiled
and to prevent rusting, the motor shaft should be rotated sev-
eral revolutions every 2 weeks. While the shaft is rotating it
should be pushed to both extremes of the endplay to allow
for oil flow over the entire length of the journals.
External Gear Storage — All internal and unpainted
external surfaces of the gear drives have been treated with a
rust preventative at the factory before shipment. The pro-
tective life of the rust preventative varies with temperature
fluctuations, atmospheric moisture content, degree of expo-
sure to the elements during storage, and degree of contact
with other objects.
Inspect all machined surfaces, and spray or add rust in-
hibitor to exposed metal surfaces that may have had the pro-
tective coating removed during shipping and handling.
To be sure that the gear drive operates satisfactorily at start-
up, take certain precautions when you receive it. The ex-
pected length of storage and the storage atmosphere dictate
the maintenance schedule to be followed. The gear must al-
ways be stored in its operating position, level on its mount-
ing feet, and free of loads or weights on input and output
shafts.
Fig. 46 — Motor Riggings
If the motor is lifted with the top air housing removed, the
angle of the lifting slings with the horizontal should never
be less than 45 degrees.
With the exclusion of the TEWAC cooler, the top air hous-
ing is provided with 3⁄4-10 tapped holes for lifting devices to
be installed in order to remove the air housing from the mo-
tor. The top air housing can be detached by removing the
enclosure holddown bolts, located in the inside corners of
the enclosure. These enclosure holddown bolts are accessed
through the louver/screens located on the front and rear end
of the chiller or through access panels bolted to the sides of
the enclosure.
SHORT-TERM STORAGE (Indoors) — If the units are to
be stored for 30 days or less, observe the following precau-
tions.
• Store the unit in a clean, dry location with the factory pack-
ing intact and with as nearly a constant temperature as
possible.
• Elevate the unit a minimum of 6 in. above the floor level.
• Avoid areas that are subject to extremes in temperature,
vibration, and humidity.
Uneven lifting must always be avoided. When single
point lifting is to be used, slings of equal lengths must
always be used to avoid uneven lifting.
LONG-TERM STORAGE (Indoors) — If the unit is to be
stored for more than 30 days, observe the following precau-
tions. Store in a clean, dry location. Elevate the unit at a
minimum of 6 in. above the ground floor level. Avoid areas
that are subject to extremes in temperature, vibration, and
humidity. In addition, do one of the following:
• Remove the breather and replace it with pipe plugs. Pack
the entire seal area with grease to form a vapor barrier and
seal with tape.
Under no circumstances should the motor be lifted us-
ing the shaft as an attachment point.
NOTE: Refer to weights specified on certified drawing to
determine proper lifting equipment required for specific com-
ponents or assemblies.
Motor Storage — If the chiller is to be placed in ex-
tended shutdown, certain precautions must be taken to
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Fill the gear drive to the recommended oil level with heated
Shell VSI grade 68 oil or its equivalent, heated between
110 and 120 F (43 and 49 C). Do not overfill. Immediately
close the openings to keep the vapors in the housing.
Inspect the unit every 30 days and spray or add rust in-
hibitor suitable for anticipated storage conditions, as
required.
Drain and replace the oil with the recommended oil type
prior to start-up.
• Remove the breather and replace it with a pipe plug. Pack
the entire seal area with grease to form a vapor barrier and
seal it with tape.
A vapor-phase rust inhibitor, such as Daubert Chemical,
Non-Rust Motorstor VCi-10 or its equivalent, may be added
to the recommended oil type in the amount of 2% of the
total sump capacity. Fill the unit to the recommended level.
Do not overfill.
Inspect the unit every 30 days and spray or add rust in-
hibitor suitable for anticipated storage conditions, as
required.
Annually
• Check the heat exchanger for corrosion and clogged tubes.
• Check the bearing clearance and end play.
Disassembly and Assembly Instructions — The following in-
structions apply to standard high speed gear units.
• Required Equipment: In addition to standard mechanic’s
tools, have the following equipment on hand: hoist, sling,
torque wrench, feeler gages, and dial indicator.
• General Instructions: Clean external surfaces of the gear
unit before removing the cover to prevent contaminants
from falling into it. Record the mounting dimensions and
the location of accessories for reference when reassem-
bling. To remove the gear from its operating area, discon-
nect all connected equipment and lift the gear from its
foundation using 4 lifting lugs.
Inspect the Heat Exchanger Tubes
COOLER — Inspect and clean the cooler tubes at the end of
the first operating season. Because these tubes have internal
ridges, a rotary-type tube cleaning system is necessary to fully
clean the tubes. Upon inspection, the tube condition deter-
mines the scheduled frequency for cleaning and indicates
whether water treatment is adequate in the chilled water/
brine circuit. Inspect the entering and leaving chilled water
temperature sensors for signs of slime, corrosion, or scale.
Replace the sensor if corroded or remove any scale if found.
The unit may run without changing this oil mixture.
EXTENDED DOWNTIME — Consider the length of down-
time the unit will undergo. The lubricating oil used in the
unit should protect the interior parts for up to 30 days of
shutdown. If the unit will be shut down longer than 30 days,
it must be operated a minimum of 30 minutes every 30 days
to distribute the lubricant to all interior parts.
If it is impractical to operate the unit every 30 days, the
long-term storage instructions described above must be fol-
lowed. All seals applied for this storage condition must be
removed before operating the unit.
CONDENSER — Since this water circuit is usually an open-
type system, the tubes may be subject to contamination and
scale. Clean the condenser tubes with a rotary tube cleaning
system at least once per year and more often if the water is
contaminated. Inspect the entering and leaving condenser wa-
ter sensors for signs of slime, corrosion, or scale. Replace
the sensor if corroded or remove any scale if found.
Higher than normal condenser pressures, together with the
inability to reach full refrigeration load, usually indicate dirty
tubes or air in the chiller. If the refrigeration log indicates a
rise above normal condenser pressures, check the condenser
refrigerant temperature against the leaving condenser water
temperature. If this reading is more than what the design dif-
ference is supposed to be, then the condenser tubes may be
dirty, or water flow may be incorrect. Because HFC 134a is
a high-pressure refrigerant, air usually does not enter the chiller;
rather, the refrigerant leaks out.
Compressor Bearing Maintenance — The key to
good bearing maintenance is proper lubrication. Use the proper
grade of oil, maintained at recommended level, temperature,
and pressure. Inspect the lubrication system regularly and
thoroughly.
Only a trained service technician should remove and
examine the bearings. The bearings should be examined on
a scheduled basis for signs of wear. The frequency of ex-
amination is determined by the hours of chiller operation,
load conditions during operation, and the condition of the
oil and the lubrication system. Excessive bearing wear can
sometimes be detected through increased vibration or in-
creased bearing temperature. If either symptom appears, con-
tact an experienced and responsible service organization for
assistance.
During the tube cleaning process, use brushes especially
designed to avoid scraping and scratching the tube wall. Con-
tact your Carrier representative to obtain these brushes. Do
not use wire brushes.
External Gear Maintenance — Perform the re-
quired maintenance and recommended intervals. Good pre-
ventive maintenance prolongs the life of the unit.
Hard scale may require chemical treatment for its pre-
vention or removal. Consult a water treatment specialist
for proper treatment.
Daily
• Inspect for leaks and loose connections.
• Check the oil level.
• Check the oil temperature and pressure.
• Check for unusual noise and/or vibration.
Water Leaks — Water in the refrigerant is indicated dur-
ing chiller operation by the refrigerant moisture indicator on
the refrigerant motor cooling line. Water leaks should be re-
paired immediately.
Weekly — Check the oil filter.
Monthly
• Obtain oil sample analysis.
• Clean or replace oil filters.
• Check the foundation mounting bolts for tightness.
• Clean the air filter.
• Check the operation of all auxiliary equipment.
The chiller must be dehydrated after repair of water leaks.
See Chiller Dehydration section, page 49.
Water Treatment — Untreated or improperly treated wa-
ter may result in corrosion, scaling, erosion, or algae. The
services of a qualified water treatment specialist should be
obtained to develop and monitor a treatment program.
Semi-Annually
• Check gear tooth wear.
• Check the oil and replace it if necessary.
• Check the coupling alignment.
82
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Stop the compressor and isolate the system by closing
the discharge service valve.
5. Slowly remove the oil return line connection. Add oil as
required.
6. Replace the connection and reopen the compressor serv-
ice valves.
Water must be within design flow limits, clean, and treated
to ensure proper chiller performance and reduce the po-
tential of tube damage due to corrosion, scaling, ero-
sion, and algae. Carrier assumes no responsibility for
chiller damage resulting from untreated or improperly
treated water.
PUMPOUT SAFETY CONTROL SETTINGS (Fig. 47) —
The pumpout system high-pressure switch should open at
161 psig (1110 kPa) and close at 130 psig (896 kPa). Check
the switch setting by operating the pumpout compressor and
slowly throttling the pumpout condenser water.
Inspect the Starting Equipment — Before work-
ing on any starter, shut off the chiller, and open all discon-
nects supplying power to the starter.
The disconnect on the starter front panel does not de-
energize all internal circuits. Open all internal and re-
mote disconnects before servicing the starter.
Never open isolating knife switches while equipment is
operating. Electrical arcing can cause serious injury.
Inspect the starter contact surfaces for wear or pitting on
mechanical-type starters. Do not sandpaper or file silver-
plated contacts. Follow the starter manufacturer’s instruc-
tions for contact replacement, lubrication, spare parts
ordering, and other maintenance requirements.
Periodically vacuum or blow off accumulated debris on
the internal parts with a high-velocity, low-pressure blower.
Power connections on newly installed starters may relax
and loosen after a month of operation. Turn power off and
retighten. Recheck annually thereafter.
Fig. 47 — Controls for Optional Pumpout
Compressor
Loose power connections can cause voltage spikes, over-
heating, malfunctioning, or failures.
Ordering Replacement Chiller Parts — When or-
dering Carrier specified parts, the following information must
accompany an order:
• chiller model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment
Check Pressure Transducers — Prior to start-up
and once a year, the pressure transducers should be checked
against a pressure gage reading. Check all three transducers:
oil pressure, condenser pressure, and cooler pressure.
Note the evaporator and condenser pressure readings on
the STATUS01 screen on the LID. Attach an accurate set of
refrigeration gages to the cooler and condenser Schrader fit-
tings. Compare the two readings. If there is a difference in
readings, the transducer can be calibrated, as described in
the Troubleshooting Guide section.
MOTOR REPLACEMENT PARTS — Replacement or re-
newal parts information for the motor and any auxiliary de-
vices can be obtained from the nearest Westinghouse Motor
Company sales office. A complete description of the needed
part(s) is necessary, together with the complete motor name-
plate reading for positive motor identification.
Pumpout System Maintenance — For compres-
sor maintenance details, refer to the 06D, 07D Installation,
Start-Up, and Service Instructions.
EXTERNAL GEAR REPLACEMENT PARTS — Replace-
ment or renewal parts information for the external gear and
any auxiliary devices can be obtained from the nearest Nut-
tall or Lufkin sales office. Acomplete description of the needed
part(s) is necessary, together with the complete gear name-
plate reading for positive identification.
OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE —
Use oil conforming to Carrier specifications for reciprocat-
ing compressor usage. See Table 11.
Oil should be visible in the compressor sight glass both
during operation and at shutdown. Always check the oil
level before operating the compressor. Before adding or chang-
ing oil, relieve the refrigerant pressure as follows:
1. Attach a pressure gage to the gage port of either com-
pressor service valve (Fig. 34).
2. Close the suction service valve and open the discharge
line to the storage tank or the chiller.
TROUBLESHOOTING GUIDE
Overview — The PIC has many features to help the op-
erator and the technician troubleshoot a 17EX chiller.
• By using the LID display, the actual operating conditions
of the chiller can be viewed while the unit is running.
• The CONTROL ALGORITHM STATUS table includes
screens with information that can be used to diagnose prob-
lems with chilled water temperature control, chilled water
3. Operate the compressor until the crankcase pressure drops
to 2 psig (13 kPa).
83
Download from Www.Somanuals.com. All Manuals Search And Download.
temperature control overrides, hot gas bypass, surge al-
gorithm status, and time schedule operation. Refer to
Fig. 14 and Table 2, Examples 11-14.
See Fig. 6 for sensor locations. The sensors are immersed
directly in the refrigerant or water circuits. The wiring at each
sensor is easily disconnected by unlatching the connector.
These connectors allow only one-way connection to the sen-
sor. When installing a new sensor, apply a pipe sealant or
thread sealant to the sensor threads.
DUAL TEMPERATURE SENSORS — There are 2 sensing
elements on each of the bearing temperature sensors for ser-
vicing convenience. In case one of the dual sensors is dam-
aged, the other one can be used by moving a wire.
• The control test feature checks for proper operation and
tests the temperature sensors, pressure transducers, the guide
vane actuator, oil pumps, water pumps, tower control, and
other on/off outputs while the compressor is stopped. It
also has the ability to lock off the compressor and turn on
water pumps for pumpout operation. The LID display shows
the required temperatures and pressures during these op-
erations. Refer to Fig. 16 for the CONTROL TEST menu
structure and to the Control Test section, page 85, for more
information on this feature.
• Other SERVICE menu tables can access configured items,
such as chilled water resets, override set points, etc.
• If an operating fault is detected, an alarm message is gen-
erated and displayed on the LID default screen. A more
detailed message, along with a diagnostic message, is also
stored in the ALARM HISTORY table in the PIC.
The number 1 terminal in the sensor terminal box is the
common line. To use the second sensor, move the wire from
the number 2 position to the number 3 position.
Checking Pressure Transducers — The 17EX chiller
has 5 transducers. These transducers sense cooler pressure,
condenser pressure, compressor oil supply pressure, oil sump,
and gear oil supply pressure. The compressor oil supply pres-
sure and the oil transmission sump pressure difference is cal-
culated by a differential pressure power supply module. The
PSIO then reads this differential. In effect, then, the
PSIO reads 3 pressure inputs. The cooler and condenser
transducers are used by the PIC to determine refrigerant
temperatures.
All pressure inputs can be calibrated, if necessary. It is not
usually necessary to calibrate at initial start-up. However, at
high altitude locations, calibration of the transducer will be
necessary to ensure the proper refrigerant temperature/
pressure relationship. Each transducer is supplied with 5 vdc
power from a power supply. If the power supply fails, a trans-
ducer voltage reference alarm occurs. If the transducer read-
ing is suspected of being faulty, check the supply voltage. It
should be 5 vdc ± .5 v. If the supply voltage is correct, the
transducer should be re-calibrated or replaced.
Checking the Display Messages — The first area
to check when troubleshooting the 17EX is the LID display.
If the alarm light is flashing, check the primary and second-
ary message lines on the LID default screen (Fig. 11). These
messages indicate where the fault is occurring. The ALARM
HISTORY table on the SERVICE menu also carries an alarm
message to further expand on this alarm. For a complete list
of alarm messages, see Table 12. If the alarm light starts to
flash while accessing a menu screen, depress the EXIT soft-
key to return to the default LID screen to read the failure
message. The compressor does not run while an alarm con-
dition exists unless the alarm type is an unauthorized start or
a failure to shut down.
To calibrate oil pressure differential, refer to Oil Pressure
Differential Calibration at the end of this section.
Checking Temperature Sensors — All tempera-
ture sensors are thermistors. This means that the resistance
of the sensor varies with temperature. All sensors have the
same resistance characteristics. Determine sensor tempera-
ture by measuring voltage drop if the controls are powered,
or resistance if the controls are powered off. Compare the
readings to the values listed in Table 14A or 14B.
Calibration can be checked by comparing the pressure read-
ings from the transducer against an accurate refrigeration gage.
These readings are all viewed or calibrated from the
STATUS01 screen on the LID. The transducer can be checked
and calibrated at 2 pressure points. These calibration points
are 0 psig (0 kPa) and between 240 and 260 psig (1655 to
1793 kPa). To calibrate these transducers:
1. Shut down the compressor.
2. Disconnect the transducer in question from its Schrader
fitting.
RESISTANCE CHECK — Turn off the control power and
disconnect the terminal plug of the sensor in question from
the module. With a digital ohmmeter, measure the sensor re-
sistance between the receptacles designated by the wiring
diagram. The resistance and corresponding temperature are
listed in Table 14A or 14B. Check the resistance of both wires
to ground. This resistance should be infinite.
NOTE: If the cooler or condenser vessels are at 0 psig
(0 kPa) or are open to atmospheric pressure, the trans-
ducers can be calibrated for zero without removing the
transducer from the vessel.
VOLTAGE DROP — Using a digital voltmeter, the voltage
drop across any energized sensor can be measured while the
control is energized. Table 14A or 14B lists the relationship
between temperature and sensor voltage drop (volts dc mea-
sured across the energized sensor). Exercise care when mea-
suring voltage to prevent damage to the sensor leads, con-
nector plugs, and modules. The sensor wire should also be
checked at the sensor plug connection. Check the sensor wire
by removing the condenser at the sensor and measure for
5 vdc back to the module, if the control is powered.
3. Access the STATUS01 screen, and view the particular trans-
ducer reading; it should read 0 psi (0 kPa). If the reading
is not 0 psi (0 kPa), but within ± 5 psi (35 kPa), the
value may be zeroed by pressing the SELECT softkey
while the parameter for the transducer is highlighted.
Then, press the ENTER softkey. The value will now go
to zero.
If the transducer value is not within the calibration range,
the transducer returns to the original reading. If the LID
pressure value is within the allowed range (noted above),
check the voltage ratio of the transducer. To obtain the
voltage ratio, divide the voltage (dc) input from the trans-
ducer by the supply voltage signal, measured at the PSIO
terminals J7-J34 and J7-J35. For example, the condenser
transducer voltage input is measured at PSIO terminals
J7-1 and J7-2. The voltage ratio must be between
0.80 vdc and 0.11 vdc for the software to allow calibra-
tion. Pressurize the transducer until the ratio is within range.
Then attempt calibration again.
Relieve all refrigerant pressure or drain the water prior
to replacing the temperature sensors.
CHECK SENSOR ACCURACY — Place the sensor in a
medium of a known temperature and compare that tempera-
ture to the measured reading. The thermometer used to de-
termine the temperature of the medium should be of labo-
ratory quality with 0.5° F (.25° C) graduations. The sensor
in question should be accurate to within 2° F (1.2° C).
84
Download from Www.Somanuals.com. All Manuals Search And Download.
4. A high pressure point can also be calibrated between 240
and 260 psig (1655 and 1793 kPa) by attaching a regu-
lated 250 psig (1724 kPa) pressure (usually from a ni-
trogen cylinder). The high pressure point can be calibrated
by accessing the appropriate transducer on the
TROUBLESHOOTING TRANSDUCERS — When trouble-
shooting transducers, keep the negative lead of your volt-
ohmmeter on terminal U4 of the power supply (or terminal
4 on power supplies without the comparator circuit).
Voltage VO1 = (VH1-VL1) + .467 ± .1 V
For all PIC transducers:
STATUS01 screen, highlighting the transducer, pressing
the SELECT softkey, and then increasing or decreasing
the value to the exact pressure on the refrigerant gage.
Press ENTER to finish. High altitude locations must com-
pensate the pressure so that the temperature/pressure re-
lationship is correct.
Measured pressure = (507.97 × (V /V )) − 47.33
out in
V
V
= transducer output ref. to neg. terminal
(4 or U4) i.e., VH1 to U4 or VL1 to U4
= power supply output, i.e., U3 to U4
out
in
If the transducer reading returns to the previous value and
the pressure is within the allowed range, check the volt-
age ratio of the transducer. Refer to Step 3 above. The
voltage ratio for this high pressure calibration must be
between 0.585 and 0.634 vdc to allow calibration. Change
the pressure at the transducer until the ratio is within the
acceptable range. Then attempt to calibrate to the new
pressure input.
TRANSDUCER REPLACEMENT — Since the transduc-
ers are mounted on Schrader-type fittings, there is no need
to remove refrigerant from the vessel. Disconnect the trans-
ducer wiring by pulling up on the locking tab while pulling
up on the weather-tight connecting plug from the end of the
transducer. Do not pull on the transducer wires. Unscrew
the transducer from the Schrader fitting. When installing a
new transducer, do not use pipe sealer, which can plug the
sensor. Put the plug connector back on the sensor and snap
into place. Check for refrigerant leaks.
The PIC will not allow calibration if the transducer is too
far out of calibration. A new transducer must be installed
and re-calibrated.
OIL DIFFERENTIAL PRESSURE/POWER SUPPLY MOD-
ULE CALIBRATION — (See Fig. 48.) The oil reservoir in
the 17EX chiller is not common to cooler pressure. There-
fore, a comparison of pump output to cooler pressure can
not be used to provide differential oil pressure information.
A different method has been developed.
Oil transmission sump pressure and oil supply pressure
are fed to a comparator circuit on a 5V power supply board.
The output of this circuit, which represents differential oil
pressure, is fed to the PSIO. The oil differential pressure is
calibrated to 0 psid (0 kPad) by selecting the oil pressure
input on the STATUS01 screen. Then, with the oil pump turned
Make sure to use a backup wrench on the Schrader fit-
ting whenever removing a transducer.
Control Algorithms Checkout Procedure — One
of the tables in the SERVICE menu is the CONTROL AL-
GORITHM STATUS table. This table has 6 screens that may
be viewed to see how a particular control algorithm is
operating, that is, to see what parameters and values the PIC
is using to control the chiller.
OFF and the transducers connected, press the ENTER soft-
MAINT01
MAINT02
MAINT03
Capacity
Control
The values used to calculate the chilled
water/brine control point.
key to zero the point. No high end calibration is needed or
possible.
Override
Status
Details of all chilled water control over-
ride values
17EX OIL PRESSURE INPUT
Surge/
HGBP
Status
The surge and hot gas bypass control
algorithm status as well as the values
dealing with this control.
MAINT04
LEAD/LAG LEAD/LAG operation status.
Status
OCCDEFM
Time
The Local and CCN occupied sched-
Schedules ules, displayed in a way that allows the
Status
operator to quickly determine whether
the schedule is in an occupied period
or not.
WSMDEFME Water
System
The status of the WSM (water system
manager), a CCN module that can turn
on the chiller and change the chilled
water control point.
Manager
Status
These maintenance tables are very useful in determining
guide vane position, reaction from load changes, control point
overrides, hot gas bypass reaction, surge prevention, etc.
Control Test — The control test feature can check all
the thermistor temperature sensors, including those on the
Options modules, pressure transducers, pumps and their as-
sociated flow switches, the guide vane actuator, and other
control outputs, such as hot gas bypass. The tests can help
to determine whether a switch is defective, or a pump relay
is not operating, among other useful troubleshooting tests.
During pumpdown operations, the pumps are energized
to prevent freeze-up, and the vessel pressures and tempera-
tures are displayed. The pumpdown/lockout feature pre-
vents the compressor from starting up when there is no re-
frigerant in the chiller or when the vessels are isolated. The
operator then uses the terminate lockout screen to end the
pumpdown lockout after the pumpdown procedure is re-
versed and refrigerant is added.
Fig. 48 — Oil Differential Pressure/Power
Supply Module
85
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND FOR TABLE 12, A - N
1CR AUX
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Compressor Start Contact
Compressor Current
Carrier Comfort Network
Condenser Water Flow
Chiller Start/Stop
OILPD
OILT
PIC
PRS TRIP
PSIO
RLA
RUN AUX
SMM
SPR PL
STR FLT
TXV
—
—
—
—
—
—
—
—
—
—
—
—
—
Oil Pressure
CA
P
Oil Sump Temperature
Product Integrated Control
Pressure Trip Contact
Processor Sensor Input/Output Module
Rated Load Amps
Compressor Run Contact
Starter Management Module
Spare Protective Limit Input
Starter Fault
CCN
CDFL
CHIL
CHW
CMPD
CRP
S
S
Chilled Water
Discharge Temperature
Condenser Pressure
Evaporator Refrigerant Temperature
Chilled Water Flow
Target Guide Vane Position
Light-Emitting Diode
Local Interface Device
Bearing Temperature
Motor Winding Temperature
ERT
EVFL
GV TRG
LED
LID
Thermostatic Expansion Valve
Line Voltage: Percent
Voltage Reference
V
V
P
REF
MTRB
MTRW
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. SHUTDOWN WITH ON/OFF/RESET-OFF
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
PIC in OFF mode, press the CCN or local softkey to
start unit.
MANUALLY STOPPED — PRESS
CCN OR LOCAL TO START
Enter the CONTROL TEST table and select TERMINATE LOCKOUT
to unlock compressor.
TERMINATE PUMPDOWN MODE
SHUTDOWN IN PROGRESS
SHUTDOWN IN PROGRESS
ICE BUILD
TO SELECT CCN OR LOCAL
COMPRESSOR UNLOADING
COMPRESSOR DEENERGIZED
OPERATION COMPLETE
Chiller unloading before shutdown due to soft/stop feature.
Chiller compressor is being commanded to stop. Water pumps are deen-
ergized within one minute.
Chiller shutdown from Ice Build operation.
B. TIMING OUT OR TIMED OUT
PRIMARY MESSAGE
SECONDARY MESSAGE
UNOCCUPIED MODE
PROBABLE CAUSE/REMEDY
Time schedule for PIC is unoccupied.
Chillers will start only when occupied.
READY TO START IN XX MIN
READY TO START IN XX MIN
READY TO START IN XX MIN
READY TO START IN XX MIN
REMOTE CONTACTS OPEN
STOP COMMAND IN EFFECT
RECYCLE RESTART PENDING
Remote contacts have stopped chiller. Close contacts to start.
Chiller START/STOP on STATUS01 manually forced to stop. Re-
lease value to start.
Chiller in recycle mode.
Time schedule for PIC is unoccupied. Chiller will start when occu-
pied. Make sure the time and date have been set on the
SERVICE menu.
READY TO START
UNOCCUPIED MODE
READY TO START
READY TO START
REMOTE CONTACTS OPEN
STOP COMMAND IN EFFECT
Remote contacts have stopped chiller. Close contacts to start.
Chiller START/STOP on STATUS01 manually forced to stop. Re-
lease value to start.
READY TO START IN XX MIN
READY TO START IN XX MIN
READY TO START
REMOTE CONTACTS CLOSED
OCCUPIED MODE
Chiller timer counting down unit. Ready for start.
Chiller timer counting down unit. Ready for start.
Chiller timers complete, unit start will commence.
Chiller timers complete, unit start will commence.
CCN loadshed module commanding chiller to stop.
REMOTE CONTACTS CLOSED
OCCUPIED MODE
READY TO START
STARTUP INHIBITED
LOADSHED IN EFFECT
Chiller START/STOP on STATUS01 has been manually forced to
start. Chiller will start regardless of time schedule or remote contact
status.
READY TO START IN XX MIN
START COMMAND IN EFFECT
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
Unit in recycle mode, chilled water temperature is not high enough
to start.
RECYCLE RESTART PENDING
OCCUPIED MODE
Unit in recycle mode, chilled water temperature is not high enough
to start.
RECYCLE RESTART PENDING
RECYCLE RESTART PENDING
RECYCLE RESTART PENDING
REMOTE CONTACT CLOSED
START COMMAND IN EFFECT
ICE BUILD MODE
Chiller START/STOP on STATUS01 manually forced to start, chilled
water temperature is not high enough to start.
Chiller in ICE BUILD mode. Chilled water/brine temperature is satis-
fied for ICE BUILD SETPOINT temperature.
86
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
PRIMARY MESSAGE
PRESTART ALERT
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
STARTS LIMIT EXCEEDED
STARTS EXCESSIVE Compressor Starts (8 in
12 hours)
Depress the RESET softkey if additional start is
required. Reassess start-up requirements.
PRESTART ALERT
PRESTART ALERT
HIGH MOTOR TEMPERATURE
HIGH BEARING TEMPERATURE
MTRW [VALUE] exceeded limit of [LIMIT]*.
Check motor temperature.
Check motor cooling line for proper operation.
Check for excessive starts within a short time
span.
MTRB [VALUE] exceeded limit of [LIMIT]*.
Check thrust bearing temperature.
Check oil heater for proper operation, check for
low oil level, partially closed oil supply valves,
etc. Check sensor accuracy.
PRESTART ALERT
PRESTART ALERT
PRESTART ALERT
PRESTART ALERT
HIGH DISCHARGE TEMP
LOW REFRIGERANT TEMP
LOW OIL TEMPERATURE
LOW LINE VOLTAGE
CMPD [VALUE] exceeded limit of [LIMIT]*.
Check discharge temperature.
Check sensor accuracy. Allow discharge tem-
perature to cool. Check for excessive starts.
ERT [VALUE] exceeded limit of [LIMIT]*. Check
refrigerant temperature.
Check transducer accuracy. Check for low chilled
water/brine supply temperature.
OILT [VALUE] exceeded limit of [LIMIT]*.
Check oil temperature.
Check oil heater power, oil heater relay. Check
oil level.
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply. Check voltage transform-
ers. Consult power utility if voltage is low. Cali-
brate voltage reading on STATUS01 Table.
Check voltage supply.
PRESTART ALERT
HIGH LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply. Check voltage transform-
ers. Consult power utility if voltage is low. Cali-
brate voltage reading on STATUS01 table.
Check voltage supply.
PRESTART ALERT
PRESTART ALERT
HIGH CONDENSER PRESSURE
HIGH GEAR OIL TEMP
CRP [VALUE] exceeded limit of [LIMIT]*. Check
condenser water and transducer.
Check for high condenser water temperature.
Check transducer accuracy.
GEAOILT [VALUE] exceeded limit of [LIMIT].*
Check gear oil cooler flow.
Check for cooler water flow. Check sensor for
accuracy.
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
E. NORMAL OR AUTO.-RESTART
PRIMARY MESSAGE
STARTUP IN PROGRESS
STARTUP IN PROGRESS
SECONDARY MESSAGE
OCCUPIED MODE
PROBABLE CAUSE/REMEDY
Chiller starting. Time schedule is occupied.
Chiller starting. Remote contacts are closed.
REMOTE CONTACT CLOSED
Chiller starting. Chiller START/STOP on STATUS01 manually forced
to start.
STARTUP IN PROGRESS
START COMMAND IN EFFECT
AUTORESTART IN PROGRESS
AUTORESTART IN PROGRESS
OCCUPIED MODE
Chiller starting. Time schedule is occupied.
Chiller starting. Remote contacts are closed.
REMOTE CONTACT CLOSED
Chiller starting. Chiller START/STOP on STATUS01 manually forced
to start.
AUTORESTART IN PROGRESS
START COMMAND IN EFFECT
F. SPARE SENSOR ALERT MESSAGES
PRIMARY MESSAGE
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SECONDARY MESSAGE
COMMON CHWS SENSOR
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
Sensor Fault: Check common CHWS sensor.
COMMON CHWR SENSOR
REMOTE RESET SENSOR
TEMP SENSOR — SPARE 1
TEMP SENSOR — SPARE 2
TEMP SENSOR — SPARE 3
TEMP SENSOR — SPARE 4
TEMP SENSOR — SPARE 5
TEMP SENSOR — SPARE 6
TEMP SENSOR — SPARE 7
TEMP SENSOR — SPARE 8
TEMP SENSOR — SPARE 9
Sensor Fault: Check common CHWR
sensor.
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
SPARE SENSOR ALERT
Sensor Fault: Check remote reset tempera-
ture sensor.
Sensor Fault: Check temperature sensor —
Spare 1.
Sensor Fault: Check temperature sensor —
Spare 2.
Sensor Fault: Check temperature sensor —
Spare 3.
Check alert temperature set points on EQUIP-
MENT SERVICE table, SERVICE2 screen.
Check sensor for accuracy if reading is not
accurate.
Sensor Fault: Check temperature sensor —
Spare 4.
Sensor Fault: Check temperature sensor —
Spare 5.
Sensor Fault: Check temperature sensor —
Spare 6.
Sensor Fault: Check temperature sensor —
Spare 7.
Sensor Fault: Check temperature sensor —
Spare 8.
Sensor Fault: Check temperature sensor —
Spare 9.
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
G. START-UP FAILURES: This is an alarm condition. A manual reset is required to clear.
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
FAILURE TO START LOW OIL PRESSURE
OILPD [VALUE] exceeded limit of [LIMIT]*. Check Check for closed oil supply valves. Check oil filter.
oil pump system.
Check for low oil temperature. Check transducer
accuracy.
FAILURE TO START OIL PRESS SENSOR FAULT
OILPD [VALUE] exceeded limit of [LIMIT]*. Check Check for excessive refrigerant in oil sump. Run oil
oil pressure sensor.
pump manually for 5 minutes. Check calibration of
oil pressure differential amplifier modules. Check wir-
ing. Replace transducers if necessary.
FAILURE TO START LOW CHILLED WATER FLOW
EVFL Evap Flow Fault: Check water pump/flow Check wiring to flow switch. Check through CON-
switch. TROL TEST for proper switch operation.
FAILURE TO START LOW CONDENSER
CDFL Cond. Flow Fault: Check water pump/flow Check wiring to flow switch. Check through CON-
switch. TROL TEST for proper switch operation.
WATER FLOW
FAILURE TO START STARTER FAULT
STR FLT Starter Fault: Check Starter for Fault A starter protective device has faulted. Check starter
Source. for ground fault, voltage trip, temperature trip, etc.
FAILURE TO START STARTER OVERLOAD TRIP
FAILURE TO START LINE VOLTAGE DROPOUT
STR FLT Starter Overload Trip: Check amps Reset overloads, check ICR relay before restarting
calibration/reset overload. chiller.
V
P Single-Cycle Dropout Detected: Check volt- Check voltage supply. Check transformers for sup-
age supply.
ply. Check with utility if voltage supply is erratic. Moni-
tor must be installed to confirm consistent, single-
cycle dropouts. Check low oil pressure switch.
FAILURE TO START HIGH CONDENSER
High Condenser Pressure [LIMIT]:* Check switch Check for proper design condenser flow and tem-
PRESSURE
2C aux, and water temperature/flow.
perature. Check condenser approach. Check 2C aux-
iliary contacts on oil sump starter. Check high pres-
sure switch.
FAILURE TO START EXCESS ACCELERATION
CA P Excess Acceleration: Check guide vane clo- Check that guide vanes are closed at start-up. Check
TIME
sure at start-up.
starter for proper operation. Reduce unit pressure
if possible.
FAILURE TO START STARTER TRANSITION
RUN AUX Starter Transition Fault: Check 1CR/ Check starter for proper operation.
1M/Interlock mechanism. Run contact failed to close.
FAULT
FAILURE TO START 1CR AUX CONTACT FAULT
1CR AUX Starter Contact Fault: Check 1CR/1M Check starter for proper operation.
aux. contacts. Start contact failed to close.
FAILURE TO START MOTOR AMPS NOT SENSED
CA P Motor Amps Not Sensed: Check motor load Check for proper motor amps signal to SMM. Check
signal.
wiring from SMM to current transformer. Check main
motor circuit breaker for trip.
FAILURE TO START CHECK REFRIGERANT TYPE
FAILURE TO START LOW OIL PRESSURE
Current Refrigerant Properties Abnormal — Check Pressures at transducers indicate another refriger-
Selection of refrigerant type.
ant type in control test. Make sure to access the AT-
TACH TO NETWORK DEVICE screen after speci-
fying HFC-134a refrigerant type.
Low Oil Pressure [LIMIT]:* Check oil pressure switch/ The oil pressure differential switch is open when the
pump and 2C aux.
compressor tried to start. Check the switch for proper
operation. Also, check the oil pump interlock (2C aux)
in the power panel and the high condenser pres-
sure switch.
FAILURE TO START LOW GEAR OIL PRESSURE
GEAROILP [VALUE] exceeded limit of [LIMIT].*
Check gear oil pump/filter.
Check for closed oil supply valves. Check oil filter.
Check transducer accuracy.
FAILURE TO START GEAR OIL PRESSURE SENSOR Gear Oil Pressure Transducer Out of Range [VALUE]. Check calibration of transducer. Replace if
necessary.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
H. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
UNAUTHORIZED
OPERATION
UNIT SHOULD BE
STOPPED
CA P Emergency: Compressor
running without control authorization.
Compressor is running with more than 10% RLA
and control is trying to shut it down. Turn power
off to compressor if unable to stop. Determine cause
before re-powering.
POTENTIAL FREEZE-UP
FAILURE TO STOP
EVAP PRESS/TEMP
TOO LOW
ERT Emergency: Freeze-up
prevention.
Determine cause. If pumping refrigerant out of
chiller, stop operation and go over pumpout
procedures.
DISCONNECT POWER
WITH STARTER
RUN AUX Emergency: DISCONNECT
POWER.
Starter run and start contacts are energized while
control tried to shut down. Disconnect power to
starter.
LOSS OF
COMMUNICATION
Loss of Communication with Starter: Check
chiller.
Check wiring from PSIO to SMM. Check SMM mod-
ule troubleshooting procedures.
STARTER CONTACT
FAULT
ABNORMAL 1CR OR
RUN AUX
1CR AUX Starter Contact Fault: Check
1CR/1M aux. contacts.
Starter run and start contacts energized while chiller
was off. Disconnect power.
POTENTIAL FREEZE UP
COND PRESS/TEMP
TOO LOW
CRT [VALUE] exceeded limit of [LIMIT]*
Emergency: Freeze-up prevention.
The condenser pressure transducer is reading a
pressure that could freeze the water in the con-
denser tubes. Check for condenser refrigerant leaks,
bad transducers, or transferred refrigerant. Place
the unit in PUMPDOWN mode to eliminate the
alarm if vessel is evacuated.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
88
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
I. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE
SECONDARY MESSAGE
4-20MA SIGNAL
PROBABLE CAUSE/REMEDY
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
REMOTE SENSOR CONTROL
CHW TEMP DIFFERENCE
LEAVING CHILLED WATER
ENTERING CHILLED WATER
TEMPERATURE RAMP LOADING
BY DEMAND RAMP LOADING
BY LOCAL DEMAND SETPOINT
BY 4-20MA SIGNAL
Reset program active based on CONFIG screen setup.
Default method of temperature control.
ECW control activated on CONFIG screen.
Ramp loading in effect. Use SERVICE1 screen to modify.
Ramp loading in effect. Use SERVICE1 screen to modify.
Demand limit set point is Ͻ actual demand.
BY CCN SIGNAL
Demand limit is active based on CONFIG screen setup.
BY LOADSHED/REDLINE
Hot gas bypass option is energized. See surge prevention in the
control section.
RUNNING — TEMP CONTROL
HOT GAS BYPASS
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
BY LOCAL SIGNAL
ICE BUILD MODE
Active demand limit manually overridden on STATUS01 table.
Chiller is running under Ice Build temperature control.
J. NORMAL RUN OVERRIDES ACTIVE (ALERTS)
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
RUN CAPACITY LIMITED
HIGH CONDENSER PRESSURE
CRP [VALUE] exceeded limit of [LIMIT]*.
Condenser pressure override.
RUN CAPACITY LIMITED
RUN CAPACITY LIMITED
RUN CAPACITY LIMITED
RUN CAPACITY LIMITED
HIGH MOTOR TEMPERATURE
LOW EVAP REFRIG TEMP
HIGH COMPRESSOR LIFT
MANUAL GUIDE VANE TARGET
MTRW [VALUE] exceeded limit of [LIMIT]*.
Motor temperature override.
See Capacity Overrides, Table 4.
Correct operating condition, modify set-
point, or release override.
ERT [VALUE] exceeded limit of [LIMIT]*. Check
refrigerant charge level.
Surge Prevention Override; lift too high for
compressor.
GV TRG Run Capacity Limited: Manual guide
vane target.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual temperature, pressure, voltage, etc., at which the control tripped.
K. OUT-OF-RANGE SENSOR FAILURES
PRIMARY MESSAGE
SENSOR FAULT
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
LEAVING CHW TEMPERATURE
Sensor Fault: Check leaving CHW
sensor.
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
SENSOR FAULT
ENTERING CHW TEMPERATURE
CONDENSER PRESSURE
EVAPORATOR PRESSURE
BEARING TEMPERATURE
MOTOR WINDING TEMP
Sensor Fault: Check entering CHW
sensor.
Sensor Fault: Check condenser pressure
transducer.
Sensor Fault: Check evaporator pressure
transducer.
See sensor test procedure and check
sensors for proper operation and
wiring.
Sensor Fault: Check bearing temperature
sensor.
Sensor Fault: Check motor temperature
sensor.
DISCHARGE TEMPERATURE
OIL SUMP TEMPERATURE
OIL PRESSURE TRANSDUCER
Sensor Fault: Check discharge temperature
sensor.
Sensor Fault: Check oil sump temperature
sensor.
Sensor Fault: Check oil pressure
transducer.
89
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
L. CHILLER PROTECT LIMIT FAULTS
Excessive numbers of the same fault can lead to severe chiller
damage. Seek service expertise.
PRIMARY MESSAGE
PROTECTIVE LIMIT
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
HIGH DISCHARGE TEMP
CMPD [VALUE] exceeded limit of [LIMIT]*. Check discharge temperature immediately. Check sen-
Check discharge temperature.
sor for accuracy; check for proper condenser flow and
temperature; check oil reservoir temperature. Check
condenser for fouled tubes or air in chiller. Check for
proper guide vane actuator operation.
PROTECTIVE LIMIT
PROTECTIVE LIMIT
LOW REFRIGERANT TEMP
ERT [VALUE] exceeded limit of [LIMIT]*. Check for proper amount of refrigerant charge; check
Check evap pump and flow switch.
for proper water flow and temperatures. Check for
proper guide vane actuator operation.
HIGH MOTOR TEMPERATURE
MTRW [VALUE] exceeded limit of [LIMIT]*. Check motor temperature immediately. Check sen-
Check motor cooling and solenoid.
sor for accuracy. Check for proper condenser flow and
temperature. Check motor cooling system for restric-
tions. Check motor cooling solenoid for proper opera-
tion. Check refrigerant filter.
PROTECTIVE LIMIT
PROTECTIVE LIMIT
HIGH BEARING TEMPERATURE
LOW OIL PRESSURE
MTRB [VALUE] exceeded limit of [LIMIT]*. Check for throttled oil supply isolation valves. Valves
Check oil cooling control.
should be wide open. Check oil cooler thermal ex-
pansion valve. Check sensor accuracy. Check jour-
nal and thrust bearings. Check refrigerant filter. Check
for excessive oil sump level.
OILPD [VALUE] exceeded limit of [LIMIT]*. Check power to oil pump and oil level. Check for dirty
Check oil pump and transducer.
filters or oil foaming at start-up. Check for thermal over-
load cutout. Reduce ramp load rate if foaming noted.
NOTE: This alarm is not related to pressure switch
problems.
Low Oil Pressure [OPEN]*. Check oil
pressure switch/pump and 2C aux.
Check the oil pressure switch for proper operation.
Check oil pump for proper pressure. Check for ex-
cessive refrigerant in oil system.
PROTECTIVE LIMIT
NO MOTOR CURRENT
CA
P
Loss of Motor Current: Check Check wiring: Check torque setting on solid-state starter.
sensor.
Check for main circuit breaker trip. Check power sup-
ply to PSIO module.
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
POWER LOSS
V
P Power Loss: Check voltage
supply.
Check 24-vac input on the SMM (terminals 23 and
LOW LINE VOLTAGE
HIGH LINE VOLTAGE
LOW CHILLED WATER FLOW
V
P [VALUE] exceeded limit of [LIMIT]*. 24). Check transformers to SMM. Check power to PSIO
Check voltage supply.
module. Check distribution bus. Consult power
company.
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
EVFL Flow Fault: Check evap pump/flow
switch.
Perform pumps control test (from CONTROL TEST
table) and verify proper switch operation. Check all
water valves and pump operation.
LOW CONDENSER WATER FLOW CDFL Flow Fault: Check condenser pump/
flow switch.
HIGH CONDENSER PRESSURE
High Cond Pressure [OPEN]*: Check switch, Check the high-pressure switch. Check for proper con-
oil pressure contact, and water temp/flow.
denser pressures and condenser water flow. Check
for fouled tubes. Check the 2C aux. contact and the
oil pressure switch in the power panel. This alarm is
not caused by the transducer.
High Cond Pressure [VALUE]*: Check switch, Check water flow in condenser. Check for fouled tubes.
water flow, and transducer.
Transducer should be checked for accuracy. This alarm
is not caused by the high pressure switch.
PROTECTIVE LIMIT
HIGH CONDENSER PRESSURE
High Cond Pressure [VALUE]*: Check switch, Check water flow in condenser. Check for fouled tubes.
water flow, and transducer.
Transducer should be checked for accuracy. This alarm
is not caused by the high pressure switch.
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
1CR AUX CONTACT FAULT
RUN AUX CONTACT FAULT
CCN OVERRIDE STOP
CR AUX Starter Contact Fault: Check 1CR auxiliary contact opened while chiller was run-
1CR/1M aux contacts. ning. Check starter for proper operation.
RUN AUX Starter Contact Fault: Check Run auxiliary contact opened while chiller was run-
1CR/1M aux contacts. ning. Check starter for proper operation.
CHIL
S
S CCN Override Stop while in CCN has signaled chiller to stop. Reset and restart
LOCAL run mode.
when ready. If the signal was sent by the LID, release
the Stop signal on STATUS01 table.
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
SPARE SAFETY DEVICE
EXCESSIVE MOTOR AMPS
EXCESSIVE COMPR SURGE
STARTER FAULT
SRP PL Spare Safety Fault: Check
contacts.
Spare safety input has tripped or factory-installed jumper
not present.
CA P [VALUE] exceeded limit of [LIMIT]*. Check motor current for proper calibration. Check guide
High Amps; Check guide vane drive. vane drive and actuator for proper operation.
Compressor Surge: Check condenser wa- Check condenser flow and temperatures. Check con-
ter temp and flow. figuration of surge protection.
STR FLT Starter Fault: Check starter for Check starter for possible ground fault, reverse rota-
tion, voltage trip, etc.
fault source.
STARTER OVERLOAD TRIP
STR FLT Starter Overload Trip: Check Reset overloads and reset alarm. Check motor cur-
amps calibration/reset overload.
rent calibration or overload calibration (do not field-
calibrate overloads).
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the
operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at
which the control tripped. [OPEN] indicates that an input circuit is open.
90
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
L. CHILLER PROTECT LIMIT FAULTS (cont)
Excessive numbers of the same fault can lead to severe chiller
damage. Seek service expertise.
PRIMARY MESSAGE
PROTECTIVE LIMIT
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
TRANSDUCER VOLTAGE FAULT
V
REF [VALUE] exceeded limit of [LIMIT]*.
Check transformer power (5 vdc) supply to
transducers. Power must be 4.5 to 5.5 vdc.
Check transducer power supply.
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
LOW GEAR OIL PRESSURE
HIGH GEAR OIL TEMP
CCN OVERRIDE STOP
GEAROILP [VALUE] exceeded imit of
[LIMIT]*. Check gear oil pump filter.
Check for closed oil supply valves. Check oil fil-
ter. Check transducer accuracy.
GEAOILT [VALUE] exceeded limit of
[LIMIT]*. Check gear oil cooler filter.
Check for cooler water flow. Check sensor for
accuracy.
CHIL
S
S CCN. Override stop while in
Machine received a command from the net-
work to stop overriding local operating mode.
local run mode.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by
the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped. [OPEN] indicates that an input circuit is open.
M. CHILLER ALERTS
PRIMARY MESSAGE
RECYCLE ALERT
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
HIGH AMPS AT SHUTDOWN
HighAmps at Recycle: Check guide vane
drive.
Check that guide vanes are closing. Check
motor amps correction calibration is cor-
rect. Check actuator for proper operation.
SENSOR FAULT ALERT
SENSOR FAULT ALERT
LEAVING COND WATER TEMP
ENTERING COND WATER TEMP
CHECK OIL FILTER
Sensor Fault: Check leaving condenser
water sensor.
Check sensor. See sensor test procedure.
Sensor Fault: Check entering condenser
water sensor.
LOW OIL PRESSURE
ALERT
Low Oil Pressure Alert: Check oil
Check oil filter. Check for improper oil level
or temperature.
AUTORESTART PENDING
AUTORESTART PENDING
AUTORESTART PENDING
SENSOR ALERT
POWER LOSS
V
P Power Loss: Check voltage
Check power supply if there are excessive
compressor starts occurring.
supply.
LOW LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
HIGH LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
HIGH DISCHARGE TEMP
CMPD [VALUE] exceeded limit of
[LIMIT]*. Check discharge
temperature.
Discharge temperature exceeded the alert
threshold. Check entering condenser water
temperature.
SENSOR ALERT
HIGH BEARING TEMP
MTRB [VALUE] exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.
Thrust bearing temperature exceeded the
alert threshold. Check for closed valves, im-
proper oil level or temperatures.
CONDENSER PRESSURE
ALERT
PUMP RELAY ENERGIZED
CRP High Condenser Pressure [LIMIT]*.
Pump energized to reduce pressure.
Check ambient conditions. Check con-
denser pressure for accuracy.
RECYCLE ALERT
EXCESSIVE RECYCLE STARTS
Excessive recycle starts.
The chiller load is too small to keep the chiller
on line and there have been more than 5
restarts in 4 hours. Increase chiller load, ad-
just hot gas bypass, increase RECYCLE RE-
START DELTA T from SERVICE1 screen.
SENSOR ALERT
SENSOR ALERT
LOW GEAR OIL PRESSURE
HIGH GEAR OIL TEMP
GEAROILP [VALUE] exceeded imit of
[LIMIT]*. Check gear oil pump filter.
Check for closed oil supply valves. Check
oil filter. Check transducer accuracy.
GEAOILT [VALUE] exceeded limit of
[LIMIT]*. Check gear oil cooler filter.
Check for cooler water flow. Check sensor
for accuracy.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by
the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped.
91
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
N. OTHER PROBLEMS/MALFUNCTIONS
DESCRIPTION/MALFUNCTION
PROBABLE CAUSE/REMEDY
Chilled Water/Brine Temperature
Too High (Chiller Running)
Chilled water set point set too high. Access set point on LID and verify.
Capacity override or excessive cooling load (chiller at design capacity). Check
LID status messages. Check for outside air infiltration into conditioned space.
Condenser temperature too high. Check for proper flow, examine cooling
tower operation, check for air or water leaks, check for fouled tubes.
Refrigerant level low. Check for leaks, add refrigerant, and trim charge.
Liquid bypass in waterbox. Examine division plates and gaskets for leaks.
Guide vanes fail to open. Use control test to check operation.
Chilled water control point too high. Access CONTROL ALGORITHM STA-
TUS table, MAINT01 screen, and check chilled water control operation.
Guide vanes fail to open fully. Be sure that the guide vane target is released.
Check guide vane linkage. Check limit switch in actuator. Check that sensor
is in the proper terminals.
Chilled Water/Brine Temperature Too Low (Chiller
Running)
Chilled water set point set too low. Access set point on LID and verify.
Chilled water control point too low. Access CONTROL ALGORITHM STA-
TUS tables, MAINT01 screen, and check chilled water control for proper
resets.
High discharge temperature keeps guide vanes open.
Guide vanes fail to close. Be sure that guide vane target is released. Check
chilled water sensor accuracy. Check guide vane linkage. Check actuator
operation.
Chilled Water Temperature Fluctuates. Vanes Hunt
Deadband too narrow. Configure LID for a larger deadband (SERVICE1 screen).
Proportional bands too narrow. Either PROPORTIONAL INC BAND or PRO-
PORTIONAL DEC BAND should be increased (MAINT01 screen).
Loose guide vane drive. Adjust chain drive.
Defective vane actuator. Check using control test feature.
Defective temperature sensor. Check sensor accuracy.
Check for proper oil level (not enough oil).
Low Oil Sump Temperature While Running
(Less than 100 F [38 C])
At Power Up, Default Screen Does Not Appear, ‘‘Tables Load-
ing’’ Message Continually Appears
Check for proper communications wiring on PSIO module. Check that the
COMM1 communications wires from the LID are terminated to the COMM1
PSIO connection. Check for ground or short on CCN system wiring.
SMM Communications Failure
Check that PSIO communication plugs are connected correctly. Check SMM
communication plug. Check for proper SMM power supply. See Control Mod-
ules section on page 96.
High Oil Temperature While Running
Check for proper oil level (too much oil). Check water supply to oil cooler.
Blank LID Screen (Minimal Contrast Visible)
Increase contrast potentiometer. See Fig. 49. Check red LED on LID for
proper operation, (power supply). If LED is blinking, but green LED’s are
not, replace LID module, (memory failure). Check light bulb if backlit model.
‘‘Communications Failure’’ Highlighted Message At
Bottom of LID Screen
LID is not properly addressed to the PSIO. Make sure that, on ATTACH TO
NETWORK DEVICE screen,. LOCAL DEVICE is set to read the PSIO ad-
dress. Check LEDs on PSIO. Is red LED operating properly? Are green LEDs
blinking? See Control Module troubleshooting section.
Control Test Disabled
Press the Stop pushbutton. The PIC must be in the OFF mode for the con-
trol test feature to operate. Clear all alarms. Check line voltage percent on
STATUS01 screen. The percent must be within 90% to 110%. Check volt-
age input to SMM; calibrate starter voltage potentiometer for accuracy.
Vanes Will Not Open in Control Test
Oil Pump Does Not Run
Low pressure alarm is active. Put chiller into PUMPDOWN mode or equal-
ize pressure. Check guide vane actuator wiring.
Check oil pump voltage supply. Cooler vessel pressure under vacuum.
Pressurize vessel. Check temperature overload cutout switch.
LID Default Screen Does Not Update
This is normal operation when an alarm is present. The screen freezes the
moment the alarm is activated to aid in troubleshooting. The STATUS01 screen
provides current information.
Chiller Does Not Stop When the STOP Button is Pressed
LID Screen Dark
The STOP button wiring connector on the LID module is not properly con-
nected or the chiller is in soft stop mode and the guide vanes are
closing.
Light bulb burned out. Replace as needed.
92
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13 — External Gear Troubleshooting Guide
PROBLEM
Excessive Operating Temperature
Oil Leakage
POSSIBLE CAUSE — ITEM NO.s*
1,2,3,4,5,6,7,9,12,18,20,21
1,2,3,4,5,7,9,12,13,18,19,21
Gear Wear
Bearing Failure
Unusual Noise
1,2,3,4,6,7,8,9,10,11,12,13,14,15,16,18,19,21,22
1,6,7,8,9,10,11,12,15,16,19,20,21
1,2,3,4,6,7,8,9,10,11,12,13,15,16,17,20,21
*See table below for probable cause and suggested remedy.
POSSIBLE CAUSE
1. Unit Overload
ACTION
Reduce the loading.
2. Incorrect Oil Level
Verify that the oil level is correct. Too little or too much oil can cause high
temperature.
3. Wrong Oil Grade
Use only the AGMA (American Gear Manufacturers Association) grade oil
as specified for the unit size and ambient temperature.
4. Contaminated Oil
5. Clogged Breather
If oil is oxidized, dirty, or has high sludge content, change the oil.
Clean breather regularly.
6. Improper Bearing Clearance
Too large or too small bearing clearance. Refer to drawing or contact the
gear manufacturer for correct clearance, checking technique, and toler-
ance. Shafts should turn freely when disconnected from the load.
7. Improper Coupling Alignment
8. Incorrect Coupling
Disconnect couplings, check spacing between shafts, and check alignment.
Realign as required.
Rigid couplings can cause shaft failure. Replace with a coupling that pro-
vides flexibility and lateral float.
9. Excessive Operating Speed
Reduce the speed.
10. Torsional or Lateral Vibrations
Vibrations can occur through a particular speed range known as the critical
speed. Contact the factory for specific recommendations.
11. Extreme Repetitive Shocks
Apply couplings capable of absorbing shocks.
12. Improper Lubrication of Bearings
13. Improper Storage or Prolonged Shutdown
Verify that all bearings are receiving adequate amounts of lubricating oil.
Destructive rusting of bearings and gears will be caused by storage or pro-
longed shutdown in moist ambient temperatures. If rust is found, unit must
be disassembled, inspected, and repaired.
14. Excessive Backlash
15. Misalignment of Gears
16. Housing Twisted or Distorted
17. Gear Tooth Wear
Contact gear manufacturer.
Contact pattern to be a minimum of 80% of face.
Verify proper shimming or stiffness of the foundation.
Contact gear manufacturer.
18. Open Drains
Tighten drain plugs.
19. Loosely Bolted Covers
20. Motor Related
Check all bolted joints and tighten if necessary.
Verify that actual operating conditions are consistent with motor nameplate.
21. Excessive Ambient Temperature
Shield unit from heat source and maintain proper air flow around the gear
unit.
93
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14A — Thermistor Temperature (F) vs Resistance/Voltage Drop
TEMPERATURE
(F)
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
TEMPERATURE
(F)
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
TEMPERATURE
(F)
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
−25.0
−24.0
−23.0
−22.0
−21.0
−20.0
−19.0
−18.0
−17.0
−16.0
−15.0
−14.0
−13.0
−12.0
−11.0
−10.0
−9.0
−8.0
−7.0
−6.0
−5.0
−4.0
−3.0
−2.0
−1.0
0.0
4.821
4.818
4.814
4.806
4.800
4.793
4.786
4.779
4.772
4.764
4.757
4.749
4.740
4.734
4.724
4.715
4.705
4.696
4.688
4.676
4.666
4.657
4.648
4.636
4.624
4.613
4.602
4.592
4.579
4.567
4.554
4.540
4.527
4.514
4.501
4.487
4.472
4.457
4.442
4.427
4.413
4.397
4.381
4.366
4.348
4.330
4.313
4.295
4.278
4.258
4.241
4.223
4.202
4.184
4.165
4.145
4.125
4.103
4.082
4.059
4.037
4.017
3.994
3.968
3.948
3.927
3.902
3.878
3.854
3.828
3.805
3.781
3.757
3.729
3.705
3.679
3.653
3.627
3.600
3.575
3.547
3.520
3.493
3.464
3.437
3.409
3.382
3.353
3.323
3.295
3.267
3.238
3.210
3.181
3.152
3.123
98010
94707
91522
88449
85486
82627
79871
77212
74648
72175
69790
67490
65272
63133
61070
59081
57162
55311
53526
51804
50143
48541
46996
45505
44066
42679
41339
40047
38800
37596
36435
35313
34231
33185
32176
31202
30260
29351
28473
27624
26804
26011
25245
24505
23789
23096
22427
21779
21153
20547
19960
19393
18843
18311
17796
17297
16814
16346
15892
15453
15027
14614
14214
13826
13449
13084
12730
12387
12053
11730
11416
11112
10816
10529
10250
9979
71
72
3.093
3.064
3.034
3.005
2.977
2.947
2.917
2.884
2.857
2.827
2.797
2.766
2.738
2.708
2.679
2.650
2.622
2.593
2.563
2.533
2.505
2.476
2.447
2.417
2.388
2.360
2.332
2.305
2.277
2.251
2.217
2.189
2.162
2.136
2.107
2.080
2.053
2.028
2.001
1.973
1.946
1.919
1.897
1.870
1.846
1.822
1.792
1.771
1.748
1.724
1.702
1.676
1.653
1.630
1.607
1.585
1.562
1.538
1.517
1.496
1.474
1.453
1.431
1.408
1.389
1.369
1.348
1.327
1.308
1.291
1.289
1.269
1.250
1.230
1.211
1.192
1.173
1.155
1.136
1.118
1.100
1.082
1.064
1.047
1.029
1.012
0.995
0.978
0.962
0.945
0.929
0.914
0.898
0.883
0.868
0.853
5781
5637
5497
5361
5229
5101
4976
4855
4737
4622
4511
4403
4298
4196
4096
4000
3906
3814
3726
3640
3556
3474
3395
3318
3243
3170
3099
3031
2964
2898
2835
2773
2713
2655
2597
2542
2488
2436
2385
2335
2286
2239
2192
2147
2103
2060
2018
1977
1937
1898
1860
1822
1786
1750
1715
1680
1647
1614
1582
1550
1519
1489
1459
1430
1401
1373
1345
1318
1291
1265
1240
1214
1190
1165
1141
1118
1095
1072
1050
1029
1007
986
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
0.838
0.824
0.810
0.797
0.783
0.770
0.758
0.745
0.734
0.722
0.710
0.700
0.689
0.678
0.668
0.659
0.649
0.640
0.632
0.623
0.615
0.607
0.600
0.592
0.585
0.579
0.572
0.566
0.560
0.554
0.548
0.542
0.537
0.531
0.526
0.520
0.515
0.510
0.505
0.499
0.494
0.488
0.483
0.477
0.471
0.465
0.459
0.453
0.446
0.439
0.432
0.425
0.417
0.409
0.401
0.393
0.384
0.375
0.366
719
705
690
677
663
650
638
626
614
602
591
581
570
561
551
542
533
524
516
508
501
494
487
480
473
467
461
456
450
445
439
434
429
424
419
415
410
405
401
396
391
386
382
377
372
367
361
356
350
344
338
332
325
318
311
304
297
289
282
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
1.0
97
2.0
98
3.0
99
4.0
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
36.0
37.0
38.0
39.0
40.0
41.0
42.0
43.0
44.0
45.0
46.0
47.0
48.0
49.0
50.0
51.0
52.0
53.0
54.0
55.0
56.0
57.0
58.0
59.0
60.0
61.0
62.0
63.0
64.0
65.0
66.0
67.0
68.0
69.0
70.0
9717
9461
9213
8973
8739
8511
8291
965
8076
945
7868
925
7665
906
7468
887
7277
868
7091
850
6911
832
6735
815
6564
798
6399
782
6238
765
6081
750
5929
734
94
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14B — Thermistor Temperature (C) vs Resistance/Voltage Drop
TEMPERATURE
(C)
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
TEMPERATURE
(C)
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
−40
−39
−38
−37
−36
−35
−34
−33
−32
−31
−30
−29
−28
−27
−26
−25
−24
−23
−22
−21
−20
−19
−18
−17
−16
−15
−14
−13
−12
−11
−10
−9
4.896
4.889
4.882
4.874
4.866
4.857
4.848
4.838
4.828
4.817
4.806
4.794
4.782
4.769
4.755
4.740
4.725
4.710
4.693
4.676
4.657
4.639
4.619
4.598
4.577
4.554
4.531
4.507
4.482
4.456
4.428
4.400
4.371
4.341
4.310
4.278
4.245
4.211
4.176
4.140
4.103
4.065
4.026
3.986
3.945
3.903
3.860
3.816
3.771
3.726
3.680
3.633
3.585
3.537
3.487
3.438
3.387
3.337
3.285
3.234
3.181
3.129
3.076
3.023
2.970
2.917
2.864
2.810
2.757
2.704
2.651
2.598
2.545
2.493
2.441
2.389
2.337
2.286
2.236
2.186
2.137
2.087
2.039
1.991
1.944
168 230
157 440
147 410
138 090
129 410
121 330
113 810
106 880
100 260
94 165
88 480
83 170
78 125
73 580
69 250
65 205
61 420
57 875
54 555
51 450
48 536
45 807
43 247
40 845
38 592
38 476
34 489
32 621
30 866
29 216
27 633
26 202
24 827
23 532
22 313
21 163
20 079
19 058
18 094
17 184
16 325
15 515
14 749
14 026
13 342
12 696
12 085
11 506
10 959
10 441
9 949
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
1.898
1.852
1.807
1.763
1.719
1.677
1.635
1.594
1.553
1.513
1.474
1.436
1.399
1.363
1.327
1.291
1.258
1.225
1.192
1.160
1.129
1.099
1.069
1.040
1.012
0.984
0.949
0.920
0.892
0.865
0.838
0.813
0.789
0.765
0.743
0.722
0.702
0.683
0.665
0.648
0.632
0.617
0.603
0.590
0.577
0.566
0.555
0.545
0.535
0.525
0.515
0.506
0.496
0.486
0.476
0.466
0.454
0.442
0.429
0.416
0.401
0.386
0.370
2 184
2 101
2 021
1 944
1 871
1 801
1 734
1 670
1 609
1 550
1 493
1 439
1 387
1 337
1 290
1 244
1 200
1 158
1 118
1 079
1 041
1 006
971
938
906
876
836
805
775
747
719
693
−8
669
−7
645
−6
623
−5
602
−4
583
−3
564
−2
547
−1
531
0
516
1
502
2
489
3
477
4
466
5
456
6
446
7
436
8
427
9
419
10
410
11
9 485
402
12
9 044
393
13
8 627
385
14
8 231
376
15
7 855
367
16
7 499
357
17
7 161
346
18
6 840
335
19
6 536
324
20
6 246
312
21
5 971
299
22
5 710
285
23
5 461
24
5 225
25
5 000
26
4 786
27
4 583
28
4 389
29
4 204
30
4 028
31
3 861
32
3 701
33
3 549
34
3 404
35
3 266
36
3 134
37
3 008
38
2 888
39
2 773
40
2 663
41
2 559
42
2 459
43
2 363
44
2 272
95
Download from Www.Somanuals.com. All Manuals Search And Download.
RED LEDs
Control Modules
PSIO Module — If the LED is blinking continuously at a
2-second rate, it is indicating proper operation. If it is lit con-
tinuously it indicates a problem requiring replacement of the
module. Off continuously indicates that the power should be
checked. If the red LED blinks 3 times per second, a soft-
ware error has been discovered and the module must be re-
placed. If there is no input power, check the fuses and the
circuit breaker. If the fuses are good, check for a shorted
secondary of transformer, or if power is present to the mod-
ule, replace the module.
4-In/2-Out Module — If the LED is blinking, this module is
operating properly. A steady red light indicates a module fail-
ure. Replace the 4-In/2-Out module.
GREEN LEDs — There are 1 or 2 green LEDs on each type
of module. These LEDs indicate communication status be-
tween different parts of the controller and the network mod-
ules as follows:
Turn the controller power off before servicing the con-
trols. This ensures safety and prevents damage to the
controller.
The Processor/Sensor Input/Output module (PSIO), 8-input
(Options) modules, Starter Management Module (SMM),
4-in/2-out module, and the Local Interface Device (LID) mod-
ule perform continuous diagnostic evaluations of the hard-
ware to determine its condition. Proper operation of all modules
is indicated by LEDs (light-emitting diodes) located on the
side of the LID (Fig. 49); on the top horizontal surface of the
PSIO (Fig. 50), SMM, and 8-input modules; and on the 4-in/
2-out module.
LID Module
Upper LED — Communication with CCN network, if present;
blinks when communication occurs.
Lower LED — Communication with PSIO module; must blink
every 5 to 8 seconds when the LID default screen is
displayed.
PSIO Module
Green LED Closest to Communications Connection — Com-
munication with SMM and 8-input module; must blink
continuously.
Other Green LED — Communication with LID; must blink
every 3 to 5 seconds.
8-Input Modules and SMM — Communication with PSIO
module; blinks continuously.
4-In/2-Out Module — Communication with PSIO module;
blinks continuously.
Notes on Module Operation
1. The chiller operator monitors and modifies configura-
tions in the microprocessor through the 4 softkeys and
the LID. Communication with the LID and the PSIO is
accomplished through the CCN bus (COMM1). The com-
munication between the PSIO, SMM, both 8-input mod-
ules, and the 4-in/2-out module is accomplished through
the sensor bus (COMM3), which is a 3-wire cable. On
the sensor bus terminal strips, Terminal 1 of the PSIO
module is connected to Terminal 1 of each of the other
modules. Terminals 2 and 3 are connected in the same
manner, except for the connection to the 4-in/2-out mod-
ule. See Fig. 51.
NOTE: Address switches on this module can be at any position. Ad-
dresses are only changed through the LID screen for CCN.
Fig. 49 — LID Module (Rear View) and
LED Locations
2. If a green LED is on continuously, check the communi-
cation wiring. If a green LED is off, check the red LED
operation. If the red LED is normal, check the module
address switches (Fig. 52-54). Proper addresses are set as
shown below:
ADDRESS
MODULE
S1
S2
SMM (Starter Management Module)
8-input Options Module 1
8-input Options Module 2
3
6
7
2
4
2
SWITCH
MODULE
1
2
3
4
5
6
7
8
4-In/2-Out Module
O
O
O
O
C
O
C
O
O
C
—
—
Open
Closed
Fig. 50 — PSIO Module LED Locations
96
Download from Www.Somanuals.com. All Manuals Search And Download.
If all modules indicate a communications failure, check
the communications plug on the PSIO module for proper
seating. Also check the wiring (CCN bus — 1:red, 2:wht,
3:blk; Sensor bus — 1:red, 2:blk, 3:clr/wht). If a good
connection is assured and the condition persists, replace
the PSIO module.
If only one 8-input module, the SMM, or the 4-in/2-out
module indicates a communication failure, check the com-
munications plug on that module. If a good connection is
assured and the condition persists, replace the module.
All system operating intelligence rests in the PSIO mod-
ule. Some safety shutdown logic resides in the SMM in
case communications are lost between the 2 modules. The
PSIO monitors conditions using input ports on the PSIO,
the SMM, the 8-input modules, and the 4-in/2-out mod-
ules. Outputs are controlled by the PSIO and SMM as
well.
3. Power is supplied to the modules within the control panel.
The transformers are located within the power panel, with
the exception of the SMM, which operates from a 24-vac
power source and has its own 24-vac transformer located
in the starter.
In the power panel, T1 supplies power 21-vac to the LID,
the PSIO, and the 5-vac power supply for the transduc-
ers. T3 supplies 24-vac power to the 4-in/2-out module.
T4 is another 21-vac transformer, which supplies power
to both 8-input modules (if present). T4 is capable of sup-
plying power to two modules; if additional modules are
added, another power supply will be required.
NOTE: Address switches on this module can be at any position. Addresses can
only be changed through the LID or CCN.
Fig. 52 — Processor (PSIO) Module
Power is connected to Terminals 1 and 2 of the power
input connection on each module.
Starter Management Module (SMM) (Fig. 53)
INPUTS — Inputs on strips J2 and J3 are a mix of analog
and discrete (on/off) inputs. The chiller application deter-
mines which terminals are used. Always refer to the indi-
vidual unit wiring diagram for terminal numbers.
PSIO (J8)
SMM (J5)
4-IN/2-OUT (J3)
8-INPUT (J5)
8-INPUT (J5)
+
1
+
1
+
1
+
1
+
1
GRD
GRD
GRD
GRD
2
-
2
3
2
3
2
3
2
3
OUTPUTS — Outputs are 24 vdc and wired to strip J1. There
are 2 terminals used per output.
-
-
-
-
GRD
3
LEGEND
GRD
—
—
—
Ground
PSIO
—
Processor/Sensor Input/
Output Module
J
Junction
SMM
Starter Management
Module
Pins
Fig. 51 — Sensor Input/Output (SIO) Wiring
Schematic for COMM3 Bus
Processor/Sensor Input/Output Module (PSIO)
(Fig. 52)
INPUTS — Each input channel has 3 terminals; only 2 of
the terminals are used. The chiller application determines which
terminals are normally used. Always refer to individual unit
wiring diagrams for terminal numbers.
OUTPUTS — Output is 20 vdc. There are 3 terminals per
output, only 2 of which are used, depending on the appli-
cation. Refer to the unit wiring diagram.
NOTE: SMM address switches should be set as follows: S1 set at 3; S2 set
at 2.
Fig. 53 — Starter Management Module (SMM)
97
Download from Www.Somanuals.com. All Manuals Search And Download.
configurations. The inputs monitor the gear oil temperature
and pressure. InputAI#2 should be factory-set with the jumper
on (T). Inputs AI#3, and AI#4 should be factory set on (V).
Options Modules (8-Input) — The options modules
are optional additions to the PIC, and are used to add tem-
perature reset inputs, spare sensor inputs, and demand limit
inputs. Each option module contains 8 inputs, each input meant
for a specific duty. See the wiring diagram for exact module
wire terminations. Inputs for each of the options modules
available include the following:
OUTPUTS — The two analog outputs are each configurable
by on-board jumpers as 0 to 10 vdc (maximum current:
10 mA) or 4 to 20 mA (maximum load: 600 ohms) outputs.
The outputs control the relay that activates the gear oil pump
starter. Outputs AO#1 and AO#2 should be factory set with
the jumper on (V).
This module has a field-configurable DIP (dual in-line pack-
age) switch to designate its address. It should be factory set
with the following switches open: 1, 2, 3, 4, 6, and 8. Switches
5 and 7 should be closed.
OPTIONS MODULE 1
4 to 20 mA Auto. Demand Reset
4 to 20 mA Auto. Chilled Water Reset
Common Chilled Water Supply Temperature
Common Chilled Water Return Temperature
Remote Temperature Reset Sensor
Spare Temperature 1
Spare Temperature 2
Spare Temperature 3
Note the SIO bus wiring for this module. Unlike the stand-
ard PIC modules, Pin 2 is negative and Pin 3 is the ground
(or common). See Fig. 51.
OPTIONS MODULE 2
4 to 20 mA Spare 1
4 to 20 mA Spare 2
Spare Temperature 4
Spare Temperature 5
Spare Temperature 6
Spare Temperature 7
Spare Temperature 8
Spare Temperature 9
Replacing Defective Processor Modules — The
replacement part number is printed on a small label on the
front of the PSIO module. The model and serial numbers are
printed on the unit nameplate located on an exterior corner
post. The proper software is factory-installed by Carrier in
the replacement module. When ordering a replacement pro-
cessor module (PSIO), specify complete replacement part num-
ber, full unit model number, and serial number. This new
unit requires reconfiguration to the original chiller data by
the installer. Follow the procedures described in the Set Up
Chiller Control Configuration section on page 54. Electrical
shock can cause personal injury. Disconnect all electrical power
before servicing.
Terminal block connections are provided on the options
modules. All sensor inputs are field wired and installed.
Options module 1 can be factory or field-installed. Options
module 2 is shipped separately and must be field installed.
For installation, refer to the unit or field wiring diagrams. Be
sure to address the module for the proper module number
(Fig. 54) and to configure the chiller for each feature being
used.
Electrical shock can cause personal injury. Disconnect
all electrical power before servicing.
INSTALLATION OF NEW PSIO MODULE
1. Verify that the existing PSIO module is defective by us-
ing the procedure described in the Notes on Module Op-
eration section, page 96, and the Control Modules sec-
tion, page 96. Do not access theATTACH TO NETWORK
DEVICE screen if the LID displays a communication
failure.
2. Data regarding the PSIO configuration should have been
recorded and saved. This data must be reconfigured into
the LID. If this data is not available, follow the proce-
dures described in the Set Up Chiller Control Configu-
ration section, page 54. Record the TOTAL COMPRES-
SOR STARTS and the COMPRESSOR ONTIME from the
STATUS01 table on the LID.
If a CCN Building Supervisor or Service Tool is present,
the module configuration should have already been up-
loaded into memory; then, when the new module is in-
stalled, the configuration can be downloaded from the
computer (if the software version is the same).
Any communication wires from other chillers or CCN
modules must be disconnected.
3. Check that all power to the unit is off. Carefully dis-
connect all wires from the defective module by unplug-
ging the 6 connectors. It is not necessary to remove any
of the individual wires from the connectors.
SWITCH SETTING
OPTIONS MODULE 1
OPTIONS MODULE 2
S1
S2
6
4
7
2
4. Remove the defective PSIO by removing its mounting
screw with a long-shaft Phillips screwdriver and remov-
ing the module from the control box. Save the screw for
later use. The green ground wire is held in place with
the module mounting screw.
5. Package the defective module in the carton of the new
module for return to Carrier.
Fig. 54 — Options Module
Four-In/Two-Out Module (Fig. 55)
INPUTS — The four analog inputs each have 3 terminals
and are configurable by movable on-board jumpers as ther-
mistor (T), 4 to 20 mA (C), or 0 to 10 vdc (V)
98
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Restore control system power (the LID displays, COM-
MUNICATION FAILURE at the bottom of the screen).
same as the value from the old module. Press the
ENTER softkey to save this value.
15. Move the highlight bar to the COMPRESSOR
7. Access the SERVICE menu. Highlight and select
the ATTACH TO NETWORK DEVICE screen. Press
ONTIME line. Press the SELECT softkey and the, us-
the ATTACH softkey. (The LID displays, UPLOAD-
ING TABLES. PLEASE WAIT; then, COMMUNICA-
TION FAILURE.) Press the EXIT softkey.
8. Turn off control power.
9. Mount the new module in the unit control box using a
long-shaft Phillips screwdriver and the screw saved in
Step 4 on page 98. Make sure that the green grounding
wire is reinstalled along with the mounting screw.
10. Connect the LID communication wires (CCN bus) and
the power wires. If CCN wiring has been attached to the
CCN bus, disconnect the wires. Attach the sensor bus
plug and the input and output plugs.
11. Carefully check all wiring connections before restoring
power.
12. Restore control power and verify that the red and green
LEDs on the PSIO are functioning properly.
13. The LID should indicate AVAILABLE MEMORY and
a value. This value should start to decrease. (If it does
not, check the LID wiring to the PSIO; ensure connec-
tion to the proper plug.) The bottom of the screen dis-
plays, UPLOADING TABLES, PLEASE WAIT.
14. After the PSIO tables have been uploaded into the LID,
access the STATUS01 screen. Move the highlight bar to
the TOTAL COMPRESSOR STARTS line. Press the
ing the INCREASE or DECREASE softkeys, change
this value until it matches the old module run hours. Press
the SELECT softkey to save this value.
16. Change the address of the PSIO In the CONTROLLER
IDENTIFICATION table back to its previous value. Write
the address on the PSIO.
17. Use the configuration sheets (pages CL-3 to CL-11) to
input set point, configuration, and schedule information
into the PSIO. The TIME AND DATE table from the
SERVICE menu must also be set. A Building Supervi-
sor terminal can be used to download the old configu-
ration into the PSIO.
18. Access the CONTROL TEST table and perform the con-
trol tests to verify all that all tested functions are work-
ing properly.
If the software version has been updated, a CCN down-
load of the configuration will not be allowed. Configure
the PSIO by hand, and upload the PSIO into the net-
work using the ATTACH TO NETWORK DEVICE
screen.
19. Restore the chiller to normal operation; calibrate the mo-
tor amps.
PHYSICAL DATA AND WIRING
SCHEMATICS
Tables 15-26 and Fig. 56-61 provide additional informa-
tion regarding compressor fits and clearances, physical and
electrical data, and wiring schematics for operator conve-
nience during troubleshooting.
SELECT softkey and then, using the INCREASE or
DECREASE softkeys, change the value until it is the
Fig. 55 — 4-In/2-Out Module
99
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 56 — Model Number Nomenclature for Compressor Size (See Fig. 1 Also)
Table 15 — 17EX Heat Exchanger Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*
COOLER
TOTAL
WEIGHT
ECONOMIZER/
STORAGE
VESSEL
COOLER
CHARGE
ECONOMIZER MISCELLANEOUS PUMPOUT
REFRIGERANT PIPING UNIT
COOLER
SIZE†
Dry**
Operating††
lb kg
Refrigerant
lb kg
Water
gal kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
L
45
46
47
48
25,032 11 355 30,098 13 652 2,060
25,529 11 580 30,881 14 008 2,160
934 3,006 361 1 364 1366
980 3,192 383 1 448 1450
7,900
3 583
840
318
1,149
521
210 95
26,025 11 805 31,663 14 362 2,260 1 025 3,378 405 1 532 1533
28,153 12 770 34,866 15 815 2,540 1 152 4,173 500 1 893 1893
CONDENSER TOTAL WEIGHT
CONDENSER
CONDENSER CHARGE
Refrigerant Water
Dry**
Operating††
SIZE†
lb
kg
lb
kg
lb
kg
lb
kg
45
46
47
55
56
57
16,676
17,172
17,669
20,725
21,663
22,446
7 564
7 789
8 015
9 401
9 826
10 182
20,596
21,280
21,965
25,598
26,891
27,971
9 342
9 653
1,200
1,200
1,200
1,420
1,420
1,420
544
544
544
644
644
644
2,720
2,908
3,096
3,453
3,808
4,105
1 234
1 319
1 404
1 566
1 727
1 862
9 963
11 611
12 198
12 688
**Dry weight includes all components attached to economizer: covers, float valves,
brackets, control center (31 lb [14 kg]), and power panel (20 lb [9 kg]). Dry
weight does not include compressor weight, motor weight, or pumpout con-
densing unit weight. The pumpout condensing unit weight is 210 lb (95 kg).
For compressor and motor weights, refer to Tables 18 and 20A and 20B.
††Operating weight includes dry weight, refrigerant weight, and water weight.
*If a chiller configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox
configuration is used, refer to Tables 16 and 17 to obtain the additional dry and
water weights that must be added to the values shown in this table.
†Cooler and condenser weights shown are based on 2-pass, nozzle-in-head
(NIH) waterboxes with 150 psig (1034 kPa) covers. Includes components at-
tached to cooler, but does not include suction/discharge, elbow, or other
interconnecting piping.
Table 16 — Additional Cooler Weights*
DESIGN MAXIMUM
WATER PRESSURE
ADDITIONAL
DRY WEIGHT
ADDITIONAL
COOLER
FRAME
WATERBOX
TYPE
NUMBER
WATER WEIGHT
OF PASSES
psig
150
300
300
150
150
300
300
kPa
1034
2068
2068
1034
1034
2068
2068
lb
kg
lb
—
—
gal
—
kg
—
L
—
—
—
2314
1157
2314
1157
NIH
NIH
NIH
Marine
Marine
Marine
Marine
1, 3
1, 3
2
1, 3
2
515
234
2941
2085
2100
792
1334
946
953
—
—
—
—
—
4
5102
2551
5102
2551
612
306
612
306
2314
1157
2314
1157
359
1, 3
2
3844
2536
1744
1150
*When using a chiller configuration other than 2-pass, NIH waterboxes with 150 psig (1038 kPa) covers, add the weighs listed in this table to the
appropriate weights in Table 15 to obtain the correct cooler weight.
100
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 17 — Additional Condenser Weights*
DESIGN MAXIMUM
NUMBER OF
ADDITIONAL
DRY WEIGHT
ADDITIONAL
HEAT EXCHANGER
SIZE
WATER PRESSURE
WATER WEIGHT
COMPONENT
WATERBOX TYPE
PASSES
psig
150
300
300
150
150
300
300
150
300
300
150
300
kPa
lb
kg
156
749
513
767
306
1 202
739
†
lb
—
kg
—
NIH
NIH
1, 3
1, 3
2
1034
2068
2068
1034
1034
2068
2068
1034
2068
2068
1034
2068
344
1652
1132
1692
674
—
—
NIH
—
—
45 - 47
Marine
Marine
Marine
Marine
NIH
1, 3
2
3 400
1 700
3 400
1 700
—
1 542
771
1 542
771
—
1, 3
2
2651
1630
†
CONDENSER
1
NIH
1
1588
1591
25
720
721
11
—
—
55 - 57
NIH
2
—
—
Marine
Marine
2
1 734
1 734
787
787
2
1225
555
NIH
—
Nozzle-In-Head
†Subtract 228 lb (103 kg) from the weight shown in Table 15.
*When using a chiller configuration other than 2-pass, NIH waterboxes with
150 psig (1034 kPa) covers, add the weights listed in this table to the appro-
priate weights in Table 15 to obtain the correct condenser weight.
Table 18 — Compressor Weight and Elbow Weight
WEIGHT*
English (lb)
COMPONENT
SI (kg)
2270
225
COMPRESSOR
5000
500
SUCTION ELBOW
*Approximate.
Table 19 — Drive Component Weights*
COUPLING
GEAR
BASE
GUARD
kg
23
High
Low
lb
kg
lb
kg
lb
kg
lb
kg
lb
2200
998
1500
680
32
15
75
34
50
*See Table 20A or 20B for motor weights.
101
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 20A — Total Motor Weight, English (lb)
ENCLOSURE
TYPE
HERTZ
VOLTAGE
SIZE (HP)
FH (1600)
FA, FF (1250)
FB, FG (1500)
FC, FJ (1750)
FD, FK (2000)
2400
3300
4160
6900
4836
4824
4836
5596
5721
5832
5721
6577
5900
5832
5900
8776
5900
5832
5900
8776
7160
7127
7160
8990
60 Hz
Open-Drip Proof
(ODP)
3000
3300
6300
5518
5518
5596
5878
5878
6577
7148
7148
8875
7148
7148
8875
9048
9073
8976
50 Hz
60 Hz
50Hz
HA, HF (1250)
HB, HG (1500)
HH (1600)
HC, HJ (1750)
HD, HK (2000)
2400
3300
4160
6900
5146
5134
5146
5906
6151
6262
6151
7007
6330
6262
6330
9206
6330
6262
6330
9206
7600
7567
7600
9430
Weather Protected
Type II (WPII)
3000
3300
6300
5828
5828
5906
6308
6308
7007
7578
7578
9305
7578
7578
9305
9488
9513
9416
JA, JF (1250)
JB, JG (1500)
JH (1600)
JC, JJ (1750)
JD, JK (2000)
2400
3300
4160
6900
5707
5694
5707
6466
6746
6857
6746
7602
6925
6857
6925
9801
6925
6857
6925
9801
8290
8257
60 Hz
50 Hz
Totally Enclosed
Water-To-Air Cooled
(TEWAC)
8290
10,120
3000
3300
6300
6388
6388
6466
6903
6903
7602
8173
8173
9900
8173
8173
9900
10,178
10,203
10,106
Table 20B — Total Motor Weight, SI (kg)
ENCLOSURE
TYPE
FREQ
VOLTAGE
SIZE (kW)
FA, FF (932)
FB, FG (1119)
FH (1194)
FC, FJ (1305)
FD, FK (1492)
2400
3300
4160
6900
2194
2188
2194
2538
2595
2645
2595
2983
2676
2645
2676
3981
2676
2645
2676
3981
3248
3233
3248
4033
60 Hz
Open-Drip Proof
(ODP)
3000
3300
6300
2503
2503
2538
2666
2666
2983
3242
3242
4026
3242
3242
4026
4104
4116
4072
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
HA, HF (932)
HB, HG (1119)
HH (1194)
HC, HJ (1305)
HD, HK (1492)
2400
3300
4160
6900
2334
2329
2334
2679
2790
2840
2790
3178
2871
2840
2871
4175
2871
2840
2871
4126
3447
3432
3447
4277
Weather Protected
Type II (WPII)
3000
3300
6300
2644
2644
2679
2861
2861
3178
3437
3437
4221
3437
3437
4221
4304
4315
4271
JA, JF (932)
JB, JG (1119)
JH (1194)
JC, JJ (1305)
JD, JK (1492)
2400
3300
4160
6900
2587
2583
2587
2933
3060
3110
3060
3448
3141
3110
3141
4446
3141
3110
3141
4446
3760
3745
3760
4590
Totally Enclosed
Water-To-Air Cooled
(TEWAC)
3000
3300
6300
2898
2898
2933
3131
3131
3448
3707
3707
4491
3707
3707
4490
4617
4628
4584
102
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Marine Waterbox Cover Weights*
DESIGN MAXIMUM WATER PRESSURE
COOLER
CONDENSER
HEAT EXCHANGER
SIZE
psi
150
300
150
300
kPa
1034
2068
1034
2068
lb
kg
1015
1389
—
lb
kg
579
754
746
1018
2236
3060
—
1275
1660
1643
2243
45 - 48
55 - 57
—
—
*Heat exchangers with marine waterboxes have heavier dry and operating weights than heat exchangers
with nozzle-in-head waterboxes.
Table 22 — NIH Waterbox Cover Weights*
DESIGN MAXIMUM WATER PRESSURE
COOLER
lb kg
CONDENSER
HEAT EXCHANGER
SIZE
PASSES
psi
150
300
150
300
150
300
150
300
150
300
150
300
kPa
lb
kg
788
1140
856
1176
807
1153
923
1335
1203
1653
—
1034
2068
1034
2068
1034
2068
1034
2068
1034
2068
1034
2068
2997 1361 1735
4225 1918 2510
2984 1355 1885
4188 1901 2590
3035 1378 1777
4244 1927 2539
1
45 - 48
2†
3
—
—
—
—
—
—
—
—
—
—
—
—
2032
2940
2649
3640
—
1
55 - 57
2†
3
—
—
NIH
—
Nozzle-in-Head
*The 150 psig (1034 kPa) waterbox cover weights are included in the dry weight shown in Table 15.
†Two different waterbox covers are present on 2-pass chillers. The weight shown in this table represents the
weight of the waterbox cover that contains the nozzles. A blank waterbox cover is also present on 2-pass
units. The weight of the blank waterbox cover is identical to the weight of the same size marine waterbox
cover. Refer to Table 21.
Table 23 — Approximate Refrigerant (HCFC-134a) Charge*
TOTAL CHILLER
COOLER
SIZE
CONDENSER
SIZE
CHARGE
lb
kg
45
46
47
55
56
57
45
46
47
55
56
57
45
46
47
55
56
57
45
46
47
55
56
57
4100
1860
45
46
47
48
4320
4200
4420
4300
4520
4580
4800
1960
1905
2005
1950
2050
2077
2177
*Total chiller refrigerant charge includes the cooler, condenser, and economizer charges.
NOTE: Regulations mandate that chiller shipping charge is limited to 7500 lb (3402 kg).
103
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 24 — Auxiliary Systems, Electrical Data
DESIGN CENTER
AVERAGE kW
SUPPLY
V-PH-Hz
POWER SOURCE
ITEM
FLA
4.78
4.35
3.50
8.70
2.00
LRA
21.7
4.35
—
VOLTAGE
Seal Leakage
Pump
0.23
0.50
0.40
1.00
0.20
115
115
115
115
115
115-1-50/60
115-1-50/60
Motor Space
Heater
Control Module
and Actuator
115-1-60
115-1-50
1
115-1-60
115-1-50
Oil Sump Heater
—
Hot Gas*
Bypass
115-1-50/60
4.75
220
430
563
200/240-3-60
380/480-3-60
507/619-3-60
4.34
2.15
2.14
24.5
13.1
25.0
Compressor
Oil Pump
2†
3†
0.66
0.7
230
393
220/240-3-50
346/440-3-50
4.84
2.59
28.0
12.2
204
220
460
575
200/208-3-60
208/230-3-60
440/480-3-60
518/632-3-60
5.7
4.2
2.1
1.7
33.5
30.6
15.3
12.3
Gear
Oil Pump
205
410
190/220-3-50
380/440-3-50
5.0
2.5
28.9
14.5
204
230
460
575
200/208-3-60
220/240-3-60
440/480-3-60
550/600-3-60
10.90
9.50
4.70
3.80
63.5
57.5
28.8
23.0
Pumpout*
Compressor
4
3.41
400
380/415-3-50
4.70
28.8
LEGEND
NOTE: The oil pump is powered through a field wiring terminal into
the power panel. Power to the controls and oil heater via the power
panel must be on circuits that can provide continuous service when
the compressor starter is disconnected.
FLA
LRA
—
—
Full Load Amps
Locked Rotor Amps
*Available as an option on 17EX chillers.
†The compressor and gear oil pump contactors are wired together
on the line side. Their amperage values must be added together
when sizing conductors.
Table 25 — Relief Valve Locations and Data
NOMINAL
OUTLET
PIPE SIZE
(in.)
HEAT EXCHANGER
SIZE
REQUIRED
C FACTOR
RATED RELIEF
PRESSURE
RELIEF VALVE
LOCATION
NUMBER OF
VALVES
Cooler
Condenser
lb air/min.
kg air/sec.
psig
kPa
45-47
48
45-47
55-57
216.3
228.5
1.64
1.73
11⁄4 FPT
11⁄4 NPT
3
3
225
225
1551
1551
Cooler
Economizer/Storage
Vessel
ALL
ALL
ALL
ALL
84.3
1.5
0.64
0.01
11⁄4 FPT
2*
1
225
385
1551
2655
Pumpout Unit
Condenser
3
⁄8
in. Male Flare MPT
*To ensure relief valve serviceability, and as required in ASHRAE 15,
latest edition, three-way valves and redundant relief valves are in-
stalled on the storage vessel. Only one of the ‘‘No. of Valves’’ listed
are in service at any time.
2. Relief valve discharge pipe sizing is to be calculated per latest
version of ASHRAE 15, using the tabulated C-factors and nom-
inal pipe size listed above. Cooler and economizer/storage vessel
rated relief valve pressure is 225 psig (1551 kPa).
3. The pumpout unit condenser contains less than 110 lb (50 kg) of
HFC-134a, which is a Group A1 refrigerant. The ASHRAE 15 stand-
ard exempts small-volume vessels from the requirement to vent
outside. However, Carrier recommends that the pumpout con-
denser be connected to the rest of the vent system.
NOTES:
1. The cooler relief C-factor is for both cooler and condenser vented
through the cooler in accordance with ASHRAE (American
Society of Heating, Refrigeration, and Air Conditioning Engi-
neers) 15, latest edition.
104
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: Refer to Table 26 for item number references.
Fig. 57 — Compressor Fits and Clearances
105
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 26 — Compressor Fits and Clearances
CLEARANCE
TYPE OF
MEASURE
ITEM
DESCRIPTION
Minimum
Maximum
in.
mm
in.
mm
1
2
3
4
5
6
7
8
1st Stage Impeller to Diaphragm
Interstage Labyrinth
See Tabulation
Axial
Diametral
Axial
0.012
0.305
0.016
0.406
2nd Stage Impeller to Discharge Wall
Thrust End Journal Bearing
Thrust End Float
See Tabulation
0.0035
0.010
0.0889
0.254
0.0055
0.015
0.1397
0.381
Diametral
Axial
Inner Carbon Ring Travel
Shaft End Labyrinth
.06 in. (1.52 mm) minimum in each direction
Axial
0.001
0.092
0.008
0.023
0.006
0.008
0.018
0.008
0.016
0.018
0.0035
0.025
2.337
0.203
0.584
0.152
0.203
0.457
0.203
0.406
0.457
0.0889
0.005
0.095
0.010
0.025
0.010
0.012
0.022
0.012
0.020
0.022
0.0055
0.127
2.413
0.254
0.635
0.254
0.305
0.559
0.305
0.508
0.559
0.1397
Diametral
Diametral
Windage Baffle to Shaft
Shaft Displacement (Shrouds 3 - 6)
Detector (Shrouds 8 & 9)
9
10
11
12
13
14
Axial
Counterthrust Bearing Seal Ring
Balancing Piston, Labyrinth
2nd Stage Labyrinth
Diametral
Diametral
Diametral
Diametral
Diametral
(Shrouds 3 - 6)
(Shrouds 8 & 9)
1st Stage
Labyrinth
Seal End Journal Bearing
106
Download from Www.Somanuals.com. All Manuals Search And Download.
Tabulation — Impeller Clearances (Open-Drive Compressors)
DIMENSION*
IMPELLER DIAMETER
COMPRESSOR
SIZE
DIAM
CODE
SHROUD
Item 1
Item 3
in.
mm
304.8
314.5
323.8
336.6
349.2
304.8
314.5
323.8
336.6
349.2
304.8
314.5
323.8
336.6
349.2
304.8
314.5
323.8
336.6
349.2
349.2†
342.9**
349.2†
342.9**
in.
mm
in.
mm
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
12.00
12.38
12.75
13.25
13.75
12.00
12.38
12.75
13.25
13.75
12.00
12.38
12.75
13.25
13.75
12.00
12.38
12.75
13.25
13.75
13.75†
13.50**
13.75†
13.50**
.837
21.26
20.24
19.23
18.21
17.53
24.82
23.80
22.78
23.62
20.57
29.90
28.88
27.36
25.83
24.64
32.94
31.42
29.90
27.86
26.67
.638
.609
.579
.541
.541
.760
.726
.688
.639
.632
.895
.852
.809
.750
.731
.972
.928
.880
.817
.796
16.21
15.47
14.71
13.74
13.74
19.30
18.44
17.48
16.23
16.05
25.02
21.64
20.55
19.05
18.57
24.69
23.57
22.35
20.75
20.22
.797
3
.757
.717
.690
.977
.937
4
5
6
.897
.837
.810
1.177
1.137
1.077
1.017
.970
17FX
1.297
1.237
1.177
1.097
1.050
8
9
1-9
1-9
4.425
4.425
112.39
112.39
.876
22.25
26.80
1.055
*Measured with shaft in thrust position (towards suction end); tolerance = ± .005 in. (± .127 mm).
†First-stage diameter.
**Second-stage diameter.
107
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
BRG
C
—
—
—
—
—
—
—
—
Bearing
DIFF
—
—
—
—
—
—
—
—
Differential
INT
J
—
—
—
—
—
—
—
—
Internal
Contactor
DISCH
ENT
Discharge
Entering
Junction
CB
Circuit Breaker
Channel
Communications
Compressor
Condenser
Detector
K
Relay Designation
Line Terminal
Leak Detector
Local Interface Device
Leaving
CH
EVAP
EXT
Evaporator
External
Guide Vane
Hot Gas Bypass
Heater
L
COM
COMP’R
COND
DETR
LD
LID
LVG
M
G.V.
HGBP
HTR
Motor
Fig. 58 — Typical 17EX Power Panel and Control Panel Wiring Schematic
108
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
PH
—
—
—
Phase
TEMP
—
—
Temperature
IMPORTANT: Wiring shown is typical and not intended to
show detail for a specific installation. Refer to certified field
wiring diagrams.
PRESS.
PSIO
Pressure
TEWAC
Totally Enclosed
Water-to-Air Cooled
Terminal Designation
Terminal Strip
Processor/Sensor
Input/Output Module
Terminal Designation
Starter Management Module
Terminal
Thermistor
Terminal Block
TG
TS
—
—
R
—
—
—
—
—
SMM
T
Required Power Wiring
Required Control Wiring
Options Wiring
t*
TB
Fig. 58 — Typical 17EX Power Panel and Control Panel Wiring Schematic (cont)
109
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
NOTE: Voltage to terminals LL1 and LL2 comes from a control trans-
former in a starter built to Carrier specifications. Do not connect an
outside source of control power to the compressor motor starter (ter-
minals LL1 and LL2). An outside power source will produce danger-
ous voltage at the line side of the starter, because supplying voltage
at the transformer secondary terminals produces input level voltage
at the transformer primary terminals.
CB
—
—
—
—
—
—
—
—
—
Circuit Breaker
Communications
Normally Open
Normally Closed
Overload
COMM
N.O.
N.C.
O.L.
PR
Pilot Relay
RLA
SMM
TB
Rated Load Amps
Starter Management Module
Terminal Block
Starter Vendor Supplied Wiring
Field Wiring
Carrier Factory Wiring
Fig. 59 — Elementary Wiring Diagram for Starter Management Module (SMM) and Control Interface Between
Starter and Chiller Power Panel (For Low and Medium Voltage Free-Standing Starters)
110
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 59 — Elementary Wiring Diagram for Starter Management Module (SMM) and Control Interface Between
Starter and Chiller Power Panel (For Low and Medium Voltage Free-Standing Starters) (cont)
111
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
⌬P
—
—
—
—
—
—
Differential Pressure
PR
SP
—
—
Pilot Relay
IMPORTANT: Wiring shown is typical and not intended to show detail
for a specific installation. Refer to certified field wiring diagrams.
C
Contactor
Open Terminal Designation
(Open Space)
Switch
COMP’R
Compressor
Ground
Line Terminal
Control Power Line
Terminal
Motor
Overloads
3-Phase Current Power
Source
G
SW
T
TB
—
—
—
L
Terminal
Terminal Board
Required Power Wiring
Required Control Wiring
Options Wiring
LL
M
OL’s
OS
—
—
—
Fig. 60 — Field Wiring Diagram (Medium Voltage Motor, PIC Controls With Free-Standing Starter)
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES FOR FIG. 60
I GENERAL
3.4 Do not route control wiring carrying 30 v or less within a conduit
which has wires carrying 50 v or higher or alongside wires car-
rying 50 v or higher.
1.0 Starters shall be designed and manufactured in accordance
with Carrier Engineering requirement Z-375.
3.5 Voltage selector switch in chiller power panel is factory set for
115 v control and oil heater power source. The 230 v position is
not used. If switch is set to 230 v position, oil heater will not
operate.
3.6 Control wiring cables between starter and power panel must be
shielded with minimum rating of 600 v, 80 C. Ground shield at
starter. Starter Management Module (SMM) communication cable
must be separate.
1.1 All field-supplied conductors and devices, field-installation wir-
ing, and termination of conductors and devices must be in com-
pliance with all applicable codes and job specifications.
1.2 The routing of field-installed conduit and conductors and the
location of field-installed devices must not interfere with equip-
ment access of the reading, adjusting, or servicing of any
component.
1.3 Equipment installation and all starting and control devices must
comply with details in equipment submittal drawings and
literature.
1.4 Contacts and switches are shown in the position they would
assume with the circuit deenergized and the chiller shut down.
1.5 WARNING: Do not use aluminum conductors.
1.6 Installer is responsible for any damage caused by improper
wiring between starter and chiller.
3.7 If optional oil pump circuit breaker is not supplied within the starter
enclosure as shown, it must be located within sight of the chiller
with wiring routed to suit.
3.8 Voltage to terminals LL1 and LL2 comes from a control trans-
former in a starter built to Carrier specifications. Do not connect
an outside source of control power to the compressor motor starter
(terminals LL1 and LL2). An outside power source will produce
dangerous voltage at the line side of the starter, because sup-
plying voltage at the transformer secondary terminals produces
input level voltage at the transformer primary terminals.
4.0 Medium voltage (over 600 volts) compressor motors have 3 ter-
minal connections (lead hooks). Use suitable splice connectors
and insulation for high voltage alternating current cable termi-
nations (these items are not supplied by Carrier). Compressor
motor starter must have nameplate stamped to conform with
Carrier requirement Z-375.
II POWER WIRING TO STARTER
2.0 Provide a means of disconnecting power to the starter.
2.1 Power conductor rating must meet minimum unit nameplate
voltage and compressor motor RLA (rated load amps). When
3 conductors are used:
Minimum ampacity per conductor = 1.25 x compressor RLA.
When 6 conductors are used:
Minimum ampacity per conductor = 0.721 x compressor RLA.
2.2 Lug adapters may be required if installation conditions dic-
tate that conductors be sized beyond the minimum ampacity
required. Contact starter supplier for lug information.
2.3 Compressor motor and controls must be grounded by using
equipment grounding lugs provided inside starter enclosure.
4.1 Power conductor rating must meet minimum unit nameplate volt-
age and compressor motor RLA. (Conductor as defined below
may be a single lead or multiple smaller ampacity leads in par-
allel for the purpose of carrying the equivalent or higher current
of a single larger lead.)
III CONTROL WIRING
When (3) conductors are used:
3.0 Field supplied control conductors to be at least 18 AWG
Minimum ampacity per conductor = 1.25 × compressor RLA.
4.2 When more than one conduit is used to run conductors form starter
to compressor motor terminal box, an equal number of leads from
each phase (conductor) must be in each conduit to prevent ex-
cessive heating (e.g., conductors to motor terminals 1, 2 and 3
in one conduit, and those to 1, 2 and 3 in another.)
4.3 Compressor motor power connections can be made through top,
top rear, or sides of compressor motor terminal box using holes
cut by contractor to suit conduit. Flexible conduit should be used
for the last few feet to the terminal box for unit vibration isolation.
Use of stress cones may require an oversize (special) motor ter-
minal box (not supplied by Carrier).
4.4 Compressor motor frame to be grounded in accordance with the
National Electrical Code (NFPA-70) and applicable codes. Means
for grounding compressor motor is 2 ground pads, 1 each lo-
cated near each motor foot opposite the shaft end.
4.5 Do not allow motor terminals to support weight of wire cables.
Use cable supports and strain reliefs as required.
(American Wire Gage) or larger.
3.1 Chilled water and condenser water flow switch contacts, op-
tional remote start device contacts, and optional spare safety
device contacts must have 24 vdc rating. Maximum current is
60 mA; nominal current is 10 mA. Switches with gold plated
bifurcated contacts are recommended.
3.2 Remove jumper wire between 12A and 12B before connect-
ing auxiliary safeties between these terminals.
3.3 Pilot relays can control cooler and condenser pump and tower
fan motor contactor coil loads rated up to 10 amps at 115 vac
or up to 3 amps at 600 vac. Control wiring required for Carrier
to start pumps and tower fan motors must be provided to as-
sure chiller protection. If primary pump and tower motor con-
trol is by other means, also provide a parallel means for con-
trol by Carrier. Do not use starter control transformer as the
power source for pilot relay loads.
113
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
EQUIP
GND
HGBP
S
T1-T4
TS
—
—
—
—
—
—
Equipment
Ground
Hot Gas Bypass
Switch
Power Panel Transformers
Terminal Strip
Fig. 61 — Oil Pump and Control Power Panel (Interior View)
114
Download from Www.Somanuals.com. All Manuals Search And Download.
INDEX
Abbreviations, 5
Check Pressure Transducers, 83
Check Pumpout System Controls and Optional
Pumpout Compressor, 56
Access the Service Screen, To (Service Operation), 42
Accidental Start-Up, To Prevent, 61
Accuracy, Check Sensor (Checking
Temperature Sensors), 84
Check Relief Devices, 50
Check Safety and Operating Controls Monthly, 76
Check Sensor Accuracy (Checking Temperature Sensors), 84
Check Starter, 53
Check the Compressor Oil Heater, Power Up
the Controls and, 54
Check the Lubrication System, 76
Check the Running System, 62
Check Voltage Supply, 56
Checking Guide Vane Linkage, 68
Checking Pressure Transducers, 84
Checking Temperature Sensors (Troubleshooting Guide), 84
Checking the Display Messages, 84
Checklist for 17EX Externally Geared Centrifugal
Liquid Chiller, Initial Start-Up, CL-1 to CL-12
Checkout Procedure, Control Algorithms, 85
Chilled Water Control, Entering, 32
Chilled Water Recycle Mode, 44
Chiller Alignment, 71
Chiller Communication Wiring (Lead/Lag Control), 38
Chiller Control Configuration, Set Up, 54
Chiller Cycles (Instruct the Operator), 62
Chiller Dehydration, 49
Chiller Familiarization, 17EX, 5
Chiller Identification Label, 5
Adding Refrigerant, 67
Adjusting the Refrigerant Charge, 67
After Extended Shutdown, 63
After Limited Shutdown, 63
After Power Failure,
Auto. Restart (Lead/Lag Control), 40
Auto. Restart (Controls), 36
Alarm Contacts, Spare, 36
Alarms and Alerts, 16
Alerts, Alarms and, 16
Algorithm, Surge Prevention, 37
Alignment,
Chiller, 71
Disc Coupling, and Installation, 59
Final (Chiller Alignment), 74
Near Final (Chiller Alignment), 71
Preliminary (Chiller Alignment), 71
Alignment Check,
Hot (Chiller Alignment), 74
Hot, 61
Alignment Methods (Chiller Alignment), 71
Altitude Locations, High, 57
Analog Signal (Controls), 11
Attach to Network Device Control, 41
Attaching to Other CCN Modules
(Attach to Network Device Control), 41
Auto. Restart After Power Failure (Controls), 36
Auto. Restart After Power Failure (Lead/Lag Control), 40
Automated Control Test, Perform an, 56
Automatic Soft Stop Amps Threshold, 44
Auxiliary Compressor Oil Pump Control, 33
Auxiliary Devices, Motor, 46
Auxiliary Equipment (Instruct the Operator), 62
Auxiliary Gear Oil Pump Control, 33
Balancing, Load (Lead/Lag Control), 40
Bearing Maintenance, Compressor, 82
Before Initial Start-Up, 45
Chiller Operating Condition, Check, 61
Chiller Parts, Ordering Replacement, 83
Chiller Tightness, Check, 46
Chiller Timers, 32
Chiller, Leak Test the, 46
Cleanliness (Motor Maintenance), 79
Cold Weather Operation, 63
Common Point Sensor Installation (Lead/Lag Control), 38
Communication Wiring, Chiller (Lead/Lag Control), 38
Components,
PIC System, 12
System, 5
Compressor, 5
Compressor Assembly (Instruct the Operator), 62
Compressor Bearing Maintenance, 82
Compressor Lubrication Cycle, 8
Compressor Lubrication System (Instruct the Operator), 62
Compressor Oil (Oil Changes), 77
Compressor Oil Charge, 54
Calibrate Motor Current Demand Setting, 61
Calibration, Oil Differential Pressure/Power Supply
Module (Checking Pressure Transducers), 85
Capacity Control, 32
Capacity Override, 35
Carrier Comfort Network Interface (CCN), 53
CCN Modules, Attaching to Other (Attach to
Network Device Control), 41
Compressor Oil Cooling, 8
Compressor Oil Filter (Changing the Oil Filters), 76
Compressor Oil Pump Contactor (2C) and Gear
Oil Pump Contactor (5C), 16
Change LID Configuration If Necessary, 55
Change Point Status, To View or, 17
Change Set Points, To View and, 22
Change Time Schedule Operation, To View or, 18
Changing the Oil Filters, 76
Charge, Compressor Oil, 54
Charge Refrigerant into Chiller, 57
Check,
Hot Alignment (Chiller Alignment), 74
Hot Alignment, 61
Resistance (Checking Temperature Sensors), 84
Check Chiller Operating Condition, 61
Check Chiller Tightness, 46
Check Insulation Resistance (Inspect Wiring), 50
Check Motor Rotation, 58
Check Oil Pressure and Compressor Stop, 61
Check Operator Knowledge, 62
Check Optional Pumpout Compressor Water Piping, 50
Compressor Oil Pump Control, Auxiliary, 33
Compressor Stop, Check Oil Pressure and, 61
Compressor, Operating the Optional Pumpout, 63
Condenser, 5
Condenser (Inspect the Heat Exchanger Tubes), 82
Condenser Freeze Prevention, 36
Condenser Pump Control, 36
Configuration,
Change LID, If Necessary, 55
Modify Equipment, If Necessary, 56
Set Up Chiller Control, 54
Configurations, Input Service, 54
Contact Seal Maintenance, 68
Contactor (IC), Oil Heater, 16
Contactors, Compressor Oil Pump (2C) and
Gear Oil Pump (5C), 16
Contacts, Spare Alarm, 36
115
Download from Www.Somanuals.com. All Manuals Search And Download.
INDEX (cont)
Eight-Input Modules, 16
Control,
Auxiliary Compressor Oil Pump, 33
Electrical Connection, Motor, 45
Entering Chilled Water Control, 32
Equipment Configuration, Modify If Necessary, 56
Equipment Required (Before Initial Start-Up), 45
Equipment Service Parameters, Input If Necessary, 55
Extended Downtime (External Gear Storage), 82
Extended Shutdown, 63
Auxiliary Gear Oil Pump, 33
Capacity, 32
Condenser Pump, 36
Entering Chilled Water, 32
High Discharge Temperature, 35
Ice Build, 40
Lead/Lag, 38
Extended Shutdown, After, 63
Oil Sump Temperature, 35
External Gear (Remove Shipping Packaging), 45
External Gear Lubrication Cycle, 9
External Gear Lubrication System (Instruct the
Operator), 62
Ramp Loading, 33
Control Algorithms Checkout Procedure, 85
Control and Oil Heater Voltage Selector (S1), 16
Control Center, 5
External Gear Maintenance, 82
Control Center, Inspect the (Scheduled Maintenance), 76
Control Configuration, Set Up Chiller, 54
Control Modules, 96
External Gear Oil (Oil Changes), 77
External Gear Oil Cooling, 8
External Gear Oil Filter (Changing the Oil Filters), 77
External Gear Pre-Start Checks, 51
External Gear Replacement Parts, 83
External Gear Storage, 81
Familiarization, 17EX Chiller, 5
Faulted Chiller Operation (Lead/Lag Control), 40
Filter,
Control Settings, Pumpout Safety, 83
Control System (Instruct the Operator), 62
Control Test (Troubleshooting Guide), 85
Control Test, Perform and Automated, 56
Control Transformers (T1-T4), 16
Controller Identification, Modify If Necessary, 55
Controls, 11
Compressor Oil (Changing the Oil Filters), 76
External Gear Oil (Changing the Oil Filters), 77
Final Alignment (Chiller Alignment), 74
Four-In/2-Out Module, 16, 98
Controls,
Remote Start/Stop, 36
Safety, 33
Cooler, 5
Freeze, Default Screen, 33
Freeze Prevention, Condenser, 36
Functions, PIC System, 32
Cooler (Inspect the Heat Exchanger Tubes), 82
Cooler-Condenser (Instruct the Operator), 62
Cooler/Condenser/Compressor Section, Transferring
Refrigerant Into the, 67
Gasketed Joints and Guide Vane Shaft Packing,
Tighten All, 46
Coupling, Disc, Installation and Alignment, 59
Coupling Maintenance, 78
Gear, External, 45
Gear Maintenance, External, 82
Cycle,
Gear Oil Pump Contactor (5C), and Compressor
Oil Pump Contactor (2C), 16
Lubrication, 8
Oil Cooling, 8
Gear Oil Pump Control, Auxiliary, 33
General (Controls), 11
General (LID Operation and Menus), 16
General Maintenance, 67
Refrigeration, 5
Cycles, Chiller (Instruct the Operator), 62
Date, Input Time and, 55
Deadband (PIC System Functions), 32
Default Screen Freeze, 33
Green LEDs (Control Modules), 96
Guide Vane Linkage, Checking, 68
Guide Vane Operation, Manual (Operating Instructions), 63
Guide Vane Shaft Packing, Tighten All Gasketed
Joints and, 46
Guide Vanes, Manual Operation of the, 58
Guide, Troubleshooting, 83
Handling/Rigging, Motor, 81
Heat Exchanger Tubes, Inspect the (Scheduled
Maintenance), 82
High Altitude Locations, 57
High Discharge Temperature Control, 35
Holiday Scheduling (Service Operation), 42
Hot Alignment Check, 61
Hot Alignment Check (Chiller Alignment), 74
Hot Gas Bypass Contactor Relay (3C) (Optional), 16
Ice Build,
Default Screen Menu Items, LID, 17
Defective Processor Modules, Replacing, 98
Definitions, 11
Dehydration, Chiller, 49
Demand Limit Control Option (Requires Optional
8-Input Module), 37
Demand Limiting, 32
Design Set Points, Input the, 54
Device (LID), Local Interface, 16
Digital Signal (Control), 11
Disc Coupling Installation and Alignment, 59
Display Messages, Checking the, 84
Doweling, (Chiller Alignment), 75
Doweling, (Initial Start-Up), 61
Downtime, Extended (External Gear Storage), 82
Dry Nitrogen, To Pressurize With, 68
Dry Run to Test Start-Up Sequence, 58
Dual Temperature Sensors (Checking Temperature
Sensors), 84
Temperature Control During (Ice Build Control), 41
Termination of (Ice Build Control), 41
Ice Build Control, 40
Ice Build Initiation (Ice Build Control), 40
Identification Label, Chiller, 5
Duties, Operator, 62
Economizer/Storage Vessel (Instruct the Operator), 62
Economizer/Storage Vessel and Pumpout System,
Using the, 45
Important Information (Disc Coupling Installation
and Alignment), 61
Initial Start-Up, 57
Economizer/Storage Vessel, 5
Economizer/Storage Vessel, Transferring Refrigerant
Into the, 66
Initial Start-Up Checklist for 17EX Externally
Geared Centrifugal Liquid Chiller, CL-1 to CL-12
116
Download from Www.Somanuals.com. All Manuals Search And Download.
INDEX (cont)
Maintenance,
Initial Start-Up,
Before, 45
Compressor Bearing, 82
Motor, 58
Contact Seal, 68
Initiation, Ice Build (Ice Build Control), 40
Input Equipment Service Parameters If Necessary, 55
Input/Output Module (PSIO), Processor/Sensor, 16
Input Service Configurations, 54
Input the Design Set Points, 54
Input the Local Occupied Schedule (OCCPC01S), 54
Input Time and Date, 55
Coupling, 78
External Gear, 82
General, 67
Motor, 78
Pumpout System, 83
Scheduled, 76
Weekly, 76
Inputs,
(4-In/2-Out Module), 98
(Processor/Sensor Input/Output Module), 97
(Starter Management Module), 97
Spare Safety, 36
Inspect Refrigerant Float System (Scheduled
Maintenance), 78
Inspect Relief Valves and Piping (Scheduled
Maintenance), 78
Major Leak, Test After Service, Repair or, 67
Manual Guide Vane Operation (Operating Instructions), 63
Manual Operation of the Guide Vanes, 58
Mechanical Starters (Check Starter), 53
Memory, Volatile, 11
Menu Items, LID Default Screen, 17
Menu Structure, 17
Menus, LID Operation and, 16
Messages, Checking the Display, 84
Mode, Chilled Water Recycle, 44
Modify Controller Identification If Necessary, 55
Modify Equipment Configuration If Necessary, 56
Module,
Installation of New PSIO, 98
Oil Differential Pressure/Power Supply, 16
Processor/Sensor Input/Output (Troubleshooting
Guide), 97
Starter Management (Troubleshooting Guide), 97
Module (PSIO), Processor/Sensor Input/Output, 16
Module (PSIO), Processor/Sensor Input/Output
(Troubleshooting Guide), 97
Inspect the Control Center (Scheduled Maintenance), 76
Inspect the Heat Exchanger Tubes (Scheduled
Maintenance), 82
Inspect the Starting Equipment (Scheduled Maintenance), 83
Inspect Water Piping, 50
Inspect Wiring, 50
Installation and Alignment, Disc Coupling, 59
Installation of New PSIO Module, 98
Installation, Common Point Sensor (Lead/Lag Control), 38
Instruct the Operator, 62
Instructions, Operating, 62
Insulation Resistance, Check (Inspect Wiring), 50
Interface (CCN), Carrier Comfort Network, 53
Introduction, 5
Module (SMM), Starter Management, 16
Module (SMM), Starter Management (Troubleshooting
Guide), 97
Job Data Required (Before Initial Start-Up), 45
Label, Chiller Identification, 5
Lead/Lag Control, 38
Module Calibration, Oil Differential Pressure/Power
Supply (Checking Pressure Transducers), 85
Module Operation, Notes on, 96
Module, 4-In/2-Out, 16, 98
Lead/Lag Operation (Lead/Lag Control), 39
Leak,
Test the Chiller, 46
Modules,
Water, 82
Attaching to Other CCN (Attach to Network Device
Control), 41
Leak Rate, 67
LEDs,
Control, 96
Green (Control Modules), 96
Red (Control Modules), 96
Eight-Input, 16
Options (8-Input), 98
LID Configuration, Change If Necessary, 55
LID Default Screen Menu Items, 17
LID, Local Interface Device, 16
LID Operation and Menus, 16
Limited Shutdown, After, 63
Linkage, Checking Guide Vane, 68
Load Balancing (Lead/Lag Control), 40
Local Interface Device (LID), 16
Local Occupied Schedule (OCCPC01S), Input the, 54
Local Start-Up, 43
Replacing Defective Processor, 98
Monthly, Check Safety and Operating Controls, 76
Motor (Remove Shipping Packaging), 45
Motor Auxiliary Devices, 46
Motor Current Demand Setting, Calibrate, 61
Motor Electrical Connection, 45
Motor Handling/Rigging, 81
Motor Initial Start-Up, 58
Motor Maintenance, 78
Motor Pre-Start Checks, 51
Log Off, To (Service Operation), 42
Log, Refrigeration, 63
Motor Replacement Parts, 83
Motor Rotation, Check, 58
Long-Term Storage (External Gear Storage), 81
Lubrication Cycle, 8
Motor Sleeve Bearing and Pumpout Compressor Oil
(Oil Changes), 78
Lubrication Cycle,
Motor Starter, 5
Motor Storage, 81
Compressor, 8
External Gear, 9
Near Final Alignment (Chiller Alignment), 71
Network Device Control, Attach to, 41
Nitrogen, To Pressurizes With Dry, 68
Non-Ice Build Operations, Return to (Ice Build Control), 41
Normal Operating Conditions, Return Chiller to, 67
Notes on Module Operation, 96
Lubrication System,
Check the, 76
Compressor (Instruct the Operator), 62
External Gear (Instruct the Operator), 62
Maintenance (Instruct the Operator), 62
117
Download from Www.Somanuals.com. All Manuals Search And Download.
INDEX (cont)
Perform an Automated Control Test, 56
OCCPC01S, Input the Local Occupied Schedule, 54
Occupancy Schedule, 32
Physical Data and Wiring Schematics, 99
PIC System Components, 12
PIC System Functions, 32
Occupied Schedule (OCCPC01S), Input the Local, 54
Oil,
Compressor, 77
Piping,
External Gear, 77
Check Optional Pumpout Compressor Water, 50
Inspect Relief Valves and (Scheduled Maintenance), 78
Inspect Water, 50
Oil Auxiliary Relay (4C), 16
Oil Changes (Scheduled Maintenance), 77
Oil Charge, Compressor, 54
Point Status, To View or Change, 17
Power Failure,
Oil Charge, Optional Pumpout Compressor, 83
Oil Circuit Valves, Open, 46
Auto. Restart After (Lead/Lag Control), 40
Auto. Restart After (Controls), 36
Power Up the Controls and Check the Compressor
Oil Heater, 54
Oil Control, Shaft Seal, 33
Oil Cooler, 36
Oil Cooling Cycle, 8
Oil Differential Pressure/Power Supply Module, 16
Oil Differential Pressure/Power Supply Module
Calibration (Checking Pressure Transducers), 85
Oil Filter,
Pre-Start Checks,
External Gear, 51
Motor, 51
Preliminary Alignment (Chiller Alignment), 71
Preparation (Initial Start-Up), 57
Preparation (Pumpout and Refrigerant Transfer
Procedures), 63
Compressor (Changing the Oil Filters), 76
External Gear (Changing the Oil Filters), 77
Oil Filters, Changing the, 76
Oil Heater Contactor (IC), 16
Oil Heater, Power Up the Controls and Check the
Compressor, 54
Prepare the Chiller for Start-Up, 62
Pressure Transducers,
Check, 83
Oil Heater Voltage Selector (SI), Control and, 16
Oil Pressure and Compressor Stop, Check, 61
Oil Pump Contactors, Compressor (2C) and Gear (5C), 16
Oil Specifications, 77
Checking, 84
Pressure/Power Supply Module, Oil Differential, 16
Pressurize With Dry Nitrogen, To, 68
Prevent Accident Start-Up, To, 61
Prevention Algorithm, Surge, 37
Prevention, Condenser Freeze, 36
Processor/Sensor Input/Output (PSIO) Module
(Troubleshooting Guide), 97
Oil Sump Temperature Control, 35
Ontime, Service, 76
Open Oil Circuit Valves, 46
Operating Condition, Check Chiller, 61
Operating Instructions, 62
Operating the Optional Pumpout Compressor, 63
Operation,
Cold Weather, 63
Faulted Chiller (Lead/Lag Control), 40
Lead/Lag (Lead/Lag Control), 39
Manual Guide Vane (Operating Instructions), 63
Service, 22, 42
Processor/Sensor Input/Output Module (PSIO), 16
Processor Modules, Replacing Defective, 98
Proportional Bands and Gain, 32
Protection, Surge, 38
PSIO Module,
Installation of New, 98
Processor/Sensor Input/Output (Troubleshooting
Guide), 97
Start-Up Recycle (Ice Build Control), 40
Operation and Menus, LID, 16
Operation of the Guide Vanes, Manual, 58
Operations,
PSIO, Processor/Sensor Input/Output Module, 16
Pumpout and Refrigerant Transfer Procedures, 63
Pumpout Compressor (Optional), Check Pumpout
System Controls and, 56
Override, 18
Pumpout Compressor Oil, Motor Sleeve Bearing
and (Oil Changes), 78
Return to Non-Ice Build (Ice Build Control), 41
Operator Duties, 62
Operator, Instruct the, 62
Operator Knowledge, Check, 62
Option, Demand Limit Control (Requires Optional
8-Input Module), 37
Optional Pumpout Compressor,
Check Pumpout System Controls and, 56
Operating the, 63
Pumpout Compressor, Operating the Optional, 63
Pumpout Compressor Water Piping, Check Optional, 50
Pumpout Safety Control Settings, 83
Pumpout System (Instruct the Operator), 62
Pumpout System Controls and Optional Pumpout
Compressor, Check, 56
Pumpout System Maintenance, 83
Pumpout System, Using the Economizer/Storage
Vessel and, 45
Optional Pumpout Compressor Oil Charge, 83
Options Modules (8-Input), 98
Ordering Replacement Chiller Parts, 83
Outputs,
Ramp Loading Control, 33
Reading Refrigerant Pressures, 63
Recycle Mode, Chilled Water, 44
Red LEDs (Control Modules), 96
Refrigerant,
(4-In/2-Out Module), 98
(Processor/Sensor Input/Output Module), 97
(Starter Management Module), 97
Override, Capacity, 35
Adding, 67
Charge into Chiller, 57
Override Operations, 18
Removing, 67
Overview (Troubleshooting Guide), 83
Packaging, Remove Shipping, 45
Parameters, Input Service Equipment, If Necessary, 55
Parts, Motor Replacement, 83
Password, 54
Transferring Into the Cooler/Condenser/Compressor
Section, 67
Transferring Into the Economizer/Storage Vessel, 66
Refrigerant Charge,
Adjusting the, 67
Trimming, 57
118
Download from Www.Somanuals.com. All Manuals Search And Download.
INDEX (cont)
Refrigerant Float System, Inspect (Scheduled
Maintenance), 78
Shunt Trip (Safety Controls), 33
Shutdown,
Refrigerant Leak Testing, 67
After Extended, 63
Refrigerant Pressures, Reading, 63
Refrigerant Properties, 67
After Limited, 63
Extended, 63
Refrigerant Tracer (Test After Service, Repair, or
Major Leak), 68
Safety, 45
Shutdown Sequence, 44
Six-Pack Relay Board, 16
Sleeve Bearings (Motor Maintenance), 79
SMM,
Refrigerant Tracer, 46
Refrigerant Transfer Procedures, Pumpout and, 63
Refrigeration Cycle, 5
Refrigeration Log, 63
Starter Management Module (Troubleshooting Guide), 97
Starter Management Module, 16
Soft Stop Amps Threshold, Automatic, 44
Software Version, 54
Relay (3C) (Optional), Hot Gas Bypass Contactor, 16
Relay (4C), Oil Auxiliary, 16
Relay Board, Six-Pack, 16
Relay, Tower Fan, 36
Solid-State Starters (Check Starter), 53
Spare Alarm Contacts, 36
Spare Safety Inputs, 36
Relief Devices, Check, 50
Relief Valves and Piping, Inspect (Schedule
Maintenance), 78
Specifications, Oil, 77
Remote Start/Stop Controls, 36
Standing Vacuum Test, 49
Start-Up,
Remove Shipping Packaging, 45
Removing Refrigerant, 67
Before Initial, 45
Repair, or Major Leak, Test After Service, 67
Repair the Leak, Retest, and Apply Standing
Vacuum Test, 68
Initial, 57
Local, 43
Motor Initial, 58
Replacement Chiller Parts, Ordering, 83
Replacement Parts, External Gear, 83
Replacement Parts, Motor, 83
Prepare the Chiller for, 62
To Prevent Accidental, 61
Start-Up Checklist for 17EX Externally Geared
Centrifugal Liquid Chiller, Initial, CL-1 to CL-12
Start-Up/Recycle Operation (Ice Build Control), 40
Start-Up Sequence, Dry Run to Test, 58
Start-Up/Shutdown/Recycle Sequence, 43
Start/Stop Controls, Remote, 36
Starter Management Module (SMM) (Troubleshooting
Guide), 97
Replacement, Transducer, 85
Replacing Defective Processor Modules, 98
Required, Equipment (Before Initial Start-Up), 45
Required, Job Data (Before Initial Start-Up), 45
Reset, Water/Brine, 37
Resistance Check (Checking Temperature Sensors), 84
Return Chiller to Normal Operating Conditions, 67
Return to Non-Ice Build Operations (Ice Build Control), 41
Rotation, Check Motor, 58
Starter Management Module (SMM), 16
Starter,
Running System, Check the, 62
Check, 53
S1, Control and Oil Heater Voltage Selector, 16
Safety and Operating Controls, Check Monthly, 76
Safety Considerations, 1
Motor, 5
Starters, 9
Starters,
Safety Controls, 33
Mechanical (Check Starter), 53
Solid-State (Check Starter), 53
Starting Equipment, Inspect the (Scheduled
Maintenance), 83
Safety Devices and Procedures (Instruct the Operator), 62
Safety Inputs, Spare, 36
Safety Shutdown, 45
Schedule (OCCPC01S), Input the Local Occupied, 54
Schedule, Occupancy, 32
Starting the Chiller, 62
Stopping the Chiller, 62
Storage,
Schedule Maintenance, 76
Scheduling, Holiday (Service Operation), 42
Schematics, Physical Data and Wiring, 99
Screen Freeze, Default, 33
External Gear, 81
Motor, 81
Structure, Menu, 17
Seal Disassembly (Contact Seal Maintenance), 68
Seal Reassembly (Contact Seal Maintenance), 70
Sensor Installation, Common Point (Lead/Lag Control), 38
Sensors, Checking Temperature (Troubleshooting Guide), 84
Service Configurations, Input, 54
Service Ontime, 76
Surge Prevention Algorithm, 37
Surge Protection, 38
System Components, 5
T1-T4, Control Transformers, 16
Temperature Control During Ice Build (Ice Build
Control), 41
Service Operation, 22, 42
Temperature Control,
Service, Repair, or Major Leak, Test After, 67
Service Screen, To Access the (Service Operation), 42
Set Points, Input the Design, 54
High Discharge, 35
Oil Sump, 35
Temperature Sensors,
Set Points, To View and Change, 22
Set Up Chiller Control Configuration, 54
Settings, Pumpout Safety Control, 83
Shaft Seal Oil Control, 33
Shipping Packaging, Remove, 45
Short-Term Storage (External Gear Storage), 81
Checking (Troubleshooting Guide), 84
Dual (Checking Temperature Sensors), 84
Termination of Ice Build (Ice Build Control), 41
Test After Service, Repair, or Major Leak, 67
Test Start-Up Sequence, Dry Run to, 58
119
Download from Www.Somanuals.com. All Manuals Search And Download.
INDEX (cont)
Test,
Trimming Refrigerant Charge, 57
Control (Troubleshooting Guide), 85
Trip, Shunt (Safety Controls), 33
Troubleshooting Guide, 83
Perform and Automated Control, 56
Standing Vacuum, 49
Testing, Refrigerant Leak, 67
This Manual (Instruct the Operator), 62
Threshold, Automatic Soft Stop Amps, 44
Tighten All Gasketed Joints and Guide Vane Shaft
Packing, 46
Tightness, Check Chiller, 46
Time and Date, Input, 55
Time Schedule Operation, To View or Change, 18
Timers, Chiller, 32
Troubleshooting Transducers, 85
Tubes, Inspect the Heat Exchanger (Scheduled
Maintenance), 82
Using the Economizer/Storage Vessel and Pumpout
System, 45
Vacuum Test, Standing, 49
Valves, Open Oil Circuit, 46
Vessel, Economizer/Storage, 5
View and Change Set Points, To, 22
View or Change Time Schedule Operation, To, 18
View or Change Point Status, To, 17
Volatile Memory, 11
To Prevent Accidental Start-Up, 61
To View and Change Set Points, 22
To View or Change Point Status, 17
To View or Change Time Schedule Operation, 18
Tower Fan Relay, 36
Voltage Drop (Checking Temperature Sensors), 84
Voltage Selector (SI), Control and Oil Heater, 16
Voltage Supply, Check, 56
Tracer, Refrigerant, 46, 68
Water Leaks, 82
Water Piping,
Transducer Replacement, 85
Transducers,
Check Optional Pumpout Compressor, 50
Inspect, 50
Check Pressure, 83
Checking Pressure, 84
Water Treatment, 82
Troubleshooting, 85
Water/Brine Reset, 37
Transferring Refrigerant into the Cooler/Condenser/
Compressor Section, 67
Weekly Maintenance, 76
Wiring, Chiller Communication (Lead/Lag Control), 38
Wiring, Inspect, 50
Transferring Refrigerant into the Economizer/Storage
Vessel, 66
Wiring Schematics, Physical Data and, 99
Transformers (T1-T4), Control, 16
Copyright 1997 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 211
Catalog No. 531-721
Printed in U.S.A.
Form 17EX-1SS
Pg 120
7-97
Replaces: New
Tab 5d
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Beko Washer WM 6133 S User Manual
Belkin Computer Drive F9L1109V1 User Manual
Billy Goat Vacuum Cleaner KD 410 User Manual
Bodyline Products International Electric Shaver AX 0100 User Manual
Bosch Appliances Home Security System PLE 10M2 EU User Manual
Cables to Go Switch 89035 User Manual
Campbell Hausfeld Staple Gun IFN328K0 User Manual
Centrios DVD Recorder 1611304 User Manual
Char Broil Gas Grill 463263110 User Manual
Cisco Systems Network Card 3522 BRI User Manual