Honeywell Thermometer B User Manual

TP970 and TP9600 Series  
Pneumatic Thermostats  
SERVICE DATA  
TP973A,B and TP9630A,B  
GENERAL  
The TP973A, B and TP9630A,B are one- or two-pipe bleed-  
type thermostats for heating or cooling applications.  
The TP970 and TP9600 Series Pneumatic Thermostats are  
one-, two-, or three-pipe, proportioning thermostats with  
bimetal elements. They are suitable for controlling dampers  
and/or valves in HVAC systems.  
TP974A  
The TP974A is a pneumatic space temperature sensor for  
either one- or two-pipe applications. It is suitable as a remote  
temperature indicator or as the sensor for a receiver  
controller.  
APPLICATION  
TP970A-D and TP9600A,B  
TP978A-E  
The TP970 and TP9600 are single-temperature, pilot-bleed,  
two-pipe thermostats. The TP970A and TP9600A are used for  
heating (Direct Acting [DA]), the TP970B and the TP9600B for  
cooling (Reverse Acting [RA]), and the TP970C and D for  
heating/cooling. There are TP970A and B models with Limited  
Control Range (LCR) for energy conservation. The TP970C  
and D have a wide throttling range capability, allowing an  
adjustable Zero Energy Band (ZEB) between heating and  
cooling operations.  
The TP978 is a dual-element bleed-type thermostat used in  
dual one-pipe applications, suitable for use with variable  
volume systems. These thermostats may be used to control  
separate heating and cooling actuators in sequence, with a  
Zero Energy Band (ZEB) for energy conservation. The  
heating setpoint is limited to 73F (23C) maximum, and the  
cooling setpoint is limited to 77F (25C) minimum. Heating and  
cooling are available in both DA and RA configurations.  
Except for the TP978E, there are no upgraded replacements  
for the TP978.  
TP971A-E and TP9610A,B  
The TP971A-E and TP9610A,B are two-temperature, pilot-  
bleed, two-pipe thermostats for DAY/NITE operation, with  
automatic switchover from mainline pressure. The TP971C is  
a three-pipe thermostat for unit ventilator DAY/NITE  
application.  
TP979A-E  
The TP979 contains two cooling/heating, DAY/NITE  
thermostats. They are one- or two-temperature, two-pipe  
thermostats for independent proportioning control of heating  
and cooling.  
TP972A and TP9620A  
The TP972A and TP9620A are single-temperature, pilot-  
bleed, two-pipe thermostats with cooling/heating cycles and  
automatic switchover from mainline pressure. The  
TP972A2143 is designed specifically for replacing Johnson  
cooling/heating thermostats (see SPECIFICATIONS section).  
Contents  
General ............................................................................... 1  
Application .......................................................................... 1  
Specifications ...................................................................... 2  
Operation ............................................................................ 8  
Maintenance ....................................................................... 11  
General ............................................................................... 11  
Cleaning .............................................................................. 11  
Calibration ........................................................................... 12  
Troubleshooting .................................................................. 14  
Repair.................................................................................. 15  
Parts and Accessories ........................................................ 18  
Accessories......................................................................... 21  
® U.S. Registered Trademark  
75-7134-1  
Copyright © 1997 Honeywell Inc.  
All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 1. TP970A-D Thermostat Specifications (continued).*  
Supply Air Degrees  
Old  
New  
Pressure Throttling  
Model No.  
Model No.  
Description  
Setpoint  
psi (kPa)  
Range  
Special Features  
TP970B 1069  
TP970B 1077  
TP970B 2069  
TP970B 2077  
RA, 2-Pipe  
60-90°F  
18 (124)  
Includes 25 ft (7.6m) Twin Tubing with  
1400406-121 Cover  
Adjustable  
2-10°F  
(1.1-5.6°C)  
Convertastat Kit with Universal Window  
Cover  
TP970B 2085  
TP970B 2093  
TP970B 2101  
TP970B 2119  
TP970B 2127  
TP970B 2135  
TP970C 2000  
Quick Mount with 14004407-300 Cover  
Quick Mount with 14004407-121 Cover  
Quick Mount with 14004407-111 Cover  
Quick Mount with 14004406-300 Cover  
Quick Mount with 14004406-121 Cover  
Quick Mount with 14004406-111 Cover  
TP970C 1000  
DA, 2-Pipe  
RA, 2-Pipe  
Wide Throttle Range Allows Zero Energy  
Band (ZEB)  
Adjustable  
5-25F  
(2.8-13.9C)  
TP970C 1018  
TP970D 1008  
TP970D 1016  
No  
Universal Zero Energy Band (ZEB)  
Modernization Kit  
Replacement  
TP970D 2000  
Wide Throttle Range Allows Zero Energy  
Band (ZEB)  
No  
Universal Zero Energy Band (ZEB)  
Modernization Kit  
Replacement  
*All single-temperature, pilot bleed.  
Table 2. TP971A-E Thermostat Specifications.*  
Supply Air  
Pressure  
psi (kPa)  
Degrees  
Throttling  
Range  
Old  
Model No.  
New  
Model No.  
Description  
Setpoint  
Special Features  
TP971A 1003  
TP971A 1011  
TP971A 1029  
TP971A 1037  
TP971A 2003  
TP971A 2011  
TP971A 2029  
TP971A 2037  
DA, Heating,  
2-Pipe  
60-90°F  
13 or 18  
(90 or 124)  
Adjustable  
2-10°F  
DAY Range  
15-30°C  
DAY Range  
(1.1-5.6°C)  
60-90°F  
DAY Range  
16 or 21  
(110 or 145)  
13 or 18, 16 or  
Universal Modernization Kit  
21 (90 or 124,  
110 or 145)  
Honeywell Thermostat Modernization Kit  
with Universal Window Cover  
TP971A 1052  
TP971A 1060  
TP971A 1078  
TP971A 2052  
TP971A 2060  
15-30°C  
16 or 21  
(110 or 145)  
DAY Range  
60-90°F  
DAY Range  
Includes 14004406-901 Cover  
No  
60-90°F  
50-75°F  
13 or 18  
(90 or 124)  
Adjustable 5-  
25°F (2.8-  
Replacement  
13.9°C)  
DAY, 2-10°F  
(1.1-5.6°C) NITE  
TP971A 1086  
TP971A 1094  
TP971A 2086  
TP971A 2094  
60-90°F  
20 or 25  
Adjustable  
DAY Range  
(138 or 172)  
2-10°F  
(1.1-5.6°C)  
Includes 25 ft (7.6m) Twin Tubing and  
14004407-121 Cover  
TP971A 1102  
TP971A 2102  
13 or 18, or 16  
or 20 (90 or  
124, or 110 or  
145)  
Convertastat Kit with Universal Window  
Cover  
*All DAY/NITE, two-temperature, pilot-bleed.  
(continued)  
75-7134—1  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 2. TP971A-E Thermostat Specifications (continued).*  
Supply Air  
Pressure  
psi (kPa)  
Degrees  
Throttling  
Range  
Old  
Model No.  
New  
Model No.  
Description  
Setpoint  
Special Features  
TP971A 2110  
DA, Heating,  
2-Pipe  
60-90°F  
DAY Range  
13 or 18  
Adjustable 2-  
10°F (1.1-5.6°C)  
Quick Mount with 14004407-300 Cover  
TP971A 2128  
TP971A 2136  
TP971A 2144  
TP971A 2151  
TP971A 2169  
TP971B 2001  
TP971B 2019  
(90 or 124)  
Quick Mount with 14004407-121 Cover  
Quick Mount with 14004407-111 Cover  
Quick Mount with 14004406-300 Cover  
Quick Mount with 14004406-121 Cover  
Quick Mount with 14004406-111 Cover  
TP971B 1001  
TP971B 1019  
RA,  
Heating,  
2-Pipe  
16 or 21  
(110 or 145)  
TP971B 1027  
TP971B 1035  
TP971B 2027  
TP971B 2035  
15-30°C  
13 or 18  
(90 or 124)  
DAY Range  
60-90°F  
DAY Range  
16 or 21  
(110 or 145)  
Includes 14004406-901 Cover  
TP971B 1043  
TP971B 1050  
TP971B 2043  
TP971B 2050  
20 or 25  
(138 or 172)  
Includes 25 ft (7.6m) Twin Tubing with  
14004407-121 Cover  
TP971C 1009  
TP971C 1017  
TP971C 2009  
TP971C 2017  
DA,  
13 or 18,  
With Secondary Branch  
Heating,  
3-Pipe  
15-30°C  
DAY Range  
(90 or 124)  
TP971C 1025  
TP971C 2025  
DA,  
Cooling,  
60-90°F  
DAY Range  
16 or 21  
(110 or 145)  
TP971C 1041  
TP971D 1007  
TP971C 2041  
TP971D 2007  
3-Pipe  
20 or 25  
DA, Cooling,  
2-Pipe  
(138 or 172)  
NITE Set-Up (75 to 100F)  
TP971E 1004  
TP971E 2004  
RA, Cooling,  
2-Pipe  
13 or 18  
(90 or 124)  
*All DAY/NITE, two-temperature, pilot-bleed.  
75-7134—1  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 3. TP972A Thermostat Specifications.*  
Action  
Left Right  
Supply Air  
Pressure  
psi (kPa)  
Degrees  
Throttling  
Range  
Old  
Model No.  
New  
Model No.  
Bimetal Bimetal  
Setpoint  
60-90°F  
15-30°C  
60-90°F  
Special Features  
TP972A 1002  
TP972A 1010  
TP972A 1028  
TP972A 2002  
TP972A 2010  
TP972A 2028  
13 (Cooling) or  
18 (Heating)  
(90 or 124)  
Adjustable  
2-10°F  
R.A.  
D.A.  
(1.1-5.6°C)  
Universal Modernization Kit with Universal  
Window Cover  
TP972A 1036  
TP972A 1044  
TP972A 2036  
TP972A 2044  
60-90°F  
Energy Conservation, Separate Setpoints  
(Cooling)  
(50-75°F  
(Heating)  
Honeywell Thermostat Modernization Kit  
with Universal Window Cover  
TP972A 1051 No Replacement  
78-90°F  
(Cooling)  
60-72°F  
(Heating)  
Separately  
Adjustable  
2-10°F  
Limited Control Range (LCR)  
(1.1-5.6°C)  
TP972A 1077 No Replacement  
TP972A 1085 No Replacement  
75-90°F  
Setpoint Stop at 75F Minimum  
(Cooling)  
50-75°F  
(Heating)  
16 (Cooling) or  
21 (Heating)  
(110 or 145)  
TP972A 1093 No Replacement  
TP972A 1101 No Replacement  
TP972A 1119 No Replacement  
TP972A 1127 No Replacement  
78-90°F  
13 (Cooling) or  
18 (Heating)  
Limited Control Range (LCR)  
(Cooling)  
60-72°F  
(Heating)  
(90 or 124)  
Universal Limited Control Range (LCR)  
Modernization Kit  
78-90°F  
(Cooling)  
13 (Cooling) or  
18 (Heating)  
Limited Control Range (LCR)  
55-65°F  
(Heating)  
(90 or 124)  
Universal Limited Control Range (LCR)  
Modernization Kit  
TP972A 1143  
TP972A 1150  
TP972A 1168  
TP972A 1176  
TP972A 1184  
TP972A 2143  
TP972A 2150  
TP972A 2168  
TP972A 2176  
TP972A 2184  
D.A.  
R.A.  
D.A.  
D.A.  
R.A.  
60-90°F  
14 (Heating) or  
19 (Cooling)  
(97 or 131)  
Separately  
Adjustable  
2-10°F  
Specifically for replacing Johnson  
Cooling/Heating Thermostats  
D.A. 15-30°C Cooling 13 (Cooling) or  
(1.1-5.6°C)  
Energy Conservation, Separate Setpoints  
12-24 Heating  
18 (Heating)  
(90 or 124)  
R.A.  
R.A.  
60-90°F  
(Cooling)  
50-75°F  
16 (Cooling) or  
21 (Heating)  
110 or 145)  
(Heating)  
20 (Cooling) or  
25 (Heating)  
(138 or 172)  
13 (Cooling or  
18 (Heating)  
Includes 14004406-901 Cover, Separate  
Setpoints  
TP972A 2192  
TP972A 2200  
R.A.  
D.A.  
D.A.  
R.A.  
60-90°F  
(90 or 124)  
Includes Universal Window Cover  
14 (Cooling) or  
19 (Heating)  
(97 or 131)  
*All single-temperature, tw0-pipe, two-element, automatic changeover, and cooling/heating.  
75-7134—1  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 4. TP973A and B Thermostat Specifications.*  
Supply Air  
Pressure  
psi (kPa)  
Degrees  
Throttling  
Range  
Old  
Model No.  
New  
Model No.  
Action  
Setpoint  
Special Features  
TP973A 1068  
TP973A 2068  
DA  
60-90°F  
18 (124)  
Universal Modernization Kit with Universal  
Window Cover  
Adjustable  
2-10°F  
(1.1-5.6°C)  
TP973A 1076  
TP973A 1084  
TP973A 1092  
TP973A 2076  
TP973A 2084  
TP973A 2092  
15-30°C  
60-90°F  
Honeywell Thermostat Modernization Kit with  
Universal Window Cover  
TP973A 1100  
TP973A 1117  
TP973A 1126  
TP973A 1134  
TP973A 1142  
TP973A 1159  
TP973A 1167  
TP973A 1175  
TP973A 1183  
TP973B 1066  
TP973B 1074  
TP973B 1090  
TP973B 1108  
TP973B 1116  
TP973B 1124  
TP973B 1132  
TP973B 1140  
TP973B 1157  
TP973A 2100  
No Replacement  
No Replacement  
No Replacement  
No Replacement  
TP973A 2159  
TP973A 2167  
TP973A 2175  
TP973A 2183  
TP973B 2066  
TP973B 2074  
TP973B 2090  
TP973B 2108  
TP973B 2116  
TP973B 2124  
TP973B 2132  
TP973B 2140  
TP973B 2157  
Includes 14004406-901 Cover  
Includes 25 ft (7.6m) Twin Tubing and  
Blank Plastic Cover  
Includes 14004407-121 Cover  
Includes 14004407-300 Cover  
RA  
15-30°C  
60-90°F  
Includes 1400406-901 Cover  
15-30°C  
60-90°F  
Includes 14004407-121 Cover  
Includes 14004407-300 Cover  
Includes 25 ft (7.6m) Twin Tubing and  
14004407-121 Cover  
*All one- or two-pipe, bleed type.  
75-7134—1  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 5. TP974A, TP978A-E, TP979A-E Thermostat Specifications.  
Supply Air Degrees  
Old  
New  
Pressure Throttling  
Model No.  
Model No.  
Action  
DA, 1- or  
2-Pipe Sensor  
Bleed Type  
Setpoint  
psi (kPa)  
Range  
Special Features  
TP974A 1000  
TP974A 2000  
50-100°F  
18 (124)  
Sensor for use with  
RP908 & RP920  
Controller  
(10-38°C) 3-15 (21-103)  
Range  
Output  
TP978A 1006  
No  
DA Heating  
DA Cooling  
60-73°F  
Heating  
18 (124)  
2-10°F  
ZEB Energy  
Replacement  
(1.1-5.6°C) Conservation, Setpoint  
Stop 73°F (Heating),  
77°F (Cooling)  
TP978B 1004  
TP978C 1002  
TP978D 1000  
TP978E 1007  
No  
RA heating  
DA Cooling  
77-90°F  
Replacement  
Cooling  
No  
DA Heating  
RA Cooling  
Replacement  
No  
RA Heating  
RA Cooling  
Replacement  
TP978E 2007  
RA (Right Side)  
DA (Left Side)  
68-82°F  
60-90°F  
0.18 (1)  
18 (124)  
1-4°F  
Includes Cover  
Special System-  
Powered Thermostat  
for Carrier  
TP979A 1005  
TP979A 2005  
DA Heating  
DA Cooling  
Adjustable  
2-10°F  
(1.1-5.6°C)  
TP979B 1003  
TP979C 1001  
TP979B 2003  
TP979C 2001  
RA Heating  
RA Cooling  
DA Heating or  
Cooling  
RA Heating or  
Cooling  
TP979D 1009  
TP979E 1006  
TP979D 2009  
TP979E 2006  
DA Heating  
DA Cooling  
13 (90) Day  
18 (124) Nite  
Day/Nite Heat with  
night set down; Cool  
with night set up.  
DA Heating  
RA Cooling  
75-7134—1  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 6. TP9600 Thermostat Specifications.  
Model No.  
Description  
Setpoint Slot  
Includes Stat.  
Single Temperature, Two-Pipe:  
TP9600A 1007  
DA, Open Windows  
RA, Open Windows  
DA, Close Windows  
RA, Close Windows  
Open  
Open  
TP970A 2004  
TP970B 2002  
TP970A 2004  
TP970B 2002  
TP9600B 1006  
TP9603A 1001  
Closed  
Closed  
TP9603B 1000  
Day/Night, Two-Pipe:  
TP9610A 1006  
DA, Open Windows  
RA, Open Windows  
DA, Close Windows  
RA, Close Windows  
Open  
Open  
TP971A 2003  
TP971B 2001  
TP971A 2003  
TP971B 2001  
TP9610B 1005  
TP9613A 1000  
Closed  
Closed  
TP9613B 1009  
Heating/Cooling, Two-Pipe:  
TP9620A 1005  
DA, Open Windows  
RA, Close Windows  
Open  
TP972A 2002  
TP972B 2002  
TP9623B 1009  
Closed  
Single Temperature, One or Two-Pipe:  
TP9630A 1004  
TP9630B 1003  
TP9633A 1008  
TP9633B 1007  
DA, Open Windows  
Open  
Open  
TP973A 2076  
TP973B 2066  
TP973A 2076  
TP973B 2066  
RA, Open Windows  
DA, Close Windows  
RA, Close Windows  
Closed  
Closed  
Various ZEB ranges, heating control points, and cooling  
control points are obtained by selecting the appropriate  
thermostat setpoint, throttling range, and spring range or ratio  
relays.  
OPERATION  
TP970A,B and TP9600A,B  
When using a TP970A or TP9600A (Fig. 1) in heating  
applications with a normally open valve, a fall in temperature  
lowers Branchline Pressure (BLP) to the valve. THis lower  
BLP provides proportional valve action matching the existing  
load requirements. When a TP970B or TP9600B is used in a  
cooling application, a rise in temperature causes the TP970B  
or TP9600B to lower BLP. The energy conservation models  
limit control temperature to a maximum (heating) or minimum  
(cooling) of 72F (24C).  
15  
(100)  
14  
(90)  
(80)  
(70)  
(60)  
(50)  
(40)  
(30)  
(20)  
(10)  
0
13  
12  
11  
10  
9
8
7
6
5
4
3
TP970C MINIMUM  
THROTTLING RANGE =  
5F (2.8C)  
TP970C MAXIMUM  
THROTTLING RANGE =  
20F (11.1C)  
SETPOINT  
2.5 2.5  
2
12.5 10 7.5  
5
5
7.5  
10 12.5 15  
1
15  
TP970A,B OR  
TP9600A,B  
(8) (7) (6) (5) (4) (3) (2) (1)  
(1) (2) (3) (4) (5) (6) (7) (8)  
ABOVE SETPOINT  
M B  
SETPOINT  
BELOW SETPOINT  
M
DEVIATION IN SPACE TEMPERATURE—DEGREES F (C)  
C3536  
Fig. 2. TP970C Space Temperature vs. Branchline  
Pressure.  
N.O.  
SUPPLY  
C3535-1  
Fig. 1. TP970A,B and TP9600A,B Typical Operation.  
TP970C and D  
The TP970C and D with wide throttling range (Fig. 2 and 3)  
allow use of heating and cooling valve assemblies with either  
selected spring ranges (Fig. 4) or ratio relays (Fig. 5) to  
achieve a ZEB range.  
75-7134—1  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
15  
14  
13  
12  
11  
10  
9
8
7
6
5
TP971A, B, D, E and TP9610A,B  
(100)  
(90)  
(80)  
(70)  
(60)  
(50)  
(40)  
(30)  
(20)  
(10)  
0
These thermostats provide a BLP proportional to the ambient  
temperature. In a heating application with a normally open  
valve (Fig. 6), a fall in room temperature causes the  
thermostat to lower the BLP to the valve, providing a  
proportional action matching the existing load requirement.  
When the supply air pressure is 13 psi (90 kPa), the  
thermostat controls at the normal DAY setting. When the  
supply air is switched to 18 psi (124 kPa), the thermostat  
controls at the reduced NITE setting. Models with 16 or 21 psi  
(110 or 145 kPa) pressure are available. The TP971D is the  
same as the TP971A with the addition of NITE setup. The  
TP971E is the same as the TP971B with the addition of NITE  
setup.  
TP970D MINIMUM  
THROTTLING RANGE =  
5F (2.8C)  
TP970D MAXIMUM  
THROTTLING  
RANGE = 20F (11.1C)  
4
3
SETPOINT  
2.5 2.5  
2
1
12.5 10 7.5  
5
5
7.5  
10 12.5 15  
15  
(8) (7) (6) (5) (4) (3) (2) (1)  
(1) (2) (3) (4) (5) (6) (7) (8)  
SETPOINT  
ABOVE SETPOINT  
BELOW SETPOINT  
DEVIATION IN SPACE TEMPERATURE—DEGREES F (C)  
C3537  
Fig. 3. TP970D Space Temperature Vs Branchline  
Pressure.  
The manual reset lever protrudes through the DAY/AUTO slot  
in the cover. The lever is used to manually reset the  
thermostat from AUTO to DAY to restore day operation. The  
lever automatically returns to the AUTO position when the  
supply air reaches DAY pressure.  
TP970C  
DIRECT  
ACTING  
M B  
M
HEATING  
VALVE  
2 TO 5 PSI  
(14 TO 34 kPa)  
SPRING  
COOLING  
VALVE  
9 TO 13 PSI  
(62 TO 90 kPa)  
SPRING  
TP971A OR  
TP9610A  
DAY  
13 PSI  
(90 kPa)  
M B  
N.O.  
N.C.  
M
NITE  
18 PSI  
(124 kPa)  
VALVE  
OPEN  
N.O.  
4 DEGREES F  
(2.2 DEGREES C)  
ZERO  
HOT WATER  
OR STEAM  
SUPPLY  
C3540-1  
ENERGY  
BAND  
VALVE  
CLOSED  
Fig. 6. TP971A and TP9610A Typical Operation.  
66F  
68F  
20C  
70F  
72F  
22C  
74F  
76F  
24C  
78F  
TP971C  
THERMOSTAT SETTING  
TR=10 DEGREES F  
(5.6 DEGREES C)  
The TP971C can be used with a unit ventilator to control a  
heating valve, outdoor- and return-air dampers, and blower  
motor (Fig. 7). When supply air pressure is 13 psi (90 kPa),  
the TP971C controls the valve and damper at the normal DAY  
setpoint. When supply air pressure is 18 psi (125 kPa), the  
TP971C closes the outdoor-air damper and switches the  
blower from constant to automatic operation. The TP971C  
then cycles the unit at reduced night setpoint. Models with 18  
or 21 psi (125 or 145 kPa) pressure are available.  
C3538  
Fig. 4. Typical TP970C Operation Using Selected Spring  
Range Valve Operators.  
TP970C  
DIRECT  
ACTING  
M B  
M
RP971A—3 PSI  
RANGE—SET  
10 PSI (68.9 kPa)  
START  
RP971A—3 PSI  
SPAN—SET  
3.9 PSI (26.9 kPa)  
START  
The manual reset lever protrudes through the DAY/AUTO slot  
in the cover. The lever may be used to manually reset the  
TP971C from AUTO to DAY to restore DAY operation,  
including outdoor-air damper operation. The reset lever  
automatically returns to the AUTO position when the supply  
air reaches DAY pressure.  
2
1
4
2
1
4
3
3
EXH  
EXH  
M
M
HEATING  
VALVE  
3 TO 10 PSI  
(21 TO 68.9 kPa)  
COOLING  
VALVE  
N.O.  
N.C.  
3 TO 10 PSI  
(21 TO 68.9 kPa)  
VALVE  
OPEN  
4 DEGREES F  
(2.2 DEGREES C)  
ZERO  
ENERGY  
BAND  
VALVE  
CLOSED  
66F  
68F  
20C  
70F  
72F  
22C  
74F  
76F  
24C  
78F  
THERMOSTAT SETTING  
TR=10 DEGREES F  
(5.6 DEGREES C)  
C3539  
Fig. 5. Typical TP970C Operation Using Ratio Relays.  
75-7134—1  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
DISCHARGE AIR  
TP973A OR  
TP9630A  
AIR  
STREAM  
STAT  
M
N.O.  
HOT WATER OR  
STEAM SUPPLY  
VALVE  
C3543-1  
HEATING  
COIL  
Fig. 9. TP973A and TP9630A Typical Operation, One-Pipe  
Using External Restriction.  
H
120V AC  
50/60 HZ  
P638  
TP971  
G
FAN  
TP974A  
MSB  
K
H
The TP974A Sensor (Fig. 10) provides a pneumatic output  
signal of 3 to 15 psi (21 to 103 kPa) in direct relation to the  
sensed temperature, allowing direct and remote readout of  
the temperature. An RP908 or RP920 Controller is used with  
the TP974A to convert the output into a usable signal to  
operate a pneumatic valve, damper, or other equipment.  
MP516C  
D/N  
D/N  
2
1
HI  
M
LO  
13/18 PSI  
(90/124 kPa)  
FILTER  
OUTDOOR  
AIR  
RETURN  
AIR  
RP920  
4
8
9
N.C.  
N.O.  
C3541  
2
3
1
Fig. 7. TP971C Typical Operation.  
M
VALVE  
TP972A and TP9620A  
TEMP  
GAGE  
M
B
The standard TP972Aand TP9620A is RA for cooling and DA  
for heating. A rise in temperature at the TP972Aand TP9620A  
with main air pressure at 13 psi (90 kPa) causes the  
TP972Aand TP9620A to lower BLP, opening the valve to  
control the temperature with chilled water. A fall in  
temperature at the TP972Aand TP9620A with main air  
pressure at 18 psi (124 kPa) causes the TP972Aand  
TP9620A to lower BLP, opening the valve to control the  
temperature with hot water (Fig. 8).  
C3544A  
TP974  
Fig. 10. TP974 Typical Operation.  
TP978E  
NOTE: To vary the ZEB between heating and cooling  
operation, adjust the setpoints on the TP978E.  
TP972A OR  
13 PSI  
TP9620A  
(90 kPa) RA  
M B  
A fall in temperature within the cooling range at the TP978E  
causes the TP978E to increase the BLP of the cooling  
element. This action proportionally closes the normally open  
cooling valve (Fig. 11) to maintain the temperature set on the  
high range portion of the TP978E. The normally open heating  
valve is held closed by the high BLP on the DA side of the  
TP978E.  
S/W  
18 PSI  
(124 kPa)  
DA  
N.O.  
HOT WATER/CHILLED  
WATER SUPPLY  
C3542-1  
Fig. 8. TP972A and TP9620A Typical Operation with a  
Normally Open Water Valve Assembly.  
A continued fall in temperature, into the heating range at the  
TP978E, lowers the BLP of the heating element. This action  
proportionally opens the normally open heating valve to  
maintain the temperature set on the low range portion of the  
Models are available that limit the cooling setpoint to a  
minimum of 75 or 78F, the heating setpoint to a maximum of  
72 or 75F. They work with 13/18, 16/21, 25/20, 19/14, or 20/  
25 psi changeover. Some models are DA for both cooling and  
heating.  
TP978E.  
TP978E  
H C  
DA  
RA  
TP973A,B and TP9630A,B  
EXTERNAL  
RESTRICTORS  
0.005  
N.O.  
N.O.  
A fall in temperature at the TP973A or TP9630A causes the  
TP973A or TP9630A to lower BLP, providing proportional  
control of existing load requirements for heating (Fig. 9). A  
rise in temperature at the TP973B or TP9630B causes the  
TP973B or TP9630B to lower BLP, providing proportional  
control of existing load requirements for cooling.  
COOLING  
VALVE  
HEATING  
VALVE  
M
C3545  
Fig. 11. TP978A Typical Operation.  
75-7134—1  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
TP979A-E  
MAINTENANCE  
The TP979 thermostats provide independent control of  
heating and cooling with dual thermostats and separate  
setpoints and branch lines. This enables ZEB operation  
without selected actuator springs or ratio relays (Fig. 12).  
TP979C  
General  
See Figure 14 for tools necessary to calibrate TP970 and  
TP9600 Series thermostats.  
DA  
RA  
H C  
COOLING VALVE  
PNEUMATIC  
OPERATOR WITH  
4 TO 11 PSI  
(28 to 76 kPa)  
SPRING RANGE  
HEATING VALVE  
PNEUMATIC  
OPERATOR WITH  
4 TO 11 PSI  
(28 to 76 kPa)  
SPRING RANGE  
N.O.  
N.O.  
M
THERMOSTAT TOOL  
VALVE OPEN  
ZERO  
ENERGY  
BAND  
VALVE CLOSED  
72F  
64F  
66F  
68F  
20C  
70F  
74F  
76F  
78F  
120  
140  
100  
160  
TEST THERMOMETER  
80  
60  
40  
20  
180  
200  
220  
18C  
22C  
24C  
26C  
HEATING  
SETPOINT  
COOLING  
SETPOINT  
0
C3546  
20  
25  
15  
Fig. 12. TP979 Typical Operation.  
10  
30  
The TP979D and E models provide automatic night setback  
of setpoint for heating and setup for cooling. Figure 13 shows  
potential energy savings with night setback operation.  
5
0
GAGE PORT NEEDLE  
VALVE OPEN  
GAGE  
NIGHT SETBACK  
ENERGY SAVINGS  
VALVE CLOSED  
60F  
62F  
64F  
66F  
68F  
20C  
70F  
DIGITAL RELATIVE  
HUMIDITY INDICATOR PEN  
16C  
18C  
22C  
6 DEGREES F  
(3.3 DEGREES C)  
NIGHT SETBACK  
C3929  
NIGHT  
DAY  
HEATING  
SETPOINT  
COOLING  
SETPOINT  
C3547  
Fig. 14. TP970 and TP9600 Series Thermostat  
Calibration Tools.  
Fig. 13. Night Setback Operation, TP979.  
Covers  
Cleaning  
Both metal and plastic covers are available offering a wide  
selection of windows. See Tables 11 and 12 in the  
ACCESSORIES section for more information.  
Remove the thermostat cover and clean or dust the  
thermostat using a soft brush or air hose. In extremely dirty or  
dusty environments, clean the thermostats more frequently.  
DO NOT use a high pressure air hose to remove dust. Use  
only a soft brush to clean the throttling plate nozzle assembly.  
No lubrication is necessary.  
75-7134—1  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
3. Turn the calibration screw in the opposite direction until  
the gage reads 8 ±1 psi (55 ±7 kPa).  
Calibration  
4. The TP970 and TP9600 are now calibrated. The  
setpoint indicator and thermometer should be within 1  
degree F (0.56 degree C) of each other.  
5. Remove the gage and gage adaptor and replace the  
cover.  
6. Turn the setpoint indicator adjustment until the setpoint  
indicator is at the desired setting.  
NOTES:  
1. The antihum spring (Fig. 15) must be free. Be sure the  
spring just touches the throttling plate and is not  
wedged against it (does not apply to all TP970C and D  
or any TP970 series starting with 2000, i.e.,  
TP972A2143 and TP9600 series).  
2. The thermostats are very sensitive and should not be  
heated by excessive handling during calibration.  
3. Calibration of the TP974 is not recommended.  
4. To check calibration or to recalibrate the Limited Control  
Range (LCR) thermostats, the space temperature must  
be 78F (26C) or above for cooling applications, and 72  
or 68F (22 or 20C) or below for heating applications,  
depending on the model. TP972A1119 and  
THROTTLING RANGE  
SCALE (2)  
GAGE TAP  
(DAY/SUMMER)  
ANTIHUM  
SPRING (2)  
THROTTLING  
PLATE (2)  
THROTTLING  
RANGE  
ADJUSTMENT (2)  
(NITE/WINTER)  
THERMOMETER  
CALIBRATION  
BOBBIN  
TP972A1127 are 68F (20C). The setpoint limitation is  
nonadjustable.  
5. To check calibration or to recalibrate the TP978 ZEB  
thermostats, measure actual room temperature with a  
test thermometer. The 75F (24C) limit is nonadjustable.  
SCALEPLATE  
TEMPERATURE  
INDICATOR  
SETPOINT  
INDICATOR  
60  
70  
80  
90  
SETPOINT  
INDICATOR  
(NITE/WINTER)  
CALIBRATION  
SCREW  
(DAY/SUMMER)  
Calibration Check  
SETPOINT DIAL  
(NITE/WINTER)  
STOPS  
TEMPERATURE  
SETTING  
1. Turn the setpoint indicator adjustment down (DA) or up  
(RA) until the setpoint indicator reads 5 degrees F (2.8  
degrees C) below (DA) or above (RA) room  
temperature. The BLP at the thermostat should build up  
within 30 seconds.  
2. Turn the setpoint indicator adjustment up (DA) or down  
(RA) slowly. The thermostat should begin to bleed off  
audibly between 1 and 3 degrees F (0.56 and 1.7  
degrees C) below (DA) or above (RA) room  
temperature.  
SETPOINT INDICATOR  
ADJUSTMENT  
DAY/AUTO LEVER  
(TP971 ONLY)  
C3946-3  
NOTE: NOT ALL ADJUSTMENTS ARE ON ALL THERMOSTATS.  
Fig. 15. Thermostat Front View, Cover Off, Showing  
Controls and Indicators.  
TP970C and D  
Thermometers  
1. Set the throttling range to value specified on the job  
drawing.  
1. Measure the ambient temperature with an accurate  
thermometer. Compare the thermometer reading with  
the thermostat thermometer reading.  
2. If the difference is more than 1 degree F (0.56 degree  
C), use the Thermometer Calibration Tool MQT970 to  
twist the thermostat thermometer calibration bobbin  
(Fig. 15) until the thermostat thermometer reading is  
correct.  
2. Check the mechanical throttling range by turning the  
setpoint indicator adjustment to determine the  
difference in setpoint indicator readings when BLP  
reads 3 psi (21 kPa) and 13 psi (90 kPa). It may be  
necessary to turn the calibration screw to obtain this  
measurement.  
3. Reset the throttling range to within ±2 degrees F (±1.1  
degrees C) of the specified throttling range for accurate  
control. If either the throttling range adjustment or  
calibration screw were changed, recalibrate the  
thermostat.  
Calibration Set-Up (For All Thermostats)  
4. See TP970A and B, beginning at Step 1, for the  
balance of TP970C and D calibration.  
1. Start with the main air pressure at the recommended  
setting.  
2. Remove the thermostat cover.  
3. All thermostats except the TP978E: Install Gage  
305965 (0 to 30 psi [0 to 207 kPa]) with Gage Adapter  
315161A (Fig. 14) into the branchline pressure gage  
tap (except TP978E).  
TP978E: Install a 0 to 30 psi (0 to 207 kPa) gage in the  
branchline remote from the TP978E.  
4. Turn the setpoint indicator adjustment until the setpoint  
indicator reads the existing temperature.  
TP971A-E and TP971A,B  
1. With 13 psi (90 kPa) main air pressure, turn the DAY  
(SUMMER) (left) calibration screw (Fig. 15) until the  
gage reads 0 psi (0 kPa).  
2. Turn the calibration screw in the opposite direction until  
the gage reads 8 ±1 psi (55 ±7 kPa).  
3. With 18 psi (124 kPa) main air pressure, rotate the  
NITE (WINTER) setpoint dial until the setting agrees  
with the indicated temperature.  
TP970A,B and TP9600A,B  
4. Repeat Steps 1 and 2 using the NITE (WINTER) (right)  
calibration screw (Fig. 15). The TP971 is now  
calibrated.  
1. Set throttling range to value specified on the job  
drawing.  
5. Remove the gage and replace the cover.  
2. Turn the calibration screw (Fig. 15) until the gage reads  
0 psi (0 kPa).  
75-7134—1  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
TP972A and TP9620A  
Switchover Calibration  
1. With 13 psi (90 kPa) main air pressure, turn the DAY  
(SUMMER) (left) calibration screw (Fig. 15) until the  
gage reads 0 psi (0 kPa).  
Switchover allows for normal supply line fluctuations.  
TP971A-E and TP9610A,B  
2. Turn the calibration screw in the opposite direction until  
the gage reads 8 ±1 psi (55 ±7 kPa).  
3. With 18 psi (124 kPa) main air pressure, repeat Steps 1  
and 2 using the NITE (WINTER) (right) calibration  
screw (Fig. 15). The TP972 and TP9620 are now  
calibrated.  
1. Ensure that main line pressure is set to low (13 psi)  
pressure requirement.  
2. Turn the setpoint indicator adjustment until the setpoint  
indicator reads 5 degrees F (2.8 degrees C) below  
actual temperature.  
3. BLP gage should read 0 psi (0 kPa) (RA) or 13 psi (90  
kPa) (DA). If it does not, turn switchover adjustment  
screw (Fig. 16) clockwise until it does.  
4. Remove the gage and replace the cover.  
4. Turn the switchover adjustment screw counterclockwise  
until the pressure begins to increase (RA) or decrease  
(DA). This indicates switchover. Allow the gage to go to  
full line pressure (RA) or 0 psi (0 kPa) (DA).  
5. Turn the switchover adjustment screw counterclockwise  
until pressure decreases to 0 psi (0 kPa) (RA) or  
increases to full main line pressure (DA). Turn the  
switchover adjustment screw an additional 1/8 to 1/4  
turn clockwise. Switchover is calibrated.  
TP973A,B and TP9630A,B  
If the TP973A, B and TP9630A,B are not properly calibrated  
but the remainder of the system is operating properly, turn the  
calibration screw until the TP973A, B or TP9630A,B performs  
as in Step 2 under CALIBRATION CHECK.  
TP974A  
TP972A and TP9620A (Cooling, RA;  
Field calibration of the TP974A is not recommended.  
Heating, DA)  
1. Ensure that main line pressure is set to low (13 psi)  
pressure requirement.  
TP978A-E  
2. Turn the setpoint indicator adjustment until the setpoint  
indicator reads 5 degrees F (2.8 degrees C) below  
actual temperature.  
3. BLP gage should read 0 psi (0 kPa). If it does not, turn  
the switchover adjustment screw (Fig. 16) clockwise  
until it does.  
If a TP978 thermostat is not properly calibrated but the  
remainder of the system is operating properly, turn the  
calibration screw until the thermostat performs as in Step 2  
under CALIBRATION CHECK.  
TP979A-C  
4. Turn the switchover adjustment screw counterclockwise  
until the pressure begins to increase. This indicates  
switchover. Allow the gage to go to full main line  
pressure.  
1. Turn the calibration screw (Fig. 15) until the gage reads  
0 psi (0 kPa).  
5. Turn the switchover adjustment screw counterclockwise  
until pressure decreases to 0 psi (switchover point).  
Turn the switchover adjustment screw an additional 1/8  
to 1/4 turn clockwise. Switchover is calibrated.  
2. Turn the calibration screw in the opposite direction until  
the gage reads 8 ±1 psi (55 ±7 kPa).  
3. The thermostat is now calibrated. The setpoint indicator  
and thermometer should be within 1 degree F (0.56  
degree C) of each other.  
4. Remove the gage and gage adaptor and replace the  
cover.  
5. Turn the setpoint indicator adjustment until the setpoint  
indicator is at the desired setting.  
TP979D and E  
BACK PLATE  
SCREWS (4)  
1. With 13 psi (90 kPa) main line pressure, turn the DAY  
(SUMMER) (left) calibration screw (Fig. 15) until the  
gage reads 0 psi (0 kPa).  
2. Turn the calibration screw in the opposite direction until  
the gage reads 8 ±1 psi (55 ±7 kPa).  
3. With 18 psi (124 kPa) main air pressure, rotate the  
night setpoint dial until the setting agrees with the  
indicated temperature.  
B
M
THERMOSTAT  
MULTISTAGE  
FILTER  
P
SWITCHOVER  
ADJUSTMENT  
SCREW  
4. Repeat Steps 1 and 2 using the NITE (WINTER) (right)  
calibration screw (Fig. 15). The thermostat is now  
calibrated.  
5. Remove the gage and replace cover.  
DAY/AUTO  
LEVER  
M12211  
Fig. 16. Back View of Thermostat Showing Switchover  
Adjustment Screw and DAY/AUTO Lever.  
75-7134—1  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
TROUBLESHOOTING  
See Table 7 for troubleshooting procedures.  
Table 7. TP970 Series Thermostat Troubleshooting Procedures.  
Possible Cause Solution*  
Problem  
Excessive noise  
If there is an antihum spring, it is not  
touching the throttling plate.  
Reposition spring to touch throttling plate.  
Stick an adhesive paper dot on the throttling  
plate across the hinge between the two rivets  
so that the dot is directly below the “A” in MAX  
printed on the bimetal.  
If there is no antihum spring or cone,  
Stick an adhesive paper dot on the throttling  
the adhesive paper dot has fallen off of plate as described above.  
the throttling plate.  
Air leak in restrictor block and filter  
assembly.  
Use a bubble solution to locate the leak and  
repair it.  
Replace the restrictor block assembly and  
filter.  
Install Stiffener Plate 14004609-001 on the  
backplate.  
Oil or moisture in lines.  
Replace the restrictor block assembly and  
filter. Also ensure that the air supply to the  
thermostat is dry and clean.  
Slow response  
Inadequate air flow caused by a  
partially clogged restrictor block  
assembly and/or filter cartridge.  
Replace restrictor block assembly and/or  
filter.  
Thermostat instability  
Inaccurate readings  
System gain is too high.  
Move throttling range adjustment toward MAX  
position and then recalibrate.  
Inaccurate calibration.  
Recalibrate thermostat.  
Turn setscrews in.  
Metal cover setscrews over-tightened.  
Backplate over-tightened.  
Install Stiffener Plate 14004609-001 on the  
backplate.  
Thermostat not switching  
over at changeover pressure  
Pressure at thermostat is incorrect.  
Readjust compressed airline to proper  
switching pressure.  
Switchover pressure in thermostat is  
incorrectly calibrated.  
Turn switchover adjustment screw to  
recalibrate pressure for proper switching.  
Air leak  
Branch line plug leaking.  
Oil or moisture in lines.  
Install Plug 14002172.  
Cannot calibrate thermostat  
Replace the restrictor block assembly and  
filter. Also ensure that the air supply to the  
thermostat is dry and clean.  
*If these solutions fail, replace the thermostat.  
75-7134—1  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Setpoint Indicator Adjustment Replacement  
REPAIR  
NOTE: Dual temperature thermostats require removal of  
only one of the bimetal assemblies.  
Thermometer Replacement  
NOTE: The following procedure requires a 1/4-in. (6 mm)  
nut driver and a small screwdriver.  
1. Remove the setpoint indicator (Fig. 17) by prying it off  
the indicator post with a small screwdriver.  
2. Remove the thermometer bimetal (Fig. 17) by lifting the  
plate to which the scaleplate is attached, at the hex of  
the bimetal mounting post.  
1. Insert the blade of a small screwdriver under the  
bimetal (Fig. 17) and pry up. Older style thermostats  
have a locking ring. Insert the blade between the ring  
and white nylon bushing and pry the ring from the  
thermometer bimetal mounting post.  
2. Remove the bimetal and bushing by lifting the top of the  
plate to which the scaleplate is attached, near the hex  
of the bimetal mounting post.  
3. Bend the scaleplate locking tabs (Fig. 17) up and  
compress the scaleplate mounting posts (Fig. 17)  
together with the thumb and forefinger to free the  
scaleplate from the holding notches in the post.  
4. Remove and replace setpoint indicator adjustment (Fig.  
17), using caution not to damage or distort the bimetal  
sensing element(s). On models with DAY-NITE  
temperature setpoint wheel (located under the right  
sensing element), see the NOZZLE, THROTTLING  
PLATE, and BIMETAL ASSEMBLY REPLACEMENT  
section for removal of the bimetal and DAY-NITE scale  
prior to removing the setpoint indicator adjustment.  
5. Reassemble in reverse order and recalibrate if  
required. It is not necessary to re-engage the scaleplate  
locking tabs (Fig. 17) in the holding notches of the  
scaleplate mounting posts, as they are primarily for  
shipping purposes.  
CAUTION  
The new bimetal can be easily distorted if extreme  
care is not used when handling it.  
3. Press the new bimetal and bushing into the  
thermometer post using a 1/4-in. (6 mm) nut driver over  
the bobbin. Allow the bimetal to cool down to the  
ambient temperature after handling. Slowly rotate the  
bushing until the thermometer pointer is aligned with  
the existing ambient temperature on the scaleplate.  
Nozzle, Throttling Plate and Bimetal  
Assembly Replacement  
ANTIHUM  
SPRING/CONE  
1
1. Remove cover.  
2. Remove the thermometer bimetal, temperature  
indicator, and scaleplate as previously described, if  
applicable.  
BIMETAL  
3. Unscrew center holding screw (TP978) or thermometer  
mounting post using Thermostat Tool CCT735A  
(MQT735A).  
4. Remove the Phillips head screw and the defective  
assembly (Fig. 18).  
5. Replace with new assembly being sure the rubber O-  
ring, if used, is properly aligned around the nozzle  
opening in the recess on the bottom of the aluminum  
block.  
SETPOINT  
INDICATOR  
SCALEPLATE  
MOUNTING POSTS  
6. Insert spring cone (if used) into new assembly from the  
bottom.  
7. Reassemble the thermostat.  
SCALEPLATE  
LOCKING TABS  
8. Check that the antihum spring or cone (if used) is  
properly positioned so that the spring just touches the  
throttling plate and the base of the spring (larger end) is  
seated properly in the recess of the spring mounting  
hole (Fig. 17).  
SETPOINT INDICATOR  
ADJUSTMENT  
1
IF THERE IS NO ANTIHUM SPRING/CONE, THERE IS AN  
ADHESIVE PAPER DOT ON THE THROTTLING PLATE.  
M11384  
9. Calibrate the thermostat.  
Fig. 17. Internal View of Thermostat.  
75-7134—1  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
NOZZLE, THROTTLING PLATE  
SCREW  
AND BIMETAL ASSEMBLY  
SCREW  
TYPICAL POST  
SETPOINT CAM  
ASSEMBLY  
TYPICAL  
PNEUMATIC  
ASSEMBLY  
SCREW  
SPRING  
O-RING  
BOTTOM VIEW OF  
BIMETAL ASSEMBLY  
NOZZLE,  
1
THROTTLING  
PLATE AND  
BIMETAL  
ANTIHUM  
SPRING  
OR CONE  
IF THERE IS NO ANTIHUM SPRING/CONE, THERE IS AN  
ADHESIVE PAPER DOT ON THE THROTTLING PLATE.  
1
ASSEMBLY  
M12208  
Fig. 18. Nozzle, Throttling Plate, Bimetal Assembly Replacement.  
Restrictor Block and Filter Replacement  
CAUTION  
When replacing these parts, use extreme caution to  
prevent dirt, dust, or chips from entering various  
chambers and openings of the thermostat.  
1. Remove the four Phillips head screws which fasten the  
restrictor block and filter (Fig. 19) to the back of the  
thermostat.  
2. Carefully remove the restrictor block assembly (plate,  
restrictor, filter, gasket[s]).  
3. Replace the restrictor block and filter.  
a. Align the appropriate gasket over the  
corresponding holes in the thermostat.  
b. Insert the filter into the gasket until it bottoms.  
c. Position the restrictor block.  
TYPICAL  
PNEUMATIC  
ASSEMBLY  
GASKET  
FILTER  
d. Align the other gasket on the restrictor block.  
e. Position the plate.  
f. Replace screws and tighten.  
RESTRICTOR  
GASKET  
PLATE  
SCREW  
M12206  
Fig. 19. Restrictor Block and Filter Replacement.  
75-7134—1  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Day/Auto Lever Assembly Replacement  
Switchover Adjustment Spring Replacement  
1. Remove the three Phillips head screws that fasten the  
lever mechanism to the back of the thermostat (Fig.  
20).  
2. Lift off the cover plate and remove the lever (with  
attached seal).  
1. Using a screwdriver, carefully remove the screw and  
switchover adjustment spring (Fig. 21). See PARTS  
LIST in PARTS and ACCESSORIES section for  
available springs.  
2. Replace the spring, then carefully position and replace  
the screw.  
3. Lift the spring from the post.  
4. Install the replacement parts in reverse order.  
5. Replace and tighten screws.  
3. Calibrate the thermostat.  
14001992-001  
16/21 PSI  
CHANGEOVER  
SPRING  
SPRING  
LEVER  
SCREW  
COVER  
PLATE  
M12137  
CAUTION:  
Fig. 21. Switchover Adjustment Spring Replacement.  
THIS PIN IS FREE  
TO DROP OUT WHEN  
LEVER IS RELEASED.  
M12205  
Fig. 20. DAY/AUTO Lever Assembly Replacement.  
75-7134—1  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
1A  
PARTS AND ACCESSORIES  
Parts List  
1B  
1C  
1
TP970-TP974 and TP9600-TP9630  
6
1
1D  
See Figures 22 and 23, and Table 8 for TP970-TP974 and  
TP9600-TP9630 Thermostat repair parts and assemblies.  
2
7
2
1A  
3
1B  
4
8
1
1C  
1D  
1
9
2
5
7
10  
*
1
1
8
6
10B  
10A  
10E  
1
2
9
6
10C  
10D  
10F  
10  
11  
12  
BOTTOM VIEW  
*
OF 10  
10  
12  
10B  
10C  
10D  
1
2
REPLACE THE SETPOINT CAM ASSEMBLY AND NOZZLE,  
THROTTLING PLATE, AND BIMETAL ASSEMBLY TOGETHER.  
IF THERE IS NO ANTIHUM SPRING/CONE, THERE IS AN  
ADHESIVE PAPER DOT ON THE THROTTLING PLATE.  
M12210  
1
2
REPLACE THE SETPOINT CAM ASSEMBLY  
AND NOZZLE, THROTTLING PLATE, AND  
BIMETAL ASSEMBLY TOGETHER.  
Fig. 23. Dual Element Thermostat Exploded View  
Showing Repair Parts and Assemblies.  
IF THERE IS NO ANTIHUM SPRING/CONE,  
THERE IS AN ADHESIVE PAPER DOT ON  
11  
M12209  
THE THROTTLING PLATE.  
Fig. 22. Single Element Thermostat Exploded View  
Showing Repair Parts and Assemblies.  
75-7134—1  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 8. TP970-TP974 and TP9600-TP9630 Thermostat Repair Parts and Assemblies.  
Part No. Description  
Key  
No.  
1
14004459-001 Scaleplate Bag Assembly (60 to 90F) - TP970A-D, TP973A, B  
14004459-002 Scaleplate Bag Assembly (40 to 70F) - TP970A-D  
14004459-003 Scaleplate Bag Assembly (15 to 30C) - TP970A-D, TP973A, B  
14004459-004 Scaleplate Bag Assembly (60 to 90F) - TP971A-E  
14004459-005 Scaleplate Bag Assembly (15 to 30C) - TP971A-C  
1A  
1B  
1C  
1D  
2
Pointer  
Thermostat Assembly  
Scaleplate  
Thermostat Mounting Post  
Retainer Ring (Fig. 23)  
Washer (Fig. 24)  
Scaleplate  
2
3
4
Post, Thermostat Assembly  
Bushing - TP973  
5
*
14004447-001 Setpoint Cam Assembly - TP970A1004, A1012, A1020, A1038, A1046, A1053, A1095, A2004,  
A2012, A2020, A2038, A2053, A2095; TP970C; TP972A1143, A2143; TP973A1001, A1019,  
A1127  
14004447-002 Setpoint Cam Assembly - TP970B1002, B1010, B1028, B1036, B2002, B2010, B2028, B2036;  
TP970D; TP972A1002, A1010, A1028, A1044, A2002, A2010, A2028, A2044; TP973B1009,  
B1017, B1025, B1108  
14004447-003 Setpoint Cam Assembly - TP971A, C, D; TP972A1168, A2168, A2176  
14004447-004 Setpoint Cam Assembly - TP971B, E; TP972A1036, A1077, A1085, A1150, A1184, A2036,  
A2150  
14004447-005 Setpoint Cam Assembly - TP970B1044; TP972A1051, A1101  
14004447-006 Setpoint Cam Assembly - TP970A1061, A1087, A2087  
14004447-007 Setpoint Cam Assembly - TP972A1093, A1127  
14004447-008 Setpoint Cam Assembly - TP972A 1119  
14004429-001 Setpoint Cam - TP973A1035, A1043, A1050, A1068, A1076, A1084, A1092, A1100, A2068,  
A2076, A2084, A2092, A2100  
14004429-002 Setpoint Cam - TP973B1033, B1041, B1058, B1066, B1074, B1090, B2066, B2074, B2090  
7
Screw, No. 4-3/16 pan head  
8*  
14004460-001 Nozzle, Throttling Plate, Bimetal Assembly, DA, Left Side - TP970A; TP971A, C, D; TP972A;  
TP973A  
14004460-002 Nozzle, Throttling Plate, Bimetal Assembly, RA Left Side - TP970B; TP971B, E; TP972A;  
TP973B  
14004460-003 Nozzle, Throttling Plate, Bimetal Assembly, DA, Right Side - TP971A, C; TP972A  
14004460-004 Nozzle, Throttling Plate, Bimetal Assembly, DA - TP970C  
14004460-005 Nozzle, Throttling Plate, Bimetal Assembly, RA - TP970D  
14004460-006 Nozzle, Throttling Plate, Bimetal Assembly, DA, Right Side - TP971D  
14004460-007 Nozzle, Throttling Plate, Bimetal Assembly, RA, Right Side - TP971E  
9†  
Antihum Spring/Cone  
*Replace the Setpoint Cam Assembly and Nozzle, Throttling Plate, Bimetal Assembly together.  
†If there is no antihum spring or cone, there is an adhesive paper dot on the throttling plate.  
(continued)  
75-7134—1  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 8. TP970-TP974 and TP9600-TP9630 Thermostat Repair Parts and Assemblies (continued).  
Key  
No.  
Part No.  
Description  
10  
14002051-001 Pneumatic Assembly, TP970-TP973 - Includes 10B and 10C below  
14002102-004 Pneumatic Assembly, TP974A - Includes 10B and 10C below  
10A  
Tab and Screw - TP974A  
10B 14004419-001 Gasket, Restrictor block (included with 14002374-XXX)  
10C 14001865-001 Filter  
10D 14002374-001 Restrictor Block Assembly (0.005 restrictor, 2 pipe) - TP970A-D; TP971A, B, D, E; TP972A;  
TP973A, B  
14002374-005 Restrictor Block Assembly (0.005 restrictor, 3 pipe) - TP971C  
14002374-006 Restrictor Block Assembly (0.007 restrictor, 2 pipe) - TP974A  
10E 14002373-001 Switchover Spring Assembly, silver - 16 to 21 psi (110 to 145 kPa)  
14002373-002 Switchover Spring Assembly, gold - 13 to 18 psi (90 to 124 kPa)  
14003923-001 Switchover Spring Assembly, blue - 20 to 25 psi (140 to 175 kPa)  
10F 14002372-001 DAY/AUTO Lever Assembly  
11  
12  
Screw, No. 4-40 x 5/8 an head (included with 14002374-XXX)  
14002053-001 Wall Plate Assembly with setscrews 14003454-001 (2)  
*Replace the Setpoint Cam Assembly and Nozzle, Throttling Plate, Bimetal Assembly together.  
†If there is no antihum spring or cone, there is an adhesive paper dot on the throttling plate.  
TP978E  
1
2
3
4
5
See Figure 24 and Table 9 for TP978E Thermostat repair  
parts and assemblies. The TP978A-D Thermostats have not  
been replaced.  
M12207  
Fig. 24. TP978E Exploded View.  
75-7134—1  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 9. TP978E Thermostat Repair Parts and Assemblies.  
Model  
C
A
B
D
E
Key No.  
Part No.  
Description  
Screw, No. 4 x 3/16 pan head (2)  
Washer  
1
2
3
X
X
X
X
X
14002387-004  
14002098-004  
14002098-005  
14003855-005  
14002095-001  
14002387-005  
14002387-006  
14002387-007  
Nozzle, Throttling Plate, Bimetal Assembly (DA, left)  
Nozzle, Throttling Plate, Bimetal Assembly (RA, left)  
Nozzle, Throttling Plate, Bimetal Assembly (DA, right)  
Base and Cam Assembly  
4
5
Mounting Plate Assembly  
X
X
X
X
left side (R.A.) 60-73  
X
Right side (D.A.) 77-90  
X
Right side (R.A.) 77-90  
Table 10. TP979A-E Thermostat Repair Parts  
and Assemblies.  
TP979A-E  
See Figure 25 and Table 10 for TP979A-E Thermostat repair  
parts and assemblies.  
Key  
No.  
Part No.  
14004057-001  
14004058-001  
TP979A  
Description  
Mounting Plate Assembly  
Manifold Assembly  
1
1
2
3
Requires two TP970A2004  
Requires two TP970B2002  
TP979B  
2
TP979C  
Requires one TP970A2004 and  
one TP970B2002  
3
TP979D  
TP979E  
Requires one TP9712003 and  
one TP971D2007  
COOL  
M
B2  
HEAT  
Requires one TP971B2001 and  
one TP971E2004  
M
B1  
90  
80  
70  
60  
90  
Accessories  
80  
70  
60  
See TP970-TP974 and HP970 Series Fittings Installation  
Instructions 95-7134 for illustrations or further information on  
the following pneumatic fittings.  
M12221  
Fig. 25. TP979 Exploded View.  
75-7134—1  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 11. TP970 Series Thermostat Accessories.  
Description  
Part No.  
Airhead:  
Two-pipe red—angled  
14000686-002  
14000742-002  
14001527-001  
14004558-002  
14004558-001  
14002172-001  
Two-pipe red—straight  
Three-pipe —white, straight  
Tube-Spring assembly—6 inch branch, black  
Tube-Spring assembly—6 inch main, red  
Branch Line Gage Tap Plug  
Cable Assembly:  
14001494-001  
14001494-002  
14001494-003  
See Tables 11 & 12  
14004505-001  
14002362-001  
14001496-001  
311699  
One-pipe—8 ft (2.5m) poly sheathing  
Two-pipe—8 ft (2.5m) poly sheathing  
Three-pipe—8 ft (2.5m) poly sheathing  
Covers:  
Double Elbow—Used with airheads  
Duct Sampling Chamber with Shallow Wall Plate Fittings  
Electrical Box Adapter Plate  
Internal Tubing Spring—Used as strain relief inside plastic tubing  
Modernization Fitting, Universal:  
14002573-001  
14002573-002  
14003192-001  
One- and Two-Pipe  
Three-Pipe  
Serviceline Adapter Kit (for Honeywell stats prior to 1985)  
Mounting Ring:  
14004458-001  
14004458-001  
14000885-001  
14004300-001  
Flush  
Surface  
Standoff Plaster Ring  
Setpoint (Indicator Adjustment) Knob Retainer Kit—Used to prevent setpoint knob breakage  
on TP970 and TP973 thermostats with metal covers. Kit contains two socket-head screws,  
an Allen key, two round spacers, and a bar. The bar fits across the bottom of the  
thermostat to shield setpoint knob.  
14002430-001  
14002424-002  
AK3970  
Thermostat Heavy Duty Guard  
Wall Box—Aspirating with 8 ft (2.5m) 5/32-in. O.D. plastic tubing  
Cover for Aspirating Wall Box  
Wall Box—Deep:  
14001494-001  
14001494-002  
14001494-003  
14001492-001  
14001354-001  
14001355-001  
One-Pipe—8 ft (2.5m) copper tubing assembly  
Two-Pipe—8 ft (2.5m) copper tubing assembly  
Three-Pipe—8 ft (2.5m) copper tubing assembly  
Two-Pipe—8 ft (2.5m), 5/32-in. plastic tubing assembly (modified 1985)  
Mounting Bracket—Deep Wall Box  
Box alone  
Wall Box—Shallow:  
14001615-001  
14001616-001  
14001615-002  
14001616-002  
14001614-001  
One-Pipe—8 ft (2.5m) copper tubing assembly (modified 1985)  
One-Pipe—8 ft (2.5m), 5/32-in. plastic tubing assembly (modified 1985)  
Two-Pipe—8 ft (2.5m) copper tubing assembly (modified 1985)  
Two-Pipe—8 ft (2.5m), 5/32-in. plastic tubing assembly (modified 1985)  
Plate alone  
Wall Plate:  
14002136-004  
14002136-005  
14002540-002  
14004401-002  
14001905-001  
14002053-001  
Black  
Beige  
Q629 A-C Fan Speed Switch  
Convertastat Adapter  
Wall Plate Assembly—blank, beige, with screws  
Mounting Plate Assembly (Before 1985 this was a metal plate requiring an airhead. Now it is  
plastic and includes tube connection barbs.)  
Steel Stiffener Plate (for stronger support of 14002053-001)  
14004609-001  
75-7134—1  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS  
Table 12. TP970 Series Thermostat Covers—Satin Chrome.  
Part Number 14004406-XXX*  
Honeywell Logo  
Setpoint Slot  
No Logo  
Setpoint Slot  
Open  
Mounting  
Closed  
Mounting  
Open  
Mounting  
Horiz  
Closed  
Mounting  
Vert Horiz  
Window  
Insert  
Display Unit  
Vert  
Horiz  
Vert  
Horiz Vert  
None  
——  
——  
-300  
-400  
——  
——  
-800  
Setpoint  
Thermometer  
15-30 (C)  
60-90 (F)  
40-70 (F)  
60-90 (F)  
15-30 (C)  
60-90 (F)  
40-70 (F)  
Heat  
-110  
-111  
-112  
-114  
-210  
-211  
——  
——  
-310  
-311  
——  
——  
——  
——  
——  
——  
——  
-511  
——  
——  
——  
-611  
——  
——  
——  
-711  
——  
——  
——  
——  
——  
——  
60 70 80 90  
60 70 80 90  
range/  
Cool range  
60-90 (F)  
15-30 (C)  
60-90 (F)  
40-70 (F)  
COOLER/  
WARMER  
——  
——  
——  
——  
-120  
-121  
-122  
-123  
——  
——  
——  
——  
-320  
-321  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
60 70 80 90  
60 70 80 90  
——  
——  
15-30 (C)  
60-90 (F)  
-330  
——  
——  
——  
——  
——  
——  
——  
*When ordering, use complete part number including three-digit suffix.  
†14004406-008 Cover also suitable for vertical mounting.  
75-7134—1  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13. TP970 Series Thermostat Covers—Beige Plastic.  
Part Number 14004407-XXX*  
Honeywell Logo  
Setpoint Slot  
No Logo  
Setpoint Slot  
Open  
Mounting  
Closed  
Mounting  
Open  
Mounting  
Horiz  
Closed  
Mounting  
Vert Horiz  
Window  
Insert  
Display Unit  
Vert  
Horiz  
Vert  
Horiz Vert  
None  
——  
——  
-300  
-400  
——  
——  
-800  
Setpoint  
Thermometer  
15-30 (C)  
60-90 (F)  
15-30 (C)  
60-90 (F)  
15-30 (C)  
-110  
-111  
-113  
-210  
——  
——  
——  
-311  
——  
——  
——  
——  
——  
-511  
——  
——  
——  
——  
——  
——  
——  
——  
——  
——  
60-90 (F)  
60 70 80 90  
60 70 80 90  
60-90 (F)  
——  
-121  
——  
——  
——  
——  
——  
——  
——  
60 70 80 90  
*When ordering, use complete part number including three-digit suffix.  
†14004406-008 Cover also suitable for vertical mounting.  
Table 14. TP9600 Series Thermostat Covers.  
Model Setpoint Thermometer  
14004407-XXX Covers are paintable. See HP970-72 and  
TP970-74 Pneumatic Sensors, Humidistats, and Thermostats  
Installation Instructions 95-5597 for painting information.  
TP9600A  
TP9600B  
TP9603A  
TP9603B  
TP9610A  
TP9610B  
TP9613A  
TP9613B  
TP9620A  
TP9623B  
TP9630A  
TP9630B  
TP9633A  
TP9633B  
Visible and adjustable Visible  
Visible and adjustable Visible  
Concealed  
Concealed  
Concealed  
Concealed  
Visible and adjustable Visible  
Visible and adjustable Visible  
Concealed  
Concealed  
Concealed  
Concealed  
Visible and adjustable Visible  
Concealed  
Concealed  
Visible and adjustable Visible  
Visible and adjustable Visible  
Concealed  
Concealed  
Concealed  
Concealed  
Fig. 26. TP9600 Series Thermostat.  
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
P.O. Box 524  
Minneapolis MN 55408-0524  
M2H 3N7  
Printed in U.S.A. on recycled  
paper containing at least 10%  
75-7134—1 R. F. Rev. 12-97  
post-consumer paper fibers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Harbor Freight Tools Impact Driver 37730 User Manual
Harbor Freight Tools Nail Gun 42528 User Manual
Harbor Freight Tools Pressure Washer 67596 User Manual
Heath Zenith Universal Remote 598 1116 10 User Manual
Hotpoint Oven Accessories SX 1049L CX User Manual
HP Hewlett Packard Laptop x1100 User Manual
HP Hewlett Packard Oven 45WDG PLUS User Manual
Huawei Network Router HG532S User Manual
Hubbell Switch LXi 2400 User Manual
IKEA Indoor Furnishings AA 233194 2 User Manual