Carrier Water Dispenser 30XW325 400 User Manual

AQUAFORCE®  
30XW325-400  
Water-Cooled Liquid Screw  
Chillers  
Product  
Data  
325 to 400 Nominal Tons  
(1133 to 1354 kW)  
Carrier's AquaForce 30XW chillers  
provide a great combination of perfor-  
mance and compact footprint for  
cooling and heat recovery applica-  
tions. These chillers provide excellent  
reliability and efficiency at true operat-  
ing conditions without compromising  
the environment.  
• Chlorine-free R-134a HFC  
refrigerant  
• Positive displacement, twin screw  
compressors  
• AHRI (Air Conditioning, Heating,  
and Refrigeration Institute) certified  
efficiencies to 0.468 kW per ton  
IPLV (integrated part load value)  
• Dual independent refrigerant  
circuits  
• Compact footprint, less than 48 in.  
(1219 mm) wide  
• Easy to use controls  
Features/Benefits  
Quality design and  
construction make the  
AquaForce 30XW chillers an  
excellent choice for modern,  
efficient chilled water plants.  
Small footprint  
The 30XW chillers feature a compact  
footprint and are delivered as a single  
complete package less than 48 in.  
(1219 mm) wide for easy installation  
and minimal indoor space. The 30XW  
chiller footprints may be up to 30%  
smaller when compared to other chill-  
ers and may require less mechanical  
room floor space and smaller concrete  
pads.  
Copyright 2009 Carrier Corporation  
Form 30XW-2PD  
of the system. The AquaForce® 30XW Electronic thermal-dispersion flow  
Carrier's exclusive handheld Naviga-  
tor display provides convenience and  
powerful information in the palm of  
your hand. The Navigator display helps  
technicians to quickly diagnose prob-  
lems and even prevent them from  
occurring.  
chiller's positive pressure design  
ensures that air, moisture and other  
performance degrading contaminants  
are not sucked inside the chiller. Purge  
units and their associated maintenance  
are no longer necessary.  
switch  
An electronic thermal-dispersion flow  
switch switch is included with the evap-  
orator. The switch is factory installed  
and tested and contains no moving  
parts for high reliability.  
All 30XW units are ready to be used  
with Carrier Comfort Network® (CCN)  
devices.  
Controls features include:  
Automatic capacity override  
This function unloads the compressor  
whenever key safety limits are  
approached, increasing unit life.  
High performance tubing  
Refrigerant isolation valves  
The refrigerant isolation valves enable  
service personnel to store the refriger-  
ant charge in the evaporator or con-  
denser during servicing. These valves  
also allow the refrigerant to be stored  
inside the chiller during shipment from  
the factory minimizing start-up time.  
During servicing, the in-chiller storage  
reduces refrigerant loss and eliminates  
time-consuming transfer procedures.  
As a self-contained unit, the AquaForce  
30XW chiller does not require addi-  
tional remote storage systems.  
Carrier's AquaForce chillers utilize  
advances in heat transfer technology  
providing compact, high-efficiency  
heat exchangers. Tubing with  
advanced internally and externally  
enhanced geometry improves chiller  
performance by reducing overall resis-  
tance to heat transfer while reducing  
fouling.  
Chilled liquid reset  
Reset can be accomplished manually or  
automatically from the building man-  
agement system. For a given capacity,  
reset allows operation at slower com-  
pressor speeds, saving energy when  
warmer chilled liquid can be used.  
Evaporator tube expansion  
Evaporator tube expansion at center  
support sheets prevents unwanted tube  
movement and vibration, thereby  
reducing the possibility of premature  
tube failure. Tube wall thickness is  
greater at the expansion location, sup-  
port sheets, and end tube sheets, to  
provide maximum strength and long  
tube life.  
Closely spaced intermediate sup-  
port sheets  
Support sheets prevent tube sagging  
and vibration, thereby increasing heat  
exchanger life.  
Optional suction service valves  
The optional suction service valves  
allow for further isolation of the com-  
pressor from the evaporator vessel.  
Demand limiting  
This feature limits the power draw of  
the chiller during peak loading condi-  
tions. When incorporated into the  
CCN building automation system, a red  
line command holds chillers at their  
present capacity and prevents any  
other chillers from starting. If a load  
shed signal is received, the compres-  
sors are unloaded to avoid demand  
charges whenever possible.  
Marine container shipment  
The compact design allows for con-  
tainer shipment to export destinations,  
ensuring quality while reducing ship-  
ping cost.  
Heat exchangers  
Refrigerant filter isolation valves  
The Aquaforce 30XW chillers utilize  
mechanically cleanable shell and tube  
evaporators and condensers available  
with a complete line of waterbox  
options to meet project specific  
requirements. One, two, and three  
pass arrangements are available to  
meet a wide variety of flow conditions.  
Nozzle in head and marine waterboxes  
are available to meet 150 psig  
These valves allow filter replacement  
without pumping down the chiller,  
reducing service time and expense.  
Ramp loading  
Ramp loading ensures smooth pull-  
down of liquid loop temperature and  
prevents a rapid increase in compres-  
sor power consumption during the  
pulldown period.  
Automated controls test  
The test can be executed prior to start-  
Microprocessor controls  
The AquaForce 30XW screw chiller  
controls communicate in easy to under-  
stand English, making it as easy as pos-  
sible to monitor and control each  
(1034 kPa) and 300 psig (2068 kPa)  
piping requirements.  
Heat exchanger features include:  
chiller while maintaining fluid tempera- up to verify that the entire control sys-  
tures. Controls are available with  
French, Portuguese and Spanish as  
standard configuration options. These  
controls result in higher chiller reliabil-  
ity, simplified training and correspond-  
ingly lower operational and  
tem is functioning properly.  
365-day real time clock  
This feature allows the operator to pro-  
gram a yearly schedule for each week,  
weekends, and holidays.  
ASME certified construction  
An independent agency certifies the  
design, manufacture, and testing of all  
heat exchangers to American Society  
of Mechanical Engineers (ASME) stan-  
dards, ensuring heat exchanger safety,  
reliability and long life. The ASME  
U-stamp is applied to the refrigerant  
side of the evaporator and condenser  
and is applied to the water side of these  
heat exchangers when 300 psig  
(2068 kPa) marine waterboxes are  
provided.  
Occupancy schedules  
maintenance costs.  
Schedules can be programmed into the  
controller to ensure that the chiller  
operates when cooling is required and  
remains off when not needed by the  
tenants or process.  
Two user interface options are avail-  
able, the Touch Pilot™ display and the  
Navigator™ module.  
The Touch Pilot display is an easy to  
use touch screen display that provides  
simple navigation for configuration and  
control of the 30XW units.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features/Benefits (cont)  
Extensive service menu  
Alarm file  
Configuration data backup  
Unauthorized access to the service  
menu can be password-protected.  
Built-in diagnostic capabilities assist in  
troubleshooting and recommend  
proper corrective action for pre-set  
alarms, resulting in greater up time.  
This file maintains the last 50 time and  
Non-volatile memory provides protec-  
date-stamped alarm and alert messages tion during power failures and  
in memory. This function reduces trou- eliminates time consuming control  
bleshooting time and cost.  
reconfiguration.  
a30-4456  
30-562  
TOUCH PILOT™ DISPLAY  
SMOOTH ROTARY COMPRESSOR  
TWIN-SCREW DESIGN  
Comf  
or  
t
Link  
MODE  
Alar  
m
Run Status  
Ser  
Status  
vice  
T
e
st  
T
e
mper  
atures  
Pressures  
Setpoints  
Inputs  
Outputs  
Configur  
ation  
Time Cloc  
k
ESC  
Oper  
ating Modes  
Alar  
ms  
ENTER  
a30-3924  
OPTIONAL NAVIGATOR™ DISPLAY  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model number nomenclature  
30XW  
325  
6
4
3
B
30XW – AquaForce® Water-Cooled  
Screw Chiller  
Packaging/Charging Options  
B – R-134a Refrigerant with Bag (Std)  
C – R-134a Refrigerant with Crate Over Bag  
D – Nitrogen Refrigerant with Bag  
Design Series  
F – Nitrogen Refrigerant with Crate Over Bag  
Unit Size (Nominal Tons) (kW)  
325 325 (1133)  
350 350 (1206)  
Controls/Communications Options  
-
– Navigator™ Display  
0 – Navigator Display, EMM  
400 – 400 (1354)  
1 – Navigator Display, GFCI Service Option  
2 – Navigator Display, EMM, GFCI Service Option  
3 – Touch Pilot™ Display (Std)  
Voltage  
4 – Touch Pilot, EMM  
1 – 575-3-60  
2 380-3-60  
4 – 230-3-60  
6 – 460-3-60  
7 – 200-3-60  
5 – Touch Pilot, GFCI Service Option  
6 – Touch Pilot, EMM, GFCI Service Option  
7 – Navigator Display, BACnet™ Translator  
8 – Navigator Display, EMM, BACnet Translator  
9 – Navigator Display, GFCI Service Option,  
BACnet Translator  
B – Navigator Display, EMM, GFCI Service Option,  
Condenser Options  
BACnet Translator  
-
– 2 Pass, NIH, 150 psig (1034 kPa), Victaulic, Discharge Connections (Std)  
C – Touch Pilot Display (Std), BACnet Translator  
D – Touch Pilot Display, EMM, BACnet Translator  
F – Touch Pilot Display, GFCI Service Option,  
BACnet Translator  
0 – 2 Pass, NIH, 150 psig (1034 kPa), Victaulic, Suction Connections  
1 – 2 Pass, NIH, 150 psig (1034 kPa), Flange, Discharge Connections  
2 – 2 Pass, NIH, 150 psig (1034 kPa), Flange, Suction Connections  
3 – 2 Pass, NIH, 300 psig (2068 kPa), Victaulic, Discharge Connections  
4 – 2 Pass, NIH, 300 psig (2068 kPa), Victaulic, Suction Connections  
5 – 2 Pass, NIH, 300 psig (2068 kPa), Flange, Discharge Connections  
6 – 2 Pass, NIH, 300 psig (2068 kPa), Flange, Suction Connections  
7 – 2 Pass, MWB, 150 psig (1034 kPa), Victaulic, Discharge Connections  
8 – 2 Pass, MWB, 150 psig (1034 kPa), Victaulic, Suction Connections  
9 – 2 Pass, MWB, 300 psig (2068 kPa), Victaulic, Discharge Connections  
B – 2 Pass, MWB, 300 psig (2068 kPa), Victaulic, Suction Connections  
C – 2 Pass, MWB, 150 psig (1034 kPa), Flange, Discharge Connections  
D – 2 Pass, MWB, 150 psig (1034 kPa), Flange, Suction Connections  
F – 2 Pass, MWB, 300 psig (2068 kPa), Flange, Discharge Connections  
G – 2 Pass, MWB, 300 psig (2068 kPa), Flange, Suction Connections  
H – 1 Pass, NIH, 150 psig (1034 kPa), Flange, Discharge Leaving  
J – 1 Pass, NIH, 300 psig (2068 kPa), Flange, Discharge Leaving  
K – 1 Pass, MWB, 150 psig (1034 kPa), Flange, Discharge Leaving  
L – 1 Pass, MWB, 300 psig (2068 kPa), Flange, Discharge Leaving  
G – Touch Pilot Display, EMM, GFCI Service Option,  
BACnet Translator  
H – Navigator Display, LON Translator  
J – Navigator Display, EMM, LON Translator  
K – Navigator Display, GFCI Service Option,  
LON Translator  
L – Navigator Display, EMM, GFCI Service Option,  
LON Translator  
M – Touch Pilot Display (Std), LON Translator  
N – Touch Pilot Display, EMM, LON Translator  
P – Touch Pilot Display, GFCI Service Option,  
LON Translator  
Q – Touch Pilot Display, EMM, GFCI Service  
Option, LON Translator  
Electrical Options  
-
Single Point, XL Starter, Terminal Block  
(Std 380, 460, 575-v)  
Heat Machine  
-
Std Condenser/Comfort Cooling (Std)  
0 Single Point, Wye-Delta Starter, Terminal  
M – Heat Machine Condenser/Comfort Cooling  
Block (Std 200,230-v)  
3 – Dual Point, XL Starter, Terminal Block  
4 – Dual Point, Wye-Delta Starter, Terminal Block  
7 Single Point, XL Starter, Non-Fused Disconnect  
8 Single Point, Wye-Delta, Non-Fused Disconnect  
C – Dual Point, XL Starter, Non-Fused Disconnect  
D – Dual Point, Wye-Delta Starter, Non-Fused  
Disconnect  
H Single Point, XL Starter, Terminal Block, CPT  
J Single Point, Wye-Delta Starter, Terminal  
Block, CPT  
Evaporator Options  
-
– 2 Pass, NIH, 150 psig (1034 kPa), Victaulic, Discharge Connections (Std)  
0 – 2 Pass, NIH, 150 psig (1034 kPa), Victaulic, Suction Connections  
1 – 2 Pass, NIH, 150 psig (1034 kPa), Flange, Discharge Connections  
2 – 2 Pass, NIH, 150 psig (1034 kPa), Flange, Suction Connections  
3 – 2 Pass, NIH, 300 psig (2068 kPa), Victaulic, Discharge Connections  
4 – 2 Pass, NIH, 300 psig (2068 kPa), Victaulic, Suction Connections  
5 – 2 Pass, NIH, 300 psig (2068 kPa), Flange, Discharge Connections  
6 – 2 Pass, NIH, 300 psig (2068 kPa), Flange, Suction Connections  
7 – 2 Pass, MWB, 150 psig (1034 kPa), Victaulic, Discharge Connections  
8 – 2 Pass, MWB, 150 psig (1034 kPa), Victaulic, Suction Connections  
9 – 2 Pass, MWB, 300 psig (2068 kPa), Victaulic, Discharge Connections  
B – 2 Pass, MWB, 300 psig (2068 kPa), Victaulic, Suction Connections  
C – 2 Pass, MWB, 150 psig (1034 kPa), Flange, Discharge Connections  
D – 2 Pass, MWB, 150 psig (1034 kPa), Flange, Suction Connections  
F – 2 Pass, MWB, 300 psig (2068 kPa), Flange, Discharge Connections  
G – 2 Pass, MWB, 300 psig (2068 kPa), Flange, Suction Connections  
H – 1 Pass, NIH, 150 psig (1034 kPa), Flange, Discharge Leaving  
J – 1 Pass, NIH, 300 psig (2068 kPa), Flange, Discharge Leaving  
K – 1 Pass, MWB, 150 psig (1034 kPa), Flange, Discharge Leaving  
L – 1 Pass, MWB, 300 psig (2068 kPa), Flange, Discharge Leaving  
M 3 Pass, NIH, 150 psig (1034 kPa), Flange, Discharge Leaving  
N 3 Pass, NIH, 150 psig (1034 kPa), Flange, Suction Leaving  
P 3 Pass, NIH, 300 psig (2068 kPa), Flange, Discharge Leaving  
Q 3 Pass, NIH, 300 psig (2068 kPa), Flange, Suction Leaving  
R 3 Pass, MWB, 150 psig (1034 kPa), Flange, Discharge Leaving  
S 3 Pass, MWB, 150 psig (1034 kPa), Flange, Suction Leaving  
T 3 Pass, MWB, 300 psig (2068 kPa), Flange, Discharge Leaving  
V 3 Pass, MWB, 300 psig (2068 kPa), Flange, Suction Leaving  
M – Dual Point, XL Starter, Terminal Block, CPT  
N – Dual Point, Wye-Delta Starter, Terminal  
Block, CPT  
R Single Point, XL Starter, Non-Fused  
Disconnect, CPT  
S Single Point, Wye-Delta, Non-Fused  
Disconnect, CPT  
W – Dual Point, XL Starter, Non-Fused  
Disconnect, CPT  
X – Dual Point, Wye-Delta Starter, Non-Fused  
Disconnect, CPT  
Refrigeration Circuit Options  
4 Standard Unit  
*
6 – With Suction Service Valves  
D – With Minimum Load Control  
G – With Suction Service Valves and Minimum  
Load Control  
N – With Condenser Insulation for Heat Machine  
Q – With Suction Service Valves and Condenser  
Insulation for Heat Machine  
X – With Minimum Load Control and Condenser  
LEGEND  
Insulation for Heat Machine  
CPT  
Control Power Transformer  
Energy Management Module  
Ground Fault Circuit Interrupter  
Local Operating Network  
MWB  
NIH  
XL  
Marine Waterbox  
Nozzle-In-Head  
Across-the-Line Start  
Z – With Suction Service Valves, Minimum Load  
Control and Condenser Insulation for  
Heat Machine  
EMM  
GFCI  
LON  
*Evaporator insulation is standard.  
a30-4744  
Quality Assurance  
Certified to ISO 9001:2000  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Capacity ratings  
EVAPORATOR  
FLOW  
EVAPORATOR  
CONDENSER  
FLOW  
CONDENSER  
CAPACITY  
INPUT  
POWER  
(kW)  
FULL LOAD  
EFFICIENCY  
(kW/Ton)  
PRESSURE DROP  
PRESSURE DROP  
30XW  
UNITSIZE  
IPLV  
(kW/Ton)  
Output  
Ft of  
Ft of  
Tons  
gpm  
L/s  
kPa  
gpm  
L/s  
kPa  
(kW)  
Water  
Water  
325  
350  
400  
322  
343  
385  
1132.5  
1206.3  
1354.0  
204.8  
215.7  
242.8  
773  
824  
924  
48.8  
52.0  
58.3  
15.6  
17.5  
21.5  
46.5  
52.2  
64.1  
967  
1029  
1155  
61.0  
64.9  
72.9  
10.9  
12.3  
15.2  
32.5  
36.7  
45.3  
0.636  
0.629  
0.631  
0.468  
0.471  
0.474  
LEGEND  
Fouling Factor (Evaporator):  
0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W)  
Fouling Factor (Condenser):  
AHRI — Air Conditioning, Heating and Refrigeration Institute  
IPLV — Integrated Part Load Value  
0.00025 hr x sq ft x F per Btuh (0.000044 m2 x K per W)  
3. IPLV is a single number part-load efficiency value calculated from  
the system full-load efficiency values and corrected for a typical  
building air-conditioning application.  
NOTES:  
1. Certified in accordance with AHRI Standard 550/590 at standard  
rating conditions.  
4. Contact Carrier for custom ratings.  
2. Standard rating conditions are as follows:  
Evaporator Conditions:  
5. Data shown for standard chiller with 2 pass, nozzle-in-head (NIH)  
waterboxes.  
Leaving Water Temperature: 44 F (6.7 C)  
Flow:  
2.4 gpm per ton (0.043 L/s per kW)  
Condenser Conditions:  
Entering Water Temperature:85 F (29.4 C)  
Flow:  
3.0 gpm per ton (0.054 L/s per kW)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Physical data  
30XW325-400 UNIT PHYSICAL DATA — ENGLISH  
30XW UNIT SIZE  
NOMINAL CAPACITY (tons)  
UNIT WEIGHT (lb) (Operating/Shipping)  
325  
325  
14,319/13,163  
350  
350  
14,515/13,369  
400  
400  
14,759/13,489  
COMPRESSORS  
Semi-hermetic, twin screw  
3500  
Compressor Speed (rpm)  
Compressor Model Number (qty)  
Unloading Type  
06TU483 (2)  
06TU554 (2)  
Slide Valve  
15%  
Minimum Step Capacity % (standard)  
Optional %  
10%  
Economizer  
No  
Yes  
3/8  
Temperature Relief Valve Connection (in. SAE Flare) (each circuit)  
REFRIGERANT  
HFC, R-134a  
Charge (lb) Circuit A  
Charge (lb) Circuit B  
260  
260  
270  
270  
OIL  
POE, SW-220  
Charge (gal.) Circuit A  
Charge (gal.) Circuit B  
4
4
EVAPORATOR  
Net Fluid Volume (gal.)  
76.0  
220  
Maximum Refrigerant Pressure (psig)  
Maximum Water Side Pressure (psig)  
Standard  
150  
300  
Optional  
Water Connections  
Inlet and Outlet (in.)  
1-Pass NIH or MWB Flange (optional)  
1-Pass NIH Victaulic (optional)  
2-Pass NIH or MWB Flange (optional)  
2-Pass NIH Victaulic (standard)  
2-Pass MWB Victaulic (optional)  
3-Pass NIH or MWB Flange (optional)  
3-Pass NIH Victaulic (optional)  
Drain (in. NPT)  
6
8
6
8
6
6
8
3
/
8
3
Relief Valve Connection (in. NPTF)  
Quantity Per Circuit  
/
4
1
Relief Valve Setting (psig)  
Flow Rate (lb air/min)  
220  
31.7  
CONDENSER  
Net Fluid Volume (gal.)  
82.6  
Maximum Refrigerant Pressure (psig)  
Standard Condenser  
220  
300  
Heat Machine  
Maximum Water Side Pressure (psig)  
Standard  
150  
300  
300  
Optional  
Heat Machine  
Water Connections  
Inlet and Outlet (in.)  
1-Pass NIH or MWB Flange (optional)  
1-Pass NIH Victaulic (optional)  
2-Pass NIH or MWB Flange (optional)  
2-Pass NIH Victaulic (standard)  
2-Pass MWB Victaulic (optional)  
Drain (in. NPT)  
6
8
6
8
6
3
/
Relief Valve Connection (in. NPTF) (Standard/Heat Machine)  
Quantity Per Circuit  
3/4 /83/4  
2/2  
Relief Valve Setting (psig)  
Flow Rate (lb air/min)  
Temperature Relief Valve Connection (in. SAE Flare)  
Discharge Line (Qty per Circuit)  
Liquid Line (Qty per Circuit)  
220/300  
31.7/46.6  
1
/
4
1
1
CHASSIS DIMENSIONS (ft-in.)  
Length  
Width  
13 - 3 3/4  
3 - 11 3/8  
Height  
6 - 6 11  
/
16  
LEGEND  
HFC — Hydrofluorocarbon  
MWB — Marine Waterbox  
NIH — Nozzle-In-Head  
NPTF — National Pipe Thread Female  
POE — Polyolester  
SAE — Society of Automotive Engineers  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
30XW325-400 UNIT PHYSICAL DATA — SI  
30XW UNIT SIZE  
NOMINAL CAPACITY (kW)  
UNIT WEIGHT (kg) (Operating/Shipping)  
325  
1133  
6495/5971  
350  
1206  
6584/6064  
400  
1354  
6695/6119  
COMPRESSORS  
Semi-hermetic, twin screw  
58.3  
Compressor Speed (r/s)  
Compressor Model Number (qty)  
Unloading Type  
06TU483 (2)  
06TU554 (2)  
Slide Valve  
15%  
Minimum Step Capacity % (standard)  
Optional %  
10%  
Economizer  
No  
Yes  
3
Temperature Relief Valve Connection (in. SAE Flare) (each circuit)  
/
8
REFRIGERANT  
HFC, R-134a  
Charge (kg) Circuit A  
Charge (kg) Circuit B  
117.9  
117.9  
122.5  
122.5  
OIL  
POE, SW-220  
15.1  
Charge (L) Circuit A  
Charge (L) Circuit B  
15.1  
EVAPORATOR  
Net Fluid Volume (L)  
287.7  
1517  
Maximum Refrigerant Pressure (kPa)  
Maximum Water Side Pressure (kPa)  
Standard  
1034  
2068  
Optional  
Water Connections  
Inlet and Outlet (in.)  
1-Pass NIH or MWB Flange (optional)  
1-Pass NIH Victaulic (optional)  
2-Pass NIH or MWB Flange (optional)  
2-Pass NIH Victaulic (standard)  
2-Pass MWB Victaulic (optional)  
3-Pass NIH or MWB Flange (optional)  
3-Pass NIH Victaulic (optional)  
Drain (in. NPT)  
6
8
6
8
6
6
8
3
/
8
3
Relief Valve Connection (in. NPTF)  
Quantity Per Circuit  
/
4
1
Relief Valve Setting (kpa)  
Flow Rate (kg air/min)  
1517  
14.38  
CONDENSER  
Net Fluid Volume (L)  
312.7  
Maximum Refrigerant Pressure (kPa)  
Standard Condenser  
1517  
2068  
Heat Machine  
Maximum Water Side Pressure (kPa)  
Standard  
1034  
2068  
2068  
Optional  
Heat Machine  
Water Connections  
Inlet and Outlet (in.)  
1-Pass NIH or MWB Flange (optional)  
1-Pass NIH Victaulic (optional)  
2-Pass NIH or MWB Flange (optional)  
2-Pass NIH Victaulic (standard)  
2-Pass MWB Victaulic (optional)  
Drain (in. NPT)  
6
8
6
8
6
3
/
Relief Valve Connection (in. NPTF) (Standard/Heat Machine)  
Quantity Per Circuit  
3/4 /83/4  
2/2  
1517/2068  
14.38/21.1  
Relief Valve Setting (kpa)  
Flow Rate (kg air/min)  
LEGEND  
8
Options and accessories  
The 300 psig (2068 kPa) evaporator operating  
pressure option allows operation for water-side pressure  
up to 300 psig (2068 kPa).  
The 300 psig (2068 kPa) condenser operating  
pressure option allows operation for water-side pressure  
up to 300 psig (2068 kPa).  
Minimum load control allows additional capacity reduc-  
tion for unit operation below the minimum step of unload-  
ing via hot gas bypass.  
Marine waterboxes provide water piping connections  
extending from the side of the waterbox (as opposed to  
extending from the end of the waterbox). This option also  
includes a removable bolt on waterbox cover allowing  
access to the heat exchanger tubes without breaking the  
existing field piping. This option is available for both the  
evaporator and condenser.  
FACTORY-  
INSTALLED  
OPTION  
FIELD-  
ITEM  
INSTALLED  
ACCESSORY  
Controls Options  
Navigator Hand-Held Display  
Remote Enhanced Display  
BACnet Translator Control  
LON Translator Control  
Energy Management Module  
Evaporator Options  
One-Pass Evaporator Head  
Three-Pass Evaporator Head  
Marine Waterboxes  
Flanged Connections  
Suction Service Valve  
300 psig (2068 kPa) Operating Pressure  
Condenser Options  
Heat Machine Condenser  
One-Pass Condenser Head  
Marine Waterboxes  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Flanged Connections  
300 psig (2068 kPa) Operating Pressure  
Starter Options  
Wye-Delta Starter  
Dual Point Power  
Non-Fused Disconnect  
Control Transformer  
115-v GFCI Convenience Outlet  
Unit Options  
X
X
X
X
X
Minimum Load Control  
Temperature Reset Sensor  
Nitrogen Charge  
X
X
X
X
a30-4684.eps  
Crate for Shipment  
Vibration Pads  
Vibration Isolation Springs  
X
X
Flanged connection option provides an ANSI (Ameri-  
can National Standards Institute) flange on the end of the  
chiller water piping for connection to a customer supplied  
mating flange in the field piping. This option is available  
for both the evaporator and condenser.  
Factory-installed options  
Navigator™ module provides a portable, hand-held dis-  
play for convenient access to unit status, operation, config-  
uration and troubleshooting diagnostics capability. The  
four-line, 20-character LCD (liquid crystal display) display  
provides clear language information in English, French,  
Spanish, or Portuguese. The Navigator module features an  
industrial grade extension chord and magnets located on  
the back of the weatherproof enclosure to allow attach-  
ment to sheet metal components for hands free operation.  
BACnet™ translator control provides an interface  
between the chiller and BACnet Local Area Network  
(LAN, i.e., MS/TP EIA 485). The BACnet translator con-  
trol is also available as a field-installed option.  
LON translator control provides an interface between  
the chiller and Local Operating Network (LON, i.e., LON-  
Works FT-10A ANSI/EIA-709.1). The LON translator  
control is also available as a field-installed option.  
Energy management module provides energy manage-  
ment capabilities to minimize chiller energy consumption.  
Several features are provided with this module including  
leaving fluid temperature reset, cooling set point reset or  
demand limit control from a 4 to 20 mA signal, 2-point  
demand limit control (from 0 to 100%) activated by a  
remote contact closure, and discrete input for "Ice Done"  
indication for ice stage system interface.  
a30-4685  
One-pass evaporator provides a lower pressure drop  
through the evaporator for applications with low delta T  
(temperature) or high flow or where the evaporators are  
piped in a series or side stream arrangement. One-pass  
evaporator is only available with flanged connections and  
with discharge end leaving water connection.  
Three-pass evaporator provides a greater efficiency for  
brine applications and in applications with a high delta T  
and low flow. Three-pass evaporator is only available with  
flanged connections.  
Heat machine condenser allows operation with up to  
140 F (60 C) leaving condenser water temperature (see  
E-CAT for selections). In addition, this option provides  
factory-installed thermal insulation on the condenser,  
condenser flow switch and leaving condenser water  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options and accessories (cont)  
temperature sensor to facilitate operating in HEAT mode.  
Heat machine units require 300 psig (2068 kPa) option  
and field-installed thermal insulation on the compressor  
discharge piping and waterbox heads because of high  
temperature.  
One-pass condenser provides a lower pressure drop  
through the condenser for applications with low delta T  
(temperature) or high flow or where the condensers are  
piped in a series. The one-pass condenser option is only  
available with flanged connections and with a discharge  
end leaving water connection.  
Wye-delta start is an alternate starting method which  
reduces the inrush current when starting the compressor.  
Wye delta start is standard on 208-v, and 230-v units,  
optional for 380-v, 460-v, and 575-v.  
Dual point power provides a means for connecting two  
sources of power to dual compressor 30XW chillers. One  
source of power is wired to operate the compressor on the  
A circuit and one source of power is wired to operate the  
compressor on the B circuit of the chiller.  
Non-fused disconnect provides a no load, lockable,  
through the door handle disconnect for unit power on the  
chiller. On dual point power, one disconnect is provided for  
each of the two main power supplies. This disconnect does  
not remove the control circuit from power supply.  
Control transformer is sized to supply the needs of the  
control circuit from the main power supply.  
115-v GFCI convenience outlet includes 4 amp GFI  
(ground fault interrupt) receptacle. Convenience outlet is  
115-v female receptacle. Not available with 380-v units.  
Nitrogen charge provides a 15 lb (6.8 kg) charge of  
nitrogen instead of a full factory charge of R-134a refrig-  
erant to keep the chiller refrigerant circuit dry during ship-  
ment. This option is recommended for applications where  
the unit will be disassembled prior to installation. Units  
shipped with a nitrogen charge will receive an electrical  
continuity test at the factory prior to shipment.  
Crate for shipment provides a wooden crate around the  
chiller. The chiller is bagged prior to being placed in the  
crate. This option is recommended for export orders.  
Suction service valves allow for further isolation of the  
compressor from the evaporator vessel.  
BACnet™ translator control provides an interface  
between the chiller and BACnet Local Area Network  
(LAN, i.e., MS/TP EIA 485). The BACnet translator con-  
trol is also available as a factory-installed option.  
LON translator control provides an interface between  
the chiller and Local Operating Network (LON, i.e., LON-  
Works FT-10A ANSI/EIA-709.1). The LON translator  
control is also available as a factory-installed option.  
Energy management module provides energy manage-  
ment capabilities to minimize chiller energy consumption.  
Several features are provided with this module including  
leaving fluid temperature reset, cooling set point reset or  
demand limit control from a 4 to 20 mA signal, 2-point  
demand limit control (from 0 to 100%) activated by a  
remote contact closure, and discrete input for "Ice Done"  
indication for ice stage system interface.  
Temperature reset sensor provides temperature reset  
capability from either the occupied space or outdoor tem-  
perature sensor.  
NOTE: Temperature reset capability using return tempera-  
ture is standard.  
Vibration isolation pads are neoprene pads for installa-  
tion under the chiller feet at the jobsite.  
Vibration springs provide a set of non-siesmic spring  
isolators for installation at the jobsite.  
Navigator™ module provides a portable, hand-held dis-  
play for convenient access to unit status, operation, config-  
uration and troubleshooting diagnostics capability. The  
four-line, 20-character LCD (liquid crystal display) display  
provides clear language information in English, French,  
Spanish, or Portuguese. The Navigator module features an  
industrial grade extension chord and magnets located on  
the back of the weatherproof enclosure to allow attach-  
ment to sheet metal components for hands free operation.  
Field-supplied and field-installed insulation  
Evaporator waterbox insulation must be field installed.  
When insulating waterboxes, allow for service access and  
removal of covers. To estimate waterbox cover areas, refer  
to the following figure.  
Insulation for discharge piping between the compres-  
sor and condenser must be field installed on heat machine  
units. Refer to the following figure.  
Condenser waterbox insulation must be field installed  
on heat machine units. When insulating waterboxes, allow  
for service access and removal of covers. To estimate  
waterbox cover areas, refer to the following figure.  
Field-installed accessories  
Remote enhanced display is a remotely mounted  
indoor 40-character per line, 16-line display panel for unit  
monitoring and diagnostics.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD-SUPPLIED AND FIELD-INSTALLED INSULATION  
DISCHARGE PIPING  
INSULATION NEEDED (HEAT  
MACHINE UNITS ONLY)  
EVAPORATOR WATERBOX  
INSULATION NEEDED  
EVAPORATOR WATERBOX  
INSULATION NEEDED  
CONDENSER WATERBOX  
INSULATION NEEDED (HEAT  
MACHINE UNITS ONLY)  
CONDENSER WATERBOX  
INSULATION NEEDED (HEAT  
MACHINE UNITS ONLY)  
EVAPORATOR WATERBOX  
INSULATION NEEDED  
NOTES:  
a30-4686  
1. Field-installed insulation for standard units shown in light gray.  
2. Field-installed insulation for heat machine units shown in dark gray.  
3. Back of the unit shown.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
30XW UNIT DIMENSIONS  
a30-4745  
SEE NIH EVAPORATOR  
DETAIL FOR NOZZLE  
MEASUREMENTS  
EVAPORATOR  
SUCTION  
END  
DISCHARGE  
END  
CONDENSER  
SEE NIH CONDENSER  
DETAIL FOR NOZZLE  
MEASUREMENTS  
MLV (OPTIONAL)  
MLV (OPTIONAL)  
LEGEND  
STANDARD 30XW UNIT DIMENSIONS  
MLV — Minimum Load Valve  
MWB — Marine Waterbox  
NIH — Nozzle-In-Head  
MOUNTING LOCATION WEIGHT, lb [kg]  
DIMENSIONS (ft-in. [mm])  
30XW UNIT  
SIZE  
OPERATING  
WEIGHT, lb [kg]  
1
2
3
4
A
B
C
SSV — Suction Service Valve  
325  
350  
400  
14,319 [6495]  
14,515 [6584]  
14,759 [6695]  
3734 [1694] 3828 [1736] 3337 [1514] 3420 [1551] 6-3/8 [1837] 6-3/8 [1837]  
3785 [1717] 3880 [1760] 3383 [1535] 3467 [1573] 6-3/8 [1837] 6-3/8 [1837]  
3848 [1745] 3946 [1790] 3439 [1560] 3526 [1599] 6-3/8 [1837] 6-3/8 [1837]  
/
8
/
8
/
8
[9.53]  
[9.53]  
[9.53]  
3
3
3
NOTES:  
1. Weights shown for standard chiller (2 pass with NIH, victaulic waterboxes).  
2. See page 14 for unit mounting locations.  
30XW UNIT AND WATERBOX DIMENSIONS  
MAX UNIT OPERATING WEIGHT lb [kg]  
WATERBOX  
NOZZLE  
TYPE  
D
E
F
CONNECTIONS PASSES  
(EVAP/COND)  
ft-in. [mm]  
ft-in. [mm]  
ft-in. [mm]  
325  
350  
400  
Victaulic  
Flange  
Victaulic  
Flange  
Victaulic  
Flange  
Victaulic  
Flange  
Victaulic  
Flange  
Victaulic  
Flange  
Victaulic  
Flange  
Victaulic  
Flange  
Flange  
Flange  
Flange  
Flange  
13-33/4 [4057]  
13-91/16 [4193]  
14,319 [6495]  
14,651 [6646]  
14,498 [6576]  
14,739 [6685]  
14,489 [6572]  
14,746 [6689]  
14,668 [6653]  
14,834 [6729]  
14,319 [6495]  
14,651 [6646]  
14,498 [6576]  
14,739 [6685]  
14,489 [6572]  
14,746 [6689]  
14,668 [6653]  
14,834 [6729]  
14,828 [6726]  
15,223 [6905]  
15,244 [6915]  
15,581 [7067]  
14,515 [6495]  
14,847 [6646]  
14,694 [6576]  
14,935 [6685]  
14,685 [6572]  
14,768 [6689]  
14,864 [6653]  
15,030 [6729]  
14,515 [6495]  
14,847 [6646]  
14,694 [6576]  
14,935 [6685]  
14,685 [6572]  
14,768 [6689]  
14,864 [6653]  
15,030 [6729]  
15,024 [6726]  
14,768 [6896]  
15,440 [6894]  
15,777 [7063]  
14,759 [6695]  
15,091 [6845]  
14,938 [6776]  
15,179 [6885]  
14,929 [6772]  
15,012 [6809]  
15,108 [6853]  
15,274 [6928]  
14,759 [6695]  
15,091 [6845]  
14,938 [6776]  
15,179 [6885]  
14,929 [6772]  
15,012 [6809]  
15,108 [6853]  
15,274 [6928]  
15,268 [6925]  
15,012 [6809]  
15,684 [7114]  
16,021 [7267]  
NIH/NIH  
NIH/MWB  
MWB/NIH  
MWB/MWB  
NIH/NIH  
Same Ends  
3-113/8 [1210]  
6-611  
/16 [1999]  
13-115/8 [4258]  
2 Pass  
13-65/16 [4123]  
14-47/16 [4380]  
14-23/16 [4323]  
NIH/MWB  
MWB/NIH  
MWB/MWB  
14-615  
14-213  
/
/
16 [4443]  
16 [4339]  
14-83/16 [4475]  
14-1011  
16 [4539]  
14-55/8 [4410]  
Opposite Ends  
3-113/8 [1210]  
6-611  
/16 [1999]  
/
NIH/NIH  
NIH/MWB  
MWB/NIH  
MWB/MWB  
1 or  
3 Pass  
14-1011  
/16 [4539]  
NOTES:  
1. Operating weight includes weight of water, refrigerent, and oil.  
2.  
3. Dimensions shown in ft-in. [mm] unless noted.  
4. The recommended service clearance around the machine is 3 ft [914.4 mm].  
Denotes center of gravity.  
5. Victaulic nozzles are standard on all units. A flow switch can be factory-installed in evaporator inlet victaulic nozzle.  
6. Maximum fluid side pressure of condenser or evaporator is 150 psig [1034 kPa] (standard) or 300 psig [2068 kPa] (optional).  
7. Operating weight includes weight of water, refrigerant, and oil.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a30-4755  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions (cont)  
30XW UNIT DIMENSIONS (cont)  
WATERBOX FLANGE DETAIL  
MOUNTING  
LOCATIONS  
a30-4688  
a30-4725  
a30-4751  
a30-4749  
NIH EVAPORATOR  
NIH CONDENSER  
DISCHARGE  
DISCHARGE  
DISCHARGE  
DISCHARGE  
DISCHARGE  
SUCTION  
SUCTION  
SUCTION  
SUCTION  
SUCTION  
CONNECTION SIZE  
UNIT  
CONNECTION SIZE  
Flange Victaulic  
NUMBER OF  
A
B
NUMBER OF  
A
B
UNIT  
PASSES  
in. (mm)  
in. (mm)  
PASSES  
in. (mm)  
in. (mm)  
Flange  
Victaulic  
61/16 (154)  
61/16 (154)  
6
6
6
8
8
8
2
1
63/4 (171) 63/4 (171)  
0 (0) 0 (0)  
6
6
8
8
2
1
3
30XW325-400  
30XW325-400  
0 (0)  
61/16 (154)  
0 (0)  
61/16 (154)  
a30-4750  
a30-4752  
MARINE CONDENSER  
MARINE EVAPORATOR  
DISCHARGE  
DISCHARGE  
DISCHARGE  
DISCHARGE  
DISCHARGE  
SUCTION  
SUCTION  
SUCTION  
SUCTION  
SUCTION  
CONNECTION SIZE  
CONNECTION SIZE  
Flange Victaulic  
NUMBER OF  
PASSES  
A
B
NUMBER OF  
PASSES  
A
B
UNIT  
UNIT  
in. (mm)  
in. (mm)  
in. (mm) in. (mm)  
Flange  
Victaulic  
2
1
3
71/2 (191)  
71/2 (191)  
6
6
6
6
2
1
73/8 (187) 73/8 (187)  
6
6
6
30XW325-400  
30XW325-400  
0 (0)  
71/2 (191)  
0 (0)  
71/2 (191)  
0 (0)  
0 (0)  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection procedure  
Carrier’s packaged selection program provides quick,  
easy selection of Carrier’s water-cooled chillers. The pro-  
gram considers specific temperature, fluid and flow  
requirements among other factors such as fouling and alti-  
tude corrections.  
Before selecting a chiller, consider the following points:  
Leaving water (fluid) temperature (LWT)  
• The LWT must be at least 40 F (4.4 C) or greater.  
• If the LWT requirement is greater than 60 F (15.5 C), a  
mixing loop is required.  
Evaporator pressure drop:  
• A high evaporator pressure drop can be expected when  
the evaporator delta-T is low. A mixing loop can help to  
alleviate this situation.  
• The three-pass evaporator option is recommended to  
increase performance when the evaporator delta T is  
high. This is particularly helpful with brine applications.  
Condenser pressure drop:  
• A high condenser pressure drop can be expected when  
the condenser delta-T is low. A one-pass condenser can  
help lower pressure drop.  
Entering water (fluid) temperature (EWT)  
Series chillers:  
• If the EWT requirement is greater than 70 F (21.1 C), a  
mixing loop is required. The EWT should not exceed  
70 F (21.1 C) for extended operation. Pulldown can be  
accomplished from 95 F (35 C).  
• One-pass heat exchangers can help lower pressure  
drop when heat exchangers are placed in series.  
Water quality, fouling factor:  
• Poor water quality can increase the required evaporator  
fouling factor.  
• Higher than standard fouling factors lead to lower  
capacity and higher input kW from a given chiller size  
compared to running the same application with better  
water quality (and lower fouling factors).  
Temperature reset:  
• Return water (standard)  
• Outside air temperature (standard)  
• Space temperature (accessory sensor required)  
• 4 to 20 mA (requires an energy management module)  
Demand limit:  
• 2-step (requires an energy management module)  
• 4 to 20 mA (requires an energy management module)  
• CCN Loadshed  
Evaporator flow rate or evaporator delta-T:  
• The evaporator delta-T (EWT – LWT) must fall between  
5 and 20° F (2.8 and 11.1° C) while still meeting the  
maximum entering requirements.  
• For larger or smaller delta-T applications, a mixing loop  
is required. If the evaporator flow is variable, the rate of  
change of flow should not exceed 10% per minute.  
The loop volume in circulation must equal or exceed  
3 gallons per nominal ton (3.2 L per kW) of cooling for  
temperature stability and accuracy in normal air condi-  
tioning applications. In process cooling applications,  
there should be 6 to 10 gallons per ton (6.5 to 10.8 L  
per kW). To achieve this loop volume, it is often neces-  
sary to install a tank in the loop. The tank should be baf-  
fled to ensure there is no stratification, and that water  
(or brine) entering the tank is adequately mixed with liq-  
uid in the tank. See Water Loop Volume in the Applica-  
tion Data section.  
Performance data  
EVAPORATOR AND CONDENSER FLOW RATES  
EVAPORATOR  
CONDENSER  
NOMINAL  
Leaving Fluid/Entering Fluid  
Minimum Entering Maximum Leaving  
Fluid  
Fluid  
Minimum  
Maximum  
Evaporator  
Condenser  
40 F (4.4 C)/  
45 F (7.2 C)  
60 F (15.6 C)/  
70 F (21.1 C)  
30XW UNIT  
65 F (18.3 C)  
118 F (47.8 C)*  
Minimum  
Flow Rate  
Maximum  
Flow Rate  
Minimum  
Flow Rate  
Maximum  
Flow Rate  
Nominal  
Flow Rate  
Nominal  
Flow Rate  
GPM  
L/s  
GPM  
1481  
3126  
987  
1557  
3287  
1038  
1751  
3696  
1167  
L/s  
93.4  
197.2  
62.3  
98.2  
207.4  
65.5  
110.4  
233.1  
73.6  
GPM  
494  
987  
519  
1038  
584  
1167  
L/s  
31.1  
62.3  
32.7  
65.5  
36.8  
73.6  
GPM  
1974  
3290  
2076  
3460  
2334  
3890  
L/s  
124.5  
207.6  
131.0  
218.3  
147.3  
245.4  
GPM  
L/s  
GPM  
L/s  
Two pass  
411  
790  
247  
433  
830  
260  
486  
934  
292  
25.9  
49.8  
15.6  
27.3  
52.4  
16.4  
30.7  
58.9  
18.4  
790  
790  
790  
830  
830  
830  
934  
934  
934  
49.8  
49.8  
49.8  
52.4  
52.4  
52.4  
58.9  
58.9  
58.9  
987  
987  
1038  
1038  
1167  
1167  
62.3  
62.3  
65.5  
65.5  
73.6  
73.6  
325  
350  
400  
One pass  
Three pass  
Two pass  
One pass  
Three pass  
Two pass  
One pass  
Three pass  
*Maximum condenser fluid temperature shown for standard condensing  
option. Heat machine option may have leaving fluid temperatures up to  
140 F (60 C).  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
30XW325-400 EVAPORATOR MARINE WATERBOX  
(kPa) ft wg  
(119.4) 40.00  
3 pass  
(104.4) 35.00  
(89.5) 30.00  
(74.6) 25.00  
(59.7) 20.00  
(44.8) 15.00  
(29.8) 10.00  
(14.9) 5.00  
(0) 0.00  
1 pass  
2 pass  
0
(0)  
500  
(31.5)  
1000  
(63.1)  
1500  
(94.6)  
2000  
(126.2)  
2500  
(157.7)  
3000 gpm  
(189.3) (L/s)  
Evaporator Flow Rate  
NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over  
the entire range of evaporator water flow rates represented.  
A30-4691  
30XW325-400 EVAPORATOR NIH FLANGE  
(kPa) ft wg  
(119.4) 40.00  
1 pass  
3 pass  
(104.4) 35.00  
2 pass  
(89.5) 30.00  
(74.6) 25.00  
(59.7) 20.00  
(44.8) 15.00  
(29.8) 10.00  
(14.9) 5.00  
(0) 0.00  
gpm  
(L/s)  
0
(0)  
500  
(31.5)  
1000  
(63.1)  
1500  
(94.6)  
2000  
(126.2)  
Evaporator Flow Rate  
LEGEND  
NIH — Nozzle-In-Head  
NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over the  
entire range of evaporator water flow rates represented.  
A30-4692  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30XW325-400 EVAPORATOR NIH VICTAULIC  
(kPa) ft wg  
(119.4) 40.00  
3 pass  
(104.4) 35.00  
(89.5) 30.00  
(74.6) 25.00  
(59.7) 20.00  
(44.8) 15.00  
(29.8) 10.00  
(14.9) 5.00  
(0) 0.00  
1 pass  
2 pass  
0
(0)  
500  
(31.5)  
1000  
(63.1)  
1500  
(94.6)  
2000  
(126.2)  
2500  
(157.7)  
3000 gpm  
(189.3) (L/s)  
Evaporator Flow Rate  
LEGEND  
NIH — Nozzle-In-Head  
A30-4693  
NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over the  
entire range of evaporator water flow rates represented.  
30XW325-400 CONDENSER MARINE WATERBOX  
(kPa) ft wg  
(119.4) 40.00  
(104.4) 35.00  
1 pass  
2 pass  
(89.5) 30.00  
(74.6) 25.00  
(59.7) 20.00  
(44.8) 15.00  
(29.8) 10.00  
(14.9) 5.00  
(0) 0.00  
0
500  
1000  
1500  
2000  
2500  
3000  
3500 gpm  
(0)  
(31.5)  
(63.1)  
(94.6) (126.2) (157.7) (189.3) (220.8) (L/s)  
Condenser Flow Rate  
NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over the  
entire range of condenser water flow rates represented.  
A30-4694  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance data (cont)  
30XW325-400 CONDENSER NIH FLANGE  
(kPa) ft wg  
(119.4) 40.00  
(104.4) 35.00  
(89.5) 30.00  
(74.6) 25.00  
(59.7) 20.00  
(44.8) 15.00  
(29.8) 10.00  
(14.9) 5.00  
(0) 0.00  
2 pass  
1 pass  
0
(0)  
500  
(31.5)  
1000  
(63.1)  
1500  
(94.6)  
2000  
(126.2)  
2500 gpm  
(157.7) (L/s)  
Condenser Flow Rate  
LEGEND  
NIH — Nozzle-In-Head  
A30-4695  
NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over the entire  
range of evaporator water flow rates represented.  
30XW325-400 CONDENSER NIH VICTAULIC  
(kPa) ft wg  
(119.4) 40.00  
(104.4) 35.00  
1 pass  
2 pass  
(89.5) 30.00  
(74.6) 25.00  
(59.7) 20.00  
(44.8) 15.00  
(29.8) 10.00  
(14.9) 5.00  
(0) 0.00  
0
500  
1000  
1500  
2000  
2500  
3000  
3500 gpm  
(0)  
(31.5)  
(63.1)  
(94.6) (126.2) (157.7) (189.3) (220.8) (L/s)  
LEGEND  
NIH — Nozzle-In-Head  
Condenser Flow Rate  
A30-4696  
NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over the  
entire range of evaporator water flow rates represented.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
point to a warmer temperature thereby reducing compres-  
sor power usage and saving energy. Three reset options  
are offered. With any chilled water reset application, hu-  
midity control should be considered since higher coil tem-  
peratures will reduce latent capacity. For details on apply-  
ing a reset option, refer to the Controls, Start-Up, Opera-  
tion, Service and Troubleshooting guide.  
Return fluid temperature reset — This feature  
increases LWT set point as return (entering) fluid tempera-  
ture decreases (indicating load decrease). This option may  
be used where return fluid temperature provides accurate  
load indication. No additional hardware is required.  
Microprocessor  
The chiller microprocessor controls overall unit operation  
and controls a number of processes simultaneously. These  
processes include internal timers, reading inputs, analog to  
digital conversions, display control, diagnostic control, out-  
put relay control, demand limit, capacity control, head  
pressure control, and temperature reset. Some processes  
are updated almost continuously, others every 2 to 3 sec-  
onds, and some every 30 seconds. The microprocessor  
routine is started by switching the emergency ON-OFF  
switch to the ON position.  
Control sequence  
Outdoor-air temperature reset  
This feature  
Pre-start — After control switches on, the prestart takes  
place. The microprocessor checks itself, and if configured,  
energizes the evaporator and condenser pumps to the  
internal (or CCN) time schedule (or input occupied signal  
from an external system) and waits for temperature to  
stabilize.  
Start-up — The chiller will receive a call for cooling when  
chilled fluid temperature increases above the set point plus  
a dead band, or if an override start command is received.  
If flow has been proven, the first compressor starts 1 to 3  
minutes after the call for cooling. The controlled pulldown  
feature limits compressor loading on start up to reduce  
demand on start up and unnecessary compressor usage.  
Capacity control — On the first call for cooling, the  
microprocessor starts the compressor on the lead circuit.  
The microprocessor maintains leaving fluid temperature  
set point through intelligent positioning of the slide valve.  
As the load increases above the compressor's capacity, the  
compressor on the lag circuit is started and both compres-  
sors are staged together.  
Maintaining set point — The control monitors entering  
and leaving chilled water temperature to anticipate  
changes in cooling load. The speed at which capacity is  
added or reduced is controlled by temperature deviation  
from set point and rate of temperature change of the  
chilled fluid. The basic logic for determining when to add  
or remove capacity is a time band integration of deviation  
from set point plus rate of change of leaving fluid tempera-  
ture. When leaving-fluid temperature is close to the set  
point and slowly moving closer, logic prevents additional  
capacity. Accuracy depends on loop volume, loop flow  
rate, load and condenser water temperatures.  
Return fluid temperature compensation — No adjust-  
ment for cooling range or evaporator flow rate is required  
because the control automatically compensates for cooling  
range by measuring both return fluid temperature and leav-  
ing fluid temperature.  
Low temperature override — This feature prevents  
LWT (leaving water temperature) from overshooting the  
set point to prevent nuisance low suction temperature  
trips.  
High temperature override — This feature allows the  
chiller to add capacity quickly during rapid load variations.  
Temperature reset (chilled water reset) When  
latent loads in the conditioned space are reduced, it may be  
possible to reset the leaving chilled water temperature set  
increases LWT set point as outdoor ambient temperatures  
decreases (indicating load decrease). This reset should only  
be applied where outdoor ambient temperature is an indi-  
cation of load. A field-installed thermistor is required.  
Space temperature reset — This feature increases the  
LWT as space temperature decreases (indicating load  
decrease). This reset should only be applied where space  
temperature is an indication of load. A field-supplied ther-  
mistor is required.  
Minimum load control — The main base board (MBB)  
responds to the supply chilled water temperature to match  
cooling load requirements and controls the minimum load  
control valve. The minimum load control valve allows hot  
gas to pass directly into the evaporator circuit permitting  
the unit to operate at lower loads with less compressor  
cycling. Minimum load control should be given consider-  
ation when operation is anticipated below the minimum  
unloading step.  
Pull down control — If pulldown control has been  
selected (adjustable setting), no additional capacity is added  
as long as the difference between fluid temperature and the  
set point is greater than 4 F (2.2 C) and rate of change in  
leaving water temperature is greater than the 90 seconds  
since the last capacity change, compressors will continue  
to run unless a safety device trips. This prevents rapid  
cycling and also helps return oil during short operating  
periods.  
Maximum operating pressure control — If the enter-  
ing fluid temperature is 95 F (35 C) and the saturated suc-  
tion temperature is 50 F (10 C) or higher, the maximum  
operating pressure (MOP) feature limits the suction to keep  
the chiller online. The control automatically starts the  
chiller in the unloaded state to eliminate the potential of  
compressor overload due to high head pressure or low suc-  
tion pressure.  
Equalized run time — The controller will equalize run  
time on each circuit through the lead / lag feature. If a cir-  
cuit becomes disabled, the control will automatically set the  
active circuit to lead, keeping the chiller online at a reduced  
capacity.  
Sensors — Thermistors are used to control temperature  
sensing inputs to the microprocessor. No additional ther-  
mistor sensors are required for leaving chilled water tem-  
perature, optional return water reset, or outdoor air reset.  
The following sensors can be used on 30XW units:  
• Evaporator leaving fluid temperature (T1)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls (cont)  
• Evaporator entering fluid temperature (T2)  
• Suction gas temperature (T4 - Circuit A, T7 - Circuit B)  
• Economizer gas temperature (T5 - Circuit A, T11 -  
Circuit B) (sizes 350, 400 only)  
Loss of flow protection — This feature will shut off the  
chiller if the detected flow is below the configured mini-  
mum flow rate. Thermal dispersion flow switches are  
installed in 30XW chillers to confirm evaporator flow.  
Sensor failures — The microprocessor monitors tem-  
perature and pressure sensors to ensure readings are  
within the expected range. Loss of communication to a  
sensor or readings outside of the expected range will  
prompt corrective action.  
Other safeties — Other safety features include electric  
overload, thermal overload protection, oil pressure, loss of  
refrigerant charge, loss of phase protection, reverse  
rotation protection (prevents compressor start), current  
imbalance, and ground current.  
Demand limit function — This function can be used to  
limit the total power draw of the chiller to a user-defined  
set point. The optional energy management module is  
required and can provide either 2-step or 4 to 20 mA  
demand limit. This optional electronic board interfaces  
with the microprocessor to control the number of com-  
pressors operating and their operating capacity to limit  
power consumption to the user specified value.  
The microprocessor can control the number of compres-  
sors operating and their operating capacity to limit power  
consumption to the user specified value.  
Diagnostics — The microprocessor includes a service  
test feature that displays the condition of each sensor and  
switch in the chiller and allows the observer to check for  
proper operation of the compressors. Refer to the Con-  
trols, Start Up, Operation, Service and Troubleshooting  
guide for further information.  
Default settings — To facilitate quick start-ups, 30XW  
chillers are pre-configured with a default setting that  
assumes stand-alone operation with a 44 F (6.6 C) chilled  
water set point. Configuration settings will be based on any  
options or accessories included with the unit at the time of  
manufacturing. Date and time are set to U.S.A. Eastern  
Time zone and will need reconfiguring based on location  
and local time zone. If operation based on occupancy  
schedule is desired, the schedule must be set during  
installation.  
Additional information — Detailed information on con-  
trols and operation is available in the Controls, Start-Up,  
Operation, Service and Troubleshooting guide included  
with each unit. Packaged Service Training programs are  
also available. Contact your local Carrier representative for  
more information.  
• Space temperature (T8)  
• Discharge gas temperature (T9 - Circuit A, T10 -  
Circuit B)  
• Condenser entering fluid temperature (T12)  
• Condenser leaving fluid temperature (T13)  
• Compressor motor temperature  
There are 3 (size 325) or 4 (sizes 350, 400) refrigerant  
pressure transducers used in each circuit for sensing suc-  
tion, discharge, oil, and economizer (sizes 350, 400) pres-  
sure. The microprocessor uses these inputs to control  
capacity.  
• Saturated condensing temperature  
• Evaporator saturation temperature  
Electronic expansion valve (EXV) — The EXV con-  
trols refrigerant flow to the evaporator for different operat-  
ing conditions by varying an orifice size to increase or  
decrease the flow area through the valve based on micro-  
processor input. The orifice is positioned by a stepper  
motor through approximately 3,600 discrete steps and is  
monitored every 3 seconds.  
Safeties  
Abnormal conditions — All control safeties in the chiller  
operate through compressor protection board, control  
relays or the chiller microprocessor. Loss of feedback sig-  
nal to the MBB will cause the compressor(s) to shut down.  
For other safeties, the microprocessor makes appropriate  
decision to shut down a compressor due to a safety trip or  
bad sensor reading and displays the appropriate failure  
code on the display. Chiller holds in safety mode until  
reset; it then reverts to normal control when the unit is  
reset.  
Low-pressure safety — This safety will shut down the  
chiller and display the appropriate alarm code if the system  
pressure drops below configured minimums.  
High-pressure safety — This safety will shut down the  
chiller and display the appropriate alarm code if the com-  
pressor discharge pressure increases to 185 psig for stan-  
dard condenser units or 250 psig for high condensing or  
heat machine units.  
Compressor anti-cycling — This feature monitors com-  
pressor starts to limit compressor cycling during periods of  
low load.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical control wiring schematics  
30XW UNIT CONTROL WIRING SCHEMATIC  
a30-4697  
LEGEND  
AWG  
American Wire Gage  
Circuit Breaker  
NEC  
PMP  
PMPI  
TB  
National Electrical Code  
Chilled Water Pump  
Chilled Water Pump Interlock  
Terminal Block  
CB  
COM  
EMM  
Communication Port  
Energy Management Module  
Equipment Ground  
Factory-Installed Option  
Minimum Load Valve  
EQUIP GND  
FIOP  
Field Power Wiring  
Field Control Wiring  
Factory-Installed Wiring  
MLV  
NOTES:  
6. For control of chilled water pumps, a set of normally open contacts rated  
for dry circuit application must be supplied from field-supplied pump  
starter relay. Connect contacts directly to connector at main base board  
channel 18.  
7. Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load  
allowed for the alarm relay is 10-va sealed, 25-va inrush at 24-v. Field  
power supply is not required.  
8. Make appropriate connections to TB6 as shown for energy management  
board options. The contacts for occupancy override, demand limit, and  
ice done options must be rated for dry circuit application capable for han-  
dling a 24-vac load up to 50 mA.  
9. Terminal blocks TB5 and TB6 are located in the display panel box for all  
units. Refer to certified dimensional drawing for each unit to get the exact  
locations.  
10. Refer to certified dimensional drawings for exact locations of the main  
power and control power entrance locations.  
1. Factory wiring is in accordance with UL 1995 standards. Field modifica-  
tions or additions must be in compliance with all applicable codes.  
2. Wiring for main field supply must be rated 75C minimum. Use copper for  
all units. Incoming wire size range for the terminal block is #4 AWG to  
500 kcmil for single point power (two conductors per phase). Incoming  
wire size range for the terminal blocks for dual point power option is  
#4 AWG to 500 kcmil for single point power (one conductor per phase).  
Incoming wire size range for 200/300-v models is 3/0 to 500 kcmil for sin-  
gle point power (one conductor per phase).  
3. Terminals 9 and 10 of TB5 are for field external connections for remote  
on-off. The contacts must be rated for dry circuit application capable of  
handling a 24-vac load up to 50 mA.  
4. Terminals 1 and 2 of TB5 are for external connections of chilled water  
pump interlock. The contacts must be rated for dry circuit application  
capable of handling a 24-vac load up to 50 mA.  
5. Terminals 11 and 13 of TB5 are for control of chilled water pump 1  
(PMP 1) starter. Terminals 15 and 13 of TB5 are for control of chilled  
water pump 2 (PMP 2) starter. Remove factory-installed jumper when  
using pump interlock. The maximum load allowed for the chilled water  
pump relay is 5-va sealed, 10-va inrush at 24-v. Field power supply is not  
required.  
11. For control of condenser pump, connect field-supplied relay (max 5-va  
sealed, 10-va inrush at 24-v) directly to connector at main base board  
channel 22.  
12. For head pressure control option, 0-10-vdc signal wires are factory-  
installed (violet and brown) from HGBP/COND board channel 9. Refer to  
controls manual for application with field-supplied water regulating valve.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application data  
Unit storage  
Evaporator flow range  
Store chiller and starter indoors, protected from construc-  
tion dirt and moisture. Inspect under shipping tarps, bags,  
or crates to be sure water has not collected during transit.  
Keep protective shipping covers in place until machine is  
ready for installation. Assure that the inside of the protec-  
tive cover meets the following criteria:  
For minimum and maximum evaporator flow rates please  
see the Evaporator and Condenser Flow Rates table. A  
high flow rate is generally limited by the maximum pres-  
sure drop that can be tolerated by the unit. The 30XW  
chillers are designed for a full load temperature rise of 5 to  
20 F (2.8 to 11.1 C). See the Carrier selection program for  
pressure drop values and performance.  
• Temperature is between 40 F (4.4 C) and 120 F  
(48.9 C)  
Minimum evaporator flow  
• Relative humidity is between 10% and 80% (non-  
condensing)  
When system design conditions require a lower flow (or  
higher temperature rise) than the minimum allowable evap-  
orator flow rate, please follow the recommendations  
below.  
• Multiple smaller chillers may be applied in series, each  
providing a portion of the design temperature rise.  
• Try increasing the number of passes in the evaporator  
(1, 2, or 3 passes available).  
• Evaporator fluid may be recirculated to raise the flow  
rate to the chiller. The mixed temperature entering the  
evaporator must be maintained to a minimum of at least  
5
°
F (2.8 
°
C) above the leaving chilled fluid tempera-  
ture and a maximum of no more than 20 F (11.1 C)  
above the leaving chilled fluid temperature.  
Chiller location  
Unit should be located indoors on a level surface in an area  
with temperatures between 50 F (10 C) and 104 F (40 C).  
Clearance should be provided around the unit for service  
and local code requirements. See dimensional drawings for  
specific unit clearance requirements. Consideration should  
be given to using rubber-in-shear pads. For applications  
other than ground to slab, it is recommended spring isola-  
tors are used to minimize structure borne transmission.  
Acoustic consideration should be given near sound sensi-  
tive areas.  
Relief valve vent lines:  
1. Vent per local code requirements.  
NOTE: Recirculation flow is shown below.  
2. Each chiller has 2 relief valves on the evaporator, 2  
on the condenser and one relief valve on each com-  
pressor discharge line.  
Maximum evaporator flow  
RECIRCULATION FLOW  
Strainers  
CHILLER EVAPORATOR  
A screen strainer with minimum screen size of 20 mesh  
must be installed within 10 ft (3 m) of the inlet pipe con-  
nection to both the evaporator and condenser to prevent  
debris from damaging internal tubes of the evaporator. The  
pump strainer shall not be used to meet this requirement.  
a30-4698  
Oversizing chillers  
Oversizing chillers by more than 15% at design conditions  
should be avoided as the system operating efficiency is  
adversely affected (resulting in greater or excessive electri-  
cal demand). When future expansion of equipment is antic-  
ipated, install a single chiller to meet present load  
requirements and add a second chiller to meet the addi-  
tional load demand. It is also recommended that 2 smaller  
chillers be installed where operation at minimum load is  
critical. The operation of a smaller chiller loaded to a  
greater percentage over minimum is preferred to operating  
a larger chiller at or near its minimum recommended value.  
Operation at its minimum load should only be done inter-  
mittently, not for long periods of time. Minimum load con-  
trol should not be used as a means to allow oversizing  
chillers.  
The maximum evaporator flow (approximately 5 
°
F  
(2.8
°
C) rise results in a practical maximum pressure drop  
through the evaporator. Optional marine waterboxes may  
help reduce pressure drop by a small amount. If this is  
insufficient, a return fluid may bypass the evaporator to  
keep the pressure drop through the evaporator within  
acceptable limits. This permits a higher delta T with lower  
fluid flow through the evaporator and mixing after the  
evaporator.  
NOTE: Bypass flow is shown below.  
BYPASS FLOW  
CHILLER EVAPORATOR  
Evaporator water temperature  
Maximum leaving fluid temperature for the unit is 60 F  
(15.5 C). The unit can start and pull down with up to 95 F  
(35 C) entering fluid temperature. For sustained operation,  
it is recommended the fluid temperature not exceed 70 F  
(21.1 C). Water flowing through the evaporator should  
never exceed 100 F (37.8 C). Minimum leaving water tem-  
perature is 40 F (4.4 C).  
a30-4699  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
concentration of at least 15
°
F (8.3
°
C) below the leaving  
fluid temperature set point. If chiller fluid lines are in an  
area where ambient conditions fall below 34 F (1.1 C), it is  
recommended that an antifreeze solution be added to pro-  
tect the unit and fluid piping to a temperature 15 
°
F  
(8.3
°
C) below the lowest anticipated temperature. For  
corrections to performance, refer to the chiller selection  
program.  
NOTE: Use only antifreeze solutions approved for heat  
exchanger duty. Use of automotive antifreeze is not recom-  
mended because of the fouling that can occur once their  
relatively short-lived inhibitors break down.  
Variable evaporator flow rates  
Variable flow rates may be applied to a standard chiller.  
The unit will, however, attempt to maintain a constant  
leaving fluid temperature. In such cases minimum flow  
must be in excess of minimum flow given in the  
Evaporator and Condenser Flow Rates table, and mini-  
mum loop volume must be in excess of 3 gallons per ton  
(3.21 L per kW). Combined flow rate and change in load  
must not change by more than 10% per minute. Additional  
loop volume may be necessary to ensure fluid is not quickly  
recirculated back to the chiller before the chiller has  
adjusted to the previous change in flow rate and load  
condition.  
Multiple chillers  
Water loop volume  
Where multiple chillers are required, or where standby  
capability is desired, chillers may be installed in parallel.  
Units may be of the same or different sizes. However,  
evaporator flow rates must be balanced according to the  
recommendations of each chiller to ensure proper flow.  
Unit software is capable of controlling two units as a sin-  
gle plant. Refer to the Controls, Start-Up, Operation, Ser-  
vice and Troubleshooting guide for further details.  
The loop volume in circulation must equal or exceed 3 gal.  
per nominal ton (3.2 L per kW) of cooling for temperature  
stability and accuracy in normal air-conditioning applica-  
tions. In process cooling applications, there should be 6 to  
10 gallons per ton (6.5 to 10.8 L per kW). To achieve this  
loop volume, it is often necessary to install a tank in the  
loop. The tank should be baffled to ensure there is no strat-  
ification, and that water (or brine) entering the tank is ade-  
quately mixed with liquid in the tank. See Tank installation  
drawing.  
Dual chiller control  
The chiller on board controller allows 2 chillers (piped in  
parallel or series) to operate as a single chilled water plant  
with standard control functions coordinated through the  
master chiller controller. This feature requires a communi-  
cation link between the 2 chillers. There are several advan-  
tages to this type of control:  
TANK INSTALLATION  
• Redundancy (multiple circuits)  
• Better low load control (lower tonnage capability)  
• Lower rigging lift weights (2 machines rather than one  
large machine)  
BAD  
GOOD  
• Chiller lead-lag operation (evens the wear between the  
two machines)  
Parallel chiller operation  
Parallel chiller operation is the recommended option for  
dual chiller control. In this case, each chiller must control  
its own dedicated pumps or isolation valves. Balancing  
valves are recommended to ensure the proper flow to each  
chiller. Two field-supplied and installed dual chiller leaving  
water temperature sensors are required (one for each mod-  
ule) for this function to operate properly.  
Consider adding additional isolation valves to isolate  
each chiller to allow for service on the machine, and still  
allow for partial capacity from the other chiller.  
BAD  
GOOD  
a30-3185  
Evaporator fouling factor  
The fouling factor used to calculate tabulated ratings is  
0.0001 sq ft hr °F/Btu (0.000018 sq m ⋅ ° C/W). As  
fouling factor is increased, both unit capacity and EER  
(Energy Efficiency Ratio) decrease. The impact of the foul-  
ing factor on performance varies significantly with chiller  
size and application conditions. Ratings must be deter-  
mined by the Carrier selection program.  
Series chiller operation  
Series chiller operation is an alternate control method sup-  
ported by the chiller control system. Certain applications  
might require that two chillers be connected in series. For  
nominal 10 F (5.6 C) evaporator ranges, use the one-pass  
heat exchanger options to reduce fluid side pressure drop.  
Use the standard pass arrangement for low flow, high tem-  
perature rise applications. Two field-supplied and installed  
dual chiller leaving water temperature sensors are required  
(one for each module) for this function to operate properly.  
Condenser minimum flow rate  
The minimum condenser flow rate is shown in the Mini-  
mum and Maximum Condenser Flow Rate Table. If the  
condenser flow rate is below the minimum rate shown, try  
increasing the number of condenser passes (1 or 2 pass  
available).  
Evaporator and condenser freeze protection  
The solution concentration must be sufficient to protect the  
chilled water loop to a freeze protection (first crystals)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application data (cont)  
Consider adding additional piping and isolation valves to  
isolate each chiller to allow for service on the machine, and  
still allow for partial capacity from the other chiller.  
shed to keep electricity demand below a prescribed maxi-  
mum level. Typically, this happens on hot days when air  
conditioning is most needed. The energy management  
module (EMM) option can be added to accomplish this  
reduction. Demand may be limited on the unit by resetting  
water temperature, or by unloading the chiller to a given  
predetermined percentage of the load. Demand limit may  
also be driven by an external 4 to 20 mA signal. These fea-  
tures require a signal from an intelligent central control.  
Duty cycling — Duty cycling will cycle an electrical load  
at regular intervals regardless of need. This reduces the  
electrical demand by "fooling" demand measuring devices.  
Duty cycling of the entire compressor is NOT recom-  
mended since motor windings and bearing life will suffer  
from constant cycling.  
Even if evaporators are piped in series, parallel con-  
denser piping should be considered on constant speed  
chillers to maximize capacity and efficiency while minimiz-  
ing condenser pressure drop and saturated condensing  
temperatures. If the condensers are piped in series, ensure  
that the leaving fluid temperature does not exceed 122 F  
(50 C) for standard units, or 140 F (60 C) for high con-  
densing or heat machine condensers.  
Electric utility interests  
Energy management Use of energy management  
practices can significantly reduce operating costs, espe-  
cially during off-peak modes of operation. Demand limiting  
and temperature reset are two techniques for accomplish-  
ing efficient energy management. See Demand Limiting  
(also called load shedding) section below for further details.  
Remote on-off control — Remote on-off control may be  
applied by hard-wired connection (see the Controls,  
Start-Up, Operation, Service and Troubleshooting guide)  
or by connection to the Carrier Comfort Network® (CCN)  
system.  
Demand limiting (load shedding) — When a utility's  
demand for electricity exceeds a certain level, loads are  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical piping and wiring  
a30-4700  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD SINGLE INPUT POWER CONFIGURATION  
LEGEND  
3. Maximum instantaneous current flow (ICF) during start-up is the point  
in the starting sequence where the sum of the LRA for the start-up  
compressor, plus the total RLA for all running compressors is at a  
maximum.  
4. Maximum incoming wire size for each terminal block is 500 kcmil.  
5. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.  
6. Use copper conductors only.  
NOTES:  
1. Each main power source must be supplied from a field-supplied fused  
electrical service with a (factory-installed or field-installed) disconnect  
located in sight from the unit.  
2. Control circuit power must be supplied from a separate source through  
a field-supplied disconnect. An optional control transformer may be  
used to provide control circuit power from the main unit power supply.  
26  
OPTIONAL DUAL INPUT POWER CONFIGURATION  
UNIT VOLTAGE  
Supplied  
CONTROL CIRCUIT  
30XA  
UNIT  
SIZE  
NO. POWER  
ICF  
REC FUSE  
SIZE  
SUPPLY  
MCA  
MOCP  
MCA and  
V-Ph-Hz  
V-Ph-Hz  
CONDUCTORS  
MOCP  
Min  
187  
207  
342  
414  
518  
187  
207  
342  
414  
518  
187  
207  
342  
414  
518  
187  
207  
342  
414  
518  
187  
207  
342  
414  
518  
187  
207  
342  
414  
518  
Max  
220  
253  
418  
506  
633  
220  
253  
418  
506  
633  
220  
253  
418  
506  
633  
220  
253  
418  
506  
633  
220  
253  
418  
506  
633  
220  
253  
418  
506  
633  
WD  
XL  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
6/6  
6/6  
3/3  
3/3  
3/3  
6/6  
6/6  
3/3  
3/3  
3/3  
6/6  
6/6  
3/3  
3/3  
3/3  
6/6  
6/6  
3/3  
3/3  
3/3  
6/6  
6/6  
3/3  
3/3  
3/3  
6/6  
6/6  
6/6  
3/3  
3/3  
511.3/511.3  
443.9/443.9  
270.9/270.9  
222.8/222.8  
176.3/176.3  
800/800  
700/700  
450/450  
400/400  
300/300  
938/938  
816/816  
700 700 115-1-60  
600 600 115-1-60  
494/494 1537/1537 350 350 115-1-60  
408/408 1270/1270 300 300 115-1-60  
326/326 1016/1016 225 225 115-1-60  
800 800 115-1-60  
700 700 115-1-60  
700/700 2179/2179 450 450 115-1-60  
578/578 1800/1800 350 350 115-1-60  
462/462 1440/1440 300 300 115-1-60  
700 700 115-1-60  
600 600 115-1-60  
494/494 1537/1537 350 350 115-1-60  
408/408 1270/1270 300 300 115-1-60  
326/326 1016/1016 225 225 115-1-60  
800 800 115-1-60  
700 700 115-1-60  
700/700 2179/2179 450 450 115-1-60  
578/578 1800/1800 350 350 115-1-60  
462/462 1440/1440 300 300 115-1-60  
700 700 115-1-60  
700 700 115-1-60  
494/494 1537/1537 400 400 115-1-60  
408/408 1270/1270 350 350 115-1-60  
326/326 1016/1016 250 250 115-1-60  
1000 1000 115-1-60  
800 800 115-1-60  
700/700 2179/2179 500 500 115-1-60  
578/578 1800/1800 400 400 115-1-60  
462/462 1440/1440 350 350 115-1-60  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
325  
649.0/649.0 1000/1000 1329/1329  
565.8/565.8 1000/1000 1156/1156  
325  
HM  
341.4/341.4  
283.8/283.8  
226.0/226.0  
511.3/511.3  
443.9/443.9  
270.9/270.9  
222.8/222.8  
176.3/176.3  
649.0/649.0 1000/1000 1329/1329  
565.8/565.8 1000/1000 1156/1156  
341.4/341.4  
283.8/283.8  
226.0/226.0  
600/600  
500/500  
400/400  
800/800  
700/700  
450/450  
400/400  
300/300  
938/938  
816/816  
350  
350  
HM  
600/600  
500/500  
400/400  
578.5/578.5 1000/1000  
938/938  
816/816  
501.6/501.6  
302.9/302.9  
251.6/251.6  
203.5/203.5  
738.8/738.8 1200/1200 1329/1329  
642.6/642.6 1000/1000 1156/1156  
389.4/389.4  
322.1/322.1  
258.0/258.0  
800/800  
500/500  
450/450  
350/350  
400  
400  
HM  
600/600  
500/500  
450/450  
LEGEND  
3. Maximum instantaneous current flow (ICF) during start-up is the point in  
the starting sequence where the sum of the LRA for the start-up com-  
pressor, plus the total RLA for all running compressors is at a maximum.  
4. Maximum incoming wire size for each terminal block is 500 kcmil.  
5. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.  
6. Use copper conductors only.  
ICF  
Maximum Instantaneous Current Flow  
Heat Machine Units  
HM  
LRA  
MCA  
Locked Rotor Amps  
Minimum Circuit Ampacity (for wire sizing)  
MOCP — Maximum Overcurrent Protection  
7. The MOCP is calculated as follows:  
RLA  
WD  
XL  
Rated Load Amps  
Wye-Delta Start  
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse  
one size down from the result. The RLAs are listed on the nameplate.  
Across-the-Line Start  
NOTES:  
The recommended fuse size in amps (RFA) is calculated as follows:  
1. Each main power source must be supplied from a field-supplied fused  
electrical service with a (factory-installed or field-installed) disconnect  
located in sight from the unit.  
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse  
one size up from the result. The RLAs are listed on the nameplate.  
2. Control circuit power must be supplied from a separate source through a  
field-supplied disconnect. An optional control transformer may be used  
to provide control circuit power from the main unit power supply.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical data (cont)  
COMPRESSOR ELECTRICAL DATA  
COMPRESSOR A  
COMPRESSOR B  
LRA (WD)  
938  
30HX UNIT  
SIZE  
VOLTAGE  
V-Ph-Hz  
COMPRESSOR  
RLA  
409.0  
355.1  
216.7  
178.2  
141.0  
519.2  
452.6  
273.1  
227.0  
180.8  
409.0  
355.1  
216.7  
178.2  
141.0  
519.2  
452.6  
273.1  
227.0  
180.8  
462.8  
401.3  
242.3  
201.3  
162.8  
591.0  
514.1  
311.5  
257.7  
206.4  
LRA (WD)  
938  
LRA (XL)  
N/A  
RLA  
409.0  
355.1  
216.7  
178.2  
141.0  
519.2  
452.6  
273.1  
227.0  
180.8  
409.0  
355.1  
216.7  
178.2  
141.0  
519.2  
452.6  
273.1  
227.0  
180.8  
462.8  
401.3  
242.3  
201.3  
162.8  
591.0  
514.1  
311.5  
257.7  
206.4  
LRA (XL)  
N/A  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
200-3-60  
230-3-60  
380-3-60  
460-3-60  
575-3-60  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU483  
06TU554  
06TU554  
06TU554  
06TU554  
06TU554  
06TU554  
06TU554  
06TU554  
06TU554  
06TU554  
816  
494  
408  
326  
1329  
1156  
700  
578  
462  
938  
816  
494  
408  
N/A  
816  
494  
408  
326  
1329  
1156  
700  
578  
462  
938  
816  
494  
408  
N/A  
325  
325 HM  
350  
1537  
1270  
1016  
N/A  
1537  
1270  
1016  
N/A  
N/A  
N/A  
2179  
1800  
1440  
N/A  
2179  
1800  
1440  
N/A  
N/A  
N/A  
1537  
1270  
1016  
N/A  
1537  
1270  
1016  
N/A  
326  
326  
1329  
1156  
700  
578  
462  
938  
816  
494  
408  
1329  
1156  
700  
578  
462  
938  
816  
494  
408  
N/A  
N/A  
350 HM  
400  
2179  
1800  
1440  
N/A  
2179  
1800  
1440  
N/A  
N/A  
N/A  
1537  
1270  
1016  
N/A  
1537  
1270  
1016  
N/A  
326  
326  
1329  
1156  
700  
578  
462  
1329  
1156  
700  
578  
462  
N/A  
N/A  
400 HM  
2179  
1800  
1440  
2179  
1800  
1440  
LEGEND  
HM  
Heat Machine Units  
Locked Rotor Amps  
Not Applicable  
LRA  
N/A  
RLA  
WD  
XL  
Rated Load Amps  
Wye-Delta Start  
Across-the-Line Start  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications  
C. Evaporator:  
1. Shall be tested and stamped in accordance  
Water-Cooled Chiller  
HVAC Guide Specifications  
with ASME Code (U.S.A.) for a refrigerant  
working-side pressure of 220 psig (1408 kPa).  
Water-side pressure rating shall be 150 psig  
(1034 kPa). In Canada, maximum water-side  
pressure shall be 250 psig (1725 kPa), per the  
Canadian National Registry.  
Size Range: 325 to 400 Nominal Tons  
(1133 to 1354 kW)  
Carrier Model Number: 30XW  
Part 1 — General  
1.01 SYSTEM DESCRIPTION  
2. Shall be mechanically cleanable shell-and-tube  
type with removable heads.  
3. Tubes shall be internally enhanced, seamless-  
copper type, and shall be rolled into tube  
sheets.  
Microprocessor controlled water-cooled liquid chiller  
utilizing screw compressors and electronic expan-  
sion valves.  
1.02 QUALITY ASSURANCE  
A. Unit shall be rated in accordance with AHRI Stan-  
dard 550/590 (U.S.A.), latest edition.  
B. Unit construction shall comply with ASHRAE 15  
Safety Code, NEC, and ASME applicable codes  
(U.S.A. codes).  
C. Unit shall be manufactured in a facility registered to  
ISO 9001:2000 Manufacturing Quality Standard.  
D. 200-v, 230-v, 460-v, 575-v, 60 Hz units shall be  
constructed in accordance with UL or UL Canada  
standards and shall be tested and listed by ETL or  
ETL, Canada, as conforming to those standards.  
Units shall carry the ETL and ETL, Canada, labels.  
4. Shall be equipped with victaulic fluid  
connections.  
3
5. Shell shall be insulated with /4-in. (19-mm)  
closed-cell, polyvinyl chloride foam with a maxi-  
mum K factor of 0.28. Heads may require field  
insulation.  
6. Shall have a evaporator drain and vent.  
7. Design shall incorporate 2 independent refrig-  
erant circuits.  
8. Shall include isolation valves to allow isolation  
of the refrigerant charge in either the evapora-  
tor or the condenser.  
9. Shall be equipped with factory-installed thermal  
dispersion chilled fluid flow switch.  
1.03 DELIVERY, STORAGE, AND HANDLING  
A. Unit controls shall be capable of withstanding 150 F  
(65.5 C) storage temperatures in the control  
compartment.  
D. Condenser:  
1. Shall be tested and stamped in accordance  
with ASME code (U.S.A.) for a refrigerant  
working-side pressure of 220 psig (1408 kPa).  
Water-side pressure rating shall be 150 psig  
(1034 kPa). In Canada, maximum water-side  
pressure shall be 250 psig (1725 kPa), per the  
Canadian National Registry.  
2. Shall be mechanically cleanable shell-and-tube  
type with removable heads.  
3. Tubes shall be internally enhanced, seamless-  
copper type, and shall be rolled into tube  
sheets.  
B. Chiller and starter should be stored indoors, pro-  
tected from construction dirt and moisture. An  
inspection should be conducted under shipping  
tarps, bags, or crates to be sure water has not col-  
lected during transit. Protective shipping covers  
should be kept in place until machine is ready for  
installation. The inside of the protective cover  
should meet the following criteria:  
1. Temperature is between 40 F (4.4 C) and  
120 F (48.9 C).  
2. Relative humidity is between 10% and 80%  
(non-condensing).  
4. Shall be equipped with victaulic water  
connections.  
5. Design shall incorporate 2 independent refrig-  
erant circuits.  
Part 2 — Products  
2.01 EQUIPMENT  
A. General:  
Factory assembled, single-piece, water-cooled liquid  
chiller with dual (2) independent refrigerant circuits.  
Contained within the unit cabinet shall be all factory  
wiring, piping, controls, refrigerant charge (HFC-  
134a) and special features required prior to field  
start-up.  
E. Heat Machines:  
1. Condenser shall be tested and stamped in  
accordance with ASME Code (U.S.A.) for a  
refrigerant working-side pressure of 300 psig  
(2068 kPa).  
2. Design shall incorporate 2 independent refrig-  
erant circuits.  
3. Heat machine condensers shall include factory-  
installed thermal insulation on the condenser,  
condenser flow switch and leaving water  
temperature sensor. Heat machine units  
require field-installed thermal insulation on the  
B. Compressors:  
1. Semi-hermetic twin-screw compressors with  
internal muffler and check valve.  
2. Each compressor shall be equipped with a dis-  
charge shutoff valve.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications (cont)  
compressor discharge piping and waterbox  
heads because of high temperature.  
F. Refrigeration Components:  
H. Safeties:  
Unit shall be equipped with thermistors and all nec-  
essary components in conjunction with the control  
system to provide the unit with the following  
protections:  
1. Loss of refrigerant charge.  
2. Reverse rotation.  
3. Low chilled fluid temperature.  
4. Motor overtemperature.  
5. High pressure.  
Refrigerant circuit components shall include oil sep-  
arator, high and low side pressure relief devices, dis-  
charge and liquid line shutoff valves, filter drier,  
moisture indicating sight glass, expansion valve,  
refrigerant economizer (unit sizes 350, 400), and  
complete charge of compressor oil. The units shall  
have a complete operating charge of refrigerant  
HFC-134a.  
G. Controls:  
6. Electrical overload.  
7. Loss of phase.  
8. Loss of chilled water flow  
I. Diagnostics:  
1. Unit controls shall include the following mini-  
mum components:  
a. Microprocessor with non-volatile memory.  
Battery backup system shall not be accepted.  
b. Separate terminal block for power and  
controls.  
c. Separate 115-v power supply to serve all  
controllers, relays, and control components.  
d. ON/OFF control switch.  
1. The control panel shall include, as standard, a  
display:  
a. Touch screen display consisting of ¼ VGA  
LCD (liquid crystal display) with adjustable  
contrast and backlighting.  
b. Display shall allow a user to navigate  
through menus, select desired options and  
modify data.  
e. Replaceable solid-state controllers.  
f. Pressure sensors installed to measure  
suction, oil, economizer, and discharge  
pressure. Thermistors installed to measure  
evaporator entering and leaving fluid  
temperatures.  
2. Features of the display shall include:  
a. Display shall be customizable and allow up to  
72 data points.  
b. Display shall support both local equipment  
or network made for remote mount.  
c. Display shall allow access to configuration,  
maintenance, service, set point, time sched-  
ules, alarm history and status data.  
d. Display shall have one button for chiller on/  
off.  
e. Display shall include three levels of password  
protection against unauthorized access to  
configuration and maintenance informa-  
tion, and display set up parameters.  
f. Display shall allow for easy connection of a  
portable hand held technician tool to access  
information and upload and/or download  
chiller settings.  
g. Display shall be compatible with the Carrier  
Comfort Network® (CCN) system and pro-  
vide network alarm acknowledgement or  
indication and provide capability to fully  
monitor and control chiller.  
h. Display alarms and parameters shall be  
capable of being displayed in full text.  
2. Unit controls shall include the following  
functions:  
a. Automatic circuit lead/lag.  
b. Capacity control based on leaving chilled  
fluid temperature and compensated by rate  
of change of return-fluid temperature with  
temperature set point accuracy to 0.1° F  
(0.05° C).  
c. Limiting the chilled fluid temperature  
pulldown rate at start-up to an adjustable  
range of 0.2° F to 2° F (0.1 to 1.1° C) per  
minute to prevent excessive demand spikes  
at start-up.  
d. Seven-day time schedule.  
e. Leaving chilled fluid temperature reset from  
return fluid and outside air temperature.  
f. Chilled water and condenser water pump  
start/stop control.  
g. Chiller control for parallel chiller applications  
without addition of hardware modules and  
control panels (requires thermistors).  
h. Timed maintenance scheduling to signal  
i. Display shall be capable of displaying the last  
50 alarms and will store a snapshot of a  
minimum of 20 status data parameters for  
each alarm.  
maintenance  
activities  
for  
strainer  
maintenance and user-defined maintenance  
activities.  
i. Single step demand limit control activated by  
remote contact closure.  
j. Compressor run hours.  
k. Compressor number of starts.  
l. Compressor current.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
m. Time of day:  
1) Display module, in conjunction with the  
* 5. Minimum Load Control:  
Unit shall be equipped with factory-installed,  
microprocessor-controlled, minimum load con-  
trol that shall permit unit operation down to  
10% of full capacity.  
microprocessor, must also be capable of  
displaying the output (results) of a ser-  
vice test. Service test shall verify opera-  
tion of every switch, thermistor, and  
compressor before chiller is started.  
2) Diagnostics shall include the ability to  
review a list of the 30 most recent  
alarms with clear language descriptions  
of the alarm event. Display of alarm  
codes without the ability for clear lan-  
guage descriptions shall be prohibited.  
3) An alarm history buffer shall allow the  
user to store no less than 30 alarm  
events with clear language descriptions,  
time and date stamp event entry.  
4) The chiller controller shall include multi-  
ple connection ports for communicating  
with the local equipment network, the  
Carrier Comfort Network (CCN) sys-  
tem and the ability to access all chiller  
control functions from any point on the  
chiller.  
6. One-Pass Evaporator:  
Factory-installed option shall reduce pressure  
drop for high flow applications.  
7. Three-Pass Evaporator:  
Factory-installed option shall enhance perfor-  
mance for low flow applications.  
8. Energy Management Module:  
A factory or field installed module shall provide  
the following energy management capabilities:  
4 to 20 mA signals for leaving fluid temperature  
reset, cooling set point reset or demand limit  
control; 2-point demand limit control (from 0 to  
100%) activated by a remote contact closure;  
and discrete input for "Ice Done" indication for  
ice storage system interface.  
9. BACnet™ Translator Control:  
Unit shall be supplied with field-installed inter-  
face between the chiller and a BACnet Local  
Area Network (LAN, i.e., MS/TP EIA-485).  
5) The control system shall allow software  
upgrade without the need for new hard-  
ware modules.  
10. LON Translator Control:  
J. Operating Characteristics:  
Unit shall be supplied with field-installed inter-  
face between the chiller and a Local Operating  
Network (LON, i.e., LonWorks® FT-10A  
ANSI/EIA-709.1).  
Unit shall be capable of starting up with 95 F (35 C)  
entering fluid temperature to the evaporator.  
K. Electrical Requirements:  
11. Navigator™ Hand Held Portable Display:  
1. Unit primary electrical power supply shall enter  
the unit at a single location.  
2. Unit shall operate on 3-phase power at the volt-  
age shown in the equipment schedule.  
3. Control voltage shall be 115-v (60 Hz), single-  
phase, separate power supply.  
a. Portable hand held display module with a  
minimum of 4 lines and 20 characters per  
line, or clear English, Spanish, Portuguese  
or French language.  
b. Display menus shall provide clear language  
descriptions of all menu items, operating  
modes, configuration points and alarm diag-  
nostics. Reference to factory codes shall not  
be accepted.  
c. RJ-14 connection plug shall allow display  
module to be connected to factory-installed  
receptacle.  
d. Industrial grade coiled extension cord shall  
allow the display module to be moved  
around the chiller.  
L. Special Features:  
Certain standard features are not applicable when  
the features designated by * are specified. For assis-  
tance in amending the specifications, contact your  
local Carrier Sales office.  
* 1. Wye-Delta Starter:  
Unit shall have a factory-installed, wye-delta  
starter to minimize electrical inrush current.  
2. Vibration Isolation:  
Unit shall be supplied with rubber-in-shear  
vibration isolators for field installation.  
3. Control Power Transformer:  
e. Magnets shall hold the display module to  
any sheet metal panel to allow hands-free  
operation.  
f. Display module shall have NEMA 4x  
housing.  
g. Display shall have back light and contrast  
adjustment for easy viewing in bright sun-  
light or night conditions.  
Unit shall be supplied with a factory-installed  
controls transformer that will supply control cir-  
cuit power from the main unit power supply.  
4. Temperature Reset Sensor:  
Unit shall reset leaving chilled fluid temperature  
based on outdoor ambient temperature or  
space temperature when this sensor is installed.  
h. Raised surface buttons with positive tactile  
response.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guide specifications (cont)  
12. Compressor Suction Service Valve:  
19. Dual Point Power:  
Standard refrigerant discharge isolation and  
liquid valves enable service personnel to store  
the refrigerant charge in the evaporator or  
condenser during servicing. This factory-  
installed option allows for further isolation of  
the compressor from the evaporator vessel.  
The dual point power option shall provide a  
means for connecting two sources of power to  
dual compressor chillers. One source of power  
is wired to operate the compressor on the A  
circuit and one source of power is wired to  
operate the compressor on the B circuit of the  
chiller.  
13. GFI Convenience Outlet:  
20. Non-Fused Disconnect:  
Shall be factory or field-installed and mounted  
with easily accessible 115-v female receptacle.  
Shall include 4 amp GFI receptacle.  
This option shall provide a no load, lockable,  
through the door handle disconnect for unit  
power on the chiller. On dual point power,  
one disconnect is provided for each of the two  
main power supplies. This disconnect does  
not remove the control circuit from power  
supply.  
14. 300 psig (2068 kPa) Evaporator Operating  
Pressure:  
This option shall provide for water-side pres-  
sure operation up to 300 psig (2068 kPa).  
15. 300 psig (2068 kPa) Condenser Operating  
Pressure:  
This option shall provide for water-side pres-  
sure operation up to 300 psig (2068 kPa).  
16. Marine Waterboxes:  
21. Control Transformer:  
The control transformer shall be sized to sup-  
ply the needs of the control circuit from the  
main power supply.  
22. Nitrogen Charge:  
Marine waterboxes shall provide water piping  
connections extending from the side of the  
waterbox (as opposed to extending from the  
end of the waterbox). This option also includes  
a removable bolt on waterbox cover allowing  
access to the heat exchanger tubes without  
breaking the existing field piping. This option  
is available for both the evaporator and  
condenser.  
A nitrogen charge option is available to pro-  
vide a 15 lb (6.8 kg) charge of nitrogen  
instead of a full factory charge of R-134a  
refrigerant to keep the chiller refrigerant cir-  
cuit dry during shipment. This option is rec-  
ommended for applications where the unit will  
be disassembled prior to installation. Units  
shipped with a nitrogen charge will receive an  
electrical continuity test at the factory prior to  
shipment.  
17. Flanged Connection:  
The flanged connection option shall provide  
an ANSI flange on the end of the chiller water  
piping for connection to a customer supplied  
mating flange in the field piping. This option  
is available for both the evaporator and  
condenser.  
23. Crate for Shipment:  
This option is recommended for export  
orders. The chiller will be bagged prior to  
being placed in a wooden crate.  
24. Remote Enhanced Display:  
This option is a remotely mounted indoor  
40-character per line, 16-line display panel for  
unit monitoring and diagnostics.  
18. One-Pass Condenser:  
This option shall provide a lower pressure  
drop through the condenser for applications  
with low delta T (temperature) or high flow or  
where the condensers are piped in a series.  
The one-pass condenser option is only avail-  
able with flanged connections and with a dis-  
charge end leaving water connection.  
25. Vibration Springs:  
A set of non-siesmic spring isolators can be  
provided for installation at the jobsite.  
Carrier Corporation • Syracuse, New York 13221  
6-09  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Pg 32  
Catalog No. 04-52300015-01  
Printed in U.S.A.  
Form 30XW-2PD  
Replaces: 30XW-1PD  
Section 9  
Tab 9a  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Network Cables PM01141ea User Manual
Berkel Mixer FMS30 User Manual
Black Box Network Hardware LGC200A User Manual
Bosch Appliances Cooktop BOSCH Cooktop User Manual
Bosch Appliances Security Camera NBN 921 User Manual
Bravetti Frozen Dessert Maker KP300H User Manual
Brother Fax Machine LE8235001 User Manual
Casio Electronic Keyboard CTK 6200 User Manual
Casio Watch MA1310 EA User Manual
Chicago Electric Power Roller SKU 91780 User Manual