Product Information SM 210 LSN RW
PI - 32.52c
1. Product description
Call points SM 210 LSN RW are used for manual alarming.
Manual call points SM 210 LSN RW are used within the Local Security Network
LSN in association with fire detection central units.
Manual call points SM 210 LSN RW are available in 3 versions:
- SM 210 LSN RW, with back box for indoor surface mounting
- SM 210 LSN RW, with bezel for indoor flush mounting
- SM 210 LSN RW, with back box for outdoor surface mounting
2. Features
D Alarm initiating by pushing (breaking) the glass plate
⇒ injury protection by foilcoated glass plate
D Detector request routines with evaluation and multi data transmission
D Detector identification and address reported at the fire panel in the event of an
alarm for a faster fire localization.
D Alarm indication at the detector via a flashing red LED
3. Planning notes
D Manual call points should be installed in easy visible and accessible places.
D Manual call points should be illuminated adequately by daylight or another light
source (inclusively safety light if present).
D Manual call points should be installed in rescue- and escaping corridors (i.e. exits,
passages, stairways).
3.1. Maximum connectable detectors
Because of the different current consumption of LSN elements out of the LSN data-
line the maximum current consumption value per LSN loop is absolute to aboden.
For limit values please refer to the product information of the used fire detection
central unit.
3.2. Standards, guidelines, projecting recommendations
See standards, guidelines and projecting recommendations for installation place
and so on.
Heed the regulations of the local fire brigades.
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 3 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
4. Order list
Order number DU*
Designation
4.998.098.964 ST Manual call point SM 210 LSN RW, colour red, with test key
and back box for indoor surface mounting
Manual call point as per UL / LPC -standard.
4.998.098.965 ST Manual call point SM 210 LSN RW, colour red, with test key
and bezel for indoor flush mounting.
Manual call point as per UL / LPC -standard.
4.998.104.058 ST Manual call point SM 210 LSN RW, colour red, with test key
and back box for outdoor surface mounting
Manual call point as per UL / LPC -standard.
4.998.103.969 ST Spare glass for SM 210 LSN RW / SM 120 RW
*DU = delivery unit / ST = Piece
5. Construction
5
3
1
8
7
6
2
4
9
Pos. Designation
1
2
3
4
5
6
7
8
9
detector front plate
alarm indication (LED)
glass plate with labeled protection foil
mechanism for alarm reset and detector test
micro switch
detector housing
hole for under plaster cable feed
template for cable glands
back box
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 4 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
6. Functional description
After pushing in the glass plate (1) the alarm will be released by the knob of the
microswitch (2) and the LED (3) starts flashing.
The reset of the microswitch (2) follows by replacing the glass plate (1).
2
1
5
3
4
Call point without front plate
6.1. Detector test
Shifting the test key into the recess (4) will unlock the retaining collar (5). Therefore
the glass plate (1) shifts downwards and the knob of the microswitch (2) releases an
alarm. The indicating LED (3) starts flashing.
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 5 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
7. Installation notes
Flush call point
PI - 32.52c
The flush call point comes complete with a bezel and will mount onto any standard
U.K. single gang back box with a depth of min. 25mm or directly to a wall. Conside-
ration should be given to the amount of cabling space at the rear of the call point,
i.e. a deeper box or spacer eases installation.
Surface call point
The surface mounting call point comes complete with a back box onto which the
calll point is mounted. There is provision for rear cable entry. By using the template
at the leaflet, cable holes can be drilled into the top or bottom of the back box to
accept one or two cable glands - Max. dia. 20mm.
7.1. Fixing details for the indoor versions (IP54)
View: back box inside
View: bezel
87
∅ 4
∅ 4
20
36
60
100
Cable feed over plaster,
via cable glands
Cable feed under plaster for
detector mounting with back
box and rear cable entry
See template at the call
point leaflet for the hole
positions of cable glands.
TP
TOP
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 6 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
7.2. Fixing details for the outdoor version (IP67)
View: back box inside
View: back box with
mounted call point
20
45
97
Cable feed over plaster, via cable glands
87
111
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 7 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
7.3. Connection
LSN
LSN
a2
b2
LSN2
a1
b1
LSN1
+U
0V
Detector backside
Back box for surface mounting
Connecting terminals
+U
0V
rt
power supply for other LSN-Elements i.e. LSN-Couplers
coming from the fire panel or an upstream LSN-Element
sw
a2
b2
ws
ge
LSN2
LSN1
a1
b1
ws
ge
going to the next LSN-Element
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 8 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
8. Notes for Maintenance and Service
Maintenance and service works should be undertaken regularly by skilled and trai-
ned personnel in accordance with the national legislative requirements.
Faulty detectors under the warranty terms will be replaced free of charge.
8.1. Further Documentation
Order number DU*
Designation
3.002.218.156
3.002.218.155
ST Connection manual AHB BMZ / EMZ
ST Connection manual AHB UGM
*DU = delivery unit, ST = piece
For those with access authorization, on the Bosch ST ExtraNet at
the current information for each product, as well as the installation instructions
supplied with the device, are available for download as a PDF file.
8.2. Disposal
Defective manual call points will be completely replaced and should be
disposed according to the legal requirements.
9. Technical data
Voltage rating (LSN): 10V DC . . . 31V DC
Current consumption (LSN):
0.4mA
IP Rating (as per EN 60529): IP 54 (indoor versions)
IP 67 (outdoor version)
Environmental temperature:
Environmental class (VdS):
Dimensions (H x B x T):
-25°C . . . +65°C
III
Indoor Versions
87 x 87 x 53mm (surface mounting)
87 x 87 x 20mm (flush mounting)
107 x 107 x 36mm (flush mounting with bezel)
Outdoor Version
111 x 111 x 65mm (surface mounting)
Housing material:
Colour:
Plastic, ABS
Red (RAL 3001)
approx. 150g
378c
Weight:
LPC-Approval number:
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 9 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
10. Abbreviatons
AHB = Anschaltehandbuch / Connection manual
BMZ = Brandmeldezentrale / Fire panel
BM
= Brandmelder / Fire detector
DIN = Deutsches Institut f. Normung / German institute for standardization
EMZ = Einbruchmeldezentrale / Intrusion panel
EN
GMZ = Gefahrenmeldeanlage / Security system
KI = Kundendienst Information / Maintenance information
= Europa Norm / European standard
LED = Light emittend diode
LPC = Loss prevention council
LSN = Local Security Network
SM
= Springknopfmelder / Manual call point
UGM = Universelle Gefahrenmeldezentrale (Universal security system panel
VDE = Verband Deutscher Elektrotechniker e.V. /
Association of German Electrotechnicians
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 10 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Information SM 210 LSN RW
PI - 32.52c
11. Memos
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Seite 11 von 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Bosch Security Systems
Robert-Koch-Str. 100
D-85521 Ottobrunn
Info-Service
Telephone: +49 89 6290 - 1039
Fax:
+49 89 6290 - 1039
Page 12 of 12