Bosch Appliances Smoke Alarm SM 210 LSN RW User Manual

PRODUCT INFORMATION  
PI-34.52c  
Manual call point SM 210 LSN RW  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 1  
Seit 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
1. Product description  
Call points SM 210 LSN RW are used for manual alarming.  
Manual call points SM 210 LSN RW are used within the Local Security Network  
LSN in association with fire detection central units.  
Manual call points SM 210 LSN RW are available in 3 versions:  
- SM 210 LSN RW, with back box for indoor surface mounting  
- SM 210 LSN RW, with bezel for indoor flush mounting  
- SM 210 LSN RW, with back box for outdoor surface mounting  
2. Features  
D Alarm initiating by pushing (breaking) the glass plate  
injury protection by foilcoated glass plate  
D Detector request routines with evaluation and multi data transmission  
D Detector identification and address reported at the fire panel in the event of an  
alarm for a faster fire localization.  
D Alarm indication at the detector via a flashing red LED  
3. Planning notes  
D Manual call points should be installed in easy visible and accessible places.  
D Manual call points should be illuminated adequately by daylight or another light  
source (inclusively safety light if present).  
D Manual call points should be installed in rescue- and escaping corridors (i.e. exits,  
passages, stairways).  
3.1. Maximum connectable detectors  
Because of the different current consumption of LSN elements out of the LSN data-  
line the maximum current consumption value per LSN loop is absolute to aboden.  
For limit values please refer to the product information of the used fire detection  
central unit.  
3.2. Standards, guidelines, projecting recommendations  
See standards, guidelines and projecting recommendations for installation place  
and so on.  
Heed the regulations of the local fire brigades.  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 3 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
4. Order list  
Order number DU*  
Designation  
4.998.098.964 ST Manual call point SM 210 LSN RW, colour red, with test key  
and back box for indoor surface mounting  
Manual call point as per UL / LPC -standard.  
4.998.098.965 ST Manual call point SM 210 LSN RW, colour red, with test key  
and bezel for indoor flush mounting.  
Manual call point as per UL / LPC -standard.  
4.998.104.058 ST Manual call point SM 210 LSN RW, colour red, with test key  
and back box for outdoor surface mounting  
Manual call point as per UL / LPC -standard.  
4.998.103.969 ST Spare glass for SM 210 LSN RW / SM 120 RW  
*DU = delivery unit / ST = Piece  
5. Construction  
5
3
1
8
7
6
2
4
9
Pos. Designation  
1
2
3
4
5
6
7
8
9
detector front plate  
alarm indication (LED)  
glass plate with labeled protection foil  
mechanism for alarm reset and detector test  
micro switch  
detector housing  
hole for under plaster cable feed  
template for cable glands  
back box  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 4 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
6. Functional description  
After pushing in the glass plate (1) the alarm will be released by the knob of the  
microswitch (2) and the LED (3) starts flashing.  
The reset of the microswitch (2) follows by replacing the glass plate (1).  
2
1
5
3
4
Call point without front plate  
6.1. Detector test  
Shifting the test key into the recess (4) will unlock the retaining collar (5). Therefore  
the glass plate (1) shifts downwards and the knob of the microswitch (2) releases an  
alarm. The indicating LED (3) starts flashing.  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 5 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
7. Installation notes  
Flush call point  
PI - 32.52c  
The flush call point comes complete with a bezel and will mount onto any standard  
U.K. single gang back box with a depth of min. 25mm or directly to a wall. Conside-  
ration should be given to the amount of cabling space at the rear of the call point,  
i.e. a deeper box or spacer eases installation.  
Surface call point  
The surface mounting call point comes complete with a back box onto which the  
calll point is mounted. There is provision for rear cable entry. By using the template  
at the leaflet, cable holes can be drilled into the top or bottom of the back box to  
accept one or two cable glands - Max. dia. 20mm.  
7.1. Fixing details for the indoor versions (IP54)  
View: back box inside  
View: bezel  
87  
4  
4  
20  
36  
60  
100  
Cable feed over plaster,  
via cable glands  
Cable feed under plaster for  
detector mounting with back  
box and rear cable entry  
See template at the call  
point leaflet for the hole  
positions of cable glands.  
TP  
TOP  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 6 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
7.2. Fixing details for the outdoor version (IP67)  
View: back box inside  
View: back box with  
mounted call point  
20  
45  
97  
Cable feed over plaster, via cable glands  
87  
111  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 7 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
7.3. Connection  
LSN  
LSN  
a2  
b2  
LSN2  
a1  
b1  
LSN1  
+U  
0V  
Detector backside  
Back box for surface mounting  
Connecting terminals  
+U  
0V  
rt  
power supply for other LSN-Elements i.e. LSN-Couplers  
coming from the fire panel or an upstream LSN-Element  
sw  
a2  
b2  
ws  
ge  
LSN2  
LSN1  
a1  
b1  
ws  
ge  
going to the next LSN-Element  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 8 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
8. Notes for Maintenance and Service  
Maintenance and service works should be undertaken regularly by skilled and trai-  
ned personnel in accordance with the national legislative requirements.  
Faulty detectors under the warranty terms will be replaced free of charge.  
8.1. Further Documentation  
Order number DU*  
Designation  
3.002.218.156  
3.002.218.155  
ST Connection manual AHB BMZ / EMZ  
ST Connection manual AHB UGM  
*DU = delivery unit, ST = piece  
For those with access authorization, on the Bosch ST ExtraNet at  
the current information for each product, as well as the installation instructions  
supplied with the device, are available for download as a PDF file.  
8.2. Disposal  
Defective manual call points will be completely replaced and should be  
disposed according to the legal requirements.  
9. Technical data  
Voltage rating (LSN): 10V DC . . . 31V DC  
Current consumption (LSN):  
0.4mA  
IP Rating (as per EN 60529): IP 54 (indoor versions)  
IP 67 (outdoor version)  
Environmental temperature:  
Environmental class (VdS):  
Dimensions (H x B x T):  
-25°C . . . +65°C  
III  
Indoor Versions  
87 x 87 x 53mm (surface mounting)  
87 x 87 x 20mm (flush mounting)  
107 x 107 x 36mm (flush mounting with bezel)  
Outdoor Version  
111 x 111 x 65mm (surface mounting)  
Housing material:  
Colour:  
Plastic, ABS  
Red (RAL 3001)  
approx. 150g  
378c  
Weight:  
LPC-Approval number:  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 9 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
10. Abbreviatons  
AHB = Anschaltehandbuch / Connection manual  
BMZ = Brandmeldezentrale / Fire panel  
BM  
= Brandmelder / Fire detector  
DIN = Deutsches Institut f. Normung / German institute for standardization  
EMZ = Einbruchmeldezentrale / Intrusion panel  
EN  
GMZ = Gefahrenmeldeanlage / Security system  
KI = Kundendienst Information / Maintenance information  
= Europa Norm / European standard  
LED = Light emittend diode  
LPC = Loss prevention council  
LSN = Local Security Network  
SM  
= Springknopfmelder / Manual call point  
UGM = Universelle Gefahrenmeldezentrale (Universal security system panel  
VDE = Verband Deutscher Elektrotechniker e.V. /  
Association of German Electrotechnicians  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 10 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Information SM 210 LSN RW  
PI - 32.52c  
11. Memos  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  
601-4.998.125.088  
A2.en / 29.12.2004  
ST-FIR/ PRM1 / deh  
Seite 11 von 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bosch Security Systems  
Robert-Koch-Str. 100  
D-85521 Ottobrunn  
Info-Service  
Telephone: +49 89 6290 - 1039  
Fax:  
+49 89 6290 - 1039  
Page 12 of 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bionaire Fan BTF1616 User Manual
Blomberg Printer TKF 7230 User Manual
Bogen Car Stereo System FMR User Manual
Bogen Microphone WCU250 User Manual
Bosch Appliances Ventilation Hood GWH 1600 H User Manual
Boston Acoustics Speaker DSi465T2 User Manual
Bravetti Food Processor EP114H User Manual
Canon Camcorder Accessories HF M300 User Manual
Child Craft Crib CCH0070109 00 User Manual
Cisco Systems Computer Accessories 15454M6DC User Manual