					CHAMPION® SERIES   
					SINGLE PACKAGE AIR CONDITIONERS   
					ELECTRIC/ELECTRIC, AIR-COOLED   
					Supersedes: Nothing   
					174065-YIM-A-0206   
					INSTALLATION INSTRUCTION   
					MODELS D2EB018 THRU 060   
					1-1/2 THRU 5 TON   
					(8.8 - 9.4 EER)   
					EXPORT   
					damage should be noted on the carrier's freight bill. Aseparate   
					request for inspection by the carrier's agent should be made in   
					writing. Refer to Form 50.15-NM for additional information.   
					GENERAL   
					Model D2EB units are factory assembled cooling only air condi-   
					tioners designed for outdoor installation on a rooftop or a slab.   
					Field-installed electric heater accessories are available to provide   
					electric heat combined with electric cooling. All units and heaters   
					are certified by CSA.   
					REFERENCE   
					Additional information on the design, installation, operation   
					and service of this equipment is available in the following refer-   
					ence forms:   
					The units are completely assembled on rigid, but easily remov-   
					able base rails. All piping, refrigerant charge, and electrical wir-   
					ing is factory installed and tested. The units require only electric   
					power and duct connections at the point of installation.   
					• 174065   
					-General Installation   
					• 511.26-N1.1V -Electric Heater Accessory   
					The electric heaters have nickel-chrome resistance wire ele-   
					ments and utilize single point power connection.   
					REPLACEMENT PARTS   
					INSPECTION   
					• Refer to Replacement Parts Manual for complete listing of   
					replacement parts on this equipment.   
					As soon as a unit is received, it should be inspected for possible   
					damage during transit. If damage is evident, the extent of the   
					Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make   
					the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury   
					and/or equipment damage may result if installation procedure is not handled properly.   
					CAUTION   
					THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH   
					THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE   
					LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED   
					TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.   
					WARNING   
					INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE   
					OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY   
					OR PROPERTY DAMAGE.   
				174065-YIM-A-0206   
					CLEARANCES   
					FILTERS   
					All units require certain clearances for proper operation and   
					service. Refer to Figure 3 for the clearances required for com-   
					bustion, construction, servicing and proper unit operation.   
					Single phase units are shipped without a filter and is the responsi-   
					bility of the installer to secure a filter in the return air ductwork or   
					install a Filter/Frame Kit (1FF0114).   
					WARNING:Do not permit overhanging structures or shrubs to   
					obstruct the condenser air discharge outlet.   
					A filter rack and a filters are standard on three phase units.   
					Filters must always be used and must be kept clean. When fil-   
					ters become dirt laden, insufficient air will be delivered by the   
					blower, decreasing your units efficiency and increasing operat-   
					ing costs and wear-and-tear on the unit and controls.   
					DUCT WORK   
					These units are adaptable to downflow use as well as rear sup-   
					ply and return air duct openings. To convert to downflow, use   
					the following steps:   
					Filters should be checked monthly especially since this unit   
					may be used for both heating and cooling.   
					1. Remove the duct covers found in the bottom return and   
					supply air duct openings. There are four (4) screws secur-   
					ing each duct cover (save these screws to use later).   
					CONDENSATE DRAIN   
					2. Install the duct covers, removed in step one, to the rear sup-   
					ply and return air duct openings. Secure with the four (4)   
					screws used in step one.   
					A condensate trap is required to be installed in the condensate   
					drain. The plumbing must conform to local codes. Use a seal-   
					ing compound on male pipe threads. Install the condensate   
					3. Seal the duct covers with silicone caulking.   
					3 
					drain line ( “ NPTF) to spill into an open drain.   
					4 
					Downflow units must have an L-shaped supply duct without   
					any outlets or registers located directly below the supply outlet   
					of the unit.   
					SERVICE ACCESS   
					Access to all serviceable components is provided by the follow-   
					ing removable panels:   
					Duct work should be designed and sized according to the   
					methods of the Air Conditioning Contractors of America   
					(ACCA), as set forth in their Manual D.   
					• Blower service access   
					• Electrical/filter access   
					• Compressor service access   
					A closed return duct system shall be used. This shall not pre-   
					clude use of economizers or ventilation air intake. Flexible   
					joints may be used in the supply and return duct work to mini-   
					mize the transmission of noise.   
					Refer to Figure 3 for location of these access panels and mini-   
					mum clearance.   
					THERMOSTAT   
					CAUTION: When fastening duct work to the side duct flanges on   
					the unit, insert the screws through the duct flanges only.   
					DO NOT insert the screws through the casing. Outdoor   
					duct work must be insulated and waterproofed.   
					The room thermostat should be located on an inside wall ap-   
					proximately 56" above the floor where it will not be subject to   
					drafts, sun exposure or heat from electrical fixtures or appli-   
					ances. Follow manufacturer's instructions enclosed with the   
					thermostat for general installation procedure. Four or five color   
					coded insulated wires (minimum #18 AWG) should be used to   
					connect thermostat to unit. See Figure 2.   
					NOTE: Be sure to note supply and return openings.   
					Refer to Figure 3 for information concerning rear and bottom   
					supply and return air duct openings.   
					TABLE 3 - PHYSICAL DATA   
					DEB   
					MODELS   
					018   
					024   
					030   
					036   
					042   
					048   
					060   
					11 x 10   
					1 
					CENTRIFUGAL BLOWER (Dia. x Wd. in.)   
					FAN MOTOR HP (Three Speed)   
					ROWS DEEP   
					9 X 6   
					1 
					2 
					10 X 8   
					1 
					2 
					10 X 8   
					1 
					2 
					10 x 8   
					3 
					4 
					11 X 10   
					11 x 10   
					EVAPORATOR   
					BLOWER   
					3 
					4 
					3 
					4 
					2 
					13   
					2 
					15   
					2 
					15   
					2 
					15   
					2 
					15   
					2 
					13   
					3 
					EVAPORATOR   
					COIL   
					FINS PER INCH   
					16   
					FACE AREA (Sq. Ft.)   
					PROPELLER DIA. (in.)   
					FAN MOTOR HP   
					2.19   
					2.81   
					4.38   
					4.38   
					4.38   
					5.62   
					5.26   
					22   
					1 
					4 
					22   
					1 
					4 
					22   
					1 
					4 
					22   
					1 
					4 
					22   
					1 
					4 
					22   
					1 
					4 
					22   
					1 
					4 
					CONDENSER   
					FAN   
					NOM. CFM TOTAL   
					1,800   
					1 
					2,200   
					1 
					2,400   
					1 
					2,400   
					1 
					2,400   
					1 
					2,800   
					1 
					2,800   
					1 
					ROWS DEEP   
					CONDENSER   
					COIL   
					FINS PER INCH   
					18   
					16   
					20   
					18   
					16   
					13   
					20   
					FACE AREA (Sq. Ft.)   
					REFRIGERANT 22 (lbs./oz.)   
					FACE AREA (Sq. Ft. / Qty. / Size)   
					8.3   
					3 / 4   
					8.3   
					3 / 5   
					8.3   
					8.3   
					11.7   
					4 / 7   
					16.4   
					5 / 15   
					16.4   
					5 / 15   
					CHARGE   
					FILTER   
					3 / 13   
					3 / 10   
					2.14 / 2 / 14" x 22"   
					Recip Recip Recip   
					COMPRESSOR HERMETIC Type, (Qty. = 1)   
					Recip   
					Recip   
					Scroll   
					Scroll   
					Unitary Products Group   
					3 
				174065-YIM-A-0206   
					POWER AND CONTROL WIRING   
					Electrical line must be sized properly to carry the load. Each   
					unit must be wired with a separate branch circuit fed directly   
					from the meter panel and properly fused.   
					Field wiring to the unit must conform to provisions of the current   
					N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.   
					The unit must be electrically grounded in accordance with local   
					codes or, in their absence, with the N.E.C./C.E.C. Voltage toler-   
					ances which must be maintained at the compressor terminals   
					during starting and running conditions are indicated on the unit   
					Rating Plate and Table 3.   
					Refer to Figure 2 for typical field wiring and to the appropriate unit   
					wiring diagram for control circuit and power wiring information.   
					COMPRESSORS   
					The wiring entering the cabinet must be provided with me-   
					chanical strain relief.   
					Units are shipped with compressor mountings factory-adjusted   
					for shipping. CAUTION: Loosen compressor mounting bolts   
					half turn before operating unit.   
					A fused or HACR breaker disconnect switch should be field pro-   
					vided for the unit. If any of the wire supplied with the unit must be   
					replaced, replacement wire must be of the type shown on the wir-   
					ing diagram.   
					CONTROL WIRING   
					UNIT TERMINAL STRIP   
					NOTE:   
					THERMOSTAT   
					HEAT ANTICIPATOR   
					SHOULD BE SET AT 0.25   
					AMPS FOR ALL MODELS.   
					**   
					R 
					R 
					** = Minimum wire size of 18 AWG   
					wire should be used for all field   
					installed 24 volt wire.   
					G 
					G 
					Y 
					Y 
					PROGRAMMABLE   
					THERMOSTAT ONLY   
					24 VOLT TRANSFORMER   
					W 
					W 
					* 
					* = Only required on units with   
					supplemental electric heat.   
					C 
					C 
					CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can   
					cause improper and dangerous operation. Verify proper operation after servicing.   
					POWER WIRING   
					REFER TO ELECTRICAL DATA   
					TABLES TO SIZE THE DISCON-   
					NECT SWITCH, WIRING &   
					OVERCURRENT PROTECTION.   
					FIG. 2 - TYPICAL FIELD WIRING DIAGRAM   
					4 
					Unitary Products Group   
				174065-YIM-A-0206   
					TABLE 4 - ELECTRICAL DATA (BASIC UNIT)   
					VOLTAGE   
					LIMITATIONS COMPRESSOR   
					SUPPLY   
					AIR   
					BLOWER CIRCUIT SIZE, BREAKER POWER   
					MAX.   
					MINIMUM FUSE   
					MAX.   
					HACR   
					COND.   
					FAN   
					MOTOR,   
					FLA   
					UNIT   
					MODEL POWER SUP-   
					DEB   
					TRANSFORMER   
					SIZE (VA)   
					1 
					PLY   
					MOTOR, AMPACITY AMPS   
					FLA   
					SIZE, FACTOR   
					AMPS   
					2 
					MIN. MAX.   
					RLA   
					LRA   
					018 208/230-1-60 187   
					024 208/230-1-60 187   
					030 208/230-1-60 187   
					036 208/230-1-60 187   
					042 208/230-1-60 187   
					048 208/230-1-60 187   
					060 208/230-1-60 187   
					253   
					253   
					253   
					253   
					253   
					253   
					253   
					9.0   
					48.0   
					60.0   
					1.1   
					1.1   
					1.1   
					1.1   
					1.1   
					1.3   
					1.3   
					2.6   
					2.6   
					2.6   
					3.5   
					3.5   
					4.0   
					4.0   
					14.9   
					18.1   
					22.1   
					26.2   
					30.2   
					35.8   
					44.4   
					20   
					25   
					30   
					35   
					40   
					45   
					60   
					20   
					25   
					30   
					35   
					40   
					45   
					60   
					.96   
					.96   
					.96   
					.96   
					.96   
					.96   
					.96   
					40   
					40   
					40   
					40   
					40   
					40   
					40   
					11.5   
					14.7   
					17.3   
					20.5   
					24.4   
					28.9   
					73.0   
					94.0   
					120.0   
					140.0   
					165.0   
					= Rated in accordance with ARI Standard 110, utilization range “A”.   
					= Dual element, time delay type.   
					* = KW listed is for 240 volts, use this table for 208 or 230 volts.   
					KW CAP. MULTI-   
					ELECTRIC HEAT   
					CORRECTION   
					FACTORS   
					NOMINAL VOLTAGE   
					VOLTAGE   
					PLIER   
					.75   
					.92   
					208   
					230   
					240   
					Unitary Products Group   
					5 
				174065-YIM-A-0206   
					TABLE 5 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT)   
					COMPRESSOR   
					ELECTRIC HEAT ACCESSORY   
					SUPPLY   
					AIR   
					BLOWER   
					MOTOR,   
					FLA   
					COND.   
					FAN   
					MOTOR   
					FLA   
					MAX.   
					FUSE   
					MAX.   
					MINIMUM   
					CIRCUIT   
					AMPACITY   
					POWER   
					SUPPLY   
					HACR2   
					SIZE,1 BREAKER   
					AMPS   
					SIZE   
					TOTAL   
					AMPS   
					RLA   
					LRA   
					MODEL NO.   
					KW   
					2NH04500506   
					2NH04500706   
					1 
					2 
					3.8/5.0 *   
					5.6/7.5 *   
					18.1/20.8   
					27.1/31.3   
					25.8/29.3   
					37.1/42.3   
					30/30   
					40/45   
					30/30   
					40/45   
					018 208/230-1-60 9.0   
					024 208/230-1-60 11.2   
					48.0   
					60.0   
					1.1   
					1.1   
					2.6   
					2.6   
					2NH04500506   
					2NH04500706   
					2NH04501006   
					1 
					2 
					2 
					3.8/5.0 *   
					5.6/7.5 *   
					7.5/10.0 *   
					18.1/20.8   
					27.1/31.3   
					36.1/41.7   
					25.8/29.3   
					37.1/42.3   
					48.4/55.3   
					30/30   
					40/45   
					50/60   
					30/30   
					40/45   
					50/60   
					2NH04500506   
					2NH04500706   
					2NH04501006   
					2NH04501506   
					1 
					2 
					2 
					2 
					3.8/5.0 *   
					5.6/7.5 *   
					7.5/10.0 *   
					11.3/15.0 *   
					18.1/20.8   
					27.3/31.3   
					36.1/41.7   
					54.2/62.5   
					25.8/29.3   
					37.1/42.3   
					48.4/55.3   
					71.0/81.4   
					30/30   
					40/45   
					50/60   
					80/90   
					30/30   
					40/45   
					50/60   
					80/90   
					030 208/230-1-60 12.0   
					036 208/230-1-60 17.3   
					042 208/230-1-60 20.5   
					73.0   
					94.0   
					1.1   
					1.1   
					1.1   
					2.6   
					3.5   
					3.5   
					2NH04501006   
					2NH04501506   
					2 
					2 
					7.5/10.0 *   
					11.3/15.0 *   
					36.1/41.7   
					54.2/62.5   
					49.5/56.5   
					72.1/82.5   
					50/60   
					80/90   
					50/60   
					80/90   
					2NH04500506   
					2NH04500706   
					2NH04501006   
					2NH04501506   
					1 
					2 
					2 
					2 
					3.8/5.0 *   
					5.6/7.5 *   
					7.5/10.0 *   
					11.3/15.0 *   
					18.1/20.8   
					27.1/31.3   
					36.1/41.7   
					54.2/62.5   
					30.2/30.4   
					38.2/43.4   
					49.5/56.5   
					72.1/82.5   
					40/40   
					50/50   
					50/60   
					80/90   
					40/40   
					50/50   
					50/60   
					80/90   
					120.0   
					2NH04501006   
					2NH04501506   
					2NH04502006   
					2NH04502506   
					2 
					2 
					2 
					2 
					7.5/10.0 *   
					11.3/15.0 *   
					15.0/20.0 *   
					36.1/41.7   
					54.2/62.5   
					50.1/57.1   
					72.1/83.1   
					60/60   
					80/90   
					72.2/83.3 95.3/109.2 100/110 100/110   
					60/60   
					80/90   
					048 208/230-1-60 24.4   
					140.0   
					165.0   
					1.3   
					1.3   
					4.0   
					7.0   
					18.8/25.0 * 90.3/104.2 117.8/135.2 125/150 125/150   
					2NH04501006   
					2NH04501506   
					2NH04502006   
					2NH04502506   
					2 
					2 
					2 
					2 
					7.5/10.0 *   
					11.3/15.0 *   
					15.0/20.0 *   
					36.1/41.7 70/70   
					54.2/62.5 80/90   
					72.2/83.3 99.0/112.9 100/125 100/125   
					53.9/60.8   
					76.5/86.9   
					70/70   
					80/90   
					060 208/230-1-60 28.9   
					18.8/25.0 * 90.3/104.2 121.6/139.0 125/150 125/150   
					* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.   
					** = KW listed is for 480 volts, use table on previous page for 460 volts.   
					= Dual element, time delay type.   
					= Standard circuit breakers may be used in Canada and on applications   
					over 60 amps where the heaters are separately fused.   
					6 
					Unitary Products Group   
				174065-YIM-A-0206   
					Checking Supply Air CFM   
					a dry coil, the compressors should be deactivated while the test   
					is being run.   
					To check the supply air CFM after the initial balancing has been   
					completed:   
					4.Knowing the pressure drop across a dry coil, the actual CFM   
					through the unit can be determined from the curve in Coil Delta   
					P vs. Supply Air CFM figure.   
					1.Remove the two ¼ inch dot plugs in the duct panel.   
					2.Insert at least 8 inches of ¼ inch tubing into each of these   
					holes for sufficient penetration into the airflow on both sides of   
					the indoor coil.   
					WARNING! Failure to properly adjust the total system air quan-   
					tity can result in extensive system damage.   
					After readings have been obtained, remove the tubes and rein-   
					stall the two ¼ inch plugs removed in Step 1.   
					3.Using an inclined manometer, determine the pressure drop   
					across the dry evaporator coil. Since the moisture on an evapo-   
					rator coil may vary greatly, measuring the pressure drop across   
					a wet coil under field conditions would be inaccurate. To ensure   
					NOTE: De-energize the compressors before taking any test   
					measurements to ensure a dry indoor coil.   
					DEB Coil Delta P vs Airflow   
					DEB018   
					DEB048   
					DEB024   
					0.4   
					0.35   
					0.3   
					0.25   
					0.2   
					DEB018   
					DEB048   
					DEB024   
					DEB030, 36, & 42   
					DEB060   
					0.15   
					0.1   
					DEB060   
					0.05   
					0 
					DEB030-42   
					400   
					600   
					800   
					1000   
					1200   
					1400   
					1600   
					1800   
					2000   
					2200   
					-0.05   
					Airflow (CFM)   
					Unitary Products Group   
					7 
				174065-YIM-A-0206   
					TABLE 6 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB018   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 600 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					57   
					59   
					61   
					23.9   
					20.2   
					16.4   
					9.0   
					8.0   
					6.9   
					5.3   
					- 
					63   
					25.9   
					22.8   
					19.7   
					13.6   
					12.0   
					10.4   
					8.0   
					5.5   
					- 
					65   
					27.9   
					25.4   
					23.0   
					18.1   
					16.0   
					13.8   
					10.6   
					7.4   
					67   
					29.9   
					28.1   
					26.3   
					22.6   
					19.9   
					17.3   
					13.3   
					9.2   
					69   
					71   
					73   
					75   
					65   
					70   
					17.8   
					19.8   
					21.8   
					31.1   
					29.3   
					27.6   
					24.0   
					21.7   
					19.3   
					16.0   
					12.7   
					9.3   
					32.3   
					30.6   
					28.9   
					25.4   
					23.4   
					21.3   
					18.7   
					16.1   
					13.4   
					10.8   
					33.6   
					31.9   
					30.2   
					26.8   
					25.1   
					23.3   
					21.4   
					19.5   
					17.6   
					15.7   
					34.8   
					33.1   
					31.5   
					28.3   
					26.8   
					25.3   
					24.1   
					22.9   
					21.7   
					20.5   
					12.2   
					14.9   
					17.5   
					75   
					6.6   
					9.9   
					13.2   
					85   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					90   
					95   
					100   
					105   
					110   
					115   
					- 
					- 
					5.2   
					- 
					- 
					- 
					- 
					6.0   
					TABLE 7 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB024   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					57   
					59   
					61   
					18.0   
					15.2   
					12.4   
					9.6   
					6.7   
					6.3   
					6.0   
					5.3   
					- 
					63   
					19.6   
					16.9   
					14.3   
					11.6   
					9.0   
					8.3   
					7.6   
					6.6   
					5.5   
					- 
					65   
					21.1   
					18.6   
					16.2   
					13.7   
					11.2   
					10.3   
					9.3   
					7.8   
					6.4   
					- 
					67   
					22.6   
					20.3   
					18.1   
					15.8   
					13.5   
					12.3   
					11.0   
					9.1   
					69   
					23.9   
					21.9   
					19.8   
					17.8   
					15.7   
					14.5   
					13.3   
					11.1   
					8.9   
					71   
					73   
					75   
					65   
					70   
					13.5   
					15.0   
					16.5   
					25.3   
					23.4   
					21.6   
					19.8   
					17.9   
					16.7   
					15.5   
					13.1   
					10.6   
					8.2   
					26.6   
					25.0   
					23.4   
					21.8   
					20.2   
					19.0   
					17.8   
					15.0   
					12.3   
					9.6   
					27.9   
					26.5   
					25.2   
					23.8   
					22.4   
					21.2   
					20.0   
					17.0   
					14.0   
					11.0   
					8.0   
					10.1   
					11.8   
					13.5   
					75   
					6.7   
					8.6   
					10.5   
					80   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					5.4   
					7.5   
					85   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					90   
					95   
					100   
					105   
					110   
					115   
					7.2   
					- 
					5.3   
					6.7   
					- 
					- 
					- 
					- 
					- 
					5.7   
					6.8   
					TABLE 8 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB030   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,000 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					57   
					22.5   
					19.3   
					16.0   
					12.8   
					9.6   
					5.6   
					- 
					59   
					23.4   
					20.5   
					17.6   
					14.7   
					11.8   
					7.9   
					- 
					61   
					24.3   
					21.7   
					19.1   
					16.5   
					14.0   
					10.3   
					6.6   
					5.4   
					- 
					63   
					25.3   
					23.0   
					20.7   
					18.4   
					16.1   
					12.6   
					9.1   
					7.2   
					5.3   
					- 
					65   
					26.2   
					24.2   
					22.2   
					20.3   
					18.3   
					15.0   
					11.6   
					9.1   
					67   
					27.1   
					25.4   
					23.8   
					22.1   
					20.5   
					17.3   
					14.1   
					10.9   
					7.8   
					69   
					71   
					73   
					75   
					65   
					70   
					21.6   
					27.5   
					26.0   
					24.5   
					23.0   
					21.5   
					18.8   
					16.2   
					13.5   
					10.9   
					8.3   
					28.0   
					26.6   
					25.2   
					23.8   
					22.4   
					20.3   
					18.3   
					16.1   
					14.0   
					11.9   
					9.8   
					28.4   
					27.1   
					25.9   
					24.7   
					23.4   
					21.9   
					20.3   
					18.7   
					17.1   
					15.5   
					14.0   
					28.8   
					27.7   
					26.6   
					25.5   
					24.4   
					23.4   
					22.4   
					21.3   
					20.3   
					19.2   
					18.1   
					18.0   
					75   
					14.5   
					80   
					11.0   
					85   
					7.4   
					90   
					- 
					- 
					- 
					- 
					- 
					- 
					95   
					100   
					105   
					110   
					115   
					- 
					- 
					- 
					- 
					6.6   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					5.7   
					TABLE 9 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB036   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,200 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					57   
					13.4   
					11.4   
					9.3   
					7.2   
					5.1   
					5.5   
					5.9   
					5.5   
					- 
					59   
					15.4   
					13.4   
					11.4   
					9.4   
					7.5   
					7.4   
					7.3   
					6.6   
					6.0   
					5.4   
					- 
					61   
					17.4   
					15.5   
					13.6   
					11.7   
					9.8   
					63   
					19.4   
					17.6   
					15.8   
					13.9   
					12.1   
					11.0   
					9.9   
					65   
					67   
					69   
					71   
					73   
					75   
					65   
					70   
					11.5   
					21.4   
					19.6   
					17.9   
					16.2   
					14.5   
					12.8   
					11.2   
					10.2   
					9.3   
					23.4   
					21.7   
					20.1   
					18.4   
					16.8   
					14.6   
					12.5   
					11.4   
					10.3   
					9.2   
					24.6   
					23.3   
					22.0   
					20.6   
					19.3   
					17.6   
					15.9   
					15.0   
					14.0   
					13.1   
					12.1   
					25.9   
					24.9   
					23.9   
					22.8   
					21.8   
					20.6   
					19.3   
					18.5   
					17.7   
					16.9   
					16.1   
					27.1   
					26.4   
					25.7   
					25.1   
					24.4   
					23.6   
					22.8   
					22.1   
					21.4   
					20.7   
					20.0   
					28.4   
					28.0   
					27.6   
					27.3   
					26.9   
					26.5   
					26.2   
					25.6   
					25.1   
					24.5   
					24.0   
					9.3   
					75   
					7.1   
					80   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					85   
					90   
					9.2   
					95   
					8.6   
					100   
					105   
					110   
					115   
					7.8   
					9.0   
					7.1   
					8.2   
					- 
					6.4   
					7.3   
					8.3   
					- 
					5.7   
					6.5   
					7.3   
					8.1   
					8 
					Unitary Products Group   
				174065-YIM-A-0206   
					TABLE 10 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB042   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					57   
					21.9   
					18.5   
					15.1   
					11.7   
					8.2   
					6.5   
					- 
					59   
					23.5   
					20.3   
					17.1   
					13.9   
					10.8   
					9.1   
					7.4   
					5.8   
					- 
					61   
					25.0   
					22.1   
					19.2   
					16.2   
					13.3   
					11.7   
					10.0   
					7.9   
					63   
					26.6   
					23.9   
					21.2   
					18.5   
					15.8   
					14.2   
					12.7   
					10.0   
					7.3   
					65   
					67   
					69   
					71   
					73   
					75   
					65   
					70   
					20.3   
					28.1   
					25.7   
					23.2   
					20.8   
					18.4   
					16.8   
					15.3   
					12.0   
					8.7   
					29.7   
					27.5   
					25.3   
					23.1   
					20.9   
					19.4   
					17.9   
					14.1   
					10.2   
					6.4   
					30.6   
					28.6   
					26.6   
					24.5   
					22.5   
					21.0   
					19.5   
					16.3   
					13.0   
					9.8   
					31.6   
					29.7   
					27.8   
					25.9   
					24.0   
					22.6   
					21.1   
					18.4   
					15.8   
					13.2   
					10.5   
					32.6   
					30.8   
					29.1   
					27.3   
					25.6   
					24.1   
					22.7   
					20.6   
					18.6   
					16.5   
					14.5   
					33.6   
					32.0   
					30.4   
					28.7   
					27.1   
					25.7   
					24.3   
					22.8   
					21.4   
					19.9   
					18.5   
					16.7   
					75   
					13.0   
					80   
					9.4   
					85   
					5.7   
					90   
					- 
					- 
					- 
					- 
					- 
					- 
					95   
					100   
					105   
					110   
					115   
					- 
					- 
					5.8   
					- 
					- 
					- 
					- 
					5.5   
					- 
					- 
					- 
					- 
					- 
					- 
					6.5   
					TABLE 11 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB048   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,600 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					57   
					59   
					17.3   
					14.7   
					12.2   
					9.7   
					7.2   
					6.1   
					- 
					61   
					19.1   
					16.8   
					14.5   
					12.1   
					9.8   
					7.7   
					5.7   
					5.3   
					- 
					63   
					21.0   
					18.8   
					16.7   
					14.5   
					12.4   
					9.4   
					65   
					22.8   
					20.9   
					18.9   
					17.0   
					15.0   
					11.0   
					7.0   
					67   
					24.7   
					22.9   
					21.2   
					19.4   
					17.6   
					12.7   
					7.7   
					69   
					71   
					73   
					75   
					65   
					70   
					13.5   
					15.4   
					26.1   
					24.7   
					23.3   
					21.8   
					20.4   
					16.6   
					12.7   
					11.1   
					9.5   
					27.6   
					26.5   
					25.4   
					24.2   
					23.1   
					20.5   
					17.8   
					15.1   
					12.4   
					9.7   
					29.0   
					28.2   
					27.5   
					26.7   
					25.9   
					24.4   
					22.8   
					19.1   
					15.3   
					11.6   
					7.8   
					30.5   
					30.0   
					29.6   
					29.1   
					28.6   
					28.3   
					27.9   
					23.0   
					18.2   
					13.4   
					8.6   
					10.7   
					12.7   
					75   
					7.8   
					10.0   
					80   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					7.3   
					85   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					90   
					95   
					6.3   
					100   
					105   
					110   
					115   
					- 
					5.9   
					6.5   
					7.1   
					- 
					5.5   
					6.0   
					6.6   
					- 
					- 
					5.0   
					5.5   
					6.0   
					7.8   
					- 
					- 
					- 
					- 
					5.4   
					6.2   
					7.0   
					TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB060   
					SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 2,000 CFM/TON   
					INDOOR WB TEMPERATURE (F)   
					OUTDOOR   
					TEMPERATURE   
					(F)   
					55   
					25.3   
					22.2   
					19.2   
					16.1   
					13.1   
					10.3   
					7.6   
					6.6   
					5.6   
					- 
					57   
					25.8   
					23.0   
					20.1   
					17.3   
					14.5   
					11.7   
					8.9   
					59   
					26.3   
					23.7   
					21.1   
					18.5   
					15.9   
					13.1   
					10.3   
					8.9   
					61   
					63   
					65   
					67   
					69   
					71   
					73   
					75   
					65   
					70   
					26.8   
					24.4   
					22.1   
					19.7   
					17.3   
					14.5   
					11.6   
					10.1   
					8.6   
					27.3   
					25.1   
					23.0   
					20.9   
					18.8   
					15.9   
					13.0   
					11.3   
					9.6   
					27.8   
					25.9   
					24.0   
					22.1   
					20.2   
					17.3   
					14.3   
					12.5   
					10.6   
					8.7   
					28.3   
					26.6   
					24.9   
					23.3   
					21.6   
					18.6   
					15.7   
					13.6   
					11.6   
					9.5   
					28.7   
					27.4   
					26.1   
					24.7   
					23.4   
					21.1   
					18.7   
					16.7   
					14.6   
					12.5   
					10.5   
					29.1   
					28.2   
					27.2   
					26.2   
					25.2   
					23.5   
					21.8   
					19.7   
					17.6   
					15.6   
					13.5   
					29.6   
					28.9   
					28.3   
					27.7   
					27.0   
					25.9   
					24.8   
					22.7   
					20.7   
					18.6   
					16.5   
					30.0   
					29.7   
					29.4   
					29.1   
					28.9   
					28.3   
					27.8   
					25.8   
					23.7   
					21.6   
					19.5   
					75   
					80   
					85   
					90   
					95   
					100   
					105   
					110   
					115   
					7.7   
					6.6   
					7.6   
					5.4   
					6.2   
					7.0   
					7.9   
					- 
					- 
					- 
					5.5   
					6.2   
					6.8   
					7.5   
					Unitary Products Group   
					9 
				174065-YIM-A-0206   
					HIGH VOLTAGE CONN.   
					" DIA. KNOCKOUT   
					FRONT   
					“A”   
					COMPRESSOR   
					SERVICE ACCESS   
					COMPARTMENT PANEL   
					HIGH VOLTAGE CONN.   
					" DIA. KNOCKOUT   
					1 
					DIMENSION   
					“A”   
					LOW VOLTAGE CONN.   
					“ DIA. KNOCKOUT   
					UNIT SIZE   
					(OVERALL)   
					2 3   
					018 - 042   
					048 - 060   
					33 1   
					8 
					2 
					411   
					2 
					SIDE SUPPLY   
					AIR OPENING   
					REFRIGERANT   
					CONNECTIONS   
					SIDE RETURN   
					AIR OPENING   
					ELECTRICAL/FILTER   
					SERVICE ACCESS   
					COMPARTMENT PANEL   
					HIGH VOLTAGE CONN.   
					" DIA. KNOCKOUT   
					17   
					28   
					47   
					(OVERALL)   
					17   
					28   
					1 
					22   
					49   
					2 1   
					22   
					2 
					(OVERALL)   
					3 
					LOW VOLTAGE CONN.   
					“ DIA. KNOCKOUT   
					11   
					2 
					FRONT   
					UNIT CONDENSATE   
					CONNECTION “ NPTI   
					(TRAP REQUIRED)   
					4 1   
					2 
					HIGH VOLTAGE   
					CONN. 1 “ x “ DIA.   
					KNOCKOUT   
					All dimensions are in inches. They are   
					subject to change without notice. Certified   
					dimensions will be provided upon request.   
					SIDE SUPPLY   
					AIR OPENING   
					14   
					43   
					40   
					26   
					28   
					22   
					6 
					14   
					BACK   
					OUTDOOR   
					COIL   
					3 
					CONDENSATE   
					DRAIN “ NPTI   
					SIDE RETURN   
					AIR OPENING   
					BOTTOM SUPPLY   
					AIR OPENING   
					2 3   
					8 
					14   
					13   
					4 
					15   
					3 
					15   
					4 
					13   
					4 
					15   
					28   
					CLEARANCES   
					(Minimum)   
					BOTTOM RETURN   
					AIR OPENING   
					3 
					Front   
					Back   
					12"   
					0"   
					13   
					4 
					Left Side (Filter Access) 24"   
					Units may be installed on combustible floors made from wood or class A,   
					B or C roof covering material.   
					Right Side   
					Below Unit1   
					24"   
					0"   
					Units must be installed outdoors. Overhanging structures or shrubs   
					should not obstruct outdoor air discharge outlet.   
					36" (For Condenser   
					Air Discharge)   
					Above Unit2   
					FIG. 3 - DIMENSIONS AND CLEARANCES   
					10   
					Unitary Products Group   
				174065-YIM-A-0206   
					SEQUENCE OF OPERATION   
					Heating   
					Cooling   
					The following sequences of operation are based on using a   
					standard single-stage cooling thermostat.   
					WITH POWER TO UNIT AND THERMOSTAT IN HEATING   
					MODE.   
					WITH POWER TO UNIT AND THERMOSTAT IN COOLING   
					MODE.   
					1. If the fan switch on the thermostat is in the “ON” position,   
					the 24 volts at “G” will energize the “K1" relay contacts, and   
					energize the indoor blower motor. If the fan switch on the   
					thermostat is in the ”AUTO" position, the blower will oper-   
					ate only when there is a call for heating by the thermostat.   
					1. If the fan switch on the thermostat is in the “ON” position,   
					the 24 volts at “G” will energize the “K1" relay on the fan   
					control board, close the ”K1" relay contacts, and energize   
					the indoor blower motor. If the fan switch is in the “AUTO”   
					position, the blower will operate only when there is a call for   
					cooling by the thermostat.   
					2. On a call for heating, the thermostat will send 24 volts to   
					“W1" on the fan control board. The 24 volts signal will ener-   
					gize relay ”K2" on the fan control board, and the first stage   
					of electric heat will be energized.   
					2. On a call for cooling, the thermostat will send 24 volts to “Y”   
					on the fan control board. The 24 volt signal will energize   
					contactor “M1", and power will be supplied to the compres-   
					sor and outdoor fan motor. If the fan switch on the thermo-   
					stat is on the ”AUTO" position, the thermostat will also send   
					a 24 volt signal to “G” on the fan control board and the in-   
					door blower will operate as indicated in step 1.   
					3. When the heating demand is satisfied, the electric heat will   
					be de-energized when the 24 volt “W1" and ”W2" signals   
					are removed. If the fan switch on the thermostat is in the   
					“ON” position, the indoor blower will continue to run. If the   
					fan switch is in the “AUTO” position, the “K1" relay will open   
					and de-energize the indoor blower motor after the appropri-   
					ate time delay.   
					3. When the demand for cooling has been satisfied, the “M1"   
					contactor will be de-energized when the 24 volt ”Y" signal is   
					removed. If the fan switch on the thermostat is energized   
					when the 24 volt “Y” signal is removed. If the fan switch on   
					the thermostat is in the “ON” position, the indoor blower will   
					continue to run. If the fan switch is in the “AUTO” posi-   
					tion, the 24 volt “G” signal will be removed, and after a   
					60 second delay, the “K1" relay will open and de-   
					energize the indoor blower motor,   
					Please refer to Table 13 for more information.   
					TABLE 13 - THERMOSTAT SIGNALS (SINGLE PHASE UNITS)   
					BOARD FUNCTION   
					BOARD FUNCTION   
					ON FAN INSTANT ON   
					“G”   
					OFF FAN INSTANT OFF   
					FAN INSTANT ON   
					COMPRESSOR AND OUTDOOR FAN INSTANT ON   
					FAN INSTANT ON   
					HEATER BANK 1 ELEC. HEAT INSTANT ON   
					ON   
					ON   
					“G”   
					“Y”   
					“W1"   
					”W2"   
					COMPRESSOR AND OUTDOOR FAN INSTANT OFF   
					FAN 60 SECOND DELAY OFF   
					HEATER BANK 1 ELEC. HEAT INSTANT OFF   
					FAN 5 SECOND DELAY OFF   
					OFF   
					OFF   
					FAN INSTANT ON   
					FAN INSTANT ON   
					HEATER BANK 1 ELEC. HEAT INSTANT ON   
					1 
					ON   
					ON HEATER BANK 1 ELEC. HEAT 2 SEC. DELAY OFF   
					HEATER BANK 2 ELEC. HEAT INSTANT ON   
					“G”   
					“W1"   
					1 
					HEATER BANK 1 ELEC. HEAT 2 SEC. DELAY OFF   
					OFF HEATER BANK 2 ELEC. HEAT INSTANT OFF   
					FAN 5 SECOND DELAY OFF   
					HEATER BANK 1 ELEC. HEAT INSTANT OFF   
					FAN 5 SECOND DELAY OFF   
					OFF   
					FAN INSTANT ON   
					FAN INSTANT ON   
					HEATER BANK 1 ELEC. HEAT INSTANT ON   
					HEATER BANK 2 ELEC. HEAT 10 SECOND DELAY ON   
					HEATER BANK 3 ELEC. HEAT 20 SECOND DELAY ON   
					HEATER BANK 1 ELEC. HEAT INSTANT ON   
					HEATER BANK 2 ELEC. HEAT 10 SECOND DELAY ON   
					HEATER BANK 3 ELEC. HEAT 20 SECOND DELAY ON   
					ON   
					ON   
					“G”   
					“W1"   
					”W2"   
					“W1"   
					”W2"   
					HEATER BANK 1 ELEC. HEAT INSTANT OFF   
					1 
					HEATER BANK 2 ELEC. HEAT 2 SECOND DELAY ON   
					HEATER BANK 3 ELEC. HEAT 1 SECOND DELAY ON   
					FAN 6 12 SECOND DELAY OFF   
					STAGE 1 ELEC. HEAT INSTANT OFF   
					1 
					HEATER BANK 2 ELEC. HEAT 2 SECOND DELAY ON   
					HEATER BANK 3 ELEC. HEAT 1 SECOND DELAY ON   
					FAN 6 12 SECOND DELAY OFF   
					OFF   
					OFF   
					Unitary Products Group   
					11   
				174065-YIM-A-0206   
					SECURE OWNER'S APPROVAL: When the system is functioning properly, secure the owner's approval. Show him the   
					location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature   
					settings within the limitations of the system.   
					MAINTENANCE   
					NORMAL MAINTENANCE   
					WARNING:Prior to any of the following maintenance proce-   
					dures, shut off all power to the unit, to avoid per-   
					sonal injury.   
					OUTDOOR COIL- Dirt should not be allowed to accumulate on   
					the outdoor coil surface or other parts in the air circuit. Cleaning   
					should be as often as necessary to keep the coil clean. Use a   
					brush, vacuum cleaner attachment, or other suitable means. If   
					water is used to clean the coil, be sure that the power to the unit   
					is shut off prior to cleaning.   
					Periodic maintenance consists of changing or cleaning filters   
					and general cleaning of the outdoor coil.   
					FILTERS - Inspect once a month. Replace Disposable or clean   
					Permanent Type as necessary. DO NOT replace Permanent   
					Type with Disposable.   
					CAUTION: Exercise care when cleaning the coil so that the   
					coil fins are not damaged.   
					Do not permit the hot condenser air discharge to be   
					obstructed by overhanging structures or shrubs.   
					MOTORS - Indoor and outdoor fan motors are permanently lu-   
					bricated and require no maintenance.   
					12   
					Unitary Products Group   
				174065-YIM-A-0206   
					FOR DUAL POINT   
					ELECTRIC HEAT   
					POWER SUPPLY   
					SEE DETAIL A   
					SEE   
					DETAIL   
					"B"   
					SECONDARY POWER SUPPLY   
					FOR DUAL POINT ELEC HEAT   
					208/230-1-60   
					USE COPPER   
					CONDUCTORS ONLY   
					POWER SUPPLY   
					208/230-1-60   
					USE COPPER   
					CONDUCTORS ONLY   
					F2   
					F4   
					F1   
					F3   
					709/BK   
					703/BK   
					710/PR   
					705/PR   
					(M1)   
					(M1)   
					(K3)   
					(K5)   
					(HTR2)   
					(HTR3)   
					711/BK   
					713/PR   
					F5   
					F6   
					706/BK   
					714/BK   
					708/PR   
					716/PR   
					(K4)   
					(K6)   
					(HTR4)   
					(HTR5)   
					DETAIL A   
					DUAL POINT ELECTRIC HEAT (SEE NOTE 9)   
					FIG. 4 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY)   
					Unitary Products Group   
					13   
				174065-YIM-A-0206   
					TYPICAL WIRING DIAGRAM LEGEND   
					CB   
					CIRCUIT BREAKER 24V, 3 AMP   
					CCH   
					COMPR   
					DS   
					F1 F2 F3   
					F4 F5 F6   
					F7 F8 F9   
					F24   
					CRANKCASE HEATER (OPTIONAL)   
					COMPRESSOR   
					DEFROST SENSOR, CLOSES @ 31˚F, OPENS @ 55˚F.   
					FUSES, LINE VOLTAGE - 60 AMP (10, 15, 20 & 25 KW ELEC HEAT)   
					FUSES, LINE VOLTAGE - 30 AMP (10, 15, 20 & 25 KW ELEC HEAT)   
					FUSES, LINE VOLTAGE - 30 AMP (20, 25 KW ELEC HEAT)   
					FUSE 24V SECONDARY, 5 AMP   
					FS   
					HP   
					FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26˚ F   
					HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 280 PSIG   
					ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT)   
					ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT)   
					ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)   
					ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 & 25 KW ELEC HEAT)   
					ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)   
					ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)   
					RELAY INDOOR FAN MOTOR   
					HTR 1   
					HTR 2   
					HTR 3   
					HTR 4   
					HTR 5   
					HTR 6   
					K1   
					K2   
					RELAY ELECTRIC HEATER   
					K3   
					RELAY ELECTRIC HEATER, 24 VDC COIL   
					K7   
					RELAY LIMIT TRIP, 25 VDC COIL   
					LP   
					LS   
					M1   
					M2   
					LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG   
					LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY)   
					CONTACTOR, COMPRESSOR & OUTDOOR FAN   
					CONTACTOR, ELECTRIC HEAT, 230V COIL   
					M3   
					CONTACTOR, ELECTRIC HEAT, 230V COIL   
					PTCR   
					RC1/RC2   
					RC1   
					RC2   
					RC3   
					START ASSIST (OPTIONAL DEVICE)   
					COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR   
					COMPRESSOR START CAPACITOR (ALTERNATE)   
					OUTDOOR FAN RUN CAPACITOR (ALTERNATE)   
					INDOOR FAN RUN CAPACITOR   
					RVS   
					REVERSING VALVE SOLENOID   
					S2/P2   
					S3/P3   
					S4/P4   
					S3/P3   
					T1   
					SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE   
					SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE   
					SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V   
					SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V   
					TRANSFORMER, 24V, 40 VA   
					TB2   
					TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS   
					IDENTIFIED TERMINAL ON RUN CAPACITOR   
					ROOM THERMOSTAT 24V CONNECTIONS   
					TB1 ON FAN/ELEC HEAT CONTROL BOARD   
					FACTORY WIRING AND DEVICES   
					OPTIONAL WIRING AND DEVICES   
					FIELD WIRING   
					TYPICAL WIRING DIAGRAM NOTES   
					14   
					Unitary Products Group   
				174065-YIM-A-0206   
					NOTES   
					Unitary Products Group   
					15   
				NOTES   
					Unitary Products Group   
					5005 York Drive, Norman Oklahoma 73069   
					Subject to change without notice. Printed in U.S.A.   
					Copyright © by York International Corporation 2006. All Rights Reserved.   
					Supersedes: Nothing   
					174065-YIM-A-0206   
				 | 
Toshiba Air Conditioner Mmy Map1604ht8z E User Manual
Siemens Barcode Reader Simatic S7 400 User Manual
Samsung Clp 315wkg User Manual
Philips Sc469sbc User Manual
MCCULLOCH CABRIO 433L User Manual
DELL S2421HS User Manual
CRAFTSMAN 921.164710 User Manual
BLACK DECKER HS2000 User Manual
ASUS VE228S User Manual
ACER CHROMEBOOK 514 CB514 1W User Manual