036-21411-002-A-0204
®
FLEXIBLE EASY TO INSTALL SINGLE
PACKAGE UNITS.
TECHNICAL GUIDE
SUNLINE PLUS™
AIR-COOLED
GENERAL
YORK Model DEE/DEG units are single package air condi-
tioners designed for outdoor installation on a rooftop or a
slab. These units can be equipped with field installed elec-
tric heaters for cooling/heating applications or factory
installed gas heat. The units are completely assembled on
rigid, permanently attached base rails. All piping, refriger-
ant charge, and electrical wiring is factory installed and
tested. The units require only electric power and duct con-
nections at the point of installation.
AIR CONDITIONERS
D1EG/D1EE036, 048, & 060
3, 4, AND 5 NOMINAL TONS
11 - 11.5 SEER
FEATURING
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
COMMON FOOTPRINT / COMMON CABINET
HIGH EFFICIENCY
CONVERTIBLE AIRFLOW DESIGN
OPTIONAL MOTORIZED AIR DAMPER
OPTIONAL MANUAL OUTDOOR DAMPER
FLEXIBLE INDOOR AIRFLOWS
FULL PERIMETER BASE RAILS
INSTALLER FRIENDLY CONTROL CIRCUIT
EASY UTILITY CONNECTIONS
1” OR 2” FILTERS WITH NO MODIFICATIONS
DIRECT DRIVE
OPTIONAL BELT DRIVE
1 YEAR LIMITED WARRANTY
COMPRESSORS 5 YEAR WARRANTY
10 YEAR LIMITED WARRANTY ON GAS-FIRED
HEAT EXCHANGERS
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21411-002-A-0204
Adjustable belt drive blowers are available on all models from
the factory for complete airflow flexibility.
DESCRIPTION
YORK Sunline Plus™ units are high efficiency, convertible,
single package air conditioners with a common cabinet and a
common roof curb for the 3, 4 and 5 ton sizes. The units were
designed for light commercial and commercial applications.
They can easily be installed on a roof curb, slab, roof jack or
frame.
FIELD--INSTALLED ACCESSORIES -- Accessories were
designed for quick and easy installation. The motorized
damper and economizers simply slide in, and electrical con-
nections are made by modular plugs. Electric heaters mount
easily, and knockouts are provided in the internal partitions to
connect the elements to the control box single point kit.
All units are self--contained and assembled on rigid full
perimeter base rails with fork lift slots on three sides and
holes for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to provide for a quick
and easy field installation.
The motorized air damper includes a slid--in/plug--in damper
assembly with a rainhood and filters. The outdoor air damp-
ers open when the indoor fan motor is energized. The
damper is capable of providing 0% through 100% of outdoor
return air opening.
The units are available in cooling only, and cooling with gas
heat. Electric heaters are available as field--installed acces-
sories.
The manual outdoor damper provides 0% through 35% or 0%
through 100% of return air opening (field adjustable).
Designed for duct mounted side or bottom supply/return
applications. Includes rain hood assembly and filter.
Both bottom and side duct connections are available without
having to swap panels. The installer simply removes the duct
covers for the desired configuration. Economizers may be
used on either bottom and side duct applications with no
modifications required.
The 14" high roof curb is shipped knocked down. An insu-
lated deck is not required because the bottom of the unit is
insulated.
Low ambient controls are available to provide stable unit
operation at outdoor temperatures down to 0 ºF.
All models include a 5--year limited warranty on compres-
sors, a 10--year limited warranty on gas--fired heat exchang-
ers and a 1--year limited warranty on other parts.
Propane, high altitude and low NOx kits are also available to
cover all gas heating applications.
FEATURES
WIDE RANGE OF INDOOR AIRFLOWS -- All models oper-
ate over a wide range of design conditions with a 3--speed
direct--drive fan motor. Belt--drive blowers are also available
on all models.
COMMON FOOTPRINT/COMMON CABINET -- All model
sizes and configurations share a common cabinet and a com-
mon roof curb. The installer has the flexibility of setting one
curb and placing the proper tonnage unit on that curb after
the internal load has been determined. He can even decide
between gas or electric heat after the curb has been set.
FULL PERIMETER BASE RAILS -- The permanently
attached base rails provide a solid foundation for the entire
unit and protect the unit during shipment. The rails provide
fork lift access from 3 sides, and rigging holes are also pro-
vided so that an overhead crane can be used to place the
units on a roof.
HIGH EFFICIENCY -- All units have a high cooling efficiency
of at least 11.0 SEER and gas / electric models have an
AFUE as high as 80.9%. All efficiencies exceed legislated
minimum levels and provide low operating costs.
SYSTEM PROTECTION -- Internal overload protection is
standard on all compressors. Every unit has a liquid line filter-
-drier, high and low pressure/loss of charge switches and a
suction line freezestat to protect all system components. All
units will provide cooling at ambient temperatures down to 45
ºF.
CONVERTIBLE AIRFLOW DESIGN -- Both the side and bot-
tom duct openings are covered when they leave the factory. If
a side supply / side return is desired, you simply remove the
two side duct covers from the outside of the unit and discard
them. If a bottom supply / bottom return is desired, you simply
remove the two knockout panels from the base of the unit and
discard them. No panel cutting or swapping is required! Con-
vertible airflow design allows maximum field flexibility and
minimum inventory.
UTILITY CONNECTIONS MADE EASY -- Gas and electric
utility knockouts are provided in the unit base as well as the
side of the unit. A clearly identified location is provided to
mount a field supplied electrical disconnect switch. Utility
connections can be made quickly and with a minimum
amount of field labor.
FACTORY--INSTALLED OPTIONS -- Economizers can be
installed at the factory. The economizers are shipped
installed and wired. Only the rain hood needs to be field
assembled and installed. Field labor dollars can be saved by
having the components arrive already installed.
SIMPLE CONTROL CIRCUIT -- A low voltage printed circuit
board contains a compressor lockout indicator light and a low
Unitary Products Group
3
036-21411-002-A-0204
voltage terminal strip. An additional set of pin connectors is
also provided to simplify the field interface of external con-
trols. Mate--n--lock plug connectors are used where line and
low voltage wires pass through internal bulkheads. This
allows for easier troubleshooting and component replace-
ment. The electrical control box is not located in the compres-
sor compartment so the access cover can be removed for
troubleshooting without affecting the normal system operat-
ing pressures.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER -
Includes the same damper system and rain hood with filters
as described for a single enthalpy economizer except this
accessory contains two enthalpy sensors. It uses a differen-
tial enthalpy control that compares the outdoor air versus the
return air. The logic module then optimizes the economizer
operation for additional savings over the single input econo-
mizer.
MOTORIZED AIR DAMPER - Includes a slid-in/plug-in
damper assembly with a rainhood and filters. The outdoor air
dampers open when the indoor fan motor is energized. The
damper is capable of providing 0% through 100% of outdoor
return air opening.
AIR FILTERS -- Units are shipped with 1" throwaway filters.
The unit filter racks can accommodate 1" or 2" filters without
any modifications.
FACTORY-INSTALLED OPTIONS
MANUAL OUTDOOR DAMPER - Provides 0% through 35%
or 0% through 100% of return air opening (field adjustable).
Designed for duct mounted side or bottom supply/return
applications. Includes rain hood assembly and filter.
ECONOMIZERS: Units equipped with a factory-installed
economizer option have dampers that are positioned by a
spring return, fully modulating damper actuator and are capa-
ble of introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is determined by a single input electronic enthalpy
control or by a dual input electronic enthalpy control. Simulta-
neous compressor and economizer operation is also possi-
ble.
ELECTRIC HEATERS - Include nickel chromium elements, a
terminal block, fuses (where required by UL), all the neces-
sary connectors and hardware. All heaters utilize single point
power supply hookup. Capacities from 5 KW through 30 KW
heating are available.
FUSE BLOCK KITS - These kits have a fuse box with a fuse
block and fuses. They're available for all 460-3-60 volt heat-
ers and 208/230-3-60 volt heaters 7 KW and smaller.
The single enthalpy system contains a sensor that monitors
the outdoor air which automatically operates the damper
actuator allowing the dampers to open or close.
OUTDOOR THERMOSTAT - A 24-volt thermostat providing
two stages of control for units equipped with electric heat
accessories.
The dual enthalpy system contains a second sensor that
monitors both the temperature and the humidity of the return
air in addition to the outdoor air sensor described for a single
enthalpy system. The logic module compares the inputs from
both sensors and switches to economizer operation when-
ever the outdoor air is cooler than the return air for maximum
efficiency of the economizer system.
ROOF CURB - This 14" high full perimeter roof curb is
shipped knocked down for field assembly and contains duct
supports that can easily be shifted for the desired unit duct
arrangement. No insulated deck is required because the unit
underside is insulated.
The economizer is completely wired and installed at the fac-
tory. Only the outdoor air hood, including its filters, need be
assembled and installed in the field.
START ASSIST KIT - Provides increased starting torque for
single phase units in areas with low voltage conditions. It con-
tains a 12.5 OHM PTCR temperature resistor with a support
clip and hardware for mounting.
BELT DRIVE BLOWERS: Adjustable belt-drive blowers pro-
viding maximum flexibility to handle many airflow require-
ments, are available on all models.
LOW AMBIENT KIT - A head pressure controller maintains
stable system operation by reducing the speed of the con-
denser fan motor when the outdoor temperature is between
45 and 0 ºF. Condenser fan motors with ball bearings and
heavier windings are also available for these low ambient
applications.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -
Includes a slide-in / plug-in damper assembly with fully modu-
lating spring return motor actuator capable of introducing up
to 100% outdoor air, one outdoor air electronic enthalpy sen-
sor and a rain hood with filters. The rain hood is painted to
match the basic unit and must be field-assembled before
installation. Economizer dampers are 2% low leakage type.
ANTI-RECYCLE TIMER - A timer to prevent the unit com-
pressor from short cycling. It assures a 5-minute off-time
between compressor cycles.
4
Unitary Products Group
036-21411-002-A-0204
PROPANE CONVERSION KIT - Converts a gas-fired heater
from natural gas to propane. It contains main burner orifices,
a pilot orifice and a regulator spring.
GAS PIPING - This kit contains 1/2" pipe nipples, fittings and
gas cock (including panel access gaskets) required for bot-
tom gas supply connection with external shut-off.
LOW NOx KIT (natural gas furnaces only) - Contains five
stainless steel expanded metal sheets for mounting into the
heat exchanger tubes to meet the California low nitrous oxide
emission requirements.
OUTDOOR COIL GUARD - Consists of grille-type sections
for installation over the outdoor coil to protect it from damage.
WALL THERMOSTAT - The units are designed to operate
with 24-volt electronic and electro-mechanical thermostats.
All units can operate with single stage heat / single stage cool
thermostats - with or without the economizer.
HIGH ALTITUDE CONVERSION (NATURAL AND PRO-
PANE) - Provides orifices for proper furnace operation at alti-
tudes up to 6000 feet. For propane applications, the propane
conversion kit will also be required.
L
P
O
N
G
L
A
S
T
I
N
G
O
W
D
E
R
P
A
I
N
T
F
I
N
I
S
H
2
T
0
G
A
U
G
E
A
L
U
M
I
N
I
Z
E
D
S
T
E
E
L
L
A
O
W
V
O
L
T
A
G
E
R
E
L
A
Y
B
O
A
R
D
U
B
U
L
A
R
H
E
A
T
E
X
C
H
A
N
G
E
R
E
L
L
E
C
T
R
I
C
H
E
A
T
A
C
e
C
E
S
S
O
R
Y
N
D
T
E
R
M
I
N
A
L
S
T
R
I
P
O
C
A
T
I
O
N
(
E
l
e
c
/
E
l
c
U
n
i
t
s
)
D
I
R
E
C
T
D
R
I
V
E
B
L
O
W
E
R
M
O
T
O
R
(
B
e
l
t
D
r
i
v
e
O
p
t
i
o
n
P
W
O
W
E
R
V
E
N
T
E
R
M
O
T
O
R
a
m
l
s
o
a
v
a
i
l
a
b
l
e
o
n
s
o
m
e
E
M
(
L
E
C
T
R
I
C
A
L
D
I
S
C
O
N
N
E
C
T
I
T
H
P
O
S
T
P
U
R
G
E
C
Y
C
L
E
o
d
e
l
s
)
O
U
N
T
n
I
N
G
L
O
C
A
T
I
O
N
F
i
e
l
d
I
s
t
a
l
l
e
d
)
C
A
C
O
P
P
E
R
T
M
U
B
E
/
L
U
M
I
N
U
F
I
N
O
N
D
E
N
S
E
R
C
O
I
L
E
C
O
N
O
M
I
Z
E
R
H
O
O
D
H
C
I
O
G
H
E
F
F
I
C
I
E
N
C
Y
O
U
T
D
O
O
I
R
A
I
R
O
P
E
N
I
N
N
G
M
P
R
E
S
S
O
R
S
F
I
O
R
S
L
D
E
-
I
N
C
/
P
L
U
O
G
I
N
T
E
R
N
A
L
E
O
N
M
I
Z
E
R
S
D
I
D
E
R
E
T
U
R
N
A
I
R
U
C
T
O
P
E
N
I
N
G
F
U
L
L
P
E
R
I
M
E
T
E
R
B
A
S
E
R
A
I
L
S
W
L
I
T
H
F
O
R
K
L
L
I
E
F
T
S
L
O
T
S
A
N
D
I
F
T
I
N
G
H
O
S
B
D
O
T
C
T
O
M
R
E
T
U
R
N
A
I
R
U
T
O
P
E
N
I
N
G
K
G
N
O
C
K
O
U
T
F
O
R
S
I
D
E
A
S
S
U
P
P
L
Y
E
N
T
R
Y
K
G
N
O
C
K
O
U
T
F
O
R
B
O
T
T
O
M
3
C
/
4
"
P
V
C
F
E
M
A
L
E
A
S
S
U
P
P
L
Y
E
N
T
R
Y
O
N
D
E
N
S
A
T
E
D
R
A
I
N
M
O
D
E
L
D
E
G
T
E
R
M
I
N
A
L
B
L
O
C
K
K
P
N
O
O
C
K
O
U
T
F
O
R
B
O
T
T
O
M
K
N
O
C
K
O
U
T
S
F
O
R
S
I
D
E
(
F
o
r
S
i
n
g
l
e
P
o
i
n
t
P
o
c
w
e
r
(
G
a
s
H
e
a
t
i
n
g
)
W
E
R
E
N
T
R
Y
P
E
O
N
W
E
R
A
N
D
C
O
N
T
R
O
L
S
u
p
p
l
y
o
n
E
l
e
c
/
E
l
e
U
n
i
t
s
)
T
R
Y
FIGURE 1 - SUNLINE PLUS COMPONENT LOCATION
Unitary Products Group
5
036-21411-002-A-0204
TABLE 1: CAPACITY RATINGS - COOLING / ELECTRIC HEATING
ARI RATINGS1
COOLING CAPACITY 80 / 67-95°F
NOMINAL ELECTRIC HEAT CAPACITY2 (kW)
SOUND
RATING3
(dBels)
MODEL
SEER4
EER5
MBH
42.5
49.5
58.5
240V
480V
600V
5, 7, 10, 15 &
20
5, 7, 10, 15 &
20
5, 7, 10, 15,
20, & 30
DEE036
DEE048
DEE060
11.5
11.0
11.0
10.10
86.0
86.0
86.0
7, 10, 15 & 20
7, 10, 15 & 20
10, 15, & 20
10, 15, & 20
10.0
7, 10, 15, 10,
& 30
10, 15, 20 &
30
10.05
1.
2.
3.
4.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
Heaters are available as accessories - all with single point power supply
Not ARI required
Rated in accordance with ARI Standard 270.
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
divided by the total electric power input in watt-hours during the same period.
5.
EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given
set of rating conditions, expressed in BTUH per watt (BTUH/watt).
TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING
ARI RATINGS1
GAS HEAT CAPACITY
COOLING CAPACITY 80 /
67-95°F
SOUND
TEMP.
RISE
(°F)
MODEL
INPUT
(MBH)
OUTPUT
(MBH)
GASE LINE SIZE
(in. O.D.)
RATING2
(dBels)
AFUE3 (%)
S.S.E.4 (%)
SEER5
11.5
11.5
11.0
11.0
11.0
11.0
EER6
10.1
10.1
10.0
10.0
10.05
10.05
MBH
42.5
42.5
49.5
49.5
58.5
58.5
DEG036N040
DEG036N079
DEG048N060
DEG048N099
DEG060N079
DEG060N099
86
86
86
86
86
86
50
100
75
125
100
125
40
79
59
99
79
99
80.9
80.5
80.9
80.3
80.5
80.3
81.6
80.8
81.6
80.6
80.8
80.6
15-45
40-70
25-55
45-75
25-55
35-65
1/2
1/2
1/2
1/2
1/2
1/2
1.
Ratings are in accordance with ARI Standard 210.
Not ARI required
2.
3.
4.
5.
Sound ratings are in accordance with ARI Standard 270.
AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.
S.S.E. = Steady State Efficiency (Percent Output).
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
divided by the total electric power input in watt-hours during the same period.
6.
EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given
set of rating conditions, expressed in BTUH per watt (BTUH/watt).
TABLE 3: SOUND POWER RATINGS1
SOUND POWER (dB 10-12 WATTS)
OCTAVE BAND CENTERLINE FREQUENCY (Hz)
ESP
BLOWER
SPEED
LOW
HIGH
HIGH
UNIT
SIZE
CFM
dBA
@ 10Ft2
41
42
43
SWL
dB(A)
IWG
0.60
0.55
0.45
kW
0.60
0.80
1.00
63
84
85
86
125
84
85
250
74
75
500
67
68
1000
69
2000
62
4000
57
8000
52
036
048
060
1200
1600
2000
74
75
76
70
63
58
53
54
86
76
69
71
64
59
1.
These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The
dBA values provided are to be used fro reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.
2.
At a distance of 10 feet from the blower.
6
Unitary Products Group
036-21411-002-A-0204
TABLE 4: PHYSICAL DATA - BASIC UNIT
DEE/DEG
048
MODELS
036
060
Centrifugal Blower (Dia. x Wd. in.)
EVAPORATOR
12 x 10
1/2
1.5
12 x 10
3/4
1.5
12 x 10
Fan Motor HP (Direct - Drive)
BLOWER
1
Fan Motor HP (Belt - Drive)
1.5
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
3
13
3.6
3
13
4.3
3
13
5.1
EVAPORATOR
COIL
Propeller Dia. (in.)
Fan Motor HP
Nom. CFM. Total
22
1/2
4,500
22
1/2
4,200
22
1/2
4,500
CONDENSER
FAN
Rows Deep
2
2
2
CONDENSER
Fins Per Inch
18
18
18
COIL
Face Area (Sq. Ft.)
17.1
17.1
17.1
Quantity Per Unit (15” x 20” x 1”)
Quantity Per Unit (14” x 25” x 1”)
Total Face ARea (Sq. Ft.)
2
1
6.6
2
1
6.6
2
1
6.6
AIR FILTERS1
SYSTEM CHARGE
COMPRESSOR
Refrigerant 22 (Lbs./Oz.)
Quantity Per Unit: (Hermetic Type)
9/12
1 / Recpt
9/8
1 / Recpt
9/8
1 / Scroll
1.
Filter racks are adapted for 1” or 2” thick filters.
Unitary Products Group
7
036-21411-002-A-0204
TABLE 5: COOLING CAPACITIES - 3 TON (DEE / DEG036)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
95°F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
TOTAL
CAP.1
MBH
POWER
INPUT2
kW
TOTAL
POWER
INPUT2
kW.
.1
CAP
WB
MBH
CFM
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
55
52
42
42
51
49
39
40
48
46
36
37
46
44
35
36
45
42
34
35
3.4
3.3
3.2
3.2
3.3
3.3
3.2
3.2
3.2
3.3
3.2
3.2
3.3
3.3
3.2
3.2
3.3
3.2
3.2
3.1
35
47
42
42
32
42
39
40
28
37
36
37
26
34
35
36
24
31
34
35
31
42
42
42
28
38
39
40
24
34
36
37
23
31
34
35
21
29
32
33
26
38
42
42
24
34
37
38
21
30
33
35
19
28
31
32
18
26
26
30
22
33
37
38
20
30
33
34
17
27
29
31
16
25
28
29
15
23
26
27
18
29
33
33
16
26
29
30
14
23
26
27
13
22
24
26
13
20
23
25
-
-
51
48
39
39
49
47
37
38
48
46
36
37
45
43
34
35
43
40
32
33
3.7
3.6
3.5
3.5
3.6
3.5
3.5
3.5
3.6
3.5
3.5
3.4
3.6
3.5
3.4
3.4
3.5
3.5
3.4
3.4
35
45
39
39
32
42
37
38
29
39
36
37
26
35
34
35
23
30
32
33
30
41
39
39
28
38
37
38
25
36
36
37
23
32
33
34
20
28
30
32
26
36
39
39
24
34
37
38
22
32
35
37
20
28
31
33
17
25
28
29
21
32
34
35
20
30
33
34
18
38
31
33
16
25
28
30
15
22
25
26
17
28
30
30
16
26
29
30
15
25
28
30
13
22
25
27
12
19
22
24
-
-
24
28
29
-
22
25
26
-
19
22
24
-
18
21
23
-
20
24
24
-
18
21
22
-
16
19
20
-
15
18
20
-
23
25
26
-
22
25
26
-
21
24
26
-
19
22
23
-
19
21
21
-
18
21
22
-
18
21
22
-
16
19
20
-
1500
1350
1200
62
57
72
67
62
57
72
67
62
57
1050
17
20
22
15
18
19
16
19
21
14
17
18
900
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
115°F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
TOTAL
CAP
MBH
POWER
INPUT2
kW.
TOTAL
POWER
INPUT2
kW.
.1
.1
CAP
WB
MBH
CFM
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
47
44
36
36
44
42
34
34
42
40
32
32
40
38
30
31
38
36
29
30
3.9
3.8
3.7
3.7
3.9
3.8
3.7
3.7
3.8
3.8
3.7
3.7
3.8
3.7
3.7
3.6
3.8
3.7
3.6
3.6
33
43
36
36
30
39
34
34
27
36
32
32
24
32
30
31
22
29
29
30
29
39
36
36
26
36
34
34
23
32
32
32
21
29
30
31
19
26
28
29
25
35
36
36
22
32
33
34
20
29
31
33
18
26
28
30
16
23
26
27
20
30
31
31
18
28
29
30
16
25
28
29
15
23
25
27
13
20
23
24
16
26
27
27
14
24
25
26
12
22
24
26
12
19
22
24
11
17
20
21
-
-
43
40
33
33
39
37
30
30
36
34
27
28
35
33
27
27
34
32
26
26
4.1
4.1
4.0
3.9
4.1
4.0
4.0
3.9
4.1
4.0
3.9
3.9
4.1
4.0
3.9
3.9
4.0
4.0
3.9
3.9
32
40
33
33
28
36
30
30
24
33
27
28
22
30
27
27
20
27
26
26
28
38
33
33
24
33
30
30
21
29
27
28
19
26
27
27
18
24
26
26
23
33
33
33
20
29
30
31
17
25
28
29
16
23
26
27
15
21
24
25
19
29
28
28
16
25
26
27
14
22
24
26
13
20
22
24
12
18
21
22
14
24
24
24
12
21
22
23
10
18
20
22
10
17
19
21
9
-
-
22
22
23
-
20
21
22
-
18
20
22
-
16
19
20
-
17
18
18
-
16
17
18
-
14
17
19
-
13
16
17
-
20
19
20
-
17
18
19
-
15
17
18
-
14
16
17
-
16
15
15
-
13
14
15
-
11
13
15
-
11
13
14
-
1500
1350
1200
62
57
72
67
62
57
72
67
62
57
1050
15
17
19
12
15
16
16
18
19
13
15
17
10
13
14
900
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 8 or 11, multiply
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
ALL SENSIBLE CAPACITY
NOMINAL RATING
8
Unitary Products Group
036-21411-002-A-0204
TABLE 6: COOLING CAPACITIES - 4 TON (DEE / DEG048)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
95°F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
TOTAL
CAP.1
MBH
POWER
INPUT2
kW
TOTAL
POWER
INPUT2
kW.
.1
CAP
WB
MBH
CFM
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
64
57
54
54
62
55
52
52
59
54
50
50
58
52
49
49
57
50
48
48
3.9
3.8
3.8
3.8
3.9
3.8
3.8
3.8
3.9
3.8
3.7
3.7
3.8
3.8
3.7
3.7
3.8
3.8
3.7
3.7
45
55
54
54
42
51
52
52
38
48
50
50
35
44
48
49
32
40
47
48
39
49
54
54
36
46
52
52
33
43
50
50
31
39
47
48
29
36
44
45
33
43
53
54
31
40
49
51
29
38
46
47
27
35
43
44
25
32
40
41
27
37
47
48
25
35
44
45
24
33
41
42
23
31
39
40
21
29
36
37
21
31
41
42
20
30
39
40
19
29
36
38
18
27
34
36
17
25
33
34
-
-
60
53
50
50
58
52
49
49
57
52
47
47
55
49
46
46
53
47
45
45
4.2
4.1
4.0
4.0
4.2
4.1
4.1
4.1
4.2
4.2
4.1
4.1
4.2
4.2
4.1
4.1
4.2
4.2
4.1
4.1
44
53
50
50
41
50
49
49
38
47
47
47
34
42
46
46
31
38
45
45
38
47
50
50
35
44
49
49
33
42
47
47
30
38
45
46
28
35
42
43
32
41
50
50
30
39
47
49
28
37
45
46
26
34
42
43
24
31
38
39
26
35
44
46
24
34
42
44
23
32
40
41
22
30
37
38
20
27
34
35
20
29
38
40
19
28
37
38
18
28
35
37
17
26
33
34
16
23
31
32
-
-
25
35
36
-
24
33
35
-
24
32
33
-
22
30
31
-
19
29
30
-
19
28
29
-
19
27
28
-
18
26
27
-
23
32
34
-
23
31
33
-
23
31
32
-
21
29
30
-
17
26
28
-
18
26
27
-
18
26
27
-
17
25
26
-
2000
1800
1600
62
57
72
67
62
57
72
67
62
57
1400
21
29
30
17
25
26
20
27
28
16
23
24
1200
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
115°F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
TOTAL
CAP
MBH
POWER
INPUT2
kW.
TOTAL
POWER
INPUT2
kW.
.1
.1
CAP
WB
MBH
CFM
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
56
50
47
47
54
49
46
46
53
48
44
44
51
46
43
43
50
44
42
42
4.7
4.6
4.5
4.5
4.7
4.6
4.5
4.5
4.7
4.6
4.6
4.5
4.7
4.6
4.5
4.5
4.7
4.6
4.5
4.5
42
50
47
47
39
47
46
46
36
45
44
44
33
41
43
43
30
37
42
42
36
45
47
47
34
43
46
46
31
40
44
44
29
37
42
43
27
33
41
41
30
39
47
47
29
37
45
46
27
35
43
44
25
33
40
41
23
30
37
38
25
33
41
44
23
32
40
42
22
31
38
39
21
28
36
37
19
26
33
34
19
28
35
38
17
27
34
36
17
26
33
34
16
24
31
32
16
22
29
30
-
-
53
47
44
44
51
46
43
43
49
44
41
41
48
43
40
40
47
42
39
39
5.2
5.1
5.0
5.0
5.1
5.1
5.0
5.0
5.1
5.1
5.0
5.0
5.1
5.0
5.0
5.0
5.1
5.0
5.0
5.0
41
47
44
44
38
45
43
43
35
43
41
41
32
40
40
40
30
36
39
39
35
44
44
44
33
41
43
43
30
39
41
41
28
35
40
40
26
32
39
39
29
38
44
44
27
36
43
43
25
34
41
41
24
31
38
39
22
29
35
36
23
32
38
42
22
31
37
40
21
29
36
37
20
27
34
35
18
25
32
33
17
26
32
36
17
25
32
34
16
24
31
32
15
23
30
31
15
21
28
29
-
-
22
29
32
-
21
29
31
-
21
29
30
-
20
27
28
-
16
23
26
-
16
23
26
-
16
24
25
-
16
23
24
-
20
26
30
-
20
26
29
-
19
26
28
-
19
25
26
-
14
20
24
-
14
21
24
-
15
22
23
-
14
21
22
-
2000
1800
1600
62
57
72
67
62
57
72
67
62
57
1400
19
26
27
15
22
23
18
24
25
14
21
22
1200
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 9 or 11, multiply
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
NOMINAL RATING
ALL SENSIBLE CAPACITY
Unitary Products Group
9
036-21411-002-A-0204
TABLE 7: COOLING CAPACITIES - 5 TON (DEE / DEG060)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
95°F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
TOTAL
CAP.1
MBH
POWER
INPUT2
kW
TOTAL
POWER
INPUT2
kW.
.1
CAP
WB
MBH
CFM
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
75
67
62
56
74
67
61
55
73
66
60
55
72
65
60
54
71
63
59
53
4.6
4.5
4.5
4.4
4.6
4.5
4.5
4.4
4.5
4.5
4.4
4.4
4.5
4.5
4.4
4.4
4.5
4.5
4.4
4.4
53
64
62
56
51
62
61
55
49
60
60
55
45
55
60
54
41
50
59
53
46
56
62
56
44
55
61
55
43
54
60
55
40
50
59
53
37
46
57
52
38
49
62
56
37
48
61
55
37
48
60
54
34
44
56
50
32
41
52
47
31
41
54
48
31
42
54
48
31
42
54
48
29
39
50
45
27
36
47
42
23
34
47
41
24
35
47
41
25
36
48
42
24
34
45
40
23
32
43
38
-
-
73
65
60
55
72
64
59
53
70
63
58
52
68
61
56
50
66
58
54
49
5.0
4.9
4.9
4.8
5.0
5.0
4.9
4.8
5.0
5.0
4.9
4.8
5.0
4.9
4.9
4.8
5.0
4.9
4.9
4.8
53
64
60
55
50
61
59
53
47
58
58
52
43
53
56
50
40
48
54
49
46
56
60
55
43
54
59
53
41
52
58
52
38
47
56
50
35
43
54
49
38
49
60
55
37
47
59
53
35
46
57
61
33
42
53
48
30
39
49
44
31
41
53
47
30
41
52
46
29
40
51
45
27
37
48
42
26
34
44
40
23
34
46
40
23
34
45
39
23
34
45
39
22
32
42
37
21
29
40
35
-
-
26
39
33
-
28
40
35
-
30
42
36
-
29
40
34
-
19
32
26
-
21
34
28
-
24
36
30
-
23
35
29
-
26
38
32
-
27
38
33
-
28
39
33
-
26
27
32
-
19
31
25
-
20
32
26
-
22
33
27
-
21
32
27
-
2500
2250
2000
62
57
72
67
62
57
72
67
62
57
1750
27
38
33
22
34
28
25
35
30
20
31
26
1500
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
115°F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB, °F
TOTAL
CAP
MBH
POWER
INPUT2
kW.
TOTAL
POWER
INPUT2
kW.
.1
.1
CAP
WB
MBH
CFM
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
66
59
55
49
65
58
54
48
63
58
52
47
62
55
51
46
60
53
49
44
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
51
58
55
49
48
57
54
48
45
55
52
47
42
50
51
46
38
46
49
44
44
54
55
49
42
52
54
48
39
50
52
47
36
45
51
46
33
41
49
44
36
46
55
49
35
45
54
48
33
44
52
47
31
40
50
45
29
37
47
42
29
39
47
42
28
38
48
42
28
38
48
43
26
35
45
40
24
32
42
37
21
31
40
35
21
31
41
36
22
32
42
37
21
30
40
35
19
27
37
33
-
-
60
53
49
44
58
52
48
44
57
52
47
43
55
50
46
41
53
47
44
40
6.0
6.0
5.9
5.9
6.0
6.0
5.9
5.9
6.0
6.0
5.9
5.9
6.1
6.0
6.0
5.9
6.1
6.1
6.0
6.0
49
53
49
44
46
52
48
44
44
52
47
43
40
48
46
41
36
44
44
40
41
51
49
44
40
49
48
44
38
48
47
43
35
43
46
41
32
39
44
40
34
43
49
44
33
43
48
44
32
42
47
43
30
38
46
41
27
35
44
40
26
36
42
37
26
36
44
39
26
36
46
41
24
33
43
38
23
30
39
35
19
28
34
29
20
29
37
32
20
30
40
35
19
28
37
33
18
25
35
30
-
-
24
32
27
-
25
34
29
-
26
36
31
-
24
35
30
-
16
25
20
-
18
28
22
-
20
30
25
-
19
29
24
-
21
27
22
-
22
30
25
-
24
34
29
-
22
32
27
-
13
19
15
-
16
24
19
-
18
28
23
-
17
27
22
-
2500
2250
2000
62
57
72
67
62
57
72
67
62
57
1750
23
33
28
18
28
23
21
30
26
16
25
21
1500
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 10 or 11, multiply
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
NOMINAL RATING
ALL SENSIBLE CAPACITY
10
Unitary Products Group
036-21411-002-A-0204
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE -DEE/DEG036 W/ BELT DRIVE & SIDE DUCT1 2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG3
AIR
FLOW
CFM
MODEL
0.20
WATTS
0.30
WATTS
0.40
WATTS
0.50
WATTS
0.60
WATTS
0.70
WATTS
0.80
WATTS
DEE/DEG
RPM
843
817
790
-
-
-
-
-
-
RPM
880
854
828
RPM
919
893
867
840
818
-
RPM
956
930
906
881
858
842
833
-
RPM
993
970
944
920
898
882
867
858
847
RPM
1030
1008
985
961
940
922
904
893
880
RPM
1067
1046
1025
1001
980
962
942
932
916
2000
1900
1800
1700
1600
1500
1400
1300
1200
860
775
700
-
-
-
-
-
-
925
850
760
670
-
-
-
-
-
1005
920
840
745
665
-
-
-
-
1065
995
905
815
740
695
650
-
1145
1065
980
900
820
755
705
665
640
1195
1125
1040
970
890
835
765
725
680
1235
1170
1100
1030
950
895
820
785
730
802
036
-
-
-
-
-
-
-
-
-
-
AVAILABLE EXTERNAL STATIC PRESSURE - IWG3
1.10 1.20 1.30
WATTS WATTS WATTS
AIR
FLOW
CFM
MODEL
0.90
1.00
WATTS
-
1.40
WATTS
1.50
WATTS
DEE/DEG
RPM
1103
1085
1064
1040
1020
1003
982
WATTS
1270
1210
1145
1075
1005
945
RPM
-
-
1102
1081
1060
1044
1024
1010
992
RPM
-
RPM
RPM
RPM
RPM
2000
1900
1800
1700
1600
1500
1400
1300
1200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1180
1115
1050
995
920
870
815
1121
1100
1086
1067
1053
1034
1140
1085
1035
965
920
855
036
-
880
835
780
1107
1099
1080
1000
960
905
970
953
1.
230/460/575 Volts
2.
3.
For 208 Volts multiply values by 0.95.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance values on applications
other than gas / electric units with side duct airflows.
Unitary Products Group
11
036-21411-002-A-0204
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE -DEE/DEG048 W/ BELT DRIVE & SIDE DUCT1 2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG3
0.40 0.50 0.60
WATTS WATTS WATTS
AIR
FLOW
CFM
MODEL
0.20
WATTS
0.30
WATTS
0.70
WATTS
0.80
WATTS
DEE/DEG
RPM
843
817
790
-
-
-
-
-
-
RPM
880
854
828
RPM
919
893
867
840
818
-
RPM
956
930
906
881
858
842
833
-
RPM
993
970
944
920
898
882
867
858
847
RPM
1030
1008
985
961
940
922
904
893
880
RPM
1067
1046
1025
1001
980
962
942
932
916
2000
1900
1800
1700
1600
1500
1400
1300
1200
860
775
700
-
-
-
-
-
-
925
850
760
670
-
-
-
-
-
1005
920
840
745
665
-
-
-
-
1065
995
905
815
740
695
650
-
1145
1065
980
900
820
755
705
665
640
1195
1125
1040
970
890
835
765
725
680
1235
1170
1100
1030
950
895
820
785
730
802
048
-
-
-
-
-
-
-
-
-
-
AVAILABLE EXTERNAL STATIC PRESSURE - IWG3
1.10 1.20 1.30
WATTS WATTS WATTS
AIR
FLOW
CFM
MODEL
0.90
1.00
WATTS
-
1.40
WATTS
1.50
WATTS
DEE/DEG
RPM
1103
1085
1064
1040
1020
1003
982
WATTS
1270
1210
1145
1075
1005
945
RPM
-
-
1102
1081
1060
1044
1024
1010
992
RPM
-
RPM
RPM
RPM
RPM
2000
1900
1800
1700
1600
1500
1400
1300
1200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1180
1115
1050
995
920
870
815
1121
1100
1086
1067
1053
1034
1140
1085
1035
965
920
855
048
-
880
835
780
1107
1099
1080
1000
960
905
970
953
1.
230/460/575 Volts
2.
3.
For 208 Volts multiply values by 0.95.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance values on applications
other than gas / electric units with side duct airflows.
12
Unitary Products Group
036-21411-002-A-0204
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE -DEE/DEG060 W/ BELT DRIVE & SIDE DUCT1 2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG3
AIR
FLOW
CFM
MODEL
0.20
WATTS
0.30
WATTS
0.40
WATTS
0.50
WATTS
0.60
WATTS
0.70
WATTS
0.80
WATTS
DEE/DEG
RPM
1059
1032
1005
980
930
877
-
-
-
-
-
RPM
1077
1054
1024
1002
957
908
-
-
-
-
-
RPM
1095
1074
1049
1022
983
941
894
855
-
RPM
1114
1094
1069
1044
1010
976
940
903
884
864
-
RPM
1134
1116
1090
1066
1039
1009
980
RPM
1158
1140
1116
1090
1064
1040
1014
988
RPM
1181
1167
1142
1117
1092
1070
1047
1022
1001
987
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1560
1405
1260
1160
1060
950
-
-
-
-
-
1590
1470
1275
1170
1070
975
-
-
-
-
-
1630
1525
1370
1190
1080
1000
885
815
-
1650
1560
1440
1250
1100
1020
940
1660
1595
1475
1350
1160
1050
980
1685
1620
1505
1410
1260
1100
1020
940
1720
1640
1535
1440
1340
1225
1095
970
060
860
815
950
925
905
850
964
948
880
835
910
870
-
-
770
908
805
-
-
-
882
740
926
780
965
830
AVAILABLE EXTERNAL STATIC PRESSURE - IWG3
0.40 0.50 0.60
WATTS WATTS WATTS
AIR
FLOW
CFM
MODEL
DEE/DEG
0.20
WATTS
-
0.30
WATTS
-
0.70
WATTS
0.80
WATTS
RPM
-
RPM
-
-
RPM
-
RPM
-
RPM
RPM
-
-
-
-
-
-
-
RPM
-
-
-
-
-
-
-
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1193
1170
1148
1121
1100
1079
1058
1035
1020
1004
1665
1580
1480
1385
1285
1180
1060
960
-
-
-
-
-
1202
1180
1155
1133
1110
1090
1071
1056
1038
1620
1530
1425
1340
1240
1135
1030
965
-
-
-
-
-
-
1190
1169
1143
1122
1103
1088
1070
1475
1385
1280
1190
1100
1035
925
-
-
-
-
-
-
060
1205
1178
1158
1134
1118
1101
1445
1330
1240
1140
1065
980
1222
1196
1164
1145
1130
1375
1295
1175
1105
1045
-
-
-
1197
1170
1158
1205
1130
1075
-
900
860
1198
1184
1150
1110
880
1.
230/460/575 Volts
2.
3.
For 208 Volts multiply values by 0.95.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance values on applications
other than gas / electric units with side duct airflows.
Unitary Products Group
13
036-21411-002-A-0204
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - DEE/DEG036-060 W/ DIRECT DRIVE1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG2
0.30 0.40
MODEL
MOTOR
SPEED
0.20
0.50
DEE/DEG
CFM
-
WATTS
-
CFM
-
WATTS
-
CFM
1699
1582
1421
1868
1714
1604
2274
2145
2029
WATTS
825
CFM
1650
1524
1367
1795
1650
1541
2167
2071
1965
WATTS
785
720
650
880
765
695
1045
990
910
HI
036
048
060
MED
LOW
HI
MED
LOW
HI
1684
1487
1996
1804
1681
2400
2290
2150
800
710
960
838
1631
1464
1933
1765
1640
2338
2214
2100
780
690
936
810
738
1125
1065
990
750
670
910
785
760
715
1155
1105
1020
1095
1030
950
MED
LOW
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
0.70 0.80 0.90
MODEL
MOTOR
SPEED
0.6
1.00
DEE/DEG
CFM
1570
1410
1315
1722
1589
1490
2096
1990
1905
WATTS
755
690
620
845
735
670
1010
950
880
CFM
1430
1324
1246
1635
1508
1416
1990
1911
1816
WATTS
725
650
605
820
705
645
980
920
CFM
1360
1260
1185
1544
1407
1337
1887
1828
1724
WATTS
700
630
590
790
675
620
945
885
CFM
1280
1185
1110
1419
1306
1230
1771
1724
1644
WATTS
680
CFM
1180
1100
1020
1300
1195
1120
1629
1604
1531
WATTS
655
590
545
740
625
575
855
798
HI
036
048
MED
LOW
HI
MED
LOW
HI
610
570
765
645
595
905
835
770
060
MED
LOW
838
800
710
1.
Side Duct application (230/460/575 Volts)
2.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance val-
ues on applications other than gas / electric units with side duct airflows.
TABLE 12: STATIC RESISTANCES
RESISTANCE, IWG
CFM
DESCRIPTION
1000
0.07
0.04
0.06
0.06
1200
0.08
0.05
0.07
0.07
1400
0.09
0.06
0.08
0.08
1600
0.11
0.07
0.09
0.09
1800
2000
0.15
0.10
0.13
0.11
2200
2400
0.20
0.14
0.17
0.14
2600
0.23
0.16
0.20
0.16
2800
0.26
0.19
0.23
0.19
3000
0.30
0.22
0.26
0.22
ECONOMIZER1 2
0.13
0.08
0.11
0.10
0.17
0.12
0.15
0.12
5 - 15 kW
20 - 30 kW
ELECTRIC HEATERS1
BOTTOM DUCT CONNECTIONS1
COOLING ONLY3
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
1.
Deduct these resistance values from the available external static pressure shown on Tables 8, 9, 10, and 11.
2.
The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
3.
Add these resistance values to the available static resistance in the respective Blower Performance Table (see Tables 8, 9, 10,
and 11).
14
Unitary Products Group
036-21411-002-A-0204
TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER
ADJUSTABLE
MOTOR PULLEY
FIXED
BLOWER PULLEY
MOTOR1
BELT
BLOWER
RANGE
RPM
MODEL
PITCH
DIA.
(in.)
PITCH
BORE
DIA.
(in.)
PITCH
LENGTH
(in.)
FRAME
SIZE
SERVICE
FACTOR
BORE
(in.)
DESIG-
NATION
HP
RPM
(in.)
DEE / DEG 036
DEE / DEG 048
DEE / DEG 060
780 - 1120
790 - 1120
850 - 1220
1-1/2
1-1/2
1-1/2
1725
1725
1725
56
56
56
1.15
1.15
1.15
2.4-3.4
2.4-3.4
2.4-3.4
7/8
7/8
7/8
5.7
5.7
5.2
1
1
1
37.3
37.3
37.3
A36
A36
A36
1.
All motors have a solid base and are inherently protected. These motors can be selected to operate into their service fac-
tor because they are located in the moving air, upstream of any heating device.
TABLE 14: BASIC UNIT W/ DIRECT-DRIVE ELECTRICAL DATA
VOLTAGE
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MAX.
HACR
BREAKER
SIZE,
AMPS
MAX.
FUSE
SIZE2
AMPS
CON.
FAN
MOTOR,
FLA
COMPRESSOR
LIMITATIONS1
MODEL
DEE/
DEG
MINIMUM
CIRCUIT
AMPACITY
POWER
SUPPLY
MIN
MAX
RLA
LRA
208/230-1-60
208/230-3-60
460-3-60
575-3-603
208/230-1-60
208/230-3-60
460-3-60
575-3-603
208/230-1-60
208/230-3-60
460-3-60
187
187
414
518
253
253
504
630
16.7
13.1
6.7
87
110
54
2.3
2.3
1.4
1.4
4.4
4.4
2.2
2.2
27.5
23.1
12.0
10.7
40
35
15
15
40
35
15
-
036
048
5.1
44
187
187
414
518
187
187
414
518
253
253
504
630
253
253
504
630
18.7
11.9
6.3
135
130
64
2.3
2.3
1.4
1.4
2.3
2.3
1.4
1.4
5.0
5.0
2.2
2.2
6.6
6.6
3.3
3.3
38.6
25.7
13.2
11.4
49.0
33.0
17.2
14.6
60
40
20
15
80
50
25
20
60
40
20
-
4.9
52
32.1
19.3
10.0
7.9
169
123
62
80
50
25
-
060
1.
575-3-603
50
Rated in accordance with ARI Standard 110, utilization range “A”.
Dual element, time delay type.
2.
3.
DEE models only.
Unitary Products Group
15
036-21411-002-A-0204
TABLE 15: BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA
VOLTAGE
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MAX.
MAX.
CON.
COMPRESSOR
LIMITATIONS1
MODEL
DEE/
DEG
MINIMUM
CIRCUIT
AMPACITY
HACR
FUSE
POWER
SUPPLY
FAN
MOTOR,
FLA
BREAKER
SIZE,
SIZE2
MIN
MAX
RLA
LRA
AMPS
AMPS
208/230-1-60
208/230-3-60
460-3-60
575-3-603
208/230-1-60
208/230-3-60
460-3-60
575-3-603
208/230-1-60
208/230-3-60
460-3-60
187
187
414
253
253
504
16.7
13.1
6.7
87
110
54
2.3
2.3
1.4
7.6
5.3
2.6
30.1
23.9
12.4
45
35
20
45
35
20
036
048
518
187
187
414
518
630
253
253
504
630
5.1
18.7
11.9
6.3
44
135
130
64
1.4
2.3
2.3
1.4
1.4
2.0
8.6
5.2
2.6
2.0
9.8
15
60
40
20
15
15
60
40
20
15
42.6
26.3
14.3
11.4
4.9
52
187
187
414
518
253
253
504
630
32.1
19.3
10.0
7.9
169
123
62
2.3
2.3
1.4
1.4
8.6
6.0
3.0
2.4
51.0
32.4
16.9
13.7
80
50
25
20
80
50
25
20
060
1.
575-3-603
50
Rated in accordance with ARI Standard 110, utilization range “A”.
Dual element, time delay type.
2.
3.
= DEE models only.
16
Unitary Products Group
036-21411-002-A-0204
TABLE 16: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE036
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MAX
HEATER
ACCESSORY
MODEL
MAX.
SIZE
HACR2
MINIMUM
CIRCUIT
AMPACITY
FUSE
MODEL
DEE
POWER
SUPPLY
TOTAL
AMPS
kW
STAGES
SIZE1
AMPS
NUMBER
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
4.0
5.6
8.0
11.9
15.9
5.3
1
1
1
2
2
1
1
1
2
2
1
19.1
27.1
38.3
57.4
76.6
22.1
31.3
44.2
66.0
88.3
11.0
30.7
39.4
53.4
77.3
101.2
33.1
44.6
60.7
88.3
115.9
24.3
45
45
60
80
110
45
45
70
90
125
35
45
45
60
80
110
45
45
70
90
125
35
208-1-60
230-1-60
4.4
4.4
7.5
10.6
15.9
21.2
4.0
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
5.6
8.0
11.9
15.9
5.3
1
1
2
2
1
15.6
22.1
33.1
44.2
12.7
25.0
33.1
46.9
60.7
24.3
35
35
50
70
35
35
35
50
70
35
208-3-60
230-3-60
4.4
4.4
036
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE045007463
2CE045010463
2CE045015463
2CE045020463
2CE04501058
2CE04501558
2CE04502058
7.5
10.6
15.9
21.2
6.8
1
1
2
2
1
18.0
25.5
38.2
51.0
8.2
28.1
37.4
53.3
69.2
13.0
35
40
60
70
15
35
40
60
70
15
10.1
13.6
1
1
12.1
16.4
17.9
23.2
20
25
20
25
460-3-60
575-3-60
2.2
2.2
19.5
10.6
15.9
21.2
2
1
1
2
23.5
10.2
15.3
20.4
32.1
15.5
21.9
28.2
35
20
25
30
35
20
25
30
1.
Dual element, time delay type.
2.
3.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse
Unitary Products Group
17
036-21411-002-A-0204
TABLE 17: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE048
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MAX
MAX.
FUSE
SIZE
HEATER
ACCESSORY
MODEL
MINIMUM
CIRCUIT
AMPACITY
MODEL
DEE
POWER
SUPPLY
TOTAL
AMPS
kW
STAGES
SIZE1
HACR2
AMPS
NUMBER
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
4.0
5.6
8.0
11.9
15.9
5.3
1
1
1
2
2
1
1
1
2
2
1
19.1
27.1
38.3
57.4
76.6
22.1
31.3
44.2
66.3
88.3
11.0
38.6
39.9
54.3
77.8
101.8
38.6
45.3
61.5
89.1
116.7
25.7
60
60
60
80
110
60
60
70
90
125
40
60
60
60
80
110
60
60
70
90
125
40
208-1-60
230-1-60
5.0
5.0
7.5
10.6
15.9
21.2
4.0
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
5.6
8.0
11.9
15.9
5.3
1
1
2
2
1
15.6
22.1
33.1
44.2
12.7
25.7
34.0
47.5
61.4
25.7
40
40
50
70
40
40
40
50
70
40
208-3-60
230-3-60
5.0
5.0
048
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE045007463
2CE045010463
2CE045015463
2CE045020463
2CE04501058
2CE04501558
2CE04502058
7.5
10.6
15.9
21.2
6.8
1
1
2
2
1
18.0
25.5
38.2
51.0
8.2
28.8
38.0
54.0
70.0
13.2
40
40
60
70
20
40
40
60
70
20
10.1
13.6
1
1
12.1
16.4
17.9
23.2
20
25
20
25
460-3-60
575-3-60
2.2
2.2
19.5
10.6
15.9
21.2
2
1
1
2
23.5
10.2
15.3
20.4
32.1
15.5
21.9
28.2
35
20
25
30
35
20
25
30
1.
Dual element, time delay type.
2.
3.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse
TABLE 18: ELECTRIC HEAT CORRECTION
FACTORS
TABLE 19: FUSE BLOCK ACCESSORY
PART NUMBER
2FB04700425
2FB04700546
VOLTS
208/240 Volts
460 Volts
NOMINAL VOLTAGE
VOLTAGE
208
kW CAP. MULTIPLIER
208
240
480
600
1.00
0.92
0.92
0.92
230
460
575
18
Unitary Products Group
036-21411-002-A-0204
TABLE 20: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE060
ELECTRIC HEATERS
MAX.
SIZE
HACR2
BREAKER
AMPS
SUPPLY
AIR
BLOWER
MOTOR
FLA
MAX.
FUSE
SIZE1
AMPS
HEATER
ACCESSORY
MODEL
MINIMUM
CIRCUIT
AMPACITY
MODEL
DEE
POWER
SUPPLY
TOTAL
AMPS
kW
STAGES
NUMBER
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04503006
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04503006
4.0
5.6
8.0
11.9
15.9
22.2
5.3
1
1
1
2
2
2
1
1
1
2
2
2
1
19.1
27.1
38.3
57.4
76.6
106.9
22.1
31.3
44.2
66.3
88.3
123.3
11.0
49.0
49.0
56.1
80
80
80
80
80
80
208-1-60
230-1-60
8.6
8.6
80.0
90
90
103.9
141.9
49.0
49.0
63.5
110
150
80
80
80
100
125
175
50
110
150
80
80
80
100
125
175
50
7.5
10.6
15.9
21.2
29.6
4.0
91.1
118.7
162.4
33.0
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE04503025
5.6
8.0
11.9
15.9
22.2
5.3
1
1
2
2
2
1
15.6
22.1
33.1
44.2
61.7
12.7
33.0
35.9
49.7
63.5
85.4
33.0
50
50
50
70
90
50
50
50
50
70
90
50
208-3-60
230-3-60
6.0
6.0
060
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE04503025
2CE045007463
2CE045010463
2CE045015463
2CE045020463
2CE045030463
2CE04501058
2CE04501558
2CE04502058
2CE04503058
7.5
10.6
15.9
21.2
29.6
6.8
1
1
2
2
2
1
18.0
25.5
38.2
51.0
71.2
8.2
33.0
40.1
56.1
72.0
97.3
17.2
50
50
60
80
100
25
50
50
60
80
100
25
10.1
13.6
19.5
1
1
2
12.1
16.4
23.5
19.3
24.6
33.4
25
25
35
25
25
35
460-3-60
575-3-60
3.0
2.4
28.8
10.6
15.9
21.2
30.4
2
1
1
2
2
34.6
10.2
15.3
20.4
29.3
47.4
16.9
23.2
29.6
40.7
50
20
25
30
45
50
20
25
30
45
1.
Dual element, time delay type.
2.
3.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse
Unitary Products Group
19
036-21411-002-A-0204
TABLE 21: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ BELT DRIVE DEE036 & 048
ELECTRIC HEATERS
MAX.
SIZE
HACR2
BREAKER
AMPS
SUPPLY
AIR
BLOWER
MOTOR
FLA
MAX.
FUSE
SIZE1
AMPS
HEATER
ACCESSORY
MODEL
MINIMUM
CIRCUIT
AMPACITY
MODEL
DEE
POWER
SUPPLY
TOTAL
AMPS
kW
STAGES
NUMBER
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
4.0
5.6
8.0
11.9
15.9
5.3
1
1
1
2
2
1
1
1
2
2
1
19.1
27.1
38.3
57.4
76.6
22.1
31.2
44.2
66.3
88.3
11.0
34.9
44.6
58.6
82.5
106.4
38.4
49.8
66.0
93.6
121.2
25.2
50
50
60
90
110
50
50
70
100
125
35
50
50
60
90
110
50
50
70
100
125
35
208-1-60
230-1-60
5.3
5.3
7.5
10.6
15.9
21.2
4.0
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
5.6
8.0
11.9
15.9
5.3
1
1
2
2
1
15.6
22.1
33.1
44.2
12.7
26.2
34.2
48.1
61.9
25.2
35
35
50
70
35
35
35
50
70
35
208-3-60
230-3-60
5.3
5.3
036
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE045007463
2CE045010463
2CE045015463
2CE045020463
2CE04501058
2CE04501558
2CE04502058
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
7.5
10.6
15.9
21.2
6.8
1
1
2
2
1
18.0
25.5
38.2
51.0
8.2
29.2
38.5
54.4
70.4
14.1
35
40
60
80
20
35
40
60
80
20
10.1
13.6
1
1
12.1
16.4
19.1
24.3
20
25
20
25
460-3-60
575-3-60
208-1-60
3.1
3.1
8.6
19.5
10.6
15.9
21.2
4.0
5.6
8.0
11.9
15.9
5.3
2
1
1
2
1
1
1
2
2
1
1
1
2
2
1
23.5
10.2
15.3
20.4
19.1
27.1
38.3
57.4
76.6
22.1
31.2
44.2
66.3
88.3
11.0
33.2
16.6
23.0
29.4
42.2
44.4
58.8
82.3
106.3
42.2
49.8
66.0
93.6
121.2
25.9
35
20
25
30
60
60
60
90
110
60
60
70
100
125
40
35
20
25
30
60
60
60
90
110
60
60
70
100
125
40
7.5
230-1-60
208-3-60
8.6
5.2
10.6
15.9
21.2
4.0
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
5.6
8.0
11.9
15.9
5.3
1
1
2
2
1
15.6
22.1
33.1
44.2
12.7
25.9
34.3
47.8
61.7
25.9
40
40
50
70
40
40
40
50
70
40
048
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE045007463
2CE045010463
2CE045015463
2CE045020463
2CE04501058
2CE04501558
2CE04502058
7.5
10.6
15.9
21.2
6.8
1
1
2
2
1
18.0
25.5
38.2
51.0
8.2
29.1
38.4
54.3
70.2
13.6
40
40
60
80
20
40
40
60
80
20
230-3-60
5.2
10.1
13.6
1
1
12.1
16.4
18.4
23.7
20
25
20
25
460-3-60
575-3-60
2.6
2.0
19.5
10.6
15.9
21.2
2
1
1
2
23.5
10.2
15.3
20.4
32.6
15.2
21.6
28.0
35
20
25
30
35
20
25
30
1.
Dual element, time delay type.
2.
3.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago) see Table 19 for
fuse block accessories available for field installation.
20
Unitary Products Group
036-21411-002-A-0204
TABLE 22: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ BELT DRIVE DEE060
ELECTRIC HEATERS
MAX.
SIZE
HACR2
BREAKER
AMPS
SUPPLY
AIR
BLOWER
MOTOR
FLA
MAX.
FUSE
SIZE1
AMPS
HEATER
ACCESSORY
MODEL
MINIMUM
CIRCUIT
AMPACITY
MODEL
DEE
POWER
SUPPLY
TOTAL
AMPS
kW
STAGES
NUMBER
2CE045005253
4.0
1
19.1
51.0
80
80
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE04503025
5.6
8.0
11.9
15.9
22.2
5.3
1
1
2
2
2
1
27.1
38.3
57.4
76.6
106.9
22.1
51.0
58.6
82.5
106.4
144.4
51.0
80
80
90
110
150
80
80
80
90
110
150
80
208-1-60
230-1-60
208-3-60
230-3-60
8.6
8.6
6.0
6.0
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE04503025
7.5
10.6
15.9
21.2
29.6
4.0
1
1
2
2
2
1
31.3
44.2
66.3
88.3
123.3
11.0
51.0
66.0
93.6
121.1
164.9
32.4
80
80
100
125
175
50
80
80
100
125
175
50
2CE045005253
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE04503025
5.6
8.0
11.9
15.9
22.2
1
1
2
2
2
15.6
22.1
33.1
44.2
61.7
32.4
35.1
48.9
62.7
84.6
50
50
50
70
90
50
50
50
70
90
060
2CE045005253
5.3
7.5
1
1
12.7
18.0
32.4
32.4
50
50
50
50
2CE045007253
2CE04501025
2CE04501525
2CE04502025
2CE04503025
2CE045007463
2CE045010463
2CE045015463
2CE045020463
2CE045030463
2CE04501058
2CE04501558
2CE04502058
2CE04503058
10.6
15.9
21.2
29.6
6.8
1
2
2
2
1
25.5
38.2
51.0
71.2
8.2
39.4
55.3
71.2
96.5
16.4
50
60
80
100
25
50
60
80
100
25
10.1
13.6
19.5
1
1
2
12.1
16.4
23.5
18.9
24.2
33.1
25
25
35
25
25
35
460-3-60
575-3-60
3.0
2.4
28.8
10.6
15.9
21.2
30.4
2
1
1
2
2
34.6
10.2
15.3
20.4
29.3
47.1
15.7
22.1
28.5
39.6
50
20
25
30
40
50
20
25
30
40
1.
Dual element, time delay type.
2.
3.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago) see Table 19 for
fuse block accessories available for field installation.
Unitary Products Group
21
036-21411-002-A-0204
1
T
H
E
R
M
O
S
T
A
T
T
E
R
M
I
N
A
L
S
U
N
I
T
T
E
R
M
I
N
A
L
S
T
R
I
P
T
B
1
R
R
C
H
2
4
V
O
L
T
A
D
D
T
R
A
N
S
F
O
R
M
E
R
R
J
U
M
P
E
R
Y
Y
1
2
Y
Y
1
2
2
3
W
W
1
2
W
W
1
2
4
G
G
REFER TO THE ELECTRI-
CAL DATA TABLES TO SIZE
THE DISCONNECT
SWITCH, OVERCURRENT
PROTECTION AND WIRING
B
B
X
L
L
E
E
D
D
1
2
N
U
O
S
T
N
E
D
C
O
M
4
A
A
1
2
A
D
D
J
U
M
P
E
R
FIGURE 2 - POWER SUPPLY, POWER WIRING
SINGLE PHASE
T
T
T
O
R
E
M
O
T
E
S
E
N
S
O
R
2
T
H
0
4
0
7
0
2
2
2
4
I
F
U
S
E
D
1
2
3
E
S
S
L
E
C
T
R
O
N
I
C
P
R
O
G
R
A
M
I
M
A
B
S
L
E
T
H
E
R
M
O
S
R
T
A
T
2
E
T
0
4
7
0
0
2
2
4
(
I
N
C
L
U
D
E
S
S
U
B
B
A
S
E
)
E
E
C
C
O
O
N
N
D
D
S
S
T
T
A
A
G
G
E
E
C
H
O
E
O
L
N
G
I
N
O
T
R
E
Q
U
I
E
D
O
N
U
N
I
T
S
L
E
S
S
E
C
O
T
N
O
M
I
Z
E
R
.
A
T
I
N
G
I
S
O
N
L
Y
R
E
Q
U
I
R
E
D
O
N
U
N
I
T
S
W
I
T
H
A
W
O
S
T
A
G
E
E
L
E
C
T
R
I
C
H
E
A
T
E
R
.
4
R
E
M
O
V
E
J
U
M
B
E
R
J
2
F
R
O
M
T
E
R
M
I
N
A
L
S
4
A
N
D
9
O
N
J
U
M
P
E
R
P
L
U
G
C
O
N
N
E
C
T
O
R
P
6
O
N
U
N
I
T
S
W
I
T
H
E
C
O
N
M
I
Z
E
R
.
T
E
R
M
I
N
A
L
S
A
Z
1
A
N
D
A
2
P
R
O
V
I
D
E
A
R
E
L
A
Y
O
T
U
T
-
P
U
T
T
O
C
L
O
S
E
T
H
E
O
U
T
D
O
O
R
E
C
O
N
O
M
I
E
R
D
A
M
P
E
R
S
W
H
E
N
T
H
E
H
E
R
M
O
S
T
A
T
S
W
I
T
C
H
E
S
T
O
T
H
E
S
E
T
-
B
A
C
K
P
O
S
I
T
I
O
N
.
FIGURE 5 - CONTROL WIRING- COOLING &
HEATING MULTI-STAGE
FIGURE 3 - POWER SUPPLY, POWER WIRING
THREE PHASE
C
O
O
L
I
N
G
/
H
E
A
T
I
N
G
(
2
4
V
O
L
T
T
H
E
R
M
O
S
T
A
T
)
1
T
H
E
R
M
O
S
T
A
T
T
E
R
M
I
N
A
L
S
U
N
I
T
T
E
R
M
I
N
A
L
R
R
H
C
S
T
R
I
P
T
B
1
A
D
D
J
U
M
P
E
R
R
Y
Y
1
2
4
V
O
L
T
T
R
A
N
S
F
O
R
M
E
R
Y
G
2
W
W
1
W
2
G
B
1
2
4
V
O
L
T
T
H
E
R
M
O
S
T
A
T
2
T
H
0
7
7
0
1
0
2
4
.
I
F
T
H
E
U
N
I
T
H
A
S
A
N
E
C
O
N
O
M
I
Z
E
R
,
R
E
M
O
V
E
O
J
U
M
P
E
I
R
J
1
F
A
R
O
M
T
E
R
O
M
I
N
A
L
S
8
A
N
D
F
1
0
O
N
C
T
H
E
P
R
E
L
A
Y
B
O
A
A
R
D
T
O
H
P
R
E
V
E
N
T
S
M
U
L
T
N
E
O
O
U
S
P
E
R
A
T
I
O
N
O
T
H
E
O
M
R
O
E
S
S
O
R
N
D
T
E
C
E
C
N
O
M
I
Z
E
R
.
I
C
F
Y
U
W
A
N
T
T
O
C
O
N
T
R
O
E
L
T
H
E
R
E
C
N
O
M
I
Z
E
R
O
N
A
S
W
E
O
N
T
D
S
T
A
G
E
O
F
O
O
L
E
I
N
G
O
R
H
A
V
E
A
N
D
L
A
E
C
T
R
I
C
H
7
E
A
T
A
C
C
E
S
S
O
R
Y
I
T
H
W
O
S
T
A
G
E
S
O
F
H
A
T
,
U
S
E
T
H
E
R
M
O
S
T
T
2
T
H
0
4
1
0
2
4
FIGURE 6 - CONTROL WIRING - COOLING/
HEATING (24 VOLT THERMOSTAT)
FIGURE 4 - CONTROL WIRING - COOLING ONLY
22
Unitary Products Group
036-21411-002-A-0204
C
O
O
T
L
I
N
G
/
H
E
A
T
I
N
G
(
E
L
E
C
T
R
O
G
N
E
I
C
T
H
E
R
M
O
S
T
A
T
)
S
I
N
G
L
E
S
T
A
1
H
E
R
M
O
S
T
A
T
U
N
I
T
T
E
R
M
I
N
A
L
T
E
R
M
I
N
A
L
S
S
T
R
I
P
T
B
1
R
R
H
C
R
A
D
D
Y
Y
1
J
U
M
P
E
R
W
W
1
G
G
B
2
4
V
O
L
T
T
R
A
N
S
F
O
R
M
E
R
1
E
L
E
C
T
R
O
N
I
C
P
R
O
G
R
A
M
M
A
B
L
E
T
H
E
R
M
O
S
T
A
T
2
E
T
0
7
7
E
0
1
0
J
2
4
(
I
N
C
L
U
T
D
E
S
S
U
B
B
A
S
E
)
.
I
F
T
H
I
S
U
N
I
T
H
A
S
A
N
D
E
C
O
N
O
M
I
Z
E
R
,
R
E
M
O
V
E
J
U
M
P
R
1
F
R
O
M
E
R
M
I
N
A
L
S
8
A
N
D
1
0
O
N
T
H
E
R
E
L
A
Y
B
O
A
R
D
T
O
P
R
E
V
E
N
T
S
I
M
U
L
T
A
N
E
O
U
S
O
P
E
R
A
T
I
O
N
O
F
T
H
E
C
E
O
M
P
R
E
S
S
O
R
A
N
D
T
H
E
E
C
O
N
O
M
I
Z
E
R
.
I
F
Y
O
U
W
A
N
T
T
O
C
O
N
T
R
O
L
T
T
H
E
C
O
N
O
M
I
Z
E
R
O
N
A
S
E
C
O
N
D
S
T
A
G
E
O
F
C
O
O
L
I
N
G
,
U
S
E
T
H
E
R
M
O
S
T
A
2
E
T
0
4
7
0
0
2
2
4
.
FIGURE 7 - CONTROL WIRING - COOLING/HEATING (ELECTRONIC THERMOSTAT)
2
7
-
1
/
2
1
-
5
/
8
2
7
-
1
/
2
1
9
-
3
/
4
4
4
-
7
/
8
1
9
-
1
/
2
FIGURE 8 - UNIT DIMENSIONS WITH ECONOMIZER RAINHOOD
Unitary Products Group
23
036-21411-002-A-0204
R
S
E
T
P
U
R
N
A
I
R
U
P
L
Y
A
I
R
O
U
T
D
O
O
R
A
I
R
O
U
T
D
O
O
R
A
I
R
E
c
o
n
o
m
i
z
e
r
DEE UNITS
3-5 TON
All dimensions are in inches. They are
subject to change without notice. Cer-
tified dimensions will be provided upon
request.
FIGURE 9 - UNIT DIMENSIONS DEE 3, 4, & 5 TON
TABLE 23: UTILITIES ENTRY DATA
KNOCKOUT
SIZE (DIA.)
HOLE
USED FOR
Control Wiring (Side or
Bottom)2
Power Wiring (Side or
Bottom)
7/8”1
A
B
2”
C
D
1-5/8”
1-1/2”
Gas Piping (Front)
Gas Piping (Bottom)
1.
2.
Knockouts in the bottom of the unit can be located by
the slice in the insulation.
DO NOT remove the 2” knockout ring.
FIGURE 10 -ACCESS PANELS AND DISCONNECT
24
Unitary Products Group
036-21411-002-A-0204
R
S
E
T
P
U
R
N
A
I
R
U
P
L
Y
A
i
I
R
O
U
T
D
O
O
R
A
I
R
O
U
T
D
O
O
R
A
I
R
E
c
o
n
o
m
z
e
r
DEG UNITS
3-5 TON
FIGURE 11 -UNIT DIMENSIONS DEG 3, 4, & 5 TON
TABLE 24: DEE/DEG UNIT CLEARANCES
Note: DEE Models and ductwork are approved for zero
clearance to combustible materials when equipped
with electric heaters.
DEE UNITS
DEG UNITS
24”
32”
FRONT
Note: EG Models must have a 1” clearance between any
combustible material and the supply air ductwork for
a distance of 3 feet from the unit.
12” (Less Economizer)
36” (With Economizer or
Fixed Air/Motorized
Damper)
BACK
24” (Less Economizer)
36” (With Economizer)
The products of combustion must not be allowed to accumu-
late within a confined space and recirculate. Locate unit so
that the vent air outlet hood is at least:
LEFT SIDE (Filter Access)
RIGHT SIDE (Cond. Coil)
BELOW UNIT1
24”
0”
72” (For Condenser Air
Discharge)
ABOVE UNIT2
•
•
•
Three feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
Four feet below, 4 horizontal feet from, or 1 foot above
any door or gravity air inlet into the building.
Four feet from electric meters, gas meters, regulators
and relief equipment.
1.
Units may be installed on combustible floors made from
wood or class A, B, or C roof covering material.
2.
Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
Unitary Products Group
25
036-21411-002-A-0204
FIGURE 12 -DEE/DEG DIMENSIONS REAR VIEW - 3, 4, & 5 TON
Duct covers - units are shipped with all air duct openings
covered.
For side duct applications:
•
•
Remove and discard the supply and return air duct
covers.
Connect ductwork to duct flanges on the rear of the unit.
For bottom duct applications:
•
Remove the side supply air duct cover to gain access to
the bottom supply air knockout panel.
Remove and discard the bottom knockout panel.
Replace the side duct cover.
With filter section access panel removed from the unit,
remove and discard the bottom return air knockout
panel.
•
•
•
•
Replace the filter Access panel.
26
Unitary Products Group
036-21411-002-A-0204
2
7
-
1
/
2
7
-
1
/
4
2
7
-
1
/
2
1
0
-
1
/
4
3
-
1
/
2
1
9
-
1
/
8
8
-
1
/
4
"
A
"
4
4
-
7
/
8
4
-
3
/
8
L
.
H
.
E
N
D
V
I
E
W
R
E
A
R
V
I
E
W
D
I
M
E
N
S
I
O
N
"
A
"
F
I
X
E
D
1
2
O
U
T
D
O
O
R
A
I
R
D
A
M
P
E
R
M
O
T
O
R
I
Z
E
D
1
6
-
1
/
2
D
A
M
P
E
R
FIGURE 13 -DETAIL B UNIT DIMENSIONS WITH DAMPER/RAINHOOD
FIGURE 14 -UNIT & CURB APPLICATION
Unitary Products Group
27
036-21411-002-A-0204
FIGURE 15 -ROOF CURB DIMENSIONS DEE & DEG 3, 4, & 5 TON
TABLE 25: UNIT WEIGHTS
TABLE 26: ACCESSORY’S WEIGHT
CORNER WEIGHTS
(location, lbs.)
DESCRIPTION
ECONOMIZER
MOTORIZED OUTDOOR AIR DAMPER
UNIT
WEIGHT
(lbs.)
UNIT
50
26
18
23
“A”
188
199
206
160
173
180
“B”
185
196
203
157
170
177
“C”
145
154
159
123
135
140
“D”
147
156
162
125
137
143
DEG036
DEG048
DEG060
DEE036
DEG048
DEG060
665
705
730
565
615
640
ELECTRIC
HEAT
(nom. kW
DEE only)
5-7 kW
10 - 15 kW
10 - 30 kW
28
ROOF MOUNTING CURB
RELIEF/FIXED AIR DAMPER
BELT-DRIVE BLOWER
92
10
5
C
O
R
N
E
R
"
D
"
O
R
N
E
R
"
A
"
C
O
R
N
E
R
"
C
"
B
A
C
K
4
4
-
7
/
8
8
2
-
1
/
2
4
0
-
3
/
4
C
E
O
N
D
E
N
S
E
R
C
O
I
L
N
D
O
F
U
N
I
T
A
C
P
P
R
O
E
X
I
M
A
T
E
E
N
T
R
O
F
G
R
A
V
I
T
Y
1
9
-
3
/
4
F
R
O
N
T
FIGURE 16 -CENTER OF GRAVITY
28
Unitary Products Group
036-21411-002-A-0204
8. Condensate pan shall be internally sloped and conform
to ASHARE 62-89 self-draining standards. Condensate
connection shall be a minimum of 3/4" I.D. female and be
a ridged mount connection.
MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be High Efficiency factory-assembled, single pack-
aged, (DUS Electric Cooling/Gas Heat, DHC Electric Cooling/
Optional Electric Heat), designed for outdoor mounted instal-
lation. Units shall have minimum SEER ratings of 11.0. They
shall have built in field convertible duct connections for down
discharge supply/return or horizontal discharge supply/return,
and be available with factory installed options or field installed
accessories.
INDOOR (EVAPORATOR) FAN ASSEMBLY
1. Fan shall be direct drive, multi-speed, or a factory
installed belt drive, adjustable-pitch motor pulley option.
Job site selected (B.H.P.) brake horse power shall not
exceed the motors nameplate horse power rating, plus
the service factor. Units shall be designed not to operate
above service factor.
The units shall be factory wired, piped, charged with R-22
refrigerant and factory tested prior to shipment. All unit wiring
shall be both numbered and color coded. Enclosed in each
unit shall be a factory test log sheet consisting of the unit
tested pressures, temperatures and amps, as tested prior to
shipment.
2. Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly
throughout the entire range of operation. Airflow design
shall be constant air volume.
3. Bearings shall be sealed and permanently lubricated for
longer life and no maintenance.
All units shall be manufactured in a facility certified to ISO
9001 standards, and the cooling performance shall be rated
in accordance with DOE and ARI test procedures. Units shall
be UL listed and classified to ANSIZ21.47 standards and UL
1995/CAN/CSA No. 236-M90 conditions.
OUTDOOR (CONDENSER) FAN ASSEMBLY
1. The outdoor fan shall be of the direct-driven propeller
type, discharge air vertically, have aluminum blades riv-
eted to corrosion resistant steel spider bracket and shall
be dynamically balanced for smooth operation.
UNIT CABINET
2. The outdoor fan motor shall be totally enclosed with per-
manently lubricated bearings and internally protected
against overload conditions.
1. Unit cabinet shall be constructed of G90 galvanized
steel, with exterior surfaces coated with a non-chalking,
powered paint finish, certified at 750 hours salt spray test
per ASTM-B117 standards.
REFRIGERANT COMPONENTS
2. Indoor blower section shall be insulated with up to 1”
thick insulation, coated on the air side. Aluminum foil
faced insulation shall be used in the furnace compart-
ment and be fastened with ridged fasteners to prevent
insulation from entering the air stream.
1. Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
3. Cabinet panels shall be large size, easily removable for
servicing and maintenance.
4. Full perimeter base rails shall be provided to assure reli-
able transit of equipment, overhead rigging, fork truck
access and proper sealing on roof curb applications.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on
mounting.
a
dedicated, independent
5. Disposable 1" filters shall be furnished and be accessible
through a removable access door, sealed air tight. Units
filter track shall be designed to accommodate either 1 or
2" filters.
2. Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally-enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
6. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measure-
ments of evaporator fan performance without removing
panels or creating air by-pass of the coils.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-through design.
7. Units vertical discharge and return duct configuration
shall be designed to fit between standard 24" O.C.
beams without modification to building structure, duct
work and base unit.
3. Refrigerant Circuit and Refrigerant Safety Components
shall include:
30
Unitary Products Group
036-21411-002-A-0204
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
6. Heating section shall be provided with the following mini-
mum protection:
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
a. Primary and auxiliary high-temperature limit
switches.
c. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
b. Induced draft motor speed sensor.
c. Flame roll out switch (automatic reset).
d. Flame proving controls.
d. The refrigeration system shall provide at least 15 ºF
of liquid sub-cooling at design conditions.
ELECTRIC HEATING SECTION (DEE MODELS)
4. Unit Controls:
1. An electric heating section, with nickel chromium ele-
ments, shall be provided in a range of 5 through 30 KW,
offering two stages of capacity - 16 KW and above on
208/230 volt heaters and 20 KW and above on 460 and
575 volt heaters.
a. Unit shall be complete with self contained low-volt-
age control circuit protected by a resetable circuit
breaker fuse on the 24 volt transformer side.
b. Unit shall incorporate a lock-out circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor:
2. The heating section shall have a primary limit control(s)
and automatic reset, to prevent the heating element sys-
tem from operating at an excessive temperature.
3. The Heating Section assembly shall slide out of the unit
for easy maintenance and service.
I. Loss-of-charge/Low-pressure switch.
II. High-pressure switch.
4. Units with Electric Heating Sections shall be wired for a
single point power supply with branch circuit fusing
(where required).
III.Freeze-protection thermostat, evaporator
coil.
If any of the above safety devices trip, an LED (light-emitting
diode) indicator shall illuminate.
UNIT OPERATING CHARACTERISTICS
1. Unit shall be capable of starting and running at 125 ºF
outdoor temperature, exceeding maximum load criteria
of ARI Standard 210/240.
c. Unit shall incorporate AUTO RESET compressor
over temperature, over current protection.
d. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
2. The compressor, with standard controls, shall be capable
of operation down to 45 ºF outdoor temperature. Acces-
sory low ambient kit shall be available for operation
down to 0 ºF.
GAS HEATING SECTION (DEG MODELS)
3. Unit shall be provided with fan time delay to prevent cold
air delivery before heat exchanger warms up. (Gas heat
only.)
1. Shall be designed with induced draft combustion with
post purge logic, energy saving direct spark ignition and
redundant main gas valve. Ventor wheel shall be con-
structed of stainless steel for corrosion resistance.
ELECTRICAL REQUIREMENTS
2. The heat exchanger shall be of the tubular type, con-
structed of T1-40 aluminized steel for corrosion resis-
tance and allowing minimum mixed air entering
temperature of 25 ºF.
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
3. Burners shall be of the in-shot type, constructed of alu-
minum coated steel and contain air mixture adjustments.
STANDARD LIMITED WARRANTIES
4. All gas piping shall enter the unit cabinet at a single loca-
tion, through either the side or bottom, without any field
modifications.
•
•
•
•
Compressor- 5 Years
Heat Exchanger- 10 Years
Elect. Heat. Elem.- 5 Years
Parts - 1 Year
5. An integrated control board shall provide timed control of
evaporator fan functioning and burner ignition.
Unitary Products Group
31
OPTIONAL OUTDOOR AIR
OTHER PRE-ENGINEERED ACCESSORIES AVAIL-
ABLE
(Shall be made available by either/or):
1. ROOF CURB - 14" AND 8" high, full perimeter knock-
down curb with hinged design for quick assembly.
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55 ºF. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
2. MANUAL OUTDOOR DAMPER - Provides 0% through
35% or 0% through 100% outdoor air capability (field
adjustable). Designed for duct mounted side supply/
return applications. Includes a hood and a screen
assembly.
3. OUTDOOR COIL GUARD - Prevents coil damage.
4. BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
5. PROPANE CONVERSION KIT - Contains new orifices
and gas valve regulator to convert from natural to L.P.
gas.
6. LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nano grams per joule.
7. HIGH ALTITUDE - NATURAL GAS - Required for appli-
cations between 2000 and 6000 feet altitude.
8. HIGH ALTITUDE - PROPANE GAS - Required for appli-
cations between 2000 and 6000 feet altitude. Must be
used with propane conversion kit.
2. DUAL INPUT DIFFERENTIAL ELECTRONIC
ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake damp-
ers shall not exceed 2% when dampers are fully closed
and operating against a pressure differential of 0.5 IWG.
A unit mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in
the design CFM of outdoor air to meet the minimum ven-
tilation requirement of the conditioned space during nor-
mal operation. During economizer operation, a mixed-air
temperature control shall modulate the outdoor and
return air damper assembly to prevent the supply air
temperature from dropping below 55 ºF. Changeover
from compressor to economizer operation shall be pro-
vided by two integral electronic enthalpy controls - one
that senses outdoor air and one that senses indoor air.
Both enthalpy sensors supply input to the logic module
which modulates both sets of dampers for maximum
economizer savings. The outdoor intake opening shall
be covered with a rain hood that matches the exterior of
the unit. Water eliminator/filters shall be provided. Simul-
taneous economizer/compressor operation is also possi-
ble. Dampers shall fully close on power loss.
9. GAS PIPING - Contains pipe nipples, fittings and gas
cock (including panel assess gaskets) required for bot-
tom gas supply connection with external shut-off.
10. BURGLAR BARS - Designed to work with above
roofcurbs. Fits duct openings of curb supply and return
air openings.
11. THERMOSTATS - Multiple models available from
A.C.O., M.C.O., Electronic or Electrical Mechanical ver-
sions.
12. ANTI-RECYCLE TIMER - Assures 5-minute off-time
between compressor cycles.
13. LOW AMBIENT KIT - Provides unit cooling operation
down to 0 ºF.
14. ELECTRIC HEAT - Slide-in design, provides single point
power and ranges from 5 to 30 KW.
OTHER FACTORY INSTALLED OPTIONS
1. HIGH PERFORMANCE BELT DRIVE MOTOR
2. TECHNICOAT PHENOLIC COATED COND. COIL
3. ELECTRONIC ENTHALPY ECONOMIZER
4. DUAL INPUT ELECTRONIC ENTHALPY ECONO-
MIZER
Subject to change without notice. Printed in U.S.A.
036-21411-002-A-0204
Copyright © 2004 by Unitary Products Group. All rights reserved.
Supersedes: 036-21411-001-A-0502
Unitary
Products
Group
5005
York
Drive
Norman
OK
73069
|