Installation
Owner
Diagnostics
Vertical Stack
Water-Source Heat Pump
Model GETB
Models
“A” and later Design Sequence
GETB
009-036 – 60 HZ
009-036 – 50 HZ
February 2006
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Installation/Startup/Commissioning
Pre-installation Checklist
General Information
4
4
5
6
Dimensions/Weights
9
Installation Instructions
18
Electrical Requirements
19
20
Pre-Startup Checklist
Startup/Commissioning
Sequence of Operation
20
21
24
25
26
27
29
Operating Pressures
Startup Checklist & Log
Maintenance
Warranty Information
Troubleshooting Checklist
Unit Wiring
WSHP-SVN08B-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Pre-installation
Checklist
!
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this
product during installation, maintenance or repair will expose you to
airborne particles of glass wool fibers and ceramic fibers known to the
state of California to cause cancer through inhalation. Glass wool fibers
may also cause respiratory, skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of
lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifications.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been com-
pleted. Check for damage promptly after the unit(s) are unloaded. Once the
bill of lading is signed at the jobsite, the unit(s) are now the property of the
SOLD TO party and future freight claims MAY NOT be accepted by the freight
company.
4. Verify that the refrigerant charge has been retained during shipment by use
of gauges. Schrader taps are located external to the cabinet on the 2-ton
through 6-ton equipment.
5. After assuring that charge has been retained, reinstall the schrader caps to
assure that refrigerant leakage does not occur.
CAUTION
Microbial Growth!
Wet interior unit insulation can become an amplification site for
microbial growth (mold), which may cause odors and damage to the
equipment and building materials. If there is evidence of microbial
growth (mold) on the interior insulation, the insulation should be
removed and replaced prior to operating the system.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to
the elements, and to prevent possible IAQ contaminant sources from growing,
the unit should be stored indoors. If indoor storage is not possible, the following
provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the ground to assure ade-
quate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent
moisture from standing on the unit(s) surfaces. Wet interior unit insulation
can become an amplification site for microbial growth (mold) which has
been determined to be a cause of odors and serious health related indoor air
quality problems.
4. Store refrigeration units (chassis) units in the normal UP orientation to main-
tain oil in the compressor. Cabinet configurations may be stored as crated.
5. Do not stack units.
4
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Information
Unit Nameplate
Sound Attenuation
ZN510 Controls
(GET option)
The unit nameplate is located at the
front of the unit. It includes the unit
model number, serial number, electri-
cal characteristics, refrigerant charge,
and other pertinent unit data.
Sound attenuation is applied as a stan-
dard feature in the product design. The
enhanced reduction package includes
a heavy gage base plate, and gasket/
insulation around the compressor en-
closure.
Units incorporating the ZN510 control
option design will include a digital
TM
LonTalk certified control board. The
control board will support such op-
tions as: random start delay, heating/
cooling status, occupied/unoccupied
mode and fan/filter status.
Compressor Nameplate
The nameplate for the compressors
are located on the compressor shell.
An optional deluxe sound reduction
package is also available. It includes a
heavy gage base plate, gasket and in-
sulation around the compressor enclo-
sure, and vibration isolation between
the chassis and cabinet. An additional
dampening treatment is applied
Power wiring is made at the contactor.
The wiring is fed through the left or
right conduit tube, and into the cabi-
net’s control box (contactor). See
manual WSHP-IOP-2 for diagnostic in-
formation.
Unit Description
Before shipment, each unit is leak test-
ed, dehydrated, charged with refriger-
ant and run tested for proper control
operation.
around the compressor enclosure to
achieve greater acoustical reductions.
Water-to-Refrigerant Coils
Schrader Connections
The co-axial water-to-refrigerant heat
exchanger for the 3/4-ton through 3-
ton equipment is constructed of cop-
per or cupro-nickel (option) for the wa-
ter section and stainless steel for the
refrigeration section.
Controls
Connections for the low and high side
of the refrigeration system are located
conveniently on the chassis’ top be-
neath a sheet metal plate.
The control system offered to control
the unit is a Basic 24 volt control for
the 3/4-ton through 2-ton retrofit
(WPRD) equipment. A 50 VA trans-
former is factory supplied on this unit
configuration. See wiring diagram on
chassis access panel for field wiring
connection to the 24 volt mechanical
thermostat.
The heat exchanger is leak tested to
assure there is no cross leakage be-
tween the water and refrigerant gas.
Water Connections
1/2" or 3/4" water connections are lo-
cated on the chassis’s upper section
and clearly labeled for water-in/out
hose to riser hook-up.
Deluxe 24V Controls
(GET model)
Units containing the Deluxe 24V con-
trol design will incorporate a micro-
processor-based control board. The
Trane microprocessor board is factory
wired to a terminal strip to provide all
necessary terminals for field connec-
tion. The deluxe board is equipped
with a random start relay, anti-short
cycle timer, brown out protection,
compressor disable, unit safety con-
trol, diagnostics and a generic relay
(which may be available for field use).
See page 16 for diagnostic informa-
tion.
Blower/Motor
The blower and motor is located inside
the unit cabinet. The blower and motor
may be removed from the cabinet
through the chassis opening. After re-
moving the chassis, the blower as-
sembly is strapped into the unit
cabinet through a single metal, flexi-
ble bracket. We refer to this bracket as
a housing belly bracket. After detach-
ing one screw at the bottom/front edge
of the bracket, the housing and motor
are free to be lifted from the fan deck.
Power wiring is made at the contactor.
The wiring is fed through the left or
right conduit tube, and into the cabi-
net’s control box (contactor).
WSHP-SVN08B-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions/Weights/
Clearance
Table 1: Unit weights
Shipping
Shipping
Weight
!
WARNING
Size
Weight
with pallet (lb) w/o pallet (lb)
Improper Unit Lift!
Cabinet
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
009
012
015
018
024
036
135
135
175
175
225
225
115
115
150
150
195
195
Chassis
009
012
015
018
024
036
90
95
80
85
110
115
190
200
100
105
180
190
Unit Location and Clearances
Locate the unit in an indoor area. The
ambient temperature surrounding the
unit must not be less than 45°F. Do not
locate the unit in areas subject to
freezing.
R
S
D
Attention should be given to service
clearance and technician safety. The
unit chassis should be easily removed
from the cabinet in all applications.
There must be enough space for ser-
vice personnel to perform mainte-
nance or repair. Provide sufficient
room to make water, and electrical
connection(s). Local and national
codes should be followed in providing
electrical power connections. See Fig-
ure 1 for mechanical clearances.
ALLOW 36" (914 mm)
AT UNIT FRONT FOR
CHASSIS REMOVAL
Figure 1: Mechanical clearances
6
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
GET 009-036
12 1/2"
(318)
GET
A
B
C
D
E
F
8" (203)
3 3/4"
(95)
009, 012 16 1/4" (413) 16 1/4" (413) 8 1/8" (206) 39 1/8" (994) 14 3/4" (375) 3/4" (19)
VARIES DEPENDENT
ON RISER O.D.
R
S
D
015-018
024-036
18" (457)
24" (610)
20" (508)
24" (610)
10" (254)
40 5/8" (1032) 18 3/4" (476) 3/4" (19)
3/4" (19
12" (305) 49 5/8" (1260) 22 5/8" (575)
RETURN
SUPPLY
OPTIONAL
DUCT OPENING
1" (12.7) DUCT
COLLAR
11" (279) FOR 80" (2032) CABINET HEIGHT
3" (76) FOR 88" (2235) CABINET HEIGHT
G
H
DRAIN
SUPPLY-AIR OPENINGS AND RISER LOCATIONS CANNOT
BE ONTHE SAME SIDE OFTHE UNIT.
1/2" (12.7) O.D.
ELECTRIC CONDUIT
1" (25.4)
RISER LOCATION CAN BE ON ANY SIDE EXCEPT FRONT,
AND MAY BE SUPPLIED BYTRANE OR BY OTHERS.
J
B
TOP
SWAGE 3" (76)
A
G
SUPPLY-AIR
OPENING
LOW VOLTAGE
CONNECTION BOX
FORTHERMOSTAT
C
CONTROL BOX
THROWAWAY
FILTER
D
RISER CONNECTION
1/2” (13) NPTE = 009-018
3/4” (19) NPTE = 024,036
CHASSIS
ACCESS
PANEL
DRAIN
NOTE:
4 3/4"
(121)
CONNECTION
RIGHT RISER
LOCATION SHOWN
IN FRONT AND RIGHT
VIEWS.
3/4" (19) O.D.
E
F
FRONT
RIGHT SIDE
WSHP-SVN08B-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Hinged Acoustical Door
Return Air (hinged)
Acoustical Door
3 1/2” 3/8”
The hinged acoustical door is recessed
into the wall so that the door is flush
with the surface of the wall.
A
2“ X 4” STUD
SHEETROCK
The opening through the wall
for the door assembly must be
centered with the return-air
opening of the unit cabinet.
For full installing instructions
of the return-air acoustical
door, see page 12.
B
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR OPENING
FLANGE ON CABINET
A
SHEET ROCK
OPENING
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR OPENING
FLANGE ON CABINET
Unit Size
A
B
09
012
19 1/4”
(489)
44 1/8”
(1121)
2“ X 4”
STUD
SHEETROCK
015
018
23 1/4”
(591)
45 1/4”
(1149)
Note:
TOP VIEW
024
036
27 1/8”
(689)
54 5/8”
(1387)
Finished wall and framing should not
touch the unit cabinetry.
CABINET
3 1/2” 3/8”
SHEETR
RETURN AIR
DOOR FRAME
2 X 4 STUD
RETURN-AIR OPENING
FLANGE ON CABINET
1“ X 1” CLOSED
CELL INSULATION
B
1“ X 1” CLOSED
CELL INSULATION
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN AIR
DOOR FRAME
2 1/4“
5“
4 5/8“
SHEETROCK
FLOOR
CABINET
1 1/2” X 2 3/8”
3 1/2” 3/8”
SIDE VIEW
8
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
General Installation Checks
!
WARNING
The checklist below is a summary of
the steps required to successfully in-
stall a unit. This checklist is intended to
acquaint the installing personnel with
procedures required in the installation
process. It does not replace the de-
tailed instructions called out in the ap-
plicable sections of this manual.
Hazardous
Voltage!
Disconnect all electric power,
including remote disconnects and
discharge all motor start/run
capacitors before servicing.
Follow proper lockout/tagout
procedures to ensure the power
can not be inadvertently
1
Remove packaging and inspect the
unit. Check the unit for shipping
damage and material shortage; file
a freight claim and notify appropri-
ate sales representation.
energized. Failure to disconnect
power before servicing could
result in death or serious injury.
Main Electrical
5
6
7
Verify the power supply complies
with the unit nameplate specifica-
tions.
Note: The unit cabinet is packaged
in a wooden crate. A pry bar and/
or hammer will be needed for
packaging removal.
Inspect all control panel compo-
nents; tighten any loose connec-
tions.
The chassis sits inside a cardboard
tray with an upper box for protec-
tion. Typically four chassis will be
shrink-wrapped to a single pallet.
Connect properly sized and pro-
tected power supply wiring to a
field-supplied/installeddisconnect
switch and to the unit power block
(1TB1) in the unit’s cabinet control
box for equipment.
2
3
4
Verify the correct model, options
and voltage from the unit name-
plate.
8
Install proper grounding wires to
an earth ground.
Verify the installation location of
the unit will provide the required
clearance for proper operation.
Note: All field-installed wiring must
comply with NEC and applicable local
codes.
Remove refrigeration access panel
and inspect the unit. Be certain the
refrigerant tubing has clearance
from adjacent parts.
Low Voltage Wiring (AC & DC)
Requirements
9
Connect properly sized control wir-
ing to the proper termination
points between the field supplied
thermostat and the terminal plug
in the equipment’s junction box.
WSHP-SVN08B-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
expansion slots. The stubouts
should be perpendicular to the cab-
inet panel.
!
WARNING
Improper Unit Lift!
Test lift unit approximately 24
inches to verify proper center of
gravity lift point. To avoid
7 Verify all risers are vertical and that
they penetrate the swaged joint at
least 1". Riser should not be al-
lowed to bottom out.
dropping of unit, reposition lifting
point if unit is not level. Failure to
properly lift unit could result in
death or serious injury or possible
equipment or property-only
damage.
8 Braze riser joints. Soft solder or
low-temperature alloys should not
be used in this application.
9 If risers are field provided, it is rec-
ommended that the risers be an-
chored to the building structure
with a minimum of one contact
point. For expansion and contrac-
tion reasons, do not fasten risers
rigidly to the building.
Unit Placement
If unit cabinet assembly includes fac-
tory provided risers, and "no" field
provided between-the-floor riser ex-
tensions, please move to Step 1.
Note: Risers are designed to accom-
modate a maximum of 1 1/2" to 3" ex-
pansion and contraction. If the total
calculated riser expansion exceeds 3",
expansion devices must be field pro-
vided.
10 Seal access holes made through the
cabinet for piping with suitable ma-
terial to help eliminate air leakage.
FLOOR
11 See page 14 for system flushing.
If unit cabinet assembly includes fac-
tory provided risers and field provided
between-the-floor riser extensions are
required, install the extensions before
installing the cabinet.
Water Connection
3" SWAGE
For vibration isolation, it is recom-
mended that flexible steel braided
hoses be installed instead of hard pip-
ing between the vertical risers and the
unit chassis.
1 Install drain valve, shut-off/balanc-
ing valves, flow indicators and
drain at the base of each supply and
return riser to enable system flush-
ing at start-up, balancing and ser-
vice/maintenance.
Trane offers 4-types of hose kit varia-
tions:
•
•
•
•
Stainless steel braided flexible
hose with manual shut-off (ball)
valves
2 Lift cabinet into space while align-
ing it into the 3"swage of the riser
below.
Stainless steel braided flexible
hose with manual deluxe shut-off
(ball) valves
Note: Take extra care as not to scrape
or dent risers during positioning. The
riser should fall approximately 2" into
the 3" swage. This will allow for the
variation in floor-to-floor dimensions,
and keep the riser joints from bottom-
ing out.
Stainless steel braided flexible
hose with manual circuit-setter
valve
Stainless steel braided flexible
hose with automatic balancing
valve
FLOOR
3 Level the cabinet.
4 Plumb risers in two planes to as-
sure proper unit operation and con-
densate drainage.
Additional accessories, such as a
strainer are recommended for use to
eliminate contaminants from entering
the co-axial water-to-refrigerant heat
exchangers.
Figure 2: Stacking illustration
5 Anchor all units into place.
6 For field provided risers, center the
supply/return stubouts into the unit
10
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Field Installed Power Wiring
Power wiring to the equipment must
conform to National and Local Electric
Codes (NEC) by a professional electri-
cian.
The high voltage connection is made
at the 1PB1 power block in the cabinet
control box. Refer to the customer
connection diagram that is shipped
with the unit for specific termination
points.
FACTORY CONDUIT
Provide proper grounding for the unit
in accordance with the local and na-
tional codes.
!
WARNING
Live Electrical
Control Power Transformer
The 24-volt control power transform-
ers are to be used only with the acces-
sories called out in this manual.
Transformers rated greater than 50 VA
are equipped with internal circuit
breakers. If a circuit breaker trips, turn
OFF all power to the unit before at-
tempting to reset it.
Components!
During installation, testing, ser-
vicing and troubleshooting of this
product, it may be necessary to
work with live electrical compo-
nents. Have a qualified licensed
electrician or other individual
who has been properly trained in
handling live electrical compo-
nents perform these tasks. Failure
to follow all electrical safety pre-
cautions when exposed to live
electrical components could re-
sult in death or serious injury.
Figure 3: Power wire entrance
!
WARNING
Hazardous Voltage!
Disconnect all electric power, in-
cluding remote disconnects and
discharge motor start/run capaci-
tors before servicing. Follow prop-
er lockout/tagout procedures to
ensure the power can not be inad-
vertently energized. Failure to dis-
connect power before servicing
could result in death or serious in-
jury.
Verify that the power supply available
is compatible with the unit’s name-
plate. Use only copper conductors to
connect the power supply to the unit.
CAUTION
Use Copper
Conductors Only!
Unit terminals are not designed
to accept other types of conduc-
tors. Failure to use copper con-
ductors may result in equipment
damage.
The transformer is located in the
chassis control box.
Main Unit Power Wiring
A field supplied disconnect switch
must be installed at or near the unit in
accordance with the National Electric
Code (NEC latest edition).
Location of the applicable electric ser-
vice entrance for HIGH (line voltage)
may be found in Figure 3.
1
Route power wire to the cabinet
control box through the factory in-
stalled conduit at the top of the unit
cabinetry.
WSHP-SVN08B-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
4 Place the door frame into the sheet rock opening. A positive seal is critical be-
tween the back of the door frame and the front of the cabinet. Ensure that the
gasket material seals properly. Note: When placing the sheet rock panel, make
certain the opening for the door is centered with the return-air opening in the
cabinet ( 1/8").
Drywall Installation
Before installing drywall around cabi-
net. Cover the cabinet supply and re-
turn openings with plastic or
cardboard to help prevent dust or con-
struction debris from reaching unit
components. Warranties will be void-
ed if paint or foreign debris is allowed
to contaminate internal unit compo-
nents.
3 1/2” 3/8”
A
2“ X 4” STUD
SHEETROCK
The location of the drywall may be de-
pendent upon the type of return air ac-
cess design.
B
1 Units that contain a field provided
return air access assembly, contrac-
tor must calculate location of dry-
wall to allow for frame mounting.
1“ X 1” CLOSED
CELL INSULATION
RETURN AIR OPENING
FLANGE ON CABINET
A
Units utilizing Hinged Acoustic
Door Assembly.
SHEET ROCK
1“ X 1” CLOSED
RETURN AIR OPENING
OPENING
CELL INSULATION
1 Locate the side studs a minimum of
1 1/4-inches and a maximum of 1 3/
8-inches from the cabinet to the side
of the stud. This critical dimension,
combined with "distance between
studs" is used to determine the side-
to-side opening for the door, dimen-
sion A. The distances provided in
the table are a "minimum" dimen-
sion. Allow 3 1/2-inches from the
front of the cabinet to the sheet rock
surface, Figure 4 - Top View. Figure
5, mock-up of stud placement.
FLANGE ON CABINET
Unit Size
A
B
09
012
19 1/4”
(489)
44 1/8”
(1121)
2“ X 4”
STUD
SHEETROCK
015
018
23 1/4”
(591)
45 1/4”
(1149)
Note:
TOP VIEW
024
036
27 1/8”
(689)
54 5/8”
(1387)
Finished wall and framing should not
touch the unit cabinetry.
CABINET
3 1/2” 3/8”
SHEETR
2 The height of the door assembly
must be positioned to recess the
door 2 1/4-inches from the cabinet’s
return-air opening, Figure 4 - Side
View blow-up.
RETURN AIR
DOOR FRAME
2 X 4 STUD
RETURN-AIR OPENING
FLANGE ON CABINET
1“ X 1” CLOSED
CELL INSULATION
3 Locate dimensions A and B for sheet
rock opening size. The position of
the sheet rock opening must be cen-
tered side-to-side with the return-air
opening in the cabinet. Ensure the
bottom of the sheet rock opening is
2 1/4-inches below the return-air
opening in the cabinet. This allows
the door recess to rest on the bot-
tom of the sheet rock opening for
proper vertical placement of the
door.
B
Figure 5:
1“ X 1” CLOSED
CELL INSULATION
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN AIR
DOOR FRAME
2 1/4“
5“
4 5/8“
SHEETROCK
FLOOR
CABINET
1 1/2” X 2 3/8”
3 1/2” 3/8”
SIDE VIEW
Figure 4: Drywall installation for hinged acoustic door
12
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Chassis Installation
1 Remove three 16-inch bolts on the
chassis and discard, Figure 9.
1 Secure the door frame to the side
studs using the holes located in the
door frame and field provided
screws, Figure 6.
3 After verifying that the air panel gas-
ket is sealed to the coil, secure the
air panel to the door frame using the
slots located on the sides of the air
panel, Figure 8.
Figure 9: Shipping bolts
2 Rotate the triangular metal plate to
cover the bolt holes in the chassis.
Secure with two sheet metal screws.
Figure 6: Door opening
3 Remove two shipping brackets (one
on each side) attached to the chassis
slide rails and discard, Figure 10.
Note: Remove this bracket only if
the enhanced sound package design
is preferred.
Figure 8: Secure to door frame
Note: If the gap between the door
frame, and the side stud is over 1/16-
inch, place a shim in between the door
frame and the stud to prevent the door
frame from bending/denting.
4 Install Filter.
5 Vacuum all dust and construction
debris from unit after cutting out
supply/return openings.
2 Place the air panel into the door
opening. The gasket on the back
side of the air panel should seal
around the coil perimeter, Figure 7.
Supply Air Ductwork
1 A 2" (50.8 mm) duct flange (field
provided) may be required to help
eliminate supply air from recirculat-
ing back into the return air, air-to-re-
frigerant coil prior to discharging
into the space.
2 Equipment containing a top dis-
charge, ducted design: install field
ductwork to the unit providing a wa-
ter tight flexible connector at the
unit. This helps prevent operating
sounds from transmitting through
the ductwork. Elbows with turning
vanes or splitters are recommended
to minimize air noise due to turbu-
lence and to help reduce static pres-
sure.
Figure 10: Bracket removal for
enhanced sound package
4 Connect water coil pipe to the sys-
tem riser with a flexible steel hose
assembly.
5 Verify that the shut-off/balancing
valve in the return line/supply line
are closed.
Figure 7: Air panel gasket
6 Place shut-off valves in appropriate
location (see sticker on the equip-
ment for best placement recom-
mendation) to allow chassis to slide
easily in/out of unit cabinetry.
WSHP-SVN08B-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
IMPORTANT
5 With the air vented and the water
circulating, the entire system
should be checked for leaks with re-
pairs made as required.
6 Operate the supplementary heat
system making checks per manu-
facturer’s instructions. During this
operation, visual checks should be
made for leaks that may have oc-
curred due to increased heat. Re-
pair as required.
!
WARNING
Ensure the gasket material creates a
positive seal around the entire coil to
avoid coil bypass.
Live Electrical
Components!
During installation, testing, ser-
vicing and troubleshooting of this
product, it may be necessary to
work with live electrical compo-
nents. Have a qualified licensed
electrician or other individual
who has been properly trained in
handling live electrical compo-
nents perform these tasks. Failure
to follow all electrical safety pre-
cautions when exposed to live
electrical components could re-
sult in death or serious injury.
If a field supplied door is used, ensure
the front cover is attached to the build-
ing structure and not the unit cabinet.
Supply Grille installation
See Table 2 for supply air dimensions.
1
Install the supply grille(s) into the
cabinet discharge opening. Insure
there are no air gaps between the
cabinet supply air and the grille.
This helps prevent recirculation of
supply air into the return air open-
ing behind the drywall.
7 Open the system at the lowest point
for the initial blow down (making
sure the make up water is equal to
the water being dumped). Continue
blow down until the water leaving
the drain runs clear, but not less
than 2 hours.
7 Flush system. See Cleaning and
Flushing the Water Loop for flushing
instructions.
8 Open the unit water valves and
check piping for leaks.
2
Secure grille(s) into the drywall via
two screws.
8 Shut down pumps and supplemen-
tary heat system. Reconnect the
hoses placing the water-to-refriger-
ant heat exchanger in the water cir-
culating system.
Cleaning and Flushing
the Water Loop
After the piping system is complete,
the flexible hose connectors should be
doubled back to complete the water
circuit external to the unit (avoiding
trash settle-out in the condenser). An
extra pipe may be necessary to con-
nect the hose kits. See Page 15 for an-
tifreeze/water mixture by volume.
9 Connect electrical to unit chassis via
the quick connect mating plugs.
Note: Vents should be open when the
pumps and supplementary heat sys-
tem are shut down.
Note: Four plugs are included (motor,
optional condensate overflow, power
and thermostat).
CONNECTION
HOSE
10Slide chassis into the cabinet. Cen-
ter the chassis left to right to mini-
mize sound transmission. See
Figure 11.
CIRCULATING
PUMP
3 Water circulation system should be
filled with clean water using the wa-
ter make up connections. Note: Air
vents should be opened during fill-
ing.
WATER-SOURCE
HEAT PUMP
TEMPORARY
CONNECTION
FOR SYSTEM
FLUSHING
4 With the air vents closed, start the
circulating pump and then crack the
air vents to bleed off the trapped
air, assuring circulation through all
components of the system.
GROUND-LOOP
OR
COOLINGTOWER/BOILER
Note: Make up water must be available
to the system to replace the volume
formerly occupied by the air that is
bled off.
Figure 12: Flushing the water loop
Table 2: Supply air opening size
Top Discharge
Up to 100%
CFM
GET
Single Grille
100% CFM
Two Grille
50% CFM
Three Grille
33% CFM
Model
Figure 11: Install chassis centered
12W x 10H
(305 x 254)
10W x 6H
Not
14 x 10
009, 012
(254 x 152)
Recommended
(356 x 254)
11 Verify unit’s air filter is properly
place in the chassis filter rack.
015, 018,
024
14W x 12H
(356 x 305)
14W x 12H
(356 x 305)
12W x 8H
(305 x 203)
16 x 14
(406 x 356)
12 Install cabinet’s front cover to the
hinged door.
Not
16W x 14H
14W x 12H
(356 x 305)
17 x 17
(432 x 432)
036
Recommended (406 x 356)
14
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 3: Antifreeze requirements based on volume
Using Antifreeze
In areas of the country where entering
water temperatures drop below 45°F
or where piping is being run through
areas subject to freezing, the loop
must be freeze protected by using an
approved antifreeze solution to pre-
vent the earth loop water from freez-
ing inside the heat exchanger.
Methanol and glycols are the most
commonly used antifreeze solutions.
Consult your geothermal unit supplier
for locally approved solutions in your
area.
Minimum Temperature for Freeze Protection
Type of Antifreeze
10°F
25%
-
15°F
21%
-
20°F
16%
-
25°F
10%
-
30°F
3%
Methanol
Propylene Glycol
6%
Propylene glycol is not recommended
in installations where the water tem-
perature are expected to fall below
30°F. At extreme temperatures, the vis-
cosity increases to the point where
normal loop circulating pumps may
not maintain proper flow.
If propylene glycol is the only locally
approved solution for anti-freeze,
good engineering practices should be
used to achieve the desired flow.
Calculate the approximate volume of
water in the system by using the re-
quirements detailed in Table 8, Water
Volume. Add three gallons to this total
to allow for the water contained in the
hose kit and geothermal unit.
WSHP-SVN08B-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Low Voltage Wiring
Low Voltage Wiring
Factory ordered thermostats and zone
sensors are pre-wired with a quick
connecting plug.
Factory provided plug
1 After installing the cabinet assem-
bly, simply plug the male portion of
thermostat/zone sensor plug into
the female portion of the plug locat-
ed inside the unit’s junction box.
2 Mount the thermostat or zone sen-
sor on the finished drywall.
Six (6) Pin Connector/Harness
Red = 24V
Black = Fan
Orange = RV
Yellow = Compressor
Blue = Common
Thermostat/zone sensor connection is
shown in Figure 13.
Low Voltage Wiring for Field
Provided Thermostats/Zone
Sensors
Ensure that the AC control wiring be-
tween the controls and the unit’s ter-
mination point does not exceed three
(3) ohms/conductor for the length of
the run.
Figure 13: Zone sensor connection
Table 5: Deluxe controller diagnostic LEDs
Color: Green
Color: Red
Controller Mode
LED1
OFF
ON
LED2
LED3
OFF
OFF
OFF
Control OFF
Normal/Compressor OFF
Anti-short Cycle
Note: Resistance in excess of 3-ohms
per conductor may cause component
failure due to insufficient AC voltage
supply.
OFF
ON
OFF
FLASH
ON
ON
OFF
Normal/Compressor ON
Brownout Condition
Check all loads and conductors for
grounds, shorts, and mis-wiring.
FLASH
ON
ON
OFF
FLASH
FLASH
ON
ON
Soft Lockout (low pressure)
Soft Lockout (high pressure)
Manual Lockout (low pressure)
Manual Lockout (high pressure)
Manual Lockout (condensate overflow)
Compressor Disable
Use copper conductors unless other-
wise specified.
ON
FLASH
ON
ON
Do not run the AC low voltage wiring
in the same conduit with the high volt-
age power wiring.
ON
ON
FLASH
OFF
ON
FLASH
ON
ON
OFF
Table 4: 24V AC conductors
Distance from unit
to Control
Recommended
Wire Size
000-460 feet
461-732 feet
733-1000 feet
18 gauge
16 gauge
14 gauge
16
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Air Flow Adjustment
Blower Motor Speed Retrofit
Motors installed in the unit have mul-
tiple speed configurations. To modify
the rpm of the motor, the following
steps may be followed.
1
Locate the blower motor relay in-
side the chassis control box.
Remove the undesired speed tap.
Select desired speed tap wire by
using information from Table 7.
Connect desired tap wire to the
1K4 relay at spade 4.
2
3
4
5
!
WARNING
Reconnect power to the unit.
Hazardous Voltage!
Disconnect all electric power, in-
cluding remote disconnects and
discharge motor start/run capaci-
tors before servicing. Follow prop-
er lockout/tagout procedures to
ensure the power can not be inad-
vertently energized. Failure to dis-
connect power before servicing
could result in death or serious in-
jury.
Table 6: Lead change
Lead Colors
Lead Speed
Blower
High
Low
1G
9A
Table F1: Blower External Static Pressure without Return Air Door (RAD), with filter
External Static Pressure (in. of wg)
Model Speed
Min Max
CFM CFM
280 482
Ducted
No.
Tap
0
-
-
350
285
-
0.05
456
341
-
-
-
442
-
-
-
582
-
-
-
0.1
422
329
-
-
-
422
-
-
-
566
-
-
-
0.15
383
309
-
0.2
347
283
-
0.25
0.3
0.35
0.4
0.45
0.5
0.55
0.6
0.65
0.7
GET009 High
GET009 Low
GET009 High
GET009 Low
GET012 High
GET012 Low
GET012 High
GET012 Low
GET015 High
GET015 Low
GET015 High
GET015 Low
GET018 High
GET018 Low
GET018 High
GET018 Low
GET024 High
GET024 Low
GET024 High
GET024 Low
GET036 High
GET036 Low
GET036 High
GET036 Low
Yes
Yes
No
308
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No
-
-
-
-
-
-
-
-
-
-
-
-
Yes
Yes
No
380 481
481
404
-
-
458
384
-
-
435
411
385
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
492
402
-
-
-
-
-
-
-
-
-
-
-
No
-
-
-
-
-
-
-
-
-
-
Yes
Yes
No
475 652
-
-
652
631
611
584
561
535
503
467
429
689
-
-
-
-
-
-
-
551
-
-
-
628
-
-
-
535
-
-
-
613
-
-
974
814
-
519
505
486
-
-
-
-
-
-
-
585
485
-
-
-
-
-
-
-
-
-
-
-
No
-
-
-
-
-
-
-
-
-
-
Yes
Yes
No
570 800
-
-
799
772
747
723
693
664
632
603
-
-
-
-
-
-
-
648
-
-
-
642
-
-
-
596
580
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
713
552
-
-
-
-
-
-
No
-
954
793
-
-
-
-
927
773
-
-
-
-
-
-
Yes
Yes
No
760 974
905
877
846
824
790
-
-
-
-
-
-
-
878
853
836
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
987
807
-
-
-
-
-
-
-
-
-
-
No
-
-
Yes
Yes
No
1135 1344
1344 1313 1282 1255 1219
-
-
-
-
-
-
-
1271 1263 1253 1238 1230 1213 1196 1178 1155
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1324
1229
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No
1
2
3
The NO "Ducted" option is for non-ducted (free return) units.
Units specified as "non-ducted" (free return) are factory wired to low-speed.
Units specified as "ducted" are factory wired to high-speed.
WSHP-SVN08B-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
Table F2: Blower External Static Pressure with Return Air Door (RAD), with filter
External Static Pressure (in. of wg)
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7
Speed
Tap
Min
CFM
280
-
-
-
380
-
-
-
475
-
-
-
Max
CFM
482
-
-
Model No.
Ducted
0
-
-
345
280
-
GET009
GET009
GET009
GET009
GET012
GET012
GET012
GET012
GET015
GET015
GET015
GET015
GET018
GET018
GET018
GET018
GET024
GET024
GET024
GET024
GET036
GET036
GET036
GET036
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
Yes
Yes
No
451
336
-
-
417
324
-
-
378
304
-
-
459
382
-
-
342
278
-
-
436
362
-
-
303
-
-
-
413
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No
-
Yes
Yes
No
481
-
-
-
652
-
-
-
800
-
-
-
-
-
389
-
-
363
-
-
-
420
-
-
-
572
-
-
-
623
-
-
-
400
-
-
-
556
-
-
-
617
-
-
-
470
380
-
No
-
-
-
-
Yes
Yes
No
-
-
642
621
601
574
551
525
-
-
-
698
-
-
-
493
-
-
-
668
-
-
-
457
-
-
-
419
-
-
-
679
-
-
-
-
541
-
-
-
603
-
-
-
525
-
-
-
588
-
-
927
767
-
509
495
476
-
-
575
475
-
-
-
-
-
-
No
-
-
-
-
-
Yes
Yes
No
570
-
-
-
-
-
774
747
722
639
607
578
-
571
555
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
690
524
-
-
-
-
-
-
No
-
907
746
-
-
-
-
880
726
-
-
-
-
-
-
Yes
Yes
No
760
974
858
830
799
777
743
-
-
-
-
-
-
-
831
806
789
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
940
760
-
-
-
-
-
-
-
-
-
-
No
-
-
Yes
Yes
No
1135 1344
1250 1219 1188 1161 1125
-
-
-
-
-
-
-
1177 1169 1159 1144 1136 1119 1102 1084 1061
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1280
1140
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No
1
2
3
The NO "Ducted" option is for non-ducted (free return) units.
Units specified as "non-ducted" (free return) are factory wired to low-speed.
Units specified as "ducted" are factory wired to high-speed.
Table E1: Electrical Performance
Blower
Motor
FLA
Blower
Motor
HP
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Total
FLA
Comp.
RLA
Comp.
LRA
Model No.
Oversized Blower
Volts
GET009
GET009
GET009
GET009
GET012
GET012
GET012
GET012
GET015
GET015
GET015
GET015
GET018
GET018
GET018
GET018
GET024
GET024
GET024
GET024
GET036
GET036
GET036
GET036
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
208/60/1
220-240/50/1
230/60/1
265/60/1
208/60/1
220-240/50/1
230/60/1
265/60/1
208/60/1
220-240/50/1
230/60/1
265/60/1
208/60/1
220-240/50/1
230/60/1
265/60/1
208/60/1
220-240/50/1
230/60/1
265/60/1
208/60/1
4.0
3.6
4.0
3.6
5.7
4.9
5.7
4.9
6.1
5.4
6.1
5.4
9.3
7.4
9.3
7.4
13.1
11.7
13.1
11.7
19.3
16.4
19.3
16.4
3.4
3.1
3.4
3.1
5.0
4.3
5.0
4.3
5.4
4.8
5.4
4.8
7.6
6.3
7.6
6.3
10.9
9.9
22.2
18.8
22.2
18.8
27.9
22.2
27.9
22.2
29.0
27.0
29.0
27.0
45.0
32.0
45.0
32.0
56.0
55.0
56.0
55.0
82.0
64.0
82.0
64.0
0.6
0.5
0.6
0.5
0.7
0.6
0.7
0.6
0.7
0.6
0.7
0.6
1.7
1.1
1.7
1.1
2.2
1.8
2.2
1.8
3.3
2.8
3.3
2.8
1/10
1/10
1/10
1/10
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/5
1/5
1/5
1/5
1/5
1/5
1/5
1/5
1/2
1/2
1/2
1/2
4.9
4.4
4.9
4.4
6.9
6.0
6.9
6.0
7.5
6.6
7.5
6.6
11.2
9.0
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
25
20
25
20
35
30
35
30
11.2
9.0
15.8
14.2
15.8
14.2
23.3
19.8
23.3
19.8
10.9
9.9
16.0
13.6
16.0
13.6
220-240/50/1
230/60/1
265/60/1
18
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Pre-Start
Checklist
Pre-Start-up Checklist
Before energizing the unit, the following system devices must be checked:
____ Is the high voltage power supply correct and in accordance with the nameplate ratings?
____ Is the field wiring and circuit protection the correct size?
____ Is the low voltage control circuit wiring correct per the unit wiring diagram?
____ Is the piping system clean/complete and correct? (A recommendation of all system flushing of debris from
the water-to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger
be done in accordance with the Closed-Loop/Ground Source Heat Pump Systems Installation Guide).
____ Is vibration isolation provided? (i.e. unit isolation pad, hose kits)
____ Is unit serviceable? (See clearance specifications on page 6).
____ Are the low/high-side pressure temperature caps secure and in place?
____ Are all the unit access panels secure and in place?
____ Is the thermostat in the OFF position?
____ Is the water flow established and circulating through all the units?
____ Is the duct work (if required) correctly sized, run, taped, insulated and weather proofed with proper unit
arrangement?
____ Is the condensate line properly sized, run, trapped and pitched?
____ Does the indoor blower turn freely without rubbing?
____ Has all work been done in accordance with applicable local and national codes?
____ Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?
____ Are the compressor bolts removed from the chassis?
____ Have the chassis isolation rails been released?
____ Is there a good seal between the front air panel and the coil?
WSHP-SVN08B-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Sequence
of Operation
Initial Unit Start-up
Start-up with deluxe controls is included below:
TM
Note: Start-up for the Tracer
ZN510 controller may be found in WSHP-IOP-2.
!
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with
live electrical components. Have a qualified licensed electrician or other individual who has been properly
trained in handling live electrical components perform these tasks. Failure to follow all electrical safety pre-
cautions when exposed to live electrical components could result in death or serious injury.
1.
2.
3.
Set the thermostat to the highest position.
Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
Reduce the temperature control setting until the compressor, reversing valve, solenoid valve, and loop
pump are energized. Adjust water flow utilizing pressure/temperature plugs and comparing to tables con-
tained in specification sheet data. Water leaving the heat exchanger should be warmer than the entering
water temperature (approximately 9°F-12°F); blower operation should be smooth; compressor and blower
amps should be within data plate ratings; the suction line should be cool with no frost observed in the
refrigerant circuit.
4.
5.
Check the cooling refrigerant pressures against values in Table OP1. (Page 21).
Turn the thermostat switch to the OFF position. Unit should stop running and the reversing valve should
de-energize.
6.
7.
Leave unit off for approximately FIVE minutes to allow for pressure equalization.
Turn the thermostat to the lowest setting.
8.
9.
Set the thermostat system switch to the HEAT position.
Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register.
A water temperature decrease of approximately 5°F-9°F leaving the heat exchanger should be noted. The
blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures against values in Table OP1. (Page 21)
11. Set the thermostat to maintain the desired space temperature.
12. Instruct the owner on system operation.
20
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Pressures
Table OP-1: Operating Pressures
GENERAL: There are many variables (airflow, air temperatures) in an air conditioning system that will affect operating re-
frigerant pressures and temperatures. The chart below shows approximate conditions and is based on air flow at the rated
SCFM, entering air at 80.6 °FDB, 66.2 °FWB in cooling, 68 °FDB in heating. (+)Heating data with 35 °F EWT is based on the
use of an anti-freeze solution having a freezing point 20 °F lower than the minimum expected entering temperature.
Operating Data
Cooling
Heating
Entering
Water
Water
Flow
GPM
Suction
Discharge
Water
Temp
Rise, °F
Air Temp
Drop,
Suction
Discharge
Water
Temp
Drop, °F
Air Temp
Rise,
°FDB
Model
Pressure, Pressure,
Pressure, Pressure,
Temp, °F
PSIG
PSIG
°FDB
PSIG
46 - 52
46 - 53
55 - 63
56 - 65
65 - 75
66 - 76
78 - 90
79 - 91
85 - 98
87 - 100
96 - 110
98 - 113
PSIG
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 009
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 012
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
GET 015
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
1.8
2.25
1.8
2.25
1.8
2.25
1.8
2.25
1.8
2.25
1.8
2.25
1.8
2.25
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
2.8
3.5
158 - 201
159 - 203
171 - 218
172 - 219
182 - 231
183 - 233
193 - 246
195 - 248
201 - 256
202 - 257
208 - 265
209 - 266
5 - 6
4 - 5
11 - 15
12 - 15
13 - 17
14 - 18
15 - 19
16 - 20
18 - 22
18 - 23
19 - 24
19 - 25
21 - 26
21 - 27
68 - 78
68 - 78
70 - 80
70 - 80
73 - 84
73 - 84
75 - 86
74 - 86
77 - 88
76 - 88
78 - 90
78 - 90
100 - 127
97 - 123
11 - 14
9 - 11
11 - 15
12 - 15
11 - 14
12 - 15
11 - 14
12 - 15
11 - 14
11 - 15
11 - 14
11 - 15
11 - 14
11 - 14
6 - 7
5 - 6
117 - 148
113 - 144
142 - 180
138 - 176
157 - 199
153 - 195
183 - 233
179 - 227
206 - 262
202 - 257
11 - 14
9 - 11
7 - 9
6 - 7
10 - 13
9 - 11
8 - 10
7 - 9
10 - 13
8 - 11
9 - 11
7 - 9
10 - 13
8 - 11
10 - 13
8 - 10
10 - 13
8 - 10
44 - 50
45 - 51
54 - 62
55 - 63
64 - 74
65 - 75
75 - 86
76 - 87
79 - 90
79 - 91
84 - 96
85 - 97
160 - 204
162 - 206
170 - 217
172 - 219
181 - 230
182 - 232
192 - 245
194 - 247
196 - 250
198 - 252
203 - 258
204 - 260
5 - 6
4 - 5
5 - 7
4 - 6
6 - 8
5 - 7
7 - 9
6 - 8
8 - 10
6 - 8
8 - 11
7 - 9
19 - 24
19 - 24
21 - 27
22 - 27
24 - 31
25 - 31
27 - 35
28 - 36
29 - 37
29 - 37
30 - 39
31 - 39
68 - 78
67 - 77
72 - 83
71 - 82
74 - 86
74 - 85
76 - 87
75 - 86
77 - 89
77 - 88
79 - 91
78 - 90
106 - 135
102 - 130
124 - 158
120 - 153
152 - 193
147 - 187
168 - 213
163 - 207
195 - 248
190 - 242
219 - 279
214 - 273
10 - 13
9 - 11
10 - 13
9 - 11
10 - 13
8 - 11
10 - 13
8 - 10
10 - 12
8 - 10
9 - 12
8 - 10
18 - 23
19 - 24
18 - 23
18 - 23
17 - 22
18 - 23
17 - 21
17 - 22
16 - 20
16 - 21
15 - 19
15 - 19
42 - 49
44 - 51
51 - 59
53 - 61
61 - 70
63 - 72
75 - 87
77 - 89
83 - 95
84 - 97
92 - 106
94 - 108
161 - 204
163 - 208
171 - 217
174 - 221
181 - 231
184 - 234
195 - 249
198 - 252
203 - 258
205 - 261
211 - 269
214 - 272
5 - 7
4 - 6
16 - 20
16 - 20
18 - 23
19 - 24
21 - 26
21 - 27
24 - 31
25 - 31
26 - 33
26 - 34
28 - 36
29 - 37
71 - 81
71 - 81
73 - 84
73 - 84
75 - 86
74 - 86
75 - 86
75 - 86
76 - 87
76 - 87
77 - 88
77 - 88
100 - 127
97 - 124
12 - 15
10 - 12
12 - 15
10 - 12
12 - 15
10 - 12
12 - 15
10 - 12
12 - 15
9 - 12
16 - 20
16 - 21
16 - 20
16 - 20
15 - 20
16 - 20
15 - 19
15 - 19
14 - 18
15 - 19
14 - 18
14 - 18
6 - 8
5 - 7
116 - 147
112 - 143
141 - 179
137 - 174
156 - 199
152 - 194
184 - 234
179 - 228
208 - 265
203 - 258
8 - 10
6 - 8
9 - 12
7 - 9
10 - 13
8 - 10
11 - 14
9 - 12
11 - 14
9 - 12
WSHP-SVN08B-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Pressure
Table OP-1: Operating Pressures
Operating Data
Cooling
Heating
Entering
Water
Water
Flow
GPM
Suction
Pressure, Pressure,
Discharge
Water
Temp
Air Temp
Drop,
Suction
Discharge
Water
Temp
Air Temp
Rise,
Model
Pressure, Pressure,
Temp, °F
PSIG
PSIG
Rise, °F
°FDB
PSIG
41 - 47
42 - 49
50 - 58
52 - 60
60 - 69
62 - 71
73 - 84
75 - 86
80 - 92
82 - 94
90 - 103
92 - 106
PSIG
Drop, °F
°FDB
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 018
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 024
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
GET 036
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
35
35
45
45
55
55
68
68
75
75
86
86
95
95
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6.0
4.8
6
164 - 209
166 - 211
174 - 222
176 - 224
184 - 235
186 - 237
198 - 252
200 - 254
205 - 260
207 - 263
215 - 274
217 - 277
5 - 6
4 - 5
6 - 7
5 - 6
7 - 8
5 - 7
8 - 10
6 - 8
8 - 11
7 - 9
9 - 12
8 - 10
16 - 20
16 - 21
18 - 23
18 - 23
20 - 26
21 - 26
23 - 30
24 - 30
25 - 32
25 - 32
27 - 34
28 - 35
69 - 79
68 - 78
71 - 82
71 - 81
73 - 84
73 - 84
74 - 86
74 - 85
76 - 87
76 - 87
77 - 89
77 - 88
110 - 139
106 - 134
128 - 163
123 - 157
155 - 198
151 - 192
172 - 219
167 - 212
201 - 256
195 - 249
227 - 289
221 - 281
12 - 15
9 - 12
17 - 21
17 - 22
16 - 21
17 - 21
16 - 20
16 - 21
16 - 20
16 - 20
15 - 19
15 - 19
14 - 18
15 - 19
12 - 15
9 - 12
11 - 15
9 - 12
11 - 14
9 - 12
11 - 14
9 - 12
11 - 14
9 - 11
41 - 48
42 - 49
51 - 58
52 - 59
59 - 68
61 - 70
70 - 81
72 - 82
75 - 87
77 - 89
83 - 96
85 - 98
163 - 207
164 - 209
175 - 223
177 - 225
187 - 238
189 - 240
202 - 257
204 - 259
209 - 266
211 - 269
220 - 280
222 - 283
5 - 7
4 - 6
18 - 22
18 - 23
21 - 26
21 - 27
24 - 30
24 - 31
27 - 34
28 - 35
29 - 37
29 - 37
31 - 39
32 - 40
64 - 74
63 - 73
67 - 78
67 - 77
71 - 82
70 - 81
72 - 83
72 - 83
75 - 86
74 - 85
76 - 88
76 - 88
108 - 138
104 - 133
125 - 159
121 - 154
151 - 193
147 - 187
167 - 213
162 - 207
195 - 249
190 - 241
221 - 281
215 - 273
12 - 16
10 - 13
12 - 16
10 - 13
12 - 16
10 - 13
12 - 15
10 - 12
12 - 15
10 - 12
11 - 15
9 - 12
17 - 22
17 - 22
17 - 22
17 - 22
16 - 21
17 - 21
16 - 20
16 - 21
15 - 20
16 - 20
15 - 19
15 - 19
6 - 8
5 - 7
7 - 10
6 - 8
9 - 11
7 - 9
9 - 12
8 - 10
10 - 13
8 - 11
7.2
9.0
7.2
9.0
7.2
9.0
7.2
9.0
7.2
9.0
7.2
9.0
7.2
9
40 - 46
41 - 48
49 - 57
51 - 58
58 - 67
59 - 68
71 - 82
72 - 83
78 - 89
79 - 91
82 - 94
83 - 95
155 - 198
157 - 200
167 - 212
168 - 214
177 - 226
179 - 228
192 - 244
194 - 246
200 - 254
202 - 257
206 - 263
208 - 265
4 - 6
4 - 5
6 - 7
5 - 6
7 - 9
5 - 7
8 - 10
7 - 8
9 - 11
7 - 9
9 - 12
7 - 9
17 - 22
17 - 22
20 - 26
21 - 26
23 - 30
24 - 30
27 - 35
28 - 35
29 - 37
29 - 37
30 - 39
31 - 39
63 - 72
61 - 71
67 - 77
66 - 76
71 - 82
71 - 82
73 - 84
73 - 84
75 - 86
75 - 86
76 - 88
76 - 87
113 - 144
109 - 139
129 - 164
124 - 158
155 - 197
149 - 189
170 - 217
164 - 209
198 - 252
191 - 243
224 - 285
216 - 275
12 - 15
9 - 12
20 - 26
20 - 26
20 - 26
20 - 26
20 - 25
20 - 25
19 - 24
19 - 25
18 - 23
19 - 24
18 - 23
18 - 23
12 - 15
10 - 12
12 - 15
9 - 12
11 - 15
9 - 12
11 - 14
9 - 11
11 - 14
9 - 11
22
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Pressures
Water Pressure Drop
Table 7 should be used to define feet of head/pressure drop. Note: To calculate feet of head, when using gauges that read
in PSIG, multiply PSI by 2.31.
Table 7: Water pressure drops (WPD) in feet of head
Cooling
Ft. Head
Heating
Ft. Head
Unit Size
GPM
EWT
F
EWT
F
Pressure
5.1
Pressure
5.8
10.6
14.0
8.5
16.6
22.0
7.4
14.1
18.8
3.1
5.9
7.7
6.2
11.8
14.5
5.5
11.0
14.7
1.5
2.3
2.7
2.5
3.1
3.7
2.3
3.5
4.2
2.9
4.5
5.4
3.9
6.0
7.2
5.9
9.0
10.8
009
012
015
018
024
036
77
77
77
77
77
77
9.3
55
55
55
55
55
55
12.4
10.2
14.6
19.6
6.2
12.3
16.8
2.4
4.9
6.6
5.0
9.9
13.2
4.9
9.8
13.3
Water Volume
Table 8 is provided for use in calculating glycol requirements for the unit.
Table 8: Water volume
Unit
Model
GET
Water Side
Volume
Cubic In.
Water Side
Volume
Cubic Ft.
Water Side
Volume
Gallons
009
012
015
018
024
036
17.0
17.0
36.0
48.0
55.0
71.0
0.010
0.010
0.021
0.028
0.032
0.041
0.074
0.074
0.156
0.208
0.238
0.307
Flow Checks
For the operating temperature drop (heating) and rise (cooling), refer to Table OP1 and OP2 for the proper water tempera-
ture change. Depending on the unit size, entering water temperature and water flow rate, the cooling temperature rise is
from 8°F-16°F. Based on the same criteria for heating, the temperature drop is from 2°F-13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with the P/T port adapter, measure the pressure difference between
the water-in and water-out connections. Compare the pressure differential to Table 6 to determine flow.
Start-up Checklist and Log
Use the form on page 24 to log system and unit temperatures during start-up.
!
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with
live electrical components. Have a qualified licensed electrician or other individual who has been properly
trained in handling live electrical components perform these tasks. Failure to follow all electrical safety pre-
cautions when exposed to live electrical components could result in death or serious injury.
WSHP-SVN08B-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-up Checklist
and Log
Installing Contractor: Use this form to thoroughly check-out the system and units before and during start-
up. (This form need not be returned to the factory unless requested during technical service support).
Job Name:
Model Number:
Date:
Serial Number:
In order to minimize troubleshooting and costly system failures, complete the following checks and data
entries before the system is put into full operation.
MODE
HEAT
COOL
Entering fluid temperature
Leaving fluid temperature
Temperature differential
F
F
F
F
Return-air temperature DB/WB
Supply-air temperature DB/WB
Temperature differential
F
F
F
F
F
F
F
F
Water coil heat exchanger
(Water Pressure IN)
Water coil heat exchanger
(Water Pressure OUT)
PSIG
PSIG
Pressure Differential
PSIG
PSIG
PSIG
PSIG
COMPRESSOR
Amps
Volts
Discharge line temperature
(after 10 minutes)
F
F
24
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
should be performed by an experi-
enced service person.
Preventive Maintenance
Maintenance on the unit is simplified
with the following preventive sugges-
tions:
! WARNING
Hazardous
Chemicals!
Filter maintenance must be performed
to assure proper operation of the
equipment. Filters should be inspect-
ed at least every three months, and re-
placed when it is evident they are
dirty. Filter sizing includes:
Coil cleaning agents can be either
acidic or highly alkaline. Handle
chemical carefully. Proper han-
dling should include goggles or
face shield, chemical resistant
gloves, boots, apron or suit as re-
quired. For personal safety, refer
to the cleaning agent manufactur-
ers Materials Safety Data Sheet
and follow all recommended safe
handling practices. Failure to fol-
low all safety instructions could
result in death or serious injury.
Model GET
009, 012
015
Filter Size (nominal)
14 x 20 (356 x 508)
18 x 20 (457 x 508)
18 x 25 (457 x 635)
20 x 30 (508 x 762)
018
024, 036
!
WARNING
Hazardous
Voltage!
It should be noted that the water qual-
ity should be checked periodically. See
Table 9.
Disconnect all electric power, in-
cluding remote disconnects and
discharge motor start/run capaci-
tors before servicing. Follow prop-
er lockout/tagout procedures to
ensure the power can not be inad-
vertently energized. Failure to dis-
connect power before servicing
could result in death or serious in-
jury.
Table 9: Water Quality Table
Scaling
Calcium and magne-
Less than 350
sium (total hardness) ppm
Corrosion
pH
7-9.5
Hydrogen Sulfide
Sulfates
Less than 1 ppm
Less than 25 ppm
Check the contactors and relays within
the control panel at least once a year.
It is good practice to check the tight-
ness of the various wiring connections
within the control panel.
Less than 125
ppm
Chlorides
Carbon Dioxide
Less than 75 ppm
Total dissolved solids
(TDS)
Less than 1000
ppm
A strainer (60 mesh or greater) must
be used on an open loop system to
keep debris from entering the unit heat
exchanger and to ensure a clean sys-
tem.
Biological Growth
Iron Bacteria
Erosion
Low
Low
Suspended Solids
For units on well water, it is important
to check the cleanliness of the water-
to-refrigerant heat exchanger. Should
it become contaminated with dirt and
scaling as a result of bad water, the
heat exchanger will have to be back
flushed and cleaned with a chemical
that will remove the scale. This service
WSHP-SVN08B-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
Information
Warranty Information
Standard Warranty
The standard water-source heat pump warranty is Trane’s parts-only warranty, running 12-months from star-
tup, not to exceed 18-months from shipment.
Extended Warranty
The optional extended warranty is a second through fifth year warranty. The time starts at the end of standard
1-year coverage through the fifth year.
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems
Group sales territories and must be ordered prior to start-up.
26
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
General Operation
!
WARNING
The standard model is designed for in-
door installation. When the unit is in-
stalled in an unconditioned space, the
unit may not start in cool weather (ap-
proximately 45°F). It may then be nec-
essary to start the unit in the cooling
mode for three to five minutes. The
unit may then be shut-off (there will be
a two minute time-out of the unit), and
restarted in the heating mode. The
freeze protection thermostat should
also be checked as it may be adversely
affected by ambient temperature.
Like any other type of mechanical
equipment, the unit performs best
when it is well maintained.
Hazardous Service
Procedures!
The maintenance and trouble
shooting procedures recommend-
ed in this section of the manual
could result in exposure to electri-
cal, mechanical or other potential
safety hazards. Always refer to
the safety warnings provided
throughout this manual concern-
ing these procedures. When possi-
ble, disconnect all electrical
power including remote discon-
nects before servicing. Follow
proper lockout/tagout procedures
to ensure the power can not be in-
advertently energized. When nec-
essary to work with live electrical
components, have a qualified li-
censed electrician or other indi-
vidual who has been trained in
handling live electrical compo-
nents per these tasks. Failure to
follow all of the recommended
safety warnings provided, could
result in death or serious injury.
Operation with a Conventional
Thermostat
The unit is equipped with safety con-
trols, including high pressure control,
low pressure control and a freeze pro-
tection thermostat, set to shut off the
compressor under abnormal tempera-
ture or pressure conditions. If the safe-
ties shut off the compressor, a lockout
relay prevents short cycling from the
abnormal condition. When conditions
are corrected, the lockout control can
be reset by setting the thermostat sys-
tem switch to OFF wait a few minutes
for the system pressure to equalize,
and then return to HEAT or COOL. If
the condition continues, an authorized
service person should check out the
unit.
Preliminary Trouble Inspection
If operational difficulties are encoun-
tered, be sure to perform the prelimi-
nary checks before referring to the
troubleshooting chart on page 28.
• Verify that the unit is receiving elec-
tric supply power.
• Ensure that the fuses in the fused
disconnect are intact.
After completing the preliminary
checks, inspect the unit for other obvi-
ous problems such as leaking connec-
tion, broken or disconnected wires,
etc. If everything appears to be in or-
der, but the unit still fails to operate
properly, refer to the troubleshooting
chart on page 28.
WSHP-SVN08B-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Checklist
Problem
Heating Cooling Cause
Correction
Check fuses
Replace
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Main power off
Defective control transformer
Broken or loose connection
Defective thermostat
No response to any
thermostat setting
Repair
Replace
Transformer
Reset Transformer
Relocate
Unit short cycles
Thermostat or sensor improperly located
Defective compressor overload
Defective compressor contactor
Supply Voltage too low
Defective compressor capacitor
Defective windings
Replace (if external)
Replace
Blower runs, but compressor does not
Correct
Replace
Replace
Limit switches open
Check cause/Replace or repair
Replace/clean
Correct
Dirty filter
Blower RPM too low
Loss of conditioned air due to leaks in
ductwork
X
X
X
Repair leaks
Introduction of excessively hot return-air
Introduction of excessively cold return-air
Correct
Correct
X
X
Locate leak, repair and recharge by
weight (not by superheat)
X
Low on refrigerant charge
Insufficient capacity
X
X
X
X
X
X
X
X
X
X
X
X
X
Restricted thermal expansion valve
Defective reversing valve
Thermostat improperly located
Unit undersized
Replace
See WSHP-IOM-# for touch test chart
Relocate
Recalculate heat gains/losses
Increase GPM
Inadequate water flow
Scaling in heat exchanger
Water too hot
Clean or replace
Decrease temperature
Increase temperature
Increase water flow to unit
Decrease temperature
Check, clean blower and coil
Clean/replace
X
Water too cold
X
X
Inadequate GPM
Water too hot
X
X
X
X
Inadequate air flow
Dirty filter
High pressure switch open
X
X
X
X
X
X
X
Overcharged with refrigerant
Defective pressure switch
Trash in heat exchanger
Low water flow
Decrease charge
Check or replace
Backflush
Increase GPM
X
X
X
X
X
X
X
Overcharge of refrigerant
Non-condensable in system
Water too hot
Decrease charge
High head pressure
Evacuate and recharge by weight
Decrease temperature
Clean / replace
Dirty filter
Inadequate air flow
Undercharged
Check, clean blower and coil
Locate leak, repair and recharge
Repair / replace
X
X
X
X
Restricted thermal expansion valve
Inadequate air flow
Dirty filter
Low suction pressure
Check, clean blower and coil
Clean/replace
X
Inadequate GPM
Increase GPM
28
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
Retrofit Diagram
208/230V-50/60 Hz-1PH
L1
L2
1
AVERTISSEMENT
WARNING
HAZARDOUS VOLTAGE!
VOLTAGE HASARDEUX!
2
1PB1
1S2
DISCONNECT ALL ELECTRIC POWER DECONNECTEZ TOUTES LES SOURCES
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
ELECTRIQUES INCLUANT LES
3
DISJONCTEURS SITUES
A
DISTANCE
AVANT D'EFFECTUER L'ENTRETIEN.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR
DEATH.
3F
3B1C2
1A
2A
FAUTE DE DECONNECTER LA SOURCE
ELECTRIQUE AVANT D'EFFECTUER
L'ENTRETIEN PEUT ENTRAINER DES
BLESSURES CORPORELLES SEVERES
OU LA MORT.
4
7
(BR)
2A
**
1B
5
2B
(G)
6
(W)
IMPORTANT
3B1
USE COPPER CONDUCTORS ONLY TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT ANY OTHER WIRING.
7
6
1FU1
8
8
6
INSET "C"
1C,D
E
2 C,D
E
9
HORIZONTAL DISCHARGE
5
1K1
SIZE
009-013
019
1F
10A
CAP
6A,B
6A
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
2C
2X
J1-1 P1-1
R/T3
S/T2
RED (LO)
RED (LO)
RED (LO)
BK (HI)
BK (HI)
BK (HI)
BL (MED)
NONE
2B1C1
B
5A
4A
5
2B1
026
BL (MED)
1K1
1C
1X
J1-5 P1-5
TOP DISCHARGE
L1 T1
C/T1
SIZE
009-013
019
1F
10A
CAP
BL (MED)
BL (MED)
BK
BK (HI)
BK (HI)
BL (MED)
RED (LO)
RED (LO)
RED (LO)
6
1D
2D
1F
8A
026
J2-3 P2-3
9A
1K4
2F
3B1C2
A,B(Y)
J2-2 P2-2
2
4
(G)
9B(Y)
6
265V
3B1
1TB2
5
77A
78A
1T1
N
4
(R)
10B
10A
1K11
J2-1 P2-1
6
N
1E
(O)
2E
(BK)
INSET "B"
4
1T1
16A(BL)
B
1K11
1K10
15B
15C
1K10
C1 C2
15D
16G
1K4
19A
F,G
1
3
C
1K3
20B
29A,B
J1-6 P1-6
C2
C1
20C
D
1K1
1K3
4S3
4S1
C2
C1
27A
28A
29A
D,E
29B
3
6
5
1
1S1
4L1
B
E
J1-3 P1-3
15A
19A
20A
22A
ADD JUMPER
BETWEEN
Y & W.
G
Y
R
W
O
SINGLE
STAGE
ROOM
T'STAT
B
LEGEND
DESCRIPTION
DEVICE PREFIX LOCATION CODE
LOCATION
DEVICE
DESIGNATION
LINE
AREA
NUMBER
1
2
3
4
5
CONTROL PANEL
COMPRESSOR
1FU1
1K1
1K3
1K4
FUSE BLOCK
6,7,8
11,13,32
30,31
17,27
25,26
25
COMPRESSOR CONTACTOR
LOCKOUT RELAY
BLOWER MOTOR
UNIT MTD
BLOWER MOTOR RELAY
CUSTOMER PROVIDED
1K10
RELAY, RANDOM START (OPT)
1K11
1S1
RELAY, NIGHT SETBACK (OPT)
RELAY, TIME DELAY (OPTIONAL)
DISCONNECT SWITCH
32
1S2
3,4,5
2,19
1TB2
1T1
1PB1
TERMINAL BOARD
NOTES:
23
TRANSFORMER 24V
POWER BLOCK
SHOWN AT 25°
C
(77° F), AT ATMOSPHERIC
1
2
UNLESS OTHERWISE NOTED, ALL SWITCHES ARE
PRESSURE, AT 50% RELATIVE HUMIDITY, WITH
NORMAL SHUTDOWN HAS OCCURRED.
11
11
2B1
COMPRESSOR MOTOR
COMPRESSOR CAPACITOR
ALL UTILITIES TURNED OFF, AND AFTER
A
2B1C1
DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
3B1
BLOWER MOTOR
18
17
AND/OR DASHED DEVICE OUTLINES INDICATECOMPONENTS PROVIDED BY THE FIELD. PHANTOM
LINE ENCLOSURES INDICATE ALTERNATE
INDICATE WIRING BY TRANE CO.
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINES
3B1C2
BLOWER MOTOR CAPACITOR
NUMBERS ALONG THE RIGHT SIDE OF THE
SCHEMATIC DESIGNATE THE LOCATION OF
CONTACTS
3
36
31
4L1
4S1
4S3
REVERSING VALVE
BY LINE NUMBER. AN UNDERLINED
CONTACT. AN
NUMBER INDICATES
A
NORMALLY CLOSED
FREEZE PROTECTION SWITCH
HIGH PRESSURE SWITCH
AN OPEN ARROWHEAD BELOW THELINE NUMBER POINTING UPWARD INDICATES A TIMED
CONTACT WHICH BEGINS TIMING WHENENERGIZED.
31
TRANSFORMER SHOWN IS WIRED FOR 230V, RED LEAD IS FOR 208V.
SEE INSET "B" FOR 265V TRANSFORMER.
4
208/230 WPRD SIZE 009
5
6
FAN SPEED WIRING
OPTIONAL DISCONNECT SWITCH.
7
8
OPTIONAL DISCONNECT SWITCH AND FUSE BLOCK.
WSHP-SVN08B-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
Deluxe Diagram
208V-50/60 Hz-1PH
30
WSHP-SVN08B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Wiring
ZN510 Diagram
230V-50/60 Hz-1PH
WSHP-SVN08B-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
WSHP-SVN08B-EN
SV-UN-WSHP-SVN08B-EN-0206
SV-UN-WSHP-SVN08A-EN-1105
Inland
Supersedes
Trane
Stocking Location
A business of American Standard Companies
Trane has a policy of continuous product and data improvement and reserves the right to change
design and specifications without notice.
For more information, contact your local district
office or e-mail us at [email protected]
Download from Www.Somanuals.com. All Manuals Search And Download.
|