Trane Air Conditioner 3RT PRC005 EN User Manual

Packaged Cooling with  
Electric Heat Rooftop Units  
Precedent™  
3 - 10Tons — 60 Hz  
RT-PRC005-EN  
August 2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction  
2
4
Features and Benefits  
Application Considerations  
11  
Selection Procedure  
Model Number Description  
General Data  
12  
14  
15  
Performance Data  
19  
19  
37  
59  
Cooling Performance  
Fan Performance  
Heating Performance  
Controls  
62  
64  
78  
87  
Electric Power  
Dimension andWeights  
Mechanical Specifications  
RT-PRC005-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Factory Installed Options  
• Black Epoxy Pre-Coated Coils  
Dehumidification Option  
• High Pressure Cutout  
• Hinged Access Doors  
• Novar Return Air Sensor  
• Novar Unit Controls  
Field Installed Options  
CO2 Sensing  
Digital Display Zone Sensor  
DualThermistor Remote Zone Sensor  
High Static Drive  
Humidity Sensor  
Manual Outside Air Damper  
Motorized Outside Air Dampers  
Powered Exhaust  
• Phase Monitor  
• Powered or Unpowered Convenience  
Outlet  
• Supply and/or Return Air Smoke  
Detector  
Remote Potentiometer  
Roof Curb  
Thermostat  
• Thermal ExpansionValve  
• Through the Base Electrical Access  
• Through the Base ElectricalWith Circuit  
Breaker  
Ventilation Override Accessory  
Zone Sensor  
• Through the Base ElectricalWith  
Disconnect Switch  
Two-Inch Pleated Filters  
Factory or Field Installed Options  
Clogged Filter/Fan Failure Switch  
Differential Pressure Switches  
Discharge Air Sensing Kit  
Economizer  
Electric Heaters  
Frostat  
LonTalk® Communications Interface  
Oversized Motors  
Reference or Comparative Enthalpy  
Tool-less Hail Guards  
Trane Communications Interface (TCI)  
4
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Precedent with ReliaTel reduces the  
number of components required to  
operate the unit, thereby reducing  
possibilities for component failure.  
Some zone sensor options have central  
control panel lights which indicate the  
mode the unit is in and possible  
diagnostic information (dirty filters for  
example).  
Easy to Install, Service and  
Maintain  
Because todays owners are very cost-  
conscious when it comes to service and  
maintenance, theTrane Precedent was  
designed with direct input from service  
contractors.This valuable information  
helped to design a product that would get  
the serviceman off the job quicker and  
save the owner money. Precedent does  
this by offering:  
ReliaTel Makes Installing and  
Servicing Easy  
Other ReliaTel Benefits  
ReliaTel eliminates the need for field  
installed anti-shortcycle timer and time  
delay relays. ReliaTel controls provide  
these functions as an integral part of the  
unit.The contractor no longer has to  
purchase these controls as options and  
pay to install them.  
The ReliaTel built-in anti-shortcycle timer,  
time delay relay and minimum “on” time  
control functions are factory tested to  
assure proper operation.  
ReliaTel softens electrical “spikes” by  
staging on fans, compressors and  
heaters.  
Quality and Reliability  
ReliaTel™ Controls (LCI-R)  
The wiring of the low voltage connections  
to the unit and the zone sensors is as  
easy as 1-1, 2-2, and 3-3.This simplified  
system makes wiring easier for the  
installer.  
Intelligent Fallback is a benefit to the  
building occupant. If a component goes  
astray, the unit will continue to operate at  
predetermined temperature setpoint.  
Intelligent Anticipation is a standard  
ReliaTel feature. It functions continuously  
as ReliaTel and zone sensor(s) work  
together in harmony to provide much  
tighter comfort control than conventional  
electro-mechanical thermostats.  
ReliaTel MakesTesting Easy  
ReliaTel requires no special tools to run  
the Precedent unit through its paces.  
Simply place a jumper betweenTest 1  
andTest 2 terminals on the LowVoltage  
Terminal Board and the unit will walk  
through its operational steps  
automatically.  
The same ReliaTel Board fits all  
Precedent Packaged Gas/Electrics,  
Cooling with Electric Heat, and Heat  
Pump models.This provides  
standardization of parts for contractors.  
Less money is tied up in inventory with  
ReliaTel.  
ReliaTel controls provide unit control for  
heating, cooling and ventilating utilizing  
input from sensors that measure outdoor  
and indoor temperature.  
—The unit automatically returns  
control to the zone sensor after  
stepping through the test mode a  
single time, even if the jumper is  
left on the unit.  
Quality and Reliability are enhanced  
through ReliaTel control and logic:  
Electromechanical Controls  
As long as the unit has power and the  
“system on” LED is lit, ReliaTel is  
operational.The light indicates that the  
controls are functioning properly.  
—prevents the unit from short cycling,  
considerably improving  
compressor life.  
For the simpler job that does not require  
a building automation system, or  
expanded diagnostics capabilities,  
Precedent offers electromechnical  
controls. This 24-volt control includes the  
control transformer and contactor  
pressure lugs for power wiring.  
—ensures that the compressor will run  
for a specific amount of time which  
allows oil to return for better  
lubrication, enhancing the reliability of  
the compressor.  
ReliaTel features expanded diagnostic  
capabilities when utilized withTrane  
Integrated Comfort™ Systems.  
ReliaTel™  
RT-PRC005-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Compressors  
Dehumidification (Hot Gas Reheat)  
Option  
Outstanding Standard and  
Optional Components  
Precedent contains the best compressor  
technology available to achieve the  
highest possible performance. Our  
compressor line includesTrane built  
ClimaTuff® reciprocating and scrolls.  
This option allows for increased outdoor  
air ventilation. It reduces humidity levels  
while increasing comfort level in the air  
space. Cooling can operate without a  
demand for dehumidification.The hot gas  
reheat coil is designed to deliver  
maximum reheat temperatures and  
pivot to allow for easy access cleaning.  
Black Epoxy Pre-Coated Coils  
Provides corrosion protection to  
condenser coils for seacoast application.  
Cabinet Integrity  
For added water integrity, Precedent has  
a raised 11/8" lip around the supply and  
return of the downflow units to prevent  
water from blowing into the ductwork.  
Clogged Filter/Fan Failure Switch  
A dedicated differential pressure switch is  
available to achieve active fan failure  
indication and/or clogged filter indication.  
These sensors allow a zone sensor  
service light or Integrated Comfort  
System to indicate a dirty filter or a fan  
thats not working.The field installation  
charges for these valuable feedback  
devices often eliminate them from  
consideration. Factory installation can  
make such features a good investment.  
Condenser Coil  
Precedent boasts a patent-pending  
1+1+1 condenser coil, permanently  
gapped for easy cleaning.  
Digital Display Zone Sensor  
CO2 Sensing  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone sensors. This sensor  
should be utilized with ReliaTel™ controls.  
The CO2 sensor has the ability to monitor  
space occupancy levels within the  
building by measuring the parts per  
million of CO2 (Carbon Dioxide) in the air.  
As the CO2 levels increase, the outside air  
damper modulates to meet the CO2  
space ventilation requirements.The CO  
sensor kit is available as a field installed2  
accessory.  
Discharge Air Sensing Kit  
Provides true discharge air sensing in  
heating models. The kit is functional only  
with the ReliaTel Options Module.  
DownflowAnd Horizontal Economizers  
The economizers come with three control  
options — dry bulb is standard, enthalpy  
and differential enthalpy are optional.  
ColoredAnd NumberedWiring  
Save time and money tracing wires and  
diagnosing the unit.  
DualThermistor Remote Zone Sensor  
This sensor will reduce the total number  
of remote sensors to obtain space  
temperature averaging. This sensor  
should be utilized with ReliaTel controls.  
6
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Foil-Faced Insulation  
Phase Monitor  
Standardized Components  
All panels in the evaporator section of the  
unit have cleanable foil-faced insulation.  
All edges are either captured or sealed to  
ensure no fibers get into the airstream.  
Phase monitor shall provide 100%  
protection for motors and compressors  
against problems caused by phase loss,  
phase imbalance, and phase reversal.  
Phase monitor is equipped with an LED  
that provides an ON or FAULT indicator.  
Components are placed in the same  
location on all Precedent units. Familiarize  
yourself with one Precedent and you are  
familiar with every Precedent.  
Factory Built Roof Curbs  
Due to standardized components  
throughout the Precedent line,  
contractors/owners can stock fewer  
parts.  
Available for downflow units. Only two  
roof curbs for the entire Precedent line  
simplifies curb selection.  
Power Exhaust Option  
This option is available on downflow units  
and provides exhaust of the return air,  
when using a downflow economizer, to  
maintain proper building pressurization.  
Great for relieving most building  
overpressurization problems.  
Flexibility  
Supply and/or Return Air Smoke  
Detector  
Units are built to order in our standard  
“shortest in the industry” ship cycle time.  
With this option  
installed, if smoke is  
detected, all unit  
Fresh Air  
0 - 25% manual or 0 - 50% motorized  
outside air hoods are available.  
Quick-Access Panels  
operation will be shut  
down. Reset will be  
manual at the unit.  
Return Air Smoke  
Detectors require  
minimum allowable  
airflow when used  
with certain models.  
Remove two screws for access to the  
standardized internal components and  
wiring.  
High Pressure Cutout  
This factory-installed option is offered for  
units that do not have High Pressure  
Cutout as standard. All 3-phase units with  
scroll compressors include High Pressure  
cutout as standard.  
Quick-Adjust Idler Arm  
With the Quick-Adjust Idler Arm, the belt  
and sheaves can be quickly adjusted  
without moving the mounted fan motor.  
The result is a major savings in time and  
money.  
High Static Drive Accessory  
Thermal ExpansionValve  
Available for a wider range of  
applications.  
Available on many models, this high  
static drive accessory extends the  
capability of the standard motor. Avoid  
expensive motors and operating costs by  
installing this optimized sheave  
accessory.  
Tool-less Hail Guards  
Tool-less, hail protection quality coil  
guards shall be either factory or field-  
installed for condenser coil protection.  
This option protects the condenser coil  
from vandalism and/or hail damage.  
Hinged Access Doors  
These doors permit easy access to the  
filter, fan/heat,  
and compressor/  
control sections.  
They reduce the  
potential roof  
damage from  
screws or sharp  
access door  
Reference or Comparative Enthalpy  
Measures and communicates humidity  
while maximizing comfort control.  
corners.  
LonTalk®  
Sloped Drain Pans  
Every Precedent unit has a non-  
corrosive, removable, double-sloped  
drain pan that’s  
Communications  
Interface  
The LonTalk  
communica-  
easy to clean  
tions interface  
and reversible to  
allo w installation  
of drain trap on  
allows the unit to communicate as a  
Tracer™LCI-V device or directly with  
generic LonTalk Network Building  
Automation System Controls.  
Trane Communication Interface (TCI)  
Available factory or field installed.This  
module when applied with the ReliaTel™  
easily interfaces withTrane’s Integrated  
ComfortTM System.  
either side of the  
unit.  
RT-PRC005-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Unit Cabinet  
Ventilation Override Accessory  
Rigorous Testing  
All of Precedents designs were  
rigorously rain tested at the factory to  
ensure water integrity.  
The compact cabinet with rounded  
corners takes up less room and is less  
costly to ship. The beveled and ribbed top  
is not only aesthetically pleasing, it is  
designed to prevent water from pooling.  
With theVentilation Override Accessory  
installed, the unit can be set to transition  
to up to 3 different pre-programmed  
sequences for Smoke Purge,  
Pressurization, and Exhaust.The  
Actual shipping tests were performed to  
determine packaging requirements. Units  
were test shipped around the country to  
determine the best packaging. Factory  
shake and drop tests were used as part  
of the package design process to help  
assure that the unit arrives at the job site  
in top condition.  
transition occurs when a binary input on  
the RTOM is closed (shorted).This would  
typically be a hard wired relay output  
from a smoke detector or fire control  
panel.The ventilation override kit is  
available as a field installed accessory.  
Zone Sensors  
Available in programmable, automatic  
and manual styles.  
Rigging tests include lifting a unit into the  
air and letting it drop one foot, assuring  
that the lifting lugs and rails hold up under  
stress.  
Precedent offers ultimate flexibility. Units  
are built to order in our standard  
“shortest in the industry” ship cycle time.  
We perform a 100% coil leak test at the  
factory.The evaporator and condenser  
coils are leak tested at 200 psig and  
pressure tested to 450 psig.  
VariTrac  
All parts are inspected at the point of final  
assembly. Sub-standard parts are  
identified and rejected immediately.  
WhenTranes changeover VAV System  
for light commercial applications is  
coupled with Precedent, it provides the  
latest in technological advances for  
comfort management systems and can  
allow thermostat control in every zone  
served by VariTrac.  
Every unit receives a 100% unit run test  
before leaving the production line to  
make sure it lives up to rigorousTrane  
requirements.  
VariTrac™  
8
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
LowVoltage Connections  
Single Point Power  
A single electrical connection powers the  
unit.  
Easy to Install  
Convertible Units  
The wiring of the low voltage connections  
to the unit and the zone sensors is as  
simple as 1-1, 2-2, and 3-3.This simplified  
system makes it easy for the installer to  
wire.  
The units ship in a downflow  
configuration.They can be easily  
converted to horizontal by simply  
mUnoivtsincgotmweocpoamnepllse.te with horizontal  
duct flanges so the contractor doesn’t  
have to field fabricate them.These duct  
flanges are a time and cost saver.  
Single Side Service  
Single side service is standard on all  
units.  
Through the Base Condensate  
Every unit includes provisions for through  
the base condensate drain connections.  
This allows the drain to be connected  
through the roof curb instead of a roof  
penetration.  
Through the Base Electrical Utility  
Access  
Factory provided through the base  
openings simplify wiring and piping.  
Because these utility openings frequently  
minimize the number of roof  
penetrations, the integrity of roofing  
materials is enhanced.  
Electric Heaters  
Electric heat modules are available within  
the basic unit. If ordering theThrough the  
Base Electrical option with an Electrical  
Heater, the heater must be factory  
installed.  
Powered or Unpowered Convenience  
Outlet  
This option is a GFCI, 120v/15amp, 2 plug,  
convenience outlet, either powered or  
unpowered.This option can only be  
ordered when theThrough the Base  
Electrical with either the Disconnect  
Switch, or Circuit Breaker, option is  
ordered.This option is available on all  
downflow models.  
Easy Access LowVoltageTerminal Board  
Precedents LowVoltageTerminal Board  
is external to the electrical control  
cabinet. It is extremely easy to locate and  
attach the thermostat wire and test  
operation of all unit functions.This is  
another cost and time saving installation  
feature.  
Through the Base Electrical with Circuit  
Breaker  
This option is a factory installed thermal  
magnetic, molded case, HACR Circuit  
Breaker with provisions for through the  
base electrical connections. This option is  
available on all downflow models.  
RT-PRC005-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Through the Base Electrical with  
Disconnect Switch  
Factory installed 3-pole, molded case,  
disconnect switch with provisions for  
through the base electrical connections  
are available. This option is available on  
all downflow models.  
Added Efficiency  
Airflow  
Airflow is outstanding.The Precedent can  
replace an older machine with old  
ductwork and, in many cases, improve  
the comfort through better air  
distribution.  
Through the Base UtilitiesAccess  
Belt or direct drive – standard or  
oversized supply fan motors meet a wide  
airflow range.  
An electrical service entrance shall be  
provided allowing electrical access for  
both control and main power connections  
inside the curb and through the base of  
the unit. Option will allow for field  
Cooling  
Standard or High Efficiency Cooling  
available.  
installation of liquid-tight conduit and an  
external field installed disconnect switch.  
Economizer  
Unit Mounted Disconnect or Circuit  
Breaker  
Equipped with either dry bulb, reference  
or comparative enthalpy sensing, this  
feature provides free cooling as the  
outdoor temperature and/or humidity  
decreases. Economizers, correctly  
installed, offer a valuable energy savings.  
Factory-installed economizers save time  
and ensure proper installation.  
Codes require a method of assured unit  
shutdown for servicing. Field-installed  
disconnects sometimes interfere with  
service access. Factory installation of unit  
disconnects reduces costs, assures  
proper mounting and provides the  
opportunity to upgrade to unit circuit  
breaker protection.  
High Efficiency Motors  
This option is available with efficiency  
ratings from 86.5 up to 91.0. It is not  
available for all models.  
LowAmbient Cooling  
All Precedent microprocessor units have  
cooling capabilities down to 0°F as  
standard. Electromechanical models  
have cooling capabilities to 40°F as built,  
or to 0°F by adding the optional low  
ambient control (frostat).  
Oversized Motors  
Factory or field installed oversized  
motors available for high static  
applications.  
Convenience Outlet  
Unit Mounted Disconnect  
or Circuit Breaker  
One of our FinestAssets:  
Trane Sales Representatives are a  
Support Group that can assist you with:  
— Product  
Factory Installed Options  
A wide variety of Factory Installed  
Options (FIOPs) are available.  
— Application  
— Service  
Training  
— Special Applications  
— Specifications  
— Computer Programs and much more  
Precedent has the features and benefits  
that make it first class in the light  
commercial rooftop market.  
10  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Application of this product should be  
within the cataloged airflow and cooling  
considerations.  
Condensate Trap  
The evaporator is a draw-thru  
configuration. A trap must be field  
provided prior to start-up on the cooling  
cycle.  
LowAmbient Cooling  
The Precedent™ line features, with  
ReliaTel™ microprocessor controls, low  
ambient cooling down to 0°F. With  
electromechanical controls, Precedent  
features low ambient cooling to 40°F. The  
following options need to be included/  
considered when low ambient  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate service  
maximum capacity and peak operating  
efficiency. Actual clearances which  
appear inadequate should be reviewed  
with the localTrane sales personnel.  
applications are required: continuous fan  
operation, crankcase heaters, thermal  
expansion valves, frostat. Contact your  
localTrane Representative for more  
assistance with low ambient cooling  
applications.  
Unit Pitch  
These units have reversible sloped  
condensate drain pans. Units must be  
installed level, any unit slope must be  
toward the side of unit where condensate  
drain is connected.  
Barometric Relief  
This product line offers an optional  
barometric relief damper. for use in  
conjunction with economizer option. This  
accessory consists of gravity dampers  
which open with increased pressure. As  
the building air pressure increases, the  
pressure in the unit return air section  
also increases, opening the dampers and  
relieving the conditioned space.  
NOTE:THE EFFECTIVENESS OF  
BAROMETRIC RELIEF DAMPER DURING  
ECONOMIZING OPERATION IS SYSTEM  
RELATED.  
PRESSURE DROP OFTHE RETURN AIR  
SYSTEM SHOULD BE CONSIDEREDTO  
CONTROL BUILDING PRESSURIZATION.  
RT-PRC005-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedures  
Step 4  
Cooling Capacity  
Step 1  
Calculate the buildings total and sensible  
cooling loads at design conditions. Use  
theTrane calculation methods or any  
other standard accepted method.  
Heating Capacity  
Step 1  
Calculate the building heating load using  
theTrane calculation form or other  
standard accepted method.  
In order to select the correct unit which  
meets the buildings requirements, the  
fan motor heat must be deducted from  
the gross cooling capacity.The amount of  
heat that the fan motor generates is  
dependent on the effort by the motor -  
cfm and static pressure.To determine the  
total unit static pressure:  
Step 2  
Size the system heating capacity to  
Factors used in unit selection:  
match the calculated building heating  
A
load.The following are building heating  
External Static (duct system)  
0.36 wg  
Total Cooling Load: 59 MBh  
requirements:  
B
A
Sensible Cooling Load: 40 MBh  
Standard Filter 1 in.  
fromTable PD-61  
0.15 wg  
Total heating load of 15 MBH  
C
B
Airflow: 2000 cfm  
2000 cfm  
Economizer  
0.18 wg  
D
C
Electrical Characteristics: 460/60/3  
(100% Outside Air)  
fromTable  
PD-73  
460 volt/3 phase Power Supply  
E
Summer Design Conditions: Entering  
Evaporator Coil: 80 DB, 67WB Outdoor  
Ambient: 95  
The electric heat accessory capacities  
are listed inTable PD-62. From the table,  
a 6 kW heater will deliver 20.48 MBH at  
480 volts. In order to determine capacity  
at 460 volts, the heater voltage  
correction factor fromTable PD-63 must  
be used.Therefore, 20.48 MBH x .9118  
(voltage correction factor) = 18.80 MBH.  
Electric Heater Size 6 kW 0.056 wg  
fromTable PD-61  
F
External Static Pressure: 0.36 in. wg  
(reference “Heating Capacity” section on  
this page for determination of heater  
size)  
G
Downflow Configuration  
H
Total Static Pressure  
0.75 wg  
High Efficiency  
I
Economizer  
Note:The Evaporator Fan Performance  
Table PD-46 has deducted the pressure  
drop for a 1 in. filter already in the unit  
(see note belowTable PD-24).Therefore,  
the actual total static pressure is 0.75 -  
0.15 (fromTable PD - 61) = 0.60 wg.  
Air Delivery Selection  
External static pressure drop through  
the air distribution system has been  
calculated to be 0.60 inches of water.  
EnterTable PD-46 for aTHC060A4 at  
2000 cfm and 0.60 static pressure.The  
standard direct drive motor will give the  
desired airflow at a rated bhp of 0.90  
and 998 rpm.  
Step 2  
As a starting point, a rough determination  
must be made of the size of the unit.The  
final selection will be made after  
examining the performance at the given  
conditions. Divide the total cooling load by  
nominal BTUH per ton (12 MBh per ton);  
then round up to the nearest unit size.  
With 2000 cfm and 0.60 wg.  
Table PD-46 shows .90 bhp for this unit.  
Note below the table gives a formula to  
calculate Fan Motor Heat,  
59 MBh / 12 MBh = approx. 5 tons  
2.829 x bhp + .4024 = MBH.  
2.829 x .83 + .4024 = 2.75 MBH.  
Step 3  
Table PD-15 shows that aTHC060A4 has  
a gross cooling capacity of 62.4 MBh and  
48.4 MBh sensible capacity at 2000 cfm  
and 95 DB outdoor ambient with 80 DB,  
67 WB air entering the evaporator.  
Now subtract the fan motor heat from  
the gross cooling capacity of the unit:  
NetTotal Cooling Capacity  
= 62.4 MBH - 2.95 = 59.45 MBH.  
Net Sensible Cooling Capacity  
= 48.4 MBH - 2.95 = 45.45 MBH.  
To Find Capacity at Intermediate  
Conditions Not in theTable  
Step 5  
When the design conditions are between  
two numbers that are in the capacity  
table, interpolation is required to  
approximate the capacity. Note:  
Extrapolation outside of the table  
conditions is not recommended.  
If the performance will not meet the  
required load of the buildings total or  
sensible cooling load, try a selection at  
the next higher size unit.  
12  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedure  
Step 3: Determine reheat  
temperature rise  
Go to PD-66 for reheat temperature rise:  
26.7°F db  
Dehumidification Selection  
Typical 10 tonTHC120A  
2000 cfmTotal Supply airflow  
800 cfm Outside Air (40%)  
1200 cfm Return Air  
0.41” External Static Pressure  
68°F DB,  
67°F WB  
OA Conditions  
Part load day and raining  
68°F db  
OA  
75°F DB,  
RA'  
52% RH  
67°F wb  
MA' 72.2°F DB  
65°F WB  
RA’ conditions  
75°F db  
63°F wb  
OA  
47°F DB  
SA'  
MA'  
RA'  
73°F DB  
SA  
Step 1: Determine the mixed/  
entering air condition (MA)  
MA’ = (% outside air*outside air dry-bulb  
temperature) + (% return air*return air  
dry-bulb temperature)  
SA  
REHEAT  
SA'  
MA’ = (0.40*68°F) + (0.60*75°F)  
MA’ = 72.20°F db  
Chart C-1  
Note: Repeat for wet-bulb  
temperature (wb).  
Plot on psychrometric chart.  
Note: Reheat temperature rise is based  
on supply airflow and leaving evaporator  
coil temperature.  
Step 5: Determine static pressure  
drop add for reheat  
MA’  
72.2°F db  
65°F wb  
Table PD-61 shows a static pressure drop  
of 0.09” wc 0.41”+ 0.09” = 0.5” wc  
Step 4: Determine leaving unit  
temperature  
Reheat temperature (obtained in step 3)  
+ SA’  
26.7°F db + 47°F = 73.7°F db  
SA=73.7°F  
Table PD-57 indicates that a standard  
motor and field installed low static drive  
kit is needed for this airflow and static  
pressure range.  
Step 2: Determine leaving unit  
temperature  
Leaving UnitTemperature = SA’  
Utilize theTOPSS™ program to  
determine the leaving unit temperature.  
Consider Chart C-1. If the space relative  
humidity is equal to or above the space  
relative humidity setpoint, the  
45°F db  
44°F wb  
43°F dp  
Dehumidification option will:  
• Energize compressor or both  
compressors (2 stage compressor units).  
• Hot gas reheat valve is energized and  
hot gas is diverted to the reheat coil.  
• Dehumidification/reheat is terminated  
when space humidity is reduced to 5%  
below relative humidity setpoint.  
At MA’, air enters the RTU.The RTU filters,  
cools, and dehumidifies the air as it  
moves through the evaporator coil. Air  
leaves the evaporator coil saturated at  
the preset dew point condition (SA) and  
is reheated by the hot gas reheat coil to  
deliver 73.7°F (SA) supply air to the  
space.  
RT-PRC005-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Number  
Description  
T
1
S
2
C 036 A  
3 4,5,6 7  
3
8
R
9
B
A
**  
C
0
0
0
A
1
0
0
0
1
A
1
10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25  
DIGIT 1 - Unit Function  
DIGITS 12, 13 - Service Sequence  
** Factory Assigned  
DIGIT 20 - Convenience Outlet  
T = DX Cooling  
=
0 = No Convenience Outlet  
A = Unpowered Convenience Outlet  
B = Powered Convenience Outlet  
(3 phase only)  
DIGIT 2 - Efficiency  
DIGIT 14 - Fresh Air Selection  
S = Standard Efficiency  
H = High Efficiency  
0 = No Fresh Air  
A = Manual Outside Air Damper 0-50%  
B = Motorized Outside Air Damper 0-50%  
C = Economizer, Dry Bulb 0-100%  
without Barometric Relief  
DIGIT 21 - Communications Options  
0 = No Communications Interface  
1 = Trane Communications Interface  
2 = LonTalk® Communications Interface  
3 = Novar 2024 Controls  
DIGIT 3 - Airflow  
C = Convertible  
D = Economizer, Dry Bulb 0-100%  
with Barometric Relief  
E = Economizer, Reference Enthalpy  
0-100% without Barometric Relief  
F = Economizer, Reference Enthalpy  
0-100% with Barometric Relief  
G = Economizer, Comparative Enthalpy  
0-100% without Barometric Relief  
H = Economizer, Comparative Enthalpy  
0-100% with Barometric Relief  
DIGITS 4,5,6 - Nominal Gross Cooling  
Capacity (MBh)  
4 = Novar 3051 Controls  
DIGIT 22 - Refrigeration System Option  
036 =  
048 =  
060 =  
072 =  
090 =  
092 =  
102 =  
120 =  
3 Ton  
4 Ton  
0 = Standard Refrigeration System  
A = Thermal Expansion Valve (TXV)  
B = Dehumidification (Hot Gas Reheat  
Coil)  
5 Ton  
6 Ton  
Ton, Single Compressor  
Ton, Dual Compressor  
Ton  
DIGIT 23 - Refrigeration Controls  
DIGIT 15 - Supply Fan/Drive Type/Motor  
10 Ton  
0 = No Refrigeration Control  
1 = High Pressure Control  
2 = Frostat  
0 = Standard Drive  
1 = Oversized Motor  
2 = Optional Belt Drive Motor  
DIGIT 7 - Major Design Sequence  
A = First  
3 = Crankcase Heater  
4 = High Pressure Control and Frostat  
5 = High Pressure Control and Crankcase  
Heater  
6 = Frostat and Crankcase Heater  
7 = High Pressure Control, Frostat and  
Crankcase Heater  
DIGIT 16 - Hinged Service Access/Filters  
DIGIT 8 - Unit Voltage  
0 = Standard Panels/Standard Filters  
A = Hinged Access Panels/Standard Filters  
B = Standard Panels/2” Pleated Filters  
C = Hinged Access Panels/2” Pleated  
Filters  
1 = 208-230/60/1  
3 = 208-230/60/3  
4 = 460/60/3  
W= 575/60/3  
K = 380/60/3  
DIGIT 24 - Smoke Detector  
DIGIT 17 - Condenser Coil Protection  
DIGIT 9 - Unit Controls  
0 = No Smoke Detector  
A = Return Air Smoke Detector  
B = Supply Air Smoke Detector  
C = Supply and Return Air Smoke  
Detectors  
0 = Standard Coil  
E = Electromechanical  
R = ReliaTel™Microprocessor  
1 = Standard Coil with Hail Guard  
2 = Epoxy Coated Condenser Coil  
3 = Epoxy Coated Condenser Coil with  
Hail Guard  
DIGIT 10 - Heating Capacity  
0 = No Electric Heat  
A = 5 kW (1 phase)  
B = 6 kW (3 phase)  
C = 9 kW (3 phase)  
D = 10 kW (1 phase)  
E = 12 kW (3 phase)  
F = 14 kW (1 phase)  
G = 18 kW (1 and 3 phase)  
J = 23 kW (3 phase)  
K = 27 kW (3 phase)  
N = 36 kW (3 phase)  
P = 54 kW (3 phase)  
DIGIT 25 - Monitoring Controls  
DIGIT 18 - Through the Base Provisions  
0 = No Monitoring Control  
1 = Clogged Filter Switch  
2 = Fan Failure Switch  
3 = Discharge Air Sensing Tube  
4 = Clogged Filter Switch and Fan Fail  
Switch  
5 = Clogged Filter Switch and Discharge  
Air Sensing Tube  
6 = Fan Fail Switch and Discharge Air  
Sensing Tube  
0 = No Through the Base Provisions  
A = Through the Base Electric  
DIGIT 19 - Disconnect/Circuit Breaker/  
Phase Monitor (3 phase only)  
0 = No Disconnect/NoCircuit Breaker/No  
Phase Monitor  
1 = Unit Mounted Non-Fused Disconnect  
2 = Unit Mounted Circuit Breaker  
3 = Phase Monitor  
4 = Phase Monitor & Non-Fused  
Disconnect Switch  
5 = Phase Monitor & Circuit Breaker  
7 = Clogged Filter and Fan Fail Switches  
and Discharge Air Sensing Tube  
8 = Novar Return Air Sensor  
DIGIT 11 - Minor Design Sequence  
A = First Sequence  
Example:  
ModelnumberTSC036A3RBA**C000A10001A1describesaunitwiththefollowingcharacteristics:DXCooling,3tonnominalcoolingcapacity,208-230/60/3powersupply,ReliaTel™ controls,6kW  
electric heater model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels/filters, standard condenser coil with no coil protection, through the  
base electric, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and clogged filter switch.  
14  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(3 - 5Ton)  
Standard Efficiency  
Table GD – 1 — General Data  
3Ton Convertible Units  
TSC036A1, A3, A4, AW  
4Ton Convertible Units  
TSC048A1 TSC048A3, A4, AW  
5Ton Convertible Units  
TSC060A1 TSC060A3, A4, AW TSC060AK  
Cooling Performance1  
Gross Cooling Capacity  
SEER2  
37,400  
10.75  
50,300  
10.1  
49,200  
10.0  
63,100  
9.9  
63,100  
10.2  
63,100  
10.2  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
System Power (kW)  
1,200/1,200  
36,000  
1,600/1,600  
48,000  
5.28  
1,600/1,600  
47,000  
2,000/2,000  
60,000  
6.86  
2,000/2,000  
60,000  
6.78  
2,000/2,000  
60,000  
6.78  
3.798  
5.40  
Compressor  
No./Type  
Outdoor Sound Rating (dB)3  
1/Recip.  
83  
1/Scroll  
86  
1/Scroll  
82  
1/Scroll  
84  
1/Scroll  
84  
1/Scroll  
84  
Outdoor Coil Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
Rows/FPI  
Lanced  
0.3125  
7.19  
Lanced  
0.3125  
6.17  
Lanced  
0.3125  
9.59  
Lanced  
0.3125  
8.81  
Lanced  
0.3125  
8.81  
Lanced  
0.3125  
8.81  
2/17  
2/17  
1/17  
2/17  
2/17  
2/17  
Indoor Coil Type  
Tube Size (in.)  
Lanced  
0.3125  
Lanced  
0.3125  
Lanced  
0.3125  
Lanced  
0.3125  
Lanced  
0.3125  
Lanced  
0.3125  
Face Area (sq ft)  
5.67  
6.68  
6.17  
5.00  
5.00  
5.00  
Rows/FPI  
2/16  
3/16  
3/16  
3/16  
3/16  
3/16  
Refrigerant Control  
Drain Connection No./Size (in.)  
Short Orifice  
1/¾ NPT  
Short Orifice  
1/¾ NPT  
Short Orifice  
1/¾ NPT  
Short Orifice  
1/¾ NPT  
Short Orifice  
1/¾ NPT  
Short Orifice  
1/¾ NPT  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Propeller  
1/22  
Direct/1  
2550  
Propeller  
1/22  
Direct/1  
2850  
Propeller  
1/22  
Direct/1  
3610  
Propeller  
1/22  
Direct/1  
3470  
Propeller  
1/22  
Direct/1  
3470  
Propeller  
1/22  
Direct/1  
3470  
No. Motors/HP  
1/.20  
1/.33  
1/.33  
1/.33  
1/.33  
1/.40  
Motor RPM  
1115  
1115  
1115  
1115  
1115  
1115  
Direct Drive Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
10 x 10  
Direct/2  
1
11 x 11  
Direct/2  
1
11 x 11  
Direct/2  
1
11 x 11  
Direct/2  
1
11 x 11  
Direct/2  
1
12x11/–  
Direct/2  
1
Motor HP (Standard/Oversized)  
Motor RPM (Low/High Speed)  
Oversized Motor RPM  
(Low/High Speed)  
Motor Frame Size  
(Standard/Oversized)  
.33/.50  
950/1060  
.60/.80  
930/1000  
.60/.80  
930/1000  
.90/1.00  
985/1100  
.90/1.00  
985/1100  
1.0/–  
935/1100  
1100/1145  
48/48  
1000/1100  
48/48  
1000/1100  
48/48  
1080/1135  
48/48  
1080/1135  
48/48  
48/—  
Belt Drive Indoor Fan Type  
No. Used  
FC Centrifugal  
FC Centrifugal  
FC Centrifugal  
1
1
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
Motor HP  
Motor RPM  
11 x 11  
11 x 11  
Belt/Variable Speed  
11 x 11  
Belt/Variable Speed  
Belt/Variable Speed6  
1
1
1
1.00  
1750  
56  
1.00  
1750  
56  
1.00  
1750  
56  
Motor Frame Size  
Filters Type Furnished 7  
Throwaway  
(2) 20 x 25 x 1  
Throwaway  
(2) 20 x 25 x 1  
Throwaway  
(2) 20 x 25 x 1  
Throwaway  
(2) 20 x 25 x 1  
Throwaway  
(2) 20 x 25 x 1  
Throwaway  
(2) 20 x 25 x 1  
(No.) Size Recommended (in.)  
Refrigerant Charge (Lbs of R-22)4  
3.8  
4.4  
3.8  
4.7  
4.9  
4.9  
Notes:  
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes  
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is  
basedonARIStandard210/240exceptAK(380V/60Hz).  
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.  
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
5. TSC036A1SEERis10.5.  
6. Belt Drive Motor is not available for TSC036A1.  
7. Optional 2” Pleated Filters also available.  
8. TSC036A1SystemPower(kW)is3.91.  
RT-PRC005-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(6 - 10Ton)  
Standard Efficiency  
Table GD – 2— General Data  
6Ton  
Convertible Units  
Ton  
Convertible Units  
Ton  
Convertible Units  
10Ton  
Convertible Units  
TSC072A3, A4, AW, AK TSC090A3,A4,AW, AK TSC092A3, A4, AW  
TSC102A3, A4, AW, AK TSC120A3, A4, AW, AK  
Cooling Performance1  
Gross Cooling Capacity  
EER2  
72,000  
10.3  
95,000  
10.3  
92,000  
10.3  
105,000  
10.3  
118,000  
10.46  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part LoadValue (IPLV)3  
System Power (kW)  
Compressor  
2,400/2,100  
3,000/2,625  
3,000/2,625  
87,000  
11.18  
3,400/3,000  
100,0007  
11.98  
4,000/3,200  
114,0007  
11.58  
69,000  
90,000  
6.7  
8.74  
8.45  
9.719  
10.969  
No./Type  
1/Scroll  
88  
Lanced  
0.3125  
13.88  
1/Scroll  
90  
Lanced  
0.3125  
17.00  
2/Scrolls  
87  
Lanced  
0.3125  
2/Scrolls  
86  
Lanced  
0.3125  
2/Scrolls  
86  
Lanced  
0.3125  
Outdoor Sound Rating (dB)4  
Outdoor Coil —Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
17.00  
19.83  
19.83  
Rows/FPI  
2/17  
3/17  
2/17  
2/17  
2/17  
Indoor Coil Type  
Tube Size (in.)  
Lanced  
0.3125  
9.89  
Lanced  
0.3125  
9.89  
Lanced  
0.3125  
9.89  
Lanced  
0.3125  
12.36  
Lanced  
0.3125  
12.36  
Face Area (sq ft)  
Rows/FPI  
2/16  
3/16  
3/16  
3/16  
4/16  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
6500  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
7100  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
7000  
Direct/1  
6100  
Direct/1  
6200  
No. Motors/HP  
Motor RPM  
1/0.7011  
1115  
1/0.7011  
1115  
1/0.70  
1115  
1/0.75  
1115  
1/0.75  
1115  
Belt Drive Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size  
12 x 12  
Belt/Variable Speed  
1
12 x 12  
Belt/Variable Speed  
1
12 x 12  
Belt/Variable Speed  
1
15 x 15  
Belt/Variable Speed  
1
15 x 15  
Belt/Variable Speed  
1
1.00/2.0012  
1750  
2.00/3.00  
1750  
2.00/3.00  
1750  
2.00/3.00  
1750  
3.00/5.00  
1750/3450  
56  
56  
56  
56  
56  
Filters Type Furnished 10  
(No.) Size Recommended (in.)  
Refrigerant Charge (Lbs of R-22)5  
Throwaway  
(4) 16 x 25 x 2  
7.1  
Throwaway  
(4) 16 x 25 x 2  
11.5  
Throwaway  
(4) 16 x 25 x 2  
6.2 Circuit 1  
3.4 Circuit 2  
Throwaway  
(4) 20 x 25 x 2  
7.9 Circuit 1  
4.0 Circuit 2  
Throwaway  
(4) 20 x 25 x 2  
7.2 Circuit 1  
5.3 Circuit 2  
Notes:  
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes  
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is  
basedonARIStandard210/240exceptAK(380V/60Hz).  
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.  
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.  
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
6. EER shown is for downflow airflow. EER for horizontal airflow is 10.3.  
7. ARI Net Cooling Capacity shown is for downflow airflow. Cooling Capacity for Horizontal airflow TSC102A is 99,000; TSC120A is 112,000.  
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for Horizontal airflow TSC092A is 10.8, TSC102A is 11.5; TSC120A is 11.0.  
9. System Power (kW) shown is for downflow airflow. System Power (kW) forHorizontal airflow TSC102A is 9.61; for TSC120A is 10.87.  
10. Optional 2” Pleated Filters also available.  
11. Outdoor motor is 0.75 hp for AK (380V/60 Hz units).  
12. Standard indoor motor is 2.00 hp for AK (380V/60 Hz) units.  
16  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(3 - 5Ton)  
High Efficiency  
Table GD – 3 — General Data  
3Ton  
4Ton  
5 Ton  
Convertible Units  
THC036A1,A3,A4,AW  
Convertible Units  
THC048A1,A3,A4,AW  
Convertible Units  
THC060A1  
THC060A3,A4,AW  
Cooling Performance1  
Gross Cooling Capacity  
38,000  
49,800  
62,100  
62,400  
SEER / EER2  
12.5/—  
12.0/—  
11.8/—  
12.0/ —  
Nominal CFM / ARI Rated CFM  
1,200/1,200  
1,600/1,600  
2,000/2,000  
2,000/2,000  
ARI Net Cooling Capacity  
System Power (kW)  
Compressor  
36,600  
3.33  
47,500  
4.48  
59,000  
5.73  
59,500  
5.56  
No./Type  
1/Climatuff Scroll  
83  
1/Climatuff Scroll  
85  
1/Climatuff Scroll  
84  
1/Climatuff Scroll  
84  
Outdoor Sound Rating (dB)3  
Outdoor Coil Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
Lanced  
0.3125  
7.19  
Lanced  
0.3125  
9.59  
Lanced  
0.3125  
10.96  
Lanced  
0.3125  
10.96  
Rows/FPI  
2/17  
3/17  
3/17  
3/17  
Indoor Coil Type  
Tube Size (in.)  
Lanced  
0.3125  
6.68  
Lanced  
0.3125  
6.68  
Lanced  
0.3125  
7.71  
Lanced  
0.3125  
7.71  
Face Area (sq ft)  
Rows/FPI  
3/16  
4/16  
4/16  
4/16  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice  
1/¾ NPT  
Propeller  
1/22  
Short Orifice  
1/¾ NPT  
Propeller  
1/22  
Short Orifice  
1/¾ NPT  
Propeller  
1/22  
Direct/1  
3170  
Short Orifice9  
1/¾ NPT  
Propeller  
1/22  
Direct/110  
2550  
Direct/110  
3050  
Direct/110  
3370  
No. Motors/HP  
1/.20  
1/.33  
1/.33  
1/.33  
Motor RPM  
1115  
1115  
1115  
1115  
Direct Drive Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
10 x 10  
Direct/2  
1
11 x 11  
Direct/2  
1
11 x 11  
Direct/2  
1
11 x 11  
Direct/2  
1
Motor HP (Standard/Oversized)  
Standard Motor RPM (Low/High Speed)  
Oversized Motor RPM (Low/High Speed)  
Motor Frame Size (Standard/Oversized)  
Belt Drive Indoor Fan Type  
No. Used  
.33/.50  
950/1060  
1100/1145  
48/48  
FC Centrifugal  
1
.60/.80  
930/1000  
1000/1100  
48/48  
FC Centrifugal  
1
.90/1.00  
985/1100  
1080/1135  
48/48  
.90/1.00  
985/1100  
1080/1135  
48/48  
FC Centrifugal  
1
Diameter xWidth (in.)  
11 x 11  
11 x 11  
11 x 11  
DriveType/No. Speeds  
Belt/Variable Speed 6  
1
Belt/Variable Speed 6  
1
Belt/Variable Speed  
No. Motors  
1
Motor HP  
Standard Motor RPM  
Motor Frame Size  
1.00  
1750  
56  
1.00  
1750  
56  
1.00  
1750  
56  
Filters Type Furnished 7  
(No.) Size Recommended (in.)  
Optional Hot Gas Reheat Coil-Type12  
Tube Size (in.) OD  
Face Area (sq. ft)  
Rows/FPI  
Refrigerant Charge (Lbs of R-22)4  
Standard  
Throwaway  
(2) 20 x 25 x 1  
Lanced  
0.375  
Throwaway  
(2) 20 x 25 x 1  
Lanced  
0.375  
Throwaway  
(2) 20 x 30 x 1  
Throwaway  
(2) 20 x 30 x 111  
Lanced  
0.375  
2.22  
1/16  
2.22  
1/16  
2.22  
2/16  
5.38  
5.3  
7. 7 5  
8.5  
7. 9  
8 . 4  
10.7  
Optional Hot Gas Reheat Coil  
Notes:  
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes  
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,  
whichisbasedonARIStandard210/240.  
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.  
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.  
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
5. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.  
6. Belt Drive Motor is not available for THC036A1, THC048A1.  
7. Optional 2” Pleated Filters also available.  
8. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.  
9. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.  
10. With Dehumidification (Hot Gas Reheat) option: Direct/2 speed.  
11. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.  
12. Availableonthree-phaseonly.  
RT-PRC005-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(6 - 10Ton)  
High Efficiency  
Table GD – 4— General Data  
6Ton  
Ton  
Ton  
10Ton  
Convertible Units  
THC072A3, A4, AW  
Convertible Units  
THC092A3, A4, AW  
Convertible Units  
THC102A3, A4. AW  
Convertible Units  
THC120A3, A4, AW  
Cooling Performance1  
Gross Cooling Capacity  
EER2  
73,000  
11.56  
94,000  
11.56  
103,000  
11.56  
117,000  
11.26  
Nominal CFM / ARI Rated CFM  
ARI Net Cooling Capacity  
Integrated Part LoadValue (IPLV)3  
System Power (kW)  
Compressor  
2,400/2,100  
3,000/2,625  
90,00010  
11.98  
3,400/3,000  
98,00010  
12.18  
4,000/3,200  
109,00010  
12.08  
70,000  
6.097  
7.837  
8.527  
9.737  
No./Type  
1/Climatuff Scroll  
2/Climatuff Scrolls  
91  
2/Climatuff Scrolls  
89  
2/Climatuff Scrolls  
88  
Outdoor Sound Rating (dB)4  
Outdoor Coil —Type  
Tube Size (in.) O.D.  
Face Area (sq ft)  
89  
Lanced  
0.3125  
17.00  
Lanced  
0.3125  
17.50  
Lanced  
0.3125  
19.83  
Lanced  
0.3125  
27.21  
Rows/FPI  
3/17  
3/17  
3/17  
3/17  
Indoor Coil Type  
Tube Size (in.)  
Lanced  
0.3125  
9.89  
Lanced  
0.3125  
12.36  
Lanced  
0.3125  
12.36  
Lanced  
0.3125  
12.36  
Face Area (sq ft)  
Rows/FPI  
3/16  
3/16  
4/16  
5/16  
Refrigerant Control  
Drain Connection No./Size (in.)  
Outdoor Fan Type  
No. Used/Diameter (in.)  
DriveType/No. Speeds  
CFM  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
6100  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
6200  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
6600  
Short Orifice  
1/¾ NPT  
Propeller  
1/26  
Direct/1  
7000  
No. Motors/HP  
Motor RPM  
1/0.70  
1075  
1/0.70  
1075  
1/0.75  
1075  
1/0.75  
1075  
Belt Drive Indoor Fan Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
Diameter xWidth (in.)  
DriveType/No. Speeds  
No. Motors  
12 x 12  
Belt/Variable Speed  
1
15 x 15  
Belt/Variable Speed  
1
15 x 15  
Belt/Variable Speed  
1
15 x 15  
Belt/Variable Speed  
1
Motor HP (Standard/Oversized)  
Motor RPM (Standard/Oversized)  
Motor Frame Size  
1.00/2.00  
1750  
56  
2.00/3.00  
1750  
2.00/3.00  
1750  
3.00/5.00  
1750/3450  
56  
56  
56  
Filters Type Furnished 9  
(No.) Size Recommended (in.)  
Optional Hot Gas Reheat Coil Type  
Tube Size (in.) OD  
Throwaway  
(4) 16 x 25 x 2  
Throwaway  
(4) 20 x 25 x 2  
Lanced  
0.375  
Throwaway  
(4) 20 x 25 x 2  
Lanced  
0.375  
Throwaway  
(4) 20 x 25 x 2  
Lanced  
0.375  
Face Area (sq. ft.)  
5.19  
5.19  
5.19  
Rows/FPI  
Refrigerant Charge (Lbs of R-22)5  
10.7  
2/16  
6.4 Circuit 1  
6.2 Circuit 2  
2/16  
7.4 Circuit 1  
7.1 Circuit 2  
2/16  
11.0 Circuit 1  
7.3 Circuit 2  
Notes:  
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes  
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is  
basedonARIStandard210/240.  
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.  
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.  
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.  
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.  
6. EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.  
7. System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.  
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.  
9. Optional 2” Pleated Filters also available.  
10. Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.  
18  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance (3, 4Ton)  
Data  
Standard Efficiency  
Table PD-1 — Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TSC036A1, A3, A4, AW  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 34.6 29.0 38.6 22.3 40.6 14.7 31.2 27.3 36.6 21.1 39.5 13.8 28.2 25.6 33.4 19.6 37.8 12.9 25.1 24.1 29.6 18.2 35.5 11.9  
80 35.6 35.0 38.8 27.3 41.0 20.2 32.6 32.6 36.8 26.6 39.8 19.5 30.0 30.0 33.5 25.2 38.0 18.5 27.3 27.3 29.9 23.5 35.6 17.5  
1080  
1200  
1320  
85  
37.6 37.6 39.2 32.5 41.5 24.7 35.6 35.6 37.2 32.2 40.1 24.2 32.8 32.8 34.2 31.0 38.2 23.8 30.1 30.1 30.7 29.3 35.8 23.0  
90 39.3 39.3 39.7 37.6 42.0 29.2 37.8 37.8 37.9 37.6 40.4 29.1 35.7 35.7 35.7 35.7 38.5 28.9 33.0 33.0 32.9 32.9 36.0 28.4  
75 35.6 30.9 39.0 22.8 40.9 14.9 32.2 29.2 37.3 22.1 39.8 14.1 29.0 27.5 34.3 20.7 38.2 13.1 25.9 25.9 30.4 19.0 36.0 12.1  
80 36.7 36.7 39.3 28.4 41.4 20.6 34.3 34.3 37.4 28.1 40.2 20.3 31.4 31.4 34.5 26.9 38.4 19.3 28.6 28.6 30.7 25.2 36.1 18.3  
85 38.7 38.7 39.7 33.9 41.9 25.3 37.0 37.0 37.9 34.0 40.5 25.0 34.5 34.5 35.3 33.2 38.7 24.8 31.5 31.5 31.7 31.6 36.3 24.2  
90 40.2 40.2 40.4 39.2 42.3 30.1 38.8 38.8 38.8 38.8 40.9 30.2 37.1 37.1 37.0 37.0 39.1 30.3 34.6 34.6 34.6 34.6 36.6 30.0  
75 36.4 32.6 39.4 23.5 41.1 15.1 33.2 31.0 37.7 23.0 40.1 14.3 29.8 29.3 34.9 21.8 38.5 13.4 26.8 26.8 30.9 20.0 36.3 12.4  
80  
37.7 37.7 39.7 29.4 41.6 20.9 35.7 35.7 37.9 29.3 40.4 21.2 32.7 32.7 35.2 28.5 38.7 19.9 29.8 29.8 31.4 26.8 36.5 19.0  
85 39.4 39.4 40.2 35.2 42.1 25.9 37.9 37.9 38.5 35.6 40.8 25.7 35.9 35.9 36.2 35.3 39.1 25.7 32.9 32.9 32.9 32.9 36.7 25.3  
90 40.8 40.8 40.9 40.5 42.6 30.8 39.7 39.7 39.6 39.6 41.2 31.2 38.0 38.0 38.0 38.0 39.5 31.6 35.9 35.9 35.9 35.9 37.1 31.5  
75  
37.0 34.1 39.7 24.0 41.3 15.3 34.1 32.8 38.0 23.7 40.3 14.5 30.6 30.6 35.5 22.7 38.7 13.6 27.7 27.7 31.4 21.0 36.6 12.6  
80 38.4 38.4 40.0 30.3 41.8 21.2 36.7 36.7 38.3 30.5 40.8 21.0 33.9 33.9 35.8 30.0 39.0 20.4 30.8 30.8 32.0 28.4 36.8 19.7  
85 40.0 40.0 40.6 36.3 42.4 26.4 38.7 38.7 39.0 37.0 41.2 26.7 36.8 36.8 36.8 36.8 39.4 26.6 34.2 34.2 34.2 34.2 37.0 26.4  
90 41.4 41.4 41.4 41.4 42.9 31.6 40.3 40.3 40.3 40.3 41.5 32.1 38.7 38.7 38.7 38.7 39.9 32.7 36.7 36.7 36.7 36.7 37.6 33.0  
1440  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-2 — Gross Cooling Capacities (MBH) 4 Ton Single Phase TSC048A1  
AmbientTemperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 45.5 38.7 52.4 30.0 56.4 20.1 41.6 36.6 49.0 28.3 54.4 18.9 37.6 34.5 44.4 26.7 51.8 17.5 33.5 32.3 39.8 24.5 48.0 15.8  
80 46.5 46.5 52.5 37.6 56.8 28.1 43.2 43.2 49.1 35.9 54.8 26.7 39.9 39.9 44.6 33.8 52.0 25.2 36.5 36.5 40.1 31.6 48.2 23.4  
85 50.3 50.3 53.0 45.1 57.4 34.9 47.0 47.0 49.7 43.7 55.0 33.9 43.6 43.6 45.3 41.6 52.2 32.8 40.2 40.2 41.0 39.5 48.3 31.0  
90 53.3 53.3 53.8 52.5 57.7 41.1 50.8 50.8 50.8 50.8 55.5 41.0 47.5 47.5 47.5 47.5 52.5 40.1 44.0 44.0 44.0 44.0 48.6 38.6  
75 46.8 41.3 53.1 31.3 56.9 20.5 42.7 39.1 50.1 29.7 55.0 19.2 38.7 37.0 45.4 27.5 52.4 17.9 34.4 34.4 40.8 25.4 48.9 16.3  
80 48.7 48.7 53.4 39.5 57.5 28.9 45.2 45.2 50.3 38.2 55.4 27.8 41.8 41.8 45.7 36.0 52.7 26.3 38.2 38.2 41.1 33.9 49.1 24.7  
85 52.2 52.2 53.9 47.5 58.1 36.1 49.3 49.3 51.0 46.7 55.7 35.3 45.7 45.7 46.7 44.7 52.9 34.5 42.1 42.1 42.1 42.1 49.2 33.0  
90 54.9 54.9 54.9 54.9 58.4 42.8 52.7 52.7 52.7 52.7 56.2 42.9 49.8 49.8 49.8 49.8 53.3 42.5 46.2 46.2 46.2 46.2 49.7 41.3  
75 48.1 43.8 53.6 32.5 57.3 20.8 43.8 41.6 50.8 31.1 55.5 19.6 39.8 39.5 46.3 29.0 52.9 18.2 35.8 35.8 41.5 26.7 49.6 16.7  
80 50.5 50.5 54.0 41.2 58.0 29.6 47.1 47.1 51.1 40.3 55.9 29.0 43.4 43.4 46.7 38.2 53.2 27.4 39.8 39.8 42.0 36.0 49.7 25.8  
85 53.6 53.6 54.8 49.8 58.6 37.1 51.1 51.1 52.0 49.4 56.3 36.6 47.7 47.7 48.1 47.9 53.5 36.1 43.9 43.9 43.9 43.9 49.9 34.9  
90 56.1 56.1 56.1 56.1 59.0 44.2 54.2 54.2 54.1 54.1 56.9 44.8 51.5 51.5 51.5 51.5 54.1 44.7 48.2 48.2 48.2 48.2 50.5 43.9  
75 49.1 46.3 54.2 33.5 57.7 21.2 44.9 44.0 51.5 32.4 55.9 20.0 40.7 40.7 47.1 30.4 53.3 18.6 37.0 37.0 42.2 28.1 50.1 17.0  
80 51.9 51.9 54.6 42.7 58.4 30.1 48.8 48.8 51.8 42.2 56.3 30.2 45.0 45.0 47.7 40.4 53.7 28.5 41.2 41.2 42.9 38.2 50.3 26.9  
85 54.7 54.7 55.5 51.8 59.1 38.1 52.5 52.5 52.9 51.8 56.8 37.8 49.4 49.4 49.4 49.4 54.1 37.6 45.5 45.5 45.5 45.5 50.5 36.6  
1440  
1600  
1760  
1920  
90  
57.1 57.1 57.1 57.1 59.4 45.6 55.3 55.3 55.3 55.3 57.4 46.4 52.8 52.8 52.8 52.8 54.7 46.7 49.8 49.8 49.8 49.8 51.3 46.2  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC005-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance (4, 5Ton)  
Data  
Standard Efficiency  
Table PD-3 — Gross Cooling Capacities (MBH) 4 Ton Three Phase TSC048A3, A4, AW  
AmbientTemperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 44.8 38.6 51.4 29.8 56.1 20.1 41.0 36.6 48.2 28.2 53.7 18.9 37.3 34.7 44.2 26.4 50.8 17.6 33.4 32.7 39.6 25.2 47.1 16.0  
80 46.0 46.0 51.6 37.4 56.5 27.9 42.9 42.9 48.3 35.8 54.0 26.6 39.7 39.7 44.4 34.0 51.0 25.2 36.4 36.4 40.0 32.0 47.2 23.6  
85 49.6 49.6 52.0 44.8 56.7 34.8 46.8 46.8 48.9 43.6 54.2 34.0 43.6 43.6 45.1 41.8 51.2 32.7 40.3 40.3 41.0 39.8 47.4 31.1  
90 52.5 52.5 52.9 52.2 57.2 41.6 50.2 50.2 50.1 50.1 54.6 41.1 47.2 47.2 47.2 47.2 51.5 40.1 43.9 43.9 43.9 43.9 47.7 38.6  
75 46.1 41.1 52.1 31.1 56.7 20.5 42.1 39.0 49.1 29.6 54.4 19.3 38.3 37.1 45.1 27.8 51.5 18.0 34.3 34.3 40.6 25.7 47.9 16.5  
80 48.1 48.1 52.4 39.3 57.2 29.0 44.9 44.9 49.2 37.9 54.7 27.7 41.5 41.5 45.4 36.2 51.7 26.3 38.1 38.1 41.0 34.2 48.0 24.8  
1440  
1600  
1760  
85  
90 54.2 54.2 54.2 54.2 58.0 43.5 51.9 51.9 51.9 51.9 55.4 43.2 49.1 49.1 49.1 49.1 52.3 42.5 45.9 45.9 45.9 45.9 48.7 41.3  
75 47.2 43.5 52.8 32.3 57.3 20.9 43.3 41.5 49.8 30.9 54.9 19.7 39.1 39.1 45.8 29.1 52.0 18.3 35.6 35.6 41.3 27.1 48.5 16.8  
51.4 51.4 53.0 47.3 57.7 36.7 48.7 48.7 50.0 46.4 55.0 35.5 45.6 45.6 46.3 44.8 51.9 34.6 42.1 42.1 42.1 42.1 48.2 33.0  
80 49.7 49.7 53.1 41.0 57.8 30.1 46.7 46.7 50.1 40.0 55.3 28.8 43.3 43.3 46.2 38.3 52.3 27.4 39.7 39.7 41.8 36.3 48.7 25.9  
85 52.8 52.8 53.8 49.7 58.1 37.7 50.3 50.3 51.0 49.1 55.6 37.0 47.2 47.2 47.2 47.2 52.5 36.1 43.7 43.7 43.7 43.7 48.9 34.9  
90 55.5 55.5 55.5 55.5 58.7 45.3 53.4 53.4 53.4 53.4 56.1 45.2 50.7 50.7 50.7 50.7 53.1 44.7 47.6 47.6 47.6 47.6 49.5 43.8  
75 48.2 45.8 53.3 33.4 57.8 21.3 44.4 43.8 50.4 32.1 55.4 20.0 40.3 40.3 46.5 30.4 52.5 18.6 36.6 36.6 41.9 28.3 49.0 17.2  
80 51.0 51.0 53.7 42.7 58.3 31.1 48.1 48.1 50.7 41.9 55.7 29.6 44.7 44.7 47.0 40.3 52.8 28.4 41.1 41.1 42.6 38.3 49.2 26.9  
85 53.9 53.9 54.6 51.8 58.6 38.7 51.6 51.6 51.9 51.5 56.2 38.4 48.6 48.6 48.6 48.6 53.1 37.7 45.2 45.2 45.2 45.2 49.4 36.6  
90 56.6 56.6 56.6 56.6 59.3 47.0 54.6 54.6 54.5 54.5 56.8 47.1 52.0 52.0 52.0 52.0 53.8 46.9 49.0 49.0 49.0 49.0 50.3 46.1  
1920  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-4 — Gross Cooling Capacities (MBH) 5 Ton Single/Three Phase TSC060A1, A3, A4, AW, AK  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 57.4 49.1 64.8 37.9 69.2 25.3 53.3 47.0 61.8 36.3 67.2 24.1 49.4 45.0 57.6 34.3 64.3 22.8 45.2 42.9 52.4 32.7 60.6 21.2  
80 59.0 59.0 65.1 47.1 69.8 35.0 55.6 55.6 62.0 45.7 67.6 33.8 52.2 52.2 57.8 43.9 64.6 32.3 48.6 48.6 52.8 41.6 60.8 30.6  
85 63.1 63.1 65.7 56.2 70.2 42.9 60.3 60.3 62.7 55.3 68.0 42.3 56.8 56.8 58.9 53.6 64.9 41.3 52.9 52.9 54.0 51.4 61.0 39.9  
90 66.4 66.4 66.9 65.2 70.8 51.0 64.1 64.1 64.1 64.1 68.5 50.8 61.1 61.1 61.1 61.1 65.4 50.1 57.5 57.5 57.5 57.5 61.5 49.0  
75 59.0 52.2 65.7 39.4 69.8 25.7 54.9 50.1 62.8 37.9 67.8 24.6 50.7 48.0 58.9 36.1 64.9 23.2 46.5 45.9 53.5 33.8 61.3 21.6  
80 61.3 61.3 66.0 49.2 70.2 35.6 58.1 58.1 63.1 48.2 68.1 34.8 54.4 54.4 59.2 46.6 65.3 33.7 50.6 50.6 54.0 44.3 61.5 32.0  
85 65.1 65.1 66.8 59.1 70.9 44.2 62.5 62.5 64.0 58.5 68.7 43.8 59.3 59.3 60.4 57.3 65.7 43.1 55.2 55.2 55.8 55.2 61.8 41.9  
90 68.1 68.1 68.0 68.0 71.6 52.9 65.9 65.9 65.9 65.9 69.4 52.9 63.1 63.1 63.1 63.1 66.3 52.5 59.7 59.7 59.7 59.7 62.4 51.7  
75 60.3 55.2 66.3 40.6 70.2 26.1 56.3 53.1 63.6 39.5 68.2 25.0 52.0 51.0 59.9 37.8 65.4 23.6 47.7 47.7 54.5 35.4 61.8 22.0  
80 63.1 63.1 66.8 51.2 70.8 37.9 60.2 60.2 64.0 50.5 68.7 35.6 56.5 56.5 60.3 49.1 65.8 34.6 52.4 52.4 55.2 46.9 62.1 33.3  
85 66.5 66.5 67.7 61.6 71.5 45.4 64.2 64.2 65.0 61.3 69.4 45.2 61.2 61.2 61.7 60.5 66.4 44.7 57.3 57.3 57.3 57.3 62.5 43.8  
90 69.4 69.4 69.3 69.3 72.2 54.6 67.3 67.3 67.3 67.3 70.1 54.9 64.6 64.6 64.6 64.6 67.1 54.8 61.2 61.2 61.2 61.2 63.2 54.2  
75 61.5 58.0 66.9 41.8 70.6 26.5 57.6 56.0 64.2 40.8 68.6 25.4 53.0 53.0 60.6 39.3 65.9 24.0 49.1 49.1 55.4 37.1 62.2 22.4  
80 64.5 64.5 67.5 53.0 71.2 38.8 61.8 61.8 64.7 52.5 69.1 36.4 58.3 58.3 61.1 51.4 66.3 35.5 53.9 53.9 56.3 49.5 62.5 34.3  
1800  
2000  
2200  
2400  
85  
67.7 67.7 68.5 63.9 72.0 46.5 65.4 65.4 65.9 63.9 69.9 46.5 62.5 62.5 62.5 62.5 66.9 46.2 58.9 58.9 58.9 58.9 63.0 45.5  
90 70.4 70.4 70.4 70.4 72.8 56.1 68.4 68.4 68.4 68.4 70.6 56.6 65.8 65.8 65.8 65.8 67.7 56.8 62.4 62.4 62.4 62.4 63.9 56.5  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
20  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(6, 7½Ton)  
Standard Efficiency  
Table PD-5 — Gross Cooling Capacities (MBH) 6 Ton Three Phase  
TSC072A3, A4, AW, AK  
AmbientTemperature (F)  
95  
85  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27.3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47.7 60.9 36.4 70.3 24.6  
80  
67.6 66.2 73.7 52.2 77.5 38.9 63.2 63.2 70.9 51.1 76.0 37.8 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9  
2160  
2400  
2640  
85 71.4 71.4 74.2 61.9 78.6 47.4 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 67.3 59.7 74.0 46.0 60.4 60.4 62.2 57.3 70.8 45.0  
90 74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 77.2 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8  
75  
80 69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 37.9 57.8 57.8 62.6 49.6 71.3 36.3  
85 73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 77.2 47.9 67.4 67.4 69.1 63.6 74.8 47.6 63.2 63.2 64.2 61.4 71.7 47.0  
90 76.2 76.2 76.5 74.3 79.9 57.1 74.3 74.3 74.3 74.3 77.9 57.4 71.7 71.7 71.7 71.7 75.5 57.7 68.5 68.5 68.4 68.4 72.2 57.5  
75 69.1 61.4 74.7 44.9 77.4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4  
80 71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77.0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 37.7  
85 74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 67.3 77.8 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7  
67.7 58.3 74.0 43.8 77.1 28.7 62.9 55.9 71.7 42.6 75.9 27.7 57.9 53.4 67.9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0  
90  
77.4 77.4 77.5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8  
75 70.2 64.1 75.2 45.8 77.6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 27.3 56.2 56.2 64.7 41.9 71.7 25.8  
80 72.9 72.9 75.9 57.4 78.7 40.4 70.3 70.3 73.6 57.8 77.3 41.8 66.5 66.5 70.1 57.1 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5  
85 75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67.8 67.8 67.7 67.7 72.9 50.1  
90 78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9  
2880  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-6 — Gross Cooling Capacities (MBH) Ton Three Phase Single Compressor  
TSC090A3, A4, AW, AK  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 87.4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8  
80 89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77.6 77.6 87.2 65.3 97.4 48.2 71.6 71.6 78.9 61.5 92.9 46.0  
85 94.2 94.2 97.5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97.8 61.4 78.5 78.5 80.7 76.2 93.2 59.9  
90 98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5  
75 89.7 78.4 96.7 57.3 99.1 37.2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97.5 34.5 68.7 67.7 80.3 50.1 93.8 32.5  
80 92.2 92.2 97.5 70.9 100.3 50.4 87.4 87.4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1  
85 96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1  
90 99.5 99.5 99.9 97.0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77.4 90.1 90.1 90.0 90.0 95.3 77.7  
75 91.5 82.5 97.7 59.0 99.3 37.7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2  
80 94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1  
85 98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 97.5 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8  
90 100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97.2 97.2 97.2 97.2 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4  
75 92.9 86.2 98.1 59.9 99.4 38.2 87.3 84.1 96.3 60.6 99.8 37.2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8  
80 96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 97.1 77.5 101.0 55.7 87.6 87.6 92.5 77.2 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6  
85 99.0 99.0 99.7 88.7 101.8 62.7 97.8 97.8 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 67.3 89.1 89.1 89.1 89.1 96.3 68.3  
90 101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97.5 84.6  
2700  
3000  
3300  
3600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC005-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(7½, 8½Ton)  
Standard Efficiency  
Table PD-7 — Gross Cooling Capacities (MBH) Ton Three Phase Dual Compressors TSC092A3, A4, AW  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 84.6 72.9 93.9 55.3 98.4 36.4 78.2 69.6 90.1 53.3 96.9 35.1 71.8 66.3 83.9 50.4 94.0 33.3 65.3 63.1 76.5 47.1 89.4 31.2  
80 86.8 86.8 94.4 68.5 99.6 50.0 81.8 81.8 90.5 67.5 98.0 49.7 76.4 76.4 84.3 64.7 94.5 47.5 70.9 70.9 77.1 61.4 89.6 45.3  
85 92.2 92.2 95.4 81.7 100.8 61.3 88.4 88.4 91.5 81.5 99.0 62.4 83.2 83.2 85.8 79.3 94.9 60.9 77.6 77.6 79.0 76.1 89.9 59.3  
90 96.3 96.3 96.9 94.4 102.0 72.8 93.6 93.6 93.6 93.6 99.3 73.4 89.6 89.6 89.6 89.6 95.8 74.0 84.5 84.5 84.5 84.5 90.6 73.0  
75 86.8 77.5 94.7 57.0 98.9 37.1 80.5 74.4 91.5 55.8 97.6 35.7 74.0 71.1 85.6 53.1 94.8 34.0 67.1 67.1 78.2 49.8 90.5 31.9  
80 90.1 90.1 95.6 71.2 100.2 50.8 85.4 85.4 92.0 71.1 98.7 50.7 79.9 79.9 86.3 68.9 95.5 49.6 74.1 74.1 79.1 65.7 90.8 47.4  
85 94.7 94.7 96.8 85.3 101.4 62.7 91.5 91.5 93.3 86.2 99.7 63.7 86.9 86.9 88.2 84.9 96.1 63.5 81.3 81.3 81.2 81.2 91.2 62.6  
90 98.3 98.3 98.3 98.3 102.7 74.8 96.2 96.2 96.1 96.1 100.3 76.2 92.7 92.7 92.7 92.7 97.1 77.5 88.0 88.0 88.0 88.0 92.2 77.4  
75 88.7 81.9 95.7 58.9 99.3 37.6 82.6 79.0 92.5 58.2 98.1 36.2 75.5 75.5 87.1 55.7 95.4 34.6 69.6 69.6 79.6 52.4 91.3 32.5  
80 92.3 92.3 96.5 73.7 100.7 51.5 88.4 88.4 93.2 74.4 99.3 51.7 82.9 82.9 87.9 72.8 96.1 51.0 76.9 76.9 80.8 69.8 91.7 49.5  
85 96.5 96.5 97.8 88.4 102.0 63.9 93.8 93.8 94.8 90.3 100.0 65.0 89.8 89.8 89.8 89.8 96.9 65.8 84.4 84.4 84.4 84.4 92.3 65.5  
90 99.7 99.7 99.7 99.7 103.3 76.5 98.0 98.0 98.0 98.0 101.1 78.5 94.9 94.9 94.9 94.9 98.1 80.6 90.7 90.7 90.7 90.7 93.5 81.3  
75 90.2 85.7 96.4 60.6 99.7 38.1 84.6 83.6 93.3 60.0 98.5 36.8 77.9 77.9 88.2 58.1 96.0 35.2 71.8 71.8 80.9 55.0 92.0 33.2  
80 94.0 94.0 97.2 75.8 101.0 52.1 90.7 90.7 94.3 77.4 99.7 52.6 85.6 85.6 89.2 76.6 96.6 52.0 79.5 79.5 82.3 73.8 92.5 51.5  
2700  
3000  
3300  
3600  
85  
97.8 97.8 98.7 91.1 102.4 65.0 95.6 95.6 96.1 93.9 100.5 66.3 91.9 91.9 91.9 91.9 97.6 67.9 86.9 86.9 86.9 86.9 93.1 68.2  
90 100.8 100.8 100.8 100.8 103.7 78.1 99.3 99.3 99.3 99.3 101.7 80.7 96.6 96.6 96.6 96.6 98.9 83.4 92.7 92.7 92.7 92.7 94.6 84.9  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-8 — Gross Cooling Capacities (MBH) Ton Three Phase TSC102A3, A4, AW, AK  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 96.3 82.3 106.6 62.7 112.5 41.5 89.0 78.5 103.2 60.6 110.9 40.0 81.8 74.9 96.6 57.5 107.6 38.1 74.9 71.3 87.6 55.2 102.5 35.8  
80 98.0 98.0 107.2 77.1 113.7 57.0 92.9 91.4 103.4 76.3 111.5 57.1 86.3 86.2 96.9 73.3 108.2 54.0 80.2 80.2 88.1 69.4 102.8 51.5  
85 103.9 103.9 108.1 91.7 114.8 69.6 100.1 100.1 104.3 91.7 112.4 70.0 94.3 94.3 98.3 89.5 108.6 68.9 87.6 87.6 89.9 85.7 103.1 67.1  
90 108.6 108.6 109.6 105.7 116.0 82.4 105.9 105.9 105.9 105.9 113.2 83.0 101.6 101.6 101.9 100.2 109.3 83.4 95.6 95.6 95.6 95.5 103.6 82.3  
3060  
3400  
3740  
75 98.7 87.2 107.8 65.9 113.0 42.0 91.8 83.8 104.7 63.7 111.8 40.7 84.2 80.0 98.7 60.5 108.6 38.9 76.3 76.3 89.6 58.6 103.7 36.5  
80 101.6 100.0 108.5 80.1 114.6 58.1 96.9 96.5 105.0 80.1 112.8 57.8 90.3 90.3 99.1 77.9 109.3 56.3 83.8 83.8 90.3 74.0 104.0 53.8  
85 106.8 106.8 109.6 95.7 115.8 71.4 103.6 103.6 106.2 96.7 114.0 70.7 98.7 98.7 100.9 95.5 109.8 71.7 91.7 91.7 91.7 91.7 104.3 70.7  
90 111.0 111.0 111.0 111.0 117.0 84.9 108.8 108.8 108.9 107.2 114.4 86.1 105.1 105.1 105.0 104.8 110.7 87.4 99.8 99.8 99.7 99.7 105.2 87.1  
75 100.7 91.7 109.2 64.5 114.0 42.8 93.8 88.7 106.1 66.5 113.5 41.7 85.4 85.4 100.4 63.3 109.4 39.6 79.4 77.5 91.3 59.4 104.6 37.2  
80 104.1 103.6 109.6 82.9 115.3 59.0 100.0 100.0 106.6 84.3 113.7 59.0 94.0 94.0 100.9 82.2 109.6 60.2 87.0 87.0 92.2 78.5 105.1 56.0  
85 108.9 108.9 110.9 99.2 116.6 73.0 106.7 106.7 108.3 102.4 114.8 74.4 102.0 102.0 102.0 102.0 110.8 74.3 95.6 95.6 96.4 93.7 105.5 73.9  
90 112.8 112.8 112.8 112.8 117.8 87.2 111.8 111.8 111.8 111.2 116.0 90.0 107.7 107.7 107.7 107.7 111.9 90.9 102.9 102.9 102.9 102.9 106.6 91.4  
75 102.3 95.8 110.2 66.1 114.6 43.5 95.2 95.2 106.7 68.3 113.1 42.2 88.2 88.2 101.6 65.9 110.1 40.3 81.6 80.6 92.7 62.1 105.3 38.1  
80 106.2 106.2 110.5 85.3 115.9 59.8 102.8 102.8 107.4 86.8 114.3 60.0 97.4 97.4 102.4 86.2 111.0 58.6 89.9 89.9 94.1 82.9 105.9 58.2  
85 110.5 110.5 111.9 102.3 117.2 74.4 108.3 108.3 109.2 105.1 115.5 76.3 104.5 104.5 104.4 104.4 111.5 77.2 98.7 98.7 99.0 97.4 106.4 76.8  
90 114.2 114.2 114.2 114.2 118.5 89.3 112.7 112.7 112.7 112.7 116.8 92.7 109.7 109.7 109.7 109.7 112.9 94.2 105.2 105.2 105.2 105.2 107.8 95.4  
4080  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
22  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(10 Ton)  
Standard Efficiency  
Table PD-9 — Gross Cooling Capacities (MBH) 10 Ton Three Phase TSC120A3, A4, AW, AK  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 108.6 95.7 120.5 71.5 126.0 46.0 100.1 91.3 115.5 68.8 123.6 43.3 91.0 86.5 107.2 64.9 119.3 41.0 82.2 82.0 96.5 60.1 113.1 37.9  
80 112.8 112.8 121.2 89.2 127.5 65.7 106.3 106.3 116.1 88.1 124.8 62.8 98.5 98.5 108.2 84.5 120.1 60.5 90.5 90.5 97.8 79.7 113.6 57.4  
85 119.5 119.5 122.6 106.9 129.0 78.5 114.8 114.8 117.7 107.0 126.2 79.2 108.2 108.2 110.5 104.5 121.8 76.8 100.1 100.1 100.1 100.1 114.2 76.6  
90 124.3 124.3 124.6 123.6 130.4 93.6 121.0 121.0 121.0 121.0 127.6 95.7 116.0 116.0 116.0 116.0 122.0 95.1 109.4 109.4 109.4 109.4 115.3 94.5  
3600  
4000  
4400  
75 111.6 102.3 121.7 73.9 126.7 46.9 103.4 98.1 117.1 72.3 124.5 42.7 94.2 93.4 109.5 68.7 120.2 41.9 85.3 85.3 98.8 64.0 114.3 38.8  
80 116.7 116.7 122.6 92.7 128.2 64.5 111.1 111.1 118.0 93.0 125.7 64.2 103.4 103.4 110.8 90.4 121.4 63.2 95.0 95.0 100.6 85.8 114.9 60.3  
85 122.3 122.3 124.2 111.4 129.7 80.2 118.5 118.5 120.0 113.1 127.1 81.6 112.8 112.8 113.6 112.1 122.6 82.1 105.1 105.1 105.1 105.1 115.6 80.4  
90 126.9 126.9 126.4 126.4 131.3 96.0 123.7 123.7 123.7 123.7 128.7 99.0 119.3 119.3 119.3 119.3 124.1 100.7 113.4 113.4 113.4 113.4 117.1 100.0  
75 114.1 108.4 122.5 75.8 127.3 47.7 106.5 104.9 118.4 75.8 124.9 45.4 97.1 97.1 111.3 72.3 121.3 40.2 88.6 88.6 100.9 67.7 115.1 39.7  
80 119.5 119.5 123.8 96.1 128.9 65.5 114.7 114.7 119.5 97.3 126.3 69.2 107.7 107.7 112.9 95.9 122.2 64.9 99.0 99.0 103.1 91.7 115.8 63.2  
85 124.9 124.9 125.5 115.5 130.4 81.9 121.1 121.1 121.8 118.3 127.9 83.7 116.0 116.0 116.0 116.0 123.6 85.0 109.2 109.2 109.2 109.2 116.8 84.0  
90 127.9 127.9 128.0 128.0 132.0 98.3 126.1 126.1 125.6 125.6 129.5 101.8 121.7 121.7 121.7 121.7 125.3 104.7 116.2 116.2 116.2 116.2 118.5 104.7  
75 116.1 113.8 123.1 77.6 127.8 48.5 108.9 108.9 119.2 78.1 125.4 46.2 100.5 100.5 112.8 76.1 121.4 43.6 91.6 91.6 102.6 71.3 115.8 40.6  
80 121.4 121.4 124.5 98.6 129.4 66.4 117.3 117.3 120.8 101.1 126.9 66.5 111.1 111.1 114.6 100.9 122.9 66.4 102.5 102.5 105.4 97.5 116.5 65.7  
85 126.0 126.0 126.4 118.6 130.9 83.4 122.9 122.9 123.2 122.6 128.5 85.6 118.4 118.4 118.4 118.4 124.3 87.5 112.1 112.1 112.1 112.1 117.8 87.3  
90 129.1 129.1 129.1 129.1 132.5 100.4 127.2 127.2 126.9 126.9 130.2 104.4 124.0 124.0 123.7 123.7 126.2 108.0 118.2 118.2 118.2 118.2 119.7 108.9  
4800  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC005-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(3Ton)  
High Efficiency  
Table PD-10 — Gross Cooling Capacities (MBH) 3 Ton THC036A1, A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 34.2 29.2 39.8 22.7 43.1 15.2 31.1 27.4 37.0 21.2 41.3 14.1 28.0 25.7 33.3 19.8 39.0 12.9 24.8 24.0 29.8 18.1 36.1 11.6  
80 34.9 34.9 40.0 28.5 43.5 21.3 32.3 32.3 37.1 27.1 41.6 20.1 29.7 29.7 33.5 25.3 39.2 18.8 27.1 27.1 30.0 23.6 36.2 17.5  
1080  
1200  
1320  
85  
37.9 37.9 40.3 34.3 44.0 26.5 35.3 35.3 37.5 33.0 41.9 25.6 32.6 32.6 34.0 31.3 39.5 24.6 30.0 30.0 30.6 29.6 36.4 23.2  
90 40.5 40.5 40.9 40.0 44.5 31.7 38.4 38.4 38.4 38.4 42.3 31.0 35.7 35.7 35.7 35.7 39.7 30.3 32.9 32.9 32.9 32.9 36.7 29.0  
75 35.3 31.2 40.4 23.7 43.5 15.5 32.0 29.4 37.8 22.4 41.8 14.4 28.8 27.7 34.1 20.6 39.5 13.2 25.5 25.5 30.5 18.8 36.7 11.9  
80 36.7 36.7 40.7 30.0 44.0 21.9 33.9 33.9 38.0 28.9 42.1 20.9 31.2 31.2 34.4 27.1 39.8 19.7 28.5 28.5 30.8 25.3 36.9 18.4  
85 39.6 39.6 41.1 36.3 44.6 27.4 37.1 37.1 38.5 35.4 42.5 26.8 34.3 34.3 35.1 33.8 40.0 26.0 31.5 31.5 31.5 31.5 37.1 24.8  
90 41.9 41.9 41.9 41.9 45.1 33.0 39.9 39.9 39.9 39.9 42.9 32.6 37.6 37.6 37.6 37.6 40.4 32.1 34.7 34.7 34.7 34.7 37.4 31.1  
75 36.2 33.2 40.9 24.7 43.8 15.8 32.8 31.4 38.4 23.4 42.1 14.7 29.4 29.4 34.8 21.7 39.9 13.5 26.5 26.5 31.0 19.9 37.2 12.2  
80 38.2 38.2 41.2 31.4 44.4 22.4 35.4 35.4 38.7 30.5 42.6 21.7 32.5 32.5 35.2 28.9 40.2 20.5 29.7 29.7 31.5 27.1 37.4 19.2  
85 40.8 40.8 41.8 38.1 45.0 28.3 38.7 38.7 39.4 37.6 43.1 28.0 35.9 35.9 36.2 36.2 40.5 27.2 32.9 32.9 32.9 32.9 37.6 26.2  
90 42.9 42.9 42.9 42.9 45.6 34.2 41.1 41.1 41.1 41.1 43.4 34.0 38.9 38.9 38.9 38.9 41.0 33.8 36.3 36.3 36.3 36.3 38.1 33.1  
75  
37.1 35.1 41.3 25.5 44.1 16.1 33.6 33.3 38.9 24.4 42.4 15.0 30.4 30.4 35.5 22.8 40.2 13.8 27.5 27.5 31.5 21.0 37.5 12.5  
80 39.4 39.4 41.7 32.6 44.7 22.9 36.8 36.8 39.3 32.1 42.9 22.3 33.8 33.8 35.9 30.6 40.6 21.4 30.8 30.8 32.1 28.8 37.8 20.1  
85 41.7 41.7 42.4 39.7 45.3 29.0 39.8 39.8 40.1 39.5 43.5 29.0 37.3 37.3 37.3 37.3 40.9 28.3 34.2 34.2 34.2 34.2 38.0 27.6  
90 43.7 43.7 43.7 43.7 45.9 35.3 42.1 42.1 42.1 42.1 43.9 35.3 40.0 40.0 40.0 40.0 41.5 35.4 37.5 37.5 37.5 37.5 38.6 34.9  
1440  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
24  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(3Ton)  
High Efficiency  
Table PD-11 — Gross Cooling Capacities (MBH) 3 Ton THC036A1, A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 30.8 21.6 34.9 17.8 39.2 13.7 28.9 20.4 32.8 16.6 37.0 12.5 26.9 19.1 30.6 15.3 34.7 11.3 24.8 17.8 28.4 14.1 32.3 10.0  
80 30.9 25.0 35.0 21.2 39.3 17.2 29.0 23.8 32.9 19.9 37.1 16.0 26.9 22.5 30.8 18.7 34.8 14.8 24.9 21.1 28.6 17.4 32.4 13.5  
85 31.0 28.4 35.1 24.6 39.5 20.6 29.0 27.1 33.1 23.3 37.3 19.3 27.0 25.8 30.9 22.0 35.0 18.1 25.0 24.5 28.7 20.7 32.6 16.8  
90 31.2 31.2 35.2 27.9 39.6 23.9 29.6 29.6 33.1 26.6 37.4 22.7 28.0 28.0 31.0 25.4 35.1 21.4 26.3 26.3 28.8 24.0 32.7 20.1  
600*  
780*  
960  
75 33.1 24.8 37.3 19.7 41.8 14.5 30.9 23.5 35.0 18.5 39.3 13.2 28.8 22.2 32.6 17.1 36.7 12.0 26.5 20.8 30.2 15.8 34.1 10.7  
80 33.2 29.2 37.4 24.1 41.9 18.9 31.1 27.9 35.1 22.8 39.5 17.6 29.0 26.6 32.8 21.5 36.9 16.3 26.7 25.2 30.4 20.1 34.3 15.0  
85 33.4 33.4 37.5 28.4 42.1 23.2 31.6 31.6 35.3 27.1 39.6 21.9 29.8 29.8 32.9 25.8 37.0 20.6 27.9 27.9 30.5 24.4 34.4 19.3  
90 35.4 35.4 37.7 32.7 42.2 27.5 33.6 33.6 35.5 31.4 39.8 26.2 31.8 31.8 33.1 30.1 37.2 24.9 29.8 29.8 30.8 28.7 34.6 23.6  
75 34.6 27.8 38.9 21.5 43.4 15.1 32.4 26.5 36.5 20.2 40.9 13.8 30.1 25.1 34.0 18.9 38.1 12.6 27.7 23.7 31.4 17.5 35.3 11.2  
80 35.0 33.2 39.0 26.8 43.5 20.4 32.8 31.9 36.6 25.5 41.0 19.2 30.6 30.5 34.1 24.1 38.3 17.8 28.3 28.3 31.6 22.7 35.5 16.5  
85 36.4 36.4 39.2 32.0 43.7 25.6 34.5 34.5 36.8 30.7 41.2 24.4 32.5 32.5 34.4 29.4 38.5 23.0 30.4 30.4 31.9 28.0 35.7 21.7  
90 38.6 38.6 39.6 37.3 43.9 30.8 36.7 36.7 37.3 36.0 41.4 29.5 34.6 34.6 34.9 34.7 38.6 28.2 32.5 32.5 32.5 32.5 35.9 26.8  
75 35.5 29.7 39.7 22.9 44.1 15.4 33.2 28.4 37.2 21.6 41.6 14.2 30.8 27.0 34.6 20.3 38.8 12.9 28.4 25.6 32.0 18.9 35.9 11.6  
80 36.0 35.8 39.9 28.5 44.3 21.3 33.8 33.8 37.4 27.2 41.7 20.1 31.7 31.7 34.8 25.8 39.0 18.8 29.6 29.6 32.2 24.4 36.1 17.4  
85 38.1 38.1 40.1 34.4 44.5 27.2 36.0 36.0 37.7 33.1 41.9 25.9 33.9 33.9 35.2 31.7 39.2 24.6 31.8 31.8 32.6 30.3 36.3 23.2  
90 40.4 40.4 40.8 40.4 44.7 33.0 38.3 38.3 38.3 38.3 42.1 31.7 36.2 36.2 36.2 36.2 39.4 30.4 34.0 34.0 33.9 33.9 36.5 29.0  
1080  
1200  
75 36.2 31.6 40.4 23.7 44.8 15.7 33.8 30.2 37.8 22.4 42.2 14.5 31.4 28.8 35.2 21.0 39.4 13.2 29.0 27.4 32.5 19.6 36.4 11.9  
80  
37.1 37.1 40.6 30.2 45.0 22.3 35.0 35.0 38.0 28.8 42.3 21.0 32.9 32.9 35.4 27.5 39.6 19.7 30.7 30.7 32.7 26.1 36.6 18.3  
85 39.5 39.5 41.0 36.7 45.1 28.7 37.4 37.4 38.4 35.4 42.5 27.4 35.2 35.2 35.9 34.0 39.8 26.1 33.0 33.0 33.3 32.7 36.8 24.7  
90 42.0 42.0 42.0 42.0 45.4 35.1 39.8 39.8 39.8 39.8 42.8 33.8 37.5 37.5 37.5 37.5 40.1 32.5 35.2 35.2 35.2 35.2 37.1 31.1  
75 36.8 33.4 40.9 24.8 45.3 16.1 34.4 32.1 38.3 23.4 42.6 14.8 32.0 30.7 35.6 22.0 39.9 13.5 29.6 29.3 32.9 20.6 36.9 12.2  
80 38.3 38.3 41.2 31.9 45.5 23.1 36.1 36.1 38.6 30.5 42.8 21.9 33.9 33.9 35.9 29.1 40.0 20.6 31.7 31.7 33.2 27.7 37.1 19.2  
85 40.8 40.8 41.7 39.0 45.7 30.2 38.6 38.6 39.2 37.7 43.0 28.9 36.3 36.3 36.6 36.3 40.2 27.5 34.0 34.0 34.0 34.0 37.3 26.2  
90 43.3 43.3 43.3 43.3 46.0 37.1 41.1 41.1 41.1 41.1 43.3 35.9 38.8 38.8 38.8 38.8 40.6 34.6 36.3 36.3 36.3 36.3 37.7 33.2  
1320  
75  
37.4 35.2 41.4 25.8 45.8 16.4 35.0 33.9 38.7 24.4 43.0 15.1 32.6 32.5 36.0 23.0 40.2 13.8 30.1 30.1 33.2 21.6 37.2 12.5  
80 39.3 39.3 41.7 33.5 46.0 24.0 37.1 37.1 39.1 32.1 43.2 22.7 34.8 34.8 36.4 30.7 40.4 21.4 32.5 32.5 33.6 29.3 37.4 20.0  
85 41.9 41.9 42.4 41.3 46.1 31.6 39.7 39.7 39.6 39.6 43.4 30.3 37.3 37.3 37.3 37.3 40.6 29.0 34.9 34.9 34.9 34.9 37.7 27.6  
90 44.4 44.4 44.4 44.4 46.5 39.2 42.2 42.2 42.2 42.2 43.8 37.9 39.8 39.8 39.8 39.8 41.1 36.6 37.3 37.3 37.3 37.3 38.2 35.3  
1440  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unitapplicationsbelow960CFM  
Electricheatersrestrictedonapplicationsbelow960CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 960 CFM.  
RT-PRC005-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(4Ton)  
High Efficiency  
Table PD-12 — Gross Cooling Capacities (MBH) 4 Ton THC048A1, A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 45.3 39.9 51.4 30.3 54.9 19.9 41.1 37.7 48.4 28.8 53.1 18.7 37.1 35.6 43.9 26.7 51.0 17.4 33.2 33.2 39.3 24.6 47.8 16.0  
80  
47.1 47.1 52.0 38.4 55.5 28.1 43.8 43.8 48.7 36.9 54.6 27.2 40.3 40.3 44.3 34.9 51.3 25.6 36.9 36.9 39.8 32.8 47.9 24.1  
1440  
1600  
1760  
85 50.5 50.5 52.5 46.3 56.2 34.5 47.8 47.8 49.4 45.2 54.9 34.9 44.3 44.3 45.3 43.3 51.6 33.6 40.9 40.9 40.9 40.9 48.1 32.2  
90 53.1 53.1 53.5 53.5 56.9 41.4 51.2 51.2 51.2 51.2 54.6 41.4 48.4 48.4 48.4 48.4 52.0 41.2 45.0 45.0 45.0 45.0 48.6 40.2  
75 46.7 42.7 52.7 31.9 55.2 20.2 42.4 40.5 49.4 30.3 54.4 19.3 38.2 38.2 45.0 28.4 51.6 17.8 34.7 34.7 40.2 26.2 48.6 16.4  
80 49.2 49.2 52.8 40.4 55.9 28.2 46.0 46.0 49.8 39.4 55.2 28.4 42.3 42.3 45.6 37.5 51.9 26.9 38.7 38.7 40.9 35.3 48.7 25.4  
85 52.1 52.1 53.5 48.8 56.6 35.4 49.9 49.9 50.6 48.3 55.7 36.8 46.7 46.7 47.0 46.8 52.2 35.2 43.0 43.0 42.9 42.9 49.0 34.3  
90 54.5 54.5 54.8 54.8 57.4 42.7 52.8 52.8 52.8 52.8 55.2 42.9 50.5 50.5 50.5 50.5 52.9 43.5 47.4 47.4 47.4 47.4 49.6 43.0  
75  
47.8 45.4 53.2 33.4 55.5 20.6 43.7 43.3 50.1 31.8 54.7 19.6 39.7 39.7 46.0 30.0 51.9 18.2 36.1 36.1 41.0 27.7 49.1 16.8  
80 50.6 50.6 53.4 42.1 56.2 28.7 47.8 47.8 50.5 41.5 55.7 29.4 44.1 44.1 46.7 39.9 52.4 28.1 40.4 40.4 41.9 37.8 49.3 26.7  
85 53.1 53.1 54.2 50.9 57.0 36.2 51.4 51.4 51.6 51.0 56.2 38.0 48.6 48.6 48.6 48.6 52.8 36.7 44.9 44.9 44.9 44.9 49.7 36.3  
90 55.1 55.1 55.7 55.7 57.7 43.8 53.9 53.9 53.9 53.9 55.6 44.3 51.9 51.9 51.9 51.9 53.5 45.6 49.2 49.2 49.2 49.2 50.5 45.7  
75 48.8 48.1 53.6 34.4 55.7 20.9 45.0 45.0 50.6 33.2 55.0 20.0 41.0 41.0 46.8 31.5 52.3 18.5 37.3 37.3 41.7 29.3 49.6 17.2  
80 51.7 51.7 53.9 43.5 56.4 31.7 49.3 49.3 51.2 43.5 56.0 30.1 45.8 45.8 47.6 42.3 52.8 28.9 41.8 41.8 42.8 40.2 49.8 27.9  
85 53.9 53.9 54.8 52.7 57.2 36.9 52.4 52.4 52.4 52.4 56.5 39.1 50.0 50.0 50.0 50.0 53.2 38.1 46.6 46.6 46.6 46.6 50.3 38.1  
90 55.7 55.7 56.3 56.3 58.0 44.8 54.7 54.7 54.7 54.7 56.0 45.6 53.0 53.0 53.0 53.0 54.0 47.4 50.5 50.5 50.5 50.5 51.2 48.1  
1920  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
26  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(4Ton)  
High Efficiency  
Table PD-13 — Gross Cooling Capacities (MBH) 4 Ton THC048A1, A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 40.4 29.1 45.7 23.7 51.3 18.2 38.2 27.7 43.3 22.4 48.8 16.9 35.8 26.3 40.6 20.9 45.9 15.4 33.3 24.8 38.0 19.5 43.1 14.0  
80 40.5 33.8 45.8 28.4 51.5 22.8 38.3 32.4 43.4 27.0 48.9 21.5 35.9 31.0 40.8 25.5 46.0 20.0 33.4 29.5 38.1 24.1 43.2 18.6  
85 40.8 38.5 45.9 33.1 51.6 27.5 38.5 37.1 43.5 31.7 49.0 26.1 36.2 35.7 40.8 30.2 46.1 24.6 33.9 33.9 38.2 28.7 43.3 23.2  
90 42.0 42.0 46.1 37.7 51.7 32.1 40.1 40.1 43.7 36.3 49.1 30.7 38.1 38.1 41.0 34.8 46.2 29.2 36.1 36.1 38.4 33.3 43.4 27.8  
800*  
1040*  
1280  
75 43.3 33.5 48.8 26.4 54.6 19.2 40.8 32.1 46.2 25.0 51.8 17.8 38.2 30.6 43.2 23.5 48.6 16.3 35.5 29.1 40.4 22.0 45.5 14.9  
80 43.6 39.6 48.9 32.4 54.7 25.1 41.1 38.2 46.3 31.0 51.9 23.8 38.6 36.7 43.3 29.5 48.7 22.3 36.0 35.2 40.5 28.0 45.7 20.8  
85 44.7 44.7 49.1 38.4 54.9 31.1 42.6 42.6 46.5 37.0 52.1 29.7 40.4 40.4 43.6 35.4 48.8 28.2 38.2 38.2 40.7 33.9 45.8 26.7  
90  
47.3 47.3 49.4 44.4 55.0 37.0 45.2 45.2 46.8 42.9 52.2 35.6 43.0 43.0 44.0 41.4 49.0 34.0 40.7 40.7 41.2 39.9 46.0 32.6  
75 45.3 37.7 50.8 28.9 56.7 20.0 42.7 36.2 48.0 27.5 53.8 18.6 40.0 34.7 44.9 25.9 50.3 17.0 37.2 33.1 41.9 24.4 47.1 15.6  
80 46.0 45.1 51.0 36.2 56.9 27.3 43.4 43.4 48.2 34.7 53.9 25.9 41.1 41.1 45.1 33.1 50.5 24.3 38.7 38.7 42.1 31.6 47.3 22.9  
85 48.5 48.5 51.3 43.5 57.0 34.5 46.2 46.2 48.6 42.0 54.1 33.1 43.9 43.9 45.5 40.4 50.6 31.5 41.4 41.4 42.6 38.9 47.5 30.0  
90 51.4 51.4 52.1 50.8 57.3 41.7 49.1 49.1 49.5 49.4 54.3 40.3 46.7 46.7 46.7 46.7 50.9 38.7 44.2 44.2 44.2 44.2 47.7 37.2  
75 46.3 40.3 51.5 30.3 57.4 20.3 43.7 38.8 48.7 28.9 54.3 18.9 41.0 37.3 45.7 27.4 51.2 17.5 38.1 35.8 42.7 25.9 47.9 16.0  
80  
47.6 47.6 51.8 38.5 57.6 28.5 45.2 45.2 49.0 37.0 54.5 27.1 42.8 42.8 46.0 35.5 51.3 25.6 40.3 40.3 43.0 34.0 48.1 24.2  
1440  
1600  
85 50.6 50.6 52.3 46.6 57.7 36.5 48.2 48.2 49.5 45.2 54.7 35.1 45.7 45.7 46.6 43.7 51.5 33.7 43.2 43.2 43.7 42.2 48.3 32.2  
90 53.6 53.6 53.6 53.6 58.1 44.6 51.2 51.2 51.2 51.2 55.0 43.2 48.7 48.7 48.7 48.7 51.9 41.7 46.1 46.1 46.1 46.1 48.7 40.2  
75  
47.3 42.9 52.4 31.8 58.2 20.7 44.6 41.4 49.4 30.4 55.1 19.3 41.8 39.9 46.4 28.9 51.9 17.9 39.0 38.4 43.3 27.4 48.6 16.4  
80 49.2 49.2 52.7 40.9 58.4 29.8 46.8 46.8 49.8 39.4 55.3 28.4 44.3 44.3 46.8 37.9 52.0 26.9 41.7 41.7 43.7 36.4 48.7 25.4  
85 52.4 52.4 53.4 49.9 58.6 38.7 49.9 49.9 50.6 48.5 55.5 37.3 47.4 47.4 47.7 47.0 52.3 35.8 44.7 44.7 44.7 44.7 49.0 34.3  
90 55.6 55.6 55.6 55.6 59.1 47.6 53.1 53.1 53.1 53.1 56.0 46.2 50.4 50.4 50.4 50.4 52.8 44.7 47.7 47.7 47.7 47.7 49.5 43.2  
75 48.2 45.5 53.0 33.3 59.0 21.2 45.5 44.0 50.1 31.8 55.8 19.8 42.7 42.5 47.0 30.3 52.5 18.3 39.9 39.9 43.8 28.8 49.1 16.8  
80 50.7 50.7 53.5 43.2 59.1 31.1 48.2 48.2 50.5 41.7 55.9 29.6 45.6 45.6 47.5 40.2 52.6 28.2 42.9 42.9 44.4 38.7 49.3 26.7  
85 54.0 54.0 54.4 53.1 59.4 40.8 51.4 51.4 51.4 51.4 56.2 39.4 48.8 48.8 48.8 48.8 52.9 37.9 46.0 46.0 46.0 46.0 49.6 36.4  
1760  
90  
57.3 57.3 57.3 57.3 59.9 50.5 54.7 54.7 54.7 54.7 56.8 49.1 52.0 52.0 52.0 52.0 53.6 47.6 49.2 49.2 49.2 49.2 50.3 46.1  
75 49.0 48.1 53.6 34.7 59.6 21.6 46.1 46.1 50.6 33.3 56.3 20.2 43.6 43.6 47.5 31.8 53.0 18.7 40.9 40.9 44.3 30.2 49.5 17.2  
80 52.0 52.0 54.2 45.4 59.7 32.3 49.4 49.4 51.2 44.0 56.5 30.9 46.8 46.8 48.1 42.5 53.2 29.4 44.0 44.0 45.0 41.0 49.7 27.9  
85 55.4 55.4 55.3 55.3 60.0 42.9 52.7 52.7 52.7 52.7 56.9 41.5 50.0 50.0 50.0 50.0 53.5 40.0 47.2 47.2 47.2 47.2 50.1 38.5  
90 58.8 58.8 58.8 58.8 60.7 53.4 56.1 56.1 56.1 56.1 57.6 52.0 53.3 53.3 53.3 53.3 54.4 50.6 50.4 50.4 50.4 50.4 51.0 49.1  
1920  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unitapplicationsbelow1280CFM  
Electricheatersrestrictedonapplicationsbelow1280CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 1280 CFM.  
RT-PRC005-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(5Ton)  
High Efficiency  
Table PD-14 — Gross Cooling Capacities (MBH) 5 Ton Single Phase THC060A1– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 56.2 48.2 64.3 37.8 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1  
80  
57.6 57.6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67.3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6  
1800  
2000  
2200  
85 62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0  
90 65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5  
75  
80 60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47.6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1  
85 64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57.1 57.1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5  
90  
75 59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 67.7 24.3 49.6 49.4 57.6 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1  
80 62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47.9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5  
85 66.0 66.0 67.3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7  
90 68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6  
75 60.6 57.4 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5  
80 64.0 64.0 67.0 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8  
57.8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37.0 67.3 23.9 48.2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7  
67.6 67.6 67.6 67.6 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8  
2400  
85  
67.2 67.2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67.0 46.8 57.2 57.2 57.2 57.2 62.9 45.6  
90 69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57.1 65.5 65.5 65.5 65.5 67.5 57.3 62.2 62.2 62.2 62.2 63.9 57.2  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-15 — Gross Cooling Capacities (MBH) 5Ton Three Phase THC060A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73 61  
CFM  
Bulb  
61  
67  
73  
61  
67  
67  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 56.6 49.0 64.4 37.5 67.7 24.7 52.0 46.8 60.9 35.7 66.2 23.3 47.0 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0  
80 58.5 58.5 64.6 47.0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8  
85 62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 67.7 42.3 55.6 55.6 57.3 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5  
90 66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1  
1800  
2000  
2200  
75 58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 37.6 66.6 23.8 48.6 47.7 57.2 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5  
80 61.1 61.1 65.6 49.2 69.0 34.6 57.3 57.3 62.4 48.4 67.5 34.8 53.2 53.2 57.8 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4  
85 64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 67.8 43.0 58.4 58.4 59.2 57.5 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0  
90  
67.7 67.7 67.7 67.7 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3  
75 59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 67.0 24.2 50.0 50.0 58.3 37.3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0  
80 63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 67.9 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9  
85 66.4 66.4 67.2 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 44.2  
90 68.7 68.7 68.7 68.7 71.2 52.8 67.1 67.1 67.1 67.1 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 61.0 61.0 61.0 61.0 62.9 55.3  
75 61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 67.3 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47.2 47.2 53.4 36.6 61.7 21.4  
80 64.5 64.5 67.0 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 57.5 57.5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3  
2400  
85  
67.3 67.3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 62.6 46.2  
90 69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67.6 58.0 62.5 62.5 62.5 62.5 63.7 57.9  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
28  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(5Ton)  
High Efficiency  
Table PD-16 — Gross Cooling Capacities (MBH) 5Ton THC060A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 50.7 36.2 57.0 29.4 63.7 22.6 48.1 34.6 54.2 27.9 60.7 21.0 45.5 32.9 51.3 26.2 57.5 19.4 42.7 31.2 48.2 24.5 54.1 17.7  
80 50.8 41.8 57.1 35.1 63.8 28.2 48.3 40.2 54.4 33.5 60.8 26.6 45.6 38.6 51.5 31.9 57.6 25.0 42.9 36.8 48.4 30.1 54.2 23.3  
85 51.0 47.5 57.2 40.7 64.0 33.8 48.6 45.9 54.5 39.1 61.0 32.2 46.0 44.2 51.6 37.4 57.8 30.6 43.3 42.5 48.5 35.7 54.4 28.8  
90 52.2 52.2 57.4 46.3 64.1 39.4 50.1 50.1 54.6 44.7 61.1 37.8 47.8 47.8 51.7 43.0 57.9 36.1 45.5 45.5 48.7 41.3 54.5 34.4  
1000*  
1300*  
1600  
75 54.3 41.5 60.7 32.7 67.6 23.8 51.5 39.9 57.7 31.0 64.3 22.1 48.6 38.1 54.5 29.3 60.8 20.4 45.5 36.4 51.1 27.5 57.0 18.7  
80 54.6 48.8 60.9 40.0 67.8 31.0 51.9 47.1 57.9 38.3 64.5 29.3 49.0 45.4 54.7 36.6 60.9 27.6 46.0 43.6 51.3 34.8 57.2 25.9  
85 55.6 55.6 61.1 47.2 67.9 38.2 53.2 53.2 58.1 45.5 64.6 36.5 50.7 50.7 54.9 43.7 61.1 34.8 48.1 48.1 51.5 41.9 57.4 33.0  
90 58.8 58.8 61.5 54.4 68.1 45.3 56.3 56.3 58.5 52.7 64.8 43.6 53.7 53.7 55.3 50.9 61.3 41.9 51.0 51.0 52.0 49.1 57.5 40.1  
75 56.8 46.5 63.2 35.6 70.2 24.7 53.9 44.9 60.0 33.9 66.6 23.0 50.8 43.1 56.6 32.2 62.9 21.3 47.5 41.3 53.0 30.4 58.9 19.5  
80  
57.6 55.5 63.4 44.5 70.3 33.5 54.7 53.8 60.2 42.7 66.8 31.8 51.6 51.6 56.8 41.0 63.0 30.1 48.8 48.8 53.2 39.1 59.1 28.3  
85 60.3 60.3 63.8 53.2 70.5 42.2 57.7 57.7 60.6 51.5 67.0 40.5 54.9 54.9 57.3 49.7 63.2 38.8 52.0 52.0 53.7 47.9 59.3 36.9  
90 63.8 63.8 64.7 62.1 70.8 50.9 61.1 61.1 61.6 60.4 67.3 49.2 58.2 58.2 58.2 58.2 63.5 47.4 55.1 55.1 55.1 55.1 59.6 45.6  
75 58.1 49.6 64.5 37.5 71.4 25.2 55.1 48.2 61.1 35.8 67.8 23.5 51.9 46.3 57.6 34.0 63.9 21.8 48.6 44.5 53.9 32.2 59.8 20.0  
80 59.3 59.3 64.7 47.4 71.6 35.1 56.6 56.6 61.4 45.6 67.9 33.4 53.8 53.8 57.9 43.8 64.1 31.6 50.8 50.8 54.2 42.0 60.0 29.8  
85 62.9 62.9 65.3 57.2 71.8 44.9 60.1 60.1 62.0 55.4 68.2 43.1 57.2 57.2 58.6 53.6 64.3 41.3 54.1 54.1 55.0 51.8 60.2 39.5  
90 66.5 66.5 66.5 66.5 72.2 54.6 63.7 63.7 63.7 63.7 68.5 52.9 60.6 60.6 60.6 60.6 64.7 51.0 57.4 57.4 57.4 57.4 60.7 49.1  
1800  
2000  
75 59.3 51.6 65.9 38.8 73.0 25.8 55.9 49.6 62.1 36.9 69.0 23.9 52.3 47.6 58.3 34.8 64.9 22.0 48.7 45.5 54.4 32.8 60.8 20.1  
80 60.9 60.9 66.1 49.3 73.2 36.4 57.9 57.9 3.0 47.3 69.2 34.5 54.7 54.7 58.6 45.3 65.2 32.5 51.4 51.4 54.7 43.2 61.0 30.5  
85 64.8 64.8 66.9 59.8 73.5 46.9 61.6 61.6 63.2 57.8 69.5 44.9 58.4 58.4 59.5 55.8 65.4 42.9 55.0 55.0 55.7 53.8 61.3 40.9  
90 68.6 68.6 68.6 68.6 73.8 57.1 65.4 65.4 65.3 65.3 69.9 55.1 62.1 62.1 62.0 62.0 65.9 53.2 58.7 58.7 58.7 58.7 61.8 51.2  
75 60.4 54.5 66.7 40.5 73.8 26.4 56.9 52.4 62.9 38.5 69.8 24.5 53.3 50.4 59.0 36.5 65.7 22.5 49.6 48.3 55.1 34.4 61.5 20.5  
80 62.7 62.7 67.1 51.8 74.1 37.8 59.5 59.5 63.3 49.8 70.0 35.9 56.3 56.3 59.4 47.8 65.9 33.9 52.9 52.9 55.5 45.8 61.7 31.9  
85 66.7 66.7 68.0 63.3 74.4 49.2 63.4 63.4 64.3 61.3 70.3 47.2 60.1 60.1 60.6 59.3 66.2 45.2 56.7 56.7 56.6 56.6 62.0 43.2  
90 70.6 70.6 70.6 70.6 74.9 60.3 67.3 67.3 67.3 67.3 70.8 58.3 63.9 63.9 63.9 63.9 66.8 56.4 60.4 60.4 60.4 60.4 62.7 54.4  
2200  
75 61.3 57.2 67.5 42.1 74.6 26.9 57.8 55.2 63.6 40.1 70.5 24.9 54.2 53.2 59.7 38.0 66.3 22.9 50.4 50.4 55.7 36.0 62.1 21.0  
80 64.3 64.3 67.9 54.3 74.9 39.2 61.0 61.0 64.1 52.3 70.7 37.2 57.7 57.7 60.2 50.3 66.6 35.2 54.2 54.2 56.2 48.2 62.3 33.2  
85 68.4 68.4 69.1 66.7 75.1 51.4 65.0 65.0 65.4 64.8 71.0 49.4 61.6 61.6 61.6 61.6 66.8 47.4 58.1 58.1 58.1 58.1 62.6 45.4  
90 72.4 72.4 72.4 72.4 75.8 63.5 69.0 69.0 69.0 69.0 71.7 61.5 65.5 65.5 65.5 65.5 67.6 59.5 61.9 61.9 61.9 61.9 63.5 57.5  
2400  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unitapplicationsbelow1600CFM  
Electricheatersrestrictedonapplicationsbelow1600CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 1600 CFM.  
RT-PRC005-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(6Ton)  
High Efficiency  
Performance  
Data  
Table PD-17 — Gross Cooling Capacities (MBH) 6Ton Three Phase THC072A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73  
CFM  
61  
67  
73  
61  
67  
61  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 67.3 56.6 73.6 42.5 74.5 27.6 61.6 53.5 71.8 41.9 75.1 26.6 55.8 50.4 66.8 38.7 74.1 25.3 49.8 47.2 59.9 36.3 71.3 23.5  
80 68.7 68.2 73.8 51.7 75.4 37.0 63.6 63.6 72.0 52.1 76.0 38.1 58.9 58.9 66.9 49.7 74.7 36.4 54.1 54.1 60.2 46.5 71.5 34.5  
85 72.2 72.2 74.5 61.4 76.2 44.5 69.2 69.2 72.5 62.8 76.8 46.1 64.6 64.6 67.8 60.9 75.0 46.2 59.5 59.5 61.3 57.7 71.7 45.4  
90 74.7 74.7 75.3 70.6 77.0 51.9 73.4 73.4 73.7 73.2 77.7 55.1 70.1 70.1 70.1 70.1 75.6 56.1 65.4 65.4 65.4 65.4 72.1 55.8  
75 69.0 60.1 74.0 43.3 74.5 27.9 63.5 57.2 72.7 43.1 75.2 27.0 57.5 54.0 68.4 40.9 74.5 25.7 51.8 51.0 61.5 37.6 72.0 24.0  
80 70.7 70.7 74.3 52.9 75.4 37.2 66.8 66.8 73.0 54.6 76.2 37.8 61.9 61.9 68.7 53.0 75.1 37.4 56.7 56.7 61.9 49.8 72.4 36.1  
85 73.8 73.8 75.0 63.0 76.2 44.9 71.9 71.9 73.8 66.0 77.1 47.0 67.9 67.9 69.7 65.4 75.5 47.5 62.7 62.7 63.6 62.4 72.6 47.7  
90 75.6 75.6 75.9 72.4 77.0 52.5 75.2 75.2 75.1 75.1 78.0 56.3 72.8 72.8 72.7 72.7 76.4 58.2 68.8 68.8 68.8 68.8 73.2 59.0  
75 70.3 63.2 74.2 43.9 74.6 28.3 65.2 60.8 73.2 44.5 75.4 27.4 59.2 57.7 69.6 42.9 74.7 26.2 53.2 53.2 62.9 39.8 72.5 24.6  
80 72.3 72.3 74.5 53.9 75.4 37.4 69.5 69.5 73.8 56.7 76.3 38.2 64.6 64.6 70.0 56.1 75.6 38.5 59.2 59.2 63.5 53.0 73.0 37.7  
85 74.7 74.7 75.3 64.3 76.2 45.2 73.7 73.7 74.7 68.7 77.3 47.6 70.5 70.5 71.3 69.3 76.1 48.9 65.6 65.6 65.6 65.6 73.4 49.7  
90 76.1 76.1 76.2 73.6 76.9 53.0 76.2 76.2 76.2 76.2 78.1 57.2 74.5 74.5 74.5 74.5 76.9 59.9 71.2 71.2 71.2 71.2 74.1 61.7  
75 71.3 65.8 74.3 44.4 74.6 28.7 66.8 64.4 73.7 45.6 75.5 27.8 60.5 60.5 70.6 44.8 74.9 26.6 55.1 55.1 64.1 41.8 72.9 25.0  
80 73.3 73.3 74.7 54.8 75.4 37.6 71.4 71.4 74.4 58.5 76.4 38.5 67.0 67.0 71.0 58.9 75.9 39.1 61.4 61.4 64.9 56.2 73.3 38.6  
85 75.1 75.1 75.5 65.3 76.2 45.6 74.8 74.8 75.4 70.8 77.4 48.2 72.4 72.4 72.4 72.4 76.4 49.9 68.2 68.2 68.1 68.1 74.0 51.5  
90 76.3 76.3 76.3 74.5 76.9 53.5 76.9 76.9 76.9 76.9 78.2 58.0 75.7 75.7 75.7 75.7 77.2 61.3 72.9 72.9 72.9 72.9 74.8 64.1  
2160  
2400  
2640  
2880  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
30  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(7½Ton)  
High Efficiency  
Performance  
Data  
Table PD-18 — Gross Cooling Capacities (MBH) Ton Three Phase THC092A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73  
CFM  
61  
67  
73  
61  
67  
61  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 85.7 72.4 95.8 56.8 99.9 37.1 79.3 69.3 92.0 53.7 98.8 35.8 72.8 66.0 85.9 50.8 96.1 34.2 66.1 62.6 78.5 49.1 91.8 32.2  
80  
87.5 87.0 96.2 68.5 101.1 50.4 81.8 81.8 92.4 67.4 99.6 50.2 76.6 76.6 86.2 64.6 96.7 48.0 71.1 71.1 79.0 61.4 92.0 45.8  
2700  
3000  
3300  
85 92.8 92.8 97.0 81.6 102.3 61.3 88.5 88.5 93.1 81.1 100.3 61.3 83.4 83.4 87.1 78.6 97.0 60.9 77.9 77.9 80.3 75.4 92.3 59.4  
90  
75  
80 90.5 90.5 97.4 71.2 101.6 51.1 85.6 85.6 94.0 71.0 100.4 50.9 80.2 80.2 88.2 68.7 97.3 49.8 74.5 74.5 81.0 65.5 93.2 47.9  
85 95.6 95.6 98.4 85.1 102.9 62.5 92.2 92.2 95.0 85.8 101.3 63.3 87.3 87.3 89.5 84.1 98.1 63.3 81.8 81.8 82.9 81.2 93.6 62.5  
90 99.4 99.4 99.9 98.1 104.1 74.1 97.2 97.2 97.2 97.2 102.1 75.5 93.6 93.6 93.5 93.5 99.1 77.0 88.8 88.8 88.7 88.7 94.4 76.9  
75 89.8 81.3 97.5 59.0 100.7 38.1 83.6 78.2 94.6 58.3 99.8 37.1 77.0 75.0 89.2 55.9 97.5 35.4 70.0 70.0 82.1 52.8 93.6 33.4  
80 93.2 93.2 98.3 73.5 102.0 51.7 88.9 88.9 95.2 74.2 101.0 52.0 83.4 83.4 89.8 72.6 97.9 50.6 77.6 77.6 82.8 69.5 94.1 49.9  
97.2 97.2 98.3 94.2 103.5 72.4 94.3 94.3 94.3 94.3 101.1 73.1 90.0 90.0 90.0 90.0 97.8 73.7 84.9 84.9 84.9 84.9 92.9 72.7  
87.9 77.0 96.6 57.3 100.4 37.6 81.5 73.7 93.5 56.1 99.4 36.4 74.9 70.5 87.8 53.4 96.9 34.8 67.4 67.4 80.5 50.2 92.8 32.8  
85  
97.6 97.6 99.4 88.0 103.3 67.9 94.9 94.9 96.5 90.0 101.9 64.8 90.5 90.5 91.7 89.4 99.0 67.3 85.2 85.2 85.1 85.1 94.7 65.2  
90 100.9 100.9 100.9 100.9 104.6 75.6 99.2 99.2 99.2 99.2 102.8 77.7 96.1 96.1 96.1 96.1 100.1 80.0 91.8 91.8 91.8 91.8 95.7 80.7  
75 91.5 85.3 98.2 60.6 101.0 38.6 85.5 82.6 95.4 60.2 100.2 37.5 78.5 78.5 90.5 58.3 98.0 35.9 72.4 72.4 83.4 55.2 94.3 34.0  
80 95.2 95.2 99.0 75.4 102.3 56.8 91.5 91.5 96.3 77.2 101.5 52.7 86.3 86.3 91.3 76.3 98.4 51.4 80.4 80.4 84.4 73.4 94.7 51.4  
85 99.1 99.1 100.2 90.6 103.6 69.8 96.9 96.9 97.8 93.6 102.4 66.1 93.1 93.1 93.1 93.1 99.7 69.8 88.0 88.0 87.9 87.9 95.6 67.8  
90 101.9 101.9 101.9 101.9 105.0 76.9 100.7 100.7 100.7 100.7 103.4 79.6 98.0 98.0 97.9 97.9 100.8 82.5 94.0 94.0 94.0 94.0 96.7 84.1  
3600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC005-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(7½Ton)  
High Efficiency  
Table PD-19 — Gross Cooling Capacities (MBH) Ton Three Phase THC092A3, A4, AW – Dehumidification (Hot Gas Reheat)  
or TXV Option  
AmbientTemperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 76.3 54.5 85.6 45.2 95.8 34.8 72.9 52.4 81.9 43.2 91.7 32.8 69.2 50.2 77.9 41.1 87.3 30.8 65.3 48.0 73.7 38.9 82.8 28.6  
80 76.5 62.6 85.8 53.0 95.9 43.1 73.0 60.5 82.0 50.9 91.8 41.1 69.3 58.3 78.0 48.7 87.4 39.0 65.4 56.0 73.8 46.5 82.9 36.8  
85 76.6 70.6 85.9 61.0 96.0 51.1 73.1 68.4 82.1 58.9 91.9 49.0 69.4 66.2 78.1 56.7 87.5 46.9 65.6 63.8 73.9 54.4 83.0 44.7  
1500*  
1950*  
2400  
90  
77.3 77.3 86.1 69.0 96.1 59.0 74.5 74.5 82.3 66.9 92.0 57.0 71.5 71.5 78.3 64.6 87.7 54.8 68.3 68.3 74.0 62.3 83.1 52.6  
75 81.6 61.9 91.2 49.4 101.6 36.5 77.7 59.7 87.0 47.2 97.1 34.5 73.7 57.5 82.6 45.0 92.3 32.3 69.4 55.1 78.0 42.7 87.3 30.1  
80 81.9 72.2 91.3 59.6 101.7 47.0 78.1 70.0 87.2 57.5 97.2 44.8 74.0 67.7 82.8 55.2 92.4 42.6 69.8 65.4 78.2 52.9 87.4 40.4  
85 82.3 82.3 91.6 69.9 101.9 57.1 79.2 79.2 87.4 67.7 97.3 55.0 75.8 75.8 83.0 65.4 92.6 52.8 72.3 72.3 78.4 63.1 87.6 50.5  
90 86.9 86.9 91.9 80.0 102.0 67.2 83.6 83.6 87.8 77.8 97.5 65.1 80.2 80.2 83.4 75.5 92.7 62.8 76.5 76.5 78.9 73.2 87.8 60.6  
75 85.2 68.7 94.9 53.4 105.5 37.9 81.1 66.5 90.5 51.2 100.7 35.8 76.8 64.2 85.8 48.9 95.6 33.6 72.3 61.8 80.9 46.6 90.3 31.4  
80 86.0 81.3 95.1 65.8 105.6 50.4 82.0 79.1 90.7 63.6 100.8 48.2 77.9 76.9 86.0 61.4 95.7 46.0 73.4 73.4 81.2 59.0 90.4 43.7  
85 89.2 89.2 95.5 78.2 105.8 62.7 85.7 85.7 91.1 76.0 101.0 60.5 82.0 82.0 86.5 73.7 95.9 58.2 78.1 78.1 81.6 71.3 90.6 55.9  
90 94.2 94.2 96.4 90.6 106.1 74.9 90.6 90.6 92.1 88.4 101.3 72.8 86.8 86.8 87.6 86.2 96.2 70.4 82.8 82.8 82.8 82.8 90.9 68.1  
75  
87.1 73.0 96.8 57.3 107.4 38.7 82.9 70.9 92.2 55.1 102.5 36.6 78.5 68.6 87.4 52.9 97.2 34.4 73.9 66.2 82.3 50.6 91.8 32.2  
80 88.4 87.3 97.0 69.7 107.6 52.5 84.2 84.2 92.5 67.5 102.6 50.4 80.4 80.4 87.7 65.2 97.4 48.1 76.4 76.4 82.7 62.8 91.9 45.8  
85 92.9 92.9 97.6 83.5 107.8 66.2 89.3 89.3 93.1 81.3 102.8 64.0 85.4 85.4 88.4 79.0 97.6 61.8 81.3 81.3 83.4 76.7 92.1 59.4  
90 98.2 98.2 99.1 97.6 108.1 79.8 94.4 94.4 94.4 94.4 103.2 77.6 90.4 90.4 90.4 90.4 98.0 75.3 86.2 86.2 86.2 86.2 92.5 73.0  
2700  
3000  
75 88.7 77.2 98.3 58.4 109.0 39.5 84.5 75.0 93.6 56.1 103.9 37.3 80.0 72.7 88.7 53.8 98.6 35.1 75.3 70.3 83.5 51.4 93.0 32.8  
80 90.8 90.8 98.7 73.5 109.2 54.6 87.0 87.0 94.0 71.3 104.1 52.4 83.1 83.1 89.1 69.0 98.8 50.2 78.9 78.9 84.0 66.6 93.2 47.9  
85 96.2 96.2 99.5 88.8 109.5 69.7 92.4 92.4 94.9 86.6 104.4 67.5 88.3 88.3 90.1 84.3 99.0 65.2 84.0 84.0 85.1 81.9 93.4 62.9  
90 101.7 101.7 101.7 101.7 109.9 84.6 97.8 97.7 97.7 97.7 104.8 82.4 93.6 93.6 93.5 93.5 99.5 80.2 89.1 89.1 89.1 89.1 93.9 77.8  
75 90.2 81.4 99.7 60.7 110.4 40.1 85.9 79.1 94.8 58.5 105.2 37.9 81.4 76.8 89.8 56.1 99.7 35.7 76.7 74.4 84.6 53.8 94.0 33.4  
80 93.4 93.4 100.1 77.3 110.6 56.7 89.5 89.5 95.3 75.0 105.4 54.5 85.5 85.5 90.3 72.7 99.9 52.2 81.1 81.1 85.1 70.3 94.2 49.9  
85 99.1 99.1 101.2 94.0 110.9 73.1 95.1 95.1 96.6 91.8 105.6 70.8 90.8 90.8 91.7 89.5 100.2 68.6 86.4 86.4 86.4 86.4 94.5 66.1  
90 104.8 104.8 104.8 104.8 111.4 89.4 100.7 100.7 100.6 100.6 106.2 87.2 96.3 96.3 96.3 96.3 100.8 84.9 91.7 91.7 91.7 91.7 95.2 82.5  
3300  
75  
91.6 85.5 100.8 63.0 111.5 40.8 87.2 83.2 95.9 60.7 106.2 38.6 82.0 82.0 90.8 58.4 100.6 36.3 77.7 77.7 85.5 56.0 94.9 34.0  
80 95.8 95.8 101.3 80.9 111.7 58.6 91.8 91.8 96.5 78.7 106.4 56.4 87.5 87.5 91.4 76.3 100.8 54.1 83.1 83.1 86.1 74.0 95.0 51.8  
85 101.6 101.6 102.8 99.1 112.0 76.3 97.5 97.5 97.4 97.4 106.8 74.2 93.1 93.1 93.0 93.0 101.2 71.9 88.5 88.5 88.5 88.5 95.4 69.4  
90 107.5 107.5 107.5 107.5 112.8 94.0 103.2 103.2 103.2 103.2 107.5 91.8 98.7 98.7 98.7 98.7 102.1 89.5 93.9 93.9 93.9 93.9 96.4 87.2  
3600  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unitapplicationsbelow2400CFM  
Electricheatersrestrictedonapplicationsbelow2400CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.  
32  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(8½Ton)  
High Efficiency  
Table PD-20— Gross Cooling Capacities (MBH) Ton Three Phase THC102A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73  
CFM  
61  
67  
73  
61  
67  
61  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 94.0 81.8 105.7 62.8 110.8 40.9 86.3 77.8 100.7 59.7 109.7 39.3 79.0 74.2 92.4 56.0 105.5 37.1 71.8 70.5 84.0 53.1 99.6 34.6  
80 96.9 96.9 106.2 77.6 112.0 56.0 90.6 90.6 101.1 75.9 110.1 55.4 84.5 84.5 92.9 72.2 106.1 53.2 78.3 78.3 84.7 68.5 99.8 50.6  
85 103.5 103.5 107.2 92.9 113.2 68.7 98.6 98.6 102.2 92.1 111.6 70.3 92.1 92.1 94.5 88.8 106.4 68.8 85.8 85.8 86.7 85.2 100.0 66.5  
90 108.4 108.4 109.0 107.7 114.4 81.6 105.0 105.0 105.0 105.0 112.6 84.9 99.9 99.9 99.9 99.9 107.3 83.9 93.5 93.5 93.5 93.5 100.8 82.6  
75 96.6 87.2 107.1 64.7 111.4 41.5 88.7 83.3 102.4 62.6 110.7 40.1 81.4 79.6 94.4 59.1 106.6 37.9 74.2 74.2 85.9 55.4 101.1 35.5  
80 100.9 100.9 107.7 81.0 112.7 56.9 94.9 94.9 103.0 80.4 111.7 57.5 88.3 88.3 95.2 77.1 107.3 55.7 81.8 81.8 86.8 73.4 101.4 53.1  
85 106.6 106.6 108.9 97.4 114.0 70.2 102.6 102.6 104.4 97.8 112.8 72.9 96.5 96.5 97.6 95.6 108.0 72.4 89.9 89.9 89.8 89.8 101.8 70.8  
90 110.8 110.8 110.8 110.8 115.3 83.8 108.1 108.1 108.1 108.1 114.0 88.5 103.8 103.8 103.8 103.8 108.9 88.3 97.8 97.8 97.8 97.8 102.8 87.9  
75 98.9 92.5 107.4 65.9 112.0 42.2 91.2 88.7 103.7 65.4 111.1 40.7 83.5 83.5 96.3 62.2 107.5 38.7 76.9 76.9 87.5 58.4 102.2 36.2  
80 103.7 103.7 108.8 84.0 113.3 57.7 98.7 98.7 104.5 84.5 112.4 58.7 91.7 91.7 97.3 81.9 108.3 57.6 85.0 85.0 88.8 78.2 102.6 55.5  
85 108.8 108.8 110.1 100.9 114.6 76.9 105.4 105.4 106.4 103.0 113.7 75.1 100.2 100.2 100.2 100.2 109.3 75.7 93.4 93.4 93.4 93.4 103.1 74.4  
90 112.3 112.3 112.1 112.1 115.9 85.7 110.4 110.4 110.4 110.4 114.9 91.4 106.5 106.5 106.5 106.5 110.2 92.3 101.3 101.3 101.3 101.3 104.4 92.7  
75 100.9 97.3 108.1 67.4 112.5 42.9 93.1 93.1 104.7 67.9 111.5 41.4 86.2 86.2 97.8 65.2 108.2 39.4 79.4 79.4 88.8 61.3 103.0 36.9  
80 105.9 105.9 109.5 86.2 113.8 58.4 101.6 101.6 105.8 88.2 112.8 59.6 94.9 94.9 99.1 86.5 109.2 59.6 87.9 87.9 90.6 82.8 103.5 57.8  
85 110.2 110.2 110.9 103.4 115.1 79.5 107.6 107.6 107.6 107.6 114.1 76.6 103.0 103.0 103.0 103.0 109.9 77.6 96.6 96.6 96.6 96.6 104.2 77.7  
90 112.9 112.9 112.9 112.9 116.5 87.5 112.2 112.2 112.2 112.2 115.4 93.4 108.6 108.6 108.6 108.6 111.3 95.9 103.9 103.9 103.9 103.9 105.8 97.0  
3060  
3400  
3740  
4080  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC005-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(8½ Ton)  
High Efficiency  
Table PD-21— Gross Cooling Capacities (MBH) Ton Three Phase THC102A3, A4, AW – Dehumidification (Hot Gas Reheat)  
or TXV Option  
AmbientTemperature (F)  
85  
95  
105  
67  
115  
67  
Enter.  
Dry  
EnteringWet Bulb (F)  
73  
CFM  
Bulb  
61  
67  
73  
61  
67  
61  
73  
61  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 84.4 60.9 94.7 49.8 105.6 38.0 80.3 58.5 90.3 47.5 100.8 35.7 75.9 56.0 85.6 45.0 95.7 33.3 71.3 53.3 80.6 42.4 90.3 30.8  
80 84.5 70.3 94.8 59.1 105.8 47.6 80.4 67.9 90.4 56.7 100.9 45.2 76.1 65.3 85.7 54.1 95.9 42.7 71.5 62.6 80.7 51.5 90.5 40.2  
85 84.8 79.7 94.9 68.4 105.9 56.8 80.8 77.3 90.6 66.0 101.1 54.4 76.5 74.7 85.9 63.4 96.0 51.9 72.2 71.0 80.9 60.8 90.6 49.3  
1700*  
2210*  
2720  
3060  
3400  
3740  
90  
87.0 87.0 95.1 77.7 106.0 66.0 83.6 83.6 90.7 75.2 101.2 63.6 80.0 80.0 86.0 72.6 96.1 61.1 76.2 76.2 81.0 70.0 90.8 58.5  
75 90.0 69.6 100.5 54.9 111.8 39.9 85.6 67.0 95.7 52.4 106.5 37.5 80.8 64.4 90.6 49.8 100.9 35.0 75.8 61.6 85.1 47.1 95.1 32.4  
80 90.5 81.7 100.7 66.8 111.9 51.9 86.1 79.2 95.9 64.3 106.7 49.5 81.5 76.6 90.8 61.7 101.1 47.0 76.6 73.8 85.3 59.0 95.3 44.3  
85 92.3 92.3 101.0 78.8 112.1 63.8 88.6 88.6 96.1 76.3 106.8 61.3 84.6 84.6 91.0 73.6 101.3 58.7 80.3 80.3 85.6 70.9 95.4 56.1  
90  
97.5 97.5 101.5 90.7 112.3 75.6 93.6 93.6 96.7 88.2 107.0 73.1 89.5 89.5 91.7 87.1 101.5 70.5 85.1 85.1 86.4 82.9 95.6 67.9  
75 94.0 77.6 104.4 59.5 115.8 41.4 89.3 75.1 99.3 57.0 110.2 38.9 84.3 72.4 93.8 54.4 104.3 36.4 79.0 69.6 88.1 51.7 98.2 33.8  
80 95.2 92.6 104.7 74.1 116.0 55.9 90.7 90.1 99.5 71.5 110.4 53.4 86.0 86.0 94.1 68.9 104.5 50.9 81.4 81.4 88.4 66.2 98.4 48.2  
85 99.8 99.8 105.2 88.7 116.2 70.3 95.7 95.7 100.1 86.1 110.6 67.8 91.3 91.3 94.7 83.5 104.7 65.2 86.6 86.6 89.1 80.7 98.6 62.5  
90 105.4 105.4 106.5 103.4 116.5 84.7 101.1 101.1 101.6 100.9 110.9 82.1 96.6 96.6 96.6 96.6 105.1 79.5 91.8 91.8 91.8 91.8 98.9 76.9  
75 96.1 82.8 106.4 63.2 117.8 42.2 91.3 80.2 101.0 60.7 112.1 39.8 86.2 77.5 95.4 58.1 106.0 37.2 80.8 74.7 89.6 55.4 99.7 34.6  
80 98.1 98.1 106.7 78.8 118.1 58.5 93.8 93.8 101.4 76.2 112.2 55.9 89.3 89.3 95.8 73.5 106.2 53.3 84.6 84.6 90.0 70.8 99.9 50.7  
85 103.8 103.8 107.5 95.1 118.3 74.5 99.5 99.5 102.3 92.5 112.5 72.0 94.8 94.8 96.9 89.9 106.4 69.4 89.9 89.9 91.2 87.2 100.1 66.7  
90 109.7 109.7 109.7 109.7 118.7 90.6 105.2 105.2 105.2 105.2 112.9 88.1 100.4 100.4 100.4 100.4 106.9 85.4 95.4 95.4 95.4 95.4 100.7 82.7  
75  
97.9 87.9 108.0 65.4 119.4 43.1 93.0 85.3 102.5 62.8 113.5 40.6 87.8 82.6 96.8 60.1 107.4 38.1 82.5 79.9 90.8 57.4 100.9 35.4  
80 101.3 101.3 108.4 83.4 119.7 60.9 96.9 96.9 103.0 80.8 113.7 58.4 92.2 92.2 97.3 78.1 107.5 55.8 87.3 87.3 91.4 75.3 101.1 53.1  
85 107.3 107.3 109.6 101.4 120.0 78.7 102.8 102.8 104.3 98.8 114.0 76.1 98.0 98.0 98.9 96.2 107.8 73.5 92.9 92.9 92.9 92.9 101.4 70.8  
90 113.4 113.4 113.4 113.4 120.6 96.4 108.8 108.8 108.7 108.7 114.6 93.8 103.8 103.8 103.8 103.8 108.6 91.2 98.6 98.6 98.6 98.6 102.2 88.5  
75 99.6 92.9 109.3 68.2 120.7 43.8 94.6 90.3 103.8 65.6 114.8 41.4 89.4 87.6 98.0 62.9 108.5 38.8 83.8 83.8 91.9 60.2 101.9 36.2  
80 104.1 104.1 109.9 87.9 121.0 63.3 99.5 99.5 104.4 85.3 114.9 60.7 94.7 94.7 98.7 82.6 108.7 58.1 89.6 89.6 92.6 79.8 102.1 55.4  
85 110.4 110.4 111.6 107.6 121.4 82.7 105.7 105.7 106.3 105.1 115.3 80.1 100.7 100.7 100.6 100.6 109.0 77.5 95.4 95.4 95.4 95.4 102.5 74.9  
90 116.7 116.7 116.7 116.7 122.1 102.0 111.8 111.8 111.8 111.8 116.2 99.5 106.7 106.7 106.7 106.7 110.0 96.8 101.2 101.2 101.2 101.2 103.6 94.2  
75 101.1 97.8 110.5 71.0 121.9 44.6 96.1 95.2 104.9 68.3 115.8 42.1 90.8 90.8 98.9 65.7 109.4 39.5 85.7 85.7 92.7 62.9 102.8 36.8  
80 106.6 106.6 111.2 92.2 122.1 65.7 101.9 101.9 105.7 89.6 116.0 63.1 96.9 96.9 99.8 87.0 109.6 60.5 91.6 91.6 93.8 84.2 103.0 57.8  
85 113.1 113.1 113.0 113.0 122.5 86.7 108.2 108.2 108.1 108.1 116.4 84.1 103.0 103.0 103.0 103.0 110.0 81.5 97.6 97.6 97.6 97.6 103.5 78.8  
90 119.5 119.5 119.5 119.5 123.6 107.6 114.5 114.5 114.5 114.5 117.5 105.0 109.2 109.2 109.2 109.2 111.3 102.4 103.6 103.6 103.6 103.6 104.9 99.8  
4080  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unitapplicationsbelow2720CFM  
Electricheatersrestrictedonapplicationsbelow2720CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.  
34  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(10 Ton)  
High Efficiency  
Table PD-22 — Gross Cooling Capacities (MBH) 10 Ton Three Phase THC120A3, A4, AW– Standard Refrigeration Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73  
CFM  
61  
67  
73  
61  
67  
61  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 107.0 94.4 117.4 75.0 123.4 46.0 98.7 90.1 114.7 68.8 121.9 44.4 88.5 88.5 107.2 65.3 118.6 42.2 82.3 78.8 97.8 61.1 113.6 39.6  
80 110.9 108.6 119.9 88.2 125.0 62.5 104.5 104.1 115.2 87.5 123.4 62.3 97.7 97.7 107.8 84.3 119.4 60.8 90.6 90.6 98.5 80.1 114.3 58.3  
85 117.6 117.6 120.9 105.0 126.6 76.7 113.1 113.1 116.5 105.8 124.9 78.1 106.9 106.9 107.0 107.0 120.9 78.1 99.9 99.9 100.0 100.0 114.8 76.5  
90 122.5 122.5 122.4 122.4 128.2 91.1 119.6 119.6 119.6 117.1 126.4 94.1 115.0 115.0 114.7 114.6 121.6 94.3 109.0 109.0 109.0 109.0 115.8 94.3  
3600  
4000  
4400  
75 109.8 100.5 119.4 71.9 122.5 46.5 99.7 99.7 116.1 71.5 121.7 45.0 92.5 92.5 110.1 69.1 119.4 43.0 85.6 83.4 100.9 65.0 114.6 40.5  
80 114.6 114.1 120.8 90.1 124.1 68.3 109.3 109.3 117.0 91.2 123.4 62.7 102.3 102.3 110.8 89.9 120.6 62.5 94.8 94.8 101.9 86.0 115.5 61.1  
85 120.5 120.5 122.3 107.9 125.9 76.4 117.0 117.0 118.6 110.2 125.0 78.8 111.6 111.6 111.8 111.8 122.1 80.4 104.7 104.7 105.8 102.6 116.3 79.7  
90 125.2 125.2 124.2 124.2 127.6 90.9 122.4 122.4 121.7 120.9 126.6 95.1 118.5 118.5 118.3 118.3 123.6 98.4 113.1 113.1 113.3 113.3 117.7 98.6  
75 112.3 106.1 121.2 74.8 124.6 47.6 103.6 103.6 117.1 75.5 123.0 46.0 96.7 93.9 111.2 72.2 120.0 43.7 88.6 88.0 102.0 68.2 115.3 41.2  
80 117.6 117.6 122.5 94.7 126.3 64.2 113.0 113.0 118.4 95.8 124.7 64.4 106.3 106.3 112.2 94.9 121.5 64.3 98.8 98.8 103.5 91.1 116.1 62.8  
85 122.4 122.4 124.3 113.8 128.0 79.6 119.6 119.6 119.6 119.6 126.4 81.8 115.1 115.1 115.5 111.7 122.7 83.0 109.1 109.1 108.8 107.4 117.2 83.2  
90 126.0 126.0 127.1 125.0 129.6 95.2 124.3 124.3 124.2 124.2 128.0 99.4 120.9 120.9 120.9 120.9 123.9 101.2 116.1 116.1 116.1 116.1 118.8 103.3  
75 113.4 113.4 121.8 76.2 125.0 48.4 107.6 104.0 118.5 77.0 123.5 46.9 99.6 98.2 112.7 75.4 120.5 44.8 91.6 91.6 103.7 71.6 115.9 41.9  
80 119.5 119.5 123.2 97.0 126.7 64.8 115.8 115.8 119.8 99.6 125.2 65.3 109.8 109.8 113.9 99.4 122.1 65.5 102.3 102.3 105.5 96.3 117.2 66.8  
85 124.3 124.3 125.2 116.6 128.4 80.7 121.5 121.5 121.5 121.5 126.9 83.3 117.5 117.5 117.6 115.4 123.7 85.6 111.8 111.8 111.8 111.8 118.5 86.4  
90 127.5 127.5 128.0 126.7 130.1 96.9 126.0 126.0 125.5 125.5 128.6 101.5 122.6 122.6 123.0 123.0 125.5 105.5 118.2 118.2 118.2 118.2 120.3 107.5  
4800  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC005-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(10 Ton)  
High Efficiency  
Table PD-23— Gross Cooling Capacities (MBH) 10Ton THC120A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option  
AmbientTemperature (F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb (F)  
73 61  
CFM  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
Airflow  
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC  
75 94.2 68.9 105.8 56.2 118.4 42.6 89.7 66.2 101.0 53.6 113.2 40.0 84.8 63.4 95.8 50.9 107.6 37.3 79.7 60.4 90.2 48.1 101.5 34.6  
80 94.4 79.8 106.0 66.8 118.6 53.6 89.9 77.1 101.2 64.1 113.4 51.0 85.0 74.2 96.0 61.4 107.8 48.3 79.9 71.2 90.4 58.4 101.7 45.4  
85 93.0 93.0 106.3 77.6 118.8 64.3 90.4 86.3 101.4 74.9 113.6 61.7 86.1 82.8 96.2 72.1 108.0 59.0 81.6 79.1 90.7 69.2 101.9 56.1  
90 98.0 97.2 106.4 88.3 119.0 75.0 94.4 94.4 101.6 85.6 113.8 72.4 90.4 90.4 96.4 82.8 108.2 69.6 86.1 86.1 90.9 79.8 102.1 66.7  
2000*  
2600*  
3200  
3600  
4000  
4400  
75 100.5 78.8 112.6 62.6 125.6 44.8 95.6 76.0 107.3 59.9 119.9 42.2 90.4 73.0 101.6 57.1 113.8 39.5 84.8 70.0 95.6 54.1 107.2 36.6  
80 101.1 92.6 112.9 75.8 125.8 58.8 96.4 89.9 107.6 73.1 120.1 56.1 89.7 89.7 101.9 70.2 114.0 53.3 86.0 81.9 95.8 67.1 107.4 50.4  
85 104.0 102.0 113.2 89.6 126.1 72.5 99.7 98.7 107.9 86.8 120.4 69.8 95.4 95.4 102.3 83.9 114.2 67.0 90.6 90.6 96.2 80.9 107.6 64.0  
90 109.9 109.9 113.9 103.3 126.4 86.1 105.6 105.6 108.7 100.5 120.7 83.4 101.1 101.1 101.1 101.1 114.5 80.6 96.2 96.2 97.5 92.3 107.9 77.6  
75 104.9 87.8 117.1 67.4 130.2 46.6 99.8 85.0 111.5 65.7 124.2 44.0 94.3 82.0 110.8 64.8 117.7 41.2 88.4 78.9 99.0 59.8 110.7 38.2  
80 106.6 102.0 117.4 84.1 130.5 63.4 102.0 98.4 111.8 81.3 124.5 60.6 97.0 94.6 105.8 78.4 118.0 57.8 91.6 90.5 99.4 75.3 111.0 54.8  
85 112.2 112.2 118.1 100.7 130.8 79.9 107.8 107.8 112.6 98.0 124.7 77.2 103.0 103.0 106.7 95.0 118.2 74.3 97.7 97.7 100.4 91.9 111.2 71.3  
90 118.6 118.6 118.8 118.8 131.1 96.5 114.2 114.2 115.0 110.5 125.1 93.7 109.2 109.2 109.6 106.5 118.7 90.8 103.8 103.8 103.9 102.2 111.7 87.8  
75 107.3 93.6 119.4 70.7 132.5 47.7 102.1 90.8 113.6 67.9 126.3 45.0 96.5 87.8 107.2 64.9 119.4 42.1 90.4 84.7 100.6 61.8 112.1 39.1  
80 110.3 107.5 119.7 89.4 132.8 66.3 105.6 104.0 114.0 86.6 126.6 63.5 100.4 100.3 107.6 83.5 119.6 60.5 95.1 95.1 101.1 80.4 112.4 57.5  
85 116.7 116.7 120.8 107.9 133.2 84.7 112.2 112.2 115.2 105.1 126.9 82.0 107.1 107.1 108.9 102.1 119.9 79.0 101.4 101.4 101.4 101.4 112.7 75.9  
90 123.5 123.5 124.2 120.7 133.7 103.1 118.8 118.8 119.0 116.9 127.5 100.3 113.6 113.6 113.2 112.8 120.6 97.3 107.7 107.7 107.7 107.7 113.4 94.2  
75 110.8 101.0 122.7 75.2 136.1 49.4 105.2 97.9 116.6 72.2 129.5 46.5 99.5 94.8 110.2 69.2 122.6 43.6 92.8 92.8 103.6 66.0 115.5 40.6  
80 115.3 115.3 123.1 96.0 136.3 70.2 110.3 110.3 117.0 93.1 129.7 67.3 105.0 105.0 110.7 90.0 122.9 64.3 99.5 99.5 104.1 86.8 115.7 61.3  
85 122.3 122.3 124.5 116.8 136.6 90.7 117.2 117.2 117.2 117.2 130.0 87.8 111.8 111.8 111.8 111.8 123.1 84.8 106.2 106.2 106.6 103.4 116.0 81.8  
90 129.5 129.5 129.3 129.3 137.2 111.3 124.2 124.2 124.2 124.2 130.6 108.4 118.7 118.7 118.6 118.6 123.9 105.4 112.9 112.9 112.8 112.8 116.9 102.4  
75 112.7 106.4 124.3 78.3 137.7 50.3 106.1 106.1 118.0 75.3 130.9 47.4 100.8 100.8 111.5 72.2 123.9 44.4 95.5 93.3 104.7 69.1 116.7 41.4  
80 118.4 118.4 124.8 100.9 137.9 72.8 113.2 113.2 118.6 98.0 131.2 69.9 107.8 107.8 112.2 94.9 124.2 67.0 102.1 102.1 105.5 91.7 116.9 63.9  
85 125.7 125.7 125.7 125.7 138.2 95.2 120.4 120.4 120.4 120.4 131.5 92.3 114.8 114.8 115.1 112.5 124.5 89.3 109.0 109.0 109.0 107.8 117.3 86.3  
90 133.1 133.1 133.1 133.1 139.0 117.5 127.6 127.6 127.6 127.6 132.4 114.6 121.9 121.9 121.9 121.9 125.5 111.6 115.9 115.9 115.9 115.9 118.5 108.6  
75 113.7 113.7 125.6 81.3 139.0 51.1 108.5 108.5 119.2 78.3 132.2 48.2 103.0 103.0 112.6 75.2 125.1 45.3 97.3 96.6 105.8 72.0 117.7 42.2  
80 121.1 121.1 126.2 105.7 139.3 75.4 115.8 115.8 120.0 102.7 132.4 72.5 110.2 110.2 113.5 99.7 125.3 69.5 104.4 104.4 106.8 96.5 118.0 66.5  
85 128.6 128.6 128.6 128.6 139.6 99.5 123.2 123.2 123.4 121.4 132.8 96.6 117.4 117.4 117.4 116.7 125.7 93.6 111.5 111.5 111.4 111.4 118.4 90.6  
90 136.2 136.2 136.2 136.2 140.7 123.6 130.6 130.6 130.6 130.6 134.0 120.7 124.7 124.7 124.7 124.7 127.1 117.6 118.5 118.5 118.5 118.5 118.5 118.5  
4800  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow  
tablenotes.  
2. MBH = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
*Unitapplicationsbelow3200CFM  
Electricheatersrestrictedonapplicationsbelow3200CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 3200 CFM.  
36  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(3, 4, 5Ton)  
Standard Efficiency  
Table PD-24— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A  
External Static Pressure (Inches ofWater) & Motor Power (Bhp)1  
Standard Motor  
High Speed Low Speed  
ESP ESP  
Oversized Motor  
High Speed Low Speed  
ESP ESP  
Unit  
Model No. CFM  
Tons  
3
BHP  
0.36  
0.37  
0.38  
0.39  
0.40  
0.41  
0.42  
0.42  
0.43  
0.53  
0.54  
0.54  
0.55  
0.55  
0.56  
0.56  
0.57  
0.57  
0.78  
0.82  
0.85  
0.88  
0.90  
0.93  
0.95  
0.97  
1.00  
0.36  
0.37  
0.38  
0.39  
0.40  
0.41  
0.42  
0.42  
0.43  
0.53  
0.54  
0.54  
0.55  
0.55  
0.56  
0.56  
0.57  
0.57  
0.78  
0.82  
0.85  
0.88  
0.90  
0.93  
0.95  
0.97  
1.00  
BHP  
0.28  
0.28  
0.29  
0.29  
0.30  
0.30  
0.31  
0.31  
BHP  
0.39  
0.41  
0.43  
0.44  
0.45  
0.46  
0.48  
0.49  
0.52  
0.67  
0.68  
0.70  
0.73  
0.75  
0.78  
0.82  
0.83  
0.85  
0.90  
0.94  
0.98  
1.02  
1.05  
1.10  
1.12  
1.17  
1.20  
0.39  
0.41  
0.43  
0.44  
0.45  
0.46  
0.48  
0.49  
0.52  
0.67  
0.68  
0.70  
0.73  
0.75  
0.78  
0.82  
0.83  
0.85  
0.90  
0.94  
0.98  
1.02  
1.05  
1.10  
1.12  
1.17  
1.20  
BHP  
0.35  
0.47  
0.39  
0.40  
0.41  
0.42  
0.44  
0.45  
0.48  
0.56  
0.58  
0.60  
0.63  
0.64  
0.66  
0.68  
0.70  
0.73  
0.85  
0.89  
0.91  
0.94  
0.95  
0.96  
0.96  
0.97  
0.35  
0.47  
0.39  
0.40  
0.41  
0.42  
0.44  
0.45  
0.48  
0.56  
0.58  
0.60  
0.63  
0.64  
0.66  
0.68  
0.70  
960  
1020  
1080  
1140  
0.81  
0.77  
0.73  
0.69  
0.66  
0.60  
0.55  
0.49  
0.44  
0.93  
0.87  
0.80  
0.73  
0.66  
0.57  
0.47  
0.37  
0.27  
0.90  
0.85  
0.80  
0.70  
0.60  
0.50  
0.40  
0.30  
0.20  
0.86  
0.82  
0.78  
0.74  
0.71  
0.65  
0.60  
0.54  
0.49  
0.98  
0.92  
0.85  
0.78  
0.71  
0.62  
0.52  
0.42  
0.32  
0.95  
0.90  
0.85  
0.75  
0.65  
0.55  
0.45  
0.35  
0.25  
0.61  
0.57  
0.50  
0.42  
0.34  
0.26  
0.14  
0.05  
0.81  
0.75  
0.68  
0.60  
0.51  
0.38  
0.23  
0.13  
0.82  
0.68  
0.56  
0.46  
0.30  
0.14  
0.05  
0.96  
0.94  
0.91  
0.88  
0.84  
0.80  
0.75  
0.70  
0.64  
1.20  
1.15  
1.10  
1.05  
1.00  
0.95  
0.90  
0.83  
0.75  
1.20  
1.15  
1.05  
0.98  
0.90  
0.80  
0.70  
0.60  
0.48  
1.01  
0.99  
0.96  
0.93  
0.89  
0.85  
0.80  
0.75  
0.69  
1.25  
1.20  
1.15  
1.10  
1.05  
1.00  
0.95  
0.88  
0.80  
1.25  
1.20  
1.10  
1.03  
0.95  
0.85  
0.75  
0.65  
0.53  
0.89  
0.86  
0.82  
0.77  
0.74  
0.70  
0.65  
0.59  
0.54  
0.99  
0.94  
0.88  
0.81  
0.74  
0.65  
0.50  
0.35  
0.25  
1.05  
0.95  
0.85  
0.75  
0.65  
0.50  
0.35  
0.15  
0.89  
0.91  
0.87  
0.82  
0.79  
0.75  
0.70  
0.64  
0.59  
1.04  
0.99  
0.93  
0.86  
0.79  
0.70  
0.55  
0.40  
TSC036A 1200  
Horizontal 1260  
1320  
1380  
1440  
1280  
1360  
1440  
1520  
0.47  
0.47  
0.48  
0.48  
0.49  
0.49  
0.50  
0.50  
0.64  
0.65  
0.65  
0.65  
0.66  
0.66  
0.67  
4
5
3
4
5
TSC048A 1600  
Horizontal 1680  
1760  
1840  
1920  
1600  
1700  
1800  
1900  
TSC060A3 2000  
Horizontal 2100  
2200  
2300  
2400  
960  
1020  
1080  
1140  
0.61  
0.62  
0.55  
0.47  
0.39  
0.31  
0.19  
0.10  
0.86  
0.80  
0.73  
0.65  
0.56  
0.43  
0.28  
0.18  
0.87  
0.73  
0.61  
0.51  
0.35  
0.19  
0.10  
0.28  
0.28  
0.29  
0.29  
0.30  
0.30  
0.31  
0.31  
0.47  
0.47  
0.48  
0.48  
0.49  
0.49  
0.50  
0.50  
0.64  
0.65  
0.65  
0.65  
0.66  
0.66  
0.67  
TSC036A 1200  
Downflow 1260  
1320  
1380  
1440  
1280  
1360  
1440  
1520  
TSC048A 1600  
Downflow 1680  
1760  
1840  
1920  
1600  
1700  
1800  
1900  
1.10  
1.00  
0.90  
0.80  
0.70  
0.55  
0.40  
0.20  
0.85  
0.89  
0.91  
0.94  
0.95  
0.96  
0.96  
0.97  
TSC060A3 2000  
Downflow 2100  
2200  
2300  
2400  
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and  
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance  
tripping or premature motor failure. Our product’s warranty will not be affected.  
Notes:  
1. Data includes pressure drop due to wet coil and filters.  
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.  
3. YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard motor  
performancedata.  
RT-PRC005-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3Ton)  
Standard Efficiency  
Performance  
Data  
Table PD-25 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
1-HPStandardMotor&Drive  
960  
528  
557  
588  
622  
657  
0.12  
0.15  
0.19  
0.23  
0.28  
599  
625  
652  
681  
713  
0.16  
0.19  
0.23  
0.27  
0.33  
658  
685  
712  
738  
765  
0.20  
0.24  
0.28  
0.32  
0.37  
713  
738  
764  
790  
817  
0.24  
0.28  
0.33  
0.38  
0.43  
763  
786  
811  
838  
865  
0.29  
0.33  
0.38  
0.44  
0.50  
810  
832  
856  
882  
909  
0.33  
0.38  
0.43  
0.49  
0.56  
855  
876  
898  
923  
949  
0.38  
0.43  
0.48  
0.55  
0.62  
898 0.43  
917 0.48  
939 0.54  
962 0.60  
987 0.68  
939 0.49  
957 0.54  
978 0.59  
1000 0.66  
1024 0.74  
1080  
1200  
1320  
1440  
552  
588  
0.18  
0.23  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other  
options/accessories  
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybe  
necessary.  
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybe  
necessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurpose  
motors, specifically designed and tested to operate reliably and continuously at  
all cataloged conditions. Using the full horsepower range of our fan motors as  
shown in our tabular data will not result in nuisance tripping or premature  
motor failure. Our product’s warranty will not be affected.  
Table PD-25 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
960  
978  
995  
1015  
1036  
1060  
0.54  
0.59  
0.65  
0.72  
0.80  
1016  
1033  
1051  
1072  
1094  
0.60  
0.65  
0.71  
0.78  
0.86  
1052  
0.66  
0.71  
0.77  
0.85  
0.93  
1086  
1103  
1120  
1138  
1160  
0.72  
0.78  
0.84  
0.91  
1.00  
1120  
1136  
1154  
1171  
1192  
0.78  
0.84  
0.91  
0.98  
1.07  
1080  
1200  
1320  
1440  
1069  
1086  
1106  
1128  
1-HPStandardMotor&FieldSuppliedHighStaticDrive(2)  
Table PD-26 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied  
1-HPStandardMotor&Drive  
Low Static Drive (1)  
960  
588  
622  
654  
687  
723  
0.15  
0.18  
0.23  
0.28  
0.33  
661  
694  
727  
760  
793  
0.19  
0.24  
0.28  
0.34  
0.40  
725  
756  
787  
821  
855  
0.24  
0.29  
0.34  
0.40  
0.47  
782  
813  
843  
875  
908  
0.29  
0.34  
0.40  
0.46  
0.53  
832  
864  
895  
925  
956  
0.35  
0.40  
0.46  
0.53  
0.60  
878  
910  
942  
0.40  
0.46  
0.52  
0.59  
919  
954  
986  
0.46  
0.52  
0.59  
958 0.51  
993 0.59  
1026 0.66 1064 0.73  
996 0.56  
1031 0.65  
1080  
1200  
1320  
1440  
531  
570  
610  
651  
0.13  
0.17  
0.22  
0.27  
973  
1017  
0.66 1058 0.73 1095 0.81  
0.75 1088 0.82 1127 0.89  
1003  
0.67 1047  
1-HP Standard Motor &Field Supplied High Static Drive (2)  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other  
options/accessories.  
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybe  
necessary.  
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybe  
necessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurpose  
motors, specifically designed and tested to operate reliably and continuously at  
all cataloged conditions. Using the full horsepower range of our fan motors as  
shown in our tabular data will not result in nuisance tripping or premature  
motor failure. Our product’s warranty will not be affected.  
Table PD-26 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
960  
1032 0.62  
1066  
1099  
1133  
1167  
1199  
0.67  
0.76  
0.86  
0.96  
1.05  
1101  
0.73  
0.82  
0.93  
1.04  
1.14  
1133  
1164  
1197  
1230  
1263  
0.79  
0.89  
0.99  
1.11  
1.22  
1166  
1194  
1227  
1261  
1294  
0.86  
0.95  
1.06  
1.19  
1.30  
1080  
1200  
1320  
1440  
1065  
1099  
1132  
1164  
0.70  
0.80  
0.88  
0.97  
1132  
1166  
1200  
1232  
1-HPStandardMotor&FieldSuppliedHighStaticDrive(2)  
38  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(4Ton)  
Standard Efficiency  
Performance  
Data  
Table PD-27 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied  
1-HP Standard Motor & Drive  
Low Static Drive (1)  
1280  
1440  
1600  
1760  
1920  
616  
663  
711  
758  
807  
0.22  
0.29  
0.37  
0.46  
0.57  
677  
719  
764  
811  
859  
0.26  
0.33  
0.42  
0.52  
0.64  
734  
772  
813  
856  
903  
0.31  
0.38  
0.47  
0.58  
0.71  
787  
823  
860  
901  
945  
0.37  
0.44  
0.53  
0.64  
0.77  
834  
871  
906  
944  
985  
0.42  
0.51  
0.59  
0.70  
0.83  
878  
914  
951  
986  
1024  
0.48  
0.57  
0.66  
0.77  
919  
954  
992  
0.53  
0.63  
0.74  
959 0.59  
993 0.69  
1029 0.80 1065 0.87  
997 0.64  
1029 0.75  
596  
647  
701  
755  
0.23  
0.31  
0.41  
0.52  
1027  
0.85 1066 0.93  
0.97 1101 1.05  
1102 1.00  
1137 1.14  
0.89 1063  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other  
options/accessories  
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all  
cataloged conditions. Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or premature motor failure.  
Ourproduct’s warranty will not be affected.  
Table PD-27 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
1280  
1440  
1600  
1760  
1920  
1033  
1066  
1099  
1136  
1172  
0.70  
0.81  
0.93  
1.08  
1.23  
1069  
1099  
1132  
1168  
1205  
0.77  
0.87  
1.00  
1.15  
1.31  
1103  
0.83  
0.94  
1.07  
1.22  
1.39  
1136  
1165  
1196  
1229  
0.89  
1.01  
1.14  
1.29  
1170  
1196  
1228  
0.96  
1.08  
1.21  
1133  
1166  
1200  
1236  
Table PD-28 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied  
1-HPStandardMotor&Drive  
Low Static Drive (1)  
1280  
1440  
1600  
1760  
1920  
604  
660  
717  
774  
833  
0.20  
0.28  
0.36  
0.47  
0.59  
683  
731  
783  
837  
892  
0.26  
0.34  
0.43  
0.54  
0.67  
756  
800  
846  
894  
946  
0.32  
0.41  
0.51  
0.62  
0.76  
816  
862  
907  
952  
998  
0.39  
0.48  
0.58  
0.70  
0.85  
869  
914  
961  
1006  
1050  
0.45  
0.54  
0.66  
0.79  
0.94  
920  
963  
1008  
1054  
1100  
0.51  
0.61  
0.73  
0.87  
1.03  
967  
0.57  
0.68 1053  
0.81 1095  
1011  
0.64  
1052 0.71 1090 0.79  
1009  
1053  
1098  
1144  
0.76 1094 0.83  
1133 0.91  
1174 1.05  
1216 1.21  
1259 1.39  
0.89  
1.04  
1.21  
1135 0.97  
1178 1.12  
1224 1.30  
0.95  
1.12  
1139  
1185  
1-HPStandardMotor&FieldSuppliedHighStaticDrive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56  
Notes:  
Data includes pressure drop due to standard filters and wet coils  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other  
options/accessories.  
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.  
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all  
cataloged conditions. Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or premature motor failure.  
Our product’s warranty will not be affected.  
Table PD-28 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
1280  
1440  
1600  
1760  
1920  
1125  
1169  
1211  
1253  
1295  
0.86  
0.98  
1.13  
1.30  
1.48  
1160  
1204  
1247  
1289  
0.94  
1.07  
1.21  
1.39  
1192  
1.01  
1.15  
1.30  
1.47  
1223  
1269  
1312  
1.08  
1.23  
1.39  
1254  
1300  
1343  
1.15  
1.32  
1.48  
1237  
1280  
1322  
1-HP Standard Motor & FieldSuppliedHighStaticDrive  
RT-PRC005-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(5Ton)  
Standard Efficiency  
Table PD-29— Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
0.70  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
1-HPStandardMotor&Drive  
1011 0.77 1048 0.84 1084 0.90  
0.93 1098 1.01  
1111  
1164  
1221  
1600  
1800  
2000  
2200  
2400  
674  
743  
813  
886  
959  
0.33  
0.46  
0.61  
0.80  
1.03  
735  
801  
866  
933  
1000  
0.39  
0.52  
0.68  
0.87  
1.10  
786  
849  
914  
980  
1045  
0.45  
0.59  
0.76  
0.96  
1.19  
835  
894  
956  
1019  
1085  
0.50  
0.65  
0.83  
1.03  
1.28  
883  
937  
995  
1057  
1121  
0.56  
0.70  
0.89  
1.11  
1.36  
928  
979  
1035  
1093  
1154  
0.63  
0.77  
0.96  
1.18  
1.45  
972  
1021  
1073  
1129  
1188  
0.85 1060  
1134 1.09  
1183 1.28  
1233 1.50  
1.02  
1.25  
1.53  
1.10  
1.33  
1.60  
1147 1.19  
1198 1.40  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Table PD-29 — Continued  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other  
options/accessories  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all  
cataloged conditions. Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or premature motor failure.  
Our product’s warranty will not be affected.  
1-HPStandardMotor&Drive  
1600  
1800  
2000  
2200  
2400  
1117  
1167  
1216  
0.97  
1.16  
1.37  
1150  
1199  
1249  
1.04  
1.24  
1.47  
1183  
1.11  
1.31  
1215  
1259  
1.18  
1.39  
1244  
1289  
1.25  
1.47  
1230  
Table PD-30 — Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied  
Low Static Drive (1)  
1-HPStandardMotor&Drive  
1600  
1800  
2000  
2200  
2400  
746  
824  
902  
981  
1061  
0.39  
0.54  
0.72  
0.93  
1.19  
812  
883  
957  
1032  
1109  
0.47  
0.62  
0.80  
1.03  
1.29  
876  
940  
1008  
1080  
1153  
0.54  
0.70  
0.90  
1.13  
1.40  
934  
996  
1059  
1126  
1196  
0.62  
0.79  
0.99  
1.23  
1.50  
985  
1048  
1110  
1173  
0.70  
0.88  
1.09  
1.34  
1032  
1094  
1157  
1219  
0.77  
0.96  
1.19  
1.44  
1074  
1137  
1200  
0.85  
1.05  
1.28  
1117  
1176  
1239  
0.93  
1.14  
1.38  
1157 1.01  
1214 1.22  
1276 1.47  
1196 1.09  
1252 1.31  
1311 1.50  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Table PD-30 — Continued  
Data includes pressure drop due to standard filters and wet coils  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/  
accessories.  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan motors as shown in our tabular  
data will not result in nuisance tripping or premature motor failure. Our product’s  
warranty will not be affected.  
1-HPStandardMotor&Drive  
1600  
1800  
2000  
2200  
2400  
1232  
1289  
1.18  
1.41  
1267  
1323  
1.26  
1.50  
1299  
1.35  
1332  
1.45  
40  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(6 Ton)  
Standard Efficiency  
Table PD-31 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied Low Static Drive (1)  
1-HPStandardMotor&Drive  
1920  
2160  
2400  
2640  
2880  
573  
602  
635  
670  
706  
0.34  
0.42  
0.52  
0.64  
0.78  
630  
656  
682  
715  
749  
0.41  
0.50  
0.60  
0.72  
0.86  
680  
706  
732  
758  
789  
0.48  
0.58  
0.69  
0.81  
0.96  
726  
751  
777  
802  
830  
0.55  
0.65  
0.77  
0.91  
1.06  
769  
792  
818  
845  
870  
0.62  
0.73  
0.86  
1.01  
1.16  
811  
832  
856  
883  
909  
0.70  
0.81  
0.95  
1.10  
1.27  
851 0.78  
871 0.90  
893 1.04  
919 1.20  
945 1.37  
889 0.87  
908 0.99  
930 1.13  
953 1.29  
979 1.48  
548  
584  
621  
660  
0.35  
0.45  
0.56  
0.69  
569  
612  
0.47  
0.60  
Table PD-31 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM BHP  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1 HP Standard Motor & Drive  
1HP Standard Motor & High Static Drive Kit  
(or2HPOversizedMotor&Drive)  
1920  
2160  
2400  
2640  
2880  
925  
944  
964  
986  
1011  
0.95  
1.08  
1.22  
1.39  
1.58  
960  
978  
998  
1019  
1043  
1.03  
1.17  
1.32  
1.49  
1.69  
994  
1.11  
1.26  
1.42  
1.60  
1.79  
1026  
1043  
1063  
1082  
1103  
1.19  
1.36  
1.53  
1.71  
1.90  
1057  
1073  
1092  
1112  
1133  
1.27  
1.44  
1.63  
1.81  
2.02  
1087  
1104  
1123  
1141  
1161  
1.36  
1.54  
1.73  
1.92  
2.13  
1116  
1133  
1151  
1169  
1190  
1.44  
1.63  
1.83  
2.03  
2.26  
1144  
1162  
1179  
1198  
1.52  
1.72  
1.93  
1173 1.61  
1189 1.81  
1206 2.03 1233 2.13  
1200 1.70  
1216 1.91  
1010  
1030  
1051  
1073  
2.15 1225 2.26  
2HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.  
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000  
1. FieldSuppliedFanSheaveAK84andBeltAX34required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Table PD-32 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
1-HPStandardMotor&Drive  
1920  
2160  
2400  
2640  
2880  
565  
609  
660  
710  
762  
0.31  
0.41  
0.54  
0.68  
0.86  
627  
663  
701  
745  
795  
0.39  
0.48  
0.60  
0.76  
0.94  
679  
716  
751  
788  
828  
0.45  
0.57  
0.69  
0.83  
1.02  
726  
762  
798  
833  
869  
0.52  
0.64  
0.78  
0.93  
1.11  
771  
804  
839  
875  
911  
0.60  
0.72  
0.87  
1.04  
1.21  
814  
843  
877  
914  
950  
0.69  
0.80  
0.95  
1.13  
1.33  
857  
883  
914  
949  
986  
0.77  
0.90  
1.04  
1.22  
1.44  
899 0.85  
922 0.99  
950 1.14  
984 1.31  
1019 1.53  
939 0.93  
960 1.08  
984 1.24  
1016 1.42  
1051 1.63  
566  
619  
672  
726  
0.35  
0.47  
0.61  
0.77  
2-HPOversized  
Motor&Drive  
1HP Standard Motor & High Static Drive Kit (or 2 HP Oversized Motor & Drive)  
External Static Pressure (Inches of Water)  
Table PD-32 — Continued  
1.10  
RPM  
1.20  
RPM  
1.30  
RPM  
1.40 1.50 1.60  
RPM RPM RPM  
1.70  
RPM  
1.80  
RPM  
1.90  
RPM BHP  
2.00  
RPM BHP  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HP Standard  
Motor& Drive  
1-HP Standard Motor & High Static Drive Kit  
(or 2 HP oversized Motor& Drive)  
1920  
2160  
2400  
2640  
2880  
978  
996  
1020  
1049  
1081  
1.02  
1015  
1034  
1055  
1081  
1112  
1.11  
1.27  
1.45  
1.65  
1.86  
1051  
1069  
1089  
1113  
1141  
1.20  
1.36  
1.55  
1.76  
1.97  
1086  
1103  
1122  
1144  
1170  
1.30  
1.46  
1.66  
1.87  
2.10  
1118  
1136  
1154  
1176  
1199  
1.39  
1.56  
1.76  
1.98  
2.22  
1150  
1169  
1186  
1207  
1.49  
1.67  
1.86  
2.10  
1180  
1199  
1216  
1237  
1.58  
1.77  
1.97  
2.21  
1209  
1229  
1246  
1.68  
1.88  
1236 1.77  
1258 1.98  
1263 1.86  
1.17  
1.35  
1.53  
1.74  
2.08 1276 2.20  
2-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop  
duetootheroptionsaccessories.  
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000  
1. FieldSuppliedFanSheaveAK84andBeltAX34required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
RT-PRC005-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(6 Ton)  
Standard Efficiency  
Performance  
Data  
Table PD-33 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072,AK — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
2-HPStandardMotor&Drive  
1920  
2160  
2400  
2640  
2880  
-
-
-
-
-
-
-
573  
602  
635  
670  
706  
0.34  
0.42  
0.52  
0.64  
0.78  
630  
656  
682  
715  
749  
0.41  
0.50  
0.60  
0.72  
0.86  
680  
706  
732  
758  
789  
0.48  
0.58  
0.69  
0.81  
0.96  
726  
751  
777  
802  
830  
0.55  
0.65  
0.77  
0.91  
1.06  
769  
792  
818  
845  
870  
0.62  
0.73  
0.86  
1.01  
1.16  
811  
832  
856  
883  
909  
0.70  
0.81  
0.95  
1.10  
1.27  
851 0.78  
871 0.90  
893 1.04  
919 1.20  
945 1.37  
889 0.87  
908 0.99  
930 1.13  
953 1.29  
979 1.48  
548  
584  
621  
660  
0.35  
0.45  
0.56  
0.69  
-
569  
612  
0.47  
0.60  
Table PD-33 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
2-HPStandard Motor&HighStaticDrive  
1920  
2160  
2400  
2640  
2880  
925  
944  
964  
986  
1011  
0.95  
1.08  
1.22  
1.39  
1.58  
960  
978  
998  
1019  
1043  
1.03  
1.17  
1.32  
1.49  
1.69  
994  
1.11  
1.26  
1.42  
1.60  
1.79  
1026  
1043  
1063  
1082  
1103  
1.19  
1.36  
1.53  
1.71  
1.90  
1057  
1073  
1092  
1112  
1133  
1.27  
1.44  
1.63  
1.81  
2.02  
1087  
1104  
1123  
1141  
1161  
1.36  
1.54  
1.73  
1.92  
2.13  
1116  
1133  
1151  
1169  
1190  
1.44  
1.63  
1.83  
2.03  
2.26  
1144  
1162  
1179  
1198  
-
1.52  
1.72  
1.93  
1173 1.61  
1189 1.81  
1206 2.03 1233 2.13  
1200 1.70  
1216 1.91  
1010  
1030  
1051  
1073  
2.15 1225 2.26  
-
-
-
-
-
-
-
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Table PD-34 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072,AK — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
2-HPStandardMotor&Drive  
1920  
2160  
2400  
2640  
2880  
-
-
565  
609  
660  
710  
762  
0.31  
0.41  
0.54  
0.68  
0.86  
627  
663  
701  
745  
795  
0.39  
0.48  
0.60  
0.76  
0.94  
679  
716  
751  
788  
828  
0.45  
0.57  
0.69  
0.83  
1.02  
726  
762  
798  
833  
869  
0.52  
0.64  
0.78  
0.93  
1.11  
771  
804  
839  
875  
911  
0.60  
0.72  
0.87  
1.04  
1.21  
814  
843  
877  
914  
950  
0.69  
0.80  
0.95  
1.13  
1.33  
857  
883  
914  
949  
986  
0.77  
0.90  
1.04  
1.22  
1.44  
899 0.85  
922 0.99  
950 1.14  
984 1.31  
1019 1.53  
939 0.93  
960 1.08  
984 1.24  
1016 1.42  
1051 1.63  
566  
619  
672  
726  
0.35  
0.47  
0.61  
0.77  
Table PD-34 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
1.30  
1.70  
BHP  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandard Motor&HighStaticDrive  
2-HPStandard  
Motor&Drive  
1920  
2160  
2400  
2640  
2880  
978  
996  
1.02  
1.17  
1.35  
1.53  
1.74  
1015  
1034  
1055  
1081  
1112  
1.11  
1.27  
1.45  
1.65  
1.86  
1051  
1069  
1089  
1113  
1141  
1.20  
1.36  
1.55  
1.76  
1.97  
1086  
1103  
1122  
1144  
1170  
1.30  
1.46  
1.66  
1.87  
2.10  
1118  
1136  
1154  
1176  
1199  
1.39  
1.56  
1.76  
1.98  
2.22  
1150  
1169  
1186  
1207  
-
1.49  
1.67  
1.86  
2.10  
-
1180  
1199  
1216  
1237  
-
1.58  
1.77  
1.97  
2.21  
-
1209  
1229  
1246  
-
1.68  
1.88  
1236 1.77  
1258 1.98  
1263 1.86  
-
-
-
-
-
-
-
-
1020  
1049  
1081  
2.08 1276 2.20  
-
-
-
-
-
-
-
2-HPStandardMotor&HighStaticDrive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
42  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(7½ Ton)  
Standard Efficiency  
Performance  
Data  
Table PD-35 — Belt Drive Evaporator Fan Performance — 7½ Ton — TSC090,092A3,A4,AW,AK — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
2-HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
656  
713  
771  
0.71  
0.93  
1.19  
652  
699  
747  
797  
848  
0.54  
0.70  
0.91  
1.15  
1.42  
701  
743  
789  
836  
885  
0.63  
0.79  
0.99  
1.24  
1.53  
750  
787  
827  
873  
921  
0.72  
0.89  
1.10  
1.34  
1.63  
794  
830  
867  
908  
954  
0.81  
0.99  
1.20  
1.45  
1.74  
834  
871  
906  
944  
986  
0.90  
1.09  
1.31  
1.57  
1.87  
873  
908  
944  
980  
1019  
0.98  
1.19  
1.43  
1.69  
1.99  
909 1.08  
943 1.29  
980 1.54  
1016 1.82  
945 1.17  
977 1.39  
1013 1.65  
1050 1.94  
652  
703  
755  
809  
0.63  
0.81  
1.03  
1.29  
1052 2.13 1085 2.26  
Table PD-35 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
2-HPStandard Motor&HighStaticDrive  
Kit (or 3-HP Oversized Motor & Drive)  
2400  
2700  
3000  
3300  
3600  
980  
1010  
1045  
1081  
1116  
1.27  
1.49  
1.76  
2.06  
2.39  
1013  
1043  
1076  
1111  
1.37  
1.60  
1.87  
2.18  
2.53  
1046  
1074  
1105  
1141  
1177  
1.47  
1.71  
1.98  
2.30  
2.66  
1076  
1105  
1134  
1168  
1204  
1.57  
1.82  
2.09  
2.42  
2.79  
1106  
1134  
1163  
1197  
1232  
1.68  
1.93  
2.21  
2.55  
2.93  
1137  
1163  
1192  
1222  
1257  
1.78  
2.04  
2.34  
2.66  
3.05  
1166  
1192  
1219  
1249  
1283  
1.89  
2.16  
2.45  
2.79 1276  
3.19  
1194  
1219  
1247  
1.99  
2.27  
1220 2.08 1248 2.19  
1246 2.39 1273 2.51  
2.58 1272 2.71 1299 2.84  
2.92 1301 3.06 1326 3.19  
1148  
1309 3.32  
3-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.  
1. FieldSuppliedMotorSheave1VL40Lx7/8andFanSheaveAK71required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Table PD-36 — Belt Drive Evaporator Fan Performance — 7½ Ton — TSC090,092A3,A4,AW,AK — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
2400  
2700  
3000  
3300  
3600  
673  
738  
805  
873  
942  
0.56  
0.76  
1.00  
1.29  
1.63  
718  
773  
837  
903  
970  
0.63  
0.83  
1.08  
1.38  
1.74  
769  
817  
870  
930  
996  
0.72  
0.92  
1.17  
1.47  
1.84  
814  
862  
0.82  
1.02  
1.26  
1.57  
1.94  
855  
904  
951  
1000  
1052  
0.90  
1.13  
1.38  
1.68  
2.04  
893  
941  
989  
0.98  
1.23  
1.51  
1.80  
2.16  
929  
975  
1025  
1073  
1121  
1.08  
1.32  
1.62  
1.94  
2.29  
965 1.18  
1009 1.42  
1056 1.72  
1106 2.08  
1153 2.44  
999 1.29  
1041 1.52  
1088 1.82  
1136 2.19  
1184 2.59  
702  
771  
842  
913  
0.68  
0.91  
1.19  
1.53  
912  
963  
1021  
1037  
1086  
3-HPOversizedMotor  
&Drive  
2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor)  
External Static Pressure (Inches of Water)  
Table PD-36 — Continued  
1.10  
1.20  
BHP  
1.30  
1.40 1.50 1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM BHP  
2-HP Standard Motor & High Static Drive Kit  
(or3-HPOversizedMotor&Drive)  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
2400  
2700  
3000  
3300  
3600  
1035  
1073  
1117  
1165  
1215  
1.39  
1.64  
1.93  
2.30  
2.73  
1070  
1104  
1146  
1194  
1242  
1.50  
1.76  
2.05  
2.41  
2.86  
1104  
1136  
1176  
1220  
1269  
1.60  
1.87  
2.17  
2.52  
2.98  
1137  
1167  
1205  
1248  
1295  
1.70  
1168  
1198  
1233  
1275  
1319  
1.81  
2.11  
2.44  
2.79  
3.22  
1201  
1228  
1261  
1301  
1345  
1.92  
2.22  
2.56  
2.93  
3.35  
1232  
1258  
1289  
1326  
2.03 1261  
2.14 1291 2.26  
2.46 1315 2.58 1343 2.69  
2.82 1344 2.95 1372 3.08  
3.22 1378 3.36  
1319 2.38  
1.99  
2.31  
2.66  
3.10  
2.34 1287  
2.69 1317  
3.07 1352  
3-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.  
1. FieldSuppliedMotorSheave1VL40Lx7/8andFanSheaveAK71required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
RT-PRC005-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(8½ Ton)  
Standard Efficiency  
Table PD-37— Belt Drive Evaporator Fan Performance — 8½ Ton — TSC102A3,A4,AW, AK —DownflowAirflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&FieldSupplied  
2-HP Standard Motor  
&Drive  
LowStaticDrive(1)  
2720  
3060  
3400  
3740  
4080  
622  
671  
0.76  
0.96  
612  
659  
706  
0.68  
0.86  
1.08  
613  
650  
689  
729  
770  
0.60  
0.74  
0.91  
1.10  
1.32  
655  
688  
724  
764  
804  
0.72  
0.85  
1.02  
1.23  
1.46  
695  
725  
759  
795  
834  
0.84  
0.98  
1.15  
1.35  
1.60  
733  
761  
792  
826  
864  
0.95  
1.11  
1.29  
1.49  
1.74  
769  
796  
825  
857  
892  
1.08  
1.25  
1.43  
1.64  
1.88  
802 1.21  
828 1.38  
856 1.58  
887 1.79  
920 2.04  
833 1.34  
861 1.52  
887 1.72  
916 1.96  
948 2.20  
611  
651  
693  
738  
0.64  
0.79  
0.97  
1.19  
Table PD-37 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
3-HPOversizedMotor&Drive  
2720  
3060  
3400  
3740  
4080  
863  
891  
917  
945  
976  
1.48  
1.66  
1.87  
2.11  
2.38  
892  
919  
946  
974  
1002  
1.63  
1.81  
2.03  
2.28  
2.56  
920  
946  
974  
1001  
1029  
1.78  
1.96  
2.18  
2.44  
2.73  
946  
973  
1001  
1028  
1055  
1.93  
2.12  
2.34  
2.61  
2.91  
973  
999  
1026  
1054  
1081  
2.08  
2.29  
2.52  
2.78  
3.09  
999  
2.24  
2.46  
2.69  
2.96  
3.26  
1025  
1048  
1074  
1103  
1130  
2.39 1050  
2.63 1072  
2.86 1099  
2.55 1073 2.71 1098 2.88  
1024  
1051  
1079  
1105  
2.80 1096 2.98  
1119 3.14  
1143 3.41  
3.05  
3.32  
1121 3.23  
3.14  
3.45  
1126  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to stnadard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.  
1. FieldSuppliedFanSheaveAK79andBeltAX38required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Table PD-38 — Belt Drive Evaporator Fan Performance — 8½ Ton — TSC102A3,A4,AW, AK —Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
RPM BHP  
1.00  
RPM BHP  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
2-HPStandardMotor&Drive  
2720  
3060  
3400  
3740  
4080  
598  
654  
711  
770  
828  
0.57  
0.77  
1.01  
1.30  
1.65  
646  
693  
743  
799  
857  
0.67  
0.86  
1.10  
1.40  
1.76  
689  
735  
781  
830  
883  
0.78  
0.98  
1.22  
1.51  
1.86  
734  
773  
819  
865  
913  
0.90  
1.10  
1.36  
1.65  
1.99  
781  
812  
853  
899  
945  
1.04  
1.23  
1.49  
1.79  
2.15  
826  
855  
886  
930  
977  
1.18  
1.39  
1.62  
1.94  
2.30  
865  
897  
925  
960  
1006  
1.31  
1.55  
1.79  
2.09  
898 1.44  
934 1.70  
964 1.97  
994 2.26  
928 1.56  
969 1.85  
1000 2.14  
1028 2.44  
616  
675  
735  
796  
0.69  
0.92  
1.20  
1.53  
2.47 1034 2.63 1061 2.79  
3-HPOversizedMotor&Drive  
Table PD-38 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
3-HPOversizedMotor&Drive  
2720  
3060  
3400  
3740  
4080  
956  
999  
1.67  
1.99  
2.32  
2.63  
2.99  
982  
1.79  
2.12  
2.49  
2.84  
3.19  
1008  
1052  
1094  
1129  
1157  
1.91  
2.26  
2.64  
3.03  
3.40  
1033  
1078  
1120  
1158  
2.03  
2.39  
2.79  
3.21  
1056  
1101  
1145  
1185  
2.14  
2.52  
2.94  
3.39  
1079  
1124  
1168  
2.26  
2.66  
3.09  
1102  
1146  
1191  
2.38  
2.79  
3.24 1213  
1125  
1168  
2.50  
2.92  
3.39  
1146 2.62  
1168 2.74  
1026  
1067  
1098  
1125  
1188 3.05 1209 3.18  
1034  
1063  
1093  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.  
1. FieldSuppliedFanSheaveAK79andBeltAX38required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
44  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(10 Ton)  
Standard Efficiency  
Table PD-39 — Belt Drive Evaporator Fan Performance — 10 Ton — TSC120A3,A4,AW,AK — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
3200  
3600  
4000  
4400  
4800  
741  
803  
1.27  
1.62  
715  
773  
833  
747  
803  
861  
1.21  
1.53  
1.90  
718  
764  
814  
864  
916  
0.97  
1.20  
1.49  
1.82  
2.20  
754  
797  
844  
894  
945  
1.10  
1.33  
1.63  
1.98  
2.38  
789  
829  
874  
922  
972  
1.25  
1.48  
1.77  
2.13  
2.55  
822  
860  
903  
948  
997  
1.38  
1.63  
1.93  
2.28  
2.71  
856 1.53  
892 1.79  
932 2.09  
975 2.44  
887 1.67  
922 1.95  
960 2.27  
1001 2.62  
731  
782  
834  
887  
1.08  
1.35  
1.67  
2.04  
1.09  
1.40  
1.76  
1022 2.87 1046 3.04  
3-HPStandardMotor&Drive  
Table PD-39 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3-HPStandardMotor&Drive  
3200  
3600  
4000  
4400  
4800  
917  
951  
988  
1028  
1071  
1.82  
2.11  
2.44  
2.81  
3.23  
945  
979  
1015  
1053  
1095  
1.97  
2.27  
2.62  
3.00  
3.42  
973  
1007  
1042  
1078  
1119  
2.14  
2.43  
2.79  
3.19  
3.62  
999  
1033  
1068  
1103  
1142  
2.30  
2.60  
2.97  
3.38  
3.83  
1024  
2.47  
2.78  
3.15  
3.57  
4.04  
1048  
1082  
1117  
1152  
1189  
2.65  
2.95  
3.33  
3.77  
4.25  
1072  
1107  
1142  
1176  
1212  
2.82 1095  
3.00  
3.33  
3.70  
1117 3.17  
1152 3.52  
1187 3.91  
1140 3.36  
1173 3.71  
1209 4.11  
1059  
1093  
1128  
1166  
3.14  
3.52  
3.96  
1130  
1164  
1198  
4.15 1221 4.36 1243 4.56  
4.66 1256 4.88 1277 5.09  
4.46 1233  
5-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.  
1. FieldSuppliedMotorSheave1VM50x7/8”,FanSheaveAK89 andBeltAX40required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Table PD-40— Belt Drive Evaporator Fan Performance — 10 Ton — TSC120A3,A4,AW,AK — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1.72  
RPM BHP  
RPM BHP  
3-HPStandardMotor&FieldSuppliedLowStaticDrive(1)  
1.13  
1.52  
1.99  
2.56  
3200  
3600  
4000  
4400  
4800  
730  
792  
860  
931  
1002  
1.00  
1.32  
1.73  
2.24  
2.84  
771  
829  
890  
955  
1025  
1.13  
1.45  
1.86  
2.35  
2.96  
807  
865  
923  
983  
1048  
1.26  
1.60  
2.01  
2.49  
3.08  
844  
898  
956  
1014  
1074  
1.39  
1.74  
2.17  
2.66  
3.24  
886  
930  
986  
1045  
1102  
1.55  
1.89  
2.32  
2.84 1072  
3.43 1131  
926  
965  
1015  
965 1.89  
1000 2.06  
729  
802  
876  
950  
761  
833  
905  
977  
1.22  
1.63  
2.12  
2.70  
2.06 1002 2.24 1038 2.43  
2.48 1044 2.65 1077 2.85  
3.01 1098 3.18  
3.63 1156 3.81  
1125 3.36  
1181 4.00  
3-HPStandardMotor&Drive  
5-HPOversizedMotor&Drive  
Table PD-40 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
3-HPStandardMotor&Drive  
1.30  
1.70  
BHP  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
RPM  
BHP  
RPM BHP  
RPM BHP  
3200  
3600  
4000  
4400  
4800  
1029  
1072  
1111  
1152  
1205  
2.20  
2.62  
3.05  
3.55  
4.19  
1057  
1106  
1143  
1182  
2.35  
2.81  
3.26  
3.76  
1084  
1134  
1174  
1211  
1253  
2.49  
2.98  
3.47  
3.99  
4.58  
1108  
1160  
1204  
1241  
1280  
2.63  
3.15  
3.68  
4.21  
4.81  
1132  
1185  
1232  
1270  
1309  
2.77  
3.31  
3.88  
4.44  
5.06  
1155  
1209  
1260  
1299  
1336  
2.91  
3.47  
4.09  
4.68  
5.31  
1177  
1231  
1283  
1327  
1363  
3.05  
1198  
3.18  
1219 3.32 1239 3.46  
3.63 1252  
4.27 1306  
4.91 1352  
3.78 1274 3.94 1295 4.10  
4.46 1327 4.63 1349 4.81  
5.14 1377 5.37 1400 5.57  
1229 4.39  
5.56  
5-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.  
1. FieldSuppliedMotorSheave1VM50x7/8”,FanSheaveAK89 andBeltAX40required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
RT-PRC005-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(3, 4, 5Ton)  
High Efficiency  
Table PD-41— Direct Drive Evaporator Fan Performance — 3, 4, and 5 Ton — THC036A, THC048A, THC060A  
External Static Pressure (Inches ofWater) & Motor Power (Bhp)1  
Standard Motor  
Low Speed  
Oversized Motor  
Low Speed  
Unit  
High Speed  
ESP  
High Speed  
ESP  
Tons Model No.  
CFM  
960  
BHP  
0.36  
0.37  
0.38  
0.39  
0.40  
0.41  
0.42  
0.43  
0.44  
0.53  
0.54  
0.54  
0.55  
0.55  
0.56  
0.56  
0.57  
0.57  
0.78  
0.80  
0.85  
0.88  
0.90  
0.93  
0.94  
0.95  
0.97  
0.36  
0.37  
0.38  
0.39  
0.40  
0.41  
0.42  
0.43  
0.44  
0.53  
0.54  
0.54  
0.55  
0.55  
0.56  
0.56  
0.57  
0.57  
0.78  
0.80  
0.85  
0.88  
0.90  
0.93  
0.94  
0.95  
0.97  
ESP  
0.56  
0.49  
0.44  
0.37  
0.29  
0.19  
0.10  
0.00  
0.79  
0.71  
0.65  
0.56  
0.44  
0.32  
0.17  
0.05  
0.94  
0.81  
0.70  
0.61  
0.45  
0.30  
0.15  
BHP  
0.28  
0.28  
0.29  
0.29  
0.30  
0.30  
0.31  
0.31  
0.47  
0.47  
0.48  
0.48  
0.49  
0.49  
0.50  
0.50  
0.64  
0.65  
0.65  
0.65  
0.66  
0.66  
0.67  
BHP  
0.38  
0.39  
0.41  
0.43  
0.44  
0.45  
0.47  
0.48  
0.51  
0.67  
0.68  
0.70  
0.73  
0.75  
0.78  
0.82  
0.83  
0.85  
0.90  
0.94  
0.98  
1.02  
1.05  
1.10  
1.12  
1.17  
1.20  
0.38  
0.39  
0.41  
0.43  
0.44  
0.45  
0.47  
0.48  
0.51  
0.67  
0.68  
0.70  
0.73  
0.75  
0.78  
0.82  
0.83  
0.85  
0.90  
0.94  
0.98  
1.02  
1.05  
1.10  
1.12  
1.17  
1.20  
ESP  
0.82  
0.77  
0.74  
0.69  
0.65  
0.61  
0.57  
0.52  
0.45  
0.95  
0.90  
0.85  
0.77  
0.68  
0.59  
0.42  
0.29  
0.18  
1.23  
1.13  
1.02  
0.92  
0.81  
0.68  
0.47  
0.23  
0.82  
0.82  
0.79  
0.74  
0.70  
0.66  
0.62  
0.57  
0.50  
1.00  
0.95  
0.90  
0.82  
0.73  
0.64  
0.47  
0.34  
BHP  
0.35  
0.36  
0.38  
0.40  
0.41  
0.42  
0.44  
0.45  
0.48  
0.56  
0.58  
0.60  
0.63  
0.64  
0.66  
0.68  
0.70  
0.73  
0.85  
0.89  
0.91  
0.94  
0.95  
0.96  
0.96  
0.97  
0.35  
0.36  
0.38  
0.40  
0.41  
0.42  
0.44  
0.45  
0.48  
0.56  
0.58  
0.60  
0.63  
0.64  
0.66  
0.68  
0.70  
0.74  
0.69  
0.65  
0.61  
0.55  
0.51  
0.46  
0.41  
0.34  
0.90  
0.83  
0.76  
0.69  
0.60  
0.51  
0.42  
0.31  
0.21  
1.04  
0.97  
0.92  
0.82  
0.74  
0.64  
0.51  
0.42  
0.31  
0.79  
0.74  
0.70  
0.66  
0.60  
0.56  
0.51  
0.46  
0.39  
0.95  
0.88  
0.81  
0.74  
0.65  
0.56  
0.47  
0.36  
0.26  
1.09  
1.02  
0.97  
0.87  
0.79  
0.69  
0.56  
0.47  
0.36  
0.89  
0.85  
0.82  
0.77  
0.74  
0.70  
0.67  
0.64  
0.57  
1.16  
1.11  
1020  
1080  
1140  
1200  
1260  
1320  
1380  
1440  
1280  
1360  
1440  
1520  
1600  
1680  
1760  
1840  
1920  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
960  
1020  
1080  
1140  
1200  
1260  
1320  
1380  
1440  
1280  
1360  
1440  
1520  
1600  
1680  
1760  
1840  
1920  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
3
4
5
3
4
5
THC036A  
Horizontal  
1.06  
1.01  
0.94  
0.89  
0.84  
0.75  
0.67  
1.37  
1.29  
1.21  
1.20  
1.03  
0.94  
0.83  
0.73  
0.60  
0.94  
0.90  
0.87  
0.82  
0.79  
0.75  
0.72  
0.69  
0.62  
1.21  
1.16  
1.11  
1.06  
0.99  
0.94  
0.89  
0.80  
0.72  
1.42  
1.34  
1.26  
1.25  
1.08  
0.99  
0.88  
0.78  
0.65  
THC048A  
Horizontal  
THC060A  
Horizontal  
0.56  
0.54  
0.49  
0.42  
0.34  
0.24  
0.15  
0.05  
0.84  
0.76  
0.70  
0.61  
0.49  
0.37  
0.22  
0.10  
0.99  
0.86  
0.75  
0.66  
0.50  
0.35  
0.20  
0.28  
0.28  
0.29  
0.29  
0.30  
0.30  
0.31  
0.31  
0.47  
0.47  
0.48  
0.48  
0.49  
0.49  
0.50  
0.50  
0.64  
0.65  
0.65  
0.65  
0.66  
0.66  
0.67  
THC036A  
Downflow  
THC048A  
Downflow  
1.28  
1.18  
1.07  
0.97  
0.86  
0.73  
0.52  
0.28  
0.85  
0.89  
0.91  
0.94  
0.95  
0.96  
0.96  
0.97  
THC060A  
Downflow  
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate  
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will  
not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Notes:  
1. Data includes pressure drop due to wet coil and filters.  
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.  
46  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(3 Ton)  
High Efficiency  
Table PD-42 — Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1-HPStandardMotor&Drive  
600*  
720*  
840*  
960  
1080  
1200  
1320  
1440  
552  
588  
0.18  
0.23  
449  
475  
501  
528  
557  
588  
622  
657  
0.06  
0.08  
0.10  
0.12  
0.15  
0.19  
0.23  
0.28  
525  
547  
572  
599  
625  
652  
681  
713  
0.09  
0.11  
0.13  
0.16  
0.19  
0.23  
0.27  
0.33  
593  
612  
634  
658  
685  
712  
738  
765  
0.12  
0.14  
0.17  
0.20  
0.24  
0.28  
0.32  
0.37  
653  
669  
690  
713  
738  
764  
790  
817  
0.16  
0.18  
0.21  
0.24  
0.28  
0.33  
0.38  
0.43  
707  
724  
742  
763  
786  
811  
838  
865  
0.20  
0.22  
0.25  
0.29  
0.33  
0.38  
0.44  
0.50  
757  
774  
791  
810  
832  
856  
882  
909  
0.23  
0.26  
0.29  
0.33  
0.38  
0.43  
0.49  
0.56  
802  
821  
837  
855  
876  
898  
923  
949  
0.27  
0.31  
0.34  
0.38  
0.43  
0.48  
0.55  
0.62  
845 0.31  
864 0.35  
881 0.39  
898 0.43  
917 0.48  
939 0.54  
962 0.60  
987 0.68  
885 0.36  
905 0.40  
922 0.44  
939 0.49  
957 0.54  
978 0.59  
1000 0.66  
1024 0.74  
Table PD-42 — Continued  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow960CFM  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
Electricheatersrestrictedonapplicationsbelow960CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
arerequiredonapplicationsbelow960CFM.  
Notes:  
1-HPStandardMotor&Drive  
600*  
720*  
840*  
960  
1080  
1200  
1320  
1440  
924  
943  
962  
978  
995  
1015  
1036  
1060  
0.40  
0.45  
0.50  
0.54  
0.59  
0.65  
0.72  
0.80  
962  
980  
999  
1016  
1033  
1051  
1072  
1094  
0.45  
0.50  
0.55  
0.60  
0.65  
0.71  
0.78  
0.86  
997  
0.49  
0.55  
0.60  
0.66  
0.71  
0.77  
0.85  
0.93  
1031  
1050  
1068  
1086  
1103  
1120  
1138  
1160  
0.54  
0.60  
0.66  
0.72  
0.78  
0.84  
0.91  
1.00  
1065  
1082  
1103  
1120  
1136  
1154  
1171  
1192  
0.59  
0.65  
0.71  
0.78  
0.84  
0.91  
0.98  
1.07  
1016  
1034  
1052  
1069  
1086  
1106  
1128  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Data does not include pressure drop due to reheat coil.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/  
accessories  
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. BAYLSDR006ARequired.  
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan motors as shown in our tabular  
data will not result in nuisance tripping or premature motor failure. Our product’s  
warranty will not be affected.  
1-HP Standard Motor & Field  
SuppliedHighStaticDrive(2)  
Table PD-43— Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1-HPStandardMotor&Drive  
600*  
720*  
840*  
960  
1080  
1200  
1320  
1440  
493  
523  
555  
588  
622  
654  
687  
723  
0.07  
0.09  
0.12  
0.15  
0.18  
0.23  
0.28  
0.33  
567  
599  
631  
661  
694  
727  
760  
793  
0.11  
0.13  
0.16  
0.19  
0.24  
0.28  
0.34  
0.40  
628  
662  
694  
725  
756  
787  
821  
855  
0.14  
0.17  
0.21  
0.24  
0.29  
0.34  
0.40  
0.47  
683  
716  
750  
782  
813  
843  
875  
908  
0.18  
0.21  
0.25  
0.29  
0.34  
0.40  
0.46  
0.53  
737  
766  
799  
832  
864  
895  
925  
956  
0.22  
0.25  
0.30  
0.35  
0.40  
0.46  
0.53  
0.60  
786  
811  
0.26  
0.29  
0.35  
0.40  
0.46  
0.52  
0.59  
832  
856  
886  
919  
954  
986  
1017  
0.30  
0.34  
0.39  
0.46  
0.52  
0.59  
876 0.35  
899 0.39  
925 0.44  
958 0.51  
993 0.59  
918 0.40  
940 0.44  
965 0.49  
996 0.56  
1031 0.65  
427  
460  
493  
531  
570  
610  
651  
0.06  
0.08  
0.10  
0.13  
0.17  
0.22  
0.27  
844  
878  
910  
942  
973  
1003  
1026 0.66 1064 0.73  
0.66 1058 0.73 1095 0.81  
0.75 1088 0.82 1127 0.89  
0.67 1047  
1-HPStandardMotor&  
Field Supplied High Static Drive (2)  
Table PD-43— Continued  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow960CFM  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
Electricheatersrestrictedonapplicationsbelow960CFM.  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase  
Heatersarerequiredonapplicationsbelow960CFM.  
Notes:  
1-HPStandardMotor&Drive  
600*  
720*  
840*  
960  
1080  
1200  
1320  
1440  
958  
978  
1002  
0.45  
0.49  
0.55  
996  
0.50  
0.55  
0.60  
0.67  
0.76  
0.86  
0.96  
1.05  
1032  
0.55  
0.61  
0.67  
0.73  
0.82  
0.93  
1.04  
1.14  
1068  
1087  
1109  
1133  
1164  
1197  
1230  
1263  
0.60  
0.66  
0.72  
0.79  
0.89  
0.99  
1.11  
1102  
1121  
1143  
1166  
1194  
1227  
1261  
1294  
0.66  
0.72  
0.79  
0.86  
0.95  
1.06  
1.19  
1.30  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/  
accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. BAYLSDR006ARequired.  
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan motors as shown in our tabular  
data will not result in nuisance tripping or premature motor failure. Our product’s  
warranty will not be affected.  
1016  
1039  
1066  
1099  
1133  
1167  
1199  
1053  
1076  
1101  
1132  
1166  
1200  
1232  
1032 0.62  
1065  
1099  
1132  
1164  
0.70  
0.80  
0.88  
0.97  
1.22  
1-HPStandardMotor&  
FieldSuppliedHighStaticDrive(2)  
RT-PRC005-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(4 Ton)  
High Efficiency  
Table PD-44 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1-HPStandardMotor&Drive  
800*  
960*  
1120*  
1280  
1440  
1600  
1760  
1920  
501  
539  
580  
626  
674  
724  
775  
825  
0.09  
0.13  
0.17  
0.23  
0.30  
0.38  
0.48  
0.59  
571  
609  
646  
686  
730  
776  
825  
875  
0.13  
0.17  
0.21  
0.27  
0.34  
0.44  
0.54  
0.66  
633  
668  
706  
744  
783  
825  
870  
918  
0.16  
0.21  
0.26  
0.32  
0.39  
0.49  
0.60  
0.73  
690  
721  
758  
796  
834  
872  
915  
959  
0.20  
0.25  
0.31  
0.38  
0.45  
0.54  
0.66  
0.79  
742  
771  
805  
843  
882  
919  
0.25  
0.29  
0.36  
0.43  
0.52  
0.61  
0.72  
0.86  
792  
819  
0.29  
0.34  
0.41  
0.49  
0.58  
0.68  
0.79  
838  
864  
893  
927  
964  
1002  
1040  
0.34  
0.39  
0.46  
0.54  
0.64  
882 0.39  
906 0.44  
934 0.51  
967 0.60  
923 0.44  
947 0.50  
973 0.57  
1005 0.66  
459  
509  
559  
609  
661  
716  
771  
0.09  
0.13  
0.18  
0.24  
0.32  
0.42  
0.53  
850  
885  
924  
962  
999  
1039  
1002 0.70 1038 0.76  
0.75 1039 0.82 1076 0.89  
0.87 1078 0.95  
1.00 1116 1.09  
958  
1000  
1113 1.03  
1151 1.17  
0.92 1078  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow1280CFM  
Table PD-44 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
Electricheatersrestrictedonapplicationsbelow1280CFM.  
1.10  
RPM  
1.50  
RPM  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase  
Heatersarerequiredonapplicationsbelow1280CFM.  
Notes:  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other  
options/accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. BAYLSDR007ARequired.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all  
cataloged conditions. Using the full horsepower range of our fan motors as shown  
in our tabular data will not result in nuisance tripping or premature motor failure.  
Our product’s warranty will not be affected.  
800*  
960*  
1120*  
1280  
1440  
1600  
1760  
1920  
963  
986  
0.49  
0.55  
0.63  
0.72  
0.83  
0.95  
1.10  
1.26  
999  
0.54  
0.61  
0.69  
0.78  
0.89  
1.02  
1.17  
1.34  
1034  
1060  
1084  
1110  
1141  
1175  
1211  
1249  
0.59  
0.67  
0.75  
0.84  
0.96  
1.09  
1.25  
1.42  
1068  
0.65  
0.73  
0.81  
0.91  
1.03  
1.17  
1.32  
1101  
1127  
1151  
1176  
1205  
1236  
0.70  
0.79  
0.88  
0.98  
1.10  
1.24  
1023  
1048  
1076  
1108  
1142  
1179  
1218  
1095  
1118  
1143  
1174  
1207  
1241  
1012  
1041  
1074  
1109  
1147  
1186  
Table PD-45 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1-HPStandardMotor&Drive  
800*  
960*  
1120*  
1280  
1440  
1600  
1760  
1920  
461  
509  
561  
617  
674  
733  
793  
853  
0.08  
0.11  
0.16  
0.21  
0.29  
0.38  
0.49  
0.62  
553  
600  
649  
696  
745  
799  
854  
911  
0.11  
0.16  
0.21  
0.27  
0.35  
0.45  
0.56  
0.70  
629  
672  
719  
767  
815  
862  
911  
964  
0.16  
0.20  
0.26  
0.34  
0.42  
0.53  
0.65  
0.79  
692  
736  
779  
826  
874  
922  
969  
1018  
0.20  
0.25  
0.32  
0.40  
0.49  
0.60  
0.73  
0.88  
745  
791  
836  
879  
925  
975  
1023  
1069  
0.25  
0.30  
0.37  
0.46  
0.56  
0.68  
0.82  
0.97  
794  
841  
886  
930  
974  
1020  
1069  
1118  
0.29  
0.36  
0.43  
0.52  
0.63  
0.75  
0.90  
1.06  
838  
887  
932  
0.34  
0.42  
0.50  
0.59  
881  
927  
975  
0.38  
0.47  
0.56  
922 0.43  
966 0.52  
1014 0.63 1052 0.69  
962 0.48  
1004 0.58  
976  
1020  
0.66 1060 0.73 1098 0.80  
1020  
1065  
1112  
1161  
0.70 1064  
0.77  
0.91  
1.07  
1.25  
1104 0.85  
1147 0.99  
1191 1.15  
1239 1.34  
1142 0.92  
1186 1.07  
1230 1.24  
1275 1.43  
0.83  
0.98  
1.15  
1107  
1152  
1201  
1-HP Standard Motor & Field  
Table PD-45 — Continued  
SuppliedHighStaticDrive(2)  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
1-HPStandardMotor  
BHP  
BHP  
BHP  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow1280CFM  
800*  
960*  
1120*  
1280  
1440  
1600  
1760  
1920  
1001  
1040  
1087  
1132  
1179  
1223  
1267  
0.54  
0.63  
0.75  
0.88  
1.01  
1.15  
1.33  
1038  
1073  
1119  
1167  
1213  
1258  
1301  
0.60  
0.68  
0.81  
0.95  
1.09  
1.24  
1.42  
1072  
0.65  
0.75  
0.88  
1.03  
1.17  
1.33  
1108  
1141  
1183  
1231  
1277  
1322  
0.71  
0.81  
0.94  
1.10  
1.26  
1.42  
1142  
1175  
1213  
1260  
1307  
0.78  
0.88  
1.00  
1.17  
1.34  
Electricheatersrestrictedonapplicationsbelow1280CFM.  
1108  
1152  
1199  
1245  
1291  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
arerequiredonapplicationsbelow1280CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/  
accessories  
1-HP Standard Motor &  
FieldSuppliedHighStaticDrive(2)  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. BAYLSDR007ARequired.  
2. FieldSuppliedFanSheaveAK41required. FieldSuppliedBeltmaybenecessary.  
Factory supplied motors, in commercial equipment, are  
definitepurposemotors, specificallydesignedandtestedtooperate  
reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data  
will not result in nuisance tripping or premature motor failure. Our  
product’s warranty will not be affected.  
48  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(5 Ton)  
High Efficiency  
Table PD-46— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&  
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1-HPStandard  
Motor&Drive  
LowStaticDriveAccessoryKit(1)  
1000*  
1200*  
1400*  
1600  
1800  
2000  
537  
588  
645  
703  
760  
821  
885  
950  
0.13  
0.19  
0.26  
0.36  
0.47  
0.62  
0.80  
1.02  
608  
652  
702  
757  
815  
873  
930  
990  
0.17  
0.23  
0.31  
0.41  
0.54  
0.69  
0.87  
1.08  
667  
712  
756  
806  
861  
918  
977  
1034  
0.21  
0.28  
0.36  
0.47  
0.60  
0.76  
0.95  
1.16  
721  
764  
808  
854  
904  
958  
1016  
1074  
0.25  
0.33  
0.41  
0.52  
0.66  
0.83  
1.03  
1.25  
770  
811  
0.30  
0.38  
0.48  
0.58  
0.72  
0.90  
1.10  
1.00  
817  
856  
900  
944  
988  
1036  
1089  
1143  
0.35  
0.43  
0.54  
0.65  
0.78  
0.96 1073  
1.17  
1.42  
861  
898  
941  
985  
1028  
0.39  
0.48  
0.59  
0.73  
905 0.45  
939 0.54  
979 0.65  
944 0.50  
517  
576  
640  
706  
773  
840  
909  
0.15  
0.21  
0.31  
0.42  
0.57  
0.75  
0.96  
978 0.59  
1017 0.71  
856  
899  
947  
998  
1053  
1110  
1023 0.79 1060 0.86  
0.86 1067 0.94  
1104 1.02  
1147 1.19  
1191 1.39  
1.02  
1.24  
1.50  
1111 1.10  
1158 1.31  
2200  
2400  
1124  
1177  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow1600CFM  
Table PD-46 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
1.10  
RPM  
1.50  
RPM  
Electricheatersrestrictedonapplicationsbelow1600CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters  
arerequiredonapplicationsbelow1600CFM.  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
Notes:  
1000*  
1200*  
1400*  
1600  
1800  
2000  
985  
1015  
1052  
1093  
1138  
1182  
1226  
0.56  
0.65  
0.77  
0.92  
1.10  
1.28  
1.48  
1021  
1051  
1088  
1126  
1171  
1215  
0.62  
0.71  
0.84  
0.99  
1.17  
1.37  
1058  
0.68  
0.77  
0.90  
1.06  
1.25  
1.46  
1093  
1120  
1153  
1190  
1232  
0.74  
0.84  
0.97  
1.13  
1.32  
1126  
1154  
1185  
1222  
1262  
0.80  
0.91  
1.04  
1.20  
1.39  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/  
accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. BAYLSDR008ARequired.  
2. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan motors as shown in our tabular  
data will not result in nuisance tripping or premature motor failure. Our product’s  
warranty will not be affected.  
1086  
1121  
1160  
1203  
1246  
2200  
2400  
Table PD-47 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1-HPStandardMotor&Drive  
1000*  
1200*  
1400*  
1600  
1800  
2000  
507  
570  
638  
707  
778  
850  
923  
997  
0.11  
0.17  
0.25  
0.35  
0.48  
0.65  
0.84  
1.07  
599  
654  
711  
774  
840  
908  
978  
1049  
0.16  
0.23  
0.31  
0.42  
0.56  
0.73  
0.93  
1.17  
671  
727  
0.21  
0.28  
0.38  
0.50  
0.64  
0.81  
1.02  
1.27  
735  
787  
844  
0.26  
0.34  
0.44  
0.57  
0.72  
0.90  
1.12  
1.37  
792  
843  
896  
0.31  
0.40  
0.51  
0.65  
0.81  
1.00  
1.22  
1.48  
843  
895  
946  
0.37  
0.46  
0.58  
0.72  
0.89  
1.09  
1.32  
889  
942  
993  
1045  
1102  
1157  
1211  
0.42  
0.52  
0.65  
931  
986  
0.48  
0.59  
971 0.54  
1007 0.59  
1026 0.66 1064 0.73  
782  
837  
897  
961  
1028  
1096  
1037  
0.80 1087  
0.72 1078 0.79  
1117 0.86  
1168 1.03  
1219 1.23  
1274 1.47  
898  
953  
1012  
1075  
1140  
953  
1001  
1058  
1111  
1166  
0.87  
1.06  
1.28  
1129 0.95  
1181 1.15  
1237 1.37  
1008  
1062  
1120  
1183  
0.98  
1.19  
1.43  
1143  
1198  
2200  
2400  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow1600CFM  
Table PD-47 — Continued  
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
RPM RPM RPM  
Electricheatersrestrictedonapplicationsbelow1600CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase  
Heatersarerequiredonapplicationsbelow1600CFM.  
1.10  
RPM  
1.50  
RPM  
CFM  
BHP  
BHP  
BHP  
BHP  
BHP  
1-HPStandardMotor&Drive  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/  
accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
1. BAYLSDR008ARequired.  
2. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.  
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,  
specifically designed and tested to operate reliably and continuously at all cataloged  
conditions. Using the full horsepower range of our fan motors as shown in our tabular  
data will not result in nuisance tripping or premature motor failure. Our product’s  
warranty will not be affected.  
1000*  
1200*  
1400*  
1600  
1800  
2000  
1042  
1099  
1153  
1206  
1256  
0.65  
0.80  
0.94  
1.12  
1.32  
1078  
1133  
1188  
1241  
1291  
0.70  
0.86  
1.02  
1.20  
1.41  
1110  
1166  
1221  
1275  
1326  
0.76  
0.93  
1.10  
1.28  
1.50  
1142  
1197  
1253  
1306  
0.82  
0.99  
1.18  
1.37  
1175  
1227  
1284  
1338  
0.89  
1.06  
1.27  
1.46  
2200  
2400  
RT-PRC005-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(6 Ton)  
High Efficiency  
Table PD-48— Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW* — Downflow Airflow— Standard Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied  
1-HPStandardMotor&Drive  
LowStaticDrive(1)  
1920  
2160  
2400  
2640  
2880  
589  
634  
0.50  
0.63  
588  
618  
652  
690  
728  
0.35  
0.44  
0.54  
0.67  
0.82  
643  
672  
701  
734  
770  
0.43  
0.52  
0.63  
0.76  
0.91  
693  
721  
750  
779  
810  
0.50  
0.60  
0.72  
0.85  
1.01  
738  
765  
794  
822  
851  
0.57  
0.68  
0.81  
0.95  
1.11  
782  
806  
834  
864  
892  
0.65  
0.76  
0.90  
1.05  
1.22  
823  
847  
873  
901  
930  
0.73  
0.85  
0.98  
1.15  
1.33  
862 0.81  
885 0.93  
909 1.08  
936 1.24  
965 1.44  
900 0.89  
922 1.02  
945 1.17  
971 1.34  
999 1.54  
564  
602  
642  
682  
0.37  
0.47  
0.59  
0.74  
Table PD-48 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
1.30  
BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HPStandard  
Motor & Drive  
1-HP Standard Motor & High Static Drive Kit  
(or 2 HP Oversized Motor & Drive)  
1920  
2160  
2400  
2640  
2880  
937  
0.98  
1.12  
1.27  
1.44  
1.64  
971  
1.06  
1.21  
1.37  
1.55  
1.75  
1004  
1024  
1046  
1067  
1092  
1.14  
1.30  
1.47  
1.65  
1.86  
1037  
1057  
1076  
1098  
1123  
1.22  
1.40  
1.57  
1.77  
1.98  
1068  
1087  
1106  
1129  
1151  
1.30  
1.49  
1.68  
1.88  
2.09  
1097  
1.38  
1.58  
1.78  
1.99  
2.22  
1127  
1146  
1166  
1185  
1.47  
1.67  
1.89  
2.10 1214  
1154  
1174  
1194  
1.55  
1.76  
1.99  
2.22  
1182 1.64  
1201 1.85  
1220 2.08 1248 2.19  
1210 1.74  
1227 1.95  
957  
980  
1004  
1030  
991  
1117  
1137  
1158  
1181  
1013  
1036  
1061  
2-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000  
1. FieldSuppliedFanSheaveAK84andBeltAX34required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
Table PD-49 — Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW — Horizontal Airflow— Standard Refrigeration System  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard Motor & Field Supplied  
1-HPStandardMotor&Drive  
LowStaticDrive(1)  
1920  
2160  
2400  
2640  
2880  
580  
623  
673  
725  
778  
0.33  
0.43  
0.56  
0.71  
0.90  
641  
679  
718  
762  
811  
0.41  
0.51  
0.63  
0.79  
0.98  
692  
731  
769  
808  
848  
0.47  
0.59  
0.72  
0.87  
1.06  
738  
775  
814  
853  
891  
0.54  
0.67  
0.82  
0.98  
1.16  
783  
817  
855  
894  
932  
0.63  
0.74  
0.90  
1.09  
1.28  
827  
857  
893  
931  
970  
0.71  
0.83  
0.98  
1.17  
1.40  
870  
896  
929  
966  
1004  
0.79  
0.93  
1.08  
1.26  
1.49  
912 0.88  
935 1.02  
965 1.18  
1000 1.36  
1037 1.59  
2-HPOversized  
Motor &Drive  
951 0.96  
974 1.12  
999 1.29  
1032 1.47  
1068 1.69  
578  
633  
688  
743  
0.37  
0.49  
0.64  
0.81  
1-HPStandardMotor&HighStatic  
Drive Kit (or 2-HP Oversized Motor)  
Table PD-49 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
1-HP Standard  
Motor & Drive  
1-HP Standard Motor & High Static Drive Kit  
(or2HPOversizedMotor&Drive)  
1920  
990  
1.05  
1026  
1047  
1070  
1097  
1130  
1.14  
1.31  
1.50  
1.71  
1.93  
1062  
1082  
1104  
1129  
1159  
1.24  
1.40  
1.60  
1.82  
2.05  
1096  
1116  
1137  
1161  
1188  
1.33  
1.50  
1.70  
1.93  
2.18  
1130  
1.43  
1.61  
1.81  
2.05  
2.30  
1160  
1182  
1201  
1223  
1.52  
1.71  
1.92  
2.16  
1190  
1211  
1232  
1252  
1.61  
1.81  
2.03 1261  
2.27  
1218  
1242  
1.71  
1.92  
1247 1.80  
1271 2.03 1298 2.14  
1273 1.90  
2160  
2400  
2640  
2880  
1010  
1035  
1065  
1099  
1.21  
1.39  
1.59  
1.80  
1150  
1168  
1192  
1217  
2.14 1291 2.26  
2-HPOversizedMotor&  
FieldSuppliedDrive(2)  
2-HPOversizedMotor&Drive  
1. FieldSuppliedFanSheaveAK84andBeltAX34required.  
2. FieldSuppliedFanSheaveAK54andBeltAX30.  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
Notes:  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to  
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as  
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty  
will not be affected.  
Data includes pressure drop due to standard filters and wet coils.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due  
tootheroptions/accessories.  
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000  
50  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(7½Ton)  
High Efficiency  
Table PD-50 — Belt Drive Evaporator Fan Performance — 7½ Ton — THC092A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1500*  
1800*  
2100*  
2400  
2700  
3000  
601  
0.68  
487  
522  
559  
599  
640  
0.32  
0.41  
0.51  
0.63  
0.79  
510  
534  
557  
583  
611  
643  
678  
713  
0.30  
0.36  
0.42  
0.50  
0.60  
0.71  
0.86  
1.02  
557  
579  
604  
627  
653  
682  
713  
748  
0.39  
0.45  
0.52  
0.61  
0.71  
0.83  
0.97  
1.14  
602  
621  
645  
669  
693  
719  
748  
780  
0.48  
0.55  
0.62  
0.72  
0.83  
0.95  
1.09  
1.26  
643  
661  
683  
708  
731  
755  
783  
811  
0.57  
0.65  
0.73  
0.83  
0.95  
1.08  
1.23  
1.40  
682  
699  
719  
743  
768  
791  
815  
844  
0.66  
0.75  
0.85  
0.95  
1.07  
1.21  
1.37  
1.55  
718 0.76  
735 0.86  
754 0.97  
776 1.08  
801 1.20  
824 1.35  
848 1.52  
874 1.70  
753 0.87  
770 0.97  
787 1.08  
808 1.21  
832 1.33  
856 1.48  
880 1.66  
904 1.86  
481  
506  
536  
569  
604  
639  
675  
0.27  
0.33  
0.40  
0.50  
0.61  
0.74  
0.89  
3300  
3600  
2-HPStandardMotor&Drive  
Table PD-50— Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
1500*  
1800*  
2100*  
2400  
2700  
3000  
785  
802  
819  
839  
862  
886  
910  
933  
0.99  
1.09  
1.21  
1.34  
1.48  
1.63  
1.81  
2.01  
818  
833  
850  
868  
891  
915  
939  
962  
1.11  
1.20  
1.33  
1.48  
1.62  
1.78  
1.96  
2.17  
847  
863  
880  
898  
918  
942  
967  
990  
1.23  
875  
892  
909  
926  
946  
968  
993  
1016  
1.35  
1.46  
1.59  
1.75  
1.92  
2.09  
2.28  
2.49  
903  
920  
936  
953  
971  
994  
1019  
1042  
1.48  
1.59  
1.72  
1.89  
2.07  
2.25  
2.45  
2.66  
930  
947  
963  
980  
998  
1019  
1043  
1067  
1.62  
1.73  
1.86  
2.04  
2.23  
2.42  
2.62  
2.84  
954  
973  
989  
1006  
1023  
1044  
1066  
1091  
1.74  
1.87  
2.00 1014  
2.18 1032  
2.38 1049  
2.59 1067  
2.79 1091  
977  
998  
1.88  
2.02  
1001 2.01 1023 2.15  
1023 2.17 1048 2.32  
1.32  
1.46  
1.61  
1.77  
1.93  
2.12  
2.33  
2.15 1039 2.30 1064 2.46  
2.34 1056 2.49 1080 2.64  
2.54 1074 2.70 1097 2.86  
2.75 1092 2.93  
2.98  
3.21  
1115 3.09  
1136 3.34  
1158 3.58  
3300  
3600  
1113 3.15  
1137 3.39  
3.02  
1114  
3-HPOversizedMotor&Drive  
2-HP Standard Motor & Low Static DriveAccessory Kit (1)  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow2400CFM  
Electricheatersrestrictedonapplicationsbelow2400CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750  
1. BAYLSDR009ARequired.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
RT-PRC005-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(7½Ton)  
High Efficiency  
Table PD-51 — Belt Drive Evaporator Fan Performance — 7½ Ton — THC092A3,A4,AW—Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1500*  
1800*  
2100*  
2400  
2700  
3000  
3300  
3600  
502  
554  
605  
658  
711  
0.36  
0.49  
0.65  
0.84  
1.07  
509  
542  
568  
603  
644  
684  
728  
776  
0.26  
0.34  
0.42  
0.52  
0.66  
0.82  
1.02  
1.27  
558  
597  
628  
653  
686  
726  
767  
809  
0.32  
0.42  
0.52  
0.63  
0.77  
0.94  
1.15  
1.38  
601  
640  
678  
707  
732  
765  
805  
846  
0.39  
0.50  
0.63  
0.75  
0.89  
1.06  
1.28  
1.52  
640  
678  
718  
754  
780  
806  
840  
880  
0.45  
0.58  
0.72  
0.88  
1.03  
1.20  
1.40  
1.66  
678  
714  
754  
792  
824  
849  
876  
912  
0.52  
0.65  
0.81  
0.99  
1.17  
1.35  
1.55  
1.80  
715  
748  
787  
825  
863  
891  
916  
943  
0.59  
0.73  
0.90  
1.09  
1.30  
1.51  
1.71  
1.95  
750 0.67  
780 0.81  
817 0.99  
857 1.19  
895 1.42  
929 1.66  
955 1.89  
783 0.75  
811 0.89  
846 1.08  
886 1.30  
925 1.54  
962 1.80  
991 2.06  
472  
511  
552  
595  
644  
694  
746  
0.24  
0.33  
0.43  
0.56  
0.73  
0.93  
1.18  
980 2.13 1016 2.30  
2-HPStandardMotor&Drive  
Table PD-51 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
1500*  
1800*  
2100*  
2400  
2700  
3000  
3300  
3600  
815  
842  
876  
913  
954  
992  
1025  
1052  
0.83  
0.98  
1.18  
1.40  
1.66  
1.94  
2.22  
2.50  
847  
872  
0.91  
1.07  
1.27  
1.51  
1.77  
2.07  
2.38  
2.69  
876  
901  
931  
0.99  
1.16  
1.36  
1.61  
1.89  
2.20  
2.53  
2.88  
904  
929  
956  
1.07  
1.25  
1.46  
1.71  
2.00  
2.32  
2.67  
3.05  
932  
957  
982  
1017  
1054  
1094  
1132  
1170  
1.16  
1.35  
1.55  
1.82  
2.12  
2.46  
2.82  
3.21  
958  
983  
1.25  
1.44  
1.66  
1.92  
2.24  
2.58  
2.96  
3.37  
985  
1008  
1034  
1064  
1100  
1138  
1178  
1.34  
1.54  
1.77  
1009  
1034  
1059  
1.43  
1.64  
1.87  
2.14  
2.47  
2.84  
1033 1.51  
1058 1.74  
1083 1.99  
1110 2.26  
1144 2.60  
1181 2.97  
1057 1.61  
1081 1.84  
1107 2.10  
1132 2.37  
1164 2.71  
1202 3.10  
904  
941  
1008  
1040  
1077  
1116  
1156  
1193  
966  
991  
2.04 1087  
981  
1006  
1045  
1082  
1117  
1030  
1069  
1108  
1144  
2.36  
2.71  
3.11  
1121  
1160  
1200  
1019  
1055  
1085  
3.25 1221 3.39  
3-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow2400CFM  
Electricheatersrestrictedonapplicationsbelow2400CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750  
1. BAYLSDR009ARequired.  
2. FieldSuppliedFanSheaveAK79andBeltAX38required.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
52  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(8½ Ton)  
High Efficiency  
Table PD-52— Belt Drive Evaporator Fan Performance — 8½ Ton — THC102A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1700*  
2040*  
2380*  
2720  
3060  
3400  
641  
693  
0.81  
1.03  
481  
511  
545  
584  
626  
669  
713  
758  
0.26  
0.34  
0.42  
0.53  
0.68  
0.84  
1.04  
1.27  
533  
562  
592  
626  
665  
706  
749  
792  
0.35  
0.43  
0.52  
0.64  
0.78  
0.96  
1.17  
1.41  
578  
608  
637  
668  
703  
741  
781  
824  
0.44  
0.52  
0.63  
0.76  
0.90  
1.08  
1.30  
1.56  
621  
649  
678  
708  
740  
775  
813  
854  
0.54  
0.63  
0.74  
0.88  
1.04  
1.21  
1.43  
1.69  
661  
686  
716  
746  
775  
809  
845  
883  
0.64  
0.74  
0.86  
1.00  
1.17  
1.36  
1.58  
1.83  
700  
722  
751  
781  
810  
841  
875  
912  
0.74  
0.85  
0.98  
1.12  
1.30  
1.51  
1.73  
1.99  
736 0.85  
757 0.97  
784 1.11  
814 1.26  
843 1.44  
873 1.65  
905 1.89  
940 2.16  
770 0.96  
791 1.09  
815 1.24  
845 1.40  
875 1.58  
904 1.81  
935 2.06  
968 2.33  
496  
539  
583  
628  
677  
726  
0.33  
0.44  
0.58  
0.72  
0.92  
1.15  
3400  
4080  
2-HPStandardMotor&Drive  
Table PD-52 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
BHP  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
1700*  
2040*  
2380*  
2720  
3060  
3400  
3400  
4080  
802  
823  
846  
874  
905  
933  
964  
995  
1.07  
1.21  
1.37  
1.54  
1.73  
1.96  
2.22  
2.51  
833  
854  
876  
904  
933  
962  
992  
1023  
1.19  
1.34  
1.51  
1.69  
1.89  
2.11  
2.39  
2.69  
864  
884  
906  
930  
960  
990  
1018  
1048  
1.32  
1.47  
1.65  
1.84  
2.05  
2.27  
2.55  
2.86  
893  
913  
1.45  
1.60  
1.79  
2.00  
2.20  
2.44  
2.72  
3.05  
921  
940  
962  
1.59  
1.73  
1.93  
2.14  
2.37  
2.62  
2.90  
3.23  
948  
967  
988  
1010  
1035  
1065  
1095  
1124  
1.72  
1.87  
2.08  
2.30  
2.54  
2.79  
3.08  
3.41  
972  
993  
1.86  
2.01  
2.22 1038  
2.46 1060  
2.71 1083  
2.97  
3.26  
998  
1018  
2.01  
1022 2.15 1045 2.30  
2.16 1043 2.32 1068 2.48  
2.37 1064 2.53 1087 2.69  
2.62 1084 2.78  
2.89  
3.15  
3.45  
934  
1014  
1035  
1059  
1089  
1118  
958  
986  
1016  
1045  
1075  
983  
1109 2.95  
1131 3.24  
1010  
1041  
1071  
1100  
1107 3.06  
1134 3.34  
1112  
1141  
3-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow2720CFM  
Electricheatersrestrictedonapplicationsbelow2720CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750  
1. BAYLSDR009ARequired.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
RT-PRC005-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(8½ Ton)  
High Efficiency  
Table PD-53 — Belt Drive Evaporator Fan Performance — 8½ Ton — THC102A3,A4,AW —Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)  
1700*  
2040*  
2380*  
2720  
3060  
3400  
3740  
4080  
473  
513  
562  
612  
667  
726  
786  
848  
0.24  
0.32  
0.45  
0.60  
0.80  
1.05  
1.36  
1.72  
542  
575  
612  
660  
709  
760  
815  
874  
0.32  
0.42  
0.54  
0.71  
0.91  
1.15  
1.46  
1.83  
591  
634  
666  
703  
750  
800  
850  
903  
0.40  
0.53  
0.66  
0.81  
1.03  
1.29  
1.59  
1.95  
633  
679  
719  
751  
788  
836  
886  
935  
0.47  
0.62  
0.78  
0.95  
1.15  
1.42  
1.74  
2.10  
672  
719  
763  
798  
830  
870  
918  
968  
0.55  
0.71  
0.90  
1.09  
1.29  
1.56  
1.88  
2.26  
707  
754  
800  
841  
873  
907  
949  
998  
0.62  
0.80  
1.01  
1.23  
1.45  
1.71  
2.03  
2.42  
742  
787  
832  
877  
914  
945  
980  
1026  
0.70  
0.89  
1.11  
1.36  
1.62  
1.88  
2.19  
774 0.77  
817 0.97  
863 1.21  
909 1.48  
951 1.77  
984 2.06  
807 0.86  
846 1.06  
893 1.32  
939 1.60  
983 1.92  
1020 2.24  
509  
570  
631  
692  
754  
817  
0.36  
0.52  
0.72  
0.96  
1.26  
1.61  
1015 2.37 1052 2.57  
2.58 1054 2.75 1085 2.94  
2-HPStandardMotor&Drive  
3-HPOversizedMotor&Drive  
Table PD-53 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
BHP  
RPM BHP  
RPM BHP  
2-HPStandardMotor&Drive  
1700*  
2040*  
2380*  
2720  
3080  
3400  
3740  
4080  
839  
876  
920  
0.94  
1.16  
1.42  
1.72  
2.06  
2.41  
2.77  
3.14  
869  
903  
946  
1.03  
1.25  
1.52  
1.84  
2.19  
2.58  
2.96  
3.36  
898  
930  
973  
1018  
1065  
1109  
1149  
1.12  
1.34  
1.63  
1.96  
2.32  
2.73  
3.15  
926  
957  
998  
1042  
1090  
1135  
1178  
1.21  
953  
984  
1021  
1066  
1113  
1159  
1.30  
1.54  
1.83  
2.19  
2.59  
3.04  
980  
1010  
1047  
1089  
1136  
1183  
1.40  
1.64  
1.95  
2.31  
2.73  
3.19  
1005  
1036  
1069  
1112  
1158  
1204  
1.49  
1.75  
2.05 1093  
2.43  
2.86  
3.33  
1031  
1061  
1.59  
1.86  
2.16  
2.55  
2.99  
1054 1.68  
1084 1.96  
1115 2.27  
1155 2.67  
1078 1.78  
1108 2.07  
1138 2.39  
1176 2.79  
1.44  
1.73  
2.07  
2.46  
2.88  
3.34  
967  
994  
1134  
1179  
1012  
1052  
1086  
1117  
1039  
1083  
1119  
1151  
1199 3.12 1220 3.26  
3-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow2720CFM  
Electricheatersrestrictedonapplicationsbelow2720CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.  
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750  
1. BAYLSDR009ARequired.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
54  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(10 Ton)  
High Efficiency  
Table PD-54— Belt Drive Evaporator Fan Performance — 10 Ton — THC120A3,A4,AW — Downflow Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3-HP Standard Motor & Low Static Drive Accessory Kit(1)  
2000*  
2400*  
2800*  
3200  
3600  
4000  
576  
638  
701  
764  
828  
0.57  
0.78  
1.04  
1.36  
1.74  
568  
606  
649  
697  
749  
803  
857  
913  
0.43  
0.56  
0.71  
0.90  
1.14  
1.44  
1.79  
2.18  
613  
650  
689  
734  
782  
834  
888  
942  
0.53  
0.67  
0.83  
1.03  
1.27  
1.58  
1.95  
2.36  
653  
691  
728  
770  
815  
863  
916  
970  
0.64  
0.78  
0.95  
1.17  
1.41  
1.72  
2.10  
2.53  
691  
728  
766  
804  
847  
894  
943  
996  
0.75  
0.90  
1.08  
1.31  
1.57  
1.87  
2.25  
2.70  
727  
763  
801  
839  
879  
923  
970  
1021  
0.86  
1.02  
1.21  
1.45  
1.73  
2.04  
2.41  
763 0.98  
796 1.16  
833 1.35  
871 1.60  
909 1.89  
952 2.21  
997 2.59  
797 1.10  
826 1.29  
864 1.50  
901 1.74  
939 2.04  
979 2.39  
1024 2.78  
564  
618  
675  
734  
795  
857  
0.50  
0.67  
0.89  
1.16  
1.49  
1.88  
607  
659  
714  
768  
825  
884  
0.60  
0.79  
1.02  
1.30  
1.63  
2.02  
4400  
4800  
2.86 1045 3.03 1070 3.22  
3-HPStandardMotor&Drive  
Table PD-54 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
BHP  
1.70  
BHP  
1.80  
RPM  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3-HPOversizedMotor&Drive  
2000*  
2400*  
2800*  
3200  
3600  
4000  
828  
858  
894  
931  
969  
1007  
1050  
1095  
1.22  
1.43  
1.65  
1.89  
2.21  
2.57  
2.97  
3.42  
859  
888  
921  
959  
997  
1034  
1075  
1119  
1.35  
1.56  
1.79  
2.06  
2.37  
2.74  
3.17  
3.62  
888  
916  
949  
1.48  
917  
945  
1.61  
1.85  
2.11  
2.39  
2.72  
3.11  
3.55  
4.05  
945  
972  
1.75  
1.99  
2.27  
2.56  
2.89  
3.29  
3.75  
4.26  
971  
998  
1.88  
2.14  
2.43  
2.74  
3.08  
3.47  
3.94  
4.47  
998  
1023  
1051  
1084  
1122  
1159  
1198  
1235  
2.03 1023  
2.29 1050  
2.59 1076  
2.19  
1048 2.35 1072 2.50  
1.70  
1.95  
2.22  
2.54  
2.93  
3.36  
3.83  
2.45 1073 2.60 1097 2.76  
975  
1001  
1037  
1074  
1112  
1150  
1189  
1027  
1061  
1098  
1136  
1173  
1212  
2.75  
3.09  
3.46  
1100 2.92  
1131 3.28  
1166 3.65  
1123 3.09  
1153 3.46  
1188 3.85  
986  
1012  
1050  
1087  
1126  
1166  
2.91  
3.27  
3.66  
4.15  
1108  
1145  
1182  
1219  
1024  
1062  
1101  
1143  
3.86 1204 4.07 1226 4.28  
4.34 1241 4.54 1264 4.77  
4.90 1280 5.12 1300 5.32  
4400  
4800  
4.68 1258  
5-HPOversizedMotor&Drive  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow3200CFM  
Electricheatersrestrictedonapplicationsbelow3200CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 3200 CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.  
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.  
1. BAYLSDR010ARequired.  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
RT-PRC005-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(10 Ton)  
High Efficiency  
Table PD-55— Belt Drive Evaporator Fan Performance — 10 Ton — THC120A3,A4,AW —Horizontal Airflow  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM BHP  
RPM BHP  
3-HP Standard Motor & Low Static DriveAccessory Kit (1)  
2000*  
2400*  
2800*  
3200  
3600  
4000  
4400  
4800  
578  
640  
706  
777  
850  
925  
1000  
584  
627  
686  
748  
811  
0.43  
0.57  
0.79  
1.06  
1.39  
1.81  
2.32  
2.95  
639  
683  
728  
787  
849  
912  
977  
1046  
0.53  
0.70  
0.90  
1.19  
1.54  
1.95  
2.46  
3.07  
682  
734  
776  
824  
883  
0.62  
0.83  
1.04  
1.32  
1.68  
2.12  
2.63  
3.23  
721  
776  
822  
864  
916  
0.71  
0.94  
1.19  
1.47  
1.82  
2.28  
2.81  
3.42  
755  
812  
865  
906  
950  
1006  
1067  
1130  
0.79  
1.05  
1.34  
1.64  
1.98  
2.43 1035  
2.98 1094  
787  
845  
900  
946  
987  
0.88  
1.15  
1.47  
1.81  
818 0.97  
876 1.26  
932 1.60  
983 1.97  
849 1.06  
904 1.36  
962 1.73  
1015 2.13  
0.48  
0.67  
0.93  
1.27  
1.70  
2.21  
2.83  
596  
671  
746  
822  
898  
974  
0.58  
0.85  
1.18  
1.59  
2.09  
2.69  
2.16 1024 2.35 1060 2.55  
2.60 1067 2.79  
3.16  
3.81  
879  
950  
1023  
946  
977  
1101 2.99  
1147 3.52  
1206 4.19  
1008  
1072  
1039  
1101  
1121 3.33  
1181 4.00  
3.62  
1156  
5-HPOversizedMotor&Drive  
Table PD-55 — Continued  
External Static Pressure (Inches of Water)  
1.40 1.50 1.60  
1.10  
1.20  
BHP  
1.30  
1.70  
BHP  
3-HPStandardMotor&Drive  
1.80  
1.90  
2.00  
CFM  
RPM  
BHP  
RPM  
RPM  
BHP  
RPM  
BHP RPM RPM  
BHP  
BHP  
RPM  
RPM  
BHP  
RPM BHP  
RPM BHP  
2000*  
2400*  
2800*  
3200  
3600  
4000  
4400  
4800  
877  
931  
989  
1044  
1093  
1135  
1177  
1229  
1.15  
1.47  
1.84  
2.28  
2.74  
3.21  
3.73  
4.39  
906  
958  
1.24  
1.58  
1.97  
2.42  
2.92  
3.42  
3.96  
4.59  
933  
983  
1.33  
1.68  
2.09  
2.57  
3.09  
3.63  
4.19  
4.83  
961  
1.43  
1.78  
2.21  
2.71  
3.25  
3.84  
4.42  
5.07  
988  
1.54  
1.89  
2.34  
2.84  
3.42  
4.05  
4.67  
5.32  
1014  
1056  
1110  
1168  
1224  
1278  
1324  
1365  
1.64  
2.00  
2.46  
2.99  
3.58  
4.23  
4.90  
5.58  
1038  
1080  
1132  
1189  
1246  
1301  
1351  
1.74  
2.11  
2.58  
3.12 1210  
3.74 1268  
4.41 1323  
5.12 1376  
1063  
1103  
1154  
1.85  
2.22  
2.71  
1087 1.96  
1126 2.34  
1176 2.83  
1111 2.07  
1149 2.46  
1196 2.95  
1008  
1064  
1122  
1176  
1227  
1268  
1310  
1032  
1087  
1145  
1201  
1254  
1297  
1338  
1015  
1072  
1124  
1167  
1207  
1254  
1040  
1097  
1151  
1198  
1239  
1282  
3.27 1231 3.41 1250 3.54  
3.90 1289 4.06 1308 4.20  
4.60 1344 4.77 1365 4.95  
5.35 1398 5.56 1420 5.75  
5-HPOversizedMotor&Drive  
3-HPStandardMotor&Low  
StaticDriveAccessoryKit(1)  
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.  
TableincludesDehumidification(HotGasReheatOption).  
*Unitapplicationsbelow3200CFM  
Electricheatersrestrictedonapplicationsbelow3200CFM.  
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 3200 CFM.  
Notes:  
Data includes pressure drop due to standard filters and wet coils.  
Data does not include pressure drop due to reheat coil.  
No accessories or options are included in pressure drop data.  
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories  
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.  
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.  
1. BAYLSDR010ARequired.  
1. FieldSuppliedMotorSheave1VM50x7/8inch,FanSheaveAK89,andBeltAX40required  
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full  
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.  
56  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-56— Standard Motor & Sheave/Fan Speed (Rpm)  
Unit  
6Turns  
Open  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
5Turns  
Open  
745  
833  
897  
723  
835  
787  
908  
4Turns  
Open  
819  
916  
987  
779  
891  
847  
969  
3Turns  
Open  
894  
1000  
1077  
835  
946  
908  
1029  
2Turns  
Open  
968  
1083  
1166  
890  
1002  
968  
1090  
1Turn  
Open  
1043  
1167  
1256  
946  
1057  
1029  
1150  
Tons  
3
Model No.  
T*C036A  
T*C048A  
T*C060A  
T*C072A  
TSC090,092A  
T*C102A  
T*C120A  
Closed  
1117  
4
5
6
7½  
8½  
10  
1250  
1346  
1002  
1113  
1089  
1211  
Factory set at 3 turns open.  
Table PD-57— Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)  
Tons  
Unit Model  
Number  
THC036A  
Drive Accessory  
Kit  
BAYLSDR006A AK84x3/4" 427  
AK69x3/4" 522  
BAYLSDR007A AK79x3/4" 455  
AK61x3/4" 593  
BAYLSDR008A AK71x3/4" 507  
AK59x3/4" 614  
BAYLSDR009A AK99x1"  
AK79x1"  
BAYLSDR009A AK99x1"  
AK79x1"  
Fan  
5Turns  
4Turns  
Open  
470  
574  
500  
652  
558  
675  
498  
627  
498  
627  
600  
3Turns 2Turns  
1Turn  
Open  
597  
732  
637  
831  
710  
860  
604  
761  
604  
761  
713  
910  
Sheave Open  
Open  
512  
627  
546  
712  
609  
737  
533  
672  
533  
672  
638  
815  
Open  
555  
679  
591  
771  
659  
798  
569  
716  
569  
716  
675  
862  
Closed  
640  
784  
682  
890  
761  
921  
640  
806  
640  
806  
750  
958  
3
4
THC048A  
THC060A  
THC092A  
THC102A  
THC120A  
5
7.5  
8.5  
10  
462  
582  
462  
582  
563  
719  
BAYLSDR010A  
AK94x1"  
AK74x1"  
767  
Factory set at 3 turns open.  
Table PD-58— Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)  
Unit  
6Turns  
Open  
N/A  
N/A  
N/A  
5Turns  
Open  
831  
958  
958  
4Turns  
Open  
895  
1022  
1022  
3Turns  
Open  
959  
1086  
1086  
2Turns  
Open  
1022  
1150  
1Turn  
Open  
1086  
1214  
1214  
Tons  
6
6
Model No.  
T*C072A3,A4,AW  
TSC072AK  
TSC090,092A  
Closed  
1150  
1278  
1278  
7½  
1150  
Factory set at 3 turns open.  
Table PD-59— Oversized Motor & Drive Sheave/Fan Speed (Rpm)  
Unit  
6Turns  
Open  
N/A  
N/A  
N/A  
5Turns  
Open  
958  
1068  
958  
4Turns  
Open  
1022  
1150  
1022  
1200  
3Turns  
Open  
1086  
1232  
1086  
1275  
2Turns  
Open  
1150  
1315  
1150  
1Turn  
Open  
1214  
1397  
1214  
1425  
Tons  
6
7½  
8½  
10  
Model No.  
T*C072A3,A4,AW  
TSC090,T*C092A  
T*C102A  
Closed  
1278  
1479  
1278  
N/A  
T*C120A  
1050  
1135  
1350  
Factory set at 3 turns open.  
Table PD-60— Outdoor Sound Power Level - dB (ref. 10 -12 Watts)  
Unit  
Octave Center Frequency  
Overall  
Tons  
3
Model No.  
T*C036A  
63.  
86  
92  
90  
92  
94  
94  
90  
91  
92  
89  
92  
88  
91  
91  
94  
125  
83  
87  
84  
86  
87  
87  
94  
95  
95  
93  
96  
92  
95  
88  
89  
250  
81  
84  
78  
83  
83  
82  
90  
90  
91  
88  
92  
87  
90  
84  
87  
500  
80  
83  
77  
82  
82  
81  
87  
87  
88  
85  
89  
84  
87  
82  
85  
1000  
78  
81  
76  
81  
79  
78  
83  
84  
84  
81  
85  
80  
84  
81  
84  
2000  
74  
76  
72  
75  
75  
74  
78  
79  
80  
76  
80  
75  
79  
76  
78  
4000  
69  
72  
70  
72  
73  
72  
74  
75  
75  
72  
76  
72  
75  
73  
75  
8000  
dBA  
83  
86  
82  
85  
84  
84  
88  
89  
90  
87  
91  
86  
89  
86  
88  
68  
69  
68  
69  
69  
69  
67  
68  
68  
66  
69  
65  
68  
67  
69  
TSC048A1  
TSC048A3,A4,AW  
THC048A  
TSC060A  
THC060A  
TSC072A  
THC072A  
TSC090A  
TSC092A  
THC092A  
TSC102A  
THC102A  
TSC120A  
THC120A  
4
5
6
7½  
8½  
10  
*IndicatesbothStandardand  
High Efficiency.  
Note:  
TestsfollowARI270-95.  
RT-PRC005-EN  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-61— Static Pressure Drop Through Accessories (Inches Water Column) — 3-10 Tons  
Economizerwith  
2 Inch  
Pleated Filter 100% OA 100% RA 100% OA 100% RA  
Electric Heater  
Unit  
ModelNo.  
Standard Through  
OA/RADampers2  
Accessory (kW)3  
5-6  
Tons  
CFM  
Filters1  
Reheat  
9-15  
17-36  
54  
Coil (WC)  
Downflow  
Horizontal  
960  
1200  
1440  
600  
0.03  
0.04  
0.06  
0.01  
0.02  
0.03  
0.04  
0.04  
0.05  
0.08  
0.02  
0.04  
0.05  
0.08  
0.10  
0.15  
0.22  
0.02  
0.04  
0.06  
0.09  
0.04  
0.06  
0.09  
0.06  
0.10  
0.14  
0.02  
0.04  
0.06  
0.09  
0.05  
0.08  
0.12  
0.02  
0.05  
0.08  
0.12  
0.07  
0.11  
0.16  
0.03  
0.07  
0.11  
0.16  
.01  
.03  
.04  
.06  
0.05  
0.07  
0.10  
0.03  
0.04  
0.05  
0.07  
0.06  
0.09  
0.12  
0.03  
0.06  
0.09  
0.12  
0.15  
0.22  
0.29  
0.04  
0.07  
0.10  
0.14  
0.07  
0.09  
0.12  
0.09  
0.13  
0.18  
0.03  
0.06  
0.09  
0.13  
0.08  
0.11  
0.16  
0.05  
0.08  
0.11  
0.16  
0.10  
0.15  
0.20  
0.06  
0.10  
0.15  
0.20  
0.05  
0.07  
0.10  
0.03  
0.05  
0.07  
0.10  
0.08  
0.12  
0.17  
0.04  
0.08  
0.12  
0.17  
0.12  
0.18  
0.26  
0.06  
0.12  
0.18  
0.26  
0.10  
0.11  
0.13  
0.11  
0.14  
0.21  
0.07  
0.11  
0.14  
0.21  
0.12  
0.19  
0.30  
0.07  
0.12  
0.19  
0.30  
0.17  
0.26  
0.34  
0.08  
0.17  
0.26  
0.34  
0.01  
0.02  
0.03  
0.01  
0.01  
0.02  
0.03  
0.03  
0.04  
0.06  
0.01  
0.03  
0.04  
0.06  
0.04  
0.07  
0.10  
0.01  
0.04  
0.07  
0.10  
0.01  
0.02  
0.04  
0.02  
0.05  
0.07  
0.01  
0.02  
0.05  
0.07  
0.03  
0.06  
0.07  
0.01  
0.03  
0.06  
0.07  
0.05  
0.07  
0.09  
0.03  
0.05  
0.07  
0.09  
0.05  
0.07  
0.10  
0.03  
0.05  
0.07  
0.10  
0.08  
0.12  
0.17  
0.04  
0.08  
0.12  
0.17  
0.12  
0.18  
0.26  
0.06  
0.12  
0.18  
0.26  
0.06  
0.08  
0.10  
0.08  
0.12  
0.25  
0.04  
0.08  
0.12  
0.25  
0.09  
0.18  
0.31  
0.05  
0.09  
0.18  
0.31  
0.14  
0.30  
0.35  
0.07  
0.14  
0.30  
0.35  
0.00  
0.01  
0.01  
0.00  
0.00  
0.01  
0.01  
0.01  
0.01  
0.02  
0.00  
0.01  
0.01  
0.02  
0.01  
0.02  
0.04  
0.01  
0.01  
0.02  
0.04  
0.02  
0.02  
0.04  
0.02  
0.05  
0.08  
0.01  
0.02  
0.05  
0.08  
0.04  
0.06  
0.09  
0.02  
0.04  
0.06  
0.09  
0.05  
0.08  
0.10  
0.02  
0.05  
0.08  
0.10  
.013  
.020  
.029  
.013  
.020  
.029  
.023  
.036  
.052  
.023  
.036  
.052  
.036  
.056  
.081  
.036  
.056  
.081  
0.02  
0.02  
0.04  
0.02  
0.05  
0.08  
0.02  
0.05  
0.08  
0.04  
0.06  
0.09  
0.04  
0.06  
0.09  
0.05  
0.08  
0.10  
.016  
.025  
.036  
.016  
.025  
.036  
.029  
.045  
.064  
.029  
.045  
.064  
.045  
.070  
.100  
.045  
.070  
.100  
0.011  
0.020  
0.033  
0.020  
0.042  
0.077  
0.016  
0.025  
0.036  
0.020  
0.032  
0.047  
0.020  
0.032  
0.047  
0.028  
0.045  
0.065  
.019  
.030  
.043  
TSC036A  
3
960  
.019  
THC036A  
TSC048A  
1200  
1440  
1280  
1600  
1920  
800  
1280  
1600  
1920  
1600  
2000  
2400  
1000  
1600  
2000  
2400  
1920  
2400  
2880  
2400  
.030  
.043  
.034  
.053  
.077  
.034  
.053  
.077  
.053  
.083  
.120  
.053  
.083  
.120  
0.021  
0.034  
0.052  
0.034  
0.063  
0.102  
0.021  
0.032  
0.046  
0.026  
0.041  
0.059  
4
.02  
.05  
.07  
.09  
THC048A  
TSC060A  
THC060A  
5
.03  
.07  
.10  
.14  
6
T*C072A  
TSC090,092A 3000  
3600  
1500  
2400  
7½  
.07  
.10  
.14  
.19  
THC092A  
TSC102A  
3000  
3600  
2720  
3400  
4080  
1700  
2720  
3400  
4080  
3200  
4000  
4800  
2000  
3200  
4000  
4800  
8½  
.08  
.12  
.17  
.23  
0.09  
0.15  
0.22  
0.31  
0.026  
0.041  
0.059  
0.036  
0.056  
0.081  
0.036  
0.056  
0.081  
THC102A  
TSC120A  
THC120A  
0.042  
0.070  
0.106  
0.042  
0.070  
0.106  
10  
0.05  
0.08  
0.10  
0.028  
0.045  
0.065  
Notes:  
1. Tested with standard filters (3-5 tons 1” filters, 6-10 tons 2” filters). Difference in pressure drop should be considered when utilizing optional 2” pleaated filters.  
2. OA = Outside Air and RA = Return Air.  
3. Nominal kW ratings at 240, 480, 600 volts.  
* Indicates both Standard and High Efficiency.  
58  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-62— Auxiliary Electric Heat Capacity  
Total2  
Stage1  
Stage 2  
Unit  
ModelNo.  
kW  
Input1  
MBH  
Output1  
No. of  
Stages  
kW  
Input1  
MBH  
Output1  
kW  
Input1  
MBH  
Output1  
Tons  
3
5.00  
10.00  
13.80  
17.07  
34.14  
47.11  
1
2
2
5.00  
5.00  
8.80  
17.07  
17.07  
30.04  
5.00  
5.00  
17.07  
17.07  
T*C036A1  
6.00  
12.00  
17.40  
5.00  
20.48  
40.97  
59.40  
17.07  
1
2
2
1
6.00  
6.00  
8.70  
5.00  
20.48  
20.48  
29.70  
17.07  
6.00  
8.70  
T*C036A3, A4, AW  
20.48  
29.69  
10.00  
13.80  
17.60  
34.14  
47.11  
60.09  
2
2
2
5.00  
8.80  
8.80  
17.07  
30.04  
30.04  
5.00  
5.00  
8.80  
17.07  
17.07  
30.04  
T*C048A1  
4
5
6.00  
12.00  
17.40  
20.48  
40.97  
59.40  
1
2
2
6.00  
6.00  
8.70  
20.48  
20.48  
29.70  
6.00  
8.70  
20.48  
29.70  
T*C048A3, A4, AW  
5.00  
10.00  
13.80  
17.60  
17.07  
34.14  
47.11  
60.09  
1
2
2
2
5.00  
5.00  
8.80  
8.80  
17.07  
17.07  
30.04  
30.04  
5.00  
5.00  
8.80  
17.07  
17.07  
30.04  
T*C060A1  
6.00  
12.00  
17.40  
23.00  
20.48  
40.97  
59.40  
78.52  
1
2
2
2
6.00  
6.00  
8.70  
20.48  
20.48  
29.70  
48.82  
T*C060A3, A4, AW  
6.00  
8.70  
8.70  
20.48  
29.70  
29.70  
14.30  
7.50  
10.90  
14.4  
25.61  
37.23  
49.18  
2
2
2
3.25  
5.45  
7.20  
11.10  
18.61  
24.59  
3.25  
5.45  
7.20  
11.10  
18.61  
24.59  
TSC060AK  
9.00  
18.00  
27.00  
36.00  
30.73  
61.45  
92.18  
1
1
2
2
9.00  
18.00  
18.00  
18.00  
30.73  
61.45  
61.45  
61.45  
9.00  
18.00  
30.73  
61.45  
T*C072A3, A4, AW  
6
122.90  
11.30  
16.90  
22.60  
38.60  
57.72  
77.18  
1
2
2
11.30  
11.30  
11.30  
38.60  
38.60  
38.60  
5.60  
11.30  
19.13  
38.60  
TSC072AK  
9.00  
18.00  
27.00  
36.00  
30.73  
61.45  
92.18  
1
1
2
2
9.00  
18.00  
18.00  
18.00  
30.73  
61.45  
61.45  
61.45  
9.00  
18.00  
30.73  
61.45  
T*SC090A3, A4, AW  
122.90  
11.30  
16.90  
22.60  
38.60  
57.72  
77.18  
1
2
2
11.30  
11.30  
11.30  
38.60  
38.60  
38.60  
5.60  
11.30  
19.13  
38.60  
7½  
TSC090AK  
9.00  
18.00  
27.00  
36.00  
30.73  
61.45  
92.18  
1
1
2
2
9.00  
18.00  
18.00  
18.00  
30.73  
61.45  
61.45  
61.45  
9.00  
18.00  
30.73  
61.45  
T*C092A3, A4, AW  
122.90  
9.00  
18.00  
27.00  
36.00  
30.73  
61.45  
92.18  
1
1
2
2
9.00  
18.00  
18.00  
18.00  
30.73  
61.45  
61.45  
61.45  
9.00  
18.00  
30.73  
61.45  
T*C102A3, A4, AW  
TSC102AK  
8½  
122.90  
16.90  
22.60  
18.00  
57.72  
77.18  
61.45  
2
2
1
11.30  
11.30  
18.00  
38.60  
38.60  
61.45  
5.60  
11.30  
19.13  
38.60  
T*C120A3, A4, AW  
27.00  
36.00  
54.00  
92.18  
122.90  
184.36  
2
2
2
18.00  
18.00  
36.00  
61.45  
61.45  
122.90  
9.00  
18.00  
18.00  
30.73  
61.45  
61.45  
10  
16.90  
22.60  
33.80  
57.72  
77.18  
115.43  
2
2
2
11.30  
11.30  
22.50  
38.60  
38.60  
76.84  
11.30  
11.30  
11.30  
38.60  
38.60  
38.60  
TSC120AK  
Notes:  
1. Does not include indoor fan power or heat.  
2. Heaters are rated at 240v, 380v, 480v. and 600v. For other than rated voltage, CAP =  
2
Voltage  
RatedVoltage  
x rated cap.  
(
)
* Indicates both Standard and High Efficiency.  
RT-PRC005-EN  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-63— Electric Heater Voltage  
Correction Factors (Applicable to Auxiliary  
Heat Capacity)  
Nominal  
Voltage  
Distribution  
Voltage  
Capacity  
Multiplier  
208  
230  
240  
380  
440  
460  
480  
540  
575  
600  
0.751  
0.918  
1.000  
1.000  
0.840  
0.918  
1.000  
0.810  
0.918  
1.000  
240  
380  
480  
600  
Table PD-64 — 3-5 Tons Air Temperature Rise Across Electric Heaters (Degrees F)  
3Ton  
4Ton  
5Ton  
1
1200 CFM  
1600CFM  
2000CFM  
SinglePhase  
Stages T*C036A1  
ThreePhase  
T*C036A3,A4,AW  
SinglePhase  
T*C048A1  
ThreePhase  
T*C048A3,A4,AW  
SinglePhase  
T*C060A1  
ThreePhase  
kW  
5.00  
6.00  
7.50  
10.00  
10.90  
12.00  
13.80  
14.40  
17.40  
17.60  
23.00  
T*C060A3,A4,AW  
TSC060AK  
1
1
2
2
2
2
2
2
2
2
2
13.2  
26.3  
36.4  
15.8  
31.6  
45.8  
9.9  
19.8  
27.3  
34.8  
11.9  
23.7  
34.4  
7.9  
15.8  
21.8  
27.8  
9.5  
19.0  
27.5  
36.4  
11.9  
17.2  
22.8  
For minimum design airflow, see airflow performance table for each unit.  
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =  
Note:  
kWx3414  
1.08xCFM  
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.  
Table PD-65 — 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)  
6Ton  
2000CFM  
7½Ton  
3000CFM  
8½Ton  
3400CFM  
10Ton  
4000CFM  
1
T*C090A3, A4, AW  
kW  
9.00  
Stages T*C072A3, A4, AW TSC072AK T*C092A3, A4, AW  
TSC090AK  
T*C102A3, A4, AW TSC102AK T*C120A3,A4,AW  
TSC120AK  
1
1
2
1
2
2
2
2
2
14.2  
28.5  
42.7  
14.9  
22.3  
29.8  
9.5  
19.0  
28.5  
11.9  
17.8  
23.8  
8.4  
13.4  
17.9  
26.7  
11.30  
16.90  
18.00  
22.60  
27.00  
33.80  
36.00  
54.00  
16.7  
25.1  
15.7  
21.0  
14.2  
21.3  
56.9  
37.9  
33.5  
28.5  
42.7  
For minimum design airflow, see airflow performance table for each unit.  
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =  
Note:  
kWx3414  
1.08xCFM  
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.  
* Indicates both Standard and High Efficiency.  
60  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-66— Hot Gas Reheat Temperature Rise3  
Leaving Evaporator Dry Bulb [F]  
Tons  
SCFM  
600  
720  
840  
960  
1080  
1200  
1320  
1440  
35  
40  
45  
50  
55  
60  
65  
20.3  
19.4  
18.5  
17.6  
16.7  
15.8  
14.9  
14.0  
20.0  
19.1  
18.2  
17.3  
16.4  
15.5  
14.6  
13.8  
19.6  
18.7  
17.9  
17.0  
16.1  
15.2  
14.3  
13.5  
19.2  
18.3  
17.5  
16.6  
15.7  
14.9  
14.0  
13.1  
18.8  
17.9  
17.1  
16.2  
15.4  
14.5  
13.6  
12.8  
18.4  
17.6  
16.7  
15.8  
15.0  
14.1  
13.3  
12.4  
18.0  
17.2  
16.3  
15.5  
14.6  
13.8  
12.9  
12.0  
3
Tons  
4
SCFM  
800  
960  
1120  
1280  
1440  
1600  
1760  
1920  
35  
40  
45  
50  
55  
60  
65  
22.0  
21.0  
20.0  
19.0  
17.9  
16.9  
15.9  
14.8  
21.8  
20.7  
19.7  
18.7  
17.7  
16.6  
15.6  
14.6  
21.5  
20.5  
19.5  
18.4  
17.4  
16.4  
15.4  
14.4  
21.2  
20.2  
19.2  
18.1  
17.1  
16.1  
15.1  
14.1  
20.9  
19.9  
18.9  
17.9  
16.9  
15.8  
14.8  
13.8  
20.6  
19.6  
18.6  
17.5  
16.5  
15.5  
14.5  
13.5  
20.3  
19.3  
18.2  
17.2  
16.2  
15.2  
14.2  
13.2  
Tons  
5
SCFM  
1000  
1200  
1400  
1600  
1800  
2000  
2200  
2400  
35  
40  
45  
50  
55  
60  
65  
23.7  
22.6  
21.4  
20.3  
19.1  
17.9  
16.8  
15.6  
23.6  
22.4  
21.2  
20.1  
18.9  
17.8  
16.6  
15.4  
23.4  
22.2  
21.0  
19.9  
18.7  
17.6  
16.4  
15.2  
23.2  
22.0  
20.9  
19.7  
18.5  
17.4  
16.2  
15.1  
23.0  
21.8  
20.7  
19.5  
18.4  
17.2  
16.0  
14.9  
22.8  
21.6  
20.4  
19.3  
18.1  
16.9  
15.7  
14.6  
22.5  
21.3  
20.2  
19.0  
17.8  
16.6  
15.4  
14.3  
Tons  
7½  
SCFM  
1500  
1800  
2100  
2400  
2700  
3000  
3300  
3600  
35  
40  
45  
50  
55  
60  
65  
22.0  
20.2  
18.5  
16.7  
14.9  
13.1  
11.4  
9.6  
22.9  
21.0  
19.2  
17.3  
15.5  
13.7  
11.8  
10.0  
23.8  
21.9  
19.9  
18.0  
16.1  
14.2  
12.3  
10.3  
24.7  
22.7  
20.7  
18.7  
16.7  
14.7  
12.7  
10.7  
25.6  
23.5  
21.4  
19.3  
17.3  
15.2  
13.1  
11.1  
26.5  
24.4  
22.3  
20.1  
18.0  
15.9  
13.7  
11.6  
27.5  
25.3  
23.1  
20.9  
18.7  
16.5  
14.3  
12.2  
Tons  
8½  
SCFM  
1700  
2040  
2380  
2720  
3060  
3400  
3740  
4080  
35  
40  
45  
50  
55  
60  
65  
22.6  
20.6  
18.6  
16.6  
14.7  
12.7  
10.7  
8.7  
23.7  
21.6  
19.5  
17.4  
15.3  
13.2  
11.1  
9.0  
24.9  
22.7  
20.4  
18.2  
15.9  
13.7  
11.4  
9.2  
26.1  
23.7  
21.3  
18.9  
16.6  
14.2  
11.8  
9.4  
27.2  
24.7  
22.2  
19.7  
17.2  
14.7  
12.2  
9.6  
28.3  
25.7  
23.0  
20.3  
17.7  
15.0  
12.3  
9.7  
29.4  
26.6  
23.8  
21.0  
18.1  
15.3  
12.5  
9.7  
Tons  
10  
SCFM  
2000  
2400  
2800  
3200  
3600  
4000  
4400  
4800  
35  
40  
45  
50  
55  
60  
65  
26.0  
23.5  
21.1  
18.7  
16.2  
13.8  
11.3  
8.9  
26.5  
24.1  
21.8  
19.5  
17.2  
14.9  
12.5  
10.2  
26.9  
24.7  
22.5  
20.3  
18.1  
15.9  
13.7  
11.5  
27.4  
25.3  
23.3  
21.2  
19.1  
17.0  
14.9  
12.9  
27.9  
25.9  
24.0  
22.0  
20.1  
18.1  
16.1  
14.2  
28.3  
26.4  
24.6  
22.7  
20.8  
19.0  
17.1  
15.3  
28.6  
26.9  
25.1  
23.4  
21.6  
19.8  
18.1  
16.3  
Notes:  
1. Temperature rise does not account for indoor fan heat.  
2.70degODAmbientTemperature.  
3. For units with the Dehumidification (Hot Gas Reheat) option.  
RT-PRC005-EN  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
Integrated ComfortTM System  
Sensor(s) available with optional  
temperature adjustment and override  
buttons to provide  
Programmable Night Setback  
Auto or manual changeover with seven-  
day programming. Keyboard selection of  
ReliaTel™ Controlled Units  
Zone Sensors are the building  
occupants comfort control devices for  
Precedent™ units with the Micro control:  
central control  
through aTrane  
Integrated  
Manual Changeover  
Heat, Cool or Off System Switch. Fan  
Auto or Off Switch.  
One temperature  
setpoint lever.  
ComfortTM system.  
Heat, Cool, Fan, Auto, or On. All  
programmable sensors have System On,  
Heat, Cool, Service LED/indicators as  
standard. Night Setback Sensors have  
one (1) Occupied, one (1) Un-occupied,  
and two (2) Override programs per day.  
DualThermistor Remote Zone Sensor  
This sensor will allow the customer to  
reduce the total number of remote  
sensors to obtain space temperature  
averaging. This sensor should be utilized  
with ReliaTel controls.  
Humidity Sensor  
Field installed, wall-mounted or duct-  
mounted humidity sensor is used to  
control activation of the hot gas reheat  
dehumidification  
Manual/Automatic Changeover  
Auto, Heat, Cool or Off System Switch.  
Fan Auto or Off Switch.Two temperature  
setpoint levers.  
Digital Display Zone Sensor  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone  
Optional Status  
option.The  
Indication LED  
humidity sensor  
lights, System On,  
can be set for  
sensors.This sensor  
Heat, Cool, or  
humidity levels  
includes a digital  
Service.  
between 40% and  
60% relative  
display of set point  
adjustment and  
humidity by  
space temperature  
adjusting the  
in F (Fahrenheit) or C  
ReliaTel Options  
(Celsius). Includes  
Module.  
FAN and SYSTEM  
buttons (supports  
the service functions  
CO2 Sensing  
of the standard  
The CO2 sensor shall have the ability to  
monitor space occupancy levels within  
the building by  
sensor). E-squared  
memory stores last  
Remote Sensor  
programmed set points. Requires 24VAC  
(Volts AC).This sensor should be utilized  
with ReliaTel™ controls.  
measuring the  
Sensor(s) available for all zone sensors to  
provide remote  
parts per million  
of CO2 (Carbon  
sensing capabilities.  
Dioxide) in the  
air. As the CO2  
levels increase,  
the outside air  
damper  
modulates to  
meet the CO2  
space ventilation  
requirements.  
The CO accessory shall be available as  
field ins2talled.  
62  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
Electromechanically Controlled  
Units  
Conventional Thermostats  
The building occupants comfort control  
devices for electromechanically  
controlled units.  
Manual Changeover  
One Heat, One  
CoolThermostat.  
Heat, Cool or Off  
System Switch.  
TM  
Fan Auto or On  
90  
70  
Switch. Set Point  
80  
Dial. Adjustable  
Heat Anticipator.  
Automatic Changeover  
One Heat,Two CoolThermostat. Off, Auto  
System Switch. Auto/On Fan Switch.  
HEAT  
COOL  
50 60 70 80  
50 60 70 80  
50 60 70 80  
TM  
FAN  
AUTO  
ON  
OFF  
AUTO  
Programmable Electronic Night Setback  
Thermostat  
Heating setback and cooling setup with 7-  
day, 5-1-1 programming capability.  
Available in two heating/cooling or one  
heating/cooling versions with automatic  
changeover.  
RT-PRC005-EN  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard  
Efficiency)  
Table ED-1 — Unit Wiring — Standard Efficiency  
Optional  
Belt Drive Indoor Fan Motor2  
Standard Indoor Fan Motor  
Minimum Maximum Fuse  
Oversize Indoor Fan Motor  
Unit  
Operating  
Voltage Range  
187-253  
187-253  
414-506  
Minimum  
Circuit  
Maximum Fuse  
Size or Maximum  
Minimum  
Circuit  
Maximum Fuse  
Size or Maximum  
Unit  
Circuit  
Size or Maximum  
Tons  
3
Model No.  
TSC036A1  
TSC036A3  
TSC036A4  
TSC036AW  
Ampacity Circuit Breaker1  
Ampacity Circuit Breaker1  
Ampacity Circuit Breaker1  
25.3  
17.9  
9.2  
40  
25  
15  
15  
27.7  
20.3  
10.4  
8.3  
40  
30  
15  
15  
N/A  
20.6  
10.6  
8.3  
N/A  
30  
15  
517-633  
7.7  
15  
TSC048A1  
TSC048A3  
TSC048A4  
TSC048AW  
TSC060A1  
TSC060A3  
TSC060A4  
TSC060AW  
TSC060AK  
TSC072A3  
TSC072A4  
TSC072AW  
TSC072AK  
TSC090A3  
TSC090A4  
TSC090AW  
TSC090AK  
TSC092A3  
TSC092A4  
TSC092AW  
TSC102A3  
TSC102A4  
TSC102AW  
TSC102AK  
TSC120A3  
TSC120A4  
TSC120AW  
TSC120AK  
187-253  
187-253  
414-506  
517-633  
187-253  
187-253  
414-506  
517-633  
342-418  
187-253  
414-506  
517-633  
342-418  
187-253  
414-506  
517-633  
342-418  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
342-418  
187-253  
414-506  
517-633  
342-418  
34.0  
23.9  
12.8  
9.8  
47.3  
31.5  
16.0  
12.2  
19.6  
32.7  
17.6  
12.8  
23.2  
42.7  
22.6  
17.6  
28.4  
38.9  
20.5  
15.5  
45.1  
24.0  
19.5  
32.6  
52.6  
26.9  
21.8  
32.6  
50  
35  
20  
15  
60  
50  
25  
15  
30  
50  
25  
20  
35  
60  
35  
25  
40  
50  
25  
20  
60  
30  
25  
40  
60  
35  
25  
40  
36.1  
26.0  
14.4  
10.6  
49.0  
33.2  
16.3  
12.8  
34.0  
18.2  
13.6  
45.8  
24.1  
18.8  
29.9  
42.0  
22.0  
16.7  
48.2  
25.5  
20.7  
35.6  
56.6  
28.9  
23.5  
35.6  
50  
40  
20  
15  
60  
50  
25  
20  
50  
25  
20  
60  
35  
25  
45  
50  
25  
20  
60  
35  
25  
45  
70  
35  
30  
45  
N/A  
25.3  
13.6  
10.0  
N/A  
30.3  
15.6  
11.8  
N/A  
35  
20  
15  
N/A  
45  
25  
15  
4
5
6
7½  
8½  
10  
Notes:  
1. HACR breaker per NEC.  
2. Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.  
64  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High  
Efficiency)  
Table ED-2 — Unit Wiring — High Efficiency  
Optional  
Standard Indoor Fan Motor  
Minimum Maximum Fuse  
Oversize Indoor Fan Motor  
Belt Drive Indoor Fan Motor2  
Unit  
Operating  
Voltage Range  
187-253  
187-253  
414-506  
517-633  
187-253  
187-253  
414-506  
517-633  
187-253  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
187-253  
414-506  
517-633  
Minimum  
Circuit  
Maximum Fuse  
Minimum  
Circuit  
Maximum Fuse  
Unit  
Circuit  
Size or Maximum  
Size or Maximum  
Size or Maximum  
Tons  
3
Model No.  
THC036A1  
THC036A3  
THC036A4  
THC036AW  
THC048A1  
THC048A3  
THC048A4  
THC048AW  
THC060A1  
THC060A3  
THC060A4  
THC060AW  
THC072A3  
THC072A4  
THC072AW  
THC092A3  
THC092A4  
THC092AW  
THC102A3  
THC102A4  
THC102AW  
THC120A3  
THC120A4  
THC120AW  
Ampacity Circuit Breaker1  
Ampacity Circuit Breaker1  
Ampacity Circuit Breaker1  
23.9  
17.2  
9.0  
40  
25  
15  
15  
45  
30  
15  
15  
60  
45  
20  
15  
50  
25  
20  
50  
25  
15  
50  
25  
20  
60  
30  
25  
26.3  
19.6  
10.2  
7.7  
31.5  
23.3  
12.6  
9.1  
41.2  
31.7  
15.0  
12.4  
36.1  
18.1  
14.3  
41.2  
20.9  
16.0  
45.4  
22.9  
17.8  
52.6  
27.3  
21.6  
40  
30  
15  
15  
50  
35  
15  
15  
60  
45  
20  
15  
50  
25  
20  
50  
25  
20  
60  
30  
20  
60  
35  
25  
N/A  
19.9  
10.4  
7.7  
N/A  
22.6  
11.8  
8.5  
N/A  
28.8  
14.3  
11.4  
N/A  
30  
15  
15  
N/A  
35  
15  
15  
N/A  
45  
20  
15  
7.1  
29.4  
21.2  
11.0  
8.3  
4
39.5  
30.0  
14.7  
11.8  
34.8  
17.5  
13.5  
38.1  
19.4  
14.8  
42.3  
21.4  
16.6  
48.6  
25.3  
19.9  
5
6
7½  
8½  
10  
Notes:  
1. HACR breaker per NEC.  
2. Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.  
RT-PRC005-EN  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard  
Efficiency)  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) —208/230 Volts — Standard Efficiency  
StandardIndoorMotor  
Oversize Indoor Motor  
Max Fuse Size or  
To Use  
With  
Heater  
ModelNo.  
Heater  
Control  
Stages  
Max Fuse Size or  
Tons  
3
kW Rating1  
MCA  
Max Circuit Breaker2  
MCA  
Max Circuit Breaker2  
208/230 Volts Single Phase  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
3.8/5.0  
7.5/10.0  
10.4/13.8  
3.8/5.0  
7.5/10.0  
10.4/13.8  
13.2/17.6  
3.8/5.0  
1
2
2
1
2
2
2
1
2
2
2
25.5/28.9  
48.0/55.0  
65.1/74.8  
34.0/34.0  
49.6/56.6  
66.8/76.4  
84.0/96.1  
47.3/47.3  
52.9/59.9  
70.0/79.6  
87.3/99.4  
40/40  
50/60  
70/80  
50/50  
50/60  
70/80  
90/100  
60/60  
60/60  
80/80  
90/100  
28.5/31.9  
51.0/58.0  
68.1/77.8  
36.1/36.1  
52.3/59.3  
69.4/79.0  
86.6/98.8  
49.0/49.0  
55.0/62.0  
72.1/81.8  
89.4/101.54  
40/40  
60/60  
70/80  
50/50  
60/60  
70/80  
90/100  
60/60  
60/70  
80/90  
90/110  
TSC036A1  
TSC048A1  
TSC060A1  
4
5
7.5/10.0  
10.4/13.8  
13.2/17.6  
208/230 Volts Three Phase  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR323A  
BAYHTRS309A  
BAYHTRS318A  
BAYHTRS327A  
BAYHTRS336A  
BAYHTRS309A  
BAYHTRS318A  
BAYHTRS327A  
BAYHTRS336A  
BAYHTRS309A  
BAYHTRS318A  
BAYHTRS327A  
BAYHTRS336A  
BAYHTRT309A  
BAYHTRT318A  
BAYHTRT327A  
BAYHTRT336A  
BAYHTRT318A  
BAYHTRT327A  
BAYHTRT336A  
BAYHTRT354A  
4.5/6.0  
9.0/12.0  
13.1/17.4  
4.5/6.0  
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
18.5/20.9  
34.1/39.0  
48.3/55.3  
23.9/23.9  
35.8/40.6  
49.9/56.9  
31.5/31.5  
39.0/43.9  
53.1/60.1  
67.8/76.9  
32.7/33.4  
53.1/60.4  
76.6/87.5  
100.1/114.5  
42.7/42.7  
54.8/62.0  
78.3/89.1  
101.8/116.1  
38.9/38.9  
54.8/62.0  
78.3/89.1  
101.8/116.1  
45.1/45.1  
54.8/62.0  
78.3/89.1  
101.8/116.1  
58.6/65.9  
82.1/93.0  
105.8/120.0  
152.5/141.7  
25/25  
35/40  
50/60  
35/35  
40/45  
50/60  
50/50  
50/50  
60/70  
70/80  
50/50  
60/70  
80/90  
110/125  
60/60  
60/70  
80/90  
110/125  
50/50  
60/70  
80/90  
110/125  
60/60  
60/70  
80/90  
110/125  
60/70  
90/100  
110/125  
175/150  
21.5/23.9  
37.1/42.0  
51.3/58.3  
26.0/26.0  
38.4/43.3  
52.5/59.5  
33.2/33.2  
41.1/46.0  
55.3/62.3  
69.9/79.0  
34.0/35.0  
54.8/62.0  
78.3/89.1  
101.8/116.1  
45.8/45.8  
58.6/65.9  
82.1/93.0  
105.6/120.0  
42.0/42.0  
58.6/65.9  
82.1/93.0  
105.6/120.0  
48.2/48.2  
58.6/65.9  
82.193.0  
30/30  
40/45  
60/60  
40/40  
40/45  
60/60  
50/50  
50/50  
60/70  
70/80  
50/50  
60/70  
80/90  
110/125  
60/60  
60/70  
90/100  
110/125  
50/50  
3
4
TSC036A3  
TSC048A3  
9.0/12.0  
13.1/17.4  
4.5/6.0  
9.0/12.0  
13.1/17.4  
17.3/23.0  
6.8/9.0  
5
6
TSC060A3  
TSC072A3  
13.5/18.0  
20.3/27.0  
27.0/36.0  
6.8/9.0  
TSC090A3  
TSC092A3  
TSC102A3  
TSC120A3  
13.5/18.0  
20.3/27.0  
27.0/36.0  
6.8/9.0  
7½  
8½  
13.5/18.0  
20.3/27.0  
27.0/36.0  
6.8/9.0  
60/70  
90/100  
110/125  
60/60  
13.5/18.0  
20.3/27.0  
27.0/36.0  
13.5/18.0  
20.3/27.0  
27.0/36.0  
40.6/54.0  
60/70  
90/100  
110/125  
70/80  
90/100  
125/125  
175/150  
105.6/120.0  
63.6/70.9  
87.1/98.0  
110.6/125.0  
157.5/146.7  
10  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
66  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard  
Efficiency)  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection)—380, 460 Volts — Standard Efficiency, continued  
StandardIndoorMotor  
Max Fuse Size or  
Max Circuit Breaker2  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
kW Rating1  
Control  
Stages  
Max Fuse Size or  
Tons  
MCA  
MCA  
Max Circuit Breaker2  
380 Volts Three Phase  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR423A  
BAYHTRS418A  
BAYHTRS427A  
BAYHTRS436A  
BAYHTRS418A  
BAYHTRS427A  
BAYHTRS436A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT454A  
7.5  
2
2
2
1
2
2
1
2
2
2
2
2
2
2
19.6  
26.1  
32.8  
27.6  
38.3  
49.0  
28.4  
38.3  
49.0  
38.8  
49.0  
40.1  
50.9  
72.3  
30  
30  
35  
35  
40  
50  
40  
40  
50  
40  
50  
45  
60  
80  
45  
45  
60  
45  
60  
45  
60  
80  
5
TSC060AK  
TSC072AK  
TSC090AK  
10.9  
14.4  
11.3  
16.9  
22.6  
11.3  
16.9  
22.6  
16.9  
22.6  
16.9  
22.6  
33.8  
6
29.9  
40.1  
50.9  
40.1  
50.9  
43.6  
54.4  
75.8  
7½  
8½  
10  
TSC102AK  
TSC120AK  
460 Volts Three Phase  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR423A  
BAYHTRS409A  
BAYHTRS418A  
BAYHTRS427A  
BAYHTRS436A  
BAYHTRS409A  
BAYHTRS418A  
BAYHTRS427A  
BAYHTRS436A  
BAYHTRS409A  
BAYHTRS418A  
BAYHTRS427A  
BAYHTRS436A  
BAYHTRT409A  
BAYHTRT418A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT418A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT454A  
6.0  
12.0  
17.4  
6.0  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
9.0  
18.0  
27.0  
36.0  
9.0  
18.0  
27.0  
36.0  
9.0  
18.0  
27.0  
36.0  
9.0  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
54.0  
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
10.4  
19.4  
27.5  
12.8  
20.1  
28.3  
16.0  
21.6  
29.8  
38.3  
17.6  
30.3  
43.8  
57.3  
22.6  
31.0  
44.5  
58.0  
20.5  
31.0  
44.5  
58.0  
24.0  
31.0  
44.5  
58.0  
32.9  
46.4  
59.9  
70.8  
15  
20  
30  
20  
25  
30  
25  
25  
30  
40  
25  
35  
45  
60  
35  
35  
45  
60  
25  
35  
45  
60  
30  
35  
45  
60  
35  
50  
60  
80  
11.9  
20.9  
29.0  
14.4  
22.1  
30.3  
16.3  
22.0  
30.1  
38.6  
18.2  
31.0  
44.5  
58.0  
24.1  
32.9  
46.4  
59.9  
22.0  
32.9  
46.4  
59.9  
25.5  
32.9  
46.4  
59.9  
35.4  
48.9  
62.4  
73.3  
15  
25  
30  
20  
25  
35  
25  
25  
35  
40  
25  
35  
45  
60  
35  
35  
50  
60  
25  
35  
50  
60  
35  
35  
50  
60  
40  
50  
70  
80  
3
4
TSC036A4  
TSC048A4  
5
6
TSC060A4  
TSC072A4  
TSC090A4  
TSC092A4  
TSC102A4  
TSC120A4  
7½  
8½  
10  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V, unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC005-EN  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard  
Efficiency)  
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — Standard Efficiency, continued  
StandardIndoorMotor  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
kW Rating1  
Control  
Stages  
Max Fuse Size or  
Max Circuit Breaker2  
Max Fuse Size or  
Max Circuit Breaker2  
Tons  
MCA  
MCA  
575 Volts Three Phase  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW23A  
BAYHTRSW09A  
BAYHTRSW18A  
BAYHTRSW27A  
BAYHTRSW36A  
BAYHTRSW09A  
BAYHTRSW18A  
BAYHTRSW27A  
BAYHTRSW36A  
BAYHTRSW09A  
BAYHTRSW18A  
BAYHTRSW27A  
BAYHTRSW36A  
BAYHTRTW18A  
BAYHTRTW27A  
BAYHTRTW36A  
BAYHTRTW18A  
BAYHTRTW27A  
BAYHTRTW36A  
BAYHTRTW54A  
6.0  
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
2
2
2
8.6  
15  
20  
25  
15  
20  
25  
15  
20  
25  
35  
20  
25  
35  
50  
25  
25  
40  
50  
20  
25  
40  
50  
25  
40  
50  
30  
40  
50  
60  
9.3  
15  
20  
25  
15  
20  
25  
20  
20  
25  
35  
20  
25  
40  
50  
25  
30  
40  
50  
20  
30  
40  
50  
30  
40  
50  
30  
40  
50  
70  
3
4
TSC036AW  
TSC048AW  
12.0  
17.4  
6.0  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
9.0  
18.0  
27.0  
36.0  
9.0  
15.8  
22.3  
9.8  
16.6  
23.1  
10.6  
17.3  
23.8  
12.8  
17.8  
24.3  
31.0  
14.0  
24.8  
35.6  
46.4  
18.8  
26.3  
37.1  
47.9  
16.7  
26.3  
37.1  
47.9  
26.3  
37.1  
47.9  
28.4  
39.3  
50.0  
58.8  
16.3  
22.8  
12.2  
17.1  
23.6  
30.3  
13.0  
23.8  
34.6  
45.4  
17.6  
24.8  
35.6  
46.4  
15.5  
24.8  
35.6  
46.4  
24.8  
35.6  
46.4  
26.3  
37.1  
47.9  
56.6  
5
6
TSC060AW  
TSC072AW  
TSC090AW  
TSC092AW  
18.0  
27.0  
36.0  
9.0  
7½  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
54.0  
8½  
TSC102AW  
TSC120AW  
10  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
68  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard  
Efficiency)  
Table ED-4 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — Standard Efficiency  
Optional Belt Drive Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
Control  
Stages  
Max Fuse Size or  
Tons  
3
kW Rating1  
MCA  
Max Circuit Breaker2  
208/230 Volts Single Phase  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
TSC036A1  
TSC048A1  
TSC060A1  
4
5
208/230 Volts Three Phase  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR323A  
4.5/6.0  
9.0/12.0  
13.1/17.4  
4.5/6.0  
1
2
2
1
2
2
1
2
2
2
21.9/24.3  
37.5/42.4  
51.6/58.6  
25.3/25.3  
37.5/42.4  
51.6/58.6  
30.3/30.3  
37.5/42.4  
51.6/58.6  
66.3/75.4  
30/30  
40/45  
60/60  
35/35  
40/45  
60/60  
45/45  
45/45  
60/60  
70/80  
3
4
TSC036A3  
TSC048A3  
9.0/12.0  
13.1/17.4  
4.5/6.0  
9.0/12.0  
13.1/17.4  
17.3/23.0  
5
TSC060A3  
460 Volts Three Phase  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR423A  
6.0  
12.0  
17.4  
6.0  
1
2
2
1
2
2
1
2
2
2
12.1  
21.1  
29.3  
13.6  
21.1  
29.3  
15.6  
21.1  
29.3  
37.8  
15  
25  
30  
20  
25  
30  
25  
25  
30  
40  
3
4
TSC036A4  
TSC048A4  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
5
TSC060A4  
575 Volts Three Phase  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW23A  
6.0  
12.0  
17.4  
6.0  
1
2
2
1
2
2
1
2
2
2
9.3  
15  
20  
25  
15  
20  
25  
15  
20  
25  
30  
3
4
TSC036AW  
TSC048AW  
16.6  
23.1  
10.0  
16.6  
23.1  
11.8  
16.6  
23.1  
29.8  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
5
TSC060AW  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC005-EN  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High  
Efficiency)  
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 208/230 Volts — High Efficiency  
StandardIndoorMotor  
Oversize Indoor Motor  
Max Fuse Size or  
To Use  
With  
Heater  
ModelNo.  
Heater  
Control  
Stages  
Max Fuse Size or  
Tons  
3
kW Rating1  
MCA  
Max Circuit Breaker2  
MCA  
Max Circuit Breaker2  
208/230 Volts Single Phase  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
3.8/5.0  
7.5/10.0  
10.4/13.8  
3.8/5.0  
7.5/10.0  
10.4/13.8  
13.2/17.6  
3.8/5.0  
1
2
2
1
2
2
2
1
2
2
2
25.5/28.9  
48.0/55.0  
65.1/74.8  
29.4/30.5  
49.6/56.6  
66.8/76.4  
84.0/96.1  
39.5/39.5  
52.9/59.9  
70.0/79.6  
87.3/99.4  
40/40  
50/60  
70/80  
45/45  
50/60  
70/80  
90/100  
60/60  
60/60  
80/80  
90/100  
28.5/31.9  
51.0/58.0  
68.1/77.8  
31.5/33.1  
52.3/59.3  
69.4/79.0  
86.6/98.8  
41.2/41.2  
55.0/62.0  
72.1/81.8  
89.4/101.5  
40/40  
60/60  
70/80  
50/50  
60/60  
70/80  
90/100  
60/60  
60/70  
80/90  
90/100  
THC036A1  
THC048A1  
THC060A1  
4
5
7.5/10.0  
10.4/13.8  
13.2/17.6  
208/230 Volts Three Phase  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR323A  
BAYHTRS309A  
BAYHTRS318A  
BAYHTRS327A  
BAYHTRS336A  
BAYHTRT309A  
BAYHTRT318A  
BAYHTRT327A  
BAYHTRT336A  
BAYHTRT309A  
BAYHTRT318A  
BAYHTRT327A  
BAYHTRT336A  
BAYHTRT318A  
BAYHTRT327A  
BAYHTRT336A  
BAYHTRT354A  
4.5/6.0  
9.0/12.0  
13.1/17.4  
4.5/6.0  
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
18.5/20.9  
34.1/39.0  
48.3/55.3  
21.2/22.5  
35.8/40.6  
49.9/56.9  
30.0/30.0  
39.0/43.9  
53.1/60.1  
67.8/76.9  
34.8/34.8  
53.1/60.4  
76.6/87.5  
100.1/114.5  
38.1/38.1  
54.8/62.0  
78.3/89.1  
101.8/116.1  
42.3/42.3  
54.8/62.0  
78.3/89.1  
101.8/116.1  
58.6/65.9  
82.1/93.0  
105.6/120.0  
152.5/141.7  
30/30  
35/40  
50/60  
30/30  
40/45  
50/60  
45/45  
45/45  
60/70  
70/80  
50/50  
60/70  
80/90  
110/125  
50/50  
60/70  
80/90  
110/125  
50/50  
21.5/23.9  
37.1/42.0  
51.3/58.3  
23.3/25.1  
38.4/43.3  
52.5/59.5  
31.7/31.7  
41.1/46.0  
55.3/62.3  
69.9/79.0  
35.7/35.7  
54.8/62.0  
78.3/89.1  
101.8/116.1  
44.2/44.2  
58.6/65.9  
82.1/93.0  
105.6/120.0  
44.2/44.2  
58.6/65.9  
82.1/93.0  
105.6/120.0  
63.6/70.9  
87.1/98.0  
110.6/125.0  
157.5/146.7  
30/30  
40/45  
60/60  
35/35  
40/45  
60/60  
45/45  
45/50  
60/70  
70/80  
50/50  
60/70  
80/90  
110/125  
50/50  
60/70  
90/100  
110/125  
50/50  
3
4
THC036A3  
THC048A3  
9.0/12.0  
13.1/17.4  
4.5/6.0  
9.0/12.0  
13.1/17.4  
17.3/23.0  
6.8/9.0  
5
6
THC060A3  
THC072A3  
13.5/18.0  
20.3/27.0  
27.0/36.0  
6.8/9.0  
7½  
8½  
THC092A3  
THC102A3  
THC120A3  
13.5/18.0  
20.3/27.0  
27.0/36.0  
6.8/9.0  
13.5/18.0  
20.3/27.0  
27.0/36.0  
13.5/18.0  
20.3/27.0  
27.0/36.0  
40.6/54.0  
60/70  
80/90  
60/70  
90/100  
110/125  
70/80  
90/100  
125/125  
175/150  
110/125  
60/70  
90/100  
110/125  
175/150  
10  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
70  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(High  
Efficiency)  
Electrical  
Data  
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 460 Volts — High Efficiency, continued  
StandardIndoorMotor  
Oversize Indoor Motor  
To Use  
With  
Heater  
Heater  
kW Rating1  
Control  
Stages  
Max Fuse Size or  
Max Circuit Breaker2  
Max Fuse Size or  
Max Circuit Breaker2  
Tons  
ModelNo.  
MCA  
MCA  
460 Volts Three Phase  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR423A  
BAYHTRS409A  
BAYHTRS418A  
BAYHTRS427A  
BAYHTRS436A  
BAYHTRT409A  
BAYHTRT418A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT409A  
BAYHTRT418A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT418A  
BAYHTRT427A  
BAYHTRT436A  
BAYHTRT454A  
6.0  
12.0  
17.4  
6.0  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
9.0  
18.0  
27.0  
36.0  
9.0  
18.0  
27.0  
36.0  
9.0  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
54.0  
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
10.4  
19.4  
27.5  
11.1  
20.1  
28.3  
14.7  
21.6  
29.8  
38.3  
17.5  
30.3  
43.8  
57.3  
19.4  
31.0  
44.5  
58.0  
21.4  
31.0  
44.5  
58.0  
32.9  
46.4  
59.9  
70.8  
15  
20  
30  
15  
25  
30  
20  
25  
30  
40  
25  
35  
45  
60  
25  
35  
45  
60  
25  
35  
45  
60  
35  
50  
60  
80  
11.9  
20.9  
29.9  
13.1  
22.1  
30.3  
15.0  
22.0  
30.1  
38.6  
18.1  
31.0  
44.5  
58.0  
20.9  
32.9  
46.4  
59.9  
22.9  
32.9  
46.4  
59.9  
35.4  
48.9  
62.4  
73.3  
15  
25  
30  
15  
25  
35  
20  
25  
35  
40  
25  
35  
45  
60  
25  
35  
50  
60  
30  
35  
50  
60  
40  
50  
70  
80  
3
4
5
THC036A4  
THC048A4  
THC060A4  
6
THC072A4  
THC092A4  
THC102A4  
THC120A4  
7½  
8½  
10  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC005-EN  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High  
Efficiency)  
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — High Efficiency, continued  
StandardIndoorMotor  
Oversize Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
kW Rating1  
Control  
Stages  
Max Fuse Size or  
Max Circuit Breaker2  
Max Fuse Size or  
Max Circuit Breaker2  
Tons  
MCA  
MCA  
575 Volts Three Phase  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW23A  
BAYHTRSW09A  
BAYHTRSW18A  
BAYHTRSW27A  
BAYHTRSW36A  
BAYHTRTW18A  
BAYHTRTW27A  
BAYHTRTW36A  
BAYHTRTW18A  
BAYHTRTW27A  
BAYHTRTW36A  
BAYHTRTW18A  
BAYHTRTW27A  
BAYHTRTW36A  
BAYHTRTW54A  
6.0  
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
2
2
1
2
2
1
2
2
2
8.6  
15  
20  
25  
15  
20  
25  
15  
20  
25  
35  
20  
25  
35  
50  
25  
40  
50  
25  
40  
50  
30  
40  
50  
60  
9.3  
15  
20  
25  
15  
20  
25  
15  
20  
25  
35  
20  
25  
40  
50  
30  
40  
50  
30  
40  
50  
30  
40  
50  
70  
3
4
THC036AW  
THC048AW  
12.0  
17.4  
6.0  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
9.0  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
18.0  
27.0  
36.0  
54.0  
15.8  
22.3  
9.1  
16.6  
23.1  
10.1  
17.3  
23.8  
12.4  
17.8  
24.3  
31.0  
14.3  
24.8  
35.6  
46.4  
26.3  
37.1  
47.9  
26.3  
37.1  
47.9  
28.4  
39.3  
50.0  
58.8  
16.3  
22.8  
11.8  
17.1  
23.6  
30.3  
13.5  
23.8  
34.6  
45.4  
24.8  
35.6  
46.4  
24.8  
35.6  
46.4  
26.3  
37.1  
47.9  
56.6  
5
6
THC060AW  
THC072AW  
7½  
THC092AW  
THC102AW  
THC120AW  
8½  
10  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
72  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(High  
Efficiency)  
Table ED-6 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — High Efficiency  
Belt Drive Indoor Motor  
To Use  
With  
Heater  
ModelNo.  
Heater  
Control  
Stages  
Max Fuse Size or  
Tons  
3
kW Rating1  
MCA  
Max Circuit Breaker2  
208/230 Volts Single Phase  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
BAYHTRR105A  
BAYHTRR110A  
BAYHTRR114A  
BAYHTRR118A  
N/A  
N/A  
N/A  
N/A  
N/A  
1N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
THC036A1  
THC048A1  
THC060A1  
4
5
208/230 Volts Three Phase  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR306A  
BAYHTRR312A  
BAYHTRR318A  
BAYHTRR323A  
4.5/6.0  
9.0/12.0  
13.1/17.4  
4.5/6.0  
1
2
2
1
2
2
1
2
2
2
21.9/24.3  
37.5/42.4  
51.6/58.6  
22.6/24.3  
37.5/42.4  
51.6/58.6  
28.8/28.8  
37.5/42.4  
51.6/58.6  
66.3/75.4  
25/25  
40/45  
60/60  
35/35  
40/45  
60/60  
45/45  
45/45  
60/60  
70/80  
3
4
THC036A3  
THC048A3  
9.0/12.0  
13.1/17.4  
4.5/6.0  
9.0/12.0  
13.1/17.4  
17.3/23.0  
5
THC060A3  
460 Volts Three Phase  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR406A  
BAYHTRR412A  
BAYHTRR418A  
BAYHTRR423A  
6.0  
12.0  
17.4  
6.0  
1
2
2
1
2
2
1
2
2
2
12.1  
21.1  
29.3  
12.1  
21.1  
29.3  
14.3  
21.1  
29.3  
37.8  
15  
25  
30  
15  
25  
30  
20  
25  
30  
40  
3
4
5
THC036A4  
THC048A4  
THC060A4  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
575 Volts Three Phase  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW06A  
BAYHTRRW12A  
BAYHTRRW18A  
BAYHTRRW23A  
6.0  
12.0  
17.4  
6.0  
1
2
2
1
2
2
1
2
2
2
9.3  
15  
20  
25  
15  
20  
25  
15  
20  
25  
30  
3
4
THC036AW  
THC048AW  
16,6  
23.1  
9.3  
16.6  
23.1  
11.4  
16.6  
23.1  
29.8  
12.0  
17.4  
6.0  
12.0  
17.4  
23.0  
5
THC060AW  
Notes:  
1. Heater kW ratings are at 208/240 for 208/230V unit.  
2. HACR type circuit breaker per NEC.  
RT-PRC005-EN  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-7 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized  
StandardEvaporatorFanMotor  
OversizedEvaporatorFanMotor  
Amps  
FLA  
Amps  
Unit  
Tons  
3
Model No.  
T*C036A1  
T*C036A3  
T*C036A4  
T*C036AW  
T*C048A1  
T*C048A3  
T*C048A4  
T*C048AW  
T*C060A1  
T*C060A3  
T*C060A4  
T*C060AW  
TSC060AK  
T*C072A3  
T*C072A4  
T*C072AW  
TSC072AK  
T*C090A3  
T*C090A4  
T*C090AW  
TSC090AK  
T*C092A3  
T*C092A4  
T*C092AW  
T*C102A3  
T*C102A4  
T*C102AW  
TSC102AK  
T*C120A3  
T*C120A4  
T*C120AW  
TSC120AK  
No.  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volts  
208-230  
208-230  
460  
Phase  
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
HP  
.33  
.33  
.33  
.33  
.60  
.60  
.60  
.60  
.90  
.90  
.90  
.90  
1.00  
1.00  
1.00  
1.00  
2.0  
FLA  
2.30  
2.30  
1.10  
1.10  
3.60  
3.60  
1.70  
1.50  
6.20  
6.20  
2.90  
2.10  
4.3  
LRA  
3.90  
3.90  
2.00  
1.80  
6.60  
6.60  
2.80  
2.40  
14.0  
14.0  
6.60  
4.90  
No.  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volts  
208-230  
208-230  
460  
Phase  
1
HP  
.50  
LRA  
9.80  
9.80  
5.20  
3.60  
4.70  
4.70  
2.30  
1.70  
5.70  
5.70  
3.30  
2.30  
7.90  
7.90  
3.2  
1
1
1
1
1
1
1
1
1
1
1
.50  
.50  
.50  
.80  
..80  
.80  
.80  
1.00  
1.00  
1.00  
1.00  
575  
460  
208-230  
208-230  
460  
208-230  
208-230  
460  
13.60  
13.60  
7.20  
4
5
6
575  
575  
5.80  
208-230  
208-230  
460  
575  
380  
208-230  
460  
575  
208-230  
208-230  
460  
575  
16.40  
16.40  
8.20  
2.4  
5.00  
8.3  
5.00  
2.50  
1.70  
4.9  
32.20  
16.10  
13.20  
35.0  
48.00  
24.00  
18.20  
35.0  
48.00  
24.00  
18.20  
48.00  
24.00  
18.20  
35.0  
83.00  
42.00  
31.00  
51.1  
208-230  
460  
575  
3
3
3
2.00  
2.00  
2.00  
6.30  
3.10  
2.50  
48.00  
24.00  
18.20  
380  
3
208-230  
460  
575  
3
3
3
3
2.00  
2.00  
2.00  
2.0  
6.30  
3.10  
2.50  
4.9  
208-230  
460  
575  
3
3
3
3
3.00  
3.00  
3.00  
3.0  
9.40  
4.60  
3.70  
6.4  
83.00  
42.00  
31.00  
51.1  
380  
380  
7½  
8½  
10  
208-230  
460  
575  
208-230  
460  
575  
3
3
3
3
3
3
3
2.00  
2.00  
2.00  
2.00  
2.00  
2.00  
2.0  
6.30  
3.10  
2.50  
6.30  
3.10  
2.50  
4.9  
208-230  
460  
575  
208-230  
460  
575  
3
3
3
3
3
3
3
3.00  
3.00  
3.00  
3.00  
3.00  
3.00  
3.0  
9.40  
4.60  
3.70  
9.40  
4.60  
3.70  
6.4  
83.00  
42.00  
31.00  
83.00  
42.00  
31.00  
51.1  
380  
380  
208-230  
460  
575  
3
3
3
3
3.00  
3.00  
3.00  
3.0  
9.40  
4.60  
3.70  
6.4  
208-230  
460  
575  
3
3
3
3
5.00  
5.00  
5.00  
5.0  
13.40  
6.60  
5.40  
10.8  
112.00  
56.00  
44.0  
380  
380  
66.5  
Table ED-8 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Optional Belt Drive  
Amps  
Unit  
Tons  
3
ModelNo.  
No.  
Volts  
Phase  
HP  
FLA  
LRA  
T*C036A3  
T*C036A4  
T*C036AW  
1
1
1
208-230  
460  
575  
3
3
3
1.00  
1.00  
1.00  
5.00  
2.50  
1.70  
32.20  
16.10  
13.20  
T*C048A3  
T*C048A4  
T*C048AW  
1
1
1
208-230  
460  
575  
3
3
3
1.00  
1.00  
1.00  
5.00  
2.50  
1.70  
32.20  
16.10  
13.20  
4
5
T*C060A3  
T*C060A4  
T*C060AW  
1
1
1
208-230  
460  
575  
3
3
3
1.00  
1.00  
1.00  
5.00  
2.50  
1.70  
32.20  
16.10  
13.20  
* Indicates both Standard and High Efficiency.  
74  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
(Standard  
Efficiency)  
Table ED-9— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency  
CompressorMotors  
Condenser Fan Motors  
Amps  
1
Amps  
Unit  
ModelNo.  
Tons  
3
No.  
Volts  
Phase  
HP2  
RPM  
RLA  
LRA  
No.  
Phase  
HP  
FLA  
LRA  
TSC036A1  
TSC036A3  
TSC036A4  
TSC036AW  
TSC048A1  
TSC048A3  
TSC048A4  
TSC048AW  
TSC060A1  
TSC060A3  
TSC060A4  
TSC060AW  
TSC060AK  
TSC072A3  
TSC072A4  
TSC072AW  
TSC072AK  
TSC090A3  
TSC090A4  
TSC090AW  
TSC090AK  
TSC092A3  
TSC092A4  
TSC092AW  
TSC102A3  
TSC102A4  
TSC102AW  
TSC102AK  
TSC120A3  
TSC120A4  
TSC120AW  
TSC120AK  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
1
2
2
2
1
208-230  
208-230  
460  
1
3
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.1  
3.1  
3.1  
3.1  
3.9  
3.9  
3.9  
3.9  
5.1  
5.1  
5.1  
5.1  
5.1  
6
6
6
6
7.5  
7.5  
7.5  
7.5  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
17.2  
11.3  
6.0  
104.0  
74.0  
37.6  
30.4  
131.0  
91.0  
46.0  
37.0  
144.0  
128.0  
63.0  
49.0  
64  
156  
75  
54  
70  
181.5  
95.0  
69.0  
106.3  
91/77  
50/39  
37/31  
128/77  
63/39  
49/31  
64/39  
128/91  
63/46  
49/37  
64/54  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.20  
.20  
.20  
.20  
.33  
.33  
..33  
.33  
.33  
.33  
.33  
.33  
.40  
.70  
.70  
.70  
.75  
.70  
.70  
.70  
.75  
.70  
.70  
.70  
.75  
.75  
.75  
.75  
.75  
.75  
.75  
.75  
1.5  
1.5  
.6  
2.5  
2.5  
1.3  
575  
4.9  
.5  
1.2  
208-230  
208-230  
460  
22.7  
14.6  
7.9  
2.0  
2.0  
1.2  
6.6  
6.6  
2.5  
1.5  
6.6  
6.6  
2.5  
1.5  
4.3  
9.30  
5.80  
3.60  
7.7  
9.30  
5.80  
3.60  
7.7  
9.30  
5.80  
3.60  
9.4  
6.8  
6.2  
7.7  
9.4  
6.8  
6.2  
7.7  
4
5
575  
6.1  
.7  
208-230  
208-230  
460  
575  
380  
208-230  
460  
575  
380  
208-230  
460  
575  
380  
208-230  
460  
575  
208-230  
460  
575  
380  
208-230  
460  
31.3  
18.6  
9.5  
2.0  
2.0  
1.2  
.7  
1.1  
7.5  
11.4  
19.0  
10.1  
7.7  
12.2  
26.0  
13.6  
10.9  
16.4  
3.85  
2.50  
1.54  
2.5  
3.85  
2.50  
1.54  
2.5  
3.85  
2.50  
1.54  
4.0  
2.8  
2.4  
2.5  
4.0  
2.8  
2.4  
2.5  
6
7½  
8½  
4/2.8  
4/2.8  
4/2.8  
3450 14.7/10.3  
3450  
3450  
7.6/5.4  
5.8/4.2  
5.1/2.8 3450 18.6/10.3  
5.1/2.8 3450 10.0/5.4  
5.1/2.8 3450  
5.1/2.8 3450 12.1/6.6  
5.1/3.9 3450 18.6/14.7  
5.1/3.9 3450  
5.1/3.9 3450  
5.1/3.9 3450  
8.2/4.2  
10  
9.5/7.4  
7.8/5.8  
11.5/9.0  
575  
380  
Notes:  
1. Amp draw for each motor; multiply value by number of motors to determine total amps.  
2. HP for each compressor.  
RT-PRC005-EN  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-10 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency  
CompressorMotors  
Condenser Fan Motors  
Amps1  
Unit  
Amps1  
RLA LRA  
88.0  
Tons  
3
ModelNo.  
No.  
Volts  
Phase  
HP2  
RPM  
No.  
Phase  
HP  
FLA  
LRA  
THC036A1  
THC036A3  
THC036A4  
THC036AW  
THC048A1  
THC048A3  
THC048A4  
THC048AW  
THC060A1  
THC060A3  
THC060A4  
THC060AW  
THC072A3  
THC072A4  
THC072AW  
THC092A3  
THC092A4  
THC092AW  
THC102A3  
THC102A4  
THC102AW  
THC120A3  
THC120A4  
THC120AW  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
208-230  
208-230  
460  
1
3
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2.8  
2.8  
2.8  
2.8  
3.5  
3.5  
3.5  
3.5  
4.5  
4.5  
4.5  
4.5  
5.7  
5.7  
5.7  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
3450  
16.1  
10.7  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.20  
.20  
.20  
.20  
.33  
.33  
.33  
.33  
.33  
.33  
.33  
.33  
.70  
.70  
.70  
.70  
.70  
.70  
.75  
.75  
.75  
.75  
.75  
.75  
1.5  
1.5  
2.5  
2.5  
1.3  
77.0  
39.0  
31.0  
5.8  
4.4  
0.6  
0.5  
2.0  
2.0  
1.2  
0.7  
2.0  
2.0  
1.2  
0.9  
3.85  
2.50  
1.54  
3.85  
2.50  
1.54  
4.0  
2.8  
2.4  
4.0  
2.8  
2.4  
575  
1.2  
208-230  
208-230  
460  
19.0  
12.5  
6.5  
4.9  
25.0  
17.4  
7.8  
6.2  
109.0  
88.0  
44.0  
34.0  
169.0  
124.0  
59.6  
49.4  
156  
6.6  
6.6  
2.5  
1.5  
6.6  
6.6  
2.5  
1.5  
9.30  
5.80  
3.60  
9.30  
5.80  
3.60  
9.4  
6.8  
6.2  
9.4  
6.8  
6.2  
4
575  
208-230  
208-230  
460  
575  
208-230  
460  
575  
208-230  
460  
575  
208-230  
460  
5
20.7  
6
10  
75  
8.2  
54  
3.5/3.3 3450  
3.5/3.3 3450  
3.5/3.3 3450  
3.9/3.5 3450  
3.9/3.5 3450  
3.9/3.5 3450  
4.8/3.5 3450  
4.8/3.5 3450  
4.8/3.5 3450  
12.4/12.4  
6.4/5.8  
4.8/4.8  
14.7/12.4  
7.1/6.4  
5.4/4.8  
88/88  
44/44  
34/34  
91/88  
50/44  
37/34  
7½  
8½  
575  
208-230  
460  
17.3/12.4 124/88  
10  
9.0/6.4  
7.1/4.8  
59.6/44  
49.4/34  
575  
Notes:  
1. Amp draw for each motor; multiply value by number of motors to determine total amps.  
2. HP for each compressor.  
Table ED-11— Electrical Characteristics — Power Exhaust  
Tons  
6-10  
6-10  
6-10  
Volts  
208-230  
460  
Phase  
HP  
RPM1  
1075  
1075  
1075  
FLA  
LRA  
16.3  
6.8  
1
1
1
0.87  
0.87  
0.87  
5.7  
3.3  
2.3  
575  
5.4  
Note:  
1. Twospeed.  
76  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Jobsite  
Connections  
Zone Sensors —Typical Number OfWires  
DISCONNECT  
SWITCH  
(BYOTHERS)  
A— ManualChangeover ....................................... 4  
Manual/AutoChangeover ............................... 5  
Manual/AutoChangeoverwith  
StatusIndicationLED’s ........................... 10  
Programmable Night Setback with  
ZONESENSOR  
ORTHERMOSTAT  
StatusIndicationLED’s ............................. 7  
ROOFTOP  
UNIT  
ThermostatsTypicalNumberofWires  
A — 3 wires, 24-volts, Cooling Only  
4 wires, 24-volts, with Electric Heat  
B— 3 Power Wires + 1 Ground Wire (three phase)  
2 Power Wires + 1 Ground Wire (single phase)  
For specific wiring information, see the installation instructions.  
All wiring except power wires is low voltage.  
All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes. Wiring shown dotted is to be furnished and installed  
bythecustomer.  
RT-PRC005-EN  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(3-5 Tons)  
All dimensions are in inches/millimeters.  
3 - 5 Tons Standard Efficiency  
3 and 4 Tons High Efficiency  
32 1/4"  
819 MM  
4 1/4"  
108 MM  
23 9/16"  
598 MM  
42 1/4"  
69 7/8"  
1073 MM  
1775 MM  
5 9/16"  
141 MM  
5 5/8"  
143 MM  
7 5/8"  
194 MM  
9 5/8"  
244 MM  
44 1/4"  
1124 MM  
36 1/4"  
921 MM  
5 Tons High Efficiency  
4 1/4"  
108 MM  
23 9/16"  
598 MM  
42 1/4"  
69 7/8"  
1073 MM  
1775 MM  
5 9/16"  
141 MM  
5 5/8"  
143 MM  
7 5/8"  
194 MM  
9 5/8"  
244 MM  
44 1/4"  
1124 MM  
78  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(3-5 Tons)  
All dimensions are in inches/millimeters.  
Downflow Airflow Supply/Return  
Through the Base Utilities  
Horizontal Airflow Supply/Return  
Unit Clearance and Roof Opening  
RT-PRC005-EN  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(3-5 Tons)  
All dimensions are in inches.  
Downflow Duct Connections — Field Fabricated  
80  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(6-10 Tons)  
All dimensions are in inches.  
6 Tons Standard and High  
Efficiency 7½ Tons Standard  
Efficiency  
Tons High Efficiency  
8½ and 10 Tons Standard and High Efficiency  
RT-PRC005-EN  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(6-10 Tons)  
All dimensions are in inches.  
6-10 Tons — Downflow Airflow Supply and Return;  
Through the Base Utilities  
Return  
Supply  
6-10 Tons — Horizontal Airflow Supply and Return  
6-10 Tons — Unit Clearance and Roof  
Opening  
82  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(6-10 Tons)  
All dimensions are in inches.  
6-10 Tons — Roof Curb  
857  
857  
ALL FLANGES 1 1/4” (31 MM)  
6-10 Tons — Downflow Duct  
Connections — Field Fabricated  
RT-PRC005-EN  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(3-5Tons Options/  
Accessories)  
All dimensions are in inches.  
Economizer , Manual or Motorized Fresh Air Damper  
Barometric Relief Damper Hood  
17 7/8"  
16"  
22 1/4"  
(454 MM)  
(406 MM)  
(565 MM)  
Swing Diameter for Hinged Doors Option  
See Page 79 for Through the Base Utilities Information  
84  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(6-10 Tons Options/  
Accessories)  
All dimensions are in inches.  
6-10 Tons — Power Exhaust  
6-10 Tons — Economizer and Barometric  
Relief Damper Hoods  
17"  
432 MM  
34 5/8"  
879 MM  
21 3/8"  
543 MM  
6-10 Tons — Swing Diameter for Hinged  
Door(s) Option  
See Page 82 for Through the Base Utilities Information  
RT-PRC005-EN  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table W-1— Maximum Unit and Corner Weights (Lbs) And Center of Gravity Dimensions (In.)  
MaximumWeights(Lbs)  
Corner Weights (Lbs)1  
Center of Gravity (In.)  
Unit  
ModelNo.  
Tons  
Shipping2  
501  
Net  
A
B
C
D
Length  
31  
Width  
19  
TSC036A  
409  
132  
104  
79  
94  
3
4
5
6
THC036A  
TSC048A  
THC048A  
TSC060A  
THC060A  
518  
526  
560  
543  
610  
426  
434  
468  
451  
518  
139  
140  
146  
149  
165  
108  
110  
113  
114  
124  
84  
91  
95  
94  
32  
33  
31  
31  
31  
19  
19  
20  
18  
19  
97  
88  
111  
99  
105  
124  
TSC072A  
THC072A  
824  
861  
681  
718  
236  
235  
177  
182  
119  
128  
150  
173  
38  
38  
21  
22  
TSC090A  
TSC092A  
THC092A  
897  
899  
1000  
754  
756  
857  
257  
261  
289  
188  
202  
222  
129  
131  
148  
180  
162  
197  
37  
39  
38  
22  
21  
21  
7½  
8½  
TSC102A  
THC102A  
978  
1036  
835  
893  
281  
294  
223  
233  
149  
159  
181  
207  
40  
39  
21  
22  
TSC120A  
THC120A  
1023  
1125  
880  
982  
298  
323  
238  
253  
158  
178  
187  
229  
40  
39  
21  
22  
10  
Notes:  
1. Corner weights are given for information only.  
2. Weights are approximate.  
Table W-2 — Factory-installed Options Net Weights (Lbs)1,2  
NetWeight  
Accessory  
Economizer  
Barometric Relief  
Powered Exhaust  
Motorized Outside Air Damper  
Manual Outside Air Damper  
Roof Curb  
3-5Tons  
26  
7
20  
16  
70  
5
6-10Tons  
36  
10  
80  
30  
26  
115  
8
Oversized Motor  
Belt Drive Motor  
31  
7
5
12  
10  
38  
8
15  
5
7
5
20  
12  
38  
13  
30  
5
Smoke Detector, Return  
Smoke Detector, Supply  
Coil Guards  
Hinged Doors  
Powered Convenience Outlet  
Through the Base Electrical  
Electric Heaters  
Unit Mounted Circuit Breaker  
Unit Mounted Disconnect  
Novar Control  
5
8
5
8
Dehumidification (Hot Gas Reheat) Coil  
15  
25  
Notes:  
1.Weights for options not listed are < 5 lbs.  
2.Net weight should be added to unit weight when ordering factory-installed accessories.  
86  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
General  
UnitTop  
Evaporator and Condenser Coils  
The units shall be convertible airflow.The  
operating range shall be between 115°F  
and 0°F in cooling as standard from the  
factory for units with microprocessor  
controls. Operating range for units with  
electromechanical controls shall be  
between 115°F and 40°F. Cooling  
The top cover shall be one piece  
construction or where seams exist, it  
shall be double-hemmed and gasket-  
sealed. The ribbed top adds extra  
strength and prevents water from  
pooling on unit top.  
Internally finned, 5/16” copper tubes  
mechanically bonded to a configured  
aluminum plate fin shall be standard.  
Coils shall be leak tested at the factory to  
ensure the pressure integrity.The  
evaporator coil and condenser coil shall  
be leak tested to 200 psig and pressure  
tested to 450 psig.The condenser coil  
shall have a patent pending 1+1+1 hybrid  
coil designed with slight gaps for ease of  
cleaning. A removeable, reversible,  
double-sloped condensate drain pan with  
provision for through the base  
Filters  
performance shall be rated in accordance  
with ARI testing procedures. All units shall  
be factory assembled, internally wired,  
fully charged with R-22, and 100 percent  
run tested to check cooling operation, fan  
and blower rotation, and control  
sequence before leaving the factory.  
Wiring internal to the unit shall be colored  
and numbered for simplified  
identification. Units shall be UL listed and  
labeled, classified in accordance to UL  
1995/CAN/CSA No. 236-M90 for Central  
Cooling Air Conditioners. Canadian units  
shall be CSA Certified.  
One inch, throwaway filters shall be  
standard on all 3-5 ton units.The filter rack  
can be converted to two inch capability.  
Two inch filters shall be factory supplied  
on all 6-10 ton units. Optional 2-inch  
pleated filters shall be available.  
condensate drain is standard.  
Compressors  
Outdoor Fans  
All 3 ton standard units shall have direct-  
drive, hermetic, reciprocating type  
compressors.The reciprocating type  
compressors have a centrifugal oil pump  
providing positive lubrication to moving  
parts. Motor shall be suction gas-cooled  
and shall have a voltage utilization range  
of plus or minus 10 percent of unit  
nameplate voltage. Crankcase heater,  
internal temperature, and current-  
sensitive motor overloads shall be  
included for maximum protection.  
Compressors shall have internal spring  
isolation and sound muffling to minimize  
vibration transmission and noise. Low  
pressure switches shall be standard.  
The outdoor fan shall be direct-drive,  
statically and dynamically balanced,  
draw-through in the vertical discharge  
position.The fan motor shall be  
permanently lubricated and shall have  
built-in thermal overload protection.  
Casing  
Indoor Fan  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
All 3-5 ton 3-phase units offer a choice of  
direct-drive, FC, centrifugal fans or belt  
driven, FC centrifugal fans with  
adjustable motor sheaves. 3-5 ton direct  
drive oversized motors shall be available  
for high static operations. All 6-10 ton  
units shall have belt drive motors with an  
adjustable idler-arm assembly for quick-  
adjustment to fan belts and motor  
sheaves. All motors shall be thermally  
protected. All indoor fan motors meet the  
U.S. Energy Policy Act of 1992 (EPACT).  
weather-resistant baked enamel finish.  
Units surface shall be tested 1000 hours  
in a salt spray test in compliance with  
ASTM B117. Cabinet construction shall  
allow for all maintenance on one side of  
the unit. Service panels shall have lifting  
handles and be removed and reinstalled  
by removing only a single fastener while  
providing a water and air tight seal. All  
exposed vertical panels and top covers in  
the indoor air section shall be insulated  
with a cleanable foil-faced, fire-retardent  
permanent, odorless glass fiber material.  
The base of the unit shall be insulated  
with 1/2 inch, 1 pound density foil-faced,  
closed-cell material. All insulation edges  
shall be either captured or sealed.The  
units base pan shall have no penetrations  
within the perimeter of the curb other  
than the raised 11/ inch high downflow  
supply/return ope8nings to provide an  
added water integrity precaution, if the  
condensate drain backs up.The base of  
the unit shall have provisions for forklift  
and crane lifting, with forklift capabilities  
on three sides of the unit.  
3 ton high efficiency and 4-10 ton  
standard and high efficiency units shall  
have direct-drive, hermetic, scroll type  
compressors with centrifugal type oil  
pumps. Motor shall be suction gas-cooled  
and shall have a voltage utilization range  
of plus or minus 10 percent of unit  
nameplate voltage. Internal overloads  
shall be provided with the scroll  
compressors. Crankcase heaters shall be  
included on 7½ ton standard efficiency  
units.  
Refrigerant Circuits  
Each refrigerant circuit offers a choice of  
independent fixed orifice expansion  
devices or thermal expansion valve.  
Service pressure ports, and refrigerant  
line filter driers are factory-installed as  
standard. An area shall be provided for  
replacement suction line driers.  
RT-PRC005-EN  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Controls  
Powered or Unpowered Convenience  
Outlet  
Factory Installed Options  
Black Epoxy Pre-Coated Coils  
The black epoxy coils have a thermoset  
vinyl coating that is bonded to the  
aluminum fin stock prior to the fin-  
stamping process.The pre-coated coils  
are an economical option for protection in  
mildly corrosive environments.  
Unit shall be completely factory-wired  
with necessary controls and contactor  
pressure lugs or terminal block for power  
wiring. Unit shall provide an external  
location for mounting a fused disconnect  
device.  
This is a GFCI, 120v/15amp, 2 plug,  
convenience outlet, either powered or  
unpowered.When the convenience outlet  
is powered, a service receptacle  
disconnect will be available.The  
convenience outlet is powered from the  
line side of the disconnect or circuit  
breaker, and therefore will not be  
affected by the position of the disconnect  
or circuit breaker.This option can only be  
ordered when theThrough the Base  
Electrical with either the Disconnect  
Switch or Circuit Breaker option is  
ordered.  
A choice of microprocessor or  
electromechanical controls shall be  
available.  
Dehumidification Option  
The dehumidification (hot gas reheat)  
option shall provide increased  
Microprocessor controls provide for all 24  
volt control functions.The resident control  
algorithms shall make all heating, cooling,  
and/or ventilating decisions in response  
to electronic signals from sensors  
dehumidification.The option shall consist  
of a hot-gas reheat coil located on the  
leaving air side of the evaporator coil  
prepiped and circuited.  
The option shall be equipped with  
crankcase heater(s), low pressure  
switch(es), Frostat™, and a thermostatic  
expansion valve(s) (TXV) as standard.  
measuring indoor and outdoor  
Supply and/or Return Air Smoke  
Detector  
temperatures.The control algorithm  
maintains accurate temperature control,  
minimizes drift from set point, and  
With this option, if smoke is detected, all  
unit operation will be shut down. Reset  
will be manual at the unit. Return Air  
Smoke Detectors require minimum  
allowable airflow when used with certain  
models. See the Installation, Operation,  
and Maintenance (IOM) manual for the  
models affected and the minimum  
allowable airflow required.This option is  
available for microprocessor controlled  
units.  
provides better building comfort. A  
centralized Microprocessor shall provide  
anti-short cycle timing and time delay  
between compressors to provide a  
higher level of machine protection.  
High Pressure Cutout  
This is offered for units that do not have  
High Pressure cutout as standard. All 3-  
phase units with scroll compressors  
include High Pressure Cutout as  
standard.  
24-volt electromechanical control circuit  
shall include control transformer and  
contactor pressure lugs for power wiring.  
Units shall have single point power entry  
as standard.  
Hinged Access Doors  
Sheet metal hinges are available on the  
Filter/Evaporator, Supply Fan/Heat, and  
the Compressor/Control Access Doors.  
Thermal ExpansionValve  
All units shall have a short orifice  
refrigerate control metering device. For  
more exact refrigerant flow, when using  
unit in low airflow applications, aThermal  
ExpansionValve option shall be available.  
Novar Return Air Sensor  
This option, when used in conjunction  
with Novar Controls, will contain a factory  
provided and wired zone temperature  
sensor located in the return air stream.  
Through the Base Electrical Access  
An electrical service entrance shall be  
provided allowing electrical access for  
both control and main power connections  
inside the curb and through the base of  
the unit. Option will allow for field  
Novar Unit Controls  
Optional Novar rooftop unit controls shall  
be installed and tested. The Novar  
electronic thermostat module will  
interface to the unit microprocessor and  
will control the unit to the desired stage of  
cooling or heating.  
installation of liquid-tight conduit and an  
external field-installed disconnect switch.  
Phase Monitor  
Phase monitor shall provide 100%  
protection for motors and compressors  
against problems caused by phase loss,  
phase imbalance, and phase reversal.  
Phase monitor is equipped with an LED  
that provides an ON or FAULT indicator.  
88  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Through the Base Electrical with Circuit  
Breaker  
Discharge Air Sensing  
LonTalk® Communication Interface  
This option shall be provided to allow the  
unit to communicate as aTracer™LCI-R  
device or directly with generic LonTalk  
Network Building Automation System  
Controls.  
This option provides true discharge air  
sensing in heating models.This sensor is  
a status indicator readable through  
Tracer™ orTracker™. This option is  
available for microprocessor controlled  
units.  
This option is a thermal magnetic, molded  
case, HACR Circuit Breaker with  
provisions for through the base electrical  
connections.The circuit breaker will be  
installed in a water tight enclosure in the  
unit with access through a swinging door.  
Wiring will be provided from the switch to  
the unit high voltage terminal block.The  
circuit breaker will provide overcurrent  
protection, be sized per NEC and UL  
guidelines, and be agency recognized by  
UL/CSA.  
Oversized Motors  
Direct drive oversized motors shall be  
available for high static applications.  
Economizer  
This accessory shall be available with or  
without barometric relief.The assembly  
includes fully modulating 0-100 percent  
motor and dampers, minimum position  
setting, preset linkage, wiring harness  
with plug, spring return actuator and  
fixed dry bulb control.The barometric  
relief shall provide a pressure operated  
damper that shall be gravity closing and  
shall prohibit entrance of outside air  
during the equipment off” cycle.  
Optional solid state or differential  
enthalpy control shall be available for  
either factory or field installation.The  
economizer arrives in the shipping  
position and shall be moved to the  
operating position by the installing  
contractor.  
Reference or Comparative Enthalpy  
Reference Enthalpy is used to measure  
and communicate outdoor humidity.The  
unit receives and uses this information to  
provide improved comfort cooling while  
using the economizer. Comparative  
Enthalpy measures and communicates  
humidity for both outdoor and return air  
conditions, and return air temperature.  
The unit receives and uses this  
Through the Base Electrical with  
Disconnect Switch  
This 3-pole, molded case, disconnect  
switch with provisions for through the  
base electrical connections are available.  
The disconnect switch will be installed in  
the unit in a water tight enclosure with  
access through a swinging door.Wiring  
will be provided from the switch to the  
unit high voltage terminal block.The  
switch will be UL/CSA agency recognized.  
Note: The disconnect switch will be sized  
per NEC and UL guidelines but will not be  
used in place of unit overcurrent  
protection.  
information to maximize use of  
economizer cooling, and to provide  
maximum occupant comfort control.  
Reference or Comparative Enthalpy  
option shall be available when a factory  
or field installed Downflow Economizer is  
ordered.This option is available on all  
downflow models.  
Electric Heaters  
Electric heat modules shall be available  
for installation within basic unit. Electric  
heater elements shall be constructed of  
heavy-duty nickel chromium elements  
internally delta connected for 240 volt,  
wye connected for 480 and 600 volt.  
Staging shall be achieved through  
ReliaTel™. Each heater package shall  
have automatically reset high limit  
control operating through heating  
element contactors. All heaters shall be  
individually fused from the factory, where  
required, and shall meet all NEC and CEC  
requirements when properly installed.  
Power assemblies shall provide single-  
point connection. Electric heat modules  
shall be UL listed or CSA certified.  
Tool-less Hail Guards  
Tool-less, hail protection quality coil  
guards are available for condenser coil  
protection.  
Two-Inch Pleated Filters  
Two inch pleated media filters shall be  
available on all models.  
Trane Communication Interface  
Factory or Field Installed  
Options  
This option shall be provided to interface  
ReliaTel™ controlled units with theTrane  
Integrated ComfortTM systems.  
Clogged Filter/Fan Failure Switch  
A dedicated differential pressure switch is  
available to achieve active fan failure  
indication and/or clogged filter indication.  
These indications will be registered with  
either a zone sensor with status indication  
lights or an Integrated Comfort™ System.  
This option is available for  
microprocessor controlled units.  
Frostat  
Differential Pressure Switches  
This option is to be utilized as a safety  
device.The Frostat opens when  
temperatures on the evaporator coil fall  
below 10°F. The temperature will need to  
rise to 50°F before closing.This option  
should be utilized in low airflow or high  
outside air applications.  
These sensors allow individual fan failure  
and dirty filter indication for  
microprocessor controlled units.The fan  
failure switch will disable all unit functions  
and “flash” the Service LED on the zone  
sensor.The dirty filter switch will light the  
Service LED on the zone sensor and will  
allow continued unit operation.  
RT-PRC005-EN  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Humidity Sensor  
Thermostat  
Field Installed Options  
CO2 Sensing  
This duct-mounted humidity sensor is  
used to control activation of the hot gas  
reheat dehumidification option.The  
humidity sensor can be set for humidity  
levels between 40% and 60% relative  
humidity by adjusting the ReliaTel Options  
Module.  
Two stage heating and cooling operation  
or one stage heating and cooling shall be  
available in either manual or automatic  
changeover. Automatic programmable  
electronic with night set back shall also be  
available.  
The CO2 sensor shall have the ability to  
monitor space occupancy levels within  
the building by measuring the parts per  
million of CO2 (Carbon Dioxide) in the air.  
As the CO2 levels increase, the outside air  
damper modulates to meet the CO2  
space ventilation requirements.  
Ventilation Override Accessory  
Manual Outside Air Damper  
This rain hood and screen shall provide  
up to 50 percent outside air.  
With theVentilation Override Accessory  
installed, the unit can be set to transition  
up to 3 different pre-programmed  
sequences for Smoke Purge,  
Digital Display Zone Sensor  
The Digital LCD (Liquid Crystal Display)  
zone sensor has the look and functionality  
of standard zone sensors.This sensor  
includes a digital display of set point  
adjustment and space temperature in F  
(Fahrenheit) or C (Celsius). Includes FAN  
and SYSTEM buttons (supports the  
service functions of the standard sensor).  
E-squared memory stores last  
Motorized Outside Air Dampers  
Pressurization, and Exhaust.The  
Manually set outdoor air dampers shall  
provide up to 50 percent outside air. Once  
set, outdoor air dampers shall open to set  
position when indoor fan starts.The  
damper shall close to the full closed  
position when indoor fan shuts down.  
transition occurs when a binary input on  
the RTOM is closed (shorted).This would  
typically be a hard wired relay output  
from a smoke detector or fire control  
panel.The ventilation override accessory  
shall be available as field installed.  
Powered Exhaust  
Zone Sensor  
programmed set points. Requires 24VAC  
(Volts AC).This sensor should be utilized  
with ReliaTel™ controls.  
The powered exhaust, available for 6-10  
ton units, shall provide exhaust of return  
air, when using an economizer, to  
maintain better bulding pressurization.  
This control shall be provided to interface  
with the Micro equipped units and shall  
be available in either manual, automatic  
programmable with night setback, with  
system malfunction lights, or remote  
sensor options.  
DualThermistor Remote Zone Sensor  
This sensor will allow the customer to  
reduce the total number of remote  
sensors to obtain space temperature  
averaging. This sensor should be utilized  
with ReliaTel controls.  
Remote Potentiometer  
The minimum position setting of the  
economizer shall be adjusted with this  
accessory.  
Roof Curb  
High Static Drive  
The roof curb shall be designed to mate  
with the units downflow supply and  
return and provide support and a water  
tight installation when installed properly.  
The roof curb design shall allow field-  
fabricated rectangular supply/return  
ductwork to be connected directly to the  
curb. Curb design shall comply with  
NRCA requirements. Curb shall be  
shipped knocked down for field assembly  
and shall include wood nailer strips.  
The high static drive option shall allow the  
standard motor on the 6 and 7½ ton units  
to operate with improved external static  
capabilities.  
Humidity Sensor  
This wall-mounted humidity sensor is  
used to control activation of the hot gas  
reheat dehumidification option.The  
humidity sensor can be set for humidity  
levels between 40% and 60% relative  
humidity by adjusting the ReliaTel Options  
Module.  
90  
RT-PRC005-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*High Efficiency Units only  
Literature Order Number  
RT-PRC005-EN  
File Number  
PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-08-04  
PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-05-04  
05-04 Webb/Mason 08-04 Electronic Only  
Supersedes  
Trane  
Stocking Location  
A business ofAmerican Standard Companies  
For more information contact your local dealer  
(distributor), local district office, or e-mail us at  
Trane has a policy of continuous product and product data improvement and reserves the right to change design  
and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taurus Group Hair Dryer Airindb User Manual
Technicolor Thomson DVD Recorder DTH8555 X User Manual
Technicolor Thomson Network Router TG576 v7 User Manual
Technicolor Thomson Universal Remote VPH6920F User Manual
Tekkeon Battery Charger IA1000 User Manual
Teledex Telephone BTX4750 User Manual
Toshiba Flat Panel Television 24SL415U User Manual
Trane Air Conditioner PRC001 EN User Manual
ViewSonic Power Supply PS500B User Manual
Weber Gas Grill 2000 LX User Manual