Packaged Cooling with
Electric Heat Rooftop Units
Precedent™
3 - 10Tons — 60 Hz
RT-PRC005-EN
August 2004
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Introduction
2
4
Features and Benefits
Application Considerations
11
Selection Procedure
Model Number Description
General Data
12
14
15
Performance Data
19
19
37
59
Cooling Performance
Fan Performance
Heating Performance
Controls
62
64
78
87
Electric Power
Dimension andWeights
Mechanical Specifications
RT-PRC005-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Factory Installed Options
• Black Epoxy Pre-Coated Coils
• Dehumidification Option
• High Pressure Cutout
• Hinged Access Doors
• Novar Return Air Sensor
• Novar Unit Controls
Field Installed Options
• CO2 Sensing
• Digital Display Zone Sensor
• DualThermistor Remote Zone Sensor
• High Static Drive
• Humidity Sensor
• Manual Outside Air Damper
• Motorized Outside Air Dampers
• Powered Exhaust
• Phase Monitor
• Powered or Unpowered Convenience
Outlet
• Supply and/or Return Air Smoke
Detector
• Remote Potentiometer
• Roof Curb
• Thermostat
• Thermal ExpansionValve
• Through the Base Electrical Access
• Through the Base ElectricalWith Circuit
Breaker
• Ventilation Override Accessory
• Zone Sensor
• Through the Base ElectricalWith
Disconnect Switch
• Two-Inch Pleated Filters
Factory or Field Installed Options
• Clogged Filter/Fan Failure Switch
• Differential Pressure Switches
• Discharge Air Sensing Kit
• Economizer
• Electric Heaters
• Frostat
• LonTalk® Communications Interface
• Oversized Motors
• Reference or Comparative Enthalpy
• Tool-less Hail Guards
• Trane Communications Interface (TCI)
4
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Precedent with ReliaTel reduces the
number of components required to
operate the unit, thereby reducing
possibilities for component failure.
Some zone sensor options have central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Easy to Install, Service and
Maintain
Because today’s owners are very cost-
conscious when it comes to service and
maintenance, theTrane Precedent was
designed with direct input from service
contractors.This valuable information
helped to design a product that would get
the serviceman off the job quicker and
save the owner money. Precedent does
this by offering:
ReliaTel Makes Installing and
Servicing Easy
Other ReliaTel Benefits
ReliaTel eliminates the need for field
installed anti-shortcycle timer and time
delay relays. ReliaTel controls provide
these functions as an integral part of the
unit.The contractor no longer has to
purchase these controls as options and
pay to install them.
The ReliaTel built-in anti-shortcycle timer,
time delay relay and minimum “on” time
control functions are factory tested to
assure proper operation.
ReliaTel softens electrical “spikes” by
staging on fans, compressors and
heaters.
Quality and Reliability
ReliaTel™ Controls (LCI-R)
The wiring of the low voltage connections
to the unit and the zone sensors is as
easy as 1-1, 2-2, and 3-3.This simplified
system makes wiring easier for the
installer.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate at
predetermined temperature setpoint.
Intelligent Anticipation is a standard
ReliaTel feature. It functions continuously
as ReliaTel and zone sensor(s) work
together in harmony to provide much
tighter comfort control than conventional
electro-mechanical thermostats.
ReliaTel MakesTesting Easy
ReliaTel requires no special tools to run
the Precedent unit through its paces.
Simply place a jumper betweenTest 1
andTest 2 terminals on the LowVoltage
Terminal Board and the unit will walk
through its operational steps
automatically.
The same ReliaTel Board fits all
Precedent Packaged Gas/Electrics,
Cooling with Electric Heat, and Heat
Pump models.This provides
standardization of parts for contractors.
Less money is tied up in inventory with
ReliaTel.
ReliaTel controls provide unit control for
heating, cooling and ventilating utilizing
input from sensors that measure outdoor
and indoor temperature.
—The unit automatically returns
control to the zone sensor after
stepping through the test mode a
single time, even if the jumper is
left on the unit.
Quality and Reliability are enhanced
through ReliaTel control and logic:
Electromechanical Controls
As long as the unit has power and the
“system on” LED is lit, ReliaTel is
operational.The light indicates that the
controls are functioning properly.
—prevents the unit from short cycling,
considerably improving
compressor life.
For the simpler job that does not require
a building automation system, or
expanded diagnostics capabilities,
Precedent offers electromechnical
controls. This 24-volt control includes the
control transformer and contactor
pressure lugs for power wiring.
—ensures that the compressor will run
for a specific amount of time which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
ReliaTel features expanded diagnostic
capabilities when utilized withTrane
Integrated Comfort™ Systems.
ReliaTel™
RT-PRC005-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Compressors
Dehumidification (Hot Gas Reheat)
Option
Outstanding Standard and
Optional Components
Precedent contains the best compressor
technology available to achieve the
highest possible performance. Our
compressor line includesTrane built
ClimaTuff® reciprocating and scrolls.
This option allows for increased outdoor
air ventilation. It reduces humidity levels
while increasing comfort level in the air
space. Cooling can operate without a
demand for dehumidification.The hot gas
reheat coil is designed to deliver
maximum reheat temperatures and
pivot to allow for easy access cleaning.
Black Epoxy Pre-Coated Coils
Provides corrosion protection to
condenser coils for seacoast application.
Cabinet Integrity
For added water integrity, Precedent has
a raised 11/8" lip around the supply and
return of the downflow units to prevent
water from blowing into the ductwork.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
These sensors allow a zone sensor
service light or Integrated Comfort
System to indicate a dirty filter or a fan
that’s not working.The field installation
charges for these valuable feedback
devices often eliminate them from
consideration. Factory installation can
make such features a good investment.
Condenser Coil
Precedent boasts a patent-pending
1+1+1 condenser coil, permanently
gapped for easy cleaning.
Digital Display Zone Sensor
CO2 Sensing
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors. This sensor
should be utilized with ReliaTel™ controls.
The CO2 sensor has the ability to monitor
space occupancy levels within the
building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.The CO
sensor kit is available as a field installed2
accessory.
Discharge Air Sensing Kit
Provides true discharge air sensing in
heating models. The kit is functional only
with the ReliaTel Options Module.
DownflowAnd Horizontal Economizers
The economizers come with three control
options — dry bulb is standard, enthalpy
and differential enthalpy are optional.
ColoredAnd NumberedWiring
Save time and money tracing wires and
diagnosing the unit.
DualThermistor Remote Zone Sensor
This sensor will reduce the total number
of remote sensors to obtain space
temperature averaging. This sensor
should be utilized with ReliaTel controls.
6
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Foil-Faced Insulation
Phase Monitor
Standardized Components
All panels in the evaporator section of the
unit have cleanable foil-faced insulation.
All edges are either captured or sealed to
ensure no fibers get into the airstream.
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Components are placed in the same
location on all Precedent units. Familiarize
yourself with one Precedent and you are
familiar with every Precedent.
Factory Built Roof Curbs
Due to standardized components
throughout the Precedent line,
contractors/owners can stock fewer
parts.
Available for downflow units. Only two
roof curbs for the entire Precedent line
simplifies curb selection.
Power Exhaust Option
This option is available on downflow units
and provides exhaust of the return air,
when using a downflow economizer, to
maintain proper building pressurization.
Great for relieving most building
overpressurization problems.
Flexibility
Supply and/or Return Air Smoke
Detector
Units are built to order in our standard
“shortest in the industry” ship cycle time.
With this option
installed, if smoke is
detected, all unit
Fresh Air
0 - 25% manual or 0 - 50% motorized
outside air hoods are available.
Quick-Access Panels
operation will be shut
down. Reset will be
manual at the unit.
Return Air Smoke
Detectors require
minimum allowable
airflow when used
with certain models.
Remove two screws for access to the
standardized internal components and
wiring.
High Pressure Cutout
This factory-installed option is offered for
units that do not have High Pressure
Cutout as standard. All 3-phase units with
scroll compressors include High Pressure
cutout as standard.
Quick-Adjust Idler Arm
With the Quick-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.
High Static Drive Accessory
Thermal ExpansionValve
Available for a wider range of
applications.
Available on many models, this high
static drive accessory extends the
capability of the standard motor. Avoid
expensive motors and operating costs by
installing this optimized sheave
accessory.
Tool-less Hail Guards
Tool-less, hail protection quality coil
guards shall be either factory or field-
installed for condenser coil protection.
This option protects the condenser coil
from vandalism and/or hail damage.
Hinged Access Doors
These doors permit easy access to the
filter, fan/heat,
and compressor/
control sections.
They reduce the
potential roof
damage from
screws or sharp
access door
Reference or Comparative Enthalpy
Measures and communicates humidity
while maximizing comfort control.
corners.
LonTalk®
Sloped Drain Pans
Every Precedent unit has a non-
corrosive, removable, double-sloped
drain pan that’s
Communications
Interface
The LonTalk
communica-
easy to clean
tions interface
and reversible to
allo w installation
of drain trap on
allows the unit to communicate as a
Tracer™LCI-V device or directly with
generic LonTalk Network Building
Automation System Controls.
Trane Communication Interface (TCI)
Available factory or field installed.This
module when applied with the ReliaTel™
easily interfaces withTrane’s Integrated
ComfortTM System.
either side of the
unit.
RT-PRC005-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Unit Cabinet
Ventilation Override Accessory
Rigorous Testing
All of Precedent’s designs were
rigorously rain tested at the factory to
ensure water integrity.
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed top
is not only aesthetically pleasing, it is
designed to prevent water from pooling.
With theVentilation Override Accessory
installed, the unit can be set to transition
to up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust.The
Actual shipping tests were performed to
determine packaging requirements. Units
were test shipped around the country to
determine the best packaging. Factory
shake and drop tests were used as part
of the package design process to help
assure that the unit arrives at the job site
in top condition.
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.The ventilation override kit is
available as a field installed accessory.
Zone Sensors
Available in programmable, automatic
and manual styles.
Rigging tests include lifting a unit into the
air and letting it drop one foot, assuring
that the lifting lugs and rails hold up under
stress.
Precedent offers ultimate flexibility. Units
are built to order in our standard
“shortest in the industry” ship cycle time.
We perform a 100% coil leak test at the
factory.The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
VariTrac
All parts are inspected at the point of final
assembly. Sub-standard parts are
identified and rejected immediately.
WhenTrane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorousTrane
requirements.
VariTrac™
8
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
LowVoltage Connections
Single Point Power
A single electrical connection powers the
unit.
Easy to Install
Convertible Units
The wiring of the low voltage connections
to the unit and the zone sensors is as
simple as 1-1, 2-2, and 3-3.This simplified
system makes it easy for the installer to
wire.
–The units ship in a downflow
configuration.They can be easily
converted to horizontal by simply
–mUnoivtsincgotmweocpoamnepllse.te with horizontal
duct flanges so the contractor doesn’t
have to field fabricate them.These duct
flanges are a time and cost saver.
Single Side Service
Single side service is standard on all
units.
Through the Base Condensate
Every unit includes provisions for through
the base condensate drain connections.
This allows the drain to be connected
through the roof curb instead of a roof
penetration.
Through the Base Electrical Utility
Access
Factory provided through the base
openings simplify wiring and piping.
Because these utility openings frequently
minimize the number of roof
penetrations, the integrity of roofing
materials is enhanced.
Electric Heaters
Electric heat modules are available within
the basic unit. If ordering theThrough the
Base Electrical option with an Electrical
Heater, the heater must be factory
installed.
Powered or Unpowered Convenience
Outlet
This option is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered.This option can only be
ordered when theThrough the Base
Electrical with either the Disconnect
Switch, or Circuit Breaker, option is
ordered.This option is available on all
downflow models.
Easy Access LowVoltageTerminal Board
Precedent’s LowVoltageTerminal Board
is external to the electrical control
cabinet. It is extremely easy to locate and
attach the thermostat wire and test
operation of all unit functions.This is
another cost and time saving installation
feature.
Through the Base Electrical with Circuit
Breaker
This option is a factory installed thermal
magnetic, molded case, HACR Circuit
Breaker with provisions for through the
base electrical connections. This option is
available on all downflow models.
RT-PRC005-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Through the Base Electrical with
Disconnect Switch
Factory installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available. This option is available on
all downflow models.
Added Efficiency
Airflow
Airflow is outstanding.The Precedent can
replace an older machine with old
ductwork and, in many cases, improve
the comfort through better air
distribution.
Through the Base UtilitiesAccess
Belt or direct drive – standard or
oversized supply fan motors meet a wide
airflow range.
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
Cooling
Standard or High Efficiency Cooling
available.
installation of liquid-tight conduit and an
external field installed disconnect switch.
Economizer
Unit Mounted Disconnect or Circuit
Breaker
Equipped with either dry bulb, reference
or comparative enthalpy sensing, this
feature provides free cooling as the
outdoor temperature and/or humidity
decreases. Economizers, correctly
installed, offer a valuable energy savings.
Factory-installed economizers save time
and ensure proper installation.
Codes require a method of assured unit
shutdown for servicing. Field-installed
disconnects sometimes interfere with
service access. Factory installation of unit
disconnects reduces costs, assures
proper mounting and provides the
opportunity to upgrade to unit circuit
breaker protection.
High Efficiency Motors
This option is available with efficiency
ratings from 86.5 up to 91.0. It is not
available for all models.
LowAmbient Cooling
All Precedent microprocessor units have
cooling capabilities down to 0°F as
standard. Electromechanical models
have cooling capabilities to 40°F as built,
or to 0°F by adding the optional low
ambient control (frostat).
Oversized Motors
Factory or field installed oversized
motors available for high static
applications.
Convenience Outlet
Unit Mounted Disconnect
or Circuit Breaker
One of our FinestAssets:
Trane Sales Representatives are a
Support Group that can assist you with:
— Product
Factory Installed Options
A wide variety of Factory Installed
Options (FIOPs) are available.
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Precedent has the features and benefits
that make it first class in the light
commercial rooftop market.
10
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
LowAmbient Cooling
The Precedent™ line features, with
ReliaTel™ microprocessor controls, low
ambient cooling down to 0°F. With
electromechanical controls, Precedent
features low ambient cooling to 40°F. The
following options need to be included/
considered when low ambient
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate service
maximum capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be reviewed
with the localTrane sales personnel.
applications are required: continuous fan
operation, crankcase heaters, thermal
expansion valves, frostat. Contact your
localTrane Representative for more
assistance with low ambient cooling
applications.
Unit Pitch
These units have reversible sloped
condensate drain pans. Units must be
installed level, any unit slope must be
toward the side of unit where condensate
drain is connected.
Barometric Relief
This product line offers an optional
barometric relief damper. for use in
conjunction with economizer option. This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers and
relieving the conditioned space.
NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED.
PRESSURE DROP OFTHE RETURN AIR
SYSTEM SHOULD BE CONSIDEREDTO
CONTROL BUILDING PRESSURIZATION.
RT-PRC005-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedures
Step 4
Cooling Capacity
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Heating Capacity
Step 1
Calculate the building heating load using
theTrane calculation form or other
standard accepted method.
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount of
heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure.To determine the
total unit static pressure:
Step 2
Size the system heating capacity to
Factors used in unit selection:
match the calculated building heating
A
load.The following are building heating
External Static (duct system)
0.36 wg
Total Cooling Load: 59 MBh
requirements:
B
A
Sensible Cooling Load: 40 MBh
Standard Filter 1 in.
fromTable PD-61
0.15 wg
Total heating load of 15 MBH
C
B
Airflow: 2000 cfm
2000 cfm
Economizer
0.18 wg
D
C
Electrical Characteristics: 460/60/3
(100% Outside Air)
fromTable
PD-73
460 volt/3 phase Power Supply
E
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67WB Outdoor
Ambient: 95
The electric heat accessory capacities
are listed inTable PD-62. From the table,
a 6 kW heater will deliver 20.48 MBH at
480 volts. In order to determine capacity
at 460 volts, the heater voltage
correction factor fromTable PD-63 must
be used.Therefore, 20.48 MBH x .9118
(voltage correction factor) = 18.80 MBH.
Electric Heater Size 6 kW 0.056 wg
fromTable PD-61
F
External Static Pressure: 0.36 in. wg
(reference “Heating Capacity” section on
this page for determination of heater
size)
G
Downflow Configuration
H
Total Static Pressure
0.75 wg
High Efficiency
I
Economizer
Note:The Evaporator Fan Performance
Table PD-46 has deducted the pressure
drop for a 1 in. filter already in the unit
(see note belowTable PD-24).Therefore,
the actual total static pressure is 0.75 -
0.15 (fromTable PD - 61) = 0.60 wg.
Air Delivery Selection
External static pressure drop through
the air distribution system has been
calculated to be 0.60 inches of water.
EnterTable PD-46 for aTHC060A4 at
2000 cfm and 0.60 static pressure.The
standard direct drive motor will give the
desired airflow at a rated bhp of 0.90
and 998 rpm.
Step 2
As a starting point, a rough determination
must be made of the size of the unit.The
final selection will be made after
examining the performance at the given
conditions. Divide the total cooling load by
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
With 2000 cfm and 0.60 wg.
Table PD-46 shows .90 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
59 MBh / 12 MBh = approx. 5 tons
2.829 x bhp + .4024 = MBH.
2.829 x .83 + .4024 = 2.75 MBH.
Step 3
Table PD-15 shows that aTHC060A4 has
a gross cooling capacity of 62.4 MBh and
48.4 MBh sensible capacity at 2000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
NetTotal Cooling Capacity
= 62.4 MBH - 2.95 = 59.45 MBH.
Net Sensible Cooling Capacity
= 48.4 MBH - 2.95 = 45.45 MBH.
To Find Capacity at Intermediate
Conditions Not in theTable
Step 5
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
12
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Step 3: Determine reheat
temperature rise
Go to PD-66 for reheat temperature rise:
26.7°F db
Dehumidification Selection
Typical 10 tonTHC120A
2000 cfmTotal Supply airflow
800 cfm Outside Air (40%)
1200 cfm Return Air
0.41” External Static Pressure
68°F DB,
67°F WB
OA Conditions
Part load day and raining
68°F db
OA
75°F DB,
RA'
52% RH
67°F wb
MA' 72.2°F DB
65°F WB
RA’ conditions
75°F db
63°F wb
OA
47°F DB
SA'
MA'
RA'
73°F DB
SA
Step 1: Determine the mixed/
entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
SA
REHEAT
SA'
MA’ = (0.40*68°F) + (0.60*75°F)
MA’ = 72.20°F db
Chart C-1
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
Note: Reheat temperature rise is based
on supply airflow and leaving evaporator
coil temperature.
Step 5: Determine static pressure
drop add for reheat
MA’
72.2°F db
65°F wb
Table PD-61 shows a static pressure drop
of 0.09” wc 0.41”+ 0.09” = 0.5” wc
Step 4: Determine leaving unit
temperature
Reheat temperature (obtained in step 3)
+ SA’
26.7°F db + 47°F = 73.7°F db
SA=73.7°F
Table PD-57 indicates that a standard
motor and field installed low static drive
kit is needed for this airflow and static
pressure range.
Step 2: Determine leaving unit
temperature
Leaving UnitTemperature = SA’
Utilize theTOPSS™ program to
determine the leaving unit temperature.
Consider Chart C-1. If the space relative
humidity is equal to or above the space
relative humidity setpoint, the
45°F db
44°F wb
43°F dp
Dehumidification option will:
• Energize compressor or both
compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.
At MA’, air enters the RTU.The RTU filters,
cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 73.7°F (SA) supply air to the
space.
RT-PRC005-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
T
1
S
2
C 036 A
3 4,5,6 7
3
8
R
9
B
A
**
C
0
0
0
A
1
0
0
0
1
A
1
10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
DIGIT 1 - Unit Function
DIGITS 12, 13 - Service Sequence
** Factory Assigned
DIGIT 20 - Convenience Outlet
T = DX Cooling
=
0 = No Convenience Outlet
A = Unpowered Convenience Outlet
B = Powered Convenience Outlet
(3 phase only)
DIGIT 2 - Efficiency
DIGIT 14 - Fresh Air Selection
S = Standard Efficiency
H = High Efficiency
0 = No Fresh Air
A = Manual Outside Air Damper 0-50%
B = Motorized Outside Air Damper 0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
DIGIT 21 - Communications Options
0 = No Communications Interface
1 = Trane Communications Interface
2 = LonTalk® Communications Interface
3 = Novar 2024 Controls
DIGIT 3 - Airflow
C = Convertible
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
DIGITS 4,5,6 - Nominal Gross Cooling
Capacity (MBh)
4 = Novar 3051 Controls
DIGIT 22 - Refrigeration System Option
036 =
048 =
060 =
072 =
090 =
092 =
102 =
120 =
3 Ton
4 Ton
0 = Standard Refrigeration System
A = Thermal Expansion Valve (TXV)
B = Dehumidification (Hot Gas Reheat
Coil)
5 Ton
6 Ton
7½ Ton, Single Compressor
7½ Ton, Dual Compressor
8½ Ton
DIGIT 23 - Refrigeration Controls
DIGIT 15 - Supply Fan/Drive Type/Motor
10 Ton
0 = No Refrigeration Control
1 = High Pressure Control
2 = Frostat
0 = Standard Drive
1 = Oversized Motor
2 = Optional Belt Drive Motor
DIGIT 7 - Major Design Sequence
A = First
3 = Crankcase Heater
4 = High Pressure Control and Frostat
5 = High Pressure Control and Crankcase
Heater
6 = Frostat and Crankcase Heater
7 = High Pressure Control, Frostat and
Crankcase Heater
DIGIT 16 - Hinged Service Access/Filters
DIGIT 8 - Unit Voltage
0 = Standard Panels/Standard Filters
A = Hinged Access Panels/Standard Filters
B = Standard Panels/2” Pleated Filters
C = Hinged Access Panels/2” Pleated
Filters
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
W= 575/60/3
K = 380/60/3
DIGIT 24 - Smoke Detector
DIGIT 17 - Condenser Coil Protection
DIGIT 9 - Unit Controls
0 = No Smoke Detector
A = Return Air Smoke Detector
B = Supply Air Smoke Detector
C = Supply and Return Air Smoke
Detectors
0 = Standard Coil
E = Electromechanical
R = ReliaTel™Microprocessor
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil
3 = Epoxy Coated Condenser Coil with
Hail Guard
DIGIT 10 - Heating Capacity
0 = No Electric Heat
A = 5 kW (1 phase)
B = 6 kW (3 phase)
C = 9 kW (3 phase)
D = 10 kW (1 phase)
E = 12 kW (3 phase)
F = 14 kW (1 phase)
G = 18 kW (1 and 3 phase)
J = 23 kW (3 phase)
K = 27 kW (3 phase)
N = 36 kW (3 phase)
P = 54 kW (3 phase)
DIGIT 25 - Monitoring Controls
DIGIT 18 - Through the Base Provisions
0 = No Monitoring Control
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = Discharge Air Sensing Tube
4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
0 = No Through the Base Provisions
A = Through the Base Electric
DIGIT 19 - Disconnect/Circuit Breaker/
Phase Monitor (3 phase only)
0 = No Disconnect/NoCircuit Breaker/No
Phase Monitor
1 = Unit Mounted Non-Fused Disconnect
2 = Unit Mounted Circuit Breaker
3 = Phase Monitor
4 = Phase Monitor & Non-Fused
Disconnect Switch
5 = Phase Monitor & Circuit Breaker
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
8 = Novar Return Air Sensor
DIGIT 11 - Minor Design Sequence
A = First Sequence
Example:
ModelnumberTSC036A3RBA**C000A10001A1describesaunitwiththefollowingcharacteristics:DXCooling,3tonnominalcoolingcapacity,208-230/60/3powersupply,ReliaTel™ controls,6kW
electric heater model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels/filters, standard condenser coil with no coil protection, through the
base electric, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and clogged filter switch.
14
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(3 - 5Ton)
Standard Efficiency
Table GD – 1 — General Data
3Ton Convertible Units
TSC036A1, A3, A4, AW
4Ton Convertible Units
TSC048A1 TSC048A3, A4, AW
5Ton Convertible Units
TSC060A1 TSC060A3, A4, AW TSC060AK
Cooling Performance1
Gross Cooling Capacity
SEER2
37,400
10.75
50,300
10.1
49,200
10.0
63,100
9.9
63,100
10.2
63,100
10.2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
System Power (kW)
1,200/1,200
36,000
1,600/1,600
48,000
5.28
1,600/1,600
47,000
2,000/2,000
60,000
6.86
2,000/2,000
60,000
6.78
2,000/2,000
60,000
6.78
3.798
5.40
Compressor
No./Type
Outdoor Sound Rating (dB)3
1/Recip.
83
1/Scroll
86
1/Scroll
82
1/Scroll
84
1/Scroll
84
1/Scroll
84
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Lanced
0.3125
7.19
Lanced
0.3125
6.17
Lanced
0.3125
9.59
Lanced
0.3125
8.81
Lanced
0.3125
8.81
Lanced
0.3125
8.81
2/17
2/17
1/17
2/17
2/17
2/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Face Area (sq ft)
5.67
6.68
6.17
5.00
5.00
5.00
Rows/FPI
2/16
3/16
3/16
3/16
3/16
3/16
Refrigerant Control
Drain Connection No./Size (in.)
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Propeller
1/22
Direct/1
2550
Propeller
1/22
Direct/1
2850
Propeller
1/22
Direct/1
3610
Propeller
1/22
Direct/1
3470
Propeller
1/22
Direct/1
3470
Propeller
1/22
Direct/1
3470
No. Motors/HP
1/.20
1/.33
1/.33
1/.33
1/.33
1/.40
Motor RPM
1115
1115
1115
1115
1115
1115
Direct Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
10 x 10
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
12x11/–
Direct/2
1
Motor HP (Standard/Oversized)
Motor RPM (Low/High Speed)
Oversized Motor RPM
(Low/High Speed)
Motor Frame Size
(Standard/Oversized)
.33/.50
950/1060
.60/.80
930/1000
.60/.80
930/1000
.90/1.00
985/1100
.90/1.00
985/1100
1.0/–
935/1100
1100/1145
48/48
1000/1100
48/48
1000/1100
48/48
1080/1135
48/48
1080/1135
48/48
—
48/—
Belt Drive Indoor Fan —Type
No. Used
FC Centrifugal
—
—
—
—
—
—
—
—
FC Centrifugal
—
—
—
—
—
—
—
—
FC Centrifugal
—
—
—
—
—
—
—
—
1
1
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
Motor HP
Motor RPM
11 x 11
11 x 11
Belt/Variable Speed
11 x 11
Belt/Variable Speed
Belt/Variable Speed6
1
1
1
1.00
1750
56
1.00
1750
56
1.00
1750
56
Motor Frame Size
Filters —Type Furnished 7
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)4
3.8
4.4
3.8
4.7
4.9
4.9
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
basedonARIStandard210/240exceptAK(380V/60Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. TSC036A1SEERis10.5.
6. Belt Drive Motor is not available for TSC036A1.
7. Optional 2” Pleated Filters also available.
8. TSC036A1SystemPower(kW)is3.91.
RT-PRC005-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(6 - 10Ton)
Standard Efficiency
Table GD – 2— General Data
6Ton
Convertible Units
7½Ton
Convertible Units
8½Ton
Convertible Units
10Ton
Convertible Units
TSC072A3, A4, AW, AK TSC090A3,A4,AW, AK TSC092A3, A4, AW
TSC102A3, A4, AW, AK TSC120A3, A4, AW, AK
Cooling Performance1
Gross Cooling Capacity
EER2
72,000
10.3
95,000
10.3
92,000
10.3
105,000
10.3
118,000
10.46
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue (IPLV)3
System Power (kW)
Compressor
2,400/2,100
3,000/2,625
3,000/2,625
87,000
11.18
3,400/3,000
100,0007
11.98
4,000/3,200
114,0007
11.58
69,000
90,000
—
—
6.7
8.74
8.45
9.719
10.969
No./Type
1/Scroll
88
Lanced
0.3125
13.88
1/Scroll
90
Lanced
0.3125
17.00
2/Scrolls
87
Lanced
0.3125
2/Scrolls
86
Lanced
0.3125
2/Scrolls
86
Lanced
0.3125
Outdoor Sound Rating (dB)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
17.00
19.83
19.83
Rows/FPI
2/17
3/17
2/17
2/17
2/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
9.89
Lanced
0.3125
9.89
Lanced
0.3125
9.89
Lanced
0.3125
12.36
Lanced
0.3125
12.36
Face Area (sq ft)
Rows/FPI
2/16
3/16
3/16
3/16
4/16
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/¾ NPT
Propeller
1/26
Short Orifice
1/¾ NPT
Propeller
1/26
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6500
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
7100
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
7000
Direct/1
6100
Direct/1
6200
No. Motors/HP
Motor RPM
1/0.7011
1115
1/0.7011
1115
1/0.70
1115
1/0.75
1115
1/0.75
1115
Belt Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size
12 x 12
Belt/Variable Speed
1
12 x 12
Belt/Variable Speed
1
12 x 12
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
1.00/2.0012
1750
2.00/3.00
1750
2.00/3.00
1750
2.00/3.00
1750
3.00/5.00
1750/3450
56
56
56
56
56
Filters —Type Furnished 10
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)5
Throwaway
(4) 16 x 25 x 2
7.1
Throwaway
(4) 16 x 25 x 2
11.5
Throwaway
(4) 16 x 25 x 2
6.2 Circuit 1
3.4 Circuit 2
Throwaway
(4) 20 x 25 x 2
7.9 Circuit 1
4.0 Circuit 2
Throwaway
(4) 20 x 25 x 2
7.2 Circuit 1
5.3 Circuit 2
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
basedonARIStandard210/240exceptAK(380V/60Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow is 10.3.
7. ARI Net Cooling Capacity shown is for downflow airflow. Cooling Capacity for Horizontal airflow TSC102A is 99,000; TSC120A is 112,000.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for Horizontal airflow TSC092A is 10.8, TSC102A is 11.5; TSC120A is 11.0.
9. System Power (kW) shown is for downflow airflow. System Power (kW) forHorizontal airflow TSC102A is 9.61; for TSC120A is 10.87.
10. Optional 2” Pleated Filters also available.
11. Outdoor motor is 0.75 hp for AK (380V/60 Hz units).
12. Standard indoor motor is 2.00 hp for AK (380V/60 Hz) units.
16
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(3 - 5Ton)
High Efficiency
Table GD – 3 — General Data
3Ton
4Ton
5 Ton
Convertible Units
THC036A1,A3,A4,AW
Convertible Units
THC048A1,A3,A4,AW
Convertible Units
THC060A1
THC060A3,A4,AW
Cooling Performance1
Gross Cooling Capacity
38,000
49,800
62,100
62,400
SEER / EER2
12.5/—
12.0/—
11.8/—
12.0/ —
Nominal CFM / ARI Rated CFM
1,200/1,200
1,600/1,600
2,000/2,000
2,000/2,000
ARI Net Cooling Capacity
System Power (kW)
Compressor
36,600
3.33
47,500
4.48
59,000
5.73
59,500
5.56
No./Type
1/Climatuff Scroll
83
1/Climatuff Scroll
85
1/Climatuff Scroll
84
1/Climatuff Scroll
84
Outdoor Sound Rating (dB)3
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
Lanced
0.3125
7.19
Lanced
0.3125
9.59
Lanced
0.3125
10.96
Lanced
0.3125
10.96
Rows/FPI
2/17
3/17
3/17
3/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
6.68
Lanced
0.3125
6.68
Lanced
0.3125
7.71
Lanced
0.3125
7.71
Face Area (sq ft)
Rows/FPI
3/16
4/16
4/16
4/16
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/¾ NPT
Propeller
1/22
Short Orifice
1/¾ NPT
Propeller
1/22
Short Orifice
1/¾ NPT
Propeller
1/22
Direct/1
3170
Short Orifice9
1/¾ NPT
Propeller
1/22
Direct/110
2550
Direct/110
3050
Direct/110
3370
No. Motors/HP
1/.20
1/.33
1/.33
1/.33
Motor RPM
1115
1115
1115
1115
Direct Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
10 x 10
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
Motor HP (Standard/Oversized)
Standard Motor RPM (Low/High Speed)
Oversized Motor RPM (Low/High Speed)
Motor Frame Size (Standard/Oversized)
Belt Drive Indoor Fan —Type
No. Used
.33/.50
950/1060
1100/1145
48/48
FC Centrifugal
1
.60/.80
930/1000
1000/1100
48/48
FC Centrifugal
1
.90/1.00
985/1100
1080/1135
48/48
.90/1.00
985/1100
1080/1135
48/48
FC Centrifugal
1
—
—
Diameter xWidth (in.)
11 x 11
11 x 11
—
11 x 11
DriveType/No. Speeds
Belt/Variable Speed 6
1
Belt/Variable Speed 6
1
—
Belt/Variable Speed
No. Motors
—
1
Motor HP
Standard Motor RPM
Motor Frame Size
1.00
1750
56
1.00
1750
56
—
—
—
1.00
1750
56
Filters —Type Furnished 7
(No.) Size Recommended (in.)
Optional Hot Gas Reheat Coil-Type12
Tube Size (in.) OD
Face Area (sq. ft)
Rows/FPI
Refrigerant Charge (Lbs of R-22)4
Standard
Throwaway
(2) 20 x 25 x 1
Lanced
0.375
Throwaway
(2) 20 x 25 x 1
Lanced
0.375
Throwaway
(2) 20 x 30 x 1
Throwaway
(2) 20 x 30 x 111
Lanced
0.375
—
—
—
—
2.22
1/16
2.22
1/16
2.22
2/16
5.38
5.3
7. 7 5
8.5
7. 9
—
8 . 4
10.7
Optional Hot Gas Reheat Coil
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
whichisbasedonARIStandard210/240.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.
6. Belt Drive Motor is not available for THC036A1, THC048A1.
7. Optional 2” Pleated Filters also available.
8. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.
9. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
10. With Dehumidification (Hot Gas Reheat) option: Direct/2 speed.
11. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
12. Availableonthree-phaseonly.
RT-PRC005-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(6 - 10Ton)
High Efficiency
Table GD – 4— General Data
6Ton
7½Ton
8½Ton
10Ton
Convertible Units
THC072A3, A4, AW
Convertible Units
THC092A3, A4, AW
Convertible Units
THC102A3, A4. AW
Convertible Units
THC120A3, A4, AW
Cooling Performance1
Gross Cooling Capacity
EER2
73,000
11.56
94,000
11.56
103,000
11.56
117,000
11.26
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue (IPLV)3
System Power (kW)
Compressor
2,400/2,100
3,000/2,625
90,00010
11.98
3,400/3,000
98,00010
12.18
4,000/3,200
109,00010
12.08
70,000
—
6.097
7.837
8.527
9.737
No./Type
1/Climatuff Scroll
2/Climatuff Scrolls
91
2/Climatuff Scrolls
89
2/Climatuff Scrolls
88
Outdoor Sound Rating (dB)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
89
Lanced
0.3125
17.00
Lanced
0.3125
17.50
Lanced
0.3125
19.83
Lanced
0.3125
27.21
Rows/FPI
3/17
3/17
3/17
3/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
9.89
Lanced
0.3125
12.36
Lanced
0.3125
12.36
Lanced
0.3125
12.36
Face Area (sq ft)
Rows/FPI
3/16
3/16
4/16
5/16
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6100
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6200
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6600
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
7000
No. Motors/HP
Motor RPM
1/0.70
1075
1/0.70
1075
1/0.75
1075
1/0.75
1075
Belt Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
12 x 12
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size
1.00/2.00
1750
56
2.00/3.00
1750
2.00/3.00
1750
3.00/5.00
1750/3450
56
56
56
Filters —Type Furnished 9
(No.) Size Recommended (in.)
Optional Hot Gas Reheat Coil —Type
Tube Size (in.) OD
Throwaway
(4) 16 x 25 x 2
—
Throwaway
(4) 20 x 25 x 2
Lanced
0.375
Throwaway
(4) 20 x 25 x 2
Lanced
0.375
Throwaway
(4) 20 x 25 x 2
Lanced
0.375
—
Face Area (sq. ft.)
—
5.19
5.19
5.19
Rows/FPI
Refrigerant Charge (Lbs of R-22)5
—
10.7
2/16
6.4 Circuit 1
6.2 Circuit 2
2/16
7.4 Circuit 1
7.1 Circuit 2
2/16
11.0 Circuit 1
7.3 Circuit 2
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
basedonARIStandard210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.
7. System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.
9. Optional 2” Pleated Filters also available.
10. Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.
18
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (3, 4Ton)
Data
Standard Efficiency
Table PD-1 — Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TSC036A1, A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.6 29.0 38.6 22.3 40.6 14.7 31.2 27.3 36.6 21.1 39.5 13.8 28.2 25.6 33.4 19.6 37.8 12.9 25.1 24.1 29.6 18.2 35.5 11.9
80 35.6 35.0 38.8 27.3 41.0 20.2 32.6 32.6 36.8 26.6 39.8 19.5 30.0 30.0 33.5 25.2 38.0 18.5 27.3 27.3 29.9 23.5 35.6 17.5
1080
1200
1320
85
37.6 37.6 39.2 32.5 41.5 24.7 35.6 35.6 37.2 32.2 40.1 24.2 32.8 32.8 34.2 31.0 38.2 23.8 30.1 30.1 30.7 29.3 35.8 23.0
90 39.3 39.3 39.7 37.6 42.0 29.2 37.8 37.8 37.9 37.6 40.4 29.1 35.7 35.7 35.7 35.7 38.5 28.9 33.0 33.0 32.9 32.9 36.0 28.4
75 35.6 30.9 39.0 22.8 40.9 14.9 32.2 29.2 37.3 22.1 39.8 14.1 29.0 27.5 34.3 20.7 38.2 13.1 25.9 25.9 30.4 19.0 36.0 12.1
80 36.7 36.7 39.3 28.4 41.4 20.6 34.3 34.3 37.4 28.1 40.2 20.3 31.4 31.4 34.5 26.9 38.4 19.3 28.6 28.6 30.7 25.2 36.1 18.3
85 38.7 38.7 39.7 33.9 41.9 25.3 37.0 37.0 37.9 34.0 40.5 25.0 34.5 34.5 35.3 33.2 38.7 24.8 31.5 31.5 31.7 31.6 36.3 24.2
90 40.2 40.2 40.4 39.2 42.3 30.1 38.8 38.8 38.8 38.8 40.9 30.2 37.1 37.1 37.0 37.0 39.1 30.3 34.6 34.6 34.6 34.6 36.6 30.0
75 36.4 32.6 39.4 23.5 41.1 15.1 33.2 31.0 37.7 23.0 40.1 14.3 29.8 29.3 34.9 21.8 38.5 13.4 26.8 26.8 30.9 20.0 36.3 12.4
80
37.7 37.7 39.7 29.4 41.6 20.9 35.7 35.7 37.9 29.3 40.4 21.2 32.7 32.7 35.2 28.5 38.7 19.9 29.8 29.8 31.4 26.8 36.5 19.0
85 39.4 39.4 40.2 35.2 42.1 25.9 37.9 37.9 38.5 35.6 40.8 25.7 35.9 35.9 36.2 35.3 39.1 25.7 32.9 32.9 32.9 32.9 36.7 25.3
90 40.8 40.8 40.9 40.5 42.6 30.8 39.7 39.7 39.6 39.6 41.2 31.2 38.0 38.0 38.0 38.0 39.5 31.6 35.9 35.9 35.9 35.9 37.1 31.5
75
37.0 34.1 39.7 24.0 41.3 15.3 34.1 32.8 38.0 23.7 40.3 14.5 30.6 30.6 35.5 22.7 38.7 13.6 27.7 27.7 31.4 21.0 36.6 12.6
80 38.4 38.4 40.0 30.3 41.8 21.2 36.7 36.7 38.3 30.5 40.8 21.0 33.9 33.9 35.8 30.0 39.0 20.4 30.8 30.8 32.0 28.4 36.8 19.7
85 40.0 40.0 40.6 36.3 42.4 26.4 38.7 38.7 39.0 37.0 41.2 26.7 36.8 36.8 36.8 36.8 39.4 26.6 34.2 34.2 34.2 34.2 37.0 26.4
90 41.4 41.4 41.4 41.4 42.9 31.6 40.3 40.3 40.3 40.3 41.5 32.1 38.7 38.7 38.7 38.7 39.9 32.7 36.7 36.7 36.7 36.7 37.6 33.0
1440
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (MBH) 4 Ton Single Phase TSC048A1
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.5 38.7 52.4 30.0 56.4 20.1 41.6 36.6 49.0 28.3 54.4 18.9 37.6 34.5 44.4 26.7 51.8 17.5 33.5 32.3 39.8 24.5 48.0 15.8
80 46.5 46.5 52.5 37.6 56.8 28.1 43.2 43.2 49.1 35.9 54.8 26.7 39.9 39.9 44.6 33.8 52.0 25.2 36.5 36.5 40.1 31.6 48.2 23.4
85 50.3 50.3 53.0 45.1 57.4 34.9 47.0 47.0 49.7 43.7 55.0 33.9 43.6 43.6 45.3 41.6 52.2 32.8 40.2 40.2 41.0 39.5 48.3 31.0
90 53.3 53.3 53.8 52.5 57.7 41.1 50.8 50.8 50.8 50.8 55.5 41.0 47.5 47.5 47.5 47.5 52.5 40.1 44.0 44.0 44.0 44.0 48.6 38.6
75 46.8 41.3 53.1 31.3 56.9 20.5 42.7 39.1 50.1 29.7 55.0 19.2 38.7 37.0 45.4 27.5 52.4 17.9 34.4 34.4 40.8 25.4 48.9 16.3
80 48.7 48.7 53.4 39.5 57.5 28.9 45.2 45.2 50.3 38.2 55.4 27.8 41.8 41.8 45.7 36.0 52.7 26.3 38.2 38.2 41.1 33.9 49.1 24.7
85 52.2 52.2 53.9 47.5 58.1 36.1 49.3 49.3 51.0 46.7 55.7 35.3 45.7 45.7 46.7 44.7 52.9 34.5 42.1 42.1 42.1 42.1 49.2 33.0
90 54.9 54.9 54.9 54.9 58.4 42.8 52.7 52.7 52.7 52.7 56.2 42.9 49.8 49.8 49.8 49.8 53.3 42.5 46.2 46.2 46.2 46.2 49.7 41.3
75 48.1 43.8 53.6 32.5 57.3 20.8 43.8 41.6 50.8 31.1 55.5 19.6 39.8 39.5 46.3 29.0 52.9 18.2 35.8 35.8 41.5 26.7 49.6 16.7
80 50.5 50.5 54.0 41.2 58.0 29.6 47.1 47.1 51.1 40.3 55.9 29.0 43.4 43.4 46.7 38.2 53.2 27.4 39.8 39.8 42.0 36.0 49.7 25.8
85 53.6 53.6 54.8 49.8 58.6 37.1 51.1 51.1 52.0 49.4 56.3 36.6 47.7 47.7 48.1 47.9 53.5 36.1 43.9 43.9 43.9 43.9 49.9 34.9
90 56.1 56.1 56.1 56.1 59.0 44.2 54.2 54.2 54.1 54.1 56.9 44.8 51.5 51.5 51.5 51.5 54.1 44.7 48.2 48.2 48.2 48.2 50.5 43.9
75 49.1 46.3 54.2 33.5 57.7 21.2 44.9 44.0 51.5 32.4 55.9 20.0 40.7 40.7 47.1 30.4 53.3 18.6 37.0 37.0 42.2 28.1 50.1 17.0
80 51.9 51.9 54.6 42.7 58.4 30.1 48.8 48.8 51.8 42.2 56.3 30.2 45.0 45.0 47.7 40.4 53.7 28.5 41.2 41.2 42.9 38.2 50.3 26.9
85 54.7 54.7 55.5 51.8 59.1 38.1 52.5 52.5 52.9 51.8 56.8 37.8 49.4 49.4 49.4 49.4 54.1 37.6 45.5 45.5 45.5 45.5 50.5 36.6
1440
1600
1760
1920
90
57.1 57.1 57.1 57.1 59.4 45.6 55.3 55.3 55.3 55.3 57.4 46.4 52.8 52.8 52.8 52.8 54.7 46.7 49.8 49.8 49.8 49.8 51.3 46.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (4, 5Ton)
Data
Standard Efficiency
Table PD-3 — Gross Cooling Capacities (MBH) 4 Ton Three Phase TSC048A3, A4, AW
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 44.8 38.6 51.4 29.8 56.1 20.1 41.0 36.6 48.2 28.2 53.7 18.9 37.3 34.7 44.2 26.4 50.8 17.6 33.4 32.7 39.6 25.2 47.1 16.0
80 46.0 46.0 51.6 37.4 56.5 27.9 42.9 42.9 48.3 35.8 54.0 26.6 39.7 39.7 44.4 34.0 51.0 25.2 36.4 36.4 40.0 32.0 47.2 23.6
85 49.6 49.6 52.0 44.8 56.7 34.8 46.8 46.8 48.9 43.6 54.2 34.0 43.6 43.6 45.1 41.8 51.2 32.7 40.3 40.3 41.0 39.8 47.4 31.1
90 52.5 52.5 52.9 52.2 57.2 41.6 50.2 50.2 50.1 50.1 54.6 41.1 47.2 47.2 47.2 47.2 51.5 40.1 43.9 43.9 43.9 43.9 47.7 38.6
75 46.1 41.1 52.1 31.1 56.7 20.5 42.1 39.0 49.1 29.6 54.4 19.3 38.3 37.1 45.1 27.8 51.5 18.0 34.3 34.3 40.6 25.7 47.9 16.5
80 48.1 48.1 52.4 39.3 57.2 29.0 44.9 44.9 49.2 37.9 54.7 27.7 41.5 41.5 45.4 36.2 51.7 26.3 38.1 38.1 41.0 34.2 48.0 24.8
1440
1600
1760
85
90 54.2 54.2 54.2 54.2 58.0 43.5 51.9 51.9 51.9 51.9 55.4 43.2 49.1 49.1 49.1 49.1 52.3 42.5 45.9 45.9 45.9 45.9 48.7 41.3
75 47.2 43.5 52.8 32.3 57.3 20.9 43.3 41.5 49.8 30.9 54.9 19.7 39.1 39.1 45.8 29.1 52.0 18.3 35.6 35.6 41.3 27.1 48.5 16.8
51.4 51.4 53.0 47.3 57.7 36.7 48.7 48.7 50.0 46.4 55.0 35.5 45.6 45.6 46.3 44.8 51.9 34.6 42.1 42.1 42.1 42.1 48.2 33.0
80 49.7 49.7 53.1 41.0 57.8 30.1 46.7 46.7 50.1 40.0 55.3 28.8 43.3 43.3 46.2 38.3 52.3 27.4 39.7 39.7 41.8 36.3 48.7 25.9
85 52.8 52.8 53.8 49.7 58.1 37.7 50.3 50.3 51.0 49.1 55.6 37.0 47.2 47.2 47.2 47.2 52.5 36.1 43.7 43.7 43.7 43.7 48.9 34.9
90 55.5 55.5 55.5 55.5 58.7 45.3 53.4 53.4 53.4 53.4 56.1 45.2 50.7 50.7 50.7 50.7 53.1 44.7 47.6 47.6 47.6 47.6 49.5 43.8
75 48.2 45.8 53.3 33.4 57.8 21.3 44.4 43.8 50.4 32.1 55.4 20.0 40.3 40.3 46.5 30.4 52.5 18.6 36.6 36.6 41.9 28.3 49.0 17.2
80 51.0 51.0 53.7 42.7 58.3 31.1 48.1 48.1 50.7 41.9 55.7 29.6 44.7 44.7 47.0 40.3 52.8 28.4 41.1 41.1 42.6 38.3 49.2 26.9
85 53.9 53.9 54.6 51.8 58.6 38.7 51.6 51.6 51.9 51.5 56.2 38.4 48.6 48.6 48.6 48.6 53.1 37.7 45.2 45.2 45.2 45.2 49.4 36.6
90 56.6 56.6 56.6 56.6 59.3 47.0 54.6 54.6 54.5 54.5 56.8 47.1 52.0 52.0 52.0 52.0 53.8 46.9 49.0 49.0 49.0 49.0 50.3 46.1
1920
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (MBH) 5 Ton Single/Three Phase TSC060A1, A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 57.4 49.1 64.8 37.9 69.2 25.3 53.3 47.0 61.8 36.3 67.2 24.1 49.4 45.0 57.6 34.3 64.3 22.8 45.2 42.9 52.4 32.7 60.6 21.2
80 59.0 59.0 65.1 47.1 69.8 35.0 55.6 55.6 62.0 45.7 67.6 33.8 52.2 52.2 57.8 43.9 64.6 32.3 48.6 48.6 52.8 41.6 60.8 30.6
85 63.1 63.1 65.7 56.2 70.2 42.9 60.3 60.3 62.7 55.3 68.0 42.3 56.8 56.8 58.9 53.6 64.9 41.3 52.9 52.9 54.0 51.4 61.0 39.9
90 66.4 66.4 66.9 65.2 70.8 51.0 64.1 64.1 64.1 64.1 68.5 50.8 61.1 61.1 61.1 61.1 65.4 50.1 57.5 57.5 57.5 57.5 61.5 49.0
75 59.0 52.2 65.7 39.4 69.8 25.7 54.9 50.1 62.8 37.9 67.8 24.6 50.7 48.0 58.9 36.1 64.9 23.2 46.5 45.9 53.5 33.8 61.3 21.6
80 61.3 61.3 66.0 49.2 70.2 35.6 58.1 58.1 63.1 48.2 68.1 34.8 54.4 54.4 59.2 46.6 65.3 33.7 50.6 50.6 54.0 44.3 61.5 32.0
85 65.1 65.1 66.8 59.1 70.9 44.2 62.5 62.5 64.0 58.5 68.7 43.8 59.3 59.3 60.4 57.3 65.7 43.1 55.2 55.2 55.8 55.2 61.8 41.9
90 68.1 68.1 68.0 68.0 71.6 52.9 65.9 65.9 65.9 65.9 69.4 52.9 63.1 63.1 63.1 63.1 66.3 52.5 59.7 59.7 59.7 59.7 62.4 51.7
75 60.3 55.2 66.3 40.6 70.2 26.1 56.3 53.1 63.6 39.5 68.2 25.0 52.0 51.0 59.9 37.8 65.4 23.6 47.7 47.7 54.5 35.4 61.8 22.0
80 63.1 63.1 66.8 51.2 70.8 37.9 60.2 60.2 64.0 50.5 68.7 35.6 56.5 56.5 60.3 49.1 65.8 34.6 52.4 52.4 55.2 46.9 62.1 33.3
85 66.5 66.5 67.7 61.6 71.5 45.4 64.2 64.2 65.0 61.3 69.4 45.2 61.2 61.2 61.7 60.5 66.4 44.7 57.3 57.3 57.3 57.3 62.5 43.8
90 69.4 69.4 69.3 69.3 72.2 54.6 67.3 67.3 67.3 67.3 70.1 54.9 64.6 64.6 64.6 64.6 67.1 54.8 61.2 61.2 61.2 61.2 63.2 54.2
75 61.5 58.0 66.9 41.8 70.6 26.5 57.6 56.0 64.2 40.8 68.6 25.4 53.0 53.0 60.6 39.3 65.9 24.0 49.1 49.1 55.4 37.1 62.2 22.4
80 64.5 64.5 67.5 53.0 71.2 38.8 61.8 61.8 64.7 52.5 69.1 36.4 58.3 58.3 61.1 51.4 66.3 35.5 53.9 53.9 56.3 49.5 62.5 34.3
1800
2000
2200
2400
85
67.7 67.7 68.5 63.9 72.0 46.5 65.4 65.4 65.9 63.9 69.9 46.5 62.5 62.5 62.5 62.5 66.9 46.2 58.9 58.9 58.9 58.9 63.0 45.5
90 70.4 70.4 70.4 70.4 72.8 56.1 68.4 68.4 68.4 68.4 70.6 56.6 65.8 65.8 65.8 65.8 67.7 56.8 62.4 62.4 62.4 62.4 63.9 56.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
20
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6, 7½Ton)
Standard Efficiency
Table PD-5 — Gross Cooling Capacities (MBH) 6 Ton Three Phase
TSC072A3, A4, AW, AK
AmbientTemperature (F)
95
85
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27.3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47.7 60.9 36.4 70.3 24.6
80
67.6 66.2 73.7 52.2 77.5 38.9 63.2 63.2 70.9 51.1 76.0 37.8 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9
2160
2400
2640
85 71.4 71.4 74.2 61.9 78.6 47.4 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 67.3 59.7 74.0 46.0 60.4 60.4 62.2 57.3 70.8 45.0
90 74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 77.2 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8
75
80 69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 37.9 57.8 57.8 62.6 49.6 71.3 36.3
85 73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 77.2 47.9 67.4 67.4 69.1 63.6 74.8 47.6 63.2 63.2 64.2 61.4 71.7 47.0
90 76.2 76.2 76.5 74.3 79.9 57.1 74.3 74.3 74.3 74.3 77.9 57.4 71.7 71.7 71.7 71.7 75.5 57.7 68.5 68.5 68.4 68.4 72.2 57.5
75 69.1 61.4 74.7 44.9 77.4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4
80 71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77.0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 37.7
85 74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 67.3 77.8 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7
67.7 58.3 74.0 43.8 77.1 28.7 62.9 55.9 71.7 42.6 75.9 27.7 57.9 53.4 67.9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0
90
77.4 77.4 77.5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8
75 70.2 64.1 75.2 45.8 77.6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 27.3 56.2 56.2 64.7 41.9 71.7 25.8
80 72.9 72.9 75.9 57.4 78.7 40.4 70.3 70.3 73.6 57.8 77.3 41.8 66.5 66.5 70.1 57.1 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5
85 75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67.8 67.8 67.7 67.7 72.9 50.1
90 78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9
2880
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-6 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase Single Compressor
TSC090A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 87.4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8
80 89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77.6 77.6 87.2 65.3 97.4 48.2 71.6 71.6 78.9 61.5 92.9 46.0
85 94.2 94.2 97.5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97.8 61.4 78.5 78.5 80.7 76.2 93.2 59.9
90 98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5
75 89.7 78.4 96.7 57.3 99.1 37.2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97.5 34.5 68.7 67.7 80.3 50.1 93.8 32.5
80 92.2 92.2 97.5 70.9 100.3 50.4 87.4 87.4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1
85 96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1
90 99.5 99.5 99.9 97.0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77.4 90.1 90.1 90.0 90.0 95.3 77.7
75 91.5 82.5 97.7 59.0 99.3 37.7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2
80 94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1
85 98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 97.5 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8
90 100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97.2 97.2 97.2 97.2 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4
75 92.9 86.2 98.1 59.9 99.4 38.2 87.3 84.1 96.3 60.6 99.8 37.2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8
80 96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 97.1 77.5 101.0 55.7 87.6 87.6 92.5 77.2 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6
85 99.0 99.0 99.7 88.7 101.8 62.7 97.8 97.8 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 67.3 89.1 89.1 89.1 89.1 96.3 68.3
90 101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97.5 84.6
2700
3000
3300
3600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½, 8½Ton)
Standard Efficiency
Table PD-7 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase Dual Compressors TSC092A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 84.6 72.9 93.9 55.3 98.4 36.4 78.2 69.6 90.1 53.3 96.9 35.1 71.8 66.3 83.9 50.4 94.0 33.3 65.3 63.1 76.5 47.1 89.4 31.2
80 86.8 86.8 94.4 68.5 99.6 50.0 81.8 81.8 90.5 67.5 98.0 49.7 76.4 76.4 84.3 64.7 94.5 47.5 70.9 70.9 77.1 61.4 89.6 45.3
85 92.2 92.2 95.4 81.7 100.8 61.3 88.4 88.4 91.5 81.5 99.0 62.4 83.2 83.2 85.8 79.3 94.9 60.9 77.6 77.6 79.0 76.1 89.9 59.3
90 96.3 96.3 96.9 94.4 102.0 72.8 93.6 93.6 93.6 93.6 99.3 73.4 89.6 89.6 89.6 89.6 95.8 74.0 84.5 84.5 84.5 84.5 90.6 73.0
75 86.8 77.5 94.7 57.0 98.9 37.1 80.5 74.4 91.5 55.8 97.6 35.7 74.0 71.1 85.6 53.1 94.8 34.0 67.1 67.1 78.2 49.8 90.5 31.9
80 90.1 90.1 95.6 71.2 100.2 50.8 85.4 85.4 92.0 71.1 98.7 50.7 79.9 79.9 86.3 68.9 95.5 49.6 74.1 74.1 79.1 65.7 90.8 47.4
85 94.7 94.7 96.8 85.3 101.4 62.7 91.5 91.5 93.3 86.2 99.7 63.7 86.9 86.9 88.2 84.9 96.1 63.5 81.3 81.3 81.2 81.2 91.2 62.6
90 98.3 98.3 98.3 98.3 102.7 74.8 96.2 96.2 96.1 96.1 100.3 76.2 92.7 92.7 92.7 92.7 97.1 77.5 88.0 88.0 88.0 88.0 92.2 77.4
75 88.7 81.9 95.7 58.9 99.3 37.6 82.6 79.0 92.5 58.2 98.1 36.2 75.5 75.5 87.1 55.7 95.4 34.6 69.6 69.6 79.6 52.4 91.3 32.5
80 92.3 92.3 96.5 73.7 100.7 51.5 88.4 88.4 93.2 74.4 99.3 51.7 82.9 82.9 87.9 72.8 96.1 51.0 76.9 76.9 80.8 69.8 91.7 49.5
85 96.5 96.5 97.8 88.4 102.0 63.9 93.8 93.8 94.8 90.3 100.0 65.0 89.8 89.8 89.8 89.8 96.9 65.8 84.4 84.4 84.4 84.4 92.3 65.5
90 99.7 99.7 99.7 99.7 103.3 76.5 98.0 98.0 98.0 98.0 101.1 78.5 94.9 94.9 94.9 94.9 98.1 80.6 90.7 90.7 90.7 90.7 93.5 81.3
75 90.2 85.7 96.4 60.6 99.7 38.1 84.6 83.6 93.3 60.0 98.5 36.8 77.9 77.9 88.2 58.1 96.0 35.2 71.8 71.8 80.9 55.0 92.0 33.2
80 94.0 94.0 97.2 75.8 101.0 52.1 90.7 90.7 94.3 77.4 99.7 52.6 85.6 85.6 89.2 76.6 96.6 52.0 79.5 79.5 82.3 73.8 92.5 51.5
2700
3000
3300
3600
85
97.8 97.8 98.7 91.1 102.4 65.0 95.6 95.6 96.1 93.9 100.5 66.3 91.9 91.9 91.9 91.9 97.6 67.9 86.9 86.9 86.9 86.9 93.1 68.2
90 100.8 100.8 100.8 100.8 103.7 78.1 99.3 99.3 99.3 99.3 101.7 80.7 96.6 96.6 96.6 96.6 98.9 83.4 92.7 92.7 92.7 92.7 94.6 84.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-8 — Gross Cooling Capacities (MBH) 8½ Ton Three Phase TSC102A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 96.3 82.3 106.6 62.7 112.5 41.5 89.0 78.5 103.2 60.6 110.9 40.0 81.8 74.9 96.6 57.5 107.6 38.1 74.9 71.3 87.6 55.2 102.5 35.8
80 98.0 98.0 107.2 77.1 113.7 57.0 92.9 91.4 103.4 76.3 111.5 57.1 86.3 86.2 96.9 73.3 108.2 54.0 80.2 80.2 88.1 69.4 102.8 51.5
85 103.9 103.9 108.1 91.7 114.8 69.6 100.1 100.1 104.3 91.7 112.4 70.0 94.3 94.3 98.3 89.5 108.6 68.9 87.6 87.6 89.9 85.7 103.1 67.1
90 108.6 108.6 109.6 105.7 116.0 82.4 105.9 105.9 105.9 105.9 113.2 83.0 101.6 101.6 101.9 100.2 109.3 83.4 95.6 95.6 95.6 95.5 103.6 82.3
3060
3400
3740
75 98.7 87.2 107.8 65.9 113.0 42.0 91.8 83.8 104.7 63.7 111.8 40.7 84.2 80.0 98.7 60.5 108.6 38.9 76.3 76.3 89.6 58.6 103.7 36.5
80 101.6 100.0 108.5 80.1 114.6 58.1 96.9 96.5 105.0 80.1 112.8 57.8 90.3 90.3 99.1 77.9 109.3 56.3 83.8 83.8 90.3 74.0 104.0 53.8
85 106.8 106.8 109.6 95.7 115.8 71.4 103.6 103.6 106.2 96.7 114.0 70.7 98.7 98.7 100.9 95.5 109.8 71.7 91.7 91.7 91.7 91.7 104.3 70.7
90 111.0 111.0 111.0 111.0 117.0 84.9 108.8 108.8 108.9 107.2 114.4 86.1 105.1 105.1 105.0 104.8 110.7 87.4 99.8 99.8 99.7 99.7 105.2 87.1
75 100.7 91.7 109.2 64.5 114.0 42.8 93.8 88.7 106.1 66.5 113.5 41.7 85.4 85.4 100.4 63.3 109.4 39.6 79.4 77.5 91.3 59.4 104.6 37.2
80 104.1 103.6 109.6 82.9 115.3 59.0 100.0 100.0 106.6 84.3 113.7 59.0 94.0 94.0 100.9 82.2 109.6 60.2 87.0 87.0 92.2 78.5 105.1 56.0
85 108.9 108.9 110.9 99.2 116.6 73.0 106.7 106.7 108.3 102.4 114.8 74.4 102.0 102.0 102.0 102.0 110.8 74.3 95.6 95.6 96.4 93.7 105.5 73.9
90 112.8 112.8 112.8 112.8 117.8 87.2 111.8 111.8 111.8 111.2 116.0 90.0 107.7 107.7 107.7 107.7 111.9 90.9 102.9 102.9 102.9 102.9 106.6 91.4
75 102.3 95.8 110.2 66.1 114.6 43.5 95.2 95.2 106.7 68.3 113.1 42.2 88.2 88.2 101.6 65.9 110.1 40.3 81.6 80.6 92.7 62.1 105.3 38.1
80 106.2 106.2 110.5 85.3 115.9 59.8 102.8 102.8 107.4 86.8 114.3 60.0 97.4 97.4 102.4 86.2 111.0 58.6 89.9 89.9 94.1 82.9 105.9 58.2
85 110.5 110.5 111.9 102.3 117.2 74.4 108.3 108.3 109.2 105.1 115.5 76.3 104.5 104.5 104.4 104.4 111.5 77.2 98.7 98.7 99.0 97.4 106.4 76.8
90 114.2 114.2 114.2 114.2 118.5 89.3 112.7 112.7 112.7 112.7 116.8 92.7 109.7 109.7 109.7 109.7 112.9 94.2 105.2 105.2 105.2 105.2 107.8 95.4
4080
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
22
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
Standard Efficiency
Table PD-9 — Gross Cooling Capacities (MBH) 10 Ton Three Phase TSC120A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 108.6 95.7 120.5 71.5 126.0 46.0 100.1 91.3 115.5 68.8 123.6 43.3 91.0 86.5 107.2 64.9 119.3 41.0 82.2 82.0 96.5 60.1 113.1 37.9
80 112.8 112.8 121.2 89.2 127.5 65.7 106.3 106.3 116.1 88.1 124.8 62.8 98.5 98.5 108.2 84.5 120.1 60.5 90.5 90.5 97.8 79.7 113.6 57.4
85 119.5 119.5 122.6 106.9 129.0 78.5 114.8 114.8 117.7 107.0 126.2 79.2 108.2 108.2 110.5 104.5 121.8 76.8 100.1 100.1 100.1 100.1 114.2 76.6
90 124.3 124.3 124.6 123.6 130.4 93.6 121.0 121.0 121.0 121.0 127.6 95.7 116.0 116.0 116.0 116.0 122.0 95.1 109.4 109.4 109.4 109.4 115.3 94.5
3600
4000
4400
75 111.6 102.3 121.7 73.9 126.7 46.9 103.4 98.1 117.1 72.3 124.5 42.7 94.2 93.4 109.5 68.7 120.2 41.9 85.3 85.3 98.8 64.0 114.3 38.8
80 116.7 116.7 122.6 92.7 128.2 64.5 111.1 111.1 118.0 93.0 125.7 64.2 103.4 103.4 110.8 90.4 121.4 63.2 95.0 95.0 100.6 85.8 114.9 60.3
85 122.3 122.3 124.2 111.4 129.7 80.2 118.5 118.5 120.0 113.1 127.1 81.6 112.8 112.8 113.6 112.1 122.6 82.1 105.1 105.1 105.1 105.1 115.6 80.4
90 126.9 126.9 126.4 126.4 131.3 96.0 123.7 123.7 123.7 123.7 128.7 99.0 119.3 119.3 119.3 119.3 124.1 100.7 113.4 113.4 113.4 113.4 117.1 100.0
75 114.1 108.4 122.5 75.8 127.3 47.7 106.5 104.9 118.4 75.8 124.9 45.4 97.1 97.1 111.3 72.3 121.3 40.2 88.6 88.6 100.9 67.7 115.1 39.7
80 119.5 119.5 123.8 96.1 128.9 65.5 114.7 114.7 119.5 97.3 126.3 69.2 107.7 107.7 112.9 95.9 122.2 64.9 99.0 99.0 103.1 91.7 115.8 63.2
85 124.9 124.9 125.5 115.5 130.4 81.9 121.1 121.1 121.8 118.3 127.9 83.7 116.0 116.0 116.0 116.0 123.6 85.0 109.2 109.2 109.2 109.2 116.8 84.0
90 127.9 127.9 128.0 128.0 132.0 98.3 126.1 126.1 125.6 125.6 129.5 101.8 121.7 121.7 121.7 121.7 125.3 104.7 116.2 116.2 116.2 116.2 118.5 104.7
75 116.1 113.8 123.1 77.6 127.8 48.5 108.9 108.9 119.2 78.1 125.4 46.2 100.5 100.5 112.8 76.1 121.4 43.6 91.6 91.6 102.6 71.3 115.8 40.6
80 121.4 121.4 124.5 98.6 129.4 66.4 117.3 117.3 120.8 101.1 126.9 66.5 111.1 111.1 114.6 100.9 122.9 66.4 102.5 102.5 105.4 97.5 116.5 65.7
85 126.0 126.0 126.4 118.6 130.9 83.4 122.9 122.9 123.2 122.6 128.5 85.6 118.4 118.4 118.4 118.4 124.3 87.5 112.1 112.1 112.1 112.1 117.8 87.3
90 129.1 129.1 129.1 129.1 132.5 100.4 127.2 127.2 126.9 126.9 130.2 104.4 124.0 124.0 123.7 123.7 126.2 108.0 118.2 118.2 118.2 118.2 119.7 108.9
4800
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3Ton)
High Efficiency
Table PD-10 — Gross Cooling Capacities (MBH) 3 Ton THC036A1, A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.2 29.2 39.8 22.7 43.1 15.2 31.1 27.4 37.0 21.2 41.3 14.1 28.0 25.7 33.3 19.8 39.0 12.9 24.8 24.0 29.8 18.1 36.1 11.6
80 34.9 34.9 40.0 28.5 43.5 21.3 32.3 32.3 37.1 27.1 41.6 20.1 29.7 29.7 33.5 25.3 39.2 18.8 27.1 27.1 30.0 23.6 36.2 17.5
1080
1200
1320
85
37.9 37.9 40.3 34.3 44.0 26.5 35.3 35.3 37.5 33.0 41.9 25.6 32.6 32.6 34.0 31.3 39.5 24.6 30.0 30.0 30.6 29.6 36.4 23.2
90 40.5 40.5 40.9 40.0 44.5 31.7 38.4 38.4 38.4 38.4 42.3 31.0 35.7 35.7 35.7 35.7 39.7 30.3 32.9 32.9 32.9 32.9 36.7 29.0
75 35.3 31.2 40.4 23.7 43.5 15.5 32.0 29.4 37.8 22.4 41.8 14.4 28.8 27.7 34.1 20.6 39.5 13.2 25.5 25.5 30.5 18.8 36.7 11.9
80 36.7 36.7 40.7 30.0 44.0 21.9 33.9 33.9 38.0 28.9 42.1 20.9 31.2 31.2 34.4 27.1 39.8 19.7 28.5 28.5 30.8 25.3 36.9 18.4
85 39.6 39.6 41.1 36.3 44.6 27.4 37.1 37.1 38.5 35.4 42.5 26.8 34.3 34.3 35.1 33.8 40.0 26.0 31.5 31.5 31.5 31.5 37.1 24.8
90 41.9 41.9 41.9 41.9 45.1 33.0 39.9 39.9 39.9 39.9 42.9 32.6 37.6 37.6 37.6 37.6 40.4 32.1 34.7 34.7 34.7 34.7 37.4 31.1
75 36.2 33.2 40.9 24.7 43.8 15.8 32.8 31.4 38.4 23.4 42.1 14.7 29.4 29.4 34.8 21.7 39.9 13.5 26.5 26.5 31.0 19.9 37.2 12.2
80 38.2 38.2 41.2 31.4 44.4 22.4 35.4 35.4 38.7 30.5 42.6 21.7 32.5 32.5 35.2 28.9 40.2 20.5 29.7 29.7 31.5 27.1 37.4 19.2
85 40.8 40.8 41.8 38.1 45.0 28.3 38.7 38.7 39.4 37.6 43.1 28.0 35.9 35.9 36.2 36.2 40.5 27.2 32.9 32.9 32.9 32.9 37.6 26.2
90 42.9 42.9 42.9 42.9 45.6 34.2 41.1 41.1 41.1 41.1 43.4 34.0 38.9 38.9 38.9 38.9 41.0 33.8 36.3 36.3 36.3 36.3 38.1 33.1
75
37.1 35.1 41.3 25.5 44.1 16.1 33.6 33.3 38.9 24.4 42.4 15.0 30.4 30.4 35.5 22.8 40.2 13.8 27.5 27.5 31.5 21.0 37.5 12.5
80 39.4 39.4 41.7 32.6 44.7 22.9 36.8 36.8 39.3 32.1 42.9 22.3 33.8 33.8 35.9 30.6 40.6 21.4 30.8 30.8 32.1 28.8 37.8 20.1
85 41.7 41.7 42.4 39.7 45.3 29.0 39.8 39.8 40.1 39.5 43.5 29.0 37.3 37.3 37.3 37.3 40.9 28.3 34.2 34.2 34.2 34.2 38.0 27.6
90 43.7 43.7 43.7 43.7 45.9 35.3 42.1 42.1 42.1 42.1 43.9 35.3 40.0 40.0 40.0 40.0 41.5 35.4 37.5 37.5 37.5 37.5 38.6 34.9
1440
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
24
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3Ton)
High Efficiency
Table PD-11 — Gross Cooling Capacities (MBH) 3 Ton THC036A1, A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 30.8 21.6 34.9 17.8 39.2 13.7 28.9 20.4 32.8 16.6 37.0 12.5 26.9 19.1 30.6 15.3 34.7 11.3 24.8 17.8 28.4 14.1 32.3 10.0
80 30.9 25.0 35.0 21.2 39.3 17.2 29.0 23.8 32.9 19.9 37.1 16.0 26.9 22.5 30.8 18.7 34.8 14.8 24.9 21.1 28.6 17.4 32.4 13.5
85 31.0 28.4 35.1 24.6 39.5 20.6 29.0 27.1 33.1 23.3 37.3 19.3 27.0 25.8 30.9 22.0 35.0 18.1 25.0 24.5 28.7 20.7 32.6 16.8
90 31.2 31.2 35.2 27.9 39.6 23.9 29.6 29.6 33.1 26.6 37.4 22.7 28.0 28.0 31.0 25.4 35.1 21.4 26.3 26.3 28.8 24.0 32.7 20.1
600*
780*
960
75 33.1 24.8 37.3 19.7 41.8 14.5 30.9 23.5 35.0 18.5 39.3 13.2 28.8 22.2 32.6 17.1 36.7 12.0 26.5 20.8 30.2 15.8 34.1 10.7
80 33.2 29.2 37.4 24.1 41.9 18.9 31.1 27.9 35.1 22.8 39.5 17.6 29.0 26.6 32.8 21.5 36.9 16.3 26.7 25.2 30.4 20.1 34.3 15.0
85 33.4 33.4 37.5 28.4 42.1 23.2 31.6 31.6 35.3 27.1 39.6 21.9 29.8 29.8 32.9 25.8 37.0 20.6 27.9 27.9 30.5 24.4 34.4 19.3
90 35.4 35.4 37.7 32.7 42.2 27.5 33.6 33.6 35.5 31.4 39.8 26.2 31.8 31.8 33.1 30.1 37.2 24.9 29.8 29.8 30.8 28.7 34.6 23.6
75 34.6 27.8 38.9 21.5 43.4 15.1 32.4 26.5 36.5 20.2 40.9 13.8 30.1 25.1 34.0 18.9 38.1 12.6 27.7 23.7 31.4 17.5 35.3 11.2
80 35.0 33.2 39.0 26.8 43.5 20.4 32.8 31.9 36.6 25.5 41.0 19.2 30.6 30.5 34.1 24.1 38.3 17.8 28.3 28.3 31.6 22.7 35.5 16.5
85 36.4 36.4 39.2 32.0 43.7 25.6 34.5 34.5 36.8 30.7 41.2 24.4 32.5 32.5 34.4 29.4 38.5 23.0 30.4 30.4 31.9 28.0 35.7 21.7
90 38.6 38.6 39.6 37.3 43.9 30.8 36.7 36.7 37.3 36.0 41.4 29.5 34.6 34.6 34.9 34.7 38.6 28.2 32.5 32.5 32.5 32.5 35.9 26.8
75 35.5 29.7 39.7 22.9 44.1 15.4 33.2 28.4 37.2 21.6 41.6 14.2 30.8 27.0 34.6 20.3 38.8 12.9 28.4 25.6 32.0 18.9 35.9 11.6
80 36.0 35.8 39.9 28.5 44.3 21.3 33.8 33.8 37.4 27.2 41.7 20.1 31.7 31.7 34.8 25.8 39.0 18.8 29.6 29.6 32.2 24.4 36.1 17.4
85 38.1 38.1 40.1 34.4 44.5 27.2 36.0 36.0 37.7 33.1 41.9 25.9 33.9 33.9 35.2 31.7 39.2 24.6 31.8 31.8 32.6 30.3 36.3 23.2
90 40.4 40.4 40.8 40.4 44.7 33.0 38.3 38.3 38.3 38.3 42.1 31.7 36.2 36.2 36.2 36.2 39.4 30.4 34.0 34.0 33.9 33.9 36.5 29.0
1080
1200
75 36.2 31.6 40.4 23.7 44.8 15.7 33.8 30.2 37.8 22.4 42.2 14.5 31.4 28.8 35.2 21.0 39.4 13.2 29.0 27.4 32.5 19.6 36.4 11.9
80
37.1 37.1 40.6 30.2 45.0 22.3 35.0 35.0 38.0 28.8 42.3 21.0 32.9 32.9 35.4 27.5 39.6 19.7 30.7 30.7 32.7 26.1 36.6 18.3
85 39.5 39.5 41.0 36.7 45.1 28.7 37.4 37.4 38.4 35.4 42.5 27.4 35.2 35.2 35.9 34.0 39.8 26.1 33.0 33.0 33.3 32.7 36.8 24.7
90 42.0 42.0 42.0 42.0 45.4 35.1 39.8 39.8 39.8 39.8 42.8 33.8 37.5 37.5 37.5 37.5 40.1 32.5 35.2 35.2 35.2 35.2 37.1 31.1
75 36.8 33.4 40.9 24.8 45.3 16.1 34.4 32.1 38.3 23.4 42.6 14.8 32.0 30.7 35.6 22.0 39.9 13.5 29.6 29.3 32.9 20.6 36.9 12.2
80 38.3 38.3 41.2 31.9 45.5 23.1 36.1 36.1 38.6 30.5 42.8 21.9 33.9 33.9 35.9 29.1 40.0 20.6 31.7 31.7 33.2 27.7 37.1 19.2
85 40.8 40.8 41.7 39.0 45.7 30.2 38.6 38.6 39.2 37.7 43.0 28.9 36.3 36.3 36.6 36.3 40.2 27.5 34.0 34.0 34.0 34.0 37.3 26.2
90 43.3 43.3 43.3 43.3 46.0 37.1 41.1 41.1 41.1 41.1 43.3 35.9 38.8 38.8 38.8 38.8 40.6 34.6 36.3 36.3 36.3 36.3 37.7 33.2
1320
75
37.4 35.2 41.4 25.8 45.8 16.4 35.0 33.9 38.7 24.4 43.0 15.1 32.6 32.5 36.0 23.0 40.2 13.8 30.1 30.1 33.2 21.6 37.2 12.5
80 39.3 39.3 41.7 33.5 46.0 24.0 37.1 37.1 39.1 32.1 43.2 22.7 34.8 34.8 36.4 30.7 40.4 21.4 32.5 32.5 33.6 29.3 37.4 20.0
85 41.9 41.9 42.4 41.3 46.1 31.6 39.7 39.7 39.6 39.6 43.4 30.3 37.3 37.3 37.3 37.3 40.6 29.0 34.9 34.9 34.9 34.9 37.7 27.6
90 44.4 44.4 44.4 44.4 46.5 39.2 42.2 42.2 42.2 42.2 43.8 37.9 39.8 39.8 39.8 39.8 41.1 36.6 37.3 37.3 37.3 37.3 38.2 35.3
1440
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unitapplicationsbelow960CFM
•
•
Electricheatersrestrictedonapplicationsbelow960CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 960 CFM.
RT-PRC005-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(4Ton)
High Efficiency
Table PD-12 — Gross Cooling Capacities (MBH) 4 Ton THC048A1, A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.3 39.9 51.4 30.3 54.9 19.9 41.1 37.7 48.4 28.8 53.1 18.7 37.1 35.6 43.9 26.7 51.0 17.4 33.2 33.2 39.3 24.6 47.8 16.0
80
47.1 47.1 52.0 38.4 55.5 28.1 43.8 43.8 48.7 36.9 54.6 27.2 40.3 40.3 44.3 34.9 51.3 25.6 36.9 36.9 39.8 32.8 47.9 24.1
1440
1600
1760
85 50.5 50.5 52.5 46.3 56.2 34.5 47.8 47.8 49.4 45.2 54.9 34.9 44.3 44.3 45.3 43.3 51.6 33.6 40.9 40.9 40.9 40.9 48.1 32.2
90 53.1 53.1 53.5 53.5 56.9 41.4 51.2 51.2 51.2 51.2 54.6 41.4 48.4 48.4 48.4 48.4 52.0 41.2 45.0 45.0 45.0 45.0 48.6 40.2
75 46.7 42.7 52.7 31.9 55.2 20.2 42.4 40.5 49.4 30.3 54.4 19.3 38.2 38.2 45.0 28.4 51.6 17.8 34.7 34.7 40.2 26.2 48.6 16.4
80 49.2 49.2 52.8 40.4 55.9 28.2 46.0 46.0 49.8 39.4 55.2 28.4 42.3 42.3 45.6 37.5 51.9 26.9 38.7 38.7 40.9 35.3 48.7 25.4
85 52.1 52.1 53.5 48.8 56.6 35.4 49.9 49.9 50.6 48.3 55.7 36.8 46.7 46.7 47.0 46.8 52.2 35.2 43.0 43.0 42.9 42.9 49.0 34.3
90 54.5 54.5 54.8 54.8 57.4 42.7 52.8 52.8 52.8 52.8 55.2 42.9 50.5 50.5 50.5 50.5 52.9 43.5 47.4 47.4 47.4 47.4 49.6 43.0
75
47.8 45.4 53.2 33.4 55.5 20.6 43.7 43.3 50.1 31.8 54.7 19.6 39.7 39.7 46.0 30.0 51.9 18.2 36.1 36.1 41.0 27.7 49.1 16.8
80 50.6 50.6 53.4 42.1 56.2 28.7 47.8 47.8 50.5 41.5 55.7 29.4 44.1 44.1 46.7 39.9 52.4 28.1 40.4 40.4 41.9 37.8 49.3 26.7
85 53.1 53.1 54.2 50.9 57.0 36.2 51.4 51.4 51.6 51.0 56.2 38.0 48.6 48.6 48.6 48.6 52.8 36.7 44.9 44.9 44.9 44.9 49.7 36.3
90 55.1 55.1 55.7 55.7 57.7 43.8 53.9 53.9 53.9 53.9 55.6 44.3 51.9 51.9 51.9 51.9 53.5 45.6 49.2 49.2 49.2 49.2 50.5 45.7
75 48.8 48.1 53.6 34.4 55.7 20.9 45.0 45.0 50.6 33.2 55.0 20.0 41.0 41.0 46.8 31.5 52.3 18.5 37.3 37.3 41.7 29.3 49.6 17.2
80 51.7 51.7 53.9 43.5 56.4 31.7 49.3 49.3 51.2 43.5 56.0 30.1 45.8 45.8 47.6 42.3 52.8 28.9 41.8 41.8 42.8 40.2 49.8 27.9
85 53.9 53.9 54.8 52.7 57.2 36.9 52.4 52.4 52.4 52.4 56.5 39.1 50.0 50.0 50.0 50.0 53.2 38.1 46.6 46.6 46.6 46.6 50.3 38.1
90 55.7 55.7 56.3 56.3 58.0 44.8 54.7 54.7 54.7 54.7 56.0 45.6 53.0 53.0 53.0 53.0 54.0 47.4 50.5 50.5 50.5 50.5 51.2 48.1
1920
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
26
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(4Ton)
High Efficiency
Table PD-13 — Gross Cooling Capacities (MBH) 4 Ton THC048A1, A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 40.4 29.1 45.7 23.7 51.3 18.2 38.2 27.7 43.3 22.4 48.8 16.9 35.8 26.3 40.6 20.9 45.9 15.4 33.3 24.8 38.0 19.5 43.1 14.0
80 40.5 33.8 45.8 28.4 51.5 22.8 38.3 32.4 43.4 27.0 48.9 21.5 35.9 31.0 40.8 25.5 46.0 20.0 33.4 29.5 38.1 24.1 43.2 18.6
85 40.8 38.5 45.9 33.1 51.6 27.5 38.5 37.1 43.5 31.7 49.0 26.1 36.2 35.7 40.8 30.2 46.1 24.6 33.9 33.9 38.2 28.7 43.3 23.2
90 42.0 42.0 46.1 37.7 51.7 32.1 40.1 40.1 43.7 36.3 49.1 30.7 38.1 38.1 41.0 34.8 46.2 29.2 36.1 36.1 38.4 33.3 43.4 27.8
800*
1040*
1280
75 43.3 33.5 48.8 26.4 54.6 19.2 40.8 32.1 46.2 25.0 51.8 17.8 38.2 30.6 43.2 23.5 48.6 16.3 35.5 29.1 40.4 22.0 45.5 14.9
80 43.6 39.6 48.9 32.4 54.7 25.1 41.1 38.2 46.3 31.0 51.9 23.8 38.6 36.7 43.3 29.5 48.7 22.3 36.0 35.2 40.5 28.0 45.7 20.8
85 44.7 44.7 49.1 38.4 54.9 31.1 42.6 42.6 46.5 37.0 52.1 29.7 40.4 40.4 43.6 35.4 48.8 28.2 38.2 38.2 40.7 33.9 45.8 26.7
90
47.3 47.3 49.4 44.4 55.0 37.0 45.2 45.2 46.8 42.9 52.2 35.6 43.0 43.0 44.0 41.4 49.0 34.0 40.7 40.7 41.2 39.9 46.0 32.6
75 45.3 37.7 50.8 28.9 56.7 20.0 42.7 36.2 48.0 27.5 53.8 18.6 40.0 34.7 44.9 25.9 50.3 17.0 37.2 33.1 41.9 24.4 47.1 15.6
80 46.0 45.1 51.0 36.2 56.9 27.3 43.4 43.4 48.2 34.7 53.9 25.9 41.1 41.1 45.1 33.1 50.5 24.3 38.7 38.7 42.1 31.6 47.3 22.9
85 48.5 48.5 51.3 43.5 57.0 34.5 46.2 46.2 48.6 42.0 54.1 33.1 43.9 43.9 45.5 40.4 50.6 31.5 41.4 41.4 42.6 38.9 47.5 30.0
90 51.4 51.4 52.1 50.8 57.3 41.7 49.1 49.1 49.5 49.4 54.3 40.3 46.7 46.7 46.7 46.7 50.9 38.7 44.2 44.2 44.2 44.2 47.7 37.2
75 46.3 40.3 51.5 30.3 57.4 20.3 43.7 38.8 48.7 28.9 54.3 18.9 41.0 37.3 45.7 27.4 51.2 17.5 38.1 35.8 42.7 25.9 47.9 16.0
80
47.6 47.6 51.8 38.5 57.6 28.5 45.2 45.2 49.0 37.0 54.5 27.1 42.8 42.8 46.0 35.5 51.3 25.6 40.3 40.3 43.0 34.0 48.1 24.2
1440
1600
85 50.6 50.6 52.3 46.6 57.7 36.5 48.2 48.2 49.5 45.2 54.7 35.1 45.7 45.7 46.6 43.7 51.5 33.7 43.2 43.2 43.7 42.2 48.3 32.2
90 53.6 53.6 53.6 53.6 58.1 44.6 51.2 51.2 51.2 51.2 55.0 43.2 48.7 48.7 48.7 48.7 51.9 41.7 46.1 46.1 46.1 46.1 48.7 40.2
75
47.3 42.9 52.4 31.8 58.2 20.7 44.6 41.4 49.4 30.4 55.1 19.3 41.8 39.9 46.4 28.9 51.9 17.9 39.0 38.4 43.3 27.4 48.6 16.4
80 49.2 49.2 52.7 40.9 58.4 29.8 46.8 46.8 49.8 39.4 55.3 28.4 44.3 44.3 46.8 37.9 52.0 26.9 41.7 41.7 43.7 36.4 48.7 25.4
85 52.4 52.4 53.4 49.9 58.6 38.7 49.9 49.9 50.6 48.5 55.5 37.3 47.4 47.4 47.7 47.0 52.3 35.8 44.7 44.7 44.7 44.7 49.0 34.3
90 55.6 55.6 55.6 55.6 59.1 47.6 53.1 53.1 53.1 53.1 56.0 46.2 50.4 50.4 50.4 50.4 52.8 44.7 47.7 47.7 47.7 47.7 49.5 43.2
75 48.2 45.5 53.0 33.3 59.0 21.2 45.5 44.0 50.1 31.8 55.8 19.8 42.7 42.5 47.0 30.3 52.5 18.3 39.9 39.9 43.8 28.8 49.1 16.8
80 50.7 50.7 53.5 43.2 59.1 31.1 48.2 48.2 50.5 41.7 55.9 29.6 45.6 45.6 47.5 40.2 52.6 28.2 42.9 42.9 44.4 38.7 49.3 26.7
85 54.0 54.0 54.4 53.1 59.4 40.8 51.4 51.4 51.4 51.4 56.2 39.4 48.8 48.8 48.8 48.8 52.9 37.9 46.0 46.0 46.0 46.0 49.6 36.4
1760
90
57.3 57.3 57.3 57.3 59.9 50.5 54.7 54.7 54.7 54.7 56.8 49.1 52.0 52.0 52.0 52.0 53.6 47.6 49.2 49.2 49.2 49.2 50.3 46.1
75 49.0 48.1 53.6 34.7 59.6 21.6 46.1 46.1 50.6 33.3 56.3 20.2 43.6 43.6 47.5 31.8 53.0 18.7 40.9 40.9 44.3 30.2 49.5 17.2
80 52.0 52.0 54.2 45.4 59.7 32.3 49.4 49.4 51.2 44.0 56.5 30.9 46.8 46.8 48.1 42.5 53.2 29.4 44.0 44.0 45.0 41.0 49.7 27.9
85 55.4 55.4 55.3 55.3 60.0 42.9 52.7 52.7 52.7 52.7 56.9 41.5 50.0 50.0 50.0 50.0 53.5 40.0 47.2 47.2 47.2 47.2 50.1 38.5
90 58.8 58.8 58.8 58.8 60.7 53.4 56.1 56.1 56.1 56.1 57.6 52.0 53.3 53.3 53.3 53.3 54.4 50.6 50.4 50.4 50.4 50.4 51.0 49.1
1920
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unitapplicationsbelow1280CFM
•
•
Electricheatersrestrictedonapplicationsbelow1280CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 1280 CFM.
RT-PRC005-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5Ton)
High Efficiency
Table PD-14 — Gross Cooling Capacities (MBH) 5 Ton Single Phase THC060A1– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.2 48.2 64.3 37.8 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1
80
57.6 57.6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67.3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6
1800
2000
2200
85 62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0
90 65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5
75
80 60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47.6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1
85 64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57.1 57.1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5
90
75 59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 67.7 24.3 49.6 49.4 57.6 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1
80 62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47.9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5
85 66.0 66.0 67.3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7
90 68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6
75 60.6 57.4 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5
80 64.0 64.0 67.0 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8
57.8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37.0 67.3 23.9 48.2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7
67.6 67.6 67.6 67.6 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8
2400
85
67.2 67.2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67.0 46.8 57.2 57.2 57.2 57.2 62.9 45.6
90 69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57.1 65.5 65.5 65.5 65.5 67.5 57.3 62.2 62.2 62.2 62.2 63.9 57.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-15 — Gross Cooling Capacities (MBH) 5Ton Three Phase THC060A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.6 49.0 64.4 37.5 67.7 24.7 52.0 46.8 60.9 35.7 66.2 23.3 47.0 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0
80 58.5 58.5 64.6 47.0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8
85 62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 67.7 42.3 55.6 55.6 57.3 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5
90 66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1
1800
2000
2200
75 58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 37.6 66.6 23.8 48.6 47.7 57.2 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5
80 61.1 61.1 65.6 49.2 69.0 34.6 57.3 57.3 62.4 48.4 67.5 34.8 53.2 53.2 57.8 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4
85 64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 67.8 43.0 58.4 58.4 59.2 57.5 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0
90
67.7 67.7 67.7 67.7 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3
75 59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 67.0 24.2 50.0 50.0 58.3 37.3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0
80 63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 67.9 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9
85 66.4 66.4 67.2 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 44.2
90 68.7 68.7 68.7 68.7 71.2 52.8 67.1 67.1 67.1 67.1 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 61.0 61.0 61.0 61.0 62.9 55.3
75 61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 67.3 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47.2 47.2 53.4 36.6 61.7 21.4
80 64.5 64.5 67.0 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 57.5 57.5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3
2400
85
67.3 67.3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 62.6 46.2
90 69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67.6 58.0 62.5 62.5 62.5 62.5 63.7 57.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
28
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5Ton)
High Efficiency
Table PD-16 — Gross Cooling Capacities (MBH) 5Ton THC060A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 50.7 36.2 57.0 29.4 63.7 22.6 48.1 34.6 54.2 27.9 60.7 21.0 45.5 32.9 51.3 26.2 57.5 19.4 42.7 31.2 48.2 24.5 54.1 17.7
80 50.8 41.8 57.1 35.1 63.8 28.2 48.3 40.2 54.4 33.5 60.8 26.6 45.6 38.6 51.5 31.9 57.6 25.0 42.9 36.8 48.4 30.1 54.2 23.3
85 51.0 47.5 57.2 40.7 64.0 33.8 48.6 45.9 54.5 39.1 61.0 32.2 46.0 44.2 51.6 37.4 57.8 30.6 43.3 42.5 48.5 35.7 54.4 28.8
90 52.2 52.2 57.4 46.3 64.1 39.4 50.1 50.1 54.6 44.7 61.1 37.8 47.8 47.8 51.7 43.0 57.9 36.1 45.5 45.5 48.7 41.3 54.5 34.4
1000*
1300*
1600
75 54.3 41.5 60.7 32.7 67.6 23.8 51.5 39.9 57.7 31.0 64.3 22.1 48.6 38.1 54.5 29.3 60.8 20.4 45.5 36.4 51.1 27.5 57.0 18.7
80 54.6 48.8 60.9 40.0 67.8 31.0 51.9 47.1 57.9 38.3 64.5 29.3 49.0 45.4 54.7 36.6 60.9 27.6 46.0 43.6 51.3 34.8 57.2 25.9
85 55.6 55.6 61.1 47.2 67.9 38.2 53.2 53.2 58.1 45.5 64.6 36.5 50.7 50.7 54.9 43.7 61.1 34.8 48.1 48.1 51.5 41.9 57.4 33.0
90 58.8 58.8 61.5 54.4 68.1 45.3 56.3 56.3 58.5 52.7 64.8 43.6 53.7 53.7 55.3 50.9 61.3 41.9 51.0 51.0 52.0 49.1 57.5 40.1
75 56.8 46.5 63.2 35.6 70.2 24.7 53.9 44.9 60.0 33.9 66.6 23.0 50.8 43.1 56.6 32.2 62.9 21.3 47.5 41.3 53.0 30.4 58.9 19.5
80
57.6 55.5 63.4 44.5 70.3 33.5 54.7 53.8 60.2 42.7 66.8 31.8 51.6 51.6 56.8 41.0 63.0 30.1 48.8 48.8 53.2 39.1 59.1 28.3
85 60.3 60.3 63.8 53.2 70.5 42.2 57.7 57.7 60.6 51.5 67.0 40.5 54.9 54.9 57.3 49.7 63.2 38.8 52.0 52.0 53.7 47.9 59.3 36.9
90 63.8 63.8 64.7 62.1 70.8 50.9 61.1 61.1 61.6 60.4 67.3 49.2 58.2 58.2 58.2 58.2 63.5 47.4 55.1 55.1 55.1 55.1 59.6 45.6
75 58.1 49.6 64.5 37.5 71.4 25.2 55.1 48.2 61.1 35.8 67.8 23.5 51.9 46.3 57.6 34.0 63.9 21.8 48.6 44.5 53.9 32.2 59.8 20.0
80 59.3 59.3 64.7 47.4 71.6 35.1 56.6 56.6 61.4 45.6 67.9 33.4 53.8 53.8 57.9 43.8 64.1 31.6 50.8 50.8 54.2 42.0 60.0 29.8
85 62.9 62.9 65.3 57.2 71.8 44.9 60.1 60.1 62.0 55.4 68.2 43.1 57.2 57.2 58.6 53.6 64.3 41.3 54.1 54.1 55.0 51.8 60.2 39.5
90 66.5 66.5 66.5 66.5 72.2 54.6 63.7 63.7 63.7 63.7 68.5 52.9 60.6 60.6 60.6 60.6 64.7 51.0 57.4 57.4 57.4 57.4 60.7 49.1
1800
2000
75 59.3 51.6 65.9 38.8 73.0 25.8 55.9 49.6 62.1 36.9 69.0 23.9 52.3 47.6 58.3 34.8 64.9 22.0 48.7 45.5 54.4 32.8 60.8 20.1
80 60.9 60.9 66.1 49.3 73.2 36.4 57.9 57.9 3.0 47.3 69.2 34.5 54.7 54.7 58.6 45.3 65.2 32.5 51.4 51.4 54.7 43.2 61.0 30.5
85 64.8 64.8 66.9 59.8 73.5 46.9 61.6 61.6 63.2 57.8 69.5 44.9 58.4 58.4 59.5 55.8 65.4 42.9 55.0 55.0 55.7 53.8 61.3 40.9
90 68.6 68.6 68.6 68.6 73.8 57.1 65.4 65.4 65.3 65.3 69.9 55.1 62.1 62.1 62.0 62.0 65.9 53.2 58.7 58.7 58.7 58.7 61.8 51.2
75 60.4 54.5 66.7 40.5 73.8 26.4 56.9 52.4 62.9 38.5 69.8 24.5 53.3 50.4 59.0 36.5 65.7 22.5 49.6 48.3 55.1 34.4 61.5 20.5
80 62.7 62.7 67.1 51.8 74.1 37.8 59.5 59.5 63.3 49.8 70.0 35.9 56.3 56.3 59.4 47.8 65.9 33.9 52.9 52.9 55.5 45.8 61.7 31.9
85 66.7 66.7 68.0 63.3 74.4 49.2 63.4 63.4 64.3 61.3 70.3 47.2 60.1 60.1 60.6 59.3 66.2 45.2 56.7 56.7 56.6 56.6 62.0 43.2
90 70.6 70.6 70.6 70.6 74.9 60.3 67.3 67.3 67.3 67.3 70.8 58.3 63.9 63.9 63.9 63.9 66.8 56.4 60.4 60.4 60.4 60.4 62.7 54.4
2200
75 61.3 57.2 67.5 42.1 74.6 26.9 57.8 55.2 63.6 40.1 70.5 24.9 54.2 53.2 59.7 38.0 66.3 22.9 50.4 50.4 55.7 36.0 62.1 21.0
80 64.3 64.3 67.9 54.3 74.9 39.2 61.0 61.0 64.1 52.3 70.7 37.2 57.7 57.7 60.2 50.3 66.6 35.2 54.2 54.2 56.2 48.2 62.3 33.2
85 68.4 68.4 69.1 66.7 75.1 51.4 65.0 65.0 65.4 64.8 71.0 49.4 61.6 61.6 61.6 61.6 66.8 47.4 58.1 58.1 58.1 58.1 62.6 45.4
90 72.4 72.4 72.4 72.4 75.8 63.5 69.0 69.0 69.0 69.0 71.7 61.5 65.5 65.5 65.5 65.5 67.6 59.5 61.9 61.9 61.9 61.9 63.5 57.5
2400
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unitapplicationsbelow1600CFM
•
•
Electricheatersrestrictedonapplicationsbelow1600CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 1600 CFM.
RT-PRC005-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
(6Ton)
High Efficiency
Performance
Data
Table PD-17 — Gross Cooling Capacities (MBH) 6Ton Three Phase THC072A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73
CFM
61
67
73
61
67
61
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 67.3 56.6 73.6 42.5 74.5 27.6 61.6 53.5 71.8 41.9 75.1 26.6 55.8 50.4 66.8 38.7 74.1 25.3 49.8 47.2 59.9 36.3 71.3 23.5
80 68.7 68.2 73.8 51.7 75.4 37.0 63.6 63.6 72.0 52.1 76.0 38.1 58.9 58.9 66.9 49.7 74.7 36.4 54.1 54.1 60.2 46.5 71.5 34.5
85 72.2 72.2 74.5 61.4 76.2 44.5 69.2 69.2 72.5 62.8 76.8 46.1 64.6 64.6 67.8 60.9 75.0 46.2 59.5 59.5 61.3 57.7 71.7 45.4
90 74.7 74.7 75.3 70.6 77.0 51.9 73.4 73.4 73.7 73.2 77.7 55.1 70.1 70.1 70.1 70.1 75.6 56.1 65.4 65.4 65.4 65.4 72.1 55.8
75 69.0 60.1 74.0 43.3 74.5 27.9 63.5 57.2 72.7 43.1 75.2 27.0 57.5 54.0 68.4 40.9 74.5 25.7 51.8 51.0 61.5 37.6 72.0 24.0
80 70.7 70.7 74.3 52.9 75.4 37.2 66.8 66.8 73.0 54.6 76.2 37.8 61.9 61.9 68.7 53.0 75.1 37.4 56.7 56.7 61.9 49.8 72.4 36.1
85 73.8 73.8 75.0 63.0 76.2 44.9 71.9 71.9 73.8 66.0 77.1 47.0 67.9 67.9 69.7 65.4 75.5 47.5 62.7 62.7 63.6 62.4 72.6 47.7
90 75.6 75.6 75.9 72.4 77.0 52.5 75.2 75.2 75.1 75.1 78.0 56.3 72.8 72.8 72.7 72.7 76.4 58.2 68.8 68.8 68.8 68.8 73.2 59.0
75 70.3 63.2 74.2 43.9 74.6 28.3 65.2 60.8 73.2 44.5 75.4 27.4 59.2 57.7 69.6 42.9 74.7 26.2 53.2 53.2 62.9 39.8 72.5 24.6
80 72.3 72.3 74.5 53.9 75.4 37.4 69.5 69.5 73.8 56.7 76.3 38.2 64.6 64.6 70.0 56.1 75.6 38.5 59.2 59.2 63.5 53.0 73.0 37.7
85 74.7 74.7 75.3 64.3 76.2 45.2 73.7 73.7 74.7 68.7 77.3 47.6 70.5 70.5 71.3 69.3 76.1 48.9 65.6 65.6 65.6 65.6 73.4 49.7
90 76.1 76.1 76.2 73.6 76.9 53.0 76.2 76.2 76.2 76.2 78.1 57.2 74.5 74.5 74.5 74.5 76.9 59.9 71.2 71.2 71.2 71.2 74.1 61.7
75 71.3 65.8 74.3 44.4 74.6 28.7 66.8 64.4 73.7 45.6 75.5 27.8 60.5 60.5 70.6 44.8 74.9 26.6 55.1 55.1 64.1 41.8 72.9 25.0
80 73.3 73.3 74.7 54.8 75.4 37.6 71.4 71.4 74.4 58.5 76.4 38.5 67.0 67.0 71.0 58.9 75.9 39.1 61.4 61.4 64.9 56.2 73.3 38.6
85 75.1 75.1 75.5 65.3 76.2 45.6 74.8 74.8 75.4 70.8 77.4 48.2 72.4 72.4 72.4 72.4 76.4 49.9 68.2 68.2 68.1 68.1 74.0 51.5
90 76.3 76.3 76.3 74.5 76.9 53.5 76.9 76.9 76.9 76.9 78.2 58.0 75.7 75.7 75.7 75.7 77.2 61.3 72.9 72.9 72.9 72.9 74.8 64.1
2160
2400
2640
2880
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
30
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
(7½Ton)
High Efficiency
Performance
Data
Table PD-18 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase THC092A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73
CFM
61
67
73
61
67
61
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 85.7 72.4 95.8 56.8 99.9 37.1 79.3 69.3 92.0 53.7 98.8 35.8 72.8 66.0 85.9 50.8 96.1 34.2 66.1 62.6 78.5 49.1 91.8 32.2
80
87.5 87.0 96.2 68.5 101.1 50.4 81.8 81.8 92.4 67.4 99.6 50.2 76.6 76.6 86.2 64.6 96.7 48.0 71.1 71.1 79.0 61.4 92.0 45.8
2700
3000
3300
85 92.8 92.8 97.0 81.6 102.3 61.3 88.5 88.5 93.1 81.1 100.3 61.3 83.4 83.4 87.1 78.6 97.0 60.9 77.9 77.9 80.3 75.4 92.3 59.4
90
75
80 90.5 90.5 97.4 71.2 101.6 51.1 85.6 85.6 94.0 71.0 100.4 50.9 80.2 80.2 88.2 68.7 97.3 49.8 74.5 74.5 81.0 65.5 93.2 47.9
85 95.6 95.6 98.4 85.1 102.9 62.5 92.2 92.2 95.0 85.8 101.3 63.3 87.3 87.3 89.5 84.1 98.1 63.3 81.8 81.8 82.9 81.2 93.6 62.5
90 99.4 99.4 99.9 98.1 104.1 74.1 97.2 97.2 97.2 97.2 102.1 75.5 93.6 93.6 93.5 93.5 99.1 77.0 88.8 88.8 88.7 88.7 94.4 76.9
75 89.8 81.3 97.5 59.0 100.7 38.1 83.6 78.2 94.6 58.3 99.8 37.1 77.0 75.0 89.2 55.9 97.5 35.4 70.0 70.0 82.1 52.8 93.6 33.4
80 93.2 93.2 98.3 73.5 102.0 51.7 88.9 88.9 95.2 74.2 101.0 52.0 83.4 83.4 89.8 72.6 97.9 50.6 77.6 77.6 82.8 69.5 94.1 49.9
97.2 97.2 98.3 94.2 103.5 72.4 94.3 94.3 94.3 94.3 101.1 73.1 90.0 90.0 90.0 90.0 97.8 73.7 84.9 84.9 84.9 84.9 92.9 72.7
87.9 77.0 96.6 57.3 100.4 37.6 81.5 73.7 93.5 56.1 99.4 36.4 74.9 70.5 87.8 53.4 96.9 34.8 67.4 67.4 80.5 50.2 92.8 32.8
85
97.6 97.6 99.4 88.0 103.3 67.9 94.9 94.9 96.5 90.0 101.9 64.8 90.5 90.5 91.7 89.4 99.0 67.3 85.2 85.2 85.1 85.1 94.7 65.2
90 100.9 100.9 100.9 100.9 104.6 75.6 99.2 99.2 99.2 99.2 102.8 77.7 96.1 96.1 96.1 96.1 100.1 80.0 91.8 91.8 91.8 91.8 95.7 80.7
75 91.5 85.3 98.2 60.6 101.0 38.6 85.5 82.6 95.4 60.2 100.2 37.5 78.5 78.5 90.5 58.3 98.0 35.9 72.4 72.4 83.4 55.2 94.3 34.0
80 95.2 95.2 99.0 75.4 102.3 56.8 91.5 91.5 96.3 77.2 101.5 52.7 86.3 86.3 91.3 76.3 98.4 51.4 80.4 80.4 84.4 73.4 94.7 51.4
85 99.1 99.1 100.2 90.6 103.6 69.8 96.9 96.9 97.8 93.6 102.4 66.1 93.1 93.1 93.1 93.1 99.7 69.8 88.0 88.0 87.9 87.9 95.6 67.8
90 101.9 101.9 101.9 101.9 105.0 76.9 100.7 100.7 100.7 100.7 103.4 79.6 98.0 98.0 97.9 97.9 100.8 82.5 94.0 94.0 94.0 94.0 96.7 84.1
3600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½Ton)
High Efficiency
Table PD-19 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase THC092A3, A4, AW – Dehumidification (Hot Gas Reheat)
or TXV Option
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 76.3 54.5 85.6 45.2 95.8 34.8 72.9 52.4 81.9 43.2 91.7 32.8 69.2 50.2 77.9 41.1 87.3 30.8 65.3 48.0 73.7 38.9 82.8 28.6
80 76.5 62.6 85.8 53.0 95.9 43.1 73.0 60.5 82.0 50.9 91.8 41.1 69.3 58.3 78.0 48.7 87.4 39.0 65.4 56.0 73.8 46.5 82.9 36.8
85 76.6 70.6 85.9 61.0 96.0 51.1 73.1 68.4 82.1 58.9 91.9 49.0 69.4 66.2 78.1 56.7 87.5 46.9 65.6 63.8 73.9 54.4 83.0 44.7
1500*
1950*
2400
90
77.3 77.3 86.1 69.0 96.1 59.0 74.5 74.5 82.3 66.9 92.0 57.0 71.5 71.5 78.3 64.6 87.7 54.8 68.3 68.3 74.0 62.3 83.1 52.6
75 81.6 61.9 91.2 49.4 101.6 36.5 77.7 59.7 87.0 47.2 97.1 34.5 73.7 57.5 82.6 45.0 92.3 32.3 69.4 55.1 78.0 42.7 87.3 30.1
80 81.9 72.2 91.3 59.6 101.7 47.0 78.1 70.0 87.2 57.5 97.2 44.8 74.0 67.7 82.8 55.2 92.4 42.6 69.8 65.4 78.2 52.9 87.4 40.4
85 82.3 82.3 91.6 69.9 101.9 57.1 79.2 79.2 87.4 67.7 97.3 55.0 75.8 75.8 83.0 65.4 92.6 52.8 72.3 72.3 78.4 63.1 87.6 50.5
90 86.9 86.9 91.9 80.0 102.0 67.2 83.6 83.6 87.8 77.8 97.5 65.1 80.2 80.2 83.4 75.5 92.7 62.8 76.5 76.5 78.9 73.2 87.8 60.6
75 85.2 68.7 94.9 53.4 105.5 37.9 81.1 66.5 90.5 51.2 100.7 35.8 76.8 64.2 85.8 48.9 95.6 33.6 72.3 61.8 80.9 46.6 90.3 31.4
80 86.0 81.3 95.1 65.8 105.6 50.4 82.0 79.1 90.7 63.6 100.8 48.2 77.9 76.9 86.0 61.4 95.7 46.0 73.4 73.4 81.2 59.0 90.4 43.7
85 89.2 89.2 95.5 78.2 105.8 62.7 85.7 85.7 91.1 76.0 101.0 60.5 82.0 82.0 86.5 73.7 95.9 58.2 78.1 78.1 81.6 71.3 90.6 55.9
90 94.2 94.2 96.4 90.6 106.1 74.9 90.6 90.6 92.1 88.4 101.3 72.8 86.8 86.8 87.6 86.2 96.2 70.4 82.8 82.8 82.8 82.8 90.9 68.1
75
87.1 73.0 96.8 57.3 107.4 38.7 82.9 70.9 92.2 55.1 102.5 36.6 78.5 68.6 87.4 52.9 97.2 34.4 73.9 66.2 82.3 50.6 91.8 32.2
80 88.4 87.3 97.0 69.7 107.6 52.5 84.2 84.2 92.5 67.5 102.6 50.4 80.4 80.4 87.7 65.2 97.4 48.1 76.4 76.4 82.7 62.8 91.9 45.8
85 92.9 92.9 97.6 83.5 107.8 66.2 89.3 89.3 93.1 81.3 102.8 64.0 85.4 85.4 88.4 79.0 97.6 61.8 81.3 81.3 83.4 76.7 92.1 59.4
90 98.2 98.2 99.1 97.6 108.1 79.8 94.4 94.4 94.4 94.4 103.2 77.6 90.4 90.4 90.4 90.4 98.0 75.3 86.2 86.2 86.2 86.2 92.5 73.0
2700
3000
75 88.7 77.2 98.3 58.4 109.0 39.5 84.5 75.0 93.6 56.1 103.9 37.3 80.0 72.7 88.7 53.8 98.6 35.1 75.3 70.3 83.5 51.4 93.0 32.8
80 90.8 90.8 98.7 73.5 109.2 54.6 87.0 87.0 94.0 71.3 104.1 52.4 83.1 83.1 89.1 69.0 98.8 50.2 78.9 78.9 84.0 66.6 93.2 47.9
85 96.2 96.2 99.5 88.8 109.5 69.7 92.4 92.4 94.9 86.6 104.4 67.5 88.3 88.3 90.1 84.3 99.0 65.2 84.0 84.0 85.1 81.9 93.4 62.9
90 101.7 101.7 101.7 101.7 109.9 84.6 97.8 97.7 97.7 97.7 104.8 82.4 93.6 93.6 93.5 93.5 99.5 80.2 89.1 89.1 89.1 89.1 93.9 77.8
75 90.2 81.4 99.7 60.7 110.4 40.1 85.9 79.1 94.8 58.5 105.2 37.9 81.4 76.8 89.8 56.1 99.7 35.7 76.7 74.4 84.6 53.8 94.0 33.4
80 93.4 93.4 100.1 77.3 110.6 56.7 89.5 89.5 95.3 75.0 105.4 54.5 85.5 85.5 90.3 72.7 99.9 52.2 81.1 81.1 85.1 70.3 94.2 49.9
85 99.1 99.1 101.2 94.0 110.9 73.1 95.1 95.1 96.6 91.8 105.6 70.8 90.8 90.8 91.7 89.5 100.2 68.6 86.4 86.4 86.4 86.4 94.5 66.1
90 104.8 104.8 104.8 104.8 111.4 89.4 100.7 100.7 100.6 100.6 106.2 87.2 96.3 96.3 96.3 96.3 100.8 84.9 91.7 91.7 91.7 91.7 95.2 82.5
3300
75
91.6 85.5 100.8 63.0 111.5 40.8 87.2 83.2 95.9 60.7 106.2 38.6 82.0 82.0 90.8 58.4 100.6 36.3 77.7 77.7 85.5 56.0 94.9 34.0
80 95.8 95.8 101.3 80.9 111.7 58.6 91.8 91.8 96.5 78.7 106.4 56.4 87.5 87.5 91.4 76.3 100.8 54.1 83.1 83.1 86.1 74.0 95.0 51.8
85 101.6 101.6 102.8 99.1 112.0 76.3 97.5 97.5 97.4 97.4 106.8 74.2 93.1 93.1 93.0 93.0 101.2 71.9 88.5 88.5 88.5 88.5 95.4 69.4
90 107.5 107.5 107.5 107.5 112.8 94.0 103.2 103.2 103.2 103.2 107.5 91.8 98.7 98.7 98.7 98.7 102.1 89.5 93.9 93.9 93.9 93.9 96.4 87.2
3600
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unitapplicationsbelow2400CFM
•
•
Electricheatersrestrictedonapplicationsbelow2400CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.
32
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½Ton)
High Efficiency
Table PD-20— Gross Cooling Capacities (MBH) 8½ Ton Three Phase THC102A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73
CFM
61
67
73
61
67
61
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 94.0 81.8 105.7 62.8 110.8 40.9 86.3 77.8 100.7 59.7 109.7 39.3 79.0 74.2 92.4 56.0 105.5 37.1 71.8 70.5 84.0 53.1 99.6 34.6
80 96.9 96.9 106.2 77.6 112.0 56.0 90.6 90.6 101.1 75.9 110.1 55.4 84.5 84.5 92.9 72.2 106.1 53.2 78.3 78.3 84.7 68.5 99.8 50.6
85 103.5 103.5 107.2 92.9 113.2 68.7 98.6 98.6 102.2 92.1 111.6 70.3 92.1 92.1 94.5 88.8 106.4 68.8 85.8 85.8 86.7 85.2 100.0 66.5
90 108.4 108.4 109.0 107.7 114.4 81.6 105.0 105.0 105.0 105.0 112.6 84.9 99.9 99.9 99.9 99.9 107.3 83.9 93.5 93.5 93.5 93.5 100.8 82.6
75 96.6 87.2 107.1 64.7 111.4 41.5 88.7 83.3 102.4 62.6 110.7 40.1 81.4 79.6 94.4 59.1 106.6 37.9 74.2 74.2 85.9 55.4 101.1 35.5
80 100.9 100.9 107.7 81.0 112.7 56.9 94.9 94.9 103.0 80.4 111.7 57.5 88.3 88.3 95.2 77.1 107.3 55.7 81.8 81.8 86.8 73.4 101.4 53.1
85 106.6 106.6 108.9 97.4 114.0 70.2 102.6 102.6 104.4 97.8 112.8 72.9 96.5 96.5 97.6 95.6 108.0 72.4 89.9 89.9 89.8 89.8 101.8 70.8
90 110.8 110.8 110.8 110.8 115.3 83.8 108.1 108.1 108.1 108.1 114.0 88.5 103.8 103.8 103.8 103.8 108.9 88.3 97.8 97.8 97.8 97.8 102.8 87.9
75 98.9 92.5 107.4 65.9 112.0 42.2 91.2 88.7 103.7 65.4 111.1 40.7 83.5 83.5 96.3 62.2 107.5 38.7 76.9 76.9 87.5 58.4 102.2 36.2
80 103.7 103.7 108.8 84.0 113.3 57.7 98.7 98.7 104.5 84.5 112.4 58.7 91.7 91.7 97.3 81.9 108.3 57.6 85.0 85.0 88.8 78.2 102.6 55.5
85 108.8 108.8 110.1 100.9 114.6 76.9 105.4 105.4 106.4 103.0 113.7 75.1 100.2 100.2 100.2 100.2 109.3 75.7 93.4 93.4 93.4 93.4 103.1 74.4
90 112.3 112.3 112.1 112.1 115.9 85.7 110.4 110.4 110.4 110.4 114.9 91.4 106.5 106.5 106.5 106.5 110.2 92.3 101.3 101.3 101.3 101.3 104.4 92.7
75 100.9 97.3 108.1 67.4 112.5 42.9 93.1 93.1 104.7 67.9 111.5 41.4 86.2 86.2 97.8 65.2 108.2 39.4 79.4 79.4 88.8 61.3 103.0 36.9
80 105.9 105.9 109.5 86.2 113.8 58.4 101.6 101.6 105.8 88.2 112.8 59.6 94.9 94.9 99.1 86.5 109.2 59.6 87.9 87.9 90.6 82.8 103.5 57.8
85 110.2 110.2 110.9 103.4 115.1 79.5 107.6 107.6 107.6 107.6 114.1 76.6 103.0 103.0 103.0 103.0 109.9 77.6 96.6 96.6 96.6 96.6 104.2 77.7
90 112.9 112.9 112.9 112.9 116.5 87.5 112.2 112.2 112.2 112.2 115.4 93.4 108.6 108.6 108.6 108.6 111.3 95.9 103.9 103.9 103.9 103.9 105.8 97.0
3060
3400
3740
4080
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½ Ton)
High Efficiency
Table PD-21— Gross Cooling Capacities (MBH) 8½ Ton Three Phase THC102A3, A4, AW – Dehumidification (Hot Gas Reheat)
or TXV Option
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 84.4 60.9 94.7 49.8 105.6 38.0 80.3 58.5 90.3 47.5 100.8 35.7 75.9 56.0 85.6 45.0 95.7 33.3 71.3 53.3 80.6 42.4 90.3 30.8
80 84.5 70.3 94.8 59.1 105.8 47.6 80.4 67.9 90.4 56.7 100.9 45.2 76.1 65.3 85.7 54.1 95.9 42.7 71.5 62.6 80.7 51.5 90.5 40.2
85 84.8 79.7 94.9 68.4 105.9 56.8 80.8 77.3 90.6 66.0 101.1 54.4 76.5 74.7 85.9 63.4 96.0 51.9 72.2 71.0 80.9 60.8 90.6 49.3
1700*
2210*
2720
3060
3400
3740
90
87.0 87.0 95.1 77.7 106.0 66.0 83.6 83.6 90.7 75.2 101.2 63.6 80.0 80.0 86.0 72.6 96.1 61.1 76.2 76.2 81.0 70.0 90.8 58.5
75 90.0 69.6 100.5 54.9 111.8 39.9 85.6 67.0 95.7 52.4 106.5 37.5 80.8 64.4 90.6 49.8 100.9 35.0 75.8 61.6 85.1 47.1 95.1 32.4
80 90.5 81.7 100.7 66.8 111.9 51.9 86.1 79.2 95.9 64.3 106.7 49.5 81.5 76.6 90.8 61.7 101.1 47.0 76.6 73.8 85.3 59.0 95.3 44.3
85 92.3 92.3 101.0 78.8 112.1 63.8 88.6 88.6 96.1 76.3 106.8 61.3 84.6 84.6 91.0 73.6 101.3 58.7 80.3 80.3 85.6 70.9 95.4 56.1
90
97.5 97.5 101.5 90.7 112.3 75.6 93.6 93.6 96.7 88.2 107.0 73.1 89.5 89.5 91.7 87.1 101.5 70.5 85.1 85.1 86.4 82.9 95.6 67.9
75 94.0 77.6 104.4 59.5 115.8 41.4 89.3 75.1 99.3 57.0 110.2 38.9 84.3 72.4 93.8 54.4 104.3 36.4 79.0 69.6 88.1 51.7 98.2 33.8
80 95.2 92.6 104.7 74.1 116.0 55.9 90.7 90.1 99.5 71.5 110.4 53.4 86.0 86.0 94.1 68.9 104.5 50.9 81.4 81.4 88.4 66.2 98.4 48.2
85 99.8 99.8 105.2 88.7 116.2 70.3 95.7 95.7 100.1 86.1 110.6 67.8 91.3 91.3 94.7 83.5 104.7 65.2 86.6 86.6 89.1 80.7 98.6 62.5
90 105.4 105.4 106.5 103.4 116.5 84.7 101.1 101.1 101.6 100.9 110.9 82.1 96.6 96.6 96.6 96.6 105.1 79.5 91.8 91.8 91.8 91.8 98.9 76.9
75 96.1 82.8 106.4 63.2 117.8 42.2 91.3 80.2 101.0 60.7 112.1 39.8 86.2 77.5 95.4 58.1 106.0 37.2 80.8 74.7 89.6 55.4 99.7 34.6
80 98.1 98.1 106.7 78.8 118.1 58.5 93.8 93.8 101.4 76.2 112.2 55.9 89.3 89.3 95.8 73.5 106.2 53.3 84.6 84.6 90.0 70.8 99.9 50.7
85 103.8 103.8 107.5 95.1 118.3 74.5 99.5 99.5 102.3 92.5 112.5 72.0 94.8 94.8 96.9 89.9 106.4 69.4 89.9 89.9 91.2 87.2 100.1 66.7
90 109.7 109.7 109.7 109.7 118.7 90.6 105.2 105.2 105.2 105.2 112.9 88.1 100.4 100.4 100.4 100.4 106.9 85.4 95.4 95.4 95.4 95.4 100.7 82.7
75
97.9 87.9 108.0 65.4 119.4 43.1 93.0 85.3 102.5 62.8 113.5 40.6 87.8 82.6 96.8 60.1 107.4 38.1 82.5 79.9 90.8 57.4 100.9 35.4
80 101.3 101.3 108.4 83.4 119.7 60.9 96.9 96.9 103.0 80.8 113.7 58.4 92.2 92.2 97.3 78.1 107.5 55.8 87.3 87.3 91.4 75.3 101.1 53.1
85 107.3 107.3 109.6 101.4 120.0 78.7 102.8 102.8 104.3 98.8 114.0 76.1 98.0 98.0 98.9 96.2 107.8 73.5 92.9 92.9 92.9 92.9 101.4 70.8
90 113.4 113.4 113.4 113.4 120.6 96.4 108.8 108.8 108.7 108.7 114.6 93.8 103.8 103.8 103.8 103.8 108.6 91.2 98.6 98.6 98.6 98.6 102.2 88.5
75 99.6 92.9 109.3 68.2 120.7 43.8 94.6 90.3 103.8 65.6 114.8 41.4 89.4 87.6 98.0 62.9 108.5 38.8 83.8 83.8 91.9 60.2 101.9 36.2
80 104.1 104.1 109.9 87.9 121.0 63.3 99.5 99.5 104.4 85.3 114.9 60.7 94.7 94.7 98.7 82.6 108.7 58.1 89.6 89.6 92.6 79.8 102.1 55.4
85 110.4 110.4 111.6 107.6 121.4 82.7 105.7 105.7 106.3 105.1 115.3 80.1 100.7 100.7 100.6 100.6 109.0 77.5 95.4 95.4 95.4 95.4 102.5 74.9
90 116.7 116.7 116.7 116.7 122.1 102.0 111.8 111.8 111.8 111.8 116.2 99.5 106.7 106.7 106.7 106.7 110.0 96.8 101.2 101.2 101.2 101.2 103.6 94.2
75 101.1 97.8 110.5 71.0 121.9 44.6 96.1 95.2 104.9 68.3 115.8 42.1 90.8 90.8 98.9 65.7 109.4 39.5 85.7 85.7 92.7 62.9 102.8 36.8
80 106.6 106.6 111.2 92.2 122.1 65.7 101.9 101.9 105.7 89.6 116.0 63.1 96.9 96.9 99.8 87.0 109.6 60.5 91.6 91.6 93.8 84.2 103.0 57.8
85 113.1 113.1 113.0 113.0 122.5 86.7 108.2 108.2 108.1 108.1 116.4 84.1 103.0 103.0 103.0 103.0 110.0 81.5 97.6 97.6 97.6 97.6 103.5 78.8
90 119.5 119.5 119.5 119.5 123.6 107.6 114.5 114.5 114.5 114.5 117.5 105.0 109.2 109.2 109.2 109.2 111.3 102.4 103.6 103.6 103.6 103.6 104.9 99.8
4080
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unitapplicationsbelow2720CFM
•
•
Electricheatersrestrictedonapplicationsbelow2720CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.
34
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-22 — Gross Cooling Capacities (MBH) 10 Ton Three Phase THC120A3, A4, AW– Standard Refrigeration Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73
CFM
61
67
73
61
67
61
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 107.0 94.4 117.4 75.0 123.4 46.0 98.7 90.1 114.7 68.8 121.9 44.4 88.5 88.5 107.2 65.3 118.6 42.2 82.3 78.8 97.8 61.1 113.6 39.6
80 110.9 108.6 119.9 88.2 125.0 62.5 104.5 104.1 115.2 87.5 123.4 62.3 97.7 97.7 107.8 84.3 119.4 60.8 90.6 90.6 98.5 80.1 114.3 58.3
85 117.6 117.6 120.9 105.0 126.6 76.7 113.1 113.1 116.5 105.8 124.9 78.1 106.9 106.9 107.0 107.0 120.9 78.1 99.9 99.9 100.0 100.0 114.8 76.5
90 122.5 122.5 122.4 122.4 128.2 91.1 119.6 119.6 119.6 117.1 126.4 94.1 115.0 115.0 114.7 114.6 121.6 94.3 109.0 109.0 109.0 109.0 115.8 94.3
3600
4000
4400
75 109.8 100.5 119.4 71.9 122.5 46.5 99.7 99.7 116.1 71.5 121.7 45.0 92.5 92.5 110.1 69.1 119.4 43.0 85.6 83.4 100.9 65.0 114.6 40.5
80 114.6 114.1 120.8 90.1 124.1 68.3 109.3 109.3 117.0 91.2 123.4 62.7 102.3 102.3 110.8 89.9 120.6 62.5 94.8 94.8 101.9 86.0 115.5 61.1
85 120.5 120.5 122.3 107.9 125.9 76.4 117.0 117.0 118.6 110.2 125.0 78.8 111.6 111.6 111.8 111.8 122.1 80.4 104.7 104.7 105.8 102.6 116.3 79.7
90 125.2 125.2 124.2 124.2 127.6 90.9 122.4 122.4 121.7 120.9 126.6 95.1 118.5 118.5 118.3 118.3 123.6 98.4 113.1 113.1 113.3 113.3 117.7 98.6
75 112.3 106.1 121.2 74.8 124.6 47.6 103.6 103.6 117.1 75.5 123.0 46.0 96.7 93.9 111.2 72.2 120.0 43.7 88.6 88.0 102.0 68.2 115.3 41.2
80 117.6 117.6 122.5 94.7 126.3 64.2 113.0 113.0 118.4 95.8 124.7 64.4 106.3 106.3 112.2 94.9 121.5 64.3 98.8 98.8 103.5 91.1 116.1 62.8
85 122.4 122.4 124.3 113.8 128.0 79.6 119.6 119.6 119.6 119.6 126.4 81.8 115.1 115.1 115.5 111.7 122.7 83.0 109.1 109.1 108.8 107.4 117.2 83.2
90 126.0 126.0 127.1 125.0 129.6 95.2 124.3 124.3 124.2 124.2 128.0 99.4 120.9 120.9 120.9 120.9 123.9 101.2 116.1 116.1 116.1 116.1 118.8 103.3
75 113.4 113.4 121.8 76.2 125.0 48.4 107.6 104.0 118.5 77.0 123.5 46.9 99.6 98.2 112.7 75.4 120.5 44.8 91.6 91.6 103.7 71.6 115.9 41.9
80 119.5 119.5 123.2 97.0 126.7 64.8 115.8 115.8 119.8 99.6 125.2 65.3 109.8 109.8 113.9 99.4 122.1 65.5 102.3 102.3 105.5 96.3 117.2 66.8
85 124.3 124.3 125.2 116.6 128.4 80.7 121.5 121.5 121.5 121.5 126.9 83.3 117.5 117.5 117.6 115.4 123.7 85.6 111.8 111.8 111.8 111.8 118.5 86.4
90 127.5 127.5 128.0 126.7 130.1 96.9 126.0 126.0 125.5 125.5 128.6 101.5 122.6 122.6 123.0 123.0 125.5 105.5 118.2 118.2 118.2 118.2 120.3 107.5
4800
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-23— Gross Cooling Capacities (MBH) 10Ton THC120A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 94.2 68.9 105.8 56.2 118.4 42.6 89.7 66.2 101.0 53.6 113.2 40.0 84.8 63.4 95.8 50.9 107.6 37.3 79.7 60.4 90.2 48.1 101.5 34.6
80 94.4 79.8 106.0 66.8 118.6 53.6 89.9 77.1 101.2 64.1 113.4 51.0 85.0 74.2 96.0 61.4 107.8 48.3 79.9 71.2 90.4 58.4 101.7 45.4
85 93.0 93.0 106.3 77.6 118.8 64.3 90.4 86.3 101.4 74.9 113.6 61.7 86.1 82.8 96.2 72.1 108.0 59.0 81.6 79.1 90.7 69.2 101.9 56.1
90 98.0 97.2 106.4 88.3 119.0 75.0 94.4 94.4 101.6 85.6 113.8 72.4 90.4 90.4 96.4 82.8 108.2 69.6 86.1 86.1 90.9 79.8 102.1 66.7
2000*
2600*
3200
3600
4000
4400
75 100.5 78.8 112.6 62.6 125.6 44.8 95.6 76.0 107.3 59.9 119.9 42.2 90.4 73.0 101.6 57.1 113.8 39.5 84.8 70.0 95.6 54.1 107.2 36.6
80 101.1 92.6 112.9 75.8 125.8 58.8 96.4 89.9 107.6 73.1 120.1 56.1 89.7 89.7 101.9 70.2 114.0 53.3 86.0 81.9 95.8 67.1 107.4 50.4
85 104.0 102.0 113.2 89.6 126.1 72.5 99.7 98.7 107.9 86.8 120.4 69.8 95.4 95.4 102.3 83.9 114.2 67.0 90.6 90.6 96.2 80.9 107.6 64.0
90 109.9 109.9 113.9 103.3 126.4 86.1 105.6 105.6 108.7 100.5 120.7 83.4 101.1 101.1 101.1 101.1 114.5 80.6 96.2 96.2 97.5 92.3 107.9 77.6
75 104.9 87.8 117.1 67.4 130.2 46.6 99.8 85.0 111.5 65.7 124.2 44.0 94.3 82.0 110.8 64.8 117.7 41.2 88.4 78.9 99.0 59.8 110.7 38.2
80 106.6 102.0 117.4 84.1 130.5 63.4 102.0 98.4 111.8 81.3 124.5 60.6 97.0 94.6 105.8 78.4 118.0 57.8 91.6 90.5 99.4 75.3 111.0 54.8
85 112.2 112.2 118.1 100.7 130.8 79.9 107.8 107.8 112.6 98.0 124.7 77.2 103.0 103.0 106.7 95.0 118.2 74.3 97.7 97.7 100.4 91.9 111.2 71.3
90 118.6 118.6 118.8 118.8 131.1 96.5 114.2 114.2 115.0 110.5 125.1 93.7 109.2 109.2 109.6 106.5 118.7 90.8 103.8 103.8 103.9 102.2 111.7 87.8
75 107.3 93.6 119.4 70.7 132.5 47.7 102.1 90.8 113.6 67.9 126.3 45.0 96.5 87.8 107.2 64.9 119.4 42.1 90.4 84.7 100.6 61.8 112.1 39.1
80 110.3 107.5 119.7 89.4 132.8 66.3 105.6 104.0 114.0 86.6 126.6 63.5 100.4 100.3 107.6 83.5 119.6 60.5 95.1 95.1 101.1 80.4 112.4 57.5
85 116.7 116.7 120.8 107.9 133.2 84.7 112.2 112.2 115.2 105.1 126.9 82.0 107.1 107.1 108.9 102.1 119.9 79.0 101.4 101.4 101.4 101.4 112.7 75.9
90 123.5 123.5 124.2 120.7 133.7 103.1 118.8 118.8 119.0 116.9 127.5 100.3 113.6 113.6 113.2 112.8 120.6 97.3 107.7 107.7 107.7 107.7 113.4 94.2
75 110.8 101.0 122.7 75.2 136.1 49.4 105.2 97.9 116.6 72.2 129.5 46.5 99.5 94.8 110.2 69.2 122.6 43.6 92.8 92.8 103.6 66.0 115.5 40.6
80 115.3 115.3 123.1 96.0 136.3 70.2 110.3 110.3 117.0 93.1 129.7 67.3 105.0 105.0 110.7 90.0 122.9 64.3 99.5 99.5 104.1 86.8 115.7 61.3
85 122.3 122.3 124.5 116.8 136.6 90.7 117.2 117.2 117.2 117.2 130.0 87.8 111.8 111.8 111.8 111.8 123.1 84.8 106.2 106.2 106.6 103.4 116.0 81.8
90 129.5 129.5 129.3 129.3 137.2 111.3 124.2 124.2 124.2 124.2 130.6 108.4 118.7 118.7 118.6 118.6 123.9 105.4 112.9 112.9 112.8 112.8 116.9 102.4
75 112.7 106.4 124.3 78.3 137.7 50.3 106.1 106.1 118.0 75.3 130.9 47.4 100.8 100.8 111.5 72.2 123.9 44.4 95.5 93.3 104.7 69.1 116.7 41.4
80 118.4 118.4 124.8 100.9 137.9 72.8 113.2 113.2 118.6 98.0 131.2 69.9 107.8 107.8 112.2 94.9 124.2 67.0 102.1 102.1 105.5 91.7 116.9 63.9
85 125.7 125.7 125.7 125.7 138.2 95.2 120.4 120.4 120.4 120.4 131.5 92.3 114.8 114.8 115.1 112.5 124.5 89.3 109.0 109.0 109.0 107.8 117.3 86.3
90 133.1 133.1 133.1 133.1 139.0 117.5 127.6 127.6 127.6 127.6 132.4 114.6 121.9 121.9 121.9 121.9 125.5 111.6 115.9 115.9 115.9 115.9 118.5 108.6
75 113.7 113.7 125.6 81.3 139.0 51.1 108.5 108.5 119.2 78.3 132.2 48.2 103.0 103.0 112.6 75.2 125.1 45.3 97.3 96.6 105.8 72.0 117.7 42.2
80 121.1 121.1 126.2 105.7 139.3 75.4 115.8 115.8 120.0 102.7 132.4 72.5 110.2 110.2 113.5 99.7 125.3 69.5 104.4 104.4 106.8 96.5 118.0 66.5
85 128.6 128.6 128.6 128.6 139.6 99.5 123.2 123.2 123.4 121.4 132.8 96.6 117.4 117.4 117.4 116.7 125.7 93.6 111.5 111.5 111.4 111.4 118.4 90.6
90 136.2 136.2 136.2 136.2 140.7 123.6 130.6 130.6 130.6 130.6 134.0 120.7 124.7 124.7 124.7 124.7 127.1 117.6 118.5 118.5 118.5 118.5 118.5 118.5
4800
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
tablenotes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Unitapplicationsbelow3200CFM
•
•
Electricheatersrestrictedonapplicationsbelow3200CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 3200 CFM.
36
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3, 4, 5Ton)
Standard Efficiency
Table PD-24— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A
External Static Pressure (Inches ofWater) & Motor Power (Bhp)1
Standard Motor
High Speed Low Speed
ESP ESP
Oversized Motor
High Speed Low Speed
ESP ESP
Unit
Model No. CFM
Tons
3
BHP
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.42
0.43
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.82
0.85
0.88
0.90
0.93
0.95
0.97
1.00
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.42
0.43
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.82
0.85
0.88
0.90
0.93
0.95
0.97
1.00
BHP
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
BHP
0.39
0.41
0.43
0.44
0.45
0.46
0.48
0.49
0.52
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
0.39
0.41
0.43
0.44
0.45
0.46
0.48
0.49
0.52
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
BHP
0.35
0.47
0.39
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
0.73
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
0.35
0.47
0.39
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
—
960
1020
1080
1140
0.81
0.77
0.73
0.69
0.66
0.60
0.55
0.49
0.44
0.93
0.87
0.80
0.73
0.66
0.57
0.47
0.37
0.27
0.90
0.85
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.86
0.82
0.78
0.74
0.71
0.65
0.60
0.54
0.49
0.98
0.92
0.85
0.78
0.71
0.62
0.52
0.42
0.32
0.95
0.90
0.85
0.75
0.65
0.55
0.45
0.35
0.25
0.61
0.57
0.50
0.42
0.34
0.26
0.14
0.05
—
0.81
0.75
0.68
0.60
0.51
0.38
0.23
0.13
—
0.82
0.68
0.56
0.46
0.30
0.14
0.05
—
0.96
0.94
0.91
0.88
0.84
0.80
0.75
0.70
0.64
1.20
1.15
1.10
1.05
1.00
0.95
0.90
0.83
0.75
1.20
1.15
1.05
0.98
0.90
0.80
0.70
0.60
0.48
1.01
0.99
0.96
0.93
0.89
0.85
0.80
0.75
0.69
1.25
1.20
1.15
1.10
1.05
1.00
0.95
0.88
0.80
1.25
1.20
1.10
1.03
0.95
0.85
0.75
0.65
0.53
0.89
0.86
0.82
0.77
0.74
0.70
0.65
0.59
0.54
0.99
0.94
0.88
0.81
0.74
0.65
0.50
0.35
0.25
1.05
0.95
0.85
0.75
0.65
0.50
0.35
0.15
—
0.89
0.91
0.87
0.82
0.79
0.75
0.70
0.64
0.59
1.04
0.99
0.93
0.86
0.79
0.70
0.55
0.40
—
TSC036A 1200
Horizontal 1260
1320
1380
1440
1280
1360
1440
1520
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
4
5
3
4
5
TSC048A 1600
Horizontal 1680
1760
1840
1920
1600
1700
1800
1900
TSC060A3 2000
Horizontal 2100
2200
2300
2400
960
1020
1080
1140
—
—
0.61
0.62
0.55
0.47
0.39
0.31
0.19
0.10
—
0.86
0.80
0.73
0.65
0.56
0.43
0.28
0.18
—
0.87
0.73
0.61
0.51
0.35
0.19
0.10
—
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
TSC036A 1200
Downflow 1260
1320
1380
1440
1280
1360
1440
1520
TSC048A 1600
Downflow 1680
1760
1840
1920
1600
1700
1800
1900
1.10
1.00
0.90
0.80
0.70
0.55
0.40
0.20
—
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
TSC060A3 2000
Downflow 2100
2200
2300
2400
—
—
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
Notes:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
3. YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard motor
performancedata.
RT-PRC005-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
(3Ton)
Standard Efficiency
Performance
Data
Table PD-25 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
1-HPStandardMotor&Drive
960
—
—
—
—
—
528
557
588
622
657
0.12
0.15
0.19
0.23
0.28
599
625
652
681
713
0.16
0.19
0.23
0.27
0.33
658
685
712
738
765
0.20
0.24
0.28
0.32
0.37
713
738
764
790
817
0.24
0.28
0.33
0.38
0.43
763
786
811
838
865
0.29
0.33
0.38
0.44
0.50
810
832
856
882
909
0.33
0.38
0.43
0.49
0.56
855
876
898
923
949
0.38
0.43
0.48
0.55
0.62
898 0.43
917 0.48
939 0.54
962 0.60
987 0.68
939 0.49
957 0.54
978 0.59
1000 0.66
1024 0.74
1080
1200
1320
1440
—
552
588
0.18
0.23
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybe
necessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybe
necessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-25 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
960
978
995
1015
1036
1060
0.54
0.59
0.65
0.72
0.80
1016
1033
1051
1072
1094
0.60
0.65
0.71
0.78
0.86
1052
0.66
0.71
0.77
0.85
0.93
1086
1103
1120
1138
1160
0.72
0.78
0.84
0.91
1.00
1120
1136
1154
1171
1192
0.78
0.84
0.91
0.98
1.07
1080
1200
1320
1440
1069
1086
1106
1128
1-HPStandardMotor&FieldSuppliedHighStaticDrive(2)
Table PD-26 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
960
—
—
588
622
654
687
723
0.15
0.18
0.23
0.28
0.33
661
694
727
760
793
0.19
0.24
0.28
0.34
0.40
725
756
787
821
855
0.24
0.29
0.34
0.40
0.47
782
813
843
875
908
0.29
0.34
0.40
0.46
0.53
832
864
895
925
956
0.35
0.40
0.46
0.53
0.60
878
910
942
0.40
0.46
0.52
0.59
919
954
986
0.46
0.52
0.59
958 0.51
993 0.59
1026 0.66 1064 0.73
996 0.56
1031 0.65
1080
1200
1320
1440
531
570
610
651
0.13
0.17
0.22
0.27
973
1017
0.66 1058 0.73 1095 0.81
0.75 1088 0.82 1127 0.89
1003
0.67 1047
1-HP Standard Motor &Field Supplied High Static Drive (2)
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other
options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybe
necessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybe
necessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-26 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
960
1032 0.62
1066
1099
1133
1167
1199
0.67
0.76
0.86
0.96
1.05
1101
0.73
0.82
0.93
1.04
1.14
1133
1164
1197
1230
1263
0.79
0.89
0.99
1.11
1.22
1166
1194
1227
1261
1294
0.86
0.95
1.06
1.19
1.30
1080
1200
1320
1440
1065
1099
1132
1164
0.70
0.80
0.88
0.97
1132
1166
1200
1232
1-HPStandardMotor&FieldSuppliedHighStaticDrive(2)
38
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
(4Ton)
Standard Efficiency
Performance
Data
Table PD-27 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1280
1440
1600
1760
1920
—
—
616
663
711
758
807
0.22
0.29
0.37
0.46
0.57
677
719
764
811
859
0.26
0.33
0.42
0.52
0.64
734
772
813
856
903
0.31
0.38
0.47
0.58
0.71
787
823
860
901
945
0.37
0.44
0.53
0.64
0.77
834
871
906
944
985
0.42
0.51
0.59
0.70
0.83
878
914
951
986
1024
0.48
0.57
0.66
0.77
919
954
992
0.53
0.63
0.74
959 0.59
993 0.69
1029 0.80 1065 0.87
997 0.64
1029 0.75
596
647
701
755
0.23
0.31
0.41
0.52
1027
0.85 1066 0.93
0.97 1101 1.05
1102 1.00
1137 1.14
0.89 1063
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure.
Ourproduct’s warranty will not be affected.
Table PD-27 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1280
1440
1600
1760
1920
1033
1066
1099
1136
1172
0.70
0.81
0.93
1.08
1.23
1069
1099
1132
1168
1205
0.77
0.87
1.00
1.15
1.31
1103
0.83
0.94
1.07
1.22
1.39
1136
1165
1196
1229
—
0.89
1.01
1.14
1.29
—
1170
1196
1228
—
0.96
1.08
1.21
—
1133
1166
1200
1236
—
—
Table PD-28 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
1280
1440
1600
1760
1920
604
660
717
774
833
0.20
0.28
0.36
0.47
0.59
683
731
783
837
892
0.26
0.34
0.43
0.54
0.67
756
800
846
894
946
0.32
0.41
0.51
0.62
0.76
816
862
907
952
998
0.39
0.48
0.58
0.70
0.85
869
914
961
1006
1050
0.45
0.54
0.66
0.79
0.94
920
963
1008
1054
1100
0.51
0.61
0.73
0.87
1.03
967
0.57
0.68 1053
0.81 1095
1011
0.64
1052 0.71 1090 0.79
1009
1053
1098
1144
0.76 1094 0.83
1133 0.91
1174 1.05
1216 1.21
1259 1.39
0.89
1.04
1.21
1135 0.97
1178 1.12
1224 1.30
0.95
1.12
1139
1185
1-HPStandardMotor&FieldSuppliedHighStaticDrive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56
Notes:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other
options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure.
Our product’s warranty will not be affected.
Table PD-28 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1280
1440
1600
1760
1920
1125
1169
1211
1253
1295
0.86
0.98
1.13
1.30
1.48
1160
1204
1247
1289
—
0.94
1.07
1.21
1.39
—
1192
1.01
1.15
1.30
1.47
—
1223
1269
1312
—
1.08
1.23
1.39
—
1254
1300
1343
—
1.15
1.32
1.48
—
1237
1280
1322
—
—
—
—
—
1-HP Standard Motor & FieldSuppliedHighStaticDrive
RT-PRC005-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5Ton)
Standard Efficiency
Table PD-29— Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.70
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
1-HPStandardMotor&Drive
1011 0.77 1048 0.84 1084 0.90
0.93 1098 1.01
1111
1164
1221
1600
1800
2000
2200
2400
674
743
813
886
959
0.33
0.46
0.61
0.80
1.03
735
801
866
933
1000
0.39
0.52
0.68
0.87
1.10
786
849
914
980
1045
0.45
0.59
0.76
0.96
1.19
835
894
956
1019
1085
0.50
0.65
0.83
1.03
1.28
883
937
995
1057
1121
0.56
0.70
0.89
1.11
1.36
928
979
1035
1093
1154
0.63
0.77
0.96
1.18
1.45
972
1021
1073
1129
1188
0.85 1060
1134 1.09
1183 1.28
1233 1.50
1.02
1.25
1.53
1.10
1.33
1.60
1147 1.19
1198 1.40
—
—
—
—
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Table PD-29 — Continued
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other
options/accessories
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure.
Our product’s warranty will not be affected.
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
1117
1167
1216
—
0.97
1.16
1.37
—
1150
1199
1249
—
1.04
1.24
1.47
—
1183
1.11
1.31
—
—
—
1215
1259
—
—
—
1.18
1.39
—
—
—
1244
1289
—
—
—
1.25
1.47
—
—
—
1230
—
—
—
—
—
—
—
Table PD-30 — Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
Low Static Drive (1)
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
746
824
902
981
1061
0.39
0.54
0.72
0.93
1.19
812
883
957
1032
1109
0.47
0.62
0.80
1.03
1.29
876
940
1008
1080
1153
0.54
0.70
0.90
1.13
1.40
934
996
1059
1126
1196
0.62
0.79
0.99
1.23
1.50
985
1048
1110
1173
—
0.70
0.88
1.09
1.34
—
1032
1094
1157
1219
—
0.77
0.96
1.19
1.44
—
1074
1137
1200
—
0.85
1.05
1.28
—
1117
1176
1239
—
0.93
1.14
1.38
—
1157 1.01
1214 1.22
1276 1.47
1196 1.09
1252 1.31
1311 1.50
—
—
—
—
—
—
—
—
—
—
—
—
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Table PD-30 — Continued
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories.
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
1232
1289
—
—
—
1.18
1.41
—
1267
1323
—
1.26
1.50
—
1299
1.35
—
—
—
—
1332
—
—
—
—
1.45
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
40
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6 Ton)
Standard Efficiency
Table PD-31 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive (1)
1-HPStandardMotor&Drive
1920
2160
2400
2640
2880
—
—
—
—
—
—
—
573
602
635
670
706
0.34
0.42
0.52
0.64
0.78
630
656
682
715
749
0.41
0.50
0.60
0.72
0.86
680
706
732
758
789
0.48
0.58
0.69
0.81
0.96
726
751
777
802
830
0.55
0.65
0.77
0.91
1.06
769
792
818
845
870
0.62
0.73
0.86
1.01
1.16
811
832
856
883
909
0.70
0.81
0.95
1.10
1.27
851 0.78
871 0.90
893 1.04
919 1.20
945 1.37
889 0.87
908 0.99
930 1.13
953 1.29
979 1.48
548
584
621
660
0.35
0.45
0.56
0.69
—
569
612
0.47
0.60
Table PD-31 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM BHP
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1 HP Standard Motor & Drive
1HP Standard Motor & High Static Drive Kit
(or2HPOversizedMotor&Drive)
1920
2160
2400
2640
2880
925
944
964
986
1011
0.95
1.08
1.22
1.39
1.58
960
978
998
1019
1043
1.03
1.17
1.32
1.49
1.69
994
1.11
1.26
1.42
1.60
1.79
1026
1043
1063
1082
1103
1.19
1.36
1.53
1.71
1.90
1057
1073
1092
1112
1133
1.27
1.44
1.63
1.81
2.02
1087
1104
1123
1141
1161
1.36
1.54
1.73
1.92
2.13
1116
1133
1151
1169
1190
1.44
1.63
1.83
2.03
2.26
1144
1162
1179
1198
—
1.52
1.72
1.93
1173 1.61
1189 1.81
1206 2.03 1233 2.13
1200 1.70
1216 1.91
1010
1030
1051
1073
2.15 1225 2.26
—
—
—
—
—
—
—
2HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-32 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
1-HPStandardMotor&Drive
1920
2160
2400
2640
2880
—
—
565
609
660
710
762
0.31
0.41
0.54
0.68
0.86
627
663
701
745
795
0.39
0.48
0.60
0.76
0.94
679
716
751
788
828
0.45
0.57
0.69
0.83
1.02
726
762
798
833
869
0.52
0.64
0.78
0.93
1.11
771
804
839
875
911
0.60
0.72
0.87
1.04
1.21
814
843
877
914
950
0.69
0.80
0.95
1.13
1.33
857
883
914
949
986
0.77
0.90
1.04
1.22
1.44
899 0.85
922 0.99
950 1.14
984 1.31
1019 1.53
939 0.93
960 1.08
984 1.24
1016 1.42
1051 1.63
566
619
672
726
0.35
0.47
0.61
0.77
2-HPOversized
Motor&Drive
1HP Standard Motor & High Static Drive Kit (or 2 HP Oversized Motor & Drive)
External Static Pressure (Inches of Water)
Table PD-32 — Continued
1.10
RPM
1.20
RPM
1.30
RPM
1.40 1.50 1.60
RPM RPM RPM
1.70
RPM
1.80
RPM
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
BHP
1-HP Standard
Motor& Drive
1-HP Standard Motor & High Static Drive Kit
(or 2 HP oversized Motor& Drive)
1920
2160
2400
2640
2880
978
996
1020
1049
1081
1.02
1015
1034
1055
1081
1112
1.11
1.27
1.45
1.65
1.86
1051
1069
1089
1113
1141
1.20
1.36
1.55
1.76
1.97
1086
1103
1122
1144
1170
1.30
1.46
1.66
1.87
2.10
1118
1136
1154
1176
1199
1.39
1.56
1.76
1.98
2.22
1150
1169
1186
1207
—
1.49
1.67
1.86
2.10
—
1180
1199
1216
1237
—
1.58
1.77
1.97
2.21
—
1209
1229
1246
—
1.68
1.88
1236 1.77
1258 1.98
1263 1.86
1.17
1.35
1.53
1.74
—
—
—
—
—
—
—
—
2.08 1276 2.20
—
—
—
—
—
—
—
2-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop
duetootheroptionsaccessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular datawill not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC005-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
(6 Ton)
Standard Efficiency
Performance
Data
Table PD-33 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HPStandardMotor&Drive
1920
2160
2400
2640
2880
-
-
-
-
-
-
-
573
602
635
670
706
0.34
0.42
0.52
0.64
0.78
630
656
682
715
749
0.41
0.50
0.60
0.72
0.86
680
706
732
758
789
0.48
0.58
0.69
0.81
0.96
726
751
777
802
830
0.55
0.65
0.77
0.91
1.06
769
792
818
845
870
0.62
0.73
0.86
1.01
1.16
811
832
856
883
909
0.70
0.81
0.95
1.10
1.27
851 0.78
871 0.90
893 1.04
919 1.20
945 1.37
889 0.87
908 0.99
930 1.13
953 1.29
979 1.48
548
584
621
660
0.35
0.45
0.56
0.69
-
569
612
0.47
0.60
Table PD-33 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
2-HPStandard Motor&HighStaticDrive
1920
2160
2400
2640
2880
925
944
964
986
1011
0.95
1.08
1.22
1.39
1.58
960
978
998
1019
1043
1.03
1.17
1.32
1.49
1.69
994
1.11
1.26
1.42
1.60
1.79
1026
1043
1063
1082
1103
1.19
1.36
1.53
1.71
1.90
1057
1073
1092
1112
1133
1.27
1.44
1.63
1.81
2.02
1087
1104
1123
1141
1161
1.36
1.54
1.73
1.92
2.13
1116
1133
1151
1169
1190
1.44
1.63
1.83
2.03
2.26
1144
1162
1179
1198
-
1.52
1.72
1.93
1173 1.61
1189 1.81
1206 2.03 1233 2.13
1200 1.70
1216 1.91
1010
1030
1051
1073
2.15 1225 2.26
-
-
-
-
-
-
-
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-34 — Belt Drive Evaporator Fan Performance — 6 Ton — TSC072,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HPStandardMotor&Drive
1920
2160
2400
2640
2880
-
-
565
609
660
710
762
0.31
0.41
0.54
0.68
0.86
627
663
701
745
795
0.39
0.48
0.60
0.76
0.94
679
716
751
788
828
0.45
0.57
0.69
0.83
1.02
726
762
798
833
869
0.52
0.64
0.78
0.93
1.11
771
804
839
875
911
0.60
0.72
0.87
1.04
1.21
814
843
877
914
950
0.69
0.80
0.95
1.13
1.33
857
883
914
949
986
0.77
0.90
1.04
1.22
1.44
899 0.85
922 0.99
950 1.14
984 1.31
1019 1.53
939 0.93
960 1.08
984 1.24
1016 1.42
1051 1.63
566
619
672
726
0.35
0.47
0.61
0.77
Table PD-34 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
1.30
1.70
BHP
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM
BHP
RPM BHP
RPM BHP
2-HPStandard Motor&HighStaticDrive
2-HPStandard
Motor&Drive
1920
2160
2400
2640
2880
978
996
1.02
1.17
1.35
1.53
1.74
1015
1034
1055
1081
1112
1.11
1.27
1.45
1.65
1.86
1051
1069
1089
1113
1141
1.20
1.36
1.55
1.76
1.97
1086
1103
1122
1144
1170
1.30
1.46
1.66
1.87
2.10
1118
1136
1154
1176
1199
1.39
1.56
1.76
1.98
2.22
1150
1169
1186
1207
-
1.49
1.67
1.86
2.10
-
1180
1199
1216
1237
-
1.58
1.77
1.97
2.21
-
1209
1229
1246
-
1.68
1.88
1236 1.77
1258 1.98
1263 1.86
-
-
-
-
-
-
-
-
1020
1049
1081
2.08 1276 2.20
-
-
-
-
-
-
-
2-HPStandardMotor&HighStaticDrive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
42
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
(7½ Ton)
Standard Efficiency
Performance
Data
Table PD-35 — Belt Drive Evaporator Fan Performance — 7½ Ton — TSC090,092A3,A4,AW,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HP Standard Motor & Drive
2400
2700
3000
3300
3600
—
—
656
713
771
—
—
0.71
0.93
1.19
—
—
652
699
747
797
848
0.54
0.70
0.91
1.15
1.42
701
743
789
836
885
0.63
0.79
0.99
1.24
1.53
750
787
827
873
921
0.72
0.89
1.10
1.34
1.63
794
830
867
908
954
0.81
0.99
1.20
1.45
1.74
834
871
906
944
986
0.90
1.09
1.31
1.57
1.87
873
908
944
980
1019
0.98
1.19
1.43
1.69
1.99
909 1.08
943 1.29
980 1.54
1016 1.82
945 1.17
977 1.39
1013 1.65
1050 1.94
652
703
755
809
0.63
0.81
1.03
1.29
1052 2.13 1085 2.26
Table PD-35 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
2-HPStandard Motor&HighStaticDrive
Kit (or 3-HP Oversized Motor & Drive)
2400
2700
3000
3300
3600
980
1010
1045
1081
1116
1.27
1.49
1.76
2.06
2.39
1013
1043
1076
1111
1.37
1.60
1.87
2.18
2.53
1046
1074
1105
1141
1177
1.47
1.71
1.98
2.30
2.66
1076
1105
1134
1168
1204
1.57
1.82
2.09
2.42
2.79
1106
1134
1163
1197
1232
1.68
1.93
2.21
2.55
2.93
1137
1163
1192
1222
1257
1.78
2.04
2.34
2.66
3.05
1166
1192
1219
1249
1283
1.89
2.16
2.45
2.79 1276
3.19
1194
1219
1247
1.99
2.27
1220 2.08 1248 2.19
1246 2.39 1273 2.51
2.58 1272 2.71 1299 2.84
2.92 1301 3.06 1326 3.19
1148
1309 3.32
—
—
—
—
3-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedMotorSheave1VL40Lx7/8andFanSheaveAK71required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-36 — Belt Drive Evaporator Fan Performance — 7½ Ton — TSC090,092A3,A4,AW,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2400
2700
3000
3300
3600
—
—
673
738
805
873
942
0.56
0.76
1.00
1.29
1.63
718
773
837
903
970
0.63
0.83
1.08
1.38
1.74
769
817
870
930
996
0.72
0.92
1.17
1.47
1.84
814
862
0.82
1.02
1.26
1.57
1.94
855
904
951
1000
1052
0.90
1.13
1.38
1.68
2.04
893
941
989
0.98
1.23
1.51
1.80
2.16
929
975
1025
1073
1121
1.08
1.32
1.62
1.94
2.29
965 1.18
1009 1.42
1056 1.72
1106 2.08
1153 2.44
999 1.29
1041 1.52
1088 1.82
1136 2.19
1184 2.59
702
771
842
913
0.68
0.91
1.19
1.53
912
963
1021
1037
1086
3-HPOversizedMotor
&Drive
2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor)
External Static Pressure (Inches of Water)
Table PD-36 — Continued
1.10
1.20
BHP
1.30
1.40 1.50 1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM BHP
2-HP Standard Motor & High Static Drive Kit
(or3-HPOversizedMotor&Drive)
BHP
RPM
BHP
RPM BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
2400
2700
3000
3300
3600
1035
1073
1117
1165
1215
1.39
1.64
1.93
2.30
2.73
1070
1104
1146
1194
1242
1.50
1.76
2.05
2.41
2.86
1104
1136
1176
1220
1269
1.60
1.87
2.17
2.52
2.98
1137
1167
1205
1248
1295
1.70
1168
1198
1233
1275
1319
1.81
2.11
2.44
2.79
3.22
1201
1228
1261
1301
1345
1.92
2.22
2.56
2.93
3.35
1232
1258
1289
1326
—
2.03 1261
2.14 1291 2.26
2.46 1315 2.58 1343 2.69
2.82 1344 2.95 1372 3.08
3.22 1378 3.36
—
1319 2.38
1.99
2.31
2.66
3.10
2.34 1287
2.69 1317
3.07 1352
—
—
—
—
—
—
—
—
3-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedMotorSheave1VL40Lx7/8andFanSheaveAK71required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC005-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½ Ton)
Standard Efficiency
Table PD-37— Belt Drive Evaporator Fan Performance — 8½ Ton — TSC102A3,A4,AW, AK —DownflowAirflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSupplied
2-HP Standard Motor
&Drive
LowStaticDrive(1)
2720
3060
3400
3740
4080
—
—
—
622
671
—
—
—
0.76
0.96
—
—
612
659
706
—
—
0.68
0.86
1.08
—
—
613
650
689
729
770
0.60
0.74
0.91
1.10
1.32
655
688
724
764
804
0.72
0.85
1.02
1.23
1.46
695
725
759
795
834
0.84
0.98
1.15
1.35
1.60
733
761
792
826
864
0.95
1.11
1.29
1.49
1.74
769
796
825
857
892
1.08
1.25
1.43
1.64
1.88
802 1.21
828 1.38
856 1.58
887 1.79
920 2.04
833 1.34
861 1.52
887 1.72
916 1.96
948 2.20
611
651
693
738
0.64
0.79
0.97
1.19
Table PD-37 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
3-HPOversizedMotor&Drive
2720
3060
3400
3740
4080
863
891
917
945
976
1.48
1.66
1.87
2.11
2.38
892
919
946
974
1002
1.63
1.81
2.03
2.28
2.56
920
946
974
1001
1029
1.78
1.96
2.18
2.44
2.73
946
973
1001
1028
1055
1.93
2.12
2.34
2.61
2.91
973
999
1026
1054
1081
2.08
2.29
2.52
2.78
3.09
999
2.24
2.46
2.69
2.96
3.26
1025
1048
1074
1103
1130
2.39 1050
2.63 1072
2.86 1099
2.55 1073 2.71 1098 2.88
1024
1051
1079
1105
2.80 1096 2.98
1119 3.14
1143 3.41
3.05
3.32
—
1121 3.23
—
—
3.14
3.45
1126
—
—
—
—
—
—
—
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-38 — Belt Drive Evaporator Fan Performance — 8½ Ton — TSC102A3,A4,AW, AK —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HPStandardMotor&Drive
2720
3060
3400
3740
4080
—
—
598
654
711
770
828
0.57
0.77
1.01
1.30
1.65
646
693
743
799
857
0.67
0.86
1.10
1.40
1.76
689
735
781
830
883
0.78
0.98
1.22
1.51
1.86
734
773
819
865
913
0.90
1.10
1.36
1.65
1.99
781
812
853
899
945
1.04
1.23
1.49
1.79
2.15
826
855
886
930
977
1.18
1.39
1.62
1.94
2.30
865
897
925
960
1006
1.31
1.55
1.79
2.09
898 1.44
934 1.70
964 1.97
994 2.26
928 1.56
969 1.85
1000 2.14
1028 2.44
616
675
735
796
0.69
0.92
1.20
1.53
2.47 1034 2.63 1061 2.79
3-HPOversizedMotor&Drive
Table PD-38 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
3-HPOversizedMotor&Drive
2720
3060
3400
3740
4080
956
999
1.67
1.99
2.32
2.63
2.99
982
1.79
2.12
2.49
2.84
3.19
1008
1052
1094
1129
1157
1.91
2.26
2.64
3.03
3.40
1033
1078
1120
1158
—
2.03
2.39
2.79
3.21
—
1056
1101
1145
1185
—
2.14
2.52
2.94
3.39
—
1079
1124
1168
—
2.26
2.66
3.09
—
1102
1146
1191
—
2.38
2.79
3.24 1213
—
—
1125
1168
2.50
2.92
3.39
—
1146 2.62
1168 2.74
1026
1067
1098
1125
1188 3.05 1209 3.18
1034
1063
1093
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
44
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
Standard Efficiency
Table PD-39 — Belt Drive Evaporator Fan Performance — 10 Ton — TSC120A3,A4,AW,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
3200
3600
4000
4400
4800
—
—
—
741
803
—
—
—
1.27
1.62
—
—
715
773
833
—
—
—
—
747
803
861
—
—
1.21
1.53
1.90
—
—
718
764
814
864
916
0.97
1.20
1.49
1.82
2.20
754
797
844
894
945
1.10
1.33
1.63
1.98
2.38
789
829
874
922
972
1.25
1.48
1.77
2.13
2.55
822
860
903
948
997
1.38
1.63
1.93
2.28
2.71
856 1.53
892 1.79
932 2.09
975 2.44
887 1.67
922 1.95
960 2.27
1001 2.62
731
782
834
887
1.08
1.35
1.67
2.04
1.09
1.40
1.76
1022 2.87 1046 3.04
3-HPStandardMotor&Drive
Table PD-39 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&Drive
3200
3600
4000
4400
4800
917
951
988
1028
1071
1.82
2.11
2.44
2.81
3.23
945
979
1015
1053
1095
1.97
2.27
2.62
3.00
3.42
973
1007
1042
1078
1119
2.14
2.43
2.79
3.19
3.62
999
1033
1068
1103
1142
2.30
2.60
2.97
3.38
3.83
1024
2.47
2.78
3.15
3.57
4.04
1048
1082
1117
1152
1189
2.65
2.95
3.33
3.77
4.25
1072
1107
1142
1176
1212
2.82 1095
3.00
3.33
3.70
1117 3.17
1152 3.52
1187 3.91
1140 3.36
1173 3.71
1209 4.11
1059
1093
1128
1166
3.14
3.52
3.96
1130
1164
1198
4.15 1221 4.36 1243 4.56
4.66 1256 4.88 1277 5.09
4.46 1233
5-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. FieldSuppliedMotorSheave1VM50x7/8”,FanSheaveAK89 andBeltAX40required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-40— Belt Drive Evaporator Fan Performance — 10 Ton — TSC120A3,A4,AW,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1.72
RPM BHP
RPM BHP
3-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
—
1.13
1.52
1.99
2.56
3200
3600
4000
4400
4800
—
—
—
730
792
860
931
1002
1.00
1.32
1.73
2.24
2.84
771
829
890
955
1025
1.13
1.45
1.86
2.35
2.96
807
865
923
983
1048
1.26
1.60
2.01
2.49
3.08
844
898
956
1014
1074
1.39
1.74
2.17
2.66
3.24
886
930
986
1045
1102
1.55
1.89
2.32
2.84 1072
3.43 1131
926
965
1015
965 1.89
1000 2.06
729
802
876
950
761
833
905
977
1.22
1.63
2.12
2.70
2.06 1002 2.24 1038 2.43
2.48 1044 2.65 1077 2.85
3.01 1098 3.18
3.63 1156 3.81
1125 3.36
1181 4.00
3-HPStandardMotor&Drive
5-HPOversizedMotor&Drive
Table PD-40 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
3-HPStandardMotor&Drive
1.30
1.70
BHP
1.80
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM
BHP
RPM BHP
RPM BHP
3200
3600
4000
4400
4800
1029
1072
1111
1152
1205
2.20
2.62
3.05
3.55
4.19
1057
1106
1143
1182
2.35
2.81
3.26
3.76
1084
1134
1174
1211
1253
2.49
2.98
3.47
3.99
4.58
1108
1160
1204
1241
1280
2.63
3.15
3.68
4.21
4.81
1132
1185
1232
1270
1309
2.77
3.31
3.88
4.44
5.06
1155
1209
1260
1299
1336
2.91
3.47
4.09
4.68
5.31
1177
1231
1283
1327
1363
3.05
1198
3.18
1219 3.32 1239 3.46
3.63 1252
4.27 1306
4.91 1352
3.78 1274 3.94 1295 4.10
4.46 1327 4.63 1349 4.81
5.14 1377 5.37 1400 5.57
1229 4.39
5.56
—
—
—
—
—
—
5-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. FieldSuppliedMotorSheave1VM50x7/8”,FanSheaveAK89 andBeltAX40required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC005-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3, 4, 5Ton)
High Efficiency
Table PD-41— Direct Drive Evaporator Fan Performance — 3, 4, and 5 Ton — THC036A, THC048A, THC060A
External Static Pressure (Inches ofWater) & Motor Power (Bhp)1
Standard Motor
Low Speed
Oversized Motor
Low Speed
Unit
High Speed
ESP
High Speed
ESP
Tons Model No.
CFM
960
BHP
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.43
0.44
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.80
0.85
0.88
0.90
0.93
0.94
0.95
0.97
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.43
0.44
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.80
0.85
0.88
0.90
0.93
0.94
0.95
0.97
ESP
0.56
0.49
0.44
0.37
0.29
0.19
0.10
0.00
—
0.79
0.71
0.65
0.56
0.44
0.32
0.17
0.05
—
0.94
0.81
0.70
0.61
0.45
0.30
0.15
—
BHP
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
BHP
0.38
0.39
0.41
0.43
0.44
0.45
0.47
0.48
0.51
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
0.38
0.39
0.41
0.43
0.44
0.45
0.47
0.48
0.51
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
ESP
0.82
0.77
0.74
0.69
0.65
0.61
0.57
0.52
0.45
0.95
0.90
0.85
0.77
0.68
0.59
0.42
0.29
0.18
1.23
1.13
1.02
0.92
0.81
0.68
0.47
0.23
—
0.82
0.82
0.79
0.74
0.70
0.66
0.62
0.57
0.50
1.00
0.95
0.90
0.82
0.73
0.64
0.47
0.34
—
BHP
0.35
0.36
0.38
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
0.73
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
0.35
0.36
0.38
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
—
0.74
0.69
0.65
0.61
0.55
0.51
0.46
0.41
0.34
0.90
0.83
0.76
0.69
0.60
0.51
0.42
0.31
0.21
1.04
0.97
0.92
0.82
0.74
0.64
0.51
0.42
0.31
0.79
0.74
0.70
0.66
0.60
0.56
0.51
0.46
0.39
0.95
0.88
0.81
0.74
0.65
0.56
0.47
0.36
0.26
1.09
1.02
0.97
0.87
0.79
0.69
0.56
0.47
0.36
0.89
0.85
0.82
0.77
0.74
0.70
0.67
0.64
0.57
1.16
1.11
1020
1080
1140
1200
1260
1320
1380
1440
1280
1360
1440
1520
1600
1680
1760
1840
1920
1600
1700
1800
1900
2000
2100
2200
2300
2400
960
1020
1080
1140
1200
1260
1320
1380
1440
1280
1360
1440
1520
1600
1680
1760
1840
1920
1600
1700
1800
1900
2000
2100
2200
2300
2400
3
4
5
3
4
5
THC036A
Horizontal
1.06
1.01
0.94
0.89
0.84
0.75
0.67
1.37
1.29
1.21
1.20
1.03
0.94
0.83
0.73
0.60
0.94
0.90
0.87
0.82
0.79
0.75
0.72
0.69
0.62
1.21
1.16
1.11
1.06
0.99
0.94
0.89
0.80
0.72
1.42
1.34
1.26
1.25
1.08
0.99
0.88
0.78
0.65
THC048A
Horizontal
THC060A
Horizontal
—
—
0.56
0.54
0.49
0.42
0.34
0.24
0.15
0.05
—
0.84
0.76
0.70
0.61
0.49
0.37
0.22
0.10
—
0.99
0.86
0.75
0.66
0.50
0.35
0.20
—
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
THC036A
Downflow
THC048A
Downflow
1.28
1.18
1.07
0.97
0.86
0.73
0.52
0.28
—
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
THC060A
Downflow
—
—
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Notes:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
46
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3 Ton)
High Efficiency
Table PD-42 — Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1-HPStandardMotor&Drive
600*
720*
840*
960
1080
1200
1320
1440
—
—
—
—
—
—
552
588
—
—
—
—
—
—
0.18
0.23
449
475
501
528
557
588
622
657
0.06
0.08
0.10
0.12
0.15
0.19
0.23
0.28
525
547
572
599
625
652
681
713
0.09
0.11
0.13
0.16
0.19
0.23
0.27
0.33
593
612
634
658
685
712
738
765
0.12
0.14
0.17
0.20
0.24
0.28
0.32
0.37
653
669
690
713
738
764
790
817
0.16
0.18
0.21
0.24
0.28
0.33
0.38
0.43
707
724
742
763
786
811
838
865
0.20
0.22
0.25
0.29
0.33
0.38
0.44
0.50
757
774
791
810
832
856
882
909
0.23
0.26
0.29
0.33
0.38
0.43
0.49
0.56
802
821
837
855
876
898
923
949
0.27
0.31
0.34
0.38
0.43
0.48
0.55
0.62
845 0.31
864 0.35
881 0.39
898 0.43
917 0.48
939 0.54
962 0.60
987 0.68
885 0.36
905 0.40
922 0.44
939 0.49
957 0.54
978 0.59
1000 0.66
1024 0.74
Table PD-42 — Continued
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow960CFM
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
•
•
Electricheatersrestrictedonapplicationsbelow960CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
arerequiredonapplicationsbelow960CFM.
Notes:
1-HPStandardMotor&Drive
600*
720*
840*
960
1080
1200
1320
1440
924
943
962
978
995
1015
1036
1060
0.40
0.45
0.50
0.54
0.59
0.65
0.72
0.80
962
980
999
1016
1033
1051
1072
1094
0.45
0.50
0.55
0.60
0.65
0.71
0.78
0.86
997
0.49
0.55
0.60
0.66
0.71
0.77
0.85
0.93
1031
1050
1068
1086
1103
1120
1138
1160
0.54
0.60
0.66
0.72
0.78
0.84
0.91
1.00
1065
1082
1103
1120
1136
1154
1171
1192
0.59
0.65
0.71
0.78
0.84
0.91
0.98
1.07
1016
1034
1052
1069
1086
1106
1128
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Data does not include pressure drop due to reheat coil.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006ARequired.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
1-HP Standard Motor & Field
SuppliedHighStaticDrive(2)
Table PD-43— Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1-HPStandardMotor&Drive
600*
720*
840*
960
1080
1200
1320
1440
—
—
493
523
555
588
622
654
687
723
0.07
0.09
0.12
0.15
0.18
0.23
0.28
0.33
567
599
631
661
694
727
760
793
0.11
0.13
0.16
0.19
0.24
0.28
0.34
0.40
628
662
694
725
756
787
821
855
0.14
0.17
0.21
0.24
0.29
0.34
0.40
0.47
683
716
750
782
813
843
875
908
0.18
0.21
0.25
0.29
0.34
0.40
0.46
0.53
737
766
799
832
864
895
925
956
0.22
0.25
0.30
0.35
0.40
0.46
0.53
0.60
786
811
0.26
0.29
0.35
0.40
0.46
0.52
0.59
832
856
886
919
954
986
1017
0.30
0.34
0.39
0.46
0.52
0.59
876 0.35
899 0.39
925 0.44
958 0.51
993 0.59
918 0.40
940 0.44
965 0.49
996 0.56
1031 0.65
427
460
493
531
570
610
651
0.06
0.08
0.10
0.13
0.17
0.22
0.27
844
878
910
942
973
1003
1026 0.66 1064 0.73
0.66 1058 0.73 1095 0.81
0.75 1088 0.82 1127 0.89
0.67 1047
1-HPStandardMotor&
Field Supplied High Static Drive (2)
Table PD-43— Continued
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow960CFM
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
•
•
Electricheatersrestrictedonapplicationsbelow960CFM.
CFM
BHP
BHP
BHP
BHP
BHP
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heatersarerequiredonapplicationsbelow960CFM.
Notes:
1-HPStandardMotor&Drive
600*
720*
840*
960
1080
1200
1320
1440
958
978
1002
0.45
0.49
0.55
996
0.50
0.55
0.60
0.67
0.76
0.86
0.96
1.05
1032
0.55
0.61
0.67
0.73
0.82
0.93
1.04
1.14
1068
1087
1109
1133
1164
1197
1230
1263
0.60
0.66
0.72
0.79
0.89
0.99
1.11
1102
1121
1143
1166
1194
1227
1261
1294
0.66
0.72
0.79
0.86
0.95
1.06
1.19
1.30
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006ARequired.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
1016
1039
1066
1099
1133
1167
1199
1053
1076
1101
1132
1166
1200
1232
1032 0.62
1065
1099
1132
1164
0.70
0.80
0.88
0.97
1.22
1-HPStandardMotor&
FieldSuppliedHighStaticDrive(2)
RT-PRC005-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(4 Ton)
High Efficiency
Table PD-44 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1-HPStandardMotor&Drive
800*
960*
1120*
1280
1440
1600
1760
1920
—
—
501
539
580
626
674
724
775
825
0.09
0.13
0.17
0.23
0.30
0.38
0.48
0.59
571
609
646
686
730
776
825
875
0.13
0.17
0.21
0.27
0.34
0.44
0.54
0.66
633
668
706
744
783
825
870
918
0.16
0.21
0.26
0.32
0.39
0.49
0.60
0.73
690
721
758
796
834
872
915
959
0.20
0.25
0.31
0.38
0.45
0.54
0.66
0.79
742
771
805
843
882
919
0.25
0.29
0.36
0.43
0.52
0.61
0.72
0.86
792
819
0.29
0.34
0.41
0.49
0.58
0.68
0.79
838
864
893
927
964
1002
1040
0.34
0.39
0.46
0.54
0.64
882 0.39
906 0.44
934 0.51
967 0.60
923 0.44
947 0.50
973 0.57
1005 0.66
459
509
559
609
661
716
771
0.09
0.13
0.18
0.24
0.32
0.42
0.53
850
885
924
962
999
1039
1002 0.70 1038 0.76
0.75 1039 0.82 1076 0.89
0.87 1078 0.95
1.00 1116 1.09
958
1000
1113 1.03
1151 1.17
0.92 1078
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow1280CFM
Table PD-44 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
•
•
Electricheatersrestrictedonapplicationsbelow1280CFM.
1.10
RPM
1.50
RPM
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heatersarerequiredonapplicationsbelow1280CFM.
Notes:
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other
options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007ARequired.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure.
Our product’s warranty will not be affected.
800*
960*
1120*
1280
1440
1600
1760
1920
963
986
0.49
0.55
0.63
0.72
0.83
0.95
1.10
1.26
999
0.54
0.61
0.69
0.78
0.89
1.02
1.17
1.34
1034
1060
1084
1110
1141
1175
1211
1249
0.59
0.67
0.75
0.84
0.96
1.09
1.25
1.42
1068
0.65
0.73
0.81
0.91
1.03
1.17
1.32
—
1101
1127
1151
1176
1205
1236
—
0.70
0.79
0.88
0.98
1.10
1.24
—
1023
1048
1076
1108
1142
1179
1218
1095
1118
1143
1174
1207
1241
—
1012
1041
1074
1109
1147
1186
—
—
Table PD-45 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1-HPStandardMotor&Drive
800*
960*
1120*
1280
1440
1600
1760
1920
461
509
561
617
674
733
793
853
0.08
0.11
0.16
0.21
0.29
0.38
0.49
0.62
553
600
649
696
745
799
854
911
0.11
0.16
0.21
0.27
0.35
0.45
0.56
0.70
629
672
719
767
815
862
911
964
0.16
0.20
0.26
0.34
0.42
0.53
0.65
0.79
692
736
779
826
874
922
969
1018
0.20
0.25
0.32
0.40
0.49
0.60
0.73
0.88
745
791
836
879
925
975
1023
1069
0.25
0.30
0.37
0.46
0.56
0.68
0.82
0.97
794
841
886
930
974
1020
1069
1118
0.29
0.36
0.43
0.52
0.63
0.75
0.90
1.06
838
887
932
0.34
0.42
0.50
0.59
881
927
975
0.38
0.47
0.56
922 0.43
966 0.52
1014 0.63 1052 0.69
962 0.48
1004 0.58
976
1020
0.66 1060 0.73 1098 0.80
1020
1065
1112
1161
0.70 1064
0.77
0.91
1.07
1.25
1104 0.85
1147 0.99
1191 1.15
1239 1.34
1142 0.92
1186 1.07
1230 1.24
1275 1.43
0.83
0.98
1.15
1107
1152
1201
1-HP Standard Motor & Field
Table PD-45 — Continued
SuppliedHighStaticDrive(2)
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
1-HPStandardMotor
BHP
BHP
BHP
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow1280CFM
800*
960*
1120*
1280
1440
1600
1760
1920
1001
1040
1087
1132
1179
1223
1267
—
0.54
0.63
0.75
0.88
1.01
1.15
1.33
—
1038
1073
1119
1167
1213
1258
1301
—
0.60
0.68
0.81
0.95
1.09
1.24
1.42
—
1072
0.65
0.75
0.88
1.03
1.17
1.33
—
1108
1141
1183
1231
1277
1322
—
0.71
0.81
0.94
1.10
1.26
1.42
—
1142
1175
1213
1260
1307
—
0.78
0.88
1.00
1.17
1.34
—
•
•
Electricheatersrestrictedonapplicationsbelow1280CFM.
1108
1152
1199
1245
1291
—
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
arerequiredonapplicationsbelow1280CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
—
—
—
—
Refer to Table PD-61 to determine additional static pressure drop due to other options/
—
—
—
—
accessories
1-HP Standard Motor &
FieldSuppliedHighStaticDrive(2)
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007ARequired.
2. FieldSuppliedFanSheaveAK41required. FieldSuppliedBeltmaybenecessary.
Factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
48
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5 Ton)
High Efficiency
Table PD-46— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1-HPStandard
Motor&Drive
LowStaticDriveAccessoryKit(1)
1000*
1200*
1400*
1600
1800
2000
—
—
537
588
645
703
760
821
885
950
0.13
0.19
0.26
0.36
0.47
0.62
0.80
1.02
608
652
702
757
815
873
930
990
0.17
0.23
0.31
0.41
0.54
0.69
0.87
1.08
667
712
756
806
861
918
977
1034
0.21
0.28
0.36
0.47
0.60
0.76
0.95
1.16
721
764
808
854
904
958
1016
1074
0.25
0.33
0.41
0.52
0.66
0.83
1.03
1.25
770
811
0.30
0.38
0.48
0.58
0.72
0.90
1.10
1.00
817
856
900
944
988
1036
1089
1143
0.35
0.43
0.54
0.65
0.78
0.96 1073
1.17
1.42
861
898
941
985
1028
0.39
0.48
0.59
0.73
905 0.45
939 0.54
979 0.65
944 0.50
517
576
640
706
773
840
909
0.15
0.21
0.31
0.42
0.57
0.75
0.96
978 0.59
1017 0.71
856
899
947
998
1053
1110
1023 0.79 1060 0.86
0.86 1067 0.94
1104 1.02
1147 1.19
1191 1.39
1.02
1.24
1.50
1111 1.10
1158 1.31
2200
2400
1124
1177
—
—
—
—
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow1600CFM
Table PD-46 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
•
•
Electricheatersrestrictedonapplicationsbelow1600CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
arerequiredonapplicationsbelow1600CFM.
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
Notes:
1000*
1200*
1400*
1600
1800
2000
985
1015
1052
1093
1138
1182
1226
—
0.56
0.65
0.77
0.92
1.10
1.28
1.48
—
1021
1051
1088
1126
1171
1215
—
0.62
0.71
0.84
0.99
1.17
1.37
—
1058
0.68
0.77
0.90
1.06
1.25
1.46
—
1093
1120
1153
1190
1232
—
0.74
0.84
0.97
1.13
1.32
—
1126
1154
1185
1222
1262
—
0.80
0.91
1.04
1.20
1.39
—
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008ARequired.
2. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
1086
1121
1160
1203
1246
—
2200
2400
—
—
—
—
—
—
—
—
—
—
—
—
Table PD-47 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1-HPStandardMotor&Drive
1000*
1200*
1400*
1600
1800
2000
507
570
638
707
778
850
923
997
0.11
0.17
0.25
0.35
0.48
0.65
0.84
1.07
599
654
711
774
840
908
978
1049
0.16
0.23
0.31
0.42
0.56
0.73
0.93
1.17
671
727
0.21
0.28
0.38
0.50
0.64
0.81
1.02
1.27
735
787
844
0.26
0.34
0.44
0.57
0.72
0.90
1.12
1.37
792
843
896
0.31
0.40
0.51
0.65
0.81
1.00
1.22
1.48
843
895
946
0.37
0.46
0.58
0.72
0.89
1.09
1.32
—
889
942
993
1045
1102
1157
1211
—
0.42
0.52
0.65
931
986
0.48
0.59
971 0.54
1007 0.59
1026 0.66 1064 0.73
782
837
897
961
1028
1096
1037
0.80 1087
0.72 1078 0.79
1117 0.86
1168 1.03
1219 1.23
1274 1.47
898
953
1012
1075
1140
953
1001
1058
1111
1166
—
0.87
1.06
1.28
—
1129 0.95
1181 1.15
1237 1.37
1008
1062
1120
1183
0.98
1.19
1.43
—
1143
1198
—
2200
2400
—
—
—
—
—
—
—
—
—
—
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow1600CFM
Table PD-47 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
•
•
Electricheatersrestrictedonapplicationsbelow1600CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heatersarerequiredonapplicationsbelow1600CFM.
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008ARequired.
2. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Factorysuppliedmotors, incommercialequipment, aredefinitepurposemotors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
1000*
1200*
1400*
1600
1800
2000
1042
1099
1153
1206
1256
—
0.65
0.80
0.94
1.12
1.32
—
1078
1133
1188
1241
1291
—
0.70
0.86
1.02
1.20
1.41
—
1110
1166
1221
1275
1326
—
0.76
0.93
1.10
1.28
1.50
—
1142
1197
1253
1306
—
—
—
0.82
0.99
1.18
1.37
—
—
—
1175
1227
1284
1338
—
0.89
1.06
1.27
1.46
—
—
—
—
—
—
—
2200
2400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
RT-PRC005-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6 Ton)
High Efficiency
Table PD-48— Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW* — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
LowStaticDrive(1)
1920
2160
2400
2640
2880
—
—
—
589
634
—
—
—
0.50
0.63
—
—
588
618
652
690
728
0.35
0.44
0.54
0.67
0.82
643
672
701
734
770
0.43
0.52
0.63
0.76
0.91
693
721
750
779
810
0.50
0.60
0.72
0.85
1.01
738
765
794
822
851
0.57
0.68
0.81
0.95
1.11
782
806
834
864
892
0.65
0.76
0.90
1.05
1.22
823
847
873
901
930
0.73
0.85
0.98
1.15
1.33
862 0.81
885 0.93
909 1.08
936 1.24
965 1.44
900 0.89
922 1.02
945 1.17
971 1.34
999 1.54
564
602
642
682
0.37
0.47
0.59
0.74
Table PD-48 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
1.30
BHP
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandard
Motor & Drive
1-HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920
2160
2400
2640
2880
937
0.98
1.12
1.27
1.44
1.64
971
1.06
1.21
1.37
1.55
1.75
1004
1024
1046
1067
1092
1.14
1.30
1.47
1.65
1.86
1037
1057
1076
1098
1123
1.22
1.40
1.57
1.77
1.98
1068
1087
1106
1129
1151
1.30
1.49
1.68
1.88
2.09
1097
1.38
1.58
1.78
1.99
2.22
1127
1146
1166
1185
—
1.47
1.67
1.89
2.10 1214
—
1154
1174
1194
1.55
1.76
1.99
2.22
—
1182 1.64
1201 1.85
1220 2.08 1248 2.19
1210 1.74
1227 1.95
957
980
1004
1030
991
1117
1137
1158
1181
1013
1036
1061
—
—
—
—
—
—
—
—
—
2-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-49 — Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
LowStaticDrive(1)
1920
2160
2400
2640
2880
—
—
580
623
673
725
778
0.33
0.43
0.56
0.71
0.90
641
679
718
762
811
0.41
0.51
0.63
0.79
0.98
692
731
769
808
848
0.47
0.59
0.72
0.87
1.06
738
775
814
853
891
0.54
0.67
0.82
0.98
1.16
783
817
855
894
932
0.63
0.74
0.90
1.09
1.28
827
857
893
931
970
0.71
0.83
0.98
1.17
1.40
870
896
929
966
1004
0.79
0.93
1.08
1.26
1.49
912 0.88
935 1.02
965 1.18
1000 1.36
1037 1.59
2-HPOversized
Motor &Drive
951 0.96
974 1.12
999 1.29
1032 1.47
1068 1.69
578
633
688
743
0.37
0.49
0.64
0.81
1-HPStandardMotor&HighStatic
Drive Kit (or 2-HP Oversized Motor)
Table PD-49 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard
Motor & Drive
1-HP Standard Motor & High Static Drive Kit
(or2HPOversizedMotor&Drive)
1920
990
1.05
1026
1047
1070
1097
1130
1.14
1.31
1.50
1.71
1.93
1062
1082
1104
1129
1159
1.24
1.40
1.60
1.82
2.05
1096
1116
1137
1161
1188
1.33
1.50
1.70
1.93
2.18
1130
1.43
1.61
1.81
2.05
2.30
1160
1182
1201
1223
—
1.52
1.71
1.92
2.16
—
1190
1211
1232
1252
—
1.61
1.81
2.03 1261
2.27
—
1218
1242
1.71
1.92
1247 1.80
1271 2.03 1298 2.14
1273 1.90
2160
2400
2640
2880
1010
1035
1065
1099
1.21
1.39
1.59
1.80
1150
1168
1192
1217
2.14 1291 2.26
—
—
—
—
—
—
2-HPOversizedMotor&
FieldSuppliedDrive(2)
2-HPOversizedMotor&Drive
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
2. FieldSuppliedFanSheaveAK54andBeltAX30.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
Notes:
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty
will not be affected.
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due
tootheroptions/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
50
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½Ton)
High Efficiency
Table PD-50 — Belt Drive Evaporator Fan Performance — 7½ Ton — THC092A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1500*
1800*
2100*
2400
2700
3000
—
—
—
—
—
—
—
601
—
—
—
—
—
—
—
0.68
—
—
—
487
522
559
599
640
—
—
—
0.32
0.41
0.51
0.63
0.79
—
—
510
534
557
583
611
643
678
713
0.30
0.36
0.42
0.50
0.60
0.71
0.86
1.02
557
579
604
627
653
682
713
748
0.39
0.45
0.52
0.61
0.71
0.83
0.97
1.14
602
621
645
669
693
719
748
780
0.48
0.55
0.62
0.72
0.83
0.95
1.09
1.26
643
661
683
708
731
755
783
811
0.57
0.65
0.73
0.83
0.95
1.08
1.23
1.40
682
699
719
743
768
791
815
844
0.66
0.75
0.85
0.95
1.07
1.21
1.37
1.55
718 0.76
735 0.86
754 0.97
776 1.08
801 1.20
824 1.35
848 1.52
874 1.70
753 0.87
770 0.97
787 1.08
808 1.21
832 1.33
856 1.48
880 1.66
904 1.86
481
506
536
569
604
639
675
0.27
0.33
0.40
0.50
0.61
0.74
0.89
3300
3600
2-HPStandardMotor&Drive
Table PD-50— Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
1500*
1800*
2100*
2400
2700
3000
785
802
819
839
862
886
910
933
0.99
1.09
1.21
1.34
1.48
1.63
1.81
2.01
818
833
850
868
891
915
939
962
1.11
1.20
1.33
1.48
1.62
1.78
1.96
2.17
847
863
880
898
918
942
967
990
1.23
875
892
909
926
946
968
993
1016
1.35
1.46
1.59
1.75
1.92
2.09
2.28
2.49
903
920
936
953
971
994
1019
1042
1.48
1.59
1.72
1.89
2.07
2.25
2.45
2.66
930
947
963
980
998
1019
1043
1067
1.62
1.73
1.86
2.04
2.23
2.42
2.62
2.84
954
973
989
1006
1023
1044
1066
1091
1.74
1.87
2.00 1014
2.18 1032
2.38 1049
2.59 1067
2.79 1091
977
998
1.88
2.02
1001 2.01 1023 2.15
1023 2.17 1048 2.32
1.32
1.46
1.61
1.77
1.93
2.12
2.33
2.15 1039 2.30 1064 2.46
2.34 1056 2.49 1080 2.64
2.54 1074 2.70 1097 2.86
2.75 1092 2.93
2.98
3.21
1115 3.09
1136 3.34
1158 3.58
3300
3600
1113 3.15
1137 3.39
3.02
1114
3-HPOversizedMotor&Drive
2-HP Standard Motor & Low Static DriveAccessory Kit (1)
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow2400CFM
•
•
Electricheatersrestrictedonapplicationsbelow2400CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009ARequired.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC005-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½Ton)
High Efficiency
Table PD-51 — Belt Drive Evaporator Fan Performance — 7½ Ton — THC092A3,A4,AW—Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1500*
1800*
2100*
2400
2700
3000
3300
3600
—
—
—
502
554
605
658
711
—
—
—
0.36
0.49
0.65
0.84
1.07
—
—
509
542
568
603
644
684
728
776
0.26
0.34
0.42
0.52
0.66
0.82
1.02
1.27
558
597
628
653
686
726
767
809
0.32
0.42
0.52
0.63
0.77
0.94
1.15
1.38
601
640
678
707
732
765
805
846
0.39
0.50
0.63
0.75
0.89
1.06
1.28
1.52
640
678
718
754
780
806
840
880
0.45
0.58
0.72
0.88
1.03
1.20
1.40
1.66
678
714
754
792
824
849
876
912
0.52
0.65
0.81
0.99
1.17
1.35
1.55
1.80
715
748
787
825
863
891
916
943
0.59
0.73
0.90
1.09
1.30
1.51
1.71
1.95
750 0.67
780 0.81
817 0.99
857 1.19
895 1.42
929 1.66
955 1.89
783 0.75
811 0.89
846 1.08
886 1.30
925 1.54
962 1.80
991 2.06
472
511
552
595
644
694
746
0.24
0.33
0.43
0.56
0.73
0.93
1.18
980 2.13 1016 2.30
2-HPStandardMotor&Drive
Table PD-51 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
1500*
1800*
2100*
2400
2700
3000
3300
3600
815
842
876
913
954
992
1025
1052
0.83
0.98
1.18
1.40
1.66
1.94
2.22
2.50
847
872
0.91
1.07
1.27
1.51
1.77
2.07
2.38
2.69
876
901
931
0.99
1.16
1.36
1.61
1.89
2.20
2.53
2.88
904
929
956
1.07
1.25
1.46
1.71
2.00
2.32
2.67
3.05
932
957
982
1017
1054
1094
1132
1170
1.16
1.35
1.55
1.82
2.12
2.46
2.82
3.21
958
983
1.25
1.44
1.66
1.92
2.24
2.58
2.96
3.37
985
1008
1034
1064
1100
1138
1178
—
1.34
1.54
1.77
1009
1034
1059
1.43
1.64
1.87
2.14
2.47
2.84
1033 1.51
1058 1.74
1083 1.99
1110 2.26
1144 2.60
1181 2.97
1057 1.61
1081 1.84
1107 2.10
1132 2.37
1164 2.71
1202 3.10
904
941
1008
1040
1077
1116
1156
1193
966
991
2.04 1087
981
1006
1045
1082
1117
1030
1069
1108
1144
2.36
2.71
3.11
—
1121
1160
1200
—
1019
1055
1085
3.25 1221 3.39
—
—
—
—
—
—
—
3-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow2400CFM
•
•
Electricheatersrestrictedonapplicationsbelow2400CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009ARequired.
2. FieldSuppliedFanSheaveAK79andBeltAX38required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
52
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½ Ton)
High Efficiency
Table PD-52— Belt Drive Evaporator Fan Performance — 8½ Ton — THC102A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1700*
2040*
2380*
2720
3060
3400
—
—
—
—
—
—
641
693
—
—
—
—
—
—
0.81
1.03
—
—
—
—
481
511
545
584
626
669
713
758
0.26
0.34
0.42
0.53
0.68
0.84
1.04
1.27
533
562
592
626
665
706
749
792
0.35
0.43
0.52
0.64
0.78
0.96
1.17
1.41
578
608
637
668
703
741
781
824
0.44
0.52
0.63
0.76
0.90
1.08
1.30
1.56
621
649
678
708
740
775
813
854
0.54
0.63
0.74
0.88
1.04
1.21
1.43
1.69
661
686
716
746
775
809
845
883
0.64
0.74
0.86
1.00
1.17
1.36
1.58
1.83
700
722
751
781
810
841
875
912
0.74
0.85
0.98
1.12
1.30
1.51
1.73
1.99
736 0.85
757 0.97
784 1.11
814 1.26
843 1.44
873 1.65
905 1.89
940 2.16
770 0.96
791 1.09
815 1.24
845 1.40
875 1.58
904 1.81
935 2.06
968 2.33
496
539
583
628
677
726
0.33
0.44
0.58
0.72
0.92
1.15
3400
4080
2-HPStandardMotor&Drive
Table PD-52 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
BHP
1.80
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
1700*
2040*
2380*
2720
3060
3400
3400
4080
802
823
846
874
905
933
964
995
1.07
1.21
1.37
1.54
1.73
1.96
2.22
2.51
833
854
876
904
933
962
992
1023
1.19
1.34
1.51
1.69
1.89
2.11
2.39
2.69
864
884
906
930
960
990
1018
1048
1.32
1.47
1.65
1.84
2.05
2.27
2.55
2.86
893
913
1.45
1.60
1.79
2.00
2.20
2.44
2.72
3.05
921
940
962
1.59
1.73
1.93
2.14
2.37
2.62
2.90
3.23
948
967
988
1010
1035
1065
1095
1124
1.72
1.87
2.08
2.30
2.54
2.79
3.08
3.41
972
993
1.86
2.01
2.22 1038
2.46 1060
2.71 1083
2.97
3.26
—
998
1018
2.01
1022 2.15 1045 2.30
2.16 1043 2.32 1068 2.48
2.37 1064 2.53 1087 2.69
2.62 1084 2.78
2.89
3.15
3.45
—
934
1014
1035
1059
1089
1118
—
958
986
1016
1045
1075
983
1109 2.95
1131 3.24
1010
1041
1071
1100
1107 3.06
1134 3.34
1112
1141
—
—
—
—
—
—
—
—
—
—
—
3-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow2720CFM
•
•
Electricheatersrestrictedonapplicationsbelow2720CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009ARequired.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC005-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½ Ton)
High Efficiency
Table PD-53 — Belt Drive Evaporator Fan Performance — 8½ Ton — THC102A3,A4,AW —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&LowStaticDriveAccessoryKit(1)
1700*
2040*
2380*
2720
3060
3400
3740
4080
—
—
—
—
473
513
562
612
667
726
786
848
0.24
0.32
0.45
0.60
0.80
1.05
1.36
1.72
542
575
612
660
709
760
815
874
0.32
0.42
0.54
0.71
0.91
1.15
1.46
1.83
591
634
666
703
750
800
850
903
0.40
0.53
0.66
0.81
1.03
1.29
1.59
1.95
633
679
719
751
788
836
886
935
0.47
0.62
0.78
0.95
1.15
1.42
1.74
2.10
672
719
763
798
830
870
918
968
0.55
0.71
0.90
1.09
1.29
1.56
1.88
2.26
707
754
800
841
873
907
949
998
0.62
0.80
1.01
1.23
1.45
1.71
2.03
2.42
742
787
832
877
914
945
980
1026
0.70
0.89
1.11
1.36
1.62
1.88
2.19
774 0.77
817 0.97
863 1.21
909 1.48
951 1.77
984 2.06
807 0.86
846 1.06
893 1.32
939 1.60
983 1.92
1020 2.24
509
570
631
692
754
817
0.36
0.52
0.72
0.96
1.26
1.61
1015 2.37 1052 2.57
2.58 1054 2.75 1085 2.94
2-HPStandardMotor&Drive
3-HPOversizedMotor&Drive
Table PD-53 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
1700*
2040*
2380*
2720
3080
3400
3740
4080
839
876
920
0.94
1.16
1.42
1.72
2.06
2.41
2.77
3.14
869
903
946
1.03
1.25
1.52
1.84
2.19
2.58
2.96
3.36
898
930
973
1018
1065
1109
1149
—
1.12
1.34
1.63
1.96
2.32
2.73
3.15
—
926
957
998
1042
1090
1135
1178
—
1.21
953
984
1021
1066
1113
1159
—
1.30
1.54
1.83
2.19
2.59
3.04
—
980
1010
1047
1089
1136
1183
—
1.40
1.64
1.95
2.31
2.73
3.19
—
1005
1036
1069
1112
1158
1204
—
1.49
1.75
2.05 1093
2.43
2.86
3.33
—
1031
1061
1.59
1.86
2.16
2.55
2.99
—
1054 1.68
1084 1.96
1115 2.27
1155 2.67
1078 1.78
1108 2.07
1138 2.39
1176 2.79
1.44
1.73
2.07
2.46
2.88
3.34
—
967
994
1134
1179
—
—
—
1012
1052
1086
1117
1039
1083
1119
1151
1199 3.12 1220 3.26
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow2720CFM
•
•
Electricheatersrestrictedonapplicationsbelow2720CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009ARequired.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
54
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-54— Belt Drive Evaporator Fan Performance — 10 Ton — THC120A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HP Standard Motor & Low Static Drive Accessory Kit(1)
2000*
2400*
2800*
3200
3600
4000
—
—
—
576
638
701
764
828
—
—
—
0.57
0.78
1.04
1.36
1.74
—
—
—
—
—
—
—
—
568
606
649
697
749
803
857
913
0.43
0.56
0.71
0.90
1.14
1.44
1.79
2.18
613
650
689
734
782
834
888
942
0.53
0.67
0.83
1.03
1.27
1.58
1.95
2.36
653
691
728
770
815
863
916
970
0.64
0.78
0.95
1.17
1.41
1.72
2.10
2.53
691
728
766
804
847
894
943
996
0.75
0.90
1.08
1.31
1.57
1.87
2.25
2.70
727
763
801
839
879
923
970
1021
0.86
1.02
1.21
1.45
1.73
2.04
2.41
763 0.98
796 1.16
833 1.35
871 1.60
909 1.89
952 2.21
997 2.59
797 1.10
826 1.29
864 1.50
901 1.74
939 2.04
979 2.39
1024 2.78
564
618
675
734
795
857
0.50
0.67
0.89
1.16
1.49
1.88
607
659
714
768
825
884
0.60
0.79
1.02
1.30
1.63
2.02
4400
4800
2.86 1045 3.03 1070 3.22
3-HPStandardMotor&Drive
Table PD-54 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
BHP
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPOversizedMotor&Drive
2000*
2400*
2800*
3200
3600
4000
828
858
894
931
969
1007
1050
1095
1.22
1.43
1.65
1.89
2.21
2.57
2.97
3.42
859
888
921
959
997
1034
1075
1119
1.35
1.56
1.79
2.06
2.37
2.74
3.17
3.62
888
916
949
1.48
917
945
1.61
1.85
2.11
2.39
2.72
3.11
3.55
4.05
945
972
1.75
1.99
2.27
2.56
2.89
3.29
3.75
4.26
971
998
1.88
2.14
2.43
2.74
3.08
3.47
3.94
4.47
998
1023
1051
1084
1122
1159
1198
1235
2.03 1023
2.29 1050
2.59 1076
2.19
1048 2.35 1072 2.50
1.70
1.95
2.22
2.54
2.93
3.36
3.83
2.45 1073 2.60 1097 2.76
975
1001
1037
1074
1112
1150
1189
1027
1061
1098
1136
1173
1212
2.75
3.09
3.46
1100 2.92
1131 3.28
1166 3.65
1123 3.09
1153 3.46
1188 3.85
986
1012
1050
1087
1126
1166
2.91
3.27
3.66
4.15
1108
1145
1182
1219
1024
1062
1101
1143
3.86 1204 4.07 1226 4.28
4.34 1241 4.54 1264 4.77
4.90 1280 5.12 1300 5.32
4400
4800
4.68 1258
5-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow3200CFM
•
•
Electricheatersrestrictedonapplicationsbelow3200CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 3200 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. BAYLSDR010ARequired.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC005-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-55— Belt Drive Evaporator Fan Performance — 10 Ton — THC120A3,A4,AW —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HP Standard Motor & Low Static DriveAccessory Kit (1)
2000*
2400*
2800*
3200
3600
4000
4400
4800
—
—
—
—
—
578
640
706
777
850
925
1000
—
584
627
686
748
811
0.43
0.57
0.79
1.06
1.39
1.81
2.32
2.95
639
683
728
787
849
912
977
1046
0.53
0.70
0.90
1.19
1.54
1.95
2.46
3.07
682
734
776
824
883
0.62
0.83
1.04
1.32
1.68
2.12
2.63
3.23
721
776
822
864
916
0.71
0.94
1.19
1.47
1.82
2.28
2.81
3.42
755
812
865
906
950
1006
1067
1130
0.79
1.05
1.34
1.64
1.98
2.43 1035
2.98 1094
787
845
900
946
987
0.88
1.15
1.47
1.81
818 0.97
876 1.26
932 1.60
983 1.97
849 1.06
904 1.36
962 1.73
1015 2.13
0.48
0.67
0.93
1.27
1.70
2.21
2.83
596
671
746
822
898
974
0.58
0.85
1.18
1.59
2.09
2.69
2.16 1024 2.35 1060 2.55
2.60 1067 2.79
3.16
3.81
879
950
1023
946
977
1101 2.99
1147 3.52
1206 4.19
1008
1072
1039
1101
1121 3.33
1181 4.00
3.62
1156
5-HPOversizedMotor&Drive
Table PD-55 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
1.20
BHP
1.30
1.70
BHP
3-HPStandardMotor&Drive
1.80
1.90
2.00
CFM
RPM
BHP
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM
BHP
RPM BHP
RPM BHP
2000*
2400*
2800*
3200
3600
4000
4400
4800
877
931
989
1044
1093
1135
1177
1229
1.15
1.47
1.84
2.28
2.74
3.21
3.73
4.39
906
958
1.24
1.58
1.97
2.42
2.92
3.42
3.96
4.59
933
983
1.33
1.68
2.09
2.57
3.09
3.63
4.19
4.83
961
1.43
1.78
2.21
2.71
3.25
3.84
4.42
5.07
988
1.54
1.89
2.34
2.84
3.42
4.05
4.67
5.32
1014
1056
1110
1168
1224
1278
1324
1365
1.64
2.00
2.46
2.99
3.58
4.23
4.90
5.58
1038
1080
1132
1189
1246
1301
1351
—
1.74
2.11
2.58
3.12 1210
3.74 1268
4.41 1323
5.12 1376
1063
1103
1154
1.85
2.22
2.71
1087 1.96
1126 2.34
1176 2.83
1111 2.07
1149 2.46
1196 2.95
1008
1064
1122
1176
1227
1268
1310
1032
1087
1145
1201
1254
1297
1338
1015
1072
1124
1167
1207
1254
1040
1097
1151
1198
1239
1282
3.27 1231 3.41 1250 3.54
3.90 1289 4.06 1308 4.20
4.60 1344 4.77 1365 4.95
5.35 1398 5.56 1420 5.75
—
—
—
—
—
—
—
5-HPOversizedMotor&Drive
3-HPStandardMotor&Low
StaticDriveAccessoryKit(1)
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-56.
TableincludesDehumidification(HotGasReheatOption).
*Unitapplicationsbelow3200CFM
•
•
Electricheatersrestrictedonapplicationsbelow3200CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 3200 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. BAYLSDR010ARequired.
1. FieldSuppliedMotorSheave1VM50x7/8inch,FanSheaveAK89,andBeltAX40required
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
56
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-56— Standard Motor & Sheave/Fan Speed (Rpm)
Unit
6Turns
Open
N/A
N/A
N/A
N/A
N/A
N/A
N/A
5Turns
Open
745
833
897
723
835
787
908
4Turns
Open
819
916
987
779
891
847
969
3Turns
Open
894
1000
1077
835
946
908
1029
2Turns
Open
968
1083
1166
890
1002
968
1090
1Turn
Open
1043
1167
1256
946
1057
1029
1150
Tons
3
Model No.
T*C036A
T*C048A
T*C060A
T*C072A
TSC090,092A
T*C102A
T*C120A
Closed
1117
4
5
6
7½
8½
10
1250
1346
1002
1113
1089
1211
Factory set at 3 turns open.
Table PD-57— Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)
Tons
Unit Model
Number
THC036A
Drive Accessory
Kit
BAYLSDR006A AK84x3/4" 427
AK69x3/4" 522
BAYLSDR007A AK79x3/4" 455
AK61x3/4" 593
BAYLSDR008A AK71x3/4" 507
AK59x3/4" 614
BAYLSDR009A AK99x1"
AK79x1"
BAYLSDR009A AK99x1"
AK79x1"
Fan
5Turns
4Turns
Open
470
574
500
652
558
675
498
627
498
627
600
3Turns 2Turns
1Turn
Open
597
732
637
831
710
860
604
761
604
761
713
910
Sheave Open
Open
512
627
546
712
609
737
533
672
533
672
638
815
Open
555
679
591
771
659
798
569
716
569
716
675
862
Closed
640
784
682
890
761
921
640
806
640
806
750
958
3
4
THC048A
THC060A
THC092A
THC102A
THC120A
5
7.5
8.5
10
462
582
462
582
563
719
BAYLSDR010A
AK94x1"
AK74x1"
767
Factory set at 3 turns open.
Table PD-58— Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit
6Turns
Open
N/A
N/A
N/A
5Turns
Open
831
958
958
4Turns
Open
895
1022
1022
3Turns
Open
959
1086
1086
2Turns
Open
1022
1150
1Turn
Open
1086
1214
1214
Tons
6
6
Model No.
T*C072A3,A4,AW
TSC072AK
TSC090,092A
Closed
1150
1278
1278
7½
1150
Factory set at 3 turns open.
Table PD-59— Oversized Motor & Drive Sheave/Fan Speed (Rpm)
Unit
6Turns
Open
N/A
N/A
N/A
5Turns
Open
958
1068
958
4Turns
Open
1022
1150
1022
1200
3Turns
Open
1086
1232
1086
1275
2Turns
Open
1150
1315
1150
1Turn
Open
1214
1397
1214
1425
Tons
6
7½
8½
10
Model No.
T*C072A3,A4,AW
TSC090,T*C092A
T*C102A
Closed
1278
1479
1278
N/A
T*C120A
1050
1135
1350
Factory set at 3 turns open.
Table PD-60— Outdoor Sound Power Level - dB (ref. 10 -12 Watts)
Unit
Octave Center Frequency
Overall
Tons
3
Model No.
T*C036A
63.
86
92
90
92
94
94
90
91
92
89
92
88
91
91
94
125
83
87
84
86
87
87
94
95
95
93
96
92
95
88
89
250
81
84
78
83
83
82
90
90
91
88
92
87
90
84
87
500
80
83
77
82
82
81
87
87
88
85
89
84
87
82
85
1000
78
81
76
81
79
78
83
84
84
81
85
80
84
81
84
2000
74
76
72
75
75
74
78
79
80
76
80
75
79
76
78
4000
69
72
70
72
73
72
74
75
75
72
76
72
75
73
75
8000
dBA
83
86
82
85
84
84
88
89
90
87
91
86
89
86
88
68
69
68
69
69
69
67
68
68
66
69
65
68
67
69
TSC048A1
TSC048A3,A4,AW
THC048A
TSC060A
THC060A
TSC072A
THC072A
TSC090A
TSC092A
THC092A
TSC102A
THC102A
TSC120A
THC120A
4
5
6
7½
8½
10
*IndicatesbothStandardand
High Efficiency.
Note:
TestsfollowARI270-95.
RT-PRC005-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-61— Static Pressure Drop Through Accessories (Inches Water Column) — 3-10 Tons
Economizerwith
2 Inch
Pleated Filter 100% OA 100% RA 100% OA 100% RA
Electric Heater
Unit
ModelNo.
Standard Through
OA/RADampers2
Accessory (kW)3
5-6
Tons
CFM
Filters1
Reheat
9-15
17-36
54
Coil (WC)
Downflow
Horizontal
960
1200
1440
600
0.03
0.04
0.06
0.01
0.02
0.03
0.04
0.04
0.05
0.08
0.02
0.04
0.05
0.08
0.10
0.15
0.22
0.02
0.04
0.06
0.09
0.04
0.06
0.09
0.06
0.10
0.14
0.02
0.04
0.06
0.09
0.05
0.08
0.12
0.02
0.05
0.08
0.12
0.07
0.11
0.16
0.03
0.07
0.11
0.16
—
—
—
.01
.03
.04
.06
—
0.05
0.07
0.10
0.03
0.04
0.05
0.07
0.06
0.09
0.12
0.03
0.06
0.09
0.12
0.15
0.22
0.29
0.04
0.07
0.10
0.14
0.07
0.09
0.12
0.09
0.13
0.18
0.03
0.06
0.09
0.13
0.08
0.11
0.16
0.05
0.08
0.11
0.16
0.10
0.15
0.20
0.06
0.10
0.15
0.20
0.05
0.07
0.10
0.03
0.05
0.07
0.10
0.08
0.12
0.17
0.04
0.08
0.12
0.17
0.12
0.18
0.26
0.06
0.12
0.18
0.26
0.10
0.11
0.13
0.11
0.14
0.21
0.07
0.11
0.14
0.21
0.12
0.19
0.30
0.07
0.12
0.19
0.30
0.17
0.26
0.34
0.08
0.17
0.26
0.34
0.01
0.02
0.03
0.01
0.01
0.02
0.03
0.03
0.04
0.06
0.01
0.03
0.04
0.06
0.04
0.07
0.10
0.01
0.04
0.07
0.10
0.01
0.02
0.04
0.02
0.05
0.07
0.01
0.02
0.05
0.07
0.03
0.06
0.07
0.01
0.03
0.06
0.07
0.05
0.07
0.09
0.03
0.05
0.07
0.09
0.05
0.07
0.10
0.03
0.05
0.07
0.10
0.08
0.12
0.17
0.04
0.08
0.12
0.17
0.12
0.18
0.26
0.06
0.12
0.18
0.26
0.06
0.08
0.10
0.08
0.12
0.25
0.04
0.08
0.12
0.25
0.09
0.18
0.31
0.05
0.09
0.18
0.31
0.14
0.30
0.35
0.07
0.14
0.30
0.35
0.00
0.01
0.01
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.02
0.01
0.02
0.04
0.01
0.01
0.02
0.04
0.02
0.02
0.04
0.02
0.05
0.08
0.01
0.02
0.05
0.08
0.04
0.06
0.09
0.02
0.04
0.06
0.09
0.05
0.08
0.10
0.02
0.05
0.08
0.10
.013
.020
.029
—
.013
.020
.029
.023
.036
.052
—
.023
.036
.052
.036
.056
.081
—
.036
.056
.081
0.02
0.02
0.04
0.02
0.05
0.08
—
0.02
0.05
0.08
0.04
0.06
0.09
—
0.04
0.06
0.09
0.05
0.08
0.10
—
.016
.025
.036
—
.016
.025
.036
.029
.045
.064
—
.029
.045
.064
.045
.070
.100
—
.045
.070
.100
0.011
0.020
0.033
0.020
0.042
0.077
—
0.016
0.025
0.036
0.020
0.032
0.047
—
0.020
0.032
0.047
0.028
0.045
0.065
—
.019
.030
.043
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
TSC036A
3
960
.019
THC036A
TSC048A
1200
1440
1280
1600
1920
800
1280
1600
1920
1600
2000
2400
1000
1600
2000
2400
1920
2400
2880
2400
.030
.043
.034
.053
.077
—
.034
.053
.077
.053
.083
.120
—
.053
.083
.120
0.021
0.034
0.052
0.034
0.063
0.102
—
0.021
0.032
0.046
0.026
0.041
0.059
—
—
—
4
.02
.05
.07
.09
—
THC048A
TSC060A
THC060A
—
—
5
.03
.07
.10
.14
—
—
—
—
—
6
T*C072A
TSC090,092A 3000
3600
1500
2400
—
7½
.07
.10
.14
.19
—
THC092A
TSC102A
3000
3600
2720
3400
4080
1700
2720
3400
4080
3200
4000
4800
2000
3200
4000
4800
—
—
—
—
—
—
8½
.08
.12
.17
.23
—
—
—
0.09
0.15
0.22
0.31
0.026
0.041
0.059
0.036
0.056
0.081
—
0.036
0.056
0.081
THC102A
TSC120A
THC120A
—
0.042
0.070
0.106
—
0.042
0.070
0.106
10
0.05
0.08
0.10
0.028
0.045
0.065
Notes:
1. Tested with standard filters (3-5 tons 1” filters, 6-10 tons 2” filters). Difference in pressure drop should be considered when utilizing optional 2” pleaated filters.
2. OA = Outside Air and RA = Return Air.
3. Nominal kW ratings at 240, 480, 600 volts.
* Indicates both Standard and High Efficiency.
58
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-62— Auxiliary Electric Heat Capacity
Total2
Stage1
Stage 2
Unit
ModelNo.
kW
Input1
MBH
Output1
No. of
Stages
kW
Input1
MBH
Output1
kW
Input1
MBH
Output1
Tons
3
5.00
10.00
13.80
17.07
34.14
47.11
1
2
2
5.00
5.00
8.80
17.07
17.07
30.04
—
5.00
5.00
—
17.07
17.07
T*C036A1
6.00
12.00
17.40
5.00
20.48
40.97
59.40
17.07
1
2
2
1
6.00
6.00
8.70
5.00
20.48
20.48
29.70
17.07
—
6.00
8.70
—
—
T*C036A3, A4, AW
20.48
29.69
—
10.00
13.80
17.60
34.14
47.11
60.09
2
2
2
5.00
8.80
8.80
17.07
30.04
30.04
5.00
5.00
8.80
17.07
17.07
30.04
T*C048A1
4
5
6.00
12.00
17.40
20.48
40.97
59.40
1
2
2
6.00
6.00
8.70
20.48
20.48
29.70
—
6.00
8.70
—
20.48
29.70
T*C048A3, A4, AW
5.00
10.00
13.80
17.60
17.07
34.14
47.11
60.09
1
2
2
2
5.00
5.00
8.80
8.80
17.07
17.07
30.04
30.04
—
—
5.00
5.00
8.80
17.07
17.07
30.04
T*C060A1
6.00
12.00
17.40
23.00
20.48
40.97
59.40
78.52
1
2
2
2
6.00
6.00
8.70
20.48
20.48
29.70
48.82
—
—
T*C060A3, A4, AW
6.00
8.70
8.70
20.48
29.70
29.70
14.30
7.50
10.90
14.4
25.61
37.23
49.18
2
2
2
3.25
5.45
7.20
11.10
18.61
24.59
3.25
5.45
7.20
11.10
18.61
24.59
TSC060AK
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T*C072A3, A4, AW
6
122.90
11.30
16.90
22.60
38.60
57.72
77.18
1
2
2
11.30
11.30
11.30
38.60
38.60
38.60
—
5.60
11.30
—
19.13
38.60
TSC072AK
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T*SC090A3, A4, AW
122.90
11.30
16.90
22.60
38.60
57.72
77.18
1
2
2
11.30
11.30
11.30
38.60
38.60
38.60
—
5.60
11.30
—
19.13
38.60
7½
TSC090AK
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T*C092A3, A4, AW
122.90
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T*C102A3, A4, AW
TSC102AK
8½
122.90
16.90
22.60
18.00
57.72
77.18
61.45
2
2
1
11.30
11.30
18.00
38.60
38.60
61.45
5.60
11.30
—
19.13
38.60
—
T*C120A3, A4, AW
27.00
36.00
54.00
92.18
122.90
184.36
2
2
2
18.00
18.00
36.00
61.45
61.45
122.90
9.00
18.00
18.00
30.73
61.45
61.45
10
16.90
22.60
33.80
57.72
77.18
115.43
2
2
2
11.30
11.30
22.50
38.60
38.60
76.84
11.30
11.30
11.30
38.60
38.60
38.60
TSC120AK
Notes:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 380v, 480v. and 600v. For other than rated voltage, CAP =
2
Voltage
RatedVoltage
x rated cap.
(
)
* Indicates both Standard and High Efficiency.
RT-PRC005-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-63— Electric Heater Voltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal
Voltage
Distribution
Voltage
Capacity
Multiplier
208
230
240
380
440
460
480
540
575
600
0.751
0.918
1.000
1.000
0.840
0.918
1.000
0.810
0.918
1.000
240
380
480
600
Table PD-64 — 3-5 Tons Air Temperature Rise Across Electric Heaters (Degrees F)
3Ton
4Ton
5Ton
1
1200 CFM
1600CFM
2000CFM
SinglePhase
Stages T*C036A1
ThreePhase
T*C036A3,A4,AW
SinglePhase
T*C048A1
ThreePhase
T*C048A3,A4,AW
SinglePhase
T*C060A1
ThreePhase
kW
5.00
6.00
7.50
10.00
10.90
12.00
13.80
14.40
17.40
17.60
23.00
T*C060A3,A4,AW
TSC060AK
1
1
2
2
2
2
2
2
2
2
2
13.2
—
—
26.3
—
—
36.4
—
—
—
—
—
15.8
—
—
—
31.6
—
—
45.8
—
—
9.9
—
—
19.8
—
—
27.3
—
—
34.8
—
—
11.9
—
—
—
23.7
—
—
34.4
—
—
7.9
—
—
15.8
—
—
21.8
—
—
27.8
—
—
9.5
—
—
—
19.0
—
—
27.5
—
36.4
—
—
11.9
—
17.2
—
—
22.8
—
—
—
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =
Note:
kWx3414
1.08xCFM
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
Table PD-65 — 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)
6Ton
2000CFM
7½Ton
3000CFM
8½Ton
3400CFM
10Ton
4000CFM
1
T*C090A3, A4, AW
kW
9.00
Stages T*C072A3, A4, AW TSC072AK T*C092A3, A4, AW
TSC090AK
T*C102A3, A4, AW TSC102AK T*C120A3,A4,AW
TSC120AK
1
1
2
1
2
2
2
2
2
14.2
—
—
28.5
—
42.7
—
—
14.9
22.3
—
29.8
—
—
—
—
9.5
—
—
19.0
—
28.5
—
—
11.9
17.8
—
23.8
—
—
—
—
8.4
—
—
—
—
—
—
—
13.4
—
17.9
—
26.7
—
11.30
16.90
18.00
22.60
27.00
33.80
36.00
54.00
—
16.7
—
25.1
—
15.7
—
21.0
—
—
14.2
—
21.3
—
—
56.9
—
37.9
—
33.5
—
—
—
28.5
42.7
—
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =
Note:
kWx3414
1.08xCFM
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
* Indicates both Standard and High Efficiency.
60
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-66— Hot Gas Reheat Temperature Rise3
Leaving Evaporator Dry Bulb [F]
Tons
SCFM
600
720
840
960
1080
1200
1320
1440
35
40
45
50
55
60
65
20.3
19.4
18.5
17.6
16.7
15.8
14.9
14.0
20.0
19.1
18.2
17.3
16.4
15.5
14.6
13.8
19.6
18.7
17.9
17.0
16.1
15.2
14.3
13.5
19.2
18.3
17.5
16.6
15.7
14.9
14.0
13.1
18.8
17.9
17.1
16.2
15.4
14.5
13.6
12.8
18.4
17.6
16.7
15.8
15.0
14.1
13.3
12.4
18.0
17.2
16.3
15.5
14.6
13.8
12.9
12.0
3
Tons
4
SCFM
800
960
1120
1280
1440
1600
1760
1920
35
40
45
50
55
60
65
22.0
21.0
20.0
19.0
17.9
16.9
15.9
14.8
21.8
20.7
19.7
18.7
17.7
16.6
15.6
14.6
21.5
20.5
19.5
18.4
17.4
16.4
15.4
14.4
21.2
20.2
19.2
18.1
17.1
16.1
15.1
14.1
20.9
19.9
18.9
17.9
16.9
15.8
14.8
13.8
20.6
19.6
18.6
17.5
16.5
15.5
14.5
13.5
20.3
19.3
18.2
17.2
16.2
15.2
14.2
13.2
Tons
5
SCFM
1000
1200
1400
1600
1800
2000
2200
2400
35
40
45
50
55
60
65
23.7
22.6
21.4
20.3
19.1
17.9
16.8
15.6
23.6
22.4
21.2
20.1
18.9
17.8
16.6
15.4
23.4
22.2
21.0
19.9
18.7
17.6
16.4
15.2
23.2
22.0
20.9
19.7
18.5
17.4
16.2
15.1
23.0
21.8
20.7
19.5
18.4
17.2
16.0
14.9
22.8
21.6
20.4
19.3
18.1
16.9
15.7
14.6
22.5
21.3
20.2
19.0
17.8
16.6
15.4
14.3
Tons
7½
SCFM
1500
1800
2100
2400
2700
3000
3300
3600
35
40
45
50
55
60
65
22.0
20.2
18.5
16.7
14.9
13.1
11.4
9.6
22.9
21.0
19.2
17.3
15.5
13.7
11.8
10.0
23.8
21.9
19.9
18.0
16.1
14.2
12.3
10.3
24.7
22.7
20.7
18.7
16.7
14.7
12.7
10.7
25.6
23.5
21.4
19.3
17.3
15.2
13.1
11.1
26.5
24.4
22.3
20.1
18.0
15.9
13.7
11.6
27.5
25.3
23.1
20.9
18.7
16.5
14.3
12.2
Tons
8½
SCFM
1700
2040
2380
2720
3060
3400
3740
4080
35
40
45
50
55
60
65
22.6
20.6
18.6
16.6
14.7
12.7
10.7
8.7
23.7
21.6
19.5
17.4
15.3
13.2
11.1
9.0
24.9
22.7
20.4
18.2
15.9
13.7
11.4
9.2
26.1
23.7
21.3
18.9
16.6
14.2
11.8
9.4
27.2
24.7
22.2
19.7
17.2
14.7
12.2
9.6
28.3
25.7
23.0
20.3
17.7
15.0
12.3
9.7
29.4
26.6
23.8
21.0
18.1
15.3
12.5
9.7
Tons
10
SCFM
2000
2400
2800
3200
3600
4000
4400
4800
35
40
45
50
55
60
65
26.0
23.5
21.1
18.7
16.2
13.8
11.3
8.9
26.5
24.1
21.8
19.5
17.2
14.9
12.5
10.2
26.9
24.7
22.5
20.3
18.1
15.9
13.7
11.5
27.4
25.3
23.3
21.2
19.1
17.0
14.9
12.9
27.9
25.9
24.0
22.0
20.1
18.1
16.1
14.2
28.3
26.4
24.6
22.7
20.8
19.0
17.1
15.3
28.6
26.9
25.1
23.4
21.6
19.8
18.1
16.3
Notes:
1. Temperature rise does not account for indoor fan heat.
2.70degODAmbientTemperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.
RT-PRC005-EN
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Integrated ComfortTM System
Sensor(s) available with optional
temperature adjustment and override
buttons to provide
Programmable Night Setback
Auto or manual changeover with seven-
day programming. Keyboard selection of
ReliaTel™ Controlled Units
Zone Sensors are the building
occupant’s comfort control devices for
Precedent™ units with the Micro control:
central control
through aTrane
Integrated
Manual Changeover
Heat, Cool or Off System Switch. Fan
Auto or Off Switch.
One temperature
setpoint lever.
ComfortTM system.
Heat, Cool, Fan, Auto, or On. All
programmable sensors have System On,
Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have
one (1) Occupied, one (1) Un-occupied,
and two (2) Override programs per day.
DualThermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Humidity Sensor
Field installed, wall-mounted or duct-
mounted humidity sensor is used to
control activation of the hot gas reheat
dehumidification
Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off Switch.Two temperature
setpoint levers.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone
Optional Status
option.The
Indication LED
humidity sensor
lights, System On,
can be set for
sensors.This sensor
Heat, Cool, or
humidity levels
includes a digital
Service.
between 40% and
60% relative
display of set point
adjustment and
humidity by
space temperature
adjusting the
in F (Fahrenheit) or C
ReliaTel Options
(Celsius). Includes
Module.
FAN and SYSTEM
buttons (supports
the service functions
CO2 Sensing
of the standard
The CO2 sensor shall have the ability to
monitor space occupancy levels within
the building by
sensor). E-squared
memory stores last
Remote Sensor
programmed set points. Requires 24VAC
(Volts AC).This sensor should be utilized
with ReliaTel™ controls.
measuring the
Sensor(s) available for all zone sensors to
provide remote
parts per million
of CO2 (Carbon
sensing capabilities.
Dioxide) in the
air. As the CO2
levels increase,
the outside air
damper
modulates to
meet the CO2
space ventilation
requirements.
The CO accessory shall be available as
field ins2talled.
62
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Electromechanically Controlled
Units
Conventional Thermostats
The building occupant’s comfort control
devices for electromechanically
controlled units.
Manual Changeover
One Heat, One
CoolThermostat.
Heat, Cool or Off
System Switch.
TM
Fan Auto or On
90
70
Switch. Set Point
80
Dial. Adjustable
Heat Anticipator.
Automatic Changeover
One Heat,Two CoolThermostat. Off, Auto
System Switch. Auto/On Fan Switch.
HEAT
COOL
50 60 70 80
50 60 70 80
50 60 70 80
TM
FAN
AUTO
ON
OFF
AUTO
Programmable Electronic Night Setback
Thermostat
Heating setback and cooling setup with 7-
day, 5-1-1 programming capability.
Available in two heating/cooling or one
heating/cooling versions with automatic
changeover.
RT-PRC005-EN
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-1 — Unit Wiring — Standard Efficiency
Optional
Belt Drive Indoor Fan Motor2
Standard Indoor Fan Motor
Minimum Maximum Fuse
Oversize Indoor Fan Motor
Unit
Operating
Voltage Range
187-253
187-253
414-506
Minimum
Circuit
Maximum Fuse
Size or Maximum
Minimum
Circuit
Maximum Fuse
Size or Maximum
Unit
Circuit
Size or Maximum
Tons
3
Model No.
TSC036A1
TSC036A3
TSC036A4
TSC036AW
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
25.3
17.9
9.2
40
25
15
15
27.7
20.3
10.4
8.3
40
30
15
15
N/A
20.6
10.6
8.3
N/A
30
15
517-633
7.7
15
TSC048A1
TSC048A3
TSC048A4
TSC048AW
TSC060A1
TSC060A3
TSC060A4
TSC060AW
TSC060AK
TSC072A3
TSC072A4
TSC072AW
TSC072AK
TSC090A3
TSC090A4
TSC090AW
TSC090AK
TSC092A3
TSC092A4
TSC092AW
TSC102A3
TSC102A4
TSC102AW
TSC102AK
TSC120A3
TSC120A4
TSC120AW
TSC120AK
187-253
187-253
414-506
517-633
187-253
187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418
187-253
414-506
517-633
187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418
34.0
23.9
12.8
9.8
47.3
31.5
16.0
12.2
19.6
32.7
17.6
12.8
23.2
42.7
22.6
17.6
28.4
38.9
20.5
15.5
45.1
24.0
19.5
32.6
52.6
26.9
21.8
32.6
50
35
20
15
60
50
25
15
30
50
25
20
35
60
35
25
40
50
25
20
60
30
25
40
60
35
25
40
36.1
26.0
14.4
10.6
49.0
33.2
16.3
12.8
—
34.0
18.2
13.6
—
45.8
24.1
18.8
29.9
42.0
22.0
16.7
48.2
25.5
20.7
35.6
56.6
28.9
23.5
35.6
50
40
20
15
60
50
25
20
—
50
25
20
—
60
35
25
45
50
25
20
60
35
25
45
70
35
30
45
N/A
25.3
13.6
10.0
N/A
30.3
15.6
11.8
—
—
—
—
—
—
—
—
—
—
—
—
—
N/A
35
20
15
N/A
45
25
15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
4
5
6
7½
8½
—
—
—
—
—
—
—
10
Notes:
1. HACR breaker per NEC.
2. Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.
64
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High
Efficiency)
Table ED-2 — Unit Wiring — High Efficiency
Optional
Standard Indoor Fan Motor
Minimum Maximum Fuse
Oversize Indoor Fan Motor
Belt Drive Indoor Fan Motor2
Unit
Operating
Voltage Range
187-253
187-253
414-506
517-633
187-253
187-253
414-506
517-633
187-253
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
Minimum
Circuit
Maximum Fuse
Minimum
Circuit
Maximum Fuse
Unit
Circuit
Size or Maximum
Size or Maximum
Size or Maximum
Tons
3
Model No.
THC036A1
THC036A3
THC036A4
THC036AW
THC048A1
THC048A3
THC048A4
THC048AW
THC060A1
THC060A3
THC060A4
THC060AW
THC072A3
THC072A4
THC072AW
THC092A3
THC092A4
THC092AW
THC102A3
THC102A4
THC102AW
THC120A3
THC120A4
THC120AW
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
23.9
17.2
9.0
40
25
15
15
45
30
15
15
60
45
20
15
50
25
20
50
25
15
50
25
20
60
30
25
26.3
19.6
10.2
7.7
31.5
23.3
12.6
9.1
41.2
31.7
15.0
12.4
36.1
18.1
14.3
41.2
20.9
16.0
45.4
22.9
17.8
52.6
27.3
21.6
40
30
15
15
50
35
15
15
60
45
20
15
50
25
20
50
25
20
60
30
20
60
35
25
N/A
19.9
10.4
7.7
N/A
22.6
11.8
8.5
N/A
28.8
14.3
11.4
—
N/A
30
15
15
N/A
35
15
15
N/A
45
20
15
—
7.1
29.4
21.2
11.0
8.3
4
39.5
30.0
14.7
11.8
34.8
17.5
13.5
38.1
19.4
14.8
42.3
21.4
16.6
48.6
25.3
19.9
5
6
—
—
—
—
—
—
7½
8½
—
—
—
—
—
—
—
—
—
—
—
—
10
—
—
—
—
Notes:
1. HACR breaker per NEC.
2. Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.
RT-PRC005-EN
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) —208/230 Volts — Standard Efficiency
StandardIndoorMotor
Oversize Indoor Motor
Max Fuse Size or
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Tons
3
kW Rating1
MCA
Max Circuit Breaker2
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
3.8/5.0
7.5/10.0
10.4/13.8
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
3.8/5.0
1
2
2
1
2
2
2
1
2
2
2
25.5/28.9
48.0/55.0
65.1/74.8
34.0/34.0
49.6/56.6
66.8/76.4
84.0/96.1
47.3/47.3
52.9/59.9
70.0/79.6
87.3/99.4
40/40
50/60
70/80
50/50
50/60
70/80
90/100
60/60
60/60
80/80
90/100
28.5/31.9
51.0/58.0
68.1/77.8
36.1/36.1
52.3/59.3
69.4/79.0
86.6/98.8
49.0/49.0
55.0/62.0
72.1/81.8
89.4/101.54
40/40
60/60
70/80
50/50
60/60
70/80
90/100
60/60
60/70
80/90
90/110
TSC036A1
TSC048A1
TSC060A1
4
5
7.5/10.0
10.4/13.8
13.2/17.6
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
BAYHTRT309A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT354A
4.5/6.0
9.0/12.0
13.1/17.4
4.5/6.0
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
18.5/20.9
34.1/39.0
48.3/55.3
23.9/23.9
35.8/40.6
49.9/56.9
31.5/31.5
39.0/43.9
53.1/60.1
67.8/76.9
32.7/33.4
53.1/60.4
76.6/87.5
100.1/114.5
42.7/42.7
54.8/62.0
78.3/89.1
101.8/116.1
38.9/38.9
54.8/62.0
78.3/89.1
101.8/116.1
45.1/45.1
54.8/62.0
78.3/89.1
101.8/116.1
58.6/65.9
82.1/93.0
105.8/120.0
152.5/141.7
25/25
35/40
50/60
35/35
40/45
50/60
50/50
50/50
60/70
70/80
50/50
60/70
80/90
110/125
60/60
60/70
80/90
110/125
50/50
60/70
80/90
110/125
60/60
60/70
80/90
110/125
60/70
90/100
110/125
175/150
21.5/23.9
37.1/42.0
51.3/58.3
26.0/26.0
38.4/43.3
52.5/59.5
33.2/33.2
41.1/46.0
55.3/62.3
69.9/79.0
34.0/35.0
54.8/62.0
78.3/89.1
101.8/116.1
45.8/45.8
58.6/65.9
82.1/93.0
105.6/120.0
42.0/42.0
58.6/65.9
82.1/93.0
105.6/120.0
48.2/48.2
58.6/65.9
82.193.0
30/30
40/45
60/60
40/40
40/45
60/60
50/50
50/50
60/70
70/80
50/50
60/70
80/90
110/125
60/60
60/70
90/100
110/125
50/50
3
4
TSC036A3
TSC048A3
9.0/12.0
13.1/17.4
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
6.8/9.0
5
6
TSC060A3
TSC072A3
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
TSC090A3
TSC092A3
TSC102A3
TSC120A3
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
7½
8½
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
60/70
90/100
110/125
60/60
13.5/18.0
20.3/27.0
27.0/36.0
13.5/18.0
20.3/27.0
27.0/36.0
40.6/54.0
60/70
90/100
110/125
70/80
90/100
125/125
175/150
105.6/120.0
63.6/70.9
87.1/98.0
110.6/125.0
157.5/146.7
10
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
66
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection)—380, 460 Volts — Standard Efficiency, continued
StandardIndoorMotor
Max Fuse Size or
Max Circuit Breaker2
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Tons
MCA
MCA
Max Circuit Breaker2
380 Volts Three Phase
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRT427A
BAYHTRT436A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
7.5
2
2
2
1
2
2
1
2
2
2
2
2
2
2
19.6
26.1
32.8
27.6
38.3
49.0
28.4
38.3
49.0
38.8
49.0
40.1
50.9
72.3
30
30
35
35
40
50
40
40
50
40
50
45
60
80
—
—
—
—
—
—
—
—
—
—
—
45
45
60
45
60
45
60
80
5
TSC060AK
TSC072AK
TSC090AK
10.9
14.4
11.3
16.9
22.6
11.3
16.9
22.6
16.9
22.6
16.9
22.6
33.8
6
—
29.9
40.1
50.9
40.1
50.9
43.6
54.4
75.8
7½
8½
10
TSC102AK
TSC120AK
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRT409A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
6.0
12.0
17.4
6.0
12.0
17.4
6.0
12.0
17.4
23.0
9.0
18.0
27.0
36.0
9.0
18.0
27.0
36.0
9.0
18.0
27.0
36.0
9.0
18.0
27.0
36.0
18.0
27.0
36.0
54.0
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
10.4
19.4
27.5
12.8
20.1
28.3
16.0
21.6
29.8
38.3
17.6
30.3
43.8
57.3
22.6
31.0
44.5
58.0
20.5
31.0
44.5
58.0
24.0
31.0
44.5
58.0
32.9
46.4
59.9
70.8
15
20
30
20
25
30
25
25
30
40
25
35
45
60
35
35
45
60
25
35
45
60
30
35
45
60
35
50
60
80
11.9
20.9
29.0
14.4
22.1
30.3
16.3
22.0
30.1
38.6
18.2
31.0
44.5
58.0
24.1
32.9
46.4
59.9
22.0
32.9
46.4
59.9
25.5
32.9
46.4
59.9
35.4
48.9
62.4
73.3
15
25
30
20
25
35
25
25
35
40
25
35
45
60
35
35
50
60
25
35
50
60
35
35
50
60
40
50
70
80
3
4
TSC036A4
TSC048A4
5
6
TSC060A4
TSC072A4
TSC090A4
TSC092A4
TSC102A4
TSC120A4
7½
8½
10
Notes:
1. Heater kW ratings are at 208/240 for 208/230V, unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — Standard Efficiency, continued
StandardIndoorMotor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Max Circuit Breaker2
Max Fuse Size or
Max Circuit Breaker2
Tons
MCA
MCA
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW54A
6.0
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
2
2
2
8.6
15
20
25
15
20
25
15
20
25
35
20
25
35
50
25
25
40
50
20
25
40
50
25
40
50
30
40
50
60
9.3
15
20
25
15
20
25
20
20
25
35
20
25
40
50
25
30
40
50
20
30
40
50
30
40
50
30
40
50
70
3
4
TSC036AW
TSC048AW
12.0
17.4
6.0
12.0
17.4
6.0
12.0
17.4
23.0
9.0
18.0
27.0
36.0
9.0
15.8
22.3
9.8
16.6
23.1
10.6
17.3
23.8
12.8
17.8
24.3
31.0
14.0
24.8
35.6
46.4
18.8
26.3
37.1
47.9
16.7
26.3
37.1
47.9
26.3
37.1
47.9
28.4
39.3
50.0
58.8
16.3
22.8
12.2
17.1
23.6
30.3
13.0
23.8
34.6
45.4
17.6
24.8
35.6
46.4
15.5
24.8
35.6
46.4
24.8
35.6
46.4
26.3
37.1
47.9
56.6
5
6
TSC060AW
TSC072AW
TSC090AW
TSC092AW
18.0
27.0
36.0
9.0
7½
18.0
27.0
36.0
18.0
27.0
36.0
18.0
27.0
36.0
54.0
8½
TSC102AW
TSC120AW
10
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
68
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-4 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — Standard Efficiency
Optional Belt Drive Indoor Motor
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Tons
3
kW Rating1
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TSC036A1
TSC048A1
TSC060A1
4
5
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
4.5/6.0
9.0/12.0
13.1/17.4
4.5/6.0
1
2
2
1
2
2
1
2
2
2
21.9/24.3
37.5/42.4
51.6/58.6
25.3/25.3
37.5/42.4
51.6/58.6
30.3/30.3
37.5/42.4
51.6/58.6
66.3/75.4
30/30
40/45
60/60
35/35
40/45
60/60
45/45
45/45
60/60
70/80
3
4
TSC036A3
TSC048A3
9.0/12.0
13.1/17.4
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
5
TSC060A3
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
6.0
12.0
17.4
6.0
1
2
2
1
2
2
1
2
2
2
12.1
21.1
29.3
13.6
21.1
29.3
15.6
21.1
29.3
37.8
15
25
30
20
25
30
25
25
30
40
3
4
TSC036A4
TSC048A4
12.0
17.4
6.0
12.0
17.4
23.0
5
TSC060A4
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
6.0
12.0
17.4
6.0
1
2
2
1
2
2
1
2
2
2
9.3
15
20
25
15
20
25
15
20
25
30
3
4
TSC036AW
TSC048AW
16.6
23.1
10.0
16.6
23.1
11.8
16.6
23.1
29.8
12.0
17.4
6.0
12.0
17.4
23.0
5
TSC060AW
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High
Efficiency)
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 208/230 Volts — High Efficiency
StandardIndoorMotor
Oversize Indoor Motor
Max Fuse Size or
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Tons
3
kW Rating1
MCA
Max Circuit Breaker2
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
3.8/5.0
7.5/10.0
10.4/13.8
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
3.8/5.0
1
2
2
1
2
2
2
1
2
2
2
25.5/28.9
48.0/55.0
65.1/74.8
29.4/30.5
49.6/56.6
66.8/76.4
84.0/96.1
39.5/39.5
52.9/59.9
70.0/79.6
87.3/99.4
40/40
50/60
70/80
45/45
50/60
70/80
90/100
60/60
60/60
80/80
90/100
28.5/31.9
51.0/58.0
68.1/77.8
31.5/33.1
52.3/59.3
69.4/79.0
86.6/98.8
41.2/41.2
55.0/62.0
72.1/81.8
89.4/101.5
40/40
60/60
70/80
50/50
60/60
70/80
90/100
60/60
60/70
80/90
90/100
THC036A1
THC048A1
THC060A1
4
5
7.5/10.0
10.4/13.8
13.2/17.6
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
BAYHTRT309A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT309A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT354A
4.5/6.0
9.0/12.0
13.1/17.4
4.5/6.0
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
18.5/20.9
34.1/39.0
48.3/55.3
21.2/22.5
35.8/40.6
49.9/56.9
30.0/30.0
39.0/43.9
53.1/60.1
67.8/76.9
34.8/34.8
53.1/60.4
76.6/87.5
100.1/114.5
38.1/38.1
54.8/62.0
78.3/89.1
101.8/116.1
42.3/42.3
54.8/62.0
78.3/89.1
101.8/116.1
58.6/65.9
82.1/93.0
105.6/120.0
152.5/141.7
30/30
35/40
50/60
30/30
40/45
50/60
45/45
45/45
60/70
70/80
50/50
60/70
80/90
110/125
50/50
60/70
80/90
110/125
50/50
21.5/23.9
37.1/42.0
51.3/58.3
23.3/25.1
38.4/43.3
52.5/59.5
31.7/31.7
41.1/46.0
55.3/62.3
69.9/79.0
35.7/35.7
54.8/62.0
78.3/89.1
101.8/116.1
44.2/44.2
58.6/65.9
82.1/93.0
105.6/120.0
44.2/44.2
58.6/65.9
82.1/93.0
105.6/120.0
63.6/70.9
87.1/98.0
110.6/125.0
157.5/146.7
30/30
40/45
60/60
35/35
40/45
60/60
45/45
45/50
60/70
70/80
50/50
60/70
80/90
110/125
50/50
60/70
90/100
110/125
50/50
3
4
THC036A3
THC048A3
9.0/12.0
13.1/17.4
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
6.8/9.0
5
6
THC060A3
THC072A3
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
7½
8½
THC092A3
THC102A3
THC120A3
13.5/18.0
20.3/27.0
27.0/36.0
6.8/9.0
13.5/18.0
20.3/27.0
27.0/36.0
13.5/18.0
20.3/27.0
27.0/36.0
40.6/54.0
60/70
80/90
60/70
90/100
110/125
70/80
90/100
125/125
175/150
110/125
60/70
90/100
110/125
175/150
10
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
70
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
(High
Efficiency)
Electrical
Data
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 460 Volts — High Efficiency, continued
StandardIndoorMotor
Oversize Indoor Motor
To Use
With
Heater
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Max Circuit Breaker2
Max Fuse Size or
Max Circuit Breaker2
Tons
ModelNo.
MCA
MCA
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
BAYHTRT409A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT409A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
6.0
12.0
17.4
6.0
12.0
17.4
6.0
12.0
17.4
23.0
9.0
18.0
27.0
36.0
9.0
18.0
27.0
36.0
9.0
18.0
27.0
36.0
18.0
27.0
36.0
54.0
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
2
10.4
19.4
27.5
11.1
20.1
28.3
14.7
21.6
29.8
38.3
17.5
30.3
43.8
57.3
19.4
31.0
44.5
58.0
21.4
31.0
44.5
58.0
32.9
46.4
59.9
70.8
15
20
30
15
25
30
20
25
30
40
25
35
45
60
25
35
45
60
25
35
45
60
35
50
60
80
11.9
20.9
29.9
13.1
22.1
30.3
15.0
22.0
30.1
38.6
18.1
31.0
44.5
58.0
20.9
32.9
46.4
59.9
22.9
32.9
46.4
59.9
35.4
48.9
62.4
73.3
15
25
30
15
25
35
20
25
35
40
25
35
45
60
25
35
50
60
30
35
50
60
40
50
70
80
3
4
5
THC036A4
THC048A4
THC060A4
6
THC072A4
THC092A4
THC102A4
THC120A4
7½
8½
10
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High
Efficiency)
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — High Efficiency, continued
StandardIndoorMotor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Max Circuit Breaker2
Max Fuse Size or
Max Circuit Breaker2
Tons
MCA
MCA
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW54A
6.0
1
2
2
1
2
2
1
2
2
2
1
1
2
2
1
2
2
1
2
2
1
2
2
2
8.6
15
20
25
15
20
25
15
20
25
35
20
25
35
50
25
40
50
25
40
50
30
40
50
60
9.3
15
20
25
15
20
25
15
20
25
35
20
25
40
50
30
40
50
30
40
50
30
40
50
70
3
4
THC036AW
THC048AW
12.0
17.4
6.0
12.0
17.4
6.0
12.0
17.4
23.0
9.0
18.0
27.0
36.0
18.0
27.0
36.0
18.0
27.0
36.0
18.0
27.0
36.0
54.0
15.8
22.3
9.1
16.6
23.1
10.1
17.3
23.8
12.4
17.8
24.3
31.0
14.3
24.8
35.6
46.4
26.3
37.1
47.9
26.3
37.1
47.9
28.4
39.3
50.0
58.8
16.3
22.8
11.8
17.1
23.6
30.3
13.5
23.8
34.6
45.4
24.8
35.6
46.4
24.8
35.6
46.4
26.3
37.1
47.9
56.6
5
6
THC060AW
THC072AW
7½
THC092AW
THC102AW
THC120AW
8½
10
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
72
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High
Efficiency)
Table ED-6 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — High Efficiency
Belt Drive Indoor Motor
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Tons
3
kW Rating1
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
N/A
N/A
N/A
N/A
N/A
1N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
THC036A1
THC048A1
THC060A1
4
5
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
4.5/6.0
9.0/12.0
13.1/17.4
4.5/6.0
1
2
2
1
2
2
1
2
2
2
21.9/24.3
37.5/42.4
51.6/58.6
22.6/24.3
37.5/42.4
51.6/58.6
28.8/28.8
37.5/42.4
51.6/58.6
66.3/75.4
25/25
40/45
60/60
35/35
40/45
60/60
45/45
45/45
60/60
70/80
3
4
THC036A3
THC048A3
9.0/12.0
13.1/17.4
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
5
THC060A3
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
6.0
12.0
17.4
6.0
1
2
2
1
2
2
1
2
2
2
12.1
21.1
29.3
12.1
21.1
29.3
14.3
21.1
29.3
37.8
15
25
30
15
25
30
20
25
30
40
3
4
5
THC036A4
THC048A4
THC060A4
12.0
17.4
6.0
12.0
17.4
23.0
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
6.0
12.0
17.4
6.0
1
2
2
1
2
2
1
2
2
2
9.3
15
20
25
15
20
25
15
20
25
30
3
4
THC036AW
THC048AW
16,6
23.1
9.3
16.6
23.1
11.4
16.6
23.1
29.8
12.0
17.4
6.0
12.0
17.4
23.0
5
THC060AW
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-7 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized
StandardEvaporatorFanMotor
OversizedEvaporatorFanMotor
Amps
FLA
Amps
Unit
Tons
3
Model No.
T*C036A1
T*C036A3
T*C036A4
T*C036AW
T*C048A1
T*C048A3
T*C048A4
T*C048AW
T*C060A1
T*C060A3
T*C060A4
T*C060AW
TSC060AK
T*C072A3
T*C072A4
T*C072AW
TSC072AK
T*C090A3
T*C090A4
T*C090AW
TSC090AK
T*C092A3
T*C092A4
T*C092AW
T*C102A3
T*C102A4
T*C102AW
TSC102AK
T*C120A3
T*C120A4
T*C120AW
TSC120AK
No.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208-230
208-230
460
Phase
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
HP
.33
.33
.33
.33
.60
.60
.60
.60
.90
.90
.90
.90
1.00
1.00
1.00
1.00
2.0
FLA
2.30
2.30
1.10
1.10
3.60
3.60
1.70
1.50
6.20
6.20
2.90
2.10
4.3
LRA
3.90
3.90
2.00
1.80
6.60
6.60
2.80
2.40
14.0
14.0
6.60
4.90
No.
1
1
1
1
1
1
1
1
1
1
1
1
—
1
1
1
—
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208-230
208-230
460
Phase
1
HP
.50
LRA
9.80
9.80
5.20
3.60
4.70
4.70
2.30
1.70
5.70
5.70
3.30
2.30
7.90
7.90
3.2
1
1
1
1
1
1
1
1
1
1
1
—
.50
.50
.50
.80
..80
.80
.80
1.00
1.00
1.00
1.00
—
575
460
208-230
208-230
460
208-230
208-230
460
13.60
13.60
7.20
4
5
6
575
575
5.80
208-230
208-230
460
575
380
208-230
460
575
208-230
208-230
460
575
—
16.40
16.40
8.20
2.4
—
5.00
—
8.3
5.00
2.50
1.70
4.9
32.20
16.10
13.20
35.0
48.00
24.00
18.20
35.0
48.00
24.00
18.20
48.00
24.00
18.20
35.0
83.00
42.00
31.00
51.1
208-230
460
575
3
3
3
—
2.00
2.00
2.00
—
6.30
3.10
2.50
—
48.00
24.00
18.20
—
380
3
—
208-230
460
575
3
3
3
3
2.00
2.00
2.00
2.0
6.30
3.10
2.50
4.9
208-230
460
575
3
3
3
3
3.00
3.00
3.00
3.0
9.40
4.60
3.70
6.4
83.00
42.00
31.00
51.1
380
380
7½
8½
10
208-230
460
575
208-230
460
575
3
3
3
3
3
3
3
2.00
2.00
2.00
2.00
2.00
2.00
2.0
6.30
3.10
2.50
6.30
3.10
2.50
4.9
208-230
460
575
208-230
460
575
3
3
3
3
3
3
3
3.00
3.00
3.00
3.00
3.00
3.00
3.0
9.40
4.60
3.70
9.40
4.60
3.70
6.4
83.00
42.00
31.00
83.00
42.00
31.00
51.1
380
380
208-230
460
575
3
3
3
3
3.00
3.00
3.00
3.0
9.40
4.60
3.70
6.4
208-230
460
575
3
3
3
3
5.00
5.00
5.00
5.0
13.40
6.60
5.40
10.8
112.00
56.00
44.0
380
380
66.5
Table ED-8 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Optional Belt Drive
Amps
Unit
Tons
3
ModelNo.
No.
Volts
Phase
HP
FLA
LRA
T*C036A3
T*C036A4
T*C036AW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.00
2.50
1.70
32.20
16.10
13.20
T*C048A3
T*C048A4
T*C048AW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.00
2.50
1.70
32.20
16.10
13.20
4
5
T*C060A3
T*C060A4
T*C060AW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.00
2.50
1.70
32.20
16.10
13.20
* Indicates both Standard and High Efficiency.
74
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-9— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency
CompressorMotors
Condenser Fan Motors
Amps
1
Amps
Unit
ModelNo.
Tons
3
No.
Volts
Phase
HP2
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
TSC036A1
TSC036A3
TSC036A4
TSC036AW
TSC048A1
TSC048A3
TSC048A4
TSC048AW
TSC060A1
TSC060A3
TSC060A4
TSC060AW
TSC060AK
TSC072A3
TSC072A4
TSC072AW
TSC072AK
TSC090A3
TSC090A4
TSC090AW
TSC090AK
TSC092A3
TSC092A4
TSC092AW
TSC102A3
TSC102A4
TSC102AW
TSC102AK
TSC120A3
TSC120A4
TSC120AW
TSC120AK
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
1
2
2
2
1
208-230
208-230
460
1
3
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.1
3.1
3.1
3.1
3.9
3.9
3.9
3.9
5.1
5.1
5.1
5.1
5.1
6
6
6
6
7.5
7.5
7.5
7.5
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
17.2
11.3
6.0
104.0
74.0
37.6
30.4
131.0
91.0
46.0
37.0
144.0
128.0
63.0
49.0
64
156
75
54
70
181.5
95.0
69.0
106.3
91/77
50/39
37/31
128/77
63/39
49/31
64/39
128/91
63/46
49/37
64/54
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.20
.20
.20
.20
.33
.33
..33
.33
.33
.33
.33
.33
.40
.70
.70
.70
.75
.70
.70
.70
.75
.70
.70
.70
.75
.75
.75
.75
.75
.75
.75
.75
1.5
1.5
.6
2.5
2.5
1.3
575
4.9
.5
1.2
208-230
208-230
460
22.7
14.6
7.9
2.0
2.0
1.2
6.6
6.6
2.5
1.5
6.6
6.6
2.5
1.5
4.3
9.30
5.80
3.60
7.7
9.30
5.80
3.60
7.7
9.30
5.80
3.60
9.4
6.8
6.2
7.7
9.4
6.8
6.2
7.7
4
5
575
6.1
.7
208-230
208-230
460
575
380
208-230
460
575
380
208-230
460
575
380
208-230
460
575
208-230
460
575
380
208-230
460
31.3
18.6
9.5
2.0
2.0
1.2
.7
1.1
7.5
11.4
19.0
10.1
7.7
12.2
26.0
13.6
10.9
16.4
3.85
2.50
1.54
2.5
3.85
2.50
1.54
2.5
3.85
2.50
1.54
4.0
2.8
2.4
2.5
4.0
2.8
2.4
2.5
6
7½
8½
4/2.8
4/2.8
4/2.8
3450 14.7/10.3
3450
3450
7.6/5.4
5.8/4.2
5.1/2.8 3450 18.6/10.3
5.1/2.8 3450 10.0/5.4
5.1/2.8 3450
5.1/2.8 3450 12.1/6.6
5.1/3.9 3450 18.6/14.7
5.1/3.9 3450
5.1/3.9 3450
5.1/3.9 3450
8.2/4.2
10
9.5/7.4
7.8/5.8
11.5/9.0
575
380
Notes:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.
RT-PRC005-EN
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-10 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency
CompressorMotors
Condenser Fan Motors
Amps1
Unit
Amps1
RLA LRA
88.0
Tons
3
ModelNo.
No.
Volts
Phase
HP2
RPM
No.
Phase
HP
FLA
LRA
THC036A1
THC036A3
THC036A4
THC036AW
THC048A1
THC048A3
THC048A4
THC048AW
THC060A1
THC060A3
THC060A4
THC060AW
THC072A3
THC072A4
THC072AW
THC092A3
THC092A4
THC092AW
THC102A3
THC102A4
THC102AW
THC120A3
THC120A4
THC120AW
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
208-230
208-230
460
1
3
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2.8
2.8
2.8
2.8
3.5
3.5
3.5
3.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
16.1
10.7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.20
.20
.20
.20
.33
.33
.33
.33
.33
.33
.33
.33
.70
.70
.70
.70
.70
.70
.75
.75
.75
.75
.75
.75
1.5
1.5
2.5
2.5
1.3
77.0
39.0
31.0
5.8
4.4
0.6
0.5
2.0
2.0
1.2
0.7
2.0
2.0
1.2
0.9
3.85
2.50
1.54
3.85
2.50
1.54
4.0
2.8
2.4
4.0
2.8
2.4
575
1.2
208-230
208-230
460
19.0
12.5
6.5
4.9
25.0
17.4
7.8
6.2
109.0
88.0
44.0
34.0
169.0
124.0
59.6
49.4
156
6.6
6.6
2.5
1.5
6.6
6.6
2.5
1.5
9.30
5.80
3.60
9.30
5.80
3.60
9.4
6.8
6.2
9.4
6.8
6.2
4
575
208-230
208-230
460
575
208-230
460
575
208-230
460
575
208-230
460
5
20.7
6
10
75
8.2
54
3.5/3.3 3450
3.5/3.3 3450
3.5/3.3 3450
3.9/3.5 3450
3.9/3.5 3450
3.9/3.5 3450
4.8/3.5 3450
4.8/3.5 3450
4.8/3.5 3450
12.4/12.4
6.4/5.8
4.8/4.8
14.7/12.4
7.1/6.4
5.4/4.8
88/88
44/44
34/34
91/88
50/44
37/34
7½
8½
575
208-230
460
17.3/12.4 124/88
10
9.0/6.4
7.1/4.8
59.6/44
49.4/34
575
Notes:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.
Table ED-11— Electrical Characteristics — Power Exhaust
Tons
6-10
6-10
6-10
Volts
208-230
460
Phase
HP
RPM1
1075
1075
1075
FLA
LRA
16.3
6.8
1
1
1
0.87
0.87
0.87
5.7
3.3
2.3
575
5.4
Note:
1. Twospeed.
76
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Jobsite
Connections
Zone Sensors —Typical Number OfWires
DISCONNECT
SWITCH
(BYOTHERS)
A— ManualChangeover ....................................... 4
Manual/AutoChangeover ............................... 5
Manual/AutoChangeoverwith
StatusIndicationLED’s ........................... 10
Programmable Night Setback with
ZONESENSOR
ORTHERMOSTAT
StatusIndicationLED’s ............................. 7
ROOFTOP
UNIT
Thermostats—TypicalNumberofWires
A — 3 wires, 24-volts, Cooling Only
4 wires, 24-volts, with Electric Heat
B— 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes. Wiring shown dotted is to be furnished and installed
bythecustomer.
RT-PRC005-EN
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5 Tons)
All dimensions are in inches/millimeters.
3 - 5 Tons Standard Efficiency
3 and 4 Tons High Efficiency
32 1/4"
819 MM
4 1/4"
108 MM
23 9/16"
598 MM
42 1/4"
69 7/8"
1073 MM
1775 MM
5 9/16"
141 MM
5 5/8"
143 MM
7 5/8"
194 MM
9 5/8"
244 MM
44 1/4"
1124 MM
36 1/4"
921 MM
5 Tons High Efficiency
4 1/4"
108 MM
23 9/16"
598 MM
42 1/4"
69 7/8"
1073 MM
1775 MM
5 9/16"
141 MM
5 5/8"
143 MM
7 5/8"
194 MM
9 5/8"
244 MM
44 1/4"
1124 MM
78
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5 Tons)
All dimensions are in inches/millimeters.
Downflow Airflow Supply/Return
Through the Base Utilities
Horizontal Airflow Supply/Return
Unit Clearance and Roof Opening
RT-PRC005-EN
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5 Tons)
All dimensions are in inches.
Downflow Duct Connections — Field Fabricated
80
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10 Tons)
All dimensions are in inches.
6 Tons Standard and High
Efficiency 7½ Tons Standard
Efficiency
7½ Tons High Efficiency
8½ and 10 Tons Standard and High Efficiency
RT-PRC005-EN
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10 Tons)
All dimensions are in inches.
6-10 Tons — Downflow Airflow Supply and Return;
Through the Base Utilities
Return
Supply
6-10 Tons — Horizontal Airflow Supply and Return
6-10 Tons — Unit Clearance and Roof
Opening
82
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10 Tons)
All dimensions are in inches.
6-10 Tons — Roof Curb
857
857
ALL FLANGES 1 1/4” (31 MM)
6-10 Tons — Downflow Duct
Connections — Field Fabricated
RT-PRC005-EN
83
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5Tons Options/
Accessories)
All dimensions are in inches.
Economizer , Manual or Motorized Fresh Air Damper
Barometric Relief Damper Hood
17 7/8"
16"
22 1/4"
(454 MM)
(406 MM)
(565 MM)
Swing Diameter for Hinged Doors Option
See Page 79 for Through the Base Utilities Information
84
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10 Tons Options/
Accessories)
All dimensions are in inches.
6-10 Tons — Power Exhaust
6-10 Tons — Economizer and Barometric
Relief Damper Hoods
17"
432 MM
34 5/8"
879 MM
21 3/8"
543 MM
6-10 Tons — Swing Diameter for Hinged
Door(s) Option
See Page 82 for Through the Base Utilities Information
RT-PRC005-EN
85
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
Table W-1— Maximum Unit and Corner Weights (Lbs) And Center of Gravity Dimensions (In.)
MaximumWeights(Lbs)
Corner Weights (Lbs)1
Center of Gravity (In.)
Unit
ModelNo.
Tons
Shipping2
501
Net
A
B
C
D
Length
31
Width
19
TSC036A
409
132
104
79
94
3
4
5
6
THC036A
TSC048A
THC048A
TSC060A
THC060A
518
526
560
543
610
426
434
468
451
518
139
140
146
149
165
108
110
113
114
124
84
91
95
94
32
33
31
31
31
19
19
20
18
19
97
88
111
99
105
124
TSC072A
THC072A
824
861
681
718
236
235
177
182
119
128
150
173
38
38
21
22
TSC090A
TSC092A
THC092A
897
899
1000
754
756
857
257
261
289
188
202
222
129
131
148
180
162
197
37
39
38
22
21
21
7½
8½
TSC102A
THC102A
978
1036
835
893
281
294
223
233
149
159
181
207
40
39
21
22
TSC120A
THC120A
1023
1125
880
982
298
323
238
253
158
178
187
229
40
39
21
22
10
Notes:
1. Corner weights are given for information only.
2. Weights are approximate.
Table W-2 — Factory-installed Options Net Weights (Lbs)1,2
NetWeight
Accessory
Economizer
Barometric Relief
Powered Exhaust
Motorized Outside Air Damper
Manual Outside Air Damper
Roof Curb
3-5Tons
26
7
—
20
16
70
5
6-10Tons
36
10
80
30
26
115
8
Oversized Motor
Belt Drive Motor
31
7
5
12
10
38
8
15
5
—
7
5
20
12
38
13
30
5
Smoke Detector, Return
Smoke Detector, Supply
Coil Guards
Hinged Doors
Powered Convenience Outlet
Through the Base Electrical
Electric Heaters
Unit Mounted Circuit Breaker
Unit Mounted Disconnect
Novar Control
5
8
5
8
Dehumidification (Hot Gas Reheat) Coil
15
25
Notes:
1.Weights for options not listed are < 5 lbs.
2.Net weight should be added to unit weight when ordering factory-installed accessories.
86
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
General
UnitTop
Evaporator and Condenser Coils
The units shall be convertible airflow.The
operating range shall be between 115°F
and 0°F in cooling as standard from the
factory for units with microprocessor
controls. Operating range for units with
electromechanical controls shall be
between 115°F and 40°F. Cooling
The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasket-
sealed. The ribbed top adds extra
strength and prevents water from
pooling on unit top.
Internally finned, 5/16” copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity.The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig.The condenser coil
shall have a patent pending 1+1+1 hybrid
coil designed with slight gaps for ease of
cleaning. A removeable, reversible,
double-sloped condensate drain pan with
provision for through the base
Filters
performance shall be rated in accordance
with ARI testing procedures. All units shall
be factory assembled, internally wired,
fully charged with R-22, and 100 percent
run tested to check cooling operation, fan
and blower rotation, and control
sequence before leaving the factory.
Wiring internal to the unit shall be colored
and numbered for simplified
identification. Units shall be UL listed and
labeled, classified in accordance to UL
1995/CAN/CSA No. 236-M90 for Central
Cooling Air Conditioners. Canadian units
shall be CSA Certified.
One inch, throwaway filters shall be
standard on all 3-5 ton units.The filter rack
can be converted to two inch capability.
Two inch filters shall be factory supplied
on all 6-10 ton units. Optional 2-inch
pleated filters shall be available.
condensate drain is standard.
Compressors
Outdoor Fans
All 3 ton standard units shall have direct-
drive, hermetic, reciprocating type
compressors.The reciprocating type
compressors have a centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
internal temperature, and current-
sensitive motor overloads shall be
included for maximum protection.
Compressors shall have internal spring
isolation and sound muffling to minimize
vibration transmission and noise. Low
pressure switches shall be standard.
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position.The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.
Casing
Indoor Fan
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
All 3-5 ton 3-phase units offer a choice of
direct-drive, FC, centrifugal fans or belt
driven, FC centrifugal fans with
adjustable motor sheaves. 3-5 ton direct
drive oversized motors shall be available
for high static operations. All 6-10 ton
units shall have belt drive motors with an
adjustable idler-arm assembly for quick-
adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. All indoor fan motors meet the
U.S. Energy Policy Act of 1992 (EPACT).
weather-resistant baked enamel finish.
Unit’s surface shall be tested 1000 hours
in a salt spray test in compliance with
ASTM B117. Cabinet construction shall
allow for all maintenance on one side of
the unit. Service panels shall have lifting
handles and be removed and reinstalled
by removing only a single fastener while
providing a water and air tight seal. All
exposed vertical panels and top covers in
the indoor air section shall be insulated
with a cleanable foil-faced, fire-retardent
permanent, odorless glass fiber material.
The base of the unit shall be insulated
with 1/2 inch, 1 pound density foil-faced,
closed-cell material. All insulation edges
shall be either captured or sealed.The
unit’s base pan shall have no penetrations
within the perimeter of the curb other
than the raised 11/ inch high downflow
supply/return ope8nings to provide an
added water integrity precaution, if the
condensate drain backs up.The base of
the unit shall have provisions for forklift
and crane lifting, with forklift capabilities
on three sides of the unit.
3 ton high efficiency and 4-10 ton
standard and high efficiency units shall
have direct-drive, hermetic, scroll type
compressors with centrifugal type oil
pumps. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Internal overloads
shall be provided with the scroll
compressors. Crankcase heaters shall be
included on 7½ ton standard efficiency
units.
Refrigerant Circuits
Each refrigerant circuit offers a choice of
independent fixed orifice expansion
devices or thermal expansion valve.
Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.
RT-PRC005-EN
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Controls
Powered or Unpowered Convenience
Outlet
Factory Installed Options
Black Epoxy Pre-Coated Coils
The black epoxy coils have a thermoset
vinyl coating that is bonded to the
aluminum fin stock prior to the fin-
stamping process.The pre-coated coils
are an economical option for protection in
mildly corrosive environments.
Unit shall be completely factory-wired
with necessary controls and contactor
pressure lugs or terminal block for power
wiring. Unit shall provide an external
location for mounting a fused disconnect
device.
This is a GFCI, 120v/15amp, 2 plug,
convenience outlet, either powered or
unpowered.When the convenience outlet
is powered, a service receptacle
disconnect will be available.The
convenience outlet is powered from the
line side of the disconnect or circuit
breaker, and therefore will not be
affected by the position of the disconnect
or circuit breaker.This option can only be
ordered when theThrough the Base
Electrical with either the Disconnect
Switch or Circuit Breaker option is
ordered.
A choice of microprocessor or
electromechanical controls shall be
available.
Dehumidification Option
The dehumidification (hot gas reheat)
option shall provide increased
Microprocessor controls provide for all 24
volt control functions.The resident control
algorithms shall make all heating, cooling,
and/or ventilating decisions in response
to electronic signals from sensors
dehumidification.The option shall consist
of a hot-gas reheat coil located on the
leaving air side of the evaporator coil
prepiped and circuited.
The option shall be equipped with
crankcase heater(s), low pressure
switch(es), Frostat™, and a thermostatic
expansion valve(s) (TXV) as standard.
measuring indoor and outdoor
Supply and/or Return Air Smoke
Detector
temperatures.The control algorithm
maintains accurate temperature control,
minimizes drift from set point, and
With this option, if smoke is detected, all
unit operation will be shut down. Reset
will be manual at the unit. Return Air
Smoke Detectors require minimum
allowable airflow when used with certain
models. See the Installation, Operation,
and Maintenance (IOM) manual for the
models affected and the minimum
allowable airflow required.This option is
available for microprocessor controlled
units.
provides better building comfort. A
centralized Microprocessor shall provide
anti-short cycle timing and time delay
between compressors to provide a
higher level of machine protection.
High Pressure Cutout
This is offered for units that do not have
High Pressure cutout as standard. All 3-
phase units with scroll compressors
include High Pressure Cutout as
standard.
24-volt electromechanical control circuit
shall include control transformer and
contactor pressure lugs for power wiring.
Units shall have single point power entry
as standard.
Hinged Access Doors
Sheet metal hinges are available on the
Filter/Evaporator, Supply Fan/Heat, and
the Compressor/Control Access Doors.
Thermal ExpansionValve
All units shall have a short orifice
refrigerate control metering device. For
more exact refrigerant flow, when using
unit in low airflow applications, aThermal
ExpansionValve option shall be available.
Novar Return Air Sensor
This option, when used in conjunction
with Novar Controls, will contain a factory
provided and wired zone temperature
sensor located in the return air stream.
Through the Base Electrical Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
Novar Unit Controls
Optional Novar rooftop unit controls shall
be installed and tested. The Novar
electronic thermostat module will
interface to the unit microprocessor and
will control the unit to the desired stage of
cooling or heating.
installation of liquid-tight conduit and an
external field-installed disconnect switch.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
88
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Through the Base Electrical with Circuit
Breaker
Discharge Air Sensing
LonTalk® Communication Interface
This option shall be provided to allow the
unit to communicate as aTracer™LCI-R
device or directly with generic LonTalk
Network Building Automation System
Controls.
This option provides true discharge air
sensing in heating models.This sensor is
a status indicator readable through
Tracer™ orTracker™. This option is
available for microprocessor controlled
units.
This option is a thermal magnetic, molded
case, HACR Circuit Breaker with
provisions for through the base electrical
connections.The circuit breaker will be
installed in a water tight enclosure in the
unit with access through a swinging door.
Wiring will be provided from the switch to
the unit high voltage terminal block.The
circuit breaker will provide overcurrent
protection, be sized per NEC and UL
guidelines, and be agency recognized by
UL/CSA.
Oversized Motors
Direct drive oversized motors shall be
available for high static applications.
Economizer
This accessory shall be available with or
without barometric relief.The assembly
includes fully modulating 0-100 percent
motor and dampers, minimum position
setting, preset linkage, wiring harness
with plug, spring return actuator and
fixed dry bulb control.The barometric
relief shall provide a pressure operated
damper that shall be gravity closing and
shall prohibit entrance of outside air
during the equipment “off” cycle.
Optional solid state or differential
enthalpy control shall be available for
either factory or field installation.The
economizer arrives in the shipping
position and shall be moved to the
operating position by the installing
contractor.
Reference or Comparative Enthalpy
Reference Enthalpy is used to measure
and communicate outdoor humidity.The
unit receives and uses this information to
provide improved comfort cooling while
using the economizer. Comparative
Enthalpy measures and communicates
humidity for both outdoor and return air
conditions, and return air temperature.
The unit receives and uses this
Through the Base Electrical with
Disconnect Switch
This 3-pole, molded case, disconnect
switch with provisions for through the
base electrical connections are available.
The disconnect switch will be installed in
the unit in a water tight enclosure with
access through a swinging door.Wiring
will be provided from the switch to the
unit high voltage terminal block.The
switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized
per NEC and UL guidelines but will not be
used in place of unit overcurrent
protection.
information to maximize use of
economizer cooling, and to provide
maximum occupant comfort control.
Reference or Comparative Enthalpy
option shall be available when a factory
or field installed Downflow Economizer is
ordered.This option is available on all
downflow models.
Electric Heaters
Electric heat modules shall be available
for installation within basic unit. Electric
heater elements shall be constructed of
heavy-duty nickel chromium elements
internally delta connected for 240 volt,
wye connected for 480 and 600 volt.
Staging shall be achieved through
ReliaTel™. Each heater package shall
have automatically reset high limit
control operating through heating
element contactors. All heaters shall be
individually fused from the factory, where
required, and shall meet all NEC and CEC
requirements when properly installed.
Power assemblies shall provide single-
point connection. Electric heat modules
shall be UL listed or CSA certified.
Tool-less Hail Guards
Tool-less, hail protection quality coil
guards are available for condenser coil
protection.
Two-Inch Pleated Filters
Two inch pleated media filters shall be
available on all models.
Trane Communication Interface
Factory or Field Installed
Options
This option shall be provided to interface
ReliaTel™ controlled units with theTrane
Integrated ComfortTM systems.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available to achieve active fan failure
indication and/or clogged filter indication.
These indications will be registered with
either a zone sensor with status indication
lights or an Integrated Comfort™ System.
This option is available for
microprocessor controlled units.
Frostat
Differential Pressure Switches
This option is to be utilized as a safety
device.The Frostat opens when
temperatures on the evaporator coil fall
below 10°F. The temperature will need to
rise to 50°F before closing.This option
should be utilized in low airflow or high
outside air applications.
These sensors allow individual fan failure
and dirty filter indication for
microprocessor controlled units.The fan
failure switch will disable all unit functions
and “flash” the Service LED on the zone
sensor.The dirty filter switch will light the
Service LED on the zone sensor and will
allow continued unit operation.
RT-PRC005-EN
89
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Humidity Sensor
Thermostat
Field Installed Options
CO2 Sensing
This duct-mounted humidity sensor is
used to control activation of the hot gas
reheat dehumidification option.The
humidity sensor can be set for humidity
levels between 40% and 60% relative
humidity by adjusting the ReliaTel Options
Module.
Two stage heating and cooling operation
or one stage heating and cooling shall be
available in either manual or automatic
changeover. Automatic programmable
electronic with night set back shall also be
available.
The CO2 sensor shall have the ability to
monitor space occupancy levels within
the building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.
Ventilation Override Accessory
Manual Outside Air Damper
This rain hood and screen shall provide
up to 50 percent outside air.
With theVentilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors.This sensor
includes a digital display of set point
adjustment and space temperature in F
(Fahrenheit) or C (Celsius). Includes FAN
and SYSTEM buttons (supports the
service functions of the standard sensor).
E-squared memory stores last
Motorized Outside Air Dampers
Pressurization, and Exhaust.The
Manually set outdoor air dampers shall
provide up to 50 percent outside air. Once
set, outdoor air dampers shall open to set
position when indoor fan starts.The
damper shall close to the full closed
position when indoor fan shuts down.
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.The ventilation override accessory
shall be available as field installed.
Powered Exhaust
Zone Sensor
programmed set points. Requires 24VAC
(Volts AC).This sensor should be utilized
with ReliaTel™ controls.
The powered exhaust, available for 6-10
ton units, shall provide exhaust of return
air, when using an economizer, to
maintain better bulding pressurization.
This control shall be provided to interface
with the Micro equipped units and shall
be available in either manual, automatic
programmable with night setback, with
system malfunction lights, or remote
sensor options.
DualThermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Remote Potentiometer
The minimum position setting of the
economizer shall be adjusted with this
accessory.
Roof Curb
High Static Drive
The roof curb shall be designed to mate
with the unit’s downflow supply and
return and provide support and a water
tight installation when installed properly.
The roof curb design shall allow field-
fabricated rectangular supply/return
ductwork to be connected directly to the
curb. Curb design shall comply with
NRCA requirements. Curb shall be
shipped knocked down for field assembly
and shall include wood nailer strips.
The high static drive option shall allow the
standard motor on the 6 and 7½ ton units
to operate with improved external static
capabilities.
Humidity Sensor
This wall-mounted humidity sensor is
used to control activation of the hot gas
reheat dehumidification option.The
humidity sensor can be set for humidity
levels between 40% and 60% relative
humidity by adjusting the ReliaTel Options
Module.
90
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
*High Efficiency Units only
Literature Order Number
RT-PRC005-EN
File Number
PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-08-04
PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-05-04
05-04 Webb/Mason 08-04 Electronic Only
Supersedes
Trane
Stocking Location
A business ofAmerican Standard Companies
For more information contact your local dealer
(distributor), local district office, or e-mail us at
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Taurus Group Hair Dryer Airindb User Manual
Technicolor Thomson DVD Recorder DTH8555 X User Manual
Technicolor Thomson Network Router TG576 v7 User Manual
Technicolor Thomson Universal Remote VPH6920F User Manual
Tekkeon Battery Charger IA1000 User Manual
Teledex Telephone BTX4750 User Manual
Toshiba Flat Panel Television 24SL415U User Manual
Trane Air Conditioner PRC001 EN User Manual
ViewSonic Power Supply PS500B User Manual
Weber Gas Grill 2000 LX User Manual