| THE CHOICE OF MOUNTING SITE(Please note the following matters and obtain permission from customer before installation.)   FOR SERVICE PERSONNEL ONLY   WARNING   WARNING   • The unit should be mounted at stable, non-vibratory location   which can provide full support to the unit.   • The Outdoor unit must be mounted at a location which can   support heavy weight. Otherwise, noise and vibration will   increase.   CAUTION   No nearby heat source and no obstruction near the air   CAUTION   • • • • • • • Do not expose the unit under direct sunshine or rain.   Besides, ventilation must be good and clear of obstruction.   The air blown out of the unit should not point directly to   animals or plants.   outlet is allowed.   The clearance distances from top, right and left are   specified in figure below.   The location must be convenient for water drainage and   pipe connection with the Outdoor unit.   To avoid interference from noise, please place the unit and   its remote controller at least 1m from the radio and   television.   To avoid any error in signal transmission from the remote   controller, please put the controller far away from high-   frequency machines and high-power wireless systems.   The clearances of the unit from top, left, right and front are   specified in figure below. At least two of the above sides   must be open air.   The installation height should be at least 2,300 mm or more   from the floor.   Be sure that the hot air blown out of the unit and noise do   not disturb the neighbourhood.   Do not install at a location where there is flammable gas,   steam, oil and smoke.   • • • • SAFETY PRECAUTION   • • The location must be convenient for water drainage.   Place the Outdoor unit and its connecting cord at least 1 m   away from the antenna or signal line of television, radio or   telephone. This is to avoid noise interference.   • Read the safety precautions carefully before operating the unit.   Names of Indoor Components   • The contents of this section are vital to ensure safety. Please pay special attention to the following sign.   WARNING .......... Incorrect methods of installation may cause death or serious injury.   CAUTION .......... Improper installation may result in serious consequence.   Make sure to connect earth line.   The Length of Indoor Unit   Connecting Cord   No.   Item   Qty   Hanger   above   0.9 m   above   1.6 m   1 1 This sign in the figures indicates prohibition.   Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of   the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.   Figure showing the Installation   of Indoor and Outdoor Unit.   Screw for Hanger   When the power is   supplied from the   indoor unit, pull the   power cable from the   cable drawer at the   right or left side of   the indoor unit.   2 6 above   50mm   WARNING   (4.1 x 32)   • • • • Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the   installation work yourself.   Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause   water leakage, electric shock and fire.   Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may   collapse and impose danger.   Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing   with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and   fire may occur due to the use of low quality wire or improper work.   Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the   conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the   terminal base. Improper insertion and loose contact may cause over-heating and fire.   Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or   stronger vibration may occur.   Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.   When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)   does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally   which could result in a rupture and injury.   Holder for Remote   Controller   2 1 above 50mm   above 50mm   3 4 5 1 2 2 Cable drawer (right side)   Be sure to   completely   seal any gap   with putty.   AAA size Battery   Direction of Piping   Backward piping   from left   2,300 mm or more   Screw for holder of   Remote Controller   • • Used in   6 Connection   (3.1 x 16)   horizontal piping   There are 6 directions allowed,   namely, backward piping,   backward piping from left,   horizontally piping from right,   horizontally piping from left,   vertically down from right, vertically   down from left.   Holder   • • 6 7 8 9 1 1 1 1 7 4 5 Remote Controller   Insulation sheet   Bush   3 Plug (Procure locally)   • • • • Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may   occur.   After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the   room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.   Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner   technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.   Be sure to connect the earth line from the power supply wire to the outdoor unit and between   the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the   telephone unit. Improper earthing may cause electric shocks.   Dimension of Mounting   Stand of the Outdoor unit   (unit : mm)   The indoor piping should be   insulated with the enclosed   insulation pipe. (If the insulator is   insufficient, please use commercial   products.)   50   Mounting   Stand   • The refrigerating machine oil is   easily affected by moisture. Use   caution to prevent water from   entering the cycle.   12   35   500   125   • • When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.   If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a   pressure in the freezing cycle system will build up steeply, causing an explosion or injury.   When installing the unit, be sure to install the refrigerant pipe before starting the compressor.   If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the   pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.   • • The difference in height between   the indoor and outdoor unit   should be kept below 10m.   The connecting pipe, no matter   big or small, should all be   insulated with insulation pipe and   then wrapped with vinyl tape.   (The insulator will deteriorate if   it is not wrapped with tape).   above 200mm   Drain Pipe   above 50 mm when   installed on the   ceiling of balcony   0 1 above 50mm   give clearance   as wide as   possible   Switch Cover   Purifying Filter   CAUTION   A B 1 1 • • A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the   outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.   Without a circuit breaker, the danger of electric shock exists.   Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire   if flammable gas leaks around it.   above   200mm   The connection of insulated drain   hose.   above 100mm   above 300mm   Inner diameter 16mm   Please use insulated drain hose for   the indoor piping (commercial   product)   The components of 9 & 0 are included   in the package of the outdoor unit.   • • Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.   An IEC approved power cord should be used. Power cord type: NYM.   INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES   2 Installation Of The Indoor Unit   1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe   • The refrigerating pipe should be adjusted to fit into   Drain hose   Cutting Low Cover bush   the hole on the wall and then ready for further   CAUTION   • While installing the pipe from the right, left or   bottom side, use a knife to cut openings as   shown in figure. Then smoothen the edges of   openings with a file.   connection.   • The terminals of 2 connected pipes must be covered   • The draining of the water container inside the Indoor unit can be done from the left.   Therefore the hanger must be fixed horizontally or slightly tilted towards the side of   drain hose. Otherwise, condensed water may overflow the water container.   Connecting   cord   with insulator used for terminal connection. Then the   pipes are wrapped with insulation pipe.   • Connect the connecting cord after removing low   cover.   Openings   Pipe   Direct Mounting On The Wall   • Please use hidden beams in the wall to hold the hanger.   (Refer to "CONNECTION OF POWER CORD")   • After adjustment, fit the connecting cord and pipes   into the space available under the unit. Use holder to   hold them tight.   • Holder can be attached at the either of 2 places.   Please select the easier position.   Openings   Visible outline of the   450mm   ¡ Preparation   PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)   400mm   outdoor unit   316mm   20mm   125mm   41mm   125mm   44mm   Insulation pipe (must be wrapped withHolder   vinyl tape at every 120 mm)   • Connect connecting cord.   • Pull out the pipe, connecting cord and drain hose.   Wall hole   Installation   THE CONNECTION OF REFRIGERATING PIPE DURING   42mm   45mm   Connecting cords, pipe and   drain hose must be laid   together with Vinyl tape.   • Insert the pipe through the wall hole.   ¡ The upper part of the Indoor unit is hanged on the   hanger.   ™ The projection at the lower part of the Indoor unit is   hooked onto the hanger.   THE INSTALLATION OF INDOOR UNIT   45mm   ø65mm   The end of the refrigerating pipes are at   390mm   530mm   780mm   ø65mm   Drain Hose   65mm   10mm   Preparation To Install Refrigerating Pipes   • The refrigerating pipes and connecting cord   transform and are attached.   Drain Hose   locations marked with “M” symbol.   Wall hole   Level   2 Screw for Hanger   Pipe   1 Hanger   Drain hose   Cable   Screw the hanger at the   1 Hanger   1 Hanger   ¡ positions possibly near the   upper and lower hooks where   the indoor unit is hung. Use 4 or   more screws to fix the hanger.   0.85m   below   5mm   Drain layout of   backward piping   Lift the body   of the unit   upwards and   then force it   downwards.   Please bend at a small   radius to form an arc   Installation   Refrigerating   Pipe   Line   Weight   Wall hole   Hang the indoor unit onto the hanger. Use the temporary stand Projection   at the back of the Indoor unit to push its lower part 15cm   forwards.   • Place the drain hose through the hole on the wall.   • Wrap the refrigerating pipes with insulation pipe after   connecting refrigerating pipe.   • Connect the connecting cord after removing low cover.   (Refer to "Connection of Power Cord")   • After adjustment, the connecting cord and refrigerating pipes   Procedures of Installation and Precautions   • Procedures to fix the hanger.   ™ Hook   Protection   Pipe   Connecting Cord   Drain Hose   Projection   1.Drill holes on wall.   (As shown below)   2.Push plug into the holes. 3.Fix the hanger on wall with   ™ Preparation   PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)   (As shown below)   4.1 x 32 screw.   (As shown in figure below)   about 15cm   Wall   Plug   (Procure   locally)   Changed of Drain Hose and Installation Procedures.   Exchange the location of drain hose and drain cap while installing the pipe from the left side as   shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.   1 Hanger   2 Screw   Ceiling   • are placed into the space available under the Indoor unit.   • The projection of Indoor unit must hook to the hanger.   Protection   pipe   above 50mm   • Please use pliers to pull out the drain cap.   (This is an easier way to remove the drain   cap).   CAUTION   Insufficient insert may   result in water leakage.   Wall hole   Drain hose   32mm   Refrigerating   pipe   Connecting   cord   Wall   Pull this to the front during the   connection of refrigerating   pipe to ease task.   Pipe   Drain hose   Cable   Heat   insulation pipe   Connecting cord   • Procedures to fix the holder of remote control.   Drain layout of backward piping from left   4.1 x 32 screw   Connected   section   Holder   1.Drill holes on wall.   (As shown below)   2.Push plug into the holes.   (As shown below)   3 Heat Insulation and Finish of the Piping   Rib at the Indoor unit   Wall   • The connected terminals should be completed sealed   with heat insulator and then tied up with rubber strap.   • Do not tie the terminals with the tape too tight.   If any clearance or over-tightening may cause   condensation.   • Please tie the pipe and power line together with vinyl   tape as shown in the figure showing the installation of   Indoor and Outdoor units.   Insulation material for pipe   connection   Insulating   section of the   drain hose end   Drain cap   Drain Hose   3 Remote   Control   5 Screw   Plug   (Procure locally)   • • Remove low cover   Insert drain cap up to the   location securely till the   cap stops.   Holder   • Push the pipe deeply until the insulating   section of the drain hose end gets over the   rib at the indoor unit side.   Sleeve of   protection pipe   20mm   Putty   • To enhance the heat insulation and to prevent water   condensation, please cover the outdoor part of the   drain hose and pipe with insulation pipe.   Drain cap   Wall Penetration and Installation of Protection Pipe   • Drill a ø65mm hole on wall which is   slightly tilted towards the outdoor side.   Drill the wall at a small angle.   • Cut the protection pipe according to the   wall thickness.   • Empty gap in the sleeve of protection   pipe should be completely sealed with   putty to avoid dripping of rain water into   the room.   • Please ensure smooth flow of water   when installing the drain hose. Improper   installing may wet your funiture.   • An IEC approved power cord should be   used. Power cord type: NYM.   Indoor   Outdoor   2-5mm   • Completely seal any gap with putty.   CAUTION   WARNING   Putty   • The rubber strap used for fixing the insulator   should not be tied with great force. Otherwise,   this will damage heat insulation and causes   water condensation.   • Please pull the lower part of the Indoor unit   outwards to check if the unit is hooked onto   the hanger. Improper installation may cause   vibration and noise.   Be sure that the wire is not   in contact with any metal in   the wall. Please use the   protection pipe as wire   passing through the hollow   part of the wall so as to   prevent the possibility of   damaged by mouse.   Seal with   putty   Seal with   putty   4 Installation of Drain Hose   Pipe   Rubber strap tied   with great force   CAUTION   Be sure that the drain hose is   not loosely connected bend or   proper condition like left figure.   Ditch   Condensed   water pond   Protection   pipe   WALL   Bending upwards   Condensed water   pond   Sleeve of   protection   pipe   Unless it seals completely,   any air with high humidity   flows from outdoor and any   dew may drop.   • Transform the piping while holding down the   lower portion of pipe-support by hand.   Pipe   You are free to choose the side (left or right) for the installation of drain   hose. Please ensure the smooth flow of condensed water of the Indoor   unit during installation. (Careless may result in water leakage.)   Transform after   bending downward.   support   CAUTION   06K108_RAS-35_YH6_English.p65   1 11/13/06, 3:02 PM   |