Ethernet Adaptor Kit for UDC3500
Document Number: 51-52-33-152
Effective: 06/03/2005
Supersedes: N/A
Summary
The 50010425-501 Ethernet Adaptor kit allows you to connect your UDC to a MDI-compliant hub or switch
with a straight-through cable or directly to a PC with a crossover cable.
Contents
1 Ethernet Adaptor Assembly, 2 Tie Wraps
Table 1 UDC3500 procedure
Step
Action
1
28
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
29
L1
L2/N
4
30
31
32
5
33
6
34
7
24
27
35
8
9
36
Tie Wraps (2)
Figure 1 UDC3500 terminal connections
Remove the four Rear Terminal Screws from positions 24, 25, 26 and 27. Assemble Ethernet Adaptor as
shown using the four long #6 screws in kit. Route the wire from Adaptor board to Terminal #4 on UDC.
UDC Terminal
Position 4
Position 24
Position 25
Position 26
Position 27
UDC Signal Name
Shield
RX-
RX+
TX-
TX+
RJ45 Socket Pin #
Shield
6
3
2
1
Hub/PC Signal Name
Shield
TX-
TX+
RX-
RX+
2
For strain relief, secure your Ethernet cable to the controller with the tie wraps included in the kit using the
holes in the bottom controller flange.
Warranty/Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship.
Contact your local sales office for warranty information. If warranted goods are returned to Honeywell
during the period of coverage, Honeywell will repair or replace without charge those items it finds defective.
The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied,
including those of merchantability and fitness for a particular purpose. Specifications may change
without notice. The information we supply is believed to be accurate and reliable as of this printing.
However, we assume no responsibility for its use.
While we provide application assistance personally, through our literature and the Honeywell web site, it is
up to the customer to determine the suitability of the product in the application
Page 1 of 1
Download from Www.Somanuals.com. All Manuals Search And Download.
|