Gianni Industries Door GL600 S User Manual

GL600-S  
Mini Surface Electromagnetic Lock  
Regular Installation  
Magnet  
Armature  
(On Power)  
Fire Exposure and Hose Stream Tests were conducted in  
accordance with the standard, "Positive Pressure Fire Tests of  
Door Assemblies," ANSI / UL 10B and 10C, uniform building  
code standard UBC 7-2 (1997).  
Unique Anti-Residual design  
When the power is switched off, the holding force will be  
discontinuity and the bolt was installed in armature will pop  
Statement  
GL-600S mini surface water-proof Electromagnetic Locks  
design with no mechanical parts but magnetic force to secure  
and release the doors, suitable for use in areas which required  
access controlled or egress such as exit door.  
The Electromagnetic Locks are totally sealed in an epoxy  
filled stainless steel case for water-resistant and vandal-  
resistant purpose. A threaded conduit fitting ensures weather  
resistant protection of the wiring therefore it is ideal for indoor  
and outdoor applications, even in severe weather.  
We offers up to 600 pounds holding force with 12V DC  
power input (24V DC or 12/24V DC dual input voltage available  
by special order), and with the full range of optional brackets, it  
can be installed on all type of door frames such as Hollow,  
Wooden door. It is the best choice for electronic security  
industry and system integrators.  
This series of Waterproof Magnetic Lock is made with epoxy  
potting compound and is protected by this compound. Also,  
GEM Waterproof Series Magnetic Locks have been proved to  
Specifications  
have withstood  
a
water resistance as established in  
Voltage Tolerance: 15%  
accordance with the test procedures of IPX7, IPX8 through a  
trusted third party. Therefore users need not worry that the  
lock will be rusted or sparked, if the lock is using in outdoor  
applications and installing in confined space where any  
inflammable gas.  
Current Draw: 508mA@12Vdc (at temperature 20C)  
(Further notice for diverse input voltage on special order requirement)  
Operating Temperature: -10~55C )14~131F(  
Humidity: 0~95% non-condensing.  
Lock's surface Temperature (when the power is on):  
<current temperature +20C  
Holding Force: 600 lbs )272 Kg(  
Dimensions:  
Magnet:(L) 203, (W) 43, (D) 40 mm  
Armature Plate:(L) 159, (W) 41, (D) 14 mm  
Special Finishes for magnet and armature plate: Zinc  
Epoxy Potting Compound: E87252 (S), UL94V-0  
Weight )Approx.(: 2.0 Kg  
Warranty  
Magnetic bond sensor monitor output (GL600R-S)  
(SPDT rated 0.25A@12V DC), remotely monitors the door  
lock or unlock status. (N.C. Output--Door opened; N.O.  
Output--Door closed)  
The product is warranted against defects in material and  
workmanship while used in normal service for a period of  
year from the date of sale to the original customer. The GEM  
policy is one of continual development and improvement;  
therefore GEM reserves the right to change specifications  
without notice.  
5
GIANNI INDUSTRIES, INC.  
No. 13, Zhong Sing Road, Tu-Cheng Industrial Zone,  
Tu-Cheng City, Taipei, Taiwan 23678  
The products are manufactured under an ISO  
9001  
&
QC 080000 Certified Quality  
Management Program environment back its  
product quality, performance and commitment  
to customer satisfaction.  
Tel: 886-2 2267 7986 / Fax: 886-2 2267 9876  
Website: gianni.tw  
Copyright 2008 Gianni industries, inc. All rights reserved.  
DM-CA-GL600-S Ver. C Published on 2008.05.12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Dyson Patio Heater AM 04 User Manual
Ei Electronics Smoke Alarm Ei 100TYC User Manual
Euro Pro Carpet Cleaner SC505 User Manual
Finisar Laptop THG User Manual
Fisher Price Baby Gym B0846 User Manual
GE Dehumidifier ADEW30 User Manual
Generac Portable Generator 6519 User Manual
GE Range 229C4053P447 3 1 User Manual
Gigabyte Network Card GA K8NF 9 RH User Manual
Goldmund TV Converter Box MIMESIS 207 User Manual