®
POWER SYSTEMS, INC.
Owner’s Manual
GTS “W”Type
Automatic
Transfer Switch
200 Amp, 250 Volts
Model 04635-0
This manual should remain with the unit.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
• Because jewelry conducts electricity, wearing it
may cause dangerous electrical shock. Remove all
jewelry (such as rings, watches, bracelets, etc.)
before working on this equipment.
• If work must be done on this equipment while
standing on metal or concrete, place insulative
mats over a dry wood platform. Work on this
equipment only while standing on such insulative
mats.
Safety Rules..........................................Inside Front Cover
Section 1 — General Information ..................................2
1.1 Introduction ............................................................2
1.2 Equipment Description ............................................2
1.3 Transfer Switch Data Plate ......................................2
1.4 Transfer Switch Enclosure ......................................2
1.5 Safe Use Of Transfer Switch ....................................2
Section 2 — Installation ....................................................3
2.1 Introduction to Installation ......................................3
2.2 Unpacking ................................................................3
2.3 Mounting ..................................................................3
2.4 Connecting Power Source and Load Lines................3
2.4.1 2-Pole Mechanism ..........................................3
2.5 Connecting Start Circuit Wires ................................4
2.6 Auxiliary Contacts ....................................................4
Section 3 — Operation ......................................................5
3.1 Functional Tests & Adjustments ..............................5
3.2 Manual Operation ....................................................5
3.2.1 Close to Normal Source Side ........................6
3.2.2 Close to Emergency Source Side....................6
3.2.3 Return to Normal Source Side ......................6
3.3 Voltage Checks..........................................................6
3.4 Generator Tests Under Load ....................................7
Section 4 – Mounting Dimensions ................................8
Section 5 – Electrical Data ..............................................9
Section 6 – Exploded Views & Parts Lists..................12
Section 7 – Warranty ......................................Back Cover
• Never work on this equipment while physically or
mentally fatigued.
• Keep the transfer switch enclosure door closed and
bolted at all times. Only qualified personnel
should be permitted access to the switch interior.
• In case of an accident caused by electric shock,
immediately shut down the source of electrical
power. If this is not possible, attempt to free the
victim from the live conductor but AVOID DIRECT
CONTACT WITH THE VICTIM. Use
a
nonconducting implement, such as a rope or
board, to free the victim from the live conductor. If
the victim is unconscious, apply first aid and get
immediate medical help.
• When an automatic transfer switch is installed for
a standby generator set, the generator engine may
crank and start at any time without warning. To
avoid possible injury that might be caused by such
sudden start-ups, the system’s automatic start
circuit must be disabled before working on or
around the generator or transfer switch. For that
purpose, a SAFETY DISCONNECT is provided
inside the transfer switch. Always set that switch
to its MANUAL position before working on the
equipment. Then place a “DO NOT OPERATE” tag
on the transfer switch and on the generator.
Remove the Negative (Neg) or (–) battery cable.
®
Generac Power Systems, Inc.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1 — General Information
Generac GTS “W” Type Transfer Switch
When requesting information or ordering parts for this
equipment, make sure to include all information from
the DATA DECAL.
1.1 INTRODUCTION
This manual has been prepared especially for the
purpose of familiarizing personnel with the design,
application, installation, operation and servicing of
the applicable equipment. Read the manual carefully
and comply with all instructions. This will help to
prevent accidents or damage to equipment that might
otherwise be caused by carelessness, incorrect
application, or improper procedures.
Record the Model and Serial numbers in the space
provided below for future reference.
ASSEMBLY #
SERIAL #
Every effort has been expended to make sure that the
contents of this manual are both accurate and
current. Generac, however, reserves the right to
change, alter or otherwise improve the product at any
time without prior notice.
1.4 TRANSFER SWITCH ENCLOSURE
The standard switch enclosure is a National
Electrical Manufacturer’s Association (NEMA) 3R
type. NEMA 3R type enclosures primarily provide a
degree of protection against falling rain and sleet;
undamaged by the formation of ice on the
enclosure.
1.2 EQUIPMENT DESCRIPTION
The automatic transfer switch is used for
transferring critical electrical load from a UTILITY
(Normal) power source to
a
EMERGENCY
(STANDBY) power source. Such a transfer of
electrical loads occurs automatically when the
UTILITY power source has failed or is substantially
reduced and the EMERGENCY source voltage and
frequency have reached an acceptable level. The
transfer switch prevents electrical feedback between
two different power sources (such as the UTILITY
and EMERGENCY sources) and, for that reason,
codes require it in all standby electric system
installations.
1.5 SAFE USE OF TRANSFER SWITCH
Before installing, operating or servicing this
equipment, read the SAFETY RULES (inside front
cover) carefully. Comply strictly with all SAFETY
RULES to prevent accidents and/or damage to the
equipment. Generac recommends that a copy of the
SAFETY RULES be posted near the transfer switch.
Also, be sure to read all instructions and information
found on tags, labels and decals affixed to the
equipment.
The transfer switch consists of a solid state
intelligence circuit, a transfer mechanism and a
control panel.
Two publications that outline the safe use of transfer
switches are the following:
1.3 TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer
switch enclosure. Use this transfer switch only with
the specific limits shown on the DATA DECAL and on
other decals and labels that may be affixed to the
switch. This will prevent damage to equipment and
property.
• NFPA 70; National Electrical Code
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC
TRANSFER SWITCHES
®
2
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Generac GTS “W” Type Transfer Switch
Wiring diagrams and electrical schematics are
provided in this manual. Power source and load
connections are made at a transfer mechanism,
inside the switch enclosure.
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the
factory. Installing the switch includes the following
procedures:
• Mounting the enclosure.
2.4.1 2-POLE MECHANISM
• Connecting power source and load leads.
• Connecting the generator start circuit.
• Connecting any auxiliary contact (if needed)
• Installing/connecting any options and accessories.
• Testing functions.
These switches (Figure 2.1) are used with a single
phase system, when the single phase NEUTRAL line
is to be connected to a Neutral Lug and is not to be
switched.
Figure 2.1 — Typical 2-Pole Transfer Mechanism
(100 Amp Shown)
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely
for any damage that might have occurred during
shipment. The purchaser must file with the carrier any
claims for loss or damage incurred while in transit.
Check that all packing material is completely
removed from the switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch
enclosure are in this manual. Enclosures are
typically wall-mounted. See “Mounting Dimensions”.
Handle transfer switches carefully when
installing. Do not drop the switch. Protect the
switch against impact at all times, and against
!
construction grit and metal chips. Never
install a transfer switch that has been
damaged.
Solderless, screw-type terminal lugs are standard.
The conductor size range is as follows:
Install the transfer switch as close as possible to the
electrical loads that are to be connected to it. Mount
the switch vertically to a rigid supporting structure.
To prevent switch distortion, level all mounting
points. If necessary, use washers behind mounting
holes to level the unit.
Switch Rating
Wire Range
200A
#4-400 MCM
Conductor sizes must be adequate to handle the
maximum current to which they will be subjected;
based on the 75°C column of tables, charts, etc. used
to size conductors. The installation must comply fully
with all applicable codes, standards and regulations.
2.4 CONNECTING POWER SOURCE
AND LOAD LINES
DANGER
Before connecting wiring cables to terminals, remove
any surface oxides from the cable ends with a wire
brush. All power cables should enter the switch next
to transfer mechanism terminals. If ALUMINUM
conductors are used, apply corrosion inhibitor to
conductors. Tighten terminal lugs to the torque
values as noted on the decal located on the inside of
the door. After tightening terminal lugs, carefully wipe
away any excess corrosion inhibitor.
Make sure to turn OFF both the UTILITY
(NORMAL) and EMERGENCY (STANDBY)
power supplies before trying to connect
power source and load lines to the transfer
switch. Supply voltages are extremely high
and dangerous. Contact with such high
voltage power supply lines causes extremely
hazardous, possibly lethal, electrical shock.
All power cables should enter the switch next to the
transfer mechanism terminals.
®
Generac Power Systems, Inc.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Generac GTS “W” Type Transfer Switch
2.6 AUXILIARY CONTACTS
If desired, there are Auxiliary Contacts on the
transfer switch to operate customer accessories,
remote advisory lights, or remote annunciator
devices. A suitable power source must be connected
to the COMMON (C) terminal. See Figure 2.3.
Use a torque wrench to tighten the
conductors, being sure not to overtighten, or
damage to the switch base could occur. If
undertightened, a loose connection would
result, causing excess heat which could
damage the switch base.
!
Contact operation is shown in the following chart:
Switch Position
Connect power source load conductors to clearly
marked transfer mechanism terminal lugs as follows
Utility
Open
Standby
Closed
Open
Common to Normally Open
Common to Normally Closed
1. Connect UTILITY (NORMAL) power source cables
to switch terminals N1, N2.
Closed
2. Connect EMERGENCY (STANDBY) source power
cables to transfer switch terminals E1, E2.
3. Connect customer LOAD leads to switch
terminals Load 1, Load 2. (Load 1 and Load 2 are
used with liquid-cooled units only.)
NOTE:
Auxiliary Contacts are rated 10 amps at 125 or
250 volts AC. DO NOT EXCEED THE RATED
VOLTAGE AND CURRENT OF THE CONTACTS.
Conductors must be properly supported, of approved
insulative qualities, protected by approved conduit,
and of the correct wire gauge size in accordance with
applicable codes.
Figure 2.3 – Auxiliary Contacts
Be sure to maintain proper electrical clearance
between live metal parts and grounded metal. Allow
at least 1/2 inch for 100-400 amp circuits; at least
one inch for circuits over 400 amps.
Optional
Auxiliary Contact
(Actuated)
2.5 CONNECTING START CIRCUIT
WIRES
Side views shown in Utility position
Control system interconnections consist of UTILITY
1 and 2, LOAD 1 and 2 (liquid-cooled units only); and
leads 23 and 194. Control system interconnection
leads must be run in a conduit that is separate from
the AC power lead. Recommended wire gauge sizes
for this wiring depends on the length of the wire, as
recommended below:
MAXIMUM WIRE LENGTH
RECOMMENDED WIRE
SIZE
460 feet (140m)
No. 18 AWG.
No. 16 AWG.
No. 14 AWG.
No. 12 AWG.
461 to 730 feet (223m)
731 to 1,160 feet (354m)
1,161 to 1,850 feet (565m)
®
4
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Generac GTS “W” Type Transfer Switch
3.1 FUNCTIONAL TESTS AND
3.2 MANUAL OPERATION
DANGER
ADJUSTMENTS
Following transfer switch installation and
interconnection, inspect the entire installation
carefully. A competent, qualified electrician
should inspect it. The installation should comply
strictly with all applicable codes, standards, and
regulations. When absolutely certain the
installation is proper and correct, complete a
functional test of the system.
Do NOT manually transfer under load.
Disconnect transfer switch from all power
sources by approved means, such as a main
!
circuit breaker(s).
A manual HANDLE is shipped with the transfer
switch. Manual operation must be checked BEFORE
the transfer switch is operated electrically. To check
manual operation, proceed as follows:
1. Turn the generator’s AUTO-OFF-MANUAL switch
to OFF.
Perform functional tests in the exact order
2. Turn OFF both UTILITY and EMERGENCY
power supplies to the transfer switch, with
whatever means provided (such as the main line
circuit breakers).
3. Note position of transfer mechanism main
contacts by observing display windows in “A” and
“B” in Figure 3.1 as follows:
• Window “A” ON, Window “B” OFF - LOAD
terminals (T1, T2) are connected to UTILITY
terminals (N1, N2).
presented in this manual, or the switch could
be damaged.
!
IMPORTANT: Before proceeding with functional
tests, read and make sure all instructions and
information in this section is understood. Also read
the information and instructions of labels and decals
affixed to the switch. Note any options or accessories
that might be installed and review their operation.
Figure 3.1 — Actuating Transfer Switch
®
Generac Power Systems, Inc.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Generac GTS “W” Type Transfer Switch
• Window “A” OFF, Window “B” ON - LOAD
terminals (T1, T2) are connected to
EMERGENCY terminals (E1, E2).
Single-phase utility supply:
Measure across ATS terminal lugs N1 and N2; N1
to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is
correct and compatible with transfer switch
ratings, turn OFF the UTILITY supply to the
transfer switch.
4. On the generator panel, set the AUTO-OFF-
MANUAL switch to MANUAL position. The
generator should crank and start.
Do not use excessive force when operating
the transfer switch manually or the manual
handle could be damaged.
!
3.2.1 CLOSE TO NORMAL SOURCE SIDE
◆
5. Let the generator stabilize and warm up at no-
Before proceeding, verify the position of the switch by
observing window “A” in Figure 3.1. If window “A”
reads “ON”, the contacts are closed in the NORMAL
position, no further action is required. If it reads
“OFF”, proceed with Step 1.
load for at least five minutes.
6. Set the generator's main circuit breaker (CB1) to
its ON or CLOSED position.
DANGER
Step 1: With the handle attached to the actuating
shaft, move handle in the direction of the
arrow on the switch cover until it stops — DO
NOT FORCE. Release handle slowly to allow
the spring in the switch box to relax. “ON”
now appears in Window “A” and “OFF”
appears in Window “B”.
PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED
TO TRANSFER SWITCH TERMINALS. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL
ELECTRICAL SHOCK.
7. With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
Single-phase generator supply:
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
◆
Before proceeding, verify the position of the switch by
observing window “B” in Figure 3.1. If window “B”
reads “ON”, the contacts are closed in the
EMERGENCY (STANDBY) position. No further action
is required. If it reads “OFF”, proceed with Step 1.
Measure across ATS terminal lugs E1 to E2; E1
to NEUTRAL and E2 to NEUTRAL.
a. Frequency ......................................60-62 Hz
b. Terminals E1 to E2 ........................240-246 VAC
c. Terminals E1 to NEUTRAL ............120-123 VAC
d. Terminals E2 to NEUTRAL ............120-123 VAC
It will also be necessary to verify that the phase
rotation of the utility matches the phase rotation of
the generator. This can be done by using a phase
rotation indicator.
Step 1: With the handle attached to the actuating
shaft, move the handle in the direction of the
arrow on the switch cover until it stops - DO
NOT FORCE. Release handle slowly to allow
the spring in the switch box to relax. “OFF”
now appears in Window “A” and “ON” appears
in Window “B”.
3.2.3 RETURN TO NORMAL SOURCE SIDE
Manually actuate switch to return Window “A” to the
“ON” position.
◆
Failure to do so may result in damage to
certain rotary equipment.
!
8. Set the generator’s main circuit breaker (CB1) to
its OFF or OPEN position.
9. Set the AUTO-OFF-MANUAL switch to the OFF
position to shut down the generator.
NOTE:
3.3 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the
transfer switch with whatever means provided
(such as the UTILITY maim line circuit breaker).
DANGER
Do NOT proceed until generator AC output voltage
and frequency are correct and within stated limits.
If the no-load voltage is correct but no-load
frequency is incorrect, the engine governed speed
probably requires adjustment. If no-load
frequency is correct but voltage is not, the voltage
regulator may require adjustment.
PROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
HAZARDOUS AND POSSIBLY FATAL
ELECTRICAL SHOCK.
2. With an accurate AC voltmeter, check for correct
voltage.
®
6
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Generac GTS “W” Type Transfer Switch
5. When checkout under load is complete, set main
circuit breaker of the generator to its OFF or
OPEN position.
3.4 GENERATOR TESTS UNDER LOAD
1. Set the generator's main circuit breaker to its
OFF or OPEN position.
6. Let the generator run at no-load for several
minutes. Then, shut down by setting the AUTO-
OFF-MANUAL switch to its OFF position.
7. Move the switch's main contacts back to their
utility position. For example, load connected to
utility power supply. Refer to Manual Operation.
Handle and operating lever of transfer switch
should be in down position.
8. Turn on the utility power supply to transfer
switch, using whatever means provided (such as
a utility main line circuit breaker). The utility
power source now powers the loads.
2. Manually actuate the transfer switch main
contacts to their EMERGENCY (STANDBY)
position. Refer to Manual Operation.
3. To start the generator, set the AUTO-OFF-
MANUAL switch to MANUAL. When engine starts,
let it stabilize for a few minutes.
4. Turn the generator's main circuit breaker to its
ON or CLOSED position. The generator now
powers all LOAD circuits. Check generator
operation under load as follows:
•
Turn ON electrical loads to the full rated
wattage/amperage capacity of the generator.
DO NOT OVERLOAD.
9. Set the generator's AUTO-OFF-MANUAL switch to
its AUTO position. The system is now set for fully
automatic operation.
•
With maximum rated load applied, check
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 volts; frequency should be
greater than 59 Hz.
•
Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc.,
that might indicate a problem.
®
Generac Power Systems, Inc.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Mounting Dimensions
Generac GTS “W” Type Transfer Switch
Mounting Dimensions – Drawing No. 0D3714-B
®
8
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5 — Electrical Data
Generac GTS “W” Type Transfer Switch
Transfer Switch Interconnections - Drawing No. 079963-B
4
A D 1
T I L I T Y 1
®
Generac Power Systems, Inc.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5 — Electrical Data
Generac GTS “W” Type Transfer Switch
Transfer Switch Interconnections - Drawing No. 074106-A
4
A D 1
T I L I T Y 2
T I L I T Y 1
®
10 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5 — Electrical Data
Generac GTS “W” Type Transfer Switch
Wiring Diagram - 200 Amp, 2-pole Switch – Drawing No. 0D3819
®
Generac Power Systems, Inc. 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Exploded Views and Parts List
Generac GTS “W” Type Transfer Switch
Transfer Switch Assembly (2-pole) – Drawing No. 0D4406-E
®
12 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Exploded Views and Parts List
Generac GTS “W” Type Transfer Switch
Transfer Switch Assembly (2-pole) – Drawing No. 0D4406-E
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
0C8884
0A9949
0C4896
067989
026902
0C7907H
022259
057329
022142
027482
022129
073591
090388
0A1495
063617
0C2454
0A1661
0C4449A
0D3714
0D5589
0C8308
0A2595
022264
0D4637
022097
025870
057593
064761
063321
073590A
0D3587
067210A
0A9457
0D4545
0C8275
0D3305
081221
1
6
6
6
6
2
1
1
1
1
1
4
5
6
1
2
2
1
1
1
2
1
6
1
3
1
5
5
1
4
1
1
1
1
4
1
1
XFER SW-W 200A600V2P
LUG SLDLSS 400-#4X1/4-20 CU7AL
SCREW FHMS M8-1.25 X 20MM CR
NUT LOCK FL M8-1.25 YEL CHR
SCREW HHTT #8-32 X 1/4 CZ
LUG COV2P 150/200AMP
NUT HEX 5/16-18 STEEL
LUG SLDLSS 350-#6X13/32 AL/CU
SCREW HHC 5/16-18 X 3/4 G5
WASHER SHAKEPROOF EXT 5/16 STL
WASHER LOCK M8-5/16
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
27
28
29
30
31
32
33
34
35
36
37*
38
FUSE HOLDER
SCREW HHTT M6-1.0 X 12 YC
SCREW HHTT M4-0.7 X 10 BP
RELAY PNL 12VDC DPDT 10A@240VA
SCREW TH-FRM M6-1X16 N WA Z/JS
RIVET POP .156 X .160-.164/#20
ASS'Y-NTRL BL150-200A
WELDMENT, TRANSFER SWITCH BOX
SILK SCREEN, ATS COVER
DECAL TERMINAL SHOCK HAZARD
DECAL, TERM. STRIP
WASHER LOCK #8-M4
DECAL, SWITCH RATING
WASHER LOCK M6-1/4
NUT WING 1/4-20
CABLE TIE MOUNT BLACK
TIE WRAP UL 5.6 X .10 NATL
HANDLE XFER SWITCH 1-400A
FUSE 5A X BUSS
DECAL, FUSE REPLACEMENT
DECAL GROUND LUG
DECAL NEUTRAL
DECAL, MANUAL OPERATION
SCREW PPHM DSEMS M4-7 X 10 ZNC
DECAL, TEST SEQUENCE 2P TS
DECAL-UL LIST HSB
*CENTER DECAL ON INSIDE OF THE COVER (ITEM #20)
®
Generac Power Systems, Inc. 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Warranty
Generac GTS “W” Type Transfer Switch
GENERAC POWER SYSTEMS STANDARD TWO-YEAR LIMITED WARRANTY
FOR GENERAC TRANSFER SWITCH SYSTEMS
For a period of 2 (two) years from the date of sale, Generac Power Systems, Inc. will, at its option, repair or replace any
part(s) which, upon examination, inspection, and testing by Generac Power Systems or a Generac Power Systems
Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the
warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by
the nearest Generac Power Systems Authorized Warranty Service Dealer. All transportation costs under the warranty,
including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to
Generac Power Systems Transfer Switch applications, as Generac Power Systems, Inc. have defined Transfer Switch
application.
WARRANTY SCHEDULE
• YEAR ONE — 100% (one hundred percent) coverage labor, and parts listed.
• ALL COMPONENTS
• YEAR TWO — 100% (one hundred percent) coverage on parts listed.
• ALL COMPONENTS — *PARTS ONLY
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a
non Generac genset is substituted for use and directly causes damage to the Generac Transfer Switch, no warranty
coverage shall apply.
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and
Procedures Flat Rate Manual.
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
1. Any unit built/manufactured prior to January 1, 2002.
2. Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.
3. Costs of normal maintenance i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up.
4. Use of Non-Generac replacement part(s) will void the warranty in its entirety.
5. Damage related to rodent or insect infestation
6. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or
sizing.
7. Failures caused by any external cause or act of God such as collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.
8. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in
repair or replacement of the defective part(s).
10. Failure due to misapplication, or misrepresentation.
11. Telephone, cellular phone, facsimile, internet access or other communication expenses.
12. Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific
unit warranty period.
13. Rental equipment used while warranty repairs are being performed.
14. Overtime labor.
15. Expenses related to “customer instruction” or troubleshooting where no manufacturing defect is found.
16. Overnight freight costs for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC
POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above
limitation may not apply to you.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED
ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL
DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may
not apply to you. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence.
This warranty gives you specific legal rights. You also may have other rights that vary from state to state.
GENERAC® POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 5319087
Part No. 0D4001
Revision C (10/17/03)
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|