GE Electronic Accessory ge multilin User Manual

GE MULTILIN TM  
PMCS 6.15  
Read-This-Book-First  
Installation Guide  
DEH-211  
GE Power Management Control System  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GE MULTILIN TM  
PMCS 6.15  
Read-This-Book-First  
Microsoft, Microsoft Excel and Microsoft PowerPoint are registered trademarks, and Windows 2000 is a  
trademark of Microsoft Corporation.  
Multilin 269+ Motor Management Relay® are registered trademarks of Multilin Inc., and Multilin SR489  
Generator Management Relay™ and Multilin SR745 Transformer Management Relay™ are trademarks of  
Multilin Inc.  
US Pat Nos 5,768,148; 5,764,155; 5,862,391  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This Page is Left Blank Intentionally)  
CIMPLICITY PMCS Read-This-Book-First  
i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Back to Main Page  
Contents  
Introduction  
6
Welcome....................................................................................................................................6  
How to Use this Book................................................................................................................6  
About CIMPLICITY PMCS Version 6.15 ................................................................................7  
Performance.................................................................................................................7  
Features .......................................................................................................................7  
Supported Devices.......................................................................................................8  
Getting Started  
10  
First Steps ................................................................................................................................10  
Understanding Terminology......................................................................................10  
System Requirements ................................................................................................13  
PMCS 6.15 Envelope definition................................................................................14  
Where to Get Help.....................................................................................................15  
What’s next?..............................................................................................................15  
Installing the Software  
17  
Computer Preparation..............................................................................................................17  
When Installing On Windows 2003 Server...............................................................18  
Installing CIMPLICITY ............................................................................................19  
Installing Additional Software...................................................................................20  
Installing the EPM Software Components ................................................................23  
Installing the PMCS software..................................................................................................23  
eLicensing PMCS software .......................................................................................23  
Host PC Installation...................................................................................................25  
Viewer Workstation Installation................................................................................25  
PMCS Installation Steps............................................................................................25  
After PMCS IIS – Setting up PMCS Server..............................................................44  
Un-elicensing PMCS.................................................................................................44  
Uninstalling PMCS....................................................................................................45  
Reinstallation Steps ...................................................................................................47  
Upgrading from previous versions to PMCS 6.15 ....................................................48  
Working with Cimplicity Viewer Node  
50  
How to view the screens on a viewer node..............................................................................50  
Configuring the Software  
52  
ii TBack to Main PageT  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Organize Your Information.......................................................................................52  
Configuration Procedure ...........................................................................................54  
EPM Device-Special Considerations  
57  
Introduction .............................................................................................................................57  
EPM Software Components ....................................................................................................58  
Network Builder: Building the Network Configuration File.....................................58  
ION Designer: Programming Devices and Software Nodes .....................................58  
Communications Server: System Communications ..................................................58  
ION_LINK DDE Server: Communication with Windows Applications ..................58  
Workstation Configuration Guidelines....................................................................................59  
Configuring the EPM Device Network ...................................................................................60  
Running Network Builder .........................................................................................60  
Building the Power-Monitoring Network in NetBuilder...........................................61  
Adding Devices (Meters) ..........................................................................................65  
Saving and Exiting ....................................................................................................65  
Index  
67  
CIMPLICITY PMCS Read-This-Book-First  
Contents iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally)  
CIMPLICITY PMCS Read-This-Book-First  
Introduction 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Welcome  
Hello and welcome to the POWER LEADER Power Management Control  
System for CIMPLICITY® HMI. You are about to begin using your computer in  
an exciting new way—as a tool to help you increase productivity while reducing  
downtime and energy costs.  
This book is for anyone getting started with CIMPLICITY PMCS. It contains  
the information you need to install and begin using PMCS effectively.  
Chapter 2, Getting Started, explains the terminology of power-  
management systems, describes each of your PMCS items,  
outlines the minimum system requirements, and lists methods of  
getting GE Technical Support.  
Chapter 3, Installing the Software, explains how to prepare your  
system and install all of the PMCS software. Any special  
installation steps are outlined for each software module.  
Chapter 4, Configuring the Software, describes how to efficiently  
configure PMCS to get up and running in the shortest time.  
Chapter 5, EPM Device Special Considerations, details the  
additional configuration required to use EPM 7700, EPM 7600  
and EPM 7500 meters in a PMCS network.  
How to Use this Book  
You will find this book easy to use if you look for these simple conventions:  
Boldface type indicates the name of an item you need to select.  
Monospace type indicates an example or text that is displayed on  
the screen.  
UPPERCASE type indicates a file name, command name, or  
acronym.  
6 Introduction  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About CIMPLICITY PMCS Version 6.15  
CIMPLICITY PMCS Version 6.15 is the latest Power Management Control  
System in the robust line of POWER LEADER power-management products  
from GE Multilin. CIMPLICITY PMCS seamlessly integrates the  
comprehensive line of POWER LEADER devices, as well as many new  
Modbus RTU devices and systems. PMCS comes with built-in Ethernet  
compatibility and is optimized for the Windows 2000 and Windows XP  
operating system. All of this adds up to the most flexible, high-performance,  
open-architecture power-management system available. PMCS software is the  
backbone of your new power management system, with state-of-the-art graphics  
and features designed to maximize productivity and minimize downtime and  
energy costs.  
Performance  
With built-in Modbus RTU and Ethernet compatibility, PMCS delivers critical  
power-management information faster than ever. PMCS supports baud rates of  
up to 38.4 kbps on a Modbus RTU network and 10 Mbps on an Ethernet TCP/IP  
network. This results in near “real-time” screen refresh rates and immediate  
access to critical event and alarm data.  
Features  
PMCS comes with the following features that make the system more powerful  
and easy to use:  
Compatible with industry-standard third-party SCADA platforms.  
Built-in Modbus RTU network compatibility for an open network  
architecture and high-speed communications.  
Built-in Ethernet TCP/IP network compatibility for very high-  
speed communications and reduced wiring costs.  
Built-in support for the comprehensive line of POWER LEADER  
power-management devices, as well as additional GE meters and  
relays, Fanuc 90/30 and 90/70 programmable logic controllers,  
plus support for third-party meters and relays.  
3D virtual-device interaction with accurately reproduced device  
look and feel.  
Improved waveform capture, including extensive analysis tools.  
Comprehensive alarm and event reporting for immediate diagnosis  
of electrical system problems.  
Single Viewer Workstation support for seamless access and  
sharing of power-management data across your existing LAN.  
Configurable password protection and user-activity logging for  
improved security and restriction of setup or control operations.  
PMCS option modules are available to further increase productivity and reduce  
energy costs. Your system may include one or more of the following modules:  
CIMPLICITY PMCS Read-This-Book-First  
Introduction 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CIMPLICITY PMCS Interface Toolkit with tools to quickly create  
accurate, intelligent floor plans, one-line diagrams, and elevation  
views.  
System Test Simulator to design and test PMCS systems without  
connection to real networks or devices.  
Supported Devices  
CIMPLICITY PMCS 6.15 supports the following devices. Firmware revisions other than those  
listed may not be compatible with PMCS. Contact your GE Sales Representative or the GE  
Resolution Center, at 1-888-GE-RESOLV for more information.  
IED  
Versions  
IED Product  
Versions  
Supported  
5.1x  
Product Supported  
239  
Note:  
2.3x to 2.7x  
6.0x  
Spectra  
MicroVersa Trip  
Enhanced  
MicroVersa Trip C  
UR has been categorized into  
three different Device Types.  
269+  
369  
4.1x  
4.1x  
1.6x to 2.3x  
Enhanced  
UR  
- supports 2.6x to 4.6x  
MicroVersa Trip D  
UR480 - supports 4.8x  
UR490 - supports 4.9x and 5.0x  
469  
489  
735/737  
745  
750/760  
F650  
MMII  
MMIII  
MIF2  
PQM  
PQMII  
RRTD  
SPM  
2.5x to 5.0x  
1.3x to 4.0x  
1.5x  
2.4x to 5.0x  
3.6x to 7.0x  
1.6x to 2.20  
4.0x to 5.1x  
1.0x to 1.2x  
1.0  
3.3x to 3.6x  
1.0x to 2.2x  
1.4x, 1.5x  
2.0x, 2.1x  
EPM1000  
EPM2000  
EPM4000  
EPM5000P  
EPM5200P  
EPM5300P  
EPM5350P  
EPM6000  
EPM9450Q  
EPM9650Q  
PLEPM  
3.8x  
1.0  
3.8x  
2.4x  
2.4x  
2.4x  
2.4x  
1.0  
2.1x  
2.1x  
1.0x  
5.4x, 6.0x  
5.4x, 6.0x  
1.0  
MX150  
MX250  
SMR2  
B30  
C30  
C60  
D30  
D60  
F35  
F60  
G30  
G60  
L60  
L90  
M60  
N60  
T35  
T60  
2.6x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
3.0x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
4.4x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
3.4x to 5.0x  
2.6x to 5.0x  
2.6x to 5.0x  
MPRO  
FIRETRACER  
UPSLP  
UPSSG  
VERSAMAX  
1.0  
1.0  
1.0  
1.0  
1.0  
8 Introduction  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally)  
CIMPLICITY PMCS Read-This-Book-First  
Introduction 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
First Steps  
If you are already familiar with PMCS, simply review the system requirements  
and skip ahead to Chapter 3.  
Getting started with PMCS is easy. This chapter explains power management  
and leads you through the steps to take prior to installing your PMCS software.  
If you need help with your PMCS system, the GE Technical Support telephone  
number is given at the end of this chapter.  
Understanding Terminology  
Power-management system terminology can be intimidating to new PMCS  
users. The list below defines many of the important terms and acronyms used in  
this guide and other PMCS manuals. Refer back to this list as new terms are  
presented later.  
Baud rate: A measurement of a communication channel's signaling rate or  
information-carrying capacity. Communicating devices typically have  
configurable baud rates to provide compatibility with various speed  
communication networks. Higher baud rates generally provide faster data-  
refresh times.  
CIMPLICITY HMI: An industry-standard SCADA software package providing  
flexible, accurate, and easy-to-use graphics. CIMPLICITY HMI is based on  
client-server architecture, consisting of Servers and Viewer Workstations.  
Servers are responsible for the collection and distribution of data. Viewer  
Workstations connect into Servers and have full access to the collected data for  
viewing and control actions. Servers and Viewer Workstations can be easily  
networked together to seamlessly share data without the need to replicate your  
point database from node to node.  
CIMPLICITY HMI Server Development: CIMPLICITY HMI Server  
Development allows you to create new projects and can also function as a  
runtime system.  
CIMPLICITY HMI Server Runtime: CIMPLICITY HMI Server Runtime  
systems do not support project configuration. They may be used as runtime  
systems only.  
CIMPLICITY HMI Viewer Runtime: CIMPLICITY HMI Viewer Runtime  
connects to Servers for viewing data and controlling actions.  
Commnet: A GE Industrial Systems standard for device communications that  
specifies the communication protocol and the communication network.  
10 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication network: A physical standard for wiring and interconnection of  
communicating devices. A communication network standard usually includes  
specifications of voltages, maximum cable-run lengths, shielding, termination,  
and cable requirements. RS485 and Ethernet are examples of communication-  
network standards.  
Communication protocol: A language or convention used for reliable  
transmission and reception of binary data. A communication protocol is often  
independent of the physical method or network used for transmission. Modbus  
RTU and TCP/IP are examples of communication protocol standards.  
DDE Server: A software application that typically runs in the background,  
gathering information from the network and providing the information in DDE  
format for use by one or more applications. The PMCS DDE Server is included  
in the PMCS Network & Device Configurator and comes in versions optimized  
for Ethernet TCP/IP or RS485 Modbus RTU networks.  
DDE: Dynamic Data Exchange. A Microsoft Windows standard for efficient  
sharing of data between applications on the same PC. See also NetDDE.  
Ethernet Gateway: A POWER LEADER device used to connect four RS485  
Modbus RTU networks to an Ethernet TCP/IP network. The Gateway increases  
performance of a PMCS system through multiple Modbus networks and reduces  
overall wiring costs through reuse of existing Ethernet LAN wiring.  
Ethernet: An industry-standard communication network commonly used for  
local-area networks (LANs) of PCs. Ethernet PMCS systems provide very high-  
speed, reliable communications at 10 megabits per second.  
Event Logger: A standard PMCS application that efficiently analyzes, sorts, and  
logs unusual system behavior such as circuit breaker trips, undervoltages, and  
overcurrents. Extensive data-logging capabilities make it a useful tool for  
analyzing and predicting system maintenance patterns.  
Host PC: The PC running the PMCS DDE Server is referred to as the Host PC.  
All other PCs running PMCS client programs are referred to as Viewer  
Workstations or networked PCs.  
Interface Toolkit: An optional PMCS tool used to quickly generate accurate and  
friendly graphical user interfaces. The Interface Toolkit provides dozens of  
wizards to efficiently create intelligent one-line diagrams, equipment elevation  
views, floor plans, 3D virtual-faceplate views, and tabular displays.  
Modbus Concentrator: A POWER LEADER device used to connect eight  
commnet networks to an RS485 Modbus RTU network. The Concentrator  
provides full compatibility between the PMCS software and the extensive line  
of POWER LEADER devices with commnet communications, as well as simple  
expansion of a RS485 Modbus RTU network to up to 247 devices.  
Modbus RTU: An industry-standard, nonproprietary communications protocol  
typically used in medium-speed networks (up to 38.4 kpbs) on RS485.  
Multinet: Multinet is an Ethernet communications module that allows  
connection for up to 32 ModBus devices, providing ModBus TCP/IP  
communications for these devices over Ethernet. This allows connection to  
Fiber Optic LAN and WAN systems for remote access to data  
NetBEUI: A network protocol usually used in small, department-size local-area  
networks of 1 to 200 clients.  
CIMPLICITY PMCS Read-This-Book-First  
Getting Started 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NetDDE: A version of Dynamic Data Exchange (DDE) that allows  
communications between applications running on different PCs over network  
connections.  
NT Service: A designated piece of software which runs in the background of  
Windows NT and can be set to automatically start when the machine is booted  
up. For example, the PMCS DDE Server can be set to operate as a Windows NT  
Service, rather than a manually launched application. Another advantage of NT  
Services is that they are persistent across multiple user logins and logouts; that  
is, PMCS DDE Server when operating as a Windows NT Service will not shut  
down when a user logs off.  
ODBC: Open Database Connectivity. An inter-application communication  
protocol required for certain PMCS client applications to share data.  
Automatically installed and configured as part of the PMCS installation routine.  
PMCS: Power Management Control System. GE’s high-performance power-  
management system for Windows 2000, including open network protocols,  
waveform capture and analysis, event logging, and several optional modules.  
POWER LEADER: The family of GE power-management devices, including  
meters, relays, trip units, and software.  
RS485: An industry-standard communication network supporting up to 32-  
networked devices. RS485 provides medium-speed, reliable communication  
transport through shielding, balanced transmission voltages, and termination.  
SCADA: Supervisory Control and Data Acquisition. A category of systems that  
primarily acquires data for logging and analysis, as well as providing  
supervisory control in applications without time-critical requirements. Power-  
management systems are a direct application of SCADA technology.  
TCP/IP: Transmission Control Protocol / Internet Protocol. An industry-  
standard protocol typically used on Ethernet or Token-Ring local-area networks  
(LANs).  
Waveform Capture: A standard PMCS application that provides a window into  
power-quality data in an electrical system. Waveform Capture is used to view  
snapshots of voltage and current waveforms from various points in an electrical  
system to analyze harmonics and unusual system behavior.  
12 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Requirements  
The following table shows the minimum and recommended PC system  
configuration for running PMCS Version 6.15. Note that regardless of  
configuration, the PC system must be Windows NT-certified according to the  
Windows 2000 with Service Pack 4 or Windows XP with Service Pack 2  
Hardware Compatibility List, available from Microsoft (www.microsoft.com).  
In addition to the requirements described below, setting up PMCS and EPM  
7700 workstations will require Windows NT Administrator-level authority  
privileges.  
Recommended  
1GHz or greater single processor Dell OptiPlex  
Windows 2000 SP4 Professional  
Windows XP SP2 Professional  
Cimplicity HMI Version 6.1 SP5  
512MB or greater RAM  
512K cache  
30GB or greater AT-100 hard drive  
10/10/32 CDRW (not operating burning CDs while  
application is running)  
2 10-BaseT Ethernet Cards (static IP addresses only- no  
DHCP support)  
1 parallel port printer  
1 analog phone modem (no Winmodems)  
.Net Framework 1.1.4322(if not installed PMCS setup will  
install this component)  
Internet Services Manager (IIS)  
Additional hard disk space is recommended for increased storage of log and  
trend data. Also recommended are an uninterruptible power supply (UPS), 17”  
or larger monitor, tape drive or other backup mechanism, and (if Remote Access  
technical support is desired) a 28.8 Kbps or faster modem.  
The version of CIMPLICITY installed must be 6.1 with Service Pack 5. Also,  
the "Advanced DDE Communications" option must be installed.  
Microsoft Internet Explorer 3.02 or later is required to run the EPM 7700  
component help system. To take advantage of all available HTML help features,  
Internet Explorer version 4.0 or higher must be installed. (The latest version of  
Internet Explorer is available at www.microsoft.com.)  
Please note that the host PC requirements are directly tied to the complexity of  
your PMCS system. The minimum requirements will suffice for a simple PMCS  
system. However, as the number and complexity of your power management  
device grows, and you add more complex software requirements such as custom  
interfaces designed with third-party HMI tools, your PC requirements increase  
as well. A faster processor and more memory provide better performance for  
your PMCS system.  
CIMPLICITY PMCS Read-This-Book-First  
Getting Started 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PMCS 6.15 Envelope definition  
1) Physical System Size  
75 power management devices (IEDs) (100 max),  
150 I/O points (through IEDs or PLCs)  
64 ethernet serial communications ports,  
2 Modbus Monitors (maximum) using standard Modbus Monitor Proxy  
2) HMI Application Size -  
20,000 points/tags in HMI database (30K Max)  
600 HMI alarms configured max  
600 trended points (8 max per device)  
HMI I/O rates, alarm rates, and logging rates not to exceed 750 pts/sec  
13 HMI screens in CIMPLICITY utilizing Power Builder -10 device  
type and 50 user screens  
150 HMI screens in InTouch  
5 DDE ports in CIMPLICITY with no more than 10 devices  
configured per port  
10% of tags connected to enterprise solution  
Web-enabled only via CIMPLICITY WebView - no waveform or  
event viewers  
Maximum of one Viewer node  
3) Special Application Issues  
No redundancy  
Components to be run as NT services by default  
4) Performance  
Response times:  
1 second or less to open an HMI screen  
1 seconds update time to populate a screen per device per serial  
port*(Except for UR Device)  
4 to 7 second time delay to display event in PMCS Event Viewer  
1 second response time to make device change (settings/ command  
coil) not including device feedback  
1000 device events/ sec burst support  
Configuration:  
Maximum 15 devices per serial port  
Device baud rates set to maximum  
CIMPLICITY HMI points set for on-demand  
Devices supporting 125 register block reads  
Average CPU utilization <35%  
99% system uptime  
14 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where to Get Help  
The GE Industrial Systems Resolution Center is available at 1-888-GE-  
RESOLV to answer your questions about installing or using PMCS. Please have  
your product serial number(s) ready when calling.  
Also, technical notes are available on the Internet at:  
What’s next?  
The following chapters discuss the details of installing and getting quick results  
from your new PMCS software. Set aside at least an hour and be sure to follow  
the procedures carefully to guarantee correct installation of your PMCS  
software.  
CIMPLICITY PMCS Read-This-Book-First  
Getting Started 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally)  
16 Getting Started  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Software  
Computer Preparation  
PMCS must be installed on a PC running Windows 2000 SP4. This host PC  
must be dedicated to the PMCS system. Performance and data integrity  
cannot be predicted unless the PC is configured solely for the purpose of  
running PMCS.  
The Windows 2000 SP4 System control panel offers a Performance tab  
that allows you to boost performance for the applications as shown below:  
The Virtual Memory setting may be left at the Windows 2000 SP4 defaults.  
Make sure your system meets these requirements before proceeding with the  
remaining installation steps. PMCS will not run correctly unless these  
requirements are satisfied.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When Installing On Windows 2003 Server  
The Following steps to be executed before starting the PMCS installation. This  
applies for all the licenses of PMCS application. This is basically to avoid the  
problem caused by e-license wrapped PMCS applications to open after  
installation. If the below steps are not done before PMCS installation, the  
applications will give error message when we open them.  
1. Right Click on “My Computer”. Select “Properties”. Select  
Advanced”. Below dialog is seen.  
.
2. Click on “Settings” button under Performance heading. Below  
dialog opens. By default the second one “Turn on DEP for all  
programs and services except those I select”. Instead of this select the  
first option as shown in the below dialog. It says “Turn on DEP for  
essential programs and services only”.  
18 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click on Apply and then click on Ok button. After this restart the PC and  
then start the PMCS installation process as mentioned in this document.  
Installing CIMPLICITY  
If CIMPLICITY HMI was provided with your PMCS software, you must install  
it before proceeding. If your computer already has CIMPLICITY HMI installed,  
make sure the following requirements are met.  
CIMPLICITY HMI for Windows 2000 SP4 (Intel) Version 6.1 SP5 is  
required. Other versions of CIMPLICITY may not be compatible with  
PMCS.  
If you are installing CIMPLICITY HMI, follow the directions provided with the  
software (inside the CD jewel case). Choose CIMPLICITY HMI as the  
product to install, and then select either the HMI Server or Viewer as the  
product option to install, and C:\CIMPLICITY\HMI as the installation  
directory. If you install the Server option, also install Server Option -  
Communications - Advanced DDE/DDE Client.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Additional Software  
Install any additional software, such as Microsoft Excel, at this point in the  
procedure. Follow the instruction procedures provided by the manufacturer.  
RS485 PMCS Network Interfaces  
If you are using an RS485 interface card to connect to the PMCS network, install the  
card following the manufacturer’s installation instructions. Be sure to install any  
Windows NT drivers provided by the interface-card vendor. Typically, drivers are  
installed at Control Panel>Administrative Tools >Computer Management>System  
Information> Components>Network>Adapter by following the instructions. You may  
be prompted to insert the manufacturer’s disk into the A: drive.  
20 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Select the appropriate network adapter from the list and click Have Disk….  
Follow the instructions provided on the screen to complete the network card  
installation.  
For PMCS systems using one or more GE Multilin RS232 to RS485 converters  
(or equivalent), no additional drivers are required.  
Ethernet PMCS Network Interfaces  
If you are using an Ethernet interface card to connect to the PMCS network  
through one or more Ethernet Gateways or directly to a network of Universal  
Relays, EPM 9650 / 9450s (Modbus TCP/IP), follow the manufacturer’s  
installation instructions and be sure to install the provided Windows NT drivers  
using Control Panel>Administrative Tools >Computer  
Management>System Information> Components>Network>Adapter. Refer  
to the screen shots above for an example, though the selections will differ based  
on the hardware you are installing.  
Ethernet requires the TCP/IP protocol for compatibility with the Ethernet  
Gateway. TCP/IP should have been installed with Windows 2000 SP4; you can  
check this using Control Panel>Administrative Tools >Computer  
Management>System Information> Components>Network>Protocol. The  
screen shot below shows a system with TCP/IP installed. If TCP/IP is not  
installed on your system, refer to the Windows 2000 SP4 documentation for  
installation instructions.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Local Area Network (LAN) Interfaces  
PMCS supports multiple View Nodes through NetDDE links over a local area  
network. Thus, in addition to the PMCS network interface, the Host PC may  
also have a LAN interface.  
A Host PC with an Ethernet PMCS network interface may use either the same  
Ethernet card as the LAN interface or a separate LAN interface card. A Host PC  
with an RS485 PMCS network interface requires an additional LAN interface  
card to support View Nodes.  
Typical LAN interface cards include Ethernet and Token Ring. Any LAN  
interface card should be installed according to the manufacturer’s instructions.  
22 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Additional Software  
Install any additional software, such as Microsoft Excel or COMTRADE file  
browsers for analyzing waveform files, at this point in the procedure. Follow the  
instruction procedures provided by the manufacturer.  
Installing the EPM Software Components  
The EPM 7700, EPM 7600 and EPM 7500 Meters require additional software to  
operate with PMCS client software such as the Event Logger, Waveform  
Capture Module, or CIMPLICITY Wizards. This is because the EPM 7700,  
EPM 7600 and EPM 7500 are not compatible with the standard PMCS DDE  
Server. Instead, a separate DDE Server called the 7700 Gateway Server must be  
installed, along with a pair of ‘helper’ applications, the Communications Server  
and the ION_Link Server. The Communications Server processes all  
communications between the Gateway Server and/or the ION_Link and the  
Ethernet-based EPM 7700, EPM 7600 and EPM 7500 meters.  
The EPM 7700 software may be selected during the standard PMCS installation  
routine. If you are not using any EPM devices in your PMCS setup, you do not  
need to install the EPM options during PMCS installation.  
The EPM software components do require some special configuration beyond  
that required for other PMCS components. Refer to the section titled EPM  
Device Special Considerations for details after running the installation routine  
described in this section.  
Installing the PMCS software  
Once you have set up Windows NT and any third-party software (if appropriate)  
you are ready to install the PMCS software. PMCS should be installed last, after  
all other software installations are completed. Your PMCS software is provided  
on a CD-ROM.  
The diagram below depicts the relationship of the Host PC and any optional  
Viewer Workstations in your system. Follow the specific instructions below for  
software installation on Host PCs and Viewer Workstations.  
eLicensing PMCS software  
General Electric Industrial Systems has added security technology that requires  
your PMCS software to be licensed in order to run. A separate license is  
required for each computer that will receive PMCS. Each eLicense Order ID  
that is sent with your order corresponds to one license.  
You license your software as part of the automated PMCS installation process.  
When you launch the installation process the first screen that will appear will be  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
your eLicense Option screen (see below). This screen allows you to either trial  
or fully license your PMCS software.  
720 Hours (30-Day) Trial  
You have the option to Trial PMCS for 720 Hours (30 days) through the 720  
Hours Trial selection on this screen. All functionality of PMCS is available to  
trial users and all configurations made for the software will be maintained from  
one use to the next. A single trial is registered to each PC and may not be  
uninstalled and re-installed for another trial.  
Licensing via the Web  
Choose the Web License option if you have a working Internet connection on  
your PMCS computer. This option will automatically connect you to General  
Electric Industrial Systems’ eLicense distribution system. Once connected, an  
automated process will retrieve your unique PMCS eLicense key.  
24 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selecting the Web License option from the License Option brings you to the  
Web License Screen. This screen requires you to enter your eLicense Order  
ID. This information is contained on the Order Confirmation Sheet that  
accompanied your PMCS software or it can be obtained from your Purchase  
Confirmation e-mail Enter the Order ID and click on Get License to initiate the  
Web connection to General Electric Industrial Systems’ eLicense distribution  
system.  
Similar to the trial, each eLicense is registered to the computer in which case,  
the eLicense Order ID can only be used for one computer The software must  
be unlicensed to be re-licensed with the same eLicense Order ID on another  
computer Select Launch from your License Installation Success Screen to  
continue installing PMCS.  
Host PC Installation  
Every PMCS system requires one Host PC that is directly connected to the  
PMCS network and communicates with the power-management devices. The  
Host PC is also typically used to view and analyze data.  
If you are installing multiple PMCS catalog numbers on the Host PC, you will  
need the CD and serial number from each package. Follow the Installation Steps  
section below. If the Host PC will be providing data to View Nodes, be sure to  
refer to GEH-6510, Network and Device Configurator, to configure NetDDE  
for operation with the View Node PCs.  
Viewer Workstation Installation  
PMCS supports optional Viewer Workstations, which interact with the power-  
management network through NetDDE links to the Host PC. Viewer  
Workstations are not directly connected to the PMCS network but are connected  
via LAN to the Host PC. Viewer Workstations are not mandatory in a PMCS  
system because the data is available for display and analysis at the Host PC.  
When installing PMCS View Nodes, be sure to use only an appropriate catalog  
number for the installation. Do not install any other PMCS software on a PMCS  
Viewer Workstation.  
NOTE: The EPM software differs from the standard PMCS usage of Viewer  
Workstations. Refer to the section titled EPM Device - Special Considerations  
for more details on EPM Workstations and View Nodes.  
PMCS Installation Steps  
Note:  
1. When the system on which PMCS is being installed is not having any  
database server installed on it. The PMCS 6.15 installation will go  
ahead by installing MSDE 2000 for PMCS databases. This is applicable  
for all licenses where database installation takes place.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. When the system on which PMCS is being installed is not having any  
.Net Framework installed on it. The PMCS 6.15 installation will go  
ahead by installing .Net Framework 1.1.4322. This is applicable for all  
licenses.  
3. When the on which PMCS is being installed is not having IIS installed.  
The PMCS setup gives option to cancel installation, install IIS and start  
PMCS setup again or continue with the installation. If continued with  
installation without IIS installation then the installed PMCS system  
cannot be used by Remote Viewer Installation to connect as a PMCS  
Server setup. On Windows 2003 Server machine, after IIS is installed  
run the steps mentioned in “Application Note 120 – Adding ASP.net  
component in W2K3 Server. PDFeither after PMCS installation or  
after PMCS installation.  
4. During the steps of installation, if cancel button is clicked then finish  
dialog pops up. When Finish is clicked a message box titled “Internal  
Error” pops up. Please click ok and it will cancel the installation. AT  
any point of time you can again start with the PMCS installation  
without any problem.  
Follow the procedure below to install each PMCS catalog number. Be sure the  
catalog numbers you are installing are appropriate for the destination PC (Host  
PC or View Node). Close any open applications before installation.  
1. Insert the PMCS Installation CD into the CD-ROM drive.  
2. Click the Start button from the Windows 2000 SP4 Task Bar and select  
Run.  
26 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. In the Run dialog box, enter X:\setup (where X is the appropriate CD-ROM  
drive designation).  
4. The below screen is observed when .Net is not installed on the machine  
where PMCS is being installed.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
28 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Click on I agree and click on Install button. It will now install .Net  
Framework on the machine where PMCS installation is started. After the  
.Net installation is completed below message box is displayed. Click OK to  
continue.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. GE PMCS 6.15 welcome screen appears. When you select the Next button in the  
Welcome screen, the PMCS license agreement screen is shown. Please take a moment to read  
over the license agreement, and then click Yes.  
30 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. At the User Information screen shown below, enter your name, your  
company name, and the serial number for the PMCS component you are  
installing. Serial numbers for PMCS components are located on the PMCS  
CD-ROM jewel case. If you make an error in the serial number, the  
installation routine will prompt you for a correct PMCS serial number.  
When you have completed the registration information, click Next.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When you select the Next button in the User Information screen, a registration  
confirmation screen prompts you to verify your entries. Ensure that you have  
made no mistakes in the User Information fields, and then continue.  
8. If IIS is not installed in the Machine for the licenses it is required. Below  
message pops up. Click ok to continue without IIS or click cancel to abort  
PMCS installation, install IIS and start PMCS setup again.  
32 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
At the Choose Destination Location dialog, specify a drive on which to  
install PMCS. Default is “C”. Click Next to continue.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. At the Setup Type screen, select Custom installation, standard PMCS  
installation, or PMCS with EPM 7700 Components. PMCS installation is  
recommended and will install all components for the PMCS catalog number  
you entered in the User Information screen. Select PMCS with EPM 7700  
Components if you will be installing EPM 7700, EPM 7600 or EPM 7500  
devices in your network. Select Custom if you wish to select specific PMCS  
software components to install. Choose the type desired and Click Next to  
continue.  
NOTE: This dialog does not appear for certain license keys of PMCS, they are -  
PMCS View node license where Remote Viewer gets installed, for low cost server  
catalog, for SCADA catalog, for Only Serves catalog. After step 8 the step 13  
follows. Otherwise the below steps are followed.  
If you select PMCS with EPM 7700 Components, you may also be required to  
view an additional license agreement for MS Data Access components. This  
software is required by the EPM 7700 software. Take a moment to read the  
license agreement information, then continue.  
34 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. If you did not select “PMCS with EPM 7700 Components” in the Setup  
Type dialog box (Step 9), skip this step and proceed to Step 13.  
If you are installing the EPM 7700 Components, select whether this is to be a  
Primary node installation or Secondary node installation. You must install at  
least one Primary node on your PMCS network; it is recommended that you  
install the Primary node at the same machine as the PMCS DDE Server for  
convenience in configuration. Secondary nodes are akin to PMCS view nodes  
and may be installed on remote machines to access EPM 7700 data from the  
Primary node. (For additional details on Primary and Secondary nodes, see the  
section on configuring EPM 7700 components later in this chapter.)  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. If you did not select “PMCS with EPM 7700 Components” in the Setup  
Type dialog box (Step 9) or if you selected “Primary Node Installation” in  
Step 10, skip this step and proceed to Step 13.  
If you selected Secondary Node installation in Step 10, the following dialog box  
appears prompting you to select either "Full Station" or "Stationless" node  
installation. If you are installing software on a computer that will service EPM  
7700, EPM 7600 or EPM 7500 IEDs directly, choose "Full Station". If you are  
installing software on a computer that will not be connected to IEDs but will be  
used to access data from other network workstations, choose "Stationless". For  
more details on EPM 7700 network configuration, refer to the EPM Device  
Special Considerations section later in this manual, or to DEH-40035, the GE  
7700 Gateway User’s Guide.  
36 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12. If you did not select “PMCS with EPM 7700 Components” in the Setup  
Type dialog box (Step 9), or if you selected “Primary Node Installation” in  
Step 10, skip this step and proceed to Step 13.  
If you selected Secondary Node installation in Step 9, the following dialog box  
appears prompting you for the name of the computer on which the Primary  
Node is installed.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13. Select the Program Folder for PMCS installation. It is recommended that  
the default Program Folder be chosen. Click Next to continue.  
38 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14. If you chose the “PMCS” installation, you may be presented with one DDE  
Server selections depending upon the PMCS catalog number you entered in  
the User Information screen. Select this DDE communication server if you  
wish to use it on your system. By default it is selected you can deselect it if  
intend to not to use it.  
15. If you chose the “Custom Installation” then you will be presented with the  
dialog which gives option to select one DDE Server which is EIND, option  
to select or deselect the wizards installation and option to select or deselect  
EPM7700 components. the dialog shown looks as mentioned below.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16. The Selected Components screen offers you the opportunity to verify the  
installation settings before any files are copied to your hard drive. Confirm  
that the installation settings are correct, then click Next. The installation  
program copies the appropriate files to your hard drive.  
If you have selected the EPM 7700 System Components (either manually when  
performing a Custom install or automatically when PMCS with EPM 7700  
Components install is selected), the installer will check your system for a copy  
of Microsoft Internet Explorer, version 3.02 or higher. This is because the EPM  
7700 software components use .html-format help files which require Internet  
Explorer to view. If Internet Explorer is not found, the following dialog box  
appears:  
If you wish to view the EPM 7700 software help files, you should separately  
install Microsoft Internet Explorer, version 3.02 or higher. (To take advantage  
of all available help system features, Internet Explorer version 4.0 or higher is  
required.) Internet Explorer is not included as part of PMCS. You may obtain  
the latest version of Internet Explorer by downloading it from  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17. After completing the selected PMCS installation, the installation program  
checks the host PC for an older version of the POWER LEADER Modbus  
Monitor Proxy software. If the installer locates the Proxy software, it  
prompts you to update the Proxy to the PCMS 6.xx-compatible version  
before finishing the PMCS installation routine. (If your system does not use  
POWER LEADER Modbus Monitor devices or does not have the Monitor  
Proxy software installed, the PMCS installer will skip this step.)  
18. At this point, the installation program copies the appropriate files to your  
hard drive.  
19. After the Setup program finishes installing the PMCS components you have  
selected, you will be prompted to install the Adobe Acrobat Reader  
software. If you do not have Acrobat Reader 5.0 or later installed on your  
PC, you may wish to install Acrobat Reader at this time. The PMCS CD-  
ROM includes a full complement of technical documentation in Acrobat  
PDF format which may be viewed with the Acrobat Reader program. The  
documentation is located in the TechDocs directory of the CD-ROM.  
20. When all the installations are complete, the Setup Complete dialog box,  
shown below, prompts you to restart your computer.  
42 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If No is selected and clicked on finish it will prompt the below message box and will  
again redirect to the above dialog asking to restart. So select Yes to restart at this  
dialog.  
After restarting your computer, be sure to view the ReadMe file to check any late-  
breaking information useful to the configuration or operation of your PMCS system.  
NOTE: Your computer MUST be restarted after installing PMCS software. This step is  
critical to proper operation of the software, as it enables the following to happen:  
The operating system will register the new software components.  
The MMS Server (if installed) will update its alias table.  
Initial network configurations for EPM7700, EPM 7600 and EPM 7500 devices will  
be created.  
It will startup the main Application of the PMCS system which is EnerVista Status  
Tool which enables the use of all the other PMCS components.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
.
After PMCS IIS – Setting up PMCS Server  
For any PMCS remote viewer system to connect to the PMCS server, the  
prerequisite is to have IIS installed on the PC first then .Net Framework  
installed on the same PC and after that installation of PMCS. But if PMCS is  
installed before IIS is installed on any PC then please follow the steps  
mentioned in the below:  
For Windows 2000 SP4 / Windows XP SP2 OS  
1. Install PMCS with server licences  
2. Install IIS  
3. In the PMCS CD – there is dependencies folder .  
3a. Double click on the dependencies folder.  
3b. Double click on the PMCS_FS_Web folder  
3c. Double click on PMCS_FS_WEB.bat file  
3d. Double click on PMCS_FS_WEB.msi file.  
3e. It will prompt with the startup dialog click on Next will install the  
required components to make it to work for PMCS Remote Viewer  
Connectivity.  
3f. Installation successful window is poped. Click Close to complete  
the setup.  
For Windows 2003 Server machine follow the below steps:  
1. First Install PMCS  
2. Install IIS  
3. Follow the steps mentioned in “Application Note 120 – Adding ASP.net  
component in W2K3 Server. PDFkept in PMCS installation  
CD\Tech_Doc\GE_CD\Application Notes. This step can be executed  
either after PMCS is installed or before PMCS is installed but after IIS  
is installed.  
4. In the PMCS CD – there is dependencies folder.  
3a. Double click on the dependencies folder.  
3b. Double click on the PMCS_FS_Web folder  
3c. Double click on PMCS_FS_WEB.bat file  
3d. Double click on PMCS_FS_WEB.msi file.  
3e. It will prompt with the startup dialog click on Next will install the  
required components to make it to work for PMCS Remote Viewer  
Connectivity.  
3f. Installation successful window is popped. Click Close to complete  
the setup.  
This will make the setup complete for setting up the PMCS server if IIS is  
installed after PMCS.  
Un-elicensing PMCS  
44 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
In order to unlicense your software to use your eLicense Order ID for another  
computer – you must have an internet connection. To retrieve your license for  
use on another PMCS installation, simply right click on any PMCS executable  
on your desktop and select unlicense.  
The screen will request the eLicense Order ID to be entered.  
A screen will appear to indicate that you have successfully un-eLicensed and  
you may now take the eLicense Order ID for use on another PMCS installation.  
Please note that you can not retrieve an eLicense for re-use through the  
unlicense process past 3 years of initial Licensing.  
Uninstalling PMCS  
All PMCS software is provided with an uninstall utility to fully remove PMCS  
components from your system. Uninstalling PMCS will permanently delete any  
configuration information.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: The Uninstaller may not delete some files such as error logs, system  
logs, and configuration records, which are created after the PMCS installation is  
complete. Since these files are not part of the initial installation, they will not be  
removed by the Uninstaller, and must be deleted manually.  
If you are uninstalling EPM 7700 components, be aware that the Pegasys  
System Log Service does not properly unregister itself as an NT Service. The  
following procedure will allow you to manually uninstall this component: the  
remaining PMCS software can then be uninstalled in the usual manner.  
Uninstalling the Pegasys System Log Service:  
1. Open a Command Prompt window.  
2. Make the C drive the current directory (assuming your Windows system  
files reside on the C drive).  
3. Type “slservice –e” EXACTLY as shown and hit enter.  
4. If the Pegasys System Log Service was installed and running you will  
receive the message “Pegasys System Log Service stopped”. If you do not  
receive this message, the Log Service was not installed on your system.  
Exit the command prompt and continue uninstalling PMCS.  
5. If you received the correct message in step 4, uninstall the service. Type  
“slservice –u” EXACTLY as shown and hit enter. A message appears  
indicating “Pegasys System Log Service uninstalled”. Exit the command  
prompt and continue uninstalling PMCS.  
46 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reinstallation Steps  
Follow the procedure below to reinstall your PMCS software.  
1. If your system includes the PMCS Interface Toolkit, uninstall the  
CIMPLICITY Wizards from any third-party HMI tools.  
2. Close any open applications.  
3. Insert the PMCS Version 6.15 CD into the CD-ROM drive.  
4. From Start menu, select Run and enter X:\setup (where X is the  
appropriate CD-ROM drive designation).  
5. Read the general information and disclaimers shown on the screen and click  
Next.  
6. Enter your name, your company name, and the serial number located on the  
PMCS CD jewel case, then click Next. If you make an error in the serial  
number, the installation routine will prompt you for a correct PMCS serial  
number.  
7. Choose the installation type; either PMCS, PMCS with EPM 7700  
Components, or Custom installation. PMCS or PMCS with EPM 7700  
Components installation will reinstall all components of the appropriate  
PMCS catalog number. Select Custom if you wish to reinstall only selected  
PMCS software components.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Upgrading from previous versions to PMCS 6.15  
PMCS 6.15 provides an easy-to-use, automatic upgrade path from previous  
versions of PMCS. The software installer examines your hard drive and, if it  
locates any previous version of PMCS, it makes decisions on upgrading each  
component.  
Follow the procedure below to upgrade your currently installed PMCS version  
(such as 5.0, 5.1, or 6.xx) to PMCS version 6.15. This procedure assumes you  
have an existing PMCS installation with configured ports, topics and  
(optionally) generic topics, and that CIMPLICITY Wizards are installed in the  
generic HMI application.  
WARNING: PMCS 5.1 and PMCS 5.1b Modbus DDE Server users only:  
Upgrading from PMCS 5.1 to PMCS 6.15 may cause the Modbus version of the  
DDE Server to lose its port configuration. You may need to reconfigure your  
communications ports from the PMCS DDE Server after upgrading. The  
Ethernet version of the DDE Server is not affected.  
PMCS 5.0 users: Port configuration is lost when a PMCS 5.0 configuration file  
is converted to a PMCS 5.1b configuration file. You will need to reconfigure  
your communications ports from the PMCS DDE Server. Refer to GEH-6510  
for instructions. Also, any generic topics you may have configured at the PMCS  
DDE Server will be lost, and you will need to re-configure these generic topics.  
Note: While upgrading the previous versions to PMCS 6.15, a message appears  
saying that EPM 7330 device is configured as a generic device and in PMCS  
6.15 this device is a tightly integrated device. Ignore this message and proceed  
further.  
1. Close any open applications, and insert the PMCS 6.15 CD into the CD-  
ROM drive.  
2. From Start menu, select Run and enter X:\setup (where X is the appropriate  
CD-ROM drive designation).  
3. Read the general information and disclaimers shown, then click Next.  
4. Enter your name, your company name, and the serial number located on the  
PMCS CD jewel case, then click Next. If you make an error in the serial  
number, the installation routine prompts you for a correct PMCS serial  
number.  
5. Choose either PMCS, PMCS with EPM 7700 Components or Custom  
installation. PMCS or PMCS with EPM 7700 Components installation will  
reinstall all components of the appropriate PMCS catalog number. Select  
Custom if you wish to reinstall only selected PMCS software components.  
6. After upgrading, existing HMI applications that use PMCS wizards will  
continue to work. If you upgrade device firmware you will need to replace  
the old wizard screens with new screens to maintain compatibility between  
your application and the device. The old PMCS wizards will remain on  
your system unless you uninstall the previous version of PMCS. It is highly  
recommended that all new applications use PMCS 6.15 Advanced wizards  
exclusively.  
7. After upgrading, launch the PMCS DDE Server. The Server will convert  
your previous PMCS configuration to a PMCS 6.15 configuration.  
48 Installing the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: Event Logger users only: Upgrading your EventServer or  
Eventlogger application will result in the loss of all device configurations and  
annunciator panel items. Make a list of these items so that they may be  
reconstructed in the new application.  
Copy the existing PMCS EventLogger database files before starting the  
installation as they will be overwritten by the 6.15 installation. To view  
databases created with earlier editions of PMCS, use Microsoft Access to open  
the .mdb files.  
WARNING: Generic Device users only: On upgrading earlier versions of  
PMCS with PMCS 6.15, take the backup of Generic device by following this.  
Export the device registry groups information and device mnemonic information  
before starting the installation and import them back after PMCS 6.15  
installation is completed.  
CIMPLICITY PMCS Read-This-Book-First  
Installing the Software 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Working with Cimplicity Viewer  
Node  
How to view the screens on a viewer node  
To configure the project on a Cimplicity viewer node, running on a HMI server,  
follow the directions below.  
1) Install Cimplicity HMI 6.1 SP5 on one machine with HMI Server option on  
a Windows 2000 SP4 machine.  
2) Install PMCS 6.15 on the same machine with the serial numbers given.  
3) Install Cimplicity HMI 6.1 SP5 on another machine with Viewer Runtime  
option on a Windows 2000 SP4 machine.  
4) Install PMCS 6.15 on the same machine with the serial numbers given for a  
viewer node, which installs Runtime wizards and WC and EV only.  
5) Now create a project in HMI Server node, with Enable project Broadcast  
option. Drop the wizards which contains LFP and also tab selection mode  
wizards.  
6) On the viewer node now map the drive (preferably Cimplicity Directory) of  
HMI server node.  
7) Important Note: On the viewer node neither you copy the project nor  
screens.  
8) Now after mapping the drive, open the MainMenu.cim file, which is on  
HMI server node from the Viewer node. Or On the viewer node, Go to  
Start\Programs\Cimplicity\HMI\Cimview-> Common dialog box  
appears, select\point the Mainmenu.cim file (obviously on the HMI server  
node’s file). See the following figure.  
9) Open the small faceplate wizard files to get the configured screens.  
50 Working with Cimplicity Viewer Node  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CIMPLICITY PMCS Read-This-Book-First  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring the Software  
To get the most out of your new PMCS system, follow the directions below to  
configure your system.  
Organize Your Information  
Host PC  
You need the following information to properly configure the PMCS software  
for the Host PC. This information is used throughout the configuration process  
and you should archive it for any future maintenance of your system.  
For RS485 PMCS network interfaces, you need to list all devices in the power-  
management network (including Modbus Concentrators) with associated device  
types, Modbus RTU addresses, and COM ports. Assign names of less than 20  
characters (no spaces) to these devices.  
For example, in a simple system with four devices (and one Modbus  
Concentrator), you may have a table similar to the following:  
COM port  
Modbus RTU Address  
Device Type  
MODCONC  
E3720  
Device (Topic) Name  
MCI  
1
1
1
1
2
2
12  
33  
61  
210  
Main_Meter  
Mfg_Meter  
PLEPM  
MVT  
Mfg_Breaker  
Mill_Relay  
ML269  
For an Ethernet PMCS network interface (Ethernet Gateway), you must list all  
devices in the power-management network, including the device types and  
Modbus RTU addresses. You need to know the appropriate Ethernet Gateway  
IP address and COM port (1–4) to which each device is connected. Assign  
names of less than 20 characters (no spaces) to these devices.  
For example, in a simple system with 10 devices, you may have a table similar  
to the following (this system uses one Ethernet Gateway and other devices).  
52 Configuring the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ethernet Gateway COM  
Modbus RTU  
Address  
IP Address  
port  
Device Type  
EPM 9650Q  
E3720  
Device (Topic) Name  
E9650Q  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
10.47.28.201  
1
2
1
12  
Main_Meter  
Mfg_Meter  
1
33  
PLEPM  
PLEPM  
UR L90  
PLEPM  
PLM  
1
61  
Plating_Meter  
UR  
2
12  
2
66  
Office1_Meter  
Office2_Meter  
Feeder1_Relay  
Mfg_Breaker  
Mill_Relay  
2
80  
2
90  
MDP  
2
100  
200  
21  
MVT  
3
ML269  
4
EPM5350P  
MVT  
E5350P  
4
201  
210  
Plating_Breaker  
Office_Breaker  
4
MVT  
View Node  
You should configure View Nodes after you have configured and tested the  
Host PC to ensure all functions are operating. View Nodes require a copy of the  
network architecture list used above. Refer to GEH-6510, Network and Device  
Configurator, for complete configuration instructions.  
CIMPLICITY PMCS Read-This-Book-First  
Configuring the Software 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Procedure  
Follow the procedure below to efficiently configure your system and minimize  
your time to startup.  
Host PC Configuration  
1. Configure the DDE Server. Your Host PC will likely have several versions  
of the DDE Server installed (RS485-Modbus, TCP/IP Modbus, TCP/IP  
Encapsulated Modbus and Ethernet-TCP/IP). Configure only the server  
appropriate for your PMCS network interface (GE32MODB, GE32MTCP,  
GE32GTWY or GE32ENET). See GEH-6510, Network and Device  
Configurator, for complete details.  
2. EPM 7700, EPM 7600 and EPM 7500 users only (all others proceed to  
step 3): Configure the Communications Server and GE 7700 Gateway  
Server. If you installed the EPM software options and you are going to use  
EPM 7700, EPM 7600 or EPM 7500 devices in your PMCS network, you  
will need to configure both the Communications Server and the GE 7700  
Gateway Server. For Comm Server configuration instructions, refer to EPM  
Software Components Configuration later in this guide. For GE 7700  
Gateway Server configuration instructions, refer to DEH-40035, the GE  
7700 Gateway Server User’s Guide.  
3. Configure the user interface. If your system was provided with a generic  
HMI software application, either load or create the custom HMI (using the  
Interface Toolkit wizards, if appropriate; see DEH-210, CIMPLICITY  
PMCS Interface Toolkit or refer to the HMI software’s documentation.  
4. Configure the applications. As appropriate, configure the following  
application modules, referring to the instruction manuals provided.  
Event Logger, GEH-6512  
Waveform Capture, GEH-6511  
5. Test the applications. Test the functioning of all applications to ensure  
proper Host PC operation. Do not proceed to step 5 until you are sure the  
Host PC operates as expected.  
6. Set up NetDDE. If your system has one or more View Nodes, set up  
NetDDE shares and trusts in the Host PC, following the procedures in  
GEH-6510, Network & Device Configurator and the CIMPLICITY HMI  
documentation.  
7. Set up NetDDE. If your system uses the PMCS Waveform Capture client,  
and you intend to access waveform data from View Nodes, set up NetDDE  
shares and trusts for the PMCS Waveform Server following the procedures  
in GEH-6511, PMCS Waveform Capture Module.  
Viewer Workstation Configuration  
1. Configure the user interface. Load the custom HMI. Refer to the  
CIMPLICITY HMI documentation as appropriate.  
2. Configure the applications. As appropriate, configure the application  
modules, referring to the instruction manuals provided. See step 3 of the  
Host PC Configuration for the appropriate instruction manual numbers.  
54 Configuring the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EPM Software Components Configuration  
The EPM 7700, EPM 7600 and EPM 7500 requires several separate software  
components which are installed during the PMCS setup. This section provides a  
brief overview of the steps required to configure these components; the  
following section describes the EPM software components in greater detail.  
For details of using the NetBuilder software, refer to the Configuring the EPM  
7700 Device Network section of this manual, and to DEH-440035, the GE 7700  
Gateway User’s Guide.  
1. Launch the NetBuilder application. From the Start menu, select  
Programs>Power Management Ltd>Utilities>Network Builder.  
2. Insert a workstation(s). Normally all the workstations in a PMCS network  
are automatically configured during the installation of the software – these  
instructions are provided in case you need to enter the information  
manually. Select the Items menu from NetBuilder, and choose Workstation  
to insert a workstation. Name the workstation (up to 15 alphanumeric  
characters, the first character must be alphabetic), and choose OK. Repeat  
this step for each workstation (computer) in your network.  
3. Insert Ethernet Sites. Select Items>Insert>Ethernet Site to insert an Ethernet  
site. Set the proper time synchronization options, then choose OK. Repeat  
this step to add additional sites to the workstation if necessary.  
4. Insert devices to the site. Select Items>Insert>Device, and complete the  
dialog box with the proper device type, Group, Ethernet address and name  
for an Ethernet device (EPM 7700, EPM 7600 or EPM 7500). The device  
name may be no more than eight alphanumeric characters, and the first  
character must be alphabetic. The IP service port field must be "7700" for  
any device connected to the Ethernet, and "7800" for any additional device  
connected through an EPM 7700’s RS485 port. Choose OK to close the  
Insert Device dialog box. Repeat this step as necessary to add additional  
devices to the site.  
5. Save and exit. When all workstations, sites, and devices have been added,  
select the save icon and then exit.  
CIMPLICITY PMCS Read-This-Book-First  
Configuring the Software 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally)  
56 Configuring the Software  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EPM Device-  
Special Considerations  
Introduction  
The GE EPM 7700, EPM 7600 and EPM 7500 devices add new level of power  
management capabilities to PMCS. These EPM devices also require some  
special configuration which is not necessary for other PMCS-compatible  
devices. This section describes the additional requirements and configuration  
steps necessary to use the EPM 7700, EPM 7600 and EPM 7500 in conjunction  
with PMCS.  
NOTE: If you are not using the EPM 7700, EPM 7600 or EPM 7500 meters in  
your PMCS network, it is not necessary to read this section of the manual.  
Although the EPM 7700, EPM 7600 and EPM 7500 meters are compatible with  
PMCS and its client applications (Waveform Capture, custom wizards, etc.),  
and EPM 7700, EPM 7600 and EPM 7500 meters may co-exist on the same  
Ethernet as other PMCS network segments, the EPM 7700, EPM 7600 and EPM  
7500 use a slightly different metaphor than a straight PMCS network. An EPM  
device power-monitoring network is comprised of a number of nodes that are  
connected to the PMCS workstation through Ethernet links. Nodes in the  
power-monitoring network are IEDs such as the EPM 7700 meter (power  
meters are also referred to ‘meters’ or ‘devices’). IEDs may be distributed  
across one or more networks as required to service the particular application.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device-Special Considerations 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EPM Software Components  
There are four major components of the EPM software. The Network Builder,  
ION Designer, Communications Server, and ION_LINK DDE Server each  
interact to support the EPM 7700, EPM 7600 and EPM 7500 Meters. When you  
selected the “PMCS with EPM 7700 Components” selection during the PMCS  
installation routine, these software components were installed automatically.  
The four components and their functions are described below.  
Network Builder: Building the Network  
Configuration File  
The Network Builder presents a graphical view of the EPM 7700, EPM 7600  
and EPM 7500 devices in your network, allowing you to easily add, remove or  
configure sites, services and meters. Network Builder creates a central network  
configuration file that holds information for the workstation, the network  
connections, and every connected device. You may want to restrict access to  
Network Builder or the network configuration file, since if the file is tampered  
with, EPM 7700, EPM 7600 and EPM 7500 components may be rendered  
inoperable.  
ION Designer: Programming Devices and  
Software Nodes  
The ION Designer component allows you to customize the operation of an  
ION-compliant node, such as 7000-series meters and 3000-series meters. Be  
aware that misuse of ION Designer can adversely affect the operation of your  
meters.  
IMPORTANT: For purposes of PMCS network compatibility, it is CRITICAL  
that any EPM 7700, EPM 7600 and EPM 7500 meters be configured with the  
GE PMCS standard configuration. Using ION Designer to customize EPM  
7700, EPM 7600 or EPM 7500 functionality can compromise compatibility with  
the PMCS client applications attempting to access the device.  
Communications Server: System  
Communications  
The Communications Server is the core communications component for EPM  
7700, EPM 7600 and EPM 7500 meters. The Communications Server manages  
all communications between the meters connected to your network and the  
GE77GTWY and ION_Link DDE Server software applications.  
ION_LINK DDE Server: Communication with  
Windows Applications  
The ION_LINK DDE Server uses Dynamic Data Exchange to share  
information with applications such as Microsoft Excel or the CIMPLICITY  
Wizards.  
58 EPM Device-Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Workstation Configuration Guidelines  
If you are using the EPM 7700, EPM 7600 or EPM 7500 Meters in your PMCS  
network, the following guidelines in this section must be adhered to before  
continuing with the EPM configuration.  
NOTE: If you are adding a PMCS installation to an existing network, please  
refer your network administrator to GEH-6502, the PMCS Network Architecture  
Guide, for integration details.  
Each computer in the network must be assigned a Windows 2000  
SP4 computer name. The name must be one to fifteen  
alphanumeric characters in length. Spaces may not be used, and  
the first character of the computer name may not be numeric.  
The System Control Panel should have the Performance Boost for  
Foreground Application value set to None, and a paging file  
should be created on the C: drive with the Initial and Maximum  
sizes set to twice the workstation’s installed RAM.  
The Network Control Panel’s Adapter tab should have the MS  
Loopback adapter installed if a physical network adapter is not  
installed in the workstation. Under the Protocols tab, TCP/IP or  
NetBEUI should be installed; if TCP/IP is installed, use IP address  
192.168.100.xxx and subnet mask 255.255.255.0 unless your  
network administrator has assigned you an IP address. Under the  
Services tab, install Remote Access Server (RAS) and configure it  
by enabling NetBEUI (if using NetBEUI or, if TCP/IP is used,  
assign two or more IP addresses, starting at xxx.xxx.xxx.254 and  
working down. Set RAS to start automatically and set access to  
“entire network” (if available).  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device-Special Considerations 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuring the EPM Device Network  
The PMCS installation routine described earlier in this manual creates initial  
workstation and software node entries in the EPM 7700 network configuration  
file. After EPM 7700 software components are installed, the next step is to add  
Ethernet sites and devices to the PMCS power-monitoring network using  
Network Builder software.  
Running Network Builder  
Network Builder software presents your EPM power-monitoring network  
graphically, showing the installed components in a hierarchical tree. Network  
Builder allows you to edit the Network Configuration file— the file that  
identifies every node in the EPM power-monitoring network.  
The first step is to run Network Builder from the Start Menu: (Programs >  
Power Measurement Ltd > Utilities > Network Builder.)  
The following figure shows how Network Builder displays a system comprised  
of the basic EPM software components, a single EPM 7700 meter, a Primary  
Node and a Stationless Secondary node (also called a ‘view node’).  
Workstation: the network name  
of the Primary Node computer  
running the Communications  
Software nodes: Stationless  
Secondary nodes appear here.  
Ethernet Site: Defines the Ethernet  
connection between the PMCS  
system and the connected device(s).  
Device: Name(s) of attached  
device(s).  
60 EPM Device-Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Building the Power-Monitoring Network in  
NetBuilder  
When Network Builder is running, you can begin configuring your EPM system  
by adding a site to the workstation, then adding devices to the site. For larger  
systems multiple sites are added; one for each network of devices monitored.  
NOTE: The PMCS installation wizard creates initial entries for the workstation  
and software nodes. If you do not need to make changes to the information  
provided during installation, skip this section and begin with the section title  
"Adding an Ethernet Site".  
Adding a Workstation  
When you use the PMCS installation wizard to install a Primary node or Full  
Station Secondary node, it creates a Workstation in the Network Configuration  
for you. Stationless Secondary nodes do not appear in the network configuration  
as workstations, but as software nodes under the Primary workstation. See the  
section on software nodes for more information.  
To add a new workstation, right click “System” and choose “Insert  
Workstation” from the pop-up menu. The “System – Add Workstation” dialog  
box appears as shown below. Type the network name of the computer in the  
“Name” field. (Use the default settings on the “Advanced” tab.) Click “OK, then  
proceed to “Adding Software Nodes” below.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device-Special Considerations 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding Software Nodes  
Software nodes identify the various software components in the network.  
Stationless Secondary nodes, although they are physically separate computers,  
do not run a Communications Server and are therefore not considered  
Workstations by Network Builder. Instead, Stationless Secondary nodes appear  
in the network diagram as software nodes under the Primary Workstation. Full  
Station Secondary nodes appear as Workstations because they do run an  
instance of the Communications Server.  
Acknowledging the Add Workstation dialog brings up a message box asking if  
you want to set up the default software nodes – choose Yes to display the  
software nodes dialog (shown below). Select only ION Designer and Pegasys  
ION_Link DDE Server as shown, then click OK to proceed. The other options  
are not supported in PMCS 6.15.  
62 EPM Device-Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding an Ethernet Site  
An Ethernet site defines the network connection between the devices and the  
Workstation(s). You add Ethernet sites to Workstations, then add devices to the  
sites. To add a new Ethernet site, right-click a Workstation name and choose  
“Insert: Ethernet site” from the pop-up menu – attach it to the current  
Workstation. Click OK to continue.  
An Add Ethernet Site dialog box (shown below) appears.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device-Special Considerations 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Set the following communications parameters for the site.  
Enter the Transmit delay setting (in milliseconds). This setting  
determines the level of traffic on the network. If the PMCS system is  
the sole user of the network, set this value to 5 (or less) to maximize  
performance. Increase the transmit delay in situations where the  
network is shared with other users, such as on a corporate LAN. Refer  
to the PMCS Network Architecture Guide for guidelines on setting this  
parameter for best system performance.  
Change the RX timeout delay from 10000 to 30000 on the Advanced  
tab. (See the following figure for Advanced tab.)  
All other parameters may be left at their default values for most applications.  
When you click OK in the Add Site dialog box, Network Builder will inform  
you if there is additional information you must enter.  
64 EPM Device-Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding Devices (Meters)  
To add a meter, right-click on the Ethernet site you want to add the meter to,  
and select Insert Device… from the pop-up menu. The Add Ethernet Device  
dialog box appears (shown below).  
Enter the following information:  
Choose the meter type from the Type list (Power Measurement 7700  
ION).  
Type a name in the Group box, or choose a Group from the list (by  
default the Group will be the name of the workstation).  
Enter a name for the meter (or accept the default). The meter name  
must begin with a letter.  
Enter the IP address for the meter.  
Enter the IP Service Port number (socket) for the meter. For a 7700,  
7600 and 7500 ION this number is 7700, for a 3720 ACM, 3721.  
Saving and Exiting  
Once you have added all of your sites and devices to the network tree, click the  
Save button (or choose Save from the File menu), and exit Network Builder.  
You have now configured your EPM 7700, EPM 7600 and EPM 7500 meters to  
operate with the PMCS, and you should be able to access EPM 7700, EPM 7600  
and EPM 7700 metering data from PMCS client applications.  
CIMPLICITY PMCS Read-This-Book-First  
EPM Device-Special Considerations 65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(This page left blank intentionally)  
66 EPM Device-Special Considerations  
CIMPLICITY PMCS Read-This-Book-First  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
A
D
E
N
alarm, 4  
NetBuilder, 51  
Network Builder, 51  
O
P
DDE Server, 54  
option modules, 4  
Ethernet, 4, 8, 18, 19, 48, 50  
event, 4  
PEGASYS  
nodes, 53  
Performance, 4  
F
Fanuc, 4  
First Steps, 7  
S
servers  
DDE, 54  
I
Interface Toolkit, 5, 8, 43, 50  
T
TCP/IP, 4, 8, 9, 18, 50  
Technical Support, 3, 7, 12  
Terminology, 7  
M
minimum system requirements, 3  
Modbus Monitor Proxy, 39  
Modbus RTU, 4, 8, 48  
W
waveform capture, 4  
Windows NT, 9, 18, 21  
CIMPLICITY PMCS Read-This-Book-First  
Index 67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GE MULTILIN  
General Electric Company  
215 Anderson Avenue, Markham ON, L6E 1B3,  
CANADA USA & Canada: 1-800-547-8629 Global: (905) 294-6222 Fax: (905) 201-2098  
Email: multilin.tech@indsys.ge.com <mailto:multilin.tech@indsys.ge.com>  
DEH-211 R12 03/02  
© 2000 – 2006 General Electric Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Chainsaw 2CS 450 User Manual
Eizo Computer Monitor L350P User Manual
Elation Professional Indoor Furnishings 216 User Manual
Electro Voice Microphone CT30 User Manual
Festool Sander DTS 400 Q User Manual
Fluke Marine Instruments 700G User Manual
Fujitsu Video Game Controller PG RMCU1 User Manual
GE Freezer FUF21SVRWW User Manual
GE Mixer 169024 User Manual
Global Upholstery Co Patio Furniture 2400 18 User Manual