EVERGREEN®
Product
Data
23XRV
High-Efficiency Variable Speed Screw Chiller
with FOXFIRE™ Compression Technology
50/60 Hz
HFC-134a
300 to 550 Nominal Tons (1055 to 1934 Nominal kW)
®
Carrier’s Evergreen® 23XRV chiller is
the world’s first integrated variable
speed, water-cooled, screw chiller.
It incorporates significant break-
throughs in water-cooled chiller tech-
nology to provide excellent reliability
and achieve superior efficiencies at
true operating conditions without com-
promising the environment.
The 23XRV chiller provides:
• Variable speed, positive
displacement screw compressor.
• Air Conditioning, Heating, and
Refrigerant Institute (AHRI) certified
efficiencies to 0.33 kW/ton (AHRI
IPLV).
• Chlorine-free HFC-134a refrigerant.
• IEEE-519 compliance for harmonic
distortion.
• An ideal solution for constant and
variable flow pumping systems.
Features/Benefits
Quality design and con-
struction make the Evergreen
23XRV chillers the best
choice for modern, efficient
chilled water plants.
Product reliability
The 23XRV chiller uses proven tech-
nology from Carrier’s existing line of
23XRV
Evergreen chillers along with innova-
tions that increase reliability. The
23XRV compressors are designed for
extremely high reliability. The ad-
vanced tri-rotor compressor features a
balanced rotor geometry and shorter
SEISMICOMPLIANT*
* Meets IBC 2006, ASCE-7-05, CBC 2007, and OSHPD seismic requirements.
screw lengths, resulting in vastly re-
duced compressor bearing loads and a
minimum L10 compressor bearing life
in excess of 500,000 hours when op-
erated at AHRI conditions.
2008 AHR EXPO®
INNOVAATION
AWARD
WINNER – Green Building
Copyright 2010 Carrier Corporation
Form 23XRV-3PD
Download from Www.Somanuals.com. All Manuals Search And Download.
• Machine room cooling requirements input power leads to the VFD provides refrigerant more evenly over the
associated with air-cooled motors, all unit power.
which dissipate heat to the mechan-
length of the vessel for improved
efficiency.
Closely spaced intermediate sup-
port sheets — Support sheets pre-
Marine container shipment — The
ical room.
compact design allows for open-top
container shipment to export destina-
tions, ensuring quality while reducing
shipping cost.
• High noise levels common with air-
cooled motors, which radiate noise
to the machine room and adjacent
areas.
Heat exchanger combinations —
The Evergreen 23XRV chillers are
available with a complete line of heat
exchangers, ensuring the best combi-
nation of chiller components to meet
project specific tonnage and efficiency
requirements. One, 2 and 3-pass
arrangements are available to meet a
wide variety of flow conditions. Nozzle-
in-head and marine waterboxes are
available to meet 150 psig and
• Shaft alignment problems that occur
with open-drive designs during start-
up and operation, when equipment
temperature variations cause ther-
mal expansion.
Positive pressure design — Posi-
tive pressure designs eliminate the
need for costly low pressure contain-
ment devices, reducing the initial cost
of the system. The Evergreen® 23XRV
chiller’s positive pressure design en-
sures that air, moisture and other per-
formance degrading contaminants are
not sucked inside the chiller. Purge
units and their associated mainte-
nance are no longer necessary.
Optional refrigerant isolation
valves — The optional refrigerant
isolation valves allow the refrigerant
to be stored inside the chiller during
shipment from the factory, minimizing
start-up time. During servicing, the
“in-chiller” storage reduces refrigerant
loss and eliminates time-consuming
transfer procedures. As a self-contained
unit, the Evergreen 23XRV chiller does
not require additional remote storage
systems.
Optional pumpdown unit — Com-
bined with the refrigerant isolation
valves listed above, the optional pump-
down unit eliminates complex connec-
tions to portable transfer systems,
thereby reducing service costs. The op-
tional pumpdown compressor meets
Environmental Protection Agency’s
(EPA) vacuum level requirements that
mandate minimizing refrigerant emis-
sions during service.
300 psig piping requirements.
Heat exchanger features
ASME certified construction — An
independent agency certifies the
design, manufacture, and testing of
all heat exchangers to American
Society of Mechanical Engineers
(ASME) standards, ensuring heat ex-
changer safety, reliability and long life.
The ASME U-stamp is applied to the
refrigerant side of the evaporator and
condenser and is applied to the water
side of heat exchangers when 300 psig
marine water boxes are provided.
High performance tubing — Carrier’s
Evergreen chillers utilize advances in heat
transfer technology, providing compact,
high-efficiency heat exchangers. Tubing
with advanced internally and externally
enhanced geometry improves chiller per-
formance by reducing overall resistance
to heat transfer while reducing fouling.
Cooler tube expansion — Cooler
tube expansion at center support
sheets prevents unwanted tube move-
ment and vibration, thereby reducing
the possibility of premature tube fail-
ure. Tube wall thickness is greater at
the expansion location, support sheets,
and end tube sheets in order to provide
maximum strength and long tube life.
Double-grooved end tube sheet
holes — This design provides a more
robust seal than single rolled joints, re-
ducing the possibility of leaks between
the water and refrigerant sides of the
chiller.
Modular construction — The cool-
er, condenser, and compressor assem-
blies are bolted together, making Ever-
green 23XRV chillers ideally suited for
replacement jobs where ease of disas-
sembly and reassembly at the jobsite
are essential.
Single point power — The 23XRV
chiller features internal control power
transformers to provide low voltage
power (115 v and 24 vdc) for machine
controls. Simply connecting the three
Condenser baffle — The baffle de-
flects hot discharge gas before it con-
tacts condenser tubes, reducing tube
vibration and wear while distributing
3
Features/Benefits (cont)
feature also allows the machine to
operate at reduced capacity, rather
Ramp loading — Ramp loading en-
sures smooth pulldown of liquid loop
can be prevented through password
protection. Built-in diagnostic capabili-
ties assist in troubleshooting and rec-
ommend proper corrective action for
preset alarms, resulting in greater
working time.
than shut down, when key safety limits temperature and prevents a rapid
are approached.
increase in compressor power con-
sumption during the pulldown period.
Chilled liquid reset — Reset can be
accomplished manually or automatical- Automated controls test — The
ly from the building management sys-
tem. For a given capacity, reset allows
operation at slower compressor
speeds, saving energy when warmer
chilled liquid can be used.
Demand limiting — This feature lim- a yearly schedule for each week, week- last 25 alert messages in memory. This
its the power draw of the chiller during ends, and holidays.
peak loading conditions. When incor-
porated into the Carrier Comfort
Network® building automation system,
a red line command holds chillers at
their present capacity and prevents any
other chillers from starting. If a load
shed signal is received, the compres-
sors are unloaded to avoid demand
charges whenever possible.
test can be executed prior to start-up
to verify that the entire control system
is functioning properly.
365-day real time clock — This
feature allows the operator to program Alert file — This file maintains the
Alarm file — This file maintains the
last 25 time-and date-stamped alarm
messages in memory. This function re-
duces troubleshooting time and cost.
function provides prognostic informa-
tion and corrective actions that can
avoid unit shutdown.
Configuration data backup —
Non-volatile memory provides
protection during power failures and
eliminates time consuming control
reconfiguration.
Occupancy schedules — Schedules
can be programmed into the controller
to ensure that the chiller operates
when cooling is required and remains
off when not needed by the tenants or
process.
Extensive service menu — Unau-
thorized access to the service menu
Model number nomenclature
S–Special
Not Used
23XRV – High Efficiency
Variable Speed Screw Chiller
Voltage Code
3 –380-3-60
4 –416-3-60
5 –460-3-60
9 –380/415-3-50
Cooler Size*
30-32
35-37
40-42
45-47
50-52
55-57
Drive
Code
AA
Amps
In†
440
520
520
608
Amps
Out†
442
Condenser Size*
30-32
35-37
BA
442
BB
CC
520
608
40-42
45-47
50-52
55-57
Motor Code
P
Q
R
S
T
U
V
a23-1648
Economizer Option
E – With Economizer
N – No Economizer
*First number denotes frame size.
†Maximum limits only. Additional application
limits apply that may reduce these ampacities.
R – Compressor
Quality Assurance
Certified to ISO 9001:2000
AHRI (Air Conditioning, Heating
and Refrigeration Institute)
Performance Certified
ASME
‘U’ Stamp
SEISMICOMPLIANT*
* Meets IBC 2006, ASCE-7-05, CBC 2007, and OSHPD seismic requirements.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Physical data
23XRV COMPRESSOR AND MOTOR WEIGHTS
ENGLISH
Motor
SI
Total
Motor
Terminal
Cover
(kg)
MOTOR
Stator
Weight
(lb)
Rotor
Weight
(lb)
Compressor
Weight
Stator
Weight
(kg)
Rotor
Weight
(kg)
Compressor
SIZE
Terminal
Cover
(lb)
Weight
(lb)
(kg)
P,Q,R,S,
T,U,V
4866
441
229
46
2207
200
104
21
COMPONENT WEIGHTS
FRAME 3 HEAT
EXCHANGER
FRAME 4 HEAT
EXCHANGER
FRAME 5 HEAT
EXCHANGER
COMPONENT
lb
70
179
747
1650
700
542
kg
32
81
339
749
318
246
lb kg
lb
115
232
747
1650
700
kg
52
Isolation Valves
Suction Elbow
Discharge Elbow/Muffler
Control Center/VFD
Vaporizer and Oil Sump
Economizer
70
237
32
108
339
749
318
246
105
339
749
318
246
747
1650
700
542
542
LEGEND
VFD
—
Variable Frequency Drive
23XRV HEAT EXCHANGER WEIGHTS
ENGLISH
METRIC (SI)
Machine Charge
Dry Rigging
Dry Rigging
NUMBER
OF TUBES
Weight
Machine Charge
Weight
(lb)*
(kg)*
CODE
Refrigerant
Weight (lb)
With Without
Economizer Economizer
Liquid Weight
(lb)
Refrigerant
Weight (kg)
With Without
Economizer Economizer
Liquid Weight
(kg)
Cooler Cond.
Cooler Cond.
Only
Only
Only
Only
Cooler Cond.
Cooler Cond.
Cooler Cond.
30
31
32
35
36
37
40
41
42
45
46
47
50
51
52
55
56
57
200
240
282
200
240
282
324
364
400
324
364
400
431
485
519
431
485
519
218
266
315
218
266
315
366
415
464
366
415
464
507
556
602
507
556
602
4148
4330
4522
4419
4627
4845
5008
5178
5326
5463
5659
5830
5827
6053
6196
6370
6631
6795
3617
3818
4023
4529
4758
4992
4962
5155
5347
5525
5747
5967
6013
6206
6387
6708
6930
7138
800
800
800
910
910
910
900
900
900
1015
1015
1015
1250
1250
1250
1430
1430
1430
650
650
650
760
760
760
825
825
825
960
960
960
1100
1100
1100
1280
1280
1280
464
531
601
511
587
667
863
930
990
464
542
621
513
602
692
915
995
1074
998
1088
1179
1225
1304
1379
1339
1429
1514
1877
1959
2046
2000
2094
2193
2675
2758
2832
2882
2976
3061
3182
3294
3364
3429
3556
3636
1676
1769
1860
2089
2195
2299
2746
2839
2932
3001
3108
3214
3304
3397
3485
3620
3726
3826
363
363
363
413
413
413
408
408
408
460
460
460
567
567
567
649
649
649
295
295
295
345
345
345
375
375
375
436
436
436
499
499
499
581
581
581
210
241
273
232
266
303
391
422
449
425
460
491
499
541
566
545
591
621
210
246
282
233
274
314
415
451
487
453
494
535
556
591
626
607
648
687
938
1014
1083
1101
1192
1248
1201
1304
1369
COND — Condenser
*Rigging weights are for standard tubes of standard wall thickness (EDE and
Spikefin 3, 0.025-in. [0.635 mm] wall).
NOTES:
1. Cooler includes the suction elbow and 1/2 the distribution piping weight.
2. Condenser includes float valve and sump, discharge elbow, and 1/2 the
distribution piping weight.
3. For special tubes, refer to the 23XRV Computer Selection Program.
4. All weights for standard 2-pass NIH (nozzle-in-head) design with vic-
taulic grooves.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDITIONAL WEIGHTS FOR 23XRV MARINE WATERBOXES*
150 psig (1034 kPa) MARINE WATERBOXES
ENGLISH (lb)
SI (kg)
NUMBER
OF
PASSES
FRAME
Cooler
Condenser
Cooler
Condenser
Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt
1 and 3
730
365
1888
944
2445
1223
700
350
908
452
1019
510
N/A
365
N/A
989
N/A
1195
N/A
350
N/A
452
N/A
499
331
166
856
428
1109
555
318
159
412
205
462
231
N/A
166
N/A
449
N/A
542
N/A
159
N/A
205
N/A
226
3
4
5
2
1 and 3
2
1 and 3
2
300 psig (2068 kPa) MARINE WATERBOXES
ENGLISH (lb)
SI (kg)
NUMBER
OF
PASSES
FRAME
Cooler
Condenser
Cooler
Condenser
Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt Rigging Wgt Liquid Wgt
1 and 3
860
430
2162
1552
2655
1965
700
350
908
393
1019
439
N/A
430
N/A
1641
N/A
1909
N/A
350
N/A
393
N/A
418
390
195
981
704
1204
891
318
159
412
178
462
199
N/A
195
N/A
744
N/A
866
N/A
159
N/A
178
N/A
190
3
4
5
2
1 and 3
2
1 and 3
2
*Add to cooler and condenser weights for total weights. Cooler and condenser weights may be found in the 23XRV Heat Exchanger
Weights table on page 5. The first digit of the heat exchanger code (first column) is the heat exchanger frame size.
23XRV WATERBOX COVER WEIGHTS — ENGLISH (lb)
FRAMES 3, 4, AND 5
COOLER
Frame 4
CONDENSER
Frame 4
WATERBOX
DESCRIPTION
Frame 3
Frame 5
Frame 3
Frame 5
Victaulic
Victaulic
Victaulic
Victaulic
Victaulic
Victaulic
Flanged
Flanged
Flanged
Flanged
Flanged
Flanged
Nozzles
Nozzles
Nozzles
Nozzles
Nozzles
Nozzles
NIH,1 pass Cover 150 psig
NIH,2 pass Cover 150 psig
NIH,3 pass Cover 150 psig
NIH Plain End, 150 psig
282
287
294
243
318
340
310
243
148
202
472
138
185
256
488
138
168
222
617
154
229
275
634
154
282
287
294
225
318
340
310
225
148
191
503
138
185
245
519
138
168
224
628
154
229
298
655
154
MWB End Cover, 150 psig* 243/315 243/315 138/314 138/314 154/390 154/390 225/234 225/234 138/314 138/314 154/390 154/390
NIH,1 pass Cover 300 psig
NIH,2 pass Cover 300 psig
NIH,3 pass Cover 300 psig
NIH Plain End, 300 psig
411
411
433
294
486
518
468
294
633
626
660
522
709
733
694
522
764
760
795
658
840
867
830
658
411
411
433
270
486
518
468
270
633
622
655
522
709
729
689
522
764
727
785
658
840
878
838
658
MWB End Cover, 300 psig* 445/619 445/619 522/522 522/522 658/658 658/658 359/474 359/474 658/658 658/658 658/658 658/658
LEGEND
*Nozzle end weight/return end weight.
NIH
—
Nozzle-in-Head
NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in
the heat exchanger weights shown on page 5.
MWB — Marine Waterbox
23XRV WATERBOX COVER WEIGHTS — SI (kg)
FRAMES 3, 4, AND 5
COOLER
Frame 4
CONDENSER
Frame 4
WATERBOX
DESCRIPTION
Frame 3
Frame 5
Frame 3
Frame 5
Victaulic
Victaulic
Nozzles
Victaulic
Nozzles
Victaulic
Nozzles
Victaulic
Nozzles
Victaulic
Flanged
Flanged
Flanged
Flanged
Flanged
Flanged
Nozzles
Nozzles
NIH,1 pass Cover 1034 kPa
NIH,2 pass Cover 1034 kPa
NIH,3 pass Cover 1034 kPa
NIH Plain End, 1034 kPa
128
130
133
110
144
154
141
110
67
92
214
63
84
116
221
63
76
101
280
70
104
125
288
70
128
130
133
102
144
154
141
102
67
87
228
63
84
111
235
63
76
102
285
70
104
135
297
70
MWB End Cover, 2068 kPa*
LEGEND
*Nozzle end weight/return end weight.
NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in
the heat exchanger weights shown on page 5.
6
Options and accessories
ITEM
.028 or .035 in. (0.711 or 0.889 mm) Internally/Externally Enhanced Copper Tubing — Cooler/Condenser
.028 or .035 in. (0.711 or 0.889 mm) Internally/Externally Enhanced Cupronickel Tubing — Condenser
.028 or .035 in. (0.711 or 0.889 mm) Smooth Bore/Externally Enhanced Copper Tubing — Cooler/Condenser
.028 or .035 in. (0.711 or 0.889 mm) Smooth Bore/Externally Enhanced Cupronickel Tubing — Condenser
Flanged Cooler and/or Condenser Waterbox Nozzles**
Hinged Waterboxes
Marine Waterboxes, 150 psig (1034 kPa)††
Marine Waterboxes, 300 psig (2068 kPa)††
Nozzle-in Head Waterbox, 300 psig (2068 kPa)
One, 2, or 3 Pass Cooler or Condenser Waterside Construction
Seismic Kit
OPTION* ACCESSORY†
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Zinc Anodes
100K AIC (Amp Interrupt Capacity) High Interrupt Circuit Breaker with Shunt Trip
Analog Voltmeter and Ammeter with 3 Phase Selector Switch
BACnet*** Communications
LonWorks††† Carrier Translator
Sensor Package
Refrigerant Isolation Valves
Separate Storage Tank and Pumpout Unit
Shipped Factory Charged with Refrigerant
Stand-Alone Pumpout Unit
Unit-Mounted Pumpout Unit
Hot Gas Bypass
Soleplate Package
Spring Isolator Kit
Acoustical Sound Insulation Kit
Full Cold Surface Thermal Insulation (Except Waterbox Covers)
Customer Factory Performance Testing
Export Crating
Extended Warranty (North American Operations [NAO] only)
Service Contract
*Factory-installed.
††Optional marine waterboxes available for 23XRV heat exchanger
frames 3-5 only. Standard waterboxes for 23XRV are nozzle-in-head
type, 150 psig (1034 kPa).
†Field-installed.
**Standard waterbox nozzles are victaulic type. Flanged nozzles are
available as an option with either nozzle-in-head type waterboxes or
marine waterboxes.
***Sponsored by ASHRAE (American Society of Heating, Refrigerating,
and Air Conditioning Engineers).
†††Registered trademark of Echelon Corporation.
910
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
23XRV DIMENSIONS
TUBE REMOVAL
SPACE FOR
MOTOR SERVICE
CLEARANCE
EITHER END
SIZES 30-32, 40-42
50-52
1’-10” (559 mm)
FRAME R COMPRESSOR 3’-0” (915mm)
14’-3” (4343 mm)
SIZES 35-37, 45-47
55-57
RECOMMENDED OVERHEAD SERVICE CLEARANCE
14’-0” (4267 mm)
a23-1646
C
2’ MIN
(610 mm)
B
(WIDEST POINT)
A
4’ MIN
(1219 mm)
SERVICE AREA
4’-10” MIN
(1475 mm)
23XRV DIMENSIONS (NOZZLE-IN-HEAD WATERBOX)
A (Length, with Nozzle-in-Head Waterbox)
B (Width)
C (Height)
HEAT EXCHANGER
SIZE
1 Pass
ft-in.
14- 31/4
15-113/4
14- 9
2-Pass*
3 Pass
mm
4350
4870
4496
5017
4521
5042
ft-in.
mm
4172
4693
4347
4867
4382
4902
ft-in.
mm
4350
4870
4420
4940
4432
4953
ft-in.
6- 4
mm
1930
ft-in.
mm
30 to 32
35 to 37
40 to 42
45 to 47
50 to 52
55 to 57
13- 81/4
15- 43/4
14- 31/8
15-115/8
14- 41/2
16- 1
14- 31/4
15-113/4
14- 6
16- 21/2
14- 61/2
16- 3
7- 25/8
7- 25/8
7- 61/2
7- 61/2
7- 63/4
7- 63/4
2200
2200
2299
2299
2305
2305
6- 4
1930
2045
2045
2127
2127
6- 81/2
6- 81/2
6-113/4
6-113/4
16- 51/2
14-10
16- 61/2
23XRV DIMENSIONS (MARINE WATERBOX)
A (Length, Marine Waterbox)
B (Width)
HEAT EXCHANGER
SIZE
2-Pass*
1 or 3 Pass†
ft-in.
C (Height)
ft-in.
14- 9
mm
4496
5017
4642
5163
4661
5182
mm
4997
5518
5086
5607
5093
5613
ft-in.
mm
30 to 32
35 to 37
40 to 42
45 to 47
50 to 52
55 to 57
16- 43/4
18- 11/4
16- 31/4
18- 43/4
16- 81/2
18- 5
6- 93/8
6- 93/8
6- 93/4
6- 93/4
7- 1
2067
2067
2076
2076
2159
2159
16- 51/2
15- 23/4
16-113/4
15- 31/2
17- 0
See unit
certified
drawings
7- 1
*Assumes both cooler and condenser nozzles on same end of chiller.
†1 or 3 pass length applies if cooler is a 1 or 3 pass design.
NOTES:
1. Service access should be provided per American Society of Heat-
ing, Refrigerating, and Air Conditioning Engineers (ASHRAE) 15,
latest edition, National Fire Protection Association (NFPA) 70, and
local safety code.
2. Allow at least 3 ft (915 mm) overhead clearance for service rigging
for the compressor.
3. Certified drawings available upon request.
4. Marine waterboxes may add 6 in. (152 mm), to the width of the
machine. See certified drawings for details.
5. ‘A’ length and ‘B’ width dimensions shown are for standard
150 psig (1034 kPa) design and victaulic connections. The
300 psig (2068 kPa) design and/or flanges will add length. See cer-
tified drawings.
6. Dished head waterbox covers not available for the 3-pass design.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
NOZZLE SIZE
NOZZLE SIZE (in.)
(Nominal Pipe Size)
FRAME
SIZE
23XRV HEAT EXCHANGER MIN/MAX FLOW RATES*
ENGLISH (GPM)
*Flow rates based on standard tubes in the cooler and condenser. Minimum flow based on tube velocity of 3 ft/sec (0.91 m/sec);
maximum flow based on tube velocity of 12 ft/sec (3.66 m/sec). Consult the factory if variable primary flow.
SI (L/s)
*Flow rates based on standard tubes in the cooler and condenser. Minimum flow based on tube velocity of 3 ft/sec (0.91 m/sec);
maximum flow based on tube velocity of 12 ft/sec (3.66 m/sec). Consult the factory if variable primary flow.
9
Electrical data
VFD FRAME SIZES
FRAME SIZE
MAX INPUT CURRENT*
MAX OUTPUT CURRENT*
AA
BA
BB
CC
440
520
520
608
442
442
520
608
*Maximum limits only. Additional application limits apply that will reduce these ampacities.
AUXILIARY RATINGS*
MAXIMUM
PROTECTIVE DEVICE
SIZE (AMPS)
ITEM
VOLTAGE
WATTS
Controls, Oil Pump And Heater Circuit†
Oil Pump
115
115
115
15
1.48
4.35
—
130
500
Oil Sump Heater
Oil Vaporizer Heater Circuit†
Oil Vaporizer Heater
115
115
15
13
—
1500
*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
• High VFD inverter temperature*†
• DC bus voltage (Low/High)
Capacity control
• Leaving chilled liquid control
• Entering chilled liquid control
• Soft loading control by temperature or load ramping
• Hot gas bypass valve (optional)
• Power (demand) limiter
• Automatic chilled liquid reset (3 methods)
• Manual speed control
Microprocessor controls
Microprocessor controls provide the safety, interlock, ca-
pacity control, indications and accessibility necessary to
operate the chiller in a safe and efficient manner.
Control system
The microprocessor control on each Carrier chiller is
factory-mounted, factory-wired, and factory-tested to
ensure machine protection and efficient capacity control.
In addition, the program logic ensures proper starting,
stopping, and recycling of the chiller and provides a com-
munication link to the Carrier Comfort Network® (CCN)
system.
Interlocks
• Manual/automatic remote start
• Starting/stopping sequence
Pre-lube/post-lube
Pre-flow/post-flow
• Compressor run interlock
• Pre-start check of safeties and alerts
• Low chilled liquid (load) recycle
• Monitor/number compressor starts and run hours
• Manual reset of safeties
Indications
• Chiller operating status message
• Power-on
Features
Control system
• Component test and diagnostic check
• Programmable recycle allows chiller to recycle at opti-
mum loads for decreased operating costs
• Menu-driven keypad interface for status display, set
point control, and system configuration
• CCN system compatible
• Primary and secondary status messages
• Individual start/stop schedules for local and CCN opera-
tion modes
• Recall of up to 25 alarm messages and 25 alert mes-
sages with diagnostic help
• Two chiller lead/lag with third chiller standby is stan-
dard in the PIC III software
• Optional soft stop unloading decreases compressor
speed to unload the motor to the configured amperage
level prior to stopping
• Languages pre-programmed at factory for English, Chi-
nese, Japanese, Korean
• ILT (International Language Translator) available for
conversion of extended ASCII characters
Safety cutouts
• Pre-start diagnostic check
• Compressor motor amps
• Alert (pre-alarm)††
• Alarm
• Contact for remote alarm
• Safety shutdown messages
• Elapsed time (hours of operation)
• Chiller input kW
• Demand kW
Drive control parameters
• Compressor 100% speed (Hz)
• Rated line voltage
• Rated line amps
• Rated line kW
• Motor rated Load kW
• Motor rated Load amps
• Motor nameplate amps
• Motor nameplate RPM
• Motor nameplate kW
• Inverter PWM frequency
• Motor high temperature*†
• Refrigerant (condenser) high pressure*†
• Refrigerant (cooler) low temperature*†
• Lube oil low pressure*
• Compressor (refrigerant) high discharge temperature*
• Under voltage**
• Over voltage**
• Cooler and condenser liquid flow
• Motor overload†
• Motor acceleration time
• Intermittent power loss**
• Motor stall protection
*Can be configured by the user to provide alert indication
at user-defined limit.
†Override protection: Causes compressor to first unload
and then, if necessary, shut down.
**Will not require manual reset or cause an alarm if auto-
restart after power failure is enabled.
††By display code only.
• Low level ground fault
• Cooler and condenser freeze prevention*
• Low oil temperature
• Line voltage imbalance**
• Line current imbalance**
• Line frequency
• Motor current imbalance
• Motor rotation reversal
• Excessive motor amps
• Motor starts limit
• VFD speed out of range
• High VFD rectifier temperature*†
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls (cont)
CONTROL PANEL DISPLAY (Front View)
ICVC ENGLISH DISPLAY IN SI UNITS
CONTROL PANEL DISPLAY (Front View)
ICVC CHINESE DISPLAY IN METRIC UNITS
12
Download from Www.Somanuals.com. All Manuals Search And Download.
a23-1649
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls (cont)
Control sequence
CONTROL SEQUENCE
To start — Local start-up (manual start-up) is initiated by
pressing the LOCAL or CCN menu softkey, which is indi-
cated on the default international chiller visual control
(ICVC) screen. Time schedule 01 or 03, respectively, must
be in the Occupied mode and the internal 15-minute start-
to-start and the 1-minute stop-to-start inhibit timers must
have expired. All pre-start safeties are checked to verify
that all prestart alerts and safeties are within limits (if one is
not, an indication of the fault displays and the start will be
delayed or is aborted). The signal is sent to start the cooler
liquid pump. Five seconds later, the condenser liquid pump
is energized. If satisfied, it checks the chilled liquid temper-
ature against the control point. If the temperature is less
than or equal to the chilled liquid control point, the con-
denser liquid pump is deenergized and the chiller goes into
a recycle mode.
0
0
MACHINE SAFETIES,
EVAPORATOR PUMP
CONDENSER WATER
PUMP
WATER FLOWS
CHILLED WATER
TEMP,TOWER FAN
CONTROL
OILPUMP
OILPRESSURE
VERIFIED
If the chilled liquid temperature is high enough, the start-
up sequence continues. The oil pump is started and waits a
minimum of 45 sec to verify oil flow. Once oil flow is veri-
fied, the VFD is energized. The control will monitor for a
phase reversal condition. At this time, the following occurs:
VDF FAULT TEST
COMPRESSOR, PHASE
REVERSAL,
COMPRESSOR AND
SERVICE ONTIME
COMPRESSOR
RUNNING
RAMP VDF TO
TARGET SPEED
• The “start-to-stop” timer is activated.
• The “compressor on-time” and “service on-time” timers
are activated.
15-MINUTE
START-TO-START
TIMER
• The “starts in 12-hour counter” advances by one.
1-MINUTE
• The “total compressor starts counter” advances by one.
STOP-TO-START
TIMER (SOFTWARE
VERSION 13)
Once started — If the VFD average current >5% within
15 seconds after VFD start, the machine enters run mode
and speed will be ramped up to meet VFD target speed.
Once the target speed is met the controls, enter the capac-
ity control mode.
Shutdown sequence — The chiller shutdown is initiated
if any of the following occur:
D
E
G
A
C
TIME
F
H
O/A
B
I
J
L
K
0
— Phase reversal monitored
A
—
START INITIATED: Pre-start checks are made; evaporator pump
started
B
— Condenser liquid pump started (5 seconds after A); tower fan control
enabled
• The Stop button is pressed for at least one second (the
alarm light blinks once to confirm the stop command).
• A recycle shutdown is initiated.
C
D
— Liquid flows verified (30 sec to 5 minutes maximum after B)
— Chilled liquid temperature checked against control point; oil pump
on.
— Oil pressure verified (oil pressure verified 45-300 sec after D).
— VFD starts; phase reversal conditions monitored; compressor
ontime and service ontime start; 15-minute inhibit timer starts (VFD
fault tests for 15 sec after F)
— Verify average current >5% within 15 sec after VFD start, ramp to
VFD target speed.
— Compressor reaches target speed, chiller set to running status
E
F
• The time schedule has gone into unoccupied mode.
• The chiller protective limit has been reached and the
chiller is in alarm.
G
• The start/stop status is overridden to stop from the
ICVC, CCN system, or building management system.
H
I
J
—
Shutdown initiated: Target VFD speed to 0% (or J occurs)
— Ramp down until percent line current < soft stop amps threshold
(0-60 sec after I)
Once the controls shutdown sequence is initiated, the
compressor is stopped and the VFD target speed is set to 0.
If optional soft stop unloading is activated when the Stop
button is pressed or the remote contacts open, motor
speed decreases to a configured amperage level, and the
compressor is stopped. The display indicates “Shutdown in
Progress” while the motor speed decreases. Compressor
ontime and service ontime timers stop once the current in
all phases is <5%, indicating a VFD Stop Complete. The oil
pump and cooler liquid pump are then deenergized. The
condenser liquid pump shuts down when the refrigerant
temperature or entering condenser liquid temperature is be-
low pre-established limits. The 3-minute start-to-stop timer
starts.
K
L
— Oil pump relay off (1-20 sec after J)
— Evaporator pump deenergized (60 sec after K); condenser pump
and tower fan control may continue to operate if condenser pressure
is high; evaporator pump may continue if in RECYCLE mode
O/A — Restart permitted (both inhibit timers expired) (minimum of 15 min-
utes after F; minimum of 3 minutes after L)
Restart — Restart is permitted after both inhibit timers
have expired. If shutdown was due to a safety shutdown,
the reset button must be depressed before restarting the
chiller.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical piping and wiring
23XRV CHILLER
MAIN COMPRESSOR
MOTOR POWER
1
1
1
1
8
7
6
TO CHILLED LIQUID PUMP
TO CONDENSER LIQUID PUMP
2
TO COOLING TOWER FAN
9
TO
COOLING
TOWER
9
3
3
FROM
COOLING
TOWER
TO
LOAD
FROM
LOAD
DRAIN
5
4
NOTES:
LEGEND
1. Wiring and piping shown are for general point-of-connection only and are not
intended to show details for a specific installation. Certified field wiring and
dimensional diagrams are available on request.
2. All wiring must comply with applicable codes.
3. Refer to Carrier System Design Manual for details regarding piping techniques.
4. Wiring not shown for optional devices such as:
• remote start/stop
1
2
3
4
5
6
7
8
9
—
—
—
—
—
—
—
—
—
Disconnect
Unit-Mounted VFD/Control Center
Pressure Gages
Chilled Liquid Pump
Condenser Liquid Pump
Chilled Liquid Pump Starter
Condenser Liquid Pump Starter
Cooling Tower Fan Starter
Vents
• remote alarms
• optional safety device
• 4 to 20 mA resets
Piping
Control Wiring
Power Wiring
• optional remote sensors
• kW output
• head pressure reference
5. Flow switches are NOT required.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Control wiring schematic
23XRV COMPONENT ARRANGEMENT
LEGEND
CCM — Chiller Control Module
CCN — Carrier Comfort Network®
ICVC — International Chiller Visual Controller
GND — Ground
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Application data
23XRV MACHINE FOOTPRINT
A
D
C
C
L
VESSELS
COND.
C
L
ACCESSORY
SOLEPLATE
B
TYP.
0’-3”
F
[76.2mm]
COOLER
C
L
a23-1650
E
X
X*
G
0’-01/2”
[13mm]
TYP.
Y*
Y
*See detail on page 18.
23XRV
DIMENSIONS (ft-in.)
DIMENSIONS (mm)
HEAT EXCHANGER
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SIZE
30-32
35-37
40-42
45-47
50-52
55-57
12-103/4
14- 71/4
12-103/4
14- 71/4
12-103/4
14- 71/4
5-41/4
5-41/4
6-0
6-0
6-51/2
6-51/2
0
0
0-35/8
0-35/8
0-35/8
0-35/8
0-35/8
0-35/8
1-13/4
1-13/4
1-13/4
1-13/4
1-13/4
1-13/4
0-9
0-9
0-9
0-9
0-9
0-9
0-1/2
0-1/2
0-1/2
0-1/2
0-1/2
0-1/2
3931
4451
3931
4451
3931
4451
1632
1632
0
0
92 349
92 349
229 13
229 13
229 13
229 13
229 13
229 13
0-11/2
0-11/2
0-
0-
1829 38 92 349
1829 38 92 349
1969 13 92 349
1969 13 92 349
1
/
/
2
1
2
910
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Application data (cont)
23XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGE
TYPICAL ISOLATION
STANDARD ISOLATION
ELASTOMERIC PAD
VIEW Y-Y
ISOLATION WITH ISOLATION PACKAGE ONLY
(STANDARD)
NOTE: Isolation package includes 4 elastomeric pads.
a23-1647
ACCESSORY SOLEPLATE DETAIL
VIEW X-X
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Accessory soleplate package includes 4 soleplates, 16 jacking screws and leveling
pads. Requires isolation package.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use
only pre-mixed non-shrinking grout, Ceilcote 748 or Chemrex Embeco 636 Plus
Grout, 0-11/2 (38.1) to 0-21/4 (57) thick.
5. Service clearance under the chiller is enhanced if leveling pads are not extended
along the entire length of the heat exchangers.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
23XRV NOZZLE ARRANGEMENTS
NOZZLE-IN-HEAD WATERBOXES
DISCHARGE END
SUCTION END
FRAME 3
12
3
6
5
9
11
10
2
1
8
4
7
DISCHARGE END
SUCTION END
FRAMES 4 AND 5
NOZZLE ARRANGEMENT CODES FOR ALL 23XRV NOZZLE-IN-HEAD WATERBOXES
COOLER WATERBOXES CONDENSER WATERBOXES
PASS
PASS
Arrangement
Arrangement
In
Out
In
Out
Code*
Code*
8
5
7
4
7
4
5
8
9
6
6
9
A
B
C
D
E
F
11
2
10
1
10
1
2
11
12
3
3
12
P
Q
R
S
T
1
2
3
1
2
3
U
*Refer to certified drawings.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Application data (cont)
23XRV NOZZLE ARRANGEMENTS (cont)
MARINE WATERBOXES
DISCHARGE END
SUCTION END
FRAME 3
NOZZLE ARRANGEMENT CODES
COOLER WATERBOXES
CONDENSER WATERBOXES
PASS
PASS
Arrangement
Arrangement
In
Out
In
Out
Code
Code
8
5
7
4
7
4
5
8
9
6
6
9
A
B
C
D
E
F
—
—
10
1
—
—
12
3
—
—
R
1
2
3
1
2
3
S
—
—
—
—
—
—
DISCHARGE END
SUCTION END
FRAMES 4, AND 5
NOZZLE ARRANGEMENT CODES
COOLER WATERBOXES
CONDENSER WATERBOXES
PASS
PASS
Arrangement
Arrangement
In
Out
In
Out
Code
Code
—
9
6
7
4
7
4
6
9
9
6
6
9
A
B
C
D
E
F
—
—
10
1
—
—
12
3
1
2
3
1
2
3
—
R
S
—
—
—
—
—
—
20
Download from Www.Somanuals.com. All Manuals Search And Download.
23XRV WATERBOX NOZZLE SIZES (Nozzle-In-Head and Marine Waterboxes
NOMINAL PIPE SIZE (in.)
ACTUAL PIPE ID (in.)
Cooler Condenser
FRAME
SIZE
PRESSURE
psig (kPa)
PASS
Cooler
Condenser
1
2
3
1
2
3
1
2
3
10
8
6
10
8
6
10
8
6
10
8
6
10
8
6
10
10
8
10.020
7.981
6.065
10.020
7.981
6.065
10.020
7.981
6.065
10.020
7.981
6.065
10.020
7.981
6.065
10.020
10.020
7.981
150/300
3
4
5
(1034/2068)
150/300
(1034/2068)
150/300
(1034/2068)
RELIEF VALVE LOCATIONS
FRAME
RELIEF VALVE
LOCATION
QUANTITY
SIZE
3-5
OUTLET SIZE
11/4-in. NPT FEMALE CONNECTOR
11/4-in. NPT FEMALE CONNECTOR
11/4-in. NPT FEMALE CONNECTOR
MUFFLER
COOLER
CONDENSER
1
1 or 2*
2
3-5
3-5
OPTIONAL
STORAGE TANK
N/A
1-in. NPT FEMALE CONNECTOR
2
* Coolers without optional isolation require 2 relief valves.
NOTE: All valves relieve at 185 psig (1275 kPa).
RELIEF VALVE ARRANGEMENTS
WITH OPTIONAL ISOLATION OF DISCHARGE AND COOLER
WITH OPTIONAL ISOLATION
WITHOUT OPTIONAL ISOLATION
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Application data (cont)
Each heat exchanger and economizer (if equipped) is
ASME ‘U’ stamped on the refrigerant side of each vessel.
Vent and drain connections
Nozzle-in-head waterboxes have vent and drain connec-
tions on covers. Marine waterboxes have vent and drain
connections on waterbox shells.
Relief valve discharge pipe sizing
See page 21 for number of relief valves.
Relief valve discharge piping size should be calculated
per the current version of the ASHRAE 15, latest edition,
code using the tabulated C factors for each vessel shown in
the table below.
Provide high points of the chiller piping system with vents
and the low points with drains. If shutoff valves are provid-
ed in the main liquid pipes near the unit, a minimal amount
of system liquid is lost when the heat exchangers are
drained. This reduces the time required for drainage and
saves on the cost of re-treating the system liquid.
It is recommended that pressure gages be provided at
points of entering and leaving liquid to measure pressure
drop through the heat exchanger. Gages may be installed
as shown in Pressure Gage Location table. Pressure gages
installed at the vent and drain connections do not include
nozzle pressure losses.
23XRV RELIEF VALVE DISCHARGE PIPE SIZING
RELIEF
VESSEL
VALVE
RATED
FIELD
CONNECTION
SIZE (FPT)
HEAT
EXCHANGER
FRAME REQUIRED
SIZE
C FACTOR
(lb air/Min)
C FACTOR
(lb air/Min)
30 to 32
35 to 37
40 to 42
45 to 47
50 to 52
55 to 57
30 to 32
35 to 37
40 to 42
45 to 47
50 to 52
55 to 57
43.4
49.5
50.4
57.4
53.7
61.1
41.4
47.1
47.1
53.7
51.2
58.3
70.8
70.8
70.8
70.8
70.8
70.8
70.8
70.8
70.8
70.8
70.8
70.8
11/4
11/4
11/4
11/4
11/4
11/4
11/4
11/4
11/4
11/4
11/4
11/4
Use a reliable differential pressure gage to measure pres-
sure differential when determining liquid flow. Regular gag-
es of the required pressure range do not have the accuracy
to provide accurate measurement of flow conditions.
COOLER
PRESSURE GAGE LOCATION
NUMBER
GAGE LOCATION
OF
(Cooler or Condenser)
CONDENSER
PASSES
1 or 3
2
One gage in each waterbox
Two gages in waterbox with nozzles
ASME stamping
Carrier further recommends that an oxygen sensor be
installed to protect personnel. Sensor should be able to
sense the depletion or displacement of oxygen in the ma-
chine room below 19.5% volume oxygen per ASHRAE
15, latest edition.
All 23XRV heat exchangers are constructed in accordance
with ASHRAE (American Society of Heating, Refrigerat-
ing, and Air Conditioning Engineers) 15 Safety Code for
Mechanical Refrigeration (latest edition). This code, in
turn, requires conformance with ASME (American Society
of Mechanical Engineers) Code for Unfired Pressure Ves-
sels wherever applicable.
Design pressures
Design and test pressures for heat exchangers are listed
below.
DESIGN AND TEST PRESSURES (23XRV)
SHELL SIDE
(Refrigerant)
STANDARD TUBE SIDE
(Liquid)
OPTIONAL TUBE SIDE
(Liquid)
PRESSURES
psig
kPa
psig
kPa
psig
kPa
Leak Test at Design Pressure*
Hydrostatic
Proof Test*
185
—
204
1276
—
1407
150
195
—
1034
1344
—
300
390
—
2068
2689
—
*Nitrogen/Helium.
HEAT EXCHANGER MATERIAL SPECIFICATIONS
ITEM
MATERIAL
SPECIFICATION
Shell
HR Steel
HR Steel
HR Steel
ASME SA516 GR 70
ASME SA516 GR 70
ASME SA516 GR 70, SA-36, or SA-285 GRC
ASME SA675 GR 60, SA-516 GR70, or SA-181 CL70,
SA-36, SA-675 GR70, SAE AME 7496
Tube Sheet
Condenser/Cooler Waterbox Cover
Condenser/Cooler Waterbox Shell
HR Steel
Tubes
Finned Copper
ASME SB359
Discharge/Suction
Pipe
Flanges
Steel
Steel
ASME SA106 GRB
ASME SA105
LEGEND
ASME — American Society of Mechanical Engineers
HR
—
Hot Rolled
22
Download from Www.Somanuals.com. All Manuals Search And Download.
conforms with Underwriters Laboratories (UL) Standard
94, Classification 94 HF-1. Both the 1/2-in. foam and the
3/16-in. vinyl layer will pass flammability test method
MVSS 302.
Insulation
23XRV MINIMUM FIELD-INSTALLED INSULATION
REQUIREMENTS
Field insulation — As indicated in the Condensation vs
Relative Humidity table, the factory insulation provides
excellent protection against condensation under most op-
erating conditions. If temperatures in the equipment area
exceed the maximum design conditions, extra insulation is
recommended.
If the machine is to be field insulated, obtain the approx-
imate areas from the 23XRV Minimum Field-Installed Insu-
lation Requirements table.
Insulation of waterbox is made only in the field and this
area is not included in 23XRV Minimum Field-Installed In-
sulation Requirements table. When insulating the covers,
allow for service access and removal of covers. To estimate
water-box cover areas, refer to certified drawings.
High humidity jobsite locations may require field sup-
plied and installed insulation on the float chamber, suction
housing, and the lower half of the condenser.
INSULATION
COMPONENT
SIZE
ft2
m2
30-32
35-37
40-42
45-47
50-52
55-57
96
108
109
122
115
130
8.9
10.0
10.1
11.3
10.7
12.1
Cooler
Misc. Liquid Lines
Economizer
Compressor Motor
All Sizes
All Sizes
All Sizes
21
20
17
2.0
1.9
1.6
Factory insulation — Thermal insulation is factory-
provided to the following areas:
• Cooler (not including waterbox)
• Suction line
• Compressor and motor
• Oil cooling line and oil return system line (oil and refrig-
erant lines at or near evaporator pressure are insulated)
• VFD cooling line (oil and refrigerant lines at or near
evaporator pressure are insulated)
• Motor cooling line
CONDENSATION VS RELATIVE HUMIDITY*
ROOM DRY-BULB TEMPERATURE
AMOUNT OF
80 F (27 C)
90 F (32 C)
100 F (38 C)
CONDENSATION
• Vaporizer
• Liquid line and discharge line
• Float chamber
% Relative Humidity
None
80
87
94
76
84
91
70
77
84
Slight
Extensive
• Optional economizer (including vent line and econo-
mizer muffler)
Factory insulation is not available for the waterboxes.
*These approximate figures are based on 35 F (1.7 C) saturated suction
temperature. A 2° F (1.1° C) change in saturated suction temperature
changes the relative humidity values by 1% in the same direction.
Insulation applied at the factory is 1/2-in. (13 mm) thick
closed cell and 1/2-in. (13 mm) open cell PVC-Nitrile foam.
Some parts of the chiller are also treated with an outer
layer of /16-in. (5 mm) thick vinyl. The /2-in. (13 mm)
closed cell foam has a thermal conductivity K value of
0.28 (BTU in.)/(hr sqft °F) [0.0404 W/(m °C)] and
Minimum fluid loop volume
Minimum fluid volume must be in excess of 1.5 gal per ton
(20 L per kW) for comfort cooling applications and apply 3
to 5 gal per ton (40 to 66 L per kW) fluid loop volume for
process applications.
3
1
23
910
Download from Www.Somanuals.com. All Manuals Search And Download.
Guide specifications
1.02 QUALITY ASSURANCE
Variable Speed Screw Chiller
A. Chiller performance shall be rated in accordance
with AHRI Standard 550/590, latest edition.
B. Equipment and installation shall be in compliance
with ANSI/ASHRAE 15 (latest edition).
C. Cooler and condenser refrigerant side shall include
ASME “U” stamp and nameplate certifying compli-
ance with ASME Section VIII, Division 1 code for
unfired pressure vessels.
D. A manufacturer’s data report is required to verify
pressure vessel construction adherence to ASME
vessel construction requirements. Form U-1 as
required per ASME code rules is to be furnished
to the owner. The U-1 Form must be signed by a
qualified inspector, holding a National Board
Commission, certifying that construction conforms
to the latest ASME Code Section VIII, Div. 1 for
pressure vessels. The ASME symbol “U” must also
be stamped on the heat exchanger. Vessels specifi-
cally exempted from the scope of the code must
come with material, test, and construction methods
certification and detailed documents similar to
ASME U-1; further, these must be signed by an offi-
cer of the company.
HVAC Guide Specifications
Size Range: 300 to 550 Tons (1055 to 1934 kW)
Nominal
Carrier Model Number: 23XRV
Part 1 — General
1.01 SYSTEM DESCRIPTION
A. Microprocessor-controlled liquid chiller shall use a
semi-hermetic screw compressor using refrigerant
HFC-134a only. Chiller refrigerant shall not have a
planned phase out date.
B. If a manufacturer proposes a liquid chiller using
HCFC-123 refrigerant, which has a planned phase
out date, then the manufacturer shall include in the
chiller price:
1. A vapor activated alarm system consisting of all
alarms, sensors, safeties, and ventilation equip-
ment as required by ANSI/ASHRAE Standard
15 Safety Code for Mechanical Refrigeration
(latest edition) with the quotation. System shall
be capable of responding to HCFC-123 levels
of 10 ppm Allowable Exposure Limit (AEL).
2. A free-standing refrigerant storage tank and
pumpout unit shall be provided. The storage
vessels shall be designed per ASME Section VIII
Division 1 code with 300 psig (2068 kPa)
design pressure. Double relief valves per ANSI/
ASHRAE 15, latest edition, shall be provided.
The tank shall include a liquid level gage and
pressure gage. The pumpout unit shall use a
semi-hermetic reciprocating compressor with
water cooled condenser. Condenser water pip-
ing, 3-phase motor power, and 115-volt control
power shall be installed at the jobsite by the
installing contractor.
3. Zero emission purge unit capable of operating
even when the chiller is not operating.
4. Back-up relief valve to rupture disk.
5. Factory-installed chiller pressurizing system to
prevent leakage of noncondensables into the
chiller during shutdown periods.
E. Chiller shall be designed and constructed to meet
UL and UL of Canada requirements and have labels
appropriately affixed.
F. Unit shall be manufactured in a facility registered to
ISO 9001:2000 Manufacturing Quality Standard.
G. Each compressor assembly shall undergo a mechan-
ical run-in test to verify vibration levels, oil pressures,
and temperatures are within acceptable limits. Each
compressor assembly shall be proof tested at a mini-
mum 204 psig (1407 kPa) and leak tested at
185 psig (1276 kPa) with a tracer gas mixture.
H. Entire chiller assembly shall be proof tested at
204 psig (1407 kPa) and leak tested at 185 psig
(1276 kPa) with a tracer gas mixture on the refriger-
ant side. The leak test shall not allow any leaks
greater than 0.5 oz per year of refrigerant. The
water side of each heat exchanger shall be hydro-
statically tested at 1.3 times rated working pressure.
I. Prior to shipment, the chiller automated controls
test shall be executed to check for proper wiring and
ensure correct controls operation.
J. Chillers shall have factory-mounted, factory-wired
and factory-tested unit-mounted variable frequency
drive (VFD). Proper VFD operation shall be con-
firmed prior to shipment.
6. Plant room ventilation.
7. Removal and disposal of refrigerant at the end
of the phase out period.
8. Chillers utilizing a purge unit shall include in the
machine price the costs to perform the follow-
ing regular maintenance procedures:
a. Weekly: Check refrigerant charge.
1.03 DELIVERY, STORAGE AND HANDLING
b. Quarterly: Charge purge unit dehydrator at
least quarterly, more often if necessary.
Clean foul gas strainer. Perform chemical
analysis of oil.
c. Annually: Clean and inspect all valves. Drain
and flush purge shell. Clean orifices.
A. Unit shall be stored and handled in accordance with
manufacturer’s instructions.
B. Unit shall be shipped with all refrigerant piping and
control wiring factory-installed.
C. Unit shall be shipped charged with oil and full
charge of refrigerant HFC-134a or a nitrogen hold-
ing charge as specified on the equipment schedule.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Unit shall be shipped with firmly attached labels that
indicate name of manufacturer, chiller model num-
ber, chiller serial number, and refrigerant used.
b. Oil pressure sensor with differential readout
at main control center.
c. Oil pressure regulator.
E. If the unit is to be exported, the manufacturer shall
provide sufficient protection against sea water corro-
sion, making the unit suitable for shipment in a
standard open top ocean shipping container.
F. Chiller and starter shall be stored indoors, protected
from construction dirt and moisture. Chiller shall be
inspected under shipping tarps, bags, or crates to be
sure water has not collected during transit. Protec-
tive shipping covers shall be kept in place until
machine is ready for installation. The inside of the
protective cover shall meet the following criteria:
d. Oil filter with isolation valves to allow filter
change without removal of refrigerant
charge.
e. Oil sump heater [115 v, 50 or 60 Hz] con-
trolled from unit microprocessor.
f. Oil reservoir temperature sensor with main
control center digital readout.
g. All wiring to oil pump, oil heater, and con-
trols shall be pre-wired in the factory and
power shall be applied to check proper
operation prior to shipment.
1. Temperature is between 40 F (4.4 C) and
120 F (48.9 C)
2. Relative humidity is between 10% and 80%
non-condensing.
7. Compressor shall be fully field serviceable.
Compressors that must be removed and
returned to the factory for service shall be
unacceptable.
1.04 WARRANTY
8. Acoustical attenuation shall be provided as
required, to achieve a maximum (full load
or part load) sound level, measured per AHRI
Standard 575 (latest edition).
Warranty shall include parts and labor for one year
after start-up or 18 months from shipment, which-
ever occurs first. A refrigerant warranty shall be
provided for a period of 5 years.
C. Motor:
Part 2 — Products
2.01 EQUIPMENT
A. General:
1. Compressor motor shall be of the semi-
hermetic, liquid refrigerant cooled, squirrel
cage, induction type suitable for voltage shown
on the equipment schedule.
2. If an open (air cooled) motor is provided, a
compressor shaft seal leakage containment
system shall be provided:
Factory-assembled, single piece, liquid chiller shall
consist of compressor, motor, VFD, lubrication sys-
tem, cooler, condenser, initial oil and refrigerant
operating charges, microprocessor control system,
and documentation required prior to start-up.
a. An oil reservoir shall collect oil and refriger-
ant that leaks past the seal.
b. A float device shall be provided to open
when the reservoir is full, directing the
refrigerant/oil mixture back into the com-
pressor housing.
B. Compressor:
1. One variable speed, tri-rotor screw compressor
of the high performance type.
2. Compressor and motor shall be hermetically
sealed into a common assembly and arranged
for easy field servicing.
3. The compressor motor shall be accessible for
servicing without removing the compressor
base from the chiller. Connections to the com-
pressor casing shall use O-rings and gaskets to
reduce the occurrence of refrigerant leakage.
Connections to the compressor shall be flanged
or bolted for easy disassembly.
4. Compressor bearings must have individual
design life of 500,000 hours or greater.
5. Compressor shall provide capacity modulation
from 100% to 15% capacity without the use of
hot gas bypass or mechanical unloaders.
6. Compressor shall be provided with a factory-
installed positive pressure lubrication system to
deliver oil under pressure to bearings and rotors
at all operating conditions. Lubrication system
shall include:
c. A refrigerant sensor shall be located next to
the open drive seal to detect leaks.
3. Motors shall be suitable for operation in a
refrigerant atmosphere and shall be cooled by
atomized refrigerant in contact with the motor
windings.
4. Motor stator shall be arranged for service or
removal with only minor compressor disassem-
bly and without removing main refrigerant
piping connections.
5. Full load operation of the motor shall not
exceed nameplate rating.
6. One motor winding temperature sensor (and on
spare) shall be provided.
7. Should the mechanical contractor choose to
provide a chiller with an air-cooled motor
instead of the specified semi-hermetic motor,
the contractor shall install additional cooling
a. Oil pump with factory-installed motor con-
tactor with overload protection.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Guide specifications (cont)
equipment to dissipate the motor heat as per
the following formula:
Btuh = (FLkW motor) (0.05) (3413)
Btuh = (FLkW motor) (171)
and, alternately
f. Integrated controls shall coordinate motor
speed to optimize chiller performance over a
wide variety of operating conditions.
2. Enclosure:
a. Pre-painted unit mounted, NEMA 1 cabinet
shall include hinged, lockable doors and
removable lifting lugs.
Tons = Btuh/12,000
The additional piping, valves, air-handling
equipment, insulation, wiring, switchgear
changes, ductwork, and coordination with other
trades shall be the responsibility of the mechan-
ical contractor. Shop drawings reflecting any
changes to the design shall be included in the
submittal, and incorporated into the final as-
built drawings for the project.
b. The VFD shall have a short circuit interrupt
and withstand rating of at least 65,000 amps.
c. Provisions to padlock main disconnect han-
dle in the “Off” positions shall be provided.
Mechanical interlock to prevent opening
cabinet door with disconnect in the “On”
position or moving disconnect to the “On”
position while the door is open shall be
provided.
8. Also, if an open motor is provided, a mechani-
cal room thermostat shall be provided and set
at 104 F (40 C). If this temperature is
exceeded, the chillers shall shut down and an
alarm signal shall be generated to the central
Energy Management System (EMS) display
module, prompting the service personnel to
diagnose and repair the cause of the overtem-
perature condition. The mechanical contractor
shall be responsible for all changes to the
design, including coordination with temperature
control, electrical and other trades. In addition,
the electrical power consumption of any auxil-
iary ventilation and/or mechanical cooling
required to maintain the mechanical room con-
ditions stated above shall be considered in the
determination of conformance to the scheduled
chiller energy efficiency requirement.
d. Provisions shall be made for top entry of
incoming line power cables.
3. Heat Sink:
a. The heat sink shall be refrigerant cooled.
Heat sink and mating flanges shall be suit-
able for ASME design working pressure of
185 psig (1276 kPa).
b. Refrigerant cooling shall be metered to
maintain heat sink temperature within
acceptable limits for ambient temperature.
4. VFD Rating:
a. Drive shall be suitable for operation at name-
plate voltage 10%.
b. Drive shall be suitable for continuous opera-
tion at 100% of nameplate amps and 150%
of nameplate amps for 5 seconds.
D. Unit-Mounted Variable Frequency Drive (VFD) with
Built-In Harmonic LiquiFlo™ II Filter:
c. Drive shall comply with applicable ANSI,
NEMA, UL and NEC standards.
The compressor shall be factory-mounted, factory-
wired and factory-tested prior to shipment by the
chiller manufacturer. All interconnecting wiring and
piping between the VFD and the chiller shall be
factory-installed. Customer electrical connection for
compressor motor power shall be limited to main
power leads to the VFD, and wiring liquid pumps
and tower fans to the chiller control circuit. The
VFD shall incorporate the following features:
d. Drive shall be suitable for operation in ambient
temperatures between 40 and 122 F (4 and
50 C), 95% humidity (non-condensing) for
altitudes up to 6000 ft (1829 m) above sea
level. Specific drive performance at jobsite
ambient temperature and elevation shall be
provided by the manufacturer in the bid.
5. User Interface:
1. Design:
A single display shall provide interface for pro-
gramming and display of VFD and chiller
parameters. Viewable parameters include:
a. Operating, configuration and fault messages
b. Frequency in hertz
c. Load and line side voltage and current (at the
VFD)
d. kW
a. The VFD shall be refrigerant cooled,
microprocessor based, pulse width modu-
lated design. Water cooled designs are not
acceptable.
b. Input and output power devices shall be
Insulated Gate Bipolar Transistors (IGBTs).
c. Rectifier shall convert incoming fixed volt-
age/frequency to fixed DC voltage.
e. IGBT temperature
6. VFD Performance:
d. Transistorized inverter and control regulator
shall convert fixed DC voltage to a sinusoidal
PWM waveform.
e. Low voltage control sections and main
power sections shall be physically isolated.
a. The VFD Voltage Total Harmonic Distortion
(THD) and Harmonic Current Total Demand
Distortion (TDD) shall not exceed IEEE-519
requirements using the VFD circuit breaker
26
Download from Www.Somanuals.com. All Manuals Search And Download.
input terminals as the point of common cou-
pling (PCC).
i. Motor overload protection (NEMA Class 10)
j. Motor over temperature protection
b. The VFD full load efficiency shall meet or
exceed 97% at 100% VFD rated ampacity.
c. Active rectifier shall regulate unity displace-
ment power factor to 0.99 or higher.
11. VFD Testing:
The VFD shall be factory-mounted, factory-
wired and factory-tested on the chiller prior to
shipment.
d. Voltage boost capability to provide full motor
voltage at reduced line voltage conditions.
e. The VFD shall feature soft start, linear accel-
eration, and coast to stop capabilities.
f. Base motor frequency shall permit motor to
be utilized at nameplate voltage. Adjustable
frequency range shall permit capacity con-
trol down to 15%.
g. The VFD shall have 150% instantaneous
torque generation.
E. Evaporator and Condenser:
1. Evaporator and condenser shall be of shell and
tube type construction, each in separate shells.
Units shall be fabricated with high-performance
tubing, steel shell and tube sheets with fabri-
cated steel waterboxes. Waterboxes shall be
nozzle-in-head type with stub out nozzles having
Victaulic grooves to allow for use of Victaulic
couplings.
2. Tubing shall be copper, high-efficiency type,
with integral internal and external enhance-
ment unless otherwise noted. Tubes shall be
nominal 3/4-in. OD with nominal wall thickness
of 0.025 in. measured at the root of the fin
unless otherwise noted. Tubes shall be rolled
into tube sheets and shall be individually
replaceable. Tube sheet holes shall be double
grooved for joint structural integrity. Intermedi-
ate support sheet spacing shall not exceed
36 in. (914 mm).
7. VFD Electrical Service (single point power):
a. The VFD shall have input circuit breaker
with minimum 65,000 amp interrupt
capacity.
b. The VFD shall have standard branch oil
pump circuit breaker to provide power for
chiller oil pump.
c. The VFD shall have standard 3 KVA control
power transformer with circuit breaker to
provide power for oil heater, VFD controls
and chiller controls.
d. The branch oil pump circuit breaker and
control power transformer shall be factory-
wired.
3. Waterboxes and nozzle connections shall be
designed for 150 psig (1034 kPa) minimum
working pressure unless otherwise noted.
Nozzles should have grooves to allow use of
Victaulic couplings.
4. The tube sheets of the cooler and condenser
shall be bolted together to allow for field disas-
sembly and reassembly.
e. Input power shall be 380/460 vac, 10%,
3 Phase, 50/60 Hz, 2% Hz.
8. Discrete Outputs:
5. The vessel shall display an ASME nameplate
that shows the pressure and temperature data
and the “U” stamp for ASME Section VIII,
Division 1. A re-seating pressure relief valve(s)
shall be installed on each heat exchanger. If a
non-reseating type is used, a backup reseating
type shall be installed in series.
6. Waterboxes shall have vents, drains, and covers
to permit tube cleaning within the space shown
on the drawings. A thermistor type temperature
sensor with quick connects shall be factory-
installed in each water nozzle.
7. Cooler shall be designed to prevent liquid refrig-
erant from entering the compressor. Devices
that introduce pressure losses (such as mist
eliminators) shall not be acceptable because
they are subject to structural failures that can
result in extensive compressor damage.
8. Tubes shall be individually replaceable from
either end of the heat exchanger without affect-
ing the strength and durability of the tube sheet
and without causing leakage in adjacent tubes.
115-v discrete contact outputs shall be provided
for:
a. Circuit breaker shunt trip
b. Chilled water pump
c. Condenser water pump
d. Alarm status
9. Analog Output:
An analog (4 to 20 mA) output for head pres-
sure reference shall be provided. This signal
shall be suitable to control a 2-way or 3-way
water regulating valve in the condenser piping.
10. Protection (the following shall be supplied):
a. Under-voltage
b. Over voltage
c. Phase loss
d. Phase reversal
e. Ground fault
f. Phase unbalance protection
g. Single cycle voltage loss protection
h. Programmable auto re-start after loss of
power
9. The condenser shell shall include a FLASC
(Flash Subcooler) which cools the condensed
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Guide specifications (cont)
liquid refrigerant to a reduced temperature,
thereby increasing the refrigeration cycle
efficiency.
10) Variable frequency drive status
11) Optional spare input channels
12) Line current and voltage for each phase
13) Frequency, kW, kWhr, demand kW
g. Schedule Function:
F. Refrigerant Flow Control:
To improve part load efficiency, liquid refrigerant
shall be metered from the condenser to the cooler
using a float-type metering valve to maintain the
proper liquid level of refrigerant in the heat
exchangers under both full and part load operating
conditions. By maintaining a liquid seal at the float
valve, bypassed hot gas from the condenser to the
cooler is eliminated.
The chiller controls shall be configurable for
manual or automatic start-up and shutdown.
In automatic operation mode, the controls
shall be capable of automatically starting and
stopping the chiller according to a stored
user programmable occupancy schedule.
The controls shall include built-in provisions
for accepting:
1) A minimum of two 365-day occupancy
schedules.
2) Minimum of 8 separate occupied/unoc-
cupied periods per day
3) Daylight savings start/end
4) 18 user-defined holidays
5) Means of configuring an occupancy
timed override
6) Chiller start-up and shutdown via remote
contact closure
G. Controls, Safeties, and Diagnostics:
1. Controls:
a. The chiller shall be provided with a factory-
installed and factory-wired microprocessor
control center. The control center shall include
a 16-line by 40-character liquid crystal display,
4 function keys, stop button, and alarm light.
Other languages are available using the inter-
national language translator software.
b. All chiller and motor control monitoring shall
be displayed at the chiller control panel.
c. The controls shall make use of non-volatile
memory.
d. The chiller control system shall have the ability
to interface and communicate directly to the
building control system.
e. The default standard display screen shall simul-
taneously indicate the following minimum
information:
h. Service Function:
The controls shall provide a password
protected service function which allows
authorized individuals to view an alarm
history file which shall contain the last
25 alarm/alert messages with time and date
stamp. These messages shall be displayed in
text form, not codes.
i. Network Window Function:
1) Date and time of day
2) 24-character primary system status
message
3) 24-character secondary status message
4) Chiller operating hours
5) Entering chilled water temperature
6) Leaving chilled water temperature
7) Evaporator refrigerant temperature
8) Entering condenser water temperature
9) Leaving condenser water temperature
10) Condenser refrigerant temperature
11) Oil supply pressure
Each chiller control panel shall be capable of
viewing multiple point values and statuses
from other like controls connected on a
common network, including controller main-
tenance data. The operator shall be able to
alter the remote controller’s set points or
time schedule and to force point values or
statuses for those points that are operator
forcible. The control panel shall also have
access to the alarm history file of all like con-
trollers connected on the network.
j. Pump Control:
12) Oil sump temperature
13) Percent motor rated load amps (RLA)
Upon request to start the compressor, the
control system shall start the chilled and
condenser water pumps and shall verify that
flows have been established.
f. In addition to the default screen, status
screens shall be accessible to view the status
of every point monitored by the control
center including:
k. Ramp Loading:
A user-configurable ramp loading rate, effec-
tive during the chilled water temperature
pulldown period, shall prevent a rapid
increase in compressor power consumption.
The controls shall allow configuration of the
ramp loading rate in either degrees per min-
ute of chilled water temperature pulldown or
percent motor amps per minute. During the
ramp loading period, a message shall be
1) Evaporator pressure
2) Condenser pressure
3) Compressor speed
4) Bearing oil supply temperature
5) Compressor discharge temperature
6) Motor winding temperature
7) Number of compressor starts
8) Control point settings
9) Discrete output status of various devices
28
Download from Www.Somanuals.com. All Manuals Search And Download.
displayed informing the operator that the
chiller is operating in ramp loading mode.
parameters are outside their normal operat-
ing range:
l. Chilled Water Reset:
1) High condenser pressure
2) High motor temperature
The control center shall allow reset of the
chilled water temperature set point based on
any one of the following criteria:
1) Chilled water reset based on an external
4 to 20 mA signal.
3) Low evaporator refrigerant temperature
4) High motor amps
5) High VFD rectifier temperature
6) High VFD inverter temperature
c. During the capacity override period, a pre-
alarm (alert) message shall be displayed
informing the operator which condition is
causing the capacity override. Once the con-
dition is again within acceptable limits, the
override condition shall be terminated and
the chiller shall revert to normal chilled
water control. If during either condition the
protective limit is reached, the chiller shall
shut down and a message shall be displayed
informing the operator which condition
caused the shutdown and alarm.
2) Chilled water reset based on a remote
temperature sensor (such as outdoor
air).
3) Chilled water reset based on water tem-
perature rise across the evaporator.
m. Demand Limit:
The control center shall limit amp draw of
the compressor to the rated load amps or to
a lower value based on one of the following
criteria:
1) Demand limit based on a user input
ranging from 40% to 100% of compres-
sor rated load amps
d. Internal built in safeties shall protect the
chiller from loss of water flow. Differential
pressure switches shall not be allowed to be
the only form of freeze protection.
2) Demand limit based on external 4 to
20 mA signal.
n. Controlled Compressor Shutdown:
3. Diagnostics and Service:
The controls shall be capable of being
configured to soft stop the compressor. The
display shall indicate “shutdown in progress.”
a. A self diagnostic controls test shall be an
integral part of the control system to allow
quick identification of malfunctioning
components.
2. Safeties:
b. Once the controls test has been initiated, all
pressure and temperature sensors shall be
checked to ensure they are within normal
operating range. A pump test shall automat-
ically energize the chilled water pump, con-
denser water pump, and oil pump. The
control system shall confirm that water flow
and oil pressure have been established and
require operator confirmation before pro-
ceeding to the next test.
a. Unit shall automatically shut down when any
of the following conditions occur (each of
these protective limits shall require manual
reset and cause an alarm message to be dis-
played on the control panel screen, inform-
ing the operator of the shutdown cause):
1) Motor overcurrent
2) Over voltage*
3) Under voltage*
4) Single cycle dropout*
c. In addition to the automated controls test,
the controls shall provide a manual test
which permits selection and testing of indi-
vidual control components and inputs. A
thermistor test and transducer test shall dis-
play on the ICVC screen the actual reading
of each transducer and each thermistor
installed on the chiller. All out-of-range sen-
sors shall be identified. Pressure transducers
shall be serviceable without the need for
refrigerant charge removal or isolation.
5) Low oil sump temperature
6) Low evaporator refrigerant temperature
7) High condenser pressure
8) High motor temperature
9) High compressor discharge temperature
10) Low oil pressure
11) Prolonged stall
12) Loss of cooler water flow
13) Loss of condenser water flow
14) Variable frequency drive fault
15) High variable frequency drive temperature
4. Multiple Chiller Control:
* Shall not require manual reset or cause an
alarm if auto-restart after power failure is
enabled.
The chiller controls shall be supplied as stan-
dard with a two-chiller lead/lag and a third
chiller standby system. The control system shall
automatically start and stop a lag or second
chiller on a two-chiller system. If one of the two
chillers on line goes into a fault mode, the third
standby chiller shall be automatically started.
The two-chiller lead/lag system shall allow
b. The control system shall detect conditions
that approach protective limits and take self-
corrective action prior to an alarm occur-
ring. The system shall automatically reduce
chiller capacity when any of the following
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Guide specifications (cont)
manual rotation of the lead chiller and a stag-
gered restart of the chillers after a power fail-
ure. The lead/lag system shall include load
balancing if configured to do so.
2. Spring Isolators:
Spring isolators shall be field furnished and
selected for the desired degree of isolation.
3. Spare Sensors with Leads:
Unit manufacturer shall furnish additional tem-
perature sensors and leads.
4. Sound Insulation Kit:
H. Electrical Requirements:
1. Electrical contractor shall supply and install
main electrical power line, disconnect switches,
circuit breakers, and electrical protection
devices per local code requirements and as indi-
cated necessary by the chiller manufacturer.
2. Electrical contractor shall wire the chilled water
pump and flow, condenser water pump and
flow, and tower fan control circuit to the chiller
control circuit.
Unit manufacturer shall furnish a sound insula-
tion kit that covers the compressor housing,
motor housing, compressor discharge pipe,
suction line, evaporator, and economizer (if
equipped).
5. Stand-Alone Pumpout Unit:
A free-standing pumpout unit shall be provided.
The pumpout unit shall use a semi-hermetic
reciprocating compressor with liquid-cooled
condenser. Condenser liquid piping and
3-phase motor power shall be installed at the
jobsite by the installing contractor.
3. Electrical contractor shall supply and install
electrical wiring and devices required to inter-
face the chiller controls with the building control
system if applicable.
4. Electrical power shall be supplied to the unit at
the voltage, phase, and frequency listed in the
equipment schedule.
6. Separate Storage Tank and Pumpout Unit:
A free-standing refrigerant storage tank and
pumpout unit shall be provided. The storage
vessels shall be designed per ASME Section VIII
Division 1 code with 150 psig (1034 kPa)
design pressure. Double relief valves per ANSI/
ASHRAE 15, latest edition, shall be provided.
The tank shall include a liquid level gage and
pressure gage. The pumpout shall use a
hermetic reciprocating compressor with water-
cooled condenser. Condenser water piping and
3-phase motor power shall be installed at the
jobsite by the installing contractor.
I. Piping Requirements — Instrumentation and Safeties:
1. Mechanical contractor shall supply and install
pressure gages in readily accessible locations in
piping adjacent to the chiller such that they can
be easily read from a standing position on the
floor. Scale range shall be such that design val-
ues shall be indicated at approximately mid-
scale.
2. Gages shall be installed in the entering and leav-
ing water lines of the cooler and condenser.
J. Vibration Isolation:
Chiller manufacturer shall furnish neoprene isolator
pads for mounting equipment on a level concrete
surface.
7. Building Control System Interface (LON):
The chiller control system shall have the ability
to interface and communicate directly to the
building control using a LON based system. The
LonWorks Carrier Translator shall output data
in standard LON profiles.
K. Start-Up:
1. The chiller manufacturer shall provide a factory-
trained representative, employed by the chiller
manufacturer, to perform the start-up proce-
dures as outlined in the Start-Up, Operation
and Maintenance manual provided by the
chiller manufacturer.
8. Refrigerant Charge:
The chiller shall ship from the factory fully
charged with R-134a refrigerant and oil.
9. Thermal Insulation:
2. Manufacturer shall supply the following
literature:
Unit manufacturer shall insulate the cooler
shell, economizer, suction elbow, motor shell
and motor cooling lines. Insulation shall be 1 in.
(25.4 mm) thick with a thermal conductivity not
exceeding
a. Start-up, operation and maintenance
instructions.
b. Installation instructions.
c. Field wiring diagrams.
(Btu · in.)
hr. Ft2 F
W
m C
0.28
0.0404
d. One complete set of certified drawings.
L. Special Features:
(
)
and shall conform to UL standard 94, classifica-
tion 94 HF-1.
1. Soleplate Package:
Unit manufacturer shall furnish a soleplate
package consisting of soleplates, jacking
screws, leveling pads, and neoprene pads.
10. Automatic Hot Gas Bypass:
Hot gas bypass valve and piping shall be
factory-furnished to permit chiller operation for
extended periods of time.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Cooler and Condenser Tubes:
18. Optional Compressor Discharge Isolation Valve
and Liquid Line Ball Valve:
Contact a local Carrier Representative for other
tube offerings.
12. Cooler and Condenser Passes:
These items shall be factory-installed to allow
isolation of the refrigerant charge in the con-
denser for servicing the compressor.
Unit manufacturer shall provide the cooler and/
or condenser with 1, 2 or 3 pass configuration
on the water side.
19. Pumpout Unit:
A refrigerant pumpout system shall be installed
on the chiller. The pumpout system shall
include a hermetic compressor and drive, inter-
nal piping, internal wiring, and motor. Field-
supplied main power wiring and water piping
shall be required.
13. Nozzle-In-Head, 300 psig (2068 kPa):
Unit manufacturer shall furnish nozzle-in-head
style waterboxes on the cooler and/or con-
denser rated at 300 psig (2068 kPa).
14. Marine Waterboxes:
20. BACnet Communication Option:
Unit manufacturer shall furnish marine style
waterboxes on cooler and/or condenser rated
at 150 psig (1034 kPA).
Shall provide factory installed communication
capability with a BACnet MS/TP network.
Allows integration with i-Vu® Open control sys-
tem or a BACnet building automation system.
15. Marine Waterboxes:
Unit manufacturer shall furnish marine style
waterboxes on cooler and/or condenser rated
at 300 psig (2068 kPA).
denser for servicing the compressor.
21. Optional Seismic Isolation Package:
Package shall meet International Building Code
and ASCE 7 seismic qualification requirements
in concurrence with ICC ES AC156 Accep-
tance Criteria for Seismic Qualification by
Shake-Table Testing of Nonstructural Compo-
nents and Systems. Manufacturer shall provide
seismic certificate from OSHPD (California
only).
16. Flanged Water Nozzles:
Unit manufacturer shall furnish standard
flanged piping connections on the cooler and/
or condenser.
17. Hinges:
Unit manufacturer shall furnish hinges on
waterboxes to facilitate tube cleaning.
31
910
Download from Www.Somanuals.com. All Manuals Search And Download.
Carrier Corporation • Syracuse, New York 13221
910
5-10
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Section 9
Pg 32
Catalog No. 04-52230002-01
Printed in U.S.A.
Form 23XRV-3PD
Replaces: 23XRV-2PD
Tab 9a
Download from Www.Somanuals.com. All Manuals Search And Download.
|