40RM
40RMQ
40RMS
Packaged Air-Handling Units
50/60 Hz
Installation, Start-Up and
Service Instructions
filters. All other operations should be performed by trained
CONTENTS
service personnel.
Page
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . 1
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 1
Moving and Storage . . . . . . . . . . . . . . . . . . . . . . . . 1
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Refrigerant and Chilled Water
Piping Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . 17
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . 18
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . 19
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . 22
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 22
• Use care in handling, rigging, and setting bulky
equipment.
Be sure all power to equipment is shut off before per-
forming maintenance or service. More than one discon-
nect may be present.
PRE-INSTALLATION
Moving and Storage — To transfer unit from truck to
storage site, use a fork truck. Do not stack units more than
2 high during storage. If unit is to be stored for more than
2 weeks before installation, choose a level, dry storage site
free from vibration. Do not remove plastic wrap or skid from
unit until final installation.
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-39
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fan Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . 23
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . 23
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Shaft Position Adjustment . . . . . . . . . . . . . . 24
Individual Fan Wheel Adjustment . . . . . . . . . . . 24
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . 25
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . 25
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . 25
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chilled Water Coil Freeze Protection . . . . . . . . 25
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . 25
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . 25
Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Rigging — All 40RM Series units can be rigged by us-
ing the shipping skid. Units are shipped fully assembled. Do
not remove shipping skids or protective covering until unit
is ready for final placement; damage to bottom panels can
result. Use slings and spreader bars as applicable to lift unit.
INSTALLATION
General — Allow 21⁄2 ft at front and side of unit for
service clearance and airflow. For units equipped with an econo-
mizer, refer to the accessory installation instructions for ad-
ditional clearance requirements. Be sure floor, wall, or ceil-
ing can support unit weight (Tables 1A-1F). See
Fig. 1A-1C for dimensions.
START-UP CHECKLIST . . . . . . . . . . . . . . . . CL-1,CL-2
Uncrating — Move unit as near as possible to final lo-
cation before removing shipping skid.
Remove metal banding, top skid, and plastic wrap. Ex-
amine unit for shipping damage. If shipping damage is
evident, file claim with transportation agency. Remove base
skid just prior to actual installation.
Check nameplate information against available power
supply and model number description in Fig. 2.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components
and equipment location (elevated structures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils, and cleaning and replacing
Accessories — Refer to instructions shipped with each
accessory for specific information.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI Pg 1 11-95 Replaces: 40RM-1SI
Tab 3c 2e
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1B — 40RMQ Physical Data, English
UNIT 40RMQ
008
71⁄2
012
016
NOMINAL CAPACITY (Tons)
10
15
OPERATING WEIGHT (lb)
Base Unit with TXV
Plenum
385
97
427
97
713
140
FANS
Qty...Diam. (in.)
1...15
3000
1...15
4000
2...15
6000
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
Motor Speed (rpm)
208/230-1-60
2250-3750
3000-5000
4500-7500
2.4
2.4
2.0
2.4
—
—
2.4
2.0
2.9
3.7
3.0
2.9
1725
1725
1725
1425
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
1725
1725
1425
1725
1725
1425
REFRIGERANT
Operating charge (lb)
(approx per circuit)*
R-22
3.0
2.0/2.0
3.0/3.0
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
8.33
1
10.0
2
17.67
2
No. of Splits
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/in.
15
9
16
—
3...15
Face...50/50
4...15
4...15
STEAM COIL
Max Working Pressure (psig at 400 F)
Total Face Area (sq ft)
Rows...Fins/in.
175
6.67
1...9
6.67
1...9
13.33
1...10
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
Water Volume
(gal)
150
6.67
2...8.5
6.67
2...8.5
13.33
2...8.5
8.3
1.1
13.9
1.85
(ft3)
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...11⁄8
1...5⁄8
2...11⁄8
2...5⁄8
2...11⁄8
2...5⁄8
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...2
1...2
1...11⁄4 ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
4...16 x 24 x 2
Quantity...Size (in.)
Access Location
4...16 x 24 x 2
Either Side
LEGEND
TXV
—
Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1C — 40RMS Physical Data, English
UNIT 40RMS
008
71⁄2
010
81⁄2
012
014
121⁄2
016
024
028
034
NOMINAL CAPACITY (Tons)
10
15
20
25
30
OPERATING WEIGHT (lb)
Base Unit
Plenum
390
97
391
97
391
97
661
140
677
140
683
140
1035
180
1042
180
FANS
Qty...Diam. (in.)
1...15
3000
1...15
3400
1...15
4000
2...15
5000
2...15
6000
2...15
8000
2...18
2...18
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp
(Standard Motor)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
230-3-50 and 400-3-50
Motor Speed (rpm)
208/230-1-60
10,000
12,000
2250-3750 2250-4250 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
2.4
2.4
2.0
2.4
2.4
2.4
2.0
2.4
—
—
—
—
—
—
2.4
2.0
2.9
2.9
3.0
2.9
3.7
3.0
2.9
5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0
1725
1725
1725
1425
1725
1725
1725
1425
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50 and 400-3-50
1725
1725
1425
1725
1725
1425
1725
1725
1425
1745
1745
1425
1745
1755
1425
1745
1755
1425
CHILLED WATER COIL
Max Working Pressure
(psig)
Face Area (sq ft) — Upper
Face Area (sq ft) — Lower
Rows...Fins/in.
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
8.3
—
9.0
—
4.9
4.9
8.3
5.5
8.3
8.3
11.0
8.3
12.4
12.4
15.5
12.4
3...15
175
STEAM COIL
Max Working Pressure
(psig at 400 F)
Total Face Area (sq ft)
Rows...Fins/in.
6.67
1...9
6.67
1...9
6.67
1...9
13.33
1...10
13.33
1...10
13.33
1...10
15.0
1...10
15.0
1...10
HOT WATER COIL
Max Working Pressure
(in. wg)
150
Total Face Area (sq ft)
Rows...Fins/in.
Water Volume
(gal)
6.67
2...8.5
6.67
6.67
2...8.5
13.33
2...8.5
13.33
13.33
2...8.5
15.0
2...12.5
15.0
2...12.5
2...8.5
2...8.5
8.3
1.1
13.9
1.85
14.3
1.90
(ft3)
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In
1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Chilled Water — Out
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...2
1...2
1...11⁄4 ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
4...16 x 20 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Quantity...Size (in.)
Access Location
4...16 x 24 x 2
4...16 x 24 x 2
Either Side
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1D — 40RM Physical Data, SI
UNIT 40RM
007
008
012
014
016
024
028
034
NOMINAL CAPACITY (kW)
21
26
35
43
52
70
87
105
OPERATING WEIGHT (kg)
Base Unit with TXV
Plenum
173
44
175
44
184
44
304
63
311
63
313
63
463
82
467
82
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230-1-60
1...381
1133
1...381
1604
1...381
1888
2...381
2360
2...381
2831
2...381
3775
2...457
4719
2...457
5663
850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079
0.97
1.79
0.75
1.79
1.79
1.79
1.49
1.79
—
—
—
—
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
Motor Speed (r/s)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
1.79
1.49
2.16
2.16
2.24
2.16
2.76
2.24
2.16
3.73
3.73
3.73
5.60
5.60
5.60
7.46
7.46
7.46
28.8
28.8
28.8
23.8
28.8
28.8
28.8
23.8
—
—
—
—
—
—
28.8
28.8
23.8
28.8
28.8
23.8
28.8
28.8
23.8
29.1
29.1
23.8
29.1
29.3
23.8
29.1
29.3
23.8
REFRIGERANT
Operating charge (kg)
(approx per circuit)*
R-22
1.36
1.36
0.68/0.68 0.90/0.90 1.13/1.13 1.59/1.59 2.04/2.04 2.27/2.27
DIRECT-EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
2999
0.62
1
0.77
1
0.93
2
0.93
2
1.64
2
1.85
2
2.30
2
2.77
2
No. of Splits
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/m
12
15
9
9
12
13
15
18
—
3...591
—
3...591
Face...50/50
3...670
3...591
3...591
3...670
3...591
3...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C)
Total Face Area (sq m)
Rows...Fins/m
1207
0.62
1...355
0.62
1...355
0.62
1...355
1.24
1...394
1.24
1.24
1...394
1.39
1...394
1.39
1...394
1...394
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
1034
0.62
2...335
0.62
0.62
2...335
1.24
2...335
1.24
1.24
2...335
1.39
1.39
2...493
2...335
2...335
2...493
31.4
0.031
52.6
0.052
54.1
(m3)
0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...11⁄8
1...11⁄8
2...11⁄8
2...11⁄8
2...11⁄8
2...11⁄8
2...13⁄8
2...13⁄8
1...5⁄8
2...5⁄8
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...2
1...2
1...11⁄4 ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Either Side
4...508 x 610 x 51
4...508 x 635 x 51
Quantity...Size
Access Location
4...406 x 610 x 51
LEGEND
TXV
—
Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1E — 40RMQ Physical Data, SI
UNIT 40RMQ
008
012
016
NOMINAL CAPACITY (kW)
26
35
52
OPERATING WEIGHT (kg)
Base Unit with TXV
Plenum
175
44
194
44
323
63
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230-1-60
1...381
1604
1...381
1888
2...381
2831
1203-2006
1416-2360
2124-3539
1.79
1.79
1.49
1.79
—
—
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
Motor Speed (r/s)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
230-3-50, 400-3-50
1.79
1.49
2.16
2.76
2.24
2.16
28.8
28.8
28.8
23.8
—
—
28.8
28.8
23.8
28.8
28.8
23.8
REFRIGERANT
Operating charge (kg)
(approx per circuit)*
R-22
1.36
0.91/0.91
1.36/1.36
DIRECT-EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
2999
0.77
1
0.93
2
1.64
2
No. of Splits
No. of Circuits per Split
Split Type...Percentage
Rows...Fins/m
15
9
16
—
3...591
Face...50/50
4...591
4...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C)
Total Face Area (sq m)
Rows...Fins/m
1207
0.62
1...355
0.62
1...355
1.24
1...394
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
1034
0.62
2...335
0.62
2...335
1.24
2...335
31.4
0.031
52.6
0.052
(m3)
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (Male PVC)
1...11⁄8
1...5⁄8
2...11⁄8
2...5⁄8
2...11⁄8
2...5⁄8
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...2
1...2
1...11⁄4 ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Quantity...Size
Access Location
4...406 x 610 x 51
Either Side
LEGEND
TXV
—
Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1F — 40RMS Physical Data, SI
UNIT 40RMS
008
010
012
014
016
024
028
034
NOMINAL CAPACITY (kW)
26
29
35
43
52
70
87
105
OPERATING WEIGHT (kg)
Base Unit
Plenum
177
44
177
44
177
44
300
63
307
63
310
63
469
82
473
82
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
1...381
1416
1062-
1770
1...381
1605
1204-
2006
1...381
1888
1416-
2360
2...381
2360
1770-
2949
2...381
2831
2124-
3539
2...381
3775
2831-
4719
2...457
4719
3539-
5899
2...457
5663
4247-
7079
Airflow Range (L/s)
Nominal Motor kW
(Standard Motor)
208/230-1-60
1.79
1.79
1.49
1.79
1.79
1.79
1.49
1.79
—
—
—
—
—
—
208/230-3-60, 460-3-60
575-3-60
1.79
1.49
2.16
1.79
1.49
2.16
2.76
2.24
2.16
3.73
3.73
3.73
5.60
5.60
5.60
7.46
7.46
7.46
230-3-50, 400-3-50
Motor Speed (r/s)
208/230-1-60
208/230-3-60, 460-3-60
575-3-60
230-3-50, 400-3-50
28.8
28.8
28.8
23.8
28.8
28.8
28.8
23.8
—
—
—
—
—
—
28.8
28.8
23.8
28.8
28.8
23.8
28.8
28.8
23.8
29.1
29.1
23.8
29.1
29.3
23.8
29.1
29.3
23.8
CHILLED WATER COIL
Max Working Pressure
(kPag)
Face Area (sq m) — Upper
Face Area (sq m) — Lower
Rows...Fins/m
2999
0.77
—
3...591
0.84
—
3...591
0.91
—
3...591
0.77
0.51
3...591
0.77
0.77
3...591
1.02
0.77
3...591
1.15
1.15
3...591
1.44
1.15
3...591
STEAM COIL
Max Working Pressure
(kPag at 204.4 C)
Total Face Area (sq m)
Rows...Fins/m
1207
1034
0.62
0.62
0.62
1.24
1.24
1.24
1.39
1.39
1...355
1...355
1...355
1...355
1...394
1...394
1...394
1...394
HOT WATER COIL
Max Working Pressure
(kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
0.62
2...335
0.62
2...335
0.62
2...335
1.24
2...335
1.24
2...335
1.24
2...335
1.39
2...493
1.39
2...493
31.4
0.031
52.6
0.052
54.1
0.054
(m3)
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In
1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
1...13⁄8 ODF 1...13⁄8 ODF 2...13⁄8 ODF 2...13⁄8 ODM 2...13⁄8 ODM 2...13⁄8 ODM 2...21⁄8 ODM 2...21⁄8 ODM
Chilled Water — Out
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...21⁄2
1...11⁄2
1...11⁄2
1...11⁄2
1...2
1...2
1...11⁄4 ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Either Side
4...508 x 610 x 51
4...508 x 635 x 51
Quantity...Size (mm)
Access Location
4...406 x 610 x 51
7
Download from Www.Somanuals.com. All Manuals Search And Download.
TXV
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
—
Thermostatic Expansion Valve
3. Recommended clearance:
• Rear: 3 in. (76 mm )
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMS units may require alternate or ad-
ditional field-fabricated piping access holes.
UNIT WEIGHT
UNIT
lb (kg)
40RM007
381 (173)
385 (175)
405 (184)
385 (175)
427 (194)
390 (177)
391 (177)
391 (177)
40RM008
40RM012
40RMQ008
40RMQ012
40RMS008
40RMS010
40RMS012
Fig. 1A — Dimensions — Sizes 007-012
8
Download from Www.Somanuals.com. All Manuals Search And Download.
TXV
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
—
Thermostatic Expansion Valve
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMQ016 and 40RMS units may re-
quire alternate or additional field-fabricated
piping access holes.
UNIT WEIGHT
UNIT
lb (kg)
40RM014
40RM016
40RM024
40RMQ016
40RMS014
40RMS016
40RMS024
670 (304)
685 (311)
690 (313)
713 (323)
661 (300)
677 (307)
683 (310)
Fig. 1B — Dimensions — Sizes 014-024
9
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT WEIGHT
lb (kg)
UNIT
40RM028
40RM034
40RMS028
40RMS034
1020 (463)
1030 (467)
1035 (469)
1042 (473)
TXV
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
—
Thermostatic Expansion Valve
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RMS units may require alternate or
additional field-fabricated piping ac-
cess holes.
Fig. 1C — Dimensions — Sizes 028,034
10
Download from Www.Somanuals.com. All Manuals Search And Download.
*YC and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60
power designate standard motor and high-static drive.
NOTE: See the following table for the sizes available for each unit.
UNIT
40RM
007
008
X
010
012
X
014
016
X
024
028
034
X
X
X
X
X
40RMQ
40RMS
X
X
X
X
X
X
X
X
X
X
X
Fig. 2 — Model Number Nomenclature
Unit Positioning — The unit can be mounted on the
floor for vertical application with return air entering the face
of the unit and supply air discharging vertically through the
top of the unit. The unit can also be applied in a horizontal
arrangement with return air entering horizontally and the sup-
ply air discharging horizontally. When applying the unit in
a horizontal arrangement, ensure the condensate drain pan is
located at the bottom center of the unit for adequate con-
densate disposal. See Fig. 3 for condensate connections for
each unit position.
LEGEND
Accessory Line
Typical positioning and alternate return air locations are
shown in Fig. 3. Alternate return air locations can be used by
moving the unit panel from the alternate return air location
to the standard return air location.
Alternate Air Intake and Discharge
Air Intake and Discharge
Fig. 3 — Typical Unit Positioning
IMPORTANT: Do NOT attempt to install unit with
return air entering top panel of unit. Condensate will
not drain from unit.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Isolation — Where extremely quiet operation is
essential, install isolators between floor and base of unit, or
between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points when
leveling.
Refrigerant Piping — See Tables 1A, 1B, 1D, 1E for
refrigerant pipe connection sizes. For ease in brazing, it is
recommended that all internal solder joints be made before
unit is placed in final position.
The 40RM and 40RMQ direct-expansion units have
internal factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-22. See Table 2 for
part numbers. Knockouts are provided in the unit corner posts
for 40RM and 40RMQ008 and 012 refrigerant piping. The
40RMQ016 unit requires additional field-fabricated piping
access holes. See Fig. 4, which also lists recommended knock-
outs and access holes to use for each 40RM and 40RMQ
unit size. Recommended fittings are listed in Table 3.
Refrigerant and Chilled Water Piping Access —
The 40RM Series units come with standard knockouts for
refrigerant and chilled water piping. These knockouts are lo-
cated on both sides of the unit for installation flexibility. The
standard knockouts provide sufficient access to the unit’s coils
for all 40RM and some 40RMQ units, however, for 40RMQ016
and 40RMS units, additional holes must be field-fabricated
to accommodate the piping. See Fig. 4 for the positions and
dimensions of the additional access holes required for these
units, including hole diameters and drilling dimensions. Rec-
ommended access hole use is also listed for all units. Note
that Fig. 4 shows the access holes on the control-box side of
the unit; this is the side of the unit with the coil headers, so
it is used most often for piping access.
The sensor bulb capillary tubes must be routed from the
TXVs inside the unit through one of the piping access holes.
Clamp the TXV sensor bulb on a vertical portion of the suc-
tion line, outside the unit. See Fig. 5.
FIELD-FABRICATED HOLE DIAMETERS,
in. (mm)
FIELD-FABRICATED HOLE POSITION
DIMENSIONS, in. (mm)
USE HOLE
NUMBERS
UNIT
No. 5
No. 6
No. 7
No. 8
A
B
C
D
40RM007,008
40RMQ008
1, 3
—
—
—
—
—
—
—
—
40RM012-034
40RMQ012
1, 2, 3, 4
—
—
—
—
—
—
—
—
—
—
—
—
40RMS008-012
40RMS014-024
40RMQ016
4, 5
13⁄4 (44.5)
13⁄4 (44.5) 13⁄4 (44.5) 13⁄4 (44.5)
11⁄8 (28.6) 11⁄8 (28.6) 13⁄4 (44.5)
—
—
—
6.25 (158.8)
3.0 (76.2)
3.25 (82.6)
—
—
—
4, 5, 6, 7
3*, 5, 6, 7
5, 6, 7, 8
6.0 (152.4) 10.5 (266.7)
6.125 (155.6) 10.38 (263.7)
40RMS028,034
21⁄2 (63.5) 21⁄2 (63.5) 21⁄2 (63.5) 21⁄2 (63.5) 6.0 (152.4) 9.625 (244.5) 13.38 (339.9) 17.0 (431.8)
*Must be enlarged from 11⁄8 in. to 13⁄4 inches.
NOTE: Access hole knockouts 1-4 are factory-supplied.
Fig. 4 — Refrigerant and Chilled Water Piping Access Holes
12
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped por-
tion of the suction line.
40RM Series evaporator coils have a face-split design. En-
sure that lower circuit of coil is first on/last off when con-
nected to the condensing unit and/or system controls. See
Fig. 6.
External TXV equalizer connections are provided and factory-
brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction
line at least 45 degrees above bottom, at approximately the
4 o’clock or 8 o’clock position. See Fig. 7.
NOTE: The 40RMQ units are supplied with factory-installed
thermostatic expansion valves and check valve bypasses.
No extra piping connections or kits are required to install the
40RMQ with a 38AQS condensing unit in a heat pump
system, however, some field supplied components may be
required. See the following two sections.
FIRST ON/LAST OFF=B
VERTICAL INSTALLATION
FIRST ON/LAST OFF=A
HORIZONTAL INSTALLATION
Fig. 6 — Typical Evaporator Coil Connections
(40RM, 40RMQ)
LEGEND
TXV
—
Thermostatic Expansion Valve
NOTE: Component location arrangement shown for field installation
of sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.
The TXVs and equalizer lines are factory installed.
Fig. 5 — Face-Split Coil Suction and
Liquid Line Piping (Typical)
LEGEND
TXV
—
Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.
Fig. 7 — TXV Sensing Bulb Location
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — Factory-Installed Nozzle and Distributor Data
FEEDER TUBES
PER DISTRIBUTOR*
Qty...Size (in.)
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
NOZZLE
Qty...Part No.
UNIT
40RM007
40RM008
40RMQ008
40RM012
40RMQ012
40RM014
40RM016
40RMQ016
40RM024
40RM028
40RM034
1...XVE-5
1...SVE-8
1...SVE-8
2...XVE-4
2...XVE-4
2...XVE-5
2...XVE-8
2...SVE-8
2...XVE-10
2...EBSVE-11
2...SVE-15
1...1116
1...1126
1...1657
2...1115
2...1655
2...1115
2...1116
2...1126
2...1116
2...1126
2...1126
12
15
15
9
1...E5
1...C6
1...C6
2...E4
2...E4
2...E5
2...E6
2...C6
2...E8
2...C10
2...C12
9
9
12
16
13
15
18
1
* Feeder tube size is
⁄
4
in. (6.35 mm).
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.
38AQS008/40RMQ008 HEAT PUMP SYSTEM PIPING —
Addition of a liquid solenoid valve (LLSV) is recommended
when the piping system length exceeds 75 feet. The LLSV
must be a bi-flow type suited for use in heat pump systems.
The recommended valve is Sporlan model CB14S2 (5/8-in.
ODF, 7/8-in. ODM) available from the Replacement Com-
ponents Division as part number EF23JS-214. This solenoid
valve requires Sporlan part no. MKC-2 coils that must be
purchased locally. Wire the solenoid valve in parallel with
the compressor contactor coil.
The LLSV must be installed at the outdoor unit with the
LEGEND
flow arrow pointed toward the outdoor unit (in-flow
TXV
—
Thermostatic Expansion Valve
direction for the heating mode.)
RECOMMENDED FILTER DRIERS*
(38AQS012,016/40RMQ SYSTEMS)
FILTER DRIER REQUIREMENTS FOR 38AQS012/
40RMQ012 AND 38AQS016/40RMQ016 HEAT PUMP
LIQUID
UNIT
LINE
QUANTITY
FIGURE
SYSTEMS — The 38AQS012 and 016 units do not in-
clude filter driers. Filter driers must be field-supplied
and installed in 38AQS012/40RMQ012 and 38AQS016/
40RMQ016 systems. The filter driers used with these sys-
tems must be bi-flow types suited for use in heat pump
applications. The Replacement Component Division part num-
bers listed in Fig. 8 are recommended and available for field
installation.
PART NO.
38AQS SIZE
REQUIRED REFERENCE
(in.)
1
⁄
⁄
⁄
⁄
2
8
2
8
P504-8084S
P504-8165S
P504-8084S
P504-8085S
2
1
2
2
A
B
A
A
012
016
5
1
5
*Available from Carrier Replacement Components Division.
Fig. 8 — Filter Drier Requirements —
38AQS012/40RMQ012 and 38AQS016/40RMQ016
Heat Pump Systems
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Fitting Requirements
ACCESS
HOLE NO.*
CONNECTION
FITTINGS REQUIRED†
(in.)
UNIT
CIRCUIT
TYPE
11⁄8 Street Elbow
1
3
1
3
Suction
—
—
—
—
11⁄8 Nipple, 105⁄8
L
11⁄8 Long Radius Elbow
40RM
007
5
⁄
⁄
⁄
8
8
8
Street Elbow
Nipple, 85⁄8
Long Radius Elbow
5
5
Liquid
Suction
Liquid
L
11⁄8 Street Elbow
11⁄8 Nipple, 85⁄8
L
40RM
40RMQ
008
11⁄8 Long Radius Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
Nipple, 85⁄8
Long Radius Elbow
5
5
L
13⁄8 Nipple, 43⁄8
13⁄8 Long Radius Elbow
13⁄8 Nipple, 73⁄8
13⁄8 Long Radius Elbow
L
4
Return
—
L
40RMS
008-012
13⁄8 Nipple, 65⁄8
L
5
1
Supply
Suction
—
13⁄8 Long Radius Elbow
Lower
(2) 11⁄8 Street Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
2
3
Liquid
Liquid
Lower
Upper
Nipple, 81⁄2
L
Long Radius Elbow
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
40RM
012
Nipple, 131⁄2
L
Long Radius Elbow
11⁄8 Nipple, 53⁄4
L
11⁄8 Long Radius Elbow
11⁄8 Nipple, 12 L
4
Suction
Upper
11⁄8 Long Radius Elbow
1
2
Suction
Liquid
Lower
Lower
(2) 11⁄8 Street Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
Nipple, 51⁄2
L
Long Radius Elbow
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
40RMQ
012
3
4
Liquid
Upper
Upper
Nipple, 101⁄2
L
Long Radius Elbow
11⁄8 Nipple, 55⁄8
L
11⁄8 Long Radius Elbow
11⁄8 Nipple, 12 L
Suction
11⁄8 Long Radius Elbow
11⁄8 Street Elbow
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
11⁄8 Nipple, 75⁄8
L
11⁄8 Long Radius Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
Nipple, 17⁄16
L
Long Radius Elbow
40RM
014
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
Nipple, 111⁄2
L
Long Radius Elbow
11⁄8 Nipple, 55⁄8
L
11⁄8 Long Radius Elbow
11⁄8 Nipple, 13 L
4
Suction
Upper
11⁄8 Long Radius Elbow
13⁄8 Long Radius Elbow
4
5
6
7
Supply
Return
Return
Supply
Lower
Lower
Upper
Upper
13⁄8 Nipple, 33⁄4
L
13⁄8 Long Radius Elbow
13⁄8 Long Radius Elbow
13⁄8 Nipple, 33⁄8
L
13⁄8 Long Radius Elbow
40RMS
014-024
13⁄8 Long Radius Elbow
13⁄8 Nipple, 7 L
13⁄8 Long Radius Elbow
13⁄8 Long Radius Elbow
13⁄8 Nipple, 113⁄4
L
13⁄8 Long Radius Elbow
*See Fig. 4 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Fitting Requirements (cont)
ACCESS
HOLE NO.*
CONNECTION
CIRCUIT
FITTINGS REQUIRED†
(in.)
UNIT
TYPE
11⁄8 Street Elbow
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
11⁄8 Nipple, 23⁄4
L
11⁄8 Long Radius Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
Nipple, 13⁄8
L
Long Radius Elbow
40RM
016
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
Nipple, 111⁄2
L
Long Radius Elbow
11⁄8 Nipple, 55⁄8
L
11⁄8 Long Radius Elbow
11⁄8 Nipple, 13 L
4
3
5
Suction
Suction
Liquid
Upper
Lower
Lower
11⁄8 Long Radius Elbow
11⁄8 Nipple, 3 L
11⁄8 Long Radius Elbow
5
⁄
⁄
⁄
⁄
8
8
8
8
Nipple, 27⁄8
45° Elbow
Nipple, 15⁄8
L
5
5
5
L
Long Radius Elbow
5
5
5
5
40RMQ
016
⁄
⁄
⁄
⁄
8
8
8
8
Nipple, 27⁄8
45° Elbow
Nipple, 41⁄4
L
6
7
Liquid
Upper
Upper
L
Long Radius Elbow
11⁄8 Nipple, 5 L
11⁄8 45° Elbow
11⁄8 Nipple, 83⁄4
Suction
L
11⁄8 Long Radius Elbow
11⁄8 Street Elbow
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
11⁄8 Nipple, 75⁄8
L
11⁄8 Long Radius Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
Nipple, 61⁄2
L
Long Radius Elbow
40RM
024
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
Nipple, 91⁄2
L
Long Radius Elbow
11⁄8 Nipple, 55⁄8
L
11⁄8 Long Radius Elbow
11⁄8 Nipple, 11 L
4
Suction
Upper
11⁄8 Long Radius Elbow
13⁄8 Street Elbow
13⁄8 Nipple, 11 L
13⁄8 Long Radius Elbow
5
1
2
3
Suction
Liquid
Liquid
Lower
Lower
Upper
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
Nipple, 11⁄2
L
Long Radius Elbow
40RM
028
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
Nipple, 193⁄4
L
Long Radius Elbow
13⁄8 Nipple, 43⁄16
13⁄8 Long Radius Elbow
13⁄8 Nipple, 231⁄4
13⁄8 Long Radius Elbow
L
4
Suction
Upper
L
*See Fig. 4 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Fitting Requirements (cont)
ACCESS
HOLE NO.*
CONNECTION
CIRCUIT
FITTINGS REQUIRED†
(in.)
UNIT
TYPE
21⁄8 Long Radius Elbow
5
6
7
8
1
2
3
Supply
Return
Return
Supply
Suction
Liquid
Lower
Lower
Upper
Upper
Lower
Lower
Upper
21⁄8 Nipple, 31⁄2
L
21⁄8 Long Radius Elbow
21⁄8 Long Radius Elbow
21⁄8 Nipple, 3 L
21⁄8 Long Radius Elbow
40RMS
028, 034
21⁄8 Long Radius Elbow
21⁄8 Nipple, 67⁄8
L
21⁄8 Long Radius Elbow
21⁄8 Long Radius Elbow
21⁄8 Nipple, 117⁄8
L
21⁄8 Long Radius Elbow
13⁄8 Street Elbow
13⁄8 Nipple, 3 L
13⁄8 Long Radius Elbow
5
⁄
⁄
⁄
8
8
8
Street Elbow
5
5
Nipple, 73⁄4
L
Long Radius Elbow
40RM
034
5
5
5
⁄
⁄
⁄
8
8
8
Street Elbow
Liquid
Nipple, 181⁄2
L
Long Radius Elbow
13⁄8 Nipple, 43⁄16
13⁄8 Long Radius Elbow
13⁄8 Nipple, 191⁄4
13⁄8 Long Radius Elbow
L
4
Suction
Upper
L
*See Fig. 4 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
To size, design, and install chilled water piping, consult
the Carrier System Design manual. See Fig. 9 for an ex-
ample of a typical installation. Recommended fittings are listed
in Table 3.
Chilled Water Piping — See Tables 1C and 1F for
chilled water connection sizes. For ease in brazing, it is rec-
ommended that all internal solder joints be made before unit
is placed in final position.
To access 40RMS coil vents and drains, remove the unit
side panel over the coil header. Vent and drain plugs are on
the top and bottom of header, respectively. See the Service
section for information on preventing coil freeze-up during
winter.
Knockouts are provided in the unit corner posts for 40RM
and 40RMQ refrigerant piping; additional field-fabricated ac-
cess holes are required for 40RMS chilled water piping. See
Fig. 4, which lists recommended knockouts and access holes
to use for each 40RMS unit size.
Fig. 9 — Typical 40RMS Chilled Water Piping
17
Download from Www.Somanuals.com. All Manuals Search And Download.
outlet at both ends of the unit, push drain pan down in
the slots near the drain connection, and up in the slots
on the opposite end. Retighten screws. The pan should
have a pitch of at least 1⁄4-in. over its length toward the drain
connection.
Condensate Drain — Install a trapped condensate drain
line to unit connection as shown in Fig. 10. The unit drain
connection is a PVC stub. See Fig. 11. Some areas may re-
quire an adapter to connect to either galvanized steel or
copper pipe. For these applications, install a field-supplied
threaded PVC adapter.
NOTE: A trap must be installed in the condensate drain line
to ensure that the static pressure of fans is balanced with the
water column in the drain line and that condensate can drain
completely from pan. Without a trap, air can be drawn up
drain line until water level in condensate pan becomes equal
to static pressure created by fans, preventing complete drain-
age. Conditions will worsen as filters become dirty.
Fan Motors and Drives — Motor and drive pack-
ages are factory installed in all units. The standard motor
and drive packages consist of the following items:
1 — fan motor
1 — adjustable motor pulley
1 — fan pulley
1 —fan belt (40RM007-016, 40RMQ008-016, 40RMS
008-016 units)
2 —matched fan belts (40RM024-034, 40RMS024-034
units)
Install clean-out plugs in trap. Pitch drain line downward
to an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels. Observe
all local sanitary codes.
For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive Adjust-
ment in the Service section.
As shipped, the unit’s condensate drain pan is NOT sloped
towards the drain connection. The pan slope must be changed
to pitch towards the side of the unit with the drain con-
nection. See Fig. 11. Loosen the 2 screws next to the drain
Fig. 11 — Drain Pan Slope Adjustment
NOTE: Dimensions in [ ] are in millimeters.
Fig. 10 — Condensate Drains
18
Download from Www.Somanuals.com. All Manuals Search And Download.
230-v, 3-ph, 60 Hz operation. Rewire the motor according to
the diagram plate on the motor. After reconfiguring the mo-
tor, place the sticker specifying 230-v operation (supplied in
installation packet) over the 460-v sticker on the units cor-
ner post.
Power Supply and Wiring — Check the unit data
plate to ensure that available power supply matches electri-
cal characteristics of the unit. Provide a disconnect switch of
size required to provide adequate fan motor starting current.
See Tables 4 - 6 for unit electrical data.
Fan motors are factory installed on all units. Indoor-fan
contactors are located in the fan contactor box behind the
side access panel (see Fig. 12 and 13). Wire the thermostat
to the 24-v control circuit terminal block located in the side
of the fan contactor control box, according to Fig. 14 or the
unit label diagram. If the air handler is part of a split system,
complete the wiring from the condensing unit to the ther-
mostat shown in Fig. 14.
Install disconnect switch and power wiring in accordance
with all applicable local codes. See Fig. 12-14 and the unit
label diagram. For units with motor sizes less than 5 Hp
(3.7 kW), connect power wiring to unit with no. 10 ring ter-
minal. For units with motor sizes of 5 Hp (3.7 kW) or more,
1
connect power wiring with ⁄4-in. ring terminal.
The 40RM, 40RMQ and 40RMS size 007-016 units (ex-
cept 40RM016 with YC or WD option) that have motors wired
for 460-v, 3-ph, 60 Hz operation can be field-converted to
FAN
CONTACTOR
BOX
FAN SCROLL
MOTOR
AND DRIVE
WIRING
ACCESS
CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)
FAN DRIVE
PULLEY
COIL
FILTER
ELEMENTS
TXV BULB
ACCESS
FAN
CONTACTOR
REFRIGERANT/
CHILLED WATER
PIPING ACCESS
24V
TERMINAL
BLOCK
FILTER
RETAINER
CLIP
CONDENSATE
DRAIN
CONNECTION
(VERTICAL)
POWER
WIRING
KNOCKOUT
TXV
—
Thermostatic Expansion Valve
Fig. 13 — Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)
Fig. 12 — Wiring and Service Access
(Side Panel Removed)
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4 — Electrical Data, Standard Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
Minimum
Circuit Amps
UNIT
V*-PH-HZ
LIMITS
Hp
FLA
MOCP
208/230-1-60
208/230-3-60
460-3-60
187-253
187-253
414-528
518-632
207-253
360-440
187-253
187-253
414-528
518-632
207-253
360-440
187-253
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
1.3
2.4
2.4
1.0
2.4
2.4
2.4
2.4
2.4
2.0
2.4
2.4
2.4
2.4
2.4
2.0
2.4
2.4
2.4
2.4
2.0
2.9
2.9
2.9
2.9
3.0
2.9
2.9
3.7
3.7
3.0
2.9
2.9
5.0
5.0
5.0
5.0
5.0
7.5
7.5
7.5
7.5
7.5
10.0
10.0
10.0
10.0
10.0
7.6
5.8
9.5
15
15
15
15
15
15
20
15
15
15
15
15
20
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
15
15
15
15
30/30
15
15
30
15
45/45
20
15
45
20
55/55
25
20
55
25
7.3
2.6
3.3
40RM
007
575-3-60
1.35
5.8
1.7
230-3-50
7.3
400-3-50
2.6
3.3
208/230-1-60
208/230-3-60
460-3-60
11.0
5.8
13.8
7.3
40RM
40RMQ
40RMS
008
2.6
3.3
575-3-60
2.4
3.0
230-3-50
5.8
7.3
400-3-50
2.6
3.3
208/230-1-60
208/230-3-60
460-3-60
11.0
5.8
13.8
7.3
2.6
3.3
40RMS
010
575-3-60
2.4
3.0
230-3-50
5.8
7.3
400-3-50
2.6
3.3
208/230-3-60
460-3-60
5.8
7.3
40RM
40RMQ
40RMS
012
2.6
3.3
575-3-60
2.4
3.0
230-3-50
7.5
9.4
400-3-50
3.4
4.3
208/230-3-60
460-3-60
7.5
9.4
3.4
4.3
40RM
40RMS
014
575-3-60
3.8
4.8
230-3-50
7.5
9.4
400-3-50
3.4
4.3
208/230-3-60
460-3-60
10.6
4.8
13.3
6.0
40RM
40RMQ
40RMS
016
575-3-60
3.8
4.8
230-3-50
7.5
9.4
400-3-50
3.4
4.3
208/230-3-60
460-3-60
15.2/14.4
7.2
19.0/18.0
9.0
40RM
40RMS
024
575-3-60
5.6
7.0
230-3-50
14.4
7.2
18.0
9.0
400-3-50
208/230-3-60
460-3-60
22.0/21.0
10.5
7.6
27.5/26.3
13.1
9.5
40RM
40RMS
028
575-3-60
230-3-50
21.0
10.5
26.4/25.0
12.5
9.6
26.3
13.1
33.0/31.3
15.6
12.0
31.3
15.6
400-3-50
208/230-3-60
460-3-60
40RM
40RMS
034
575-3-60
230-3-50
25.0
12.5
440-3-50
See Legend and Notes on page 21.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Electrical Data, Alternate Motors
FAN MOTOR
VOLTAGE
POWER SUPPLY
Minimum
Circuit Amps
13.8
9.4
UNIT
V*-PH-HZ
LIMITS
Hp
FLA
MOCP
208/230-1-60
208/230-3-60
460-3-60
187-253
187-253
414-528
518-632
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
187-253
414-528
518-632
207-253
360-440
2.4
2.9
2.9
2.0
2.9
2.9
3.0
2.9
2.9
2.9
2.9
3.0
2.9
2.9
3.7
3.7
3.0
5.0
5.0
3.7
3.7
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
7.5
7.5
7.5
7.5
7.5
10.0
10.0
10.0
10.0
10.0
11.0
7.5
20
15
40RM
007
3.4
4.3
15
575-3-60
2.4
3.0
15
208/230-3-60
460-3-60
7.5
9.4
15
40RM
40RMQ
40RMS
008
3.4
4.3
15
575-3-60
3.8
4.8
15
230-3-50
7.5
9.4
15
400-3-50
3.4
4.3
15
208/230-3-60
460-3-60
7.5
9.4
15
3.4
4.3
15
40RMS
010
575-3-60
3.8
4.8
15
230-3-50
7.5
9.4
15
400-3-50
3.4
4.3
15
208/230-3-60
460-3-60
10.6
4.8
13.3
6.0
20
40RM
40RMQ
40RMS
012
15
575-3-60
3.8
4.8
15
230-3-50
14.4
7.2
18.0
9.0
30
400-3-50
15
208/230-3-60
460-3-60
10.6
4.8
13.3
6.0
20
15
40RM
40RMS
014
575-3-60
5.6
7.0
15
230-3-50
14.4
7.2
18.0
9.0
30
400-3-50
15
208/230-3-60
460-3-60
15.2/14.4
7.2
19.9/18.0
9.0
30/30
15
40RM
40RMQ
40RMS
016
575-3-60
5.6
7.0
15
230-3-50
14.4
7.2
18.0
9.0
30
400-3-50
15
208/230-3-60
460-3-60
22.0/21.0
10.5
7.6
27.5/26.3
13.1
9.5
45/45
20
40RM
40RMS
024
575-3-60
15
230-3-50
21.0
10.5
26.4/25.0
12.5
9.6
26.3
13.1
33.0/31.3
15.6
12.0
31.3
15.6
45
400-3-50
20
208/230-3-60
460-3-60
55/55
25
40RM
40RMS
028
575-3-60
20
230-3-50
25.0
12.5
55
400-3-50
25
LEGEND
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
FLA
—
—
Full Load Amps
MOCP
Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nomi-
nal voltages shown. Voltages should not exceed the limits shown in
the Voltage Limits column.
393 + 403 + 396
Average Voltage =
3
1192
3
NOTES:
=
1. Minimum Circuit Amp and MOCP values are calculated in
accordance with NEC (National Electrical Code) (U.S.A. stand-
ard), Article 440.
= 397
Determine maximum deviation from average voltage.
(AB) 397 − 393 = 4 v
(BC) 403 − 397 = 6 v
(AC) 397 − 396 = 1 v
2. Motor FLA values are established in accordance with UL (Under-
writers’ Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
% Voltage Imbalance = 100 x
397
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
= 1.5%
average voltage
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
CB
—
Circuit Breaker
HC
—
—
—
—
—
—
—
Heating Contactor
Electric Heater
HTR
IFC
Indoor-Fan Contactor
Indoor-Fan Motor
National Electrical Code
Terminal Block
IFM
NEC
TB
T’STAT
Thermostat
Factory Wiring
Field Control Wiring
NOTE: Use copper conductors only.
Fig. 14 — Unit Wiring
→
Table 6 — Fan Contactor Coil Data
UNIT
40RM, 40RMQ
40RMS
MAXIMUM
VOLTAGE
(vac)
HOLDING
VA
007-034
24
10
Connecting Ductwork — Refer to the Carrier Sys-
tem Design Manual for the recommended design and layout
of ductwork. Figure 15 shows recommended duct connec-
tion to units with 2 fans.
DISCHARGE CONNECTIONS — Duct flanges are factory
supplied; they are shipped inside the unit attached to the hair-
pin end of the coil tube sheet for field installation. Using the
existing screws, install the duct flanges on the unit’s fan deck.
Each fan discharge requires 2 flanges; each flange must be
bent in the middle to conform to the discharge opening. See
Fig. 16. After flanges are installed, connect them to the sup-
ply duct using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to pre-
vent high air friction losses and air noise.
RETURN CONNECTION — When using return-air duct-
work, route return-air duct to the unit’s return air inlet near
the filter rack, using a canvas connection to prevent trans-
mission of unit vibration. If the duct blocks off the unit’s
access panel, provide a slip joint in the ductwork to permit
removal for servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoor-
air inlet to field-installed accessory economizer. Refer to econo-
mizer Installation Instructions.
Return-Air Filters — Type and size of filters are
shown in Tables 1A-1F and are factory-supplied and in-
stalled. In all units with 2 fans, a filter replacement tool (hook)
is shipped inside the unit for field use when replacing filters.
See the Service section for instructions on filter element
replacement.
Fig. 15 — Typical Fan Discharge Connections
for Multiple Fan Units
596
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 16 — Duct Flange Installation
START-UP
Fan Motor Lubrication — Fan motor supplied with
unit is permanently lubricated and requires no further
lubrication.
Before starting unit, check the following and correct as
necessary:
Fan Shaft Bearings — Bearings on 007-012 size units
are sealed, permanently lubricated bearings that require no
further lubrication. Size 014-034 units have pillow-block bear-
ings (Fig. 17) that must be lubricated with suitable bearing
grease approximately every 3 months. See Table 7 for suit-
able lubricants.
• Is unit solidly supported?
• Is fan adjusted for speed and pulley alignment?
• Are pulleys, motor, and bearings securely mounted?
• Are there any loose parts that will rattle or vibrate?
• Is condensate drain pan pitched for correct drainage?
• Are coil baffle plates tight against coil to prevent air
bypass?
• Are all panels securely fastened?
• Are all electrical connections correct and tight?
Table 7 — Lubricant Data
MANUFACTURER
LUBRICANT
Also refer to condensing unit instructions before starting
a split system. A split system start-up checklist is provided
in the back of these instructions.
Sunoco
Texaco
Texaco
Mobil
Prestige 42
Multifak 2
Regal AFB-2*
Mobilplex EP No. 2
*Preferred lubricant because it contains rust and oxidation
inhibitors.
SERVICE
Inspection and maintenance should be performed at
regular intervals and should include the following:
• Complete cleaning of cabinet, fan wheel, cooling coil, con-
densate pan and drain, heating coils, and return-air grille
(if present).
• Inspection of panels and sealing of unit against air
leakage.
• Adjustment of fan motor, belt, bearings, and wheels.
• Cleaning or replacement of filters.
• Testing for cooling/heating system leaks.
• Checking of all electrical connections.
Most unit service can be performed by removing one or
both of the unit’s side panels. Coil cleaning or removal or
insulation cleaning may require removal of a rear, top, or
bottom panel, depending on the unit’s orientation. When serv-
ice is completed, replace unit panels.
Panels — Panels are fastened to unit frame with sheet
metal screws. Fan and coil compartment must be sealed tightly
after service to prevent air from bypassing the cooling coil.
Fig. 17 — Fan Shaft, Bearings, and Fan Wheel
(Typical)
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Centering Fan Wheel — If fan and fan shaft assem-
bly are not properly centered, blades may scrape against scroll
or may create an objectionable whistling noise. It may be
necessary to adjust individual fan wheels or move entire fan
shaft. See the following two sections.
Individual Fan Wheel Adjustment — Loosen the
2 locking bolts holding fan wheel hub to shaft. See Fig. 17.
Position fan wheel in center of the fan housing and tighten
locking bolts. Clearance between wheel and housing should
be the same on both sides.
Fan Shaft Position Adjustment — Loosen set-
screw or locking collar of each fan shaft bearing. Slide shaft
into correct position and replace locking collar (Fig. 18). To
replace locking collar, push collar up against inner face of
bearing. Turn collar in direction of fan rotation until tight,
and tighten setscrew. Tightening locking collar in direction
of fan rotation results in further tightening of collar should
setscrew work itself loose.
Fan Belts — Motor mounting plate and motor support
angles are slotted to permit both vertical and horizontal
adjustment. Adjust belt(s) for correct deflection by loosen-
ing motor plate mounting bolts, moving motor/plate assem-
bly forward or back, and retightening bolts. Press down on
belt with one finger midway between fan and motor pulleys
to check deflection. For units with motor sizes up to and
3
including 3.7 Hp (2.76 kW), correct deflection is ⁄16-in.
(4.8 mm) For larger motor sizes, correct deflection is 1⁄8-in.
(3.2 mm). See Fig. 19.
NOTE: The 028 and 034 size units with 60 Hz motors are
shipped with an extra set of matching belts. Use the pre-
installed belts or extra belts depending on the adjustable
pulley setting.
If complete belt replacement is required during serv-
icing, loosen the motor plate mounting bolts (Fig. 19), move
motor/plate assembly towards fan pulley, and pull belt(s) off
pulleys. Reverse the procedure with new bolts and readjust
deflection.
Fan Rotation — Correct fan rotation with respect to
fan outlet is shown in Fig. 20.
To reverse the direction of rotation of a 3-phase fan mo-
tor, reverse any 2 of the power leads. Refer to the connection
diagram on the inside of motor terminal box cover for proper
reversing procedure of single-phase motor.
Fig. 18 — Fan Shaft Bearing
Fig. 19 — Fan Motor Mounting
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 20 — Fan Rotation
Fan Pulley Alignment — Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan pul-
ley to lock it in place.
3. Use the methods shown in Fig. 21 to check proper pulley
alignment.
Fig. 21 — Fan Pulley Adjustments
4. If pulleys are not in correct alignment, loosen the motor
holddown bolts and slide the motor axially until the pul-
leys are aligned.
Alternative freeze protection methods follow:
5. Tighten motor holddown bolts.
• Circulate hot water within the water coil’s supply main or
supplementary space heating.
• Close off supply lines to unit and open a union or field-
supplied drain valve in the return line.
Pulley and Drive Adjustment — To obtain desired
fan speed, refer to the fan motor and drive data in
Tables 8A-10D and adjust fan motor pulley as follows:
IMPORTANT: Draining from return line will not
completely drain water from coils.
1. Remove belt from fan motor pulley after loosening mo-
tor from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw move-
able flange toward fixed flange to increase the fan speed
and away from fixed flange to reduce speed. Before tight-
ening setscrew, make certain that setscrew is over nearest
flat surface of pulley hub (Fig. 21).
After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil
from freezing.
• Add a sufficient quantity of non-corrosive antifreeze to the
entire system to prevent all water within the system from
freezing.
Coil Removal — Remove unit panels and corner posts
as required. Disconnect coil connections and remove fasten-
ing screws. Remove coil through end or side sections of unit.
Increasing fan speed produces a greater load on mo-
tor. Do not exceed rated capacity of motor.
Cleaning Cooling Coil — Remove return-air filters.
Remove any heavy dirt that may have accumulated on un-
derside of coil. Coil can be cleaned more easily with a stiff
brush, vacuum cleaner, or compressed air when coil is dry.
If coil is wet or if water is to be used for cleaning, guard
against splashing water on electrical components or dam-
aging surrounding area. Clean coil baffles as applicable and
check for tight fit to be sure air does not bypass coil.
Condensate Drains — Keep condensate drains free of
dirt and foreign matter.
Return-Air Filters — Refer to Replacing Filters sec-
tion, page 39, for filter accessibility and removal. Replace
with clean filters of the sizes listed in Tables 1A-1F.
Cleaning Insulation — The insulation contains an
immobilized antimicrobial agent that helps prevent the
growth of bacteria and fungi. Clean the inner surface of the
insulation according to the separate maintenance instruc-
tions shipped with the unit.
Chilled Water Coil Freeze Protection — Shut off
water supply to unit. Remove side panel of unit and remove
vent and drain plugs in top and bottom of coil header. Drain
coil and blow out remaining water. Reinstall plugs and side
panel.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8A — Fan Motor Data, Standard Motor — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
208/230-1-60
Speed (rpm)
Hp
1725
1.3
1725
2.4
1725
2.4
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
56Y
5
5
5
⁄
8
⁄
8
⁄
8
208/230-3-60 and 460-3-60
Speed (rpm)
Hp
1725
1725
2.4
1725
2.4
1725
2.4
1725
2.9
1725
3.7
1745
5.0
1745
7.5
1745
10.0
2.4
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
56Y
56Y
56Y
56Y
S184T
11⁄8
S213T
13⁄8
S215T
13⁄8
5
5
5
5
7
7
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
575-3-60
Speed (rpm)
Hp
1725
1.0
1725
2.0
1725
2.0
1725
2.0
1725
3.0
1725
3.0
1745
5.0
1755
7.5
1755
10.0
Frame (NEMA)
Shaft Dia (in.)
230-3-50 and 400-3-50
Speed (rpm)
Hp
56
56HZ
56HZ
56HZ
56HZ
56HZ
184T
11⁄8
S213T
13⁄8
D215T
13⁄8
5
7
7
7
7
7
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
1425
2.4
1425
2.4
1425
2.4
1425
2.9
1425
2.9
1425
2.9
1425
5.0
1425
7.5
1425
10.0
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
56Y
56Y
56Y
56Y
184T
11⁄8
S213T
13⁄8
S215T
13⁄8
5
5
5
7
7
7
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
NEMA
—
National Electrical Manufacturers Association
Table 8B — Fan Motor Data, Alternate Motor — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
007
40RMS
010
UNIT
208/230-1-60
Speed (rpm)
1725
2.4
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Hp
Frame (NEMA)
Shaft Dia (in.)
208/230-3-60 and 460-3-60
56Y
5
⁄
8
Speed (rpm)
Hp
1725
2.9
1725
2.9
1725
2.9
1725
3.7
1725
3.7
1725
5.0
1745
7.5
1745
10.0
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
56Y
Y56Y
Y56Y
S184T
11⁄8
S213T
13⁄8
S215T
13⁄8
7
7
7
7
7
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
575-3-60
Speed (rpm)
Hp
1725
2.0
1725
3.0
1725
3.0
1725
3.0
1745
5.0
1745
5.0
1755
7.5
1750
10.0
Frame (NEMA)
Shaft Dia (in.)
230-3-50 and 400-3-50
Speed (rpm)
Hp
56HZ
56HZ
56HZ
56HZ
184T
11⁄8
184T
11⁄8
S213T
13⁄8
D215T
13⁄8
7
7
7
7
⁄
8
⁄
8
⁄
8
⁄
8
—
—
—
—
1425
2.9
1425
2.9
1425
5.0
1425
5.0
1425
5.0
1425
7.5
1425
10.0
Frame (NEMA)
Shaft Dia (in.)
56Y
56Y
S184T
S184T
11⁄8
S184T
11⁄8
S213T
13⁄8
S215T
13⁄8
7
7
7
⁄
8
⁄
8
⁄
8
NEMA
—
National Electrical Manufacturers Association
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8C — Fan Motor Data, Standard Motor — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
208/230-1-60
Speed (r/s)
28.75
0.97
56Y
28.75
1.79
56Y
28.75
1.79
56Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
15.9
15.9
15.9
208/230-3-60 and 460-3-60
Speed (r/s)
Shaft kW
28.75
28.75
1.79
56Y
28.75
1.79
56Y
28.75
1.79
56Y
28.75
2.16
56Y
28.75
2.76
56Y
29.08
3.73
29.08
5.60
29.08
7.46
1.79
56Y
15.9
Frame (NEMA)
Shaft Dia (mm)
575-3-60
S184T
28.6
S213T
34.9
S215T
34.9
15.9
15.9
15.9
22.2
22.2
Speed (r/s)
28.75
0.746
56
28.75
1.49
28.75
1.49
28.75
1.49
28.75
2.24
28.75
2.24
29.08
3.73
29.25
5.60
29.25
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
230-3-50 and 400-3-50
Speed (r/s)
56HZ
22.2
56HZ
22.2
56HZ
22.2
56HZ
22.2
56HZ
22.2
184T
28.6
S213T
34.9
S215T
34.9
15.9
23.75
1.79
56Y
23.75
1.79
56Y
23.75
1.79
56Y
23.75
2.16
56Y
23.75
2.16
56Y
23.75
2.16
56Y
23.75
3.73
23.75
5.60
23.75
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
184T
28.6
S213T
34.9
S215T
34.9
15.9
15.9
15.9
22.2
22.2
22.2
NEMA
—
National Electrical Manufacturers Association
Table 8D — Fan Motor Data, Alternate Motor — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
007
40RMS
010
40RMQ
40RMS
016
UNIT
208/230-1-60
Speed (r/s)
28.75
1.79
56Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
15.9
208/230-3-60 and 460-3-60
Speed (r/s)
Shaft kW
28.75
28.75
2.16
56Y
28.75
2.16
56Y
28.75
2.76
28.75
2.76
29.08
3.73
29.08
5.60
29.17
7.46
2.16
56Y
22.2
Frame (NEMA)
Shaft Dia (mm)
575-3-60
Y56Y
22.2
Y56Y
22.2
S184T
28.6
S213T
34.9
S215T
34.9
22.2
22.2
Speed (r/s)
28.75
1.49
28.75
2.24
28.75
2.24
28.75
2.24
29.08
3.73
29.08
3.73
29.25
5.60
29.17
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
230-3-50 and 400-3-50
Speed (r/s)
56HZ
22.2
56HZ
22.2
56HZ
22.2
56HZ
22.2
184T
28.6
184T
28.6
S213T
34.9
D215T
34.9
—
—
—
—
23.75
2.16
56Y
23.75
2.16
56Y
23.75
3.73
23.75
3.73
23.75
3.73
23.75
5.60
23.75
7.46
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
S184T
22.2
S184T
28.6
S184T
28.6
S213T
34.9
S215T
34.9
22.2
22.2
NEMA
—
National Electrical Manufacturers Association
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9A — Standard Drive Data, 60 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
2.4-3.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.4-4.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
8.8
1
8.8
1
8.8
1
8.8
1
9.0
17⁄16
1—A
9.0
17⁄16
1—A
9.4
17⁄16
2—B
11.0
115⁄16
2—B*
11.0
115⁄16
2—B*
1—A
1—A
1—A
1—A
(2) 42.8
(2) 43.8
(2) 42.8
(2) 43.8
Belt Pitch (in.)
40.3
41.3
41.3
42.3
42.3
42.3
41.8
FAN SPEEDS (rpm)
Factory Setting
Range
568
470-666
1200
647
549-745
1200
647
549-745
1200
764
666-863
1200
632
537-728
1200
632
537-728
1200
771
679-863
1200
752
682-841
1100
752
674-831
1100
Max Allowable Speed (rpm)
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
19.6
19.6
19.6
19.7
19.1
19.1
15.3
13.1
13.1
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.12-
10.99
6.67-
9.43
6.67-
9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
Table 9B — Medium-Static Drive Data, 60 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
8.8
1
8.0
1
8.0
1
8.0
1
8.2
17⁄16
1—A
8.6
17⁄16
1—B
9.4
17⁄16
2—B
9.4
115⁄16
9.4
115⁄16
1—A
1—A
1—A
1—A
2—B*
2—B*
(2) 38.8
(2) 39.8
(2) 38.8
(2) 39.8
Belt Pitch (in.)
42.3
40.3
40.3
40.3
41.3
41.8
41.8
FAN SPEEDS (rpm)
Factory Setting
Range
764
666-863
1200
841
733-949
1200
841
733-949
1200
841
733-949
1200
820
715-926
1200
842
742-943
1200
881
798-984
1200
881
798-984
1100
881
798-984
1100
Max Allowable Speed (rpm)
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
19.7
21.6
21.6
21.6
21.1
16.7
15.3
15.3
15.3
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
6
6
6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
6.67-
9.43
6.67-
9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9C — High-Static Drive Data, 60 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
7.0
1
6.0*
1
6.0
1
6.0
1
7.4
17⁄16
1—B
39.8
7.9
17⁄16
1—B
39.8
7.4
17⁄16
2—B
36.8
8.6
8.6
115⁄16
2—B
37.8
115⁄16
2—B
37.8
1—A
41.3
1—A
37.3
1—A
37.3
1—A
37.3
FAN SPEEDS (rpm)
Factory Setting
961
1121
1121
1121
979
1060
1118
1024
1024
838-
1084
978-
1200*†
978-
1200†
978-
1200†
873-
1096
950-
1171
1014-
1200†
873-
1075
873-
1075
Range
Max Allowable Speed (rpm)
1200
24.6
1200
28.7
1200
28.7
1200
28.7
1200
19.4
1200
1200
—
—
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
18.4
19.4
16.7
16.7
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
6
6
6
6
6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32**
9.16-
10.99
8.16-
10.02
6.67-
9.43
6.67-
9.43
*Valves for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.
Table 9D — Standard Drive Data, 50 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
2.4-3.4
2.5
2.8-3.8
2.5
2.8-3.8
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
4.3-5.3
3.0
4.3-5.3
3.0
4.3-5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
8.0
1
8.0
1
8.0
1
8.0
1
9.0
17⁄16
1—A
42.3
9.0
17⁄16
1—A
42.3
8.6
17⁄16
1—B
41.8
11.0
115⁄16
2—B
43.8
11.0
115⁄16
2—B
43.8
1—A
39.3
1—A
39.3
1—A
39.3
1—A
40.3
517
428-606
1200
588
499-677
1200
588
449-677
1200
695
606-784
1200
618
538-697
1200
618
538-697
1200
795
713-878
1200
622
557-687
1100
622
557-687
1100
Max Allowable Speed (rpm)
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
17.8
17.8
17.8
17.8
15.9
15.9
13.8
10.8
10.8
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.12-
10.99
6.67-
9.43
6.67-
9.43
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9E — Medium-Static Drive Data, 50 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
3.7-4.7
3.0
4.0-5.0
2.5
4.3-5.3
3.0
4.3-5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
8.0
1
7.0
1
7.0
1
6.0
1
7.5
17⁄16
1—A
39.3
7.9
17⁄16
1—B
39.8
7.0
17⁄16
2—A
36.8
9.4
9.4
115⁄16
2—B
39.8
115⁄16
2—B
39.8
1—A
40.3
1—A
41.3
1—A
41.3
1—A
37.3
695
606-784
1200
794
692-896
1200
794
692-896
1200
926
808-1045
1200
741
646-836
1200
756
667-848
1200
916
814-1018
1200
728
652-803
1100
728
652-803
1100
Max Allowable Speed (rpm)
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
17.8
20.4
20.4
23.7
19.0
15.1
20.4
12.6
12.6
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
5
6
6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
9.16-
10.99
6.67-
9.43
6.67-
9.43
Table 9F — High-Static Drive Data, 50 Hz — English
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
3.4-4.4
2.5
3.4-4.4
2.5
3.4-4.4
2.5
4.0-5.0
3.0
3.4-4.4
2.5
4.0-5.0
3.0
4.0-5.0
3.0
4.3-5.3
3.0
4.3-5.3
3.0
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
6.0
1
5.5
1
5.5
1
5.5
1
6.0
17⁄16
2—A
36.3
7.0
17⁄16
2—A
39.3
6.4
17⁄16
2—A
34.3
8.0
8.6
115⁄16
2—B
36.8
115⁄16
2—B
37.8
1—A
37.3
1—A
37.3
1—A
37.3
1—A
36.3
FAN SPEEDS (rpm)
Factory Setting
926
1010
1010
1166
926
916
1002
855
795
808-
1045
881-
1140
881-
1140
1036-
1200*
808-
1045
814-
1018
891-
1113
766-
944
713-
878
Range
Max Allowable Speed (rpm)
1200
23.7
1200
1200
1200
1200
23.7
1200
17.0
1200
1100
1100
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
25.9
25.9
21.6
18.5
14.8
13.8
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
6
5
6
6
6
6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32
10.44-
12.32
10.44-
12.32
916-
10.99
9.16-
10.99
9.16-
10.99
8.16-
10.02
6.67-
9.43
6.67-
9.43
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9G — Standard Drive Data, 60 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
61.0-
86.4
71.1-
96.5
71.1-
96.5
86.4-
111.8
71.1-
96.5
71.1-
96.5
94.0-
119.4
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
224
25.4
1—A
224
25.4
1—A
224
25.4
1—A
224
25.4
1—A
229
36.5
1—A
229
36.5
1—A
239
36.5
2—B
279
49.2
279
49.2
2—B*
2—B*
(2) 1087
(2) 1113
(2) 1087
(2) 1113
Belt Pitch (mm)
1024
1049
1049
1074
1074
1074
1062
FAN SPEEDS (r/s)
Factory Setting
Range
9.5
7.8-11.1
20.0
10.8
9.2-12.4
20.0
10.8
9.2-12.4
20.0
12.7
11.1-14.4
20.0
10.5
9.0-12.1
20.0
10.5
9.0-12.1
20.0
12.9
11.3-14.4
20.0
12.5
11.4-14.0
18.3
12.5
11.2-13.9
18.3
Max Allowable Speed (r/s)
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
0.327
0.327
0.327
0.328
0.318
0.318
0.255
0.218
0.218
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE
(mm)
265-313
265-313
265-313
265-313
265-313
265-313
232-279
169-240
169-240
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
Table 9H — Medium-Static Drive Data, 60 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
94.0-
119.4
109.2-
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
224
25.4
1—A
203
25.4
1—A
203
25.4
1—A
203
25.4
1—A
208
36.5
1—A
218
36.5
1—B
239
36.5
2—B
239
49.2
239
49.2
2—B*
2—B*
(2) 986
(2) 1011
(2) 986
(2) 1011
Belt Pitch (mm)
1074
1024
1024
1024
1049
1062
1062
FAN SPEEDS (r/s)
Factory Setting
12.7
14.0
14.0
14.0
13.7
14.0
14.7
14.7
14.7
11.1-
14.4
12.2-
15.8
12.2-
15.8
12.2-
15.8
11.9-
15.4
12.4-
15.7
13.3-
16.4
13.3-
16.4
13.3-
16.4
Range
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
0.328
0.360
0.360
0.360
0.352
0.278
0.255
0.255
0.255
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
6
6
6
SHAFTS CENTER DISTANCE
(mm)
265-313
265-313
265-313
265-313
265-313
265-313
232-279
169-240
169-240
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9I — High-Static Drive Data, 60 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
94.0-
119.4
109.2
134.6
109.2-
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
178
25.4
1—A
1049
152*
25.4
1—A
947
152
25.4
1—A
947
152
25.4
1—A
947
188
36.5
1—B
1011
201
36.5
1—B
1011
188
36.5
2—B
935
203
49.2
2—B
935
203
49.2
2—B
960
16.0
18.7
18.7
18.7
16.3
17.7
18.6
17.1
17.1
14.0-
18.1
16.3-
20.0*†
16.3-
20.0†
16.3-
20.0†
14.4-
18.3
15.8-
19.5
16.9-
20.0†
14.6-
17.9
14.6-
17.9
Range
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
0.410
0.478
0.478
0.478
0.323
0.307
0.323
0.278
0.278
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
6
6
6
6
6
SHAFTS CENTER DISTANCE
(mm)
265-313
265-313
265-313
265-313
265-313**
232-279
207-255
169-240
169-240
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 178 mm and
resulting fan speed is 14.0-18.3 r/s.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed
20 r/s.
**575-v unit has a center distance of 233-279.
Table 9J — Standard Drive Data, 50 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
61.0-
86.4
71.1-
96.5
71.1-
96.5
86.4-
111.8
86.4-
111.8
86.4-
111.8
109.2-
134.6
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
203
25.4
1—A
998
203
25.4
1—A
998
203
25.4
1—A
998
203
25.4
1—A
1024
229
36.5
1—A
1074
229
36.5
1—A
1074
218
36.5
1—B
1062
279
49.2
2—B
1113
279
49.2
2—B
1113
8.6
9.8
9.8
11.6
10.3
10.3
13.3
10.4
10.4
7.1-
10.1
8.3-
11.3
8.3-
11.3
10.1-
13.1
9.0-
11.6
9.0-
11.6
11.9-
14.6
9.3-
11.5
9.3-
11.5
Range
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
0.297
0.297
0.297
0.297
0.265
0.265
0.230
0.180
0.180
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
5
6
6
6
SHAFTS CENTER DISTANCE
(mm)
265-313
265-313
265-313
265-313
265-313
265-313
232-279
169-240
169-240
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9K — Medium-Static Drive Data, 50 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
86.4-
111.8
94.0-
119.4
101.6-
127.0
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
2.5
2.5
3.0
2.5
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
203
25.4
1—A
1024
178
25.4
1—A
1049
178
25.4
1—A
1049
152
25.4
1—A
947
191
36.5
1—A
998
201
36.5
1—B
1011
178
36.5
2—A
922
239
49.2
2—B
1011
239
49.2
2—B
1011
11.6
13.2
13.2
15.4
12.4
12.6
15.3
12.1
12.1
10.1-
13.1
11.5-
14.9
11.5-
14.9
13.5-
17.4
10.8-
13.9
11.1-
14.1
13.6-
17.0
10.9-
13.4
10.9-
13.4
Range
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
0.297
0.340
0.340
0.395
0.317
0.252
0.340
0.210
0.210
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
5
5
6
5
6
6
SHAFTS CENTER DISTANCE
(mm)
265-313
265-313
265-313
265-313
265-313
232-279
232-279
169-240
169-240
Table 9L — High-Static Drive Data, 50 Hz — SI
40RM
40RMQ
40RMS
008
40RM
40RMQ
40RMS
012
40RM
40RMQ
40RMS
016
40RM
40RMS
014
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
40RM
007
40RMS
010
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
86.4-
111.8
86.4-
111.8
86.4-
111.8
101.6-
127.0
86.4-
111.8
101.6-
127.0
101.6-
127.0
109.2-
134.6
109.2-
134.6
Pulley Factory Setting
Full Turns Open
2.5
2.5
2.5
3.0
2.5
3.0
3.0
3.0
3.0
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
152
25.4
1—A
947
140
25.4
1—A
947
140
25.4
1—A
947
140
25.4
1—A
922
152
36.5
2—A
922
178
36.5
2—A
998
163
36.5
2—A
871
203
49.2
2—B
935
218
49.2
2—B
960
15.4
16.8
16.8
19.4
15.4
15.3
16.7
14.3
13.3
13.5-
17.4
14.7-
19.0
14.7-
19.0
17.3-
20.0*
13.5-
17.4
13.6-
17.0
14.9-
18.6
12.8-
15.7
11.9-
14.6
Range
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
20.0
18.3
18.3
1
Change per
⁄
2
Turn of
Moveable Motor Pulley
Flange
0.395
0.432
0.432
0.360
0.395
0.283
0.308
0.247
0.230
MAX FULL TURNS FROM
CLOSED POSITION
5
5
5
6
5
6
6
6
6
SHAFTS CENTER DISTANCE
(mm)
265-313
265-313
265-313
234-279
232-279
232-279
207-255
169-240
169-240
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 20 r/s.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10A — Fan Performance Data — 0.0-1.2 in. wg ESP — English
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
UNIT
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
320
373
427
480
533
359
415
478
542
598
396
462
527
593
659
444
518
592
666
740
471
550
628
706
785
363
416
484
552
605
391
460
521
590
651
405
476
539
611
674
503
586
670
754
838
412
481
549
618
687
471
550
628
707
785
Bhp
0.22
0.31
0.42
0.54
0.69
0.32
0.45
0.62
0.82
1.03
0.42
0.60
0.80
1.05
1.33
0.58
0.82
1.11
1.44
1.83
0.61
0.87
1.17
1.53
1.93
0.37
0.53
0.81
1.17
1.51
0.51
0.80
1.13
1.60
2.10
0.54
0.85
1.20
1.69
2.22
1.07
1.64
2.37
3.28
4.39
1.15
1.76
2.55
3.52
4.71
1.78
2.72
3.93
5.44
7.27
Rpm
442
483
526
570
616
472
516
569
624
673
502
556
612
670
729
541
604
669
735
803
564
632
701
772
845
475
517
573
631
678
495
551
602
663
718
507
566
620
683
740
587
660
735
812
891
492
550
610
672
735
539
608
679
752
826
Bhp
0.32
0.42
0.53
0.67
0.82
0.44
0.57
0.75
0.95
1.17
0.54
0.72
0.93
1.18
1.47
0.71
0.95
1.25
1.59
1.98
0.74
1.00
1.31
1.67
2.08
0.58
0.78
1.08
1.47
1.83
0.75
1.08
1.43
1.93
2.45
0.79
1.13
1.50
2.03
2.58
1.37
1.98
2.74
3.69
4.83
1.53
2.17
2.99
4.00
5.22
2.17
3.15
4.40
5.94
7.81
Rpm
534
569
606
646
687
560
599
645
695
740
586
634
684
737
791
621
677
736
797
861
642
703
766
832
900
566
601
650
702
744
581
629
675
730
779
592
643
691
748
800
661
726
795
867
941
568
616
669
725
783
604
665
730
797
867
Bhp
0.42
0.53
0.64
0.78
0.94
0.55
0.68
0.86
1.08
1.29
0.65
0.84
1.06
1.31
1.60
0.83
1.08
1.38
1.72
2.12
0.86
1.13
1.44
1.81
2.22
0.80
1.02
1.35
1.76
2.15
1.00
1.35
1.73
2.26
2.81
1.03
1.40
1.81
2.36
2.93
1.67
2.31
3.12
4.09
5.27
2.00
2.66
3.50
4.53
5.78
2.63
3.64
4.92
6.49
8.39
Rpm
611
642
676
712
750
634
669
712
758
800
658
701
748
797
848
691
742
797
854
914
710
766
825
887
952
645
676
719
766
805
657
700
741
791
837
667
713
756
809
857
727
787
851
918
988
640
680
726
777
830
667
720
779
841
907
Bhp
0.52
0.63
0.75
0.89
1.05
0.65
0.79
0.98
1.20
1.42
0.76
0.95
1.18
1.44
1.73
0.94
1.20
1.51
1.86
2.26
0.97
1.25
1.57
1.94
2.36
1.02
1.26
1.62
2.06
2.47
1.25
1.63
2.04
2.59
3.16
1.28
1.68
2.11
2.69
3.29
1.97
2.65
3.49
4.50
5.70
2.56
3.22
4.07
5.12
6.38
3.17
4.18
5.48
7.08
9.01
Rpm
678
708
739
773
808
700
732
773
815
855
722
762
806
852
901
753
801
853
907
964
771
824
879
938
1000
715
743
782
826
862
725
764
801
847
890
735
776
816
865
910
789
844
904
967
1034
710
742
782
827
876
728
774
827
885
947
Bhp
0.61
0.73
0.86
1.00
1.16
0.75
0.90
1.09
1.31
1.60
0.87
1.06
1.30
1.56
1.86
1.05
1.32
1.63
1.99
2.39
1.09
1.37
1.69
2.07
2.50
1.24
1.50
1.89
2.36
2.79
1.50
1.91
2.34
2.92
3.52
1.54
1.97
2.42
3.03
3.65
2.28
2.99
3.86
4.90
6.14
3.22
3.86
4.70
5.76
7.04
3.78
4.79
6.09
7.71
9.66
Rpm
739
767
796
828
862
759
790
828
869
906
780
818
860
904
950
809
855
904
956
1010
827
877
930
987
1045
779
805
841
881
915
787
823
858
901
941
797
835
872
918
960
846
898
954
1014
1077
776
802
836
876
922
788
827
874
928
986
Bhp
0.70
0.82
0.96
1.11
1.28
0.86
1.01
1.20
1.43
1.66
0.97
1.18
1.41
1.68
1.98
1.17
1.44
1.75
2.12
2.53
1.20
1.49
1.82
2.20
2.63
1.47
1.74
2.16
2.66
3.11
1.76
2.20
2.65
3.26
3.88
1.80
2.26
2.73
3.37
4.02
2.59
3.33
4.23
5.31
6.85
3.98
4.58
5.40
6.45
7.74
4.46
5.45
6.76
8.38
10.35
Rpm
795
821
849
880
912
814
843
879
918
954
833
870
910
952
997
862
906
953
1003
1055
878
926
978
1032
1089
839
862
896
934
966
845
878
911
Bhp
0.80
0.92
1.06
1.21
1.39
0.96
1.11
1.32
1.55
1.78
1.08
1.29
1.53
1.80
2.11
1.28
1.56
1.88
2.24
2.66
1.31
1.60
1.94
2.33
2.76
1.69
1.99
2.44
2.96
3.43
2.02
2.48
2.96
3.60
4.24
2.06
2.55
3.05
3.71
4.38
2.90
3.67
4.61
5.72
7.02
4.83
5.38
6.17
7.21
8.49
5.22
6.18
7.47
9.10
11.07
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
2,550
2,975
3,400
3,825
4,250
3,000
3,500
4,000
4,500
5,000
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000
40RM
007
40RM
40RMQ
40RMS
008
40RMS
010
40RM
40RMS
012
40RMQ
012
40RM
40RMS
014
40RM
40RMS
016
951
990
854
890
924
968
1008
900
948
1001
1059
1120
840
860
889
925
966
845
878
921
970
1024
40RMQ
016
40RM
40RMS
024
40RM
40RMS
028
40RM
40RMS
034
See Legend and Notes on page 36.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10B — Fan Performance Data — 1.4-2.4 in. wg ESP — English
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
UNIT
1.4
1.6
1.8
2.0
2.2
2.4
Rpm
847
Bhp
0.89
1.02
1.16
1.32
1.49
1.06
1.22
1.43
1.66
1.90
1.18
1.40
1.64
1.92
2.23
1.39
1.67
2.00
2.37
2.79
1.43
1.72
2.06
2.45
2.90
1.91
2.23
2.71
3.25
3.75
2.29
2.78
3.28
3.94
4.60
2.33
2.84
3.36
4.05
4.75
3.21
4.02
4.99
6.13
7.46
5.79
6.26
7.01
8.02
9.29
6.07
6.98
8.24
9.86
11.84
Rpm
896
Bhp
0.98
1.11
1.26
1.42
1.60
1.16
1.33
1.54
1.78
2.02
1.29
1.51
1.76
2.04
2.35
1.50
1.79
2.12
2.50
2.92
1.54
1.84
2.19
2.58
3.03
2.14
2.48
2.98
3.55
4.07
2.56
3.08
3.60
4.28
4.97
2.61
3.14
3.69
4.40
5.12
3.53
4.37
5.37
6.54
7.91
6.83
7.22
7.91
8.89
10.15
6.98
7.84
9.07
10.67
—
Rpm
942
Bhp
1.07
1.21
1.36
1.52
1.71
1.27
1.43
1.65
1.89
2.13
1.40
1.62
1.87
2.16
2.48
1.61
1.90
2.24
2.62
3.05
1.65
1.95
2.31
2.71
—
Rpm
986
Bhp
1.16
1.30
1.46
1.63
1.81
1.37
1.54
1.76
2.00
2.25
1.50
1.73
1.98
2.27
2.60
1.72
2.02
2.36
2.74
—
Rpm
1027
1050
1073
1099
1126
1042
1067
1098
1131
1162
1059
1090
1124
1160
1199
1084
1122
1162
—
Bhp
1.25
1.40
1.55
1.73
1.92
1.47
1.65
1.87
2.12
2.37
1.61
1.84
2.10
2.39
2.72
1.83
2.13
2.48
—
Rpm
—
Bhp
—
1,800
2,100
2,400
2,700
3,000
2,250
2,600
3,000
3,400
3,750
2,550
2,975
3,400
3,825
4,250
3,000
3,500
4,000
4,500
5,000
3,000
3,500
4,000
4,500
5,000
3,750
4,300
5,000
5,700
6,250
4,500
5,300
6,000
6,800
7,500
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000
872
920
965
1008
1033
1059
1087
1001
1027
1058
1092
1124
1018
1050
1085
1122
1161
1044
1082
1124
1168
—
—
—
40RM
007
899
946
990
—
—
928
974
1018
1046
958
—
—
959
1004
913
—
—
865
—
—
40RM
40RMQ
40RMS
008
893
940
984
—
—
928
973
1017
1052
1084
975
—
—
965
1010
1043
931
—
—
1000
884
—
—
—
—
919
965
1009
1044
1082
1123
1002
1041
1084
1129
1177
1017
1060
1107
1156
—
—
—
40RMS
010
957
1002
1041
1083
958
—
—
998
—
—
1041
911
—
—
1123
1159
1199
—
1.94
2.25
2.60
—
953
998
40RM
40RMS
012
999
1042
1089
1138
973
1047
1097
927
—
—
—
—
1058
1101
1146
1194
—
1.76
2.07
2.43
2.83
—
1098
1139
1184
—
1.87
2.18
2.55
—
1137
1177
—
1.98
2.30
—
973
1018
1066
1116
1170
947
40RMQ
012
1023
1075
1130
894
—
—
—
—
—
—
996
2.37
2.73
3.26
3.86
4.39
2.84
3.38
3.92
4.63
5.34
2.89
3.45
4.01
4.75
5.49
3.85
4.72
5.75
6.96
—
1044
1062
1089
1120
1147
1046
1072
1098
1132
1164
1054
1082
1111
1146
1181
1089
1129
1173
—
2.60
2.98
3.53
4.16
4.71
3.12
3.68
4.24
4.98
5.71
3.17
3.75
4.34
5.10
5.86
4.17
5.07
6.13
—
1089
1107
1133
1162
1188
1091
1116
1141
1173
—
2.83
3.24
3.81
4.46
5.03
3.41
3.99
4.57
5.33
—
—
—
916
967
1016
1044
1076
1104
999
—
—
40RM
40RMS
014
948
997
—
—
984
1031
1060
951
—
—
1014
899
—
—
1133
1157
1181
—
3.70
4.30
4.91
—
930
980
1027
1055
1089
1123
1008
1038
1067
1104
1140
1045
1086
1133
1183
—
40RM
40RMS
016
961
1009
1045
1080
959
999
1036
908
—
—
1098
1126
1153
1187
—
3.46
4.06
4.67
5.46
—
1141
1167
1193
—
3.75
4.38
5.00
—
941
991
40RMQ
016
974
1022
1061
1098
999
1015
1054
950
—
—
1131
1169
—
4.50
5.43
—
1172
—
4.83
—
996
1042
1091
1143
1200
963
40RM
40RMS
024
1047
1102
1160
903
—
—
—
—
—
—
—
—
—
—
—
—
1021
1025
1040
1064
1095
1008
1026
1055
1092
—
7.98
8.26
8.89
9.83
11.05
7.98
8.76
9.95
11.52
—
1078
1078
1089
—
9.21
9.38
9.93
—
—
—
—
—
917
972
—
—
—
—
40RM
40RMS
028
941
991
—
—
—
—
972
1019
1053
955
—
—
—
—
1010
901
—
—
—
—
—
—
1060
1073
1098
—
9.05
9.74
10.88
—
—
—
—
—
928
978
—
—
—
—
40RM
40RMS
034
966
1011
1052
—
—
—
—
—
1011
1062
—
—
—
—
—
—
—
—
—
—
See Legend and Notes on page 36.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Legend and Notes for Table 10A and 10B
LEGEND
Factory-Supplied Filter Pressure Drop — English
Bhp
ESP
—
—
Brake Horsepower Input to Fan
External Static Pressure
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
UNIT
NOTES:
1,800
2,400
3,000
0.05
0.08
0.11
40RM
007
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pres-
sure drop.
40RM
40RMQ
40RMS
008
2,250
3,000
3,750
0.07
0.11
0.15
3. Refer to fan motor and drive tables for additional data.
2,550
3,400
4,250
0.09
0.13
0.18
40RMS
010
40RM
40RMQ
40RMS
012
3,000
4,000
5,000
0.11
0.17
0.23
40RM
40RMS
014
3,750
5,000
6,250
0.06
0.10
0.13
40RM
40RMQ
40RMS
016
4,500
6,000
7,500
0.08
0.12
0.17
40RM
40RMS
024
6,000
8,000
10,000
0.12
0.19
0.26
40RM
40RMS
028
7,500
10,000
12,500
0.15
0.22
0.30
40RM
40RMS
034
9,000
12,000
15,000
0.19
0.29
0.40
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10C — Fan Performance Data — 0-300 Pa ESP — SI
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
UNIT
0
50
100
150
200
250
300
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
r/s
kW
850
1000
1150
1300
1450
1000
1200
1400
1600
1800
1200
1400
1600
1800
2000
1450
1670
1900
2120
2350
1450
1670
1900
2120
2350
1750
2050
2350
2650
2950
2100
2450
2800
3150
3500
2100
2450
2800
3150
3500
2900
3350
3800
4250
4700
3500
4100
4700
5300
5900
4250
4950
5650
6350
7050
5.34
6.28
7.22
8.17
9.11
0.17
0.24
0.33
0.43
0.55
0.22
0.32
0.46
0.62
0.80
0.31
0.44
0.60
0.78
0.99
0.46
0.63
0.84
1.08
1.36
0.49
0.67
0.89
1.14
1.43
0.27
0.41
0.60
0.84
1.13
0.37
0.57
0.82
1.14
1.52
0.39
0.60
0.86
1.19
1.59
0.86
1.28
1.81
2.46
3.24
0.84
1.29
1.88
2.62
3.52
1.33
2.03
2.92
4.02
5.37
7.38
0.25
0.32
0.41
0.52
0.64
0.30
0.41
0.55
0.71
0.90
0.40
0.54
0.70
0.88
1.09
0.56
0.73
0.95
1.18
1.17
0.58
0.77
0.99
1.24
1.54
0.43
0.60
0.81
1.06
1.37
0.55
0.77
1.05
1.38
1.78
0.58
0.81
1.09
1.44
1.86
1.09
1.53
2.09
2.76
3.57
1.12
1.60
2.21
3.00
3.90
1.63
2.35
3.27
4.40
5.77
8.91
9.53
0.32
0.40
0.50
0.61
0.73
0.38
0.50
0.64
0.80
0.10
0.49
0.63
0.79
0.98
1.19
0.65
0.83
1.05
1.29
1.57
0.67
0.86
1.09
1.35
1.65
0.59
0.78
1.01
1.28
1.61
0.73
0.97
1.27
1.63
2.05
0.76
1.01
1.32
1.70
2.14
1.32
1.79
2.37
3.07
3.90
1.47
1.96
2.59
3.37
4.32
1.97
2.72
3.66
4.81
6.21
10.20
10.80
11.40
12.00
12.70
10.40
11.10
11.80
12.60
13.50
11.00
11.70
12.50
13.30
14.10
11.60
12.50
13.30
14.20
15.20
12.00
12.90
13.80
14.80
15.80
10.70
11.30
12.00
12.70
13.40
10.90
11.60
12.30
13.10
13.90
11.10
11.80
12.50
13.40
14.20
12.30
13.20
14.30
15.30
16.40
10.70
11.30
12.10
12.90
13.90
11.10
12.00
13.00
14.00
15.10
0.39
0.48
0.58
0.69
0.82
0.45
0.57
0.72
0.89
1.09
0.57
0.71
0.88
1.07
1.29
0.73
0.92
1.14
1.39
1.68
0.76
0.95
1.19
1.45
1.75
0.75
0.96
1.21
1.50
1.85
0.92
1.18
1.49
1.87
2.31
0.95
1.22
1.55
1.95
2.41
1.55
2.04
2.64
3.37
4.22
1.89
2.38
3.02
3.81
4.77
2.37
3.12
4.08
5.25
6.66
11.30
11.80
12.40
13.00
13.60
11.50
12.10
12.80
13.60
14.40
12.00
12.70
13.40
14.20
15.00
12.70
13.40
14.30
15.10
16.00
13.00
13.80
14.70
15.60
16.60
11.90
12.40
13.00
13.70
14.40
12.10
12.70
13.30
14.00
14.80
12.20
12.90
13.60
14.30
15.10
13.30
14.20
15.10
16.10
17.20
11.80
12.40
13.00
13.80
14.60
12.20
12.90
13.80
14.70
15.70
0.46
0.55
0.66
0.77
0.91
0.53
0.66
0.81
0.98
1.18
0.65
0.80
0.97
1.16
3.38
0.82
1.01
1.24
1.48
1.78
0.85
1.04
1.28
1.55
1.85
0.92
1.14
1.41
1.72
2.08
1.11
1.39
1.72
2.12
2.58
1.13
1.43
1.78
2.20
2.68
1.78
2.30
2.93
3.67
4.55
2.39
2.86
3.49
4.29
5.26
2.83
3.58
4.54
5.72
7.15
12.30
12.80
13.40
13.90
14.50
12.50
13.10
13.80
14.50
15.20
13.00
13.60
14.30
15.10
15.80
13.60
14.30
15.10
15.90
16.80
13.90
14.70
15.60
16.40
17.40
13.00
13.50
14.00
14.60
15.30
13.10
13.70
14.30
14.90
15.60
13.30
13.80
14.50
15.20
15.90
14.20
15.10
16.00
16.90
17.90
12.90
13.40
13.90
14.60
15.40
13.20
13.80
14.60
15.50
16.40
0.53
0.63
0.73
0.85
0.99
0.61
0.74
0.89
1.07
1.27
0.73
0.88
1.05
1.25
1.48
0.90
1.10
1.33
1.58
1.88
0.93
1.13
1.38
1.64
1.95
1.08
1.33
1.61
1.94
2.32
1.30
1.60
1.95
2.36
2.84
1.31
1.63
2.01
2.45
2.95
2.01
2.55
3.21
3.98
4.88
2.96
3.40
4.02
4.82
5.79
3.34
4.08
5.04
6.23
7.67
13.30
13.70
14.20
14.80
15.40
13.40
14.00
14.60
15.30
16.00
13.90
14.50
15.20
15.90
16.60
14.50
15.20
15.90
16.70
17.60
14.80
15.50
16.40
17.20
18.10
14.00
14.40
14.90
15.50
16.10
14.10
14.60
15.10
15.80
16.40
14.20
14.80
15.40
16.00
16.70
15.10
15.90
16.80
17.70
18.60
14.00
14.30
14.80
15.40
16.10
14.10
14.70
15.40
16.20
17.10
0.60
0.70
0.81
0.93
1.07
0.68
0.82
0.97
1.16
1.36
0.81
0.96
1.14
1.34
1.57
0.99
1.18
1.42
1.68
1.98
1.02
1.22
1.47
1.74
2.05
1.25
1.51
1.82
2.16
2.56
1.50
1.81
2.18
2.61
3.11
1.50
1.84
2.24
2.70
3.22
2.25
2.81
3.49
4.28
5.21
3.61
4.00
4.60
5.38
6.35
3.92
4.62
5.57
6.77
8.21
8.10
40RM
007
8.86
10.20
10.90
11.60
9.11
9.64
10.50
7.61
5.63
6.76
7.89
9.01
10.10
6.58
7.67
8.77
9.86
11.0
40RM
40RMQ
40RMS
008
8.49
9.88
9.42
10.70
11.60
12.50
9.76
10.40
11.40
8.35
9.25
10.60
11.40
12.30
13.20
10.50
11.40
12.30
13.30
14.30
10.90
11.80
12.80
13.90
15.00
9.41
40RMS
010
10.20
11.10
12.10
9.18
7.58
8.73
9.93
11.10
12.30
8.04
9.26
10.50
11.80
13.00
5.99
7.01
8.04
9.07
10.10
6.43
7.51
8.58
9.65
10.70
6.65
7.76
8.87
9.98
11.10
8.58
9.91
11.30
12.60
13.90
6.79
7.95
9.12
10.30
11.40
7.86
9.15
10.40
11.70
13.00
10.20
11.20
12.20
13.30
9.57
40RM
40RMS
012
10.60
11.80
12.90
14.00
7.88
40RMQ
012
8.68
10.10
10.80
11.60
12.40
9.65
40RM
40RMS
014
9.53
10.40
11.30
8.19
9.06
10.40
11.20
12.00
12.90
9.83
40RM
40RMS
016
9.96
10.90
11.90
8.39
9.30
10.60
11.50
12.30
13.20
11.20
12.20
13.30
14.50
15.60
9.42
40RMQ
016
10.20
11.20
12.20
9.96
11.10
12.30
13.60
14.80
8.14
40RM
40RMS
024
9.12
10.20
11.10
12.10
13.10
10.10
11.10
12.20
13.30
14.40
40RM
40RMS
028
10.10
11.20
12.30
8.99
10.10
11.30
12.50
13.70
40RM
40RMS
034
See Legend and Notes on page 39.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10D — Fan Performance Data — 350-600 Pa ESP — SI
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
UNIT
350
400
450
500
550
600
r/s
kW
r/s
kW
r/s
kW
0.81
0.91
1.03
1.17
1.32
0.91
1.05
1.22
1.41
1.63
1.05
1.21
1.40
1.61
1.85
1.24
1.44
1.69
1.96
2.27
1.27
1.48
1.74
2.02
—
r/s
kW
0.87
0.98
1.11
1.25
1.40
0.99
1.13
1.30
1.50
1.72
1.12
1.29
1.48
1.70
1.94
1.32
1.53
1.78
2.05
—
r/s
17.20
17.60
18.00
18.40
18.90
17.30
17.80
18.30
18.90
19.50
17.70
18.20
18.80
19.40
—
kW
0.94
1.06
1.18
1.32
1.48
1.06
1.21
1.39
1.58
1.80
1.20
1.37
1.57
1.79
—
r/s
—
kW
—
850
1000
1150
1300
1450
1000
1200
1400
1600
1800
1200
1400
1600
1800
2000
1450
1670
1900
2120
2350
1450
1670
1900
2120
2350
1750
2050
2350
2650
2950
2100
2450
2800
3150
3500
2100
2450
2800
3150
3500
2900
3350
3800
4250
4700
3500
4100
4700
5300
5900
4250
4950
5650
6350
7050
14.10
14.60
15.10
15.60
16.10
14.30
14.80
15.40
16.10
16.80
14.70
15.30
16.00
16.60
17.30
15.30
16.00
16.70
17.50
18.30
15.60
16.30
17.10
17.90
18.80
14.90
15.30
15.80
16.30
16.90
15.00
15.50
16.00
16.60
17.20
15.10
15.60
16.20
16.80
17.50
16.00
16.70
17.50
18.40
19.30
15.10
15.30
15.70
16.20
16.90
15.00
15.50
16.10
16.90
17.70
0.67
0.77
0.88
1.01
1.15
0.76
0.90
1.06
1.24
1.45
0.89
1.05
1.23
1.43
1.66
1.07
1.27
1.51
1.77
2.07
1.10
1.31
1.56
1.83
2.15
1.42
1.70
2.02
2.39
2.80
1.70
2.03
2.42
2.87
3.38
1.68
2.05
2.47
2.95
3.49
2.49
3.08
3.77
4.59
5.54
4.33
4.67
5.23
5.99
6.95
4.55
5.22
6.16
7.34
8.79
15.00
15.40
15.90
16.40
16.90
15.10
15.60
16.20
16.80
17.50
15.50
16.10
16.70
17.40
18.00
16.10
16.70
17.40
18.20
19.00
16.30
17.00
17.80
18.60
19.50
15.80
16.20
16.60
17.10
17.70
15.80
16.30
16.80
17.40
18.00
16.00
16.40
17.00
17.60
18.20
16.80
17.50
18.20
19.10
20.00
16.10
16.20
16.50
17.00
17.60
16.00
16.30
16.90
17.50
18.30
0.74
0.84
0.96
1.09
1.24
0.83
0.98
1.14
1.33
1.54
0.97
1.13
1.31
1.52
1.76
1.15
1.36
1.60
1.86
2.17
1.18
1.40
1.65
1.93
2.25
1.58
1.88
2.22
2.61
3.04
1.90
2.25
2.66
3.12
3.65
1.87
2.25
2.69
3.19
3.76
2.73
3.34
4.06
4.90
5.87
5.12
5.39
5.91
6.65
7.59
5.24
5.86
6.77
7.94
9.39
15.70
16.10
16.60
17.10
17.60
15.80
16.40
16.90
17.50
18.20
16.30
16.80
17.40
18.10
18.70
16.80
17.40
18.10
18.80
19.60
17.10
17.80
18.50
19.30
—
16.50
16.90
17.30
17.80
18.30
16.60
17.10
17.60
18.20
18.90
17.00
17.50
18.10
18.70
19.40
17.50
18.10
18.80
19.50
—
—
—
40RM
007
—
—
—
—
—
—
—
—
40RM
40RMQ
40RMS
008
—
—
—
—
—
—
—
—
—
—
—
—
40RMS
010
—
—
—
—
—
—
18.20
18.80
19.40
—
1.40
1.62
1.87
—
18.80
19.40
—
1.48
1.70
—
40RM
40RMS
012
—
—
—
—
—
—
17.80
18.40
19.20
19.90
—
1.35
1.57
1.83
2.11
—
18.40
19.10
19.80
—
1.43
1.66
1.92
—
19.10
19.70
—
1.52
1.74
—
40RMQ
012
—
—
—
—
—
—
16.60
17.00
17.40
17.90
18.40
16.70
17.10
17.60
18.10
18.70
16.80
17.20
17.80
18.30
19.00
17.50
18.20
18.90
19.80
—
1.75
2.07
2.43
2.83
3.28
2.11
2.47
2.90
3.38
3.93
2.06
2.46
2.92
3.44
4.03
2.97
3.61
4.35
5.21
—
17.40
17.80
18.20
18.60
19.10
17.40
17.80
18.30
18.80
19.40
17.50
18.00
18.50
19.00
19.60
18.30
18.90
19.60
—
1.93
2.26
2.64
3.06
3.53
2.32
2.70
3.14
3.64
4.20
2.24
2.67
3.15
3.69
4.30
3.22
3.87
4.64
—
18.20
18.50
18.90
19.30
19.80
18.20
18.60
19.00
19.50
—
2.10
2.45
2.84
3.28
3.77
2.53
2.93
3.38
3.90
—
—
—
—
—
40RM
40RMS
014
—
—
—
—
—
—
18.90
19.30
19.70
—
2.74
3.16
3.63
—
40RM
40RMS
016
—
—
18.30
18.70
19.20
19.70
—
2.43
2.88
3.38
3.94
—
19.00
19.40
19.80
—
2.62
3.09
3.61
—
40RMQ
016
—
—
19.00
19.60
—
3.47
4.14
—
19.70
—
3.72
—
40RM
40RMS
024
—
—
—
—
—
—
—
—
—
—
—
—
17.10
17.10
17.40
17.80
18.30
16.80
17.10
17.60
18.20
—
5.98
6.18
6.64
7.35
8.27
5.99
6.56
7.43
8.58
—
18.00
18.00
18.20
—
6.92
7.02
7.43
—
—
—
—
—
—
—
—
—
40RM
40RMS
028
—
—
—
—
—
—
—
—
—
—
—
—
—
—
17.70
17.90
18.30
—
6.79
7.30
8.13
—
—
—
—
—
—
—
—
—
40RM
40RMS
034
—
—
—
—
—
—
—
—
—
—
—
—
—
—
See Legend and Notes on page 39.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Legend and Notes for Tables 10C and 10D
Replacing Filters — Filters can be removed and in-
stalled from either side of the unit. Install new filters in units
that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip.
3. Remove old filters by tilting them and lifting them out of
the filter track. See Fig. 12 and 22.
4. Reverse the procedure to install new filters.
LEGEND
ESP
—
External Static Pressure
NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and
034; 20 r/s for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 51-mm
filters, and unit casing. See right for factory-supplied filter pres-
sure drop.
3. Refer to fan motor and drive tables for additional data.
To install new filters in larger units that have 2 fans, fol-
low the preceding steps, but use the factory-supplied
filter hook to slide filters within reach for removal. The
filter hook is shipped inside the unit in the baserail.
Factory-Supplied Filter Pressure Drop — SI
AIRFLOW
(L/s)
PRESSURE DROP
(Pa)
UNIT
850
1150
1450
13
20
28
40RM
007
Do not operate unit without air filters.
40RM
40RMQ
40RMS
008
1000
1400
1800
17
27
38
1200
1600
2000
21
32
45
40RMS
010
40RM
40RMQ
40RMS
012
1450
1900
2350
28
42
56
40RM
40RMS
014
1750
2350
2950
15
24
33
40RM
40RMQ
40RMS
016
2100
2800
3500
20
30
42
40RM
40RMS
024
2900
3800
4700
32
47
64
40RM
40RMS
028
3500
4700
5900
36
55
76
40RM
40RMS
034
4250
5650
7050
47
71
98
Fig. 22 — Filter Removal/Replacement
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
4
PC 111
Catalog No. 534-053
Printed in U.S.A.
Form 40RM-9SI
Pg 42
596
11-95
Replaces: 40RM-1SI
Tab 3c 2e
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RM/RMQ/RMS UNITS)
A. Preliminary Information
OUTDOOR: MODEL NO.
SERIAL NO.
SERIAL NO.
INDOOR: MODEL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE?
IF SO, WHERE:
(Y/N)
WILL THIS DAMAGE PREVENT UNIT START-UP?
(Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
(Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?
(Y/N)
(Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED?
(Y/N)
CONTROLS
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED?
(Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?
(Y/N)
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS?
(Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?
(Y/N)
ARE PROPER AIR FILTERS IN PLACE?
(Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?
(Y/N)
DO THE FAN BELTS HAVE PROPER TENSION?
(Y/N)
PIPING
40RM,RMQ
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT COILS AS REQUIRED?
(Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR?
(Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)?
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS?
(Y/N)
(Y/N)
40RMS
HAS AIR BEEN BLED FROM SYSTEM?
(Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS?
LOCATE, REPAIR, AND REPORT ANY LEAKS.
(Y/N)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI CL-1 11-95 Replaces: 40RM-1SI
Tab 3c 2e
4
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB
(AB + AC + BC)/3 = AVERAGE VOLTAGE =
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
V
AC
V
BC
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
C. Start-Up
CHECK EVAPORATOR FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1
COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
INDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
COMPRESSOR AMPS (L1/L2/L3)
/
/
/
/
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
1
1
OIL LEVEL AT ⁄8 TO ⁄3 FULL?
(Y/N)
NOTES:
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI CL-2 596 11-95 Replaces: 40RM-1SI
Tab 3c 2e
Download from Www.Somanuals.com. All Manuals Search And Download.