Bradford White Corp Water Heater BMT2H User Manual

InstallationandOperationInstructions  
Document1245  
Installation and Operation Instructions for  
BRUTE DELUXE  
Hydronic Boiler  
Model BMT2H  
Volume Water Heater  
Model BMT2V  
Sizes 500–2000 MBTU/h  
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,  
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could  
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.  
Improper installation and/or operation will void the warranty. For indoor installations, as an additional  
measure of safety, Bradford White strongly recommends installation of suitable Carbon Monoxide  
detectors in the vicinity of this appliance and in any adjacent occupied spaces.  
AVERTISSEMENT  
WARNING  
Assurez-vous de bien suivres les instructions  
If the information in this manual is not  
données dans cette notice pour réduire au  
followed exactly, a fire or explosion may  
minimum le risque d’incendie ou d’explosion ou  
result causing property damage, personal  
pour éviter tout dommage matériel, toute  
injury or loss of life.  
blessure ou la mort.  
Ne pas entreposer ni utiliser d’essence ni  
d’autres vapeurs ou liquides inflammables dans  
le voisinage de cet appareil ou de tout autre  
appareil.  
Do not store or use gasoline or other  
flammable vapors and liquids in the vicinity  
of this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not  
use any phone in your building.  
• Immediately call your gas supplier from a  
nearby phone. Follow the gas supplier's  
instructions.  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:  
• Ne pas tenter d’allumer d’appareils.  
• Ne touchez à aucun interrupteur. Ne pas vous  
servir des téléphones dansle bâtiment où  
vous vous trouvez.  
• Appelez immédiatement votre fournisseur de  
gaz depuis un voisin. Suivez les instructions  
du fournisseur.  
• If you cannot reach your gas supplier, call  
the fire department.  
• Si vous ne pouvez rejoindre le fournisseur de  
gaz, appelez le sservice des incendies.  
Installation and service must be performed by  
a qualified installer, service agency, or gas  
supplier.  
L’installation et l’entretien doivent être assurés par  
un installateur ou un service d’entretien qualifié ou  
par le fournisseur de gaz.  
238-49222-00A REV 4/11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 3  
most operating issues are caused by improper  
installation.  
The Brute Deluxe appliance is protected against  
over pressurization. A pressure relief valve is fitted to  
all appliances. It is installed on the outlet header, at the  
water outlet of the appliance.  
SECTION 1.  
General Information  
USING THIS MANUAL – Because Brute  
Deluxe Boilers and Water Heaters are identical  
appliances, with the exception of materials of  
manufacture, labels and ultimate use application,  
this manual provides information for the proper  
installation, operation and maintenance of all  
products. Where differences exist between the  
application of the appliances and their operation, the  
sections pertinent to only one appliance or the other  
will be so identified.  
IMPORTANT: The inlet gas pressure to the appliance  
must not exceed 13" W.C. (3.2kPa).  
All installations must be made in accordance with:  
1). In the U.S., the " National Fuel Gas  
Code"ANSI Z223.1/NFPA54, Latest Edition and all  
applicable local codes as required by the Authorities  
Having Jurisdiction (AHJ), or  
2). In Canada, the "Natural Gas and Propane  
Installation Code", CSA B149.1, latest edition and  
all applicable local codes as required by the AHJ.  
In the Commonwealth of Massachusetts, this app-  
liance must be installed by a licensed plumber or gas fitter.  
WARNING  
All electrical wiring is to be done in accordance with:  
1). In the U.S., the "National Electrical Code"  
(NEC), ANSI/NFPA 70, latest Edition and all applicable  
local codes as required by the AHJ, or  
2). In Canada, the “Canadian Electrical Code - Part  
1”, CSA STD. C22.1 and all applicable local codes as  
required by the AHJ.  
This appliance must be electrically grounded in  
accordance with the applicable codes and standards  
referenced above.  
The Brute Deluxe hydronic boiler or water heater must  
be installed in accordance with the procedures  
detailed in this manual, or the Bradford White warranty  
may be voided. The installation must conform to the  
requirements of the local jurisdiction having authority,  
and, in the United States, to the latest edition of the  
National Fuel Gas Code, ANSI Z223.1/NFPA54. In  
Canada, the installation must conform to the latest  
edition of the Natural Gas and Propane Installation  
Code, CSA B149.1 and/or local codes. Where  
required by the authority having jurisdiction, the  
installation of appliances must conform to the  
Standard for Controls and Safety Devices for  
Automatically Fired Boilers, ANSI/ASME CSD-1. Any  
modifications to the unit, its gas controls, or wiring  
may void the warranty. If field conditions require  
modifications, consult the factory representative  
1.2 Model Identification  
Consult the rating plate on the unit. The following  
information describes the model number structure.  
1-4 Model Series Designation  
B M T 2 = Brute Deluxe  
4
Usage  
H = Hydronic  
V = Volume Water  
before initiating such modifications.  
1.1 Introduction  
5-8 Size  
0 5 0 0 = 500,000 BTU/h input  
This manual provides information necessary for the  
installation, operation, and maintenance of Bradford  
White Brute Deluxe copper tube appliances. Read it  
carefully before installation.  
0 7 5 0 = 750,000 BTU/h input  
1 0 0 0 = 999,000 BTU/h input  
1 2 5 0 = 1,250,000 BTU/h input  
1 5 0 0 = 1,500,000 BTU/h input  
1 7 5 0 = 1,750,000 BTU/h input  
2 0 0 0 = 1,999,000 BTU/h input  
All application and installation procedures should  
be reviewed completely before proceeding with the  
installation. Consult the Bradford White factory, or local  
factory representative, with any issues or questions  
regarding this equipment. Experience has shown that  
1
2
3
T
4
2
5
6
7
8
9
10  
11  
A
12  
C
13  
K
14  
1
15  
16  
17  
B
M
SERIES  
SIZE  
LOCATION  
REVISION  
USAGE  
H
V
FUEL  
N
P
ALTITUDE  
FIRING  
MODE  
K 2-Stage  
HEAT  
OPTIONS  
CODE  
PUMP  
EXCHANGER  
OPTIONS  
B
M
T
2
0
5
0
0
C
1
A
K
P
S
X
J
N
0
1
1
1
1
2
7
0
2
5
7
0
5
0
5
0
5
0
0
0
0
0
0
0
BMT2V: H  
BMT2H:  
C
N
B
BMT2V:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 4  
9
Fuel  
the appliance or to lower floors of the structure.  
N = Natural Gas  
P = Propane  
When such a location is not available, it is  
recommended that a suitable drain pan, adequately  
drained, be installed under the appliance.  
10 Altitude  
A = 0–10,000 feet  
11 Location  
C = Indoor and Outdoor  
The appliance is design certified by CSA-  
International for installation on combustible flooring; in  
basements; in closets, utility rooms or alcoves. Brute  
Deluxe Boilers or Water Heaters must never be  
installed on carpeting. The location for the appliance  
should be chosen with regard to the vent pipe lengths  
and external plumbing. The unit shall be installed such  
that the gas ignition system components are protected  
from water (dripping, spraying, rain, etc.) during  
operation and service (circulator replacement, control  
replacement, etc.). When vented vertically, the Brute  
Deluxe must be located as close as practical to a  
chimney or outside wall. If the vent terminal and/or  
combustion air terminal terminate through a wall, and  
there is potential for snow accumulation in the local  
area, both terminals should be installed at an appropriate  
level above grade.  
12 Firing Mode  
K = Two-stage  
13 Revision  
1 = First version of design  
14 Heat Exchanger  
B = Glass-lined cast iron / copper / bronze trim  
(std. on BMT2V)  
C = Glass-lined cast iron / copper  
(std. on BMT2H)  
K = Bronze / copper  
N = Glass-lined cast iron / cupro-nickel  
(n/a on water heaters)  
P = Glass-lined cast iron / cu-nickel / bronze trim  
S = Bronze / cupro-nickel  
The dimensions and requirements that are shown in  
Table 1 should be met when choosing the locations for  
the appliance.  
15 Option Code  
X = Standardunit  
J = CSD-1, FM, IRI, IL  
1.6 Locating Pump-Mounted Water Heater  
16 Pump Options  
with Respect to Storage Tank(s)  
For best results, a pump-mounted Brute Deluxe  
water heater should be located within 15 feet (4.6m) of  
the storage tank(s). The pump is sized for 30 feet (9.1m)  
of piping.  
H = Pump mounted BMT2V, hard water pump  
N = Pump mounted (any), normal water pump  
1.3 Warranty  
If the appliance must be installed with longer piping  
runs, then larger diameter pipe or tubing shall be used.  
Consult the factory for assistance.  
Bradford White’s appliances are covered by a  
limited warranty. Owners should submit online warranty  
registration at www.branfordwhite.com.  
All warranty claims must be made to an authorized  
Bradford White representative or directly to Customer  
Service. Claims must include the serial number and  
model (this information can be found on the rating plate),  
installation date, and name of the installer. Shipping  
costs are not included in the warranty coverage.  
Some accessory items are shipped in separate  
packages. Verify receipt of all packages listed on the  
packing slip. Inspect everything for damage immediately  
upon delivery, and advise the carrier of any shortages or  
damage. Any such claims should be filed with the  
carrier. The carrier, not the shipper, is responsible for  
shortages and damage to the shipment whether visible or  
concealed.  
1.7 Locating Pump-Mounted Boiler with  
Respect to Return/Supply Header  
For the best results, a pump-mounted Brute Deluxe  
REQUIRED  
CLEARANCEFROM  
COMBUSTIBLEMATERIAL  
RECOMMENDED  
SERVICEACCESS  
CLEARANCE  
APPLIANCE  
SURFACE  
inches  
cm  
inches  
cm  
Left Side  
Right Side  
Top  
1
1
1
1
1
2.5  
2.5  
2.5  
2.5  
2.5  
24  
24  
12  
**12**  
36  
61  
61  
30  
30**  
91  
Back  
Front  
Vertical  
(Category 1)  
Vent  
Horizontal  
(Category 3)  
Vent  
1.4 Dimensions  
6*  
15.2*  
See Figures 1 and 2.  
per UL1738 venting  
system supplier’s  
instructions  
1.5 Locating the Appliance  
The appliance should be located to provide  
*1" (2.5cm) when b-vent is used.  
**When vent and/or combustion air connects to the back, recommended  
clearance is 36" (91cm).  
clearances on all sides for maintenance and inspection. It  
should not be located in an area where leakage of any  
connections will result in damage to the area adjacent to  
Table 1. Clearances.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 5  
Air  
Conn.  
W
Vent  
Conn.  
V
Shipping Weight1  
Size  
500  
A
B
C
D
E
lbs  
kg  
33¾ 85  
16¾ 43  
17  
10 25  
8
20  
6
15  
15  
20  
20  
20  
20  
8
20  
10 25  
10 25  
12 30  
12 30  
12 30  
14 36  
425 193  
505 229  
615 279  
675 306  
760 345  
825 375  
955 434  
750  
45¾ 116  
57¾ 147  
68¼ 173  
78¾ 200  
89¼ 227  
99¾ 253  
22¾ 53  
28¾ 73  
17  
17  
10¼ 26  
10¼ 26  
10¼ 26  
10¼ 26  
10 25  
10 25  
10 25  
10 25  
10 25  
10 25  
24  
24  
6
8
8
8
8
1000  
1250  
1500  
1750  
2000  
34  
87  
9
9
9
9
23  
23  
23  
23  
39½ 100  
44¾ 113  
49¾ 127  
12 30  
NOTES: 1. Add 55 lbs (25kg) for pump-mounted units.  
Dimensions in inches cm.  
Figure 1. Dimensional Data (standard units).  
1.8 Locating Appliance for Correct  
Horizontal Vent/Ducted Air Distance  
Boiler should be located within 15 feet (4.6m) of the  
supply and return headers. The pump is sized for 30 feet  
(9.1m) of piping.  
If the appliance must be installed with longer piping  
runs, then larger diameter tubing shall be used. Consult  
the factory for assistance.  
from Outside Wall  
The forced draft combustion air blower/blowers in  
the appliance has/have sufficient power to pull air and  
vent properly when the following guidelines for  
horizontal air and vent are followed (see Table 2).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 6  
Air  
Conn.  
W
Vent  
Conn.  
V
Size  
500  
A
B
C
D
E
F
33¾  
45¾  
57¾  
68¼  
78¾  
89¼  
99¾  
86  
16¾ 43  
17  
10 25  
8
20  
46¼  
58¼  
70¼  
80¾  
91¼  
117  
148  
178  
205  
232  
6
6
8
8
8
8
15  
15  
20  
20  
20  
20  
8
20  
750  
116  
147  
173  
200  
227  
253  
22¾ 58  
28¾ 73  
34¼ 87  
39½ 100  
44¾ 113  
49¾ 127  
17  
17  
10¼ 26  
10¼ 26  
10¼ 26  
10¼ 26  
10 25  
10 25  
10 25  
10 25  
10 25  
10 25  
24  
24  
10 25  
10 25  
12 30  
12 30  
12 30  
14 36  
1000  
1250  
1500  
1750  
2000  
9
9
9
9
23  
23  
23  
23  
101¾ 258  
112¼ 285  
12 30  
Figure 2. Dimensional Data (pump-mounted models).  
HORIZONTAL  
VENTPIPE  
DIAMETER  
AIR COLLAR  
&PIPE  
DIAMETER  
VENT COLLAR  
SIZE  
MAX.PIPE  
LENGTH  
MAX.NO.  
OF ELBOWS  
SIDEWALL  
SIDEWALL  
COMBUSTION  
AIRTERMINAL  
SIZE  
VENT  
TERMINAL  
in  
cm  
20  
25  
25  
30  
30  
30  
36  
in  
6
8
8
8
8
8
12  
cm  
15  
20  
20  
20  
20  
20  
30  
in  
6
6
8
8
8
8
12  
cm  
15  
15  
20  
20  
20  
20  
30  
ft  
m
PARTNUMBER  
CA001401  
CA001401  
CA001402  
CA001403  
CA001403  
CA001403  
CA001404  
PARTNUMBER  
20260701  
20260701  
20260703  
20260703  
20260703  
20260703  
20260706  
500  
750  
8
50 15  
50 15  
50 15  
50 15  
50 15  
50 15  
50 15  
3
3
3
3
3
3
3
10  
10  
12  
12  
12  
14  
1000  
1250  
1500  
1750  
2000  
Table 2. Horizontal Vent / Combustion Air Parameters.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 7  
NOTE: The vent collar size is larger than the size of the  
vent pipe that can be used. Vent collar size and  
horizontal pipe diameters can be found in Table 2. The  
larger vent collar size is to accommodate Category I  
(vertical) vent systems.  
communicate with the outdoors and shall have a  
minimum free area of 1 square inch per 3000 BTU/hr (7  
square cm/kW) of the total input rating of all equipment  
located in the enclosure. This opening must not be less  
than the sum of the areas of all vent connectors in the  
confined space.  
NOTE: When located on the same wall, the Brute Deluxe  
combustion air intake terminal must be installed a minimum  
of 12" (30cm) below the exhaust vent terminal and sep-  
arated by a minimum of 36 inches (91cm) horizontally.  
The air intake terminal must be installed high enough  
to avoid blockage from snow, leaves and other debris.  
Other methods of introducing combustion and  
ventilation air are acceptable, providing they conform to  
the requirements in the applicable codes listed above.  
In Canada, consult local building and safety codes or,  
in absence of such requirements, follow CSA B149.1.  
2.1.2 IntakeCombustionAir  
SECTION 2.  
The combustion air can be taken through the wall,  
or through the roof. When taken from the wall, it must be  
taken from out-of-doors by means of the horizontal wall  
terminal (see Table 2). When taken from the roof, a  
field-supplied rain cap or an elbow arrangement must be  
used to prevent entry of rain water (see Figure 3).  
Use single-wall galvanized pipe, per Table 4, for  
the combustion air intake (see Table 2 for appropriate  
size). Route the intake to the heater as directly as  
possible. Seal all joints with tape. Provide adequate  
hangers. The unit must not support the weight of the  
combustion air intake pipe. Maximum linear pipe length  
allowed is 50 feet (15.2m). Three elbows have been  
calculated into the 50-foot (15.2m) linear run. Subtract  
10 allowable linear feet (3.0m) for every additional  
elbow used (see Table 2). When fewer than 3 elbows are  
used, the maximum linear pipe length allowed is still 50  
feet (15.2m).  
Venting and Combustion Air  
2.1 Combustion Air  
Brute Deluxe boilers and water heaters must have  
provisions for combustion and ventilation air in  
accordance with section 5.3, Air for Combustion and  
Ventilation, of the National Fuel Gas Code, ANSI  
Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1,  
Installation Codes, or applicable provisions of the local  
building codes.  
A Brute Deluxe appliance may receive combustion  
air from the space in which it is installed, or it can be  
ducted directly to the unit from the outside. Ventilation  
air must be provided in either case.  
2.1.1 CombustionAirFromRoom  
In the United States, the most common  
requirements specify that the space shall communicate  
with the outdoors in accordance with method 1 or 2,  
which follow. Where ducts are used, they shall be of the  
same cross-sectional area as the free area of the  
openings to which they connect.  
The connection for the intake air pipe is on the  
filter box. The Brute Deluxe appliances have venting  
and combustion air ducting attached to the top.  
In addition to air needed for combustion, air shall  
also be supplied for ventilation, including all air required  
for comfort and proper working conditions for personnel.  
The Brute Deluxe loses less than 1 percent of its input  
Method 1: Two permanent openings, one  
commencing within 12 inches (30 cm) of the top and one  
commencing within 12 inches (30 cm) of the bottom, of  
the enclosure shall be provided. The openings shall  
communicate directly, or by ducts, with the outdoors or  
spaces that freely communicate with the outdoors. When  
directly communicating with the outdoors, or when  
communicating to the outdoors through vertical ducts,  
each opening shall have a minimum free area of 1 square  
inch per 4000 BTU/hr (5.5 square cm/kW) of total input  
rating of all equipment in the enclosure. When  
EACHOPENING*  
UNIT  
SIZE  
SQUAREINCHES  
SQUARECM  
500  
750  
125  
188  
250  
313  
375  
438  
500  
807  
1213  
1613  
2020  
2420  
2826  
3226  
1000  
1250  
1500  
1750  
2000  
communicating to the outdoors through horizontal ducts,  
each opening shall have a minimum free area of not less  
than 1 square inch per 2000 BTU/hr (11 square cm/kW)  
of total input rating of all equipment in the enclosure.  
Table 3 shows data for this sizing method, for each Brute  
Deluxe model.  
*Net Free Area in Square Inches / Square cm  
Area indicated is for one of two openings; one at floor level and one  
at the ceiling, so the total net free area could be double the figures  
indicated.  
Method 2: One permanent opening, commencing  
within 12 inches (30 cm) of the top of the enclosure, shall  
be permitted. The opening shall directly communicate  
with the outdoors or shall communicate through a vertical  
or horizontal duct to the outdoors or spaces that directly  
Thischartisforusewhencommunicatingdirectlywiththeoutdoors.  
For special conditions and alternate methods, refer to the latest  
edition of ANSI Z223.1.  
Note: Check with louver manufacturers for net free area of louvers.  
Correct for screen resistance to the net free area if a screen is  
installed. Check all local codes applicable to combustion air.  
Table 3. Combustion Air Openings.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 8  
rating to the room, but other heat sources may be present.  
may lead to serious injury or death. If safe operation of  
all appliances connected to a common vent cannot be  
assured, including prevention of spillage of flue gasses  
into living spaces, common venting should not be applied,  
and appliances should each be vented separately.  
2.2 Venting  
2.2.1 VentCategories  
Depending upon desired Brute Deluxe venting, it  
may be considered a Category I or a Category III  
appliance. In general, a vertical vent system will be a  
Category I system. However, in rare instances, a vertical  
vent system may be considered Category III. In the U.S.,  
the National Fuel Gas Code (ANSI Z223.1-Latest  
Edition), or in Canada the CSA B149.1 (latest edition),  
defines a Category I vent system, and includes rules and  
tables to size these vent systems. If the Brute Deluxe’s  
vertical vent system does not satisfy the criteria for  
Category I venting, it must be vented as a Category III  
system.  
Proper vent sizing, construction and safety  
requirements from the National Fuel Gas Code, ANSI  
Z223.1 or in Canada, from CSA B149.1 as well as all  
applicable local codes must be followed.  
As an additional precaution, it is recommended that  
a Carbon Monoxide (CO) alarm be installed in all  
enclosed spaces containing combustion appliances.  
Brute Deluxe units are not allowed to be vented  
into a common horizontal vent system, unless a properly  
sized vent fan is used, and the common vent system is  
properly designed by the vent fan manufacturer or a  
qualified engineer.  
Refer to the installation and operating instructions on  
all appliances to be common vented for instructions,  
warnings, restrictions and safety requirements. If safe  
operation of all appliances connected to a common vent  
cannot be assured, including prevention of spillage of flue  
gasses into living spaces, common venting should not be  
applied, and appliances should each be vented separately.  
All Brute Deluxe vent systems which discharge  
horizontally (without the use of a power venter) are  
considered Category III vent systems.  
2.2.2 CategoryIVent  
When vented as a category I appliance, the vent  
system must conform to the National Fuel Gas Code (ANSI  
Z223.1-Latest Edition) in the U.S., or in Canada, to CSA  
B149.1 (latest edition). The vent system must be sized and  
installed for a Category I Fan-Assisted Appliance.  
If chimney height is greater than 25 feet, or if multiple  
units are vented into the same vertical vent, a barometric  
damper must be installed on each appliance, such that the  
flue draft does not exceed (negative) 0.1" w.c.  
If using a power venter for any type of Category I  
venting, the draft should be set between (negative) 0.01  
and 0.10" w.c.  
2.2.4 CategoryIIIVent  
When the Brute Deluxe is vented with horizontal  
discharge, it must be installed per this installation  
manual and the venting system manufacturer’s  
installation instructions. The vent system must be sealed  
stainless steel (see Table 5).  
Route the vent pipe to the heater as directly as  
possible. Seal all joints and provide adequate hangers as  
required in the venting system manufacturer’s Instal-  
2.2.3 CommonVentingSystems  
Brute Deluxe units are Category I fan-assisted  
when vented vertically and adhering to all applicable  
codes.  
When common venting Brute Deluxe fan-assisted  
unit with other appliances through one shared vertical  
duct called a “common vent”, special care must be taken  
by the installer to ensure safe operation. In the event that  
the common vent is blocked, it is possible, especially for  
fan-assisted devices, to vent backwards through non-  
operating appliances sharing the vent, allowing  
combustion products to infiltrate occupied spaces. If the  
appliances are allowed to operate in this condition,  
serious injury or death may occur.  
WARNING  
Operation of appliances with a blocked common vent  
TERM  
DESCRIPTION  
Single-wall galvanized steel pipe, 24 gauge  
minimum (either insulated or non-insulated)  
Pipe  
Joint  
Permanent duct tape or aluminum tape  
Sealing  
Table 4. Required Combustion Air Piping Material.  
Figure 3. Combustion Air and Vent Through Roof.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 9  
lation Instructions. Horizontal portions of the venting  
system must be supported to prevent sagging and may  
not have any low sections that could trap condensate.  
The unit must not support the weight of the vent pipe.  
Horizontal runs must slope downwards not less than ¼  
inch per foot (2 cm/m) from the unit to the vent terminal.  
Reference Table 1 for the size of the Category III vent  
system. Up to three elbows can be used with 50 linear  
feet (15.2m) of pipe. Subtract 10 allowable linear feet  
(3.0m) for every additional elbow used.  
on building surfaces or other nearby objects. Vent  
products may damage such surfaces or objects.  
7. If the boiler or water heater uses ducted  
combustion air from an intake terminal located on  
the same wall, locate the vent terminal at least 3  
feet (0.9m) horizontally from the combustion air  
terminal, and locate the vent terminal at least 1 foot  
(0.3m) above the combustion air terminal.  
2.3.2 SideWallCombustionAirTerminal  
The side wall combustion air terminal (see Table  
2) must be used when the unit takes its combustion air  
through a duct from a side wall. Consider the following  
wheninstallingtheterminal:  
1. Do not locate the air inlet terminal near a source of  
corrosive chemical fumes (e.g., cleaning fluid,  
chlorinated compounds, etc.)  
2. Locate the terminal so that it will not be subject to  
damage by accident or vandalism.  
WARNING  
The outdoor vent terminal gets hot. Unit must be  
installed in such a way as to reduce the risk of burns  
from contact with the vent terminal.  
2.3 Locating Vent & Combustion Air  
Terminals  
2.3.1 Side Wall Vent Terminal  
3. Locate the combustion air terminal so that it cannot  
be blocked by snow. The National Fuel gas code  
requires that it be at a minimum of 12" above  
grade. Depending on local conditions, the installer  
should ensure that it remains at least 12" above the  
maximum potential snow line. Seek local  
The appropriate side wall vent hood must be used,  
and is listed in the installation and operation manual.  
The terminal provides a means of installing the vent  
piping through the building wall, and must be located in  
accordance with ANSI Z223.1/NFPA 54 and applicable  
local codes. In Canada, the installation must be in  
accordance with CSA B149.1 or .2 and local applicable  
codes. Consider the following when installing the  
terminal:  
municipalities and their codes for appropriate  
installation techniques.  
WARNING: It is critical that the combustion air  
intake and the vent terminals remain at least 12"  
above the maximum potential snow line. If either  
the vent terminal or the air terminal is blocked by  
snow, there may be potential for the unit to  
produce excess carbon monoxide and or  
recirculate flue gasses into the building/dwelling.  
Personal injury or DEATH may occur. Natural  
snowfall, drifting, and banking should all be taken  
into account when locating the terminals in a  
potentialsnowenvironment.  
1. Figure 4 shows the requirements for mechanical  
vent terminal clearances for the U.S. and Canada.  
2. Vent terminals for condensing appliances or  
appliances with condensing vents are not permitted  
to terminate above a public walkway, or over an  
area where condensate or vapor could create a  
nuisance or hazard.  
3. Locate the vent terminal so that vent gases cannot  
be drawn into air conditioning system inlets.  
4. Locate the vent terminal so that vent gases cannot  
enter the building through doors, windows, gravity  
inlets or other openings. When possible, locations  
under windows or near doors should be avoided.  
5. Locate the vent terminal so that it cannot be  
blocked by snow. The National Fuel gas code  
requires that it be at a minimum of 12" above  
grade. In a location that has the possibility of snow  
accumulation, it is critical the installer places the  
vent at least 12" higher than the maximum potential  
snow line. Seek local municipalities and their  
codes for appropriate installation techniques.  
6. Locate the terminal so the vent exhaust does not settle  
4. If the Brute Deluxe is side-wall vented to the same  
wall, locate the vent terminal at least 3 feet (0.9m)  
horizontally from the combustion air terminal, and  
locate the vent terminal at least 1 foot (0.3m) above  
the combustion air terminal (see Figure 4).  
2.3.3 VerticalVentTerminal  
When the unit is vented through the roof, the vent  
must extend at least 3 feet (0.9m) above the point at  
which it penetrates the roof. It must extend at least 2 feet  
(0.6m) higher than any portion of a building within a  
horizontal distance of 10 feet (3.0m), and high enough  
above the roof line to prevent blockage from snow.  
When the combustion air is taken from the roof, the  
combustion air must terminate at least 12" (30cm) below  
the vent terminal (see Figure 3). Seek local  
TERM  
DESCRIPTION  
Pipe  
Must comply with UL Standard 1738  
such as Type 29-4C Stainless Steel  
(either insulated or non-insulated).  
Joint  
Sealing  
Follow vent manufacturer’s instructions  
municipalities and their codes for appropriate  
installation techniques.  
Table 5. Required Horizontal Venting Material.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 10  
U.S. Installations (see note 1)  
Canadian Installations (see note 2)  
A= Clearance above grade, veranda, porch,  
12 inches (30 cm)  
12 inches (30 cm)  
36 inches (91 cm)  
See note 5  
deck, or balcony  
B= Clearance to window or door that may be  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
See note 4  
opened  
C= Clearance to permanently closed window  
D= Vertical clearance to ventilated soffit located  
above the terminal within a horizontal  
distance of 2 feet (61cm) from the center  
line of the terminal  
See note 4  
See note 5  
E= Clearance to unventilated soffit  
F= Clearance to outside corner  
G= Clearance to inside corner  
See note 4  
See note 4  
See note 4  
See note 5  
See note 5  
See note 5  
H= Clearance to each side of center line  
3 feet (91 cm) within a height 15 feet above  
the meter/regulator assembly  
3 feet (91 cm)  
extended above meter/regulator assembly  
See note 4  
See note 4  
I= Clearance to service regulator vent outlet  
J= Clearance to nonmechanical air supply inlet  
to building or the combustion air inlet to  
any other appliance  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
3 feet (91 cm) above if within 10 feet (3 m)  
horizontally  
36 inches (91 cm)  
6 feet (1.83 m)  
K= Clearance to a mechanical air supply inlet  
Vent termination not allowed in this location  
for category IV appliances. A vent shall not  
terminate directly above a sidewalk or paved  
driveway that is located between two single  
Vent termination not allowed in this location  
L= Clearance above paved sidewalk or paved for category IV appliances. For Category III  
driveway located on public property  
appliances, vent must terminate at least 7  
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.  
For Category III appliances that do not violate  
the previous condition, vent must terminate  
at least 7 feet (2.13m) above the sidewalk or  
driveway.  
M= Clearance under veranda, porch, deck,  
See note 4  
12 inches (30 cm) (see note 3)  
or balcony  
Notes:  
1. In accordance with the currentANSI Z223.1 / NFPA 54 National Fuel Gas Code.  
2. In accordance with the current CSA-B149.1 Installation Codes.  
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.  
4. For clearances not specified inANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of  
the gas supplier.  
5. For clearances not specified in CSA-B149.1, clearance is in accordance with local installation codes and the requirements of the gas supplier.  
Figure 4. Combustion Air and Vent Through Side Wall.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 11  
of a ProductApproved side wall horizontally vented gas fueled  
From Massachusetts Rules and Regulations 248 CMR 5.08:  
(a) For all side wall horizontally vented gas fueled equipment  
installed in every dwelling, building or structure used in  
whole or inpart for residential purposes, including those  
owned or operated by the Commonwealth and where the  
side wall exhaust vent termination is less than seven (7)  
feet above finished grade in the area of the venting,  
including but not limited to decks and porches, the  
following requirements shall be satisfied:  
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.  
At the time of installation of the side wall horizontal vented gas  
fueled equipment, the installing plumber or gasfitter shall  
observe that a hard-wired carbon monoxide detector with an  
alarm and battery back-up is installed on the floor level where  
the gas equipment is to be installed. In addition, the installing  
plumber or gasfitter shall observe that a battery operated or  
hard-wired carbon monoxide detector with an alarm is installed  
on each additional level of the dwelling, building or structure  
served by the side wall horizontal vented gas fueled equipment.  
It shall be the responsibility of the property owner to secure the  
services of qualified licensed professionals for the installation  
of hard-wired carbon monoxide detectors.  
equipment does not provide the parts for venting the fuel gases,  
but identifies "special venting systems", the following require-  
ments shall be satisfied by the manufacturer:  
1. The identification of each "special venting system" shall include  
either the listing of the website, phone number or  
manufacturer's address where the venting system installation  
instructions can be obtained; and  
2. The "special venting systems" shall be ProductApproved by the  
Board, and the instructions provided with that system shall  
include a parts list and detailed installation instructions.  
(e) A copy of all installation instructions for the Product  
Approved side wall horizontally vented gas fueled  
equipment, and all the venting instructions, parts lists,  
and/or design instructions for the venting system shall  
remain with the appliance or equipment at the completion  
of the installation.  
Manufacturers' websites where venting system installation  
instructions may be obtained is located on the website at:  
2.3.4 VerticalCombustionAirTerminal  
When combustion air is taken from the roof, a  
field-supplied rain cap or an elbow arrangement must be  
used to prevent entry of rain water (see Figure 3). The  
opening on the end of the terminal must be at least 12"  
(30cm) above the point at which it penetrates the roof,  
and high enough above the roof line to prevent blockage  
from snow. When the vent terminates on the roof, the  
combustion air must terminate at least 12" (30cm) below  
the vent terminal.  
a. In the event that the side wall horizontally vented gas fueled  
equipment is installed in a crawl space or an attic, the hard-  
wired carbon monoxide detector with alarm and battery back-  
up may be installed on the next adjacent floor level.  
b. In the event that the requirements of this subdivision cannot  
be met at the time of completion of installation, the owner shall  
have a period of thirty (30) days to comply with the above  
requirements; provided, however, that during said thirty (30)  
day period, a battery operated carbon monoxide detector with  
an alarm shall be installed.  
2. APPROVED CARBON MONOXIDE DETECTORS.Each  
carbon monoxide detector as required in accordance with the  
above provisions shall comply with NFPA720 and beANSI/UL  
2034 listed and IAS certified.  
2.4 Common Vent Test — Boilers  
When an existing boiler is removed from a common  
venting system, the common venting system is likely to  
be too large for proper venting of the appliances  
remaining connected to it.  
At the time of removal of an existing boiler, the  
following steps shall be followed with each appliance  
remaining connected to the common venting system placed  
in operation, while the other appliances remaining con-  
nected to the common venting system are not in operation.  
1. Seal any unused openings in the common venting  
system.  
3. SIGNAGE.A metal or plastic identification plate shall be  
permanently mounted to the exterior of the building at a  
minimum height of eight (8) feet above grade directly in line  
with the exhaust vent terminal for the horizontally vented gas  
fueled heating appliance or equipment. The sign shall read, in  
print size no less than one-half (½) inch in size, "GAS VENT  
DIRECTLYBELOW. KEEPCLEAR OFALLOBSTRUCTIONS".  
4. INSPECTION. The state or local gas inspector of the side wall  
horizontally vented gas fueled equipment shall not approve the  
installation unless, upon inspection, the inspector observes  
carbon monoxide detectors and signage installed in accor-  
dance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.  
(b) EXEMPTIONS: The following equipment is exempt from  
248 CMR 5.08(2)(a) 1 through 4:  
1. The equipment listed in Chapter 10 entitled "Equipment Not  
Required To Be Vented" in the most current edition of NFPA 54  
as adopted by the Board; and  
2. ProductApproved side wall horizontal vented gas fueled  
equipment installed in a room or structure separate from the  
dwelling, building or structure used in whole or in part for  
residential purposes.  
2. Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion and other  
deficiencies which could cause an unsafe condition.  
3. Insofar as it is practical, close all building doors  
and windows and all doors between the space in  
which the appliances remaining connected to the  
common venting system are located and other  
spaces of the building. Turn on clothes dryers and  
any appliance not connected to the common venting  
system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will operate  
at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT  
VENTING SYSTEM PROVIDED. When the manufacturer of  
ProductApproved side wall horizontally vented gas equipment  
provides a venting system design or venting system compo-  
nents with the equipment, the instructions provided by the  
manufacturer for installation of the equipment and the venting  
system shall include:  
1. Detailed instructions for the installation of the venting system  
design or the venting system components; and  
4. Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat  
so appliance will operate continuously.  
2. A complete parts list for the venting system design or venting  
system.  
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT  
VENTING SYSTEMNOT PROVIDED. When the manufacturer  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 12  
5. Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use the  
flame of a match or candle, or smoke from a  
cigarette, cigar or pipe.  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above,  
return doors, windows, exhaust fans, fireplace  
dampers and any other gas burning appliance to  
their previous conditions of use.  
7. Any improper operation of the common venting  
system should be corrected so that the installation  
conforms to the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and/or CSA B149.1, Installation  
Codes. When resizing any portion of the common  
venting system, the common venting system should  
be resized to approach the minimum size as  
determined using the appropriate tables in Part II of  
the National Fuel Gas Code, ANSI Z223.1/NFPA  
54 and/or CSA B149.1, Installation Codes.  
3.1 Gas Supply and Piping  
Gas piping should be supported by suitable  
hangers or floor stands, not by the appliance.  
Brute Deluxe’s gas train allows the user to pipe the  
gas from either the right side or the left side of the unit.  
As shipped, the right side of the gas train is capped off,  
and there is a manual valve on the left side. If desired,  
the manual valve on the left side of the gas train may be  
moved to the right side, and the cap on the right side  
may be moved to the left.  
Review the following instructions before  
proceeding with the installation.  
1. Verify that the appliance is fitted for the proper  
type of gas by checking the rating plate. Brute  
DISTANCE FROM GAS METER  
SIZE  
OR LAST STAGE REGULATOR  
AND  
GAS TYPE  
0-100'  
100-200'  
200-300'  
500 natural  
1½"  
1"  
2"  
2"  
1½"  
500 propane  
1½"  
750 natural  
2"  
2"  
2½"  
2"  
2.5 Vent Terminals for Outdoor Units  
For outdoor applications, the vent and combustion  
air openings must be covered with proper terminals to  
prevent rain, snow and other objects from falling into the  
Brute Deluxe.  
If local codes allow, outdoor installations may use  
1' of appropriately sized galvanized single wall or B-  
Vent and a rain cap for exhaust vent termination in the  
default configuration (venting out of the top). Note that  
some local codes may require a higher vertical vent  
height, extending above any perimeter fencing, etc. In  
installations where the appearance of the vent is  
objectionable, the low profile vent terminals in Table 6  
may be used.  
Combustion air inlets consist of appropriately sized  
galvanized pipe and elbows to allow the open end to  
face down aside the boiler. This is available as a  
Commercial Kit from the manufacturer.  
Part numbers for the low profile terminals to cover the  
vent and combustion air openings are shown in Table 6.  
750 propane  
1½"  
1½"  
1000 natural  
2"  
1½"  
2½"  
2"  
2½"  
2"  
2½"  
2"  
3"  
2½"  
3"  
2½"  
1000 propane  
1250 natural  
1250 propane  
1500 natural  
2½"  
2"  
2½"  
2"  
3"  
2½"  
3"  
2½"  
3"  
2½"  
3"  
2½"  
1500 propane  
1750 natural  
1750 propane  
2000 natural  
3"  
2½"  
3"  
2½"  
3½"  
3"  
2000 propane  
Metric Equivalent  
DISTANCE FROM GAS METER  
OR LAST STAGE REGULATOR  
SIZE  
AND  
GAS TYPE  
0-31m  
31-61m  
61-91m  
500 natural  
3.8cm  
2.5cm  
5.1cm  
3.8cm  
5.1cm  
3.8cm  
500 propane  
750 natural  
5.1cm  
3.8cm  
5.1cm  
3.8cm  
6.4cm  
5.1cm  
750 propane  
1000 natural  
5.1cm  
3.8cm  
6.4cm  
5.1cm  
7.6cm  
6.4cm  
1000 propane  
SECTION 3.  
1250 natural  
6.4cm  
5.1cm  
6.4cm  
5.1cm  
7.6cm  
6.4cm  
1250 propane  
Gas Supply and Piping  
1500 natural  
6.4cm  
5.1cm  
6.4cm  
5.1cm  
7.6cm  
6.4cm  
7.6cm  
6.4cm  
7.6cm  
6.4cm  
7.6cm  
6.4cm  
1500 propane  
OUTDOOR  
COMBUSTION  
AIRTERMINAL  
OUTDOOR VENT  
1750 natural  
SIZE  
TERMINAL  
1750 propane  
500  
750  
20254703  
20254705  
20254705  
D2007700  
D2007700  
D2007800  
D2007800  
D2007900  
D2007900  
D2008000  
D2008000  
D2008000  
D2008000  
D2008200  
2000 natural  
7.6cm  
6.4cm  
7.6cm  
6.4cm  
8.9cm  
7.6cm  
2000 propane  
1000  
1250  
1500  
1750  
2000  
NOTES: 1. These figures are based on 1/2" (0.12kPa) water column  
pressuredrop.  
2. Check supply pressure and local code requirements  
before proceeding with work.  
3. Pipe fittings must be considered when determining gas  
pipe sizing.  
Table 7. Gas Piping Sizes.  
Table 6. Vent Terminals for Outdoor Units.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 13  
Deluxe appliances are equipped to operate at  
elevations up to 10,000 feet (3050m). Brute  
Deluxe appliances may be adjusted to operate  
properly at altitudes above 2500 feet (see Section  
6.6.2) and the input will be reduced if the heating  
value of the gas supply is below sea level values.  
2. The maximum inlet gas pressure must not exceed  
13" W.C (3.2kPa). The minimum inlet gas pressure  
is 5" W.C. (1.2kPa).  
NOTE: The Brute Deluxe appliance and all other gas  
appliances sharing the gas supply line must be firing at  
maximum capacity to properly measure the inlet supply  
pressure. The pressure can be measured at the supply  
pressure port on the gas valve. Low gas pressure could  
be an indication of an undersized gas meter, undersized  
gas supply lines and/or an obstructed gas supply line.  
3. Refer to Table 7, size supply.  
SECTION 4A.  
Water Connections — Boiler  
4. Run gas supply line in accordance with all  
applicable codes.  
5. Locate and install manual shutoff valves in  
accordance with state and local requirements.  
6. A sediment trap must be provided upstream of the  
gas controls.  
4A.1 Heating System Piping:  
Hot Supply Connections — Boiler  
NOTE: This appliance must be installed in a closed  
pressure system with a minimum of 12 psi (82.7kPa)  
static pressure at the boiler.  
7. All threaded joints should be coated with piping  
compound resistant to action of liquefied  
petroleum gas.  
8. The appliance and its individual shutoff valve must  
be disconnected from the gas supply piping during  
any pressure testing of that system at test pressures  
in excess of 1/2 PSIG (3.45kpa).  
9. The unit must be isolated from the gas supply  
system by closing its individual manual shutoff  
valve during any pressure testing of the gas supply  
piping system at test pressures equal to or less than  
1/2 PSIG (3.45kpa).  
10. The appliance and its gas connection must be leak  
tested before placing it in operation.  
11. Purge all air from gas lines.  
Hot water piping should be supported by suitable  
hangers or floor stands. Do not support piping with this  
appliance. Due to expansion and contraction of copper  
pipe, consideration should be given to the type of  
hangers used. Rigid hangers may transmit noise through  
the system resulting from the piping sliding in the  
hangers. It is recommended that padding be used when  
rigid hangers are installed. Maintain 1" clearance to  
combustibles for hot water pipes.  
Pipe the discharge of the relief valve (full size) to a  
drain or in a manner to prevent injury in the event of  
pressure relief. Install an air purger, an air vent, a  
20°F  
H/L  
25°F  
flow  
30°F  
H/L  
35°F  
flow  
WARNING  
Do not use open flame to check for leaks. An open  
SIZE  
flow  
gpm  
H/L  
flow  
H/L  
feet  
feet  
1.7  
3.3  
5.0  
8.1  
gpm  
34  
51  
68  
85  
feet  
gpm  
feet  
0.9  
1.7  
3.1  
4.7  
5.5  
8.4  
gpm  
24  
36  
49  
61  
73  
85  
flame could lead to explosion, which could result in  
property damage, serious injury or death.  
500  
750  
43  
64  
85  
1.1  
2.3  
3.6  
6.1  
28  
43  
57  
71  
85  
0.7  
1.2  
2.2  
3.4  
4.2  
5.8  
8.3  
1000  
1250  
1500  
1750  
2000  
106  
128 10.0 102 7.2  
N/R N/R 119 10.5 99  
N/R N/R 136 12.5 113 10.4 97  
Metric Equivalent  
11°C  
14°C  
flow  
lpm  
17°C  
H/L  
19°C  
flow  
lpm  
SIZE  
flow  
lpm  
H/L  
m
H/L  
m
flow  
lpm  
H/L  
m
m
500  
750  
1000  
1250  
1500  
1750  
2000  
161  
241  
321  
401  
483  
0.5  
1.0  
1.5  
2.5  
3.0  
129 0.3 107 0.3  
92  
0.2  
193 0.7 161 0.5 138 0.4  
257 1.1 214 0.9 184 0.7  
322 1.9 269 1.4 231 1.0  
386 2.2 322 1.7 276 1.3  
N/R N/R 451 3.2 375 2.6 322 1.8  
N/R N/R 515 3.8 429 3.2 368 2.5  
Notes: gpm = gallons per minute, lpm = liters per minute,  
H/L = headloss, ft = headloss in feet, m = headloss in meters.  
Maximum temperature rise is 35°F (19°C), as shown. Headloss is  
forboiler’sheatexchangeronly. N/R=notrecommended.  
Figure 5. Typical Gas Train Configuration.  
Table 8. Water Flow Requirements — BMT2H.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 14  
diaphragm-type expansion tank, and a hydronic flow  
check in the system supply loop. Minimum fill pressure  
must be 12psig (82.7kPa). Install shutoff valves where  
required by code.  
Suggested piping diagrams are shown (see Figures  
6 through 14). These diagrams are meant only as a  
guide. Components required by local codes must be  
properly installed.  
precautions are made for freeze protection. A non toxic,  
heating system, anti-freeze may be added to the hydronic  
system provided that the concentration does not exceed  
50% and the anti freeze contains an anti foamant. When  
a 50/50 mixture is used, increase the water flow  
requirements by 15%, and increase the headloss  
requirements by 20%.  
Power outage, interruption of gas supply, failure of  
system components, activation of safety devices, etc., may  
prevent a boiler from firing. Any time a boiler is subjected  
to freezing conditions, and the boiler is not able to fire, and/  
or the water is not able to circulate, there is a risk of  
freezing in the boiler or in the pipes in the system. When  
water freezes, it expands. This can result in bursting of  
pipes in the system, or damage to the boiler, which could  
result in leaking or flooding conditions.  
IMPORTANT NOTES: Different glycol products may  
provide varying degrees of protection. Glycol products  
must be maintained properly in a heating system, or they  
may become ineffective. Consult the glycol specifications,  
or the glycol manufacturer, for information about specific  
products, maintenance of solutions, and set up according  
to your particular conditions.  
4A.2 Cold Water Make-Up — Boiler  
1. Connect the cold water supply to the inlet  
connection of an automatic fill valve.  
2. Install a suitable back flow preventer between the  
automatic fill valve and the cold water supply.  
3. Install shut off valves where required.  
NOTE: The boiler, when used in connection with a  
refrigeration system, must be installed so the chilled  
medium is piped in parallel with the boiler with  
appropriate valves to prevent the chilled medium from  
entering the boiler.  
The boiler piping system of a hot water heating  
boiler connected to heating coils located in air handling  
appliances where they may be exposed to refrigerated  
air circulation must be equipped with flow control  
valves or other automatic means to prevent gravity  
circulation of the boiler water during the cooling cycle.  
A boiler installed above radiation level, or as  
required by the authority having jurisdiction, must be  
provided with a low water cutoff device either as a part  
of the boiler or at the time of boiler installation.  
SECTION 4B.  
Water Connections —  
Water Heater  
4B.1 Water System Piping —  
Water Heater  
Hot water piping should be supported by suitable  
hangers or floor stands. Do not support piping with this  
appliance. Due to expansion and contraction of copper  
pipe, consideration should be given to the type of  
hangers used. Rigid hangers may transmit noise through  
the system resulting from the piping sliding in the  
hangers. It is recommended that padding be used when  
rigid hangers are installed.  
4A.3 Water Flow Requirements — Boiler  
A hydronic heating (closed loop) application re-  
circulates the same fluid in the piping system. As a  
result, no new minerals or oxygen is introduced into the  
system. To ensure a proper operating temperature  
leading to long boiler life, a flow rate has been  
established based on the fluid temperature rise for this  
specific size boiler.  
The Brute Deluxe can be used with several different  
types of readily available storage tanks. A pump draws  
water from the storage tank and pumps the water through  
the heater and back into the tank. Pump-mounted units have  
a circulating pump built into the water heater. The pumps  
used are sized for the headloss through the heater, plus 30  
feet (9.1m) of full-sized piping (same size as boiler outlet)  
and a normal number of fittings. Pumps used on pump-  
mounted unit are sized for soft/normal or hard water, so  
make sure a pump-mounted unit matches the water quality  
of the installation.  
Pump-mounted boilers can be ordered for use in  
primary secondary piping systems. The pumps used are  
sized for the headloss through the heater, plus 30 feet  
(9.1m) of full-sized piping (same size as boiler outlet)  
and a normal number of fittings.  
Table 8 specifies water flow rates for boilers,  
which will enable the user to size a pump. The headloss  
shown is for the heater only, and the user will need to  
add the headloss of the system piping to properly size  
the pump.  
The minimum inlet water temperature for the Brute  
Deluxe is 120°F (49°C) to avoid condensing on the  
copper coils.  
Pipe the outlet from the heater’s relief valve such  
that any discharge from the relief valve will be  
conducted to a suitable place for disposal when relief  
occurs. Do not reduce line size or install any valves in  
this line. The line must be installed to allow complete  
drainage of both the valve and the line.  
4A.4 Freeze Protection — Boiler  
Boiler installations are not recommended in areas  
where the danger of freezing exists unless proper  
Suggested piping diagrams are shown in Figures 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 15  
through 13. These diagrams are meant only as a guide.  
Components required by local codes must be properly  
installed.  
NOTE: These systems are not allowed in the  
Commonwealth of Massachusetts.  
Piping and components connected to this water  
heater for the space heating application shall be suitable  
for use with potable water.  
Toxic chemicals, such as used for boiler treatment,  
shall not be introduced into the potable water used for  
space heating.  
This water heater when used to supply potable  
water shall not be connected to any heating system or  
component(s) previously used with a non-potable water  
heating appliance.  
When the system requires water for heating at  
temperatures higher than required for other uses, an  
anti-scald mixing or tempering valve shall be  
installed to temper the water for those uses in order  
to reduce scald hazard potential.  
The minimum inlet water temperature for the Brute  
Deluxe is 120°F (49°C) to avoid condensing on the  
copper coils.  
4B.2 Hot Water Supply Piping —  
Water Heater  
Follow the tank manufacturer’s guidelines for  
completion of the hot water system connections.  
NOTE: A listed temperature and pressure relief valve  
listed as complying with the Standard for Relief  
Valves and Automatic Gas Shutoff Devices for Hot  
Water Supply Systems (ANSI Z21.22 / CSA 4.4) of  
suitable discharge capacity must be installed in the  
separate storage tank system.  
If the Brute Deluxe water heater is installed in a  
closed water supply system, such as one having a  
backflow preventer in the cold water supply line, the  
relief valve may discharge periodically, due to thermal  
expansion. Means (such as a properly-sized expansion  
tank) shall be provided to control thermal expansion.  
Contact the water supplier or local plumbing inspector  
on how to control this situation.  
4B.5 Freeze Protection – Water Heater  
Although Brute Deluxe water heaters are design-  
certified for outdoor installations, such installations are  
not recommended in areas subject to freezing  
temperatures, unless proper precautions are taken.  
Power outage, interruption of gas supply, failure of  
system components, activation of safety devices, etc., may  
prevent a heater from firing. Any time a heater is sub-  
jected to freezing conditions, and the heater is not able  
to fire, and/or the water is not able to circulate, there is  
a risk of freezing in the heater or in the pipes in the  
system. When water freezes, it expands. This can result in  
bursting of pipes in the system, or damage to the heater,  
which could result in leaking or flooding conditions.  
Contact the local factory representative or for  
additionalinformation.  
4B.3 Water Flow Requirements —  
Water Heater  
In a water heating application (an open system),  
new water is constantly being introduced. With the new  
water comes a fresh supply of minerals that can be  
deposited on the unit’s heat exchanger. This is  
commonly known as scaling. The amount of minerals  
will depend upon the hardness of the water. Water can  
also be aggressive, and can erode metals, including  
copper, if the water is moved too quickly. The water  
flow requirements for the Brute Deluxe water heater are  
based upon the hardness of the water. The water flow is  
kept high enough to prevent scaling, but low enough to  
prevent tube erosion. For extremely soft or hard water,  
cupro-nickel tubes are available. Contact a  
Representative if you have questions or concerns about  
water quality.  
SECTION 5.  
Electrical Connections  
WARNING  
The appliance must be electrically grounded in  
accordance with the requirements of the authority  
having jurisdiction or, in the absence of such  
requirements, with the latest edition of the National  
Electrical Code, ANSI/NFPA 70, in the U.S. and with  
latest edition of CSA C22.1 Canadian Electrical Code,  
Part 1, in Canada. Do not rely on the gas or water  
piping to ground the metal parts of the boiler. Plastic  
pipe or dielectric unions may isolate the boiler  
electrically. Service and maintenance personnel, who  
work on or around the boiler, may be standing on wet  
floors and could be electrocuted by an ungrounded  
Pump-mounted water heaters can be ordered with  
standard pumps for soft or normal water or with pumps  
for hard water. The pumps used are sized for the  
headloss through the heater, plus 30 feet (9.1m) of full-  
sized piping (same size as heater outlet) and a normal  
number of fittings.  
Table 9 specifies water flow rates for water  
heaters, which will enable the user to size a pump. The  
headloss shown is for the heater only, and the user will  
need to add the headloss of the piping system to  
properly size the pump.  
boiler.  
Single pole switches, including those of safety  
controls and protective devices must not be wired in a  
grounded line.  
4B.4 Combined Water Heating (potable)  
and Space Heating — Water Heater  
All electrical connections are made in the field  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 16  
Figure 6. Hydronic Piping — Multiple Boilers, Primary Secondary System.  
Figure 7. Hydronic Piping — Multiple Boilers, Low Temperature System.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 17  
Figure 8. Hydronic Piping — One Boiler, Multi-Temperature System.  
Figure 9. Hydronic Piping - Primary-Secondary, Reverse-Return.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 18  
Figure 10. Hydronic Piping - Primary-Secondary, Reverse-Return, Low Temperature.  
Figure 11. Water Heater Piping — One Heater, One Tank.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 19  
Figure 12. Water Heater Piping — Multiple Heaters, One Tank.  
Figure 13. Water Heater Piping — One Heater, Multiple Tanks.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 20  
Figure 14. Water Heater Piping — Multiple Heaters, Multiple Tanks.  
gpm  
N
ft  
Temp Rise °F  
lpm  
N
m
N
Temp Rise °C  
Size  
500  
750  
1000  
1250  
1500  
1750  
2000  
S
H
S
N
H
S
N
H
9
S
H
S
H
S
10  
16 10  
N
7
H
5
8
45  
45  
45  
68  
68  
68  
68  
68  
68  
68  
68  
68  
90  
90  
90  
90  
90  
90  
1.8  
2.1  
2.3  
3.8  
3.9  
4.0  
2.3  
3.0  
3.6  
3.8  
3.9  
4.0  
3.5  
6.0  
6.1  
6.3  
6.5  
6.7  
19 13  
170 257 341  
170 257 341  
170 257 341  
257 257 341  
257 257 341  
257 257 341  
424 424 424  
0.5 0.7 1.1  
0.6 0.9 1.8  
0.6 1.1 1.9  
1.2 1.2 1.9  
1.2 1.2 2.0  
1.2 1.2 2.0  
3.0 3.0 3.0  
28 19 14  
38 25 19  
31 31 24  
38 38 28  
44 44 33  
30 30 30  
21 14 10  
17 17 13  
21 21 16  
24 24 18  
17 17 17  
112 112 112  
10.0 10.0 10.0  
NOTES: S = soft water (1 to 7.5 grains hardness).  
N = normal water (7.6 to 17 grains hardness).  
H = hard water (more than 17 grains hardness).  
gpm = gallons per minute; lpm = liters per minute; ft = headloss in feet; m = headloss in meters.  
Headloss is for heater's heat exchanger only.  
Table 9. Water Flow Requirements — BMT2V.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 21  
wiring terminal strip, which is located at the right side of  
the appliance.  
NOTE: All internal electrical components have been pre-  
wired. No attempt should be made to connect electrical  
wires to any other location except the wiring box.  
NOTE: This pump control is equipped with a delay on  
break typically set for 3 minutes, but can be adjusted  
between 0.1 and 10 minutes.  
Field Interlocks: To install other field-wired  
devices to interlock with the boiler (tank stats, louver  
switches, flow switches, etc.), remove the jumper  
between terminals 3 and 4 and wire the device in series  
across these terminals. These terminals are located in  
the upper main control panel.  
External Control Wiring: These terminals are  
located in the upper main control panel (see Section 5.3).  
Optional Alarm Contacts: As an option, the Brute  
Deluxe is available with an alarm kit. This alarm kit  
contains a dry contact for up to 120V which is available  
within the 120V field wiring panel. These terminals will be  
clearly labeled "Alarm" and are rated up to 10 amps.  
5.1 Main Power  
The main power requires a 120-volt fused supply that  
is connected to the “main power” terminal strip. The over  
current protection must be sized as specified ( Figure 15).  
The BMT2 pump (pump-mount units) requires a  
separate (additional) 120-volt fused supply connected to  
the pump terminal strip (also specified in Figure 15).  
5.2 Field Wiring  
Main Power: The main 120V field wiring panel is  
located on the right side of the unit, under the main  
power switch. Within this panel are the terminals for  
incoming 120V single-phase power clearly labeled on  
the right-hand side as “120V (L1)”, “NEUTRAL” and  
“GROUND”.  
Pump Power: Also located on the 120V field  
wiring panel is the pump terminal strip. This strip is  
located on the left side (denoted as “120V L2”, “N2  
(Pump mounted)” and “GROUND 2 (Pump Mounted)”).  
External Pumps: External Pump: All non-pump-  
mounted BMT2 units have an internal (dry) contact rated  
for 20Amps. A field-supplied pump can be connected  
directly to this contact if it does not draw more than 20  
Amps. If more current is required, a separate pump  
contactor must be installed.  
To utilize this internal pump contact, supply 120  
volt single-phase power to the terminal marked “120V  
(L2)” and supply the pump using the terminal marked  
“L2 LOAD (EXT. PUMP)”.  
SIZE  
500  
750  
1000  
1250  
1500  
1750  
2000  
PUMP CIRCUIT MAIN CIRCUIT  
15A  
15A  
15A  
15A  
15A  
15A  
20A  
15A  
15A  
20A  
20A  
20A  
20A  
20A  
Figure 15. Field Wiring.  
Figure 16. Brute Deluxe (500–750) Wiring Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 22  
Figure 17. Brute Deluxe (1000) Wiring Diagram.  
Figure 18. Brute Deluxe (1250–2000) Wiring Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 23  
Figure 19. Brute Deluxe (500–750) Connection Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 24  
Figure 20. Brute Deluxe (1000) Connection Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 25  
Figure 21. Brute Deluxe (1250–2000) Connection Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 26  
When pressure circuit has been satisfied, proving  
combustion air and adequate water flow, the hot surface  
igniter will initiate. The ignition control checks that the  
igniter current reached a predetermined level then will  
dwell momentarily. When dwell time is complete the gas  
valve will open.  
5.3 External Staging Control Wiring  
WARNING  
Improper field wiring may result in fire or explosion  
which can cause property damage, severe injury, or  
death. Make only wiring connections which are in  
accordance with the Installation and Operation manual.  
After a 4-second trial for ignition, the igniter  
switches off. Unless a flame is detected by the flame  
sensor (a minimum value of 0.4µA), the gas valve will  
close and The ignition module will either attempt  
ignition again (up to three times) or will lock out if the  
optional lockout ignition module is used.  
AVERTISSEMENT  
Un câblage incorrect lors de l’installation peut causer  
un incendie ou une explosion pouvant entraîner des  
dommages matériels, de graves blessures ou la mort.  
Ne faire seulement que les connexions conformes au  
Manueld’installationetd’exploitation.  
If flame is sensed, the burner will continue to fire  
as long as there is a call for heat and adequate flame  
signal. If there is a subsequent loss of flame signal, the  
burner will attempt re-ignition up to three times (only  
once if optional lockout ignition is used.) When the call  
for heat is satisfied, the gas valves(s) close and the  
blowers continues to run for 30 seconds.  
If controlling the stages of the BMT2 from an  
external source (multiple boiler control, BAS, etc.), wire  
Stage 1 to the terminals marked "Input Stage 1" and  
"Stage 1", and wire Stage 2 to the terminals marked  
"Input Stage 2" and "Stage 2". The "Local/Remote"  
selector switch above the terminal strip must be placed  
in the "Remote" position for the external controller to  
manage the staging.  
The pump will continue to run for 0.1 to 10  
minutes, depending on what the pump time delay has  
been set to. Brute Deluxe sizes 1,000-2,000 have two  
ignition controls that control the individual stages. If one  
ignition control should fail for any reason, the remaining  
module can operate its burners independently. (Note that  
if a single blower is disabled on units 1250-2000, the  
other fan will continue to operate and safely allow the  
boiler to run with a single stage.)  
If it is intended to use the BMT2's on-board 2-  
stage controller, no extra wiring is necessary. Ensure the  
Local/Remote selector switch is in the "Local" position.  
SECTION 6.  
Operating Instructions  
6.2 Filling the System  
1. Ensure the system is fully connected. Close all  
bleeding devices and open make-up water valve.  
Allow system to fill slowly.  
6.1 Sequence of Operation  
Upon initiation of the main power switch, 120V  
will be sent to multiple items. Among these are the open  
contact fan relays, open contact ignitor relay, open  
contact pump relay, ignition control module(s) and open  
contact lock out indicators (the optional alarm package  
uses this). In addition to these, 24V will travel through  
the optional gas pressure switches and optional auto  
reset high limit. 24V will then travel through the block  
flue switch and the manual reset high limit to the  
temperature controller.  
2. If make-up water pump is employed, adjust  
pressure switch on pumping system to provide a  
minimum of 12 psi (81.8 kPa) at the highest point  
in the heating loop.  
3. If a water pressure regulator is provided on the  
make-up water line, adjust the pressure regulator to  
provide at least 12 psi (81.8 kPa) at the highest  
point in the heating loop.  
4. Open bleeding devices on all radiation units at the  
high points in the piping throughout the system,  
unless automatic air bleeders are provided at such  
points.  
5. Run system circulating pump for a minimum of 30  
minutes with the boiler shut off.  
Upon a call for heat from the BMT2’s internal  
control or an external staging control, 24V travels  
through the field interlock (if closed) and then to the  
ignition control(s) “T-stat” terminal (500-750 models are  
equipped with one ignition control and models 1000-  
2000 are equipped with two ignition controls).  
When “T-stat” on an ignition control is energized,  
its fan will energize and the ignition control will seek  
signal from the “pressure circuit”. The pressure circuits  
consist of the flow switch and proof of fan.  
Sizes 500-1000 calls for fan, fan prove, initiate  
pump then prove flow, after which “pressure circuit” has  
been satisfied.  
Sizes 1250-2000 calls for pump, proof of flow,  
initiate fan then prove fan, after which “pressure circuit”  
has been satisfied. The fan prove will only occur for the  
active stage that has been called.  
6. Open all strainers in the circulating system, check  
flow switch operation, and check for debris. If debris  
is present, clean out to ensure proper circulation.  
7. Recheck all air bleeders as described in Step 4.  
8. Check liquid level in expansion tank. With the  
system full of water and under normal operating  
pressure, the level of water in the expansion tank  
should not exceed ¼ of the total, with the balance  
filled with air.  
9. Start up system according to the procedure in this  
manual. Operate the entire system, including the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 27  
pump, boiler, and radiation units for one (1) hour.  
10. Recheck the water level in the expansion tank. If  
the water level exceeds ¼ of the volume of the  
expansion tank, open the tank drain, and drain to  
that level.  
Because the Brute Deluxe controller senses inlet  
water and the manual reset high limit senses outlet water,  
the high limit should be set 40-50°F higher than the  
controller, to avoid nuisance lockout of the manual reset  
highlimit.  
11. Shut down the entire system and vent all radiation  
units and high points in the system piping, as  
described in Step 4.  
6.4 External Boiler Operations  
If controlling the stages of the BMT2 from an  
external source (multiple boiler control, BAS, etc) the  
"Local/Remote" selector switch above the terminal strip  
must be placed in the "Remote" position. In this mode,  
the controller that is mounted on the BMT2 will no  
longer have control of the unit. The 24V from the unit  
waits at the input terminal, and the external control  
switches this 24V from the input terminal to the stage  
terminal.  
12. Close make-up water valve and check strainer in  
pressure reducing valve for sediment or debris  
from the make-up water line. Reopen make-up  
water valve.  
13. Check gauge for correct water pressure and also  
check water level in the system. If the height  
indicated above the boiler insures that water is at  
the highest point in the circulating loop, then the  
system is ready for operation.  
14. Refer to local codes and the make-up water valve  
manufacturer’s instructions as to whether the make-  
up water valve should be left open or closed.  
15. After placing the unit in operation, the ignition  
system safety shutoff device must be tested. First,  
shut off the manual gas valve, and call the unit for  
heat. After the pre-purge and ignitor heat-up time,  
the main gas terminals will be energized, attempting  
to light, for four (4) seconds, and then will de-  
energize. The unit will go into lockout mode.  
Second, turn the power off and then on again, open  
the manual gas valve and allow the unit to light.  
While the unit is operating, close the manual gas  
valve and ensure that power to the main gas valve  
has been cut.  
6.5 Limit Controls  
The manual reset high limit control is provided as  
standard equipment on all heaters. An additional  
automatic reset switch is optional.A high limit  
temperature-sensing bulb is always located in the heater  
outlet. Burners will automatically shut down whenever  
overheating occurs.  
6.6 Operating the Burner and Set Up  
6.6.1 Set Up for 0 to 2500 Feet Altitude  
The Brute Deluxe appliance utilizes a modular  
16. Within three (3) days of start-up, recheck all air  
bleeders and the expansion tank as described in  
Steps 4 and 8 above.  
Important: The installer is responsible for identifying to  
the owner/operator the location of all emergency shutoff  
devices.  
WARNING  
Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician  
to inspect the appliance  
and to replace any part of the control system and any  
gas control that may have been  
under water.  
6.3 Operating Temperature Control  
All Brute Deluxe's are equipped with a two-stage  
aquastat. To utilize this mounted controller be sure to  
have the "Local/Remote" selector switch to "Local". Set  
the controller to the desired operating set point. The  
controller has an interstage differential that can be  
adjusted from 3°F to 10°F. This allows the user to have  
some control over how stage 2 and stage 1 call for heat  
(see Figure 22).  
1
Difference between the temperatures at which the two switches  
*
make R-W. Adjustable from 3°F to 10°F (1.7°C to 5.6°C) on standard  
models, or from 3.6°F to 12°F (2.0°C to 6.7°C); 55°F to 175°F (13°C  
to 79°C) models.  
2 Two DPDT switches operate in sequence. Each switch  
differential is fixed at approximately 3°F (1.7°C) on standard models,  
or 3.6°F (2.0°C); 55°F to 175°F (13°C to 79°C) models.  
*
Figure 22. Honeywell L8008G.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 28  
design to achieve its stage-firing. The setup must be  
checked before the unit is put in operation. Problems  
such as failure to start, rough ignition, strong exhaust  
odors, etc. can be due to improper setup. Damage to the  
Brute Deluxe resulting from improper setup is not  
covered by the limited warranty.  
light the main burners for that stage, the second ignition  
control will still be active, and will be able to energize  
stage 2. This, of course, will only occur upon call for  
stage 2 and if all other safety devices confirm that the  
unit will run in a safe condition.  
1. Using this manual, make sure the installation is  
complete and fully in compliance with the  
instructions.  
6.6.2 HighAltitudeAdjustmentandSetUp  
Brute Deluxe appliances may be operated at high  
altitude (7700 ft., 2347 m) with a reduction in output of  
approximately 10%. At altitudes of less than or more than  
7700 ft. (2347 m) the appliance will perform equally as  
well, but with differing reductions in output. At elevations  
higher than 7700 ft. (2347 m) the reduction in output will  
exceed 10% and at elevations below 7700 ft. (2347 m) it  
will be less than 10%. High altitude adjustment must not be  
made on appliances operating at elevations below 2500 ft.  
(762 m).  
2. Determine that the appliance and system are filled  
with water and all air has been bled from both.  
Open all valves.  
3. Observe all warnings on the Operating Instructions  
label and turn on gas and electrical power to  
appliance.  
4. Switch on the appliance power switch located on  
the right side of the unit.  
5. The Brute Deluxe will enter the start sequence, as  
long as the unit is being called for heat. The blower  
and pump come on for pre-purge, then the ignitor  
warm-up sequence starts and after the ignitor  
warm-up is complete and all safety devices are  
verified, the gas valves open. If ignition doesn’t  
occur, check that there is proper gas supply. Wait 5  
minutes and start the unit again. During initial start  
up, air in the gas line may cause the Brute Deluxe  
to "lock out" during the first few trials for ignition.  
Depending on the ignition modules installed, the  
manual reset button on the ignition modules may  
need to be depressed to restart the Brute Deluxe.  
6. When the unit is running, the supply gas pressure  
must be checked. Inlet gas pressure must not  
exceed 13" W.C. (3.2kPa). The minimum inlet gas  
pressure is 5" W.C. (1.2kPa).  
No orifice changes are required to adjust the Brute  
Deluxe appliances for high altitude. High altitude  
adjustment is accomplished by adjustment of the gas  
valve manifold pressure and the air shutter(s). The  
required instruments used to assist in these adjustments  
are a CO2 or O2 Analyzer and a U-Tube Manometer or  
other device capable of reading a pressure of 2.5-3.0  
inches W.C. (0.62-0.75 kPa).  
Start the adjustment process by checking the CO2  
in the “as installed” condition. Adjust the air shutter(s)  
so that the CO2 is about 8% or the O2 is about 6.8% for  
appliances operating on Natural Gas. For appliances  
operating on LP Gas adjust the air shutter(s) so that the  
CO2 is about 9.2% or the O2 is about 6.8%. Appliances  
with two blowers should be adjusted so that the air  
shutters below each blower are open the same amount.  
Once the CO2 or O2 has been set, the manifold  
pressure may be adjusted. Remove the 1/8 NPT plug  
from the lower side of the gas valve that is to be set and  
install a fitting, hose and manometer. Start the appliance  
and observe the manifold pressure. Manifold pressure  
must be adjusted to 3.0 in. W.C. (0.75 kPa) (for high  
altitude only, standard operating pressure is 2.5 in. W.C.  
(0.62 kPa)). It is adjusted by removing the slotted cap on  
the gas valve and turning the adjustment screw (beneath  
the cap) clockwise to increase pressure and replaced  
after the adjustments have been completed and the  
fitting, hose and manometer have been removed and the  
1/8" plug has been replaced. Repeat this process until all  
gas valves have been set. Note: The pressure can be set  
only when the appliance is operating and only when the  
particular gas valve being adjusted is energized by a call  
for heat from the staging control.  
7. Once the inlet gas pressure is verified, the outlet  
gas pressure from each valve (manifold gas  
pressure) must be checked, and adjusted, if  
necessary. The manifold gas pressure must be 2.5"  
W.C. (0.62kPa).  
2
8. Complete the setup by checking the CO at the  
2
outlet of the unit. The CO should be 8% for  
natural gas, or 9.2% for propane.  
9. After placing the appliance in operation, the  
Burner Safety Shutoff Device must be tested.  
(a) Close gas shutoff valve with burner operating.  
(b) The flame will go out and blower will  
continue to run for the post purge cycle. One  
additional attempt to light will follow. Ignition  
will not occur as the gas is off. The ignition  
control will lockout, and will have to be reset  
before the unit will operate.  
After all of the gas valve manifold pressures have  
been set, the CO2 or O2 must be reset. CO2 or O2 will  
have changed when the manifold pressure was adjusted.  
Open the air shutter(s) to reduce the CO2 or O2 to the  
values achieved previously.  
The procedure is complete when all gas valves are  
adjusted to a manifold pressure of 3.0 in. W.C. (0.75  
kPa) and the CO2 is adjusted to 8.0% for Natural Gas  
(c) Open gas shutoff valve. Restart the appliance.  
The ignition sequence will start again and the  
burner will start. The appliance will return to  
its previous mode of operation.  
NOTE: Unit sizes 1000–2000 have two ignition controls  
and two ignitors, which work independently of one  
another. If the ignition control for stage 1 fails to properly  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 29  
appliances or 9.2% for LP appliances (to be checked  
only at full fire). When using an O2 analyzer, the correct  
O2 is 6.8% for both Natural Gas and LP appliances.  
protected from freezing.  
6. Low water cutoffs, if installed, should be checked  
every 6 months. Float type low water cutoff should  
be flushed periodically.  
7. Inspect flue passages, and clean with brushes/  
vacuums, if necessary. Sooting in flue passages  
indicates improper combustion. Determine the  
cause and correct.  
8. Inspect the vent system and air intake system, and  
if the vent system is Category III, ensure that all  
joints are sealed properly. If joints need to be  
resealed, completely remove existing sealing  
material, and clean with alcohol. Apply new sealing  
material, and re-assemble.  
Caution  
Should any odor of gas be detected, or if the gas  
burner does not appear to be functioning in a normal  
manner, close main shutoff valve, do not shut off  
switch, and contact your heating contractor, gas  
company, or factory representative.  
6.7 Shutting Down the Brute Deluxe  
1. Switch off the main electrical disconnect switch.  
2. Close all manual gas valves.  
3. If freezing is anticipated, drain the Brute Deluxe and  
be sure to also protect building piping from freezing.  
This step to be performed by a qualified service  
person.  
7.2 Appliance Maintenance and  
Component Description  
Only genuine replacement parts should be used.  
Caution  
6.8 To Restart the Brute Deluxe  
If drained, follow Section 6.2 in this manual for  
proper filling and purging.  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and dan-  
gerous operation. Verify proper operation after servicing.  
1. Switch off the main electrical disconnect switch.  
2. Close all manual gas valves.  
3. WAIT FIVE (5) MINUTES.  
See Figure 5 for location of gas train components.  
The gas and electric controls on the appliance are  
engineered for long life and dependable operation, but  
the safety of the equipment depends on their proper  
functioning. It is strongly recommended that a qualified  
service technician inspect the basic items listed below  
every year.  
4. Set the aquastat or thermostat to its lowest setting.  
5. Open all manual gas valves.  
6. Reset all safety switches (pressure switch, manual  
reset high limit, etc.).  
7. Set the temperature controller to the desired  
temperature setting and switch on electrical power.  
8. Burner will go through a prepurge period and  
ignitor warm-up period, followed by ignition.  
a. Ignitioncontrols  
b. Ignitors  
c. Water temperature control  
d. Automatic gas valve  
e. Pressure switches  
SECTION 7.  
Maintenance  
f.  
Blowers  
7.2.1 Burners  
7.1 System Maintenance  
Close main manual gas valve before proceeding.  
Checking the burners for debris - Remove the ignitor  
inspection panels(s) and ignitor(s) and inspect the burners  
through the ignitor hole(s) using a flashlight to illuminate.  
If there is any indication of debris on the burners that are  
visible, all the burners will need to be inspected more  
thoroughly. Remove the screws from around the front of  
the air box (large panel from which the ignitor inspection  
panel(s) were removed), and remove the large panel.  
Remove the gas manifold assemblies and the burner  
panels. Inspect the burners. Clean burners, if necessary,  
by blowing compressed air from the outside of the  
burners into the center of the burner. A dirty burner may  
be an indication of improper combustion or dirty  
combustion air. Determine the cause, and correct.  
Replace the burners in the reverse order  
1. Lubricate the system water-circulating pump, if  
required, per the instructions on the pump.  
2. If a strainer is employed in a pressure reducing  
valve or the piping, clean it every six months.  
3. Inspect the venting system for obstruction or  
leakage at least once a year. Periodically clean the  
screens in the vent terminal and combustion air  
terminal (when used).  
4. Keep the appliance area clear and free from  
combustible materials, gasoline, and other  
flammable vapors and liquids.  
5. If the appliance is not going to be used for  
extended periods in locations where freezing  
normally occurs, it should be isolated from the  
system and completely drained of all water. All  
systems connected to it should also be drained or  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 30  
7.2.2 Filter  
7.2.7 Ignitors/Sensor  
The filter used in the Brute Deluxe is washable  
with an 83% arrestance. Since the filter is washable, it  
will only need replacement when unwashable,  
deteriorated or damaged. If filter replacement is needed,  
it should only be replaced with a factory part. Inspect the  
air filter. If there is debris on the air filter, remove it from  
the filter box, and wash it with mild soap and water.  
Ensure that the filter is completely dry before re-  
installing, in reverse order.  
The ignitor/sensor used are 120v "hot surface"  
type. They are energized whenever there is a call for  
heat and switched off when ignition is established and  
flame has been sensed. Brute Deluxe sizes 500 and 750  
have one ignitor/sensor. Sizes 1000 to 2000 have two  
ignitor/sensors. To replace the ignitor/sensor, shut off the  
120-volt power to the appliance, remove the ignitor  
access panel, disconnect the Molex connector, remove  
the two mounting screws on the ignitor/sensor flange and  
pull the ignitor out. ((Hot Surface) Ignitor and the Flame  
Sensor are the same items). Install in reverse order,  
always using a new ignitor gasket with the replacement  
ignitor.  
7.2.3 Gas Valves  
The gas valves are designed to operate with supply  
pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).  
To remove a valve, shut off 120-volt power and the  
manual gas shutoff valve. Remove the top front panel from  
the unit. Disconnect the wires to the valve. Disengage the  
flanged fitting before and after the valve, and remove the  
valve. Re-install in reverse order. Ensure o-rings are  
properly installed for both inlet and outlet. Turn on manual  
gas shutoff valve and 120 volt power and check appliance  
operation and tightness of gas valve connections.  
Caution  
Ignitor gets hot.  
7.2.8Transformer  
The transformer is not capable of supplying control  
voltage for external devices such as zone valves, which  
must have their own separate power supply. Should a  
transformer need replacing, shut off the 120-volt power.  
Unplug the transformer wires, remove the mounting  
screws and remove the transformer. Replace transformer  
in the reverse order.  
7.2.4 ManualResetHighLimitControl  
The high limit switch is manual reset switch with an  
adjustable set point, up to 240°F (116°C) on boiler  
models and 200°F (93°C) on water heater models and  
boilers ordered with low temperature controls. To  
replace the switch, shut off the 120-volt power to the  
appliance. Remove the cover from the switch to access  
the mounting screws. Remove the screws, and pull the  
switch off the control panel. Remove the capilliary and  
bulb from the thermal well located in the header.  
Replace in reverse order.  
7.2.9 Blowers  
The combustion air blowers bring the combustion  
air for the Brute Deluxe from the upper chamber to the  
lower chamber. Mixing of the gas and air occurs in the  
burners. Sizes 500, 750 and 1000 each have one blower,  
and sizes 1250 to 2000 each have two blowers. If a  
blower change is required, turn off the 120-volt power  
and gas supply to the unit. Remove the front panel.  
Disconnect the blower's wire harness. Remove the  
screws at the blower flange, and pull the blower out.  
Replace blower in reverse order, ensuring that all joints  
are made correctly. After replacement, ensure that the  
unit operates properly, by following the set-up procedure  
in this manual.  
7.2.5 TemperatureControl  
The temperature control is a Honeywell L6008. To  
replace the control, shut off the 120-volt power to the  
appliance. Remove the cover from the control panel, and  
remove the mounting screws to remove the controller.  
Replace in reverse order.  
7.2.6 IgnitionControls  
7.2.10 Flow Switch  
The ignition controls ensure the proved interrupted-  
type ignition system. They control the hot surface  
ignitors and prove that the flame signal is appropriate for  
powering the gas valves. It also controls the blower’s  
pre-purge and post-purge. Brute Deluxe sizes 500 and  
750 have one ignition control. Sizes 1000 to 2000 have  
two ignition controls. On sizes up to 750, one ignition  
control controls stages 1 and 2. On unit sizes 1000–  
2000, one ignition control is for stage 1, and the other is  
for stage 2.  
To replace a control, shut off the 120-volt power to  
the appliance. Remove the cover from the control panel.  
Remove the electrical connectors from the ignition control.  
Take out the controller’s mounting screws, and pull the  
controller out. Replace in reverse order.  
The Brute Deluxe uses a paddle-type flow switch  
to ensure that the unit has water flow before ignition is  
allowed.  
7.2.11 Heat Exchanger Coil  
WARNING  
Black carbon soot buildup on a dirty heat exchanger  
can be ignited by a random spark or flame, thereby  
creating a risk of fire or explosion.. To prevent this  
from happening, dampen the soot deposits with a wet  
brush or fine water spray before servicing the heat  
exchanger.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 31  
The Brute Deluxe has a pre-mixed burner system.  
These systems provide the burners with sufficient air for  
complete combustion, and black carbon sooting is  
seldom experienced. If sooting is suspected, view ports  
for inspection of the heat exchanger are provided on the  
right side of the boiler. They are located below the  
headers, and are accessed by opening the small round  
cover that is attached by one screw. In the unlikely event  
that there is a buildup of black carbon soot or other  
debris on the heat exchanger, clean per the following:  
flow. If the tubes show signs of scaling, clean the  
internal surface. offers a tube cleaning kit, part  
number R0010000.  
11. Reassemble in the reverse order, and check  
appliance operation after start-up.  
NOTE: The Warranty does not cover damage caused  
by lack of required maintenance, lack of water flow,  
or improper operating practices.  
1. Disconnect the electrical supply to the unit.  
SECTION 8.  
2. Turn off the gas supply by closing the manual gas  
Trouble Shooting  
valve on the heater.  
3. Disconnect and remove the wires, conduit and  
sensors from all components that are attached to  
the inlet/outlet header.  
8.1 Resolving Lockouts  
There are many causes of lockouts. The three most  
common causes are: (1) inadequate gas supply, (2) poor  
combustion, (3) ignitor failure.  
4. Isolate the heat exchanger from the water supply.  
5. Disconnect the header flanges from the inlet and  
1. Inadequate gas supply: Before proceeding, ensure  
that the gas supply has not been shutoff or the LP tank  
(LP boilers) is not empty. Then, restart the boiler and  
observe the operational cycle. After a 15-second fan  
pre-purge, the ignitor will heat up for 20 seconds, and  
then the unit will light. If it does not, check the gas  
supply pressure to the appliance, after resetting the  
appliance and attempting another start-up. The gas  
pressure to the appliance must be above 5" W.C.  
(1.2kPa) throughout the entire start-up cycle. If it is  
not, correct the supply problem (check gas valves or  
supply piping). If the supply pressure is adequate,  
consult the factory for assistance.  
outlet.  
6. Allow the heat exchanger to drain. Remove the  
front cover(s) by removing the rubber access  
strip(s) and the retaining screws. Remove the  
venting and remove the top, by removing the  
screws that attach the top to the side panels.  
Remove the side panels. Remove the front lower  
panels sealing the combustion area. To remove the  
gas train, disconnect the unions located below the  
intermediate pan and the field installed union  
located outside the cabinet, and pull up, bringing  
the union end connectors through the grommets in  
the intermediate pan. To remove the intermediate  
pan, remove the slide out control assembly and  
blower(s) to reveal the screws. Remove the screws  
holding the intermediate pan, and lift up to remove  
it. The heat exchanger has integral metal sections  
attached, which connect to the frame of the boiler.  
Locate and remove the screws along the front, rear  
and bottom of the integral metal sections, and  
remove the heat exchanger and metal sections by  
lifting up. On the larger appliances, a center heat  
exchanger support must be unbolted before it can  
be removed.  
7. Remove the heat exchanger from the unit. Note:  
The heat exchangers are heavy and may require  
two people to remove to avoid personal injury.  
8. Clean the heat exchanger: A light accumulation of  
soot or corrosion on the outside of the heat exchanger  
can be easily removed. Use a wire brush to remove  
loose soot and scale from the heat exchanger. Do not  
use water or compressed air for cleaning.  
9. Note: While the heat exchanger is out of the unit,  
inspect the firewall refractory insulation. Replace if  
necessary.  
10. Inspect the inside of the copper tubes for scale  
buildup. Scale can build up on the inner surface of  
the heat exchanger tubes, which can restrict water  
2. Poor combustion: Poor combustion should be  
suspected if there is a strong flue gas odor. The  
odor may result from an improper gas/air ratio  
(high or low O2 or CO2). Brute Deluxe appliances  
operate best with 45% excess air (8% CO2 on  
natural gas, 9.2% CO2 on LP). Check the CO2 of  
the appliance and adjust if necessary.  
3. Ignitor failure: If the boiler goes through a normal  
start cycle but combustion does not occur, ignitor  
failure should be suspected. Check the ignitor by  
unplugging the ignitor plug and measuring the  
ignitor resistance. It should be 50-80 ohms at room  
temperature. If the resistance is not 50-80 ohms,  
replace the ignitor. If the resistance is correct, reset  
the boiler and check for 120 VAC at the ignitor  
plug during the start cycle. If there is no voltage,  
replace the faulty ignitor wire harness or the  
ignitioncontrol.  
8.2 Delayed Ignition — Possible Causes  
A defective burner can cause a delayed ignition. If  
the gas supply pressure is proper and the gas valves are  
functioning properly, then burners should be inspected.  
There should be no distortion or perforations in the  
burners outside of the active burner port area. Replace if  
indicated.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 32  
8.3 Short Cycling — Boiler  
SECTION 9.  
Because the Brute Deluxe is a stage-fired boiler,  
and its input will decrease when there is a reduction in  
heating load, short cycling is greatly reduced. If the  
heating load drops below the minimum input of the  
boiler for an extended period, the boiler will have a  
tendency to short cycle. This can be a symptom of  
improper control strategy or setpoints, or a load  
distribution problem. Contact your representative to  
discuss possible remedies.  
Replacement Parts  
Only genuine replacement parts should be used.  
9.1 General Information  
To order or purchase parts for the Brute Deluxe,  
contact your nearest dealer or distributor. If they cannot  
supply you with what you need, contact Customer  
Service (see back cover for information).  
9.2 Parts List - see next page.  
8.4 Short Cycling — Water Heater  
Short cycling will generally occur only in  
combination space heating and water heating  
applications when the water heater is operating in the  
space-heating mode. Because the Brute Deluxe is a  
stage-fired water heater and its input will reduce when  
there is a reduction in heating load, short cycling is  
greatly reduced. If the heating load drops below the  
minimum input of the water heater for an extended  
period, the water heater will have a tendency to short  
cycle. If short cycling is frequently experienced,  
regardless of the control’s attempt to limit it, the heating  
load should be redistributed to control it.  
If short cycling occurs in a water heater application,  
it is probably caused by undersized piping between the  
water heater and the storage tank or by some other factor  
that restricts proper water flow through the water heater.  
The cause should be determined and corrected.  
8.5 High Gas Consumption  
Appliances operating with an improper air/fuel  
ratio are very inefficient and consequently, have very  
high gas consumption. Because efficiency is high when  
the CO2 is high (or O2 is low), appliances operating with  
low CO2 or high O2 (especially LP appliances) consume  
more gas. Adjust the CO2 or O2 for optimum efficiency.  
If no combustion analyzing equipment (CO2 or O2) is  
available then a proper adjustment of the air/fuel ratio  
(CO2 or O2) cannot be accomplished. However, by  
briefly sniffing the flue gases it is possible to determine  
if the CO2 or O2 is within the proper range. No  
significant flue gas odor should be detected when  
combustion is proper. A strong piercing smell indicates  
poor combustion and generally a lean mixture - low CO2  
or high O2 . The CO2 should be 8% at high fire. To check  
the CO2, first verify that the supply gas pressure is  
within 5" to 13" w.c. (1.2 to 3.2 kPa) With the Brute  
Deluxe running with all stages firing, set the air box  
pressure to 1.5" w.c. (0.37 kPa) (as a starting point), by  
adjusting the air shutter(s) at the bottom of the fan(s).  
Check the CO2, and adjust the air shutters if further  
adjustment to the CO2 is needed. Sizes 1250 to 2000  
have two blowers and two air chambers (boxes). The  
pressure of each air box must be equal when the final  
adjustment is made.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 37  
Figure 23. Sheet Metal Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 38  
Figure 24. Internal Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brute Deluxe (500-2000)  
Page 39  
Brute Deluxe Water Heater  
Brute Deluxe Hydronic Boiler  
Size  
Pump p/n  
Size  
500  
750  
1000  
1250  
1500  
1750  
2000  
Pump p/n  
A2001700  
A2001700  
A2001800  
A2001800  
A2001900  
A2001900  
A2109700  
Soft Water  
A2001700  
A2001700  
A2001700  
A2001700  
A2001700  
A2001900  
A2109700  
Normal Water  
A2001700  
A2001700  
A2001800  
A2001800  
A2001900  
A2001900  
A2109700  
Hard Water  
A2001900  
A2001900  
A2001900  
A2001900  
A2001900  
A2001900  
A2109700  
500  
750  
1000  
1250  
1500  
1750  
2000  
Figure 25. Heat Exchanger Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 40  
Figure 26. Electrical Components.  
Bradford White Company reserves the right to change specifications, components, features, or to discontinue products without notice.  
Ambler, PA19002  
Tech. Service (800) 334-3393  
Service Parts (800) 538-2020  
Warranty Service (800) 531-2111  
Litho in U.S.A. © Bradford White 1102 Document 1245  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blodgett Convection Oven FA GZL User Manual
Blue Rhino Outdoor Fireplace GAD730T User Manual
Bosch Appliances Home Security System 9 6 BLCC110U User Manual
Braun Electric Toothbrush 8500 DLX OxyJet User Manual
Briggs Stratton Portable Generator 30348 User Manual
Brother Sewing Machine BAS 411 User Manual
Carrier Furnace 58MEC User Manual
Casio Watch AMW700B 1AV User Manual
CDA Refrigerator FW420 User Manual
Chief Manufacturing Indoor Furnishings PTS Series User Manual