InstallationandOperationInstructions
Document1245
Installation and Operation Instructions for
BRUTE DELUXE
Hydronic Boiler
Model BMT2H
Volume Water Heater
Model BMT2V
Sizes 500–2000 MBTU/h
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death.
Improper installation and/or operation will void the warranty. For indoor installations, as an additional
measure of safety, Bradford White strongly recommends installation of suitable Carbon Monoxide
detectors in the vicinity of this appliance and in any adjacent occupied spaces.
AVERTISSEMENT
WARNING
Assurez-vous de bien suivres les instructions
If the information in this manual is not
données dans cette notice pour réduire au
followed exactly, a fire or explosion may
minimum le risque d’incendie ou d’explosion ou
result causing property damage, personal
pour éviter tout dommage matériel, toute
injury or loss of life.
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans
le voisinage de cet appareil ou de tout autre
appareil.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où
vous vous trouvez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• If you cannot reach your gas supplier, call
the fire department.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
Installation and service must be performed by
a qualified installer, service agency, or gas
supplier.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
238-49222-00A REV 4/11
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 3
most operating issues are caused by improper
installation.
The Brute Deluxe appliance is protected against
over pressurization. A pressure relief valve is fitted to
all appliances. It is installed on the outlet header, at the
water outlet of the appliance.
SECTION 1.
General Information
USING THIS MANUAL – Because Brute
Deluxe Boilers and Water Heaters are identical
appliances, with the exception of materials of
manufacture, labels and ultimate use application,
this manual provides information for the proper
installation, operation and maintenance of all
products. Where differences exist between the
application of the appliances and their operation, the
sections pertinent to only one appliance or the other
will be so identified.
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance with:
1). In the U.S., the " National Fuel Gas
Code"ANSI Z223.1/NFPA54, Latest Edition and all
applicable local codes as required by the Authorities
Having Jurisdiction (AHJ), or
2). In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and
all applicable local codes as required by the AHJ.
In the Commonwealth of Massachusetts, this app-
liance must be installed by a licensed plumber or gas fitter.
WARNING
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code"
(NEC), ANSI/NFPA 70, latest Edition and all applicable
local codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part
1”, CSA STD. C22.1 and all applicable local codes as
required by the AHJ.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
referenced above.
The Brute Deluxe hydronic boiler or water heater must
be installed in accordance with the procedures
detailed in this manual, or the Bradford White warranty
may be voided. The installation must conform to the
requirements of the local jurisdiction having authority,
and, in the United States, to the latest edition of the
National Fuel Gas Code, ANSI Z223.1/NFPA54. In
Canada, the installation must conform to the latest
edition of the Natural Gas and Propane Installation
Code, CSA B149.1 and/or local codes. Where
required by the authority having jurisdiction, the
installation of appliances must conform to the
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1. Any
modifications to the unit, its gas controls, or wiring
may void the warranty. If field conditions require
modifications, consult the factory representative
1.2 Model Identification
Consult the rating plate on the unit. The following
information describes the model number structure.
1-4 Model Series Designation
B M T 2 = Brute Deluxe
4
Usage
H = Hydronic
V = Volume Water
before initiating such modifications.
1.1 Introduction
5-8 Size
0 5 0 0 = 500,000 BTU/h input
This manual provides information necessary for the
installation, operation, and maintenance of Bradford
White Brute Deluxe copper tube appliances. Read it
carefully before installation.
0 7 5 0 = 750,000 BTU/h input
1 0 0 0 = 999,000 BTU/h input
1 2 5 0 = 1,250,000 BTU/h input
1 5 0 0 = 1,500,000 BTU/h input
1 7 5 0 = 1,750,000 BTU/h input
2 0 0 0 = 1,999,000 BTU/h input
All application and installation procedures should
be reviewed completely before proceeding with the
installation. Consult the Bradford White factory, or local
factory representative, with any issues or questions
regarding this equipment. Experience has shown that
1
2
3
T
4
2
5
6
7
8
9
10
11
A
12
C
13
K
14
1
15
16
17
B
M
SERIES
SIZE
LOCATION
REVISION
USAGE
H
V
FUEL
N
P
ALTITUDE
FIRING
MODE
K 2-Stage
HEAT
OPTIONS
CODE
PUMP
EXCHANGER
OPTIONS
B
M
T
2
0
5
0
0
C
1
A
K
P
S
X
J
N
0
1
1
1
1
2
7
0
2
5
7
0
5
0
5
0
5
0
0
0
0
0
0
0
BMT2V: H
BMT2H:
C
N
B
BMT2V:
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 4
9
Fuel
the appliance or to lower floors of the structure.
N = Natural Gas
P = Propane
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
10 Altitude
A = 0–10,000 feet
11 Location
C = Indoor and Outdoor
The appliance is design certified by CSA-
International for installation on combustible flooring; in
basements; in closets, utility rooms or alcoves. Brute
Deluxe Boilers or Water Heaters must never be
installed on carpeting. The location for the appliance
should be chosen with regard to the vent pipe lengths
and external plumbing. The unit shall be installed such
that the gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement, control
replacement, etc.). When vented vertically, the Brute
Deluxe must be located as close as practical to a
chimney or outside wall. If the vent terminal and/or
combustion air terminal terminate through a wall, and
there is potential for snow accumulation in the local
area, both terminals should be installed at an appropriate
level above grade.
12 Firing Mode
K = Two-stage
13 Revision
1 = First version of design
14 Heat Exchanger
B = Glass-lined cast iron / copper / bronze trim
(std. on BMT2V)
C = Glass-lined cast iron / copper
(std. on BMT2H)
K = Bronze / copper
N = Glass-lined cast iron / cupro-nickel
(n/a on water heaters)
P = Glass-lined cast iron / cu-nickel / bronze trim
S = Bronze / cupro-nickel
The dimensions and requirements that are shown in
Table 1 should be met when choosing the locations for
the appliance.
15 Option Code
X = Standardunit
J = CSD-1, FM, IRI, IL
1.6 Locating Pump-Mounted Water Heater
16 Pump Options
with Respect to Storage Tank(s)
For best results, a pump-mounted Brute Deluxe
water heater should be located within 15 feet (4.6m) of
the storage tank(s). The pump is sized for 30 feet (9.1m)
of piping.
H = Pump mounted BMT2V, hard water pump
N = Pump mounted (any), normal water pump
1.3 Warranty
If the appliance must be installed with longer piping
runs, then larger diameter pipe or tubing shall be used.
Consult the factory for assistance.
Bradford White’s appliances are covered by a
limited warranty. Owners should submit online warranty
All warranty claims must be made to an authorized
Bradford White representative or directly to Customer
Service. Claims must include the serial number and
model (this information can be found on the rating plate),
installation date, and name of the installer. Shipping
costs are not included in the warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on the
packing slip. Inspect everything for damage immediately
upon delivery, and advise the carrier of any shortages or
damage. Any such claims should be filed with the
carrier. The carrier, not the shipper, is responsible for
shortages and damage to the shipment whether visible or
concealed.
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
For the best results, a pump-mounted Brute Deluxe
REQUIRED
CLEARANCEFROM
COMBUSTIBLEMATERIAL
RECOMMENDED
SERVICEACCESS
CLEARANCE
APPLIANCE
SURFACE
inches
cm
inches
cm
Left Side
Right Side
Top
1
1
1
1
1
2.5
2.5
2.5
2.5
2.5
24
24
12
**12**
36
61
61
30
30**
91
Back
Front
Vertical
(Category 1)
Vent
Horizontal
(Category 3)
Vent
1.4 Dimensions
6*
15.2*
See Figures 1 and 2.
per UL1738 venting
system supplier’s
instructions
1.5 Locating the Appliance
The appliance should be located to provide
*1" (2.5cm) when b-vent is used.
**When vent and/or combustion air connects to the back, recommended
clearance is 36" (91cm).
clearances on all sides for maintenance and inspection. It
should not be located in an area where leakage of any
connections will result in damage to the area adjacent to
Table 1. Clearances.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 5
Air
Conn.
W
Vent
Conn.
V
Shipping Weight1
Size
500
A
B
C
D
E
lbs
kg
33¾ 85
16¾ 43
6½ 17
10 25
8
20
6
15
15
20
20
20
20
8
20
10 25
10 25
12 30
12 30
12 30
14 36
425 193
505 229
615 279
675 306
760 345
825 375
955 434
750
45¾ 116
57¾ 147
68¼ 173
78¾ 200
89¼ 227
99¾ 253
22¾ 53
28¾ 73
6½ 17
6½ 17
10¼ 26
10¼ 26
10¼ 26
10¼ 26
10 25
10 25
10 25
10 25
10 25
10 25
9½ 24
9½ 24
6
8
8
8
8
1000
1250
1500
1750
2000
34
87
9
9
9
9
23
23
23
23
39½ 100
44¾ 113
49¾ 127
12 30
NOTES: 1. Add 55 lbs (25kg) for pump-mounted units.
Dimensions in inches cm.
Figure 1. Dimensional Data (standard units).
1.8 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
Boiler should be located within 15 feet (4.6m) of the
supply and return headers. The pump is sized for 30 feet
(9.1m) of piping.
If the appliance must be installed with longer piping
runs, then larger diameter tubing shall be used. Consult
the factory for assistance.
from Outside Wall
The forced draft combustion air blower/blowers in
the appliance has/have sufficient power to pull air and
vent properly when the following guidelines for
horizontal air and vent are followed (see Table 2).
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 6
Air
Conn.
W
Vent
Conn.
V
Size
500
A
B
C
D
E
F
33¾
45¾
57¾
68¼
78¾
89¼
99¾
86
16¾ 43
6½ 17
10 25
8
20
46¼
58¼
70¼
80¾
91¼
117
148
178
205
232
6
6
8
8
8
8
15
15
20
20
20
20
8
20
750
116
147
173
200
227
253
22¾ 58
28¾ 73
34¼ 87
39½ 100
44¾ 113
49¾ 127
6½ 17
6½ 17
10¼ 26
10¼ 26
10¼ 26
10¼ 26
10 25
10 25
10 25
10 25
10 25
10 25
9½ 24
9½ 24
10 25
10 25
12 30
12 30
12 30
14 36
1000
1250
1500
1750
2000
9
9
9
9
23
23
23
23
101¾ 258
112¼ 285
12 30
Figure 2. Dimensional Data (pump-mounted models).
HORIZONTAL
VENTPIPE
DIAMETER
AIR COLLAR
&PIPE
DIAMETER
VENT COLLAR
SIZE
MAX.PIPE
LENGTH
MAX.NO.
OF ELBOWS
SIDEWALL
SIDEWALL
COMBUSTION
AIRTERMINAL
SIZE
VENT
TERMINAL
in
cm
20
25
25
30
30
30
36
in
6
8
8
8
8
8
12
cm
15
20
20
20
20
20
30
in
6
6
8
8
8
8
12
cm
15
15
20
20
20
20
30
ft
m
PARTNUMBER
CA001401
CA001401
CA001402
CA001403
CA001403
CA001403
CA001404
PARTNUMBER
20260701
20260701
20260703
20260703
20260703
20260703
20260706
500
750
8
50 15
50 15
50 15
50 15
50 15
50 15
50 15
3
3
3
3
3
3
3
10
10
12
12
12
14
1000
1250
1500
1750
2000
Table 2. Horizontal Vent / Combustion Air Parameters.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 7
NOTE: The vent collar size is larger than the size of the
vent pipe that can be used. Vent collar size and
horizontal pipe diameters can be found in Table 2. The
larger vent collar size is to accommodate Category I
(vertical) vent systems.
communicate with the outdoors and shall have a
minimum free area of 1 square inch per 3000 BTU/hr (7
square cm/kW) of the total input rating of all equipment
located in the enclosure. This opening must not be less
than the sum of the areas of all vent connectors in the
confined space.
NOTE: When located on the same wall, the Brute Deluxe
combustion air intake terminal must be installed a minimum
of 12" (30cm) below the exhaust vent terminal and sep-
arated by a minimum of 36 inches (91cm) horizontally.
The air intake terminal must be installed high enough
to avoid blockage from snow, leaves and other debris.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform to
the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or,
in absence of such requirements, follow CSA B149.1.
2.1.2 IntakeCombustionAir
SECTION 2.
The combustion air can be taken through the wall,
or through the roof. When taken from the wall, it must be
taken from out-of-doors by means of the horizontal wall
terminal (see Table 2). When taken from the roof, a
field-supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water (see Figure 3).
Use single-wall galvanized pipe, per Table 4, for
the combustion air intake (see Table 2 for appropriate
size). Route the intake to the heater as directly as
possible. Seal all joints with tape. Provide adequate
hangers. The unit must not support the weight of the
combustion air intake pipe. Maximum linear pipe length
allowed is 50 feet (15.2m). Three elbows have been
calculated into the 50-foot (15.2m) linear run. Subtract
10 allowable linear feet (3.0m) for every additional
elbow used (see Table 2). When fewer than 3 elbows are
used, the maximum linear pipe length allowed is still 50
feet (15.2m).
Venting and Combustion Air
2.1 Combustion Air
Brute Deluxe boilers and water heaters must have
provisions for combustion and ventilation air in
accordance with section 5.3, Air for Combustion and
Ventilation, of the National Fuel Gas Code, ANSI
Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1,
Installation Codes, or applicable provisions of the local
building codes.
A Brute Deluxe appliance may receive combustion
air from the space in which it is installed, or it can be
ducted directly to the unit from the outside. Ventilation
air must be provided in either case.
2.1.1 CombustionAirFromRoom
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of the
same cross-sectional area as the free area of the
openings to which they connect.
The connection for the intake air pipe is on the
filter box. The Brute Deluxe appliances have venting
and combustion air ducting attached to the top.
In addition to air needed for combustion, air shall
also be supplied for ventilation, including all air required
for comfort and proper working conditions for personnel.
The Brute Deluxe loses less than 1 percent of its input
Method 1: Two permanent openings, one
commencing within 12 inches (30 cm) of the top and one
commencing within 12 inches (30 cm) of the bottom, of
the enclosure shall be provided. The openings shall
communicate directly, or by ducts, with the outdoors or
spaces that freely communicate with the outdoors. When
directly communicating with the outdoors, or when
communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1 square
inch per 4000 BTU/hr (5.5 square cm/kW) of total input
rating of all equipment in the enclosure. When
EACHOPENING*
UNIT
SIZE
SQUAREINCHES
SQUARECM
500
750
125
188
250
313
375
438
500
807
1213
1613
2020
2420
2826
3226
1000
1250
1500
1750
2000
communicating to the outdoors through horizontal ducts,
each opening shall have a minimum free area of not less
than 1 square inch per 2000 BTU/hr (11 square cm/kW)
of total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method, for each Brute
Deluxe model.
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at floor level and one
at the ceiling, so the total net free area could be double the figures
indicated.
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure, shall
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a vertical
or horizontal duct to the outdoors or spaces that directly
Thischartisforusewhencommunicatingdirectlywiththeoutdoors.
For special conditions and alternate methods, refer to the latest
edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of louvers.
Correct for screen resistance to the net free area if a screen is
installed. Check all local codes applicable to combustion air.
Table 3. Combustion Air Openings.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 8
rating to the room, but other heat sources may be present.
may lead to serious injury or death. If safe operation of
all appliances connected to a common vent cannot be
assured, including prevention of spillage of flue gasses
into living spaces, common venting should not be applied,
and appliances should each be vented separately.
2.2 Venting
2.2.1 VentCategories
Depending upon desired Brute Deluxe venting, it
may be considered a Category I or a Category III
appliance. In general, a vertical vent system will be a
Category I system. However, in rare instances, a vertical
vent system may be considered Category III. In the U.S.,
the National Fuel Gas Code (ANSI Z223.1-Latest
Edition), or in Canada the CSA B149.1 (latest edition),
defines a Category I vent system, and includes rules and
tables to size these vent systems. If the Brute Deluxe’s
vertical vent system does not satisfy the criteria for
Category I venting, it must be vented as a Category III
system.
Proper vent sizing, construction and safety
requirements from the National Fuel Gas Code, ANSI
Z223.1 or in Canada, from CSA B149.1 as well as all
applicable local codes must be followed.
As an additional precaution, it is recommended that
a Carbon Monoxide (CO) alarm be installed in all
enclosed spaces containing combustion appliances.
Brute Deluxe units are not allowed to be vented
into a common horizontal vent system, unless a properly
sized vent fan is used, and the common vent system is
properly designed by the vent fan manufacturer or a
qualified engineer.
Refer to the installation and operating instructions on
all appliances to be common vented for instructions,
warnings, restrictions and safety requirements. If safe
operation of all appliances connected to a common vent
cannot be assured, including prevention of spillage of flue
gasses into living spaces, common venting should not be
applied, and appliances should each be vented separately.
All Brute Deluxe vent systems which discharge
horizontally (without the use of a power venter) are
considered Category III vent systems.
2.2.2 CategoryIVent
When vented as a category I appliance, the vent
system must conform to the National Fuel Gas Code (ANSI
Z223.1-Latest Edition) in the U.S., or in Canada, to CSA
B149.1 (latest edition). The vent system must be sized and
installed for a Category I Fan-Assisted Appliance.
If chimney height is greater than 25 feet, or if multiple
units are vented into the same vertical vent, a barometric
damper must be installed on each appliance, such that the
flue draft does not exceed (negative) 0.1" w.c.
If using a power venter for any type of Category I
venting, the draft should be set between (negative) 0.01
and 0.10" w.c.
2.2.4 CategoryIIIVent
When the Brute Deluxe is vented with horizontal
discharge, it must be installed per this installation
manual and the venting system manufacturer’s
installation instructions. The vent system must be sealed
stainless steel (see Table 5).
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers as
required in the venting system manufacturer’s Instal-
2.2.3 CommonVentingSystems
Brute Deluxe units are Category I fan-assisted
when vented vertically and adhering to all applicable
codes.
When common venting Brute Deluxe fan-assisted
unit with other appliances through one shared vertical
duct called a “common vent”, special care must be taken
by the installer to ensure safe operation. In the event that
the common vent is blocked, it is possible, especially for
fan-assisted devices, to vent backwards through non-
operating appliances sharing the vent, allowing
combustion products to infiltrate occupied spaces. If the
appliances are allowed to operate in this condition,
serious injury or death may occur.
WARNING
Operation of appliances with a blocked common vent
TERM
DESCRIPTION
Single-wall galvanized steel pipe, 24 gauge
minimum (either insulated or non-insulated)
Pipe
Joint
Permanent duct tape or aluminum tape
Sealing
Table 4. Required Combustion Air Piping Material.
Figure 3. Combustion Air and Vent Through Roof.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 9
lation Instructions. Horizontal portions of the venting
system must be supported to prevent sagging and may
not have any low sections that could trap condensate.
The unit must not support the weight of the vent pipe.
Horizontal runs must slope downwards not less than ¼
inch per foot (2 cm/m) from the unit to the vent terminal.
Reference Table 1 for the size of the Category III vent
system. Up to three elbows can be used with 50 linear
feet (15.2m) of pipe. Subtract 10 allowable linear feet
(3.0m) for every additional elbow used.
on building surfaces or other nearby objects. Vent
products may damage such surfaces or objects.
7. If the boiler or water heater uses ducted
combustion air from an intake terminal located on
the same wall, locate the vent terminal at least 3
feet (0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1 foot
(0.3m) above the combustion air terminal.
2.3.2 SideWallCombustionAirTerminal
The side wall combustion air terminal (see Table
2) must be used when the unit takes its combustion air
through a duct from a side wall. Consider the following
wheninstallingtheterminal:
1. Do not locate the air inlet terminal near a source of
corrosive chemical fumes (e.g., cleaning fluid,
chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject to
damage by accident or vandalism.
WARNING
The outdoor vent terminal gets hot. Unit must be
installed in such a way as to reduce the risk of burns
from contact with the vent terminal.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Side Wall Vent Terminal
3. Locate the combustion air terminal so that it cannot
be blocked by snow. The National Fuel gas code
requires that it be at a minimum of 12" above
grade. Depending on local conditions, the installer
should ensure that it remains at least 12" above the
maximum potential snow line. Seek local
The appropriate side wall vent hood must be used,
and is listed in the installation and operation manual.
The terminal provides a means of installing the vent
piping through the building wall, and must be located in
accordance with ANSI Z223.1/NFPA 54 and applicable
local codes. In Canada, the installation must be in
accordance with CSA B149.1 or .2 and local applicable
codes. Consider the following when installing the
terminal:
municipalities and their codes for appropriate
installation techniques.
WARNING: It is critical that the combustion air
intake and the vent terminals remain at least 12"
above the maximum potential snow line. If either
the vent terminal or the air terminal is blocked by
snow, there may be potential for the unit to
produce excess carbon monoxide and or
recirculate flue gasses into the building/dwelling.
Personal injury or DEATH may occur. Natural
snowfall, drifting, and banking should all be taken
into account when locating the terminals in a
potentialsnowenvironment.
1. Figure 4 shows the requirements for mechanical
vent terminal clearances for the U.S. and Canada.
2. Vent terminals for condensing appliances or
appliances with condensing vents are not permitted
to terminate above a public walkway, or over an
area where condensate or vapor could create a
nuisance or hazard.
3. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
4. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows, gravity
inlets or other openings. When possible, locations
under windows or near doors should be avoided.
5. Locate the vent terminal so that it cannot be
blocked by snow. The National Fuel gas code
requires that it be at a minimum of 12" above
grade. In a location that has the possibility of snow
accumulation, it is critical the installer places the
vent at least 12" higher than the maximum potential
snow line. Seek local municipalities and their
codes for appropriate installation techniques.
6. Locate the terminal so the vent exhaust does not settle
4. If the Brute Deluxe is side-wall vented to the same
wall, locate the vent terminal at least 3 feet (0.9m)
horizontally from the combustion air terminal, and
locate the vent terminal at least 1 foot (0.3m) above
the combustion air terminal (see Figure 4).
2.3.3 VerticalVentTerminal
When the unit is vented through the roof, the vent
must extend at least 3 feet (0.9m) above the point at
which it penetrates the roof. It must extend at least 2 feet
(0.6m) higher than any portion of a building within a
horizontal distance of 10 feet (3.0m), and high enough
above the roof line to prevent blockage from snow.
When the combustion air is taken from the roof, the
combustion air must terminate at least 12" (30cm) below
the vent terminal (see Figure 3). Seek local
TERM
DESCRIPTION
Pipe
Must comply with UL Standard 1738
such as Type 29-4C Stainless Steel
(either insulated or non-insulated).
Joint
Sealing
Follow vent manufacturer’s instructions
municipalities and their codes for appropriate
installation techniques.
Table 5. Required Horizontal Venting Material.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 10
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
36 inches (91 cm)
See note 5
deck, or balcony
B= Clearance to window or door that may be
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
See note 4
opened
C= Clearance to permanently closed window
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal
distance of 2 feet (61cm) from the center
line of the terminal
See note 4
See note 5
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
See note 4
See note 4
See note 4
See note 5
See note 5
See note 5
H= Clearance to each side of center line
3 feet (91 cm) within a height 15 feet above
the meter/regulator assembly
3 feet (91 cm)
extended above meter/regulator assembly
See note 4
See note 4
I= Clearance to service regulator vent outlet
J= Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to
any other appliance
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
3 feet (91 cm) above if within 10 feet (3 m)
horizontally
36 inches (91 cm)
6 feet (1.83 m)
K= Clearance to a mechanical air supply inlet
Vent termination not allowed in this location
for category IV appliances. A vent shall not
terminate directly above a sidewalk or paved
driveway that is located between two single
Vent termination not allowed in this location
L= Clearance above paved sidewalk or paved for category IV appliances. For Category III
driveway located on public property
appliances, vent must terminate at least 7
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.
For Category III appliances that do not violate
the previous condition, vent must terminate
at least 7 feet (2.13m) above the sidewalk or
driveway.
M= Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the currentANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA-B149.1 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified inANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specified in CSA-B149.1, clearance is in accordance with local installation codes and the requirements of the gas supplier.
Figure 4. Combustion Air and Vent Through Side Wall.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 11
of a ProductApproved side wall horizontally vented gas fueled
From Massachusetts Rules and Regulations 248 CMR 5.08:
(a) For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or inpart for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented gas
fueled equipment, the installing plumber or gasfitter shall
observe that a hard-wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level where
the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or
hard-wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property owner to secure the
services of qualified licensed professionals for the installation
of hard-wired carbon monoxide detectors.
equipment does not provide the parts for venting the fuel gases,
but identifies "special venting systems", the following require-
ments shall be satisfied by the manufacturer:
1. The identification of each "special venting system" shall include
either the listing of the website, phone number or
manufacturer's address where the venting system installation
instructions can be obtained; and
2. The "special venting systems" shall be ProductApproved by the
Board, and the instructions provided with that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for the Product
Approved side wall horizontally vented gas fueled
equipment, and all the venting instructions, parts lists,
and/or design instructions for the venting system shall
remain with the appliance or equipment at the completion
of the installation.
Manufacturers' websites where venting system installation
instructions may be obtained is located on the website at:
2.3.4 VerticalCombustionAirTerminal
When combustion air is taken from the roof, a
field-supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water (see Figure 3). The
opening on the end of the terminal must be at least 12"
(30cm) above the point at which it penetrates the roof,
and high enough above the roof line to prevent blockage
from snow. When the vent terminates on the roof, the
combustion air must terminate at least 12" (30cm) below
the vent terminal.
a. In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard-
wired carbon monoxide detector with alarm and battery back-
up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision cannot
be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above
requirements; provided, however, that during said thirty (30)
day period, a battery operated carbon monoxide detector with
an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA720 and beANSI/UL
2034 listed and IAS certified.
2.4 Common Vent Test — Boilers
When an existing boiler is removed from a common
venting system, the common venting system is likely to
be too large for proper venting of the appliances
remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system placed
in operation, while the other appliances remaining con-
nected to the common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
3. SIGNAGE.A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line
with the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall read, in
print size no less than one-half (½) inch in size, "GAS VENT
DIRECTLYBELOW. KEEPCLEAR OFALLOBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in accor-
dance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not
Required To Be Vented" in the most current edition of NFPA 54
as adopted by the Board; and
2. ProductApproved side wall horizontal vented gas fueled
equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for
residential purposes.
2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers and
any appliance not connected to the common venting
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate
at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM PROVIDED. When the manufacturer of
ProductApproved side wall horizontally vented gas equipment
provides a venting system design or venting system compo-
nents with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting
system shall include:
1. Detailed instructions for the installation of the venting system
design or the venting system components; and
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
2. A complete parts list for the venting system design or venting
system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEMNOT PROVIDED. When the manufacturer
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 12
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas burning appliance to
their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Installation
Codes. When resizing any portion of the common
venting system, the common venting system should
be resized to approach the minimum size as
determined using the appropriate tables in Part II of
the National Fuel Gas Code, ANSI Z223.1/NFPA
54 and/or CSA B149.1, Installation Codes.
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not by the appliance.
Brute Deluxe’s gas train allows the user to pipe the
gas from either the right side or the left side of the unit.
As shipped, the right side of the gas train is capped off,
and there is a manual valve on the left side. If desired,
the manual valve on the left side of the gas train may be
moved to the right side, and the cap on the right side
may be moved to the left.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Brute
DISTANCE FROM GAS METER
SIZE
OR LAST STAGE REGULATOR
AND
GAS TYPE
0-100'
100-200'
200-300'
500 natural
1½"
1"
2"
2"
1½"
500 propane
1½"
750 natural
2"
2"
2½"
2"
2.5 Vent Terminals for Outdoor Units
For outdoor applications, the vent and combustion
air openings must be covered with proper terminals to
prevent rain, snow and other objects from falling into the
Brute Deluxe.
If local codes allow, outdoor installations may use
1' of appropriately sized galvanized single wall or B-
Vent and a rain cap for exhaust vent termination in the
default configuration (venting out of the top). Note that
some local codes may require a higher vertical vent
height, extending above any perimeter fencing, etc. In
installations where the appearance of the vent is
objectionable, the low profile vent terminals in Table 6
may be used.
Combustion air inlets consist of appropriately sized
galvanized pipe and elbows to allow the open end to
face down aside the boiler. This is available as a
Commercial Kit from the manufacturer.
Part numbers for the low profile terminals to cover the
vent and combustion air openings are shown in Table 6.
750 propane
1½"
1½"
1000 natural
2"
1½"
2½"
2"
2½"
2"
2½"
2"
3"
2½"
3"
2½"
1000 propane
1250 natural
1250 propane
1500 natural
2½"
2"
2½"
2"
3"
2½"
3"
2½"
3"
2½"
3"
2½"
1500 propane
1750 natural
1750 propane
2000 natural
3"
2½"
3"
2½"
3½"
3"
2000 propane
Metric Equivalent
DISTANCE FROM GAS METER
OR LAST STAGE REGULATOR
SIZE
AND
GAS TYPE
0-31m
31-61m
61-91m
500 natural
3.8cm
2.5cm
5.1cm
3.8cm
5.1cm
3.8cm
500 propane
750 natural
5.1cm
3.8cm
5.1cm
3.8cm
6.4cm
5.1cm
750 propane
1000 natural
5.1cm
3.8cm
6.4cm
5.1cm
7.6cm
6.4cm
1000 propane
SECTION 3.
1250 natural
6.4cm
5.1cm
6.4cm
5.1cm
7.6cm
6.4cm
1250 propane
Gas Supply and Piping
1500 natural
6.4cm
5.1cm
6.4cm
5.1cm
7.6cm
6.4cm
7.6cm
6.4cm
7.6cm
6.4cm
7.6cm
6.4cm
1500 propane
OUTDOOR
COMBUSTION
AIRTERMINAL
OUTDOOR VENT
1750 natural
SIZE
TERMINAL
1750 propane
500
750
20254703
20254705
20254705
D2007700
D2007700
D2007800
D2007800
D2007900
D2007900
D2008000
D2008000
D2008000
D2008000
D2008200
2000 natural
7.6cm
6.4cm
7.6cm
6.4cm
8.9cm
7.6cm
2000 propane
1000
1250
1500
1750
2000
NOTES: 1. These figures are based on 1/2" (0.12kPa) water column
pressuredrop.
2. Check supply pressure and local code requirements
before proceeding with work.
3. Pipe fittings must be considered when determining gas
pipe sizing.
Table 7. Gas Piping Sizes.
Table 6. Vent Terminals for Outdoor Units.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 13
Deluxe appliances are equipped to operate at
elevations up to 10,000 feet (3050m). Brute
Deluxe appliances may be adjusted to operate
properly at altitudes above 2500 feet (see Section
6.6.2) and the input will be reduced if the heating
value of the gas supply is below sea level values.
2. The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas pressure
is 5" W.C. (1.2kPa).
NOTE: The Brute Deluxe appliance and all other gas
appliances sharing the gas supply line must be firing at
maximum capacity to properly measure the inlet supply
pressure. The pressure can be measured at the supply
pressure port on the gas valve. Low gas pressure could
be an indication of an undersized gas meter, undersized
gas supply lines and/or an obstructed gas supply line.
3. Refer to Table 7, size supply.
SECTION 4A.
Water Connections — Boiler
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of the
gas controls.
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa)
static pressure at the boiler.
7. All threaded joints should be coated with piping
compound resistant to action of liquefied
petroleum gas.
8. The appliance and its individual shutoff valve must
be disconnected from the gas supply piping during
any pressure testing of that system at test pressures
in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be leak
tested before placing it in operation.
11. Purge all air from gas lines.
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with this
appliance. Due to expansion and contraction of copper
pipe, consideration should be given to the type of
hangers used. Rigid hangers may transmit noise through
the system resulting from the piping sliding in the
hangers. It is recommended that padding be used when
rigid hangers are installed. Maintain 1" clearance to
combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to a
drain or in a manner to prevent injury in the event of
pressure relief. Install an air purger, an air vent, a
20°F
H/L
25°F
flow
30°F
H/L
35°F
flow
WARNING
Do not use open flame to check for leaks. An open
SIZE
flow
gpm
H/L
flow
H/L
feet
feet
1.7
3.3
5.0
8.1
gpm
34
51
68
85
feet
gpm
feet
0.9
1.7
3.1
4.7
5.5
8.4
gpm
24
36
49
61
73
85
flame could lead to explosion, which could result in
property damage, serious injury or death.
500
750
43
64
85
1.1
2.3
3.6
6.1
28
43
57
71
85
0.7
1.2
2.2
3.4
4.2
5.8
8.3
1000
1250
1500
1750
2000
106
128 10.0 102 7.2
N/R N/R 119 10.5 99
N/R N/R 136 12.5 113 10.4 97
Metric Equivalent
11°C
14°C
flow
lpm
17°C
H/L
19°C
flow
lpm
SIZE
flow
lpm
H/L
m
H/L
m
flow
lpm
H/L
m
m
500
750
1000
1250
1500
1750
2000
161
241
321
401
483
0.5
1.0
1.5
2.5
3.0
129 0.3 107 0.3
92
0.2
193 0.7 161 0.5 138 0.4
257 1.1 214 0.9 184 0.7
322 1.9 269 1.4 231 1.0
386 2.2 322 1.7 276 1.3
N/R N/R 451 3.2 375 2.6 322 1.8
N/R N/R 515 3.8 429 3.2 368 2.5
Notes: gpm = gallons per minute, lpm = liters per minute,
H/L = headloss, ft = headloss in feet, m = headloss in meters.
Maximum temperature rise is 35°F (19°C), as shown. Headloss is
forboiler’sheatexchangeronly. N/R=notrecommended.
Figure 5. Typical Gas Train Configuration.
Table 8. Water Flow Requirements — BMT2H.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 14
diaphragm-type expansion tank, and a hydronic flow
check in the system supply loop. Minimum fill pressure
must be 12psig (82.7kPa). Install shutoff valves where
required by code.
Suggested piping diagrams are shown (see Figures
6 through 14). These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
precautions are made for freeze protection. A non toxic,
heating system, anti-freeze may be added to the hydronic
system provided that the concentration does not exceed
50% and the anti freeze contains an anti foamant. When
a 50/50 mixture is used, increase the water flow
requirements by 15%, and increase the headloss
requirements by 20%.
Power outage, interruption of gas supply, failure of
system components, activation of safety devices, etc., may
prevent a boiler from firing. Any time a boiler is subjected
to freezing conditions, and the boiler is not able to fire, and/
or the water is not able to circulate, there is a risk of
freezing in the boiler or in the pipes in the system. When
water freezes, it expands. This can result in bursting of
pipes in the system, or damage to the boiler, which could
result in leaking or flooding conditions.
IMPORTANT NOTES: Different glycol products may
provide varying degrees of protection. Glycol products
must be maintained properly in a heating system, or they
may become ineffective. Consult the glycol specifications,
or the glycol manufacturer, for information about specific
products, maintenance of solutions, and set up according
to your particular conditions.
4A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet
connection of an automatic fill valve.
2. Install a suitable back flow preventer between the
automatic fill valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a
refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium from
entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air handling
appliances where they may be exposed to refrigerated
air circulation must be equipped with flow control
valves or other automatic means to prevent gravity
circulation of the boiler water during the cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be
provided with a low water cutoff device either as a part
of the boiler or at the time of boiler installation.
SECTION 4B.
Water Connections —
Water Heater
4B.1 Water System Piping —
Water Heater
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with this
appliance. Due to expansion and contraction of copper
pipe, consideration should be given to the type of
hangers used. Rigid hangers may transmit noise through
the system resulting from the piping sliding in the
hangers. It is recommended that padding be used when
rigid hangers are installed.
4A.3 Water Flow Requirements — Boiler
A hydronic heating (closed loop) application re-
circulates the same fluid in the piping system. As a
result, no new minerals or oxygen is introduced into the
system. To ensure a proper operating temperature
leading to long boiler life, a flow rate has been
established based on the fluid temperature rise for this
specific size boiler.
The Brute Deluxe can be used with several different
types of readily available storage tanks. A pump draws
water from the storage tank and pumps the water through
the heater and back into the tank. Pump-mounted units have
a circulating pump built into the water heater. The pumps
used are sized for the headloss through the heater, plus 30
feet (9.1m) of full-sized piping (same size as boiler outlet)
and a normal number of fittings. Pumps used on pump-
mounted unit are sized for soft/normal or hard water, so
make sure a pump-mounted unit matches the water quality
of the installation.
Pump-mounted boilers can be ordered for use in
primary secondary piping systems. The pumps used are
sized for the headloss through the heater, plus 30 feet
(9.1m) of full-sized piping (same size as boiler outlet)
and a normal number of fittings.
Table 8 specifies water flow rates for boilers,
which will enable the user to size a pump. The headloss
shown is for the heater only, and the user will need to
add the headloss of the system piping to properly size
the pump.
The minimum inlet water temperature for the Brute
Deluxe is 120°F (49°C) to avoid condensing on the
copper coils.
Pipe the outlet from the heater’s relief valve such
that any discharge from the relief valve will be
conducted to a suitable place for disposal when relief
occurs. Do not reduce line size or install any valves in
this line. The line must be installed to allow complete
drainage of both the valve and the line.
4A.4 Freeze Protection — Boiler
Boiler installations are not recommended in areas
where the danger of freezing exists unless proper
Suggested piping diagrams are shown in Figures 10
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 15
through 13. These diagrams are meant only as a guide.
Components required by local codes must be properly
installed.
NOTE: These systems are not allowed in the
Commonwealth of Massachusetts.
Piping and components connected to this water
heater for the space heating application shall be suitable
for use with potable water.
Toxic chemicals, such as used for boiler treatment,
shall not be introduced into the potable water used for
space heating.
This water heater when used to supply potable
water shall not be connected to any heating system or
component(s) previously used with a non-potable water
heating appliance.
When the system requires water for heating at
temperatures higher than required for other uses, an
anti-scald mixing or tempering valve shall be
installed to temper the water for those uses in order
to reduce scald hazard potential.
The minimum inlet water temperature for the Brute
Deluxe is 120°F (49°C) to avoid condensing on the
copper coils.
4B.2 Hot Water Supply Piping —
Water Heater
Follow the tank manufacturer’s guidelines for
completion of the hot water system connections.
NOTE: A listed temperature and pressure relief valve
listed as complying with the Standard for Relief
Valves and Automatic Gas Shutoff Devices for Hot
Water Supply Systems (ANSI Z21.22 / CSA 4.4) of
suitable discharge capacity must be installed in the
separate storage tank system.
If the Brute Deluxe water heater is installed in a
closed water supply system, such as one having a
backflow preventer in the cold water supply line, the
relief valve may discharge periodically, due to thermal
expansion. Means (such as a properly-sized expansion
tank) shall be provided to control thermal expansion.
Contact the water supplier or local plumbing inspector
on how to control this situation.
4B.5 Freeze Protection – Water Heater
Although Brute Deluxe water heaters are design-
certified for outdoor installations, such installations are
not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure of
system components, activation of safety devices, etc., may
prevent a heater from firing. Any time a heater is sub-
jected to freezing conditions, and the heater is not able
to fire, and/or the water is not able to circulate, there is
a risk of freezing in the heater or in the pipes in the
system. When water freezes, it expands. This can result in
bursting of pipes in the system, or damage to the heater,
which could result in leaking or flooding conditions.
Contact the local factory representative or for
additionalinformation.
4B.3 Water Flow Requirements —
Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the new
water comes a fresh supply of minerals that can be
deposited on the unit’s heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water
flow requirements for the Brute Deluxe water heater are
based upon the hardness of the water. The water flow is
kept high enough to prevent scaling, but low enough to
prevent tube erosion. For extremely soft or hard water,
cupro-nickel tubes are available. Contact a
Representative if you have questions or concerns about
water quality.
SECTION 5.
Electrical Connections
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and with
latest edition of CSA C22.1 Canadian Electrical Code,
Part 1, in Canada. Do not rely on the gas or water
piping to ground the metal parts of the boiler. Plastic
pipe or dielectric unions may isolate the boiler
electrically. Service and maintenance personnel, who
work on or around the boiler, may be standing on wet
floors and could be electrocuted by an ungrounded
Pump-mounted water heaters can be ordered with
standard pumps for soft or normal water or with pumps
for hard water. The pumps used are sized for the
headloss through the heater, plus 30 feet (9.1m) of full-
sized piping (same size as heater outlet) and a normal
number of fittings.
Table 9 specifies water flow rates for water
heaters, which will enable the user to size a pump. The
headloss shown is for the heater only, and the user will
need to add the headloss of the piping system to
properly size the pump.
boiler.
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
4B.4 Combined Water Heating (potable)
and Space Heating — Water Heater
All electrical connections are made in the field
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 16
Figure 6. Hydronic Piping — Multiple Boilers, Primary Secondary System.
Figure 7. Hydronic Piping — Multiple Boilers, Low Temperature System.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 17
Figure 8. Hydronic Piping — One Boiler, Multi-Temperature System.
Figure 9. Hydronic Piping - Primary-Secondary, Reverse-Return.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 18
Figure 10. Hydronic Piping - Primary-Secondary, Reverse-Return, Low Temperature.
Figure 11. Water Heater Piping — One Heater, One Tank.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 19
Figure 12. Water Heater Piping — Multiple Heaters, One Tank.
Figure 13. Water Heater Piping — One Heater, Multiple Tanks.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 20
Figure 14. Water Heater Piping — Multiple Heaters, Multiple Tanks.
gpm
N
ft
Temp Rise °F
lpm
N
m
N
Temp Rise °C
Size
500
750
1000
1250
1500
1750
2000
S
H
S
N
H
S
N
H
9
S
H
S
H
S
10
16 10
N
7
H
5
8
45
45
45
68
68
68
68
68
68
68
68
68
90
90
90
90
90
90
1.8
2.1
2.3
3.8
3.9
4.0
2.3
3.0
3.6
3.8
3.9
4.0
3.5
6.0
6.1
6.3
6.5
6.7
19 13
170 257 341
170 257 341
170 257 341
257 257 341
257 257 341
257 257 341
424 424 424
0.5 0.7 1.1
0.6 0.9 1.8
0.6 1.1 1.9
1.2 1.2 1.9
1.2 1.2 2.0
1.2 1.2 2.0
3.0 3.0 3.0
28 19 14
38 25 19
31 31 24
38 38 28
44 44 33
30 30 30
21 14 10
17 17 13
21 21 16
24 24 18
17 17 17
112 112 112
10.0 10.0 10.0
NOTES: S = soft water (1 to 7.5 grains hardness).
N = normal water (7.6 to 17 grains hardness).
H = hard water (more than 17 grains hardness).
gpm = gallons per minute; lpm = liters per minute; ft = headloss in feet; m = headloss in meters.
Headloss is for heater's heat exchanger only.
Table 9. Water Flow Requirements — BMT2V.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 21
wiring terminal strip, which is located at the right side of
the appliance.
NOTE: All internal electrical components have been pre-
wired. No attempt should be made to connect electrical
wires to any other location except the wiring box.
NOTE: This pump control is equipped with a delay on
break typically set for 3 minutes, but can be adjusted
between 0.1 and 10 minutes.
Field Interlocks: To install other field-wired
devices to interlock with the boiler (tank stats, louver
switches, flow switches, etc.), remove the jumper
between terminals 3 and 4 and wire the device in series
across these terminals. These terminals are located in
the upper main control panel.
External Control Wiring: These terminals are
located in the upper main control panel (see Section 5.3).
Optional Alarm Contacts: As an option, the Brute
Deluxe is available with an alarm kit. This alarm kit
contains a dry contact for up to 120V which is available
within the 120V field wiring panel. These terminals will be
clearly labeled "Alarm" and are rated up to 10 amps.
5.1 Main Power
The main power requires a 120-volt fused supply that
is connected to the “main power” terminal strip. The over
current protection must be sized as specified ( Figure 15).
The BMT2 pump (pump-mount units) requires a
separate (additional) 120-volt fused supply connected to
the pump terminal strip (also specified in Figure 15).
5.2 Field Wiring
Main Power: The main 120V field wiring panel is
located on the right side of the unit, under the main
power switch. Within this panel are the terminals for
incoming 120V single-phase power clearly labeled on
the right-hand side as “120V (L1)”, “NEUTRAL” and
“GROUND”.
Pump Power: Also located on the 120V field
wiring panel is the pump terminal strip. This strip is
located on the left side (denoted as “120V L2”, “N2
(Pump mounted)” and “GROUND 2 (Pump Mounted)”).
External Pumps: External Pump: All non-pump-
mounted BMT2 units have an internal (dry) contact rated
for 20Amps. A field-supplied pump can be connected
directly to this contact if it does not draw more than 20
Amps. If more current is required, a separate pump
contactor must be installed.
To utilize this internal pump contact, supply 120
volt single-phase power to the terminal marked “120V
(L2)” and supply the pump using the terminal marked
“L2 LOAD (EXT. PUMP)”.
SIZE
500
750
1000
1250
1500
1750
2000
PUMP CIRCUIT MAIN CIRCUIT
15A
15A
15A
15A
15A
15A
20A
15A
15A
20A
20A
20A
20A
20A
Figure 15. Field Wiring.
Figure 16. Brute Deluxe (500–750) Wiring Diagram.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 22
Figure 17. Brute Deluxe (1000) Wiring Diagram.
Figure 18. Brute Deluxe (1250–2000) Wiring Diagram.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 23
Figure 19. Brute Deluxe (500–750) Connection Diagram.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 24
Figure 20. Brute Deluxe (1000) Connection Diagram.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 25
Figure 21. Brute Deluxe (1250–2000) Connection Diagram.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 26
When pressure circuit has been satisfied, proving
combustion air and adequate water flow, the hot surface
igniter will initiate. The ignition control checks that the
igniter current reached a predetermined level then will
dwell momentarily. When dwell time is complete the gas
valve will open.
5.3 External Staging Control Wiring
WARNING
Improper field wiring may result in fire or explosion
which can cause property damage, severe injury, or
death. Make only wiring connections which are in
accordance with the Installation and Operation manual.
After a 4-second trial for ignition, the igniter
switches off. Unless a flame is detected by the flame
sensor (a minimum value of 0.4µA), the gas valve will
close and The ignition module will either attempt
ignition again (up to three times) or will lock out if the
optional lockout ignition module is used.
AVERTISSEMENT
Un câblage incorrect lors de l’installation peut causer
un incendie ou une explosion pouvant entraîner des
dommages matériels, de graves blessures ou la mort.
Ne faire seulement que les connexions conformes au
Manueld’installationetd’exploitation.
If flame is sensed, the burner will continue to fire
as long as there is a call for heat and adequate flame
signal. If there is a subsequent loss of flame signal, the
burner will attempt re-ignition up to three times (only
once if optional lockout ignition is used.) When the call
for heat is satisfied, the gas valves(s) close and the
blowers continues to run for 30 seconds.
If controlling the stages of the BMT2 from an
external source (multiple boiler control, BAS, etc.), wire
Stage 1 to the terminals marked "Input Stage 1" and
"Stage 1", and wire Stage 2 to the terminals marked
"Input Stage 2" and "Stage 2". The "Local/Remote"
selector switch above the terminal strip must be placed
in the "Remote" position for the external controller to
manage the staging.
The pump will continue to run for 0.1 to 10
minutes, depending on what the pump time delay has
been set to. Brute Deluxe sizes 1,000-2,000 have two
ignition controls that control the individual stages. If one
ignition control should fail for any reason, the remaining
module can operate its burners independently. (Note that
if a single blower is disabled on units 1250-2000, the
other fan will continue to operate and safely allow the
boiler to run with a single stage.)
If it is intended to use the BMT2's on-board 2-
stage controller, no extra wiring is necessary. Ensure the
Local/Remote selector switch is in the "Local" position.
SECTION 6.
Operating Instructions
6.2 Filling the System
1. Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to fill slowly.
6.1 Sequence of Operation
Upon initiation of the main power switch, 120V
will be sent to multiple items. Among these are the open
contact fan relays, open contact ignitor relay, open
contact pump relay, ignition control module(s) and open
contact lock out indicators (the optional alarm package
uses this). In addition to these, 24V will travel through
the optional gas pressure switches and optional auto
reset high limit. 24V will then travel through the block
flue switch and the manual reset high limit to the
temperature controller.
2. If make-up water pump is employed, adjust
pressure switch on pumping system to provide a
minimum of 12 psi (81.8 kPa) at the highest point
in the heating loop.
3. If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator to
provide at least 12 psi (81.8 kPa) at the highest
point in the heating loop.
4. Open bleeding devices on all radiation units at the
high points in the piping throughout the system,
unless automatic air bleeders are provided at such
points.
5. Run system circulating pump for a minimum of 30
minutes with the boiler shut off.
Upon a call for heat from the BMT2’s internal
control or an external staging control, 24V travels
through the field interlock (if closed) and then to the
ignition control(s) “T-stat” terminal (500-750 models are
equipped with one ignition control and models 1000-
2000 are equipped with two ignition controls).
When “T-stat” on an ignition control is energized,
its fan will energize and the ignition control will seek
signal from the “pressure circuit”. The pressure circuits
consist of the flow switch and proof of fan.
Sizes 500-1000 calls for fan, fan prove, initiate
pump then prove flow, after which “pressure circuit” has
been satisfied.
Sizes 1250-2000 calls for pump, proof of flow,
initiate fan then prove fan, after which “pressure circuit”
has been satisfied. The fan prove will only occur for the
active stage that has been called.
6. Open all strainers in the circulating system, check
flow switch operation, and check for debris. If debris
is present, clean out to ensure proper circulation.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank
should not exceed ¼ of the total, with the balance
filled with air.
9. Start up system according to the procedure in this
manual. Operate the entire system, including the
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 27
pump, boiler, and radiation units for one (1) hour.
10. Recheck the water level in the expansion tank. If
the water level exceeds ¼ of the volume of the
expansion tank, open the tank drain, and drain to
that level.
Because the Brute Deluxe controller senses inlet
water and the manual reset high limit senses outlet water,
the high limit should be set 40-50°F higher than the
controller, to avoid nuisance lockout of the manual reset
highlimit.
11. Shut down the entire system and vent all radiation
units and high points in the system piping, as
described in Step 4.
6.4 External Boiler Operations
If controlling the stages of the BMT2 from an
external source (multiple boiler control, BAS, etc) the
"Local/Remote" selector switch above the terminal strip
must be placed in the "Remote" position. In this mode,
the controller that is mounted on the BMT2 will no
longer have control of the unit. The 24V from the unit
waits at the input terminal, and the external control
switches this 24V from the input terminal to the stage
terminal.
12. Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.
13. Check gauge for correct water pressure and also
check water level in the system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.
14. Refer to local codes and the make-up water valve
manufacturer’s instructions as to whether the make-
up water valve should be left open or closed.
15. After placing the unit in operation, the ignition
system safety shutoff device must be tested. First,
shut off the manual gas valve, and call the unit for
heat. After the pre-purge and ignitor heat-up time,
the main gas terminals will be energized, attempting
to light, for four (4) seconds, and then will de-
energize. The unit will go into lockout mode.
Second, turn the power off and then on again, open
the manual gas valve and allow the unit to light.
While the unit is operating, close the manual gas
valve and ensure that power to the main gas valve
has been cut.
6.5 Limit Controls
The manual reset high limit control is provided as
standard equipment on all heaters. An additional
automatic reset switch is optional.A high limit
temperature-sensing bulb is always located in the heater
outlet. Burners will automatically shut down whenever
overheating occurs.
6.6 Operating the Burner and Set Up
6.6.1 Set Up for 0 to 2500 Feet Altitude
The Brute Deluxe appliance utilizes a modular
16. Within three (3) days of start-up, recheck all air
bleeders and the expansion tank as described in
Steps 4 and 8 above.
Important: The installer is responsible for identifying to
the owner/operator the location of all emergency shutoff
devices.
WARNING
Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance
and to replace any part of the control system and any
gas control that may have been
under water.
6.3 Operating Temperature Control
All Brute Deluxe's are equipped with a two-stage
aquastat. To utilize this mounted controller be sure to
have the "Local/Remote" selector switch to "Local". Set
the controller to the desired operating set point. The
controller has an interstage differential that can be
adjusted from 3°F to 10°F. This allows the user to have
some control over how stage 2 and stage 1 call for heat
(see Figure 22).
1
Difference between the temperatures at which the two switches
*
make R-W. Adjustable from 3°F to 10°F (1.7°C to 5.6°C) on standard
models, or from 3.6°F to 12°F (2.0°C to 6.7°C); 55°F to 175°F (13°C
to 79°C) models.
2 Two DPDT switches operate in sequence. Each switch
differential is fixed at approximately 3°F (1.7°C) on standard models,
or 3.6°F (2.0°C); 55°F to 175°F (13°C to 79°C) models.
*
Figure 22. Honeywell L8008G.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 28
design to achieve its stage-firing. The setup must be
checked before the unit is put in operation. Problems
such as failure to start, rough ignition, strong exhaust
odors, etc. can be due to improper setup. Damage to the
Brute Deluxe resulting from improper setup is not
covered by the limited warranty.
light the main burners for that stage, the second ignition
control will still be active, and will be able to energize
stage 2. This, of course, will only occur upon call for
stage 2 and if all other safety devices confirm that the
unit will run in a safe condition.
1. Using this manual, make sure the installation is
complete and fully in compliance with the
instructions.
6.6.2 HighAltitudeAdjustmentandSetUp
Brute Deluxe appliances may be operated at high
altitude (7700 ft., 2347 m) with a reduction in output of
approximately 10%. At altitudes of less than or more than
7700 ft. (2347 m) the appliance will perform equally as
well, but with differing reductions in output. At elevations
higher than 7700 ft. (2347 m) the reduction in output will
exceed 10% and at elevations below 7700 ft. (2347 m) it
will be less than 10%. High altitude adjustment must not be
made on appliances operating at elevations below 2500 ft.
(762 m).
2. Determine that the appliance and system are filled
with water and all air has been bled from both.
Open all valves.
3. Observe all warnings on the Operating Instructions
label and turn on gas and electrical power to
appliance.
4. Switch on the appliance power switch located on
the right side of the unit.
5. The Brute Deluxe will enter the start sequence, as
long as the unit is being called for heat. The blower
and pump come on for pre-purge, then the ignitor
warm-up sequence starts and after the ignitor
warm-up is complete and all safety devices are
verified, the gas valves open. If ignition doesn’t
occur, check that there is proper gas supply. Wait 5
minutes and start the unit again. During initial start
up, air in the gas line may cause the Brute Deluxe
to "lock out" during the first few trials for ignition.
Depending on the ignition modules installed, the
manual reset button on the ignition modules may
need to be depressed to restart the Brute Deluxe.
6. When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not
exceed 13" W.C. (3.2kPa). The minimum inlet gas
pressure is 5" W.C. (1.2kPa).
No orifice changes are required to adjust the Brute
Deluxe appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the gas
valve manifold pressure and the air shutter(s). The
required instruments used to assist in these adjustments
are a CO2 or O2 Analyzer and a U-Tube Manometer or
other device capable of reading a pressure of 2.5-3.0
inches W.C. (0.62-0.75 kPa).
Start the adjustment process by checking the CO2
in the “as installed” condition. Adjust the air shutter(s)
so that the CO2 is about 8% or the O2 is about 6.8% for
appliances operating on Natural Gas. For appliances
operating on LP Gas adjust the air shutter(s) so that the
CO2 is about 9.2% or the O2 is about 6.8%. Appliances
with two blowers should be adjusted so that the air
shutters below each blower are open the same amount.
Once the CO2 or O2 has been set, the manifold
pressure may be adjusted. Remove the 1/8 NPT plug
from the lower side of the gas valve that is to be set and
install a fitting, hose and manometer. Start the appliance
and observe the manifold pressure. Manifold pressure
must be adjusted to 3.0 in. W.C. (0.75 kPa) (for high
altitude only, standard operating pressure is 2.5 in. W.C.
(0.62 kPa)). It is adjusted by removing the slotted cap on
the gas valve and turning the adjustment screw (beneath
the cap) clockwise to increase pressure and replaced
after the adjustments have been completed and the
fitting, hose and manometer have been removed and the
1/8" plug has been replaced. Repeat this process until all
gas valves have been set. Note: The pressure can be set
only when the appliance is operating and only when the
particular gas valve being adjusted is energized by a call
for heat from the staging control.
7. Once the inlet gas pressure is verified, the outlet
gas pressure from each valve (manifold gas
pressure) must be checked, and adjusted, if
necessary. The manifold gas pressure must be 2.5"
W.C. (0.62kPa).
2
8. Complete the setup by checking the CO at the
2
outlet of the unit. The CO should be 8% for
natural gas, or 9.2% for propane.
9. After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested.
(a) Close gas shutoff valve with burner operating.
(b) The flame will go out and blower will
continue to run for the post purge cycle. One
additional attempt to light will follow. Ignition
will not occur as the gas is off. The ignition
control will lockout, and will have to be reset
before the unit will operate.
After all of the gas valve manifold pressures have
been set, the CO2 or O2 must be reset. CO2 or O2 will
have changed when the manifold pressure was adjusted.
Open the air shutter(s) to reduce the CO2 or O2 to the
values achieved previously.
The procedure is complete when all gas valves are
adjusted to a manifold pressure of 3.0 in. W.C. (0.75
kPa) and the CO2 is adjusted to 8.0% for Natural Gas
(c) Open gas shutoff valve. Restart the appliance.
The ignition sequence will start again and the
burner will start. The appliance will return to
its previous mode of operation.
NOTE: Unit sizes 1000–2000 have two ignition controls
and two ignitors, which work independently of one
another. If the ignition control for stage 1 fails to properly
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 29
appliances or 9.2% for LP appliances (to be checked
only at full fire). When using an O2 analyzer, the correct
O2 is 6.8% for both Natural Gas and LP appliances.
protected from freezing.
6. Low water cutoffs, if installed, should be checked
every 6 months. Float type low water cutoff should
be flushed periodically.
7. Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages
indicates improper combustion. Determine the
cause and correct.
8. Inspect the vent system and air intake system, and
if the vent system is Category III, ensure that all
joints are sealed properly. If joints need to be
resealed, completely remove existing sealing
material, and clean with alcohol. Apply new sealing
material, and re-assemble.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a normal
manner, close main shutoff valve, do not shut off
switch, and contact your heating contractor, gas
company, or factory representative.
6.7 Shutting Down the Brute Deluxe
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Brute Deluxe and
be sure to also protect building piping from freezing.
This step to be performed by a qualified service
person.
7.2 Appliance Maintenance and
Component Description
Only genuine replacement parts should be used.
Caution
6.8 To Restart the Brute Deluxe
If drained, follow Section 6.2 in this manual for
proper filling and purging.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dan-
gerous operation. Verify proper operation after servicing.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
See Figure 5 for location of gas train components.
The gas and electric controls on the appliance are
engineered for long life and dependable operation, but
the safety of the equipment depends on their proper
functioning. It is strongly recommended that a qualified
service technician inspect the basic items listed below
every year.
4. Set the aquastat or thermostat to its lowest setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch, manual
reset high limit, etc.).
7. Set the temperature controller to the desired
temperature setting and switch on electrical power.
8. Burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.
a. Ignitioncontrols
b. Ignitors
c. Water temperature control
d. Automatic gas valve
e. Pressure switches
SECTION 7.
Maintenance
f.
Blowers
7.2.1 Burners
7.1 System Maintenance
Close main manual gas valve before proceeding.
Checking the burners for debris - Remove the ignitor
inspection panels(s) and ignitor(s) and inspect the burners
through the ignitor hole(s) using a flashlight to illuminate.
If there is any indication of debris on the burners that are
visible, all the burners will need to be inspected more
thoroughly. Remove the screws from around the front of
the air box (large panel from which the ignitor inspection
panel(s) were removed), and remove the large panel.
Remove the gas manifold assemblies and the burner
panels. Inspect the burners. Clean burners, if necessary,
by blowing compressed air from the outside of the
burners into the center of the burner. A dirty burner may
be an indication of improper combustion or dirty
combustion air. Determine the cause, and correct.
Replace the burners in the reverse order
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean the
screens in the vent terminal and combustion air
terminal (when used).
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 30
7.2.2 Filter
7.2.7 Ignitors/Sensor
The filter used in the Brute Deluxe is washable
with an 83% arrestance. Since the filter is washable, it
will only need replacement when unwashable,
deteriorated or damaged. If filter replacement is needed,
it should only be replaced with a factory part. Inspect the
air filter. If there is debris on the air filter, remove it from
the filter box, and wash it with mild soap and water.
Ensure that the filter is completely dry before re-
installing, in reverse order.
The ignitor/sensor used are 120v "hot surface"
type. They are energized whenever there is a call for
heat and switched off when ignition is established and
flame has been sensed. Brute Deluxe sizes 500 and 750
have one ignitor/sensor. Sizes 1000 to 2000 have two
ignitor/sensors. To replace the ignitor/sensor, shut off the
120-volt power to the appliance, remove the ignitor
access panel, disconnect the Molex connector, remove
the two mounting screws on the ignitor/sensor flange and
pull the ignitor out. ((Hot Surface) Ignitor and the Flame
Sensor are the same items). Install in reverse order,
always using a new ignitor gasket with the replacement
ignitor.
7.2.3 Gas Valves
The gas valves are designed to operate with supply
pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).
To remove a valve, shut off 120-volt power and the
manual gas shutoff valve. Remove the top front panel from
the unit. Disconnect the wires to the valve. Disengage the
flanged fitting before and after the valve, and remove the
valve. Re-install in reverse order. Ensure o-rings are
properly installed for both inlet and outlet. Turn on manual
gas shutoff valve and 120 volt power and check appliance
operation and tightness of gas valve connections.
Caution
Ignitor gets hot.
7.2.8Transformer
The transformer is not capable of supplying control
voltage for external devices such as zone valves, which
must have their own separate power supply. Should a
transformer need replacing, shut off the 120-volt power.
Unplug the transformer wires, remove the mounting
screws and remove the transformer. Replace transformer
in the reverse order.
7.2.4 ManualResetHighLimitControl
The high limit switch is manual reset switch with an
adjustable set point, up to 240°F (116°C) on boiler
models and 200°F (93°C) on water heater models and
boilers ordered with low temperature controls. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull the
switch off the control panel. Remove the capilliary and
bulb from the thermal well located in the header.
Replace in reverse order.
7.2.9 Blowers
The combustion air blowers bring the combustion
air for the Brute Deluxe from the upper chamber to the
lower chamber. Mixing of the gas and air occurs in the
burners. Sizes 500, 750 and 1000 each have one blower,
and sizes 1250 to 2000 each have two blowers. If a
blower change is required, turn off the 120-volt power
and gas supply to the unit. Remove the front panel.
Disconnect the blower's wire harness. Remove the
screws at the blower flange, and pull the blower out.
Replace blower in reverse order, ensuring that all joints
are made correctly. After replacement, ensure that the
unit operates properly, by following the set-up procedure
in this manual.
7.2.5 TemperatureControl
The temperature control is a Honeywell L6008. To
replace the control, shut off the 120-volt power to the
appliance. Remove the cover from the control panel, and
remove the mounting screws to remove the controller.
Replace in reverse order.
7.2.6 IgnitionControls
7.2.10 Flow Switch
The ignition controls ensure the proved interrupted-
type ignition system. They control the hot surface
ignitors and prove that the flame signal is appropriate for
powering the gas valves. It also controls the blower’s
pre-purge and post-purge. Brute Deluxe sizes 500 and
750 have one ignition control. Sizes 1000 to 2000 have
two ignition controls. On sizes up to 750, one ignition
control controls stages 1 and 2. On unit sizes 1000–
2000, one ignition control is for stage 1, and the other is
for stage 2.
To replace a control, shut off the 120-volt power to
the appliance. Remove the cover from the control panel.
Remove the electrical connectors from the ignition control.
Take out the controller’s mounting screws, and pull the
controller out. Replace in reverse order.
The Brute Deluxe uses a paddle-type flow switch
to ensure that the unit has water flow before ignition is
allowed.
7.2.11 Heat Exchanger Coil
WARNING
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame, thereby
creating a risk of fire or explosion.. To prevent this
from happening, dampen the soot deposits with a wet
brush or fine water spray before servicing the heat
exchanger.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 31
The Brute Deluxe has a pre-mixed burner system.
These systems provide the burners with sufficient air for
complete combustion, and black carbon sooting is
seldom experienced. If sooting is suspected, view ports
for inspection of the heat exchanger are provided on the
right side of the boiler. They are located below the
headers, and are accessed by opening the small round
cover that is attached by one screw. In the unlikely event
that there is a buildup of black carbon soot or other
debris on the heat exchanger, clean per the following:
flow. If the tubes show signs of scaling, clean the
internal surface. offers a tube cleaning kit, part
number R0010000.
11. Reassemble in the reverse order, and check
appliance operation after start-up.
NOTE: The Warranty does not cover damage caused
by lack of required maintenance, lack of water flow,
or improper operating practices.
1. Disconnect the electrical supply to the unit.
SECTION 8.
2. Turn off the gas supply by closing the manual gas
Trouble Shooting
valve on the heater.
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
8.1 Resolving Lockouts
There are many causes of lockouts. The three most
common causes are: (1) inadequate gas supply, (2) poor
combustion, (3) ignitor failure.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header flanges from the inlet and
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP tank
(LP boilers) is not empty. Then, restart the boiler and
observe the operational cycle. After a 15-second fan
pre-purge, the ignitor will heat up for 20 seconds, and
then the unit will light. If it does not, check the gas
supply pressure to the appliance, after resetting the
appliance and attempting another start-up. The gas
pressure to the appliance must be above 5" W.C.
(1.2kPa) throughout the entire start-up cycle. If it is
not, correct the supply problem (check gas valves or
supply piping). If the supply pressure is adequate,
consult the factory for assistance.
outlet.
6. Allow the heat exchanger to drain. Remove the
front cover(s) by removing the rubber access
strip(s) and the retaining screws. Remove the
venting and remove the top, by removing the
screws that attach the top to the side panels.
Remove the side panels. Remove the front lower
panels sealing the combustion area. To remove the
gas train, disconnect the unions located below the
intermediate pan and the field installed union
located outside the cabinet, and pull up, bringing
the union end connectors through the grommets in
the intermediate pan. To remove the intermediate
pan, remove the slide out control assembly and
blower(s) to reveal the screws. Remove the screws
holding the intermediate pan, and lift up to remove
it. The heat exchanger has integral metal sections
attached, which connect to the frame of the boiler.
Locate and remove the screws along the front, rear
and bottom of the integral metal sections, and
remove the heat exchanger and metal sections by
lifting up. On the larger appliances, a center heat
exchanger support must be unbolted before it can
be removed.
7. Remove the heat exchanger from the unit. Note:
The heat exchangers are heavy and may require
two people to remove to avoid personal injury.
8. Clean the heat exchanger: A light accumulation of
soot or corrosion on the outside of the heat exchanger
can be easily removed. Use a wire brush to remove
loose soot and scale from the heat exchanger. Do not
use water or compressed air for cleaning.
9. Note: While the heat exchanger is out of the unit,
inspect the firewall refractory insulation. Replace if
necessary.
10. Inspect the inside of the copper tubes for scale
buildup. Scale can build up on the inner surface of
the heat exchanger tubes, which can restrict water
2. Poor combustion: Poor combustion should be
suspected if there is a strong flue gas odor. The
odor may result from an improper gas/air ratio
(high or low O2 or CO2). Brute Deluxe appliances
operate best with 45% excess air (8% CO2 on
natural gas, 9.2% CO2 on LP). Check the CO2 of
the appliance and adjust if necessary.
3. Ignitor failure: If the boiler goes through a normal
start cycle but combustion does not occur, ignitor
failure should be suspected. Check the ignitor by
unplugging the ignitor plug and measuring the
ignitor resistance. It should be 50-80 ohms at room
temperature. If the resistance is not 50-80 ohms,
replace the ignitor. If the resistance is correct, reset
the boiler and check for 120 VAC at the ignitor
plug during the start cycle. If there is no voltage,
replace the faulty ignitor wire harness or the
ignitioncontrol.
8.2 Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition. If
the gas supply pressure is proper and the gas valves are
functioning properly, then burners should be inspected.
There should be no distortion or perforations in the
burners outside of the active burner port area. Replace if
indicated.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 32
8.3 Short Cycling — Boiler
SECTION 9.
Because the Brute Deluxe is a stage-fired boiler,
and its input will decrease when there is a reduction in
heating load, short cycling is greatly reduced. If the
heating load drops below the minimum input of the
boiler for an extended period, the boiler will have a
tendency to short cycle. This can be a symptom of
improper control strategy or setpoints, or a load
distribution problem. Contact your representative to
discuss possible remedies.
Replacement Parts
Only genuine replacement parts should be used.
9.1 General Information
To order or purchase parts for the Brute Deluxe,
contact your nearest dealer or distributor. If they cannot
supply you with what you need, contact Customer
Service (see back cover for information).
9.2 Parts List - see next page.
8.4 Short Cycling — Water Heater
Short cycling will generally occur only in
combination space heating and water heating
applications when the water heater is operating in the
space-heating mode. Because the Brute Deluxe is a
stage-fired water heater and its input will reduce when
there is a reduction in heating load, short cycling is
greatly reduced. If the heating load drops below the
minimum input of the water heater for an extended
period, the water heater will have a tendency to short
cycle. If short cycling is frequently experienced,
regardless of the control’s attempt to limit it, the heating
load should be redistributed to control it.
If short cycling occurs in a water heater application,
it is probably caused by undersized piping between the
water heater and the storage tank or by some other factor
that restricts proper water flow through the water heater.
The cause should be determined and corrected.
8.5 High Gas Consumption
Appliances operating with an improper air/fuel
ratio are very inefficient and consequently, have very
high gas consumption. Because efficiency is high when
the CO2 is high (or O2 is low), appliances operating with
low CO2 or high O2 (especially LP appliances) consume
more gas. Adjust the CO2 or O2 for optimum efficiency.
If no combustion analyzing equipment (CO2 or O2) is
available then a proper adjustment of the air/fuel ratio
(CO2 or O2) cannot be accomplished. However, by
briefly sniffing the flue gases it is possible to determine
if the CO2 or O2 is within the proper range. No
significant flue gas odor should be detected when
combustion is proper. A strong piercing smell indicates
poor combustion and generally a lean mixture - low CO2
or high O2 . The CO2 should be 8% at high fire. To check
the CO2, first verify that the supply gas pressure is
within 5" to 13" w.c. (1.2 to 3.2 kPa) With the Brute
Deluxe running with all stages firing, set the air box
pressure to 1.5" w.c. (0.37 kPa) (as a starting point), by
adjusting the air shutter(s) at the bottom of the fan(s).
Check the CO2, and adjust the air shutters if further
adjustment to the CO2 is needed. Sizes 1250 to 2000
have two blowers and two air chambers (boxes). The
pressure of each air box must be equal when the final
adjustment is made.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 33
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 34
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 35
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 36
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 37
Figure 23. Sheet Metal Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 38
Figure 24. Internal Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (500-2000)
Page 39
Brute Deluxe Water Heater
Brute Deluxe Hydronic Boiler
Size
Pump p/n
Size
500
750
1000
1250
1500
1750
2000
Pump p/n
A2001700
A2001700
A2001800
A2001800
A2001900
A2001900
A2109700
Soft Water
A2001700
A2001700
A2001700
A2001700
A2001700
A2001900
A2109700
Normal Water
A2001700
A2001700
A2001800
A2001800
A2001900
A2001900
A2109700
Hard Water
A2001900
A2001900
A2001900
A2001900
A2001900
A2001900
A2109700
500
750
1000
1250
1500
1750
2000
Figure 25. Heat Exchanger Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 40
Figure 26. Electrical Components.
Bradford White Company reserves the right to change specifications, components, features, or to discontinue products without notice.
Ambler, PA19002
Tech. Service (800) 334-3393
Service Parts (800) 538-2020
Warranty Service (800) 531-2111
Litho in U.S.A. © Bradford White 1102 Document 1245
Download from Www.Somanuals.com. All Manuals Search And Download.
|