AMABILIA Vacuum Cleaner DORFC 1 User Manual

DOUBLE O-RING  
GEOTHERMAL  
FLOW CENTERS  
INSTALLATION  
INSTRUCTIONS  
Models: DORFC-1 DORFC-2  
DORFC-1  
DORFC-2  
WARNING: After flushing is complete, but prior to pump motor start-up, loosen the large screw in  
the center of the pump motor(s) to allow air to escape. Once water has seeped out around the screw,  
re-tighten. Failure to perform this step will likely result in premature pump motor failure!  
PUMP MOTOR REPLACEMENT: Bard Part #8300-003 (UP26-99F)  
Manual:  
2100-518B  
Supersedes: 2100-518A  
BMC, Inc.  
Bryan, Ohio 43506  
File:  
Volume I, Tab 8  
Date:  
04-23-12  
Page  
1 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GettinG Other infOrmatiOn and PublicatiOns  
These publications can help you install the air  
conditioner or heat pump. You can usually find these  
at your local library or purchase them directly from the  
publisher. Be sure to consult current edition of each  
standard.  
fOr mOre infOrmatiOn, cOntact  
these Publishers:  
ACCA  
Air Conditioning Contractors of America  
1712 New Hampshire Avenue  
Washington, DC 20009  
National Electrical Code.......................ANSI/NFPA 70  
Telephone: (202) 483-9370  
Fax: (202) 234-4721  
Standard for the Installation...............ANSI/NFPA 90A  
of Air Conditioning and Ventilating Systems  
ANSI  
American National Standards Institute  
11 West Street, 13th Floor  
New York, NY 10036  
Standard for Warm Air.......................ANSI/NFPA 90B  
Heating and Air Conditioning Systems  
Telephone: (212) 642-4900  
Fax: (212) 302-1286  
Load Calculation for Residential ......ACCA Manual J  
Winter and Summer Air Conditioning  
ASHRAE American Society of Heating Refrigerating,  
and Air Conditioning Engineers, Inc.  
1791 Tullie Circle, N.E.  
Duct Design for Residential..............ACCA Manual D  
Winter and Summer Air Conditioning and Equipment  
Selection  
Atlanta, GA 30329-2305  
Telephone: (404) 636-8400  
Fax: (404) 321-5478  
Closed-Loop/Ground Source Heat Pump ........IGSHPA  
Systems Installation Guide  
NFPA  
National Fire Protection Association  
Batterymarch Park  
P.O. Box 9101  
Quincy, MA 02269-9901  
Telephone: (800) 344-3555  
Fax: (617) 984-7057  
Grouting Procedures for Ground-Source.........IGSHPA  
Heat Pump Systems  
Soil and Rock Classification for ......................IGSHPA  
the Design of Ground-Coupled Heat Pump Systems  
IGSHPA International Ground Source  
Heat Pump Association  
Ground Source Installation Standards .............IGSHPA  
490 Cordell South  
Stillwater, OK 74078-8018  
Closed-Loop Geothermal Systems ..................IGSHPA  
– Slinky Installation Guide  
Manual 2100-518B  
Page 3 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GeOthermal flOw centers nOmenclature  
DORFC  
2
Double  
O-Ring  
Flow  
Center  
1 = 1-Pump Version, 208/230V, 60 Hz, 1-phase, 22’ HD @ 16 GPM  
2 = 2-Pump Version, 208/230V, 60 Hz, 1-phase, 44’ HD @ 16 GPM  
warninG  
flOw center descriPtiOn  
Indicates a potentially hazardous situation which, if not  
avoided, will result in death or serious injury.  
The DORFC Series Flow Centers are a compact, easy to  
mount polystyrene cabinet that contains 3-way valves and  
pump(s) with connections for flushing, filling and pumping  
fluids for geothermal closed loop systems. The proven  
design is foam insulated to prevent condensation and full  
flow service valves minimize pressure drop.  
cautiOn  
Indicates a potentially hazardous situation or an unsafe  
practice which, if not avoided, could result in minor or  
moderate injury or product or property damage.  
One or two Grundfos pump models UP26-99 are available  
based upon flow requirements and loop design.  
Unit and loop connections are designed for double o-ring  
fittings with several varieties of connections available  
(fusion, threaded, barbed and sweat). Pump motor(s) are  
230VAC, 60 Hz, 1-phase.  
nOtice  
Notification of installation, operation or maintenance  
information, which is important, but which is not hazard-  
related.  
An attractive light gray polystyrene cabinet (that matches  
geothermal unit) with black pump(s) provides an  
aesthetically pleasing enclosure for pump(s) and valves.  
warninG  
safety  
Failure to do so could cause property  
damage, bodily harm or death.  
Warnings, cautions and notices appear throughout this  
Manual. Read these items carefully before attempting any  
installation, service or troubleshooting of the equipment.  
danGer  
Indicates an immediate hazardous situation which, if not  
avoided, will result in death or serious injury. DANGER  
labels on unit access panels must be observed.  
cautiOn  
Failure to do so could cause property  
damage, bodily harm or death.  
Manual 2100-518B  
Page  
4 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flOw center PerfOrmance  
FIGURE 1A  
PERFORMANCE MODEL DORFC-1 FLOW CENTER  
35  
30  
25  
20  
15  
10  
5
0
0
5
10  
15  
20  
25  
30  
35  
Flow (GPM)  
FIGURE 1B  
PERFORMANCE MODEL DORFC-2 FLOW CENTER  
70  
60  
50  
40  
30  
20  
10  
0
0
5
10  
15  
20  
25  
30  
35  
Flow (GPM)  
Manual 2100-518B  
Page 5 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
dimensiOnal drawinG  
fiGure 2  
flOw center dimensiOns  
F
G
A
D
H
C
B
TYPE  
DORFC-1  
DORFC-2  
SHIPPING WEIGHT  
26 LBS  
A
B
10.3  
26.2  
C
7.5  
19.1  
D
12.4  
31.5  
E
2.0  
5.1  
F
2.6  
6.7  
G
5.0  
12.7  
H
4.7  
11.4  
INCHES 13.5  
31 LBS  
CM  
34.3  
MIS-2658  
Manual 2100-518B  
Page 6 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flOw center mOuntinG  
cautiOn  
The following instructions represent  
industry accepted installation practices for  
closed-loop earth coupled (ground loop)  
installations. Instructions are provided to  
assist the contractor in installing trouble  
free ground loops. These instructions are  
recommendations only. State/provincial and  
local codes MUST be followed and installation  
MUST conform to ALL applicable codes. It is  
the responsibility of the installing contractor  
to determine and comply with ALL applicable  
codes and regulations.  
nOtice  
side Of unit  
The Flow Center must be mounted with the pump shaft in  
the horizontal position. In other words, it should always be  
mounted in a vertical position (not on its back or mounted to  
the ceiling). See Figure 3.  
Mounting on the side of the unit is possible, but  
not necessarily recommended because it can inhibit  
serviceability and also lead to vibration of the sheet  
metal casing. It could also lead to puncturing an internal  
refrigerant or water pipe. If necessary, however, the flow  
center can be mounted to the sheet metal casing utilizing  
four (4) self-drilling screws. (Pay close attention not to  
puncture internal components.)  
The pump should be located as close to the unit as possible  
to limit the length of rubber hose kit or interconnect piping  
and thus its associated pressure drop.  
stud wall  
Mounting on stud wall with or without drywall can be  
accomplished by using two (2) lag bolts through the top and  
bottom center holes directly into the stud. See Figure 4A.  
cOncrete/masOnry wall  
Mounting onto a concrete wall can be accomplished  
typically using four (4) 1/4" diameter tapcon cement screws  
in the four (4) outer corner mounting holes. See Figure 4B.  
Manual 2100-518B  
Page  
7 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 3  
PumP hOrizOntal aPPlicatiOns  
OK  
IMPELLER SHAFT  
HORIZONTAL  
OK  
IMPELLER SHAFT  
HORIZONTAL  
NO  
IMPELLER SHAFT  
CAN NOT BE  
VERTICAL  
MIS-2659  
Manual 2100-518B  
Page 8 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 4  
mOuntinG  
FIGURE 4A  
Studded Wall Mounting  
1/4" LAG BOLTS  
DIRECTLY INTO STUD  
FIGURE 4B  
Masonry Wall Mounting  
1/4" TAPCON SCREWS  
MIS-2660  
Manual 2100-518B  
Page  
9 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PiPinG installatiOn  
NOTE: Apply petroleum jelly to O-Rings to prevent  
damage and aid in insertion.  
The Flow Center features Double O-Ring fittings for  
installation flexibility and ease of installation – maintaining  
a reliable connection. Table 1 illustrates the connection  
options available for Flow Centers. Pressure drop in  
piping systems should be calculated to ensure adequate  
flow through the unit. All piping should be properly  
insulated with closed cell insulation of 1/2" wall thickness.  
Piping insulation should be glued and sealed to prevent  
condensation using closed cell insulation glue. The swivel  
connectors on the flow center and at the unit are designed  
to be hand-tightened only.  
Loop side piping is typically polyethylene piping directly into  
the flow center. Connection to the flow center can be made  
with either a fusion or barbed fitting as shown in Table 1.  
Connection between the flow center and the geothermal  
heat pump typically would be made using the hose kit  
(DORLFCK-1), which contains all fittings necessary for  
connection between the heat pump and the flow center as  
shown in Figure 5. Other variety of materials may also be  
used for this connection - such as PE or copper piping.  
table 1  
description  
Part number  
DORF125-S  
DORLFCK-1  
DORB1-S-4HC  
DORMP1-S  
DORFP1-S  
1-1/4" PE Fusion X Double O-Ring  
Double O-Ring Loop Flow Center Kit  
1" Barb X Double O-Ring (includes {4} hose clamps)  
1" MPT X Double O-Ring  
1" FPT X Double O-Ring  
1" Copper Sweat X Double O-Ring (includes {2} P/T fittings)  
DORS1-S  
1" Hose Barb X Double O-Ring 90° Elbow (includes {4} hose clamps and {2} P/T fittings)  
1" MPT X Double O-Ring, 90° Elbow (includes {2} P/T fittings)  
Quick Connect Cam Lock X Double O-Ring 90° Elbow  
DORB1-90-4HC  
DORMP1-90  
DORCL1-90  
DORGHMT  
Male Garden Hose Thread X Double O-Ring (1-piece per box)  
NOTE: All fittings boxed in pairs (2-pieces each) will exception of DORGHMT.  
1" hose barb X  
double O-ring  
1-1/4" socket fusion X  
double O-ring  
1" mPt X double O-ring  
dOrmP1-s  
dOrb1-s-4hc  
dOrf125-s  
Manual 2100-518B  
Page  
10 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PiPinG installatiOn (cOntinued)  
1" copper sweat X double O-ring with 1/4"  
fPt Port & Pressure/temperature test Plugs  
elbow, 1" hose barb X double  
O-ring with 1/4" Port and Pressure/  
temperature test Plugs  
1" swivel X double O-ring  
dOrfP1-s  
dOrs1-s  
dOrb1-90-4hc  
elbow, 1" mPt X double  
O-ring with 1/4" Port and  
1" cam lever male X  
double O-ring  
Garden hose male X O-ring  
(single) adapter  
Pressure/temperature test Plugs  
dOrcl1-90  
dOrGhmt  
dOrmP1-90  
NOTES:  
1.  
2.  
Apply petroleum jelly to O-Rings to prevent damage and aid in insertion.  
Use two (2) stainless steel clamps per connection (included quantities of hose clamps with fittings and hose kits are  
per this recommendation).  
3.  
Adaptors required from 1" MPT, 1" FPT, Copper, etc. provided by others.  
Manual 2100-518B  
Page 11 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 5a  
flOw center cOnnectiOn tO GV series mOdel  
PIPE TO GROUND LOOP  
PIPE FROM  
GROUND LOOP  
PUMP  
MODULE  
OPTIONAL VISUAL  
FLOW METER  
NOTE: IF USED  
STRAIGHT BARBED  
BRASS ADAPTERS  
SUPPORT WITH A  
FIELD-FABRICATED  
WALL BRACKET  
WATER IN  
WATER OUT  
NOTE: APPLY PETROLEUM JELLY  
TO O-RINGS TO PREVENT DAMAGE  
AND AID IN INSERTION.  
HOSE CLAMPS  
1" FLEXIBLE HOSE  
MIS-2621 A  
multiPle unit tO sinGle lOOP  
cOnnectiOn  
In instances where multiple units are connected to a singular  
loop, our recommendation is to apply a flow center to each  
individual system with full-port balancing valves installed  
on each unit. See Figure 6.  
Manual 2100-518B  
Page  
12 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 5b  
flOw center cOnnectiOn tO Gt series mOdel  
PIPE TO  
GROUND LOOP  
PIPE FROM  
GOUND LOOP  
PUMP MODULE  
STRAIGHT BARBED  
BRASS ADAPTERS  
OPTIONAL VISUAL  
FLOW METER  
NOTE: IF USED SUPPORT  
WITH A FIELD FABRICATED  
WALL BRACKET  
HOSE CLAMPS  
1" FLEXIBLE HOSE  
NOTE: APPLY PETROLEUM JELLY  
TO O-RINGS TO PREVENT DAMAGE  
AND AID IN INSERTION  
WATER OUT  
WATER IN  
MIS-2827 A  
Manual 2100-518B  
Page  
13 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 5c  
flOw center cOnnectiOn tO Qw series mOdel  
FLEXIBLE HOSE  
PUMP MODULE  
(See Spec Sheet  
for Model No.)  
PIPE FROM  
GROUND LOOP  
PIPE TO  
GROUND  
LOOP  
NOTE: Apply petroleum  
jelly to o-rings to prevent  
damage and aid in insertion  
WATER  
OUT  
MIS-2748 A  
Manual 2100-518B  
Page 14 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Manual 2100-518B  
Page 15 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flOw center wirinG  
warninG  
To avoid possible injury or death due to  
electrical shock, open the power supply  
disconnect switch and secure it in an open  
position during installation.  
cautiOn  
Use only copper conductors for field installed  
electrical wiring. Unit terminals are not  
designed to accept other types of conductors.  
Power wiring to the Flow Center should conform to all applicable codes. Figure 7 shows the required wiring between the  
geothermal heat pump and the flow center. Note: the flow center is only available in 208/230 Volt, 60 Hz, 1-phase. The flow  
center electrical connection interior of the heat pump control panel is circuit breaker protected (both L1 and L2 power lines).  
See Table 2 for the electrical requirements.  
table 2  
electrical ratinGs  
PumP  
Quantity  
mOdel  
VOlts  
amPs  
hP  
DORFC-1  
DORFC-2  
1
2
230  
230  
1.07  
2.14  
1/6  
1/3  
Manual 2100-518B  
Page 16 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 7  
electrical cOnnectiOns  
FLOW CENTER  
ELECTRICAL  
ENTRANCE  
FLOW CENTER  
CONNECTION  
Circuit Breakers  
MIS-2665  
38  
PUSH  
3
L1  
L2  
Red  
37  
Black  
PUSH  
3
2
Terminal Block  
Manual 2100-518B  
Page 17 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flushinG & charGinG  
After flushing is complete, but prior to unit start up,  
remove the large screw from the center of the flow center  
pump(s) to allow air to escape (water will drip out).  
Replace the screw after pump has filled with fluid.  
All Flushing of earth loops should be performed using a  
1.5 HP or larger pump (as specified by IGSHPA). Flushing  
can be accomplished using three different methods. The  
first flushing method applies a one-step installation of the  
loop, unit and inside piping. The second method allows a  
Loop Contractor to use flush cart when installing the loop,  
and at a later date, the dealer can install the unit to the  
loop using only domestic water to flush the unit. The third  
procedure shown is used when replacing the pump, coaxial  
refrigerant to water coil, or unit. The following are step-by-  
step procedures. Be careful not to rotate the 3-way valves  
into a position where air can be introduced into the loop.  
Reflushing will be required if this occurs. Valve position  
can be verified by looking on the end of the valve stem for  
the pattern position.  
For final pressurization, run the unit in heating or cooling  
for a period of 20 minutes. Following this 20 minute run  
time, pressurize the loop using the flush cart to 50-75 psig in  
winter or 40-50 psig in summer.  
In areas where entering loop temperatures drop below  
40°F (5°C) or where piping will be routed through areas  
subject to freezing, antifreeze is needed to prevent the loop  
from freezing inside the pipe or heat exchanger. Alcohols  
and glycols are commonly used as antifreeze, however,  
you should consult with your distributor for assistance in  
selecting the antifreeze best suited for your region.  
Consult the IGSHPA for more complete flushing and  
antifreeze instructions.  
PrOcedures fOr addinG  
antifreeze  
Flush in one direction for one hour, deadheading  
in increments - checking site glass for air pockets.  
Reverse flow in opposite direction, again for one hour,  
deadheading in increments - checking site glass for air  
pockets.  
1. Flush cart should be half full of water.  
2. Add measured amount of antifreeze through hose  
below the water level (calculate based upon loop).  
The presence of air can be detected by “deadheading” the  
pump. To deadhead the pump, close off the return to the  
pump and watch the water level site glass. Once you have  
no more than 1/2" to 3/4" drop in the site glass, you will  
have achieved complete air removal.  
3. Add antifreeze to loop side only (see valve position in  
Figure 9A).  
4. Pump and dump (discharge).  
5. Turn off pump; close discharge valve.  
Power flushing can be achieved using the home’s city water  
supply (or well water) connected to the flush cart. This  
uses the combined pressure of the flush cart pump and the  
home’s water system for faster flushing.  
6. Repeat the procedure to add remaining antifreeze to  
loop.  
Manual 2100-518B  
Page  
18 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flushinG & charGinG (cOntinued)  
fiGure 8  
cOnnectinG flush cart tO flOw center  
RETURN  
SUPPLY  
MIS-2661  
Manual 2100-518B  
Page 19 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flushinG & charGinG (cOntinued)  
fiGures 9a & 9b  
flOw center ValVe POsitiOninG  
FLUSH LOOP ONLY  
FLUSH LOOP & UNIT TOGETHER  
MIS-2662  
Manual 2100-518B  
Page 20 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flushinG & charGinG (cOntinued)  
fiGures 9c & 9d  
flOw center ValVe POsitiOninG  
FLUSH UNIT ONLY  
OPERATION  
MIS-2663  
Manual 2100-518B  
Page 21 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flushinG & charGinG (cOntinued)  
flushinG & fillinG earth lOOP and  
unit(s) tOGether  
flushinG earth lOOP Only  
1. Connect loop to flow center.  
All air and debris must be removed from the earth loop  
piping system before operation. Flush the loop with a high  
volume of water at a high velocity (2 fps in all piping in  
accordance with IGSHPA guidelines).  
2. Connect the unit side connections of the flow center  
together with a jumper hose.  
3. Remove caps and plugs from flow center front access  
ports.  
1. Connect the unit and loop to the flow center.  
4. Connect flush cart hoses to access ports.  
2. Connect the flush cart hoses to the front port of the  
flow center (see Figure 8).  
5. Position valve stems as shown in Figure 9A.  
6. Fill the flush cart two-thirds full for initial flushing.  
3. Fill closed loop (outside) evenly with domestic water  
and discharge the return water by adding water to the  
flush cart until water returns to the reservoir. The  
return water should be filtered or discharged to  
remove debris.  
7. Restart the pump. Once you have a steady flow of  
water on the return side from the system, deadhead  
the pump by closing the ball valve on the hose  
returning to the reservoir. This will generate the  
maximum pressure on the system. While the return  
ball valve is closed, note the fluid level in the  
reservoir. If all the air is purged from the system, the  
level will drop only 1/2" to 3/4" in the flush cart site  
glass, since water is not compressible. This is the  
only way to tell if the air is purged from the system.  
Open valve quickly, wait one minute, then deadhead  
again. Repeat this process until all air is purged from  
the system.  
4. Fill the flush cart two-thirds full for initial flushing.  
5. Flush the lowest portion of the system first.  
Depending upon the individual layout, this could be  
the loop or the unit. (If unit is lowest part of system,  
set valve position as shown in Figure 9C. If loop is  
lowest part of system, set flow center valve position  
as shown in Figure 9A.)  
6. Restart the pump. Once you have a steady flow of  
water on the return side from the system, deadhead  
the pump by closing the ball valve on the hose  
returning to the reservoir. This will generate the  
maximum pressure on the system. While the return  
ball valve is closed, note the fluid level in the  
reservoir. If all the air is purged from the system, the  
level will drop only 1/2" to 3/4" in the flush cart site  
glass, since water is not compressible. This is the  
only way to tell if the air is purged from the system.  
Open valve quickly, wait one minute, then deadhead  
again. Repeat this process until all air is purged from  
the system.  
8. Reverse the flow direction with the flush cart and  
repeat Step #7.  
9. Rotate the flow center valves to isolate the flush cart  
from the rest of the system (see Figure 9C).  
10. Turn off flush cart pump, relieve pressure on the  
hoses and remove them.  
11. Replace flow center access plugs and caps.  
12. Rotate valves back to position as shown in Figure 9B.  
13. Remove jumper from unit connection ports.  
7. Reverse the flow direction with the flush cart and  
repeat Step #6.  
8. Repeat Step #6 for the higher elevation side of the  
system. (If unit is highest part of system, set valve  
position as shown Figure 9C. If loop is highest part  
of system, set flow center valve position as shown in  
Figure 9A.)  
9. After flushing both sides of the system, reset flow  
control valves to flush the entire system. Set valve  
position as shown in Figure 9B and repeat Step #7.  
Manual 2100-518B  
Page  
22 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flushinG & charGinG (cOntinued)  
7. Flush flow center and unit with domestic water until  
flushinG unit Only (alsO used  
when rePlacinG unit, cOaXial  
cOil, hOse kit Or PumP)  
air is removed.  
8. Close drain valve on discharge hose and pressurize  
system to domestic water pressure (approx. 4-75  
psig).  
1. Connect unit to flow center.  
2. Rotate 3-way valve to position shown in Figure 9C.  
9. Remove bleed screw(s) from flow center pump  
3. Remove access port caps and plugs and connect either  
flush cart or Bard DORGHMT fitting (service only -  
not intended for primary flush).  
motors to purge air and replace screw(s).  
10. Close valve on supply hose to trap pressure in the  
system.  
4. Attach garden hose to domestic water supply.  
11. Rotate 3-way valves back to normal operating  
position (see Figure 9D).  
5. Purge air from garden hose before connecting to port  
in flow center.  
12. Remove water supply hose from flow center and  
6. Attach another length of garden hose to the other port  
replace access port caps/plugs.  
in the flow center, leading to drain.  
Manual 2100-518B  
Page 23 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
flOw center initial startuP  
1. Check to make sure the loop and unit isolation valves  
are completely open and the flush ports are closed and  
sealed (see Figure 9D).  
Pressure/temPerature PluGs  
The pressure/temperature plugs (P/T plugs) supplied with  
the ground water connectors are provided as a means of  
measuring flow and temperature (see Figure 10). The  
waterflow through the unit can be checked by measuring  
the incoming water pressure at the supply pressure P/T and  
subtracting the leaving water pressure at the return water  
P/T plug. Comparing the differential to the pressure drop/  
flow chart (Table 3) will determine the flow rate through  
the heat pump.  
2. Geothermal units have two low pressure switches  
installed. One switch is intended for Ground Water  
Applications (default factory wired - blue wires), and  
the second is intended for Ground Loop Applications  
(yellow wires). Remove the “blue” wires from the  
LPS terminals of the compressor control module  
internal of the control panel of the geothermal heat  
pump and replace with the yellow low pressure switch  
wires (see unit wiring diagram).  
Example: Model GV51S1 with a measured pressure  
drop of 5.1 psig is equivalent to 9 GPM flow.  
3. Check and record the earth loop pressure (use P/T  
ports at geothermal heat pump).  
GPM rates higher than the required minimum flow rates will  
not be detrimental to performance. However, insufficient  
flow can significantly reduce capacity, efficiency and create  
nuisance trips of safety controls, and possibly damage to  
components in extreme conditions.  
Loop Pressure_____IN_____OUT  
4. Check and record flow rate.  
FLOW RATE - _____GPM  
5. Check performance of unit. (Refer to Geothermal  
Heat Pump Installation Manual.)  
NOTE: Pressure/Temperature probes should be lubricated  
with a water-based lubricant prior to gently pushing the  
probes into the P/T ports to prevent internal damage.  
Thermometers, probes and gauges are available for  
conducting these tests.  
PrOcedure fOr PressurizinG the  
system  
1. Once system is completely flushed and antifreeze is  
added, it can then be pressurized. Perform this by  
deadheading the pump by closing the return hose ball  
valve. This will increase the pressure on the loop via  
the flush cart pump. As the pressure will fluctuate  
with the seasons (set higher in winter and lower in  
summer), it is suggested that the initial loop pressure  
be 50-75 psig in winter and 40-50 psig in summer. If  
you cannot reach these pressures with the flush cart  
pump alone, turn on the fresh water feed to the cart  
while still deadheading the pump. The potable water  
pressure, along with the pump, will increase the  
amount of pressure in the loop.  
2. Bleed any air from the inside of the pump. This can  
be done by removing the bleed screw from the center  
of the pump motor head, allowing a small amount of  
fluid to drip out. Replace the bleed screw.  
3. Rotate the flow center valves to isolate the flush cart  
from the rest of the system (see Figure 9D).  
4. Turn off the flush cart pump, relieve the pressure on  
the hoses and remove them.  
5. Replace flow center access plugs and caps.  
NOTE: If the flow center is mounted in the horizontal  
position, the supply hose must be connected to the lower  
flushing port to allow air to pass out of the upper port  
during the final flushing.  
Manual 2100-518B  
Page  
24 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fiGure 10  
Pressure temPerature POrts  
Thermometer  
NOTE: Slide retaining cap back to expose  
double o-rings. Apply petroleum jelly to o-rings  
to prevent damage and aid in insertion  
Dial face pressure guage  
with guage adaptor  
6
0
5
0
7
0
Retaining cap, hand tighten only  
4
0
8
0
3
0
9
0
2
0
100  
10  
110  
0
0
12  
P/T  
s test plug  
Test plug cap  
Barbed 90° adapter  
MIS-2622 A  
table 3a  
GV series cOil Pressure drOP  
model  
GV27s1  
Psid  
GV38s1 / GV51s1  
GV61s1  
GV71s1  
ft. hd.  
0.23  
1.15  
2.77  
3.92  
5.31  
7.15  
9.46  
Psid  
ft. hd.  
Psid  
ft. hd.  
Psid  
ft. hd.  
GPm  
3
0.1  
0.5  
1.2  
1.7  
2.3  
3.1  
4.1  
4
5
0.9  
1.4  
2.3  
3.2  
4.1  
5.1  
6.1  
7.1  
8.2  
9.4  
10.6  
2.08  
3.23  
6
5.31  
7
7.38  
2
4.61  
5.77  
8
9.46  
2.5  
3.2  
3.9  
4.7  
5.5  
6.4  
7.3  
8.1  
9
2
4.61  
5.54  
9
11.77  
14.07  
16.38  
18.92  
21.69  
24.45  
7.38  
2.4  
2.8  
3.4  
3.9  
4.5  
5.2  
5.9  
6.7  
7.4  
8.4  
10  
11  
12  
13  
14  
15  
16  
17  
18  
9.00  
6.46  
10.84  
12.69  
14.76  
16.84  
18.69  
20.76  
22.84  
7.84  
9.00  
10.38  
12.00  
13.61  
15.46  
17.07  
19.38  
9.9  
Manual 2100-518B  
Page 25 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
table 3b  
Gt series cOil Pressure drOP  
model  
Gtc36s1  
Psid  
Gtc48s1  
Gtc60s1  
ft. hd.  
0.23  
1.15  
2.77  
3.92  
5.31  
7.15  
9.46  
Psid  
ft. hd.  
Psid  
ft. hd.  
GPm  
3
0.1  
0.5  
1.2  
1.7  
2.3  
3.1  
4.1  
4
5
0.9  
1.4  
2.3  
3.2  
4.1  
5.1  
6.1  
7.1  
8.2  
9.4  
10.6  
2.08  
3.23  
6
5.31  
7
7.38  
2
4.61  
5.77  
8
9.46  
2.5  
3.2  
3.9  
4.7  
5.5  
6.4  
7.3  
8.1  
9
9
11.77  
14.07  
16.38  
18.92  
21.69  
24.45  
7.38  
10  
11  
12  
13  
14  
15  
16  
17  
18  
9.00  
10.84  
12.69  
14.76  
16.84  
18.69  
20.76  
22.84  
9.9  
table 3c  
Qw series cOil Pressure drOP  
model  
Qw2s1 & Qw3s1  
Qw4s1  
Qw6s1  
Psid  
0.1  
0.5  
1.2  
1.7  
2.3  
3.1  
4.1  
ft. hd.  
0.23  
1.15  
2.77  
3.92  
5.31  
7.15  
9.46  
Psid  
ft. hd.  
Psid  
ft. hd.  
GPm  
3
4
5
0.9  
1.4  
2.3  
3.2  
4.1  
5.1  
6.1  
7.1  
8.2  
9.4  
10.6  
2.08  
3.23  
6
5.31  
7
7.38  
2
4.61  
5.77  
8
9.46  
2.5  
3.2  
3.9  
4.7  
5.5  
6.4  
7.3  
8.1  
9
9
11.77  
14.07  
16.38  
18.92  
21.69  
24.45  
7.38  
10  
11  
12  
13  
14  
15  
16  
17  
18  
9.00  
10.84  
12.69  
14.76  
16.84  
18.69  
20.76  
22.84  
9.9  
Manual 2100-518B  
Page 26 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
trOubleshOOtinG  
Problem  
Water Drips Out  
Possible causes  
Condensation  
checks & corrections  
Insulate piping, check for insulation gaps.  
Water Leak  
Inspect/tighten fittings.  
Power Loss  
Check power supply from the heat pump.  
Reset circuit breaker for flow center in heat pump control box.  
Replace or tighten wires.  
Blown Circuit Breaker  
Broken or Loose Wires  
Pump Shaft Stuck  
Air Lock  
Remove the indication plug and ensure that shaft is rotating.  
Flush loop to eliminate air.  
Improperly Sized Pump  
Defective Pump  
No Positive Pressure  
Viscous Solution  
Add pump capacity.  
Low Flow / No Flow  
Replace.  
Check for leaks, add fluid, flush as required and pressurize.  
Change type of antifreeze.  
Switch thermostat to A/C operation to see if flow improves at warmer temperature.  
Add antifreeze and measure freeze protection.  
Loop Freezing or Frozen  
Kink in Loop  
Defective Pump  
Air in Loop  
Straighten or Replace.  
Replace.  
Noisey  
Flush loop again.  
Vibration  
Check mounting.  
Leak  
Repair.  
Pressure Loss  
Temperature Change  
Pipe Expansion  
Not a problem; pressure should vary as temperature changes.  
Not a problem; plastic piping relaxing.  
Unit Trips Out on Water Flow  
(Low Pressure or High Pressure)  
Low Flow / No Flow  
See Low Flow / No Flow.  
Manual 2100-518B  
Page  
27 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
antifreeze selectiOn & use  
Selection of antifreeze solutions for ground loop  
applications requires consideration of many important  
factors, which may have long-term implications in regards  
to performance and system component life. Each area  
of concern leads to a different antifreeze solution. The  
fact that there is no “ideal” antifreeze and any choice will  
require compromises in one area or another. Some of these  
considering factors include:  
Methanol – Considered toxic in pure form, good heat  
transfer, low to mid-price, flammable in concentrations  
greater than 25%, non-corrosive and low viscosity.  
Methanol has delivered outstanding performance in ground  
loop applications for over 20 years. Its only drawbacks  
are toxicity and flammability. Although methanol enjoys  
widespread consumer use as windshield washer fluid in even  
higher concentrations, some local codes may limit its use in  
ground loops. (Note: Do NOT use automotive windshield  
washer fluid as antifreeze. Most washer fluids contain  
chemicals that will cause foaming.) To increase safety, a  
pre-mixed form should be used on the jobsite to increase  
the safety factor. Pure methanol can be purchased from any  
chemical supplier.  
Safety – The toxicity and flammability of the  
antifreeze solution.  
Thermal Performance – The heat transfer and  
viscosity effects of the antifreeze.  
Cost – The prices vary widely.  
Ethanol – Good heat transfer (lower than methanol),  
high price, flammable in concentrations greater than 10%,  
non-corrosive and low viscosity. Ethanol in pure form is  
considered non-toxic and shows promise as a geothermal  
heat transfer fluid. However, the U.S. Bureau of Alcohol,  
Tobacco & Firearms (ATF) limit its distribution. All non-  
beverage ethanol is required to be denatured and rendered  
unfit to drink. Generally, this is done by adding a small  
percentage of toxic substances such as methanol, benzene  
or gasoline as a denaturant. Many of the denaturants are  
difficult to identify by the casual user, and many are not  
compatible with polyethylene pipe. Only denatured ethanol  
can be purchased for commercial use. The use of ethanol  
is not recommended because of the unknown denaturants  
included in the solution and their possible toxicity  
and damage resulting to polyethylene piping systems.  
Denaturing agents that are petroleum based can damage  
polyethylene pipe.  
Corrosiveness – System materials must be compatible  
with the antifreeze solution.  
Stability – Will the solution require periodic change  
out or maintenance?  
Convenience – Is the solution readily available and  
easy to transport and install?  
Codes – Will the solution meet local/regional/state/  
national regulatory standards?  
It is highly recommended to utilize pre-mixed antifreeze  
solutions where possible to alleviate many installation  
problems and extra labor.  
The following are some general observations about the  
types of antifreeze materials presently being applied in the  
geothermal ground loop markets:  
Manual 2100-518B  
Page  
28 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
antifreeze selectiOn & use (cOntinued)  
Potassium Acetate (GS4) – Non-toxic, good heat  
transfer, high price, non-corrosive with added inhibitors,  
low viscosity. Due to its low surface tension, Potassium  
Acetate has been known to leak through mechanical  
fittings and certain thread sealants. A variant of the salt  
family, it can be extremely corrosive when exposed to air.  
Potassium Acetate is not recommended in ground loop  
applications due to the leaking and (ultimately) corrosion  
problems associated with it.  
Propylene Glycol – Non-toxic, non-corrosive,  
expensive, hard to handle when cold, poorest heat transfer,  
has formed “slime-type” coatings inside system piping.  
Propylene Glycol is acceptable in systems anticipating  
loop temperatures no colder than 40°F (4.4°C). These  
systems typically use antifreeze because of low ambient  
conditions (outside plumbing or cooling tower, etc.).  
When loop temperatures are below 40°F, the fluid becomes  
very difficult to pump and heat transfer characteristics  
suffer greatly. Only food grade propylene glycol is  
recommended to prevent the corrosion inhibitors from  
reacting with local water causing “slime-type” coatings  
inside heat exchangers. If propylene glycol must be  
used (code requirements), careful consideration of loop  
Reynolds numbers, pump selection and pressure drop must  
be considered.  
NoTE: Consult with your local distributor if you have  
questions regarding antifreeze selection and any comments  
to report about problems or success with any particular  
methods in your area.  
table 4  
fluid VOlume  
Approximate Fluid Volume per 100’ (10 Meters) of Pipe  
VOlume  
(u.s. GallOn/100'PiPe)  
VOlume  
(liters/10 meters)  
tyPe  
size  
Copper  
1" CTS  
4.1  
6.4  
9.2  
3.0  
4.7  
7.5  
9.8  
15.4  
15.5  
24.2  
34.8  
11.4  
17.8  
28.4  
37.1  
58.3  
Copper  
1-1/4" CTS  
Copper  
1-1/2" CTS  
Polyethylene  
Polyethylene  
Polyethylene  
Polyethylene  
Polyethylene  
3/4" - IPS SDR 11  
1" - IPS SDR 11  
1-1/4" - IPS SDR 11  
1-1/2" - IPS SDR 11  
2" - IPS SDR 11  
table 5  
PercentaGes by VOlume  
Antifreeze Percentages by Volume  
minimum temperature for freeze Protection  
type  
10°f (-12.2°c)  
25%  
15°f (-9.4°c)  
21%  
20°f (-6.7°c)  
16%  
25°f (-3.9°c)  
10%  
Methanol  
Ethanol *  
29%  
25%  
20%  
14%  
100% USP  
Food Grade  
Propylene  
Glycol  
27%  
24%  
20%  
13%  
* Must not be denatured with any petroleum based product.  
Manual 2100-518B  
Page 29 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
cautiOn  
warninG  
Always use properly marked vehicles (D.O.T.  
placards) and clean/suitable/properly marked  
identified containers for handling flammable  
antifreeze mixtures. Post and advise those  
on the jobsite of chemical use and potential  
dangers of handling and storage.  
Always obtain MSDS (material safety data  
sheets) for all chemicals used in ground loop  
applications - including chemicals used as  
antifreeze.  
fiGure 11  
density VerificatiOn  
for sOlutiOn strenGth  
antifreeze VerificatiOn  
Both Glycol and Alcohol based antifreeze solutions can  
be verified to the specific percentage of volume within the  
ground loop system. One of the easiest ways to check this  
is through use of a Hydrometer to check the specific density  
of the ground loop fluid and comparing these to the charts  
supplied by the antifreeze manufacturer (see Figure 11).  
Hydrometers can be purchased from your local distributor  
and are also available through national wholesalers.  
MIS-2666  
TABLE 6  
TABLE 7  
It is recommended that IGSHPA design and specifications are utilized for Loop Design, Pipe Manifolding and Hot Fusion  
operations.  
There are many available software programs available to aid with loop design parameters. Your local loop material or equipment  
supplier may have this technology available. Technical Service has the capability to assist you in this area as well, but it is on a  
first come - first serve basis.  
Manual 2100-518B  
Page  
30 of 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  

3Com Network Router 3CRWER100 75 User Manual
3Com Switch 10005622 User Manual
Agilent Technologies Portable Generator E4400 90333 User Manual
Aigo Clock F029 User Manual
Altec Lansing MP3 Docking Station IMV712 User Manual
Aluratek Battery Charger AUCS02F User Manual
Amana Air Conditioner ASX 14 SEER User Manual
American Standard Multi tool 2004 User Manual
Athena Technologies Portable Speaker LS 50 User Manual
Audiovox Remote Starter 128 7853 User Manual