ADC Clothes Dryer ML 82 User Manual

ML-8 2  
Service Man u al  
American Dryer Corporation  
88 Currant Road  
Fall River, MA02720-4781  
Telephone: (508) 678-9000 / Fax: (508) 678-9447  
ADC Part No. 450404  
082499MFM/tcosta  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT  
YOU MUST DISCONNECT and LOCKOUTTHE ELECTRIC SUPPLYandTHE GAS  
SUPPLY or THE STEAM SUPPLY BEFORE ANY COVERS or GUARDS ARE  
REMOVED FROM THE MACHINETOALLOWACCESS FOR CLEANING,ADJUST-  
ING, INSTALLATION, or TESTINGOFANY EQUIPMENT per OSHA (Occupational  
Safety and HealthAdministration) STANDARDS.  
«Attention: Lor des opérations d’entretien  
des commandes étiqueter tous fils avant  
de les déconnecter. Toute erreur de  
câblage peut étre une source de danger et  
de panne.»  
“Caution: Label all wires prior to  
disconnection when servicing controls. Wiring  
errors can cause improper operation.”  
CAUTION  
DRYERS SHOULD NEVER BE LEFT UNATTENDEDWHILE IN OPERATION.  
WARNING  
CHILDREN SHOULD NOT BEALLOWEDTO PLAYON OR NEARTHE DRYERS.  
CHILDREN SHOULD BE SUPERVISED IFNEAR DRYERS IN OPERATION.  
FORYOUR SAFETY  
DO NOT DRYMOPHEADS INTHE DRYER.  
DO NOT USE DRYER INTHE PRESENCE OF DRYCLEANING FUMES.  
WARNING  
UNDER NO CIRCUMSTANCES should the door switch or the heat circuit devices  
ever be disabled.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
The dryer must never be operated with any of the back guards, outer tops, or service  
panels removed. PERSONALINJURYor FIRE COULD RESULT.  
WARNING  
DRYER MUST NEVER BE OPERATEDWITHOUTTHE LINT FILTER (SCREEN) IN  
PLACE, EVEN IFAN EXTERNALLINT COLLECTION SYSTEM IS USED.  
IMPORTANT  
PLEASE OBSERVE ALL SAFETY PRECAUTIONS displayed on the equipment or  
specified in the installation/operator's manual included with the dryer.  
Dryers must not be installed or stored in an area where it will be exposed to water or weather.  
The wiring diagram for the dryer is located in the front electrical control box area.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ta ble of Con t en t s  
SECTION I  
IMPORTANT INFORMATION ........................................................................................................ 3  
A. Safety Precautions................................................................................................................................... 3  
SECTION II  
SPECIFICATIONS/COMPONENT IDENTIFICATION................................................................. 5  
A. Specifications ........................................................................................................................................... 5  
B. Component Identification ......................................................................................................................... 7  
SECTION III  
ROUTINE MAINTENANCE............................................................................................................. 9  
A. Cleaning ................................................................................................................................................... 9  
B. Adjustments ........................................................................................................................................... 10  
C. Lubrication ............................................................................................................................................. 10  
SECTION IV  
DESCRIPTION OFPARTS ............................................................................................................. 11  
A. Control PanelAssembly ........................................................................................................................ 11  
B. Door Switch Assembly .......................................................................................................................... 11  
C. Lint Drawer and Lint Drawer Switch ................................................................................................... 11  
D. The Basket and Support Assembly ....................................................................................................... 12  
E. Temperature Sensor Bracket Assembly ................................................................................................ 12  
F. Tumbler BearingAssembly ................................................................................................................... 12  
G. Idler Arm Assembly............................................................................................................................... 13  
H. Blower Motor ........................................................................................................................................ 13  
I. Drive/Fan MountAssembly................................................................................................................... 13  
J. HSI (Hot Surface Ignition) Burner Box Assembly ............................................................................... 14  
K. Sail SwitchAssembly ............................................................................................................................ 14  
L
Front Panel Assembly............................................................................................................................ 14  
M. Reversing Relay Panel .......................................................................................................................... 15  
SECTION V  
SERVICING ...................................................................................................................................... 16  
A. Computer Controls................................................................................................................................. 16  
B. Ignition Controls ..................................................................................................................................... 18  
C. To Replace Burner Hi-Limit Thermostat (Gas Models Only) ............................................................... 21  
D. Sail Switch Assembly (Gas Models Only) ............................................................................................. 22  
E. Front Panel and Main Door Assemblies ................................................................................................ 23  
F. Steam Controls ...................................................................................................................................... 26  
G. Tumbler and BearingAssembly............................................................................................................. 28  
H. Idler Shaft and Bearing Assembly ......................................................................................................... 29  
I. Drive Pulley ........................................................................................................................................... 30  
J. Tumbler (Basket) ................................................................................................................................... 30  
K. V-Belts (Refer to Illustrations in Sections I, and K).............................................................................. 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION VI  
PHASE 6 OPL SYSTEM DIAGNOSTICS ...................................................................................... 34  
A. Diagnostic (L.E.D. Display) Failure Codes........................................................................................... 34  
B. L.E.D. (Light Emitting Diode) Display Indicators ................................................................................. 36  
C. Phase 6 OPL Microprocessor Controller Relay Output L.E.D. Indicators........................................... 37  
D. L.E.D. Codes ........................................................................................................................................ 41  
E. Fault Codes ............................................................................................................................................ 42  
SECTION VII  
TROUBLESHOOTING .................................................................................................................... 43  
SECTION VIII  
ELECTRICAL TROUBLESHOOTING .......................................................................................... 47  
SECTION IX  
TECHNICALINFORMATION ....................................................................................................... 51  
A. Motor Plate (High and Low Voltage) .................................................................................................... 51  
B. Data Label ............................................................................................................................................. 53  
C. Computer Logic ..................................................................................................................................... 55  
SECTION X  
SERVICE/PARTS INFORMATION ............................................................................................... 56  
A. Service ................................................................................................................................................... 56  
B. Parts ...................................................................................................................................................... 56  
SECTION XI  
WARRANTYINFORMATION ....................................................................................................... 57  
A. Returning Warranty Card(s) .................................................................................................................. 57  
B. Parts ...................................................................................................................................................... 57  
C. Returning Warranty Parts...................................................................................................................... 57  
D. ML-82 Tool List..................................................................................................................................... 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION I  
IMPORTANT INFORMATION  
A. SAFETY PRECAUTIONS  
WARNING: For your safety, the information in this manual must be followed to minimize the risk of  
fire or explosion or to prevent property damage, personal injury, or loss of life.  
WARNING: The dryer must never be operated with any of the back guards, outer tops, or  
service panels removed. PERSONALINJURY or FIRE COULD RESULT.  
1. DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other  
appliance.  
2. Purchaser/user should consult the local gas supplier for proper instructions to be followed in the event the user  
smells gas. The instructions should be posted in a prominent location.  
3. WHAT TO DO IF YOU SMELL GAS.  
a. DO NOT try to light any appliance.  
b. DO NOT touch any electrical switch.  
c. DO NOT use any phone in your building.  
d. Clear the room, building, or area of ALL occupants.  
e. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.  
f. If you cannot reach your gas supplier, call the fire department.  
4. Installation and service must be performed by a qualified installer, service agency, or gas supplier.  
5. Dryer(s) must be exhausted to the outdoors.  
6. Although ADC produces a very versatile machine, there are some articles that, due to fabric composition or  
cleaning method, should not be dried in it.  
WARNING: Dry only water-washed fabrics. DO NOT dry articles spotted or washed in dry  
cleaning solvents, a combustible detergent, or “all purpose” cleaner.  
EXPLOSION COULD RESULT.  
WARNING: DO NOT dry rags or articles coated or contaminated with gasoline, kerosene, oil, paint,  
wax.  
EXPLOSION COULD RESULT.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: DO NOT dry mop heads. Contamination by wax or flammable solvents will create  
a fire hazard.  
WARNING: DO NOT use heat for drying articles that contain plastic, foam, sponge rubber, or  
similarly textured rubber materials. Drying in a heated basket (tumbler) may damage  
plastics or rubber and also may be a fire hazard.  
7. A program should be established for the inspection and cleaning of lint in the heating unit area, exhaust duct  
work, and inside the dryer. The frequency of inspection and cleaning can best be determined from experience  
at each location.  
WARNING: The collection of lint in the burner area and exhaust duct work can create a  
potential fire hazard.  
8. For personal safety, the dryer must be electrically grounded in accordance with local codes and/or the  
National Electrical Code ANSI/NFPA NO. 70-LATEST EDITION or in Canada, the Canadian Electrical  
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.  
NOTE: Failure to do so will VOID THE WARRANTY.  
9. UNDER NO CIRCUMSTANCES should the dryer door switches, lint door switch, heat safety circuit ever  
be disabled.  
WARNING: PERSONALINJURYor FIRE COULD RESULT.  
10. This dryer is not to be used in the presence of dry cleaning solvents or fumes.  
11. Remove articles from the dryer as soon as the drying cycle has been completed.  
WARNING: Articles left in the dryer after the drying and cooling cycles have been completed  
can create a fire hazard.  
12. DO NOT operate steam dryers with more than 125 PSI (8.61 bars) steam pressure. Excessive steam  
pressure can damage steam coil and/or harm personnel.  
13. Replace leaking flexible hoses or other steam fixtures immediately. DO NOT operate the dryer with leaking  
flexible hoses. PERSONAL INJURY MAY RESULT.  
14. READ and FOLLOW ALL CAUTION and DIRECTION LABELS ATTACHED TO THE DRYER.  
WARNING: YOU MUST DISCONNECT and LOCKOUTTHE ELECTRIC SUPPLYand  
THE GAS SUPPLYorTHE STEAM SUPPLYBEFOREANYCOVERS or  
GUARDSARE REMOVED FROM THE MACHINE TOALLOWACCESS  
FOR CLEANING,ADJUSTING, INSTALLATION, orTESTINGOFANY  
EQUIPMENT perOSHA(Occupational Safety and HealthAdministration)  
STANDARDS.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION II  
SPECIFICATIONS/COMPONENT IDENTIFICATION  
A. SPECIFICATIONS  
BASKET (TUMBLER) DIAMETER  
37"  
36"  
94 cm  
91.5 cm  
BASKET (TUMBLER) DEPTH  
BASKET (TUMBLER) MOTOR  
BLOWER MOTOR  
1/2 HP  
3 HP  
.373 kw  
2.238 kw  
54.61 cm  
.634 cu.m.  
DOOR OPENING (DIAMETER)  
BASKET (TUMBLER) VOLUME  
DRYERS PER 20'/40' CONTAINER  
DRYERS PER 6m/12m CONTAINER  
DRYERS PER 45'/48' TRUCK  
DRYERS PER 14m/15m TRUCK  
VOLTAGE AVAILABLE  
APPROX. WEIGHT (UNCRATED)  
APPROX. WEIGHT (CRATED)  
HEAT INPUT  
21-1/2"  
22.4 cu. ft.  
10/20  
10/20  
24/24  
24/24  
208-460v 3ø 50/60 Hz  
828 lbs.  
375.6 kg  
398.3 kg  
878 lbs.  
270,000 btu/hr  
1,700 cfm  
1"  
68,040 kcal/hr  
48.14 cmm  
2.54 cm  
AIRFLOW  
INLET PIPE SIZE  
VOLTAGE AVAILABLE  
APPROX. WEIGHT (UNCRATED)  
APPROX. WEIGHT (CRATED)  
AIRFLOW  
208-460v 3ø 50/60 Hz  
828 lbs.  
914 lbs.  
392.7 kg  
415.5 kg  
98.8 cmm  
---  
2,500 cfm  
1/8" F.P.T.  
AIR CONNECTION  
BOILER HP  
NORMAL LOAD  
STEAM CONSUMPTION  
375 lbs/hr  
OPERATING STEAM PRESSURE  
125 psi max  
8.79 kg/cm2  
Shaded areas are stated metric equivalents  
170.5 kg/hr  
11  
STEAM SUPPLY  
STEAM RETURN  
1"  
2.54 cm  
1"  
2.54 cm  
IMPORTANT: Steam dryers must be provided with a clean, dry, regulated 80 PSI +/- 10 PSI (5.51  
bars +/- .68 bars) supply.  
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or  
obligation.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specificat ion s  
MLG-8 2 (Gas)  
MLS-8 2 (St eam )  
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or  
obligation.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. COMPONENT IDENTIFICATION  
1. Dryer Front View  
Illus. No.  
Description  
1
2
3
4
5
6
Controls  
Control (top access) Door Assembly  
Main DoorAssembly  
Lint Compartment Area (lint screen located behind door)  
Lint Drawer  
Data Label and Installation Label (located behind control [service] door)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Dryer Rear View  
Illus. No.  
Description  
1
2
Heating Unit  
1/8" CompressedAir Supply Inlet  
(behind Electric Service Relay Box for Steam Models Only)  
Electric Service Relay Box  
Tumbler Bearing MountAssembly  
Idler Bearing MountAssembly  
Basket (Drive) Motor Assembly (for Reversing Models Only)  
Blower Motor Assembly  
3*  
4
5
6
7
8
Dryer Exhaust  
* Electric service connections for Gas Models and Steam Models are made in this box.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION III  
ROUTINE MAINTENANCE  
A. CLEANING  
A program or schedule should be established for periodic inspection, cleaning, and removal of lint from various  
areas of the dryer, as well as throughout the duct work system. The frequency of cleaning can best be determined  
from experience at each location. Maximum operating efficiency is dependent upon proper air circulation. The  
accumulation of lint can restrict this airflow. If the guidelines in this section are met, an ADC dryer will provide  
many years of efficient, trouble-free, and - most importantly - safe operation.  
WARNING: LINT FROM MOST FABRICS IS HIGHLY COMBUSTIBLE. THE  
ACCUMULATION OFLINT CAN CREATEAPOTENTIALFIRE HAZARD.  
WARNING: KEEPDRYERAREACLEARAND FREE FROM COMBUSTIBLE  
MATERIALS, GASOLINE, and OTHER FLAMMABLE VAPORS and  
LIQUIDS.  
NOTE: Suggested time intervals shown are for average usage which is considered six (6) to eight (8)  
operational (running) hours per day.  
SUGGESTED CLEANING SCHEDULE  
EVERY THIRD or FOURTH LOAD  
Clean the lint screen every third or fourth load. A clogged lint screen will cause poor dryer performance. The  
lint screen is located behind the lint door in the base of the dryer. Open the lint door, brush the lint off of the lint  
screen, and remove the lint. Inspect the lint screen and replace if torn.  
NOTE: The frequency of cleaning the lint screens can best be determined from experience at each  
location.  
WEEKLY  
Clean lint accumulation from the lint chamber, thermostat, and microprocessor temperature sensor (sensor  
bracket) area.  
WARNING: TOAVOID HAZARD OFELECTRICALSHOCK, DISCONTINUE  
ELECTRICALPOWER SUPPLYTO THE DRYER.  
STEAM DRYERS  
Clean the steam coil fins. Suggest using compressed air and a vacuum cleaner with brush attachment.  
NOTE: When cleaning steam coil fins, be careful not to bend the fins. If the fins are bent,  
straighten by using a fin comb, which is available from any local air conditioning supply house.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
90 DAYS  
1. Remove lint from around basket (tumbler), drive motors, and surrounding areas.  
2. Remove lint from gas valve burner area with a dusting brush or vacuum cleaner attachment.  
3. Clean any lint accumulation in and around both the blower and drive motor casing openings.  
NOTE: To prevent damage, avoid cleaning or touching the hot surface ignitor assembly.  
EVERY 6 MONTHS  
Inspect and remove lint accumulation in customer furnished exhaust duct work system and from dryers internal  
exhaust ducting.  
NOTE: THEACCUMULATION OFLINT IN THE EXHAUST DUCTWORK CAN  
CREATEAPOTENTIALFIRE HAZARD.  
NOTE: DO NOT OBSTRUCT THE FLOW OF COMBUSTION and VENTILATIONAIR.  
CHECK CUSTOMER FURNISHED BACK DRAFT DAMPERS IN THE EXHAUST  
DUCT WORK. INSPECT and REMOVEANY LINTACCUMULATION WHICH  
CAN CAUSE THE DAMPER TO BIND or STICK.  
NOTE: A back draft damper that is sticking partially closed can result in slow drying and shut-down  
of heat circuit safety switches or thermostats.  
NOTE: When cleaning the dryer cabinets, avoid using harsh abrasives. Aproduct intended for the  
cleaning of appliances is recommended.  
B. ADJUSTMENTS  
7 DAYS AFTER INSTALLATION and EVERY 6 MONTHS THEREAFTER  
Inspect bolts, nuts, screws, (bearing set screws), nonpermanent gas connections (unions, shut-off valves, orifices,  
and grounding connections). Motor and drive belts should be examined. Cracked or seriously frayed belts  
should be replaced. Tighten loose V-belts when necessary. Complete operational check of controls and  
valves. Complete operational check of ALL safety devices (door switches, lint drawer switch, sail switch,  
burner and hi-limit thermostats).  
C. LUBRICATION  
The motor bearings, idler bearings, and under normal/most conditions the tumbler bearings are permanently  
lubricated. It is physically possible to re-lubricate the tumbler bearings if you choose to do so even though this  
practice is not necessary. Use Shell Alvania #3 grease or its equivalent. The tumbler bearings used in the dryer  
does not have a grease fitting. Provisions are made in the bearing housing for the addition of a grease fitting  
which can be obtained elsewhere.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION IV  
DESCRIPTION OF PARTS  
A. CONTROL PANEL ASSEMBLY  
The control panel assemble is made up of a keypad to enter  
your selections, and a Phase 6 main computer board. The  
computer controls all input and output functions of the  
machine.  
B. DOOR SWITCH ASSEMBLY  
The main door switch assembly is a safety device used to  
stop the tumbler in case the main door is opened during a  
cycle.  
C. LINT DRAWER  
AND LINT DRAWER SWITCH  
The lint door/drawer is located in the bottom front of the  
machine. It is a drawer that pulls out with a fine mesh  
screen that catches the lint. The lint drawer switch is  
another safety device to stop the basket from turning when  
the lint drawer is opened.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. THE BASKET AND SUPPORT  
ASSEMBLY  
The basket and support assembly is designed for 80  
lbs. (36 km) of dry material. It is supported by a shaft  
and two (2) bearings.  
E. TEMPERATURE SENSOR  
BRACKET ASSEMBLY  
This bracket assembly is equipped with two (2)  
important devices. One is the temperature probe and  
the other is the 225º F (107º C) basket hi-limit. The  
temperature probe senses the temperature in the basket  
and sends a signal to the computer to read that  
temperature. This sensor is also known as the “TEMP  
SENSOR FAIL” sensor. The 225º F (107º C)  
thermostat is a safety device to shut down the gas valve  
in a case of the temperature exceeding 225º F (107º  
C).  
F. TUMBLER BEARING ASSEMBLY  
The bearing box is the holder for the pillow block bearing  
and it also has the adjustments for the basket on it.  
The bearings are what support the tumbler support and  
basket to the dryer. The rotational sensor is another  
safety device to stop the motor if it senses the basket  
has stopped during a cycle.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G. IDLER ARM ASSEMBLY  
The idler arm/pulley has the purpose of taking the  
speed of the motor and reducing it.Adding tourque  
to the 18” (46 cm) basket pulley is also the function  
of the idler arm/pulley.  
H. BLOWER MOTOR  
The blower/fan motor has only one purpose in  
the dryer. It produces the airflow (cfm)  
throughout the machine.  
I. DRIVE/FAN MOUNT ASSEMBLY  
The drive motor is used to turn the basket in the forward  
and reverse motion. The fan mount assembly is used  
to increase the speed of the blower motor which in turn  
increases the cfm throughout the machine.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J. HSI (HOT SURFACE IGNITION)  
BURNER BOX ASSEMBLY  
The HSI (Hot Surface Ignition) burner box assembly  
consists of a number of very important parts for the dryer.  
Agas valve, hot surface ignitor, hot surface module, flame  
sensor, sail switch, burner hi-limit. These parts are for  
the “heat” of the dryer.  
K. SAIL SWITCH ASSEMBLY  
The sail switch assembly is used on gas and  
electric heated machines. It is an airflow switch,  
the damper pulls in due to the air suction on the  
burner; making the switch which lets the voltage  
proceed to the HSI (Hot Surface Ignition)  
module.  
L. FRONT PANEL ASSEMBLY  
The front panel is a little different than our other models.  
This one is the full height and width of the dryer.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M. REVERSING RELAY PANEL  
This panel is located in the back of the machine  
at the upper left hand corner. On this panel is an  
arc suppressor (A.S.) board which filters out  
“noise” that might go to the coils of the  
contactors. Also mounted on this panel are the  
drive and blower/fan contactors. The two (2)  
fuses mounted on the panel are protecting the  
L1 and L3 voltage. The transformer is stepping  
down the incoming voltage to 24 VAC to supply  
the voltage to the computer and controls.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION V  
SERVICING  
INTRODUCTION  
ALL electrical and mechanical service or repairs should be made with the electrical power to the dryer  
disconnected (power off).  
WARNING: PERSONALINJURYCOULD RESULT.  
The information provided in this section should not be misconstrued as a device for use by an untrained person  
making repairs. Service work should be performed by competent technicians in accordance with local, state,  
and federal codes. When contacting the factory for assistance, always have the dryer model and serial numbers  
available.  
CAUTION: Observe ALL safety precautions displayed on the dryer or specified in this manual before  
and while making repairs.  
Before considering replacement, make sure that ALL connectors are in place and making proper contact.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. COMPUTER CONTROLS  
To Replace Computer Board  
1. Disconnect electrical power to dryer.  
2. Unplug keyboard ribbon from rear of computer.  
3. Unplug all wiring harnesses connected to the  
computer board.  
4. Remove the two (2) screws securing the computer  
to the computer panel. Remove the computer by  
pulling the other two corners off the clinch studs.  
5. Install new computer by reversing this procedure.  
To Replace Keyboard Label Assembly  
1. Discontinue electrical power to the dryer.  
2. Unplug keyboard ribbon from rear of computer.  
3. Slowly peel off and remove keyboard label assembly from control panel.  
4. Peel paper backing off new keyboard label assembly.  
5. Holding the new keyboard label assembly close to the panel, insert the keyboard ribbon through the rectangular  
slot in the control panel. Align label assembly into position by matching the red viewing window on the label  
to the rectangular cutout in the panel and gently press into place.  
6. Connect keyboard ribbon to the computer.  
7. Reestablish electrical power to dryer.  
To Replace Microprocessor Temperature Sensor Probe  
1. Discontinue electrical power to the dryer.  
2. Open lint door.  
3. Remove microprocessor sensor bracket assembly from  
dryer.  
a. Disconnect sensor bracket harness connector.  
b. Loosen the two (2) Phillips head screws which  
secure bracket assembly to dryer and remove  
bracket from dryer.  
NOTE: DO NOT remove screws.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Disassemble sensor probe from bracket assembly by removing the top push-on fastener securing the probe  
from bracket. Use a small screwdriver to slowly pry the fastener off.  
5. Disconnect the two (2) orange wires from the high heat (225º F [107º C]) thermostat, and remove modular  
bracket connector, wires, and probe from bracket assembly.  
6. Install new sensor probe assembly (ADC P/N 880251) by reversing procedure.  
7. Reestablish electrical power to the dryer.  
NOTE: If, when electrical power is reestablished, the computer display reads “TEMPSENSOR FAIL  
CHECK TEMP SENSOR FUSE,” check for a loose connection in the wiring.  
B. IGNITION CONTROLS  
To Remove Hot Surface Ignitor  
1. Discontinue electrical power to the dryer.  
2. Disconnect wire from S1 and GND on the HSI  
module.  
3. Disassemble ignitor from burner by removing the  
one (1) self tapping screw.  
4. Reverse procedure for installation of new ignitor.  
To Remove Flame Sensor Probe  
1. Discontinue electrical power to the dryer.  
2. Disconnect the red wire from the flame sensor probe which goes to S2 on the HSI module.  
3. Disassemble flame sensor probe from burner by removing the one (1) self tapping screw.  
4. Reverse procedure for installation of new flame sensor probe.  
HSI Ignitor Flame Sensor Probe  
NOTE: Before reestablishing electrical  
power to dryer visually check  
the following. (Refer to illustration):  
1. That the Hot Surface Ignitor wires are connected  
to S1 and GND on the HSI module.  
2. DO NOT wrap the hot surface ignitor wires  
and the flame electrode wire together. Improper  
operation may result. They may run alongside  
each other.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Replace Gas Valve (Refer to burner illustration on page 14)  
1. Discontinue electrical power to the dryer.  
2. Close shut-off valves in gas supply line.  
3. Disconnect gas valve wiring.  
NOTE: Identify location of each wire for correct reinstallation.  
4. Break union connection before gas valve.  
5. Loosen and remove four (4) screws securing pipe brackets to burner.  
6. Remove valve and manifold assembly from dryer.  
7. Remove valve mounting bracket, manifold and piping from gas valve.  
8. Reverse procedure for installing new gas valve.  
WARNING: Test ALLconnections for leaks by brushing on a soapy water solution.  
WARNING: NEVER TEST FOR LEAKS WITHA FLAME!!!  
To Replace Main Burner Orifices  
1. Refer to “To Replace Gas Valve” above and follow Step #1 through Step #6.  
2. Unscrew main burner orifices and replace.  
NOTE: Use extreme care when removing and replacing orifices. These orifices are made of brass and  
are easily damaged.  
3. Reverse the removal procedure for reinstalling.  
NOTE: Test ALL connections for leaks by brushing on a soapy water solution.  
WARNING: NEVER TEST FOR LEAKS WITH A FLAME!!!  
To Test and Adjust Gas (Water Column) Pressure  
There are two (2) types of devices commonly used to measure column pressure. They are spring and mechanical-  
type gauges and manometers. The spring and mechanical-type gauge is not recommended, because it is easily  
damaged and not always accurate. A manometer is simply a glass or transparent plastic tube with a scale in  
inches. When filled with water and pressure applied, the water in the tube rises showing the exact water column  
pressure.  
NOTE: Manometers are available from the factory by ordering ADC P/N 122804.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. To test gas water column (W.C.) Pressure:  
a. Connect water column test gauge connection to gas valve pressure  
tap (1/8" NPT). This pressure tap is located on the outlet (manifold)  
side of the valve.  
b. Start dryer. With burner on, the correct water column reading in  
inches would be:  
Natural Gas - 3.5 Inches Water Column - 8.7 mb.  
L.P. Gas - 10.5 Inches Water Column - 26.1 mb.  
2. To adjust water column pressure (natural gas only, L.P. gas must be  
regulated at source):  
a. Remove the slotted vent cap on the top of the valve.  
b. Turn the slotted adjustment screw located on the top of the valve  
next to the terminals. Turn clockwise (CW) to increase manifold  
pressure and counterclockwise (CCW) to decrease.  
NOTE: If correct water column pressure cannot be achieved, problems may be due to an undersized  
gas supply line, a faulty or underrated gas meter, etc.  
To Convert Natural Gas to L.P. Gas  
NOTE: ALL dryers are sold as natural gas, unless otherwise specified at the time the dryer order was  
placed. For L.P. gas the dryer must be converted as follows.  
1. Refer to “Replace Gas Valve” and follow Step #1 through Step #6.  
a. Remove top vent cap.  
b. Insert spring and pin.  
c. Replace vent cap.  
2. Unscrew main burner orifices and replace with L.P. orifices.  
NOTE: Use extreme care when removing orifices. They are made of brass and are easily damaged.  
3. Reverse the procedure for reinstalling valve assembly to the dryer.  
WARNING: Test ALL connections for leaks by brushing on a soapy water solution.  
WARNING: NEVER TEST FOR LEAKS WITH A FLAME!!!  
NOTE: There is no regulator provided in an L.P. dryer. The column pressure must be regulated at the  
source (L.P. tank) or an external regulator must be added to each dryer.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Replace Burner Tubes  
1. Refer to “Replace Gas Valve” and follow Steps  
#1 through Step #6.  
2. Remove four (4) screws securing the Hot Surface  
Ignitor (HSI) module mounting bracket.  
3. Remove front flanges of the burner tubes to the  
burner tube rest.  
4. Remove the screws securing the burner tube rest  
to the oven and remove this rest.  
5. Remove screws securing burner box cover plate  
to the oven and remove the cover.  
6. Remove burner tubes by sliding them out.  
7. Replace by reversing procedure.  
To Replace HSI Module  
1. Discontinue electrical power to the dryer.  
2. Remove the wires connected to the terminal strip  
at the bottom of the module. (Mark correct  
location of each wire to aid in replacement on  
new module).  
3. Remove the four (4) pal nuts securing the module  
to the mounting bracket.  
4. Replace module by reversing procedure.  
5. Reestablish electrical power to dryer.  
C. TO REPLACE BURNER HI-LIMIT THERMOSTAT (GAS MODELS ONLY)  
1. This thermostat is an important safety device as an added  
protection against failure of the airflow (sail switch) to open  
in the event of motor failure or reduced airflow conditions.  
IMPORTANT: Under no circumstances should heat  
circuit safety devices ever be disabled.  
NOTE: Models manufactured as of 1998 are equipped  
with a manual reset hi-limit thermostat.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Discontinue electrical power to the dryer.  
2. Disconnect wires from hi-limit thermostat.  
3. Remove the two (2) screws, washers and nuts securing thermostat to the bracket. Remove thermostat.  
4. Reversing procedure for installing new thermostat.  
5. Reestablish electrical power to dryer.  
To Replace Lint Compartment Hi-Heat Protector (225º F [107º C]) Thermostat  
This thermostat is part of the “sensor bracket  
assembly” and is secured to the underside of the  
basket wrapper in the lint compartment. As a  
safety device, this thermostat will open (shut off)  
the heating unit circuit if an excessive temperature  
occurs. The dryer motor will remain on, even if  
the thermostat is open.  
1. Disconnect electrical power to dryer.  
2. Open lint door.  
3. Locate sensor bracket assembly and loosen the two (2) Phillips  
head screws securing bracket assembly to the tumbler wrapper.  
NOTE: DO NOT remove the screws.  
4. Remove bracket assembly by slightly sliding bracket toward the rear of the dryer and to the left.  
5. Disconnect sensor bracket harness connector and remove bracket assembly from dryer.  
6. Disconnect the two (2) orange wires from the thermostat.  
7. Disassemble thermostat from bracket assembly by removing the two (2) mounting screws, washers and nuts.  
8. Reverse this procedure for installing a hi-heat protector thermostat.  
9. Reestablish electrical power to the dryer.  
D. SAIL SWITCH ASSEMBLY (GAS MODELS ONLY)  
The sail switch is a heat circuit safety device which  
controls the burner circuit only. When the dryer is  
operating and there is proper airflow, the sail switch  
damper pulls in and closes the sail switch. Providing  
all the other heat-related circuits are functioning  
properly, ignition should now be established. If an  
improper airflow occurs, the sail switch damper will  
release, and the circuit will open.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Replace Sail Switch  
1. Discontinue electrical power to the dryer.  
2. Remove the two (2) screws which hold the sail switch box cover to sail switch box.  
3. Disconnect the two (2) wires from the switch.  
4. Disassemble sail switch from mounting bracket by removing the two (2) screws securing switch in place.  
5. Reverse this procedure for installing new sail switch. Adjust sail switch described in the next section.  
To Adjust Sail Switch  
With the dryer operating at a high temperature setting, pull the sail switch away from the burner. The sail switch  
should open and extinguish the burner. Let the sail switch damper return to the burner wall. The sail switch  
should close to restart the burner ignition cycle. If the sail switch circuit does not operate as described, bend the  
actuator arm of the sail switch accordingly until proper operation is achieved. To check proper “open” position of  
sail switch, open main door, manually depress main door switch and start dryer. With the main door open and the  
dryer operating, the sail switch should be open, and the burner should not come on.  
CAUTION: DO NOT abort this switch by taping or screwing sail switch damper to burner.  
PERSONALINJURYor FIRE COULD RESULT.  
E. FRONT PANEL and MAIN DOOR ASSEMBLIES  
To Replace Main Door Switch  
1. Discontinue electrical power to the dryer.  
2. Open main door.  
3. Remove the two (2) Phillips head screws holding the main door switch  
bracket assembly in place.  
4. Disconnect wiring from switch assembly.  
5. Reverse this procedure for installing new door switch assembly.  
6. Reestablish electrical power to dryer.  
.
IMPORTANT: UNDER NO CIRCUMSTANCES should the door switch be disabled.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Replace Main Door Assembly  
1. Open main door.  
2. Holding the door upward remove the two (2) screws from the top hinge block.  
3. Lift the door up to remove.  
4. Reverse this procedure for reinstalling new main door assembly.  
To Install New Main Door Glass  
1. Remove main door assembly from dryer (follow main door removal procedure).  
2. Lay main door on flat surface with back of door face down.  
3. Remove glass and clean all old sealant off main door. This area must be completely clean for correct bonding.  
4. Apply a narrow bead of silicone (ADC P/N 170730) all around main door area where glass will rest.  
5. Install glass onto door and adhesive. Slightly/gently press glass into place.  
6. The door assembly should now be put in an area where it will not be disturbed for a few hours. This will give  
the silicone a chance to harden.  
IMPORTANT: DO NOT press hard or silicone thickness between the glass and door will be  
reduced, resulting in poor bonding.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. After the curing period, install the main door on the dryer by reversing Step #4 through Step #1.  
NOTE: Once the silicone is cured you may want to trim any excess silicone on the inside of the main  
door assembly.  
To Replace Front Panel  
1. Discontinue electrical power to the dryer.  
2. Remove bottom lint door assembly.  
3. Remove the front panel by removing the screws.  
IMPORTANT: When pulling the front panel off, the door switch harness in the upper right hand  
corner must be unplugged.  
NOTE: The main door assembly can be removed to make the panel removal easier. Refer to  
“Replace Main DoorAssembly” directions.  
4. Disconnect other door switch wiring switch from the old panel and reinstall on the new front panel.  
5. Reinstall the new front panel by reversing Step #1 through Step #3.  
6. Reestablish electrical power to dryer.  
To Replace Main Door Hinge Block  
1. Discontinue electrical power to the dryer.  
2. Follow procedure for removal of main door assembly for top hinge removal.  
3. Remove the two screws from the bottom hinge block.  
4. Reassemble by reversing removal procedure.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F. STEAM CONTROLS  
Installation  
Piping must be installed in accordance with good commercial steam system practice. See the illustration below  
for a typical pipe arrangement.  
To Replace Steam Coil (Damper System)  
1. Discontinue electrical power to the dryer.  
2. Remove the four (4) lock washers and hex nuts securing the hinges to steam coil.  
3. Remove hinges from steam coil housing (these will be used on new assembly).  
4. Remove six (6) washers and hex nuts securing steam coil to dryer.  
5. Remove steam coil assembly.  
6. Reverse procedure for new steam coil assembly.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Replace Piston  
1. Discontinue electrical power to the dryer.  
2. Discontinue the air supply to the dryer.  
3. Remove left and right piston supports by removing two (2) washers and hex nuts and slide pin out.  
4. Remove 1/8” M.P.T. connector from the piston and remove acorn nut on the end of piston shaft (this will be  
used on new piston).  
5. Reverse procedure for installing new piston.  
To Replace The Needle Valve  
1. Discontinue electrical power to the dryer.  
2. Discontinue the air to the dryer.  
3. Remove the 1/8” brass close nipple from the needle valve.  
4. Remove the 1/8” M.P.T. connector from the needle valve.  
5. Remove the needle valve.  
6. Reverse procedure to install new needle valve.  
To Replace the 3-Way Micro Valve  
1. Discontinue electrical power to the dryer.  
2. Discontinue the air to the dryer.  
3. Remove inlet side of air from the 3-way valve.  
4. Remove the two (2) 1 inch machine bolts and mounting hardware holding the 3-way valve to the bracket.  
5. Remove the 1/8” brass close nipple from the outlet side of the valve.  
6. Remove valve.  
7. Reverse procedure to install new micro valve.  
To Replace Steam Coil  
1. Shut off steam supply line to the dryer and run dryer to remove any condensation.  
2. Discontinue electrical power to the dryer.  
3. Break union at flexible hose just before the steam coil at both inlet and outlet.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION: Steam coil and/or piping may be hot, allow time to cool.  
4. Remove remaining piping from steam coil.  
5. Remove six (6) screws holding coil to steam rack and lift core out.  
6. Reverse procedures for installing new core.  
G. TUMBLER and BEARING ASSEMBLY  
(Remove back guard to access assembly)  
Reversing  
To Replace Tumbler Pulley (Reversing)  
1. Loosen V-belts, then rotate pulley and roll V-belts out of grooves.  
2. Remove cap screws securing taper lock hub to pulley.  
3. Insert cap screws in tapped removal holes and tighten evenly until  
bushing becomes loose in pulley. Refer to Figure “A.”  
4. Remove bushing, pulley, and key.  
5. Assemble bushing and pulley as shown in Figure “B.” When cap  
screws are loosely inserted, bushing remains fully expanded to  
provide a sliding fit to the shaft.  
6. Insert key on the shaft, then slide pulley to desired position with  
cap screw heads to the outside.  
FigureA  
7. Tighten cap screws progressively. There remains a gap between  
the pulley hub and the flange of the bushing.  
IMPORTANT: Tighten screws evenly and progressively.  
Never allow the pulley to be in contact with  
the flange of the bearing. This gap should  
measure from 1/8” to 1/4”. Proper cap  
Figure B  
screw torque is 30 ft.-lbs. (4.14 kg-m), if  
greater tightening forces are applied, excess  
pressure will be created in the hub of the  
mounted pulley which may cause it to crack.  
To Replace The Rear Tumbler Bearing  
1. Remove tumbler pulley (follow tumbler pulley removal procedure).  
2. Remove the four (4) bolts securing the bearing box to the back of the dryer.  
3. Loosen set screws securing bearing to shaft.  
4. Pull bearing box and bearing off of shaft.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: If any rust has developed, use an emery cloth to polish the shaft.  
5. Remove bolts securing bearing to bearing box and remove tumbler bearing.  
6. Reverse procedure for installing new tumbler bearing.  
NOTE: Check alignment of pulleys before operating dryer.  
To Replace The Front Tumbler Bearing  
1. Remove tumbler pulley and bearing box (follow “To Replace The Rear Tumbler Bearing” Step #1 through  
Step #4).  
2. Loosen set screws on rear tumbler bearing.  
3. Using a wheel puller gently push the tumbler shaft towards the front through the front tumbler bearing.  
NOTE: An alternate method would be to place a block of wood on the end of the tumbler shaft and  
strike it with a heavy hammer. To prevent damage to the shaft the wheel puller method is  
preferred.  
4. Remove the four (4) nuts securing the bearing to the dryer back and remove the bearing.  
5. Reverse procedure for installing new tumbler bearing.  
NOTE: Check tension of belts and alignment of tumbler before operating dryer.  
6. Replace back guard.  
H. IDLER SHAFT and BEARING ASSEMBLY  
(Remove back guard to access assembly)  
To Replace Idler Pulley  
1. Remove back guard.  
2. Loosen V-belts, then rotate pulley and roll V-belts  
out of grooves.  
3. Loosen the two (2) set screws on the pulley and  
pull off the shaft.  
4. Reverse procedure for installing new idler pulley.  
NOTE: Check tension and alignment of belts before operating dryer.  
To Replace Idler Bearing  
1. Remove idler pulley (follow “To Replace Idler Pulley”).  
2. Remove idler arm.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a. Remove two (2) bolts securing idler arm to the idler backup plate.  
b. Remove idler arm assembly.  
c. Loosen set screws on both the front and rear bearing and remove the idler shaft.  
d. Remove three (3) bolts securing the bearing to the idler arm and remove bearings.  
3. Reverse procedure for installing new idler bearings.  
NOTE: Check tension and alignment of belts before operating dryer.  
I. DRIVE PULLEY  
(Remove back guard to access assembly)  
1. Remove back guard.  
2. Loosen V-belts, then rotate pulley and roll V-belts out of grooves.  
3. Loosen set screws and pull motor pulley off.  
NOTE: If rust has developed on the shaft use an emery cloth to  
polish the shaft.  
4. Reverse procedure for installing new drive pulley.  
NOTE: Check tension and alignment of belts before operating dryer.  
J. TUMBLER (BASKET)  
TumblerAlignment (Vertical)  
1. Discontinue electrical power to the dryer.  
2. Remove back guard.  
3. Loosen the four (4) hex head bolts on the  
sides of the bearing box (2 on each side).  
4. Back off jam nuts on the two (2)Allen head  
adjustment screws at the top of the bearing  
box.  
5. Turn the screws clockwise (CW) evenly  
to raise the tumbler or counterclockwise  
(CCW) evenly to lower the tumbler.  
NOTE: V-belt tension may need to be loosened.  
6. Rotate the tumbler from the front and check alignment with the main door opening.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Leave a larger gap from the inside ring on the top of the front  
panel opening to the tumbler, and a smaller gap on the bottom  
to compensate for the weight of the clothes being dried.  
8. Tighten the four (4) hex head bolts on the sides of the bearing  
box, and the two (2) Allen head adjustment screws.  
9. Replace back guard.  
10. Reestablish electrical power to the dryer.  
TumblerAlignment (Lateral)  
1. Discontinue electrical power to the dryer.  
2. Remove back guard.  
3. Loosen the two (2) hex head bolts, (one turn is enough), that holds the pillow block bearing to the bearing box.  
4. Back off the two (2) jam nuts on the side adjustment bolts. Now rotate the tumbler from the front of the dryer,  
checking the space between the tumbler and the front panel. This should be equal on the left hand and right  
hand side.  
5. Lateral adjustment (viewing from the rear)  
a. Loosening (by turning counterclockwise [CCW]) the left hand adjustment bolt and tightening (by turning  
clockwise [CW]) the right hand adjustment bolt will shift the basket to the right.  
b. Loosening (by turning counterclockwise [CCW]) the right hand adjustment bolt and tightening (by turning  
clockwise [CW]) the left hand adjustment bolt will shift the basket to the left.  
6. Tighten and secure both adjustment bolts and jam nuts.  
7. Tighten the bearing box bolts.  
8. Replace back guard and reestablish electrical power to the dryer.  
To Replace The Tumbler And/Or Tumbler Support  
1. Remove tumbler pulley.  
2. Remove front panel assembly.  
a. Discontinue electrical power to the dryer.  
b. Open control (service) door.  
c. Open lint door.  
d. Remove the screws securing the front panel to the dryer.  
e. Gently remove the top right hand corner of the front panel assembly from the dryer.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
f. Disconnect the main door switch harness at connector.  
IMPORTANT: When removing front panel assembly be careful not to damage door switch wires.  
3. Loosen set screws on rear tumbler bearings.  
4. Using a wheel puller gently push the tumbler shaft towards the front through the tumbler bearings.  
NOTE: An alternate method would be to place a block of wood on the end of the tumbler shaft and  
strike it with a heavy hammer. To prevent damage to the shaft, the wheel puller method is  
preferred.  
5. Remove the tumbler and support through the front of the dryer.  
a. Remove the bolt in the center of the tumbler back wall.  
b. Loosen and remove the nuts and washers from the tumbler tie rods. Remove the rods.  
c. Replace either tumbler or tumbler support by reversing the procedure.  
6. Reassemble components into dryer by reversing Step #1 through Step #4.  
7. Check tumbler lateral and vertical alignment. Also, check belt tension and alignment.  
8. Replace back guard and reestablish electrical power to dryer.  
K. V-BELTS (REFER TO ILLUSTRATIONS IN SECTIONS I and K)  
V-belts should have proper tension. If too loose, they will slip, if too tight excessive wear on the bearing will  
result. If the pulleys are not properly aligned, excessive belt wear will result. Proper belt tension will allow 1/2”  
displacement under normal thumb pressure at mid span of the belt.  
V-Belt TensionAdjustment-Tumbler To Idler  
1. Loosen two (2) bolts connecting idler arm to backup plate.  
2. Back off jam nut on the adjustment bolt.  
3. Tighten belts by turning adjustment bolt clockwise (CW).  
(Turn counterclockwise [CCW] to loosen belts)  
4. Tighten both bolts connecting idler arm to backup plate.  
5. Check vertical plane of idler pulley for parallel alignment  
with tumbler pulley.  
6. If realignment is required, loosen tumbler pulley and move  
tumbler pulley to proper position.  
7. Retighten jam nut.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V-Belt Tension Alignment - Motor To Idler  
1. Loosen two (2) bolts connecting idler arm to backup plate.  
2. Back off on jam nut(s) on the adjusting bolt.  
3. Loosen/tighten adjustment bolt to decrease/increase belt tension.  
4. Tighten adjustment bolt jam nut(s).  
5. Tighten the two (2) bolts loosened in Step #1.  
To Replace V-Belts  
1. Loosen tension on V-belts, so that they can easily be rolled off pulleys.  
2. Replace V-belts.  
3. Retighten V-belts and adjust tension and alignment per previous instructions.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION VI  
PHASE 6 OPL SYSTEM DIAGNOSTICS  
IMPORTANT: You must DISCONNECT and LOCKOUTTHE ELECTRIC, GAS or  
STEAM SUPPLYBEFOREANYCOVERS or GUARDSARE REMOVED  
FROM THE MACHINE TOALLOWACCESS FOR CLEANING,  
ADJUSTING, INSTALLATION, or TESTINGOFANYEQUIPMENT per  
OSHA(Occupational Safety and HealthAdministration) STANDARDS.  
ALL major circuits, including door, microprocessor temperature sensor, heat and motor circuits are monitored.  
The Phase 6 OPL microprocessor controller (computer) will inform the user, via the L.E.D. (light emitting diode)  
display of certain failure codes, along with indicators both in L.E.D. display and at the output of each relay (and  
door switch circuit) to easily identify failures.  
A. DIAGNOSTIC (L.E.D. DISPLAY) FAILURE CODES  
1. SAIL SWITCH FAIL- This routine will prevent start up on the machine unless the sail switch is in the  
correct position. If the sail switch is closed prior to start up the display will read “SAIL SWITCH FAIL”  
along with an audio indication.  
2. No AIRFLOW- If the sail switch opens during cycle operation the display will read “No AIRFLOW”  
along with an audio indication. The machine will continue to run with no heat for three (3) minutes or until  
the temperature drops below 100º F (38º C). Upon failure the machine will shut down and display “No  
AIRFLOW” with an audio indication.  
3. bURNER SAFETY FAIL- Routine monitors the temperature above the burner. If the Burner Hi-Limit  
switch opens the display will read “bURNER SAFETY FAIL.” The machine will run with no heat for  
three (3) minutes or until the temperature drops below 100º F (38º C). Upon failure the machine will shut  
down and display “bURNER SAFETY FAIL” with an audio indication.  
4. dRUM SAFETY FAIL- This routine monitors the tumbler temperature of the tumbler Hi-Limit switch  
opens prior or during the cycle while the heat was on the machine will display “dRUM SAFETY FAIL.”  
The machine will continue to run with no heat for three (3) minutes or until the temperature drops below  
100º F (38º C). Upon failure the machine will shut down and display “dRUM SAFETY FAIL” with an  
audio indication.  
5. No HEAT- This routine monitors the burner ignition. If the burner mis-ignites (does not light) the HSI  
(Hot Surface Ignition) module will check to see of the microprocessor program has any retries left. The  
standard retry count is two (2). If the module notices that there are retries left it will purge for one (1)  
minute then try to ignite the burner again. The HSI module will try this for a total of three (3) times or  
until there are no retries left. If the burner does not ignite after three attempts the L.E.D. display will  
display the error code “no heat” with an audio indication. When this occurs the machine will run with no  
heat for three (3) minutes or until the temperature drops below 100º F (38º C).  
IMPORTANT: For other countries, such asAustralia, the retry count may not apply due to local  
approvals.  
6. bURNER CONTROLFAIL- This routine monitors the ignition control’s gas valve output response. If  
the valve output signal is not present from the ignition control within the valve time limits the Phase 6  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
microprocessor controller (computer) determines the ignition control has failed. If this occurs when the  
cycle is active the machine will display “bURNER CONTROL FAIL.” If the tumbler temperature is  
above 100º F (38º C) the machine will continue to display “bURNER CONTROL FAIL.” The machine  
will run with no heat for three (3) minutes or until the temperature drops below 100º F (38º C). If the  
tumbler temperature is below 100º (38º C) upon failure the machine will shut down and display “bURNER  
CONTROL FAIL” with an audio indication.  
7. bURNER FLAME FAIL- This routine allows two (2) Flame out retries to occur before proceeding  
into the error. The count of two (2) will be established every time the call for heat was to occur. Only if  
it reaches the count of two (2) before the tumbler temperature has reached the set temperature will this  
error be triggered. The machine will run with no heat for three (3) minutes or until the temperature drops  
below 100º F (38º C). If the tumbler temperature is below 100º F (38º C) upon failure, the machine will  
shut down and display “bURNER FLAME FAIL” with an audio indication. This process will occur  
every time the heat output is active.  
8. MAIN DOOR- This monitors the door circuit. If the machine was not active and the main door was  
opened the display would ready “REAdY. If a program attempt was made with the main doors open the  
display will read “MAIN dOOR” with an audio indication. If the machine is active and the main door  
was opened the display would read “MAIN dOOR” with no audio indication and the dryer will shut  
down. Once the main door has closed the display would read “PRESS START” press the “ENTER/  
START” key and it will continue the programmed cycle.  
9. LINT dOOR- This monitors the lint drawer and door circuit. If the machine was not active and the lint  
drawer and door was opened the display would read “REAdY. If a program attempt was made with the  
lint drawer and door open the display would read “LINT dOOR” with an audio indication. If the machine  
is active and the lint drawer and door was opened the display would read “LINT dOOR” with no audio  
indication and the dryer will shut down. Once the lint door was closed the display would read “PRESS  
START” press the “ENTER/START” key and it will continue the programmed cycle.  
10. TEMP SENSOR FAIL CHECK TEMP SENSOR FUSE- This routine monitors the tumbler  
temperature. When the temperature sensor or fuse opens with the machine not active the display will  
read “TEMP SENSOR FAIL CHECK TEMP SENSOR FUSE” with an audio indication. If the machine  
was active at the time that the temperature sensor or fuse opened the display would read “TEMP  
SENSOR FAIL CHECK TEMP SENSOR FUSE.” If the tumbler temperature is above 100º F (38º C)  
the machine will continue to display “TEMP SENSOR FAIL CHECK TEMP SENSOR FUSE” with an  
audio indication and run with no heat for three (3) minutes or until the temperature drops below 100º F  
(38º C). If the tumbler temperature is below 100º F (38º C) upon failure the machine will shut down and  
display “TEMP SENSOR FAIL CHECK TEMP SENSOR FUSE” with an audio indication. The display  
will continue to read “TEMP SENSOR FAIL CHECK TEMP SENSOR FUSE” an audio indication will  
sound for approximately 5 seconds, every 30 seconds until the problem is corrected or the power to the  
dryer is disconnected (and the problem is corrected).  
NOTE: Once the Phase 6 microprocessor controller (computer) detects a problem in the heat circuit,  
it updates every 30 seconds, so that if the problem was a loose connection in the circuit which  
corrected itself, the “TEMPSENSOR FAILCHECK TEMPSENSOR FUSE” condition  
would automatically be cancelled and the display will return to “REAdY.”  
11. ROTATE SENSOR FAIL- Indicates a rotational sensor circuit failure meaning that there is a fault  
somewhere in the basket (tumbler) rotating circuit, or the Phase 6 OPL microprocessor controller (com-  
puter) program related to this circuit (program location 2) is set incorrectly. In the active mode it should  
be (ROTATE SENSOR ACTIVE), if the dryer is not equipped with the optional rotational sensor it  
should be set in the nonactive mode (No ROTATE SENSOR).  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: RPM- This routine monitors the timing response from the existing rotational sensor input and  
derives a RPM measurement. To display this RPM measurement (press the “ENTER/  
START” key once and release, then press the “ENTER/START” key a second time and hold.  
This will display the RPM measurement). The rotational sensor must be active for operation  
of this feature.  
12. CHECK MAIN FUSE- Indicates that the circuit fuse protection which is located on the back side of  
the Phase 6 microprocessor controller (computer) the display would read “CHECK MAIN FUSE.” If  
the display continues after the fuse has been replaced then it is the fault of the Phase 6 microprocessor  
controller (computer).  
B. L.E.D. (LIGHT EMITTING DIODE) DISPLAY INDICATORS  
The L.E.D. (light emitting diode) indicator dots located on the top portion of the display indicates various Phase 6  
OPL computer output functions while a cycle is in progress. These indicator dots (as shown in the illustration  
below) do not necessarily mean that the outputs are functioning. They are only indicating that the function output  
should be active (on).  
1. L.E.D. DISPLAY INDICATOR NUMBER 1  
a. For Optional Reversing Models:  
1. This indicator dot is on when the drive (basket [tumbler]) motor is operating in the forward mode  
(clockwise direction).  
2. L.E.D. DISPLAY INDICATOR NUMBER 2  
a. For Optional Reversing Models:  
1. This indicator dot is on when the drive (basket [tumbler]) motor is operating in the reverse mode  
(counterclockwise direction).  
3. L.E.D. DISPLAY INDICATOR NUMBER 3  
a. Heat Circuit Indicator:  
1. This indicator dot is on whenever the Phase 6 OPL microprocessor controller (computer) is calling  
for the heating circuit to be active (on).  
4. L.E.D. DISPLAY INDICATOR NUMBER 4  
a. On Indicator:  
1. This indicator dot is on whenever a cycle is in progress. Additionally, when the Anti-Wrinkle  
program is active, the indicator dot will be on whenever the Phase 6 OPL microprocessor controller  
(computer) is in the Guard On Time program.  
5. L.E.D. DISPLAY INDICATOR NUMBER 5  
a. Air Jet Circuit - OPTIONAL  
1. This indicator dot is on at the end of the dryer cycle for approximately 60 seconds.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. PHASE 6 OPL MICROPROCESSOR CONTROLLER RELAY  
OUTPUT L.E.D. INDICATORS  
There are a series of five (5) L.E.D. (light emitting diode) indicators (ORANGE LIGHTS) located at the backside  
are of the Phase 6 OPL microprocessor controller (computer). These are identified or labeled (from top to  
bottom in the illustration below as: FAN-BLOWER, FOR-FORWARD, REV-REVERSE, AIR-AIR-JET, HT1-  
HEAT OUTPUT. There are a series of seven (7) L.E.D. indicators (red lights) FUSE-MAIN FUSE, LINT-  
LINT DOOR, MAIN-MAIN DOOR, DRUM-TUMBLER HI-LIMIT, SAIL-SAIL SWITCH, BURN-BURNER  
HI LIMIT, FLAME-FLAME PROBE). The L.E.D. in the center of the board (red light) indicates power  
supplied to the Phase 6 OPL microprocessor controller (computer). These L.E.D.’s indicate the inputs and  
outputs of the Phase 6 OPL microprocessor (computer) as it monitors the safety circuits.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. “FAN” (BLOWER) Output L.E.D. (light emitting diode) Indicator  
A. If the dryer is started and the blower motor is not operating, yet the Phase 6 OPL microprocessor  
controller (computer) display fan indicator dot and power supply input L.E.D. are on, but the fan  
output L.E.D. is off, then the fault is the Phase 6 OPL microprocessor controller (computer) itself.  
1. If the motor is not operating. The fan indicator dot and output L.E.D. are also on, then the problem  
(fault) is elsewhere (i.e., external of the Phase 6 OPL microprocessor controller [computer]).  
2. “FOR” (FORWARD) Output L.E.D. Indicator (for optional reversing model ONLY)  
A. If the dryer is started and the blower motor is operating, but the drive (basket/tumbler) motor is not, yet  
the Phase 6 OPL microprocessor controller (computer) display “FORWARD” indicator dot is on, the  
“FOR” (FORWARD) motor output L.E.D. is off; then the fault is the Phase 6 OPL microprocessor  
controller (computer) itself.  
1. If the drive (basket and tumbler) motor is not operating and the forward indicator dot and output  
L.E.D. in on; then the problem (fault) is elsewhere (i.e., external of the Phase 6 OPL microprocessor  
controller [computer]).  
3. “REV” (REVERSE) Output L.E.D. Indicator (for optional reversing models ONLY)  
A. If the dryer is started and the blower motor is operating but the drive (basket and tumbler) motor is not,  
yet the Phase 6 OPL microprocessor controller (computer) displays “REVERSE” indicator dot is on  
but the “REV” (REVERSE) motor output L.E.D. is off; then the fault is of the Phase 6 OPL  
microprocessor controller (computer) itself.  
1. If the drive (basket and tumbler) motor is not operating and reverse indicator dot and output L.E.D.  
is on; then the problem (fault) is elsewhere (i.e., external of the Phase 6 OPL microprocessor  
controller [computer]).  
4. “AIR” (AIR JET) Output L.E.D. Indicator - OPTIONAL  
A. “AIR” is on with the display dot at the end of the dry cycle once the display reads “dONE,” it is on for  
approximately 60 seconds and the output L.E.D. indicator and the display dot go out. If the air jet does  
not energize it is not the fault of the Phase 6 OPL microprocessor controller (computer). If the output  
L.E.D. or dot do not go on it is the fault of the Phase 6 OPL microprocessor controller (computer).  
5. “HT1” (HEAT) Output L.E.D. Indicator  
A. If the dryer is started and there is “No Heat” yet the Phase 6 OPL microprocessor controller (computer)  
display heat circuit indicator dot is on, but the “HT1” output L.E.D. indicator is off; then the fault is in  
the Phase 6 OPL microprocessor controller (computer) itself.  
1. If the dryer is started and there is “No Heat” yet both the Phase 6 OPL microprocessor controller  
(computer) display indicator dots and the “HT1” output L.E.D. indicator are on; then the problem  
(fault) is elsewhere (i.e., external of the Phase 6 OPL microprocessor controller [computer]).  
6. “FUSE” (MAIN FUSE) Input L.E.D. Indicator  
A. Should be on ALL the time (even if the dryer is not running). If the L.E.D. is not on; then the display  
will read “CHECK MAIN FUSE.” If the main fuse is good then the fault is on the Phase 6  
microprocessor controller (computer).  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. “LINT” (LINT DOOR) Input L.E.D. (light emitting diode) Indicator  
A. Should be on ALL the time (unless the lint door is opened then the “LINT” L.E.D. indicator will go  
out).  
B. If the dryer is active (running) and the lint door is opened the “LINT” L.E.D. indicator will go out and  
the display will read “LINT dOOR.” The dryer will stop until the Lint Drawer has been closed, at  
which time the L.E.D. display will read “PRESS START.” At this time, to resume the drying cycle  
press “ENTER/START” key.  
8. “MAIN” (MAIN DOOR) Input L.E.D. Indicator  
A. Should be on ALL the time (unless the lint door is open or the main door is opened then the “MAIN”  
L.E.D. indicator will go out).  
B. If the dryer is active (running) and the main door is opened the “MAIN” L.E.D. indicator will go out  
and the display will read “MAIN dOOR.” The dryer will stop until the main door has been closed, at  
which time the L.E.D. display will read “PRESS START.” At this time, to resume the drying cycle  
press “ENTER/START” key.  
9. “DRUM” (TUMBLER HI-LIMIT) Input L.E.D. Indicator  
A. Should be on at ALL times (unless the tumbler hi-limit switch opens prior during the cycle while the  
heat was on the display would read “dRUM Safety FAIL”). The machine will run with no heat for  
three (3) minutes or until the temperature drops below 100º F (38º C). Then the machine will shut  
down still displaying “dRUM SAFETYFAIL” with an audio indication.  
10. “SAIL” (SAIL SWITCH) Input L.E.D. Indicator  
A. This routine will prevent start up on the machine unless the sail switch is in the correct position. If the  
sail switch is in the closed position prior to start, the “SAIL” output L.E.D. indicator will be off, the  
machine will not start and the display will read “SAILSWITCH FAIL” along with an audio indication.  
B. If the sail switch opens during the cycle the “SAIL” output L.E.D. will go out and the display will read  
“NO AIRFLOW.” The machine will run with no heat for three (3) minutes or until the temperature  
drops below 100º F (38º C). Then the machine will shut down still displaying “NOAIRFLOW” along  
with an audio indication.  
11. “BURN” (BURN HI-LIMIT) Input L.E.D. Indicator  
A. This routine monitors the temperature of the burner. If the burner hi-limit opens during the cycle while  
the heat was on the “BURN” output L.E.D. indicator goes out and the display reads “bURNER  
SAFETY FAIL.” The machine will run with no heat for three (3) minutes or until the temperature  
drops below 100º F (38º C) then the machine will shut down still displaying “bURNER SAFETY  
FAIL” with an audio indication.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12. “FLAME” (bURNER CONTROL FAIL) Input L.E.D. (light emitting diode) Indicator  
A. This routine monitors the ignition control’s gas valve output response. If the valve output signal is not  
present from the ignition control within the valve time limits the microprocessor determines the ignition  
control has failed. If this occurs when the cycle is active the “FLAME” output L.E.D. indicator will  
go out and the display will read “bURNER CONTROL FAIL.” The machine will run with no heat for  
three (3) minutes or until the temp drops below 100º F (38º C). Then the machine will shut down still  
displaying “bURNER CONTROL FAIL” with an audio indication.  
13. “POWER SUPPLY” Input L.E.D. Indicator  
A. Should be on at ALL times (even if the dryer is not running). The power supply L.E.D. output  
indicator will not be on if the power supply fuse to the Phase 6 OPL microprocessor is not present. If  
the power supply fuse is bad the L.E.D. output will be off and there will be no display or keypad  
function. The “FUSE,” LINT,” and “DRUM” output L.E.D. indicators will remain on.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. L.E.D. CODES  
1. Display Codes  
A
SLOPE FACTOR  
ALL REV  
ALWAYS REVERSING  
ANTI WRINKL dELAY TIME  
ANTI WRINKL GUARd ACTIVE  
ANTI WRINKL GUARd ON TIME  
AUTO CYCLE  
ANTI-WRINKLE DELAY TIME  
ANTI-WRINKLE PROGRAM ACTIVE  
ANTI-WRINKLE GUARD ON TIME  
AUTOMATIC MODE  
b
HEAT LOSS (OFF SET) FACTOR  
GAS ONLY POWER (24VAC) IS NOT EVIDENT AT GAS VALVE  
NO BURNER FLAME SENSED  
GAS/ELECTRIC ONLY BURNER/OVEN OPEN HI-LIMIT CIRCUIT  
BUZZER (TONE)  
bURNER CONTROL FAIL  
bURNER FLAME FAIL  
bURNER SAFETY FAIL  
bUZZ  
bUZZ TIME  
CEL  
BUZ TIME  
DEGREE IN CELSIUS  
CHECK MAIN FUSE  
CLEAN LINT  
COOL  
COOL TIME_M  
COOL TEMP_  
CYCLEA  
MAIN FUSE FAILURE  
PROMPT TO CLEAN LINT SCREEN, DRYER CYCLE LOCK-OUT  
COOL DOWN CYCLE IN PROGRESS  
COOL DOWN TIME  
COOL DOWN TEMPERATURE  
PREPROGRAMMED CYCLE A  
CYCLEb  
PREPROGRAMMED CYCLE B  
CYCLEC  
PREPROGRAMMED CYCLE C  
CYCLED  
PREPROGRAMMED CYCLE D  
CYCLEE  
PREPROGRAMMED CYCLE E  
CYCLEF  
PREPROGRAMMED CYCLE F  
dONE  
dRYING  
DRYING or COOLING CYCLE COMPLETE OR DRYER IN ANTI-WRINKLE MODE  
DRYING CYCLE IN PROGRESS  
dRY LEVEL_  
dRY TEMP F_  
dRY TIME_M  
dRUM SAFETY FAIL  
ELAPSE TIME_MIN  
ELECTRIC  
DRYNESS LEVEL (PERCENTAGE OF EXTRACTION) (NUMERICAL VALUE)  
DRYING TEMPERATURE  
LENGTH OF DRYING CYCLE  
TUMBLER HI-LIMIT CIRCUIT IS OPEN  
CYCLE DISPLAY TIME  
SPECIFIC HEAT TYPE OR DRYER ELECTRICALLY HEATED  
FABRIC TEMPERATURE  
F
FAR  
DEGREE IN FAHRENHEIT  
FLASH  
FLASH DISPLAY ACTIVE  
GAS  
HOT  
SPECIFIC HEAT TYPE OF DRYER GAS HEATED  
INDICATES AN OVERHEAT CONDITION  
LINT DRAWER/DOOR CIRCUIT IS OPEN OR FAULT IN THE A.C. SWITCH CIRCUIT  
DRYING CYCLES RANGE FROM 1-10 CYCLES BEFORE CLEAN LINT DISPLAY  
CYCLE DISPLAY TIME  
DOOR CIRCUIT IS OPEN OR FAULT IN THE A.C. DOOR SWITCH CIRCUIT  
MANUAL MODE  
MAXIMUM GUARD TIME  
LINT dOOR  
LINT COUNT  
_M REMAIN  
MAIN dOOR  
MANUAL CYCLE  
MAX ANTI WRINKL GUARd  
NFLASH  
FLASH DISPLAY NOT ACTIVE  
NoAIR FLOW  
NoANTI WRINKL GUARd  
NoBUZZ  
SAIL SWITCH OPEN  
ANTI-WRINKLE PROGRAM IS NOT ACTIVE  
NO BUZZER (TONE)  
NoHEAT  
NoREV  
GAS ONLY IGNITION ATTEMPT FAILURE  
NO REVERSE  
NoROTATE SENSOR  
PROGRAM  
NO ROTATIONAL SENSOR SELECTED  
PROGRAM MODE  
REAdY  
NO CYCLE IN PROGRESS  
ROTATE SENSOR ACTIVE  
ROTATE SENSOR FAIL  
_RPM  
ROTATIONAL SENSOR SELECTED  
ROTATIONAL SENSOR CIRCUIT FAILURE  
MONITORS TUMBLER RPM WITH ROTATIONAL SENSOR CIRCUIT ACTIVE  
GAS/ELECTRIC ONLY ATTEMPT MADE TO START DRYER WITH SAIL  
SWITCH DISABLED IN CLOSED POSITION  
SELET REVERSE  
SAIL SWITCH FAIL  
SELREV  
SPIN TIME  
SPIN TIME  
START GUARd  
STEAM  
STOP TIME  
START ANTI WRINKLE GUARD CYCLE  
SPECIFIC HEAT TYPE OR DRYER STEAM HEATED  
STOP TIME  
TEMP SENSOR FAIL CHECK  
TEMP SENSOR FUSE  
FAULT IN M.P. HEAT SENSING CIRCUIT  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E. FAULT CODES  
bURNER CONTROL FAIL  
- GAS MODELS ONLY POWER (24 VAC) IS NOT EVIDENT AT GAS VALVE  
bURNER FLAME FAIL  
- The Phase 6 Microprocessor Controller (computer) DOES NOT SENSE  
FLAME VERIFICATION (GAS MODEL ONLY)  
bURNER SAFETY FAIL  
- GAS/ELECTRIC ONLY BURNER/OVEN OPEN HI-LIMIT CIRCUIT  
dRUM SAFETY FAIL  
- Fault in the TUMBLER HI-LIMIT CIRCUIT  
HOT  
- Indicates an OVERHEAT CONDITION  
LINT dOOR  
- When the LINT DOOR OR DRAWER is open or there is a fault in the LINT  
DOOR/DRAWER CIRCUIT  
MAIN dOOR  
- When the MAIN DOOR is open or there is a fault in the DOOR CIRCUIT  
No AIRFLOW  
- Fault in the SAIL SWITCH CIRCUIT (GAS/ELECTRIC MODELS ONLY)  
No HEAT  
- GAS ONLY IGNITION ATTEMPT FAILURE  
ROTATE SENSOR FAIL  
- Fault in the ROTATION SENSOR CIRCUIT  
SAIL SWITCH FAIL  
- Fault in the SAIL SWITCH CIRCUIT (GAS/ELECTRIC MODELS ONLY)  
TEMP SENSOR CHECK TEMP SENSOR FUSE  
- Fault in the MICROPROCESSOR TEMPERATURE SENSOR CIRCUIT  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION VII  
TROUBLESHOOTING  
WARNING: YOU MUST DISCONNECT and LOCKOUTTHE ELECTRIC SUPPLYand  
THE GAS SUPPLYorTHE STEAM SUPPLYBEFOREANYCOVERS or  
GUARDSARE REMOVED FROM THE MACHINE TOALLOWACCESS  
FOR CLEANING,ADJUSTING, INSTALLATION, orTESTINGOFANY  
EQUIPMENTper OSHA(Occupational Safety and HealthAdministration)  
STANDARDS.  
The information provided will help isolate the most probable component(s) associated with the difficulty described.  
The experienced technician realizes, however, that a loose connection or broken/shorted wire may be at fault  
where electrical components are concerned...not necessarily the suspected component itself. Electrical parts  
should always be checked for failure before being returned to the factory.  
IMPORTANT: When replacing blown fuses, the replacement must be of the exact rating as the fuse  
being replaced. The information provided should not be misconstrued as a  
handbook for use by an untrained person in making repairs.  
WARNING: ALL SERVICE and TROUBLESHOOTING SHOULD BE PERFORMED BYA  
QUALIFIED PROFESSIONALor SERVICEAGENCY.  
WARNING: WHILE MAKING REPAIRS, OBSERVE ALL SAFETYPRECAUTIONS  
DISPLAYED ON THE DRYER or SPECIFIED IN THIS MANUAL.  
A. No L.E.D. (light emitting diode) display on microprocessor controller (computer)...  
1. Open circuit breaker switch or blown fuse.  
2. Tripped blower motor overload.  
3. Faulty wiring connection.  
4. Faulty transformer.  
5. “EMERGENCY STOP” (E-Stop) button is depressed.  
6. Faulty microprocessor controller (computer).  
B. Computer will not accept keypad (touchpad) entries...  
1. Keypad (touchpad) ribbon is not plugged into computer securely.  
2. Faulty keypad (touchpad).  
3. Faulty microprocessor controller (computer).  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Dryer will not start, but computer display indicators are on...  
1. Failed contactors.  
2. Failed arc suppressor (A.S.) board.  
3. Failed microprocessor controller (computer).  
4. Failed motors.  
D. Drive motor runs, burner is on, but basket will not turn...  
1. Broken, damaged or loose V-belt.  
2. Belts contaminated (oil, grease, etc.).  
3. Loose or broken pulley.  
E. Dryer operates but is taking too long to dry...  
1. Improperly programmed microprocessor controller (computer).  
2. An inadequate exhaust duct work system.  
3. Restriction in exhaust system.  
4. Insufficient make-up air.  
5. Poor housekeeping.  
Dirty or clogged lint screen.  
6. Washing machine extractors are not performing properly.  
7. An exceptionally cold/humid or low barometric pressure atmosphere.  
8. The supply gas may have a low heating valve...check with local gas supplier.  
9. Failed temperature sensor (temperature calibration is incorrect).  
10. Failed microprocessor controller (computer).  
F. Thermal overload for drive motor is tripping...  
1. Either an exceptionally low or high voltage supply.  
2. Motor bearing failure.  
3. Motor vents are blocked with lint.  
4. Failed motor.  
5. Failed overload.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Out of balance impellor (fan).  
7. Insufficient make-up air.  
G. Overload for impellor (fan) motor is tripping...  
1. Either an exceptionally low or high voltage supply.  
2. Motor bearing failure.  
3. Motor vents are blocked with lint.  
4. Failed motor.  
5. Failed overload.  
6. Insufficient make-up air.  
H. Burner hi-limit safety thermostat is tripping...  
1. Insufficient exhaust duct work, size, or restriction in exhaust system.  
2. Insufficient make-up air.  
3. Lint screen needs cleaning.  
4. Damaged impellor.  
I. L.E.D. (light emitting diode) display reads “Temp Sensor Failure Check Temp Sensor Fuse”...  
1. Check 1/8-amp fuse on microprocessor (computer).  
2. Faulty microprocessor temperature sensor probe.  
3. Open circuit in either one of two (2) wires leading from the sensor probe to the computer...  
a. Connection at sensor bracket assembly connector.  
b. Connection at computer harness connector.  
4. Faulty microprocessor controller (computer).  
J. Dryer does not start...display reads “main door” or “lint door” with an audio indication...  
1. Main door is open.  
2. Lint drawer is open.  
3. Faulty main door or lint door switch.  
4. Open circuit in either main door or lint drawer switch harnesses.  
5. Faulty 24 VAC transformer.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
K. There is excessive vibration coming from the basket...  
1. Basket is out of adjustment.  
2. Drive shaft or idler shaft is out of alignment.  
3. Faulty pillow block bearing.  
4. Faulty tumbler wheel.  
5. Drive motor and shaft not aligned.  
6. Faulty retaining wheel.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION VIII  
ELECTRICAL TROUBLESHOOTING  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. No Display Condition  
a. Check fuse 1 or 2 and if either are blown, replace.  
b. Take voltage reading across the microprocessor (J7) 9-pin connector pins 1 and 2. If no voltage is present  
at pins 1 and 2, double check the secondary (24 VAC) side of transformer at the blower motor contactor  
number 13 to ground if voltage is present. Problem is bad wire or faulty connection from blower motor  
contactor #13 back through J2 9-pin connector and then to computer connector pin 1.  
c. Check primary voltage to the 24 VAC transformer. (208-240 VAC). If voltage replace the transformer.  
If no voltage check blower motor. Overload to see if tripped. If tripped reset, if not tripped check  
incoming to power block -- (L1, L3).  
NOTE: In this next section ALL voltage checks must be done in the operating mode with the  
appropriate microprocessor dot on. Also appropriate L.E.D. (light emitting diode) output light  
on.  
NOTE: In this next section when checking for voltage you are looking for 25AC volts unless  
otherwise specified.  
2. Drive motor reverses but does not forward, blower motor runs  
a. If computer dot (first dot on the left) does not come on replace the computer.  
b. Check for voltage across the coil of the forward contactor located in the reversing panel box. The  
contactor according to your diagram is marked CR2. The coil markings A1 and A2.  
If voltage is present, replace reversing contactor.  
If voltage is not present, there is a bad wire or termination between BS2 and contactor coil (CR2).  
c. If there is voltage across the two (2) AS2 terminals and no voltage across the two (2) BS2 terminals,  
replace the arc suppressor board.  
If there is no voltage across the two (2) AS2 terminals on the arc suppressor (A.S.) board, the problem is  
a bad wire or termination between the AS2 board and the J7 9-pin computer connector no. 8 or faulty  
computer.  
3. Drive motor works in forward mode but does not reverse, blower motor runs  
a. If computer dot (second one from left) does not come on, check program to see if set for reverse.  
b. If set for reverse, replace computer.  
c. Check for voltage across the coil of the reversing contactor located in the rear panel box. The contactor  
according to your diagram is CR3, also the markings on the coil are A1 and A2.  
If there is voltage, replace the coil or the complete contactor.  
If there is no voltage, check for voltage across the two (2) BS3 terminals on the arc suppressor (A.S.)  
board.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If there is voltage across the two BS3 terminals and no voltage across the coil of the reversing contactor  
(A1 and A2), the problem is bad wires or terminations between BS1 and the contactor coil.  
d. If there is no voltage between the two (2) BS3 terminals on the arc suppressor board, check for voltage  
across the two (2) AS3 terminals on the board.  
If there is voltage across the two (2) AS3 terminals and no voltage across the two (2) BS3 terminals,  
replace the arc suppressor board.  
If there is no voltage across the two (2) AS3 terminals, the problem is bad wires or terminations between  
the arc suppressor board and the computer 9-pin connector no. 9 or a faulty computer.  
4. Blower motor does not operate, drive motor runs  
a. Check for voltage across terminalsA1 andA2 of the impellor contactor. This is the single contactor in the  
reversing control box.  
If voltage is present check for voltage across the blower motor. If there is voltage at the blower motor  
replace the motor.  
If there is no voltage at the blower motor, the problem is bad wires or terminations between the contactor  
and the motor.  
b. If there is no voltage present at A1 and A2 of the contactor, check for voltage across the two (2) BS1  
terminals of the arc suppressor (A.S.) board.  
If there is voltage present at the two (2) BS1 terminals, the problem is bad wires or terminations between  
the two (2) BS1 terminals and the coil (A1 and A2) terminals.  
If there is no voltage across the two (2) BS1 terminals, check for voltage across the two (2)AS1 terminals.  
If there is voltage across the two (2) AS1 terminals and there is no voltage between the two (2) BS1  
terminals, replace the arc suppressor (A.S.) board.  
c. If there is no voltage across the two (2) AS1 terminals, the problem is bad wires or terminations between  
the two (2) AS1 terminals and the computer board J7 9-pin connector no. 7 or faulty computer.  
5. Lint Door Condition  
NOTE: Make sure main door and lint door are closed. Also, if checking either switch, the plunger  
must be depressed.  
a. Check L.E.D. (light emitting diode) input light “LINT” on the component side of the computer. If the light  
is on, replace the microprocessor controller (computer).  
b. Check voltage (24 VAC) from J7 9-pin connector no. 3 to ground. If voltage is present check no. 4 to  
ground if voltage is present replace microprocessor controller (computer).  
c. If no voltage is present at J7 9-pin connector no. 4 to ground, but voltage is present at no. 3 to ground. The  
problem is a bad switch, wires or termination between J7 to J11 and J11 to the lint switch.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
d. If no voltage is present at J7 9-pin connector no. 3 to ground, then voltage should not be present at no. 5  
to ground. Replace the microprocessor controller (computer).  
6. Main Door Condition  
NOTE: Make sure main door and lint door are closed. Also, if checking either switch, the plunger  
must be depressed.  
a. Check L.E.D. (light emitting diode) input light “MAIN” on the component side of the computer. If the  
light is on, replace the computer.  
b. Check voltage (24 VAC) from J7 9-pin connector no. 5 to ground. If voltage is present, check no. 6 to  
ground. If voltage is present, replace board.  
c. If no voltage is present at J7 9-pin connector no. 6 to ground, but voltage is present at no. 5 to ground. The  
problem is a bad switch, bad wires or terminations J7 to J5, or J5 to main door switch.  
7. “No Heat” drive and blower motors run, display reads normal (gas models).  
a. Check L.E.D. input light “HT1” on the component side of the computer. If the light is on replace the  
board.  
b. If the L.E.D. input light “HT1” on the component side of the computer is on and there is no voltage to the  
Hot Surface Ignitor (HSI) module “w” the display will read “BURNER CONTROLFAIL.” The problem  
is bad wires or terminations between microprocessor and HSI module.  
c. If voltage is present on the HSI module “w” to ground. Check voltage at the gas valve if voltage is present  
across the two (2) “yellow” wires at the gas valve and the gas supply is on then the fault is that of the gas  
valve.  
8. “Temp Sensor Fail Check”  
a. Replace the temperature sensor underneath the basket on a bracket (the bullet shaped device).  
b. If it still read “TEMP SENSOR FAIL CHECK TEMP SENSOR FUSE,” unplug J3 4-pin connector from  
the temperature sensor bracket. Also, unplug the microprocessor J14 4-pin connector from the computer  
board. Take a continuity reading from J14 no. 1 to J3 no. 1, then from J14 no. 2 to J3 no. 2.  
If there is no continuity, check for break in wire, a short to the ground, loose terminations, or even replace  
the wire.  
If there is continuity, microprocessor controller (computer) is faulty.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION IX  
TECHNICALINFORMATION  
The following section contains various technical information important to the service person in servicing and  
maintaining the dryer.  
A. MOTOR PLATE (HIGH and LOW VOLTAGE)  
The motor plate is located on the side of the drive motor (see illustration) and contains a graphical representation  
of the motor wiring for both low and high voltage ratings.  
Removing the cap reveals the wiring to the motor. On each wire there is a number which corresponds to the  
numbers on the motor plate. Depending on whether the dryer is operating on low or high voltage, the wiring  
should match the motor plate as follows:  
The dots and lines represent connections (refer to the illustration above).  
For example:  
On low voltage - wire no. 14 connected to wire no. 4  
- wire no. 1 is connected to wire no. 7, which in turn are both connected to L1  
On high voltage - wire no. 14 is insulated or capped  
- wire no. 4 is connected to wire no. 7  
- wire no. 1 is connected to L1  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. DATALABEL  
Contact American Dryer Corporation  
When contacting American Dryer Corporation certain information is required to insure proper service/parts  
information from American Dryer. This information is on the data label located on the inside of the control door.  
When contacting American Dryer please have the model number and serial number available.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THE DATA LABEL  
1. MODEL DRYER  
The model number is an ADC number which describes the size of the dryer and the  
type of heat (gas, electric, or steam).  
2. SERIAL NUMBER  
The serial number allows ADC to gather information on your particular dryer.  
3. MANUFACTURING CODE NUMBER  
The manufacturing code number is a number issued by ADC which describes ALL  
possible options on your particular model.  
4. TYPE OF HEAT  
The type of heat describes the type heat for your particular dryer; gas (either natural  
gas or liquid propane [L.P.]), or steam.  
5. HEAT INPUT (for GAS DRYERS)  
This describes the heat input in British Thermal Units per Hour (BTUH).  
6. ORIFICE SIZE (for GAS DRYERS)  
Gives the number drill size used.  
7. ELECTRIC SERVICE  
This describes the electric service for your particular model.  
8. GAS MANIFOLD PRESSURE (for GAS DRYERS)  
This describes the manifold pressure taken at the gas valve tap.  
9. APPLICABLE APPROVAL SEAL(S)  
I.E., American Gas Association, Canadian Gas Association.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT  
MANUAL RESET HI-LIMIT INSTRUCTIONS  
FOR PHASE 6 MODELS  
This dryer was manufactured with a manual reset burner hi-limit thermostat which is monitored by the Phase 6  
computer. If the manual reset burner hi-limit thermostat is open prior to the start of the machine, the dryer will  
start momentarily and the shut down displaying “burner safety fail” with an audio indication.  
If the manual reset burner hi-limit opens during a drying cycle, the display will read “burner safety fail” with an  
audio indication. If the drum temperature is above 100º F (38º C), the dryer will continue to run with no heat for  
three minutes or until the drum temperature has fallen below 100º F (38º C). The clear and stop button on the  
Phase 6 keypad must be pressed to clear this “burner safety fail” condition. The manual reset burner hi-limit  
switch must be reset “manually” prior to the start of the next drying cycle.  
This hi-temperature condition may be caused due to a restricted exhaust, poor airflow or improper burner oven  
operation.  
The location of the manual reset hi-limit switch is on the right side of the burner box.  
IMPORTANT  
HEATING UNIT IS EQUIPPED WITHA  
HI-LIMITTHERMOSTAT  
WHICH MUST BE RESET MANUALLY.  
WARNING - DISCONTINUE POWER  
TO DRYER BEFOREATTEMPTING TO  
RESETHI-LIMIT.  
ADC P/N: 114076  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. COMPUTER LOGIC  
1. Operator enters desired selections.  
2. Information entered is sent to the microprocessor via the keyboard (touchpad).  
3. The input information is sorted, processed and executed by the microcomputer chip.  
4. The microcomputer output signal activates the contactors and HSI (Hot Surface Ignition) module which  
control machine functions.  
The wiring diagrams used in troubleshooting are specifically for dryers manufactured at the time of publishing.  
Your particular model may vary slightly depending on the date of manufacturing and options available. The  
correct wiring diagram and number is either taped to the rear of the control door or each dryer, or placed in the  
control box. If your particular diagram is lost or unreadable, call ADC with the serial number of the dryer. ADC  
will be more than happy to send you a diagram by fax or mail.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION X  
SERVICE/PARTS INFORMATION  
A. SERVICE  
1. Service must be performed by a qualified trained technician, service agency, or gas supplier. If service is  
required, contact the distributor from whom the ADC equipment was purchased. If the distributor cannot be  
contacted or is unknown, contact the ADC Service Department for a distributor in your area.  
NOTE: When contacting the ADC Service Department, be sure to give them the correct model  
number and serial number so that your inquiry is handled in an expeditious manner.  
B. PARTS  
1. Replacement parts should be purchased from the distributor from whom the ADC equipment was pur-  
chased. If the distributor cannot be contacted or is unknown, contact the ADC Parts Department for a  
distributor in your area. Parts may also be purchased directly from the factory by calling the ADC Parts  
Department at (508) 678-9000 or you may FAX in your order at (508) 678-9447.  
NOTE: When ordering replacement parts from the ADC dealer or the ADC factory be sure to give  
them the correct model number and serial number so that your parts order can be  
processed in an expeditious manner.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION XI  
WARRANTY INFORMATION  
A. RETURNING WARRANTY CARD(S)  
1. Before any dryer leaves the ADC factory test area, a warranty card is placed on the back side of the main  
door glass. These warranty cards are intended to serve the customer where we record the individual  
installation date and warranty information to better serve you should you file a warranty claim.  
a. If a warranty card did not come with your dryer, contact the ADC Warranty Department or ADC Service  
Department at (508) 678-9000.  
B. PARTS  
For a copy of the ADC commercial warranty covering your particular dryers, contact the ADC distributor from  
whom you purchased the equipment and request an ADC warranty form. If the distributor cannot be contacted  
or is unknown, warranty information can be obtained from the factory by contacting the ADC Warranty Department  
at (508) 678-9000.  
NOTE: Whenever contacting the ADC factory for warranty information, be sure to have the dryer’s  
model number and serial number available so that your inquiry can be handled in an  
expeditious manner.  
C. RETURNING WARRANTY PARTS  
ALL dryer or parts warranty clams or inquiries should be addressed to the ADC Warranty Parts Department.  
To expedite processing, the following procedures must be followed:  
1. No parts are to be returned to ADC without prior written authorization (“Return Material Authorization”)  
from the factory.  
NOTE: An R.M.A. (“Return MaterialAuthorization”) is valid for only sixty (60) days from date of  
issue.  
a. The R.M.A. issued by the factory, as well as any other correspondence pertaining to the returned parts,  
must be included inside the package with the failed merchandise.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Each part must be tagged with the following information:  
a. Model number and serial number of the dryer from which part was removed.  
b. Nature of failure (be specific).  
c. Date of dryer installation.  
d. Date of part failure.  
e. Specify whether the part(s) being returned is for a replacement, a credit, or a refund.  
NOTE: If a part is marked for a credit or a refund, the invoice number covering the purchase of the  
replacement part must be provided.  
NOTE: Warranty tags (ADC Part No. 450064) are available at “no charge” from ADC upon request.  
3. The company returning the part(s) must clearly note the complete company name and address on the outside  
of the package.  
4. ALL returns must be properly packaged to insure that they are not damaged in transit. Damage claims are  
the responsibility of the shipper.  
IMPORTANT: No replacements, credits or refunds will be issued for merchandise damaged in  
transit.  
5. ALL returns should be shipped to the ADC factory in such a manner that they are insured and a proof of  
delivery can be obtained by the sender.  
6. Shipping charges are not the responsibility of ADC. ALL returns should be “prepaid” to the  
factory. Any “C.O.D. or “COLLECT” returns will not be accepted.  
IMPORTANT: No replacements, credits, or refunds will be issued if the claim cannot be processed  
due to insufficient information. The party filing the claim will be notified in writing,  
either by “FAX” or “CERTIFIED MAIL- Return Receipt Requested,” as to the  
information necessary to process claim. If reply is not received by the ADC  
Warranty Department within thirty (30) days from the FAX/letter date, then no  
replacement, credit, or refund will be issued, and the merchandise will be discarded.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. ML-82 TOOL LIST  
Straight Head Screwdriver  
Phillips Head Screwdriver  
Sensor Pin and Socket Tool (P/N 122801)  
Pliers  
1/4” Nut Driver  
3/8” Open End Wrench  
5/8” Open End Wrench  
3/8” Socket Wrench  
1/2” Socket or Open End Wrench  
1/4” Open End Wrench  
5/16” Socket or Open Wrench  
1/2” Socket Wrench  
7/16” Socket or Open End Wrench  
5/16” Nut Driver  
12” Pipe Wrench (2)  
1/8” “T” Shaped or “L” Shaped Allen Wrench  
3/16” “T” Shaped or “L” Shaped Allen Wrench  
Wire Cutters  
1/2” Allen Wrench  
3/8” Allen Wrench  
Channel Locks  
Manometer (ADC P/N 122804)  
MP Pin Extraction Tool (ADC P/N 122800)  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADC 450404 1- 12/21/99-50  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acnodes Computer Hardware MPC 6171A User Manual
Aiphone Intercom System DA 1MD User Manual
Alcatel Carrier Internetworking Solutions Telephone 4008 User Manual
Allied Telesis Network Card AT 2916T User Manual
Alpine GPS Receiver NVE N852ADVD User Manual
American Audio MP3 Player Portable Audio Recorder User Manual
Ask Proxima Projector IN35W User Manual
Atmel Projection Television STK594 User Manual
Axor Paint Sprayer 284466XX1 User Manual
Bakers Pride Oven Fryer LGF User Manual