Gossen MetraWatt U1601 U1602 U1603 Operating Instructions User Manual |
Operating Instructions
U1601, U1602, U1603
3-348-869-03
15/1.21
Summators – Energy Control System ECS
Operation (menu displays) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Menu 2: Display Interval Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
In-Service Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Menu: Display Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Setup Parameters Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Setup Selection Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
RS232 Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
LON Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
ECS LAN Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.10 Master Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.11 Basic Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Characteristic Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
LON Bus System Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
11.1 Maximum Cable Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
11.2 Cable Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
11.3 Bus Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
12.1 Network Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
12.2 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
12.3 Device Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
12.4 Reinstalling a LON Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
12.6 Replacing a LON Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
12.7 Additional LON Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
12.8 Channel Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Functions Overviews . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Gossen Metrawatt GmbH
3
1
Applications
The Energy Control System (ECS) allows for unambiguous cost center accounting.
Electrical as well as non-electrical energy and its consumption can be recorded,
optimized and billed to individual cost centers.
The U1601, U1602 and U1603 summators are at the heart of the Energy Control
System (ECS) and enable the recording and billing of both analog and digital quantities.
ECS operating software revision level: V2.57
The current operating instructions covering the latest firmware update are available for download
LON is a registered trade mark of the Echelon Corporation.
2
System Description
• Analog signals from orifice plates, measuring transducers or other measuring
instruments are acquired, analyzed and stored together with meter pulses from energy
meters, flow meters and heat meters at the intelligent U1601 summator.
• Each summator can be connected to up to 12 energy meters with pulse output. Data
collected at the meter inputs are integrated and stored according to various criteria to
a semiconductor memory with battery back-up.
• 64 channels are available for the generation of sums and/or differences based upon
meter values. Values from other summators which are connected to the ECS LAN can
be used to generate virtual channels as well. All of the stored measurement values
can be displayed at the summator.
• Stored values can be read out from the U1601 summator with a PC, or can be remote
queried with the help of a modem. A radio-controlled clock for correct time
synchronization or a printer for the generation of reports can be connected to the
second RS232 interface.
• Several summators can be linked to one another via the ECS LAN, a multi-master
compatible RS485 field bus, for applications which required the use of more than 12
inputs (analog/binary). The linking of up to 255 summators from 16xx series
instruments via the ECS LAN allows for the establishment of a powerful energy control
system, which is controlled and monitored with a PC.
• All of the instruments connected to the bus can be queried and programmed from any
desired summator thanks to the multi-master system structure. A limit value violation at
summator M can thus trigger a signal at summator N. Each bus user has access to all
data and functions throughout the entire system.
• LON is a new type of intelligent bus concept with allows controllers, sensors and
actuators to communicate with one another. In addition, up to 63 nodes can be
connected to a U1601 summator via the integrated LON network.
• Two freely programmable relays allow for the generation of messages or the triggering
of specific actions if certain criteria have been fulfilled.
• User generated programs can be installed to the summators through the use of the
system-specific programming language, Energy Control Language (ECL). The
summators can thus be adapted to customer-specific calculations, analyses,
monitoring and optimization independent of the energy control system.
• ECSwin PC software for configuring parameters at the summators, and for reading in
energy consumption data and displaying them in tabular and graphic form.
4
Gossen Metrawatt GmbH
3
Instrument Description
3.1
Instrument Overview
LAN L LAN R
to Summator Port
LON Meter
Input
2
Relay Outputs
Relay 1, Relay 2
LEDs
LCD
2
Analog Outputs
A1, A2 (= K13,14)
Display
PC/Modem
Printer/Clock
Com-Server
Status Relay
Aux. Power, U
for external meter
v
12
Inputs
E1 ... E12
4
Binary Outputs
S1 ... S4
64 Channels
analog / S0 S0 Standard
3.2
Channels / Calculations
64 software channels are available. The input type for each channel can be selected for
the basic configuration with the CMODE channel parameter (0 ... 4).
OFF
0
OFF
3
S0
1
E
n
Channel K
n
Analog Value
Desired
Channel
2
Calculation
Calculation
Power
Energy
Energy
4
LON
Meter
LON
Channels
Cyclical Generation of Channel Registers
Due to the fact that many various energy data registers are made available to each
channel (33 registers without maximum values: Etot, EtotT1, EtotT2, Pmom, 10+1 times
Eday, 12+1 times Emon, 4+1 times Eyear), only the most important summations are
performed continuously, and less important summations are performed in accordance
with a rotating schedule. For example, Etot is calculated continuously, whereby Emon-
12 is determined less frequently (approximately every 30 to 90 seconds). Power values,
except for Pmom, are continuously calculated based upon energy values, and thus
need not be summated.
Gossen Metrawatt GmbH
5
Channel Names
A name can be assigned to each channel with a length of up to 8 characters. These
names allow for improved channel identification during data processing, as well as for
graphic representations. System-wide access to a given channel is also enabled through
the use of such names.
<A> Etot Motor5
A system-wide search for a channel with the name “Motor5” is performed from
summator A, and total energy from this channel is graphically displayed (see also ECL
command: FINDER).
Channel Numbers
If inputs (E1 ... E12) are to be assigned to the channels, each input can only be assigned
to the channel which bears the same number, i.e.:
Inputs E / Outputs A
Channels
E1
...
1
...
E12
A1
A2
12
13
14
...
64
Virtual Channels
• Any unused channel can be utilized as a virtual channel for the generation of any
desired sums or differences which result from physical inputs or other virtual
channels. It makes no difference which summators within the ECS LAN the channels
have been assigned to!
• Unused physical channels can also be utilized as virtual channels, in which case even
the maximum value registers for the corresponding physical channel are made
available.
• The synchronizing-interval data logger can record data from virtual channels.
Differential Linking (ECL commands dVSUM and dVIRT)
As soon as they have been defined, incoming energy quantities (~ meter pulses) from
the source channels are continuously summed and the summed energy quantities are
fed to the virtual channel, “as if they had actually just been measured”. The virtual
channel is decoupled from the source channels and data can be manipulated as
desired.
Areas of application: logical coupling of input signals (as if the corresponding input
signals had been switched together to a single channel).
Example 1:
Channel 26 at summator D generates a cost center based upon channels 1 ... 5+8 from
summator B weighted with a factor of 0.7, and channel 4 from summator C weighted
with a factor of 0.3
H1=’B:dVSUM 1..5+8 0.7, C:dVSUM 4 0.3, D:dVIRT 26=’
Example 2:
Channel 10 is the difference between 1 ... 8 and total-sum channel 9
(sum of 1 ... 8 minus channel 9):
6
Gossen Metrawatt GmbH
H2=’dVSUM 1..8, dVSUM 9 -1, dVIRT 10=’
Channel Parameters (chapter 6.4, page 33)
Numbers Range
In order to ensure greatest possible accuracy, all internal calculation operations are
performed with 64 bit floating decimal point numbers. This means that 15 (!) significant
decimal places are possible.
Switching the Channel Display On and Off
The On/Off function only determines whether or not a channel is visible while browsing
through channel data at the display, or during read-out with '*' (ECL command:
ONOFF). The function of the channel remains otherwise entirely unaffected.
Channel Start/Stop
The Start/Stop function is used to determine whether or not meter pulses are to be
accepted at a given input (ECL command: STARTSTOP).
• A virtual channel which has been generated by means of “differential linking” can be
influenced with the Start/Stop function in an analog fashion.
• Since the binary input status of a channel is not influenced, this function can be used,
for example, to avoid taking undesired binary data into consideration.
Energy Metering
Meter pulses filtered out in this fashion are integrated, per channel, into a temporary
meter. The meter values are converted into their corresponding energy values every 1 to
2 seconds, and are added to total energy registers. Pulses are converted to energy
values by means of the following formula:
Energy Calculation
PulsesImp
Imp
MeterConstant --------
kWh
EnergykWh = -------------------------------------------------- U
I
KFactor
ratio ratio
where:
I
U
primary
primary
I
= ----------------------
U
= ------------------------
ratio
ratio
I
U
secondary
secondary
Power Calculation
Instantaneous power, PMOM, is determined based upon the interval between the
incoming pulses. All other power values are calculated from the corresponding energy
value, taking the corresponding time interval into consideration.
The calculation of power assumes the assignment of an energy unit of measure per hour
(kWh). The power factor must be adapted accordingly for other units of measure (e.g.
liters per minute) (ECL command: PFACTOR). The default value is 3600, and it would be
60 for the “liters per minute” example.
Formula for the calculation of power based upon energy E and duration dt:
P = E * Pfactor / dt
Only sensors which have been connected via the LON network are capable of
transmitting already calculated power and energy values to the summators.
Gossen Metrawatt GmbH
7
3.3
Inputs E1 ... E12 and E1 ... E6 respectively (analog / binary)
Analog Inputs
For summator U1601 12 optically isolated analog inputs are available, E1 ... E12, for
summator U1603 6 optically isolated analog inputs are available, E1 ... E6. These can
switch settings and appropriate software settings.
One metering channel, 1 ... 12, can be assigned to each of the inputs, E1 ... E12,
one metering channel, 1 ... 6, can be assigned to each of the inputs, E1 ... E6.
The applied analog input value may correspond to a measured power quantity.
The input ranges (20 mA, 5 mA, 10 V, S0) must be pre-selected with the DIP switches,
as well as the I/O RANGE parameter. Energy is matched to the various ranges, and
calculated and recorded as a channel quantity with the configurable ANAFAKTOR and
ANAOFFSET parameters.
Binary Meter Inputs
The 12 analog inputs, E1 ... E12, of
A
D
summator U1601, and the 6 analog inputs,
E1 ... E6, of summator U1603 respectively,
can also be used as binary inputs (in
accordance with the S0 standard).
E
N
Configuration is accomplished by means of
A binary input recognizes two different levels, high level “1” and low level “0” (max. low
level adjustable with ECL command: LEVEL). Thus switching back and forth between
tariffs T1 and T2 can be performed with input 12. The synchronization pulse from the
electric utility can also be connected, for example, to input 11. Status can be queried via
software with the ECL command INPUT.
Debouncing Time and Trigger Edge
Debouncing time and the trigger edge can be configured individually for each of the
maximal 12 channels. Sampling time for all maximal 12 channels amounts to 5 ms.
• Debouncing time is adjustable from 10 ms to 2.55 s in 10 ms steps, ECL command:
PULSE
• High level trigger flank (1): Triggering occurs for change from low level to high level,
ECL command: EDGE
• Low level trigger edge (0): Triggering occurs for change from high level to low level.
If an input is used as a binary input, the selected debouncing time applies to this
operating mode as well. For example, if debouncing time has been set to 1 s, only those
signals are processed which remain stable at either high or low level for at least 1
second. Only debounced signals appear at the input status display at the control panel
as well.
3.4
Analog Outputs A1 and A2
Two configurable analog outputs can be driven with the ECL command ANA. The
output quantity (20 mA or 10 V range) must be selected with the DIP switches and the I/
Input channels can be recorded, scaled and read out continuously as transduced
quantities with the help of a background program (see also ECL command: ANA 13,
ANA14).
8
Gossen Metrawatt GmbH
3.5
S0 Outputs S1 through S4
Just like the relay outputs, four freely programmable S0 outputs allow for the forwarding
of messages when certain conditions have been fulfilled. Selectable voltage is limited to
50 V. Additionally, these outputs can be used as floating pulse outputs for the
transmission of meter readings to remote locations with the help of ECL background
programs (see ECL command: S0REL 1 ... 4).
3.6
Relay Outputs
Two freely programmable relays (changeover contacts) allow for the generation of a
message or the triggering of an action, if certain criteria have been fulfilled. For example,
a relay output can be activated if the mean power value within the synchronization
interval exceeds a certain value. The current relay status is displayed at the LCD under
summator status. A ?indicates that the contact is closed and active. Please observe the
characteristic values in the appendix.
Relay Names
A channel name can be assigned to each of the relays and may have a length of up to 8
characters. This name allows for improved relay identification during data processing, as
well as for graphic representations. System-wide access to a given relay is also enabled
through the use of such names:
<A> REL Horn=1
A system wide search for a relay with the name “Horn” is performed from summator A,
and this relay is activated (see also ECL command: FINDER).
3.7
Self Test
As long as the electronics are functional and no system error has been detected, the
status LED and the status relay are on. If the instrument electronics malfunction, the
relay is released and the LED goes out. A horn which can be driven with the status
relay’s break contact can be used to indicate a malfunction.
The current relay status is displayed in the status window (see chapter 5.8, page 26).
Functional testing can be expanded by means of appropriate programming (ECL
command: STATCHECK, see detailed information in online help: ? STATCHECK). For
example, the output can be deactivated (error condition) as soon as the 24 V power
supply drops to below 16 V, or if the condition of the lithium battery no longer allows for
reliable data storage.
3.8
RS232 Interface
Communications with a host computer (PC), a terminal, a modem or a printer is made
possible via the RS232 serial interface.
Access to All Measurement Data
A PC which has been connected to the RS232 interface has full access to all stored
system measurement values. ECSwin parameters configuring software, which runs on
the PC, manages all ECS data and allows for tabular data analysis.
Port Configuration
The RS232 port is configured in the DTE format (data terminal equipment), and signals
are conducted by a 9-pin D-SUB plug. The DTE configuration is compatible with
standard PC and terminal configurations. Wiring of the connector cable is described in
Gossen Metrawatt GmbH
9
3.9
ECS LAN
Several summators can be linked to one another via a multi-master compatible RS485
field bus (ECS LAN) for applications which require the use of more than 64 channels.
The connection can be established by means of a 2-wire cable using either bus or a line
topology. The maximum length per segment is1200 meters. Distances of several
kilometers between 2 summators can be accommodated with fiber optic transmission
and
4-wire technology.
A maximum of 255 summators can be connected to the ECS LAN. This means that a
maximum distance of approximately 300 km can be covered without additional
boosters.
Multi-Master System Architecture
The most significant advantage of the multi-master system architecture is the fact that
each of the bus users has full access to all of the data and functions encompassed by
the overall system. It is thus unnecessary to assign the designation of bus master a
single summator.
General Notes Concerning the ECS LAN
• The connector technology for the individual LAN segments can be freely selected and
combined.
• The longest cable length is determined by the transmission speed in accordance with
RS485. The ECS LAN normally runs at 62.5 KBaud, which corresponds to a
maximum cable length of 1.2 km, (see also chapter 6.7, page 39).
• The transmission cable must be terminated at both ends (and only at the ends) with
matching resistors. The matching resistors are integrated and can be switched on or off
at the control panel. Correct functioning of the 2-wire connection can only be secured
through the use of these integrated matching resistors. No external resistors may be
used!
• The loop resistance of the transmission cable may not exceed 100 Ohms in 2-wire
operation.
• Up to 16 summators can be connected to a single bus segment. If the matching
resistors have been correctly installed (see above), if spur line lengths have been
minimized and if the overall loop resistance of the transmission cable is less than 100
Ohms, up to 32 summators can be operated within a single segment.
• User statistics can be queried via the control panel (instrument status).
10
Gossen Metrawatt GmbH
ECS LAN, Sample Network
Gossen Metrawatt GmbH
11
Bus Left, Bus Right
Each summator is equipped with 2 complete ECS LAN interfaces. They are designated
as LAN L and LAN R. Each of these interfaces can be operated with
either 2-wire or 4-wire transmission technology (RS485).
2-Wire
A bus system, by means of which several summators are connected to the same bus
cable, must be laid out with 2-wire technology.
4-Wire
4-wire technology is used where unusually long transmission paths are involved, or
when boosters need to be integrated into the system. In such cases only line-to-line
connection is possible.
Cable Lengths (LAN Bus)
If several summators (up to 16) are to be installed in close proximity to one another
(overall maximum bus cable length of 100 m), a bus connection making use of a
twisted, two conductor cable is recommended. A line-to-line connection with a twisted
four conductor cable is not necessary until the distance between 2 summators is
greater than 400 m (max. 1200 m).
2-Wire Bus
ECS LAN, Sample Network
U1601
U1601
LAN
LAN
R
L
+ EA + E + EA + E
45 46 47 48 49 50 51 52
U1601
U1601
LAN
LAN
R
LAN
LAN
R
L
L
+ EA + E + EA + E
45 46 47 48 49 50 51 52
+ EA + E + EA + E
45 46 47 48 49 50 51 52
2-Wire Line-to-Line
LAN
LAN
R
L
+ EA + E + EA + E
45 46 47 48 49 50 51 52
2-Wire Line-to-Line
U1601
U1601
LAN
LAN
LAN
LAN
R
L
R
L
+ EA + E + EA + E
45 46 47 48 49 50 51 52
+ EA + E + EA + E
45 46 47 48 49 50 51 52
4-Wire Line-to-Line
Suitable for fiber optic cable transmission
and RS485 boosters
ECS-LAN Terminal Assignments
User Directory
Directory of ECS LAN Users
Each summator automatically generates an internal directory (ECL command: DIR) of all
users connected to the ECS LAN (assuming that unique identification has been
assigned throughout the entire system). Each summator acknowledges its presence to
12
Gossen Metrawatt GmbH
the entire system every 3 seconds with a so-called broadcast message, and all
receiving summators update their internal directories accordingly. If no message is
broadcast for a period of greater than 20 seconds, the summator in question is deleted
from the internal directories of the other summators.
Unique Identification
Each summator within the ECS LAN must be assigned its own unique summator
identification. Up to 255 different, freely selectable identifications can be created.
The following format is used: A, A1 .. A9, B, B1 .. B9, .. , Z, Z1 .. Z4
System-Wide Access to Measurement Data
Example: Total energy from channel 1 at summator D1 is to be queried from
summator A:
<A> D1:Etot 1
3.10 LAN LED (LANL/LANR)
One LED each for bus left and bus right indicates correct operation of the ECS LAN:
• If no ECS LAN users have been connected, the LED does not light up.
• If one or more users are connected to the corresponding bus segment, the LED lights
up.
• If two or more users have the same identification, the LAN LEDs which represent the
users with identical identification blink. Exception: If the summators with identical
identification are connected to the same LAN segment, no decisive error message
occurs. For this reason, the number of summators should always be compared with
the total number indicated in the user statistics (control panel, instrument status)
during instrument installation.
• If the internal matching resistor has not been switched on during bus operation, the
corresponding LAN LED blinks.
3.11 LON Connection
LON is a relatively new type of intelligent bus concept which allows control units,
sensors and actuators to communicate with one another. Rapid, cost-effective wiring is
achieved by means of intelligent decentralization. Each node (user) is equipped with a
neuron chip, and can communicate with all of the other nodes via the LON-Talk
protocol. Data transmission is accomplished with a standardized, twisted, potential-free
two conductor cable, which can be wired either in bus, ring or star configuration (freely
selectable topology!). The electrically isolating FTT10 transceiver used to this end is
protected against polarity reversal and transmits data at a speed of 78 kb per second.
Thus up to 63 additional nodes can be connected to a U1601 summator via the
integrated LON network. During the first phase of completion, bus users include LON
compatible bus meters, as well as input/output modules, gas or water meters etc. at
later stages.
Energy values from the LON meters can be freely assigned to channels K1 ... K64 by
means of differential linking.
3.12 LON LED
LON LED off
Blinking LON LED
LON LED on
All LON channels deactivated (page 33)
Error in communication with LON users
LON bus OK
Gossen Metrawatt GmbH
13
4
Measurement Data
4.1
Overview of Available Measurement Data
The following measurement data are available for each meter input and virtual channel:
Energy Values (cumulative as of a defined starting point)
Etot
Total energy, independent of tariff
EtotT1
Total energy for tariff T1
EtotT2
Total energy for tariff T2
EtotT1+T2
Total energy for tariffs T1 plus T2
Energy Values (cumulative for defined time periods)
EInt
EInt-1
... EInt-xx
Cumulative energy for the current,
and the last xx* intervals (data logger)
Eday
Emon
Eyear
Eday-1
EMon-1
Eyear-1
... Eday-10
... EMon-12
... Eyear-4
Cumulative energy
for the current, and the last 10 days
Cumulative energy
for the current, and the last 12 months
Cumulative energy
for the current, and the last 4 years
*
Interval value depending upon memory depth
Maximum Values from Synchronization-Interval Measurement Data (with date and time)
EMax
EMax-1
... EMax-xx
The xx* highest values
EMaxDay
EMaxDay-1
... EMaxDay-10
Maximum energy value
for the current, and the last 10 days
EMaxMon
EMaxYear
EMaxMon-1
EMaxYear-1
... EMaxMon-12
... EMaxYear-4
Maximum energy value
for the current, and the last 12 months
Maximum energy value
for the current, and the last 4 years
Costs (cumulative as of a defined starting point)
CostT1
Costs for tariff T1
CostT2
Costs for tariff T2
CostT1+T2
Costs for tariffs T1 plus T2
Power Values (mean values for defined time periods)
Pmom
Instantaneous power
between the last 2 meter pulses
PInt
PInt-1
... PInt-xx
Power for the current,
and the last xx* intervals (data logger)
PDay
PDay-1
... PDay-10
Mean power value
for the current, and the last 10 days
14
Gossen Metrawatt GmbH
PMon
Pyear
PMon-1
Pyear-1
... PMon-12
... Pyear-4
Mean power value
for the current, and the last 12 months
Mean power value
for the current, and the last 4 years
Maximum Values from Synchronization-Interval Measurement Data (with date and time)
PMax
PMax-1
... PMax-10
PMaxDay-10
10 highest values from all meas. intervals
PMaxDay
PMaxDay-1
Maximum power value
for the current, and the last 10 days
PMaxMon
PMaxYear
PMaxMon-1
PMaxYear-1
... PMaxMon-12
... PMaxYear-4
Maximum power value
for the current, and the last 12 months
Maximum power value
for the current, and the last 4 years
Summary of Available Measurement Data per Channel
Energy
Values
Max. Energy Max. Power
Power Values
Costs
Values
Values
Etot
Pmom
EtotT1
EtotT2
EtotT1T2
Eint
CostT1
CostT2
CostT1T2
Pint
Emax
Pmax
Eday
EMon
Eyear
PDay
PMon
Pyear
EmaxDay
EmaxMon
EmaxYear
PMaxDay
PmaxMon
PmaxYear
Relationship between Memory Duration and Number of Channels
for Synchronization-Interval Measurement Data (measurement data list, format: 0 3):
800
682
700
600
500
400
300
200
10 0
0
273
151
16
10 5
24
80
32
65
40
54
47
56
41
64
2
8
48
Number of Channels
Gossen Metrawatt GmbH
15
Memory Duration as a Function of Number of Channels I
Number of Channels
Number of Records
Memory Duration in Days
with a 15 minute interval
2
65535
26214
14563
10082
7710
682
273
151
105
80
8
16
24
32
40
48
56
64
6241
65
5242
54
4519
3971
47
41
4.2
Synchronizing-Interval Data Logger
The energy values which have been measured during a given interval can be stored to a
data logger. This interval (duration: 10 s .. 999 hr., default: 15 minutes) is either derived
from system time, or the interval limit is determined with a trigger pulse slope (default:
channel 11). Energy measured during this interval (EINT) is entered into a list along with
the time and the date. The mean power value occurring within the interval (PINT) is
calculated based upon EINT and the duration of the corresponding interval.
Formatting the Data Logger
!
Attention!
The contents of the data logger are deleted during formatting.
The number of records in the data logger depends upon the number of channels. Thus
the data logger can be formatted in accordance with the desired number of channels.
Formatting can only be performed with an interpreter. Data area resolution is also
defined simultaneously (ECL command: FORMAT).
Defining the Number of Records
The format command reserves adequate space for the selected number of channels in
system memory. The greatest possible number of records is thus determined, but not
memory duration which is solely dependent upon the duration of the interval.
Example: Only channels 1 ... 4, channel 17 and channels 21 .. 23 are to be recorded to
the data logger.
<A> FORMAT=1..4+17+21..23
If the format command is called up without parameters, status information is read out to
the data logger. Most importantly, the number of records which can be entered to the
data logger is shown here.
<A> FORMAT = 1...4 + 17 + 21 ... 23
<A> format
Format(0): 8 channels, 26214 records (= 273 days, with a 15 min. interval)
Channels: 1;2;3;4;17;21;22;23
16
Gossen Metrawatt GmbH
Reading Out the Data Logger
Data stored to the data logger can be read out together with time and date either
directly at the instrument’s control panel or via the serial interface with the ECL
command EINT. The following example shows a read-out of all measurement data for
channels 1 through 5 in ASCII format:
<A> Eint/## 1..5 * **
16.04.93;17:45:00;1;0.5;0.75;0.99;1.36
16.04.93;18:00:00;1.01;0.1;0.76;0.80;0.83
16.04.93;18:15:00;0.99;0.48;0.75;1.02;1.28
Querying a Specific Record
Data for a specific date can be read out with the ECL command INDEX. The example
below shows the value from the data logger for channel 1 on 16 April 1993 at 6:15 p.m.
(in clear text):
<A> Index 16.04.93 18h15, Eint/ 1 .
16.04.93 18:15:00 : Eint-863 (01:Motor7) = 0.99 kWh
Data Logger Memory Structure
The data logger is a ring buffer of fixed size which is formatted accordingly. Access is
made with an index number. Index 0 always refers to the current interval, index 1 to the
last interval and index 2 to the interval before the last etc. The ECL command INDEX
transforms a time entry into the corresponding index number.
Ring Buffer
When memory capacity has been used up, the oldest record (the record with the
highest index number) is deleted to make room for the newest record. The interval which
has just been completed is thus assigned index number 1, and the index numbers for all
previous records is increased by 1.
Range of Values for the Data Logger
Limitation of Resolution to Reduce Data Volume
All data registers at the summator are internally 8 bytes wide (64 bit floating point).
However, where the data list is concerned (as of Eint-1), for which overall memory
duration is directly dependent upon available memory capacity, a format with a width of
2 bytes must be used (which results in a loss of accuracy). Since only energy values are
stored to memory (and no power values since these are calculated), standard “0”
formatting results in the following limitation of the range for values:
Range of Values
–0.8191 ... 0 ... +0.8191
–81.91 ... -0.82, +0.82 ... +81.91
–8191 ... -82, +82 ... +8191
Resolution
Resolution: 0.0001
Resolution: 0.01
Resolution: 1.0
Resolution: 100
–819100 ... -8200, +8200 ... +819100
Gossen Metrawatt GmbH
17
5
Operation (menu displays)
The U1602 micro-summator and the U1603 mini-summator are not equipped with any
display or operating elements. Communications and parameters configuring are
accomplished with ECSwin software. The display which appears in the control panel
mode is identical to the operating menus provided with the U1601 summator.
Extreme caution must be exercised when changing the parameters for the COM1 and
COM2 serial ports.
If the settings are changed, no communication takes place between the PC and the
summator. Only one port should be changed at any given time, so that the summator
can still be controlled with the other. COM2 must be set to ECL or ECL+HP.
5.1
Menu: Overview (main menu display)
Menu Displays 1 ... 5
Main Menu Display
ESC
Displays total
energy, power,
costs (menu 1)
Displays interval
energy (menu 2)
F1
F2
F3
Menu
TOT. ENERGY
INTERVAL
ENERGY
OVERVIEW
Displays interval
energy max. values
(menu 3)
ANALOG
IN/OUTPUTS
F4
F5
APPLICATIONS
SETUP:
press
Displays analog
inputs and outputs
(menu 4)
>1s
STATUS DISPLAYS
Select and start
programs
Status display
(menu 5)
From Channel
Display
The following applies in general to the sub-menu displays:
F1
F5
▲
▼
Use the
channels.
keys to advance 1 channel and the
keys to advance 10
18
Gossen Metrawatt GmbH
5.2
Menu 1: Display Total Energy, Power and Costs
Multi-Channel Display
To Main Menu
Single Channel Display
K64:
ESC
K01: Etot
F3
Etot
K02:
K01: Pmom
Etot
Menu 1
K02:
...
F1
F2
F3
K01:
Etot
P-Momentary
Pmom
TOTAL
ENERGY
K64:
Pmom
ZW
E (Tariff1)
EtotT1
K01: Cost T1
02:
K01: EtotT1
K02:
E (Tariff2)
EtotT2
F4
F5
...
E (Tariff T1+T2)
EtotT1T2
K64:
K64:
K02:
K01:
F4
K01: Cost T2
K02: Cost T2
K01: EtotT2
K02:
EtotT1,Cost(T1)
EtotT2,Cost(T2)
EtotT1T2,
...
Cost(T1+T2)
K64:
F1
K01: Cost T1+T2
▲
K01: Etot T1+T2
▼
F1
F5
F5
K02:
▲
▼
...
K64:
EInt, PInt, E /Day/Mon/Year
Emax, Pmax /Day/Mon/Year
Menu Advance
Channel Selection
• Multi-Channel Display (all channels with only 1 measurement value)
F4
F2
K#
Name
Pmom
Etot
K# Name
Pmom
K# Name
Pmom
K# Name
K# Etot
K# Etot
Time from
Motor-01
80.7321
23.12.08 10:27:00
01
02
01
01
80.7
kWh
22.2
Area-16
02
22.2475
02
23.12.08 10:28:10
kVarh
Wh
03
3456788.2
3456788.2458
23.12.08 10:16:33
Cooler1
03
03
Z1422152
Sun 9-20
Room 25
Wh
04
05
06
07
3422654.1
3422654.1698
23.12.08 11:45:00
04
04
MWh
24.6
24.6587
23.12.08 10:27:00
05
05
180.3
MWh
180.3470
23.12.08 10:27:00
06
06
21365.9
kWh
Room 27
Hall 33
07
21365.9487
07
23.12.08 10:27:00
08
kWh
234546.3
21.7
2356.4
234546.3414
23.12.08 10:27:00
08
08
kWh
F5:
F4: P
09
21.7774
23.12.08 10:27:00
House 31
Hall 22
09
09
2356.4444
kWh
10
23.12.08 10:27:00
10
F1:
10
F1:
Channel selection same as above
F1:
F5:
F2:
F5:
F3:
F4: P
F2:
F2:
F3:
F4: P
F3:
• Single Channel Display (1 channel with all measurement values)
Channel Mode
01 Motor01
Etot
LON
kWh
Channel 01
Etot
80.7321
Pmom
ZW
Pmom
ZW
10.7221 kW
Additional Meas. Values
102376.84 kWh
EtotT1, CostT1
EtotT2, CostT2
EtotT1T2, CostT1+T2
EInt, PInt, E /Day/Mon/Year
Emax, Pmax /Day/Mon/Year
AsynchronMotorNo.1
Channel 01 Long Name
Gossen Metrawatt GmbH
F1:
F3:
F5:
19
5.3
Menu 2: Display Interval Energy
Single Channel Display
K64:
Multi-Channel Display
To Main Menu
K01: PInt
ESC
F3
K02:
K01:
K01: EInt- ...
K02:
EInt-....
...
K64:
K64:
K02:
K01:
K01: Pday
EINT
Menu 2
F1
F2
F3
: st T
K01: Eday- ...
E (Day)
Eday
INTERVAL
ENERGY
K02:
...
Eday-....
E (Month)
EMon
K64:
E (Year)
Eyear
F4
F4
F5
K64:
K02:
K01:
K01: PMon
K01: EMon- ...
K02:
MAXIMA ...
...
K64:
EMon-...
Jump to
Menu 3
K01: Pyear
K64:
K02:
K01:
K01: Eyear- ...
F1
F5
K02:
...
K64:
▲
▼
Eyear-...
Menu Advance
Channel Selection
Emax, Pmax /Day/Mon/Year
Etot /T1/T2/T1T2
Channel Selection
• Multi-Channel Display
K#
Name
PInt-xxxx
EInt-xxxx
K# PInt-xxxx
Advance
Page
K#
EInt-xxxx
K# Name
F2
01
01
02
03
Motor-01
kWh
80.7321
80.7
22.2
3456788.2
3422654.1
24.6
180.3
21365.9
02
22.2475
Area-16
kVarh
Cooler
Wh
03
3456788.2458
Wh
04
F1
F5
3422654.1698
04
05
06
07
Z1422152
05
MWh
24.6587
Sun 9-20
Room 25
Area 27
▲
▼
06
MWh
180.3470
07
kWh
21365.9487
Channel Selection
➟
F1:
23.10.08
13.02.15
23.10.08
13.02.15
12.57.10
03.11.08
➟
12.57.10
03.11.08
F2:
xxxx:
Interval Selection
F4
F1:
F5:
F5:
F2:
F3:
F4: P
F3:
F4: P
• Single Channel Display
Channel Mode
01 Motor01
EInt-xxxx
LON
Channel 01
EInt
80.7321 kWh
10.7221 kW
PInt-xxxx
PInt
Additional Meas. Values
xxxx:
23.10.08
03.11.08
13.02.15
12.57.10
E, P /Day/Mon/Year
Selectable Interval
➟
Emax, Pmax /Day/Mon/Year
Etot, Pmom, ZW /T1/T2/T1T2
Eint, Pint
Set index to 0.
ESC
Channel 01 Long Name
AsynchronMotorNo.1
F1:
F3:
F5:
20
Gossen Metrawatt GmbH
5.4
Menu 3: Display Maximum Values for Interval Energy
To Main Menu
Multi-Channel Display
Single Channel Display
K64:
K02:
K01: Pmax-xx
ESC
F3
K01: Emax-xx
K02:
K01:
...
K64:
Emax-xx
K01: PmaxDay-xx
K64:
K02:
EmaxInt
Menu 3
F1
F2
K01: EmDay-xx
K02:
...
Emax (Day)
EmaxDay
INTERVAL
ENERGY
K01:
K64:
EmDay-xx
Emax (Month)
EmaxMon
MAXIMA
F3
F4
F5
F4
Emax (Year)
EmaxYear
K01: PmaxMon-xx
K64:
K02:
K02: Cost T2
K01: EmaxMon-xx
K02:
...
K64:
K01:
EmMon-xx
K01: PMaxYear-xx
K64:
K02:
K01: EmaxYear-xx
F1
F5
K02:
...
▲
▼
K01:
K64:
Menu Advance
Channel Selection
Etot, Pmom /T1/T2/T1T2
EmYear-...
Eint, Pint, E, P /Day/Mon/Year
• Multi-Channel Display
F4
F2
K#
Name
Pmax-xx
Emax-xx
K# Name
Pmax-xx
K# Name
Pmax-xx
K# Name
K# Emax-xx
K# Emax-xx
Time From
Motor-01
23.12.08 10:27:00
01
02
01
01
80.7
kWh
80.7321
22.2
Area-16
02
22.2475
02
23.12.08 10:28:10
kVarh
3456788.2
Wh
03
3456788.2458
23.12.08 10:16:33
Cooler1
03
03
Z1422152
Sun 9-20
Room 25
Wh
F5:
F4: P
04
05
06
07
3422654.1
3422654.1698
23.12.08 11:45:00
04
04
MWh
24.6
24.6587
23.12.08 10:27:00
05
05
MWh
180.3470
180.3
23.12.08 10:27:00
06
06
21365.9
kWh
Room 27
Hall 33
07
21365.9487
07
23.12.08 10:27:00
08
kWh
234546.3
21.7
2356.4
234546.3414
23.12.08 10:27:00
08
08
kWh
09
21.7774
23.12.08 10:27:00
House 31
Hall 22
09
09
2356.4444
kWh
10
23.12.08 10:27:00
10
10
F1:
F1:
F5:
F2:
F5:
F3:
F4: P
F1:
F2:
F2:
F3:
F4: P
F3:
Channel selection same as above
• Single Channel Display
Channel Mode
01 Motor01
Emax-xx
LON
Channel 01
Emax
21.32 kWh
Additional Meas. Values
Pmax-xx
Pmax
1279.260
kW
Emax, Pmax /Day/Mon/Year
Etot, Pmom, ZW /T1/T2/T1T2
Cost /T1/T2/T1T2
Eint, Pint
E, P /Day/Mon/Year
23.10.08
03.11.08
13.02.15
12.57.10
Set index to 0.
ESC
➟
xx:
AsynchronMotorNo.1
for Selection of
Maximum 0 ... 10
F1:
F3:
F5:
Gossen Metrawatt GmbH
21
5.5
Menu 4: Display Analog Inputs and Outputs
Multi-Channel Display
E01: Ana
E0
Single Channel Display
To Main Menu
A14:
E02:
R
ESC
F3
1
:
A
n
aN
E01: Ana
Ana
E01:
...
AnaN
AnaR
E12:
A13:
A14:
ANA
Menu 4
F1
F2
F3
E01: AnaMaxR
E01:AnaMaxN
A14:
E02:
Maxima
AnaMAX
ANALOG
INPUTS
E01: AnaMAX
E01: AnaMax
AnaMaxN
...
Minima
AnaMIN
E12:
AnaMaxR
A13:
F4
A14:
Lon ANA
F4
F5
E01: AnaMinR
E01:AnaMinN
A14:
E02:
Output
STATUS
I
E01: AnaMin
E01: AnaMin
AnaMinN
...
F1
F5
E12:
AnaMinR
▲
▼
A13:
A14:
Channel Selection
Channel Selection (see left))
Ana: Scaled value with AnaOFFSET, AnaFAKTOR
R: Raw value in V/mA, which is applied to the input
N: Phys. meas. value scaled to 1 (10V, 20mA = 1)
Menu Advance
Display of current output value
from analog outputs A1, A2
(in station status)
A13,14 Correspond here to analog outputs A1,2
22
Gossen Metrawatt GmbH
• Multi-Channel Display
F4
K#
[
]
K#
[
]
K#
[
]
AnaMin
AnaMax
AnaMinN
AnaMaxN
AnaMinR
AnaMaxR
K#
[
]
K#
[
]
K#
[
]
K#
[
]
K#
[
]
K#
[
]
Ana
AnaN
AnaR
2356.44 kW
0.235
0.222
2.35
2.22
E01
E01
E01
V
22.24 kW
V
E02
E02
E02
3456788.24 kW
E03
3.45
0.345
V
V
V
V
V
V
V
E03
E03
E04
3422654.16
E04
0.342
E04
3.42
kW
0.024
0.24
E05
E05
E05
24.65 kW
180.34 kW
1.80
E06
E06
E06
0.180
21365.94 kW
2.13
E07
E07
E07
0.213
E08
E08
0.234
E08
2.34
234546.34
kW
F5:
E10
F5:
E10
F2:
F2:
E09
E10
21.77 kW
E09
0.217
E09
2.17
F2:
80.73 kW
0.403
8.07 mA
F5:
F1:
F1:
F1:
F3:
F4: N
F3:
F4: R
F3:
F4: S
Channel selection same as above
K#
LonANA
Name
11
12
C21
Vorlauf1
22.8
73.4
F1:
F5:
F2:
F3:
• Single Channel Display
11 C21
LonANA
01 Motor01
LonA
22.8 C
LON
2356.44 kW
Channel Mode
Channel 01
Ana
Ana
AnaN
AnaN
0.235
2.35
Additional Values
AnaR
AnaR
V
AnaMax, AnaMaxN, AnaMaxR
AnaMin, AnaMInN, AnaMinR
23.10.08
13.02.15
Asynchronous motor No. 1
F1:
F3:
F5:
Gossen Metrawatt GmbH
23
5.6
In-Service Function
An error bit is used in order to inform the analysis software that a channel is not reading
out valid data because, for example, it is currently being calibrated (ErrChan 24:
inservice). The in-service function is activated by configuring the in-service feature:
Example: INSERVICE FEATURE = 3
This function is only active per channel in mode 4=LON.
In-Service
0
1
Explanation
In-service not available (default setting)
In-service available
Same as 1, but direct jumping from the individual basic display to
SETUP CHANNEL menu 4 is also possible by pressing the F4 key
3
5
7
Same as 1, but in-service can only be activated for one channel
Same as 3, but in-service can only be activated for one channel
In-service can be configured with CHANNEL DATA under SETUP in menu 4:
InService OFF / InService ON / ALL OFF
In-service activation is indicated in
the individual basic display.
Z1: U1601Hebl
12:32:10
Z1: U1601Hebl
12:32:10
–SETUP
CHANNEL
Menu 4
MODE:LON-ANA
21¦U1661.1 ¦ ¦LonA
INSERVICE
ON
ETot
1)
15.615 kW
0.014 kW
Channel 21
Pmom
PULSE TIME
50 ms
Select
Channel
<<<<In-Service ON >>>>
Cold Water T4
TRIGGER EDGE
1:__--
The *ERIS enumeration is used specifically with the in-service function.
Example: All, Channel& *eris reads out all channels with the in-service status.
1)
is only shown when function InService is activated.
24
Gossen Metrawatt GmbH
5.7
Menu: Display Applications
To Main Menu
ESC
15 programs can be entered here which
have been created with the ECL interpreter
and have been uploaded to the summator
via the data interface.
These are15 of 32 possible P programs
which are capable of performing single
operations by pressing a key, but which
cannot execute cyclical tasks, for example:
– Perform calculations
(weighting for energy values)
– Read out specific energy channels
via the data interface
(3)
(2)
PROGRAM22
PROGRAM11
F1
F2
F3
PROGRAM01
TIME-PROG2
APPLICA-
TIONS
(1)
HELPPROG3
F4
F5
MYPROG44
PROG1of32
Gossen Metrawatt GmbH
25
5.8
Menu 5: Display Status Menu (time, relays, errors, interfaces)
To Main Menu
To Main Menu
To Last
ESC
ESC
Channel Display
Display time,
date, switching
outputs
F1
F2
F3
TIME+DATE
Menu 5
STATUS
Channel Errors
Station Errors
Stat.+Chan.
ERROR LIST
F4
F5
Display
STATUS
LAN Status
COM/LON Status
Station Status2
Stations Status1
Menu Advance
• Display Time, Date and Relays
A:
Station ID
A: U1601-2
12:32:10
U1601-2: Station Name
12:15:00 Current Time
To Main Menu
TIME: 12:32:10
DATE: 31.03.09
1, 2: Relay1/2
3 ... 6: S1 ... S4
S:
* :
Relay Status
Active
1 2 3 4 5 6 S
Relay
*
• Display Station / Channel Errors (see error table)
To Main Menu
ECS
To Last Channel Display
STATION ERRORS
CHANNEL ERRORS
CHANNEL-xx:
Communications Error
Phase Sequence Error
Overflow
xx:
STATION:
LON Error
Batt. low
Channel Selection
F1
F5
▲
▼
Channel Error exists
Channel Error exists
To Next
Error Channel
F2
F4
To Previous
Error Channel
F1:
F2:
F5:
F3: STA F4: –
F3:Chan
26
Gossen Metrawatt GmbH
• Status Displays
STATION STATUS
ECSYS V2.52 / 23.03.09
RAM : 1 MB
BATTERY : low
24V : OK
AnaR A1 : –18.45 mA
AnaR A2 12.20 mA
Operating system, version, date created
Summator memory capacity
Battery charge level
24V supply power U for external switching contacts
V
Instantaneous values for analog outputs A1, A2
:
!STAT/CHAN ERROR
(F4)!
Channel or station error has occurred (display with F4)
Relay and S0 output switching status:
Relay
1 2 3 4 5 6 S
*
1,2:
Relay 1/2
3 ... 6: S1 ... S4
S:
Relay status
(* = active
STATION STATUS
INTERVAL : 1m
I-SOURCE : Time
FORMAT : 32 Channel
Selected energy interval time: 1 minute
The internal clock is used as the interval source
Number of channels from which interval values, Eint, are to be
generated (see FORMAT commands)
Currently selected tariff
Tariff source is an H program which switches among the tariffs.
TARIFF
: T1
T-SOURCE: PROG
Max.L-LEVEL: 10% (0)
Maximum low level for inputs E1 ... E12, when they are used
as S0 inputs
Level for inputs E1 ... E12: _low, high
E1-E12
1
5
_ _9_ _
_ _
_ _
_ _ _ _
COM-STATUS
ECL operation
Selected baud rate
No parity
COM-1
: ECL
: 9600
: Off
Baud
Parity
H/S
Handshake mode
: Xon/Xoff
COM-2
Baud
Parity
H/S
: ECL+HP
: 115200
: Off
ECL operation and read-out via background programs is
possible via COM2.
: Xon/Xoff
LON: 1
Nodes
! Error !
LAN-STATUS
LAN-L
Baud
Mode
Users
Selected baud rate
: 62K5
: 2 D
: 10 (10)
2-wire connection (Bus)
Number of users: 10 total, of which (10) are direct
LAN-R
Baud
Mode
Users
Selected baud rate
4-wire connection (point-to-point)
Number of users: 5 total, of which (1) is direct
: 62K5
: 4 D
: 5 (1)
16 users are present at the LAN L/R (including this station)
Total users: 16
LON-STATUS
1 node ERROR
Termination: 50 Ohm
On meter (node) has been found at the LON bus.
Gossen Metrawatt GmbH
27
6
Basic Configuration
6.1
Setup Parameters Overview
STATION
CHANNEL DATA
. . .
RS232
ECS LAN
LON
64
1
Installation
Subnet / node
address
Timing code
Poll delay
Bus termination
CHANNEL:
Time / Date
ECS LAN, left:
Mode
Terminated (yes/no)
Baud Rate
COM1:
Mode
Baud rate
Parity
Handshake
-------------
COM2:
Mode (OFF, LON...)
Channel Name
Long Name
E-Unit
P-Unit
------------
Chan. Visible on/off
Chan. Start/Stop
Fix Point
C-Factor
------------
Meter Const.
U-Ratio
I-Ratio
P-Factor
------------
Pulse Time
Station Name
Station ID
Interval
Interval Source
---------------------
Tariff Source
Tariff Unit (EUR)
Tariff Fix Point
Cost Factor T1
Cost Factor T2
---------------------
Password
LCD Contrast
Language
Date Format
---------------------
Relay Mode
-------------------
ECS LAN, right:
Mode
Terminated (yes/no)
Baud Rate
Mode
Baud rate
Parity
Handshake
Trigger Edge
------------------------
LON CHANNEL:
LON Sub-channel
LON Activity
Neuron ID
Analog Out Test
S0 Level
Bootstrap & Tests
------------
LON Factor
LON Offset
------------------------
ANALOG CHANNEL:
Ana Faktor
Ana Offset
Ana Sign
I/O Range
------------
Unit Select
A Unit
Ana Fix Point
Resolution
Ana Interval (A1, A2);
command: ANAINT)
28
Gossen Metrawatt GmbH
6.2
Setup Selection Menu
Setup Selection Menu
ESC
Setup Sub-Menus
Station Parameters
To Main
Display Menu
From all
Displays
Menus 1 ... 4
To Last
Display Menu
ESC
>1 sec
Channel Parameters
Menus 1 ... 8
F1
STATION
- SETUP -
Select
F2
F3
CHANNEL DATA
RS 232
RS232 Parameters
F4
F5
ECS-LAN
ERASE:
press
> 3 sec
LON
ECS LAN Parameters
LON
Bus Termination, etc.
see page 40 for DELETE menu
Gossen Metrawatt GmbH
29
6.3
Station Parameters (IDs, intervals, tariffs, outputs, ... )
From
SETUP Selection
Sub-Menus / Parameters
ESC
F1
F2
F3
TIME / DATE
Set date and time
- SETUP -
STATION
Menu 1
STATION NAME
BUILDING 3
EDITING menu
STATION ID
A:
e.g. A, A1 ... A9, Z1 ... Z4
INTERVAL
15 m
F4
F5
from 10 s to 999 h, here: 15 minutes
Time, Prog, Channel 11
INTERVAL SOURCE
Prog
Prog, Channel 12
SOURCE: Prog
F1
F2
F3
- SETUP -
STATION
Menu 2
TARIFF UNIT
EUR
T Fix POINT
2: 0.00
1 to 4 characters, here: EUR
TARIFFS
T1 [x]
T2 [ ]
0, 1, 2 or 3 places after the decimal
for the display of energy costs
COSTFACT-T1
0.17
0.001 ... 99999
F4
F5
COSTFACT-T2
0.11
0.001 ... 99999
F1
F2
F3
PASSWORD
PASSWORD Menu
- SETUP -
STATION
Menu 3
LCD CONTRAST
5
–5 ... 15, default = 0
LANGUAGE
English
German, English
F4
F5
DATE FORMAT
dd.mm.yy
dd.mm.yy, mm/dd/yy, mm-dd-yy
F1
F2
F3
- SETUP -
STATION
Menu 4
RELAY/S1..S4-
MODE
ANALOG
OUTPUT TEST
OFF, ON, PROG
Output to A1, A2:
0, 4, 20 mA or 0, 2, 5, 10 V
S0/ LEVEL
0: 10%
F4
F5
10, 25, 50, 70%
BOOTSTRAP
and TESTS ...
BOOTSTRAP Menu
see page 42
_________________________
(1 Password must first be entered
30
Gossen Metrawatt GmbH
Time / Date
After the time has been entered to the first line, the cursor jumps to the date line. Entries
have an immediate effect on the integrated real-time clock, and for this reason entry
cannot be interrupted. ECL command: TIME/DATE
Station Name
The station name must have a length of between 1 and 8 characters. If no name is
entered, the name “-” is automatically assigned to the station. The following characters
can be used: _ + – 0 ... 9 A ... Z a ... z. ECL command: STATION
Station ID
Each station within the ECS LAN must have its own unique ID. The same ID may not be
used more than once. Up to 255 IDs can be assigned. The ID has a maximum length of
2 characters. If a blank is entered into the character string, the string is truncated as of
the blank when the entry is acknowledged with F4. IDs have the following format: A, A1
... A9, B, B1 .. B9 ... Z, Z1 .. Z4.
Interval
Range of possible entries for the synchronization interval: 10 seconds ... 999 hours
(entry in seconds). ECL command: INTERVAL (ITV)
Interval Source
The synchronization interval can be generated in three different ways:
Time: Intervals are generated based upon the selected interval duration.
Program: An interval is only generated by the ECL command: SYNC=.
Channel 11: A meter input serves as a binary input for the synchronization signal. The
selected pulse duration and pulse edge are taken into consideration.
ECL command: INTERVAL SOURCE (IQ)
Source (tariff source)
Selection of the appropriate tariff T1 or T2 can be made in two ways:
Channel 12: A meter input serves as a binary input for determining the valid tariff. The
selected pulse duration is taken into consideration. The pulse edge parameter is used to
determine which level is assigned to tariffs T1 and T2. If the “+” edge (1) is selected: low
level (0 V at input) corresponds to tariff T1, and high level (24 V) to tariff T2. If the “-”
edge is selected, these relationships are reversed.
Program: The appropriate tariff is selected with the ECL command TARIFF=1 or
TARIFF=2. These commands are only enabled if “Program” has been selected as the
source. ECL command: TARIFFSOURCE (TQ)
Tariff Unit
The maximum length for the tariff unit of measure is 4 characters. The tariff unit of
measure must be at least one character long. ECL command: TUNIT
T Fix Point
Determines the number of places after the decimal point which are used for the display
of incurred energy costs. ECL command: TFIX
Cost Factors T1 and T2
Cost factors are entered in the same way for tariffs T1 and T2.
The cost factor is used to convert energy values into costs. This conversion can be
applied to the total energy registers for tariffs EtotT1 and EtotT2, as well as EtotT1T2.
Cost factors can be entered within a range of 0.000 to 99.999
ECL command: COSTFAC1, COSTFAC2.
Gossen Metrawatt GmbH
31
Password
This function provides a sub-menu for the entry of passwords for 5 users (see page 41).
LCD Contrast
This menu allows for an adjustment of the contrast at the LCD. 20 different contrast
levels are available (–5 to +15). The default setting is 0 and provides for good results in
most cases.
Language
All menus, ECL messages and online help are displayed in the selected language. ECL
command: LANGUAGE
Date Format
3 different formats are available: dd.mm.yy, mm/dd/yy, mm-dd-yy.
Relay / S0 Mode
Determines the operating mode for relays 1 and 2, as well as S0 outputs S1 ... S4. If
PROG is selected, a user program (H/P program) determines the status of the outputs.
ECL command: RELM.
Analog Output Test
Voltage or current values can be read out from analog outputs A1 and A2 for test
purposes with this function. Selection of either voltage or current output can be made in
the menu: SETUP CHANNELS (I/O RANGE) (see page 36).
S0 / Level
The sensitivity of the S0 input channels (S1 ... S4) can be selected as a percentage
(10, 25, 50 or 70%). ECL command: LEVEL
Bootstrap and Tests
Open the bootstrap loader in the bootstrap menu (see page 42).
LON Test Display: Display of several important LON parameters.
LCD Test: Tests for correct functioning of the 4 LEDs and the LCD. All four LEDs light up
and a checkerboard pattern appears at the LCD during this test.
Keyboard Test: All of the instrument’s keys are displayed at the LCD and activation of
each key is acknowledged at the LCD.
32
Gossen Metrawatt GmbH
6.4
(Channel) Parameters (mode, name, units, displays, ... )
From
SETUP Selection
Sub-Menus / Parameters
ESC
- SETUP -
CHANNEL
Menu 1
F1
F2
F3
OFF, ANA, COUNT, LON, LON-ANA, LON-PE, LON-INP,
LON-REL
1 to 8 characters, here: MOTOR-01
MODE:
LON
CHANNEL NAME
MOTOR-01
CHAN: 1
LONG NAME
ASYNC.MOTOR1
1 to 20 characters, here: ASYNC.MOTOR1
1 to 4 characters, freely definable energy unit of measure
E-UNIT
kWh
F4
F5
Select
Channel:
P-UNIT
kW
1 to 4 characters, freely definable power unit of measure
- SETUP -
CHAN.
Menu 2
Same mode as above
ON/OFF
MODE:
LON
F1
F2
F3
Visible
ON
StartStop
START
CHAN. 1
START/STOP
FIX POINT
2: 0.00
0 to 3 places after the decimal point
for the display of energy and power values
F4
F5
Select
Channel:
C-FACTOR
1.00
0.001 ... 99999.999
- SETUP -
CHAN.
Menu 3
Same mode as above
F1
F2
F3
MODE:
LON
METER CONST.
100.00
0.001 ... 99999.999 pulses per kWh
0.001 ... 99999.999
CHAN. 1
U-RATIO
1.00
I-RATIO
1.00
0.001 ... 99999.999
0.001 ... 99999.999
F4
F5
Select
Channel:
P-FACTOR
3600.00
- SETUP -
CHAN.
Menu 4
MODE:
LON
F1
F2
F3
Same mode as above
CHAN. 1
PULSE TIME
50 ms
F4
F5
1 ... 9999 ms time required for valid S0 signal
1 / 0, i.e. trigger for S0 signal at pos. / neg. edge
Select
Channel:
TRIGGER EDGE
1:__--
Gossen Metrawatt GmbH
33
(Channel) Mode
The following selections can be made with the following sub-menus, depending on the
summator type:
U1601/3:
U1602:
Channel mode 0 ... 8
Channel mode 0, 4 ... 8
0: OFF:
1: ANA:
The channel is switched off entirely and all functions are deactivated.
The applied analog quantity is displayed for this channel with the
corresponding “A UNIT” (see A-UNIT parameter on page 37).
2: P E:
3: Count:
A binary input quantity is used for energy measurement in accordance
with the S0 standard (COUN) (see chapter 5.2).
4: LON
Measured energy data are made available to the system via linking
amongst various LON users.
5: LON-ANA Analog values via LON for A2000, A210/A230, DME400, U1661,
U128X W1, U138X W1, U228x W1 and U238x W1 (see chapter 5.5)
6: LON-PE
Same as LON-ANA, plus energy is calculated based on LON analog
values (see chapter 5.5)
7: LON-INP Binary inputs via LON for U1660
8: LON-REL Relay outputs via LON for OCL210.
Channel Name
Each physical channel can be assigned a name for the purpose of improved
identification. The name need not be unique, unless it is also used as a field name for a
database. The length of the name may not exceed 8 characters, and it must be at least
one character long. ECL command: CHANNEL
Long Name
An expanded channel name including up to 20 characters. ECL command: LNAME
E-Unit, P-Unit
A freely definable energy unit of measure (e.g. kWh) and power unit of measure (e.g. kW)
can be assigned to each physical channel. The units of measure may not exceed a
length of 4 characters, and must be at least one character long.
ECL command: EUNIT, PUNIT
(Channel) Visible
Each physical channel can be made visible or invisible for queries from the control panel
or for “*” - lists during interpreter operation. The function of the channel remains
otherwise unchanged! If, for example, only channels 1 through 3 are visible, values can
only be queried for these channels in the normal display mode, and the instrument
appears to be a 3 channel device. If “Etot*”, is queried during interpreter operation, total
energy is only displayed for these three channels.
If all channels have been deactivated, time and date are displayed in the normal display
mode. These entries are immediately effective and need not be acknowledged.
ECL command: ONOFF
Channel Start/Stop
The acceptance of meter pulses at a given input is controlled with the Start/Stop
function. A channel which has been created by means of t “differential linking” can be
influenced with the Start/Stop function in an analog fashion. Since the binary input
status of the channel is not influenced, undesired counting of binary data can, for
example, be avoided with this function. These entries are immediately effective and
need not be acknowledged. ECL command: STARTSTOP (STSP)
34
Gossen Metrawatt GmbH
Fix Point
A determination can be made as to how many places after the decimal point will be
used for the display (not the calculation) of energy or power values for each physical
channel.
(0) No places
(1) One place
0
0.0
(2) Two places
(3) Three places
0.00
0.000
These entries are immediately effective and need not be acknowledged.
ECL command: CFIX
C-Factor
The following can, for example, be accomplished with this function: The measured
quantity is consumption in cubic meters. This quantity needs to be displayed in the unit
3
of measure standard cubic meters [Nm ], so that a correction factor is required. This (C-
Factor) is thus the desired multiplication factor used for the calculation of the energy
value for a given channel.
Meter Constant
The meter constant can be defined individually for each physical channel. It indicates
how many meter pulses are generated by a connected meter per kWh, and is used in
U-Ratio, I-Ratio
The Uratio and Iratio factor can be defined individually for each physical channel (see
page 7 for calculation formula).
Sign Changes (+, -): Press “<<” (F2) when the cursor is all the way to the left.
Range of possible entries for Uratio and Iratio: 0.000 ... 99999.999
If the Uratio or Iratio factor is set to zero for a given channel, meter pulses can be
disabled for the channel in question. However, it is better to use the Start/Stop function
for this purpose. ECL command: URAT, IRAT
Note
A detailed description on URAT and IRAT is given in the ECL Interpreter and
Command List (3-348-870-03).
P-Factor
The P-Factor can be defined individually for each physical channel (see page 7 for
calculation formula).
Sign Changes (+, -): Press “<<” (F2) when the cursor is all the way to the left.
Range of possible entries for Uratio and Iratio: 0.000 ... 99999.999
ECL command: P-FACTOR
Pulse Time
The duration for which a pulse must be applied to the S0 input of a channel in order to
be recognized as an S0 pulse (debouncing time). ECL command: PULSE
Trigger Edge
Determines whether the meter pulse is triggered at its positive (1) or negative (0) edge.
ECL command: EDGE
Gossen Metrawatt GmbH
35
Setup Channel Parameters (menus 5 ... 8)
Sub-Menus / Parameters
▲
▼
- SETUP -
CHAN.
Menu 5
F1
F2
F3
MODE:
LON
OFF, ANA, COUNT, LON, LON-ANA, LON-PE, LON-INP,
LON-REL
CHAN. 1
LON
SUB-CHANNEL
5
LON user has 8 channels, channel 5 is displayed
RUN, STOPPED
U1660.8
LON ACTIVITY
(run)
F4
F5
Select
Channel:
NEURON-ID
0100221DFC00
12 place address for the selected LON user
▲
▼
- SETUP -
CHAN.
Menu 6
F1
F2
F3
MODE:
LON
Same mode as above
0.001 ... 99999.999
0.001 ... 99999.999
LON FACTOR
0.00
LON OFFSET
0.00
CHAN. 1
LON
U1660.8
F4
F5
Select
Channel:
▲
▼
- SETUP -
CHAN.
Menu 7
F1
F2
F3
MODE:
LON
Same mode as above
0,001 ... 99999,999
0,001 ... 99999,999
ANA FAKTOR
1.00
CHAN. 1
ANA OFFSET
0.00
ANALOG
E-01
ANA SIGN
Range: +/–
F4
F5
+/–, +, –
Select
Channel:
I/O Range
20 mA
5mA, 4-20mA, 20mA, 10V, S0
▲
▼
- SETUP -
CHAN.
Menu 8
F1
F2
F3
MODE:
LON
Same mode as above
UNIT SELECT
P-Unit
None, E-Unit (energy), P-Unit (power),
A-Unit (analog value)
CHAN. 1
A-Unit
kW
Freely definable dimension, if an analog input
quantity (A-Unit) is to be displayed
ANALOG
E-01
ANA FIX POINT
9: 0.0...
0, 1, 2, 3 or 9 determines number of places after
the decimal point for the display
F4
F5
Select
Channel:
RESOLUTION
2000
100 ... 10000
36
Gossen Metrawatt GmbH
Mode
LON Channel
The LON user which has been selected with its neuron ID has 8 channels. Channel 5 is
displayed at local channel 1, if channel 1 has been set to the LON mode.
LON Activity
If a LON user malfunctions, all local channels which are used to display LON channels
indicate errors. In this way, the LON channel can be displayed (run) or suppressed
(stopped) without switching off individual channels.
Neuron ID
This is the internationally unique address for a LON user and consists of a 12 place
hexadecimal value. The summator automatically establishes contact with the LON user
which has been assigned to this address. If the local channel has been set to the LON
mode, the suppressed “LON channel” is displayed (channel 5 from the previous
example).
LON Factor, LON Offset
LON user values are scaled to a value of -1 ... 0 ... +1.
The range characteristics can be freely adapted to the measuring task with the
LON Factor and LON Offset parameters. ECL commands: LONFACTOR, LONOFFSET
ANA Faktor, ANA Offset
Analog output values are scaled to a value of -1 ... 0 ... +1.
The range characteristics can be freely adapted to the measuring task with the Ana-
Factor and Ana-Offset parameters. ECL commands: ANAFAKTOR, ANAOFFSET.
Sign (+, -)
Indicates the polarity of the input and output signals. + and - correspond to positive and
negative signals from the appropriate input or output. ECL command: ANASSEL
I/O Range
Indicates the range of the respective analog input or output. Possible ranges include:
5 mA, 4 - 20 mA, 20 mA, 10 V, S0. For the analog outputs, only the 10 V and/or 20 mA
ranges are possible. The hardware must also be set to the same value. The required DIP
switches are located under the cover plate at the top of the instrument (see page 50).
Unit Select
Determines which unit of measure (none, energy, power, analog value) is used for the
display of the channel’s input quantity. ECL command: ANAUSEL
A-Unit
Freely definable magnitude for the display of measured quantities, if these are measured
3
as analog values, e.g. kW, °C, m , mA. The display can include up to 5 places.
ECL command: AUNIT
ANA Fix Point
Determines the number of decimal places used after the comma for the display (not the
calculation) of the measured analog quantity for each physical channel.
(0) No places
0
0.0
(2) Two places
(3) Three places
0.00
0.000
(1) One place
(9) Floating decimal point
Gossen Metrawatt GmbH
37
These entries are immediately effective and need not be acknowledged.
ECL command: ANAFIX
Resolution
For the 12 analog input channels E1 ... E12. ECL command: ANARESO
6.5
RS232 Menu
From
SETUP Selection
ESC
Sub-Menus / Parameters
- COM-2 -
COM-1/2
COM-1/2
- SETUP -
F1
F2
F3
Switches between COM1 and COM2
MODE
ECL
COM-1: ECL, LAN-L, LAN-R, DCF77
COM-2: OFF, ECL, ECL+HP, LAN-L, LAN-R, DCF77
RS232
COM-1
BAUD RATE
9600
1200, 2400,4800, 9600, 19200,
38400, 57600, 115200
PARITY
––
F4
F5
–– (= off), EVEN
HANDSHAKE
RTS/CTS
RTS/CTS, XON/XOFF
ECS LAN via COM
If a 4-wire ECS-LAN connection is to be provided via an asynchronous V24 interface, a
new mode is available for the serial interfaces as from V2.48:
LAN-R or LAN-L.
Example: Two devices shall be interconnected in a TCP/IP network at ECS-LAN level.
Two COM servers are used for this purpose which are linked to one device each per RS
232 interface and are interconnected per Ethernet. COM servers transmit signals in a
transparent manner from the RS 232 interface to the allocated COM server.
As soon as LAN-R or LAN-L has been selected by COM-1 or COM-2 in the setup
menu, the ECS LAN data stream is diverted to this COM interface. The interface
parameters baudrate, parity and handshake are now applicable, instead of the ECS LAN
settings which were previously in use.
Recommendation: maximum baud rate (115200 Bd), parity OFF, handshake RTS/CTS.
The selected parameters must correspond to the settings of the connected COM
server, however, they may deviate from those of the opposite terminal, if necessary.
Please note that the now redundant ECS LAN connection should no longer be used.
Please also make sure that the matching resistor for 2-wire parameters configuration is
activated in order to prevent any ECS LAN errors.
Special case: Use of COM and ECS LAN Connection
The ECS LAN connection is not deactivated in the ECS LAN-via-COM operating mode.
Any telegrams to be sent are transmitted both via the associated COM interface and the
ECS LAN interface. Incoming telegrams are processed by both interfaces. Nevertheless,
it is not a star hub configuration as the two interfaces (COM and ECS LAN) cannot “see”
one another.
38
Gossen Metrawatt GmbH
6.6
LON Menu
From
SETUP Selection
Sub-Menus / Parameters
ESC
F1
F2
F3
INSTALLATION
- SETUP -
LON
SUBNET/NODE
S001N003
Subnet 1 ... 255
Node 1 ... 127
TIMING-CODE
9
0 ... 15
POLL DELAY
300 ms
0 ... 32000 ms
F4
F5
TERMINATION
open
Open bus termination, 50 Ohm, 100 Ohm
INSTALLATion
SUBNET/NODE
TIMING CODE
POLL DELAY
All LON users are sought out and reinstalled.
LON address of the summator
Waiting time is set for a response with TIMING CODE.
POLL DELAY is waiting time between queries from 2 channels in
milliseconds.
TERMINATION
LON network termination is set via TERMINATION.
6.7
ECS LAN Menu
From
SETUP Selection
Sub-Menus / Parameters
ESC
Sub-menu: 15K6 / 31K2 / 62K5 /125K / 375K;
separate settings for LAN-L; LAN-R
F1
F2
F3
BAUD RATE
- SETUP -
ECS LAN
L
MODE
2-Wire
LAN-L: 2 or 4-wire connection
LEFT
[ ]
TERMINATED
Yes
LAN-L: open or terminated (always with 4-wire connection)
R
MODE
2-Wire
LAN-R. 2 or 4-wire connection
F4
F5
RIGHT
[ ]
TERMINATED
Yes
LAN-R: open or terminated (always with 4-wire connection)
LAN-L: Settings for LAN left (terminals 49 through 52)
LAN-R: Settings for LAN right (terminals 53 through 56)
2-wire connection is normally used (terminals 45 + 46 or 49 + 50), and this is the only
possibility which allows for bus configuration with multiple users at the same bus cable.
In this configuration the first and the last instruments on the bus cable must be
terminated with the internal matching resistors. Proper functioning of the bus is not
possible if the terminating resistors are not activated (Bus LED LAN/L or LAN/R blinks).
For long transmission distances, or if boosters are required, 4-wire connection can be
used (only line-to-line connection is possible). The required terminating resistors are
automatically activated. The default baud rate is 62.5 kBaud.
Note
Additional information on adjusting the interface (parameter type SET... ) is also
provided in the ECL Interpreter and Command List (3-348-870-03).
Gossen Metrawatt GmbH
39
6.8
SETUP Sub-Menus (edit, erase, outputs, bootstrap loader, password)
EDIT Menu (example)
From
Setup Menu
abc
A/a
F1 Characters list
(requires password
entry, valid until the
setup menu is exited.)
Edit:
Switch between upper and
F2
Station Name
lower case letters
B u i l d i n g
3
=
– – – – – – – –
INS
: OK
F4
Adds a blank
ESC
Escape
ESC: Escape
: Char. List
Save
Value
DEL F5
Deletes active character
F3 : Clipboard
Character Selection
F1 Additional characters window
Switch between upper and
0
A
K
U
1
B
L
V
.
2
3
D
N
X
–
4
E
O
Y
/
5
F
P
Z
*
6
7
H
R
Ö
-
8
I
9
J
F2
lower case letters
C
G
Q
Ä
=
Select
character
M
W
+
S
Ü
°
T
▲
▼
ß
Save character
@
F1:abc F2:A/a
: ok
ERASE Menu
Requires password entry.
From all
Displays
ESC
Abort
>2sec
Deletes measurement data (in this case Etot)
for the displayed function of the selected channel
F1
F2
F3
Ana
ERASE
Chan. 1
Deletes all measurement data for the selected channel
CHANNEL DATA
DATA OF ALL
CHANNELS
Deletes all measurement data for all channels,
except for data logger entries
F4
F5
Channel
Change:
DATA LOGGER
Deletes all entries from the data logger
F1 ... F4
here, e.g., F4
Select Channel
Abort
▲
▼
ESC
ERASE
all channel data
YES
ESC NO
: YES
ESC : ESCAPE
40
Gossen Metrawatt GmbH
Password Menu
Passwords consist of a combination of the F1
through F5 keys and always have 6 places.
User 1
User 2
User 3
User 4
F1
F2
F3
NEW
PASSWORD
Entry
1.
Select
the User
F4
F5
User 5
When the summator is shipped, all of the passwords have been deleted: any user is
able to configure parameters. If this needs to be avoided, passwords can be entered for
5 users:
Enter a password for user 1 first (master). Passwords for other users (2 through 5)
cannot be entered until the password for user 1 has been entered. After the password
for user 1 has been entered, parameters can be changed for a period of 5 minutes if
none of the keys are activated. After this time period, or after an instrument self-test,
password entry is once again required.
Each user can change his password at will.
After the user has logged on with his password, he has only 5 minutes to change his
own password, even if none of the keys have been activated during this time.
If password protection is to be cancelled for all users, user 1 (master) must enter special
password “111111”. The system deletes all passwords and parameters can be
configured by any user.
Note
For details on the parameter Password please refer to the ECL Interpreter and
Command List (3-348-870-03).
Analog Output Test
ANALOG
OUTPUT
TEST
From
Station Menu
TEST:
ON
F1
F2
0 mA
A-01:
–20mA
–4 mA F3
ESC
Abort
Selection:
F
..Select. F
5
2
Save
Value
F4
F5
–10 mA
–20 mA
more:
Channel:
Gossen Metrawatt GmbH
41
S0/Relay Output Menu
RELAY
MODE
From
Setup Menu
RELAY 1:
F2
F3
OFF, ON, PROG
[ 1 ]
1: ON
RELAY 2:
[ 1 ]
2: PROG
ESC
Abort
Control of the Relay / S0 output (here with program)
2 corresponds to the PROG selection
Status of the respective output
Store
Value
more:
RELAY
MODE
RELAY 3/S1
F2
F3
F4
F5
[ 0 ]
RELAY 4/S2
[ 1 ]
0: OFF
1: ON
RELAY 5/S3
[ 0 ]
2: PROG
RELAY 6/S4
[ 1 ]
more:
2: PROG
BOOTSTRAP Menu
From
Setup Menu
LOADER 1.15
12:15:00
>
Data window
displays transmitted
>
data.
COM1:
8/1/P-
H/S: RTS/CTS
Baudrate:
115200
ESC
Abort
Save
Value
Change baud rate from 9600 to 115200
After software has been uploaded
F3
F4
F5
RESET
BREAK
Also possible during transmission,
in which case old version remains.
42
Gossen Metrawatt GmbH
6.9
Firmware Update
The operating system is stored to flash memory. Summator updating is performed on
site via the serial interface.
Required Tools
• PC with serial interface. Notebooks are best suited because they can be operated
without mains power.
• Null modem cable, e.g. GTZ5232000R0001 (RTS/CTS conductors must be used due
Preparation
• Download the new firmware version from our website:
Save it to an empty directory and decompress the files.
• Connect the summator (COM 1) and the PC with the null modem cable.
• Disconnect the LON bus plug from the summator.
The following work steps are required to this end:
1. Abbreviated Instructions
➭ PC: Start the download with the “Update32.exe” program.
➭ Select the desired language.
➭ Select the COM port to which the summator is connected.
➭ Update the bootstrap loader first.
Update > new bootstrap loader
Set the U1601 ... 3 summator to the download mode to this end, and start the
update.
The summator is automatically reset after updating has been completed.
➭ Then update the firmware and the help texts:
Update > update all
Set the U1601 ... 3 summator to the download mode to this end, and start the
update procedure.
Two files are transferred to the summator.
The summator is automatically reset after updating has been completed.
Done!
The summator is once again ready for use.
Note
If you have connected LON users to your summator, the LON LED on the
summator may blink in exceptional cases. If this is the case, the LON nodes
must be reinstalled (see chapter 12.4).
Gossen Metrawatt GmbH
43
2. Complete Instructions
➭ Connect the U1601 ... 3 summator directly to the PC with the GTZ5232000R0001
null modem cable. A hardware handshake is necessary due to the high baud rate, for
which reason the RTS/CTS leads have to be crossed over (see wiring diagram
below).
➭ PC: Start the download with the “Update32.exe” program.
➭ Select the desired language.
➭ Select the COM port to which the summator is connected.
➭ Update the bootstrap loader first.
Update > new bootstrap loader
– U1601 Summator:
The U1601 summator can be set to the download mode in two ways:
• Press and hold the menu key until “SETUP SELECTION” appears.
Press the menu key 4 times until “SETUP-STATION Menu4” appears.
Then press the F5 key = BOOTSTRAP LOADER AND TESTS ...
Press and hold F1 (BOOTSTRAP LOADER) until the bootstrap loader menu appears.
The default value of 115,200 baud has proven itself in actual practice, and should not
be changed.
• Alternative: Press and hold the F1 key and disconnect auxiliary power at the device
(power-up reset). The summator is now ready to receive data.
– U1602 and U1603 Summators:
These summators can be set to the download mode as follows:
• Press and hold the BOOT button with a pencil until the LEDs go out briefly. When the
button is released, the 4 LEDs start blinking. The LED which remains illuminated the
longest indicates the utilized baud rate:
STATUS : 115,200 baud
LAN/L : 38,400baud
LAN/R : 19,200 baud
LON :
9,600baud
The default value of 115,200 baud has proven itself in actual practice, and should not
be changed.
The summator is now ready to receive data.
Start the update procedure with the PC software.
The summator is automatically reset after updating has been completed.
➭ Then update the firmware and the help texts.
Select update > all.
Set the U1601 ... 3 summator to the download mode to this end, and start the
update procedure.
Two files are transferred to the summator.
The summator is automatically reset after updating has been completed.
Done!
The summator is once again ready for use.
44
Gossen Metrawatt GmbH
Note
If you have connected LON users to your summator, the LON LED on the
summator may blink in exceptional cases. If this is the case, the LON nodes
must be reinstalled (see chapter 12.4).
6.10 Master Reset
A normal reset is executed after interrupting auxiliary power and when the integrated
watchdog is triggered, i.e. neither measurement data nor parameters are deleted.
However, if you would nevertheless like to delete all measurement data and reset the
parameters to their default values, a master reset must be executed using the keypad at
the U1601 summator. This is only possible within the first seven seconds after switching
the summator on. Press and hold the following keys simultaneously for at least three
seconds to this end:
F1 + F5 + MENÜ
Master reset can also be triggered with the following ECL command: SYSRESET = 590.
The master reset is now performed, after which the instrument returns to its normal
display. The following parameters are not effected by the master reset:
ID
Linking of the status relay
Language
Password configuration
LON matching resistor
Baud rate for the RS232 interface
Parity for the RS232 interface
BUS/L and BUS/R parameters
Gossen Metrawatt GmbH
45
6.11 Basic Software Configuration
The instrument is configured as follows upon receipt from the factory, or after a MASTER RESET:
Designation
Station Name
ID
Parameter
STATION
SETID
Value
U1601
A
*
Synchronization Interval
Interval Source
Tariff Source
Tariff Unit of Measure
Tariff Fix Point
Cost Factor, Tariff 1
Cost Factor, Tariff 2
Password
INTERVAL
IQ
TQ
TUNIT
TFIX
COSTFAC1
COSTFAC2
PASSWORD
-
LANGUAGE
RELM
15 minutes
Time
Program
EUR
2
0.20
0.15
*
*
LCD Contrast
Language
Relay Mode
5
German
2 (per program)
1
Level
LEVEL
Channel Mode
KMODE
Channel 1 12: COUNT
13 14: ANA
15 64: OFF
Channel Name
Long Name
Energy Unit of Measure
Power Unit of Measure
Visible
Start/Stop Function
Channel Fix Point
C-Factor
Meter Constant
Voltage Transformation Ratio
Current Transformation Ratio
P-Factor
KNAME
LNAME
EUNIT
Channel x
Long name, channel x
kWh
kW
ON
START
2
1
1
1
1
3600
PUNIT
ONOFF
STARTSTOP
KFIX
KFACTOR
MCONST
URAT
IRAT
PFACTOR
PULSE
Pulse Time
20 ms
Pulse Edge
EDGE
1 (+)
LON Activity
Neuron ID
LONSTOP
LONID
0
000 000 000 000
LON Matching Resistor
LON-SUBNET/NODE
*
SetLON
LonSUBNODE
50
S001N126
(Subnet = 1, Node = 126)
LON-TIMING-CODE
LON-POLL-DELAY
LON-Sub-channel
LON Factor
LON Offset
C-Factor
LonSTATTIMing 9 (384 ms)
LonPOLLDELay
LONKAN
0
1
1
0
1
LONFACTOR
LONOFFSET
KFACTOR
46
Gossen Metrawatt GmbH
Designation
Ana-Factor
Ana-Offset
Ana-Sign
Selected Ana-Unit
Ana-Unit
Parameter
ANAFAKTOR
ANAOFFSET
ANASSEL
ANAUSEL
AUNIT
Value
1
0
0 ( )
2
kW
Ana-Mode
I/O Range
Ana Fix Point
ANAMODE
ANAMODSEL
ANAFIX
3 (count)
3 (S0)
2
*
Resolution
COM1 Mode
COM1 Baud Rate
COM1 Parity
COM1 Handshake
COM2 Mode
COM2 Baud Rate
COM2 Parity
COM2 Handshake
ECS LAN 2-Wire- / 4-Wire Connection
ECS LAN Matching Resistor
ECS LAN Baud Rate
ANARESO
SetCOM1
SetCOM1
SetCOM1
SetCOM1
SetCOM2
SetCOM2
SetCOM2
SetCOM2
2000
ECL
9600
Off
Xon/Xoff
ECL
9600
Off
*
*
*
*
*
*
*
*
*
*
*
Xon/Xoff
SetLanL, SetLanR BL: 2-wire, BR: 2-wire
SetLanL, SetLanR BL: ON, BR: ON
SetLanL, SetLanR BL: 62K5, BR: 62K5
Background Program: Daylight Saving /
Standard Time
H 31
'SUWI,IF,TIME–,+,TIME=.'
Format
Group Name
Status Relay Linking
FORMAT
GROUP
STATCHECK
Channels 1 ... 64 in format 0
ECS
1 (linked)
*) These parameters remain unchanged after a master reset.
Gossen Metrawatt GmbH
47
7
Connections
7.1
Terminal Assignments
U1601
Analog / SO
+ E1 + E2 + E3 + E4 + E5 + E6 + E7 + E8 + E9 + E10 + E11 + E12
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Relay 1
Relay 2
1
2
3
4
5
6
7
8
25 26 27
28 29 30
+
–
U
LAN
LAN
U
H
Analog
SO
LON
Status
v
L
R
+ A1 + A2 + S1 + S2 + S3 + S4 + 24V + EA + E + EA + E A B
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
L
N
55 56 57
58 59 60
U1602
+
–
U
LAN
LAN
U
H
LON
Status
v
L
R
+ 24V + EA + E + EA + E A B
43 44 45 46 47 48 49 50 51 52 53 54
L
N
55 56 57
58 59 60
U1603
Analog / SO
Relay 1
Relay 2
+ E1 + E2 + E3 + E4 + E5 + E6
1
2
3
4
5
6
7
8
9 10 11 12
25 26 27
28 29 30
+
~
–
U
LAN
LAN
U
H
Analog
SO
LON
Status
v
L
R
~
+ A1 + A2 + S1 + S2 + S3 + S4 + 24V + EA + E + EA + E A B
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
L
N
55 56 57
58 59 60
48
Gossen Metrawatt GmbH
Terminal
1
2
Function
Input E1
Input E1
Input E2
Input E2
Input E3
Input E3
Input E4
Input E4
Input E5
Input E5
Input E6
Input E6
Input E7
Input E7
Input E8
Input E8
Input E9
Input E9
Input E10
Input E10
Input E11
Input E11
Input E12
Input E12
Relay 1
Designation
Terminal
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Function
Output A1, analog
Output A1, analog
Output A2, analog
Output A2, analog
Output S1, binary (S0)
Output S1, binary (S0)
Output S2, binary (S0)
Output S2, binary (S0)
Output S3, binary (S0)
Output S3,, binary (S0)
Output S4, binary (S0)
Output S4, binary (S0)
Power, external contacts
Power, external contacts
LAN Left
Designation
+
–
+
–
3
+
–
+
4
–
5
6
+
–
+
–
7
+
–
+
–
+
8
9
–
+
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
–
+
–
+
–
+
–
+
–
+ 24 V
0 V
EA+
EA–
E+
E–
EA+
EA–
E+
E–
A
LAN Left
LAN Left
LAN Left
LAN Right
LAN Right
LAN Right
LAN Right
LON
+
–
+
–
+
–
+
–
LON
B
Ö
Status Relay
Ö
Relay 1
Relay 1
W
Sch
Ö
Status Relay
Status Relay
W
Sch
L / +
Relay 2
Auxiliary Power Supply
Relay 2
Relay 2
W
Sch
Auxiliary Power Supply
N / –
Note:
The meter power supply U provides max. 24 V DC at max. 0.15 A (short-circuit proof).
V
Inputs E1 ... E12 can be configured as either analog or binary inputs (S0) – see chapter
Gossen Metrawatt GmbH
49
7.2
Input and Output Configuration (DIP switches)
Remove the cover plate at the top of the instrument. The analog inputs and outputs can
be adapted to the desired measuring range, and can be configured as binary inputs (S0)
with the DIP switches. These setting must also be entered to the channel data (I/O
RANGE parameter, see page 37).
U1601
T T
T
10V
T
E1
E2
E3
E4
E5
E6
E7
E8
E9 E10 E11 E12
A1
A2
T T 10V
T T
20mA
20mA T T T 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1
T
T
5mA T T
T
T
S0
T
DIP switches for analog outputs
DIP switches for analog inputs
S0 corresponds to binary input
Set at the factory to S0
Switching between voltage and current
Set to 20 mA at the factory
U1603
T T
T
10 V
T
E1
E2
E3
E4
E5
E6
A1
A2
T T 10 V
T T
20 mA T T T 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1
6 5 4 3 2 1
T
20 mA
T
5 mA T T
T
T
S0
T
DIP switches for analog inputs
S0 corresponds to binary input
Set to S0 at the factory
DIP switches for analog outputs
Switching between voltage and current
Set to 20 mA at the factory
7.3
Interface Pin Assignments, Connector Cable
Cable type GTZ5232000R0001 is required for connecting a summator to a PC. This is a
9-pole null modem cable with two socket connectors and a length of approximately
2 meters. A faultless connection can only be guaranteed with the cable by
Gossen Metrawatt GmbH.
7.3.1 U1601
Pin Assignments for D9 Sub-Miniature Connector Plug for COM1
Pin Number
Function
DCD
1
2
3
4
5
6
7
8
9
RXD
TXD
Signal - ground
RTS
CTS
50
Gossen Metrawatt GmbH
Pin Assignments for D9 Sub-Miniature Connector Plug for COM2
Pin Number
Function
1
2
3
4
5
6
7
8
9
TXD
Signal - ground
CTS
RXD
7.3.2 U1602, U1603
Pin Assignments for D9 Sub-Miniature Connector Plug for COM1
Pin Number
Function
DCD
1
2
3
4
5
6
7
8
9
RXD
TXD
Signal - ground
RTS
CTS
Pin Assignments for D9 Sub-Miniature Connector Plug for COM2
Pin Number
Function
1
2
3
4
5
6
7
8
9
RXD
TXD
Signal - ground
RTS
CTS
Gossen Metrawatt GmbH
51
Meter Connection (example)
Meter Connection
with S0 Interface
U368x
analog / SO
+
+ E1 + E2 + E3 + E4 + E5 + E6 + E7 + E8 + E9 + E10 + E11 + E12
22 21 20
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
U
LAN LAN
LON
v
L
R
+ S1 + S2 + S3 + S4 + 24V + EA + E + EA + E A B
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
U1664
U128x W1
U138x W1
U228x W1
U238x W1
23 24
25 24
Meter connection
with LON interface
Meter connection
with S0 interface
U128x
U138x
analog / SO
+
+ E1 + E2 + E3 + E4 + E5 + E6 + E7 + E8 + E9 + E10 + E11 + E12
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
21 20
1
2
3
4
5
6
7
8
U
LAN LAN
R
LON
v
L
+ S1 + S2 + S3 + S4 + 24V + EA + E + EA + E A B
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
+E3
5 6
U228x W0
U238x W0
S02
25 24 23
S01
+
Legend
Import
Export
Gossen Metrawatt GmbH
53
9
Programming
9.1
General Information
ECL - Energy Control Language
The flexibility of the ECS is based upon programmability of the individual summators
using a programming language which was developed especially for the ECS, namely
ECL or Energy Control Language. See ECL Interpreter operating instructions and
command reference for more details concerning this high level language which is similar
to FORTH, and which is just as easy to learn as BASIC. Thanks to its programmability,
the following, additional system characteristics are made available:
Virtual Channels
Even complex formulas for the creation of virtual channels can be concisely and plainly
formulated as background programs. No predefined patterns get in the was of flexibility.
Programming the Relays
Relay switching may depend upon a multitude of conditions. Any desired conditions,
even conditions which effect more than one summator, can be formulated with ECL.
These conditions are monitored continuously by a background program. A specialized
type of relay output programming might even correspond to a simple form of
energy management ...
Simple Energy Management
Example: If mean power at a given load component exceeds a specified value, the load
component is switched off by activating one of the two relays. Whether or not this shut-
down is desired at all can be determined by the system clock (e.g. nighttime only), by
querying a binary input (e.g. only shut down if high level is applied to input 10) or by
analyzing the power values of additional load components.
Tariff Selection
Highly specialized requirements for switching between tariffs can be fulfilled by means of
time comparison functions with background programs.
Flexible Adaptation to Database-Specific Transmission Formats
Repetitive queries to the database can be set up as normal P programs. Complete
ASCII oriented database formats can also be realized with this type of program. When
the program is started, data transmission is performed in accordance with the desired
format.
Background Programs H0 through H31
32 background programs, H0 through H31, are available. Each program can record up
to 127 characters. The background programs are run continuously, one after the other.
Due to the multi-tasking structure of the operating program, normal operating
sequences are not effected at all by the background programs.
Programs P0 ... P31, Q0 ... Q31
64 programs, P0 through P31, or Q0 through Q31, respectively, record repetitive
command sequences which can then be run simply by opening the corresponding
program. Programs can be nested, and a normal P program can be run as a sub-
program from a background program.
54
Gossen Metrawatt GmbH
Program Names
Names can be assigned to P programs. P programs can be queried system-wide with
the help of such names.
9.2
Parameters Configuration and Data Visualization at a PC
The easiest way to communicate with a summator from a PC is by means of terminal
emulation, e.g. with the help of HyperTerminal. However, the user must be very familiar
with the commands.
ECSwin provides a much more convenient method.
Program features:
ECSwin is used primarily for configuring parameters at U1600, U1601, U1602, U1603
and U1615 summators in an ECS LAN. Beyond this, reading in and visualizing energy
consumption data in the form of measured value tables and graphics (online display) is
supported as well. The 32 bit program (as from version V3.4 x) runs under MS Windows
Vista, 7 (32 and 64 bit), 8 and 10. Connection to U16sxx is possible via TCP/IP or
RS232.
The following functions are provided by the software:
• A dialog box for logging on and configuring access authority
• A dialog box for setting time in the ECS LAN
• A dialog box for configuring summator parameters
• A dialog box for configuring channel parameters
• A dialog box for setting meter readings
• A dialog box for configuring relay parameters
• Transmit user created command sequences to the summator
• A dialog box for generating virtual channels
• Control panel display (including device display, keys and LEDs) for U1600 and U1601
• Ascertainment and graphic representation of the ECS LAN network topology
• Querying and display (as table or characteristic curve) of Intervalic, daily, monthly and
annual energy and power data which have been stored to memory at the summator
• Querying and graphic display of current measured values in data logger format
• Data transmission via modem (maintenance of a dial-up list)
• Terminal emulation
Gossen Metrawatt GmbH
55
10
Characteristic Values
• Inputs E1 ... E12 (U1601, U1603)
The 12 inputs can be configured individually as voltage, current or binary inputs with
DIP switches (see page 50).
Analog Input (current)
Input quantity
direct current
Allowable Range of Input Quantities
Allowable Continuous
Overload
Upper Value (configurable)
Max. Continuous Input
Input Impedance
X2:20 mA
X2:5 mA
Input Wiring
–20 mA X 20 mA
2.5 X2
1 mA X2 20 mA
1.25 X2
75
300
see figure 1 for wiring diagram
with optocoupler
Electrical Isolation
Common-Mode Rejection
( 120 Hz)
80 dB
Analog Input (voltage)
Input quantity
direct voltage
–10 V X 10 V
30 V
1 V X2 10 V
1.25 X2
118 k
Allowable Range of Input Quantities
Allowable Continuous Overload
Upper Value (configurable)
Max. Continuous Input
Input Impedance
Input Wiring
Electrical Isolation
see figure 1 for wiring diagram
with optocoupler
Common-Mode Rejection
( 120 Hz)
80 dB
Binary Input (SO)
Input quantity
direct voltage
(square-wave pulse, S0 compatible)
Allowable Range
of Input Quantities
Allowable Overload
Continuous
signal level:
H: 0.8 mA ... 4.8 mA
L: 0 mA ... 0.4 mA
48 V
60 V
Intermittent (t 1 s)
Allowable Contact Types
Series Resistor (internal)
Input Wiring
semiconductor switching device, relay
4.7 k
see figure 1 for wiring diagram
with optocoupler
10 ... 2550 ms
2 ms
250 Hz
22 places of which 15 are usable
Electrical Isolation
Pulse Duration T (adjustable)
on
Interpulse Period T
Pulse Frequency
off
Counting Range Limit
56
Gossen Metrawatt GmbH
• Outputs
Analog Outputs A1 and A2 (U1601, U1603)
Type
floating
2
Number (DIP switch coded)
Current Output:
Allowable Range
–20 mA Y 20 mA
–4 mA Y 20 mA
4 mA Y 20 mA
1 mA Y2 20 mA
Upper Value Y2 (linear
parameters configuration)
Max. Output Voltage
Max. Output Current
Load Range
Voltage Output:
Allowable Range
Upper Value Y2 (linear
parameters configuration)
Max. Output Voltage
Max. Output Current
Load Range
30 V
1.25 Y2
0 5 V/Y2 10 V/Y2
–10 V Y 10 V
1 V Y2 10 V
1.25 Y2
40 mA
Y2/2 mA Y2/1 mA
0.005 Y2
Alternating Component
Binary Outputs S1 through S4 (U1601, U1603)
Type
Number
floating
4
Contact Type (DIN 43864)
Volume Resistance (AC/DC)
Output Voltage (external, passive)
Output Current
MOS relay
5
50 V
ON
200 mA
10 A
OFF
Relay Outputs, Relay 1 and Relay 2
Switching Element
Number of Relays
relay
2
Contact Type
changeover contacts
250 V~, 30 V=
8 A ohmic, 3 A inductive
Switching Voltage
Switching Current
5
Switching Cycles
10
Power Supply for External Switching Contacts
Voltage U (electrically isolated)
24 V
V
=
Voltage Tolerance
4%
Current (short-circuit and idling proof)
Alternating Component ( 100 kHz)
Voltage Check
0.15 A
2% V
PP
=
16 V
Gossen Metrawatt GmbH
57
• RS 232 Interface (PC / printer)
Number
1 (channel A and channel B)
plug connector, 9-pin Sub-D
Connectors
Possible Connections
Channel A:
ECL, modem, terminal, radio-controlled clock
ECL, printer, radio-controlled clock, OFF
8
Channel B:
Data Bits
Transmission Speed
Channel A/B:
1,200 ... 115,000 bits per second
none
full duplex, handshake Xon/Xoff
Parity
Operating Mode
• ECS LAN Interface (RS 485, for linking summators)
Number
2
Connectors
plug connectors with screw
connection (up to 255 users)
16 (32 with loop resistance < 100 )
multi-master, half duplex
or full duplex
Users per Segment
Operating Mode
Data Protocol
HDLC/SDLC (adapted to
multi-master requirements)
1200 m open ring
100 m mixed
Topology (line and/or open ring)
Transmission
15.6 ... 375 kBit/s
(hamming distance = 4)
Status Display
2 LEDs
switchable
Matching Resistor
• LON Interface (for connecting meters)
Number
1 (FTT-10, twisted 2 conductor cable)
plug connectors with screw connection (up to
63 user per summator)
Connectors
Operating Mode
Topology
LonTalk protocol (CSMA)
freely wired
500 m
terminated bus
2700 m
(cable type: Belden 85102,
1.3 mm diameter, 28 /Km)
78 kbps
Transmission Speed
Status Display
Bus Termination
1 LED, LON active
switchable
• Display (U1601 only)
Display Type
Format
graphic LCD, 128 x 128 (illuminated)
21 characters, 16 lines
58
Gossen Metrawatt GmbH
• Measurement Value Storage
Storage Mode
continuous
Memory Capacity,
with 1 channel:
87,380 records
3,971 records
with 15 min. Interval
Memory Stability
with 64 channels:
5 years with backup battery (see also aux.
power supply – backup battery)
Resetting of Meter Values to Zero
via PC or keypad at instrument
• Clock for Date and Time
Smallest Time Unit
Allowable Deviation
1 s
10 ppm = 5.3 min. per year
• Functions Monitoring
Status Display
LED at front panel
changeover contact
250 V~, 30 V=
Status Relay
Switching Voltage
Switching Current
Switching Cycles
8 A ohmic, 3 A inductive
5
10
• Influencing Quantities and Influence Errors
Influencing Quantity
Nominal Range of Use
Allowable Influence Error
as Percentage of Accuracy Class
Temperature
10 C ... 22 - 24 ... 40 C
0 C ... 22 - 24 ... 55 C
load range
50%
100%
20%
Output Load
HF Interference
IEC 255-4 E5
500%
2.5 kV, 200 ,1 MHz, 400 Hz
IEC 8001-3
EM Fields
(severity level 3)
EMC Burst
500%
500%
200%
10%
10 V/m 27 - 1000 MHz
IEC 801-4
(severity level 3)
EMC RF cable
(severity level 3)
Auxiliary Voltage
2 kV, 5/50 ns, 5 kHz
IEC 801-6
0.15 - 80 MHz, 10 V
nominal range of use
• Electrical Safety
Protection Class
I
Overvoltage Category
III
Nominal Insulation Voltage:
Input
50 V
30 V
250 V
50 V
265 V
80 V
Output: Analog, Binary, Uv
Output Relay
Interfaces
Auxiliary Voltage, AC
Auxiliary Voltage, DC
Interference Suppression EN 55022
(VDE 878.3) device: class B
ESD Protection IEC 801-2
EMV Surge (severity level 3)
(IEC 801-5)
0.15 - 1000 MHz
4 kV
2 kV
Gossen Metrawatt GmbH
59
Test Voltages
Input - Housing
Input - Output
Aux. Voltage - Input
Input - Relay
0.5 kV
0.5 kV
3.7 kV
3.7 kV
• Resistance to Climatic Conditions
Relative Humidity
75%
Temperature Ranges
Operation / Function
–10C ... +55C
–25C ... +70C
Storage, Transport
• Auxiliary Power Supply
Extended Range Input, AC - DC
Nominal Range of Use,
AC (45 ... 420 Hz)
Nominal Range of Use, DC
Power Consumption
Fuse
85 V ... 264 V
100 V ... 280 V
15 W (25 VA)
2 A slow-blow
Direct Voltage Input (optional)
Nominal Range of Use, DC
Power Consumption
20 V ... 72 V
15 W
2 A slow-blow
Fuse
Backup Battery
Lithium Cell (can be replaced
without tools or data loss)
Service Life
without Aux. Voltage at 20C
Loss of Capacity after 5 Years
with Aux. Voltage at 20C
Supply Voltage for External Circuits
Voltage Range
CR 2450
5 years
15%
direct voltage 24 V 4%
max. 0.15 A
from all other circuits
Overload Capacity
Electrically Isolated
• Mechanical Design
Housing Material
Dimensions
Installation Position
Mounting
aluminum sheet
212 mm x 125 mm x 85 mm
any
mounting to top-hat rail per EN 50022/35 mm or
screw mounted to plate
housing: IP 40
terminals: IP 20
1.6 kg
Protection
Weight
Terminals
Protective Conductor
screw terminals, max. 2.5 square mm
6.3 mm cable lug
60
Gossen Metrawatt GmbH
11
LON Bus System Structure
The most commonly used transmission medium for industrial and building management
applications is twisted pair copper cable, which is used together with the electrically
isolated FTT-10A transceiver. Both of the conductors can be connected to either pole,
and installation is thus reverse polarity protected.
Maximum transmission distances are influenced by the electrical characteristics of the
cable, and the network topology. Utilized cables should comply with the stipulated
specifications in order to prevent interference during communication. Due to the
possibility of reflections, only one cable type may be used in any given bus segment.
Network Topologies:
Bus Topology
(bus terminator at both ends)
Free Topology
(bus terminator at one end)
If a bus structure is used, the components are connected in parallel, one after the other.
A bus terminating resistor must be used at each end. Branch lines may not exceed a
length of 3 meters. Only one bus terminator is required with free topologies, but
transmission distances are limited in this case.
If repeaters are used, the bus signal can be boosted thus increasing maximum possible
transmission distance. Due to response characteristics, only one passive repeater may
be included in any given bus segment. The transition to other physical transmission
media, and/or targeted forwarding of data packets to individual bus segments, is
accomplished by means of routers.
The following recommendation is based upon experience gained by Gossen Metrawatt
GmbH during installation and start-up of LON systems. The environment within which
the cable is laid has a decisive influence on correct cable selection, and must therefore
be taken into consideration during the planning stage. All generally applicable directives
for laying control and telecommunications cables must be adhered to during installation.
Gossen Metrawatt GmbH
61
11.1 Maximum Cable Lengths
Cable Type / Designation
Bus Topology
(bus terminator at both ends)
Free Topology
(bus terminator at one end)
JY (ST) Y 2 ea. 2 x 0.8 mm
900 m
500 m
max. 320 m from device to device
UNITRONIC bus cable
Level IV, 22AWG
Belden 8471
900 m
500 m
max. 320 m from device to device
1400 m
2700 m
2700 m
500 m
max. 400 m from device to device
500 m
max. 400 m from device to device
Belden 85102
500 m
Specified values apply to total cable length and are only valid for the FTT-10A transceiver.
11.2 Cable Type
Inexpensive wiring is possible for applications in environments with minimal interference
using the following cable type: JY (ST) Y 2 ea. 2 x 0.8 mm with twisted wire pairs. The
above specified dimension of 0.8 mm refers to the diameter of the wire, which results in
a wire cross-section of 0.5 square mm.
In most cases no shielding is required. It may be possible to eliminate communications
problems occurring in environments with excessive interference by connecting the
shield at one end. If cables are used which contain several wire pairs, it may be
advantageous if the individual pairs are shielded. Special LON bus cable can be used for
highly demanding requirements.
11.3 Bus Termination
Additional bus terminators are required for bus topologies, and where repeaters are
utilized. These can be purchased as auxiliary LON component U1664 in top-hat rail
mount housing. Each unit includes a one-ended and a two-ended bus terminator.
62
Gossen Metrawatt GmbH
12
Connecting LON Bus Compatible Devices
Up to 64 nodes can be connected to a U1601...3 summator via the LON network. The
summator is capable of interacting with the following LON compatible devices:
• Multifunctional power meter
• Programmable multi-transducer
• Electric meters
A2000, A210, A230
DME400
U1681, U1687, U1689,
U128x W1, U138x W1
U228x W1, U238x W1
• 8-channel (S0) meter polling module
• 6-channel analog input module
• 6-channel relay output module
U1660
U1661
OCL210
12.1 Network Interface
A so-called binding is generally required in order to enable communication amongst
LON devices. This means that network variable outputs are linked (bound) to network
variables inputs with the help of a tool.
Binding is not required for the U1601, which significantly simplifies installation. The
nodes are addressed via the neuron ID (LON ID). The neuron ID is a twelve digit number
which is printed on the device, and which can be queried via the display at the A2000.
The channel function is configured with the mode command (CMODE). The desired
values are selected with the sub-channel command (LonCHANNEL). Selected values
and any error messages generated by the LON devices are queried cyclically (polling).
12.2 Functions
Acquiring Energy and Power Values (mode: LON, CMODE = 4 LON)
The U1601 continuously acquires meter readings and power values from the LON
devices. A delta value is generated based upon the current meter reading and the
previous value, which is added to Etot and Eint. The current meter reading is stored to
non-volatile memory for use in generating the next delta value. Only positive delta values
are taken into consideration.
Special feature for U1660 and U1661: These devices are not equipped with a non-volatile
memory. If supply power to any given LON data logger is interrupted, it starts counting
again from zero. Meter readings acquired after this point in time are smaller than the
recorded energy value, and thus no delta value is generated. In order to assure that this
energy is not ignored, the first value after a power failure is saved as the previous value,
and is used as a basis for generating the next delta value.
Acquiring Analog Values (mode: LON-ANA, CMODE = 5 LonA)
LON device network variables can also be acquired as analog values. This operating
mode is especially useful for the innumerable values read out by the A2000 and the
DME400. Values are no integrated in this case.
Acquiring Analog Values with Integration (mode: LON-PE, CMODE = 6 L-PE)
If the analog value represents power, energy is calculated by means of integration.
Binary Inputs and Outputs
(mode: LON-INP, CMODE = 7 LonI or LON-REL, CMODE = 8 LonR)
Binary inputs can be queried with the U1660 meter polling module, and the OCL210
relay output module is capable of switching relays.
Gossen Metrawatt GmbH
63
12.3 Device Descriptions
12.3.1 A2000 Multifunctional Power Meter
Energy and Power Function
Settings:
CMODE k = 4 LON. Desired energy is selected by means of the network variable
number under LonCHANNEL. LonCHANNEL k = Nv#. The displayed unit of
measure is the power unit of measure. Only the energy network variable is entered,
and corresponding power is read out automatically.
Energy Values and Corresponding Power
Nv#
51
52
53
54
58
59
60
61
Name
Description
Nv#
27
27
27
27
35
35
35
35
Name
Description
NvoWHTotExpLT
NvoWHTotImpLT
NvoWHTotExpHT
NvoWHTotImpHT
NvoVarHTotExpLT
NvoVarHTotImpLT
NvoVarHTotExpHT
NvoVarHTotImpHT
Active energy export LT
Active energy import LT
Active energy export HT
Active energy import HT
Reactive energy export LT
Reactive energy import LT
Reactive energy export HT
Reactive energy import HT
nvoWatTot
nvoWatTot
nvoWatTot
nvoWatTot
nvoVarTot
nvoVarTot
nvoVarTot
nvoVarTot
Active power in the network
Active power in the network
Active power in the network
Active power in the network
Reactive power in the network
Reactive power in the network
Reactive power in the network
Reactive power in the network
Only the LTHT setting is supported by the A2000 (default status).
Analog Value Function
All other network variables can be read in as analog values.
Settings:
CMODE k = 5 LonA. The desired value is selected by means of the network
variable number under LonCHANNEL.
LonCHANNEL k = Nv#. The displayed unit of measure is the power unit of
measure.
12.3.2 DME400 Programmable Multi-Transducer
LON Settings:
Domain 1:
Node state:
Length 1, ID 00
Configured, online
Energy and Power Function
Settings:
CMODE k = 4 LON. Desired energy is selected by means of the network variable
number under LonCHANNEL. LonCHANNEL k = Nv#. The displayed unit of
measure is the power unit of measure. Only the energy network variable is entered,
and corresponding power is read out automatically.
Energy Values and Corresponding Power
Nv#
Name
Description
Nv#
27
Name
Description
51
Nvo_EnergyA
Nvo_EnergyB
Nvo_EnergyC
Nvo_EnergyD
Active energy export
Active energy import
Inductive reactive energy
Capacitive reactive energy
nvo_TrueSY_Power
nvo_TrueSY_Power
nvo_ReactSY_Pwr
nvo_ReactSY_Pwr
Active power in the network
Active power in the network
Reactive power in the network
Reactive power in the network
52
27
53
35
54
35
Only this setting is supported (must be configured).
64
Gossen Metrawatt GmbH
Analog Value Function
All other network variables can be read in as analog values.
Settings:
CMODE k = 5 LonA. The desired value is selected by means of the network
variable number under LonCHANNEL. LonCHANNEL k = Nv#. The displayed
unit of measure is the power unit of measure.
12.3.3 U1681, U1687 and U1689 Electric Meters
Settings:
CMODE k = 4 LON. Desired energy is selected via LonCHANNEL.
LonCHANNEL k = 1reads out active energy import, LonCHANNEL k = 2reads
out active energy export. Corresponding power is read out automatically.
Energy Values and Corresponding Power
Nv#
Name
Description
Nv#
22
Name
Description
8
Nvo01EnergyInL
Nvo01EnergyOutL
Active energy import
Active energy export
nvo02Power
nvo02Power
Active power in the network
Active power in the network
10
22
12.3.4 U1660 8-Channel (S0) Meter Polling Module
Energy Meter Function
Settings:
CMODE k = 4 LON. The desired input is selected via LonCHANNEL.
LonCHANNEL k = 1...8reads out the number of meter pulses from channels 1
through 8, from which energy is calculated by the summator. Corresponding
power is calculated by the U1660 and read out automatically. The meter constant
(Mconst) is transmitted to the device during installation to this end.
Binary Input Function
A U1660 meter polling module can be assigned to each of the channels of the U1601.
Settings:
CMODE k = 7 LonI. LonINP reads out the status of all 8 S0 inputs of the U1660.
The energy meter function of the U1660 remains unaffected. Each input
corresponds to one bit:
Input
Bit
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
Example: LonINP 3 = 3means U1660 at channel 3, inputs 1 and 2 on, all
others off.
Gossen Metrawatt GmbH
65
12.3.5 U1661 6-Channel Analog Input Module
Energy Meter / Flow Meter Function
Settings:
CMODE k = 4 LON. The desired input is selected via LonCHANNEL.
LonCHANNEL k = 1...6reads out energy from channels 1 through 6.
Corresponding power is calculated by the U1661 and read out automatically. The
Pfactor, LonFACTORand LonOFFSETparameters are transmitted to the device
during installation to this end.
Analog Value Function (instantaneous power)
Settings:
CMODE k = 5 LonA. The desired analog value is selected via LonCHANNEL.
LonCHANNEL = 1...6reads out analog values from channels 1 through 6. The
Pfactor, LonFACTORand LonOFFSETparameters are transmitted to the device
during installation.
Power Function via LON, Energy Calculation in the U1601
Settings:
CMODE k = 6 L-PE. Desired power is selected via LonCHANNEL.
LonCHANNEL = 1...6 reads out analog power from channels 1 through 6.
Corresponding power is calculated by the U1601. The Pfactor, LonFACTORand
LonOFFSETparameters are transmitted to the device during installation.
12.3.6 OCL210 6-Channel Relay Output Module
An OCL210 relay module with 6 relays can be assigned to each channel of the U1601.
Settings:
CMODE k = 8 LonR. Each relay corresponds to one bit:
Relay
Bit
6 5 4 3 2 1
8 7 6 5 4 3 2 1
Example: LonREL 2 = 5switches relays 1 and 3 on at channel 2 in the OCL210,
all other relays are off.
12.3.7 Multifunctional Energy Meters U128x W1 and U138x W1
and A210/A230 (as from Version 4.0) mit EMMOD205 (as from Version 1.1)
Energy and Power Function
Settings:
KMODE k = 4 LON. The desired energy is selected via LonCHANNEL.
LonCHANNEL
Description
1
2
3
Active Energy, Active Power and Errors
Secondary Energy, Secondary Power and Errors
Reactive Energy, Reactive Power and Errors
only U128x/U138x
66
Gossen Metrawatt GmbH
Function Analog Values
Settings:
KMODE k = 5 LonA. The desired value is selected via LonCHANNEL. The unit displayed
is the P-unit.
LonCHANNEL Description
7
Current in phase L1
9
Current in phase L2
8
Current in phase L3
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
27
26
6
Mean value of phase currents
Total active power of the three phases
Active power in phase L1
Active power in phase L2
Active power in phase L3
Total reactive power of the three phases
Total power factor
Power factor in phase L1
Power factor in phase L2
Power factor in phase L3
Voltage between phases L1 and L2
Voltage between phases L2 and L3
Voltage between phases L3 and L1
Voltage between phase L1 and N
Voltage between phase L2 and N
Voltage between phase L3 and N
Mean value of phase voltages
Basic frequency of voltage
Operating hours since last activation of operating voltage
Operating hours exceeded upon starting threshold of meter
only U128x/U138x
only U128x/U138x
33
Function Determination of Mean Value from Analog Values.
KMODE k=6 LON-PE.
In this mode the analog instantaneous value (Pmom) is indicated as under LonA.
Furthermore, a mean value is determined in the summator for the preset interval duration
(e.g. 15 minutes) which is stored in the interval memory (Pint).
The desired value is selected via LonCHANNEL.
LonTYPE
After installation, the device type and Q characteristic are indicated as LonTYPE, e. g.
U1389 Q1.
Gossen Metrawatt GmbH
67
12.3.8 Multifunctional Energy Meters U228x W1, U238x W1
The new energy meters of the EM228x and EM238x series transmit the primary values
via LON interface. This means for features Q1 and Q9 that the secondary value is
multiplied with the transformer ratio (CTxVT).
This implies for feature Q1, where CT and VT are freely configurable within specified
limits, that the energy value also changes when the product of CTxVT is changed.
Consequently, such a change should only be made in open-circuit mode without any
load applied.
Energy and Power Function
Settings:
KMODE k = 4 LON. The desired energy is selected via LonKANAL.
Lon
Network Variable
Data Type
Description
OBIS
Channel
8
nvokWhPosT1Pri
nvokWhPosT2Pri
nvokWhPosT3Pri
nvokWhPosT4Pri
nvokWhPosT5Pri
nvokWhPosT6Pri
nvokWhPosT7Pri
nvokWhPosT8Pri
nvokWhNegT1Pri
nvokWhNegT2Pri
nvokWhNegT3Pri
nvokWhNegT4Pri
nvokWhNegT5Pri
nvokWhNegT6Pri
nvokWhNegT7Pri
nvokWhNegT8Pri
nvokVArhPosT1Pri
nvokVArhPosT2Pri
nvokVArhPosT3Pri
nvokVArhPosT4Pri
nvokVArhPosT5Pri
nvokVArhPosT6Pri
nvokVArhPosT7Pri
nvokVArhPosT8Pri
nvokVArhNegT1Pri
nvokVArhNegT2Pri
nvokVArhNegT3Pri
nvokVArhNegT4Pri
nvokVArhNegT5Pri
nvokVArhNegT6Pri
nvokVArhNegT7Pri
nvokVArhNegT8Pri
nvokWhPosPri
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
UNVT_energy_U160x
Primary active energy import, all phases, tariff no. 1
Primary active energy import, all phases, tariff no. 2
Primary active energy import, all phases, tariff no. 3
Primary active energy import, all phases, tariff no. 4
Primary active energy import, all phases, tariff no. 5
Primary active energy import, all phases, tariff no. 6
Primary active energy import, all phases, tariff no. 7
Primary active energy import, all phases, tariff no. 8
Primary active energy supply, all phases, tariff no. 1
Primary active energy supply, all phases, tariff no. 2
Primary active energy supply, all phases, tariff no. 3
Primary active energy supply, all phases, tariff no. 4
Primary active energy supply, all phases, tariff no. 5
Primary active energy supply, all phases, tariff no. 6
Primary active energy supply, all phases, tariff no. 7
Primary active energy supply, all phases, tariff no. 8
1.8.1
1.8.2
1.8.3
1.8.4
1.8.5
1.8.6
1.8.7
1.8.8
2.8.1
2.8.2
2.8.3
2.8.4
2.8.5
2.8.6
2.8.7
2.8.8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Primary reactive energy import, all phases, tariff no. 1 3.8.1
Primary reactive energy import, all phases, tariff no. 2 3.8.2
Primary reactive energy import, all phases, tariff no. 3 3.8.3
Primary reactive energy import, all phases, tariff no. 4 3.8.4
Primary reactive energy import, all phases, tariff no. 5 3.8.5
Primary reactive energy import, all phases, tariff no. 6 3.8.6
Primary reactive energy import, all phases, tariff no. 7 3.8.7
Primary reactive energy import, all phases, tariff no. 8 3.8.8
Primary reactive energy supply, all phases, tariff no. 1 4.8.1
Primary reactive energy supply, all phases, tariff no. 2 4.8.2
Primary reactive energy supply, all phases, tariff no. 3 4.8.3
Primary reactive energy supply, all phases, tariff no. 4 4.8.4
Primary reactive energy supply, all phases, tariff no. 5 4.8.5
Primary reactive energy supply, all phases, tariff no. 6 4.8.6
Primary reactive energy supply, all phases, tariff no. 7 4.8.7
Primary reactive energy supply, all phases, tariff no. 8 4.8.8
Primary active energy import, all tariffs
Primary active energy supply, all tariffs
Primary reactive energy import, all tariffs
Primary reactive energy supply, all tariffs
1.8.0
2.8.0
3.8.0
4.8.0
nvokWhNegPri
nvokVArhPosPri
nvokVArhNegPri
68
Gossen Metrawatt GmbH
Analog Values Function
Settings:
KMODE k = 5 LonA. The desired value is selected via LonKANAL. The unit shown is the
P-unit.
Lon
Channel
Network Variable
Data Type
Description
Phase voltages
44
45
46
47
48
49
50
51
52
53
54
nvoU12
SNVT_volt_f
Phase-to-phase voltage, L1 and L2
Phase-to-phase voltage, L2 and L3
Phase-to-phase voltage, L3 and L1
Phase-to-neutral voltage, L1 and N
Phase-to-neutral voltage, L2 and N
Phase-to-neutral voltage, L3 and N
Mean value of line-to-line voltage
Fundamental voltage frequency
THD voltage L1
nvoU23
SNVT_volt_f
nvoU31
SNVT_volt_f
nvoU1N
nvoU2N
nvoU3N
nvoUAvg
nvoFreq
nvoThdU1
nvoThdU2
nvoThdU3
SNVT_volt_f
SNVT_volt_f
SNVT_volt_f
SNVT_volt_f
SNVT_freq_hz
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
THD voltage L2
THD voltage L3
Phase currents
55
56
57
58
59
60
61
62
nvoI1
SNVT_amp_f
Current in phase L1
Current in phase L2
Current in phase L3
Phase current mean value
Calculated neutral conductor current
THD current I1
nvoI2
SNVT_amp_f
nvoI3
SNVT_amp_f
nvoIAvg
nvoIN
SNVT_amp_f
SNVT_amp_f
nvoThdI1
nvoThdI2
nvoThdI3
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
THD current I2
THD current I3
Please refer to the interface description for the LON interface (3-349-908-03) for further
information.
Gossen Metrawatt GmbH
69
12.4 Reinstalling a LON Device
The following actions are executed when a LON device is installed:
– Find a bus user based upon the entered neuron ID.
– Read out device type.
– Assign net variables to be read in to a summator channel. Each multi-channel device
has only one neuron ID. The channel is selected with the sub-channel parameter.
– For U1660 and U1661: Transmit parameters to the device.
– For energy metering (MODE = LON): Start delta value generation, i.e. the first value is
saved as previous value energyOld. Delta value = energy – energyOld. Energy values
recorded previously by the LON device are not taken into consideration.
Reinstallation of a LON channel is initialized with the LonNEW c = 1 command, or by
changing the neuron ID. Reinstallation of all LON channels is initialized with the
command:
LonNEW ** = 1 or via SETUP / LON / INSTALLATion
12.4.1 Preparing the Summator
Set bus termination at the control panel:
SETUP / LON / TERMINATION = 50 Ohm (SetLON = RA50)
LON network termination is set via TERMINATION:
TERMINATION = open
in case of external termination
TERMINATION = 50 Ohm with free topology
TERMINATION = 100 Ohm with bus topology using two terminators
(branch lines < 3 m).
12.4.2 Preparing the LON Device
Connect the LON terminal at the LON device to the summator.
Connect operating power to the LON device.
12.4.3 Configuration via the Summator Control Panel
• Configure the summator channel:
LON activity = STOPPED
Set the channel mode: MODE = LON (or LON-ANA, LON-PE, LON-INP, LON-REL)
Enter the sub-channel.
Enter the neuron ID of the LON device.
Enter and/or check all other channel parameters.
LON activity = RUN
• If the summator finds the device, the device type is displayed in the left column.
U1661.6 indicates a U1661 device with 6 channels.
Parameters are transmitted to the device, and are read back in the case of the U1660
and the U1661.
U1660: Check METER CONSTANT.
U1661: Check LONFACTOR, LONOFFSET and P-FACTOR.
• Check LON type.
If the type is displayed correctly: Check for channel errors.
Installation is now complete.
If the connected device is not displayed at LON type: Check the LON ID.
If LON type is ??????.?: Check the LON ID, and check LON wiring.
70
Gossen Metrawatt GmbH
Start reinstallation:
By changing the neuron ID. For example, set the first digit to 1, and then back to 0.
Reinstallation of all channels can be initialized via SETUP / LON / INSTALLATion.
Repeat this procedure until the device type is recognized.
12.5 Configuration at a PC with ECSwin Software
• Log on to the desired summator at the terminal.
• Access the “Configure / Channel parameters” menu function.
• Wait until all data have been read in.
• Enter all parameters to the “Meter inputs” index register.
– MConst is transmitted to the device for the U1660 (double check).
– P-FACTOR is transmitted to the device for the U1661 (double check).
• Enter all parameters to the “LON parameters” index register.
– The LON factor and LON offset parameters are transmitted to the device for the
U1661, (double check).
• Transmit data to the summator.
• Data are read back automatically and the LONtype column is filled in (this column has
read-only access). Due to the fact that type recognition via the LON bus takes several
seconds, “???????.?” is sometimes displayed as a type designation. The channel
parameters window should then be exited and reopened.
• Check LON type.
If the type is displayed correctly: Check for channel errors.
Installation is now complete.
If the connected device is not displayed at LON type: Check the LON ID.
If LON type is ??????.?: Check the LON ID, and check LON wiring.
Start reinstallation:
Use the following command for a single channel: LonRE c = 1 in terminal window
Use the following command for a all channels: LonRE ** = 1
Repeat this procedure until the device type is recognized.
12.6 Replacing a LON Device
• Deactivate the affected summator channel
(control panel: MODE = OFF; ECSwin: CMode = 0).
Deactivate all affected channels for multi-channel devices.
• Replace the LON device.
• Enter a new LON ID.
• Reactivate all deactivated channels
(control panel: MODE = LON; ECSwin: CMode = 4).
• Check LON type.
If the type is displayed correctly: Check for channel errors.
Replacement is now complete.
If the connected device is not displayed at LON type: Check the LON ID.
If LON type is ??????.?: Check the LON ID, and check LON wiring.
Parameters are transmitted to the device in the case of the U1660 and the U1661.
Check for parameters configuring errors. Control panel: CHANNEL ERROR menu,
terminal: ErrChan c
Gossen Metrawatt GmbH
71
If a parameters configuring error is detected:
For U1660: Check METER CONSTANT
For U1661: Check LONFACTOR, LONOFFSET and P-FACTOR.
Start reinstallation:
At the control panel: by changing the neuron ID. For example, set the first digit to 1,
and then back to 0.
Reinstallation of all channels can be initialized via SETUP / LON / INSTALLATion.
At terminal window: For one channel with the following command LonRE c = 1
For all channels with the following command LonRE ** = 1
Repeat this procedure until the device type is recognized.
12.7 Additional LON Parameters
• Waiting time for responses:
SETUP / LON / TIMING CODE = 9 (LONSTATTIMing = 9
TIMING-CODE
Waiting time in ms
)
LONSTATTIMing
Waiting time is set for a response with TIMING CODE.
TIMING CODE is an encoded value for the duration of
time allowed between a query and a response. The
default setting (9) should only be changed by experts!
0
16
1
24
2
32
3
48
4
64
• Time between two queries:
A delay can be selected here in order to reduced data
traffic in the bus.
SETUP / LON / POLL DELAY = 0 (LonPOLLDELay = 0
POLL DELAY is time between queries from 2 channels
in milliseconds.
Example: POLL DELAY = 300, 60 channels:
all channels are queried in 18 seconds.
5
96
6
128
192
256
384
512
768
1.024
1.536
2.048
3.072
7
)
8
9
10
11
12
13
14
15
Default:
POLL DELAY = 0, 60 channels:
all channels are queried in 5 seconds.
12.8 Channel Errors
The following channel errors may occur depending upon the type of installed device:
Bit U1601 Description A2000 DME400 U1660 U1661 U1681 U1687 U1689 OCL21 U1281 U1289 EM228x
0
U1381 U1387 EM238x
U1389
1
Communications error
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
2 Unknown device
3 Self-test error
4 Calibration error
6 Off-line
✔
1)
9 Broken sensor
10 Phase failure
11 Phase sequence error
12 Overflow
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
25 Parameter configura-
tion error
✔
1)
Only for U1661 B2 4 ... 20 mA
72
Gossen Metrawatt GmbH
Functions Overview U1602
74
Gossen Metrawatt GmbH
Functions Overview U1603
Gossen Metrawatt GmbH
75
14
Index
Numerics
E
2-wire technology ....................................................12
4-wire technology ....................................................12
ECL - Energy Control Language ............................... 54
Energy metering ........................................................ 7
Energy values ......................................................... 14
E-unit, P-unit .......................................................... 34
A
ANA faktor, ANA offset .............................................37
ANA fix point ............................................................37
Analog inputs (binary)
F
General ............................................................8
Terminal assignments .....................................48
Analog output test ....................................................32
Analog outputs A1 and A2 ..........................................8
ASCII oriented database .................................... 17, 54
Fiber optic transmission ........................................... 10
FINDER .................................................................6, 9
Firmware update ..................................................... 43
Floating decimal point numbers ................................. 7
H
B
I
Background Programs ..............................................54
Identification ........................................................... 13
Basic software configuration .....................................46
Battery
Interval ................................................................... 16
Interval source ........................................................ 31
Interval time ............................................................ 31
fault condition ..................................................9
Binary input ...............................................................8
Binary meter inputs ....................................................8
Binding ....................................................................63
Bootstrap and tests ..................................................32
Broadcast message ..................................................13
L
Language ............................................................... 32
LCD contrast ........................................................... 32
LEVEL ....................................................................... 8
Linking, differetial ..................................................... 6
LON activity ............................................................ 37
LON channel ........................................................... 37
LON factor, LON offset ............................................ 37
Long name ............................................................. 34
Loop resistance ...................................................... 10
C
C-Factor ..................................................................35
Channel errors .........................................................72
Channel numbers .......................................................6
Channel Start/Stop .............................................. 7, 34
Channel visible ........................................................34
Cost factors T1 and T2 .............................................31
M
Matching resistor (ECS LAN) .................................... 10
Maximum cable lengths ........................................... 62
Memory duration ..................................................... 16
Meter connection
Circuit diagram .............................................. 53
Settings ........................................................ 65
Meter constant ........................................................ 35
Multi-master system architecture ............................. 10
D
Data logger ..............................................................16
Data logger memory structure ..................................17
Date format .............................................................32
Debouncing time ........................................................8
DIR .........................................................................12
DME400 connection .................................................64
Drill hole pattern ......................................................52
DTE - Data Terminal Equipment ..................................9
N
Network topologies .................................................. 61
Neuron ID ............................................................... 37
Numbers range ......................................................... 7
76
Gossen Metrawatt GmbH
U-ratio, I-ratio ..........................................................35
User directory ..........................................................12
O
On/Off function ..........................................................7
P
P program ...............................................................54
Password ................................................................32
P-factor ..............................................................7, 35
POLL DELAY ...........................................................39
Power calculation ......................................................7
Power factor ............................................................35
Pulse time ...............................................................35
V
Virtual channels .................................................. 6, 54
R
Range of values for the data logger ...........................17
Reinstallation ...........................................................39
Repeat ....................................................................61
RS485 ....................................................................12
S
S0 / Level ...............................................................32
S0 standard ..............................................................8
Sampling time ...........................................................8
Source (tariff source) ...............................................31
Start/Stop function .....................................................7
STATCHECK ..............................................................9
Station ID ................................................................31
Station name ...........................................................31
SUBNET/NODE ........................................................39
Sub-program ...........................................................54
Switching the channel display On and Off ....................7
Synchronization pulse ................................................8
T
T fix point ................................................................31
Tariff unit ................................................................31
Time / Date .............................................................31
TIMING CODE ..........................................................39
Toroidal-core memory ..............................................17
Transmission speed .................................................10
Trigger edge .......................................................8, 35
U
Gossen Metrawatt GmbH
77
15
Maintenance, Repair, Product Support
Battery Maintenance
The integrated backup battery (MnO -Li button cell) can be replaced with the help of the
2
cover plate at the top of the instrument. The cover plate must first be removed. The
rounded end of the plate and its 90° angle tab are designed to accommodate the
battery. After laying the plate onto the button cell and snapping the tab into place, the
battery can be removed by gently pulling on the plate.
The new button cell (only type CR2450 batteries may be used) can then simply be
inserted gently into the battery compartment.
Attention: Only use the cover plate designed for this purpose to remove the battery, and
do not insert the plate into the housing next to the battery!
Opening of Equipment / Repair
The equipment may be opened only by authorized service personnel to ensure the safe
and correct operation of the equipment and to keep the warranty valid.
Even original spare parts may be installed only by authorized service personnel.
In case the equipment was opened by unauthorized personnel, no warranty regarding
personal safety, measurement accuracy, conformity with applicable safety measures or
any consequential damage is granted by the manufacturer.
Repair and Replacement Parts Service
DAkkS Calibration Center and Rental Instrument Service
If required please contact:
GMC-I Service GmbH
Service Center
Beuthener Straße 41
90471 Nürnberg • Germany
Phone +49 911 817718-0
Fax
+49 911 817718-253
e-mail [email protected]
This address is only valid in Germany. Please contact our representatives or subsidiaries
for service in other countries.
Product Support Industrial Division
If required please contact:
Gossen Metrawatt GmbH
Product Support Hotline – Industrial Division
Phone +49 911 8602-500
Fax
+49 911 8602-340
E-mail [email protected]
78
Gossen Metrawatt GmbH
Gossen Metrawatt GmbH
79
© Gossen Metrawatt GmbH
Edited in Germany • Subject to change without notice / Errors excepted • A PDF version is available on the Internet
All trademarks, registered trademarks, logos, product names, and company names are the property of their
respective owners.
Phone +49 911 8602-111
Fax
+49 911 8602-777
Gossen Metrawatt GmbH
Südwestpark 15
90449 Nürnberg • Germany
E-mail [email protected]
|