ABB MAGNE 3 User Manual

1. Install Magne and accessories as close to the door handle as possible. Use  
relevant mounting kit and follow the installation guide included in the kit.  
Installation tolerances for Magne 3 and JSM D23C on a sliding door:  
Excerpts from Original instructions  
Magne 3 and 4 Electromagnetic process lock  
A. Magne  
B. Anchor plate  
C. Cellular rubber  
D. Sliding door  
E. Fence  
Complete Product Manual [EN]  
found at:  
Product description  
X. 60 mm  
Y. 69 mm ±5  
Z. 18 mm ±5  
Magne is an electromagnetic process lock that locks a door or a hatch and is intended  
for applications that are sensitive to unintentional or unnecessary interruptions.  
Magne has a holding force of up to 1500 N.  
Magne can be installed on a door, preferably using an ABB mounting kit, available for  
sliding doors or hinged (conventional) doors.  
Magne 3 keeps a door locked. If used in safety applications, Magne 3 needs to be  
complemented with an external interlocking device.  
Magne 4 has an integrated Adam sensor which provides an interlocking function  
together with an Eva actuator. The Eva actuator is ordered and installed separately.  
2. Anchor plate (B) is installed with cellular rubber (C) between the anchor plate and  
the bracket (G) mounted on the door. The cellular  
rubber is attached to the anchor plate with  
Magne 4 is available with integrated Adam DYN (DYNlink signal) or Adam OSSD (OSSD  
signal) using M12 5-pole or M12 8-pole connector.  
adhesive tape and enables the anchor plate to  
adjust to Magne. Use suitable M8 screw (F).  
Recommended tightening torque is 7 Nm ±2.  
Anchor plates are delivered with a cellular rubber. Anchor plate 32E has an integrated  
permanent magnet. Anchor plate 32D is without a magnet. Y-connectors and other  
accessories are available to facilitate connection in series.  
Note! Do not compress the cellular rubber to  
a thickness less than 8 mm. Do not overtighten  
the screw. This can deform the anchor plate,  
causing reduced or no holding force.  
Connections  
Make sure the surfaces of the electromagnet (A) and the anchor plate (B) are  
completely parallel, i.e. that full  
contact is obtained when the door  
is closed.  
Installation tolerances:  
X. ±3 mm sideways  
Y. ±5 mm lengthways  
M12 5-pole connector  
1) Brown: Locking signal +24 VDC  
2) White: Not used  
M12 5-pole connector  
1) Brown: +24 VDC  
2) White: DYNlink signal in  
M12 8-pole connector  
1) White: DYNlink signal in  
2) Brown: +24 VDC  
3) Blue: 0 V  
4) Black: Not used  
5) Grey: Info output, locked  
3) Blue: 0 V  
4) Black: DYNlink signal out  
5) Grey: Locking signal +24 VDC  
3) Green: Locking signal +24 VDC  
4) Yellow: 0 V  
5) Grey: Info output (Adam and Eva  
closed & Magne locked)  
6) Pink: DYNlink signal out  
7) Blue: 0 V  
3. The safety functionality of Magne 4 is based on the integrated Adam sensor and  
the Eva actuator. Eva unit (A) must be  
8) Red: Not used  
correctly positioned above the yellow  
cover on Magne/Adam (B) when the  
door is closed.  
Warning! Always use shielded  
cables to connect the unit to the  
rest of the safety circuit.  
Warning! The info output is  
non-failsafe and shall never be  
used to control a safety  
application.  
Positioning tolerances:  
X. ±5 mm sideways  
Y. ±5 mm lengthways  
Z. 2-7 mm  
Warning! The DYNlink signal  
or OSSD signals are used to  
control the safety application.  
M12 8-pole connector  
1) White: DYNlink signal in  
2) Brown: +24 VDC  
3) Green: Locking signal +24 VDC  
4) Yellow: 0 V  
5) Grey: Info output (Adam and  
Eva closed)  
6) Pink: DYNlink signal out  
7) Blue: 0V  
M12 8-pole connector  
1) White: OSSD1 out  
2) Brown: +24 VDC  
3) Green: OSSD1 in  
4) Yellow: OSSD2 in  
5) Grey: Info output (Adam and  
Eva closed & Magne locked)  
6) Pink: OSSD2 out  
7) Blue: 0 V  
8) Red: Locking signal +24 VDC  
Note! For the sensor to work as  
intended it is very important that the units are correctly positioned and that the  
safety functions are tested.  
Note! Several Magne 3X units  
can be connected using a M12-3A  
Y-connector or several Magne 4  
OSSD-Info using a M12-3G Y-  
connector, but the info-signal will  
not be available. Several Magne 4X  
DYN units can be connected using  
a M12-3S Y-conector.  
4. Connect the pin out according to chapter ‘Connections’.  
5. Connect the M12 connector to Magne.  
8) Red: Info output (Locked)  
Note! Make sure no power supply is connected when cable is fitted to the  
Magne M12 pin out.  
Safety precautions  
6. Close the door to put Eva within sensing distance of Adam.  
7. Connect Magne to the power supply and turn power on.  
Warning! Carefully read through the entire product manual before using the  
device.  
Warning! The devices shall be installed by authorized personnel following the  
Safety regulations, standards and the Machinery directive.  
Note! Only connect Magne to power supply when Eva is within sensing  
distance. The integrated Adam sensor in Magne 4 needs to learn the Eva code.  
For Magne 3 the blue LED will illuminate with a solid light when connected.  
For Magne 4 the green LED will illuminate with a solid light. The blue LED will  
illuminate with a solid light when the locking signal is activated.  
Warning! Failure to comply with instructions, operation that is not in accordance  
with the use prescribed in the instructions, improper installation or handling of the  
device can affect the safety of people and the plant.  
Installation  
8. After installation, check the locking function.  
Installation shall be done in accordance with a risk assessment for the individual  
application.  
Warning! All safety functions shall be tested before starting up the system.  
Warning! Do not defeat, tamper or bypass the safety function. Failure can result  
in death or serious injury.  
Caution! After installation, check the locking function and that the surfaces of  
the magnet and the anchor plate are parallel, i.e. that full contact is obtained when  
the door is closed. If the anchor plate tilts, the holding force of the lock can be  
significantly reduced or eliminated.  
Warning! The M12 connector shall be connected after Magne has been installed  
on the intended surface.  
Caution! Magne shall be installed as close to the door handle as possible. The  
distance between the lock and the handle creates a lever effect, reducing the holding  
force.  

Motorola MOTO 68000202973 B User Manual
IronKey USB Flash Drives User Manual
Fujitsu MCM3064AP User Manual
Fujitsu Embedded MegaRAID SATA CA97232 0014 01EN User Manual
Cypress Quad HOTLink II CYV15G0404RB User Manual
Curtis RCD633 User Manual
Centon electronic DataStick Designer DSD4GB 005 User Manual
Bunn H10X User Manual
Bunn Coffeemaker LCC 2 User Manual
Ariston MCA15NAP User Manual