Smith Cast Iron Boilers GB100W User Manual

GB100IOM-7  
GB100W  
NATURAL OR PROPANE GAS BOILER  
INSTALLATION & OPERATING  
INSTRUCTIONS  
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE  
VESSEL CODE, SECTION IV FOR MAXIMUM ALLOWABLE WORKING PRESSURE OF  
50 PSI, 345 kPa WATER  
NOTE TO INSTALLING CONTRACTOR: READ THESE INSTRUCTIONS CAREFULLY.  
THEY WILL SAVE YOU TIME IN ASSEMBLING BOILER PROPERLY.  
WARNING: Installation and service must be performed by a qualified installer, service  
agency or the gas supplier in accordance with all local and national codes. Failure to  
comply with this warning can result in a fire or explosion causing property damage,  
personal injury or loss of life!  
WARNING: If the information in this manual is not followed  
exactly, a fire or explosion may result causing property damge,  
personal injury or loss of life.  
Do not store or use gasoline or other flammable vapors and liquids  
in the vicinity of this or any other appliance.  
What to do if you smell gas:  
• Do not try to light any appliance.  
• Do not touch any electrical switch. Do not use any phone in your  
building.  
• Immediately call your gas supplier from a neighbor's phone.Follow  
the gas supplier's instructions.  
• If you cannot reach your gas supplier, call the fire department.  
Installation and service must be performed by a qualified installer,  
service agency or the gas supplier.  
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE BOILER.  
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  
In Canada: 7555 Tranmere Drive, Mississauga, Ont. L5S 1L4 (905) 672-2991 Fax (905) 672-2883  
Page 3  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Direct all questions to your Smith Cast Iron Boiler  
BOILER LOCATION  
distributor or write to the Customer Service Department,  
260 North Elm Street, Westfield, MA 01085. Always  
include the model and serial numbers from the rating  
plate of the boiler in question.  
WARNING: This boiler is for installation on non-  
combustible floors only! A special base  
supplied by the manufacturer must be used to  
install this boiler on a combustible floor. Failure  
to comply with this warning can result in  
property damage, severe personal injury or  
death!  
The owner should maintain a record of all service work  
performed with the date and a description of the work  
done. Include the name of the service organization for  
future reference.  
1. Locate the boiler in an area that provides good  
access to the unit. Keep in mind that servicing may  
require the removal of jacket panels. Accessibility  
clearances must take precedence over fire  
protection clearances.  
Where required by the authority having jurisdiction, the  
installation must conform to the Standard for Controls  
and Safety Devices for Automatically Fired Boilers,  
ANSI/ ASME CSD-1.  
The installation must conform to the requirements of  
the authority having jurisdiction or, in the absence of  
such requirements, to the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54-latest revision. In Canada,  
installation must be in accordance with the requirements  
of CAN/CGA B149.1 or 2 Installation Code for Gas  
Burning Appliances and Equipment.  
2. An optimum site will be level, central to the piping  
system, close to a chimney and have adequate  
fresh air for combustion.  
3. Ensure that the floor is structurally sound and will  
support the weight of the boiler. This boiler is  
designed for non combustible floors only! A special  
base supplied by Smith Cast Iron Boilers must be  
used if the boiler is to be installed on a combustible  
floor. NEVER USE A SUBSTITUTE BASE ON A  
COMBUSTIBLE FLOOR! Never install this boiler on  
carpeting!  
BOILER RATINGS AND CAPACITIES  
Before undertaking the installation of the GB100W  
check the boiler rating plate to ensure that the boiler is  
the proper size for the job. The “Net I=B=R Ratings”  
specify the equivalent amount of direct cast iron  
radiation that the boiler can handle under normal  
conditions. Also ensure that the boiler has been set up  
for the type of gas available at the installation site.  
Other important considerations are the availability of  
an adequate electrical supply, fresh air for combustion  
and a suitable chimney or vent system.  
4. DO NOT install this boiler in a location that would  
subject any of the gas ignition components to direct  
contact with water or excessive moisture during  
operation or servicing.  
5. DO NOT place this boiler in a location that would  
restrict the introduction of combustion air into the  
boiler. NEVER store objects on or around the boiler.  
NOTES:  
1. For altitudes above 2000 ft, 610 m, ratings should  
be reduced at the rate of 4% for each 1000 ft, 305  
m above sea level, 10% in Canada.  
2. If ordering a boiler for use with LP gas add a P to  
the model number, ie PGB100.  
WARNING: Never store combustible materials,  
gasoline or any product containing flammable  
vapors or liquids in the vicinity of the boiler.  
Failure to comply with this warning can result in  
extensive property damage, severe personal  
injury or death!  
Page 4  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
6. If the boiler is to be located in an alcove, closet or  
other confined space the distances from the boiler  
and it’s vent system to all combustible construction  
must be equal to or greater than the minimum  
clearances in Figure 1. When installed in a closet or  
confined space two permanent openings of equal  
area adjoining another room or rooms having  
sufficient volume to meet the requirements of an  
unconfined space must be provided. Each opening  
must have a minimum free area of one square inch  
per 1000 Btu/hr, 2200 mm2/kW based on the total  
input rating of all gas utilization equipment in the  
confined area. Each opening must be no less than  
100 in2, 64516 mm2, in size. The upper opening  
must be within 12 in, 305 mm, of, but not less than  
3 in, 76 mm, from the top of the enclosure. The  
bottom opening must be within 12 in, 305 mm, of,  
but not less than 3 in, 76 mm, from the bottom of the  
enclosure.  
WARNING: Never install a PGB100W, propane  
boiler in a closet or other confined or enclosed  
spaceunless the installation conforms to the  
latest revision of the National Fuel Gas Code,  
ANSI Z223.1 and all applicable local building  
codes! Failure to comply with this WARNING  
could result in a fire or explosion causing  
extensive property damage, severe personal  
injury or death!  
Figure 1: Clearances to Combustible Construction  
C
TO  
COMBUSTIBLE  
MATERIAL  
A
*
E
F
D
B
FRONT  
For  
AL  
CL  
Servicing  
in  
in  
24  
*
mm  
610  
*
in  
51  
2
mm  
1295  
51  
mm  
N/A  
N/A  
152  
102  
254  
254  
A
B
C
D
E
F
N/A  
N/A  
6
6
152  
102  
178  
102  
6
152  
102  
178  
102  
4
4
4
7
7
10  
10  
4
4
AL = Alcove  
CL = Closet  
*No Front Wall in Alcove  
Page 5  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Figure 2: Special Base Installation on  
Combustible Flooring  
COMBUSTIBLE FLOOR OPTION  
The GB100W boiler has been designed for use on  
noncombustible floors only. If a GB100W boiler is to  
be installed on combustible flooring of any type, it MUST  
be installed using the Special Base designed by the  
Smith Cast Iron Boiler Co. Do NOT use any base other  
than the one specifically designed for it if installing a  
GB100W boiler on combustible flooring.  
WARNING: Never install a GB100W boiler on  
combustible flooring without using the special  
base specifically designed for it by the Smith  
Cast Iron Boiler Co. Do not alter in any way the  
special base supplied by the Smith Cast Iron  
Boiler Co. Failure to comply with this warning  
may result in a fire causing property damage,  
personal injury or death!  
To order the Special Base contact the nearest  
Smith Cast Iron Boiler distributor and ask for the  
“Noncombustible Floor Pan”.  
Determine where the boiler will be located by following  
the instructions in the Boiler Location section of this  
manual. Place the Special Base in this location and  
fasten it in place to prevent it from moving while the  
boiler is being placed on it.  
SUPPORT  
CHANNEL  
FRONT  
GRILL  
If the GB100W is being installed in an alcove or closet  
ensure that the minimum distance to combustible  
construction requirements, listed in Figure 1, are met.  
Remove the sheet metal base pan attached to the  
boiler. Position the boiler in front of the Special Base. It’s  
suggested that two lengths of 3" pipe the width of the  
boiler, or longer, be placed under the boiler base side  
panels.  
COMBUSTION AIR  
WARNING: This boiler must be supplied with  
combustion air in accordance with Section 5.3,  
Air for Combustion & Ventilation, of the latest  
revision of the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and all applicable local building  
codes. Failure to provide adequate combustion  
air for this appliance can result in excessive  
levels of carbon monoxide which can result in  
severe personal injury or death!  
CAUTION: Be careful not to damage the burners,  
pilot assembly or any other gas train components  
during this procedure. If a component is damaged,  
replace it!  
Carefully roll the boiler up to the front of the Special  
Base. Align the boiler base side panels with the Special  
Base support channels. Using great care, slide the boiler  
onto the Special Base.  
Table 1: Vent and Chimney Dimensions  
Boiler Size  
3
4
5
6
7
8
9
10 11 12  
(Sections)  
Vent Pipe  
Dia. (In.)  
CAUTION: Never lift the boiler by the jacket panels  
or flue collector/draft diverter or severe damage to  
the boiler may result!  
5
5
6
6
7
7
8
8
9
9
Chimney  
Flue Size  
Chimney  
Height (Ft.)  
8 x 8  
8 x 12  
Center the boiler from side to side on the Special Base.  
Ensure that the back of the burner base side panels  
are flush with the back of the Special Base support  
channels. Install the front grill supplied with the Special  
Base. Complete the installation in accordance with the  
instructions set forth in this manual.  
18 18 18 17 17 17 16 16 16 16  
Page 6  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
To operate properly and safely this boiler requires a  
continuous supply of air for combustion. Oxygen is used  
by the burners in the boiler to burn the gas. In addition,  
air is also used to assist in the safe disposal of the  
products of combustion. This air is known as dilution  
air and mixes with the products of combustion to assist  
in it’s exit through the flue pipe and chimney. An  
adequate supply of outside air must be available to  
replace that used by these processes.  
WARNING : If an appliance using any type of a  
mechanical draft system operating under  
positive pressure is connected to a chimney  
flue, never connect any other appliances to this  
flue. Doing so can result in the accumulation of  
carbon monoxide which can cause severe  
personal injury or death!  
Older houses often have enough “leakage” to provide VENT CONNECTIONS  
an adequate amount of combustion air provided that  
the demand for combustion air is not too great. Homes  
that are relatively new or “tight” will most likely require  
the installation of a fresh air duct or other means of  
providing air for combustion. Any home utilizing other  
gas burning appliances, a fireplace, wood stove or any  
type of exhaust fan must be checked for adequate  
combustion air when all of these devices are in operation  
at one time. Sizing of an outside air duct must be done  
to meet the requirements of all such devices.  
Always use a type B or C vent pipe of the proper  
diameter for the boiler. Use the shortest, straightest  
vent system possible for the particular application. The  
vent system should be sloped up toward the chimney  
at a rate of 1/4 in/ft, 2 mm/m. Ensure that the flue pipe  
is properly supported and each connection securely  
fastened with at least 3 corrosion resistant sheet metal  
screws. The termination of the vent pipe should be  
flush with the inside of the chimney flue.  
Always provide a minimum clearance of 6 in, 152 mm,  
between type C vent pipe and any combustible  
materials. Type B1 vent may be used, clearance  
between it and any combustible material must be as  
listed.  
Table 2: Combustion Air Duct Sizing  
Input Btuh  
1/4" Wire  
Mesh Screen  
Input Btuh  
Metal  
Louvers  
Input Btuh  
Wooden  
Louvers  
Fresh Air  
Duct Size  
3" x 12"  
8" x 8"  
144,000  
256,000  
384,000  
512,000  
108,000  
192,000  
288,000  
384,000  
36,000  
64,000  
96,000  
128,000  
WARNING: Failure to maintain minimum  
clearances between vent connectors and any  
combustible material can result in extensive  
property damage, severe personal injury or  
death!  
8" x 12"  
8-1/2" x 16"  
If the boiler will be located in an alcove, closet or any  
confined space refer to item 6 in the Boiler Location  
section of this manual.  
WARNING: Never modify or alter any part of the  
draft hood or vent damper supplied with this  
boiler. This includes the removal or alteration of  
any baffles in the draft hood or flue collar.  
Never install a vent pipe of a diameter different  
than that of the boiler draft hood flue collar,  
table 1. Failure to comply with this warning can  
result in severe personal injury or death.  
CHIMNEY & VENT PIPE CONNECTIONS  
WARNING: This boiler must be vented in  
accordance with Part 7, Venting of Equipment, of  
the latest revision of the National Fuel Gas code,  
ANSI Z223.1/NFPA 54 and all applicable local  
building codes. Improper venting of this  
appliance can result in excessive levels of  
carbon monoxide which can result in severe  
personal injury or death!  
Common Vent Systems  
If an existing appliance is removed from a common  
venting system, the common venting system may then  
be too large for the proper venting of the remaining  
appliances connected to it. At the time of removal of  
an existing boiler, the following steps shall be followed  
with each appliance remaining connected to the  
common venting system placed in operation, while the  
other appliances remaining connected to the common  
venting system are not in operation.  
Chimney Inspection & Sizing  
If this boiler will be connected to a masonry chimney, a  
thorough inspection of the chimney must be performed.  
Ensure that the chimney is clean, properly constructed  
and properly sized. Table 1 lists the flue size and  
chimney height required for this boiler.  
Au moment du retrait d'une chaudière existante, les  
mesures suivantes doivent être prises pour chaque  
appareil toujours raccordé au système d'évacuation  
commun et qui fonctionne alors que d'autres appareils  
toujoursraccordésausystèmed'évacuationnefonction-  
nent pas: système d'évacuation.  
When more than one appliance is connected to the  
same chimney flue, the flue must be large enough to  
handle both appliances.  
The vent installation must be in accordance with Part 7  
of the latest revision of the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54.  
Page 7  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
f) After it has been determined that each appliance  
a) Sealallunusedopeningsinthecommonventsystem  
and repair any leaks.  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers  
and any other gas-burning appliance to their previ-  
ous condition of use.  
Sceller toutes les ouvertures non utilisées du sys-  
tème d'évacuation.  
b) Visually inspect the vent system to ensure that it is  
properly pitched and sized and that there are no  
structural deficiencies such as blockages, restric-  
tions, leakage, or corrosion that could cause an  
unsafe condition.  
Une fois qu'il a été d éterminé, selon la métode  
indiquée ci-dessus, que chaque appareil raccordé  
au système d'évacuation est mis à l'air libre de façor  
adéquate. Remettre les portes et les fenêtres, les  
ventilateurs, les registres de cheminées et les  
appareils au gaz à leur position originale.  
Inspecter de façon visuelle le système d'évacu-ation  
pourdéterminerlagrosseretl'inclinaisonhorizontale  
qui conviennent et s'assurer que le système est  
exempt d'obstruction, d'étranglement de fruite, de  
corrosion et autres défaillances qui pourraient  
présenter des risques.  
g) Any improper operation of the common venting sys-  
tem should be corrected so the installation conforms  
with the National Fuel Gas Code, ANSI Z223.1/  
NFPA 54. When resizing any portion of the common  
venting system, the common venting system should  
be resized to approach the minimum size as deter-  
mined using the appropriate tables in Appendix F in  
the National Fuel Gas Code, ANSI Z223.1/ NFPA 54  
and or CSA B149 Installation Codes.  
c) As far as is practical close all doors and windows  
common to the space in which the vent system and  
appliances connected to the common vent system  
are contained. Turn on all exhaust fans, clothes  
dryers, range hoods and appliances requiring air for  
combustion that are not connected to the common  
vent system. Ensure that all appliances operate at  
maximum speed. Do not operate a summer exhaust  
fan. Close all fireplace dampers.  
Tout mauvais fonctionnement du systéme d'évacu-  
tion commun devrait étré corrigé de façor que  
l'installation soit conforme au National Fue Gas  
Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'in-  
stallationCSA-B149. Silagrosseurd'unesectiondu  
système d' évacuation doit étré modifiée, le système  
devrait étré modifié pour respecter les valeurs  
minimales des tableaux pertinents de l'appendice F  
du National Fuel Gas Code, ANSI Z223.1/ NFPA 54  
et (ou) des codes d'installation CSA-B149.  
Dans la mesure du possible, fermer toutes les portes  
et les fenêtres du bâtiment et toutes les portes entre  
l'espace où les appareils toujours raccordés du  
système d'évacuation sont installés et les autres  
espaces du bâtiment. Mettre en marche les  
sécheuses, tous les appareils non raccordés au  
systèmed'évacuationcommunettouslesventilateurs  
d'extraction comme les hottes de cuisinère et les  
ventilateurs des salles de bain. S'assurer que ces  
ventilateurs fonctionnent à la vitesse maximale. Ne  
pas faire fonctionner les ventilateurs d'été. Fermer  
les registres des cheminées.  
Vent Dampers  
This boiler comes from the factory equipped with a  
vent damper specifically engineered for it. The vent  
damper must be properly installed to obtain the high  
performance for which this boiler was designed. If the  
damper is damaged or missing do not install the boiler  
without it! Contact the nearest Smith Cast Iron Boilers  
distributor to obtain the proper vent damper.  
d) Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat so  
appliance will operate continuously.  
WARNING: On boilers with a constant pilot  
ignition system, ensure that the hole in the  
damper blade is not plugged. Failure to do this  
could result in the spillage of carbon monoxide  
which can result in severe personal injury!  
Mettre l'appareil inspecté en marche. Suivre les  
instructions d'allumage. Régler le thermostat de  
façon que l'appareil fonctionne de façon continue.  
e) Test for spillage at the draft hood relief opening after  
5 minutes of main burner operation. Use the flame of  
a match or candle, or smoke from a cigarette, cigar or  
pipe.  
Vent dampers are designed for use with only one  
appliance. NEVER connect more than one appliance  
to a single vent damper.  
Locate the vent damper so that it is accessible and the  
damper position indicator is visible. Maintain a minimum  
of 6 inches between the damper and any combustible  
materials!  
Faire fonctionner le brûleur principal pendant 5 min  
ensuite, déterminer si le coupe-tirage déborde à  
l'ouverture de décharge. Utiliser la flamme d'une  
allunette ou d'une chandelle ou la fumée d'une ciga-  
rette, d'un cigare ou d'une pipe.  
Page 8  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Fasten the vent damper to the flue collar and vent pipe  
Figure 4: Heating System Piping  
using at least 3 corrosion resistant sheet metal screws  
per joint. Connect the damper harness to the top panel  
with the BX connector supplied. Plug the Molex  
connector on the damper harness into the mating plug  
on the harness located inside the control compartment.  
DISCHARGE PIPE  
SUPPORT DISCHARGE PIPING  
SO AS TO AVOID STRAIN ON  
THE VALVE BODY.  
SIZE TO EQUAL  
VALVE OUTLET.  
DO NOT RESTRICT  
FLOW.  
FOR DISCHARGE  
THROUGH ROOF  
CONSULT THE  
SMITH CO.  
The vent damper is operating properly when it opens  
completely upon a call for heat and closes completely  
when the call for heat ends. The vent damper must be  
in the open position when the boilers main burners are  
in operation.  
1" CLEARANCE MUST BE  
MAINTAINED BETWEEN  
HOT WATER PIPING  
AND COMBUSTIBLE  
CONSTRUCTION.  
Figure 3: Vent Damper Location  
DAMPER BLADE POSITIONED  
FRONT TO BACK OF BOILER  
MOTOR TO FACE  
FRONT OF BOILER  
DISCHARGE SO AS TO AVOID EXPOSURE OF PERSONS TO  
HOT LIQUID OR VAPOR. LEAVE OPEN END VISIBLE FOR  
PERIODIC INSPECTION FOR SLOW LEAKAGE OR DRIPS.  
FRONT OF  
BOILER  
HEATING SYSTEM PIPING  
CAUTION: All piping must be installed by a qualified  
technician in accordance with the provisions set  
forth in the applicable ANSI/ASME standards and  
local building codes and regulations. Improper  
piping of this boiler can cause flooding, extensive  
property damage, heating system damage or  
damage to the boiler.  
The GB100W hot water boiler comes from the factory  
ready to be piped to the heating system. Each boiler is  
equipped with a safety relief valve. This valve must be  
piped in accordance with the ANSI/ASME Boiler and  
Pressure Vessel Code, Section IV. Figure 4 provides a  
pictorial description of the boiler and piping components.  
Page 9  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
The boiler should be placed in the location selected for  
Figure 5: TACO 007 Performance Curve  
it. Refer to the BOILER LOCATION section in this  
manual. Ensure that the boiler is level from front to  
back and from side to side. Use metal shims to level  
the boiler. NEVER use wood, plastic or other  
combustible materials as shims.  
10  
8
6
All heating system piping must be installed in  
accordance with the ANSI/ASME Boiler and Pressure  
Vessel Code, Section IV, and ANSI/ ASME CSD-1,  
Standard for Controls and Safety Devices for  
Automatically Fired Boilers. All applicable local codes  
and ordinances must also be followed.  
4
TACO 007 CIRCULATOR  
PERFORMANCE CURVE  
If the boiler is installed above any radiation elements it  
must be fitted with a low water cutoff device, L.W.C.O.,  
installed above the normal boiler water level.  
2
0
Circulators  
A TACO 007 circulator has been supplied as standard  
equipment with the boiler. The 007 is sized for use in a  
closed heating system with a 30 psi, 207 kPa, maximum  
operating pressure. If the 007 circulator furnished with  
this boiler does not have the required capacity for the  
system in which it is to be installed, an extra zone  
circulator must be provided. A circulator with a higher  
capacity may also be used. Figure 5 depicts the  
performance curve for the TACO 007 circulator.  
0
5
10  
15  
20  
25  
FLOW - GPM  
Piping For Use With Cooling Units  
The boiler, when used in connection with a refrigeration  
system, must be installed so the chilled medium is piped  
in parallel with the boiler. Appropriate valves must be  
used to prevent the chilled water from entering the  
boiler. See Figure 6 for the proper piping layout.  
When a boiler is connected to a heating coil that may  
be exposed to refrigerated air from an air handling  
device, the piping system must be equipped with flow-  
control valves or some other automatic means of  
preventing gravity circulation of the boiler water during  
the cooling cycle.  
Page 10  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
CAUTION: To prevent damage due to excessive  
condensation, one of the following piping options  
Figure 8: Pump Away Bypass  
should be used.  
SUPPLY  
RETURN  
System Bypass  
For systems using a circulator on the return as either a  
single zone, or multiple zones with zone valves, install  
a system bypass line between the supply and return  
on the suction side of the circulator, see Figure 7.  
Install a metering valve in this bypass line to regulate  
the amount of flow that will be diverted to the return. A  
plug valve offers the best control for this application.  
Although other valves may be less expensive, a plug  
valve will be easier to set accurately.  
50%  
120° F  
50%  
160° F  
50%  
160° F  
100%  
140° F  
100%  
160° F  
PUMP AWAY  
BYPASS  
In the absence of a flow indicator, set the metering  
valve using temperature as a guide. The accompanying  
diagram suggests one scenario. This addition requires  
only two tees, a plug valve, and a small amount of pipe  
and offers the simplest approach to reliably control  
condensation. For this system and those that follow,  
be aware that you are using a percentage of the pump  
capacity to blend, but the friction loss for the entire  
pump flow has been reduced. In most cases, the  
standard pump packaged with the boiler has enough  
capacity to feed the baseboard distribution system and  
the bypass line.  
Pumped Blend  
An additional circulator can also be used to provide a  
return water temperature blend. This method works  
well with systems with multiple zones with circulators,  
see Figure 9. The dedicated bypass circulator provides  
a strong blending flow without diminishing the flow  
available to any heating zone. Any residentially sized  
circulator is adequate for this purpose.  
Each of these bypass solutions also has the added  
benefit of increasing circulation in the boiler which will  
maximize tankless coil output and increase the accuracy  
of temperature sensing controls.  
Figure 7: System Bypass  
SUPPLY  
RETURN  
Figure 9: Pumped Bypass  
50%  
120° F  
50%  
160° F  
50%  
160° F  
SUPPLY  
RETURN  
100%  
100%  
160° F  
140° F  
100%  
120° F  
100%  
160° F  
100%  
160° F  
SYSTEM  
BYPASS  
200%  
140° F  
200%  
160° F  
Pump Away Bypass  
PUMPED  
BYPASS  
For systems that use a single circulator to pump away  
from the boiler, the bypass should be installed on the  
discharge side of the circulator, see Figure 8. Full  
temperature water supplies the baseboard distribution  
system as before. Half of the circulator’s volume moves  
through the bypass, blending and heating the cooler  
return water. Again, the cost of installing the bypass is  
small and setting it by temperature can be accomplished  
with a contact thermometer.  
Page 11  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Reverse Acting Aquastats  
GAS SUPPLY PIPING  
An alternative for existing systems experiencing  
condensation that does not require re-piping the boiler  
utilizes a reverse acting aquastat, one that makes on  
temperature rise. This approach works best in single  
zone systems. Wired in series with the circulator, this  
control holds the circulator off until the boiler reaches  
an acceptable temperature and then starts system  
circulation, see Figure 10.  
WARNING: All gas piping must be installed by a  
qualified technician in accordance with the  
provisions set forth in the latest revision of ANSI  
Z223.1 and all applicable local building codes  
and regulations. All LP gas connections must  
be made by a licensed propane installer. Failure  
to comply with this WARNING can result in  
extensive property damage, severe personal  
injury or death!  
The most commonly available reverse acting aquastat  
is a Honeywell L4006B. The aquastat should be  
mounted in an immersion well directly installed in the  
boiler. The use of heat conductive grease, Honeywell  
part # 972545, in the immersion well is strongly  
recommended for fast and accurate temperature  
response. Set this adjustable aquastat to make at no  
less than 130° F, 54°C. While this method can cause  
the circulator to cycle more frequently, setting the  
aquastat’s differential to the maximum 25-30°F will  
minimize short cycling.  
The GB100W hot water boiler comes from the factory  
ready to be piped to the gas supply.  
WARNING: Check the boiler rating plate to make  
sure that the boiler is for the type of gas that will  
be used. If it isn’t, do not connect the boiler to  
the gas supply. Failure to comply with this  
warning can result in extensive property  
damage, severe personal injury or death!  
Figure 10: Reverse Aquastat  
If for any reason the boiler is not for the type of gas  
available at the installation site, call the nearest Smith  
Cast Iron Boiler distributor to resolve the problem.  
115 volts  
reverse  
aquastat  
Table 3 should be used to ensure that the gas supply  
piping is sized properly. If more than one appliance is  
supplied by the same supply pipe, the piping must be  
sized based on the maximum possible demand. Do not  
neglect the pressure drop due to pipe fittings. Table 4  
should be used in conjunction with Table 3 to ensure  
that the supply piping has the capacity to meet the  
demand.  
N.O.  
circulator  
24 volts  
T
t'stat  
T
operating  
aquastat  
REVERSE  
AQUASTAT  
Table 3: Gas Pipe Capacity  
Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas  
GV  
N.C.  
SET AT 120° F  
at pressure of 0.5 psig or less and a 0.3" W.C. pressure drop.  
Nominal  
Pipe length in feet  
40 50 60  
Maximum gas volume in cubic feet/hr, (ft3/hr)  
90 79  
520 350 285 245 215 195 170 150 120  
Iron Pipe 10  
Size (in.)  
20 30  
80 100 150  
3/4"  
1"  
278 190 152 130 115 105  
64  
1-1/4" 1050 730 590 500 440 400 350 305 250  
1-1/2" 1600 1100 890 760 670 610 530 460 380  
Table 4: Equivalent Length Chart  
Eqivalent length of pipe fittings in feet  
Nominal  
Iron Pipe  
Size  
Type of pipe fitting  
90° Elbow  
Tee  
Gate Valve  
Gas Cocks  
(flow thru branch) (full port)  
Equivalent length in feet  
(inches.)  
3/4"  
2.06  
2.62  
3.45  
4.02  
4.12  
5.24  
6.90  
8.04  
0.48  
0.61  
0.81  
0.94  
1.25  
1.60  
2.15  
2.50  
1"  
1-1/4"  
1-1/2"  
Page 12  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Figure 11 depicts the proper way to connect the boiler  
to the gas supply piping. The manual shut-off valve  
ELECTRICAL WIRING  
MUST be installed in the supply piping. It should be  
approximately 5 ft, 1.5 m above the floor. Provide a  
drip leg/sediment trap at the bottom of the vertical  
section of the gas supply pipe. A ground joint union  
should be installed between the boiler gas controls  
and the supply piping. Each of these items are needed  
to ensure long life and ease of servicing. Always use a  
pipe sealant that is suitable for use with LP gas.  
WARNING: All electrical wiring must conform to  
all applicable local codes and the latest revision  
of the National Electrical Code, ANSI/NFPA-70.  
Failure to comply with this warning can result in  
extensive property damage, personal injury or  
death!  
Electrical Power Connections  
Figure 11: Gas Supply Piping  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors can cause  
improper and dangerous operation!  
GAS INLET  
INSTALL MANUAL  
SHUT-OFF VALVE  
5 FT. ABOVE FLOOR  
WHERE REQUIRED BY  
LOCAL CODES  
ATTENTION: Au moment de l'entretien des  
commandes, étiquetez tous les fils avant de les  
débrancher.Deserreursdecâblagepeuvententraîner  
un fonctionnement in-adéquat et dangereux.  
S'assurer que l'appareil fonc-tionne adéquatement  
une fois l'entretirn terminé.  
GAS SUPPLY  
PIPING  
GROUND JOINT  
UNION  
SEDIMENT TRAP  
OR  
DRIP LEG  
(TO EXTEND TO FLOOR)  
The electrical connections to this boiler must be made  
in accordance with all applicable local codes and the  
latest revision of the National Electrical Code, ANSI/  
NFPA-70. Installation should also conform with CSA  
C22.1 Canadian Electrical Code Part I if installed in  
Canada. Install a separate 120 volt 15 amp circuit for  
the boiler. A shut-off switch should be located at the  
boiler. The boiler must be grounded in accordance with  
the authority having jurisdiction, or if none, the latest  
revision of the National Electrical Code, ANSI/NFPA-  
70.  
TO  
BOILER  
FLOOR LEVEL  
CAUTION: Always use a wrench on the gas valve  
body when making gas connections to it. Never  
over-tighten the piping entering the gas valve body.  
Failure to comply with this caution may result in gas  
valve failure!  
Line voltage field wiring of controls and other devices  
must conform to the temperature limitation of type T  
wire at 95°F, 35°C, above room temperature. Use  
copper conductors with a minimum size of #14 awg.  
Low voltage wiring must not be less than #18 awg with  
a neoprene, thermoplastic or other equivalent insulation  
having a minimum insulation thickness of 0.012 in,  
0.3 mm.  
Safe lighting and other performance criteria were met  
with the gas manifold and control assembly provided  
on the boiler. All gas connections MUST be leak tested  
before putting the boiler into operation.  
WARNING: Never use an open flame to test for  
gas leaks. Always use an approved leak  
detection method. Failure to comply with this  
warning can cause extensive property damage,  
severe personal injury or death!  
Thermostat Installation  
ALWAYS follow the instructions included with the  
thermostat to be used to control the boiler. Proper  
location of the thermostat will ensure efficient trouble-  
free operation of the boiler. Mount the thermostat to an  
inside wall at a height approximately five feet above  
the floor. Avoid placing the thermostat in areas that will  
not provide an accurate measurement of the room  
temperature. Locating the thermostat behind a door, in  
an alcove, close to a source of thermal radiation or in a  
drafty area will cause poor or sporadic heating.  
Whenever the gas supply piping is pressure tested the  
boiler gas controls must be protected. If the test  
pressure is equal to, or less than 1/2 psig, 3.5 kPa,  
isolate the boiler by closing it’s manual shut off valve,  
see Figure 11. If the test pressure is greater than, or  
equal to 1/2 psig, 3.5 kPa, disconnect the boiler and  
it’s individual shut-off valve.  
Vent Damper  
The vent damper supplied with the boiler has been  
wired with a 6 pin molex connector that will plug directly  
into the boiler’s wiring harness.  
Page 13  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Figure 12: Fenwal/Honeywell Direct Ignition  
Page 14  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Figure 13: Honeywell Intermittent Pilot Ignition  
Page 15  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Figure 14: Honeywell Continuous Pilot Ignition  
Page 16  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Figure 15: Multi Zone Diagram  
Figure 16: Multi Zone Diagram  
T87F ZONE 1  
T87F ZONE 2  
T87F ZONE 3  
TO ADDITIONAL  
R845A RELAYS  
FOR OTHER ZONES  
LINE VOLTAGE  
LOW VOLTAGE  
V8043F  
END SWITCH  
V8043F  
END SWITCH  
V8043F  
END SWITCH  
R8285D  
1
R845A RELAY  
ZONE 1  
TH-TR  
TH  
TR  
TH-TR  
TH  
TR  
TH-TR  
TH  
TR  
6
5
4
3
1
2
3
W
G
Y
R8285D  
1
R
C
LINE VOLTAGE  
LOW VOLTAGE  
3
2
W
G
Y
W
L
BK  
(HOT)  
LOW  
R
C
CIRCULATOR  
ZONE 1  
VOLTAGE  
THERMOSTAT  
L1  
1
L2  
1
L
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
POWER  
SUPPLY  
1
POWER  
1
2
SUPPLY  
W
BK  
CIRCULATOR  
L1  
L2  
POWER  
SUPPLY  
1
1
2
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
SIZE ADDITIONAL TRANSFORMER 8VA PER EACH V8043F ZONE VALVE THAT IS REQUIRED.  
Figure 17: Multi Zone Diagram  
LINE VOLTAGE  
LOW VOLTAGE  
ZONE 1  
THERMOSTAT  
ZONE 2  
THERMOSTAT  
ZONE 3  
THERMOSTAT  
R8285D  
1
3
R882C  
N.O.  
N.C.  
COM.  
R882C  
N.O.  
N.C.  
COM.  
R882C  
N.O.  
N.C.  
COM.  
24  
VAC  
W
G
Y
N.O.  
N.C.  
COM.  
N.O.  
N.C.  
COM.  
N.O.  
N.C.  
COM.  
2
1
C
R
2
W
B
W
B
W
B
W
BK  
W
BK  
L1  
CIRCULATOR  
ZONE 1  
CIRCULATOR  
ZONE 2  
CIRCULATOR  
ZONE 3  
L2  
1
L1  
POWER  
SUPPLY  
1
1
2
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
L2  
POWER  
SUPPLY  
SIZE ADDITIONAL TRANSFORMER 15VA PER EACH R882C ZONE RELAY THAT IS REQUIRED.  
Page 17  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Never attempt to bypass the flame roll-out safety  
shutoff switch for the purpose of operating the  
boiler!  
BOILER SET UP  
NOTE: Before starting the boiler, turn off the  
electrical supply going to it. Make sure that gas is  
available at the combination control inlet. Open the  
valves in the return and supply piping. Failure to  
take these precautions will prevent the boiler from  
operating properly.  
The boiler should be inspected and serviced before  
each heating season by a qualified service agency. The  
boiler flue passages, venting system, ignition  
components and the burners should be cleaned and  
examined for deterioration due to corrosion. All  
operational characteristics of the boiler such as  
combustion products, the ignition safety shutoff devices  
and proper control function must be thoroughly checked  
out.  
Fill the boiler and all of the radiation with water. Make  
sure that the system is completely purged of air.  
Review these instructions and make sure that the boiler  
installation complies with ALL of the stated instruction up  
to this point.  
During the heating season, the owner should check the  
boiler and the area around it at least once a month.  
Clear away all objects on or near the boiler. Ensure that  
there is no discoloration of adjacent combustible  
materials due to heat. If there is, IMMEDIATELY call the  
installer or a qualified service agency.  
Flame Roll-out Safety Shutoff System  
The GB100W gas boiler is fitted with a flame roll-out  
switch that detects the presence of hot flue gases in the  
control compartment. If something prevents the  
combustion products from property passing through the  
boiler, the roll-out switch will shut the boiler off. If the  
flame roll-out safety system is activated, contact  
qualified service agency to correct the problem and  
reset the flame roll-out safety switch. Do not attempt to  
start the boiler until problem has been corrected and the  
switch has been reset.  
Page 18  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
FORYOUR SAFETY READ BEFORE OPERATING  
WARNING  
If you do not follow these instructions exactly, a fire or explosion may result  
causing property damage, personal injury or loss of life.  
• Immediately call your gas supplier from a neighbor’s  
A. 1. If this appliance is equipped with a pilot that must  
phone. Follow the gas supplier’s instructions.  
• If you cannot reach your gas supplier, call the fire  
department.  
be lit by hand, follow lighting instructions exactly  
when lighting the pilot.  
2. If this appliance is equipped with an ignition  
device that automatically lights the pilot or burner,  
follow operating instruction, do not try to light the  
pilot or burner by hand.  
C. Use only your hand to push in or turn the gas control  
knob. Never use tools. If the knob will not push in or  
turn by hand, don’t try to repair it, call a qualified service  
technician. Force or attempted repair may result in a fire  
or explosion.  
B. BEFORE LIGHTING smell all around the  
appliance area for gas. Be sure to smell next to the  
floor because some gas is heavier than air and will  
settle on the floor.  
D. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician to  
inspect the appliance and to replace any part of the  
control system and any gas control which has been  
under water.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electric switch; do not use any  
phone in your building.  
LIGHTING INSTRUCTIONS  
Continuous Pilot-Honeywell VR8200A and VR8300A (Natural or Propane), VRF8200P  
and VR8300C (Propane Only)  
1. STOP! Read the safety information above.  
2. Set the thermostat to lowest setting.  
3. Turn off all electric power to the appliance.  
4. Remove control access panel.  
button. The button should pop back and the pilot  
remain lit. If it goes out repeat steps 5 - 10.  
*If the button does not pop up when released, stop  
and immediately call your service technician or gas  
supplier.  
5. Turn the gas control knob clockwise  
to “OFF”.  
6. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you smell  
gas, STOP! Follow “B” in the safety information  
above. If you don’t smell gas, go to the next step.  
7. Remove the pilot access panel located just above  
the burner tubes.  
*If the pilot will not stay lit after several tries, turn the  
gas control knob to “OFF” and call your service  
technician or gas supplier.  
11. Replace the pilot access panel.  
12. Turn the gas control knob counterclock-wise  
to “ON”.  
13. Replace control access panel.  
8. The pilot’s located behind this panel.  
9. Turn the knob on the gas control counterclock-wise  
to “PILOT”.  
14. Turn on all electric power to the appliance.  
15. Set thermostat to desired setting.  
10.Push and hold down the red button next to the  
control knob. Light the pilot with a match and wait  
approximately one (1) minute before releasing the  
16. If the appliance will not operate, follow the  
instructions “TO TURN OFF GAS TO APPLIANCE”  
and call your service technician or gas supplier.  
1"  
±1/16  
PRESSURE REGULATOR  
ADJUSTMENT (UNDER  
CAP SCREW)  
OUTLET PRESS. TAP  
5/16  
±1/16  
3/8" - 1/2"  
FLAME  
ON PROBE  
GAS INLET  
GAS OUTLET  
ON  
BURNER  
TUBE  
PILOT  
OFF  
PILOT  
BRACKET  
RED RESET BUTTON  
GAS CONTROL KNOB  
CONTINUOUS PILOT  
Page 19  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
POUR VOTRE SÉCURITÉ LISEZ AVANT D'ALLUMER  
AVERTISSEMENT. Quiconque ne respecte pas à la lettre les instructions dans la présente notice risque  
de déclencher un incendie ou une explosion entraînant des dommages, des blessures ou la mort.  
• Si vous ne pouvez rejoindre le fournisseur, appelez le  
service des incendies.  
A. Cet appareil est muni d'une veilleuse qui doit être  
allumée manuellement. Respectez les instructions  
cidessois à la lettre.  
C. Ne poussez ou tournez la manette d'admission du  
gaz qu'à la main; ne jamzis utiliser d'outil. Si la manette  
reste coincée, ne tentez pas de la réparer; appelez un  
technicien qualifié. Le fait de forcer la manette ou de la  
réparer peut délencher une explosion ou un incendie.  
B. Avant d'allumer la veilleuse, reniflez tout autour de  
l'appareil pour déceler une odeur de gaz. Reniflez près  
du plancher, car certains gaz sont plus lourds que l'air et  
peuvent s'accumuler au niveau du sol.  
D. N'utilisez pas cet appareil s'il été plongé dans l'eau,  
même partiellement. Faites inspecter l'appareil par un  
technicien qualifié et remplacez toute partie du systeme  
de contrôle et toute commende qui ont été plongés dans  
l'eau.  
QUE PAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:  
• Ne pas tenter d'allumer d'appareil.  
• Netouchezàaucuninterrupteur;nepasvousservirdes  
téléphones se trouvant dans le bâtiment.  
• Appelezimmédiatenemtvotrefournisseurdegasdepuis  
un voisin. Suivez les instructions du fournisseur.  
INSTRUCTIONS D'ALLUMAGE  
1. ARRÊTEZ! Lisez les instructions de sécurité sur la  
portion supérieure de cette étiquette.  
8. Identifiez la veilleuse,  
suivez le tube métal-  
2. Réglez le thermostat à la température la plus basse.  
3. Coupez l'alimentation électrique de l'appareil.  
4. Enlever le panneau de porte du réchauffer.  
5. Poussez légèrement la manette de commande de  
lique de la manette de  
commade de gaz. La  
veilleuse se trouve  
entrelesdeuxtubesde  
gaz et tournez-la vers la droite jusqu'  
position “OFF”.  
à la  
brûleurs derrière la  
trappe d'observation.  
9. Tournez la manette de commande de gaz dans le  
sens contraire des aiguilles d' une montre jusqu' à la  
position (Veilleuse).  
10. Enfoncez la manette de commande et maintenez-la.  
Allumez immediatement la veilleuse avec des  
allumettes. Continuez à appuyer sur la manette  
pendant environ 1 minute après l' allumage de la  
veilleuse. Relâcher la veilleuse et elle reprendra sa  
position initiale. La veilleuse doit rester allumée. Si  
elle s' éteint, repettez les étapes de 4 à 9.  
Si la manette ne se soulève pas d' elle- même  
lorsqu' on la relâche, arrêtez et appelez immédi-  
atement le technicien ou le fournisseur de gaz.  
Si la veilleuse ne reste pas allumée après plusieurs  
tenatives, tournez la manette de commande de gaz  
6. Attendre cinq (5) minutes pour laisser échapper tout  
le gaz. Reniflez tout autour de l'appareil, y compris  
pres du plancher, pour déceler une 'odeur de gaz.  
Si vous sentez une odeur de gas, ARRÊTEZ! Pas-  
sez à l'étape “B” des instructions de sécurité sur la  
portion sepérieure (à gauche) de cette etiquette. S'il  
n'y a pas d'odeur de gaz, passer à l'étape suivante.  
7. Ouvrez la trappe d'observation de la chambre  
de combustion située au-dessus des brûleurs  
principaux.  
sur la position "OFF" et appelez le technicien  
ou le fournisseur.  
11. Refermez la trappe de la chambre d' observation.  
12. Déplacez la manette de commande de gaz vers la  
gauche jusqu'  
à la position "ON"  
13. Rebranchez l' alimentation électrique de l'appareil.  
14. Réglez le thermostat à la température désirée.  
COMMENT COUPER L'ADMISSION DE GAZ DE L'APPAREIL  
1. Mette le thermostat à la température la plus basse.  
2. Siunentretiendoitêtreeffectué,coupezl'alimentation  
électrique de l'appareil.  
4. Tourner le bouton de commande de gaz vers  
droite, enpositiond'arrêtOFF”. Nepasforcer!  
5. Replacer le panneau de parte du réchauffer.  
3. Lever le panneau de parte du réchauffer.  
Page 20  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
OPERATING INSTRUCTIONS  
Intermittent Pilot - WHITE RODGERS 36C & 36E and Honeywell VR8304A (Natural or Propane),  
VR8304P (Propane Only)  
Direct Ignition - White Rodgers 36C & 36E and Honeywell VR8305A (Natural or Propane),  
VR8305P (Propane Only)  
1. STOP! Read the safety information above.  
2. Set the thermostat to lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition device  
which automatically lights the pilot or burner. Do not  
try to light the pilot or burner by hand!  
smell for gas, including near the floor. If you smell  
gas, STOP! Follow “B” in the safety information  
above. If you don’t smell gas, go to the next step.  
8. Turn the gas control knob counterclock-wise  
to “ON”.  
9. Replace control access panel.  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
5. Remove control access panel.  
6. Turn the gas control knob clockwise  
to the  
full “OFF” position, on W-R 36C/E push the knob  
before turning.  
7. Wait five (5) minutes to clear out any gas. Then  
12. If the appliance will not operate, follow the  
instructions “TO TURN OFF GAS TO APPLIANCE”  
and call your service technician or gas supplier.  
PRESSURE REGULATOR  
ADJUSTMENT (UNDER  
CAP SCREW)  
OUTLET PRESS. TAP  
PRESSURE REGULATOR  
ADJUSTMENT (UNDER  
CAP SCREW)  
OUTLET PRESS. TAP  
GROUND  
TERMINALS (2)  
GROUND  
TERMINALS (2)  
GAS INLET  
GAS OUTLET  
GAS INLET  
GAS OUTLET  
ON  
ON  
OFF  
OFF  
GAS CONTROL KNOB  
GAS CONTROL KNOB  
HONEYWELL VR8304A/P  
HONEYWELL VR8305M/P  
PRESS. REGULATOR  
PRESS. REGULATOR  
GAS INLET  
GAS OUTLET  
OF  
F
GAS INLET  
GAS OUTLET  
NO  
ON  
OFF  
GAS CONTROL KNOB  
SHOWN IN "ON" POSITION  
PILOT FLOW ADJ. SCR.  
GAS CONTROL KNOB  
SHOWN IN "OFF" POSITION  
PILOT FLOW ADJ. SCR.  
WHITE RODGERS 36E  
WHITE RODGERS 36C  
TO TURN OFF GAS TO APPLIANCE  
4. Turn the gas control knob clockwise  
to  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service  
is to be performed.  
“OFF”. On W-R controls push the knob in before  
turning, don’t force it.  
5. Replace control access panel.  
3. Remove control access panel.  
Page 21  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
POUR VOTRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE  
AVERTISSEMENT. Quinconque ne respecte pas à la lettre les instructions dans la présente  
notice risque de déclencher un incendie ou une explosion entraînant des dommages, des  
blessures ou la mort.  
• Appelez immédiatement votre fournisseur de gaz  
depuis un voisin. Suives les instructions du  
fournisseur.  
A. 1. Cet appareil est muni d'ue veilleuse qui doit être  
allumée manuellement. Respectez lis instructions  
cidessous à la lettre.  
• Si vous ne pouvez rejoindre le fournisseur, appelez  
le service de incendies.  
2. Cet appareil ne comporte pas de veilleuse. Il  
est muni d'un dispositif d'allumage qui allume  
automatique la brûleur. Ne tentez pas d'allumer  
la brûleur manuellement.  
C. Ne poussez ou tournez la maneette d'admission  
du gaz qu'à la main; ne jamais utiliser d'outil. Si  
la manette reste coincée; ne pas tenter de la  
réparer; appelez un technicien qualifié. Le fait de  
forcer la manette ou de la réparer peut déclencher  
une explosion ou un incendie.  
B. AVANT DE FAIRE FONCTIONNER, reniflez tout  
autour de l'appareil pour déceler une odeur de  
gaz. Reniflez près du plancher, car certains gaz  
sont plus lourds que l'air et peuvent s'accumuler  
au niveau du sol.  
D. N'utilisez pas cet appareil s'il a été plongé dans  
l'eau, même partiellement. Faites inspecter  
l'appareil par un tecnicien qualifié et remplacez  
toute partie du système de contrôle et toute  
commande qui ont été plongés dans l'eau.  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ  
• Ne pas tenter d'allumer d'appareil.  
• Ne touchez à aucun interrupteur; ne pas vous servir  
des téléphones se trouvant dans le bâtiment.  
INSTRUCTIONS DE MISE EN MARCHE  
1. ARRÊTEZ! Lisez les instructions de sécurité sur  
la portion supérieure de cette étiquette.  
7. Attendre cinq (5) minutes pour laisser échapper  
tout le gaz. Reniflez tout autour de l'appareil, y  
compris près du plancher, pour déceler une odeur  
de gaz. Si vous sentez une odeur de gaz,  
ARRÊTEZ! Passez à l'étape B des instructions de  
sécurité sur la portion supérieure de cette  
étiquette. S'il n'y a pas d'odeur de gaz, passez à  
l'étape suivante.  
2. Mette le thermostat à la température la plus  
basse.  
3. Coupez l'alimentation électrique de l'appareil.  
4. Cet appareil est équipé d'un dispositif d'allumage  
automatique la brûleur.  
8. Tourner le bouton de commande de gaz vers la  
gauche  
, en position de marche “ON”.  
9. Replacer le panneau de parte du réchauffer.  
10. Rétablìr toute l'alimentation électrique de la  
chaudiere.  
11. Mette le thermostat thermostat sur le régleage  
désiré.  
5. Enlever le panneau de parte du réchauffer.  
12. Si l'appareil ne fonctionné pas, voir les instructions  
de “COÙPURE DE L'ARRIVE DE GAZ A LA  
CHAUDIERE” et appeler un technicien reparateur  
ou le fournisseur de gaz.  
6. Tourner le bouton de commande de gaz vers la  
droite  
, en position d'arrêt “OFF”. Ne pas  
forcer!  
COÙPURE DE L'ARRIVE DE GAZ A LA CHAUDIERE  
1. Mette le thermostat à la température la plus basse.  
4. Tourner le bouton de commande de gaz vers la  
droite,  
forcer!  
en position d'arrêt "OFF". Ne pas  
2. Si un entretien doit être effectué, coupez  
l'alimentation électrique de l'appareil.  
5. Replacer le panneau de parte du réchauffer.  
3. Lever le panneau de parte du réchauffer.  
Page 22  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
C. Raise the thermostat at least 5 degrees above the  
room temperature. The burners should light.  
BOILER OPERATION  
WARNING: Before attempting to operate this  
boiler you !MUST! read and fully understand the  
lighting instructions in the “For Your Safety  
Read Before Operating” section of this manual.  
If you attempt to operate this boiler without a full  
understanding of it’s ignition system a fire or  
explosion may result causing extensive property  
damage, severe personal injury or death!  
D. A boiler designed for use with natural gas should  
have a manifold gas pressure of 3.5" WC. On an LP  
boiler, the manifold pressure should be 10" WC. To  
adjust the manifold gas pressure, remove the gas  
valve pressure regulator cap and turn the regulator  
screw to obtain the correct pressure.  
E. Test the ignition safety shutoff device, turn the gas  
control knob on the gas valve to “PILOT”. The burners  
should go out. Extinguish the pilot and wait 3 minutes.  
Turn the gas valve control knob to “ON”. There should  
be NO gas flow to the main burners with the pilot out! If  
gas flow is detected, immediately turn the gas valve  
control knob to “OFF” and have the problem corrected.  
WARNING: Before proceeding read and fully  
understand the instructions contained in this  
manual. Do not attempt to operate this boiler if it  
has not been installed in accordance with the  
guidelines set forth in this manual.  
Shouldoverheatingoccurorthegassupplyfailtoshutoff,  
do not turn off or disconnect the electrical supply to the  
pump. Instead, shut off the gas supply at a location  
external to the appliance.  
Intermittent & Direct Ignition Systems  
A. Connect a manometer having a minimum capacity  
of 10 in, 254 mm, WC to the outlet pressure port of the  
gas valve. Make sure that the gas supply piping has  
been purged of air and that all gas joints up to the gas  
valve have been thoroughly checked for leaks. Wait at  
least five minutes for the gas to dissipate before turning  
on the electrical power.  
En cas de surchauffe ou si l'alimentation de gaz ne peut  
être coupée, ne pas couper ni débrancher l'alimentation  
électrique de la ponpe. Fermer plutôt le robinet  
d'admission de gaz à l'extérieur de l'appareil..  
B. Read, understand and follow the lighting  
instructions contained in this manual that are applicable  
to the type of ignition system installed on the boiler.  
Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician to  
inspect the appliance and to replace any part of the  
control system and any gas control that has been under  
water.  
C. Raise the thermostat at least 5 degrees above the  
room temperature. For models equipped with an  
intermittent pilot the pilot should light and then the  
burners. If a direct ignition system is employed, a delay  
of approximately 20 seconds will take place as the  
silicon carbide ignitor heats up. Once the ignitor is hot,  
the main gas valve will open and the burners should  
light. If the burners fail to light the system will make  
two more ignition attempts. If the burners light, but go  
out within 4 seconds, the system will make three more  
ignition attempts. If the burners have not lit after the  
last ignition try, the gas valve will close and the system  
will go into lock out. DO NOT attempt to reset the  
system until the ignition system has been inspected  
and the problem resolved. After 5 minutes has passed  
since the last ignition attempt, reset the system by  
turning the thermostat to it’s lowest setting and then  
back to where it was. Momentarily interrupting the  
electrical power to the boiler will also reset the system.  
N'utilisez pas cet appareil s'il a été plongé dans l'eau,  
même partiellement. Faites inspecter l'appareil par un  
tecnicienqualifiéetremplaceztoutepartiedusystèmede  
contrôle et toute commande qui ont été plongés dans  
l'eau.  
Continuous Pilot System  
A. Connect a manometer having a minimum  
capacity of 10" WC to the outlet pressure port of the gas  
valve. Make sure that the gas supply piping has been  
purged of air and that all gas joints up to the gas valve  
have been thoroughly checked for leaks. Wait at least  
five minutes for the gas to dissipate before turning on the  
electrical power.  
B. Read, understand and follow the lighting  
instructions contained in this manual that are applicable  
to the type of ignition system installed on the boiler.  
D. With the burners in operation, close the manual  
shutoff valve in the gas supply line. As soon as the  
burner flames go out, open the manual shutoff valve. A  
normal ignition sequence should take place.  
CAUTION: To prevent being burned, take care not to  
touch any hot metal parts. Stand clear of the boiler  
during ignition to prevent being burned in the case  
of flashback.  
Page 23  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Gas Pressure Adjustment  
E. With the burners in operation, interrupt the power  
to the control circuit by lowering and raising the  
thermostat. A normal ignition sequence should follow.  
NATURAL GAS: Optimum results are obtained when  
the boiler is operated at its full input rating, with 3.5 in,  
89 mm, WC of manifold pressure. The manifold  
pressure should not be more that 5% off this value. The  
gas valve pressure regulator has been preset at the  
factory. If adjustment is necessary the following steps  
must be followed:  
F. To test the ignition safety shutoff device, close the  
manual shutoff valve in the gas supply line. Within 6  
seconds of main burner flame extinction, the main gas  
valve solenoid should close with an audible noise.  
1. Attach a manometer to the pressure tap on the gas  
valve body.  
2. Remove the regulator adjustment screw cap from  
the gas valve body.  
3. Rotate the regulator adjustment screw clockwise to  
increase the manifold pressure, counterclockwise to  
decrease it.  
4. Replace the regulator adjustment screw cap and  
pressure tap plug.  
On intermittent pilot systems a ticking noise should be  
heard while the ignition module tries to relight the pilot.  
After 1 minute the module should lockout and the try  
for ignition end.  
If a direct ignition system is employed, the ignitor should  
glow and an attempt at ignition take place. After  
unsuccessfully attempting to light the main burners the  
ignition module should lock out.  
CAUTION: Never force the regulator adjustment  
screw beyond the stop limits or damage to the gas  
valve will occur!  
Open the manual shutoff valve in the gas supply line.  
Reset the ignition control system by interrupting, then  
restoring electrical power to the boiler. A normal  
ignition sequence should take place.  
PROPANE GAS: A manifold pressure of 10.0 in,  
254 mm, WC must be maintained for proper operation of  
the boiler. If the manifold pressure is off by more than  
5% adjust it according to steps 1 through 4 above.  
BOILER CHECKING & ADJUSTMENT  
Pilot Adjustment  
Input Rate  
The pilot burner flame should envelope 3/8 in, 9.5 mm  
to 1/2 in, 13 mm, of the thermocouple tip or flame  
sensing probe, depending on the pilot type. If the pilot  
flame is out of adjustment, remove the cap next to the  
pilot tube fitting on the gas valve. Turn the pilot  
adjustment screw clockwise to decrease the flame,  
counterclockwise to increase it. Figure 18 depicts a  
constant pilot, but the adjustment dimensions for an  
intermittent pilot would be the same.  
Gas appliances are rated based on sea level operation  
with no adjustment required at elevations up to 2000  
feet. At elevations above 2000 ft, 610 m, input ratings  
should be reduced by 4% for each 1000 ft, 305 m above  
sea level. Check the input rate as follows:  
1. Turn off all other gas appliances that use the same  
gas meter as the boiler.  
2. Call your gas supplier and ask for the heating  
value of the gas.  
3. Start the boiler and let it run for 15 minutes.  
4. Using the gas meter and a stop watch, clock the  
time that it takes to burn 1 cubic foot of gas. To  
increase the accuracy of the time, clock the time  
that it takes to burn 10 cubic feet of gas and divide  
the time by 10.  
Figure 18: Pilot Location  
1"  
±1/16  
5/16  
±1/16  
3/8" - 1/2"  
FLAME  
ON PROBE  
5. Insert the heating value and the time, in seconds,  
into the formula below.  
RATE in = HEATING VALUE (BTU/FT3) (3600S/HR)  
Time (s/ft3)  
BURNER  
TUBE  
PILOT  
BRACKET  
EXAMPLE: If: heating value = 1000 BTU/ft3  
time/ft3 = 18 s/ft3  
RATE in = (1000 BTU/ft3) (3600 s/hr)  
18 s/ft3  
RATE in = 200,000 BTU/hr  
Page 24  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
If the computed rate deviates by more than 5% from the  
rated input value of the unit adjust the gas valve  
Burner Removal  
1. Close the manual shutoff valve in the gas supply  
line and turn off electrical power to the boiler.  
2. Disconnect the boiler ground joint union, see  
Figure 12.  
pressure accordingly. DO NOT adjust the manifold  
pressure by more than 5%. If a proper rate cannot be  
maintained without adjusting the manifold pressure  
beyond the 5% limit, the main burner orifices must be  
replaced. If the input rate is too low, go to the next lager  
size orifices. If the input rate is too high, go to the next  
smaller size.  
3. Remove the front access panel.  
4. Where applicable, disconnect the wires, pilot tube  
and thermocouple from the gas valve.  
5. Remove the two nuts that retain the manifold  
assembly and remove the assembly.  
6. The burner support panel has two jacket screws in  
it. Remove the screws to free the support panel and  
burners.  
CAUTION: Never increase the input to the boiler  
above that for which it is rated. Doing so can cause  
premature failure of the boiler!  
WARNING: Yellow, floating flames indicate a  
lack of combustion air. Do not operate the boiler  
until the problem is solved or severe personal  
injury or death may occur!  
Burner Installation  
1. DO NOT install damaged or badly corroded  
burners - replace them.  
2. Insert the crimped end of each burner into the  
burner base rear panel slots. Carefully slide the  
burner support panel over the burner tubes and  
studs.  
Low Water Cutoff  
If the boiler is equipped with a low water cutoff device  
make sure that the main burners will NOT light when the  
boiler has no water in it. To check, turn the boiler off,  
close the valves in the water supply and return lines and  
drain the boiler. If the boiler’s main burners light shut the  
boiler off immediately and correct the problem.  
3. Work the manifold assembly into position and  
reattach it using the two nuts.  
4. Replace the two jacket screws and reconnect all  
wires, tubing and anything else that was  
disconnected during the burner removal operation.  
5. Complete the reassembly and follow the  
instructions in the BOILER OPERATION section  
of this manual.  
Thermostat Adjustment  
For a thermostat that employs an adjustable heat  
anticipator, adjust the anticipator to match the current  
measured in the thermostat circuit. An increased  
anticipator setting may be necessary if the unit cycles  
frequently. If the room temperature over-shoots the  
thermostat setting, reduce the anticipator setting.  
Heat Exchanger Cleaning  
The burners should be removed to protect them from  
falling rust and scale. Follow the Burner Removal  
instructions in this manual.  
1. Disconnect the vent pipe and the stack damper.  
2. Remove the front access and top panels.  
3. Disconnect the spill switch wires.  
BOILER MAINTENANCE  
WARNING: The ceramic combustion chamber in  
the burner box and its gasket contain crystalline  
silica. Wear a tightly fitted dust mask when  
servicingtheburnerandgentlyhandletheburner  
and its gasket to prevent inhalation of airborne  
fibers.Crystallinesilicafibershavebeenidentified  
as carcinogenic, or possibly carcinogenic when  
inhaled.  
4. Remove the two screws from the flue collector  
retaining clips. Separate the flue collector from the  
heat exchanger.  
5. Remove the flue collector.  
6. Remove as much of the old flue collector sealant as  
possible. Thoroughly clean the flue passages with a  
wire brush.  
7. Vacuum out the burner base and clean and  
inspect all of the components. Replace any  
damaged or badly corroded parts.  
8. Reseal the flue collector using Dow Corning #732 or  
an equivalent sealant. And install the flue collector  
retaining clips and screws.  
CAUTION: Servicing, inspection and adjustment  
must be done by a trained technician in accordance  
with all applicable local and national codes. Verify  
proper operation after servicing. Improper servicing  
or adjustment can damage the boiler!  
WARNING: Failure to properly seal the flue  
collector to the heat exchanger can result in  
leakage of combustion products which can  
result in severe personal injury or death!  
The boiler should be cleaned and inspected once a  
year, before each heating season. Make sure that the  
burners and ignition components are free from dust,  
soot, dirt, corrosion or other deposits that would impair  
the boiler’s performance. Refer to Replacement Parts  
page for component identification.  
9. Replace the top panel and reconnect the spill switch  
wires and vent system.  
10. Follow the Burner Installation procedure  
outline in this section.  
Page 25  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Vent System  
INSTRUCTIONS TO THE INSTALLER  
This copy of the INSTALLATION AND OPERATING  
INSTRUCTIONS should be given to the owner of this  
boiler and kept on file.  
Thoroughly inspect the vent system for any signs of  
blockage, corrosion or leakage. Immediately replace any  
unsound vent system piping.  
WARNING: Failure to properly inspect the vent  
system on a regular basis may leave problems  
undetected that can result in excessive levels  
of carbon monoxide which can cause severe  
personal injury or death!  
The INSTALLER must make sure that the owner or  
operator has a basic understanding of the following:  
1. The lighting instructions, the type of ignition system  
installed and how it operates.  
2. What the labels on the boiler say.  
3. How to start up and shut off the boiler.  
4. How to turn the gas and electrical power on or off.  
5. What to do if the boiler shuts down on ignition  
system lock out.  
6. Where to check the system temperature and  
pressure and what they should be.  
Controls  
Use the BOILER OPERATION and BOILER  
CHECKING AND ADJUSTMENT sections of this  
manual as a reference.  
1. Check the thermostat for proper operation.  
2. If the boiler has been equipped with a low water  
cutoff device, L.W.C.O, ensure that it operates  
properly. A float type L.W.C.O. should be flushed  
out.  
3. The relief valve should vent water when the test  
lever is lifted. It should not weep or discharge water  
at normal system pressure. NEVER try to clean or  
repair the relief valve! If the valve fails to operate  
properly, replace it!  
7. The importance of reading, understanding and  
following these instructions.  
The INSTALLER MUST make sure that the owner  
knows to shut the boiler off and call for service if the  
following conditions occur:  
1. Yellow lazy flames or flames outside the boiler  
acket.  
2. Gas smell or other strange odors.  
4. The aquastat high limit controls the maximum  
water temperature in the boiler. It is adjustable  
from 140°F, 60°C to 240°F, 116°C. If the water  
temperature reaches the set temperature before  
the demand for heat has been met, the aquastat  
high limit should shut the boiler off. The water  
temperature should never exceed the maximum set  
point of 240°F, 60°C. The aquastat high limit  
cannot be repaired. If it fails to function properly  
replace it.  
3. Discoloration of boiler or surrounding materials due  
to overheating.  
4. Water leaking from the heating system piping or  
relief valve.  
5. Flue products leaking from the vent system into the  
living space. Dampness or condensation in the  
building is a good indicator of this condition.  
6. The boiler’s blocked vent shutoff system is actuated.  
7. The boiler’s flame roll-out safety system is actuated.  
8. Control malfunction or sporadic operation.  
Page 26  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
REPLACEMENT PARTS  
GB100 SERIES REPAIR PARTS  
Number of Sections  
Ref #  
Name of Part  
Part No.  
55703  
55704  
55705  
55706  
55707  
55708  
55709  
55710  
55711  
55712  
55701  
55702  
55813  
55814  
55815  
55816  
55817  
55818  
55819  
55820  
55821  
55822  
3
4
5
6
7
8
9
10  
11  
12  
1
Top, Rear, Inner Front and Front Panels  
1
1
1
1
1
1
1
1
1
1
1
1
2
3
4
Left Side Panel  
Right Side Panel  
Floor Pan  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 27  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
Number of Sections  
Ref #  
Name of Part  
Part No.  
3
4
5
6
7
8
9
10  
11  
12  
5
Flue Collector/Drafthood  
55803  
55804  
55805  
55806  
55807  
55808  
55809  
55810  
55811  
55812  
69879  
69880  
69881  
69882  
69883  
69884  
69885  
69886  
69887  
69888  
69445  
60176  
60177  
69786  
69787  
69788  
69789  
69790  
69791  
69792  
69793  
69794  
69795  
50155  
50154  
60567  
60226  
69425  
69426  
69427  
69428  
69429  
61988  
60265  
1
1
1
1
1
1
1
1
1
1
6
Heat Exchanger/Assembled Block  
1
1
1
1
1
1
1
1
1
1
7
8
Burner  
2
2
2
1
3
3
3
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
9
9
9
10  
10  
11  
11  
Burner Orifice (#42, NG)  
Burner Orifice (#54, LP)  
Manifold  
9
1
1
1
1
1
1
1
1
1
1
1
1
1
10  
11  
12  
13  
14  
High Limit (L4080B-1253)  
Control Center (R8285D-1026)  
Spill Switch (262 deg. F) 404257A  
Rollout Switch (350 deg. F) 30T15  
Vent Damper (5")  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Vent Damper (6")  
Vent Damper (7")  
1
1
1
1
Vent Damper (8")  
Vent Damper (9")  
1
1
1
1
1
1
1
1
15  
16  
Pressure Relief Valve (30 psi)  
Temp & Pressure Gauge  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
SPARK IGNITION - HONEYWELL  
Ignition Module (S8600M-1013)  
Pilot-Ignitor Sensor PSE-NA29 NG & LP*  
***For LP also order LP orifice  
17  
18  
51177  
50978  
50998  
50143  
50701  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
19  
Gas Valve (VR8304M-3103) NG & LP**  
***For LP also order LP orifice  
STANDING PILOT - HONEYWELL  
Thermocouple (K16RA)  
20  
51006  
50068  
50069  
50701  
50018  
61015  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Gas Valve (VR8200) NG & LP 3 - 10 Sec.***  
Gas Valve (VR8300) NG & LP 11 & 12 Sec.***  
***For LP also order LP orifice  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
21  
Pilot Burner (Q314A-6961)***  
***For LP also order LP orifice  
HSI - FENWALL IGNITION SYSTEM  
Ignition Module (35-655922-001)  
Ignitor  
20  
21  
22  
50337  
50072  
50010  
50009  
50057  
61239  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Gas Valve (36E01-308) NG  
Gas Valve (36C67-423) NG  
Gas Valve (VR8305M-3506) LP  
Ignitor Bracket  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 28  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
CANADIAN SUPPLEMENT  
DANGER  
Only the boiler may be served by the vent damper. Do not use it to vent an additional appliance; this will  
cause a fire or carbon monoxide poisoning.  
DANGER  
LE VOLET DE VENTILATION DOIT SERVIR SEULE-MENT À LA CHAUDIÈRE. NE PAS L´UTILISER POUR  
VENTILER D´AUTRES APPAREILS; SINON CELA POURRAIT PROVOQUER UN INCENDIE OU CAUSER  
UN EMPOISONNEMENT PAR LE MONOXYDE DE CARBONE.  
METHOD OF INSTALLATION FOR MOTORIZED VENT DAMPER  
MÉTHOSE D´INSTALLATION POUR LE VOLET MOTORISÉ DE VENTILATION  
The damper must be mounted as close as possible to  
the draft hood without modifying the draft hood or  
damper device.  
Le registre doit être installé aussi près que possible du  
coupe-tirage sans qu´une modification de ce coupe-  
tirage ou le registre ne soit nécessaire.  
Attach the lower portion of the vent damper to the draft  
hood with 1/2 in, 13 mm or shorter screws or pop rivets.  
Attacher la partie inférieure du volet de ventilation au  
coupe-tirage à l´aide de vis de 13 mm ou plus courtes  
ou des rivets aveugles.  
Do not install within 6 in, 152 mm, of combustible  
materials. Make sure the motor actuator and position  
indicator are readily visible and accessible.  
Ne pas installer le registre à moins de 152mm des  
matériaux de combustion. S´assurer que dispositif de  
commande du moteur est visible et facilement acces-  
sible.  
Plug the Molex connector on the damper harness into  
the mating plug on the harness located inside the control  
compartment.  
Enficher la prise Molex sur le faisceau de fils du volet de  
ventilation dans la prise a l´interieur d´armoire de  
commande.  
Determine the amperage draw of the gas control circuit  
and damper device. Check heat anticipator in comfort  
thermostat to determine that it’s properly adjusted.  
Dèterminer l´appel de courant en ampères du circuit du  
régulateur de gaz et du registre. Vérifier la résistance  
anticipatrice de chaleur du thermostat d´ambiance afin  
de déterminer si elle est correctement réglée.  
To manually open the damper, follow instructions inside  
the damper cover.  
Pour ouvrir manuellement le registre suivre les  
instructions apparaissant à l´intérieur du couverele.  
DAMPER MUST BE IN OPEN POSI-  
TION WHEN APPLIANCE MAIN  
BURNERS ARE OPERATING.  
LE REGISTRE DOIT ÊTRE EN  
POSITION OUVERTE LORSQUE  
LE BRULEÛR PRINCIPAL EST EN  
MARCHE.  
WIRE HARNESS FOR  
VENT DAMPER  
FAISCEAU DE FILIS DU  
VOLET DE VENTILATION  
POSITION INDICATOR  
DISPOSITIF DE COMMANDE  
CLOSED  
CLOS  
OPEN  
OUVERTE  
FLOW DIRECTION  
SENS DE DEBIT  
CONNECT WIRE HARNESS  
BRANCHER LE FAISCEAU DU FILIS  
Page 29  
LIMITED LIFETIME WARRANTY  
FOR RESIDENTIAL WATER BOILERS  
This warranty statement is effective for all units manufactured after December 15, 1992 and supersedes all other warranties,  
including those contained in other documents which might be included with this merchandise. This warranty applies only to the  
original homeowner at the original place of installation.  
First Through Tenth Year  
Westcast, Inc. warrants that the cast iron sections of its residential water boiler for Smith Cast Iron Boilers were free of defects in  
material and workmanship when shipped, and will remain free of defects under normal usage from the date of original installation,  
for a period of ten years. In the event that the cast iron section is found to be defective in material or workmanship during this  
period, Westcast, Inc. will repair or replace, at its option, the defective section.  
Eleventh Year and Above  
Westcast, Inc. warrants that the cast iron sections of its residential water boilers will remain free of defects in material and  
workmanship under normal usage for the lifetime of the original owner at the original place of installation. Should any sections be  
found to be defective, Westcast, Inc. will repair or replace, at its option, the original cast iron sections upon the payment of a  
proportionate charge based on the time the defective section was in service. The proportionate charge will be equal to the  
appropriate percentage of the retail price of the section at the time the warranty claim is made, determined as follows:  
Year  
11th  
5
12th  
10  
13th  
15  
14th  
20  
15th  
25  
16th  
30  
17th  
35  
18th  
40  
19th  
45  
20th  
50  
21st 23nd 24th 25th & above  
55 60 65 75  
% of  
Retail Price  
Procedure for Obtaining Warranty Service  
The homeowner should perform the following in order to insure prompt warranty service:  
1. Notify the installer, who in turn should notify the distributor, promptly upon discovery of a condition believed to be caused by a  
defect in manufacture. Failing this, the owner should notify Westcast, Inc., 260 North Elm St., Westfield, MA 01085 in writing,  
giving full particulars in support of the claim.  
2. Make available for inspection to Westcast, Inc. or its representative the parts alleged to be defective, and if requested by  
Westcast, Inc., ship said parts prepaid to Westcast, Inc., 47 Westfield Industrial Park Road, Westfield, MA 01085 for inspection or  
repair.  
3. The homeowner is required to complete and mail the Warranty card attached hereto within ten days after the installation of the  
boiler before coverage under the Warranty commences.  
Exceptions and Exclusions  
1. This Warranty covers cast iron boiler sections only. Other cast iron parts such as but not limited to grates and grate parts are  
specifically not warranted. The burner, jacket, controls and other auxiliary equipment furnished by Westcast, Inc., but purchased  
from others shall be limited to that manufacturer's warranty, if any.  
2. This Warranty does not include expenses for removal or re-installation. The user will be responsible for the cost of replacement of  
the defective part and labor and material necessary to the exchange. Replacement material will be invoiced to the Distributor in  
the usual manner and will be subject to adjustment upon proof of defect.  
3. Nothing herein shall be construed as a guaranty of workmanship of any installer in installing Westcast, Inc. cast iron boilers, or as  
imposing on the Company any liability of any nature for unsatisfactory performance caused by faulty workmanship in installation,  
which liability is expressly disclaimed.  
4. This Warranty will not apply if the boiler is structurally altered; is used or operated at over its rated capacity; or is not maintained in  
accordance with Westcast, Inc.'s recommendations or the accepted good practice of the industry as defined by the Hydronics  
Institute, A.S.M.E. or other accepted authority.  
5. This Warranty will not apply if the boiler has been damaged a result of: fire or other casualties; flooding or exposure to the  
elements; settlement, distortion, collapse or cracking of any foundation area, beams or pipes surrounding the boiler; improper  
or negligent installation, service or operation (including but not limited to the following - operated with insufficient water, allowed  
to freeze; subject to flood conditions; or operated with water conditions and/or fuels or additives which have caused unusual  
deposits or corrosion in or on the cast sections).  
6. This Warranty applies only to boilers installed within the United States and Canada.  
7. In order for this Warranty to be effective:  
A. The boiler must have been properly installed in a single or two-family residential dwelling. Warranty does not apply to boilers  
installed in apartments, commercial or industrial installations.  
B. The boiler must have been assembled in strict accordance with Westcast, Inc. installation instructions furnished with the boiler.  
C. Boiler sections must not have been damaged in handling during shipment or installation. The determination of damage in  
handling or installation is a considered judgement of Westcast, Inc. and decision shall be final.  
D. The boiler must have been serviced annually by a licensed contractor and proof of such service must be provided with warranty  
claim. This service must include but is not limited to fireside cleaning and proper burner adjustment with combustion testing.  
8. In no case shall Westcast, Inc.'s liability exceed the original selling price of the product found to be defective.  
9. THIS WARRANTY IS IN LIEU OF ALL EXPRESS WARRANTIES OF ANY KIND. THE REMEDIES UNDER THIS WARRANTY  
ARE EXCLUSIVE AND WESTCAST, INC. NEITHER ASSUMES NOR AUTHORIZES ANYONE TO ASSUME FOR IT ANY  
OTHER OBLIGATIONS. IN NO EVENT SHALL WESTCAST, INC. BE LIABLE UNDER THIS WARRANTY OR OTHERWISE  
IN ANY MANNER FOR ANY INCIDENTAL, REMOTE OR CONSEQUENTIAL DAMAGES RESULTING FROM BREACH OF  
THIS WARRANTY OR CONDITION IMPLIED BY LAW OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OF  
MERCHANTABILITY OR FITNESS, FOR A PARTICULAR PURPOSE. SOME STATES DO NOT ALLOW THE EXCLUSION  
OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY  
NOT APPLY TO YOU.  
10. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.  
WARNING  
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon  
monoxide (CO).  
Carbon Monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic.  
If your Smith boiler is not working properly, or is not vented properly, dangerous levels of CO may accumulate.  
CO is lighter than air and thus may travel throughout the building. BRIEF EXPOSURE TO HIGH  
CONCENTRATIONS OF CO, OR PROLONGED EXPOSURE TO LESSER AMOUNTS OF CO MAY RESULT IN  
CARBON MONOXIDE POISONING.  
EXPOSURE CAN BE FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT IN THE  
SUDDEN ONSET OF SYMPTOMS INCLUDING UNCONSCIOUSNESS.  
Symptoms of CO poisoning include the following:  
dizziness  
headaches  
nausea  
vision problems  
loss of muscle control  
weakness  
shortness of breath  
unclear thinking  
unconsciousness  
The symptoms of CO poisoning are often confused with those of influenza, and the highest incidence of poisoning  
occurs at the onset of cold weather or during flu season. A victim may not experience any symptoms, only one  
symptom, or a few symptoms. Suspect the presence of carbon monoxide if symptoms tend to disappear when  
you leave your home.  
The following signs may indicate the presence of carbon monoxide:  
• Hot gases from appliance, venting system, pipes or chimney, escaping into the living space.  
• Flames coming out around the appliance.  
• Yellow colored flames in the appliance.  
• Stale or smelly air.  
• The presence of soot or carbon in or around the appliance.  
• Very high unexplained humidity inside the building.  
If any of the symptoms of CO poisoning occur, or if any of the signs of carbon monoxide are present, VACATE  
THE PREMISES IMMEDIATELY AND CONTACT A QUALIFIED HEATING SERVICE COMPANY OR THE GAS  
COMPANY OR THE FIRE DEPARTMENT.  
To reduce the risk of CO poisoning, have your heating system “tuned up” by a licensed heating contractor or the  
gas company -- preferably before each heating season. Also have the service company check your chimney or  
vent pipes for blockage.  
Your home should also be adequately ventilated, particularly if you have insulated your home.  
ONLY QUALIFIED, LICENSED SERVICE CONTRACTORS  
SHOULD PERFORM WORK ON YOUR SMITH BOILER.  
WARNING  
Install, operate and maintain unit in accordance with manufacturer's instructions to avoid exposure to fuel sub-  
stances or substances from incomplete combustion which can cause death or serious illness. The State of  
California has determined that these substances may cause cancer, birth defects, or other reproductive harm.  
Also, install and service this product to avoid exposure to airborne particles of glasswool fibers and/or ceramic  
fibers known to the State of California to cause cancer through inhalation.  
Page 31  
GB100W NATURAL OR PROPANE BOILER  
INSTALLATION AND OPERATING INSTRUCTIONS  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  

Toshiba IK TF7 User Manual