Sanyo Eco I 09ahx52 User Manual

Print Form  
ECO-i Submittal Data  
09AHX52  
Indoor Unit: 1 Way Air Discharge  
Job Name:  
Location:  
Approval:  
Date:  
Engineer:  
Construction:  
Unit #:  
Drawing #:  
Submitted to:  
Submitted by:  
Reference:  
Parts Warranty: 1 Year  
Built in Drain Pump  
Washable Filter  
Wired, Wireless or Simple Remote Option  
Remote Sensor Option  
Capacities  
Fan  
Cooling: Btu/h  
Heating: Btu/h  
Sensible Heat Ratio  
9,600  
11,000  
0.72  
Quantity/Type:  
Fan Motor Output (W):  
Drive:  
Centrifugal  
60  
Direct  
Airflow Rate (L/M/H):  
212 / 247 / 282  
Cooling Mode Nominal Conditions  
Indoor: °F DB/°F WB  
Outdoor: °F DB  
80/67  
95  
Power Supply  
V/PH/Hz.  
208 / 230 / 1 / 60  
25  
0
Pipe Length (feet):  
Level Difference (feet):  
Minimum circuit Amps (MCA): Amps  
Max. Overcurrent Protection (MOCP):  
Nominal Power Input-Cooling (W):  
Nominal Power Input-Heat (W):  
Running Amps:  
15  
15  
48/50  
Heating Mode Nominal Conditions  
Indoor: °F DB  
Outdoor: °F DB/ °F WB  
Pipe Length (feet):  
44/46  
70  
47/43  
25  
0.26/0.29  
43  
Weight (lbs):  
Level Difference (feet):  
0
Sound Data  
Refrigerant and Piping  
Refrigerant Type:  
Metering Device (Electronic Expansion Valve):  
Liquid Piping (inches):  
Sound Level (H/M/L) 5’ below unit:  
33 / 31 / 29  
410A  
EEV  
1/4  
Coil  
1.14  
3
Gas Piping (inches):  
1/2  
Coil Face Area (sq. ft.):  
Number of Rows:  
Condensate  
Drain Piping (OD) Inches:  
1.25  