261660-YTG-C-0707
®
DESCRIPTION
YORK Sunline Magnum™ units are convertible single pack-
age high efficiency rooftops. All models have independent
dual refrigerant circuits for efficient part load operation.
Although the units are primarily designed for curb mounting
on a roof, they can also be slab-mounted at ground level or
set on steel beams above a finished roof.
TECHNICAL GUIDE
All units include:
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
•
Two-stage cooling provided by dual independent
refrigeration circuits with expansion valves, filter-driers,
high and low pressure/loss of charge switches and
freezestats
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE AIR
CONDITIONERS
•
•
Scroll compressors
Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
DJ 180, 210, 240 & 300
15 & 25 NOMINAL TONS
•
•
Permanently lubricated motors
12.00 EER (15 TONS), 11.70 EER (17.5 TONS),
11.3 EER (20 TONS), 10.5 EER (25 TONS)
Bottom or side air discharge configuration capability
(field convertible)
•
•
Belt Drive Blower Motor with high static drive option
Constant supply air volume (CV) with optional variable
air volume (VAV)
•
•
•
•
•
•
Manufactured under the quality standards of ISO9001
S implicity® Control Board
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and tool free latched doors
Hinged tool free blower, blower motor, filters and electri-
cal panel access
•
•
•
•
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units
WARRANTY
•
•
One-year parts warranty
A Five-year parts warranty on the compressors and
electric heat elements
•
Ten-year parts warranty on the gas-fired heat
exchangers
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
261660-YTG-C-0707
PRODUCT NOMENCLATURE
15-25 Ton Magnum™ Model Number Nomenclature
D J 180 N24 A 2 A AA 1 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
J = 11.0+ EER A/C
SS Drain Pan
CPC Controller, DFS, APS
Nominal Cooling Capacity
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
180 = 15 Ton
210 = 17.5 Ton
240 = 20 Ton
300 = 25 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD (not available with factory installed BAS options)
Variable Air Volume, VFD with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD (BAS ready)
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No field installed
electric heat
Gas Heat Options
Variable Air Volume, VFD and Manual Bypass (BAS ready)
Variable Air Volume, VFD Ready (for customer provided, field installed drive)
Variable Air Volume, VFD Ready with ModLINC (for customer-provided, field-installed drive)
2" Pleated filters
N24 = 240 MBH Output Aluminized Steel
N32 = 320 MBH Output Aluminized Steel
S24 = 240 MBH Output Stainless Steel
S32 = 320 MBH Output Stainless Steel
4" Pleated filters
Electric Heat Options
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Double Wall Construction
E18 = 18 KW
E36 = 36 KW
E54 = 54 KW
E72 = 72 KW
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
Airflow
1 = First Generation
2 = Second Generation
A = Std. Drive
B = Std. Drive/Single Input Econo.
C = Std. Drive/Single Input Econo./Power Exhaust
(Downflow Only)
Additional Options
Hinged Filter Door & Tool Free Access Cabinet
D = Std. Drive/Motorized Damper
Standard Cabinet
E = Std. Drive/Motorized Damper/Barometric Relief
J = Std. Drive/Single Input Econo./Barometric Relief
N = Hi Static Drive
AA = None
BA = Hinged Filter Door & Tool Free Access Panels
BB = Phase Monitor, Hinged Filter Door & Tool Free
Access Panels
AB = Phase Monitor
P = Hi Static Drive/Single Input Econo.
Q = Hi Static Drive/Single Input Econo./Power Exhaust
(Downflow Only)
R = Hi Static Drive/Motorized Damper
K = Hi Static Drive/Motorized Damper/Barometric Relief
S = Hi Static Drive/Single Input Econo./Barometric Relief
AC = Coil Guard
AD = Dirty Filter Switch
BC = Coil Guard, Hinged Filter Door & Tool Free
Access Panels
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
BD = Dirty Filter Switch, Hinged Filter Door &
Tool Free Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Tool Free Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Tool Free Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Tool Free Access Panels
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Tool Free Access Panels
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Unitary Products Group
3
261660-YTG-C-0707
•
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
•
•
Lead-Lag - An integrated Lead-Lag option allows
equal run time hours on all compressors, thereby
extending the life of all compressors. This option is
selectable on the unit control board.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
All models are available with these “factory mounted” outdoor
air damper options:
•
Single enthalpy economizer with or without power
exhaust
•
•
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
•
•
•
BAS-ready economizer with or without power exhaust
Motorized outdoor air damper
Barometric Relief Damper
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement. A variable air vol-
ume (VAV) option using a variable frequency drive is available
for applications requiring a constant supply duct pressure. A
differential pressure transducer is used to monitor supply duct
static pressure and return a speed reference signal to the VFD
to control the output of the indoor blower motor.
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
All compressors include scroll compressors and internal pres-
sure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot
gas bypass option, consisting of an adjustable compressor
discharge bypass valve, is available for low cooling load
applications.
All models are CSA approved.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
Gas Heat Operation - All gas heat units are built with
two heating sections for two equal stages of capacity
control. Each section includes a durable heat exchanger
•
S implicity® Controls - S implicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
4
Unitary Products Group
261660-YTG-C-0707
LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)
FIGURE 1 - UNIT CUTAWAY
with aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
BAS-READY ECONOMIZER - Includes a slide-in / plug-
in damper assembly with fully modulating spring-return
motor actuator with zero to 95-degree rotation capable of
introducing up to 100% outdoor air with nominal 1% leak-
age type dampers.
•
Electric Heat Operation - All electric heat models (fac-
tory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to pro-
vide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
Actuator requires 2-10 VDC input from an external
source, such as a field-installed or factory-installed BAS
controller. BAS-ready actuators have an adjustable auxil-
iary end-switch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, a factory-installed, dry bulb sensor deter-
mines if outdoor air temperature is low enough to provide
free-cooling operation. (Field-installed humidity sensors
for either outdoor air or outdoor & return air streams are
available for single enthalpy and differential enthalpy
configurations, respectively).
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.
•
BAS Controls - York’s Magnum series units offer factory
mounted BAS controls such as York® S implicity® Intelli-
Comfort™, Novar, Honeywell, Johnson, and CPC.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer opera-
tion. BAS-ready economizer actuators have an adjustable
auxiliary end-switch to provide a range of damper positions
available to energize power exhaust. For units with optional
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
Unitary Products Group
5
261660-YTG-C-0707
VAV, power exhaust is energized by means of a binary out-
put signal from the unit's VAV control board.
bracket, the maximum recommended drive dimensions
are as follows:
For 5-hp motor applications ........................13” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.
If the drive will not fit in the allotted space, then it will
have to be mounted elsewhere; either within the building
on a perpendicular wall which is not subjected to exces-
sive temperature, vibration, humidity, dust, corrosive
gas, explosive gas, etc., or within an appropriate enclo-
sure rated for outside installation to safeguard against
moisture, dust and excessive heat.
The power exhaust option can only be used on bot-
tom duct configurations.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
A terminal block located in the control box is provided for
field connection of the VFD controls.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
HOT GAS BYPASS - To allow for low cooling load oper-
ation, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evapo-
rator pressure. HGBP is standard on all units with VAV
and optional with CV units.
•
BAROMETRIC RELIEF DAMPER - This damper option
can be used to relieve internal building air pressure on
units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
•
FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated fil-
ters are offered as a factory installed option.
•
•
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or
you may order the unit with a “non-powered” conve-
nience outlet that can be wired in the field.
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the speed of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
DOUBLE WALL CONSTRUCTION - Optional double
wall construction is available to provide smooth inner
surfaces for easy and effective cleaning to reduce risk of
dirt and bacterial accumulation. Fiberglass insulation is
sandwiched between heavy gauge steel sheets to form a
durable, rigid casing to withstand higher working pres-
sures and impact forces. The heavy-duty construction
provides excellent acoustic and thermal insulation and
eliminates erosion of insulation material and contamina-
tion of the air stream.
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and oper-
ate the motor at full speed, or to power the drive (and not
the motor) for diagnostic purposes.
•
BAS - Building Automation System Controls (avail-
able on two-system cooling product only).
S implicity® INTELLI-Comfort™ CONTROL - The York®
S implicity® INTELLI-Comfort™ control is factory installed.
It includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field installed
dirty filter indicator switch, an air-proving switch, an Out-
side Air Humidity sensor, a Return Air Humidity sensor, an
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-
struction mode operation, 365-day real time clock with 7
day programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved
Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the cus-
tomer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment
which may accommodate other vendor’s drives depend-
ing on their size. In order to utilize the unit’s mounting
through the INTELLI-Comfort™ using CO sensors. It
2
6
Unitary Products Group
261660-YTG-C-0707
uses an inside CO sensor to perform Demand Ventila-
•
•
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
2
tion. It can also use an Outside CO sensor to perform Dif-
2
ferential Demand Ventilation. It uses a Patented Comfort
Ventilation algorithm to provide comfortable ventilation air
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating condi-
tions exist. Humidity in the occupied space or return duct
can be monitored and controlled via humidity sensors and
the on-board connection for hot gas re-heat system. It
uses the INTELLI-Start™ algorithm to maximize energy
savings by recovering the building from the Unoccupied
Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The S implicity® INTELLI-
Comfort™ balances space temperature, ventilation air
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
STAINLESS STEEL DRAIN PAN - An optional rust-
proof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environ-
ments.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
•
•
HIGH STATIC DRIVE - Includes a belt and blower pulley
upgrade to enhance blower performance.
temperature, CO and humidity for ultimate comfort.
2
S implicity® INTELLI-Comfort™ with ModLINC CON-
TROL - The York® S implicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
•
HINGED FILTER DOOR/”TOOL FREE” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
NOTE:Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool free operation.
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR,
FILTER AND ELECTRIC ACCESS PANELS - This
option allows for complete hinged and tool free access to
the unit's blower, blower motor, filters and electrical panel
sections.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
Factory installed smoke detectors in the return air
may be subjected to freezing temperatures during
“off” times due to outside air infiltration. These
smoke detectors have an operation limit of 32°F to
131°F. Smoke detectors installed in areas that
could be outside those limitations will have to be
moved to prevent having false alarms.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
Unitary Products Group
7
261660-YTG-C-0707
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
•
HIGH STATIC DRIVE - A smaller blower pulley and a
shorter belt increase the speed of the supply air blower
for applications with a higher CFM and/or static pressure
requirements.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
•
•
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
•
SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
•
•
WOOD SKID - Allows unit to be handled with 90” forks.
CO SENSOR - Senses CO levels and automatically
2
2
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
8
Unitary Products Group
261660-YTG-C-0707
1
TABLE 1: SOUND POWER RATING
SOUND POWER (db 10-12 Watts)
ESP
IWG
BLOWER
UNIT
SIZE
Octave Band Centerline Frequency (Hz)
dB(A)
@
10Ft.2
CFM
SWL
dB(A)
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
6,000
8,000
1.00
1.00
1.30
1,080
1,120
1160
4.60
6.65
12.5
99
99
89
92
98
82
85
91
84
87
93
77
80
86
72
75
81
67
70
76
89
92
98
56
180
210/240
300
102
108
102
108
59
10,000
65
1.
These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.
2.
At a distance of 10 feet from the blower.
1
TABLE 3: GAS HEAT RATIINGS
TABLE 2: CAPACITY RATINGS - (ARI 360)
EER2
IPLV3
MODEL
MBH INPUT
MBH OUTPUT
MODEL
MBH
300
240
320
240
320
240
320
240
320
DJ180N/S24
DJ180N/S32
COOLING ONLY
DJ180C/E00
DJ210C/E00
DJ240C/E00
DJ300C/E00
400
178
208
230
292
12.0
11.7
11.3
10.5
12.5
12.7
12.0
11.2
300
DJ210N/S24
DJ210N/S32
400
300
DJ240N/S24
DJ240N/S32
COOLING WITH GAS HEAT
DJ180N/S
400
178
208
230
292
12.0
11.7
11.3
10.5
12.5
12.7
12.0
11.2
300
DJ300N/S24
DJ300N/S32
DJ210N/S
400
DJ240N/S
NOTE: All gas units are two-stage heating.
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.
DJ300N/S
COOLING WITH ELECTRIC HEAT
DJ180E18
DJ180E36
DJ180E54
DJ180E72
DJ210E18
DJ210E36
DJ210E54
DJ210E72
DJ240E18
DJ240E36
DJ240E54
DJ240E72
DJ300E18
DJ300E36
DJ300E54
DJ300E72
178
178
176
176
208
208
206
206
230
230
228
228
292
292
290
290
12.0
12.0
11.8
11.8
11.7
11.7
11.5
11.5
11.3
11.3
11.1
11.1
10.5
10.5
10.3
10.3
12.5
12.5
12.2
12.2
12.7
12.7
12.4
12.4
12.0
12.0
11.7
11.7
11.2
11.2
11.0
11.0
For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.
If there are VAV boxes present in the duct sys-
tem, the boxes must be driven to the full-open
position using a customer-supplied power
source to assure adequate airflow across elec-
tric heating elements or gas heat exchanger
tubes.
1.
2.
3.
Certified in accordance with the Unitary Large Equip-
ment certification program which is based on ARI Stan-
dard 340/360.
EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
IPLV = Integrated Part Load Value.
Unitary Products Group
9
261660-YTG-C-0707
TABLE 4: COOLING CAPACITIES FOR DJ180
Temperature of Air on Condenser Coil
Air on Evaporator Coil
85°F
95°F
2
Total Total2
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
80 77 74
Total Total
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
WB
(°F)
1
CFM
Cap.1 Input
(MBH) (kW) 86
Cap. Input
68 (MBH) (kW) 86
83
71
-
83
80
77
74
71
-
68
-
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
206.8 11.94 119.7 106.8 94.0 81.2 68.3
-
196.1 12.98 115.7 102.9 90.1 77.3 64.4
187.4 11.64 148.6 135.7 122.9 110.1 97.2 84.4 71.6 178.1 12.70 144.6 131.8 119.0 106.1 93.3 80.5 67.6
169.3 11.37 169.3 162.1 149.3 136.5 123.6 110.8 98.0 161.7 12.49 161.7 157.0 144.2 131.4 118.5 105.7 92.9
166.8 11.36 166.8 164.1 151.3 138.5 125.6 112.8 100.0 163.4 12.53 163.4 160.3 147.5 134.7 121.8 109.0 96.2
4500
212.8 12.00 132.2 117.0 101.8 86.7 71.5
-
-
201.2 13.06 127.9 112.7 97.6 82.4 67.2
-
-
192.8 11.70 163.5 148.3 133.2 118.0 102.8 87.7 72.5 182.8 12.78 159.2 144.0 128.8 113.7 98.5 83.3 68.2
174.2 11.43 174.2 170.7 161.7 146.6 131.4 116.3 101.1 166.0 12.57 166.0 163.6 156.2 141.0 125.9 110.7 95.5
171.6 11.42 171.6 170.3 163.9 148.8 133.6 118.4 103.3 167.7 12.61 167.7 166.2 159.8 144.6 129.4 114.3 99.1
5250
6000
6600
7200
218.9 12.06 144.7 127.2 109.7 92.2 74.7
-
-
206.4 13.14 140.0 122.5 105.1 87.6 70.1
-
-
198.3 11.76 178.4 160.9 143.4 125.9 108.4 90.9 73.4 187.5 12.86 173.7 156.2 138.7 121.2 103.7 86.2 68.7
179.2 11.49 179.2 179.2 174.2 156.7 139.2 121.7 104.2 170.2 12.65 170.2 170.2 168.2 150.7 133.2 115.7 98.2
176.5 11.48 176.5 176.5 176.5 159.0 141.5 124.0 106.6 172.0 12.69 172.0 172.0 172.0 154.5 137.0 119.5 102.0
224.3 12.14 156.2 136.7 117.2 97.8 78.3
-
-
211.4 13.22 150.4 131.0 111.5 92.0 72.5
-
-
203.2 11.83 192.2 172.8 153.3 133.8 114.3 94.9 75.4 192.0 12.93 185.1 166.7 147.2 127.7 108.2 88.8 69.3
183.6 11.57 183.6 183.6 181.1 161.7 142.2 122.7 103.2 174.3 12.72 174.3 174.3 173.3 153.8 134.4 114.9 95.4
180.9 11.56 180.9 180.9 180.9 161.4 141.9 122.5 103.0 176.2 12.76 176.2 176.2 176.2 156.7 137.2 117.7 98.3
229.7 12.22 167.7 146.3 124.8 103.3 81.9
-
-
216.4 13.30 160.8 139.4 117.9 96.4 75.0
-
-
208.1 11.91 206.1 184.6 163.2 141.7 120.3 98.8 77.3 196.6 13.01 196.6 177.1 155.7 134.2 112.8 91.3 69.8
188.1 11.64 188.1 188.1 188.1 166.6 145.1 123.7 102.2 178.5 12.80 178.5 178.5 178.5 157.0 135.6 114.1 92.6
185.3 11.63 185.3 185.3 185.3 163.8 142.3 120.9 99.4 180.4 12.84 180.4 180.4 180.4 158.9 137.4 116.0 94.5
105°F
115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
184.9 14.46 111.3 98.5 85.6 72.8 60.0
-
-
173.7 15.93 106.8 94.0 81.2 68.3 55.5
-
-
167.9 14.19 140.0 127.2 114.3 101.5 88.7 75.9 63.0 157.7 15.68 135.4 122.6 109.7 96.9 84.1 71.2 58.4
152.9 14.00 152.9 149.0 136.2 123.4 110.5 97.7 84.9 144.1 15.50 144.1 141.0 128.2 115.4 102.5 89.7 76.9
155.3 14.03 155.3 152.1 139.3 126.5 113.6 100.8 88.0 147.3 15.53 147.3 143.9 131.1 118.3 105.4 92.6 79.8
4500
5250
6000
6600
7200
189.7 14.51 123.4 108.2 93.1 77.9 62.7
-
-
178.3 15.95 118.9 103.7 88.6 73.4 58.2
-
-
172.3 14.24 154.6 139.5 124.3 109.1 94.0 78.8 63.6 161.8 15.70 150.1 134.9 119.8 104.6 89.4 74.3 59.1
156.9 14.05 156.9 155.0 148.1 132.9 117.7 102.6 87.4 147.8 15.52 147.8 146.3 139.9 124.8 109.6 94.4 79.3
159.4 14.08 159.4 157.8 151.4 136.2 121.1 105.9 90.8 151.2 15.55 151.2 149.5 143.1 127.9 112.7 97.6 82.4
194.6 14.56 135.5 118.0 100.5 83.0 65.5
-
-
182.8 15.97 131.0 113.5 96.0 78.5 61.0
-
-
176.7 14.29 169.2 151.7 134.2 116.7 99.3 81.8 64.3 166.0 15.72 164.8 147.3 129.8 112.3 94.8 77.3 59.8
160.9 14.09 160.9 160.9 159.9 142.4 124.9 107.4 89.9 151.6 15.54 151.6 151.6 151.6 134.1 116.6 99.1 81.6
163.5 14.13 163.5 163.5 163.5 146.0 128.5 111.0 93.5 155.0 15.56 155.0 155.0 155.0 137.5 120.0 102.6 85.1
199.3 14.65 145.7 126.3 106.8 87.3 67.8
-
-
187.1 16.07 141.1 121.6 102.1 82.6 63.1
-
-
180.9 14.38 177.2 162.1 142.6 123.1 103.7 84.2 64.7 169.9 15.82 169.3 157.5 138.1 118.6 99.1 79.6 60.1
164.8 14.18 164.8 164.8 164.3 144.8 125.3 105.8 86.3 155.2 15.64 155.2 155.2 155.2 135.7 116.2 96.8 77.3
167.4 14.21 167.4 167.4 167.4 148.0 128.5 109.0 89.5 158.7 15.66 158.7 158.7 158.7 139.2 119.7 100.3 80.8
203.9 14.74 156.0 134.5 113.1 91.6 70.1
-
-
191.5 16.18 151.2 129.7 108.2 86.8 65.3
-
-
185.2 14.47 185.2 172.5 151.0 129.5 108.1 86.6 65.2 173.8 15.93 173.8 167.8 146.3 124.9 103.4 81.9 60.5
168.6 14.27 168.6 168.6 168.6 147.2 125.7 104.2 82.8 158.8 15.74 158.8 158.8 158.8 137.3 115.9 94.4 72.9
171.4 14.30 171.4 171.4 171.4 149.9 128.4 107.0 85.5 162.4 15.77 162.4 162.4 162.4 140.9 119.4 98.0 76.5
125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
162.5 17.41 102.4 89.5 76.7 63.9 51.0
-
-
147.5 17.18 130.8 118.0 105.1 92.3 79.5 66.6 53.8
135.2 17.00 135.2 133.0 120.2 107.4 94.5 81.7 68.9
139.2 17.02 139.2 135.7 122.9 110.1 97.2 84.4 71.6
4500
5250
6000
6600
7200
166.8 17.40 114.4 99.2 84.1 68.9 53.7
-
-
151.3 17.17 145.5 130.4 115.2 100.1 84.9 69.7 54.6
138.8 16.99 138.8 137.7 131.8 116.6 101.5 86.3 71.1
142.9 17.01 142.9 141.1 134.7 119.6 104.4 89.2 74.1
171.0 17.38 126.4 108.9 91.4 73.9 56.5
-
-
155.2 17.16 155.2 142.8 125.3 107.8 90.3 72.8 55.3
142.3 16.98 142.3 142.3 142.3 125.9 108.4 90.9 73.4
146.6 17.00 146.6 146.6 146.6 129.1 111.6 94.1 76.6
175.0 17.50 136.4 116.9 97.4 77.9 58.5
-
-
158.8 17.27 158.8 153.0 133.5 114.0 94.5 75.0 55.6
145.6 17.10 145.6 145.6 145.6 126.7 107.2 87.7 68.2
150.0 17.12 150.0 150.0 150.0 130.5 111.0 91.5 72.0
179.0 17.62 146.3 124.9 103.4 81.9 60.5
-
-
162.4 17.38 162.4 162.4 141.7 120.2 98.7 77.3 55.8
148.9 17.21 148.9 148.9 148.9 127.5 106.0 84.5 63.1
153.4 17.23 153.4 153.4 153.4 131.9 110.4 89.0 67.5
1.
2.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
10
Unitary Products Group
261660-YTG-C-0707
TABLE 5: COOLING CAPACITIES FOR DJ210
Temperature of Air on Condenser Coil
Air on Evaporator Coil
85°F
95°F
2
Total Total2
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
80 77 74
Total Total
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
WB
(°F)
1
CFM
Cap.1 Input
(MBH) (kW) 86
Cap. Input
68 (MBH) (kW) 86
83
71
-
83
80
77
74
71
-
68
-
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
238.9 14.24 142.6 125.5 108.4 91.3 74.2
-
222.9 15.81 136.5 119.4 102.3 85.2 68.1
221.2 13.83 178.6 161.5 144.4 127.3 110.2 93.1 76.0 207.1 15.38 172.8 155.7 138.6 121.5 104.4 87.2 70.1
207.4 13.57 207.4 192.8 175.7 158.5 141.4 124.3 107.2 197.6 15.09 197.6 181.0 163.8 146.7 129.6 112.5 95.4
197.6 13.52 197.6 195.7 178.6 161.4 144.3 127.2 110.1 186.0 15.06 186.0 181.8 164.7 147.6 130.5 113.4 96.3
6000
246.1 14.36 154.5 135.8 117.0 98.3 79.5
-
-
231.8 15.91 149.7 130.9 112.2 93.4 74.6
-
-
227.9 13.95 193.5 174.7 156.0 137.2 118.4 99.7 80.9 215.4 15.48 189.4 170.7 151.9 133.2 114.4 95.6 76.9
213.7 13.69 213.7 206.4 189.7 170.9 152.2 133.4 114.6 205.5 15.19 205.5 197.1 179.6 160.9 142.1 123.4 104.6
203.6 13.64 203.6 202.6 192.8 174.1 155.3 136.5 117.8 193.5 15.15 193.5 191.3 180.6 161.8 143.1 124.3 105.5
6500
7000
7875
8750
253.4 14.48 166.5 146.1 125.7 105.3 84.9
-
-
240.7 16.00 162.8 142.4 122.0 101.6 81.2
-
-
234.6 14.06 208.3 187.9 167.5 147.1 126.7 106.3 85.9 223.6 15.57 206.1 185.7 165.3 144.8 124.4 104.0 83.6
220.0 13.80 220.0 220.0 203.7 183.3 162.9 142.5 122.1 213.3 15.28 213.3 213.3 195.4 175.0 154.6 134.2 113.8
209.6 13.75 209.6 209.6 207.1 186.7 166.2 145.8 125.4 200.9 15.24 200.9 200.9 196.4 176.0 155.6 135.2 114.8
258.4 14.56 180.9 157.6 134.4 111.2 87.9
-
-
243.3 16.09 176.8 153.6 130.3 107.1 83.8
-
-
239.3 14.14 225.6 202.4 179.1 155.9 132.6 109.4 86.1 226.0 15.65 217.3 199.8 176.5 153.3 130.0 106.8 83.5
224.4 13.88 224.4 224.4 216.2 193.0 169.7 146.5 123.2 215.6 15.36 215.6 215.6 206.7 183.4 160.2 136.9 113.7
213.8 13.82 213.8 213.8 212.5 189.2 166.0 142.8 119.5 203.0 15.32 203.0 203.0 200.8 177.6 154.3 131.1 107.8
263.5 14.63 195.3 169.2 143.1 117.0 91.0
-
-
245.9 16.17 190.8 164.7 138.7 112.6 86.5
-
-
243.9 14.21 242.9 216.8 190.7 164.7 138.6 112.5 86.4 228.4 15.73 228.4 213.9 187.8 161.7 135.6 109.5 83.5
228.7 13.95 228.7 228.7 228.7 202.6 176.6 150.5 124.4 217.9 15.43 217.9 217.9 217.9 191.8 165.8 139.7 113.6
217.9 13.90 217.9 217.9 217.9 191.8 165.8 139.7 113.6 205.2 15.40 205.2 205.2 205.2 179.1 153.0 126.9 100.9
105°F
115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
210.2 17.65 131.0 113.9 96.8 79.7 62.6
-
-
197.6 19.49 125.5 108.3 91.2 74.1 57.0
-
-
195.1 17.21 167.5 150.4 133.3 116.2 99.1 82.0 64.9 183.1 19.04 162.2 145.1 128.0 110.9 93.8 76.7 59.6
186.9 17.01 186.9 170.6 153.5 136.4 119.3 102.2 85.1 176.3 18.92 176.3 160.2 143.1 126.0 108.9 91.8 74.7
174.4 16.80 174.4 172.3 155.2 138.1 121.0 103.9 86.8 162.8 18.55 162.8 162.8 145.7 128.6 111.5 94.4 77.3
6000
6500
7000
7875
8750
218.3 17.77 143.8 125.0 106.3 87.5 68.7
-
-
204.8 19.63 137.9 119.1 100.3 81.6 62.8
-
-
202.6 17.33 183.9 165.1 146.4 127.6 108.8 90.1 71.3 189.9 19.18 178.3 159.5 140.8 122.0 103.3 84.5 65.8
194.1 17.12 194.1 186.0 168.5 149.8 131.0 112.2 93.5 182.8 19.06 182.8 174.8 157.4 138.6 119.9 101.1 82.4
181.1 16.92 181.1 180.1 170.4 151.7 132.9 114.1 95.4 168.8 18.69 168.8 168.8 160.3 141.5 122.8 104.0 85.2
226.4 17.89 156.6 136.2 115.7 95.3 74.9
-
-
212.1 19.77 150.3 129.9 109.5 89.0 68.6
-
-
210.1 17.45 200.2 179.8 159.4 139.0 118.6 98.2 77.8 196.6 19.32 194.4 174.0 153.6 133.2 112.7 92.3 71.9
201.3 17.24 201.3 201.3 183.6 163.1 142.7 122.3 101.9 189.3 19.20 189.3 189.3 171.7 151.3 130.9 110.5 90.0
187.8 17.03 187.8 187.8 185.6 165.2 144.8 124.4 104.0 174.8 18.82 174.8 174.8 174.8 154.4 134.0 113.6 93.2
228.5 17.97 171.3 148.0 124.8 101.5 78.3
-
-
213.7 19.85 165.7 142.5 119.2 96.0 72.7
-
-
212.1 17.53 207.1 193.3 171.9 148.6 125.4 102.2 78.9 198.1 19.40 197.0 186.8 167.3 144.0 120.8 97.5 74.3
203.2 17.32 203.2 203.2 194.3 171.0 147.8 124.5 101.3 190.7 19.28 190.7 190.7 181.9 158.6 135.4 112.1 88.9
189.6 17.11 189.6 189.6 188.5 165.2 142.0 118.7 95.5 176.1 18.90 176.1 176.1 176.1 152.9 129.6 106.4 83.1
230.6 18.05 186.0 159.9 133.8 107.7 81.7
-
-
215.2 19.94 181.1 155.1 129.0 102.9 76.8
-
-
214.0 17.61 214.0 206.7 184.4 158.3 132.2 106.1 80.0 199.5 19.48 199.5 199.5 181.0 154.9 128.8 102.7 76.6
205.0 17.40 205.0 205.0 205.0 178.9 152.8 126.8 100.7 192.1 19.36 192.1 192.1 192.1 166.0 139.9 113.8 87.8
191.3 17.19 191.3 191.3 191.3 165.2 139.1 113.0 87.0 177.4 18.98 177.4 177.4 177.4 151.3 125.2 99.1 73.1
125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
184.9 21.33 119.9 102.8 85.7 68.6 51.5
-
-
171.1 20.87 156.9 139.8 122.7 105.6 88.5 71.4 54.3
165.7 20.84 165.7 149.9 132.7 115.6 98.5 81.4 64.3
151.2 20.30 151.2 151.2 136.2 119.1 102.0 84.9 67.8
6000
6500
7000
7875
8750
191.4 21.49 132.0 113.2 94.4 75.7 56.9
-
-
177.1 21.03 172.7 154.0 135.2 116.5 97.7 79.0 60.2
171.5 21.00 171.5 163.6 146.3 127.5 108.8 90.0 71.3
156.5 20.46 156.5 156.5 150.1 131.4 112.6 93.8 75.1
197.8 21.65 144.0 123.6 103.2 82.8 62.3
-
-
183.1 21.19 183.1 168.1 147.7 127.3 106.9 86.5 66.1
177.3 21.16 177.3 177.3 159.8 139.4 119.0 98.6 78.2
161.8 20.61 161.8 161.8 161.8 143.6 123.2 102.8 82.4
198.9 21.74 160.2 136.9 113.7 90.4 67.2
-
-
184.1 21.27 184.1 180.2 162.6 139.4 116.2 92.9 69.7
178.2 21.24 178.2 178.2 169.5 146.3 123.0 99.8 76.5
162.6 20.69 162.6 162.6 162.6 140.5 117.3 94.0 70.8
199.9 21.82 176.3 150.2 124.2 98.1 72.0
-
-
185.1 21.35 185.1 185.1 177.6 151.5 125.4 99.3 73.2
179.2 21.32 179.2 179.2 179.2 153.1 127.0 100.9 74.8
163.5 20.77 163.5 163.5 163.5 137.4 111.3 85.2 59.2
1.
2.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
11
261660-YTG-C-0707
TABLE 6: COOLING CAPACITIES FOR DJ240
Temperature of Air on Condenser Coil
Air on Evaporator Coil
85°F
95°F
2
Total Total2
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
80 77 74
Total Total
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
WB
(°F)
1
CFM
Cap.1 Input
(MBH) (kW) 86
Cap. Input
68 (MBH) (kW) 86
83
71
-
83
80
77
74
71
-
68
-
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
273.1 16.90 149.8 132.7 115.6 98.5 81.4
-
257.3 18.45 150.2 133.1 116.0 98.9 81.8
248.6 16.43 197.6 180.5 163.4 146.3 129.1 112.0 94.9 237.3 17.83 192.3 175.1 158.0 140.9 123.8 106.7 89.6
231.2 16.44 227.9 210.8 193.7 176.6 159.5 142.4 125.3 215.2 17.64 215.2 200.8 183.7 166.6 149.5 132.4 115.3
216.6 15.98 216.6 210.2 193.1 176.0 158.9 141.8 124.7 221.2 17.98 221.2 213.2 196.1 179.0 161.8 144.7 127.6
6000
278.7 16.96 165.8 145.6 125.4 105.1 84.9
-
-
264.7 18.51 167.2 146.9 126.7 106.5 86.3
-
-
253.8 16.49 217.5 197.3 177.1 156.9 136.7 116.5 96.2 244.2 17.89 213.1 192.9 172.7 152.4 132.2 112.0 91.8
236.0 16.50 234.4 225.8 210.0 189.8 169.6 149.4 129.2 221.5 17.70 221.5 214.3 200.7 180.5 160.3 140.0 119.8
221.1 16.04 221.1 217.9 209.3 189.1 168.9 148.7 128.5 227.6 18.04 227.6 223.6 214.2 194.0 173.8 153.5 133.3
7000
8000
8700
9400
284.4 17.02 181.8 158.4 135.1 111.8 88.4
-
-
272.2 18.58 184.1 160.8 137.4 114.1 90.8
-
-
259.0 16.55 237.5 214.2 190.9 167.5 144.2 120.9 97.6 251.0 17.95 233.9 210.6 187.3 164.0 140.6 117.3 94.0
240.8 16.56 240.8 240.8 226.3 203.0 179.7 156.4 133.0 227.7 17.76 227.7 227.7 217.7 194.4 171.0 147.7 124.4
225.6 16.10 225.6 225.6 225.6 202.3 178.9 155.6 132.3 234.0 18.10 234.0 234.0 232.3 209.0 185.7 162.4 139.0
291.0 17.43 193.1 167.5 141.8 116.1 90.4
-
-
277.5 18.98 195.6 169.9 144.2 118.5 92.9
-
-
265.0 16.95 251.7 226.0 200.3 174.7 149.0 123.3 97.6 256.0 18.33 247.4 222.2 196.5 170.8 145.2 119.5 93.8
246.4 16.96 246.4 246.4 237.6 211.9 186.2 160.5 134.9 232.2 18.14 232.2 232.2 227.2 201.5 175.8 150.1 124.5
230.8 16.49 230.8 230.8 230.8 205.2 179.5 153.8 128.1 238.6 18.50 238.6 238.6 237.7 212.1 186.4 160.7 135.0
297.7 17.84 204.5 176.5 148.5 120.5 92.4
-
-
282.9 19.38 207.0 179.0 151.0 123.0 94.9
-
-
271.0 17.35 265.8 237.8 209.8 181.8 153.7 125.7 97.7 260.9 18.72 260.9 233.7 205.7 177.7 149.7 121.7 93.6
252.0 17.36 252.0 252.0 248.8 220.7 192.7 164.7 136.7 236.6 18.53 236.6 236.6 236.6 208.6 180.6 152.6 124.6
236.1 16.88 236.1 236.1 236.1 208.1 180.1 152.0 124.0 243.2 18.89 243.2 243.2 243.2 215.1 187.1 159.1 131.1
105°F
115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
244.1 20.09 146.5 129.4 112.3 95.2 78.1
-
-
230.8 21.72 142.8 125.7 108.6 91.5 74.4
-
-
225.3 19.63 186.7 169.6 152.5 135.4 118.3 101.2 84.1 213.4 21.43 181.2 164.1 147.0 129.9 112.8 95.7 78.6
202.7 19.37 202.7 194.9 177.7 160.6 143.5 126.4 109.3 190.2 21.09 190.2 188.9 171.8 154.7 137.6 120.5 103.4
211.7 19.63 211.7 205.7 188.6 171.5 154.4 137.3 120.2 202.2 21.28 202.2 198.2 181.1 164.0 146.9 129.8 112.7
6000
7000
8000
8700
9400
250.6 20.15 162.5 142.2 122.0 101.8 81.6
-
-
236.4 21.79 157.8 137.5 117.3 97.1 76.9
-
-
231.3 19.69 206.2 185.9 165.7 145.5 125.3 105.1 84.9 218.5 21.50 199.2 179.0 158.8 138.6 118.4 98.1 77.9
208.1 19.43 208.1 204.2 193.1 172.9 152.7 132.5 112.3 194.8 21.16 194.8 194.1 185.6 165.4 145.1 124.9 104.7
217.3 19.70 217.3 214.3 204.9 184.7 164.5 144.3 124.1 207.0 21.35 207.0 205.1 195.7 175.4 155.2 135.0 114.8
257.0 20.22 178.4 155.1 131.7 108.4 85.1
-
-
241.9 21.87 172.7 149.4 126.0 102.7 79.4
-
-
237.3 19.76 225.6 202.3 178.9 155.6 132.3 109.0 85.6 223.6 21.58 217.3 193.9 170.6 147.3 123.9 100.6 77.3
213.5 19.50 213.5 213.5 208.5 185.2 161.9 138.5 115.2 199.4 21.24 199.4 199.4 199.4 176.0 152.7 129.4 106.1
222.9 19.77 222.9 222.9 221.3 197.9 174.6 151.3 128.0 211.9 21.43 211.9 211.9 210.2 186.9 163.5 140.2 116.9
264.1 20.56 191.3 165.6 139.9 114.3 88.6
-
-
250.6 22.15 187.0 161.3 135.6 110.0 84.3
-
-
243.8 20.09 238.0 215.7 190.0 164.4 138.7 113.0 87.3 231.7 21.85 228.5 209.3 183.6 157.9 132.2 106.6 80.9
219.4 19.83 219.4 219.4 216.9 191.2 165.5 139.8 114.2 206.6 21.51 206.6 206.6 206.6 180.9 155.2 129.5 103.9
229.0 20.10 229.0 229.0 228.2 202.5 176.9 151.2 125.5 219.5 21.70 219.5 219.5 218.7 193.0 167.3 141.7 116.0
271.1 20.91 204.1 176.1 148.1 120.1 92.1
-
-
259.4 22.43 201.3 173.3 145.2 117.2 89.2
-
-
250.3 20.43 250.3 229.2 201.1 173.1 145.1 117.1 89.1 239.7 22.13 239.7 224.6 196.6 168.6 140.5 112.5 84.5
225.2 20.16 225.2 225.2 225.2 197.2 169.2 141.1 113.1 213.8 21.78 213.8 213.8 213.8 185.7 157.7 129.7 101.7
235.2 20.43 235.2 235.2 235.2 207.1 179.1 151.1 123.1 227.2 21.98 227.2 227.2 227.2 199.2 171.1 143.1 115.1
125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
217.6 23.35 139.1 122.0 104.9 87.8 70.7
-
-
201.4 23.23 175.7 158.6 141.5 124.4 107.3 90.2 73.1
177.7 22.82 177.7 177.7 165.8 148.7 131.6 114.5 97.4
192.7 22.93 192.7 190.8 173.7 156.5 139.4 122.3 105.2
6000
7000
8000
8700
9400
222.2 23.43 153.1 132.8 112.6 92.4 72.2
-
-
205.6 23.31 192.3 172.1 151.9 131.7 111.4 91.2 71.0
181.5 22.90 181.5 181.5 178.0 157.8 137.6 117.4 97.1
196.8 23.01 196.8 195.8 186.4 166.2 146.0 125.7 105.5
226.8 23.51 167.0 143.7 120.3 97.0 73.7
-
-
209.9 23.39 208.9 185.6 162.3 138.9 115.6 92.3 68.9
185.2 22.98 185.2 185.2 185.2 166.9 143.5 120.2 96.9
200.8 23.09 200.8 200.8 199.1 175.8 152.5 129.1 105.8
237.2 23.74 182.7 157.0 131.3 105.7 80.0
-
-
219.5 23.61 219.0 202.8 177.1 151.5 125.8 100.1 74.4
193.7 23.19 193.7 193.7 193.7 170.6 144.9 119.2 93.6
210.0 23.30 210.0 210.0 209.2 183.5 157.8 132.1 106.5
247.6 23.96 198.4 170.4 142.4 114.3 86.3
-
-
229.1 23.84 229.1 220.0 192.0 164.0 136.0 107.9 79.9
202.3 23.41 202.3 202.3 202.3 174.3 146.3 118.2 90.2
219.2 23.52 219.2 219.2 219.2 191.2 163.2 135.1 107.1
1.
2.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
12
Unitary Products Group
261660-YTG-C-0707
TABLE 7: COOLING CAPACITIES FOR DJ300
Temperature of Air on Condenser Coil
Air on Evaporator Coil
85°F
95°F
2
Total Total2
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
80 77 74
Total Total
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
WB
(°F)
1
CFM
Cap.1 Input
(MBH) (kW) 86
Cap. Input
68 (MBH) (kW) 86
83
71
-
83
80
77
74
71
-
68
-
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
332.2 21.58 206.4 185.0 163.6 142.3 120.9
-
324.4 25.42 191.5 170.2 148.8 127.4 106.0
327.2 21.26 256.1 234.7 213.3 192.0 170.6 149.2 127.8 305.5 24.73 245.9 224.5 203.1 181.7 160.4 139.0 117.6
321.0 20.60 320.3 298.9 277.5 256.1 234.7 213.4 192.0 301.1 24.23 295.5 274.2 252.8 231.4 210.0 188.6 167.2
313.6 20.57 313.6 305.9 284.5 263.1 241.8 220.4 199.0 292.2 24.07 292.2 277.1 255.7 234.3 212.9 191.5 170.1
7500
329.6 22.39 217.2 191.9 166.6 141.4 116.1
-
-
326.8 25.46 207.5 182.3 157.0 131.7 106.4
-
-
324.6 22.06 267.8 242.5 217.3 192.0 166.7 141.4 116.2 307.7 24.76 264.9 239.6 214.4 189.1 163.8 138.5 113.3
318.4 21.37 318.0 307.3 282.6 257.3 232.0 206.8 181.5 303.3 24.26 300.5 289.8 266.7 241.5 216.2 190.9 165.7
311.1 21.34 311.1 307.2 289.7 264.5 239.2 213.9 188.6 294.3 24.10 294.3 286.7 269.8 244.5 219.3 194.0 168.7
8750
10000
11250
12500
326.9 23.20 228.0 198.8 169.6 140.5 111.3
-
-
329.1 25.49 223.5 194.4 165.2 136.1 106.9
-
-
321.9 22.86 279.5 250.3 221.2 192.0 162.8 133.7 104.5 309.9 24.79 283.9 254.7 225.6 196.4 167.3 138.1 108.9
315.8 22.15 315.8 315.8 287.7 258.5 229.4 200.2 171.0 305.5 24.29 305.5 305.5 280.7 251.6 222.4 193.2 164.1
308.5 22.12 308.5 308.5 294.9 265.8 236.6 207.5 178.3 296.4 24.13 296.4 296.4 283.9 254.8 225.6 196.5 167.3
333.6 23.42 241.2 208.0 174.8 141.6 108.4
-
-
336.1 25.73 238.9 205.7 172.5 139.3 106.1
-
-
328.6 23.07 294.3 261.1 227.9 194.7 161.5 128.3 95.1 316.4 25.02 302.0 268.8 235.5 202.3 169.1 135.9 102.7
322.3 22.35 322.3 322.3 296.5 263.3 230.0 196.8 163.6 311.9 24.52 311.9 311.9 293.1 259.9 226.7 193.5 160.3
314.9 22.32 314.9 314.9 304.0 270.7 237.5 204.3 171.1 302.7 24.36 302.7 302.7 296.5 263.2 230.0 196.8 163.6
340.4 23.63 254.5 217.3 180.0 142.7 105.5
-
-
343.1 25.96 254.3 217.1 179.8 142.5 105.3
-
-
335.2 23.28 309.2 271.9 234.7 197.4 160.2 122.9 85.6 323.0 25.25 320.0 282.8 245.5 208.2 171.0 133.7 96.5
328.8 22.55 328.8 328.8 305.2 268.0 230.7 193.5 156.2 318.4 24.74 318.4 318.4 305.5 268.2 231.0 193.7 156.5
321.3 22.53 321.3 321.3 313.0 275.7 238.4 201.2 163.9 309.0 24.58 309.0 309.0 309.0 271.7 234.4 197.2 159.9
105°F
115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
301.8 27.73 184.5 163.2 141.8 120.4 99.0
-
-
279.1 30.03 177.6 156.2 134.8 113.4 92.0
-
-
289.0 27.27 238.8 217.4 196.0 174.6 153.2 131.9 110.5 272.6 29.81 231.6 210.3 188.9 167.5 146.1 124.7 103.3
283.6 26.57 280.8 259.7 238.3 216.9 195.5 174.1 152.7 266.0 28.91 266.0 245.2 223.8 202.4 181.0 159.6 138.3
271.5 26.43 271.5 260.3 238.9 217.6 196.2 174.8 153.4 250.9 28.79 250.9 243.6 222.2 200.8 179.4 158.1 136.7
7500
8750
306.8 27.83 201.3 176.1 150.8 125.5 100.2
-
-
286.9 30.20 195.1 169.8 144.6 119.3 94.0
-
-
293.9 27.37 259.0 233.7 208.5 183.2 157.9 132.7 107.4 280.1 29.98 253.1 227.9 202.6 177.3 152.0 126.8 101.5
288.3 26.67 286.9 276.4 253.4 228.1 202.8 177.6 152.3 273.3 29.07 273.3 262.9 240.0 214.8 189.5 164.2 138.9
276.1 26.53 276.1 270.5 254.1 228.8 203.5 178.3 153.0 257.9 28.96 257.9 254.2 238.3 213.1 187.8 162.5 137.3
311.8 27.93 218.1 188.9 159.8 130.6 101.5
-
-
294.6 30.38 212.7 183.5 154.4 125.2 96.0
-
-
298.7 27.47 279.3 250.1 220.9 191.8 162.6 133.5 104.3 287.6 30.16 274.6 245.5 216.3 187.1 158.0 128.8 99.7
293.1 26.77 293.1 293.1 268.5 239.3 210.2 181.0 151.9 280.7 29.24 280.7 280.7 256.3 227.1 198.0 168.8 139.6
280.6 26.63 280.6 280.6 269.2 240.0 210.9 181.7 152.6 264.8 29.13 264.8 264.8 254.5 225.3 196.2 167.0 137.8
10000
11250
12500
318.7 28.19 233.1 199.9 166.7 133.5 100.3
-
-
301.4 30.66 227.3 194.1 160.9 127.7 94.5
-
-
305.4 27.73 294.9 263.7 230.5 197.3 164.1 130.9 97.7 294.3 30.44 287.8 258.7 225.5 192.3 159.1 125.9 92.7
299.6 27.02 299.6 299.6 280.1 246.9 213.7 180.5 147.3 287.2 29.52 287.2 287.2 267.2 234.0 200.8 167.6 134.3
286.8 26.88 286.8 286.8 280.9 247.7 214.5 181.2 148.0 270.9 29.40 270.9 270.9 265.3 232.1 198.9 165.7 132.5
325.6 28.46 248.2 210.9 173.6 136.4 99.1
-
-
308.2 30.95 242.0 204.8 167.5 130.2 93.0
-
-
312.0 27.99 310.5 277.4 240.1 202.8 165.6 128.3 91.1 300.9 30.72 300.9 272.0 234.7 197.4 160.2 122.9 85.7
306.0 27.27 306.0 306.0 291.8 254.5 217.3 180.0 142.8 293.6 29.79 293.6 293.6 278.1 240.8 203.6 166.3 129.0
293.0 27.13 293.0 293.0 292.5 255.3 218.0 180.8 143.5 277.0 29.68 277.0 277.0 276.1 238.9 201.6 164.3 127.1
125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
256.5 32.33 170.6 149.2 127.8 106.4 85.0
-
-
256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2
248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8
230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0
7500
8750
266.9 32.57 188.9 163.6 138.4 113.1 87.8
-
-
266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6
258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6
239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5
277.3 32.82 207.3 178.1 148.9 119.8 90.6
-
-
276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0
268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4
249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1
10000
11250
12500
284.0 33.13 221.6 188.3 155.1 121.9 88.7
-
-
283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6
274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4
255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9
290.7 33.44 235.9 198.6 161.3 124.1 86.8
-
-
289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3
281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3
261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7
1.
2.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
13
261660-YTG-C-0707
order to use the indoor blower tables for high altitude applica-
tions, certain corrections are necessary.
CFM, STATIC PRESSURE, AND POWER - ALTI-
TUDE AND TEMPERATURE CORRECTIONS
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In
TABLE 8: ALTITUDE CORRECTION FACTORS
ALTITUDE (FEET)
AIR TEMP
0
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
40
50
1.060
1.039
1.019
1.000
0.982
0.964
0.946
60
70
80
90
100
The examples below will assist in determining the airflow per-
formance of the product at altitude.
blower tables to select the blower speed and the BHP
requirement.
Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower performance
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature informa-
tion is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table
8 must be used to determine the static pressure and BHP.
Since no temperature data is given, we will assume an air
temperature of 70°F. Table 8 shows the correction factor to
be 0.832.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to
BHP at 5,000 ft = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
14
Unitary Products Group
261660-YTG-C-0707
FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
Unitary Products Group
15
261660-YTG-C-0707
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY
180 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
6000
BHP
BLOWER
SPEED,
(RPM)
4500
BHP
5250
BHP
6750
BHP
7200
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
850
870
6.0**
5.5
4.5
3.5
3.0
2.0
1.0
0.9
1.0
1.1
1.2
1.3
1.4
1.5
2.4
2.5
2.6
2.9
3.0
3.1
3.2
2.2
2.3
2.4
2.6
2.7
2.8
2.9
0.7
0.8
0.9
1.0
1.1
1.2
1.3
3.0
3.1
3.4
3.6
3.7
3.8
3.9
2.7
2.8
3.0
3.2
3.3
3.4
3.5
0.5
0.6
0.7
0.8
0.9
1.0
1.1
3.2
3.5
3.7
4.0
4.1
4.2
4.5
2.9
3.1
3.3
3.6
3.7
3.8
4.0
-
-
-
-
-
-
0.2
0.3
0.5
0.6
0.7
0.9
4.1
4.4
4.7
4.8.
5.0
5.2
3.7
3.9
4.2
4.3
4.5
4.7
-
-
-
915
0.2
0.4
0.5
0.6
0.7
4.5
4.9
5.1
5.4
5.7
4.0
4.4
4.6
4.8
5.1
965
980
1010
1040
208 VOLT AND HIGH STATIC DRIVE
965
980
6.0
5.5
4.5
3.5
3.0
2.0
1.0
1.2
1.3
1.5
1.6
1.7
1.9
2.1
2.9
3.0
3.2
3.4
3.5
3.7
3.9
2.6
2.7
2.9
3.0
3.1
3.3
3.5
1.0
1.1
1.3
1.4
1.5
1.7
2.0
3.6
3.7
3.9
4.0
4.2
4.5
4.7
3.2
3.3
3.5
3.6
3.8
4.0
4.2
0.8
0.9
1.1
1.2
1.3
1.5
1.8
4.0
4.1
4.5
4.7
4.9
5.1
5.5
3.6
3.7
4.0
4.2
4.4
4.6
4.9
0.5
0.6
0.8
1.0
1.2
-
4.7
4.8
5.1
5.5
5.7
-
4.2
4.3
4.6
4.9
5.1
-
0.4
5.0
4.4
0.5
5.1
4.6
1025
1065
1095
1130
1170
0.7
5.6
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
915
6.0**
5.0
4.0
3.5
2.0
1.0
1.0
1.1
1.2
1.3
1.5
1.6
2.4
2.6
2.9
3.0
3.2
3.3
2.2
2.4
2.6
2.7
2.9
3.0
0.8
0.9
1.0
1.1
1.3
1.4
3.1
3.3
3.6
3.7
3.9
4.0
2.8
3.0
3.2
3.3
3.5
3.6
0.6
0.7
0.8
0.9
1.1
1.2
3.5
3.7
4.0
4.1
4.5
4.7
3.1
3.3
3.6
3.7
4.0
4.2
0.2
0.3
0.5
0.6
0.9
1.0
4.1
4.4
4.7
4.8
5.3
5.5
3.7
3.9
4.2
4.3
4.7
4.9
-
-
-
0.2
0.4
0.5
0.7
-
4.5
5.0
5.1
5.7
-
4.0
4.4
4.6
5.1
-
965
980
1040
1065
230/460/575 VOLT AND HIGH STATIC DRIVE
980
6.0
4.5
4.0
3.5
2.5
1.5
1.0
1.3
1.5
1.6
1.7
1.9
2.1
2.2
2.9
3.2
3.4
3.5
3.7
3.9
4.0
2.6
2.9
3.0
3.1
3.3
3.5
3.6
1.1
1.3
1.4
1.5
1.7
2.0
2.1
3.7
3.9
4.0
4.2
4.5
4.7
4.8
3.3
3.5
3.6
3.8
4.0
4.2
4.3
0.9
1.1
1.2
1.3
1.5
1.8
2.0
4.1
4.5
4.7
4.9
5.1
5.5
5.7
3.7
4.0
4.2
4.4
4.6
4.9
5.1
0.6
0.9
1.0
1.2
-
4.8
5.3
5.5
5.7
-
4.3
4.7
4.9
5.1
-
0.5
5.1
4.6
1040
1065
1095
1130
1170
1190
0.7
5.7
5.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
16
Unitary Products Group
261660-YTG-C-0707
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY
210 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
8000
BHP
9000
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
1015
6.0**
5.0
4.0
3.0
2.0
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.1
3.2
4.1
4.6
5.3
5.9
1.8
2.7
3.4
3.9
4.5
5.0
0.1
0.5
0.9
1.1
1.4
1.7
2.3
3.5
4.5
5.1
5.8
6.5
2.0
2.9
3.8
4.3
4.9
5.5
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
3.8
4.9
5.5
6.3
7.0
3.2
4.1
4.6
5.3
5.9
-
-
-
0.1
0.4
0.7
1.0
5.1
5.9
6.9
7.7
4.3
5.0
5.8
6.5
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.5
2.0
1.0
1.3
1.6
1.8
1.9
2.0
2.1
2.3
2.4
4.6
5.3
5.8
6.1
6.2
6.4
6.6
6.7
3.9
4.5
4.9
5.1
5.2
5.4
5.5
5.6
1.1
1.4
1.7
1.8
1.9
2.0
2.1
2.2
5.1
5.8
6.3
6.5
6.8
7.0
7.2
7.3
4.3
4.9
5.3
5.5
5.7
5.9
6.0
6.1
0.8
1.2
1.5
1.6
1.7
1.8
1.9
2.1
5.5
6.3
6.9
7.1
7.4
7.6
7.8
7.9
4.6
5.3
5.8
6.0
6.2
6.4
6.6
6.7
0.4
0.7
1.0
1.1
1.2
1.3
1.5
-
5.9
6.9
7.5
7.8
8.1
8.3
8.6
-
5.0
5.8
6.3
6.6
6.8
7.0
7.2
-
1010
1020
1035
1050
1075
1100
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.0
2.1
3.2
4.1
4.6
5.3
5.9
6.1
1.8
2.7
3.4
3.9
4.5
5.0
5.1
0.1
0.5
0.9
1.1
1.4
1.7
1.8
2.3
3.5
4.5
5.1
5.8
6.5
6.6
2.0
2.9
3.8
4.3
4.9
5.5
5.6
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
1.6
3.8
4.9
5.5
6.3
7.0
7.3
3.2
4.1
4.6
5.3
5.9
6.1
-
-
-
930
0.1
0.4
0.7
1.0
1.1
5.1
5.9
6.9
7.7
7.9
4.3
5.0
5.8
6.5
6.7
950
980
1015
1025
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.0
1.5
1.0
1.3
1.6
1.9
2.0
2.1
2.3
2.4
2.5
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
3.9
4.5
5.0
5.2
5.4
5.5
5.6
5.7
1.1
1.4
1.7
1.9
2.0
2.1
2.2
2.3
5.1
5.8
6.5
6.8
7.0
7.2
7.3
7.4
4.3
4.9
5.5
5.7
5.9
6.0
6.1
6.2
0.8
1.2
1.5
1.7
1.8
1.9
2.1
2.2
5.5
6.3
7.0
7.4
7.6
7.8
7.9
8.1
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
0.4
0.7
1.0
1.2
1.3
1.5
-
5.9
6.9
7.7
8.1
8.3
8.6
-
5.0
5.8
6.5
6.8
7.0
7.2
-
1015
1035
1050
1080
1100
1120
-
-
-
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Unitary Products Group
17
261660-YTG-C-0707
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
8000
BHP
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
9000
BHP
9400
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
1015
6.0**
5.0
4.0
3.0
2.0
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.1
3.2
4.1
4.6
5.3
5.9
1.8
2.7
3.4
3.9
4.5
5.0
0.1
0.5
0.9
1.1
1.4
1.7
2.3
3.5
4.5
5.1
5.8
6.5
2.0
2.9
3.8
4.3
4.9
5.5
-
-
-
-
-
-
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
3.8
4.9
5.5
6.3
7.0
3.2
4.1
4.6
5.3
5.9
-
-
-
0.1
0.4
0.7
1.0
5.1
5.9
6.9
7.7
4.3
5.0
5.8
6.5
-
-
-
-
-
-
0.2
0.6
7.3
8.2
6.1
6.9
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.5
2.0
1.0
1.3
1.6
1.8
1.9
2.0
2.1
2.3
2.4
4.6
5.3
5.8
6.1
6.2
6.4
6.6
6.7
3.9
4.5
4.9
5.1
5.2
5.4
5.5
5.6
1.1
1.4
1.7
1.8
1.9
2.0
2.1
2.2
5.1
5.8
6.3
6.5
6.8
7.0
7.2
7.3
4.3
4.9
5.3
5.5
5.7
5.9
6.0
6.1
0.8
1.2
1.5
1.6
1.7
1.8
1.9
2.1
5.5
6.3
6.9
7.1
7.4
7.6
7.8
7.9
4.6
5.3
5.8
6.0
6.2
6.4
6.6
6.7
0.4
0.7
1.0
1.1
1.2
1.3
1.5
-
5.9
6.9
7.5
7.8
8.1
8.3
8.6
-
5.0
5.8
6.3
6.6
6.8
7.0
7.2
-
-
0.2
0.5
0.6
0.7
-
-
7.3
7.9
8.3
8.6
-
-
6.1
6.7
7.0
7.3
-
1010
1020
1035
1050
1075
1100
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.0
2.1
3.2
4.1
4.6
5.3
5.9
6.1
1.8
2.7
3.4
3.9
4.5
5.0
5.1
0.1
0.5
0.9
1.1
1.4
1.7
1.8
2.3
3.5
4.5
5.1
5.8
6.5
6.6
2.0
2.9
3.8
4.3
4.9
5.5
5.6
-
-
-
-
-
-
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
1.6
3.8
4.9
5.5
6.3
7.0
7.3
3.2
4.1
4.6
5.3
5.9
6.1
-
-
-
930
0.1
0.4
0.7
1.0
1.1
5.1
5.9
6.9
7.7
7.9
4.3
5.0
5.8
6.5
6.7
-
-
-
950
-
-
-
980
0.2
0.6
0.7
7.3
8.2
8.6
6.1
6.9
7.3
1015
1025
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.0
1.5
1.0
1.3
1.6
1.9
2.0
2.1
2.3
2.4
2.5
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
3.9
4.5
5.0
5.2
5.4
5.5
5.6
5.7
1.1
1.4
1.7
1.9
2.0
2.1
2.2
2.3
5.1
5.8
6.5
6.8
7.0
7.2
7.3
7.4
4.3
4.9
5.5
5.7
5.9
6.0
6.1
6.2
0.8
1.2
1.5
1.7
1.8
1.9
2.1
2.2
5.5
6.3
7.0
7.4
7.6
7.8
7.9
8.1
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
0.4
0.7
1.0
1.2
1.3
1.5
-
5.9
6.9
7.7
8.1
8.3
8.6
-
5.0
5.8
6.5
6.8
7.0
7.2
-
-
0.2
0.6
0.7
-
-
7.3
8.2
8.6
-
-
6.1
6.9
7.3
-
1015
1035
1050
1080
1100
1120
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
18
Unitary Products Group
261660-YTG-C-0707
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT
180 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
6000
BHP
BLOWER
SPEED,
(RPM)
4500
BHP
5250
BHP
6750
BHP
7200
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
850
870
6.0**
5.5
4.5
3.5
3.0
2.0
1.0
0.9
1.0
1.1
1.2
1.3
1.4
1.6
2.4
2.5
2.6
2.7
2.9
3.0
3.2
2.1
2.2
2.4
2.5
2.6
2.7
2.9
0.6
0.7
0.8
0.9
1.0
1.1
1.3
2.9
3.0
3.1
3.2
3.4
3.6
3.8
2.6
2.7
2.8
2.9
3.0
3.2
3.4
0.3
0.4
0.5
0.6
0.7
0.8
1.0
3.4
3.5
3.6
3.7
3.8
4.0
4.4
3.0
3.1
3.2
3.3
3.4
3.6
3.9
-
-
-
-
-
-
-
-
-
-
-
-
915
0.2
0.4
0.5
0.6
0.8
4.1
4.4
4.5
4.7
5.0
3.7
3.0
4.0
4.2
4.5
-
-
-
965
0.2
0.3
0.4
0.6
5.0
5.1
5.4
5.6
4.5
4.6
4.8
5.0
980
1010
1040
208 VOLT AND HIGH STATIC DRIVE
965
980
6.0
5.5
4.5
3.5
2.0
1.0
1.2
1.3
1.4
1.6
1.9
2.1
2.7
2.9
3.1
3.4
3.6
3.9
2.5
2.6
2.8
3.0
3.2
3.5
0.9
1.0
1.2
1.4
1.7
1.9
3.2
3.4
3.6
3.9
4.4
4.7
2.9
3.0
3.2
3.5
3.9
4.2
0.6
0.7
0.9
1.1
1.4
1.6
3.7
3.8
4.1
4.5
5.0
5.5
3.3
3.4
3.7
4.0
4.5
4.9
0.4
0.5
0.7
0.9
1.2
-
4.4
4.5
4.8
5.1
5.8
-
3.9
4.0
4.3
4.6
5.2
-
0.2
0.3
0.4
-
5.0
5.1
5.5
-
4.5
4.6
4.9
-
1025
1065
1125
1170
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
915
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.5
2.6
2.7
2.9
3.0
3.1
3.4
2.2
2.4
2.5
2.6
2.7
2.8
3.0
0.7
0.8
0.9
1.0
1.1
1.2
1.4
3.0
3.1
3.2
3.4
3.6
3.7
3.9
2.7
2.8
2.9
3.0
3.2
3.3
3.5
0.4
0.5
0.6
0.7
0.8
0.9
1.1
3.5
3.6
3.7
3.8
4.0
4.2
4.5
3.1
3.2
3.3
3.4
3.6
3.8
4.0
-
-
-
-
-
-
0.2
0.4
0.5
0.6
0.7
0.9
4.1
4.4
4.5
4.7
4.9
5.1
3.7
3.9
4.0
4.2
4.4
4.6
-
-
-
965
0.2
0.3
0.4
0.5
-
5.0
5.1
5.4
5.7
-
4.5
4.6
4.8
5.1
-
980
1015
1050
1065
230/460/575 VOLT AND HIGH STATIC DRIVE
980
6.0
4.5
4.0
2.5
1.5
1.0
1.3
1.6
1.7
1.9
2.1
2.2
2.9
3.2
3.4
3.6
3.9
4.0
2.6
2.9
3.0
3.2
3.5
3.6
1.0
1.3
1.4
1.7
1.8
1.9
3.4
3.8
3.9
4.4
4.7
4.8
3.0
3.4
3.5
3.9
4.2
4.3
0.7
1.0
1.1
1.4
1.6
1.7
3.8
4.4
4.5
5.0
5.5
5.6
3.4
3.9
4.0
4.5
4.9
5.0
0.5
0.8
0.9
1.2
-
4.5
5.0
5.1
5.8
-
4.0
4.5
4.6
5.2
-
0.3
5.1
4.6
1045
1065
1125
1170
1190
0.6
5.6
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Unitary Products Group
19
261660-YTG-C-0707
TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT
210 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
8000
BHP
9000
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
995
1015
6.0**
5.0
4.0
3.0
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
3.6
3.8
4.1
4.2
4.5
4.6
4.8
3.0
3.2
3.4
3.6
3.8
3.9
4.0
0.7
0.9
1.1
1.3
1.5
1.6
1.7
4.3
4.7
5.0
5.1
5.4
5.5
4.7
3.7
4.0
4.2
4.3
4.5
4.7
4.8
0.2
0.4
0.6
0.8
1.0
1.1
1.2
5.1
5.6
5.9
6.0
6.3
6.4
6.6
4.3
4.7
5.0
5.1
5.3
5.4
5.6
-
-
-
-
-
-
0.1
0.2
0.4
0.5
0.7
6.7
6.9
7.2
7.5
7.8
5.7
5.8
6.1
6.3
6.6
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
3.5
2.5
2.0
1.0
1.7
1.9
2.1
2.3
2.5
2.6
2.9
4.2
4.5
4.5
4.9
5.1
5.3
5.6
3.6
3.8
3.9
4.1
4.3
4.4
4.7
1.3
1.5
1.6
1.8
2.0
2.1
2.3
5.1
5.4
5.5
5.8
6.1
6.3
6.8
4.3
4.5
4.7
4.9
5.1
5.3
5.7
0.8
1.0
1.1
1.3
1.4
1.5
1.8
6.0
6.3
6.4
6.7
7.1
7.3
7.9
5.1
5.3
5.4
5.7
6.0
6.2
6.6
0.2
0.4
0.5
0.7
0.9
1.0
-
6.9
7.2
7.5
8.0
8.4
8.6
-
5.8
6.1
6.3
6.7
7.0
7.2
-
995
1025
1050
1065
1100
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
2.3
3.6
3.8
4.1
4.2
4.5
4.6
4.8
4.9
3.0
3.2
3.4
3.6
3.8
3.9
4.0
4.1
0.7
0.9
1.1
1.3
1.5
1.6
1.7
1.8
4.3
4.7
5.0
5.1
5.4
5.5
5.7
5.8
3.7
4.0
4.2
4.3
4.5
4.7
4.8
4.9
0.2
0.4
0.6
0.8
1.0
1.1
1.2
1.3
5.1
5.6
5.9
6.0
6.3
6.4
6.6
6.7
4.3
4.7
5.0
5.1
5.3
5.4
5.6
5.7
-
-
-
-
-
-
930
0.1
0.2
0.4
0.5
0.6
0.7
6.7
6.9
7.2
7.5
7.8
8.0
5.7
5.8
6.1
6.3
6.6
6.7
950
965
995
1015
1025
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
4.0
3.5
3.0
2.5
1.5
1.0
1.7
1.9
2.1
2.2
2.3
2.5
2.6
2.9
3.1
4.2
4.5
4.6
4.8
4.9
5.1
5.3
5.6
5.8
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
1.3
1.5
1.6
1.7
1.8
2.0
2.1
2.3
2.5
5.1
5.4
5.5
5.7
5.8
6.1
6.3
6.8
7.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
4.7
5.9
0.8
1.0
1.1
1.2
1.3
1.4
1.5
1.8
1.9
6.0
6.3
6.4
6.6
6.7
7.1
7.3
7.9
8.3
5.1
5.3
5.4
5.6
5.7
6.0
6.2
6.6
6.9
0.2
0.4
0.5
0.6
0.7
0.9
1.0
-
6.9
7.2
7.5
7.8
8.0
8.4
8.6
-
5.8
6.1
6.3
6.6
6.7
7.0
7.2
-
995
1015
1025
1050
1065
1100
1120
-
-
-
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
20
Unitary Products Group
261660-YTG-C-0707
TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
8000
BHP
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
9000
BHP
9400
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
995
1015
6.0**
5.0
4.0
3.0
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
3.6
3.8
4.1
4.2
4.5
4.6
4.8
3.0
3.2
3.4
3.6
3.8
3.9
4.0
0.7
0.9
1.1
1.3
1.5
1.6
1.7
4.3
4.7
5.0
5.1
5.4
5.5
4.7
3.7
4.0
4.2
4.3
4.5
4.7
4.8
0.2
0.4
0.6
0.8
1.0
1.1
1.2
5.1
5.6
5.9
6.0
6.3
6.4
6.6
4.3
4.7
5.0
5.1
5.3
5.4
5.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1
0.2
0.4
0.5
0.7
6.7
6.9
7.2
7.5
7.8
5.7
5.8
6.1
6.3
6.6
-
-
-
0.1
0.2
-
8.5
8.6
-
7.1
7.3
-
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
3.5
2.5
2.0
1.0
1.7
1.9
2.1
2.3
2.5
2.6
2.9
4.2
4.5
4.5
4.9
5.1
5.3
5.6
3.6
3.8
3.9
4.1
4.3
4.4
4.7
1.3
1.5
1.6
1.8
2.0
2.1
2.3
5.1
5.4
5.5
5.8
6.1
6.3
6.8
4.3
4.5
4.7
4.9
5.1
5.3
5.7
0.8
1.0
1.1
1.3
1.4
1.5
1.8
6.0
6.3
6.4
6.7
7.1
7.3
7.9
5.1
5.3
5.4
5.7
6.0
6.2
6.6
0.2
0.4
0.5
0.7
0.9
1.0
-
6.9
7.2
7.5
8.0
8.4
8.6
-
5.8
6.1
6.3
6.7
7.0
7.2
-
-
-
-
0.1
8.5
7.1
995
0.2
8.6
7.3
1025
1050
1065
1100
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
2.3
3.6
3.8
4.1
4.2
4.5
4.6
4.8
4.9
3.0
3.2
3.4
3.6
3.8
3.9
4.0
4.1
0.7
0.9
1.1
1.3
1.5
1.6
1.7
1.8
4.3
4.7
5.0
5.1
5.4
5.5
5.7
5.8
3.7
4.0
4.2
4.3
4.5
4.7
4.8
4.9
0.2
0.4
0.6
0.8
1.0
1.1
1.2
1.3
5.1
5.6
5.9
6.0
6.3
6.4
6.6
6.7
4.3
4.7
5.0
5.1
5.3
5.4
5.6
5.7
-
-
-
-
-
-
-
-
-
-
-
-
930
0.1
0.2
0.4
0.5
0.6
0.7
6.7
6.9
7.2
7.5
7.8
8.0
5.7
5.8
6.1
6.3
6.6
6.7
-
-
-
-
-
-
950
965
0.1
0.2
-
8.5
8.6
-
7.1
7.3
-
995
1015
1025
-
-
-
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
4.0
3.5
3.0
2.5
1.5
1.0
1.7
1.9
2.1
2.2
2.3
2.5
2.6
2.9
3.1
4.2
4.5
4.6
4.8
4.9
5.1
5.3
5.6
5.8
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
1.3
1.5
1.6
1.7
1.8
2.0
2.1
2.3
2.5
5.1
5.4
5.5
5.7
5.8
6.1
6.3
6.8
7.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
4.7
5.9
0.8
1.0
1.1
1.2
1.3
1.4
1.5
1.8
1.9
6.0
6.3
6.4
6.6
6.7
7.1
7.3
7.9
8.3
5.1
5.3
5.4
5.6
5.7
6.0
6.2
6.6
6.9
0.2
0.4
0.5
0.6
0.7
0.9
1.0
-
6.9
7.2
7.5
7.8
8.0
8.4
8.6
-
5.8
6.1
6.3
6.6
6.7
7.0
7.2
-
-
-
-
0.1
8.5
7.1
995
0.2
8.6
7.3
1015
1025
1050
1065
1100
1120
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Unitary Products Group
21
261660-YTG-C-0707
TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT
300 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
10000
BHP
BLOWER
SPEED,
(RPM)
7500
BHP
8750
BHP
11250
BHP
12500
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
975
6.0
5.0
4.0
3.0
2.0
1.0
0.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
5.0
0.7
0.9
1.1
1.3
1.6
1.8
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
6.3
6.7
7.0
7.3
7.6
8.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
-
-
-
-
-
-
0.2
0.4
0.6
0.8
1.0
9.7
10.2
10.6
11.1
11.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
-
-
-
-
-
0.2
13.5
11.0
208 VOLT AND HIGH STATIC DRIVE
1140
1180
1215
1255
1290
1330
1365
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.2
2.5
2.7
3.0
3.2
3.5
3.7
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
1.6
1.9
2.1
2.4
2.7
3.0
3.2
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
0.9
1.2
1.4
1.7
2.0
2.3
2.6
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.3
0.6
0.9
1.2
1.5
1.8
13.7
14.3
15.0
15.6
16.4
17.0
11.2
11.7
12.3
12.8
13.4
13.9
8.6
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.1
9.5
10.0
10.5
230/460/575 VOLT AND STANDARD DRIVE
975
6.0*
5.0
4.0
3.0
2.0
1.0
0.0
1.4
1.6
1.8
2.0
2.1
2.4
2.6
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
1.0
1.2
1.4
1.6
1.8
2.0
2.2
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
6.3
6.7
7.0
7.3
7.6
8.0
0.5
0.7
0.9
1.1
1.3
1.6
1.8
8.8
9.2
7.2
7.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
0.1
0.3
0.6
0.8
1.0
1.3
10.9
11.4
11.9
12.4
13.0
13.5
8.9
-
-
9.7
9.4
-
-
-
10.2
10.6
11.1
11.6
9.8
-
-
-
10.2
10.6
11.0
0.2
0.4
0.7
14.3
14.9
15.5
11.7
12.2
12.7
230/460/575 VOLT AND HIGH STATIC DRIVE
1140
1180
1215
1255
1290
1330
1365
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.4
2.7
2.9
3.2
3.4
3.7
3.9
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
2.1
2.3
2.6
2.9
3.1
3.4
3.7
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
1.6
1.9
2.2
2.5
2.7
3.0
3.3
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
1.1
1.4
1.7
2.0
2.2
2.6
2.9
13.1
13.7
14.3
15.0
15.6
16.4
17.0
10.7
11.2
11.7
12.3
12.8
13.4
13.9
0.5
0.8
1.1
1.4
-
15.0
15.8
16.4
17.2
-
12.3
12.9
13.5
14.1
-
8.6
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.1
9.5
10.0
10.5
-
-
-
-
-
-
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
22
Unitary Products Group
261660-YTG-C-0707
TABLE 16: BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
MOTOR
BLOWER
DRIVE RANGE
(RPM)
MODEL
SIZE
OUTSIDE PITCH
PITCH
LENGTH QTY.
(IN.)
EFF.
(%)
DESIG-
NATION
BORE DESIG-
(IN.) NATION
BORE DESIG-
(IN.) NATION
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
Standard 850/1065
BK90
1-1/8
BK80
8.75
7.75
11.75
10.75
11.3
8.4
1
BX81
BX78
BX83
BX81
82.8
79.8
84.8
82.8
86.0
84.0
1
1
1
1
1
1
2
15 TON
5
184 T
83
89
91
1VP56
1VP68
5.35
6.75
7.5
4.3-5.3
High
965/1190
Static
7.4
1
Standard 870/1025
BK120
11.4
10.4
11.1
9.5
1-3/16
1-3/16
17.5 &
20 TON
7.5 213 T
15 254 T
1-3/8
High
5.5-6.5
6.2-7.4
950/1120
Static
BK110
Standard 975/1165
1B5V110
1-7/16 5VX860
1-7/16 5VX840
25 TON
1VP75X
1-5/8
High
1140/1365
Static
1B5V94
9.7
1.
2.
All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because
they are located in the moving air, upstream of any heating device.
Do NOT close this pulley below 1 turn open.
1
TABLE 17: STATIC RESISTANCES
RESISTANCE, IWG
CFM
DESCRIPTION
15 TON
6000
0.1
17.5 TON
20 TON
25 TON
9400 7500 10000 12500
4500
7200 6000
7500
0.1
0.4
0.5
0.5
0.5
0.1
0.3
9000 6000
8000
0.1
0.4
0.5
0.5
0.5
0.1
0.3
WET INDOOR COIL
0.1
0.3
0.3
0.4
0.4
0.1
0.1
0.1
0.4
0.5
0.5
0.5
0.1
0.3
0.1
0.4
0.4
0.5
0.5
0.1
0.2
0.1
0.5
0.5
0.6
0.6
0.2
0.5
0.1
0.4
0.4
0.5
0.5
0.1
0.2
0.1
0.5
0.5
0.6
0.6
0.2
0.5
0.1
0.4
0.5
0.5
0.5
0.1
0.3
0.1
0.5
0.5
0.6
0.6
0.2
0.5
0.1
0.6
0.6
0.7
0.7
0.3
0.6
18 KW
36 KW
54 KW
72 KW
0.4
0.4
ELECTRIC HEAT OPTIONS
0.5
0.5
ECONOMIZER OPTION
0.1
HORIZONTAL DUCT CONNECTIONS2
0.2
1.
Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for
exception.)
2.
Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values
on the respective unit’s blower performance table.
TABLE 18: POWER EXHAUST PERFORMANCE
STATIC RESISTANCE OF RETURN DUCTWORK, IWG
0.3 0.4 0.5
MOTOR
SPEED1
0.2
0.6
CFM
kW
CFM
kW
CFM
kW
CFM
kW
CFM
kW
HIGH2
MEDIUM
LOW
5250
4900
4400
0.83
0.77
0.72
4500
3900
3700
0.85
0.79
0.74
4200
3500
3000
0.88
0.82
0.78
3750
2900
-
0.93
0.85
-
3000
0.99
-
-
-
-
1.
Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
The factory setting.
2.
Unitary Products Group
23
261660-YTG-C-0707
TABLE 19: DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
BRKR1
SIZE
ID
MIN.
CIRCUIT
AMPACITY
(AMPS)
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
(AMPS)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
0.0
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
74.2
74.2
112.9
160.1
169.4
73.2
73.2
126.3
147.9
191.2
36.1
36.1
63.1
74.0
95.6
28.2
29.0
50.7
59.3
76.7
86.0
86.0
118.7
165.9
175.2
86.0
86.0
133.3
154.9
198.2
43.2
43.2
66.6
77.5
99.1
35.0
35.0
53.6
62.2
79.5
90
90
125
175
200
90
13.5
27.0
40.6
54.1
0.0
37.5
75.1
112.6
150.1
~
208
230
460
575
208
230
460
575
22.4
22.4
10.9
8.3
164
164
100
78
2.1
2.1
1.1
0.9
2.1
2.1
1.1
0.9
15.4
15.4
7.2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
17.3
34.6
52.0
69.3
~
90
150
175
225
45
180
(15)
45
70
90
110
35
35
5.9
60
70
90
110
110
125
175
200
110
110
150
175
225
50
13.5
27.0
40.6
54.1
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
37.5
75.1
112.6
150.1
~
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
25.6
25.6
12.8
10.3
190
190
95
20.0
20.0
10.0
8.2
210
(17 1/2)
50
70
90
110
45
18.0
36.0
54.0
72.0
17.3
34.6
52.0
69.3
45
60
70
75
90
NOTE 1: HACR Type per NEC.
24
Unitary Products Group
261660-YTG-C-0707
TABLE 19: DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET (CONTINUED)
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
125
125
125
175
200
125
125
150
175
225
70
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
0.0
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
110.4
110.4
118.7
165.9
175.2
110.4
110.4
133.3
154.9
198.2
56.5
13.5
27.0
40.6
54.1
0.0
37.5
75.1
112.6
150.1
~
208
230
460
575
208
230
460
575
33.6
33.6
17.3
13.5
47.1
47.1
19.6
15.8
225
225
114
80
3.7
3.7
1.9
1.5
3.7
3.7
1.9
1.5
20.0
20.0
10.0
8.2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
17.3
34.6
52.0
69.3
~
240
(20)
56.5
70
66.6
77.5
99.1
70
90
110
50
50
44.6
44.6
53.6
60
62.2
79.5
70
90
159.4
159.4
159.4
189.1
198.4
159.4
159.4
159.4
178.2
221.5
71.0
200
200
200
200
225
200
200
200
200
250
90
13.5
27.0
40.6
54.1
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
37.5
75.1
112.6
150.1
~
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
245
245
125
100
38.6
38.6
19.3
15.4
300
(25)
71.0
78.3
90
90
89.1
110.7
57.0
100
125
70
18.0
36.0
54.0
72.0
17.3
34.6
52.0
69.3
57.0
62.6
71.2
70
70
80
88.5
100
NOTE 1: HACR Type per NEC.
Unitary Products Group
25
261660-YTG-C-0707
TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
BRKR1
SIZE
ID
MIN.
CIRCUIT
AMPACITY
(AMPS)
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
VOLTAGE
RLA
LRA
MODEL
STAGES AMPS
KW
EACH
EACH
NAGE)
(AMPS)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
0.0
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
84.2
84.2
125.4
172.6
181.9
83.2
100
100
150
175
200
100
100
150
175
225
50
13.5
27.0
40.6
54.1
0.0
37.5
75.1
112.6
150.1
~
208
230
460
575
208
230
460
575
22.4
22.4
10.9
8.3
164
164
100
78
2.1
2.1
1.1
0.9
2.1
2.1
1.1
0.9
15.4
15.4
7.2
10.0
10.0
5.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
17.3
34.6
52.0
69.3
~
84.6
138.8
160.4
203.7
41.1
180
(15)
42.3
50
69.4
80.2
101.9
32.2
34.0
70
90
110
40
40
5.9
4.0
55.7
60
64.3
81.7
96.0
70
90
110
110
150
200
200
110
110
150
175
225
60
13.5
27.0
40.6
54.1
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
37.5
75.1
112.6
150.1
~
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
96.0
25.6
25.6
12.8
10.3
190
190
95
20.0
20.0
10.0
8.2
10.0
10.0
5.0
131.2
178.4
187.7
96.0
96.0
145.8
167.4
210.7
48.2
48.2
72.9
210
(17 1/2)
60
80
83.7
105.4
39.0
90
110
45
18.0
36.0
54.0
72.0
17.3
34.6
52.0
69.3
39.0
58.6
67.2
45
60
70
75
4.0
84.5
90
NOTE 1: HACR Type per NEC.
26
Unitary Products Group
261660-YTG-C-0707
TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED)
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
150
150
150
200
200
150
150
150
175
225
70
VOLTAGE
RLA
LRA
MODEL
STAGES AMPS
KW
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
0.0
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
1
2
2
2
~
120.4
120.4
131.2
178.4
187.7
120.4
120.4
145.8
167.4
210.7
61.5
13.5
27.0
40.6
54.1
0.0
37.5
75.1
112.6
150.1
~
208
230
460
575
208
230
460
575
33.6
33.6
17.3
13.5
47.1
47.1
19.6
15.8
225
225
114
80
3.7
3.7
1.9
1.5
3.7
3.7
1.9
1.5
20.0
20.0
10.0
8.2
10.0
10.0
5.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
17.3
34.6
52.0
69.3
~
240
(20)
61.5
70
72.9
83.7
105.4
48.6
48.6
80
90
110
60
60
4.0
58.6
60
67.2
84.5
70
90
169.4
169.4
169.4
201.6
210.9
169.4
169.4
169.4
190.7
234.0
76.0
200
200
200
225
225
200
200
200
225
250
90
13.5
27.0
40.6
54.1
0.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
37.5
75.1
112.6
150.1
~
43.3
86.6
129.9
173.2
~
21.7
43.3
65.0
86.6
~
245
245
125
100
38.6
38.6
19.3
15.4
10.0
10.0
5.0
300
(25)
76.0
84.5
90
90
95.3
117.0
61.0
110
125
70
18.0
36.0
54.0
72.0
17.3
34.6
52.0
69.3
61.0
67.6
76.2
70
70
90
4.0
93.5
100
NOTE 1: HACR Type per NEC.
Unitary Products Group
27
261660-YTG-C-0707
1
TABLE 21: DJ VOLTAGE LIMITATIONS
VOLTAGE LIMITATIONS
VOLTAGE
POWER
SUPPLY
MIN.
MAX.
VOLTAGE
208/230-3-60
187
253
LIMITATIONS
414
518
506
630
460-3-60
575-3-60
1.
Utilization Range “A” in accordance with ARI Standard
110.
TABLE 22: PHYSICAL DATA
MODELS
DJ180
DJ210
DJ240
DJ300
CENTRIFUGAL BLOWER (Dia. x Wd.)
FAN MOTOR HP
15x15
5.0
18x15
7.5
18x15
7.5
18x15
15
EVAPORATOR
BLOWER
ROWS DEEP
4
EVAPORATOR
COIL
FINS PER INCH
13.5
25
FACE AREA (Sq. Ft.)
PROPELLER DIA. (In.) (Each)
24
1/3
24
1/3
30
3/4
30
3/4
CONDENSER FAN
(Four Per Unit)
FAN MOTOR HP
NOM. CFM TOTAL
ROWS DEEP
(Each)
(Each)
4,000
4,000
5,000
5,000
2
CONDENSER
COIL
FINS PER INCH
FACE AREA (Sq. Ft.)
20
63.8
COMPRESSOR
(Qty. Per Unit)
SCROLL
2
QUANTITY PER UNIT (12" X 24" X 2"
TOTAL FACE AREA (Sq. Ft.)
12
24
FILTERS
CHARGE
SYSTEM No.1
SYSTEM No. 2
COOLING ONLY
23/0
23/8
24/0
24/0
2540
2740
2780
23/8
23/8
23/8
23/8
2660
2860
2900
REFRIGERANT
22 (Lb./Oz.)
2260
2460
2500
2560
2760
2800
BASIC UNIT
N24
N32
GAS / ELECTRIC
DOUBLE WALL
260
160
ECONOMIZER
ECONOMIZER WITH
POWER EXHAUST
MOTORIZED DAMPER
245
150
25
30
35
40
10
18 KW
OPTIONS
36 KW
54 KW
72 KW
OPERATING
WEIGHTS
(LBS.)
ELECTRIC HEATER
HOT GAS BYPASS
SUPPLY FAN VFD
ROOF CURB
185
45
BAROMETRIC DAMPER
ECONOMIZER / MOTORIZED
DAMPER RAIN HOOD
ECONOMIZER / POWER
EXHAUST RAIN HOOD
WOOD SKID
55
90
220
28
Unitary Products Group
261660-YTG-C-0707
TABLE 23: SUPPLY FAN VFD WEIGHTS, IN LBS.
TABLE 24: ELECTRIC HEAT CORRECTION
FACTORS
SUPPLY FAN MOTOR
230V
460V
575V
kW CAP. MULTI-
PLIER
W/O MANUAL BYPASS
NOMINAL VOLTAGE
VOLTAGE
25
30
30
30
25
30
30
30
30
30
35
40
5.0 hp
7.5 hp
208
230
460
575
1.00
0.92
0.92
0.92
208
240
480
600
10.0 hp
15.0 hp
W/MANUAL BYPASS
5.0 hp
30
35
35
40
30
35
35
35
35
35
40
45
7.5 hp
10.0 hp
15.0 hp
CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
UNIT TERMINAL
BLOCK 1TB2
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
R
RH
RC
Y1
Y2
TERMINALS
Y1
Y2
W1
UNIT TERMINAL
BLOCK 1 TB2
RC
RH
R
ADD
JUMPER
W2
G
Y1
Y2
Y1
Y2
ADD
JUMPER
W1
W2
B
W1
W2
G
W1
W2
24 VOLT
TRANSFORMER
X
3
3
A1
A2
Y3
G
G
B
X
B
124 Volt Thermostat 2TH04701024 or 2TH04701524
(with Subbase 2TB04700324).
LED1
24 VOLT
TRANSFORMER
LED2
4
A1
A2
NOT USED
2Terminal strip 1TB - located on relay board in 24-volt section
of the unit control box.
4
COM
A1
3Second stage heating is not required on units with a single stage
electric heater.
ADD
JUMPER
A2
T
POWER WIRING
T
L1
Refer to the
TO REMOTE SENSOR
2THO4702224 IF USED
LINE VOLTAGE
TERMINAL
BLOCK 2TB
ELECTRICAL DATA
tables to size the
power wiring, the
fuses and the
L2
L3
1Electronic programmable thermostat 2ET04700224 (includes subbase).
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3Second stage heating is not required on units with a single stage electric heater.
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
when the thermostat switches to the set-back position.
IN CONTROL BOX
disconnect switch.
GROUND LUG
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.
FIGURE 3 - TYPICAL DJ FIELD WIRING DIAGRAM
Unitary Products Group
29
261660-YTG-C-0707
ECONOMIZER / MOTORIZED DAMPER
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail Y)
BLOWER MOTOR
ACCESS (Location
of Optional VFD Bypass)
BLOWER ACCESS
(Location of
Optional VFD)
BLOWER
COMPARTMENT
ACCESS
COMPRESSOR ACCESS
180-19/32
(Auxiliary)
DOT PLUG
(For pressure
drop reading)
52-5/8
GAS OR ELECTRIC
HEAT
ACCESS
COIL
GUARD
KIT
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET HOOD
21.00
9-3/4
(C) GAS
SUPPLY
ENTRY
CONDENSER
COILS
7-1/8
136-1/4
(A) CONTROL WIRING
ENTRY
92
6-3/8
46-5/8
5
DISCONNECT
SWITCH
LOCATION
11-1/2
CONTROL BOX
ACCESS
5-7/8
(B) POWER
WIRING
ENTRY
All dimensions are in inches. They are
subject to change without notice.
Certified dimensions will be provided
upon request.
35
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
35-1/4
RETURN
AIR
33
2-3/4
SUPPLY
AIR
3-3/4
21-1/2
UNIT BASE RAILS
Shown separately to illustrate
Bottom Duct openings. Power
and Gas Piping Connection
location.
(D)
GAS SUPPLY
ENTRY
(B) POWER WIRING
ENTRY
11-1/8
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for proper size of the
supply and return air duct connections.
8-1/8
(A) CONTROL WIRING
ENTRY
12-1/2
46-5/8
9-1/4
9-3/4
FIGURE 4 - FRONT VIEW DIMENSIONS
TABLE 25: UTILITIES ENTRY DATA
OPENING SIZE
HOLE
USED FOR
(DIA.)
1-1/8” KO
Side
Control Wiring
A
3/4” NPS (Fem.)
3-5/8” KO
Bottom
Side
B
Power Wiring
3” NPS (Fem.)
Bottom
1
2-3/8” KO
C
D
Gas Piping (Front)
,
2
1-11/16” Hole
Gas Piping (Bottom)
1.
2.
One-inch gas piping NPT required.
Opening in the bottom of the unit can be located by the slice in
the insulation.
NOTE: All entry holes should be field sealed to prevent rain
water entry into the building.
30
Unitary Products Group
261660-YTG-C-0707
EVAPORATOR
SECTION
DOT PLUG
(For pressure
drop reading)
40-3/8"
FILTER
ACCESS
SUPPLY
AIR
RETURN
AIR
COMPRESSOR
ACCESS
OUTDOOR
AIR
40-1/2"
SUPPLY AIR
ACCESS
18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION
27-3/4"
Dimensions listed are for side
5-1/8"
RETURN AIR
ACCESS
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.
OUTDOOR AIR
COMPARTMENT
ACCESS
39-5/8"
REAR
VIEW
FIGURE 5 - REAR VIEW DIMENSIONS
NOTE:Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for
connecting side ducts.
For bottom duct applications:
For side duct applications:
1. Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
1. Replace the side panels on the supply and return air
compartments with the side duct flange accessory kit
panels.
2. Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.
2. Connect ductwork to the flanges on those panels.
3. Replace the side supply and return air compartment
panels.
Unitary Products Group
31
261660-YTG-C-0707
NOTE: ELEC / ELEC Models: Units and ductwork are
TABLE 26: MINIMUM CLEARANCES
approved for zero clearance to combustible material
when equipped with electric heaters.
LOCATION
CLEARANCE
36”
Front
24” (Less Economizer)
49” (With Economizer)
Rear
GAS / ELEC Models: A 1” clearance must be
provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the
unit.
24” (Less Economizer)
Left Side (Filter Access)
Right Side (Cond. Coil)
3
36” (With Economizer)
36”
0”
1
Below Unit
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)
2
Above Unit
Locate unit so that the vent air outlet hood is at least:
1.
2.
Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
• Three (3) feet above any force air inlet located
within 10 horizontal feet (excluding those integral to
the unit).
Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters,
regulators and relief equipment.
ECONOMIZER
MOTORIZED
DAMPER
POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)
SUPPLY AIR
RAIN HOOD
(on Outdoor Air Compartment)
COMPARTMENT
ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS
FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
Compartment)
36-5/8”
1“ CONDENSATE
DRAIN
(Must be trapped)
16-1/8”
5”
28-3/16”
92”
REAR VIEW
LH VIEW
DETAIL “Y”
UNIT WITH RAIN HOODS
FIGURE 6 - UNIT DIMENSIONS DJ180, 210, 240 & 300 (RAINHOOD)
32
Unitary Products Group
261660-YTG-C-0707
FIGURE 7 - UNIT CENTER OF GRAVITY
ROOF JACK
INSTALLATION
ROOF CURB
INSTALLATION
SLAB ON
GROUND
INSTALLATION
FIGURE 8 - TYPICAL UNIT APPLICATIONS
Unitary Products Group
33
261660-YTG-C-0707
B
E
F
C
D
C
A
A
D
B
FIGURE 9 - FOUR AND SIX POINT LOADS
TABLE 27: FOUR AND SIX POINT LOADS
Total
Shipping
Weight
2660
4 Point Loads (lbs)
Unit Size
A
B
C
D
180 Gas
210 Gas
240 Gas
300 Gas
180 Elec
210 Elec
240 Elec
300 Elec
454
510
516
531
419
476
481
496
847
954
964
992
784
888
899
927
885
954
964
992
819
888
899
927
474
510
516
531
438
476
481
496
2928
2960
3046
2460
2728
2760
2846
Total
Shipping
Weight
2660
6 Point Loads (lbs)
Unit Size
A
B
C
D
E
F
180 Gas
210 Gas
240 Gas
300 Gas
180 Elec
210 Elec
240 Elec
300 Elec
302
340
344
354
280
317
321
331
316
340
344
354
292
317
321
331
453
488
493
508
419
455
460
474
590
636
643
661
546
592
599
618
565
636
643
661
523
592
599
618
434
488
493
508
401
455
460
474
2928
2960
3046
2460
2728
2760
2846
NOTE: These weights are with economizer, and high option heat (gas or electric)
34
Unitary Products Group
261660-YTG-C-0707
25-1/4"
FIGURE 10 - UNIT ROOF CURB DIMENSIONS
FIGURE 11 - ROOF CURB DUCT OPENINGS
DIMENSION
FIGURE 12 - CUT AWAY OF ROOF CURB
1. The 2” space between the ducts allows for “jumping” an
existing roof joist.
2. The 58-1/2” overall dimension of the ducts allows duct-
work penetration between roof joists that are spaced on
72” centers.
Note: Ducts can be installed into the curb from the roof. All
electrical and gas line connections can be made inside the
curb.
Unitary Products Group
35
261660-YTG-C-0707
THERMOSTAT
TERMINALS
CONTROL
TERMINAL
BLOCK
W1
W1
W2
Y1
G
1
W2
Y1
2
Y2
OCC
P
P1
Y2
X
G
R
C
Smoke
Detector
R
SD
C
Jumper 3
R
SD
SD
C
4
RC
5
OCC
24 VAC
Class 2
6
X
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
1
2
3
4
5
6
Second stage heating not required on single stage heating units.
Second stage cooling not required on single stage cooling units.
Jumper is required if there is no Smoke Detector circuit.
Jumper is required for any combination of R, RC, or RH.
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.
FIGURE 13 - TYPICAL SIMPLICITY® WIRING DIAGRAM
36
Unitary Products Group
261660-YTG-C-0707
They shall have built-in field convertible duct connections for
down discharge supply/return or horizontal discharge supply/
return, and be available with factory installed options or field
installed accessories. The units shall be factory wired, piped,
charged with R-22 refrigerant and factory tested prior to ship-
ment. All unit wiring shall be both numbered and color coded.
All units shall be manufactured in a facility certified to ISO
9001 standards and the cooling performance shall be rated in
accordance with DOE and ARI test procedures. Units shall
be ETL & CGA listed, classified to ANSIZ21.47 standards, UL
1995/CAN/CSA No. 236-M90 conditions.
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline Magnum™ units are convertible single pack-
age units. All models have dual independent refrigerant cir-
cuits for efficient part load operation and maximum comfort
control. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, replace the supply and return air panels
on the rear of the unit with a side duct flange accessory. All
supply air blowers are equipped with a belt drive that can be
adjusted to meet the exact requirements of the job.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel, with
exterior surfaces coated with a non-chalking, powdered paint
finish, certified at 1000 hours salt spray test per ASTM-B117
standards. Indoor blower section shall be insulated with a min-
imum 1/2" thick insulation, coated on the airside. Aluminum foil
faced insulation shall be used in the furnace compartment and
be fastened with ridged fasteners to prevent insulation from
entering the air stream. Cabinet panels shall be "large" size,
easily removable for servicing and maintenance. Full perimeter
base rails shall be provided to assure reliable transit of equip-
ment, overhead rigging and proper sealing on roof curb appli-
cations. Disposable 2" filters shall be furnished and be
accessible through a removable access door, sealed airtight.
Units filter track shall be designed to accommodate either 1" or
2" filters. Fan performance measuring ports shall be provided
on the outside of the cabinet to allow accurate air measure-
ments of evaporator fan performance without removing panels
or creating air by-pass of the coils. Condensate pan shall be
internally sloped and conform to ASHRAE 62-89 self-draining
standards. Condensate connection shall be a minimum of 1"
I.D. female and be a ridged mount connection. Unit shall incor-
porate a fixed outdoor air damper with an outdoor air intake
opening covered with a bird screen and a rain hood painted to
match the exterior of the unit.
Each unit shall have 4 condenser fan motors. A high static
drive option is available for applications with a higher CFM
and/or static pressure requirement. All compressors include
crankcase heat and internal pressure relief. Every refrigerant
circuit includes an expansion valve, a liquid line filter-drier, a
discharge line high pressure switch and a suction line with a
freezestat and low pressure/loss of charge switch. The unit
control circuit includes a 75 VA transformer, a 24-volt circuit
breaker and a relay board with two compressor lockout cir-
cuits, a terminal strip for thermostat wiring, plus an additional
set of pin connectors to simplify the interface of additional field
controls. All units have long lasting powder paint cabinets with
1000 hour salt spray test approval under ASTM-B117 proce-
dures. All 208/230 and 460-volt models are ETL approved. All
208/230 and 575-volt models are CGA approved. All models
include a 1-year limited warranty on the complete unit. Com-
pressors and electric heater elements carry an additional 4-
year warranty. Aluminized steel tubular heat exchangers carry
an additional 9-year warranty.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable-
pitch motor pulley. Job site selected (B.H.P.) brake horsepower
shall not exceed the motors nameplate horsepower rating, plus
the service factor. Units shall be designed not to operate above
service factor. Fan wheel shall be double-inlet type with for-
ward-curved blades, dynamically balanced to operate smoothly
throughout the entire range of operation. Airflow design shall be
constant air volume.
A variable air volume (VAV) option using a variable frequency
drive (VFD) is available for applications requiring a constant
supply duct static pressure. Units equipped for VAV shall be
controlled by a duct pressure transducer with a 0 - 5” WC pres-
sure range. The pressure transducer shall provide a 0 - 5 VDC
output signal to a VAV control board which, in turn shall provide
a 2 - 10 VDC speed reference signal to the VFD. The VAV con-
trol board shall operate using factory-installed Supply Air,
Return Air and Outside Air Temperature Sensors. Units
equipped with VFD’s shall have factory-installed manual
bypass as an option.
DESCRIPTION
Units shall be factory-assembled, single packaged, DJ***N
Electric Cooling/Gas Heat, DJ***C/E Electric Cooling/
Optional Electric Heat, designed for outdoor mounted instal-
lation. The 15,17.5, and 20 ton units shall have minimum
EER ratings of 11.1. The 25 ton unit shall have a minimum
EER rating of 10.5.
Unitary Products Group
37
261660-YTG-C-0707
OUTDOOR (CONDENSER) FAN ASSEMBLY
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
The outdoor fans shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to cor-
rosion resistant steel spider brackets and shall be dynami-
cally balanced for smooth operation. The 4 outdoor fan
motors shall be totally enclosed with permanently lubricated
bearings, internally protected against overload conditions and
staged independently.
c. Loss-of-charge/Low-pressure switch.
1. High-pressure switch.
2. Freeze-protection thermostat, evaporator coil. If
any of the above safety devices trip, a LED
(light-emitting diode) indicator shall flash a
diagnostic code that indicates which safety
switch has tripped.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be Scroll compressors internally protected with
internal high-pressure relief and over temperature
protection.
d. Unit shall incorporate "AUTO RESET" compressor
over temperature, over current protection.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent
mounting.
e. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
f. Unit control board shall have on-board diagnostics
and fault code display.
Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
g. Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0 °F.
h. Control board shall monitor each refrigerant safety
switch independently.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
i.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
GAS HEATING SECTION (DJ***N MODELS)
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
Shall be designed with induced draft combustion with post
purge logic and energy saving direct spark ignition, redun-
dant main gas valve. Ventor wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25° F. Burners shall be of the in-
shot type, constructed of aluminum coated steel and contain
air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
c. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 15° F
of sub-cooling at design conditions.
e. All models shall have two independent circuits.
f. Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in
low-load applications. HGBP shall be a standard
feature on VAV models and an optional feature on
CV models.
a. Primary and auxiliary high-temperature limit
switches.
UNIT CONTROLS
b. Induced draft motor speed sensor.
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
c. Flame roll out switch (automatic reset).
d. Flame proving controls. Unit shall have two inde-
pendent stages of capacity.
38
Unitary Products Group
261660-YTG-C-0707
ELECTRIC HEATING (DJ***C/E MODELS)
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
Nickel chromium electric heating elements shall be provided
as required by the application with 1 or 2 stage control, as
required, from 13.5 KW to 72 KW capacities. The heating
section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating
at an excessive temperature. Units with Electric Heating shall
be wired for a single point power supply with branch circuit
fusing (where required).
•
BAS-READY ECONOMIZER - Outdoor and return air
dampers that are interlocked and positioned by a fully-
modulating, spring return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG.
For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, free-cooling shall be available while the
outdoor dry bulb temperature (OAT) remains below a
programmable set-point of the controller. Field-installed
humidity sensors for either outdoor air or outdoor &
return air streams are available to provide free-cooling
based on single-enthalpy or dual-enthalpy configura-
tions, respectively. If free-cooling is available, a call for
cooling shall modulate the economizer in order to main-
tain a supply air temperature (SAT) programmable set-
point. With the use of a field-installed indoor air quality
sensor, the controller shall provide Demand Ventilation
by modulating the economizer dampers to allow more
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125° F
outdoor temperature, exceeding maximum load criteria of
ARI Standard 340/360. The compressor, with standard
controls, shall be capable of operation down to 25° F outdoor
temperature. Accessory low ambient kit shall be available for
operation to 0° F. Unit shall be provided with fan time delay to
prevent cold air delivery before heat exchanger warms up
(Gas heat only).
ELECTRICAL REQUIREMENTS
outside airflow upon detection of elevated indoor CO
2
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
concentrations above a programmable set-point. With an
additional field-installed outdoor air quality sensor, Differ-
ential Demand Ventilation shall be provided.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water elimina-
tor/filters shall be provided.
STANDARD LIMITED WARRANTIES
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
•
•
•
•
Compressor 5 Years
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in
the design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected posi-
tions - regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
•
ROOF CURB - 14" high, full perimeter curb with wood
nailer (shipped knocked-down).
100% BAROMETRIC RELIEF DAMPER - Contains a
rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure
through the unit.
Unitary Products Group
39
•
•
•
•
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
•
•
•
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
•
•
•
•
•
•
•
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
DOUBLE WALL
PHASE MONITOR
BURGLAR BARS - Designed to work with above roof
curbs, depending on unit model. Fits duct openings of
curb supply and return air openings.
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on units
with power exhaust.
BAS CONTROLS (S implicity® Intelli-Comfort™, CPC,
JOHNSON, HONEYWELL, NOVAR)
•
•
•
BAS READY ECONOMIZER ( 2-10 V.D.C. Actuator
without a controller)
HIGH STATIC DRIVE - Includes blower pulley and belt
for higher CFM and/or static pressure requirements.
HINGED FILTER DOOR ACCESS AND TOOL FREE
ACCESS PANELS
•
•
WOOD SKID - Allows unit to be handled with 90" forks.
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD
(DJN/E/C300 only) - Contains all hood panels and the
hardware for assembling.
HINGED TOOL FREE BLOWER, BLOWER MOTOR,
FILTER AND ELECTRICAL ACCESS PANELS
•
•
•
•
•
•
HIGH STATIC DRIVE
•
•
•
ANTI-RECYCLE TIMER - Assures 5-minute off time
between compressor cycles.
2" PLEATED FILTERS
4" THROW AWAY FILTERS
DISCONNECT SWITCH
LOW AMBIENT KIT - Provides unit cooling operation
down to 0°F.
COIL GUARD KIT - Guard for cooling coil.
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
Subject to change without notice. Printed in U.S.A.
261660-YTG-C-0707
Copyright © 2007 by Unitary Products Group. All rights reserved.