Print Form
™
ECO-i Submittal Data
WCHDZ20053
Heat Recovery: 16 tons VRF Outdoor Unit
Job Name:
Location:
Approval:
Date:
Engineer:
Construction:
Unit #:
Drawing #:
Submitted to:
Submitted by:
Reference:
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also available
Capacities
Fan
Cooling: Btu/h
Power Input: KW
Heating: Btu/h
Power Input: KW
191,00
8.12 (each)
215,000
Quantity/Type:
Fan Motor Output (KW):
1 Propeller (each)
0.7 (each)
7.97 (each)
Power Supply
V/PH/Hz.
208-230 / 3 / 60
37 (each)
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
Outdoor: °F DB
Minimum circuit Amps (MCA): Amps
Max. Overcurrent Protection (MOCP):
80/67
95
50 (each)
25
0
Pipe Length (feet):
Level Difference (feet):
Weight (lbs):
657 (each)
410A
Refrigerant:
Heating Mode Nominal Conditions
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length (feet):
70
47/43
25
Coil
Coil Face Area (sq. ft.):
Number of Rows:
22.5 (each)
4 (each)
Level Difference (feet):
0
Protection Devices
High Pressure Switch:
Overcurrent (CT Method):
Crankcase Heaters (W):
Operating Range
Cooling: °F DB:
Heating: °F DB:
Yes
Yes
25 + 32 (each)
14 to 113
-4 to 59
Heating + Cooling °F DB
14 to 113
External Finish:
Electrostatic Powder Coating
Compressor
1 Inverter driven rotary & 1 fxed speed scroll (each)
Quantity/Type:
10-100%
Capacity Control Range:
|