Mitsubishi Electronics Msh 24nv User Manual

This Servise Manual OB207 deals with MSH-07/09/12/18/24NV-E1,  
MUH-07/09/12/18/24NV-E1, MSH-18NV-E2, and MUH-18NV-E2 in  
OB176 REVISED EDITION-A issued in July in1997.  
Therefore, please refer to OB207, not to OB176 REVISED  
EDITION-A, for the above models.  
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS  
No. OB207  
SERVICE MANUAL  
Wireless type  
Models  
MSH-07NV - · MUH-07NV -  
E1  
E1  
(
)
WH  
E1  
MSH-09NV - · MUH-09NV -  
E1  
E1  
E1  
E1  
E2  
E2  
E2  
E2  
E2  
E3  
(
)
WH  
E1  
MSH-12NV - · MUH-12NV -  
(
)
WH  
E1  
MSH-18NV - · MUH-18NV -  
(
)
WH  
E1  
MSH-24NV - · MUH-24NV -  
(
)
WH  
E2  
MSH-07NV - · MUH-07NV -  
(
)
WH  
E2  
MSH-09NV - · MUH-09NV -  
(
)
WH  
E2  
MSH-12NV - · MUH-12NV -  
(
)
WH  
E2  
MSH-18NV - · MUH-18NV -  
(
)
WH  
E2  
MSH-24NV - · MUH-24NV -  
(
)
WH  
E3  
MSH-18NV - · MUH-18NV -  
(
)
WH  
CONTENTS  
1. TECHNICAL CHANGES ····································2  
2. PART NAMES AND FUNCTIONS······················3  
3. SPECIFICATION·················································6  
4. OUTLINES AND DIMENSIONS ······················ 11  
5. WIRING DIAGRAM ··········································15  
6. REFRIGERANT SYSTEM DIAGRAM··············24  
7. PERFORMANCE CURVES······························29  
8. MICROPROCESSOR CONTROL ····················33  
9. SERVICE FUNCTIONS ····································44  
10. TROUBLESHOOTING······································47  
11. DISASSEMBLY INSTRUCTIONS·····················60  
12. PARTS LIST······················································70  
13. OPTIONAL PARTS ····································BACK  
E1  
E2  
E3  
MSH-18NV -  
MSH-18NV -  
MSH-18NV -  
E1  
E2  
E3  
Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-  
E1  
are connected with MXZ-32NV-  
as multi system units.  
2
PART NAMES AND FUNCTIONS  
INDOOR UNIT  
E1  
E2  
E2  
E2  
E1  
E1  
E2  
E2  
E3  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
E1  
E1  
(When the front panel is open)  
E1  
E2  
E1  
E2  
E1  
E2  
MSH-07NV -  
MSH-07NV -  
MSH-09NV -  
MSH-09NV -  
MSH-12NV -  
MSH-12NV -  
E1  
E1  
E2  
E1  
E2  
MSH-07NV -  
MSH-07NV -  
MSH-09NV -  
MSH-09NV -  
MSH-12NV -  
MSH-12NV -  
E2  
E1  
E2  
E1  
E3  
E2  
MSH-18NV -  
MSH-24NV -  
E2  
MSH-24NV -  
MSH-18NV -  
MSH-18NV -  
E1  
E2  
E1  
E3  
MSH-18NV -  
MSH-24NV -  
MSH-24NV -  
MSH-18NV -  
MSH-18NV -  
OUTDOOR UNIT  
E1  
E1  
E1  
MUH-07NV -  
MUH-09NV -  
MUH-07NV -  
MUH-09NV -  
MUH-12NV -  
MUH-18NV -  
MUH-18NV -  
MUH-18NV -  
MUH-24NV -  
MUH-24NV -  
E1  
E1  
E2  
E3  
E2  
E2  
E2  
3
E1  
E1  
E1  
E1  
E2  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
MSH-18NV -  
MSH-18NV -  
REMOTE CONTROLLER  
4
E1  
E1  
MSH-07NV - (Serial number 7000201T~) MSH-09NV - (Serial number 7000201T~)  
E1  
E1  
E2  
E2  
MSH-12NV - (Serial number 7000001T~) MSH-24NV -  
E2  
MSH-07NV -  
MSH-12NV -  
MSH-24NV -  
MSH-09NV -  
E2  
E2  
MSH-18NV - (Serial number 7000001T~)  
E3  
MSH-18NV -  
5
3
SPECIFICATION  
E1  
E2  
E1  
E2  
Model  
Function  
MSH-07NV -  
Cooling  
MSH-09NV -  
Cooling  
Heating  
Heating  
Power supply  
Capacity  
Single phase,220-240V,50HzSingle phase,220-240V,50Hz  
2.2  
0.8  
2.5  
2.5  
1.1  
3.1  
kW  
Capacity  
R/h  
Dehumidification  
Air flow  
K /h INDOOR 492 OUTDOOR 1620 INDOOR 492 OUTDOOR 1620  
A
A
10  
10  
Power outlet  
3.30-3.20  
710-750  
3.15-3.05  
680-720  
4.10-4.00  
880-920  
4.30-4.10  
920-940  
Running current  
Power input  
W
A(kW)  
%
Auxiliary heater  
Power factor  
98-96  
97-96  
Electrical data  
98-98  
25  
A
25  
Starting current  
Compressor motor current  
Fan motor current  
2.80-2.70  
2.65-2.55  
3.60-3.50  
3.80-3.60  
A
A
INDOOR 0.17 OUTDOOR 0.33 INDOOR 0.17 OUTDOOR 0.33  
3.10-2.93 3.68-3.47  
2.84-2.72 3.37-3.30  
RH-135VGHT RH-174VGHT  
Coefficient of performance(C.O.P)  
Model  
Compressor  
Output  
W
650  
800  
"
C-R4.17 C-S5.75  
RC4V19-AA  
C-R3.26 C-S5.82  
RC4V19-AA  
Winding resistance(at20:)  
Indoor  
Model  
fan motor  
Outdoor  
fan motor  
"
WHT-BLK292 BLK-RED324 WHT-BLK292 BLK-RED324  
RA6V29-CB RA6V29-CB  
WHT-BLK218.0 BLK-RED423.7 WHT-BLK218.0 BLK-RED423.7  
Winding resistance(at20:)  
Model  
"
Winding resistance(at20:)  
Width  
mm  
mm  
mm  
mm  
mm  
mm  
kg  
815  
275  
183  
780  
540  
255  
8
815  
275  
183  
780  
540  
255  
8
Indoor unit  
Height  
Depth  
Width  
Height  
Depth  
Dimensions  
Weight  
Outdoor unit  
Indoor unit  
Outdoor unit  
Air direction  
Sound level  
(Hi)  
kg  
34  
34  
5
5
dB  
dB  
37  
37  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
47  
48  
rpm  
rpm  
1,100  
790-820  
4
1,100  
790-820  
4
Fan speed  
(Hi)  
Special remarks  
Fan speed  
regulator  
1
1
kg  
k"  
k"  
k"  
0.85  
10  
0.85  
10  
Refrigerant filling capacity(R-22)  
RT11(at25:)  
10  
10  
Thermistor  
RT12(at25:)  
33.18  
33.18  
RT61(at0:)  
NOTE:Test conditions  
Cooling : Indoor DB27°C / WB19°C  
Outdoor DB35°C / WB24°C  
Heating : Indoor DB20°C /WB15.5°C  
Outdoor DB 7°C / WB 6°C  
6
E1  
E2  
E1  
E2  
E3  
Model  
Function  
MSH-12NV -  
Cooling  
MSH-18NV -  
Cooling  
Heating  
Heating  
Power supply  
Single phase,220-240V,50HzSingle phase,220-240V,50Hz  
3.4  
1.6  
4.0  
5.1  
2.5  
5.4  
kW  
Capacity  
Capacity  
R/h  
Dehumidification  
Air flow  
K /h INDOOR 558 OUTDOOR 2130-2244 INDOOR 756 OUTDOOR 2142  
A
A
10  
15  
Power outlet  
5.75-5.90  
1220-1300  
5.95-6.10  
1260-1350  
9.4-9.2  
2030-2120  
9.2-9.0  
1980-2070  
Running current  
Power input  
W
A(kW)  
%
Auxiliary heater  
Power factor  
96-92  
96-92  
98-96  
98-96  
Electrical data  
A
35  
52-58  
8.76-8.56 8.56-8.36  
Starting current  
Compressor motor current  
Fan motor current  
5.21-5.36  
5.41-5.56  
A
A
INDOOR 0.17 OUTDOOR 0.37 INDOOR 0.25 OUTDOOR 0.39  
2.78-2.61 3.17-2.96  
2.51-2.41 2.73-2.61  
RH-231VHAT NH-36VMDT  
Coefficient of performance(C.O.P)  
Model  
Compressor  
Output  
W
1100  
1700  
"
C-R2.1 C-S3.9  
RC4V19-AA  
C-R1.2 C-S2.7  
RA4V27-EA  
Winding resistance(at20:)  
Indoor  
Model  
fan motor  
Outdoor  
fan motor  
"
WHT-BLK292 BLK-RED324 WHT-BLK183.8 BLK-RED250.5  
RA6V40-EC or EE RA6V50-OD or OF  
WHT-BLK130 BLK-RED134.6 WHT-BLK116.4 BLK-RED111.0  
Winding resistance(at20:)  
Model  
"
Winding resistance(at20:)  
Width  
mm  
mm  
mm  
mm  
mm  
mm  
kg  
815  
275  
183  
850  
605  
290  
8
1015  
320  
190  
850  
605  
290  
14  
Indoor unit  
Height  
Depth  
Width  
Height  
Depth  
Dimensions  
Weight  
Outdoor unit  
Indoor unit  
Outdoor unit  
Air direction  
Sound level  
(Hi)  
kg  
43  
59  
5
5
dB  
dB  
42  
42  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
50  
52  
rpm  
rpm  
1230  
780-820  
4
1180  
810-845  
4
Fan speed  
(Hi)  
Special remarks  
Fan speed  
regulator  
1
1
kg  
k"  
k"  
k"  
1.15  
10  
1.8  
Refrigerant filling capacity(R-22)  
10  
RT11(at25:)  
10  
10  
Thermistor  
RT12(at25:)  
33.18  
33.18  
RT61(at0:)  
NOTE:Test conditions  
Cooling : Indoor DB27°C / WB19°C  
Outdoor DB35°C / WB24°C  
Heating : Indoor DB20°C /WB15°.5C  
Outdoor DB 7°C / WB 6°C  
7
E1  
E2  
Model  
Function  
MSH-24NV -  
Cooling  
Heating  
Power supply  
Single phase,220-240V,50Hz  
kW  
R/h  
K /h  
A
6.0  
3.1  
6.2  
Capacity  
Capacity  
Dehumidification  
Air flow  
816  
25  
Power outlet  
A
12.6-11.7  
11.5-11.0  
Running current  
Power input  
W
2720-2750 2470-2580  
A(kW)  
%
Auxiliary heater  
Power factor  
Electrical data  
98  
A
59  
Starting current  
Compressor motor current  
Fan motor current  
A
11.73-10.83 10.63-10.13  
INDOOR 0.29 OUTDOOR 0.58  
A
2.21-2.18  
2.51-2.40  
Coefficient of performance(C.O.P)  
Model  
NH-47VMDT  
Compressor  
Output  
W
2200  
"
C-R 0.96 C-S 2.07  
Winding resistance(at20:)  
Indoor  
RA4V27-EC  
Model  
fan motor  
Outdoor  
fan motor  
"
WHT-BLK183.8 BLK-RED250.5  
Winding resistance(at20:)  
Model  
RA6V85-AA  
"
WHT-BLK62.7 BLK-YLW30.2 YLW-RED62.9  
Winding resistance(at20:)  
Width  
mm  
mm  
mm  
mm  
mm  
mm  
kg  
1015  
320  
190  
870  
850  
295  
14  
Indoor unit  
Height  
Depth  
Width  
Height  
Depth  
Dimensions  
Weight  
Outdoor unit  
Indoor unit  
Outdoor unit  
Air direction  
Sound level  
(Hi)  
kg  
72  
5
dB  
dB  
45  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
53  
rpm  
rpm  
1,260  
720-750  
4
Fan speed  
(Hi)  
Special remarks  
Fan speed  
regulator  
2
kg  
k"  
k"  
k"  
2.4  
Refrigerant filling capacity(R-22)  
10  
RT11(at25:)  
10  
Thermistor  
RT12(at25:)  
33.18  
RT61(at0:)  
NOTE:Test conditions  
Cooling : Indoor DB27°C / WB19°C  
Outdoor DB35°C / WB24°C  
Heating : Indoor DB20°C /WB15.5°C  
Outdoor DB 7°C / WB 6°C  
8
E1  
E2  
E3  
Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-  
are  
E1  
connected with MXZ-32NV-  
as multi system units.  
Model  
E1 E2  
E1 E2  
(INDOOR UNIT) MSH-09NV- (INDOOR UNIT)  
MSH-07NV-  
Function  
Cooling  
Heating  
Cooling  
Heating  
Power supply  
Single phase,220-240V,50Hz Single phase,220-240V,50Hz  
kW  
R/h  
K /h  
A
Capacity  
Capacity  
Dehumidification  
Air flow  
492  
492  
10  
10  
Power outlet  
A
0.17  
0.17  
Running current  
Power input  
W
35  
35  
A(kW)  
%
Auxiliary heater  
Power factor  
Electrical data  
94-86  
94-86  
A
Starting current  
Compressor motor current  
Fan motor current  
A
A
0.17  
0.17  
Coefficient of performance(C.O.P)  
Model  
Compressor  
Output  
W
"
Winding resistance(at20:)  
Indoor  
RC4V19-AA  
RC4V19-AA  
Model  
fan motor  
Outdoor  
fan motor  
"
WHT-BLK292 BLK-RED324 WHT-BLK292 BLK-RED324  
Winding resistance(at20:)  
Model  
"
Winding resistance(at20:)  
Width  
mm  
mm  
mm  
mm  
mm  
mm  
kg  
815  
275  
183  
815  
275  
183  
Indoor unit  
Height  
Depth  
Width  
Height  
Depth  
Dimensions  
Weight  
Outdoor unit  
8
8
Indoor unit  
Outdoor unit  
Air direction  
Sound level  
(Hi)  
kg  
5
5
dB  
dB  
37  
37  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
rpm  
rpm  
1,100  
1,100  
Fan speed  
(Hi)  
Special remarks  
4
4
Fan speed  
regulator  
kg  
k"  
k"  
k"  
Refrigerant filling capacity(R-22)  
10  
10  
10  
10  
RT11(at25:)  
Thermistor  
RT12(at25:)  
RT61(at0:)  
Please refer to Service manual OB185 for capacity.  
NOTE:Test conditions  
Cooling : Indoor DB27°C / WB19°C  
Outdoor DB35°C / WB24°C  
Heating : Indoor DB20°C /WB15.5°C  
Outdoor DB 7°C / WB 6°C  
9
E1  
E2  
E3  
Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-  
are  
E1  
connected with MXZ-32NV-  
as multi system units.  
E1 E2  
E2 E3  
Model  
MSH-12NV-  
(INDOOR UNIT)MSH-18NV-  
(INDOOR UNIT)  
Heating  
Function  
Cooling  
Heating  
Cooling  
Power supply  
Single phase,220-240V,50Hz Single phase,220-240V,50Hz  
kW  
R/h  
K /h  
A
Capacity  
Capacity  
Dehumidification  
Air flow  
558  
756  
10  
10  
Power outlet  
A
0.17  
0.28  
Running current  
Power input  
W
35  
60  
A(kW)  
%
Auxiliary heater  
Power factor  
Electrical data  
94-86  
97-89  
A
Starting current  
Compressor motor current  
Fan motor current  
A
A
0.17  
0.25  
Coefficient of performance(C.O.P)  
Model  
Compressor  
Output  
W
"
Winding resistance(at20:)  
Indoor  
RA4V19-AA  
RA4V27-EA  
Model  
fan motor  
Outdoor  
fan motor  
"
WHT-BLK292 BLK-RED324 WHT-BLK184 BLK-RED251  
Winding resistance(at20:)  
Model  
"
Winding resistance(at20:)  
Width  
mm  
mm  
mm  
mm  
mm  
mm  
kg  
815  
275  
183  
1015  
320  
190  
Indoor unit  
Height  
Depth  
Width  
Height  
Depth  
Dimensions  
Weight  
Outdoor unit  
8
14  
Indoor unit  
Outdoor unit  
Air direction  
Sound level  
(Hi)  
kg  
5
5
dB  
dB  
42  
42  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
Indoor unit  
Outdoor unit  
rpm  
rpm  
1,230  
1,180  
Fan speed  
(Hi)  
Special remarks  
4
4
Fan speed  
regulator  
kg  
k"  
k"  
k"  
Refrigerant filling capacity(R-22)  
10  
10  
10  
10  
RT11(at25:)  
Thermistor  
RT12(at25:)  
RT61(at0:)  
Please refer to Service manual OB185 for capacity.  
NOTE:Test conditions  
Cooling : Indoor DB27°C / WB19°C  
Outdoor DB35°C / WB24°C  
Heating : Indoor DB20°C /WB15.5°C  
Outdoor DB 7°C / WB 6°C  
10  
4
OUTLINES AND DIMENSIONS  
Unit: mm  
E1  
E1  
E2  
E2  
MSH-07NV -  
MSH-09NV -  
MSH-07NV -  
MSH-09NV -  
INDOOR UNIT  
E1  
E1  
E2  
E2  
MUH-07NV -  
MUH-09NV -  
MUH-07NV -  
MUH-09NV -  
OUTDOOR UNIT  
11  
Unit: mm  
E1  
E2  
MSH-12NV -  
MSH-12NV -  
INDOOR UNIT  
9.52  
E1  
E2  
MUH-12NV -  
MUH-12NV -  
OUTDOOR UNIT  
If the right/left sides or  
back side is vacant,the  
front has only to be 50cm  
unobstructed.  
12  
Unit: mm  
E1  
E1  
E2  
E2  
E3  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
INDOOR UNIT  
Indoor unit  
217  
4holes 1120  
150  
648  
995  
450  
450  
438  
352  
Wall hole [75  
Installation plate  
190  
1015  
5
Installation plate  
Liquid line [8-0.5m  
Gas linee [12-0.43m  
Insulatiion [50 O.D  
[28 I.D  
Air in  
{
Drain hose [16  
Insulattion [28  
50  
775  
190  
Air out  
Power suppply cord  
Lead too right 2m  
Lead too left 1m  
17.5  
56  
E1  
E2  
E3  
MUH-18NV -  
MUH-18NV -  
MUH-18NV -  
OUTDOOR UNIT  
If the right/left sides or  
back side is vacant,the  
front has only to be 50cm  
unobstructed.  
13  
E1  
E2  
MUH-24NV-  
MUH-24NV-  
Unit : mm (inch)  
4 5  
5 3  
1 5 0  
2 0 0  
2 5 m a x .  
8 0  
5 0 0  
1 7  
8 5 0 ( 3 3 - 7 / 1 6 )  
5 5 3  
4 5  
4 2  
3 6 2 ( 1 4 - 1 / 4 )  
3 3 0 ( 1 3 ) 1 5  
2 7 . 5 3 9 . 5  
3 5 2  
3 3 7  
1 7  
4 0 3  
5 2 4  
1 7 9  
4 4 1  
3 3  
2 3  
2 0 0  
1 3 8  
14  
5
WIRING DIAGRAM  
MODELS WIRING DIAGRAM  
E1  
MSH-07NV -  
MSH-09NV -  
E1  
INDOOR UNIT  
~
~/N  
FOR MULTI SYSTEM  
L
3
2
N
12VDC  
TO OUTDOOR  
UNIT  
CONNECTING  
;
SYMBOL  
C11  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
TERMINAL BLOCK  
VANE MOTOR  
INDOOR FAN CAPACITOR  
FUSE(93:)  
VARISTOR  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
CONTACTOR  
F12  
MV  
FUSE(3.15A)  
SOLID STATE RELAY  
F11  
RT12  
SR11  
INDOOR FAN MOTOR  
MF  
52C  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E1  
MUH-07NV -  
MUH-09NV -  
MODELS WIRING DIAGRAM  
E1  
OUTDOOR UNIT  
SYMBOL  
NAME  
SYMBOL  
MF  
NAME  
SYMBOL  
X62  
NAME  
COMPRESSOR CAPACITOR  
OUTDOOR FAN MOTOR CAPACITOR  
CONTACTOR  
OUTDOOR FAN MOTOR  
VARISTOR  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
DC/DC CONVERTER  
C1  
C65  
52C  
F61  
MC  
NR61  
RT61  
SR61  
TB  
21S4  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
IC881  
FUSE(2A)  
COMPRESSOR(INNER THERMOSTAT)  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
15  
E1  
MODEL WIRING DIAGRAM  
MSH-12NV -  
INDOOR UNIT  
~
~/N  
FOR MULTI SYSTEM  
L
3
2
N
12VDC  
TO OUTDOOR  
UNIT  
CONNECTING  
;
SYMBOL  
C11  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
TERMINAL BLOCK  
VANE MOTOR  
INDOOR FAN CAPACITOR  
FUSE(93:)  
VARISTOR  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
CONTACTOR  
F12  
MV  
FUSE(3.15A)  
SOLID STATE RELAY  
F11  
RT12  
SR11  
INDOOR FAN MOTOR  
MF  
52C  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E1  
MODEL WIRING DIAGRAM  
MUH-12NV -  
OUTDOOR UNIT  
SYMBOL  
NAME  
COMPRESSOR CAPACITOR  
SYMBOL  
MF  
NAME  
SYMBOL  
X62  
NAME  
OUTDOOR FAN MOTOR  
VARISTOR  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
DC/DC CONVERTER  
C1  
C65  
52C  
F61  
MC  
OUTDOOR FAN MOTOR CAPACITOR  
CONTACTOR  
NR61  
RT61  
SR61  
TB  
21S4  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
IC881  
FUSE(2A)  
COMPRESSOR(INNER THERMOSTAT)  
NOTE:1. Use copper conductors only.(For field wiring)  
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
16  
E1  
MSH-18NV -  
MODEL WIRING DIAGRAM  
INDOOR UNIT  
SYMBOL  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
INDOOR FAN CAPACITOR  
FUSE(93:)  
VARISTOR  
TERMINAL BLOCK  
SURGE ABSORBER  
DC/DC CONVERTER  
C11  
F12  
F11  
MF  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
HYBRID IC  
DSAR  
HIC1  
FUSE(3.15A)  
RT12  
IC141  
52C  
INDOOR FAN MOTOR  
VANE MOTOR  
CONTACTOR  
MV  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E1  
MUH-18NV -  
MODEL WIRING DIAGRAM  
OUTDOOR UNIT  
SYMBOL  
NAME  
COMPRESSOR CAPACITOR  
SYMBOL  
MF  
NAME  
SYMBOL  
X62  
NAME  
OUTDOOR FAN MOTOR  
VARISTOR  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
C1  
C65  
DSAR  
F61  
OUTDOOR FAN MOTOR CAPACITOR  
SURGE ABSORBER  
FUSE(2A)  
NR61  
RT61  
SR61  
TB  
21S4  
52C  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
COMPRESSOR<INNER THERMOSTAT>  
MC  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
17  
E1  
MSH-24NV -  
MODEL WIRING DIAGRAM  
TB  
220-240V~  
INDOOR UNIT  
3
2
RED  
CN  
RT12  
RT11  
112  
F12  
220-240V~  
HIC1  
WHT  
IC141  
CN  
111  
L
NF  
BLU2  
1
TO OUTDOOR  
UNIT  
BLU  
3
4
BRN  
3
BRN  
4
CN  
121  
CN201  
52C  
YLW  
GRY  
WHT  
RED  
BLK  
N
CONNECTING  
3
BLU  
3
TRANS  
CN211  
1
MF  
BLU  
4
2
1
WHT  
F11  
POWER  
SUPPLY  
CORD  
CN  
151  
CN  
101  
CN  
102  
ELECTRONIC CONTROL P.C BOARD  
~/N 220-240V  
5
50Hz  
3
3
MV  
DISPLAY  
RECEIVER  
P.C.BOARD  
CIRCUIT BREAKER  
GRN/YLW  
P.C.BOARD  
REMOTE  
CONTROLLER  
SYMBOL  
C11  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
TERMINAL BLOCK  
DC/DC CONVERTER  
NOISE FILTER  
INDOOR FAN MOTOR CAPACITOR  
FUSE(93:)  
VARISTOR  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
HYBRID IC  
F12  
HIC1  
NF  
FUSE(3.15A)  
F11  
RT12  
IC141  
52C  
INDOOR FAN MOTOR  
VANE MOTOR  
MF  
CONTACTOR  
MV  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E1  
MUH-24NV -  
MODEL WIRING DIAGRAM  
RT61  
X1  
5
3
OUTDOOR UNIT  
6
5
4
3
2
21S4  
YLW 1  
YLW  
BLK  
WHT  
ORN  
BRN  
BLK  
WHT  
ORN  
RED RED  
MF  
1
2
3
4
CN661  
CN721  
CN711  
C2  
1
CN730  
X62  
TB  
3
2
1
3
12VDC ❈  
RED  
IC881  
WHT  
220-240V~2 WHT  
F
ORN  
RED  
TB2  
BLU  
7
8
RED  
BLU  
X1  
TRANS  
26F1  
N
TAB20  
YLW  
52C  
DEICER  
P.C. BOARD  
52C1  
3
4 ❈  
VLT CR  
WHT  
CZ  
52C1  
YLW  
WHT  
WHTWHT  
C
2
1
C1  
MC  
BLU  
R
S
RED  
BLK  
SYMBOL  
C1  
NAME  
SYMBOL  
NAME  
SYMBOL  
X62  
NAME  
SYMBOL  
NAME  
OUTDOOR FAN MOTOR  
COMPRESSOR CAPACITOR  
OUTDOOR FAN MOTOR CAPACITOR  
SURGE ABSORBER 1  
FUSE(2A)  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
FUSE(2A)  
MF  
NR61  
RT61  
F
<INNER THERMOSTAT>  
VARISTOR  
THERMOSTAT (AIR FLOW CONTROL)  
DC/DC CONVERTER  
C2  
21S4  
52C  
26F1  
IC881  
CR  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
DSAR  
F61  
COMPRESSOR CONTACTOR  
FAN MOTOR RELAY  
SURGE ABSORBER 2  
SURGE ABSORBER 3  
SR61  
52C1  
X1  
COMPRESSOR<INNER THERMOSTAT>  
MC  
TB. TB2  
CZ  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
18  
E2  
E2  
E2  
MSH-07NV - MSH-09NV - MSH-12NV -  
MODELS WIRING DIAGRAM  
INDOOR UNIT  
TO OUTDOOR  
UNIT  
TB  
SR11  
L
CN  
BRN  
RT12  
RT11  
112  
CONNECTING  
BRN  
HIC1  
CN  
111  
3
12VDC  
RED  
BLU  
F12  
BLK  
CN201  
3
1
2
1
2
3
4
5
6
2
220-240V~  
WHT  
3
BLU  
GRY  
YLW  
NR11  
C11  
CN  
121  
52C  
3
2
1
4
N
BLU  
TRANS  
BLU  
MF  
BRN  
3
2
1
WHT  
RED  
BLU  
F11  
1
CN  
122  
POWER  
SUPPLY  
CORD  
CN211  
CN  
151  
LD101  
GUARD  
PLATE  
ELECTRONIC CONTROL P.C BOARD  
~/N 220-240V  
50Hz  
5
5
POWER MONITOR,  
RECEIVER  
MV  
CIRCUIT BREAKER  
P.C.BOARD  
FOR MULTI SYSTEM  
L
3
TO OUTDOOR12VDC  
UNIT  
2
REMOTE  
N
CONNECTING  
CONTROLLER  
SYMBOL  
C11  
NAME  
SYMBOL  
NAME  
SYMBOL  
TERMINAL BLOCK  
TB  
NAME  
INDOOR FAN MOTOR CAPACITOR  
FUSE(93:)  
VARISTOR  
NR11  
RT11  
RT12  
52C  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
CONTACTOR  
DC/DC CONVERTER  
SOLID STATE RELAY  
VANE MOTOR  
F12  
HIC1  
SR11  
MV  
FUSE(3.15A)  
F11  
INDOOR FAN MOTOR  
MF  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E2  
E2  
MUH-07NV -  
MUH-09NV -  
MODELS WIRING DIAGRAM  
21S4  
OUTDOOR UNIT  
RT61  
CN661  
CN721  
TB  
3
MF  
X62  
F61  
12VDC  
RED  
SR61  
1
CN730  
RED  
WHT  
2
1
2
3
4
220-240V~  
C65  
IC881  
NR61  
TRANS  
N
BLU  
WHT  
BLK  
TAB20  
BLU  
52C  
4 3  
CN711  
X62  
DEICER P.C. BOARD  
WHT  
C
C1  
MC  
GRN/YLW  
RED  
R
S
BLK  
SYMBOL  
C1  
NAME  
NAME  
NAME  
NAME  
SYMBOL  
SYMBOL  
X62  
SYMBOL  
C65  
OUTDOOR FAN MOTOR  
COMPRESSOR CAPACITOR  
FUSE(2A)  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
FAN MOTOR CAPACITOR  
DC/DC CONVERTER  
TERMINAL BLOCK  
MF  
<INNER THERMOSTAT>  
VARISTOR  
F61  
NR61  
RT61  
21S4  
52C  
IC881  
TB  
COMPRESSOR<INNER THERMOSTAT>  
SOLID STATE RELAY  
DEFROST THERMISTOR  
MC  
SR61  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
19  
E2  
MUH-12NV -  
MODEL WIRING DIAGRAM  
OUTDOOR UNIT  
21S4  
RT61  
TB  
MF  
12VDC  
3
RED  
WHT  
BLU  
CN661  
CN721  
1
X62  
CN730  
RED  
WHT  
RED  
1
2
3
4
1
2
3
4
SR61  
220-240V~ 2  
N
ORN  
WHT  
BLK  
BLK  
TRANS  
CN711  
52C  
TAB20  
X62  
3
4
DEICER P.C.BOARD  
GRN/YLW  
C
WHT  
C1  
BLU  
RED  
BLK  
S MC  
R
SYMBOL  
C1  
NAME  
NAME  
NAME  
NAME  
SYMBOL  
SYMBOL  
X62  
SYMBOL  
C65  
OUTDOOR FAN MOTOR  
COMPRESSOR CAPACITOR  
FUSE(2A)  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
FAN MOTOR CAPACITOR  
DC/DC CONVERTER  
TERMINAL BLOCK  
MF  
<INNER THERMOSTAT>  
VARISTOR  
F61  
NR61  
RT61  
21S4  
52C  
IC881  
TB  
COMPRESSOR<INNER THERMOSTAT>  
SOLID STATE RELAY  
DEFROST THERMISTOR  
MC  
SR61  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
20  
E2  
MSH-18NV -  
MODEL WIRING DIAGRAM  
INDOOR UNIT  
~/N  
FOR MULTI SYSTEM  
L
3
2
N
12VDC  
TO OUTDOOR  
UNIT  
CONNECTING  
;
SYMBOL  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
INDOOR FAN CAPACITOR  
FUSE(93:)  
VARISTOR  
TERMINAL BLOCK  
SURGE ABSORBER  
DC/DC CONVERTER  
C11  
F12  
F11  
MF  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
HYBRID IC  
DSAR  
HIC1  
FUSE(3.15A)  
RT12  
IC141  
52C  
INDOOR FAN MOTOR  
VANE MOTOR  
CONTACTOR  
MV  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E2  
MUH-18NV -  
MODEL WIRING DIAGRAM  
OUTDOOR UNIT  
SYMBOL  
NAME  
COMPRESSOR CAPACITOR  
SYMBOL  
MF  
NAME  
SYMBOL  
X62  
NAME  
OUTDOOR FAN MOTOR  
VARISTOR  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
C1  
C65  
DSAR  
F61  
OUTDOOR FAN MOTOR CAPACITOR  
SURGE ABSORBER  
FUSE(2A)  
NR61  
RT61  
SR61  
TB  
21S4  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
52C  
DC/DC CONVERTER  
IC881  
COMPRESSOR<INNER THERMOSTAT>  
MC  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
21  
E2  
MSH-24NV -  
MODEL WIRING DIAGRAM  
INDOOR UNIT  
TB  
220-240V~  
3
RED  
WHT  
CN  
RT12  
RT11  
112  
F12  
220-240V~ 2  
HIC1  
IC141  
CN  
111  
L
TO OUTDOOR  
UNIT  
NF  
BLU2  
1
3
BLU  
BRN  
3
BRN  
4
3
CN  
121  
CN201  
3
1
52C  
YLW  
GRY  
WHT  
RED  
BLK  
4
CONNECTING  
N
BLU  
BLU  
TRANS  
CN211  
MF  
4
2
1
F11  
WHT  
POWER  
SUPPLY  
CORD  
CN  
CN  
101  
CN  
102  
151 ELECTRONIC CONTROL P.C BOARD  
5
~/N 220-240V  
50Hz  
3
3
MV  
RECEIVER  
DISPLAY  
P.C.BOARD  
P.C.BOARD  
CIRCUIT BREAKER  
GRN/YLW  
REMOTE  
CONTROLLER  
SYMBOL  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
INDOOR FAN CAPACITOR  
FUSE(93:)  
VARISTOR  
TERMINAL BLOCK  
NOISE FILTER  
C11  
F12  
F11  
MF  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
HYBRID IC  
NF  
FUSE(3.15A)  
DC/DC CONVERTER  
RT12  
IC141  
52C  
HIC1  
INDOOR FAN MOTOR  
VANE MOTOR  
CONTACTOR  
MV  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E2  
MUH-24NV -  
MODEL WIRING DIAGRAM  
RT61  
OUTDOOR UNIT  
X1  
6
5
4
21S4  
1
YLW  
BLK  
YLW  
BLK  
5
BRN  
3
WHT WHT  
MF  
3
ORN  
RED  
ORN  
RED  
CN661  
CN721  
2
1
CN711 1 2 3 4  
C2  
CN730  
X62  
TB  
3
3
2
1
12VDC  
RED  
IC881  
TRANS  
WHT  
2
220-240V~  
WHT F  
RED  
RED 8  
BLU  
ORN  
7
X1  
TB2  
26F1  
N
TAB20  
BLU  
52C  
YLW  
A2  
52C1  
CR  
DEICER  
A1  
3 4  
P.C. BOARD  
VLT  
WHT  
YLW  
CZ  
WHT  
52C1  
WHT  
WHT  
C
1
2
MC  
S
R
BLU  
C1  
RED  
BLK  
SYMBOL  
NAME  
SYMBOL  
MF  
NAME  
SYMBOL  
X62  
NAME  
COMPRESSOR CAPACITOR  
FAN MOTOR CAPACITOR  
SURGE ABSORBER 1  
SURGE ABSORBER 2  
SURGE ABSORBER 3  
FUSE(2A)  
OUTDOOR FAN MOTOR  
VARISTOR  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
C1  
C2  
NR61  
RT61  
SR61  
TB,TB2  
F
21S4  
52C  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
FUSE(2A)  
DSAR  
CR  
COMPRESSOR CONTACTOR  
DC/DC CONVERTER  
FAN MOTOR RELAY  
52C1  
IC881  
X1  
CZ  
F61  
MC  
COMPRESSOR<INNER THERMOSTAT>  
THERMOSTAT (AIR FLOW CONTROL)  
26F1  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
22  
E3  
MSH-18NV -  
MODEL WIRING DIAGRAM  
TO OUTDOOR  
TB  
INDOOR UNIT  
UNIT  
L
3
BRN  
CN  
112  
RT12  
CONNECTING  
HIC1  
BRN  
IC141  
12VDC  
RED  
BLU  
F12  
3
BRN  
CN  
121  
4
2
2
220-240V~  
WHT  
BLU 1  
YLW  
GRY  
WHT  
RED  
BLK  
52C  
CN201  
3
1
3
CN211  
N
TRANS  
MF  
BLU  
BLU  
4
2
1
CN  
111  
BLU  
BRN  
F11  
LD1  
POWER  
SUPPLY  
CORD  
CN  
151  
CN CN  
102  
RT11  
101  
ELECTRONIC CONTROL P.C BOARD  
~/N 220-240V  
50Hz  
5
3
3
MV  
GRN/YLW  
DISPLAY  
RECEIVER  
P.C.BOARD  
CIRCUIT BREAKER  
P.C.BOARD  
FOR MULTI SYSTEM  
L
12VDC 3  
TO OUTDOOR  
UNIT  
2
REMOTE  
N
CONTROLLER  
CONNECTING  
SYMBOL  
NAME  
SYMBOL  
NR11  
RT11  
NAME  
SYMBOL  
TB  
NAME  
INDOOR FAN CAPACITOR  
FUSE(93:)  
VARISTOR  
TERMINAL BLOCK  
C11  
F12  
F11  
MF  
ROOM TEMPERATURE THERMISTOR  
INDOOR COIL THERMISTOR  
HYBRID IC  
SURGE ABSORBER  
DC/DC CONVERTER  
DSAR  
HIC1  
FUSE(3.15A)  
RT12  
IC141  
52C  
INDOOR FAN MOTOR  
VANE MOTOR  
CONTACTOR  
MV  
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.  
2. Use copper conductors only.(For field wiring)  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
E3  
MUH-18NV -  
MODEL WIRING DIAGRAM  
OUTDOOR UNIT  
21S4  
52C  
RT61  
TB  
MF  
CN730  
1
12VDC  
3
RED  
WHT  
CN661  
F61  
CN721  
CN720  
SR61  
X62  
RED  
WHT  
RED  
1
2
3
4
1
2
3
4
220-240V~2  
N
ORN  
WHT  
BLK  
TAB21  
BLU  
BLK  
TRANS  
CN711  
X62  
TAB20  
DEICER P.C.BOARD  
52C  
WHT  
WHT NO  
BLU  
COM  
GRN/YLW  
C
C1  
RED  
BLK  
MC  
S
R
SYMBOL  
NAME  
SYMBOL  
MF  
NAME  
SYMBOL  
X62  
NAME  
COMPRESSOR CAPACITOR  
OUTDOOR FAN MOTOR CAPACITOR  
SURGE ABSORBER  
OUTDOOR FAN MOTOR  
VARISTOR  
REVERSING VALVE COIL RELAY  
REVERSING VALVE COIL  
CONTACTOR  
C1  
C65  
DSAR  
F61  
NR61  
RT61  
SR61  
TB  
21S4  
DEFROST THERMISTOR  
SOLID STATE RELAY  
TERMINAL BLOCK  
52C  
FUSE(2A)  
DC/DC CONVERTER  
IC881  
COMPRESSOR<INNER THERMOSTAT>  
MC  
NOTE:1. Use copper conductors only.(For field wiring)  
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.  
3. Symbols below indicate.  
: Terminal block,  
: Connector  
1.Slide the sleeve.  
2.Pull the wire while  
pushing the locking  
lever.  
4. “”show the terminals with a lock mechanism, so they cannot be removed when you pull  
the lead wire.  
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.  
23  
6
REFRIGERANT SYSTEM DIAGRAM  
Unit:mm  
E1  
E1  
MSH-07NV -  
MSH-07NV -  
MUH-07NV -  
MUH-07NV -  
E2  
E2  
Refrigerant pipe [ 9.52  
(Option)  
Muffler  
Reversing valve  
(4-way valve)  
INDOOR UNIT  
OUTDOOR UNIT  
(with heat insulator)  
Indoor coil  
Indoor  
Outdoor  
heat  
exchanger  
thermistor  
RT12  
heat  
exchanger  
Stop valve  
(with service  
port)  
Strainer  
Defrost  
thermistor  
RT61  
Flared connection  
Room temperature  
thermistor  
Capillary tube  
[1.4x800 (2 pcs)  
RT11  
Accumulator  
Capillary tube  
[1.6x750  
Check  
valve  
Flared connection  
Reversing valve coil  
(4-way valve coil)  
heating ON  
Strainer  
Stop valve  
Capillary tube  
[1.4x850  
Refrigerant pipe [6.35  
(Option)  
cooling OFF  
Refrigerant flow in cooling  
Refrigerant flow in heating  
(with heat insulator)  
Unit:mm  
E1  
E1  
MUH-09NV -  
MSH-09NV -  
MSH-09NV -  
MSH-09NV -  
E2  
E2  
Muffler  
Refrigerant pipe [9.52  
(Option)  
Reversing valve  
(4-way valve)  
OUTDOOR UNIT  
INDOOR UNIT  
(with heat insulator)  
Indoor coil  
Indoor  
thermistor  
RT12  
Outdoor  
heat  
exchanger  
heat  
exchanger  
Stop valve  
(with service  
port)  
Strainer  
Defrost  
thermistor  
RT61  
Flared connection  
Room temperature  
thermistor  
Capillary tube  
[1.4x800 (2 pcs)  
RT11  
Accumulator  
Capillary tube  
[1.6x400  
Check  
valve  
Flared connection  
Reversing valve coil  
(4-way valve coil)  
heating ON  
Strainer  
Stop valve  
Capillary tube  
[1.6x1300  
Refrigerant pipe [6.35  
(Option)  
cooling OFF  
Refrigerant flow in cooling  
Refrigerant flow in heating  
(with heat insulator)  
24  
Unit:mm  
E1  
E1  
E2  
MUH-12NV -  
MUH-12NV -  
MSH-12NV -  
MSH-12NV -  
E2  
Reversing valve  
(4-way valve)  
Refrigerant pipe [12.7  
(Optional)  
OUTDOOR UNIT  
INDOOR UNIT  
(with heat insulator)  
Muffler  
Indoor  
heat  
exchanger  
Indoor coil  
thermistor  
RT12  
Outdoor  
heat  
exchanger  
Stop valve  
(with service port)  
Flared connection  
Defrost  
thermistor  
RT61  
RT11  
Room temperature  
thermistor  
RT11  
Accumulator  
Compressor  
Capillary tube  
[1.6x400  
Flared connection  
Capillary tube  
[1.4x500  
Reversing valve coil  
(4-way valve coil)  
heating ON  
Strainer  
cooling OFF  
Stop valve  
Refrigerant pipe  
(Option) [6.35  
Refrigerant flow in cooling  
Check  
valve  
(with heat insulator)  
Refrigerant flow in heating  
Unit:mm  
E1  
MUH-18NV -  
MUH-18NV -  
MUH-18NV -  
E1  
MSH-18NV -  
MSH-18NV -  
MSH-18NV -  
E2  
E2  
E3  
E3  
Reversing valve  
(4- way valve)  
OUTDOOR UNIT  
Refrigerant pipe [15.88  
(Option)  
INDOOR UNIT  
Muffler  
(with heat insulator)  
Indoor coil  
Indoor  
heat  
exchanger  
thermistor  
RT12  
Strainer  
Stop valve  
(with service port)  
Outdoor  
heat  
exchanger  
Distributor  
Defrost  
thermistor  
RT61  
Flared connection  
Room temperature  
thermistor  
RT11  
Accumulator  
Compressor  
Capillary tube  
[1.6x750  
(2 pcs)  
Flared connection  
Capillary tube  
[2.0X800  
Strainer  
Reversing valve coil  
(4-way valve coil)  
heating ON  
Stop valve  
Refrigerant pipe  
(Option) [6.35  
cooling OFF  
Check  
valve  
(with heat insulator)  
Refrigerant flow in cooling  
Refrigerant flow in heating  
25  
Unit:mm  
E1  
E2  
E1  
E2  
MUH-24NV -  
MUH-24NV -  
MSH-24NV -  
MSH-24NV -  
Reversing valve  
(4- way valve)  
OUTDOOR UNIT  
INDOOR UNIT  
Refrigerant pipe [15.88  
(Option)  
(with heat insulator)  
Muffler  
Indoor coil  
thermistor  
RT12  
Strainer  
Indoor  
heat  
Ball valve  
exchanger  
Outdoor  
heat  
Distributor  
Flared connection  
exchanger  
Room temperature  
thermistor  
RT11  
Accumulator  
Defrost  
thermistor  
RT61  
Compressor  
Discharge pressure  
regurator open  
23.5 kgf/J  
Flared connection  
Capillary tube  
[1.6X350  
Check  
valve  
Strainer  
Ball valve  
with Service port  
Capillary tube  
[2.4X200  
Refrigerant pipe  
(Option) [9.52  
(with heat insulator)  
Check  
valve  
Refrigerant flow in cooling  
Refrigerant flow in heating  
Capillary tube  
[2.0X350  
26  
MAX. REFRIGERANT PIPING LENGTH  
Refrigerant piping  
Piping size O.D : mm  
Length of connecting pipe : m  
Outdoor unit  
Models  
Max. length : m  
A
Indoor unit  
Gas  
9.52  
12.7  
Liquid  
MSH-07NV - E1  
MSH-09NV - E1  
MSH-07NV - E2  
MSH-09NV - E2  
10  
15  
MSH-12NV - E1  
MSH-12NV - E2  
6.35  
9.52  
0
0.43  
MSH-18NV - E1  
MSH-18NV - E2  
MSH-18NV - E3  
MSH-24NV - E1  
MSH-24NV - E2  
15.88  
MAX. HEIGHT DIFFERENCE  
ADDITIONAL REFRIGERANT CHARGE(R-22 : g)  
Refrigerant piping length (one way)  
10m  
Outdoor unit precharged  
Models  
7m  
15m  
(up to 7m)  
MSH-07NV - E1  
MSH-09NV - E1  
MSH-07NV - E2  
MSH-09NV - E2  
MSH-12NV - E1  
MSH-12NV - E2  
850  
0
150  
1150  
1800  
E1  
MSH-18NV -  
400  
E2  
MSH-18NV -  
E3  
MSH-18NV -  
Calculation : Xg=50g/m (A-7)m  
Refrigerant piping length (one way)  
10m  
Outdoor unit precharged  
(up to 7m)  
Models  
7m  
0
15m  
520  
E1  
E2  
MSH-24NV -  
MSH-24NV -  
2400  
195  
Calculation : Xg=65g/m (A-7)m  
27  
EVACUATION PROCEDURES(AIR PURGE)  
Connect the refrigerant pipes (both the liquid and gas pipes)  
between the indoor and the outdoor units.  
Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.(The stop valve will not  
work in its initial state fresh out of the factory (totally closed with cap on))  
When vacuuming  
Connect the gage manifold valve and the vacuum pump to  
the service port of the stop valve on the liquid pipe side of the  
outdoor unit.  
Run the vacuum pump for more than 15 minutes and at this  
time confirm that the pressure gage indicates 0.1 Mpa.  
Check the vacuum with the gage manifold valve, then close  
the gage manifold valve, and stop the vacuum pump.  
Leave it as it is for one or two minutes. Make sure the pointer  
of the gage manifold valve remains in the same position.  
Remove the gage manifold valve quickly from the service port of the stop valve.  
After refrigerant pipes are connected and evacuated, fully open all stop valves on gas and liquid pipe sides.  
Operating without fully opening lowers the performance and causes trouble.  
Pipe length :  
7m maximum  
No gas charge  
is needed  
Pipe length  
exceeding 7m  
Charge the prescribed  
amount of gas  
Tighten the cap to the service port to obtain the initial status.  
Retighten the cap.  
Leak test  
28  
7
PERFORMANCE CURVES  
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,  
since operating conditions vary according to the areas where these units are installed. The following information has been pro-  
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.  
(1) GUARANTEED VOLTAGE  
Rated voltage : ±10% (198 ~ 264V  
),50Hz  
(2) AIR FLOW  
Air flow should be set at MAX.  
(3) MAIN READINGS  
(1) Indoor intake air wet-bulb temperature :  
(2) Indoor outlet air wet-bulb temperature :  
(3) Outdoor intake air dry-bulb temperature :  
(4) Total input:  
(5) Indoor intake air dry-bulb temperature :  
(6) Outdoor intake air wet-bulb temperature :  
(7) Total input :  
°CWB  
°CWB  
°CDB  
W
°CDB  
°CWB  
W
Cooling  
Heating  
}
}
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the  
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.  
How to measure the indoor air wet-bulb/dry-bulb temperature difference  
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets  
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air  
speed is high.  
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.  
Cover the thermometers to prevent direct rays of the sun.  
3. Check that the air filter is cleaned.  
4. Open windows and doors of room.  
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.  
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.  
7. 10 minutes later, measure temperature again and check that the temperature does not change.  
OUTDOOR UNIT  
INDOOR UNIT  
Wet-and dry-bulb  
thermometers  
Wet-and dry-bulb  
thermometers  
29  
12.0  
11.4  
10.4  
9.4  
14.0  
12.7  
11.5  
10.3  
9.2  
9.1  
8.5  
7.6  
8.1  
19.9  
25.5 28.7  
28.0  
25.9  
23.7  
21.6  
28.0  
25.9  
23.7  
21.6  
23.5 26.5  
21.6 24.3  
19.6 22.5  
18.4  
16.9  
15.3  
13.8  
12.3  
10.7  
9.2  
17.6 19.9  
15.6 17.7  
13.7 15.5  
19.4  
17.2  
15.1  
19.4  
17.2  
15.1  
11.7 13.2  
12.9  
12.9  
NOTE:The above curves are for the heating operation without any frost.  
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT  
COOL operation  
Both indoor and outdoor unit are under the same temperature/humidity condition.  
Relative humidity(%)  
Dry-bulb temperature  
20  
25  
30  
50  
60  
70  
Air flow should be set at MAX.  
The unit of pressure has been changed to MPa on the international system of units(SI unit system).  
The conversion factor is : 1(MPa • G) =10.2(kgf/f• G)  
(kgf/F•G)(MPa•G)  
E1  
E2  
E1  
E2  
MUH-07NV -  
MUH-07NV -  
0.7  
7
220V  
0.6  
6
240V  
220/240V  
0.5  
5
0.4  
4
0.3  
3
Ambient temperature(˚C)  
Ambient humidity(%)  
Ambient temperature(˚C)  
Ambient humidity(%)  
30  
E1  
E2  
(kgf/F•G)(MPa•G)  
E1  
E2  
MUH-09NV -  
MUH-09NV -  
0.7  
7
220V  
0.6  
6
240V  
0.5  
5
220/240V  
0.4  
0.3  
4
3
Ambient temperature(˚C)  
Ambient humidity(%)  
Ambient temperature(˚C)  
Ambient humidity(%)  
E1  
E2  
(kgf/F•G)(MPa•G)  
E1  
E2  
MUH-12NV -  
MUH-12NV -  
0.7  
7
220V  
240V  
0.6  
6
0.5  
5
220/240V  
0.4  
4
0.3  
3
Ambient temperature(˚C)  
Ambient humidity(%)  
Ambient temperature(˚C)  
Ambient humidity(%)  
E1  
E2  
E3  
E1  
E2  
E3  
(kgf/F•G)(MPa•G) MUH-18NV -  
MUH-18NV -  
0.7  
7
220/240V  
0.6  
6
220V  
0.5  
0.4  
5
4
240V  
0.3  
0.2  
3
2
Ambient temperature(˚C)  
Ambient humidity(%)  
Ambient temperature(˚C)  
Ambient humidity(%)  
E1  
E2  
(kgf/F•G)(MPa•G)  
E1  
E2  
MUH-24NV -  
MUH-24NV -  
0.7  
7
13  
12  
220V  
220V  
0.6  
6
240V  
0.5  
0.4  
5
4
0.3  
0.2  
3
2
Ambient temperature(˚C)  
Ambient humidity(%)  
Ambient temperature(˚C)  
Ambient humidity(%)  
31  
HEAT operation  
Outdoor:Dry bulb temperature 7,15,20°C  
Wet bulb temperature 6,12,14.5°C  
Condition indoor:Dry bulb temperature 20.0°C  
Wet bulb temperature 14.5°C  
E1  
E2  
E1  
E2  
MUH-12NV -  
MUH-07NV -  
220V  
240V  
220V  
240V  
Ambient temperature(˚C)  
Ambient temperature(˚C)  
E1  
E2  
MUH-09NV -  
E1  
E2  
E3  
MUH-18NV -  
220V  
240V  
220V  
240V  
Ambient temperature(˚C)  
Ambient temperature(˚C)  
E1  
E2  
MUH-24NV -  
13  
12  
11  
10  
9
220V  
240V  
Ambient temperature(˚C)  
32  
8
MICROPROCESSOR CONTROL  
Wireless remote controller  
E1  
E1  
E2  
E2  
E1  
E1  
E2  
E2  
E1  
MSH-07NV -  
MSH-18NV -  
MSH-07NV -  
MSH-18NV -  
MSH-09NV -  
MSH-24NV -  
MSH-09NV -  
MSH-24NV -  
MSH-12NV -  
E2  
E3  
MSH-12NV -  
MSH-18NV -  
Once the controls are set, the same operation mode can be  
repeated by simply turning the OPERATE/STOP button ON.  
Indoor unit receives the signal with a beep tone.  
When the system turns off, 3-minute time delay will operate to  
protect system from overload and compressor will not restart  
for 3 minutes.  
8-1. “I FEEL CONTROL” (  
) OPERATION  
(1) Press OPERATE/STOP button on the remote controller.  
OPERATION INDICATOR lamp of the indoor unit will turn  
on with a beep tone.  
(2) Press OPERATION SELECT button to set “I FEEL CON-  
TROL”(  
). Then a beep tone is heard.  
(3) The operation mode is determined by the initial room  
temperature at start-up of the operation.  
Initial room temperature  
Mode  
COOL mode of  
"I FEEL CONTROL"  
more than 25:  
DRY mode of  
"I FEEL CONTROL"  
23: to 25:  
HEAT mode of  
"I FEEL CONTROL"  
less than 23:  
Once the mode is fixed, the mode will not change by  
room temperature afterwards.  
Under the ON-TIMER (  
) operation, mode is deter-  
mined according to the room temperature as the opera-  
tion starts.  
When the system is stopped with the OPERATE/STOP  
button on the remote controller, and restarted within 2  
hours in “I FEEL CONTROL” (  
) mode, the system  
operates in previous mode automatically regardless of  
the room temperature.  
Example  
Restart  
COOL mode of  
“I FEEL CONTROL”  
Previous operation  
COOL mode of  
“I FEEL CONTROL”  
or COOL mode  
When the system is restarted after 2 hours, the operation  
mode is determined by the initial room temperature at  
start-up of the operation.  
Restart  
Example  
COOL or DRY or  
HEAT mode of “I FEEL  
CONTROL” that deter-  
mined by initial room  
temperature at start-up  
of the operation.  
Previous operation  
COOL mode of  
“I FEEL CONTROL”  
or COOL mode  
INDOOR UNIT DISPLAY SECTION  
33  
(4) The initial set temperature is decided by the initial room temperature.  
Model  
Initial room temperature  
Initial set temperature  
26:or more  
24:  
COOL mode of  
1  
"I FEEL CONTROL"  
Initial room temperature  
26: or less  
23: or 25:  
23: or less  
minus 2:  
Initial room temperature  
minus 2:  
DRY mode of  
"I FEEL CONTROL"  
HEAT mode of  
"I FEEL CONTROL"  
26:  
1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless of  
the initial set temperature.  
The set temperature is calculated by the previous set temperature.  
(5) TEMPERATURES buttons  
In “I FEEL CONTROL” (  
) mode, set temperature is decided by the microprocessor based on the room temperature.  
In addition, set temperature is controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.  
Each time the TOO WARM or TOO COOL button is pressed,the indoor unit receives the signal and emits a beep tone.  
Fuzzy control  
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering  
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or  
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.  
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.  
TOO  
COOL  
To raise the set temperature 1~2 degrees(°C)  
TOO  
WARM  
To lower the set temperature 1~2 degrees(°C)  
34  
— COOL mode of “I FEEL CONTROL” —  
ON  
ON  
OFF  
OFF  
ON  
Compressor and  
outdoor fan motor  
Run continuously in cooling mode  
Indoor fan motor  
NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL”  
There are two types of controls in coil frost prevention.  
Temperature control  
<MSH-07/09/12> When the indoor coil thermistor RT12 reads 4°C or below for 5 minutes, the coil frost prevention mode  
starts.  
<MSH-18/24>When the indoor coil thermistor RT12 reads 3°C or below, the coil frost prevention mode starts immediately.  
However the coil frost prevention will not work for 5 minutes after the compressor starts.  
The compressor stops and the indoor fan operates at the set speed for 5 minutes.  
After that, if RT12 still reads below 4°C (MSH-07/09/12) or below 3°C (MSH-18/24) this mode prolonged until the RT12  
reads over 4°C (MSH-07/09/12) or 3°C (MSH-18/24).  
Time control  
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.  
a. Compressor has been continuously operating.  
b. Indoor fan speed is Lo or Me.  
c. Room temperature is below 26°C.  
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the  
beginning.  
Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds  
26°C.However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.  
Indoor fan operates at the set speed by FAN SPEED CONTROL button.  
Followings are the fan speed in AUTO.  
Initial temperature difference  
Fan Speed  
Room temperature minus set temperature : 2 degrees or more ··············································Hi  
Room temperature minus set temperature : 1 degree or more and less than 2 degrees·······Me  
Room temperature minus set temperature : less than 1 degree··············································Lo  
2 deg.  
4 deg.  
1.66 deg.  
1 deg.  
—DRY mode of “I FEEL CONTROL”—  
The system for dry operation uses the same refrigerant circuit as the cooling circuit.  
The compressor and the indoor fan are controlled by the temperature and the microprocessor.  
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature  
decrease.  
The operation of the compressor and indoor fan is as follows.  
1. When the room temperature is 23°C or over:  
Compressor operates by temperature control and time control.  
Set temperature is controlled to fall 2°C as initial set temperature.  
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.  
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.  
Indoor fan and outdoor fan operate in the same cycle as the compressor.  
2. When the room temperature is under 23°C.  
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.  
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.  
35  
Operation time chart  
Example  
ON  
1st ON  
OFF  
Thermostat  
Indoor fan  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
Outdoor fan  
compressor  
1 min.  
3 min.  
8 min.  
4 min.  
NOTE Coil frost prevention during DRY mode of “I FEEL CONTROL”  
The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.  
However the indoor fan speed becomes the set speed or Lo.  
— HEAT mode of “I FEEL CONTROL” —  
1. Indoor fan speed control  
(1) Followings are the fan speed in AUTO.  
Initial temperature difference  
Fan speed  
Set temperature minus room temperature: 2 degrees or more················································· Hi  
Set temperature minus room temperature: 1 degree or more and less than 2 degrees··········· Me  
Set temperature minus room temperature: less than 1 degree················································· Lo  
(2) Cold air prevention control  
2 deg.  
4 deg.  
1 deg.  
1.66 deg.  
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at VLo  
when the temperature is below 18°C. But the fan stops when the indoor fan operates at VLo and the temperature is  
15°C or less.  
NOTE : At initial in hysteresis this control works.  
Released  
Cold Air Prevention  
18: 22:  
(3) New warm air control.  
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil ther-  
mistor RT12 temperature to blow out warm air.  
After releasing of cold air prevention, when the indoor coil temperature is 37°C or above, the fan speed shifts to the set  
speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed.  
When the indoor coil temperature is less than 37°C, the fan speed is controlled by time as below.  
<Time condition> <Indoor fan speed>  
less than 2 minutes························Lo  
2 minutes to 4 minutes···················Me  
4 minutes or more··························Hi  
The upper limit of the fan speed is the set speed.  
If the thermostat turns off, this operation changes to flow soft control.  
(4) Flow soft control  
After the thermostat turns off, the indoor fan operates at VLo.  
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan  
does not start until the indoor coil thermistor RT12 reads 22°C or more.  
36  
2. High pressure protection  
During heating operation, the outdoor fan motor is controlled by the indoor coil thermistor RT12 temperature for excess rise  
protection of compressor discharge pressure.  
Outdoor fan OFF : 52°C (MSH-07/09/12/24), 50°C (MSH-18)  
Outdoor fan ON : 48°C (MSH-07/09/12/24), 46°C (MSH-18)  
High pressure protection time chart  
Indoor coil thermistor  
RT12 temperature  
Outdoor fan motor  
turn OFF  
52˚C(MSH-07/09/12/24)  
50˚C(MSH-18)  
Outdoor fan motor  
turn ON  
48˚C(MSH-07/09/12/24)  
46˚C(MSH-18)  
ON  
ON  
Outdoor fan motor  
OFF  
OFF  
NOTE 1 :When the outdoor fan is OFF in heating, defrosting of outdoor heat exchanger is not detected by the defrost thermis-  
tor RT61.  
E1  
E1  
E2  
NOTE 2 :When connected to MXZ-32NV-  
outdoor unit,the MSH-07/09/12NV- , MSH-07/09/12/18NV-  
and  
E3  
MSH-18NV-  
indoor unit sends the data for the temperature to the outdoor unit according to the indoor coil temper-  
ature.For the further information,refer to the service manual No.OB185.  
3. Defrostings  
Defrostings of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61.  
(1) Defrost starting conditions  
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.  
a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes without the defrosting opera-  
tion working.  
b) The defrost thermistor RT61 reads - 3°C or less.  
c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.  
(2) Defrost terminating conditions  
When the condition d) or e) is satisfied, the defrosting operation stops.  
d) The defrost thermistor RT61 reads 3.1°C or more.  
e) The defrosting time exceeds 10 minutes.  
37  
(3) Defrosting time chart  
Defrost thermistor RT61  
3.1: or more  
-3: or less  
Outdoor 52C  
relay(Compressor)  
ON  
OFF  
X62  
(Reversing valve coil)  
ON  
15 sec.  
30 sec.  
OFF  
30 sec.  
5~15 sec.  
ON  
SR61  
Outdoor fan  
OFF  
ON  
Defrost  
counter  
OFF  
Max 10 min.  
VLo  
ON  
Indoor fan  
OFF  
Horizontal  
Indoor vane  
Set position  
NOTE1 When the indoor coil thermistor reads above 18°C, indoor fan operates at VLo for 30 seconds.  
When the indoor coil thermistor reads 18°C or less, the indoor fan stops.  
E1  
E2  
E3  
NOTE2: Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-  
E1  
are connected with MXZ-32NV-  
as multi system units.  
38  
4. Reversing valve control  
Heating · · · · · ON  
Cooling · · · · · OFF  
Dry · · · · · · · · OFF  
NOTE1: The Reversing valve reverses for 5 seconds right before start-up of the compressor.  
E1  
E2  
E3  
NOTE2: Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-  
E1  
are connected with MXZ-32NV-  
as multi system units.  
(HEAT)  
5 sec.  
(COOL / DRY)  
5 sec.  
ON  
OFF  
ON  
OFF  
Compressor  
ON  
OFF  
ON  
OFF  
Reversing valve  
ON  
OFF  
ON  
OFF  
Outdoor fan  
8-2. COOL (  
) OPERATION  
(1) Press OPERATE/STOP button.  
OPERATION INDICATOR of the indoor unit turns on with a beep tone.  
(2) Select COOL mode.  
(3) Set the TEMPERATURES button.  
(TOO WARM or TOO COOL button)  
The setting range is 16 ~ 31°C  
Indoor fan continues to operate regardless of  
thermostat’s OFF-ON  
Coil frost prevention is as same as COOL  
mode of “I FEEL CONTROL”  
8-3. DRY (  
) OPERATION  
(1) Press OPERATE/STOP button.  
OPERATION INDICATOR of the indoor unit  
turns on with a beep tone.  
(2) Select DRY mode.  
(3) The microprocessor reads the room tempera-  
ture and determines the set temperature. Set  
temperature is as shown on the right chart.  
Thermostat (SET TEMP.)does not work.  
The other operations are same as DRY mode of  
“I FEEL CONTROL”.  
(4) DRY operation will not function when the room  
temperature is 13°C or below.  
(5) When DRY operation functions, the fan speed  
is lower than cool operation.  
8-4. HEAT (  
) OPERATION  
(1) Press OPERATE/STOP button.  
OPERATION INDICATOR on the indoor unit turns on with a beep tone.  
(2) Select HEAT mode.  
(3) Press TEMPERATURES button (TOO WARM or TOO COOL button) to select the desired temperature.  
The setting range is 16 ~ 31°C.  
(4) Indoor fan speed control, high pressure protection, defrosting, heater control are the same as HEAT mode of “I FEEL  
CONTROL”.  
39  
8-5. FAN MOTOR CONTROL  
(1) Rotational frequency feedback control  
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback  
the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Hi,Me,Lo,SLEEP),  
the microprocessor controls SR11 (MSH-07/09/12), IC141 (MSH-18/24) and adjusts fan motor electric current to make the  
current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the  
rotational frequency changes smoothly.  
SLEEP  
(2) Fan motor lock-up protection  
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect  
the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 min-  
utes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR  
lamp flashes on and off to show the fan motor abnormality. (See page 49.)  
8-6. AUTO VANE OPERATION  
(1) Vane motor drive  
MSH-N series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are  
controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.  
(2) The auto vane angle changes as follows by pressing the VANE CONTROL (  
) button.  
40  
(3) Positioning  
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.  
The positioning is decided as follows.  
(a) When the OPERATE/STOP button is pressed. (POWER ON/OFF)  
(b) When the vane control is changed from AUTO to MANUAL.  
(c) When the SWING is finished.  
(d) When the test run starts.  
(e) When the power supply turns ON.  
(4) VANE AUTO (  
) mode  
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum  
room-temperature distribution.  
In COOL and DRY operation  
Vane angle is fixed to Angle 1.  
In HEAT operation  
Vane angle is fixed to Angle 4.  
(5) Dew prevention  
During COOL or DRY operation at vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the  
vane angle automatically changes to Angle 1 for dew prevention.  
(6) SWING MODE (  
)
By pressing the SWING button (  
) vane swings vertically. The remote controller displays “ ”. SWING mode is cancelled  
when the SWING button or VANE CONTROL button (  
(7) Cold air prevention in HEAT operation  
) is pressed or the operation stops or changes to other mode.  
When either of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle 1 automati-  
cally to prevent cold air blowing on users.  
Compressor is not operating.  
Defrosting is performed.  
Indoor coil thermistor RT12 reads 24: or below.  
Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.  
Set position  
Indoor coil thermistor RT12 temperature  
Angle 1  
24:  
28:  
NOTE:At initial in hysteresis this control works.  
8-7. SLEEP MODE (  
)
• When the SLEEP button ( ) is pressed, the indoor fan speed drops and the air flow sound from the  
indoor unit is decreased.  
• The indications of the remote controller are “  
• When the FAN SPEED CONTROL button (  
mode is released.  
” and “  
”.  
) is pressed during the SLEEP mode, the SLEEP  
41  
8-8. TIMER OPERATION  
1. How to set the timer  
(1) Press OPERATE/STOP button to start the air conditioner.  
(2) Check that the current time is set correctly.  
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display  
of TIME MONITOR so set the current time, correctly with CLOCK SET button.  
(3) Press TIMER CONTROL button to select the operation.  
” button... AUTO START operation (ON timer)  
” button... AUTO STOP operation (OFF timer)  
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.  
HR. and MIN. button will work when “  
These marks disappear in 1 minute.  
” or “  
” mark is flashing.  
When setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.  
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during  
TIMER operation, or the set time may deviate within the range of about 10 minutes.  
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.  
A power failure occurs.  
The circuit breaker functions.  
2. CANCEL  
TIME setting can be cancelled with the TIMER CONTROL buttons. (“  
” or “  
”)  
To cancel the ON timer, press the “  
” button.  
To cancel the OFF timer, press the “  
” button.  
TIME is cancelled and the display of set time disappears.  
PROGRAM TIMER  
The OFF timer and ON timer can be used in combination.  
“  
” and “  
” display shows the order of the OFF timer and ON timer operation.  
(Example 2) The current time is 11:00 AM.  
The unit turns on at 5:00 PM, and off at 9:00 PM.  
(Example 1) The current time is 8:00 PM.  
The unit turns off at 11:00 PM, and on at 6:00 AM.  
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.  
42  
8-9. EMERGENCY-TEST OPERATION  
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY OPERATION switch  
on the front of the indoor unit. The unit will start and the OPERATION INDICATOR lamp will light.  
The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high  
speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal.  
After 30 minutes of test run operation the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of 24°C.  
The fan shifts to Me speed.  
This operation continues until the EMERGENCY OPERATION switch is pressed or a button on the remote controller is  
pressed, then normal operation will start.  
The coil frost prevention circuit operates in this operation, and defrosting operates too.  
In the test run or emergency operation, the horizontal vane operates in AUTO mode with a set temperature of 24°C.  
Defrosting of outdoor heat exchanger works in EMERGENCY HEAT MODE.  
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.  
Press once  
<Cool>  
Press again  
<Heat>  
Press once again  
<Stop>  
Emergency operation  
switch  
43  
9
SERVICE FUNCTIONS  
1. COMPULSORY DEFROSTING MODE FOR SERVICE  
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accomplished  
regardless of the defrost interval restriction. See Page 56 and 59.  
Defrost thermistor RT61 must read below -3°C  
2. DEFROST TERMINATION CHANGE  
<JPC> when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. (See page 56 and 59.)  
<JPE> when the JPE wire of the deicer P.C. board is cut, the defrost temperature will be changed. (See page 56 and 59.)  
MODEL  
Junper wire  
JPC  
Change point  
E1 E2  
MSH-07/09/12NV-  
Defrost interval time changes from 40 minutes to 15 minutes  
E1 E2 E3  
MSH-18NV-  
MSH-24NV-  
Deforst start temperature changes from -3:to 0:  
E1 E2  
JPE  
Deforst finish temperature changes from 3.1:to 10.1:.  
3. TIMER SHORT MODE  
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.  
The time will be shortened as follows.  
3-minute delay : 3-minute 3-second.  
AUTO START : 1 hour 1-minutes  
AUTO STOP : 1 hour 1-minutes  
Short the connector during the timer mode.  
}
4. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION  
A maximum of 4 indoor units with wireless remote controllers can be used in a room.  
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be  
modified according to the number of the indoor unit.  
(1)<The reset button can be located on the rear side.>  
E1  
E1  
E1  
E1  
MSH-07NV -  
MSH-18NV -  
MSH-09NV -  
MSH-12NV -  
MSH-18NV -  
E2  
How to modify the remote controller P.C. board  
Remove batteries before modification.  
The board has a print as shown below :  
NOTE : For remodeling, take out the batteries at first.  
After finish remodeling, put back the batteries then push the RESET button.  
Originally, chip parts are fitted on J10/J20 side and there is no chip parts on the other side.  
Remove the chip parts of J10/J20 side and connect Jumper wire to J11/J21 side as shown in Table 1.  
Either J1O or J11 /J20 or J21 should be attached for normal operation.  
Table.1  
1 unit operation  
2 units operation  
Same as at left  
Replace J10 with J 11  
3 units operation  
Same as at left  
4 units operation  
Same as at left  
No. 1 unit  
No modification  
No. 2 unit  
No. 3 unit  
Same as at left  
Same as at left  
Replace J20 with J 21  
Same as at left  
Replace J10 with J11  
Replace J20 with J21  
No. 4 unit  
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When  
the power supply is turned on and indoor unit receives the first signals from the remote controller, the  
remote controller number is designated as the indoor unit number. Therefore at and after the second  
time indoor unit accepts the remote controller of the initial setting number.  
At setting - error, turn the power supply off to cancel the individual operation and then turn the power  
supply on to restart the setting.  
44  
(2)<The reset button can be located on the front side.>  
E1  
E1  
MSH-07NV - (Serial number 7000201T~) MSH-09NV - (Serial number 7000201T~)  
E1  
E1  
E2  
E2  
MSH-12NV - (Serial number 7000001T~) MSH-24NV -  
E2  
MSH-07NV -  
MSH-12NV -  
MSH-24NV -  
MSH-09NV -  
E2  
E2  
MSH-18NV - (Serial number 7000001T~)  
E3  
MSH-18NV -  
How to modify the remote controller P.C. board  
Remove batteries before modification.  
The board has a print as shown below :  
NOTE : For remodeling, take out the  
batteries at first.  
After finish remodeling, put  
back the batteries then  
push the RESET button.  
The P.C.board has the print “J1” and “J2”.Jumper wires are mounted to each “J1” and “J2”.Cut J1 and J2 according to the  
number of indoor unit as shown in Table 1.  
After modification,push the reset button.  
Table.1  
1 unit operation  
2 units operation  
Same as at left  
Cut J1  
3 units operation  
Same as at left  
Same as at left  
Cut J2  
4 units operation  
Same as at left  
Same as at left  
Same as at left  
No. 1 unit  
No modification  
No. 2 unit  
No. 3 unit  
No. 4 unit  
Cut both J1 and J2  
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When  
the power supply is turned on and indoor unit receives the first signals from the remote controller, the  
remote controller number is designated as the indoor unit number. Therefore at and after the second  
time indoor unit accepts the remote controller of the initial setting number.  
At setting - error, turn the power supply off to cancel the individual operation and then turn the power  
supply on to restart the setting.  
45  
5. AUTO RESTART FUNCTION  
E2  
E2  
E2  
MSH-07NV -  
MSH-12NV -  
MSH-18NV -  
MSH-09NV -  
MSH-24NV -  
E2  
E3  
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are  
memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power  
has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEEL CON-  
TROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is decided  
by the initial room temperature.  
How to set “AUTO RESTART FUNCTION”  
1Turn off the main power for the unit.  
2Removed the electronic control P.C. board and the display P.C.board. (See page 60 and 62.)  
3Cut the RESISTOR JR07 (MSH-07/09/12) or JR06(MSH-18/24) on the indoor electronic control P.C.board.  
MSH-07/09/12  
MSH-18/24  
IC141  
C11  
52C  
CN201  
IC101  
RA102  
CN151  
JR06  
JR07  
Operation  
1If the main power (220/240V AC) has been cut, the operation settings remain.  
2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes  
for the compressor to start running.)  
Note:  
The operation settings are memorized when 10 seconds have passed after the remote controller was operated.  
If main power is cut while AUTO START/STOP timer is active ,the timer setting is cancelled when auto restart function  
works.  
If the unit has been off with the remote controller before power failure, the auto restart function does not works as the  
power button of the remote controller is off.  
To prevent breaker off due to the rush of startting current, systematize other home appliance not to turn on at the same  
time.  
When more than one air conditioners are connected under the same power system,compressor starting current as large  
as that for all the compressors used flows at a time as soon as the units restart automatically.  
Therefore, the specific counter-measures are required to prevent main voltage drop or the rush of starting current after  
power failure by providing the system to allow the units to start in regular succession.  
46  
10 TROUBLESHOOTING  
E1  
E1  
E2  
E2  
E1  
E1  
E2  
E3  
E1  
E2  
E2  
MSH-07NV -  
MSH-18NV -  
MSH-09NV -  
MSH-24NV -  
MSH-09NV -  
MSH-24NV -  
MSH-12NV -  
MSH-18NV -  
MSH-12NV -  
MSH-07NV -  
MSH-18NV -  
10-1 Cautions on troubleshooting  
10-1-1 Before troubleshooting, check the followings:  
1) Check the power supply voltage.  
2) Check the indoor/outdoor connecting wire for mis-wiring.  
10-1-2 Take care the followings during servicing.  
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after  
confirming the horizontal vane is closed, turn off the breaker.  
2) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the  
components.  
3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.  
Housing point  
Lead wiring  
10-1-3 Troubleshooting procedure  
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.  
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.  
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and  
the components for bursting and discoloration.  
3) When troubleshooting, refer to the flow chart on page 48 and the check table on page 49.  
10-1-4 How to replace batteries  
Weak batteries may cause the remote controller malfunction.  
In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote con-  
troller normally, discharge the remote controller in the following order.  
This remote controller has the reset button. After refilling new batteries, press the reset button with tip end of ball point  
pen or the like, and then use the remote controller.  
B
A
RESET button  
RESET button  
There are two kind of remote controllers. A type has the RESET button at the back, and B type does it on the  
front. How to use the two buttons are given in the Instruction Manual.  
47  
10-2 Instruction of troubleshooting  
Start  
Indoor unit  
Indoor unit doesn’t  
receive the signal from  
remote controller.  
Also, OPERATION INDI-  
CATOR lamp doesn’t  
flash, when the EMER-  
GENCY OPERATION  
switch is pressed.  
Indoor unit oper-  
ates. Outdoor unit  
doesn’t operate.  
OPERATION INDICATOR  
lamp on the indoor unit is  
flashing on and off.  
dosen’t receive  
the signal from  
remote  
controller.  
2-time flash  
Outdoor unit  
operates in  
only Test  
Run opera-  
tion.  
Outdoor unit  
doesn’t oper-  
ate even in  
Test Run  
Refer to  
B
”Check of  
receiver P.C.  
board” on page  
51.  
2.5-second OFF  
3-time flash  
operation.  
C
Refer to  
“Check of  
indoor electronic control  
P.C. board” on page 52.  
2.5-second OFF  
1-time flash  
Refer to  
“Check of  
outdoor unit”  
on page 52.  
D
Check room  
temperature  
thermistor.  
6-time flash  
Cause:indoor/outdoor unit  
connecting  
Cause:Indoor unit  
2-time-Room tempera-  
ture/Indoor coil  
thermistor trouble  
3-time-Indoor fan motor  
trouble  
2.5-second OFF  
Trouble of mis-wiring  
(
Trouble of the serial signal  
Cause:outdoor unit  
6-time-Replace the out-  
door thermistor  
E
Refer to  
“How to check  
mis-wiring and sig-  
nal error  
Check room temperature  
thermistor. Refer to“Test  
point diagram and volt-  
age” on page 55,57 and  
58.  
(when outdoor unit  
doesn’t work)”  
on page 53 and  
54.1  
Refer to  
A
Check indoor coil  
“Check of indoor  
fan motor” on  
page 51.  
thermistor. Refer  
to“Test point dia-  
gram and voltage”  
on page 55,57 and  
58.  
1<The case of the trouble of the serial signal>  
When turn off the power and then turn on the power again, the  
indication shows “the trouble of mis-wiring.”  
48  
10-2-1 troubleshooting check table  
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.  
Self check table  
Abnormal  
point  
NO.  
Indication  
Symptom  
Detect method  
Check point  
0.5-second ON  
When serial signal stops for 4  
to 5 seconds after 1st on of  
52C relay by POWER turning  
on.  
Mis-wiring  
Check wiring (visual check and conductiv-  
ity check).  
Check indoor electronic control  
P.C.board.  
Check outdoor DEICER P.C. board.  
Check electrical parts.  
0.5-second OFF  
1-time flash  
Outdoor unit  
does not run.  
1
When serial signal from out-  
door unit stops for 4 to 5 sec-  
onds.  
Serial sig-  
nal  
2.5-second OFF  
2-time flash  
Check thermistor calibration.  
Reconnect connector.  
Check indoor electronic control P.C.board.  
Indoor coil  
thermistor  
Detect Indoor coil/room tem-  
perature thermistor short or  
open circuit every 2 seconds  
during operation.  
Outdoor unit  
does not run.  
2
Room  
tempera-  
ture ther-  
mistor  
2.5-second OFF  
Disconnect connector CN211 and then  
Indoor fan  
repeats 12 sec-  
onds ON and 3 When rotational frequency  
minutes OFF. feedback signal is not emit  
When the indoor during 12-second indoor fan  
fan breaks, the operation.  
fan keeps stop-  
ping.  
2
3
check connector CN121  
-
to make  
3-time flash  
sure rotational frequency feedback signal  
of 1.5V or over exists.  
Check indoor electronic control P.C.  
board.  
Check indoor fan motor.  
Reconnect conector.  
Indoor fan  
motor  
3
4
2.5-second OFF  
6-time flash  
Shortage of refrigerent.  
When the outdoor thermistor  
Outdoor unit  
Check outdoor DEICER P.C. board.  
Outdoor  
thermistor  
shorts or opens after the com-  
does not run  
pressor start-up.  
2.5-second OFF  
5-time flash  
7-time flash  
When the compressor opera-  
tion is continuosly three times  
Check the inverter output.  
Check the compressor.  
Outdoor  
power  
system  
Outdoor unit  
interruped by overcurrent pro-  
does not run  
5
tection within 1 minute after  
start-up , it stops operation.  
2.5-second OFF  
The outdoor unit stops opera-  
Outdoor  
control  
P.C. board  
tion when it cannot properly  
Outdoor unit  
read data in the nonvolatile  
does not run  
6
Check the outdoor control P.C.board.  
memory of the outdoor control  
P.C.board.  
2.5-second OFF  
10-time flash  
When the indoor unit detects  
Outdoor  
control  
P.C. board  
Check the drain punp.  
Check the drain sensor.  
Check LEV.  
Outdoor unit  
does not run  
drain abnormality and the  
indoor coil temperature is too  
low.  
7
2.5-second OFF  
When the operation mode of  
each rooms is setted  
COOL(includes DRY) and  
HEAT at same time, it take  
precedence the operation  
mode runs first.  
Outdoor unit  
runs but the  
indoor unit does  
not run.  
Outdoor  
control  
P.C. board  
Adjust the operation mode.  
8
light  
flash  
2.5-second OFF  
E1  
The indication is shown only when the indoor unit connects with the outdoor unit MXZ-32NV-  
.
49  
10-2-2 Trouble criterion of main parts  
E1  
E1  
E2  
E2  
E1  
E1  
E2  
E2  
E1  
MSH-07NV-  
MSH-18NV-  
MSH-07NV-  
MSH-18NV-  
Part name  
MSH-09NV-  
MSH-24NV-  
MSH-09NV-  
MSH-24NV-  
MSH-12NV-  
E2  
E3  
MSH-12NV-  
MSH-18NV-  
Check method and criterion  
Figure  
Room  
temperature  
thermistor  
Measure the resistance with a tester.  
(Part temperature 10°C ~ 30°C)  
Normal  
Abnormal  
Indoor coil  
thermistor  
Opened or short-circuited  
8k~ 20kΩ  
Measure the resistance with a tester.  
(Part temperature –10°C ~ 40°C)  
Defrost  
thermistor  
Normal  
Abnormal  
Opened or short-circuited  
5k~ 60kΩ  
Measure the resistance between the terminals with a tester.  
(Coil wiring temperature –10°C ~ 40°C)  
WHT  
C
P
Normal  
Abnormal  
AUX.  
RED  
MAIN  
Compressor  
07NV  
09NV  
12NV  
18NV  
24NV  
S
R
BLK  
3.67~4.50  
5.07~6.20  
0.85~1.04Ω  
1.83~2.23Ω  
1.85~2.281.05~1.30Ω  
2.88~3.52Ω  
5.13~6.28Ω  
C-R  
C-S  
Opened or  
short-circuited  
2.38~2.91Ω  
3.44~4.21Ω  
Measure the resistance between the terminals with a tester.  
(Coil wiring temperature10°C ~ 30°C)  
Normal  
Abnormal  
07/09/12NV  
280 ~ 303Ω  
313 ~ 336Ω  
18/24NV  
MAIN  
AUX.  
176 ~ 192Ω  
240 ~ 261Ω  
WHT-BLK  
BLK-RED  
Opened or  
short-circuited  
Indoor fan  
motor  
FUSE  
Measure the voltage Power ON.  
Normal  
BLK  
RED  
WHT  
Abnormal  
BRN-YLW  
4.5 ~ 5.5V  
(When fan revolved one time)  
0V5V0V  
Remain 0V or 5V  
YLW-GRY  
(Approx.)  
MAIN  
AUX.  
07NV  
09NV  
P
Measure the resistance between the terminals with a tester.  
(Coil wiring temperature –10°C ~ 40°C)  
BLK REDWHT  
MAIN  
AUX.  
Outdoor fan  
motor  
12NV  
18NV  
Normal  
P
Abnormal  
12NV  
114 ~ 141  
118 ~ 146Ω  
18NV  
24NV  
07/09NV  
192~236Ω  
373~458Ω  
BLK REDORN WHT  
MAIN  
WHT-BLK  
BLK-RED  
BLK-YLW  
YLW-RED  
102 ~ 126Ω  
97.9 ~ 120Ω  
55.3 ~ 67.6Ω  
24NV  
Opened or  
short-circuited  
AUX.1AUX.2  
P
26.6 ~ 32.6Ω  
55.5 ~ 67.8Ω  
C
BLK YLW REDORNWHT  
Vane motor  
Measure the resistance between the terminals with a tester.  
(Part temperature10°C ~ 30°C)  
PNK  
ROTOR  
Normal  
Abnormal  
Vane motor  
ORN  
RED  
07/09/12NV 282 ~ 305Ω  
18/24NV 358 ~ 388Ω  
Opened or short-circuited  
YLW  
BLU  
INNER PROTECTOR  
P
50  
A
Check of indoor fan motor  
Turn OFF power supply.  
Check connector CN211 visually.  
Inodoor fan does not operate.  
Yes  
No  
No  
Are lead wires connected?  
Is soldered point nomal?  
Yes  
Reconnect the lead wires.  
Resolder it.  
Disconnect lead wires from connector CN211 on indoor electronic control P.C. board.  
Measure resistance between lead wires  
No.1 and No.4 and then No.1 and No.2(MSH-18/24)  
No.1 and No.3 and then No.2 and No.3(MSH-07/09/12)  
}
{
Replace the indoor electronic con-  
trol P.C. board.  
Is resistance 0 (short circuit) or (open circuit)?  
Yes ( 0 or )  
No  
(others)  
Repair the indoor fan motor.  
B Check of receiver P.C. board  
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.  
Check the model name of remote  
controller.  
No  
Is LCD display on remote con-  
Replace the batteries.(see page 47.)  
troller visible?  
(not clear)  
Yes  
Remove batteries and then set them back.  
Check if the unit operates with remote  
controller.  
No  
Turn on a radio to AM and press switch on  
remote controller.  
Does the unit operate with remote  
controller?  
Yes  
OK  
No  
Replace the remote controller.  
Is noise heard from radio?  
Yes  
Are there any fluorescent lights of  
inverter or rapid-start type within  
the range of 1m?  
Yes  
Re-install the unit away from lights.  
Attach a filter on receiving part.  
No  
Measure the voltage between  
receiver P.C. board connector No.2(+)and No.1(MSH-18/24)  
indoor electronic control P.C. board connector LD101 No.2 and JPG(MSH-07/09/12)  
}
{
when remote controller button is pressed.  
Yes  
Is the voltage approx. 4V DC?  
Replace the indoor electronic control P.C.  
board.  
No(5V or 0V DC)  
Replace the receiver.  
51  
C Check of indoor electronic control P.C. board  
The unit doesn’t operate with the  
remote controller.  
Replace the fuse.  
Yes  
Also, the OPERATION INDICA-  
TOR lamp doesn’t light up by  
pressing the EMERGENCY  
OPERATION switch.  
Trouble of indoor electronic con-  
trol P.C. board.  
Yes  
No  
Is fuse(F11)blown?  
1.Pull out power supply  
cord.  
2.Measure resistance  
between CN201  
Is there resistance ?  
(Approx.0)  
Be sure to check both fuse  
and varistor in any case.  
1
on indoor electronic  
Check both “parts side”and “pattern  
sideof indoor electronic control P.C.  
board visually.  
control P.C. board  
and  
N
on the terminal  
No  
block with a tester.  
Trouble of fuse(F12)  
Is varistor(NR11)burnt?  
CN201  
No  
07/09NV  
12/18NV  
3
1
Yes  
F12  
L
Terminal  
block  
N
CN201  
Replace the varistor.  
1
2
F12  
F12  
L
N
Terminal  
block  
CN201  
24NV  
3
2
3
1
NF  
D
Check of outdoor unit  
L
Terminal  
block  
N
Compressor and outdoor fan do not operate.(Only indoor fan operates.)  
Start  
Press EMERGENCY OPERATION switch.  
3-minute time delay works.  
24NV  
No  
Is voltage applied to fan motor and compressor  
relay normal when you look at checkpoints about  
outdoor DEICER P.C.borad?  
Replace  
DEICER  
P.C.board  
Test run operation operates for 30 minutes.  
Yes  
Yes  
Yes  
Check voltage to terminal block of outdoor unit. Is  
N
2
there AC220-240V to terminal block between  
-
?
07/09/12/18NV  
Check the outdoor DEICER P.C.board at first, then check  
No  
the outdoor fan motor and the compressor.  
Check voltage to terminal block of indoor unit. Is  
N
2
there AC220-240V to terminal block between  
-
?
07/09/12/18NV  
No  
24NV  
Check the continuity of indoor and outdoor unit connection.  
Replace the indoor elec-  
tronic control P.C. board.  
Confirm wiring connection  
at indoor terminal block.  
52  
E How to check mis-wiring and serial signal error (when outdoor unit does not work)  
MSH-07NV  
Start  
MSH-09NV  
MSH-12NV  
MSH-18NV  
1 Short circuit of JPG and JPS on the  
1. Turn OFF power supply.  
2. Turn ON power supply.  
3. Press EMERGENCY OPERATION switch.  
indoor electronic control P.C. board  
enables self-check to be displayed in 3  
seconds.  
Serial signal error is indicated.  
(0.5-sec.ON, 2.5-sec.OFF)  
3 min. later, when relay 52C turns ON, what self-check result is  
displayed on OPERATION INDICATOR lamp on indoor unit? 1  
Mis-wiring is indicated.(0.5-sec.ON, 0.5-sec.OFF)  
Yes  
Repair wiring.  
Is there mis-wiring, poor contact, or wire disconnection?  
No  
1. Turn OFF power supply and disconnect in-out connecting wire on indoor side.  
N
3
2. Short-circuit between indoor terminal block  
and  
3. Turn ON power supply and press EMERGENCY OPERATION switch.  
Is there 20V DC between both ends of R132 when  
relay (52C) turns ON?  
( By tester, the stylus is between 0 ~ 20V. )  
No  
Replace the indoor electronic control  
P.C. board.  
Yes  
•Turn OFF power supply.  
•Connect ON in-out connecting wire.  
•Turn ON power supply.  
3 minutes later, when EMERGENCY OPERATION switch is pressed  
and 52C relay turns ON, is there AC 220-240V between outdoor  
No  
Rectify in-out connecting wire.  
2
N
terminal block  
-
?
Yes  
Under the same condition as 3 minutes later, when  
EMERGENCY OPERATION switch is pressed and  
No  
No  
Check and rectify fuse and varistor on out-  
door DEICER P.C. board.  
52C relay turns on, is there DC 5V between  
+
J8 -J7 –  
?
Yes  
Under the same condition as 3 minutes later, when  
EMERGENCY OPERATION switch is pressed and  
52C relay turns on, is there DC 10V between both  
ends of R601?  
Rectify in-out connecting wire.  
(By tester, the stylus is between 5 ~10V)  
Yes  
Replace the outdoor DEICER P.C. board.  
53  
E How to check mis-wiring and serial signal error (when outdoor unit does not work)  
MSH-24NV  
Start  
1 Short circuit of JPG and JPS on the  
1. Turn OFF power supply.  
2. Turn ON power supply.  
3. Press EMERGENCY OPERATION switch.  
indoor electronic control P.C. board  
enables self-check to be displayed in 3  
seconds.  
Serial signal error is indicated.  
(0.5-sec.ON, 2.5-sec.OFF)  
3 min. later, what self-check result is displayed on OPERATION  
INDICATOR lamp on indoor unit? 1  
Mis-wiring is indicated.(0.5-sec.ON, 0.5-sec.OFF)  
Yes  
Repair wiring.  
Is there in-out mis-wiring, poor contact, or wire disconnection?  
No  
1. Turn OFF power supply and disconnect in-out connecting wire on indoor side.  
N
3
2. Short-circuit between indoor terminal block  
and  
3. Turn ON power supply and press EMERGENCY OPERATION switch.  
3 minutes later,is there DC 20V between both ends  
of R132?  
( By tester, the stylus is between 0 ~ 20V. )  
No  
Replace the indoor electronic control  
P.C. board.  
Yes  
•Turn OFF power supply.  
•Connect ON in-out connecting wire.  
•Turn ON power supply.  
No  
Replace in-out connecting wire of  
2
N
Is there AC220~240V between outdoor terminal blocks  
-
?
2
N
and  
.
Yes  
No  
3 minutes later, when EMERGENCY OPERATION  
switch is pressed is there DC 5V between J8 -J7  
on outdoor DEICER P.C. board?  
Check and rectify fuse and varistor on out-  
door DEICER P.C. board.  
+
Yes  
3 minutes later, when EMERGENCY OPERATION  
switch is pressed and 52C relay turns on, is there  
DC 10V between both ends of R601?  
No  
3
Replace  
in-out connecting wire.  
(By tester, the stylus is between 5 ~10V)  
Yes  
Replace the outdoor DEICER P.C. board.  
54  
TEST POINT DIAGRAM AND VOLTAGE  
E1  
MSH-18NV -  
Indoor electric control P.C.board  
Fan motor power supply  
}
Fuse AC250V 3.15A  
Power supply input  
AC 220-240V  
}
+
--  
R132  
}
DC 0 ~20V  
C144  
+
DC5V  
}
--  
C144  
Room temperature thermistor(RT11)  
Indoor coil thermistor(RT12)  
Timer short mode point  
Emergency operation  
switch  
JPG  
--  
DC12V  
}
JP43  
+
55  
E1  
MUH-18NV -  
Outdoor deicer P.C. board  
R601  
DC5~10V  
Defrost  
thermistor(RT61)  
INPUT  
AC 220-240V  
Reversing valve coil  
AC 220-240V  
Outdoor fan motor  
AC 220-240V  
+
--  
DEICER P.C. BOARD  
Fuse  
2A/250V  
Defrost interval  
time short pin  
+ J8  
DC5V  
}
-- J7  
+
--  
+
--  
Defrost termination  
temperature change.  
Jumper wire JPC and JPE  
DC12V  
52C  
DC12V  
56  
TEST POINT DIAGRAM AND VOLTAGE  
E1  
E1  
E1  
E2  
MSH-07NV -  
MSH-07NV -  
MSH-09NV -  
MSH-09NV -  
MSH-12NV -  
MSH-12NV -  
E2  
E2  
Indoor electronic control P.C. board  
Power supply input  
AC 220-240V  
}
CN201 No1  
Varistor(NR11)  
Fuse AC250V 3.15A  
Room temperature  
thermistor(RT11)  
Indoor coil  
thermistor(RT12)  
Time short mode point  
Indoor coil thermistor(RT12)  
Room temperature thermistor(RT11)  
R132  
DC0~20V  
P.C.board  
57  
TEST POINT DIAGRAM AND VOLTAGE  
E1  
E2  
MSH-24NV - MSH-18NV -  
E2  
E3  
MSH-24NV - MSH-18NV -  
Fan motor power supply  
Fuse AC 250V 3.15A  
Power supply input  
AC 220-240V  
}
C144  
+
DC5V  
}
C144  
Room temperature  
thermistor(RT11)  
Indoor coil thermistor(RT12)  
JPS  
Time short mode point  
JPS  
Emergency operation switch  
JPG  
DC12V  
JP41  
}
+
R132  
DC0~20V  
P.C.board  
58  
E1  
E1  
E2  
E3  
E1  
E2  
E2  
E1  
E2  
E2  
MUH-07NV -  
MUH-24NV -  
MUH-12NV -  
MUH-18NV -  
MUH-09NV -  
MUH-07NV -  
MUH-18NV -  
MUH-12NV -  
MUH-09NV -  
MUH-24NV -  
Outdoor deicer P.C. board  
R601  
DC5~10V  
Reversing valve  
INPUT  
AC 220-240V  
Outdoor fan motor  
coil  
AC 220-240V  
AC 220-240V  
+
Defrost thermistor(RT61)  
DEICER P.C. BOARD  
Fuse 2A/250V  
Defrost interval  
time short pin  
+
J9  
J8  
DC5V  
}
+
+
DC12V  
Defrost termination  
temperature change.  
Jumper wire JPC and JPE  
52C  
DC12V  
59  
11  
DISASSEMBLY INSTRUCTIONS  
NOTE:  
On the wiring diagram shows the terminals with a lock mechanism, so it  
cannot be removed when you pull the lead wire Be sure to pull the wire by  
pushing the locking lever (projected part) of the terminal with a finger.  
Slide the sleeve.  
Pull the wire while pushing  
the locking lever.  
E1  
E2  
E1  
E2  
E1  
11-1 MSH-07NV -  
MSH-07NV -  
MSH-09NV -  
MSH-09NV -  
MSH-12NV -  
MSH-12NV -  
E2  
INDOOR UNIT  
PHOTOS  
OPERATING PROCEDURE  
1. Removing the front panel  
Photo 1  
(1) Remove the screws caps of the front panel.  
Front panel  
Remove the screws.  
(2) Pull the panel down to your side slightly and unhook the  
catches at the top.  
Screw  
2. Removing the electronic control P.C. board and the  
display P.C. board.  
Photo 2  
Room temperature  
thermistor connector  
(1) Remove the front panel. (Refer to 1)  
(2) Remove the screw of the electrical cover.  
Remove the electrical cover.  
Ground wire screw  
(3) Disconnect the room temperature thermistor and the con-  
nector from the indoor coil thermistor.  
(4) Remove the terminal cover.  
Cord clamp  
Remove the screw of the terminal block.  
(5) Remove the cord clamp.  
(6) Disconnect all the connectors on the electronic control P.C.  
board.  
(7) Remove the screw of the ground wire.  
(8) Disconnect the white lead wire and the brown lead wire  
from 52C relay.  
(9) Remove the electronic control P.C. board and the display  
P.C. board.  
Terminal block  
cover  
Indoor electronic  
control P.C.board  
Terminal block  
cover screw  
60  
OPERATING PROCEDURE  
PHOTOS  
3. Removing the electrical box  
Photo 3  
(1) Remove the front panel. (Refer to 1)  
(2) Remove the electrical cover.  
(3) Disconnect the connector of the indoor coil thermistor.  
(4) Disconnect the motor connector (CN211 and CN121) and  
the vane motor connector (CN151) on the electronic con-  
trol P.C. board.  
(5) Unhook the catches (both upper and lower), remove the  
electrical box.  
Catch  
4. Removing the vane motor  
(1) Remove the front panel.  
Vane motor screw  
Photo 4  
(2) Remove the screw of the vane motor, disconnect the con-  
nector.  
(3) Remove the vane motor.  
Drain hose  
Vane motor  
5. Removing the line flow fan and the indoor fan motor  
(1) Remove the front panel. (Refer to 1)  
Photo 5  
(2) Disconnect the connector from the vane motor.  
(3) Pull out the drain hose from the nozzle assembly, remove  
the nozzle assembly.  
(4) Lifting the left side of the heat exchanger, remove the elec-  
trical box.  
(5) Remove the fixture of the fan motor.  
(6) Remove the hexagon socket set screws.  
(7) Remove the line flow fan and the fan motor.  
Fan motor  
catches  
Indoor coil  
termistor  
Fan motor  
fixture  
61  
E1  
E3  
E1  
E2  
E2  
11-2 MSH-18NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
MSH-24NV -  
INDOOR UNIT  
OPERATING PROCEDURE  
PHOTOS  
1. Removing the front panel  
Photo 1  
(1) Remove the screw caps at the down of the front panel.  
Remove the screws.  
(2) Pull the panel down to your side slightly and unhook the  
catches at the top.  
Front panel  
Screws  
2. Removing the electronic control P.C. board  
(1) Remove the front panel. (Refer to 1)  
Photo 2  
(2) Remove the electrical cover.  
(3) Remove the screw, remove the terminal cover.  
(4) Remove the screw of terminal block.  
(5) Unhook the catch of the lamp holder.  
(6) Remove the receiver holder.  
(7) Disconnect the connectors and the lead wire from 52C  
relay on the electronic control P.C. board and remove the  
ground and the indoor coil thermistor.  
Ground  
Indoor coil thermistor  
(8) Remove the electronic control P.C. board.  
Screw  
Terminal  
block  
screw  
Indoor  
electronic  
control  
P.C. board  
62  
OPERATING PROCEDURE  
PHOTOS  
3. Removing the electrical box  
screw  
Photo 3  
(1) Remove the front panel. (Refer to 1)  
(2) Remove the electrical cover.  
(3) Disconnect the connector of the indoor coil thermistor.  
(4) Disconnect the motor connector (CN211 and CN121) and  
the vane motor connector (CN151) on the electronic con-  
trol P.C. board.  
(5) Remove the screw of the electrical box, remove the electri-  
cal box.  
screw  
4. Removing the indoor fan motor and the line flow fan  
(1) Remove the front panel.  
Photo 4  
Heat exchanger  
(2) Remove the electrical box.  
(3) Unhook the catch on the both sides of the nozzle assem-  
bly.  
(4) Remove the nozzle assembly.  
Catch  
(5) Remove the screws of the bearing support.  
(6) Remove the screw of the heat exchanger unhook the  
catch.  
Heat exchanger  
screw  
(7) Lifting the heat exchanger, remove the bearing support.  
(8) Remove the motor support.  
(9) Loose the screw fixing the line flow fan, remove the line  
Bearing support  
screws  
flow fan.  
( )  
10 Remove the screws of the motor band, remove the fan  
motor.  
Photo 5  
Indoor fan motor  
Fan  
motor  
screws  
Line flow fan  
Motor band  
63  
E1  
E1  
E2  
E2  
11-3 MUH-07NV -  
OUTDOOR UNIT  
MUH-09NV -  
MUH-07NV -  
MUH-09NV -  
OPERATING PROCEDURE  
PHOTOS  
1. Removing the cabinet  
Photo 1  
(1) Remove the top panel.  
(2) Remove the cabinet  
Photo 2  
Service  
panel  
Screw for  
service panel  
Screw for  
top panel  
Screw for  
top panel  
Screws for  
cabinet  
Screws for  
cabinet  
2. Remove the deicer P.C. board  
Photo 3  
(1) Remove the top panel, the service panel and the cabinet.  
(2) Disconnect all the connectors and the terminals on the  
deicer P.C. board.  
Deicer P.C board  
(3) Remove the deicer P.C. board.  
3. Removing the propeller fan  
Propeller fan  
Photo 4  
(1) Turn the propeller nut clockwise to remove.  
(2) Pull the propeller fan toward you to remove.  
Propeller nut  
64  
OPERATING PROCEDURE  
PHOTOS  
4. Removing the outdoor fan motor  
(1) Remove the screws securing the outdoor fan motor.  
(2) Remove the lead clamps.  
Photo 5  
Outdoor fan motor set screws  
(3) Disconnect the capacitor terminal and wire of the terminal.  
(4) Pull out the outdoor fan motor.  
Lead  
fxture  
Outdoor fan motor  
5. Removing the compressor  
(1) Remove the lead clamps.  
Photo 6  
(2) Remove the screws securing the relay panel.  
(3) Remove the screw securing the service port.  
(4) Remove the terminal cover. (See Photo 7.)  
(5) Pull out the lead from the compressor terminal.  
(6) Remove the overcurrect relay.  
(7) Remove the compressor nuts.  
(8) Detach the suction pipe welded section and discharge pipe  
welded section with a burner.  
Relay panel  
NOTE  
Before using a burner, purge gas from the pipes until the pres-  
sure gauge shows 0 kg/cm2.  
Use the burner under the condition that gas can be released  
even when the inner pressure rises by heat.  
Photo 7  
Photo 9  
Terminal cover  
Compressor  
Photo 8  
Discharge pipe  
Sound proof felt  
Compressor nuts  
Suction pipe  
65  
E1  
E3  
E1  
E2  
E2  
11-4 MUH-12NV -  
MUH-18NV -  
MUH-18NV -  
MUH-12NV -  
MUH-18NV -  
OUTDOOR UNIT  
OPERATING PROCEDURE  
PHOTOS  
1. Removing the cabinet  
Photo 1  
(1) Remove the screws of the cabinet.  
(2) Hold the down of the cabinet on the both side to remove  
the cabinet.  
Photo 2  
Screws  
Service  
panel  
Screws  
2. Removing the deicer P.C. board  
(1) Remove the service panel and the cabinet.  
(2) Disconnect all the connectors and the terminals on the  
deicer P.C. board.  
Photo 3  
Screws  
Deicer  
P.C. board  
(3) Remove the deicer P.C. board.  
Compressor  
Red lead wire  
Black lead wire  
White lead wire  
Terminal  
block  
66  
OPERATING PROCEDURE  
PHOTOS  
Photo 4  
3. Removing the outdoor fan motor  
Set screws for  
outdoor fan motor  
(1) Remove the cabinet. (Refer to 1)  
(2) Disconnect the connector remove the clamp of fan motor  
lead wire.  
Lead clamps  
propeller fan  
(3) Remove the propeller nut and remove the propeller.  
(4) Remove screws securing the fan motor.  
Outdoor  
fan motor  
Propeller  
fan nut  
Set screws for  
outdoor fan motor  
4. Removing the compressor  
(1) Remove the cabinet. (Refer to 1)  
(2) Remove the soundproof felt.  
Photo 5  
(3) Remove the terminal cover on the compressor  
(4) Remove the electrical assembly.  
(Refer to 2)  
(5) Release gas from the refrigerant circuit.  
(6) Disconnect the welded part of the discharge pipe.  
(7) Disconnect the welded part of the suction pipe.  
(8) Remove nuts fixing the compressor.  
(9) Remove the compressor.  
Terminal cover  
Discharge  
pipe  
Suction  
pipe  
Compressor  
Compressor nuts  
67  
E1  
E2  
11-5 MUH-24NV-  
OUTDOOR UNIT  
OPERATING PROCEDURE  
MUH-24NV-  
PHOTOS  
1. Removing the electrical parts  
Photo 1  
( )  
1 Remove the screws and the top panel.  
( )  
Screws  
2 Remove the screw of the cover panel. To remove the  
cover panel, pull it toward you and unhook the catch-  
es from the side panel.  
3 Remove the screw of the service panel. To remove the  
service panel, pull it down toward you and unhook the  
catches on the both sides.  
Top panel  
( )  
Service panel  
Panel cover  
Front panel  
Photo 2  
Transformer  
Capacitor  
Outdoor controller  
board  
Contactor  
Overcurrent  
relay  
Screws  
Terminal block  
2. Removing the fan motor  
Photo 3  
( )  
1 Remove the screws of the front panel.  
Open the front panel to a 45-degree angle.  
Then lift it and unhook the catches to remove.  
2 Remove the propeller nut and the propeller fan.  
3 Remove the screws and the fan motor.  
Disconnect the lead connectors.  
Motor support Separator support  
Lead  
( )  
( )  
Propeller  
fan  
connectors  
Valve bed  
Propeller nut  
68  
OPERATING PROCEDURE  
PHOTOS  
3. Removing the heat exchanger and the compressor  
Photo 4  
( )  
1 Remove the rear panel.Remove the valve bed, and  
Screws  
open the rear panel to the rear to remove.  
NOTE :  
All panels are fixed by catches, and must be removed by  
shifting up and down.  
( )  
2 Remove the screws of the right side panel and remove  
it.  
( )  
3 Remove the screws of the rear guard and remove it.  
( )  
4 Remove the screws of the separator support plate and  
remove it.  
( )  
5 Remove the screws of the motor support and remove  
it.  
Screws  
( )  
6 Remove the screws of the valve bed.  
The valve bed is fixed by the catches on the right and  
left sides.  
Lift it to remove.  
( )  
7 Remove the electrical parts box.  
Disconnect the connectors from the high pressure  
switch, crank case heater, shell thermo, and fan motor  
lead.  
( )  
8 Remove the screws of the separator and remove it.  
( )  
9 Remove the screws of the heat exchanger and remove  
Photo 5  
it.  
Heat exchanger  
Detach the welded point of pipe.  
( )  
10 Remove the nuts of the compressor and remove it.  
Detach the welded points of the compressor suction  
pipe and discharge pipe.  
Accumulator  
Photo 6  
Charge plug  
Ball valve  
Compressor  
69  
12 PARTS LIST  
INDOOR UNIT  
STRUCTURAL PARTS  
E1  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
5
E1  
E1  
E2  
E2  
E2  
1
6
4
2
Optional parts  
3
Symbol  
in Wiring  
Diagram  
Q'ty/unit  
NO.  
Part No.  
Part Name  
Remarks  
MSH-07NV- E1 MSH-07NV- E2 MSH-09NV- E1 MSH-09NV- E2 MSH-12NV- E1 MSH-12NV- E2  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
E02 154 000 FRONT PANEL(WH)  
E02 157 000 FRONT PANEL(WH)  
E02 199 000 FRONT PANEL(WH)  
E02 151 010 GRILL(WH)  
1
1
1
1
1
1
1
2
1
1
1
2
1
2
1
1
2
1
2
1
1
2
2
3
E02 164 100 AIR FILTER  
1PC/SET  
2PCS/SET  
E02 151 234 BOX(WH)  
4
E02 166 234 BOX(WH)  
1
1
2
1
1
2
1
1
2
E02 151 970 INSTALLATION PLATE  
E02 166 067 SCREW CAP(WH)  
1
2
1
2
1
2
5
6
INDOOR UNIT  
1
HEAT EXCHANGER  
E1  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
(WH)  
E1  
E1  
E2  
E2  
E2  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
3
2
Symbol  
in Wiring  
Diagram  
Q'ty/unit  
NO.  
Part No.  
Part Name  
Remarks  
E1 E2  
E1  
E2  
MSH-07/09NV-  
(WH)  
MSH-12NV-  
(WH)  
E02 151 620 INDOOR HEAT EXCHANGER  
E02 155 620 INDOOR HEAT EXCHANGER  
E02 151 666 UNION(GAS)  
1
1
1
1
2
1
{9.52  
{12.7  
{6.35  
E02 155 666 UNION(GAS)  
1
1
E02 151 667 UNION(LIQUID)  
3
70  
INDOOR UNIT  
ELECTRICAL PARTS  
E1  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
MSH-07NV -  
MSH-09NV -  
MSH-12NV -  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
E1  
E1  
E2  
E2  
E2  
10  
9
7
8
16  
6
3
5
1
4
2
13  
12  
Part number that are circled is not shown in the illustration.  
Symbol  
Q'ty/unit  
in Wiring  
Diagram  
NO.  
Part No.  
Part Name  
Remarks  
E1  
E2  
MSH-07NV-  
(WH)  
E1  
E2  
MSH-09NV-  
(WH)  
E1  
E2  
MSH-12NV-  
(WH)  
E02 166 235 NOZZLE(WH)  
E02 166 040 VANE(WH)  
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
E02 141 702 DRAIN HOSE  
E02 151 303 VANE MOTOR  
E02 151 300 INDOOR FAN MOTOR  
E02 151 505 RUBBER MOUNT  
E02 151 302 LINE FLOW FAN  
E02 151 509 BEARING MOUNT  
1
3
MV  
MF  
1
4
1
RC4V19 -  
5
2
2PCS/SET  
6
1
7
1
8
ROOM TEMPERATURE THERMISTOR  
RT11  
RT12  
TB  
1
E02 151 308  
E02 151 307  
E02 198 375  
E02 199 450  
E02 200 450  
E02 201 450  
E02 152 395  
E02 127 382  
E02 085 385  
E02 001 504  
E02 151 468  
E02 199 520  
9
INDOOR COIL THERMISTOR  
TERMINAL BLOCK  
ELECT CONTROL P.C.BOARD  
ELECT CONTROL P.C.BOARD  
ELECT CONTROL P.C.BOARD  
POWER SUPPLY CORD  
FUSE  
1
10  
11  
1
1
12  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
13  
14  
15  
16  
17  
18  
F11  
3.15A  
VARISTOR  
NR11  
SLEEVE BEARING  
RECEIVER  
FAN GUARD  
71  
OUTDOOR UNIT  
STRUCTURAL PARTS  
E1  
MUH-07NV -  
MUH-09NV -  
MUH-07NV -  
MUH-09NV -  
E1  
E2  
5
11  
13  
E2  
2
1
9
10  
7
8
4
6
3
Part number that are circled is not shown in the illustration.  
Symbol  
in Wiring  
Diagram  
Q'ty/unit  
NO.  
Part No.  
Part Name  
Remarks  
E1 E2  
-
E1 E2  
-
MUH-09NV  
MUH-07NV  
1
1
1
1
1
1
1
1
1
1
1
CABINET  
E02 096 232  
E02 085 297  
E02 199 521  
E02 085 245  
E02 096 630  
E02 128 900  
E02 164 900  
E02 047 506  
E02 096 290  
E02 096 662  
E02 096 661  
E02 085 515  
E02 154 642  
E02 077 961  
E02 154 936  
E02 159 936  
E02 134 937  
E02 199 936  
E02 139 936  
1
2
3
4
5
TOP PANEL  
FAN GUARD  
SERVICE PANEL  
OUTDOOR HEAT EXCHANGER  
COMPRESSOR  
MC  
MC  
RH-174VGHT  
RH-135VGHT  
6
1
1
1
1
1
1
1
1
COMPRESSOR  
1
1
1
1
1
1
1
1
COMPRESSOR RUBBER SET  
BASE  
7
8
STOP VALVE(LIQUID)  
STOP VALVE(GAS)  
MOTOR SUPPORT  
CHECK VALVE  
{6.35  
9
{9.52  
10  
11  
12  
13  
REVERSING VALVE  
CAPILLARY TUBE  
CAPILLARY TUBE  
CAPILLARY TUBE  
CAPILLARY TUBE  
CAPILLARY TUBE  
{3.0 {1.6 1300  
{3.0 {1.4 800  
{3.0 {1.6 400  
{3.0 {1.4 850  
{3.0 {1.6 750  
2
2
1
14  
1
1
72  
OUTDOOR UNIT  
FUNCTIONAL PARTS AND ELECTRICAL PARTS  
E1  
MUH-07NV -  
MUH-09NV -  
MUH-07NV -  
MUH-09NV -  
E1  
E2  
E2  
6
5
1
2
4
3
Part number that are circled is not shown in the illustration.  
Symbol  
Q'ty/unit  
in Wiring  
Diagram  
NO.  
Part No.  
Part Name  
Remarks  
E1  
E2  
MUH-07/09NV  
-
1
1
1
1
1
1
1
E02 085 501 PROPELLER FAN  
1
2
3
4
5
6
7
E02 096 301 OUTDOOR FAN MOTOR  
E02 085 353 COMPRESSOR CAPACITOR  
E02 199 374 TERMINAL BLOCK  
MF  
C1  
RA6V29-  
25+/440VAC  
TB  
E02 096 310 DEFROST THERMISTOR  
E02 199 451 DEICER P.C. BOARD  
E02 154 490 REVERSING VALVE COIL  
RT61  
21S4  
73  
OUTDOOR UNIT  
STRUCTURAL PARTS  
3
17  
18  
E1  
MUH-12NV -  
MUH-12NV -  
E2  
15  
7
16  
2
14  
12  
4
10  
11  
13  
6
5
8
9
1
Part number that are circled is not shown in the illustration.  
Symbol  
in Wiring  
Diagram  
Q'ty/unit  
NO.  
Part No.  
Part Name  
Remarks  
- E1  
E2  
MUH-12NV  
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
E02 141 521 GRILL  
1
2
E02 141 232 CABINET ASSEMBLY  
E02 140 233 BACK PANEL  
3
E02 141 245 SERVICE PANEL  
4
E02 075 506 COMPRESSOR RUBBER SET  
E02 139 515 MOTOR SUPPORT  
E02 156 630 OUTDOOR HEAT EXCHANGER  
E02 141 900 COMPRESSOR  
3 RUBBER  
5
6
7
MC  
RH-231VHAT  
8
E02 201 290 BASE  
9
E02 139 662 STOP VALVE(LOQUID)  
E02 140 661 STOP VALVE(GAS)  
E02 077 961 REVERSING VALVE  
E02 141 501 PROPELLER FAN  
E02 141 301 OUTDOOR FAN MOTOR  
E02 079 353 COMPRESSOR CAPACITOR  
E02 201 374 TERMINAL BLOCK  
E02 139 310 DEFROST THERMISTOR  
E02 201 451 DEICER P.C. BOARD  
E02 156 490 REVERSING VALVE COIL  
E02 156 936 CAPILLARY TUBE  
E02 134 937 CAPILLARY TUBE  
E02 154 642 CHECK VALVE  
{6.35  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
{12.7  
MF  
CI  
RA6V40 -  
30+/440VAC  
TB  
RT61  
21S4  
{3.0{1.4500  
20  
21  
{3.0{1.6400  
74  
INDOOR UNIT  
STRUCTURAL PARTS  
E1  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
E1  
E2  
E2  
E3  
1
5
3
2
Optional parts  
6
4
Part number that are circled is not shown in the illustration.  
Symbol  
Q'ty/unit  
in Wiring  
MSH-18NV-  
MSH-24NV-  
NO.  
Part No.  
Part Name  
Remarks  
E1  
E2 E3  
E1 E2  
(WH)  
(WH)  
(WH)  
Diagram  
FRONT PANEL(WH)  
GRILLE(WH)  
E02 138 000  
E02 138 010  
E02 143 234  
E02 141 100  
E02 141 970  
E02 143 067  
E02 168 007  
E02 214 007  
1
1
1
1
1
2
1
3
1
1
2
3
4
5
6
1
1
2
1
3
1
1
2
1
3
1
BOX(WH)  
AIR FILTER  
1PC/SET  
INSTALLATION PLATE  
SCREW CAP(WH)  
LAMP PANEL(WH)  
LAMP PANEL(WH)  
3PCS/SET  
7
1
INDOOR UNIT  
1
HEAT EXCHANGER PARTS  
E1  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
E1  
E2  
E2  
E3  
2
3
Symbol  
Q'ty/unit  
in Wiring  
Diagram  
MSH-18NV-  
MSH-24NV-  
NO.  
Part No.  
Part Name  
Remarks  
E1 E2 E3  
E1 E2  
(WH)  
(WH)  
E02 141 620 INDOOR HEAT EXCHANGER  
E02 138 667 UNION(LIQUID)  
E02 176 667 UNION(LIQUID)  
E02 138 666 UNION(GAS)  
1
1
1
1
2
{6.35  
{9.52  
1
1
{15.88  
1
3
75  
INDOOR UNIT  
ELECTRICAL PARTS  
E1  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
MSH-24NV -  
MSH-18NV -  
(WH)  
(WH)  
(WH)  
(WH)  
(WH)  
E1  
E2  
E2  
E3  
10  
8
11  
15  
5
7
5
4
3
16  
1
9
6
12  
2
14  
17  
Part number that are circled is not shown in the illustration.  
Symbol  
Q'ty/unit  
MSH-18NV-  
MSH-24NV-  
in Wiring  
Diagram  
NO.  
Part No.  
Part Name  
NOZZLE(WH)  
VANE(WH)  
Remarks  
E1  
E2 E3  
E1  
E2  
(WH)  
(WH)  
(WH)  
(WH)  
1
2
3
E02 143 235  
E02 143 040  
E02 141 702  
E02 141 300  
E02 213 300  
E02 001 505  
E02 138 395  
E02 320 395  
E02 139 450  
E02 198 450  
E02 214 450  
E02 141 302  
E02 141 303  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
DRAIN HOSE  
RA4V27 -EA  
RA4V27 -EC  
2PCS/SET  
INDOOR FAN MOTOR  
INDOOR FAN MOTOR  
RUBBER MOUNT  
MF  
MF  
4
5
6
1
2
1
1
2
2
1
2
1
POWER SUPPLY CORD  
POWER SUPPLY CORD  
ELECT CONTROL P.C. BOARD  
ELECT CONTROL P.C. BOARD  
ELECT CONTROL P.C. BOARD  
LINE FLOW FAN  
1
1
7
1
1
1
1
1
1
1
1
1
1
1
1
1
8
9
1
1
1
1
1
1
1
1
1
VANE MOTOR  
MV  
10 E02 138 329  
11 E02 141 509  
E02 198 375  
12 E02 139 375  
E02 278 375  
13 E02 085 385  
14 E02 141 468  
15 E02 001 504  
16 E02 138 307  
17 E02 138 308  
18 E02 127 382  
DISPLAY P.C. BOARD  
BEARING MOUNT  
TERMINAL BLOCK  
TERMINAL BLOCK  
TERMINAL BLOCK  
VARISTOR  
TB  
TB  
1
1
1
1
1
1
1
1
1
TB  
NR11  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RECEIVER P. C. BOARD  
SLEEVE BEARING  
INDOOR COIL THERMISTOR RT12  
ROOM TEMPERATURE THERMISTOR RT11  
3.15A  
FUSE  
FAN GUARD  
F11  
E02 138 520  
19  
76  
OUTDOOR UNIT  
STRUCTURAL PARTS  
17  
20  
19  
E1  
MUH-18NV -  
MUH-18NV -  
MUH-18NV -  
E2  
12  
E3  
10  
8
4
1
22  
15  
16  
3
9
5
2
7
14  
6
Part number that are circled is not shown in the illustration.  
Symbol  
Q'ty/unit  
in Wiring  
Diagram  
MUH-18NV-  
NO.  
Part No.  
Part Name  
CABINET  
Remarks  
E1  
E2  
E3  
E02 141 232  
E02 141 521  
E02 141 245  
E02 139 630  
E02 139 515  
E02 139 900  
E02 139 290  
E02 144 301  
E02 141 501  
E02 082 353  
E02 004 340  
E02 139 374  
E02 198 374  
E02 139 936  
E02 139 937  
E02 138 506  
E02 139 662  
E02 150 661  
E02 140 233  
E02 095 382  
E02 139 451  
E02 198 451  
E02 139 310  
E02 139 490  
E02 077 961  
E02 128 383  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
GRILLE  
3
SERVICE PANEL  
4
OUTDOOR HEAT EXCHANGER  
MOTOR SUPPORT  
COMPRESSOR  
5
6
NH-36VMDT  
RA6V50 -  
MC  
MF  
7
BASE  
8
OUTDOOR FAN MOTOR  
PROPELLER FAN  
COMPRESSOR CAPACITOR  
CONTACTOR  
9
10  
11  
50+/440V  
C1  
52C  
TB  
TERMINAL BLOCK  
TERMINAL BLOCK  
CAPILLARY TUBE  
CAPILLARY TUBE  
COMPRESSOR RUBBER SET  
STOP VALVE(LIQUID)  
STOP VALVE(GAS)  
BACK PANEL  
12  
13  
1
2
1
4
1
1
1
1
1
2
1
4
1
1
1
1
TB  
2
1
4
1
1
1
1
1
{3.0{1.6750  
{3.0{2.0800  
14  
15  
16  
17  
18  
{6.35  
{15.88  
FUSE  
F61  
DEICER P.C. BOARD  
DEICER P.C. BOARD  
DEFROST THERMISTOR  
REVERSING VALVE COIL  
REVERSING VALVE  
SURGE ABSORBER  
19  
1
1
1
1
1
1
1
1
1
1
20  
21  
22  
23  
1
1
1
1
RT61  
21S4  
DSAR  
77  
OUTDOOR UNIT  
STRUCTURAL PARTS  
17  
E1  
MUH-24NV-  
MUH-24NV-  
E2  
13  
1
22  
2
7
5
3
19 10 18  
11  
24  
23  
8
4
9
20  
12  
14 6  
15  
16  
78  
OUTDOOR UNIT  
STRUCTURAL PARTS  
E1  
MUH-24NV-  
MUH-24NV-  
E2  
Part number that are circled is not shown in the illustration.  
Symbol  
Q'ty/unit  
in Wiring  
MUH-24NV-  
MUH-24NV-  
NO.  
Part No.  
Part Name  
CABINET  
Remarks  
E1  
E2  
Diagram  
1
2
E02 214 232  
E02 214 521  
E02 214 245  
E02 214 630  
E02 214 515  
E02 042 900  
E02 214 290  
E02 214 301  
E02 214 501  
E02 082 353  
E02 010 342  
E02 198 374  
E02 214 249  
E02 138 506  
E02 010 662  
E02 010 661  
E02 214 297  
E02 138 351  
E02 214 451  
E02 214 310  
E02 176 936  
E02 256 936  
E02 262 936  
E02 214 522  
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
FAN GUARD  
3
SERVICE PANEL  
4
OUTDOOR HEAT EXCHANGER  
MOTOR SUPPORT  
COMPRESSOR  
5
6
NH-47VMDT  
RA6V85 -  
MC  
MF  
7
BASE  
8
OUTDOOR FAN MOTOR  
PROPELLER FAN  
COMPRESSOR CAPACITOR  
CONTACTOR  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
50+/440VAC  
C1  
52C1  
TB  
TERMINAL BLOCK  
SIDE PANEL  
COMPRESSOR RUBBER SET  
STOP VALVE(LIQUID)  
STOP VALVE(GAS)  
TOP PANEL  
{9.52  
{15.88  
3.0+/440VAC  
C11  
FAN MOTOR CAPACITOR  
DEICER P.C. BOARD  
DEFROST THERMISTOR  
CAPILLARY TUBE  
CAPILLARY TUBE  
CAPILLARY TUBE  
REAR PANEL  
RT61  
[3.0[1.6350  
[3.0[2.0350  
[4.0[2.4200  
21  
22  
23 E02 095 382  
24 E02 214 381  
25 E02 288 343  
2A  
FUSE  
TRS  
THERMAL READ SWITCH  
FAN MOTOR RELAY  
1
ACCESSORY AND REMOTE CONTROLLER PARTS  
E1  
MSH-07NV - (WH)  
E1  
MSH-09NV - (WH)  
2
E1  
MSH-12NV - (WH)  
E1  
MSH-18NV - (WH)  
E1  
MSH-24NV - (WH)  
E2  
MSH-07NV - (WH)  
E2  
MSH-09NV - (WH)  
E2  
MSH-12NV - (WH)  
E2  
MSH-18NV - (WH)  
E2  
MSH-24NV - (WH)  
E3  
MSH-18NV - (WH)  
Symbol  
in Wiring  
Diagram  
Q'ty/unit  
NO.  
Part No.  
Part Name  
Remarks  
E1  
E2  
MSH-07/09/12/18/24NV -  
(WH)  
E3  
MSH-18NV -  
(WH)  
1
1
E02 139 426 REMOTE CONTROLLER  
1
2
E02 141 083 REMOTE CONTROLLER HOLDER  
79  
13 OPTIONAL PARTS  
1. REFRIGERANT PIPES  
The air conditioner has flared connections its indoor and outdoor sides.  
Please use the optional extension pipe as follows.  
Additional  
refrigerant  
charge  
Pipe size O.D mm (in.)  
Model  
Part No.  
Pipe length  
Cross-section  
A-Gas  
B-Liquid  
Insulation  
R-22(g)  
C
D
MAC-440PI  
MAC-441PI  
MAC-442PI  
MAC-443PI  
MAC-660PI  
MAC-661PI  
MAC-662PI  
MAC-663PI  
MAC-664PI  
MAC-670PI  
MAC-671PI  
MAC-672PI  
MAC-673PI  
MAC-674PI  
MAC-860PIE  
MAC-861PIE  
MAC-862PIE  
MAC-863PIE  
MAC-864PIE  
3m  
5m  
7m  
10m  
3m  
5m  
E1  
E1  
E2  
E2  
MSH-07NV-  
MSH-09NV-  
MSH-07NV-  
MSH-09NV-  
0
150  
0
9.52 (3/8)  
27  
21  
E1  
E2  
MSH-12NV-  
MSH-12NV-  
7m  
12.7 (1/2)  
10m  
15m  
3m  
5m  
7m  
10m  
15m  
3m  
5m  
7m  
6.35 (1/4)  
150  
400  
E1  
0
MSH-18NV-  
MSH-18NV-  
MSH-18NV-  
E2  
E3  
31  
27  
150  
400  
15.88 (5/8)  
0
MSH-24NV-  
MSH-24NV-  
E1  
E2  
9.52 (3/8)  
10m  
15m  
195  
520  
2. AIR CLEANING FILTER  
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.  
Normal life of AIR CLEANING FILTER is 3 months. However, when it becomes dirty, replace it as soon as possible.  
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.  
DO NOT reuse AIR CLEANING FILTER even if it is washed.  
DO NOT remove or attach AIR CLEANING FILTER during unit operation.  
Part No.  
Model  
E1  
E2  
E2  
E2  
MSH-07NV-  
MSH-09NV-  
MSH-12NV-  
MSH-18NV-  
MSH-24NV-  
MSH-18NV-  
MSH-07NV-  
MSH-09NV-  
MSH-12NV-  
E1  
E1  
E1  
E1  
E2  
MAC-1000FT  
MAC-1100FT  
E2  
E3  
MSH-24NV-  
MSH-18NV-  
3. DEODORIZING FILTER  
DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odors of pets.  
Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.  
For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.  
When the filter color is still dark even after cleaning, replace the filter with a new one.  
Replace the filter at least once a year.  
Part No.  
Model  
E1  
E2  
E2  
E2  
E2  
E3  
MSH-07NV-  
MSH-09NV-  
MSH-12NV-  
MSH-18NV-  
MSH-24NV-  
MSH-18NV-  
MSH-07NV-  
E1  
E1  
E1  
E1  
E2  
MSH-09NV-  
MSH-12NV-  
MSH-24NV-  
MSH-18NV-  
MAC-1500DF  
MAC-1600DF  
DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.  
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO  
C Copyright 1997 MITSUBISHI ELECTRIC ENGINIEERING CO.,LTD  
Issued in Sep. 1997. No.OB207 646  
Printed in Japan  
New publication, effective Sep. 1997  
Specifications subject to change without notice.  

Lexmark D02 User Manual
Mitsubishi Electronics Srk507j S User Manual
Multi Tech Systems All In One Printer Mt5600ba User Manual
Panasonic Workio Dp 8020p User Manual
Samsung Sh09zs8x User Manual
Sanyo N 4000drl User Manual
Sharp Al 1255 User Manual
Sharp Ux 465l User Manual
Simplicity Sac8017ee User Manual
Tekkeon Tekcharge Mp1580 User Manual