This Servise Manual OB207 deals with MSH-07/09/12/18/24NV-E1,
MUH-07/09/12/18/24NV-E1, MSH-18NV-E2, and MUH-18NV-E2 in
OB176 REVISED EDITION-A issued in July in1997.
Therefore, please refer to OB207, not to OB176 REVISED
EDITION-A, for the above models.
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
No. OB207
SERVICE MANUAL
Wireless type
Models
MSH-07NV - · MUH-07NV -
E1
E1
(
)
WH
E1
MSH-09NV - · MUH-09NV -
E1
E1
E1
E1
E2
E2
E2
E2
E2
E3
(
)
WH
E1
MSH-12NV - · MUH-12NV -
(
)
WH
E1
MSH-18NV - · MUH-18NV -
(
)
WH
E1
MSH-24NV - · MUH-24NV -
(
)
WH
E2
MSH-07NV - · MUH-07NV -
(
)
WH
E2
MSH-09NV - · MUH-09NV -
(
)
WH
E2
MSH-12NV - · MUH-12NV -
(
)
WH
E2
MSH-18NV - · MUH-18NV -
(
)
WH
E2
MSH-24NV - · MUH-24NV -
(
)
WH
E3
MSH-18NV - · MUH-18NV -
(
)
WH
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································6
4. OUTLINES AND DIMENSIONS ······················ 11
5. WIRING DIAGRAM ··········································15
6. REFRIGERANT SYSTEM DIAGRAM··············24
7. PERFORMANCE CURVES······························29
8. MICROPROCESSOR CONTROL ····················33
9. SERVICE FUNCTIONS ····································44
10. TROUBLESHOOTING······································47
11. DISASSEMBLY INSTRUCTIONS·····················60
12. PARTS LIST······················································70
13. OPTIONAL PARTS ····································BACK
E1
E2
E3
MSH-18NV -
MSH-18NV -
MSH-18NV -
E1
E2
E3
Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-
E1
are connected with MXZ-32NV-
as multi system units.
2
PART NAMES AND FUNCTIONS
INDOOR UNIT
E1
E2
E2
E2
E1
E1
E2
E2
E3
MSH-07NV -
MSH-09NV -
MSH-12NV -
MSH-07NV -
MSH-09NV -
MSH-12NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
E1
E1
(When the front panel is open)
E1
E2
E1
E2
E1
E2
MSH-07NV -
MSH-07NV -
MSH-09NV -
MSH-09NV -
MSH-12NV -
MSH-12NV -
E1
E1
E2
E1
E2
MSH-07NV -
MSH-07NV -
MSH-09NV -
MSH-09NV -
MSH-12NV -
MSH-12NV -
E2
E1
E2
E1
E3
E2
MSH-18NV -
MSH-24NV -
E2
MSH-24NV -
MSH-18NV -
MSH-18NV -
E1
E2
E1
E3
MSH-18NV -
MSH-24NV -
MSH-24NV -
MSH-18NV -
MSH-18NV -
OUTDOOR UNIT
E1
E1
E1
MUH-07NV -
MUH-09NV -
MUH-07NV -
MUH-09NV -
MUH-12NV -
MUH-18NV -
MUH-18NV -
MUH-18NV -
MUH-24NV -
MUH-24NV -
E1
E1
E2
E3
E2
E2
E2
3
E1
E1
E1
E1
E2
MSH-07NV -
MSH-09NV -
MSH-12NV -
MSH-18NV -
MSH-18NV -
REMOTE CONTROLLER
4
E1
E1
MSH-07NV - (Serial number 7000201T~) MSH-09NV - (Serial number 7000201T~)
E1
E1
E2
E2
MSH-12NV - (Serial number 7000001T~) MSH-24NV -
E2
MSH-07NV -
MSH-12NV -
MSH-24NV -
MSH-09NV -
E2
E2
MSH-18NV - (Serial number 7000001T~)
E3
MSH-18NV -
5
3
SPECIFICATION
E1
E2
E1
E2
Model
Function
MSH-07NV -
Cooling
MSH-09NV -
Cooling
Heating
Heating
Power supply
Capacity
Single phase,220-240V,50HzSingle phase,220-240V,50Hz
2.2
0.8
2.5
—
2.5
1.1
3.1
—
kW
Capacity
R/h
Dehumidification
Air flow
K /h INDOOR 492 OUTDOOR 1620 INDOOR 492 OUTDOOR 1620
A
A
10
10
Power outlet
3.30-3.20
710-750
—
3.15-3.05
680-720
—
4.10-4.00
880-920
—
4.30-4.10
920-940
—
Running current
Power input
W
A(kW)
%
Auxiliary heater
Power factor
98-96
97-96
Electrical data
98-98
25
A
25
Starting current
Compressor motor current
Fan motor current
2.80-2.70
2.65-2.55
3.60-3.50
3.80-3.60
A
A
INDOOR 0.17 OUTDOOR 0.33 INDOOR 0.17 OUTDOOR 0.33
3.10-2.93 3.68-3.47
2.84-2.72 3.37-3.30
RH-135VGHT RH-174VGHT
Coefficient of performance(C.O.P)
Model
Compressor
Output
W
650
800
"
C-R4.17 C-S5.75
RC4V19-AA
C-R3.26 C-S5.82
RC4V19-AA
Winding resistance(at20:)
Indoor
Model
fan motor
Outdoor
fan motor
"
WHT-BLK292 BLK-RED324 WHT-BLK292 BLK-RED324
RA6V29-CB RA6V29-CB
WHT-BLK218.0 BLK-RED423.7 WHT-BLK218.0 BLK-RED423.7
Winding resistance(at20:)
Model
"
Winding resistance(at20:)
Width
mm
mm
mm
mm
mm
mm
kg
815
275
183
780
540
255
8
815
275
183
780
540
255
8
Indoor unit
Height
Depth
Width
Height
Depth
Dimensions
Weight
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
kg
34
34
5
5
dB
dB
37
37
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
47
48
rpm
rpm
1,100
790-820
4
1,100
790-820
4
Fan speed
(Hi)
Special remarks
Fan speed
regulator
1
1
kg
k"
k"
k"
0.85
10
0.85
10
Refrigerant filling capacity(R-22)
RT11(at25:)
10
10
Thermistor
RT12(at25:)
33.18
33.18
RT61(at0:)
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
6
E1
E2
E1
E2
E3
Model
Function
MSH-12NV -
Cooling
MSH-18NV -
Cooling
Heating
Heating
Power supply
Single phase,220-240V,50HzSingle phase,220-240V,50Hz
3.4
1.6
4.0
—
5.1
2.5
5.4
—
kW
Capacity
Capacity
R/h
Dehumidification
Air flow
K /h INDOOR 558 OUTDOOR 2130-2244 INDOOR 756 OUTDOOR 2142
A
A
10
15
Power outlet
5.75-5.90
1220-1300
—
5.95-6.10
1260-1350
—
9.4-9.2
2030-2120
—
9.2-9.0
1980-2070
—
Running current
Power input
W
A(kW)
%
Auxiliary heater
Power factor
96-92
96-92
98-96
98-96
Electrical data
A
35
52-58
8.76-8.56 8.56-8.36
Starting current
Compressor motor current
Fan motor current
5.21-5.36
5.41-5.56
A
A
INDOOR 0.17 OUTDOOR 0.37 INDOOR 0.25 OUTDOOR 0.39
2.78-2.61 3.17-2.96
2.51-2.41 2.73-2.61
RH-231VHAT NH-36VMDT
Coefficient of performance(C.O.P)
Model
Compressor
Output
W
1100
1700
"
C-R2.1 C-S3.9
RC4V19-AA
C-R1.2 C-S2.7
RA4V27-EA
Winding resistance(at20:)
Indoor
Model
fan motor
Outdoor
fan motor
"
WHT-BLK292 BLK-RED324 WHT-BLK183.8 BLK-RED250.5
RA6V40-EC or EE RA6V50-OD or OF
WHT-BLK130 BLK-RED134.6 WHT-BLK116.4 BLK-RED111.0
Winding resistance(at20:)
Model
"
Winding resistance(at20:)
Width
mm
mm
mm
mm
mm
mm
kg
815
275
183
850
605
290
8
1015
320
190
850
605
290
14
Indoor unit
Height
Depth
Width
Height
Depth
Dimensions
Weight
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
kg
43
59
5
5
dB
dB
42
42
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
50
52
rpm
rpm
1230
780-820
4
1180
810-845
4
Fan speed
(Hi)
Special remarks
Fan speed
regulator
1
1
kg
k"
k"
k"
1.15
10
1.8
Refrigerant filling capacity(R-22)
10
RT11(at25:)
10
10
Thermistor
RT12(at25:)
33.18
33.18
RT61(at0:)
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15°.5C
Outdoor DB 7°C / WB 6°C
7
E1
E2
Model
Function
MSH-24NV -
Cooling
Heating
Power supply
Single phase,220-240V,50Hz
kW
R/h
K /h
A
6.0
3.1
6.2
—
Capacity
Capacity
Dehumidification
Air flow
816
25
Power outlet
A
12.6-11.7
11.5-11.0
Running current
Power input
W
2720-2750 2470-2580
A(kW)
%
—
Auxiliary heater
Power factor
Electrical data
98
A
59
Starting current
Compressor motor current
Fan motor current
A
11.73-10.83 10.63-10.13
INDOOR 0.29 OUTDOOR 0.58
A
2.21-2.18
2.51-2.40
Coefficient of performance(C.O.P)
Model
NH-47VMDT
Compressor
Output
W
2200
"
C-R 0.96 C-S 2.07
Winding resistance(at20:)
Indoor
RA4V27-EC
Model
fan motor
Outdoor
fan motor
"
WHT-BLK183.8 BLK-RED250.5
Winding resistance(at20:)
Model
RA6V85-AA
"
WHT-BLK62.7 BLK-YLW30.2 YLW-RED62.9
Winding resistance(at20:)
Width
mm
mm
mm
mm
mm
mm
kg
1015
320
190
870
850
295
14
Indoor unit
Height
Depth
Width
Height
Depth
Dimensions
Weight
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
kg
72
5
dB
dB
45
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
53
rpm
rpm
1,260
720-750
4
Fan speed
(Hi)
Special remarks
Fan speed
regulator
2
kg
k"
k"
k"
2.4
Refrigerant filling capacity(R-22)
10
RT11(at25:)
10
Thermistor
RT12(at25:)
33.18
RT61(at0:)
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
8
E1
E2
E3
Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-
are
E1
connected with MXZ-32NV-
as multi system units.
Model
E1 E2
E1 E2
(INDOOR UNIT) MSH-09NV- (INDOOR UNIT)
MSH-07NV-
Function
Cooling
Heating
Cooling
Heating
Power supply
Single phase,220-240V,50Hz Single phase,220-240V,50Hz
kW
R/h
K /h
A
—
—
—
—
—
—
—
—
Capacity
Capacity
Dehumidification
Air flow
492
492
10
10
Power outlet
A
0.17
0.17
Running current
Power input
W
35
35
A(kW)
%
—
—
Auxiliary heater
Power factor
Electrical data
94-86
94-86
A
—
—
Starting current
Compressor motor current
Fan motor current
A
—
—
A
0.17
0.17
—
—
Coefficient of performance(C.O.P)
Model
—
—
Compressor
Output
W
—
—
—
—
"
Winding resistance(at20:)
Indoor
RC4V19-AA
RC4V19-AA
Model
fan motor
Outdoor
fan motor
"
WHT-BLK292 BLK-RED324 WHT-BLK292 BLK-RED324
Winding resistance(at20:)
Model
—
—
—
—
"
Winding resistance(at20:)
Width
mm
mm
mm
mm
mm
mm
kg
815
275
183
—
815
275
183
—
Indoor unit
Height
Depth
Width
Height
Depth
Dimensions
Weight
—
—
Outdoor unit
—
—
8
8
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
kg
—
—
5
5
dB
dB
37
—
37
—
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
rpm
rpm
1,100
—
1,100
—
Fan speed
(Hi)
Special remarks
4
4
Fan speed
regulator
—
—
kg
k"
k"
k"
—
—
Refrigerant filling capacity(R-22)
10
10
—
10
10
—
RT11(at25:)
Thermistor
RT12(at25:)
RT61(at0:)
Please refer to Service manual OB185 for capacity.
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
9
E1
E2
E3
Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-
are
E1
connected with MXZ-32NV-
as multi system units.
E1 E2
E2 E3
Model
MSH-12NV-
(INDOOR UNIT)MSH-18NV-
(INDOOR UNIT)
Heating
Function
Cooling
Heating
Cooling
Power supply
Single phase,220-240V,50Hz Single phase,220-240V,50Hz
kW
R/h
K /h
A
—
—
—
—
Capacity
Capacity
—
—
Dehumidification
Air flow
558
756
10
10
Power outlet
A
0.17
0.28
Running current
Power input
W
35
60
A(kW)
%
—
—
Auxiliary heater
Power factor
Electrical data
94-86
97-89
A
—
—
Starting current
Compressor motor current
Fan motor current
A
—
—
A
0.17
0.25
—
—
Coefficient of performance(C.O.P)
Model
—
—
Compressor
Output
W
—
—
—
—
"
Winding resistance(at20:)
Indoor
RA4V19-AA
RA4V27-EA
Model
fan motor
Outdoor
fan motor
"
WHT-BLK292 BLK-RED324 WHT-BLK184 BLK-RED251
Winding resistance(at20:)
Model
—
—
—
—
"
Winding resistance(at20:)
Width
mm
mm
mm
mm
mm
mm
kg
815
275
183
—
1015
320
190
—
Indoor unit
Height
Depth
Width
Height
Depth
Dimensions
Weight
—
—
Outdoor unit
—
—
8
14
—
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
kg
—
5
5
dB
dB
42
—
42
—
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
rpm
rpm
1,230
—
1,180
—
Fan speed
(Hi)
Special remarks
4
4
Fan speed
regulator
—
—
kg
k"
k"
k"
—
—
Refrigerant filling capacity(R-22)
10
10
—
10
10
—
RT11(at25:)
Thermistor
RT12(at25:)
RT61(at0:)
Please refer to Service manual OB185 for capacity.
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
10
4
OUTLINES AND DIMENSIONS
Unit: mm
E1
E1
E2
E2
MSH-07NV -
MSH-09NV -
MSH-07NV -
MSH-09NV -
INDOOR UNIT
E1
E1
E2
E2
MUH-07NV -
MUH-09NV -
MUH-07NV -
MUH-09NV -
OUTDOOR UNIT
11
Unit: mm
E1
E2
MSH-12NV -
MSH-12NV -
INDOOR UNIT
9.52
E1
E2
MUH-12NV -
MUH-12NV -
OUTDOOR UNIT
If the right/left sides or
back side is vacant,the
front has only to be 50cm
unobstructed.
12
Unit: mm
E1
E1
E2
E2
E3
MSH-18NV -
MSH-24NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
INDOOR UNIT
Indoor unit
217
4holes 11✕20
150
648
995
450
450
438
352
Wall hole [75
Installation plate
190
1015
5
Installation plate
Liquid line [8-0.5m
Gas linee [12-0.43m
Insulatiion [50 O.D
[28 I.D
Air in
{
Drain hose [16
Insulattion [28
50
775
190
Air out
Power suppply cord
Lead too right 2m
Lead too left 1m
17.5
56
E1
E2
E3
MUH-18NV -
MUH-18NV -
MUH-18NV -
OUTDOOR UNIT
If the right/left sides or
back side is vacant,the
front has only to be 50cm
unobstructed.
13
E1
E2
MUH-24NV-
MUH-24NV-
Unit : mm (inch)
4 5
5 3
1 5 0
2 0 0
2 5 m a x .
8 0
5 0 0
1 7
8 5 0 ( 3 3 - 7 / 1 6 )
5 5 3
4 5
4 2
3 6 2 ( 1 4 - 1 / 4 )
3 3 0 ( 1 3 ) 1 5
2 7 . 5 3 9 . 5
3 5 2
3 3 7
1 7
4 0 3
5 2 4
1 7 9
4 4 1
3 3
2 3
2 0 0
1 3 8
14
5
WIRING DIAGRAM
MODELS WIRING DIAGRAM
E1
MSH-07NV -
MSH-09NV -
E1
INDOOR UNIT
❈
❈
❈
~
❈
❈
❈
~/N
FOR MULTI SYSTEM
L
3
2
N
12VDC
TO OUTDOOR
UNIT
CONNECTING
;
SYMBOL
C11
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
TERMINAL BLOCK
VANE MOTOR
INDOOR FAN CAPACITOR
FUSE(93:)
VARISTOR
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
CONTACTOR
F12
MV
FUSE(3.15A)
SOLID STATE RELAY
F11
RT12
SR11
INDOOR FAN MOTOR
MF
52C
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E1
MUH-07NV -
MUH-09NV -
MODELS WIRING DIAGRAM
E1
OUTDOOR UNIT
❈
❈
❈
❈
❈
❈
❈
SYMBOL
NAME
SYMBOL
MF
NAME
SYMBOL
X62
NAME
COMPRESSOR CAPACITOR
OUTDOOR FAN MOTOR CAPACITOR
CONTACTOR
OUTDOOR FAN MOTOR
VARISTOR
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
DC/DC CONVERTER
C1
C65
52C
F61
MC
NR61
RT61
SR61
TB
21S4
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
IC881
FUSE(2A)
COMPRESSOR(INNER THERMOSTAT)
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
15
E1
MODEL WIRING DIAGRAM
MSH-12NV -
INDOOR UNIT
❈
❈
❈
~
❈
❈
❈
~/N
FOR MULTI SYSTEM
L
3
2
N
12VDC
TO OUTDOOR
UNIT
CONNECTING
;
SYMBOL
C11
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
TERMINAL BLOCK
VANE MOTOR
INDOOR FAN CAPACITOR
FUSE(93:)
VARISTOR
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
CONTACTOR
F12
MV
FUSE(3.15A)
SOLID STATE RELAY
F11
RT12
SR11
INDOOR FAN MOTOR
MF
52C
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E1
MODEL WIRING DIAGRAM
MUH-12NV -
OUTDOOR UNIT
❈
❈
❈
❈
❈
❈
SYMBOL
NAME
COMPRESSOR CAPACITOR
SYMBOL
MF
NAME
SYMBOL
X62
NAME
OUTDOOR FAN MOTOR
VARISTOR
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
DC/DC CONVERTER
C1
C65
52C
F61
MC
OUTDOOR FAN MOTOR CAPACITOR
CONTACTOR
NR61
RT61
SR61
TB
21S4
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
IC881
FUSE(2A)
COMPRESSOR(INNER THERMOSTAT)
NOTE:1. Use copper conductors only.(For field wiring)
2. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block,
: Connector
16
E1
MSH-18NV -
MODEL WIRING DIAGRAM
INDOOR UNIT
❈
❈
❈
❈
❈
❈
SYMBOL
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
INDOOR FAN CAPACITOR
FUSE(93:)
VARISTOR
TERMINAL BLOCK
SURGE ABSORBER
DC/DC CONVERTER
C11
F12
F11
MF
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
HYBRID IC
DSAR
HIC1
FUSE(3.15A)
RT12
IC141
52C
INDOOR FAN MOTOR
VANE MOTOR
CONTACTOR
MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E1
MUH-18NV -
MODEL WIRING DIAGRAM
OUTDOOR UNIT
❈
❈
❈
❈
❈
SYMBOL
NAME
COMPRESSOR CAPACITOR
SYMBOL
MF
NAME
SYMBOL
X62
NAME
OUTDOOR FAN MOTOR
VARISTOR
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
C1
C65
DSAR
F61
OUTDOOR FAN MOTOR CAPACITOR
SURGE ABSORBER
FUSE(2A)
NR61
RT61
SR61
TB
21S4
52C
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
COMPRESSOR<INNER THERMOSTAT>
MC
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
17
E1
MSH-24NV -
MODEL WIRING DIAGRAM
TB
220-240V~
INDOOR UNIT
3
2
RED
❈
❈
CN
RT12
RT11
112
F12
220-240V~
HIC1
WHT
IC141
CN
111
L
NF
BLU2
1
TO OUTDOOR
UNIT
BLU
3
4
BRN
3
BRN
4
CN
121
CN201
52C
YLW
GRY
WHT
RED
BLK
N
❈
CONNECTING
3
❈
BLU
3
TRANS
CN211
1
MF
BLU
4
2
1
WHT
F11
POWER
SUPPLY
CORD
CN
151
CN
101
CN
102
ELECTRONIC CONTROL P.C BOARD
~/N 220-240V
5
50Hz
3
3
MV
DISPLAY
RECEIVER
P.C.BOARD
CIRCUIT BREAKER
GRN/YLW
P.C.BOARD
REMOTE
CONTROLLER
SYMBOL
C11
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
TERMINAL BLOCK
DC/DC CONVERTER
NOISE FILTER
INDOOR FAN MOTOR CAPACITOR
FUSE(93:)
VARISTOR
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
HYBRID IC
F12
HIC1
NF
FUSE(3.15A)
F11
RT12
IC141
52C
INDOOR FAN MOTOR
VANE MOTOR
MF
CONTACTOR
MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E1
MUH-24NV -
MODEL WIRING DIAGRAM
RT61
X1
5
3
OUTDOOR UNIT
6
5
4
3
2
21S4
YLW 1
YLW
BLK
WHT
ORN
BRN
BLK
WHT
ORN
RED RED
MF
1
2
3
4
CN661
CN721
CN711
C2
1
CN730
X62
TB
3
2
1
3
12VDC ❈
RED
IC881
WHT
❈
220-240V~2 WHT
F
ORN
RED
TB2
BLU
7
8
RED
BLU
❈
X1
TRANS
26F1
N
TAB20
❈
YLW
52C
DEICER
P.C. BOARD
52C1
❈
3
4 ❈
VLT CR
WHT
CZ
52C1
YLW
WHT
WHTWHT
C
2
1
C1
MC
BLU
R
S
RED
BLK
SYMBOL
C1
NAME
SYMBOL
NAME
SYMBOL
X62
NAME
SYMBOL
NAME
OUTDOOR FAN MOTOR
COMPRESSOR CAPACITOR
OUTDOOR FAN MOTOR CAPACITOR
SURGE ABSORBER 1
FUSE(2A)
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
FUSE(2A)
MF
NR61
RT61
F
<INNER THERMOSTAT>
VARISTOR
THERMOSTAT (AIR FLOW CONTROL)
DC/DC CONVERTER
C2
21S4
52C
26F1
IC881
CR
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
DSAR
F61
COMPRESSOR CONTACTOR
FAN MOTOR RELAY
SURGE ABSORBER 2
SURGE ABSORBER 3
SR61
52C1
X1
COMPRESSOR<INNER THERMOSTAT>
MC
TB. TB2
CZ
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
18
E2
E2
E2
MSH-07NV - MSH-09NV - MSH-12NV -
MODELS WIRING DIAGRAM
INDOOR UNIT
TO OUTDOOR
UNIT
TB
SR11
L
CN
BRN
RT12
RT11
❈
112
CONNECTING
BRN
❈
HIC1
CN
111
3
12VDC
RED
❈
BLU
F12
BLK
CN201
3
1
2
1
2
3
4
5
6
2
❈
220-240V~
WHT
3
BLU
GRY
YLW
NR11
C11
CN
121
52C
3
2
1
❈
4
N
BLU
TRANS
BLU
MF
❈
BRN
3
2
1
WHT
RED
BLU
F11
1
CN
122
POWER
SUPPLY
CORD
CN211
CN
151
LD101
GUARD
PLATE
ELECTRONIC CONTROL P.C BOARD
~/N 220-240V
50Hz
5
5
POWER MONITOR,
RECEIVER
MV
CIRCUIT BREAKER
P.C.BOARD
FOR MULTI SYSTEM
L
3
TO OUTDOOR12VDC
UNIT
2
REMOTE
N
CONNECTING
CONTROLLER
SYMBOL
C11
NAME
SYMBOL
NAME
SYMBOL
TERMINAL BLOCK
TB
NAME
INDOOR FAN MOTOR CAPACITOR
FUSE(93:)
VARISTOR
NR11
RT11
RT12
52C
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
CONTACTOR
DC/DC CONVERTER
SOLID STATE RELAY
VANE MOTOR
F12
HIC1
SR11
MV
FUSE(3.15A)
F11
INDOOR FAN MOTOR
MF
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E2
E2
MUH-07NV -
MUH-09NV -
MODELS WIRING DIAGRAM
21S4
OUTDOOR UNIT
RT61
CN661
CN721
TB
3
MF
X62
F61
12VDC
❈
RED
SR61
1
CN730
RED
WHT
2
1
2
3
4
220-240V~
❈
❈
C65
IC881
NR61
TRANS
N
BLU
WHT
BLK
TAB20
BLU
52C
4 3
CN711
X62
❈
❈
DEICER P.C. BOARD
WHT
C
C1
MC
GRN/YLW
RED
R
S
❈
❈
BLK
SYMBOL
C1
NAME
NAME
NAME
NAME
SYMBOL
SYMBOL
X62
SYMBOL
C65
OUTDOOR FAN MOTOR
COMPRESSOR CAPACITOR
FUSE(2A)
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
FAN MOTOR CAPACITOR
DC/DC CONVERTER
TERMINAL BLOCK
MF
<INNER THERMOSTAT>
VARISTOR
F61
NR61
RT61
21S4
52C
IC881
TB
COMPRESSOR<INNER THERMOSTAT>
SOLID STATE RELAY
DEFROST THERMISTOR
MC
SR61
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
19
E2
MUH-12NV -
MODEL WIRING DIAGRAM
OUTDOOR UNIT
21S4
RT61
TB
MF
12VDC
3
RED
WHT
BLU
CN661
CN721
❈
❈
❈
1
X62
CN730
RED
WHT
RED
1
2
3
4
1
2
3
4
SR61
220-240V~ 2
N
ORN
WHT
BLK
BLK
TRANS
❈
CN711
52C
TAB20
X62
❈
3
❈
4
DEICER P.C.BOARD
GRN/YLW
C
WHT
C1
BLU
RED
BLK
S MC
R
SYMBOL
C1
NAME
NAME
NAME
NAME
SYMBOL
SYMBOL
X62
SYMBOL
C65
OUTDOOR FAN MOTOR
COMPRESSOR CAPACITOR
FUSE(2A)
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
FAN MOTOR CAPACITOR
DC/DC CONVERTER
TERMINAL BLOCK
MF
<INNER THERMOSTAT>
VARISTOR
F61
NR61
RT61
21S4
52C
IC881
TB
COMPRESSOR<INNER THERMOSTAT>
SOLID STATE RELAY
DEFROST THERMISTOR
MC
SR61
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
20
E2
MSH-18NV -
MODEL WIRING DIAGRAM
INDOOR UNIT
❈
❈
❈
❈
❈
❈
~/N
FOR MULTI SYSTEM
L
3
2
N
12VDC
TO OUTDOOR
UNIT
CONNECTING
;
SYMBOL
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
INDOOR FAN CAPACITOR
FUSE(93:)
VARISTOR
TERMINAL BLOCK
SURGE ABSORBER
DC/DC CONVERTER
C11
F12
F11
MF
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
HYBRID IC
DSAR
HIC1
FUSE(3.15A)
RT12
IC141
52C
INDOOR FAN MOTOR
VANE MOTOR
CONTACTOR
MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E2
MUH-18NV -
MODEL WIRING DIAGRAM
OUTDOOR UNIT
❈
❈
❈
❈
❈
SYMBOL
NAME
COMPRESSOR CAPACITOR
SYMBOL
MF
NAME
SYMBOL
X62
NAME
OUTDOOR FAN MOTOR
VARISTOR
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
C1
C65
DSAR
F61
OUTDOOR FAN MOTOR CAPACITOR
SURGE ABSORBER
FUSE(2A)
NR61
RT61
SR61
TB
21S4
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
52C
DC/DC CONVERTER
IC881
COMPRESSOR<INNER THERMOSTAT>
MC
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
21
E2
MSH-24NV -
MODEL WIRING DIAGRAM
INDOOR UNIT
TB
❈
220-240V~
3
RED
WHT
CN
RT12
RT11
112
F12
220-240V~ 2
HIC1
IC141
❈
CN
111
L
TO OUTDOOR
UNIT
NF
BLU2
1
3
BLU
BRN
3
BRN
4
❈
3
CN
121
CN201
3
1
52C
YLW
GRY
WHT
RED
BLK
4
CONNECTING
N
❈
BLU
BLU
TRANS
CN211
MF
4
2
1
F11
WHT
POWER
SUPPLY
CORD
CN
CN
101
CN
102
151 ELECTRONIC CONTROL P.C BOARD
5
~/N 220-240V
50Hz
3
3
MV
RECEIVER
DISPLAY
P.C.BOARD
P.C.BOARD
CIRCUIT BREAKER
GRN/YLW
REMOTE
CONTROLLER
SYMBOL
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
INDOOR FAN CAPACITOR
FUSE(93:)
VARISTOR
TERMINAL BLOCK
NOISE FILTER
C11
F12
F11
MF
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
HYBRID IC
NF
FUSE(3.15A)
DC/DC CONVERTER
RT12
IC141
52C
HIC1
INDOOR FAN MOTOR
VANE MOTOR
CONTACTOR
MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E2
MUH-24NV -
MODEL WIRING DIAGRAM
RT61
OUTDOOR UNIT
X1
6
5
4
21S4
1
YLW
BLK
YLW
BLK
5
BRN
3
WHT WHT
MF
3
ORN
RED
ORN
RED
CN661
CN721
2
1
CN711 1 2 3 4
C2
CN730
X62
TB
3
3
2
1
12VDC
❈
RED
IC881
TRANS
WHT
2
220-240V~
❈
WHT F
RED
RED 8
BLU
ORN
❈
7
X1
TB2
26F1
N
TAB20
❈
BLU
52C
YLW
A2
52C1
CR
DEICER
A1
3 ❈ 4
❈
P.C. BOARD
VLT
WHT
YLW
CZ
WHT
52C1
WHT
WHT
C
1
2
MC
S
R
BLU
C1
RED
BLK
SYMBOL
NAME
SYMBOL
MF
NAME
SYMBOL
X62
NAME
COMPRESSOR CAPACITOR
FAN MOTOR CAPACITOR
SURGE ABSORBER 1
SURGE ABSORBER 2
SURGE ABSORBER 3
FUSE(2A)
OUTDOOR FAN MOTOR
VARISTOR
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
C1
C2
NR61
RT61
SR61
TB,TB2
F
21S4
52C
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
FUSE(2A)
DSAR
CR
COMPRESSOR CONTACTOR
DC/DC CONVERTER
FAN MOTOR RELAY
52C1
IC881
X1
CZ
F61
MC
COMPRESSOR<INNER THERMOSTAT>
THERMOSTAT (AIR FLOW CONTROL)
26F1
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
22
E3
MSH-18NV -
MODEL WIRING DIAGRAM
TO OUTDOOR
TB
INDOOR UNIT
UNIT
L
3
BRN
❈
CN
112
RT12
CONNECTING
HIC1
BRN
❈
IC141
12VDC
RED
❈
BLU
F12
3
BRN
CN
121
4
2
2
220-240V~
WHT
❈
BLU 1
❈
YLW
GRY
WHT
RED
BLK
52C
CN201
3
1
3
CN211
N
TRANS
MF
BLU
❈
BLU
4
2
1
CN
111
BLU
BRN
F11
LD1
POWER
SUPPLY
CORD
CN
151
CN CN
102
RT11
101
ELECTRONIC CONTROL P.C BOARD
~/N 220-240V
50Hz
5
3
3
MV
GRN/YLW
DISPLAY
RECEIVER
P.C.BOARD
CIRCUIT BREAKER
P.C.BOARD
FOR MULTI SYSTEM
L
12VDC 3
TO OUTDOOR
UNIT
2
REMOTE
N
CONTROLLER
CONNECTING
SYMBOL
NAME
SYMBOL
NR11
RT11
NAME
SYMBOL
TB
NAME
INDOOR FAN CAPACITOR
FUSE(93:)
VARISTOR
TERMINAL BLOCK
C11
F12
F11
MF
ROOM TEMPERATURE THERMISTOR
INDOOR COIL THERMISTOR
HYBRID IC
SURGE ABSORBER
DC/DC CONVERTER
DSAR
HIC1
FUSE(3.15A)
RT12
IC141
52C
INDOOR FAN MOTOR
VANE MOTOR
CONTACTOR
MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block,
: Connector
E3
MUH-18NV -
MODEL WIRING DIAGRAM
OUTDOOR UNIT
21S4
52C
RT61
TB
❈
MF
CN730
1
12VDC
3
RED
WHT
CN661
F61
CN721
CN720
SR61
X62
RED
WHT
RED
❈
❈
1
2
3
4
1
2
3
4
220-240V~2
N
ORN
WHT
BLK
TAB21
❈ BLU
BLK
TRANS
❈
CN711
X62
TAB20
DEICER P.C.BOARD
52C
WHT
WHT NO
BLU
COM
GRN/YLW
C
C1
RED
BLK
MC
S
R
SYMBOL
NAME
SYMBOL
MF
NAME
SYMBOL
X62
NAME
COMPRESSOR CAPACITOR
OUTDOOR FAN MOTOR CAPACITOR
SURGE ABSORBER
OUTDOOR FAN MOTOR
VARISTOR
REVERSING VALVE COIL RELAY
REVERSING VALVE COIL
CONTACTOR
C1
C65
DSAR
F61
NR61
RT61
SR61
TB
21S4
DEFROST THERMISTOR
SOLID STATE RELAY
TERMINAL BLOCK
52C
FUSE(2A)
DC/DC CONVERTER
IC881
COMPRESSOR<INNER THERMOSTAT>
MC
NOTE:1. Use copper conductors only.(For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers.
3. Symbols below indicate.
: Terminal block,
: Connector
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
4. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
23
6
REFRIGERANT SYSTEM DIAGRAM
Unit:mm
E1
E1
MSH-07NV -
MSH-07NV -
MUH-07NV -
MUH-07NV -
E2
E2
Refrigerant pipe [ 9.52
(Option)
Muffler
Reversing valve
(4-way valve)
INDOOR UNIT
OUTDOOR UNIT
(with heat insulator)
Indoor coil
Indoor
Outdoor
heat
exchanger
thermistor
RT12
heat
exchanger
Stop valve
(with service
port)
Strainer
Defrost
thermistor
RT61
Flared connection
Room temperature
thermistor
Capillary tube
[1.4x800 (2 pcs)
RT11
Accumulator
Capillary tube
[1.6x750
Check
valve
Flared connection
Reversing valve coil
(4-way valve coil)
heating ON
Strainer
Stop valve
Capillary tube
[1.4x850
Refrigerant pipe [6.35
(Option)
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
(with heat insulator)
Unit:mm
E1
E1
MUH-09NV -
MSH-09NV -
MSH-09NV -
MSH-09NV -
E2
E2
Muffler
Refrigerant pipe [9.52
(Option)
Reversing valve
(4-way valve)
OUTDOOR UNIT
INDOOR UNIT
(with heat insulator)
Indoor coil
Indoor
thermistor
RT12
Outdoor
heat
exchanger
heat
exchanger
Stop valve
(with service
port)
Strainer
Defrost
thermistor
RT61
Flared connection
Room temperature
thermistor
Capillary tube
[1.4x800 (2 pcs)
RT11
Accumulator
Capillary tube
[1.6x400
Check
valve
Flared connection
Reversing valve coil
(4-way valve coil)
heating ON
Strainer
Stop valve
Capillary tube
[1.6x1300
Refrigerant pipe [6.35
(Option)
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
(with heat insulator)
24
Unit:mm
E1
E1
E2
MUH-12NV -
MUH-12NV -
MSH-12NV -
MSH-12NV -
E2
Reversing valve
(4-way valve)
Refrigerant pipe [12.7
(Optional)
OUTDOOR UNIT
INDOOR UNIT
(with heat insulator)
Muffler
Indoor
heat
exchanger
Indoor coil
thermistor
RT12
Outdoor
heat
exchanger
Stop valve
(with service port)
Flared connection
Defrost
thermistor
RT61
RT11
Room temperature
thermistor
RT11
Accumulator
Compressor
Capillary tube
[1.6x400
Flared connection
Capillary tube
[1.4x500
Reversing valve coil
(4-way valve coil)
heating ON
Strainer
cooling OFF
Stop valve
Refrigerant pipe
(Option) [6.35
Refrigerant flow in cooling
Check
valve
(with heat insulator)
Refrigerant flow in heating
Unit:mm
E1
MUH-18NV -
MUH-18NV -
MUH-18NV -
E1
MSH-18NV -
MSH-18NV -
MSH-18NV -
E2
E2
E3
E3
Reversing valve
(4- way valve)
OUTDOOR UNIT
Refrigerant pipe [15.88
(Option)
INDOOR UNIT
Muffler
(with heat insulator)
Indoor coil
Indoor
heat
exchanger
thermistor
RT12
Strainer
Stop valve
(with service port)
Outdoor
heat
exchanger
Distributor
Defrost
thermistor
RT61
Flared connection
Room temperature
thermistor
RT11
Accumulator
Compressor
Capillary tube
[1.6x750
(2 pcs)
Flared connection
Capillary tube
[2.0X800
Strainer
Reversing valve coil
(4-way valve coil)
heating ON
Stop valve
Refrigerant pipe
(Option) [6.35
cooling OFF
Check
valve
(with heat insulator)
Refrigerant flow in cooling
Refrigerant flow in heating
25
Unit:mm
E1
E2
E1
E2
MUH-24NV -
MUH-24NV -
MSH-24NV -
MSH-24NV -
Reversing valve
(4- way valve)
OUTDOOR UNIT
INDOOR UNIT
Refrigerant pipe [15.88
(Option)
(with heat insulator)
Muffler
Indoor coil
thermistor
RT12
Strainer
Indoor
heat
Ball valve
exchanger
Outdoor
heat
Distributor
Flared connection
exchanger
Room temperature
thermistor
RT11
Accumulator
Defrost
thermistor
RT61
Compressor
Discharge pressure
regurator open
23.5 kgf/J
Flared connection
Capillary tube
[1.6X350
Check
valve
Strainer
Ball valve
with Service port
Capillary tube
[2.4X200
Refrigerant pipe
(Option) [9.52
(with heat insulator)
Check
valve
Refrigerant flow in cooling
Refrigerant flow in heating
Capillary tube
[2.0X350
26
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Piping size O.D : mm
Length of connecting pipe : m
Outdoor unit
Models
Max. length : m
A
Indoor unit
Gas
9.52
12.7
Liquid
MSH-07NV - E1
MSH-09NV - E1
MSH-07NV - E2
MSH-09NV - E2
10
15
MSH-12NV - E1
MSH-12NV - E2
6.35
9.52
0
0.43
MSH-18NV - E1
MSH-18NV - E2
MSH-18NV - E3
MSH-24NV - E1
MSH-24NV - E2
15.88
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R-22 : g)
Refrigerant piping length (one way)
10m
Outdoor unit precharged
Models
7m
15m
(up to 7m)
MSH-07NV - E1
MSH-09NV - E1
MSH-07NV - E2
MSH-09NV - E2
MSH-12NV - E1
MSH-12NV - E2
850
0
150
1150
1800
E1
MSH-18NV -
400
E2
MSH-18NV -
E3
MSH-18NV -
Calculation : Xg=50g/m ✕ (A-7)m
Refrigerant piping length (one way)
10m
Outdoor unit precharged
(up to 7m)
Models
7m
0
15m
520
E1
E2
MSH-24NV -
MSH-24NV -
2400
195
Calculation : Xg=65g/m ✕ (A-7)m
27
EVACUATION PROCEDURES(AIR PURGE)
Connect the refrigerant pipes (both the liquid and gas pipes)
between the indoor and the outdoor units.
Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.(The stop valve will not
work in its initial state fresh out of the factory (totally closed with cap on))
When vacuuming
Connect the gage manifold valve and the vacuum pump to
the service port of the stop valve on the liquid pipe side of the
outdoor unit.
Run the vacuum pump for more than 15 minutes and at this
time confirm that the pressure gage indicates –0.1 Mpa.
Check the vacuum with the gage manifold valve, then close
the gage manifold valve, and stop the vacuum pump.
Leave it as it is for one or two minutes. Make sure the pointer
of the gage manifold valve remains in the same position.
Remove the gage manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on gas and liquid pipe sides.
Operating without fully opening lowers the performance and causes trouble.
Pipe length :
7m maximum
No gas charge
is needed
Pipe length
exceeding 7m
Charge the prescribed
amount of gas
Tighten the cap to the service port to obtain the initial status.
Retighten the cap.
Leak test
28
7
PERFORMANCE CURVES
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 264V
),50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :
(2) Indoor outlet air wet-bulb temperature :
(3) Outdoor intake air dry-bulb temperature :
(4) Total input:
(5) Indoor intake air dry-bulb temperature :
(6) Outdoor intake air wet-bulb temperature :
(7) Total input :
°CWB
°CWB
°CDB
W
°CDB
°CWB
W
Cooling
Heating
}
}
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
OUTDOOR UNIT
INDOOR UNIT
Wet-and dry-bulb
thermometers
Wet-and dry-bulb
thermometers
29
12.0
11.4
10.4
9.4
14.0
12.7
11.5
10.3
9.2
9.1
8.5
7.6
8.1
19.9
25.5 28.7
28.0
25.9
23.7
21.6
28.0
25.9
23.7
21.6
23.5 26.5
21.6 24.3
19.6 22.5
18.4
16.9
15.3
13.8
12.3
10.7
9.2
17.6 19.9
15.6 17.7
13.7 15.5
19.4
17.2
15.1
19.4
17.2
15.1
11.7 13.2
12.9
12.9
NOTE:The above curves are for the heating operation without any frost.
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
① Both indoor and outdoor unit are under the same temperature/humidity condition.
Relative humidity(%)
Dry-bulb temperature
20
25
30
50
60
70
➁ Air flow should be set at MAX.
③ The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa • G) =10.2(kgf/f• G)
(kgf/F•G)(MPa•G)
E1
E2
E1
E2
MUH-07NV -
MUH-07NV -
0.7
7
220V
0.6
6
240V
220/240V
0.5
5
0.4
4
0.3
3
Ambient temperature(˚C)
Ambient humidity(%)
Ambient temperature(˚C)
Ambient humidity(%)
30
E1
E2
(kgf/F•G)(MPa•G)
E1
E2
MUH-09NV -
MUH-09NV -
0.7
7
220V
0.6
6
240V
0.5
5
220/240V
0.4
0.3
4
3
Ambient temperature(˚C)
Ambient humidity(%)
Ambient temperature(˚C)
Ambient humidity(%)
E1
E2
(kgf/F•G)(MPa•G)
E1
E2
MUH-12NV -
MUH-12NV -
0.7
7
220V
240V
0.6
6
0.5
5
220/240V
0.4
4
0.3
3
Ambient temperature(˚C)
Ambient humidity(%)
Ambient temperature(˚C)
Ambient humidity(%)
E1
E2
E3
E1
E2
E3
(kgf/F•G)(MPa•G) MUH-18NV -
MUH-18NV -
0.7
7
220/240V
0.6
6
220V
0.5
0.4
5
4
240V
0.3
0.2
3
2
Ambient temperature(˚C)
Ambient humidity(%)
Ambient temperature(˚C)
Ambient humidity(%)
E1
E2
(kgf/F•G)(MPa•G)
E1
E2
MUH-24NV -
MUH-24NV -
0.7
7
13
12
220V
220V
0.6
6
240V
0.5
0.4
5
4
0.3
0.2
3
2
Ambient temperature(˚C)
Ambient humidity(%)
Ambient temperature(˚C)
Ambient humidity(%)
31
HEAT operation
Outdoor:Dry bulb temperature 7,15,20°C
Wet bulb temperature 6,12,14.5°C
Condition indoor:Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
E1
E2
E1
E2
MUH-12NV -
MUH-07NV -
220V
240V
220V
240V
Ambient temperature(˚C)
Ambient temperature(˚C)
E1
E2
MUH-09NV -
E1
E2
E3
MUH-18NV -
220V
240V
220V
240V
Ambient temperature(˚C)
Ambient temperature(˚C)
E1
E2
MUH-24NV -
13
12
11
10
9
220V
240V
Ambient temperature(˚C)
32
8
MICROPROCESSOR CONTROL
Wireless remote controller
E1
E1
E2
E2
E1
E1
E2
E2
E1
MSH-07NV -
MSH-18NV -
MSH-07NV -
MSH-18NV -
MSH-09NV -
MSH-24NV -
MSH-09NV -
MSH-24NV -
MSH-12NV -
E2
E3
MSH-12NV -
MSH-18NV -
Once the controls are set, the same operation mode can be
repeated by simply turning the OPERATE/STOP button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to
protect system from overload and compressor will not restart
for 3 minutes.
8-1. “I FEEL CONTROL” (
) OPERATION
(1) Press OPERATE/STOP button on the remote controller.
OPERATION INDICATOR lamp of the indoor unit will turn
on with a beep tone.
(2) Press OPERATION SELECT button to set “I FEEL CON-
TROL”(
). Then a beep tone is heard.
(3) The operation mode is determined by the initial room
temperature at start-up of the operation.
Initial room temperature
Mode
COOL mode of
"I FEEL CONTROL"
more than 25:
DRY mode of
"I FEEL CONTROL"
23: to 25:
HEAT mode of
"I FEEL CONTROL"
less than 23:
● Once the mode is fixed, the mode will not change by
room temperature afterwards.
● Under the ON-TIMER (
) operation, mode is deter-
mined according to the room temperature as the opera-
tion starts.
● When the system is stopped with the OPERATE/STOP
button on the remote controller, and restarted within 2
hours in “I FEEL CONTROL” (
) mode, the system
operates in previous mode automatically regardless of
the room temperature.
Example
Restart
COOL mode of
“I FEEL CONTROL”
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
● When the system is restarted after 2 hours, the operation
mode is determined by the initial room temperature at
start-up of the operation.
Restart
Example
COOL or DRY or
HEAT mode of “I FEEL
CONTROL” that deter-
mined by initial room
temperature at start-up
of the operation.
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
INDOOR UNIT DISPLAY SECTION
33
(4) The initial set temperature is decided by the initial room temperature.
Model
Initial room temperature
Initial set temperature
26:or more
24:
COOL mode of
❈1
"I FEEL CONTROL"
Initial room temperature
26: or less
23: or 25:
23: or less
minus 2:
Initial room temperature
minus 2:
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
26:
❈1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless of
the initial set temperature.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” (
) mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature is controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.
Each time the TOO WARM or TOO COOL button is pressed,the indoor unit receives the signal and emits a beep tone.
● Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
▲ TOO
…
COOL
To raise the set temperature 1~2 degrees(°C)
▼ TOO
WARM
…
To lower the set temperature 1~2 degrees(°C)
34
— COOL mode of “I FEEL CONTROL” —
ON
ON
OFF
OFF
ON
Compressor and
outdoor fan motor
Run continuously in cooling mode
Indoor fan motor
NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL”
There are two types of controls in coil frost prevention.
① Temperature control
<MSH-07/09/12> When the indoor coil thermistor RT12 reads 4°C or below for 5 minutes, the coil frost prevention mode
starts.
<MSH-18/24>When the indoor coil thermistor RT12 reads 3°C or below, the coil frost prevention mode starts immediately.
However the coil frost prevention will not work for 5 minutes after the compressor starts.
The compressor stops and the indoor fan operates at the set speed for 5 minutes.
After that, if RT12 still reads below 4°C (MSH-07/09/12) or below 3°C (MSH-18/24) this mode prolonged until the RT12
reads over 4°C (MSH-07/09/12) or 3°C (MSH-18/24).
② Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Lo or Me.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the
beginning.
Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds
26°C.However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.
●Indoor fan operates at the set speed by FAN SPEED CONTROL button.
Followings are the fan speed in AUTO.
Initial temperature difference
Fan Speed
Room temperature minus set temperature : 2 degrees or more ··············································Hi
Room temperature minus set temperature : 1 degree or more and less than 2 degrees·······Me
Room temperature minus set temperature : less than 1 degree··············································Lo
2 deg.
4 deg.
1.66 deg.
1 deg.
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the temperature and the microprocessor.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
The operation of the compressor and indoor fan is as follows.
1. When the room temperature is 23°C or over:
Compressor operates by temperature control and time control.
① Set temperature is controlled to fall 2°C as initial set temperature.
② When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
2. When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
35
Operation time chart
Example
ON
1st ON
OFF
Thermostat
Indoor fan
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
Outdoor fan
compressor
1 min.
3 min.
8 min.
4 min.
NOTE ● Coil frost prevention during DRY mode of “I FEEL CONTROL”
The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
However the indoor fan speed becomes the set speed or Lo.
— HEAT mode of “I FEEL CONTROL” —
1. Indoor fan speed control
(1) Followings are the fan speed in AUTO.
Initial temperature difference
Fan speed
Set temperature minus room temperature: 2 degrees or more················································· Hi
Set temperature minus room temperature: 1 degree or more and less than 2 degrees··········· Me
Set temperature minus room temperature: less than 1 degree················································· Lo
(2) Cold air prevention control
2 deg.
4 deg.
1 deg.
1.66 deg.
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at VLo
when the temperature is below 18°C. But the fan stops when the indoor fan operates at VLo and the temperature is
15°C or less.
NOTE : At initial in hysteresis this control works.
Released
Cold Air Prevention
18: 22:
(3) New warm air control.
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil ther-
mistor RT12 temperature to blow out warm air.
After releasing of cold air prevention, when the indoor coil temperature is 37°C or above, the fan speed shifts to the set
speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed.
When the indoor coil temperature is less than 37°C, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed>
less than 2 minutes························Lo
2 minutes to 4 minutes···················Me
4 minutes or more··························Hi
The upper limit of the fan speed is the set speed.
If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at VLo.
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start until the indoor coil thermistor RT12 reads 22°C or more.
36
2. High pressure protection
During heating operation, the outdoor fan motor is controlled by the indoor coil thermistor RT12 temperature for excess rise
protection of compressor discharge pressure.
Outdoor fan OFF : 52°C (MSH-07/09/12/24), 50°C (MSH-18)
Outdoor fan ON : 48°C (MSH-07/09/12/24), 46°C (MSH-18)
High pressure protection time chart
Indoor coil thermistor
RT12 temperature
Outdoor fan motor
turn OFF
52˚C(MSH-07/09/12/24)
50˚C(MSH-18)
Outdoor fan motor
turn ON
48˚C(MSH-07/09/12/24)
46˚C(MSH-18)
ON
ON
Outdoor fan motor
OFF
OFF
NOTE 1 :When the outdoor fan is OFF in heating, defrosting of outdoor heat exchanger is not detected by the defrost thermis-
tor RT61.
E1
E1
E2
NOTE 2 :When connected to MXZ-32NV-
outdoor unit,the MSH-07/09/12NV- , MSH-07/09/12/18NV-
and
E3
MSH-18NV-
indoor unit sends the data for the temperature to the outdoor unit according to the indoor coil temper-
ature.For the further information,refer to the service manual No.OB185.
3. Defrostings
Defrostings of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61.
(1) Defrost starting conditions
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes without the defrosting opera-
tion working.
b) The defrost thermistor RT61 reads - 3°C or less.
c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.
(2) Defrost terminating conditions
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 3.1°C or more.
e) The defrosting time exceeds 10 minutes.
37
(3) Defrosting time chart
Defrost thermistor RT61
3.1: or more
-3: or less
Outdoor 52C
relay(Compressor)
ON
OFF
X62
(Reversing valve coil)
ON
15 sec.
30 sec.
OFF
30 sec.
5~15 sec.
ON
SR61
Outdoor fan
OFF
ON
Defrost
counter
OFF
Max 10 min.
❈
VLo
ON
Indoor fan
OFF
Horizontal
Indoor vane
Set position
NOTE1 ● When the indoor coil thermistor reads above 18°C, indoor fan operates at VLo for 30 seconds.
● When the indoor coil thermistor reads 18°C or less, the indoor fan stops.
E1
E2
E3
NOTE2: Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-
E1
are connected with MXZ-32NV-
as multi system units.
38
4. Reversing valve control
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
NOTE1: The Reversing valve reverses for 5 seconds right before start-up of the compressor.
E1
E2
E3
NOTE2: Refer to the Service Manual OB185 when MSH-07/09/12NV- , MSH-07/09/12/18NV- , and MSH-18NV-
E1
are connected with MXZ-32NV-
as multi system units.
(HEAT)
5 sec.
(COOL / DRY)
5 sec.
ON
OFF
ON
OFF
Compressor
ON
OFF
ON
OFF
Reversing valve
ON
OFF
ON
OFF
Outdoor fan
8-2. COOL (
) OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit turns on with a beep tone.
(2) Select COOL mode.
(3) Set the TEMPERATURES button.
(TOO WARM or TOO COOL button)
The setting range is 16 ~ 31°C
✻ Indoor fan continues to operate regardless of
thermostat’s OFF-ON
✻ Coil frost prevention is as same as COOL
mode of “I FEEL CONTROL”
8-3. DRY (
) OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit
turns on with a beep tone.
(2) Select DRY mode.
(3) The microprocessor reads the room tempera-
ture and determines the set temperature. Set
temperature is as shown on the right chart.
Thermostat (SET TEMP.)does not work.
The other operations are same as DRY mode of
“I FEEL CONTROL”.
(4) DRY operation will not function when the room
temperature is 13°C or below.
(5) When DRY operation functions, the fan speed
is lower than cool operation.
8-4. HEAT (
) OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR on the indoor unit turns on with a beep tone.
(2) Select HEAT mode.
(3) Press TEMPERATURES button (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
(4) Indoor fan speed control, high pressure protection, defrosting, heater control are the same as HEAT mode of “I FEEL
CONTROL”.
39
8-5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback
the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Hi,Me,Lo,SLEEP),
the microprocessor controls SR11 (MSH-07/09/12), IC141 (MSH-18/24) and adjusts fan motor electric current to make the
current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the
rotational frequency changes smoothly.
SLEEP
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect
the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 min-
utes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR
lamp flashes on and off to show the fan motor abnormality. (See page 49.)
8-6. AUTO VANE OPERATION
(1) Vane motor drive
MSH-N series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are
controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The auto vane angle changes as follows by pressing the VANE CONTROL (
) button.
40
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
The positioning is decided as follows.
(a) When the OPERATE/STOP button is pressed. (POWER ON/OFF)
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO (
) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
① In COOL and DRY operation
Vane angle is fixed to Angle 1.
➁ In HEAT operation
Vane angle is fixed to Angle 4.
(5) Dew prevention
During COOL or DRY operation at vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the
vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE (
)
By pressing the SWING button (
) vane swings vertically. The remote controller displays “ ”. SWING mode is cancelled
when the SWING button or VANE CONTROL button (
(7) Cold air prevention in HEAT operation
) is pressed or the operation stops or changes to other mode.
When either of the following conditions occurs in HEAT operation, the horizontal vane angle changes to Angle 1 automati-
cally to prevent cold air blowing on users.
① Compressor is not operating.
➁ Defrosting is performed.
➂ Indoor coil thermistor RT12 reads 24: or below.
➃ Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Set position
Indoor coil thermistor RT12 temperature
Angle 1
24:
28:
NOTE:At initial in hysteresis this control works.
8-7. SLEEP MODE (
)
• When the SLEEP button ( ) is pressed, the indoor fan speed drops and the air flow sound from the
indoor unit is decreased.
• The indications of the remote controller are “
• When the FAN SPEED CONTROL button (
mode is released.
” and “
”.
) is pressed during the SLEEP mode, the SLEEP
41
8-8. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR so set the current time, correctly with CLOCK SET button.
(3) Press TIMER CONTROL button to select the operation.
“
” button... AUTO START operation (ON timer)
“
” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “
These marks disappear in 1 minute.
” or “
” mark is flashing.
When setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
● A power failure occurs.
● The circuit breaker functions.
2. CANCEL
TIME setting can be cancelled with the TIMER CONTROL buttons. (“
” or “
”)
To cancel the ON timer, press the “
” button.
To cancel the OFF timer, press the “
” button.
TIME is cancelled and the display of set time disappears.
PROGRAM TIMER
● The OFF timer and ON timer can be used in combination.
● “
” and “
” display shows the order of the OFF timer and ON timer operation.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
42
8-9. EMERGENCY-TEST OPERATION
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY OPERATION switch
on the front of the indoor unit. The unit will start and the OPERATION INDICATOR lamp will light.
The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high
speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal.
After 30 minutes of test run operation the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of 24°C.
The fan shifts to Me speed.
This operation continues until the EMERGENCY OPERATION switch is pressed or a button on the remote controller is
pressed, then normal operation will start.
The coil frost prevention circuit operates in this operation, and defrosting operates too.
In the test run or emergency operation, the horizontal vane operates in AUTO mode with a set temperature of 24°C.
Defrosting of outdoor heat exchanger works in EMERGENCY HEAT MODE.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
Press once
<Cool>
Press again
<Heat>
Press once again
<Stop>
Emergency operation
switch
43
9
SERVICE FUNCTIONS
1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accomplished
regardless of the defrost interval restriction. See Page 56 and 59.
Defrost thermistor RT61 must read below -3°C
2. DEFROST TERMINATION CHANGE
<JPC> when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. (See page 56 and 59.)
<JPE> when the JPE wire of the deicer P.C. board is cut, the defrost temperature will be changed. (See page 56 and 59.)
MODEL
Junper wire
JPC
Change point
E1 E2
MSH-07/09/12NV-
Defrost interval time changes from 40 minutes to 15 minutes
E1 E2 E3
MSH-18NV-
MSH-24NV-
Deforst start temperature changes from -3:to 0:
E1 E2
JPE
Deforst finish temperature changes from 3.1:to 10.1:.
3. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows.
3-minute delay : 3-minute ➔ 3-second.
AUTO START : 1 hour ➔ 1-minutes
AUTO STOP : 1 hour ➔ 1-minutes
Short the connector during the timer mode.
}
4. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
(1)<The reset button can be located on the rear side.>
E1
E1
E1
E1
MSH-07NV -
MSH-18NV -
MSH-09NV -
MSH-12NV -
MSH-18NV -
E2
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodeling, take out the batteries at first.
After finish remodeling, put back the batteries then push the RESET button.
Originally, chip parts are fitted on J10/J20 side and there is no chip parts on the other side.
Remove the chip parts of J10/J20 side and connect Jumper wire to J11/J21 side as shown in Table 1.
Either J1O or J11 /J20 or J21 should be attached for normal operation.
Table.1
1 unit operation
2 units operation
Same as at left
Replace J10 with J 11
–
3 units operation
Same as at left
4 units operation
Same as at left
No. 1 unit
No modification
No. 2 unit
No. 3 unit
–
–
Same as at left
Same as at left
Replace J20 with J 21
Same as at left
Replace J10 with J11
Replace J20 with J21
No. 4 unit
–
–
–
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When
the power supply is turned on and indoor unit receives the first signals from the remote controller, the
remote controller number is designated as the indoor unit number. Therefore at and after the second
time indoor unit accepts the remote controller of the initial setting number.
At setting - error, turn the power supply off to cancel the individual operation and then turn the power
supply on to restart the setting.
44
(2)<The reset button can be located on the front side.>
E1
E1
MSH-07NV - (Serial number 7000201T~) MSH-09NV - (Serial number 7000201T~)
E1
E1
E2
E2
MSH-12NV - (Serial number 7000001T~) MSH-24NV -
E2
MSH-07NV -
MSH-12NV -
MSH-24NV -
MSH-09NV -
E2
E2
MSH-18NV - (Serial number 7000001T~)
E3
MSH-18NV -
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodeling, take out the
batteries at first.
After finish remodeling, put
back the batteries then
push the RESET button.
The P.C.board has the print “J1” and “J2”.Jumper wires are mounted to each “J1” and “J2”.Cut J1 and J2 according to the
number of indoor unit as shown in Table 1.
After modification,push the reset button.
Table.1
1 unit operation
2 units operation
Same as at left
Cut J1
3 units operation
Same as at left
Same as at left
Cut J2
4 units operation
Same as at left
Same as at left
Same as at left
No. 1 unit
No modification
No. 2 unit
No. 3 unit
–
–
–
No. 4 unit
–
–
–
Cut both J1 and J2
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When
the power supply is turned on and indoor unit receives the first signals from the remote controller, the
remote controller number is designated as the indoor unit number. Therefore at and after the second
time indoor unit accepts the remote controller of the initial setting number.
At setting - error, turn the power supply off to cancel the individual operation and then turn the power
supply on to restart the setting.
45
5. AUTO RESTART FUNCTION
E2
E2
E2
MSH-07NV -
MSH-12NV -
MSH-18NV -
MSH-09NV -
MSH-24NV -
E2
E3
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power
has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEEL CON-
TROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is decided
by the initial room temperature.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit.
2Removed the electronic control P.C. board and the display P.C.board. (See page 60 and 62.)
3Cut the RESISTOR JR07 (MSH-07/09/12) or JR06(MSH-18/24) on the indoor electronic control P.C.board.
MSH-07/09/12
MSH-18/24
IC141
C11
52C
CN201
IC101
RA102
CN151
JR06
JR07
Operation
1If the main power (220/240V AC) has been cut, the operation settings remain.
2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
Note:
•The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
•If main power is cut while AUTO START/STOP timer is active ,the timer setting is cancelled when auto restart function
works.
•If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
•To prevent breaker off due to the rush of startting current, systematize other home appliance not to turn on at the same
time.
•When more than one air conditioners are connected under the same power system,compressor starting current as large
as that for all the compressors used flows at a time as soon as the units restart automatically.
Therefore, the specific counter-measures are required to prevent main voltage drop or the rush of starting current after
power failure by providing the system to allow the units to start in regular succession.
46
10 TROUBLESHOOTING
E1
E1
E2
E2
E1
E1
E2
E3
E1
E2
E2
MSH-07NV -
MSH-18NV -
MSH-09NV -
MSH-24NV -
MSH-09NV -
MSH-24NV -
MSH-12NV -
MSH-18NV -
MSH-12NV -
MSH-07NV -
MSH-18NV -
10-1 Cautions on troubleshooting
10-1-1 Before troubleshooting, check the followings:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
10-1-2 Take care the followings during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker.
2) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Housing point
Lead wiring
10-1-3 Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on page 48 and the check table on page 49.
10-1-4 How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote con-
troller normally, discharge the remote controller in the following order.
This remote controller has the reset button. After refilling new batteries, press the reset button with tip end of ball point
pen or the like, and then use the remote controller.
B
A
RESET button
RESET button
There are two kind of remote controllers. A type has the RESET button at the back, and B type does it on the
front. How to use the two buttons are given in the Instruction Manual.
47
10-2 Instruction of troubleshooting
Start
Indoor unit
Indoor unit doesn’t
receive the signal from
remote controller.
Also, OPERATION INDI-
CATOR lamp doesn’t
flash, when the EMER-
GENCY OPERATION
switch is pressed.
Indoor unit oper-
ates. Outdoor unit
doesn’t operate.
OPERATION INDICATOR
lamp on the indoor unit is
flashing on and off.
dosen’t receive
the signal from
remote
controller.
2-time flash
Outdoor unit
operates in
only Test
Run opera-
tion.
Outdoor unit
doesn’t oper-
ate even in
Test Run
Refer to
B
”Check of
receiver P.C.
board” on page
51.
2.5-second OFF
3-time flash
operation.
C
Refer to
“Check of
indoor electronic control
P.C. board” on page 52.
2.5-second OFF
1-time flash
Refer to
“Check of
outdoor unit”
on page 52.
D
Check room
temperature
thermistor.
6-time flash
Cause:indoor/outdoor unit
connecting
Cause:Indoor unit
2-time-Room tempera-
ture/Indoor coil
thermistor trouble
3-time-Indoor fan motor
trouble
2.5-second OFF
Trouble of mis-wiring
(
Trouble of the serial signal
Cause:outdoor unit
6-time-Replace the out-
door thermistor
E
Refer to
“How to check
mis-wiring and sig-
nal error
Check room temperature
thermistor. Refer to“Test
point diagram and volt-
age” on page 55,57 and
58.
(when outdoor unit
doesn’t work)”
on page 53 and
54.❈1
Refer to
A
Check indoor coil
“Check of indoor
fan motor” on
page 51.
thermistor. Refer
to“Test point dia-
gram and voltage”
on page 55,57 and
58.
❈1<The case of the trouble of the serial signal>
When turn off the power and then turn on the power again, the
indication shows “the trouble of mis-wiring.”
48
10-2-1 troubleshooting check table
❈ Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
Abnormal
point
NO.
Indication
Symptom
Detect method
Check point
0.5-second ON
When serial signal stops for 4
to 5 seconds after 1st on of
52C relay by POWER turning
on.
Mis-wiring
● Check wiring (visual check and conductiv-
ity check).
● Check indoor electronic control
P.C.board.
● Check outdoor DEICER P.C. board.
● Check electrical parts.
0.5-second OFF
1-time flash
Outdoor unit
does not run.
1
When serial signal from out-
door unit stops for 4 to 5 sec-
onds.
Serial sig-
nal
2.5-second OFF
2-time flash
● Check thermistor calibration.
● Reconnect connector.
● Check indoor electronic control P.C.board.
Indoor coil
thermistor
Detect Indoor coil/room tem-
perature thermistor short or
open circuit every 2 seconds
during operation.
Outdoor unit
does not run.
2
Room
tempera-
ture ther-
mistor
2.5-second OFF
● Disconnect connector CN211 and then
Indoor fan
repeats 12 sec-
onds ON and 3 When rotational frequency
minutes OFF. feedback signal is not emit
When the indoor during 12-second indoor fan
fan breaks, the operation.
fan keeps stop-
ping.
2
3
check connector CN121
-
to make
3-time flash
sure rotational frequency feedback signal
of 1.5V or over exists.
● Check indoor electronic control P.C.
board.
● Check indoor fan motor.
● Reconnect conector.
Indoor fan
motor
3
4
2.5-second OFF
6-time flash
● Shortage of refrigerent.
When the outdoor thermistor
Outdoor unit
● Check outdoor DEICER P.C. board.
Outdoor
thermistor
shorts or opens after the com-
does not run
pressor start-up.
2.5-second OFF
5-time flash
7-time flash
When the compressor opera-
tion is continuosly three times
● Check the inverter output.
● Check the compressor.
❈
Outdoor
power
system
Outdoor unit
interruped by overcurrent pro-
does not run
5
tection within 1 minute after
start-up , it stops operation.
2.5-second OFF
The outdoor unit stops opera-
❈
Outdoor
control
P.C. board
tion when it cannot properly
Outdoor unit
read data in the nonvolatile
does not run
6
● Check the outdoor control P.C.board.
memory of the outdoor control
P.C.board.
2.5-second OFF
10-time flash
❈
When the indoor unit detects
Outdoor
control
P.C. board
● Check the drain punp.
● Check the drain sensor.
● Check LEV.
Outdoor unit
does not run
drain abnormality and the
indoor coil temperature is too
low.
7
2.5-second OFF
When the operation mode of
each rooms is setted
COOL(includes DRY) and
HEAT at same time, it take
precedence the operation
mode runs first.
Outdoor unit
runs but the
indoor unit does
not run.
❈
Outdoor
control
P.C. board
●Adjust the operation mode.
8
light
flash
2.5-second OFF
❈
E1
The indication is shown only when the indoor unit connects with the outdoor unit MXZ-32NV-
.
49
10-2-2 Trouble criterion of main parts
E1
E1
E2
E2
E1
E1
E2
E2
E1
MSH-07NV-
MSH-18NV-
MSH-07NV-
MSH-18NV-
Part name
MSH-09NV-
MSH-24NV-
MSH-09NV-
MSH-24NV-
MSH-12NV-
E2
E3
MSH-12NV-
MSH-18NV-
Check method and criterion
Figure
Room
temperature
thermistor
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Normal
Abnormal
Indoor coil
thermistor
Opened or short-circuited
8kΩ ~ 20kΩ
Measure the resistance with a tester.
(Part temperature –10°C ~ 40°C)
Defrost
thermistor
Normal
Abnormal
Opened or short-circuited
5kΩ ~ 60kΩ
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
WHT
C
P
Normal
Abnormal
AUX.
RED
MAIN
Compressor
07NV
09NV
12NV
18NV
24NV
S
R
BLK
3.67~4.50Ω
5.07~6.20Ω
0.85~1.04Ω
1.83~2.23Ω
1.85~2.28Ω 1.05~1.30Ω
2.88~3.52Ω
5.13~6.28Ω
C-R
C-S
Opened or
short-circuited
2.38~2.91Ω
3.44~4.21Ω
Measure the resistance between the terminals with a tester.
(Coil wiring temperature10°C ~ 30°C)
Normal
Abnormal
07/09/12NV
280 ~ 303Ω
313 ~ 336Ω
18/24NV
MAIN
AUX.
176 ~ 192Ω
240 ~ 261Ω
WHT-BLK
BLK-RED
Opened or
short-circuited
Indoor fan
motor
FUSE
Measure the voltage Power ON.
Normal
BLK
RED
WHT
Abnormal
BRN-YLW
4.5 ~ 5.5V
(When fan revolved one time)
0V➔5V➔0V
Remain 0V or 5V
YLW-GRY
(Approx.)
MAIN
AUX.
07NV
09NV
P
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
BLK REDWHT
MAIN
AUX.
Outdoor fan
motor
12NV
18NV
Normal
P
Abnormal
12NV
114 ~ 141Ω
118 ~ 146Ω
–
18NV
24NV
07/09NV
192~236Ω
373~458Ω
–
BLK REDORN WHT
MAIN
WHT-BLK
BLK-RED
BLK-YLW
YLW-RED
102 ~ 126Ω
97.9 ~ 120Ω
55.3 ~ 67.6Ω
–
24NV
Opened or
short-circuited
AUX.1AUX.2
P
–
26.6 ~ 32.6Ω
55.5 ~ 67.8Ω
C
–
–
–
BLK YLW REDORNWHT
Vane motor
Measure the resistance between the terminals with a tester.
(Part temperature10°C ~ 30°C)
PNK
ROTOR
Normal
Abnormal
Vane motor
ORN
RED
07/09/12NV 282 ~ 305Ω
18/24NV 358 ~ 388Ω
Opened or short-circuited
YLW
BLU
INNER PROTECTOR
P
50
A
Check of indoor fan motor
Turn OFF power supply.
Check connector CN211 visually.
Inodoor fan does not operate.
Yes
No
No
Are lead wires connected?
Is soldered point nomal?
Yes
Reconnect the lead wires.
Resolder it.
Disconnect lead wires from connector CN211 on indoor electronic control P.C. board.
Measure resistance between lead wires
No.1 and No.4 and then No.1 and No.2(MSH-18/24)
No.1 and No.3 and then No.2 and No.3(MSH-07/09/12)
}
{
Replace the indoor electronic con-
trol P.C. board.
Is resistance 0 (short circuit) or ∞ (open circuit)?
Yes ( 0 or ∞ )
No
(others)
Repair the indoor fan motor.
B Check of receiver P.C. board
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check the model name of remote
controller.
No
Is LCD display on remote con-
Replace the batteries.(see page 47.)
troller visible?
(not clear)
Yes
Remove batteries and then set them back.
Check if the unit operates with remote
controller.
No
Turn on a radio to AM and press switch on
remote controller.
Does the unit operate with remote
controller?
Yes
OK
No
Replace the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
Yes
● Re-install the unit away from lights.
● Attach a filter on receiving part.
No
Measure the voltage between
receiver P.C. board connector No.2(+)and No.1(MSH-18/24)
indoor electronic control P.C. board connector LD101 No.2 and JPG(MSH-07/09/12)
}
{
when remote controller button is pressed.
Yes
Is the voltage approx. 4V DC?
Replace the indoor electronic control P.C.
board.
No(5V or 0V DC)
Replace the receiver.
51
C Check of indoor electronic control P.C. board
The unit doesn’t operate with the
remote controller.
Replace the fuse.
Yes
Also, the OPERATION INDICA-
TOR lamp doesn’t light up by
pressing the EMERGENCY
OPERATION switch.
Trouble of indoor electronic con-
trol P.C. board.
Yes
No
Is fuse(F11)blown?
1.Pull out power supply
cord.
2.Measure resistance
between CN201
Is there resistance ?
(Approx.0Ω)
Be sure to check both fuse
and varistor in any case.
1
on indoor electronic
Check both “parts side”and “pattern
side”of indoor electronic control P.C.
board visually.
control P.C. board
and
N
on the terminal
No
block with a tester.
Trouble of fuse(F12)
Is varistor(NR11)burnt?
CN201
No
07/09NV
12/18NV
3
1
Yes
F12
L
Terminal
block
N
CN201
Replace the varistor.
1
2
F12
F12
L
N
Terminal
block
CN201
24NV
3
2
3
1
NF
D
Check of outdoor unit
L
Terminal
block
N
Compressor and outdoor fan do not operate.(Only indoor fan operates.)
Start
Press EMERGENCY OPERATION switch.
3-minute time delay works.
24NV
No
Is voltage applied to fan motor and compressor
relay normal when you look at checkpoints about
outdoor DEICER P.C.borad?
Replace
DEICER
P.C.board
Test run operation operates for 30 minutes.
Yes
Yes
Yes
Check voltage to terminal block of outdoor unit. Is
N
2
there AC220-240V to terminal block between
-
?
07/09/12/18NV
Check the outdoor DEICER P.C.board at first, then check
No
the outdoor fan motor and the compressor.
Check voltage to terminal block of indoor unit. Is
N
2
there AC220-240V to terminal block between
-
?
07/09/12/18NV
No
24NV
Check the continuity of indoor and outdoor unit connection.
Replace the indoor elec-
tronic control P.C. board.
Confirm wiring connection
at indoor terminal block.
52
E How to check mis-wiring and serial signal error (when outdoor unit does not work)
MSH-07NV
Start
MSH-09NV
MSH-12NV
MSH-18NV
❈ 1 Short circuit of JPG and JPS on the
1. Turn OFF power supply.
2. Turn ON power supply.
3. Press EMERGENCY OPERATION switch.
indoor electronic control P.C. board
enables self-check to be displayed in 3
seconds.
Serial signal error is indicated.
(0.5-sec.ON, 2.5-sec.OFF)
3 min. later, when relay 52C turns ON, what self-check result is
displayed on OPERATION INDICATOR lamp on indoor unit? ❈ 1
Mis-wiring is indicated.(0.5-sec.ON, 0.5-sec.OFF)
Yes
Repair wiring.
Is there mis-wiring, poor contact, or wire disconnection?
No
1. Turn OFF power supply and disconnect in-out connecting wire on indoor side.
N
3
2. Short-circuit between indoor terminal block
and
3. Turn ON power supply and press EMERGENCY OPERATION switch.
Is there 20V DC between both ends of R132 when
relay (52C) turns ON?
( By tester, the stylus is between 0 ~ 20V. )
No
Replace the indoor electronic control
P.C. board.
Yes
•Turn OFF power supply.
•Connect ON in-out connecting wire.
•Turn ON power supply.
3 minutes later, when EMERGENCY OPERATION switch is pressed
and 52C relay turns ON, is there AC 220-240V between outdoor
No
Rectify in-out connecting wire.
2
N
terminal block
-
?
Yes
Under the same condition as 3 minutes later, when
EMERGENCY OPERATION switch is pressed and
No
No
Check and rectify fuse and varistor on out-
door DEICER P.C. board.
52C relay turns on, is there DC 5V between
+
J8 -J7 –
?
Yes
Under the same condition as 3 minutes later, when
EMERGENCY OPERATION switch is pressed and
52C relay turns on, is there DC 10V between both
ends of R601?
Rectify in-out connecting wire.
(By tester, the stylus is between 5 ~10V)
Yes
Replace the outdoor DEICER P.C. board.
53
E How to check mis-wiring and serial signal error (when outdoor unit does not work)
MSH-24NV
Start
❈ 1 Short circuit of JPG and JPS on the
1. Turn OFF power supply.
2. Turn ON power supply.
3. Press EMERGENCY OPERATION switch.
indoor electronic control P.C. board
enables self-check to be displayed in 3
seconds.
Serial signal error is indicated.
(0.5-sec.ON, 2.5-sec.OFF)
3 min. later, what self-check result is displayed on OPERATION
INDICATOR lamp on indoor unit? ❈ 1
Mis-wiring is indicated.(0.5-sec.ON, 0.5-sec.OFF)
Yes
Repair wiring.
Is there in-out mis-wiring, poor contact, or wire disconnection?
No
1. Turn OFF power supply and disconnect in-out connecting wire on indoor side.
N
3
2. Short-circuit between indoor terminal block
and
3. Turn ON power supply and press EMERGENCY OPERATION switch.
3 minutes later,is there DC 20V between both ends
of R132?
( By tester, the stylus is between 0 ~ 20V. )
No
Replace the indoor electronic control
P.C. board.
Yes
•Turn OFF power supply.
•Connect ON in-out connecting wire.
•Turn ON power supply.
No
Replace in-out connecting wire of
2
N
Is there AC220~240V between outdoor terminal blocks
-
?
2
N
and
.
Yes
No
3 minutes later, when EMERGENCY OPERATION
switch is pressed is there DC 5V between J8 -J7
on outdoor DEICER P.C. board?
Check and rectify fuse and varistor on out-
door DEICER P.C. board.
–
+
Yes
3 minutes later, when EMERGENCY OPERATION
switch is pressed and 52C relay turns on, is there
DC 10V between both ends of R601?
No
3
Replace
in-out connecting wire.
(By tester, the stylus is between 5 ~10V)
Yes
Replace the outdoor DEICER P.C. board.
54
TEST POINT DIAGRAM AND VOLTAGE
E1
MSH-18NV -
Indoor electric control P.C.board
Fan motor power supply
}
Fuse AC250V 3.15A
Power supply input
AC 220-240V
}
+
--
R132
}
DC 0 ~20V
C144
+
DC5V
}
--
C144
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Timer short mode point
Emergency operation
switch
JPG
--
DC12V
}
JP43
+
55
E1
MUH-18NV -
Outdoor deicer P.C. board
R601
DC5~10V
Defrost
thermistor(RT61)
INPUT
AC 220-240V
Reversing valve coil
AC 220-240V
Outdoor fan motor
AC 220-240V
+
--
DEICER P.C. BOARD
Fuse
2A/250V
Defrost interval
time short pin
+ J8
DC5V
}
-- J7
+
--
+
--
Defrost termination
temperature change.
Jumper wire JPC and JPE
DC12V
52C
DC12V
56
TEST POINT DIAGRAM AND VOLTAGE
E1
E1
E1
E2
MSH-07NV -
MSH-07NV -
MSH-09NV -
MSH-09NV -
MSH-12NV -
MSH-12NV -
E2
E2
Indoor electronic control P.C. board
Power supply input
AC 220-240V
}
CN201 No1
Varistor(NR11)
Fuse AC250V 3.15A
Room temperature
thermistor(RT11)
Indoor coil
thermistor(RT12)
Time short mode point
Indoor coil thermistor(RT12)
Room temperature thermistor(RT11)
R132
DC0~20V
P.C.board
57
TEST POINT DIAGRAM AND VOLTAGE
E1
E2
MSH-24NV - MSH-18NV -
E2
E3
MSH-24NV - MSH-18NV -
Fan motor power supply
Fuse AC 250V 3.15A
Power supply input
AC 220-240V
}
C144
+
DC5V
}
C144
Room temperature
thermistor(RT11)
Indoor coil thermistor(RT12)
JPS
Time short mode point
JPS
Emergency operation switch
JPG
DC12V
JP41
}
+
R132
DC0~20V
P.C.board
58
E1
E1
E2
E3
E1
E2
E2
E1
E2
E2
MUH-07NV -
MUH-24NV -
MUH-12NV -
MUH-18NV -
MUH-09NV -
MUH-07NV -
MUH-18NV -
MUH-12NV -
MUH-09NV -
MUH-24NV -
Outdoor deicer P.C. board
R601
DC5~10V
Reversing valve
INPUT
AC 220-240V
Outdoor fan motor
coil
AC 220-240V
AC 220-240V
+
Defrost thermistor(RT61)
DEICER P.C. BOARD
Fuse 2A/250V
Defrost interval
time short pin
+
J9
J8
DC5V
}
+
+
DC12V
Defrost termination
temperature change.
Jumper wire JPC and JPE
52C
DC12V
59
11
DISASSEMBLY INSTRUCTIONS
NOTE:
❈ On the wiring diagram shows the terminals with a lock mechanism, so it
cannot be removed when you pull the lead wire Be sure to pull the wire by
pushing the locking lever (projected part) of the terminal with a finger.
① Slide the sleeve.
➁ Pull the wire while pushing
the locking lever.
E1
E2
E1
E2
E1
11-1 MSH-07NV -
MSH-07NV -
MSH-09NV -
MSH-09NV -
MSH-12NV -
MSH-12NV -
E2
INDOOR UNIT
PHOTOS
OPERATING PROCEDURE
1. Removing the front panel
Photo 1
(1) Remove the screws caps of the front panel.
Front panel
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
Screw
2. Removing the electronic control P.C. board and the
display P.C. board.
Photo 2
Room temperature
thermistor connector
(1) Remove the front panel. (Refer to 1)
(2) Remove the screw of the electrical cover.
Remove the electrical cover.
Ground wire screw
(3) Disconnect the room temperature thermistor and the con-
nector from the indoor coil thermistor.
(4) Remove the terminal cover.
Cord clamp
Remove the screw of the terminal block.
(5) Remove the cord clamp.
(6) Disconnect all the connectors on the electronic control P.C.
board.
(7) Remove the screw of the ground wire.
(8) Disconnect the white lead wire and the brown lead wire
from 52C relay.
(9) Remove the electronic control P.C. board and the display
P.C. board.
Terminal block
cover
Indoor electronic
control P.C.board
Terminal block
cover screw
60
OPERATING PROCEDURE
PHOTOS
3. Removing the electrical box
Photo 3
(1) Remove the front panel. (Refer to 1)
(2) Remove the electrical cover.
(3) Disconnect the connector of the indoor coil thermistor.
(4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con-
trol P.C. board.
(5) Unhook the catches (both upper and lower), remove the
electrical box.
Catch
4. Removing the vane motor
(1) Remove the front panel.
Vane motor screw
Photo 4
(2) Remove the screw of the vane motor, disconnect the con-
nector.
(3) Remove the vane motor.
Drain hose
Vane motor
5. Removing the line flow fan and the indoor fan motor
(1) Remove the front panel. (Refer to 1)
Photo 5
(2) Disconnect the connector from the vane motor.
(3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly.
(4) Lifting the left side of the heat exchanger, remove the elec-
trical box.
(5) Remove the fixture of the fan motor.
(6) Remove the hexagon socket set screws.
(7) Remove the line flow fan and the fan motor.
Fan motor
catches
Indoor coil
termistor
Fan motor
fixture
61
E1
E3
E1
E2
E2
11-2 MSH-18NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
MSH-24NV -
INDOOR UNIT
OPERATING PROCEDURE
PHOTOS
1. Removing the front panel
Photo 1
(1) Remove the screw caps at the down of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
Front panel
Screws
2. Removing the electronic control P.C. board
(1) Remove the front panel. (Refer to 1)
Photo 2
(2) Remove the electrical cover.
(3) Remove the screw, remove the terminal cover.
(4) Remove the screw of terminal block.
(5) Unhook the catch of the lamp holder.
(6) Remove the receiver holder.
(7) Disconnect the connectors and the lead wire from 52C
relay on the electronic control P.C. board and remove the
ground and the indoor coil thermistor.
Ground
Indoor coil thermistor
(8) Remove the electronic control P.C. board.
Screw
Terminal
block
screw
Indoor
electronic
control
P.C. board
62
OPERATING PROCEDURE
PHOTOS
3. Removing the electrical box
screw
Photo 3
(1) Remove the front panel. (Refer to 1)
(2) Remove the electrical cover.
(3) Disconnect the connector of the indoor coil thermistor.
(4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con-
trol P.C. board.
(5) Remove the screw of the electrical box, remove the electri-
cal box.
screw
4. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel.
Photo 4
Heat exchanger
(2) Remove the electrical box.
(3) Unhook the catch on the both sides of the nozzle assem-
bly.
(4) Remove the nozzle assembly.
Catch
(5) Remove the screws of the bearing support.
(6) Remove the screw of the heat exchanger unhook the
catch.
Heat exchanger
screw
(7) Lifting the heat exchanger, remove the bearing support.
(8) Remove the motor support.
(9) Loose the screw fixing the line flow fan, remove the line
Bearing support
screws
flow fan.
( )
10 Remove the screws of the motor band, remove the fan
motor.
Photo 5
Indoor fan motor
Fan
motor
screws
Line flow fan
Motor band
63
E1
E1
E2
E2
11-3 MUH-07NV -
OUTDOOR UNIT
MUH-09NV -
MUH-07NV -
MUH-09NV -
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
Photo 1
(1) Remove the top panel.
(2) Remove the cabinet
Photo 2
Service
panel
Screw for
service panel
Screw for
top panel
Screw for
top panel
Screws for
cabinet
Screws for
cabinet
2. Remove the deicer P.C. board
Photo 3
(1) Remove the top panel, the service panel and the cabinet.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
Deicer P.C board
(3) Remove the deicer P.C. board.
3. Removing the propeller fan
Propeller fan
Photo 4
(1) Turn the propeller nut clockwise to remove.
(2) Pull the propeller fan toward you to remove.
Propeller nut
64
OPERATING PROCEDURE
PHOTOS
4. Removing the outdoor fan motor
(1) Remove the screws securing the outdoor fan motor.
(2) Remove the lead clamps.
Photo 5
Outdoor fan motor set screws
(3) Disconnect the capacitor terminal and wire of the terminal.
(4) Pull out the outdoor fan motor.
Lead
fxture
Outdoor fan motor
5. Removing the compressor
(1) Remove the lead clamps.
Photo 6
(2) Remove the screws securing the relay panel.
(3) Remove the screw securing the service port.
(4) Remove the terminal cover. (See Photo 7.)
(5) Pull out the lead from the compressor terminal.
(6) Remove the overcurrect relay.
(7) Remove the compressor nuts.
(8) Detach the suction pipe welded section and discharge pipe
welded section with a burner.
Relay panel
NOTE
● Before using a burner, purge gas from the pipes until the pres-
sure gauge shows 0 kg/cm2.
● Use the burner under the condition that gas can be released
even when the inner pressure rises by heat.
Photo 7
Photo 9
Terminal cover
Compressor
Photo 8
Discharge pipe
Sound proof felt
Compressor nuts
Suction pipe
65
E1
E3
E1
E2
E2
11-4 MUH-12NV -
MUH-18NV -
MUH-18NV -
MUH-12NV -
MUH-18NV -
OUTDOOR UNIT
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
Photo 1
(1) Remove the screws of the cabinet.
(2) Hold the down of the cabinet on the both side to remove
the cabinet.
Photo 2
Screws
Service
panel
Screws
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
Photo 3
Screws
Deicer
P.C. board
(3) Remove the deicer P.C. board.
Compressor
Red lead wire
Black lead wire
White lead wire
Terminal
block
66
OPERATING PROCEDURE
PHOTOS
Photo 4
3. Removing the outdoor fan motor
Set screws for
outdoor fan motor
(1) Remove the cabinet. (Refer to 1)
(2) Disconnect the connector remove the clamp of fan motor
lead wire.
Lead clamps
propeller fan
(3) Remove the propeller nut and remove the propeller.
(4) Remove screws securing the fan motor.
Outdoor
fan motor
Propeller
fan nut
Set screws for
outdoor fan motor
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the soundproof felt.
Photo 5
(3) Remove the terminal cover on the compressor
(4) Remove the electrical assembly.
(Refer to 2)
(5) Release gas from the refrigerant circuit.
(6) Disconnect the welded part of the discharge pipe.
(7) Disconnect the welded part of the suction pipe.
(8) Remove nuts fixing the compressor.
(9) Remove the compressor.
Terminal cover
Discharge
pipe
Suction
pipe
Compressor
Compressor nuts
67
E1
E2
11-5 MUH-24NV-
OUTDOOR UNIT
OPERATING PROCEDURE
MUH-24NV-
PHOTOS
1. Removing the electrical parts
Photo 1
( )
1 Remove the screws and the top panel.
( )
Screws
2 Remove the screw of the cover panel. To remove the
cover panel, pull it toward you and unhook the catch-
es from the side panel.
3 Remove the screw of the service panel. To remove the
service panel, pull it down toward you and unhook the
catches on the both sides.
Top panel
( )
Service panel
Panel cover
Front panel
Photo 2
Transformer
Capacitor
Outdoor controller
board
Contactor
Overcurrent
relay
Screws
Terminal block
2. Removing the fan motor
Photo 3
( )
1 Remove the screws of the front panel.
Open the front panel to a 45-degree angle.
Then lift it and unhook the catches to remove.
2 Remove the propeller nut and the propeller fan.
3 Remove the screws and the fan motor.
Disconnect the lead connectors.
Motor support Separator support
Lead
( )
( )
Propeller
fan
connectors
Valve bed
Propeller nut
68
OPERATING PROCEDURE
PHOTOS
3. Removing the heat exchanger and the compressor
Photo 4
( )
1 Remove the rear panel.Remove the valve bed, and
Screws
open the rear panel to the rear to remove.
NOTE :
All panels are fixed by catches, and must be removed by
shifting up and down.
( )
2 Remove the screws of the right side panel and remove
it.
( )
3 Remove the screws of the rear guard and remove it.
( )
4 Remove the screws of the separator support plate and
remove it.
( )
5 Remove the screws of the motor support and remove
it.
Screws
( )
6 Remove the screws of the valve bed.
The valve bed is fixed by the catches on the right and
left sides.
Lift it to remove.
( )
7 Remove the electrical parts box.
Disconnect the connectors from the high pressure
switch, crank case heater, shell thermo, and fan motor
lead.
( )
8 Remove the screws of the separator and remove it.
( )
9 Remove the screws of the heat exchanger and remove
Photo 5
it.
Heat exchanger
Detach the welded point of pipe.
( )
10 Remove the nuts of the compressor and remove it.
Detach the welded points of the compressor suction
pipe and discharge pipe.
Accumulator
Photo 6
Charge plug
Ball valve
Compressor
69
12 PARTS LIST
INDOOR UNIT
STRUCTURAL PARTS
E1
MSH-07NV -
MSH-09NV -
MSH-12NV -
MSH-07NV -
MSH-09NV -
MSH-12NV -
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
5
E1
E1
E2
E2
E2
1
6
4
2
Optional parts
3
Symbol
in Wiring
Diagram
Q'ty/unit
NO.
Part No.
Part Name
Remarks
MSH-07NV- E1 MSH-07NV- E2 MSH-09NV- E1 MSH-09NV- E2 MSH-12NV- E1 MSH-12NV- E2
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
E02 154 000 FRONT PANEL(WH)
E02 157 000 FRONT PANEL(WH)
E02 199 000 FRONT PANEL(WH)
E02 151 010 GRILL(WH)
1
1
1
1
1
1
1
2
1
1
1
2
1
2
1
1
2
1
2
1
1
2
2
3
E02 164 100 AIR FILTER
1PC/SET
2PCS/SET
E02 151 234 BOX(WH)
4
E02 166 234 BOX(WH)
1
1
2
1
1
2
1
1
2
E02 151 970 INSTALLATION PLATE
E02 166 067 SCREW CAP(WH)
1
2
1
2
1
2
5
6
INDOOR UNIT
1
HEAT EXCHANGER
E1
MSH-07NV -
MSH-09NV -
MSH-12NV -
MSH-07NV -
MSH-09NV -
MSH-12NV -
(WH)
E1
E1
E2
E2
E2
(WH)
(WH)
(WH)
(WH)
(WH)
3
2
Symbol
in Wiring
Diagram
Q'ty/unit
NO.
Part No.
Part Name
Remarks
E1 E2
E1
E2
MSH-07/09NV-
(WH)
MSH-12NV-
(WH)
E02 151 620 INDOOR HEAT EXCHANGER
E02 155 620 INDOOR HEAT EXCHANGER
E02 151 666 UNION(GAS)
1
1
1
1
2
1
{9.52
{12.7
{6.35
E02 155 666 UNION(GAS)
1
1
E02 151 667 UNION(LIQUID)
3
70
INDOOR UNIT
ELECTRICAL PARTS
E1
MSH-07NV -
MSH-09NV -
MSH-12NV -
MSH-07NV -
MSH-09NV -
MSH-12NV -
(WH)
(WH)
(WH)
(WH)
(WH)
(WH)
E1
E1
E2
E2
E2
10
9
7
8
16
6
3
5
1
4
2
13
12
Part number that are circled is not shown in the illustration.
Symbol
Q'ty/unit
in Wiring
Diagram
NO.
Part No.
Part Name
Remarks
E1
E2
MSH-07NV-
(WH)
E1
E2
MSH-09NV-
(WH)
E1
E2
MSH-12NV-
(WH)
E02 166 235 NOZZLE(WH)
E02 166 040 VANE(WH)
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
E02 141 702 DRAIN HOSE
E02 151 303 VANE MOTOR
E02 151 300 INDOOR FAN MOTOR
E02 151 505 RUBBER MOUNT
E02 151 302 LINE FLOW FAN
E02 151 509 BEARING MOUNT
1
3
MV
MF
1
4
1
RC4V19 -
5
2
2PCS/SET
6
1
7
1
8
ROOM TEMPERATURE THERMISTOR
RT11
RT12
TB
1
E02 151 308
E02 151 307
E02 198 375
E02 199 450
E02 200 450
E02 201 450
E02 152 395
E02 127 382
E02 085 385
E02 001 504
E02 151 468
E02 199 520
9
INDOOR COIL THERMISTOR
TERMINAL BLOCK
ELECT CONTROL P.C.BOARD
ELECT CONTROL P.C.BOARD
ELECT CONTROL P.C.BOARD
POWER SUPPLY CORD
FUSE
1
10
11
1
1
12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
13
14
15
16
17
18
F11
3.15A
VARISTOR
NR11
SLEEVE BEARING
RECEIVER
FAN GUARD
71
OUTDOOR UNIT
STRUCTURAL PARTS
E1
MUH-07NV -
MUH-09NV -
MUH-07NV -
MUH-09NV -
E1
E2
5
11
13
E2
2
1
9
10
7
8
4
6
3
Part number that are circled is not shown in the illustration.
Symbol
in Wiring
Diagram
Q'ty/unit
NO.
Part No.
Part Name
Remarks
E1 E2
-
E1 E2
-
MUH-09NV
MUH-07NV
1
1
1
1
1
1
1
1
1
1
1
CABINET
E02 096 232
E02 085 297
E02 199 521
E02 085 245
E02 096 630
E02 128 900
E02 164 900
E02 047 506
E02 096 290
E02 096 662
E02 096 661
E02 085 515
E02 154 642
E02 077 961
E02 154 936
E02 159 936
E02 134 937
E02 199 936
E02 139 936
1
2
3
4
5
TOP PANEL
FAN GUARD
SERVICE PANEL
OUTDOOR HEAT EXCHANGER
COMPRESSOR
MC
MC
RH-174VGHT
RH-135VGHT
6
1
1
1
1
1
1
1
1
COMPRESSOR
1
1
1
1
1
1
1
1
COMPRESSOR RUBBER SET
BASE
7
8
STOP VALVE(LIQUID)
STOP VALVE(GAS)
MOTOR SUPPORT
CHECK VALVE
{6.35
9
{9.52
10
11
12
13
REVERSING VALVE
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
{3.0 ✕{1.6 ✕ 1300
{3.0 ✕{1.4 ✕ 800
{3.0 ✕{1.6 ✕ 400
{3.0 ✕{1.4 ✕ 850
{3.0 ✕{1.6 ✕ 750
2
2
1
14
1
1
72
OUTDOOR UNIT
FUNCTIONAL PARTS AND ELECTRICAL PARTS
E1
MUH-07NV -
MUH-09NV -
MUH-07NV -
MUH-09NV -
E1
E2
E2
6
5
1
2
4
3
Part number that are circled is not shown in the illustration.
Symbol
Q'ty/unit
in Wiring
Diagram
NO.
Part No.
Part Name
Remarks
E1
E2
MUH-07/09NV
-
1
1
1
1
1
1
1
E02 085 501 PROPELLER FAN
1
2
3
4
5
6
7
E02 096 301 OUTDOOR FAN MOTOR
E02 085 353 COMPRESSOR CAPACITOR
E02 199 374 TERMINAL BLOCK
MF
C1
RA6V29-
25+/440VAC
TB
E02 096 310 DEFROST THERMISTOR
E02 199 451 DEICER P.C. BOARD
E02 154 490 REVERSING VALVE COIL
RT61
21S4
73
OUTDOOR UNIT
STRUCTURAL PARTS
3
17
18
E1
MUH-12NV -
MUH-12NV -
E2
15
7
16
2
14
12
4
10
11
13
6
5
8
9
1
Part number that are circled is not shown in the illustration.
Symbol
in Wiring
Diagram
Q'ty/unit
NO.
Part No.
Part Name
Remarks
- E1
E2
MUH-12NV
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
E02 141 521 GRILL
1
2
E02 141 232 CABINET ASSEMBLY
E02 140 233 BACK PANEL
3
E02 141 245 SERVICE PANEL
4
E02 075 506 COMPRESSOR RUBBER SET
E02 139 515 MOTOR SUPPORT
E02 156 630 OUTDOOR HEAT EXCHANGER
E02 141 900 COMPRESSOR
3 RUBBER
5
6
7
MC
RH-231VHAT
8
E02 201 290 BASE
9
E02 139 662 STOP VALVE(LOQUID)
E02 140 661 STOP VALVE(GAS)
E02 077 961 REVERSING VALVE
E02 141 501 PROPELLER FAN
E02 141 301 OUTDOOR FAN MOTOR
E02 079 353 COMPRESSOR CAPACITOR
E02 201 374 TERMINAL BLOCK
E02 139 310 DEFROST THERMISTOR
E02 201 451 DEICER P.C. BOARD
E02 156 490 REVERSING VALVE COIL
E02 156 936 CAPILLARY TUBE
E02 134 937 CAPILLARY TUBE
E02 154 642 CHECK VALVE
{6.35
10
11
12
13
14
15
16
17
18
19
{12.7
MF
CI
RA6V40 -
30+/440VAC
TB
RT61
21S4
{3.0✕{1.4✕ 500
20
21
{3.0✕{1.6✕ 400
74
INDOOR UNIT
STRUCTURAL PARTS
E1
MSH-18NV -
MSH-24NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
(WH)
(WH)
(WH)
(WH)
(WH)
E1
E2
E2
E3
1
5
3
2
Optional parts
6
4
Part number that are circled is not shown in the illustration.
Symbol
Q'ty/unit
in Wiring
MSH-18NV-
MSH-24NV-
NO.
Part No.
Part Name
Remarks
E1
E2 E3
E1 E2
(WH)
(WH)
(WH)
Diagram
FRONT PANEL(WH)
GRILLE(WH)
E02 138 000
E02 138 010
E02 143 234
E02 141 100
E02 141 970
E02 143 067
E02 168 007
E02 214 007
1
1
1
1
1
2
1
3
1
1
2
3
4
5
6
1
1
2
1
3
1
1
2
1
3
1
BOX(WH)
AIR FILTER
1PC/SET
INSTALLATION PLATE
SCREW CAP(WH)
LAMP PANEL(WH)
LAMP PANEL(WH)
3PCS/SET
7
1
INDOOR UNIT
1
HEAT EXCHANGER PARTS
E1
MSH-18NV -
MSH-24NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
(WH)
(WH)
(WH)
(WH)
(WH)
E1
E2
E2
E3
2
3
Symbol
Q'ty/unit
in Wiring
Diagram
MSH-18NV-
MSH-24NV-
NO.
Part No.
Part Name
Remarks
E1 E2 E3
E1 E2
(WH)
(WH)
E02 141 620 INDOOR HEAT EXCHANGER
E02 138 667 UNION(LIQUID)
E02 176 667 UNION(LIQUID)
E02 138 666 UNION(GAS)
1
1
1
1
2
{6.35
{9.52
1
1
{15.88
1
3
75
INDOOR UNIT
ELECTRICAL PARTS
E1
MSH-18NV -
MSH-24NV -
MSH-18NV -
MSH-24NV -
MSH-18NV -
(WH)
(WH)
(WH)
(WH)
(WH)
E1
E2
E2
E3
10
8
11
15
5
7
5
4
3
16
1
9
6
12
2
14
17
Part number that are circled is not shown in the illustration.
Symbol
Q'ty/unit
MSH-18NV-
MSH-24NV-
in Wiring
Diagram
NO.
Part No.
Part Name
NOZZLE(WH)
VANE(WH)
Remarks
E1
E2 E3
E1
E2
(WH)
(WH)
(WH)
(WH)
1
2
3
E02 143 235
E02 143 040
E02 141 702
E02 141 300
E02 213 300
E02 001 505
E02 138 395
E02 320 395
E02 139 450
E02 198 450
E02 214 450
E02 141 302
E02 141 303
1
1
1
1
1
1
1
1
1
1
1
1
1
1
DRAIN HOSE
RA4V27 -EA
RA4V27 -EC
2PCS/SET
INDOOR FAN MOTOR
INDOOR FAN MOTOR
RUBBER MOUNT
MF
MF
4
5
6
1
2
1
1
2
2
1
2
1
POWER SUPPLY CORD
POWER SUPPLY CORD
ELECT CONTROL P.C. BOARD
ELECT CONTROL P.C. BOARD
ELECT CONTROL P.C. BOARD
LINE FLOW FAN
1
1
7
1
1
1
1
1
1
1
1
1
1
1
1
1
8
9
1
1
1
1
1
1
1
1
1
VANE MOTOR
MV
10 E02 138 329
11 E02 141 509
E02 198 375
12 E02 139 375
E02 278 375
13 E02 085 385
14 E02 141 468
15 E02 001 504
16 E02 138 307
17 E02 138 308
18 E02 127 382
DISPLAY P.C. BOARD
BEARING MOUNT
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
VARISTOR
TB
TB
1
1
1
1
1
1
1
1
1
TB
NR11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RECEIVER P. C. BOARD
SLEEVE BEARING
INDOOR COIL THERMISTOR RT12
ROOM TEMPERATURE THERMISTOR RT11
3.15A
FUSE
FAN GUARD
F11
E02 138 520
19
76
OUTDOOR UNIT
STRUCTURAL PARTS
17
20
19
E1
MUH-18NV -
MUH-18NV -
MUH-18NV -
E2
12
E3
10
8
4
1
22
15
16
3
9
5
2
7
14
6
Part number that are circled is not shown in the illustration.
Symbol
Q'ty/unit
in Wiring
Diagram
MUH-18NV-
NO.
Part No.
Part Name
CABINET
Remarks
E1
E2
E3
E02 141 232
E02 141 521
E02 141 245
E02 139 630
E02 139 515
E02 139 900
E02 139 290
E02 144 301
E02 141 501
E02 082 353
E02 004 340
E02 139 374
E02 198 374
E02 139 936
E02 139 937
E02 138 506
E02 139 662
E02 150 661
E02 140 233
E02 095 382
E02 139 451
E02 198 451
E02 139 310
E02 139 490
E02 077 961
E02 128 383
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
GRILLE
3
SERVICE PANEL
4
OUTDOOR HEAT EXCHANGER
MOTOR SUPPORT
COMPRESSOR
5
6
NH-36VMDT
RA6V50 -
MC
MF
7
BASE
8
OUTDOOR FAN MOTOR
PROPELLER FAN
COMPRESSOR CAPACITOR
CONTACTOR
9
10
11
50+/440V
C1
52C
TB
TERMINAL BLOCK
TERMINAL BLOCK
CAPILLARY TUBE
CAPILLARY TUBE
COMPRESSOR RUBBER SET
STOP VALVE(LIQUID)
STOP VALVE(GAS)
BACK PANEL
12
13
1
2
1
4
1
1
1
1
1
2
1
4
1
1
1
1
TB
2
1
4
1
1
1
1
1
{3.0✕{1.6✕750
{3.0✕{2.0✕800
14
15
16
17
18
{6.35
{15.88
FUSE
F61
DEICER P.C. BOARD
DEICER P.C. BOARD
DEFROST THERMISTOR
REVERSING VALVE COIL
REVERSING VALVE
SURGE ABSORBER
19
1
1
1
1
1
1
1
1
1
1
20
21
22
23
1
1
1
1
RT61
21S4
DSAR
77
OUTDOOR UNIT
STRUCTURAL PARTS
17
E1
MUH-24NV-
MUH-24NV-
E2
13
1
22
2
7
5
3
19 10 18
11
24
23
8
4
9
20
12
14 6
15
16
78
OUTDOOR UNIT
STRUCTURAL PARTS
E1
MUH-24NV-
MUH-24NV-
E2
Part number that are circled is not shown in the illustration.
Symbol
Q'ty/unit
in Wiring
MUH-24NV-
MUH-24NV-
NO.
Part No.
Part Name
CABINET
Remarks
E1
E2
Diagram
1
2
E02 214 232
E02 214 521
E02 214 245
E02 214 630
E02 214 515
E02 042 900
E02 214 290
E02 214 301
E02 214 501
E02 082 353
E02 010 342
E02 198 374
E02 214 249
E02 138 506
E02 010 662
E02 010 661
E02 214 297
E02 138 351
E02 214 451
E02 214 310
E02 176 936
E02 256 936
E02 262 936
E02 214 522
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
FAN GUARD
3
SERVICE PANEL
4
OUTDOOR HEAT EXCHANGER
MOTOR SUPPORT
COMPRESSOR
5
6
NH-47VMDT
RA6V85 -
MC
MF
7
BASE
8
OUTDOOR FAN MOTOR
PROPELLER FAN
COMPRESSOR CAPACITOR
CONTACTOR
9
10
11
12
13
14
15
16
17
18
19
20
50+/440VAC
C1
52C1
TB
TERMINAL BLOCK
SIDE PANEL
COMPRESSOR RUBBER SET
STOP VALVE(LIQUID)
STOP VALVE(GAS)
TOP PANEL
{9.52
{15.88
3.0+/440VAC
C11
FAN MOTOR CAPACITOR
DEICER P.C. BOARD
DEFROST THERMISTOR
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
REAR PANEL
RT61
[3.0✕[1.6✕350
[3.0✕[2.0✕350
[4.0✕[2.4✕200
21
22
23 E02 095 382
24 E02 214 381
25 E02 288 343
2A
FUSE
TRS
THERMAL READ SWITCH
FAN MOTOR RELAY
1
ACCESSORY AND REMOTE CONTROLLER PARTS
E1
MSH-07NV - (WH)
E1
MSH-09NV - (WH)
2
E1
MSH-12NV - (WH)
E1
MSH-18NV - (WH)
E1
MSH-24NV - (WH)
E2
MSH-07NV - (WH)
E2
MSH-09NV - (WH)
E2
MSH-12NV - (WH)
E2
MSH-18NV - (WH)
E2
MSH-24NV - (WH)
E3
MSH-18NV - (WH)
Symbol
in Wiring
Diagram
Q'ty/unit
NO.
Part No.
Part Name
Remarks
E1
E2
MSH-07/09/12/18/24NV -
(WH)
E3
MSH-18NV -
(WH)
1
1
E02 139 426 REMOTE CONTROLLER
1
2
E02 141 083 REMOTE CONTROLLER HOLDER
79
13 OPTIONAL PARTS
1. REFRIGERANT PIPES
The air conditioner has flared connections its indoor and outdoor sides.
Please use the optional extension pipe as follows.
Additional
refrigerant
charge
Pipe size O.D mm (in.)
Model
Part No.
Pipe length
Cross-section
A-Gas
B-Liquid
Insulation
R-22(g)
C
D
MAC-440PI
MAC-441PI
MAC-442PI
MAC-443PI
MAC-660PI
MAC-661PI
MAC-662PI
MAC-663PI
MAC-664PI
MAC-670PI
MAC-671PI
MAC-672PI
MAC-673PI
MAC-674PI
MAC-860PIE
MAC-861PIE
MAC-862PIE
MAC-863PIE
MAC-864PIE
3m
5m
7m
10m
3m
5m
E1
E1
E2
E2
MSH-07NV-
MSH-09NV-
MSH-07NV-
MSH-09NV-
0
150
0
9.52 (3/8)
27
21
E1
E2
MSH-12NV-
MSH-12NV-
7m
12.7 (1/2)
10m
15m
3m
5m
7m
10m
15m
3m
5m
7m
6.35 (1/4)
150
400
E1
0
MSH-18NV-
MSH-18NV-
MSH-18NV-
E2
E3
31
27
150
400
15.88 (5/8)
0
MSH-24NV-
MSH-24NV-
E1
E2
9.52 (3/8)
10m
15m
195
520
2. AIR CLEANING FILTER
● AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
● Normal life of AIR CLEANING FILTER is 3 months. However, when it becomes dirty, replace it as soon as possible.
● Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
● DO NOT reuse AIR CLEANING FILTER even if it is washed.
● DO NOT remove or attach AIR CLEANING FILTER during unit operation.
Part No.
Model
E1
E2
E2
E2
MSH-07NV-
MSH-09NV-
MSH-12NV-
MSH-18NV-
MSH-24NV-
MSH-18NV-
MSH-07NV-
MSH-09NV-
MSH-12NV-
E1
E1
E1
E1
E2
MAC-1000FT
MAC-1100FT
E2
E3
MSH-24NV-
MSH-18NV-
3. DEODORIZING FILTER
● DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odors of pets.
● Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
● For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.
● When the filter color is still dark even after cleaning, replace the filter with a new one.
Replace the filter at least once a year.
Part No.
Model
E1
E2
E2
E2
E2
E3
MSH-07NV-
MSH-09NV-
MSH-12NV-
MSH-18NV-
MSH-24NV-
MSH-18NV-
MSH-07NV-
E1
E1
E1
E1
E2
MSH-09NV-
MSH-12NV-
MSH-24NV-
MSH-18NV-
MAC-1500DF
MAC-1600DF
● DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
C Copyright 1997 MITSUBISHI ELECTRIC ENGINIEERING CO.,LTD
Issued in Sep. 1997. No.OB207 646
Printed in Japan
New publication, effective Sep. 1997
Specifications subject to change without notice.
|
Lexmark D02 User Manual
Mitsubishi Electronics Srk507j S User Manual
Multi Tech Systems All In One Printer Mt5600ba User Manual
Panasonic Workio Dp 8020p User Manual
Samsung Sh09zs8x User Manual
Sanyo N 4000drl User Manual
Sharp Al 1255 User Manual
Sharp Ux 465l User Manual
Simplicity Sac8017ee User Manual
Tekkeon Tekcharge Mp1580 User Manual