The Z-COM module joins with functional modules (Z-TIO, Z-DIO modules) and performs PLC
communication and host communication. The combination of Z-COM module and functional module
is called an SRZ unit.
2.3 Dimensions
Module Type Controller SRZ
2. MOUNTING
(Unit: mm)
Installation
Manual
76.9
30
6.7
Communication
Extension Module
Host computer
Z-COM
!
WARNING
SRZ unit
Z-COM module
All Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.
IMS01T05-E2
To prevent electric shock or instrument failure, always turn off the
power before mounting or removing the instrument.
Host communication
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
Programmable controller
PLC communication
This manual describes the mounting, wiring and specifications only. For the basic operations, see
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-Eꢁ), Z-COM PLC
Communication Data List (IMS01T15-Eꢁ) and Z-COM Host Communication Quick Instruction
Manual (IMS01T09-Eꢁ). For the detail handling procedures and various function settings, please
refer to separate Z-COM Instruction Manual (IMS01T07-Eꢁ).
2.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions.
(IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
Z-TIO and Z-DIO modules
Power supply 24 V DC
(2) Use this instrument within the following environment conditions.
•
•
Allowable ambient temperature:
Allowable ambient humidity:
−10 to +50 °C
The above manuals can be downloaded from our website:
5 to 95 % RH
(Absolute humidity: MAX. W. C 29.3 g/m3 dry air at 101.3 kPa)
•
Installation environment conditions: Indoor use
Altitude up to 2000 m
ꢃSpace required between each
module vertically
ꢃDepth for communication cables mount
type module
ꢂ
ꢂ
Accessories check
(3) Avoid the following conditions when selecting the mounting location:
When the module is mounted on the panel,
allow a minimum of 50 mm at the top and
bottom of the module to attach the module
to the mainframe.
Space for communication cables must be
considered when installing.
Z-COM Installation Manual (This manual) ........................................................................ 1
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-Eꢁ)....................... 1
Z-COM PLC Communication Data List (IMS01T15-Eꢁ)................................................. 1
Z-COM Host Communication Quick Instruction Manual (IMS01T09-Eꢁ) ...................... 1
Joint connector cover (KSRZ-517A).................................................................................. 2
Power terminal cover (KSRZ-518A).................................................................................. 1
1. PARTS DESCRIPTION
•
•
•
•
•
•
•
•
•
Rapid changes in ambient temperature which may cause condensation.
Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam splashes.
Excessive dust, salt or iron particles.
Excessive induction noise, static electricity, magnetic fields or noise.
Direct air flow from an air conditioner.
Exposure to direct sunlight.
ꢂ
Module mainframe
(Unit: mm)
Approx. 50
76.9
Address setting switch
Z-COM module (Right side view)
Indication lamp (FAIL/RUN)
Communication
cables
Safety precautions
Excessive heat accumulation.
50 mm or more
Loader communication
connector
(4) Take the following points into consideration when mounting this instrument in the panel.
•
•
•
•
Ensure at least 50 mm space on top and bottom of the instrument for maintenance and
environmental reasons.
!
WARNING
Indication lamp (RX1/TX1)
Do not mount this instrument directly above equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors).
If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or
the like. However, do not allow cooled air to blow this instrument directly.
In order to improve safety and the immunity to withstand noise, mount this instrument as far
away as possible from high voltage equipment, power lines, and rotating machinery.
ꢃAn external protection device must be installed if failure of this instrument
Communication port
COM. PORT1
could result in damage to the instrument, equipment or injury to personnel.
DIP switch
ꢃAll wiring must be completed before power is turned on to prevent electric
Communication 1
ꢂ
Procedure for mounting or removing
COM. PORT2
shock, fire or damage to instrument and equipment.
The procedure for mounting or removing the Z-COM module is the same as that of the function
module (Z-TIO or Z-DIO). Both DIN rail mounting and screw mounting are available.
For details on module mounting or removing, see the Z-TIO INSTRUCTION MANUAL
(IMS01T01-Eꢄ).
ꢃThis instrument must be used in accordance with the specifications to
Indication lamp (RX2/TX2)
High voltage equipment: Do not mount within the same panel.
prevent fire or damage to instrument and equipment.
Power lines:
Rotating machinery:
Separate at least 200 mm.
Separate as far as possible.
Communication port
COM. PORT3
ꢃThis instrument is not intended for use in locations subject to flammable or
Communication 2
•
Be sure the Z-COM module and functional modules (Z-TIO, Z-DIO) are joined when using them.
explosive gases.
COM. PORT4
ꢃDo not touch high-voltage connections such as power supply terminals,
3. WIRING
etc. to avoid electric shock.
Top
OFF
ON
ꢃRKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
Indication lamp
!
WARNING
FAIL/RUN
When normal:
A green lamp is on (RUN)
A green lamp flashes (FAIL)
Bottom
To prevent electric shock or instrument failure, do not turn on the
power until all the wiring is completed.
[Green or Red]
Self-diagnostic error:
CAUTION
Instrument abnormality: A red lamp is on (FAIL)
(5) This instrument is Permanently connected to equipment, please take the following points.
RX1/TX1
[Green]
The green lamp is lit when data corresponding to communication 1
(COM. PORT1/COM. PORT2) is sent or received.
•
•
•
A switch or circuit-breaker shall be included in the building installation.
It shall be in close proximity to the equipment and within easy reach of the operator.
It shall be marked as the disconnecting device for the equipment.
ꢃ This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
RX2/TX2
[Green]
The green lamp is lit when data corresponding to communication 2
(COM. PORT3/COM. PORT4) is sent or received.
3.1 Wiring Cautions
ꢃ This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply, source
of power and loads.
•
To avoid noise induction, keep communication signal wire away from instrument power line, load
lines and power lines of other electric equipment.
2.2 Joining Each Module
Communication port (modular connector) and Communication connector
•
If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
ꢃ Be sure to provide an appropriate surge control circuit respectively for the following:
Before joining the Z-COM module and functional modules, use the DIP
switches to make the communication settings. For the setting procedure, see
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-Eꢁ).
COM. PORT1
(Communication 1)
Used to connecting the Operation panel or Host computer.
[RS-485 or RS-422A]
−
Shorten the distance between the twisted power supply wire pitches to achieve the most
effective noise reduction.
−
If input/output or signal lines within the building are longer than 30 meters.
If input/output or signal lines leave the building, regardless the length.
−
−
Always install the noise filter on a grounded panel. Minimize the wiring distance between the
noise filter output and the instrument power supply terminals to achieve the most effective
noise reduction.
COM. PORT2
(Communication 1)
The COM. PORT2 is used for the extension of the SRZ unit.
[RS-485 or RS-422A]
ꢃ This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage
connections such as power supply terminals must be enclosed in the instrumentation panel to
avoid electric shock by operating personnel.
The maximum number of functional modules (Z-TIO-A/B, Z-DIO) described in the following can be
joined per Z-COM module. For details on joining functional modules with the Z-COM module, see
the Z-TIO INSTRUCTION MANUAL (IMS01T01-Eꢄ).
COM. PORT3
(Communication 2)
Used to connecting the programmable controller (PLC), Operation
panel or Host computer. [RS-485 or RS-422A]
−
Do not connect fuses or switches to the noise filter output wiring as this will reduce the
effectiveness of the noise filter.
ꢃ All precautions described in this manual should be taken to avoid damage to the instrument or
COM. PORT4
(Communication 2)
The COM. PORT4 is used for the extension of the SRZ unit.
[RS-485 or RS-422A]
•
•
•
Power supply wiring must be twisted and have a low voltage drop.
For an instrument with 24 V power supply, supply power from a SELV circuit.
A suitable power supply should be considered in the end-use equipment.
The power supply must be in compliance with a limited-energy circuits (maximum available
current of 8 A).
equipment.
ꢃ All wiring must be in accordance with local codes and regulations.
•
•
When joining functional modules of the same type:
When joining functional modules of two or more different types: Up to 31 modules
(However, the maximum joinable number of functional modules of the same type is 16.)
Up to 16 modules
Loader
communication
connector
This is a connector to be connected to converter and personal
computer when loader communication is performed.
ꢃ To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
•
•
Supply the power to only one of the joined modules. When power is supplied to any one of the
joined modules, all of the joined modules will receive power.
Select the power capacity which is appropriate for the total power consumption of all joined
modules and the initial current surge when the power is turned on.
ꢃ Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric
[Example] When the Z-TIO-A/B and Z-DIO modules are joined
shock, fire or malfunction.
Switch
ꢃ Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
SRZ unit
Address setting
switch
Set unit address of SRZ unit with address setting switch.
fire or malfunction.
Power consumption (at maximum load):
30 mA max. (at 24 V DC)
Rush current: 10 A or less
Z-COM module
ꢃ For proper operation of this instrument, provide adequate ventilation for heat dispensation.
DIP switch
• Sets communication speed, communication protocol and data bit
configuration corresponding to each of communication 1 and
communication 2.
•
When connecting the wiring to the power supply terminals on the base, use the specified
solderless terminals. Only these specified solderless terminals can be used due to the insulation
ꢃ Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
between the terminals.
• Sets dip switch setting validity/invalidity.
ꢃ Turn off the power supply before cleaning the instrument.
φ 5.5 MAX
Screw Size: M3 × 7 (with 5.8 × 5.8 square washer)
ꢃ Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
φ 3.2 MIN
φ 3.2
Recommended tightening torque: 0.4 N・m (4 kgf・cm)
Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm2
Specified solderless terminal:
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
ꢂ
Base
16 Z-TIO-A/B modules 15 Z-DIO modules
Functional modules: Up to 31 modules
ꢃ
To avoid damage to instrument display, do not rub with an abrasive material or push front panel
with a hard object.
Manufactured by J.S.T MFG CO., LTD.
Circular terminal with isolation V1.25−MS3
(M3 screw, width 5.5 mm, hole diameter 3.2 mm)
Joint connector
9.0 mm
Mounting holes (M3 screw)
Holes for screws to fix the base
to a panel, etc.
Customer must provide the M3
screws.
5.6 mm
Used to mechanically and
electrically connect
each module.
NOTICE
ꢃ This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
When the number of correspondence channels is specified using the model code, only the
amount of data corresponding to the specified number of channels can be sent or received
(PLC communication only).
process control, computer technology and communications.
3.2 Terminal Configuration
Base
ꢃ The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
ꢃ RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
ꢂ
The number of the
correspondence
channels
Power supply terminals
instrument failure or indirect damage.
Z-TIO-A/B module
Z-DIO module
1
2
These are terminals to supply
power to the Z-COM module
or joined function modules.
Power supply
terminals
ꢃ RKC is not responsible for any damage and/or injury resulting from the use of instruments made
by imitating this instrument.
Supply the power to only one of the
joined modules.
64 channels
(However, up to 16 modules)
48 channels
(However, up to 16 modules)
128 channels
(Up to 16 modules)
96 channels
(Up to 12 modules)
64 channels
(Up to 8 modules)
32 channels
(Up to 4 modules)
1
2
64 channels
48 channels
32 channels
16 channels
ꢃ Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
When power is supplied to any one of the
joined modules, all of the joined modules
will receive power.
1
2
Mounting bracket
3
4
5
ꢃ Every effort has been made to ensure accuracy of all information contained herein. RKC makes
no warranty expressed or implied, with respect to the accuracy of the information. The information
in this manual is subject to change without prior notice.
Used to fix the module on
DIN rails and also to fix
Terminal 3, 4 and 5
3
4
5
−
32 channels
16 channels
+
These terminals cannot be
used for the Z-COM module.
(Usage is prohibited.)
each module joined together.
24 V DC
ꢃ
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
Terminals 3, 4 and 5 (Usage is prohibited.)
(Continued on the next page ꢀ)
Download from Www.Somanuals.com. All Manuals Search And Download.
|