Vulcan Hart Electric Steamer MHB24G User Manual

SERVICE MANUAL  
VHX BOILER BASE SERIES  
HIGH EFFICIENCY GAS  
STEAMERS  
VHX24G  
VHX24G5 ML-126590  
MHB24G ML-114954 (BASE ONLY)  
ML-114795  
VHX24G SHOWN  
- NOTICE -  
This Manual is prepared for the use of trained Vulcan Service  
Technicians and should not be used by those not properly  
qualified. If you have attended a Vulcan Service School for this  
product, you may be qualified to perform all the procedures  
described in this manual.  
This manual is not intended to be all encompassing. If you have  
not attended a Vulcan Service School for this product, you should  
read, in its entirety, the repair procedure you wish to perform to  
determine if you have the necessary tools, instruments and skills  
required to perform the procedure. Procedures for which you do  
not have the necessary tools, instruments and skills should be  
performed by a trained Vulcan Service Technician.  
Reproduction or other use of this Manual, without the express  
written consent of Vulcan, is prohibited.  
A product of VULCAN-HART  
LOUISVILLE, KY 40201-0696  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS  
Air Pressure Switch Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Gas Pilot Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Gas Manifold Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Ignition Control Module Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Cooking Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Intake Shut-Off Valve Adjustment (Steam Flow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Door Sealing Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Door Latch Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
ELECTRICAL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
Water Level Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
Low Level Cut-Off & Differential Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
Auxiliary Low Level Cut-Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Board Layout and LED Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Boiler Operational Status (LED Indicator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
New Style Controls - Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Old Style Controls - Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
Models Built After 5/25/00 (New Style Boiler Controls) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
Models Built Before 5/25/00 (Old Style Boiler Controls) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55  
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56  
Models Built After 5/25/00 (New Style Boiler Controls) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56  
Models Built Before 5/25/00 (Old Style Boiler Controls) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61  
CONDENSED SPARE PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68  
© VULCAN 2001  
Page 3 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - GENERAL  
GENERAL  
Model Designations  
INSTALLATION  
Refer to the Installation and Operation Manual for  
detailed installation instructions.  
MAINTENANCE  
Refer to the Installation and Operation Manual for  
specific maintenance instructions.  
CLEANING  
Refer to the Installation and Operation Manual for  
specific cleaning instructions.  
INTRODUCTION  
Boiler Code Descriptions  
Vulcan-Hart incorporates redundant controls in  
compliance with the CSD-1 controls and safety  
devices for boiler construction on these High  
Efficiency Steam models. A Description of the code  
is listed below.  
Steam Cooking  
Convection cooking in pressure-less steaming  
compartments will steam cook fresh foods or will  
steam defrost and cook frozen foods providing the  
maximum color, flavor and nutritional value with the  
least expenditure of energy and labor. The pressure-  
less steaming compartments on the VHX series  
allows the operator to open and close the door,  
anytime during a cooking cycle. The steam supply  
will shut off when the door is opened, then re-start  
when the door is closed.  
CSD-1 Construction - Redundant controls in the  
electrical safety circuits that, if tripped, must  
manually be reset after the condition causing the trip  
subsides. These controls consist of - (1) dual  
function water level cycling and low level cut off  
control and (1) single function low water level cut-off  
control (Aux LLCO) and a high pressure relief switch  
in conjunction with a mechanical pressure relief  
valve. Additionally, both circuits have individual  
indicator lights for low water and high pressure that  
will illuminate for a visual verification of the  
shutdown mode.  
Compartment Pan Capacity  
PAN  
DEPTH  
(INCHES)  
NUMBER OF PANS  
PER COMPARTMENT  
MODEL  
CSD-1 construction requires operator intervention in  
the event of a shutdown. The indicator lights show  
the operator which safety system was shutdown.  
2
4.0  
2.5  
1.0  
4.0  
2.5  
1.0  
VHX24G  
3
6
3
VHX24G5  
5
10  
Pan Size 12" x 20"  
F24700 (October 2001)  
Page 4 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - GENERAL  
Boiler Control Styles  
VHX Steamers manufactured using the old style boiler controls ended on 5/19/00. Steamers that were in stock at  
the time of the boiler control changeover were removed and equipped with the new style controls without  
recording the serial number for tracking.  
Refer to the pictures below to differentiate between the old style and new style boiler controls.  
Page 5 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - GENERAL  
WATER CONDITIONING  
SPECIFICATIONS  
Furnishing the boiler with treated water to reduce  
scale formation is important. Scale formation will  
reduce steam output, cause premature component  
failure, and shorten equipment life. Most water  
supplies contain scale producing minerals such as  
Calcium and Magnesium. As steam is generated,  
the minerals remain and dissolve into the water. As  
the concentration of these minerals increases past a  
certain point, they precipitate from the water and  
coat the inside of the boiler, heating elements, and  
water level sensors. Because of the high  
Water Supply  
The fact that a water supply is potable is no  
guarantee that it is suitable for steam generation.  
The supply connection to the steam generator  
should be “treated” water and must be within the  
guidelines listed below. For drain water cooling only,  
an “untreated“ water supply connection should be  
used.  
Supply pressure should be  
In line strainer for supply line  
Supply connection  
Total dissolved solids (TDS)*  
Total alkalinity  
20-60 psig  
(Not Supplied)  
cold  
temperature of these surfaces, the precipitated  
minerals bake onto them and become very difficult  
to remove.  
less than 60 ppm  
less than 20 ppm  
less than 13 ppm  
less than 30 ppm  
7 to 8  
This may cause several problems:  
1. Reduced heat transfer efficiency.  
2. Premature heating element failures.  
3. False readings from water level sensors.  
Silica  
Chloride  
PH factor  
(*17.1 ppm = 1 grain of hardness)  
These problems are common to any manufacturer's  
steamer regardless of design, but they can all be  
minimized by furnishing the boiler with treated  
water.  
Electrical  
Voltage - 120/60/1  
Amps - 3.0 (max)  
Other factors affecting steam generation are iron  
content, amount of chlorination and dissolved  
gases.  
The desired water properties can best be achieved  
by using a properly maintained water treatment  
system.  
Boiler Pressure  
Operating - 8 to 10 psi  
Maximum - 15 psi  
The water level probes in the boiler use ions in the  
water to detect the water level. Do not use fully  
demineralized or de-ionized water since it is  
"non conductive" and the water level can not be  
detected.  
The use of strainers or non approved filters will not  
remove minerals from the water.  
Water supplies vary from state to state and from  
locations within a state. Therefore, a water  
treatment specialist should be consulted before  
the installation of any steam generating equipment.  
Steamers that operate over a long period of time  
without the benefit of a water treatment system,  
which have developed a heavy scale build up,  
should be cleaned before using the system.  
F24700 (October 2001)  
Page 6 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - GENERAL  
Gas Supply  
MODEL  
LINE PRESSURE  
(INCHES W.C.)  
MANIFOLD  
PRESSURE  
(INCHES W.C.) (INCHES W.C.)  
PILOT  
PRESSURE  
INPUT  
(BTU/HR)  
NATURAL  
MINIMUM  
PROPANE  
MINIMUM  
MAXIMUM  
ALLOWED  
NAT.  
PROP. NAT. PROP. NAT. PROP.  
RECOMMENDED RECOMMENDED  
200,000 200,000  
270,000 270,000  
200,000 200,000  
270,000 270,000  
200,000 200,000  
270,000 270,000  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
11.0  
11.0  
11.0  
11.0  
11.0  
11.0  
VHX24G  
VHX24G5  
MHB24G  
14.0  
1. Output Boiler Horsepower (BHP): 4.3 BHP for 200,000 BTU; 5.5 BHP for 270,000 BTU.  
2. Input BTU/HR difference is based on gas orifice size and air orifice size.  
NOTE  
:
TOOLS  
Standard  
Standard set of hand tools.  
Volt-Ohm-Meter (VOM) with AC current tester.  
(Any quality VOM with a sensitivity of at least 20,000 ohms per volt can be used)  
Gas leak checking equipment.  
Gas pressure manometer  
Temperature meter and thermocouple.  
Special  
The recommended deliming chemical for the water treatment system in use, for deliming of the boiler.  
Contact Vulcan Authorized Service Centers.  
Heat Exchanger Gasket (joint sealant strip, Teflon) P/N 854058-1.  
Page 7 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - OPERATION  
STEAMER OPERATION  
2) If pilot burner flame is not  
CABINET BASE BOILER  
established immediately, sparking will  
continue for 90 seconds. After that  
duration, the ignition control module  
will lock out and needs to be reset to  
start the pilot and main burner lighting  
cycle again.  
Ensure that all utility connections to the steamer  
have been made and are turned ON and that the  
knob on the main gas valve is in the ON position.  
The VHX Series steamers are CSD-1 compliant and  
are equipped with amber colored lights on the boiler  
control panel for High Pressure and Low Water level  
that illuminate and stay on until the boiler is full and  
the manual reset switch pressed.  
New Style Controls - Power to the  
Pilot gas valve operates on a "timer"  
circuit allowing gas flow to the pilot  
for approximately 15 seconds, during  
ignition trial, then turns off.  
1. Turn power switch ON.  
D. Main gas valve opens, burner ignites and  
begins to heat the water in the boiler. After  
approximately 15 minutes, steam should  
be present for cooking product. Observe  
that the boiler pressure gauge indicates a  
steam pressure of 8-10 psi before the  
burner shuts OFF.  
A. Amber colored lights on the boiler control  
panel for High Pressure and Low Water  
level will illuminate. and stay on until the  
boiler is full and the reset switch is  
pressed.  
B. Water will begin filling the boiler and the  
blowdown solenoid valve will close. The  
boiler should fill, in four to eleven minutes.  
3. The cycling pressure switch will maintain steam  
pressure in the boiler by cycling the main  
burner ON and OFF.  
C. As water fills the boiler, observe water  
level gauge glass to verify that water is in  
boiler. See "WATER LEVEL GAUGE  
ASSEMBLY" in "COMPONENT  
COOKING COMPARTMENT  
CONTROLS  
FUNCTIONand COMPONENT  
LOCATION under "REMOVAL AND  
REPLACEMENT OF PARTS".  
When the steam pressure in the cooking  
compartment manifold reaches approximately 3 psi,  
the cooking compartment pressure switch closes,  
suppling power to the other cooking compartment  
controls. The ready lights will illuminate and after  
approximately one minute, the steam pressure in  
the boiler will reach the upper limit of 10 psi. If the  
pressure drops below approximately 3 psi, the  
pressure switch will open, removing power from the  
controls.  
D. Once the water in the boiler reaches the  
minimum level, the green ready light on  
the boiler control panel will illuminate.  
NOTE: If the fill has stopped, one visible inch  
of water should be in the gauge glass.  
2. Press the reset switch on the boiler control  
panel.  
A. Low water level safety circuit will be reset  
and the Low Water level light (amber) will  
turn off.  
NOTE: On initial startup, if a cooking timer is set  
immediately after the ready light comes on, steam  
solenoid chattering will be heard (oil canning) and  
the ready lights will flash for several seconds. This  
condition is caused by the manifold steam pressure  
being on the fringeof the pressure switch set point.  
When a cook timer is set, the compartment steam  
solenoid valve opens causing the manifold steam  
pressure to drop, slightly below the pressure switch  
set point. At the same time, steam pressure is still  
increasing in the boiler. This opposing condition  
causes a pressure bounceto occur. After the  
steam pressure passes approximately 4 psi this  
condition subsides. During normal operation, this  
condition will not be seen.  
B. High pressure safety circuit will be reset  
and the High Pressure light (amber) will  
turn off.  
C. Sparking will begin three seconds later to  
light the pilot burner.  
1) If the pilot burner lights, a signal is  
sent back through the ignition cable  
indicating the presence of pilot burner  
flame and sparking stops.  
F24700 (October 2001)  
Page 8 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - OPERATION  
1. With both timer knobs at the off position, open  
BOILER BLOWDOWN AND  
STEAMER SHUT OFF  
the compartment doors and observe that no  
steam has entered the cooking compartments,  
then close the doors.  
2. Set both timer knobs at 2 minutes. The ready  
lights will go off, the cooking lights will come  
on, and steam will begin to enter the  
compartments.  
Turn the steamer off at least once daily to blowdown  
the boiler. This will aid in the removal of sediment  
and scale build-up in the boiler.  
NOTE: Boiler should be with-in normal operating  
3. After one minute, open each door and observe  
that steam has ceased to enter each  
compartment, cooking lights go back to ready,  
and one minute is remaining on each cook  
timer.  
pressures.  
1. Turn power switch OFF.  
2. Boiler blowdown sequence starts.  
A. The blowdown/drain solenoid valve will be  
de-energized and the boiler will begin to  
drain.  
4. Close doors and steam generation and cook  
timing will resume. Observe the floor drain to  
ensure that live steam from compartments is  
being cooled by cold water from the cold water  
condenser solenoid valve.  
B. The cold water condenser solenoid will  
operate, as needed, to condense steam  
and to cool the water going into the drain.  
5. When timer knobs reach "0", buzzers will  
sound, steam generation will cease, cooking  
lights will go off and ready lights will come on.  
To silence buzzers, turn timer knobs to off  
position.  
6. During idle time or a cooking cycle, the heating  
system will cycle on and off as necessary to  
maintain steam pressure in the boiler.  
7. Turn power switch off to remove power from  
the steamer.  
A. Boiler blowdown starts.  
Page 9 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - COMPONENT FUNCTION  
COMPONENT FUNCTION  
CABINET BASE BOILER CONTROLS  
Power Switch (ON/OFF) . . . . . . . . . When turned ON, supplies power to the control circuit.  
Reset Switch (Manual) . . . . . . . . . . Resets the low water level safety circuit on initial startup or the  
occurrence of a low water condition and allows the boiler to fill with  
water. Also, resets the high pressure level safety circuit on initial startup  
or the occurrence of a high pressure condition and allows the gas  
ignition cycle to start.  
Boiler Fill Solenoid Valve . . . . . . . . Admits water to the boiler when demanded by the water level control to  
maintain the correct water level in the boiler.  
Cold Water Condenser  
Solenoid Valve . . . . . . . . . . . . . . . . . Allows cold water flow into the boiler blowdown drain box to condense  
steam and cool the hot water before its discharge into the drain.  
Blowdown/Drain  
Solenoid Valve . . . . . . . . . . . . . . . . . A normally open valve (N.O.) that closes to allow boiler to fill and  
pressurize when power switch is turned ON and opens when power  
switch is turned off to blowdown and drain the boiler. This valve is  
plumbed into the drain line of the boiler.  
Cycling Pressure Switch . . . . . . . . . Controls boiler pressure between prescribed limits by turning the heat  
source on and off.  
High Limit Pressure Switch . . . . . . Protects the boiler from pressures above 15 psi by removing power from  
the heating circuit. This pressure setting is higher than the cycling  
pressure switch in order to turn off the heat source before the boiler  
pressure reaches its limit. After the pressure drops below approximately  
12psi, press the rest switch of the front control panel to rest the safety  
circuit.  
Main Water Level Control . . . . . . . . A dual functioning control that allows water to fill and maintain the  
proper level in the boiler providing differential water level control; and  
shuts off the main gas valve if the water level drops too low providing  
low level cut-off protection. The water level control works by using three  
different probe lengths to monitor the water level. The probes consist of  
a high level (HL), low level (LL) and low water cut-off (LLCO).  
Auxiliary Water Level Control . . . . . A back up to the low level cut-off on the main control. Protects the boiler  
and heating system components from a low water cut-off condition by  
opening the 24VAC voltage path to the heating system circuit. Also,  
energizes the low water "light" on the front control panel.  
Transformer . . . . . . . . . . . . . . . . . . . Provides 24VAC power to ignition control module and heating circuit.  
Ignition Control Module . . . . . . . . . Controls and monitors gas heating. Energizes pilot valve coil to supply  
gas to pilot, generates spark to ignite gas at the pilot, monitors the  
presence of flame and energizes the main and pilot valve coils on the  
main gas valve upon a call for heat.  
Main Gas Valve . . . . . . . . . . . . . . . . A gas solenoid valve that opens to allow gas flow to the main burner  
after the successful ignition of the pilot burner when a call for heat is  
made.  
Pilot Gas Valve . . . . . . . . . . . . . . . . A gas solenoid valve that opens to allow gas flow to the pilot to ignite the  
main burner when a call for heat is made. The valve is energized by a  
time delay circuit on the relay board during ignition trial for  
approximately 15 seconds. New style controls only.  
Combustion Blower . . . . . . . . . . . . Provides forced air to the gas/air mixture for gas pilot and main burner  
combustion.  
F24700 (October 2001)  
Page 10 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - COMPONENT FUNCTION  
Relay Board . . . . . . . . . . . . . . . . . . . Provides a centralized location for wire harness connections and power  
transfer through board relays (K1-K7) to the steamer controls. Also,  
provides a condition or component troubleshooting indicator by utilizing  
seventeen LEDS on the board to represent the status of the condition or  
component in the operation sequence. For an LED legend, see "RELAY  
BOARD" under "ELECTRICAL OPERATION". New style controls only.  
NOTE: The relays below are mounted on the relay board and are not individually replaceable.  
K1 Relay . . . . . . . . . . . . . . . . . . . . . . Energized when Aux LLCO is satisfied and turns ready light (green) ON  
if high limit pressure switch is closed. Also, K1 allows K3 to be energized  
when the reset switch is pressed.  
K2 Relay . . . . . . . . . . . . . . . . . . . . . . Energized when high limit pressure switch is closed (high limit pressure  
condition satisfied). When K1 & K2 are energized, the ready light (green)  
will be ON.  
K3 Relay . . . . . . . . . . . . . . . . . . . . . . When Aux LLCO is satisfied and the manual reset switch is activated,  
K3 is energized. When K3 is energized, turns water error light OFF and  
allows the ignition sequence to begin. K3 must be energized for ignition  
sequence to begin.  
K4 Relay . . . . . . . . . . . . . . . . . . . . . . Energized when K2 contacts are closed and manual reset switch is  
activated. When K4 is energized, the high pressure light is OFF. When  
K3 and K4 are both energized, power to the ignition system is supplied.  
K5 Relay . . . . . . . . . . . . . . . . . . . . . . Energized when operating conditions are met and reset switch is  
activated. Provides power to start combustion blower.  
K6 Relay . . . . . . . . . . . . . . . . . . . . . . Energized by time delay circuit for approximately 15 seconds. When K6  
and K7 are energized, power is supplied to the pilot gas valve.  
K7 Relay . . . . . . . . . . . . . . . . . . . . . . Energized when pilot voltage (PV) from the ignition module is present.  
Also used in the time delay circuit.  
Pilot . . . . . . . . . . . . . . . . . . . . . . . . . Ignites to light the main burner upon a call for heat.  
Main Burner . . . . . . . . . . . . . . . . . . . Heats the water in the boiler to generate steam.  
Water Level  
Gauge Assembly . . . . . . . . . . . . . . . Permits a visual confirmation the water level is being maintained in  
boiler during operation. The correct water level is approximately one  
visible inch in the glass. The manual valves at the top and bottom of this  
assembly must be fully open and only closed if the glass tube is  
damaged.  
Water Inlet Valve (manual) . . . . . . . The water inlet valve is used to stop water flow to the steamer when the  
steamer is being serviced. This valve should remain open during normal  
operation.  
Inline Water Strainer . . . . . . . . . . . . A "Y" strainer is installed upstream of the blowdown solenoid valve to  
prevent foreign matter from becoming lodged in the valve. A strainer  
(not supplied) should also be installed in the water supply line to prevent  
foreign matter from becoming lodged in the fill or cold water condenser  
solenoid valves and to keep unwanted particles out of the system.  
Pressure Relief Valve . . . . . . . . . . . A mechanical device that opens to relieve steam pressure in the boiler if  
the pressure exceeds 13 psi.  
High Pressure Relief Valve . . . . . . . A back-up mechanical device that opens to relieve steam pressure in  
the boiler if the pressure exceeds 15 psi.  
Descaler . . . . . . . . . . . . . . . . . . . . . . Hangs below the water level inside the boiler and is used to help control  
boiler surface scaling. Two descalers are used in each boiler.  
Boiler Pressure Gauge . . . . . . . . . . Indicates the amount of steam pressure in the boiler.  
Steam Header Assembly . . . . . . . . . Main steam supply line from the boiler to the steam header inlet in the  
cooking control compartment.  
Page 11 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - COMPONENT FUNCTION  
COOKING COMPARTMENT CONTROLS  
The upper section of the steamer consists of two separate cooking compartments. Each compartment functions  
independently with its own set of controls. Power is supplied to the controls only after the steam pressure rises  
above the compartment pressure switch setting to close the N.O. contacts.  
Ready Light (Green) . . . . . . . . . . . . When lit, indicates steamer is ready to cook.  
Cooking Light (Red) . . . . . . . . . . . . When lit, indicates steamer is in a cooking cycle.  
Cooking Timer . . . . . . . . . . . . . . . . . Use to set desired cooking cycle time between 0-60 minutes. When a  
timer is set, the steam supply solenoid valve is energized to allow steam  
into the cooking compartment but only after the boiler has reached its  
operating pressure. Also, energizes the buzzer when time expires.  
Buzzer . . . . . . . . . . . . . . . . . . . . . . . Signals end of a cook cycle, must be turned off manually.  
Door Switch . . . . . . . . . . . . . . . . . . . Removes electrical power to the timer. If time is dialed on the cooking  
timer and compartments are steaming, removes power to the steam  
solenoid valve when the compartment door is opened.  
Steam Solenoid Valve . . . . . . . . . . . When energized, opens to allow steam into the cooking compartment  
(normally closed valve).  
Compartment Pressure Switch . . . . Supplies power to the controls only after the steam pressure rises above  
approximately 3 psi to close the compartment pressure switch. The  
switch remains closed as long as steam pressure stays above this  
pressure.  
Manifold Pressure Gauge . . . . . . . . Indicates the amount of steam pressure in manifold. The intake shut-off  
valve should be adjusted so manifold pressure remains at 9 psi with both  
compartments on.  
Steam Supply Manifold . . . . . . . . . . Main steam supply line from the boiler for each cooking compartment.  
Supplies steam up to the steam solenoid valve.  
Intake Shut-Off Valve . . . . . . . . . . . Main steam supply shut-off from the boiler to the steam supply manifold.  
This valve should NOT be left fully OPEN to boiler steam supply. See  
INTAKE SHUT-OFF VALVE ADJUSTMENT (STEAM FLOW)" in  
SERVICE PROCEDURES AND ADJUSTMENTS".  
F24700 (October 2001)  
Page 12 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
REMOVAL AND REPLACEMENT OF PARTS  
COMPONENT LOCATIONS  
Cabinet Base Boiler Controls  
Page 13 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
Cabinet Base Boiler Controls Continued  
F24700 (October 2001)  
Page 14 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
Cooking Compartment Controls  
WATER LEVEL CONTROLS  
(MAIN OR AUXILIARY LLCO)  
RELAY BOARD  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1. Open the cabinet base door.  
1. Open the cabinet base door.  
2. Remove the cover from the main control box to  
access the relay board. Refer to "CABINET  
BASE BOILER CONTROLS" under  
2. Remove the cover from the pressure switch  
control box to access the water level controls.  
Refer to "CABINET BASE BOILER  
CONTROLS" under "COMPONENT  
LOCATIONS" in "REMOVAL AND  
"COMPONENT LOCATIONS" in "REMOVAL  
AND REPLACEMENT OF PARTS".  
3. Disconnect all lead wires from the board.  
REPLACEMENT OF PARTS".  
4. Compress the locking tab on the board  
mounting "standoffs" and remove the relay  
board.  
3. Disconnect lead wires from the board being  
replaced.  
4. Compress the locking tab on the board  
mounting "standoffs" and remove the water  
level control.  
5. Reverse procedure to install and check for  
proper operation.  
5. Reverse procedure to install and check for  
proper operation.  
Page 15 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
1) Remove the mounting screws on the  
WATER LEVEL GAUGE  
ASSEMBLY  
back side of the control box and lift  
out the pressure switch. Proceed to  
step 5.  
B. High limit control - disconnect the lead  
wires.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
5. Disconnect the pressure fittings at the bottom  
of the switch.  
6. Preset the new pressure switch to the  
approximate cut-out (OFF) and cut-in (ON) set  
points before installing. Refer to "PRESSURE  
SWITCHES" in "SERVICE PROCEDURES  
AND ADJUSTMENTS".  
1. Open the cabinet base door and remove the  
right side panel.  
2. Close the valve at the top and at the bottom of  
the gauge assembly.  
7. Reverse procedure to install.  
3. Unscrew the packing nuts at the top and bottom  
of the glass tube.  
8. Adjust the pressure switch(s) final set points as  
outlined under "PRESSURE SWITCHES" in  
"SERVICE PROCEDURES AND  
4. Slide the glass tube upwards until the bottom of  
the tube is clear of the fitting and lift it out.  
ADJUSTMENTS".  
NOTE: Clean tube if dirty or clogged and replace if  
damaged or broken.  
BOILER ASSEMBLY  
NOTE: Do not over tighten the packing nuts or  
gauge glass may break.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
5. Install the tube using new sealing washers.  
6. Open the top and bottom valves.  
7. Turn the power switch ON and allow boiler to  
come up to pressure.  
WARNING: SHUT OFF THE GAS BEFORE  
8. Check gauge glass for water/steam leaks and if  
necessary, gradually tighten packing nuts until  
leak stops.  
SERVICING THE UNIT.  
WARNING: ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
PRESSURE SWITCHES  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1. Blowdown the boiler and, if necessary, allow to  
cool.  
2. Disconnect the steam supply line, power leads  
and drain lines from the cooking compartment  
top to the boiler base.  
1. Open the cabinet base door and remove the  
left side panel.  
3. Refer to "HEAT EXCHANGER" and perform  
steps 3 through 12A.  
2. Remove the cover from the pressure switch  
control box to access the pressure switches.  
Refer to "CABINET BASE BOILER  
CONTROLS" under "COMPONENT  
LOCATIONS" in "REMOVAL AND  
4. Remove bolts securing the boiler to frame.  
5. Drain any remaining water from the boiler.  
A. The suggested methods are:  
REPLACEMENT OF PARTS".  
1) Where the drain line exits the boiler  
on the lower left side, separate the  
drain line union.  
3. The pressure switches are located at the  
bottom of the box. The pressure switch on the  
left is the cycling or primary control; the one on  
the right is the high limit control.  
2) Remove the access panel between  
the boiler and the cooking  
compartment on the right side.  
4. If replacing:  
3) Disconnect the steam supply hose  
from the cooking compartment steam  
manifold.  
A. Cycling control - remove cover from  
pressure switch and disconnect the lead  
wires.  
F24700 (October 2001)  
Page 16 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
a. From the bottom right side, raise  
the boiler two to three inches so  
it tilts to the left. When the  
remaining water has drained out,  
lower the boiler before.  
WARNING:  
ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
proceeding.  
NOTE: Gas combination control valves are not  
serviceable and should not be disassembled. Once  
the problem has been isolated to this component,  
replace it. Do not attempt to repair the assembly.  
B. Remove the drain/scale clean-out plug  
from the bottom of the boiler.  
6. Slide the boiler forward and remove it from  
base frame.  
1. Open the cabinet door to access the Pilot gas  
valve.  
7. Install a new boiler and secure it to frame.  
2. Disconnect the lead wires.  
8. Refer to "HEAT EXCHANGER" and perform  
steps 13 through 15.  
3. Remove pilot gas tubing from the top of the  
valve (outlet side).  
9. Reconnect all steam, water, drain and power  
connections and check for proper operation.  
4. Remove the valve from the gas supply piping.  
5. Reverse procedure to install and adjust pilot  
pressure as outlined under "GAS PILOT  
PRESSURE ADJUSTMENT" in "SERVICE  
PROCEDURES AND ADJUSTMENTS".  
BOILER FILL AND COLD WATER  
CONDENSER SOLENOID VALVES  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
MAIN GAS VALVE  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1. Turn off the water supply to the steamer.  
2. Open the cabinet base door and remove the  
cover from the pressure switch control box to  
access the solenoid valves. Both solenoid  
valves are located side by side at the rear of  
the box with the boiler fill near the bottom and  
the cold water condenser near the middle.  
Refer to "CABINET BASE BOILER  
WARNING: SHUT OFF THE GAS SUPPLY  
BEFORE SERVICING THE UNIT.  
WARNING: ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
CONTROLS" under "COMPONENT  
LOCATIONS" in REMOVAL AND  
REPLACEMENT OF PARTS.  
NOTE: Gas combination control valves are not  
serviceable and should not be disassembled. Once  
the problem has been isolated to this component,  
replace it. Do not attempt to repair the assembly.  
3. Disconnect the power lead wires from the  
solenoid valve being serviced.  
4. Disconnect the water lines for the valve being  
serviced and remove the valve.  
1. Open the cabinet base door to access the main  
gas valve.  
5. Reverse procedure to install.  
2. Disconnect the lead wires.  
PILOT GAS VALVE  
3. Separate the union above the gas valve (outlet  
side).  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
4. Remove the valve from the gas supply piping.  
5. Reverse procedure to install and adjust  
manifold pressure as outlined under "GAS  
MANIFOLD PRESSURE ADJUSTMENT" in  
"SERVICE PROCEDURES AND  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
ADJUSTMENTS".  
Page 17 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
BURNER HEAD ASSEMBLY  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: SHUT OFF THE GAS SUPPLY  
BEFORE SERVICING THE UNIT.  
1. Remove the pressure gauge tubing and power  
cable from the rear of the control panel then  
remove the panel.  
2. Disconnect the spark ignition cable from the  
ignitor terminal.  
3. Disconnect pilot gas tubing from the air  
pressure switch tee.  
3. Remove the four nuts from the burner tube  
assembly then slowly pull the assembly straight  
out from the heat exchanger.  
4. Separate the union above the main gas valve  
and remove the gas valve piping assembly.  
NOTE: Removal of the gas valve piping assembly  
assumes the use of a gas line quick connect or  
union at the gas supply inlet to the steamer.  
5. Remove the screws from the burner head  
assembly end plate and pull the assembly out  
from the complete burner assembly.  
6. Reverse procedure to install and check for  
proper operation.  
COMPLETE BURNER  
ASSEMBLY  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: SHUT OFF THE GAS SUPPLY  
BEFORE SERVICING THE UNIT.  
1. Refer to steps 1 through 4 under "BURNER  
HEAD ASSEMBLY".  
CAUTION: Use care while removing as to not  
damage the ceramic insulation surrounding the  
burner.  
2. Remove the four nuts from combustion blower  
mounting flange and remove blower from  
burner tube assembly.  
4. Reverse procedure to install and check for  
proper operation.  
F24700 (October 2001)  
Page 18 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
NOTE: Removal of the gas valve piping assembly  
assumes the use of a gas line quick connect or  
union at the gas supply inlet to the steamer.  
HEAT EXCHANGER  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
8. Remove the four nuts from combustion blower  
mounting flange and remove blower from  
burner tube assembly.  
WARNING: ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
1. Blowdown the boiler and, if necessary, allow to  
cool.  
2. Disconnect the electrical power to the machine  
at the main circuit box. Place a tag on the  
circuit box indicating the circuit is being  
serviced.  
3. Remove the pressure gauge tubing and power  
cable from the rear of the control panel then  
remove the panel.  
4. Disconnect the electrical lead wires exiting the  
boiler control box from:  
A. Auxiliary LLCO probe (Orange).  
B. Burner ground (green).  
9. Remove the four bolts connecting the  
horizontal flue (left of boiler) to the flue  
"transition" piece.  
C. Air pressure switch (yellow & yellow/white  
stripe).  
D. Main gas valve (purple & grey).  
E. Pilot burner valve (red & grey).  
F. Spark ignition cable.  
5. Remove bolts securing the boiler control box  
(front) to the base frame.  
A. Lift up on left side of box and slide out.  
6. Disconnect pilot gas tubing from the air  
pressure switch tee.  
A. Separate the horizontal flue from flue  
"transition" piece, leaving the horizontal  
flue in place.  
10. Remove the four nuts from the complete  
burner tube assembly then slowly pull the  
assembly straight out from the heat exchanger.  
CAUTION: Use care while removing as to not  
damage the ceramic insulation surrounding the  
burner.  
11. Remove the flue "transition" piece from the  
heat exchanger.  
7. Separate the union above the main gas valve  
and remove the gas valve piping assembly.  
Page 19 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
12. For clearance of the heat exchanger only,  
13. To install heat exchanger:  
remove the drain nut (petcock) and the lower  
adjustment knob from the water level gauge.  
A. Clean the mating surfaces on the heat  
exchanger and boiler.  
A. Remove the remaining bolts on the heat  
exchanger then pull heat exchanger  
straight out from the boiler.  
B. Install a new gasket on the boiler side of  
the mounting flange.  
C. Insert the heat exchanger back into the  
boiler and line up the mounting holes  
being careful not to disturb gasket.  
D. Attach a 2" C-Clamp between the heat  
exchanger mounting flange and the boiler  
side mounting flange. Tighten clamp only  
enough to allow starting of bottom bolt into  
mounting hole.  
F24700 (October 2001)  
Page 20 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
NOTE: It may be necessary to use two clamps  
to draw the bottom of the heat exchanger close  
enough to be clamped. Start one clamp at a 3  
oclock position then install other clamp near  
the bottom. Once the bolts are tight enough, C-  
Clamp will fall away.  
E. Install two bolts at the bottom and two  
bolts at the top on the heat exchanger  
flange and tighten the bolts a few turns at  
a time. Starting with the bottom bolts,  
tighten the bolts in an alternating pattern  
between the bottom and top for a flush  
mounting of the heat exchanger flange  
and an even compression of the gasket.  
NOTE: If a bolt is not threading in properly by  
hand, clean out the threads with the proper size  
tap.  
F. Once those bolts are tight, install the two  
bolts to the left and the two bolts to the  
right on the heat exchanger flange. On the  
left side, be sure to install the rectangular  
flue gas plate then tighten the bolts in an  
alternating pattern.  
15. Starting at step 12, reverse procedure to install  
the remaining components.  
16. Check for water leaks and proper operation.  
COOKING COMPARTMENT  
DOOR(S)  
Removal  
1. Remove top cover.  
2. Open the door.  
3. Pull hinge rod up.  
4. Reverse the procedure to install, making sure  
the door bushings are in place.  
Gasket  
1. Open the door.  
2. Remove screws from the gasket plate.  
3. Pull the gasket plate out from the door housing  
and remove the gasket.  
4. Position the new gasket on the gasket plate  
and reverse the procedure to install. Adjust the  
door as outlined in "DOOR SEALING  
ADJUSTMENT" under "COOKING  
COMPARTMENT".  
14. To install flue "transition" piece:  
A. Clean the mating surfaces on the  
"transition" piece and the heat exchanger  
face.  
B. Install new gasket on the "transition" piece  
then secure to the heat exchanger using  
the remaining bolts.  
NOTE: Do not over tighten gasket plate screws as  
this will compress the gasket excessively and  
interfere with proper door sealing.  
NOTE: Damage to the gasket sealing surface, such  
as nicks or cuts, will cause steam leakage.  
Page 21 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
NOTE: When installing the spacers, the smaller  
diameter fits into the slot in the door and the latch  
lever must rest on top of the handle latch screw.  
5. Reverse procedure to install.  
Latch Assembly  
Handle  
1. Open the door.  
1. Open the door.  
2. Remove screws from the top and bottom of the  
door.  
2. Remove screws from the top and bottom of the  
door.  
3. Pull the inner door panel out from the door  
housing with the gasket plate and gasket still  
attached.  
3. Pull the inner door panel out from the door  
housing with the gasket plate and gasket still  
attached.  
4. Remove the screws from the side edge of the  
door that secure the latch mechanism and  
remove the latch from the door.  
NOTE: When installing, the latch lever must rest on  
top of the handle latch screw.  
5. Reverse procedure to install.  
4. Remove the nuts and spacers from the handle  
screws and remove the handle from the door.  
F24700 (October 2001)  
Page 22 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
SERVICE PROCEDURES AND ADJUSTMENTS  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRES ELECTRICAL TEST OR  
MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL  
TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST  
EQUIPMENT AND REAPPLY POWER TO TEST.  
A. Remove the strainer clean out plug, turn  
BOILER  
the steamer on and allow the boiler "fill  
water" to flush-out the drain line. Turn the  
steamer off, remove the cap and strainer  
screen and clean, if necessary, before  
replacing the screen and clean-out plug.  
Inspection  
It is recommended the boiler be inspected for  
excessive lime scale build up in a time frame  
dependant on the quality of the local water supply  
and steamer usage. In hard water areas or for  
steamers heavily used, a frequent interval should be  
used. This inspection consists of an internal  
examination and cleaning of the boiler, an  
examination of the two hanging descalers, and for  
lime build up on the water level probes. Also, a  
check of all boiler controls, including the pressure  
switches.  
7. Inspect condition of the descalers as outlined  
under "DESCALER (Cathodic Protector)" in this  
section, and replace if necessary.  
8. Install a new gasket and replace the burner  
assembly and heat exchanger by reversing the  
removal procedure from step 2.  
9. Delime the boiler as outlined under  
"DELIMING" in this section.  
Deliming  
Periodic service must be performed as outlined in  
these procedures. See WATER CONDITIONING”  
under GENERAL.  
Boiler deliming should be performed in a time frame  
dependant on the quality of the local water supply  
and steamer usage. In hard water areas or for  
steamers heavily used, a frequent interval should be  
used. See WATER CONDITIONINGunder  
GENERAL.  
Clean-Out  
1. Turn power switch OFF.  
A. Boiler should automatically start  
blowdown/drain cycle.  
On steamers using a water treatment system, follow  
the instructions for that system to delime the boiler.  
Only use the type of chemical recommended or  
described in the instructions for deliming with this  
type of system.  
2. Remove the burner assembly and heat  
exchanger as outlined under "HEAT  
EXCHANGER" in "REMOVAL AND  
REPLACEMENT OF PARTS".  
If a water treatment system is not used, follow the  
instructions for deliming the boiler as outlined in the  
steps below.  
NOTE: Access to the interior of the boiler through  
the hand hole cover is very limited on this model  
and is recommended to be removed for deliming  
purposes only.  
1. Turn power switch OFF.  
3. Remove old descalers (cathodic protectors).  
4. With a wire brush or equivalent:  
A. Boiler should automatically start  
blowdown/drain cycle.  
2. Remove hand hole plate and gasket (top front)  
from the boiler by removing the nut and clamp,  
then tap the cover lightly to free it. Hold the  
stud in the plate while tapping to prevent the  
plate from dropping into boiler.  
A. Dislodge and remove all loose scale from  
boiler shell. The loose material must be  
scooped from the boiler or flushed through  
the washout drain.  
B. Remove all loose scale form the heat  
exchanger.  
3. Clean the mating surfaces of the hand hole  
opening and plate.  
C. Clean the mating surfaces of the heat  
exchanger and boiler.  
4. Delime the boiler:  
A. If the boiler was delimed through a water  
treatment system, proceed to step 7.  
5. Check probe housing and water level probes  
for scale build up and clean as necessary.  
Refer to "WATER LEVEL CONTROLS TEST".  
B. If the boiler has not been delimed,  
proceed to step 5.  
6. Check the drain line exiting the boiler for  
obstructions.  
Page 23 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
WARNING: READ AND FOLLOW THE  
INSTRUCTIONS FOR THE DE-LIMING CHEMICAL  
BEING USED. USE PLASTIC OR RUBBER  
GLOVES TO AVOID SKIN CONTACT. IF THE  
CHEMICAL COMES IN CONTACT WITH SKIN,  
RINSE WITH CLEAN WATER.  
5. Mix deliming solution according to the  
instructions for the chemical being used.  
NOTE: Boiler water capacity is approximately seven  
gallons.  
NOTE: If deliming solution comes in contact with  
steamer components, lightly rinse off with clean  
water.  
A. Turn OFF water supply.  
B. Turn power switch ON to close the drain  
valve.  
C. Pour deliming solution into the boiler shell.  
The descaler materials serve as a sacrificial  
"Anode" and "Cathode" combination that chemically  
reacts with the contents of the boiler to meet the  
three objectives outlined above.  
6. Install a new gasket on the hand hole plate then  
position and tighten the plate to the boiler.  
7. Ensure cooking compartment timers are OFF.  
If the coiled wire has eroded away or if the  
cylindrical core of the descaler has eroded away to  
approximately half its original diameter, a new  
descaler should be installed. The size of a new  
descaler is approximately: 1 3/8" diameter and 3  
3/4" long at the core.  
8. Turn power switch ON and open water supply  
valve.  
9. Allow the boiler to reach operating pressure  
and run for 90 minutes or per the instructions  
for the deliming chemical in use.  
NOTE: While the diameter of the descaler  
decreases through erosion, the length of the  
descaler will increase. If the descaler has increased  
to a length that is touching the bottom of the boiler  
shell, the descaler should be replaced.  
A. Turn power switch OFF and allow the  
boiler to completely drain.  
B. Turn power switch ON to refill boiler and  
allow to heat until fully pressurized.  
10. Steps 9A and 9B must be repeated three times  
The descalers are accessible through the "heat  
exchanger" opening in the boiler only. For removal  
of the heat exchanger refer to "HEAT  
EXCHANGER" under "REMOVAL AND  
REPLACEMENT OF PARTS".  
to thoroughly rinse the boiler.  
11. Steamer is now ready for normal operation.  
Descaler (Cathodic Protector)  
Two descalers are installed inside the boiler shell  
and are used to as a preventative measure to:  
To install a new descaler, stretch the coiled wire at  
the top to elongate the wire and form an open loop.  
Hang the descaler on the front horizontal support  
rod so that its core will be completely below the  
minimum water level in the boiler but hanging free.  
The descaler must not contact the boiler shell or the  
heat exchanger casting.  
Reduce scale deposit buildup  
Help remove existing scale deposits  
Inhibit boiler and component corrosion  
The type of descaler used has a coiled wire  
(Cathode) wrapped around a solid cylindrical core  
(Anode) that hangs by an open loop from the front  
horizontal support rod inside the boiler.  
WATER LEVEL PROBE  
HOUSING BLOWDOWN  
The water contained in the probe housing, being  
under pressure, should be "blown through" this  
manual valve and be noticeably visible exhausting  
out the steamer drain. The probe housing blowdown  
should be performed in a time frame dependant on  
the quality of the local water supply and steamer  
usage. In hard water areas or for steamers heavily  
F24700 (October 2001)  
Page 24 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
used, a frequent interval should be used. This  
should be inspected.  
blowdown procedure is essential to proper operation  
and component life by removing sediment and  
scalants that may be lodged in the probe housing.  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
NOTE: Boiler should be within normal operating  
pressures.  
Main Water Level Control  
1. Remove the left side boiler base panel to  
access the ball valve.  
NOTE: The main water level control is a dual  
functioning control that provides for low level cut-off  
protection and differential water level control  
2. Turn the power switch ON and allow the boiler  
to reach operating pressure.  
1. Turn power switch ON and verify:  
WARNING: THE STEAMER AND ITS PARTS ARE  
HOT. USE CARE WHEN OPERATING, CLEANING  
OR SERVICING THE STEAMER. THE BOILER  
CONTAINS LIVE STEAM. STAY CLEAR WHEN  
OPENING THE VALVE.  
A. Low water light is illuminated (front control  
panel).  
B. HL LED is illuminated on the water level  
control board.  
3. Open the ball valve for approximately one  
minute while under pressure to thoroughly flush  
the probes and housing.  
C. Boiler is filling with water.  
1) If boiler isnt filling with water:  
a. Verify 120 Volt AC is being  
applied to the fill valve.  
4. Close the ball valve and replace left side panel.  
5. Press the reset switch (manual) on the boiler  
control panel and allow boiler to reach  
operating pressure.  
b. Verify fill valve isnt clogged.  
c. Verify 120 Volt AC is on main  
water level control board.  
6. Steamer is now ready for use.  
2) If water level control board doesnt  
WATER LEVEL CONTROLS  
TEST  
have 120 Volt AC:  
a. Check its power source at the  
10 pin J3 connector, pin 1  
(white) and pin 2 (black).  
Disconnect the 10-pin J3  
connector from the relay board  
in the main boiler control box.  
The procedure below applies to the water level  
control boards for both the old and new style boiler  
controls. For additional information related to the  
new style controls, refer to "RELAY BOARD" and  
"SEQUENCE OF OPERATION" under  
"ELECTRICAL OPERATION". For specific  
information related to the water level controls  
operation, refer to "WATER LEVEL CONTROLS"  
under "ELECTRICAL OPERATION".  
b. If no voltage is measured on J3  
pins 1and 2, check the F1 fuse  
(resettable circuit breaker) in the  
main control box, and the power  
switch connections in the power  
switch box.  
Loose electrical connections may prevent the  
steamer from operating properly.  
c. If 120 volt AC was measured on  
J3 connector pins 1 and 2 but  
not on the water level control  
board, verify wire connections.  
There should be continuity  
An accumulation of lime scale on or near the water  
level sensing probes may cause them to retain  
water (moist) on the probe surface and give a false  
reading. Also, a cracked or damaged insulator may  
give a false reading.  
between L1 on the water level  
control board and J3 pin 7.  
There should also be continuity  
between L2 on the water level  
control board and J3 pin 6. This  
path includes connections thru  
the J1 connector.  
These conditions may cause one or more of the  
following to occur:  
Gas burner no ignition  
Boiler no fill  
2. At the end of the initial fill:  
Boiler overfill.  
A. Verify approximately one inch of water  
visible in the boiler sight glass.  
Boiler no fill and dry fire  
NOTE: Dry firing may cause damage to the heat  
exchanger, burner assembly or the boiler. If this  
condition is suspect, the affected components  
B. Verify "green" ready light in the reset  
switch is illuminated.  
Page 25 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
C. Verify LEDs on the water level control C. Repeat at least twice to verify correct  
board, HL LED should be off, and LLCO LLCO operation.  
LED should be illuminated.  
Auxiliary Low level Cut-Off Control  
3. Open the ball valve in the probe housing  
assembly (boiler left side) about half way, to  
gradually remove boiler water and activate a fill  
cycle. Do not press the reset switch to start  
the ignition cycle. The next step requires a  
visual sight glass measurement that cannot be  
obtained, if there is boiling action in the vessel.  
5. Continued testing with focus on the auxiliary  
LLCO circuit. With water below the lowest  
visible level in the sight glass (below Aux LLCO  
probe), and boiler in state of initial fill:  
A. Verify Aux LLCO LED is off on the Aux  
water level control board.  
B. Verify Low Water light is illuminated (front  
control panel).  
A. Verify water level in the boiler sight glass  
drops 1/4" to 3/8" before a fill cycle is  
initiated. Repeat at least twice to verify  
correct fill.  
C. Verify 24 volt AC is on Aux LLCO COM,  
and 0 volt is on Aux LLCO N.O. contacts.  
1) If proper fill wasnt obtained:  
1) With the water level above the Aux  
LLCO probe and in the initial fill state:  
a. Verify probes 50, 51, and 52  
have the correct colored wire to  
them and to the water level  
control board.  
a. Verify Aux LLCO LED is  
illuminated on the auxiliary low  
water board.  
b. Remove the 3 probe assembly,  
clean lime scale build-up from  
the probes and compare probe  
lengths to drawing.  
b. Verify N2 on the relay board is  
illuminated (new style boiler  
controls only).  
c. Verify the "green" ready light in  
the reset switch is illuminated.  
d. Verify 24 volt AC is on the Aux  
LLCO common and normally  
open contacts of the auxiliary  
water level control board.  
2) With the main gas valve turned off,  
water supply valve turned off, and  
probe housing assembly ball valve  
opened, press the reset switch.  
c. Remove 3/8flex line from the  
probe housing assembly to the  
boiler and remove any  
a. Verify low water light (front  
control panel).  
b. Blower comes on.  
obstructions. The 1/4"  
compression fitting elbow and  
1/4" tee into the boiler shell for  
the balance tube are sloped 1/8"  
so condensation drains into  
boiler. When replacing, the  
assembly must have this slope  
to prevent a blockage from  
condensate build-up.  
c. Gas pilot cycles at  
approximately 15 seconds on  
and 5 seconds off.  
3) Shortly after water level drops below  
the lowest visible level in the sight  
glass, the Aux LLCO circuit should be  
activated.  
a. Low water light turns on.  
b. Aux LLCO led turns off.  
4. Test the water level control board LLCO circuit.  
A. With the boiler full with water, turn off the  
water supply and open the ball valve in the  
probe housing assembly.  
c. Combustion blower is de-  
energized.  
B. Shortly after the water drops below the  
lowest visible level in the sight glass, the  
LLCO LED on the water level control  
board should turn off, LLCO relay should  
de-energize and the normally open  
d. Gas pilot stops cycling.  
4) Press reset switch to verify lockout.  
5) Disconnect lead wire from Aux LLCO  
probe. If there is any measurable  
contacts should return there shelf state.  
resistance between the probe and the  
F24700 (October 2001)  
Page 26 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
boiler shell, remove and clean the  
Aux LLCO probe.  
4. The cycling pressure switch will maintain the  
steam pressure setting in the boiler by cycling  
the main burner ON and OFF.  
a. Replace the probe and check  
resistance again. If resistance is  
still present, install a new probe.  
High Limit  
Adjusting the High Limit pressure switch from a cold  
startup is the preferred condition of the boiler. On  
the initial cold startup, the highest overshoot  
pressure (drift) is achieved after the burner cycles  
OFF for the first time. If the boiler is already  
operating, the pressure setting can still be made  
after following the procedures outlined below.  
b. Replace lead wire on probe and  
repeat steps "2) thru 4)" to verify  
proper operation.  
PRESSURE SWITCHES  
1. The high limit pressure switch should be  
adjusted to allow a maximum pressure in the  
boiler of 14.5 to 15.0 PSI. Before making  
adjustments to the high limit pressure setting,  
the 13 PSI pressure relief valve (PRV- left side)  
must be temporarily disabled. This will allow a  
high enough pressure in the boiler to properly  
set the switch.  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
Remove the cover from the pressure switch control  
box to access the two pressure switches. The  
pressure switch near the front is the cycling pressure  
switch and the one beside it is the high limit  
pressure switch.  
A. The suggested methods to prevent the  
valve from releasing pressure are:  
Cycling  
1) Use a wooden block, a hand tool or  
other object to hold the valve plunger  
down.  
1. If the boiler is already operating, proceed to  
step 2. If the boiler is not already operating,  
start the boiler as outlined under "CABINET  
BASE BOILER" in "STEAMER OPERATION".  
2) Use a metal wire threaded through  
the hole in the valve handle and tie  
the pressure relief valve handle to the  
piping below it.  
2. Turn one of the cooking compartment timers  
ON to exhaust steam from the boiler.  
3. Monitor the boiler pressure gauge for several  
cycles and note the pressures at which the  
burner comes ON and goes OFF.  
3) If neither of the two methods keep the  
valve fully closed without leaks, an  
alternate method is:  
A. The main burner should come ON at 8 PSI  
and go OFF at 10 PSI. If the readings  
differ, adjust the pressure settings as  
described below.  
a. Turn the power switch OFF and  
allow the boiler to blowdown.  
b. Remove the discharge piping  
from the valve outlet and insert a  
pipe plug for temporary use  
only.  
1) Two pressure adjustment screws  
extend through the top of the switch  
case. The screw directly above the  
right side pointer raises or lowers both  
the cut-out (OFF) and the cut-in (ON)  
set points simultaneously, without  
affecting the differential.  
2. Turn the power switch ON and allow the boiler  
to completely fill.  
A. High Pressure and Low Water indicator  
lights (amber) come ON.  
The screw directly above the left side  
pointer raises or lowers the cut-in  
(ON) set point and changes the  
differential.  
3. When water in the boiler reaches the minimum  
level, the green light on the reset switch will  
come ON.  
A. Press the reset switch on the front control  
panel to reset the High Pressure and Low  
Water safety controls.  
2) Turn the adjustment screw above the  
right side pointer to obtain the proper  
cut-out (OFF) setting first, then adjust  
the other screw to obtain the proper  
cut-in (ON) setting.  
1) Ignition sequence starts, main burner  
lights and water in the boiler begins to  
heat.  
a. A clockwise rotation increases  
the pressure setting while a  
counterclockwise rotation  
4. Monitor the boiler pressure gauge and note the  
pressure at which the high limit switch opens.  
decreases the pressure setting.  
NOTE: In front of the boiler there is an additional  
Page 27 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
Mechanical Pressure relief valve factory set to  
approximately 15 PSI. If the pressure in the boiler  
reaches this level, the valve will OPEN.  
FILL AND COLD WATER  
SOLENOID VALVES  
A. High pressure light (amber) will come ON.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1) If the pressure switch opens at a  
pressure range other than 14.5 to  
15.0 PSI then an adjustment to the  
switch setting should be made.  
a. Proceed to step 5.  
1. Check to ensure the solenoid valve is receiving  
power.  
CAUTION: While making the adjustment, do not  
press on the wheel with extreme force. The  
switch may rotate and develop a leak at the  
compression fittings or in some cases, the rear  
lead wire may touch the control box and create  
an electrical short.  
A. If the solenoid valve is receiving power but  
the valve is not opening, the coil may be  
malfunctioning.  
1) Remove the lead wires from the  
solenoid coil and check for continuity.  
5. Turn the adjustment wheel several clicks to  
change the pressure switch set point.  
a. If continuity is measured,  
proceed to step "1. B.".  
A. A counterclockwise rotation lowers the  
pressure switch set point while a  
clockwise rotation raises the pressure  
switch set point.  
b. If no continuity is measured,  
replace the solenoid valve and  
check for proper operation.  
B. If the solenoid valve is receiving power  
and the valve appears to be opening but  
little or no water is flowing through it, then  
the valve ports may be clogged with debris  
or a valve component malfunctioning.  
NOTE: For every click of the adjustment wheel  
during rotation, the pressure setting is changed  
approximately 1/8 PSI. Make the adjustment  
in small increments.  
6. Raise the handle on the 15 PSI mechanical  
pressure relief valve and open the valve for  
approximately 4 minutes. This will exhaust  
steam down the drain line and lower the boiler  
pressure.  
2. To check solenoid valve further, proceed to  
step 3 through 8 for disassembly and inspection  
of internal components.  
3. Shut water supply off, disconnect the water line  
from the valve body then remove the solenoid  
valve from the steamer.  
A. High limit pressure switch closes at  
approximately 12 PSI (non-adjustable).  
4. Remove the coil assembly from the valve stem  
by lifting up on the retaining cap at the top of  
the solenoid valve and sliding the metal cover  
plate off.  
1) Press the reset switch to reset the  
High Pressure safety control.  
a. High pressure light (amber) goes  
out.  
5. Clamp the body of the valve in a vise.  
B. Lower the boiler pressure to approximately  
8 PSI.  
6. Mark a scribe line on the stem nut to the valve  
body for proper re-tightening.  
C. Ignition sequence starts, main burner  
lights and water in the boiler begins to  
heat.  
7. Remove the stem locking nut to remove the  
stem from the valve body.  
8. All parts are now accessible for inspection and  
cleaning.  
7. Repeat steps 4 through 6 until the High Limit  
Pressure Switch opens at the correct pressure.  
NOTE: If internal solenoid parts appear to be  
damaged or worn, then replace the solenoid valve.  
Do not reuse damaged or worn parts. No internal  
solenoid parts are available as a service  
replacement.  
8. If the 13 PSI pressure relief valve (PRV- left  
side) was temporarily disabled as outlined in  
step 1:  
A. Turn the power switch OFF and allow the  
boiler to blowdown.  
A. Check rubber seal on bottom of plunger.  
B. Check plunger spring.  
B. Return the valve to its original state.  
9. Check steamer for proper operation.  
C. Check O-ring in valve body.  
F24700 (October 2001)  
Page 28 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
D. Check ports in valve body. A. If the boiler blowdown is ok, then the drain  
line and valve are clear of debris and the  
valve is functioning properly.  
B. If considerable lime scale debris is  
apparent, then not only the blowdown  
valve, but also the boiler and water level  
probes must be thoroughly cleaned. See  
"FILL AND COLD WATER SOLENOID  
VALVES" for an inspection and cleaning  
procedure of a solenoid valve and  
"BOILER" for a procedure on boiler  
inspection, clean-out and deliming.  
INLINE WATER STRAINER  
CLEANING  
9. Reverse procedure to install.  
BOILER BLOWDOWN/DRAIN  
SOLENOID VALVE  
The procedure outlined below can be used to  
inspect and clean the inline water strainer for the  
blowdown solenoid valve and, if installed, the inline  
water strainer for the boiler fill solenoid valve. Inline  
Y strainers should always be located upstream of a  
water solenoid valve.  
The water contained in the boiler, being under  
pressure, should be "blown through" this valve and  
be noticeably visible exhausting out the steamer  
drain. Daily boiler blowdown is essential to proper  
operation and component life by removing sediment  
and scalants that may be lodged in the chamber of  
the boiler.  
NOTE: For proper operation, the strainer must be  
installed so the water flow is directed towards the  
solenoid valve and the leg of the Y with a threaded  
cap is pointing downwards to catch debris.  
The boiler blowdown/drain process is an automatic  
function and should start whenever the power switch  
is turned OFF after a normal operating cycle. The  
blowdown solenoid is a normally open (N.O.) valve  
that CLOSES when energized by the power switch.  
When the power switch is turned OFF, the  
1. Turn the power switch OFF to and allow the  
boiler to blowdown.  
2. When blowdown completes, shut OFF the  
water supply.  
blowdown solenoid is de-energized and the valve  
OPENS to allow the boiler to blowdown.  
3. Remove the cap and strainer screen from the  
leg of the Y pointing downwards toward the  
floor.  
If the blowdown operation appears to function  
sluggishly or not at all, considerable scalants may  
be lodged in the drain line plumbing exiting the  
boiler, strainer, and/or the blowdown valve.  
4. Remove the screen from the cap and clean any  
accumulated debris from the screen and also  
remove any debris trapped in the opening of  
the strainer body.  
1. Turn the power switch OFF and allow boiler to  
blowdown.  
NOTE: If screen can not be thoroughly cleaned,  
2. Turn the ON/OFF knob on the main gas valve  
to OFF.  
replace it with a new one.  
5. Insert screen into cap then re-install cap to  
strainer body.  
3. Remove the strainer clean-out plug located in  
the center of cap.  
6. Turn the water supply and power switch ON  
and allow the boiler to reach operating  
pressure.  
4. Turn the power switch ON and allow the boiler  
"fill water" to flush-out the drain line until no  
debris is seen exiting the clean-out hole.  
7. Turn the power switch OFF and check strainer  
for leaks, as the boiler blows down.  
5. Turn the power switch and the water supply  
OFF.  
6. Turn the ON/OFF knob on the main gas valve  
back to ON.  
7. Remove and clean the strainer as outlined  
under "INLINE WATER STRAINER  
CLEANING".  
Page 29 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
A. N13 on relay board ON (air pressure  
MAIN BURNER IGNITION  
CHECKS  
switch CLOSED and condition satisfied).  
B. Pilot gas valve energized and ignition  
sequence starts.  
The complete gas burner assembly is located inside  
the heat exchanger casting in the boiler. The  
perforated burner head functions as both pilot and  
main gas burner. The inner portion of the perforated  
burner head serves as the pilot to light the main  
burner during the trial for ignition. Once the main  
burner lights, the flame encompasses the entire  
perforated burner head and the pilot flame  
extinguishes.  
NOTE: If N13 is not ON or Pilot gas valve is  
not energized, then check the air pressure  
switch setting as outlined under "AIR  
PRESSURE SWITCH ADJUSTMENT".  
5. Verify 24VAC to ignition module and pilot  
valve.  
A. N1 on relay board ON (24VAC is being  
supplied for the system).  
If burner ignition problems are encountered, perform  
the following checks to ensure components are  
adjusted properly.  
B. N13 on relay board ON (24VAC is being  
supplied to the ignition module).  
C. N14 & N15 on relay board ON (24VAC is  
being supplied to the pilot ignition timing  
circuit and the pilot valve.  
1. Turn power switch ON and allow the boiler to  
fill.  
2. Verify "low water" and "high pressure" safety  
circuits are satisfied.  
6. Verify spark and pilot ignition.  
A. If pilot lights, proceed to step 7.  
A. Water Level in boiler.  
B. If sparking occurs but pilot does not light,  
then check the pilot pressure setting as  
outlined under "GAS PILOT PRESSURE  
ADJUSTMENT".  
1) Approximately one visible inch of  
water in the sight glass.  
2) Auxiliary LLCO is satisfied.  
a. N2 on relay board ON (low water  
C. If spark is not occurring:  
safety circuit satisfied).  
1) Restart power ON sequence by  
"rapidly" turning the power switch  
OFF then back ON. A rapid switching  
is needed to keep the boiler from  
starting automatic blowdown.  
b. LED on auxiliary water level  
board ON.  
B. High Limit Pressure Switch  
1) Zero reading on boiler pressure  
gauge.  
2) Remove ignition cable boot from the  
ignitor rod terminal and check ignitor  
position in the burner head assembly.  
NOTE: Burner cycles ON at less than or  
equal to 8 PSI and OFF at 10 PSI.  
3) Measure distance the ignitor terminal  
extends past the ignitor nut. Distance  
should measure approximately 3/4" to  
7/8". See diagram 5898 "COMPLETE  
BURNER ASSEMBLY" at the end of  
this procedure.  
NOTE: High Limit Pressure Switch  
automatically resets at approximately 12  
PSI.  
C. Press the reset switch to reset the safety  
circuits.  
NOTE: Touch ignitor terminal only  
and not the ceramic insulator.  
NOTE: Hi Pressure and low water lights on  
front control panel should be OFF.  
a. If distance is ok, proceed to step  
5) below and perform step "a"  
and "b" then continue with step  
"6)".  
1) N3 on relay board ON (high pressure  
safety circuit satisfied).  
3. Verify blower is running and its operation is  
quiet.  
b. If distance is other than stated,  
loosen ignitor nut, set the ignitor  
position and then re-tighten the  
ignitor nut.  
NOTE: A "noisy" blower rotation may  
indicate bearing wear and reduce air  
pressure output.  
c. Re-connect ignition cable.  
A. N12 on relay board ON (120VAC supplied  
to the blower).  
4) Press reset switch to start the ignition  
process.  
4. Verify air pressure switch is CLOSED.  
F24700 (October 2001)  
Page 30 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
a. If ignitor sparks and pilot lights,  
proceed to step 7.  
Verify the burner tube insulation and  
heat exchanger casting are intact.  
b. If ignitor does not spark, proceed  
to step "5)" below.  
NOTE: The suggested method for  
inspection is to mount a small mirror  
to a 2 foot long rod and insert the  
mirror inside the burner tube and use  
a flashlight to illuminate the area.  
5) Restart power ON sequence by  
"rapidly" turning the power switch  
OFF then back ON. A rapid switching  
is needed to keep the boiler from  
starting automatic blowdown.  
NOTE: If necessary, the complete  
burner tube assembly can be  
removed to aid in performing the  
measurement and inspections.  
a. Grasp the ignitor terminal and  
rotate the ignitor approximately  
45°.  
a. Inspect the ceramic insulation for  
damage at the area around the  
burner head inside the burner  
tube.  
b. Re-connect ignition cable.  
6) Press the reset switch to start the  
ignition process.  
b. Measure ceramic insulation  
insertion depth/location from the  
end of the insulation that  
a. If ignitor sparks and pilot lights,  
proceed to step 7.  
surrounds the burner head to the  
opposite end of the burner tube  
(end plate mounting flange). The  
dimension should measure  
approximately 23 5/8 inches  
±1/8. See diagram 5898  
"COMPLETE BURNER  
ASSEMBLY" at the end of this  
procedure.  
b. If ignitor does not spark, repeat  
steps "5)" through this step until  
rod has been rotated 360°.  
7. Verify main burner ignition.  
A. If main burner lights and remains lit with  
no intermittent problems, then burner is  
functioning properly.  
B. If main burner does not light or shows  
intermittent problems, then check the main  
burner pressure setting as outlined under  
"GAS MANIFOLD PRESSURE  
c. Verify that casting debris is not  
clogging the "heat transfer fins"  
at the end of heat exchanger  
casting and that the fins have  
not eroded away.  
ADJUSTMENT".  
1) If pressure is ok but intermittent  
burner problems continue, then the  
following components must be  
examined.  
d. Inspect the interior of heat  
exchanger casting for signs of  
water leakage. Also, signs of  
water leakage into the heat  
exchanger casting may be  
determined by examining the  
bottom area of the flue transition  
piece and floor.  
2) Turn the power switch OFF and allow  
the boiler to blowdown.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
3) Remove burner head assembly as  
outlined under "BURNER HEAD  
ASSEMBLY" in "REMOVAL AND  
REPLACEMENT OF PARTS".  
4) The complete or intermittent loss of  
burner ignition or a burner operation  
that is loud and noisy may indicate  
the burner tube insulation or heat  
exchanger casting is damaged.  
Page 31 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
F24700 (October 2001)  
Page 32 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
AIR PRESSURE SWITCH  
ADJUSTMENT  
The air pressure switch senses the pressure level  
produced by the blower for combustion. When the  
pressure is sufficient, the switch closes and supplies  
power to the ignition control module. The gas  
ignition sequence starts to light the gas pilot and  
then main burner. If the gas pilot is not lighting  
(valve not energized), the ignition control module  
may not be receiving power, assuming the minimum  
water level is satisfied. Check the air pressure  
switch operation then adjust if necessary as outlined  
in the procedure below.  
1. Turn the power switch OFF.  
2. Remove the left side panel from the cabinet  
base.  
A. Inspect the air intake to the blower for  
debris build up and clogging.  
A. Turn the adjustment screw fully clockwise  
to the highest setting.  
B. Slowly turn the adjustment screw  
counterclockwise until the pilot gas valve  
energizes then add ½ turn to the  
adjustment.  
NOTE: The screw head should not extend out  
past the screw housing.  
1) If Pilot gas valve energizes, proceed  
to step 5.  
2) If Pilot gas valve does not energize,  
check the following:  
a. Remove the lead wires from the  
switch and verify with a meter  
that the switch contacts are  
closing with the blower ON. If  
necessary, continue to turn the  
adjustment screw several turns  
counterclockwise to CLOSE the  
switch contacts.  
1) If debris is found, clean it away from  
the air intake.  
B. Turn the power switch ON and verify main  
burner ignition.  
b. If the switch contacts are not  
closing, turn the power switch  
OFF, remove the pressure  
1) If burner ignites then no adjustment to  
the pressure switch setting is  
necessary.  
switch from the TEE and check  
the air orifice for debris build up  
and clogging. If debris is found,  
clean it away from the orifice.  
2) If burner does not ignite, proceed to  
step 3.  
3. Open the cabinet base door and turn the  
ON/OFF knob for the main gas valve to OFF.  
4. Adjust the air pressure switch setting as  
follows:  
Page 33 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
2) Press the reset switch to start the  
ignition process.  
C. Listen for main gas burner ignition to  
verify operation.  
GAS PILOT PRESSURE  
ADJUSTMENT  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
1. Open the cabinet base door to access pilot gas  
valve.  
2. Remove the pilot pressure plug tap from the  
outlet side of valve.  
c. Replace the orifice, pressure  
switch and connect the lead  
wires to the switch. Turn the  
power switch ON and adjust the  
pressure switch again as outlined  
in steps 4A and 4B. Verify the  
pilot gas valve is energizing.  
d. If the pilot gas valve is not  
energizing and power is  
available to the pressure switch,  
turn the power switch OFF.  
Replace with a new air pressure  
switch and adjust the switch as  
outlined from step 3 thru the end  
of this procedure.  
5. Restart the ignition sequence by "rapidly"  
turning the power switch OFF then back ON. A  
rapid switching is needed to keep the boiler  
from starting automatic blowdown.  
A. Press the reset switch to start the ignition  
process.  
1) Listen for gas pilot ignition to verify  
operation.  
a. If gas pilot ignition is successful,  
turn the ON/OFF knob for the  
main gas valve back to ON.  
A. Install a hose barb adaptor and attach a  
gas pressure manometer.  
3. Turn the gas supply and power switch ON.  
b. Listen for main gas burner  
ignition to verify operation.  
A. Once the boiler fills, press the reset switch  
to start the ignition process.  
B. Verify the pilot and main burner both ignite  
in succession.  
NOTE: The reset switch can be pressed after  
the green ready light on the switch comes ON.  
This indicates the water level in the boiler is at  
the minimum operating level.  
1) Restart the ignition sequence by  
"rapidly" turning the power switch  
OFF then back ON. A rapid switching  
is needed to keep the boiler from  
starting automatic blowdown.  
F24700 (October 2001)  
Page 34 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
4. After the main burner lights, allow the boiler to  
reach operating pressure then turn the ON/OFF  
knob for the main gas valve to OFF.  
5. Restart the ignition sequence by "rapidly"  
turning the power switch OFF then back ON. A  
rapid switching is needed to keep the boiler  
from starting automatic blowdown.  
8. With the burner lit, set the pressure as outlined  
below.  
A. To increase pressure, turn the screw  
clockwise.  
A. Press the reset switch to start the ignition  
process.  
B. To decrease pressure, turn the screw  
counterclockwise.  
6. After the pilot burner lights, compare the  
manometer pressure reading to the pressure  
chart near the end of this procedure.  
NOTE: Accurate gas pressure adjustments can only  
be made with the gas ON and the burner lit.  
NOTE: The pilot gas valve operates on a time delay  
circuit and will only be energized for approximately  
15 seconds to light the main burner then shut OFF.  
The pilot pressure reading must be taken while the  
pilot valve is energized within this time interval.  
After the main burner ignition time expires, the  
ignition control module will sense there is no flame  
present and will then try to re-establish a flame to  
light the main burner. This cycle will continue to  
repeat until the main gas valve is turned back ON.  
PRESSURE READINGS (INCHES W.C.)  
LINE  
GAS TYPE  
PILOT  
MINIMUM  
RECOMMENDED  
MANIFOLD  
MAX  
Natural  
3.5  
3.5  
7.0  
14.0  
Propane  
11.0  
A. If the pressure is not correct, proceed to  
step 7 to adjust.  
NOTE: If the incoming line pressure is less than the  
minimum recommended, then the manifold pressure  
can not be set correctly.  
B. If the pressure is correct, turn the power  
switch OFF, replace the adjustment screw  
cap and pilot pressure plug tap to the gas  
valve. Turn the knob on the main gas  
valve back to ON.  
9. Once the correct pressure has been set, turn  
the gas supply and power switch OFF. Replace  
the adjustment screw cap and pilot pressure  
plug tap on the valve.  
7. Remove the adjustment screw cap to access  
the pressure adjustment screw.  
10. Turn the knob on the main gas valve to ON,  
the gas supply ON and check for proper  
operation.  
Page 35 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
A. If other appliances are connected to the  
GAS MANIFOLD PRESSURE  
ADJUSTMENT  
same gas line, turn them all ON and check  
manometer pressure reading again. If the  
pressure drops ½ inch water column or  
more, then the gas supply needs to be  
checked by the gas line installer or the  
local gas company for adequate sizing.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
NOTE: The gas supply line to the steamer  
should be a minimum of one inch diameter  
(ID).  
WARNING: SHUT OFF THE GAS SUPPLY  
BEFORE SERVICING THE UNIT.  
B. If the pressure does not drop as described  
above but the manifold pressure still  
1. Open the cabinet base door to access main gas  
valve.  
requires adjustment, proceed to step 5.  
5. Remove the adjustment screw cap to access  
the pressure adjustment screw.  
2. Remove the manifold pressure tap plug from  
the outlet side of valve.  
6. With the burner lit, set the pressure as outlined  
below.  
A. To increase pressure, turn the screw  
clockwise.  
B. To decrease pressure, turn the screw  
counterclockwise.  
NOTE: Accurate gas pressure adjustments can only  
be made with the gas ON and the burner lit.  
A. Install a hose barb adaptor and attach a  
gas pressure manometer.  
PRESSURE READINGS (INCHES W.C.)  
3. Turn the gas supply and power switch ON.  
A. Once the boiler fills, press the reset switch  
to start the ignition process.  
LINE  
GAS TYPE  
BURNER  
MINIMUM  
RECOMMENDED  
MANIFOLD  
MAX  
NOTE: The reset switch can be pressed after  
the green ready light on the switch comes ON.  
This indicates the water level in the boiler is at  
the minimum operating level.  
Natural  
3.0  
3.0  
7.0  
14.0  
Propane  
11.0  
4. After the main burner lights, allow the boiler to  
reach operating pressure then compare the gas  
manometer pressure reading to the pressure  
chart near the end of this procedure.  
NOTE: If the incoming line pressure is less than the  
minimum stated, then the manifold pressure can not  
be set correctly.  
F24700 (October 2001)  
Page 36 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
7. Once the correct pressure has been set, turn  
F. "Rapidly", turn the power switch OFF then  
ON. A rapid switching is needed to keep  
the boiler from starting automatic  
the gas supply and power switch OFF. Replace  
the adjustment screw cap and manifold  
pressure plug tap plug on the valve.  
blowdown. Then press the reset button.  
8. Turn the gas supply on and check for proper  
operation.  
NOTE:  
If the power is not re-set, the ignition  
module continues sparking for a total of 90  
seconds, then locks out. The module remains  
locked out until the power switch is turned to  
OFF then back ON and the reset switch is  
pressed to re-start the ignition trial cycle.  
IGNITION CONTROL MODULE  
CHECKS  
1. Turn the power switch ON and allow the boiler  
to fill.  
2. Aux. water level control satisfied and high limit  
closed.  
3. Press the reset switch.  
A. Combustion blower comes on and  
generates pressure to close the air  
pressure switch contacts.  
B. Ignition control module is energized and  
trial for ignition starts. Check for 24VAC  
between terminals five and six.  
C. Ignition module closes the internal pilot  
valve contacts. Check for 24 volts  
between terminals two and three.  
1) High voltage is sent from terminal  
nine to the spark electrode and  
sparking begins.  
Terminals:  
1. Main Valve - 24VAC will be present on terminal  
#1 with the flame sensing electrode sensing an  
adequate burner fame. This output voltage will  
remain present as long as the burner flame  
remains adequate.  
2) At the same time, pilot timing circuit  
(control board) and pilot valve are  
both energized allowing gas flow to  
the pilot.  
2. MV/PV (common).  
NOTE: The pilot valve will be energized  
by the relay board timer circuit for  
approximately 15 seconds to light the  
main burner.  
3. Pilot Valve - 24VAC will be present on terminal  
#3 at the instant an input voltage is supplied to  
the module. This output voltage will remain  
present on terminal #3 providing an adequate  
pilot flame is established within 90 seconds. In  
the event that an adequate pilot flame is not  
established within 90 seconds this output  
voltage will drop out.  
D. Pilot ignition is established (pilot lit), and  
main gas valve is energized. Check for 24  
volts between terminals one and two.  
1)  
Sparking stops.  
4. Ground (burner).  
5. 24VAC Neutral (ground).  
6. 24VAC Input.  
2) Ignition module monitors main burner  
flame.  
3) After 15 seconds relay board timer  
times out.  
7. High Voltage to spark electrode. Provides high  
output voltage (13kv peak) to the spark  
electrode to light the gas pilot. Once pilot is lit,  
provides a path for flame current sensing by  
the Ignition Module via the spark electrode high  
voltage cable on terminal #9.  
a. Pilot valve de-energized.  
E. As long as the ignition control module is  
sensing a burner flame through the ignition  
cable on terminal nine, the internal main  
voltage (MV) and pilot (PV) contacts  
(N.O.) remain closed.  
NOTE: If pilot flame is not sensed within 15  
seconds, you can re-start the ignition  
sequence.  
Page 37 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
1) If pilot lights, then ignition system is  
Spark Verification Test  
working properly.  
1. Turn the power switch OFF.  
2) If ignitor does not spark, repeat steps  
E thru this step until rod has been  
rotated 360°.  
2. Check to ensure that all electrical terminal  
connections on the ignition control module and  
the ignitor rod are clean and tight. If the ignition  
cable appears to be damaged, replace it and  
re-try lighting burner.  
3) If ignitor still does not spark, proceed  
to step 6.  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
3. Verify that the ignition control module and the  
burner ground have a good ground connection.  
6. Turn the power switch OFF.  
A. If loose connections are found, make the  
necessary adjustments and check for  
proper operation.  
7. Remove the burner head assembly as outlined  
under "BURNER HEAD ASSEMBLY" in  
"REMOVAL AND REPLACEMENT OF PARTS"  
and check the following:  
B. If connections are ok but sparking does  
not occur, proceed to step 4.  
A. The gap between the spark probe and the  
ground pin should be approximately 0.090"  
to 0.100". Adjust as necessary. See  
diagram 5899 "BURNER HEAD  
4. Remove ignition cable boot from the ignitor rod  
terminal and check ignitor position in the burner  
head assembly.  
A. Measure distance ignitor terminal extends  
past ignitor nut, approximately 3/4" to 7/8".  
See diagram 5898 "COMPLETE BURNER  
ASSEMBLY" under "MAIN BURNER  
IGNITION CHECKS.  
ASSEMBLY" under "MAIN BURNER  
IGNITION CHECKS".  
B. Inspect the ceramic flame rod insulator for  
cracks or evidence of exposure to extreme  
heat, which can permit leakage to ground.  
If either of these conditions exist, then  
replace ignitor rod and re-test.  
NOTE: Touch ignitor terminal only and not  
the ceramic insulator.  
1) If distance is ok, proceed to step 5  
and perform steps B thru E.  
1) If replacing ignitor rod, loosen the  
ignitor rod mounting nut and remove  
the ignitor rod from the burner head  
assembly.  
2) If distance is other than stated, loosen  
ignitor nut, set the ignitor position.  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
3) Re-connect ignition cable.  
B. Turn the power switch ON and allow the  
boiler to fill.  
C. Press reset switch to start the ignition  
process.  
8. Verify spark at electrode.  
A. Place the assembly on the floor and attach  
a temporary ground wire from the burner  
ground on the heat exchanger to the  
burner head assembly.  
1) If pilot lights, then ignition system is  
working properly.  
2) If ignitor does not spark, proceed to  
step 5.  
B. Turn the power switch ON and press the  
reset switch.  
5. Turn the power switch OFF.  
C. Observe spark condition from ignitor.  
A. Remove ignition cable boot from the  
ignitor rod terminal.  
1) If a good spark from ignitor is present  
then the ignition system is working  
properly.  
B. Grasp the ignitor terminal and rotate the  
ignitor approximately 45°.  
2) If ignitor is still not sparking, replace  
the ignition control module and repeat  
steps 8A and 8B to check for proper  
operation.  
NOTE: Touch ignitor terminal only and not the  
ceramic insulator.  
C. Re-connect ignition cable.  
D. Turn the power switch ON and allow the  
boiler to fill.  
3) After making the necessary  
component adjustments or  
replacements, re-assemble and  
check for proper operation.  
E. Press reset switch to start the ignition  
process.  
F24700 (October 2001)  
Page 38 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
Door Sealing Adjustment  
COOKING COMPARTMENT  
1. Check the door gasket quality. If damaged or  
worn, replace as outlined in "REMOVAL" under  
"COOKING COMPARTMENT DOOR(S)".  
NOTE: For access to compartment controls,  
remove the right side compartment panel.  
2. Loosen screws until the screw heads no longer  
touch the gasket plate.  
Intake Shut-Off Valve Adjustment (Steam Flow)  
1. With the right side compartment panel  
removed, open the intake shut-off valve  
completely.  
3. Tighten screws until screw head touches gasket  
plate and at that point begin counting turns.  
4. Tighten all screws approximately two turns.  
5. Close the door and check for proper operation.  
2. If the steamer ready light is on, then proceed to  
step 4.  
A. If necessary, tighten all screws an  
additional 1/2 turn and repeat step 5.  
3. If the boiler is off, then turn main power switch  
ON and allow boiler to heat up until steamer  
ready light comes on. Allow boiler to cycle 2 to  
3 times, then proceed to step 4.  
6. Repeat step 5 until the door closes properly  
and no steam leaks are seen around the gasket  
seal.  
4. Turn both cooking timers on.  
5. Monitor the boiler until heat source turns off.  
6. At that time, adjust the intake shut-off valve  
until the manifold pressure gauge reads 9 ±1  
psi. The valve setting should be made while the  
boiler pressure is at the upper cycling limit.  
7. Monitor gauge reading 1 to 2 cycles to ensure  
pressure is set correctly.  
8. Once the valve is set, turn both cooking timers  
off and reinstall right side compartment panel.  
Page 39 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Door Latch Adjustment  
Should the cooker door jam and can not be opened,  
DO NOT FORCE OR PRY the door as damage will  
occur.  
First, try lifting up on the bottom of the door at the  
handle end to disengage the latch. If that does not  
work, remove the right side panel.  
The striker that catches on the door latch is located  
behind the front face of the cooking cavity. Remove  
the nut from the striker and this will release it from  
the panel.  
4. Once the proper slot alignment has been set,  
hold the striker close to its base using a rag and  
vise grips, then tighten the striker nut. Be  
careful not to damage the striker slot when  
tightening or door may not latch properly.  
NOTE: Do not over tighten as the striker will begin  
to turn and change alignment.  
Once the nut and washer have been removed, door  
will open freely.  
Remove any burrs on the striker that may cause the  
latch to stick. Reinstall the striker and adjust, so  
door will not jam.  
To adjust:  
1. Reinstall the striker with the slot pointing  
upwards and hand tighten nut only.  
2. Close the door to center the striker in the oval  
mounting hole.  
3. Open the door and check the strikersslot for  
horizontal alignment. The slot on the striker  
must be kept horizontal in order for the door  
latch to catch it properly and latch.  
F24700 (October 2001)  
Page 40 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
ELECTRICAL OPERATION  
into the boiler.  
WATER LEVEL CONTROLS  
When the water level drops below the low level (LL)  
probe, power is removed from the inverse latching  
relay, the HL relay energizes through ILR-2 and HL  
contacts change state. The fill solenoid is energized  
through HL-3 to refill the boiler and the HL LED is lit.  
The HL relay and LED will toggle ON and OFF  
during a cooking cycle as needed.  
Low Level Cut-Off & Differential Control  
The steamer is equipped with three water level  
sensing probes (high, low and low level cut-off) and  
a single water level control board (solid state). The  
water level control board performs two functions: 1)  
Provide low level cut-off protection to shut off the  
heat source in case the water level drops below the  
low level cut-off (LLCO) probe. 2) Perform as a  
differential level control to maintain the water level  
between the low and high water level probes.  
The water level control (WLC) has input voltage  
(120VAC) across terminals 11 and 12 which powers  
the primary side of the transformer. On one side of  
the transformer secondary, power is provided to the  
control by a series path through chassis ground  
(terminal 10). The other side of the transformer  
secondary (12VAC) is attached to the probe that  
directs power to the other side of board relay coils  
(LLCO and HL) and to the Inverse Latching Relay  
(ILR) electronic circuit on the board. As water enters  
the boiler, it becomes part of the water level  
controls circuit. When the water level in the boiler  
reaches a probe, that circuit is completed.  
The inverse latching relay of the board is de-  
energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.)  
contacts in their shelf state.  
When the main power switch is turned ON, power is  
supplied to the WLC board which energizes the high  
level (HL) relay, closes HL-3 normally open  
contacts, and illuminates the HL relay LED. With the  
HL-3 contacts closed, the boiler fill solenoid is  
energized and water begins filling the boiler.  
When the water level reaches the low level cut-off  
(LLCO) probe, the LLCO relay is energized and  
illuminates the LLCO LED. With the LLCO-2  
contacts closed the heat source is then energized.  
The LLCO relay will remain energized and its LED  
will stay lit until the water level in the boiler drops  
below the LLCO probe. NOTE: Auxiliary control(s)  
in the heating circuit must also be satisfied before  
heating can start.  
When the water level reaches the low level (LL)  
probe, power to terminal 2 on the WLC board is  
present but no switching occurs.  
After the water level reaches the high level (HL)  
probe, the inverse latching relay of the board is  
energized and locked through the low level probe  
(LL) and ILR-1 contacts. With ILR-2 contacts open,  
this de-energizes the HL relay and the HL LED goes  
out. With the HL-3 contacts open, the boiler fill  
solenoid is de-energized, stopping the flow of water  
Page 41 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Auxiliary Low Level Cut-Off  
This control serves as a safety backup to the main  
water level control (WLC) board to meet CSD-1  
code requirements. The operation of the auxiliary  
control is identical to the low level cut-off (LLCO)  
function of the main WLC board but performs a  
single function: 1) Provide auxiliary low level cut-off  
protection to shut off the heat source in case the  
water level drops below the low level cut-off (LLCO)  
probe. A single LLCO probe, identical to the LLCO  
probe on the main WLC board, is connected to the  
auxiliary control.  
The auxiliary water level control (WLC) has input  
voltage (120VAC) across terminals 11 and 12 which  
powers the primary side of the transformer. On one  
side of the transformer secondary, power is  
provided to the control by a series path through  
chassis ground (terminal 10). The other side of the  
transformer secondary (12VAC) is attached to the  
control that directs power to the other side of the  
internal relay (LLCO). As water enters the boiler, it  
becomes part of the auxiliary water level controls  
circuit. When the water level in the boiler reaches  
the LLCO probe, the circuit is completed.  
When the main power switch is turned ON, power is  
supplied to the auxiliary WLC board but no  
switching occurs. Also, the low water level indicator  
light (amber) on the boiler base control panel comes  
on.  
When the water level reaches the low level cut-off  
(LLCO) probe, the LLCO relay is energized (LLCO-2  
close) and the LLCO LED lights up. The LLCO relay  
will remain energized and its LED will stay lit until  
the water level in the boiler drops below the LLCO  
probe.  
When the boiler stops filling, press the manual reset  
switch on the boiler base control panel. This turns  
off the low water light, energizes the combustion  
blower and allows the ignition cycle to begin.  
F24700 (October 2001)  
Page 42 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
RELAY BOARD  
Board Layout and LED Legend  
The relay board Provides a centralized location for wire harness connections and power transfer through board  
relays (K1-K7) to the other steamer controls. Also, provides a condition or component troubleshooting indicator  
by utilizing seventeen LEDS on the board to represent the status of the condition or component in the operating  
sequence. When the condition for the component being monitored is satisfied or activated, an LED will light to  
indicate its proper operation. If the corresponding LED does not light then the condition or component has not  
been satisfied or is not activated.  
LED LEGEND  
LED ON = Condition satisfied or component activated. 1 LED OFF = Condition not satisfied or component de-activated.  
LED  
N1  
DESCRIPTION  
LED  
N10  
DESCRIPTION  
Board powered (24vac).  
Auxiliary water level satisfied (LLCO) and reset switch  
activated.  
N2  
Auxiliary water level satisfied (LLCO).  
N11  
Boiler operating pressure condition satisfied and reset  
switch activated.  
N3  
N4  
N5  
High limit pressure switch closed.  
N12  
N13  
N14  
Combustion blower ON.  
Steamer is ready (ready light "green" is ON).  
Auxiliary water level satisfied (LLCO) and reset switch activated.  
Combustion blower air pressure switch satisfied.  
Ignition module pilot voltage (PV) to board level timing  
circuit.  
N6 1 Low water condition exists (N2 LED ON) or previously existed. If  
water level condition is satisfied and the reset switch is activated  
then N6 LED will turn off.  
N15 2 Pilot voltage (PV) to pilot gas valve.  
N7  
Boiler pressure condition satisfied and reset switch activated.  
N16  
N17  
Ignition module main voltage (MV) to low water level  
contacts (LLCO) on water board.  
N8 1 Boiler High pressure condition exists (N3 LED ON) or previously  
existed. If boiler pressure condition is satisfied and the reset switch  
is activated then N8 led will turn off.  
Low water level satisfied (LLCO) and main voltage (MV)  
from ignition module is supplied to main gas valve.  
N9  
Cycling pressure switch CLOSED call for heat.  
NOTES: 1. At initial power on, N6 & N8 leds will be ON until conditions are satisfied and reset switch is activated.  
NOTE: 2. Board level timing circuit energized and powers pilot gas valve for approximately 15 seconds then de-energizes.  
Page 43 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Boiler Operational Status (LED Indicator)  
Use the tables below to determine the operational status of a component or condition by utilizing the LED  
indicators on the board. The operational states are divided into categories A thru F.  
Initial Conditions: (STATE A)  
- 120V, water and gas supplied to steamer  
- Power Switch ON  
- HIGH PRESS and LOW WATER lights ON (amber, front control panel)  
- Green readylight OFF  
- Water is filling boiler  
STATUS  
LED  
DESCRIPTION  
ELECTRICAL COMPONENTS CONDITION  
ON OFF  
N1  
N2  
N3  
X
X
X
24V supplied to relay board  
Aux Water level not satisfied  
High limit pressure switch satisfied  
Aux. LLCO contacts OPEN  
K2 energized - K2(1) CLOSE, K2(2) CLOSE  
Aux Water level is initially not  
satisfied. Therefore N4 is OFF  
N4  
X
K1(1) OPEN  
N5  
N6  
N7  
X
Reset switch is not being energized  
X
Aux Water level is/was not satisfied K3 not energized  
Reset switch is not being energized  
X
High Limit pressure switch is/was  
K4 not energized  
N8  
N9  
X
X
not satisfied  
Cycling pressure switch is closed  
and unit is calling for HEAT  
N10 through N17 remain OFF  
Aux Water Level Satisfied: (STATE B)  
- Green readylight ON (ready light remains ON, until a LOW WATER or HIGH PRESSURE) condition occurs.  
Status of LEDs are the same as Initial Conditionsexcept for the following:  
STATUS  
LED  
DESCRIPTION  
ELECTRICAL COMPONENTS CONDITION  
ON OFF  
Aux. LLCO relay energized, Aux. LLCO contacts  
CLOSED  
N2  
N4  
X
Aux water level is satisfied  
Aux LLCO water level and high limit  
are satisfied. Green readylight ON.  
X
K1 energized - K1(1) CLOSE  
Reset Engaged: (STATE C)  
User presses/engages the RESET button  
- LOW WATER and HIGH PRESSURE lights OFF (amber, front control panel)  
F24700 (October 2001)  
Page 44 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
DESCRIPTION ELECTRICAL COMPONENTS CONDITION  
same as state A”  
STATUS  
ON OFF  
LED  
N1  
N2  
N3  
N4  
X
X
X
X
same as "state B"  
same as state A”  
same as "state B  
Reset switch is/was momentarily  
energized  
N5  
N6  
N7  
X
K3 energized - K3(1) CLOSE (locking circuit)  
K3 energized - K3(1) OPEN  
Aux Water level is satisfied.  
(Amber WATER light OFF)  
X
X
Reset switch is/was momentarily  
energized  
X
K4 energized - K4(1) CLOSE (locking circuit)  
K4 energized - K4(1) OPEN  
High Limit is satisfied.  
(Amber HIGH PRESS OFF)  
N8  
N9  
X
X
same as state A”  
High limit is satisfied and reset  
switch energized  
N10  
K3(2) CLOSE  
Aux Water level is satisfied and  
reset switch energized  
N11  
N12  
X
X
K4(2) CLOSE, K5 energized  
K5(1) CLOSE  
Air intake blower receiving power  
N13-N17 remain OFF  
Air Pressure Switch Satisfied: (STATE D)  
Assume water level control LLCOis satisfied (LLCO contacts closed)  
N1 thru N12 same as Reset Engaged: (state C)"  
STATUS  
LED  
DESCRIPTION  
ELECTRICAL COMPONENTS CONDITION  
ON OFF  
N13  
N14  
X
X
Air pressure switch satisfied  
24V to ignition module (term 6)  
PV CLOSE, 24V to K7  
Ignition module PV coil energized  
Pilot gas valve is energized.  
Note: N15 and the pilot gas valve will  
be ON for approximately 15 seconds,  
then turn OFF.  
K7 energized K7(1) CLOSE, relay board timer  
circuit energized and starts time count. K6  
energized K6(1) CLOSE, pilot gas valve coil  
energized for 15 sec. only.  
N15  
X
Ignition module PV coil energized,  
pilot ignition flame is detected  
MV CLOSE, 24V to water level board LLCO  
contacts  
N16  
N17  
X
X
Water level board LLCO is satisfied  
and main gas valve is receiving  
power.  
Main gas valve coil energized, main burner  
lights and flame continues to be detected.  
Burner ON, Boiler Heating to generate steam: (STATE E)  
All LEDs ON except N6 & N8, N15 (still OFF from state D)  
Burner OFF, Boiler Pressure Satisfied: (STATE F)  
These LEDs should be OFF - N6, N8, N9, , N10, N11, N12, N13, N14, N15 (still OFF from state D) N16 & N17  
These LEDs should be ON - N1 thru N5, N7  
Page 45 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
limit pressure switch contacts (N.C.).  
SEQUENCE OF OPERATION  
a. K2 contacts K2(1) N.O. & K2(2)  
N.O. close, no power  
transferred.  
NEW STYLE CONTROLS - BOILER  
This sequence of operation is written for boiler  
bases with the new style boiler controls. See  
"BOILER CONTROL STYLES" under "GENERAL".  
Refer to schematic diagram TSP1480.  
3) N9 lit. 24VAC to one side of K3(2)  
N.O. contacts through cycling  
pressure switch N.C.  
3. Water level reaches LLCO probe for both water  
level control and auxiliary low level control.  
Initial Fill and Preheat  
Conditions.  
A. LLCO relay on water level board  
energizes, LLCO contacts (N.O.) close  
A. Power switch OFF.  
1)  
LED on board lights.  
B. Boiler connected to correct voltage  
(120VAC).  
B. Aux. LLCO relay energizes, aux. LLCO  
contacts (N.O.) close.  
C. Boiler properly grounded.  
1)  
LED on board lights.  
D. Gas and water supply valve(s) ON.  
2) N2 lit. K1 is energized.  
E. Main gas valve manual valve in ON  
position  
a. K1(1) N.O. close.  
F. Cycling pressure switch closed.  
G. High limit pressure switch closed.  
b. N4 lit. Ready light (green) on the  
control panel manual reset  
switch, ON.  
H. Cold water condenser (CWC) thermostat  
open.  
3) K1(2) N.O. close.  
NOTE: No power is transferred until manual  
reset switch pressed.  
I.  
Automatic blowdown solenoid valve  
(A.B.D.) open and boiler empty.  
NOTE: The LLCO and aux. LLCO relays will  
remain energized and LLCO LEDS will remain  
lit until the water level drops below the LLCO  
probes or the power switch is turned OFF.  
2. Turn power switch ON.  
A. Automatic Blowdown valve (N.O.) is  
energized and close.  
B. Water level control (WLC) energized.  
NOTE: The reset switch could be pressed to  
start combustion blower & ignition cycle but its  
preferred to let the boiler fill the to the "High  
Level" before continuing.  
1) High level (HL) relay energized, HL-3  
contacts (N.O.) close.  
a. Fill solenoid energized, water  
begins filling the boiler (fill time  
4-11 min.).  
4. Water reaches LL (low level) probe.  
5. Water reaches HL (high level) probe.  
A. Fill solenoid is de-energized.  
B. HL-LED  
2) HL LED lit.  
C. Auxiliary water level control is powered.  
1) Aux. LLCO N.O. contacts remain  
open.  
6. Manual reset switch pressed.  
A. N5 lit. K3 is energized (120VAC).  
D. 120VAC to one side of K5(1) N.O., K1(1)  
N.O., K3(1) N.O., K4(1) N.O. contacts.  
NOTE: Relay K3 remains energized through  
K3(1) N.O. locking circuit.  
E. N6 lit. Low Water light (control panel) lit  
thru K3(1) N.C.  
1) N6 goes out. K3(1) N.O. contacts  
close and K3(1) N.C. contacts open.  
F. N8 lit. Hi Pressure light (control panel) lit  
thru K4(1) N.C.  
2) Low water light (control panel) goes  
out.  
G. N1 lit. 24VAC transformer is energized  
and relay board is powered.  
3) N10 lit. K3(2) N.O. contacts close.  
1) 24VAC to one side of auxiliary water  
level control LLCO contacts (N.O.).  
a. 24VAC to one side of K4(2) N.O.  
contacts.  
2) N3 lit. K2 energized through the high  
B. N7 lit. K4 is energized (120VAC).  
F24700 (October 2001)  
Page 46 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
pilot, quickly cycle the reset switch to prevent  
NOTE: Relay K4 remains energized through  
the boiler from draining. If the pilot is not  
established within 90 seconds from the ignitor  
module being energized, the ignition module  
locks out power to the gas valves. The module  
remains locked out until the power switch is  
turned to OFF then ON and the manual reset  
switch is pressed to r e-start the ignition trial  
cycle.  
K4(1) N.O. locking circuit.  
1) N8 goes out. K4(1) N.O. contacts  
close and K4(1) N.C. contacts open.  
2) High pressure light (control panel)  
goes out.  
C. N11 lit. K4(2) N.O. contacts close.  
1) K5 is energized (24VAC).  
D. As boiler heats up and builds pressure,  
some by-pass water/steam is produced  
which runs into the steam drain box. This  
causes the cold water condenser (CWC)  
solenoid to cycle, cooling the drain water  
and condensing any steam vapors before  
exiting the drain. The CWC solenoid is  
powered through the CWC cycling  
thermostat.  
a. N12 lit. K5(1) N.O. contacts  
close.  
a) Combustion blower starts.  
7. N13 lit. When the combustion blower  
generates sufficient air pressure, the air  
pressure switch N.O. contacts close.  
A. Ignition module is powered (24VAC).  
1) Ignition module starts sparking.  
NOTE: On initial cold startup only, the boiler  
pressure may overshoot and cause the  
mechanical pressure relief valve to open  
momentarily.  
2)  
N14 lit. Pilot voltage (PV) N.O.  
contacts close.  
E. As long as the ignition control module  
senses a burner flame, the internal main  
voltage (MV) contacts (N.O.) on the  
ignition module remain closed, and main  
gas valve stays ON.  
a. K7 is energized.  
a) K7(1) N.O. contacts close.  
3) 15 sec. timer circuit (board level,  
solid state timer) energized and  
timing of pilot gas valve ON time  
begins.  
NOTE: PV N.O. contacts are also closed, but  
K6 contacts are open to keep pilot valve  
closed.  
a. K6 energized.  
8. Boiler steam pressure reaches upper limit set  
point of 10 PSI (Approx. 15 minutes).  
a) N15 lit. K6(1) N.O. close.  
4) Pilot gas valve energized, pilot valve  
opens for gas to flow.  
A. Cycling pressure switch open.  
1) N9, N10, N11, N12, N13 go out.  
a. K5 de-energized.  
B. Pilot flame established. Micro amp flame  
"sense" current rectified to ignition module  
through ignition cable.  
a) K5(1) N.O. contacts open.  
1) Sparking stops.  
b. Combustion blower is de-  
energized.  
2) N16 lit. Main voltage (MV) N.O.  
contacts close.  
a) Air pressure switch opens.  
B. Ignition module is de-energized  
1) PV and MV contacts open.  
a. N17 LED lit. Proves LLCO on  
water level board closed.  
b. Main gas valve opens, burner  
lights and boiler begins to heat  
up.  
a. N14, N16, N17 go out.  
b. Main gas valve closes, burner  
goes out.  
C. 15 seconds after ignition module  
energized, relay board timer circuit times  
out.  
c. K7 de-energized.  
a) K7(1) open  
1) N15 goes out. K6 de-energized.  
9. Boiler steam pressure drops below lower limit  
set point of 8 PSI and the cycling pressure  
switch close.  
a. Pilot valve closes, gas flow stops  
to pilot.  
NOTE: If pilot ignition is not established within  
the allotted 15 seconds, the ignition module  
continues to spark. To attempt to relight the  
A. Boiler steam pressure is maintained by the  
cycling of the pressure switch between the  
Page 47 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
upper and lower set point limits. The B. Boiler connected to correct voltage  
cycling pressure switch continues to  
energize and de-energize the heating  
circuit to cycle the burner ON and OFF.  
(120VAC).  
1) Power to cooking compartment  
controls. See "COOKING  
This sequence continues until one of the  
following occurs:  
COMPARTMENT CONTROLS" later  
in this section.  
1) Power switch is turned OFF.  
C. Boiler properly grounded (boiler and water  
level controls share a common ground)  
2) Boiler water level drops below the  
LLCO probes for the main water level  
control (WLC) and the auxiliary low  
level control.  
D. Gas and water supply valve(s) ON.  
E. Main gas valve ON.  
F. Cycling pressure switch CLOSED.  
G. High limit pressure switch CLOSED.  
3) Boiler pressurizes to 15 PSI, causing  
the high limit pressure switch to open.  
H. Cold water condenser (CWC) thermostat  
OPEN.  
Water Refill (After Initial Fill)  
1. Water level drops below low level probe (LL).  
A. HL relay is energized.  
I.  
Automatic blowdown valve (A.B.D.) OPEN  
and boiler empty.  
1) HL-3 (N.O.) contacts close.  
2) Fill solenoid is energized.  
3) HL LED comes ON.  
2. Turn power switch ON.  
A. Relay R4 energized and R4 contacts  
(N.O.) CLOSE.  
B. Power ON light (red) comes ON.  
2. Water reaches LL (low level) probe.  
3. Water reaches high level probe.  
A. HL relay is de-energized.  
1) HL-3 (N.O.) contacts open.  
2) Fill solenoid is de-energized.  
3) HL LED goes out.  
C. Blowdown solenoid valve is energized and  
CLOSES.  
D. Auxiliary water level control is powered.  
1) Aux. LLCO N.O. contacts remain  
OPEN (Aux. LLCO relay de-  
energized).  
E. Low water level light (amber) comes ON.  
4. The water refill cycle will occur whenever the  
water level is below the low level probe and will  
not affect the operation of either the preheat or  
cook cycle.  
NOTE: The low water indicator light will remain  
ON and the safety circuit de-energized until the  
water level in the boiler reaches the auxiliary  
low level cut-off probes (aux. LLCO, minimum  
level) for the aux. water level control, and the  
manual reset switch is pressed.  
Boiler Blowdown/drain  
1. Power switch turned OFF.  
A. Automatic blowdown solenoid valve (N.O.)  
is de-energized and valve opens to drain  
the boiler.  
F. High pressure light (amber) comes ON.  
NOTE: The high pressure indicator light will  
remain ON and the safety circuit de-energized  
until the manual reset button is pressed (high  
limit pressure switch must be closed).  
B. Power is removed from all components  
except cold water condenser (CWC)  
thermostat and solenoid valve. The CWC  
thermostat cycles as necessary to lower  
the discharge temperature of the water  
and condense steam going into the drain.  
G. Power is connected through the high limit  
pressure switch contacts (N.C.) to one side  
of the push button reset switch.  
H. Water level control is powered (Low Level  
Cut-off & Differential Control).  
OLD STYLE CONTROLS - BOILER  
This sequence of operation is written for boiler  
bases with the old style boiler controls. See  
"BOILER CONTROL STYLES" under "GENERAL".  
Refer to schematic diagram 5480.  
1) High level (HL) relay is energized, HL  
contacts (N.O.) CLOSE  
a. HL LED lights up.  
Initial Fill And Preheat  
1. Conditions.  
b. Fill solenoid is energized and  
water begins filling boiler (fill  
time 4-11 min.).  
A. Power switch OFF.  
F24700 (October 2001)  
Page 48 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
3. Water level reaches LLCO (low water level cut- 3) Main voltage (MV) N.O. contacts  
off) probe for the water level control and to the  
auxiliary LLCO probe for the auxiliary low level  
cut-off control.  
CLOSE.  
a. Main gas valve OPENS, burner  
lights and boiler begins to heat  
up.  
A. LLCO relay energizes, LLCO contacts  
(N.O.) CLOSE and LED lights.  
NOTE: As boiler heats up and builds pressure,  
some by-pass water/steam is produced which  
runs into the steam drain box. This causes the  
cold water condenser (CWC) solenoid to cycle,  
cooling the drain water and condensing any  
steam vapors before exiting the drain. The  
CWC solenoid is powered by the CWC  
thermostat.  
NOTE: No power is transferred until ignition  
sequence starts.  
B. Aux. LLCO relay energizes, LLCO  
contacts (N.O.) CLOSE and LED lights.  
NOTE: The LLCO and aux. LLCO relays will remain  
energized and LLCO LEDS will remain lit until the  
water level drops below the LLCO probes or the  
power switch is turned OFF.  
NOTE: On initial cold startup only, the boiler  
pressure may overshoot and cause the  
mechanical pressure relief valve to OPEN  
momentarily.  
4. Water reaches LL (low level) probe.  
5. Water reaches HL (high level) probe.  
A. Fill solenoid is de-energized.  
6. Press the manual reset switch.  
A. Relay coil (R1) energized.  
b. As long as the ignition control  
module senses a burner flame,  
the internal main voltage (MV)  
contacts (N.O.) on the ignition  
module remain closed, and main  
gas valve stays ON.  
1) High pressure light turns OFF.  
B. Relay coil (R3) energized.  
c. If sparking is allowed to continue  
for a total of 90 seconds, then  
the ignition module locks out  
power to the gas valve (pilot  
valve and main valve remain  
closed). The module remains  
locked out until the power switch  
is turned to OFF then ON and  
the manual reset switch is  
pressed to re-start the ignition  
trial cycle.  
1) Low water light turns OFF.  
2) Transformer (T1) energized.  
7. 24VAC is connected through the cycling  
pressure switch contacts to the following  
components:  
A. Normally open (N.O.) side of the air  
pressure switch.  
NOTE: No power is transferred until air  
pressure switch CLOSES.  
8. Boiler steam pressure reaches upper limit set  
point of 10 PSI (approximately 15 min).  
B. Relay coil (R2) is energized and R2  
contacts (N.O.) CLOSE.  
A. Cycling pressure switch opens and power  
is removed from the following  
components:  
1) 120VAC is supplied to the  
combustion air blower and blower  
starts.  
1) Combustion air pressure switch  
normally open (N.O.) terminal.  
C. Once the combustion blower develops  
sufficient pressure, the air pressure switch  
CLOSES.  
2) Relay coil (R2) returning R2 contacts  
to there N.O. shelf state.  
1) 24VAC is then applied to the Ignition  
control module and the ignition cycle  
starts.  
a. Combustion air blower de-  
energized.  
a. Pilot voltage (PV) N.O. contacts  
CLOSE.  
B. Ignition control module is de-energized,  
PV and MV contacts OPEN.  
b. Pilot gas valve energized, pilot  
valve opens for gas to flow and  
Ignitor begins sparking to light  
pilot.  
1) Main gas solenoid valve de-  
energizes, gas flow shuts OFF and  
burner goes out.  
9. Boiler steam pressure drops below lower limit  
set point of 8 PSI and the cycling pressure  
switch CLOSES.  
2) Pilot ignition is established (pilot lit)  
and a micro amp flame "sense"  
current is sent back to the ignition  
module through the ignition cable.  
A. Boiler steam pressure is maintained by the  
cycling of the pressure switch between the  
Page 49 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
upper and lower set point limits. The  
1) Cooking compartment ready light  
(green) comes ON.  
cycling pressure switch continues to  
energize and de-energize the heating  
circuit to cycle the burner ON and OFF.  
3. Start a cook cycle.  
A. Insert product into steamer and close door.  
B. Set a cook time.  
This sequence continues until one of the  
following occurs:  
NOTE: On initial startup, if a cooking timer is  
set immediately after the ready light comes on,  
steam solenoid chattering will be heard (oil  
canning) and the ready lights will flash for  
several seconds. This condition is caused by  
the manifold steam pressure being on the  
"fringe" of the pressure switch set point. When  
a cook timer is set, the compartment steam  
solenoid valve opens causing the manifold  
steam pressure to drop, slightly below the  
pressure switch set point. At the same time,  
steam pressure is still increasing in the boiler.  
This opposing condition causes a pressure  
"bounce" to occur. After the steam pressure  
passes approximately 4 psi this condition  
subsides. During normal operation, this  
condition will not be seen.  
1) Power switch is turned OFF.  
2) Boiler water level drops below the  
LLCO probes for the main water level  
control and the auxiliary low level cut-  
off control  
3) Boiler pressurizes to 15 PSI, causing  
the high limit pressure switch to  
OPEN.  
Water Refill (After Initial Fill)  
1. Water level drops below low level probe (LL).  
A. HL relay is energized.  
1) HL N.O. contacts CLOSE, fill  
solenoid is energized and HL LED  
comes ON.  
2. Water reaches LL (low level) probe.  
3. Water reaches high level probe.  
A. HL relay is de-energized.  
C. Contacts 1/3 of cook timer CLOSE and  
timer motor is energized.  
1) Compartment steam solenoid valve  
energized and steam begins to enter  
the compartment.  
1) HL N.O. contacts OPEN, fill solenoid  
is de-energized and HL LED goes  
out.  
2) Ready light (green) goes out and  
Cooking light (red) comes ON.  
4. The water refill cycle will occur whenever the  
water level is below the low level probe and will  
not affect the operation of either the preheat or  
cook cycle.  
NOTE: Steam should not be seen entering  
either compartment until a cook time is  
set. This energizes the steam solenoid  
valve of the cooking compartment to allow  
steam flow.  
Boiler Blowdown/Drain  
1. Power switch turned OFF.  
A. Boiler blowdown sequence starts.  
4. Time expires on timer.  
A. Timer contacts 1/3 OPEN, timer motor de-  
energized.  
B. The automatic blowdown solenoid valve  
(N.O.) is de-energized and valve OPENS  
to drain the boiler.  
B. Steam solenoid valve de-energizes,  
stopping the flow steam into compartment.  
C. Power is removed from all components  
except cold water condenser (CWC)  
C. Timer contacts 4/1 CLOSE and energize  
buzzer until manually turned OFF.  
thermostat and solenoid valve. The CWC  
thermostat cycles as necessary to lower  
the discharge temperature of the water  
and condense steam going into the drain.  
D. Cooking light (red) goes out and Ready  
light (green) comes ON.  
5. Timer manually turned OFF.  
A. Contacts 1/4 OPEN  
COOKING COMPARTMENT CONTROLS  
1. Conditions.  
B. Alarm Buzzer de-energized and stops  
buzzing.  
A. Doors shut (closes the N.O. door switch  
contacts).  
6. Steamer reverts to preheat cycle until time is  
dialed on timer and the door is shut, water level  
drops below low level cut-off probe or the  
power switch is turned OFF.  
B. Cooking timers OFF.  
C. Compartment pressure switch contacts  
OPEN.  
2. With boiler at operating pressure.  
A. Cooking compartment pressure switch  
CLOSES (approx. 3 PSI).  
F24700 (October 2001)  
Page 50 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
- THIS PAGE INTENTIONALLY LEFT BLANK -  
Page 51 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
SCHEMATICS  
Models Built After 5/25/00 (New Style Boiler Controls)  
F24700 (October 2001)  
Page 52 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Page 53 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Models Built Before 5/25/00 (Old Style Boiler Controls)  
F24700 (October 2001)  
Page 54 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Cooking Compartment Controls  
Page 55 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
WIRING DIAGRAMS  
Models Built After 5/25/00 (New Style Boiler Controls)  
F24700 (October 2001)  
Page 56 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Page 57 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Models Built Before 5/25/00 (Old Style Boiler Controls)  
F24700 (October 2001)  
Page 58 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Page 59 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Cooking Compartment Controls  
F24700 (October 2001)  
Page 60 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
TROUBLESHOOTING  
BOILER BASE CONTROLS  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TESTS OR  
MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL  
TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST  
EQUIPMENT AND REAPPLY POWER TO TEST.  
Models with new style controls: Before performing any of the troubleshooting checks listed below, remove the  
cover from the main control box and check the condition of the LEDS on the relay board for the status of the  
condition or component in the operating sequence. By utilizing the troubleshooting LEDS, the Service  
Technician can quickly and easily determine if a component is functioning properly or in need of repair. Refer to  
"RELAY BOARD" under "ELECTRICAL OPERATION".  
SYMPTOM  
POSSIBLE CAUSES  
1. No power to steamer.  
Steamer does not operate.  
2. F1 Fuse open.  
3. Malfunctioning power switch.  
4. Malfunctioning power switch latching relay (old style controls  
only).  
Steamer ON, cannot reset low water  
condition.  
1. Low water level in boiler.  
A. Water inlet valve(s) OFF.  
B. Fill solenoid not receiving power, clogged or  
malfunctioning.  
2. Manual blowdown valve on water level probe housing open.  
3. Improper ground.  
4. Lime scale build-up auxiliary water level probe.  
5. Malfunctioning reset switch.  
6. Malfunctioning auxiliary water level control board.  
Steamer ON, cannot reset high pressure 1. Excessive pressure in boiler.  
condition.  
2. Malfunctioning reset switch.  
3. Malfunctioning high pressure limit switch.  
4. Malfunctioning pressure switch latching relay (old style controls  
only).  
Steamer ON, reset switch pressed but  
blower does not operate when calling for  
heat.  
1. Blower malfunctioning or loose connection on blower cord.  
2. 24 VAC transformer malfunctioning.  
3. Malfunction in cycling pressure switch.  
4. Malfunctioning "Low Water" or "Hi Pressure" light not indicating  
true condition.  
(boiler pressure within operating limits)  
5. Blower relay malfunctioning (old style controls only).  
Page 61 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Blower operating, no pilot gas flow.  
1. Main gas supply turned OFF.  
2. Ignition module lockout. Turn power switch OFF for several  
seconds then ON to reset the module.  
3. Air pressure switch:  
A. Not mounted in true vertical position.  
B. Incorrect pressure setting.  
C. Malfunctioning switch.  
4. Malfunctioning Ignition module.  
5. Malfunctioning pilot gas valve.  
6. Blocked or dirty pilot gas orifice.  
Pilot flame not proving or lighting main  
burner.  
1. Gas not ON.  
2. Incorrect manifold pressure for pilot gas.  
3. Poor connection between igniter and ignition cable.  
4. Fouled spark igniter.  
5. Incorrect gap in spark igniter.  
6. Faulty igniter or cracked insulation.  
7. Improper ground.  
8. Low water level in boiler or boiler not filling.  
9. Flame sensing current too low.  
10. Cracked or incorrect burner head attachment.  
11. Incorrect igniter positioning.  
12. Incorrect pilot orifice.  
Main burner not lighting correctly or  
excessive ignition noise.  
1. Blocked or dirty air orifice on blower.  
2. Insufficient gas supply pressure.  
3. Incorrect gas pilot pressure.  
4. Incorrect gas manifold pressure.  
5. Pilot flame not sensing correctly.  
6. Burner tube insulation broken or deteriorated.  
7. Blocked or restricted flue.  
8. Incorrect pilot or main gas burner orifice size.  
Excess combustion noise or combustion 1. Blocked or dirty air orifice on blower.  
induced harmonics.  
2. Incorrect gas manifold pressure.  
3. Insufficient gas supply pressure.  
4. Steam vapors introduced into blower inlet.  
5. Loose flue connections.  
Boiler not maintaining set pressure  
and/or excessive burner on time.  
1. Leaking boiler blowdown valve.  
2. Manual blowdown valve on water level probe housing open.  
3. Malfunctioning 13 psi overshoot relief valve.  
4. Low incoming gas supply pressure.  
5. Excessive load on steam outlet.  
F24700 (October 2001)  
Page 62 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Gas odor.  
1. Leaks in pipe fitting connections or components.  
2. Leaking pressure tap plug on pilot or main gas valve; loose or  
missing pressure adjustment screw cap on main gas valve.  
3. Leaking gaskets in air/gas mixture path.  
4. Pilot or main gas valve malfunction (improper venting or vent  
blocked).  
5. Incorrect gas pressure.  
6. Malfunctioning gas burner.  
7. Blocked or dirty air orifice on blower.  
8. Blocked or dirty gas orifice.  
9. Malfunctioning blower.  
10. No pilot ignition.  
11. Improper hood venting, vent blocked or room not vented  
properly.  
Drain box leaking.  
1. Clog in drain line plumbing.  
2. Drain restricted to size below 1-1/4" pipe.  
3. Drain extension plumbing not at the proper slope or plumbing  
too lengthy.  
4. Grommets not sealing.  
5. Steamer draining while under pressure and relief valve opening  
at the same time (flooding drain box).  
6. Cold water condensing spray is "over spraying".  
7. Drain box thermostat improperly set or malfunctioning.  
Cold water condenser not operating  
properly.  
1. Water supply valves(s) turned off.  
2. Cold water condenser solenoid not receiving power, inoperative  
or valve plugged.  
3. Cold water condenser thermostat malfunction or needs  
adjustment.  
4. Plugged spray nozzle.  
5. Water supply pressure high (improper valve operation).  
Heat coming on without water in boiler  
(Dry firing).  
1. Lime scale build-up on water level probes (shorted to ground).  
2. Retention of water in probe housing (assembly or aux.LLCO).  
3. Water level control malfunction.  
4. Aux. water level control malfunction.  
Spark Ignitor not sparking.  
1. Ignitor boot on ignition cable loose, damaged or missing  
causing excessive ignition voltage leakage.  
2. Loose, broken or damaged lead wires (including ground) from  
ignition module to ignitor.  
3. Poor ground on ignitor assembly.  
NOTE: Items 4, 5 & 7 see "IGNITION CONTROL MODULE  
CHECKS" in "SERVICE PROCEDURES AND  
ADJUSTMENTS".  
4. Ignition module not receiving power.  
5. Ignition module malfunction (no output voltages or spark).  
6. Ceramic flame rod insulator on ignitor cracked or damaged  
from extreme heat.  
7. Incorrect spark gap setting.  
Page 63 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Boiler Slow to Pressurize  
1. Low water supply pressure, inline water strainer clogged or fill  
solenoid valve malfunction. See "INLINE WATER STRAINER  
CLEANING" and "FILL AND COLD WATER SOLENOID  
VALVES" in "SERVICE PROCEDURES AND  
ADJUSTMENTS".  
(over 15 min. to achieve operating  
pressure)  
2. Boiler blowdown solenoid valve clogged and not fully closing.  
Check for a slow leak out of steamer drain. If not able to verify,  
then proceed to step 3. If blowdown solenoid valve appears to  
be functioning properly, then proceed to step 4.  
3. Turn power switch OFF, disconnect lead wires from blowdown  
solenoid and remove it for inspection.  
4. A heavy build-up of scalants has coated the interior of the  
boiler, creating an insulating effect. Examine interior of boiler  
as outlined under BOILERin "SERVICE PROCEDURES AND  
ADJUSTMENTS".  
5. Low incoming gas pressure is reducing BTU output.  
A. Verify gas supply line to the steamer is a minimum of one  
inch diameter (ID).  
B. Check incoming line and manifold gas pressures as  
outlined in "GAS MANIFOLD PRESSURE ADJUSTMENT"  
under "SERVICE PROCEDURES AND ADJUSTMENTS".  
6. Gas valve malfunction.  
A. Check incoming line and manifold gas pressures as  
outlined in "GAS MANIFOLD PRESSURE ADJUSTMENT  
under "SERVICE PROCEDURES AND ADJUSTMENTS".  
Boiler will not heat or build pressure.  
1. Gas not on.  
2. Power/reset switch assembly malfunction.  
3. Boiler not filling - check fill solenoid for power, clogging or  
malfunction.  
4. Gas pilot and/or gas manifold pressure low. See "GAS PILOT  
PRESSURE ADJUSTMENT" and "GAS MANIFOLD  
PRESSURE ADJUSTMENT" in "SERVICE PROCEDURES  
AND ADJUSTMENTS".  
5. Cycling pressure switch open or set too high. Steamer is  
cycling on high limit.  
6. High limit pressure switch open and not re-setting  
(malfunction).  
7. Water too "pure" for probes to properly conduct electricity.  
NOTE: Items 8 & 9 see "WATER LEVEL CONTROLS TEST"  
in "SERVICE PROCEDURES AND ADJUSTMENTS".  
8. Water Level Control malfunction.  
9. Aux. Water Level Control malfunction.  
Pressure relief valve(s) opening or  
leaking.  
1. Pressure overshoot on initial startup or long burner on times  
under heavy usage.  
2. Pressure relief valve malfunction.  
3. Cycling pressure switch set to high.  
4. High limit pressure switch not set correctly or malfunctioning.  
F24700 (October 2001)  
Page 64 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Steam output low or slow cooking.  
1. Cooking Compartment.  
A. Blocked steam injector ports. (Open door, press door  
switch button and verify good steam flow into  
compartment).  
B. Steam solenoid valve not fully opening or blocked.  
C. Steam intake shut-off valve closed or out of adjustment.  
See "INTAKE SHUT-OFF VALVE ADJUSTMENT (STEAM  
FLOW)" in "SERVICE PROCEDURES AND  
ADJUSTMENTS".  
2. Boiler Base.  
A. Cycling pressure switch malfunction or needs adjustment.  
B. Steam header line (supply) blockage.  
C. Heavy amount of condensate in the pressure controls  
steam supply line.  
D. Pressure relief valve leaking.  
E. Steam supply lines leaking badly.  
Steamer leaks water.  
Boiler water level too high.  
Boiler does not fill.  
1. Loose water, steam or drain line connections (top or base).  
2. Heat exchanger gasket not sealing.  
3. Leak at gauge glass.  
1. Fill solenoid does not shut off.  
2. Lime scale build-up (moist) on High level probe (open circuit).  
3. Water level control malfunction.  
1. Water supply not on.  
2. Fill solenoid not opening or plugged.  
3. Water level control malfunction.  
Burner wont light.  
1. Gas not on.  
2. Power/reset switch assembly malfunction.  
3. Boiler not filling - check fill solenoid for power, clogging or  
malfunction.  
4. Air pressure switch:  
A. Not mounted in true vertical position.  
B. Incorrect pressure setting.  
C. Malfunctioning switch.  
5. Ignition module not receiving power.  
6. Steamer not properly grounded and/or polarity of incoming  
power is incorrect on spark ignition systems.  
7. Ignition module malfunction.  
8. Gas valve malfunction.  
9. Water too "pure" for probes to properly conduct electricity.  
10. Cycling pressure switch open or set too high. Steamer is  
cycling on high limit.  
11. High limit pressure switch open and not re-setting  
(malfunction).  
12. Water level control malfunction.  
13. Aux. water level control malfunction.  
Page 65 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
COOKING COMPARTMENT CONTROLS  
SYMPTOM  
POSSIBLE CAUSES  
Cooking compartments do not operate.  
1. No power to compartments.  
2. Pressure in boiler is below compartment pressure switch  
setting.  
3. Door switch malfunction.  
4. Timer malfunction.  
5. Malfunctioning pressure switch in compartment.  
6. Verify correct compartment wiring and functioning  
components.  
Steam generated inside compartment  
when timer is off.  
1. Steam supply solenoid not fully closing (clogged or dirty). See  
"FILL AND COLD WATER SOLENOID VALVES" in "SERVICE  
PROCEDURES AND ADJUSTMENTS".  
2. Timer contacts 1 & 3 closed.  
Timer motor does not run.  
Door not closing properly.  
1. Door open or door switch inoperative.  
2. Timer not getting power.  
3. Timer motor inoperative.  
1. Door latch assembly malfunction or out of adjustment. See  
"DOOR SEALING ADJUSTMENT" in "SERVICE  
PROCEDURES AND ADJUSTMENTS"  
2. Striker adjustment. See "DOOR LATCH ADJUSTMENT" in  
"SERVICE PROCEDURES AND ADJUSTMENTS".  
Door wont open.  
1. Latch wont release. See "DOOR LATCH ADJUSTMENT" in  
"SERVICE PROCEDURES AND ADJUSTMENTS".  
Buzzer not operating.  
1. Timer malfunction.  
2. Buzzer malfunction.  
Compartment leaks water around door  
or water accumulating in compartment .  
1. Compartment drain screen clogged.  
2. Drain line obstructed or not to an open gap drain.  
3. Steamer not level.  
Steam leaks around door.  
1. Worn gasket - See "DOOR SEALING ADJUSTMENT" in  
"SERVICE PROCEDURES AND ADJUSTMENTS".  
2. Damaged gasket.  
3. Drain line obstructed or not to an open drain.  
F24700 (October 2001)  
Page 66 of 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER  
- NOTES -  
Page 67 of 68  
F24700 (October 2001)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - CONDENSED SPARE PARTS LIST  
CONDENSED SPARE PARTS LIST  
NEW STYLE CONTROLS ONLY  
VHX24G, VHX24G5, MHB24G  
PART NUMBER  
DESCRIPTION  
NOTES  
853582-1  
850778-1  
850735-1  
354344-4  
851315-1  
851316-1  
880413  
Igniter, Sensor  
Switch, Air Pressure  
Blower, Combustion  
Valve, Pilot Gas  
Valve, Main Gas  
Valve, Pressure Relief 13 psi  
Valve, Pressure Relief 15 psi  
Valve(s), Cold Water Condenser and Boiler Fill  
Switch, Pressure Cycling  
Switch, Pressure High Limit  
Thermostat, Condenser/drain Box  
Transformer, 120vac to 24vac  
Module, Ignition Control  
817222  
833488  
851578-1  
844062-1  
411500-12  
417980-1  
844070-1  
844069-1  
852081-1  
851613-1  
851618-1  
844130-3  
853275-1  
853273-1  
411690-1  
843836  
Control, Aux. Low Water Board  
Control, Water Board  
Circuit, Breaker 5amp Slow Blow (fuse)  
Boiler, Drain Valve (blowdown)  
Power Cord, drain Valve  
Cable, Ignitor 18"  
Switch assembly, on/off, reset & lights  
Relay Board  
Timer, Cooking  
Steam Solenoid Valves, Cooking Compartment  
F24700 (October 2001)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

TechniSat Satellite Radio VC 2002 S User Manual
Toastmaster Coffeemaker MECF10 User Manual
Toastmaster Rice Cooker TRC5 User Manual
Toshiba Satellite TV System P100 ST9012 User Manual
TRENDnet Network Card TEG MGBSX User Manual
Tripp Lite Universal Remote PR PR04 User Manual
Uniden Cordless Telephone CEZAI 998 User Manual
VistaQuest Digital Camera VQ 5010 User Manual
VTech Baby Monitor DM221 User Manual
Weed Eater Lawn Mower 164833 User Manual