Vulcan Hart Electric Steamer MHB24E User Manual

SERVICE MANUAL  
VHX BOILER BASE SERIES  
HIGH EFFICIENCY  
ELECTRIC STEAMER  
VHX24E  
VHX24E5 ML-126853  
MHB24E ML-126857 (BASE ONLY)  
ML-126852  
VHX24E SHOWN  
- NOTICE -  
This Manual is prepared for the use of trained Vulcan Service  
Techniciansandshouldnotbeusedbythosenotproperlyqualified.  
If you have attended a Vulcan Service School for this product, you  
may be qualified to perform all the procedures described in this  
manual.  
This manual is not intended to be all encompassing. If you have not  
attended a Vulcan Service School for this product, you should read,  
in its entirety, the repair procedure you wish to perform to  
determine if you have the necessary tools, instruments and skills  
requiredtoperform theprocedure. Proceduresforwhichyoudonot  
have the necessary tools, instruments and skills should be  
performed by a trained Vulcan Service Technician.  
Reproduction or other use of this Manual, without the express  
written consent of Vulcan, is prohibited.  
For additional information on Vulcan-Hart or to locate an authorized parts and  
A product of VULCAN-HART  
LOUISVILLE, KY 40201-0696  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS  
ELECTRICAL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Component Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Cabinet Base Boiler Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Component Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Boiler Base Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
Water Level Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Low Level Cut-Off & Differential Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Auxiliary Low Level Cut-Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Layout, Legend & Diagnostic Test Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Boiler Base Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Boiler Base Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Heating Element Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Cooking Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
CONDENSED SPARE PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
© VULCAN 2004  
Page 3 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - GENERAL  
GENERAL  
Cooking Compartments Control Panel  
INSTALLATION, OPERATION  
AND CLEANING  
Refer to the Installation and Operation Manual for  
specific instructions.  
INTRODUCTION  
Steam Cooking  
Convection cooking in pressure-less steaming  
compartments will steam cook fresh foods or will  
steam defrost and cook frozen foods providing the  
maximum color, flavor and nutritional value with the  
least expenditure of energy and labor. The pressure-  
less steaming compartments on the VHX series,  
allows the operator to open and close the door  
anytime during a cooking cycle. The steam supply  
will shut off when the door is opened, then re-start  
when the door is closed.  
Model Designations  
Boiler Control Panel  
Compartment Pan Capacity  
PAN  
DEPTH  
(INCHES)  
NUMBER OF PANS  
PER COMPARTMENT  
MODEL  
2
4.0  
2.5  
1.0  
4.0  
2.5  
1.0  
VHX24E  
3
6
3
VHX24E5  
5
10  
Pan Size 12" x 20"  
F25154 (February 2004)  
Page 4 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - GENERAL  
The desired water properties can best be achieved  
Boiler Code Descriptions  
by using a properly maintained water treatment  
system.  
Vulcan-Hart incorporates redundant controls in  
compliance with the CSD-1 controls and safety  
devices for boiler construction on the high efficiency  
steamer models. A description of the code is listed  
below.  
The water level probes in the boiler use ions in the  
water to detect the water level. Do not use fully  
demineralized or de-ionized water since it is non  
conductive and the water level can not be  
detected.  
CSD-1 Construction - Redundant controls in the  
electrical safety circuits that, if tripped, must  
manually be reset after the condition causing the trip  
subsides. The controls provide low water level cut-off  
protection (LLCO), auxiliary low water level cut-off  
protection (Aux LLCO), and high pressure protection  
for the boiler. Additionally, the low water and high  
pressure safety circuits have individual indicator  
lights that will illuminate for a visual verification of the  
shutdown mode.  
The use of strainers will not remove minerals from  
the water.  
Water supplies vary from state to state and from  
locations within a state. Therefore, a water  
treatment specialist should be consulted before  
the installation of any steam generating equipment.  
Steamers that operate over a long period of time  
without the benefit of a water treatment system,  
which have developed a heavy scale build-up,  
should be cleaned before using the system.  
CSD-1 construction requires operator intervention in  
the event of a shutdown. The indicator lights show  
the operator which safety system was shutdown.  
SPECIFICATIONS  
WATER CONDITIONING  
Boiler Pressure  
Operating - 10 to 12 psi  
Maximum - 15 psi  
Water Supply  
Furnishing the boiler with treated water to reduce  
scale formation is advised. Scale formation will  
reduce steam output, cause premature component  
failure, and shorten equipment life. Most water  
supplies contain scale producing minerals such as  
calcium and magnesium. As steam is generated, the  
minerals remain and dissolve into the water. As the  
concentration of these minerals increases past a  
certain point, they precipitate from the water and  
coat the inside of the boiler, heating elements, and  
water level sensors. Because of the high  
The fact that a water supply is potable is no  
guarantee that it is suitable for steam generation.  
The supply connection to the steam generator  
should be treated water and must be within the  
guidelines listed below. For drain water cooling only,  
an untreated water supply connection should be  
used.  
temperature of these surfaces, the precipitated  
minerals bake onto them and become very difficult to  
remove.  
Supply connection  
Supply pressure should be  
Hardness*  
cold water  
20-60 psig  
This may cause several problems:  
1. Reduced heat transfer efficiency.  
2. Premature heating element failures.  
3. False readings from water level sensors.  
less than 60 ppm  
less than 13 ppm  
less than 4 ppm  
7 to 8  
Silica  
Total Chloride  
PH Range  
These problems are common to any steam  
equipment manufacturer, regardless of design, but  
can be minimized by furnishing the boiler with  
treated water.  
less than 5  
microns  
Un-dissolved Solids  
Other factors affecting steam generation are iron  
content, amount of chlorination and dissolved gases.  
*17.1 ppm = 1 grain of hardness  
Page 5 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - COMPONENT FUNCTION  
Electrical  
MODELS  
AMPERAGE  
TOTAL  
KW  
1 PHASE  
3 PHASE  
208V 240V 208V 240V 480V  
24  
36  
42  
48  
116  
---  
100  
---  
67  
100  
117  
---  
58  
87  
29  
44  
---  
58  
VHX24E,  
VHX24E5,  
MHB24E  
---  
---  
---  
---  
---  
116  
1. Amperage values in the table are  
nominal. Tolerance is +5/-10%.  
NOTES:  
2. Voltage values are @ 60HZ.  
3. 24KW 3 phase is standard for both  
models. If a 24KW single phase  
connection is needed, the machine is  
field convertible at the terminal block.  
See heating element circuit diagram  
AI1388.  
TOOLS  
Standard  
!
!
Standard set of hand tools.  
VOM with AC current tester.  
NOTE: Any quality VOM with a sensitivity of at  
least 20,000 ohms per volt can be used.  
Special  
!
The recommended deliming chemical for the  
water treatment system in use, for deliming of  
the boiler.  
!
!
Heat Exchanger Gasket (joint sealant strip,  
Teflon) P/N 854058-1.  
Loctite 242 thread sealant or equivalent  
P/N 520228. Used on the top and bottom  
cooking compartment door screws.  
!
3/8 x 16 tap. Used for cleaning out threads on  
front boiler flange.  
F25154 (February 2004)  
Page 6 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
REMOVAL AND REPLACEMENT OF PARTS  
PRESSURE SWITCH CONTROL  
BOX COMPONENTS  
WARNING: DISCONNECT THE  
ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES.  
CAUTION: Certain components in this system are subject to damage by electrostatic discharge during  
field repairs. A field service grounding kit is available to prevent damage. The field service grounding kit  
must be used anytime a control board is handled.  
1. Open the cabinet base door.  
2. Remove cover from pressure switch control box.  
3. Disconnect lead wires from component being replaced.  
4. To remove:  
A. Cycling pressure switch.  
1) Disconnect compression fittings in the pressure supply line leading to the switch.  
2) Remove mounting nuts from pressure switch mounting panel.  
3) Disconnect conduit from box.  
Page 7 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
MAIN CONTROL BOX  
COMPONENTS  
WARNING: DISCONNECT THE  
ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES.  
CAUTION: Certain components in this system  
are subject to damage by electrostatic discharge  
during field repairs. A field service grounding kit  
is available to prevent damage. The field service  
grounding kit must be used anytime a control  
board is handled.  
1. Open the cabinet base door.  
2. Remove heating element cover then main  
control box cover.  
4) Disconnect lead wires from other  
components as necessary then  
remove pressure switch mounting  
panel.  
5) Remove screws securing switch to  
panel.  
B. High limit pressure switch.  
1) Disconnect compression fittings from  
switch then remove from box.  
C. Boiler fill or cold water condenser valve.  
1) Turn water supply off and disconnect  
compression fittings from valve.  
2) Remove valve bracket mounting  
screws.  
D. Main or auxiliary water level control board  
1) Compress locking tab on the board  
mounting standoffs and remove  
control board.  
3. Disconnect lead wires from component being  
replaced.  
5. Reverse procedure to install.  
NOTE: Before installing the cycling pressure switch,  
use pressure scale on the switch to preset the  
approximate cut-out (off) and cut-in (on) set points.  
A. Adjust the installed pressure switch  
(cycling or high limit) as outlined in  
SERVICE PROCEDURES AND  
ADJUSTMENTS.  
6. Check for proper operation.  
F25154 (February 2004)  
Page 8 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
WATER LEVEL GAUGE  
ASSEMBLY  
WARNING: DISCONNECT THE  
ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES.  
1. Remove right side panel.  
NOTE: If right side panel is not accessible, open the  
cabinet door and remove control panel to access  
from front.  
2. Loosen packing nuts on glass tube until threads  
disengage then slide nut toward center of tube.  
4. To remove:  
A. Contactors.  
1) Release catch at the base of  
contactor and remove from DIN rail.  
B. Relays.  
1) Remove from socket.  
C. Relay Board.  
1) Compress locking tab on the board  
mounting standoffs and remove  
control board.  
5. Reverse procedure to install and check for  
proper operation.  
NOTE: When the main control box cover is properly  
installed, the gap between the front lip of cover and  
main control box must be maintained for adequate  
ventilation. Do not seal the gap.  
LEFT SIDE VIEW SHOWN  
3. Slide glass tube up until it clears the bottom  
fitting, tilt out at the bottom and slide glass tube  
down to remove.  
NOTE: Clean glass tube if cloudy or replace if chips  
or cracks are noticed.  
4. Remove packing nuts from glass tube.  
A. A single rubber washer is installed inside  
each packing nut. Clean debris from  
washer and inspect the rubber for cracks  
or hardening.  
1) If rubber washer needs replacing,  
install a replacement rubber washer in  
each packing nut.  
NOTE: When installing, ensure friction  
washer (flat) is installed inside the packing  
nut before rubber washer.  
5. To Install:  
A. Slide packing nuts onto glass tube and  
position each nut approximately 1" from  
open end on tube.  
Page 9 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
B. Insert one end of glass tube into top gauge  
fitting then align opposite end of tube with  
bottom gauge fitting.  
C. Lower the glass tube into bottom gauge  
fitting then center the tube between top &  
bottom gauge fittings.  
D. Hold glass tube in place and hand tighten  
the bottom packing nut then top.  
E. Tighten each packing nut and additional  
1/2 turn.  
CAUTION: Do not over tighten packing nuts or  
damage to glass tube may occur.  
6. Re-connect power to the machine.  
7. Turn power switch on and allow boiler to fill.  
A. Press reset switch to begin heating (green  
ready light on).  
8. Check gauge glass for water and steam leaks.  
A. If necessary, slowly tighten packing nuts  
until leak stops.  
4. Disconnect lead wires from heating element at  
the contactor terminals.  
9. Install right side panel or front control panel (if  
removed).  
5. Remove mounting nuts from heating element  
and remove the element from boiler.  
HEATING ELEMENTS  
WARNING: DISCONNECT THE  
ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES.  
1. Turn power switch off and allow boiler to  
blowdown/drain.  
2. Open the cabinet base door.  
3. Remove heating element cover then main  
control box cover.  
6. Clean the mating surface on mounting plate  
then install a replacement gasket and heating  
element.  
7. Reverse procedure to install and check for  
proper operation.  
NOTE: When installing heating element, route the  
lead wires between the contactors.  
F25154 (February 2004)  
Page 10 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
6. Loosen both conduit locking nuts (1 1/2" & 3/8")  
HEATING ELEMENT MOUNTING  
in main control box.  
PLATE  
7. Loosen conduit nut (1 1/2") on elbow connected  
to main control box.  
WARNING: DISCONNECT THE  
ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES.  
8. Remove mounting bolts for main control box.  
A. Lift main control box to remove from the  
frame and position it to the left side.  
9. Remove heating element mounting plate.  
1. Remove heating elements as outlined under  
HEATING ELEMENTS.  
2. Loosen mounting hardware securing control  
panel to frame and lower the panel.  
10. To install:  
A. Clean the mating surfaces on heating  
element mounting plate and boiler.  
B. Install new gasket on boiler side of  
mounting flange.  
3. On models with cooking compartments only,  
disconnect power cord from power switch box  
(rear of control panel).  
4. Disconnect pressure gauge tube from fitting at  
tee.  
5. Disconnect lead wire from Aux LLCO probe.  
Page 11 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
C. Position heating element mounting plate  
with mounting studs for the element cover  
at the top.  
NOTE: When installing heating element  
mounting plate, install and tighten the mounting  
bolts as indicated to ensure the mounting plate  
is flush with boiler flange and gasket is evenly  
compressed. If bolt is not threading properly by  
hand, clean out the threads with a 3/8 x 16 tap.  
D. Align mounting holes then press and hold  
heating element mounting plate against the  
gasket. Install two bolts at the top and two  
bolts at the bottom. Hand Tighten Only.  
E. Starting with the bottom bolts, tighten each  
bolt a few turns at a time and alternate  
between the bottom and top bolts.  
RIGHT SIDE VIEW SHOWN  
8. Remove gauge glass as outlined under  
WATER LEVEL GAUGE ASSEMBLY.  
F. Install two bolts at the left and two bolts at  
the right on the heating element mounting  
plate. Tighten each bolt a few turns at a  
time and alternate between the left and  
right bolts.  
9. Disconnect water level probe lead wires.  
10. Remove coil from blowdown/drain valve.  
11. Disconnect boiler fill and cold water condenser  
valve water lines and remove lines.  
G. Install the four remaining bolts. Tighten  
each bolt a few turns at a time and  
alternate between the four remaining bolts.  
11. To complete heating element mounting plate  
installation, reverse procedure from main  
control box removal.  
BOILER ASSEMBLY  
WARNING: DISCONNECT THE  
ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES.  
NOTE: To perform this procedure, the steamer must  
be accessible from all sides.  
1. Turn power switch off and allow boiler to  
blowdown/drain.  
LEFT SIDE VIEW SHOWN  
12. Remove cover from pressure switch control box  
and loosen conduit locking nut.  
2. Turn water supply off.  
3. Remove left and right side panels.  
13. Remove mounting screws for pressure switch  
control box.  
4. Raise steamer from the bottom right side by  
approximately three inches to drain the  
remaining water from boiler. Lower steamer  
when boiler is empty.  
14. Disconnect pressure relief valve drain line at  
the valve.  
15. Disconnect water level probe housing air  
equalization tube and remove tube.  
5. Remove heating element mounting plate as  
outlined under HEATING ELEMENT  
MOUNTING PLATE.  
16. Disconnect water level probe housing drain line  
from condenser drain box.  
6. Disconnect pressure gauge tube from gauge.  
7. Disconnect air equalization tube and remove.  
17. Disconnect boiler drain line from condenser  
drain box.  
F25154 (February 2004)  
Page 12 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
LEFT SIDE VIEW SHOWN  
18. Separate union at boiler drain.  
LEFT SIDE VIEW SHOWN  
19. On models with cooking compartments:  
23. Remove main control box and pressure switch  
control box from boiler base.  
A. Remove the left and right access panels  
between the cooking compartments and  
boiler base.  
24. Remove bolts securing boiler to base frame  
then slide boiler forward to remove.  
B. Disconnect flexible steam supply line from  
boiler tee to cooking compartments and  
remove the line.  
25. Remove all plumbing components from boiler  
and install on replacement boiler.  
26. Install replacement boiler but hand tighten  
mounting bolts only.  
C. Disconnect both drain lines from cooking  
compartments to condenser drain box and  
remove the lines.  
27. To complete boiler installation, reverse  
procedure from main control box and pressure  
switch control box removal.  
20. On models with steam generator base only,  
disconnect steam supply line from boiler tee.  
28. When all connections to boiler are made,  
tighten boiler mounting bolts to secure boiler to  
base frame.  
21. Loosen conduit nut on field connection box and  
slide nut down onto conduit.  
22. Remove cover from field terminal box and  
disconnect lead wires from terminal block.  
29. Check for proper operation.  
DESCALER (Cathodic Protector)  
NOTE: The descalers are accessible only through  
the heating element mounting plate opening in boiler.  
1. Remove heating element mounting plate as  
outlined under HEATING ELEMENT  
MOUNTING PLATE.  
2. Remove the two descalers hanging from the  
front horizontal support rod.  
Page 13 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
5. Adjust the door as outlined in DOOR SEALING  
ADJUSTMENT under COOKING  
COMPARTMENT.  
NOTE: Do not over tighten gasket plate screws as  
this will compress the gasket excessively and  
interfere with proper door sealing.  
NOTE: Damage to the gasket sealing surface, such  
as nicks or cuts, will cause steam leakage.  
3. To install:  
A. On the two replacement descalers, stretch  
the coiled wire (cathode) at the top to  
elongate the wire then form an open loop.  
B. Hang the descalers on the front horizontal  
support rod; one to the left of the heating  
elements and one to the right.  
C. Position the descalers so the core (anode)  
is below the minimum water level in the  
boiler and hanging freely.  
NOTE: To function properly, the descalers must  
not contact the interior surfaces of the boiler or  
the heating elements.  
Handle  
1. Open the door.  
COOKING COMPARTMENT  
DOOR(S)  
2. Remove screws from the top and bottom of the  
door.  
3. Pull the inner door panel out from the door  
housing with the gasket plate and gasket still  
attached.  
Removal  
1. Remove top cover.  
2. Open the door.  
3. Pull hinge rod up.  
4. Reverse the procedure to install, making sure  
the door bushings are in place.  
Gasket  
1. Open the door.  
2. Remove screws from the gasket plate.  
3. Pull the gasket plate out from the door housing  
and remove the gasket.  
4. Position the new gasket on the gasket plate and  
reverse the procedure to install.  
F25154 (February 2004)  
Page 14 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
3. Pull the inner door panel out from the door  
housing with the gasket plate and gasket still  
attached.  
4. Remove the screws from the side edge of the  
door that secure the latch mechanism and  
remove the latch from the door.  
4. Remove the nuts and spacers from the handle  
screws and remove the handle from the door.  
NOTE: When installing, the latch lever must rest on  
top of the handle latch screw.  
5. Reverse procedure to install.  
NOTE: When installing the spacers, the smaller  
diameter fits into the slot in the door and the latch  
lever must rest on top of the handle latch screw.  
NOTE: When installing screws at the top and bottom  
of door, apply thread sealant.  
5. Reverse procedure to install.  
NOTE: When installing screws at the top and bottom  
of door, apply thread sealant.  
Latch Assembly  
1. Open the door.  
2. Remove screws from the top and bottom of the  
door.  
Page 15 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
SERVICE PROCEDURES AND ADJUSTMENTS  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRES ELECTRICAL TEST OR  
MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL  
TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER AND FOLLOW LOCKOUT /  
TAGOUT PROCEDURES, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.  
8. Install descalers (cathodic protectors).  
BOILER  
9. Install heating element mounting plate.  
Inspection  
10. Install heating elements.  
The boiler should be inspected for excessive lime  
scale build-up in a time frame dependant on the  
11. Check for proper operation.  
quality of the local water supply and steamer usage.  
In hard water areas or for steamers heavily used, a  
more frequent interval should be used. This  
inspection consists of an internal examination and  
cleaning of the boiler, an examination of the two  
hanging descalers (cathodic protectors) and for lime  
scale build-up on the water level probes. Also, check  
all boiler controls, including the pressure switches.  
Deliming  
Refer to the water filtration system manual supplied  
with steamer for specific instructions.  
Descaler (Cathodic Protector)  
Two descalers are installed inside the boiler and are  
used as a preventative measure to:  
Reduce scale deposit build-up  
Periodic service must be performed as outlined in  
the BOILER procedures. See WATER  
CONDITIONING under GENERAL.  
Help remove existing scale deposits  
Inhibit boiler and component corrosion  
Clean-Out  
The descaler has a coiled wire (cathode) wrapped  
around a solid cylindrical core (anode) that hangs by  
an open loop from the front horizontal support rod  
inside the boiler.  
1. Turn power switch off and allow boiler to  
blowdown/drain.  
2. Remove heating element mounting plate as  
outlined in REMOVAL AND REPLACEMENT  
OF PARTS.  
The descaler materials serve as a sacrificial anode  
and cathode combination that chemically react with  
the contents of the boiler to meet the three objectives  
outlined above.  
3. Inspect descalers (cathodic protectors) as  
outlined under DESCALER (CATHODIC  
PROTECTOR) in this section.  
4. Remove both descalers from boiler.  
5. Clean interior of boiler using a wire brush or  
equivalent.  
A. Dislodge and remove all loose scale from  
boiler. All loose debris must be removed  
from the boiler.  
B. Remove all loose scale form the heating  
element mounting plate.  
C. Clean the mating surfaces of the heating  
element mounting plate and boiler.  
6. Check boiler drain and drain line plumbing for  
obstructions.  
A. Remove cap and strainer screen from  
strainer body. Separate screen from cap  
and clean debris from screen.  
B. Through the front opening in boiler, flush  
out the boiler and drain line plumbing with  
clean water.  
7. Check probe housing and water level probes for  
scale build-up and clean as necessary.  
F25154 (February 2004)  
Page 16 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
1. Access the descalers (cathodic protectors) as  
WATER LEVEL CONTROLS  
TEST  
outlined in REMOVAL AND REPLACEMENT  
OF PARTS.  
2. Inspect the two descalers hanging in boiler.  
A build-up of lime scale on or near the water level  
sensing probes may cause them to retain moisture  
on the probe surface and can give a false reading.  
Also, a cracked or damaged insulator may give a  
false reading.  
NOTE: As descalers erode over time, the diameter  
decreases while the length increases.  
NOTE: A new descaler is approximately 1 3/8"  
diameter and 3 3/4" long at the core.  
These conditions may cause one or more of the  
following to occur:  
A. If either descaler has increased to  
approximately 6" in length and the core is  
breaking apart (pieces falling off), both  
descalers should be replaced; or on an  
annual basis.  
Boiler no heat  
Boiler no fill  
Boiler overfill  
WATER LEVEL PROBE  
HOUSING BLOWDOWN  
Boiler no fill and dry fire  
NOTE: Dry firing may cause damage to heating  
elements or boiler. If this condition is suspected, the  
affected components should be inspected.  
The water level probe housing fills to the same water  
level in the boiler; and equalizes to the operating  
pressure in the boiler. When the manual ball valve  
on the probe housing assembly is opened, water and  
steam are blown thru this valve and should be visible  
exiting steamer drain. The probe housing blowdown  
should be performed in a time frame dependant on  
the quality of the local water supply and steamer  
usage. In hard water areas or for steamers heavily  
used, a more frequent interval should be used. The  
blowdown procedure is essential to proper operation  
and component life by removing sediment and  
scalants that may be lodged in the probe housing.  
Main Water Level Control  
NOTE: The main water level control is a dual  
functioning control that provides low level cut-off  
protection and differential water level control  
1. Turn power switch on and verify:  
A. Low water light is lit (front control panel).  
B. HL LED is lit on the water level control  
board.  
C. Boiler is filling with water.  
1. Turn power switch on and allow boiler to  
completely fill (approximately 1" of water visible  
in sight glass).  
D. If boiler isn’t filling with water:  
1) Verify 120VAC to boiler fill valve.  
2. Press reset switch to begin heating and allow  
boiler to reach operating pressure.  
2) Verify water supply is on and boiler fill  
valve isn’t clogged.  
3. Remove left side boiler base panel to access  
the manual ball valve.  
2. At the end of the initial fill:  
A. Verify approximately 1" of water visible in  
sight glass.  
WARNING: THE STEAMER AND ITS PARTS ARE  
HOT. USE CARE WHEN OPERATING, CLEANING  
OR SERVICING THE STEAMER. THE BOILER  
CONTAINS LIVE STEAM. STAY CLEAR WHEN  
OPENING THE VALVE.  
B. Verify green ready light is lit (front control  
panel).  
C. Verify HL LED is not lit and LLCO LED is lit  
on the water level control board.  
4. Open the ball valve for approximately one  
minute while under pressure to thoroughly flush  
the probes and housing.  
3. Open the ball valve on probe housing assembly  
(boiler left side) about half way. This will allow  
boiler water to drain slowly and activate a fill  
cycle. Do not press the reset switch to start  
heating. The next step requires a visual sight  
glass measurement that cannot be obtained if  
there is boiling action in the vessel.  
5. Close the ball valve and replace left side panel.  
6. Press reset switch to resume heating and allow  
boiler to reach operating pressure.  
7. Steamer is ready for use.  
A. Verify water level in sight glass drops 1/4"  
to 3/8" before a fill cycle is initiated. Repeat  
at least twice to verify correct fill.  
B. If proper fill wasn’t obtained:  
Page 17 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
1) Verify wire color connections are  
correct at probe numbers 50, 51 & 52,  
and at the water level control board.  
A. Turn power switch on and allow boiler to  
fill. Do not press the reset switch to start  
heating.  
2) Turn power switch off.  
B. Turn water supply off and open the ball  
valve on probe housing assembly. This will  
allow boiler water to drain.  
3) Remove probe assembly, clean lime  
scale build-up from the probes and  
compare probe lengths to drawing.  
C. When water level is no longer visible in  
sight glass and is below LLCO probe;  
LLCO LED should turn off, LLCO relay  
should de-energize and return LLCO relay  
contacts to there shelf state.  
D. Repeat at least twice to verify correct  
LLCO operation.  
Auxiliary Low level Cut-Off Control  
5. Turn power switch off.  
6. Disconnect lead wire from Aux LLCO probe.  
4) Disconnect 3/8” flexible line (air  
equalization tube) from probe housing  
assembly and from boiler tee. Check  
flex line for obstructions and remove  
as necessary.  
5) Disconnect 3/8” flexible line (pressure  
switch tube) from boiler tee. Remove  
boiler tee and check for obstructions  
in the tee and in the mounting hole.  
Remove obstructions as necessary.  
NOTE: When replacing, boiler tee must be  
mounted vertical to prevent a blockage due  
to condensate build-up.  
A. Set VOM to read resistance (ohms) and  
connect meter leads to Aux LLCO probe  
and boiler. If there is any measurable  
resistance, remove and clean the Aux  
LLCO probe.  
B. Replace the probe and check resistance  
again. If resistance is still present, install a  
replacement probe.  
C. Verify resistance measurement with new  
probe installed.  
7. Turn power switch on and allow boiler to begin  
filling. Do not press the reset switch to start  
heating.  
8. With water below the lowest visible level in sight  
glass (below Aux LLCO probe) and boiler in  
initial fill state:  
A. Verify Aux LLCO LED is not lit on the Aux  
water level control board.  
4. Test LLCO circuit on water level control board.  
F25154 (February 2004)  
Page 18 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
B. Verify Low Water light is lit (front control 3. Press reset switch and verify high pressure light  
panel).  
turns off.  
C. Verify 120VAC is on Aux LLCO COM, and  
0 volt is on Aux LLCO N.O. contacts.  
4. When green ready light comes on, press reset  
switch to begin heating (low water light turns  
off).  
9. When water level reaches Aux LLCO probe as  
boiler continues to fill:  
A. Allow boiler to fully pressurize. Cycling  
pressure switch opens and heating stops.  
A. Verify Aux LLCO LED is lit on the auxiliary  
low water board.  
5. Turn one cooking compartment timer on to  
exhaust steam from boiler.  
B. Verify the green ready light is lit (front  
control panel).  
6. Monitor boiler pressure gauge for two complete  
cycles. Note pressure at which the heat comes  
on and goes off.  
C. Verify 120VAC is on the Aux LLCO  
common and normally open contacts of the  
auxiliary water level control board.  
The heat should come on at 10 PSI and go off  
at 12 PSI.  
10. Open the ball valve on probe housing assembly.  
This will allow boiler to drain.  
A. If pressure readings differ, continue with  
procedure to adjust.  
11. When water level is no longer visible in sight  
glass and is below LLCO probe; Aux LLCO  
circuit should activate.  
7. Two pressure adjustment screws extend  
through the top of switch cover. A clockwise  
rotation increases pressure; a counter-  
clockwise rotation decreases pressure.  
A. Low water light turns on (front control  
panel).  
A. Turn the adjustment screw above right side  
pointer to obtain the proper cut-out (off)  
pressure setting.  
B. Aux LLCO led turns off on the auxiliary low  
water board.  
C. Press reset switch to verify lockout  
condition. Low water light should remain  
on.  
B. Turn the adjustment screw above the left  
side pointer to obtain the proper cut-in (on)  
pressure setting.  
D. If lockout condition does not occur,  
NOTE: The screw directly above the right side  
pointer adjusts cut-out (off) and cut-in (on) set  
points without changing the differential. The  
screw directly above the left side pointer adjusts  
cut-in (on) set point and changes the  
differential.  
immediately turn power switch off.  
1) Disconnect power to machine.  
2) Replace auxiliary low level cut-off  
control and check for proper  
operation.  
8. Monitor boiler pressure gauge for two complete  
cycles and note the pressure at which the heat  
comes on and goes off.  
E. If lockout condition is ok, verify the auxiliary  
water level control circuit is functioning  
properly.  
A. If pressures are correct, pressure switch is  
properly adjusted.  
F. Close the ball valve on probe housing  
assembly and allow boiler to fill.  
B. If pressures are not correct, repeat the  
adjustment for up to three attempts.  
1) Verify low water light turns off (front  
control panel).  
9. If the above adjustment cannot be obtained,  
install a replacement pressure switch and adjust  
pressure settings as outlined in this procedure.  
2) Press the reset switch and verify  
auxiliary contactors A & C are  
energized and boiler is heating.  
CYCLING PRESSURE SWITCH  
ADJUSTMENT  
1. Access cycling pressure switch as outlined  
under PRESSURE SWITCH CONTROL BOX  
COMPONENTS in REMOVAL AND  
REPLACEMENT OF PARTS.  
2. Turn power switch on (boiler begins to fill).  
Page 19 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
NOTE: For every click of the adjustment wheel,  
the pressure setting is changed approximately  
1/8 PSI.  
HIGH LIMIT PRESSURE  
SWITCH ADJUSTMENT  
NOTE: Make the adjustment in small  
increments.  
NOTE: Before the high limit pressure switch can be  
adjusted, the cycling pressure switch must be  
temporarily removed from the boiler control circuit.  
This allows the boiler to pressurize above the normal  
operating range. After the high limit pressure switch  
is properly adjusted, the cycling pressure switch  
must be returned to its normal operating  
condition. Follow the procedure as outlined in the  
steps below.  
7. After adjusting high limit pressure switch, the  
boiler pressure must be reduced to check the  
pressure setting.  
A. Remove left side boiler base panel to  
access the manual ball valve on the probe  
housing assembly.  
WARNING: THE STEAMER AND ITS PARTS ARE  
HOT. USE CARE WHEN OPERATING, CLEANING  
OR SERVICING THE STEAMER. THE BOILER  
CONTAINS LIVE STEAM. STAY CLEAR WHEN  
OPENING THE VALVE.  
1. Access cycling pressure switch as outlined  
under PRESSURE SWITCH CONTROL BOX  
COMPONENTS in REMOVAL AND  
REPLACEMENT OF PARTS.  
A. Remove cover from cycling pressure  
switch.  
B. Open the manual ball valve to release  
boiler pressure and monitor the boiler  
pressure gauge.  
B. Connect a jumper wire between the two  
electrical terminals to temporarily remove  
the cycling pressure switch from the boiler  
control circuit.  
NOTE: High limit pressure switch resets at  
approximately 12 PSI (not adjustable).  
C. When pressure is reduced to  
2. Reconnect power to machine and turn power  
switch on (boiler begins to fill).  
approximately 8 PSI, close the ball valve.  
D. Press reset switch to reset the high  
pressure safety circuit and begin heating  
(high pressure light turns off).  
3. Press reset switch and verify high pressure light  
turns off.  
4. When green ready light comes on, press reset  
switch to begin heating (low water light turns  
off).  
8. Monitor boiler pressure gauge and note the  
pressure at which the high limit pressure switch  
opens.  
NOTE: A pressure relief valve with a 15 PSI setting,  
serves as back-up to the high limit pressure switch.  
A. If pressure is correct, the high limit  
pressure switch is properly adjusted.  
5. Monitor boiler pressure gauge. Note pressure at  
which the high limit pressure switch opens (high  
pressure light turns on).  
B. If pressure is not correct, repeat the  
adjustment for up to three attempts.  
9. If the above adjustment cannot be obtained,  
install a replacement high limit pressure switch  
and adjust as outlined in this procedure.  
The switch should open at boiler pressures no  
less than 14.5 PSI but no greater than 15.0 PSI  
(MAX).  
10. After the high limit pressure switch is properly  
adjusted, disconnect power to machine and  
allow boiler to blowdown/drain.  
A. If pressure reading differs, continue with  
procedure to adjust.  
CAUTION: While making the adjustment, do not  
press on the wheel with extreme force. The  
switch may rotate and develop a leak at the  
compression fittings or in some cases, the rear  
lead wire may touch the control box and create  
an electrical short.  
11. Remove jumper wire from cycling pressure  
switch to return the switch to its normal  
operating condition.  
12. Check for proper operation.  
BOILER FILL AND COLD WATER  
CONDENSER SOLENOID VALVES  
6. Turn adjustment wheel to change high limit  
pressure switch setting.  
A. A counterclockwise rotation lowers the  
pressure switch set point; a clockwise  
rotation raises the pressure switch set  
point.  
1. Access boiler fill and cold water solenoid valves  
as outlined under PRESSURE SWITCH  
CONTROL BOX COMPONENTS in REMOVAL  
AND REPLACEMENT OF PARTS.  
2. Turn power switch on (boiler begins to fill).  
F25154 (February 2004)  
Page 20 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
3. To check boiler fill valve:  
NOTE: If internal solenoid parts appear to be  
damaged or worn, then replace the solenoid valve.  
Do not reuse damaged or worn parts. No internal  
solenoid parts are available as a service  
replacement.  
A. Verify 120VAC to solenoid valve coil.  
B. If voltage is correct but valve is not opening  
(little or no water flow), turn power switch  
off and disconnect power to machine.  
A. Check rubber seal on bottom of plunger.  
B. Check plunger spring.  
1) Remove lead wires from coil and  
check for continuity.  
C. Check O-ring in valve body.  
D. Check ports in valve body.  
2) If no continuity is measured, install a  
replacement solenoid valve and check  
for proper operation.  
3) If continuity is measured, the coil is  
good.  
C. If voltage is not correct, check main water  
level control board as outlined under  
WATER LEVEL CONTROLS TEST.  
4. To check cold water condenser valve:  
NOTE: Valve should energize only during cooking  
cycles and at boiler blowdown/drain.  
A. Verify 120VAC to solenoid valve coil.  
11. Reverse procedure to install and check for  
proper operation.  
B. If voltage is correct but valve is not opening  
(little or no water flow), turn power switch  
off and disconnect power to machine.  
COLD WATER CONDENSER  
THERMOSTAT ADJUSTMENT  
1) Remove lead wires from coil and  
check for continuity.  
During a cooking cycle or boiler blowdown/drain, the  
cold water condenser thermostat (N.O.) should  
close and energize the cold water condenser  
solenoid valve. The water from spray nozzle mixes  
with the drain water in the condenser drain box to  
reduce drain water temperature and condense  
steam vapors.  
2) If no continuity is measured, install a  
replacement solenoid valve and check  
for proper operation.  
3) If continuity is measured, the coil is  
good. Continue with procedure for  
additional valve checks.  
C. If voltage is not correct, check cold water  
condenser thermostat as outlined under  
COLD WATER CONDENSER  
If excessive steam vapors are seen exiting the drain,  
adjust the cold water condenser thermostat as  
outlined below.  
THERMOSTAT ADJUSTMENT.  
1. Turn power switch off and allow boiler to  
blowdown/drain.  
5. To check valve ports for clogs or valve  
component malfunction, continue with  
procedure for disassembly and inspection of  
internal components.  
2. Access cold water condenser thermostat as  
outlined under PRESSURE SWITCH  
CONTROL BOX COMPONENTS in REMOVAL  
AND REPLACEMENT OF PARTS.  
6. Turn water supply off, disconnect water line  
from valve body then remove solenoid valve.  
3. Turn thermostat shaft fully counterclockwise to  
energize the cold water condenser solenoid  
valve.  
7. Remove coil assembly from valve stem  
8. Secure the valve body to keep it from turning.  
A. Allow cold water to flow until condenser  
drain box has completely cooled.  
9. Scribe a line on stem nut to valve body for  
proper re-tightening then remove stem locking  
nut and remove the stem from valve body.  
B. Slowly turn thermostat shaft clockwise until  
thermostat opens and de-energizes the  
solenoid valve. Turn shaft an additional 1/4  
turn to prevent the thermostat from closing  
near room ambient temperatures.  
10. All parts are now accessible for inspection and  
cleaning.  
4. Check for proper operation.  
Page 21 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
HEATING ELEMENT TEST  
COOKING COMPARTMENT  
NOTE: Before proceeding with intake shut-off valve  
adjustment, monitor boiler pressure gauge and verify  
boiler is operating between 10-12 PSI. If boiler  
pressure adjustment is necessary, refer to CYCLING  
PRESSURE SWITCH ADJUSTMENT.  
KW PER  
ELEMENT ELEMENT  
AMPS PER  
OHMS PER  
ELEMENT  
VOLTAGE  
208  
240  
9.0  
9.0  
14.4  
12.5  
6.3  
14.4  
19.2  
76.8  
12.4  
10.8  
14.4  
57.6  
Intake Shut-Off Valve Adjustment (Steam Flow)  
1. Remove right side compartment panel.  
480  
9.0  
208  
10.5  
12.0  
12.0  
12.0  
16.9  
19.3  
16.7  
8.3  
2. Allow boiler to fully pressurize (heat turns off).  
208  
NOTE: The intake shut-off valve adjustment should  
be made while boiler pressure is at the upper cycling  
limit.  
240  
480  
3. Turn both cooking compartment timers on.  
4. Open the intake shut-off valve completely.  
1. Values in the table are nominal.  
Tolerance is +5/-10%.  
NOTES:  
2. Voltage values are @ 60HZ.  
5. Slowly begin to close the intake shut-off valve  
and monitor manifold pressure gauge. Adjust  
the valve until manifold pressure gauge reading  
is between 8-10 PSI.  
3. Resistance values (ohms) are @ room  
temperature. If heating elements are  
above room temperature, the measured  
resistance will be greater.  
4. Each heating element has 3 separate  
internal elements.  
1. Access the heating elements as outlined in  
REMOVAL AND REPLACEMENT OF PARTS.  
2. Measure voltage at heating element terminals  
and verify it against data plate voltage.  
A. If voltage is incorrect, see  
TROUBLESHOOTING.  
B. If voltage is correct, continue with  
procedure.  
3. Check current draw (amps) through the heating  
element lead wires.  
NOTE: Checking current draw is the preferred  
method over a resistance check when a clamp on  
type amp meter is available.  
A. If current draw is correct then heating  
element is functioning properly. See table  
for proper values.  
B. If current draw is not correct, turn power  
switch off and disconnect the electrical  
supply.  
6. Monitor manifold pressure gauge reading for  
two complete boiler cycles.  
1) Install a replacement heating element.  
A. If the manifold pressure gauge reading  
stays within tolerance while the boiler is  
cycling, the intake shut-off valve is set  
correctly.  
C. If unable to check current draw, a  
resistance check may indicate a  
malfunctioning element.  
1) Turn power switch off and disconnect  
power to machine.  
B. If the manifold pressure gauge reading is  
outside of the tolerance repeat the  
adjustment.  
2) Remove lead wires from heating  
element and check resistance (ohms).  
See table for proper values.  
7. Once the steam supply manifold pressure is set  
correctly, turn both cooking timers off and install  
right side compartment panel.  
4. Check for proper operation.  
F25154 (February 2004)  
Page 22 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
3. Open door and check the door strikers’ slot for  
Door Sealing Adjustment  
horizontal alignment. The slot on door striker  
must be kept horizontal for the door latch to  
1. Check door gasket condition. If damaged or  
worn, replace as outlined under COOKING  
COMPARTMENT DOOR(S) in REMOVAL AND  
REPLACEMENT OF PARTS.  
catch on the door strikers slot and latch.  
<
2. Loosen screws until the screw heads no longer  
touch gasket plate.  
3. Tighten screws until the screw heads touch  
gasket plate and begin counting turns. Tighten  
all screws approximately two turns.  
4. Close the door and check for proper operation.  
A. If necessary, tighten all screws an  
additional 1/2 turn.  
B. Repeat as necessary, tightening all screws  
by 1/2 turn until the door closes properly  
and no steam leaks are seen around  
gasket seal.  
Door Latch Adjustment  
Should cooking compartment door jam and cannot  
be opened, do not force or pry the door or damage  
may occur.  
Lift bottom of door at the handle end to disengage  
latch. If door does not release, remove the right side  
panel to access door striker.  
4. Place a cloth over the door striker to protect the  
slot. Secure the door striker close to its base to  
keep it from turning and tighten striker nut.  
The door striker mounting nut is located behind the  
front panel of cooking cavity. Remove striker nut  
from striker to release door.  
NOTE: Do not over tighten as the striker will begin to  
turn and change alignment.  
5. Check for proper operation.  
Remove any burrs on door striker that may cause  
door latch to stick. Reinstall door striker and adjust  
as outlined below.  
CAUTION: When installing, do not damage the  
slot in the door striker or door may not latch  
properly.  
To adjust:  
1. Reinstall door striker with the slot pointing up  
and hand tighten striker nut only.  
2. Close door to center the door striker in the oval  
mounting hole.  
Page 23 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
ELECTRICAL OPERATION  
COMPONENT FUNCTION  
CABINET BASE BOILER CONTROLS  
Power Switch . . . . . . . . . . . . . . . . Controls 120VAC to the boiler control circuit.  
Reset Switch (Manual) . . . . . . . . . Resets the low water level safety circuit on initial startup or the occurrence of  
a low water condition. Also, resets the high pressure level safety circuit on  
initial startup or the occurrence of a high pressure condition which allows  
heating to start.  
Boiler Fill Valve . . . . . . . . . . . . . . . Allows water flow to the boiler when energized thru HL-3 contacts on the  
water level control.  
Cold Water Condenser  
Valve . . . . . . . . . . . . . . . . . . . . . . . Allows cold water to spray thru a nozzle inside the condenser drain box to  
condense steam and cool the hot water before discharging into the drain.  
Cold Water Condenser  
Cycling Thermostat . . . . . . . . . . . Regulates cold water spray inside the condenser drain box during a cooking  
cycle or boiler blowdown/drain.  
Cycling Pressure Switch . . . . . . . Regulates boiler pressure between cut-out (off) and cut-in (on) pressure  
settings of switch.  
High Limit Pressure Switch . . . . . Prevents boiler from reaching pressures above 15 PSI by removing power  
from heating circuit. The high limit automatically resets at approximately 12  
psi (green ready light on).  
Main Water Level Control . . . . . . A dual function control that allows water to fill and maintain the proper level  
in the boiler, providing differential level control; and removes power from  
heating circuit if water level drops too low, providing low level cut-off  
protection. The control uses three different probe lengths to monitor water  
level (high level HL, low level LL, low level cut-off LLCO).  
Auxiliary Water Level Control . . . A back up to the low level cut-off on the main water level control. Protects  
boiler and heating system components from a low water cut-off condition by  
opening the 120VAC voltage path to the heating circuit. The control uses a  
single probe to monitor water level (auxiliary low level cut-off Aux LLCO).  
Relay Board . . . . . . . . . . . . . . . . . . Provides a centralized location for wire harness connections and power  
transfer thru board relays (K1-K4) to the steamer controls. Also, provides  
voltage test points (T1-T7) for verifying voltage to relay coils, N.O. relay  
contacts closed, control panel lights and auxiliary contactor coils.  
NOTE: The relay’s below are mounted on the relay board and are individually replaceable.  
K1 Relay . . . . . . . . . . . . . . . . . . . . Energized when water level reaches the Aux LLCO probe (water level  
condition satisfied).  
K2 Relay . . . . . . . . . . . . . . . . . . . . Energized when high limit pressure switch is closed (high limit pressure  
condition satisfied). When K1 & K2 are energized, ready light (green) will be  
on.  
K3 Relay . . . . . . . . . . . . . . . . . . . . Energized when K1(2) N.O. contacts close and reset switch is activated.  
When K3 is energized, K3(2) N.O. contacts close and low water light turns  
off.  
K4 Relay . . . . . . . . . . . . . . . . . . . . Energized when K2(2) N.O. contacts are closed and reset switch is  
activated. When K4 is energized, K4(2) N.O. contacts close and high  
pressure light turns off. When K3 and K4 are energized, power is supplied to  
auxiliary contactors A & C.  
F25154 (February 2004)  
Page 24 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Supply Voltage Transformer . . . . Provides 120VAC to the boiler control and cooking compartment control  
circuits.  
Cycling Contactors B & D . . . . . . Supplies line voltage to one side of heating elements thru cycling pressure  
switch N.C. contacts and LLCO-1 N.O. contacts.  
Auxiliary Contactors A & C . . . . . Supplies line voltage to energize the heating elements thru relay K3 & K4  
N.O. contacts.  
Heating Elements . . . . . . . . . . . . . Heats water in boiler to generate steam.  
Blowdown/Drain  
Solenoid Valve . . . . . . . . . . . . . . . N.O. valve that closes when energized by the power switch to allow boiler to  
fill and pressurize. When de-energized, valve opens to blowdown and drain  
the boiler contents.  
COOKING COMPARTMENT CONTROLS  
The upper section of the steamer consists of two separate cooking compartments. Each compartment functions  
independently with its own set of controls. Power is supplied to the controls only after the steam pressure rises  
above the compartment pressure switch setting to close the N.O. contacts.  
Ready Light (Green) . . . . . . . . . . . When lit, indicates steamer is ready to cook.  
Cooking Light (Red) . . . . . . . . . . . When lit, indicates steamer is in a cooking cycle.  
Cooking Timer . . . . . . . . . . . . . . . Use to set cooking time between 0-60 minutes. When timer is set, energizes  
the steam solenoid valve to allow steam into the cooking compartment.  
When time expires, energizes buzzer until turned off.  
Buzzer . . . . . . . . . . . . . . . . . . . . . . Signals end of a cook cycle, must be turned off manually.  
Door Switch . . . . . . . . . . . . . . . . . Removes power to cooking timer. If time is dialed on cooking timer and  
compartments are steaming, removes power to steam solenoid valve when  
compartment door is opened.  
Steam Solenoid Valve . . . . . . . . . When energized, opens to allow steam into the cooking compartment  
(normally closed valve).  
Compartment Pressure Switch . . Supplies power to cooking compartment controls, after steam pressure rises  
above approximately 3 psi to close the pressure switch. The pressure switch  
remains closed as long as steam pressure is above the stated pressure.  
Page 25 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
COMPONENT LOCATIONS  
Boiler Base Controls  
F25154 (February 2004)  
Page 26 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Boiler Base Controls Continued  
Page 27 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Cooking Compartment Controls  
F25154 (February 2004)  
Page 28 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
When the water level drops below the low level (LL)  
WATER LEVEL CONTROLS  
probe, power is removed from the inverse latching  
relay, the HL relay energizes through ILR-2 and HL  
contacts change state. The boiler fill solenoid is  
energized through HL-1 to refill the boiler and the HL  
LED is lit. The HL relay and LED will toggle on and  
off during a cooking cycle as needed.  
Low Level Cut-Off & Differential Control  
The steamer is equipped with three water level  
sensing probes (high, low and low level cut-off) and  
a water level control board. The water level control  
board performs two functions: 1) Provide low level  
cut-off protection to shut off the heat source in case  
the water level drops below the low level cut-off  
(LLCO) probe. 2) Perform as a differential level  
control to maintain the water level between the low  
and high water level probes.  
The water level control (WLC) board has input  
voltage (120VAC) across terminals 11 and 12 which  
powers the primary side of the transformer. On one  
side of the transformer secondary, power is provided  
to the control by a series path through chassis  
ground (terminal 10). The other side of the  
transformer secondary (12VAC) is attached to the  
probe that directs power to the other side of WLC  
board relay coils (LLCO and HL) and to the inverse  
latching relay (ILR) electronic circuit on the WLC  
board. As water enters the boiler, it becomes part of  
the WLC board circuit. When the water level in the  
boiler reaches a probe, that circuit is completed.  
The inverse latching relay of the WLC board is de-  
energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.)  
contacts in their shelf state.  
When the main power switch is turned on, power is  
supplied to the WLC board which energizes the high  
level (HL) relay, closes HL-1 normally open contacts,  
and illuminates the HL relay LED. With the HL-1  
contacts closed, the boiler fill solenoid is energized  
and water begins filling the boiler.  
When the water level reaches the low level cut-off  
(LLCO) probe, the LLCO relay is energized and  
illuminates the LLCO LED. With the LLCO-1 contacts  
closed, the heat source can be energized provided  
the auxiliary control(s) in the heating circuit are  
satisfied. The LLCO relay will remain energized and  
its LED will stay lit until the water level in the boiler  
drops below the LLCO probe.  
When the water level reaches the low level (LL)  
probe, power to terminal 2 on the WLC board is  
present but no switching occurs.  
After the water level reaches the high level (HL)  
probe, the inverse latching relay of the WLC board is  
energized and locked through the low level probe  
(LL) and ILR-1 contacts. With ILR-2 contacts open,  
HL relay is de-energized and the HL LED goes out.  
With the HL-1 contacts open, the boiler fill solenoid is  
de-energized, stopping the flow of water into the  
boiler.  
Page 29 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Auxiliary Low Level Cut-Off  
This control serves as a safety backup to the main  
water level control (WLC) board to meet CSD-1 code  
requirements. The operation of the auxiliary control  
board is identical to the low level cut-off (LLCO)  
function of the main WLC board but performs a  
single function: 1) Provide auxiliary low level cut-off  
protection to shut off the heat source in case the  
water level drops below the auxiliary low level cut-off  
(Aux LLCO) probe. A single Aux LLCO probe,  
identical to the LLCO probe on the main WLC board,  
is connected to the auxiliary control.  
The auxiliary control board has input voltage  
(120VAC) across terminals 11 and 12 which powers  
the primary side of the transformer. On one side of  
the transformer secondary, power is provided to the  
control by a series path through chassis ground  
(terminal 10). The other side of the transformer  
secondary (12VAC) is attached to the Aux LLCO  
probe that directs power to the other side of the  
auxiliary control board relay (LLCO). As water enters  
the boiler, it becomes part of the auxiliary water level  
control’s circuit. When the water level in the boiler  
reaches the Aux LLCO probe, the circuit is  
completed.  
When the main power switch is turned on, power is  
supplied to the auxiliary control board but no  
switching occurs. Also, the low water level indicator  
light (amber) on the boiler base control panel comes  
on.  
When the water level reaches the auxiliary low level  
cut-off (Aux LLCO) probe, the LLCO relay is  
energized (LLCO-1 close) and the LLCO LED lights  
up. The LLCO relay will remain energized and its  
LED will stay lit until the water level in the boiler  
drops below the Aux LLCO probe.  
When the boiler stops filling, press the manual reset  
switch on the boiler base control panel. This turns off  
the low water light and energizes the heat source.  
F25154 (February 2004)  
Page 30 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
RELAY BOARD  
Layout, Legend & Diagnostic Test Points  
The relay board provides a centralized location for wire harness connections and power transfer through board  
relays (K1-K4) to the other steamer controls. Also, provides for condition or component troubleshooting by utilizing  
seven voltage test points (T1-T7) on the board to verify the voltage status for the condition or component in the  
operating sequence. When the condition for the component<s voltage measurement is satisfied or activated,  
120VAC can be measured between T1 (ref.) and T2 thru T7 test points to indicate whether the condition or  
component is receiving voltage to energize and operate. If the voltage is not present, then the condition or  
component has not been energized or is not activated.  
Page 31 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Schematic  
F25154 (February 2004)  
Page 32 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
I.  
120VAC to common terminal on WLC  
LLCO-1 contacts thru cycling pressure  
switch (N.C.).  
SEQUENCE OF OPERATION  
Refer to schematic diagram AI1385 for the electrical  
sequence of operation.  
3. Water level reaches LLCO probe for the main  
water level control and AUX LLCO probe for the  
auxiliary water level control.  
Initial Fill and Preheat  
1. Conditions.  
A. LLCO relay on water level control  
energizes, LLCO-1 contacts (N.O.) close  
A. Boiler connected to correct supply voltage  
and is properly grounded.  
1)  
LED on board lights.  
1) Supply voltage transformer energized  
and 120VAC is output from  
2) Cycling contactors B & D energized.  
Heating elements remain de-  
energized until manual reset switch  
pressed.  
transformer secondary.  
2) 120VAC to compartment controls and  
one side of the power switch.  
B. AUX LLCO relay on AUX water level  
control energizes, AUX LLCO-1 contacts  
(N.O.) close.  
B. Power switch off.  
C. Cycling pressure switch closed.  
D. High limit pressure switch closed.  
1) LED on board lights.  
2) K1 is energized thru AUX LLCO-1  
N.O. contacts.  
E. Cold water condenser (CWC) thermostat  
open.  
a. K1(1) N.O. and K1(2) N.O. close.  
F. Automatic blowdown/drain valve (A.B.D.)  
open and boiler empty.  
b. Ready light on manual reset  
switch lit thru K1(1) N.O.  
contacts.  
G. Water supply valve(s) on.  
2. Turn power switch on.  
NOTE: The LLCO and AUX LLCO relays will  
remain energized and LLCO LED’S will remain  
lit until the water level drops below the LLCO  
probes or the power switch is turned off.  
A. Automatic blowdown/drain valve (N.O.) is  
energized and closes.  
B.  
Water level control (WLC) energized.  
NOTE: The manual reset switch could be  
pressed to energize the heating elements but  
it’s preferred to let the boiler fill the to the high  
level before continuing.  
1) High level (HL) relay energized, HL-3  
N.O. contacts close.  
a. Boiler fill solenoid energized,  
water begins filling the boiler (fill  
time 4-11 min.).  
4. Water reaches LL (low level) probe.  
5. Water reaches HL (high level) probe.  
A. Boiler fill solenoid is de-energized.  
B. HL LED goes out.  
2) LLCO-1 N.O. contacts remain open.  
3) HL LED lit.  
C. Auxiliary water level control (AUX WLC)  
energized.  
6. Manual reset switch pressed.  
A. K3 is energized.  
1) AUX LLCO-1 N.O. contacts remain  
open.  
NOTE: Relay K3 remains energized through  
D. 120VAC to common relay terminal on  
K1(1) N.O., K3(1) N.O., K3(1) N.C., K3(2)  
N.O. , K4(1) N.O., K4(1) N.C contacts.  
K3(1) N.O. latching circuit.  
1) K3(1) N.O. contacts close and K3(1)  
N.C. contacts open.  
E. Low Water light lit thru K3(1) N.C.  
F. High Pressure light lit thru K4(1) N.C.  
2) Low water light goes out.  
3) K3(2) N.O. contacts close.  
G. K2 energized through the high limit  
pressure switch (N.C.).  
a. 120VAC to common side of  
K4(2) N.O. contacts.  
1) K2 contacts K2(1) N.O. & K2(2) N.O.  
close, no power transferred.  
B. K4 is energized.  
NOTE: Relay K4 remains energized through  
K4(1) N.O. latching circuit.  
H. 120VAC to common terminal on AUX  
LLCO-1 contacts.  
Page 33 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
1) K4(1) N.O. contacts close and K4(1)  
2) Boiler fill valve is de-energized.  
3) HL LED goes out.  
N.C. contacts open.  
2) High pressure light goes out.  
3) K4(2) N.O. contacts close.  
4. The water refill cycle will occur whenever the  
water level is below the low level probe and will  
not affect the operation of either the preheat or  
cook cycle.  
a. AUX contactors A & C energized,  
heating elements powered.  
Boiler Blowdown/drain  
NOTE: As boiler heats up and builds  
pressure, some by-pass water/steam  
is produced which runs into the steam  
drain box. This causes the cold water  
condenser (CWC) solenoid to cycle,  
cooling the drain water and  
1. Power switch turned off.  
A. Automatic blowdown valve (N.O.) is de-  
energized and valve opens to drain the  
boiler.  
condensing any steam vapors before  
exiting the drain. The CWC solenoid is  
powered through the CWC cycling  
thermostat.  
B. Power is removed from all components  
except cold water condenser (CWC)  
thermostat and solenoid valve. The CWC  
thermostat cycles as necessary to lower  
the discharge temperature of the water and  
condense steam going into the drain.  
7. Boiler steam pressure reaches upper limit set  
point of 12 PSI (Approx. 15 minutes).  
COOKING COMPARTMENT CONTROLS  
1. Conditions.  
A. Cycling pressure switch opens.  
1) Cycling contactors B & D de-  
energized and power is removed from  
heating elements.  
A. Doors shut (closes the N.O. door switch  
contacts).  
8. Boiler steam pressure drops below lower limit  
set point of 10 PSI and the cycling pressure  
switch closes.  
B. Cooking timers off.  
C. Compartment pressure switch contacts  
open.  
A. Cycling pressure switch continues to cycle  
between the upper and lower set point  
limits. This energizes and de-energizes the  
heating elements to maintain pressure in  
the boiler.  
2. With boiler at operating pressure.  
A. Cooking compartment pressure switch  
closes (approx. 3 PSI).  
1) Cooking compartment ready light  
(green) comes on.  
This sequence continues until one of the  
following occurs:  
3. Start a cook cycle.  
1) Power switch is turned off.  
A. Insert product into steamer and close door.  
B. Set a cook time.  
2) Boiler water level drops below the  
LLCO probe for the main water level  
control and the AUX LLCO probe for  
the auxiliary water level control.  
NOTE: On initial startup, if a cooking timer is set  
immediately after the ready light comes on,  
steam solenoid chattering will be heard (oil  
canning) and the ready lights will flash for  
several seconds. This condition is caused by  
the manifold steam pressure being on the fringe  
of the pressure switch set point. When a cook  
timer is set, the compartment steam solenoid  
valve opens causing the manifold steam  
pressure to drop, slightly below the pressure  
switch set point. At the same time, steam  
pressure is still increasing in the boiler. This  
opposing condition causes a pressure bounce  
to occur. After the steam pressure passes  
approximately 4 psi this condition subsides.  
During normal operation, this condition will not  
be seen.  
3) Boiler pressurizes to 15 PSI, causing  
the high limit pressure switch to open.  
Water Refill (After Initial Fill)  
1. Water level drops below low level probe (LL).  
A. HL relay is energized.  
1) HL-3 (N.O.) contacts close.  
2) Boiler fill valve is energized.  
3) HL LED comes on.  
2. Water reaches LL (low level) probe.  
3. Water reaches high level probe.  
A. HL relay is de-energized.  
C. Contacts 1/3 of cook timer close and timer  
motor is energized.  
1) HL-3 (N.O.) contacts open.  
F25154 (February 2004)  
Page 34 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
1) Compartment steam solenoid valve  
energized and steam begins to enter  
the compartment.  
2) Ready light (green) goes out and  
Cooking light (red) comes on.  
NOTE: Steam should not be seen entering  
either compartment until a cook time is set.  
This energizes the steam solenoid valve of  
the cooking compartment to allow steam  
flow.  
4. Time expires on timer.  
A. Timer contacts 1/3 open, timer motor de-  
energized.  
B. Steam solenoid valve de-energizes,  
stopping the flow steam into compartment.  
C. Timer contacts 4/1 close and energize  
buzzer until manually turned off.  
D. Cooking light (red) goes out and Ready  
light (green) comes on.  
5. Timer manually turned off.  
A. Contacts 1/4 open.  
B. Alarm Buzzer de-energized and stops  
buzzing.  
6. Steamer reverts to preheat cycle until time is  
dialed on timer and the door is shut, water level  
drops below low level cut-off probe or the power  
switch is turned off.  
Page 35 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
SCHEMATICS  
Boiler Base Controls  
F25154 (February 2004)  
Page 36 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Cooking Compartment Controls  
Page 37 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
WIRING DIAGRAMS  
Boiler Base Controls  
F25154 (February 2004)  
Page 38 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Page 39 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Heating Element Circuits  
F25154 (February 2004)  
Page 40 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - ELECTRICAL OPERATION  
Cooking Compartment Controls  
Page 41 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
TROUBLESHOOTING  
BOILER BASE CONTROLS  
SYMPTOM  
POSSIBLE CAUSES  
Steamer does not operate, low water light 1. Main circuit breaker off; or control circuit fuse F1 or F2 open.  
and high pressure lights not lit.  
2. Supply voltage incorrect.  
3. Supply voltage transformer - jumper missing or incorrect  
location; or transformer inoperative.  
4. Power switch malfunction.  
Steamer on, cannot reset low water  
1. Boiler fill water off or filtering system clogged.  
condition. Low water light lit, ready light  
not lit, water level not visible in sight glass.  
2. Boiler blowdown/drain valve stuck open or malfunction.  
3. Manual blowdown valve open on water level probe housing.  
4. Lime scale build-up on water level probes.  
5. Water level control board - ground connection open, not  
receiving power or malfunction.  
6. Boiler fill valve clogged or malfunction.  
7. Auxiliary water level control board - ground connection open,  
not receiving power or malfunction.  
8. Reset switch malfunction.  
9. K1, K3 relays not seated properly or malfunction.  
10. Water too pure for probes to properly conduct electricity.  
11. Interconnecting wiring malfunction.  
Steamer on, cannot reset low water  
condition. Low water light lit, ready light  
not lit, water level visible in sight glass.  
1. Ground connection open on auxiliary water level control board.  
2. Lime scale build-up dried on AUX LLCO probe.  
3. Auxiliary water level control board not receiving power or  
malfunction.  
4. Reset switch malfunction.  
5. K1, K3 relays not seated properly or malfunction.  
6. Interconnecting wiring malfunction.  
Steamer on, cannot reset high pressure  
condition. High pressure light lit, pressure  
gauge indicating 15PSI.  
1. Cycling pressure switch out of adjustment or malfunction.  
2. High limit pressure switch out of adjustment or malfunction.  
3. Reset switch malfunction.  
4. K2, K4 relays not seated properly or malfunction.  
5. Steam trap malfunction.  
6. Interconnecting wiring malfunction.  
Boiler operates but pressures are below  
the normal cycling range of 10-12 PSI.  
1. Manual blowdown valve on water level probe housing open.  
2. Boiler blowdown valve clogged and not fully closing.  
3. Supply voltage incorrect.  
4. Cycling pressure switch out of adjustment or malfunction.  
5. Heating elements not wired correctly.  
6. Contactor(s) malfunction.  
7. Heating element malfunction.  
8. Steam trap malfunction.  
9. Excessive load on boiler due to other equipment connected to  
steam line (outlet from boiler).  
F25154 (February 2004)  
Page 42 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Condenser drain box leaking.  
1. Grommets or cover panel gasket not sealing.  
2. Clog in drain line plumbing.  
3. Drain restricted due to drain pipe size below 1-1/4" NPT.  
4. Drain extension plumbing not at the proper slope or plumbing  
too lengthy.  
5. Steamer drain not plumbed to an open air gap drain.  
6. Steamer draining while under pressure and relief valve opening  
at the same time (flooding drain box).  
7. Cold water condenser spray is over spraying.  
8. Cold water condenser cycling thermostat out of adjustment or  
malfunction.  
Excessive steam vapors exiting from  
drain.  
1. Water supply for cold water condenser line off or inline strainer  
clogged.  
2. Cold water condenser solenoid not receiving power, clogged or  
malfunction.  
3. Clogged spray nozzle (condenser drain box).  
4. Water supply pressure high; or high pressure in line due to  
water hammer, causing improper valve operation.  
5. Cold water condenser thermostat out of adjustment or  
malfunction.  
Heat coming on without water in boiler  
(Dry firing).  
1. Lime scale build-up on water level probes.  
2. Retention of water in probe housing (three probe assembly or  
single AUX LLCO probe).  
3. Air equalization tubes clogged.  
4. Water level control malfunction.  
5. Auxiliary water level control malfunction.  
6. Reset switch malfunction.  
7. K1, K2, K3, K4 relays malfunction.  
8. Relay board malfunction.  
Excessive time for boiler to reach  
operating pressure (over 15 min.).  
1. Supply voltage incorrect.  
2. Heating elements not wired correctly.  
3. Contactor(s) malfunction.  
4. Water supply off or low pressure, filtering system clogged,  
boiler fill valve clogged or malfunction.  
5. Manual blowdown valve on water level probe housing open.  
6. Boiler blowdown/drain solenoid valve clogged and not fully  
closing.  
7. Steam trap malfunction (stuck open).  
8. Pressure relief valve leaking (pressure below 15PSI).  
9. Cooking compartment steam solenoid valve clogged and not  
fully closing.  
10. Excessive load on boiler due to other equipment connected to  
steam line (outlet from boiler).  
11. A heavy build-up of scalants has coated the interior of the  
boiler, creating an insulating effect.  
Page 43 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Steamer on, boiler will not heat. Reset  
switch activated, low water light and high  
pressure light not lit, ready light lit.  
1. Reset switch malfunction.  
2. Water Level Control malfunction.  
3. Cycling pressure switch out of adjustment or malfunction.  
4. High limit pressure switch out of adjustment or malfunction.  
5. K3, K4 relays malfunction.  
6. Relay board malfunction.  
7. Contactor(s) malfunction.  
8. Interconnecting wiring malfunction.  
Pressure relief valve opening or leaking.  
Steam output low or slow cooking.  
1. Pressure relief valve malfunction.  
2. Cycling pressure switch out of adjustment or malfunction.  
3. High limit pressure switch out of adjustment or malfunction.  
1. Cooking Compartments.  
A. Blocked steam injector ports. Open door, press door switch  
button and verify good steam flow into compartment.  
B. Steam solenoid valve clogged or malfunction.  
C. Steam intake shut-off valve not adjusted properly.  
2. Boiler Base.  
A. Cycling pressure switch out of adjustment or malfunction.  
B. Steam header line (supply) blockage.  
C. Excessive amount of water in condensate tube loop from  
boiler to pressure controls.  
D. Pressure relief valve leaking.  
E. Excessive steam supply line leaks.  
Steamer leaks water.  
1. Water, steam or drain line connections loose (top or base).  
2. Heating element gasket not sealing.  
3. Heating element mounting plate not sealing.  
4. Gauge glass fittings loose.  
Boiler water level too high, more than 1"  
visible in sight glass.  
1. Boiler fill valve malfunction.  
2. Water level probes not wired correctly.  
3. Lime scale build-up on HL probe.  
4. Water level control malfunction.  
Boiler does not fill or is slow to fill.  
1. Boiler fill water off or filtering system clogged.  
2. Manual blowdown valve on water level probe housing open.  
3. Boiler fill valve not receiving power, clogged or malfunction.  
4. Boiler blowdown/drain valve clogged and not fully closing.  
5. Air equalization tubes clogged.  
6. Water level control malfunction.  
F25154 (February 2004)  
Page 44 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - TROUBLESHOOTING  
COOKING COMPARTMENT CONTROLS  
SYMPTOM  
POSSIBLE CAUSES  
Cooking compartments do not operate.  
1. No power to cooking compartment controls.  
2. Pressure in boiler is below compartment pressure switch  
setting.  
3. Manual intake shutoff valve in the off position.  
4. Door switch malfunction.  
5. Timer malfunction.  
6. Malfunctioning pressure switch in compartment.  
7. Interconnecting wiring malfunction.  
Steam generated inside compartment  
when timer is off.  
1. Steam supply solenoid not fully closing (clogged or dirty).  
2. Timer contacts 1 & 3 closed.  
Timer motor does not run.  
1. Door open or door switch malfunction.  
2. Timer not receiving power or malfunction.  
Door not closing properly.  
1. Door latch assembly malfunction or out of adjustment.  
2. Striker adjustment.  
Door won’t open.  
1. Latch won’t release.  
Buzzer not operating.  
1. Timer malfunction.  
2. Buzzer malfunction.  
Compartment leaks water around door or 1. Compartment drain screen clogged.  
water accumulating in compartment .  
2. Door out of adjustment.  
3. Drain line obstructed or not to an open air gap drain.  
4. Worn or damaged door gasket.  
5. Steamer not level.  
Steam leaks around door.  
1. Door out of adjustment.  
2. Worn or damaged door gasket.  
3. Drain line obstructed or not to an open drain.  
Page 45 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER  
– NOTES –  
F25154 (February 2004)  
Page 46 of 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER  
– NOTES –  
Page 47 of 48  
F25154 (February 2004)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VHX SERIES STEAMER - CONDENSED SPARE PARTS LIST  
CONDENSED SPARE PARTS LIST  
VHX24E, VHX24E5, MHB24E  
BOILER BASE  
PART NUMBER  
DESCRIPTION  
Element, 9kw 208V  
NOTES  
855051-1  
855051-2  
855051-3  
855051-4  
855051-5  
855051-6  
855051-7  
881237  
Element, 9kw 240V  
Element, 9kw 480V  
Element, 10.5kw 208V  
Element, 12kw 208V  
Element, 12kw 240V  
Element, 12kw 480V  
Fuse, 10 Amp 600v Time Delay  
Fuse Holder  
881236  
880410  
Gasket, heating element  
Valve, Pressure Relief 15 psi  
Valve, Cold Water Condenser and Boiler Fill  
Switch, Pressure Cycling  
Switch, Pressure High Limit  
Thermostat, Condenser/drain Box  
Contactor, 50 Amp  
880413  
817222  
833488  
851578-1  
844062-1  
854839-1  
855223-1  
855225-1  
844070-1  
844069-1  
851613-1  
855177-2  
855177-3  
853275-1  
Relay Board (Includes relays)  
Relays  
Control, Aux. Low Water Board  
Control, Low Water Board  
Valve, Boiler Blowdown/drain  
Transformer 240-480/120 250VA  
Transformer 208/120 250VA  
Switch Assembly (Power, Reset W/lights)  
COOKING COMPARTMENT  
DESCRIPTION  
PART NUMBER  
842049  
NOTES  
Door Switch  
843833  
Transducer  
843832  
Pressure Switch  
411690-1  
843836  
Timer 60 Min 120v  
Solenoid, Steam Inlet  
Gasket, Door 3 Pan Compartment  
Gasket, Door 5 Pan Compartment  
844196  
844385  
F25154 (February 2004)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Thermador Ventilation Hood UCVM30FS User Manual
Toshiba Camera Accessories IK TF9U User Manual
Toshiba Car Video System SD900KY User Manual
Toshiba Universal Remote RBC AS21UL User Manual
Trane Heat Pump 4YCY4024A User Manual
True Fitness Treadmill CS500 User Manual
Uniden Welder 24 148 User Manual
Vermont Casting Ventilation Hood DVRS3 User Manual
Viking Cooktop VGRC485 6GD User Manual
Vivotek Home Security System FD7141V User Manual