Visonik Home Security System MCT 501 User Manual

MCT-501  
SMARTHOME #73951  
Installation Instructions  
Advanced Acoustic Sensor / PowerCode Transmitter  
1. INTRODUCTION  
The MCT-501 combines two modules:  
When mounted on opposite wall or adjoining walls, the range is  
6 m (20 ft) for plate, tempered, laminated and wired glass.  
The Sentrol Inc. ShatterPro™ acoustic sensor with Pattern  
Recognition Technology™ (Protected under U.S. Patent  
5,192,931)  
When mounted on the ceiling, the maximum range is 6 m (20 ft)  
for plate, tempered, laminated and wired glass  
For armor-coated glass, mount the sensor no more than 3.65 m  
(12 ft) from the glass.  
The Visonic Ltd. MCT-302 PowerCode™ transmitter  
1.2 PowerCode Transmitter  
The acoustic sensor shares its housing with  
a
miniature  
transmitter which has a unique 24-bit PowerCode ID, selected in  
the factory from over 16 million possible code combinations.  
Upon alarm (glass break detection), a digital message is  
transmitted, composed of the PowerCode ID followed by various  
status and message-type markers. Alarm and other data are thus  
forwarded to the wireless alarm control panel.  
Since transmitted messages might collide with transmissions  
from other PowerCode transmitters used in the system, a smart  
anti-collision transmission sequence is used.  
Figure 1. General View  
Figure 2. Module Identification  
1.1 Acoustic Sensor  
The MCT-501 is protected by a tamper switch that is activated  
when the cover is removed. In a tamper situation, a message is  
transmitted with the “tamper alert” marker ON.  
The acoustic sensor module of the MCT-501 is omni-directional,  
providing 360° coverage. Coverage is measured from the sensor  
to the point on the glass farthest from the sensor (see Fig. 3). The  
sensor can be mounted as close as 1 m (3.3 ft) from the glass.  
A periodic supervision message, distinguished by a specific  
marker, is transmitted automatically once in 60 minutes. The  
wireless control panel is thus informed, at regular intervals, of the  
sensor’s active participation in the system.  
A red LED mounted on the transmitter PCB (visible only when the  
cover is off) lights whenever alarm or tamper events are reported.  
The LED does not light while a supervision message is being  
transmitted.  
Operating power is obtained from an on-board 3.6 V Lithium  
Thionyl Chloride battery. A weak battery will cause a “low battery”  
marker to be added to any message transmitted.  
Figure 3. Typical Range Measurement  
2. SPECIFICATIONS  
ACOUSTIC SENSOR SECTION  
POWER SUPPLY  
Power Source: 3.6 V Lithium Thionyl Chloride (LiSOCl2) battery,  
size 1/2 AA, Tadiran TL-5902 or equivalent.  
Nominal Battery Capacity: 1.2 Ah  
Current Drain: 24 µA standby, 13 mA on alarm (including LED)  
Battery Life (with LED on):  
Microphone: Omni-directional electret  
Alarm Duration: 4 seconds  
RF immunity: 20 V/m, 1 MHz to 1000 MHz  
Temperature range: -10° to 50°C (14° to 120°F)  
Recommended Glass Size:  
Minimum: 0.3 x 0.6 m (1 x 2') or larger glass thickness  
@ 10 transmissions per day: Over 10 years  
@ 50 transmissions per day: About 6 years  
Plate: 2.4 to 6.4 mm (3/32 to 1/4")  
Tempered: 3.2 to 6.4 mm (1/8 to 1/4")  
Wired: 6.4 mm (1/4")  
Battery Supervision: Automatic transmission of battery condition data  
as part of any status report.  
PHYSICAL  
Laminated: 3.2 to 6.4 mm (1/8" to 1/4")  
Operating Temperature: 0°C to 49°C (32°F to 120°F).  
Dimensions: 80 x 108 x 43 mm (3.13 x 4.24 x 1.70 in.).  
Weight (less battery) : 130 g (4.6 oz)  
Housing Material and Color: Flame retardant ABS, white  
Standards: Meets FCC Part 15, ETS 300-220 and MPT1349  
POWERCODE TRANSMITTER SECTION  
Frequency (MHz): 315, 404, 418, 433.92 or other frequencies  
according to local requirements.  
Transmitter's ID Code: 24-bit digital word, over 16 million  
combinations, pulse width modulation.  
Overall Message Length: 36 bits  
Message Repetition: One-shot transmission (default) or once  
every 3 minutes.  
The 418 & 433.92 MHz models of this device comply with the  
European Council Directive EMC 89/336/EEC & 92/31/EEC, and  
bear the CE mark and certification.  
Supervision: Signaling at 60-minute intervals (U.S. version) or  
15 minute interval (UK version)  
Response to Tamper Event: Tamper report every 3 minutes  
(until the tamper switch is restored).  
DE3596  
1
The tamper message transmitted as a result (the transmit  
LED blinks) will do the job.  
3.4 ID Enrollment and Mounting  
Note: It is much easier to enroll the transmitter ID while holding  
C. Use the base as a template - press it against the wall at the  
selected mounting position and mark the drilling points  
through the mounting holes. Drill two holes and attach the  
base to the wall using the wall plugs and screws.  
the MCT-501 in your hand, close to the control panel.  
A. Refer to the control panel’s or PowerCode receiver’s  
installation instructions for enrolling transmitter IDs.  
B. When required to initiate a transmission for enrolling the  
D. Align the cover with the base and push it until it snaps shut.  
transmitter’s ID, press the unit’s tamper switch and release it.  
4. TESTING PROCEDURES  
D. If the LED does not go solid, but continues flashing as before,  
re-position the sensor closer to the protected windows and  
retest. This may require adding sensors in order to achieve  
adequate coverage. It is very rare that the sensor will not  
activate within its stated range of coverage. Double check  
adequate battery strength in the hand-held tester. A new  
tester battery will likely restore the range.  
4.1 How Does the Test Mode Works  
The Pattern Recognition Technology™ of the MCT-501 ignores  
most false alarm sounds, including glass-break testers. In order  
to test the MCT-501, a test mode is used. With the sensor in the  
test mode, processing of the glass-break pattern in the upper and  
lower frequencies is disabled. The MCT-501 is then sensitive only  
to the mid-range frequencies which the Sentrol 5709C hand-held  
tester reproduces. It's the mid-range frequencies that determine  
sensor coverage.  
Note: The sensor will automatically change from test mode to  
normal mode approximately one minute after the last signal  
received from the hand-held tester.  
IN THE NORMAL MODE THE DETECTION LED FLASHES BRIEFLY  
UPON RECEIVING A LOUD SOUND. WHEN IN THE NORMAL  
MODE, THE MCT-501 WILL NOT TRIP TO THE TESTER’S SIGNAL,  
UNLESS THE TESTER IS HELD NEXT TO THE SENSOR.  
IMPORTANT! Room acoustics can artificially extend the  
range of a glass-break sensor. The specified range of the  
MCT-501 has been established for worst-case conditions.  
While the sensor is likely to function at additional range, it  
may miss a “minimum output” break, or room acoustics  
may be changed at some future time, restoring sensor  
coverage back to the normal range of 6 m (20 ft).  
NOTE: Each time the sensor alarms it also goes into the TEST mode  
for one minute.  
4.2 Switching the Sensor to the Test  
Mode  
Do not exceed the rated range of the sensor, regardless of  
what the tester shows.  
Use the Sentrol 5709C or the Intellisense FG701 hand-held tester  
to switch the sensor into the test mode. Set the tester to  
tempered glass, hold the tester speaker directly on top of the  
sensor and activate the tester. The sensor will alarm, then it will  
go into test mode for one minute. When in test mode the LED on  
the sensor will flash continuously. prolong the test session by  
firing the tester at the sensor at least once a minute.  
4.4 Hand Clap Test  
The MCT-501 can be checked by the installer or end user while  
in normal mode, simply by clapping hands loudly under the  
sensor. The LED will flash twice, but the sensor will not trip. This  
verifies visually that there is power to the sensor, and that the  
microphone and circuit board are functioning.  
4.3 Testing the Sensor (see Figure 10).  
The hand clap activation is only momentary, so there is no  
appreciable effect on battery life.  
A. Holding the tester near the surface of the glass, aim the tester  
at the MCT-501 and press the test button. If drapes or blinds  
are present, test with the hand-held tester behind the closed  
drapes or blinds (do not install the sensor where heavy or  
lined drapes are used). If the sensor is mounted on same wall,  
point the tester at the opposite wall.  
INSTALLATION TIPS  
A. The MCT-501 is designed to detect the shattering of framed  
glass mounted in an outside wall. “Testing" the sensor with  
unframed glass, broken bottles, etc. may not trip the sensor.  
The MCT-501 typically does not trip to glass break tests in  
the middle of a room as such breaks are false alarms.  
B. False alarms are most likely to occur when installed on a  
24-hour loop in glass airlocks and glass vestibule areas, when  
mounted above sinks, when used in residential car garages  
and in other small, acoustically live rooms and rooms where  
multiple sounds can reflect and eventually duplicate the glass  
break frequency pattern. For occupied area glass break  
protection in such applications, use shock sensors.  
C. Installing the MCT-501 on 24-hour loops will increase false  
alarms. The MCT-501 is recommended for perimeter loops  
and is designed to function without false alarms in occupied  
areas. On a 24-hour loop, which is armed all day/all night  
every day, the false alarm technology will be pushed to its  
limit since some sounds in some conditions can duplicate the  
points on the glass break pattern that the MCT-501 detects.  
Install the MCT-501 on a perimeter loop, which is armed  
whenever the door and window contacts are armed. For  
occupied area installations, MCT-501 's false alarm immunity  
is best in rooms with only moderate noise.  
Figure 10. Testing the MCT-501  
B. The tester has a different setting for each type of glass. It  
should always be set for tempered or laminated glass (either  
is correct and both have the same range) unless you are  
certain that all the protected glass is plate glass.  
D. MCT-501 detects the shattering of glass. Like all glass-break  
sensors, it may not consistently detect cracks in glass, or  
bullets that break through the glass or break out the glass.  
Glass-break sensors should always be backed up by interior  
protection.  
C. When the LED on the sensor goes solid momentarily while the  
tester is triggered, the glass is within detection range.  
DE3596  
3
Order#73951  
5. MISCELLANEOUS COMMENTS  
Visonic Ltd. wireless systems are very reliable and are tested to  
high standards. However, due to their low transmitting power and  
limited range (required by FCC and other regulatory authorities),  
there are some limitations to be considered:  
A. Receivers may be blocked by radio signals occurring on or near  
their operating frequencies, regardless of the code selected.  
B. A repeater can only respond to one transmitter signal at a time.  
C. Wireless equipment should be tested regularly to determine  
whether there are sources of interference and to protect  
against faults.  
The digital circuitry of this device has been tested and found to  
comply with the limits for a Class B digital device, pursuant to Part 15  
of the FCC Rules. These limits are designed to provide reasonable  
protection against harmful interference in residential installations.  
This equipment generates, uses and can radiate radio frequency  
energy and, if not installed and used in accordance with the  
instructions, may cause harmful interference to radio and television  
reception. However, there is no guarantee that interference will not  
occur in a particular installation. If this device does cause such  
interference, which can be verified by turning the device off and on,  
the user is encouraged to eliminate the interference by one or more  
of the following measures:  
This device complies with FCC Rules, Part 15. Operation is  
subject to two conditions: (1) This device may not cause harmful  
interference, and (2) this device must accept any interference  
that may be received or that may cause undesired operation.  
– Re-orient or re-locate the receiving antenna.  
– Increase the distance between the device and the receiver.  
– Connect the device to an outlet on a circuit different from the one  
which supplies power to the receiver.  
WARNING! Changes or modifications to this unit not expressly  
approved by the party responsible for compliance could void the  
user's authority to operate the equipment.  
– Consult the dealer or an experienced radio/TV technician.  
SMARTHOME #73951  
4
DE3596  

Targus Mouse wireless mouse User Manual
Tektronix Yard Vacuum TM 5006 User Manual
Toshiba Computer Drive 6F3A4508 User Manual
Toshiba Security Camera IKWB81A User Manual
Tripp Lite Network Card P770 10M User Manual
Troy Bilt Lawn Mower 3114GR User Manual
Uniden Cordless Telephone EXAI 918 User Manual
Vandersteen Audio Home Theater System 2WQ User Manual
Vivitar Camera Lens V 650 1300 User Manual
Wayne Plumbing Product ISP40 User Manual