Viking Sprinkler Sprinkler 11a User Manual

Sprinkler 11a  
March 7, 2008  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
1. DESCRIPTION  
Viking Micromatic® and MicromaticHP® Standard Response Pendent Sprinklers are  
small, thermosensitive, glass-bulb spray sprinklers available in several different fin-  
ishes, temperature ratings, and K-Factors to meet design requirements. The special  
Polyester and Teflon® coatings can be used in decorative applications where colors are  
desired. In addition, these coatings have been investigated for installation in corrosive  
atmospheres and are cULus listed as corrosion resistant as indicated in the Approval  
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat-  
ings as corrosion resistant.)  
Viking standard response sprinklers may be ordered and/or used as open sprinklers  
(glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering  
Instructions on page 11b.  
2. LISTINGS AND APPROVALS  
cULus Listed: Category VNIV  
FM Approved: Classes 2001, 2002, 2006, 2015, and 2017  
NYC Approved: MEA 89-92-E, Volume 12  
ABS Certified: Certificate 04-HS407984A-PDA  
VdS Approved: Certificate G4040096, G4040098, G4060058, G4060059, G4980001, G4980002, G4980005, and G4980007  
LPC Approved: Ref. No. 096e/06 and 167a/04  
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40141, 0786-CPD-40181, 0832-CPD-2001, and  
0832-CPD-2003  
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008, and RINA Certificate  
No. MED497705C5  
NOTE: Other International approval certificates are available upon request.  
Refer to the Approval Charts on pages 11d-f and Design Criteria on page 11f for cULus and FM approval requirements that must  
be followed.  
3. TECHNICAL DATA  
Specications:  
Available since 1997.  
Minimum Operating Pressure: Refer to the Approval Chart  
Maximum Working Pressure: Sprinklers VK023 and VK122 are rated for  
Viking Technical Data may be found on  
The Viking Corporation’s Web site at  
use with water working pressures ranging from the minimum 7 psi  
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-  
The Web site may include a more recent  
sure (HP) sprinklers can be identified by locating “250” stamped on  
edition of this Technical Data Page.  
the deflector. All other Part Nos. not mentioned above are rated to a  
maximum 175 psi (12 bar) wwp.  
Factory tested hydrostatically to 500 psi (34.5 bar)  
Testing: U.S.A. Patent No. 4,831,870  
Thread size: Refer to the Approval Charts  
Nominal K-Factor: Refer to the Approval Charts  
Glass-bulb fluid temperature rated to -65 °F (-55 °C)  
Overall Length: Refer to the Approval Charts  
Material Standards:  
Frame Casting: Brass UNS-C84400  
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 10139, 10142, 10170, 10173, 10223, and  
12105. Brass UNS-C26000 for all other Sprinklers.  
Bushing (for Sprinklers 09994, 10189, 10221, and 10222): Brass UNS-C36000  
Bulb: Glass, nominal 5 mm diameter  
Form No. F_100397  
Replaces page 11a-h, dated October 12, 2007.  
(Added Dry System note in approval chart for Small Orifice)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sprinkler 11c  
March 7, 2008  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES  
Sprinkler Temperature  
Classification  
Sprinkler Nominal  
Temperature Rating1  
Maximum Ambient  
Ceiling Temperature2  
Bulb Color  
Ordinary  
Ordinary  
135 °F (57 °C)  
155 °F (68 °C)  
175 °F (79 °C)  
200 °F (93 °C)  
212 °F (100 °C)  
286 °F (141 °C)  
360 °F (182 °C)  
500 °F (260 °C)  
100 °F (38 °C)  
100 °F (38 °C)  
150 °F (65 °C)  
150 °F (65 °C)  
150 °F (65 °C)  
225 °F (107 °C)  
300 °F (149 °C)  
465 °F (240 °C)  
Orange  
Red  
Intermediate  
Intermediate  
Intermediate  
High  
Yellow  
Green  
Green  
Blue  
Extra High  
Ultra High3  
Mauve  
Black  
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®  
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon® in all temperature ratings. Wax-Coated  
Brass and Wax over Polyester5 for sprinklers with the following temperature ratings:  
135 °F (57 °C) Off-White Wax  
212 °F (100 °C) Dk. Brown Wax6  
155 °F (68 °C) Lt. Brown Wax 175 °F (79 °C) Brown Wax  
286 °F (141 °C) Dk. Brown Wax6  
200 °F (93 °C) Brown Wax  
Footnotes  
1 The sprinkler temperature rating is stamped on the deflector.  
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having  
Jurisdiction. Refer to specific installation standards.  
3 Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal oper-  
ating temperatures above 300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler  
is significantly reduced below 300 °F (149 °C), response time may be severely retarded.  
4
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated  
on pages 11 d-e. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify  
through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers,  
the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with  
Polyester and Teflon® coatings. For Teflon® coated open sprinklers only, the waterway is coated.  
5 Wax Over Polyester is unavailable for Sprinklers VK023 and VK122.  
6 Wax melting point is 170 °F (76 °C) for 212 °F (100 °C) and 286 °F (141 °C) temperature rated sprinklers.  
Figure 2: Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
March 7, 2008  
Sprinkler 11d  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
Approval Chart 1  
Micromatic® Standard Response Pendent Sprinklers  
Maximum 175 PSI (12 bar) WWP  
Nominal  
K-Factor  
Overall  
Length  
Listings and Approvals3  
(Refer also to Design Criteria on page 11 g.)  
Sprinkler  
Base Part  
Number1  
Thread Size  
NPT BSP  
SIN  
U.S. metric2 Inches mm  
cULus4  
FM  
NYC7  
VdS  
LPCB  
Standard Orifice  
10139  
VK102 1/2” 15 mm 5.6  
VK102 -- 15 mm 5.6  
80.6  
80.6  
2-3/16”  
2-3/16”  
56  
56  
B1, D5, E7, F4 A3, C6, F3 B1, D5, E7  
B1, D5, E7, F4 A3, C6, F3 B1, D5, E7  
B3  
B3  
B3, D5 G312 G314,15  
1017311  
B3, D5  
--  
--  
Large Orifice  
10223  
10142  
10170  
12105  
VK202 1/2” 15 mm 8.0  
VK202 3/4” 20 mm 8.0  
115.2  
115.2  
115.2  
115.2  
2-3/8”  
2-5/16”  
2-3/8”  
60  
59  
60  
56  
B1, D5, E7, F4 B4, D6, F4 B1, D5, E7  
B1, D5, E7, F4 B4, D6, F4 B1, D5, E7  
B3  
--  
--  
--  
--  
B3, D5 G412 G414  
B3, D5 G412 G414  
VK202  
--  
20 mm 8.0  
B1, D5, E7  
--  
C6, A4  
--  
--  
--  
--  
VK202 3/4” 20 mm 8.0  
2-3/16”  
B3  
--  
B313  
--  
Small Orifice9  
1022110  
1022210  
10175  
VK003 1/2” 15 mm 2.8  
VK004 1/2” 15 mm 4.2  
40.3  
60.5  
60.5  
40.3  
2-3/16”  
2-1/4”  
56  
58  
58  
56  
B1, D5, E7  
B4, D6  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
B1, D5, E7  
--  
B3, D5  
VK004  
--  
--  
10 mm 4.2  
15 mm 2.8  
2-1/4”  
--  
B3  
--  
B3, D5 G313 G314,15  
-- -- --  
1018910,11 VK003  
2-3/16”  
B1, D5, E7  
B4, D6  
Approved Temperature Ratings  
Approved Finishes  
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 212 °F (100 °C),  
286 °F (141 °C), and 360 °F (182 °C)  
1 - Brass, Chrome-Enloy®, White Polyester5,6, Black Polyester5,6, and Black Teflon®5  
2 - White Polyester6, Black Polyester6, Black Teflon®, Wax-Coated Brass, and Wax  
over Polyester  
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F  
(141 °C), and 360 °F (182 °C)  
3 - Brass, Chrome-Enloy®, White Polyester6, and Black Polyester6  
4 - Brass and Chrome-Enloy®  
C - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and  
212 °F (100 °C)  
5 - Wax-Coated Brass and Wax Over Polyester5  
D - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)  
E - 286 °F (141 °C)  
6 - Wax-Coated Brass (corrosion resistant)  
F - 500 °F (260 °C)8  
7 - High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum  
ambient temperature allowed at ceiling = 150 °F (65 °C)  
G - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and  
360 °F (182 °C)  
Footnotes  
1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.  
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.  
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.  
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.  
5 cULus Listed as corrosion resistant.  
6 Other colors are available on request with the same Listings and Approvals as the standard colors.  
7 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 12.  
8 Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 °F  
(149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C), the response time  
of the Ultra-High temperature rated sprinkler may be severely retarded.  
9 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems  
only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.  
10The sprinkler orifice is bushed.  
11Sprinklers 10173 and 10189 are available on special order.  
12  
Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.  
13  
Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40141 and 0786-CPD-40181.  
14  
MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.  
MED Certified, RINA Certificate No. MED497705C5.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sprinkler 11e  
March 7, 2008  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
Approval Chart 2  
Micromatic® Standard Response Pendent Sprinklers  
Maximum 175 PSI (12 bar) WWP  
Nominal  
K-Factor  
Overall  
Length  
Listings and Approvals3  
(Refer also to Design Criteria on page 11g.)  
Sprinkler  
Base Part  
Number1  
Thread Size  
NPT  
SIN  
12  
BSP  
Installed with the Viking Micromatic® Model E-1 or E-2 Recessed Escutcheon  
U.S. metric2 Inches mm  
cULus4  
FM  
NYC7  
VdS  
LPCB  
10139  
1017311  
10223  
VK102 1/2” 15 mm 5.6  
VK102 -- 15 mm 5.6  
80.6  
80.6  
2-3/16”  
2-3/16”  
2-3/8”  
56  
56  
60  
59  
60  
56  
56  
58  
B1  
B1  
B1  
B1  
B1  
--  
A210  
A310  
B310  
B310  
B310  
--  
B1  
--  
B2  
--  
B2  
B2  
--  
C2  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
VK202 1/2” 15 mm 8.0  
VK202 3/4” 20 mm 8.0  
115.2  
115.2  
115.2  
115.2  
40.3  
B1  
B1  
--  
--  
10142  
2-5/16”  
2-3/8”  
--  
B2  
B2  
--  
C2  
C2  
B2  
--  
10170  
VK202  
--  
20 mm 8.0  
--  
12105  
VK202 3/4” 20 mm 8.0  
VK003 1/2” 15 mm 2.8  
VK004 1/2” 15 mm 4.2  
2-3/16”  
2-3/16”  
2-1/4”  
--  
B2  
--  
102218,9  
102228,9  
B1  
B1  
A38  
--  
B1  
B1  
--  
60.5  
--  
B2  
--  
Installed with the Viking Microfast® Model F-1 Adjustable Escutcheon  
--  
10139  
10223  
VK102 1/2” 15 mm 5.6  
VK202 1/2” 15 mm 8.0  
VK003 1/2” 15 mm 2.8  
80.6  
115.2  
40.3  
2-3/16”  
2-3/8”  
56  
60  
56  
B1  
B1  
B1  
--  
--  
--  
B1  
B1  
B1  
D2  
B2  
--  
B2  
--  
--  
--  
--  
--  
--  
102218,9  
2-3/16”  
--  
Approved Temperature Ratings  
Approved Finishes  
1 - Brass, Chrome-Enloy®, White Polyester5,6, Black Polyester5,6, and  
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 212 °F  
(100 °C)  
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)  
C - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)  
D - 286 °F (141 °C)  
Black Teflon®5  
2 - Brass, Chrome-Enloy®, White Polyester6, and Black Polyester6  
3 - Brass and Chrome-Enloy®  
Footnotes  
1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.  
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.  
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.  
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.  
5 cULus Listed as corrosion resistant.  
6 Other colors are available on request with the same Listings and Approvals as the standard colors.  
7 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 12.  
8
Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated  
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or  
internally galvanized.  
9 The sprinkler orifice is bushed.  
10FM Approval of Viking Micromatic® Standard Response Recessed Pendent Sprinklers installed with the Viking Micromatic® Model E-1 or E-2 Recessed  
Escutcheon is limited to wet systems and preaction systems qualifying as wet systems, for hazard occupancies up to and including Ordinary Hazard,  
Group II.  
11Sprinkler 10173 is available on special order.  
12  
Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40181, 0832-CPD-2001, and 0832-CPD-2003.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
March 7, 2008  
Sprinkler 11f  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
Approval Chart 3  
MicromaticHP® Standard Response Pendent Sprinklers  
Maximum 250 PSI (17 bar) WWP  
Nominal  
K-Factor  
Overall  
Length  
Listings and Approvals3  
(Refer also to Design Criteria on page 11g.)  
Sprinkler  
Base Part  
Number1  
Thread Size  
NPT BSP  
SIN  
U.S. metric2 Inches mm  
cULus4  
FM  
NYC  
--  
VdS  
--  
LPCB  
Standard Orifice  
09992  
VK122 1/2” 15 mm 5.6  
80.6  
40.3  
2-1/4”  
2-1/4”  
58  
Small Orifice7  
58 A1  
A1, D2  
--  
--  
--  
--  
--  
--  
--  
099947,8  
VK023 1/2” 15 mm 2.8  
--  
--  
--  
Installed with the Viking Micromatic® Model E-1 or E-2 Recessed Escutcheon  
--  
09992  
VK122 1/2” 15 mm 5.6  
VK023 1/2” 15 mm 2.8  
80.6  
40.3  
2-1/4”  
2-1/4”  
58  
58  
C1  
C1  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
099947,8  
--  
Installed with the Viking Microfast® Model F-1 Adjustable Escutcheon  
--  
09992  
VK122 1/2” 15 mm 5.6  
VK023 1/2” 15 mm 2.8  
80.6  
40.3  
2-1/4”  
2-1/4”  
58  
58  
B1  
B1  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
099947,8  
--  
Approved Temperature Ratings  
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F  
(141 °C), and 360 °F (182 °C)  
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F  
(141 °C)  
C - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)  
D - 500 °F (260 °C)8  
Approved Finishes  
1 - Brass, Chrome-Enloy®, White Polyester5,6, Black Polyester5,6, and  
Black Teflon®5  
2 - Brass and Chrome-Enloy®  
Footnotes  
1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.  
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.  
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.  
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.  
5 cULus Listed as corrosion resistant.  
6 Other colors are available on request with the same Listings and Approvals as the standard colors.  
7
Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated  
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or  
internally galvanized.  
8 The sprinkler orifice is bushed.  
9 Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above  
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),  
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sprinkler 11g  
March 7, 2008  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
DESIGN CRITERIA  
(Also refer to the Approval Charts on pages 11d-f.)  
cULus Listing Requirements:  
Micromatic® and MicromaticHP® Standard Pendent Sprinklers are cULus Listed as indicated in the Approval Charts for installation in accordance with  
the latest edition of NFPA 13 for standard spray sprinklers.  
Designed for use in Light, Ordinary, and Extra Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where al-  
lowed by the installation standards being applied, with hydraulically calculated wet systems only).  
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.  
FM Approval Requirements:  
Standard Pendent Sprinklers are FM Approved as indicated in the Approval Charts for installation in accordance with the latest applicable FM Loss  
Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins  
contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and  
maximum allowable spacing, and deflector distance below the ceiling.  
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.  
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page  
SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-  
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,  
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and  
standards, whenever applicable.  
Figure 3: Wrench 13577W/B for Wax Coated Sprinklers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
March 7, 2008  
Sprinkler 11h  
MICROMATIC® AND  
MicromaticHP® STANDARD  
RESPONSE PENDENT  
SPRINKLERS  
TECHNICAL DATA  
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058  
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: [email protected]  
Figure 4: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon  
Figure 5: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons  
Form No. F_100397  
Replaces page 11a-h, dated October 12, 2007.  
(Added Dry System note in approval chart for Small Orifice)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tascam MP3 Player DR 1 User Manual
Taser Digital Camera IT INST TC 001 User Manual
Thule Automobile Accessories Kit 110 User Manual
Toastmaster Convection Oven TMHD1 User Manual
TP Link Network Router TD W9980 User Manual
TRENDnet Network Card TU2 H4PC User Manual
Vent a Hood Ventilation Hood CLH9 User Manual
Vornado Fan EH1004144 User Manual
Wayne Water Pump 550100 001 User Manual
Wayne Water Pump GPB400 User Manual