Viking Smoke Alarm VFR 400 User Manual

VFR-400  
Installation, Operation, and  
Instruction Manual  
Releasing Panel for  
Sprinkler Systems  
All specications subject to revision.  
Manual #5403548 Rev D  
10/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Notes:  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
This is the safety alert system. It is used to alert you to potential personal injury hazards. Obey all safety messages  
that follow this symbol to avoid possible injury or death.  
• The detection and suppression system employing this release panel must be designed by people trained and competent  
in the design and layout of re alarm and/or suppression systems for special hazard locations. The system shall be designed  
and installed in accordance with all local and national codes and ordinances as well as the approval of the Authority Having  
Jurisdiction. Only trained, qualied and competent individuals should install, program and/or service the VFR-400.  
Competent people would be aware of these warnings, limitations, and requirements.  
• High voltage electrocution hazard. Do not handle live AC wiring or work on the device while ac power is active.  
This manual is designed to help with the specication, installation, and programming of the VFR-400 release panel. It is  
imperative that this manual be completely read and understood before the installation or programming of the panel. Save this  
manual for future reference.  
• Zones programmed as MANUAL RELEASE will override any cross zoning features. If it is desired to not have a Manual  
Release override the cross zoning, program the zone as DETECTION and map accordingly.  
*Locate the panel and all system components in the following nominal environment:  
*Indoor heated installation only, preferably an interior wall.  
*Verify that the wire sizes are adequate for all initiating, notication, and release circuits.  
*Make certain the panel is properly grounded.  
*Remove all electronic assemblies prior to any drilling, ling, reaming, or punching of the enclosure. When possible make all cable  
entries from the sides, bottom, or rear of the cabinet. Verify that they will not interfere with the batteries or other components.  
*The panel and system must be tested and maintained in accordance with all local and national codes and ordinances.  
Operating Instructions Form  
1) Fill in the name, address and telephone number of the servicing agency on the instruction sheet provided and  
frame and place adjacent to control panel at eye level.  
2) The following documentation shall be delivered to the owner or their representative upon nal acceptance of the system:  
An owners manual and installation instructions covering all system equipment.  
Wiring diagrams  
A detailed description of the programming and operating sequence of the system.  
Fire Alarm System Limitations  
Smoke detectors may not detect smoke when the smoke does not reach the detector. Such as smoke within walls, on the other  
side of walls, on other oors, behind closed doors, explosions, etc. Smoke detectors will not operate if they are not properly  
connected to the re/release panel. The detectors and bases must be UL/ULC listed as being compatible with the panel. The  
detectors have a visible ashing light that indicates power is supplied to the detectors.  
Notication appliances may not alert people if the people are not able to hear or see the appliances such as if they are in separate  
areas of the building or room.  
A re alarm/release panel will not operate without electrical power. The panel must have sufcient backup battery capability to  
power the panel for a specied amount of time in the event of an AC power failure. The batteries and release panel shall be tested  
and maintained in accordance with the testing and maintenance requirements of NFPA72.  
In order for emergency forces, (Fire departments, etc.), to respond to events associated with this panel, the panel must transmit  
trouble, supervisory, and alarm signals to a monitoring facility either directly or through a main building re panel.  
A problem in an audible or visual device may not be apparent when the panel is in a normal condition.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Design Guidelines  
People trained in the design of special hazard systems shall determine the selection and placement of the initiating devices and  
notication appliances connected to the VFR-400. This responsible party shall also be familiar with the premises being protected.  
The equipment shall be installed in accordance with the manufacturers instructions, the applicable version of NFPA 72 and all  
local codes and ordinances. For systems employing cross zoning of smoke detectors for the activation of the release circuit, this  
can include but is not limited to the installation of photoelectric and ionization types of detectors on separate zones. One of each  
type of detector on separate zones shall be installed in the coverage area selected for a single detector. The detectors would be  
installed in close proximity to each other.  
The responsible party shall also determine the theory of operation regarding the programming sequence.  
General Description  
The model VFR-400 is a listed and approved, microprocessor based re control/releasing panel. It is primarily designed for use  
as a releasing panel for pre-action, Surere®, Firecycle® III, and deluge, water based extinguishing systems. They may also be  
used as stand alone re control panels. These units comply with NFPA-13, NFPA-15,NFPA-72, and NFPA-750.  
The VFR-400 complies with UL Standard 864, ULC S527-77, Canadian Electrical Code Part 1 C22.1, ULC S524, FM, CSFM  
and NYMEA.  
System Features  
• Four Class B (Style B) Initiating zones. Each initiating zone can be set up for any of the following:  
·
·
·
·
·
·
·
·
·
·
·
·
Alarm Zones  
Detection alarm zone  
Waterow  
Linear Heat Detection up to 700 ohms per zone.  
Manual Release  
Viking Firecycle Detectors (Zone 1 only)  
Supervisory Zones  
Supervisory  
Tamper  
Low Air Supervisory  
High Air  
Low Air Alarm  
Note: Only zones programmed as Detection, Waterow, Linear Heat, Manual Release, Firecycle and Low  
Air Alarm can be mapped to outputs programed as release.  
• Remote Annunciator Output for connection to RA-4410RC:  
RS-485 communication, (2-wire shielded cable required)  
Regulated 24VDC annunciator power  
• Two Supervisory Zones, Class B (VDC Style B). These zones can be set up for any of the following:  
·
·
·
·
·
·
Supervisory  
Tamper  
Low Air Supervisory  
High Air  
• Four Class B (Style Y) Output circuits. Each output can be set up for any of the following:  
·
·
·
·
Notication Appliance circuit  
Releasing circuit  
Supervisory Bell circuit  
Trouble Bell circuit  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
· Twelve Standard Programs for water based systems or custom program capability  
· Releasing Zones can be set up for either normal or cross zoning operation  
· All circuits inherently power limited per NEC 760 and UL 864 Section 14.4  
· Initiating Circuit Disable feature  
· Output Disable feature  
· One-Man Walktest feature with automatic 30 minute restoration and releasing circuit disable  
· Diagnostic Indicators  
· Signal Silence button  
· Manual Event scroll buttons  
· Automatic resound of silenced trouble signals after 24 hours  
· Built-in Trouble buzzer  
· Common Relay Contacts for Alarm/Trouble/Supervisory/Waterow  
· 32 Character Liquid Crystal Display (LCD)  
· 34 LED Display  
· AC, Alarm, Supervisory, Trouble, Alarm silenced LED's (Pre-discharge/discharge LED)  
· User Generated Banner Message  
· User Generated Zone Labeling  
· 24 or 90 hour Battery Standby available (Where required by FM and Others)  
· 24 Hour Clock  
· Password Protection  
· Remote annunciator output  
· Resettable 4-wire smoke detector power  
Options  
1) CAM - Module to convert one Class B Indicating Appliance Circuit to one Class A circuit.  
2) CA2Z - Module to convert two Class B Initiating Device Circuits to two Class A circuits.  
3) ARM-2 - Module to provide two Form C contacts activated by Indicating or Releasing, polarity reversing circuits  
4) RA-4410-RC – Remote annunciator provides 34 LED’s for each zone in alarm supervisory or trouble, each output activated or  
in trouble, AC power, Power trouble, System trouble, Ground fault, Supervisory, Supervisory trouble, Alarm, Alarm silence  
and Pre-discharge/Discharge.  
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the  
instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits  
for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules which are designed to provide reasonable  
protection against such interference when operated in a commercial environment. Operation of this equipment in a residential  
area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may  
be required to correct the interference.  
Specications  
VFR-400 HOUSING  
Type - 18 gauge sheet steel with hinged, removable, locked door  
Size - 18 1/2" x 14 5/8" x 4 3/4"  
Finish - red cabinet with logo.  
Knockouts - 4 - ½" and 2 - ¾" on top; 1 - ½" and 1 - ¾" each side; 2 - ½" and 1 - ¾" back  
VFR-400 Visual Indicators (Visible with door closed):  
AC LED - Green  
Alarm Silenced - Amber  
System Alarm LED - Red  
System Supervisory LED- Amber  
System Trouble LED - Amber  
Pre-discharge/Discharge LED - Amber  
32 Character Alpha-Numeric Liquid Crystal Display (LCD)  
Red alarm per zone  
Amber trouble LED per zone  
Common required systems status LED's  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LCD  
A 2 line 32 character alpha-numeric liquid crystal display shows the condition, status and circuit for all  
Alarm, Supervisory and Trouble conditions:  
CONDITION  
Alarm  
Trouble  
Supervisory  
Tamper  
Low Air  
STATUS  
CIRCUIT  
<user Dened Message> (Up To 10 Characters)  
Disabled  
Acknowledged  
Silenced  
Output #1  
Output #2  
Output #3  
Output #4  
Battery  
High Air  
Aborted  
A.C.  
Pre-discharging  
Releasing  
Released  
Supervisory  
Zone #1  
Zone #2  
Zone #3  
Zone #4  
Ground  
VFR-400 Visual Indicators  
In accordance with ULC S527-99 option B:  
LED Annunciator Module  
Red LED’s:  
Initiating Device Circuits Active (4),  
Notication/Release Circuits Active (4)  
Common Alarm (1)  
Green LED:  
AC Power  
Yellow LED’s: Initiating Device Circuits Troubles (4),  
Output Circuits Troubles (4)  
Supervisory Initiating Zone (4)  
Supervisory Bell Output Active (4)  
(1) each: Supervisory Zone, Supervisory 1, Supervisory 2, Power Trouble, Supervisory Trouble, System  
Trouble, Ground Fault, Discharging/Discharged, Alarm Silenced  
CONDITION  
Trouble  
Trouble  
Alarm  
Alarm  
Supervisory  
Supervisory  
Pre-discharge  
Discharged  
STATUS  
Non-Silenced  
Silenced  
Non-Silenced  
Silenced  
Non-Silenced  
Silenced  
LED State  
Flashing  
Steady ON  
Flashing  
Steady ON  
Flashing  
Steady ON  
Flashing  
Steady ON  
Control Buttons  
• Signal Silence - Momentary, silences signaling circuits, (except those activated by zones programmed as WATERFLOW)  
• System Reset - Momentary, resets all alarm circuits if condition has been corrected, removes power from initiating device circuits.  
• Scroll Up - Scrolls LCD display to most recent events  
• Scroll Down - Scrolls LCD display to previous events  
NOTE: Buzzer silence is accomplished by scrolling through all events.  
Circuit Parameters  
All voltages regulated DC  
Initiating Device Zones  
For connection of dry contact initiating devices and compatible 2 wire smoke detectors. (All values nominal)  
• 4 Class B, Style B (Class A Style D module available)*  
• Power limited, current limited to protect 2 wire smoke detectors  
• Maximum 2 wire 24VDC smoke detector load per zone - 2.5 ma (Use only detectors that are listed in compatibility list.)  
• Maximum Line resistance - 100 ohms (Except linear heat detection cable, 700 ohms per zone)  
• End-of-Line Resistance - 5.1K  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
• Normal standby current - approximately 4.0 mA  
• Standby voltage - 25VDC maximum, 13.4 minimum  
• Maximum short circuit current - approximately 36mA  
• Maximum Impedance for Alarm - 1400 ohms  
• Normal supervisory current - approximately 4mA  
• Low current trouble activation - approximately 3.3mA  
• Alarm activation current - approximately 10mA  
• Ripple voltage - .4 VDC  
• Maximum operating voltage range: 22.5 - 25.9V DC  
• Frequency - continuous  
* In programs 6-9, Zone 1 is a normally closed zone for Firecycle® Detectors  
Dedicated Supervisory Zones  
• For dry contact supervisory devices such as tamper, low air, or high air switches  
• 2 Class B Style B circuit, latching  
• Power limited, current limited  
• End-of-Line resistance - 5.1K ohms  
• Ripple Voltage - .1 VDC  
• Frequency - continuous  
• Maximum voltage - 25VDC  
• Maximum short circuit current - approximately 36mA  
• Maximum line resistance - 100 ohms  
• Normal supervisory current - approximately 4mA  
• Low current trouble activation - approximately 3.3mA  
• Supervisory current condition - approximately 10mA  
(Does not include power for any auxiliary devices)  
Notication/Release Circuits  
The output circuits of the VFR-400 are Non-coded. This allows the use of visual and audible appliances on the same circuit. If  
temporal notication appliances are required for evacuation, selectable tone appliances such as the AMSECO H24W horn or  
SH24W Series strobe/horns or a temporal module such as AMSECO TMP1-3A or equivalents should be used.  
The notication outputs do not provide synchronization. If synchronization is required, use AMSECO SMD10-3A  
synchronization module or equivalent, as identied on page 55. The notication appliances shall be compatible with the sync  
module selected. The current requirements of the appliances, wire gauge, and length of wire run determine the maximum  
number of appliances that can be connected to one NAC and/or sync module. The maximum cannot exceed 1 amp or whatever  
the sync module selected can support, whichever is lower. The sync module shall be installed as per manufacturers instructions.  
Equivalent sync modules are shown on page 55.  
• 4 Class B Style Y (Class A Style Z module available for notication)  
• Reverse polarity upon activation  
• Power limited, Current limited  
• 24 VDC Regulated, rated 1 amp each, 2.5 amps total for all 4 circuits  
• End-of-Line-Resistor - 5.1k ohms  
• Frequency - continuous  
• Maximum voltage - 27 VDC  
• Ripple voltage - .3 VDC  
• Maximum resistance for outputs programmed as RELEASING:  
1 divided by the current draw of the solenoid when activated  
• Normal standy supervisory current - approximately .38mA  
• Low current trouble activation - .11mA  
• Maximum impedance - 5 Ohms  
• High current trouble activation - .63ma  
Low/Missing Battery  
Causes battery and system trouble if battery falls below 22 volts. Battery circuit is fused and reverse polarity protection is provided.  
Input Power  
• Universal Input 120VAC, (60 Hz, 165VA) or 220VAC, (50 Hz, 185VA) 15 Amp Branch Line overcurrent  
protection required.  
• System trouble is also generated if voltage drops below 102V.  
Backup Power Requirements  
• VFR-400 - Standby 121 mA, alarm 274 mA at 24VDC  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Service Use  
NFPA 13 - Automatic Sprinkler  
NFPA 15 - Water Spray Fixed System  
NFPA 16 - Foam Water Sprinkler and Foam Water Spray  
NFPA 72 - National Fire Alarm Code  
• Local  
• Remote Station (protected premise unit)  
• Central Station (protected premise unit)  
NFPA 750 - Water Mist  
Listings And Approvals  
VFR-400 - UL Standard 864, ULC Standard S527, FM, CSFM and NYMEA  
Terminals  
• All terminals capable of handling #14 AWG wire  
• All terminations have transient protection  
• All four initiating device circuit terminals capable of handling linear heat detection.  
Relay Outputs  
• Common system alarm contacts SPDT rated 3 Amps, 30VDC resistive  
• Common supervisory contacts SPST, N.O. rated 3 Amps, 30VDC resistive  
• Common system trouble contacts SPDT rated 3 Amps, 30VDC resistive  
• Common system waterow contacts SPST, N.O. rated 3 Amps, 30VDC resistive  
Auxiliary Power  
• Auxiliary Power - 24VDC regulated. Rated 200 mA max. Current limited  
• Resettable for 4-wire smoke detectors  
Annunciator Connection  
• Auxiliary Power - 24VDC regulated. Rated 200 mA max. Current limited for RA-4410-RC Annunciator, non-resettable power  
• RS-485 For connection to RA-4410-RC remote annunciator  
• Maximum 2000' with 22 AWG, 4000' with 20 AWG shielded cable  
Optional Accessories  
CA2Z module (Class A initiating device circuit)  
Converts two Class B initiating device circuits to two Class A circuits.  
CAM Module (Class A Indicating Appliance Circuit)  
Converts indicating appliance circuit from Class B to Class A. One model CAM (Class A Module) is required  
for each circuit. (Do not use this on an output programmed as “TROUBLE BELL”.)  
ARM-1/ARM-2 Module (Auxiliary Relay Module)  
Activated by 24VDC Indicating and/or Releasing, polarity reversing circuits. The module provides a non-supervised DPDT Relay  
that can be used for fan shutdown, door release, elevator recall, etc.  
RA-4410RC (Remote Annunciator)  
Connects to RS-485 & 24VDC terminals. Provides 34 LED’s for each zone in alarm supervisory, or trouble, each output activated  
or in trouble, AC power, Power trouble, System trouble, Ground fault, Supervisory, Supervisory trouble, Alarm, Alarm silence and  
Pre-discharge/Discharge.  
Basic Operation  
In addition to the following events, the panel also provides an output via the RS-485 terminals to the RA-4410-RC remote  
annunciator to light the appropriate indicators. See remote annunciator operations, page 12. In addition, the remote annunciator  
has a silenceable buzzer that sounds on supervisory or trouble conditions.  
Initiating Device Circuits Alarm Condition  
An increase of current on any alarm initiating device circuit to approximately 10 mA or greater will result in the following:  
Alarm (Except zones programmed as LOW AIR ALARM):  
1) Activation of the common alarm relay contacts.  
2) Activation of the output circuit(s) which are mapped to the initiating device circuit(s). Providing all zone(s)  
necessary for the activation of those circuits is in alarm  
3) “ALARM” and zone # displayed on LCD.  
4) Activation of the red ALARM LED in a ashing mode as well as corresponding zone. NOTE: The ALARM LED will continue  
to ash until the Signal Silence button is pushed. The silence button will remove power from all outputs set up as Indicating  
except those activated by zones programmed as Waterow.  
5) Activation of zones programmed as waterow will operate the common waterow relay contacts in addition to the above.  
Note: If Zone 1 is programmed as Firecycle, an open circuit will result in the above.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Do not silence signals until all occupants are  
evacuated to a safe area.  
Low Air Alarm  
1) Operation of supervisory relay contacts and local buzzer.  
2) Activation of the notication appliance circuit(s) or releasing circuit(s) which are mapped to the initiating device circuit(s).  
Providing all zone(s) necessary for the activation of those circuits is in alarm  
3) LOW AIR ALARM and <CIRCUIT #> displayed on LCD.  
4) Activation of the amber supervisory LED in a ashing mode. NOTE: The supervisory LED will continue to ash until all  
events in the SUPERVISORY queue are viewed. This is accomplished by scrolling through all of the events by use of the  
scroll up and scroll down buttons. The LED will go steady after all alarm events have been viewed.  
Supervisory  
An increase of current to approximately 8 mA or greater on the supervisory initiating device circuit(s) or disabling an output  
programmed as releasing will result in the following:  
1) Operation of supervisory relay contacts and local buzzer.  
2) Operation of any output circuits that have been described as SUPERVISORY BELL.  
3) “SUPERVISORY”, “TAMPER”, “LOW AIR”, or “HIGH AIR” and <CIRCUIT> displayed on LCD.  
4) Activation of the amber SUPERVISORY LED in a ashing modes well as the corresponding zone LED. NOTE: The  
SUPERVISORY LED will continue to ash until all events in the SUPERVISORY queue are viewed. This is accomplished by  
scrolling through all of the events by use of the scroll up and scroll down buttons. The LED will go steady after all supervisory  
events have been viewed.  
Trouble Conditions  
Initiating Device Circuits  
A decrease of current to approximately 3.3 mA or programming the zone as disabled on any initiating device circuit will result in  
the following:  
1) Activation of trouble relay contacts and local buzzer.  
2) Operation of any output circuits which have been described as TROUBLE BELL.  
3) “TROUBLE” and <CIRCUIT> displayed on LCD.  
4) Activation of the amber TROUBLE LED in a ashing mode as well as corresponding zone. NOTE: The TROUBLE LED  
will continue to ash until all events in the TROUBLE queue are viewed. This is accomplished by scrolling through all of the  
events by use of the scroll up and scroll down buttons. The LED will go steady after all trouble events have been viewed.  
Note: When the circuits are operated in the Class A mode any trouble condition will require manual operation of the reset switch  
to restore the panel to normal after the fault has been removed.  
A complete loss of power will result in the transfer of the common system trouble relay contacts.  
If Zone 1 is programmed as Firecycle, an increase in current to 10 mA or greater will result in the above.  
Notication Appliance/Releasing Circuits  
An increase of current to approximately 0.63 mA or a decrease in current to approximately 0.11 mA on any output circuit or  
connecting an indicating appliance backwards, or disabling an output will result in the following:  
1) Activation of trouble relay contacts and local buzzer.  
2) Operation of any output circuits which have been programmed as TROUBLE BELL. If this output is in trouble, a  
TROUBLE BELL on this output may not function correctly, depending on the type of trouble.  
3) “TROUBLE” and “OUTPUT #” <CIRCUIT NO.> displayed on LCD.  
Note: A current in excess of 2.5 Amps, when the panel is in the alarm condition, will result in an output trouble as described above.  
A problem in an audible or visual device may not be apparent when the panel is in a normal condition. If the circuit indicates a  
trouble condition when the panel is in an alarm condition the problem must be located and corrected.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Ground Fault  
A short between any circuit and earth ground will result in the following:  
1) Activation of trouble relay contacts, trouble LED in a ashing mode, and local buzzer.  
2) Operation of any output circuits which have been described as TROUBLE BELL.  
3) “TROUBLE” and “GROUND” displayed on LCD.  
Loss Or Reduction Of AC Power  
A reduction in the AC input voltage will result in the following:  
1) Activation of amber trouble LED in a ashing mode and local buzzer.  
2) Operation of any output circuits which have been described as TROUBLE BELL.  
3) “TROUBLE” and “A.C.” displayed on LCD.  
4) LCD Backlight will be extinguished.  
5) Loss of green AC LED.  
6) The trouble relay contacts will transfer after 90 minutes.  
Low Battery Voltage  
Loss of or reduction of battery voltage to 22 volts will result in the following:  
1) Activation of common trouble relay contacts, amber trouble LED in a ashing mode and local buzzer.  
2) Operation of any output circuits that have been described as TROUBLE BELL.  
3) “TROUBLE” and “BATTERY” displayed on LCD.  
Loss Of Auxiliary Power Output  
Loss of output of the auxiliary power will result in the following:  
1) Activation of trouble relay contacts, trouble LED in a ashing mode and local buzzer.  
2) Operation of any output circuits that have been described as TROUBLE BELL.  
3) “TROUBLE” and “AUX LOW” displayed on LCD.  
4) Activation of amber POWER TROUBLE LED.  
5) Activation of amber SYSTEM TROUBLE LED.  
To Silence The Buzzer Or Outputs That Have Been Described As Trouble Or Supervisory Bell  
Press the scroll up or scroll down buttons. Once all events in the trouble or supervisory queue have been viewed, the buzzer and  
appropriate output will silence. The applicable system TROUBLE or SUPERVISORY LED will change from ashing to steady.  
Note: Any continuous trouble conditions that have been silenced automatically resound 24 hours after the rst trouble condition was silenced.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
To Silence A Signaling Appliance  
Press the SIGNAL SILENCE button. All silencable outputs will de-activate. A trouble condition will be created and the amber  
Alarm Silenced LED will light.  
Where audible and/or visual indicators are being used as an evacuation signal, do not silence an alarm condition without  
investigating and determining that an emergency condition does not exist.  
Notes: 1) Alarms initiated from zones that are in the waterow mode cannot be silenced. The panel must be reset to silence  
audible alarm devices.  
2) If silenceable waterow indication is desired it must be programmed as conventional alarm and annunciated on the  
zone identication portion of the LCD.  
To Reset an Alarm or Supervisory Condition  
1) Determine the cause of the alarm condition and if necessary remove the cause.  
2) Press the reset button.  
To Reset A Trouble Condition  
1) Determine the cause of the trouble condition and remove the cause.  
2) This circuit is self-restoring. When all trouble conditions are removed all indications will return to normal.  
Note: When an initiating device zone is operated in a Class A (Style D) mode any trouble condition will require manual  
operation of the reset switch to restore the panel to normal after the fault has been corrected.  
Lamp Test  
When the panel is in a Normal Condition, pushing the top two buttons will illuminate all of the LED's and display for  
approximately one second.  
Remote Annunciator Model RA-4410RC Operation  
Red LED’s:  
Initiating Device Circuits Active (4)  
Notication/Release Circuits Active (4)  
Common Alarm (1)  
Green LED’s:  
AC Power  
Yellow LED’s: Initiating Device Circuits troubles (4)  
Output Circuit Troubles (4)  
supervisory Bell Output Active (4)  
(1) each: Supervisory Zone, Power Trouble, Supervisory Trouble, System Trouble, Ground Fault, Discharging/Discharged, Alarm Silenced  
RA-4410RC  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
AC POWER  
SUPERVISORY 1  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SUPERVISORY 2  
LAMP TEST  
COMMON ALARM  
ALARM SILENCE  
STEADY: DISCHARGE  
GROUND FAULT  
FLASHING: PRE-DISCHARGE  
DWG# 3550-17VKG  
Basic Operation  
The appropriate LED ashes to indicate a change of status on the panel. A trouble or supervisory condition will ash  
the appropriate Yellow LED indicating the location of the condition. If any outputs are programmed as TROUBLE or  
SUPERVISORY BELL, that Yellow output LED will ash indicating the output is activated. Pressing the BUZZER SILENCE  
button on the panel changes the ashing zone Amber LED to steady on and turns the ashing Yellow output LED off.  
An alarm or low air alarm condition will ash a Red LED indicating the zone in alarm and any outputs mapped to that zone that  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
have activated. Pressing the SIGNAL SILENCE button changes the ashing Red Zone LED to steady on and the ashing Red  
Output LED mapped to that zone off unless the output is programmed as RELEASE. In addition, the Yellow ALARM/ SILENCE  
LED will light.  
Any zone programmed as WATERFLOW is considered non-silenceable so the signal and buzzer silence buttons will have no  
effect on the ashing zone and output LED's. A buzzer on the annunciator sounds for any trouble condition. When the panel  
has a trouble or supervisory condition, pressing the SILENCE/LAMP TEST button silences the condition at the panel and all  
annunciators. When the panel is in a normal state, pressing the SILENCE/LAMP TEST button can be used to test the LED's.  
The release panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and  
24VDC power requirements of the RA-4410-RC. Separate cables should be used for power and communication. Shielded cable  
shall be used for the communication line. Up to three annunciators can be connected to one panel. A rotary switch is provided on  
the panel to indicate how many annunciators are connected. Another rotary switch is on the annunciator to set the address. The  
annunciators must be addressed consecutively. See page 54 for wiring information. Refer to bulletin #8840024 for installation  
instructions and maximum wire run.  
Test Procedure  
The system should be inspected, tested, and maintained in accordance with NFPA-72 National Fire Alarm Code, Chapter 10 and  
any other requirements of the local authority having jurisdiction.  
Test Procedure(Canada)  
The system should be inspected, tested, and maintained in accordance with ULC Standard CAN/ULC-S536 and any other  
requirements of the local authority having jurisdiction.  
Testing should be done as a minimum as described below:  
1) Notify the re department or other receiving station if alarm, supervisory and/or trouble signals are transmitted.  
2) Notify the proper building personnel so that audible and/or visual signals can be ignored.  
3) If the release panel is monitored by a building re alarm panel, take appropriate action to eliminate any unwanted events.  
4) Momentarily open each of the following circuits.  
a) Each initiating device zone  
b) Supervisory circuit  
c) Indicating Appliance/Releasing circuit - observe that this results in a trouble condition and all indicators operate as  
described in the appropriate preceding section for the particular circuit that is faulted.  
5) Move the PROGRAM switch down. The LCD should respond: “LOOK AT HISTORY?”. Press the FUNCTION button  
until the display reads PASSWORD=000. Enter password if changed from factoy or press the SET button three times. Press  
the FUNCTION (bottom) button until the LCD reads “SYSTEM MODE: NORMAL”. Press the SELECT button. The LCD  
will read “SYSTEM MODE:  
ONE MAN WALKTEST”. Press the SET button then move the PROGRAM switch up. The panel will respond with “ONE  
MAN WALKTEST” and the time. The trouble LED will light. Any output described as “RELEASING” will automatically be disabled.  
Failure to enter the walktest mode and subsequent operation  
of initiating zones may result in a release.  
After 30 minutes of no activity in the walk test mode the panel automatically reverts to normal operation.  
6) Operate each initiating device on all zones. All audible and visual alarm devices should operate for about 3 seconds. Then the  
system will automatically reset allowing the user to go to the next initiating device.  
7) Operate each initiating device on the supervisory circuit. Observe that all the indications described in the section on  
supervisory conditions occur.  
8) Move the PROGRAM switch down again. The LCD should respond: “LOOK AT HISTORY?”  
Press the FUNCTION button until the display reads PASSWORD=000. Enter password if changed from factory or press the  
SET button three times.  
Press the FUNCTION (bottom) button until the LCD reads: “SYSTEM MODE: ONE MAN WALKTEST”  
Press the SELECT (middle) button. The LCD will read: “SYSTEM MODE: NORMAL”  
Press the SET (top) button then restore the PROGRAM switch to the up position. The LCD will show the normal banner message.  
9) All audible and visual indicators should be off.  
10) Notify all building, re department, and/or other receiving station personnel that the test has concluded.  
Maintenance: Test batteries per local and national standards. At a minimum replace batteries every four (4) years or sooner  
depending on test results. The date of purchase shall be marked on all batteries.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Programming Mode Instructions  
To use the Programming Mode push the program switch down (see drawing below).  
Panel Visual Display  
As a general rule, the following applies on the Programming Mode buttons:  
The top button (SET) sets the message on the display into the memory.  
The middle button (SELECT) scrolls through the selections available for the function displayed.  
The bottom button (FUNCTION) allows the user to skip the function without changing the program.  
ZONE 1  
ZONE 2  
OUTPUT 2  
OUTPUT 1  
OUTPUT 3  
OUTPUT 4  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
AC POWER  
POWER TBL  
SYSTEM TBL  
SUPTBL  
SUPERVISORY 1  
SCROLL-UP  
BUZZER SILENCE  
SUPERVISORY 2  
COMMONALARM  
ALARM SILENCE  
RUN  
LAMP  
TEST  
}
PROGRAM  
GROUND  
FAULT  
STEADY: DISCHARGE  
FLASHING:  
PRE-DISCHARGE  
SCROLL-DOWN  
BUZZER SILENCE  
SET  
SELECT  
SIGNAL SILENCE  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
DWG# 3550-18VKG  
To program, push the Program Switch down.  
There is no capability to back up screens in the program mode. If a mistake was made during programming, move the program  
switch back up, then move it down and start from the beginning.  
To exit the program mode at any time, move the Program Switch up.  
When the programming switch is down (see Panel Visual Display) the following will appear in the display window:  
L
O
I
O
S
K
T
A
R
T
H
O
Y
?
History  
To examine the HISTORY press the top button, the display window will show the time and date of the last event or action. To skip  
to the next function or to exit history, press the FUNCTION (bottom) button.  
SET  
Press the SET button to discover the time and date of the last event or action and to scroll forward.  
To scroll back, press the SELECT button.  
SELECT  
FUNCTION  
To exit or skip HISTORY, press the bottom button.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
S
E
T
T
I
M E  
?
Date/Time  
SELECT  
To change the time, press the SELECT button.  
FUNCTION  
To exit to the next function, press the bottom button.  
If the middle button is pushed, the date and time will appear in the display window:  
0
1
/
0
5
/
2
0
0
7
The date is shown at the top and the time at the bottom of the display window. “MINUTES” indicates that the user can now  
change the minutes.  
SET  
Pressing the SET button will decrease the minutes  
SELECT  
FUNCTION  
Pressing the SELECT button will increase the minutes.  
When nshed setting the minutes, Press the bottom button. The minutes will change to hours.  
Continue this process and change the DAY, MONTH and YEAR. When you have nished changing the year, press the  
FUNCTION (bottom) button. A display similar to the following will appear:  
P
A
S
S
W O  
R
D
=
0
0
0
^
Password  
This display prevents unauthorized programming of the panel by requiring the user to enter the proper password. To select the  
appropriate number for the space indicated by the ^ symbol, press the SELECT button. When the proper number is displayed  
press the SET button to set the number and move to the next space. If the wrong password is entered, the panel will display "Push  
Programming Switch Up". All panels are shipped from the factory with a password of 000. If the password is lost contact Potter.  
SET  
After selecting the desired number, press the SET button to set and move to the next number.  
Press the SELECT button to scroll through the numbers.  
SELECT  
FUNCTION  
Pressing the bottom button will have no effect.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
After entering the correct password, a display similar to the following will appear:  
I
N
N
I
T
B
Z
E
O
D
N
E
#
1
E
A
L
Zone Disabled/Enabled  
This display allows the user to ENABLE or DISABLE Initiating zones. This display window shows that initiating ZONE #1 is  
enabled. To toggle from ENABLED to DISABLED or visa versa, press the SELECT button.  
SET  
After selecting ENABLED or DISABLED, press the SET button to set and move to the  
next zone.  
SELECT  
FUNCTION  
Press the SELECT button to toggle between ENABLED or DISABLED.  
To skip to the next function, press the bottom button.  
After selecting all four zones or pressing the FUNCTION (bottom) button, the following will appear in the display window:  
O
E
U
N
T
P
U
L
T
E
#
1
A
B
D
Output Enable/Disable  
This display allows the user to ENABLE or DISABLE any of the output circuits.  
SET  
After selecting ENABLED or DISABLED, press the SET button to set and move to the next output.  
SELECT  
FUNCTION  
Press the SELECT button to toggle between ENABLED or DISABLED.  
To skip to the next function, press the bottom button.  
After selecting all four outputs or pressing the FUNCTION (bottom) button, the following will appear in the display window:  
Disabling any input or outputs will create a trouble condition on the panel.  
Disabling a releasing circuit will create a supervisory condition.  
S
Y
O
S
T
E
M
L
M O  
D
E
:
N
R
M
A
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
One Man Walktest  
This display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the SELECT button to  
toggle back and forth from NORMAL to ONE MAN WALKTEST. When the desired mode is displayed, press the SET button.  
If ONE MAN WALKTEST is selected for test purposes, the display must be restored to the NORMAL setting after the test is  
completed by toggling to it using the SELECT button.  
After 30 minutes of no activity the panel  
automatically reverts to normal.  
SET  
After selecting NORMAL or ONE MAN WALKTEST, press the SET button to set that mode.  
Press the SELECT button to toggle between NORMAL and CROSS ZONED.  
Press the bottom button to skip to the next function.  
SELECT  
FUNCTION  
After selecting the operating mode or pressing the FUNCTION button a display similar to the following will appear in the display  
window:  
P
R
O
G
R
A
M
#
1
VFR-400 Standard Program Information  
The VFR-400 has 12 standard programs which are detailed in the following pages. Selecting one of these programs will  
automatically program every function of the panel except the custom banner and zone message functions.  
Notes:  
The release discharge time is continuous for all programs not employing the Firecycle feature. The default soak timer for the  
Firecycle feature is continuous.  
The following is an explanation of how the various programs operate and information about the types of  
devices that are to be connected to the input and output zones. If none of the standard programs are acceptable for the installation  
required, select the custom program #0 then press the SET button. This will allow the user to custom program the panel. Turn to  
page 45 for custom program information.  
Type  
Description  
Alarm Zones  
Detection  
Waterow  
Smoke Detectors, Spot Type Heat Detectors  
PS10 Pressure Switch  
Linear Heat  
Manual Release  
Firecycle  
Cable Type Heat Detectors  
Pull Stations  
Viking normally closed heat detectors  
Supervisory Zones  
Supervisory  
Low Air supervisory  
High Air  
Valve Tamper, Low Air, High Air, Room Temperature  
Low Air Switch  
High Air Switch  
Tamper  
Valve Tamper Switch  
Low Air Alarm *  
PS10, PS40  
* Not available on Supervisory Zones Sup 1 or Sup 2  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Outputs  
Alarm  
Release  
24VDC Bells, Horns, Strobes, to indicate an alarm condition.  
Solenoid Valve, Squib, Releasing Mechanism  
Supervisory 24VDC Bells, Horns, Strobes, to indicate a supervisory condition.  
Trouble 24VDC Bells, Horns, Strobes, to indicate a trouble condition.  
To program the VFR-400 to operate with one of the following 12 standard programs:  
1) Press SELECT button to scroll to the program number (#1 thru #12) you desire.  
2) Press SET button.  
3) Turn to page 48 to program the banner message and to nish programming the panel.  
SET  
After selecting the proper program number, press the SET button to set the program and move to the next function.  
SELECT  
FUNCTION  
Press the SELECT button to scroll through the programs.  
Press the bottom button to skip to the next function.  
After selecting the desired program number with the middle button, SET must be pressed to set the program.  
When the Firecycle programs (6-9) are selected, only outputs #3 and #4 can be selected as releasing.  
If the Firecycle feature is used, Firecycle heat detectors must be connected to Zone 1. Zone 1 follows the status of the Firecycle  
detector. When the detector resets, a soak timer is initiated. The default soak timer is continuous. The soak timer is user  
selectable to 30, 60, or 90 seconds or 2 - 20 minutes in 1 minute increments.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
This page intentionally left blank.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #1  
For One Sprinkler System  
Viking Sprinkler  
System Types  
2 Release Zones,  
Waterow Zone,  
& Manual Release  
Zone  
1. Single Interlocked Preaction System with Electric Release  
2. Deluge System with Electric Release  
3. Non-Interlocked Preaction System with Electric Release  
4. Double Interlocked Preaction System with Electric/Pneumatic Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Low Air  
Valve Tamper  
Conventional  
Conventional Waterow  
Manual  
Supervisory Zone Supervisory Zone Detection Zone Detection Zone  
Zone  
X
Release Zone  
#1 General Alarm  
#2 Waterow  
X
X
X
X
X
X
#3 Release Solenoid  
#4 Supervisory Bell  
X
X
X
OPERATION DESCRIPTION  
Inputs:  
2 Conventional Detection zones, 1 Waterow zone, 1 Manual Release zone, 2 Supervisory zones  
Outputs:  
Operation:  
1 General Alarm, 1 Waterow Alarm, 1 Solenoid Release, 1 Supervisory Bell  
Activation of Conventional Detection zone #1 or #2 or Manual Release zone #4 will activate output #3  
(Release Solenoid) and output #1 (General Alarm)  
Activation of Waterow zone #3 will activate output #2 (Waterow) and output #1 (General Alarm)  
Activation of Low Air Supervisory zone #1 or Valve Tamper Supervisory zone #2 will operate output #4  
(Supervisory Bell).  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid). Black wire to positive  
terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
SUPERVISORY  
SWITCH  
CONVENTIONAL WATER  
DETECTION  
FLOW  
SWITCH  
09470  
MANUAL  
RELEASE  
STATION  
VALVE  
TAMPER  
CONVENTIONAL  
09472  
EOLR  
DETECTION  
EOLR  
SUPERVISORY  
EOLR  
5.1K  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
ZONE 2  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
5.1K  
EOLR  
GENERAL  
ALARM  
RELEASE SUPERVISORY  
WATERFLOW  
SOLENOID  
BELL  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #1”.  
8. Press the SELECT button until the display reads “PROGRAM #1”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #2  
For Two Sprinkler Systems Operating Independantly From Each Other  
Viking Sprinkler  
System Types  
2 Split Release  
Zones and 2  
Waterow Zones  
1. Single Interlocked Preaction System with Electric Release  
2. Deluge System with Electric Release  
3. Non-Interlocked Preaction System with Electric Release  
4. Double Interlocked Preaction System with Electric/Pneumatic Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Valve Tamper  
Low Air  
Conventional  
Conventional Waterow Waterow  
Supervisory Zone Supervisory Zone Detection Zone Detection Zone Zone for  
for Systems 1 & 2 for Systems 1 & 2 for System 1  
Zone for  
System 2  
for System 2  
System 1  
#1 General Alarm  
#2 Release Solenoid #1  
#3 Release Solenoid #2  
#4 Waterow  
X
X
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
2 Conventional Detection zones, 2 Waterow zones, 2 Supervisory zones  
Outputs:  
Operation:  
1 General Alarm, 1 Waterow Alarm, 2 Solenoid Release  
Activation of Conventional Detection zone #1 will activate output #2 (Release Solenoid #1) and  
output #1 (General Alarm)  
Activation of Waterow zone #3 will activate output #2 (Waterow) and output #1 (General Alarm)  
Activation of Conventional Detection zone #2 will activate output #3 (Release Solenoid #2) and  
output #1 (General Alarm)  
Activation of Waterow zone #3 or #4 will activate output #1 (General Alarm) and output #4  
(Waterow)  
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will operate  
supervisory trouble relay.  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
WATER  
FLOW  
WATER  
FLOW  
VALVE SUPERVISORY  
CONVENTIONAL  
DETECTION  
TAMPER  
SWITCH  
SUPERVISORY SYSTEMS  
SWITCH  
SYSTEM 1  
09470  
SWITCH  
SYSTEM 2  
09470  
CONVENTIONAL  
SYSTEM 2  
SYSTEMS  
1&2  
1&2  
09472  
EOLR  
DETECTION  
SYSTEM 1  
EOLR  
EOLR  
EOLR  
5.1K  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
ZONE 2  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
RUN  
LAMP TEST  
ALARM SILENCE  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
GENERAL  
ALARM  
RELEASE  
SOLENOID SOLENOID  
SYSTEM 1 SYSTEM 2  
RELEASE WATERFLOW  
DWG#14165VKG PRGM2  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #2”.  
8. Press the SELECT button until the display reads “PROGRAM #2”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #3  
For One Sprinkler System  
Viking Sprinkler  
System Types  
2 Cross Release  
zones, Waterow  
zone, and Manual  
Release zone  
1. Double Interlocked Preaction System with Electric/Pneu-Lectric Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Low Air  
Valve Tamper  
Conventional  
Low Air  
Waterow  
Manual  
Supervisory Zone Supervisory Zone Detection Zone Alarm Zone  
Zone  
Release Zone  
#1 General Alarm  
#2 Waterow  
X
X
X
X
#3 Release Solenoid  
#4 Supervisory Bell  
X X  
X X  
X
X
X
OPERATION DESCRIPTION  
Inputs:  
1 Conventional Detection zone cross zoned with 1 Low Air Alarm zone, 1 Waterow zone, 1 Manual  
Release zone, 2 Supervisory zones  
Outputs:  
1 General Alarm, 1 Waterow, 1 Release Solenoid, 1 Supervisory Bell  
Operation:  
Simultaneous activation of both the Conventional Detection zone #1 and the Low Air Alarm zone #2  
will activate output #3 (Release solenoid) and output #1 (General alarm)  
Activation of Conventional Detection zone #1 will activate output #1 (General Alarm)  
Activation of Low Air Alarm zone #2 will activate output #4 (Supervisory Bell)  
Activation of Waterow zone #3 will activate output #2 (Waterow)  
Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1  
(General Alarm)  
Activation of Low Air Supervisory zone #1 or Valve Tamper Supervisory zone #2 will operate output  
#4 (Supervisory Bell)  
XX = Cross zoned  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid). Black wire to positive  
terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
ALARM  
SWITCH  
09473  
LOW AIR  
PRESSURE  
SUPERVISORY  
SWITCH  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
VALVE  
TAMPER  
SWITCH  
09470  
CONVENTIONAL  
DETECTION  
EOLR  
09473  
EOLR  
SUPERVISORY  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
ZONE 4  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
5.1K  
EOLR  
GENERAL  
ALARM  
RELEASE SUPERVISORY  
WATERFLOW  
DWG# 14166 VKG PRGM3  
SOLENOID  
BELL  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #3”.  
8. Press the SELECT button until the display reads “PROGRAM #3”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #4  
For Two Sprinkler Systems - Operating Simultaneously  
Viking Sprinkler  
System Types  
2 Dual Release  
1. Single Interlocked Preaction System with Electric Release  
2. Deluge System with Electric Release  
Zones, Waterow  
Zone, and Dual  
Manual Release  
3. Non-Interlocked Preaction System with Electric Release  
4. Double Interlocked Preaction System with Electric/Pneumatic Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Valve Tamper  
Low Air  
Conventional  
Conventional Waterow  
Manual  
Release Zone  
Supervisory Zone Supervisory Zone Detection Zone Detection Zone  
for Systems 1 & 2 for Systems 1 & 2 for System 1  
Zone  
X
for System 2  
#1 General Alarm  
#2 Release Solenoid #1  
#3 Release Solenoid #2  
#4 Waterow  
X
X
X
X
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
2 Conventional Detection zones, 1 Waterow zone, 1 Manual Release zone, 2 Supervisory zones  
Outputs:  
Operation:  
1 General Alarm, 1 Waterow, 2 Release Solenoids  
Activation of Conventional Detection zone #1 or #2 or Manual Release zone will activate output #2  
(Release Solenoid #1) and output #3 (Release Solenoid #2) and output #1 (General Alarm)  
Activation of Waterow zone #3 will activate output #4 (Waterow)  
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will operate  
supervisory trouble relay  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
VALVE  
CONVENTIONAL  
DETECTION  
TAMPER  
WATER  
FLOW  
SUPERVISORY  
SUPERVISORY  
MANUAL  
RELEASE  
STATION  
SWITCH CONVENTIONAL  
09472  
SYSTEMS 1&2  
SYSTEM 2  
SWITCH  
09470  
SYSTEMS  
DETECTION  
SYSTEM 1  
EOLR  
1&2  
EOLR  
5.1K  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
ZONE 2  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
GROUND  
FAULT  
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
5.1K  
EOLR  
GENERAL  
ALARM  
RELEASE  
SOLENOID  
SYSTEM 1  
RELEASE WATERFLOW  
SOLENOID  
DWG# 14167 VKG PRGM4  
SYSTEM 2  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #4”.  
8. Press the SELECT button until the display reads “PROGRAM #4”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #5  
For One Sprinkler System- NYC Special  
Viking Sprinkler  
System Types  
Release Zone and 1. Single Interlocked Preaction System with Electric Release  
Manual Release  
2. Deluge System with Electric Release  
Zone  
3. Non-Interlocked Preaction with Electric Release  
4. Double Interlocked Preaction System with Electric/Pneumatic Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Valve Tamper  
Low Air  
Conventional Low Air Alarm Waterow  
Manual  
Supervisory Zone Supervisory Zone Detection Zone  
Zone  
X
Zone  
X
Release Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 Trouble Bell  
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
1 Conventional Detection zone, 1 Waterow zone, 1 Low Air Alarm zone, 1 Manual Release zone, 2  
Superviosry zones  
Outputs:  
1 General Alarm, 1 Trouble Bell, 1 Release Solenoid, 1 Supervisory Bell  
Operation:  
Activation of Conventional Detection zone #1 or Manual Release zone #4 will activate output #3  
(Release Solenoid) and output #1 (General Alarm)  
Activation of Waterow zone #3 will activate output #1 (General Alarm)  
Activation of Low Air Alarm zone or Low Air Supervisory zone or Valve Tamper Supervisory zone  
will activate output #2 (Supervisory Bell)  
A trouble condition, (low battery, wire short in outputs, loss AC, panel problem) will activate output  
#4 (Trouble Bell) and trouble relay  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
ALARM  
SWITCH  
09473  
LOW AIR  
PRESSURE  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
SUPERVISORY  
SWITCH CONVENTIONAL  
09473  
EOLR  
VALVE  
TAMPER  
SWITCH  
09470  
DETECTION  
EOLR  
SUPERVISORY  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SYSTEM RESET  
SELECT  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
5.1K  
EOLR  
GENERAL  
ALARM  
RELEASE  
SOLENOID  
TROUBLE  
BELL  
SUPERVISORY  
BELL  
DWG# 14168 VKG PRGM5  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #5”.  
8. Press the SELECT button until the display reads “PROGRAM #5”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #6  
For One Sprinkler System  
Viking Sprinkler  
System Types  
Release Zone and 1. FIRECYCLE III Single Interlocked Preaction Multicycle System  
Manual Release  
2. FIRECYCLE III Single Interlocked Preaction Multicycle System - NYC Special  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Low Air  
Valve Tamper  
FIRECYCLE  
Low Air  
Waterow  
Manual  
Supervisory Zone Supervisory Zone Detector Zone  
Alarm Zone  
Zone  
Release Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 N/O Solenoid  
X
X
X
X
X
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
FIRECYCLE Detector zone, Low Air Alarm zone, 1 Waterow zone, Manual Release zone, 2  
Supervisory zones  
Outputs:  
1 General Alarm, 1 Supervisory Alarm, 1 Release Solenoid, and 1 N/O Solenoid  
Operation:  
Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release  
Solenoid), and output #4 (N/O Solenoid)  
Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O  
Solenoid)  
Activation of Waterow zone #3 will activate output #1 (General Alarm) and output #4 (N/O Solenoid)  
Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release  
Solenoid)  
Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete  
output #3 (Release Solenoid) is deactivated  
Activation of Low Air Supervisory Zone #1 or Valve Tamper Supervisory zone #2 will activate output #2  
(Supervisory Bell)  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See specic system type data page for proper pressure switch settings.  
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.  
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.  
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.  
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
ALARM  
SWITCH  
09473  
LOW AIR  
PRESSURE  
SUPERVISORY  
SWITCH  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
VALVE  
TAMPER  
SWITCH  
09470  
FIRECYCLE  
DETECTORS  
EOLR  
09473  
EOLR  
SUPERVISORY  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 4  
ZONE 1  
ZONE 2  
ZONE 3  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO NC  
COM NO COM  
NO  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
GENERAL  
ALARM  
RELEASE  
N/O  
SUPERVISORY  
BELL  
SOLENOID SOLENOID  
DWG# 14169 VKG PRGM6  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #6”.  
8. Press the SELECT button until the display reads “PROGRAM #6”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #7  
For One Sprinkler System  
Viking Sprinkler  
System Types  
2 Cross Release 1. FIRECYCLE III Double Interlocked Preaction Multicycle System  
Zones and  
2. FIRECYCLE III Double Interlocked Preaction Multicycle System - NYC Special  
Manual Release  
Zone  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Low Air  
Valve Tamper  
FIRECYCLE  
Low Air  
Waterow  
Manual  
Supervisory Zone Supervisory Zone Detector Zone  
Alarm Zone  
Zone  
Release Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 N/O Solenoid  
X
X
X
X
X
X
X
X X  
X
X X  
X
OPERATION DESCRIPTION  
Inputs:  
1 FIRECYCLE Detector zone, 1 Low Air Alarm zone, 1 Waterow zone, 1 Manual Release zone, 2  
Supervisory zones  
Outputs:  
1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, and 1 N/O Solenoid  
Operation:  
Simultaneous activation of both the FIRECYCLE Detector zone #1 and the Low Air alarm zone #2 will  
activate output #1 (General Alarm) and output #3 (Release Solenoid)  
Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm)  
Activation of Low Air Alarm zone #2 alone will activate output #2 (Supervisory Bell) and output #4  
(N/O Solenoid)  
Activation of Waterow zone #3 will activate output #1 (General Alarm) and output #4 (N/O solenoid)  
Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release  
Solenoid)  
Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete the  
output #3 (Release Solenoid) is deactivated.  
Activation of Low Air Supervisory zone #1 or Valve Tamper Supervisory zone #2 will activate output #2  
(Supervisory Bell)  
XX = Cross-Zoned  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See specic system type data page for proper pressure switch settings.  
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.  
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.  
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) to drop out.  
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
ALARM  
SWITCH  
09473  
LOW AIR  
PRESSURE  
SUPERVISORY  
SWITCH  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
VALVE  
TAMPER  
SWITCH  
09470  
FIRECYCLE  
DETECTORS  
EOLR  
09473  
EOLR  
SUPERVISORY  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
ZONE 4  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
COM NO NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
GENERAL SUPERVISORY RELEASE  
ALARM  
N/O  
BELL  
SOLENOID SOLENOID  
DWG# 14171 VKG PRGM7  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #7”.  
8. Press the SELECT button until the display reads “PROGRAM #7”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #8  
For One Sprinkler System  
Viking Sprinkler  
System Types  
1 Release Zone 1. FIRECYCLE III Deluge Multicycle System  
and Manual  
Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Supervisory Zone  
Valve Tamper  
Supervisory Zone Detector Zone  
FIRECYCLE  
Supervisory  
Zone  
Waterow  
Manual  
Release Zone  
Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 N/O Solenoid  
X
X
X
X
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
1 FIRECYCLE Detection zone, 1 Supervisory zone, 1 Waterow zone, 1 Manual Release zone, 2  
Supervisory zones  
Outputs:  
1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, and 1 N/O Solenoid  
Operation:  
Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release  
Solenoid) and output #4 (N/O Solenoid)  
Activation of Supervisory zone #2 will activate output #2 (Supervisory Bell)  
Activation of Waterow Alarm zone #3 will activate output #1 (General Alarm) and output #4 (N/O  
Solenoid)  
Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release  
Solenoid)  
Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete the  
output #3 (Release Solenoid) is deactivated.  
Activation of Supervisory zone #1 or Valve Tamper Supervisory Zone #2 will activate output #2  
(Supervisory Bell)  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See specic system type data page for proper pressure switch settings.  
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.  
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.  
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.  
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
WATER  
FLOW  
VALVE  
TAMPER  
FIRECYCLE  
DETECTORS  
MANUAL  
RELEASE  
STATION  
SWITCH  
09470  
SUPERVISORY  
SUPERVISORY  
EOLR  
SUPERVISORY  
EOLR  
5.1K  
EOLR  
5.1K  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
ZONE 4  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SYSTEM RESET  
SELECT  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO NC  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
GENERAL SUPERVISORY RELEASE  
ALARM  
N/O  
BELL  
SOLENOID SOLENOID  
DWG# 14171 VKG PRGM8  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #8”.  
8. Press the SELECT button until the display reads “PROGRAM #8”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #9  
For One Sprinkler System  
Viking Sprinkler  
System Types  
1 Release Zone  
and Manual  
1. FIRECYCLE III Wet Multicycle System  
Release Zone  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Supervisory Zone  
Valve Tamper  
Supervisory Zone Detector Zone  
FIRECYCLE  
Supervisory  
Zone  
Waterow  
Manual  
Release Zone  
Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 N/O Solenoid  
X
X
X
X
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
1 FIRECYCLE Detection zone, 1 Supervisory zone, 1 Waterow zone, 1 Manual Release zone, 2  
Supervisory zones  
Outputs:  
1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, and 1 N/O Solenoid  
Operation:  
Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release  
Solenoid) and output #4 (N/O Solenoid)  
Activation of Supervisory zone #2 will activate output #2 (Supervisory Bell)  
Activation of Waterow Alarm zone #3 will activate output #1 (General Alarm) and output #4 (N/O  
Solenoid)  
Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release  
Solenoid)  
Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete the  
output #3 (Release Solenoid) is deactivated.  
Activation of Supervisory zone #1 or Valve Tamper Supervisory zone #2 will activate output #2  
(Supervisory Bell)  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See specic system type data page for proper pressure switch settings.  
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.  
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.  
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.  
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
VALVE  
WATER  
FLOW  
CONVENTIONAL  
DETECTION  
TAMPER  
MANUAL  
RELEASE  
STATION  
SUPERVISORY  
SWITCH  
09470  
SUPERVISORY  
EOLR  
SUPERVISORY  
EOLR  
EOLR  
5.1K  
EOLR  
5.1K  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 4  
ZONE 1  
ZONE 2  
ZONE 3  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
GROUND  
FAULT  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SELECT  
SYSTEM RESET  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO NC  
COM NO COM  
NO  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
GENERAL  
ALARM  
RELEASE  
N/O  
SUPERVISORY  
BELL  
DWG# 14172 VKG PRGM9  
SOLENOID SOLENOID  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #9”.  
8. Press the SELECT button until the display reads “PROGRAM #9”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #10  
For One Sprinkler System- NYC Special  
Viking Sprinkler  
System Types  
Release Zone and 1. SUREFIRE Single Interlocked Preaction System  
Manual Release  
2. SUREFIRE Single Interlocked Preaction System - NYC Special  
Zone  
3. SUREFIRE Single Interlocked Preprimed Preaction System  
4. SUREFIRE Single Interlocked Preprimed Preaction System - NYC Special  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Valve Tamper  
Low Air  
Conventional Low Air Alarm Waterow  
Manual  
Supervisory Zone Supervisory Zone Detection Zone  
Zone  
X
Zone  
X
Release Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 Trouble Bell  
X
X
X
X
X
X
OPERATION DESCRIPTION  
Inputs:  
1 Conventional Detection zone, 1 Waterow zone, 1 Low Air Alarm zone, 1 Manual Release zone, 2  
Superviosry zones  
Outputs:  
1 General Alarm, 1 Trouble Bell, 1 Release Solenoid, 1 Supervisory Bell  
Operation:  
Activation of Conventional Detection zone #1 will activate output #3 (Release Solenoid) and output  
#1 (General Alarm)  
Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O Solenoid)  
Activation of Waterow zone #3 will activate output #1 (General Alarm)  
Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1  
(General Alarm)  
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate  
output#2 (Supervisory Bell)  
A trouble condition will prevent output #4 (N/O Solenoid) from activating  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
9. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
ALARM  
SWITCH  
09473  
LOW AIR  
PRESSURE  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
SUPERVISORY  
VALVE  
TAMPER  
SUPERVISORY  
EOLR  
SWITCH  
09470  
SWITCH CONVENTIONAL  
09473  
EOLR  
DETECTION  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
GROUND  
FAULT  
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SYSTEM RESET  
SELECT  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO NC  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
DWG# 14173 VKG PRGM10  
GENERAL SUPERVISORY RELEASE  
ALARM  
N/O  
BELL  
SOLENOID SOLENOID  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #10”.  
8. Press the SELECT button until the display reads “PROGRAM #10”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #11  
For One Sprinkler System  
Viking Sprinkler  
System Types  
2 Cross Release  
Zones and Manual  
Release Zone  
1. SUREFIRE Double Interlocked Preaction System  
2. SUREFIRE Double Interlocked Preaction System - NYC Special  
3. SUREFIRE Double Interlocked Preprimed Preaction System  
4. SUREFIRE Double Interlocked Preprimed Preaction System - NYC Special  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Valve Tamper  
Low Air  
Conventional Low Air Alarm Waterow  
Manual  
Supervisory Zone Supervisory Zone Detection Zone  
Zone  
Zone  
X
Release Zone  
#1 General Alarm  
#2 Supervisory Bell  
#3 Release Solenoid  
#4 N/O Solenoid  
X
X
X
X
X
X X  
X
X X  
X
OPERATION DESCRIPTION  
Inputs:  
1 Conventional Detection zone, 1 Low Air Alarm zone, 1 Waterow zone, 1 Manual Release zone, 2  
Supervisory zones  
Outputs:  
1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, 1 N/O Solenoid  
Operation:  
Simultaneous activation of both the Conventional Detection zone #1 and the Low Air Alarm zone #2  
will activate output #3 (Release Solenoid) and output #1 (General Alarm)  
Activation of Conventional Detection zone #1 will activate output #1 (General Alarm)  
Activation of Low Air Alarm zone #2 will activate output #2 (Supervisory Bell) and output #4 (N/O  
Solenoid)  
Activation of Waterow zone #3 will activate output #1 (General Alarm)  
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate  
output#2 (Supervisory Bell)  
Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1  
(General Alarm)  
XX = Cross-Zoned  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
9. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW AIR  
PRESSURE  
ALARM  
SWITCH  
09473  
LOW AIR  
PRESSURE  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
SUPERVISORY  
VALVE  
TAMPER  
SUPERVISORY  
EOLR  
SWITCH  
09470  
SWITCH CONVENTIONAL  
09473  
EOLR  
DETECTION  
EOLR  
EOLR  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
RED OUTPUT LED STEADY: ABORT  
VFR -400  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
GROUND  
FAULT  
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SYSTEM RESET  
SELECT  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
EOL  
DIODE  
ASSY  
GENERAL SUPERVISORY RELEASE  
ALARM  
N/O  
BELL  
SOLENOID SOLENOID  
DWG# 14175 VKG PRGM11  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #11”.  
8. Press the SELECT button until the display reads “PROGRAM #11”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
PROGRAM #12  
For One Sprinkler System  
Viking Sprinkler  
System Types  
2 Cross Release  
Zones, Waterow  
Zone, and Manual  
Release Zone  
1. Single Interlocked Preaction System with Electric Release  
2. Deluge System with Electric Release  
3. Non-Interlocked Preaction system with Electric Release  
4. Double Interlocked Preaction System with Electric/Pneu-Lectric Release  
ZONES (Initiating Circuits)  
SUP 1  
SUP 2  
#1  
#2  
#3  
#4  
OUTPUTS  
(Indicating Circuits)  
Valve Tamper  
Low Air  
Conventional  
Conventional Waterow  
Manual  
Supervisory Zone Supervisory Zone Detection Zone Detection Zone  
Zone  
X
Release Zone  
#1 General Alarm  
#2 Waterow  
X
X
X
#3 Release Solenoid  
#4 Supervisory Bell  
X X  
X X  
X
X
X
OPERATION DESCRIPTION  
Inputs:  
2 Conventional Detection zones, 1 Waterow zone, 1 Manual Release zone, 2 Supervisory zones  
Outputs:  
Operation:  
1 General Alarm, 1 Waterow, 1 Release Solenoid, 1 Supervisory Bell  
Simultaneous activation of both the Conventional Detection zone #1 and the Conventional Detector  
zone #2 will activate output #3 (Release Solenoid) and output #1 (General Alarm)  
Activation of Conventional Detection zone #1 will activate output #1 (General Alarm)  
Activation of Conventional Detection zone #2 will activate output #1 (General Alarm)  
Activation of Waterow zone #3 will activate output #2 (Waterow)  
Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1  
(General Alarm)  
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate output  
#4 (Supervisory Bell)  
XX = Cross-Zoned  
NOTES:  
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release  
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.  
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.  
3. Leave EOLR (provided) on all unnused circuits.  
4. See the instruction manual for circuit information, panel limits, and battery sizing.  
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.  
6. See instruction manual for proper programming.  
7. See instruction manual for list of compatible smoke detectors.  
8. See specic system type data page for proper pressure switch settings.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
LOW WATER  
PRESSURE  
WATER  
FLOW  
MANUAL  
RELEASE  
STATION  
SUPERVISORY  
VALVE  
TAMPER  
CONVENTIONAL  
SWITCH  
09470  
SWITCH CONVENTIONAL  
09472  
EOLR  
DETECTION  
DETECTION  
EOLR  
SUPERVISORY  
EOLR  
EOLR  
5.1K  
EOLR  
EOLR  
5.1K  
5.1K  
5.1K  
5.1K  
5.1K  
ZONE 1  
ZONE 2  
HOT - BLACK  
NEUTRAL - WHITE  
120 OHM  
EARTH GROUND - GREEN  
N
L
24 VNR DC  
RS-485  
AUX. POWER  
24VR DC  
SUP 1  
SUP 2  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE 4  
VFR -400  
ZONE 1  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
ZONE 2  
ZONE 3  
ZONE 4  
PROGRAM  
MODE  
RUN  
MODE  
SUPERVISORY  
SUPERVISORY  
1
2
AC POWER  
POWER TBL  
SYSTEM TBL  
SUP TBL  
SCROLL-UP  
BUZZER SILENCE  
COMMON ALARM  
ALARM SILENCE  
RUN  
LAMP TEST  
}
GROUND  
FAULT  
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SYSTEM RESET  
SELECT  
FUNCTION  
VIEWING ANGLE  
WTRFLW  
TROUBLE  
COM NO  
ALARM  
COM NO  
SUPV  
OUTPUT 1  
OUTPUT 2  
OUTPUT 3  
OUTPUT 4  
NC  
COM NO COM  
NO  
NC  
BAT+ BAT-  
RELAY CONTACTS  
DRY CONTACTS RATED AT 3A, 30VDC  
5.1K  
EOLR  
5.1K  
EOLR  
EOL  
DIODE  
ASSY  
5.1K  
EOLR  
GENERAL WATERFLOW RELEASE SUPERVISORY  
ALARM  
SOLENOID BELL  
DWG#14178 VKG PRGM12  
1. Run eld wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-of-  
line resistor (EOLR) at last device. The end-of-line resistor is located on the mother board. Remove as needed. Leave factory  
installed EOLR on all unused circuits.  
2. Connect one circuit at a time and apply AC power.  
3. Connect batteries to the panel.  
4. Once last connection is made, move Program switch down.  
5. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.  
6. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET button  
to move to the next digit. After entering the third number the display will change. (All panels are shipped with a 000 password.)  
7. Press the FUNCTION (bottom) button until the display reads “PROGRAM #12”.  
8. Press the SELECT button until the display reads “PROGRAM #12”.  
9. Press the SET button.  
10. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
CUSTOM PROGRAM  
ZONES  
#1  
SUP 1  
SUP 2  
#2  
#3  
#4  
OUTPUTS  
#1  
#2  
#3  
#4  
+
-
+
-
S
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
VFR-400 Custom Program Information  
SET  
Press the SET button to set the description displayed into the panels program  
Press the SELECT button to scroll between water or chemical based modes  
Press the bottom button to skip to the next function  
SELECT  
FUNCTION  
I
N
E
I
T
E
Z
T
O
I
N
O
E
#
1
D
T
C
N
Initiating Zone Description  
This allows the user to describe the initiating zones. Ten different descriptions are available. They are:  
1) FIRECYCLE - Used only with Normally Closed Firecycle® heat detectors. Automatic restoration of the Firecycle® heat  
detector will automatically start the Soak Timer.  
2) DETECTION - These include smoke detectors, pull stations, heat detectors and other devices put on a conventional zone.  
3) WATERFLOW - Alarms from waterow zones are non-silenceable  
4) LINEAR HEAT DETECTION - These use a special wire with a fuseable insulation  
5) MANUAL RELEASE - Used to override cross zoning and cause instant release  
6) LOW AIR ALARM – This is for a low air switch used in a double interlock system. Usually cross zoned with a smoke or heat  
detector. Activation of this zone creates a supervisory condition on the panel but can still operate the release circuit.  
7) SUPERVISORY - For monitoring any supervisory function as assigned  
8) TAMPER - For control valve monitoring  
9) LOW AIR - Used to detect low air pressure  
10) HIGH AIR - Used to detect high air pressure  
The rst ve descriptions (FIRECYCLE, DETECTION, WATERFLOW, LINEAR HEAT DETECTION, and MANUAL  
RELEASE) are Alarm Zones. When activated, they will put the panel into alarm and operate the appropriate output as well as  
operating the alarm relay.  
The 6th description (LOW AIR ALARM) creates a supervisory condition on the panel but can be used to activate the release  
circuit. This activates the Supervisory relay not the Alarm relay.  
The last four descriptions (SUPERVISORY, TAMPER, LOW AIR and HIGH AIR) are Supervisory Zones. When  
activated, they will put the panel in a supervisory condition and activate any output described as “SUPERVISORY BELL”. They  
cannot activate the release circuit.  
The 1st description (FIRECYCLE) is an automatically resettable alarm zone. The status of the zone follows the status of the  
FIRECYCLE heat detector. When the detector restores, the zone restores and initiates the soak timer.  
Note: When FIRECYCLE is selected for zone 1, only outputs #3 and #4 can be mapped as releasing circuits.  
If zone 1 is programmed as the FIRECYCLE, the following will appear in the display:  
S
O
O
A
N
K
T
T
I
M
O
E
R
S
C
I
N
U
U
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Soak Timer Description  
This allows the user to select the amount of time the release circuit on output #3 will stay activated after the Firecycle zone  
restores to normal. The available times are 30, 60, 90 seconds, 2-20 minutes in 1 minute incriments, or continous.  
After describing all initiating zones or skipping to the next function, the following will appear in the display window:  
S
S
U
U
P
P
E
E
R
R
V
V
S
I
R
S
Y
R
1
Z
O
N
E
Y
SET  
Press the SET button to set the description displayed.  
SELECT  
Press the SELECT button to scroll through the ve descriptions.  
(Supervisory, Valve Tamper, Low Air, High Air)  
FUNCTION  
Press the bottom button to skip to the next function.  
After Selecting SUP 1, the following will appear in the display window.  
S
S
U
U
P
P
E
E
R
R
V
V
S
I
R
S
Y
R
2
Z
O
N
E
Y
SET  
Press the SET button to set the description displayed.  
SELECT  
Press the SELECT button to scroll through the four supervisory descriptions.  
(Supervisory, Valve Tamper, Low Air, High Air)  
FUNCTION  
Press the bottom button to skip to the next function.  
After describing what the supervisory zone is to be or skipping to the next function, the following will appear  
in the display window:  
O
I
U
N
T
P
I
U
C
T
#
I
1
D
A
T
N
G
Output Description  
This allows the user to describe the functions of the output circuits. Four descriptions are available:  
1) ALARM INDICATING - Notication appliances include bells, horns, strobes and other appliances used to indicate an alarm.  
2) RELEASING - Releasing appliances include solenoids and other electrically compatible devices.  
3) SUPERVISORY BELL - Appliances on this circuit are used to indicate the presence of a supervisory condition. Any zone  
programmed as LOW AIR ALARM, SUPERVISORY, TAMPER, HI AIR or LOW AIR is automatically mapped to this output.  
4) TROUBLE BELL - Appliances on this circuit are used to indicate the presence of a trouble condition.  
The user should describe each output circuit in the same manner as the initiating circuit was described by pressing the SELECT  
button to select and the SET button to set the desired function.  
SET  
Press the SET button to set the description displayed.  
Press the SELECT button to scroll through the descriptions.  
Press the bottom button to skip to the next function.  
SELECT  
FUNCTION  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
After selecting all four outputs or pressing FUNCTION, the following will be displayed if any outputs have been  
described as RELEASING:  
O
N
U
O
T
R
P
U
A
T
L
#
<
A
>
M
Where “<A>” is the number of the releasing circuit output.  
Normal/Cross-Zoning  
Each releasing circuit can be set up for the normal or cross zoned operation. In NORMAL operation, any alarm initiating zone  
including LOW AIR ALARM mapped to a releasing output must be in alarm before the output is activated. In cross zoned  
operation ALL initiating zones mapped to the releasing circuit must be in alarm before the output is activated. An initiating zone  
previously described as “MANUAL RELEASE” will override the cross zoning feature.  
SET  
Press the SET button to set the operation displayed.  
SELECT  
FUNCTION  
Press the SELECT button to toggle between NORMAL and CROSS ZONED.  
Press the bottom button to skip to the next function.  
V
Z
O
U
N
T
E
P
1
O
U
T
S
:
1
2
3
4
SET  
Press the SET button to set the time displayed.  
SELECT  
Press the SELECT button to scroll through the available time.  
Press the bottom button to skip to the next function  
FUNCTION  
This display is where the outputs are mapped to the initiating zones. Any output that was previously described as “RELEASING”  
or “ALARM INDICATING” can be mapped to any initiating zones that were described as alarm zones, including zones  
programmed as “LOW AIR ALARM”.  
Any initiating zone that was described as supervisory will automatically be mapped to outputs described as “SUPERVISORY  
BELL”, including zones programmed as “LOW AIR ALARM”. The “V” is pointing to the rst available output for the zone  
indicated on the display. If the output number is displayed, it is turned on for that zone. If the number is not displayed, it is turned  
off. If an output is not available for that zone, i.e. “SUPERVISORY BELL”, the “V” will skip to the next available output.  
SET  
Press the SET button to set the output to the zone displayed and move to the next available output.  
Press the SELECT button to turn the output either on or off (the output number will be displayed when turned on).  
Press the bottom button to skip to the next function.  
SELECT  
FUNCTION  
After all available outputs for the zone displayed are mapped, the display will automatically change to the next zone.  
After mapping the last zone or skipping to the next function, the following will appear in the display window:  
B
A
N
N
E
R
M
E
S
S
A
G
E
?
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Custom Message  
To change the banner message, press the SELECT button. If you don’t want to change the banner message  
press the bottom button.  
SET  
SELECT  
Press the SELECT button to change banner message.  
Press the bottom button to skip to the next function.  
FUNCTION  
If the SELECT button was pressed, the following will appear in the display window:  
^
The “^” is pointing to the rst character on the top line. Press the SET button to scroll one direction through the  
character set, or press the SELECT button to scroll the other direction. The entire alphabet, numbers and  
punctuation are included.  
SET  
Press the SET button to scroll through the character set in one direction.  
Press the SELECT button to scroll in the opposite direction.  
SELECT  
FUNCTION  
Press the bottom button to enter the character displayed and to move to the next position.  
After programming the top line (maximum 10 characters), continue this process for the bottom line and the  
initiating zones. To keep the initiating zones as “ZONE 1”, etc., press the bottom button when they are displayed.  
When nished with the last zone, the following will appear in the display window:  
N
E
W
P
A
S
S
W O  
R
D
=
0
^
0
0
This allows the user to change the password. All panels are shipped from the factory with a password of 000.  
SET  
Press the SET button to set the displayed number and move to the next space.  
Press the SELECT button to scroll through the numbers.  
SELECT  
FUNCTION  
Press the bottom button to skip this function.  
When nished with this section, the following will appear in the display window:  
P
S
U
S
I
H
T
P
R
O
B
G
A
R
C
A M  
K
M
U
I
N
G
W
C
H
P
Quit by returning the programming switch to the up position. The system is now ready for operation.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Custom Program (#0 only)  
• Describe Initiating Zones 1 - 4  
Alarm Zones  
Detection  
Waterow  
Supervisory Zones  
Supervisory  
Tamper  
Linear Heat Detection  
Manual Release  
Firecycle (Zone 1 only)  
Low Air  
High Air  
Low Air Alarm  
• Describe Initiating dedicated Supervisory Zone (Sup 1 & Sup 2)  
Supervisory  
Tamper  
Low Air  
High Air  
• Select Soak Timer  
• Describe Output Zones  
Alarm Indicating  
Releasing  
Supervisory Bell  
Trouble Bell  
1) Releasing circuits: normal/cross-zoned  
2) Discharge time: 7, 8, 9, 10, 20 minutes or continuous  
• Map Alarm Inputs to Outputs  
• Put in Banner Message  
• Put in Banner Message Bottom Line  
• Put Zone Description for Each Initiating Zone  
• Change Password  
• Finished  
Installation Instructions  
Read the entire manual before attempting to install this panel.  
This panel wiring should be installed and maintained in accordance with section 760 (Fire Protection  
Signaling Systems) and all other applicable sections of the National Electrical Code, all other applicable NFPA Code and  
Standards, local code and the authority having jurisdiction. Review the circuit parameters listed below before installing the panel.  
All wiring terminals support 14 to 18 AWG wire sizes. 18 AWG stranded or solid copper wire, (or wire size rated for the current  
carrying capacity of the circuit application), with 300V, 85°C insulation is recommended.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Wire Checkout:  
With all initiating devices and notication appliances installed and with the EOLR’s in place, check the wires with an  
ohmmeter. Meter readings outside of the following will prevent normal operation.  
From any wire to ground – less than 100K ohms.  
Across the 2 wires on each Initiating zone – between 1.8K ohms and 5.4K ohms.  
Across the 2 wires on each notication circuit – between 1.8K ohms and 23.9K ohms.  
Mounting Instructions:  
1) The unit should be mounted in a convenient location, approximately 5 ft. from the oor where it will be  
accessible for testing and servicing.  
Removal of this false front exposes electrical  
components at potentially hazardous voltages and  
should be performed by qualied personnel only.  
2) The main circuit board module should be removed before attempting to mount the cabinet. Disconnect the AC power from  
TB201. To remove the module, remove the two screws holding the chassis to the cabinet. Lift the module upwards, approximately  
1/2", in order to clear the cross-beam of the cabinet on which the module rests. Remove the module and set aside.  
3) Install all required conduits, external wiring and devices and make all connections that are external to the panel. Replace  
the module. With the AC power still turned off at the circuit breaker panel, connect the AC hot, neutral and ground wires to the  
terminal block TB201 as shown on the connection drawing. (See connection drawings on page 54)  
4) Connect all the other wiring to the terminals as shown in the connection drawings. Turn the AC power on and connect the  
standby batteries with the cable provided, polarity must be observed.  
5) Replace false front panel and secure with mounting screws.  
6) The operation of the complete system should be veried as outlined in the test procedure section.  
VFR-400 False Front Removal/Assembly Drawing  
DWG# 3550-15  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Inactive Circuits  
All inactive initiating device circuits must have the end-of-line resistor on the panel terminal.  
Operating Instructions Form  
Fill in the name, address, and telephone number of the servicing agency on the appropriate instruction sheet. Frame and place this  
sheet adjacent to control panel at eye level.  
Battery Size Calculations  
To use Calculation Table:  
1)  
List in column #1 all devices used in the system, include all modules, bells, horns, door holders, and smoke detectors  
(see table #1 or manufacturers specications).  
2)  
3)  
4)  
5)  
List in column #2 the quantity of each device.  
List in column #3 the standby current of each device (exclude all signal indicating devices).  
List in column #5 the alarm current of each device.  
For each line, multiply the gure in column #2 by the gure in column #3 and enter the product in column #4. Then  
multiply the gure in column #2 by the gure in column #5 and enter the product in column #6.  
Add the gures in columns #3 and #6, enter the sums in the appropriate Total mA box.  
Convert these gures from milliamperes to amperes by multiplying by 0.001, enter the product in the appropriate Total A box.  
Multiply the standby total amperes by required time in hours from table 2.  
Divide the alarm total amperes by 12 (5 mins.).  
6)  
7)  
8)  
9)  
10)  
Add the standby AH and the alarm AH and divide this sum by 0.85 (efciency factor). Select a battery that has an AH  
rating above this gure but not less than 6.5AH.  
Battery Size Requirements And Maintenance  
Charging Voltage: 27VDC Nominal  
Maximum Charging Current: .5A  
These panels require a 24 volt sealed lead acid battery for proper operation. 24 hours of standby power is required for Local  
Systems and Central Station (NFPA-72).  
The chart below will assist you in selecting the proper size battery: (Does not include LED Annunciator)  
No. of Smoke  
Detectors  
No. of Bells  
(100mA each)  
Auxiliary Power  
Requirements  
Standby Hours  
Required  
Battery Size/Part No.  
(2 Req.)  
0-100  
0-100  
0-100  
0-10  
0-10  
0-10  
0-25mA  
0mA  
24  
90  
90  
8AH/BT 80  
12AH/BT 120  
18AH/BT 180  
0-30mA  
Maximum allowed battery size for UL applications is 12AH. FM and others may require more than 24 hours of standby time and  
may use larger batteries. Batteries rated above 18AH require a separate battery cabinet (Potter Model BC-2). Mark the purchase  
date on the batteries. Test the batteries at least semi annually according to the battery test methods in NFPA72 or the battery  
manufacturers instructions. Replace the batteries if they either fail the test or after four years of use. The VFR-400 is capable of  
charging 24 AH batteries, (FM Applications only).  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
TABLE 1  
CURRENT REQUIREMENTS  
Module/Device  
Standby mA*  
Alarm mA**  
VFR-400  
121  
12  
274  
12  
RA-4410-RC  
*Add 23 mA plus current requirement of all devices connected for each output programmed as Trouble Bell  
**Includes one zone short circuit current.  
TABLE 2  
Service Use  
SECONDARY POWER SUPPLY REQUIREMENTS  
Standby Time  
Alarm Time  
NFPA 72  
• Central Station (PPU)  
• Local  
FMRC 1011 and 1012, Deluge and Pre-action Systems  
Where requested by FM or others.  
24 hrs.  
24 hrs.  
90 hrs.  
5 mins.  
5 mins.  
10 mins.  
90 Hours is not a UL requirement.  
CALCULATION TABLE  
1
2
3
4
5
6
Module/Device Quantity Standby mA Per Unit Total Standby Current  
Alarm mA Per Unit Total Alarm Current  
Total mA  
Total mA  
x 0.001  
x 0.001  
Convert to A  
Convert to A  
Total A  
Total A  
x ___  
÷ ___  
Multiply by hours from table 2  
Total Standby AH  
5 min/12 or 10 min/6  
Total Alarm AH  
+ Total Standby AH  
Total AH  
÷ 0.85  
Efciency Factor  
Required AH  
Use a battery with a higher AH rating than Required AH  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Typical Firecycle Wiring  
FROM  
CONTROL  
PANEL  
EOL 5.1k  
Typical 2 Wire Detector Connection Drawing  
Base wiring for Potter models IS-24 Ionization Detectors and PS-24 Photoelectric Detectors.  
Typical Style B (Class B) Wiring Using SB-46 Base  
(These bases can be used in style B or Style D wiring)  
Typical Style D (Class A) Wiring  
(These bases can be used in style B or style D wiring)  
Note: The 6" diameter bases will mount on a 3" or 4" octagon box or a 4" square box.  
Typical 4-Wire Wiring  
ZONE  
TERMINALS  
PAM-4  
End-of-Line  
Wiring  
RESETTABLE  
AUX POWER  
DWG# 3521-5VKG  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
2-Wire Smoke Detector And Synchronization Module Compatibility Data  
System Sensor (Brk) (Max. No. Of Detectors Per Zone Is 20)  
Det. Model  
1400*  
2400*  
2400TH*  
2W-B  
Identier  
Base Model  
N/A  
N/A  
N/A  
N/A  
Identier  
N/A  
N/A  
N/A  
N/A  
A
A
A
A
A
A
2WT-B  
2WTR-B  
N/A  
N/A  
N/A  
N/A  
Detection Systems (Max. No. Of Detectors Per Zone Is 25)  
Det. Model  
Identier  
Base Model  
Identier  
DS250  
DS250TH  
DS250HD  
A
A
A
MB2W/MB2WL  
MB2W/MB2WL  
MB2W/MB2WL  
A
A
A
ESL (Max. No. Of Detectors Per Zone Is 25)  
Det. Model  
611U  
Identier  
Base Model  
601U  
601U  
601U  
601U  
601U  
601U  
609U10  
609U10  
N/A  
Identier  
S00  
S00  
S00  
S00  
S00  
S00  
S00  
S00  
S10  
S10  
S10  
S10  
S10  
S10  
S10  
S10  
S10  
S10  
611UD  
611UT  
612U  
612UD  
613U5  
611UD  
612UD  
425C  
N/A  
N/A  
425CT  
N/A  
Hochiki (Max. No. Of Detectors Per Zone Is 25)  
Det. Model  
SLR-24*  
Identier  
Base Model  
HSC-221R  
HSB-221  
HSB-221N  
NS6-221  
Identier  
HB-71  
HB-54  
HB-54  
HD-3  
HD-3  
HD-3  
NS4-221  
SLR-24H*  
SIJ-24*  
HSC-221R  
HSB-221  
HSB-221N  
NS6-221  
HB-71  
HB-54  
HB-54  
NS4-221  
HSC-221R  
HSB-221  
HSB-221N  
NS6-221  
HB-71  
HB-54  
HB-54  
NS4-221  
Fenwal (Max. No. Of Detectors Per Zone Is 25)  
Det. Model  
CPD-7051*  
PSD-7155*  
PSD-7156*  
Identier  
Base Model  
2-WIRE  
2WRLT  
2WRB  
Identier  
FE51A  
FE52A  
FE55A  
I51FE1  
P55FE1  
P56FE1  
All of the above Fenwal detectors and bases can be used in any combination  
Retrot Base Adaptor 70-501000-003, Identier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003 and -005)  
Duct Housing with Detector Base DH-51, Identier DH22FE5 (for CPD-7051 and PSD-7155 detectors only)  
Potter (Max. No. Of Detectors Per Zone Is 25)  
Det. Model  
PS-24*  
Identier  
HD-3(HOCHIKI)  
Base Model  
SB-46  
Identier  
HB-71(HOCHIKI)  
HB-54(HOCHIKI)  
HB-71(HOCHIKI)  
HB-54(HOCHIKI)  
HB-71(HOCHIKI)  
HB-54(HOCHIKI)  
PS-24H  
IS-24*  
HD-3(HOCHIKI)  
HD-3(HOCHIKI)  
SB-46  
SB-46  
Only one detector can be supported in alarm per zone.  
*UL and ULC Listed  
If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.  
Sync Modules: Amseco - SMD10-3A Gentex - AVSM System Sensor - MDL Wheelock - DSM 12/24  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Releasing Device Compatibility  
Automatic Water Control Valves Compatibility Data  
Viking:  
13215 Normally open  
11591 Normally closed  
11601 Normally closed  
11602 Normally closed, explosion-proof  
11595 Normally open  
11596 Normally open, explosion-proof  
11592 Normally closed, explosion-proof  
13843 Normally closed  
13844 Normally closed, explosion-proof  
Wire Routing for VFR-400  
1
2
3
Power Inputs  
Battery Leads  
RED OUTPUT LED STEADY: ABORT  
ZONE  
ZONE  
ZONE  
1
2
3
4
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
1
2
3
4
PROGRAM  
MODE  
RUN  
Using The Cable Clamps Provided, Route All Other Wiring Away  
From Power Input Wiring.  
MODE  
ZONE  
AC POWER  
SUP 1/ABORT  
SUPERVISORY  
SCROLL-UP  
BUZZER SILENCE  
POWER TBL  
SYSTEM TBL  
SUP TBL  
2
COMMON ALARM  
RUN  
ALARM SILENCE  
GROUND  
FAULT  
STEADY: DISCHARGED  
FLASHING: PRE-  
DISCHARGE  
PROGRAM  
SET  
SCROLL-DOWN  
BUZZER SILENCE  
SIGNAL SILENCE  
SYSTEM RESET  
SELECT  
FUNCTION  
VIEWING ANGLE  
All eld installed wiring connected to this panel must maintain a spacing  
of 1/4" between all electric light, power, class 1 or non-power limited re  
protective signaling conductors.  
DWG# 3550-16  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
NEC Section 760-54. Installation of Conductors and Equipment.  
(a) Separation from Electric Light, Power, Class 1, and NPLFA Circuit Conductors.  
(1) In Cables, Compartments, Enclosures, Outlet Boxes, or Raceways. Power-limited circuit conductors shall not be placed  
in any cable, compartment, enclosure, outlet box, raceway, or similar tting containing conductors of electric light,  
power, Class 1, or nonpower-limited re alarm circuit conductors.  
Exception No. 1: Where the conductors of electric light, power, Class 1, or nonpower-limited re alarm circuit conductors  
are separated by a barrier from the power-limited re alarm circuits. In enclosures, power-limited re alarm circuits shall be  
permitted to be installed in a raceway within the enclosure to separate them from Class 1, electric light, power, and nonpower-  
limited re alarm circuits.  
Exception No. 2: Conductors in compartments, enclosures, device boxes, outlet boxes, or similar ttings, where electric light,  
power, Class 1, or nonpower-limited re alarm circuit conductors are introduced solely to connect to the equipment connected to  
power-limited circuits to which the other conductors are connected, and  
a. The electric light, power, Class 1, and nonpower-limited re alarm circuit conductors are routed to maintain a  
minimum of 0.25 in. (6,35mm) separation from the conductors and cables of power-limited re alarm circuits, or  
b. The circuit conductors operate at 150 volts or less to ground and also comply with one of the following:  
1. The re alarm power-limited circuits are installed using Types FPL, FPLR, FPLP or permitted substitute cables, provided  
these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6,35mm) or by a  
nonconductive sleeve or nonconductive barrier from all other conductors, or  
2. The re alarm power-limited circuit conductors are installed as nonpower-limited re alarm circuits in accordance with Section 760-25.  
Exception No. 3: Conductors entering compartments, enclosures, device boxes, outlet boxes, or similar ttings, where electric  
light, power, Class 1, or nonpower-limited re alarm circuit conductors are introduced solely to connect to the equipment  
connected to power-limited re alarm circuits or to other circuits controlled by the re alarm system to which the other conductors  
in the enclosure are connected. If the conductors must enter an enclosure that is provided with a single opening, they shall be  
permitted to enter through a single tting (such as a tee) provided the conductors are separated from the conductors of the other  
circuits by a continuous and rmly xed nonconductor, such as exible tubing.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFR-400 • 5403548 • REV D • 10/07  
Connection Procedure for Battery Charging Current and Voltage  
1) To measure the battery charging voltage:  
Place a voltmeter across the battery terminals as shown in FIG. 4  
2) To measure the battery charging current:  
Place a current meter in series with the battery terminals as shown in FIG. 5.  
PANEL  
PANEL  
VOLT  
METER  
CURRENT  
METER  
DWG# 3527-9  
Connection Drawing for Central Station and Remote Station Operation  
VFR-400/PFC-7500 Interconnection Drawing  
** Or other UL864 9th Edition listed stand alone DACT connected as shown and installed in the same room within 20 feet of the  
VFR-400 and with interconnecting wiring in conduit.  
See PFC-7500 Manual 8910225 for programming information.  
See PFC-7500 Manual 8910227 for installation instructions.  
Note:PFC-7500 requires RA-7690 LCD Annunciator for programming.  
The VFR-400 and PFC-7500 shall be installed in the same room within 20 feet of each other and the interconnecting wires shall be in conduit.  
PFC-7500  
MAIN  
BACKUP  
J4  
J5  
TELEPHONE CONNECTIONS  
U21  
J11  
1
2
3
4
AC  
S
AC  
B+  
BO  
RED YEL GRN BLK Z1A+ Z1A- Z1B+ Z1B- Z2+  
Z2-  
Z3+ Z3-  
Z4+  
S
Z4-  
Z5+  
Z5-  
N/C COM N/O N/C COM N/O  
120 VAC  
60 HZ  
350mA  
J12  
WLT  
TRANSFORMER  
S
S
S
S
S
S
S
S
S
S
S
S
AC MODE  
ZONE 1  
3.3K EOLR  
ZONE 2  
ZONE 3  
ZONE 4  
3.3K EOLR'S FROM PFC-7500  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Thule Automobile Accessories Kit 2181 User Manual
Toastmaster Oven TOV425RL User Manual
Toshiba Car Satellite TV System HD S25 User Manual
Toshiba Copier 310 User Manual
Toshiba DVD Recorder SD KV540SU User Manual
Tricity Bendix Oven BD900 User Manual
Uniden Battery Charger BT 1018 User Manual
Verona Oven VEBIG24 User Manual
Viking Oven F20812A EN User Manual
Vita Spa Hot Tub U 1 3 0 User Manual