Trane Ventilation Hood YCZ035F1 User Manual

YCZ-IOM-1F  
INSTALLATION  
OPERATION  
18-EB21D4-7  
Library  
Service Literature  
Product Section  
Product  
Unitary  
Packaged Gas/Electric  
Model  
YCZ  
MAINTENANCE  
Literature Type  
Sequence  
Date  
Installation, Operation, Maintenance  
1F  
December 2002  
SV-UN-RT-YCZ-IOM-1F 12/02  
New  
ALL phases of this installation must comply with  
NATIONAL, STATE AND LOCAL CODES  
File No.  
Supercedes  
Model:  
Single Package Two Stage  
Gas/Electric 16 SEER  
Convertible 3, 4, 5 Ton  
YCZ036F1/3M0B, 4MOA  
YCZ050F1/3HOA, 4H0A  
YCZ060F1/3M0B, 4M0A  
BAYLIFT002A  
LIFTING LUG KIT  
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.  
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING  
WARNING:  
All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. In the absence of local codes, the  
installation must conform with National Electric Code -- ANSI/NFPA 70 or "LATEST REVISION."  
Since Trane has a policy of continuous product and product data improvement,  
it reserves the right to change design and specification without notice.  
12/02  
© 2002 American Standard Inc. All rights reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS  
(YCZ036,050,060F Models)  
1
FIELD SUPPLIED  
SUPPORTS  
AT EACH END  
OF CURB  
ROOFING  
ROOF INSULATION  
ROOF DECK  
FIELD SUPPLIED  
CANT STRIP  
FIELD SUPPLIED  
RIGID INSULATION  
ROOF MOUNTING  
CURB  
SUPPLY AIR  
DUCT  
RETURN AIR  
DUCT  
TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A,038A  
(YCZ036,050,060F Models)  
2
SEE NOTE 1  
SEE NOTE 2  
FIELD SUPPLIED  
SUPPORTS  
AT EACH END  
OF CURB  
ROOFING  
ROOF INSULATION  
ROOF DECK  
FIELD SUPPLIED  
CANT STRIP  
FIELD SUPPLIED  
RIGID INSULATION  
ROOF MOUNTING  
CURB  
NOTES:  
SUPPLY AIR  
DUCT  
RETURN AIR  
DUCT  
1. The YCZ036F models extend out past this end of the  
curb ONLY.  
2. TheYCZ050F,YCZ060Fmodelsextendpastboththe  
end and the side of the curb as illustrated.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONAL DATA  
YCZ036,050,060F OUTLINE – BACK  
3
NET  
UNIT  
WEIGHT  
(LBS)  
CORNER WEIGHT (LBS)  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
MODEL  
W1 W2  
W3  
W4  
YCZ036F 161 106 104 157 528  
YCZ050F 172 121 137 196 626  
YCZ060F 195 129 132 199 656  
64  
36 29-3/16 18-9/16 11-1/16 6-9/16 11-1/8  
17  
18-1/2 25-1/2 17-1/2 10  
24 26-1/2  
3
8-3/4  
65-1/8 45 33-3/8 21-1/16 15-1/16 4-15/16 9-1/8 21-15/16  
20  
14 3-1/2 8-5/16  
22-3/4 25-1/2  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONAL DATA  
YCZ036,050,060F OUTLINE – FRONT  
4
CLEARANCE TO  
COMBUSTIBLE MATERIAL  
RECOMMENDED SERVICE CLEARANCE  
BACK  
LEFT SIDE  
RIGHT SIDE  
FRONT  
* 6.0"  
30.0"  
24.0"  
42.0"  
BOTTOM  
BACK  
0.0"  
1.0"  
LEFT SIDE  
RIGHT SIDE  
FRONT SIDE  
TOP  
6.0"  
6.0"  
* 18" WITH FRESH AIR ACCESSORY  
* 30" WITH ECONOMIZER  
12.0"  
36.0"  
A
64  
B
C
D
MODEL  
YCZ036F-M  
36  
45  
29-3/16 27-1/2  
33-3/8 27-15/16  
YCZ050F-M  
YCZ060F-M  
65-1/8  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONVERTING HORIZONTAL TO DOWNFLOW  
5
NOTE  
SUPPLY OPENING  
1. REMOVE SCREW NEAREST TO THE  
OPENINGANDPULLTHEPANELFIRMLY  
TOWARDTHEOUTSIDEOFTHEUNITTO  
DISENGAGE THE BACK ATTACHMENT.  
HEATER EXCHANGER  
TUBES  
RETURN OPENING  
2. REMOVE RIGHT HAND SCREW AND  
MOVE PANEL TO THE RIGHT OR RE-  
MOVE BOTH SCREWS.  
SHEET METAL  
SCREWS  
HORIZONTAL RETURN  
AIR COVER  
HORIZONTAL SUPPLY  
AIR COVER  
REQUIRED CLEARANCE FOR UNIT INSTALLATION  
AND ROOF PENETRATION HOLE SIZE REQUIRED  
6
D
A
SERVICE  
CLEARANCE  
LINES  
SERVICE  
CLEARANCE  
LINES  
SUPPLY AIR  
B
RETURN AIR  
C
SIDE RAIL  
WOOD NAILER  
SERVICE CLEARANCE & PENETRATION DIMENSIONS  
HOLE IN ROOF  
MODEL NO.  
YCZ036F  
A
B
C
D
E
F
30" 30" *12" 30" 44" 25"  
42" 30" *12" 36" 50" 25"  
YCZ050F  
YCZ060F  
E
F
* 18" WITH FRESH AIR ACCESSORY  
* 30" WITH ECONOMIZER  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCATIONS AND RECOMMENDATIONS  
3. See the unit’s nameplate for the absolute minimum clearance  
between the unit and any combustible surface(s).  
HORIZONTAL AIRFLOW APPLICATION  
1. These units are design certified for outdoor installations. These  
units may be installed directly on wood flooring or on Class A,  
Class B, or Class C roof covering material. The discharge air  
from the condenser fans must be unrestricted for a minimum of  
3 feet above the unit.  
IMPORTANT:  
1. Remove the Flue and Air Inlet Hood with gasket from the return  
air section of the unit.  
The screws that attach the flue and air inlet hood will be installed  
in their proper location at the factory. Therefore, they must be  
removed and then used to attach the flue and the air inlet hood.  
NOTE: The unit is shipped for horizontal installation.  
The Air Inlet Hood in the combustion blower access panel must  
have adequate clearance around the air opening into the  
combustion area. See Outline Drawing, Figure 3.  
2. Remove the packaging material from the components and  
secure the Flue and Air Inlet Hood with the gasket to the unit  
with sheet metal screws as illustrated in Figure 5. See “Firing  
Rate Selection” section for additional information.  
Examine all flue product-carrying areas of the furnace, its vent  
system, and the main burner for safe operation. A periodic  
inspection of the furnace should be made by a qualified service  
agency at the start of each heating season.  
NOTE: Outdoor air or other requirements during heating  
operation that result in supply air temperatures below 80  
degrees F or return air temperatures below 50 degrees F may  
cause flue gas condensate to form and is to be avoided.  
ReplacementpartslistforthisGas/ElectricAirConditioner,maybe  
obtained by contacting your local manufacturer representative.  
DOWNFLOW APPLICATION -- CURB MOUNTING  
NOTE: If any internal accessories are to be added to the unit,  
install them at the shop if at all practical.  
1. The  
Roof  
Mounting  
Curb,  
(field  
assembled  
2. Location of the unit must allow service clearance around it.  
Clearance of the unit must be given careful consideration. See  
Figures 2, 3, and 4.  
BAYCURB030,038,033,034A), or a field fabricated curb must  
be in place before the unit is hoisted to the roof top.  
2. The Roof Mounting Curb (frame) must be installed on a flat,  
level section of the roof (maximum of 1/4" per foot pitch)  
and provide a level mounting surface for the unit. In  
addition, besuretoprovidesufficientheightabovetheroof  
to prevent water from entering the unit.  
IMPORTANT: Air outlet duct must have 1" clearance to  
combustible material downstream from the unit.  
3. Check the handling facilities to ensure the safety of personnel  
and the unit(s).  
NOTE: This unit was shipped for horizontal installation. Con-  
4. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID  
vert to downflow per instructions:  
PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT  
Remove covers from the downflow supply and return air open-  
ings and place them over the horizontal supply return air  
openings(paintedsideout)andsecurewithsheetmetalscrews.  
See Figure 6.  
5. The unit must be mounted level for proper drainage of water  
through the holes in the base pan.  
6. The unit must not be exposed to direct roof water runoff.  
3. Be sure the mounting curb spans structural members (trusses)  
of the roof, thereby providing sufficient support for the weight of  
the unit, the curb, the duct(s), and any factory or field installed  
accessories. See Figures 1, 7, 8, 9, 10, and 11.  
7. Flexible duct connectors must be of a flame retardant material.  
All duct work outside of the structure must be insulated and  
weatherproofed in accordance with local codes.  
8. Holes through exterior walls must be sealed in accordance with  
local codes.  
4. Be sure the hole in the structure for the ducts is large enough  
to accommodate the fabricated ducts and the insulation sur-  
rounding them. See Figure 4.  
9. All fabricated outdoor ducts should be as short as possible.  
Note: If any internal accessories are to be added to the unit,  
install them at the shop if at all practical.  
CLEARANCES  
5. These units are design certified for outdoor installation. These  
units may be installed directly on wood flooring or on Class A,  
Class B, or Class C roof covering material. The discharge air  
from the condenser fans must be unrestricted for a minimum of  
3 feet above the unit.  
1. The recommended clearances for single-unit installations are  
illustrated in Figure 4. These minimum requirements are not  
only an important consideration when determining unit place-  
ment, but they are also essential to ensure adequate service-  
ability, maximum capacity, and peak operating efficiency.  
The air inlet hood in the combustion blower access panel must  
have adequate clearance around air openings into the combus-  
tion area. See Outline Drawing, Figure 3.  
continued on next page  
2. Any reduction of the unit clearances indicated in these illustra-  
tions may result in condenser coil starvation or the recirculation  
of warm condenser air. Actual clearances which appear to be  
inadequate should be reviewed with a local engineer.  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCATIONS AND RECOMMENDATIONS  
continued from page 7  
15. Access and service clearances for the unit must be given  
careful consideration when locating the duct entrance open-  
ings. Figure 4 provides unit dimensions.  
Examine all flue product-carrying areas of the furnace, its vent  
system, and the main burner for safe operation. A periodic  
inspection of the furnace should be made at the start of each  
heating season.  
16. All fabricated outdoor ducts should be as short as possible.  
Replacement parts list for this Gas/Electric Air Conditioner may  
be obtained by contacting your local manufacturer representa-  
tive.  
CLEARANCES  
1. The recommended clearances for single-unit installations are  
illustrated in Figure 4. These minimum requirements are not  
only an important consideration when determining unit place-  
ment, but they are also essential to ensure adequate service-  
ability, maximum capacity, and peak operating efficiency.  
6. Location of the unit must allow for service clearance around it.  
Clearance of the unit must be given careful consideration. See  
Figure 4.  
7. IMPORTANT: The air outlet duct must have one (1) inch  
clearance to combustible material downstream from the  
unit.  
2. Any reduction of the unit clearances indicated in these illustra-  
tions may result in condenser coil starvation or the recirculation  
of warm condenser air. Actual clearances which appear to be  
inadequate should be reviewed with a local sales engineer.  
8. Exhaust vents or other sources of contaminated air should not  
be near the unit’s air inlet, if outside air is to be introduced as  
makeup air or a ventilation feature is to be used.  
IMPORTANT:  
1. Remove the Flue and Air Inlet Hood with the gasket from the  
return air section of the unit.  
9. Check the handling facilities to ensure the safety of personnel  
and the unit(s).  
The screws that attach the flue and air inlet hood will be installed  
in their proper location at the factory. Therefore, they must be  
removed and then used to attach the flue and air inlet hood.  
10. Caution must be taken at all times to avoid personal  
injuries and/or damage to the equipment.  
11. The unit must be mounted level for proper drainage of water  
through the holes in the base pan.  
2. Remove the packaging material from the components and  
secure the Flue and Air Inlet Hood with the gasket to the unit  
with sheet metal screws as illustrated in Figure 16 on page 14.  
12. The unit must not be exposed to direct roof water runoff.  
NOTE: Outdoor air or other requirements during heating  
operation that result in supply air temperatures below 80  
degrees F or return air temperatures below 50 degrees F may  
cause flue gas condensate to form and is to be avoided.  
13. Flexible duct connectors must be of a flame retardant material.  
All duct work outside of the structure must be insulated and  
weatherproofed in accordance with local codes.  
14. Roof flashing must be installed to seal the roof curb cavity and  
must conform to local building codes.  
INSTALLATION  
UNIT SUPPORT  
PLACING AND RIGGING  
If the unit is to be roof mounted, check the appropriate building  
codes for weight distribution requirements. Refer to the applicable  
roof curb mounting instruction. Check the unit’s nameplate for  
supply voltage required. Determine if adequate electrical power is  
available. The furnace may be installed on Class A, B, or C roofing  
material.  
1. Before preparing the unit for lifting, check the outline drawing for  
center of gravity for lifting safety. Because of placement of  
internal components, the unit’s weight may be unevenly distrib-  
uted. Approximate unit weights are given in Figure 2, page 3.  
NOTE: Accessory BAYLIFT002AA, a kit of four (4) lifting lugs, is  
required for rigging the unit for hoisting. See Figure 7, insert B.  
LOCATION AND CLEARANCES  
2. Insert the four lifting lugs in the openings provided in the drip lip  
on the perimeter of the unit. See Figure 7, insert B. A tap or jerk  
to the lug will overcome the interference that arises due to the  
nipple on the lug.  
Installation of the unit should conform to local building codes or, in  
the absence of local codes, to the National Fuel Gas Code,  
ANSIZ223.1, Latest Revision, and the National Electrical Code.  
Canadian installations must conform to CSA and local codes.  
3. Before hoisting the unit, be sure that the proper method of  
rigging is used, with straps or slings and spreader bars for  
protection during lifting. Always test-lift the unit to determine the  
exact unit balance and stability before hoisting it to the installa-  
tion location.  
Select a location that will permit adequate combustion and ventila-  
tion air in accordance with Section 5.3, Air For Combustion and  
Ventilation, of the National Fuel Gas Code, ANSIZ223.1, Latest  
Revision, or applicable provisions of the local building code.  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
IMPORTANT: Do not lift the unit without test lifting for  
PLACING THE UNIT ON A MOUNTING CURB  
balance and rigging. Do not lift the unit in windy conditions  
or above personnel. Do not lift the unit by attaching a  
clivus, hooks, pins, or bolts to the unit casing, casing  
hardware, corner lugs, angles, tabs, or flanges. Failure to  
observe these warnings may result in equipment damage.  
1. The unit is designed with a perimeter drip lip that is lower that  
the unit base bar, see Figure 7, inset A.  
2. Position the unit drip lip down over and in contact with the  
outside corner of the curb, as illustrated in Figure 8, insert A.  
Continue to lower the unit on top of the curb, with the unit drip  
lip astraddle and in contact with both the end and side rail of the  
curb. The unit should now rest on top of the curb.  
4. When the curb and air ducts have been properly installed, the  
unit is ready to be hoisted to the roof and set in position.  
IMPORTANT: “Spreader Bars” must be used when hoist-  
ing the unit.  
3. Take the two (2) hold-down brackets shipped with the curb and  
secure the unit to the curb with hold-down brackets as illus-  
trated in Figure 8, insert A.  
5. IMPORTANT: The unit must be lowered into position. The  
P.V.C. rubber tape on the curb flange permits the unit to be  
repositioned if required without destroying the P.V.C. rub-  
ber seals affixed to the mounting curb.  
7
SPREADER BARS  
OUTDOOR COIL  
END OF UNIT  
BASE OF UNIT  
REST ON TOP OF  
CURB RAILS  
DRIP LIP ON  
PERIMETER OF UNIT  
“B”  
UNIT CORNER  
DRIP LIP  
BAYLIFT002A  
LIFTING LUGS  
DIMPLE  
CURB CORNER  
SEE DETAIL “A”  
GASKET SEAL  
NOTE:  
THE INNER PERIMETER OF THE DRIP LIP ON ALL UNITS  
SHOULD BE FLUSH WITH THE OUTER PERIMETER OF THE  
CURB ON THE TWO SIDES SHOWN HERE. SEE FIGURE 2 FOR  
THE LOCATION OF THE UNIT OVERHANG ON THE  
YCZ036-060F MODELS.  
“A”  
8
EXISTING  
SHEET METAL  
SCREW  
HOLD-DOWN  
BRACKET WITH  
CURB  
“A”  
FLANGE OF  
CURB  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
ROOFTOP -- UNITS  
4. Place the unit on the frame or roof curb. Refer to Figures 9 or  
10.  
For roof top applications using a field fabricated frame and ducts,  
use the following procedure:  
5. Secure the unit to the frame or roof curb.  
1. The frame must be located and secured by bolting or welding  
to the roof. Flashing is required.  
6. Insulate any ductwork outside of the structure with at least two  
(2) inches of insulation and then weatherproof. There must be  
a weatherproof seal where the duct enters the structure.  
2. The hole in the roof must be prepared in advance of installing  
the unit.  
7. Complete the installation according to the instructions in the  
following sections of this manual.  
3. Secure the ducts to the roof.  
TYPICAL ROOFTOP APPLICATION WITH FRAME  
(YCZ036,050,060F)  
9
RETURN AIR SUPPLY AIR  
WEATHER-PROOF  
DUCT  
FLUE  
INLET HOOD  
ROOF FLASHING  
ANGLE IRON  
FRAME  
TYPICAL ROOFTOP APPLICATION WITH FRAME  
(YCZ036,060F MODELS)  
0
FLUE  
INLET HOOD  
WEATHER-PROOF  
ROOF FLASHING  
DUCT  
SUPPLY AIR  
ROOF FLASHING  
RETURN AIR  
ANGLE IRON  
FRAME  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
GROUND LEVEL -- HORIZONTAL UNITS  
2. Attach the supply and return air ducts to the unit.  
For ground level installations, the unit should be positioned on a pad  
the size of the unit or larger. The unit must be level on the pad. The  
pad must not come in contact with the structure (See Figure 11.) Be  
sure the outdoor portion of the supply and return air ducts are as  
short as possible.  
3. Insulate any ductwork outside of the structure with at least 2  
inchesofinsulationandweatherproof.Theremustbeaweather-  
proof seal where the duct enters the structure.  
4. Complete the installation according to the instructions in the  
following sections of this manual.  
Proceed with the installation as follows:  
1. Place the unit on the pad and the five (5) rubber isolators  
provided.  
TYPICAL GROUND LEVEL APPLICATION  
(YCZ036,050,060F MODELS)  
q
OUTDOOR AIR  
DISCHARGE  
SUPPLY AIR  
DUCT  
RETURN AIR  
DUCT  
SIDING  
OUTDOOR AIR  
INTAKE  
FLUE  
INLET HOOD  
SUPPORT PAD  
FOUNDATION  
EXTERIOR  
WALL  
INSULATE  
WEATHERPROOF  
OR RAIN SHIELD  
ISOLATORS  
(1 PER CORNER  
AND 1 UNDER  
FLEXIBLE DUCT  
CONNECTORS  
UNIT CONTROL BOX)  
CONDENSATE DRAIN PIPING  
A 3/4-inch female NPT condensate drain connection is provided on  
the evaporator access panel end of the unit. See Figure 4. Provide  
a trap and fill it with water before starting the unit to avoid air from  
being drawn through. Follow local codes and standard piping  
practices when running the drain line. Pitch the line downward away  
from the unit. Avoid long horizontal runs. See Figure 12.  
TYPICAL CONDENSATE DRAIN PIPING  
w
3
/
4" PVC OR COPPER  
TUBING AND FITTINGS  
NOTE: Do not use reducing fittings in the drain lines. The  
condensate drain must be:  
1-1/2" MIN.  
Made of 3/4" pipe size.  
Pitched 1/4" per foot to provide free drainage to convenient drain  
system.  
Trapped.  
Must not be connected to closed drain system.  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DUCTWORK  
ATTACHING DOWNFLOW DUCTWORKTOROOFCURB  
ATTACHING HORIZONTAL DUCTWORK TO UNIT  
All conditioned air ductwork should be insulated to minimize heating  
and cooling duct losses. Use a minimum of two (2) inches of  
insulation with a vapor barrier. The outside ductwork must be  
weatherproofed between the unit and the building.  
Supply and return air flanges are provided on the roof curb for easy  
duct installation. All ductwork must be run and attached to the curb  
before the unit is set into place.  
Follow these guidelines for ductwork construction:  
When attaching ductwork to a horizontal unit, provide a flexible  
watertight connection to prevent noise transmission from the unit to  
the ducts. The flexible connection must be indoors and made out  
of heavy canvas.  
Connections to the unit should be made with three-inch canvas  
connectors to minimize noise and vibration transmission.  
Elbows with turning vanes or splitters are recommended to mini-  
mize air noise and resistance.  
NOTE: Do not draw the canvas taut between the solid ducts.  
The first elbow in the ductwork leaving the unit should be no closer  
than two feet from the unit, to minimize noise and resistance.  
AIR PROOF  
THIS SEAM  
UNIT BASE  
UNIT EXTERIOR  
WEATHERPROOF  
FIELD DUCT  
THIS SEAM  
UNIT DUCT  
FLANGE  
UNIT DUCT  
FLANGE  
FIELD DUCT  
AIR PROOF  
THIS SEAM  
UNIT DUCT  
FLANGE  
UNIT EXTERIOR  
UNIT BASE  
FIELD DUCT  
UNIT DUCT FLANGE  
WEATHERPROOF  
THIS SEAM  
AIR PROOF  
THIS SEAM  
FIELD DUCT  
UNIT BASE  
FIELD  
DUCT  
UNIT DUCT FLANGE  
UNIT BASE  
UNIT EXTERIOR  
WEATHERPROOF  
UNIT DUCT  
FLANGE  
THIS SEAM  
UNIT DUCT  
FLANGE  
WATERPROOF SEAM  
WITH BUTYL OR  
SILICONE  
FIELD DUCT  
NOT RECOMMENDED  
FIELD DUCT  
HORIZONTAL  
DOWNFLOW  
The following warning complies with State of California law, Proposition 65.  
Wash clothes separately from other clothing: rinse  
washer thoroughly.  
WARNING:  
This product contains  
fiberglass wool insulation! Fiberglass dust and ceramic  
fibers are believed by the State of California to cause  
cancer through inhalation. Glasswool fibers may also  
cause respiratory, skin, or eye irritation.  
Operations such as sawing, blowing, tear-out, and  
spraying may generate fiber concentrations requiring  
additional respiratory protection. Use the appropriate  
NIOSH approved respirator in these situations.  
PRECAUTIONARY MEASURES  
FIRST AID MEASURES  
Eye Contact  
Avoid breathing fiberglass dust.  
-
Flush eyes with water to remove dust.  
If symptoms persist, seek medical  
attention.  
Use a NIOSH approved dust/mist respirator.  
Avoid contact with the skin or eyes. Wear long-  
sleeved, loose-fitting clothing, gloves, and eye  
protection.  
Skin Contact - Wash affected areas gently with soap  
and warm water after handling.  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS PIPING INSTALLATION  
CAUTION: Before making the gas pipe connection give seri-  
NOTE: If this is an LPG application, consult your LPG supplier  
for pipe sizes and deliveries.  
ous consideration to providing the required clearance neces-  
sary to remove the access panels on the unit (e.g., economizer  
and filter access panels).  
GAS PRESSURE SETUP PRECAUTIONS  
NOTE: In the absence of local codes, the installation must  
conform with American National Standard--Z223.1--National  
Fuel Gas Code, Latest Revision.  
WARNING:  
NEVER USE AN OPEN FLAME  
TO TEST FOR GAS LEAKS: AN EXPLOSION COULD  
OCCUR, CAUSING INJURY OR DEATH.  
The available gas supply must agree with the required gas supply  
marked on the unit nameplate. Minimum permissible gas supply  
pressure for purpose of input adjustment must be at least 7.0 in.  
w.c.(incheswatercolumn)fornaturalgasand11in.w.c.forLPgas.  
IMPORTANT: The furnace and its individual shut-off valve  
must be disconnected from the gas supply piping system  
during any pressure testing of that system at test pressures  
exceeding 1/2 psig (3.48 kPa).  
PIPE DELIVERY SCHEDULE  
The furnace must be isolated from the gas supply piping system by  
closing its individual manual shut-off valve during any pressure  
testing of the gas supply piping system at test pressures less than  
or equal to 1/2 psig (3.48 kPa).  
NOTE: The following procedure and tables below apply to  
Natural Gas only.  
1. Obtain from the gas company the heating value and specific  
gravity of the gas delivered.  
GAS SUPPLY LINE PRESSURE  
2. Determine the exact length of pipe needed.  
3. Read BTUH input nameplate on the furnace.  
Before connecting the unit to the gas supply line, be sure to  
determine the gas pressure in the line.  
If the gas supply pressure is excessive (above 14 inches water  
column or 1/2 psig), install a pressure regulator either at the supply  
source or in the branch circuit serving the unit. Once the regulator  
is installed, set it to provide a pressure of 7 inches water column with  
the unit operating and no greater than 14 inches water column with  
the unit not firing.  
4. Use the multiplier opposite the specific gravity of the gas given  
in Table 1 below and insert in the following formula:  
Furnace Input in BTUH  
CFH =  
Gas Heat Content in BTU/Cu. Ft. X Multiplier  
TABLE 1  
NOTE: Gas pressure in excess of 14 inches water column  
(1/2 psig) may damage the regulator, while improper regulation  
may result at pressures lower than 5.5 inches water column at  
the unit inlet.  
This will give the factor for columns 2 through 6 in Table 2.  
SPECIFIC  
MULTIPIER  
GRAVITY  
.50  
.55  
.60  
.65  
1.10  
1.04  
1.00  
.962  
MULTIPIERS TO BE USED  
WHEN THE SPECIFIC  
GRAVITY OF THE GAS IS  
OTHER THAN 0.60  
If the supply line pressure is below the minimum supply pressure  
indicated on the unit nameplate, contact the gas supply company.  
Follow these steps to complete the installation of the unit gas piping.  
See Figure 14.  
5. Using Table 2, select the pipe length nearest to yours.  
1. Install a tapped, Style A (1/8-inch NPT tap) shut-off gas cock at  
the end of the gas supply line near the unit. Be sure the tapped  
gas cock is downstream of the pressure regulator, if used.  
TABLE 2  
6. Follow this line vertically down to the exact CFH found in Step 4  
above or the next highest value.  
SCHEMATIC DIAGRAM OF  
NATURAL GAS ONLY  
r
GAS PIPING TO UNIT  
TABLE OF CUBIC FEET PER HOUR OF GAS  
FOR VARIOUS PIPE SIZES AND LENGTHS  
DEALER INSTALLED  
GROUND UNION  
PIPE  
SIZE  
LENGTH OF PIPE (feet)  
1/8" N.P.T.PLUGGED  
ACCESS FOR TEST  
GAUGE CONNECTION  
(inch)  
10  
132  
278  
520  
1050  
20  
92  
30  
73  
40  
63  
50  
56  
60  
50  
70  
46  
1/2  
3/4  
1
FROM  
GAS SUPPLY  
6"  
MIN  
190  
350  
730  
152  
285  
590  
130  
245  
520  
115  
215  
440  
105  
195  
400  
96  
TO MAIN  
CONTROL  
VALVE  
180  
370  
1-1/4  
DRIP LEG  
FIELD SUPPLIED MAIN  
UNIT  
THIS TABLE IS BASED ON PRESSURE DROP OF 0.3 INCH W.C. AND 0.6 SP.GR. GAS  
GAS VALVE, MUST BE  
INSTALLED BY DEALER  
OUTSIDE UNIT.  
7. Read horizontally to the left of this column for the required pipe  
size diameter.  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS PIPING INSTALLATION  
NOTE: The shut-off gas cock must be installed outside of the  
t BURNER & VALVE ILLUSTRATION  
unit and should meet the specifications of all applicable national  
and local codes.  
2. Install a ground union joint downstream of the shut-off cock.  
This joint must also be installed outside of the unit.  
COVER  
ALTERNATE  
MANUAL  
"ON/OFF"  
SWITCH  
3. Install a drip leg at least six (6) inches in depth next to the union  
as shown in Figure 14. This drip leg is required to collect any  
sediment that may be deposited in the line.  
BRACKET-BURNER  
HOLD DOWN  
FUSE LINK  
4. Before connecting the piping circuit to the unit, bleed the air  
from the supply line. Then cap or plug the line and test the  
pressure at the tapped shut-off cock. The pressure reading  
should not exceed 14 inches water column.  
SCREW  
BURNER  
1ST STAGE  
ADJUSTMENT  
3/32" ALLEN  
ORFICE  
GAS VALVE  
5. Using an appropriate backup wrench on the gas valve inlet  
boss, connect the gas piping to the unit. Check the completed  
piping for leaks using a soap and water solution or the equiva-  
lent.  
2ND STAGE  
ADJUSTMENT  
3/32" ALLEN  
SCREW  
6. After installation of the gas pipe in the unit, the pipe chase  
opening should be closed with the filler/barrier plug provided.  
BRACKET  
BURNER  
SUPPORT  
MANIFOLD  
MANIFOLD PRESSURE  
C664400  
Check the manifold pressure at the unit gas valve. Do not exceed  
the recommended pressure shown on the unit nameplate.  
FLUE AND HOOD ILLUSTRATION  
y
C664399  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS PIPING INSTALLATION  
INPUT CHECK AND ADJUSTMENT  
TABLE 3  
GAS FLOW IN CUBIC FEET PER HOUR  
1. Make sure all gas appliances are off except the furnace.  
2 CUBIC FOOT DIAL  
Sec. Flow Sec. Flow Sec. Flow Sec. Flow  
2. Clock the gas meter with the furnace operating (determine the  
dial rating of the meter) for one revolution.  
8
900  
800  
720  
655  
600  
555  
514  
480  
450  
424  
400  
379  
360  
343  
327  
313  
300  
288  
277  
267  
257  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
248  
240  
232  
225  
218  
212  
206  
200  
195  
189  
185  
180  
176  
172  
167  
164  
160  
157  
153  
150  
147  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
62  
64  
66  
68  
70  
72  
74  
76  
78  
80  
144  
141  
138  
136  
133  
131  
129  
126  
124  
122  
120  
116  
112  
109  
106  
103  
100  
97  
82  
84  
88  
86  
84  
82  
80  
78  
76  
75  
73  
72  
69  
67  
64  
62  
60  
58  
56  
54  
53  
51  
50  
9
3. Match the “Sec” column in the gas flow (in cfh) Table 3 with the  
time clocked.  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
86  
88  
90  
92  
94  
96  
98  
100  
104  
108  
112  
116  
120  
124  
128  
132  
136  
140  
144  
4. Read the “Flow” column opposite the number of seconds  
clocked.  
5. Use the following factors if necessary.  
For 1 Cu. Ft. Dial Gas Flow CFH =  
Chart Flow Reading / 2  
For 1/2 Cu Ft. Dial Gas Flow CFH =  
Chart Flow Reading / 4  
For 5 Cu. Ft. Dial Gas Flow CFH =  
10X Chart Flow Reading / 4  
6. Multiply the final figure by the heating value of the gas obtained  
from the utility company and compare to the nameplate rating.  
This must not exceed the nameplate rating.  
95  
92  
90  
7. Changes can be made by adjusting the manifold pressure.  
a. Attach a manifold pressure gauge.  
b. Remove the slot screw on top of the gas valve for 1st stage  
manifold pressure adjustment. Remove slot screw on outlet  
side for 2nd stage adjustment (See Figure 17).  
u
c. Turn the adjustment nut in to increase the gas flow rate, and  
out to decrease the gas flow rate using a 3/32" hex wrench.  
2nd Stage (Hi)  
Manifold  
Pressure  
Note:  
If Model YCZ036F1,3M is installed in a region where NOX must be  
below 40 nanograms per input to 72,000 BTUH.  
Adjustment  
HIGH ALTITUDE INSTALLATION  
1st Stage (Lo)  
Manifold  
Pressure  
Unit nameplate ratings are based on equipment operation from sea  
level to 2000 feet elevation above sea level. If the unit installation  
is from 2000 - 4500 feet elevation, it will be necessary to change  
the burner orifices to the noted sizes, (ref. National Fuel Gas Code,  
sec 8.1.2, Appendix F, Table F4).  
Adjustment  
GAS  
TYPE  
MAN. PRESS  
( in. W.C. )  
ORIFICE SIZE  
0 - 2000 ft  
ORIFICE SIZE  
2000 - 4500 ft  
NATURAL  
PROPANE  
3.3  
43  
55  
42*  
10.0  
54  
* FACTORY SHIPPED  
Switch Toggles  
"ON" or "OFF"  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FILTER INSTALLATION  
AIR FILTERS  
TABLE 4  
NOMINAL  
FILTER*  
Sq.Ft.- SIZE RESISTANCE  
FILTER  
Filters are to be used with the YCZ036,050,060F heating/cooling  
units. The basic unit does not have filters in it. However, a filter  
frame accessory is offered that will allow filters to be installed within  
the unit.  
UNIT  
CFM  
1200  
1600  
2000  
YCZ036F  
YCZ050F  
YCZ060F  
4
0.05  
0.05  
0.05  
5.33  
6.67  
Otherwise a filter rack must be installed by the installer in the duct  
work.  
Affix the filter label supplied with the unit adjacent to the filter area.  
*Filters must be installed in the return air system. The above square  
footages are based on 300 F.P.M. face velocity. If permanent filters are  
used, size per mfg. recommendation with clear resistance of 0.05" WC.  
ELECTRICAL WIRING  
ELECTRICAL CONNECTIONS  
NOTE: Unit must be grounded for ignitor to operate prop-  
erly. Gas pipe to unit is not an adequate ground. Ground  
the unit internally as provided. See wiring diagram for  
location.  
Electrical wiring and grounding must be installed in accordance with  
local codes or, in the absence of local codes, with the National  
Electrical Code ANSI/NFPA 70, Latest Revision.  
CONTROL WIRING (CLASS II)  
ELECTRICAL POWER  
Low voltage control wiring should not be run in conduit with power  
wiring unless Class 1 wire of proper voltage rating is used. Route  
the thermostat cable or equivalent single leads of No. 18 AWG  
colored wire from the thermostat subbase terminals through the  
rubber gromment on the unit. See Figures 3 and 4 for the control  
entry location. Make connections as shown on the unit wiring  
diagram and in Figure 18.  
It is important that proper electrical power be available for the unit.  
Voltage variation should remain within the limits stamped onthe unit  
nameplate.  
DISCONNECT SWITCH  
Provide an approved weatherproof disconnect either on the side of  
the unit or within close proximity and within sight of the unit.  
Do not short thermostat wires since this will damage the control  
transformer.  
OVER CURRENT PROTECTION  
Recommended wire sizes and lengths for installing the unit thermo-  
stat are provided in Table 5. The total resistance of these low  
voltage wires must not exceed one (1) ohm. Any resistance in  
excess of 1 ohm may cause the control to malfunction because of  
the excessive voltage drop.  
The branch circuit feeding the unit must be protected as shown on  
the unit rating plate.  
POWER WIRING  
The power supply lines must be run in weathertight conduit to the  
disconnectandintothebottomoftheunitcontrolbox. Providestrain  
relief for all conduit with suitable connectors.  
TABLE 5  
THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH  
WIRE SIZE  
MAXIMUM LENTGH (Ft)  
Provide flexible conduit supports whenever vibration transmission  
may cause a noise problem within the building structure.  
18  
16  
14  
75  
125  
200  
Be sure all connections are made tight. See Figure 18.  
NOTES: For branch circuit wiring (main power supply to unit  
disconnect), wire size for the length of run should be determined  
using the circuit ampacity found on the unit nameplate and the  
N.E.C.  
THERMOSTAT HEAT ANTICIPATOR  
The thermostat heat anticipators should be set to .4 amps on single  
or two stage thermostats.  
For more than 3 conductors in a raceway or cable, see the  
N.E.C. for derating the ampacity of each conductor.  
IMPORTANT: Upon completion of wiring check all electrical  
connections, including factory wiring within the unit, make  
sure all connections are tight. Replace and secure all electrical box  
covers and access doors before leaving the unit or turning on the  
power to the unit.  
GROUNDING: THEUNITMUSTBEELECTRICALLYGROUNDED  
IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL  
ELECTRIC CODE.  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
After all electrical wiring is complete, set the thermostat system  
the Thermostat System Switch until power has been applied long  
enough to evaporate any liquid R-22 in the compressor. It is  
recommended that the sump heater be energized for eight (8) hours  
prior to starting.  
switch in the OFF position so that the compressor will not run  
and then apply power by closing the system main disconnect  
switch. This will activate the compressor sump heat. Do not change  
YCZ-F FIELD WIRING DIAGRAM  
i
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START - UP  
NOTE: Donotusethepressuresfromtheunit'sSERVICEFACTS  
PRE-START QUICK CHECKLIST  
to determine the unit refrigerant charge. The correct charge is  
shown on the unit nameplate. To charge the system accurately,  
weigh in the charge according to the unit nameplate.  
Is the unit properly located and level with the proper clearance?  
See Figure 4.  
Is the duct work correctly sized, run, taped, insulated, and  
weatherproofed with proper unit arrangement? See Ductwork  
Installation section.  
VOLTAGE  
With the compressor operating, check the line voltage at the unit.  
The voltage should be within the range shown on the unit name-  
plate. If low voltage is encountered, check the size and length of the  
supply line from the main disconnect to the unit. The line may be  
undersized for the length of the run.  
Is the gas piping correctly sized, run, trapped, and purged of air?  
See Gas Piping section.  
Is the condensate line properly sized, run, trapped, and pitched?  
COOLING SHUT DOWN  
Is the filter of the correct size and number? Is it clean and in place?  
Place the system selector in the OFF position or reset thermostat at  
a setting above room temperature.  
Is the wiring properly sized and run according to the unit wiring  
diagram?  
Do not de-energize the main power disconnect except when unit is  
to be serviced. Power is required to keep the heat pump compres-  
sor warm and boil off refrigerant in the compressor.  
Are all the wiring connections, including those in the unit, tight?  
Has the unit been properly grounded and fused with the recom-  
mended fuse size? See Wiring Data.  
HEATING CYCLE  
Is the thermostat level, correctly wired, well located, and set for  
NOTE: See Sequence of Heating Operation.  
the proper heat anticipation?  
These units are equipped with a solid-state ignition control that  
lights the burners each time the thermostat calls for heat. The  
burners are extinguished during the OFF cycle.  
Have the air conditioning systems been checked at the service  
ports for charge and leak tested if necessary?  
Does the condenser fan and indoor blower turn free without  
Thegasheatingsectionoftheunitcanbestartedusingthefollowing  
procedure:  
rubbing, and are they tight on the shafts?  
Has the indoor blower speed been determined and the proper  
1. Be sure the thermostat is at its lowest setting and the power to  
the unit is off.  
speed been set? See the Unit Wiring Diagram.  
Has all work been done in accordance with applicable local and  
a. Turn the main shutoff valve on the gas supply line ON.  
national codes?  
b. Turn or switch the manual valve on the combination gas  
valve ON position.  
Are all covers and access panels in place to prevent air loss and  
safety hazards?  
2. Be sure the burner compartment access panel is in place.  
a. Turn on the electrical power to the unit.  
STARTING THE UNIT IN THE COOLING MODE  
b. Turn the thermostat to the highest setting in the heating  
cycle.  
CAUTION: Before starting the system on the cooling cycle, turn the  
thermostat switch to OFF and close the unit disconnect switch. This  
procedure energizes the compressor crankcase heater, vaporizing  
any liquid refrigerant in the crankcase. This is a precaution against  
foaming at start-up which could damage the compressor bearings.  
Allow the heater to operate a minimum of eight (8) hours.  
3. As the thermostat calls for heat, the system cycles as follows:  
a. The combustion blower is energized.  
b. The pressure switch is closed.  
NOTE: See the section on “Sequence of Operation” for a  
c. The gas valve opens and the ignitor lights the burner.  
description of the cooling operating sequence.  
d. Cycle the thermostat on and off a few times to check out the  
control system and burner operation characteristics.  
To start the unit in the cooling mode, set the thermostat system  
switch to COOL and move the thermostat COOL indicator to a  
setting below room temperature. The condenser (outdoor) fan  
motor compressor and evaporator (indoor) fan motor will operate  
automatically.  
4. With the burners operating, check the manifold pressure with a  
manometer. Do not exceed recommended pressures.  
5. Adjust the unit to obtain an air temperature rise with that  
specified on the unit nameplate.  
OPERATING PRESSURES  
6. NOTE: For manifold pressures and orifice sizes for gas with  
other BTU ratings, contact the local gas utility. Manifold  
pressure should be 3.3 inches water column (+0.1). Input must  
not exceed the value shown on the rating plate.  
After the unit has operated in the cooling mode for a short period of  
time, install pressure gauges on the gauge ports of the discharge  
and suction line valves. Check the suction and discharge pressures  
and compare them to the normal operating pressures provided in  
the unit’s SERVICE FACTS.  
7. Set the heatanticipatorof the thermostatto equal the amperage  
draw of the gas valve, approximately 0.7.  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START - UP  
8. Set the thermostat at the desired temperature setting and the  
6. Cycle the thermostat OFF and ON a few times at a rate of not  
more than once every thirty (30) seconds. Check both the  
control operation and the burner operating conditions.  
unit will function automatically.  
STARTING THE UNIT IN THE GAS HEATING MODE  
MANIFOLD PRESSURE  
1. Check to make sure all grilles and registers are open and all unit  
access doors are closed before start-up.  
1. Connect a manometer to the pressure tap at the outlet side of  
the unit’s gas valve. Read the manifold pressure with the main  
burners firing.  
2. Purge the gas supply line of air by opening the union ahead of  
the unit. When the odor of gas is detected, retighten the union  
and wait five (5) minutes before proceeding.  
2. If the manifold pressure reading does not match the value  
indicated on the unit nameplate, the unit pressure regulator  
must be adjusted as follows:  
3. Set the wall thermostat to its lowest position and place the fan  
switch in the AUTO or ON position.  
a. Remove the cover screw on the gas regulator located on the  
front side of the unit’s gas valve.  
4. Open the main gas valve(s) and turn on the unit power supply.  
b. Turn the adjusting screw clockwise to increase manifold  
pressure or counterclockwise to decrease manifold pres-  
sure.  
5. Reset the heating temperature lever on the room thermostat at  
the highest value above room temperature. The combustion  
blower motor should energize. The main burners should light  
within 20-25 seconds. Initial start may be delayed somewhat if  
the unit has not been purged and air is trapped in the gas line.  
3. Check the temperature rise during furnace operation to insure  
that it falls within the range specified on the unit nameplate.  
NOTE: Blue smoke produced by the heat exchanger during the  
initial burner firing is caused by a thin film of oil on the surface  
of the heat exchanger. This oil will burn off quickly.  
4. If the temperature rise noted is outside of the specified limits,  
adjust the indoor air flow to cause the temperature rise of the  
heat exchanger to fall within the required range.  
SEQUENCE OF OPERATION  
Operation of the unit heating or cooling cycles is controlled by the  
setting of the system switch on the room thermostat. Once the  
system switch is placed either in the “HEAT” or “COOL” position,  
unit operation is automatic. A fan switch on the thermostat also  
provides for it continuous operation of the evaporator fan when  
desired. The fan switch “ON” position provides continuous opera-  
tion while the “AUTO” position provides operation during the heat-  
ing or cooling cycles.  
Call for 2nd stage after 1st stage:  
(R) and (W2) thermostat contacts close signaling a call for second  
stage heat. The induced draft motor (CBM) is energized on high  
speed and the gas valve on second stage. After approximately 30  
seconds the control energizes the indoor blower on high speed.  
2nd stage satisfied, 1st stage still called:  
(R) and (W2) opens, the induced draft blower is reduced to low  
speed the gas valve is reduced to first stage. After aprox. 30  
seconds the indoor blower motor is reduced to low speed.  
1st stage satisfied:  
HEATING CYCLE  
Thermostat call for heat ( 2-stage thermostat)  
(R) and (W1) opens, the gas valve (GV) will close. The induced draft  
blower (CBM) will be de-energized after approximately 5 seconds  
postpurge. Theindoorblowermotor(IDM)willcontinuetorunforthe  
fan off period (field selectable 60 or 90 seconds [by jumpers]), then  
will be de-energized by the control module.  
Call for 1st stage only:  
(R) and (W1) thermostat contacts close signaling the control mod-  
ule (IGN) to run its self-check routine. After the control has verified  
that the pressure switch (PS) contacts are open, the limit switch  
(TCO) contacts are closed, and the flame rollout (FL) switch is  
closed, the induced draft blower (CBM) will be energized on high  
speed for approximately 15 seconds.  
Thermostat satisfied:  
(R) and (W1/W2) (jumpered) contacts open signaling the control  
module to close the gas valve and de-energize the induced draft  
blower after approximately 5 second postpurge. The I.D. blower  
motor will continue to operate at the current speed for 60 or 90  
seconds after the flames are extinguished .  
After the induced draft blower (CBM) has come up to speed, the  
control will verify that the pressure switch (PS) contacts are closed  
and switch the induced draft blower to low speed for an additional  
5 seconds of prepurge. The gas valve (GV) is energized in the first  
stage to permit gas flow and the spark ignitor (IP) is energized. The  
flame detector (FD) confirms that ignition has been achieved within  
the 7 second trial period.  
SAFETY SEQUENCES  
This product is equipped with safety devices to protect against  
abnormal conditions.  
The temperature limit switch (TCO) is located in the gas com-  
partment on the vestibule panel above the burner assembly. This  
automatic reset device protects against excessive leaving air  
temperature. If this device opens, the gas valve is immediately  
closed and will not permit operation until the limit switch closes.  
As the flame detector confirms that ignition has been achieved the  
delay to indoor fan on period begins timing and after approximately  
45 seconds, the indoor blower motor (IDM) will be energized at low  
speed and will continue to run during the heating cycle.  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEQUENCE OF OPERATION  
The rollout switch (FS) is located in the gas compartment near the  
Call for 2nd stage after 1st stage:  
inlet of the burners. This is a single use device designed to protect  
against any form of flame rollout. If this device is opened the gas  
valve is immediately de-energized and the control (IGN) will lockout  
the system. The rollout switch (FS) must be replaced before  
operation is allowed to continue.  
The Y2 thermostat contact closes to the control board. For 1 minute  
both compressors are off, (all lights are flashing for 1 minute), than  
the board will energize the (CC2) compressor contactor, and the  
outdoor fan relay for high speed then the board (YCZ050 ONLY- will  
energize the (CC1) and 1 second later the (CC2) compressor  
contactors) and the indoor fan high to the Y on the ICMC board is  
energized for indoor high speed fan operation. (The status light is  
flashing and the Y1 and Y2 lights are on.)  
The pressure switch (PS) is located in the upper right side of the gas  
compartment. This automatic device assures adequate combus-  
tion air pressure. If pressure against the induced draft blower outlet  
becomes excessive, the pressure switch will react and shut off the  
gas valve, until acceptable combustion pressure is again available.  
2nd stage satisfied, 1st stage still called:(YCZ036,060F ONLY)  
The Y2 thermostat contact opens to the control board. For 1 minute  
both compressors are off, (the status and Y1 light are flashing for 1  
minute),thantheboardwillenergize(CC1)lowcompressorcontactor,  
andtheoutdoorfanrelayforlowspeedandindoorfanforlowspeed.  
(The status light is flashing and the Y1 light is on.)  
If the control (IGN) does not sense flame within the first trial for  
ignition period. The gas valve will be de-energized. The control  
(IGN) will initiate a 60 seconds interpurge. Following the interpurge,  
on the second trial the gas valve will be energized on second stage  
(high heat input). If the flame is sensed within 10 seconds after the  
second try and only a call for first stage exists, the gas valve will be  
reduced to first stage. If the second try is not successful. The control  
will start other 60 second interpurge. After the interpurge, a third  
attempt will be tried. The gas valve will be energized on second  
stage (high heat input). If the flame is sensed within 10 seconds  
after the third try and only a call for first stage exists, the gas valve  
will be reduced to first stage. If the third try is not successful. The  
control will lock out.  
2nd stage satisfied, 1st stage still called:( YCZ050 ONLY)  
The Y2 thermostat contact opens to the control board. The board  
will de-energize (CC2) second compressor contactor, and ener-  
gize the outdoor fan relay for low speed and indoor fan for low  
speed. (The status light is flashing and the Y1 light is on.)  
ICM FAN MOTOR ADJUSTMENTS  
If the airflow needs to be increased or decreased, see the Indoor  
Blower Performance Table below. Information on changing the dip  
switch settings for speed control of the blower motor is in this table.  
Blower speed changes are made on the ICM Fan Control mounted  
in the control box. The ICM Fan Control controls the variable speed  
motor.  
If loss of flame occurs during a heating cycle, the control (IGN) will  
close the gas valve. The control will than recycle the ignition  
sequence, then if ignition isnot achieved, it willshut off the gasvalve  
and lock out the system.  
There is a bank of 8 dip switches, (See Figure below), located at the  
lower right side of the board. The dip switches work in pairs to select  
the cooling/heat airflow (CFM/TON), and Fan off-delay options.  
If control lock out occurs, the control (IGN) will retry a complete  
ignition sequence in 1 hour.  
The control (IGN) can be reset by removing power to the unit or by  
turning the thermostat from “on” to “off" for approximately three  
seconds, then back “on.”  
INDOOR BLOWER TIMING  
The ICM Fan Control controlsthe variable speed indoor blower. The  
FAN-OFF period is set on the ICM Fan Control board by dip  
switches #5 and #6.  
COOLING CYCLE  
Thermostat call for cool ( 2-stage thermostat)  
CFMICM FAN CONTROL  
Call for 1st stage only:  
o
DIP  
SELECTION  
LIGHT  
With the room thermostat system switch in the “COOLING” position  
and the fan switch in the “AUTO” position, the Y1 thermostat  
contacts closes to the micro board, (the board will wait 3 seconds  
to check if the Y2 may also be calling) the micro will energize (CC1)  
and the outdoor fan relay for low speed and the G thermostat  
contact to G-IGN and to G1 on the ICMC is energized. (The status  
light is flashing and the Y1 light is on.)  
SWITCHES  
The energized compressor contactor (CC1) completes the circuit to  
the compressor (CPR1), If the compressor safety controls are  
closed, the compressor (CPR1) will operate with the outdoor fan  
motor (ODM) on low speed. The indoor fan motor (IDM) will operate  
on low speed. The thermostat will continue to cycle the compressor  
and fans to maintain the desired temperature.  
WiththethermostatfanswitchintheONposition, theGthermostat  
contact is closed to G1 on the ICMC board and the indoor fan motor  
(IDM) will continue to run on low speed regardless of compressor  
and condenser fan operation.  
DIP SWITCHES (TYPICAL SETTINGS)  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IGN LED DIAGNOSTIC INDICATOR  
FLASHING SLOW  
CONTINUOUS ON  
CONTINUOUS OFF  
2 FLASHES  
NORMAL CALL FOR HEAT  
NORMAL  
CHECK POWER / INTERNAL FAILURE  
SYSTEM LOCKOUT ( NO FLAME )  
PRESSURE SWITCH PROBLEM  
HIGH LIMIT (TCO) OPEN  
3 FLASHES  
4 FLASHES  
5 FLASHES  
FLAME SENSED WITH GAS VALVE OFF  
FLAME ROLLOUT SWITCH (FL) OPEN  
W1 & W2 SWAPPED  
6 FLASHES  
7 FLASHES  
CHECKOUT PROCEDURE  
p
TROUBLESHOOTING CHART  
SYSTEM FAULTS  
REFRIGERANT CIRCUIT  
Liquid Pressure Too high  
Liquid Pressure Too Low  
Suction Pressure Too High  
Suction Pressure Too Low  
Liquid Refrigerant floodback (TXV System)  
Liquid Refrig. floodback (Cap. Tube System)  
I. D. Coil Frosting  
Compressor Runs Inadequate or No Cooling  
ELECTRICAL  
Compressor & O.D. fan Do Not Start  
Compressor Will Not Start But O.D. Fan Runs  
O.D. Fan Won't Start  
Compressor Hums But Will Not Start  
Compressor Cycles on IOL  
I.D. Blower Won't Start  
P-PRIMARY CAUSES S-SECONDARY CAUSES  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
ROUTINE MAINTENANCE BY OWNER  
Visually inspect the unit to ensure that the airflow required for  
combustionandcondensercoilisnotobstructedfromtheunit.  
You can do some of the periodic maintenance functions for your  
YCZ-F unit yourself; this includes replacing the disposable or  
cleaning the permanent air filters, cleaning the unit cabinet,  
cleaning the condenser coil, and conducting a general unit  
inspection on a regular basis.  
Inspect the control panel wiring to verify that all electrical  
connections are tight and that the wire insulation is intact.  
Check the operation of the gas ignition system as follows:  
Turnoffthegassupplywiththeunitoperatingtoverifythatthe  
gas valve closes and that a ignition cycle is initiated by the  
unit.  
When the system is in constant operation. In new homes,  
check the filters every week for the first four (4) weeks.  
Visually inspect the inside of the burners and the burner ports  
for deposit buildup and corrosion. Wipe and brush the inside  
of the burner and the burner ports and then clean with a dry  
cloth. If the deposit buildup or corrosion is excessive, replace  
the burners.  
If you have disposable-type filters, replace them with new filters  
ofthesametypeandsize. Donotattempttocleandisposable  
filters.  
Permanent-type filters can be cleaned by washing them with a  
mild detergent and water. Make sure that the filters are thor-  
oughly dry before reinstalling them in the unit (or duct system).  
FLUE CLEANING  
Before each heating season, the flue should be inspected for  
signs of flaking rust and soot deposits. Dirty flues should be  
cleaned by qualified service personnel ONLY using the  
following procedure:  
NOTE: It may be necessary to replace permanent filters  
annually if washing fails to clean the filter or if the filter shows  
signs of deterioration. Be sure to use the same type and size  
as was originally installed.  
1. TurntheroomthermostattotheOFFposition. Turnthemain  
power disconnect OFF. Turn the manual gas valve OFF.  
CONDENSER COIL  
2. Remove the flue cap, the lower access panel, and the upper  
access panel.  
Unfilteredaircirculatesthroughtheunit'scondensercoilandcan  
cause the coil’s surface to become clogged with dust, dirt, etc.  
To clean the coil, vertically (i.e., with the fins) stroke the coil  
surface with a soft-bristled brush.  
3. Remove the combustion blower assembly from the fluebox.  
Remove the flue box and the flue restrictors.  
4. Remove all wires from the gas value while carefully noting  
their location.  
Be sure to keep all vegetation away from the condenser coil  
area.  
5. Disconnect the gas supply line from the valve.  
6. Remove the manifold retaining screws and pull the burner-  
manifold assembly from the heat exchanger.  
WARNING:  
TO PREVENT AN EXPLOSION  
OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE,  
DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE  
7. Remove the inlet turbulators being careful not to break or  
damage them.  
8. Wipe the flue box and flue baffles clean with a clean, dry  
cloth.  
9. CAUTION: Never use combustible cleaning fluids on  
MAINTENANCE PERFORMED BY SERVICEMAN--  
COOLING SEASON  
any part of the furnace.  
10. Replace all gaskets with new ones.  
To keep your unit operating safely and efficiently, the manufac-  
turer recommends that a qualified serviceman check the entire  
system at least once each year and any other time that you feel  
one is needed. Your serviceman should examine these areas of  
your DCX-F unit:  
11. Replace all damaged or broken turbulators with new ones.  
12. Reassemble the unit by reversing Steps 2 through 7 above.  
Take care that all gaskets seat properly.  
13. Check all wires for correct installation by referring to the  
unit’s electrical wiring diagram.  
filters (for cleaning or replacement)  
motors and drive system components  
economizer gaskets (for possible replacement)  
safety controls (for mechanical cleaning)  
14. Leak test all gas line connections with a soap and water  
solution or the equivalent.  
15. Reinstall the top and bottom access panels and the flue  
stack.  
electrical components and wiring (for possible replacement  
16. Visuallyinspecttheunittoensurethattheairflowopeningfor  
combustion is not obstructed.  
and connection tightness)  
condensate drain (for cleaning)  
17. Follow the start-up procedure above to place the unit back in  
service.  
unit duct connections (to see that they are physically sound  
and sealed to the unit casing)  
unit mounting support (for structural integrity)  
WARNING:  
DO NOT OPERATE THE UNIT  
the unit (for obvious unit deterioration)  
WITHOUT THE EVAPORATOR FAN ACCESS PANEL IN  
PLACE. REINSTALL THE ACCESS PANEL AFTER  
PERFORMING ANY MAINTENANCE PROCEDURES ON THE  
FAN. OPERATING THE UNIT WITHOUT THE ACCESS  
PANEL PROPERLY INSTALLED MAY RESULT IN SEVERE  
PERSONAL INJURY OR DEATH.  
MAINTENANCE PERFORMED BY SERVICEMAN--  
HEATING SEASON  
Complete the unit inspections and service routines described  
below at the beginning of each heating season.  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
COMBINATION GAS ELECTRIC AIR CONDITIONER  
YCZ, YCY AND YCX  
Models Less Than 20 Tons for Residential Use*  
(Parts Only)  
This limited warranty is extended by American Standard Inc., to the original purchaser and to any  
succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is  
originally affixed, and applies to products purchased and retained for use within the U.S.A. and  
Canada.  
If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect  
within five years from the date of the original purchase,Warrantor will furnish without charge the  
required replacement part. Any local transportation, related service labor, diagnosis calls, air filters,  
refrigerant and related items are not included.  
In addition, if the sealed motor-compressor(s) fail(s) or the outdoor coilshould become defective,  
either or both events occurring because of a manufacturing defect within the sixth through tenth year  
from the date of original purchase,Warrantor will furnish without charge the required replacement  
compressor and/or outdoor coil. Any local transportation, related service labor, diagnosis calls,  
refrigerant and related items are not included.  
NOTE: If your Combination Gas Electric Air Conditioner is installed within one mile of salt water,  
including but not limited to seacoasts and inland waterways, your outdoor coil warranty as stated  
above is limited to five years from the date of original purchase.  
In addition, if the steel heat exchanger fails because of a manufacturing defect within the sixth  
through twentieth year  
from the date of original purchase,Warrantor will furnish without charge a replacement heat  
exchanger. Any local transportation, related service labor and diagnosis calls are not included.  
This limited warranty does not cover failure of your combination gas electric air conditioner if it is  
damaged while in your possession, damage caused by unreasonable use of the combination gas  
electric air conditioner and/or damage from failure to properly maintain the combination gas  
electric air conditioner as set forth in the Use and Care manual (see Proper Maintenance section).  
This limited warranty applies to product installed on or after 10/1/2001 where product is manufactured  
after 1/1/2000.This limited warranty is not retroactive to any installations prior to 10/1/2001 or on  
product produced prior to 2000.  
THE LIMITEDWARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER  
WARRANTIES AND LIABILITIES,WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS  
OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIEDWARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL  
WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.  
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow  
the exclusion or limitation of incidental or consequential damages, so the above limitation or  
exclusion may not apply to you.This limited warranty gives you specific legal rights, and you may  
also have other rights which vary from state to state.  
Parts will be provided by our factory organization through an authorized service organization in your  
area listed in the yellow pages. If you wish further help or information concerning this limited  
warranty, contact:  
American Standard Inc.  
Troup Highway  
GW-631-1802  
Tyler,TX 75711-9010  
Attention: Manager, After Sales Support  
*This limited warranty is for residential usage of this equipment and not applicable when this  
equipment is used for a commercial application. A commercial use is any application where the end  
Page 23  
purchaser uses the product for other than personal, family or household purposes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
COMBINATION GAS ELECTRIC AIR CONDITIONER  
YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC  
Models Less Than 20 Tons for Commercial Use*  
(Parts Only)  
his warranty is extended by American Standard Inc., to the original purchaser and to any succeeding owner of  
the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to  
products purchased and retained for use within the U.S.A. and Canada. There is no warranty against  
corrosion, erosion or deterioration.  
If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within one  
year from the date of the original purchase, Warrantor will furnish without charge the required replacement  
part.  
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through  
fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement  
compressor.  
In addition, if the steel heat exchanger fails because of a manufacturing defect within the second through fifth  
year from the date of original purchase, Warrantor will furnish without charge a replacement heat exchanger.  
Warrantor’s obligations and liabilities under this warranty are limited to furnishing F.O.B.Warrantor factory or  
warehouse at Warrantor designated shipping point, freight allowed to Buyer’s city, replacement parts for  
Warrantor’s products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost  
refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability shall be  
limited solely to the purchase price of the equipment under warranty shown to be defective.  
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER  
WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS  
OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL  
WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.  
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or  
limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.  
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.  
American Standard Inc.  
Troup Highway  
Tyler, TX 75711-9010  
Attention: Manager, After Sales Support  
GW-606-4800  
* This warranty is for commercial usage of said equipment and not applicable when the equipment is used for  
a residential application. Commercial use is any application where the end purchaser uses the product for  
other than personal, family or household purposes.  
Since Trane has a policy of continuous product and  
product data improvement, it reserves the right to  
change design and specification without notice.  
Trane  
6200 Troup Highway  
Tyler, TX 75707-9010  
A business of AmericanStandard Companies  
Technical Literature - Printed in U.S.A.  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technicolor Thomson Stereo System DPL590 User Manual
Technics Home Theater System SC EH560 User Manual
Tektronix Thermometer P6230 User Manual
Toshiba Cash Register MA 132 SERIES User Manual
Transcend Information Network Card TS0MFLRD8E User Manual
Transition Networks Switch MIL SM808GPXX User Manual
TRENDnet Switch TE100S24G User Manual
Tripp Lite TV Cables P502 010 RA User Manual
Tripp Lite Welding System APINT Series User Manual
Verona Cooktop VECTEM365 VECTEM304 User Manual