Trane Heat Pump WC IOM 7 User Manual

Installation  
Operation  
Maintenance  
Packaged Heat Pump  
Model Number  
WC*150B***G*  
WC*200B***G*  
WC*155B***G*  
WC*240B***G*  
WC*180B***G*  
December 2004  
WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ƽWARNING  
Contains Refrigerant!  
System contains oil and refrigerant under high pressure. Recover refrigerant to  
relieve pressure before opening the system. See unit nameplate for refrigerant  
type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant  
additives.  
Failure to follow proper procedures or the use of non-approved refrigerants,  
refrigerant substitutes, or refrigerant additives could result in death or serious  
injury or equipment damage.  
ƽWARNING  
Hazardous Voltage w/Capacitors!  
Disconnect all electric power, including remote disconnects and discharge all  
motor start/run capacitors before servicing. Follow proper lockout/tagout  
procedures to ensure the power cannot be inadvertently energized. Verify with  
an appropriate voltmeter that all capacitors have discharged. Failure to  
disconnect power and discharge capacitors before servicing could result in death  
or serious injury.  
NOTICE  
Equipment Damage From Ultraviolet (UV) Lights!  
The manufacturer does not recommend field installation of ultraviolet lights in  
its equipment for the intended purpose of improving indoor air quality. High  
intensity C-band ultraviolet light is known to severely damage polymer (plastic)  
materials and poses a personal safety risk to anyone exposed to the light  
without proper personal protective equipment. Polymer materials commonly  
found in HVAC equipment that may be susceptible include insulation on  
electrical wiring, fan belts, thermal insulation, various fasteners and bushings.  
Degradation of these materials can result in serious damage to the equipment.  
The manufacturer accepts no responsibility for the performance or operation of  
our equipment in which ultraviolet devices were installed outside of the  
manufacturer’s factory or its approved suppliers.  
WC-IOM-7 • Packaged Heat Pump  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
System Input Devices & Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
General Unit Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
4
WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56  
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
Heat Pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
Heat Pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
WC-IOM-7  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model Number Description  
W
1
C
2
D
3
1
4
5
5
0
6
C
7
3
8
0
9
0
B
A
10  
11  
12  
Digits 1, 2 - Product Type  
Digit 8 - Electrical characteristics  
3 = 208-230/60/3  
4 = 460/60/3  
WC = Packaged cooling, electric heat  
WF = With factory installed options  
D = 400/50/3  
Digit 3 - Airflow Configuration  
D = Downflow  
T = 380/60/3  
W = 575/60/3  
H = Horizontal  
Digit 9, 10 - Factory installed options  
Digit 4, 5, 6 - Nominal gross cooling capacity (MBh) 00 = No factory installed options  
150 = 12 1/2 tons standard efficiency  
180 = 15 tons standard efficiency  
240 = 20 tons standard efficiency  
0A = Factory-installed economizer  
0B = Oversized motor  
0C = Downflow economizer/oversized motor  
0F = Trane communications interface (TCI)  
0G = Downflow economizer/TCI  
Digit 7 - Major development sequence  
Digit 11 - Minor design sequence  
Digit 12 - Service digit  
6
WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Information  
Unit Nameplate  
A Mylar unit nameplate is located on the units corner support next to the control  
box. It includes the unit model number, serial number, electrical characteristics,  
refrigerant charge, as well as other pertinent unit data.  
Compressor Nameplate  
The nameplate for the compressors are located on the side of the compressor.  
Unit Description  
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant  
and compressor oil, and run tested for proper control operation.  
The condenser coils are aluminum fin, mechanically bonded to copper tubing.  
Direct-drive, vertical discharge condenser fans are provided with built-in thermal  
overload protection.  
The ReliaTel™ Control Module is a microelectronic control system that is referred  
to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively  
throughout this document when referring to the control system network.  
This module through Proportional/Integral control algorithms perform specific  
unit functions that governs unit operation in response to; zone temperature,  
supply air temperature, and/or humidity conditions depending on the  
application. The stages of capacity control for these units are achieved by starting  
and stopping the compressors.  
The RTRM is mounted in the control panel and is factory wired to the respective  
internal components. The RTRM receives and interprets information from other  
unit modules, sensors, remote panels, and customer binary contacts to satisfy  
the applicable request for cooling.  
Economizer Control Actuator ReliaTel™ Control  
The ECA monitors the mixed air temperature, return air temperature, minimum  
position setpoint (local or remote), power exhaust setpoint, CO2 setpoint, CO2,  
and ambient dry bulb/enthalpy sensor or comparative humidity (return air  
humidity against ambient humidity) sensors, if selected, to control dampers to an  
accuracy of +/- 5% of stroke. The actuator is spring returned to the closed  
position any time that power is lost to the unit. It is capable of delivering up to 25  
inch pounds of torque and is powered by 24 VAC.  
RTCI -- ReliaTel™ Trane Communication Interface (Optional)  
This module is used when the application calls for an ICSTM building  
management type control system. It allows the control and monitoring of the  
system through an ICS panel. The module can be ordered from the factory or  
WC-IOM-7 • Packaged Heat Pump  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
General Information  
ordered as a kit to be field installed. Follow the installation instruction that ships  
with each kit when field installation is necessary.  
RLCI - ReliaTel™ LonTalk Communication Interface (Optional)  
This module is used when the application calls for an ICSTM building  
management type control system that is LonTalk. It allows the control and  
monitoring of the system through an ICS panel. The module can be ordered from  
the factory or ordered as a kit to be field installed. Follow the installation  
instruction that ships with each kit when field installation is necessary.  
RTOM – ReliaTel™ Options Module (Optional)  
The RTOM monitors the supply fan proving, clogged filter, supply air  
temperature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke  
detector. Refer to system input devices and functions for operation.  
System Input Devices & Functions  
The RTRM must have a zone sensor or thermostat input in order to operate the  
unit. The flexibility of having several mode capabilities depends upon the type of  
zone sensor or thermostat selected to interface with the RTRM.  
The descriptions of the following basic Input Devices used within the RTRM  
network are to acquaint the operator with their function as they interface with the  
various modules. Refer to the units electrical schematic for the specific module  
connections.  
The following controls are available from the factory for field installation.  
Supply Fan Failure Input (Optional)  
The Fan Failure Switch can be connected to sense indoor fan operation:  
FFS (Fan Failure Switch) If air flow through the unit is not proven by the  
differential pressure switch connected to the RTOM (factory set point 0.07 “ w.c.)  
within 40 seconds nominally, the RTRM will shut off all mechanical operations,  
lock the system out, send a diagnostic to ICS, and the SERVICE output will flash.  
The system will remain locked out until a reset is initiated either manually or  
through ICS.  
Clogged Filter Switch (Optional)  
The unit mounted clogged filter switch monitors the pressure differential across  
the return air filters. It is mounted in the filter section and is connected to the  
RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure  
differential across the filters is at least 0.5" w.c. The contacts will automatically  
open when the pressure differential across the filters decreases to approximately  
0.4" w.c. The clogged filter output is energized when the supply fan is operating  
and the clogged filter switch has been closed for at least 2 minutes. The system  
will continue to operate regardless of the status of the filter switch.  
8
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
General Information  
Compressor Disable (CPR1/2)  
This input incorporates the low pressure control (LPC) of each refrigeration  
circuit and can be activated by opening a field supplied contact installed on the  
LTB.  
If this circuit is open before the compressor is started, the compressor will not be  
allowed to operate. Anytime this circuit is opened for 1 continuous second during  
compressor operation, the compressor for that circuit is immediately turned  
“Off. The compressor will not be allowed to restart for a minimum of 3 minutes  
should the contacts close.  
If four consecutive open conditions occur during the first three minutes of  
operation, the compressor for that circuit will be locked out, a diagnostic  
communicated to the remote panel (if installed), and a manual reset will be  
required to restart the compressor.  
Low Pressure Control  
ReliaTel Control  
When the LPC is opened for 1 continuous second, the compressor for that circuit  
is turned off immediately. The compressor will not be allowed to restart for a  
minimum of 3 minutes.  
If four consecutive open conditions occur during the first three minutes of  
operation, the compressor will be locked out, a diagnostic communicated to  
ICSTM if applicable, and a manual reset will be required to restart the  
compressor.  
High Pressure Control (Optional)  
ReliaTel Control  
The high pressure controls are wired in series between the compressor outputs  
on the RTRM and the compressor contactor coils. If the high pressure control  
switch opens, the RTRM senses a lack of current while calling for cooling and  
locks the compressor out.  
On dual circuit units, if the high pressure control opens, the compressor on the  
affected circuit is locked out. A manual reset for the affected circuit is required.  
Power Exhaust Control (Optional)  
The power exhaust fan is started whenever the position of the economizer  
dampers meets or exceed the power exhaust setpoint when the indoor fan is on.  
The setpoint panel is located in the return air section and is factory set at 25%.  
WC-IOM-7 • Packaged Heat Pump  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
General Information  
Lead/Lag Control (Dual Circuit Only)  
Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from  
the factory with the Lead/Lag control disabled. To activate the Lead/Lag function,  
simply cut the wire connected to J3-8 at the RTRM. When it is activated, each  
time the designated lead compressor is shut off due to the load being satisfied,  
the lead compressor or refrigeration circuit switches. When the RTRM is powered  
up, i.e. after a power failure, the control will default to the number one circuit  
compressor.  
Zone Sensor Module (ZSM) (BAYSENS007B)  
This electronic sensor features three system switch settings (Heat, Cool, and Off)  
and two fan settings (On and Auto). It is a manual changeover control with single  
setpoint. (Cooling Setpoint Only)  
Zone Sensor Module (ZSM) (BAYSENS009B)  
This electronic sensor features four system switch settings (Heat, Cool, Auto, and  
Off) and two fan settings (On and Auto). It is a manual or auto changeover control  
with dual setpoint capability. It can be used with a remote zone temperature  
sensor BAYSENS017B.  
Zone Sensor (BAYSENS011B)  
This electronic sensor features four system switch settings (Heat, Cool, Auto, and  
Off) and two fan settings (On and Auto) with four system status LEDs. It is a  
manual or auto changeover control with dual setpoint capability. It can be used  
with a remote zone temperature sensor BAYSENS017B.  
Programmable Zone Sensor - BAYSENS019B  
This 7 day programmable sensor features 2, 3 or 4 periods for Occupied or  
Unoccupied programming per day. If the power is interrupted, the program is  
retained in permanent memory. If power is off for an extended period of time,  
only the clock and day may have to be reset.  
The Zone Sensor allows selection of 2, 3 or 4 system modes (Heat, Cool, Auto,  
and Off), two fan modes (On and Auto). It has dual temperature selection with  
programmable start time capability.  
The occupied cooling set point ranges between 45 and 98 degrees Fahrenheit.  
The heating set point ranges between 43 and 96 degrees Fahrenheit.  
A liquid crystal display (LCD) displays zone temperature, temperature set points,  
day of the week, time, and operational mode symbols.  
The Option Menu is used to enable or disable applicable functions, i.e.; Morning  
Warm-up, Economizer minimum position override during unoccupied status,  
Fahrenheit or Centigrade, Supply air tempering, Remote zone temperature  
sensor, 12/24 hour time display, Smart fan, and Computed recovery.  
10  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Remote Zone Sensor (BAYSENS013C)  
This electronic sensor features remote zone sensing and timed override with  
override cancellation. It is used with a Trane Integrated ComfortTM building  
management system.  
Remote Zone Sensor (BAYSENS014C)  
This electronic sensor features single setpoint capability and timed override with  
override cancellation. It is used with a Trane Integrated ComfortTM building  
management system.  
Remote Zone Sensor (BAYSENS016A)  
This bullet type temperature sensor can be used for; outside air (ambient)  
sensing, return air temperature sensing, supply air temperature sensing, remote  
temperature sensing (uncovered. Wiring procedures vary according to the  
particular application and equipment involved. Refer to the units wiring  
diagrams for proper connections.  
Remote Zone Sensor (BAYSENS017B)  
This electronic sensor can be used with BAYSENS006B, 008B, 010B, 019B Remote  
Panels. When this sensor is wired to a BAYSENS019B Remote Panel, wiring must  
be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the  
specific Remote Panel for wiring details.  
High Temperature Sensor (BAYFRST001A)  
This sensor connects to the RTRM Emergency Stop Input on the LTB and  
provides high limit “shutdown” of the unit. The sensor is used to detect high  
temperatures due to fire in the air conditioning or ventilation ducts. The sensor is  
designed to mount directly to the sheet metal duct. Each kit contains two  
sensors. The return air duct sensor (X1310004001) is set to open at 135°F. The  
supply air duct sensor (X1310004002) is set to open at 240°F. The control can be  
reset after the temperature has been lowered approximately 25°F below the  
cutout setpoint.  
Evaporator Frost Control  
This input incorporates the Frostat™ control (FOS) mounted in the indoor coil  
and can be activated by closing a field supplied contact installed in parallel with  
the FOS.  
If this circuit is open before the compressor is started, the compressor will not be  
allowed to operate. Anytime this circuit is opened for 5 continuous seconds  
during compressor operation, the compressor for that circuit is immediately  
turned “Off. The compressor will not be allowed to restart for a minimum of 3  
minutes should the FOS close.  
WC-IOM-7 • Packaged Heat Pump  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Smoke Detector Sensor (Optional)  
This sensor is only applicable on units equipped with a RTOM. It provides high  
limit “shutdown” of the unit and requires a manual reset. The sensor is used to  
detect smoke due to fire in the air conditioning or ventilation ducts.  
Important: The supply and return air smoke detectors are designed to shut off the  
unit if smoke is sensed in the supply air stream or return air stream. This function  
is performed by sampling the airflow entering the unit at the return air opening.  
Follow the instructions provided below to assure that the airflow through the unit  
is sufficient for adequate sampling. Failure to follow these instructions will  
prevent the smoke detectors from performing it's design function. Important:  
Airflow through the unit is affected by the amount of dirt and debris accumulated  
on the indoor coil and filters. To insure that airflow through the unit is adequate  
for proper sampling by the return air smoke detector, complete adherence to the  
maintenance procedures, including recommended intervals between filter  
changes, and coil cleaning is required.  
Note: Important! Periodic checks and maintenance procedures must be  
performed on the smoke detector to insure that it will function properly.  
For detailed instructions concerning these checks and procedures, refer to  
the appropriate section(s) of the smoke detector Installation and  
Maintenance Instructions provided with the literature package for this  
unit.  
In order for the supply air smoke detector or return air smoke detector to  
properly sense smoke in the supply air stream or return air stream, the air  
velocity entering the smoke detector unit must be between 500 and 4000 feet per  
minute. Equipment covered in this manual will develop an airflow velocity that  
falls within these limits over the entire airflow range specified in the evaporator  
fan performance tables.  
Unit Inspection  
As soon as the unit arrives at the job site:  
Verify that the nameplate data matches the data on the sales order and bill of  
lading (including electrical data).  
Verify that the power supply complies with the unit nameplate specifications.  
Visually inspect the exterior of the unit, including the roof, for signs of  
shipping damage.  
Visually inspect the internal components for shipping damage as soon as  
possible after delivery and before it is stored. Do not walk on the sheet metal  
base pans.  
If concealed damage is discovered, notify the carriers terminal of damage  
immediately by phone and by mail. Concealed damage must be reported  
within 15 days.  
Request an immediate joint inspection of the damage by the carrier and the  
consignee. Do not remove damaged material from the receiving location.  
12  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Information  
Take photos of the damage, if possible. The owner must provide reasonable  
evidence that the damage did not occur after delivery.  
Notify the appropriate sales representative before installing or repairing a  
damaged unit.  
ƽWARNING  
Fiberglass Wool  
Product contains fiberglass wool. Disturbing the insulation in this product  
during installation, maintenance or repair will expose you to airborne particles of  
glass wool fibers and ceramic fibers known to the state of California to cause  
cancer through inhalation. Glass wool fibers may also cause respiratory, skin or  
eye irritation.  
Precautionary Measures  
Avoid breathing fiberglass dust.  
Use a NIOSH approved dust/mist respirator.  
Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting  
clothing, gloves, and eye protection.  
Wash clothes separately from other clothing: rinse washer  
thoroughly.  
Operations such as sawing, blowing, tear-out, and spraying may  
generate fiber concentrations requiring additional respiratory  
protection. Use the appropriate NIOSH approved respiration in  
these situations.  
First Aid Measures  
Eye Contact - Flush eyes with water to remove dust. If symptoms  
persist, seek medical attention.  
Skin Contact - Wash affected areas gently with soap and warm  
water after handling.  
Storage  
Take precautions to prevent condensate from forming inside the units electrical  
compartments and motors if:  
1. the unit is stored before it is installed; or,  
2. the unit is set on the roof curb, and temporary heat is provided in the  
building. Isolate all side panel service entrances and base pan openings (e.g.,  
conduit holes, S/A and R/A openings, and flue openings) from the ambient air  
until the unit is ready for start-up.  
Note: Do not use the units heater for temporary heat without first completing  
the start-up procedure detailed under “Starting the Unit.  
WC-IOM-7 • Packaged Heat Pump  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Information  
The manufacturer will not assume any responsibility for equipment damage  
resulting from condensate accumulation on the units electrical and/or  
mechanical components.  
Unit Clearances  
Figure 1 illustrates the minimum operating and service clearances for either a  
single or multiple unit installation. These clearances are the minimum distances  
necessary to assure adequate serviceability, cataloged unit capacity, and peak  
operating efficiency.  
Providing less than the recommended clearances may result in condenser coil  
starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation  
of hot condenser air.  
14  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Unit Dimensions  
Figure 1. Typical Installation Clearances for Single & Multiple Unit Applications  
WC-IOM-7 • Packaged Heat Pump  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Unit Dimensions  
Figure 2. Unit Dimensional Data 12 1/2 Ton, 15 Ton  
Figure 3. Roof Curb Dimensional Data 12 1/2 Ton, 15 Ton  
16  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Dimensions  
Figure 4. Unit Dimensional Data 20 Ton  
Figure 5. Roofcurb Dimensional Data 20 Ton  
WC-IOM-7 • Packaged Heat Pump  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Dimensions  
Figure 6. Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton  
Figure 7. Horizontal Duct Dimensional Data 20 Ton  
18  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Dimensions  
ƽWARNING  
Heavy Objects!  
Do not use cables (chains or slings) except as shown. Each of the cables (chains  
or slings) used to lift the unit must be capable of supporting the entire weight of  
the unit. Lifting cables (chains or slings) may not be of the same length. Adjust  
as necessary for even unit lift. Other lifting arrangements may cause equipment  
or property-only damage. Failure to properly lift unit may result in death or  
serious injury. See details below.  
ƽWARNING  
Improper Unit Lift!  
Test lift unit approximately 24 inches to verify proper center of gravity lift point.  
To avoid dropping of unit, reposition lifting point if unit is not level. Failure to  
properly lift unit could result in death or serious injury or possible equipment or  
property-only damage.  
Table 1.  
Typical weights and point loading data  
Center of  
Corner Weights (lbs.) Gravity (in.)  
Unit  
Net  
A
B
C
D
Length Width  
Description Weight  
WC*150B  
WC*155B  
WC*180B  
WC*200B  
WC*240B  
1375  
1412  
1412  
1916  
1916  
465 344 231 311  
547 638 231 343  
547 638 231 343  
640 497 340 438  
640 497 340 438  
46  
43  
43  
51  
51  
29  
27  
27  
34  
34  
Note: Corner weights are given for information only. Unit is to be supported continuously by  
a curb or equivalient frame support.  
Figure 8. Rigging and center of gravity data  
WC-IOM-7 • Packaged Heat Pump  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Unit Dimensions  
Rigging  
Refer to Figure 8 and Table 1 for typical unit operating weights riffing before  
proceeding.  
1. Remove the shipping crate from around the unit. Do not remove the crating  
from the top of the unit.  
2. Rig the unit as shown in Figure 8. Attach adequate strength lifting slings to all  
four lifting brackets in the unit base rail. Do not use cables, chains, or slings  
except as shown.  
3. Install a lifting bar, as shown in Figure 8, to protect the unit and to facilitate a  
uniform lift. The minimum distance between the lifting hook and the top of  
the unit should be 7 feet.  
4. Test-lift the unit to ensure it is properly rigged and balanced, make any  
necessary rigging adjustments.  
5. Lift the unit and position it into place.  
6. Downflow units; align the base rail of the unit with the curb rail while  
lowering the unit onto the curb. Make sure that the gasket on the curb is not  
damaged while positioning the unit.  
20  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Foundation  
Horizontal Units  
If the unit is installed at ground level, elevate it above the snow line. Provide  
concrete footings at each support location with a “full perimeter” support  
structure or a slab foundation for support. Refer to Table 1 on page 19 for the  
units operating and point loading weights when constructing a footing  
foundation.  
If anchoring is required, anchor the unit to the slab using hold down bolts or  
isolators. Isolators should be installed to minimize the transmission of vibrations  
into the building.  
For rooftop applications, ensure the roof is strong enough to support the  
combined unit and support structural weight. Refer to Table 1 on page 19 for the  
unit operating weights. If anchoring is required, anchor the unit to the roof with  
hold-down bolts or isolators.  
Check with a roofing contractor for proper waterproofing procedures.  
Ductwork  
Elbows with turning vanes or splitters are recommended to minimize air noise  
due to turbulence and to reduce static pressure.  
When attaching the ductwork to the unit, provide a water- tight flexible connector  
at the unit to prevent operating sounds from transmitting through the ductwork.  
All outdoor ductwork between the unit and the structure should be weather  
proofed after installation is completed.  
Note: For sound consideration, cut only the holes in the roof deck for the  
ductwork penetrations. Do not cut out the entire roof deck within the curb  
perimeter.  
If a Curb Accessory Kit is not used:  
1. The ductwork can be attached directly to the factory-provided flanges around  
the units supply and return air openings. Be sure to use flexible duct  
connections at the unit.  
2. For “built-up” curbs supplied by others, gaskets must be installed around the  
curb perimeter flange and the supply and return air opening flanges.  
General Unit Requirements  
The checklist listed below is a summary of the steps required to successfully  
install a commercial unit. This checklist is intended to acquaint the installing  
WC-IOM-7 • Packaged Heat Pump  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation  
personnel with what is required in the installation process. It does not replace the  
detailed instructions called out in the applicable sections of this manual.  
Check the unit for shipping damage and material shortage; file a freight claim  
and notify appropriate sales representative.  
Verify correct model, options and voltage from nameplate.  
Verify that the installation location of the unit will provide the required  
clearance for proper operation.  
Assemble and install the roof curb (if applicable). Refer to the latest edition of  
the curb installers guide that ships with each curb kit.  
Fabricate and install ductwork; secure ductwork to curb.  
Rigging the unit.  
Set the unit onto the curb; check for levelness.  
Ensure unit-to-curb seal is tight and without buckles or cracks.  
Install and connect a condensate drain line to the evaporator drain  
connection.  
Factory Installed Economizer  
Ensure the economizer has been pulled out into the operating position. Refer  
to the economizer installers guide for proper position and setup.  
Install all access panels.  
Main Electrical Power Requirements  
Verify that the power supply complies with the unit nameplate specifications.  
Inspect all control panel components; tighten any loose connections.  
Connect properly sized and protected power supply wiring to a field-  
supplied/installed disconnect switch and to the main power terminal block  
(HTB1) in the unit control panel.  
Install proper grounding wires to an earth ground.  
Note: All field-installed wiring must comply with NEC and applicable local  
codes.  
Electric Heat Requirements  
Verify that the power supply complies with the electric heater specifications  
on the unit and heater nameplate.  
Inspect the heater junction box and control panel; tighten any loose  
connections.  
Check electric heat circuits for continuity.  
Low Voltage Wiring (AC & DC) Requirements  
Install the zone thermostat, with or without switching subbase.  
22  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
Connect properly sized control wiring to the proper termination points  
between the zone thermostat and the unit control panel.  
Condensate Drain Configuration  
An evaporator condensate drain connection is provided on each unit. Refer to  
Unit Dimensions for the appropriate drain location.  
A condensate trap must be installed at the unit due to the drain connection being  
on the “negative pressure” side of the fan. Install the P-Trap using the guidelines  
in Figure 9.  
A condensate drain line must be connected to the P-Trap. Pitch the drain lines at  
least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow.  
Do not allow the horizontal run to sag causing a possible double-trap condition  
which could result in condensate backup due to “air lock.  
Figure 9. Condensate Trap Installation  
Filter Installation  
Each unit ships with 2 inch filters installed. The quantity of filters is determined  
by unit size. Access to the filters is obtained by removing the indoor fan access  
panel.  
Refer to the unit Service Facts (shipped with each unit) for filter requirements.  
Note: Do not operate the unit without filters.  
Field Installed Power Wiring  
An overall dimensional layout for the standard field installed wiring entrance into  
the unit is illustrated in Unit Dimensions. To insure that the units supply power  
wiring is properly sized and installed, follow the guidelines outlined below.  
WC-IOM-7 • Packaged Heat Pump  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
Note: All field installed wiring must conform to NEC guidelines as well as State  
and Local codes.  
Verify that the power supply available is compatible with the units nameplate  
ratings. The available supply power must be within 10% of the rated voltage  
stamped on the nameplate. Use only copper conductors to connect the power  
supply to the unit.  
NOTICE  
Use Copper Conductors Only!  
Unit terminals are not designed to accept other types of conductors. Failure to  
use copper conductors may result in equipment damage. Failure to do so may  
cause damage to the equipment.  
Note: If the unit is not equipped with an optional factory installed nonfused  
disconnect switch or circuit breaker, a field supplied disconnect switch  
must be installed at or near the unit in accordance with the National  
Electrical Code (NEC latest edition).  
Main Unit Power  
Standard Wiring  
The electrical service must be protected from over current and short circuit  
conditions in accordance with NEC requirements. Protection devices must be  
sized according to the electrical data on the nameplate.  
1. If the unit is not equipped with an optional factory installed nonfused  
disconnect switch or circuit breaker, a field supplied disconnect switch must  
be installed at or near the unit in accordance with the National Electrical Code  
(NEC latest edition).  
2. Location of the applicable electrical service entrance is illustrated in Unit  
Dimensions. Complete the units power wiring connections onto either; the  
main terminal block HTB1 inside the unit control panel, the factory mounted  
nonfused disconnect switch (UCD) or circuit breaker (UCB), or the electric  
heat terminal block. Refer to the customer connection diagram that shipped  
with the unit for specific termination points.  
3. Provide proper grounding for the unit in accordance with local and national  
codes.  
Optional TBUE Wiring  
(Through the Base Electrical Option)  
1. Location of the applicable electrical service is illustrated in the following  
illustration. Refer to the customer connection diagram that is shipped with  
the unit for specific termination points. The termination points, depending on  
the customer option selected would be a factory mounted nonfused  
disconnect switch (UDC) or circuit breaker (UCB).  
24  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
2. Provide proper grounding for the unit in accordance with local and national  
codes.  
Figure 10.  
Field Installed Control Wiring  
An overall layout of the various control options available with the required  
number of conductors for each control device is illustrated in Figure 8.  
Note: All field wiring must conform to NEC guidelines as well as state and local  
codes.  
Control Power Transformer  
The 24 volt control power transformers are to be used only with the accessories  
called out in this manual. Transformers rated greater than 50 VA are equipped  
with internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the  
unit before attempting to reset it.  
ƽWARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing.  
Follow proper lockout/tagout procedures to ensure the power can not be  
inadvertently energized. Failure to disconnect power before servicing could  
result in death or serious injury.  
WC-IOM-7 • Packaged Heat Pump  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
The transformer is located in the control panel. The circuit breaker is located on  
the left side of the transformer and can be reset by pressing in on the black reset  
button.  
Controls using 24 VAC  
Before installing any connecting wiring, refer to Unit Dimensions for the  
electrical access locations provided on the unit and Table 2 for AC conductor  
sizing guidelines, and;  
1. Use copper conductors unless otherwise specified.  
2. Ensure that the AC control wiring between the controls and the units  
termination point does not exceed three (3) ohms/conductor for the length of  
the run.  
Note: Resistance in excess of 3 ohms per conductor may cause component  
failure due to insufficient AC voltage supply.  
3. Be sure to check all loads and conductors for grounds, shorts, and mis-  
wiring.  
4. Do not run the AC low voltage wiring in the same conduit with the high  
voltage power wiring.  
5. Route low voltage wiring per illustrations on Figure 11.  
Table 2.  
Electromechanical Thermostat 24V AC conductors with ReliaTel™  
Distance from Unit to Control Recommended Wire Size  
000 - 460 feet  
000 - 140 m  
18 gauge  
.75 mm2  
16 gauge  
1.3 mm2  
14 gauge  
2.0 mm2  
461 - 732 feet  
141 - 223 m  
733 - 1000 feet  
224 - 305 m  
Controls using DC Analog Input/Outputs (Standard Low Voltage  
Multiconductor Wire)  
Before installing any connecting wiring between the unit and components  
utilizing a DC analog input\output signal, refer to Unit Dimensions for the  
electrical access locations provided on the unit.  
1. Table 3 lists the conductor sizing guidelines that must be followed when  
interconnecting the DC binary output devices and the system components  
utilizing a DC analog input\output signal to the unit.  
26  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in  
the accuracy of the controls.  
2. Ensure that the wiring between controls and the units termination point does  
not exceed two and a half (2.5) ohms/conductor for the length of the run.  
3. Do not run the electrical wires transporting DC signals in or around conduit  
housing high voltage wires.  
Table 3.  
DC Conductors Zone Sensor Module wiring  
Distance from Unit to Control Recommended Wire Size  
0 - 150 feet  
0 - 45.7 m  
22 gauge  
.33 mm2  
20 gauge  
.50 mm2  
18 gauge  
.75 mm2  
16 gauge  
1.3 mm2  
14 gauge  
2.0 mm2  
151 - 240 feet  
46 - 73.1 m  
241 -385 feet  
73.5 - 117.3 m  
386 - 610 feet  
117.7 - 185.9 m  
611 - 970 feet  
186.2 - 295.7 m  
Figure 11. Reliatel conventional thermostat field wiring diagram  
RTRM  
WC-IOM-7 • Packaged Heat Pump  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation  
Smoke Detector Customer Low Voltage Wiring  
When interlocking System Sensor smoke detectors together, all of the detectors  
must be powered from the same power supply. If multiple smoke detectors are  
required, all detectors must be disconnected from the HVAC unit power supply  
and connected together from another single source supply.  
Note: Do not interconnect smoke detectors together that have separate power  
supplies. Do not exceed ten smoke detectors on one power supply.  
Note: Multiple System Sensor smoke detectors are connected together using  
terminals 1 and 12 on each detector.  
If you have supply and return smoke detectors in all HVAC units, you can connect  
a maximum of 5 HVAC units (10 detectors) up to one power supply. See the  
following field wiring example.  
If you have more than 5 HVAC units, you can connect all the supply detectors  
together on one power supply (up to 10 HVAC units), and all the return detectors  
together (up to 10 HVAC units) on another power supply. See the following field  
wiring example.  
Figure 12. Smoke detector wiring  
Up to 5 HVAC units  
More than 5 HVAC units  
28  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Figure 13. Typical field wiring diagrams for optional controls (ReliaTel™ only)  
WC-IOM-7 • Packaged Heat Pump  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Space Temperature Averaging  
Space temperature averaging is accomplished by wiring a number of remote  
sensors in a series/parallel circuit.  
Using the BAYSENS016* or BAYSENS017*, at least four sensors are required to  
accomplish space temperature averaging. Example #1 illustrates two series  
circuits with two sensors in each circiut wired in parallel. The square of any  
number of remote sensors is required. Example #2 illustrates three sensors  
squared in a series/parallel circuit. Using BAYSENS032*, two sensors are  
required to accomplish space temperature averaging. Example #3 illustrates the  
circuit required for this senor. Table 4 lists the temperature versus resistance  
coefficient for all sensing.  
Figure 14.  
30  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Table 4.  
Temperature vs. Resistance  
Temperature  
Degrees F° Degrees C° Nominal Resistance  
-20°  
-15°  
-10°  
-5°  
-28.9°  
-26.1°  
-23.3°  
-20.6°  
-17.8°  
-15.0°  
-12.2°  
-9.4°  
-6.7°  
-3.8°  
-1.1°  
1.7°  
170.1 K - Ohms  
143.5 K - Ohms  
121.4 K - Ohms  
103.0 K - Ohms  
87.56 K - Ohms  
74.65 K - Ohms  
63.80 K - Ohms  
54.66 K - Ohms  
46.94 K - Ohms  
40.40 K - Ohms  
34.85 K - Ohms  
30.18 K - Ohms  
26.22 K - Ohms  
22.85 K - Ohms  
19.96 K - Ohms  
17.47 K - Ohms  
15.33 K - Ohms  
13.49 K - Ohms  
11.89 K - Ohms  
10.50 K - Ohms  
9.297 K - Ohms  
8.247 K - Ohms  
7.330 K - Ohms  
6.528 K - Ohms  
5.824 K - Ohms  
0°  
5°  
10°  
15°  
20°  
25°  
30°  
35°  
40°  
45°  
50°  
55°  
60°  
65°  
70°  
75°  
80°  
85°  
90°  
95°  
100°  
4.4°  
7.2°  
10.0°  
12.8°  
15.6°  
18.3°  
21.1°  
23.9°  
26.7°  
29.4°  
32.2°  
35.0°  
37.8°  
Use the checklist provided below in conjunction with the “General Unit  
Requirements” checklist to ensure that the unit is properly installed and ready for  
operation.  
ƽWARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing.  
Follow proper lockout/tagout procedures to ensure the power can not be  
inadvertently energized. Failure to disconnect power before servicing could  
result in death or serious injury.  
Check all electrical connections for tightness and “point of termination”  
accuracy.  
Verify that the condenser airflow will be unobstructed.  
Verify that the condenser fan and indoor blower turn freely without rubbing  
and are properly tightened on the shafts.  
WC-IOM-7 • Packaged Heat Pump  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Check the supply fan belts for proper tension and the fan bearings for  
sufficient lubrication. If the belts require adjustment, or if the bearings need  
lubricating, refer to the maintenance section of this manual for instructions.  
Verify that a condensate trap is installed and the piping is properly sized and  
pitched.  
Verify that the correct size and number of filters are in place.  
Inspect the interior of the unit for tools and debris and install all panels in  
preparation for starting the unit.  
Voltage Imbalance  
Three phase electrical power to the unit must meet stringent requirements for  
the unit to operate properly. Measure each leg (phase-to-phase) of the power  
supply. Each reading must fall within the utilization range stamped on the unit  
nameplate. If any of the readings do not fall within the proper tolerances, notify  
the power company to correct this situation before operating the unit.  
Excessive three phase voltage imbalance between phases will cause motors to  
overheat and eventually fail. The maximum allowable voltage imbalance is 2%.  
Measure and record the voltage between phases 1, 2, and 3 and calculate the  
amount of imbalance as follows:  
% Voltage Imbalance =  
AV VD  
AV  
-----------------------  
100  
where Average Voltage (AV);  
Volt1 + Volt2 + Volt3  
----------------------------------------------------------------  
AV=  
3
V1, V2, V3 = Line Voltage Readings  
VD = Line Voltage reading that deviates the farthest from the average voltage.  
Example: If the voltage readings of the supply power measured 221, 230, and 227,  
the average volts would be:  
221 + 230 + 227  
---------------------------------------------- = 2.2percent  
3
VD (reading farthest from average) = 221  
The percentage of Imbalance equals:  
226 221  
----------------------------  
100  
= 2.2percent  
226  
The 2.2% imbalance in this example exceeds the maximum allowable imbalance  
of 2.0%. This much imbalance between phases can equal as much as a 20%  
current imbalance with a resulting increase in motor winding temperatures that  
will decrease motor life. If the voltage imbalance is over 2%, notify the proper  
agencies to correct the voltage problem before operating this equipment.  
32  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
Electrical Phasing  
(Three Phase Motors)  
The compressor motor(s) and the supply fan motor are internally connected for  
the proper rotation when the incoming power supply is phased as A, B, C.  
Proper electrical supply phasing can be quickly determined and corrected before  
starting the unit by using an instrument such as an Associated Research Model  
45 Phase Sequence Indicator and following the steps below:  
Turn the field supplied disconnect switch that provides power to the main  
power terminal block or to the “Line” side of the optional factory mounted  
disconnect switch to the “Off” position.  
Connect the phase sequence indicator leads to the terminal block or to the  
“Line” side of the optional factory mounted disconnect switch as follows;  
Black (phase A) to L1  
Red (phase B) to L2  
Yellow (phase C) toL3  
Close the field supplied main power disconnect switch or circuit protector  
switch that provides the supply power to the unit.  
ƽWARNING  
Live Electrical Components!  
During installation, testing, servicing and troubleshooting of this product, it may  
be necessary to work with live electrical components. Have a qualified licensed  
electrician or other individual who has been properly trained in handling live  
electrical components perform these tasks. Failure to follow all electrical safety  
precautions when exposed to live electrical components could result in death or  
serious injury.  
To prevent injury or death from electrocution, it is the responsibility of the  
technician to recognize this hazard and use extreme care when performing  
service procedures with the electrical power energized.  
Observe the ABC and CBA phase indicator lights on the face of the  
sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA  
indicator light glows, open the disconnect switch or circuit protection switch  
and reverse any two power wires.  
Restore the main electrical power and recheck the phasing. If the phasing is  
correct, open the disconnect switch or circuit protection switch and remove  
the phase sequence indicator.  
Compressor Crankcase Heaters (Optional)  
Each compressor can be equipped with a crankcase heater. The proper operation  
of the crankcase heater is important to maintain an elevated compressor oil  
temperature during the “Off” cycle to reduce oil foaming during compressor  
WC-IOM-7 • Packaged Heat Pump  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
starts. Oil foaming occurs when refrigerant condenses in the compressor and  
mixes with the oil. In lower ambient conditions, refrigerant migration to the  
compressor could increase.  
When the compressor starts, the sudden reduction in crankcase pressure causes  
the liquid refrigerant to boil rapidly causing the oil to foam. This condition could  
damage compressor bearings due to reduced lubrication and could cause  
compressor mechanical failures.  
Before starting the unit in the “Cooling” mode, set the system switch to the “Off”  
position and turn the main power disconnect to the “On” position and allow the  
crankcase heater to operate a minimum of 8 hours.  
Before closing the main power disconnect switch, insure that the “System”  
selection switch is in the “Off” position and the “Fan” selection switch is in the  
Auto” position.  
Close the main power disconnect switch and the unit mounted disconnect switch,  
if applicable.  
ƽWARNING  
Live Electrical Components!  
During installation, testing, servicing and troubleshooting of this product, it may  
be necessary to work with live electrical components. Have a qualified licensed  
electrician or other individual who has been properly trained in handling live  
electrical components perform these tasks. Failure to follow all electrical safety  
precautions when exposed to live electrical components could result in death or  
serious injury.  
To prevent injury or death from electrocution, it is the responsibility of the  
technician to recognize this hazard and use extreme care when performing  
service procedures with the electrical power energized.  
ReliaTel Controls  
Upon power initialization, the RTRM performs self-diagnostic checks to insure  
that all internal controls are functional. It also checks the configuration  
parameters against the components connected to the system. The Liteport LED  
located on the RTRM module is turned “On” within one second of power-up if  
internal operation is okay.  
Use one of the following “Test” procedure to bypass some time delays and to  
start the unit at the control panel. Each step of unit operation can be activated  
individually by temporarily shorting across the “Test” terminals for two to three  
seconds. The Liteport LED located on the RTRM module will blink when the test  
mode has been initiated. The unit can be left in any “Test” step for up to one hour  
before it will automatically terminate, or it can be terminated by opening the  
main power disconnect switch. Once the test mode has been terminated, the  
Liteport LED will glow continuously and the unit will revert to the “System”  
control.  
34  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Pre-Start  
Test Modes  
There are three methods in which the “Test” mode can be cycled at LTB-Test 1  
and LTB-Test 2.  
1. Step Test Mode - This method initiates the different components of the unit,  
one at a time, by temporarily shorting across the two test terminals for two to  
three seconds.  
For the initial start-up of the unit, this method allows the technician to cycle a  
component “On” and have up to one hour to complete the check.  
2. Resistance Test Mode - This method can be used for start-up providing a  
decade box for variable resistance outputs is available. This method initiates  
the different components of the unit, one at a time, when a specific resistance  
value is placed across the two test terminals. The unit will remain in the  
specific test mode for approximately one hour even though the resistance is  
left on the test terminals.  
3. Auto Test Mode - This method is not recommended for start-up due to the  
short timing between individual component steps. This method initiates the  
different components of the unit, one at a time, when a jumper is installed  
across the test terminals. The unit will start the first test step and change to  
the next step every 30 seconds. At the end of the test mode, control of the  
unit will automatically revert to the applied "System" control method.  
For unit test steps, test modes, and step resistance values to cycle the various  
components, refer to Table 5.  
Table 5.  
Service test guide for component operation  
TEST  
STEP  
Econ  
(Note 2)  
MODE  
Fan  
Comp 1  
Comp 2  
Heat 1 Heat 2 Ohms  
1
Fan  
On  
Minimum  
Off  
Off  
Off  
2.2K  
Position Off  
Setpoint 0%  
Minimum  
Ventilation  
On  
Selectable  
Open  
Off  
Off  
Off  
Off  
Off  
2
3
Economizer  
Test Open  
On  
On  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
3.3K  
4.7K  
6.8K  
Cool Stage 1  
Minimum  
Position  
(Note 1)  
On  
4 (Note 3) Cool Stage 2  
Minimum  
Position  
(Note 1)  
On  
(Note 1)  
On  
5 (Note 3) Reheat  
6 (Note 3) Heat Stage 1  
7 (Note 3) Heat Stage 2  
Notes:  
On  
On  
On  
Minimum  
Minimum  
Minimum  
On  
Off  
Off  
On  
Off  
Off  
Off  
On  
On  
Off  
Off  
On  
33K  
10K  
15K  
1 - The condenser fans will operate any time a compressor is "On" providing the outdoor air temperatures are within the operating values.  
2 - The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.  
3 - Steps for optional accessories and non-applicable modes in unit will be skipped.  
WC-IOM-7 • Packaged Heat Pump  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Pre-Start  
Verifying Proper Air Flow  
(Units with Belt Drive Indoor Fan)  
Much of the systems performance and reliability is closely associated with, and  
dependent upon having the proper airflow supplied both to the space that is  
being conditioned and across the evaporator coil.  
The indoor fan speed is changed by opening or closing the adjustable motor  
sheave.  
Before starting the SERVICE TEST, set the minimum position setpoint for the  
economizer to 0 percent using the setpoint potentiometer located on the  
Economizer Control (ECA), if applicable.  
ReliaTel Control  
Using the Service Test Guide in Table 5, momentarily jump across the Test 1 &  
Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test.  
Once the supply fan has started, check for proper rotation. The direction of  
rotation is indicated by an arrow on the fan housing.  
With the fan operating properly, determine the total system airflow (CFM) by;  
1. Measuring the actual RPM,  
2. Measure the amperage at the supply fan contactor and compare it with the  
full load amp (FLA) rating stamped on the motor nameplate.  
a. Calculate the theoretical BHP  
Actual Motor Amps X Motor HP  
Motor Nameplate Amps  
b. Using the fan performance tables in the unit Service Facts, plot the actual  
RPM (step 1) and the BHP (step 2a) to obtain the operating CFM.  
3. If the required CFM is too low, (external static pressure is high causing motor  
HP output to be below table value),  
a. Relieve supply and/or return duct static.  
b. Change indoor fan speed and repeat steps 1 and 2.  
To Increase Fan RPM; Loosen the pulley adjustment set screw and turn  
sheave clockwise.  
To Decrease Fan RPM; Loosen the pulley adjustment set screw and turn  
sheave counterclockwise.  
If the required CFM is too high, (external static pressure is low causing motor  
HP output to be above table value), change indoor fan speed and repeat steps  
1 and 2.  
To stop the SERVICE TEST, turn the main power disconnect switch to the  
“Off” position or proceed to the next component start-up procedure. Remove  
electro mechanical test mode connections (if applicable).  
36  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Pre-Start  
Return Air Smoke Detector  
The return air smoke detector is designed to shut off the unit if smoke is sensed  
in the return air stream. Sampling the airflow entering the unit at the return air  
opening performs this function.  
In order for the smoke detector to properly sense smoke in the return air stream,  
the air velocity entering the unit must be between 500 and 4000 feet per minute.  
Equipment covered in this manual will develop an airflow velocity that falls  
within these limits over the entire airflow range specified in the evaporator fan  
performance tables.  
WC-IOM-7 • Packaged Heat Pump  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start Up  
Economizer Start-Up  
ReliaTel Control  
Using the Service Test Guide in Table 5, p. 35, momentarily jump across the Test  
1 & Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test.  
1. Set the minimum position setpoint for the economizer to the required  
percentage of minimum ventilation using the setpoint potentiometer located  
on the Economizer Control (ECA).  
The economizer will drive to its minimum position setpoint, exhaust fans (if  
applicable) may start at random, and the supply fan will start when the  
SERVICE TEST is initiated.  
ƽWARNING  
Rotating Components!  
During installation, testing, servicing and troubleshooting of this product it may  
be necessary to measure the speed of rotating components. Have a qualified or  
licensed service individual who has been properly trained in handling exposed  
rotating components, perform these tasks. Failure to follow all safety  
precautions when exposed to rotating components could result in death or  
serious injury.  
The Exhaust Fan will start anytime the economizer damper position is equal to or  
greater than the exhaust fan setpoint.  
2. Verify that the dampers stroked to the minimum position.  
3. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional  
time if continuing from previous component start-up or until the desired  
start-up component Test is started.  
4. Verify that the dampers stroked to the full open position.  
5. To stop the SERVICE TEST, turn the main power disconnect switch to the  
“Off” position or proceed to the next component start-up procedure. Remove  
electro mechanical test mode connections (if applicable).  
Compressor Start-Up  
1. Attach a set of service gauges onto the suction and discharge gauge ports for  
each circuit. Refer to the refrigerant circuit illustration in the Service Facts.  
Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST  
start-up procedure for each compressor circuit.  
Momentarily jump across the Test 1 & Test 2 terminals on LTB1 one  
additional time if continuing from previous component start-up or until the  
desired start-up component Test is started.  
WC-IOM-7 • Packaged Heat Pump  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Start Up  
Scroll Compressors  
a. Once each compressor has started, verify that the rotation is correct. If a  
scroll compressor is rotating backwards, it will not pump and a loud  
rattling sound can be observed.  
b. If the electrical phasing is correct, before condemning a compressor,  
interchange any two leads (at the compressor Terminal block) to check the  
internal phasing. Refer to the following illustration for the compressor  
terminal/phase identification. If the compressor runs backward for an  
extended period (15 to 30 minutes), the motor winding can overheat and  
cause the motor winding thermostat to open.  
Figure 15.  
c. Check the compressor oil levels. The oil level in each compressor sight  
glass should be 1/2 to 3/4 full when they are “Off.  
Note: The scroll compressor uses Trane OIL-42 without substitution. The  
appropriate oil charge for a 9 and 10 Ton scroll compressor is 8 pints. For a  
14 and 15 Ton scroll compressor, use 14 pints.  
2. After the compressor and condenser fan have started and operated for  
approximately 30 minutes, observe the operating pressures. Compare the  
operating pressures to the operating pressure curve in the Service Facts.  
3. Check system superheat. Follow the instruction listed on the superheat  
charging curve in the Service Facts.  
Superheat should be within 5 F of the superheat chart value.  
4. Repeat steps 1 through 4 for each refrigerant circuit.  
5. To stop the SERVICE TEST, turn the main power disconnect switch to the  
“Off” position or proceed to the next component start-up procedure. Remove  
electro mechanical test mode connections (if applicable).  
Heating Start-Up  
1. Clamp an amp meter around one of 1st stage heater power wires at the  
heater contactor.  
WC-IOM-7 • Packaged Heat Pump  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Start Up  
2. ReliaTel Control  
Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST  
start-up procedure for each compressor circuit.  
Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional  
time if continuing from previous component start-up or until the desired  
start-up component Test is started.  
3. Verify that the heater stage is operating properly.  
4. Clamp an amp meter around one of 2nd stage heater power wires at the  
heater contactor (if applicable).  
5. ReliaTel Control  
Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST  
start-up procedure for each compressor circuit. Momentarily jump across the  
Test 1 & Test 2 terminals on LTB one additional time if continuing from  
previous component start-up or until the desired start-up component Test is  
started.  
6. Verify that the heater stage is operating properly  
7. To stop the SERVICE TEST, turn the main power disconnect switch to the  
“Off” position or proceed to the next component start-up procedure.  
Final System Setup  
After completing all of the pre-start and start-up procedures outlined in the  
previous sections (i.e., operating the unit in each of its Modes through all  
available stages of cooling & heating), perform these final checks before leaving  
the unit:  
Program the Night Setback (NSB) panel (if applicable) for proper unoccupied  
operation. Refer to the programming instructions for the specific panel.  
Verify that the Remote panel “System” selection switch, “Fan” selection  
switch, and “Zone Temperature” settings for automatic operation are correct.  
Inspect the unit for misplaced tools, hardware, and debris.  
Verify that all exterior panels including the control panel doors and  
condenser grilles are secured in place.  
Close the main disconnect switch or circuit protector switch that provides the  
supply power to the units terminal block or the unit mounted disconnect  
switch.  
40  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
ƽWARNING  
Rotating Components!  
During installation, testing, servicing and troubleshooting of this product it may  
be necessary to measure the speed of rotating components. Have a qualified or  
licensed service individual who has been properly trained in handling exposed  
rotating components, perform these tasks. Failure to follow all safety  
precautions when exposed to rotating components could result in death or  
serious injury.  
Make sure all personnel are standing clear of the unit before proceeding. The  
system components will start when the power is applied.  
Fan Belt Adjustment - Belt Drive Units  
The fan belts must be inspected periodically to assure proper unit operation.  
Replacement is necessary if the belts appear frayed or worn. Units with dual belts  
require a matched set of belts to ensure equal belt length.  
When removing or installing the new belts, do not stretch them over the sheaves.  
Loosen the belts using the belt tension adjustment bolts on the motor mounting  
base.  
Once the new belts are installed, using a Browning or Gates tension gauge (or  
equivalent) illustrated in Figure 16; adjust the belt tension as follows;  
1. To determine the appropriate belt deflection;  
a. Measure the center-to-center shaft distance (in inches) between the fan  
and motor sheaves.  
b. Divide the distance measured in Step 1a by 64; the resulting value  
represents the amount of belt deflection that corresponds to the proper  
belt tension.  
2. Set the large O-ring on the belt tension gauge at the deflection value  
determined in Step 1b.  
3. Set the small O-ring at zero on the force scale of the gauge plunger.  
4. Place the large end of the gauge at the center of the belt span; then depress  
the gauge plunger until the large O-ring is even with the top of the next belt  
or even with a straightedge placed across the fan and motor sheaves. Refer  
to Figure 16.  
5. Remove the belt tension gauge. The small O-ring now indicates a number  
other than zero on the plungers force scale. This number represents the force  
(in pounds) required to give the needed deflection.  
6. Compare the “force” scale reading (Step 5) with the appropriate “force”  
value listed in Table 6. If the “force” reading is outside the range, readjust the  
belt tension.  
WC-IOM-7 • Packaged Heat Pump  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
Note: Actual belt deflection “force” must not exceed the maximum “force”  
value shown in Table 6.  
Table 6.  
Belt tension measurement and deflection ranges  
Deflection Force (Lbs.)  
Belts  
Cross  
Section  
Small  
P.D  
Super Gripbelts  
Gripnotch  
Steel Cable  
Gripbelts  
Range  
Min.  
3
Max.  
4 1/2  
5
Min.  
Max.  
5 1/2  
6 1/4  
6 7/8  
8
Min.  
Max  
4
3.0 - 3.6  
3.8 - 4.8  
5.0 - 7.0  
3.4 - 4.2  
4.4 - 5.6  
5.8 - 8.8  
3 7/8  
4 1/2  
5
3 1/4  
3 3/4  
4 1/4  
4 1/2  
5 3/4  
7
A
B
3 1/2  
4
4 3/4  
5 1/4  
5 1/2  
7 1/4  
8 3/4  
5 1/2  
5 1/2  
7 1/8  
8 3/4  
4
5 3/4  
6 1/2  
7 3/8  
5 1/8  
6 3/8  
9 1/8  
10 1/8  
7. Recheck the belt tension at least twice during the first 2 to 3 days of  
operation. Belt tension may decrease until the new belts are “run in.  
Figure 16. Belt tension gauge  
Monthly Maintenance  
ƽWARNING  
Hazardous Voltage!  
Disconnect all electric power, including remote disconnects before servicing.  
Follow proper lockout/tagout procedures to ensure the power can not be  
inadvertently energized. Failure to disconnect power before servicing could  
result in death or serious injury.  
Before completing the following checks, turn the unit OFF and lock the main  
power disconnect switch open. Failure to disconnect power before servicing can  
cause severe personal injury or death.  
42  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
Filters  
Inspect the return air filters. Clean or replace them if necessary. Refer to the  
unit Service Facts for filter information.  
Return Air Smoke Detector Maintenance  
Airflow through the unit is affected by the amount of dirt and debris accumulated  
on the indoor coil and filters. To insure that airflow through the unit is adequate  
for proper sampling by the return air smoke detector, complete adherence to the  
maintenance procedures, including recommended intervals between filter  
changes, and coil cleaning is required.  
Periodic checks and maintenance procedures must be performed on the smoke  
detector to insure that it will function properly. For detailed instructions  
concerning these checks and procedures, refer to the appropriate section(s) of  
the smoke detector Installation and Maintenance Instructions provided with the  
literature package for this unit.  
Cooling Season  
Check the units drain pans and condensate piping to ensure that there are no  
blockages.  
Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils  
appear dirty, clean them according to the instructions described in “Coil  
Cleaning” later in this section.  
Manually rotate the condenser fan(s) to ensure free movement and check  
motor bearings for wear. Verify that all of the fan mounting hardware is tight.  
Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts  
are securely mounted. Keep the blades clean as necessary.  
Verify that all damper linkages move freely; lubricate with white grease, if  
necessary.  
Check supply fan motor bearings; repair or replace the motor as necessary.  
Check the fan shaft bearings for wear. Replace the bearings as necessary.  
Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the  
“Fan Belt Adjustment” section for belt replacement and adjustments.  
Verify that all wire terminal connections are tight.  
Remove any corrosion present on the exterior surfaces of the unit and repaint  
these areas.  
Generally inspect the unit for unusual conditions (e.g., loose access panels,  
leaking piping connections, etc.)  
Make sure that all retaining screws are reinstalled in the unit access panels  
once these checks are complete.  
WC-IOM-7 • Packaged Heat Pump  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
With the unit running, check and record the: ambient temperature;  
compressor suction and discharge pressures (each circuit); superheat (each  
circuit);  
Record this data on an operators maintenance log” like the one shown in  
Table 7 on page 46. If the operating pressures indicate a refrigerant shortage,  
measure the system superheat. For guidelines, refer to the “Compressor Start-  
Up” section.  
Note: Do Not release refrigerant to the atmosphere! If adding or removing  
refrigerant is required, the service technician must comply with all federal,  
state and local laws.  
Heating Season  
Inspect the units air filters. If necessary, clean or replace them.  
Check supply fan motor bearings; repair or replace the motor as necessary.  
Inspect both the main unit control panel and heat section control box for  
loose electrical components and terminal connections, as well as damaged  
wire insulation. Make any necessary repairs.  
Verify that the electric heat system operates properly.  
Coil Cleaning  
Regular coil maintenance, including annual cleaning, enhances the units  
operating efficiency by minimizing: compressor head pressure and amperage  
draw; evaporator water carryover; fan brake horsepower, due to increase static  
pressure losses; airflow reduction.  
At least once each year, or more often if the unit is located in a “dirty”  
environment, clean the evaporator and condenser coils using the instructions  
outlined below. Be sure to follow these instructions as closely as possible to  
avoid damaging the coils.  
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-  
up type or a high-pressure sprayer). A high-quality detergent is also required;  
suggested brands include “SPREX A.C., “OAKITE 161, “OAKITE 166” and  
“COILOX. If the detergent selected is strongly alkaline (ph value exceeds 8.5),  
add an inhibitor.  
1. Remove enough panels from the unit to gain access to the coil. Remove the  
access panel from the roof located next to the rear condenser fan.  
2. Protect all electrical devices such as motors and controllers from any over  
spray.  
3. Straighten any bent coil fins with a fin comb.  
4. Mix the detergent with water according to the manufacturers instructions. If  
desired, heat the solution to 150° F maximum to improve its cleansing  
capability.  
44  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
ƽWARNING  
Hazardous Pressures!  
Coils contain refrigerant under pressure. When cleaning coils, maintain coil  
cleaning solution temperature under 150°F to avoid excessive pressure in the  
coil. Failure to follow these safety precautions could result in coil bursting, which  
could result in death or serious injury.  
Do not heat the detergent-and-water solution above 150° F. Hot liquids sprayed  
on the exterior of the coil will raise the coils internal pressure and may cause it to  
burst. Failure to follow proper procedures can result in personal illness or injury  
or severe equipment damage.  
5. 5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is  
used:  
a. do not allow sprayer pressure to exceed 600 psi.  
b. the minimum nozzle spray angle is 15 degrees.  
c. maintain a minimum clearance of 6" between the sprayer nozzle and the  
coil.  
d. spray the solution perpendicular (at 90 degrees) to the coil face.  
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of  
the coil. Allow the cleaning solution to stand on the coil for five minutes.  
7. Rinse both sides of the coil with cool, clean water.  
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and  
7.  
9. Reinstall all of the components and panels removed in Step 1 and any  
protective covers installed in step 2.  
10. Restore the unit to its operational status and check system operation.  
Final Process  
For future reference, you may find it helpful to record the unit data requested  
below in the blanks provided.  
(1) Complete Unit Model Number:  
_______________________________________________________________________  
(2) Unit Serial Number:  
_______________________________________________________________________  
(3) Wiring Diagram Numbers (from unit control panel):  
— schematic(s)  
_______________________________________________________________________  
_______________________________________________________________________  
WC-IOM-7 • Packaged Heat Pump  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
_______________________________________________________________________  
_______________________________________________________________________  
— connection(s)  
_______________________________________________________________________  
_______________________________________________________________________  
_______________________________________________________________________  
_______________________________________________________________________  
Table 7.  
Sample maintenance log  
Refrigerant Circuit #1  
Refrigerant Circuit #2  
Date  
Current Compr. Oil Suction  
Dischcharge Super heat Sub coolF/ Compr. Oil Suction  
Dischcharge  
Pressure  
Psig/kpa  
Super heat Sub coolF/  
F/C  
Ambient Level  
temp F/C  
Pressure  
Psig/kPa  
Pressure  
Psig/kpa  
F/C  
C
Level  
Pressure  
Psig/kPa  
C
46  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
ReliaTel Control  
The RTRM has the ability to provide the service personnel with some unit  
diagnostics and system status information.  
ƽWARNING  
Hazardous Service Procedures!  
The maintenance and troubleshooting procedures recommended in this section  
of the manual could result in exposure to electrical, mechanical or other  
potential safety hazards. Always refer to the safety warnings provided  
throughout this manual concerning these procedures. When possible,  
disconnect all electrical power including remote disconnects before servicing.  
Follow proper lockout/tagout procedures to ensure the power can not be  
inadvertently energized. When necessary to work with live electrical  
components, have a qualified licensed electrician or other individual who has  
been trained in handling live electrical components perform these tasks. Failure  
to follow all of the recommended safety warnings provided, could result in death  
or serious injury.  
Before turning the main power disconnect switch “Off, follow the steps below to  
check the ReliaTel Refrigeration Module (RTRM). All diagnostics & system status  
information stored in the RTRM will be lost when the main power is turned “Off.  
To prevent injury or death from electrocution, it is the responsibility of the  
technician to recognize this hazard and use extreme care when performing  
service procedures with the electrical power energized.  
1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is  
lit, go to Step 3.  
2. If the LED is not lit, verify that 24 VAC is presence between J1-1 and J1-2. If 24  
VAC is present, proceed to Step 3. If 24 VAC is not present, check the unit  
main power supply, check transformer (TNS1). Proceed to Step 3 if necessary.  
3. Utilizing “Method 1” or “Method 2” in the “System Status Checkout  
Procedure ” section, check the following:  
System status  
Heating status  
Cooling status  
If a System failure is indicated, proceed to Step 4. If no failures are indicated,  
proceed to Step 5.  
4. If a System failure is indicated, recheck Steps 1 and 2. If the LED is not lit in  
Step 1, and 24 VAC is present in Step 2, the RTRM has failed. Replace the  
RTRM.  
5. If no failures are indicated, use one of the TEST mode procedures described  
in the “Unit Start-Up” section to start the unit. This procedure will allow you  
WC-IOM-7 • Packaged Heat Pump  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
to check all of the RTRM outputs, and all of the external controls (relays,  
contactors, etc.) that the RTRM outputs energize, for each respective mode.  
Proceed to Step 6.  
6. Step the system through all of the available modes, and verify operation of  
all outputs, controls, and modes. If a problem in operation is noted in any  
mode, you may leave the system in that mode for up to one hour while  
troubleshooting. Refer to the sequence of operations for each mode, to assist  
in verifying proper operation. Make the necessary repairs and proceed to  
Steps 7 and 8.  
7. If no abnormal operating conditions appear in the test mode, exit the test  
mode by turning the power “Off” at the main power disconnect switch.  
8. Refer to the individual component test procedures if other microelectronic  
components are suspect.  
System Status Checkout Procedure  
“System Status” is checked by using one of the following two methods:  
Method 1  
If the Zone Sensor Module (ZSM) is equipped with a remote panel with LED  
status indication, you can check the unit within the space. If the ZSM does not  
have LEDs, use Method 2. BAYSENS010B, BAYSENS011B, BAYSENS019B,  
BAYSENS020B, BAYSENS021A & BAYSENS023A all have the remote panel  
indication feature. The LED descriptions are listed below.  
LED 1 (System)  
“On” during normal operation.  
“Off” if a system failure occurs or the LED fails.  
“Flashing” indicates test mode.  
LED 2 (Heat)  
“On” when the heat cycle is operating.  
“Off” when the heat cycle terminates or the LED fails.  
“Flashing” indicates a heating failure.  
LED 3 (Cool)  
“On” when the cooling cycle is operating.  
“Off” when the cooling cycle terminates or the LED fails.  
“Flashing” indicates a cooling failure.  
48  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
LED 4 (Service)  
“On” indicates a clogged filter.  
“Off” during normal operation.  
“Flashing” indicates an evaporator fan failure  
Below is the complete listing of failure indication causes.  
System Failure  
Check the voltage between terminals 6 and 9 on J6, it should read approximately  
32 VDC. If no voltage is present, a System failure has occurred. Refer to Step 4 in  
the previous section for the recommended troubleshooting procedure.  
Cooling Failure  
1. Cooling and heating set point (slide pot) on the zone sensor has failed. Refer  
to the “Zone Sensor Test Procedure” section.  
2. Zone temperature thermistor ZTEMP on ZTS failed. Refer to the “Zone  
Sensor Test Procedure” section.  
3. CC1 or CC2 24 VAC control circuit has opened, check CC1 & CC2 coils, and  
any of the controls below that apply to the unit (HPC1, HPC2).  
4. LPC1 has opened during the 3 minute minimum “on time” during 4  
consecutive compressor starts, check LPC1 or LPC2 by testing voltage  
between the J1-8 & J3-2 terminals on the RTRM and ground. If 24 VAC is  
present, the LPCs has not tripped. If no voltage is present, LPCs has tripped.  
Service Failure  
5. If the supply fan proving switch has closed, the unit will not operate (when  
connected to RTOM), check the fan motor, belts, and proving switch.  
6. Clogged filter switch has closed, check the filters.  
Simultaneous Heat and Cool Failure  
1. Emergency Stop is activated.  
Method 2  
The second method for determining system status is done by checking voltage  
readings at the RTRM (J6). The system indication descriptions and the  
approximate voltages are listed below.  
System Failure  
Measure the voltage between terminals J6-9 & J6-6.  
Normal Operation = approximately 32 VDC  
System Failure = less than 1 VDC, approximately 0.75 VDC  
WC-IOM-7 • Packaged Heat Pump  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
Test Mode = voltage alternates between 32 VDC & 0.75 VDC  
Heat Failure  
Measure the voltage between terminals J6-7 & J6-6.  
Heat Operating = approximately 32 VDC  
Heat Off = less than 1 VDC, approximately 0.75 VDC  
Heating Failure = voltage alternates between 32 VDC & 0.75 VDC  
Cool Failure  
Measure the voltage between terminals J6-8 & J6-6.  
Cool Operating = approximately 32 VDC  
Cool Off = less than 1 VDC, approximately 0.75 VDC  
Cooling Failure = voltage alternates between 32 VDC & 0.75 VDC  
Service Failure  
Measure the voltage between terminals J6-10 & J6-6.  
Clogged Filter = Approximately 32 VDC.  
Normal = Less than 1 VDC, approximately 0.75 VDC  
Fan Failure = voltage alternates between 32 VDC & 0.75 VDC.  
To use LEDs for quick status information at the unit, purchase a BAYSENS010B  
ZSM and connect wires with alligator clamps to terminals 6 through 10. Connect  
each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6  
terminals 6 through 10.  
Note: If the system is equipped with a programmable zone sensor,  
(BAYSENS019A, BAYSENS020A or BAYSENS023A), the LED indicators  
will not function while the BAYSENS010A is connected.  
Resetting Cooling and Heating Lockouts  
Cooling Failures and Heating Lockouts are reset in an identical manner. Method 1  
explains resetting the system from the space; Method 2 explains resetting the  
system at the unit.  
Note: Before resetting Cooling Failures and Heating Lockouts check the Failure  
Status Diagnostics by the methods previously explained. Diagnostics will  
be lost when the power to the unit is disconnected.  
Method 1  
To reset the system from the space, turn the “Mode” selection switch at the zone  
sensor to the “Off” position. After approximately 30 seconds, turn the “Mode”  
selection switch to the desired mode, i.e. Heat, Cool or Auto.  
50  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Method 2  
To reset the system at the unit, cycle the unit power by turning the disconnect  
switch “Off” and then “On.  
Lockouts can be cleared through the building management system. Refer to the  
building management system instructions for more information.  
Zone Temperature Sensor (ZTS) Service Indicator  
The ZSM SERVICE LED is a generic indicator, that will signal the closing of a  
Normally Open switch at any time, providing the Indoor Motor (IDM) is  
operating. This indicator is usually used to indicate a clogged filter, or an air side  
fan failure.  
The RTRM will ignore the closing of this Normally Open switch for 2 ( 1) minutes.  
This helps prevent nuisance SERVICE LED indications. The exception is the LED  
will flash 40 seconds after the fan is turned “On” if the Fan Proving Switch is not  
made.  
Clogged Filter Switch  
This LED will remain lit the entire time that the Normally Open switch is closed.  
The LED will be turned off immediately after resetting the switch (to the Normally  
Open position), or any time that the IDM is turned “Off.  
If the switch remains closed, and the IDM is turned “On, the SERVICE LED will be  
turned “On” again after the 2 ( 1) minute ignore delay.  
This LED being turned “On, will have no other affect on unit operation. It is an  
indicator only.  
Fan Failure Switch  
When the “Fan Failure” switch is wired to the RTOM, the LED will remain flashing  
the entire time the fan proving switch is closed, indicating a fan failure, and it will  
shut the unit operations down.  
WC-IOM-7 • Packaged Heat Pump  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Zone Temperature Sensor (ZTS) Test  
Note: These procedures are not for programmable or digital models and are  
conducted with the Zone Sensor Module electrically removed from the  
system.  
Test 1  
Zone Temperature Thermistor (ZTEMP)  
This component is tested by measuring the resistance between terminals 1 and 2  
on the Zone Temperature Sensor. Below are some typical indoor temperatures,  
and corresponding resistive values.  
Table 8.  
Nominal  
ZTEMP  
Nominal CSP  
or HSP  
Zone Temperature Resistance  
Resistance  
50 F°  
55 F°  
60 F°  
65 F°  
70 F°  
75 F°  
80 F°  
85 F°  
90 F°  
10.0 C°  
12.8 C°  
15.6 C°  
18.3 C°  
21.1 C°  
23.9 C°  
26.7 C°  
29.4 C°  
32.2 C°  
19.9 K-Ohms 889 Ohms  
17.47 K-Ohms 812 Ohms  
15.3 K-Ohms 695 Ohms  
13.49 K-Ohms 597 Ohms  
11.9 K-Ohms 500 Ohms  
10.50 K-Ohms 403 Ohms  
9.3 K-Ohms  
8.25 K-Ohms 208 Ohms  
7.3 K-Ohms 110 Ohms  
305 Ohms  
Test 2  
Cooling Set Point (CSP) and Heating Set Point (HSP)  
The resistance of these potentiometers are measured between the following  
ZSM terminals. Refer to the chart above for approximate resistances at the given  
setpoints.  
Cool SP = Terminals 2 and 3  
Range = 100 to 900 Ohms approximate  
Heat SP = Terminals 2 and 5  
Range = 100 to 900 Ohms approximate  
52  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Test 3  
System Mode and Fan Selection  
The combined resistance of the Mode selection switch and the Fan selection  
switch can be measured between terminals 2 and 4 on the Zone Sensor. The  
possible switch combinations are listed on the following page with their  
corresponding resistance values.  
Test 4  
LED Indicator Test, (SYS ON, HEAT, COOL & SERVICE)  
Method 1  
Testing the LED using a meter with diode test function. Test both forward and  
reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts,  
depending on your meter. Reverse bias will show an Over Load, or open circuit  
indication if LED is functional.  
Method 2  
Testing the LED with an analog Ohmmeter. Connect Ohmmeter across LED in one  
direction, then reverse the leads for the opposite direction. The LED should have  
at least 100 times more resistance in reverse direction, as compared with the  
forward direction. If high resistance in both directions, LED is open. If low in both  
directions, LED is shorted.  
Method 3  
To test LEDs with ZSM connected to unit, test voltages at LED terminals on ZSM.  
A measurement of 32 VDC, across an unlit LED, means the LED has failed.  
Note: Measurements should be made from LED common (ZSM terminal 6 to  
respective LED terminal). Refer to the Zone Sensor Module (ZSM) Terminal  
Identification table at the beginning of this section.  
Programmable & Digital Zone Sensor Test  
Testing serial communication voltage  
1. Verify 24 VAC is present between terminals J6-14 & J6-11.  
2. Disconnect wires from J6-11 and J6-12. Measure the voltage between J6-11  
and J6-12, should be about 32 VDC.  
3. Reconnect wires to terminals J6-11 and J6-12. Measure voltage again  
between J6-11 and J6-12, voltage should flash high and low every 0.5  
seconds. The voltage on the low end will measure about 19 VDC, while the  
voltage on the high end will measure from approximately 24 to 38 VDC.  
WC-IOM-7 • Packaged Heat Pump  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
4. Verify all modes of operation, by running the unit through all of the steps in  
the “Test Modes” section discussed in “Unit Start-Up.  
5. After verifying proper unit operation, exit the test mode. Turn the fan on  
continuously at the ZSM, by pressing the button with the fan symbol. If the  
fan comes on and runs continuously, the ZSM is good. If you are not able to  
turn the fan on, the ZSM is defective.\  
Table 9.  
System mode and fan selection chart  
Resistance Valves  
(Ohms)  
Zone Sensor  
Unit/Fan Mode  
Local Fan  
Mode  
Local Unit Mode  
2.32K  
Off/ Auto  
Off  
Auto  
Auto  
Auto  
On  
4.87K  
Cool/Auto  
Cool  
7.68K  
Auto/Auto  
Auto  
10.77K  
Off/On  
Off  
13.32K  
Cool/On  
Cool  
On  
16.13K  
Auto/On  
Auto  
On  
19.48K  
Heat/Auto  
Heat  
Auto  
On  
27.93K  
Heat/On  
Heat  
35.0K  
Emergency Heat/Auto  
Emergency Heat/On  
INVALID/Short  
INVALID/Open  
Emergency Heat  
Emergency Heat  
Auto  
On  
43.45K  
Out of Range (Short)  
Out of Range (Open)  
Invalid (CV), Auto (VAV) Invalid  
Invalid (CV), Off (VAV) Invalid  
ReliaTel Refrigeration Module (RTRM) Default Chart  
If the RTCI loses input from the building management system, the RTRM will  
control in the default mode after approximately 15 minutes. If the RTRM loses the  
Heating and Cooling setpoint input, the RTRM will control in the default mode  
instantaneously. The temperature sensing thermistor in the Zone Sensor Module  
is the only component required for the “Default Mode” to operate.  
Unit Operation without a Zone Sensor  
This procedure is for temporary operation only. The economizer and condenser  
fan cycling functions are disabled.  
1. Open and Lock the unit disconnect switch.  
2. Remove the Outside Air Sensor (OAS) from the condenser section of unit.  
3. Use two (2) wire nuts, to individually cap the wires.  
4. Locate the RTRM (J6). Connect two (2) wires to terminals J6-1 and 2.  
5. Connect the sensor (OAS) using two wire nuts to the two (2) field supplied  
wires that were connected to terminals 1 and 2 on J6.  
54  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Troubleshooting  
Unit Economizer Control (ECA) Troubleshooting  
ReliaTel Control  
Table 10. Verify economizer status by economizer actuator (ECA) LED indicator:  
OFF:  
No Power or Failure  
Normal, OK to Economize  
Normal, Not OK to Economize  
1/2 Second On / 2 Seconds Off:  
Error Code:  
ON:  
Slow Flash:  
Fast Flash -  
Pulse Flash:  
Communications Failure  
2 Second On / 1/2 Second Off:  
Error Code:  
1 Flash:  
Actuator Fault  
2 Flashes:  
3 Flashes:  
4 Flashes:  
5 Flashes:  
6 Flashes:  
7 Flashes:  
8 Flashes:  
9 Flashes:  
10 Flashes:  
11 Flashes:  
CO2 Sensor  
RA Humidity Sensor  
RA Temp Sensor  
OA Quality Sensor  
OA Humidity Sensor  
OA Temp Sensor  
MA Temp Sensor  
RAM Fault  
ROM Fault  
EEPROM Fault  
WC-IOM-7 • Packaged Heat Pump  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
For easier access, after 2007, published unit wiring diagrams (individual, separate  
diagrams for unitary product lines) will become available via e-Library instead of  
through wiring manuals. Diagrams prior to 2008 will be located in wiring  
diagram books RT-SVE03A-EN and RT-SVE06A-EN.  
Drawing  
Number  
Description  
2309-3105  
2309-3108  
2309-3115  
2309-3116  
2309-3140  
2309-3149  
2309-3170  
2309-3171  
2309-3172  
2309-3173  
2309-3174  
2309-3194  
23093195  
2309-3352  
2309-3358  
2309-3360  
2309-3361  
2309-3364  
2309-3377  
2309-3382  
2309-3383  
2309-3392  
2309-3393  
2309-3394  
2309-3183  
2309-3184  
2309-3185  
2309-3186  
2309-3187  
2309-3188  
2309-3189  
2309-3190  
2309-3191  
2309-3192  
Diagram; Novar ETM-3051  
(Home Depot)  
Diagram; CONTROL WC_150 WC_240 400-575/60/3  
Diagram; Power Electrical WC 150-240  
Diagram; Power Electrical WC 240  
Diagram; Master Stacked Layer Model  
Diagram; Connection Electrical WC 180  
Diagram; Connection Electrical WC 240  
Diagram; Connection Electrical WC 240  
Diagram; Connection Electrical WC 150  
Diagram; Connection Electrical WC 150  
Diagram; Connection Electrical WC 180  
INSTRUCTIONAL DIAGRAM FOR CONVETNIONAL THERMOSTAT  
Diagram;Novar 3051  
MICRO INTERCONNECTION DIAGRAM  
Diagram; Crankcase Heater Kits for Voyager 2  
SCHEMATICS; CONNECTION DIAGRAM--VOY2 208-230V WC180  
SCHEMATICS; CONNECTION DIAGRAM--VOY2 460/575V WC 180  
Diagram 14 position plug  
MASTER DRAWING; CONNECTION DIAGRAMS--VOY2  
Schematic; Power 200-230V WC 150-240  
Schematic; Power 400-575V WC 150-240  
Schematic, Control 200-575V WC 150-240  
Diagram, Connection 208-230V WC 150  
Diagram, Connection 400-575V WC 150  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
Diagram; Electric Heat  
WC-IOM-7 • Packaged Heat Pump  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Warranty  
Heat Pump  
WCZ, WCY, WCX, WCC, WCD, WCH, WCM, WCP and WSC (Parts Only)  
Models Less Than 20 Tons for Commercial Use*  
This warranty is extended by Trane, to the original purchaser and to any  
succeeding owner of the real property to which the Heat Pump is originally  
affixed, and applies to products purchased and retained for use within the U.S.A.  
and Canada. There is no warranty against corrosion, erosion or deterioration. If  
any part of your Heat Pump fails because of a manufacturing defect within one  
year from the date of the original purchase, Warrantor will furnish without charge  
the required replacement part.  
In addition, if the sealed motor-compressor fails because of a manufacturing  
defect within the second through fifth year from the date of original purchase,  
Warrantor will furnish without charge the required replacement compressor.  
Warrantors obligations and liabilities under this warranty are limited to  
furnishing F.O.B. Warrantor factory or warehouse replacement parts for  
Warrantors products covered under this warranty. Warrantor shall not be  
obligated to pay for the cost of lost refrigerant. No liability shall attach to  
Warrantor until products have been paid for and then liability shall be limited  
solely to the purchase price of the equipment under warranty shown to be  
defective.  
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL  
OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN  
NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED  
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE,  
AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR  
CONSEQUENTIAL DAMAGES.  
Some states do not allow limitations on how long an implied warranty lasts or do  
not allow the exclusion or limitation of incidental or consequential damages, so  
the above limitation or exclusion may not apply to you. This warranty gives you  
specific legal rights, and you may also have other rights which vary from state to  
state.  
Trane  
2701 Wilma Rudolph Blvd.  
Clarksville, TN 37040-1008  
Attention: Manager, Product Service  
GW-604-4800  
* This warranty is for commercial usage of said equipment and not applicable  
when the equipment is used for a residential application. Commercial use is any  
application where the end purchaser uses the product for other than personal,  
family or household purposes.  
WC-IOM-7 • Packaged Heat Pump  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Warranty  
Heat Pump  
Standard Equipment Warranty Terms and Conditions  
Commercial Equipment Warranty and Liability  
Models Larger that 20 Tons for Commercial Use*  
The Company warrants for a period of 12 months from initial start-up or 18  
months from date of shipment, whichever is less, that the Company products  
covered by this order (1) are free from defects in material and workmanship and  
(2) have the capacities and ratings set forth in the Companys catalogs and  
bulletins, provided that no warranty is made against corrosion, erosion or  
deterioration.  
The Companys obligations and liabilities under this warranty are limited to  
furnishing f.o.b. factory or warehouse at Company designated shipping point,  
freight allowed to Buyers city (or port of export for shipment outside the  
conterminous United States) replacement equipment (or at the option of the  
Company parts therefore) for all Company products not conforming to this  
warranty and which have been returned to the manufacturer.  
The Company shall not be obligated to pay for the cost of lost refrigerant. No  
liability whatever shall attach to the Company until said products have been paid  
for and then said liability shall be limited to the purchase price of the equipment  
shown to be defective.  
The Company makes certain further warranty protection available on an optional  
extra-cost basis. Any further warranty must be in writing, signed by an officer of  
the Company.  
The warranty and liability set forth herein are in lieu of all other warranties and  
liabilities, whether in contract or in negligence, express or implied, in law or in  
fact, including implied warranties of merchantability and fitness for particular  
use. In no event shall the Company be liable for any incidental or consequential  
damages.  
Trane  
2701 Wilma Rudolph Blvd.  
Clarksville, TN 37040-1008  
Attention: Manager,Product Service  
58  
Packaged Heat Pump • WC-IOM-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
Date  
WC-IOM-7  
12/04  
Supersedes  
WC-IOM-7 (04/03)  
The manufacturer has a policy of continuous product and product data improvement and reserves  
the right to change design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taylor Frozen Dessert Maker C709 User Manual
Thermador Dishwasher DW44ZB User Manual
Thermo Products Furnace CDX1 100N User Manual
Tokina Camera Accessories TVR0614 User Manual
Toro Grill Accessory 252 Series User Manual
Tricity Bendix Cooktop SG550 1 User Manual
Tricity Bendix Oven TBS 603 User Manual
Tripp Lite TV Cables A004 012 User Manual
Troy Bilt Vacuum Cleaner 24A 070F768 User Manual
Viking Refrigerator F20872 User Manual