A
B
C
D
E
F
G
H
I
J
27.0"
11.8"
30.1"
1
2
1
2
225 Amp M.L.O.
w/ (1) #6-250kcmil
Lug per Phase (typ)
Utility Feed
B
A
C
52C
UPS Bypass
Input Breaker
225 Amp Box-
Mounted Neutral w/
(2) #6-250kcmil Lugs
N
52M
3
3
Maintenance
Bypass Breaker
52L
4
4
UPS Output
Breaker
To Critical Load
5
5
0.5" Dia.
Mounting Hole (4)
Front View
(Door Removed)
6
Left Side View
Front View
6
Feed From Utility
B
A
C
52C
225AT
7
7
A
Feed to
UPS
Input
UPS
KVA
150
UPS Output Breaker
kAIC rating at
480/600V
Part No.
Voltage
480/600
B
C
Amp Rating
Type
FD
N
MBSB80-225-43
180
25/14
Enclosure - NEMA 1, Surface-Mount (UL Listed).
8
8
ST
Box/Trim - 12-Gauge painted steel, trim held with adjustable clamps; Door equiped
with one 3x5 directory cardholder and Corbin type 15767 Snaplock.
Finish - Beige polyester powdercoat on all surfaces, treated with sealer.
Breakers - Cutler-Hammer thermal-magnetic type, 225A frame, 3-pole, trip settings as
shown, supplied with (1) #4-4/0 terminal lug per phase.
52M
225AT
52L
225AT
Feed
from
UPS
A
B
C
9
9
Weight - Approximately 190 lbs total.
Output
A
B
C
10
10
Feed To Critical Load
TITLE
Drawn by
EO
Date 07/07/04
NOTES
TOSHIBA
1) This drawing is for illustration purposes only and is subject to change without notice. TIC
is not responsible for any errors or omissions.
150kVA G8000 Series UPS
INTERNATIONAL CORPORATION
Houston Texas, USA
Approved by
JIS
3-Breaker Maintenance Bypass Panel
Date 07/07/04
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
DRAWING NO.
REV.
1.0
MBSB80-225-43
Download from Www.Somanuals.com. All Manuals Search And Download.
|