Technicolor Thomson Switch EAP 110 User Manual

02 • 07 • 01  
®
Model EAP 110  
GENERATOR SET ANNUNCIATOR  
20 Light annunciator meets or  
exceeds requirements of NFPA 110,  
NFPA 99 & CSA 282-00 building code  
standards for Emergency Standby  
Generator systems  
RS 422 Data Communication capability  
saves installation time & reduces costs  
Programmable annunciation & labeling  
allows excellent flexibility for different  
applications  
Automatic “ringback” & flashing  
annunciator lights provides excellent  
status indication of existing & incoming  
fault conditions  
4 fault annunciation circuits can be  
activated from external hardwired  
contacts for added system capability  
Multiple EAP 110 Annunciators can be  
easily interconnected to provide up to 40  
remote annunciation lights from a single  
MEC 20 engine controller  
DESCRIPTION  
he EAP 110 annunciator is designed for remote fault  
annunciation of emergency standby generator sets  
“auto-ringback” feature to annunciate subsequent alarm  
conditions. For applications requiring additional alarm  
annunciation from remote sensing contacts, the EAP 110  
can accept up to 4 hardwired contact inputs dependant  
upon the alarm configuration. The EAP 110 is DC powered  
typically from a 12 or 24V engine starting battery. Two  
EAP 110 annunciators can be interconnected together via  
the communication link to allow up to 40 remote  
annunciator points from a single MEC 20 engine controller  
(consult Thomson Technology for further details). The  
standard features of the EAP 110 meet and exceed all  
requirements of NFPA 110, NFPA 99 & CSA 282-00  
building code standards for Emergency Standby  
Generator systems.  
T
utilizing Thomson Technology MEC 2 & MEC 20 Engine  
Controllers. The advanced design uses a RS 422  
communication data link to provide the control &  
monitoring signals between the engine controller and  
remote annunciator. The communication link allows a  
simple, cost effective system installation at any building  
site. Up to 20 individual fault conditions are remotely  
monitored utilizing both visual LED lights & audible  
alarm annunciation. Lamp test and alarm horn silence  
pushbuttons are provided. Each fault is individually  
programmable for audible horn operation and alarm  
labels are field configurable. Operation logic includes a  
ISO 9001-2000  
THOMSON TECHNOLOGY INC. • 9087A - 198th STREET, LANGLEY, BC CANADA V1M 3B1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taurus Group Oven HORIZON 30 User Manual
ToCAD Camcorder Accessories 9002TM User Manual
Toshiba DVD VCR Combo D VR3SU User Manual
Toshiba Flat Panel Television 20VL43 User Manual
Toshiba Personal Computer M505 User Manual
Venture Products Car Amplifier VP100L User Manual
ViewSonic Computer Monitor VA1703w 2 User Manual
ViewSonic Projection Television PJD6211 User Manual
Viking Oven DEDO527TSS User Manual
VTech Cell Phone CS6114 User Manual