INSTALLATION AND MAINTENANCE INSTRUCTIONS
B114LP Plug-in Detector Base
CANADA - 1151A, 2151A, 2151TA; EUROPE - 1151E, 2151E
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
For use with the following smoke detectors: US - 1151, 2151, 2151T;
SPECIfICATIONS
Base Diameter:
Base Height:
Weight:
6.2 in (157 mm)
0.95 in (24 mm)
0.6 lb (274 g)
Mounting:
4˝ square box with or without plaster ring, minimum depth 1.5˝; 4˝ octagon box, minimum depth 1.5˝;
31⁄2˝ octagon box, minimum depth 1.5˝; 31⁄2˝ octagon box, minimum depth 1.5˝
0°C to 49°C (32°F to 120°F)
Operating Temperature Range:
Operating Humidity Range:
10% to 93% Relative Humidity Non-condensing
Electrical Ratings (includes base and detector)
System Voltage:
120 VAC, 60 Hz
Relay Contact Ratings Resistive Load:
Form A — 2.0A @ 30VAC/DC; Form C — 2.0A @ 30VAC/DC, 1.0A @ 125VAC
(If used, the RA400 Remote Annunciator and RTC operates within the specified detector system voltage)
36.0 seconds maximum
Start-up Time (after 60 second reset):
nect smoke detectors to control panels and accessory devices should be color-
coded to reduce the likelihood of wiring errors. Improper connections can
prevent a system from responding properly in the event of a fire.
BEfORE INSTALLINg
Please thoroughly read the System Sensor manual I56-407, Guide for Proper
Use of System Smoke Detectors. This manual provides detailed information on
detector spacing, placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor. (For installation in Canada, refer to
CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems and CEC
Part 1, Sec. 32.)
For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring for the power (+ and –) loop is recommended to
minimize the effects of electrical interference.
NOTICE: This manual should be left with the owner/user of this equipment.
fIgURE 1. TERMINAL LAyOUT:
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector used with this base
should be cleaned at least once a year.
24VDC/24VAC
TERMINALS
BASE
TERMINALS
gENERAL DESCRIPTION
6
7
The model B114LP detector base is designed for use with System Sensor model
2151 photoelectronic and 1151 ionization detector heads. This four-wire base is
equipped with screw terminals for the connection of power, ground, relay connec-
tions, and an optional RA400Z remote annunciator. It also includes a resistor that
limits current when the associated smoke detector is in the alarm state.
STRIP GAUGE
2
3
1
SHORTING
SPRING
4
8
5
9
MOUNTINg
10
11
The detector base mounts directly to 31/2-inch and 4-inch octagon boxes and
4-inch square boxes, with or without plaster rings. To mount the base, remove
the decorative ring by rotating it in either direction to unhook the snaps before
separating the ring from the base. Use the screws supplied with the junction
box to attach the base to the box through the appropriate slots in the base.
TAMPER
RESISTANT TAB
12
13
14
C1025-00
Position the decorative ring around the base and rotate it in either direction
until the ring snaps into place (see Figure 2).
fIgURE 2. MOUNTINg BASE TO BOx:
SNAP ON
DECORATIVE
RING
BASE TERMINALS
NO.
1
FUNCTION
NO.
8
FUNCTION
Alarm Relay
Form A
Remote Annunciator (+)
Test Coil (+)
N.O.
N.O.
C.
2
9
3
Not Used
10
Initiation
4
Remote Annunciator (–) 11
C.
Contacts
SCREWS
SHORTING
SPRING
(NOT SUPPLIED)
5
RTC (–)
12
13
14
N.O.
N.C.
C.
Alarm Relay
Form C
6
C.
Supervisory Relay
7
N.O. Form A Contacts
Auxiliary Contacts
DETECTOR
BASE
INSTALLATION gUIDELINES
Allowable loop resistance is an important specification for control panels as
well as for smoke detectors and their bases. The alarm system cannot be ex-
pected to operate correctly if system components have incompatible allowable
loop resistances. Therefore, before beginning installation, refer to the control
panel manufacturer’s loop resistance specification to ensure that it is listed as
compatible with the System Sensor base and smoke detector being installed.
BOX
(NOT SUPPLIED)
All wiring must be installed in compliance with the National Electrical Code
and all applicable local codes and any special requirements of the authority
having jurisdiction, using the proper wire size. The conductors used to con-
C0503-00
D150-02-00
1
I56-0598-004R
Download from Www.Somanuals.com. All Manuals Search And Download.
|