System Sensor Home Security System PDRP 1002 Series User Manual |
3825 Ohio Avenue
St. Charles, IL 60174
1-800-SENSOR2
Fax: (630) 377-6495
PDRP-1002
Series
Agent Release Control
System
Instruction Manual
Document 51135
I56-1358-01
B
04/06/2001
Rev:
PN 51135:B0
ECN 00-543
Download from Www.Somanuals.com. All Manuals Search And Download.
Adherence to the following will aid in problem-free
installation with long-term reliability:
Installation Precautions
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip-
ment may be damaged by removing and/or inserting cards,
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
modules, or interconnecting cables while the unit is energized. grounding will reduce susceptibility. Overhead or outside
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific soft-
ware. Reacceptance testing is required after any change, ad-
dition or deletion of system components, or after any modifica-
tion, repair or adjustment to system hardware or wiring.
Disconnect AC power and batteries prior to removing or in-
serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.
All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 de-
vices, must also be tested and proper system operation veri-
fied.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are re-
moved from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
This system meets NFPA requirements for operation at
0-49° C/32-120° F and at a relative humidity of 85% RH (non-
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nomi-
nal room temperature of 15-27° C/60-80° F.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
FCC Warning
Canadian Requirements
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
Download from Www.Somanuals.com. All Manuals Search And Download.
NFPA Standards
NFPA Standards
This control panel complies with the following NFPA standards:
• NFPA 2001 - Clean Agent Fire Extinguishing Systems
• NFPA 17 - Dry Chemical Extinguishing Systems
• NFPA 17A - Wet Chemical Extinguishing Systems
• NFPA 12 - CO2 Extinguishing Systems (High Pressure Only)
• NFPA 12A - Halon 1301 Extinguishing Systems
• NFPA 12B - Halon 1211 Extinguishing Systems
• NFPA 72 - Central Station Signaling Systems (Automatic, Manual, and Waterflow) - Protected
Premises Unit
Requires NOTI-FIRE 911AC DACT or 411UDAC Universal Digital Alarm Communicator
• NFPA72-LocalFireAlarmSystems (Automatic,Manual,WaterflowandSprinklerSupervisory)
• NFPA 72 - Auxiliary Fire Alarm Systems (Automatic, Manual, and Waterflow)
Requires 4XTMF
• NFPA 72 - Remote Station Fire Alarm Systems (Automatic, Manual, and Waterflow)
Requires 4XTMF or NOTI•FIRE 911AC DACT or 411UDAC
Note: Applications which require the NOTI-FIRE 911AC are not FM approved.
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
• The above listed documentation
• NFPA 72 - Automatic Fire Detectors
• NFPA 72 - Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems
• NFPA 72 - Testing Procedures for Signaling Systems
Underwriters Laboratories Documents
• UL 38 - Manually Actuated Signaling Boxes
• UL 217 - Smoke Detectors, Single and Multiple Station
• UL 228 - Door Closers - Holders for Fire Alarm Systems
• UL 268 - Smoke Detectors for Fire Alarm Systems
• UL 268A - Smoke Detectors for Duct Applications
• UL 346 - Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 - Audible Signaling Appliances
• UL 521 - Heat Detectors for Fire Protective Signaling Systems
• UL 864 - Standard for Control Units for Fire Alarm Systems
• UL 1481 - Power Supplies for Fire Protective Signaling Systems
• UL 1638 - Visual Signaling Appliances
• UL 1971 - Signaling Devices for the Hearing Impaired
• CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
• CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm System
Other
• NEC Article 300 - Wiring Methods
• NEC Article 760 - Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• ADA - Americans with Disabilities Act
4
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Table of Contents
NFPA Standards.......................................................................................................... 4
NFPA Standards .................................................................................................... 4
Underwriters Laboratories Documents ................................................................. 4
Other....................................................................................................................... 4
1. Product Description
Overview ...................................................................................................................... 7
Features ....................................................................................................................... 7
Options ........................................................................................................................ 7
Circuits ......................................................................................................................... 8
Input Circuits.......................................................................................................... 8
Output circuits........................................................................................................ 8
Front Panel Control Switches ................................................................................ 8
Suplemental Documentation ...................................................................................... 8
Control Panel............................................................................................................... 9
DIP Switch Functions................................................................................................ 10
Options ....................................................................................................................... 10
Transmitter Module - 4XTM .............................................................................. 10
Zone Relay Module - 4XZM .............................................................................. 10
Remote Annunciator - RZA-4X .......................................................................... 11
LED Interface Module - 4XLM .......................................................................... 11
Specifications ............................................................................................................. 12
AC Power............................................................................................................. 12
Battery (lead acid only)........................................................................................ 12
Initiating Device Circuits..................................................................................... 12
Notification Appliance and Releasing Circuits.................................................... 12
Alarm and Trouble Relays ................................................................................... 12
Resettable Power.................................................................................................. 12
Nonresettable Power ............................................................................................ 12
RMS Regulated Power......................................................................................... 12
2. Installation
Cabinet Mounting ..................................................................................................... 13
Removal of Circuit Board.................................................................................... 13
Mounting of Cabinet ............................................................................................ 13
Attaching Conduit................................................................................................ 13
Reinstallation of Circuit Board ............................................................................ 14
Installing Optional Voltmeter/Ammeter................................................................. 15
Power Connections.................................................................................................... 16
AC Connections ................................................................................................... 16
Battery (DC) Connections.................................................................................... 16
Power-limited Wiring Requirements ...................................................................... 17
Initiating Device Circuits.......................................................................................... 18
Four-Wire Smoke Detector Connections............................................................. 19
Output Circuits.......................................................................................................... 20
Notification Appliance Circuits ........................................................................... 20
Releasing Circuits ................................................................................................ 21
Alarm Relay Circuit............................................................................................. 22
Trouble Relay Circuit........................................................................................... 22
Powering External Devices....................................................................................... 22
Optional Modules ...................................................................................................... 23
Overview.............................................................................................................. 23
Installation - Upper Position ................................................................................ 23
Installation - Lower Position................................................................................ 24
Setup and Configuration ...................................................................................... 25
Transmitter Module - 4XTM ........................................................................ 25
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Zone Relay Module - 4XZM ........................................................................ 26
LED Interface Module - 4XLM.................................................................... 27
Setting Mode of Operation ....................................................................................... 28
DIP Switch Functions........................................................................................... 28
Switch #1 - Cross Zone................................................................................. 28
Switch #2 - Supervisory/Releasing Service.................................................. 29
Switch #3 and #4 - Timer Delay................................................................... 29
Switch # 5 and #6 - Abort Function.............................................................. 29
Zone Relay Module Configuration ...................................................................... 30
Power-Up Procedure................................................................................................. 31
3. System Operation
System Status LEDs .................................................................................................. 33
Control Switches........................................................................................................ 34
Zone Status LEDs...................................................................................................... 34
Piezo............................................................................................................................ 35
Supervisory Service................................................................................................... 35
Zone Disable............................................................................................................... 35
Last Event Recall....................................................................................................... 36
Non-Silenceable Service ............................................................................................ 36
Sprinkler Supervisory Tracking .............................................................................. 36
System Events ............................................................................................................ 36
Standby Condition................................................................................................ 36
System Trouble Condition ................................................................................... 36
Single Zone in Alarm (Cross Zone) Condition.................................................... 37
Both Zones in Alarm (Cross Zone) Condition..................................................... 37
Manual Discharge Station Alarm Condition........................................................ 37
Brownout Condition............................................................................................. 37
Appendix A: Secondary Power Calculations
Standby Battery Requirements................................................................................ 39
Calculating the Battery Capacity............................................................................. 40
Appendix B: Compatible Devices
Two-wire Smoke Detectors, UL Listed.................................................................... 41
Four-wire Smoke Detectors, UL Listed................................................................... 42
FM Approved Releasing Devices ............................................................................. 42
Notification Appliances, UL Listed.......................................................................... 43
Door Holders, UL Listed........................................................................................... 45
24 VDC Relays, UL Listed........................................................................................ 45
Appendix C: NFPA Standard-Specific Requirements
Minimum System Requirements.......................................................................... 47
Additional Requirements...................................................................................... 47
NFPA 72 - Signaling Systems for Central Station Service
(Protected Premises Unit)......................................................................... 47
NFPA 72 - Auxiliary Fire Alarm System ..................................................... 47
NFPA 72 - Remote Station Fire Alarm System............................................ 47
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC............................. 48
Universal Digital Alarm Communicator - 411UDAC............................................ 49
Local Energy Municipal Box.................................................................................... 50
Remote Station Receiver - RS82-9........................................................................... 51
Appendix D: Testing & Maintenance
Testing ........................................................................................................................ 53
Inspection ............................................................................................................. 53
Alarm Test............................................................................................................ 53
Maintenance............................................................................................................... 53
Troubleshooting......................................................................................................... 53
6
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Product Description
Overview
The PDRP-1002 Agent Release Control System has been designed as a control center for use in automatic
firesupressionsystems.Thepanelisafeature-packedcontrolunitsuitabletoperformdetectionandcontrol
functions associated with the release of gaseous agent/special hazard fire protection systems. The PDRP-
1002 is designed for maximum reliability with 100% solid state circuitry and isolated relay contacts for
outsideinterfacingandfeaturesprogrammableoptionstoallowon-sitecustomizationoftheunitforvarious
operating configurations.
An integral standby battery system, with charger, is provided. In case of commercial AC power
interruption, automatic switchover to the battery system will provide power to the panel for a minimum
of 24 hours.
The FACP is supplied complete with backbox, hinged door, control switches, and indicator LEDs.
The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm)
conduit knockouts available.
The PDRP-1002 is a 110/120 VAC agent release control panel. The PDRP-1002E is a 220/240 VAC agent
release control panel.
Features
• Microprocessor-controlled
• Last Event Recall
• Power-limited on all circuits except Municipal Box
Output and Releasing Circuits
• Battery /Earth fault supervision
• Current protection on all notification circuits
• RMS regulated output power, 2.25 amps
• Alarm and trouble resound
• Four Style B/D Initiating Device Circuits
• Two Style Y/Z Notification Appliance Circuits
• Two Style Y only Release Circuits
• General alarm and trouble relays
• Delay Timer (adjustable)
• 7 amp-hour (AH) to 18 AH battery options, up to 90
hours standby
• Resettable and nonresettable regulated power
outputs
• Extensive transient protection
• Watchdog timer to supervise microprocessor
• Output circuits protected against false activations
• Slide-in zone identification labels
• Three abort function options
• Abort and manual release circuits
• Designed for supression standards
• Disable/enable controls per Initiating Device Circuit
• Steel cabinet 14.5” (36.83cm) wide by 16.00”
(40.64cm) high by 4.75” (12.07cm) deep
Options
• 4XZM Module for 4 zone/function relays
• Cross-zone option
• 4XTM Transmitter Module - Complies with NFPA
72 Auxiliary and Remote Station Protective
Signaling systems
• Supervisory Input option
• Dead-front dress panel option (DP-4X) (Required
for Canadian applications)
• 4XMM Volt/Amp Meter Module
• Trim ring for flush mount between 16 in. (40.64 cm)
center studs (TR-4XR)
• RZA-4X Supervised remote annunciator (requires
4XLM Interface Module)
• 411UDAC or NOTI•FIRE 911AC Digital
Communicator - Complies with NFPA 72 Central
Station and Remote Station Protective Signaling
systems
Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
7
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Product Description
Circuits
Circuits
Input Circuits
Detector Zone 1 (Style B/D)
Detector Zone 2 (Style B/D)
Abort (Style B/D)
Manual Release (Style B/D)
Note: Optional auxiliary relay module 4XZM tracks these four circuits.
Output circuits
Notification Appliance Circuit 1 (Style Y/Z)
Notification Appliance Circuit 2 (Style Y/Z)
Releasing Circuit 1 (Style Y)
Releasing Circuit 2 (Style Y) / Supervisory Input (StyleB)
Front Panel Control Switches
Switch 1 - Tone Silence
Switch 2 - Alarm Silence
Switch 3 - Alarm Activate
Switch 4 - System Reset
Suplemental Documentation
The table below lists document sources containing additional information regarding the MS-4424:
For information on...
Refer to...
Part Number
Digital Alarm
Communicator/Transmitters
NOTI-FIRE 911A & 911AC
Instruction Manual
74-06200-005
411UDAC Instruction Manual
Fire•Lite RS82-9 Instruction Manual
4X Series Power Meter PID
51073
15400
15396
Remote Station Receiver
Voltmeter/Ammeter
8
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Panel
1. Product Description
Control Panel
Relays
Notification Appliance Circuits
Alarm Contacts
Trouble Contacts
Style Z (Class A) / Style Y (Class B)
Releasing Circuits
Style Y (Class B)
24VDC
Regulated Nonresettable
Regulated Resettable
RMS-Regulated
#1 - Initiating Device Circuit
#2 - Initiating Device Circuit
#3 - Abort Switch
#4 - Manual Release
Style D (Class A) / Style B (Class B)
OU T #1
OU T #2
OU T #3
B+ B–
OU T #4
B+ B–
IN #1
B+ A+ A– B–
IN #2
B+ A+ A– B–
IN #3
IN #4
B+ A+ A– B– B+ A+ A– B–
B+ A+ A– B– B+ A+ A– B–
TB1
TB4
TB3
TB2
JP1
GEN
ALM1
SUPV 1
SUPV 2
GEN
J1
J4
AC PO W ER
ZO NE 1
J5
SYSTEM
ALA RM
RELE ASE
SUPERVISO RY
SYSTEM
TRO UBLE
TB5
OPT1
ABO RT
CIRCUIT
TRO UBLE
J2
ALA RM
SILENCED
AMP
M ANUAL
RELE ASE
PO W ER
TRO UBLE
J9
J3
J10
TONE
ALARM
ALARM
SYSTEM
SILENCE SILENCE ACTIVATE RESET
OPT2
J7
J8
SW 1
MRP4424-board.cdr
SW1 - DIP Switch
Battery Fail LED
J4 - J5 - J7 - J8
Optional Module
Connectors
Micro Fail LED
Ground Fault LED
Figure 1 Control Panel
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
9
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Product Description
DIP Switch Functions
DIP Switch Functions
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode
#1
Cross Zone
Supervisory
Timer
Determines how NACs and Releasing Circuits respond to an alarm.
Selects Releasing Circuit #2 to function as a Supervisory Circuit.
Selects Timer Delay setting.
#2
#3 & #4
#5 & #6
Abort
Selects a variety of abort functions.
functions.
Options
Three optional modules are available for use on the control panel. The control panel provides mounting
slots for two of these optional module boards.
Transmitter Module - 4XTM
TB1
The Transmitter Module provides a supervised output for a Local Energy
Municipal Box transmitter and alarm and trouble reverse polarity circuits for
Remote Station Service. Also included is a DISABLE switch and disable
trouble LED.
Note: As a jumper option, the alarm reverse polarity circuit will open on trouble if no
alarm exists.
TBL
J1
SpecificationsforLocalEnergyMunicipalBoxservice(NFPA72Auxiliary
Fire Alarm System)
J2
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance
power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
Specifications for Remote Station Service (NFPA 72 Remote Station Fire Alarm System)
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
TB1
Zone Relay Module - 4XZM
The Zone Relay module provides Form-C contacts for the following:
• Relay #1 - Alarm Detected / First Alarm
• Relay #2 - Alarm Detected / Second Alarm
• Relay #3 - Release 1 / Release 1
• Relay #4 - Release 2 / Not Used
• Relay #5 - General Alarm
J2
• Relay #6 - System Trouble
Note: As a jumper option, the first four relays can be made silenceable.
DIS ABLE
Specifications
LATCH
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30
VAC (resistive).
10
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Options
1. Product Description
Remote Annunciator - RZA-4X
TheRemoteAnnunciatormountsonastandardsingle-gangbox,andprovides
LED indication of the same functions as the zone relay module. For example,
with DIP switch #1 ‘ON’ and DIP switch #2 ‘OFF’:
• One zone in alarm (red)
• Two zones in alarm (red)
• Releasing Circuit 1 (red)
• Releasing Circuit 2 (red)
• System Trouble (yellow)
S YS TE M TR O U BL E
R E -S O U ND
TO NE
S ILEN CE
FIRE ALARM ANNUNCIATO R
Alocaltroublesounderandsilenceswitcharealso provided. AllLEDwiring
is supervised for open conditions. Any open condition will cause the System
Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The Remote Annunciator requires the use of an LED Interface Module as described below.
LED Interface Module - 4XLM
The LED Interface Module supports the RZA-4X Remote Annunciator
Module. Annunciator wiring is supervised for open conditions by this module.
The module mounts to the main board on the J8 option connector.
Specifications
Maximum voltage/current, each output: 27.6 V / 8 mA.
Outputs are power-limited.
J2
Meter Module (Volts-Amps) - 4XMM
10
20
The Meter Module provides a voltmeter to measure the voltage across the
batteriesand anammetertomeasurethechargingcurrenttothebatteries. The
meters are provided as an assembly that mounts to the lower left-hand corner
of the cabinet.
30
0
DC V OLTS
0
3
3
DC A MPE RES
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
11
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Product Description
Specifications
Specifications
AC Power
PDRP-1002: 110/120 VAC, 50/60 Hz, 1.2 amps
PDRP-1002E: 220/240 VAC, 50/60 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 18 AH.
Note: Batteries larger than 12 AH require Fire•Lite BB-17 or other UL-listed external battery cabinet.
Initiating Device Circuits
Power-limited circuitry
Operation: Style B (Class B) or Style D (Class A)
Normal Operating Voltage: 24 VDC (ripple = 1.0V p-p)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 100 ohms
End-of-Line Resistor: 4.7K, 1/2-Watt (part # 71252 UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including End-of-Line Resistor)
Notification Appliance and Releasing Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-Line Resistor: 4.7K, 1/2-Watt (part # 71252 UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
Note: Any power connected to these relay contacts must come from a power-limited supply. Fail-safe operation
ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power).
Resettable Power
Up to 200 mA is available for powering four-wire smoke detectors. Maximum ripple voltage: 1.0 V p-p.
Nonresettable Power
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke detector
power). Maximum ripple voltage: 1.0 V p-p.
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available
to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.
12
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Cabinet Mounting
Carefully unpack the system and check for shipping damage.
Select a suitable location in a clean, dry, vibration-free environment that is not subject to extreme
temperatures. Locate the top of the cabinet approximately five feet above the floor with the hinge on the
left. The panel must be easily accessible for maintenance; the hinged door requires a minimum clearance
of 14 in. (35.56cm) to open.
Removal of Circuit Board
To prevent damage to the printed circuit board it should be removed prior to mounting of cabinet.
Step Action
1
2
3
Disconnect the transformer wires from the circuit board at the J1
connector.
Remove the four (4) phillips head screws securing circuit board to
backbox rails.
Carefully set board aside in a secure place.
Mounting of Cabinet
Securely mount the cabinet using the mounting holes provided.
Step Action
1
Mark and predrill holes for the top two keyhole mounting screws using the
dimensions shown in Figure 2 on page 14.
2
3
4
5
Install two upper screws in the wall with the heads protruding.
Using the upper keyholes, mount the backbox over the two screws.
Mark and drill the lower two holes.
Secure backbox by installing the remaining fasteners and tightening all
screws.
6
If required, attach optional Trim Ring (TR-4XRF) using the provided
instructions.
Attaching Conduit
Select and remove knockouts according to the number of conduits required.
Attach conduits to backbox as required.
Determine the number of conductors required for the devices to be employed. Pull required conductors
into the box through the knockouts provided.
Note: All wiring should be in accordance with the National and/or Local codes for fire alarm systems, including
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
13
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Cabinet Mounting
The figure below shows the exterior dimensions and mounting hole locations for the cabinet backbox and
dimensions of the optional trim ring:
5.375”
(13.65cm )
14.625”
(37.15cm )
16.125”
(40.96cm )
16.00”
(40.64cm )
4.75”
(12.07cm )
1.00”
(2.54cm )
14.50”
(36.83cm )
12.50”
(31.75cm )
1.00”
(2.54cm )
9.50”
(24.13cm )
1.5”
(3.81cm)
16.125”
(40.96cm)
14.625”
(37.15cm)
Figure 2 Cabinet Mounting Dimensions
Reinstallation of Circuit Board
Reinstall the printed circuit board as follows:
Step Action
1
Position circuit board over stand-offs on backbox rail and secure with four
(4) phillips screws. Tighten securely.
2
Connect transformer wires to J1 connector on circuit board.
14
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing Optional Voltmeter/Ammeter
2. Installation
Installing Optional Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMM Meter Module is required. To install
the power meter module follow the steps below:
Step Action
1
2
Cut the jumper wire labeled “AMP”.
Secure the module to the backbox with the hardware provided. Refer to
Product Installation Drawing (PID) for detailed instructions.
3
4
Connect meter cable P2 to connector J2 on the main circuit board.
Connect meter cable P3 to connector J3 on the main circuit board.
The figure below shows the mounting location and connections for the Voltmeter/Ammeter.
TB5
‘AMP’ Jumper
J2
AMP
J9
J3
10
20
30
0
D C V O LTS
0
3
3
D C A M P E R E S
Figure 3 Mounting and Connecting the Meters
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
15
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Power Connections
Power Connections
WARNING: Do not apply any type power to this control panel until all connections have been
made and verified.
!
AC Connections
Disconnect (open) the circuit breaker in the AC main breaker panel and tag it “Out of Service”.
Primary power required for the PDRP-1002 control panel is 110/120 VAC, 50/60 Hz, 1.2 amps and for
the PDRP-1002E is 220/240 VAC, 50/60 Hz, 0.6 amps.
Overcurrentprotectionforthis circuitmustcomplywithArticle760oftheNationalElectricalCode(NEC)
and/or local codes. Use #14 AWG (2.00 mm2) or larger wire with 600V insulation rating.
A separately fused and protected power connection to the panel should be supplied to prevent voltage
fluctuation and interruption of power.
Ground
Neutral
TB5
Hot
J2
AM P
J9
J3
Figure 4 AC Power Connections
Battery (DC) Connections
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
!
CAUTION: Do NOT connect the battery interconnect wire at this time. Make this connection AFTER
initial system primary power connection.
!
Place batteries into bottom of cabinet as shown below. See "Appendix A: Secondary Power Calculations"
on page 39 for calculation of correct battery rating.
Note: Batteries are shipped separately and should be mounted only after the cabinet has been installed, the conduit
connected, and all wiring pulled, tested, and made ready to be terminated.
Continued on the next page...
16
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Power-limited Wiring Requirements
2. Installation
Observe polarity when connecting the batteries. Connect thebattery cable(p/n 75203 or 75202, depending
on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided.
Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries.
Do NOT connect battery interconnect wire at this time.
TB5
J2
AM P
J9
J3
Figure 5 Battery Installation and Connection
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-
limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass
through separate knockouts and/or conduits.
Power-limited
Circuits
Nonpower-limited
Circuits
Power-limited Circuits
O
B
UT#4
A
L
A
RM
IN
#
A–
1
IN
#
A–
2
IN
#
A–
3
IN
#
A–
4
O
A
UT#1
A–
O
A
UT#2
A–
O
B
T#
B
+
+
B
–
B
+
+
B
B
+
B
–
NO NC
C
B
A
+
B
–
B
A
+
B
–
B
+
A
+
B
–
B
A
+
B
–
TB1
TB4
TB2 TB3
JP1
GEN
ALM1
SUPV
1
TB1
SUPR
2
GEN
J1
TBL
AC
P
OW
E
R
J1
ZON
E
E
E
E
1
2
3
4
SY ST EM
ALAR
M
J2
ALAR
M
T
ES
T
ZON
ZON
ZON
SUPERVISORY
SY ST EM
TR OUBLE
TB5
TB1
CIRC UIT
TR OUBLE
Power-limited
Circuits
J2
ALAR
SIL ENCED
M
AMP
POW ER
TR OUBLE
J9
J3
TONE
ALARM
ALARM
SYSTEM
RESET
SILENCE SILENCE ACTIVATE
Nonpower-limited
Circuits
J2
DISABLE
LATCH
SW
1
AC Power
Figure 6 Power-limited Wiring Requirements
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
17
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Initiating Device Circuits
Initiating Device Circuits
The control panel provides two Initiating Device Circuits (#1 and #2) and they may be configured as either
Style D (Class A) or Style B (Class B). Circuit #3 is designated as an Abort Switch Circuit and Circuit #4
is a Manual Release Circuit.
Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and
Waterflow alarm devices.
• Wire all alarm initiating devices sequentially for proper supervision.
• Observe polarity when connecting polarized devices.
• All circuits are supervised and power-limited.
• Leave dummy load resistor (provided) on all unused circuits.
Style D (Class A)
Initiating Device
Circuit
Heat
Detector
Style B (Class B)
Initiating Device
Circuit
4.7K, 1/2-Watt resistor
PN 71252 (UL listed)
Style B (Class B)
Manual Release
Circuit
Style B (Class B)
Abort Switch
Circuit
Two-wire
Smoke
Detector
Manual
Pull Station
Note: Silk screen printing on circuit board moved to bottom for clarity
Figure 7 Initiating Device Circuits
18
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Initiating Device Circuits
2. Installation
Four-Wire Smoke Detector Connections
A maximumof 200mA is available from the24VDC Resettable Power circuit onTB1 (+24VR terminals).
Any power that is drawn from the 24VDC Nonresettable Power on TB2 (+24VNR terminal) must be
Notes on Style D (Class A) and Style B (Class B) field wiring:
1. The Power Supervision Relay coil leads must be connected to the last detector base 24V screw
terminals.
2. Calculation of the maximum allowable resistance in the 24VDC resettable power wiring:
(20.6 - Vom)
Rmax =
(N x Is) + (Na x Ia) + (Ir)
Where:
Rmax = maximum resistance of the 24 VDC wires
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
4.7K, 1/2-Watt ELR
–
–
+
–
+
–
+
+
Power
Supervision
Relay
24 VDC Four-wire
Smoke Detectors
(A77-716B)
TB4
TB1
IN #1
B + A + A – B –
IN
B + A +
Control Panel
Power Circuit
Style B
Initiating Device Circuit
Figure 8 Typical Connection for Four-Wire Smoke Detectors
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
19
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Output Circuits
Output Circuits
Notification Appliance Circuits
The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits,
which are supervised and power-limited.
Each circuit is capable of 1.5 amps of current. Total current drawn from both NACs and both Releasing
• Unused circuits must be connected with a dummy load as shown.
Style Y
(Class B)
4.7K, 1/2-Watt ELR
(PN 71252)
Style Z
(Class A)
Polarized
Bell
Polarized
Strobe
Unused Style Y Circuit
(4.7K, 1/4-Watt ELR)
Polarized
Horn
TB2
Figure 9 Notification Appliance Circuits
20
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Output Circuits
2. Installation
Releasing Circuits
CAUTION: To prevent accidential discharge, connect releasing devices after initial panel tests are
completed.
!
The control panel provides two Style Y (Class B) Releasing Circuits, which are nonpower-limited.
Circuit #2 can be configured for a Supervisory Circuit (see "Setting Mode of Operation" on page 28) and
will then be power-limited.
Note: All wiring must follow the requirements as specified under "Power-limited Wiring Requirements" on page 17.
Each circuit is capable of 1.5 amps of current. Total current drawn from both Releasing Circuits and both
• UL listed and FM approved releasing devices must be used.
• Unused circuits must be connected with a dummy load as shown.
Releasing
Circuit #1
Releasing
Circuit #2
TB2
Canadian Applications
REL-4.7K
Unused
Releasing
Circuits
TB2
Figure 10 Releasing Circuits
Wiring must be configured to maintain a minimum voltage of 20.4 VDC on releasing Circuits. Calculation
of maximum allowable resistance:
20.6 VDC – 20.4 VDC
Rmax =
Is
Where:
Rmax = maximum allowable resistance of wiring
Is = Solenoid current
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
21
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Powering External Devices
Alarm Relay Circuit
One Form-C dry contact alarm relay is provided in the basic panel for controlling supplementary devices.
Contacts are rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and are non-silenceable when
an alarm occurs.
Trouble Relay Circuit
OneForm-C dry contact troublerelay isprovided in the basicpanelforcontrolling supplementary devices.
It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and will restore to normal when the trouble
condition is cleared.
Note: Power connected to these relay contacts must come from a power-limited supply. Power may be obtained from
TB1 Terminals 24VU or 24VR and TB2 Terminals 24VNR, or a UL-listed power-limited power supply.
TB3
Figure 11 Schematic Representation of Alarm/Trouble Coils & Contacts
Powering External Devices
CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources
of power before servicing. The panel and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while this unit is energized.
!
DC power connections are available from TB1 and TB2 on the control panel as shown below:
TB2
TB1
Nonresettable Power -
RMS-Regulated Power -
24 VDC filtered, nonresettable power
can be drawn from these terminals.
The combined current draws from the
Resettable and Nonresettable outputs
cannot exceed 200 mA.
24 VDC power for inductive-type
devices such as door holders can
be connected to these terminals.
This output is not suitable for
powering devices requiring
filtered DC power.
Resettable Power -
24 VDC filtered, resettable power for four-wire smoke
detectors can be obtained from these terminals.
The combined current draws from the Resettable and
Nonresettable outputs cannot exceed 200 mA.
Figure 12 Power Terminals
22
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules
2. Installation
Optional Modules
Overview
The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules
are available for the panel and they can be used in any combination, including duplicate modules. The
corresponding option jumper must be cut before installation of an optional module, to enable module
supervision.
• The 4XTM Transmitter and 4XZM Zone Relay Modules can be installed in either position.
• The 4XLM Interface Module must be installed in the lower position only.
Installation - Upper Position
To install either the 4XTM or 4XZM module in the upper position follow these instructions:
Step Action
1
2
Cut jumper ‘OPT1’ on main circuit board.
Insert the two stand-offs into the holes located on the right-side edge of the
main board. Secure with nuts and tighten securely.
3
Align the pins of J5 (and J4) connectors on the main board with the
holes on the underside of the J2 (and J1) connector on the optional
board. Carefully press down on the optional board until the pins are
through the connectors and it rests on the stand-offs.
4
5
Secure optional board to stand-offs with screws. Tighten securely.
Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
IN #2
IN #3
IN #4
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–
TB4
TB1
Install Stand-offs here
J2
J4
J5
DISAB LE
LATCH
OPT1
OPT1 - Cut prior to
J10
installation of module
OPT2
J7
J8
Figure 13 Module Installation - Upper Position
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
23
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Optional Modules
Installation - Lower Position
To install either the 4XTM, 4XZM or 4XLM module in the lower position follow these instructions:
Step Action
1
2
Cut jumper ‘OPT2’ on main circuit board.
Remove the lower-right screw securing the main board to the lower rail.
Replace with a stand-off and tighten securely.
3
4
Insert one stand-off into the other hole located on the right-side edge of the
main board. Secure with nut and tighten securely.
Align the pins of J8 (and J7) connectors on the main board with the
holes on the underside of the J2 (and J1) connector on the optional
board. Carefully press down on the optional board until the pins are
through the connectors and it rests on the stand-offs.
5
6
Secure optional board to stand-offs with screws. Tighten securely.
Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
IN #2
B+ A+ A– B–
IN #3
IN #4
B+ A+ A– B– B+ A+ A– B–
TB4
Install Stand-offs here
J4
J5
OPT1
OPT2 - Cut prior to
installation of module
J10
J2
OPT2
J7
J8
Figure 14 Module Installation - Lower Position
24
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules
2. Installation
Setup and Configuration
Transmitter Module - 4XTM
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module
as shown below. Polarities shown in activated positions.
Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
PushingtheDisconnectSwitchdownwillpreventunwantedactivationoftheMunicipalBoxduringtesting
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the
Municipal Box.
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
TB1
+
–
Remote Alarm (Power-limited)
+
–
Remote Trouble (Power-limited)
No Connection
+
–
Municipal Box (Nonpower-limited)
TBL Jumper
TBL
J1
Disconnect LED
Disconnect Switch
J2
Figure 15 4XTM Configuration
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
25
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Optional Modules
Zone Relay Module - 4XZM
Relay #1 through #4 on this module have specific functions based on the configuration of DIP switches
#1 and #2 on the control panel. See “Zone Relay Module Configuration” on page 30 for a more detailed
explaination of the conditions that will activate each relay under the different DIP switch setings.
For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the
relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,
located on the door of the control panel.
TB1
J2
DISABLE
LATCH
“Latch” Jumper
Disable Switch
Figure 16 Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of
dry contacts to maintain the required separation between circuit types.
• Ifthis module is usedto drive both nonpower-limitedandpower-limited relays thatare next to each
other, refer to the figure below which shows the one allowable arrangement.
Power-Limited
Circuit
No Connection
Nonpower-Limited
Circuit
Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits
26
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Modules
2. Installation
LED Interface Module - 4XLM
Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA-
4X Remote Annunciator.
Make wiring connections with system power off.
Maximum wire impedance is 50 ohm per wiring connection.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
+24V
Out #1
Out #2
Out #3
Out #4
Sysyem Trouble
Sound
Resound
J2
Connect to corresponding
terminals of the RZA-4X
Remote Annunciator.
Single-gang
Box
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
FIRE ALARM ANNUNCIATOR
Side View
Front View
Figure 18 Connection of 4XLM to RZA-4X
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
27
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Setting Mode of Operation
Setting Mode of Operation
Select operating mode by setting the SW1 DIP switches as described below; basic programming options
are shown in this section.
After any changes are made to the configuration of the switches, the panel must be reset.
SW 1
Basic Programming
Switch 1: Cross Zone
Switch 2: Supervisory
Delay Timer
Switch 5: Abort Option
Switch 6: Abort Option
Abort Options
Switch 3: Delay Timer
Switch 4: Delay Timer
Figure 19 DIP Switch Settings
DIP Switch Functions
Switch #1 - Cross Zone
Select the desired mode of operation and set switch per appropriate column:
OFF
ON
NAC #1
NAC #2
Activated by an alarm in either
IDC # 1 or IDC #2.
NAC #1
NAC #2
Pre-discharge Alarm - Activated by
the first alarmed zone in the system.
Initiation of an alarm on the other
zone will shut this output off
Activated by an alarm in either
IDC #1 or IDC #2.
Activated when alarms occur on
both IDC #1 or IDC #2.
Note: The NAC will pulse at 60 ppm
while timer is running or frozen by
abort and will sound steady upon
release (time out).
Note: The NAC will pulse at 60 ppm
while timer is running or frozen by
abort and will sound steady upon
release (time out).
REL #1
REL #2
Will be activated when the timer expires (provided that REL #2 is functioning as a
releasing circuit - set via DIP switch #2)
The Releasing Circuit Delay Timer will start
whenever an alarm occurs on either IDC #1 or
IDC #2.
The Releasing Circuit Delay Timer will start
whenever an alarm occurs on both IDC #1 or
IDC #2.
28
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Setting Mode of Operation
Switch #2 - Supervisory/Releasing Service
2. Installation
Set the function of Releasing Circuit #2 by setting this switch.
OFF
ON
REL #2
Will function as a solenoid releasing
circuit.
REL #2
Will function as a supervisory input
circuit.
• A short condition on this circuit
will light the Supervisory LED
and sound the supervisory tone on
the control panel piezo.
Note: This circuit is nonpower-
limited.
• An open condition generates a
circuit trouble condition.
Note: This circuit will now be power-
limited.
Switch #3 and #4 - Timer Delay
Select the desired timer setting and set these switches accordingly.
No Delay*
OFF
10 Second
OFF
20 Second
ON
30 Second
ON
Switch #3
Switch #4
OFF
ON
OFF
ON
* Abort timer will not operate when timer is set for ‘No Delay’.
Switch # 5 and #6 - Abort Function
Select the desired Abort Functions for delaying the activation of releasing circuits, and set these switches
accordingly. If ‘Cross Zone’ is selected, both IDC #1 and IDC #2 must be activated to start timer.
Switch #5
OFF
OFF
OFF
ON
ON
ON
ON
Switch #6
OFF
Standard UL-type
delay timer
IRI-type delay
timer
NYC-type delay
timer
Local Jurisdiction
delay timer
Continues to count
down upon ABORT, but
stops and holds at 10
seconds until release of
the ABORT switch.
Upon release of the
ABORT switch, the
timer resumes the
countdown at 10
Functions the same as
the UL-type timer with
the exception that the
ABORT will function
only if pressed and held
before 2nd zone goes
into alarm.
When an alarm exists,
pressing ABORT
Once the timer has
started, pressing
changes timer value to
the Timer Delay plus 90
seconds. The timer will
not start while ABORT
is held. SYSTEM
RESET restores timer to
origional Timer Delay.
Each time ABORT is
pressed again adds 90
seconds to Timer Deley.
ABORT resets the timer
to full Timer Delay. The
timer will not start
while ABORT is held.
Releasing the ABORT
switch continues the
countdown; pressing
ABORT again restores
Timer Delay to its full
value.
seconds.
These modes are the only ones that
comply with UL Standard 864.
Note: Abort timer will not operate when timer is set for ‘No Delay’. Manual pull station does not use
abort mode.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
29
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Setting Mode of Operation
Zone Relay Module Configuration
Relay #1, #2, #3 and #4 of the the 4XZM Zone Relay Module have specific functions based on the
configuration of DIP Switches #1 and #2 on the control panel. The table below provides a description of
these functions.
DIP #2 is ON (Supervisory)
DIP #1 is OFF
(Either Zone)
DIP #1 is ON
(Cross Zone)\
Either Zone
Cross Zone
Activates when first
alarm is detected in
the system
Relay #1
Same
Activate when alarm
is detected in
Same
Zone #1 or Zone #2
Activates upon
second alarm
Relay #2
Relay #3
Relay #4
Same
Same
Activates when
Release 1 is activated Release 1 is activated
Activates when
Same
Activates when
Release 2 is activated Release 2 is activated
Activates when
Not Used
Not Used
Note: Relay #5 is reserved for General Alarm and Relay #6 is reserved for System Trouble.
30
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Power-Up Procedure
2. Installation
Power-Up Procedure
WARNING: Prior to energizing this panel, notify all personnel and authorities, including any
personnel who may be working on, around, or near this unit.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
!
CAUTION: Observe polarity of batteries. Improper connection will cause damage and VOID
WARRANTY.
!
Follow these steps to power-up the FACP:
1. Conduct Visual Inspection. A careful visual inspection should be made before applying power to
the system. See “Inspection” on page 53.
2. Notification. Notify personnel who may be working with the AC power circuits before removing
the “Out of Service” tag.
3. Apply Primary Power. Switch the circuit breaker to the ‘closed’ position, providing power to the
circuit.
• The green AC power LED will illuminate.
• The Trouble LED will illuminate until battery power is applied.
4. Connect Secondary Power. Connect battery interconnect wire as shown below.
• The trouble LED will clear. If the trouble light does not clear, refer to "Troubleshooting Table" on
Battery Interconnect Wire
Figure 20 Battery Connections
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
31
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Power-Up Procedure
Notes
32
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
3. System Operation
WARNING: When used for CO2 releasing applications, observe proper precautions as stated in
NFPA 12. Do not enter the protected space unless physical lockout and other safety procedures
are fully completed. Do not use software disable functions in the panel as lockout.
!
System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged
(TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
AC P OW E R
ZONE
ZON E
1
2
SYSTEM
ALARM
RELEASE
System
Status
LEDs
SUP ERVISO RY
SYSTEM
TRO UBLE
ABO RT
CIRCUIT
TRO UBLE
ALARM
SILENCE D
M ANU AUL
RELEASE
PO W ER
TRO UBLE
TO N E
ALA RM
ALA RM
SY STE M
R ES ET
SILEN CE SILEN CE AC TIVATE
MICRO
FAIL
BATT EARTH
Figure 21 System Status LEDs
AC Power - Green LED that illuminates steadily to indicate presence of AC power.
System Alarm - Red LED that flashes when an alarm occurs.
Release - Red LED that illuminates steadily when release occurs.
Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch)
on Zone 4.
System Trouble - Yellow LED that flashes for any trouble condition, including those associated with
optional boards.
Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits (notification and
releasing).
Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
The following LEDs are located below the main panel and are visible only when the panel door is open.
Battery Fail (BATT) - Yellow LED that illuminates steadily on motherboard when battery is low or not
detected.
Ground Fault (EARTH) - Yellow LED that illuminates steadily on motherboard during a ground fault
condition.
Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor
failure.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
33
Download from Www.Somanuals.com. All Manuals Search And Download.
3. System Operation
Control Switches
Control Switches
TO N E
A LA RM
A LA RM
S YS TE M
R E S ET
S ILE N CE S ILE N CE A C TIVATE
Figure 22 Control Panel Switches
Tone Silence - Pressing this switch acknowledges alarms, troubles and supervisories. The panel has
alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate
steadily and the piezo turns off. A second trouble will resound the piezo. Trouble conditions are self-
restoring. Alarms latch and require pressing SYSTEM RESET to clear. Unless the unit is set for non-
latchingsupervisoryservice,supervisorieslatchandrequirepressingSYSTEMRESETtoclear. Thepiezo
Alarm Silence - Pressing this switch acknowledges for alarms and supervisories. This switch will
silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits.
The “Alarm Silenced” LED will illuminate. Alarm silence is a latching function and requires pressing
SYSTEM RESET to clear.
Alarm Activate - This switch may be used to activate Notification Appliance Circuits (NACs). It also
activates the System Alarm Relay. This is a latching function. Pressing ALARM SILENCE silences the
NACs and System Alarm Relay, and lights the Alarm Silenced LED. Pressing SYSTEM RESET returns
the system to normal.
System Reset - This switch breaks power to all initiating circuits, four-wire smoke detector power and
optional boards and will clear any activated output circuits. If any alarm or trouble still exists after reset,
they will reactivate the panel. Holding SYSTEM RESET down will perform a LAMP TEST function and
will activate the piezo sounder.
Zone Status LEDs
The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM
SILENCE), at which point the LED(s) will illuminate steadily.
ZONE 1
Alarm LED
ZONE 2
Trouble LED
ABORT
MANUAL
RELEASE
Figure 23 Zone Status LEDs
34
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Piezo
3. System Operation
Piezo
The piezo (local buzzer) generates different tone patterns for different event conditions:
• Alarm - Generates a steady tone, no pulse.
• Trouble - Pulses one second on, one second off. Repeats 30 pulses per minute.
• Supervisory - Pulses one-half second on, one-half second off. Repeats 60 pulses per minute.
Supervisory Service
Releasing circuit #2 can be used as an input for monitoring supervisory devices (such as valve tamper
switches) by setting SW1 DIP switch 2 to “ON” (see "Setting Mode of Operation" on page 28). After the
panel is programmed for supervisory service, a short circuit on this input (activation of a N.O. contact)
will cause the supervisory LED to flash. The piezo sounder will generate a unique sound. Pressing TONE
SILENCEwillsilencethepiezo and causethesupervisory LEDtoilluminatesteadily. Supervisory signals
latch and require SYSTEM RESET to clear. An open circuit will be reported as a circuit trouble.
Note: The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching
operation is the default setting. Canadian regulations require latching operation; for programming instructions, see
Zone Disable
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the piezo
or any output circuit. If both power sources are removed from the system, all zones will be re-enabled upon
restoration of power. Disable status will be lost.
The Zone Disable routine makes use of the four panel
switches as follows: I
TO N E
A LARM
A LARM
S YS TE M
R E SE T
S ILE N CE S ILE N CE A C TIVATE
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press
(in sequence) the ALARM SILENCE switch, the
ALARM ACTIVATE switch, and then the
SYSTEM RESET switch.
Press
&
Hold
Press ---> Press ---> Press
3. The Zone 1 Alarm LED will flash.
4. To disable Zone 1, press the SYSTEM RESET switch. The Zone 1 yellow LED will light to show
that the zone is disabled.
Note: The SYSTEM RESET switch toggles disable status for the selected zone.
5. To select the next zone, press the ALARM SILENCE switch.
6. To select the previous zone, press the ALARM ACTIVATE switch.
7. When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
35
Download from Www.Somanuals.com. All Manuals Search And Download.
3. System Operation
Last Event Recall
Last Event Recall
Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use
of the four panel switches as follows:
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press (in sequence) the SYSTEM RESET switch, the
ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3. LEDs will light to indicate the last event recorded in the panel’s buffer.
4. Release the TONE SILENCE switch to return to normal operation.
To clear the Last Event buffer, press SYSTEM RESET twice.
Non-Silenceable Service
Notification Appliance Circuit #1 can be programmed as non-silenceable by following these steps:
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then
the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.
3. Release the TONE SILENCE switch.
Note: If both primary and secondary power sources are removed from the system, these settings will be lost. When
power is restored, Notification Appliance Circuit #1 will default to silenceable operation.
Sprinkler Supervisory Tracking
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation;
latching operation is the default setting. Canadian regulations require latching operation.
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then
the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.
3. Release the TONE SILENCE switch.
Note: If both primary and secondary power sources are removed from the system, this setting will be lost. When
power is restored, supervisory will default to latching operation.
System Events
Standby Condition
Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.
System Trouble Condition
Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The
Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off,
and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will
remain in the trouble state until the trouble condition has been cleared and the panel reset.
36
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
System Events
3. System Operation
Single Zone in Alarm (Cross Zone) Condition
Upon actuation of a single-zone initiating device, a red alarm LED will illuminate to indicate whether
Zone 1 or Zone 2 is in alarm.
In addition to the LED, a single-zone alarm will activate the Alarm Relay; the piezo and NAC #1 will start
sounding. In alarm condition, the piezo will generate a steady tone. The piezo can be silenced by pressing
the trouble silence switch. If the fire is extinguished before a second zone alarm is activated, return the
system to normal standby condition by pressing the reset switch inside the panel and holding it for three
(3) seconds.
Both Zones in Alarm (Cross Zone) Condition
When the first alarm occurs, the panel will function as described above.
Upon the occurrence of a second alarm, NAC #1 will de-energize. The second alarm LED will illuminate,
and NAC #2 will energize. At the same time, the predischarge timer will be activated. At the end of the
timer cycle the solenoid valve(s) will be energized to release the suppressant agent.
Manual Discharge Station Alarm Condition
Manual discharge does not use the predischarge timer. If a manual station is used to initiate the alarm
condition, the following will take place:
• NAC #2 and the piezzo will be activated. (In alarm condition, the piezo will generate a steady tone.)
• Alarm Relay will be activated.
• The solenoid valve(s) will activate.
Brownout Condition
The total power being provided to the system’s power supply should not exceed the current draw during
fully loaded panel operation. Brownout circuitry annunciates degradation of the incoming AC voltage
supply. Abrownout condition is annunciated when theAC power decreases. When thebrownout threshold
is reached, the system reacts as if AC power is totally lost:
• Battery backup begins supplying power to operate the control panel
• General Trouble Relay contact transfers
• Green AC Power LED turns off
• Yellow System Trouble LED illuminates
• The piezo will sound one second on, one second off, and repeat until the Trouble is cleared.
When the AC voltage returns or increases above the brownout threshold, the green AC Power LED will
illuminate. The power supply circuitry will return to primary power functions and begin to recharge the
backup battery supply.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
37
Download from Www.Somanuals.com. All Manuals Search And Download.
3. System Operation
System Events
Notes
38
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A: Secondary Power Calculations
Standby Battery Requirements
The Standby Battery Current obtained in the table below represents the amount of current that must be
supplied by the secondary power source (batteries) to sustain control panel operation for one hour.
Note: The control panel will support the installation of one or two optional modules, including two of the same type of
module. Only one 4XLMF can be included in this count.
# of
Devices
Current
(amps)
Total Current
(amps)
Device Type
Main Circuit Board
1
X
X
0.088
0.008
=
=
0.088
4XZM
ZoneRelay Module
[
[
]
]
X
0.011
=
4XTM
Transmitter Module
• Reverse Polarity
Alarm output
[
[
[
]
]
]
X
X
X
X
X
X
X
X
0.005
0.005
0.019
0.001
1
=
=
=
=
=
=
=
=
• Reverse Polarity
Trouble output
RZA-4X/4XLM
Remote Annunciator
(1 max)
4XMM
Meter Module
[
[
[
[
[
]
]
]
]
]
2-wire
Detector Heads
[
[
]
4-wire
Detector Heads
]
2
[
]
End-of-line Relays
Current Draw from
[
]
3
TB2 (nonalarm)
Standby Battery Current
=
amps
2. Must use compatible listed Power Supervision Relay.
3. The total standby current must include both the resettable (TB1 - +24VR terminals) and
nonresettable (TB2 - +24VNR terminals) power. Caution must be taken to ensure that current
drawn from these outputs during alarm does not exceed maximum ratings specified.
Table 1 Standby Battery Current
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A: Secondary Power Calculations
Calculating the Battery Capacity
Calculating the Battery Capacity
Use this table to determine the battery capacity required by the system.
Standby Battery Current
Required Standby Time in Hours
1
2
3
Standby
Amp Hours
(typically 24 , 60 or 90 hours)
] hrs
[
] amps
X
=
[
Enter:
4
0.25 for 5 minutes in alarm, or
0.50 for 10 minutes in alarm
Alarm
Amp Hours
Total Standby and Alarm Load
Multiply by derating factor
Battery size required in AH
+
X
=
1.2
1. NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24 hours of standby time.
2. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby time.
3. Factory Mutual Systems require 90 hours of standby for releasing service.
4. Alarm AH assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 AH) or for 10 minutes (0.5AH).
Table 2 Amp Hour Calculations
The battery charger in this panel will charge a maximum of 18 AH of batteries within 48 hours (7 AH
minimum). Batteries larger than 12 AH will require a UL-listed battery cabinet (e.g. BB-17).
Select a battery with an equal or greater AH rating than the value obtained in the table above.
Note: Batteries must be lead-acid type.
40
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Compatible Devices
Two-wire Smoke Detectors, UL Listed
Use the two-wire detectors listed below.
Standby
Identifier Current
(mA)
Detector
Identifier
Model
Base
Model
Detectors
per Zone
Type
System Sensor 1400
System Sensor 1451
A
A
Ionization
Ionization
n/a
n/a
A
0.10
0.12
20
B401/B401B/
B406B
15/15/1
System Sensor 1851DH
System Sensor 2400
A
A
A
Ionization
DH1851DC
A
0.12
0.12
0.12
15
15
15
Photoelectric
n/a
n/a
n/a
n/a
System Sensor 2400AIT
Photo/
Isolated
Thermal/Horn
System Sensor 2400AT
System Sensor 2400TH
System Sensor 2451
A
A
A
A
Photo/
Thermal/Horn
n/a
n/a
n/a
n/a
A
0.12
0.12
0.12
0.12
15
Photo/
Thermal
15
Photoelectric B401/B401B/
B406B
15/15/1
15/15/1
System Sensor 2451TH
Photo/
Thermal
B401/B401B/
B406B
A
System Sensor 2851DH
System Sensor 1451DH
System Sensor 2451
A
A
A
A
Photoelectric DH2851DC
A
A
0.12
0.12
0.12
0.12
15
15
15
15
Ionization
DH400
DH400
n/a
Photoelectric
A
System Sensor 2300T
Photo/
n/a
Thermal
System Sensor 1800
System Sensor 1851B
System Sensor 1851B
System Sensor 2800
System Sensor 2800TH
A
A
A
A
A
Ionization
Ionization
n/a
B101B
B107B
n/a
n/a
A
0.12
0.12
0.12
0.12
0.12
n/a
n/a
n/a
n/a
n/a
Ionization
A
Photoelectric
n/a
n/a
Photo/
n/a
Thermal
System Sensor 2851B
System Sensor 2851B
System Sensor 2851BTH
A
A
A
Photoelectric
Photoelectric
B101B
B107B
B101B
A
A
A
0.12
0.12
0.12
n/a
n/a
n/a
Photo/
Thermal
System Sensor 2851BTH
System Sensor 1151
A
A
Photo/
Thermal
B107B
A
A
0.12
0.12
n/a
Ionization
B401/
B110LP/
B116LP
15/15/1
System Sensor 2151
A
Photoelectric
B401/
B110LP/
B116LP
A
0.12
15/15/1
Table 3 Two-wire Smoke Detectors
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Compatible Devices
Four-wire Smoke Detectors, UL Listed
Four-wire Smoke Detectors, UL Listed
Use the four-wire detectors listed below.
Max Standby Max Alarm
Current (mA) Current (mA)
Detector/Base
Type
System Sensor 2424
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Ionization
0.10
0.10
41
41
System Sensor 2424TH
System Sensor 2451
0.10
39
System Sensor 2451TH w/B402 Base
System Sensor 1424
0.10
39
0.10
41
System Sensor 1451 w/B402 Base
System Sensor 2412
Ionization
0.10
39
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Base
0.12
77
System Sensor 2412AT
System Sensor 2412TH
System Sensor 2312/24TB
System Sensor B112LP
System Sensor B114LP
System Sensor B404B
0.12
58
0.12
77
0.12
50
See Note
See Note
See Note
10
39
Base
75
Base
See Note
28.4
95
System Sensor 6424
Projected Beam
Ionization Duct
Photoelectric Duct
Ionization
System Sensor DH400ACDCI
System Sensor DH400ACDCP
System Sensor 1112/24
System Sensor 2112/24
System Sensor 2112/24B
System Sensor 2112/24T
25
25
95
0.05
50
Photoelectric
Photoelectric
0.05
50
0.05
65
Photoelectric w/135°
Thermal
0.05
50
System Sensor 2112/24TSRB
Photoelectric w/135°
15
45
Thermal Supervisory Relay
Note: Contact manufacturer for currents.
Table 4 Four-wire Smoke Detectors
FM Approved Releasing Devices
(System Sensor’s PDRP-1002/PDRP-1002E)
Note: Refer to the FM approval guide for automatic water control valves which are compatible with solenoids listed.
Manufacturer
Model
Voltage
Watts Amps
NPS
Orfice
Solenoid Group A
Skinner
LV2LBX25
24 VDC
11
458 mA
1/2”
5/8”
Solenoid Group B
These valves are interchangeable
ASCO
T8210A107
R8210A107
8210A107
24 VDC
24 VDC
24 VDC
16.8
16.8
16.8
700 mA
700 mA
700 mA
1/2”
1/2”
1/2”
5/8”
5/8”
5/8”
ASCO
ASCO
Solenoid Group C
Star Sprinkler Corp.
Kidde-Fenwal
Kidde-Fenwal
Kidde-Fenwal
Kidde-Fenwal
p/n 5550
p/n 890181
p/n 899175
p/n 48650001
p/n 897494
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
part of Model D Deluge Valve
2.0
2.0
0.2
33.0
1.5
Table 5 Solenoid Release Valves
42
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Notification Appliances, UL Listed
Appendix B: Compatible Devices
Notification Appliances, UL Listed
Control panels suppling Special Application (FWR, Filtered) power must use the Notification Appliances
listed below.
• Rated Voltage is nominal operating voltage
• All currents are in millamperes and worst case average.
Rated
Voltage
FWR Filtered
Product
DC
DC
System Sensor MA-12/24D Electronic Sounder
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
73
*
46
30
System Sensor SS24 Strobe
System Sensor SS24LO Strobe
45
25
System Sensor SS24LOC Ceiling Strobe (SS24LOBC - beige)
System Sensor SS24M Strobe
45
25
125
125
118
118
118
118
198
198
*
75
System Sensor SS24MC Ceiling Strobe
75
System Sensor MASS24D Electronic Sounder/Strobe
System Sensor MASS24LO Electronic Sounder/Strobe
System Sensor MASS24LOC Electronic Ceiling Sounder/Strobe
System Sensor MASS24LOLA Electronic Sounder/Strobe w/Fuego lens
System Sensor MASS24M Electronic Sounder/Strobe
System Sensor MASS24MC Electronic Ceiling Sounder/Strobe
System Sensor PA400R Sounder
71
71
71
71
121
121
15
System Sensor PS24LO Add-on Strobe
45
25
System Sensor SS2415ADA Signaling Strobe
90
75
System Sensor SS2475ADA Signaling Strobe
200
245
120
125
180
163
273
318
193
163
193
110
135
240
135
90
170
210
93
System Sensor SS24110ADA Signaling Strobe
System Sensor SS241575ADA Signaling Strobe
System Sensor SS2415ADAS Signaling Strobe with Synch. Circuit
System Sensor SS241575ADAS Signaling Strobe with Synch. Circuit
System Sensor MASS24110ADA Sounder/Signaling Strobe
System Sensor MASS2475ADA Sounder/Signaling Strobe
System Sensor MASS24110ADA Sounder/Signaling Strobe
System Sensor MASS241575ADA Sounder/Signaling Strobe
System Sensor MASS24110ADAS Sounder/Signaling Strobe w/Sync. Ckt.
System Sensor MASS241575ADAS Sounder/Signaling Strobe w/Sync. Ckt.
System Sensor PS2415ADA Mini-Sounder/Strobe
System Sensor PS2475ADA Mini-Sounder/Strobe
System Sensor PS24110ADA Mini-Sounder/Strobe
System Sensor PS241575ADA Mini-Sounder/Strobe
System Sensor SP1R2415ADA Speaker/Signaling Strobe
System Sensor SP1R2475ADA Speaker/Signaling Strobe
System Sensor SP1R24110ADA Speaker/Signaling Strobe
System Sensor SP1R241575ADA Speaker/Signaling Strobe
System Sensor V4R2415ADA Speaker/Signaling Strobe
System Sensor V4R2475ADA Speaker/Signaling Strobe
System Sensor V4R24110ADA Speaker/Signaling Strobe
System Sensor V4R241575ADA Speaker/Signaling Strobe
System Sensor SP100W24LOC Ceiling Speaker/Strobe, 8” round grill
System Sensor SP101R24LO Speaker/Strobe, 5” square grill
106
115
121
216
256
139
121
139
90
108
225
108
75
200
245
120
90
170
210
93
75
200
245
120
45
170
210
93
25
45
25
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Compatible Devices
Notification Appliances, UL Listed
Rated
Voltage
FWR Filtered
Product
DC
DC
System Sensor SP101R24M Speaker/Strobe, 5” square grill
24VDC
24VDC
125
125
75
75
System Sensor SP100W24MC Ceiling Speaker/Strobe, 8” round grill
System Sensor MA12/24EH Multi Alert Horn with Mechanical Tone
12VDC/
24VDC
20/64
38/43
System Sensor MAEH24LO Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH24LOC Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH24LOLA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH24M Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH24MC Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH1215ADA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH121575ADA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH2415ADA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH2475ADA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH241575ADA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH24110ADA Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone/Strobe
System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical Tone/Strobe
System Sensor H12 SpectrAlert Horn
24VDC
24VDC
24VDC
24VDC
24VDC
12VDC
12VDC
24VDC
24VDC
24VDC
24VDC
24VDC
24VDC
12VDC
24VDC
12VDC
12VDC
24VDC
24VDC
24VDC
24VDC
12VDC
12VDC
24VDC
24VDC
24VDC
24VDC
12VDC
12VDC
24VDC
24VDC
24VDC
24VDC
109
109
153
189
189
240
310
278
273
343
318
198
253
25
68
68
96
118
118
191
246
216
216
271
256
152
241
14
System Sensor H24 SpectrAlert Horn1
42
37
System Sensor S1215 SpectrAlert Strobe
159
182
142
132
170
220
173
196
165
177
215
265
200
240
90
133
168
83
System Sensor S121575 SpectrAlert Strobe
System Sensor S2415 SpectrAlert Strobe1
System Sensor S241575 SpectrAlert Strobe1
System Sensor S2475 SpectrAlert Strobe1
76
145
169
144
179
94
System Sensor S24110 SpectrAlert Strobe1
System Sensor P1215 SpectrAlert Horn/Strobe
System Sensor P121575 SpectrAlert Horn/Strobe
System Sensor P2415 SpectrAlert Horn/Strobe1
System Sensor P241575 SpectrAlert Horn/Strobe1
111
180
214
170
255
75
System Sensor P2475 SpectrAlert Horn/Strobe
System Sensor P24110 SpectrAlert Strobe1
System Sensor RP1215ADAA Retrofit Strobe Plate
System Sensor RP121575ADAA Retrofit Strobe Plate
System Sensor RP2415ADAA Retrofit Strobe Plate
System Sensor RP241575ADAA Retrofit Strobe Plate
120
200
245
93
System Sensor RP2475ADAA Retrofit Strobe Plate
170
210
System Sensor RP24110ADAA Retrofit Strobe Plate
Note 1: Refer to manufacturer’s installation instructions for more information
* Contact manufacturer for currents.
Table 6 Notification Appliances
44
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Door Holders, UL Listed
Appendix B: Compatible Devices
Door Holders, UL Listed
Use the Door Holders listed below.
Current
(mA)
Model
Type
FM-980-24
FM-986-24
FM-998-24
Floor Mount, Single
68
68
68
Wall Mount, Surface Wiring
Wall Mount, Concealed Wiring
Table 7 Door Holders
24 VDC Relays, UL Listed
Use the Relays listed below.
Current
(mA)
Vendor
Model
System Sensor
Air Products & Controls, LTD
A77-716B
20
MR-101/C
MR-201/C
15
35
Table 8 24 VDC Relays
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Compatible Devices
24 VDC Relays, UL Listed
Notes
46
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix C: NFPA Standard-Specific Requirements
Minimum System Requirements
The control panel has been designed for use in commercial, industrial, and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
• Fire Alarm Control Panel. Contains the main control board, cabinet (backbox and door), main
supply transformer and power supply.
• Initiating Devices. Connected to one of the control panel's Initiating Device Circuits.
• Notification Appliances. Connected to one of the control panel's Notification Appliance Circuits.
• Releasing Devices. Connected to one of the control panel’s Releasing Circuits.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA standards listed below. The
relaycontactsofthiscontrolpanelmaybeusedtotripanydialerthatisULlistedforCentralStation/Remote
Station services. The illustrations in this appendix provide examples of possible system configurations.
Note: Applications which require the the NOTI-FIRE 911AC are not FM approved.
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
• NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter (DACT) connected to a
• 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central
- 411UDAC" on page 49 for installation instructions for this unit.
NFPA 72 - Auxiliary Fire Alarm System
• 4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
NFPA 72 - Remote Station Fire Alarm System
• Fire•Lite RS82-9 Remote Station Receiver connected to a 4XTM Transmitter Module. See
"Remote Station Receiver - RS82-9" on page 51 for installation instructions for this unit.
Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 48 for installation instructions for
this unit
• 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central
installation instructions for this unit.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix C: NFPA Standard-Specific Requirements Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Note: This application is not FM approved
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises
Receiving Unit.
• AC Wiring for DACT/FACP must be connected to the same circuit.
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less
than 20 ft. (609.6 cm) in length in the same room.
• For additional information refer to the Noti-Fire 911AC Instruction manual.
See Below for Terminal
Connections
To Central
Station
PS 1270
12Volt
7AH Battery
+
To AC Power
–
Control Panel
IN #1
IN #2
IN #3
IN #4
B+ A+ A– B–
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–
TB4
TB3
4XZM Zone
Relay Module
TB1
JP1
SUPV
1
SUPR
2
J2
DISABLE
LATC H
STD DACT
OPT1
To Common
Terminal of Relay
Jumper
TB3
Place jumper over pins as shown when employing
a DACT. This directs the control panel to transmit
all trouble conditions except AC LOSS.
Figure 24 DACT Connections
48
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Universal Digital Alarm Communicator - 411UDAC
Appendix C: NFPA Standard-Specific Requirements
Universal Digital Alarm Communicator - 411UDAC
The following figure illustrates an example of Central Station/Remote Station Receiver or Protected
Premises Receiving Unit reporting using a 411UDAC. The relay contacts of the PDRP-1002 may be used
to trip any dialer listed for Central Station/Remote Station services. For additional information refer to the
Instruction Manual for the 411UDAC.
• All connections between the control panel and the 411UDAC must be in conduit, less than 20 feet
(6.1 meters) in length in the same room.
• The PDRP-1002 is non suitable for transmission of a supervisory signal to the DACT.
• Any zone of the 411UDAC can be wired to function as alarm or trouble; the unit must be
programmed accordingly. Inthis example, Zone 1 is wired to thecontrol panel’s alarm relay, Zone2
iswiredtothecontrolpanel’stroublerelay,andZone3iswiredtotheoptionalmodule’ssupervisory
relay.
• AC power is supplied directly to the 411UDAC, not through the control panel. AC wiring for both
the 411UDAC and the control panel must be connected to the same AC branch circuit.
• End-of-Line Resistors must terminate all circuits. In this example, Zone 4 is unused and is
terminated at the board.
• When employing a DACT, place the JP1 jumper, on the control panel, as shown below. This directs
the panel to transmit all trouble conditions except AC LOSS. The DACT must be configured to
transmit AC power loss to the central station.
Zone 1
Zone 2
Zone 3
Secondary Phone Line
Primary Phone Line
Alarm
Trouble
Control Panel
RELAY
NO NC
1
RELAY
NO NC
2
+12V PWR ZONE
1
ZONE
2
ZONE
3
ZONE
4
NAC
C
C
B+ B-
+
-
B+ B- B+ B- B+ A+ A- BB+ B
T B 4
T B 1
T B 2
P H 1
P H 2
Modular Cable
P/N MCBL-6
411 UDAC
Supervisory
4XZM Zone
Relay Module
Jumper
Figure 25 411UDAC Connections
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix C: NFPA Standard-Specific Requirements
Local Energy Municipal Box
Local Energy Municipal Box
Using the 4XTM Transmitter Module for connection to a Local Energy Municipal Box.
• The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for
direct short between two wires. It is not a power-limited circuit.
• This application is not suitable for separate transmission of sprinkler supervisory or trouble
conditions.
• Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.
FIRE
Municipal Box Circuit
+
–
TB1
Local Energy
Municipal Box
TBL
J1
J2
4XTM Transmitter Module
(activated polarities shown)
Figure 26 Municipal Box Connection
50
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Remote Station Receiver - RS82-9
Appendix C: NFPA Standard-Specific Requirements
Remote Station Receiver - RS82-9
Using the 4XTM Transmitter Module for connection to a Fire•Lite RS82-9 Remote Station Receiver.
• Intended for connection to a polarity reversal circuit of a remote station receiving unit having
compatible ratings.
• All connections are power-limited and supervised with the exception of the reverse polarity loop.
• Supervision of the loop is the responsibility of the receiver.
Fire•Lite RS82-9
Remote Station
Receiver
+
–
+
–
Remote
Alarm
TB1
Remote
Trouble
4XTM Transmitter
Module
TBL
J1
J2
Figure 27 RS82-9 Connections
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix C: NFPA Standard-Specific Requirements
Remote Station Receiver - RS82-9
Notes
52
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix D: Testing & Maintenance
Testing
Inspection
Perform the following prior to applying power to the system.
• Check the actual wiring hookup with the wiring diagrams.
• Insure that no pieces of wire have fallen into the circuitry.
• Check for missing or damaged parts.
Alarm Test
An initial alarm test should be conducted following installation to determine that all parts of the system
are functioning properly. The panels should remain powered for 24 to 36 hours proir to connecting the
releasingsolenoids.Thisprecautionwillavoidfalsedischargesofgasincaseoffaultyorimproperlyplaced
detectors.
To perform an alarm test on the panel follow this procedure
1. Disconnect AC power and battery power.
2. Disconnect the installed solenoid valve circuit leads an connect spare solenoid valves, or connect
an end-of-line device to serve as a dummy load.
3. Reconnect AC power and battery power.
4. Initiate a first zone alarm condition by blowing smoke into one of the Zone 1 smoke detectors. This
should cause the first zone alarm condition.
• The alarm relay will energize.
• The red zone alarm LED will be illuminated.
• The remote Indicating Circuit #1 audible alarm and the local piezo will start sounding.
Maintenance
A regular schedule of inspection, testing, and maintenance is vital to insure proper and reliable operation
of the control panel. The procedures should be performed as required by the local authority having
jurisdiction. Refer to NFPA for further details.
Troubleshooting
A troubleshooting table is included on the following page which provides for symptoms, problems and
their solutions.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix D: Testing & Maintenance
Troubleshooting
Table 9 Troubleshooting Table
Symptom
Problem
Solution
1. Check TB2 for proper connections.
2. Remove all field wiring and install dummy ELR at
output circuit. Check for supervisory voltage across it,
(Normal -2.3 V), if problem persists, replace circuit
board.
Circuit trouble Notification appliance circuit
LED ON
trouble
3. Removed dummy ELR, reconnect field wiring and
measure voltage across output; (trouble-5V, short 0V).
4. Check for ELR at last device.
5. Check field wiring.
1. Check TB4 for proper connections.
2. Remove field wiring for zone in trouble and install
dummy ELR (4.7K). If problem persists, replace
circuit board.
Any of the right
column yellow
LEDs flashing
Initiating zone open circuit
trouble
3. Check for ELR at last device.
4. Check field wiring.
1. Check installation manual.
Any of the right
column yellow
LEDs steady
ON
Zone disable
System trouble
LED ON
1. Check battery connections.
Missing or
Disconnected
1. Remove batteries, check voltage across charger
output (17 to 19V), otherwise replace circuit board.
Battery trouble
Batt yellow
LED ON
Low or
damaged
battery
2. Reconnect batteries, measure battery voltage at
battery terminals. If voltage is less than 85% of rated
voltage, allow them to charge for 48 hours.
Power trouble
LED ON
AC
3. If problem persists, replace batteries.
Power
LED ON
1. Remove field wiring from main panel and optional
module(s) (if installed). Install dummy ELR (4.7K).
2. Remove both battery leads.
Ground fault trouble
Earth yellow LED ON
3. If trouble clears, connect one circuit at the time to
pin point the problem.
4. If trouble doesn’t clear, replace circuit board.
1. Move Municipal Box disconnect switch SW1 up.
Yellow LED on
4XTM ON
4XTM
1. Install optional module(s) or replace jumper if
module(s) is not used.
OPT1, OPT2 jumper cut
1. Install dummy load if Municipal Box option isn’t
used.
Municipal Box open circuit
2. Check Municipal Box wiring.
1. Remove field wiring and install ELR. If trouble
clears, look for faulty or incorrectly wired devices.
Any of the right column red LEDs
ON
Short on initiating circuit wiring
1. Cut associated jumper OPT1 or OPT2.
Disconnecting Municipal Box
switch ON 4XTM does not create
a trouble
Jumper for optional modules
isn’t cut
1. Make sure module is properly installed.
4XZM: associated LED doesn’t
activate for alarm, trouble or
supervisory conditions
Optional module trouble
2. Move disable switch SW1 on 4XZM to the left.
1. Make sure that 4XLM module is installed on J8.
2. Check field wiring.
RZA-4X piezo doesn’t sound for
alarm, trouble or supervisory
conditions
4XLM
1. Replace circuit board.
1. Press system reset.
Micro Fail yellow LED ON
Microprocessor damaged
Power wasn’t removed prior to
installation
All RZA-4X LEDs stay ON
1. Check incoming power (TB5).
1. Replace circuit board.
Loss of main power
AC
Power
LED OFF
System trouble LED ON
Damaged circuit breaker
Microprocessor damaged
1. Replace circuit board.
Micro Fail yellow LED ON
54
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
Index
circuit breaker 16
CO2 releasing applications 33
conductors 13
Numerics
110/120 VAC 12
220/240 VAC 12
411UDAC 47, 49
conduit 13, 49
configuration, Zone Relay Module 30
Cross Zone 28, 37
current 12, 21
4XLM LED Interface Module 11, 23
4XMM Meter Module 11, 15
4XTM Transmitter Module 10, 23, 47
4XTMF Transmitter Module 50, 51
4XZM Zone Relay Module 10, 23
4XZMF Zone Relay Module 30
911AC DACT 47, 48
current draw 37
D
DC power connections 22
de-energize 37
delay timers 29
A
detector, four-wire smoke 34
detectors, type of 18
devices 21
devices, supplementary 22
dialer 47, 49
DIP switch 20, 26, 28, 35
DIP Switch #1 28, 30
DIP Switch #2 29, 30
DIP Switch #3 & #4 29
DIP Switch #5 & #6 29
DIP switch functions 10
direct short 50
Abort Function 29
Abort Switch Circuit 18
Abort timer 29
AC branch circuit 49
AC power 33, 49, 53
accidential discharge 21
acknowledge 34
activation 29
additional equipment 47
alarm 33, 49
Alarm Relay 37
alarm relay 22, 53
allowable resistance 19
ammeter 11
disable switch 26
disabled zone 35
discharge, accidential 21
Disconnect LED 25
Disconnect Switch 25
dry contacts 26
dummy load 20, 21
dummy load resistor 18
duplicate modules 23
annunciator wiring 11
audible alarm 53
authority having jurisdiction 53
B
backbox 13
backbox rail 13, 14
Batteries 16, 47
battery
E
earth fault 33
cable 17
capacity 40
ELR 19, 20
End-of-Line Resistor 12, 49
energize 37
event 33
charger 40
interconnect wire 16, 17
power 53
exterior dimensions 14
external battery cabinet 12
external devices 12
BB-17 12, 40
black wire 17
Brownout circuitry 37
buffer 36
F
Fire Alarm Control Panel 47
first alarm 37
C
Canadian 28, 35, 36
Central Station 47, 48, 49
charging current 15
circuit
first zone 53
FM approved 47, 48
Form-C contacts 10, 12
four-wire smoke detector 12, 34
Remote Alarm 25
Remote Trouble 25
reverse polarity 10
circuit board 13
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
Meter Module 11, 15
microprocessor 33
minimum clearance 13
minimum voltage 21
module connectors 23
motherboard 33
mounting hole locations 14
mounting holes 13
Municipal Box 25, 50
G
General Alarm 30
ground fault 33, 50
I
Indicating Circuit #1 53
initial alarm test 53
initiating circuits 34
initiating device 37, 47
Initiating Device Circuit 36
inspection 53
N
NACs 20
interconnect wire, battery 31
Interface Module 11
interruption of circuits 36
IRI-type delay timer 29
National Electrical Code, Article 760 16
National Fire Protection Association 47
negative 17
NFPA 53
J
NFPA standards 47
non-latching 26, 34
J1 connector 13, 14
J2 Connector 15
J3 Connector 15
J9 Connector 17
JP1 jumper 49
jumper 23, 24
LATCH 26
nonpower-limited 17, 21, 26
nonresettable power 19, 22
non-silenceable service 20
Notification Appliance Circuit 34
Notification Appliances 47
NYC-type delay timer 29
K
O
opens 50
keyhole 13
knockouts 13, 17
operating mode 28
operating voltage 19
optional boards 34
optional modules 10
Out of Service 31
output circuits 34
overcurrent protection 16
L
label
Protected Premises Unit 26
terminal identification 23, 24
LAMP TEST function 34
latch 34, 35
LATCH jumper 26
latching operation 35, 36
LED
P
paper labels 11
physical lockout 33
Disconnect 25
piezo 34, 35, 36, 37, 53
piezo tones 34
polarity 17, 18, 31
polarity reversal circuit 51
polarized devices 18, 20
positive 17
power connection 16
Power Supervision Relay 19
power-limited 17, 20, 21, 26, 51
power-limited power supply 22
predischarge timer 37
previous panel status 36
primary power 16, 31
programmed 49
System Trouble 25
LED Interface Module 11, 23
LEDs
Alarm, Trouble and Supervisory 33
Local Energy Municipal Box 10
Local Jurisdiction delay timer 29
loop resistance 50
lower position 23, 24
M
main breaker panel 16
maintenance 53
Manual Pull Stations 18
Manual Release Circuit 18
manual station 37
maximum allowable resistance 21
Maximum Battery Capacity 12
Maximum Charging Circuit 12
maximum resistance 19
Protected Premises Receiving Unit 47, 48, 49
protected space 33
56
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
System Trouble 30
System Trouble LED 25
R
rail 24
rail, backbox 13, 14
red wire 17
regulated power 22
relay contacts 49
Relay, System Alarm 34
release 33
releasing 21
Releasing Circuit 20, 21
Releasing Circuit #2 29
Releasing Devices 47
Remote Alarm circuit 25
Remote Annunciator 11
Remote Station 47, 49
Remote Station Service 10
Remote Trouble circuit 25
reset switch 37
T
tag, “Out of Service” 31
terminal identification label 23, 24
testing 53
Timer Delay 29
timer, pre-discharge 37
timer, watchdog 33
tone patterns 35
tones, piezo 34
tracking operation 35, 36
transformer wires 13, 14
Transmitter Module 10, 23, 50, 51
trim ring 14
trouble 49
condition 33, 36, 50
relay 22
resettable power 19, 22
resistance, allowable 19
resistor 49
trouble sounder 11
troubleshooting 53
resound 34
U
reverse polarity 25
reverse polarity circuit 10
reverse polarity loop 51
RS82-9 Remote Station Receiver 47, 51
RZA-4X Remote Annunciator 11
UL listed 47
UL Standard 864 29
unused circuits 20, 21
upper position 23
V
S
visual inspection 31
voltage 15
second alarm 37
Secondary Power 31
secondary power source 39
self-restoring 34
voltage drop 12
voltmeter 11
separate transmission 50
short circuit 35
silence switch 11
W
watchdog timer 33
Waterflow 18
Slide-in paper labels 11
solenoid valve 37, 53
sprinkler 35, 36
wire, primary power 16
wires, transformer 13
Z
sprinkler supervisory 50
Standard UL-type delay timer 29
Standby Battery Current 39
stand-off 14, 23, 24
Style B (Class B) 18
Style D (Class A) 18
Style Y (Class B) 20, 21
Style Z (Class A) 20
sulfuric acid 31
zone 49
Zone Relay Module 10, 23
supervised 20
Supervisory Circuit 21
supervisory device 33, 35
supervisory signal 49
Supervisory/Releasing Service 29
supplementary devices 22
suppresant agent 37
switch, disable 26
System Alarm Relay 34
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
57
Download from Www.Somanuals.com. All Manuals Search And Download.
58
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Download from Www.Somanuals.com. All Manuals Search And Download.
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Limited Warranty
System Sensor® warrants its products to be free from defects in materials and workman-
ship for eighteen (18) months from the date of manufacture, under normal use and ser-
vice. Products are date stamped at time of manufacture. The sole and exclusive
obligation of System Sensor® is to repair or replace, at is option, free of charge for parts
and labor, any part which is defective in materials or workmanship under normal use and
service. For products not under System Sensor® manufacturing date-stamp control, the
warranty is eighteen (18) months from date of original purchase by System Sensor® dis-
tributor unless the installation instructions or catalog sets forth a shorter period, in which
case the shorter period shall apply. This warranty is void if the product is altered, repaired
or serviced by anyone other than System Sensor® or its authorized distributors or if there
is a failure to maintain the products and systems in which they operate in proper and work-
able manner. In case of defect, secure a Return Authorization Number from our Customer
Service Department. Return product, transportation prepaid, to System Sensor Repair
Department, RA #_____, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note
describing the malfunction and suspected cause of failure.
This writing constitutes the only warranty made by System Sensor® with respect to its
products. System Sensor® does not represent that its products will prevent any loss by
fire or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that System Sensor® is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation,
damage, misuse, abuse, accident or similar incident.
SYSTEM SENSOR® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MER-
CHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL SYSTEM SENSOR® BE LIABLE FOR ANY LOSS OF OR
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE SYSTEM SENSOR® PRODUCTS. FUR-
THERMORE, SYSTEM SENSOR® SHALL NOT BE LIABLE FOR ANY PERSONAL
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by System
Sensor®. No increase or alteration, written or verbal, of the obligation of this warranty is
authorized.
3825 Ohio Avenue
St. Charles, IL 60174
1-800-SENSOR2
Fax: (630) 377-6495
Download from Www.Somanuals.com. All Manuals Search And Download.
|