Sierra Network Router 240 VT User Manual

Sierra Series 240 and 241  
Innova-Mass™ Multi-Parameter  
Vortex Mass Flow Meters  
Models 240-VT, 240-VTP, 241-VT, 241-VTP  
Instruction Manual  
Part Number: IM-24-HP, Rev. C 11/07  
CORPORATE HEADQUARTERS  
5 Harris Court, Building L, Monterey, CA 93940  
Phone (831) 373-0200 (800) 866-0200 Fax (831) 373-4402  
EUROPE HEADQUARTERS  
Bijlmansweid 2 1934RE Egmond ann den Hoef The Netherlands  
Phone +31 (0)72-5071400 Fax: +31 (0)72-5071401  
ASIA HEADQUARTERS  
R.M.618, Tomson Centre, Building A  
188 Zhang Yang Road,  
Pu Dong New District, Shanghai, P.R. China 200122  
Phone +8621 5879 8521/22 Fax +8621 5879 8586  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Table of Contents  
Table of Contents  
Chapter 1 Introduction  
Innova-Mass™ Vortex Mass Flow Meters.......................................... 1-1  
Using this Manual ......................................................................... 1-1  
Note and Safety Information......................................................... 1-2  
Receipt of System Components .................................................... 1-2  
Technical Assistance..................................................................... 1-2  
How the Innova-Mass Vortex Meter Operates.................................... 1-3  
Velocity Measurement/Pressure Drop .......................................... 1-3  
Temperature Measurement ........................................................... 1-6  
Pressure Measurement .................................................................. 1-7  
Flow Meter Configurations ................................................................. 1-7  
Chapter 2 Installation  
Installation Overview........................................................................... 2-1  
Flow Meter Installation Requirements.......................................... 2-1  
Unobstructed Flow Requirements................................................. 2-2  
Series 240 In-Line Flow Meter Installation......................................... 2-3  
Wafer-Style Flow Meter Installation ............................................ 2-4  
Flange-Style Flow Meter Installation............................................ 2-5  
Series 241 Insertion Flow Meter Installation ...................................... 2-6  
Cold Tap Guidelines ..................................................................... 2-7  
Hot Tap Guidelines....................................................................... 2-8  
Flow Meter Insertion ........................................................................... 2-9  
Installing Meters with a Compression Connection..................... 2-10  
Installing Meters with a Packing Gland Connection .................. 2-12  
Installing Meters (Packing Gland), No Insertion Tool ............... 2-15  
Adjusting Meter Orientation.............................................................. 2-17  
Display/Keypad Adjustment....................................................... 2-17  
Enclosure Adjustment................................................................. 2-18  
Wiring Connections........................................................................... 2-19  
Input Power Connections............................................................ 2-19  
4-20 mA Output Connections ..................................................... 2-20  
Pulse Output Connections........................................................... 2-21  
Alarm Output Connections ......................................................... 2-22  
Remote Electronics Wiring......................................................... 2-24  
Optional Input Electronics Wiring.............................................. 2-25  
Chapter 3 Operating Instructions  
Flow Meter Display/Keypad ............................................................... 3-1  
Start Up................................................................................................ 3-2  
Using the Setup Menus........................................................................ 3-3  
Programming the Flow Meter ....................................................... 3-3  
Output Menu ................................................................................. 3-4  
Display Menu................................................................................ 3-6  
Alarms Menu................................................................................. 3-7  
Totalizer Menu.............................................................................. 3-8  
IM-24-HP  
0-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Series 24-HP Instruction Manual  
Energy Menu.......................................................................3-10  
Fluid Menu.................................................................................. 3-11  
Units Menu.................................................................................. 3-12  
Time and Date Menu................................................................... 3-13  
Diagnostics Menu........................................................................ 3-14  
Calibration Menu ........................................................................ 3-15  
Password Menu........................................................................... 3-16  
Chapter 4 Troubleshooting and Repair  
Hidden Diagnostics Menus.................................................................. 4-1  
Column One Hidden Diagnostics Values ..................................... 4-2  
Column Two Hidden Diagnostics Values..................................... 4-3  
Analog Output Calibration ................................................................. 4-5  
Troubleshooting the Flow Meter......................................................... 4-6  
Symptom: Output at no Flow........................................................ 4-6  
Symptom: Erratic Output .............................................................. 4-6  
Symptom: No Output .................................................................... 4-7  
Symptom: Meter Displays Temperature Fault.............................. 4-7  
Symptom: Meter Displays Pressure Fault..................................... 4-8  
Electronics Assembly Replacement .................................................... 4-9  
Pressure Sensor Replacement (Series 240 Only) ............................... 4-9  
Returning Equipment to the Factory.................................................. 4-10  
Appendix A Product Specifications  
Appendix B Glossary  
Appendix C Fluid Calculations  
Appendix D HART Communication  
Appendix E Modbus Communication  
0-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Table of Contents  
Figures  
1-1.  
1-2.  
1-3.  
2-1.  
2-2.  
2-3.  
2-4.  
2-5.  
2-6.  
2-7.  
2-8.  
2-9.  
In-Line Vortex Multi-Parameter Mass Flow Meter ............... 1-3  
Measurement Principle of Vortex Flow Meters..................... 1-4  
Reynolds Number Range of the Innova-Mass........................ 1-6  
Recommended Pipe Length Required for Installation ........... 2-2  
Flange Bolt Torquing Sequence ............................................. 2-3  
Wafer-Style Flow Meter Installation...................................... 2-4  
Flange-Style Flow Meter Installation..................................... 2-5  
Hot Tap Sequence................................................................... 2-8  
Insertion Calculation (Compression Type) .......................... 2-10  
Flow Meter with Compression Type Fitting ........................ 2-11  
Insertion Calculation (Meters with Insertion Tool).............. 2-12  
Flow Meter with Permanent Insertion Tool ......................... 2-13  
2-10. Flow Meter with Removable Insertion Tool ........................ 2-14  
2-11. Insertion Calculation (Meters without Insertion Tool)......... 2-15  
2-12. Display/Keypad Viewing Adjustment.................................. 2-17  
2-13. Enclosure Viewing Adjustment............................................ 2-18  
2-14. AC Power Connections ........................................................ 2-19  
2-15. DC Power Connections ........................................................ 2-19  
2-16. Load Resistance Versus Input Voltage................................. 2-20  
2-17. Isolated 4-20 Output with External Power Supply............... 2-20  
2-18. Non-Isolated 4-20 Output using Input Power Supply .......... 2-21  
2-19. Isolated 4-20 Output using Meter Power Supply (AC only) 2-21  
2-20. Isolated Pulse Output using External Power Supply............ 2-22  
2-21. Non-Isolated Pulse Output using Input Power Supply......... 2-22  
2-22. Isolated Pulse Output using Meter Power Supply (AC only)2-22  
2-23. Isolated Alarm Output using External Power Supply .......... 2-23  
2-24 Non-Isolated Alarm Output using Meter Power Supply ...... 2-23  
2-25 Isolated Alarm Output using Meter Power Supply(AC only) 2-24  
2-26 Remote Electronics Junction Box Sensor Wiring ................ 2-24  
3-1.  
Flow Meter Display/Keypad .................................................. 3-1  
Tables  
2-1.  
Minimum Recommended Stud Bolt Lengths ......................... 2-3  
IM-24-HP  
0-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Series 24-HP Instruction Manual  
Warnings and Cautions  
Warning!  
Agency approval for hazardous location installations varies between flow meter models.  
Consult the flow meter nameplate for specific flow meter approvals before any hazardous  
location installation.  
Hot tapping must be performed by a trained professional. U.S. regulations often require a  
hot tap permit. The manufacturer of the hot tap equipment and/or the contractor perform-  
ing the hot tap is responsible for providing proof of such a permit.  
All flow meter connections, isolation valves and fittings for cold/hot tapping must have the  
same or higher pressure rating as the main pipeline.  
For Series 241 insertion flow meter installations, an insertion tool must be used for any  
installation where a flow meter is inserted under pressure greater than 50 psig.  
To avoid serious injury, DO NOT loosen a compression fitting under pressure.  
To avoid potential electric shock, follow National Electric Code or your local code when  
wiring this unit to a power source. Failure to do so could result in injury or death. All AC  
power connections must be in accordance with published CE directives. All wiring proce-  
dures must be performed with the power Off.  
Before attempting any flow meter repair, verify that the line is not pressurized. Always  
remove main power before disassembling any part of the mass flow meter.  
Caution!  
Calibration must be performed by qualified personnel. Sierra Instruments, Inc., strongly rec-  
ommends that you return your flow meter to the factory for calibration.  
In order to achieve accurate and repeatable performance, the flow meter must be in-  
stalled with the specified minimum length of straight pipe upstream and downstream of  
the flow meter’s sensor head.  
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four  
hours at full gas flow before installing the flow meter.  
For Series 241 insertion flow meter installations, the sensor alignment pointer must point  
downstream in the direction of flow.  
The AC wire insulation temperature rating must meet or exceed 85°C (185°F).  
0-6  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 1 Introduction  
Chapter 1 Introduction  
Innova-Mass Multi-Parameter Vortex Mass Flow Meters  
The Sierra Instruments’ Series 240 In-Line and the Series 241 Insertion  
Innova-Mass™ Vortex Flow Meters provide a reliable solution for proc-  
ess flow measurement. From a single entry point in the pipeline, Innova-  
Mass meters offer precise measurements of five parameters including  
mass flow, volumetric flow, temperature, pressure and fluid density. The  
unique Innova-Mass design reduces fugitive emissions, wiring, startup  
time and work-force requirements.  
Innova-Mass digital electronics allows reconfiguration for most gases,  
liquids and steam with generous rangeability. The meter outputs a pulse  
signal for remote totalization and up to three 4-20 mA analog signals for  
monitoring your choice of the five process variables. The local key-  
pad/display provides instantaneous flow rate, total flow, temperature,  
pressure and density in engineering units.  
The Sierra Series 240 and 241 Innova-Mass Meters’ simple installation  
combines with an easy-to-use interface that provides quick set up, long  
term reliability and accurate mass flow measurement over a wide range  
of flows, pressures and temperatures.  
Using This Manual  
This manual provides information needed to install and operate both the  
Series 240 In-Line and Series 241 Insertion Innova-Mass Flow Meters.  
The four chapters of this manual cover these areas:  
Chapter 1 includes the introduction and product description  
Chapter 2 provides information needed for installation  
Chapter 3 describes system operation and programming  
Chapter 4 covers troubleshooting and repair  
The product specifications are found in Appendix A. Appendix B con-  
tains a glossary of terms. Appendix C provides reference fluid calcula-  
tions. Appendix D provides wiring and configuration information for  
the Energy meter option.  
IM-24-HP  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1 Introduction  
Series 24-HP Instruction Manual  
Note and Safety Information  
We use note, caution and warning statements throughout this book to  
draw your attention to important information.  
Caution!  
Note  
Warning!  
This statement appears with  
information that is important to  
protect people and equipment  
from damage. Pay very close  
attention to all warnings that  
apply to your application.  
This statement appears with  
information that is important  
for protecting your equipment an important detail.  
and performance. Read and  
follow all cautions that apply  
to your application.  
This statement appears with a  
short message to alert you to  
Receipt of System Components  
When receiving a Sierra mass flow meter, carefully check the outside  
packing carton for damage incurred in shipment. If the carton is dam-  
aged, notify the local carrier and submit a report to the factory or dis-  
tributor. Remove the packing slip and check that all ordered components  
are present. Make sure any spare parts or accessories are not discarded  
with the packing material. Do not return any equipment to the factory  
without first contacting Sierra Customer Service.  
Technical Assistance  
If you encounter a problem with your flow meter, review the configura-  
tion information for each step of the installation, operation and set up  
procedures. Verify that your settings and adjustments are consistent with  
factory recommendations. Refer to Chapter 4, Troubleshooting, for spe-  
cific information and recommendations.  
If the problem persists after following the troubleshooting procedures  
outlined in Chapter 4, contact Sierra Instruments, Technical Support at  
(888) 386-7835 or (303) 682-9999 between 8:00 a.m. and 5:00 p.m.  
MST. When calling Technical Support, have the following information  
on hand:  
the flow range, serial number and Sierra order number (all  
marked on the meter nameplate)  
the problem you are encountering and any corrective action  
taken  
application information (gas, pressure, temperature and pip-  
ing configuration)  
1-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 1 Introduction  
How the Innova-Mass Vortex Mass Flow Meter Operates  
Figure 1-1. In-Line Vortex Multi-Parameter Mass Flow Meter  
Sierra Series 240 and 241 Innova-Mass™ Multi-Parameter Vortex Mass  
Flow Meters use a unique sensor head to monitor mass flow rate by di-  
rectly measuring three variables–fluid velocity, temperature and pres-  
sure. The built-in flow computer calculates the mass flow rate and volu-  
metric flow rate based on these three direct measurements. The velocity,  
temperature and pressure sensing head is built into the vortex meter’s  
flow body. To measure fluid velocity, the flow meter incorporates a bluff  
body (shedder bar) in the flow stream and measures the frequency of  
vortices created by the shedder bar. Temperature is measured using a  
platinum resistance temperature detector (PRTD). Pressure measurement  
is achieved using a solid-state pressure transducer. All three elements are  
combined into an integrated sensor head assembly located downstream  
of the shedder bar within the flow body.  
Velocity Measurement  
The Innova-Mass vortex velocity sensor is a patented mechanical design  
that minimizes the effects of pipeline vibration and pump noise, both of  
which are common error sources in flow measurement with vortex flow  
meters. The velocity measurement is based on the well-known Von Kar-  
man vortex shedding phenomenon. Vortices are shed from a shedder bar,  
and the vortex velocity sensor located downstream of the shedder bar  
senses the passage of these vortices. This method of velocity measure-  
ment has many advantages including inherent linearity, high turndown,  
reliability and simplicity.  
IM-24-HP  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1 Introduction  
Series 24-HP Instruction Manual  
Vortex Shedding Frequency  
Von Karman vortices form downstream of a shedder bar into two dis-  
tinct wakes. The vortices of one wake rotate clockwise while those of  
the other wake rotate counterclockwise. Vortices generate one at a time,  
alternating from the left side to the right side of the shedder bar. Vortices  
interact with their surrounding space by over-powering every other  
nearby swirl on the verge of development. Close to the shedder bar, the  
distance (or wave length) between vortices is always constant and meas-  
urable. Therefore, the volume encompassed by each vortex remains con-  
stant, as shown below. By sensing the number of vortices passing by the  
velocity sensor, the Innova-Mass™ Flow Meter computes the total fluid  
volume.  
Velocity sensor  
Vortex shedder bar  
Vortices  
Flow  
Constant  
wave length  
Figure 1-2. Measurement Principle of Vortex Flow Meters  
Vortex Frequency Sensing  
The velocity sensor incorporates a piezoelectric element that senses the  
vortex frequency. This element detects the alternating lift forces pro-  
duced by the Von Karman vortices flowing downstream of the vortex  
shedder bar. The alternating electric charge generated by the piezoelec-  
tric element is processed by the transmitter’s electronic circuit to obtain  
the vortex shedding frequency. The piezoelectric element is highly sensi-  
tive and operates over a wide range of flows, pressures and temperatures.  
1-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 1 Introduction  
Flow Velocity Range  
To ensure trouble-free operation, vortex flow meters must be correctly  
sized so that the flow velocity range through the meter lies within the  
measurable velocity range (with acceptable pressure drop) and the linear  
range.  
The measurable range is defined by the minimum and maximum velocity  
using the following table.  
Gas  
25  
Liquid  
ft/s  
English ρ (lb/ft3)  
ρ
Vmin  
1 ft/s  
Vmax  
300 ft/s  
37  
m/s  
30 ft/s  
Metric ρ (kg/m3)  
ρ
Vmin  
0.3 m/s  
9.1 m/s  
Vmax  
91 m/s  
The pressure drop for series 241 insertion meters is negligible. The pressure  
drop for series 240 in-line meters is defined as:  
P = .00024 ρ V2 English units (P in psi, ρ in lb/ft3, V in ft/sec)  
P = .000011 ρ V2 Metric units (P in bar, ρ in kg/m3, V in m/sec)  
The linear range is defined by the Reynolds number. The Reynolds number is the  
ratio of the inertial forces to the viscous forces in a flowing fluid and is defined  
as:  
ρ V D  
Re =  
µ
Where  
Re = Reynolds Number  
ρ
=
mass density of the fluid being measured  
V = velocity of the fluid being measured  
D = internal diameter of the flow channel  
µ
=
viscosity of the fluid being measured  
The Strouhal number is the other dimensionless number that quantifies  
the vortex phenomenon. The Strouhal number is defined as:  
f d  
St =  
V
Where  
St = Strouhal Number  
f
=
frequency of vortex shedding  
d = shedder bar width  
V = fluid velocity  
IM-24-HP  
1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1 Introduction  
Series 24-HP Instruction Manual  
As shown in Figure 1-3, Innova-Mass™ meters exhibit a constant Strou-  
hal number across a large range of Reynolds numbers, indicating a con-  
sistent linear output over a wide range of flows and fluid types. Below  
this linear range, the intelligent electronics in Innova-Mass automatically  
corrects for the variation in the Strouhal number with the Reynolds num-  
ber. The meter’s smart electronics corrects for this non-linearity via its  
simultaneous measurements of the process fluid temperature and pres-  
sure. This data is then used to calculate the Reynolds number in real  
time. Innova-Mass meters automatically correct down to a Reynolds  
number of 5,000.  
Corrected range  
0.3  
Linear range  
0.2  
0.1  
0.0  
103  
104  
5000  
10 5  
106  
Reynolds Number, Re  
107  
108  
Figure 1-3. Reynolds Number Range for the Innova-Mass  
Temperature Measurement  
Innova-Mass Flow Meters use a 1000 ohm platinum resistance temperature  
detector (PRTD) to measure fluid temperature.  
1-6  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 1 Introduction  
Pressure Measurement  
Innova-Mass Flow Meters incorporate a solid-state pressure transducer  
isolated by a 316 stainless steel diaphragm. The transducer itself is mi-  
cro-machined silicon, fabricated using integrated circuit processing tech-  
nology. A nine-point pressure/temperature calibration is performed on  
every sensor. Digital compensation allows these transducers to operate  
within a 0.3% of full scale accuracy band within the entire ambient tem-  
perature range of -4°F to 140°F. Thermal isolation of the pressure trans-  
ducer ensures the same accuracy across the allowable process fluid tem-  
perature range of -40°F to 750°F.  
Flow Meter Configurations  
Innova-Mass™ Vortex Mass Flow Meters are available in two  
configurations:  
Series 240 in-line flow meter (replaces a section of the pipeline)  
Series 241 insertion flow meter (requires a “cold” tap or a “hot” tap  
into an existing pipeline)  
Both the in-line and insertion configurations are similar in that they both  
use identical electronics and have similar sensor heads. Besides installa-  
tion differences, the main difference between an in-line flow meter and  
an insertion flow meter is their method of measurement.  
For an in-line vortex flow meter, the shedder bar is located across the en-  
tire diameter of the flow body. Thus, the entire pipeline flow is included  
in the vortex formation and measurement. The sensing head, which di-  
rectly measures velocity, temperature and pressure is located just down-  
stream of the shedder bar.  
Insertion vortex flow meters have a shedder bar located across the di-  
ameter of a short tube. The velocity, temperature and pressure sensor are  
located within this tube just downstream of a built-in shedder bar. This  
entire assembly is called the insertion sensing head. It fits through any  
entry port with a 1.875 inch minimum internal diameter.  
The sensing head of an insertion vortex flow meter directly monitors the  
velocity at a point in the cross-sectional area of a pipe, duct, or stack (re-  
ferred to as “channels”). The velocity at a point in the pipe varies as a  
function of the Reynolds number. The insertion vortex flow meter com-  
putes the Reynolds number and then computes the total flow rate in the  
channel. The output signal of insertion meters is the total flow rate in the  
channel. The accuracy of the total flow rate computation depends on ad-  
herence to the piping installation requirements given in Chapter 2. If ad-  
herence to those guidelines cannot be met, contact the factory for specific  
installation advice.  
IM-24-HP  
1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1 Introduction  
Series 24-HP Instruction Manual  
Flow Meter Electronics  
Innova-Mass Flow Meter electronics are available mounted directly to  
the flow body, or remotely mounted. The electronics housing may be  
used indoors or outdoors, including wet environments. Power require-  
ments are 100 milliamps at 12-36 VDC. An optional AC powered unit is  
available. Three analog output signals are available for your choice of  
three of the five process variables: mass flow rate, volumetric flow rate,  
temperature, pressure or fluid density.  
Innova-Mass Flow Meters include a local 2 x 16 character LCD display  
housed within the enclosure. Local operation and reconfiguration is ac-  
complished using six pushbuttons operated via finger touch. For hazard-  
ous locations, the six buttons can be operated with the electronics enclo-  
sure sealed using a hand-held magnet, thereby not compromising the in-  
tegrity of the hazardous location certification.  
The electronics include nonvolatile memory that stores all configuration  
information. The nonvolatile memory allows the flow meter to function  
immediately upon power up, or after an interruption in power.  
1-8  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Chapter 2 Installation  
Installation Overview  
Sierra’s Innova-Mass Vortex Flow Meter installations are simple and  
straightforward. Both the Series 240 In-Line and Series 241 Insertion type  
flow meter installations are covered in this chapter. After reviewing the  
installation requirements given below, see page 2-3 for Series 240 instal-  
lation instructions. See page 2-6 for Series 241 installation instructions.  
Wiring instructions begin on page 2-19.  
Flow Meter Installation Requirements  
Before installing the flow meter, verify the installation site allows for  
these considerations:  
Warning!  
Consult the flow meter name-  
plate for specific flow meter ap-  
provals before any hazardous lo-  
cation installation.  
1.  
2.  
Line pressure and temperature will not exceed the flow meter  
rating.  
The location meets the required minimum number of pipe di-  
ameters upstream and downstream of the sensor head as illus-  
trated Figure 2-1.  
3.  
4.  
5.  
Safe and convenient access with adequate overhead clear-  
ance for maintenance purposes.  
Verify that the cable entry into the instrument meets the  
specific standard required for hazardous area installations.  
For remote installations, verify the supplied cable length is  
sufficient to connect the flow meter sensor to the remote  
electronics.  
Also, before installation check your flow system for anomalies such as:  
leaks  
valves or restrictions in the flow path that could create distur-  
bances in the flow profile that might cause unexpected flow rate  
indications  
IM-24-HP  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Unobstructed Flow Requirements  
Select an installation site that will minimize possible distortion in the  
flow profile. Valves, elbows, control valves and other piping components  
may cause flow disturbances. Check your specific piping condition  
against the examples shown below. In order to achieve accurate and re-  
peatable performance install the flow meter using the recommended  
number of straight run pipe diameters upstream and downstream of the  
sensor.  
Note: For liquid applications in vertical pipes, avoid installing with flow  
in the downward direction because the pipe may not be full at all points.  
Choose to install the meter with flow in the upward direction if possible.  
A
B
A
B
C'  
C
Flow meter  
Flow meter  
Flow conditioner  
(if used)  
Example 1.  
One 90°elbow before meter  
Example 4.  
Reduction before meter  
A
B
A
B
C'  
C
Flow meter  
C'  
C
Flow meter  
Flow conditioner  
(if used)  
Example 2.  
Two 90°elbows before meter in one plane  
Example 5.  
Expansion before meter  
Flow conditioner  
(if used)  
A
B
A
B
C'  
C
Flow meter  
C'  
C
Flow meter  
Flow conditioner  
(if used)  
Flow conditioner (if used)  
Example 3.  
Two 90°elbows before meter out of plane (if three  
90°bends present, double recommended length)  
Example 6.  
Regulator or valve partially closed before meter  
(If valve is always wide open, base length  
requirements on fitting directly preceding it)  
Minimum Required  
Upstream Diameters  
No Flow  
Minimum Required  
Downstream Diameters  
No Flow  
Conditioner  
B
With Flow  
Conditioner  
Conditioner  
A
With Flow Conditioner  
C
Example  
A
N/A  
C´  
B
1
2
3
4
5
6
10 D  
15 D  
25 D  
10 D  
20 D  
25 D  
N/A  
5 D  
5 D  
5 D  
5 D  
5 D  
N/A  
5 D  
5 D  
5 D  
5 D  
5 D  
5 D  
5 D  
10 D  
5 D  
5 D  
5 D  
5 D  
5 D  
5 D  
5 D  
5 D  
10 D  
10 D  
10 D  
10 D  
10 D  
10 D  
D = Internal diameter of channel. N/A = Not applicable  
Figure 2-1. Recommended Pipe Length Requirements for Installation, Series 240 and 241  
2-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Series 240 In-Line Flow Meter Installation  
Install the Series 240 In-Line Flow Meter between two conventional pipe  
flanges as shown in Figures 2-3 and 2-4. Table 2-1 provides the recom-  
mended minimum stud bolt lengths for wafer-style meter body size and  
different flange ratings.  
The meter inside diameter is equal to the same size nominal pipe ID in  
schedule 80. For example, a 2” meter has an ID of 1.939” (2” schedule  
80). Do not install the meter in a pipe with an inside diameter  
smaller than the inside diameter of the meter. For schedule 160 and  
higher pipe, a special meter is required. Consult the factory before pur-  
chasing the meter.  
Series 240 Meters require customer-supplied gaskets. When selecting  
gasket material make sure that it is compatible with the process fluid and  
pressure ratings of the specific installation. Verify that the inside diame-  
ter of the gasket is larger than the inside diameter of the flow meter and  
adjacent piping. If the gasket material extends into the flow stream, it will  
disturb the flow and cause inaccurate measurements.  
Flange Bolt Specifications  
Stud Bolt Lengths for Each Flange Rating (inches)  
Line Size  
Class 150  
Class 300  
Class 600  
1 inch  
1.5 inch  
2 inch  
3 inch  
4 inch  
6.00  
6.25  
8.50  
9.00  
9.50  
7.00  
8.50  
8.75  
10.00  
10.75  
7.50  
9.00  
9.50  
10.50  
12.25  
Table 2-1. Minimum Recommended Stud Bolt Lengths for Wafer Meters  
The required bolt load for sealing the gasket joint is affected by several  
application-dependent factors, therefore the required torque for each ap-  
plication may be different. Refer to the ASME Pressure Vessel Code  
guidelines for bolt tightening standards.  
1
1
1
12  
5
5
7
8
6
8
9
4
3
4
3
4
3
10  
7
11  
6
2
2
2
4-bolt  
8-bolt  
12-bolt  
Figure 2-2. Flange Bolt Torquing Sequence  
IM-24-HP  
2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Wafer-Style Flow Meter Installation  
Install the wafer-style meter between two conventional pipe flanges of the  
same nominal size as the flow meter. If the process fluid is a liquid, make  
sure the meter is located where the pipe is always full. This may require  
locating the meter at a low point in the piping system. Note: Vortex flow  
meters are not suitable for two-phase flows (i.e., liquid and gas mixtures).  
For horizontal pipelines having a process temperature above 300° F,  
mount the meter at a 45 or 90-degree angle to avoid overheating the elec-  
tronics enclosure. To adjust the viewing angle of the enclosure or dis-  
play/keypad, see page 2-17.  
Caution!  
When using toxic or cor-  
rosive gases, purge the  
line with inert gas for a  
minimum of four hours  
at full gas flow before  
installing the flow meter.  
Figure 2-3. Wafer-Style Flow Meter Installation  
When installing the meter make sure the section marked “inlet” is positioned  
upstream of the outlet, facing the flow. This ensures that the sensor head is  
positioned downstream of the vortex shedder bar and is correctly aligned to  
the flow. Installing the meter opposite this direction will result in completely  
inaccurate flow measurement. To install the meter:  
1. Turn off the flow of process gas, liquid or steam. Verify that the line  
is not pressurized. Confirm that the installation site meets the re-  
quired minimum upstream and downstream pipe diameters.  
2. Insert the studs for the bottom side of the meter body between the pipe  
flanges. Place the wafer-style meter body between the flanges with the  
end stamped “inlet” facing flow. Center the meter body inside the di-  
ameter with respect to the inside diameter of the adjoining piping.  
3. Position the gasket material between the mating surfaces. Make sure  
both gaskets are smooth and even with no gasket material extending  
into the flow profile. Obstructions in the pipeline will disturb the flow  
and cause inaccurate measurements  
4. Place the remaining studs between the pipe flanges. Tighten the nuts in  
the sequence shown in Figure 2-2. Check for leaks after tightening the  
flange bolts  
2-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Flange-Style Flow Meter Installation  
Install the flange-style meter between two conventional pipe flanges of  
the same nominal size as the flow meter. If the process fluid is a liquid,  
make sure the meter is located where the pipe is always full. This may re-  
quire locating the meter at a low point in the piping system. Note: Vortex  
flow meters are not suitable for two-phase flows (i.e., liquid and gas mix-  
tures). For horizontal pipelines having a process temperature above 300°  
F, mount the meter at a 45 or 90-degree angle to avoid overheating the  
electronics enclosure. To adjust the viewing angle of the enclosure or dis-  
play/keypad, see page 2-17.  
Figure 2-4. Flange-Style Flow Meter Installation  
Caution!  
When using toxic or corro-  
sive gases, purge the line  
with inert gas for a mini-  
mum of four hours at full  
gas flow before installing  
the flow meter.  
When installing the meter make sure the flange marked “inlet” is positioned  
upstream of the outlet flange, facing the flow. This ensures that the sensor  
head is positioned downstream of the vortex shedder bar and is correctly  
aligned to the flow. Installing the meter opposite this direction will result in  
completely inaccurate flow measurement. To install the meter:  
1. Turn off the flow of process gas, liquid or steam. Verify that the line  
is not pressurized. Confirm that the installation site meets the re-  
quired minimum upstream and downstream pipe diameters.  
2. Seat the meter level and square on the mating connections with the flange  
marked “inlet” facing the flow. Position a gasket in place for each side.  
Make sure both gaskets are smooth and even with no gasket material ex-  
tending into the flow profile. Obstructions in the pipeline will disturb the  
flow and cause inaccurate measurements.  
3. Install bolts in both process connections. Tighten the nuts in the se-  
quence shown in Figure 2-2. Check for leaks after tightening the flange  
bolts.  
IM-24-HP  
2-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Series 241 Insertion Flow Meter Installation  
Prepare the pipeline for installation using either a cold tap or hot tap  
method described on the following pages. Refer to a standard code for all  
pipe tapping operations. The following tapping instructions are general in  
nature and intended for guideline purposes only. Before installing the me-  
ter, review the mounting position and isolation value requirements given  
below.  
Mounting Position  
Allow clearance between the electronics enclosure top and any other ob-  
struction when the meter is fully retracted.  
Isolation Valve Selection  
An isolation valve is available as an option with Series 241 meters. If you  
supply the isolation valve, it must meet the following requirements:  
1. A minimum valve bore di-  
ameter of 1.875 inches is re-  
1.875-inch min.  
valve bore  
quired, and the valve’s body  
size should be two inches.  
2-inch min.  
Normally, gate valves are  
used.  
2-inch  
valve size  
2. Verify that the valve’s body  
and flange rating are within  
the flow meter’s maximum  
operating pressure and tem-  
perature.  
Isolation Valve Requirements  
3. Choose an isolation valve with at least two inches existing between  
the flange face and the gate portion of the valve. This ensures that the  
flow meter’s sensor head will not interfere with the operation of the  
isolation valve.  
2-6  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Cold Tap Guidelines  
Refer to a standard code for all pipe tapping operations. The following  
tapping instructions are general in nature and intended for guideline pur-  
poses only.  
1. Turn off the flow of process gas, liquid or steam. Verify that the line  
is not pressurized.  
Caution!  
When using toxic or  
corrosive gases, purge  
the line with inert gas  
for a minimum of four  
hours at full gas flow  
before installing the  
flow meter.  
2. Confirm that the installation site meets the minimum upstream and  
downstream pipe diameter requirements. See Figure 2-1.  
3. Use a cutting torch or sharp cutting tool to tap into the pipe. The pipe  
opening must be at least 1.875 inches in diameter. (Do not attempt to  
insert the sensor probe through a smaller hole.)  
4. Remove all burrs from the tap. Rough edges may cause flow profile  
distortions that could affect flow meter accuracy. Also, obstructions  
could damage the sensor assembly when inserting into the pipe.  
5. After cutting, measure the thickness of the cut-out and record this  
number for calculating the insertion depth.  
6. Weld the flow meter pipe con-  
nection on the pipe. Make sure  
this connection is within 5°  
perpendicular to the pipe cen-  
terline.  
Warning!  
All flow meter connec-  
tions, isolation valves  
and fittings for cold tap-  
ping must have the same  
or higher pressure rating  
as the main pipeline.  
7. Install the isolation valve (if used).  
8. When welding is complete and all fittings are installed, close the  
isolation valve or cap the line. Run a static pressure check on the  
welds. If pressure loss or leaks are detected, repair the joint and re-  
test.  
9. Connect the meter to the pipe process connection.  
10. Calculate the sensor probe insertion depth as described on the follow-  
ing pages. Insert the sensor probe into the pipe.  
IM-24-HP  
2-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Hot Tap Guidelines  
Refer to a standard code for all pipe tapping operations. The following  
tapping instructions are general in nature and intended for guideline pur-  
poses only.  
Warning!  
Hot tapping must be  
performed by a trained pro-  
fessional. US. regulations of-  
ten require a hot tap permit.  
The manufacturer of the hot  
tap equipment and/or the con-  
tractor performing the hot tap  
is responsible for providing  
proof of such a permit.  
1. Confirm that the installation site meets the minimum upstream and  
downstream pipe diameter requirements.  
2. Weld a two inch mounting adapter on the pipe. Make sure the mount-  
ing adapter is within 5° perpendicular to the pipe centerline (see  
previous page). The pipe opening must be at least 1.875 inches in di-  
ameter.  
3. Connect a two inch process connection on the mounting adapter.  
4. Connect an isolation valve on the process connection. The valve’s  
full open bore must be at least 1.875 inches in diameter.  
5. Hot tap the pipe.  
Warning!  
All flow meter connections,  
isolation valves and fittings for  
hot tapping must have the  
same or higher pressure rat-  
6. Close the isolation valve. Run a static pressure check on the welds. If  
pressure loss or leaks are detected, repair the joint and re-test.  
7. Connect the flow meter to the isolation valve.  
ing as the main pipeline.  
8. Calculate the sensor probe insertion depth as described on the follow-  
ing pages. Insert the sensor probe assembly into the pipe.  
Check upstream and  
downstream piping  
requirements  
Weld mounting  
adapter  
Connect process  
connection  
(flange or NPT)  
Connect  
isolation valve  
Hot tap pipe  
Test for leaks,  
purge pipe  
FLOW  
Connect meter to  
valve, calculate  
insertion depth,  
install flow meter  
Figure 2-5. Hot Tap Sequence  
2-8  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Flow Meter Insertion  
The sensor head must be properly positioned in the pipe. For this rea-  
son, it is important that insertion length calculations are carefully fol-  
lowed. A sensor probe inserted at the wrong depth in the pipe will result  
in inaccurate readings.  
Insertion flow meters are applicable to pipes 2 inch and larger. For pipe  
sizes ten inches and smaller, the centerline of the meter’s sensing head is  
located at the pipe’s centerline. For pipe sizes larger than ten inches, the  
centerline of the sensing head is located in the pipe’s cross section five  
inches from the inner wall of the pipe; i.e., its “wetted” depth from the  
wall to the centerline of the sensing head is five inches.  
Insertion flow meters are available in three probe lengths:  
Standard Probe configuration is used with most flow meter process  
connections. The length, S, of the stem is 29.47 inches.  
Compact Probe configuration is used with compression fitting process  
connections. The length, S, of the stem is 13.1 inches.  
12-Inch Extended Probe configuration is used with exceptionally  
lengthy flow meter process connections. The length, S, of the stem is  
41.47 inches.  
Use the Correct Insertion Formula  
Depending on your flow meter’s process connection, use the applicable  
insertion length formula and installation procedure as follows:  
Flow meters with a compression type connection (NPT or flanged)  
follow the instructions beginning on page 2-10.  
Warning!  
An insertion tool must be  
used for any installation  
where a flow meter is  
inserted under pressure  
greater than 50 psig.  
Flow meters with a packing gland type connection (NPT or flanged)  
configured with an insertion tool, follow the instructions beginning  
on page 2-12.  
Flow meters with a packing gland type connection (NPT or  
flanged) without an insertion tool, follow the instructions beginning  
on page 2-15.  
IM-24-HP  
2-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Installing Flow Meters with a Compression Connection*  
Use the following formula to determine insertion length for flow meters  
(NPT and flanged) with a compression process connection. The installa-  
tion procedure is given on the next page.  
Insertion Length Formula  
I = S – F – R – t  
Where:  
I =  
S =  
Insertion length.  
Stem length – the distance from the center of the sensor head to the base  
of the enclosure adapter (S = 29.47 inches for standard probes; S = 13.1  
inches for compact; S = 41.47 inches for 12-inch extended).  
Distance from the raised face of the flange or top of NPT stem housing to  
the outside of the pipe wall.  
F =  
R =  
R =  
t =  
Pipe inside diameter ÷ 2 for pipes ten inches and smaller.  
Five inches for pipe diameters larger than ten inches.  
Thickness of the pipe wall. (Measure the disk cut-out from the tapping  
procedure or check a piping handbook for thickness.)  
Figure 2-6. Insertion Calculation (Compression Type)  
Example:  
To install a Series 241 meter with a standard probe (S = 29.47 inches) into a 14  
inch schedule 40 pipe, the following measurements are taken:  
F=3 inches  
R=5 inches  
t=0.438 inches  
The insertion length for this example is 21.03 inches. Insert the stem through  
the fitting until an insertion length of 21.03 inches is measured with a ruler.  
*All dimensions are in inches  
2-10  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Insertion Procedure for Meters with a Compression Connection  
Figure 2-7. Flow Meter with Compression Type Fitting  
1. Calculate the required sensor probe insertion length.  
Caution!  
The sensor alignment  
pointer must point  
2. Fully retract the stem until the sensor head is touching the bottom  
of the stem housing. Slightly tighten the compression nut to prevent  
slippage.  
downstream, in the  
direction of flow.  
3. Bolt or screw the flow meter assembly into the process connection.  
Use Teflon tape or pipe sealant to improve the seal and prevent seiz-  
ing on NPT styles.  
Warning!  
To avoid serious injury,  
DO NOT loosen the  
compression fitting  
4. Hold the meter securely while loosening the compression fitting.  
Insert the sensor into the pipe until the calculated insertion length,  
I, is measured between the base of the enclosure adapter and the top  
of the stem housing, or to the raised face of the flanged version. Do  
not force the stem into the pipe.  
under pressure.  
5. Align the sensor head using the sensor alignment pointer. Adjust the  
alignment pointer parallel to the pipe and pointing downstream.  
6. Tighten the compression fitting to lock the stem in position. When  
the compression fitting is tightened, the position is permanent.  
IM-24-HP  
2-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Installing Flow Meters with a Packing Gland Connection*  
Use the formula below to determine the insertion depth for flow meters  
(NPT and flanged) equipped with an insertion tool. To install, see the  
next page for instructions for meters with a permanent insertion tool. For  
meters with a removable insertion tool, see page 2-14.  
Insertion Length Formula  
I = F + R + t – 1.35  
Where:  
I = Insertion length.  
F = Distance from the raised face of the flange or  
top of the process connection for NPT style  
meters to the top outside of the process pipe.  
R = Pipe inside diameter ÷ 2 for pipes ten inches &  
smaller.  
R = Five inches for pipe diameters larger than ten  
inches.  
t = Thickness of the pipe wall. (Measure the disk  
cut-out from the tapping procedure or check a  
piping handbook for thickness.)  
Figure 2-8. Insertion Calculation (Meters with Insertion Tool)  
Example 1: Flange Style Meters:  
To install a Series 241 Flow Meter into a 14 inch schedule 40 pipe, the fol-  
lowing measurements are taken:  
F
=
12 inches  
R = 5 inches  
0.438 inches  
t
=
The example insertion length is 16.09 inches.  
Example 2: NPT Style Meters:  
The length of thread engagement on the NPT style meters is also subtracted in  
the equation. The length of the threaded portion of the NPT meter is 1.18  
inches. Measure the thread portion still showing after the installation and sub-  
tract that amount from 1.18 inches. This gives you the thread engagement  
length. If this cannot be measured use .55 inch for this amount.  
F
=
12 inches  
R = 5 inches  
0.438 inches  
t
=
The example insertion length is 15.54 inches.  
*All dimensions are in inches.  
2-12  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Insertion Procedure for Flow Meters with Permanent Insertion Tool  
Figure 2-9. Flow Meter with Permanent Insertion Tool  
1. Calculate the required sensor probe insertion length (see previous  
page). Measure from the depth marker arrow down the stanchion and  
scribe a mark at the calculated insertion depth.  
Caution!  
The sensor alignment  
pointer must point  
downstream, in the  
direction of flow.  
2. Fully retract the flow meter until the sensor head is touching the bot-  
tom of the stem housing. Attach the meter assembly to the two inch  
full-port isolation valve, if used. Use Teflon tape or pipe sealant to  
improve seal and prevent seizing on NPT style.  
3. Loosen the two packing gland nuts on the stem housing of the meter.  
Loosen the stem lock bolt adjacent to the sensor alignment pointer.  
Align the sensor head using the sensor alignment pointer. Adjust the  
alignment pointer parallel to the pipe and pointing downstream. Tighten  
the stem lock bolt to secure the sensor position.  
Note  
If line pressure is above  
500 psig, it could require  
up to 25 ft lb of torque to  
insert the flow meter.  
Do not confuse this with  
possible interference  
in the pipe.  
4. Slowly open the isolation valve to the full open position. If necessary,  
slightly tighten the two packing gland nuts to reduce the leakage  
around the stem.  
5. Turn the insertion tool handle clockwise to insert the sensor head into  
the pipe. Continue until the top of the upper retractor bracket aligns  
with the insertion length position scribed on the stanchion. Do not  
force the stem into the pipe.  
6. Tighten the packing gland nuts to stop leakage around the stem. Do  
not torque over 20 ft-lb.  
IM-24-HP  
2-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Insertion Procedure for Flow Meters with Removable Insertion Tool  
Figure 2-10. Flow Meter with Removable Insertion Tool  
1. Calculate the required sensor probe insertion length. Measure from  
the depth marker arrow down the stanchion and scribe a mark at the  
calculated insertion depth.  
Caution!  
The sensor alignment  
2. Fully retract the flow meter until the sensor head is touching the bot-  
tom of the stem housing. Attach the meter assembly to the two inch  
full-port isolation valve, if used. Use Teflon tape or pipe sealant to  
improve seal and prevent seizing on NPT style.  
pointer must point  
downstream, in the  
direction of flow.  
3. Remove the two top stem clamp nuts and loosen two stem clamp  
bolts. Slide the stem clamp away to expose the packing gland nuts.  
4. Loosen the two packing gland nuts. Loosen the stem lock bolt adja-  
cent to the sensor alignment pointer. Align the sensor head using the  
sensor alignment pointer. Adjust the alignment pointer parallel to the  
pipe and pointing downstream. Tighten the stem lock bolt to secure  
the sensor position.  
Note  
If line pressure is above  
500 psig, it could require  
up to 25 ft lb of torque to  
insert the flow meter.  
Do not confuse this with  
possible interference  
in the pipe.  
5. Slowly open the isolation valve to the full open position. If necessary,  
slightly tighten the two packing gland nuts to reduce the leakage  
around the stem.  
6. Turn the insertion tool handle clockwise to insert the stem into the  
pipe. Continue until the top of the upper retractor bracket lines up  
with the insertion length mark scribed on the stanchion. Do not force  
the stem into the pipe.  
2-14  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
7. Tighten the packing gland nuts to stop leakage around the stem. Do not  
torque over 20 ft-lbs.  
8. Slide the stem clamp back into position. Torque stem clamp bolts to 15  
ft-lbs. Replace the stem clamp nuts and torque to 10-15 ft-lbs.  
9. To separate the insertion tool from the flow meter, remove four socket  
head cap bolts securing the upper and lower retractor brackets. Remove  
the insertion tool.  
Installation of Meters with Packing Gland Connection (No Insertion Tool)*  
Use the following formula to determine insertion depth for meters with a  
packing gland connection (NPT and flanged) without an insertion tool.  
Insertion Length Formula  
I = S – F – R – t  
Where:  
I = Insertion length.  
S = Stem length – the distance from the cen-  
ter of the sensor head to the base of the  
enclosure adapter (S = 29.47 inches for  
standard probes; S = 41.47 inches for  
12 inch extended probes).  
F = Distance from the raised face of the  
flange or top of NPT stem housing to  
the outside of the pipe wall.  
R = Pipe inside diameter ÷ 2 for pipes ten  
inches & smaller.  
R = Five inches for pipe diameters larger than ten  
inches.  
t = Thickness of the pipe wall. (Measure the disk  
cut-out from the tapping procedure or check a  
piping handbook for thickness.)  
Figure 2-11. Insertion Calculation (Meters without Insertion Tool)  
Example:  
To install a Series 241 Flow Meter with a standard probe (S = 29.47) into  
a 14 inch schedule 40 pipe, the following measurements are taken:  
F = 3 inches  
R = 5 inches  
t = 0.438 inches  
The example insertion length is 21.03 inches.  
*All dimensions are in inches.  
IM-24-HP  
2-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Insertion Procedure for Flow Meters with No Insertion Tool  
(Packing Gland Connection)  
1. Calculate the required sensor probe insertion length.  
Warning!  
The line pressure  
must be less than  
2. Fully retract the stem until the sensor head is touching the bottom of the  
stem housing. Remove the two top stem clamp nuts and loosen two  
stem clamp bolts. Slide the stem clamp away to expose the packing  
gland nuts. Loosen the two packing gland nuts.  
50 psig for installation.  
3. Align the sensor head using the sensor alignment pointer. Adjust the  
alignment pointer parallel to the pipe and pointing downstream.  
Caution!  
The sensor alignment  
pointer must point  
4. Insert the sensor head into the pipe until insertion length, I, is  
achieved. Do not force the stem into the pipe.  
downstream, in the  
direction of flow.  
5. Tighten the packing gland nuts to stop leakage around the stem. Do  
not torque over 20 ft-lbs.  
6. Slide the stem clamp back into position. Torque stem clamp bolts to  
15 ft-lbs. Replace the stem clamp nuts and torque to 10-15 ft-lbs.  
2-16  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Adjusting Meter Orientation  
Depending on installation requirements, you may need to adjust the meter  
orientation. There are two adjustments available. The first rotates the po-  
sition of the LCD display/keypad and is available on both in-line and in-  
sertion meters. The second is to rotate the enclosure position. This ad-  
justment is only allowed on Series 240 In-Line meters.  
Display/Keypad Adjustment (All Meters)  
Figure 2-12. Display/Keypad Viewing Adjustment  
The electronics boards are electrostatically sensitive. Wear a grounding  
wrist strap and make sure to observe proper handling precautions required  
for static-sensitive components. To adjust the display:  
1. Disconnect power to the flow meter.  
2. Loosen the small set screw which secures the electronics enclosure.  
Unscrew and remove the cover.  
3. Loosen the 4 captive screws.  
4. Carefully pull the display/microprocessor board away from the meter  
standoffs. Make sure not to damage the connected ribbon cable.  
5. Rotate the display/microprocessor board to the desired position.  
Maximum turn, two positions left or two positions right (180-  
degrees).  
6. Align the board with the captive screws. Check that the ribbon cable  
is folded neatly behind the board with no twists or crimps.  
7. Tighten the screws. Replace the cover and set screw. Restore power  
to the meter.  
IM-24-HP  
2-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Enclosure Adjustment (Series 240 Only)  
Figure 2-13. Enclosure Viewing Adjustment  
To avoid damage to the sensor wires, do not rotate the enclosure beyond  
180-degrees from the original position. To adjust the enclosure:  
1. Remove power to the flow meter.  
2. Loosen the three set screws shown above. Rotate the display to the  
desired position (maximum 180-degrees).  
3. Tighten the three set screws. Restore power to the meter.  
2-18  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Wiring Connections  
The NEMA 4X enclosure contains an integral wiring compartment with  
one dual strip terminal block (located in the smaller end of the enclo-  
sure). Two 3/4-inch female NPT conduit entries are available for sepa-  
rate power and signal wiring. For all hazardous area installations, make  
sure to use an agency-approved fitting at each conduit entry. If conduit  
seals are used, they must be installed within 18 inches (457 mm) of the  
enclosure.  
Warning!  
To avoid potential electric shock, follow  
National Electric Code safety practices or  
your local code when wiring this unit to a  
power source and to peripheral devices.  
Failure to do so could result in injury or  
death. All AC power connections must be  
in accordance with published CE direc-  
tives. All wiring procedures must be per-  
formed with the power off.  
Input Power Connections  
To access the wiring terminal blocks, locate and loosen the small set  
screw which locks the small enclosure cover in place. Unscrew the  
cover to expose the terminal block.  
AC Power Wiring  
The AC power wire size must be 20 to 10 AWG with the wire stripped  
1/2 inch (14 mm). The wire insulation temperature must meet or exceed  
85°C (185°F). Connect 100 to 240 VAC (25 watts maximum) to the  
Hot and Neutral terminals on the terminal block. Connect the ground  
wire to the safety ground lug. Torque all connections to 4.43 to 5.31 in-  
lbs (0.5 to 0.6 Nm). Use a separate conduit entry for signal lines to re-  
duce the possibility of AC noise interference.  
Caution!  
The AC wire insulation tempera-  
ture rating must meet or exceed  
85°C (185°F).  
Figure 2-14. AC Power Connections  
AC Terminals  
DC Power Wiring  
The DC power wire size must be 20 to 10 AWG with the wire stripped  
1/2 inch (14 mm). Connect 18 to 36 VDC (100 mA maximum current  
draw) to the +Pwr and –Pwr terminals on the terminal block. Torque all  
connections to 4.43 to 5.31 in-lbs (0.5 to 0.6 Nm).  
Figure 2-15. DC Power Connections  
DC Terminals  
IM-24-HP  
2-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
4-20 mA Output Connections  
The standard Innova-Mass Flow Meter has a single 4-20 mA loop. Two  
additional loops are available on the optional communication board. The  
4-20 mA loop current is controlled by the meter electronics. The electron-  
ics must be wired in series with the sense resistor or current meter. The  
current control electronics require 12 volts at the input terminals to oper-  
ate correctly.  
The maximum loop resistance (load) for the current loop output is depend-  
ent upon the supply voltage and is given in Figure 2-16. The 4-20 mA loop  
is optically isolated from the flow meter electronics.  
Rload is the total resistance in the loop, including the wiring resistance  
(Rload = Rwire + Rsense ). To calculate Rmax, the maximum Rload for the loop,  
use the maximum loop current, 20 mA. The voltage drop in the loop due  
to resistance is 20 mA times Rload and this drop is subtracted from the in-  
put voltage. Thus:  
The maximum resistance Rload = Rmax = 50 (Vsupply – 12V).  
*
Figure 2-16. Load Resistance Versus Input Voltage  
Figure 2-17. Isolated 4–20 mA Output with External Power Supply  
2-20  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Figure 2-18. Non-Isolated 4–20 mA Output Using Meter Input Power Supply  
Figure 2-19. Isolated 4–20 mA Output using Meter Provided Power Supply  
Pulse Output Connections  
The pulse output is used for a remote counter. When the preset volume or  
mass (defined in the totalizer settings, see page 3-8) has passed the meter,  
the output provides a 50 millisecond square pulse.  
The pulse output optical relay is a normally-open single-pole relay. The  
relay has a nominal 200 volt/160 ohm rating. This means that it has a  
nominal on-resistance of 160 ohms, and the largest voltage that it can  
withstand across the output terminals is 200 volts. However, there are  
current and power specifications that must be observed. The relay can  
conduct a current up to 40 mA and can dissipate up to 320 mW. The relay  
output is isolated from the meter electronics and power supply.  
There are three connection options for the pulse output–the first with a  
separate power supply (Figure 2-20), the second using the flow meter  
power supply (Figure 2-21)(DC powered units only), and the third using the  
internal 24 VDC power supply (Figure 2-22)(AC powered units only). Use  
the first option with a separate power supply (5 to 36 VDC) if a specific  
voltage is needed for the pulse output. Use the second configuration if the  
voltage at the flow meter power supply is an acceptable driver voltage for  
the load connected. (Take into account that the current used by the pulse  
load comes from the meter’s power supply). Use the third configuration if  
you have an AC powered unit only. In any case, the voltage of the pulse  
output is the same as the voltage supplied to the circuit.  
IM-24-HP  
2-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Figure 2-20. Isolated Pulse Output with External Power Supply  
Figure 2-21. Non-Isolated Pulse Output Using Input Power Supply  
Figure 2-22. Isolated Pulse Output Using Meter Provided Power Supply  
2-22  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Alarm Output Connections  
One alarm output (Alarm 1) is included on the standard Innova-Mass™  
Flow Meter. Two or more alarms (Alarm 2 and Alarm 3) are included on  
the optional communication board. The alarm output optical relays are  
normally-open single-pole relays. The relays have a nominal 200 volt/160  
ohm rating. This means that each relay has a nominal on-resistance of 160  
ohms and the largest voltage that it can withstand across the output termi-  
nals is 200 volts. However, there are current and power specifications that  
must be observed. The relay can conduct a current up to 40 mA and can  
dissipate up to 320 mW. The relay output is isolated from the meter elec-  
tronics and power supply. When the alarm relay is closed, the current  
draw will be constant. Make sure to size Rload appropriately.  
There are three connection options for the alarm output–the first with a  
separate power supply (Figure 2-23), the second using the flow meter  
power supply (Figure 2-24)(DC powered units only) and the third with the  
meter provided power supply (Figure 2-25)(AC powered units only). Use  
the first option with a separate power supply (5 to 36 VDC) if a specific  
voltage is needed for the alarm output. Use the second configuration if the  
voltage at the flow meter power supply is an acceptable driver voltage for  
the load connected. (Take into account that the current used by the alarm  
load comes from the meter’s power supply). Use the third if you have an  
AC powered unit only. In any case, the voltage of the alarm output is the  
same as the voltage supplied to the circuit.  
The alarm output is used for transmitting high or low process conditions  
as defined in the alarm settings (see page 3-7).  
Figure 2-23. Isolated Alarm Output with External Power Supply  
Figure 2-24. Non-Isolated Alarm Output Using Internal Power Supply  
IM-24-HP  
2-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2 Installation  
Series 24-HP Instruction Manual  
Figure 2-25. Isolated Alarm Output Using Meter Provided Power Supply  
Remote Electronics Wiring  
The remote electronics enclosure should be mounted in a convenient,  
easy to reach location. For hazardous location installations, make sure to  
observe agency requirements for installation. Allow some slack in the in-  
terface cable between the junction box and the remote electronics enclo-  
sure. To prevent damage to the wiring connections, do not put stress on  
the terminations at any time.  
The meter is shipped with temporary strain relief glands at each end of  
the cable. Disconnect the cable from the meter’s terminal block inside  
the junction box–not at the remote electronics enclosure. Remove both  
glands and install appropriate conduit entry glands and conduit. When  
installation is complete, re-connect each labeled wire to the correspond-  
ing terminal position on the junction box terminal block. Make sure to  
connect each wire pair’s shield. Note: incorrect connection will cause the  
meter to malfunction.  
PWR  
GND  
Sensor V1  
Sensor V2  
Shield  
Figure 2-26. Junction Box Sensor Connections  
Note: Numeric code in junction box label matches wire labels.  
2-24  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 2 Installation  
Optional Input Electronics Wiring  
The meter has two optional input wiring terminals. These can be used to  
input a Remote or Second RTD input in the case of an Energy Monitoring  
meter, for the input of a Remote Pressure Transducer, to pass a Contact  
Closure or for a Remote Density measurement to name a few. In any  
case, the wiring diagram will be included with the meter if any of the op-  
tions are specified. Otherwise, the optional terminal blocks will be left  
blank and non functional.  
Optional Energy EMS Input Electronics Wiring  
The recommended customer supplied second RTD is a Class A 1000 ohm  
4-wire platinum RTD. If a second RTD is not being used, then the fac-  
tory supplied 1000 ohm resistor needs to be installed in its place.  
IM-24-HP  
2-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Chapter 3 Operating Instructions  
After installing the Innova-Mass Vortex Flow Meter, you are  
ready to begin operation. The sections in this chapter explain the  
display/keypad commands, meter start-up and programming. The  
meter is ready to operate at start up without any special pro-  
gramming. To enter parameters and system settings unique to  
your operation, see the following pages for instructions on using  
the setup menus.  
Flow Meter Display/Keypad  
The flow meter’s digital electronics allow you to set, adjust and  
monitor system parameters and performance. A full range of  
commands are available through the display/keypad. The LCD  
display gives 2 x 16 characters for flow monitoring and pro-  
gramming. The six push-buttons can be operated with the enclo-  
sure cover removed. Or, the explosion-proof cover can remain  
in place and the keypad operated with a hand-held magnet posi-  
tioned at the side of the enclosure as shown in the illustration at  
the left.  
Pro-VTM  
VorTek  
Instruments,  
LLC  
From the Run Mode, the  
key allows  
ENTER  
access to the Setup Menus (through a  
Display/Keypad  
Commands  
password screen). Within the Setup Menus,  
pressing  
activates the current field.  
ENTER  
To set new parameters, press the  
key  
ENTER  
until an underline cursor appears. Use the  
EXIT  
ENTER  
ꢀꢁꢂꢃ keys to select new parameters.  
Innova-Mass™  
Press  
to continue. (If change is not  
ENTER  
alllowed,  
has no effect.) All outputs  
ENTER  
are disabled when using the Setup Menus.  
SINSieTRrUrMaENTS  
The  
key is active within the Setup Menus.  
EXIT  
When using a Setup Menu,  
returns you to the  
EXIT  
Run Mode. If you are changing a parameter and  
make a mistake, allows you to start over.  
EXIT  
The ꢀꢁꢂꢃkeys advance through each screen  
of the current menu. When changing a system  
parameter, all  
ꢀꢁꢂꢃkeys are available to enter  
new parameters.  
Figure 3-1. Flow Meter Display/Keypad  
IM-24-HP  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Start-Up  
To begin flow meter operation:  
1. Verify the flow meter is installed and wired as described in Chapter  
2.  
2. Apply power to the meter. At start up, the unit runs a series of self-  
tests that check the RAM, ROM, EPROM and all flow sensing com-  
ponents. After completing the self-test sequence, the Run Mode  
screens appear.  
Note  
Starting the flow meter  
or pressing EXIT will  
always display the Run  
Mode screens.  
3. The Run Mode displays flow information as determined by system  
settings. Press the ꢀꢁ arrow keys to view the Run Mode screens.  
4. Press the ENTER key from any Run Mode screen to access the Setup  
Menus. Use the Setup Menus to configure the meter’s multi-  
parameter features to fit your application.  
Run Mode  
Screens  
ENTER  
Mass Flow  
Password  
Rate  
ENTER  
Volume  
Flow Rate  
Press Exit to return  
to Run Mode  
Setup  
Menus  
Temperature  
Pressure  
Energy  
*
Density  
Total  
Use  
keys to access  
each item  
Alarm 1  
Status  
Alarm 2  
Status  
Alarm 3  
Status  
Fluid  
Date & Time  
3-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Using the Setup Menus  
Programming the Flow Meter  
1. Enter the Setup Menu by pressing the ENTER key until prompted for a password. (All  
outputs are disabled while using the Setup Menus.)  
2. Use the ꢀꢁꢂꢃ keys to select the password characters (1234 is the factory-set  
password). When the password is correctly displayed, press ENTER to continue.  
3. Use the Setup Menus described on the following pages to customize the multi-  
parameter features of your Innova-Mass Flow Meter. (The entire lower display line is  
available for entering parameters.)  
4. To activate a parameter, press ENTER. Use the ꢀꢁꢂꢃ keys to make selections. Press  
ENTER to continue. Press EXIT to save or discard changes and return to Run Mode.  
5. Program the UNITS menu first because later menus will be based on the units  
selected.  
IM-24-HP  
3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Output Menu  
ENTER  
Run Mode  
Password  
ENTER  
Output  
Menu  
Use  
keys to access menus  
< Measure >  
None  
Mass  
Volume  
4-20mA Output 1  
More >  
< 4mA = xxxx >  
< 20mA = xxxx >  
xxxx  
< TimeConst(Sec)  
***Energy  
xxxx  
xxxx  
Temp 1,2  
Press  
***see  
below  
Density  
< Measure >  
None  
4-20mA Output 2  
More >  
Mass  
*see below  
Volume  
***Energy  
Temp 1,2  
Press  
< 4mA = xxxx >  
xxxx  
< 20mA = xxxx >  
xxxx  
< TimeConst(Sec)  
xxxx  
***see  
below  
Density  
4-20mA Output 3  
More >  
< Measure >  
None  
*see below  
Mass  
< 4mA = xxxx >  
xxxx  
< 20mA = xxxx >  
xxxx  
< TimeConst(Sec)  
xxxx  
Volume  
***Energy  
Temp 1,2  
Press  
Density  
***see  
below  
Modbus Units  
(Internal/Display)  
**see below  
Modbus Order  
0-1:2-3  
1-0:3-2  
2-3:0-1  
**see below  
**see below  
Comm Protocol  
Modbus RTU  
(None1, None2, Odd,  
Even)  
Baud Rate  
19200  
**see below  
**see below  
Address  
1
* - Physical Layer not available on Two  
Wire Mass – Accessible via HART  
** - Modbus not available on Two Wire  
Mass  
*** - Energy available on EMS meters only  
3-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Example for Setting an Output  
The following shows how to set Output 1 to measure mass flow with 4 mA = 0 lb/hr and 20 mA = 100 lb/hr with  
a time constant of 5 seconds. (All outputs are disabled while using the Setup Menus.)  
First, set the desired units of measurement:  
1. Use ꢂꢃ keys to move to the Units Menu (see page 3-9).  
2. Press key until Mass Flow Unit appears. Press ENTER.  
3. Press key until lb appears in the numerator. Press key to move the underline cursor to the  
denominator. Press the key until hr appears in the denominator. Press ENTER to select.  
4. Press key until Units Menu appears.  
Second, set the analog output:  
1. Use ꢂꢃ keys to move to the Output Menu.  
2. Press the key until 4-20 mA Output 1 appears.  
3. Press key to access Measure selections. Press ENTER and press the key to select Mass. Press ENTER.  
4. Press key to set the 4 mA point in the units you have selected for mass of lb/hr. Press ENTER and  
use ꢀꢁꢂꢃ keys to set 0 or 0.0. Press ENTER.  
5. Press key to set the 20 mA point. Press ENTER and use ꢀꢁꢂꢃ keys to set 100 or 100.0. Press ENTER.  
6. Press key to select the Time Constant. Press ENTER and use ꢀꢁꢂꢃ keys to select 5. Press ENTER.  
7. Press the EXIT key and answer YES to permanently save your changes.  
IM-24-HP  
3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Display Menu  
ENTER  
Run Mode  
Password  
ENTER  
Display  
Menu  
Use  
keys to access menus  
Cycle Time(Sec)  
0
If Cycle Time is set to zero, manual advance is required  
Number of Digits  
2
Used to set t he number of digits displayed after  
decimal point  
Display TC(sec)  
1
TC = Display Time Constant, used to smooth display  
MF Vf Te Pr De T  
Y or N  
Mf = Mass Flow  
Vf = Volume Flow  
Te = Temperature  
Pr = Pressure  
De = Density  
For each parameter:  
T = Total  
Select Yes to view parameter in Run Mode  
Select No to hide parameter in Run Mode  
A1 = Alarm 1 Status  
A2 = Alarm 2 Status  
A3 = Alarm 3 Status  
Fl = Fluid  
A1 A2 A3 Fl Dt E  
Y or N  
Dt = Density  
* Energy EMS Meters Only  
* E = Energy  
Use the Display Menu to set the cycle time for automatic screen sequencing used in the Run  
Mode, change the precision of displayed values, smooth the values or enable or disable each item  
displayed in the Run Mode screens.  
Example for Changing a Run Mode Display Item  
The following shows how to remove the temperature screen from the Run Mode screens. Note: all outputs  
are disabled while using the Setup Menus.  
1. Use ꢂꢃ keys to move to the Display Menu.  
2. Press key until Mf Vf Pr Te De T appears.  
3. Press ENTER to select. Press key until the cursor is positioned below Te.  
4. Press key until N appears. Press ENTER to select.  
5. Press EXIT and then ENTER to save changes and return to the Run Mode.  
3-6  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Alarms Menu  
Example for Setting an Alarm  
The following shows how to set Alarm 1 to activate if the mass flow rate is greater than 100 lb/hr. You can check the  
alarm configuration in the Run Mode by pressing the ꢀꢁ keys until Alarm [1] appears. The lower line displays the  
mass flow rate at which the alarm activates. Note: all outputs are disabled while using the Setup Menus.  
First, set the desired units of measurement:  
1. Use ꢂꢃ keys to move to the Units Menu (see to page 3-9).  
2. Press key until Mass Flow Unit appears. Press ENTER.  
3. Press key until lb appears in the numerator. Press key to move the underline cursor to the  
denominator. Press the key until hr appears in the denominator. Press ENTER to select.  
4. Press key until Units Menu appears.  
Second, set the alarm:  
1. Use ꢂꢃ keys to move to the Alarms Menu.  
2. Press the key until Alarm Output 1 appears.  
3. Press key to access Measure selections. Press ENTER and use the key to select Mass. Press ENTER.  
4. Press key to select the alarm Mode. Press ENTER and use key to select HIGH Alarm. Press ENTER.  
5. Press key to select the value that must be exceeded before the alarm activates. Press ENTER and use  
ꢀꢁꢂꢃ keys to set 100 or 100.0. Press ENTER.  
6. Press the EXIT key to save your changes. (Alarm changes are always permanently saved.)  
(Up to three alarm outputs are available depending on meter configuration.)  
IM-24-HP  
3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Totalizer #1 Menu  
Use the Totalizer Menu to configure and monitor the totalizer. The totalizer output is a 50  
millisecond (.05 second) positive pulse (relay closed for 50 milliseconds). The totalizer cannot  
operate faster than one pulse every 100 millisecond (.1 second). A good rule to follow is to set the  
unit per pulse value equal to the maximum flow in the same units per second. This will limit the  
pulse to no faster than one pulse every second.  
Example for Setting the Totalizer  
The following shows how to set the totalizer to track mass flow in kg/sec. (All outputs are disabled while using  
the Setup Menus.)  
First, set the desired units of measurement:  
1. Use ꢂꢃ keys to move to the Units Menu (see to page 3-9).  
2. Press key until Mass Flow Unit appears. Press ENTER.  
3. Press key until kg appears in the numerator. Press key to move the underline cursor to the  
denominator. Press the key until sec appears in the denominator. Press ENTER to select.  
4. Press key until Units Menu appears.  
Second, set the pulse output:  
1. Use ꢂꢃ keys to move to the Totalizer Menu.  
2. Press the key until Totaling appears.  
3. Press ENTER and press the key to select Mass. Press ENTER.  
4. Press key to set the pulse output in the units you have selected for mass flow of kg/sec. Press ENTER  
and use ꢀꢁꢂꢃ keys to set the pulse value equal to the maximum flow in the same units per second.  
Press ENTER.  
5. To reset the totalizer, press key until Reset Total? appears. Press ENTER and the key to reset the  
totalizer if desired. Press ENTER.  
6. Press the EXIT key and answer YES to permanently save your changes.  
3-8  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Totalizer #2 Menu  
Use the Totalizer #2 to Monitor Flow or Energy. Note that Totalizer #2 does not operate a relay, it is  
for monitoring only.  
IM-24-HP  
3-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Energy Menu – For EMS Energy Meters Only  
ENTER  
Run Mode  
Password  
ENTER  
Energy  
Menu  
Use  
keys to access menus  
Loc in Sent  
Flow  
Yes or No  
Heating  
System  
Yes or No  
% Returned  
xxx  
Configuration:  
There are several possibilities regarding the measurement of water or steam energy given the location  
of the meter and the use of a second RTD. The table below summarizes the possibilities:  
Fluid  
Water  
Water  
Water  
Steam  
Meter Location  
Second RTD  
Measurement  
“Sent” Flow Line “Return Flow Line  
“Return” Flow Line “Sent” Flow Line  
“Sent” Flow Line None  
Change in Energy  
Change in Energy  
Outgoing Energy  
“Sent” Flow Line “Return” Flow Line Change in Energy  
(condensate)  
Steam  
“Sent” Flow Line None  
Outgoing Energy  
As above, you must properly configure the meter in the Energy Menu.  
1. Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the above  
table  
2. Heating System? Select Yes for a hot water system used for heating. Select No for a chilled  
water system used for cooling. Always select Yes for a steam system.  
3. % Returned. Select a number between 0% and 100%. Estimate the amount of water that returns.  
It is usually 100%, or can be less than 100% if historical data shows the amount of makeup water  
used. If a second RTD is not used, set to 0%. When 0% is selected, the energy calculation  
represents the outgoing energy only (no return energy is subtracted). NOTE: the meter ships  
from the factory assuming 0% return and has a 1000 ohm resistor installed in the RTD #2  
wiring location. This needs to be removed if the meter is to be used in a manner other than  
with 0% return and with the customer supplied RTD in its place.  
3-10  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Fluid Menu  
ENTER  
Run Mode  
Password  
ENTER  
Fluid  
Use  
Menu  
keys to access menus  
< Liquid  
Water  
Ammonia  
Chlorine  
Flowing Fluid  
Liquids >  
Goyal-Dorais >  
API 2540 >  
< Mole Weight >  
xxxx  
< CRIT PRESS >  
xxxx  
< CRIT TEMP >  
xxxx  
< CRIT Z >  
xxxx  
< AL >  
xxxx  
< BL  
xxxx  
Nat Gas AGA8 >  
Real Gas >  
Other Gas >  
< Density  
@
60F >  
< K0 >  
xxxx  
< K1 >  
xxxx  
< AL >  
xxxx  
< BL  
xxxx  
xxxx  
< Rel. Density >  
xxxx  
< MoleFract N2 >  
xxxx  
<MoleFract CO2>  
xxxx  
<RefTemp(F)>  
xxxx  
< Ref Press(PSIA)  
xxxx  
STD Temp (F)  
xxxx  
< Gas  
Steam T &P Comp  
Steam T Comp  
Air  
Steam T Comp  
is for VT models  
STD Press (PSIA)  
xxxx  
Argon  
Ammonia  
CO  
CO2  
Helium  
Hydrogen  
Methane  
Nitrogen  
Oxygen  
NORM Temp (C)  
xxxx  
NORM Press (KPA)  
xxxx  
< Spec Gravity >  
xxxx  
< Compress (Z) >  
xxxx  
< Viscosity  
xxxx  
Use the Fluid Menu to configure the flow meter for use with common gases, liquids and steam.  
Your flow meter is pre-programmed at the factory for your application’s process fluid.  
Reference Richard W. Miller, Flow Measurement Engineering Handbook (Second Edition,  
1989), page 2-67 for definition and use of the Goyal-Doraiswamy equation and page 2-68 for  
the definition and use of the API 2540 equation. Also, see Appendix C for Fluid Calculation  
equations.  
The units of measurement used in the Fluid Menu are preset and are as follows:  
Mole Weight = lbm/(lbm·mol), CRIT PRESS = psia, CRIT TEMP = °R, Density = Kg/m3 and  
Viscosity = cP (centipoise).  
IM-24-HP  
3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Units Menu  
Use the Units Menu to configure the flow meter with the desired units of measurement. (These  
are global settings and determine what appears on all screens.  
3-12  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Time & Date Menu  
ENTER  
Run Mode  
Password  
ENTER  
Time & Date  
Menu  
Use  
keys to access menus  
Set Time  
xx:xx:xx  
Set Date  
xx/xx/xx  
Use the Time and Date Menu to enter the correct time and date into the flow meter’s  
memory. The parameters are used in the Run Mode and the alarm and system log  
files.  
Note: Time is displayed in AM/PM format, but military format is used to set the  
time. For example, 1:00 PM is entered as 13:00:00 in the Set Time menu.  
Example for Setting the Time  
How to set the time to 12:00:00. You can check the time in the Run Mode by pressing the ꢀꢁ keys  
until the Time & Date screen appears. Note: all outputs are disabled while using the Setup Menus.  
1. Use ꢂꢃ keys to move to the Time and Date Menu.  
2. Press key until Set Time appears. Press ENTER.  
3. Press key until 1 appears. Press key to move the underline cursor to the next digit.  
Press the key until 2 appears. Continue sequence until all desired parameters are en-  
tered. Press ENTER to return to the Time and Date Menu.  
4. Press EXIT to return to the Run Mode.  
IM-24-HP  
3-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Diagnostics Menu  
ENTER  
Run Mode  
Password  
ENTER  
Diagnositcs  
Menu  
Use  
keys to access menus  
Simulate Vortex  
Frequency (Hz)  
Sim Vor Freq  
xxx  
Simulate Temperature  
(degrees F)  
Sim Temp 1,2  
xxx  
Simulate Pressure  
(PSIA)  
Sim Pressure  
xxx  
Highest Recorded  
Velocity (ft/sec)  
Highest Velocity  
xxx  
Highest Recorded  
Temperature (degrees F)  
Highest Temp 1,2  
xxx  
Highest Recorded  
Pressure (PSIA)  
Highest Pressure  
xxx  
Momentarily displayed  
SysLog File # xx  
Use Left andRight  
arrows to access all  
system log flies  
System LOG  
xx Files (ENTER)  
System Log File  
Time  
Date  
Clear SysLOG?  
YES or NO  
Press EXIT to return  
to System LOG  
Use the Diagnostics Menu to simulate operation and review the system files. The system log files  
contain time/date stamped messages including: power on, power off, programming time outs,  
parameter faults, incorrect password entry and other various information relative to system  
operation and programming.  
The simulated inputs are for testing the meter to verify that the programming is correct.  
Simulated vortex frequency allows you to enter any value for the sensor input in Hz. The meter  
will calculate a flow rate based on the corresponding value and update all analog outputs (the  
totalizer display and output is not affected by a simulated frequency). The simulated  
pressure and temperature settings work the same way. The meter will output these new values  
and will use them to calculate a new density for mass flow measurement. Note: when your  
diagnostic work is complete, make sure to return the values to zero to allow the electronics to use  
the actual transducer values.  
If the meter display indicates a temperature or pressure fault, a substitute value can be entered to  
allow flow calculations to continue at a fixed value until the source of the fault is identified and  
corrected. Use only the units listed above for simulated values. If different units are  
displayed, the value must be converted into the units listed above, and the displayed value  
will be automatically converted into the display units.  
3-14  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 3 Operation  
Calibration Menu  
The Calibration Menu contains the calibration coefficients for the flow meter. These values  
should by changed only by properly trained personnel. The Vortex Coef Ck and Low Flow  
Cutoff are set at the factory. Consult the factory for help with these settings if the meter is  
showing erratic flow rate.  
IM-24-HP  
3-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3 Operation  
Series 24-HP Instruction Manual  
Password Menu  
ENTER  
Run Mode  
Password  
ENTER  
Password  
Menu  
Use  
keys to access menus  
Set Password  
1234  
Use the Password Menu to set or change the system password. The factory-set password  
is 1234.  
3-16  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 4 Troubleshooting & Repair  
Chapter 4 Troubleshooting and Repair  
Warning!  
Before attempting any flow  
meter repair, verify that the  
line is not pressurized.  
Always remove main power  
before disassembling any  
part of the mass flow meter.  
f
G
fi  
A
4- 20(1),Zero  
xxxx  
Hidden Diagnostics Menus  
The menus shown to the left can be  
accessed using the password 16363, then  
moving to the display that reads  
A1  
A3  
A2  
A4  
4- 20(1),FScale  
xxxx  
Kc  
It  
4-20(2), Zero  
xxxx  
Kb  
*
“Diagnostics Menu” and pressing ENTER  
(rather than one of the arrow keys).  
4-20(2),  
Fscale  
xxxx  
V
Re  
Rtd1 = x.x  
Rtd2 = x.x  
4-20(3), Zero  
xxxx  
Use the right arrow key to move to the  
second column. Press EXIT to move from  
the second column back to the first, press  
EXIT while in the first column to return to  
the setup menus.  
Pe(v) = 0.0  
Pv(v) = 0.0  
4-20(3),  
Fscale  
xxxx  
Alarm (1) Test  
Low  
Std = 1.000  
Nrml = 1.000  
Alarm (2) Test  
Low  
Visc = xxxx  
Cp  
Caution: password 16363 will allow full  
access to the configuration and should be  
used carefully to avoid changes that can  
adversely alter the function of the meter.  
Alarm (3) Test  
Low  
Ck  
Lvl  
Reynolds Corr.  
Adj. Filter  
xx dB  
Gain Control  
Filter Control  
Each of the menus to the left will first be  
defined followed by specific troubleshoot-  
ing steps.  
O
I
Pulse Out Queue  
xxxxxxxxxx  
High Pass Filt.  
0.33  
TOF  
G
f
Factory Defaults  
Meter Type  
Sig. Rev  
Micro Rev  
AD  
F
R
PT  
T
V
Config Code  
1BFE  
Spi Err  
Rcv  
Sent  
Test Pulse Out  
A2D Ref.  
Resistor  
2700  
Not Present on  
M22 Models  
*
Pres Cal  
Current  
Press 9 C’s  
More >  
RTD 1  
More >  
RTD 2  
More >  
Energy EMS Meters  
Only  
**  
**  
Min Delta H  
1
IM-24-HP  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Troubleshooting & Repair  
Series 24-HP Instruction Manual  
Column One Hidden Diagnostics Values  
f = vortex shedding frequency (Hz).  
fi = adaptive filter – should be approximately 25% higher than  
the vortex shedding frequency, this is a low-pass filter. If the  
meter is using the Filter Control (see below) in the manual  
mode, fi will be displayed as fm.  
G = gain (applied to vortex signal amplitude). Gain defaults to  
1.0 and can be changed using the Gain Control (see below).  
A = Amplitude of vortex signal in Volts rms.  
A1, A2, A3, A4 = A/D counts representing the vortex signal  
amplitude. Each stage (A1-A4) cannot exceed 512. Beginning  
with stage A1, the A/D counts increase as the flow increases.  
When stage A1 reaches 512, it will shift to stage A2. This will  
continue as the flow rate increases until all 4 stages read 512 at  
high flow rates. Higher flow rates (stronger signal strength)  
will result in more stages reading 512.  
Kc, It, Kb = profile equation (factory use only). Model M23  
only  
V = calculated average pipe velocity (ft/sec).  
Re = calculated Reynolds number.  
RTD1 = resistance value of integral RTD in ohms.  
RTD2 = optional RTD resistance value same as above  
Pe(v) = pressure transducer excitation voltage  
Pv(v) = pressure transducer sense voltage.  
Stnd = density of fluid at standard conditions  
Nrml = density of fluid at normal conditions  
Viscosity = calculated viscosity of flowing fluid  
Ck = calculated Ck at current operating conditions. Ck is a  
variable in the equation that relates signal strength, density, and  
velocity for a given application. It is used for noise rejection  
purposes. Ck directly controls the fi value (see above). If the  
Ck is set too low (in the calibration menu), then the fi value  
will be too low and the vortex signal will be rejected resulting  
in zero flow rate being displayed. The calculated Ck valun in  
this menu can be compared to the actual Ck setting in the cali-  
bration menu to help determine if the Ck setting is correct.  
4-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 4 Troubleshooting & Repair  
Lvl = threshold level. If the Low Flow Cutoff in the calibra-  
tion menu is set above this value, the meter will read zero flow.  
The Lvl level can be checked at no flow. At no flow, the Lvl  
must be below the Low Flow Cutoff setting or the meter will  
have an output at no flow.  
Adj. Flilter = adjustable filter. Displays the filtering in deci-  
bels. Normally reads zero. If this value is consistently -5 or  
-10, for example, the Ck or density setting may be wrong.  
O,I = factory use only.  
Pulse Out Queue = Pulse output queue. This value will accu-  
mulate if the totalizer is accumulating faster than the pulse out-  
put hardware can function. The queue will allow the pulses to  
“catch up” later if the flow rate decreases. A better practice is  
to slow down the totalizer pulse by increasing the value in the  
(unit)/pulse setting in the totalizer menu.  
TOF, G, f = factory use only.  
Sig. Rev = Signal board hardware and firmware revision.  
Miro Rev = Microprocessor board hardware and firmware re-  
vision.  
AD, R, T, F, PT, V = factory use only.  
SPR Err, Rcv, Sent = factory use only.  
Column Two Hidden Diagnostics Values  
4-20(1) Zero = Analog counts to calibrate zero on analog out-  
put 1.  
4-20(1) FScale = Analog counts to cal. full scale on analog  
output 1.  
4-20(2) Zero = Analog counts to calibrate zero on analog out-  
put 2.  
4-20(2) FScale = Analog counts to cal. full scale on analog  
output 2.  
4-20(3) Zero = Analog counts to calibrate zero on analog out-  
put 3.  
4-20(3) FScale = Analog counts to cal. full scale on analog  
output 3.  
Alarm (1) Test = Used as a test to verify that the alarm circuit  
is functioning. When low is selected the alarm will initiate a  
low alarm on the output. When High is selected it will give a  
high alarm on the output.  
IM-24-HP  
4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Troubleshooting & Repair  
Series 24-HP Instruction Manual  
Alarm (2) Test = Used as a test to verify that the alarm circuit  
is functioning. When low is selected the alarm will initiate a  
low alarm on the output. When High is selected it will give a  
high alarm on the output.  
Alarm (3) Test = Used as a test to verify that the alarm circuit  
is functioning. When low is selected the alarm will initiate a  
low alarm on the output. When High is selected it will give a  
high alarm on the output.  
Reynolds Corr. = Reynolds number correction for the flow  
profile. Set to Enable for M23 insertion and set to Disable for  
M22 inline.  
Gain Control = Manual gain control (factory use only). Leave  
set at 1.  
Filter control = Manual filter control. This value can be  
changed to any number to force the fi value to a constant. A  
value of zero activates the automatic filter control which sets fi  
at a level that floats above the f value.  
High Pass Filter = Filter setting – Factory use only  
Factory Defaults = Reset factory defaults. If you change this  
to Yes and press Enter, all the factory configuration is lost and  
you must reconfigure the entire program. Consult the factory  
before performing this process, it is required only in very rare  
cases.  
Meter Type = Insertion (M23) or Inline (M22) meter.  
Config Code = Factory Use Only  
Test Pulse Out = Force totalizer pulse. Set to Yes and press  
enter to send one pulse. Very useful to test totalizer counting  
equipment.  
A2D Ref. Resistor = Factory Use Only  
Factory Defaults = Reset to factory defaults. If you change  
this to YES and press ENTER, all factory configuration is lost  
and you must reconfigure the entire program. Consult the fac-  
tory before performing this process, it is required only in very  
rare cases.  
Force Tot Pulse = Force totalizer pulse. Set to YES and press  
ENTER to send one pulse. Very useful to test totalizer count-  
ing equipment.  
Pressure 9Cs = Nine pressure coefficients unique to the pres-  
sure transducer. Use the RIGHT ARROW to access all nine  
coefficients.  
4-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 4 Troubleshooting & Repair  
Pressure Cal Current = Calibration value for the electronics  
and pressure transducer combination. Consult Factory for  
value.  
RTD1. Press the RIGHT ARROW to access:  
o Ro = RTD resistance at 0°C (1000 ohms).  
o A = RTD coefficient A (.0039083).  
o B = RTD coefficient B (-5.775e-07).  
o Slope = unique value for each set of electronics.  
o Int = unique value for each set of electronics.  
RTD2 = Second RTD configuration, for special applications  
only.  
Min. Delta H – Energy EMS meters only. Sets the deadband  
for totalization to begin. Must be greater than this number (1  
default) to initiate the totalizer.  
Analog Output Calibration  
To check the 4–20 mA circuit, connect a DVM in series with the  
output loop. Select zero or full scale (from the second column of  
the hidden diagnostics) and then actuate the enter key twice. This  
action will cause the meter to output its 4 mA or 20 mA condition.  
If the DVM indicates a current greater than 0.006 mA from 4 or  
20, adjust the setting up or down until the output is calibrated.  
Note: these settings are not for adjusting the output zero and span  
to match a flow range, that function is located in the Output Menu.  
IM-24-HP  
4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Troubleshooting & Repair  
Series 24-HP Instruction Manual  
Troubleshooting the Flow Meter  
Symptom: Output at no Flow  
1. The low flow cutoff is set too low. At no flow, go to the  
first column of the hidden diagnostics menu and record the Lvl  
value. The low flow cutoff must be set above this value.  
2. Example: at no flow , Lvl = 25. Set the low flow cutoff in the  
Calibration Menu to approximately 28 and the meter will no  
longer read a flow rate at no flow.  
Symptom: Erratic Output  
1. The flow rate may be too low, just at the cutoff of the meter  
range, and the flow cycles above and below the cutoff making  
an erratic output. The meter range is stamped on the label on  
the outside of the electronics enclosure cover (based on appli-  
cation conditions when the meter was ordered). Consult the  
factory if necessary to confirm the meter range based on current  
operating conditions. It may be possible to lower the low flow  
cutoff to increase the meter range. See the example above for  
output at no flow, only this time the low flow cutoff is set too  
high. You can lower this value to increase the meter range as  
long as you do not create the output at no flow condition previ-  
ously described.  
2. Mechanical installation may be incorrect. Verify the straight  
run is adequate as described in Chapter 2. For in-line meters,  
make sure the meter is not installed backwards and there are no  
gaskets protruding into the flow stream. For insertion meters,  
verify the insertion depth and flow direction.  
3. The meter may be reacting to actual changes in the flow stream.  
The output can be smoothed using a time constant. The dis-  
played values can be smoothed using the time constant in the  
Display Menu. The analog outputs can be smoothed using the  
time constant in the Output Menu. A time constant of 1 will  
result in the change in value reaching 63% of its final value in  
one second. A time constant of 4 is 22%, 10 is 9.5% and 50 is  
1.9% of the final value in one second. The time constant equa-  
tion is shown below (TC = Time Constant).  
4-6  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 4 Troubleshooting & Repair  
% change to final value  
in one second  
= 100 (1 – e(-1/TC)  
)
4. The  
vortex coefficient Ck may be incorrectly set. The Ck is a value  
in the equation used to determine if a frequency represents a  
valid vortex signal given the fluid density and signal amplitude.  
In practice, the Ck value controls the adaptive filter, fi, setting.  
During flow, view the f and fi values in the first column of the  
hidden diagnostics. The fi value should be approximately 10-  
20 % higher than the f value. If you raise the Ck setting in the  
Calibration Menu, then the fi value will increase. The fi is a  
low pass filter, so by increasing it or lowering it, you can alter  
the range of frequencies that the meter will accept. If the vor-  
tex signal is strong, the fi value will increase to a large number  
– this is correct. Note: at high frequencies, the display may not  
be able to display all the digits of the fi value (for example, 114  
may be displayed and the actual value is 1140).  
Symptom: No Output  
1. For remote mounted electronics, carefully check all the wiring  
connections in the remote mount junction box. There are 18  
connections that must be correct, verify each color (black and  
red), shield, and wire number.  
2. Turn on the pressure and temperature display in the Display  
Menu and verify that the pressure and temperature are correct.  
3. Using ESD precautions and hazardous area precautions, re-  
move the electronics enclosure window cover. Disconnect the  
vortex sensor from the analog board (the analog board is the  
first board below the microprocessor (display) board. Measure  
the resistance from each outside pin to the meter ground - each  
should be open. Measure the resistance from the center pin to  
the meter ground – this should be grounded to the meter. With  
the sensor still disconnected, go to the first column of the hid-  
den diagnostics and display the vortex shedding frequency, f.  
Hold a finger on the three exposed pins on the analog board.  
The meter should read electrical noise, 60 Hz for example. If  
all readings are correct, re-install vortex sensor wires.  
4. Verify all meter configuration and troubleshooting steps previ-  
ously described. There are many possible causes of this prob-  
lem, consult factory if necessary.  
IM-24-HP  
4-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Troubleshooting & Repair  
Series 24-HP Instruction Manual  
Symptom: Meter Displays Temperature Fault  
1. For remote mounted electronics, carefully check all the wiring  
connections in the remote mount junction box. There are 18  
connections that must be correct, verify each color (black and  
red), shield, and wire number.  
2. Go to the first column of the hidden diagnostics and check the  
resistance of the rtd1. It should be about 1080 ohms at room  
temperature.  
3. Using ESD precautions and hazardous area precautions, re-  
move the electronics enclosure window cover. Disconnect the  
temperature sensor (on the right) from the pressure / tempera-  
ture board (the pressure / temperature board is the second board  
below the microprocessor (display) board. Measure the resis-  
tance across the outside pins of the temperature sensor connec-  
tor. It should read approximately 1080 ohms at room tempera-  
ture (higher resistance at higher temperatures). With the tem-  
perature sensor still disconnected, measure the current across  
the two outside pins of the exposed connector on the tempera-  
ture / pressure board. The current should be approximately  
.0002 amps. Now reconnect the temperature sensor and meas-  
ure the voltage across the two inside pins (insert probes into the  
connector where the wires enter it). This value should be ap-  
proximately .2 volts (or .0002 amps times measured resistance,  
.216 volts at room temperature).  
4. Consult factory with findings  
Symptom: Meter Displays Pressure Fault  
1. For remote mounted electronics, carefully check all the wiring  
connections in the remote mount junction box. There are 18  
connections that must be correct, verify each color (black and  
red), shield, and wire number.  
2. Using ESD precautions and hazardous area precautions, re-  
move the electronics enclosure window cover. Disconnect the  
pressure sensor (on the left) from the pressure / temperature  
board (the pressure / temperature board is the second board be-  
low the microprocessor (display) board. Measure the resistance  
across the outside pins of the pressure sensor connector, then  
across the inside pins. Both readings should be approximately  
4000 ohms. With the pressure sensor still disconnected, meas-  
ure the current across the two outside pins of the exposed con-  
4-8  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Chapter 4 Troubleshooting & Repair  
nector on the temperature / pressure board. The current should  
be approximately .0004 amps.  
3. Go to the first column of the hidden diagnostics and record the  
Pe(V) and Pv(V) values and consult the factory with findings.  
Electronics Assembly Replacement (All Meters)  
The electronics boards are electrostatically sensitive. Wear a  
grounding wrist strap and make sure to observe proper handling  
precautions required for static-sensitive components.  
1. Turn off power to the unit.  
2. Locate and loosen the small set screw which locks the larger  
enclosure cover in place. Unscrew the cover to expose the elec-  
tronics stack.  
Warning!  
Before attempting  
any flow meter re-  
pair, verify that the  
line is not pressur-  
3. Locate the sensor harnesses which come up from the neck of  
the flow meter and attaches to the circuit boards. Use small pli-  
ers to pull the sensor wiring connectors off of the circuit  
boards.  
4. Locate and loosen the small set screw which locks the smaller  
enclosure cover in place. Unscrew the cover to expose the field  
wiring strip. Tag and remove the field wires.  
5. Remove the screws that hold the black wiring label in place,  
remove the label.  
6. Locate the 4 Phillips head screws which are spaced at 90-  
degrees around the terminal board. These screws hold the elec-  
tronics stack in the enclosure. Loosen these screws (Note: that  
these are captive screws, they will stay inside the enclosure).  
7. Carefully remove the electronics stack from the opposite side  
of the enclosure. If the electronics stack will not come out, gen-  
tly tap the terminal strip with the screw driver handle. This will  
loosen the rubber sealing gasket on the other side of the enclo-  
sure wall. Be careful that the stack does not hang up on the  
loose sensor harnesses.  
8. Repeat steps 1 through 6 in reverse order to install the new  
electronics stack.  
IM-24-HP  
4-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Troubleshooting & Repair  
Pressure Sensor Replacement  
Series 24-HP Instruction Manual  
1. For local mounted electronics, remove the electronics stack as  
previously described. For remote mount electronics, remove  
all wires and sensor connectors from the remote feedthrough  
board in the junction box at the meter.  
2. Loosen the three set screws at the center of the adapter between  
the meter and the enclosure.  
3. Remove the top half of the adapter to expose the pressure trans-  
ducer.  
4. Remove the transducer and replace it with the new one using  
appropriate thread sealant.  
5. Reassemble in reverse order.  
Returning Equipment to the Factory  
Before returning any Innova-Mass flow meter to the factory,  
you must request a Return Material Authorization (RMA)  
number. To obtain an RMA number and the correct shipping ad-  
dress, contact Customer Service at:  
800-866-0200 or 831-373-0200 in the USA,  
When contacting Customer Service, be sure to have the meter se-  
rial number and model code.  
When requesting further troubleshooting guidance, record the fol-  
lowing values first:  
f, fi, G, and A at no flow and during flow if possible.  
Pressure, temperature, and flow rate  
4-10  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix A Specifications  
Appendix A Product Specifications  
Accuracy  
241 Series Insertion Meters(1)  
Process  
Variables  
240 Series In-Line Meters  
Liquids  
Gas & Steam  
Liquids  
Gas &  
Steam  
Mass Flow  
Rate  
1% of rate  
over a 30:1  
range(3)  
1.5% of  
1.5% of rate  
over a 30:1  
range(3)  
2% of  
rate(2) over  
a 30:1  
rate(2) over a  
30:1 range(3)  
range(3)  
Volumetric  
Flow Rate  
0.7% of  
rate over a  
30:1  
1% of rate  
over a 30:1  
range(3)  
1.2% of rate  
over a 30:1  
range(3)  
1.5% of  
rate over a  
30:1  
range(3)  
range(3)  
Temperature  
Pressure  
2°F  
1°C)  
2°F  
1°C)  
2°F  
1°C)  
2°F  
1°C)  
(
(
(
(
0.4% of  
transducer  
full scale  
0.4% of  
transducer  
full scale  
0.4% of  
transducer full  
scale  
0.4% of  
transducer  
full scale  
Density  
0.3% of  
reading  
0.5% of  
0.3% of  
reading  
0.5% of  
reading(2)  
reading(2)  
Notes:  
(1) Accuracies stated are for the total mass flow through the pipe.  
(2) Over 50 to 100% of the pressure transducer’s full scale.  
(3) Nominal rangeability is stated. Precise rangeability depends on fluid and pipe size.  
Repeatability  
Mass Flow Rate: 0.2% of rate.  
Volumetric Flow Rate: 0.1% of rate.  
Temperature:  
0.2°F ( 0.1°C).  
Pressure: 0.05% of full scale.  
Density: 0.1% of reading.  
Stability Over 12 Months  
Mass Flow Rate: 0.2% of rate maximum.  
Volumetric Flow Rate: Negligible error.  
Temperature: 0.1°F ( 0.5°C) maximum.  
Pressure: 0.1% of full scale maximum.  
Density: 0.1% of reading maximum.  
Response Time  
Adjustable from 1 to 100 seconds.  
Material Capability  
Series 240 In-Line Flow Meter:  
Any gas, liquid or steam compatible with 316L stainless steel, C276  
hastelloy or A105 carbon steel. Not recommended for multi-phase  
fluids.  
Series 241 Insertion Flow Meter:  
Any gas, liquid or steam compatible with 316L stainless steel. Not  
recommended for multi-phase fluids.  
Flow Rates  
Typical mass flow ranges are given in the following table. Precise  
flow depends on the fluid and pipe size. 241 insertion meters are  
applicable to pipe sizes from 2 inch and above. Consult factory for  
sizing program.  
Water Minimum and Maximum Flow Rates  
½-inch  
¾-inch  
1-inch  
1.5-inch  
2-inch  
3-inch  
4-inch  
6-inch  
8-inch  
gpm  
1
22  
1.3  
40  
2.2  
67  
5.5  
166  
9.2  
276  
21  
618  
36  
1076  
81  
2437  
142  
4270  
m3/hr  
.23  
5
.3  
9.1  
0.5  
15  
1.3  
38  
2.1  
63  
4.7  
140  
8.1  
244  
18  
554  
32  
970  
IM-24-HP  
A-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A Specifications  
Series 24-HP Instruction Manual  
Typical Air Minimum and Maximum Flow Rates (SCFM)  
Air at 70oF  
Nominal Pipe Size (in)  
Pressure  
0 psig  
0.5  
1.8  
18  
0.75  
3
1
5
1.5  
13  
2
22  
3
50  
4
87  
6
198  
8
347  
41  
9
90  
15  
221  
38  
369  
63  
826  
141  
1437  
245  
3258  
555  
5708  
972  
5
100 psig  
200 psig  
300 psig  
400 psig  
500 psig  
138  
7
325  
13  
704  
21  
1730  
52  
2890  
86  
6466  
193  
11254  
335  
25515  
761  
44698  
1332  
83931  
1615  
258  
8
609  
15  
1322  
25  
3248  
63  
5427  
104  
12140  
234  
21131  
407  
47911  
922  
380  
10  
896  
18  
1944  
29  
4775  
72  
7978  
120  
17847  
269  
31064  
467  
70431 123375  
1060 1857  
93057 163000  
1182 2071  
502  
11  
1183  
20  
2568  
33  
6309  
80  
10542  
134  
23580  
300  
41043  
521  
624  
1472  
3195  
7849  
13115  
28034  
51063 115775 203000  
Typical Air Minimum and Maximum Flow Rates (nm3/hr)  
Air at 20oC  
Nominal Pipe Size (mm)  
Pressure  
0 barg  
15  
3
20  
5
25  
9
40  
21  
50  
36  
80  
79  
100  
138  
150  
313  
200  
549  
28  
7
66  
13  
142  
21  
350  
52  
584  
87  
1307  
194  
2275  
337  
5157  
764  
9034  
1339  
53749  
1814  
98676  
2190  
5 barg  
165  
9
390  
17  
847  
29  
2080  
70  
3476  
117  
7775  
262  
13533  
457  
30682  
1035  
56329  
1250  
10 barg  
15 barg  
20 barg  
30 barg  
304  
11  
442  
13  
582  
16  
862  
716  
21  
1554  
34  
3819  
85  
6381  
142  
14273  
317  
24844  
551  
1044  
24  
2265  
40  
5565  
97  
9299  
162  
20801  
363  
36205  
632  
82087 143801  
1434 2511  
1373  
29  
2979  
48  
7318  
118  
10843  
12229  
198  
18119  
27354  
442  
40529  
47612 107949 189105  
770 1745 3057  
70544 159942 280187  
2034  
4414  
Linear Range  
Smart electronics corrects for lower flow down to a Reynolds number of 5,000. The Reynolds  
number is calculated using the fluid’s actual temperature and pres-  
sure monitored by the meter. Rangeability depends on the fluid,  
process connections and pipe size. Consult factory for your applica-  
tion. Velocity rangeability under ideal conditions is as follows:  
Liquids 30:1  
Gases 30:1  
1 foot per second velocity minimum  
30 feet per second velocity maximum  
10 feet per second velocity minimum  
300 feet per second velocity maximum  
A-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix A Specifications  
Typical Saturated Steam Minimum and Maximum Flow Rates (lb/hr)  
Nominal Pipe Size (in)  
Pressure  
5 psig  
0.5  
6.5  
52  
0.75  
12  
1
20  
1.5  
49  
2
82  
3
183  
4
318  
6
722  
8
1264  
16806  
2893  
87998  
3905  
122  
27  
265  
46  
650  
112  
1087  
187  
2431  
419  
4231  
728  
9594  
1652  
50233  
2229  
15  
100 psig  
200 psig  
300 psig  
400 psig  
500 psig  
271  
20  
639  
37  
1386  
62  
3405  
151  
5690  
253  
12729  
565  
22156  
983  
493  
24  
1163  
45  
2525  
74  
6203  
182  
10365  
304  
23184  
680  
40354  
1184  
91494 160279  
2685 4704  
716  
28  
1688  
51  
3664  
85  
9000  
209  
15040  
349  
33642  
780  
58556 132763 232575  
1358 3079 5393  
76971 174516 305717  
1514 3433 6014  
95710 217001 380148  
941  
31  
2220  
57  
4816  
95  
11831  
233  
19770  
389  
44222  
870  
1170  
2760  
5988  
14711  
24582  
54987  
Typical Saturated Steam Minimum and Maximum Flow Rates (kg/hr)  
Nominal Pipe Size (mm)  
Pressure  
0 barg  
0.5  
3
0.75  
5
1
8
1.5  
19  
2
32  
3
72  
4
126  
6
286  
8
500  
18  
6
42  
11  
91  
18  
224  
45  
375  
75  
838  
167  
1459  
290  
3309  
658  
5797  
1153  
30799  
1537  
54720  
1840  
78444  
2100  
5 barg  
95  
8
224  
15  
485  
24  
1192  
59  
1992  
99  
4455  
222  
7754  
387  
17581  
877  
10 barg  
15 barg  
20 barg  
30 barg  
168  
9
397  
17  
862  
29  
2118  
71  
3539  
119  
5073  
136  
6611  
165  
9729  
7915  
266  
13777  
463  
31237  
1050  
44779  
1199  
241  
11  
314  
13  
463  
569  
20  
1236  
33  
3036  
81  
11347  
304  
19750  
529  
742  
24  
1610  
40  
3956  
99  
14787  
369  
25738  
642  
58355 102226  
1455 2548  
85884 150451  
1092  
2370  
5822  
21763  
37880  
Linear Range  
Smart electronics corrects for lower flow down to a Reynolds number of 5,000. The Reynolds  
number is calculated using the fluid’s actual temperature and pres-  
sure monitored by the meter. Rangeability depends on the fluid,  
process connections and pipe size. Consult factory for your applica-  
tion. Velocity rangeability under ideal conditions is as follows:  
Liquids 30:1  
Gases 30:1  
1 foot per second velocity minimum  
30 feet per second velocity maximum  
10 feet per second velocity minimum  
300 feet per second velocity maximum  
Process Fluid Pressure  
240 Pressure Ratings  
Material  
Process  
Connection  
Rating  
Flanged  
Wafer  
316L SS, A105 Carbon Steel, C276 Hastelloy  
316L SS, A105 Carbon Steel, C276 Hastelloy  
150, 300, 600 lb, PN16,  
PN40, PN64  
600 lb, PN64  
IM-24-HP  
A-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A Specifications  
Series 24-HP Instruction Manual  
241 Pressure Ratings  
Probe Seal  
Compression  
Fitting  
Process  
Connection  
Material  
Rating  
Ordering  
Code  
2-inch MNPT  
316L SS  
316L SS  
ANSI 600 lb  
CNPT  
2-inch 150 lb flange,  
DN50 PN16  
ANSI 150  
lb, PN16  
C150,  
C16  
2-inch 300 lb flange,  
DN50 PN40  
316L SS  
316L SS  
ANSI 300  
lb, PN40  
C300,  
C40  
2-inch 600 lb flange,  
DN50 PN64  
ANSI 600  
lb, PN64  
C600,  
C64  
Packing Gland  
2-inch MNPT  
316L SS  
316L SS  
50 psig  
50 psig  
PNPT  
2-inch 150 lb flange,  
DN50 PN16  
P150,  
P16  
2-inch 300 lb flange,  
DN50 PN40  
316L SS  
50 psig  
P300,  
P40  
Packing Gland with  
Removable Retractor  
2-inch MNPT  
316L SS  
316L SS  
ANSI 300 lb  
ANSI 150 lb  
PM, RR  
2-inch 150 lb flange,  
DN50, PN16  
P150,  
P16,RR  
2-inch 300 lb flange  
316L SS  
ANSI 300 lb  
P300,  
P40, RR  
Packing Gland with  
Permanent Retractor  
2-inch MNPT  
316L SS  
316L SS  
ANSI 600 lb  
ANSI 150 lb  
PNPTR  
2-inch 150 lb flange,  
DN50 PN16  
P150R,  
P16R  
2-inch 300 lb flange,  
DN50, PN40  
316L SS  
316L SS  
ANSI 300 lb  
ANSI 600 lb  
P300R,  
P40R  
2-inch 600 lb flange,  
DN50 PN64  
P600R,  
P64R  
Pressure Transducer Ranges  
Pressure Sensor Ranges(1), psia (bara)  
Full Scale Operating Pres-  
sure  
Maximum Over-Range Pressure  
psia  
30  
(bara)  
2
psia  
60  
(bara)  
4
100  
300  
500  
1500  
7
200  
600  
1000  
2500  
14  
20  
40  
35  
70  
100  
175  
Note: (1) To maximize accuracy, specify the lowest full scale oper-  
ating pressure range for the application. To avoid damage,  
the flow meter must never be subjected to pressure above the  
over-range pressure shown above.  
Power Requirements  
.
12 to 36 VDC, Loop Powered for the Volumetric option only  
12 to 36 VDC, 100 mA for the Multiparameter Mass options  
100 to 240 VAC, 50/60 Hz, 25 watts for the Multiparameter Mass  
optiions  
Display  
Alphanumeric 2 x 16 LCD digital display.  
Six push-button switches (up, down, right, left, enter, exit) operable  
through explosion-proof window using hand-held magnet. Viewing  
at 90-degree mounting intervals.  
A-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix A Specifications  
Pocess Fluid and  
Ambient Temperature  
Process Fluid:  
Standard temperature sensor: –40°F to 500°F (–40°C to 260°C).  
High temperature sensor: to 750°F ( to 400°C).  
Ambient:  
Operating: –5°F to 140°F (–20°C to 60°C).  
Storage: –40°F to 150°F (–40°C to 65°C).  
0-98% relative humidity, non-condensing conditions.  
Output Signals (1)  
Analog: Volumetric Meter: field rangeable linear 4-20 mA output  
signal (1000 Ohms maximum loop resistance) selected by user for  
mass flow rate or volumetric flow rate.  
Communications: HART, MODBUS, RS485  
Multiparameter Meter: up to three field rangeable linear 4-20 mA  
output signals (1000 Ohms maximum loop resistance) selected  
from the five parameters–mass flow rate, volumetric flow rate, tem-  
perature, pressure and density.  
Pulse:Pulse output for totalization is a 50-millisecond duration pulse  
operating a solid-state relay capable of switching 40 VDC, 40 mA  
maximum.  
Note: (1) All outputs are optically isolated and require external power  
for operation.  
Alarms  
Up to three programmable solid-state relays for high, low or window  
alarms capable of switching 40 VDC, 40 mA maximum.  
Totalizer  
Based on user-determined flow units, six significant figures in sci-  
entific notation. Total stored in non-volatile memory.  
Wetted Materials  
Series 240 In-Line Flow Meter:  
316L stainless steel standard.  
C276 hastelloy or A105 carbon steel optional.  
Series 241 Insertion Flow Meter:  
316L stainless steel standard.  
Teflon® packing gland below 500°F (260°C).  
Graphite packing gland above 500°F (260°C).  
Enclosure  
NEMA 4X cast enclosure.  
Electrical Ports  
Mounting Connections  
Two 3/4-inch female NPT ports.  
Series 240: Wafer, 150, 300, 600 lb ANSI flange, PN16, PN40,  
PN64 flange.  
Series 241 Permanent installation: 2-inch MNPT; 150, 300, 600 lb  
ANSI flange, PN16, PN40, PN64 flange with compression fitting  
probe seal.  
Series 241 Hot Tap(1) Installation: 2-inch MNPT; 150, 300, 600 lb  
ANSI flange, PN16, PN40, PN64 flange and optional retractor with  
packing gland probe seal.  
Note: (1) Removable under line pressure.  
Mounting Position  
Certifications  
Series 240 In-Line Flow Meter: No effect.  
Series 241 Insertion Flow Meter: Meter must be perpendicular  
within 5°of the pipe centerline.  
Construction Inspection ( ANSI/ASME B31.3).  
Materials (NACE MR-01-75[90]).  
CE and FM approved.  
CSA, CENELEC approval pending.  
FM approvals:  
Class I, Division 1, Groups B, C, & D, T6 at Tamb = 60°C  
Class II/III, Division 1, Groups E, F, & G  
IP66, NEMA 4X  
IM-24-HP  
A-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix B Glossary  
Appendix B Glossary  
A B C D  
A
Cross sectional area.  
ACFM  
Actual Cubic Feet Per Minute (volumetric flow rate).  
American Society of Mechanical Engineers.  
ASME  
Bluff Body  
A non-streamlined body placed into a flow stream to  
create vortices. Also called a Shedder Bar.  
BTU  
British Thermal Unit, an energy measurement.  
European Electrical Code.  
Cenelec  
Compressibility  
Factor  
A factor used to correct for the non-ideal changes in  
a fluid’s density due to changes in temperature  
and/or pressure.  
CSA  
d
Canadian Standards Association.  
Width of a bluff body or shedder bar.  
Diameter of a flow channel.  
D
E F G H  
f
Frequency of vortices generated in a vortex flow  
meter, usually in Hz.  
Flow Channel  
Flow Profile  
A pipe, duct, stack, or channel containing flowing fluid.  
A map of the fluid velocity vector (usually non-  
uniform) in a cross-sectional plane of a flow channel  
(usually along a diameter).  
FM  
Factory Mutual.  
Ft  
Foot, 12 inches, a measure of length.  
Square feet, measure of area.  
Cubic feet, measure of volume.  
Gallons Per Minute.  
Ft^2  
Ft^3  
GPM  
Hz  
Hertz, cycles per second.  
IM-24-HP  
B-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B Glossary  
Series 24-HP Instruction Manual  
I J K L  
In-Line Flow Meter  
A flow meter which includes a short section of piping  
which is put in-line with the user’s piping.  
Insertion Flow Meter  
A flow meter which is inserted into a hole in the  
user’s pipeline.  
Joule  
LCD  
A unit of energy equal to one watt for one second.  
Also equal to a Newton-meter.  
Liquid crystal display.  
M N O P  
m
Mass flow rate.  
mA  
Milli-amp, one thousandth of an ampere of current.  
µ
Viscosity, a measure of a fluid’s resistance to shear stress.  
Honey has high viscosity, alcohol has low viscosity.  
P  
P
Permanent pressure loss.  
Line pressure (psia or bar absolute).  
ρ act  
The density of a fluid at the actual temperature and  
pressure operating conditions.  
ρ std  
The density of a fluid at standard conditions (usually  
14.7 psia and 20°C).  
Permanent  
Pressure Loss  
Unrecoverable drop in pressure.  
Piezoelectric Crystal  
A material which generates an electrical charge  
when the material is put under stress.  
PRTD  
psia  
An resistance temperature detector (RTD) with plati-  
num as its element. Used because of high stability.  
Pounds per square inch absolute  
(equals psig + atmospheric pressure). Atmospheric  
pressure is typically 14.696 psi at sea level.  
psig  
Pounds per square inch gauge.  
P
V
Liquid vapor pressure at flowing conditions (psia or  
bar absolute).  
B-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix B Glossary  
Q R S T  
Q
Flow rate, usually volumetric.  
Rangeability  
Highest measurable flow rate divided by the lowest  
measurable flow rate.  
Reynolds Number  
or Re  
A dimensionless number equal to the density of a fluid  
times the velocity of the fluid times the diameter of the  
fluid channel, divided by the fluid viscosity (i.e., Re =  
ρVD/µ). The Reynolds number is an important number  
for vortex flow meters because it is used to determine  
the minimum measurable flow rate. It is the ratio of the  
inertial forces to the viscous forces in a flowing fluid.  
RTD  
Resistance temperature detector, a sensor whose  
resistance increases as the temperature rises.  
scfm  
Standard cubic feet per minute (flow rate converted  
to standard conditions, usually 14.7 psia and 20°C).  
Shedder Bar  
A non-streamlined body placed into a flow stream to  
create vortices. Also called a Bluff Body.  
Strouhal Number  
or St  
A dimensionless number equal to the frequency  
of vortices created by a bluff body times the width of  
the bluff body divided by the velocity of the flowing  
fluid (i.e., St = fd/V). This is an important number for  
vortex flow meters because it relates the vortex fre-  
quency to the fluid velocity.  
Totalizer  
Traverse  
An electronic counter which records the total accu-  
mulated flow over a certain range of time.  
The act of moving a measuring point across the  
width of a flow channel.  
U V W X Y Z  
Uncertainty  
The closeness of agreement between the result of a  
measurement and the true value of the measurement.  
V
Velocity or voltage.  
Volts, alternating current.  
Volts, direct current.  
An eddy of fluid.  
VAC  
VDC  
VORTEX  
IM-24-HP  
B-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix C Fluid Calculations  
Appendix C Fluid Calculations  
Calculations for Steam T & P  
When “Steam T & P” is selected in the “Real Gas” selection of the Fluid  
Menu, the calculations are based on the equations below.  
Density  
The density of steam is calculated from the formula given by Keenan  
and Keys. The given equation is for the volume of the steam.  
4.555.04T  
v =  
+ B  
p
2
4
B = B0 + B0 g1(τ)τ p + B0 g2 (τ)τ 3 p3 B013 g3 (τ )τ12 p12  
2
B0 =1.89 2641.62τ 1080870τ  
g1(τ) = 82.546τ 1.6246105 τ 2  
g2 (τ) = 0.218281.2697105 τ 2  
g3 (τ ) = 3.635104 6.7681064 τ 24  
Where tau is 1/ temperature in Kelvin.  
The density can be found from 1/(v/ standard density of water).  
Viscosity  
The viscosity is based on an equation given by Keenan and Keys.  
1.501105  
T
η(poise) =  
1+ 446.8/
T  
Where T is the temperature in Kelvin  
IM-24-HP  
C-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C Fluid Calculations  
Series 24-HP Instruction Manual  
Calculations for Gas (“Real Gas” and “Other Gas”)  
Use this formula to determine the settings for “Real Gas; Gas” selections  
and “Other Gas” selections entered in the Fluid Menu. The calculations  
for gas were taken from Richard W. Miller, Flow Measurement Engi-  
neering Handbook (Second Edition, 1989).  
Density  
The density for real gases is calculated from the equation:  
GMw,Air pf  
ρ =  
Z f R0Tf  
Where G is the specific gravity, M is the molecular weight of air,  
w
p is the flowing pressure, Z is flowing compressibility, Ro is the  
f
universal gas constant, and T is the flowing temperature.  
The specific gravity, and Ro are known and are stored in a table used by  
the Vortex meter.  
The hard coefficient to find is the compressibility, Z. Z is found using  
the Redlich-Kwong Equation (Miller page 2-18).  
The Redlich-Kwong Equation uses the reduced temperature and pressure  
to calculate the compressibility factor. The equations are non linear and  
an iterative solution is used. The Vortex program uses Newton’s Method  
on the Redlich-Kwong equations to iteratively find the compressibility  
factor. The critical temperature and pressure used in the Redlich-Kwong  
equation are stored in the fluid data table with the other coefficients.  
Viscosity  
The viscosity for real gases is calculated using the exponential equation  
for two known viscosities. The equation is:  
µcP = aTKn  
Where a and n are found from two known viscosities at  
two temperatures.  
ln[(µcP )2 /(µcP )1]  
n =  
ln(TK 2 /TK1)  
and  
(µcP )1  
a =  
TKn1  
C-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix C Fluid Calculations  
Calculations for Liquid  
Use this formula to determine the settings for “Goyal-Dorais” selections  
and “Other Liquid” selections entered in the Fluid Menu. The liquid cal-  
culations were taken from Richard W. Miller, Flow Measurement Engi-  
neering Handbook (Second Edition, 1989).  
Density  
The liquid density is found using the Goyal-Doraiswamy Equation.  
Goyal-Doraiswamy uses the critical compressibility, critical pressure  
and critical temperature, along with the molecular weight to find the  
density. The equation for specific gravity is:  
Tf  
pc Mw  
Tc  
0.008  
0.773  
Zc  
GF =  
0.01102  
TC  
The specific gravity can then be converted into density.  
Viscosity  
The liquid viscosity is found by Andrade's equation. This uses two vis-  
cosities at different temperatures to extrapolate the viscosity.  
Andrade's equation:  
BL  
µ = AL exp  
TdegR  
To find A and B  
Tdeg R1Tdeg R2 ln(µ1 / µ2 )  
BL =  
Tdeg R2 Tdeg R1  
µ1  
exp(BL /TdegR1  
AL =  
)
The temperatures are all in degrees Rankin. Do not believe the subscript  
R means they are reduced temperatures.  
IM-24-HP  
C-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series24-HP Instruction Manual  
Appendix D HART Commands  
Appendix D HART Commands with DD Menu  
Online Menu  
K factor, Ck  
Lo Flo Cutoff  
RTD1 Slope  
RTD1 Intercept  
RTD1 Ro  
1 Device Setup  
1 Display Unit  
1 Mass Flo Unit  
2 Vol Unit  
1 PV is  
2 PV AO  
3 Temp Unit  
3 PV  
4 Line Press Unit  
5 Dens Unit  
6 Totalizer Units  
7 Std & Norm Cond  
4 PV % rnge  
5 Apply Values  
6 PV Rnge Unit  
7 PV LRV  
RTD1 alpha  
RTD1 beta  
RTD2 Slope  
RTD2 Intercept  
RTD2 Ro  
1 Norm Temp  
2 Norm Press  
3 Std Temp  
4 Std Press  
8 PV URV  
9 PV AO1 Lo End Pt  
PV AO1 Hi End Pt  
PV AO1 Added Damp  
RTD2 alpha  
RTD2 beta  
Excite Slope  
Excite Intercept  
Snsr Slopt  
Snsr Intercept  
Pcal B00, Pcal B01  
Pcal B02, Pcal B10  
Pcal B11, Pcal B12  
Pcal B20, Pcal B21  
Pcal B22  
1 Fix Analog Output  
2 Trim Analog Output  
3 Configure AO1  
4 PV is  
1 SV is  
2 SV AO  
3 SV  
4 SV % rnge  
5 Apply Values  
6 SV Rnge Unit  
7 SV LRV  
5 PV AO  
6 PV % rnge  
7 Configure AO2  
8 SV is  
9 SV AO  
SV % rnge  
Configure AO3  
TV is  
TV AO  
2 Analog Output  
Board Current  
Cal Current  
8 SV URV  
9 SV AO2 Lo End Pt  
SV AO2 Hi End Pt  
SV AO2 Added Damp  
1 USL  
2 LSL  
3 Min Span  
4 Damp  
1 Alrm 1 var  
2 Alrm 1 typ  
3 Alrm 1 set pt  
TV % rnge  
1 TV is  
2 TV AO  
1 Vtx Freq  
2 Sim Vtx Freq  
3 Vtx AtoD  
4 Filter Set  
5 Gain Set  
6 Re  
5 Snsr s/n  
6 Sim Vtx  
7 Max Vel  
8 Vortex Diag  
3 TV  
1 Disp Cycle  
2 Disp Digits  
3 Disp Damping  
4 Disp Show/Hide  
4 TV % rnge  
5 Apply Values  
6 TV Rnge Unit  
7 TV LRV  
3 Meter Display  
4 Alarm Setup  
5 Totalizer  
1 Alrm 2 var  
2 Alrm 2 typ  
3 Alrm 2 set pt  
8 TV URV  
7 Vel  
8 Max Vel  
1 K Factor  
2 Ck Value  
3 Lo Flo Cutoff  
9 TV AO3 Lo End Pt  
TV AO3 Hi End Pt  
TV AO3 Added Damp  
1 Alarm Status  
1 Alrm 3 var  
2 Alrm 3 typ  
3 Alrm 3 set pt  
2 Alarm 1 Setup  
3 Alarm 2 Setup  
4 Alarm 3 Setup  
5 Records in Log  
6 Read Alarm Log  
7 Alarm Log Clear  
1 Pres snsr unit  
2 USL  
3 LSL  
4 Min Span  
5 Damp  
6 Snsr s/n  
7 Simulate  
8 Maximum  
9 Press Diag  
Steam, Air, Argon, Ammonia, CO,  
CO2, Helium, Hydrogen, Methane,  
Nitrogen, Oxygen  
1 Press  
2 Sim Press  
3 Excite  
4 Excite AtoD  
5 Sense  
1 Total  
2 Totalize  
3 Amount/Pulse  
4 Clear Totalizer  
Specific Gravity, Compress, Viscosity  
Water, Ammonia, Chlorine  
6 Sense AtoD  
7 Max Press  
1 Exicte Slope  
2 Excite Intercept  
3 Snsr Slope  
4 Snsr Intercept  
5 Pcal B00  
6 Pcal B01  
7 Pcal B02  
8 Pcal B10  
9 Pcal B11  
Pcal B12  
Mol Wt, Crit Press, Crit Temp, Comp  
1 Fluid  
1 Calibration Review  
2 Vortex Sensor  
3 Vortex Cal  
4 Press Sensor  
5 Press Cal  
Real Gas  
Other Gas  
Liquid  
Goyal-Dorais  
API 2540  
Nat Gas  
Degrees API, API K0, API K1,  
Viscosity Ceof A1, Viscosity Coef B1  
6 Fluid Menu  
6 Temp Sensor  
7 Temp Cal  
AGA Ref Temp, AGA Ref Press,  
Relative Density, Mole Fract N2,  
Mole Fract CO2  
Pcal B20  
Pcal B21  
1 Date  
2 h  
3 min  
4 s  
Pcal B22  
Board Current  
Cal Current  
1 Vtx Freq  
2 Sim Vtx Freq  
3 Vtx AtoD  
4 Filter Set  
5 Gain Set  
6 Re  
5 Password  
6 Line Size  
7 Dev ID  
8 Tag  
9 Descriptor  
Message  
Final assy num  
Poll adr  
7 Device Menu  
1 Temp Unit  
2 USL  
3 LSL  
4 Min Span  
5 Damp  
6 Snsr s/n  
7 Simulate  
8 Maximum  
9 Temp Diag  
7 Vel  
8 Max Vel  
1 Press  
2 Sim Press  
3 Excite  
4 Excite AtoD  
5 Sense  
Num req preams  
Master reset  
1 Temp  
2 Sim Temp  
3 RTD1  
4 RTD1 AtoD  
5 Max Temp  
8 Diagnostics  
9 Sensor Cal  
Review  
6 Sense AtoD  
7 Max Press  
1 Vortex Diag  
2 Press Diag  
3 Temp Diag  
4 Vel  
5 Temp  
6 Press  
7 Records in Log  
8 Read System Log  
9 System Log Clear  
2 Process Variables  
3 PV is  
4 PV  
1 RTD1 Slope  
2 RTD1 Intercept  
3 RTD1 Ro  
4 RTD1 alpha  
5 RTD1 beta  
6 RTD2 Slope  
7 RTD2 Intercept  
8 RTD2 Ro  
1 Mass Flo  
2 Vol  
3 Temp  
4 Press  
5 Dens  
6 Totl  
1 Temp  
2 Sim Temp  
3 RTD1  
4 RTD1 AtoD  
5 Max Temp  
5 AO1 Out  
6 PV % rnge  
7 Alrm Status  
8 Diagnostics  
9 Calibration Review  
9 RTD2 alpha  
RTD2 beta  
IM-24X  
D-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix D HART Commands  
Series24-HP Instruction Manual  
Appendix D HART Commands without DD Menu  
Online Menu  
1 Device Setup  
2 PV  
3 PV AO  
1 Process Variables  
1 Snsr  
2 AI % Rnge  
3 AO1  
1 4 mA  
2 20 mA  
3 Other  
4 End  
1 4 mA  
2 20 mA  
3 Exit  
1 Test Device  
2 Loop Test  
3 Calibration  
4 D/A Trim  
2 Diag/Service  
1 Apply Values  
2 Enter Values  
1 PV LRV  
2 PV URV  
3 PV USL  
4 PV LSL  
1 Tag  
2 PV unit  
3 Range Values  
4 Device Information  
5 PV Xfer fnctn  
6 PV Damp  
1 PV LRV  
2 PV URV  
3 PV LSL  
4 PV USL  
3 Basic Setup  
1 Distributor  
2 Model  
3 Dev id  
4 Tag  
5 Date  
6 Write Protect  
7 Descriptor  
8 Message  
9 PV snsr s/n  
Final assy #  
Revision #'s  
1 Universal Rev  
2 Fld dev Rev  
3 Software Rev  
1 PV  
1 Sensors  
PV LSL, PV USL, PV Min span  
2 PV Sensor Unit  
3 Sensor information  
1 Snsr Damp  
2 URV  
3 AI LRV  
4 Xfer Fnctn  
5 AI % rnge  
1 PV LRV  
2 PV URV  
2 Signal Condition  
3 Output Condition  
1 AO1  
2 AO alarm typ  
3 Loop test  
1 4 mA  
4 Detailed Setup  
5 Review  
2 20 mA  
3 Other  
4 End  
1 Analog Output  
2 HART Output  
4 D/A trim  
5 Scaled D/A trim  
4 PV LRV  
5 URV  
1 PV LRV  
2 PV URV  
1 Distributor  
2 Model  
1 Poll addr  
3 Dev id  
4 Tag  
5 Date  
2 Num req. preams  
3 Burst mode  
4 Burst option  
4 Device Information  
6 Write Protect  
7 Descriptor  
8 Message  
9 PV snsr s/n  
Final assy #  
Revision #'s  
1 Universal Rev  
2 Fld dev Rev  
3 Software Rev  
D-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E MODBUS Commands  
Series 24-HP Instruction Manual  
Appendix E Modbus Communication  
Applicable Flow Meter Models  
Sierra Innova-Mass® Mass Flow Meters, Models 240 and 241 with Modbus communication pro-  
tocol and firmware version 3.00.02 and above.  
Overview  
This document describes the preliminary implementation of the Modbus communication protocol  
for use in monitoring common process variables in the Sierra Innova-Mass® Vortex flow meter.  
The physical layer utilizes the half-duplex RS-485 port, and the Modbus protocol.  
Reference Documents  
The following documents are available online from www.modbus.org.  
Modbus Application Protocol Specification V1.1  
Modbus Over Serial Line Specification & Implementation Guide V1.0  
Modicon Modbus Protocol Reference Guide PI–MBUS–300 Rev. J  
Menu Items  
The following menu items are in the Output Menu and allow selection and control of the  
Modbus communication protocol.  
Address  
When the Modbus protocol is selected, the Modbus address is equal to the user program-  
mable device address if it is in the range 1…247, in accordance with the Modbus specifica-  
tion. If the device address is zero or is greater than 247, then the Modbus address is inter-  
nally set to 1.  
Comm Protocol  
The Comm Protocol menu allows selection of “Modbus RTU Even,” “Modbus RTU Odd,” or “Mod-  
bus RTU None2,” or “Modbus RTU None1,” (non-standard Modbus) with Even, Odd and None re-  
ferring to the parity selection. When even or odd parity is selected, the unit is configured for 8 data  
bits, 1 parity bit and 1 stop bit; with no parity, the number of stop bits is 1 (non-standard) or 2.  
When changing the protocol, the change is made as soon as the Enter key is pressed.  
IM-24-HP  
E-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E MODBUS Commands  
Series 24-HP Instruction Manual  
Modbus Units  
The Modbus Units menu is to control what units, where applicable,  
the meter’s variables will be displayed in. Internal – these are the  
base units of the meter, °F , psia, lbm/sec , ft3/sec, Btu/sec , lbm/ft3  
Display – variables are displayed in user selected display unit.  
Modbus Order  
The byte order within registers and the order in which multiple registers contain-  
ing floating point or long integer data are transmitted may be changed with this  
menu item. According to the Modbus specification, the most significant byte of a  
register is transmitted first, followed by the least significant byte. The Modbus  
specification does not prescribe the order in which registers are transmitted  
when multiple registers represent values longer than 16 bits. Using this menu  
item, the order in which registers representing floating point or long integer data  
and/or the byte order within the registers may be reversed for compatibility with  
some PLCs and PC software.  
The following four selections are available in this menu; when selecting an  
item, the protocol is changed immediately without having to press the Enter  
key.  
0-1:2-3  
2-3:0-1  
1-0:3-2  
3-2:1-0  
Most significant register first, most significant byte first (default)  
Least significant register first, most significant byte first  
Most significant register first, least significant byte first  
Least significant register first, least significant byte first  
Note that all of the registers are affected by the byte order, includ-  
ing strings and registers representing 16-bit integers; the register  
order only affects the order of those registers representing 32-bit  
floating point and long integer data, but does not affect single 16-  
bit integers or strings.  
Modbus Protocol  
The Modbus RTU protocol is supported in this implementation. Supported baud  
rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200. The default  
baud rate is 19200 baud. Depending upon the Modbus protocol selected, data  
are transmitted in 8-bit data frames with even or odd parity and 1 stop bit, or no  
parity and 2 or 1 (non-standard) stop bits.  
The current Modbus protocol specification does not define register usage, but  
E-2  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix E MODBUS Commands  
there is an informal register numbering convention derived from the original (now  
obsolete) Modicon Modbus protocol specification, and used by many vendors of  
Modbus capable products.  
Registers  
Usage  
Valid Function Codes  
00001–09999 Read/write bits ("coils")  
01 (read coils) 05 (write single coil)  
15 (write multiple coils)  
10001–19999 Read-only bits ("discrete inputs")  
02 (read discrete inputs)  
30001–39999 Read-only 16 bit registers ("input regis-  
ters"), IEEE 754 floating point register  
03 (read holding registers) 04 (read  
input registers)  
pairs, arbitrary length strings encoded as  
two ASCII characters per 16-bit register  
40001–49999 Read/write 16-bit registers ("holding regis- 03 (read holding registers) 06 (write  
ters"), IEEE 754 floating point register  
pairs, arbitrary length strings encoded as  
two ASCII characters per 16-bit register  
single register) 16 (write multiple  
registers)  
Each range of register numbers maps to a unique range of ad-  
dresses that are determined by the function code and the register  
number. The address is equal to the least significant four digits of  
the register number minus one, as shown in the following table.  
Registers  
Function Codes  
01, 05, 15  
02  
Data Type and Address Range  
Read/write bits 0000-9998  
00001-09999  
10001-19999  
30001-39999  
40001-49999  
Read-only bits 0000-9999  
03, 04  
Read-only 16-bit registers 0000-9998  
Read/write 16-bit registers 0000-9998  
03, 06, 16  
Register Definitions  
The meter serial number and those variables that are commonly  
monitored (mass, volume and energy flow rates, total, pressure,  
temperature, density, viscosity, Reynolds number, and diagnostic  
variables such as frequency, velocity, gain, amplitude and filter set-  
ting) are accessible via the Modbus protocol. Long integer and  
floating point numbers are accessed as pairs of 16-bit registers in  
the register order selected in the Modbus Order menu. Floating  
point numbers are formatted as single precision IEEE 754 floating  
point values.  
The flow rate, temperature, pressure, and density variables may  
be accessed as either the flow meter internal base units or in the  
user-programmed display units, which is determined by the pro-  
IM-24-HP  
E-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E MODBUS Commands  
Series 24-HP Instruction Manual  
gramming Output Menu’s “Modbus Units” item. The display units  
strings may be examined by accessing their associated registers.  
Each of these units string registers contain 2 characters of the  
string, and the strings may be 2 to 12 characters in length with  
unused characters set to zero. Note that the byte order affects the  
order in which the strings are transmitted. If the Modbus Order  
menu (see page 2) is set to 0-1:2-3 or 2-3:0-1, then the charac-  
ters are transmitted in the correct order; if set to 1-0:3-2 or 3-2:1-  
0, then each pair of characters will be transmitted in reverse or-  
der.  
Registers  
Variable  
Data type  
Units  
Function  
code  
Addresses  
65100-65101  
30525-30526  
32037-32042  
30009-30010  
30007-30008  
30005-30006  
30001-30002  
30029-30030  
30015-30016  
30013-30014  
30031-30032  
30025-30026  
34532  
Serial number  
Totalizer  
unsigned long  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
03, 04  
unsigned long display units*  
524-525  
2036-2041  
8-9  
Totalizer units  
Mass flow  
string  
float  
float  
float  
float  
float  
float  
float  
float  
float  
char  
float  
float  
display units*  
Volume flow  
Pressure  
display units*  
6-7  
display units*  
4-5  
Temperature  
Velocity  
display units*  
0-1  
ft/sec  
28-29  
14-15  
12-13  
30-31  
24-25  
4531  
Density  
display units*  
Viscosity  
cP  
Reynolds number  
Vortex frequency  
Gain  
Hz  
30085-30086  
30027-30028  
Vortex amplitude  
Filter setting  
Vrms  
Hz  
84-85  
26-27  
The following registers are available with the energy meter firm-  
ware:  
Registers  
Variable  
Data type  
Units  
Function  
code  
Addresses  
30527-30528  
32043-32048  
30003-30004  
30011-30012  
Totalizer #2  
unsigned long display units*  
03, 04  
03, 04  
03, 04  
03, 04  
526-527  
2042-2047  
2-3  
Totalizer #2 units  
Temperature #2  
Energy flow  
string  
float  
float  
display units*  
display units*  
10-11  
E-4  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix E MODBUS Commands  
The following registers contain the display units strings:  
Registers  
32007-32012  
32001-32006  
32025-32030  
32019-32024  
32031-32036  
32013-32017  
Variable  
Data type  
string  
Units  
Function code  
03, 04  
Addresses  
2006-2011  
2000-2005  
2024-2029  
2018-2023  
2030-2035  
2012-2017  
Volume flow units  
Mass flow units  
Temperature units  
Pressure units  
Density units  
string  
03, 04  
string  
03, 04  
string  
03, 04  
string  
03, 04  
Energy flow units  
string  
03, 04  
Function codes 03 (read holding registers) and 04 (read input regis-  
ters) are the only codes supported for reading these registers, and  
function codes for writing holding registers are not implemented.  
We recommend that the floating point and long integer registers be  
read in a single operation with the number of registers being a mul-  
tiple of two. If these data are read in two separate operations, each  
reading a single 16-bit register, then the value will likely be invalid.  
The floating point registers with values in display units are scaled  
to the same units as are displayed, but are instantaneous values  
that are not smoothed. If display smoothing is enabled (non-zero  
value entered in the Display TC item in the Display Menu), then  
the register values will not agree exactly with the displayed val-  
ues.  
Exception Status Definitions  
The Read Exception Status command (function code 07) returns the exception  
status byte, which is defined as follows. This byte may be cleared by setting “coil”  
register #00003 (function code 5, address 2, data = 0xff00).  
Bit(s)  
0-1  
Definition  
Byte order (see Modbus Order on page 2)  
0 = 3-2:1-0 1 = 2-3:0-1  
2 = 1-0:3-2 3 = 0-1:2-3  
Temperature sensor fault  
Pressure sensor fault  
A/D converter fault  
2
3
4
5
6
7
Period overflow  
Pulse overflow  
Configuration changed  
IM-24-HP  
E-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E MODBUS Commands  
Series 24-HP Instruction Manual  
Discrete Input Definitions  
The status of the three alarms may be monitored via the Modbus Read Discrete  
Input command (function code 02). The value returned indicates the state of the  
alarm, and will be 1 only if the alarm is enabled and active. A zero value is trans-  
mitted for alarms that are either disabled or inactive,  
Registers  
10001  
Variable  
Alarm #1 state  
Alarm #2 state  
Alarm #3 state  
Function Code  
Address  
02  
02  
02  
0
1
2
10002  
10003  
Control Register Definitions  
The only writeable registers in this implementation are the Reset  
Exception Status, Reset Meter and Reset Totalizer functions, which  
are implemented as ”coils” which may be written with the Write  
Single Coil command (function code 05) to address 8 through 10,  
respectively, (register #00009 through #00011). The value sent with  
this command must be either 0x0000 or 0xff00, or the meter will re-  
spond with an error message; the totalizer will be reset or exception  
status cleared only with a value of 0xff00.  
Error Responses  
If an error is detected in the message received by the unit, the function code  
in the response is the received function code with the most significant bit set,  
Exception  
Code  
01  
Description  
Invalid function code — function code not supported by device  
02  
Invalid data address — address defined by the start address and number of registers  
is out of range  
03  
Invalid data value — number of registers = 0 or >125 or incorrect data with the Write  
Single Coil command  
and the data field will contain the exception code byte, as follows:  
If the first byte of a message is not equal to the unit’s Modbus ad-  
dress, if the unit detects a parity error in any character in the re-  
ceived message (with even or odd parity enabled), or if the mes-  
sage CRC is incorrect, the unit will not respond.  
E-6  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix E MODBUS Commands  
Command Message Format  
The start address is equal to the desired first register number minus one. The  
addresses derived from the start address and the number of registers must all be  
mapped to valid defined registers, or an invalid data address exception will occur.  
Normal Response Message Format  
Exception Response Message Format  
Examples  
Read the exception status byte from the device with address 1:  
01 07 41 E2  
01 Device address  
07 Function code, 04 = read exception status  
A typical response from the device is as follows:  
01 07 03 62 31  
01 Device address  
07 Function code  
03 Exception status byte  
62 31 CRC  
Request the first 12 registers from device with address 1:  
01 04 00 00 00 0C F0 0F  
01 Device address  
04 Function code, 04 = read input register  
00 00 Starting address  
00 0C Number of registers = 12  
F0 0F CRC  
IM-24-HP  
E-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E MODBUS Commands  
Series 24-HP Instruction Manual  
A typical response from the device is as follows: *note these are the older register  
definitions  
01 04 18 00 00 03 E8 00 00 7A 02 6C 62 00 00 41 BA 87 F2 3E BF FC 6F 42  
12 EC 8B 4D D1  
01 Device address  
04 Function code  
18 Number of data bytes = 24  
00 00 03 E8 Serial number = 1000 (unsigned long)  
00 00 7A 02 Totalizer = 31234 lbm (unsigned long)  
6C 62 00 00 Totalizer units = “lb” (string, unused characters are 0)  
41 BA 87 F2 Mass flow rate = 23.3164 lbm/sec (float)  
3E BF FC 6F Volume flow rate = 0.3750 ft3/sec (float)  
42 12 EC 8B Pressure = 36.731 psia (float)  
4D D1 CRC  
An attempt to read register(s) that don’t exist  
01 04 00 00 00 50 F1 D2  
01 Device address  
04 Function code 4 = read input register  
00 00 Starting address  
00 50 Number of registers = 80  
F0 36 CRC  
results in an error response as follows:  
01 84 02 C2 C1  
01 Device address  
84 Function code with most significant bit set indicates error  
response  
02 Exception code 2 = invalid data address  
C2 C1 CRC  
Request the state all three alarms:  
01 02 00 00 00 03 38 0B  
01 Device address  
02 Function code 2 = read discrete inputs  
00 00 Starting address  
00 03 Number of inputs = 3  
38 0B CRC  
and the unit responds with:  
01 02 01 02 20 49  
01 Device address  
02 Function code  
01 Number of data bytes = 1  
02 Alarm #2 on, alarms #1 and #3 off  
20 49 CRC  
To reset the totalizer:  
01 05 00 00 FF 00 8C 3A  
E-8  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series 24-HP Instruction Manual  
Appendix E MODBUS Commands  
01 Device address  
05 Function code 5 = write single coil  
00 09 Coil address = 9  
FF 00 Data to reset totalizer  
8C 3A CRC (not the correct CRC EJS-02-06-07)  
The unit responds with an identical message to that transmitted, and the totalizer  
is reset. If the “coil” is turned off as in the following message, the response is also  
identical to the transmitted message, but the totalizer is not affected.  
01 05 00 00 00 00 CD CA  
01 Device address  
05 Function code 5 = write single coil  
00 00 Coil address = 0  
00 00 Data to “turn off coil” does not reset totalizer  
CD CA CRC  
IM-24-HP  
E-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E MODBUS Commands  
Series 24-HP Instruction Manual  
E-10  
IM-24-HP  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Computer Monitor LL S201A User Manual
Sharp Model Vehicle LC 50LE440M User Manual
Soleus Air Fan FCM 30 User Manual
Sony Camcorder NEXVG10 User Manual
Sony Camera Lens VCL ES06A User Manual
Sony Car Speaker BKAM 101 User Manual
Sony Stereo System 3 097 194 151 User Manual
Sprint Nextel Network Card EP68 00356A User Manual
Stearns Recreational Life Jacket 0340 User Manual
Subaru Automobile Parts EA190V User Manual