SPX Cooling Technologies Humidifier SS NC 08A User Manual

Marley NC Class Stainless Crossflow CoolingTower  
/
/
Product Specifications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower  
/
/
3
NC Class Stainless Steel towers are factory  
Pages 4 thru 10 indicate those paragraphs which will  
result in the purchase of a basic cooling tower—one  
that accomplishes the specified thermal performance,  
but which will lack many operation—and maintenance-  
enhancing accessories and features that are usually  
desired by those persons who are responsible for the  
continued and continuing operation of the system of  
which the tower is part. It will also incorporate those  
standard materials which testing and experience has  
proven to provide acceptable longevity in normal  
operating conditions.  
assembled, crossflow cooling towers, designed to  
serve air conditioning and refrigeration systems as well  
as light to medium industrial process loads on clean  
water. They evolve from a factory-assembled concept  
of towers pioneered by Marley some 50 years ago, and  
incorporate all of the design advancements that our  
customers have found valuable. The NC Class has been  
designed specifically for sound control and tonnage  
density and represents the current state of the art in  
this cooling tower category.  
This booklet not only relates the language to use in  
describing an appropriate NC Class cooling tower—  
but also defines why certain items and features are  
important enough to specify with the intention of  
insisting upon compliance by all bidders. The left-hand  
column of pages 4 thru 22 provides appropriate text for  
the various specification paragraphs, whereas the right  
hand column comments on the meaning of the subject  
matter and explains its value.  
Pages 11 thru 22 provide paragraphs intended to add  
those features, components and materials that will  
customize the tower to meet the user's requirements.  
Space does not permit definition and explanation of all  
of the possible options that can be applied to the  
NC Class. We realize that you, the purchaser, must  
be happy with the tower's characteristics, and we are  
prepared to provide—or provide for—any reasonable  
enhancement that you are willing to define and  
purchase. Your needs will become part of the  
continuing evolution of this Marley product line.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
4
Specifications  
Specification Value  
1.0  
1.1  
Base:  
Your specification base establishes the type, configuration, base materi-  
al and physical limitations of the cooling tower to be quoted. During the  
planning and layout stages of your project, you will have focused your  
attention on a cooling tower selection that fits your space allotment,  
and whose power usage is acceptable. Limitations on physical size and  
total operating horsepower avoid the introduction of unforeseen opera-  
tional and site-related influences. Specifying the number of cells, and  
the maximum fan kW/cell will work to your advantage.  
Provide an induced draft, crossflow  
type, factory assembled, film fill,  
industrial duty, stainless steel cooling  
tower situated as shown on the plans.  
The limiting overall dimensions of  
the tower shall be _____ wide, _____  
long, and _____ high. Total operating  
kilowatt of all fans shall not exceed  
____ kW, consisting of ___ @ _____  
kW motor(s). Tower shall be similar and  
equal in all respects to Marley Model  
____________.  
The benefit of crossflow towers is that they are inherently easy to oper-  
ate, access and maintain. Compared to counterflow towers, crossflow  
towers have a spacious plenum between banks of fill for easy access to  
all of the towers internal components, plus the water distribution sys-  
tem is adjacent to the fan deck and can be maintained during operation.  
The NC is also available unassembled for on-site assembly.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
5
Specifications  
Specification Value  
2.0  
2.1  
Thermal Performance and Efficiency:  
CTI Certification means that the tower  
has been tested under operating condi-  
tions and found to perform as rated by  
the manufacturer under those circum-  
stances. It assures the buyer that the  
tower is not intentionally or inadvertent-  
ly undersized by the manufacturer.  
The tower shall be capable of cooling  
_____ m3/h of water from ____ °C to  
_____ °C at a design entering air wet-  
bulb temperature of _____ C and its  
thermal rating shall be Certified by the  
Cooling Technology Institute.  
2.2  
2.3  
The tower shall be capable of a mini-  
mum _____ m3/h/kilowatt efficiency per  
ASHRAE Standard 90.1.  
The minimum efficiency per ASHRAE  
Standard 90.1 for induced draft open cooling towers applied to comfort  
cooling is 8.68 kW @ 35/29.5/24.There are no efficiency requirements for  
non-comfort cooling applications. If you want greater efficiency you can  
CTI Certification notwithstanding,  
the cooling tower manufacturer shall  
guarantee that the tower supplied  
will meet the specified performance  
conditions when the tower is installed  
according to plan. If, because of a  
suspected thermal performance defi-  
ciency, the owner chooses to conduct  
an on-site thermal performance test  
under the supervision of a qualified,  
disinterested third party in accordance  
with CTI or ASME standards during the  
first year of operation; and if the tower  
fails to perform within the limits of  
test tolerance; then the cooling tower  
manufacturer will pay for the cost of  
the test and will make such corrections  
as are appropriate and agreeable to the  
owner to compensate for the perfor-  
mance deficiency.  
require it by specifying a higher ASHRAE Standard 90.1 m3  
/h/kilowatt.  
CTI certification alone is not sufficient to assure you that the tower  
will perform satisfactorily in your situation. Certification is established  
under relatively controlled conditions, and towers seldom operate  
under such ideal circumstances.They are affected by nearby structures,  
machinery, enclosures, effluent from other towers, etc. Responsible and  
knowledgeable bidders will take such site-specific effects into consider-  
ation in selecting the tower—but the specifier must insist by the written  
specification that the designer/manufacturer guarantee this “real world”  
performance. Any reluctance on the part of the bidder should cause you  
some concern.  
3.0  
Warranty:  
3.1 The entire tower, including struc-  
ture, casing, basins, decking, fan(s),  
motor(s), and all mechanical drive com-  
ponents (including belts, if used) shall  
be warranted against failure due to  
defects in materials and workmanship  
for a period of five (5) years from the  
date of shipment to the job. Towers not  
covered by a warranty of this scope  
will not be accepted.  
4.0  
4.1  
Design Loading:  
It is important to understand the distinction between structure and  
anchorage. Specifying that only the anchorage meet these require-  
ments means the tower can become non-functional, even fall down, yet  
remain attached to the foundation. Specifying structure will require the  
tower to remain operational.  
The indicated design values are the minimum allowables under accept-  
ed design standards.They give you assurance that the tower can be  
The tower structure, anchorage and all  
its components shall be designed by  
licensed structural engineers per the  
International Building Code to with-  
stand a wind load of 1.44k/Pa, as well  
as a .3g seismic load. The fan deck  
and hot water basin covers shall be  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
6
Specifications  
Specification Value  
shipped, handled, hoisted—and ultimately operated in a normal cooling  
tower environment. Most NC Class models will withstand significantly  
higher wind and seismic loads. If your geographic location dictates  
higher wind load or seismic load values, please make the appropriate  
changes, after discussion with your Marley sales representative.  
Note: Some countries and states (Florida) require structure not anchor-  
age. Check with you local officials.  
designed for 2.4kPa live load or a 91kg  
concentrated load. Guardrails, where  
specified, shall be capable of with-  
standing a 890N concentrated live load  
in any direction, and shall be designed  
in accordance with OSHA guidelines.  
1.44k/Pa windload, .3g seismic load—applicable for most applications  
but consult the local code official for actual requirements.  
2.4kPa live load, 890N concentrated load—ensures the tower can be  
safely accessed for routine maintenance when a guardrail is installed as  
well ensuring the end user complies with government safety laws.  
5.0  
5.1  
Construction:  
For pure resistance to corrosion—coupled with the capability to meet  
stringent fire and building codes—there is no substitute for stainless  
steel! No paints or electrostatically-applied coatings, however exotic  
they may be, can match stainless steel's ability to withstand adverse  
operating conditions.  
Except where otherwise specified, all  
components of the cooling tower shall  
be fabricated of heavy-gauge, series  
300 stainless steel. The tower shall be  
capable of withstanding water having a  
chloride content (NaCl) up to 750 mg/L;  
a sulfate content (SO4) up to 1200  
mg/L; a calcium content (CaCO3) up to  
800 ppm; silica (SiO2) up to 150 mg/L;  
and design hot water temperatures  
up to 52°C. The circulating water shall  
contain no oil, grease, fatty acids, or  
organic solvents.  
Although SPX CoolingTechnologies makes use of many structural FRP  
components in various other product lines, they are held to a relative  
minimum in the NC Class Stainless line.This is to assure that there will  
be no question as to the structural integrity, fire resistance, and life  
expectancy in the mind of the owner.  
Except for those unusual operating situations where the circulating  
water may be so laden with suspended solids, algae, fatty acids, prod-  
uct fibers, active organisms reflected in BOD, and the like that plug-  
ging of film type fill is a probability, the NC Class Stainless is relatively  
immune to poor water quality. Where such conditions do exist, how-  
ever, thought should be given to the prevention of such carryover—or  
to the use of a Marley splash-fill product. Please discuss your situation  
with your Marley sales representative.  
5.2  
The specifications, as written, are  
intended to indicate those materials  
that will be capable of withstanding  
the above water quality in continuing  
service, as well as the loads described  
in paragraph 4.1. They are to be regard-  
ed as minimum requirements. Where  
component materials peculiar to indi-  
vidual tower designs are not specified,  
the manufacturers shall take the above  
water quality and load carrying capabili-  
ties into account in the selection of  
their materials of manufacture.  
Factory Assembly  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
7
Specifications  
Specification Value  
The Marley NC is the only crossflow  
cooling tower approved for single-cell  
FM installations.This could have a very  
beneficial effect upon your fire insurance  
premiums.Towers not able to meet FM  
requirements may require the inclusion  
of a fire protection sprinkler system to  
achieve a comparable level of insur-  
ance premium cost. Even if you are not  
insured by FM, this requirement ensures that each cell will contain any  
fire that may occur without losing the ability of limited operations and  
capacity.  
5.3* The tower shall include all design and  
material modifications necessary to  
meet the fire rating requirements of  
Factory Mutual. The product proposed  
shall be listed in the FM Approval  
Guide, latest edition.  
*Standard on models NC8301 thru NC8309. Available  
as an option on models NC8310 thru NC8312.  
6.0  
6.1  
Mechanical Equipment:  
Propeller-type fans require only half the operating hp of blower-type  
fans. However, they should be readily adjustable to permit compensa-  
tion for jobsite conditions.  
Fan(s) shall be propeller-type, incor-  
porating wide-chord aluminum alloy  
blades and galvanized hubs. Blades  
shall be individually adjustable.  
With NC, the choice is yours.The exclusive Marley System5  
Geareducer® requires no oil changes for five years, offering you  
unmatched reliability and low maintenance. Ideal for owners concerned  
about downtime or maintenance costs. Currently available on 49 NC  
models, the Marley Power Belt drive system features all-aluminum  
sheaves, power band belts and long-life bearings for dependable ser-  
vice.  
Maximum fan tip speed shall be 66  
m/s. Fan(s) shall be driven through a  
right angle, industrial duty, oil lubricat-  
ed, geared speed reducer that requires  
no oil changes for the first five (5)  
years of operation. The gearbox bear-  
ings shall be rated at an L10A service  
life of 100,000 hours or greater.  
TEFC motors offer additional benefits overTEAO motors whose only  
source of cooling is the flow of air produced by the cooling tower fan.  
This air rate is not always ideal due to motor position, blockage, etc.  
TEFC ensures the motor will always be cooled properly.  
6.1  
(alternate)* Fan(s) shall be propeller-  
type, incorporating wide-chord alumi-  
num alloy blades and galvanized hubs.  
Blades shall be individually adjustable.  
Fan(s) shall be driven through a one-  
piece multi-groove, solid back V-type  
belt, pulleys, and tapered roller bear-  
ings. Bearings shall be rated at an L10A  
service life of 40,000 hours or greater.  
*Currently available on Models NC8304 through  
NC8309.  
Unless otherwise specified, motor speed will be 1500 RPM on standard  
models. Low noise models will use motor speeds appropriate for the  
specific model. If you prefer the operating flexibility of two-speed oper-  
ation, please specify two-speed, single-winding motors which offer full  
and half speeds for maximum energy savings. Incidentally, two speed  
motors are a better choice than separate “pony” motors which simply  
double the problems indicated above and induce parasitic loads during  
operation for lower than nameplate efficiency.  
6.2  
Motor(s) shall be ____ kW maximum,  
TEFC, 1.15 service factor, variable  
torque, and specially insulated for cool-  
ing tower duty. Speed and electrical  
characteristics shall be ______ RPM,  
single-winding, ___ phase, ____ hertz,  
____ volts. Motor shall operate in the  
shaft-horizontal position, and name-  
plate kilowatt shall not be exceeded at  
design operation.  
6.3  
The complete mechanical equipment  
assembly for each cell shall be support-  
ed by a rigid steel structural support  
that resists misalignment between the  
motor and the gear reducer.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
8
Specifications  
Specification Value  
7.0  
7.1  
Fill, Louvers and Drift Eliminators:  
Louvers integral with the fill keep the flowing water within the confines  
of the fill.The separate external louvers used by others permit water to  
escape the fill and form ice or produce an unsightly situation adjacent  
to the tower and waste water. If you  
plan to use your tower in the win-  
tertime, particularly for free cooling,  
integral louvers will put your operat-  
ing concerns to rest. Integral louvers  
offer the best available technology for  
winter operation and water conserva-  
Fill shall be film type, thermoformed  
of 0.40mm thick PVC, with louvers  
formed as part of each fill sheet. Fill  
shall be suspended from hot dip gal-  
vanized structural tubing supported  
from the tower structure, and shall be  
elevated above the floor of the cold  
water basin to facilitate cleaning. Air  
inlet faces of the tower shall be free of  
water splash-out. Fill shall be capable  
of withstanding a hot water tempera-  
ture of 52°C.  
tion.  
Fill options are available for hot water  
temperatures up to 60°C.  
Drift rate varies with design water  
loading and air rate, as well as drift  
eliminator depth and number of  
directional changes. A drift rate of  
0.001% is readily available in standard  
configuration without premium cost. If a  
lower rate is required, please discuss with your  
Marley sales representative.  
7.2  
Drift eliminators shall be PVC, triple-  
pass, and shall limit drift losses to  
0.005% or less of the design water  
flow rate.  
Keep in mind…  
• Drift for towers with three-pass high efficiency eliminators constitute a  
small percentage of water usage.  
• Unlike thermal performance, drift rates are not certified and field drift  
tests are cost prohibitive for most applications.  
• Drift rates below 0.001 are difficult to measure in the field.  
• Certain water treatment chemicals can impact the drift rate.  
DRIFT ELIMINATOR  
separate from fill  
on some models  
LOUVERS  
FILL  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
9
Specifications  
Specification Value  
8.0  
8.1  
Hot Water Distribution System:  
Gravity-flow distribution basins are a feature of crossflow type tow-  
ers, resulting in operating pump heads of 3 to 6 meters less than that  
encountered in counterflow towers with pressurized spray systems.  
Also, these basins are located where they can be easily inspected—  
even maintained—while the tower is in operation.  
Two stainless steel open basins (one  
above each bank of fill) shall receive  
hot water piped to each cell of the  
tower. These basins shall be installed  
and sealed at the factory, and shall be  
equipped with removable, stainless  
steel covers capable of withstanding  
the loads described in paragraph 4.1.  
All components of these basins, with  
the exception of the nozzles, shall be  
stainless steel. The water distribution  
system shall be accessible and main-  
tainable during tower fan and water  
operation.  
8.2  
8.3  
Each basin shall include an inlet  
hole and bolt circle to accept a 125#  
flange connection per ANSI B16.1.  
Removable, interchangeable polypro-  
pylene nozzles installed in the floor of  
these basins shall provide full coverage  
of the fill by gravity flow.  
Some manufacturers require shutting down the tower to clean the dis-  
tribution system. Can you afford to do that?  
The water distribution system shall  
be accessible and maintainable while  
tower is operating.  
Materials other than heavy-gauge steel for fan decks may be unable to  
meet your specified loading requirements. See remarks Guardrail and  
Ladder on page 13.  
9.0  
9.1  
Casing, Fan Deck and Fan Guard:  
The casing and fan deck shall be  
heavy-gauge stainless steel, and shall  
be capable of withstanding the loads  
described in paragraph 4.1. The top of  
the fan cylinder shall be equipped with  
a conical, non-sagging, removable fan  
guard, fabricated of welded 8mm and  
7 gauge rods, and hot dip galvanized  
after fabrication. Fan cylinders 1.5m in  
height and over shall not be required to  
have a fan guard.  
In addition steel is excellent at resisting damage, cracking, UV and fire.  
The heavy construction of the Marley fan guard generally precludes the  
need for stainless  
steel material. If  
you would prefer  
these to be stain-  
less steel, please  
adjust the word-  
ing of the last sen-  
tence accordingly.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Base  
/
/
10  
Specifications  
Specification Value  
10.0 Access:  
The access doors on NC8301 and  
NC8302 towers are 76cm wide by  
84cm high. On NC8303 thru NC8312  
the access doors are 122cm high.  
Small access doors are prohibitive  
and discourage maintenance, which  
in turn can impact your operation.  
Specifying the size of the door will  
cause some bidders to take excep-  
tion, alerting you to a potential  
maintenance headache.Two doors  
are standard on all NC Class tow-  
ers—one in each endwall.  
10.1 A large stainless steel, rectangular  
access door shall be located on both  
end panels for entry into the cold  
water basin. Doors shall provide  
access to the fan plenum area to facili-  
tate inspection and allow maintenance  
to the fan drive system.  
11.0 Cold Water Collection Basin:  
11.1 The collection basin shall be heavy-  
gauge S300 stainless steel, and shall  
include the number and type of suction  
connections required to accommodate  
the outflow piping system shown on  
the plans. Suction connections shall be  
equipped with stainless steel debris  
screens. A factory-installed, float-oper-  
ated, mechanical make-up valve shall  
be included. An overflow and drain  
connection shall be provided in each  
cell of the cooling tower. The basin  
floor shall slope toward the drain to  
allow complete flush out of debris and  
silt which may accumulate. Towers of  
more than one cell shall include stain-  
less steel flumes for flow and equal-  
ization between cells. The basin shall  
be accessible and maintainable while  
water is circulating.  
The NC tower design offers side-  
suctions, side-outlet sumps, and  
bottom outlets to accommodate  
a significant variety of piping schemes. Unless so specified, the tower  
you may be asked to approve may only be available with one type of  
suction connection, requiring you to redesign your piping layout.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
11  
Specifications  
Specification Value  
Convenience and Safety Options  
Guardrail and Ladder:  
11.2 Add the following paragraph in  
the Access section: The top of the  
tower shall be equipped with a sturdy  
guardrail, complete with kneerail and  
toeboard, designed according to OSHA  
guidelines and factory welded into  
subassemblies for ease of field instal-  
lation. Posts, toprails and kneerails  
shall be 38mm square tubing. The  
guardrail assembly shall be hot dipped  
galvanized after welding and capable  
of withstanding a 890N concentrated  
live load in any direction. Posts shall  
be spaced on centers of 2.4m or less.  
A 46cm wide aluminum ladder with  
76mm I-beam side rails and 32mm  
diameter rungs shall be permanently  
attached to the endwall casing of the  
tower, rising from the base of the  
tower to the top of the guardrail.  
The NC Class cooling tower has been  
designed to minimize the need for mainte-  
nance personnel to get on top of the tower  
to perform maintenance and inspections.  
For the comfort and safety of your operat-  
ing personnel, we recommend that you  
specify a ladder and guardrail—and that  
you require it of all bidders! Although not  
required for safe operation by OSHA many  
user's own safety rules may dictate these  
options.  
Outside the tower, stainless steel guardrail  
material is not normally considered necessary. If you air quality is  
sufficiently poor to warrant stainless steel, change the specifica-  
tion wording accordingly.  
Ladder Extension:  
11.2 Add the following to the end of the  
above paragraph: Provide a ladder  
extension for connection to the foot  
of the ladder attached to the tower  
casing. This extension shall be long  
enough to rise from the roof (grade)  
level to the base of the tower. The  
installing contractor shall be respon-  
sible for cutting the ladder to length;  
attaching it to the foot of the tower lad-  
der; and anchoring it at its base.  
Many towers are installed such that the base of the tower is 61cm  
or more above the roof or grade level.This makes it difficult to  
get up to the foot of the attached ladder.The ladder extension  
alleviates this problem. Marley ladder extensions are available in  
standard 1.5m and 3.3m lengths.  
Ladder Safety Cage:  
11.3 Add the following paragraph in the  
Access section: A heavy gauge galva-  
nized steel safety cage shall surround  
the ladder, extending from a point  
To meet OSHA guidelines, towers whose fan decks are 6m or  
more above roof or grade, and which are equipped with lad-  
ders, should have safety cages surrounding the ladders, but with  
approximately 2m clear headroom.  
approximately 2m above the foot of  
the ladder to the top of the guardrail.  
Outside the tower, stainless steel safety cage material is not  
normally considered necessary. If you air quality is sufficiently  
poor to warrant stainless steel, change the specification wording  
accordingly.  
Ladder Safety Gate:  
10.3 Add the following paragraph in the  
Access section: A galvanized steel,  
self-closing gate shall be provided at  
the guardrail level of the ladder.  
A galvanized self-closing gate located at the guardrail level of  
the fan deck, exterior motor access platform and access door  
platform. Stainless steel is available with the stainless guardrail  
option.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
12  
GUARDRAIL  
LADDER  
LADDER  
EXTENSION  
ACCESS DOOR  
PLATFORM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
13  
Specifications  
Specification Value  
Access Door Platform:  
11.2 Add the following paragraph in the  
Access section: There shall be an  
access platform at the base of the  
tower extending from the vertical lad-  
der to the endwall access door. The  
platform shall be galvanized steel bar  
grating, supported by galvanized steel  
framework attached to the tower.  
The platform shall be surrounded by a  
guardrail, kneerail, and toeboard.  
Where towers are installed on an elevated grillage or piers, it is  
often difficult to get to—and through—the access door conve-  
niently.This platform provides easy, safe and comfortable access  
to that door. It also extends beyond the door to provide ready  
access to the optional Control System. See drawing on page 12.  
Outside the tower, stainless steel platform material is not normal-  
ly considered necessary. If you air quality is sufficiently poor to  
warrant stainless steel, change the specification wording accord-  
ingly.  
Plenum Walkway  
11.2 Add the following paragraph in the  
Access section: Provide a factory-  
installed, galvanized steel bar grating  
walkway extending from one endwall  
access door to the other endwall. This  
walkway shall be supported by a gal-  
vanized steel framework, and the top  
of the grating shall be at or above the  
cold water basin overflow level.  
Interior Mechanical Equipment  
Access Platform NC8303 thru NC8309  
11.2 Add the following paragraph in the  
Access section: A factory-installed,  
elevated galvanized bar grating plat-  
form convenient to the care and main-  
tenance of the tower's mechanical  
equipment shall be provided.  
Interior Mechanical Equipment  
Access Platform NC8310 thru NC8312  
11.2 Add the following paragraph in the  
Access section: An internal ladder  
shall extend upward from the plenum  
walkway to an elevated galvanized  
bar grating platform convenient to the  
care and maintenance of the tower's  
mechanical equipment. The platform  
shall be surrounded by a sturdy guard-  
rail and kneerail system.  
NOTE  
OSHA and other concerned authorities are in the process  
of developing guidelines regarding the safety procedures and  
protective equipment that should be provided maintenance per-  
sonnel who are required to go inside cooling towers. We feel it  
advisable to provide for as much maintenance as possible from  
outside the cooling tower and, to that end, offer such options as  
Guardrail and Ladder—pg 11, Ladder Extension—pg 11, Ladder  
Safety Cage—pg 11, Access Door Platform—pg 13, and Motor  
Out of the Airstream—pg 18. Such interior convenience options  
as Plenum Walkway—pg 13, that are offered are not meant as  
an invitation to perform inside maintenance. They are intended  
solely to maximize the comfort and safety of maintenance per-  
sonnel during the performance of any inside work may become  
necessary.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
14  
Specifications  
Specification Value  
Control Options  
Fan Motor Starter Control Panel:  
6.4  
Add the following paragraph in  
the Mechanical Equipment sec-  
If it is your opinion that the control system for the cooling tower  
be part of the tower manufacturers responsibility, we are in  
wholehearted agreement with you. Who better to determine the  
most efficient mode and manner of a cooling towers operation—  
and to apply a system most compatible with it—than the design-  
er and manufacturer of the cooling tower?  
tion: Each cell of the cooling tower  
shall be equipped with a UL listed  
control system in a IP14 or IP56 out-  
door enclosure capable of controlling  
single-speed or two-speed motors as  
required, and designed specifically for  
cooling tower applications. The panel  
shall include a main fused disconnect  
or main circuit breaker with an external  
operating handle, lockable in the off  
position for safety. Across-the-line mag-  
netic starters or solid-state soft-start  
starters as required shall be controlled  
with a thermostatic or solid-state  
Marley variable speed drives are also available for the ultimate in  
temperature control, energy management and mechanical equip-  
ment longevity. See specifications on page 16.  
temperature controller. Door mounted  
selector switches shall be provided to  
enable automatic or manual control  
and wired for 240VAC control. Control  
circuit to be wired out to terminal  
blocks for field connection to a remote  
vibration switch, overload trip alarms  
and remote temperature control devic-  
es. The temperature controller shall be  
adjustable for the required cold-water  
temperature. If a thermostatic control-  
ler is used it shall be mounted on the  
side of the tower with the temperature  
sensing bulb installed in the cold water  
basin using a suspension mounting  
bracket. If a solid-state temperature  
controller is used the controller will be  
door mounted on the control panel.  
The temperature controller will display  
two temperatures, one for outgoing  
water and the other for set point.  
Water temperature input shall be  
obtained using a three-wire RTD with  
dry well in the outlet water piping and  
wired back to the solid-state tempera-  
ture controller in the control panel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
15  
Specifications  
Specification Value  
Vibration Limit Switch:  
6.5  
Add the following paragraph in the  
Mechanical Equipment section: A  
single-pole, double-throw vibration  
limit switch in a IP56 housing shall be  
installed on the mechanical equipment  
support for wiring into the fan motor  
shutdown circuit. The purpose of this  
switch will be to interrupt power to the  
motor in the event of excessive vibra-  
tion. It shall be adjustable for sensitiv-  
ity, and shall require manual reset.  
Unless specified otherwise, a  
Metrix switch will be provided.  
A double-pole, double-throw  
model is also available. If  
purchased in conjunction with  
the Control System, it is also  
factory-wired.The requirement  
for manual reset assures that  
the cooling tower will be vis-  
ited to determine the cause of  
excess vibration.  
Basin Heater:  
11.2 Add the following paragraph in the  
Cold Water Basin section: Provide a  
system of electric immersion heaters  
and controls for each cell of the tower  
to prevent freezing of water in the  
collection basin during periods of shut-  
down. The system shall consist of one  
or more stainless steel electric immer-  
sion heaters installed in threaded cou-  
plings provided in the side of the basin.  
A IP56 enclosure shall house a mag-  
netic contactor to energize heaters; a  
transformer to provide 24-volt control  
circuit power; and a solid-state circuit  
board for temperature and low water  
cut-off. A control probe shall be located  
in the basin to monitor water level  
and temperature. The system shall be  
capable of maintaining 5°C water tem-  
perature at an ambient air temperature  
of _____ °C.  
The Marley basin heater components described at left represent our rec-  
ommendation for a reliable automatic system for the prevention of basin  
freezing.They are normally shipped separately for installation at the job-  
site by the installing contractor. When purchased in conjunction with the  
enhanced Control System option, however, they are customarily factory-  
mounted and tested.  
Submerged in basin water,  
in which zinc ions are pres-  
ent, copper immersion heat-  
ers must not be used. Insist  
upon stainless steel.  
The ambient air temperature  
that you insert in the specifi-  
cations should be the lowest  
1% level of winter tempera-  
ture prevalent at site.  
Electric Water Level Control:  
11.1 Replace this paragraph with the fol-  
lowing: The collection basin shall be  
heavy-gauge series 300 stainless steel  
and shall include the number and type  
of suction connections required to  
Solid-state liquid level controls provide you with state of the art sys-  
tems to control and monitor the water level in your cooling tower col-  
lection basin. Relays operating in conjunction with suspended stainless  
steel electrode probes monitor basin water levels, providing simple  
solenoid-valve water makeup or discrete on/off signals to more sophis-  
ticated automation controls. Optional configurations might include  
makeup along with high and low water level alarm and cutoff, or pump  
cutoff. Packaged systems including any of these variations are available.  
Consult you Marley sales representative or download a copy of ACC-  
NC-9D from spxcooling.com for additional information.  
accommodate the out-flow piping sys-  
tem shown on the plans. Suction con-  
nections shall be equipped with stain-  
less steel debris screens. A solid-state  
water level control system to monitor  
the water level with a multi-relay con-  
trol panel pre-wired and mounted in  
a IP56 nonmetallic enclosure shall be  
provided. The system shall consist of  
water level sensing and control units  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
16  
Specifications  
Specification Value  
in quantities and locations as indicated  
on the drawings. An overflow and drain  
connection shall be provided in each  
cell of the cooling tower. The basin  
floor shall slope toward the drain to  
allow complete flush out of debris and  
silt which may accumulate. Towers of  
more than one cell shall include stain-  
less steel flumes for flow and equal-  
ization between cells. The basin shall  
be accessible and maintainable while  
water is circulating.  
Fan Motor Variable Speed Drive:  
Marley Variable Speed Drive systems are designed to combine absolute  
temperature control with ideal energy management.The cooling tower  
user selects a cold water temperature and the drive system will vary the  
fan speed to maintain that temperature. Precise temperature control is  
accomplished with far less stress to the mechanical equipment compo-  
nents.The improved energy management provides fast payback to the  
user.  
Marley All Weather ACH550 System  
6.4  
Add the following paragraph in the  
Mechanical Equipment section when  
VFD is used with customers Building  
Management System: A complete UL  
listed Variable Speed Drive system in a  
IP10 indoor, IP52 indoor or IP14 outdoor  
enclosure shall be provided. The VFD  
shall use PWM technology with IGBT  
switching and integrated bypass design.  
VFD out put switching shall not cause  
mechanical issues with gearbox teeth  
or drive shafts. The VFD shall catch a fan  
spinning in the reverse direction without  
tripping. The panel shall include a main  
disconnect with short circuit protection  
and external operating handle, lockable  
in the off position for safety. The VFD  
system shall receive a speed reference  
signal from the Building Management  
System monitoring the tower cold-water  
temperature. As an option to receiving  
the speed reference signal from a build-  
ing management system, the drive must  
have the capability to receive a 4-20 ma  
temperature signal from an RTD trans-  
mitter. The VFD shall have an internal PI  
regulator to modulate fan speed main-  
taining set point temperature. The drive's  
panel display shall be able to display the  
set-point temperature and cold-water  
temperature on two separate lines. The  
bypass shall include a complete mag-  
netic bypass circuit and with capability  
to isolate the VFD when in the bypass  
mode. Transfer to the bypass mode shall  
be manual in the event of VFD failure.  
Once the motor is transferred to the  
by-pass circuit the fan motor will run at  
constant full speed. The bypass circuit  
will not modulate ON and OFF based on  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
17  
Specifications  
Specification Value  
cold-water temperature. The application  
must be able to handle very cold water  
while VFD is in a by-pass mode. Operator  
controls shall be mounted on the front of  
the enclosure and shall consist of start  
and stop control, bypass/VFD selection,  
Auto/Manual selections, manual speed  
control. To prevent heating problems  
in the cooling tower fan motor and to  
assure proper gear reducer lubrication  
the VFD system shall de energize the  
motor once 25% motor speed is reached  
and cooling is no longer required. The  
cooling tower manufacturer shall supply  
VFD start-up assistance. Tower vibration  
testing throughout the speed range is  
required to identify and lockout any natu-  
ral frequency vibration levels which may  
exceed CTI guidelines.  
Marley Premium VFD System  
6.4  
Add the following paragraph in  
the Mechanical Equipment section  
when VFD is used as a stand alone  
system: A complete UL listed Variable  
Speed Drive system in a IP52 indoor or  
IP14 outdoor enclosure shall be provided.  
The VFD shall use PWM technology with  
IGBT switching and integrated bypass  
design. VFD output switching shall not  
cause mechanical issues with gearbox  
teeth or drive shafts. The VFD shall catch  
a fan spinning in the reverse direction  
without tripping. The panel shall include  
a main disconnect with short circuit pro-  
tection and external operating handle,  
lockable in the off position for safety.  
The system shall include a solid state,  
PI temperature controller to adjust fre-  
quency output of the drive in response  
to the tower cold-water temperature.  
The temperature of the cold water and  
set point shall be displayed on the door  
of the control panel. The bypass shall  
include a complete magnetic bypass  
circuit with capability to isolate the VFD  
when in the bypass mode. Transfer to  
the bypass mode shall be automatic in  
the event of VFD failure or for specific  
trip conditions allowing safe transfer of  
utility voltage to the motor. Automatic  
bypass with an earth ground condition is  
not allowed. The bypass contactor shall  
be cycled on and off while operating in  
bypass, to maintain the set-point temper-  
ature of the cold water. The drive design  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
18  
Specifications  
Specification Value  
shall be operated as a stand- alone sys-  
tem without the need for a BMS system.  
Operator controls shall be mounted  
on the front of the enclosure and shall  
consist of start and stop control, bypass/  
VFD selector switch, Auto/Manual  
selector switch, manual speed control,  
and solid-state temperature controller.  
An emergency bypass selector switch  
internal to the panel allowing the cooling  
tower fan motor to be run at full speed  
shall be furnished. To prevent heating  
problems in the cooling tower fan motor  
and to assure proper gear box lubrication  
the VFD system shall de energize the  
motor once 25% motor speed is reached  
and cooling is no longer required. The  
VFD shall include de-icing logic with auto  
canceling and adjustable time. Speed  
in De-Ice mode shall not exceed 50 %  
motor speed. The cooling tower manu-  
facturer shall supply VFD start-up assis-  
tance. Tower vibration testing throughout  
the speed range is required to identify  
and lockout any natural frequency vibra-  
tion levels which may exceed CTI guide-  
lines.  
Miscellaneous Options  
Motor out of the Airstream:  
For many years, a feature of  
Marley cooling towers was that  
the electric motors were located  
outside the fan cylinders, where  
they were easily accessible, and  
where they were not subjected to  
the constant humidity that exists  
inside the tower plenum.  
6.1  
Add the following to the end of this  
paragraph: The motor shall be mount-  
ed outside the casing of the tower, and  
shall be connected to the gear reducer  
by a dynamically-balanced, stainless  
steel tube and flange driveshaft.  
Although improved motor designs  
(insulation, bearings, seals, and  
lubricants) have now made it fea-  
sible for us to locate the motor inside the tower in close-coupled prox-  
imity to the Geareducer® (page 7), many users still prefer the motor to  
be located outside the humid airstream. If you are among those users—  
or are among those who see the wisdom of their thinking—please spec-  
ify this option. If you do, however, please require it of all bidders.  
Fan Cylinder Extensions:  
Extensions are available in 305mm increments to a maximum height  
equal to the diameter of the fan. Such extensions may be considered  
necessary in order to elevate the discharge beyond the bounds of an  
enclosure. Discuss applicability with your local Marley sales representa-  
tive.  
9.1  
Insert the following after the first  
sentence: Fan cylinder extensions  
shall be provided to elevate the fan dis-  
charge to a height of ___ m above the  
fan deck level.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
19  
Specifications  
Specification Value  
Marley flow-control valves have been a  
favorite of users since the 1950s.They  
remain serviceable for the life of the tower  
and provide a continuing means of flow-  
regulation between hot water basins—and  
between cells of multicell towers as well.  
Inlet Flow Control Valves:  
8.2: Add the following to the end of the  
paragraph: Heavy-duty flow-regulator  
valves shall be provided at the hot  
water inlet connections. These valves  
shall be disc-type, with cast iron  
bodies and stainless steel operating  
stems. There shall be a locking handle  
to maintain the valve setting in any  
position. Valves shall be right-angle  
configuration, precluding the need for  
inlet elbows.  
Where it is your intention to be able to operate both cells of the tower  
while the flume cover plate is installed, separate outlet connections,  
Equalizer Flume Weir Gates:  
float valves and overflows must be provided for each cell. Likewise, this  
would require separate sensors and controls for basin heater systems,  
if installed.  
11.2: Add the following paragraph under  
Cold Water Collection Basin: The  
interconnecting flume between cells  
shall be equipped with a removable  
cover plate to permit the shutdown of  
one cell for maintenance purposes, or  
to permit independent cell operation.  
Sound produced by a  
standard NC Cooling  
Sound Control  
Tower operating in an  
unobstructed environ-  
ment will meet all but  
the most restrictive  
noise limitations—and  
will react favorably to  
natural attenuation.  
Where the cooling  
1.2  
Add the following paragraph under  
Base: The cooling tower shall be quiet  
operation, and shall produce an overall  
level of sound not higher than _______  
dB(A) measured at _______ m from the  
locations in the table below. All low  
noise options and combinations shall  
be CTI Certified for thermal perfor-  
mance.  
tower has been sized  
to operate within an  
Location  
63  
125  
250  
500  
1000  
enclosure, the enclosure itself will have a damping effect on sound.  
Sound also declines with distance—by about 5 or 6 dB(A) each time the  
distance doubles. Where noise at a critical point is likely to exceed an  
acceptable limit, you have several options—listed below in ascending  
order of cost impact:  
Discharge  
Air Inlet  
Cased Face  
Location  
2000  
4000  
8000  
Overall dB(A)  
Discharge  
Air Inlet  
Cased Face  
• Where only a slight reduction in noise will satisfy—and the source of  
concern is in a particular direction—merely turning the cooling tower  
may be the answer. Less sound emanates from the cased face of the  
cooling tower than does from the air intake face.  
Inlet Sound Attenuation  
• In many cases, noise concerns are limited to nighttime, when ambi-  
ent noise levels are lower and neighbors are trying to sleep.You can  
usually resolve these situations by using two-speed motors—operating  
the fans at reduced speed without cycling “after hours.The natural  
nighttime reduction in wet-bulb temperature makes this a very feasible  
solution in most areas of the world, but the need to avoid cycling may  
cause the cold water temperature to vary significantly.  
1.3  
Add the following paragraph under  
Base: The cooling tower shall be  
equipped with inlet sound attenuation  
baffles positioned and spaced verti-  
cally. The baffles will be spaced across  
the entire length and extend the full  
height of the air inlet. The baffles will  
be constructed of perforated sheet  
metal and contained within a steel  
• A Marley Variable Speed Drive automatically minimize the towers  
noise level during periods of reduced load and/or reduced ambient  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
20  
Specifications  
Specification Value  
temperature without sacrificing the systems ability to maintain a con-  
stant cold water temperature.This is a relatively inexpensive solution,  
and can pay for itself quickly in reduced energy costs.  
box which is self supporting. The inlet  
attenuation will not be allowed to  
impact the thermal performance effi-  
ciency of the basic tower configuration.  
The most extreme cases may require inlet and discharge sound attenu-  
ator sections—however, the static pressure loss imposed by discharge  
attenuators may necessitate an increase in tower size.Two stages of  
inlet or discharge attenuators supported by the tower and designed and  
tested for the most stringent requirements are available as an option.  
Outlet Sound Attenuation  
1.4  
1.4  
6.1  
Add the following paragraph under  
Base: The cooling tower shall be  
equipped with outlet sound attenuation  
baffles positioned and spaced horizon-  
tally across the entire fan opening. The  
baffles will be constructed of perfo-  
rated sheet metal and contained within  
a steel box which is self supporting  
and made of the same material as the  
tower.  
Falling water sound—unlike counterflow towers which allow the water  
to free-fall and splash into the cold water collection basin, PVC film-  
fill crossflow towers have no splashing.This allows a crossflow tower  
much lower sound levels at the air inlet than a counterflow tower—  
especially induced draft counterflow towers. Even with the “splash-mat-  
ting” option in a counterflow cold water collection basin, a crossflow  
tower air inlet is still quieter. Plus you do not have to worry about clog-  
ging the splash matting.Yet another maintenance and operation advan-  
tage of the crossflow configuration.  
NC Class models with the “Lsuffix in the model number are the special  
low sound editions.To achieve the very lowest possible sound levels  
while maintaining efficiency, the best available combination of motor,  
gear ratio, fan blade count and blade profile were carefully selected for  
every “Lmodel. All “Lmodels come with the Low-Noise Fan option.  
If you choose the sound attenuator option, the fan will automatically  
change to the Low-Noise Fan option.  
Low Noise Fan  
Replace paragraph 6.1 with the fol-  
lowing: Fan(s) shall be propeller-type,  
incorporating a minimum of seven  
wide-chord aluminum alloy blades  
and galvanized hubs. Blades shall be  
individually adjustable. Maximum fan  
tip speed shall be 56 m/s. Fan(s) shall  
be driven through a right angle, indus-  
trial duty, oil lubricated, geared speed  
reducer that requires no oil changes  
for the first five (5) years of operation.  
The gearbox bearings shall be rated at  
an L10A service life of 100,000 hours or  
greater.  
Tip Speed—unlike thermal performance, no certification program exists  
for sound. While Marley conducts actual sound tests on all its configura-  
tions there are only  
a few ways for the  
client to ensure  
they get a quiet  
tower.  
• One is to conduct  
a field sound test  
after installation.  
On-site testing  
after installation  
can however be  
inaccurate depend-  
ing on the environ-  
ment.  
(alternate)* Fan(s) shall be propeller-  
type, incorporating a minimum of  
seven wide-chord aluminum alloy  
blades and galvanized hubs. Blades  
shall be individually adjustable. Fan(s)  
shall be driven through a one-piece  
multi-groove, solid back V-type belt,  
pulleys, and tapered roller bearings.  
Bearings shall be rated at an L10A ser-  
vice life of 40,000 hours or greater.  
*Currently available on Models NC8304 through  
NC8309.  
• Another is to conduct a sound test at the factory. However both can be  
cost prohibitive for smaller applications.  
• Specifying fan blade tip speed is one way to physically force the tower  
selection to be quiet.Tip speed is easily checked by multiplying the fan  
rpm by the fan circumference at the blade tip (π fan dia). Over 61m/s is  
considered high by most people. 51-61 is considered typical and expect-  
ed. 41-51 would be considered low noise. Below 41 is difficult to hear  
above the water noise.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
21  
Specifications  
Specification Value  
Ultra Low-Noise Fan  
For more severe cases requiring the lowest possible fan sound levels  
the Marley “Ultra Low-Noise” fan option is now available on all but the  
NC8301 NC Class models.Tower height may increase slightly—obtain  
current sales drawings from your Marley sales representative for accu-  
rate dimensions. If your requirement calls for inlet and outlet attenu-  
ation, you might consider the Ultra Low-Noise fan in lieu of attenua-  
tion. Outlet attenuators are not available with the Ultra Low-Noise Fan  
option.  
1.4  
Replace paragraph 6.1 with the fol-  
lowing: Fan(s) shall be propeller-type,  
incorporating wide-chord forward-  
swept FRP blades and galvanized  
hubs. Blades shall be individually  
adjustable. Maximum fan tip speed  
shall be 51 m/s. Fan(s) shall be driven  
through a right angle, industrial duty, oil  
lubricated, geared speed reducer that  
requires no oil changes for the first  
five (5) years of operation. The gearbox  
bearings shall be rated at an L10A ser-  
vice life of 100,000 hours or greater.  
Available on Models NC8302 through NC8312.  
Single Hot Water Inlet Connection  
per Cell:  
This option reduces what might otherwise be a complex hot water  
piping layout to a simple, single connection per cell. It also avoids an  
unsightly (perhaps unsafe) maze of pipe exposed above the top deck of  
the tower.  
8.2  
Replace this paragraph with the  
following: Each cell of the tower  
shall include a single hot water inlet  
connection located as shown on the  
plans. An internal system of piping  
shall deliver water equally to the dis-  
tribution basins without the need for  
balancing valves. This internal piping  
system shall require no scheduled  
maintenance, and shall be located such  
that it does not interfere with normal  
maintenance access. The internal pip-  
ing must extend to the tower exterior.  
Removable, interchangeable polypro-  
pylene nozzles installed in the floor of  
these basins shall provide full coverage  
of the fill by gravity flow.  
The single inlet connection can be located either in the tower's endwall  
casing, or below the cold water basin.The endwall entry point is suit-  
able for single-cell towers, and for those that might be installed in  
groups of two cells each. Bottom inlet piping lends itself to close-  
spaced, multicell installations and to those situations where it is appro-  
priate to keep all pipework below the level of the tower.  
Be sure to specify that the internal pipe extends to the tower exterior  
panel, either the casing panel or collection basin floor. Some manufac-  
turers require the contractor to complete the internal piping adding to  
your cost.  
In wooded or windy  
areas, these screens help  
to keep leaves or blowing  
debris out of the cool-  
ing tower and circulating  
water system.  
Air Inlet Screens:  
9.1  
Add the following paragraph to the  
Casing, Fan Deck and Fan Guard sec-  
tion: The air inlet faces of the tower  
shall be covered by 1" mesh hot-dipped  
galvanized welded wire screens.  
Screens shall be secured to removable  
galvanized U-edge frames.  
High wind load designs  
greater than 30 psf are  
High Wind Load/Seismic Designs:  
available up to 100 psf.  
It is important to consult  
the local code official for actual requirements. Some manufacturers will  
claim their tower is capable but have never had the design reviewed by  
a licensed structural expert. Not requiring expert review for high wind  
and seismic regions is dangerous to you and the public.  
4.1  
Replace this paragraph with the fol-  
lowing: The tower structure, anchor-  
age and all its components shall  
be designed by licensed structural  
engineers per the international build-  
ing code to withstand a wind load of  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Marley NC Class Stainless CoolingTower Specifications: Options  
/
/
22  
Specifications  
Specification Value  
______ psf, as well as a ______ seismic  
load. The fan deck and hot water basin  
covers shall be designed for 50 psf live  
load or a 200 lb. concentrated load.  
Guardrails, where specified, shall be  
capable of withstanding a 200 lb. con-  
centrated live load in any direction, and  
shall be designed in accordance with  
OSHA guidelines.  
Used as water level equalizers between multicell towers. Not intended  
for water migration. Piping and attachment hardware by others. Flat  
faced flange required.  
Multicell Basin Equalizer Outlets:  
11.1 Add the following paragraph in the  
Access section: A hole and bolt circle  
shall be provided in the depressed sec-  
tion of the basin for equalizer piping  
between cells. A full-face, .25" thick, 50  
durometer gasket shall be provided at  
each equalizer location.  
PVC sweeper piping and Lakos nozzles. Designed for the following  
flows at 20 psig:  
Basin Sweeper Piping:  
NC8301 thru NC8304, 33m3/h  
NC8305, 47m3/h  
11.1 Add the following paragraph in the  
Access section: The cold water basin  
shall be equipped with PVC sweeper  
piping with plastic eductor nozzles.  
The piping should create a grid under  
the fill and force all dirt and debris to  
the depressed section of the collection  
basin.  
NC8306 thru NC8312, 64m3/h  
The dipstick option is accessible from a portable maintenance ladder  
on one and two cell towers only. Maintenance considerations recom-  
mends this option be combined with the ladder and guardrail option on  
installations of three or more cells since the dipstick cannot be reached  
without accessing the fan deck.  
Extended Geareducer Lube Line  
with Dipstick:  
6.1  
Add the following paragraph in the  
Mechanical Equipment section: An  
external oil level dipstick shall be locat-  
ed adjacent to the motor at the fan  
deck surface and shall be accessible  
from a portable maintenance ladder.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPX COOLING TECHNOLOGIES UK LTD.  
GREGORY’S BANK  
WORCESTER WR3 8AB  
UNITED KINGDOM  
+44 (0) 1905 720 200  
spxcooling.com  
In the interest of technological progress,  
all products are subject to design and/or  
material change without notice.  
©2008 SPX Cooling Technologies  
uk_SPEC-SS-NC-08A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sigma Camera Lens 635101 User Manual
Snapper Snow Blower 1690497 User Manual
Sony Camcorder NEXVG10 User Manual
Sony Car Stereo System CDXGT920U User Manual
Sony Cassette Player CFM D1 User Manual
Sony Computer Monitor CPD G500 User Manual
Sony Digital Camera D50PH User Manual
Sony MP3 Player D EJ855 User Manual
Sony Projector VPL CX11 User Manual
Sony Stereo System STR DB870 User Manual