Schneider Electric Welder ATV61 User Guide

Altivar 61  
Migration from ATV38 V ATV61  
Transition manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of contents  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Implementation procedure  
V
Migration from ATV 38 ATV 61  
b 1 Identifying the existing ATV 38  
v Make an inventory of your Altivar 38 installation.  
b 2 Selecting the ATV 61  
v Determine the Altivar 61 catalog number.  
v Choose the various options required.  
Steps 3 and 4 must  
be performed with  
the power off.  
b 3 Mounting  
v Mount the drive in accordance with the  
instructions in this document, using the  
substitution kit.  
v Install any internal and external options.  
b 4 Wiring  
v Connect the motor, ensuring that its  
connections correspond to the voltage.  
v Connect the control.  
v Connect the speed reference.  
v Connect the line supply, after making sure  
that the power is off.  
b 5 Configuration  
v Drive  
v Communication cards  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Altivar 38 hardware identification  
Before selecting the Altivar 61, the Altivar 38 hardware configuration needs to be determined carefully.  
Measure the line voltage and indicate the type of power supply:  
1
2
Line voltage:_________V  
Three-phase  
ATV38HD16N4  
Motor Rating : 11 kW / 15HP  
Input V : 380/460V-50/60Hz  
Input phase : 3  
Output 3 Ph : 380/460V  
Output I : 22A  
Input I : 35.4/28 A  
Input fuse : Type J : 60A Max  
Output I max. transient (1mn) : 24.2A  
Output frequency : 0.1-500Hz  
Note down the drive catalog number, which appears on the Altivar 38 nameplate:  
ATV38______________________  
Cu AWG 6 : 75˚C : 20lb-in/2.26 Nm  
N998  
LISTED 170M  
IND.CONT.EQ  
Motor Protective Device  
Protection type Classe 20  
AIC 22000 A  
Serial N . 1703001070  
France - 6W  
0202  
Note down the catalog number of any EMC filter installed under the drive:  
VW3A584 ___________________  
3
4
5
Note down the catalog number of any option cards installed in the Altivar 38; this can be found on the label attached to the card:  
VW3A58_____________________  
Note down whether the operator terminal is used:  
VW3A58101:  
YES  
NO  
NO  
Is the operator terminal connected remotely on the enclosure YES  
door?  
Note down the catalog number of the NEMA type 1 mounting kit, if used:  
VW3A5885___________________  
6
Note down the catalog number of the control card fan kit, if used:  
VW3A5882___________________  
7
8
Make sure you have the diagrams for the existing installation.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Determining catalog numbers  
1. 1. Choosing the Altivar 61 catalog number  
Required information (refer to page 5): type of use, line voltage, Altivar 38 catalog number  
1. 1. 1. Your catalog number starts with ATV38H  
Power  
kW HP  
ATV38 catalog  
number  
ATV 61 catalog number  
Substitution kit  
VW3 A9 302  
Power supply  
380…460 V three-phase  
ATV38HU18N4  
0.75  
1
ATV 61H075N4 (1)  
ATV38HU29N4  
1.5  
2.2  
3.0  
4.0  
5.5  
7.5  
11  
2
ATV 61HU15N4 (1)  
ATV 61HU22N4 (1)  
ATV 61HU30N4 (1)  
ATV 61HU40N4 (1)  
ATV 61HU55N4 (1)  
ATV 61HU75N4 (1)  
ATV 61HD11N4 (1)  
ATV 61HD15N4 (1)  
ATV 61HD18N4 (2)  
ATV 61HD22N4 (2)  
ATV 61HD30N4 (2)  
ATV 61HD37N4 (2)  
ATV 61HD45N4 (2)  
ATV 61HD55N4 (2)  
ATV 61HD75N4 (2)  
ATV 61HD90N4 (2)  
ATV 61HC11N4 (2)  
ATV 61HC13N4 (2)  
ATV 61HC16N4 (2)  
ATV 61HC22N4 (2)  
ATV 61HC22N4 (2)  
ATV 61HC25N4 (2)  
ATV 61HC31N4 (2)  
ATV 61HC31N4 (2)  
VW3 A9 302  
VW3 A9 304  
VW3 A9 304  
VW3 A9 304  
VW3 A9 305  
VW3 A9 306  
VW3 A9 307  
VW3 A9 308  
VW3 A9 309  
VW3 A9 310  
VW3 A9 312  
VW3 A9 312  
VW3 A9 312  
VW3 A9 312  
VW3 A9 312  
ATV38HU41N4  
3
ATV38HU54N4  
-
ATV38HU72N4  
5
ATV38HU90N4  
7.5  
10  
ATV38HD12N4  
ATV38HD16N4  
15  
ATV38HD23N4  
15  
20  
ATV38HD25N4 (X)  
ATV38HD28N4 (X)  
ATV38HD33N4 (X)  
ATV38HD46N4 (X)  
ATV38HD54N4 (X)  
ATV38HD64N4 (X)  
ATV38HD79N4 (X)  
ATV38HC10N4 (X)  
ATV38HC13N4 (X)  
ATV38HC15N4 (X)  
ATV38HC19N4 (X)  
ATV38HC23N4 (X)  
ATV38HC25N4 (X)  
ATV38HC28N4 (X)  
ATV38HC31N4 (X)  
ATV38HC33N4 (X)  
18.5  
22  
25  
30  
30  
40  
37  
50  
45  
60  
55  
75  
75  
100  
125  
150  
200  
250  
300  
350  
400  
450  
500  
90  
110  
132  
160  
200  
220  
250  
280  
315  
Substitution kit: This kit consists of a metal support plate that makes it possible to re-use the same mounting holes as the ATV38.  
(1)Drive supplied with a graphic display terminal that can be connected remotely. To order a drive without a graphic display terminal, add  
the letter Z at the end of the catalog number. The drive will then be equipped with the integrated 7-segment display terminal.  
(2)On ATV38 catalog numbers ending with X, the RFI filter is disconnected in the event of use on an IT system (page 27 implementation).  
1. 1. 2. Your catalog number starts with ATV38ED  
You must install the Altivar 61 in an enclosure and customize the control devices yourself.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
1. Determining catalog numbers  
1. 2. Selecting the power circuit options  
1. 2. 1. Radio interference filters (VW3A684x)  
The filters previously installed on the ATV38 are not compatible with the ATV 61 and must, therefore, be replaced.  
No kit for substitution (mounting) between the 2 filter ranges.  
Drive catalog number  
Filter catalog number  
VW3 A4 401  
VW3 A4 402  
VW3 A4 403  
VW3 A4 404  
VW3 A4 405  
VW3 A4 406  
VW3 A4 407  
VW3 A4 408  
VW3 A4 410  
VW3 A4 411  
ATV 61H075N4, U15N4, U22N4  
ATV 61HU30N4, U40N4  
ATV 61HU55N4, U75N4  
ATV 61HD11N4  
ATV 61HD15N4, D18N4  
ATV 61HD22N4  
ATV 61HD30N4, D37N4  
ATV 61HD45N4, D55N4, D75N4  
ATV 61HD90N4, C11N4, C13N4, C16N4  
ATV61HC22N4, C25N4, C31N4  
1. 2. 2. Line chokes  
VZ1L0xxxMxx, VW3A5850x, VW3A6650x, VW3A6850x  
The line chokes used with the ATV38 can be re-used with the ATV 61 and do not, therefore, need to be replaced.  
1. 2. 3. Output filters (LR filters, LC filters)  
VW3A584 5x, VW3A6641x, VW3A6642x  
The output filters used with the ATV38 can be re-used with the ATV 61 and do not, therefore, need to be replaced.  
1. 2. 4. Motor chokes  
VW3A6650x, VW3A6855x  
The motor chokes used with the ATV38 can be re-used with the ATV 61 and do not, therefore, need to be replaced.  
1. 2. 5. Braking resistors  
VW3A5870x, VW3A5873x, VW3A6670x  
The braking resistors used with the ATV38 can be re-used with the ATV 61 and do not, therefore, need to be replaced.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Determining catalog numbers  
1. 3. Mounting accessories  
1. 3. 1. Removable power terminal kit (VW3A5881x)  
There is no equivalent to this kit for the Altivar 61.  
1. 3. 2. Air exchanger kit (VW3A5880x)  
There is no equivalent to this kit for the Altivar 61.  
Alternative solution: Mount the power part outside the enclosure using the ATV 61 VW3 A9 5xx flange-mounting kit. This solution can be  
used to reduce the heat dissipated inside the enclosure.  
1. 3. 3. NEMA type 1 mounting kit  
Required information: Altivar 61 catalog number  
Catalog number selection guide:  
ATV 61 catalog number  
ATV 61H075N4  
ATV 61HU15N4  
ATV 61HU22N4  
ATV 61HU30N4  
ATV 61HU40N4  
ATV 61HU55N4  
ATV 61HU75N4  
ATV 61HD11N4  
ATV 61HD15N4  
ATV 61HD18N4  
ATV 61HD22N4  
ATV 61HD30N4  
ATV 61HD37N4  
ATV 61HD45N4  
ATV 61HD55N4  
ATV 61HD75N4  
NEMA kit  
VW3 A9 201  
VW3 A9 201  
VW3 A9 201  
VW3 A9 202  
VW3 A9 202  
VW3 A9 203  
VW3 A9 203  
VW3 A9 204  
VW3 A9 205  
VW3 A9 205  
VW3 A9 206  
VW3 A9 207  
VW3 A9 207  
VW3 A9 209  
VW3 A9 209  
VW3 A9 209  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Determining catalog numbers  
1. 4. Control circuit options  
1. 4. 1. Control card fan kit (VW3A5882x)  
Required information: Altivar 61 catalog number  
At an ambient temperature between 50°C and 60°C, the Altivar 61 has a higher operating capacity than the Altivar 38.  
The control card fan kit is required for the following ATV 61 ratings if the ambient temperature is between 50 and 60°C.  
ATV 61 catalog number  
ATV 61HD22N4  
ATV 61HD30N4  
ATV 61HD37N4  
ATV 61HD45N4  
ATV 61HD55N4  
ATV 61HD75N4  
Control card fan kit  
VW3 A9 404  
VW3 A9 405  
VW3 A9 405  
VW3 A9 407  
VW3 A9 407  
VW3 A9 407  
1. 4. 2. Separate control card power supply kit (VW3A5860x)  
This kit serves no purpose as the ATV 61 integrates this function as standard and requires the presence of an external 24 V DC (30 W)  
supply.  
1. 4. 3. Remote display terminal (VW3A58103)  
Remote connection of the Altivar 61 graphic display terminal on the enclosure door  
IP54 version Remote mounting kit  
:
:
VW3 A1 102  
3-meter cable  
VW3 A1 104 R30  
IP65 version Remote mounting kit  
IP65 door  
:
:
:
VW3 A1 102  
VW3 A1 103  
3-meter cable  
VW3 A1 104 R30  
RJ45 female/female adapter  
:
VW3 A1 105  
This should be used in the above two instances.  
Note: Order an Altivar 61 with graphic display terminal (without Z at the end of the catalog number).  
Other connection cable lengths are available:  
Cable  
1 m VW3 A1 104 R10  
5 m VW3 A1 104 R50  
10 m VW3 A1 104 R100  
Note: The graphic display terminal catalog number is VW3 A1 101.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Determining catalog numbers  
1. 5. Selecting I/O extension cards (VW3A58201, VW3A58202)  
1. 5. 1. ATV38 and I/O option cards (VW3A58201, VW3A58202)  
Required information: Connection diagram, presence of an I/O extension card  
As standard the ATV 61 has more I/O than the ATV38.  
If the ATV38 is not equipped with an I/O extension card, there is no need to add a card to the Altivar 61. Ignore this section.  
• If the ATV38 is equipped with an I/O extension card, it is important to know which inputs/outputs are used as well as the function assigned  
to AI3 (VW3A58201 card) and to encoder input A, A, B, B (VW3A58201 card).  
The tables below can be used to ascertain what was used previously and, therefore, to find the equivalent on ATV 61 with or without an  
option card.  
Scenario 1: Replacing an ATV38 with or without a VW3A58201 option card:  
Used:  
Becomes:  
ATV 61  
ATV38  
Description  
VW3A58201  
VW3 A3 201 VW3 A3 202  
Description  
R1A/R1B/  
R1C  
R1A/R1B/  
R1C  
Fault relay (R1)  
COM  
0 V  
0 V  
Common  
R3A/R3B/  
R3C  
R4A/R4B/  
R4C  
R2A/R2C  
R2A/R2C  
Programmable relay (R2)  
Programmable relay  
AO 1  
COM  
AI 1  
AO 1  
COM  
AI 1+  
0-20 mA analog output  
Analog input common  
0…10 V analog input  
-10  
-10  
-10  
-10 V output  
PTC probe  
PTC probe  
TH1+  
TH1-  
TH2+  
TH2-  
1 to 10 kΩ potentiometer  
+10  
AI 2  
LI 1  
LI 2  
LI 3  
+10  
AI 2  
LI 1  
LI 2  
LI 3  
+24  
+24  
LI 7  
LI 8  
LI 9  
LI10  
+24  
Logic input power supply  
power supply  
Analog input  
0…10 V 0..4/20 mA  
LI 5 also on  
control card  
24 V DC programmable  
logic input  
LI 11  
LI 12  
LI 13  
LI 14  
24 V DC run forward logic  
inputs  
LI 6 also on  
control card  
24 V DC programmable  
logic input  
24 V DC programmable  
logic input  
24 V DC programmable  
logic input  
24 V DC programmable  
logic input  
24 V DC programmable  
logic input  
24 V DC programmable  
logic input  
LI 4  
+24  
LI 4  
+24  
LI 5  
LO  
LO 1  
LO 2  
CLO  
LO 3  
LO 4  
CLO  
Logic output  
Logic output  
Logic input power supply  
24 V DC programmable  
logic input  
LO +  
Logic output power supply  
24 V DC programmable  
logic input  
AI 3A/AI3 B  
Current  
AI3 +/AI3 -  
LI 6  
Programmable analog input  
Programmable analog input  
g
AI4  
Programmable analog  
output  
AO  
AO 2  
Programmable analog  
output  
AO 3  
FP  
+10  
+10 V output  
Pulse input  
g Review of the various instances of use of the AI3 input on the VW3A58201 card:  
AI3 assignment  
PTC  
Use LI6 on ATV 61 control card in PTC mode and adjust SW2 (see page xx)  
Use the TH inputs on the VW3 A3 201 or VW3 A3 202 option cards (see page xx)  
Speed reference  
Two different options  
ATV38  
ATV 61  
AI3 (0..10 V)  
AI3 (+/- 10 V)  
AI1 or AI2 if available  
AI1  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Determining catalog numbers  
PI feedback or summed reference: Three different options  
ATV38  
ATV 61  
AI3 (0..10 V)  
AI1 or AI2 if available  
AI4 on VW3 A3 202 option card  
AI1  
AI3 (+/- 10 V)  
Tachometer: Totally incompatible. Alternative solution: use an incremental encoder.  
Scenario 2: Replacing an ATV38 with or without a VW3A58202 option card:  
Used:  
Becomes:  
ATV 61  
VW3... card  
A3 202  
ATV38  
Description  
VW3A58202  
Description  
Common  
A3 201  
A3 407  
R1A/R1B/  
R1C  
R1A/R1B/  
R1C  
Fault relay (R1)  
COM  
0 V  
0 V  
Programmable relay  
(R2)  
R3A/R3B/  
R3C  
R4A/R4B/  
R4C  
R2A/R2C  
AO 1  
R2A/R2C  
AO 1  
Programmable relay  
-10 V output  
0-20 mA  
-10  
-10  
-10  
analog output  
Analog input common  
0…10 V analog input  
1 to 10 kΩ  
potentiometer power  
supply  
COM  
AI 1  
COM  
AI 1+  
TH1+  
TH1-  
TH2+  
TH2-  
PTC probe  
PTC probe  
Logic input power  
supply  
+10  
+10  
+24  
+24  
+24  
24 V DC  
programmable logic  
input  
24 V DCprogrammable  
logic input  
0…10 V 0..4/20 mA  
analog input  
LI 5 also on  
control card  
AI 2  
LI 1  
LI 2  
AI 2  
LI 1  
LI 2  
LI 7  
LI 8  
LI 9  
LI 11  
LI 12  
LI 13  
24 V DC run forward  
logic inputs  
LI 6 also on  
control card  
24 V DC  
programmable logic  
24 V DC programmable  
logic input  
input  
24 V DC  
programmable logic  
input  
24 V DC programmable  
logic input  
LI 3  
LI 3  
LI 10  
LI 14  
24 V DC programmable  
logic input  
Logic input power  
supply  
24 V DC programmable  
logic input  
LI 4  
+24  
LI 4  
+24  
LI 5  
LI 6  
LO  
LO 1  
LO 2  
CLO  
LO 3  
LO 4  
CLO  
Logic output  
Logic output  
Logic output power  
supply  
Programmable analog  
input  
LO +  
24 V DC programmable  
logic input  
Current  
AI3 +/AI3 -  
Programmable analog  
input  
AI4  
Programmable analog  
output  
AO  
AO 2  
Programmable analog  
output  
AO 3  
FP  
Pulse input  
Incremental encoder  
input  
Incremental encoder  
input  
Incremental encoder  
input  
A
A-  
B
A
A-  
B
Incremental encoder  
input  
B-  
B-  
0 V  
PES  
Encoder 0 V  
Encoder 5 V  
Examples:  
- If only LI5 and LI6 are used on the VW3A58202 card  
ª An option card is not needed with the ATV 61 because Li5 and Li6 are features of the standard product.  
- If only the incremental encoder inputs are used on the VW3A58202 card  
ª Use the VW3 A3 407 encoder card.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Determining catalog numbers  
1. 6. Selecting communication channels  
1. 6. 1. Communication via Modbus network  
With this type of communication, there are several possible scenarios:  
1) The Altivar 38 was connected via the connector port using the RS485 connection kit (VW3A58306): The connection cable should be  
replaced because the ATV61 has an RJ45 type Modbus port, but the port on the ATV38 is a 9-way SUB-D.  
ATV38 connected to  
Catalog number  
Description  
TSXSCA50 junction box or other screw terminals  
VW3 A8 306 D30 Length 3 m, an RJ45 connector at one end and stripped at the  
other  
TSXSCA62 subscriber socket  
VW3 A8 306  
Length 3 m, an RJ45 connector at one end and a 15-way  
SUB-D connector at the other  
The integrated Modbus port does not have any pulldown resistors, but depending on the type of subscriber and the master module  
present on the bus, it may be necessary to match these pulldown resistors (see page 39).  
2) The Altivar 38 was connected via the VW3A58303 card to a Unitelway or 4-wire Modbus RTU/Jbus/ASCII network.  
The Altivar 61’s integrated Modbus port does not support these network services and it is, therefore, necessary to use an option card.  
Card catalog number  
ATV38  
ATV 61  
VW3A58303  
VW3 A3 303  
In this example, keep the existing connections.  
If the VW3A58303 card was used with the 2-wire Modbus RTU protocol, connection on the Altivar 61’s RJ45 port is possible, as  
this is compatible with the presence of the graphic display terminal. Only the diagnostic service (08) is restricted to subcodes 00,  
0A, 0C, 0E. Use the connection method described in Point 1.  
1. 6. 2. Communication with Profibus bus (VW3A58307)  
Card catalog number  
ATV38  
ATV 61  
VW3A58307  
VW3 A3 307  
Installation and connection  
For the Altivar 61, keep the existing connections.  
1. 6. 3. Communication with DeviceNet bus (VW3A58309)  
Card catalog number  
ATV38  
ATV 61  
VW3A58309  
VW3 A3 309  
Installation and connection  
For the Altivar 61, keep the existing connections.  
1. 6. 4. Communication via Modbus Plus bus (VW3A58302)  
Card catalog number  
ATV38  
ATV 61  
VW3A58302  
VW3 A3 302  
Installation and connection  
For the Altivar 61, keep the existing connections.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Determining catalog numbers  
1. 6. 5. Communication with Metasys N2 bus VW3A58354U  
Card catalog number  
ATV38  
ATV 61  
VW3A58354U  
VW3 A3 313  
1. 6. 6. Communication with INTERBUS bus (VW3A58304(E))  
Card catalog number  
ATV38  
ATV 61  
VW3A58304  
VW3A58304E  
VW3 A3 304  
VW3 A3 304  
Installation and connection  
For the Altivar 61, keep the existing connections.  
It is essential to use the Altivar 61 control card’s external power supply function so that the bus token can circulate continuously (see  
page 26).  
1. 6. 7. Communication via Ethernet network (VW3A58310)  
Card catalog number  
ATV38  
ATV 61  
VW3A58310  
VW3 A3 310  
Installation and connection  
For the Altivar 61, keep the existing connections.  
1. 6. 8. Communication via Fipio bus VW3A58311  
Card catalog number  
ATV38  
ATV 61  
VW3A58311  
VW3 A3 311  
Installation and connection  
If a TSX FP ACC12 connector is used to link the Altivar to the bus, keep the existing connections. However, it is necessary to alter the  
position of the cable(s) when using a TSX FP ACC2 connector (see page 47).  
1. 6. 9. Communication via CANopen bus (VW3A58308)  
Card catalog number  
The Altivar 61 integrates the ATV38 CANopen communication card’s connection and services as standard (VW3A58308).  
It is however necessary to modify the wiring.  
ATV38  
ATV 61  
Screw terminals  
9-way Sub-D  
To adapt the wiring, order:  
- 9-way Sub-D connector (1 per drive): VW3 CAN KCDF 180T  
- 9-way Sub-D/RJ45 adapter (1 per drive): VW3 CAN A71  
1. 6. 10. Communication via AS-i bus (VW3A58305)  
Card catalog number  
Although the AS-i communication card has not been continued in the Altivar 61 offer, there is a solution for substitution using a 4-input/  
4-output module on the AS-i bus.  
ATV38  
ATV 61  
VW3A58305  
ASI 20M T4I4OS  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Drive implementation  
2. 1. Installation  
2. 1. 1. Using catalog numbers starting with ATV38H  
The dimensions given in the following sections can be used to compare those of an Altivar 38 equipped with an option card and its operator  
terminal with an Altivar 61 also equipped with an option card and operator terminal.  
These tables only include examples where the Altivar 61 takes up more space than the Altivar 38, as well as the proposed solutions.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
2. 1. 1. 1. Three-phase supply 380…480 V (for catalog numbers starting with ATV38H)  
Comparison of dimensions  
Width (1)  
150  
Height (2)  
226  
Depth (3)  
184  
ATV38HU18N4  
ATV 61H075N4  
130  
230  
195  
ATV38HU29N4  
150  
130  
226  
230  
184  
195  
ATV 61HU15N4  
ATV38HU41N4  
150  
130  
226  
230  
184  
195  
ATV 61HU22N4  
ATV38HU54N4  
175  
155  
285  
260  
184  
207  
ATV 61HU22N4  
ATV38HU72N4  
175  
155  
285  
260  
184  
207  
ATV 61HU40N4  
ATV38HU90N4  
175  
175  
285  
295  
184  
207  
ATV 61HU55N4  
ATV38HD12N4  
230  
175  
325  
295  
210  
187  
ATV 61HU75N4  
ATV38HD16N4  
230  
210  
325  
295  
210  
213  
ATV 61HD11N4  
ATV38HD23N4  
230  
230  
415  
400  
210  
213  
ATV 61HD15N4  
ATV38HD28N4 (X)  
240  
230  
550  
400  
283  
213  
ATV 61HD15N4  
ATV38HD25N4 (X)  
240  
230  
550  
400  
283  
213  
ATV 61HD18N4  
ATV38HD33N4 (X)  
240  
240  
550  
550  
283  
266  
ATV 61HD30N4  
ATV38HD46N4 (X)  
240  
240  
550  
550  
283  
266  
ATV 61HD37N4  
(1) No problem if space is left between 2 drives. Width incompatible if the ATV38 drives are mounted side by side.  
(2) This difference is easily made up by the space required for the drive wiring.  
(3) The depth of enclosures is usually considerably greater than that of the products.  
If the enclosure depth poses a problem, it is always possible to order an Altivar 61 with a Z at the end of the catalog number. Your drive will  
be supplied without a graphic display terminal and will, therefore, be 23 mm slimmer, e.g., ATV 61H075N4Z.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. 1. 1. 2. Three-phase supply 380…480 V for catalog numbers starting with ATV38H.  
Comparison of dimensions  
Width (1)  
Height (2)  
Depth (3)  
ATV38HD54N4 (X)  
350  
320  
650  
630  
304  
290  
ATV 61HD45N4  
ATV38H64N4(X)  
350  
320  
650  
630  
304  
290  
ATV 61HD55N4  
ATV38HD79N4 (X)  
350  
320  
650  
630  
304  
290  
ATV 61HD75N4  
ATV38HC10N4 (X)  
370  
320  
630  
920  
360  
377  
ATV 61HD90N4  
ATV38HC13N4 (X)  
480  
320  
680  
920  
400  
377  
ATV 61HC11N4  
ATV38HC15N4 (X)  
480  
360  
680  
400  
377  
ATV 61HC13N4  
1022  
ATV38HC19N4 (X)  
480  
340  
680  
400  
377  
ATV 61HC16N4  
1190  
ATV38HC23N4 (X)  
660  
440  
950  
440  
377  
ATV 61HC22N4  
1190  
ATV38HC25N4 (X)  
660  
440  
950  
440  
377  
ATV 61HC22N4  
1190  
ATV38HC28N4 (X)  
660  
440  
950  
440  
377  
ATV 61HC25N4  
1190  
ATV38HC31N4 (X)  
660  
440  
950  
440  
377  
ATV 61HC31N4  
1190  
ATV38HC33N4 (X)  
660  
440  
950  
440  
377  
ATV 61HC31N4  
1190  
(1) No problem if space is left between 2 drives. Width incompatible if the ATV38 drives are mounted side by side.  
(2) This difference is easily made up by the space required for the drive wiring.  
(3) The depth of enclosures is usually considerably greater than that of the products.  
If the enclosure depth poses a problem, it is always possible to order an Altivar 61 with a Z at the end of the catalog number. Your drive will  
be supplied without a graphic display terminal and will, therefore, be 23 mm slimmer, e.g., ATV 61H075N4Z.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. 2. Comparison of dimensions  
2. 2. 1. Dimensions  
ATV38Hppp product on heatsink  
c
=
G
a
=
ATV-38H  
a
b
c
G
H
Ø
U18N4, U29N4, U41N4  
U54N4, U72N4, U90N4  
D12N4, D16N4  
150  
175  
230  
230  
240  
350  
230  
286  
325  
415  
550  
650  
184  
184  
210  
210  
283  
304  
133  
155  
200  
200  
205  
300  
210  
270  
310  
400  
530  
619  
5
5.5  
5.5  
5.5  
7
D23N4  
D25N4p, D28N4p, D33N4p, D46N4p  
D54N4p, D64N4p, D79N4p  
9
ATV 61Hppp y 15 kW without graphic display terminal, with and without option cards  
No option card  
With 2 option cards  
With 1 option card  
4 x  
=
G
a
c
=
c2  
c1  
ATV 61H  
a
mm  
(in.)  
b
mm  
(in.)  
c
mm  
(in.)  
c1  
mm  
(in.)  
c2  
mm  
(in.)  
G
mm  
(in.)  
H
mm  
(in.)  
h
mm  
(in.)  
Ø
mm  
(in.)  
For  
screws  
Weight  
kg  
(lb.)  
130  
230  
149  
172  
195  
113.5  
220  
5
5
M4  
M4  
M5  
M5  
M6  
3
075N4, U15N4,U22N4  
U30N4, U40N4  
U55N4, U75N4  
D11N4  
(5.12)  
(9.05) (5.87) (6.77) (7.68) (4.47) (8.66) (0.20)  
(0.20)  
(6.61)  
155  
(6.10)  
260  
161  
184  
207  
138  
249  
4
5
4
(10.23) (6.34) (7.25) (8.15) (5.43) (9.80) (0.16)  
(0.20)  
(8.82)  
175  
(6.89)  
295 161 184 207 158 283  
(11.61) (6.34) (7.25) (8.15) (6.22) (11.14) (0.24)  
295 187 210 233 190 283  
(11.61) (7.36) (8.27) (9.17) (7.48) (11.14) (0.24)  
400 187 210 233 210 386  
(15.75) (7.36) (8.27) (9.17) (8.26) (15.20) (0.31)  
6
6
5.5  
(12.13)  
(0.24)  
210  
(8.27)  
6
6
7
(0.24)  
(15.43)  
230  
(9.05)  
8
6
9
D15N4  
(0.24)  
(19.84)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ATV 61Hppp y 15 kW with graphic display terminal, with and without option cards  
No option card  
With 2 option cards (1)  
With 1 option card (1)  
4 x  
c1  
c2  
c
=
G
a
=
ATV 61H  
a
b
c
c1  
c2  
G
H
h
Ø
For Weight  
mm  
mm  
mm  
mm  
mm  
mm  
mm  
mm  
mm  
screw  
kg  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
s
(lb.)  
130  
230  
172  
195  
218  
113.5  
(4.47)  
138  
(5.43)  
220  
5
5
M4  
3
075N4, U15N4,U22N4  
U30N4, U40N4  
U55N4, U75N4  
D11N4  
(5.12)  
(9.05)  
(6.77)  
(7.68)  
(8.58)  
(8.66)  
(0.20)  
(0.20)  
(6.61)  
155  
(6.10)  
175  
(6.89)  
210  
(8.27)  
230  
(9.05)  
240  
(9.45)  
240  
(9.45)  
320  
(12.60)  
260  
(10.23)  
295  
(11.61)  
295  
(11.61)  
400  
(15.75)  
420  
(16.54)  
550  
(21.65)  
630  
(24.80)  
184  
(7.25)  
184  
(7.25)  
210  
(8.27)  
210  
(8.27)  
207  
(8.15)  
207  
(8.15)  
230  
(9.06)  
230  
(9.06)  
249  
(9.80)  
283  
4
5
M4  
M5  
M5  
M6  
M6  
M6  
M8  
4
(0.16)  
(0.20)  
(8.82)  
158  
6
6
5.5  
(12.13)  
(6.22) (11.14) (0.24)  
(0.24)  
233  
256  
190  
283  
6
6
7
(9.17) (10.08) (7.48) (11.14) (0.24)  
(0.24)  
(15.43)  
233  
(9.17) (10.08) (8.26) (15.20) (0.31)  
243 266 206 403 11  
(9.57) (10.47) (8.11) (15.87) (0.45)  
263 286 206 531.5 11  
256  
210  
386  
8
6
9
D15N4, D18N4  
D22N4  
(0.24)  
(19.84)  
210  
(8.27)  
240  
5.5  
(0.22)  
5.5  
(0.22)  
30  
(66.14)  
37  
(81.57)  
45  
(99.21)  
D30N4, D37N4  
D45N4, D55N4, D75N4  
(9.45) (10.35) (11.25) (8.11) (20.93) (0.45)  
290  
315  
335  
280  
604.5  
15  
9
(11.42) (12.40) (13.19) (11.02) (23.80) (0.59)  
(0.22)  
ATV 61Hppp y 75 kW with graphic display terminal, with and without option cards  
No option card  
With 2 option cards (1)  
With 1 option card (1)  
4 x  
c1  
c2  
c
=
G
a
=
ATV 61H  
a
b
c
c1  
c2  
G
H
h
Ø
For Weight  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
mm  
(in.)  
screw  
s
kg  
(lb.)  
130  
230  
172  
195  
218  
113.5  
(4.47)  
138  
(5.43)  
220  
5
5
M4  
3
075N4, U15N4,U22N4  
U30N4, U40N4  
U55N4, U75N4  
D11N4  
(5.12)  
(9.05)  
(6.77)  
(7.68)  
(8.58)  
(8.66)  
(0.20)  
(0.20)  
(6.61)  
155  
(6.10)  
175  
(6.89)  
210  
(8.27)  
230  
(9.05)  
240  
(9.45)  
240  
(9.45)  
320  
(12.60)  
260  
(10.23)  
295  
(11.61)  
295  
(11.61)  
400  
(15.75)  
420  
(16.54)  
550  
(21.65)  
630  
(24.80)  
184  
(7.25)  
184  
(7.25)  
210  
(8.27)  
210  
(8.27)  
207  
(8.15)  
207  
(8.15)  
230  
(9.06)  
230  
(9.06)  
249  
(9.80)  
283  
4
5
M4  
M5  
M5  
M6  
M6  
M6  
M8  
4
(0.16)  
(0.20)  
(8.82)  
158  
6
6
5.5  
(12.13)  
(6.22) (11.14) (0.24)  
(0.24)  
233  
256  
190  
283  
6
6
7
(9.17) (10.08) (7.48) (11.14) (0.24)  
(0.24)  
(15.43)  
233  
(9.17) (10.08) (8.26) (15.20) (0.31)  
243 266 206 403 11  
(9.57) (10.47) (8.11) (15.87) (0.45)  
263 286 206 531.5 11  
256  
210  
386  
8
6
9
D15N4, D18N4  
D22N4  
(0.24)  
(19.84)  
210  
(8.27)  
240  
5.5  
(0.22)  
5.5  
(0.22)  
30  
(66.14)  
37  
(81.57)  
45  
(99.21)  
D30N4, D37N4  
D45N4, D55N4, D75N4  
(9.45) (10.35) (11.25) (8.11) (20.93) (0.45)  
290  
315  
335  
280  
604.5  
15  
9
(11.42) (12.40) (13.19) (11.02) (23.80) (0.59)  
(0.22)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATV 38Hppp > 75 kW and y 315 kW - Product on heatsink  
G
a
=
=
c
ATV 61H  
C10N4X  
a
mm  
(in.)  
370  
(14.57)  
b
mm  
(in.)  
630  
(24.80)  
c
mm  
(in.)  
360  
(14.17)  
G
mm  
(in.)  
317.5  
(12.50)  
H
mm  
(in.)  
609  
(23.98)  
Ø
mm  
(in.)  
12  
(0.47)  
480  
(18.90)  
680  
(26.77)  
400  
(15.75)  
426  
(16.77)  
652  
(25.67)  
12  
(0.47)  
C13N4X, C15N4X, C19N4X  
660  
(25.98)  
950  
(37.40)  
440  
(17.32)  
598  
(23.54)  
920  
(36.22)  
15  
(0.59)  
C23N4X, C25N4X, C28N4X,  
C31N4X, C33N4X  
ATV 61Hppp > 75 kW and y 315 kW with graphic display terminal, with and without option cards  
ATV61H D55M3X to D90M3X  
ATV61H D90N4 to C31N4  
With 0 or 1 option card (1)  
With 2 option cards (1)  
ATV61H C25N4 to C31N4 with braking unit  
a
670 (26.37)  
540 mm (21.26 in)  
377 mm  
392 mm  
=
G
=
ATV61H  
a
mm  
b
mm  
G
mm  
H
mm  
K
mm  
K1  
mm  
K2  
mm  
Ø
mm  
For  
screws  
Weight  
kg  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(in.)  
(lb.)  
C13N4  
C16N4  
C22N4  
C25N4  
C31N4  
360  
(14.17)  
1022  
(40.23)  
298  
(11.73)  
758  
(29.84)  
150  
(5.91)  
72  
(2.83)  
30  
(1.18)  
11.5  
(0.45)  
M10  
M10  
M10  
80  
(176)  
340  
(13.39)  
1190  
(46.62)  
285  
(11.22)  
920  
(36.22)  
150  
(5.91)  
75  
(2.95)  
30  
(1.18)  
11.5  
(0.45)  
110  
(242)  
440  
(17.32)  
1190  
(46.62)  
350  
(13.78)  
920  
(36.22)  
150  
(5.91)  
75  
(2.95)  
30  
(1.18)  
11.5  
(0.45)  
140  
(309)  
140  
(309)  
595  
(23.43)  
1190  
(46.62)  
540  
(21.26)  
920  
(36.22)  
150  
(5.91)  
75  
(2.95)  
30  
(1.18)  
11.5  
(0.45)  
M10  
215  
(474)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. 3. Mounting the RFI filter  
The dimensions given in the following sections can be used to compare the dimensions of the Altivar 38 RFI filters with those used on the  
Altivar 61.  
These tables only include examples where the Altivar 61 filters take up more space than those fitted on the Altivar 38, as well as the  
proposed solutions.  
It is important to remember that, without exception, it will be necessary to adapt the mounting as the mounting dimensions are not the same.  
2. 3. 0. 1. Three-phase supply 400 V for catalog numbers starting with ATV38H  
Width  
a
Height  
b
Depth  
c
Mounting  
Drive  
Filter  
G
H
ATV38HU18N4  
ATV 61H075N4  
VW3A58402  
VW3 A4 401  
150  
130  
276  
290  
60  
40  
133  
105  
260  
260  
ATV38HU29N4  
ATV 61HU15N4  
VW3A58402  
VW3 A4 401  
150  
130  
276  
290  
60  
40  
133  
105  
260  
260  
ATV38HU41N4  
ATV 61HU22N4  
VW3A58402  
VW3 A4 401  
150  
130  
276  
290  
60  
40  
133  
105  
260  
260  
ATV38HU90N4  
ATV 61HU55N4  
VW3A58403  
VW3 A4 403  
175  
175  
340  
370  
60  
60  
153  
150  
320  
355  
ATV38HD23N4  
ATV 61HD15N4  
VW3A58405  
VW3 A4 405  
230  
230  
480  
498.5  
60  
62  
200  
190  
460  
460  
ATV38HD54N4 (X)  
ATV 61HD45N4  
VW3A58408  
VW3 A4 408  
350  
320  
770  
750  
110  
119  
300  
280  
770  
725  
ATV38HD64N4 (X)  
ATV 61HD45N4  
VW3A58408  
VW3 A4 408  
350  
320  
770  
750  
110  
119  
300  
280  
770  
725  
ATV38HD79N4 (X)  
ATV 61HD55N4  
VW3A58408  
VW3 A4 408  
350  
320  
770  
750  
110  
119  
300  
280  
770  
725  
ATV38HC10N4 (X)  
ATV 61HD90N4  
VW3A68401  
VW3 A4 410  
204  
800  
243  
261  
88  
139  
90  
120  
80  
235  
ATV38HC13N4 (X)  
ATV 61HC11N4  
VW3A68402  
VW3 A4 410  
204  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC15N4 (X)  
ATV 61HC13N4  
VW3A68402  
VW3 A4 410  
204  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC19N4 (X)  
ATV 61HC16N4  
VW3A68402  
VW3 A4 410  
204  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC23N4 (X)  
ATV 61HC22N4  
VW3A68403  
VW3 A4 411  
224  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC25N4 (X)  
ATV 61HC22N4  
VW3A68403  
VW3 A4 411  
224  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC28N4 (X)  
ATV 61HC25N4  
VW3A68403  
VW3 A4 411  
224  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC31N4 (X)  
ATV 61HC31N4  
VW3A68403  
VW3 A4 411  
224  
800  
295  
261  
89  
139  
90  
120  
90  
235  
ATV38HC33N4 (X)  
ATV 61HC31N4  
VW3A68403  
VW3 A4 411  
224  
800  
295  
261  
89  
139  
90  
120  
90  
235  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2. 3. 0. 2. Three-phase supply 400…460 V for catalog numbers starting with ATV38H  
Width  
a
Height  
b
Depth  
c
Mounting  
Drive  
Filter  
G
H
ATV38HC10N4 (X)  
VW3A68415  
VW3 A4 410  
260  
800  
386  
261  
115  
139  
235  
120  
240  
235  
ATV 61HD90N4  
ATV38HC13N4 (X)  
VW3A68435  
VW3 A4 410  
260  
800  
386  
261  
115  
139  
235  
120  
240  
235  
ATV 61HC11N4  
ATV38HC15N4 (X)  
VW3A68435  
VW3 A4 410  
260  
800  
386  
261  
115  
139  
235  
120  
240  
235  
ATV 61HC13N4  
ATV38HC19N4 (X)  
VW3A68435  
VW3 A4 410  
260  
800  
386  
261  
115  
139  
235  
120  
240  
235  
ATV 61HC16N4  
ATV38HC23N4 (X)  
VW3A68465  
VW3 A4 411  
260  
800  
386  
261  
135  
139  
235  
120  
240  
235  
ATV 61HC22N4  
ATV38HC25N4 (X)  
VW3A68465  
VW3 A4 411  
260  
800  
386  
261  
135  
139  
235  
120  
240  
235  
ATV 61HC22N4  
ATV38HC28N4 (X)  
VW3A68465  
VW3 A4 411  
260  
800  
386  
261  
135  
139  
235  
120  
240  
235  
ATV 61HC25N4  
ATV38HC31N4 (X)  
VW3A68465  
VW3 A4 411  
260  
800  
386  
261  
135  
139  
235  
120  
240  
235  
ATV 61HC31N4  
ATV38HC33N4 (X)  
VW3A68465  
VW3 A4 411  
260  
800  
386  
261  
135  
139  
235  
120  
240  
235  
ATV 61HC31N4  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. 3. 1. Comparison of dimensions  
2. 3. 1. 1. RFI filters  
Ø
Ø
c
c
G
a
G
a
VW3  
a (mm)  
130  
b (mm)  
290  
c (mm)  
40  
G (mm)  
105  
H (mm)  
275  
H1 (mm)  
Ø (mm)  
4.5  
A4 401  
A4 402  
A4 403  
A4 404  
A4 405  
A4 409  
155  
324  
50  
130  
309  
4.5  
175  
370  
60  
150  
355  
5.5  
210  
380  
60  
190  
365  
5.5  
230  
498.5  
498.5  
62  
190  
479.5  
479.5  
460  
460  
6.6  
230  
62  
190  
6.6  
Ø
J
G
a
c
VW3  
a (mm)  
240  
b (mm)  
522  
c (mm)  
79  
G (mm)  
200  
H (mm)  
502.5  
631  
J (mm)  
40  
Ø (mm)  
6.6  
A4 406  
A4 407  
A4 408  
240  
650  
79  
200  
40  
6.6  
320  
750  
119  
280  
725  
80  
9
a1  
6xØ12  
10  
c
=
G
G
=
a
VW3  
a (mm)  
800  
a1 (mm)  
302  
b (mm)  
261  
b1 (mm)  
219  
c (mm)  
139  
G (mm)  
120  
H (mm)  
235  
A4 410  
A4 411  
800  
302  
261  
219  
139  
120  
235  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting under the drive  
4 x  
ATV 38  
ATV 61  
Side mounting against the ATV 61  
Filter  
Drive  
Filter - Drive connection  
Power connection  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. 4. NEMA mounting kits  
Dimensions, in inches and (mm)  
a
=
G
=
c
Kit  
Kit  
Kit catalog  
number  
Product  
size  
Drive catalog number  
a
(in.)  
b
(in.)  
c
(in.)  
G
(in.)  
H
(in.)  
Ø
(in.)  
d
(lb.)  
ATV38Hppppp  
VW3A58852  
VW3A58853  
VW3A58854  
VW3A58855  
2
3
4
5
U18N4, U29N4, U41N4  
U54N4, U72N4, U90N4  
D12N4, D16N4  
5.91  
9.06  
7.24  
5.20  
8.27  
0.20  
(5)  
2.81  
(71)  
(150) (230) (184) (133) (210)  
6.89 11.26 7.24  
(175) (286) (184) (155) (270) (5.5)  
9.06 12.80 8.27 7.9 12.20 0.22  
(230) (325) (210) (200) (310) (5.5)  
9.06 16.35 8.27 7.9 15.75 0.22  
(203) (415) (201) (200) (400) (5.5)  
6.10 10.63 0.22  
2.94  
(75)  
2.94  
(75)  
D23N4  
2.94  
(75)  
C
Kit  
Kit  
Kit catalog  
number  
Product  
size  
Drive catalog number  
A
(in.)  
B
(in.)  
C
(in.)  
E
(in.)  
F
(in.)  
G
(in.)  
I
K
Ø
L
ATV38Hppppp  
(in.) (in.) (in.) (lb.)  
VW3A58856  
6
D25N4, D28N4, D33N4,  
D46N4  
9.45 21.65 11.14 5.57 12.05 8.07 20.87 0.39 0.28 3.5  
(240) (550) (283) (146) (306) (205) (530) (10) (7) (89)  
VW3A58857  
7
D54N4, D64N4, D79N4  
13.78 25.59 11.97 9.29 15.35 11.81 24.37 0.39 0.36 6.75  
(350) (650) (304) (236) (390) (300) (619) (10) (9) (171)  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Kit for UL NEMA Type 1 conformity or IP 21 protection  
VW3 A9 ppp  
Drive  
VW3 A9 xxxxx kit  
VW3 A9 101…105, 201…205  
VW3 A9 106…108, 206…208  
a
a
VW3  
a (in.)  
b (in.)  
VW3  
a (in.)  
b (in.)  
A9 101, 201 130 (5.12) 113 (4.45)  
A9 102, 202 155 (6.10) 103 (4.06)  
A9 103, 203 175 (6.89) 113 (4.45)  
A9 104, 204 210 (8.27) 113 (4.45)  
A9 105, 205 230 (9.06) 108 (4.25)  
A9 106, 206  
A9 107, 207  
240 (9.45) 185 (7.28)  
240 (9.45) 180 (7.09)  
A9 108, 208 320 (12.60) 178 (7.01)  
VW3 A9 109…116, VW3 A9 209  
4xØ  
c
=
G
a
=
VW3  
a (in.)  
b (in.)  
c (in.)  
G (in.)  
K (in.)  
K1 (in.)  
K2 (in.)  
Ø (in.)  
A9 109, 209 320 (12.60) 220 (8.66) 377 (14.84) 250 (9.84) 95 (3.74) 65 (2.56)  
75 (2.95) 11.5 (0.45)  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. 5. Separate control card power supply  
This type of wiring is essential when using a VW3 A3 304 Interbus-S communication option card.  
A1  
ATV61Hppppp  
0V  
P24  
0 V  
+24 V  
2. 6. Remote display terminal  
Used to connect the programming terminal remotely on the front of the enclosure.  
Fixings:  
As the dimensions are not the same, the fixing holes must be modified.  
ATV38  
ATV 61  
55,6 mm  
24 mm  
115 mm (4.53 in)  
104 mm (4.09 in)  
4 x 3,5 mm  
36 mm  
4
F
3
F
2
F
1
F
C
S
E
P
O
ST  
RESET  
D
FW  
REV  
N
U
R
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
2. 7. Power cables  
The layout and type of power terminals have changed:  
Ring terminals must be used rather than ferrules for the ground terminals, although for the power terminals the ferrules used previously can  
be retained if they are in good condition (a flattened ferrule will not make a good connection).  
Table of correspondence for power terminals  
ATV38  
L1  
L2  
L3  
+
ATV 61  
R/L1  
S/L2  
T/L3  
PO  
Power supply  
DC bus  
-
PC/-  
PA/+  
PB  
Braking resistor  
Motor output  
PA  
PB  
U
U/T1  
V/T2  
W/T3  
V
W
Connecting to the Altivar 38  
Connecting to the Altivar 61  
A1  
A1  
ATV71HpppM3  
ATV58pppppp  
M
3 a  
M
3 a  
Braking resistor  
(if used)  
Braking resistor  
(if used)  
Disconnecting the RFI filter if using an IT system  
IT system: Isolated or impedance grounded neutral.  
Use a permanent insulation monitor compatible with non-linear loads, such as a  
Merlin Gerin type XM200 or equivalent.  
Normal  
(filter connected)  
Altivar 61 drives feature built-in RFI filters. These filters can be isolated from ground for  
operation on an IT system as follows:  
Remove the jumper located to the left of the power terminals  
IT system  
(filter disconnected)  
Layout of the ATV38 power terminals  
t
t
t
L1 L2 L3  
L1 L2 L3  
U
V
W
U
t
ATV-38HD18N4 to D23N4  
+
-
V
W
t
ATV-38HD25N4(X) to D79N4(X)  
ATV-38HC10N4(X)  
+
+
-
t
L1 L2 L3  
U
V
W
L1 L2 L3  
t
t
ATV-38H13N4(X) to C15N4(X)  
ATV-38HC23N4(X) to C33N4(X)  
+
-
U
U
V
V
W
W
L1 L2 L3  
-
t
t
+
+
Do not use  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Characteristics of the ATV38 power terminals  
Maximum wire size  
Tightening torque  
in Nm  
ATV 38 E rating  
2
AWG  
D05N4, D07N4, D09N4, AWG 8  
D12N4, D16N4, D23N4 AWG 6  
mm  
6
0.75  
2
10  
16  
35  
70  
D25N4, D28N4  
D33N4, D46N4  
AWG 4  
AWG 2  
3
4
D54N4, D64N4, D79N4 AWG 2/0  
10  
Layout of the ATV 61 power terminals and tightening torque  
For ATV 61pppppp drives  
ATV 61H  
Maximum wire Tightening  
size  
torque  
mm²  
AWG  
Nm  
(lb.in)  
075N4, U15N4, U22N4  
U30N4, U40N4  
1.2  
(10.6)  
2,5  
6
14  
8
1.2  
(10.6)  
PO PA/+ PB  
R/L1 S/L2 T/L3  
PC/-  
U/T1 V/T2 W/T3  
For ATV 61pppppp drives  
ATV 61H  
Maximum wire Tightening  
size  
torque  
mm²  
AWG  
Nm  
(lb.in)  
U55N4, U75N4  
D11N4  
2
10  
16  
35  
6
4
1
(17.7)  
2,4  
(21)  
D15N4, D18N4  
2,4  
(21)  
R/L1 S/L2 T/L3  
U/T1 V/T2 W/T3  
PO PA/+ PB  
PC/-  
For ATV 61pppppp drives  
ATV 61H  
Maximum wire Tightening  
size  
torque  
mm²  
50  
AWG  
Nm  
(lb.in)  
D22N4, D30N4, D37N4  
ATV 61H  
6
(53)  
1/0  
Maximum wire Tightening  
size  
torque  
mm² kcmils  
Nm  
(lb.in)  
D45N4, D55N4, D75N4  
19  
(168)  
120  
350  
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3  
PO PA/+ PB  
PC/-  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Layout of the ATV 61 power terminals and tightening torque  
ATV61H D55M3X, D75M3X, D90N4, C11N4  
Front view  
70 (2.74)  
60 (2.35)  
View from above  
5 (0.2)  
M12  
PO  
PA/+ PC/-  
View from below  
M10  
M8  
M10  
M10  
57(2.23)  
38 (1.49)  
60(2.35)  
32 (1.25)  
U/T1 V/T2 W/T3  
R/L1 S/L2 T/L3  
85(3.33)  
105(4.11)  
PA  
PB  
50 (1.96)  
Maximum terminal wire size/tightening torque  
Drive terminals  
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3  
PC/-, PO, PA/+  
PA, PB  
2
2
2
2 x 100 mm /24 Nm  
2 x 100 mm /41Nm  
60 mm /12 Nm  
2 x 250 MCM/212 lb.in  
2 x 250 MCM/360 lb.in  
250 MCM/106 lb.in  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATV61H D90M3X, C13N4  
Front view  
67 (2.62)  
149(5.84)  
5 (0.2)  
View from above  
M12  
PO PA/+ PC/-  
View from below  
Fan terminals  
(1)  
M10  
M8  
M10  
M10  
62 (2.43)  
38 (1.49)  
60 (2.35)  
27 (1.06)  
U/T1 V/T2 W/T3  
55,5 (2.17)  
R/L1 S/L2 T/L3  
PA PB  
79,5 (3.11)  
217 (8.50)  
Maximum terminal wire size/tightening torque  
Drive terminals  
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3  
PC/-, PO, PA/+  
PA, PB  
RO, SO, TO  
(1)  
2
2
2
2
2 x 100 mm /24Nm  
2 x 150 mm /41 Nm  
60 mm /12 Nm  
5.5 mm /1.4 Nm  
2 x 250 MCM/212 lb.in  
2 x 250 MCM/360 lb.in  
250 MCM/106 lb.in  
AWG 10/12 lb.in  
(1)Power supply for the fans, compulsory if the drive is only powered by the DC bus. Do not use if the drive is powered with a 3-phase  
supply by L1/R, L2/S, L3/T.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATV61HC16N4  
Front view  
View from above  
80 (3.13) 56 (2.19) 58 (2.28)  
M12  
PO PA/+ PC/-  
Fan terminals  
(1)  
View from below  
M10  
M10  
M10  
M8  
18 (0.71)  
43 (1.68)  
75 (2.94)  
U/T1 V/T2 W/T3  
R/L1 S/L2 T/L3  
75 (2.94)  
257 (10.07)  
80 (3.13)  
PA PB  
38 (1.49)  
Maximum terminal wire size/tightening torque  
Drive terminals  
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3  
PC/-, PO, PA/+  
PA, PB  
RO, SO, TO  
(1)  
2
2
2
2
2 x 120 mm /24 Nm  
2 x 120 mm /41 Nm  
2 x 250 MCM/360 lb.in  
120 mm /24 Nm  
5.5 mm /1.4 Nm  
2 x 250 MCM/212 lb.in  
250 MCM/212 lb.in  
AWG 10/12 lb.in  
(1)Power supply for the fans, compulsory if the drive is only powered by the DC bus. Do not use if the drive is powered with a 3-phase  
supply by L1/R, L2/S, L3/T.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATV61HC22N4  
Front view  
View from above  
100 (3.92)  
150 (5.88)  
47 (1.84)  
M12  
PO PA/+ PC/-  
Fan terminals  
(1)  
View from below  
M12  
M12  
M8  
M12  
114 (4.47)  
104 (4.07)  
102 (4.00)  
102 (4.00)  
U/T1 V/T2 W/T3  
21 (0.82)  
74 (2.90)  
R/L1 S/L2 T/L3 PA PB  
102 (4.00)  
357 (13.99)  
38 (1.49)  
Maximum terminal wire size/tightening torque  
Drive terminals  
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3  
PC/-, PO, PA/+  
PA, PB  
RO, SO, TO  
(1)  
2
2
2
2
2 x 150 mm /41 Nm  
2 x 150 mm /41 Nm  
120 mm /24 Nm  
5.5 mm /1.4 Nm  
2 x 350 MCM/360 lb.in  
2 x 350 MCM/360 lb.in  
250 MCM/212 lb.in  
AWG 10/12 lb.in  
Power supply for the fans, compulsory if the drive is only powered by the DC bus. Do not use if the drive is powered with a 3-phase supply  
by L1/R, L2/S, L3/T.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATV61H C25N4, C31N4  
Front view  
87 (3.41)  
100 (3.92)  
112 (4.39)  
View from above  
2 x M12  
PO PA/+ PC/-  
Fan terminals  
(1)  
View from below  
M12  
M12  
M12  
36 (1.41)  
43 (1.67)  
U/T1 V/T2 W/T3  
R/L1 S/L2 T/L3  
113,5 (4.45)  
173,5 (68.01)  
175 (6.85)  
176,5 (69.19)  
175 (6.85)  
130 (5.09)  
175 (6.85)  
Maximum terminal wire size/tightening torque  
Drive terminals  
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3  
PC/-, PO, PA/+  
RO, SO, TO  
(1)  
2
2
2
4 x 185 mm /41 Nm  
4 x 185 mm /41 Nm  
5.5 mm /1.4 Nm  
AWG 10/12 lb.in  
3 x 350 MCM/360 lb.in  
3 x 350 MCM/360 lb.in  
(1)Power supply for the fans, compulsory if the drive is only powered by the DC bus. Do not use if the drive is powered with a 3-phase  
supply by L1/R, L2/S, L3/T.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control wiring and I/O characteristics  
(Warning: Check the I/O assignment made by PowerSuite)  
In order to ensure that the Altivar 61 works correctly, the following rules must be adhered to:  
• Check that the SW1 switch on the Altivar 61 and the SW3 and SW4 switches on the option cards are in "Source" position.  
Source  
Int  
Source  
Ext  
SW1  
SW2  
Sink  
Sink  
SW3  
Int  
Ext  
VW3 A3 201  
RJ45  
Source  
Ext  
SW4  
Sink  
Int  
VW3 A3 202  
• Check that the strap is present between +24 and PWR.  
ATV71HpppM3  
• The PTC probes connected on an ATV 61 correspond to market standards. Please note that the values are slightly different. Check that  
the trip thresholds are suitable for the temperature levels supported by the motor.  
ATV38 value (kOhms)  
ATV 61 value (kOhms)  
Probe short-circuit  
Reset  
0.200  
1.5  
2
< 0.05  
1.8  
Overheating  
Probe break  
3
20  
> 100  
In PTC mode, Li6 is only taken into account after a Power on.  
Control and option card logic input wiring  
Control card connection diagram  
A1  
ATV71Hppppp  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection diagram for logic I/O option card (VW3 A3 201)  
A1  
VW3A3201  
Motor  
Connection diagram for extended I/O option card (VW3 A3 202)  
A1  
VW3A3202  
Source  
0-20 mA  
4-20 mA  
X-Y mA  
Motor  
0 ± 10 V  
or  
X-Y mA  
AI1 input on the ATV 61 wired as non differential 0-10 V (same as AI1 on the ATV38)  
Reference  
potentiometer  
X-Y mA  
Reference  
potentiometer  
ATV 38  
ATV61  
LI6 wired as PTC probe  
A1  
ATV61Hppppp  
Motor  
SW2  
PTC  
LI  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring the VW3 A3 401 option card encoder input when replacing an ATV38  
On the Altivar 38, encoder signals A A- or B B- had to be reversed in order to avoid the motor rotating in the wrong direction. This anomaly  
has been corrected on the Altivar 61 and, therefore, the wiring conforms to the signal order A A- B B-.  
ATV38  
OR  
0 V  
5 V  
0 V  
5 V  
Encoder  
Encoder  
ATV 61  
VW3 A3 40p  
Encoder  
The encoder card’s connector does not have a terminal for connecting the cable shielding.  
This shielding must, therefore, be connected to the power terminals; use a tag connector or an accessory: D23 FA3.  
R/L1 S/L2 T/L3  
U/T1 V/T2 W/T3  
PO PA/+ PB  
PC/-  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the Altivar 61 communication option cards  
3. 1. General  
Acceptance  
Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.  
Remove the option card from its packaging and check that it has not been damaged in transit.  
Check that the drive is turned off.  
Check that there is no voltage on the DC bus: Red LED (POWER) off, wait for 3 minutes  
after turning off the drive.  
ATV 61 075N4 to D18N4  
ATV 61H D22N4 to C31N4  
Red LED indicating that  
the DC bus is turned on.  
Installing the communication option card  
See Installation Manual pages 16 and 17.  
When migrating an Altivar 38 installation to Altivar 61, the PowerSuite v2.40 program must be used to configure the ATV61 in 8 serie mode  
in order to ensure absolute consistency of the communication, drive and adjustment parameters between the two drive ranges.  
However, for some communications options, one or more of the microswitches on the card have to be toggled manually.  
The connector for connecting the option card to the communication bus is not the same on the Altivar 61. This is now on the top right-hand  
side of the drive.  
You should, therefore, make sure that the cable(s) is(are) long enough to make this connection.  
If necessary, you should do one of the following:  
- Reconnect the wiring up and/or downstream of the drive  
- Adjust the drive position  
- Use an extension cable  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
3. Implementation of the communication option cards  
Option card fault  
The [internal com. link] (ILF-) fault appears when the following serious problems occur:  
- Hardware fault on the option card  
- Dialog fault between the option card and the drive  
The [Internal link fault 1] (ILF1) diagnostic parameter can be used to obtain more detailed information about the origin of the last  
[internal com. link] (ILF) fault:  
This parameter can be accessed on the graphic display terminal only, in the [1.10 DIAGNOSTICS] (DGt-) menu, [MORE FAULT  
INFO] (AFI-).  
Value Description of parameter values  
Value Description of parameter values  
0
1
2
3
4
5
6
7
No fault  
8
Faulty analog input  
Loss of internal communication with the drive  
Hardware fault detected  
Error in the EEPROM checksum  
Faulty EEPROM  
9
Faulty analog output  
10  
Faulty logic input  
11  
Faulty logic output  
101  
102  
103  
Unknown card  
Faulty Flash memory  
Exchange problem on the drive internal bus  
Time out on the drive internal bus (500 ms)  
Faulty RAM memory  
Faulty NVRAM memory  
• When the External Fault function is used via a communication card, the Altivar 38 would display EPF, but the Altivar 61 now displays  
EPF2.  
• When the Fast Stop function is used via a communication card, the Altivar 38 would display RDY, but the Altivar 61 now displays FST.  
• It is essential to follow the Altivar 38 internal variables manual when the Altivar 61 is being used in 8 serie mode. If not, migration may  
not proceed smoothly.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 2. Communication via Modbus network  
3. 2. 1. Calculating the polarization resistors  
Mixed schematic  
Slaves with 4.7 kΩ polarization can be integrated into a standard schematic. Suitable polarization resistance (Rp) must be calculated.  
Schematic diagram  
Master  
T
R
5 V  
Rp  
Rp  
0 V  
D1  
120 Ω  
1 nF  
D0  
Common  
5 V  
4,7 kΩ  
4,7 kΩ  
0 V  
R
R
T
T
Slave n  
Slave 1  
rd  
Type of trunk cable  
Shielded cable with 1 twisted pair and at least a 3 conductor  
Maximum length of bus  
1000 m at 19200 bps  
Maximum number of stations (without repeater) Up to 32 stations, i.e., 31 slaves (depending on Rp and the number of 4.7 kΩ resistors)  
Maximum length of tap links  
• 20 m for a single tap link  
• 40 m divided by the number of tap links on a multiple junction box  
Bus polarization  
• One pulldown resistor at the 5 V (Rp)  
• One pulldown resistor at the Common (Rp)  
This polarization can be provided in the master.  
The value of Rp should be validated (or determined) by calculating the equivalent  
polarization (Re) according to the polarization of the master and slave stations.  
The value of Re must be between 162 Ω and 650 Ω (recommended value: 650 Ω).  
Line termination  
Common polarity  
One 120 Ω 0.25 W resistor in series with a 1 nF 10 V capacitor  
Yes (Common)  
• To calculate the polarization resistance (Rp), all station polarizations must be deemed to be connected in parallel.  
Example  
If the bus Rp polarization is 470 Ω (installed in the master) and 2 slaves have 4700 Ω polarization, the equivalent polarization is:  
1/Re = 1/470 + 1/4700 + 1/4700,  
i.e., Re = 1/(1/470 + 1/4700 + 1/4700)  
and, therefore, Re = 390 Ω  
390 Ω is greater than 162 Ω, and the schematic is correct.  
For an ideal equivalent polarization (650 Ω), Rp bus polarization can be installed so that:  
1/650 = 1/Rp + 1/4700 + 1/4700,  
i.e., Rp = 1/(1/650 - 1/4700 - 1/4700)  
and, therefore, Rp = 587 Ω.  
• If the master has 470 Ω polarization, up to 18 slaves with 4.7 kΩ polarization can be connected.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 2. 2. Reminder of the various connection methods:  
ATV 61 RJ45 connector on TSXSCA50 or other screw terminals: Use cable VW3 A8 306 D30 (RJ45 to stripped end, 3 meters)  
t
2 = 0 V - brown  
3 = D_B - blue  
0VL 0VL D(A) D(B)  
2 = 0 V  
4 = D_A  
5 = D_B  
1
2
3
4
5
5 = D_A - white/blue  
8........................1  
ATV 61 RJ45 connector on TSXSCA62: Use cable VW3 A8 306 (RJ45 to 15-way Sub-D)  
2 = 0 V - brown  
15 = 0 V  
14 = D_A  
7 = D_B  
7
1
2
3
4
5
6
8
3 = D_B - blue  
9
10 11 12 13 14 15  
5 = D_A - white/blue  
8........................1  
3. 2. 2. 1. Configuring the drive  
There are two possible scenarios.  
Scenario 1 Using the built-in port when replacing the VW3A58303 Modbus/Unitelway option card  
As the PowerSuite software workshop is not able to anticipate this scenario, the communication, address and protocol-format parameters  
must be entered manually:  
Configuring the address  
Transfer the Altivar 38 parameters to the Altivar 61 using the integrated display terminal, the graphic display terminal or the PowerSuite  
software workshop:  
The configuration of the Modbus network parameters can be accessed via the [MODBUS NETWORK] (Md I-) submenu in the [1.9  
- COMMUNICATION] (COM -) menu.  
Modbus parameter  
Description/Possible values  
Terminal display  
Default value  
[Modbus Address] (Add)  
1 to 247  
Drive Modbus disabled (0)  
[1] (1) to [247] (247) [Off] (OFF)  
[Modbus baud rate] (tbr) 4800 bps  
[4.8 Kbps] (4 8)  
[9.6 Kbps] (9 6)  
[19.2 Kbps] (19 2)  
[19200] (19 2)  
9600 bps  
19200 bps  
38400 bps  
[38.4 Kbps] (38 4)  
[Modbus format] (tFO)  
8 data bits, odd parity, 1 stop bit  
[8-0-1] (8o1)  
[8 E 1] (8E1)  
8 data bits, even parity, 1 stop bit  
8 data bits, no parity, 1 stop bit  
8 data bits, no parity, 2 stop bits  
[8-E-1] (8E1)  
[8-N-1] (8n1)  
[8-N-2] (8n2)  
Configuring the drive control mode  
Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display terminal, the  
integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Configuring communication monitoring  
Since the Altivar 38’s communication monitoring time out is the same as the default value of the Altivar 61’s [Modbus time out] (ttO)  
field (10 s), there is no point in modifying the value of this field.  
Modification of these parameters will only take effect on the next power-up.  
After transfer of the drive configuration by the PowerSuite software workshop, the [Channel switching] (CHCF) parameter is  
automatically assigned to [8 serie] (SE8), thus providing access to memory mapping for the Altivar 38 compatible with the Altivar 61.  
PLC configuration and application  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) means that no changes need to be made in the PLC  
application.  
However, in response to a function 43 identification request (16#2B) the drive will identify itself as an Altivar 61, not an Altivar 38.  
Scenario 2 Using the built-in port when replacing the ATV38 terminal port  
Configuring the drive  
This example is implemented in the PowerSuite software workshop and consequently all the settings linked to the configuration parameters  
(address, baud rate, parity) will be assigned automatically, identical to the Altivar 38.  
Configuring communication monitoring  
Since the Altivar 38’s communication monitoring time out is the same as the default value of the Altivar 61’s [Modbus time out] (ttO)  
field (10 s), there is no point in modifying the value of this field.  
Modification of these parameters will only take effect on the next power-up.  
PLC configuration and application  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) means that no changes need to be made in the PLC  
application.  
However, in response to a function 43 identification request (16#2B) the drive will identify itself as an Altivar 61, not an Altivar 38.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 3. Communication via Unitelway/Modbus network and VW3 A3 303 option card  
3. 3. 1. Reminder of possible connection methods  
ATV38  
ATV 61  
3 = D(A)  
3 = D(A)  
4 = 0 V  
4 = 0 V  
7 = D(B)  
7 = D(B)  
If the chosen communication interface is the VW3 A3 303 option card (Modbus RTU/Jbus/Ascii, Unitelway) both the address and the  
protocol format must be configured manually.  
3. 3. 2. Configuring the drive address on the Modbus/Unitelway network  
Transfer the Altivar 38 address to the Altivar 61:  
An Altivar 38 was identified on the bus by its address, coded between 0 and 31.  
The address corresponds to the number represented by the binary value 1 or 0 of the 8 card switches  
(in fact only micro-switches 3 to 7 are used).  
The least significant bits are on the right.  
Transfer the Altivar 38 address to the Altivar 61 using the 8 switches on the right of the card; the value 0 being the OFF position,  
the value 1 the ON position.  
The least significant bits are on the right.  
On the Altivar 38, the binary value 1 of a switch is in the up position, on the Altivar 61 this position is reversed, and the value 1 is effective  
in the down position.  
Example  
ATV38  
ATV 61  
Address 11 = 2#0001011  
Address 11 = 2#0001011  
Address ATV38 switches  
12345678  
ATV61 switches  
12345678  
0000 0000  
0000 0001  
0000 0010  
0000 0011  
0000 0100  
0000 0101  
0000 0110  
0000 0111  
0000 1000  
0000 1001  
0000 1010  
0000 1011  
0000 1100  
0000 1101  
0000 1110  
0000 1111  
Address ATV38 switches  
12345678  
ATV61 switches  
12345678  
0001 0000  
0001 0001  
0001 0010  
0001 0011  
0001 0100  
0001 0101  
0001 0110  
0001 0111  
0001 1000  
0001 1001  
0001 1010  
0001 1011  
0001 1100  
0001 1101  
0001 1110  
0001 1111  
0
0000 0000  
0000 0010  
0000 0100  
0000 0110  
0000 1000  
0000 1010  
0000 1100  
0000 1110  
0001 0000  
0001 0010  
0001 0100  
0001 0110  
0001 1000  
0001 1010  
0001 1100  
0001 1110  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
0010 0000  
0010 0010  
0010 0100  
0010 0110  
0010 1000  
0010 1010  
0010 1100  
0010 1110  
0011 0000  
0011 0010  
0011 0100  
0011 0110  
0011 1000  
0011 1010  
0011 1100  
0011 1110  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
Use of address 0 is not recommended on a Modbus/Unitelway network as this address has the effect of deactivating the option card.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 3. 3. Configuring polarity on the drive RS 485 bus  
The card is equipped with 2 line polarity configuration switches but the orientation is not the same for the Altivar 38 and the Altivar 61.  
Configure the polarity according to the following method.  
ATV38  
ATV 61  
Unitelway protocol  
Modbus/Jbus protocol  
Configuring the drive control mode  
Check and configure as necessary the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display  
terminal, the integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
3. 3. 4. PLC configuration and application  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) performed by the PowerSuite software workshop  
means that no changes need to be made in the PLC application.  
However, in response to a function 43 identification request (16#2B) the drive will identify itself as an Altivar 61, not an Altivar 38.  
3. 4. Communication via CANopen network  
3. 4. 1. Reminder of possible connection methods  
ATV38  
ATV 61  
2 = CAN_L  
1 = CAN_GND  
2 = CAN_L  
4 = CAN_H  
3 = CAN_GND  
7 = CAN_H  
The ATV61 CANopen adapter must be used when connecting the Altivar 61 to a CANopen network.  
ATV61  
CANopen  
adapter  
E.g., ATV61HU22M3  
3. 4. 2. Matching the line termination resistor  
The VW3 CAN KCDF 180T connector for connecting to the CANopen bus incorporates a line termination resistor. You should ensure this  
has been activated when the drive is at the end of the trunk cable.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 4. 3. Configuring the drive  
On the Altivar 38’s CANopen communication option card, both addresses and the bus speed could be set via switches.  
The PowerSuite software workshop is not capable of configuring the Altivar 61 automatically since these parameters were not stored in the  
Altivar 38 but in the option card.  
The Altivar 61 parameters should, therefore, be set via the programming terminal, and where the product is being migrated, the PowerSuite  
software workshop is responsible for configuring the drive so that it is identical to the configuration that existed on the Altivar 38.  
3. 4. 4. Address and Baud rate  
Configuration of the Altivar 61’s CANopen communication functions is accessed via the [CANopen] (CnO-) submenu in the [1.9 -  
COMMUNICATION] (COM-) menu on the graphic display terminal, integrated display terminal or the PowerSuite software workshop.  
The configuration can only be modified when the motor is stopped and the drive locked (no run command present).  
In order for modifications to take effect, the drive must be shut down then restarted.  
Parameter  
Possible values  
0 to 127  
Terminal display  
[0] (0) to [127] (127)  
[50 kbps] (50)  
Default value  
[CANopen address] (AdCO)  
[CANopen bit rate] (bdCO)  
0
50 kbps  
125 kbps  
250 kbps  
500 kbps  
1000 kbps  
[125 kbps] (125)  
[250 kbps] (250)  
[500 kbps] (500)  
[1 Mbps] (1M)  
125 kbps  
3. 4. 5. PLC configuration and application  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) performed by the PowerSuite software workshop  
means that no changes need to be made in the PLC application.  
In fact, the PDO used by default in the Altivar 61 in 8 serie mode is PDO1 type and is, therefore, compatible with that in the Altivar 38.  
Configuring the drive control mode  
Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display terminal, the  
integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 5. Communication via Profibus DP network  
3. 5. 1. Reminder of the possible connection methods: Same as existing  
3 = Rx/Tx-  
5 = GND  
6 = VP  
8 = Rx/Tx+  
3. 5. 2. Configuring the drive address on the Profibus DP network  
With the Altivar 38’s VW3-A58307 Profibus DP option card, the drive address was coded via the programming terminal. You need, therefore,  
to use this terminal to find this address before turning off the drive and replacing it.  
Transfer the Altivar 38 address to the Altivar 61 using the 7 switches on the right of the card; the value 0 being the OFF position, the value  
1 the ON position.  
Example  
Address 23  
Address 89  
Address  
Switches  
1234 5678  
Address  
Switches  
1234 5678  
Address  
Switches  
Address  
Switches  
1234 5678  
1234 5678  
0
1000 0000  
1000 0001  
1000 0010  
1000 0011  
1000 0100  
1000 0101  
1000 0110  
1000 0111  
1000 1000  
1000 1001  
1000 1010  
1000 1011  
1000 1100  
1000 1101  
1000 1110  
1000 1111  
1001 0000  
1001 0001  
1001 0010  
1001 0011  
1001 0100  
1001 0101  
1001 0110  
1001 0111  
1001 1000  
1001 1001  
1001 1010  
1001 1011  
1001 1100  
1001 1101  
1001 1110  
1001 1111  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
1010 0000  
1010 0001  
1010 0010  
1010 0011  
1010 0100  
1010 0101  
1010 0110  
1010 0111  
1010 1000  
1010 1001  
1010 1010  
1010 1011  
1010 1100  
1010 1101  
1010 1110  
1010 1111  
1011 0000  
1011 0001  
1011 0010  
1011 0011  
1011 0100  
1011 0101  
1011 0110  
1011 0111  
1011 1000  
1011 1001  
1011 1010  
1011 1011  
1011 1100  
1011 1101  
1011 1110  
1011 1111  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
1100 0000  
1100 0001  
1100 0010  
1100 0011  
1100 0100  
1100 0101  
1100 0110  
1100 0111  
1100 1000  
1100 1001  
1100 1010  
1100 1011  
1100 1100  
1100 1101  
1100 1110  
1100 1111  
1101 0000  
1101 0001  
1101 0010  
1101 0011  
1101 0100  
1101 0101  
1101 0110  
1101 0111  
1101 1000  
1101 1001  
1101 1010  
1101 1011  
1101 1100  
1101 1101  
1101 1110  
1101 1111  
96  
1110 0000  
1110 0001  
1110 0010  
1110 0011  
1110 0100  
1110 0101  
1110 0110  
1110 0111  
1110 1000  
1110 1001  
1110 1010  
1110 1011  
1110 1100  
1110 1101  
1110 1110  
1110 1111  
1111 0000  
1111 0001  
1111 0010  
1111 0011  
1111 0100  
1111 0101  
1111 0110  
1111 0111  
1111 1000  
1111 1001  
1111 1010  
1111 1011  
1111 1100  
1111 1101  
0111 1110  
1
97  
2
98  
3
99  
4
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
If the PLC module was configured using the Sycon < v2.8 configuration tool, it was possible to use address 126 for a subscriber  
(Altivar or other).  
This address is reserved and, therefore, its use is prohibited from version v2.8 onwards in accordance with the recommendations  
of the Profibus consortium.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 5. 3. Configuring the drive in "ATV38 Interchangeability" mode  
The Profibus protocol operates according to the principle of exchanging periodic data.  
In order to use the output data and input data from Altivar 38 cyclic exchanges, rather than those from Altivar 61, you need to set switch 1  
to the ON position and restart the drive. This also enables the card to identify itself as an Altivar 38 (Ident_Number= 0x00B9) when the bus  
module is turned on.  
• Switch 0 (OFF)  
• Switch 1 (ON)  
: Altivar 61 mode  
: Altivar 38 Interchangeability mode  
Configuring the drive control mode  
Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display terminal, the  
integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
3. 5. 4. PLC configuration and application  
In "ATV38 Interchangeability" mode, the Altivar 61’s PKE, R/W and R/W/N parameters are adapted in order to make the PKW service  
compatible with the Altivar 38’s parameters. There is, therefore, no need to change the application GSD file.  
3. 5. 5. Communication fault  
Profibus communication faults are indicated by the red RD LED on the card.  
Parameter [Network fault] (CnF-) can be used to obtain more detailed information about the origin of the fault. It can only be accessed  
on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-).  
Value Description of the values of the [Network fault] (CnF-) parameter  
0
1
2
3
No fault  
Time out for receipt of periodic variables destined for the drive. This time out can be set by the network configuration software.  
Identification fault between the drive Profibus card and the Profibus master  
Initialization fault on the drive Profibus card (hardware problem)  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 6. Communication via Fipio network - VW3 A3 311 option card  
3. 6. 1. Reminder of the possible connection methods: Same as existing  
6 = Tx+  
7 = Tx-  
3. 6. 2. Presentation  
The VW3 A3 311 Fipio communication card can be used to connect an Altivar 61 drive to a Fipio network as a replacement for an Altivar 38.  
Its functions have been designed specifically for both periodic- and aperiodic-data transfer by means of a messaging service.  
It is designed to replace an Altivar 38 equipped with a VW3-A58311 Fipio card.  
3. 6. 3. Connecting to the Fipio bus  
If the tap junction connector used with the Altivar 38 is a TSX FP ACC12 connector, no restrictions are imposed when replacing an Altivar  
38 with an Altivar 61.  
If this tap junction connector is a TSX FP ACC2, the Fipio cables and/or  
the TSX FP ACC7 line terminator must be located on this tap junction  
connector on the side indicated opposite.  
TSX FP ACC2 connector  
with wiring on the right.  
This involves modifying the internal connections to the tap junction  
connector, and it is possible that this may pose new problems concerning  
cable length(s), see General, page 37.  
3. 6. 4. Configuring the drive address on the Fipio network  
Examples  
Address 11: 2#001011  
Address 34: 2#100010  
Address  
Switches  
1234 5678  
Address  
Switches  
1234 5678  
Address  
Switches  
1234 5678  
Address  
Switches  
1234 5678  
0
1
0000 0000  
0000 0001  
0000 0010  
0000 0011  
0000 0100  
0000 0101  
0000 0110  
0000 0111  
0000 1000  
0000 1001  
0000 1010  
0000 1011  
0000 1100  
0000 1101  
0000 1110  
0000 1111  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
0001 0000  
0001 0001  
0001 0010  
0001 0011  
0001 0100  
0001 0101  
0001 0110  
0001 0111  
0001 1000  
0001 1001  
0001 1010  
0001 1011  
0001 1100  
0001 1101  
0001 1110  
0001 1111  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
0010 0000  
0010 0001  
0010 0010  
0010 0011  
0010 0100  
0010 0101  
0010 0110  
0010 0111  
0010 1000  
0010 1001  
0010 1010  
0010 1011  
0010 1100  
0010 1101  
0010 1110  
0010 1111  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
0011 0000  
0011 0001  
0011 0010  
0011 0011  
0011 0100  
0011 0101  
0011 0110  
0011 0111  
0011 1000  
0011 1001  
0011 1010  
0011 1011  
0011 1100  
0011 1101  
0011 1110  
0011 1111  
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
Note: Addresses 0 and 63 must not be used on an Altivar 38 or an Altivar 61.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
3. Implementation of the communication option cards  
3. 6. 5. Configuring the drive in "ATV38 Interchangeability" mode  
In order to use the Altivar 38’s periodic input/output variables rather than those of the Altivar 61, you need to set switch 1 to the ON position  
and restart the drive.  
• Switch 0 (OFF)  
• Switch 1 (ON)  
: Altivar 61 mode  
: 8 serie mode  
The PowerSuite software workshop will activate 8 serie mode once the configuration has been transferred.  
Configuring the drive control mode  
Check and configure as necessary the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display  
terminal, the integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
3. 6. 6. PLC configuration and application  
In the TSX Premium master’s Fipio configurator, only the base module described in the table below is compatible with an Altivar 61 used  
in 8 serie mode.  
Family  
Base module  
ATV-38  
ATV38 PKW  
3. 6. 7. Altivar 38 PKW indexed periodic variables  
In "ATV38 Interchangeability" mode, we do not recommend using the PKW service for the Altivar 61 indexed periodic variables, as this  
service is only designed for accessing the Altivar 61 parameters.  
You should, therefore, use the PKW service for the Altivar 38 indexed periodic variables, as described in the User’s Manual for the Altivar  
38 VW3-A58311 Fipio card. This service can be used to access only the Altivar 38 parameters.  
3. 6. 8. Managing loss of Fipio communication  
In order to imitate the Altivar 38’s behavior on disconnection of the bus ("stop on ramp" imposed by the drive), you should configure it using  
the integrated display terminal or the graphic display terminal.  
In the [COMMUNICATION FAULTS] (COF-) submenu in the [1.8 - FAULT MANAGEMENT] (FLt-) menu, assign the  
value [ramp] (rMP) to the [Com Bus Flt Mgt] (CLL) parameter, which is used to imitate the Altivar 38’s behavior on disconnection  
of the Fipio bus.  
Hence, when the drive is disconnected from the Fipio bus, the CNF fault will be activated and the value of parameter  
CLL will cause the motor to stop on a ramp.  
3. 6. 9. Communication fault  
Fipio communication faults are indicated by the red RD LED on the card.  
Parameter [Network fault] (CnF-) can be used to obtain more detailed information about the origin of the fault. It can only be accessed  
on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-).  
Value Description of the values of the [Network fault] (CnF-) parameter  
0
1
2
3
4
5
No fault  
Initialization fault on the Fipio card (hardware problem)  
Time out for receipt of periodic variables destined for the drive. This time out can be set by the network configuration software.  
Hardware fault on the Fipio card  
Hardware fault on the Fipio card  
Master PLC changes from Run to STOP  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 7. Communication via Interbus network  
3. 7. 1. Reminder of the possible connection methods: Same as existing  
1 = DO2  
2 = DI2  
3 = GNDO  
4 = NC  
5 = VCCO  
6 = DO2/  
7 = DI2  
8 = NC  
9 = RBST  
The profile used by the Altivar 61 in the CMD Tool bus configurator is compatible with that of the Altivar 38, i.e., DRIVECOM Type Profile 21  
(RB) and, therefore, there is no difference in the process data.  
Use the Altivar 61 control card’s external power supply function, as in the event of a break in the drive power supply all  
communication on the Interbus-S bus will cease.  
3. 7. 2. Configuring the communication parameters  
The drive is configured by default to communicate on the bus with limited services. The data exchanged on the bus is not transmitted to the  
drive.  
On the display terminal, in the [1.9 COMMUNICATION] (COM-) menu, [COMMUNICATION CARD] (CBD-) submenu, the  
value of the [Address] (AdrC) parameter is 0.  
To operate in normal mode, in which the data exchanged on the bus is transmitted to the drive by the INTERBUS card, the value of this  
[Address] (AdrC) parameter must be changed to 1.  
Configuring the drive control mode  
Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display terminal, the  
integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
3. 7. 3. PLC configuration and application  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) performed by the PowerSuite software workshop  
means that no changes need to be made in the PLC application.  
However, in response to an "Identify" service request the drive will identify itself as an Altivar 61, not an Altivar 38.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 8. Communication via Modbus Plus network  
3. 8. 1. Reminder of the possible connection methods: Same as existing  
1 = GND  
2 = Tx  
3 = Rx  
3. 8. 2. Configuring the drive address on the Modbus Plus network  
On the Altivar 38’s Modbus Plus option card, the drive address is coded using switches 1 to 6 (LSB to MSB).  
Therefore, simply transfer the switch configuration of a Modbus Plus option card for Altivar 38 to the switches of a Modbus Plus option card  
for Altivar 61.  
The address corresponds to the binary number given by position 0 or 1 of the 6 switches increased by 1.  
E.g., address 6 = 5 (+1)  
ATV38  
ATV61  
Address  
Switches  
Address  
Switches  
Address  
Switches  
1234 5678  
Address  
Switches  
1234 5678  
1234 5678  
1234 5678  
1
2
0000 0000  
1000 0000  
0100 0000  
1100 0000  
0010 0000  
1010 0000  
0110 0000  
1110 0000  
0001 0000  
1001 0000  
0101 0000  
1101 0000  
0011 0000  
1011 0000  
0111 0000  
1111 0000  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
0000 1000  
1000 1000  
0100 1000  
1100 1000  
0010 1000  
1010 1000  
0110 1000  
1110 1000  
0001 1000  
1001 1000  
0101 1000  
1101 1000  
0011 1000  
1011 1000  
0111 1000  
1111 1000  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
0000 0100  
1000 0100  
0100 0100  
1100 0100  
0010 0100  
1010 0100  
0110 0100  
1110 0100  
0001 0100  
1001 0100  
0101 0100  
1101 0100  
0011 0100  
1011 0100  
0111 0100  
1111 0100  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
0000 1100  
1000 1100  
0100 1100  
1100 1100  
0010 1100  
1010 1100  
0110 1100  
1110 1100  
0001 1100  
1001 1100  
0101 1100  
1101 1100  
0011 1100  
1011 1100  
0111 1100  
1111 1100  
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
3. 8. 3. Configuring the drive in "ATV38 Interchangeability" mode  
In order to use the Altivar 38 Peer Cop and Global Data variables rather than those of the Altivar 61, you need to set the right-hand switch  
to the ON position and restart the drive.  
• Switch 0 (OFF): Altivar 61 mode  
• Switch 1 (ON): 8 serie mode  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 8. 4. Configuring the drive in "ATV38 Interchangeability" mode  
The following bus management parameters:  
Time out, Peer Cop node, Control station, Number of registers are transferred by the PowerSuite software workshop with the same values  
as they had in the Altivar 38.  
Configuring the drive control mode  
Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display terminal, the  
integrated display terminal or the PowerSuite software workshop.  
[Profile] (CHCF) = [8 serie] (SE8)  
3. 8. 5. PLC configuration and application  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) performed by the PowerSuite software workshop  
means that no changes need to be made in the PLC application.  
3. 8. 6. Communication fault  
Modbus Plus communication faults are indicated by the red RD LED on the card.  
Parameter [Network fault] (CnF-) can be used to obtain more detailed information about the origin of the fault. It can only be accessed  
on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-).  
Value Description of the values of the [Network fault] (CnF-) parameter  
0
1
2
3
No fault  
Time out for receipt of periodic variables destined for the drive. This time out can be set by the network configuration software.  
Master PLC changes from Run to STOP  
Initialization fault on the Modbus Plus card (hardware problem)  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 9. Communication via DeviceNet network  
3. 9. 1. Reminder of the possible connection methods: Same as existing  
ATV38  
1 = GND  
2 = CAN_L  
3 = SHIELD Bare  
Black  
Blue  
4 = CAN_H White  
5 = V+ Red  
3. 9. 2. Configuring the drive on the network  
Configuring the switches  
MAC ID Baud Rate  
When switches 7 and 8 are in position 1 (ON), the baud rate value as well as the drive MAC ID address correspond to the  
attributes ID 1 (MAC ID) and ID 2 (Baud rate) of the DEVICENET Class ID 03hex object.  
All devices connected on a DEVICENET network must have an identical baud rate: 125, 250, or 500 kbps. In accordance with the table  
below:  
Switch 7  
Switch 8  
Baud Rate  
0
0
1
1
0
1
0
1
125 kbps  
250 kbps  
500 kbps  
both the baud rate value and the drive MAC ID address correspond to the attributes of the  
DEVICENET Class ID 03hex object.  
3. 9. 3. Configuring the drive address on the DeviceNet network  
MAC  
address  
MAC  
address  
MAC  
address  
MAC  
address  
Switches  
1234 56  
Switches  
1234 56  
Switches  
1234 56  
Switches  
1234 56  
00  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
0000 00  
0000 01  
0000 10  
0000 11  
0001 00  
0001 01  
0001 10  
0001 11  
0010 00  
0010 01  
0010 10  
0010 11  
0011 00  
0011 01  
0011 10  
0011 11  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
0100 00  
0100 01  
0100 10  
0100 11  
0101 00  
0101 01  
0101 10  
0101 11  
0110 00  
0110 01  
0110 10  
0110 11  
0111 00  
0111 01  
0111 10  
0111 11  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
1000 00  
1000 01  
1000 10  
1000 11  
1001 00  
1001 01  
1001 10  
1001 11  
1010 00  
1010 01  
1010 10  
1010 11  
1011 00  
1011 01  
1011 10  
1011 11  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
1100 00  
1100 01  
1100 10  
1100 11  
1101 00  
1101 01  
1101 10  
1101 11  
1110 00  
1110 01  
1110 10  
1110 11  
1111 00  
1111 01  
1111 10  
1111 11  
Configuring the drive control mode  
Check and configure the control mode applied to the drive in the [1.6 - COMMAND] (CtL-) menu on the graphic display terminal, the  
integrated display terminal or the PowerSuite software workshop  
[Profile] (CHCF) = [8 serie] (SE8)  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
PLC configuration and application  
Only activate the Device Type option in the "Electronic Key" zone, so that there is no control over the node type when the bus starts.  
The fact of opening the Altivar 61’s "ATV38 compatibility" memory zone (SE8 mode) performed by the PowerSuite software workshop  
means that no changes need to be made in the PLC application.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 9. 4. Drive implementation on the DeviceNet network  
Before attempting to replace an Altivar 38 with an Altivar 61, its configuration must be backed up using the RSNetWorx software workshop.  
1 Launch the RSNetWorx application then "browse" the network by clicking on this icon.  
2 The scanner identifies the various nodes present on the network.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3 "Upload" the Altivar 38 configuration:  
Once the network has been identified correctly, the whole configuration can be retrieved from a slave.  
Double-click with the left mouse button on the relevant Altivar 38. The following window appears:  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
4 Click on the "Device Parameter" tab; a window appears asking whether you want to "Upload" or "Download".  
Choose Upload in order to retrieve the Altivar 38 configuration.  
Uploading in progress:  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
5 Once uploading is complete, a window appears; click on the "Device Parameters" tab to display all the Altivar 38 parameters.  
The whole Altivar 38 configuration has now been retrieved. Click "OK" to exit this window and retain a trace of the original configuration.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Backing up the configuration before transfer to the Altivar 61 in 8 serie mode:  
Select "Save As…" in the File menu to retain this configuration:  
Give your configuration a name:  
Then back up the file:  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
6 Preparation of the Altivar 61:  
It is vital to perform a special setting on the Altivar 61 so that it can accept the old Altivar 38 configuration, which will be transmitted by the  
DeviceNet network.  
This operation consists of declaring in the Altivar 61 the version of the Altivar 38 it is to replace.  
Identify and note down the Altivar 38 software version; this information can be found on the drive above the connector for connecting the  
programming terminal, and in our example it is version 5.3 ie12; only the first two numbers are required (in our example: 5.3).  
Enter the following parameters in the [1.9 - COMMUNICATION] (COM-) menu on the graphic display terminal or integrated display  
terminal, [DeviceNet] (dnEt) submenu:  
Parameter no.  
To be entered  
Example ATV38 v5.3ie12  
[P06] (P06)  
[P08] (P08)  
ATV38 version  
1
53  
1
Parameter P08 can be used to save the data entered in parameters P06; its value returns to 0 after it has been taken into account and  
saved in the Altivar 61’s EEPROM.  
Install the Altivar 61 in place of the Altivar 38 (this operation must be performed with the power off). Then turn the Altivar 61 back on.  
Right-click to load the Altivar 38 configuration that you have already saved and select "Download to Device".  
Once downloading is complete, the Altivar 61 has retrieved the whole Altivar 38 configuration.  
Turn the drive off and then back on again. This operation is essential so that the Assembly devices are taken into account by the drive.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 9. 5. Communication fault  
DeviceNet communication faults are indicated by the red RD LED on the card.  
Parameter [Network fault] (CnF-) can be used to obtain more detailed information about the origin of the fault. It can only be accessed  
on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-).  
Value Description of the values of the [Network fault] (CnF-) parameter  
0
1
2
3
4
5
6
7
8
9
No fault  
Fault caused by the user  
Duplication of the MAC ID address  
Error on the reception buffer  
Error on the transmission buffer  
Initialization fault on the drive DeviceNet card (hardware problem)  
Error during sending of a telegram  
DeviceNet bus not operating  
Time out for receipt of periodic variables destined for the drive. This time out can be set by the network configuration software.  
Cyclic or COS data acknowledgement error  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 10. Communication via Ethernet network  
3. 10. 1. Reminder of the possible connection methods: Same as existing  
1 = TD+  
2 = TD-  
3 = RD+  
6 = RD-  
8........................1  
Warning  
Because of certain minor incompatibilities, described below, the replacement of an Altivar 38 by an Altivar 61 on an Ethernet bus  
is supposed to be definitive.  
The reason is that modifications, which can be made when migrating from Altivar 38 to Altivar 61, only work in the context of  
upward compatibility (ATV38 to ATV61).  
3. 10. 2. Transmission speed  
The VW3 A3 310 Ethernet card supports speeds of 10 Mbps and 100 Mbps, as well as half-duplex and full-duplex modes for both these  
transmission speeds, and is fully compatible with the VW3 A58310 Ethernet card.  
In order to configure the Ethernet card parameters, the Altivar 61 must be configured in Expert mode; moreover, use of the graphic  
display terminal is essential for assignment of the DeviceName if DHCP-FDR protocol is used.  
3. 10. 3. Drive configuration in Expert mode  
The Altivar 61 must be in Expert mode in order to configure the VW3 A3 310 Ethernet card functions; from the main screen, open the  
[2.0 - ACCESS LEVEL] menu and select Expert mode.  
3. 10. 4. Assigning a dynamic IP address to the drive  
Using the BOOTP protocol  
In the BOOTP address server configuration, the Altivar 38 Ethernet card’s MAC address must be replaced with the Altivar 61 Ethernet card’s  
MAC address, since this type of address is unique and linked to the hardware.  
Location of the MAC address:  
ATV38  
ATV61  
This only applies if the drive IP address is supplied by a BOOTP server, i.e., if the drive IP address is 0.0.0.0 and the FDR function has not  
been enabled (parameter in the [ETHERNET] (EtH-) submenu in the [1.9 - COMMUNICATION] (COM-) menu, [FDR  
validation] (FdrU ) set to [No] (nO)).  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 10. 5. Using the DHCP-FDR protocol  
The DHCP-FDR protocol is only supported by version 2.1 of the VW3 A58310 Ethernet option card.  
This section, therefore, only applies to replacement of an Altivar 38 equipped with this type of card.  
This only applies if the drive IP address is supplied by a DHCP server, i.e., if the drive IP address is set to 0.0.0.0 and the FDR function has  
been enabled ([FDR validation] (FdrU ) parameter set to [Yes] (YES)).  
The DHCP-FDR address server configuration remains the same when the Altivar 38 drive is replaced by an Altivar 61.  
Important: It is essential to transfer the name of the Altivar 38 to the Altivar 61:  
Before turning off the Altivar 38 to be replaced, check its DHCP name (its "DeviceName") from the "8-Communication" (SL) menu via the  
programming terminal or the PowerSuite software workshop.  
Procedure on the Altivar 38:  
1 Select "Parameter 05" (-P05 or -O05) and press ENT.  
2 Use the arrow keys to enter the value "4" and press ENT; this value is reset shortly afterwards by the drive.  
3 Select "Parameter 01" (-P01 or -O01) and press ENT.  
4 Note down the value which then appears: "xxxx" (between "0" and "9999").  
The drive DHCP name is based on this value and becomes: "ATV_xxxx".  
E.g., "ATV_0004" instead of "4".  
You should then transfer this DHCP name to the Altivar 61 using the graphic display terminal or the PowerSuite software tool.  
From the main screen, open the [7.0 - DISPLAY CONFIG.] menu then [7.1 - USER PARAMETERS] and [DEVICE NAME];  
use the navigation button as well as function keys  
F1, F2, F3, F4 to enter the text "ATV_xxxx", in our example ATV_0004.  
3. 10. 6. Faulty Device Replacement (FDR)  
Activating the service  
The FDR service is only supported by version 2.1 of the VW3 A58310 Ethernet option card.  
This section, therefore, only applies to replacement of an Altivar 38 equipped with this type of card.  
If the Altivar 38 to be replaced was using the FDR service (IP address set to 0.0.0.0 and FDR service activated/enabled), the Altivar 38  
configuration should be transferred to the Altivar 61 following the procedure described below:  
1 With the Altivar 38 supplied with power, retrieve the drive configuration using the PowerSuite v2.40 software workshop; save this  
configuration in order to create an original ATV38 configuration file.  
2 Turn off the Altivar 38.  
3 Now implement the hardware (Altivar 61 and VW3 A3 310 Ethernet card).  
4 In the PowerSuite software workshop, transfer the configuration retrieved from the Altivar 38 to the drive; this has been processed by the  
PowerSuite software workshop to make it compatible with the Altivar 61.  
5 Modify the [Ethernet local conf] (LCFG) = [Yes] (YES) parameter and also the DeviceName (ATV_xxxx).  
6 Start up the DHCP-FDR server (e.g., TSX Premium PLC) and check that the drive itself receives an IP address (green IP LED lit).  
7 The drive configuration is automatically saved in the server.  
8 Once it has been saved at least once, modify parameter [Ethernet local conf] (LCFG) = [No] (nO).  
9 Use a Web browser to connect to the Ethernet card HTTP server, then access the "FDR Agent" page located in the "Setup" menu, and  
press the "Save" button.  
Incompatible FDR files  
VW3 A58310 Ethernet card FDR files are incompatible with those on VW3 A3 310 Ethernet cards.  
The procedure for replacing an Altivar 38 with an Altivar 61 on an Ethernet network, described above, causes the FDR file for  
Altivar 38 present on the FDR server to be lost.  
However, the drive configuration can be retrieved in the PowerSuite software workshop if it has been saved to a file, and the  
Altivar 38 that has been replaced still has its configuration.  
It is, therefore, possible (if necessary) to rebuild the original FDR file on the FDR server. The procedure for doing this is similar to  
the procedure described above.  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 10. 7. Programming the Altivar 38 Ethernet parameters  
Apart from the drive DHCP name ("DeviceName" parameter), all the parameters that can be accessed using the Altivar 38’s programming  
terminal are present on an Altivar 61 equipped with a VW3 A3 310 Ethernet card.  
They can be accessed from the [ETHERNET] (EtH-) submenu in the [1.9 - COMMUNICATION] (COM-) menu. The  
correspondence of these parameters between the two types of drive is described in the following table:  
Altivar 38  
Altivar 61  
Command  
Description  
Graphic display terminal or integrated display  
terminal  
Short  
parameter name  
Value in …  
P05/O05  
1
IP address  
P01/O01 to P04/  
O04  
AdrIP[1] to AdrIP[4] [IP card] (IPC-) + (IPC1) to (IPC4)  
2
3
4
5
Subnet mask  
P01/O01 to P04/  
O04  
Mask[1] to Mask[4] [IP Mask] (IPM-) + (IPM1) to (IPM4)  
Gateway address  
DeviceName  
P01/O01 to P04/  
O04  
Gtw[1] to Gtw[4]  
DeviceName  
Validation  
Local Config  
FileDef  
[IP Gate] (IPG-) + (IPG1) to (IPG4)  
XXXX  
P01/O01  
P01/O01  
P02/O02  
P03/O03  
P01/O01  
P02/O02  
P01/O01  
P02/O02  
P03/O03  
FDR configuration  
[FDR validation] (FdrU) + (NO/YES)  
[Ethernet local conf] (LCFG) +(OFF/ON)  
[FDR file error] (FdrF) + (OFF/ON)  
[FDR autosave] (FdrS) + (NO/YES)  
[FDR t. autosave] (Fdrt) + 2 to 255  
[FDR Action] (FdrA) + (IDLE, SAVE, REST, DEL)  
[FDR state] (FdrE)  
6
7
FDR-Autosave  
configuration  
AutoSave  
Timer  
FDR status  
Action  
Status  
ErrCode  
[FDR Fault] (FdrD) + 0 to 65535  
[IP FDR] (IPF-) + (IPF1) to (IPF4)  
[IP Process] (IPP-) + (IPP1) to (IPP4)  
[Eth IO Scan act] (IOSA) + (OFF/ON)  
[Ethernet Timeout] (tOUt) + 0 to 60.0  
8
DHCP-FDR server  
IP address  
P01/O01 to P04/  
O04  
Ip[1] to Ip[4]  
(DHCP-FDR)  
9
IP Master address  
P01/O01 to P04/  
O04  
Ip[1] to Ip[4]  
(Master)  
10  
IO Scanner  
configuration  
P01/O01  
Activation  
P02/O02  
Time out  
3. 10. 8. Modbus service  
Available address fields  
In "ATV38 Interchangeability" mode (SE8 mode), addresses W1 to W615, described in the Altivar 38 "Internal communication variables"  
User’s Manual, can now be accessed in order to insure that an Altivar 38 can be replaced by an Altivar 61.  
In order to access these variables by means of TCP/Modbus messaging, a UNIT_ID of 0 must be used, in the same way as before on the  
Altivar 38.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Ethernet card access to the Modbus server  
With the VW3 A3 310 Ethernet card, access to address fields W40 ppp (values transmitted by the IO Scanner), W50 ppp"" (addresses  
assigned to the IO Scanner) and W60 ppp"" (Ethernet parameters) is only possible by using a (UNIT_ID) address of 251 in your TCP/  
Modbus requests.  
E.g.,  
(* Writing one of the ATV61 Ethernet card parameters *)  
IF (NOT %MW810 :X0 AND %M65) THEN  
%MW811 :3 :=0;  
WRITE_VAR(ADR# {1.101} 6.0.251,'%MW', %MD2400, %MW2, %MW3000 :6,%MW810 :4);  
RESET %M65;  
END_IF;  
In "ATV38 Interchangeability" mode (SE8 mode), it is still essential to use this new address in order to obtain access  
to these fields, which had been available via address 0 with the VW3 A58310 Ethernet card. This address is no  
longer used for this purpose on the Altivar 61’s VW3 A3 310 card.  
Modbus functions available  
The "Drive Identification" function on the VW3 A3 310 Ethernet card is incompatible with that on the VW3 A58310 Ethernet card.  
Modification to be made in the context of upward compatibility  
Function 65 (16#41) in the VW3 A58310 Ethernet card must be replaced by function 43 (16#2B), described in the "Drive  
Identification" Request section, pages 32 and 36 in the VW3 A3 310 card Programming Manual.  
This new function conforms to the Modbus protocol identification function and is used by the new products marketed by  
Schneider Electric.  
3. 10. 9. IO Scanning service  
IO Scanning control  
In order to imitate the Altivar 38’s behavior when a CNF fault is triggered by IO Scanning control ("freewheel stop" imposed by the drive),  
you should configure it using the integrated display terminal, graphic display terminal or the PowerSuite software workshop.  
In the [1.8 - FAULT MANAGEMENT] (FLt-) menu, assign the value [Freewheel] (nSt) to the [Network fault mgt]  
parameter in the [Com. Fault Mgt] (CLL) submenu.  
In this way, when a CNF fault is triggered by IO Scanning control, the value of the CLL parameter will cause a freewheel stop.  
Note: The CMD command word cannot be removed from the Altivar 38’s IO Scanner, and the check on writing of the CMD command word  
by TCP/Modbus messaging does not apply to an Altivar 61 when it is used in "ATV38 Interchangeability" mode (SE8 mode).  
Configuring the periodic parameter assignment table  
If the Altivar 38’s VW3 A58310 Ethernet card uses periodic parameters configured by default (factory settings), it is still necessary to  
configure the periodic parameter assignment table in the Altivar 61’s VW3 A3 310 Ethernet card since, by default, only the first two input  
periodic parameters (CMD and LFRD) and the first two output periodic parameters (ETA and RFRD) are the same as those on the Altivar  
38’s VW3 A58310 Ethernet card.  
Configuration is performed either by TCP/Modbus messaging, or from the "IO Scanner" page of the standard HTTP server (see below), or  
using PowerSuite.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 10. 10. Communication fault  
Ethernet communication faults are indicated by the red FLT LED on the card.  
Parameter [Network fault] (CnF-) can be used to obtain more detailed information about the origin of the fault. It can only be accessed  
on the graphic display terminal, in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-).  
Value Description of the values of the [Network fault] (CnF-) parameter  
0
No fault  
Tcp/Modbus Time out fault.  
The Tcp/Modbus Time out is activated as soon as the control word is received:  
1
- If no IP master has been configured, the period of activity is maintained by receipt of the control word.  
- If an IP master has been configured, the period of activity is maintained by any type of Tcp/Modbus request on this IP address.  
No Time out is managed if its value equals 0.  
Ethernet network overload  
10  
11  
No signal from the Ethernet network, cable pulled out, etc.  
3. 10. 11. FDR service fault (EPF2)  
The EPF2 communication fault is indicated by the red RD LED on the card.  
This fault appears when a problem arises during the FDR status diagram sequence on the drive, provided that the FDR service is being  
used and that FDR errors are permitted on the drive ([FDR Error Mgt.] (FdrG) = [Yes] (YES) or FDR file error (address 60 060) =  
[Yes] (YES)). This fault is resettable.  
The EPF2 fault is also triggered if the drive IP address is already being used by another device. In this case, the EPF2 fault is not  
resettable. You should then modify the drive IP address, or that of the device using this IP address, then restart the drive.  
It is possible to obtain more detailed information about the origin of the fault. It can only be accessed on the graphic display  
terminal, in the [1.9 COMMUNICATION] (COM-) menu, [Ethernet] (EtH-), [FDR fault] (Fdrd).  
Value Description of the values of the [Network fault] (CnF-) parameter  
2
FDR configuration file incompatible  
3
Error reading the FDR file  
4
Error writing the FDR file  
7
Time out for access to the FTP server has elapsed. This time out cannot be set (90 s)  
Duplication of the IP address  
9
12  
FDR file not present in the FTP server  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Configuring the "IO Scanner" page from the HTTP server  
Click the "Setup" button.  
Click the "IO Scanner" button.  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Click the "PassWord" button, enter USER in the Password field; press the Enter key on your keyboard, then Deactivate the IO scanner by  
setting IoScanner to No.  
Complete the "IO Scanning" table, save the table and reactivate the IO Scanner by setting IoScanner to Yes.  
Do not take account of the new logic addresses that appear to the right of the register:  
When IO Scanner is configured via the HTTP server or PowerSuite, the Altivar 61’s logic addresses are displayed, but only the  
description matters to you.  
No modification should be made in the PLC when the IO Scanner function is being used.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Configuring the "IO Scanner" page using TCP/Modbus messaging  
Using TCP/Modbus services and calling on the Ethernet card’s Modbus server, assign the same drive parameter as for the Altivar 38  
register to each periodic register.  
The table below represents the default table for the Altivar 38 periodic data as seen by the PLC module.  
Ethernet  
server  
address  
Ethernet  
server  
address  
ATV61 register  
and address  
ATV61 register  
and address  
Description  
Description  
Output periodic  
no. 1  
Input periodic  
no. 1  
50 001  
50 002  
50 003  
50 004  
50 005  
50 006  
50 007  
50 008  
50 009  
50 010  
CMD  
8 501  
8 602  
8 504  
0 478  
0 000  
0 000  
0 000  
0 000  
0 000  
0 000  
50 017  
50 018  
50 019  
50 020  
50 021  
50 022  
50 023  
50 024  
50 025  
50 026  
ETA  
3 201  
8 604  
3 204  
0 478  
5 232  
3 205  
7 101  
3 206  
0 000  
0 000  
Output periodic  
no. 2  
Input periodic  
no. 2  
LFRD  
CMI  
IOLR  
--  
RFRD  
LCR  
IOLR  
AI1R  
OTR  
DF1  
ETI  
Output periodic  
no. 3  
Input periodic  
no. 3  
Output periodic  
no. 4  
Input periodic  
no. 4  
Output periodic  
no. 5  
Input periodic  
no. 5  
Output periodic  
no. 6  
Input periodic  
no. 6  
--  
Output periodic  
no. 7  
Input periodic  
no. 7  
--  
Output periodic  
no. 8  
Input periodic  
no. 8  
--  
Output periodic  
no. 9  
Input periodic  
no. 9  
--  
--  
Output periodic  
no. 10  
Input periodic  
no. 10  
--  
--  
We recommend that you use the configuration presented above due to the fact that neither PowerSuite nor the pages of the drive standard  
HTTP server offer the Altivar 38 parameter addresses during configuration of the periodic parameter assignment table for the Altivar 61’s  
VW3 A3 310 Ethernet card.  
If the Altivar 38’s VW3 A58310 Ethernet card uses one or more periodic parameters alongside those that are configured by default  
(modification of factory settings):  
Using the PowerSuite software workshop, pages of the drive standard HTTP server or TCP/Modbus services, you should modify the  
configuration of the periodic parameter assignment table for the Altivar 61’s VW3 A3 310 Ethernet card so that it has exactly the same  
configuration as that of the Altivar 38 (see previous section).  
Parameter incompatibilities  
When the IO Scanner is configured via the HTTP server or PowerSuite, the register’s Altivar 61 logic address is displayed, but  
only the description matters to you.  
No modification should be made in the PLC when the IO Scanner function is being used.  
Altivar 38 PKW parameter-setting service  
In "ATV38 Interchangeability" mode (SE8 mode), we recommend use of the Altivar 38’s PKW parameter-setting service as described in the  
Altivar 38 VW3 A58310 Ethernet card User’s Manual.  
Note: Both these services use the same PKE, R/W and PWE output variables (output registers 28, 29 and 31), as well as the same PKE,  
R/W/N and PWE input variables (input registers 28, 29 and 31) of the Altivar 38.  
SNMP agent  
The following modifications apply to the Altivar 61’s VW3 A3 310 Ethernet card:  
• "SysName" object: This object took the name of the Ethernet card in the case of the Altivar 38 ("VW3A58310"), whereas it now takes the  
name of the Altivar 61, if it exists.  
• "SysService" object: Value equals -1 in the case of the Altivar 38, as against 72 with the Altivar 61.  
• Use of a "community name": the "community string" character string in read/write mode for the Altivar 61 is "schneider"; "public" in  
read-only mode.  
PRIVATE  
For the Altivar 38, it was:  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
Standard HTTP server  
The storage capacity of the VW3 A3 310 Ethernet card for Web server files has been increased: 1.536 kb, as against 196 kb for the  
VW3 A58310 Ethernet card.  
The maximum number of URL files has changed from 50 to 150.  
Transferring all the URL files present on the Altivar 38’s Web server to the Altivar 61’s Web server is not permitted. There are several  
reasons for this:  
• The drive parameter addresses are totally different between the two drives and these addresses are displayed in the Web pages by  
means of a file that can be found on the drive Web server: "DataFile.txt".  
Apart from that, the content of the Web pages remains identical, and the Applets support the developments on the VW3 A3 310 card  
(example: the "Altivar Viewer"/"Altivar" page has been updated to support the Altivar 61’s additional inputs, outputs and relays).  
Nonetheless, if you have added functions to the Altivar 38’s standard HTTP server and you wish to apply them to the Altivar 61’s HTTP  
server, it is your responsibility to adapt them in accordance with the Altivar 61 Web page format, before transferring them to the Altivar 61’s  
Web server.  
"PDA Altivar" page: Last Fault = ILF Fault  
This page is no longer used with the Altivar 61’s VW3 A3 310 Ethernet card.  
Communication fault  
Ethernet communication faults are indicated by the red RD LED on the card.  
Parameter [Network fault] (CnF-) can be used to obtain more detailed information about the origin of the fault. It can only be accessed  
on the graphic display terminal, in the [1.10 DIAGNOSTICS] (DGt-) menu, [MORE FAULT INFO] (AFI-).  
Value  
Description of the values of the [Network fault] (CnF-) parameter  
0
No fault  
Tcp/Modbus Time out fault.  
The Tcp/Modbus Time out is activated as soon as the control word is received:  
1
• If no IP master has been configured, the period of activity is maintained by receipt of the control word.  
• If an IP master has been configured, the period of activity is maintained by any type of Tcp/Modbus request on  
this IP address.  
No Time out is managed if its value equals 0  
Ethernet network overload  
10  
11  
No signal from the Ethernet network, cable pulled out, etc.  
FDR service fault (EPF2)  
The EPF2 communication fault is indicated by the red RD LED on the card.  
This fault appears when a problem arises during the FDR status diagram sequence on the drive, provided that the FDR service is being  
used and that FDR errors are permitted on the drive ([FDR Error Mgt.] (FdrG) = [Yes] (YES) or FDR file error (address 60 060) =  
[No] (nO)). This fault is resettable.  
The EPF2 fault is also triggered if the drive IP address is already being used by another device. In this case, the EPF2 fault is not  
resettable. You should then modify the drive IP address, or that of the device using this IP address, then restart the drive.  
It is possible to obtain more detailed information about the origin of the fault. It can only be accessed on the graphic display  
terminal, in the [1.9 COMMUNICATION] (COM-) menu, [Ethernet] (EtH-), [FDR fault] (Fdrd).  
Value  
Description of the values of the [Network fault] (CnF-) parameter  
FDR configuration file incompatible  
2
3
Error reading the FDR file  
4
Error writing the FDR file  
7
Time out for receipt of the FDR file has elapsed. This time out can be set by the network configuration software.  
Duplication of the IP address  
9
12  
FDR file not present in the FTP server  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 11. AS-i  
The bus configuration must be modified in the PLC because the profile used by the 4I/4O (S.7.0.F.E) module is different from that of a drive  
(7E).  
4I/4O module wiring: ASI20MT4I4OR  
AS-i  
-
+
O4  
O3  
O2  
O1  
I1  
I2  
I3  
I4  
Q1  
C
C
S+  
S-  
A1  
L1  
Q2  
M1  
3
3. 11. 1. Controlling the Altivar 61 (without using parameter-setting bits)  
This configuration does not include all the As-i option card functions used on the Altivar 38. Below is a list of everything that could be deemed  
economically feasible.  
It is however necessary to assign and configure the logic inputs in the Altivar 61 manually using the HMI keypad or PowerSuite; automatic  
processing is impossible because the ASI20MT4140R module cannot be configured using PowerSuite.  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Implementation of the communication option cards  
3. 11. 1. 1. +/- speed mode  
Control bits  
D3(O)  
D2(O)  
D1(O)  
D0(O)  
Command  
LI4  
LI3  
LI2  
LI1  
- speed  
+ speed  
reverse  
forward  
0
0
1
1
0
0
1
0
1
0
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
Normal  
Stop  
Forward  
"speed maintenance"  
+ speed  
- speed  
0
0
1
0
1
0
1
1
1
0
0
0
"speed maintenance"  
+ speed  
Reverse operation  
Reset  
- speed  
0
0
1
1
0
1
0
1
1
1
1
1
1
1
1
1
Assignment of the Inputs/Outputs  
4 logic inputs used on the terminals, 2-wire control  
LI1: Forward  
LI2: Reverse  
LI3: + speed  
LI4: - speed  
3. 11. 1. 2. 7-speed mode, 1 direction of operation  
Control bits  
D3(O)  
D2(O)  
D1(O)  
D0(O)  
Command  
LI4  
LI3  
LI2  
LI1  
8-spd  
4-spd  
2-spd  
Forward  
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
1
0
1
0
1
0
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
Normal  
Stop  
Not used  
Not used  
Not used  
Not used  
st  
1
speed: LSP+AI  
nd  
2
3
4
5
6
speed: SP2  
speed: SP3  
speed: SP4  
speed: SP5  
speed: SP6  
speed: HSP  
rd  
th  
th  
th  
Forward  
Reset  
th  
7
Assignment of inputs/outputs  
4 logic inputs used on the terminals, 2-wire control  
LI1: Forward  
LI2: 2 preset speeds  
LI3: 4 preset speeds  
LI4: 8 preset speeds  
Note: The application function on the drive is "8-speed" even though with the AS-i mode only 7 are used.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 11. 2. 4-speed mode, 2 directions of operation  
Control bits  
D3(O)  
D2(O)  
D1(O)  
D0(O)  
Command  
LI4  
LI3  
LI2  
LI1  
4-spd  
2-spd  
Reverse  
Forward  
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
Normal  
Stop  
Forward  
st  
1
speed: LSP+AI  
speed: SP2  
nd  
2
3
rd  
speed: SP3  
speed: HSP  
th  
4
st  
1
speed: LSP+AI  
nd  
2
3
speed: SP2  
speed: SP3  
speed: HSP  
Reverse operation  
Reset  
rd  
th  
4
Assignment of inputs/outputs  
4 logic inputs used on the terminals, 2-wire control  
LI1: Forward  
LI2: Reverse  
LI3: 2 preset speeds  
LI4: 4 preset speeds  
3. 11. 3. Managing the terminal outputs (AS-i monitoring bits)  
Mode parameterization bits  
Monitoring bits  
Command  
Names of the AS-i variables  
(not used)  
P3  
x
P2  
x
P1  
x
P0  
x
D3(I)  
D2(I)  
D1(I)  
R2  
D0(1)  
R1  
Example of assignment to the terminal relays  
Example 1:  
D0(I)=1: drive ready for remote control  
D1(I)=1: motor running  
1
1
3. 11. 4. Limitations  
The commands transmitted by the data bits on the AS-i bus, which cannot be reproduced by means of direct wiring, are:  
• Fast stop (0 1 0 0)  
• Stop with DC injection (1 0 0 0)  
• Freewheel stop (1 1 0 0)  
• Fault reset (1 1 1 1)  
In fact, it is not possible to wire directly, for example, bit D2 (0 1 0 0 = fast stop) on an additional logic input of the Altivar 61 and assign to  
it the fast stop function, because each time bit D2 is at 1 but for another command (e.g., 0 1 0 1 = forward - SP2), the motor is stopped  
because the stop function has priority.  
3. 11. 5. Configuring the drive logic I/O  
Please refer to the Programming Guide for information about customizing Lix and Rx assignment.  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Implementation of the communication option cards  
3. 12. Application-specific option cards  
Pump card  
VW3A58210  
This card is continued on the Altivar 61 and its catalog number is VW3A3502. The functions of the two cards  
are identical.  
Multi-motor card  
VW3A58211  
Compatibility can be assured by adding an extended I/O option card VW3A3202 providing access to AI3  
and LO and requires the multi-motors function to be configured manually, because the PowerSuite software  
workshop cannot access data stored on the old option card. To do this, in menu:  
[1.7 APPLICATION FUNCT.] (FUn-) adjust [MULTIMOTORS/CONFIG.] (MMC-).  
Multi-parameter card  
VW3A58212  
This card has not been continued on the Altivar 61H.  
Only the parameter-switching function is integrated on the ATV61 and supports the switching of 3 sets of  
15 selectable parameters.  
[1.7 APPLICATION FUNCT.] (FUn-) then [PARAM. SET SWITCHING] (MLP-)  
For other operating modes (indexing, sequencing functions, etc.), it is necessary to use the Controller Inside  
card.  
Please refer to the Altivar 61 Programming Guide for information about how to use these different functions.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
atv61_migration_en_v1  
2006-04  
Download from Www.Somanuals.com. All Manuals Search And Download.  

PYLE Audio Stereo Amplifier PT 1100 PT3300 User Guide
Radica Games Games 73014 User Guide
RadioLAN Appliance Trim Kit 52TA1472 User Guide
Renesas Computer Hardware REJ06B0732 0100 User Guide
Renesas Network Card PCA7426G02 User Guide
Roberts Gorden Electric Heater TF 120 User Guide
Rockford Fosgate Speaker P1L 1X10 User Guide
Rowenta Iron Precision Steam Iron User Guide
SANRAD Switch I311205 User Guide
Sanus Systems TV Video Accessories AFV48B User Guide