Schneider Electric Marine Instruments EM4000 User Guide

TM  
PowerLogic Series EM4000  
High-Density Meter Installation Guide  
930-134-01-A.00  
11/2013  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Information  
Important Information  
Read these instructions carefully and look at the equipment to become  
familiar with the device before trying to install, operate, service or maintain it.  
The following special messages may appear throughout this manual or on  
the equipment to warn of potential hazards or to call attention to information  
that clarifies or simplifies a procedure.  
The addition of either symbol to a “Danger” or “Warning” safety label indicates that  
an electrical hazard exists which will result in personal injury if the instructions are  
not followed.  
This is the safety alert symbol. It is used to alert you to potential personal injury  
hazards. Obey all safety messages that follow this symbol to avoid possible injury  
or death.  
DANGER indicates an imminently hazardous situation which, if not avoided, will  
result in death or serious injury.  
WARNING indicates a potentially hazardous situation which, if not avoided, can  
result in death or serious injury.  
CAUTION indicates a potentially hazardous situation which, if not avoided, can  
result in minor or moderate injury.  
NOTICE is used to address practices not related to physical injury. The safety  
alert symbol shall not be used with this signal word.  
Please note  
Electrical equipment should be installed, operated, serviced and maintained only by  
qualified personnel. No responsibility is assumed by Schneider Electric for any  
consequences arising out of the use of this material.  
A qualified person is one who has skills and knowledge related to the construction,  
installation, and operation of electrical equipment and has received safety training  
to recognize and avoid the hazards involved.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notices  
FCC Part 15 Notice  
This equipment has been tested and found to comply with the limits for a Class B  
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to  
provide reasonable protection against harmful interference in a residential  
installation. This equipment generates, uses, and can radiate radio frequency  
energy and, if not installed and used in accordance with the instructions, may  
cause harmful interference to radio communications. However, there is no  
guarantee that interference will not occur in a particular installation. If this  
equipment does cause harmful interference to radio or television reception, which  
can be determined by turning the equipment off and on, the user is encouraged to  
try to correct the interference by one or more of the following measures.  
Reorient or relocate the receiving antenna.  
Increase the separation between the equipment and receiver.  
Connect the equipment to an outlet on a circuit different from that to which the  
receiver is connected.  
Consult the dealer or an experienced radio/TV technician for help.  
This Class B digital apparatus complies with Canadian ICES-003.  
FCC Part 68 Notice  
This equipment complies with Part 68 of the FCC rules and the requirements  
adopted by the Administrative Council for Terminal Attachments (ACTA). On the  
side of this equipment is a label that contains, among other information, a product  
identifier in the format US: AAAEQ##TXXXX. If requested, this number must be  
provided to the telephone company.  
This equipment uses the following Universal Service Order Codes (“USOC”) jacks:  
RJ11.  
A plug and jack used to connect this equipment to the premises wiring and  
telephone network must comply with the applicable FCC Part 68 rules and  
requirements adopted by the ACTA. A compliant telephone cord and modular plug  
or compliant modular jack is provided with this product.  
The REN is used to determine the number of devices that may be connected to a  
telephone line. Excessive RENs on a telephone line may result in the devices not  
ringing in response to an incoming call. In most but not all areas, the sum of RENs  
should not exceed five (5.0). To be certain of the number of devices that may be  
connected to a line, as determined by the total RENs, contact the local telephone  
company. The REN for this product is part of the product identifier that has the  
format US: AAAEQ##TXXXX. The digits represented by ## are the REN without a  
decimal point (e.g., 03 is a REN of 0.3).  
If this equipment, Digital Power Meter with Internal Modem, causes harm to the  
telephone network, the telephone company will notify you in advance that service  
may be temporarily discontinued. When advance notice is not practical, the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
telephone company will notify you as soon as possible. You will also be advised of  
your right to file a complaint with the FCC if you believe it is necessary.  
The telephone company may make changes in its facilities, equipment, operations  
or procedures that could affect the operation of this equipment. If this happens, the  
telephone company will provide advance notice in order for you to make necessary  
modifications to maintain uninterrupted service.  
If you experience trouble with this equipment, Digital Power Meter with Internal  
Modem, please contact Schneider Electric at 615-287-3400. If this equipment is  
causing harm to the telephone network, the telephone company may request that  
you disconnect this equipment until the problem is resolved.  
There are no user serviceable parts in this equipment.  
Connection to party line service is subject to state tariffs. Contact the state public  
utility commission, public service commission or corporation commission for  
information.  
If your premises has specially wired alarm equipment connected to the telephone  
line, ensure that the installation of this Digital Power Meter with Internal Modem  
does not disable your alarm equipment. If you have questions about what will  
disable alarm equipment, consult your telephone company or a qualified installer.  
Network Compatibility Notice for the Internal Modem  
The internal modem in meters equipped with this option is compatible with the  
telephone systems of most countries in the world, with the exception of Australia  
and New Zealand. Use in some countries may require modification of the internal  
modem’s initialization strings. If problems using the modem on your phone system  
occur, please contact Schneider Electric Technical Support.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
930-134-01-A.00  
11/2013  
PowerLogicTM EM4000 Series  
Table of Contents  
Table of Contents  
Installing Potential Transformers for Three-Phase Service  
Installing the Sense Voltage and Control Voltage Cables in  
©2013 Schneider Electric All Rights Reserved  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
PowerLogicTM EM4000 Series  
Table of Contents  
930-134-01-A.00  
11/2013  
ii  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Introduction  
This document describes the PowerLogic EM4033 and EM4080 meters, including  
procedures to install and start up the unit, and complete the initial configuration:  
This documentation is intended for those responsible for installing and configuring  
the PowerLogic EM4033 and EM4080 meters. Installers must be qualified  
electricians with knowledge of local and national code requirements. See “Safety  
System Description  
The PowerLogic EM4033 and EM4080 meters support:  
single-phase, 2-wire  
single-phase, 3-wire (network)  
three-phase wye and Delta services  
Depending on how the meters are installed and configured, they can meter 8, 12, or  
24 individual meter points. The PowerLogic EM4033 and EM4080 meters are  
designed for residential, commercial, and industrial use and display the power and  
consumption readings for each measurement point.  
PowerLogic EM4000 series System Specifications  
The PowerLogic EM4000 series system architecture includes:  
single-phase, 2-wire; single-phase, 3-wire (network); three-phase, 4-wire (wye);  
and three-phase, 3-wire (delta) compatibility  
2 control voltage variants: 120V 60Hz and 277V 60Hz  
120/208V, 120/240V and 277/480V configurations, and 347/600V with external  
potential transformers  
up to 8, 12, or 24 individual meter points  
local Ethernet configuration interface via PC and web browser  
Ethernet port for remote reporting  
Modbus RTU serial port, for remote reporting  
serial port for remote display  
2 pulse inputs to connect metering devices  
Table 1 lists the system specifications of the PowerLogic EM4033 and EM4080  
meters.  
©2013 Schneider Electric All Rights Reserved  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Table 1: PowerLogic EM4000 series meter specifications  
Specification  
PowerLogic EM4033 meter  
PowerLogic EM4080 meter  
Dimensions  
Height: 13.125 in. (33.5 cm)  
Width: 12 in. (30.5 cm)  
Depth: 2.125 in. (5.5 cm)  
Height: 13.125 in. (33.5 cm)  
Width: 12 in. (30.5 cm)  
Depth: 2.125 in. (5.5 cm)  
Weight  
8.77 lb (3.98 kg)  
8.77 lb (3.98 kg)  
Sense voltage  
100V to 300V 50/60Hz  
100V to 300V 50/60Hz  
2W+N+Protective Earth Wye  
3W+N+Protective Earth Wye  
3W+Protective Earth Delta  
2W+N+Protective Earth Wye  
3W+N+Protective Earth Wye  
3W+Protective Earth Delta  
Control voltage and current  
North America:  
North America:  
120V 125 mA 60 Hz  
277V 54 mA 60 Hz  
120V 125 mA 60 Hz  
277V 54 mA 60 Hz  
Current transformers  
Measurement Category III  
0.333 V secondary CT  
80 mA secondary CT  
200 A primary CT  
Note: All CTs used with the product  
must be UL recognized/listed.  
Meter burden: 4.04 ohms  
CT burden: 20 ohms  
Part number: METSECT80200  
Note: All CTs used with the product  
must be UL recognized/listed.  
Measurement accuracy  
ANSI C12.20 Class 0.5  
IEC 62053-22 Class 0.5S  
ANSI C12.20 Class 0.5  
IEC 62053-22 Class 0.5S  
(Accuracy compliant when used  
with 0.3% CTs)  
Measurement Canada Approved  
EG07 compliant  
Pulse inputs 1 and 2  
Dry form A and solid-state form A  
compatible  
Dry form A and solid-state form A  
compatible  
Internal 3.3 V pull-up  
Internal 3.3 V pull-up  
Maximum frequency 10 Hz  
Minimum pulse width 20 ms  
Maximum frequency 10 Hz  
Minimum pulse width 20 ms  
Non-volatile memory storage  
Onboard Ethernet port  
Onboard Modbus RTU serial port  
Fuse rating (F1)  
120 days in 15-minute intervals  
10/100 Mb/s  
120 days in 15-minute intervals  
10/100 Mb/s  
RS422 or RS485 19200/9600 Baud  
North America:120V: T125 mA, 250V  
RS422 or RS485 19200/9600 Baud  
North America:120V: T125 mA, 250V  
Environmental  
o
o
Operating temperature  
Operating humidity  
-40 to 70 C  
-40 to 70 C  
5% to 90% non-condensing  
5% to 90% non-condensing  
Usage environment  
Maximum altitude  
Indoor or enclosed outdoor environment  
Indoor or enclosed outdoor environment  
9843 ft (3000 m)  
9843 ft (3000 m)  
Pollution degree  
2
2
Installation Category  
Measurement Category  
II  
II  
III  
III  
2
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                                 
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Front Panel Display  
The PowerLogic EM4033 and EM4080 meters have the following front panel  
features (Figure 1 shows the PowerLogic EM4080 front panel):  
LCD — displays 2 rows of 16 characters for each of the meter points (8, 12, or  
24)  
Display button — cycles through the available information for each of the  
meter points  
Left and right arrow buttons — selects which of the meter points is on the  
display  
Figure 1: PowerLogic EM4080 front panel  
Display  
Select  
PowerLogic  
EM4080  
©2013 Schneider Electric All Rights Reserved  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Figure 2 shows the internal view of thePowerLogic EM4033 and EM4080 meters.  
Figure 2: PowerLogic EM4033 and PowerLogic EM4080 internal view  
6
8
9
10  
7
1
5
1
11  
12  
13  
4
14  
15  
16  
3
2
1
17  
1
Legend:  
1 Cover screw location  
2 Meter point input connector  
3 Cable connector  
4 Mounting keyhole  
5 Ingress punch-outs  
6 Earth stud  
6 Sense voltage terminal block  
8 Control voltage terminal block  
9 Fuse  
10 Control voltage jumper  
11 RTU interface  
12 Display  
13 Remote display connector  
14 Serial RS232  
15 Ethernet port  
16 Pulse in terminal blocks  
17 Pulse out connector  
4
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Safety Precautions  
Carefully observe these safety instructions.  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
Apply appropriate personal protective equipment (PPE) and follow  
safe electrical work practices. See NFPA 70E.  
Only qualified electrical workers should install this equipment. Such  
work should be performed only after reading this entire set of  
instructions.  
The equipment must be accessible to authorized personnel only.  
Equipment must be installed in areas where access can be  
restricted.  
NEVER work alone.  
Before performing visual inspections, tests, or maintenance of this  
equipment, disconnect all sources of electric power. Assume that all  
circuits are live until they have been completely de-energized,  
tested, and tagged. Pay particular attention to the design of the  
power system. Consider all sources of power, including the  
possibility of backfeeding.  
Turn off all power supplying the meter and the equipment in which  
it is installed before working on it.  
Always use a properly rated voltage sensing device to confirm that  
all power is off.  
Before closing all covers and doors, carefully inspect the work area  
for tools and objects that may have been left inside the equipment.  
Successful equipment operation requires proper handling,  
installation, and operation. Neglecting fundamental installation  
requirements can lead to personal injury as well as damage to  
electrical equipment or other property.  
NEVER bypass external fusing.  
NEVER short the secondary of a Potential Transformer (PT).  
Always short the secondary of a current transformer prior to  
disconnecting current input loads.  
Failure to follow these instructions will result in death or serious  
injury.  
Electrical Standards Compliance  
Use the unit only in accordance with the electrical power rating  
The unit is only to be installed by a qualified electrician  
Initial installation of the unit must be inspected by the local electrical Inspection Authority  
Install the unit in compliance with the following local and national electrical codes:  
Canada: Canadian Electrical Code, Part I, CSA C22.1  
United States: National Fire Protection Association (NFPA) 70; US National  
Electrical Code  
Elsewhere: International Electrotechnical Commission (IEC) 364, Part 1-7  
Ensure that the unit is properly earthed  
If the equipment is installed or used in a manner other than that specified in this  
document, it may void your warranty or impair the protection of the equipment.  
©2013 Schneider Electric All Rights Reserved  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Installation  
This section contains the following installation topics:  
Pre-Installation  
The pre-installation checklist and site planning must be performed before installing  
the equipment at the site.  
Receiving  
The equipment required for each PowerLogic EM4000 meter installation includes:  
high-density meter (PowerLogic EM4033 or PowerLogic EM4080)  
For the PowerLogic EM4033 and PowerLogic EM4080, one 12-ft (4-m) AMP  
cable with one 50-pin connector supplied with each unit  
CD and meter configuration software, this installation manual and an installation  
record form  
When you receive your order, verify that the items listed above are included with  
the shipment, and visually inspect them for damage. If any parts are missing or  
damaged, contact your Schneider Electric representative.  
Pre-Installation Checklist  
The installer must provide the following information, tools, and equipment before  
proceeding with the installation:  
certified current transformers for metering (not supplied)  
an appropriate 15-Amp maximum circuit breaker or a fused disconnect switch  
for the type of panel  
current/voltage meter to test the phasing of panels  
RJ45 Ethernet patch cable  
2
4-wire 14 AWG (1.63 mm ) cable for three-phase wye connected circuits, or 3-wire 14  
2
AWG (1.63 mm ) cable for a single-phase wye connected circuits  
small flat-head screwdriver  
#2 Phillips screwdriver  
crimping tool  
18 AWG butt splice connector  
wire strippers  
four 1-inch (25 mm) #8 mounting screws suitable for selected mounting surface  
Site Planning  
1. Determine the number of PowerLogic EM4000 series meters to be installed and  
ensure adequate space. For clearances, see Figure 3 on page 8.  
2. Determine the number of Ethernet drops required, and ensure they are installed  
before installing the PowerLogic EM4033 and EM4080 meters.  
6
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
3. Determine the number and types of meters or monitors required (single-phase,  
network, or three-phase).  
4. Determine the model number and correct sense voltage based on the voltage  
label on the top right side of the unit.  
Access to Power and Lighting  
The installation site must be supplied with access to the main electrical panel and  
any sub-panels. Portable or permanent lighting must be available to provide the  
installers with a clear view of the equipment and of the installation environment.  
Each installation may vary depending on physical site restrictions.  
Installation Procedures  
This section provides information about activities that must be performed to install  
the PowerLogic EM4033 and EM4080 meters in a single-phase 2-wire,  
single-phase 3-wire (network), or three-phase 4-wire application. The installation  
procedures must be performed in the following order:  
a.  
b.  
Mounting the PowerLogic EM4000 meter  
Figure 3 shows the general mounting layout for metering 120V/208V wye services,  
and Figure 4 shows the general mounting layout for metering 347V/600V wye  
services.  
1. Remove the front cover from the meter by removing the four screws with a #2  
Phillips screwdriver. Retain the cover and screws for later re-installation.  
2. Mount the PowerLogic meter on the wall and secure it by inserting a screw in  
each mounting keyhole and tightening the screws.  
3. Mount the shorting block enclosure on the wall as shown in Figures 3 and 4.  
Secure it by inserting a screw in each mounting keyhole and tightening the  
screws.  
4. Install the conduit for voltage and current connections.  
In Figure 3, the meter is powered and takes its sense voltage directly from a  
breaker within the panel.  
©2013 Schneider Electric All Rights Reserved  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Figure 3: 120V Mounting Layout, Dimensions and Clearances  
11.0 in  
6.0 in  
27.9 cm  
15.2cm  
(EM4033)  
2
2
1
5
1
10.67 in  
27.1cm  
2
2
1
1
4.0 in  
10.2 cm  
4
3
8
6
4
7
8
9
Legend:  
1. Mounting keyhole  
2. Cover screw location  
3. Electrical distribution panel  
4. CT conduit  
5. Voltage conduit  
6. Shorting block enclosure  
7. Shorting jumper  
8. Shorting block  
9. DIN rail  
8
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Installing Potential Transformers for Three-Phase Service Greater  
Than 277V  
Potential transformers are required when metering services greater than the rated  
voltage input of the meter. Potential transformers are used to reduce the  
line-to-neutral voltage of the service to 120V. The accuracy class should be 0.3%  
or better, with a burden rating of 30VA.  
For applications in Canada, Measurement Canada approved potential transformers  
are required. Measurement Canada requires an accuracy class of 0.3% or better,  
with a 150VA rating.  
NOTE: Potential transformer burden depends on the control voltage source. If  
control voltage is provided separately (not derived from the metered voltage), then  
lower transformer burden may be acceptable. Contact your local Schneider Electric  
representative for details.  
Mount the potential transformer enclosure between the supply voltage and the  
PowerLogic meters as shown in Figure 4. Transformer configuration must be Y||Y  
(wye-wye).  
In Figure 4, the meter is powered from the potential transformers that are fed from a  
breaker within the 600Y/347V panel. The CT cable is connected to the shorting  
enclosure before connecting to the CTs in the panel.  
©2013 Schneider Electric All Rights Reserved  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Figure 4: Typical three-phase 347V installation  
C
X1  
X2  
X1  
X2  
X1  
X2  
H1  
H1  
H1  
B
A
N
H2  
H2  
H2  
6
5
7
8
9
4
C
B
A
N
3
2
Z
10  
11  
1
Legend:  
1
2
3
4
5
6
7
8
9
Shorting block enclosure  
Shorting block  
Distribution panel  
Current transformer  
Load breaker  
11  
Meter breaker  
Transformer enclosure  
PowerLogic meter  
Load  
12  
13  
Shorting block detail  
10 Current input cable  
11 Shorting jumper  
12 Shorting block  
13 DIN rail  
10  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Installing the Sense Voltage and Control Voltage Cables in Wye and  
Delta Services  
The sense voltage (A, B, C, N) provides phase voltages for metering. The  
configuration depends on the type of service being metered:  
The PowerLogic EM4033 and EM4080 meters are shipped from the factory with a  
control voltage jumper that can be used to connect the control voltage input and the  
sense voltage inputs to provide control voltage to the unit. The following procedures  
explain how to connect the sense voltage inputs for each of the service types.  
2
For a single-phase panel, use a 3-wire (red, black, white), 14 AWG (1.63 mm ),  
o
o
90 C (194 F) cable. For a three-phase panel, use a 4-wire (red, black, blue, white),  
2
o
o
14 AWG (1.63 mm ), 90 C (194 F) cable. For a Delta service, use a 3-wire (red,  
2
o
o
black, blue), 14 AWG (1.63 mm ), 90 C (194 F) cable. Metallic, flexible armored  
cable (BX cable) is recommended for commercial installations as shown in Figure 5  
The PowerLogic meters must be connected to the sense voltage and control  
voltage through a properly rated disconnect that disconnects all line and neutral  
wires, so it can be powered down. The disconnect must be located within easy  
reach of the meter operator, and must be labeled as such. Opening the disconnect  
or breaker is the disconnect device. For multiple PowerLogic meter installations,  
the same disconnect can be used to power all meters, and must be labeled for all  
meters it supplies power to. The disconnect device must meet IEC 60947-1, IEC  
60947-3 and/or comply with the local electrical code.  
©2013 Schneider Electric All Rights Reserved  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
To install the control voltage cable in a 208Y/120V or 120/240V application:  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
Apply appropriate personal protective equipment (PPE) and follow  
safe electrical work practices. See NFPA 70E.  
This equipment must only be installed and serviced by qualified  
electrical personnel.  
Turn off all power supplying this equipment before working on or  
inside equipment.  
Always use a properly rated voltage sensing device to confirm  
power is off.  
Replace all devices, doors and covers before turning on power to  
this equipment.  
The meters must be connected to the sense voltage and control  
voltage through a properly rated voltage disconnect (not shown in  
the wiring diagrams).  
Failure to follow these instructions will result in death or serious  
injury.  
NOTE: If the circuit breaker panel does not designate phase A, phase B and phase  
C feeds, make your own designation and use it for the rest of the installation.  
1. Before connecting the sense voltages, turn off the power to the circuit being  
connected.  
2. Always use a properly rated voltage sensing device to confirm power is off.  
3. Connect the sense voltages phase A, B, C, and N leads from the voltage  
disconnect to the meter as described in Figure 5 on page 13 and Figure 6 on  
NOTE: The phase wiring sequence A, B, C between the PowerLogic EM4000  
meter and the panel must match or the measurement readings will be wrong.  
4. If more than one meter is being installed, repeat this procedure for each  
additional meter.  
12  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
For a single-phase panel with the 120V variant of the meter:  
Connect meter terminal A to the voltage disconnect phase A (red wire)  
Connect meter terminal B to the voltage disconnect phase B (black wire)  
Connect meter neutral terminal to neutral bar in the voltage disconnect panel  
(white wire)  
Connect earth wire to earth post using lug provided  
Meter terminal C is not connected  
Install power supply shorting jumpers (see Figure 5)  
The PowerLogic EM4033 and EM4080 meters are rated for direct input of 120V to  
277V 60Hz phase potential. When metering services greater than 120V, the meter  
is powered from a separate 120V instrument transformer. Figure 7 shows the wiring  
of the control voltage transformer for a 277V service.  
Figure 5: PowerLogic EM4000 meter in a 120/240V single-phase connection  
2
3
4
1
7
6
5
8
Legend:  
1 BX cable  
2 Earth  
3 Phase B (black)  
4 Shorting jumper  
5 Sense voltage terminal block (J3)  
6 Neutral (white)  
7 Phase A (red)  
8 0.75-inch (1.9-cm) strain relief  
©2013 Schneider Electric All Rights Reserved  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
For a 208Y/120V three-phase wye panel with the 120V variant of the meter:  
Connect meter terminal A to the voltage disconnect phase A (red wire)  
Connect meter terminal B to the voltage disconnect phase B (black wire)  
Connect meter terminal C to the voltage disconnect phase C (blue wire)  
Connect meter neutral terminal to neutral bar in the voltage disconnect panel  
(white wire)  
Connect earth wire to earth post using lug provided  
Install power supply shorting jumpers (see Figure 6)  
Figure 6: PowerLogic EM4000 meter 208Y/120V three-phase wye service  
connection  
2
3
4
5
1
8
7
6
9
Legend:  
1
2
3
4
5
6
7
8
BX cable  
Earth  
Phase C (blue)  
Phase B (black)  
Shorting jumper  
Sense voltage terminal block (J3)  
Neutral (white)  
Phase A (red)  
9 0.75-inch (1.9-cm) strain relief  
14  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
For a 480Y/277V three-phase wye panel with the 277V variant of the meter:  
Connect meter terminal A to the voltage disconnect phase A (red wire)  
Connect meter terminal B to the voltage disconnect phase B (black wire)  
Connect meter terminal C to the voltage disconnect phase C (blue wire)  
Connect meter neutral terminal to neutral bar in the voltage disconnect panel  
(white wire)  
Connect earth wire to earth post using lug provided  
From the auxiliary power transformer, connect 120V auxiliary power to AUXA  
and AUXN on the meter (see Figure 7)  
Figure 7: PowerLogic EM4000 meter 480Y/277V three-phase wye service  
connection  
AUX_N  
AUX_A  
FROM PANEL  
C
B
A
N
A
N
©2013 Schneider Electric All Rights Reserved  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
For a 600Y/347V or higher three-phase wye panel with potential transformers  
with the 120V variant of the meter:  
Connect meter terminal A to the voltage disconnect phase A (red wire)  
Connect meter terminal B to the voltage disconnect phase B (black wire)  
Connect meter terminal C to the voltage disconnect phase C (blue wire)  
Connect meter neutral terminal to neutral bar in the voltage disconnect panel  
(white wire)  
Connect earth wire to earth post using lug provided  
Install power supply shorting jumpers (see Figure 8)  
NOTE: For the wiring of the potential transformers, see Figure 4.  
Figure 8: PowerLogic EM4000 meter 600Y/347V or higher three-phase wye  
service with potential transformers connection  
2
3
4
5
1
8
7
6
9
Legend:  
1
2
3
4
5
6
7
8
BX cable  
Earth  
Phase C (blue)  
Phase B (black)  
Shorting jumper  
Sense voltage terminal block (J3)  
Neutral (white)  
Phase A (red)  
9 0.75-inch (1.9-cm) strain relief  
16  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Delta service metering  
To use the PowerLogic EM4000 meter in a Delta service, the line-to-line voltage  
from the Delta service must be reduced to 120V line-to-line using appropriate  
potential transformers. Metering a Delta service requires only two potential  
transformers, and only two CTs for phase A and C.  
For a three-phase Delta panel with the 120V variant of the meter:  
Connect meter terminal A to the voltage disconnect phase A (red wire)  
Connect meter terminal C to the voltage disconnect phase C (blue wire)  
Connect meter neutral terminal to meter terminal B (black wire)  
Connect earth wire to earth post using lug provided (see Figure 9)  
Figure 9: PowerLogic EM4000 meter three-phase Delta service connection  
2
3
4
5
1
8
9
7
6
Legend:  
1
2
3
4
5
6
7
8
BX cable  
Earth  
Phase C (blue)  
Phase B (black)  
Shorting jumper  
Sense voltage terminal block (J3)  
J3-B to J3-N shorting wire  
Phase A (red)  
9 0.75-inch (1.9-cm) strain relief  
©2013 Schneider Electric All Rights Reserved  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Installing the Current Transformers  
The two models of PowerLogic EM4000 meter use current transformers (CTs) with  
different secondary outputs. The PowerLogic EM4033 meter uses split-core 0.333V  
CTs (see Figure 10), and the PowerLogic EM4080 meter uses 80mA CTs only (see  
Figure 11) and is typically used where accuracy is important and long secondary  
CT wiring is required (up to 300 feet [91.44 meters]). The PowerLogic EM4080  
meter can also use a 5A CT if a 5A converter has first been installed.  
Current transformers connect to the PowerLogic EM4033 and PowerLogic EM4080  
meters through the 50-conductor CT cable provided with the meter. Table 2  
describes the CT wire pairs and the cable color scheme for each meter point. You  
can also find this information on the inside of the meter’s outer cover.  
Each CT has an X1 (positive) and X2 (neutral) wire pair and uses butt-splice  
connectors to attach the CT to a specific meter wire pair. The direction of the  
energy flow is indicated on the CT by: a label (“This side towards source”); an arrow  
that points away from the source; or a stamp/label indicating which side is H1 (H1  
side faces toward the source).  
CT shorting blocks are recommended for all CT installations. CTs measuring live  
current must either be connected to the PowerLogic meter via the 25-pair CT cable,  
or the secondary output of the CTs must be shorted together. Open-circuit CTs  
may generate a hazardous voltage and could damage equipment or cause  
personal injury.  
18  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Figure 10: PowerLogic EM4033 split-core 0.333V current transformer  
DANGER  
2
1
3
T
H
IS  
SI  
D
E
T
OW  
A
R
D
S
S
O
UR  
C
E
Legend:  
1 Source  
2 Energy flow  
3 Load  
4 X1  
5 X2  
5
4
©2013 Schneider Electric All Rights Reserved  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Figure 11: PowerLogic EM4080 mA current transformer  
DANGER  
3
H1  
2
1
Legend:  
1 Source  
2 Energy flow  
3 Load  
4 X1  
5 X2  
5
4
Installing the CTs on the PowerLogic EM4033 and PowerLogic EM4080  
Do not apply power until you have made these connections and followed all of the  
instructions below:  
Connect all CTs to the appropriate circuits  
Connect the CTs to the cables  
Connect the cables to the PowerLogic EM4000 meter  
To install the mA current transformers on the PowerLogic EM4080 or the 0.333V  
current transformers on the PowerLogic EM4033, follow these steps:  
20  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
Turn off all power supplying this equipment before working on or  
inside the equipment.  
Always use a properly rated voltage sensing device to confirm the  
power is off.  
NEVER open circuit a CT; use the shorting block to short circuit the  
leads of the CT before removing the connection from the meter.  
Do not crimp the insulation when making the wire connections.  
Failure to follow these instructions will result in death or  
serious injury.  
1. Connect the 50-pin connector to the PowerLogic connector located at the  
bottom side of the unit, and secure it in place with the retaining clips.  
2. Feed the free end of the cable through the bottom left of the meter enclosure.  
This cable is made up of twisted-pair wires for connecting the individual CTs to the  
metered points. The color codes for the X1 (positive) and X2 (neutral) connections for  
each CT are listed in Table 2 on page 24.  
NOTE: The direction of the energy flow is indicated on the CT.  
3. Turn off the power feed to the panel where the CTs are being installed. Always  
use a properly rated voltage sensing device to confirm power is off.Feed the CT  
cable into the panel through an appropriate punch-out with an approved strain  
relief.  
4. Strip the plastic sheaths on the cable to an appropriate length to expose the wire  
pairs. Cut and strip the CT leads and wire pair leads to an appropriate length.  
Crimp the CT leads to the wire pairs for each meter point.  
5. Connect the X1 lead of the CT to the X1 lead of the cable, then connect the X2  
lead of the CT to the X2 lead of the cable (see Table 2).  
6. When using solid-core CTs, remove the feed wire from the circuit breaker, place  
the CT over the wire, and reconnect to the circuit breaker. Ensure that the arrow  
on the CT label is pointing in the direction of the energy flow (toward the load).  
7. When using split-core CTs, separate the halves of the CT and place the CT over  
the wire to the circuit breaker. Ensure that the CT is facing the source as shown  
on the label. Install cable ties to ensure that the CT halves are held together  
securely.  
8. Repeat steps 4 to 7 for the remaining CTs.  
Installing 5A Converters and CTs on the PowerLogic EM4080  
When both low-current (200A and 400A) and high-current (600A or higher) circuits  
need to be measured with the same PowerLogic meter, converters are available to  
allow the use of Measurement Canada approved 5A CTs with the appropriate  
current rating. 5A CT converters transform the 5A maximum output from a standard  
CT to the 80mA maximum of the PowerLogic meter.  
The 5A side of the converter is the black and red wire pair, and the 80mA side of  
the converter is the black and white wire pair.  
NOTE: It is recommended that 5A converters and shorting devices be installed in a  
sealable metal enclosure.  
©2013 Schneider Electric All Rights Reserved  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
To connect the 5A CT to the converter on the PowerLogic EM4080, follow these  
steps:  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
Turn off all power supplying this equipment before working on or  
inside the equipment.  
Always use a properly rated voltage sensing device to confirm the  
power is off.  
NEVER open circuit a CT; use the shorting block to short circuit the  
leads of the CT before removing the connection from the meter.  
Do not crimp the insulation when making the wire connections.  
Failure to follow these instructions will result in death or  
serious injury.  
1. Connect the X1 lead of the 5A CT to the shorting device.  
2. Connect the X2 lead of the 5A CT to the shorting device.  
3. Connect the X1 lead (red) from the 5A side of the converter to the CT X1 lead on  
the shorting device.  
4. Connect the X2 lead (black) from the 5A side of the converter to the CT X2 lead  
on the shorting device.  
5. Connect the X1 lead (white) from the 80mA side of the converter to the X1 lead  
within the 25 pair cable for the selected meter point ID listed in Table 2.  
6. Connect the X2 lead (black) from the 80mA side of the converter to the X2 lead  
within the 25 pair cable for the selected meter point ID listed in Table 2  
Figure 12 shows a 5A CT connected to the converter.  
22  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Figure 12: PowerLogic EM4080 5A CT connection to converter  
6
7
4
8
5
9
2
3
1
11  
10  
12  
Legend:  
1 Shorting block  
2 X2  
3 Energy flow  
4 5A CT  
5 X1  
6 Red (X1)  
7 5A Converter  
8 X1 to 25-pair cable  
9 X2 to 25-pair cable  
10 Enclosure  
11 Black (X2)  
12 Shorting bar  
©2013 Schneider Electric All Rights Reserved  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Table 2: PowerLogic EM4000 meter CT color pair identification  
1-phase, 24 meter points  
Network- or 1-phase, 12 meter points  
3-phase, 8 meter points  
Meter point ID  
(meter point #-  
probe #)  
Connect  
X1 CT  
lead to:  
Connect  
X2 CT  
lead to:  
Meter point ID  
(meter point #-  
probe #)  
Connect  
X1 CT  
lead to:  
Connect  
X2 CT  
lead to:  
Meter point ID  
(meter point #-  
probe #)  
Connect  
X1 CT  
lead to:  
Connect  
X2 CT  
lead to:  
1-1  
Black  
Black  
Black  
Red  
Green  
White  
Red  
1-1  
1-2  
2-1  
2-2  
3-1  
3-2  
4-1  
4-2  
5-1  
5-2  
6-1  
6-2  
7-1  
7-2  
8-1  
8-2  
9-1  
9-2  
10-1  
10-2  
11-1  
11-2  
12-1  
12-2  
Black  
Black  
Black  
Red  
Green  
White  
Red  
1-1  
1-2  
1-3  
2-1  
2-2  
2-3  
3-1  
3-2  
3-3  
4-1  
4-2  
4-3  
5-1  
5-2  
5-3  
6-1  
6-2  
6-3  
7-1  
7-2  
7-3  
8-1  
8-2  
8-3  
Black  
Black  
Black  
Red  
Green  
White  
Red  
2-1  
3-1  
4-1  
Green  
White  
Orange  
Brown  
Yellow  
Blue  
Green  
White  
Orange  
Brown  
Yellow  
Blue  
Green  
White  
Orange  
Brown  
Yellow  
Blue  
5-1  
Red  
Red  
Red  
6-1  
Black  
Black  
Black  
Black  
Green  
Green  
Green  
Blue  
Black  
Black  
Black  
Black  
Green  
Green  
Green  
Blue  
Black  
Black  
Black  
Black  
Green  
Green  
Green  
Blue  
7-1  
8-1  
9-1  
10-1  
11-1  
12-1  
13-1  
14-1  
15-1  
16-1  
17-1  
18-1  
19-1  
20-1  
21-1  
22-1  
23-1  
24-1  
Yellow  
Blue  
Yellow  
Blue  
Yellow  
Blue  
White  
White  
Orange  
Brown  
Yellow  
White  
White  
Orange  
Yellow  
Brown  
Orange  
White  
Brown  
White  
White  
Orange  
Brown  
Yellow  
White  
White  
Orange  
Yellow  
Brown  
Orange  
White  
Brown  
White  
White  
Orange  
Brown  
Yellow  
White  
White  
Orange  
Yellow  
Brown  
Orange  
White  
Brown  
Green  
Green  
Blue  
Green  
Green  
Blue  
Green  
Green  
Blue  
Brown  
Orange  
Red  
Brown  
Orange  
Red  
Brown  
Orange  
Red  
Red  
Red  
Red  
Red  
Red  
Red  
Blue  
Blue  
Blue  
Yellow  
Blue  
Yellow  
Blue  
Yellow  
Blue  
24  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Connecting the Communications  
Connections for communications using the Ethernet port or Modbus RTU port are  
described in this section.  
Connecting the Ethernet Cable  
If the Ethernet port is used to report data, an RJ45 patch cable is required to  
connect the Ethernet port to the local Ethernet network.  
1. Route the cable through the slot in the PowerLogic EM4000 meter enclosure.  
2. If the local network automatically assigns IP addresses through a DHCP server,  
the PowerLogic EM4000 meter will be able to report using its factory default IP  
settings. If the local network is configured for static IP addresses, refer to the  
PowerLogic EM4000 meter Configuration Guide for instructions on how to  
configure default static IP addresses.  
Connecting the Modbus RTU Communications  
If the Modbus port is used to report data, an RS422/RS485 serial cable is required  
to connect the Modbus RTU port to the local Modbus network.  
1. Route the cable through the slot in the PowerLogic EM4000 meter enclosure.  
2. Depending on the position of the PowerLogic EM4000 meter in the Modbus  
network as shown in Figure 13, set the DIP switches as follows:  
PowerLogic meter location  
Head end  
S1  
On  
Off  
On  
S2  
Off  
Off  
On  
S3  
Off  
Off  
On  
S4  
Off  
Off  
Off  
Intermediate  
Tail end  
3. Refer to the PowerLogic meter Configuration Guide for instructions on how to  
configure the baud rate, parity settings, and Modbus base address for the  
RS485 RTU communications.  
Figure 13: Modbus wiring diagram  
©2013 Schneider Electric All Rights Reserved  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Connecting Pulse Inputs  
Each PowerLogic meter has two pulse inputs that can be used to count and report  
pulses generated by another meter (pulsing device).  
Connect the output of the pulsing device to one of the two pulse input terminal  
blocks in the PowerLogic meter, as shown in Figure 2. Each terminal block has a  
negative terminal pin on the right, and a positive terminal pin on the left. The pulse  
inputs are compatible with both dry and solid-state form A contacts, 10 Hz  
(maximum), 20 ms pulse width (minimum).  
When the pulsing device provides dry relay contacts, the PowerLogic meter pulse  
inputs are not polarity-sensitive. When the pulsing device provides solid-state  
form A outputs, the negative terminal from the source device must be connected to  
the negative terminal of the PowerLogic meter pulse in terminal block.  
The pulsing device can be located up to 1,000 feet away from the PowerLogic  
meter with 22 AWG twisted pair wire.  
Start-Up Sequence  
Use the following procedure to start up the PowerLogic EM4000 meter.  
1. Ensure that all CT and sense voltage wiring is securely installed.  
2. Remove all tools from the work area.  
3. Re-install all cover plates and equipment covers.  
4. Power up the meter. The LCD on the front panel of the meter indicates the  
operating status of the unit as follows:  
a.  
b.  
Initial power up message “PowerLogic EM4000”  
After the internal configuration is complete, the display shows default information  
for the first meter.  
Manually Testing Communications  
This procedure clears the meter memory, manually tests the communications from  
the PowerLogic EM4000 meter, and updates the meter clock. To force the meter to  
send data, follow these steps:  
1. Press and hold the Display button for 5 to 7 seconds until the diagnostics mode  
is displayed, then release.  
2. If communicating via Ethernet, press the Display button until "Local IP Address"  
appears on the display.  
a.  
If the IP address is 169.254.0.10, the meter has not found a DHCP server. As a  
result, the meter will use its default IP configuration and may not be able to report.  
See the PowerLogic EM4000 meter Configuration Guide for instructions on how to  
program default IP addresses.  
b.  
If the IP address is not 169.254.0.10, the meter has acquired an IP address from  
the local network, and will be able to report data and synchronize time.  
3. Press the Display button until the “Send” command appears on the display.  
4. Press the left or right arrow button to manually force the PowerLogic EM4000  
meter to report metering data using the Ethernet or modem connection. This  
clears data from the PowerLogic EM4000 meter memory, and ensures the time  
is set correctly.  
26  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Display Navigation  
The PowerLogic EM4000 meter has three buttons to control the information  
presented on the LCD. The display has a normal and a diagnostics mode. The  
PowerLogic EM4000 meter starts in normal mode, and enters diagnostics mode  
when the Display button is pressed and held for 5 seconds. To adjust the contrast,  
hold down the Display button, and use the right and left arrow buttons to increase  
and decrease the contrast respectively.  
Normal Mode  
In Normal mode, the Display button scrolls through the information for each meter.  
The left and right arrow buttons select the previous or next meter points  
respectively. The following information is available:  
Real Energy Delivered kWh D  
Real Energy Received kWh R  
Real Power Watts  
Reactive Energy Delivered kVarhD  
Reactive Energy Received kVarhR  
Reactive Power Var  
Peak Demand Peak W (Watts)  
In Normal mode, the right and left arrow buttons scroll the display from meter points  
1 to 8, 1 to 12, or 1 to 24, depending on your configuration.  
Diagnostics Mode  
Diagnostics mode is accessed by pressing and holding the Display button for 5  
seconds. In Diagnostics mode, pressing the Display button will scroll through the  
following additional information:  
Send data command  
CT Primary value and Real Power Watts per phase  
Current (Amps) per phase  
Power factor (pf) per phase  
Phase angle (degrees) per phase  
Voltage per phase  
Local IP address  
Reset factory default IP address command  
Verify  
Badge #  
Date and time (UTC)  
In Diagnostics mode, the right and left arrow buttons scroll the display from meter 1  
to 8, 1 to 12, or 1 to 24, depending on your configuration. When the local IP  
address is shown on the LCD, use the right and left arrow buttons to scroll through  
the following information:  
Remote host server IP address  
Time server IP address  
Default IP address  
Default NetMask  
©2013 Schneider Electric All Rights Reserved  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Default gateway  
PPP user name  
Phone number  
AT command string  
Alternate phone number  
Unit serial number  
Firmware build number  
Ethernet port MAC address  
Firmware revision  
Potential transformer ratio  
Recording the Meter Map  
The final step in the installation process is to complete the Installation Record, and  
record the mapping of the meters to the wired points. A copy of Figure 14, which is  
organized to resemble a breaker panel, is provided with each PowerLogic EM4000  
meter, and is to be completed and delivered to your system administrator.  
28  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Figure 14: Installation Record (sample shown)  
©2013 Schneider Electric All Rights Reserved  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Maintenance  
Do not perform any operation or maintenance procedures that are not described in this  
product documentation. Visually inspect the equipment yearly and ensure it is free of dust or  
other particles. If necessary, wipe with a clean cloth. Individual components are not  
user-serviceable and must be returned to Schneider Electric for repair.  
Fuse Replacement  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
Apply appropriate personal protective equipment (PPE) and follow  
safe electrical work practices. See NFPA 70E.  
Turn off all power supplying this equipment before working on or  
inside equipment.  
Always use a properly rated voltage sensing device to confirm the  
power is off.  
Replace all devices, doors and covers before turning on power to  
this equipment.  
Failure to follow these instructions will result in death or serious  
injury.  
1. Turn off all sources of power before attempting to replace the fuse. Always use  
a properly rated voltage sensing device to confirm the power is off.  
2. Remove the outer cover from the unit.  
3. Locate fuse F1 at the top left corner inside the unit.  
4. Remove the fuse cover, then remove the fuse from the holder as shown in  
Figure 15.  
5. Replace fuse F1 with a fuse that meets the specifications listed in Table 1 on  
6. Replace the fuse cover.  
7. Re-install the cover and turn on the power source.  
Figure 15: Replacing the fuse  
3
Legend:  
2
1
2
3
Fuse holder  
Fuse  
Fuse cover  
1
30  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
930-134-01-A.00  
11/2013  
PowerLogicTM Series EM4000  
Installation Guide  
Regulatory Compliance  
The PowerLogic EM4000 meter must be installed by a qualified electrician with  
knowledge of local installation regulations. Initial installation of the unit, and any  
subsequent modification to the unit, must be inspected by the local electrical  
inspection authority.  
The PowerLogic EM4000 meter complies with the standards listed in Table 3.  
Table 3: Regulatory Compliance  
Discipline  
Regulatory and industry standard  
nd  
Standards  
UL certified to IEC/EA/UL/CSA 61010-1 2 Edition  
CSA-C22.2 No. 61010-1-04  
Emissions (EMC)  
FCC Part 15 Class B, ICES-003 EN55022, IEC 6100-4-5  
ANSI/TIA968-A: 2002  
Surge power/telephone lines  
Equipment servicing and access  
The information in this section must be considered as a mandatory requirement,  
and must be strictly adhered to when installing and operating PowerLogic EM4033  
and EM4080 meters.  
Access to equipment  
The equipment must be accessible to authorized personnel only. Equipment must  
be installed in areas where access can be restricted.  
Servicing the equipment  
No preventive maintenance is required on any of the equipment. Visually inspect  
the equipment yearly and ensure it is free of dust or other particles. If necessary,  
wipe with a clean cloth.  
Component servicing  
Individual components are not user-serviceable, and must be returned to Schneider  
Electric for repair. If an equipment fault occurs, do not attempt to repair the faulty  
component.  
All maintenance activities should be performed by qualified personnel only. Do not  
perform any operating or maintenance procedures that are not described in the  
product documentation provided by Schneider Electric.  
Graphical symbols  
Table 4 shows the graphical symbols that appear on the equipment.  
©2013 Schneider Electric All Rights Reserved  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
PowerLogicTM Series EM4000  
Installation Guide  
930-134-01-A.00  
11/2013  
Table 4: Graphical symbols that appear on equipment  
Symbol  
Description  
Indicates the supply wire protective earth, also known as  
chassis ground, for the primary ground.  
This symbol indicates a replaceable fuse.  
32  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
930-134-01-A.00  
11/2013  
PowerLogicTM EM4000 Series  
Index  
Index  
current transformers 2  
dimensions 2  
Numerics  
347V installation  
fuse rating 2  
typical three-phase configuration 10  
installation in a 120/208V three-phase wye panel with  
5A converters and current transformers  
120V variant 14  
install 21  
installation in a 277/480V three-phase wye panel with  
120V variant 15  
installation in a 347/600V or higher three-phase wye panel  
5A current transformers  
install 25  
A
with 120V variant 16  
audience 1  
installation in a single-phase panel with 120V variant 13  
installation in a three-phase Delta panel with 120V variant  
internal view 4  
maximum altitude 2  
maximum pulse per second 2  
measurement accuracy 2  
minimum pulse width 2  
mounting 7  
NVM storage 2  
C
compliance  
electrical safety 5  
connect Modbus 25  
control voltage and current  
meter 2  
current transformers  
install 20  
meter 2  
onboard Ethernet port 2  
onboardModbus port 2  
operating humidity 2  
operating temperature 2  
pollution degree 2  
pulse inputs 1 and 2 2  
sense voltage 2  
D
delta service  
install sense voltage and control voltage cables 11  
dimensions  
meter 2  
usage environment 2  
weight 2  
meter map  
recording 28  
minimum pulse width  
meter 2  
E
electrical safety compliance 5  
equipment  
access 31  
servicing 31  
equipment servicing 31  
mounting  
meter 7  
F
fuse rating  
N
meter 2  
NVM storage  
meter 2  
I
install  
O
5A converters and current transformers 21  
5A current transformers 25  
potential transformers 9  
installation 6  
installation procedures  
overview 7  
Installing 21  
onboard Ethernet port  
meter 2  
onboard Modbus port  
meter 2  
operating humidity  
meter 2  
operating temperature  
meter 2  
M
maximum altitude  
P
meter 2  
pollution degree  
maximum pulse per second  
meter 2  
measurement accuracy  
meter 2  
meter  
meter 2  
potential transformers  
install 9  
pre-installation 6  
pulse inputs 27  
pulse inputs 1 and 2  
control voltage and current 2  
CT color pair identification 24  
©2013 Schneider Electric All Rights Reserved  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PowerLogicTM EM4000 Series  
Index  
930-134-01-A.00  
11/2013  
meter 2  
S
sense voltage  
meter 2  
sense voltage and control voltage cable installation  
wye and delta service 11  
servicing equipment 31  
site planning 6  
site preparation  
lighting 7  
power 7  
start-up sequence 26  
U
usage environment  
meter 2  
W
weight  
meter 2  
wye service  
install sense voltage and control voltage cables 11  
34  
©2013 Schneider Electric All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PowerLogicTM Series EM4000  
High-Density Meter Installation Guide  
PowerLogic is a trademark or registered trademark of Schneider Electric in France, the USA and  
other countries. Other trademarks used are the property of their respective owners.  
This product must be installed, connected and used in compliance with prevailing standards  
and/or installation regulations. As standards, specifications and designs change from time to time,  
always ask for confirmation of the information given in this publication.  
Schneider Electric  
35 rue Joseph Monier  
92500 Rueil-Malmaison, France  
930-134-01-A.00 11/2013  
©2013 All Rights Reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Rangemaster Cooktop RI60 User Guide
Raypak Outdoor Storage ASME CODE User Guide
RIDGID Planer TP1300LS User Guide
Rival Slow Cooker Smart SetTM User Guide
Roland Water Pump VC 30HD User Guide
Runco Home Theater System Home Theater Projection System User Guide
Samsung CRT Television BN68 02076L 00 User Guide
Samsung Portable DVD Player DVD L75 L70 User Guide
Sanyo Cell Phone PRO 200 User Guide
Sea Sea Digital Camera 860G User Guide