Samsung Air Conditioner AD18B1C09 User Guide

ROOM AIR CONDITIONER  
INDOOR UNIT  
AD26B1C13  
AD18B1C09  
OUTDOOR UNIT  
UD26B1C2  
UD18B1C2  
Manual  
SERVICE  
AIR CONDITIONER  
CONTENTS  
1. Installation  
2. Disassembly and Reassembly  
3. Troubleshooting  
4. Exploded Views and Parts List  
5. Refrigerating Cycle Block Diagrams  
6. Wiring Diagrams  
7. Schematic Diagrams  
E DB98-05645A(1)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1-2 “Pump down” Procedure  
1. Confirm that both the 2-way and 3-way valves are set to  
the open position.  
(1) Remove the valve stem caps.  
(2) Be sure to use a hexagonal wrench to operate the Gas  
side valve stems.  
2-Way Valve  
2. Operate the unit for 10 to 15 minutes.  
3. Stop operation and wait for 3 minutes, then connect the  
charge set to the service port of the 3-way valve.  
(1) Connect the charge hose with the push pin to the ser-  
vice port.  
Cap  
4. Air purging of the charge hose.  
(1) Open the low-pressure valve on the charge set slightly  
to air purge from the charge hose.  
3-Way Valve  
5. Set the liquid side 2-way valve to the closed position.  
6. Operate the air conditioner at the cooling cycle and stop  
operation immediately after setting the 3-way valve to the  
closed position when the gauge indicates 0 kg/cm2G.  
If the unit can not be operated at the Cooling Mode(weater  
is rather cool), operate the unit at the Trubo Mode.  
So that the unit can be operated.  
7. Disconnect the charge set, and mount the both 3-way  
valve’s stem nuts and the service port cap.  
Relocation of the air conditioner  
Refer to this procedure when the unit is relocated.  
1. Carry out the pump down procedure  
(refer to the details of ‘pump down’).  
2. Remove the power cord.  
3. Disconnect the assembly cable from the  
indoor and outdoor units.  
5. Disconnect the pipe connected to the out-  
door unit.  
At this time, cover the valve of the outdoor  
unit and the other pipe using a cap or vinyl  
plug to avoid foreign material entering.  
6. Make sure you do not bend the connection  
pipes in the middle and store together with  
the cables.  
4. Remove the flare nut connecting the indoor  
unit and the pipe.  
At this time, cover the pipe of the indoor  
unit and the other pipe using a cap or vinyl  
plug to avoid foreign material entering.  
7. Move the indoor and outdoor units to a new  
location.  
8. Remove the mounting plate for the indoor  
unit and move it to a new location.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Disassembly and Reassembly  
Stop operation of the air conditioner and remove the power cable before repairing the unit.  
2-1 Indoor Unit  
No  
1
Parts  
Procedure  
Remark  
Front Grille  
1) Stop the air conditioner operation and block the  
main power.  
2) Separate tape of front panel upper.  
3) Contract the second finger to the left, and right  
handle and pull to open the inlet grille.  
4) Take the left and right filter out.  
*Taking off the deodorizing filter.  
5) Loosen one of the right fixing screw and sepa-  
rate the terminal cover.  
6) Loosen three fixing screws of front grille.  
7) Pull the upper left and right of discharge softly  
for the outside cover to be pulled out.  
8) Pull softly the lower part of discharge and push  
it up.  
Caution;  
Assemble the front panel and fix the  
hooks of left and right.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
No  
2
Parts  
Procedure  
Remark  
Electrical Parts  
(Main PCB)  
1) Do 1”above.  
2) Take all the connector of PCB upper side out.  
(Inclusion Power cord)  
3) Separate the outdoor unit connection wire from  
the terminal block.  
4) If pulling the Main PCB up. it will be taken out.  
Assy Tray Drain.  
1) Do 1”, “2”, above.  
3
Separate the drain hose from the extension  
drain hose.  
2) Pull tray drain out from the back body.  
Heat Exchanger  
1) Do 1” and “2”, “3”, above.  
4
2) Loosen two fixing earth screws of right side.  
3) Separate the connection pipe.  
4) Separate the holder pipe at the rearside.  
5) Loosen the three fixing screws of right and left  
side.  
6) Lifting the heat exchanger up a little to push the  
up side for separation from the indoor unit.  
Fan Motor and  
Cross Fan  
1) Do 1”, “2”, ”3”, “4”, above.  
5
2) Loosen the fixing two screws and separate the  
motor holder.  
3) Loosen the fixing screw of fan motor.  
(By use of M3 wrench)  
4) Separate the fan motor from the fan.  
5) Separate the fan from the left holder bearing.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-2 Outdoor Unit  
No  
1
Parts  
Procedure  
Remark  
<UD26B1C2>  
Cabinet  
1) Turn off the unit and remove the power cable.  
2) Remove the top cover.  
3) Remove the control box cover.  
4) Unplug the ass'y cable.  
5) Remove the cabi-side.  
6) Remove the cabi-front.  
* When you assemble the parts, check if the  
each parts and electric connectors are fixed  
firmly.  
<UD18B1C2>  
<UD26B1C2>  
2
Fan Motor  
&
Propeller Fan  
1) Do Procedure “1” above.  
2) Remove the nut flange.  
(Turn to the right to remove as it is a left turned  
screw)  
3) Disassemble the propeller fan.  
<UD18B1C2>  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Troubleshooting  
3-1 Items to be checked first  
1) The input voltage should be rating voltage ±10% range.  
The airconditioner may not operate properly if the voltage is out of this range.  
2) Is the link cable linking the indoor unit and the outdoor unit linked properly?  
The indoor unit and the outdoor unit shall be linked by 5 cables.  
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number  
of cables. Otherwise the airconditioner may not operate properly.  
3) When a problem occurs due to the contents illustrated in the table below it is a symptom not  
related to the malfunction of the airconditioner.  
NO  
1
Operation of air conditioner  
Explanation  
The STD operation indication LED blinks when a  
power plug of the indoor unit is plugged in for the first time.  
It indicates power is on. The LED stops blinking if the operation  
ON/OFF button on the remote control unit is pushed.  
2
In a COOL operation mode, the compressor does not  
operate at a room temperature higher than the setting  
temperature that the IN DOOR FAN should operate.  
In a HEAT operation mode, the compressor does not  
operate at a room temperature lower than the setting  
temperature that indoor fan should operate.  
In happens after a delay of 3 minutes when the compressor is  
reoperated. The same phenomenon occurs when a power is on.  
As a phenomenon that the compressor is reoperated after a delay  
of 3 minutes, the indoor fan is adjusted automatically with refer-  
ence to a temperature of the air blew  
The speed of the indoor fan is set to LL in DRY mode.  
Fan speed is 5 steps is selected automatically in AUTO mode.  
3
4
5
Fan speed setting is not allowed in AUTO or DRY mode.  
Compressor stops operation intermittently in DRY mode.  
Compressor operation is controlled automatically in DRY mode  
depending on the room temperature and humidity.  
Compressor of the outdoor unit is operating although it is  
turned off in a HEAT mode.  
When the unit is turned off while de-ice is activated, the com-  
pressor continues operation for up to 9 minutes (maximum) until  
the deice is completed.  
6
7
Timer LED only of the indoor unit lights up and the  
air conditioner does not operate.  
Timer is being activated and the unit is in ready mode.  
The unit operates normally if the timer operation is cancelled.  
The compressor and indoor fan stop intermittently in HEAT  
mode.  
The compressor and indoor fan stop intermittently if room temper-  
ature exceeds a setting temperature in order to protect the com-  
pressor from overheated air in a HEAT mode.  
8
9
Indoor fan and outdoor fan stop operation intermittently in  
a HEAT mode.  
The compressor operates in a reverse cycle to remove exterior ice  
in a HEAT mode, and indoor fan and outdoor fan do not operate  
intermittently for within 20% of the total heater operation  
The compressor stops intermittently in a COOL mode or DRY  
mode, and fan speed of the indoor unit decreases.  
The compressor stops intermittently or the fan speed of the indoor  
unit decreases to prevent inside/outside air frozen depending on  
the inside/outside air temperature.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
4) Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details  
on the display panel.  
Display  
Self Diagnosis  
NO  
Standard Timer Nature Power  
(GREEN)  
X
X
X
X
X
X
X
X
X
Restore from power failure (input initial power)  
1
2
3
4
Indoor unit Room sensor Error (open or short)  
Indoor unit heat exchanger temperature sensor Error (open or short)  
Indoor fan malfunctioning (for speed is below 450rpm)  
In case that the communication between the indoor unit and outdoor unit is not made  
for 60 seconds  
(GREEN)  
X
X
5
X
X
Outdoor sensor Error (open or short)  
6
7
(GREEN)  
(GREEN)  
X
X
X
- Outdoor sensor  
- Pipe sensor A, B  
The malfunction ot 4way valve in heat mode operation.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-2 Checking and Testing Operations (Outdoor Unit)  
To complete the installation, perform the following checks and tests to ensure that  
the air conditioner is operating correctly.  
1. Review all the following elements in the installation:  
• Installation site strength  
• Piping connection tightness to detect any gas leakages  
• Connection wiring  
• Heat-resistant insulation of the piping  
• Drainage  
• Earthing wire connection  
• Correct operations (follow the steps below)  
• Room select switch in the indoor unit  
2. Apply the power to the outdoor unit.  
- Check the fuse (250V~, 5A) : The fuse is open when the power line (L1, N2) is short.  
3. Check the connection of PCB communication of outdoor unit.  
OUTDOOR UNIT  
(Check whether the red LED of outdoor unit PCB is flickering.)  
• The communication lamp is flickering after the display of each  
unit on the outdoor PCB display part. (every one second).  
LED is not flikering, if the connection is bad or the room select  
switch is located in the wrong position.  
a
- LED lamp (red) flickering after display of A (0.5 sec)  
- LED lamp (red) flickering after display of b (0.5 sec)  
- LED lamp (red) flickering after display of C (0.5 sec)  
Note : PCB switch “C” is used for triple split multi air conditioner.  
TEST OPERATING  
A
C
B
b
C
Result : If all of three units display lamps are flickering, the connection  
wires and the room option connections are good.  
A : PCB display  
B : Red LED  
C : PCB switch  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the lamp is not flickering, check as follows:  
A. Check the display part of indoor unit of each unit (A,B) after outdoor unit PCB switch S/W-A is on.  
A. Check the status of each unit indoor room select switch.  
A. (Adjust the select switch suitable to the unit A, B.)  
A. - A unit : STANDARD LED on, TIMER LED flickering  
A. - B unit : STANDARD LED on, TIMER and NATURE LED flickering  
A. - C unit : STANDARD LED on, TIMER and NATURE, POWER LED flickering (In case of triple  
split multi air conditioner)  
STANDARD  
TIMER  
NATURE  
POWER  
UNIT  
A
B
C
Lamp ON  
Lamp OFF  
Lamp Flasher  
4. Check the test operation status by pressing the PCB switch  
4. S/W-A and S/W-B of outdoor unit.  
4. • Check the operation status by pushing the switch one at time.  
4. • Perform the test operation only for the unit selected last.  
4. • Check the pipe pressure and the other operation status during the test operation.  
4. • Check items when the error occurs during the test operation (each unit)  
- Check there is enough refrigerant.  
- Check pipe connections.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISPLAY  
EXPLANATION  
REMARK  
Be sure to check after applying the power to the outdoor unit.  
Outdoor sensor error (Short/Open)  
Outdoor A cond pipe sensor error (Short/Open)  
Outdoor B cond pipe sensor error (Short/Open)  
Outdoor C cond pipe sensor error (Short/Open)  
A unit test operation error  
Display when the test operation finishes.  
When the pipe temperature difference of indoor unit  
(pipe temperature 4 minutes before - Actual pipe temperature)  
is less than 5˚C.  
B unit test operation error  
C unit test operation error  
Be sure to check during the test operation.  
A unit test communication error  
B unit test communication error  
C unit test communication error  
A,B,C unit all communication error  
A room test operation OK  
Display of power application.  
Display 4 minutes after the COMP is on.  
B room test operation OK  
C room test operation OK  
Communication unit number display : A unit  
Communication unit number display : B unit  
Normal operation  
Unit A,B and C are changed every one second.  
The communication lamp is flickering after display of each unit.  
(possibility to check the communication status)  
During the test operation the unit under test is on and off every 0.25s.  
Communication unit number display : C unit  
(In case of triple split multi air conditioner)  
Refrigerant leaks  
High temperature of the A cond  
High temperature of the B cond  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3 Fault Diagnosis by Symptom  
3-3-1 No Power (completely dead)-Initial diagnosis  
1) Checklist :  
(1) Is input voltage normal?  
(2) Is AC power linked correctly?  
(3) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC)  
2) Troubleshooting procedure  
Remove power cord and plug in  
again in approx. 5 seconds  
Is operation lamp blinking?  
NO  
YES  
Does operation start when  
YES  
NO  
YES  
Is DC voltage of PCB  
display normal?  
Normal  
run/stop button on the remote  
controller unit pushed?  
NO  
NO  
Is transmission display of the  
remote controller unit blinking?  
YES  
Is "beep"sound heard from the  
main unit?  
Refer to remote control  
unit fault diagnosis  
Is rating voltage ±10%  
range applied to the  
primary side (~,~)  
of the “BD71”  
Replace  
PCB display  
NO  
NO  
YES  
Is DC voltage of the PCB module  
normal?  
Check linkage between  
power cord and  
terminal tap  
NO  
Replace PCB module.  
Check fuse  
YES  
5VDC Is voltage of #60 (indoor fan)  
of the micom normal?  
DC12V  
YES  
Is voltage at SS71(indoor fan)  
Is 14~18VAC appear in  
the secondary side (+, -)  
of “BD71”  
DC5V  
10ms  
NO  
YES  
NO  
YES  
NO  
Check connections  
compressor 4-way  
valve, outdoor fan and  
indoor fan.  
Replace RY71,  
RY73, RY72 and  
SS71  
Replace  
SMPS PARTS  
Is output voltage of ICO2 normal?  
Is voltage at #52 terminal of the  
micom normal?  
NO  
Replace ICO2  
YES  
Check PCB pattern.  
Replace main PCB.  
10ms  
YES  
NO  
Is voltage output terminal of  
TLP180(PC02) normal?  
Are voltage at #48 and #49 of the  
micom normal?  
NO  
YES  
OK  
NO  
Replace resonator (X301)  
250ns  
Replace TLP180(pc02)  
YES  
Is operation normal?  
NO  
Replace micom  
YES  
OK  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-2 When the power voltage is not available  
1) Inspection items  
(1) Is the power voltage is normal? (The rating voltage ±10% range)  
(2) Is the power cord is correctly connected and is the contact good?  
(3) Does the sound “ting” come out with the operation lamp (green) flickering when the  
power is applied?  
If it is not flickering, do inspect and repair in accordance with the following inspection  
sequence.  
2) Inspection sequence  
Apply the power  
Is the operation lamp of  
YES  
NO  
YES  
YES  
indoor unit on when the  
operation /stop button of  
remote controller is  
pressed?  
No trouble  
(normal)  
Is the operation lamp flickering with the  
sound of “ting”?  
NO  
NO  
Is the communication  
signal of remote  
controller surely sent  
and received ?  
NO  
Check of the installation  
method and electrical circuit  
Check of remote  
controller  
Is the outdoor power connected normally?  
YES  
YES  
Is there no problem  
between the connector of  
Assy display PCB and the  
receiving module?  
YES  
Normal  
Replace the fuse (250V, 3.15 A)  
Is the fuse (F701, 250V, 3.15A) of PCB open?  
NO  
NO  
Replace of  
Ass'y display PCB  
NO  
NO  
NO  
Is the voltage at Socondary side of transformer  
of PCB (TN71)? (AC15V~AC25V)  
Transformer is out of  
order - replace  
YES  
Repair and replace the power  
source rectifying diode (D101-  
D105) and KA7812.  
Is the output voltage of voltage regulator  
IC (KA 7812) DC 10V and 12V?  
YES  
Is the output voltage of electrostatic voltage  
regulator IC (KA 7805) DC 4.5 V - 5.5 V?  
KA7805 is out of order - replace  
YES  
Replace the main PCB of indoor unit  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-3 No Power (Outdoor unit)  
1) Inspection items  
(1) Á Is the power source normal (The rating Voltage ±10% range)?  
(2) Is the outdoor power connected normally? ((1) of terminal : L, (2) of terminal : N,  
(3) of terminal : communication) ?  
(3) Check whether the display of outdoor PCB(SEG1) is shown in the order of A- B - C when the  
power is applied.  
If the display (SEG 1) is not shown the inspection and repair shall be performed in the sequence  
of the following:  
2) Inspection sequence  
Put the power off and put it on after  
5 seconds.  
Check the  
communication of  
PCB and whether  
the LED 1 is contin-  
uously flickering.  
Is the display of PCB shown in the  
sequence of A-B-C?  
YES  
YES  
Normal of  
outdoor PCB  
NO  
NO  
Reinstall the power cord and  
communication line with the  
reference of installation manual.  
NO  
NO  
Are the power cord ((1) L, (2) N) and  
communication line (3) of outdoor terminal  
block connected correctly?  
YES  
After watching the display of  
PCB board, assemble the  
color and shape of housing  
correctly as follows:  
Is the terminal of PCB terminal (RY71, 72, 73)  
are assembled in the correct position?  
Replace the  
transformer  
YES  
Is the fuse open? (F701)  
NO  
YES  
BLK  
BLK  
Replace the fuse  
(F701) 250V 3.15A.  
WHT  
WHT  
Measurement of resistance  
of power transformer  
Are they as follows?  
1st side 190 ~ 210  
2nd side 0.9 ~ 1.1Ω  
Insert the primary side of power transformer  
in the terminal GT01 and then is the voltage  
of secondary side normal? (AC 15V- AC 25V)  
NO  
NO  
RED  
RED  
YES  
YES  
YES  
NO  
Replace the fuse F101  
(250V 2 A).  
Is the fuse (F101, 250V 2 A) blown out?  
Assemble the transformer  
in the normal way.  
NO  
Check and Replace the rectifying  
diode of power side  
(D101 - D104) and KA 7812.  
Check whether the output voltage of  
IC01 (KA 7812) is DC 12V.  
YES  
NO  
Check whether the output voltage of  
IC02 (KA 7805) is DC 5V.  
Replace the IC 02 (KA7805)  
YES  
Replace the outdoor unit Ass'y main PCB.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-4 When the fan of indoor unit does not operate  
1) Inspection items  
(1) Is the power voltage normal?  
(2) Is the connector of indoor fan with the good contact? (CN73)  
(3) Is the soldering status of running condenser (CR71) with the good contact?  
(4) Is connector of the Hall IC with the good contact (CN 43) ?  
(5) Is the indoor fan rotating when it is under operation mode?  
(6) Is the FAN LED (green) flickering when the indoor fan stalled (for more than 15 seconds) and  
the trouble condition of speed detecting part?  
Put the power off and put it on after 5 seconds.  
YES  
NO  
If the power is not available  
(indoor unit), item no 3-3-1.  
Is the operation lamp flickering for 3 minutes and  
then put off?  
YES  
Error occurs after the  
indoor unit fan motor is  
rotating for 15 seconds?  
(FAN Lamp flickering)  
NO  
YES  
If the operation /stop button of the remote controller  
is pressed, is the operation lamp flickering and then is  
the indoor fan rotating after 5~6 seconds?  
Replace of indoor unit PCB Ass'y.  
YES  
YES  
YES  
NO  
Is AC 120V and higher shown across the indoor fan  
connector (CN73) ?  
Replacement of  
indoor unit fan motor.  
NO  
Is the type of MICOM (IC 04) Pin no.  
63 old type ?  
120Hz  
YES  
Is the pin no. 12 of IC 06 (KID 65003)  
the old type?  
NO  
NO  
Replace the IC 06 (KID 65003)  
and SS71(G3MB202pl).  
120Hz  
YES  
Is the pin no 25 of MICOM  
the old type?  
Replace Q401 (Ksc 945Y).  
Replace the indoor unit PCB Ass'y due to the  
Micom defect.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-5 When the outdoor unit fan does not operate  
1) Inspection items  
(1) The outdoor unit fan motor operates only when the operating conditions are satisfied and is selected  
by the RY74(LOW) and PY75(HI) to rotate.  
(2) Is the power voltage normal?  
(3) Is the contact of outdoor unit fan motor (CN 73) good?  
(4) Is the winding resistance of outdoor unit fan motor 58at Hi side and 143at low side?  
(5) The outdoor unit fan motor operates with Hi at over 28°C and low at below 26°C during the cooling  
operation, and operates with Hi at below 14°C and low at over 15°C during the heating operation.  
2) Inspection sequence  
Apply the power to the outdoor unit and operate the indoor unit.  
NO  
Is the indoor unit under operating conditions?  
Normal (operation off)  
Normal  
YES  
YES  
YES  
Is it operating in the High speed?  
NO  
Is the voltage shown across the connector (1)(3) ((1)(5))  
Check the winding resistance of outdoor unit fan  
(the rating voltage ±10% range)?  
motor winding resistance Replace  
NO  
YES  
YES  
Contact bad of RY 74(Low), RY 75(High)  
Is no. 11 ( 12) of IC 06 at low? (DC 0.7 V)  
Replace  
NO  
Defect of IC06 output  
Is pin no. 48(49) of IC 04 (MICOM) at High (DC 5 V)?  
Replace  
NO  
YES  
Is the outdoor unit fan motor under the operating  
conditions?  
Defect of IC 04(MICOM) - replace the IC 04  
or PCB assy  
NO  
Normal  
* Operating specification of the FAN of outdoor unit  
(1) When the COMP is under the COMP ON condition during the cooling and heating operation,  
Hi or LOW operation is selected according to the temperature condition of outdoor room.  
(2) When A room and B room are mixed to operate , it is always under low operation.  
(3) Perform the comp ON/OFF control in the dry mode.  
(4) When it is under the operation of anti-freezing, overload protection, defrost operation, it may  
be Low, high or Off.  
(5) Hi = High speed, Low = Low speed  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-6 When the UP/DOWN Louver Moter Does Not Operate. (Initial Diagnosis)  
1) Checklist :  
(1) Is input voltage normal?  
(2) Is the UP/DOWN louver motor properly connected with the connector (CN61)?  
2) Troubleshooting procedure  
Remove power cord and plug in again in approx. 5 seconds.  
YES  
Is operating lamp blinking?  
Check as in the procedure "No Power parts".  
Refer to page 11.  
YES  
YES  
NO  
NO  
Does operation start when swing button of  
the remote control unit pushed?  
Normal  
NO  
Micom (IC04) is faulty.  
Driver IC05 (KID65003) is faulty.  
Voltage at pin #33 ~ #36 of micom (ICO4) change?(Squarewave)  
YES  
Volatge at pin #13, #14, #15, #16 of IC05 (KID65003)  
change?(Squarewave)  
YES  
UP/DOWN louver motor is faulty.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-7 If Operation By Remote Control Unit Is Impossible. (Initial Diagnosis)  
1) Troubleshooting procedure  
Remove power cord and plug in again approx. 5 Seconds  
NO  
Is operation lamp blinking?  
Check as in the procedure “NO Power parts”.  
Refer to page 11.  
YES  
YES  
“ sound heard from the indoor unit when ON/OFF  
button on the remote control unit pushed?  
Normal  
NO  
YES  
NO  
Voltage of battery less than 2.5V (Remote Control Unit)?  
Replace battery.  
LCD is faulty.  
NO  
LCD display status of REMOCON normal?  
YES  
NO  
Transmission display lamp (  
ON/OFF button on the remote control unit pushed?  
) blinking when  
Replace button.  
Micom is faulty.  
YES  
NO  
NO  
Voltage at PIN #30 of Remocon Micom change?  
YES  
Voltage at collecter of Q601 or Q602 change?  
Q601(C4375Y) or Q602(C1623Y) is faulty.  
IR LED(CL-1L5EU) is faulty.  
YES  
NO  
Voltage at pin #26 of micom (IC04) change (INDOOR UNIT)?  
Receiver module is faulty.  
YES  
Micom (IC04) is faulty.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-8 When the 4 way valve (A,B) is not operating  
1) Inspection items  
(1) Are the 4 way valve A and B under the operating conditions?  
(When the COMP A (4 way valve A ) and COMP B (4 way valve B) are on during the  
heating operating)  
(2) Is the power voltage normal?  
(3) Is the connecting of 4 way valve A (CN 75) and B (CN 76) good?  
2) Inspection sequence  
Put off the outdoor unit power and put it on again after 5 seconds.  
Select the heating operation of A(B) room by the remote controller.  
NO  
Has 3 minutes passed after selection of A(B) room heating?  
Keep 4 way valve off.  
Normal  
YES  
YES  
YES  
Is the 4 way valve A(B) on?  
NO  
Is the voltage shown across the 4 way valve A(B) connector  
(CN 75, CN 76) ?  
Defect of RY 76 (RY 77) contact and coil  
Replace the Relay  
NO  
YES  
YES  
Is the pin no 47(46) of IC 04 ( MICOM) at high (DC 5V) ?  
Defect of IC 06 (IC 07 ) output Replace  
NO  
Defect of IC 04(MICOM) - replace the IC 04  
or PCB assy  
Is the 4 way valve A (B) under operating conditions?  
NO  
Normal  
*4 way valve operating conditions  
(1) During the defrost control, put the 4 way valve A(B) off.  
(2) During the heating operation put the 4 way valve A(B) on.  
(3) The changeover of heating to cooling : put the 4 way valve off immediately (in case of B and C room).  
(4) The changeover of cooling to heating : it is on after 170 seconds delay.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-3-9 When the compressor does not operate  
1) Inspection items  
(1) Is the COMP A under the operating conditions? (cooling operating of A, B(C) room)  
(2) Is the power voltage normal? (the rating voltage ±10% range)  
(3) Are the connector connection of COMP A(RY 72, 73) and B(RY 71) good?  
(4) The COMP A(B) is operated on and off in accordance with the operating conditions of indoor  
unit of A (B. C) room.  
2) Inspection sequence  
Apply the outdoor power and operate the indoor unit A(B, C)  
in the cooling mode.  
NO  
Normal (comp A (B) off)  
Keep Comp A (B) off  
Normal  
Is the comp A under the operating condition?  
YES  
NO  
Has 3 minutes passed COMP A(B) after the power initial  
and COMP on/off  
YES  
Is comp A (B) on?  
YES  
*Refer to the power measuring terminal  
NO  
YES  
Defect of comp A (B) and running condenser  
Is the voltage (the rating voltage ±10% range) shown  
across the terminal of Comp A(B) power applied?  
Replace  
NO  
YES  
Defect of Ry 72, 73 (Comp B) and Ry 71(comp A)  
Is the voltage of pin no. 14, 13( 15) at low  
(DC 0.7V)?  
contact and coil Replace  
NO  
YES  
YES  
Defect of IC 06 output  
Is the voltage of pin no. 50, 51 (52) of IC 04 (micom) at  
high (DC 5V)?  
Replace  
NO  
Defect of Ic 04 (micom)  
Is comp A (B ) under the operating condition?  
Replace  
NO  
Normal (comp A (B ) off)  
* Comp A (B ) operating conditions  
(1) Comp A : Comp on /off control in accordance with the A room during the heating and cooling  
indoor unit operation  
(2) Comp B : Comp on /off control in accordance with the B(C) room during the heating and cooling  
indoor unit operation  
BLK  
RY72  
(4)  
(4)  
(3)  
(3)  
BLK  
WHT  
RED  
WHT  
RED  
* Comp A(B ) power measuring terminal  
(1) Comp A measuring ; RY 73 (4) ´ RY 72 (4)  
(2) Comp B measuring ; RY 71 (4) ´ RY 72 (4)  
(3) Power input ; RY 72 (3) ´ RY 73(3)  
RY71  
RY73  
(4)  
(3)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-4 Set up the Model option  
The Method for Setting up the model option with remocon  
• It is necessary to set up option code after replacing the main-PCB as a service parts.  
Make sure that you can set up the option of code the remote controller after you replace the main  
PBA otherwise, the unit won’t be working properly and all LED lamps on display will be flickering.  
Step 1 : Preparing the remocon to main PCB option set  
1st  
Remove the battery from the remocon.  
2nd Press the temperature raise/down button simultaneously  
and insert the battery again.  
3rd Make sure the remocon display shown as  
.
Step 2 : Second stage preparation of the remocon option set.  
Note ; In case the wrong letter has been selected, continue to press the button until the correct letter appears.  
1st  
2nd Every time the ! and & button, “ ” and “ ” each continue to appear.  
If the first stage number “ ” appears on the display, proceed to the second stage.  
3rd  
Whenever pressing the @, #, $, %, ^, *, (, ), 1, 2 button, the number increase from  
0~9(0123456789) and A, b, C, d, E, F each time.  
! If the first number is , it is correct otherwise press  
until  
appear.  
@ When pressing the  
button  
button  
button  
button  
button  
~
~
~
~
~
appear on the display,  
select one of them.  
# When pressing the  
appear on the display,  
appear on the display,  
appear on the display,  
appear on the display,  
select one of them.  
$ When pressing the  
select one of them.  
% When pressing the  
select one of them.  
^ When pressing the  
select one of them.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
! If the first number is , it is correct otherwise press  
until  
appear.  
@ When pressing the  
button  
button  
button  
button  
button  
~
~
~
~
~
appear on the display,  
select one of them.  
# When pressing the  
appear on the display,  
appear on the display,  
appear on the display,  
appear on the display,  
select one of them.  
$ When pressing the  
select one of them.  
% When pressing the  
select one of them.  
^ When pressing the  
select one of them.  
Step 3 : Reconfirming option set after completion  
(in case of ex. 000000-1700b7)  
After pressing  
After pressing  
selector for the  
selector for the  
mode, the display shown as  
mode, the display shown as  
.
.
Step 4 : Pressing the ON/OFF button (  
)
When pressing the operation ON/OFF key with the  
direction of remote controller for unit, the sound “Ding” or “Diriring” is heard and the first  
LED lamp on the left side is flickering at the same time, then the input of option is complet-  
ed. (If the diriring sound isn’t heard, try again pressing the ON/OFF button.)  
Step 5 : Unit operation test-run  
First, Remove the battery from the remote controller.  
Second, Re-insert the battery into the remote controller.  
Third, Press ON/OFF key with the direction of remote controller for set.  
• Error Mode  
1st  
If all lamps of indoor unit are flickering, Plug out and plug in again and pressing ON/OFF key to retry.  
2nd  
If the unit is not working properly or all lamps are continuously flickering after setting the option code, see  
if the correct option code is set up for it’s model.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
<Table of the option code>  
MODEL  
OPTION CODE  
015773-100373  
015223-10020C  
AD26B1C13  
AD18B1C09  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MEMO  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Exploded Views and Parts List  
4-1 Indoor Unit  
18  
18-6  
18-6-1  
18-1  
18-4  
18-5  
18-3  
24  
16  
18-2  
17  
13  
13-4  
13-2  
12  
13-3  
13-1  
14  
15  
10  
11  
8
25  
20  
22  
9
23  
19  
6
5
7
4
21  
3
2
1
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I
Parts List  
Q’TY  
AD18B1C09  
No.  
CODE NO  
Description  
REMARK  
AD26B1C13  
1
2
DB64-00085A  
DB63-00064B  
DB95-00287K  
DB63-00067A  
DB92-00031L  
DB67-00051A  
DB67-00032A  
DB63-00083A  
DB94-00020A  
DB60-20011A  
DB31-00071B  
DB32-00020A  
DB93-01223A  
DB93-00319B  
DB65-00046A  
DB93-00268A  
2202-000780  
DB32-00037A  
DB39-00147A  
DB94-00056E  
DB94-00104A  
DB61-00165A  
DB70-00036A  
DB94-00058F  
DB94-00062E  
DB66-00127B  
DB66-00128A  
DB66-00128B  
DB63-00082A  
DB95-20138A  
DB31-10129A  
DB61-40251A  
DB67-60030A  
DB96-01123K  
DB96-01123J  
DB94-40003A  
DB93-00861B  
DB70-00114A  
DB63-00226A  
GRILLE AIR INLET  
GUARD-AIR FILTER  
FILTER CLEANER ASS´Y  
COVER TEMINAL  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
6
1
1
1
1
1
1
-
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
6
1
1
1
1
1
-
3
4
5
ASS´Y PANEL  
6
SPACER EVAP LOW  
SPACER EVAP UP  
7
8
COVER U BEND  
9
ASS´Y FAN CROSS  
BOLT SPECIAL  
10  
11  
MOTOR FAN IN  
12  
THERMISTOR WIRE ASS´Y  
ASS’Y CONTROL IN  
ASS´Y PCB MAIN  
13  
13-1  
13-2  
13-3  
13-3-1  
13-3-2  
13-4  
14  
TERMINAL BLOCK ASS´Y  
ASS´Y PCB DISPLAY  
C CERAMIC,MLC-AXIAL  
MODULE REMOCON  
CONNECT WIRE PCB  
ASS´Y BACK BODY(RIGHT SIDE)  
ASS´Y HOLDER MOTOR  
HOLDER PIPE  
15  
16  
17  
PLATE HANGER  
18  
ASS´Y TRAY DRAIN(RIGHT SIDE)  
ASS´Y DRAIN HOSE  
BLADE H  
18-1  
18-2  
18-3  
18-4  
18-5  
18-6  
18-6-1  
19  
BLADE V,A  
BLADE V,B  
SCREEN SAFETY WIRE  
ASS´Y MOTOR STEPPING  
MOTOR STEPPING; GSP 24RW  
HOLDER SENSOR  
20  
SPRING SENSOR  
21  
ASS’Y CYCLE IN(EVAPORATOR)  
1
1
1
1
1
22  
23  
24  
25  
ASS´Y BEARING  
ASS´Y REMOCON  
1
1
1
1
PLATE-KNOCKOUT  
COVER TERMINAL BLOCK  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-2 Outdoor Unit  
4-2-1 UD26B1C2  
12  
15  
11  
6
5
16(16-1~16-7)  
7
10  
8
4
13(13-1~13-6)  
1
3
17  
2
9(9-1~9-2)  
14(14-1~14-4)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I
Parts List  
Q’TY  
No.  
CODE NO  
Description  
Specification  
REMARK  
UD26B1C2  
1
2
DB90-00075D  
DB90-20207A  
DB67-50067A  
DB31-00095A  
DB61-20093A  
DB63-30027C  
DB94-50041D  
DB90-10574B  
DB90-40120B  
DB63-10434B  
DB63-10433B  
DB90-00742A  
DB96-01356K  
DB63-30110J  
48D135IU1EL  
DB60-30018A  
DB60-30028A  
DB63-10165D  
DB63-20002A  
DB73-00067A  
DB35-00015H  
DB99-00224A  
DB99-00225A  
DB99-00226A  
DB99-00222A  
DB95-00243C  
DB99-00223A  
DB95-00243D  
DB32-00025B  
DB93-01232A  
2301-001379  
2501-001237  
DB26-10070A  
DB61-00585A  
DB61-00584A  
DB65-40072F  
PD-UD18B1-01  
DB95-00329A  
ASSY CABI FRONT  
ASSY BASE OUT  
FAN PROPELLER  
MOTOR FAN  
ASS’Y  
ASS’Y  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
6
2
2
6
2
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
3
AS+G/F20%, D495  
OSM-738SRC  
SGCC-M, T1.2  
SC-90073T  
ASS’Y  
4
5
BASE MOTOR  
6
GUARD COND  
7
ASSY PARTITION  
ASSY CABI SIDE  
ASSY COVER  
8
ASS’Y  
9
ASS’Y  
9-1  
9-2  
10  
COVER  
PP  
COVER CONTROL  
ASSY CABI UPPER  
ASSY COND-UNIT  
SCREEN GUARD  
ROTARY COMPRESSOR  
NUT FLANGE  
PP  
ASS’Y  
11  
UD26B1C2  
P.E.H 100%  
48D135IU1EL  
PI0.8, M5  
HEX, 2C, M8  
PBT, 2.5  
12  
13  
13-1  
13-2  
13-3  
13-4  
13-5  
13-6  
14  
NUT WASHER  
COVER TERMINAL  
GASKET  
EPDM, T0.8  
NR 40˚  
GROMMET ISOLATOR  
OLP  
RAC12074-9622  
ASS’Y  
ASSY VALVE  
14-1  
14-2  
14-3  
14-3-1  
14-4  
14-4-1  
15  
ASSY VALVE CHECK A  
ASSY VALVE CHECK B  
ASSY VALVE 4WAY A  
ASSY SOLENOIDE COIL  
ASSY VALVE 4WAY B  
ASSY SOLENOIDE COIL  
THERMISTOR OUT ASS’Y  
ASSY CONTROL OUT  
C-OIL  
ASS’Y  
ASS’Y  
ASS’Y  
ASS’Y  
ASS’Y  
ASS’Y  
103AT  
16  
ASS’Y  
16-1  
16-2  
16-3  
16-4  
16-5  
16-6  
16-7  
17  
4uF, 450V  
35uF, 450V  
DC17, AC230, 600mA  
ABS  
C-OIL  
TRANS POWER  
CASE PCB  
CASE CONTROL OUT  
TERMINAL BLOCK  
ASSY PCB PARTS  
ASSY HEATER  
SGCC-M, T0.8  
ASS’Y  
ASS’Y  
ASS’Y  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-2-2 UD18B1C2  
12  
15  
11  
10  
6
5
7
16(16-1~16-7)  
4
3
13(13-1~13-6)  
1
2
9
17  
8
14(14-1~14-4)  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I
Parts List  
Q’TY  
No.  
CODE NO  
Description  
Specification  
REMARK  
UD18B1C2  
1
1-1  
2
DB90-00734A  
DB63-00320A  
DB90-00733A  
DB67-50063A  
DB31-00001A  
DB61-20008C  
DB63-00343A  
DB94-00180A  
DB90-00737B  
DB90-40176B  
DB90-00742A  
DB96-01717B  
DB61-00821D  
44B102IU2EL  
DB60-30018A  
DB60-30028A  
DB63-10165D  
DB63-20002A  
DB73-00070A  
DB35-00015C  
DB99-00231A  
DB99-00227A  
DB99-00228A  
DB94-00229A  
DB95-00243A  
DB99-00230A  
DB95-00243B  
DB32-00025A  
DB93-01234A  
2301-001370  
2501-001235  
DB26-10070A  
DB61-00585A  
DB61-00891A  
DB65-40072F  
PD-UD18B1-01  
DB95-00329B  
ASSY CABI FRONT  
GUARD FAN  
ASS’Y  
SC-90073T  
ASS’Y  
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
6
2
2
6
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
ASSY BASE OUT  
FAN PROPELLER  
MOTOR FAN  
3
AS+G/F20%, D405  
IC-9630SLJ5A  
SGCC-M,T1.2  
SC-90073T  
ASS’Y  
4
5
BASE MOTOR  
6
GUARD COND  
7
ASSY PARTITION  
ASSY CABI SIDE RH  
ASSY COVER CONTROL  
ASSY CABI UPPER  
ASSY COND-UNIT  
GUIDE SCREEN  
ROTARY COMPRESSOR  
NUT FLANGE  
8
ASS’Y  
9
ASS’Y  
10  
ASS’Y  
11  
ASS’Y  
12  
P.E.H 100%  
44B092JW1EL  
PI0.8, M5  
HEX, 2C, M8  
PBT, 2.5  
13  
13-1  
13-2  
13-3  
13-4  
13-5  
13-6  
14  
NUT WASHER  
COVER TERMINAL  
GASKET  
EPDM, T0.8  
NR 35˚  
GROMMET ISOLATOR  
OLP  
RAC12067-9622  
ASS’Y  
ASSY VALVE  
14-1  
14-2  
14-3  
14-3-1  
14-4  
14-4-1  
15  
ASSY VALVE CHECK A  
ASSY VALVE CHECK B  
ASSY VALVE 4WAY A  
ASSY SOLENOIDE COIL  
ASSY VALVE 4WAY B  
ASSY SOLENOIDE COIL  
THERMISTOR OUT ASS’Y  
ASSY CONTROL OUT  
C-OIL  
ASS’Y  
ASS’Y  
ASS’Y  
ASS’Y  
ASS’Y  
ASS’Y  
103AT  
16  
ASS’Y  
16-1  
16-2  
16-3  
16-4  
16-5  
16-6  
16-7  
17  
2.5uF, 450V  
25uF, 450V  
DC17, AC230, 600mA  
ABS  
C-OIL  
TRANS POWER  
CASE PCB  
CASE CONTROL OUT  
TERMINAL BLOCK  
ASSY PCB PARTS  
ASSY HEATER  
SGCC-M, T0.8  
ASS’Y  
ASS’Y  
ASS’Y  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-3 ASS’Y CONTROL IN (DB93-01223A)  
I
Parts List  
No  
Description  
Specification  
Remark  
1
2
HOLDER CONTROL  
ASS’Y MAIN PCB  
DB61-00160B  
DB93-00319B  
DB65-00046A  
DB93-00268A  
DB39-00147A  
DB61-00219A  
DB72-10191T  
DB72-00127V  
-
3
TERMINAL BLOCK ASSY  
ASSY DISPLAY PCB  
CONNECTOR WIRE PCB U/D  
HOLDER CLAMP IN  
SEAL CONTROL SIDE  
SEAL H/CONTROL FRONT  
SCREW MACHINE  
LABEL  
4
5
6
7
8
9
10  
11  
-
CORE  
DB31-40005A  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Refrigerating Cycle Block Diagram  
INDOOR UNIT  
OUTDOOR UNIT  
2Way valve  
T1  
Check valve  
(A)  
(B)  
Liquid side  
Capillary tube  
Capillary tube  
Heat  
exchanger  
(Condenser)  
Gas side  
Heat  
exchanger  
(Evaporator)  
Compressor-B  
T2  
Compressor-A  
3Way valve  
4Way valve  
Refrigerating cycle temperature and pressure  
STD Pressure  
Piping Temp.(°F)  
Temp. Condition F)  
Indoor Outdoor  
Operating Condition  
Standard  
(psi)  
T1  
T2  
3-WAY V/V  
DB  
80  
80  
67  
70  
80  
70  
WB  
67  
67  
57  
60  
-
DB  
95  
WB  
75  
75  
57  
43  
65  
33  
57-71  
50-54  
61-64  
34-39  
90-97  
97-104  
82-90  
50-54  
61-64  
Cooling  
Max over load  
-
115  
67  
Low temp.  
Standard  
Max over load  
Deice  
-
34-39  
242-284  
140-158  
149-167  
104-113  
47  
Heating  
-
-
75  
60  
35  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Wiring Diagrams  
6-1 Indoor Unit  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6-2 Outdoor Unit  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Schematic Diagrams  
7-1 Indoor Unit  
IIAS07A5(6)MA / AS09A5(6)MA  
34  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7-2 Outdoor Unit  
IIAS07A5(6)MA / AS09A5(6)MA  
36  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRONICS  
Printed in Korea.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

RCA Camcorder Accessories AVC8HP User Guide
RCA Mouse PC7330 User Guide
ResMed Respiratory Product LT User Guide
Rotel Stereo Amplifier RMB 1565 User Guide
Samsung Air Conditioner AS070VE User Guide
Samsung Flat Panel Television 400TS 3 User Guide
Samsung Projection Television HL R5678W User Guide
Samsung Telephone dcs application User Guide
Samsung VCR SV 6333X User Guide
Samsung Washer Q1457AV T S User Guide