Roberts Gorden Heating System DAT100 User Guide

FOR YOUR SAFETY  
If you smell gas:  
1. Open windows.  
®
2. DO NOT try to light any appliance.  
3. DO NOT use electrical switches.  
4. DO NOT use any telephone in  
your building.  
5. Leave the building.  
DualAir  
6. Immediately call your local gas  
supplier after leaving the building.  
Follow the gas supplier’s  
instructions.  
7. If you cannot reach your gas  
supplier, call the Fire Department.  
Heating and Cooling Units  
Installation, Commissioning,  
Operation & Service Manual  
WARNING  
DAT75  
DAT90  
DAT100  
DAT115  
Fire Hazard  
Do not store or use petrol or other  
flammable vapours and liquids in the  
vicinity of this or any other appliance.  
Some objects will catch fire or explode  
when placed close to heater.  
Failure to follow these instructions can  
result in death, injury or property  
damage.  
Installer  
WARNING  
Please take the time to read and understand  
these instructions prior to any installation.  
Installer must give a copy of this manual to the owner.  
Improper installation, adjustment, alteration, service  
or maintenance can result in death, injury or property  
damage. Read the installation, operation and service  
manual thoroughly before installing or servicing  
this equipment.  
Owner  
Keep this manual in a safe place in order to provide  
your serviceman with necessary information.  
Installation must be done by a registered installer/  
contractor qualified in the installation and service  
of gas-fired heating equipment or your gas supplier.  
Roberts-Gordon Europe Limited  
Unit A, Kings Hill Business Park  
Darlaston Road, Wednesbury  
West Midlands WS10 7SH UK  
Telephone: +44 (0)121 506 7700  
Fax: +44 (0)121 506 7701  
Service Telephone: +44 (0)190 249 8733  
Service Fax: +44(0)190 240 1464  
Quality in Any Language™  
P/N X527 Rev C 10/07  
© Copyright 2007 Roberts-Gordon, LLC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
4.4 DualAir® Performance Data - Graph of Air Flows v  
Static Pressure.............................................................8  
15.2 Troubleshooting For Automatic Ignition Burner  
Systems ...................................................................32  
6.2 Type C12, C32 & C62 Appliance.................................... 10  
6.3 Type B22 Appliance..................................................... 10  
6.4 Converting from Top to Side Terminations for Flue  
and Air Intake ............................................................ 10  
11.6 Turning Off the DualAir® Unit ....................................24  
© 2007 Roberts-Gordon, LLC  
All rights reserved. No part of this work covered by the copyrights herein may be reproduced  
or copied in any form or by any means - graphic, electronic, or mechanical, including  
photocopying, recording, taping or information storage and retrieval systems - without the  
written permission of Roberts-Gordon, LLC.  
Printed in U.K.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF FIGURES  
Figure 2: Installation Clearances and Clearances to  
Combustibles .............................................................4  
Type B22 Appliance................................................... 12  
Type C12 C32 & C62 Appliances ................................. 12  
Figure 9: DualAir® Units Installed in Isolated Equipment  
Rooms...................................................................... 13  
Figure 11: Gas Connection with Stainless Steel Flex  
Connector............................................................... 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Approval  
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential  
requirements of the Gas Appliance Directive, the Low Voltage Directive, the Electromagnetic  
Compatibility Directive and the Machinery Directive for use on natural gas and LPG when installed,  
commissioned and maintained in accordance with these instructions.  
These instructions refer to appliances designed to operate in the European Union.  
Appliances designed for other countries (Non-European Union) are available on request.  
This appliance must be installed in accordance with the local and national codes in force and used  
only in a sufficiently ventilated space, as specified in these instructions.  
Before installation, check that the local gas distribution systems, nature of gas and pressure, and  
adjustment of the appliance are compatible.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 1: HEATER SAFETY  
Your Safety is Important to Us!  
2.1 Clearances to Combustibles  
This symbol is used throughout the  
manual to notify you of possible fire,  
electrical or burn hazards. Please pay  
special attention when reading and  
following the warnings in these sections.  
In all situations, clearances to combustibles must be  
maintained. Caution must be used when running the  
DualAir® unit near combustible materials such as  
wood, paper, rubber, etc. A wall tag (P/N 91040089)  
is on the back cover of this manual as a permanent  
reminder of the safety instructions and the  
Installation, service and annual inspection of the  
importance of the required clearances to  
DualAir® unit must be done by a registered installer/  
contractor qualified in the installation and service of  
gas-fired heating equipment.  
combustibles. Affix the tag on a wall near the  
DualAir® unit.  
2.2 Corrosive Chemicals  
Read this manual carefully before installation,  
operation, or service of this equipment.  
This DualAir® unit is designed for heating and  
cooling non-residential indoor spaces. Do not install  
in residential spaces. These instructions, the layout  
drawing, local codes and ordinances, and applicable  
standards that apply to gas piping, electrical wiring,  
venting, refrigerant installation, etc. must be  
thoroughly understood before proceeding with the  
installation.  
CAUTION  
Do not use heater in an area containing corrosive  
chemicals.  
Corrosive chemicals will damage the burner and  
heat exchanger parts.  
Failure to follow these instructions can result in  
property damage.  
SECTION 2: INSTALLER RESPONSIBILITY  
To supply and install a suitable condenser unit  
along with associated refrigerant circuits in  
accordance with the requirements of  
all relevant local and national codes.  
To install the DualAir® unit, as well as the gas  
Roberts-Gordon cannot be responsible for ensuring  
that all appropriate safety measures are undertaken  
prior to installation; this is entirely the responsibility  
of the installer. It is essential that the contractor, the  
sub-contractor, or the owner identifies the presence  
of combustible materials, corrosive chemicals or  
halogenated hydrocarbons* anywhere in the  
and electrical supplies, in accordance with appli- premises.  
cable specifications and codes. Roberts-Gordon  
recommends the installer contact a local  
building inspector, Fire Officer or insurance  
company for guidance.  
* Halogenated Hydrocarbons are a family of chemical  
compounds characterized by the presence of halogen  
elements (fluorine, chlorine, bromine, etc.). These com-  
pounds are frequently used in refrigerants, cleaning  
agents, solvents, etc. If these compounds enter the air  
supply of the burner, the lifespan of the DualAir® unit  
components will be greatly reduced. Warranty will be  
invalid if the heater is exposed to halogenated hydrocar-  
bons.  
To use the information given in the manual  
together with the local and national codes to  
perform the installation.  
To install the DualAir® unit in accordance with the  
clearances to combustibles of this DualAir® unit.  
2.3 National Standards and Applicable Codes  
All appliances must be installed in accordance with  
the latest revision of applicable standards and local  
and national codes. This refers also to the electric,  
gas, refrigerant and venting installation. Note:  
Additional standards for installations in public  
garages, aircraft hangars, etc. may be applicable.  
To furnish all needed materials not furnished  
as standard equipment.  
To plan location of supports, flues and air  
intakes.  
To provide access for servicing.  
To provide the owner with a copy of this  
Installation, Commissioning, Operation and  
Service Manual.  
To never use the DualAir® unit as support for lad-  
der or other access equipment and never hang  
or suspend anything from heater.  
To ensure that there is sufficient ventilation in the  
area to comply with the requirements of  
all relevant local and national codes.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
SECTION 3: CRITICAL CONSIDERATIONS  
SECTION 3: CRITICAL CONSIDERATIONS  
3.1 Basic Information  
3.7 Electrical Supply  
The CTUD heater that forms the heating section of A permanent 400v 3ø 50Hz electrical supply is  
the DualAir® unit has an automatic ignition burner  
and may be operated as fully modulating or ON/OFF  
operation.  
required at the main electrical terminals. The heater  
also requires suitable energy controls in accordance  
with Section 10.  
The standard unit has the air flow from left to right  
when viewed from the controls side.  
3.8 Flue  
A special order version with the opposite air flow is  
available where the combustion air intake and flue  
will be at the front of the unit.  
Choose a location to allow for the proper alignment  
of the flue. Each DualAir® unit must be fitted with an  
individual and correctly sized sealed flue system  
3.2 Location and Suspension  
All models:  
• Must be installed indoors.  
• Must be installed in a level position.  
• May be mounted on the floor or on a shelf of  
non-combustible material. (See Page 5, Section  
4 and Page 9, Figure 3 for support points)  
No other appliance may be connected to the flue.  
For room-sealed installation, the air intake must be  
the same size sealed system and the flue/air intake  
must terminate at an approved concentric wall or  
roof terminal.  
3.9 Coil Condense Drain  
The cooling coil must be fitted with a suitable  
condense drain. The condense pipe work should be  
in plastic or copper piping in accordance with the  
latest revision of applicable standards and local and  
national codes.  
• May be suspended from above (See Page 9,  
Figure 3), on the floor, or from wall brackets of  
sufficient strength to support the DualAir® unit as  
listed in the Dimension Data Table on Page 6,  
Section 4.2. Drop rods must be a minimum of 12  
mm diameter mild steel. Six suspension points  
Figure 1: Condense Drain  
are located on top of the DualAir® unit.  
• Must be installed in a manner which allows the  
hinged door to be fully opened to provide access  
to all serviceable components.  
Drain to Open Funnel  
100 mm min.  
3.3 Minimum Required Installation Clearances  
Trap must be filled with  
water to be effective and  
prevent air being drawn  
backwards into the drip tray.  
Clearances around the DualAir® unit and flue must  
access for servicing, and correct operation.  
Install to Suitable Drain  
3.4 Clearances to Combustibles  
Failure to install the condense drain correctly may  
cause water carry over into the fan compartment,  
which may then escape and cause property  
damage.  
Clearances must be as indicated on Page 4, Figure  
2. If no clearances to combustibles are indicated,  
then installation clearances apply.  
3.5 Ventilation  
It is important to ensure that there is adequate air  
circulation around the DualAir® unit to supply air for  
combustion, ventilation and distribution in  
accordance with local and national codes.  
3.6 Gas Supply  
It is important that the gas supply pipe is sized  
correctly to provide the inlet pressure as stated on  
the heater data plate. The gas supply pipe and  
electrical connections must not support any of the  
heater's weight.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
                     
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
WARNING  
Fire Hazard  
Some objects will catch fire or explode when placed  
close to heater.  
Keep all flammable objects, liquids and vapours the  
required distance away from the heater.  
Failure to follow these instructions can result in death,  
injury or property damage.  
Figure 2: Installation Clearances and Clearances to Combustibles  
Installation Clearances  
Roof Terminal  
Clearances to Combustibles  
Alternative  
Wall  
Air  
Intake  
Flue  
Terminal  
15 cm  
15 cm  
Condense  
Drain  
Air Flow  
60 cm  
50 cm**  
Install to  
50 cm  
suitable drain,  
See Page 3,  
Figure 1.  
30 cm  
3 m  
Insulated  
refrigerant pipes  
to cooling coil  
by customer.  
2.5 - 3.5 m*  
Customer’s  
Suitable  
Condenser  
Unit  
* Free blowing DualAir® units may be mounted at  
a higher level if destratification fans and/or turn  
down nozzles are installed.  
**80 cm is necessary to  
service heater.  
Free blowing DualAir® units must always be installed at least 1.8 m above the floor.  
Ducted installations may be floor mounted.  
The flue pipe must have clearance from combustibles by 5 cm.  
If installed at low levels where individuals can come in contact with hot heat exchanger components,  
adequate guarding must be provided.  
All distances are minimum clearance requirements for service access, air flow and safety.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 4: SPECIFICATIONS  
SECTION 4: SPECIFICATIONS  
4.1 DAT  
Side View  
3010  
2070  
225  
532  
1127  
Air Intake 130 mm dia  
Flue 130 mm dia  
896  
Gas  
Air Inlet Spigot  
(35 mm flange)  
734  
671  
20 mm Conduit Entry  
for Electrical Connections  
Connection  
Coil Protection,  
Frost Thermostat  
& Pressure Switch  
1494  
1417  
1239  
Internal  
Spigot  
Height  
Heater Section Alternate  
Fan Compartment  
Flue &  
Air Intake  
Position  
Lockout  
Electrical  
Connections  
(behind door)  
Cooling Coil Condense Drain Filter Compartment  
Reset  
Air Outlet  
Spigot  
Red  
Amber  
Dirty Filter  
Warning  
Green  
Burner  
On  
Lockout  
(35 mm flange) Warning  
Front View (Left Version)  
Front View  
Standard Flue &  
Air Intake Position  
1032  
Air Intake  
315  
538  
225  
Extension  
Cover for  
Flue  
51  
890  
399  
Refrigerant  
Pipe-work  
1340  
1590  
1250 Internal Spigot Width  
Rear View  
Rear View (Left Version)  
1239  
Internal  
Spigot  
Height  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
4.2 General Technical Data Table  
75  
90  
100  
115  
Model  
Fan Data  
Designed Air Flow # with Clean Filters  
m3/sec  
m3/sec  
m3/sec  
2.88  
1.66  
3.71  
3.7  
2.60  
5.34  
Min Air Flow at Coil  
Max Air Flow at Coil  
Fan Unit  
457-486 Double Inlet Belt Drive  
2A x 180 / 2A x 200  
2A x 100 / 2A x 95  
2 x A 63  
2A x 180  
Fan Pulley  
mm PCD  
mm PCD  
2A x 112 / 2A x 118  
2 x A 64  
Motor Pulley  
Vee Belts  
Electrical Data - All models need 400v 50Hz 3N supply. Single phase supply output for control circuit  
230v 50Hz fused at 5 Amp. All alarm and status signals 230v 50Hz. Modulation input 0-10vDC.  
3.3  
2.2  
5.4  
4.0  
Total Electrical Load  
Motor Size  
kW  
kW  
A
4.45  
7.5  
Full Load Current  
4.0 / 4.5  
23.0  
7.0 / 7.5  
24.0  
Run Current at Designed Air Flow #  
Start Current  
A
A
Cooling Coil - DX  
Max Cooling Load Split into Two Equal  
Circuits  
kW  
57.74  
71.54  
7/8 copper  
Inlet Connection  
Outlet Connection  
Condensate Connection  
Refrigerant  
in  
in  
1 3/8 copper  
1 5/8 copper  
1
ISO 7-R  
R407C  
27  
25  
18.07  
13  
°C Dry Bulb  
°C Wet Bulb  
°C Dry Bulb  
°C Wet Bulb  
Design Temp. ON  
Design Temp. OFF  
19.4  
14.66  
13.72  
12.3  
Filters - All Models  
All Models  
Qty. 6 - Farr 30/30 grade 100 x 635 x 406  
mbar  
mbar  
Initial Pressure Loss  
Max. Recommended Pressure Loss  
Physical Data  
0.4  
1.5  
Weight  
kg  
612  
621  
638  
647  
NR dB(A)  
SPL dB(A)  
NR dB(A)  
SPL dB(A)  
NR dB(A)  
SPL dB(A)  
65  
68  
68  
73  
75  
76  
72  
67.5  
77  
Noise from Cabinet at 1 m  
Noise from Air Inlet at 1 m  
Noise from Air Outlet at 1 m  
75  
81  
77  
Electrical load at 230v 50Hz measured by calculating from total run current of appliance.  
* Do not exceed the maximum length of flue stated or heater may not operate properly.  
Reduce the maximum length stated by 1 m for each 90° bend installed.  
**If minimum air flow requirements are not met then temperature limit devices will shut down the heater.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 4: SPECIFICATIONS  
4.3 Technical Data Table - Heater Section  
Appliance Category II 2H/L 3B/P  
75  
95  
324  
86  
90  
111  
100  
119  
115  
134  
Model  
Heat Input  
Gross Calorific Value  
Heat Input  
kW  
Btu/h x 1000  
kW  
379  
100  
406  
107  
457  
121  
Net Calorific Value  
Btu/h x 1000  
kW  
293  
78  
341  
91  
365  
98  
413  
111  
Approximate  
Max Heat Output  
Btu/h x 1000  
kW  
266  
66.5  
311  
77.7  
334  
83.3  
379  
93.8  
Min Heat Input - Low Fire  
Gross Calorific Value  
Min Heat Input - Low Fire  
Net Calorific Value  
Btu/h x 1000  
kW  
227  
60.2  
265  
70  
284  
74.9  
320  
84.7  
Btu/h x 1000  
kW  
205  
54.6  
186  
239  
63.7  
217  
256  
68.6  
234  
289  
77.7  
265  
Min Heat Output - Low Fire  
Btu/h x 1000  
*Combination Fan/Limit Thermostat Settings  
Set Point 1 Fan OFF Temp.  
°C  
Set Point 2 Fan ON Temp.  
°C  
30  
75  
50  
85  
45  
70  
45  
75  
Set Point 3 Limit Temp.  
Secondary Limit Thermostat  
°C  
°C  
Natural Gas (G20) Data - Inlet Pressure 20 mbar Min 17 mbar Max 25 mbar  
6.6  
9.0  
319  
6.0  
10.5  
371  
2.9  
6.2  
11.3  
398  
3.0  
6.3  
12.8  
451  
3.1  
Max Burner Pressure  
mbar  
m3/h  
ft3/h  
Max Gas Flow Rate  
3.23  
6.30  
222.5  
Min Burner Pressure - Low Fire  
Min Gas Flow Rate  
mbar  
m3/h  
7.4  
7.9  
9.0  
ft3/h  
259.6  
279.3  
316.4  
Natural Gas (G25) Data - Inlet Pressure 25 mbar Min 20 mbar Max 30 mbar  
10.0  
9.49  
9.3  
11.06  
9.2  
11.86  
10.2  
13.43  
Max Burner Pressure  
mbar  
m3/h  
ft3/h  
Max Gas Flow Rate  
335.1  
4.9  
391  
4.6  
419  
4.5  
474  
5.0  
Min Burner Pressure - Low Fire  
Min Gas Flow Rate  
mbar  
m3/h  
ft3/h  
6.64  
234.6  
7.74  
273.4  
8.30  
293.2  
9.40  
332.0  
LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (Alternative where permitted 50 mbar) Minimum  
25 mbar Maximum 57.5 mbar  
25.6  
3.51  
6.5  
12.8  
12.5  
27.3  
4.09  
7.58  
14.9  
13.4  
25.3  
4.39  
8.13  
16.0  
12.4  
25.9  
4.97  
9.21  
18.1  
12.7  
Max Burner Pressure  
mbar  
m3/h  
kg/h  
Max Gas Flow Rate  
liquid l/h  
Min Burner Pressure - Low Fire  
Min Gas Flow Rate  
mbar  
m3/h  
kg/h  
2.46  
4.55  
8.96  
2.86  
5.31  
10.43  
3.07  
5.69  
11.20  
3.48  
6.45  
12.67  
liquid l/h  
LPG Butane (G30) Data - Inlet Pressure 29 mbar Min 20 mbar Max 35 mbar  
18.3  
2.65  
6.5  
11.3  
9.0  
19.4  
3.09  
7.55  
13.2  
9.5  
18.3  
3.32  
8.09  
14.1  
9.0  
18.7  
3.75  
9.17  
16.0  
9.2  
Max Burner Pressure  
mbar  
m3/h  
kg/h  
Max Gas Flow Rate  
liquid l/h  
Min Burner Pressure - Low Fire  
Min Gas Flow Rate  
mbar  
m3/h  
kg/h  
1.86  
4.53  
7.91  
2.16  
5.29  
9.24  
2.32  
5.66  
9.87  
2.63  
6.42  
11.20  
liquid l/h  
Gas rates corrected to standard conditions 1013.25 mbar 15°C.  
*See Page 44, Figure 19 for detailed Combination Fan/Limit Thermostat settings.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
4.4 DualAir® Performance Data - Graph of Air Flows v Static Pressure  
4.4.1 DAT75 and 90 (2.2 kW or 4 kW motor)  
400  
350  
300  
250  
200  
150  
100  
50  
0
3.4  
2.2  
2.4  
2.6  
2.8  
3.0  
3.2  
Air Flow m3/sec  
95 mm motor pulley x 180 mm fan pulley  
100 mm motor pulley x 200 mm fan pulley  
4.4.2 DAT100 and 115 (4 kW motor)  
400  
350  
300  
250  
200  
150  
100  
50  
0
4.0  
2.8  
3.0  
3.2  
3.4  
3.6  
3.8  
Air Flow m3/sec  
118 mm Pulley  
112 mm Pulley  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 5: HEATER INSTALLATION  
SECTION 5: HEATER INSTALLATION  
5.1 General  
DualAir® units are designed for installation above  
2.5 m. When connected to duct delivery systems  
any suitable location will be acceptable.  
For floor mounting, the DualAir® unit may stand  
directly on its base.  
5.3 Shelf Mounting and Suspension  
WARNING  
Crush Hazard  
Use 12 mm steel drop rod  
minimum.  
Failure of the supports can  
result in death, injury  
or property damage.  
5.2 Handling  
All DualAir® units have steel channel sections at the  
base to be used to support the equipment. Three  
steel sections are also provided across the top of the  
For typical suspension See Page 9, Figure 3.  
unit for support. The DualAir® unit may be  
suspended from these top sections.  
The DualAir® unit is heavy and proper handling  
equipment must be used by trained engineers.  
Figure 3: Suspension Methods  
12 mm  
Steel  
Drop Rod  
Nut  
Washers  
Nut  
Locknut  
Rolled Steel  
Channel  
Base  
Floor  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 6: FLUE INSTALLATION  
6.1 Flue Installation  
Figure 4: Flue and Roof Detail  
WARNING  
Flue  
Terminal  
Fire Hazard  
Masterflash  
soaker flashing  
or Rain Collar.  
Some objects will catch fire or explode when placed  
close to the heater section.  
Keep all flammable objects, liquids and vapours the  
required distance away from the heater section.  
Failure to follow these instructions can result in death,  
injury or property damage.  
Roof  
The flue must terminate outside of the building.  
Flues and air intakes must be fully sealed and  
correctly sized for the model. Flues should be  
assembled as detailed on Page 10, Figure 4 through  
Page 12, Figure 8. The joints between the flue  
terminal and the roof or wall must be sealed. If the  
flue passes through a wall or ceiling of combustible  
material, it must be enclosed by a sleeve of non-  
combustible material and be separated from the  
sleeve by at least a 25 mm air gap.  
Metal Sleeve  
Flue  
25mm Air Gap to  
Combustible Material  
6.4 Converting from Top to Side Terminations for  
Flue and Air Intake  
1. Remove the control section lower door and  
Figure 6 for details.  
Flues and air intakes must be adequately  
supported so that the DualAir® unit does not  
bear the weight of the pipes.  
6.4.1 Flue Conversion  
1. Remove the inner and outer flue spigots from  
the top. Retain the spigot and internal seal.  
6.2 Type C12, C32 & C62 Appliance  
Room Sealed.  
2. Disassemble the flue back to spigot "A". See  
Page 11, Figure 6. Ensure all seals are still in  
place.  
The heaters are designed to be installed as room  
sealed appliances. The flue and air intake are run as  
separate pipes to the concentric wall or roof  
terminal. See Page 12, Figure 8.  
3. Fit 90° bend directly into spigot "A" pointing  
forwards.  
4. Cut a 90 mm length from the 360 mm flue that  
was removed.  
6.3 Type B22 Appliance  
The flue must terminate outside the building and be  
fitted with a low resistance terminal.  
5. Attach this piece to the 90° bend, then attach  
the inner spigot that was removed.  
6.4.2 Air Intake Conversion  
1. Remove the flexible hose from the air intake  
spigot.  
6.3.1 Air Intake Terminal Cover  
For Type B22 appliance installations, an air intake  
terminal cover is an available option. The cover is  
scored flat sheet metal that must be bent into shape.  
See Page 12, Figure 7. Remove and retain the  
screws for the air inlet spigot. Use these screws to  
attach the cover in position over the spigot.  
2. Remove the spigot from the top.  
3. Move the blanking plate from the upper panel  
(previously removed) to the top to cover the  
original flue and air intake holes.  
4. Refit the upper panel feeding the air intake flex-  
ible hose through the upper hole and aligning  
the flue with the lower hole.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
SECTION 6: FLUE INSTALLATION  
5. Refit the air intake spigot to the flexible hose re-  
using the hose clamp and to the upper panel  
using the original screws.  
6. Align the flues’ inner and outer spigots and  
attach through the holes in the upper panel re-  
using the original screws.  
7. Refit the lower door.  
Figure 5: Control Section & Upper Panel  
Air Intake Spigot  
Inner and Outer  
Flue Spigots  
Hose Clamp  
360 mm Length  
of 130 mm dia Flue  
Flexible Hose  
Upper Panel  
Blanking Plate  
Lower Door  
Control Section  
Figure 6: Alternate  
Flexible Hose  
Upper Panel  
Hose Clamp  
90° Bend  
Spigot "A"  
90mm Flue  
Inner Spigot  
Outer Spigots  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
Figure 7: Vertical and Horizontal Flue Termination - Type B22 Appliance  
Roof Terminal  
Masterflash  
Metal Sleeve  
(25 mm air gap to  
combustible material)  
Fold leg  
down  
Fold foot  
out  
Flue  
Air Intake  
Terminal Cover  
Figure 8: Vertical and Horizontal Flue Termination - Type C12 C32 & C62 Appliances  
Roof Terminal  
Masterflash  
Manifold  
Air Intake  
Flue  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 7: AIR SUPPLY  
SECTION 7: AIR SUPPLY  
7.1 Room Sealed Installation  
When installed as a room sealed heater, the air for  
7.3 Building Ventilation  
Where ventilation is required, air must be taken from  
combustion is drawn in from outside the building. It an outside point where it is not likely to be  
is important to ensure that there is adequate  
ventilation to provide air for the distribution fan/s.  
contaminated or obstructed.  
Where natural ventilation is used, suitable ventilation  
with outside air at low level must be provided in  
accordance with Section 7.2.1 and local and national  
codes.  
Where mechanical ventilation is used, extract rate  
must be 5% - 10% less than the inlet rate. The  
mechanical ventilation must be interlocked with the  
burner on the heater.  
7.2 Open Flued Installation  
Ensure adequate air supply at all times for both  
combustion and heating requirements in  
accordance with local and national codes. The air  
supply to the heater must be fitted with a low  
resistance terminal to prevent the ingress of debris.  
7.4 Isolated Equipment Rooms  
7.2.1 Heaters Installed Within the Heated Space  
Ventilation must prevent the isolated equipment  
room temperature from exceeding 32°C as well as  
prevent any negative air pressure within the room.  
See Page 13, Figure 9. Any isolated equipment  
room containing air heaters will require permanent  
air vents direct to outside air in compliance with local  
codes.  
Where natural ventilation is used, suitable  
permanent openings at low and high level,  
communicating directly with the outside air, must be  
provided.  
Where the volume of the heated space is greater  
than 4.7 m3 per kilowatt of total rated heat input and  
the air change rate is at least 0.5/h, additional high  
and low level ventilation will not be required.  
For a building having an air change rate less than  
0.5/h, ventilation will be necessary in accordance  
with local and national codes. Ventilation direct to  
outside must be provided as follows:  
• Heaters above 70 kW heat input = 350 cm2 +  
2.5 cm2 per kW of rated heat input above 70 kW  
Where mechanical ventilation is used, extract rate  
must be 5% - 10% less than the inlet rate. The  
mechanical ventilation must be interlocked with the  
burner on the heater.  
Figure 9: DualAir® Units Installed in Isolated Equipment Rooms  
High level  
ventilation  
Manifold  
Air Intake  
Flue  
Duct distribution  
system or  
discharge to  
heated space.  
Return air duct  
from heated  
space or fresh  
air from outside  
Max Temperature 32° C  
Room air pressure must not be negative.  
Low level  
ventilation  
Wall  
Outside  
Wall  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 8: OPTIONAL HEATER CONFIGURATIONS  
8.1 Distribution Duct  
DualAir® units are designed to be connected to  
distribution and air inlet ducting.  
It is recommended that flexible duct connectors and/  
or attenuators are used to reduce duct born noises.  
It is recommended that the inlet ducting is arranged  
with both fresh air and recirculating air dampers to  
take advantage of the "free cooling" stage provided.  
Distribution ducting must be insulated to prevent  
heat gain during cooling mode.  
The duct must be designed as described on Page  
14, Section 8.1 and Figure 10 to ensure that there is  
a homogenous air flow across the whole heat  
exchanger. Failure to provide a properly distributed  
air flow will reduce the life of the heat exchanger.  
Contact Roberts-Gordon Europe Ltd. Design  
Department for recommendations regarding  
duct resistance and design. Tel: +44 (0) 121 506  
7700  
The air flow must be in the direction as stated for the  
version being installed with the heater at the  
discharge end.  
Figure 10: Ducting  
NOTE: Duct size will be full size of inlet and outlet.  
All joints between the heater and duct work should be  
made as air tight as possible.  
*Inlet Duct Minimum Dimension same as Outlet Duct  
Minimum Dimension  
Dimension  
“X”  
*Minimum-  
Twice  
Dimension  
“X”  
Airflow Indicator  
Ducting  
Flexible Flange  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
SECTION 9: GAS PIPING  
SECTION 9: GAS PIPING  
9.1 Connections  
Connect the heater to the gas supply ensuring that  
the final connections are as follows:  
• The gas supply pipe is adequately sized to carry  
the total volume of gas for the complete  
installation.  
WARNING  
• An isolating valve and union connection should  
be used and fitted into the supply adjacent to the  
heater.  
Fire Hazard  
• For suspended heaters, use an approved metal  
flexible connection between the isolating valve  
and the heater. To reduce pressure loss, use  
one pipe size larger than the heater gas  
connection.  
Connect gas supply according to Figure 11.  
Gas can leak if not installed properly.  
Failure to follow these instructions can result in death,  
injury or property damage.  
It is important that the gas supply pipe and the  
electrical connections do not support any of the  
heater’s weight.  
IMPORTANT - The complete installation must be  
purged and tested for gas soundness in accordance  
with local and national codes.  
A gas meter is connected to the service pipe by the  
gas supply company. An existing meter should be  
checked, preferably by the company, to ensure that  
the meter is adequate for the rate of gas supply  
required.  
Installation pipes must be fitted in accordance with  
local and national codes. Pipe work from the meter  
to the heater(s) must be of adequate size.  
Figure 11: Gas Connection with Stainless Steel Flex Connector  
Option A:  
Stainless Steel  
Flex Gas  
Hold gas nipple securely  
with pipe wrench when  
attaching the flex gas  
connector.  
Connector  
Do not twist flexible  
gas connector.  
Ensure all joints are  
gas tight.  
Do not bend flexible  
gas connector sharply.  
Option B:  
Gas Isolating Valve  
Medium or Heavy  
Guage Tubing  
Gas Connection  
Drip Leg  
Cap  
Union  
Connection  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 10: WIRING AND ELECTRICAL INFORMATION  
10.1 Electrical Supply  
All heater models need a constant 400 V 50 Hz 3 ø  
supply connected to terminals L1,L2, L3, N & Earth.  
Polarity "L1 & N" must be correct. The voltage  
between neutral and earth should be 0 and never  
exceed 15 volts.  
cooling temperature control. See Page 20, Section  
10.6.  
To operate the modulating gas burner, a further  
input of 0-10 V DC is required with 0V giving  
minimum fire and a 10V giving full fire, wired in  
screened cable (Belden 8451 or equivalent).  
All heaters and controls must be correctly earthed.  
All external wiring must comply with the relevant  
local codes. Wire specification H05VV-F.  
External controls must have a constant 230 V 50 Hz  
1 Ø supply.  
10.2.1 Remote Frost Thermostat  
When required, connect to terminals 2 and 3 in the  
main terminal block.  
Locate within the heated space adjacent to the most  
vulnerable equipment that requires protection.  
10.4.  
An isolator with a contact separation of at least  
3 mm on all poles must be installed adjacent to, but  
not attached to, the DualAir® unit to disconnect all  
supplies to the heater and any remote control.  
10.2.2 Remote Fan Controls  
The fan will operate automatically.  
A switch or control wired between terminals 2 & 1 in  
the terminal block will allow external control of the  
fan(s).  
The fan may be operated continuously from an  
external control, with the burner/cooling cycling on  
and off.  
The final connection to the heater should be made  
by flexible cable or conduit to the main terminal  
block in the control section using 1 mm2 cable on all  
models.  
All cables entering through the top of the heater  
should be routed via the metal shield to prevent  
inadvertent contact with the flue.  
Models  
.............................................Fuse Size  
DAT 75 & 90..................................................... 5 A  
DAT 100 & 115 ................................................10 A  
WARNING  
Electrical Shock Hazard  
Disconnect electrical power before servicing.  
Failure to follow these instructions can result in  
death or electrical shock.  
10.2 Remote Control  
Roberts Gordon markets a dedicated DualAir®  
control that will operate all the available features of  
the unit.  
The DualAir® unit requires a 230 V remote control to  
provide a time control and multistage heating/  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
SECTION 10: WIRING AND ELECTRICAL INFORMATION  
10.3 DAT Main Circuit Board Terminal Identification  
Terminal  
Number  
Use  
Relay/Function  
Operation  
Input for Remote Fan Opera-  
tion Output for Fan Operation  
Monitor  
Optional - Main Fan Runs from  
External Control  
1 Input or Output  
External Fan Control  
230 V 50 Hz supply of external  
thermostat or control  
2 Output  
3 Input  
230 V to external control  
Burner On  
Burner Fires.  
R1 energizes with gas valve  
Burner Operates.  
Fan Operates via R1  
Optional Remote Indication of  
Burner ON.  
4 Output  
5 Output  
7 Output  
8 Input  
230 V Burner ON Signal  
Neutral for Signals  
& External Control  
Optional Remote Indication of  
Burner Lockout  
230 V Burner Lockout Signal  
Burner Lockout Reset from N  
(5)  
Optional Remote Burner Lock-  
out Reset (must be from N)  
DualAir® units contains Coil  
Frost Thermostat, Coil Pres-  
sure Switch & Auxiliary Contact  
on Contactor  
Site Wiring to Condensers  
Normally Closed Controls  
Break on Fault Position  
Volt Free Safety Circuits for  
External Condensers  
9 & 10  
Burner OFF  
Fan ON from R2  
Dampers Output to T16  
230 V 1st Stage of Cooling  
(Free Cooling)  
11 Input  
R2 On  
Burner OFF  
Fan ON from R3  
Dampers Output to T15  
Output to Condenser 1 at T17  
& 18  
230 V 2nd Stage of Cooling  
Cooling Coil Stage 1  
R2 OFF  
R3 ON  
12 Input  
13 Input  
230 V 3rd Stage of Cooling  
Cooling Coil Stage 2  
All input 12 Operations  
Output to Condenser 2 at T19  
& 20  
R3 ON  
R4 ON  
14 = Neutral  
15 = Recirculated Air  
16 = Fresh Air  
230 V Output for Optional  
Damper  
14, 15 & 16 Output  
17 & 18  
From R2  
R3 ON  
Volt Free Control Circuit  
Condenser 1  
Normally Open Contact  
for Condenser 1  
R3 ON  
R4 ON  
Volt Free Control Circuit  
Condenser 2  
Normally Open Contact  
for Condenser 2  
19 & 20  
230 V Output to  
Remote Dirty Filter Warning  
21 = L  
22 = N  
21 & 22 Output  
23 & 24  
Alternative Dirty Filter Indica-  
Volt Free Output to  
Remote Dirty Filter Warning  
Normally Open Contact  
for Dirty Filter Indication  
tion for BMS or DualAir® Con-  
trol  
0 - 10 V DC Input for  
Modulating Burner  
T3 Must Be Live to Operate  
Burner  
0 V = Minimum Fire  
10 V = Maximum Fire  
25 & 26 Input  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
10.4 DAT Wiring Diagram  
Yellow  
SENSE  
BLACK  
IGNITION  
GREEN/YELLOW  
S 4563 C Honeywell  
Secondary Limit  
Thermostat N/C  
BROWN  
BLUE  
RUN  
GREEN/YELLOW  
LOCKOUT  
E
N
L
Red  
PRESSURE SWITCH  
RESET  
PUSH  
SITE  
WIRING  
BLACK  
NO\P(3)  
YELLOW  
N
L
1
2
3
7
8
WHITE  
C \P(1)  
NC\P(2)  
Blue  
Brown  
White  
Pressure Switch  
Detail  
Black  
Pink  
NOTE:  
For external fan wiring,  
Grey  
If any of the original wire supplied with the  
heater must be replaced, it must be replaced  
with wiring material having a temperature  
rating of at least 105° C and 600 volts.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 10: WIRING AND ELECTRICAL INFORMATION  
10.5 DAT Wiring Diagram  
Yellow  
Site wiring connections shown  
Condensor control circuit  
limit devices  
9
10  
Aux contact  
This appliance  
must be Earthed  
14  
13  
Fuse 5A  
contactor  
overload &  
N
1
3
2
2
400 V 50 Hz  
3 N Suppy  
L1  
L2  
main  
fan  
4
4
6
motor  
5
6
L3  
R3/2  
96 95 A2  
A1  
Remote fan controls 230 V  
1
2
3
Blue  
N
L
R2/2  
R1/1  
230 V output to controls  
Heating Stage 230 V  
Heater  
Supply  
Brown  
R1 230 V  
Relay  
Burner  
ON  
Yellow  
Violet  
4
5
7
Heat ON 230 V  
Lockout 230 V  
Coil Safety  
Violet  
N
3
1
3
2
Remote Lockout  
reset 230 V  
8
White  
Black  
H1  
H3  
1
Control inputs 230 V  
R3/1  
2
4
1
7
1st stage cool (free cool)  
11  
Filter pressure Sw  
10  
2
R2 230 V  
3
2
2nd stage cool  
3rd stage cool  
12  
13  
14  
Filter  
Pressure Switch  
2
R3 230 V  
7
R4 230 V  
N
Damper supply 230 V  
Recirc' air  
4
R2/1  
15  
16  
17  
18  
TH  
Red  
Red  
1
Limit  
Fresh air  
3
11  
3
Green  
Heat On  
Red  
9
Brown-white  
Red-white  
cooling condenser  
1st stage  
R3/3  
1
cooling condenser  
19  
20  
21  
22  
Lock Out  
Common  
Neutral  
R4/1  
2nd stage  
Blue  
Dirty filter warning 230 V  
Lock Out  
Reset  
Grey  
Pink  
2
7
R5 230 V  
H7  
H8  
Blue  
Brown  
White  
Grey  
Black  
Pink  
Grey  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
10.6 DAT Site Connections at Main Circuit Board  
Screened Cable  
Belden 8451  
(or equivalent)  
28  
27  
26  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
15  
14  
13  
12  
11  
Earthed at one end  
Burner  
Modulating Signal  
System Ground  
-
-
0 - 10 DC  
+
0 V = Minimum Fire  
+
Screen  
Volt Free Dirty Filter Warning  
N
L
Dirty Filter Warning 230 V  
2nd stage  
Volt Free  
cooling condenser  
Condenser  
Control  
1st stage  
cooling condenser  
Fresh air  
Circuits  
Cooling Stage 3  
(2nd stage  
cooling coil)  
Recirc' air  
N
Damper  
Supply  
Cooling Stage 2  
(1st stage  
cooling coil)  
Cooling Stage 1  
(free cooling when  
fresh air is connected  
and dampers fitted)  
Remote Lockout Reset  
8
7
5
4
Lockout Warning 230 V  
N
Heat ON  
Indication  
230 V  
MultiStage  
Temperature  
Control  
(or similar)  
Optional Frost Thermostat 230 V  
Heating Stage  
for ON/OFF and  
Burner Modulation  
3
2
1
Time Switch Control 230 V  
Optional External Fan Control 230 V  
L3  
L2  
L1  
N
400 V 50 Hz  
3 N Suppy  
This appliance  
MUST be  
Earthed  
Volt Free Condenser  
10  
9
Control  
Circuit Safety Devices  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 11: COMMISSIONING  
SECTION 11: COMMISSIONING  
Gas Fired Heater  
11.1.2 Electrical Checks  
Installation, service, commissioning and annual  
1. Check that all site wiring is connected in  
accordance with the appropriate wiring dia-  
inspection of the heater must be done by a  
contractor qualified in the installation and service of  
gas-fired heating equipment. Read this manual  
carefully before installation, commissioning,  
operation, or service of this equipment. All  
components are accessed via the hinged door.  
Opening the door exposes live electrical  
connections and hot components.  
2. Check the correct fuse size is fitted;  
11.2 Gas Supply  
All aspects of the gas installation including the gas  
meter must be inspected, tested for soundness and  
purged in accordance with local and national codes.  
Cooling Coils/Condensers  
Installation, service, commissioning and annual  
inspection of the cooling equipment must be done  
by a contractor qualified in the installation and  
service of refrigeration equipment. Read condenser  
manufacturer’s manual carefully before installation,  
commissioning, operation, or service of this  
equipment.  
11.3 Mechanical Checks  
1. Check that the fan is free to run and that the fan  
rotates in the correct direction. To reverse rota-  
tion, transpose two of the incoming phase con-  
nections.  
2. Check that the flue and air intake are installed  
in accordance with these instructions and local  
regulations.  
WARNING  
3. Check that the settings of the Combination Fan/  
Limit thermostat are correct - See Page 7, Sec-  
NOTE: The second limit thermostat is preset and  
sealed at the factory and is not adjustable.  
Electrical Shock Hazard  
Use extreme caution while commissioning.  
11.4 Begin Commissioning  
11.4.1 Before Operating the Heater  
Failure to follow these instructions can result in  
death or electrical shock.  
To ensure that all the controls are in safe working  
order, operate the heater for the first time with the  
isolating gas valve turned off.  
11.1 Pre-Commission Checks  
All pre-commission checks must be carried out  
before lighting the heater.  
1. Turn off the isolating gas valve  
Ensure that the heater and all controls are suitable  
for the gas, pressure and electrical supply to which  
they are to be connected.  
2. Using the installed external control, turn on the  
burner. The automatic sequence will now begin  
as described on Page 22, Figure 12.  
There will be no ignition of the burner and lockout  
will occur, proving the controls are operating  
correctly.  
11.1.1 Louvres  
Where fitted, the air delivery louvres need to be set  
during commissioning to give the required air  
distribution.  
WARNING  
Cut Hazard  
Turn off gas and electrical supply before maintenance.  
Fan can start automatically at any time.  
Failure to follow these instructions can result in severe  
injury or product damage.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
Figure 12: Automatic Burner Control Box Sequence  
Burner sequence for Honeywell S4563 or S4565C  
START  
CLOSE  
DOWN  
RUN  
Supply 230 V  
Flue Fan  
30 Sec. Purge*  
NO  
Pressure Switch  
C
P
NC  
ts**  
Ignition Spark  
Start Gas Valve  
Flame Signal  
Required Incoming Signals  
Signals Output By Control  
*Purge time begins at pressure switch change over.  
**ts=Safety time (S4563C=3 seconds [alternate 5 seconds]; S4565C=5 seconds)  
If at any stage the flame fails, the control will go to "lockout". The red light will illuminate and the  
control must be manually reset before further start attempt.  
Figure 13: Modureg Gas Valve  
Moving Shaft  
Max Pressure Adjustment  
Min Pressure Adjustment  
Plug for  
Main Gas Valve  
Modureg Modulating Regulator  
6.3mm AMP  
Terminals for  
Modulation  
Plug for  
Main Gas Valve  
Inlet Pressure  
Honeywell Gas Valve  
Gas Inlet  
Gas Outlet  
Outlet Pressure  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 11: COMMISSIONING  
11.4.2 Commissioning the Gas Valves  
sure must be corrected before completing the  
commission.  
All DualAir® units are fitted with fully modulating  
burner operation. The Honeywell automatic gas  
valves are fitted with the Honeywell Modureg  
modulating regulator.  
2. Release the moving shaft and observe that the  
burner pressure returns to the minimum setting.  
3. Turn off the external controls and reconnect the  
electrical leads to the Modureg regulator.  
The Modureg device provides the adjustments for  
maximum and minimum firing and is set using the  
two adjustments. See Page 22, Figure 13.  
The external control will operate the burner between  
these two limits depending on heat demand.  
4. Turn on the external controls and allow the  
burner to fire once again observing the burner  
pressure.  
5. Using the temperature set point device of the  
installed control system, set for maximum  
burner firing and observe that the burner pres-  
sure slowly rises to the maximum as set.  
The minimum set point must not be set lower  
than the minimum burner pressure stated on  
11.4.3 Commissioning the Gas Valve  
There are two stages to commissioning the  
modulation equipment.  
6. Reset the temperature set point by small steps  
until the burner pressure slowly drops to the  
minimum pressure set. Repeat Step 5 and  
observe that the maximum set point is again  
achieved.  
The minimum pressure setting must be adjusted  
first, any adjustment of the minimum pressure  
setting will affect the maximum pressure setting.  
Check Gas Rate  
1. After burner pressure adjustment, allow the  
heater to operate for at least 15 minutes and  
then re-check settings.  
For ON/OFF non-modulating operation set the  
minimum firing rate to be the maximum burner  
2. Remove the manometer and refit all covers to  
the valve and tighten the screw of the outlet  
pressure tap.  
11.4.3.1 Set Minimum Pressure  
1. Disconnect the leads from the coil of the  
Modureg regulator.  
3. Check gas flow rate at gas meter.  
2. Connect a suitable manometer to the burner  
pressure test point of the main gas valve.  
11.5 Combustion Testing  
The only adjustment to alter combustion  
performance is burner pressure. Combustion quality  
must be tested to prove correct heater operation.  
Incorrect results will indicate faults with the  
installation or appliance.  
3. Turn on any external controls and allow the  
burner to fire for at least five minutes.  
4. Remove cap and using a suitable 9mm span-  
ner adjust the burner minimum set pressure to  
the value shown on Page 6, Section 4.2.  
Combustion testing must be carried out at full fire  
with all covers in place. The flue gas is sampled in  
the flue, within 1 meter of the heater. The values of  
CO2 should be between 6.5% to 8.0% for natural  
gas and 7.0% to 9.1% for LPG dependant upon  
model.  
The CO will be up to 80 ppm (0.008%) dry, air free  
dependant upon model. Temperature rise of the flue  
gases above ambient should be approximately  
160°C to 180° C. Seal test hole in flue after testing.  
11.4.3.2 Set Maximum Pressure  
(Not Required for ON/OFF burners)  
1. Press in the moving shaft of the Modureg valve  
and hold in this position while adjusting the  
burner maximum pressure to the value shown  
For adjustments See Page 22, Figure 13.  
NOTE: If the correct burner pressure cannot be  
reached, then check the inlet pressure to the  
valve, with the burner firing. See Page 6, Sec-  
tion 4.2 for inlet pressure requirements.  
Following the above operate the heater for 30  
minutes at the minimum firing rate. Following this  
time the temperature of the products of combustion  
in the flue should be measured. If the flue products  
temperature is below 80° C then the minimum firing  
rate should be increased. Continuous operation of  
Do not continue to adjust the regulator if the  
pressure is not changing.  
If the inlet pressure is too low to allow a correct the burner with flue gas temperature of below 80° C  
will cause condensation to form in the heat  
burner pressure setting, then the gas inlet pres-  
exchanger and flue system. This will cause nuisance  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
water collection and a shortened heat exchanger  
life.  
Pressure Switch  
The pressure switch is factory pre-set for each  
model and is not adjustable.  
11.6 Turning Off the DualAir® Unit  
Set the external controls to the off position and the  
main burner will stop.  
The fans will run until they are stopped automatically  
by the fan thermostat.  
Do not use electrical isolator for control of  
heater. Electrical isolator will switch off the fan.  
Heat exchanger could be damaged. Warranty will  
not cover damage to the heat exchanger if  
operated improperly.  
11.7 External Controls  
External controls may include time switch, room  
thermostat and frost thermostat. Operate each  
control to ensure that they function correctly. Set the  
time switch (if fitted) and room thermostat to the  
users’ requirements. Operate the external controls  
and ensure that the installed cooling stages operate  
correctly as described on Page 17, Section 10.3.  
11.8 Complete the Commissioning  
Ensure that all covers are fitted correctly and all test  
points are properly sealed.  
11.9 Instruction to the User  
Explain the controls of the DualAir® unit to the user  
including how to turn it on and off, using the controls  
fitted on site.  
Give this manual to the user.  
Ensure that the user is shown and understands the  
importance of maintaining clearances to  
combustibles and the user instructions on Page 25,  
warnings defined in this manual.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
SECTION 12: USER INSTRUCTIONS  
SECTION 12: USER INSTRUCTIONS  
12.1 User Instructions  
12.3 Common User Controls  
12.3.1 Combination Fan/Limit Thermostat  
The Combination Fan/Limit Thermostat is located  
inside the access door at the top of the heater. See  
The DualAir® units are fully automatic and operate  
from the external controls fitted on site.  
The only user controls at the heater are the:  
Burner lockout reset button:  
This control ensures the heater does not blow cold  
air in the normal heating cycle and protects the heat  
exchanger against overheating.  
...................................See Page 26, Section 12.3.3  
Limit thermostat reset:  
.................................... See Page 25, Section 12.3.1  
Second limit thermostat reset button:  
...................................See Page 25, Section 12.3.2  
Figure 15: Fan/Limit Thermostat  
If the air flow is reduced due to power failure the  
limit thermostat will cause the burner to lockout.  
WARNING  
Red limit reset button  
(Press to reset)  
White fan button  
Electrical Shock Hazard  
Pull out for normal operation.  
Press in for constant fan.  
Disconnect electrical power before servicing.  
The combination fan/limit thermostat is preset  
during commissioning.  
Failure to follow these instructions can result in  
death or electrical shock.  
NOTE: To reset, the heat exchanger must be cool.  
12.2 Heater Operation  
Description  
Part Number  
When the heater has been switched on by the  
remote controls installed, the main burner will  
automatically turn on.  
The burner control box will control the ignition of the  
flame.  
All heaters require a constant gas and electricity  
supply which must not be interrupted during the  
normal operation of this heater.  
Combination Fan/Limit Thermostat  
K017A  
12.3.2 Secondary Limit Thermostat  
Press to reset  
12.2.1 Warning Lights  
These are hand reset devices to give further  
protection against fan failure.  
NOTE: To reset, the heat exchanger must be cool.  
The DualAir® unit has three warning lights;  
GREEN = Heater ON, burner attempting to fire  
RED = Burner LOCKOUT, see Section 12.3.3.  
AMBER = Dirty Filter, replace filter, air flow is  
dropping to an unacceptably low value.  
Description  
Part Number  
Secondary Limit Thermostat  
90412100  
Figure 14: Heater Operating Sequence  
ON  
CLOSE  
DOWN  
THERMOSTAT  
CALL FOR  
HEAT  
ON  
BURNER  
RUN  
ON  
RUN ON  
FAN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
Do not operate the DualAir® unit without filters  
as the cooling coil may become blocked and  
impossible to clean.  
WARNING  
12.5 Heating Section Lighting Instructions  
12.5.1 To Turn On Heater  
1. Ensure that the electrical and gas supplies to  
the heater are on. Check that the on site con-  
trols are “ON.  
Explosion Hazard  
NOTE: The thermostat setting must be above the  
ambient temperature for the heater to operate.  
If control locks out, do not make more than 3  
attempts to restart the heater.  
2. The green light will be on and the automatic fir-  
ing sequence will begin as described on Page  
22, Figure 12. The heater will now operate  
automatically under the control of the on site  
controls. Following long shut down periods, the  
control may go to lockout. See Page 26, Sec-  
tion 12.3.3.  
Dangerous gas mixtures can build up.  
The fault must be traced and repaired by a  
registered installer or service engineer.  
Failure to follow these instructions can result in  
death, injury or property damage.  
12.3.3 Burner Lockout Reset Button  
12.5.2 To Turn the Heater Off  
The red warning light will illuminate when the control  
has gone to lockout. This may be caused by flame  
failure. Press the reset button,(See Page 5, Section  
4.1), or the remote reset if installed on site.  
Set the installed remote controls to “OFF.  
The burner will turn off immediately.  
The fan will continue to run for a few minutes.  
To restart turn the control used above to “ON.  
12.4 Cooling Section Operation  
The temperature control will bring on the fan to  
12.6 Simple Fault Finding  
Possible reasons for the heater not operating are:  
1. Gas supply not turned ON.  
operate the DualAir® unit in cooling mode dependent  
on the current temperature and set point.  
Once the temperature rises above the set point,  
there are three stages of cooling available  
dependant on site installation.  
2. Electricity supply not turned ON.  
3. The time and/or temperature controls are not  
“ON.  
Cooling Stage 1 (optional free cooling):  
The fan runs and change over dampers (if fitted)  
allow fresh air to be drawn from outside.  
4. One or both of the limit thermostats may have  
operated. This may be caused by an interrup-  
tion of the electrical supply or failure of the  
distribution fan.  
If the limit thermostats persistently operate, there is  
a fault which must be investigated by a contractor  
qualified in the installation and service of gas-fired  
heating equipment.  
If the temperature continues to rise then  
Cooling Stage 2 operates: The fan runs, the  
dampers (if fitted) return to recirculating air and the  
first condenser operates to provide cooling at half  
load.  
Should the temperature continue to rise,  
Cooling Stage 3 operates: The fan runs, the  
dampers (if fitted) remain in recirculating air and the  
second condenser operates to provide cooling at full  
load.  
12.6.1 Simple Fault Finding (burner faults)  
If the burner fails to ignite for any reason, it will go to  
lockout. This will be indicated by the red light on the  
heater or at the remote indicator (if fitted).  
12.4.1 Filters  
Air cleaning filters are fitted to the DualAir® unit to  
protect the cooling coil and provide improved  
environmental conditions.  
1. Press in and release the lockout reset button. If  
a remote reset is not fitted a reset button is on  
the side panel of the heater. See Page 5, Sec-  
The filters will require to be replaced at least three  
times per year and in dirty environments cleaning of  
the filters may be required at more frequent  
intervals.  
When the filters are dirty the warning light will show  
see Page 25, Section 12.2.1. The filters must be  
cleaned or replaced immediately.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
SECTION 12: USER INSTRUCTIONS  
FOR YOUR SAFETY  
If you smell gas:  
1. Open windows.  
2. DO NOT try to light any appliance.  
3. DO NOT use electrical switches.  
4. DO NOT use any telephone in  
your building.  
5. Leave the building.  
6. Immediately call your local gas  
supplier after leaving the building.  
Follow the gas supplier’s  
instructions.  
7. If you cannot reach your gas  
supplier, call the Fire Department.  
WARNING  
Fire Hazard  
Do not store or use petrol or other  
flammable vapours and liquids in the  
vicinity of this or any other appliance.  
Some objects will catch fire or explode  
when placed close to heater.  
Failure to follow these instructions can  
result in death, injury or property  
damage.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 13: SERVICING  
13.1 Servicing Instructions  
to ensure that adequate air flow.  
The cooling equipment will automatically turn off  
should the air flow drop to a preset low value even  
though the fan will still run. The maximum resistance  
across a dirty filter should be no more than 150 Pa  
(1.5 mbar) and the dirty filter warning light will be on.  
A resistance higher than this indicates that the filters  
must be replaced.  
After commissioning, the DualAir® unit will require  
maintenance to be carried out annually. If the  
DualAir® unit is used in a dirty or dusty area, more  
frequent maintenance may be necessary.  
Installation, service and annual inspection of heater  
must be done by a contractor qualified in the  
installation and service of gas-fired heating  
equipment.  
13.2 Burner Maintenance  
1. Open the hinged door and remove the burner  
compartment cover. See Page 37, Section 16.2.  
2. Clean any deposits from the main burner which  
may have formed in the injectors or venturi of  
WARNING  
3. Remove the ignition electrode and flame probe.  
Check condition of ignition electrode and flame  
probe. Clean off any deposits which may have  
been formed, check condition of ceramic  
insulators. Replace as necessary.  
Cut Hazard  
13.3 Fan/Motor Assembly Maintenance  
Turn off gas and electrical supply before maintenance.  
Fan can start automatically at any time.  
The main fan bearings are permanently sealed and  
do not need lubrication. Before cleaning, turn off gas  
and electrical supply. Remove the fan compartment  
covers and use a small brush or duster to clean the  
fan blades from each side. Replace fan(s) when  
done.  
Failure to follow these instructions can result in severe  
injury or product damage.  
NOTE 1: After any maintenance or repair work  
always test fire the heater in accordance with the  
commissioning instructions on Page 21, Section 11  
through Page 24, Section 11.9 to ensure all safety  
systems are in working order before leaving the  
heater to operate. Minor faults may be traced by  
using the troubleshooting charts on Page 31,  
Figure 16: Belt Tension  
8 mm to 10 mm  
Fan  
Pulley  
Motor  
Pulley  
NOTE 2: Check all gas pipes and pipe joints to  
ensure there are no cracks or gas leaks.  
Check the condition and tension of the drive belts.  
The condition is best inspected with the belts  
removed. Check for chaffing or lateral cracks.  
Replace belts as a matched pair as necessary.  
Do not over-tighten belts, as this may cause bearing  
damage.  
NOTE 3: Inspect all suspended components and  
hardware. Insure that they are in good condition,  
properly tightened, and corrosion free.  
13.1.1 Cooling Equipment  
The cooling coil does not require maintenance  
except that during filter replacement it is  
recommended to clean the surface of the coil with a  
soft brush and vacuum cleaner. Carry out any  
maintenance recommended by the condenser  
manufacturer.  
13.4 Heat Exchanger Maintenance  
The heat exchanger will remain clean unless a  
problem has developed with combustion. Inspect the  
heat exchanger. Look for signs of overheating at the  
front tubes which may indicate burner over firing or  
persistently low air flows.  
13.1.2 Filters  
The air filters should be inspected regularly to  
ensure that no excessive build up of deposit is being  
experienced. If heavy deposit is being formed, then  
the filters may be cleaned using a vacuum cleaner.  
Filters should be replaced at least every four months  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
SECTION 13: SERVICING  
13.5 Gas Control Valve Maintenance  
No regular maintenance is required on these  
devices. To change gas control valves, See Page  
Do not repair or disassemble on site.  
Replace faulty gas valves with genuine  
ROBERTS GORDON® replacement parts.  
13.6 Flue Fan  
The flue fan should not require maintenance.  
However, If the air pressure switch is causing burner  
lockout then remove the flue fan from the vent box.  
See Page 39, Section 16.4. Ensure that the fan is  
free to run and that the fan wheel is clean.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 14: CONVERSION BETWEEN GASES  
14.1 General  
Conversion between gasses will require a change of  
burner injectors and the gas valve re-commissioning  
to the new conditions.  
14.2 Burner Conversion  
Conversion of the burner assembly from one gas to  
the other is the same for all types of heaters.  
1. Remove the burner compartment cover as  
2. Remove the connection between the gas valve  
outlet and the manifold. See Page 36, Section  
16.1 for gas valve removal.  
3. Remove the manifold from the burner assembly  
by removing the screws at the top and bottom.  
See Page 37, Section 16.2.1.  
4. Remove the main burner injectors.  
5. Replace with the injectors for the new gas  
ensuring a gas tight seal.  
6. Refit all components in reverse order.  
14.3 Gas Valves  
All gas valves used on the DualAir® units have  
pressure regulators that may be set to operate on  
natural gas or LPG.  
Conversion is carried out by re-setting the burner  
pressure to the value in the data table during  
commissioning. See Page 7, Section 4.3.  
Ensure that the gas inlet pressure to the heater is  
correct for the new gas, and that the gas supply has  
been purged of the old gas.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
SECTION 15: TROUBLESHOOTING  
SECTION 15: TROUBLESHOOTING  
15.1 General  
WARNING  
Explosion Hazard  
Installation must be done by a registered installer/  
contractor qualified in the installation and service of  
gas-fired heating equipment or your gas supplier.  
Failure to follow these instructions can result in death,  
injury or property damage.  
Start  
Are gas & electrical  
supplies on?  
No  
Turn on supplies.  
Yes  
Is Red lockout  
Yes  
No  
Use 15.2 to test burner.  
warning light on?  
No  
Press the white button on  
the combination fan/limit  
thermostat. Does the  
fan run now?  
Use 15.5 to test fan.  
Does the fan run?  
No  
Yes  
See sections 5.3 & 11.3 to  
check combination  
fan/limit thermostat settings.  
Does the fan run?  
Replace combination  
fan/limit thermostat.  
No  
No  
Yes  
No  
Yes  
With external controls on,  
does the burner continue  
through the heating cycle?  
Is combination fan/limit  
thermostat set correctly?  
See sections 5.3 &11.3.  
Adjust or replace  
as necessary.  
Has burner “Locked Out”?  
No  
Yes  
Use 15.2 to test burner.  
Yes  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44(0) 190 249 8733  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as shown on Page 21, Section 11  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
15.2 Troubleshooting For Automatic Ignition Burner Systems  
There are two burner controls used. Honeywell S4563C and  
S4565C. They both have similar operating sequences. To  
measure flame current, connect a 0 - 50 μA DC meter in  
series with the flame probe. If the meter reads negative  
values, then reverse the test leads.  
WARNING  
Electrical Shock Hazard  
Do not touch ignition components.  
Start  
Voltage from ignition components is high.  
Are gas & electrical  
supplies on?  
Turn on supplies.  
No  
Failure to follow these instructions can  
result in death or electrical shock.  
Yes  
Have limit thermostats  
operated or light faulty?  
Reset or replace as  
necessary.  
Is the green light on?  
Are external controls on?  
Yes  
No  
Yes  
No  
Yes  
Press in lockout reset button  
on rear of heater or remote  
reset button if fitted.  
Is red lockout light on?  
No  
Is 230v supply at fan  
connections?  
Does flue fan run?  
Yes  
Flue fan faulty replace  
No  
Burner control faulty or plug  
in connections faulty. Repair  
or replace as necessary  
Yes  
Check for too much flue/air inlet  
duct. Check for blockage in  
combustion air circuit.  
Check for faulty air pressure  
switch. See section 16.5.  
Does air pressure switch  
change over?  
No  
Yes  
Is HT lead okay and  
Ignition control faulty  
replace.  
Wait 30 - 40 seconds.  
connected?  
No  
No  
Yes  
Yes  
Is ignition spark operating?  
Is spark electrode okay?  
See Section 15.6.  
Yes  
Is the gas valve operating?  
To test valve,  
Replace valve.  
Does the flame light?  
No  
No  
see Section 15.4.  
Yes  
Is the flame current at  
least 1 µAmp DC when  
the flame lights?  
Trace fault in supervision  
system. See Section 16.3.  
Is red lockout light on?  
No  
For your safety and optimum heater performance  
use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as shown  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44(0) 190 249 8733  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 15: TROUBLESHOOTING  
15.3 Troubleshooting for Flame Supervision System  
START  
Connect a DC ammeter in  
series with the flame probe.  
Is the green light on and  
at least 1 µA DC fame  
current?  
Use section 15.1 to  
No  
Yes  
Yes  
trace the fault.  
Yes  
Is the connecting lead  
damaged? Is the flame probe  
damaged or touching earthed  
components?  
Is there a current flowing in the  
flame probe circuit with no  
flame present?  
Repair or replace as  
Yes  
Yes  
necessary.  
No  
Is inlet burner gas pressure  
correct? Is live and neutral  
polarity correct? Is  
Does “lockout” occur when  
there is a flame present?  
Control box faulty.  
Replace with correct type.  
flame probe circuit correct?  
No  
Repair or replace as  
necessary.  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44(0) 190 249 8733  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
15.4 Troubleshooting for Solenoid Valves  
START  
Is 230v at the valve  
terminals at the  
appropriate time.  
No  
No  
Fault elsewhere  
Fault elsewhere  
Yes  
Is gas pressure at inlet of the  
valve correct for gas type?  
Note pressure found.  
Yes  
Valve faulty.  
Replace with one of  
correct type.  
Does gas pressure at outlet  
of the valve rise when  
valve turns on?  
No  
No  
No  
Yes  
Does gas pressure at  
outlet of valve return to zero or  
lower when valve turns off?  
Valve faulty.  
Replace with one of  
correct type.  
Yes  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44(0) 190 249 8733  
Valve Operating  
TROUBLESHOOT ENDS.  
15.5 Troubleshooting for Main Fan  
START  
Is Power supply 400 V  
between any two phases or  
230 V between any Phase and  
N at the main terminal block?  
Does fan run  
automatically?  
Fault elsewhere.  
Check wiring.  
No  
No  
Yes  
Is there 230v between  
terminals 1 and N of the  
main terminal block?  
Does fan run when the white  
button of combination fan/limit  
thermostat is pushed in?  
Combination fan/limit  
thermostat faulty.  
Replace with correct type.  
No  
No  
Yes  
Yes  
Yes  
Use Section 5.3 & 11.3 to check  
combination fan/limit  
thermostat settings. Reset or  
replace as necessary.  
Fan motor or contactor faulty.  
Replace with correct type.  
Use Section 15.6 to  
trace fault.  
Does fan turn on and  
off while burner is firing  
continously?  
Yes  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44(0) 190 249 8733  
Fan Operating  
TROUBLESHOOT ENDS.  
No  
For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as shown on Page 21, Section 11  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 15: TROUBLESHOOTING  
15.6 Troubleshooting for Fan Contactor  
START  
Does main fan run  
Wiring faulty or faulty  
combination thermostat.  
Investigate.  
Is power supply 400v at  
three phase and N at the  
main terminal?  
automatically  
Fault elsewhere  
No  
No  
in heating mode?  
No  
Yes  
Does fan run when white  
button of combination  
thermostat is pushed in?  
Is there 230v between  
terminals 96 and A1 on  
the contactor?  
Has fuse 1 on the  
printed circuit board  
blown?  
Is there 230v at contactor  
coil terminal A1 and A2?  
Press in overload reset  
button and retest.  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Overload operated. Check for  
three phases at mains  
terminals, loose electrical  
terminals and motor overload.  
Replace  
combination thermostat.  
Contactor faulty.  
Replace.  
Replace fuse and  
investigate.  
Overload Faulty  
Replace.  
Yes  
Are fan belts  
loose or broken?  
Transpose two incoming  
phase connections.  
Does fan motor run with  
little or no air flow?  
Is fan/motor rotation  
No  
No  
Yes  
correct?  
Yes  
Replace or tighten belts.  
No  
Check filters and  
ducting for blockage.  
Yes  
Relay R1 faulty.  
Replace.  
Does fan run  
No  
No  
as burner fires?  
Yes  
Does main fan run  
automatically  
in cooling mode?  
Does fan run at cooling  
stage 1 (T11 live)?  
Relay R2 faulty.  
Replace.  
No  
Yes  
Does fan run at cooling  
stage 2 (T12 live)?  
Relay R3 faulty.  
Replace.  
No  
Yes  
Fan Operating  
TROUBLESHOOT ENDS.  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44(0) 190 249 8733  
For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as
on Page 21, Section 11  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
SECTION 16: REMOVAL AND REPLACEMENT PARTS  
Figure 17: Standard Regulator Removal  
See warnings and notes on Page 28, Section 13  
before removing or replacing parts.  
Sealing  
Washer  
Burner Components  
All serviceable burner parts are accessed by the  
door on the side of the heater.  
16.1 Gas Valve  
The VR4605 gas valve is fitted with the V7335A  
Modureg regulator (P/N L512) supplied as a  
separate component.  
Remove Standard  
Regulator  
Fit the Modureg ensuring that the rubber seal is in  
place and the two screws are tight. See Page 36,  
Section 16.1.1. Once fitted follow commissioning  
procedure in Section 11.  
When replacing the gas valve, the Modureg will  
need to be fitted on site. To fit the Modureg, remove  
the standard regulator by removing the two screws  
retaining the rubber sealing washer. See Page 36,  
16.1.1 Gas Valve Replacement - (all models)  
Rubber  
Seal  
Step 1  
Unscrew  
gas pipe  
from the  
valve inlet.  
Ignition  
Control  
Modureg Modulating  
Regulator  
Step 2  
Unscrew valve from the  
burner manifold  
Description  
Gas Valve VR4605  
Ignition Control  
Part Number  
90033404  
90434020  
or  
unscrew the screws for  
the inlet and outlet flanges.  
16.1.2 Gas Valve Replacement continued- (all models)  
Replace in reverse order. Verify that the gas flow  
direction of the valve is correct. Re-use the "O" ring  
seal in the outlet flange where fitted. Check that all  
the joints are leak free. Reset gas valve.  
IT IS IMPORTANT THAT ONLY THE CORRECT  
GAS VALVES SPECIFIED FOR EACH MODEL  
TYPE ARE USED WHEN REPLACING THESE  
CONTROLS.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
SECTION 16: REMOVAL AND REPLACEMENT PARTS  
16.2 Burner Compartment  
The burner compartment is a sealed  
compartment. Following any work,  
re-seal the compartment with the gas  
pipe rubber seal fully in place and all  
screws fitted and tight.  
Burner  
compartment  
cover  
Flame probe  
Viewing port  
for flame probe  
Remove flexible  
air duct from spigot  
Ignition electrode  
Viewing port  
for ignition electrode  
Remove  
access plate  
Rubber Seal  
Remove screws and  
pull off burner cover  
16.2.1 Burner Injectors  
Ensure gas tight fitting of injectors.  
Ensure correct alignment with burners.  
Ensure all pipe joints are gas tight.  
Manifold  
Burners  
Injectors  
Remove manifold  
screws and pull  
out manifold  
Manifold  
Unscrew  
Injectors  
Burner  
screws  
Marking  
MODEL  
75  
90  
100  
115  
Injector Quantity  
12  
14  
15  
17  
Natural Gas (G20) and (G25)  
mm dia  
in dia  
2.71  
2.71  
2.71  
2.71  
Injector  
Size  
0.1067  
0.1067  
0.1067  
0.1067  
Marking  
RG P/N  
36  
36  
36  
36  
91930036  
91930036  
91930036  
91930036  
LPG Gas Propane (G31) and LPG Gas Butane (G30)  
mm dia  
in dia  
1.51  
0.0594  
53  
1.51  
0.0594  
53  
1.51  
0.0594  
53  
1.51  
0.0594  
53  
Injector  
Size  
Marking  
RG P/N  
91930053  
91930053  
91930053  
91930053  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
16.3 Ignition Electrode and Flame Probe.  
Fan/Limit Thermostat  
Burners  
Secondary  
Limit  
Thermostat  
Flame  
Probe  
Flame  
Probe  
Remove all  
burner compartment  
screws to remove  
the burner  
Remove  
Screw  
compartment and  
access the  
“Front View”.  
Burner Compartment  
Front Views  
Ignition  
Electrode  
Ignition  
Electrode  
(3 mm)  
.120"  
spark  
gap  
Burners  
To replace the ignition electrode or flame probe, remove the electrical lead and screw.  
Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the  
front view of the burner compartment.  
Description  
Spark Electrode  
Part Number  
90427411  
Automatic Ignition Flame Probe  
Burners (all models)  
90439300  
92000000  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 16: REMOVAL AND REPLACEMENT PARTS  
16.4 Flue Fan  
Remove screws securing outlet  
flange to the flue adapter.  
Rear Panel  
Flue Adapter  
to Flue Fan  
screws  
Hole  
Vent Box  
Flue  
Adapter  
Vent Box  
screws  
Outlet  
Gasket  
Flue Fan  
Disconnect  
electrical connections  
at plug in tabs.  
Remove screws securing flue  
fan mounting plate to vent box  
Remove screws securing  
mounting plate to fan.  
Vent Box  
Mounting  
Plate  
Refit in reverse.  
Mounting Plate  
to Vent Box  
screws  
Use new gaskets.  
Ensure sealed joints.  
Ensure mounting plate orifice is  
clear and not obstructed.  
Gasket  
Gasket  
Mounting Plate  
to Flue Fan  
screws  
Air Plate  
MODEL  
75  
90  
100  
115  
Torin DSF  
146-052  
077274  
AO Smith  
JFIG07INS  
AO Smith  
JFIG07INS  
AO Smith  
JFIG07INS  
Flue Fan  
RG P/N  
90710001  
97.0  
90710001  
103.6  
90710001  
110.5  
90710450  
152.4  
Air Plate  
[mm dia]  
[in dia]  
3.82  
4.08  
4.35  
6
RG P/N  
11011134  
11011133  
11011132  
11011131  
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS  
USED WHEN REPLACING THESE ITEMS.  
Carry out a commission after working on or changing a flue fan. See Page 25, Section 12.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
16.5 Heater Pressure Switch  
Pull off 3 way connector. Spring open plastic clips of  
mounting cradle. Replace with correct type of  
pressure switch for model. The pressure switches  
are colour coded for each pressure setting.  
WARNING  
Carry out a commission after working on or  
changing a pressure switch.  
Carbon Monoxide Hazard  
Use correct pressure switch specified for each model.  
Use of incorrect pressure switch could cause unsafe  
condition.  
Failure to follow these instructions can result in  
death or serious injury.  
Pressure Switch  
RG P/N  
75  
90439811  
grey  
90  
100  
90439811  
grey  
115  
90439807  
brown  
90439807  
brown  
Colour Code  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 16: REMOVAL AND REPLACEMENT PARTS  
16.6 Cooling Coil Safety Devices  
16.6.1 Cooling Coil Frost Thermostat  
Coil Pressure Switch  
(Normally open contact) used to prove adequate air  
flow for safe operation of cooling coil.  
The sensing element for this device is inserted into  
the pocket of the cooling coil situated through the  
access hole in the coil cover.  
Filter Pressure Switch  
(Normally open contact) used to give indication of  
filter becoming blocked.  
The frost thermostat has two settings marked as set  
point with an arrow head and "diff". The control  
should be set at 5° C with a 1° C differential.  
To replace, remove coil compartment cover.  
Disconnect wires noting their position. Remove the  
flexible tubing noting the position of the tube  
connection. Replace in reverse order and check  
operation.  
To replace, remove screw and pull off knob.  
Remove cover. Disconnect wires.  
Pull the sensing element out of the pocket in the coil.  
Replace in reverse order.  
16.6.2 Pressure Switches  
The coil and dirty filter pressure switches are preset  
and different. They are differential pressure switches  
measuring the pressure loss across the coil or filter.  
Figure 18: Cooling Coil Safety Devices.  
Red  
White  
Coil Frost Thermostat  
set at 5°C with 1°C diff.  
Coil Pressure Switch  
set at 0.57 mbar (.23 in wc)  
Filter Pressure Switch  
set at 1.17 mbar (.47 in wc)  
White  
Filter  
Red  
N.O  
Connections  
Negative  
Pressure  
Positive  
Pressure  
Set  
Point  
Description  
Part Number  
90439801  
90439804  
K018  
Coil Pressure Switch  
Filter Pressure Switch  
Coil Frost Thermostat  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
16.7 Ignition Control  
IT IS IMPORTANT THAT ONLY THE CORRECT  
IGNITION CONTROL SPECIFIED FOR EACH  
MODEL TYPE IS USED WHEN REPLACING  
THESE ITEMS.  
16.7.1 S4563C  
This control is mounted at the electrical mounting  
plate. Pull out the 3 cable connectors.  
Pull out ignition cable, ignition earth and flame probe  
cable noting their positions. Remove the screws.  
Refit in reverse. Ensure correct location of ignition  
and flame probe cables.  
16.8 Fan Motor Removal  
Belt Tension  
Adjustment  
Locknut  
Jacking Screw  
Position  
(ensure tight)  
(adjust both ends  
the same to ensure  
motor is parallel  
to fan case)  
Motor Fixing  
Bolts  
Taper Lock  
Screws  
Pivot Bolts  
(ensure tight)  
1. Disconnect the electrical connections at the  
contactor and pull the cable back to the fan  
motor.  
2. Slacken the belt tensioning nuts and remove  
the drive belts.  
3. Unscrew the motor mounting bolt.  
(motor is heavy, may need two people)  
4. Remove the motor pulley by using a hexagonal  
key to remove the taper lock screws. Use one  
of these screws to fit into the centre jacking  
screw and tighten into this position to separate  
the taper lock bush and the pulley.  
5. Replace in reverse order.  
Use a straight edge to ensure both pulleys line  
up. Ensure the pulley fixing screws are tight  
and belt tension is correct (use new belts if  
required). Ensure motor rotation is correct.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SECTION 16: REMOVAL AND REPLACEMENT PARTS  
16.8.1 Fan Removal and Replacement  
Fan Plate  
Fan Outlet Flange  
Securing Screws  
Fan Mounting  
Brackets  
(re-use on new fan)  
Bracket Screws  
(re-use on new fan)  
Fan Foot  
Screws  
Description  
Torin Fan DDC 270-270  
Torin Fan DDC 241-241  
Part Number  
A047  
A049  
Mounting Rail  
1. Remove motor leaving the pulley in place.  
3. Fit a new thermostat ensuring that the correct  
temperature setting and type are selected. See  
2. Remove screws securing the fan outlet flange  
to the fan panel. (captive nuts)  
4. Reconnect wires and test operation.  
3. Remove nuts and bolts securing the fan feet to  
the mounting brackets.  
4. Slide the fan out.  
(fan is heavy, may need two people)  
5. Remove the fan mounting brackets from the  
fan. Retain components to fit to new fan.  
6. Remove the fan pulley by using a hexagonal  
key to remove the taper lock screws. Use one  
of these screws to fit into the centre jacking  
screw and tighten into this position to separate  
the taper lock bush and the pulley.  
7. Refit the components above to the new fan and  
refit in reverse order.  
8. Check belt alignment and tension.  
9. Check fan rotation is correct.  
16.9 Combination Fan/Limit Thermostat  
16.9.1 Removal and Replacement  
1. Remove wires.  
2. Remove the mounting screws.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL  
Figure 19: Combination Fan/Limit Thermostat  
WARNING  
Fire Hazard  
Break-off link must be removed from replacement  
thermostat.  
Heat exchanger damage may result.  
Failure to follow these instructions can result in  
death, injury, property damage or product damage.  
Dial  
Set Point 3 Limit Temp.  
Set Point 2 Fan On  
Set Point 1 Fan Off  
Push Screwdriver in  
and hold to release  
Push in Lock  
Wire to Controlled Equipment  
Fan Terminals  
Limit Stat  
Manual  
Reset Button  
(Red)  
Manual Fan Switch  
(White)  
Pull out for normal operation.  
Push in for continuous fan.  
Limit Terminals  
BREAK-OFF LINK  
MUST BE REMOVED  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Attach this information to the wall near the ROBERTS GORDON® heater.  
®
Read the installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.  
OPERATING INSTRUCTIONS  
WARNING  
1. STOP! Read all safety instructions on this information sheet.  
2. Open the manual gas valve in the heater supply line.  
3. Turn on electric power to the heater.  
4. Set the thermostat to desired setting (above ambient temperature).  
The automatic starting sequence begins.  
NOTE: Following long shutdown periods, the burner control may go to  
to 'LOCKOUT' during the start sequence. Push the reset button to  
recommence firing. Contact service department if 'LOCKOUT'  
continues (see manual for details).  
TO TURN OFF THE HEATER  
Fire Hazard  
1. Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF'  
immediately, but fans will continue to cool heat exchanger until the fan  
thermostat switches off.  
Some objects can catch fire or explode when placed  
close to heater.  
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,  
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER  
Keep all flammable objects, liquids and vapors the  
required clearances to combustibles away from heater.  
1. Set the thermostat to off or the lowest setting.  
2. Turn off electric power to the heater.  
3. Turn off the manual gas valve in the heater supply line.  
4. Call your registered installer/contractor qualified in the installation  
and service of gas-fired heating equipment.  
Failure to follow these instructions can result in death,  
injury or property damage.  
Roof Terminal  
Installation Clearances  
Clearances to Combustibles  
Alternative  
Wall  
Terminal  
Air  
Intake  
Flue  
15 cm  
15 cm  
50 cm**  
50 cm  
Air Flow  
60 cm  
Condense Drain  
Install to  
suitable drain  
30 cm  
3 m  
Insulated  
Refrigerant pipes  
to cooling coil  
by Customer  
2.5 - 3.5 m*  
Customers  
Suitable  
Condenser  
Unit  
**80 cm is necessary to service heater.  
Roberts-Gordon, LLC  
1250 William Street  
P.O. Box 44  
Roberts-Gordon Europe Limited  
Unit A, Kings Hill Business Park  
Darlaston Road, Wednesbury  
West Midlands WS10 7SH UK  
Telephone: +44 (0)121 506 7700  
Fax: +44 (0)121 506 7701  
Telephone: 716.852.4400  
Fax: 716.852.0854  
Service Telephone: +44 (0)121 506 7709  
Service Fax: +44 (0)121 506 7702  
Toll Free: 800.828.7450  
Buffalo, NY 14240-0044 USA  
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment  
sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service  
and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment  
and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.  
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.  
Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives.  
Please contact us for any further information you may require, including the Installation, Operation and Service Manual.  
This products are not for residential use.  
© 2007 Roberts-Gordon, LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical,  
including photocopying, recording, taping, or information storage and retrieval systems – without written permission of Roberts-Gordon.  
Printed in U.S.A  
P/N 91040089  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Raymarine Marine Radio RAY230E User Guide
RCA Flat Panel Television RLCDV3282A User Guide
RedMax Trimmer SRTZ2460F User Guide
Reebok Treadmill RT 80 User Guide
Reliable Iron C55LB User Guide
Renesas Camera Accessories RH850 User Guide
Samsung Answering Machine 6B User Guide
Samsung Bluetooth Headset WEP301 User Guide
Samsung Camcorder WB750 User Guide
SDI Technologies Computer Hardware SDIO Card User Guide