Powerware Power Supply FE QFE 500VA User Manual

®
Powerware FERRUPS  
FE/QFE UPS  
Installation Guide  
500 VA–18 kVA, 50 and 60 Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
®
Powerware FERRUPS  
FE/QFE UPS  
Installation Guide  
500 VA–18 kVA, 50 and 60 Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Class A EMC Statements  
FCC Part 15  
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to  
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when  
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency  
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio  
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case  
the user will be required to correct the interference at his own expense.  
ICES-003  
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment  
Regulations ICES-003.  
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.  
For Users in Germany  
We hereby certify that the uninterruptible power system (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, 1.4 kVA, 1.8 kVA,  
2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) complies with the RFI suppression  
requirements of Vfg. 243/1991 and Vfg. 46/1992. The German Postal Service was notified that the equipment is being  
marketed. The German Postal Service has the right to retest the equipment and verify compliance.  
Hiermit wird bescheinigt, daß die unterbrechungsfreie Stromversorgung (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA,  
1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) in Übereinstimmung mit  
den Bestimmungen der Vfg. 243/1991 und Vfg. 46/1992 funkentstört ist. Der Deutschen Bundespost wurde das  
Inverkehrbringen dieses Gerätes angezeigt und die Berechtigung zur Überprüfung der Serie auf Einhaltung der  
Bestimmung eingeräumt.  
Powerware reserves the right to change specifications without prior notice.  
Powerware is a registered trademark of Powerware Corporation.  
Copyright 2002 Powerware, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any  
way without the express written approval of Powerware.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
Plug-Receptacle Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Hardwired Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
1
2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
3 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Equipment Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Storage and Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
4 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
5 External Bypass Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Installation Wiring Diagrams for External Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
6 Internal Bypass Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Installation Wiring Diagrams for Internal Bypass Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
7 Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Before Installing the Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
Installing and Connecting the Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56  
Replacing the Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
Recycling the Used Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
8 Phase Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 1  
INTRODUCTION  
The Powerware FERRUPS uninterruptible power system (UPS) is  
available in plug-receptacle or hardwired models. The plug-receptacle  
models have an input plug and receptacles on the rear panel. The  
hardwired models have terminal strips that an electrician has to wire to  
AC input.  
See the following sections for steps on how to use this manual for your  
UPS installation.  
Plug-Receptacle Installation  
Only a few sections in this manual are required for installing  
plug-receptacle models:  
: Be sure to read all safety warnings before installing the UPS as stated  
in Chapter 2, “Safety Warnings.”  
: Complete Chapter 3, “Setup” for setting up the location of the UPS.  
: If you purchased an external battery cabinet, an electrician must wire  
the battery to the UPS as described in Chapter 7, “Battery Cabinet  
Installation.”  
: Continue to the startup section in the Powerware FERRUPS FE/QFE  
UPS (500 VA–18kVA) User’s Guide.  
Hardwired Installation  
Most of the sections in this manual are required for the electrician to  
install the hardwired models:  
: Be sure to read all safety warnings before installing the UPS as stated  
in Chapter 2, “Safety Warnings.”  
: Complete Chapter 3, “Setup” for setting up the location of the UPS.  
: Chapter 4, “Electrical Installation” describes the electrical  
requirements for hardwiring the UPS.  
: Continue to either Chapter 5, “External Bypass Switch Installation”  
or Chapter 6, “Internal Bypass Switch Installation” depending on the  
the type of bypass switch being installed.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
: If you purchased an external battery cabinet, see Chapter 7, “Battery  
Cabinet Installation” for wiring connections.  
: Complete the phase check as described in Chapter 8, “Phase Check.”  
: Continue to the startup section in the Powerware FERRUPS FE/QFE  
UPS (500 VA–18kVA) User’s Guide.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 2  
SAFETY WARNINGS  
Read the following precautions before you install the UPS.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you  
should follow during installation and maintenance of the UPS and batteries. Please  
read all instructions before operating the equipment and save this manual for future  
reference.  
DANGER  
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed  
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER  
SERVICEABLE PARTS inside the UPS.  
WARNING  
: This UPS contains its own energy source (batteries). The output receptacles may  
carry live voltage even when the UPS is not connected to an AC supply.  
: Do not remove or unplug the input cord when the UPS is turned on. This removes  
the safety ground from the UPS and the equipment connected to the UPS.  
: To reduce the risk of fire or electric shock, install this UPS in a temperature and  
humidity controlled, indoor environment, free of conductive contaminants. Ambient  
temperature must not exceed 40°C (104°F). Do not operate near water or  
excessive humidity (95% max).  
: To comply with international standards and wiring regulations, the total equipment  
connected to the output of this UPS must not have an earth leakage current  
greater than 1.5 milliamperes.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
CAUTION  
: Batteries can present a risk of electrical shock or burn from high short-circuit  
current. Observe proper precautions. Servicing should be performed by qualified  
service personnel knowledgeable of batteries and required precautions. Keep  
unauthorized personnel away from batteries.  
: Proper disposal of batteries is required. Refer to your local codes for disposal  
requirements.  
: Never dispose of batteries in a fire. Batteries may explode when exposed to flame.  
Sikkerhedsanvisninger  
VIGTIGE SIKKERHEDSANVISNINGER  
GEM DISSE ANVISNINGER  
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE  
SIKKERHEDSANVISNINGER  
FARE  
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og  
vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af  
UPS’ens indvendige dele kan repareres af brugeren.  
ADVARSEL!  
: Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan  
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.  
: Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er  
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.  
: Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit  
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk  
stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær  
vand eller høj fugtighed (maksimalt 95%).  
: I overensstemmelse med internationale normer og bestemmelser for el-installation  
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke  
overskride en jordafdelingsspænding på mere end 1,5 milliampere.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
ADVARSEL  
: Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj  
kortslutningsspænding. De korrekte forholdsregler bør overholdes.  
: Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for  
bortskaffelsesprocedurer.  
: Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere  
ved åben ild.  
Belangrijke Veiligheidsinstructies  
BELANGRIJKE VEILIGHEIDSINSTRUCTIES  
BEWAAR DEZE INSTRUCTIES  
DEZE HANDLEIDING BEVAT BELANGRIJKE  
VEILIGHEIDSINSTRUCTIES  
GEVAAR  
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en  
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden  
uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER  
kunnen worden GEREPAREERD.  
WAARSCHUWING  
: Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen  
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is  
aangesloten.  
: Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit  
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen  
aardebeveiliging meer hebben.  
: Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in  
een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd,  
waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur  
mag 40°C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge  
vochtigheid (max. 95%).  
: Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de  
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen  
aardlekstroom van meer dan 1,5 milliampère hebben.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
OPGELET  
: Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als  
gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.  
: De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw  
plaatselijke voorschriften.  
: Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.  
Tarkeita Turvaohjeita  
TÄRKEITÄ TURVAOHJEITA - SUOMI  
SÄILYTÄ NÄMÄ OHJEET  
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA  
VAARA  
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot  
on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä  
MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.  
VAROITUS  
: Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla  
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.  
: Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa  
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.  
: Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,  
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia  
epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä  
ja vältä kosteita tiloja (95 % maksimi).  
: Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän  
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä  
1,5 milliampeeria (mA).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
VARO  
: Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään  
oikosulkuun. Noudata asianmukaisia ohjeita.  
: Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia  
määräyksiä.  
: Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.  
Consignes de sécurité  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ  
IMPORTANTES  
DANGER!  
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de  
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.  
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.  
AVERTISSEMENT!  
: Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie  
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le  
secteur.  
: Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous  
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.  
: Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur  
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la  
température et l’humidité ambiantes sont contrôlées. La température ambiante ne  
doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère  
excessivement humide (95 % maximum).  
: Afin d’être conforme aux normes et règlements internationaux de câblage, le  
courant de fuite à la terre de la totalité du matériel branché sur la sortie de  
l’onduleur ne doit pas dépasser 1,5 mA.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
ATTENTION!  
: Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par  
des courts-circuits de haute intensité. Prendre les précautions nécessaires.  
: Une mise au rebut réglementaire des batteries est obligatoire. Consulter les  
règlements en vigueur dans votre localité.  
: Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire  
exploser.  
Sicherheitswarnungen  
WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN.  
DIESES HANDBUCH ENTHÄLT WICHTIGE  
SICHERHEITSANWEISUNGEN.  
WARNUNG  
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten  
sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine  
vom Benutzer zu wartenden Komponente.  
ACHTUNG  
: Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den  
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an  
einer Wechselspannungsquelle angeschlossen ist.  
: Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet  
ist, weil hierdurch die Sicherheitserdung von der USV und den daran  
angeschlossenen Geräten entfernt wird.  
: Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden  
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine  
leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C  
nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher  
Luftfeuchtigkeit (max. 95 %) betreiben.  
: Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an  
den Ausgang dieser USV angeschlossenen Geräte zusammen einen  
Erdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
VORSICHT!  
: Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder  
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind  
unbedingt zu beachten.  
: Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen  
Bestimmungen zu beachten.  
: Batterien niemals verbrennen, da sie explodieren können.  
:
:
:
°
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
:
:
:
:
Avvisi di sicurezza  
IMPORTANTI ISTRUZIONI DI SICUREZZA  
CONSERVARE QUESTE ISTRUZIONI  
QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI  
SICUREZZA  
PERICOLO  
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le  
operazioni di riparazione e di manutenzione devono essere effettuate  
ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo  
statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.  
AVVERTENZA  
: Questo gruppo statico di continuità contiene una fonte di energia autonoma (le  
batterie). Le prese di uscita possono condurre tensione energizzata quando il  
gruppo statico di continuità non è collegato con una fonte di alimentazione a  
corrente alternata.  
: Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di  
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di  
sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di  
continuità in un ambiente interno a temperatura ed umidità controllata, privo di  
agenti contaminanti conduttivi. La temperatura ambiente non deve superare i  
40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità  
eccessiva (95% max).  
: Per conformità con gli standard internazionali e con le norme in merito al  
cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di  
continuità non deve avere una corrente di dispersione di terra superiore a  
1,5 milliampere.  
ATTENZIONE  
: Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da  
alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.  
: Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento  
fare riferimento alle disposizioni locali.  
: Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle  
fiamme.  
Viktig Sikkerhetsinformasion  
FARLIG  
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må  
kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE  
SERVICE PÅ NOEN AV DELENE i UPS’en.  
FARLIG  
: Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være  
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.  
: Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at  
ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet  
med den.  
: For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et  
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for  
ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må  
ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere  
total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med  
internasjonale standarder og forkablingsbestemmelser.  
FORSIKTIG  
: Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy  
kortslutningsstrøm. Følg instruksene.  
: Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om  
fjerning av batterier.  
: Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.  
Regulamentos de Segurança  
INSTRUÇÕES DE SEGURANÇA IMPORTANTES  
GUARDE ESTAS INSTRUÇÕES  
ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA  
IMPORTANTES  
CUIDADO  
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser  
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não  
há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.  
ADVERTÊNCIA  
: Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída  
podem conter voltagem ativa quando a UPS não se encontra conectada a uma  
fonte de alimentação de corrente alternada.  
: Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto  
removerá o aterramento de segurança da UPS e do equipamento conectado.  
: Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente  
interno com temperatura e umidade controladas e livres de contaminadores  
condutíveis. A temperatura ambiente não deve exceder 40°C. Não opere próximo a  
água ou em umidade excessiva (máx: 95%).  
: Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o  
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga  
à terra maior que 1,5 miliampères.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
PERIGO  
: As baterias podem apresentar o risco de choque elétrico, ou queimaduras  
provenientes de alta corrente de curto-circuito. Observe as instruções adequadas.  
: Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do  
local para maiores informações sobre os regulamentos de descarte de produtos.  
: Nunca jogue as baterias no fogo, porque há risco de explosão.  
Предупреждения по мерам безопасности  
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
СОХРАНИТЕ ЭТИ УКАЗАНИЯ  
ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ  
УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
ОПАСНО  
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ.  
Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО  
УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ.  
Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.  
ПРЕДУПРЕЖДЕНИЕ  
: Данный ИБП содержит собственные источники энергии  
(аккумуляторы). На выходных розетках может иметься напряжение,  
даже когда ИБП не подключен к сети переменного тока.  
: Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки  
при включенном ИБП. При этом защитное заземление отключается  
от ИБП и от оборудования, подключенного к ИПБ.  
: Для снижения опасности пожара или поражения электрическим  
током устанавливайте ИБП в закрытом помещении с  
контролируемыми температурой и влажностью, в котором  
отсутствуют проводящие загрязняющие вещества. Температура  
окружающего воздуха не должна превышать 40°С. Не  
эксплуатируйте устройство около воды или в местах с повышенной  
влажностью (макс. 95%).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Для обеспечения соблюдения требований международных  
стандартов и требований к разводке электрических цепей,  
суммарная величина тока утечки на землю всего оборудования,  
подключенного к выходу ИБП, не должна превышать  
1,5 миллиампера.  
ОСТОРОЖНО  
: Аккумуляторы могут вызвать опасность поражения электрическим  
током или ожога от тока короткого замыкания. Соблюдайте  
соответствующие меры предосторожности.  
: Необходимо соблюдать правила утилизации аккумуляторов.  
Обратитесь к местным нормативным актам за информацией о  
требованиях к утилизации.  
: Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут  
взорваться под воздействием огня.  
Advertencias de Seguridad  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD  
IMPORTANTES  
PELIGRO  
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico  
deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO  
AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro  
del SIE.  
ADVERTENCIA  
: Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de  
salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a  
un suministro de corriente alterna (c.a.).  
: No retire o desenchufe el cable de entrada mientras el SIE se encuentre  
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos  
conectados al SIE.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un  
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes  
conductores. La temperatura ambiente no debe exceder los 40°C. No trabaje cerca  
del agua o con humedad excesiva (95% máximo).  
: Para cumplir con los estándares internacionales y las normas de instalación, la  
totalidad de los equipos conectados a la salida de este SIE no debe tener una  
intensidad de pérdida a tierra superior a los 1,5 miliamperios.  
PRECAUCIÓN  
: Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras  
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones  
correspondientes.  
: Es necesario desechar las baterías de un modo adecuado. Consulte las normas  
locales para conocer los requisitos pertinentes.  
: Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las  
expone a la llama.  
Säkerhetsföreskrifter  
VIKTIGA SÄKERHETSFÖRESKRIFTER  
SPARA DESSA FÖRESKRIFTER  
DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA  
SÄKERHETSFÖRESKRIFTER  
FARA  
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD  
SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som  
ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.  
VARNING  
: Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan  
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.  
: Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort  
skyddsjordningen från både UPS-enheten och den anslutna utrustningen.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
: Minska risken för brand eller elektriska stötar genom att installera denna  
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga  
ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C.  
Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).  
: För att överensstämma med internationell standard och installationsföreskrifter får  
inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha  
läcksström som överstiger 1,5 milliampere.  
VIKTIGT  
: Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.  
Följ tillämpliga anvisningar.  
: Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.  
: Använda batterier får aldrig brännas upp. De kan explodera.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 3  
SETUP  
This chapter explains the requirements for setting up the UPS:  
: UPS, battery cabinet, and bypass switch dimensions  
: Equipment clearances  
: Location requirements  
: Moving the UPS and batteries  
: Storage and operating environment  
Dimensions  
Table 1. FERRUPS FE/QFE 500 VA–3.1 kVA Dimensions  
Dimensions (See Figure 1)  
Height (A)  
122 (30.5 cm)  
15.12 (38.5 cm)  
21.22 (54.0 cm)  
Width (B)  
102 (25.5 cm)  
15.22 (39.0 cm)  
15.252 (39.0 cm)  
Depth (C)  
UPS Model  
500 VA, 700 VA, and 850 VA  
1.15 kVA and 1.4 kVA  
1.8 kVA, 2.1 kVA, and 3.1 kVA  
21.252 (54.0 cm)  
20.22 (51.5 cm)  
22.92 (58.5 cm)  
D
A
F
C
E
B
Figure 1. UPS Dimensions  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup  
Table 2. FERRUPS FE/QFE 4.3–18 kVA Dimensions  
Dimensions (See Figure 1)  
Height (D)  
Width (E)  
Depth without  
Internal Bypass (F)  
Depth with Internal  
Bypass Switch (F)  
UPS Model  
4.3 kVA and 5.3 kVA  
29.52 (75.0 cm) 15.52 (39.5 cm)  
252 (63.5 cm)  
332 (84.0 cm)  
7 kVA, 10 kVA, 12.5 kVA, and 18 kVA 36.52 (93.0 cm) 192 (48.5 cm)  
322 (81.5 cm)  
402 (102.0 cm)  
Table 3. Battery Cabinet Dimensions  
Dimensions (See Figure 2)  
Width  
Height  
Depth  
Model  
ASY-0468  
12.252 (31.5 cm)  
372 (94.0 cm)  
492 (124.5 cm)  
512 (129.5 cm)  
15.752 (40.0 cm)  
192 (48.5 cm)  
152 (38.5 cm)  
302 (76.5 cm)  
28.52 (72.5 cm)  
322 (81.5 cm)  
322 (81.5 cm)  
322 (81.5 cm)  
ASY-0386  
ASY-0387  
ASY-0385 and ASY-0685  
Figure 2. Battery Cabinet Dimensions  
Table 4. Bypass Switch Dimensions  
Dimensions (See Figure 3)  
C
A
B
D
E
Model  
BPE-01  
122 (30.5 cm)  
162 (40.6 cm)  
172 (43.2 cm)  
62 (15.2 cm)  
82 (20.3 cm)  
122 (30.5 cm)  
132 (33.0 cm)  
172 (43.2 cm)  
182 (45.7 cm)  
102 (25.4 cm)  
122 (30.5 cm)  
162 (40.6 cm)  
32 (7.6 cm)  
72 (17.8 cm)  
92 (22.9 cm)  
BPE-02  
BPE-04 and BPE-05  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup  
B
E
E
B
A
C
A
C
D
D
BPE-01  
BPE-02, 04, and 05  
Figure 3. Bypass Switch Dimensions  
Equipment Clearances  
All cabinet sizes require the following clearances to allow for servicing  
and adequate ventilation:  
Table 5. Clearances for the UPS and Battery Cabinets  
Dimensions (see Figure 4)  
Sides (G)  
Front (H)  
Top (I)  
Back (J)  
362 (91.5 cm)  
362 (91.5 cm)  
122 (30.5 cm)  
42 (10.0 cm)  
NOTE A minimum clearance of 42 (10 cm) is required on the sides, front, and back  
and 122 (30.5 cm) above the UPS for proper ventilation.  
NOTE For 4.3–18 kVA models with an internal bypass switch, measure from the back  
of the switch.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup  
I
I
J
G
H
H
G
Figure 4. Installation and Service Clearances  
Location Requirements  
Install the FERRUPS as close as possible to the equipment to be  
protected. If the UPS is more than 25 ft (7.6m) from the equipment,  
transient noise can reappear in the electrical distribution system. The  
UPS should be well ventilated and away from direct sunlight or other  
heat source.  
The environment can affect the reliability and performance of both the  
UPS and the batteries. Verify the storage and operating environmental  
requirements on page 21.  
If additional FERRUPS system batteries are in a separate external battery  
cabinet, the cabinet should be located as close as possible to the  
FERRUPS UPS. If the batteries will be further from the unit than the  
standard cables allow, contact your service representative or your local  
distributor for assistance.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup  
Storage and Operating Environment  
Storage Temperature: Store the batteries (in the UPS or external battery  
cabinet) at -20° to +40°C (-4° to +104°F). Batteries will have a longer  
shelf life if they are kept below 25°C (77°F). The UPS or external battery  
cabinet without batteries may be stored at -20° to +60°C (-4° to  
+140°F).  
Ventilation: The air around the UPS must be clean and free of dust,  
corrosive chemicals, and other contaminants. The air must be free to  
circulate around the UPS and battery cabinet(s).  
NOTE Do not place the UPS or batteries in a sealed room or container.  
Operating Temperature: The UPS can operate from 0° to +40°C (+32° to  
+104°F). Do not operate near water or excessive humidity (95% max).  
For full battery life, keep the UPS at an ambient temperature of 25°C  
(77°F).  
High Altitude Operation: The maximum operating temperature drops 1°C  
per 300m (2°F per 1000 ft) above sea level. Maximum elevation is  
3000m (10,000 ft).  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 4  
ELECTRICAL INSTALLATION  
NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on  
page 53 to install optional battery cabinets or to the startup section in the Powerware  
FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide.  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the  
hardwired installation. Risk of electrical shock.  
Before installing your UPS, complete the following information:  
1. From the ID label on the UPS rear panel:  
Model number:  
Input voltage:  
Output voltage:  
2. From the bypass switch label:  
Model number:  
Internal or External?  
Make-Before-Break (MBB) or Break-Before-Make (BBM)?  
3. Verify that the UPS input and output voltages are what is  
required for your application:  
Does the input voltage for the UPS at the AC service panel  
match the input voltage in Step 1?  
Does the output voltage in Step 1 match the output voltage of  
the equipment you are using with the UPS?  
NOTE The FERRUPS provides single-phase power only.  
4. If you answered NO to either question in Step 3, contact your  
service representative or your local distributor for assistance.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Installation  
Bypass Switches  
Bypass switches are available in two types: external (a separate cabinet  
that is wall-mounted) or internal (attached to the back of the UPS). The  
bypass switch has three positions as described in Table 6.  
Table 6. Bypass Switch Positions  
Switch Position Description  
LINE  
Connects the load directly to AC input power and disconnects UPS output.  
AC input power is still connected to the UPS input.  
OFF  
Disconnects the load from the UPS output power and AC input power.  
Connects the UPS output to the load.  
UPS  
NOTE In all three positions, AC input power is still connected to the input terminals  
inside the UPS (once the UPS is installed). Use the AC disconnect switch (located on  
the right side of the bypass switch) to disconnect AC input power during maintenance  
or service.  
Bypass switches may be MBB or BBM.  
An MBB switch makes a new connection before it breaks the original  
connection. For example, if you turn an MBB switch from UPS to LINE,  
the bypass switch connects the load to AC input power before  
disconnecting the load from UPS output power.  
NOTE MBB switches are not for use with 208 Vac.  
A BBM switch breaks the original connection before it makes a new one.  
If you turn a BBM switch from UPS to LINE, the switch disconnects the  
load from UPS output power before connecting the load to AC input  
power.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Installation  
Table 7 and Table 8 show the bypass switch models available for the  
FERRUPS UPS.  
Table 7. External Bypass Switch Specifications  
Model  
Number  
Ratings (UL/CSA)  
Continuous  
Ratings (TÜV)  
Continuous  
Weight  
BPE-01  
BPE-02  
BPE-04  
BPE-05  
30A/300 Vac  
40A/300 Vac  
80A/300 Vac  
104A/300 Vac  
30A/300 Vac  
50A/300 Vac  
80A/300 Vac  
120A/300 Vac  
8.25 lb/3.7 kg  
19.75 lb/9 kg  
30 lb/13.6 kg  
32.75 lb/14.9 kg  
Table 8. Internal Bypass Switch Specifications  
Model Number  
BPI-02  
Ratings (UL/CSA) Continuous Ratings (TÜV) Continuous  
40A/300 Vac  
46A/ 300 Vac  
80A/ 300 Vac  
104A/300 Vac  
50A/300 Vac  
55A/300 Vac  
80A/300 Vac  
120A/300 Vac  
BPI-03  
BPI-04  
BPI-05  
Figure 5 shows a UPS with a separate battery cabinet and an external  
bypass switch. Continue to Chapter 5, “External Bypass Switch  
Installation” on page 29 for electrical connections.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Installation  
External  
Bypass Switch  
AC  
Bypass  
Switch  
Disconnect  
Building  
Service  
Panel  
Load  
Distribution  
Panel  
Line  
Off  
UPS  
Off  
On  
Connect to (DC)  
External Batteries  
UPS  
Figure 5. Typical Hardwired Installation with External Bypass Switch  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Installation  
Figure 6 shows a UPS with a separate battery cabinet and an internal  
bypass switch. Internal bypass switches are available only for FE/QFE  
4.3–18 kVA models. Continue to Chapter 6, “Internal Bypass Switch  
Installation” on page 45 for electrical connections.  
Back of UPS  
Internal Bypass Switch  
AC  
Disconnect  
Bypass  
Switch  
Building  
Service  
Panel  
Load  
Distribution  
Panel  
Line  
Off  
UPS  
Off  
On  
Connect to (DC)  
if there are  
External Batteries  
Figure 6. Typical Hardwired Installation with Internal Bypass Switch  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Installation  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 5  
EXTERNAL BYPASS SWITCH INSTALLATION  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the  
hardwired installation. Risk of electrical shock.  
CAUTION  
Before you install the bypass switch, verify that the bypass switch and the AC  
disconnect switch are in the OFF position.  
1. Identify the installation wiring diagram that applies to your  
FERRUPS (see Table 9).  
Table 9. External Bypass Switch Wiring Diagrams  
Model (Frequency)  
UPS Input Voltage UPS Output Voltage Bypass Switch Type  
Wiring Diagram  
Figure 8 on page 36  
Figure 9 on page 37  
FE 500 VA–3.1 kVA  
120  
120  
MBB or BBM  
(60Hz)  
208 or 240  
120/208 or 120/240  
MBB or BBM  
For 208V, use BBM only  
208 or 480 source*/  
240 input  
120/240  
MBB or BBM  
Figure 10 on page 38  
QFE 500 VA–3.1 kVA  
(50 Hz)  
120  
220, 230, 240  
220  
120  
220, 230, 240  
220  
MBB or BBM  
MBB or BBM  
BBM  
Figure 8 on page 36  
Figure 11 on page 39  
Figure 8 on page 36  
FE 1.15 kVA–3.1 kVA  
(60 Hz)  
*With a step-up or step-down transformer.  
**Contact your service representative for (a) single-phase installations that do not have the same input and output voltage,  
or (b) split-phase installations that require 220 Vac.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
Model (Frequency)  
UPS Input Voltage UPS Output Voltage Bypass Switch Type  
Wiring Diagram  
FE 4.3–18 kVA (60 Hz)  
120  
120  
MBB or BBM  
Figure 12 on page 40  
(4.3–7 kVA only)  
208 or 240  
120/208 or 120/240  
120/240  
MBB or BBM  
For 208V, use BBM only  
Figure 13 on page 41  
Figure 14 on page 42  
208 or 480 source*/  
240 input  
MBB or BBM  
220**  
220  
BBM  
Figure 15 on page 43  
Figure 15 on page 43  
QFE 4.3–18 kVA (50 Hz)  
220, 230, or 240  
220, 230, or 240  
MBB or BBM  
*With a step-up or step-down transformer.  
**Contact your service representative for (a) single-phase installations that do not have the same input and output voltage,  
or (b) split-phase installations that require 220 Vac.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
2. Review the installation wiring diagram and applicable notes to  
find the proper circuit breaker size for your installation. In the  
US, see Table 10 to size the wire. In other areas, use 75°C  
copper wire and size according to the local code.  
Table 10. Recommended Wire Sizes  
Input Circuit Breaker Size  
75°C Copper Wire Size  
2
15A, 20A  
25A, 30A  
35A, 40A, 45A, 50A  
60A  
12 AWG (3.3 mm )  
2
10 AWG (5.3 mm )  
2
8 AWG (8.4 mm )  
2
6 AWG (13.3 mm )  
2
70A, 80A  
90A, 100A  
110A  
4 AWG (21.2 mm )  
2
3 AWG (26.7 mm )  
2
2 AWG (33.6 mm )  
2
125A  
1 AWG (42.1 mm )  
2
150A  
1/0 AWG (53.5 mm )  
2
This table lists the AWG and mm wire size for each circuit breaker size shown on the wiring diagrams. The minimum  
recommended circuit breaker sizes for each model and voltage application are listed on the wiring diagrams.  
Conductor sizes shall be no smaller than the 75°C wire size based on the ampacities given in Table 310–16 of the National  
Electrical Code, ANSI/NFPA 70-1999, and article 220. All circuit conductors, including the neutral and equipment grounding  
conductors, must be the same size (ampacity) wire. Code may require a larger AWG size than shown in this table because  
of temperature, number of conductors in the conduit, or long service runs. Follow local code requirements.  
3. Mount the bypass switch within sight of the UPS. If you do not  
have a Powerware bypass switch with an AC disconnect switch  
or the fuse box or panel is out of sight, you must install a  
separate disconnect switch next to the UPS.  
4. Remove the screws in the lower part of the bypass switch front  
cover and remove the lower cover panel.  
Remove the knockouts or plugs in the bottom of the bypass  
switch for AC Line Input, AC to UPS Input, AC from UPS  
Output, and AC to the UPS load.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
CAUTION  
To prevent electrical shock or damage to your equipment, verify that the UPS ON/OFF  
switch is in the OFF position before you remove the UPS front cover panel. The circuit  
breaker or disconnect switch must be turned off at the AC input service panel.  
5. Remove the UPS front cover panel according to the UPS model:  
FE or QFE 500 VA–3.1 kVA  
: Remove the #1 Phillips grounding screw on top of the UPS.  
: Remove and save the sticker in the lower right corner of the  
UPS front cover panel with the Powerware logo.  
: Use a #2 Phillips screwdriver to loosen (but not remove) the  
screw.  
: Slide the UPS front cover panel forward until it is completely  
off the UPS.  
FE or QFE 4.3–18 kVA  
: Remove the screws on the UPS side panels using a Phillips  
screwdriver.  
: Loosen (but do not remove) the three Phillips screws on the  
bar across the top of the UPS.  
: Slide the top of the UPS side panels out.  
: Lift the panels to remove them.  
6. Remove the knockouts in the UPS rear panel for AC Input and  
AC Output. If your UPS has a separate battery cabinet, also  
remove the knockout for DC.  
7. Install the conduit adapters. AC Input and AC Output  
conductors must be run through separate pieces of conduit.  
UPS output circuits shall be installed in dedicated conduit  
systems and not shared with other electrical circuits.  
CAUTION  
To prevent electrical shock or damage to your equipment, verify that the AC input is  
OFF at the service panel and the bypass and AC disconnect switches are in the OFF  
position before you connect any wires to the bypass switch terminal strip.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
8. Find the terminal strip inside the bypass switch. Using the label  
on the back of the switch’s lower front cover panel, wire the  
terminal strip and tighten all connections securely. Use copper  
wire and the appropriate wire size for the current. See Figure 7  
for sample terminal strip labels.  
BPE-01  
BPE-02,  
BPE-04,  
and  
BPE-05  
Figure 7. External Bypass Switch Terminal Strip Labels  
9. Using the installation wiring diagram, wire the UPS terminal  
strip and complete the AC wiring.  
NOTE Terminal strip connections should be exactly as shown in the installation  
wiring diagram to ensure proper phasing. Good ground connections are necessary to  
reduce electrical noise and ensure safe operation of the UPS and the load.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
10. If your UPS does not have an external battery cabinet(s),  
continue to “Phase Check” on page 65.  
If your UPS has an external battery cabinet(s), continue to  
“Battery Cabinet Installation” on page 53.  
Installation Wiring Diagrams for External Bypass Switches  
The following notes are referenced in the external bypass switch wiring  
diagrams (Figure 8 through Figure 15). To determine which diagram is  
correct for your site, see Table 9 on page 29.  
NOTE 1 The customer must provide input overcurrent protection as stated in NEC  
Section 240-21 or local codes. Size the protection device according to local code  
requirements.  
NOTE 2 The UPS bypass switch/AC disconnect must be installed within sight of the  
UPS. To properly install, complete the phase check starting on page 65.  
NOTE 3 The customer must provide and install this ground connection according to  
NEC Sections 250-20(d), 250-30, 250-62, and 250-64 or local requirements. This  
grounding electrode conductor must be at least #8 AWG (8.36 mm)), per NEC  
table 250-66. If the UPS input circuit conductors are larger than #8 AWG (8.36 mm ),  
Powerware requires the grounding electrode conductor to be the same size (ampacity)  
as the largest UPS input circuit conductor. Refer to NEC Section 110-3(b). Conduit is  
not considered an acceptable grounding electrode conductor. Powerware does not  
recommend routing the grounding electrode conductor through metallic conduit. This  
conductor may require protection from physical damage according to local  
requirements.  
NOTE 4 All circuit conductors, including the neutral and equipment grounding  
conductors, must be the same size (ampacity) and have the same rating (75°C copper  
wire), and must be sized according to the input protection device.  
NOTE 5 The customer must provide output overcurrent protection as stated in NEC  
Section 240-21 or local codes. Size the protection device according to local code  
requirements.  
NOTE 6 For maximum protection against electrical noise, use isolated ground  
receptacles. Refer to NEC Section 250-146(d) or local requirements.  
NOTE 7 For service, the UPS requires 362 (91.5 cm) clearance on the sides and in  
front, 122 (30.5 cm) above the UPS, and 42 (10.0 cm) behind the UPS. A minimum  
clearance of 42 (10 cm) is required on the sides, front, and back and 122 (30.5 cm)  
above the UPS for proper ventilation. See “Equipment Clearances” on page 19 for  
clearances before installing the UPS. Use flexible metal conduit on the UPS or the  
external battery cabinet if either must be moved.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
NOTE 8 External UPS batteries are optional. The battery cable must not be  
disconnected if a load is applied. Shut off the UPS before disconnecting the cable. See  
“Battery Cabinet Installation” on page 53 for external battery cabinet installation.  
NOTE 9 UPS output circuits must be installed in dedicated conduit and not shared  
with other electrical circuits.  
NOTE 10 The load fuse or circuit breaker should be sized to match the load current  
requirements.  
NOTE 11 For 208 Vac, use a step-up transformer. For 480 Vac, use a step-down  
transformer. Use an isolation transformer with a 120/240 grounded center-tapped  
neutral output. Do not use a buck/boost transformer.  
NOTE 12 For 120/208/240 models, connect X1 on the UPS to L1 on the bypass switch;  
for 208 Vac, connect the bypass switch L2 to the UPS XT1; for 240 Vac, connect the  
bypass switch L2 to the UPS XT2.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
QFE: 50 Hz 120 Vac Input and Output OR  
FE: 60 Hz 120 Vac Input and Output OR  
FE 1.15–3.1 kVA only: 60 Hz 220 Vac Input and Output (with single-voltage output)  
For 220 Vac, use only a BBM switch.  
Figure 8. FE or QFE 500 VA–3.1 kVA UPS with External Bypass Switch  
Table 11. Minimum Recommended Circuit Breakers for 60 Hz 120 Vac  
Charger  
Standard  
15A  
500 VA, 700 VA, and 850 VA  
1.15 kVA  
1.4 kVA  
15  
1.8 kVA  
20  
2.1 kVA  
25  
3.1 kVA  
35  
15  
15  
20  
20  
40  
45  
50  
Table 12. Input Current for 50 Hz 120 Vac - Size Overcurrent Protection According to Local Code  
Voltage and Charger  
120V, Standard Charger  
120V, 15A Charger  
500 VA  
4.4A  
700 VA  
5.8A  
850 VA 1.15 kVA 1.4 kVA  
1.8 kVA  
15A  
2.1 kVA  
16A  
3.1 kVA  
24A  
7.0A  
12A  
8.4A  
13A  
11A  
14A  
8.9A  
11A  
27A  
28A  
35A  
Table 13. Input Current for 60 Hz 220 Vac - Size Overcurrent Protection According to Local Code  
60 Hz Voltage  
220V, Standard Charger  
220V, 15A Charger  
1.15 kVA  
4.6A  
1.4 kVA  
5.8A  
1.8 kVA  
7.8A  
2.1 kVA  
9.4A  
3.1 kVA  
12A  
7A  
8A  
15A  
17A  
21A  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output  
For 208 Vac, use only a BBM switch.  
Figure 9. FE 500 VA–3.1 kVA UPS with External Bypass Switch  
Table 14. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac  
208 Vac  
240 Vac  
Charger 500 VA –1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 500 VA –1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA  
Standard  
15A  
15  
15  
15  
20  
15  
25  
20  
30  
15  
15  
15  
20  
15  
20  
15  
25  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer)  
Figure 10. FE 500 VA–3.1 kVA UPS with External Bypass Switch  
Table 15. Minimum Recommended Circuit Breakers for 240 Vac  
Charger  
Standard  
15A  
500 VA–1.4 kVA  
1.8 kVA  
15  
2.1 kVA  
15  
3.1 kVA  
15  
15  
15  
20  
20  
25  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
50 Hz 220, 230, or 240 Vac Input and Output  
Figure 11. QFE 500 VA–3.1 kVA UPS with External Bypass Switch  
Table 16. Input Current - Size Overcurrent Protection According To Local Code  
Voltage Charger  
220 Vac Standard  
15A  
500 VA  
2.6A  
4.7A  
2.5A  
4.6A  
2.4A  
4.6A  
700 VA  
3.9A  
6.0A  
3.8A  
5.9A  
3.5A  
5.7A  
850 VA  
4.4A  
6.5A  
4.2A  
6.3A  
4.0A  
6.2A  
1.15 kVA 1.4 kVA  
1.8 kVA  
7.9A  
14A  
2.1 kVA  
8.2A  
15A  
3.1 kVA  
13A  
4.9A  
7.0A  
4.6A  
6.7A  
4.4A  
6.6A  
5.7A  
7.8A  
5.4A  
7.5A  
5.2A  
7.4A  
19A  
230 Vac Standard  
15A  
7.5A  
14A  
7.8A  
14A  
12A  
18A  
240 Vac Standard  
15A  
7.2A  
14A  
7.4A  
14A  
12A  
19A  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
60 Hz 120 Vac Input - 120 Vac Output  
Figure 12. FE 4.3–7 kVA UPS with External Bypass Switch  
Table 17. Minimum Recommended Circuit Breakers for 120 Vac  
Charger  
Standard  
10A  
4.3 kVA  
40  
5.3 kVA  
50  
7 kVA  
70  
45  
60  
70  
20A  
50  
60  
70  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output  
For 208 Vac, use only a BBM switch.  
Figure 13. FE 4.3–18 kVA UPS with External Bypass Switch  
Table 18. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac  
208 Vac  
240 Vac  
Charger  
4.3  
kVA  
5.3  
kVA  
7
kVA  
10  
kVA  
12.5  
kVA  
18  
kVA  
4.3  
kVA  
5.3  
kVA  
7
kVA  
10  
kVA  
12.5  
kVA  
18  
kVA  
Standard  
10A  
25  
25  
30  
30  
30  
35  
40  
40  
40  
60  
70  
70  
80  
80  
90  
110  
125  
125  
20  
20  
25  
25  
30  
35  
35  
35  
35  
50  
60  
60  
70  
70  
80  
100  
100  
110  
20A  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer)  
Figure 14. FE 4.3–18 kVA UPS with External Bypass Switch  
Table 19. Minimum Recommended Circuit Breakers for 240 Vac  
Charger  
Standard  
10A  
4.3 kVA  
20  
5.3 kVA  
25  
7 kVA  
35  
10 kVA  
50  
12.5 kVA  
18 kVA  
100  
70  
70  
80  
20  
30  
35  
60  
100  
20A  
20  
35  
35  
60  
110  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
QFE: 50 Hz 220, 230, or 240 Vac Input and Output OR  
FE: 60 Hz 220 Vac Input and Output  
For FE 60 Hz 220 Vac, use only a BBM switch.  
Figure 15. FE or QFE 4.3–18 kVA UPS with External Bypass Switch  
Table 20. Input Current - Size Overcurrent Protection According To Local Code  
Voltage  
Charger  
Standard  
10A  
4.3 kVA  
17A  
18A  
20A  
19A  
22A  
23A  
18A  
20A  
21A  
17A  
19A  
20A  
5.3 kVA  
21A  
23A  
25A  
21A  
23A  
25A  
20A  
22A  
24A  
19A  
21A  
23A  
7 kVA  
27A  
28A  
30A  
27A  
28A  
29A  
26A  
27A  
28A  
24A  
26A  
27A  
10 kVA  
41A  
49A  
52A  
43A  
46A  
51A  
41A  
44A  
49A  
39A  
43A  
47A  
12.5 kVA  
53A  
18 kVA  
81A  
85A  
89A  
81A  
84A  
89A  
78A  
81A  
85A  
75A  
78A  
82A  
60 Hz  
220 Vac  
60A  
20A  
65A  
50 Hz  
220 Vac  
Standard  
10A  
55A  
58A  
20A  
63A  
50 Hz  
230 Vac  
Standard  
10A  
53A  
56A  
20A  
60A  
50 Hz  
240 Vac  
Standard  
10A  
51A  
54A  
20A  
58A  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Bypass Switch Installation  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 6  
INTERNAL BYPASS SWITCH INSTALLATION  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the  
hardwired installation. Risk of electrical shock.  
CAUTION  
Before you install the bypass switch, verify that the bypass switch and the AC  
disconnect switch are in the OFF position.  
1. Identify the installation wiring diagram that applies to your  
FERRUPS (see Table 21).  
Table 21. Internal Bypass Switch Wiring Diagrams  
Model (Frequency)  
UPS Input Voltage UPS Output Voltage Bypass Switch Type  
Wiring Diagram  
FE 4.3–18 kVA (60 Hz)  
120  
120  
MBB or BBM  
Figure 17 on page 49  
(4.3–7 kVA only)  
208 or 240  
120/208 or 120/240  
120/240  
MBB or BBM  
For 208V, use BBM only  
Figure 18 on page 50  
Figure 19 on page 51  
208 or 480 source*/  
240 input  
MBB or BBM  
220**  
220  
BBM  
Figure 20 on page 52  
Figure 20 on page 52  
QFE 4.3–18 kVA (50 Hz)  
220, 230, or 240  
220, 230, or 240  
MBB or BBM  
*With a step-up or step-down transformer.  
**Contact your service representative for (a) single-phase installations that do not have the same input and output voltage,  
or (b) split-phase installations that require 220 Vac.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
2. Review the installation wiring diagram and applicable notes to  
find the proper circuit breaker size for your installation. In the  
U.S., see Table 22 to size the wire. In other areas, use 75°C  
copper wire and size according to the local code.  
Table 22. Recommended Wire Sizes  
Input Circuit Breaker Size  
75°C Copper Wire Size  
2
15A, 20A  
25A, 30A  
35A, 40A, 45A, 50A  
60A  
12 AWG (3.3 mm )  
2
10 AWG (5.3 mm )  
2
8 AWG (8.4 mm )  
2
6 AWG (13.3 mm )  
2
70A, 80A  
90A, 100A  
110A  
4 AWG (21.2 mm )  
2
3 AWG (26.7 mm )  
2
2 AWG (33.6 mm )  
2
125A  
1 AWG (42.1 mm )  
2
150A  
1/0 AWG (53.5 mm )  
2
This table lists the AWG and mm wire size for each circuit breaker size shown on the wiring diagrams. The minimum  
recommended circuit breaker sizes for each model and voltage application are listed on the wiring diagrams.  
Conductor sizes shall be no smaller than the 75°C wire size based on the ampacities given in Table 310–16 of the National  
Electrical Code, ANSI/NFPA 70-1999, and article 220. All circuit conductors, including the neutral and equipment grounding  
conductors, must be the same size (ampacity) wire. Code may require a larger AWG size than shown in this table because  
of temperature, number of conductors in the conduit, or long service runs. Follow local code requirements.  
3. Remove the screws in the lower part of the bypass switch front  
cover and remove the lower cover panel.  
Remove the knockouts or plugs in the bottom of the bypass  
switch for AC Line Input, AC from UPS Output, and AC to the  
UPS load.  
4. Install the conduit adapters. AC Input and AC Output  
conductors must be run through separate pieces of conduit.  
UPS output circuits shall be installed in dedicated conduit  
systems and not shared with other electrical circuits.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
CAUTION  
To prevent electrical shock or damage to your equipment, verify that the AC input is  
OFF at the service panel and the bypass and AC disconnect switches are in the OFF  
position before you connect any wires to the bypass switch terminal strip.  
5. Find the terminal strip inside the bypass switch. Using the label  
on the back of the switch’s lower front cover panel, wire the  
terminal strip and tighten all connections securely. Use copper  
wire and the appropriate wire size for the current. See Figure 16  
for a sample terminal strip label.  
Figure 16. Internal Bypass Switch (BPI) Terminal Strip Label  
6. Using the installation wiring diagram, wire the UPS-internal  
bypass terminal strip and complete the AC wiring.  
NOTE Terminal strip connections should be exactly as shown in the installation  
wiring diagram to ensure proper phasing. Good ground connections are necessary to  
reduce electrical noise and ensure safe operation of the UPS and the load.  
7. If your UPS does not have an external battery cabinet(s),  
continue to “Phase Check” on page 65.  
If your UPS has an external battery cabinet(s), continue to  
“Battery Cabinet Installation” on page 53.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
Installation Wiring Diagrams for Internal Bypass Switches  
The following notes are referenced in the internal bypass switch wiring  
diagrams (Figure 17 through Figure 20). To determine which diagram is  
correct for your site, see Table 21 on page 45.  
NOTE 1 The customer must provide input overcurrent protection as stated in NEC  
Section 240-21 or local codes. Size the protection device according to local code  
requirements.  
NOTE 2 To properly install, complete the phase check starting on page 65.  
NOTE 3 The customer must provide and install this ground connection according to  
NEC Sections 250-20(d), 250-30, 250-62, and 250-64 or local requirements. This  
2
grounding electrode conductor must be at least #8 AWG (8.36 mm ), per NEC  
table 250-66. If the UPS input circuit conductors are larger than #8 AWG (8.36 mm ),  
2
Powerware requires the grounding electrode conductor to be the same size (ampacity)  
as the largest UPS input circuit conductor. Refer to NEC Section 110-3(b). Conduit is  
not considered an acceptable grounding electrode conductor. Powerware does not  
recommend routing the grounding electrode conductor through metallic conduit. This  
conductor may require protection from physical damage according to local  
requirements.  
NOTE 4 All circuit conductors, including the neutral and equipment grounding  
conductors, must be the same size (ampacity) and have the same rating (75°C copper  
wire), and must be sized according to the input protection device.  
NOTE 5 The customer must provide output overcurrent protection per NEC  
Section 240-21 or local codes. Size the protection device according to local code  
requirements.  
NOTE 6 For maximum protection against electrical noise, use isolated ground  
receptacles. Refer to NEC Section 250-146(d) or local requirements.  
NOTE 7 For service, the UPS requires 362 (91.5 cm) clearance on the sides and in  
front, 122 (30.5 cm) above the UPS, and 42 (10.0 cm) behind the bypass switch. A  
minimum clearance of 42 (10 cm) is required on the sides, front, and back and 122  
(30.5 cm) above the UPS for proper ventilation. See “Equipment Clearances” on  
page 19 for clearances before installing the UPS. Use flexible metal conduit on the  
UPS or the external battery cabinet if either must be moved.  
NOTE 8 External UPS batteries are optional. The battery cables are connected to the  
DC terminals on the DIN RAIL in the UPS. See “Battery Cabinet Installation” on  
page 53 for external battery cabinet installation.  
NOTE 9 UPS output circuits shall be installed in dedicated conduit systems and not  
shared with other electrical circuits.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
NOTE 10 The load fuse or circuit breaker should be sized to match the load current  
requirements.  
NOTE 11 For 208 Vac, use a step-up transformer For 480 Vac, use a step-down  
transformer. Use an isolation transformer with a 120/240 grounded center-tapped  
neutral output. Do not use a buck/boost transformer.  
60 Hz 120 Vac Input - 120 Vac Output  
Figure 17. FE 4.3–7 kVA UPS with Internal Bypass Switch  
Table 23. Minimum Recommended Circuit Breakers for 120 Vac  
Charger  
Standard  
10A  
4.3 kVA  
40  
5.3 kVA  
50  
7 kVA  
70  
45  
60  
70  
20A  
50  
60  
70  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output  
For 208 Vac, use only a BBM switch.  
Figure 18. FE 4.3–18 kVA UPS with Internal Bypass Switch  
Table 24. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac  
208 Vac  
240 Vac  
Charger  
4.3  
kVA  
5.3  
kVA  
7
kVA  
10  
kVA  
12.5  
kVA  
18  
kVA  
4.3  
kVA  
5.3  
kVA  
7
kVA  
10  
kVA  
12.5  
kVA  
18  
kVA  
Standard  
10A  
25  
25  
30  
30  
30  
35  
40  
40  
40  
60  
70  
70  
80  
80  
90  
110  
125  
125  
20  
20  
25  
25  
30  
35  
35  
35  
35  
50  
60  
60  
70  
70  
80  
100  
100  
110  
20A  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer)  
Figure 19. FE 4.3–18 kVA UPS with Internal Bypass Switch  
Table 25. Minimum Recommended Circuit Breakers for 240 Vac  
Charger  
Standard  
10A  
4.3 kVA  
20  
5.3 kVA  
25  
7 kVA  
35  
10 kVA  
50  
12.5 kVA  
18 kVA  
100  
70  
70  
80  
20  
30  
35  
60  
100  
20A  
25  
35  
35  
60  
110  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Internal Bypass Switch Installation  
QFE: 50 Hz 220, 230, or 240 Vac Input and Output  
FE: 60 Hz 220 Vac Input and Output  
For FE 60 Hz 220 Vac, use only a BBM switch.  
Figure 20. FE or QFE 4.3–18 kVA UPS with Internal Bypass Switch  
Table 26. Input Current - Size Overcurrent Protection According To Local Code  
Voltage  
Charger  
Standard  
10A  
4.3 kVA  
17A  
18A  
20A  
19A  
22A  
23A  
18A  
20A  
21A  
17A  
19A  
20A  
5.3 kVA  
21A  
23A  
25A  
21A  
23A  
25A  
20A  
22A  
24A  
19A  
21A  
23A  
7 kVA  
27A  
28A  
30A  
27A  
28A  
29A  
26A  
27A  
28A  
24A  
26A  
27A  
10 kVA  
41A  
49A  
52A  
43A  
46A  
51A  
41A  
44A  
49A  
39A  
43A  
47A  
12.5 kVA  
53A  
18 kVA  
81A  
85A  
89A  
81A  
84A  
89A  
78A  
81A  
85A  
75A  
78A  
82A  
60 Hz  
220 Vac  
60A  
20A  
65A  
50 Hz  
220 Vac  
Standard  
10A  
55A  
58A  
20A  
63A  
50 Hz  
230 Vac  
Standard  
10A  
53A  
56A  
20A  
60A  
50 Hz  
240 Vac  
Standard  
10A  
51A  
54A  
20A  
58A  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 7  
BATTERY CABINET INSTALLATION  
NOTE If you have an optional Floor Saver battery cabinet, see the Floor Saver  
instructions that came with your FERRUPS UPS.  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the  
electrical installation. Risk of electrical shock.  
CAUTION  
Full voltage and current are always present at the battery terminals. The batteries  
used in this system can produce dangerous voltages, extremely high currents and a  
risk of electric shock. They may cause severe injury if the terminals are shorted  
together or to ground (earth). You must be extremely careful to avoid electric shock  
and burns caused by contacting battery terminals or shorting terminals during battery  
installation. Do not touch uninsulated battery terminals.  
Any battery used with this UPS shall comply with the applicable requirements for  
batteries in the standard for emergency lighting and power equipment, UL 924.  
Cabinets are designed to be used with, and batteries must be replaced with,  
Powerware battery number BAT-XXXX or equivalent.  
The electrician must take these precautions:  
: Wear protective clothing and eye wear. For 120V battery systems, wear rubber  
gloves and boots. Batteries contain caustic acids and toxic materials and can  
rupture or leak if mistreated. Remove rings and metal wristwatches or other metal  
objects and jewelry. Don’t carry metal objects in your pockets where the objects  
can fall into the battery cabinet.  
: Tools must have insulated handles and must be insulated so that they will not  
short battery terminals. Do not allow a tool to short a battery terminal to another  
battery terminal or to the cabinet at any time. Do not lay tools or metal parts on  
top of the batteries, and do not lay them where they could fall onto the batteries or  
into the cabinet.  
: Install the batteries as shown on the drawing provided with the batteries. When  
connecting cables, never allow a cable to short across a battery’s terminals, the  
string of batteries, or to the cabinet.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
: Align the cables on the battery terminals so that the cable lug will not contact any  
part of the cabinet even if the battery is moved. Keep the cable away from any  
sharp metal edges.  
: Install the battery cables so they cannot be pinched by the battery cabinet or UPS  
doors.  
: Make sure the fuse is positioned so that it will not contact any cabinet parts or  
other battery posts if the batteries should move. Make sure that there is enough  
clearance when the cabinet door closes.  
: Battery cabinet chassis (ground or earth) must be connected to the UPS chassis  
(ground or earth). If you use conduit, this ground conductor must be routed in the  
same conduit as the battery conductors.  
: Where conductors may be exposed to physical damage, protect the conductors in  
accordance with ANSI/NFPA 70-1993.  
: If you are replacing batteries or repairing battery connections, follow the  
procedure in the Powerware FERRUPS FE/QFE UPS (500 VA–18kVA) User’s Guide  
to shut off your UPS and remove both AC and DC input power.  
Before Installing the Batteries  
The following items are required for battery installation. Use only tools  
with insulated handles:  
: Torque wrench calibrated in inch pounds or Newton meters  
: Petroleum jelly or conductive grease  
: Brush (to apply petroleum jelly or conductive grease to terminals)  
: Pliers  
: 92 extension  
: Standard and Phillips screwdrivers  
: Volt-ohm meter  
: Hammer  
: 7/162 socket wrench  
: Electrical tape  
: Ratchet  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
Table 27. Nominal DC Battery Voltage  
Models  
Nominal Battery  
Voltage  
QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, and 1.4 kVA  
FE 500 VA, 700 VA, and 850 VA  
12 Vdc  
24 Vdc  
48 Vdc  
QFE 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and 7 kVA  
FE 1.15 kVA, 1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and  
7 kVA  
FE and QFE 10 kVA, 12.5 kVA, and 18 kVA  
120 Vdc  
The battery cable or wire used is #1 AWG (42.11 mm2) for all  
applications with the following exceptions:  
: 18 kVA models use #1/0 (53.49 mm2) battery cables.  
: If the batteries must be some distance from the UPS, you may need to  
install larger battery cables between the battery cabinets and the UPS.  
Using long cable runs and larger diameter cables may require  
modifications inside the UPS; call your service representative if you  
did not order the longer, larger-diameter cable with the UPS.  
The UPS must have a DC disconnect switch or a removable plug so you  
can disconnect external batteries from the UPS.  
: FE/QFE 500 VA–3.1 kVA models have a removable plug at the UPS;  
the battery cabinet may also have a DC switch.  
: Most FE/QFE 4.3–18 kVA models have a DC switch at the battery  
cabinet. However, some may have a removable plug at the cabinet or  
between the UPS and the batteries, and others may have an external  
DC switch. FE/QFE 4.3–18 kVA models also have a DC switch  
behind the front cover panel.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
Installing and Connecting the Batteries  
1. Use the battery installation diagram that came with your UPS  
batteries and cabinet as you follow the steps below.  
2. Place the battery cabinet or rack as close as possible to the  
FERRUPS UPS. If the batteries will be further from the unit  
than the standard cables allow, contact your service  
representative or your local distributor for assistance.  
The battery cabinet or rack should be well ventilated and away  
from direct sunlight or other heat source. Ensure that the floor  
is level and can support the weight of the batteries, the cabinet  
or rack, and any other necessary equipment. Your Powerware  
sales coordinator can tell you the size and weight of external  
batteries.  
The temperature should be below 77°F (25°C) for the best  
battery performance. Batteries will be less efficient at  
temperatures below 65°F (18°C). High temperatures will  
reduce battery life. Typically, at about 95°F (35°C) battery life  
will be half of what it would be at a normal temperature of 77°F  
(25°C). At about 113°F (45°C), battery life will be one-fourth  
of normal.  
The batteries should be as close as possible to the UPS to  
reduce DC wiring costs and improve battery performance.  
NOTE If you are installing the batteries in a place where there may be seismic  
activity, you should anchor the UPS and battery cabinets to the floor. Anchoring kits  
are available from Powerware.  
3. Wherever conductors may be exposed to physical damage, you  
must protect the conductors in accordance with National  
Electrical Code ANSI/NFPA 70-1993. This includes battery  
cables between the UPS and the battery cabinet and cables  
between battery cabinets (if you have more than one).  
We suggest routing battery cables through flexible conduit. For  
models with a removable DC plug at the UPS end of the cables,  
we suggest routing the cables through the conduit to within  
about 122 (30.5 cm) of the UPS because the connector or plug  
does not connect to flexible conduit. Install flexible conduit for  
battery cables according to local or national code.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
4. The battery cabinet ground (or earth) must be connected to the  
UPS chassis ground (or earth).  
You must make a good connection to the battery cabinet  
chassis ground (or earth). If the battery cabinet has a terminal  
strip, you can make the ground connection at the terminal strip  
ground (or earth) lug inside the cabinet. If not, you can make  
the ground connection at one of the screws on the battery  
cabinet; to ensure a good connection, remove the paint under  
the cabinet screw.  
At the UPS, the procedure for connecting ground depends on  
your model.  
FE/QFE 500 VA–3.1 kVA: At the UPS, connect the ground wire to  
the ground lug (the green screw on the back of the UPS). This  
UPS ground (or earth) screw is marked with the label shown  
below.  
CABINET GROUND  
Figure 21. Ground Label  
FE/QFE 4.3–18 kVA: At the UPS, find the green/yellow terminal  
strip next to the UPS battery terminals. This green and yellow  
terminal strip is labeled “GROUNDING ELECTRODE  
TERMINAL;” it also has the ground or earth symbol shown  
below. Connect the ground wire to this ground terminal.  
OR  
Figure 22. Ground Symbol  
CAUTION  
Do not make connections to the RS-232 communication port if the UPS is connected to  
a positive ground battery system. The RS-232 ground must be isolated to prevent  
equipment damage. For assistance, call your service representative.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
5. Arrange the batteries in the cabinet or rack. If optional straps  
are included, install the straps as shown in the battery  
installation diagram that was packed with your batteries.  
Arrange the batteries so there is as much air flow as possible  
around the batteries and so the batteries can be cooled as much  
as possible.  
Some battery cabinets have cooling slots cut in the shelves to  
increase air flow. Arrange the batteries so these slots are not  
blocked. Some larger batteries must sit with the longest battery  
dimension in the same direction as the longest shelf dimension.  
These batteries will partly block the cooling slots. However, if  
you place the batteries next to the outside edge of the shelf to  
leave as much space between the batteries as possible, there will  
be plenty of air flow for cooling.  
CAUTION  
Never install the batteries in an air-tight enclosure.  
6. All FE and QFE models with external batteries use a fuse in the  
external battery cabinet. The external battery cabinet fuse  
protects the battery cables. The battery installation diagram  
shows the fuse type and position. A system DC fuse is inside  
the UPS.  
Connect the DC fuse(s) as shown in the battery installation  
diagram. (The fuse may be on the terminal strip.)  
7. Find the battery cable assembly that connects to the UPS. (If  
you have a removable DC plug at the UPS end, note that this  
end of the cables does not go through the conduit or connect to  
it.)  
Do not connect the external battery cables to the UPS at this  
time, but pull them through the conduit from the UPS to the  
rack or cabinet. Do not connect the cables to the batteries or  
cabinet terminals yet.  
If you have more than one external battery cabinet, find the  
battery cable assembly that will connect the battery cabinets.  
Pull the cables through the conduit that you installed between  
the cabinets.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
NOTE If you have an external DC disconnect switch between the UPS and batteries,  
see the instructions that came with your disconnect switch.  
8. Clean the cable and battery post (terminal) before you make  
the battery connection. Apply a thin coating of  
high-temperature conductive grease on the post and cable  
terminals to slow corrosion. If you use a nonconductive grease  
like petroleum jelly, do not apply any grease before you make  
the connections. Instead, make the connection first; then,  
torque it to the torque values shown below for your battery.  
After you have made the connection, apply a coating of the  
nonconductive grease to the hardware at the battery terminals.  
When you make battery terminal connections, use the torque  
wrench to tighten the battery terminal connections securely.  
For most batteries, you can find out what torque value to use  
by finding the battery number (BAT-XXXX) on the top of the  
battery. Then, use Table 28 to find the torque value for that  
battery.  
Table 28. Battery Torque Value  
Battery Type  
BAT-0046  
BAT-0048  
BAT-0050  
BAT-0053  
BAT-0103  
BAT-0122  
Torque  
Torque to 65 in lb (7.3 Nm)  
Torque to 65 in lb (7.3 Nm)  
Torque to 75 in lb (8.4 Nm)  
Torque to 40 in lb (4.5 Nm)  
Torque to 40 in lb (4.5 Nm)  
Torque to 65 in lb (7.3 Nm)  
Other batteries do not have a battery number on the top. To  
find the torque value for these batteries, check the battery  
terminal type; then, use Figure 23 to find the torque value for  
that terminal type.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
Square: Torque to  
17 in lb or 1.9 Nm.  
(BAT-0058)  
Modified Square: Torque  
to 35 in lb or 3.9 Nm.  
(BAT-0065)  
Screw Posts: Torque to  
85 in lb or 9.6 Nm.  
(BAT-0071)  
Figure 23. Battery Terminal Types  
Connect the battery cables between batteries as shown in the  
battery installation diagram. Do not connect the cables between  
battery strings or between the UPS and the batteries yet. If you  
are only using one string of batteries, go to step 11.  
9. If you are connecting more than one battery string, connect the  
positive cables as shown in the battery installation diagram.  
Next, use the voltmeter to check the DC voltage between the  
negative terminals of the strings. The measured voltage should  
be less than three volts. If it is more than three volts, correct  
any wiring errors before you go on.  
10. Use the cables provided to connect the negative () battery  
terminals of the battery strings as shown in the battery  
installation diagram. If the battery cabinet has a DC switch, the  
DC switch has been installed at the factory.  
11. To connect external batteries to your UPS, follow the  
instructions for your model:  
If your battery cabinet has a DC switch, make sure the switch is  
is in the OFF position; then, find the battery cables between the  
UPS and the batteries. The removable DC connector at one end  
of the cables connects to the UPS, and the other ends of the  
positive and negative cables connect to the external batteries.  
You should connect the cables to the batteries first. Refer to the  
battery installation diagram as you follow the steps below.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
: If your battery cabinet has a DC switch on the front, the  
positive and negative cables connect to the terminal strip in  
the back of the battery cabinet. First, find the positive (+)  
cable, and strip 0.52 (1.3 cm) of insulation from the end.  
Insert the cable into the positive (+) battery cabinet  
terminal. Next, strip 0.52 (1.3 cm) of insulation from the  
end of the negative () cable, and connect that cable to the  
negative () terminal in the battery cabinet. Tighten both  
terminal connections securely.  
If your battery cabinet does NOT have a DC switch, see your  
battery installation diagram. Connect the positive (+) cable  
to the DC fuse, and connect the negative () battery cable to  
the most negative terminal on your batteries.  
NOTE If you have an external DC disconnect switch, see the instructions that came  
with your disconnect switch.  
: Now, connect the battery cables to the UPS by plugging the  
removable DC connector into the matching connector on the  
back of the UPS.  
: If the battery cabinet has a DC switch, turn the switch to the  
ON position.  
Make sure the UPS DC Switch is in the OFF position; then, find  
the battery cables that you will connect between the UPS and  
the batteries.  
Connect the cables to the UPS first; to do this, strip 0.52  
(1.3 cm) of insulation from the end of the negative (!) and  
positive (+) cables. Next, connect the negative (!) cable to the  
negative (!) terminal on the UPS terminal strip; then, connect  
the positive (+) cable to the positive (+) terminal on the UPS  
terminal strip. Tighten the terminal connections securely.  
Now, go to the batteries. Find the positive (+) and negative ()  
cables that come from the UPS and strip 0.52 (1.3 cm) of  
insulation from the end of each cable. Insert the positive (+)  
cable into the positive (+) terminal at the back of the battery  
cabinet. Next, connect the negative () cable to the negative  
() terminal at the back of the battery cabinet. Tighten the  
terminal connections securely.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
NOTE If you have an external DC disconnect switch, see the instructions that came  
with your disconnect switch.  
Now, turn the DC ON/OFF switch on the battery cabinet(s) to  
the ON position. Leave the UPS DC switch in the OFF position.  
12. Use the meter to check for proper nominal DC voltage at the  
UPS end of the cable. Make sure the polarity agrees with the  
markings on the UPS battery terminals.  
Table 29. Nominal Battery Voltage  
Models  
Nominal Battery  
Voltage  
QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, and 1.4 kVA  
FE 500 VA, 700 VA, and 850 VA  
12 Vdc  
24 Vdc  
48 Vdc  
QFE 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and 7 kVA  
FE 1.15 kVA, 1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA,  
and 7 kVA  
FE and QFE 10 kVA, 12.5 kVA, and 18 kVA  
120 Vdc  
After you have checked the DC voltage, turn the DC switch on  
the battery cabinet(s) to the OFF position.  
13. Complete the phase check beginning on page 8.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
Replacing the Batteries  
CAUTION  
Only qualified service personnel (such as a licensed electrician) should perform the  
battery installation. Risk of electrical shock.  
Consider all warnings, cautions, and notes before replacing batteries.  
WARNING  
: Batteries can present a risk of electrical shock or burn from high short-circuit  
current. The following precautions should be observed: 1) Remove watches, rings,  
or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or  
metal parts on top of batteries.  
: ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or  
connectors. Attempting to alter wiring can cause injury.  
: Replace batteries with the same number and type of batteries as originally  
installed in the UPS.  
To replace the batteries:  
1. Use the same number and type of battery.  
To ensure continued superior performance of your UPS and to  
maintain proper charger operation, you must replace the  
batteries in the UPS or its battery cabinets or racks with the  
same number of batteries. These batteries must be the same  
type as the original batteries: valve-regulated, low-maintenance.  
The replacement batteries should have the same voltage and  
ampere-hour rating as the original batteries.  
2. Remove the ground from the battery terminal.  
If your local or national code requires you to ground either  
battery terminal, remove the connection from the terminal to  
ground (or earth) before you work on the batteries. If any  
battery terminal is inadvertently grounded, remove the source  
of the ground. Contacting any part of a grounded battery can  
cause a risk of electric shock. An electric shock will be less  
likely if you disconnect the grounding connection before you  
work on the batteries.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Cabinet Installation  
3. Handle used batteries with care!  
Assume that old batteries are fully charged. Use the same  
precautions you would use when handling a new battery. Do  
not short battery terminals or the battery string with a cable or  
tool when you disconnect the batteries! See “Recycling the  
Used Battery” on page 64 for proper disposal.  
Recycling the Used Battery  
Contact your local recycling or hazardous waste center for information  
on proper disposal of the used battery.  
WARNING  
: Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper  
disposal of batteries is required. Refer to your local codes for disposal  
requirements.  
: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to  
the skin and eyes. It may be toxic.  
CAUTION  
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,  
lead-acid batteries and must be disposed of properly. For more information, contact  
your local recycling or hazardous waste center.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 8  
PHASE CHECK  
After all hardwired connections are complete (including external battery  
cabinets, if applicable), complete the phase check using the following  
steps. You will need an AC voltmeter for the phase check.  
CAUTION  
Before operating the bypass switch, use the following procedure to check the wiring  
for correct installation. To prevent damage to the load, turn off the main circuit breaker  
in the load service panel or verify that the load cannot receive power from the UPS.  
1. Confirm that an electrician has completed and tested the  
connection to the proper power source.  
2. Verify that the bypass switch is in the OFF position.  
3. At the UPS AC input service panel, turn on the input power to  
the UPS and the bypass switch.  
4. Turn on the AC disconnect switch.  
The AC LINE indicator on the UPS illuminates.  
NOTE The AC LINE indicator does not illuminate for FE models with serial numbers  
25000 and greater until the UPS ON/OFF switch is turned to the ON position.  
5. If your UPS has a DC switch, turn on the switch according to  
the UPS model:  
500 VA–3.1 kVA: Most units do not have a DC switch on the UPS  
or external battery cabinet(s). If the external battery cabinet has  
a DC switch, turn the switch to the ON position.  
4.3–7 kVA: If you have an external battery cabinet(s) with a DC  
switch, turn the switch to the ON position.  
If you do not have an external battery cabinet(s): unlock the  
UPS front cover panel using the FERRUPS key and remove the  
front cover panel. Locate the DC switch behind the UPS front  
cover panel. If there is a precharge button next to the switch,  
press it for a few seconds. Turn the DC switch to the ON  
position and reinstall the UPS front cover panel.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Phase Check  
10–18 kVA: If you have an external battery cabinet(s) with a DC  
switch, turn the switch to the ON position.  
6. Turn the UPS ON/OFF switch to the ON position. The switch  
is located on the back of the 500 VA–3.1 kVA models and on  
the front of the 4.3–18 kVA models. The load should still be  
disconnected at this time.  
After a short startup test, the READY indicator blinks for a few  
seconds and then remains illuminated. The UPS is ready to  
supply output power.  
7. Turn the bypass switch to the UPS position.  
8. Use an AC voltmeter to measure voltages on the terminal strip  
inside the bypass switch cabinet (refer to the label on the back  
of the switch’s lower front cover panel for the terminal  
numbers).  
Record your measurements in the following chart according to  
the type of bypass switch installed. The voltages in the first  
column should be nearly equal to the voltages in the second  
column. If the values differ by more than a few volts, check the  
terminal strip connections and correct any wiring problems.  
CAUTION  
If the AC input voltage is 208V, measure 88 Vac between the AC output terminals:  
: Internal Bypass Switch: 6 and 7 or 6 and 8  
: External Bypass Switch: N and X1 or N and X2  
DO NOT connect any 120V LOAD to the 88V terminals.  
Internal Bypass Switch  
AC to UPS Load Measurement  
AC Line Input  
L1 to L2  
Measurement  
X1 to X2  
N to X1  
N to X2  
Vac  
Vac  
Vac  
Vac  
Vac  
Vac  
N to L1  
N to L1  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Phase Check  
External Bypass Switch  
BPE-01  
AC Line Input  
AC from UPS  
Output  
Measurement  
Measurement  
5 to 6  
Vac  
8 to 9  
Vac  
BPE-02, BPE-04, or BPE-05  
AC from UPS  
Output  
Measurement  
AC Line Input  
Measurement  
7 to 8*  
Vac  
Vac  
Vac  
11 to 12  
10 to 11  
10 to 12  
Vac  
Vac  
Vac  
6 to 7  
6 to 8*  
*60 Hz, 208 or 240V only.  
9. If the bypass switch is a Break-Before-Make type, skip this step  
and proceed to Step 10.  
If the bypass switch is a Make-Before-Break type, verify that the  
AC voltages from the UPS and the AC line input are in phase.  
Measure the voltage between the following points on the  
terminal strip. These measurements must be no more than  
100 Vac; if they are, call your service representative.  
Internal Bypass Switch  
X1 to L1  
Vac  
Vac  
X2 to L2*  
*60 Hz, 208 or 240V only.  
External Bypass Switch (BPE-01)  
6 to 9  
Vac  
External Bypass Switch (BPE-02, BPE-04, or BPE-05)  
7 to 11  
Vac  
Vac  
8 to 12*  
*60 Hz, 208 or 240V only.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Phase Check  
10. Measure the AC voltage between the following points on the  
terminal strip. This reading must be no more than 1 Vac; if it is,  
call your service representative.  
Internal Bypass Switch  
N (AC to UPS Load) to  
N (AC Line Input)  
Vac  
External Bypass Switch (BPE-01)  
5 to 8  
Vac  
External Bypass Switch (BPE-02, BPE-04, or BPE-05)  
6 to 10*  
Vac  
Vac  
8 to 12**  
*60 Hz, 208 or 240V only.  
**60 Hz, 120V or 50 Hz, 220/230/240V.  
11. Turn the bypass switch to the LINE position. Measure the  
voltage to the protected equipment (at the load distribution  
panel or the UPS-protected receptacles for your equipment) and  
verify that it is correct.  
12. Turn the bypass switch to the UPS position and verify the  
voltage to the protected equipment is still correct.  
13. Turn the bypass switch back to the LINE position.  
14. Reinstall the bypass switch and UPS front cover panels.  
15. Turn the UPS ON/OFF switch to the OFF position.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Phase Check  
16. Turn off the DC switch, if applicable, according to your UPS  
model:  
500 VA–3.1 kVA: If you have an external battery cabinet(s) with a  
DC switch, turn the switch to the OFF position.  
4.3–7 kVA: If you have an external battery cabinet(s) with a DC  
switch, turn the switch to the OFF position.  
If you do not have an external battery cabinet(s): unlock the  
UPS front cover panel using the FERRUPS key and remove the  
front cover panel. Locate the DC switch behind the front cover  
panel. Turn the DC switch to the OFF position.  
10–18 kVA: If you have an external battery cabinet(s) with a DC  
switch, turn the switch to the OFF position.  
17. Reinstall the UPS front cover panel.  
18. Turn the AC disconnect switch to the OFF position.  
19. If the UPS will not be operated immediately, leave the bypass  
switch in the LINE position and turn on your protected  
equipment.  
20. The equipment will not be protected by the UPS until you start  
up the UPS and turn the bypass switch to the UPS position.  
Refer to the startup section in the Powerware FERRUPS FE/QFE  
UPS (500 VA–18 kVA) User’s Guide.  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Phase Check  
®
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pelco Automobile Electronics NET5400T User Manual
Philips Electric Toothbrush FlexCare 900 User Manual
Philips Indoor Furnishings PL T57W User Manual
Philips Projection Television 55PP9753 17 User Manual
Philips TV DVD Combo 37MD359B User Manual
Polaroid Portable DVD Player PDM 0084 User Manual
Polycom Network Router DOC2230A User Manual
Precor Treadmill 931 User Manual
Princeton Electronic Keyboard SP 88 User Manual
Proxim Network Router AP 2500 User Manual