PVI Industries Water Heater CSX Single Exchanger User Manual

R
CSX Instantaneous Steam-to-Water Heater  
High-Temperature Blend-down System  
Designed for Buildings with Re-circulating Domestic Water Loops  
High-temperature blend-down is an approach  
to domestic water heating where potable water is  
initially heated by a steam heat exchanger to 220ºF to  
250ºF and then is blended with cold water through a  
mixing valve to achieve the required outlet tempera-  
ture. The approach avoids modulating steam to control  
water temperature and instead relies on the modulation  
of flows of cold and hot water.  
CSX Compared to Competitive Blend-Down  
Water Heaters with Building Re-Circulation  
Greater Temperature Accuracy - dual control valves  
CSX controls the blending of hot and cold water  
through two separate fixed-temperature mixing valves  
downstream of the heat exchanger. With a building  
re-circualtion loop, both valves are always blending.  
Greater Safety - high-limit shutdown system  
CSX is equipped with a high-temperature shutoff  
device on the hot water piping. Thermostats monitor the  
downstream side of both blending valves. A solenoid  
valve shuts off flow from the heat exchanger if water  
temperatures climb above either high-limit threshold.  
True Clean-in-Place Capability  
Unlike competitive designs that require the breaking  
of piping connections or the removal of blending valves  
to access the waterside of the heat exchanger, CSX  
provides two readily accessible CIP threaded fittings.  
All piping remains intack during cleaning.  
CSX single-exchanger models range in  
output from 15 to 75gpm of 140ºF water with  
15 psi steam. Packaged dual-exchanger  
systems are available.  
Variable “Cold” Water Temperature is No Problem  
The dual CSX blending valves respond seamlessly  
to variable temperature and flow at the cold inlet port  
and produce water within 5 degrees of the system’s  
setpoint temperature.  
Competitive designs use a blending valve that  
responds to flow as the only variable input. Using this  
type of valve requires the cold water temperature at  
the valve inlet to remain constant. With a building recir-  
culating loop, water at the valve’s cold inlet can range  
from 40ºF to 110ºF. The valve has no internal means to  
adjust to this variable and can miss the outlet tempera-  
ture target by a wide margin. Without additional down-  
stream blending valves, over- or under-temperature  
water can enter the domestic water system.  
Fixed-temperature valves (tamper-proof) are  
available to provide 120ºF, 140ºF or 160ºF  
outlet water to within  
results in cold water flow.  
5 ºF. Valve failure  
Exchanger is passivated 316L stainless steel  
with corrugated, helical tubing and a counter-  
flow design for low floor space requirements.  
Water is in the shell and steam in the tubes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Music Mixer 701R User Manual
Pelco Security Camera C2433M D User Manual
Pfaff Sewing Machine 350P User Manual
Philips Air Cleaner AC4116 User Manual
Pioneer Car Stereo System DEH 1500RXU EW User Manual
Pioneer Stereo System 920 User Manual
Pioneer Stereo System PD F1039 User Manual
Polycom Computer Hardware 3725 23487 003 A User Manual
Poulan Chainsaw 530163638 User Manual
ProForm Treadmill PFTL71431 User Manual