TABLE OF CONTENTS
Part 1: Introduction............................................................................................2
1.1
1.2
1.3
Description .................................................................................2
Safety Considerations ...............................................................3
Before You Begin .......................................................................4
Part 2: Setup.......................................................................................................5
2.1
2.2
2.3
Mounting.....................................................................................5
Rear Panel Connections............................................................7
Electrical Installation .................................................................8
2.3.1 Power Connections........................................................8
2.3.2 Thermocouple - Input Connection................................9
2.3.3 Two / Three / Four Wire RTD-Hookups.......................10
2.3.4 Process Current - Wiring Hookup...............................11
2.3.5 Process Voltage - Wiring Hookup...............................11
2.3.6 Wiring Outputs - Wiring Hookup.................................12
Part 3: Operation: Configuration Mode .........................................................14
3.1
Introduction ..............................................................................14
Turning your Instrument On for the First Time
Buttons Functions in Configuration Mode
3.2
Menu Configuration ................................................................15
3.2.1 ID Number .....................................................................16
3.2.2 Setpoints.......................................................................17
3.2.3 Configuration Menu ....................................................18
3.2.4 Input Type Menu...........................................................18
Input Type (Thermocouple) ........................................19
Input Type (RTD)...........................................................20
Input Type (Process) ...................................................21
3.2.5 Reading Configuration Menu .....................................21
3.2.6 Alarm 1 Menu ...............................................................25
3.2.7 Analog Output (Retransmission) Menu......................29
3.2.8 Alarm 2 Menu................................................................32
3.2.9 Loop Break Time Menu / Field Calibration.................33
3.2.10 Output 1 Menu ..............................................................36
3.2.11 Output 2 Menu ..............................................................43
3.2.12 Ramp and Soak Menu..................................................46
3.2.13 ID Code Menu ...............................................................48
3.2.14 Communication (Options) Menu.................................50
3.2.15 Display Color Selection Menu.....................................56
Part 4: Specifications ......................................................................................59
Part 5: Factory Preset Values .........................................................................62
CE APPROVAL INFORMATION.......................................................................65
i
Download from Www.Somanuals.com. All Manuals Search And Download.
LIST OF FIGURES:
Figure 2.1
Figure 2.2
Figure 2.3
Figure 2.4
Figure 2.5
Figure 2.6
Figure 2.7
Mounting ...............................................................................................5
Rear Panel Power and Output Connector Labels..............................7
Rear Panel Input Connector Labels....................................................7
Main Power Connections.....................................................................8
Inside Cover Rear View........................................................................8
Thermocouple Wiring Hookup ............................................................9
Two/Three/Four-wire RTD
a) RTD-1000 ohm and 500 ohm Wiring Hookup ............................10
b) RTD-100 ohm Wiring Hookup .....................................................10
Process Current Wiring Hookup
Figure 2.8
Figure 2.9
(Internal and External Excitation)......................................................11
Process Voltage Wiring Hookup
a) Without Sensor Excitation ..........................................................11
b) With Sensor Excitation................................................................11
Output Connections:
a) Mechanical Relay and SSR Outputs – Wiring Hook up............12
b) Pulse and Analog Outputs – Wiring Hook up............................12
Communication Output:
Figure 2.10
Figure 2.11
a) RS-232 Output – Wiring Hook up ...............................................12
b) RS-485 Output – Wiring Hook up ...............................................12
Excitation Output................................................................................13
Snubber Circuits Wiring Hookup......................................................13
Flow Chart for ID and Setpoints........................................................15
Flow Chart for Configuration Menu ..................................................18
Flow Chart for Input Type Menu........................................................18
Flow Chart for Reading Configuration .............................................21
Flow Chart for Alarm 1.......................................................................25
Flow Chart for Analog Output (Retransmission).............................29
Flow Chart for Alarm 2.......................................................................32
Flow Chart for Loop Break Time / Field Calibration........................33
Flow Chart for Output 1 .....................................................................36
Flow Chart for Output 2 .....................................................................43
Flow Chart for Ramp and Soak .........................................................46
Flow Chart for ID Code.......................................................................48
Flow Chart for Communication Option ............................................50
Flow Chart for Display Color Selection............................................56
Figure 2.12
Figure 2.13
Figure 3.1
Figure 3.2
Figure 3.3
Figure 3.4
Figure 3.5
Figure 3.6
Figure 3.7
Figure 3.8
Figure 3.9
Figure 3.10
Figure 3.11
Figure 3.12
Figure 3.13
Figure 3.14
LIST OF TABLES:
Table 2.1
Table 2.2
Table 2.3
Table 3.1
Table 3.2
Table 4.1
Table 5.1
Front Panel Annunciators....................................................................6
Rear Panel Connector..........................................................................7
TC Wire Color Chart .............................................................................9
Button Function in Configuration Mode...........................................14
Conversion Table................................................................................24
Input Properties..................................................................................61
Factory Preset Values ........................................................................62
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or
practices that can effect the instrument’s functionality and must refer
to accompanying documents.
TIP: Provides you helpful hints.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 1
INTRODUCTION
1.1 Description
This device can be purchased as monitor (read process value only) or as
a controller.
•
The iLD Big Display controller offers unparalleled flexibility in process
measurement. Each unit allows the user to select the input type, from
10 thermocouple types (J, K, T, E, R, S, B, C, N and J DIN), Pt RTDs (100,
500 or 1000 Ω, with either 385 or 392 curve), DC voltage, or DC current.
The voltage/current inputs are fully scalable to virtually all engineering units,
with selectable decimal point, perfect for use with pressure, flow or other
process input.
•
•
The temperature control can be achieved by using on/off or PID heat/cool
control strategy. Control can be optimized with an auto tune feature. The
instrument offers a ramp to setpoint with timed soak period before switching
off the output.
The iLD Big Display device features a large, three color programmable
display with capability to change a color every time the Alarm is triggered.
The standard features include dual outputs with relay, SSR, dc pulse, analog
voltage or current. Options include programmable RS-232 or RS-485 serial
communication and excitation. Analog Output is fully scalable and may be
configured as a proportional controller or retransmission to follow your
display. Universal power supply accepts 100 to 240 Vac.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2 Safety Considerations
This device is marked with the international caution symbol. It is important
to read this manual before installing or commissioning this device as it
contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
This instrument is protected in accordance with Class I of EN 61010
(110/240 AC power connections). Installation of this instrument should be
done by qualified personnel. In order to ensure safe operation, the
following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-
breaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch or
circuit-breaker shall meet the relevant requirements of IEC 947–1 and
IEC 947-3 (International Electrotechnical Commission). The switch shall
not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn
from the main supply in case of a fault in the equipment, an overcurrent
protection device shall be installed.
•
•
•
Do not exceed voltage rating on the label located on the top of the
instrument housing.
Always disconnect power before changing signal and power
connections.
Do not use this instrument on a work bench without its case for safety
reasons.
•
•
•
Do not operate this instrument in flammable or explosive atmospheres.
Do not expose this instrument to rain or moisture.
Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
Use electrical wires with adequate size to handle mechanical strain
and power requirements. Install without exposing bare wire outside the
connector to minimize electrical shock hazards.
•
EMC Considerations
•
•
•
•
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
Failure to follow all instructions and warnings may result in injury!
3
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as soon
as you receive the shipment. Note any evidence of rough handling in
transit. Immediately report any damage to the shipping agent. The carrier
will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing
material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free
configuration software and ActiveX controls are available from the
website listed in this manual or on the CD-ROM enclosed with your
shipment.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
To Disable Outputs:
Standby Mode is useful during setup of the instrument or when
maintenance of the system is necessary. When the instrument is in
standby, it remains in the ready condition but all outputs are disabled.
This allows the system to remain powered and ready to go.
When the instrument is in "RUN" Mode, push d twice to disable all
outputs and alarms. It is now in "STANDBY" Mode. Push d once more
to resume "RUN" Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
To Reset the Meter:
When the controller is in the "MENU" Mode, push c once to direct
controller one step backward of the top menu item.
Push c twice to reset controller, prior to resuming "Run" Mode except
after "Alarms", that will go to the "Run" Mode without resetting the
controller.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 2
SETUP
2.1 Mounting
Figure 2.1 Mounting
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting iLD Big Display Through Panel:
1. Using the panel cutout diagram shown in your Quick Start Manual, cut
an opening in the panel.
2. Remove six (or eight) screws at the back of iLD Big Display to remove
back cover.
3. Insert the unit into the opening from the front of the panel so the gasket
seals between the bezel and the front of the panel.
4. Pass all wiring through customer drilled holes in back cover and
connect wiring to terminal blocks.
5. Align back cover to iLD Big Display and reinstall screws.
Mounting iLD Big Display on Bail:
1. Remove six (or eight) screws at the back of iLD Big Display to remove
back cover.
2. Pass all wiring through customer drilled holes in back cover and
connect wiring to terminal blocks.
3. Align back cover to iLD Big Display and reinstall screws.
4. Mark the location of mounting screws on the flat surface.
5. Be sure to leave enough room around the bail to allow for removal and
rotation of the display.
6. The display can be rotated for the best viewing angle.
Table 2.1 Front Panel Annunciators
1
2
Output 1/Setpoint 1/ Alarm 1 indicator
Output 2/Setpoint 2/ Alarm 2 indicator
°C °C unit indicator
°F °F unit indicator
a
Changes display to Configuration Mode
and advances through menu items*
b
Used in Program Mode and Peak Recall*
c
Used in Program Mode and Valley Recall*
d
Accesses submenus in Configuration Mode
and stores selected values*
* See Part 3 Operation: Configuration Mode
6
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2 Rear Panel Connections
The rear panel connections are shown in Figures 2.2 and 2.3.
1
2
3
1
2
3
4
5
6
4
5
6
4
5
6
1
2
3
1
2
3
4
5
6
Figure 2.2 Rear Panel Power and Output Connections
Figure 2.3 Rear Panel Input Connections
Table 2.2 Rear Panel Connector
POWER
AC Power Connector: All models
INPUT
Input Connector: TB7 & TB8 for TC models
TB9 for PR (Process) & RTD models
OUTPUT 1 Based on one of the following models:
Relay SPDT
Solid State Relay
Pulse
Analog Output (Voltage and Current)
OUTPUT 2 Based on one of the following models:
Relay SPDT
Solid State Relay
Pulse
OPTION
Based on one of the following models:
RS-232C or RS-485
7
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3 Electrical Installation
2.3.1 Power Connections
Caution: Do not connect power to your device until you have completed all
input and output connections. Failure to do so may result in injury!
Connect the main power connections as shown in Figure 2.4.
3
2
1
Figure 2.4 Main Power Connections
AC
PWR
DC
REMOTE
COMMUNICATION
OUTPUTS
TB5
T/C INPUT
TB7 TB8
INPUTS
PWR PROGRAMMER
1
3
5
TB1
TB2 TB3
TB4
TB9
2
4
6
PJ3
1 2 3
L N
1 2 1 2 3 4 5
+ -
1 2 3
RTN Rx Tx
1 2 3 4 5 6
OUTPUT2 OUTPUT1
1 2 3 4 5 6 7 8
+ -
1 2 3 4 5 6
TB5A
1 2
TB5B TB5C
3 4 5 6
OUTPUT2
OUTPUT1
iLD24 OUTPUTS
Figure 2.5 Inside Cover Rear View
8
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.2 Thermocouple
The figure below shows the wiring hookup for any thermocouple type. For
example, for Type K hookup, connect the yellow wire to the TB7(+) terminal and
the red wire to the TB8(-) terminal.
When configuring your controller, select Thermocouple and Thermocouple
Type in the Input Type menu (see Part 3).
Figure 2.6 Thermocouple Wiring Hookup
Table 2.3 TC Wire Color Chart
TYPE
Input Connector
Terminal 8 (-) Terminal 7 (+)
Jacket (external insulation)
Extension
dark-Brown
dark-Brown
dark-Brown
dark-Brown
dark-Brown
-
Grade
Black
Yellow
Blue
Purple
Brown
Green
Green
Black
J
K
T
E
N
R
S
B
Red
Red
Red
Red
Red
Red
Red
Red
White
Yellow
Blue
Purple
Orange
Black
Black
Gray
-
-
9
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.3 Two/Three/Four-Wire RTD
The figures below show the input connections and input connector jumpers
(shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD.
Figure 2.7
a) RTD-1000 ohm and 500 ohm
Wiring Hookup
b)RTD-100 ohm Wiring Hookup
The two-wire connection is simplest method, but does not compensate for
lead-wire temperature change and often requires calibration to cancel lead-wire
resistance offset.
The three-wire connection works best with RTD leads closely equal in
resistance. The device measures the RTD, plus upper and lower lead drop
voltage and the subtracts twice the measured drop in the lower supply current
lead producing excellent lead-resistance cancellation for balanced
measurements.
The four-wire RTD hookup is applicable to unbalanced lead resistance and
enables the device to measure and subtract the lead voltage, which produces
the best lead-resistance cancellation.
When configuring your controller, select RTD type and RTD value in the
Input Type menu (see Part 3).
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message except in case of 500/1000 Ω 2-wire
RTD. In this case the display shows -OPN “Input (-) Open” message. For
safety purpose you may want to set up your alarm to be triggered when
input is open. See Alarm 1 & 2 chapters for details.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.4 Process Current
The figure below shows the wiring hookup for Process Current 0 – 20 mA.
Figure 2.8 Process Current Wiring Hookup
(Internal and External Excitation)
When configuring your instrument, select Process Type in the Input Type Menu (see Part 3).
2.3.5 Process Voltage
The figure below shows the wiring hookup for Process Voltage 0 – 100 mV,
0 – 1 V, 0 – 10 V.
Figure 2.9
a) Process Voltage Wiring Hookupb) Process Voltage Wiring Hookup
with Sensor Excitation
without Sensor Excitation
RL - Voltage limiting resistor, which allows conversion of the 24 Vdc internal excitation voltage to
the appropriate process input value. For instance: if the potentiometer value is equal to 10 kΩ, the
minimum RL is 14 kΩ for 10 V process input.
When configuring your instrument, select Process Type in the Input Type Menu (see Part 3).
11
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.6 Wiring Outputs
This meter has two, factory installed, outputs. The SPDT Mechanical Relay, SPST
Solid State Relay, Pulse and Analog Output Connection are shown below.
1
2
3
4
5
6
1
2
3
4
5
6
Figure 2.10
a) Mechanical Relay and SSR
Outputs Wiring Hookup
b) Pulse and Analog
Outputs Wiring Hookup
This device may have a programmable communication output. The RS-232 and
RS-485 Output Connection are shown below.
1
1
Figure 2.11
a) RS-232 Output Wiring Hookup b) RS-485 Output Wiring Hookup
12
Download from Www.Somanuals.com. All Manuals Search And Download.
This device may also have an excitation output.
Figure 2.12 Excitation Output
Excitation is not available if communication option is installed.
This device has snubber circuits designed to protect the contacts of the
mechanical relays when it switches to inductive loads (i.e. solenoids,
relays). These snubbers are internally connected between the Common
(C) and Normally Open (NO) relay contacts of Output 1 and Output 2.
If you have an inductive load connected between Common (C) and
Normally Closed (NC) contacts of the mechanical relays and you want to
protect them from the rush current during the switching period, you have
to connect an external snubber circuit between Common (C) and
Normally Closed (NC) contacts as indicated in the figure below.
1
2
3
4
5
6
Figure 2.13 Snubber Circuits Wiring Hookup
13
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 3
OPERATION: Configuration Mode
3.1 Introduction
The instrument has two different modes of operation. The first, Run Mode, is
used to display values for the Process Variable, and to display or clear Peak
and Valley values. The other mode, Menu Configuration Mode, is used to
navigate through the menu options and configure the controller. Part 3 of this
manual will explain the Menu Configuration Mode. For your instrument to
operate properly, the user must first "program" or configure the menu options.
Turning your Controller On for the First Time
The device becomes active as soon as it is connected to a power source. It
has no On or Off switch. The device at first momentarily shows the software
version number, followed by reset
, and then proceeds to the Run Mode.
RST
Table 3.1 Button Function in Configuration Mode
• To enter the Menu, the user must first press button.
a
• Use this button to advance/navigate to the next menu item. The user can
a
MENU
navigate through all the top level menus by pressing .
a
• While a parameter is being modified, press to escape without saving
a
the parameter.
• Press the up button to scroll through “flashing” selections. When a
b
numerical value is displayed press this key to increase value of a
parameter that is currently being modified.
b
(UP)
• Holding the button down for approximately 3 seconds will speed up the
b
rate at which the set point value increments.
• In the Run Mode press causes the display to flash the PEAK value –
b
press again to return to the Run Mode.
• Press the down button to go back to a previous Top Level Menu item.
c
• Press this button twice to reset the controller to the Run Mode.
• When a numerical value is flashing (except set point value) press to
c
scroll digits from left to right allowing the user to select the desired digit to
modify.
c
(DOWN)
• When a setpoint value is displayed press to decrease value of a
c
setpoint that is currently being modified. Holding the button down for
c
approximately 3 seconds will speed up the rate at which the setpoint
value is decremented.
• In the Run Mode press c causes the display to flash the VALLEY value –
press again to return to the Run Mode.
• Press the enter d button to access the submenus from a Top Level
Menu item.
• Press d to store a submenu selection or after entering a value — the
d
ENTER
display will flash a
message to confirm your selection.
STRD
• To reset flashing Peak or Valley press d.
• In the Run Mode, press d twice to enable Standby Mode with
flashing
.
STBY
Reset: Except for Alarms, modifying any settings of the menu configuration
will reset the instrument prior to resuming Run Mode.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2 Menu Configuration
It is recommended that you put the controller in the Standby Mode for
any configuration change other than Setpoints & Alarms.
Figure 3.1 Flow Chart for ID and Setpoints
15
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.1 ID Number
SEE ID MENU SELECTION IN CONFIGURATION SECTION FOR
ENABLE/DISABLE OR CHANGE ID CODE.
If ID Code is Disabled or set as Default (0000) the menu will skip ID step
to Setpoint Menu.
If ID Code is set to Full Security Level and user attempts to enter the
Main Menu, they will be prompted for an ID Code.
If ID Code is set to Setpoint/ID Security Level and user attempts to enter
the Configuration Menu, they will be prompted for an ID Code.
ENTERING YOUR NON-DEFAULT FULL SECURITY ID NUMBER.
Press a
1) Display shows
.
ID
2) Display advances to
Press d
.
____
Press b & c 3) Press to increase digit 0-9. Press to activate next digit
b
c
(flashing). Continue to use and c to enter your 4-digit ID
b
code.
Press d
4) If the correct ID code is entered, the menu will advance to the
Setpoint 1 Menu, otherwise an error message
will be
ERRo
displayed and the instrument will return to the Run Mode.
To change ID Code, see ID Menu in the Configuration section.
ENTERING YOUR NON-DEFAULT SETPOINT/ID SECURITY ID NUMBER.
Press a
Press a
Press a
Press d
5) Display shows
6) Display shows
7) Display shows
Setpoint 1 Menu.
Setpoint 2 Menu.
SP1
SP2
ID Code Menu.
ID
8) Display advances to
.
____
Press b & c 9) Use b and c to change your ID Code.
Press d 10) If correct ID Code is entered, the display will advance to the
Input Menu, otherwise the error message will be
INPT
ERRo
displayed and the controller will return to the Run Mode.
To prevent unauthorized tampering with the setup parameters, the
instrument provides protection by requiring the user to enter the ID Code
before allowing access to subsequent menus. If the ID Code entered
does not match the ID Code stored, the controller responds with an error
message and access to subsequent menus will be denied.
Use numbers that are easy for you to remember. If the ID Code is
forgotten or lost, call customer service with your serial number to access
and reset the default to
.
0000
16
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.2 Set Points
SETPOINT 1:
Press a
1) Press a, if necessary until
prompt appears.
SP1
Press d
2) Display shows previous value of “Setpoint 1”.
Press b & c 3) Press b and c to increase or decrease Setpoint 1
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up the
rate at which the Setpoint value increments or decrements.
Press b & c 4) Continue to use b and c to enter your 4-digit Setpoint 1 value.
Press d
5) Display shows
stored message momentarily and then
STRD
only, if a change was made, otherwise press
advances to
SP2
a to advance to
Setpoint 2 Menu.
SP2
SETPOINT 2:
Press d
6) Display shows previous value of “Setpoint 2”.
Press b & c 7) Press b and c to increase or decrease Setpoint 2
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up
the rate at which the setpoint value increments or decrements.
Press d
8) Display shows
stored message momentarily and then
STRD
only, if a change was made, otherwise press
advances to
CNFG
a to advance to
Configuration Menu.
CNFG
17
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.3 Configuration Menu
Figure 3.2 Flow Chart for Configuration Menu
Enter Configuration Menu:
Press a
Press d
Press a
1) Press a, if necessary, until
prompt appear.
CNFG
Input Menu.
2) Display advances to
INPT
3) Pressing and releasing a to scroll through all available
menus of Configuration section.
3.2.4 Input Type Menu
Figure 3.3 Flow Chart for Input Type Menu
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Input Type (Thermocouple)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until
prompt appears.
CNFG
Input Menu.
2) Display advances to
INPT
3) Display flashes
,
or
(Thermocouple, RTD or
, press a to skip to
T.ç RTD PROC
Process). If the displayed input type is
T.ç
step 6 ( stops flashing).
T.ç
THERMOCOUPLE SUBMENU:
Press b
4) Scroll through the available selection to
(flashing).
T.ç
stored message momentarily and then
Press d
5) Display shows
STRD
(not flashing).
T.ç
Press d
Press b
Press d
6) Display flashes previous thermocouple type selection. i.e.
J
(see below for types).
7) Scroll through the available thermocouple types to the
selection of your choice.
8) Display shows
stored message momentarily and then
STRD
Reading Configuration Menu.
advances to the
RDG
Use the Input Type (Thermocouple) (RTD) or (Process) and verify your
Electrical Installation (see Section 2.3).
Thermocouple Types: J, K, T, E, N, DIN J, R, S, B, C
Display:
J K T E N DNJ R S B C
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Input Type (RTD)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until
prompt appears.
CNFG
Input Menu.
2) Display advances to
INPT
3) Display flashes
,
or
(Thermocouple, RTD or
, press a to skip to
T.ç RTD PROC
Process). If the displayed input type is
RTD
step 6 ( stops flashing).
RTD
RTD SUBMENU:
Press b
4) Scroll through the available selection to
(flashing).
RTD
stored message momentarily and then
Press d
5) Display shows
STRD
(not flashing).
RTD
Press d
Press b
Press d
6) Display flashes previous RTD type selection i.e.
392.2
(see below for RTD types selection).
7) Scroll through the available RTD types to the selection of
your choice.
8) Display shows
stored message momentarily and then
STRD
advances to
RTD value.
RTD
RTD Types: 392
Display:
385
Two, Three or Four-wire
,
,
,
,
,
392.2 392.3 392.4 385.2 385.3 385.4
Last digit indicates: 2-, 3- or 4-wire input.
RTD VALUE SUBMENU:
Press d
Press b
Press d
9) Display flashes previous RTD value selection i.e.
100_
(see below for RTD value selection).
10) Scroll through the available RTD values to the selection of
your choice.
11) Display shows
stored message momentarily and then
STRD
Reading Configuration Menu.
advances to
RDG
RTD Values: 100 ohm
Display:
500 ohm
500_
1000 ohm
1000
100_
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Input Type (Process)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until
prompt appears.
CNFG
Input Menu.
2) Display advances to
T.ç RTD PROC
Process). If the displayed input type is
INPT
3) Display flashes
,
or
(Thermocouple, RTD or
, press a to skip to
PROC
step 6 ( stops flashing).
PROC
PROCESS SUBMENU:
Press b
4) Scroll through the available selection to
(flashing).
PROC
stored message momentarily and then
Press d
5) Display shows
STRD
(not flashing).
PROC
Press d
Press b
Press d
6) Display flashes previous Process type selection. i.e.
0-10
(see below for Process types selection).
7) Scroll through the available Process types to the selection of
your choice.
8) Display shows
stored message and then advances to
STRD
Reading Configuration Menu.
RDG
Process Types: 100 mV 1 V
10 V
0-0.1 0-1.0 0-10
0 – 20 mA
0-20
Display:
For 4-20 mA Input select 0-20 mA then adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under INPUT/READING submenu. The
factory preset value is 4-20 mA.
It is recommended that you put the
controller in the Standby Mode for any
configuration change other than Setpoints &
Alarms.
3.2.5 Reading Configuration
Figure 3.4 Flow Chart for Reading Configuration Menu
21
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER READING CONFIGURATION MENU:
Press
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
d
a
CNFG
Input Menu.
2) Display advances to
3) Display advances to
4) Display advances to
INPT
RDG
DEC
Reading Configuration Menu.
Decimal Point.
DECIMAL POINT SUBMENU:
Press
Press
5) Display flashes previous selection for Decimal location.
d
b
6) Scroll though the available selections and choose Decimal
location:
or
FFFF FFF.F
(also
and
— if
F.FFF PROC
FF.FF
Process type was selected in the Input Type Menu).
Press
7) Display shows stored message momentarily and then
d
STRD
Temperature Unit.
advances to
TEMP
Decimal Point for Process Input Type is passive.
TEMPERATURE UNIT SUBMENU:
Press
Press
8) Display flashes previous Temperature Unit selection.
9) Scroll though the available selections to the Temperature Unit
of your choice: or
d
b
.
°F °C
10) Display shows
Press
stored message momentarily and then
d
STRD
Filter Constant.
advances to
FLTR
FILTER CONSTANT SUBMENU:
Press
Press
11) Display flashes previous selection for Filter Constant.
d
b
12) Scroll though the available selections:
,
,
,
,
,
,
,
0001 0002 0004 0008 0016 0032 0064 0128
Press
13) Display shows
stored message momentarily only, if
STRD
d
change was made, otherwise press to advance to the next
a
menu.
If Process was selected in the Input Type Menu the display will
advance to
Input/Reading Submenu, otherwise the
IN.RD
display advances to the
Alarm 1 Menu.
ALR1
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Reading Configuration (If Process was selected)
INPUT/READING (SCALE AND OFFSET) SUBMENU:
Input Voltage or Current can be converted or scaled into values appropriate for
the process or signal being measured. So, a reading may be displayed, for
example, in units of weight or velocity instead of in amperes or volts.
The instrument determines Scale and Offset values based on two user-provided
input values entered with the corresponding readings. Note that “In1” Input 1 and
“In2” Input 2 are represented and entered as a product of the input
voltage/current and the conversion number from the Table 3.1.
The following instructions include details for a specific scenario in which a
4-20 mA input (in the 20 mA Process Mode) is to be represented as a
measurement of 0-100 percent.
Press
14) Press at the
prompt. Display shows
Input 1
IN1
d
d
IN.RD
submenu.
st
Press
Press
15) Display shows Input 1 value with 1 digit flashing.
d
b
&
&
16) Use and buttons to enter
value.
c
b
c
IN1
The
value = min. input value * conversion number.
IN1
Disregard the position of the decimal point, such that 2000
counts may actually appear as “200.0”, “20.00”, or “2.000”.
Example: 4 mA as 4(mA) x 500 = 2000.
Press
Press
17) Display advances to
Reading 1 Submenu.
RD1
d
b
18) Use and buttons to enter
value.
c
b
c
RD1
in terms of some meaningful
This value represents
IN1
engineering units. To show the 4 mA as zero percent enter
RD1
value = 0000.
RD1
19) Display IN!2 Input 2 Submenu.
Example:
value = 0000.
Press
Press
d
d
st
20) Display shows Input 2 value with 1 digit flashing.
The IN!2 value = max. input value * conversion number.
Example: 20(mA) x 500 = 10000 (9999).
Press
Press
Press
&
&
21) Use and c buttons to enter IN!2 value.
b
d
b
c
c
b
22) Display advances to RD!2 Reading 2 Submenu.
23) Use b and c buttons to enter RD!2 value.
Example: RD!2 value = 0100.
Press
24) Display flashes
stored message momentarily and
d
STRD
only, if change was made, otherwise
then advances to
ALR1
to advance to
press
Alarm 1 Menu.
ALR1
d
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Conversion number is a coefficient of conversion between input values
and real full display range (10000 counts, shown as 9999). See Table 3.2
below for proper conversion number.
Table 3.2 Conversion Table
RANGE
100 mV
1 V
10 V
0 -20 mA
CONVERSION NUMBER
10000 / (100 x 1) = 100
10000 / (1000 x 1) = 10
10000 / (1000 x 10) = 1
10000 / (20 x 1) = 500
Example =
0 - 1 V = 0 - 100.0
In 1 = 0
Rd 1 = 0
Inp 2 = 9999
Rd 2 = 100.0
24
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.6 Alarm 1
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed.
If Analog Output Option is installed, the controller will skip Alarm 1 Menu
item to Analog Output.
Alarm must be DISABLED
if Ramp is ENABLED.
Figure 3.5 Flow Chart for Alarm 1
ENTER ALARM 1 MENU:
Press a
Press d
Press a
1) Press a, if necessary, until
prompt appears.
CNFG
Input Menu.
2) Display advances to
INPT
3) Press a, if necessary, until Display advances to
Alarm 1
ALR1
Enable or Disable
ENBL DSBL
Menu.
Press d
4) Display advances to Alarm 1
Submenu and flashes the previous selection.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM 1 ENABLE/DISABLE SUBMENU:
Press b
5) Scroll though the available selection until
displays to
ENBL
use Alarm 1.
Press d
6) Display shows
stored message momentarily and then
STRD
advances to
only if it was changed, otherwise press a to
ABSo
advance to
Alarm 1 Absolute/Deviation Submenu.
ABSo
If
Alarm 1 Disabled was selected, all submenus of Alarm
DSBL
1 Menu will be skipped and meter advances to
Alarm 2
ALR2
Alarm 1 Enabled was selected, Output 1 would
Menu. If
ENBL
be automatically Disabled, and reassigned as Alarm 1.
ALARM 1 ABSOLUTE/DEVIATION SUBMENU:
Press
Press
7) Display flashes previous selection. Press to
ABSo
d
d
b
Absolute or
Deviation.
_DEV
8) Display shows
stored message momentarily and then
STRD
advances to
only if it was changed, otherwise press a to
LTçH
advance to
Alarm 1 Latch/Unlatch Submenu.
LTçH
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the
process being monitored does not change often, then "Absolute" Mode is
recommended.
Deviation Mode allows changes to Setpoint 1 to be made automatically to
Alarm 1. Deviation mode is typically the ideal mode if the process temperature
changes often. In Deviation Mode, set Alarm 1 a certain number of degrees or
counts away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is
changed.
ALARM 1 LATCH/UNLATCH SUBMENU:
Press
Press
9) Display flashes previous selection. Press to
LTçH
d
d
b
Latched or
Unlatched.
UNLT
10) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press a to
advances to
CT.CL
Contact Closure Submenu.
advance to
CT.CL
Latched Mode: Relay remains "latched" until reset. To reset already latched
alarm, select Alarm Latch and press Max twice (i.e. Unlatch and then back to
Latch) or from a Run Mode, push twice to put the controller in Standby Mode
d
and then push one more time to return to the Run Mode.
d
Unlatched Mode: Relay remains latched only as long as the alarm condition is
true.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTACT CLOSURE SUBMENU:
Press
Press
11) Display flashes previous selection. Press b to
Normally
N.ç.
d
d
Closed or
Normally Open.
N.o.
12) Display shows
stored message momentarily and then
STRD
advances to
only if it was changed, otherwise press to
AçTV
a
advance to
Active Submenu.
AçTV
Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.
Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"
conditions and becomes de-energized during alarm or power failure.
ACTIVE SUBMENU:
Press
13) Display flashes previous selection. Press to scroll through
d
d
b
Below,
the available selections:
Above,
ABoV
BELo
_DEV
HI.Lo
Deviation was
HI/Low and
selected).
Band. (Band is active if
BAND
Press
14) Display shows
stored message momentarily and then
only if it was changed, otherwise press a to
STRD
A.P.oN
advances to
advance to
Alarm Enable/Disable at Power On Submenu.
A.P.oN
Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM ENABLE/DISABLE AT POWER ON:
Press 15) Display flashes previous selection. Press to enable
ENBL
d
b
or
disable.
DSBL
16) Display shows
Press d
stored message. momentarily and then
STRD
only if it was changed, otherwise press to
advances to
ALR.L
advance to the
a
Alarm 1 Low Value Submenu.
ALR.L
If the alarm is enabled at Power On, the alarm will be active right after
reset. If the alarm is disabled at Power On, the alarm will become
enabled when the process value enters the non alarm area. The alarm is
not active while the process value is approaching Setpoint 1.
ALARM 1 LOW VALUE SUBMENU:
st
Press
17) Display flashes 1 digit of previous value. Use and to
d
b
c
enter new value.
Press
Press
&
18) Use and to enter Alarm 1 Low Value.
b
d
c
b
c
19) Display shows
storage message momentarily and
STRD
ALR.H
ALR.H
then advances to
only, if it was changed, otherwise press
a to advance to
Alarm 1 Hi Value Submenu.
ALARM 1 HI VALUE SUBMENU:
st
Press
20) Display flashes 1 digit of previous value. Use and to
d
b
c
enter new value.
Press
Press
&
21) Use and to enter Alarm1 Hi Value.
b
d
c
b
c
22) Display shows
stored message momentarily and then
STRD
advances to the next menu only, if it was changed, otherwise
press to advance to the next menu.
a
28
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.7 Analog Output (Retransmission)
Analog Output can be configured as Retransmission or Control outputs.
In this section we will discuss Retransmission Output.
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output
1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog
Output is available only, if Analog Output Option board is factory installed.
If Analog Output Option is not installed, the instrument will skip to Alarm 2 Menu.
Figure 3.6 Flow Chart for Analog Output (Retransmission)
ENTER ANALOG OUTPUT MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
a
ANLG
Analog Output Menu.
Press
4) Display advances to Analog Output
Enable or
ENBL DSBL
d
Disable Submenu and flashes the previous selection.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
ANALOG OUTPUT ENABLE/DISABLE SUBMENU:
Press
5) Scroll though the available selection until
displays to
ENBL
b
use Analog Output Retransmission (output proportional to the
input signal).
Press
6) Display shows
stored message momentarily and then
d
STRD
or
advances to
Submenu only if it was changed,
CURR VoLT
otherwise press a to advance to
or
CURR VoLT
Current/Voltage Submenu.
If
Analog Output Disabled was selected, all submenus of Analog
DSBL
Output Menu will be skipped and the meter will advance to
Alarm 2
ALR2
Analog Output Enabled was selected, Output 1 would be
Menu. If
ENBL
automatically Disabled, and reassigned as Analog Output.
CURRENT/VOLTAGE SUBMENU:
Press
Press
7) Display flashes
Current or Voltage.
VoLT
d
b
CURR
8) Scroll through the available selection: Current or Voltage
(Example ).
VoLT
9) Display shows
Press
stored message momentarily and then
d
STRD
Submenu only if it was changed, otherwise
advances to
RD1
press to advance to
a
Reading 1 Submenu.
RD1
READING 1:
st
Press
Press
Press
10) Display flashes 1 digit of previous “Reading 1” value.
d
b
d
&
11) Enter “Reading 1” value. (Example 0000)
12) Display advances to
c
Out 1 Submenu.
OUT.1
OUT 1:
st
Press d
13) Display flashes 1 digit of previous “Out 1” value.
Press b & c 14) Enter “Out 1” value. (Example 00.00)
Press d
15) Display advances to RD!2 Reading 2 Submenu.
READING 2:
st
Press
16) Display flashes 1 digit of previous “Reading 2” value.
d
b
d
Press
Press
&
17) Enter “Reading 2” value. (Example 9999)
18) Display advances to
c
c
Out 2 Submenu.
OUT.2
OUT 2:
t
st
Press
Press
Press
19) Display flashes 1 digit of previous “Out 2” value.
d
b
d
&
20) Enter “Out 2” value. (Example 10.00)
21) Display advances to the
Alarm 2 Menu.
ALR2
The above example is for 0-10 V of the entire range of the Process Input
and Analog Output. For 0-20 mA output you need to set “Analog Type” to
Current and OUT 2 to 20.00.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Accuracy of Analog Output board is +/-1% of FS (Full Scale) when following
conditions are satisfied:
1. The input is not scaled below 1% of Input FS (10 mV @ 1 V or 0.2 mA @
20 mA input ranges).
2. Analog Output is not scaled below 3% of Output FS (300 mV @ 10 V or
0.6 mA @ 20 mA output ranges).
Otherwise certain corrections need to be applied.
For example:
For entire range of process input, the Analog Output on 10 V FS scaled for
300 mV output range:
Rd1 = 0000, Out1 = 00.00
RD2 = 9999, Out2 = 00.30
The measured output will be as follows:
Rd1 = 0000, Out1 = -0.07 V
Rd2 = 9999, Out2 = 0.23 V
This means that for 300 mV output range we have -70 mV offset at zero and at
full scale. In order to compensate this 70 mV offset the correct scaling will be
as follows:
Rd1 = 0000, Out1 = 00.07
Rd2 = 9999, Out2 = 00.37
The above corrections need to be applied only for Input scaled below 1% of FS
and Output scaled below 3% of FS or if you need the Analog Output
accuracy to be better than 1% of FS.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.8 Alarm 2
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed.
Alarm must be DISABLED
if Ramp is ENABLED.
Figure 3.7 Flow Chart for Alarm 2
ENTER ALARM 2 MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
Alarm 2
a
ALR2
Menu.
Press
4) Display advances to Alarm 2
Enable or
ENBL DSBL
Disable
d
Submenu.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM 2 ENABLE/DISABLE SUBMENU:
Press
Press
5) Display flashes previous selection. Press until
ENBL
d
d
b
displays to use Alarm 2.
6) Display shows
stored message momentarily and then
STRD
advances to
only if it was changed, otherwise press to
ABSo
a
advance to
Absolute/Deviation Submenu.
ABSo
If
Alarm 2 Disabled was selected, all submenus of Alarm
DSBL
2 will be skipped and meter advances to
Loop Break
LOOP
Alarm 2 Enabled was selected, Output 2
Time Menu. If
ENBL
will automatically Disabled, and reassigned as Alarm 2.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu.
Modifying Alarm Settings will not reset the instrument.
3.2.9 Loop Break Time
Figure 3.8 Flow Chart for Loop Break Time
ENTER LOOP BREAK TIME MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
Loop
a
LOOP
Break Time Menu.
Press
4) Display advances to Loop Break Time
ENBL
Enable or
d
DSBL
Disable Submenu and flashes the previous selection.
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press b 5) Scroll through the available selections:
or
.
ENBL DSBL
stored message momentarily and then
Press
6) Display shows
d
STRD
Loop Break Time Value Submenu.
advances to
B.TIM
Loop Break is an additional safety feature intended to monitor the rate of change
of the process value, while approaching the SP1. It is strictly intended as an
additional warning system, therefore its use is entirely optional. An active Loop
Break will cause the Process Value digits to blink in a rotating pattern. If the
process value reaches the set point the blinking will stop and
is completed
B.TIM
successfully, otherwise
be turned off.
Break Alarm warning will flash, and Output 1 will
BR.AL
33
Download from Www.Somanuals.com. All Manuals Search And Download.
LOOP BREAK TIME VALUE SUBMENU:
st
Press
Press
7) Display flashes 1 digit of previous Loop Value.
d
b
&
8) Press and buttons to enter a new Loop Value
b
c
c
(0 to 99.59).
Press
9) Display shows
stored message momentarily and then
d
STRD
Reading Adjust Submenu.
advances to
R.ADJ
Loop Break Time Value allows the user to determine the time interval in MM:SS
(from zero to 99 minutes and 59 seconds) that the Process Value changes at
least 10 counts or if the Input Type is either RTD or Thermocouple, the value
changes 4° Fahrenheit or 2° Celsius. At the specified time interval, if the process
value change is less than the stated rate, flashing
will be displayed, the
B.TIM
output 1 will be de-energized, and Alarm 1 energized. Loop break time will be
disabled when the Process Value (PV) enters the control band.
C.J. READING ADJUST SUBMENU:
st
Press
Press
10) Display flashes 1 digit of previous reading adjust value.
d
b
&
11) Press and buttons to enter a new Reading Adjust value
c
b
c
(-1999 to 9999).
Press
12) Display shows
stored message momentarily and then
d
STRD
Setpoint Deviation Menu.
advances to
SP.DV
Reading Offset Adjust (C.J.) allow the user to fine tune a minor error of the
transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value R.ADJ). R.ADJ is
adjustable between -1999 to 9999.
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:
Press
13) Display advances to Setpoint Deviation
Enable or
DSBL
d
ENBL
Disable Submenu and flashes the previous selection.
14) Scroll through the available selections: or .
DSBL
Press
Press
b
d
ENBL
stored message momentarily and then
15) Display shows
STRD
°
CAL.
advances to
Menu.
Setpoint Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be
made automatically to Setpoint 2. This mode is very helpful if the Process Value
changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees
or counts away from SP1 - this relation remains fixed when SP1 is changed. For
instance: Setting SP1=200 and SP2=20 and enabling
means that the
SP.DV
absolute value of SP2=220. Moving SP1 to 300, the absolute value of SP2
becomes 320.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
THERMOCOUPLE FIELD CALIBRATION SUBMENU:
CAUTION: Do not perform the following steps until you fully
understand this entire section.
RTD and Process are perfectly calibrated. This section is applicable to
Thermocouple (TC) calibration only.
Be sure that the TC being used to calibrate the meter is of the type
selected in the TC submenu. Place the TC in an ice-bath (or other
0°C / 32°F environment). In ambient temperature conditions: connect the
TC to the meter, apply power to the meter.
CAUTION: Do not proceed with TC calibration unless the above conditions
have been in effect for at least one hour.
°
Press
Press
Press
Press
7) Display shows
.
a
d
a
d
CAL1
8) Display shows flashing
.
0000
9) Display will still show flashing
*
*
.
0000
(meaning Calibration is complete)
10) Display shows
OUT1
*
If you accidently engage the flashing
(CAL° alert) simply re-press
0000
the last button you pressed, to avoid unintentionally mis-calibrating your
meter.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.10 Output 1
Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contacts
on the rear panel connector. If Alarm 1 or Analog Output (Retransmission) is
Enabled, Output 1 is automatically Disabled.
It is recommended that you put the
controller in the Standby Mode for any
configuration change other than
Setpoints & Alarms.
Figure 3.9 Flow Chart for Output 1
36
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER OUTPUT 1 MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
Output
OUT1
a
1 Menu.
4) Display advances to
Press
Self Submenu.
SELF
d
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
Press
5) Display flashes the current setting of Self,
Enabled or
ENBL
d
Disabled.
DSBL
6) Press the button to select between Enable and Disable.
Press
Press
b
d
b
ENBL
7) If Self
Enabled was selected, display shows
STRD
stored message momentarily and then advances to the next
menu (Output 1 setting is completed).
The output is now under the direct control of the operator and
can be adjusted in the Run Mode (
to ), by pressing
M00.0 M99.9
the and buttons, where M calls for the Manual (Self)
b
c
Control. For example, setting of
M50.0
to 10 Vdc would produce roughly 5 Vdc at the output.
of an Analog Output of 0
8) If Self
Disabled was selected, display shows
DSBL
STRD
oPLO
stored message momentarily and then advances to
Minimum/Percent Low Submenu of Output 1 Menu.
There is a shorter way to Enable or Disable Self Mode. From a Run
Mode, press and then press . Self Mode is Enabled now. Press or
d
a
b
to display MXX.X. To disable Self, press and then press . Display
c
d
a
goes to the Run Mode. Self Mode is Disabled now.
MINIMUM/PERCENT LOW SUBMENU:
Specify in percent, the minimum value (0000) for control output. If the output is
analog proportional (Current or Voltage), then the minimum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),
then the minimum duty-cycle, in percent, is specified.
Press
Press
Press
9) Display flashes 1st digit of previous “Percent Low” setting.
d
b
d
&
10) Use and buttons to enter a new value for “Percent Low”.
c
b
c
11) Display shows
stored message momentarily and then
STRD
advances to
Maximum/Percent High Submenu.
oPHI
37
Download from Www.Somanuals.com. All Manuals Search And Download.
MAXIMUM/PERCENT HIGH SUBMENU:
Specify in percent, the maximum value (99) for control output. If the output is
analog proportional (Current or Voltage), then the maximum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR, or Pulse),
then the maximum duty-cycle, in percent, is specified.
st
Press
Press
Press
12) Display flashes 1 digit of previous “Percent High” setting.
d
b
d
&
13) Use and buttons to enter a new value for “Percent High”.
c
b
c
14) Display shows
stored message momentarily and then
STRD
Control Type Submenu.
advances to
CTRL
Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90,
cause the minimum on the control output to be 1 V and the maximum on the
control output to be 9 V. The same setting on a time proportional output, will
cause 10% duty cycle for the minimum control output and 90% duty cycle for
maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI
is at other values than the default (%LO = 00, %HI =99),
is disabled.
SOAK
*CONTROL TYPE OUTPUT:
(Relay, SSR, Pulse or Analog)
Press
15) Display flashes
On/Off or
Proportional, Integral,
PID
d
ON.OF
Derivative.
Press
Press
16) Scroll through the available selections: “ON/OFF” or “PID”.
b
d
17) Display flashes
then advances to
stored message momentarily and
STRD
only, if it was changed, otherwise press
AçTN
AçTN
a to advance to
Action Type Submenu.
The ON/OFF control is a coarse way of controlling the process. The “Dead
Band” improves the cycling associated with the On/Off control. The PID control is
best for processes where the Setpoint is continuously changing and/or a tight
control of the process variable is required. PID control requires tuning and
adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate"
terms by a trial-and-error method. The instrument provides an "Auto Tuning"
feature making the tuning process automatic, possibly optimum.
* If Analog Output (Current/Voltage) is your control Output 1, this menu i.e.
CTRL
for a
type will not appear, instead
Current will be displayed. Select
4-20
4-20 mA current (2-10 V Voltage) outputs or
ENBL
for a 0-20 mA current (0-10 V
DSBL
Voltage) outputs. If 4-20 mA is enabled, %HI/LO setting will have no effect.
Both Current and Voltage control outputs are active simultaneously.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it would
be called Direct Acting. If a negative error should cause the output to increase
(i.e. heating), it would be called Reverse Acting.
Press
Press
Press
18) Display flashes
Direct or Reverse.
RVRS
d
b
d
DRçT
19) Scroll through the available selections: “Direct” or “Reverse”.
20) Display shows
stored message momentarily and then
only, if it was changed, otherwise press to
STRD
advances to
AUTo
a
advance to
selected).
Auto PID Submenu (if PID Control Type was
AUTo
If “ON/OFF” was selected in the Control Type, the display skips
to the Dead Band Submenu.
AUTO PID SUBMENU:
Press
Press
21) Display flashes
or .
ENBL DSBL
d
b
22) Scroll through the available selections: “Enable” or
“Disable”.
Press
23) Display shows
stored message momentarily and then
d
STRD
only, if it was changed, otherwise press to
advances to
ANTL
Anti Integral Submenu.
a
advance to
ANTL
If “Enabled”, the controller can determine, by enabling Start PID, the
optimum values for the three adjustments — Proportional, Reset and
Rate corresponding to P, I, and D. These values may be changed once
the auto tuning is complete.
If “Disabled” is selected, the user will manually enter these three
adjustment values. If you want the instrument to do the auto PID and the
P , PI or PID, first select auto disable and enter 0000 for unwanted
parameter. i.e. for PI enter 0000 for the rate.
ANTI INTEGRAL SUBMENU:
Press
Press
Press
24) Display flashes
or .
ENBL DSBL
d
b
d
25) Scroll through the available selections: “Enable” or “Disable”.
26) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
STRT
was Enabled).
STRT
a
advance to
to Start Auto Tune PID Submenu (If auto PID
If Auto PID was disabled display advances to
Proportional Band Submenu.
PRoP
39
Download from Www.Somanuals.com. All Manuals Search And Download.
If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows
the error term outside the proportional band to be calculated and
accumulated for integration. This may be an important feature in
applications where fast response time is desirable.
START AUTO TUNE PID:
Press
Press
Press
27) Display flashes
or .
ENBL DSBL
d
b
d
28) Scroll through the available selections: “Enable” or “Disable”.
29) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
CYCL
Cycle Time Submenu.
a
advance to
CYCL
If “Enabled”, the controller is ready to calculate P, PI or PID parameters.
The instrument performs this by activating the output and observing the
delay and rate at which the Process Value changes. The setpoints must
be at least 18°F or 10°C above the (PV) Process Value in order to
perform Auto Tune, otherwise an error message will be displayed.
To start Auto Tune PlD select PID, enable Auto PID and enable Start PID.
Sometimes Auto PID parameter needs fine tuning i.e. for each 5°F over
shoot increase the Proportional Band (PB) by 15% and for each 1°F
fluctuation at the Setpoint (SP) increase reset by 20%.
Once started, display shows A.TUN with letters blinking in the rotating
pattern. When auto tune stops, display will show process value. Do not
perform any operations or settings before first stopping Auto Tune. Any
alarms or other output is disabled during Auto Tune.
If “AUTO PID” was “DISABLED”, the display will show the following
three submenus. This allows the user to manually enter values for
Proportional, Reset and Rate terms corresponding to P, I, and D. It also
can be used for auto PID for disabling unwanted parameter i.e. PI enter
0000 for rate.
PROPORTIONAL BAND SUBMENU:
st
Press
Press
Press
30) Display flashes 1 digit of the previous P
Proportional
PRoP
d
b
d
band value.
&
31) Press and buttons to enter a new “Proportional Band”
c
b
c
value.
32) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
REST
Reset Setup Submenu.
a
advance to
REST
Proportional band is in degrees of temperature or counts of process. Proportional
band is defined, as the change in the instrument input to cause a 100% change in
the controller output.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
RESET SETUP SUBMENU:
st
Press
Press
Press
33) Display flashes 1 digit of the previous I
Reset value.
d
b
d
REST
34) Press and buttons to enter a new “Reset” value.
&
c
b
c
35) Display shows
advances to
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
RATE
Rate Setup Submenu.
a
advance to
RATE
Reset unit is in seconds 0-3999.
RATE SETUP SUBMENU:
st
Press
Press
Press
36) Display flashes 1 digit of previous D
Rate value.
d
b
d
RATE
37) Press and buttons to enter a new
&
value.
c
b
c
RATE
stored message momentarily and then
38) Display shows
STRD
only, if it was changed, otherwise press
advances to the
CYCL
Cycle Time submenu for RTD and
a
to advance to
CYCL
Thermocouple types.
Rate unit is in seconds 000.0-399.9.
If the Output 1 is Analog Option the display skips to Damping
Factor.
CYCLE TIME SUBMENU:
st
Press
Press
Press
39) Display flashes 1 digit of the previous
Cycle Time
CYCL
d
b
d
value.
&
40) Press and buttons to enter a new “Cycle Time” value.
c
b
c
(1 to 199 seconds)
41) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
DPNG
Damping Factor Submenu.
a
advance to
DPNG
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).
41
Download from Www.Somanuals.com. All Manuals Search And Download.
DAMPING FACTOR SUBMENU:
Press
Press
42) Display flashes the previous “Damping Factor” selection.
43) Scroll through the available selections:
d
b
,
0000 0001 0002
,
,
,
,
,
,
.
0003 0004 0005 0006 0007
Press
44) Display flashes
stored message and then advances
STRD
d
to
to
only, if it was changed, otherwise press to advance
OUT2
OUT2
a
Output 2 Menu.
Damping Factor is a measure of speed, overshoot, and undershoot in which the
process variable responds to the output changes of the instrument, which were
used during the Auto Tune. This value is typically set to the ratio of Rate to
Reset. This Default value is (0003). For fast response time, this value should be
decreased while for slow response time it should be increased.
The "DEADBAND" Submenu will only appear if "ON/OFF" was
selected from the "Control Type" Menu.
DEADBAND SUBMENU:
st
Press
45) Display flashes 1 digit of the previous
Deadband
DEAD
d
value.
Press
Press
&
46) Press and buttons to enter a new “Deadband” value.
b
d
c
b
c
47) Display shows
stored message and then advances to
STRD
only, if it was changed, otherwise press to advance to
Output 2 Menu.
OUT2
OUT2
a
Dead Band units are the same as Proportional Band units.
The Dead Band or neutral zone is the number of degrees or counts
(if Input Type is Process) around the Setpoint which the Process Variable
must pass above or below the Setpoint, before the output changes state.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.11 Output 2
Output 2 and Alarm 2 share the same contacts on the rear panel connector. If
Alarm 2 is Enabled, Output 2 is automatically Disabled.
It is recommended that you put the
controller in the Standby Mode for any
configuration change other than
Setpoints & Alarms.
Figure 3.10 Flow Chart for Output 2
ENTER OUTPUT 2 MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
a
OUT2
Output 2 Menu.
4) Display advances to
Press
Control Type Submenu.
CTRL
d
CONTROL TYPE SUBMENU:
Press 3) Display flashes
ON/OFF, or PID.
PID
d
ON.OF
4) Scroll through the available selections: “ON/OFF” or “PID”.
Press b
Press
5) Display shows
stored message momentarily and then
STRD
d
advances to
only, if it was changed, otherwise press to
Action Type Submenu.
AçTN
a
advance to
AçTN
The ON/OFF control is a coarse way of controlling the Process. The “Dead
Band” improves the cycling associated with the ON/Off control. The PID control
is best for processes where the Setpoint is continuously changing and/or tight
control of the Process Variable is required.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it
would be called Direct Acting. If a negative error should cause the output to
decrease (i.e. heating), it would be called Reverse Acting.
Press
Press
Press
6) Display flashes
Direct or Reverse.
RVRS
d
b
d
DRçT
7) Scroll through the available selections: “Direct” or “Reverse”.
8) Display shows
stored message momentarily and then
STRD
AUTo
advances to
only, if it was changed, otherwise press to
a
advance to
selected).
Auto PID Submenu (If PID Control type was
AUTo
If ON/OFF was selected in the Control Type, the display skips to
the Dead Band Submenu.
AUTO PID SUBMENU:
Press
Press
9) Display flashes
Enable or
Disable.
DSBL
d
b
ENBL
10) Scroll through the available selections: “Enable” or “Disable”.
If "Enabled", the PID parameter of Output 1 will be copied to
Output 2.
Press
11) Display shows
stored message momentarily and then
STRD
d
advances to the next submenu only, if it was changed, otherwise
press to advance to the next submenu.
a
If AUTO PID was ENABLED", the display skips to the
CYCL
CYCLE TIME submenu. If "AUTO PID" was "DISABLED", the
display will show PROPORTIONAL BAND Submenu
PRoP
allowing the user to manually enter the Proportional Band value.
The Reset and Rate value are the same as Output 1.
PROPORTIONAL BAND SUBMENU:
st
Press
Press
Press
12) Display flashes 1 digit of the previous Proportional Band
d
b
d
value.
&
13) Press and buttons to enter a new Proportional Band
c
b
c
value.
14) Display shows
CYCL
advance to the
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
a
Cycle Time Submenu.
CYCL
Refer to “Proportional Band” Submenu of “Output 1” Menu.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
CYCLE TIME SUBMENU:
st
Press
Press
15) Display flashes 1 digit of the previous “Cycle Time” value.
d
b
&
16) Press and buttons to enter a new “Cycle Time” value
c
b
c
(1 to 199 seconds).
17) Display shows
advances to
Press
stored message momentarily and then
d
STRD
only, if it was changed, otherwise press to
RAMP
Ramp Value Submenu.
a
advance to
RAMP
A cycle time selected between 1 to 199 seconds indicates the total On/Off time
of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relays’
Control Outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher current
(higher than 1 Amp).
The DEADBAND Submenu will only appear if the ON/OFF was selected
from the "Control Type" Submenu.
DEADBAND SUBMENU:
Press
Press
Press
18) Display flashes 1st digit of the previous “Dead Band” value.
d
b
d
&
19) Press and buttons to enter a new “Dead Band” value.
c
b
c
20) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
RAMP
Ramp Value Menu.
a
advance to
RAMP
Dead Band units are the same as Proportional Band units.
The Dead Band is the number of degrees or counts around the Setpoint
which the Process Variable must pass through before the output changes
state.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
It is recommended that you put the
controller in the Standby Mode for any
configuration change other than
Setpoints & Alarms.
3.2.12 Ramp & Soak
Alarm must be
DISABLED if Ramp
is ENABLED.
Figure 3.11 Flow Chart for Ramp and Soak
ENTER RAMP AND SOAK MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
Ramp
RAMP
a
and
Soak Menu.
SOAK
RAMP ENABLE/DISABLE SUBMENU:
Press
4) Display advances to “Ramp Enable/Disable” Submenu and
flashes or
d
.
ENBL DSBL
5) Scroll through the available selections: “Enable” or “Disable”.
6) Display shows stored message momentarily and then
Press
Press
b
d
STRD
Soak Enable/Disable Menu.
advances to
SOAK
If
Disable was selected, display skips to the next menu
RAMP
item (ID Code).
SOAK ENABLE/DISABLE SUBMENU:
Press
Press
Press
7) Display flashes
or .
ENBL DSBL
d
b
d
8) Scroll through the available selections: “Enable” or “Disable”.
9) Display shows
stored message momentarily and then
STRD
advances to “Ramp Value” Submenu.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Ramp & Soak provides users with the flexibility to slowly bring the Process
Variable (PV) to the desired setpoint. Ramp & Soak values are specified in
HH.MM format. The Ramp value indicates the time specified to bring the process
variable to Setpoint 1 (SP1). Once the set point is reached, the PID takes over
and the Process Variable will be controlled at the desired set point indefinitely. If
Soak is enabled, PID will control the Process Variable at the specified Setpoint
for the duration of Soak time and then will turn off Output 1. To start a new
Ramp/Soak cycle, reset the instrument by pressing and then button.
a
c
An active Ramp/Soak will change SP1 one degree above the PV and will cause
the most significant digit to blink. The SP1 will be incremented by one degree
until it reaches the original SP1. The minimum Ramp time must be at least twice
the time that it will take the PV to reach the Setpoint Value (SV) with OUT 1 fully
ON.
RAMP VALUE SUBMENU:
st
Press
Press
Press
10) Display flashes 1 digit of previous stored “Ramp Value”.
d
b
d
&
11) Press and buttons to enter a new “Ramp Value”.
STRD
advances to “Soak Value” Submenu.
c
b
c
12) Display shows
stored message momentarily and then
SOAK VALUE SUBMENU:
Press
Press
Press
13) Display flashes 1st digit of previous stored “Soak Value”.
14) Press and buttons to enter a new “Soak Value”.
d
b
d
&
c
b
c
STRD
15) Display shows
stored message and advances to the
ID Code Menu.
ID
The Ramp and Soak time is 00:00 to 99:59 i.e. HH.MM. (from zero to 99 hours
and 59 minutes) During Ramp & Soak do not perform any operations or settings
before first stopping it. Any alarms or other output are disabled during this time.
To stop Ramp & Soak first put instrument into Standby Mode, then go to Ramp &
Soak Menu and disable it.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.13 ID CODE
Figure 3.12 Flow Chart for ID Code
ENTER ID CODE MENU:
Press 1) Press , if necessary, until
prompt appears.
a
a
CNFG
Input Menu.
Press d
Press
2) Display advances to
INPT
3) Press , if necessary, until Display advances to ID Code
ID
a
a
Menu.
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID CODE:
st
Press d
4) Display advances to
with 1 under score flashing.
____
Press
&
5) Press and to enter your 4-digit “ID Code” number.
c
b
b
c
Press d
6) Display advances to
Change ID Code Submenu.
CH.ID
If entered “ID Code” is incorrect display shows
Error
ERRo
message momentarily and then skips to the Run Mode.
Press
7) Display flashes the first digit of previous entered “ID Code”
number.
d
Press
Press
&
8) Press and buttons to enter your new “ID Code” number.
b
d
c
b
c
9) Display shows
stored message momentarily and then
STRD
advances to the
Full Security Submenu.
FULL
48
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:
Enter menu (Repeat steps from 1 to 3).
ID
Press
Press
10) Display advances to
Change ID Code Submenu.
d
d
CH.ID
message with flashing 1 digit.
st
11) Display shows
0000
If you want to change your default “ID Code” you can do it now,
otherwise press and menu will skip to
Full Security
FULL
a
Submenu.
Press
Press
&
12) Press and buttons to enter your new “ID Code” number.
b
d
c
b
c
13) Display shows
stored message momentarily and then
STRD
Full Security Submenu.
advances to the
FULL
FULL SECURITY LEVEL SUBMENU:
Press
Press
Press
14) Display flashes
Enable or Disable.
DSBL
d
b
d
ENBL
15) Scroll through the available selections: “Enable” or “Disable”.
16) Display shows stored message momentarily and then
STRD
Setpoint/ID Submenu.
advances to
SP.ID
If "Full" Security Level is "Enabled" and the user attempts to
enter the Main Menu, they will be prompted for an ID Code. The
ID Code should be correct to enter the instrument Menu item.
SETPOINT/ID SECURITY LEVEL SUBMENU:
This Security Level can be functional only if
Level is Disabled.
Security
FULL
Press
Press
Press
17) Display flashes
Enable or
Disable.
DSBL
d
b
d
ENBL
18) Scroll through the available selections: “Enable” or “Disable”.
19) Display shows
stored message momentarily and then
STRD
Communication Submenu.
advances to
COMM
If "Setpoint/ID" Security Level is "Enabled" and the user
attempts to advance into the Configuration Menu, he will
CNFG
be prompted for ID Code number. The ID Code should be
correct to proceed into the Configuration Menu, otherwise
display will show an Error and skip to the Run Mode.
If “Full” and “Setpoint/ID” Security Levels are "Disabled", the
ID code will be “Disabled” and user will not be asked for ID
Code to enter the Menu items (“ID” Submenu will not show upin
“ID/Setpoint” Menu).
49
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.14 COMMUNICATION OPTION
Purchasing the controller with Serial Communications permits an instrument to be
configured or monitored from an IBM PC compatible computer using software
available from the website or on the CD-ROM enclosed with your shipment.
For complete instructions on the use of the Communications Option, refer to the
Serial Communications Reference Manual.
Figure 3.13 Flow Chart for Communication Option
50
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER COMMUNICATION OPTION MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
a
COMM
Communication Options Menu.
Press
4) Display advances to
Submenu.
Communication Parameters
C.PAR
d
If Communication Option is not installed, the display shows
and skips to the Color Display Menu.
NONE
COMMUNICATION PARAMETERS SUBMENU:
Allows the user to adjust Serial Communications Settings of the instrument.
When connecting an instrument to a computer or other device, the
Communications Parameters must match. Generally the default settings
(as shown in Section 5) should be utilized.
Press
5) Display advances to
Baud Submenu.
BAUD
d
BAUD SUBMENU:
Press
Press
6) Display flashes previous selection for
value.
BAUD
d
b
7) Scroll through the available selections:
,
300_ 600_ 1200
,
,
,
,
,
.
2400 4800 9600 19.2K
8) Display shows
Press
stored message momentarily and then
d
STRD
only, if it was changed, otherwise press to
advances to
PRTY
Parity Submenu.
a
advance to
PRTY
PARITY SUBMENU:
Press
Press
Press
9) Display flashes previous selection for “Parity”.
d
b
d
10) Scroll through the available selections: NO, ODD, EVEN.
11) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
DATA
Data Bit Submenu.
a
advance to
DATA
DATA BIT SUBMENU:
Press
Press
Press
12) Display flashes previous selection for “Data Bit”.
d
b
d
13) Scroll through the available selections: 7-BIT, 8-BIT.
14) Display shows
STOP
STOP
stored message and then advances to
STRD
only, if it was changed, otherwise press to advance to
a
Stop Bit Submenu.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
STOP BIT SUBMENU:
Press
Press
Press
15) Display flashes previous selection for “Stop Bit”.
16) Scroll through the available selections:
d
b
d
,
.
1-BIT 2-BIT
17) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
BUS.F
Bus Format Submenu.
a
advance to
BUS.F
BUS FORMAT SUBMENU:
Determines Communications Standards and Command/Data Formats for
transferring information into and out of the controller via the Serial
Communications Bus. Bus Format submenus essentially determine how and
when data can be accessed via the Serial Communications of the device.
Press
18) Display advances to
Modbus Submenu.
M.BUS
d
MODBUS PROTOCOL SUBMENU:
Press
Press
Press
19) Display flashes previous selection for
.
d
b
d
M.BUS
20) Scroll through the available selections: NO, YES.
21) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
_LF_
Line Feed submenu.
a
advance to
_LF_
To select iSeries Protocol, set Modbus submenu to “No”.
To select Modbus Protocol, set Modbus submenu to “Yes”.
If Modbus Protocol was selected, the following Communications
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not
attempt to change these parameters.
LINE FEED SUBMENU:
Determines if data sent from the instrument will have a Line Feed appended to
the end - useful for viewing or logging results on separate lines when displayed
on communications software at a computer.
Press
Press
Press
22) Display flashes previous selection for “Line Feed”.
d
b
d
23) Scroll through the available selections: NO, YES.
24) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
ECHO
Echo Submenu.
a
advance to
ECHO
ECHO SUBMENU:
When valid commands are sent to the instrument, this determines whether the
command will be echoed to the Serial Bus. Use of echo is recommended in most
situations, especially to help verify that data was received and recognized by the
controller.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Press
Press
Press
25) Display flashes previous selection for “Echo”.
d
b
d
26) Scroll through the available selections: NO, YES.
27) Display flashes
stored message momentarily and then
STRD
only if it was changed, otherwise press to
advances to
STND
Communication Standard Submenu.
a
advance to
STND
COMMUNICATION INTERFACE STANDARD SUBMENU:
Determines whether device should be connected to an RS-232C serial port
(as is commonly used on IBM PC-compatible computers) or via an RS-485 bus
connected through appropriate RS-232/485 converter. When used in RS-485
Mode, the device must be accessed with an appropriate Address Value as
selected in the Address Submenu described later.
Press
Press
Press
28) Display flashes previous selection for “Standard”.
d
b
d
29) Scroll through the available selections: 232C, 485.
30) Display shows
stored message momentarily and then
STRD
advances to
only, if it was changed, otherwise press to
MoDE
MoDE
a
advance to
Data Flow Mode Submenu.
DATA FLOW MODE SUBMENU:
Determines whether the instrument will wait for commands and data requests
from the Serial Bus or whether the instrument will send data automatically and
continuously to the Serial Bus. Devices configured for the RS-485
Communications Standard operate properly only under Command Mode.
Press
Press
31) Display flashes previous selection for “Mode”.
32) Scroll through the available selections:
d
b
“Command”,
_
CMD
“Continuous”.
CoNT
33) Display shows
Press
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
d
advances to
SEPR
Data Separation Submenu.
a
advance to
SEPR
DATA SEPARATION CHARACTER SUBMENU:
Determines whether data sent from the device in Continuous Data Flow Mode
will be separated by spaces or by Carriage Returns.
Press
Press
34) Display flashes previous selection for “Separation” Submenu.
35) Scroll through the available selections: “Space” or
d
b
SPCE
“Carriage Return”.
_çR_
36) Display shows
Press
stored message momentarily and then
STRD
d
advances to
only, if it was changed, otherwise press to
DAT.F
a
advance to
Data Format Submenu.
DAT.F
53
Download from Www.Somanuals.com. All Manuals Search And Download.
DATA FORMAT SUBMENU:
Preformatted data can be sent automatically or upon request from the controller.
Use the Data Format Submenus to determine what data will be sent in this
preformatted data string. Refer to the iSeries Communications Manual for more
information about the data format. At least one of the following suboptions must
be enabled and hence output data to the Serial Bus.
This menu is applicable for Continuous Mode of RS-232 communication.
Press
37) Display advances to
Alarm Status Submenu.
STAT
d
ALARM STATUS SUBMENU:
Includes Alarm Status bytes in the data string.
Press
Press
Press
38) Display flashes previous selection for “Status” (alarm status).
d
b
d
39) Scroll through the available selections: NO, YES.
40) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
advance to
RDNG
Reading Submenu.
a
RDNG
MAIN READING SUBMENU:
Includes Main Reading in the data string.
Press
Press
Press
41) Display flashes previous selection for “Reading”.
42) Scroll through the available selections: NO, YES.
43) Display shows stored message momentarily and then
d
b
d
STRD
only, if it was changed, otherwise press to
advances to
PEAK
Peak Submenu.
a
advance to
PEAK
PEAK VALUE SUBMENU:
Includes Peak Value in the data string.
Press
Press
Press
44) Display flashes previous selection for
Submenu.
d
b
d
PEAK
45) Scroll through the available selections: NO, YES.
46) Display shows stored message momentarily and then
STRD
only, it was changed, otherwise press to
advances to
advance to
VALY
Valley Submenu.
a
VALY
VALLEY VALUE SUBMENU:
Includes Valley Value in the data string.
Press
Press
Press
47) Display flashes previous selection for “Valley”.
48) Scroll through the available selections: NO, YES.
49) Display shows stored message momentarily and then
d
b
d
STRD
advances to
only, if it was changed, otherwise press to
UNIT
a
advance to
Temperature Unit Submenu.
UNIT
54
Download from Www.Somanuals.com. All Manuals Search And Download.
TEMPERATURE UNIT SUBMENU:
Includes a byte in the data string to indicate whether reading is in Celsius or
Fahrenheit.
Press
Press
Press
50) Display flashes previous selection for
.
d
b
d
UNIT
51) Scroll through the available selections: NO, YES.
52) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
ADDR
Address Setup Submenu.
a
advance to
ADDR
ADDRESS SETUP SUBMENU:
This menu is applicable to the RS-485 Option only.
Press
53) Display advances to “Address Value” (0000 to 0199) Submenu.
d
ADDRESS VALUE SUBMENU:
st
Press
Press
Press
54) Display flashes 1 digit of previously stored Address Value.
d
b
d
&
55) Press and to enter new “Address Value”.
c
b
c
56) Display shows
advances to
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
TR.TM
Transmit Time Interval Submenu.
a
advance to
TR.TM
TRANSMIT TIME INTERVAL SUBMENU:
This menu is applicable if “Continuous” Mode was selected in the “Data
Flow Mode” Submenu and the device is configured as an RS-232C
Standard device. Also, one or more options under the Data Format
Submenu must be enabled.
Press
57) Display advances to “Transmit Time Value” Submenu.
d
TRANSMIT TIME INTERVAL VALUE SUBMENU:
Determines the interval at which data will be emitted to the RS-232 Serial Bus
when the instrument is in Continuous Data Flow Mode.
st
Press
Press
Press
58) Display flashes 1 digit of previous “Transmit Time Value” in
seconds.
d
b
d
&
59) Press and to enter new “Transmit Time Value”, e.g.
0030 will send the data every 30 seconds in Continuous Mode.
c
b
c
60) Display shows
advances to
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
COLR
Color Display Selection Menu.
a
advance to
COLR
For more details, refer to the Communication Manual available at the
website listed in the cover page of this manual or on the CD-ROM
enclosed with your shipment.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.15 DISPLAY COLOR SELECTION
This submenu allows the user to select the color of the display.
Figure 3.14 Flow Chart for Display Color Selection
ENTER DISPLAY COLOR SELECTION MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
a
COLR
Display Color Selection Menu.
Press
4) Display advances to
Normal Color Submenu.
N.CLR
d
NORMAL COLOR DISPLAY SUBMENU:
Press
Press
Press
5) Display flashes the previous selection for “Normal Color”.
6) Scroll through the available selections: or
d
b
d
,
.
GRN RED AMBR
stored message momentarily and then
7) Display shows
STRD
only, if it was changed, otherwise press to
advances to
advance to
1.CLR
Alarm 1 Display Color Submenu.
a
1.CLR
The menu below allows the user to change the color of display when alarm is
triggered.
ALARM 1 DISPLAY COLOR SUBMENU:
Press
8) Display flashes previous selection for “Alarm 1 Color
d
Display”.
Press
Press
9) Scroll through the available selections:
,
or .
b
d
GRN RED AMBR
stored message momentarily and then
10) Display shows
STRD
advances to
only, if it was changed, otherwise press to
2.CLR
a
advance to
Alarm 2 Display Color Submenu.
2.CLR
56
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM 2 DISPLAY COLOR SUBMENU:
Press
Press
Press
11) Display flashes previous selection for “Alarm 2 Color Display”.
12) Scroll through the available selections: or
d
b
d
,
.
GRN RED AMBR
stored message momentarily and then
13) Display shows
STRD
momentarily shows the software version number, followed by
Reset, and then proceeds to the Run Mode.
RST
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the Display to change color every time when both Alarm 1
and Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Example 1:
Output 1 & Output 2 = SSR
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200, Alarm 1
HI Value “ALR.H” = 400
"Color Display" Setup: Normal Color “N.CLR” = Green, Alarm 1 Color
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Display Colors change sequences:
GREEN RED
AMBER
-- ------------------------------ ----------------------------- ------------------------------
• ➤
•
•
➤
0
AL2.H = 200
AL1.H = 400
Example 2:
Output 1 & Output 2 = Pulse
Alarm Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300, Alarm 1
Low Value “ALR.L” = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER RED
GREEN
➤
➤
-------------- ---------------------------------- ------------------------------------------- --
•
0
•
•
•
AL1.L = 100
AL2.L = 300
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Example 3:
Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display Colors change sequences:
RED
--------------- ------ ------ -------------------------------- ------ ------- ----------------
➤
RED
RED
GREEN
RED
•➤
•
•
•
•
•
•
0
190 200 210
290 300 310
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.
If Analog Output Option board is installed (Alarm 1 is disabled), only
Alarm 2 is active and only two colors are available.
Example 4:
Output 1 = Relay, Setpoint 1 = 200
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 Setup: Deviation, Band, “ALR.H” = 20
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display colors change sequences:
AMBER RED GREEN GREEN
RED
AMBER
-- --------------- ---------------- ------------- -------------- ------------- ---------------------
• ➤
•
•
•
•
•
➤
0
180
195
200
210
220
Reset: The instrument automatically resets after the last menu of
the Configuration Mode has been entered. After the instrument
resets, it advances to the Run Mode.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 4
SPECIFICATIONS
Configuration
Accuracy
Single-ended
0.5°C temp; 0.03% reading process
Resolution
Polarity
Unipolar
1°/0.1°; 10 µV process
Temperature Stability
1) RTD: 0.04°C/°C
2) TC @ 25°C (77°F): 0.05°C/°C
- Cold Junction Compensation
3) Process: 50 ppm/°C
NMRR
Step Response
0.7 sec for 99.9%
Decimal Selection
None, 0.1 for temperature
None, 0.1, 0.01 or 0.001 for
process
Setpoint Adjustment
-1999 to 9999 counts
Span Adjustment
0.001 to 9999 counts
Offset Adjustment
-1999 to +9999
60 dB
CMRR
120 dB
A/D Conversion
Dual slope
Reading Rate
3 samples per second
Digital Filter
CONTROL
Action
Reverse (heat) or direct (cool)
Modes
Programmable
Display
4-digit or 6-digit, 7-segment LED
57.2 mm (2.25") or 101.6mm (4.00”)
red, green and amber programmable
colors for process variable, set point
and temperature units
Warm up to Rated Accuracy
60 min.
Time and Amplitude Proportional
Control Modes; selectable Manual
or Auto PID, Proportional,
Proportional with Integral,
Proportional with Derivative with
Anti-reset Windup and ON/OFF
Rate
0 to 399.9 seconds
Reset
0 to 3999 seconds
Cycle Time
INPUT
Input Types
Thermocouple, RTD, Analog Voltage,
Analog Current
1 to 199 seconds; set to 0 for
ON/OFF operation
Gain
Thermocouple Type (ITS 90)
J, K, T, E, R, S, B, C, N, L
Thermocouple Lead Resistance
100 ohm max
0.5 to 100% of span; Setpoints 1
or 2
RTD Input (ITS 68)
Damping
100/500/1000 Ω Pt sensor, 2-, 3- or
4-wire; 0.00385 or 0.00392 curve
Voltage Input
0000 to 0008
Soak
00.00 to 99.59 (HH:MM), or OFF
Ramp to Setpoint
00.00 to 99.59 (HH:MM), or OFF
Auto Tune
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc
Input Impedance
10 MΩ for 100 mV
1 MΩ for 1 or 10 Vdc
Current Input
Operator initiated from front panel
0 to 20 mA (5 ohm load)
59
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL OUTPUT 1 & 2
Relay
EXCITATION
(optional in place of
Communication)
24 Vdc @ 25 mA
250 Vac or 30 Vdc @ 3 A
(Resistive Load); configurable for
on/off, PID and Ramp and Soak
Output 1: SPDT type, can be
configured as Alarm 1 output
Output 2: SPDT type, can be
configured as Alarm 2 output
SSR
INSULATION
Power to Input/Output
2500 Vac per 1 minute test
(RS-232/485, Input or Output)
Between Inputs
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous
DC Pulse
Non-Isolated; 10 Vdc @ 20 mA
Analog Output (Output 1 only)
Non-Isolated, Proportional 0 to 10 Vdc
or 0 to 20 mA; 500 Ω max
500 Vac per 1 minute test
Approvals
See CE Approval Section
GENERAL
Power
100-240 Vac +/-10%, 50/60 Hz
22.5 W
COMMUNICATIONS (optional)
RS-232 or RS-485 programmable
300 to 19.2 K baud; complete
programmable setup capability;
program to transmit current display,
alarm status, Peak and Valley value.
RS-485
Addressable from 0 to 199
Connection
Screw terminals
Fuse
4A, 250V, GFE, 5x20mm
Environmental Conditions
0 to 40°C (32 to 104°F),
90% RH non-condensing
Installation Category
II per EN61010-1
Equipment Class
I per EN61010-1
Pollution Degree
2 per EN61010-1
ALARM 1 & 2 (programmable):
Type
Same as Output 1 & 2
Protection
NEMA-4x (IP65) front bezel
Dimensions and Panel Cutout
Refer to Quickstart Specifications.
Weight
Operation
High/low, above/below, band,
latch/unlatch, normally open/normally
closed and process/deviation; front
panel configurations
Refer to Quickstart Specifications.
ANALOG OUTPUT (programmable)
Non-Isolated, Retransmission 0 to 10
Vdc or 0 to 20 mA, 500 Ω max (Output
1 only). Accuracy is + 1% of FS when
following conditions are satisfied.
1) Input is not scaled below 1% of
Input FS.
2) Analog Output is not scaled below
3% of Output FS.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4.1 Input Properties
TC
Input Type
Iron-Constantan
Range
-210 to 760°C
Accuracy*
0.4°C
0.7°F
J
-346 to 1400°F
-270 to -160°C
-160 to 1372°C
-454 to -256°F
-256 to 2502°F
-270 to -190°C
-190 to 400°C
-454 to -310°F
-310 to 752°F
-270 to -220°C
-220 to 1000°C
-454 to -364°F
-364 to 1832°F
-50 to 40°C
40 to 1788°C
-58 to 104°F
104 to 3250°F
-50 to 100°C
100 to 1768°C
-58 to 212°F
1.0°C
0.4°C
1.8°F
CHROMEGA®-
ALOMEGA®
K
0.7°F
1.0°C
0.4°C
1.8°F
Copper-Constantan
T
0.7°F
1.0°C
0.4°C
1.8°F
CHROMEGA-
Constantan
E
R
S
0.7°F
1.0°C
0.5°C
1.8°F
Pt/13%Rh-Pt
Pt/10%Rh-Pt
0.9°F
1.0°C
0.5°C
1.8°F
212 to 3214°F
200 to 640°C
640 to 1820°C
212 to 1184°F
1184 to 3308°F
0 to 2354°C
0.9°F
1.0°C
0.5°C
1.8°F
0.9°F
0.4°C
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
0.4°C
0.7°F
30%Rh-Pt/
6%Rh-Pt
B
C
N
5%Re-W/
26%Re-W
32 to 4253°F
-250 to -100°C
-100 to 1300°C
-418 to -148°F
-148 to 2372°F
-200 to 900°C
-328 to 1652°F
200 to 900°C
-328 to 1652°F
-200 to 850°C
-328 to 1562°F
0 to 100 mV, 0 to 1 V,
0 to 10 Vdc
Nicrosil-Nisil
J
DIN
L
RTD
RTD
PROCESS
Pt, 0.00385, 100 Ω,
500 Ω, 1000 Ω
Pt, 0.00392, 100 Ω,
500 Ω, 1000 Ω
Voltage
0.4°C
0.7°F
0.4°C
0.7°F
0.03% rdg
0.03% rdg
0.03% rdg
PROCESS Current
0 to 20 mA, 4 to 20 mA
61
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 5
FACTORY PRESET VALUES
Table 5.1 Factory preset value
MENU ITEMS
FACTORY PRESET VALUES
NOTES
Set Point 1 (SP1)
Set Point 2 (SP2)
000.0
000.0
Input:
Input Type (INPT)
TC, type K
Reading Configuration (RDG):
Decimal Point (DEC.P)
Temperature unit (TEMP)
Filter value (FLTR)
FFF.F
°F
0004
:
Alarm 1 & 2
Alarm 1 (ALR1), Alarm 2 (ALR2)
Absolute/Deviation (ABSO/DEV)
Latch/Unlatch (LTCH/UNLT)
Contact Closure (CT.CL)
Active (ACTV)
Disable (DSBL)
Absolute (ABSO)
Unlatch (UNLT)
Normally Open (N.O.)
Above (ABOV)
Disable (DSBL)
-100.0
Alarm At Power On (A.P.ON)
Alarm Low (ALR.L)
Alarm 1 only
Alarm High (ALR.H)
400.0
LOOP:
Loop Break Time (LOOP)
Loop Value (B.TIM)
Disable (DSBL)
00:59
Reading Adjust Value (R.ADJ)
000.0
ANALOG OUTPUT (Retransmission):
Analog Output (ANLG)
Current/Voltage (CURR/VOLT)
Scale and Offset
Enabled (ENBL)
Voltage (VOLT)
Reading: 0 - 999.9 cts, Output: 0 - 10 V
OUTPUT 1 & 2:
Self (SELF)
Disabled (DSBL)
0000
0099
On/Off
Reverse (RVRS)
020.0
Disable (DSBL)
Disable (DSBL)
020.0
0180
0000
Output 1 only
Output 1 only
Output 1 only
% Low Value (%LO)
% High Value (%HI)
Control Type (CTRL)
Action Type (ACTN)
Dead Band (DEAD)
PID Auto (AUTO)
Anti Integral (ANTI)
Proportion Value (PROP)
Reset Value (REST)
Rate Value (RATE)
Cycle Value (CYCL)
Damping Factor (DPNG)
Output 1 only
Output 1 only
Output 1 only
0007
0003
62
Download from Www.Somanuals.com. All Manuals Search And Download.
MENU ITEMS
Ramp & Soak (RAMP)
Ramp (RAMP)
Soak (SOAK)
Ramp Value (RAMP)
Soak Value (SOAK)
FACTORY PRESET VALUES
NOTES
:
Disable (DSBL)
Disable (DSBL)
00:00
00:00
:
ID
ID Value
0000
Full ID (FULL)
Set Point ID (ID.SP)
Disable (DSBL)
Disable (DSBL)
Communication Parameters:
Baud Rate (BAUD)
Parity (PRTY)
9600
Odd
Data bit (DATA)
7 bit
Stop Bit
1 bit
Modbus Protocol (M.BUS)
Line Feed (LF)
No
No
Echo (ECHO)
Yes
Standard Interface (STND)
Command Mode (MODE)
Separation (SEPR)
Alarm Status (STAT)
Reading (RDNG)
RS-232 (232C)
Command (CMD)
Space (SPCE)
No
Yes
No
Peak
Valley (VALY)
No
Units (UNIT)
No
Multipoint Address (ADDR)
Transmit Time (TR.TM)
Display Color (COLR):
Normal Color (N.CLR)
Alarm 1 Color (1.CLR)
Alarm 2 Color (2.CLR)
0001
0016
Green (GRN)
Red (RED)
Amber (AMBR)
63
Download from Www.Somanuals.com. All Manuals Search And Download.
CE APPROVAL INFORMATION
1.Electromagnetic Compatibility (EMC)
This device conforms with requirements of EMC Directive 89/336/EEC,
amended by 93/68/EEC. This instrument complies with the following EMC
Immunity Standards as tested per EN 61326-2:1998 (Industrial Locations)
Phenomena
Test Specification
Basic Standard
Electrostatic
Discharge
+/- 4 kV contact discharge
+/- 8 kV air discharge
IEC 1000-4-2
Performance
Criteria B
Radio Frequency
electromagnetic
field.
27 - 1000 MHz
3 V/m
80% AM (1 KHz)
IEC 1000-4-3
Performance
Criteria A
Fast Transients
+/- 2 kV (ac mains)
+/- 1 kV (dc, signal I/O)
5/50 ns Tr/Th, 5 KHz rep. freq.
IEC 1000-4-4
Performance
Criteria B
Surge
+/- 1.0 kV AC Port L-L
+/- 2.0 kV AC Port L-PE
+/- 1.0 kV DC Port L-L
+/- 2.0 kV DC Port L-PE
IEC 1000-4-5
Performance
Criteria B
Radio Frequency
conducted
0.15 - 80 MHz
3 Vrms
80% AM (1 KHz)
IEC 1000-4-6
Performance
Criteria A
This instrument complies with the following EMC Emission Standards as
tested per EN 61326-2:1998 (Class B equipment)
Phenomena
Frequency
Range
Limits
Basic
Standard
Radiated
Emission
30-230 MHz
230-1000 MHz
30 dB_V/m at 10 m
37 dB_V/m at 10 m
quasi peak
CISPR 22
Class B
Conducted
Emission
0.15-0.5 MHz
0.5-5 MHz
5-30 MHz
66-56 dB_V quasi peak
56 dB_V quasi peak
60 dB_V quasi peak
CISPR 22
Class B
2.Safety
This device conforms with Low Voltage Directive 73/23/EEC, amended by 93/68/EEC.
The following LVD requirements have been met to comply with EN 61010-1, 1993
(Electrical equipment for measurement, control and laboratory use)
1.Pollution Degree 2
2.Installation Category II
3.Class I Equipment (100-240 Vac Powered Units)
64
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
65
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will
extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is
returned to OMEGA.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon
examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s
WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to
mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification.
This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having
been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification;
misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not
warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the use of its products in accordance with information provided by OMEGA, either verbal or written.
OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA
MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR
IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability
of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification,
strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is
based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth
in our basic WARRANTY/ DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in
such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE
contacting OMEGA:
FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1. Purchase Order number under which the product
was PURCHASED,
1. Purchase Order number to cover the COST
of the repair,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
2. Model and serial number of product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
© Copyright 2004 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced,
translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of
OMEGA ENGINEERING, INC.
® , and
are Trademarks of OMEGA ENGINEERING, INC.
®
®
TRADEMARK NOTICE:
, omega.com ,
™
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577
;
6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 /
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. Other US and International Patents pending or applied
for.
Download from Www.Somanuals.com. All Manuals Search And Download.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
TEMPERATURE
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Transducers & Strain Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
FLOW/LEVEL
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/Paddlewheel Systems
Totalizers & Batch Controllers
pH/CONDUCTIVITY
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters
HEATERS
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Heating Cable
Cartridge & Strip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved Oxygen Instruments
M3716/0204