Murphy Network Card SM1 User Manual

TSM-95129N  
Revised 01-97  
Section 15  
TM  
SM Series TANKTEND Systems  
(00-02-2019)  
Installation and Operation Instructions  
Models: SM1, SM1VR, SM2, SM2VR, SM3, SM3VR, SM4, SM4VR  
®
FRANK W.  
MFR.  
Please read the following information before installing. A visual inspection of this product for damage during shipping is recommended  
before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC and local codes.  
GENERAL INFORMATION  
Mounting Dimensions  
SM1 / SM1VR (1-Tank Monitoring Systems)  
14 in. (355 mm)  
WARNING  
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT  
14 in.  
(355 mm)  
Disconnect all electrical power to the machine.  
1-1/2 in.  
Make sure the machine cannot operate during installation.  
(38 mm)  
1/4 in.  
Follow all safety warnings of the machine manufacturer.  
(6 mm) dia.  
4-places  
Read and follow all installation instructions.  
Mounting Holes  
1-1/2 in. (38 mm)  
3 in.  
(76 mm)  
The SM Series System can monitor above or below ground,  
single or multi-tank systems (4 tanks maximum). The SM Series  
includes BGT1 gage (s) in a wall mounting panel. The SMVR series  
includes a vapor recovery option that compensates for gas blankets or  
head pressure caused by vapor recovery storage systems.  
SM2 / SM2VR (2-Tank Monitoring Systems)  
*
*
*
25-3/8 in. (645 mm)  
14 in.  
(355 mm)  
The SM includes a push-button actuated electrical pump assembly, that  
supplies the air to clear sensing lines for current readings. Pump oper-  
ating voltages available are 120 or 230 VAC (see below).  
2-1/2 in.  
1/4 in.  
(6 mm) dia.  
(63 mm)  
SM Series Specifications  
Panel: Hollow wall mount, cold rolled steel, painted.  
Shipping Weight (P100 Pump included):  
SM1: 27 lb. (12.25 kg) approximately.  
SM2: 44 lb. (20 kg) approx.  
SM3: 54 lb. (24.5 kg) approx.  
SM4: 65 lb. (29.5 kg) approx.  
Shipping Dimensions for All Models (P100 Pump included):  
40 x 9 x 15-3/4 in. (1016 x 229 x 400 mm).  
4-places  
Mounting Holes  
1-3/16 in.  
(30 mm)  
3 in.  
(76 mm)  
SM3 / SM3VR (3-Tank Monitoring Systems)  
36 in. (914 mm)  
14 in.  
(355 mm)  
SMPA and SMPA230 Pump Assemblies  
Operating Voltage: 120 VAC (SMPA); 230 VAC (SMPA230).  
Power Cable: Insulated, 16 AWG (1.5 mm2) x 8 ft. (2.4 m).  
Case: Weatherproof enclosure; painted.  
2-1/2 in.  
(63 mm)  
1-3/16 in.  
(30 mm)  
1/4 in. (6 mm) dia.  
Shipping Weight: 10 lbs. (4.53 kg).  
Shipping Dimensions: 12 x 12 x 10 in. (305 x 305 x 254 mm).  
3 in.  
4-places–Mounting Holes  
(76 mm)  
SM4 / SM4VR (4-Tank Monitoring Systems)  
SMPA and SMPA230 Mounting Dimensions  
39-1/2 in. (1 m)  
1-1/4 in.  
(32 mm)  
14 in.  
(355 mm)  
12-1/4 in.  
(311 mm)  
9/32 in.  
10 in.  
(7 mm) dia.  
6-places  
2-1/2 in.  
(63 mm)  
(254 mm)  
1/4 in. (6 mm) dia.  
1-3/16 in.  
(30 mm)  
3 in.  
3 in.  
3 in.  
5/8 in.  
4-places–Mounting Holes  
4-1/8 in.  
(76 mm)  
(76 mm)  
(76 mm)  
(16 mm)  
(105 mm)  
*
Mounting dimensions also apply for vertical mounting configurations.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION Continued  
Installing the CKBO Check Valve  
Fig. 3 SM Panel Tubing Configuration  
The optional CKBO check valve is designed  
to prevent product from backing up into the  
gage(s). We recommend installing the  
CKBO valve at top of the tank plug as  
follows (refer to Detail C):  
(SM2 Model shown)  
Detail C  
Tubing  
1/4 NPTM  
straight  
fitting  
Valve  
Flat  
1. Determine a location for the valve.  
Use of sealant on all fitting  
FEET  
FEET  
Check  
Valve  
T
A
N
K
MURPHY  
MURPHY  
threads is strongly suggested.  
LEVELGAGE  
LEVELGAGE  
2. Attach CKBO to the tank plug  
using wrench on valve flats.  
See markings on the valve body  
for positioning.  
1/2 NPTM to  
1/4 NPTF  
Reducer  
1/4 NPTM  
straight fitting  
Ferrule  
Hole Plug  
Ferrule nut  
UTKN Tank Plug  
or tank top  
3. Attach tubing to CKBO as shown.  
Securely tighten all fittings.  
To Pump  
Assembly  
All connections must be air tight.  
Installing the SMPA/SMPA230 Pump Assembly  
The pump assembly should be installed near the SM or SMVR panel.  
Connect the pump as follows (refer to Fig. 3 and 4 also see Detail D):  
To Tank 2 Plug  
Sensor Fitting  
To Tank 1 Plug  
Sensor Fitting  
To Tank 1 Plug  
Vapor Recovery  
Fitting  
To Tank 2 Plug  
Vapor Recovery  
Fitting  
1. Before connecting the tubing from the SM or  
Detail D  
SMVR panel to the pump assembly, make sure  
the tubing reaches the pump assembly  
Pump  
Panel  
sensor fitting.  
Fig. 4 Pump Assembly  
2. Connect the end of the tubing to the sen-  
sor fitting as shown at right (Detail D).  
Tubing should be continuous length  
without splices.  
3. The pump assembly includes a power  
cable, 16 AWG (1.5 mm2), 8 ft. (2.4 m)  
long. Connect the cable to 120 VAC or  
230 VAC power source.  
Sensor Fitting  
Ferrule  
Power  
Cable  
Pressure SWICHGAGE®  
Compression  
Nut  
Tubing  
PSI  
The pump assembly has a pressure SWICHGAGE®  
kPa  
PRESSURE  
with low and high pressure set points. When the gage pointer reaches the  
low pressure set point, the pump starts to built up purge pressure. When the  
pointer reaches the high set point, sufficient volume is reached stopping the  
pump. The set points are factory pre-set for your convenience.  
High trip point  
adjustment  
Low trip point  
adjustment  
Resetting the Pointer  
120 VAC or 230 VAC  
CAUTION: SM and SMVR models are precalibrated in feet of  
static pressure above gage connection. Pointer MUST be reset to zero.  
Tubing to SM Panel  
After the SM/SMVR complete system has been connected, reset the pointer  
for proper level indication, proceed as follows  
Detail E  
(see Fig. 5 and Detail E):  
Fig. 5  
1. Determine actual product level by any reliable  
means and record this value.  
2. Very carefully remove the retaining ring  
Turn to Raise  
Snap Ring  
the Pointer  
guarding against its spring-action, it can  
cause injuries. Remove the lens also.  
FEET  
FEET  
Pointer  
3. Carefully hold the pointer, as shown at  
right, making sure not to bend it.  
4. With a small screwdriver, turn the setting  
MURPHY  
LEVELGAGE  
MURPHY  
LEVELGAGE  
Turn to Lower  
the Pointer  
Read Button  
screw to corresponding stick reading value  
recorded in step 1.  
UNLEADED  
UNLEADED  
Clockwise to raise the pointer — counter clockwise to lower the pointer.  
5. Replace the lens and snap ring.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION Continued  
Operation Sequence  
Fig. 6  
IMPORTANT: Make sure SM Series system is completely  
installed and operative. Check that all connections are air tight.  
Snap Ring  
1. Make sure that the pump assembly is connected to a power source,  
either 120 VAC or 230 VAC according to the pump model used.  
2. Depress the read button, located next to the gage(s) and hold until the  
gage pointer stops traveling across the scale. See Fig. 6, at right.  
3. When pointer stops release the read button to allow pointer to settle.  
4. The value observed in the dial of the gage, is the level of the tank.  
5. Perform this operation as necessary for each tank to be checked.  
FEET  
FEET  
Pointer  
MURPHY  
LEVELGAGE  
MURPHY  
LEVELGAGE  
Read Button  
UNLEADED  
UNLEADED  
Service Parts and Accessories  
UTKN2:  
2 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings).  
2 NPTM tank plug less tubing (includes fittings).  
UTKN2LT:  
UTKN4:  
4 NPTM tank plug kit (includes 12 ft. [3.66 m] of stainless steel tubing/probe and fittings).  
4 NPTM tank plug less tubing (includes fittings).  
UTKN4LT:  
UTKN4VR:  
UTKN4VRLT:  
SMPA:  
4 NPTM tank kit for vapor recovery (tubing and fittings included).  
4 NPTM tank plug for vapor recovery– less tubing (includes fittings).  
Pump assembly for 120 VAC.  
SMPA230:  
05090051:  
CKBO:  
Pump assembly for 230 VAC.  
Pressure SWICHGAGE® instrument with low and high pressure limit contacts, 15 psi scale.  
Check Valve assembly–prevents product from backing up into gage.  
1/2 NPTM x 1/4 NPTF reducing bushing–for CKBO valve mounting.  
1/4 in. (6 mm) dia. 316 stainless steel tubing/ft. (probe).  
85-01-0405:  
85-01-0402:  
85-01-0403:  
86-03-0405:  
85-03-0407:  
1/4 in. (6 mm) dia. poly tubing/ft. (sensing line).  
1/4 x 1/4 male hex nipple kit–for connecting tubing line to tank top.  
1/4 x 1/4 male hex fitting kit–for connecting tubing or probe line to the tank top.  
Warranty  
A two year limited warranty on materials and workmanship is provided with this Murphy product.  
Details are available on request and are packed with each unit.  
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.  
Murphy de México, S.A. de C.V.  
Frank W. Murphy, Ltd.  
®
FRANK W.  
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje  
San Luis Potosí, S.L.P.; México 78384  
tel. +52-48-206264 fax +52-48-206336  
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.  
tel. +44 1722 410055 fax +44 1722 410088 tlx 477088  
MFR.  
Since 1939  
Frank W. Murphy Manufacturer  
P.O. Box 470248; Tulsa, Oklahoma 74147; USA  
tel. (918) 627-3550 fax (918) 664-6146  
Frank W. Murphy Pte., Ltd.  
Murphy Switch of California  
26 Siglap Drive; Republic of Singapore 456153  
tel. +65 241-3166 fax +65 241-8382  
Murphek Pty., Ltd.  
1620 Hume Highway; Campbellfield, Vic 3061; Australia  
tel. +61 3 9358-5555 fax +61 3 9358-5558  
P.O. Box 900788; Palmdale, California 93590; USA  
tel. (805) 272-4700 fax (805) 947-7570  
Frank W. Murphy France  
tel. +33 1 30 762626 fax +33 1 30 763989  
Frank W. Murphy Southern Division  
P.O. Box 1819; Rosenberg, Texas 77471; USA  
tel. (281) 342-0297 fax (281) 341-6006  
Printed in U.S.A.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  

Napoleon Grills Gas Grill PRESTIGE II 600 User Manual
NordicTrack Treadmill NTL15940 User Manual
Omega Thermostat PRG101 User Manual
Omron Computer Hardware C200HE User Manual
Onkyo CD Player DX 7555 User Manual
OPTI UPS Power Supply Standby UPS System User Manual
Panasonic All in One Printer 403171 User Manual
Panasonic Indoor Furnishings ET PKF100H User Manual
Parasound Portable Speaker PAL 380 User Manual
Patton electronic Server 29XX User Manual