Liebert Power Supply GXT2 10000RT208 User Manual

DISCONTINUED  
PRODUCT  
AC Power  
For Business-Critical Continuity™  
Liebert® GXT2-10000RT208™  
User Manual–10kVA, 60 Hz, 120/208/240V  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
1.0  
2.0  
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
INTRODUCTION AND SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
3.0  
3.1  
3.2  
3.3  
3.4  
3.5  
3.6  
3.7  
SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 5  
Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
DC to DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Static Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
4.0  
4.1  
4.2  
4.3  
MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
Main Frame and Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Internal Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Input/Output Terminal Blocks and Optional Output Distribution. . . . . . . . . . . . . . . . . . . . . 8  
5.0  
WHATS INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
6.0  
INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Install the Main Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
6.1.1 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately . . . . . . . . . . . . . . . . . . . . . . . . . 11  
External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
6.1  
6.2  
6.3  
Connect Input/Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
6.3.1 Distribution Module Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
6.3.2 Input & Output Terminal Block Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
6.3.3 Add an Output Power Distribution Module—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Install the Internal Battery Packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
6.4  
7.0  
7.1  
7.2  
INITIAL STARTUP AND ELECTRICAL CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18  
Hardwire Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Output Receptacle Distribution Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
8.0  
8.1  
8.2  
CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
Liebert GXT2-10000RT208 Configuration Program Features . . . . . . . . . . . . . . . . . . . . . . . 20  
What You Will Need. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
i
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.3  
8.4  
8.5  
Configuration Program—Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Establishing Communication Link with the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Configuration Program—Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
8.5.1 Read/Confirm UPS Configuration Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
8.5.2 Cancel Without Changing UPS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
8.5.3 Changing UPS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
8.5.4 On-Screen Reminders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
8.5.5 Programming Rejected When UPS is Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
UPS Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
8.6.1 Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
8.6.2 L-N Reverse Detection—120V UPS Models Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
8.6.3 Frequency Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Options Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
8.6  
8.7  
8.8  
8.9  
Options Tab Used With Earlier Liebert GXT2 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Battery Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
8.9.1 Low Battery Time Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
8.9.2 Auto Battery Test Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
8.9.3 Battery Cabinets Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
8.9.4 Auto Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
8.9.5 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
8.10 About Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
9.0  
9.1  
9.2  
9.3  
9.4  
9.5  
9.6  
9.7  
9.8  
9.9  
CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
ON/Alarm Silence/Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
OFF/Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
L1 & L2 Load Level Indicators (Two Rows of Indicators: 4 Green, 1 Amber). . . . . . . . . . . . 30  
Battery Level Indicators (5 Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Fault Indicator (Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Bypass Indicator (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
UPS ON Indicator (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Battery Indicator (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
AC Input Indicator (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
10.0 MODES OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
10.1 Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
10.2 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
10.3 Battery Recharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
ii  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32  
11.1 Communications Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
11.1.1 DB-9 Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
11.1.2 Communications—Liebert SNMP/OCWEBCARD SNMP Adapter. . . . . . . . . . . . . . . . . . . . . 33  
11.2 Pin 4 - Remote Shutdown on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
11.3 UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
11.4 Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
12.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35  
12.1 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
12.1.1 Internal Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
12.2 UPS Power Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
13.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38  
13.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
14.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44  
14.1 Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
iii  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
Figure 2  
Figure 3  
Figure 4  
Figure 5  
Figure 6  
Figure 7  
Figure 8  
Figure 9  
10 kVA Dual Inverter Liebert GXT2-10000RT208, front and rear views . . . . . . . . . . . . . . . . . . . . 7  
Internal battery pack and connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Hardwire terminal blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Optional output distribution modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Support base and spacers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
60A branch circuit breaker connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Hardwire terminal connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Control and indicator overlays, vertical and horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
REPO switch connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Figure 10 UPS back panel—control location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Figure 11 Power module replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
TABLES  
Table 1  
Table 2  
Table 3  
Table 4  
Table 5  
Table 6  
Table 7  
Table 8  
Table 9  
Electrical requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Fault indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Alarm conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Battery specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Optional output distribution specifications—PD-101. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Table 10 Optional output distribution specifications—PD-102. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Table 11 Optional output distribution specifications—PD-103. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Table 12 Replacement 10kVA power module specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Table 13 External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
iv  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
WARNING  
!
Opening or removing the cover may expose you to lethal voltages within this unit even when  
it is apparently not operating and the input wiring is disconnected from the electrical source.  
Observe all cautions and warnings in this manual. Failure to do so may result in serious  
injury or death. Refer all UPS and battery service to qualified service personnel. Do not  
attempt to service this product yourself. Never work alone.  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions. Read all safety, installation and operating  
instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the  
unit and in this manual. Follow all operating and user instructions. Individuals without previous  
training can install and operate this equipment.  
It is not intended for use with life support and other designated critical devices. Maximum load must  
not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If  
uncertain, consult your local dealer or Liebert representative.  
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230, 120/208,  
120/240 or 127/220 VAC, 50 Hz or 60 Hz supply. The factory default setting is 120/208 VAC, 60 Hz.  
Installation instructions and warning notices are located in this manual.  
This UPS is only for use with a four-wire input (L1, L2, N, G).  
This UPS MAY NOT be used with a three-wire, single-phase utility source (L1, N, G).  
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT2-10000RT208 Series complies with  
the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is sub-  
ject to the following two conditions: (1) This device may not cause harmful interference and (2) this  
device must accept any interference received, including interference that may cause undesired opera-  
tion. Operating this device in a residential area is likely to cause harmful interference that users  
must correct at their own expense.  
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F  
(0°C to +40°C). Install it in a clean environment, free from conductive contaminants, moisture, flam-  
mable liquids, gases and corrosive substances.  
This UPS contains no user serviceable parts except the internal battery pack. The Off/Bypass push  
button does not electrically isolate internal parts. Under no circumstances attempt to gain access  
internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to  
use the UPS if the front panel indications are not in accordance with these operating instructions or if  
the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the  
Liebert Worldwide Support Group.  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized personnel away from the batteries. PROPER DIS-  
POSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS  
FOR BATTERY DISPOSAL REQUIREMENTS.  
Never block or insert any object into the ventilation holes or other openings of the UPS.  
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from  
the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any other appli-  
ance using half-wave rectification.  
Storing magnetic media on top of the UPS may result in data loss or corruption.  
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol  
cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.  
1
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When replacing batteries, replace with the same Liebert authorized replacement battery kits. When  
replacing the power module, replace it with the same Liebert authorized replacement power module  
kit.  
CAUTION  
!
Do not dispose of battery or batteries in a fire. The battery may explode.  
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and  
eyes. It is toxic.  
CAUTION  
!
A battery can present a risk of electrical shock and high short circuit current. The following  
precautions should be observed when working on batteries:  
• Remove watches, rings and other metal objects.  
• Use tools with insulated handles.  
• Wear rubber gloves and boots.  
• Do not lay tools or metal parts on top of batteries.  
• Disconnect charging source prior to connecting or disconnecting battery terminals.  
• Determine if the battery is inadvertently grounded. If inadvertently grounded, remove  
source of ground. Contact with any part of a grounded battery can result in electrical shock.  
The likelihood of such shock will be reduced if such grounds are removed during installa-  
tion and maintenance (applicable to a UPS and a remote battery supply not having a  
grounded supply circuit).  
2
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary of Symbols  
1.0 GLOSSARY OF SYMBOLS  
Risk of electrical shock  
Indicates caution followed by important instructions  
!
AC input  
AC output  
Requests the user to consult the manual  
i
+
-
Indicates the unit contains a valve-regulated lead acid battery  
PbH2SO4  
Recycle  
R
DC voltage  
Equipment grounding conductor  
Bonded to ground  
AC voltage  
ON/Alarm Silence/Battery Test  
OFF/Bypass  
3
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction and System Description  
2.0 INTRODUCTION AND SYSTEM DESCRIPTION  
Congratulations on your choice of the Liebert GXT2-10000RT208 Uninterruptible Power Supply  
(UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.  
Upon generation, AC power is clean and stable. However, during transmission and distribution it is  
subject to voltage sags, spikes or complete power failure that may interrupt computer operations,  
cause data loss or even damage equipment. The Liebert GXT2-10000RT208 protects equipment from  
these disturbances.  
The Liebert GXT2-10000RT208 is a compact, on-line UPS. An on-line UPS continuously conditions  
and regulates its output voltage whether utility power is present or not. It supplies connected equip-  
ment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.  
For ease of use, the Liebert GXT2-10000RT208 features a light-emitting diode (LED) display to indi-  
cate both load percentage and battery capacity. It also provides self-diagnostic tests, a combination  
ON/Alarm Silence/Battery Test button, a Standby button, user configurable program and two levels  
of alarms when the unit is operating on battery.  
The Liebert GXT2-10000RT208 has an interface port for communication between the UPS and a net-  
work server or other computer systems. This port provides detailed operating information including  
voltages, currents and alarm status to the host system when used in conjunction with Liebert’s Multi-  
Link software. Liebert MultiLink software can also control UPS operation remotely.  
4
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Description  
3.0 SYSTEM DESCRIPTION  
Input  
Output  
Static  
Bypass  
L1  
L2  
L1  
L2  
TVSS &  
EMI/RFI  
Filters  
Rectifier  
/PFC  
N
Inverter  
N
DC to DC  
Converter  
Battery  
Charger  
Battery  
G
G
3.1  
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters  
These UPS components provide surge protection and filter both electromagnetic interference (EMI)  
and radio frequency interference (RFI). They minimize any surges or interference present in the util-  
ity line and keep the sensitive equipment protected.  
3.2  
Rectifier/Power Factor Correction (PFC) Circuit  
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to  
regulated DC power for use by the inverter while ensuring that the waveshape of the input current  
used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:  
• The utility power is used as efficiently as possible by the UPS.  
• The amount of distortion reflected on the utility is reduced.  
This results in cleaner power being available to other devices in the building not being protected by  
the Liebert GXT2-10000RT208.  
3.3  
3.4  
Inverter  
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and  
inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter  
receives energy from the battery through the DC to DC converter. In both modes of operation, the  
UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.  
Battery Charger  
The battery charger utilizes energy from the utility power and precisely regulates it to continuously  
float charge the batteries. The batteries are being charged whenever the Liebert GXT2-10000RT208  
is plugged in, even when the UPS is not turned on.  
5
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Description  
3.5  
3.6  
3.7  
DC to DC Converter  
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the opti-  
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-  
mum efficiency and voltage, thus increasing reliability.  
Battery  
The Liebert GXT2-10000RT208 utilizes valve-regulated, nonspillable, flame retardant, lead acid bat-  
teries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F  
(20°C to 25°C). Optional external battery cabinets are available to extend battery run times.  
Static Bypass  
The Liebert GXT2-10000RT208 provides an alternate path for utility power to the connected load in  
the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or UPS  
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is  
indicated by an audible alarm and illuminated amber Bypass indicator (other indicators may be illu-  
minated to indicate the diagnosed problem).  
The user may manually transfer the connected load from the inverter to bypass by pressing the  
Standby button once.  
NOTE  
The bypass power path does NOT protect the connected equipment from disturbances  
on the utility supply.  
6
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Major Components  
4.0 MAJOR COMPONENTS  
The Liebert GXT2-10000RT208 is composed of three major assemblies to provide easier handling,  
installation and versatility.  
4.1  
Main Frame and Electronics  
This 6U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the  
cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The  
UPS is shipped with standard hardwire terminal blocks for input and output connections.  
Figure 1 10 kVA Dual Inverter Liebert GXT2-10000RT208, front and rear views  
REAR VIEW  
Liebert  
IntelliSlot Port  
StatusIndicators  
and Controls  
®
FRONT VIEW  
Front Bezels, 3  
DB-9  
Communications  
Ports, 2  
External Battery  
Connectors  
Cooling Fan,  
1 of 3  
Output  
Circuit  
!
Breaker  
REPO  
n
t
UPSta  
Switch  
UPS/Bypass  
Breaker  
Hardwire  
Knockouts  
Input Circuit  
Breaker  
Battery Compartment  
(behind center and right bezels); Internal  
Battery Pack is shipped loose  
(see Section 4.2)  
4.2  
Internal Battery Pack  
The center front bezel may be pulled forward and removed to reveal the battery access plate. The  
cover plate can be removed by extracting the three screws at the top of the cover plate and lifting the  
plate off. The two internal battery packs are compact assemblies ready to slide into the battery com-  
partment after the front battery access plate has been removed. Electrical connection is made with  
the two slotted battery connectors.  
Figure 2 Internal battery pack and connector  
Battery connector  
on front of battery pack  
7
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Major Components  
4.3  
Input/Output Terminal Blocks and Optional Output Distribution  
The UPS is shipped with hardwire terminal blocks. For maximum flexibility, additional distribution  
options are available that provide the benefit of output receptacle convenience.  
Figure 3 Hardwire terminal blocks  
L1  
L1  
N
N
L2  
L2  
INPUT  
OUTPUT  
Figure 4 Optional output distribution modules  
PD-101  
Power Distribution Option  
with Internal Connector  
PD-102  
Power Distribution Option  
H-POTED  
PASS  
QC  
PASS  
-
O
-
O
O
O
O
O
O
O
PD-103  
Power Distribution Option  
8
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
What’s Included  
5.0 WHATS INCLUDED  
The Liebert GXT2-10000RT208 is shipped  
with these items:  
Box containing accessories is shipped in the UPS’  
battery compartment  
• UPS user manual  
• Vertical display overlay  
• Front bezels - 3  
• Top bezels - 3  
• Battery cover grille  
• Power Module cover grille  
• Battery pack brackets - 2  
• Liebert MultiLink software CD  
• Liebert MultiLink serial cable, 10 ft. (3m)  
• Rack mount handles  
• Support bases - 2  
• Mounting hardware  
• Configuration program compact disk  
• Ferrite beads - 2  
L1 L2  
BYPASS  
UPS ON  
!
Side bezels for rack  
Top bezels for tower  
BATTERY  
AC INPUT  
-
+
UPStation GXT  
Front bezels (2)  
Battery brackets  
Vertical  
display  
overlay  
Battery cover  
Support base  
with spacers  
Rack-mount  
handles  
Liebert MultiLink  
software CD  
Liebert  
MultiLink  
serial cable  
10 ft (3m)  
GXT2U™ Configuration Program  
For use with Liebert GXT2U model  
UPS systems.  
Version 1.6  
Ferrite  
For Windows XP, 2000NT, 98  
beads (2)  
Mounting hardware  
Configuration  
compact disk  
9
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.0 INSTALLATION AND CONFIGURATION  
This section includes instructions on how to install, configure and perform initial electrical checks of  
your UPS installation.  
DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until  
instructed to do so in 7.0 - Initial Startup and Electrical Checks.  
Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or  
Liebert representative.  
CAUTION  
!
The UPS is heavy (see 14.0 - Specifications). Take proper precautions when lifting or  
moving it.  
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place  
it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, cor-  
rosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front  
and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).  
NOTE  
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.  
6.1  
Install the Main Cabinet  
The Liebert GXT2-10000RT208 may be installed either as a tower unit or in a rack, depending on  
available space and use considerations. Determine the type of installation and follow the appropriate  
instructions in either 6.1.1 - Tower UPS Installation or 6.1.2 - Installing the Adjustable Rack-  
Mount Kit—Sold Separately.  
6.1.1 Tower UPS Installation  
When using the Liebert GXT2-10000RT208 in a tower configuration, use the included support base  
(shown below, left) to stabilize the UPS.  
If any external battery cabinets are added, they will include spacers to accommodate the additional  
cabinets (shown below, right).  
Figure 5 Support base and spacers  
End Bases  
Spacers  
Attach Bezels to Top  
When used as a tower, the Liebert GXT2-10000RT208 requires bezels attached to the top. To connect  
the bezels:  
1. Position the UPS so that the battery compartments are on the right side.  
2. Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of  
the UPS.  
10  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately  
This kit contains parts needed to mount several different models of UPS and external battery cabi-  
nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per  
pair of adjustable rack-mounting brackets is 200 pounds (91 kg).  
Liebert rack-mount bracket kit, part # RMKIT18-32, includes:  
Item  
Quantity  
Rear bracket members  
Front bracket members  
Inner bracket members  
M4 x 8mm machine screws  
M4 locking hex nuts  
2
2
2
16  
8
M5 x 16 mm machine screws  
Grease packet.  
12  
1
Tools needed for installation are:  
• one Phillips screwdriver  
• one 7mm wrench  
The adjustable rack-mounting brackets feature retaining latches to prevent users from inadvertently  
sliding the UPS or battery cabinet out of the rack.  
To install the rack mount brackets:  
Return  
flanges  
1. Unpack two (2) rack-mounting bracket assemblies and  
mounting hardware from this kit. Bracket assemblies are  
interchangeable between left-hand or right-hand.  
Retaining  
Latches  
Remove inner member of each bracket assembly as shown  
in at right by extending it to its outermost position,  
depressing the retaining latch and then pulling the inner  
member out of the bracket assembly.  
2. Determine the height position inside the rack enclosure  
where you want to mount the UPS or battery cabinet.  
Front  
members  
Inner  
members  
CAUTION  
!
Reduce the risk of tipping the rack enclosure by  
placing the UPS or battery cabinet in the lowest  
possible rack position.  
3. Install the rear member of each bracket assembly into rack  
enclosure with two (2) M5 screws provided in this kit (see  
figure at right). The return flanges on the bracket assembly  
fit to the inside of rack mounting rails. Insert screws loosely  
(finger-tight) into the top and bottom holes of the return  
flange on the rear member. Extend the bracket assembly by  
sliding the front member forward until it touches the front  
rack mounting rail. Insert two (2) M5 screws loosely (finger-  
tight) into top and bottom holes of the return flange on each  
front member. Make sure bracket assemblies are at the  
same mounting height on all four (4) rack mounting rails.  
M5 screws  
Front rack  
mounting rails  
Rear rack  
mounting  
rails  
M5 screws  
11  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
4. Get eight (8) M4 screws and eight (8) M4 nuts from the  
hardware pack in this kit. Each nut has a locking, nylon  
insert that begins gripping the screw when it is halfway  
tight. Make sure to tighten the nut and screw completely to  
ensure locking action. Fasten the rear member and the front  
member together using (4) screws and (4) nuts per bracket  
assembly as shown in at right. For maximum support, insert  
fasteners for each bracket assembly as far apart as possible,  
depending on rack depth, while still joining both members  
(see figures at right). Check alignment of bracket assemblies  
and TIGHTEN ALL SCREWS FROM Steps 2 and 3.  
5. Prepare the UPS or battery cabinet (the “equipment”) for  
rack mounting by following instructions in the equipment’s  
user manual. The equipment may require additional parts to  
be added or parts to be removed for rack mounting. After it is  
prepared, lay the equipment in rack-mounting position.  
Fasten the inner members from Step 1 to the equipment on  
both sides as shown at right with eight (8) M4 screws  
provided in the kit. Make sure retaining latch is near the rear  
of the equipment as shown (see figure at right).  
M4 nuts  
M4  
screws  
18" rack  
depth  
M4 nuts  
M4  
M4 nuts  
screws  
32" rack  
depth  
M4 nuts  
Retaining latch  
6. Open the grease packet provided in the kit. Apply a 1" long  
bead of grease at four (4) places inside the bottom, curved  
tracks of the front members as shown below right. The grease  
will allow the equipment to slide into the bracket assemblies  
more easily.  
M4 screws  
UPS or battery  
cabinet  
CAUTION  
!
Lifting equipment into the rack may be a two-person  
job, depending on the weight of the equipment. See  
equipment’s user manual.)  
6.  
Front  
7. Insert the equipment, with inner members attached in  
Step 5, into the bracket assemblies by inserting the top and  
bottom edges of the inner members into the top and bottom  
curved tracks of the front members and sliding the  
M4 screws  
Apply  
grease  
equipment into the rack (see figure at right). Ends of inner  
members are tapered to allow the rear of the equipment to be  
angled upward before insertion, if space allows.  
UPS or  
battery  
cabinet  
Then the rear, bottom edges of the inner members can be  
placed into the front edge of the bottom tracks and the front  
of the equipment can be tipped up so they are level to insert  
the top edges of the inner members before sliding the equip-  
ment into the rack (see figure below right). The equipment  
should move smoothly into the bracket assemblies. If it does  
not, recheck the alignment of the front and rear members  
from Steps 2 and 3.  
Apply  
grease  
(inside)  
8. Secure the front of the equipment to the rack mounting rails  
to prevent the equipment from sliding out of position. If  
securing holes are provided on the front of the equipment  
that align with the center holes on the return flange of the  
front members, you can use the four (4) extra M5 screws  
provided in the kit to secure the equipment. Otherwise, the  
equipment should be secured to the front of the rack with  
four (4) customer-supplied fasteners.  
... and push it  
into the rack.  
Insert the UPS into the front  
members, lift the front ...  
12  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.2  
External Battery Cabinet Installation  
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery  
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked  
beneath the UPS.  
The external battery cabinet frame and battery kits are shipped separately. This 4U cabinet arrives  
without internal batteries to lighten the cabinet for easier installation. Once the cabinet has been  
placed in its final floor or rack position, the internal batteries may be installed.  
CAUTION  
!
The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery  
cabinets can be used in rack-mount or tower configuration. Take proper precautions when  
lifting them.  
CAUTION  
!
Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the  
battery cabinet at this time. When installation is complete, you will be instructed to turn on  
the circuit breaker.  
When the external battery cabinet is received, it should be inspected for freight damage. Report dam-  
age to the carrier and your local dealer or Liebert representative.  
To install an external battery cabinet:  
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up.  
Optional rack-mount handles are shipped with the external battery cabinet and may be installed  
now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or  
Liebert representative for these additional options and any assistance needed.)  
2. Fasten the slides into position with the screws according to the instructions included with the  
slide rails.  
3. Use the enclosed support bases for the tower option to  
prevent the assembly from tipping over. One additional set  
of support base extensions ships with each external battery  
cabinet.  
4. Install the two battery packs and secure with the two  
brackets supplied.  
5. Connect the two slotted battery cables.  
Support Base With  
Spacers for External  
Battery Cabinets  
6. Attach the battery cover plate and the two front bezels.  
7. Connect the supplied external battery cabinet cables to  
either set of connectors on the rear of the external battery  
cabinet, then to the rear of the UPS.  
8. The UPS is now equipped with additional backup battery  
run time. For approximate battery run times, refer to Table  
6 - Battery run times in this manual.  
9. Do NOT turn on the battery cabinet circuit breaker at this  
time. Please complete the remainder of the installation first.  
NOTE  
UPS automatically detects the number of standard  
batteries that are connected. The configuration program  
may be used to set up the UPS for operation with non-  
standard external batteries. Instructions for using the  
configuration program follow in 8.0 - Configuration  
Program.  
UPS and  
External Battery Cabinet  
13  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.3  
Connect Input/Output Power  
The UPS has hardwire terminal blocks for input and output electrical connections. Optional output  
distribution modules permit connecting additional loads to the UPS. These optional plug-and-play  
distribution modules offer different types and numbers of connection plugs.  
WARNING  
!
The UPS must be completely powered down before beginning to make these electrical  
connections.  
6.3.1 Distribution Module Electrical Connections  
Electrical connections are made through a removable conduit box that attaches to the rear of the  
UPS.  
The installer must provide a 60A branch circuit breaker. The input circuit breaker and the output cir-  
cuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and  
the distribution box.  
The manual bypass switch passes utility power directly to the bypass switch from the input terminal  
block. The input circuit breaker does not disconnect power from the manual bypass switch.  
Figure 6 60A branch circuit breaker connection diagram  
UPS  
60A  
Input  
Circuit  
60A  
Output  
Circuit  
Breaker Breaker  
Output  
Terminal  
Block  
60A Maintenance  
Bypass Breaker  
Optional  
Output  
Distribution  
Plate  
Input  
Indicator Indicator  
Output  
Utility  
60A External  
Branch  
Input  
Circuit Breaker  
CAUTION  
!
!
A disconnect switch shall be provided by others for ac input circuit. To reduce the risk of fire,  
connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes  
rating in accordance with the National Electric Code, ANSI/NFPA 70.  
CAUTION  
A disconnect switch shall be provided by others for ac output circuit. To reduce the risk of fire,  
connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes  
rating in accordance with the National Electric Code, ANSI/NFPA 70.  
14  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.3.2 Input & Output Terminal Block Connections  
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not  
share the same conduit.  
Table 1  
Electrical requirements  
Recommended Wire  
Input Current Recommended (Max.) External (including ground wire)  
Maximum Wire  
Accepted by  
Terminal Block  
Terminal  
Tightening  
Torque  
Rating  
Overcurrent Protection  
(75°C copper wire)  
22 in-lb  
(2.48N-m)  
48A  
60A  
6 AWG  
4 AWG  
L2  
N
L1  
L2  
N
L1  
60A Max. Branch  
Overcurrent Protection  
OUTPUT  
INPUT  
6 AWG - USE COPPER WIRE ONLY - 22 in-lb (2.48N-m)- Strip 8mm  
L2  
N
L1  
L2  
N
L1  
0
0
Output to Load - See Note 1  
Input to UPS - See Note 2  
NOTE  
1. The installer must provide circuit breaker protection according to local codes. The utility  
disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain  
service space around the UPS or use flexible conduit.  
2. The installer must provide output distribution panels, circuit breaker protection or  
emergency disconnects according to local codes. Output circuits must not share a common  
conduit with any other wiring.  
For best performance, distribute all L-N loads evenly between L1 and L2.  
15  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.3.3 Add an Output Power Distribution Module—Optional  
To add an optional output distribution module to the Liebert GXT2 10000RT208:  
1. Remove the four screws securing the blank output distribution cover plate to the rear of the UPS.  
The cover is at top left corner in the tower configuration and at the bottom left in the rack  
configuration.  
2. Set the screws aside to attach output distribution module to UPS.  
3. Snap together the electrical connectors on the UPS and on the output distribution.  
4. Use the screws removed in Step 2 to attach the output distribution to the rear of the UPS.  
Screw holes  
Output Distribution  
to attach to UPS  
Cover Plate  
Hardwire  
Terminal  
Block  
Cover  
Screw holes  
to attach to UPS  
Electrical Connector  
snaps to connector  
inside UPS  
Optional Output  
Power Distribution  
Module  
(PD-101 shown)  
REAR VIEW  
Liebert GXT2 10000RT208  
16  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and Configuration  
6.4  
Install the Internal Battery Packs  
To facilitate shipping and installation, the Liebert GXT2-10000RT208 ships without the internal bat-  
tery packs installed. Once the UPS is installed in place, the internal battery packs must be installed.  
Controls and  
Indicators  
(horizontal overlay)  
Liebert  
!
UPStation GXT  
Mjfcfsu  
!
UPStation GXT  
Battery Compartment  
Battery  
Battery  
Bracket  
Front  
Bezel  
Battery  
Connector  
Battery  
Cover  
Front of Battery  
1. Unpack the two internal battery packs from their shipping container.  
2. Lift one battery pack from its packaging, holding it in the center of the pack.  
3. Align the battery pack so that the cable is at the top right closest to the power module in the  
frame.  
4. Slip the back of battery pack into the battery compartment and slide it in until the battery  
reaches the back of the UPS.  
5. Install the battery bracket on the front of the battery pack with two screws.  
6. Connect the two slotted connectors and tuck the wires in around the battery pack handles.  
7. Repeat for the second battery pack.  
8. Install the battery cover grille, tightening the three screws.  
9. For tower installation, place the vertical overlay over the controls and indicators (see Figure 8).  
10. Install the two front bezels.  
17  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Initial Startup and Electrical Checks  
7.0 INITIAL STARTUP AND ELECTRICAL CHECKS  
Initial Startup and the Configuration Program—The UPS ships with a default 120 VAC L-N  
setting. This is also the most robust setting in that it can operate with either input phase angle (120  
or 180 degrees). Perform initial system checks first. If the UPS configuration needs to be modified for  
your application, then go to the next section to review use of the configuration program. Some config-  
uration changes require that the UPS be in the OFF mode while powered from the utility. Therefore,  
the installer must confirm that the UPS input has been properly wired. After re-configuring your  
UPS, the UPS may be put into service with the intended loads.  
7.1  
Hardwire Input Connections  
WARNING  
!
Miswiring power to the input terminal block (L1-L2-N-G) or connecting to single-phase  
voltages (L-N-G only) may damage the UPS.  
1. Verify that the input and output circuit breakers are off. (To locate the circuit breakers, see  
Figure 1.)  
2. During initial system checks, disconnect all loads (open load disconnects).  
3. Inspect all wiring, cables and connection.  
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted  
into the sockets.  
5. Turn on the battery cabinet circuit breaker.  
6. Locate the UPS/Bypass circuit breaker on the rear of the UPS (see Figure 1).  
7. Unscrew the thumbscrew and slide the bracket to the right (toward the Input Lamp) until it is  
past the arm of the breaker.  
8. After the bracket has been moved to right, tighten the thumbscrew to secure the bracket in place.  
9. Turn the UPS/Bypass circuit breaker to Bypass (On).  
NOTE  
When the UPS is operating in manual bypass mode of operation, indicators A, C, E, Fault and  
Bypass will be illuminated. These indicators, on the front panel, signify the UPS is operating  
in Manual Bypass mode. There will be audible alarm as well.  
10. Turn on the branch circuit disconnect to apply voltage to the input terminal block (see 6.3.1 -  
Distribution Module Electrical Connections).  
11. Using a voltmeter, verify the expected L1-N, L2-N and L1-L2 voltages.  
a. The Input and Output lamps by the UPS/Bypass breaker will be illuminated.  
b. If the configuration program as been used to set the L-N voltage at 100, 110, or 115, then the  
input phase angle is required to be 180 degrees.  
c. If the configuration program as been used to set the L-N voltage to 127 VAC, then the input  
phase angle is required to be 120 degrees (leading or lagging).  
12. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power  
and close all access panels to the distribution box.  
13. Unscrew the thumbscrew and slide the bracket to the left (toward the Output Lamp) until it is  
past the arm of the breaker.  
14. After the bracket has been moved to left, tighten the thumbscrew with your hand or use a slotted  
screwdriver to secure the bracket in place.  
15. Turn the UPS/Bypass circuit breaker to the Inverter (OFF) position.  
NOTE  
When the UPS/Bypass circuit breaker is in the Inverter position, Indicators A, C, E, Fault and  
Bypass will not be illuminated and the audible alarm will clear.  
16. Reapply input power.  
17. Close the input circuit breaker located on the rear panel of the UPS. The green AC Input indicator  
should illuminate on the front panel.  
18  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Initial Startup and Electrical Checks  
18. Press the On button for one second. The bypass indicator will light for several seconds before the  
UPS On indicator turns on continuously. If the batteries are charged above 90% of capacity,  
automatic battery test will run for about 15 seconds.  
19. Close the Output circuit breaker on the rear of the UPS. The output terminal block will now be  
powered.  
20. Review all setting options provided by the configuration program. Some changes require the UPS  
to be Off. If this is the case, these should be programmed before powering the loads. The  
configuration program is described in 8.0 - Configuration Program.  
21. Connect all loads for normal operation.  
Figure 7 Hardwire terminal connections  
L1  
L1  
N
N
L2  
L2  
INPUT  
OUTPUT  
7.2  
Output Receptacle Distribution Options  
WARNING  
!
A qualified electrician should install the optional output distribution.  
1. Verify that the input feeder circuit breaker is off.  
2. Verify that the input and output circuit breakers are off.  
3. Verify the UPS is completely OFF.  
4. Remove the four screws holding the blank access plate from the rear of the UPS.  
5. Connect the four-position Anderson connector of the PD distribution into the mating connector  
inside the UPS.  
6. Using the same four screws, attach the PD distribution option to the rear of the UPS.  
7. Verify all distribution circuit breakers are in the ON position.  
8. Follow the initial startup procedures listed in 7.0 - Initial Startup and Electrical Checks.  
19  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.0 CONFIGURATION PROGRAM  
The final step of installation may require custom configuration of your UPS using the enclosed config-  
uration program. Some configuration settings may be changed only while the UPS is off. These should  
be set before the UPS is put into full time service powering the critical load.  
For most users operating with 120VAC L-N, the factory default settings will be adequate. This section  
illustrates the features available for modification, as well as the factory default setting.  
The factory default L-N setting is 120 VAC. When first powered by the AC input, the UPS will auto-  
sense the utility phase angle between L1 and L2, setting the UPS to operate as either a 120/208 VAC  
system (120 degrees, leading or lagging) or a 120/240 VAC system (180 degrees).  
If your application requires that the L1-N, L2-N voltages be set at 100, 110, 115 or 127VAC, the corre-  
sponding phase angle between L1 and L2 is restricted. The VAC settings of 100, 110 and 115 may  
work only with a phase angle of 180 degrees. A VAC setting of 127 VAC will work only with a phase  
angle of 120 degrees (leading or lagging).  
To confirm the phase angle of the utility input, measure the L1-N, L2-N and L1-L2 VAC of the utility  
input that is intended for the UPS. If the measured L1-L2 voltage is equal to the average L-N voltage  
times 2.0, then the phase angle is 180 degrees and the L-N VAC may be set at 100, 110, 115 or 120  
VAC. The nominal L1-L2 voltages for these four settings will be 200, 220, 230 or 240 VAC, respec-  
tively.  
If the measured L1-L2 voltage is equal to the average L-N voltage times 1.73, then the phase angle is  
120 degrees and the L-N VAC may be set at either 120 or 127 VAC. The nominal L1-L2 voltages for  
these two settings will be 208 or 220 VAC, respectively.  
Selecting an L-N nominal voltage that is not compatible with the L1-L2 phase angle detected by the  
UPS when AC input is applied will result in a fault alarm and the UPS will not operate from utility  
power.  
8.1  
Liebert GXT2-10000RT208 Configuration Program Features  
The configuration program enables the user to perform the following functions:  
• Select one of five input/output voltages to match voltages found around the world  
• Disable the line-neutral-reversed/missing-ground receptacle wiring alarm (120VAC, single-phase  
models only)  
• Select frequency converter operation with a fixed output frequency of 50 or 60Hz  
• Enable or disable the audible alarm  
• Set the Low Battery Warning alarm time from 2 to 30 minutes  
• Enable or disable the Auto-Battery test  
• Enable or disable the Auto Restart function  
• Set the Auto-Battery test to 7, 14, 21 or 28 days  
• Select the number of external battery cabinets connected to the UPS to adjust the remaining run-  
time calculations reported by the UPS Liebert software products  
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see 11.0 - Com-  
munications)  
8.2  
What You Will Need  
In addition to the UPS, you will need the configuration program CD (or installation file) and serial  
®
cable included in the UPS accessory box. A Windows 95 -or-later based operating system is also  
required to run the configuration program.  
!
T
X
        G
n
tio  
t
S
P
U
GXT2U™ Configuration Program  
For use with Liebert GXT2U model  
UPS systems.  
Version 1.6  
For Windows XP, 2000 NT, 98  
20  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.3  
Configuration Program—Installation  
An easy-to-use installation program streamlines the installation of the configuration program. If you  
have a previous version of this configuration program installed, Liebert recommends uninstalling it  
by using its Uninstall program before installing this updated version.  
1. Use the Windows Explorer to find and open the Lbt_gxt2-2.1.exe installation program.  
2. When the installation program begins, you see the presetup window, shown below.  
3. This will open the main installation screen. Click  
NEXT to continue with the installation screens.  
Liebert recommends using the default installation  
options, but users may modify the standard entries.  
The installation program will also install an uninstaller  
program along with the UPS configuration program.  
8.4  
Establishing Communication Link with the  
UPS  
Only use the serial communication cable supplied with  
the configuration program.  
NOTE  
If an accessory communication card has been installed in the Liebert IntelliSlot port in the  
UPS, the option card must be removed while using the configuration program.  
Use the serial communication cable to connect COM1 or COM2 of the host computer to the DB-9 com-  
munication port on the rear of the UPS. If the COM port of the host computer only has a DB-25 pin  
connector, a DB-25-to-DB-9 adapter must be added.  
The program may be used while the UPS is On to read settings, confirm the current settings and  
change some settings. The UPS must be Off and powered by the AC utility when using the configura-  
tion program to change some specified UPS settings.  
On-screen prompts will advise the user if the UPS must be turned Off for a configuration program  
operation.  
Select Lbt_gxt2.exe from the  
program group to start the con-  
figuration program. The pro-  
gram will search COM1 &  
COM2 for a properly connected  
UPS. When the UPS is found,  
the opening program window  
will display the UPS model.  
If the configuration program  
fails in its attempt to read data  
from a UPS, this error message  
will be displayed. The program  
must communicate with the  
UPS when it first opens, when a new tab is opened, and when the REFRESH, APPLY or OK buttons  
are pressed.  
21  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
If this message is displayed check the following items:  
• Verify that the serial communication cable is connected properly.  
• Verify that the COM port being used is designated COM1 or COM2.  
• Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode, or Off with AC power  
available at the input (AC Input LED on). In each case, the rear fan will be running.  
• Verify that the COM port is not in use by other UPS communication software (or non-UPS soft-  
ware). If Liebert MultiLink UPS software is installed on the computer, the Liebert MultiLink ser-  
vice must be stopped to free the COM port. Liebert MultiLink typically restarts automatically  
whenever the computer restarts.  
• The Liebert IntelliSlot port in the UPS CANNOT be in use by an internal, optional communica-  
tion card in the UPS card slot. Remove the option card.  
• The program is connected to a UPS that was not designed for this program.  
8.5  
Configuration Program—Operation  
8.5.1 Read/Confirm UPS Configuration Settings  
The UPS settings may be monitored using the configuration program while the UPS is operating in  
any mode. If the program is only used to read the present UPS settings, close the program using the  
CANCEL button.  
Settings on the UPS Tab or Options  
Tab may be changed only when the  
UPS is Off. Attempting to changes  
these variables when the UPS is run-  
ning will result in this error message.  
If this message is displayed and you  
do not wish to change any settings,  
close this error message and close the  
configuration program using the Can-  
cel button.  
8.5.2 Cancel Without Changing UPS Settings  
If you decide not to change the UPS after modifying the displayed settings, close the configuration  
program using the CANCEL button.  
8.5.3 Changing UPS Settings  
All UPS settings may be changed when the UPS is Off (with AC input power available). Settings on  
the UPS Tab and Options Tab may be changed only with the UPS Off. Settings on the Battery Tab  
may be changed with the UPS On or Off.  
If needed, turn the UPS Off to change configuration settings, press the UPS Off button twice within  
four seconds (hold the button one second each time). This will disconnect all power to the load.  
Changing any value, or selecting/deselecting any setting in the configuration window will not immedi-  
ately change the settings in the UPS. You may modify the displayed settings until you are satisfied  
with the new proposed changes. Settings displayed by the configuration program can always be  
restored to the existing values stored in the UPS by selecting the Refresh key.  
22  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.5.4 On-Screen Reminders  
As pending changes are selected, on-screen  
messages will remind the user if the UPS may  
be On, or must be Off, for the setting to be pro-  
grammed once the Apply or OK button is  
pressed. If there are no changes, these mes-  
sages are shaded.  
Values displayed will only be transmitted to  
the UPS when either the Apply or OK button is  
selected. The APPLY button sends the new set-  
tings to the UPS without closing the program. The OK button sends the new settings and closes the  
program.  
Whenever data is successfully transmitted to the  
UPS, this message will be displayed. If the UPS is  
already ON, you do not need to restart it.  
8.5.5 Programming Rejected When UPS is Off  
If the UPS appears to be Off but this error message  
is displayed when the APPLY Or OK button is  
selected to transmit new settings on the UPS tab or  
Options Tab, the UPS may be in an intermediate,  
standby condition.  
To Confirm That the UPS is Off, Repeat the Turn-Off Procedure  
While the UPS is in Normal Mode operation, press the Off button once to put the UPS into Bypass  
Mode. Once the UPS is in Bypass Mode operation, press and release the Off button two distinct times  
(for about a second each time) to turn off the UPS.  
Partial Rejection  
If the UPS is not OFF and changes from both the Battery Tab and the (UPS Tab or Options Tab) are  
selected, the UPS will only program the changes on the Battery Tab.  
23  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.6  
UPS Tab  
When the program starts, the following window will open displaying the UPS model along with the  
current UPS settings. This information can be refreshed at any time using the REFRESH button.  
These illustrations show the factory default settings for 120VAC UPS at the left, and output L-N volt-  
ages available to select at the right.  
8.6.1 Output Voltage  
The Output Voltage displayed is the nominal input/output voltage. This is not a voltmeter and will  
display the nominal voltage whether the UPS is On or Off. The drop down box will show the alternate  
L-N voltages available. Select the voltage that matches the nominal utility in your location.  
Output Voltage Selection Notes  
For the Liebert GXT2 dual inverter models, this sets the L1-N and the L2-N nominal voltage. The  
L1-L2 voltage depends upon the phase angle of the input utility and is auto-detected when power is  
first applied.  
For the Liebert GXT2 230V single inverter model, only those voltages supported by the UPS will be  
displayed.  
8.6.2 L-N Reverse Detection—120V UPS Models Only  
Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression, and surge  
suppression. The UPS checks the outlet when first plugged in. If the Line-Neutral is reversed or the  
ground is missing, the UPS will not start. If a problem is detected after the UPS is started, the UPS  
will continue to operate, but the AC INPUT LED will flash. In some unique applications the user may  
wish to disable this alarm. Except for special situations, improperly wired receptacles should be  
immediately repaired before the UPS is put into service. Click on the box to remove the check mark  
and disable this alarm.  
24  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.6.3 Frequency Selection  
The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the  
model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will Auto-sense the  
utility frequency when first plugged in and set the nominal frequency to match. Therefore, for all nor-  
mal use the Auto Sense button should be selected.  
Some special applications require that the UPS be used as a frequency converter. Frequency Con-  
verter 50Hz mode will provide 50Hz UPS output from 60Hz commercial power. Frequency converter  
60Hz mode will provide 50Hz UPS output from 60Hz commercial power.  
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is  
unable to power the load, the alternate bypass to utility power will not be available and power will be  
removed from any load.  
8.7  
Options Tab  
Computer users may choose to use versatile  
computer shutdown software that communi-  
cates with the UPS via a serial communication  
cable. The Options Tab should not be used to  
modify the UPS functions for such applica-  
tions.  
For some industrial applications and special  
computer applications, the UPS may be moni-  
tored and controlled using external voltages  
and relay contact signals. The Options tab  
expands the UPS versatility for such applica-  
tions.  
Refer to your UPS manual for a description of  
the nine-pin communication connector on the  
rear of the UPS. Pin 6 of the nine-pin commu-  
nication connector is used for “Any Mode Shut-  
down” of the UPS output. This control input  
may be used in special applications to disable  
the UPS output power—both Inverter and  
Bypass.  
The Options Tab allows the behavior of the  
Any Mode Shutdown feature to be modified.  
When the program opens, or the Refresh but-  
ton is pressed, the UPS setting is read by the  
configuration program and displayed.  
Factory Default Setting Illustrated for  
700-3000VA Models—This Options Tab illus-  
tration shows the available function defini-  
tions using pin 6 and the factory default settings.  
WARNING  
!
Auto-Enable Output  
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS  
output can turn on automatically and without warning if the Pin 6 connection is changed.  
WARNING  
!
Pin 6 Logic  
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to  
install a normally closed connection between Pins 5 & 6. This connection must be maintained  
to use the UPS or to use the configuration program again, including the ability to change the  
UPS setting back to the default setting using the configuration program via a serial  
communication link.  
25  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.8  
Options Tab Used With Earlier Liebert GXT2 Models  
This version of the configuration program will accompany Liebert GXT2 UPS models that support  
new programming features accessible using the Options Tab.  
If Version 1.6 (or later) is used with an earlier Liebert GXT2 model (with an earlier UPS firmware  
version), the Any Mode Shutdown features cannot be changed.  
If the configuration program is used with an earlier 700-3000VA UPS model (with an earlier UPS  
firmware version) that does not support the modification of these settings, the Options Tab will dis-  
play a reminder of the factory default settings, as shown. These cannot be changed.  
26  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.9  
Battery Tab  
Factory default settings illustrated.  
The boxes above show options available in  
the drop-down menus.  
The Liebert GXT2-10000RT208 automatically  
detects external battery  
cabinets when they are connected. Use the  
Battery Cabinets Number selection box to  
select non-Liebert battery cabinets when used  
with the UPS.  
8.9.1 Low Battery Time Warning  
The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated  
if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30  
minutes.  
8.9.2 Auto Battery Test Time  
The UPS performs an automated battery test periodically, if enabled. The user may also set the UPS  
to test at intervals of 7, 14, 21, and 28 days.  
8.9.3 Battery Cabinets Number  
If additional batteries are attached to the UPS, accurate battery run time estimates are possible if the  
battery number and type of batteries are entered here. The new UPS models are designed to operate  
with up to four external battery packs or four long run time (LRT) battery packs (not currently avail-  
able).  
8.9.4 Auto Battery Test  
In some applications it may be preferable to disable the automated, periodic battery test. Click on the  
box to remove the check mark and disable the periodic battery test.  
8.9.5 Auto Restart  
The UPS will provide computer grade power during power outages. If input power is unavailable for  
an extended time, the UPS will shut down when batteries are depleted, or a shutdown signal is sent  
by the computer operating system to limit battery depletion (serial data or contact closure). If Auto  
Restart is enabled (check mark in box), the UPS will restart when input power is restored. If the UPS  
turns off power to the load for any other reason, manual restart is required (See 8.7 - Options Tab  
for exceptions). Click on the box to remove the check mark and disable Auto Restart.  
27  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration Program  
8.10 About Tab  
Version number may be confirmed using the About Tab.  
28  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls and Indicators  
9.0 CONTROLS AND INDICATORS  
Figure 8 Control and indicator overlays, vertical and horizontal  
All indicators lit for illustrative purposes.  
L1 L2  
BYPASS  
UPS ON  
!
Vertical overlay  
for tower  
BATTERY  
installation  
AC INPUT  
- +  
UPStation GXT  
Horizontal overlay for rack mounting  
9.1  
ON/Alarm Silence/Battery Test Button  
This button controls output power to connected load(s) and has three functions:  
• ON  
• Alarm Silence  
• Manual Battery Test  
ON - Pressing this button will start up the UPS in order to provide conditioned and  
protected power.  
Alarm Silence - To silence alarms, press this button for at least one Second. After the  
alarm is silenced, the Liebert GXT2-10000RT208 will reactivate the alarm system to  
alert of additional problems.  
NOTE  
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.  
Manual Battery Test - To initiate a manual battery test, press the ON/Alarm Silence/Battery Test  
button for at least one second while operating from utility power with no alarm conditions present.  
• If only three of the five battery indicators illuminate, allow the UPS to recharge the batteries for  
24 hours.  
• After 24 hours, retest the batteries.  
• After the batteries have been retested, if only three of the five battery indicators illuminate, con-  
tact your local dealer, Liebert representative or Liebert Worldwide Support Group.  
9.2  
OFF/Bypass Button  
This button controls output power to connected load(s) and has dual functions: OFF  
and Bypass.  
CAUTION  
!
Pressing the OFF/Bypass button once will cause the load to be  
transferred to bypass power. Pressing the OFF/Bypass button a second  
time within 4 seconds will result in loss of power to the output  
receptacles and connected loads. Perform all necessary shutdown  
procedures on connected loads before pressing this button twice.  
Pressing the OFF/Bypass button twice within 4 seconds shuts off power to the output receptacles and  
connected loads, but the UPS’s circuits remain live, charging the unit’s battery.  
29  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls and Indicators  
9.3  
9.4  
L1 & L2 Load Level Indicators (Two Rows of Indicators: 4 Green, 1 Amber)  
The Load Level indicators display the approximate electrical load placed upon both output legs of the  
UPS at all times. Each indicator represents an approximate 25 percent increase in load. For optimum  
utilization of the UPS, distribute L-N loads to approximately balance the loads on L1 and L2. The last  
LED is amber and indicates the load exceeds 100% of the UPS’s capacity.  
Battery Level Indicators (5 Green)  
The Battery Level indicators display approximate battery capacity at all times. Each indicator repre-  
sents an approximate 20 percent increase in battery capacity.  
The Liebert GXT2-10000RT208 is equipped with automatic and remote battery test features. The  
automatic test occurs every 14 days (this option is user-configurable) if utility has not been inter-  
rupted. Should the battery fail this test, the red Fault indicator along with the A and C diagnostic  
indicators will illuminate and an alarm will sound (refer to 13.0 - Troubleshooting). The remote  
test feature functions with Liebert MultiLink 3 software and can remotely initiate the battery test.  
9.5  
9.6  
9.7  
Fault Indicator (Red)  
The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the Battery  
Level indicators may be illuminated (refer to 13.0 - Troubleshooting section).  
Bypass Indicator (Amber)  
The Bypass indicator is illuminated when the UPS is operating from bypass power. An alarm will  
sound indicating the UPS detected a problem or the manual bypass function has been activated.  
UPS ON Indicator (Green)  
The UPS ON indicator is illuminated when the UPS inverter is operating and supplying power to  
your connected loads.  
9.8  
9.9  
Battery Indicator (Amber)  
The battery indicator is illuminated when the UPS is operating on battery.  
AC Input Indicator (Green)  
The AC Input indicator is illuminated when utility power is available and within the input specifica-  
tions.  
30  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Modes of Operation  
10.0 MODES OF OPERATION  
10.1 Normal Mode Operation  
During normal operation, utility power provides energy to  
the UPS. The filters, power factor correction circuit and the  
inverter process this power to provide computer grade  
power to connected loads. The UPS maintains the batteries  
in a fully charged state. The four green Load Level indica-  
tors display an approximate level of load in 25% increments.  
If the UPS becomes loaded beyond full rating, the fifth  
(amber) indicator will illuminate and the UPS will sound an  
audible alarm. The display template indicates the percent-  
age of load (see example at right) on the UPS output.  
Normal Mode Operation  
Batteries at 100% charge  
L1 Load at 10%, L2 Load at 90%  
10.2 Battery Mode Operation  
Battery mode occurs in event of an extreme input voltage  
condition or complete utility failure. The battery system  
supplies power through the DC to DC converter to the  
inverter to generate power for the connected load. During  
battery mode an alarm sounds every 10 seconds. This will  
change to two beeps every 5 seconds when the battery runs  
low (approximately 2 minutes remaining, but this is user  
configurable). The AC Input indicator will extinguish and  
the Battery indicator will illuminate to warn that a utility  
problem has occurred. Each Battery Level indicator repre-  
sents a 20% capacity level. As capacity decreases, fewer  
indicators remain illuminated. Refer to 13.0 - Trouble-  
shooting. For approximate battery run times, refer to  
Table 6 - Battery run times. These times are approximate  
Battery Mode Operation  
Batteries at 30% charge  
L1 Load at 60%, L2 Load at 60%  
based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off  
non-essential pieces of equipment (such as idle computers and monitors) or add the optional external  
battery cabinet.  
CAUTION  
!
Turning OFF the UPS while in battery mode will result in loss of output power.  
10.3 Battery Recharge Operation  
Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger  
begins recharging.  
31  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications  
11.0 COMMUNICATIONS  
11.1 Communications Interface Port  
The Liebert GXT2-10000RT208 UPS has a standard DB-9 serial port female connector located on the  
rear of the UPS unit. Several signals are provided on this port and are assigned as follows:  
Table 2  
DB-9 pin assignment  
DB-9 Assignment Description  
Pin  
1
2
3
4
5
6
7
8
9
Low Battery (open collector)  
UPS TxD (typical RS-232 levels)  
UPS RxD (typical RS-232 levels)  
Remote Shutdown (5-12VDC, 10-24mA max; battery operation)  
Common  
Remote Shutdown (short to pin 5); all modes of operation  
Low Battery (open emitter)  
Utility Fail (open emitter)  
Utility Fail (open collector)  
Pin Assignment  
Collector to Emitter*  
Open  
Collector  
6
7
8
9
(+)  
(-)  
330 Ohms  
Open  
Emitter  
321  
4
5
* Maximum voltage and current on pins 1, 7, 8 and 9 are 60VDC and 10.0 mA  
11.1.1 DB-9 Interface Port  
Using the following directions to attach the smaller enclosed ferrite  
bead clamp to the communication cable as shown at right:  
1. Open the ferrite bead.  
2. Place the communication cable inside the ferrite bead groove.  
3. Position the ferrite bead as close as possible to the end of the cable  
that connects to the DB-9 connector of the UPS.  
4. Close the ferrite bead so that the ferrite bead’s case snaps closed  
with the cable routed through the ferrite bead’s case.  
Run cable  
through ferrite  
bead case  
32  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications  
11.1.2 Communications—Liebert SNMP/OCWEBCARD SNMP Adapter  
Attach the larger enclosed ferrite bead clamp to the network  
cable, see illustration at right, using the following directions:  
1. Open the ferrite bead.  
2. Place the network cable inside the ferrite bead groove.  
3. Wrap the cable once around the ferrite bead.  
4. Position the ferrite cable as close as possible to the end of  
the cable that connects to the UPS.  
5. Close the ferrite bead so that the ferrite bead’s case snaps  
Wrap network  
cable around  
ferrite bead  
closed with the cable routed through the ferrite bead’s case.  
11.2 Pin 4 - Remote Shutdown on Battery  
1. This pin is functional only when the UPS is in battery  
mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin.  
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using  
Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is  
used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal  
a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown  
signal for 1.5 seconds, the command cannot be canceled.  
3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown signal  
will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will  
shut down.  
4. If the utility returns during the 2-minute timer countdown, the shutdown timer will continue  
until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10  
seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and  
restart the server.  
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled  
or disabled.  
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown  
delay.  
11.3 UPS Intelligent Communications  
®
The Liebert GXT2-10000RT208 is equipped with a Liebert IntelliSlot port to provide advanced com-  
munication and monitoring options.  
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or  
server in the event of an extended power failure.  
Liebert MultiLink can also be configured for use without the serial cable when the Liebert IntelliSlot  
SNMP/OCWEBCARD is installed in the UPS. Additionally, Liebert MultiLink can be configured to  
coordinate shutdown across the network with other computers running Liebert MultiLink when you  
purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot SNMP/  
OCWEBCARD and Liebert MultiLink License Kits, visit our Web site (www.liebert.com) or contact  
your local dealer or Liebert representative.  
Several option cards are available for use in the Liebert IntelliSlot port of the Liebert  
GXT2-10000RT208. The Liebert Intellislot SNMP/OCWEBCARD provides SNMP and Web-based  
monitoring and control of the UPS across the network.  
The Liebert IntelliSlot MultiPort 4 Card allows you to install Liebert MultiLink software on four com-  
puters and coordinate shutdown in the event of a power failure.  
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications  
and delivers support for built-in shutdown for AS/400 systems.  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables  
should be segregated and run separate from all other power cables, where applicable.  
33  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communications  
11.4 Remote Emergency Power Off  
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS  
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply  
with national and local wiring codes and regulations.  
Figure 9 REPO switch connections  
REPO Connection  
REPO  
as shipped  
REPO connections  
for normally open  
switch system  
REPO connections  
for normally closed  
switch system (fail-safe)  
1
2
3
4
1
2
3
4
1
2
3
4
Key to REPO switch connections  
1. 24 VDC  
2. Sense  
3. Sense  
4. Common  
NOTE  
Remove the factory-installed jumper to use the REPO function.  
CAUTION  
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should  
be segregated and run separately from power cables.  
34  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
12.0 MAINTENANCE  
The Liebert GXT2-10000RT208 requires very little maintenance. The batteries are valve-regulated,  
non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The  
UPS continuously charges the batteries when connected to the utility supply.  
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours  
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri-  
odically will permanently degrade battery capacity.  
The Liebert GXT2-10000RT208 is designed to allow the user to safely replace the internal batteries.  
Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to  
obtain the appropriate replacement battery kit part number and pricing.  
12.1 Battery Replacement  
CAUTION  
!
A battery can present a risk of electrical shock and high short circuit current. The following  
precautions should be observed before replacing the batteries:  
• Remove rings, watches and other metal objects.  
• Use a Phillips (crosshead) screwdriver with insulated grips.  
• Do not lay tools or other metal objects on top of the batteries.  
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact  
your local dealer or Liebert representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
12.1.1 Internal Battery Replacement Procedures  
Both battery packs should be replaced at the same time.  
1. Gently remove the front center plastic bezel  
cover from the UPS by pulling forward.  
UPS  
Mjfcfsu  
2. Loosen the three screws on the front battery  
cover grille. Lay the battery cover grille aside for  
reassembly.  
!
U
P
S
t
a
t
i
o
n
G
X
T
3. Remove the battery brackets at the bottom front  
of the battery pack.  
Battery  
4. Grasp each battery pack assembly individually  
and pull each out of the front of the UPS. Be  
prepared to support the weight of the battery as  
it is withdrawn.  
Battery  
Cover  
5. Unpack the new battery assemblies taking care  
not to destroy the packing. Compare new and  
old battery assemblies to make sure they are the  
same. If so, proceed with the next step. If they  
are different, STOP and contact your local  
Front Bezels  
dealer, Liebert representative or the Liebert Worldwide Support Group.  
6. Line up and slide in the new replacement battery packs.  
7. Reinstall the brackets on the front of the battery pack.  
8. Reconnect the slotted battery cable connectors.  
9. Reattach the front battery door, tightening the two screws.  
10. Reattach the front plastic bezel to the UPS.  
NOTE  
These are hot-swappable replacement batteries. However, caution should be exercised because  
during this procedure the load is unprotected from disturbances and power outages.  
35  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
12.2 UPS Power Module Replacement  
CAUTION  
!
The UPS must be switched to manual bypass before personnel begin to replace the power  
module.  
NOTE  
During the procedure, the connected load will not be protected from power disturbances, such  
as spikes, sags and failure.  
To remove the UPS power module without shutting off power to the connected load:  
1. Place the UPS on internal bypass. This may be done by any of the three following methods:  
a. Press the Off button on the front panel one time.  
b. Slide the bracket away from the manual bypass switch on the rear of the UPS—this requires  
loosening the captive screw and sliding the bracket away from the manual bypass switch.  
c. Remove the front grille covering the power module.  
2. Move the manual bypass breaker on the rear of the UPS to the bypass position—this requires  
loosening the captive screw and sliding the bracket away from the manual bypass switch (see  
Figure 10).  
3. Open the input circuit breaker on the rear of the UPS (see Figure 10).  
4. Open the output circuit breaker on the rear of the UPS (see Figure 10).  
5. Remove the top two front plastic bezels by pulling them forward.  
6. Remove the power module cover grille and the battery cover grille with the screws securing them  
to the frame.  
7. Disconnect the slotted battery connectors from the internal battery packs.  
8. If additional external batteries are used, disconnect the two external battery connectors.  
9. Slide the power module out the front, supporting its weight as it is withdrawn.  
10. Insert the replacement UPS power module.  
11. Reconnect the slotted internal battery connectors.  
12. Reconnect the external battery cables, if used.  
13. Reattach both front cover grilles.  
14. Reattach the front plastic bezels.  
15. Close the input circuit breaker on the rear of the UPS (see Figure 10).  
16. Close the output circuit breaker on the rear of the UPS (see Figure 10).  
17. Move the bypass breaker on the rear of the UPS back to the INVERTER position (see Figure 10).  
18. Slide the bracket back next to the manual bypass breaker and tighten its thumbscrew.  
19. Press the On button on the front panel one time to return the UPS to Normal Mode operation.  
36  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Figure 10 UPS back panel—control location  
Output  
Input  
Bypass  
Inverter  
Output Breaker 60A 250V~/T  
Input Breaker 60A 250V~/T  
Figure 11 Power module replacement  
Power module  
pulled out of UPS  
(Retaining grilles  
removed for clarity)  
37  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
13.0 TROUBLESHOOTING  
The information below indicates various symptoms a user may encounter in the event the Liebert  
GXT2-10000RT208 develops a problem. Use this information to determine whether external factors  
caused the problem and how to remedy the situation.  
1. The Fault indicator will illuminate, indicating the UPS has detected a problem.  
2. An alarm will sound, alerting that the UPS requires attention.  
3. One or more additional Load Level/Battery Level indicators will be illuminated to provide a  
diagnostic aid to the operator, as described below:  
A
B
C
D
E
Fault  
indicator  
Battery  
indicators  
Load Level  
indicators  
AC Input  
indicator  
Bypass  
indicator  
Battery indicator  
UPS ON indicator  
Table 3  
Indicator status  
All indicators  
Fault indicators  
Diagnosis/Audible alarm  
On bypass due to output overload; beep every half-second  
On bypass due to overtemperature condition  
Indicator A  
Indicator B  
On bypass due to DC bus overvoltage  
Indicator C  
On bypass due to control power supply failure  
On bypass due to PFC failure  
Indicator D  
Indicator E  
On bypass due to inverter failure  
Indicators A&B  
Indicators A&C  
Indicators A&D  
Indicators B&C  
Inverter-to-Inverter communications failure; half-second beep every 1 second  
UPS failed battery test; 2-second beep every 60 seconds  
L1 to L2 phase angle unacceptable  
REPO is currently activated, UPS output cannot be started by any method  
UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power  
is restored, press the OFF button twice within four seconds (to clear the alarm), then  
press the ON button to start UPS (Auto-restart is NOT possible).  
Indicators B&D  
Indicators C&E  
Indicators D&E  
UPS shutdown due to command from communications (RS232 or SNMP); no beep  
UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds  
AC Input indicator On &  
Indicators A&C&E  
On bypass due to the power module cover plate being removed or the slide bracket  
moved from Manual Bypass switch  
AC Input indicator On &  
Battery indicator Flashing  
AC input has been applied to start UPS but the batteries are either missing or below  
the minimal level to allow the UPS to start; continuous audible alarm  
Bypass voltage is present, but is disabled for use because the voltage or frequency is  
outside acceptable limits  
Bypass indicator Flashing  
38  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger  
is operational, or for a maximum of 5 minutes while the battery charger is not operational.  
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World-  
wide Support Group. Please have the UPS model number and serial number available at the time of  
your inquiry.  
All audible alarms can be silenced, with the exception of Low Battery, Bypass Reminder and Missing  
Batteries at Startup alarms. Once silenced, the alarm will not sound again until a new alarm condi-  
tion is present.  
Table 4  
Alarm conditions  
Condition  
Alarm  
One short beep every 10 seconds; more than 2 minutes of run time  
remaining  
Battery Mode (utility failure)  
Two short beeps every 5 seconds; less than 2 minutes of run time  
remaining  
Low Battery  
On Bypass Reminder  
A one-second beep every 2 minutes  
On Internal Bypass  
(to notify user to rotate manual  
maintenance switch to Bypass  
position)  
A one-second beep every 2 seconds  
Output Overload (bypass)  
Overtemperature (bypass)  
DC Bus Overvoltage (bypass)  
One short beep every half second  
A one-second, or two-second, beep every 4 seconds  
A one-second, or two-second, beep every 4 seconds  
Control Power Supply Failure (bypass) A one-second, or two-second, beep every 4 seconds  
PFC Failure (bypass)  
Inverter Failure  
A one-second, or two-second, beep every 4 seconds  
A one-second, or two-second, beep every 4 seconds  
Inverter-to-Inverter Communication  
Failure  
A one-half second beep every 1 second  
Battery Test Failure  
REPO Activated  
A two-second beep every 1 minute  
A one-quarter second beep every half second  
39  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Table 5  
Troubleshooting guide  
Problem  
Cause  
Solution  
Ensure the UPS is OFF. Disconnect all loads and ensure  
nothing is lodged in output receptacles.  
Ensure the loads are not defective or shorted internally.  
UPS fails to start when the  
ON button is pressed.  
UPS is short-circuited or  
overloaded.  
UPS is operating in Battery Mode, make certain UPS is  
securely plugged into the wall receptacle.  
UPS not plugged in.  
UPS input protection fuse  
has blown/opened.  
UPS is operating in Battery Mode. Save data and close  
applications. Replace UPS input fuse, then restart UPS.  
Battery indicator is  
illuminated.  
UPS is operating in Battery Mode. Save data and close  
applications. Ensure utility supply voltage is within  
acceptable limits for UPS.  
Utility voltage out of UPS  
input range.  
Batteries are not fully  
charged.  
Keep UPS plugged in continuously at least 24 hours to  
recharge batteries.  
UPS has reduced battery  
time.  
UPS is overloaded.  
Check load level display and reduce the load on the UPS.  
Replace batteries. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group for  
replacement battery kit.  
Batteries may not be able to  
hold a full charge due to age.  
Fault and Bypass indicators  
and all Load Level indicators  
are illuminated.  
Check load level display and remove non-essential loads.  
Recalculate the load and reduce number of loads  
connected to UPS. Check load equipment for faults.  
UPS overloaded or load  
equipment is faulty.  
Fault and Bypass indicators  
and diagnostic indicator C are  
illuminated.  
UPS control power supply  
fault.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault and Bypass indicators  
and diagnostic indicator D are  
illuminated.  
UPS PFC (Power Factor  
Correction Circuit) fault.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Ensure the UPS is not overloaded, ventilation openings  
are not blocked and room ambient temperature is not  
excessive.  
Wait 30 minutes to allow UPS to cool, then restart UPS.  
If UPS does not restart, contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
UPS internal fan has a  
problem or UPS shutdown  
due to temperature  
condition. Load is on bypass  
power.  
Fault and Bypass indicators  
and diagnostic indicator A are  
illuminated.  
Fault and Bypass indicators  
and diagnostic indicator B are  
illuminated.  
UPS internal DC bus  
overvoltage.  
UPS requires service. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault and Bypass indicators  
and diagnostic indicator E are  
illuminated.  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
UPS inverter fault.  
Fault and Bypass indicators  
and diagnostic indicators A  
and B are illuminated.  
Inverter-to-Inverter  
Communications Failure  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
Fault indicator and diagnostic  
indicators A and C are  
illuminated.  
Replace batteries. Contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
UPS failed the battery test.  
Only phase angles of 120, 180 or 240 degrees  
(±10 degrees) are permitted. These must be compatible  
with the selections in the configuration program.  
Or the phase angle has changed while the UPS was  
running. The phase angle is detected at startup and  
cannot be changed to a different power source while  
running.  
Turn the UPS Off and wait until the fans stop. Apply input  
AC power. The UPS will reprogram the phase angle to  
match the utility, if the utility is 120, 180 or 240 degrees  
between L1 and L2. If this does not resolve the issue,  
contact a qualified electrician to verify the site wiring.  
Fault indicator and diagnostic  
indicators A and D are  
illuminated.  
L1 to L2 phase angle  
unacceptable.  
40  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Table 5  
Troubleshooting guide (continued)  
Problem  
Cause  
Solution  
Fault indicator and diagnostic  
indicators B and C are  
illuminated.  
UPS has shut down due to the REPO (Remote Emergency  
Power Off). The output cannot be started by any method.  
REPO is currently activated.  
UPS is OFF due to previous REPO (REPO is no longer  
activated). Once utility power is restored, press the OFF  
button twice within four seconds (to clear the alarm), then  
Fault indicator and diagnostic  
indicators B and D are  
illuminated.  
UPS output is OFF from a  
previous REPO command.  
REPO is no longer activated. press the ON button to start UPS (Auto-restart is NOT  
possible).  
Your UPS has received a signal or command from the  
Fault indicator and diagnostic  
indicators C and E are  
illuminated.  
UPS shutdown due to a  
command from the  
communications port(s).  
attached computer. If this was inadvertent, ensure the  
communication cable used is correct for your system. For  
assistance, contact your local dealer, Liebert  
representative or the Liebert Worldwide Support Group.  
Fault indicator and diagnostic  
indicators D and E are  
illuminated.  
UPS requires service. Contact your local dealer, Liebert  
Representative or the Liebert Worldwide Support Group.  
UPS charger fault.  
On Internal Bypass to notify  
user to move manual  
maintenance bypass switch  
to Bypass position.  
AC Input indicator is On &  
diagnostic indicators A, C and  
E are illuminated.  
Move manual bypass switch to the Bypass position, then  
follow the instructions for replacing the UPS power module  
(see 12.2 - UPS Power Module Replacement).  
Check battery connections, completely power down and  
restart UPS.  
NOTE: If the battery circuit opens while the UPS is  
running, it will be detected when the next battery test is  
performed.  
AC Input indicator is On &  
Battery indicator is flashing.  
Battery source is not  
available; continuous horn.  
The AC input powers the PFC input and serves as the  
bypass source. If the AC is present but the voltage or  
frequency exceeds the acceptable range for safe  
operation with a load, the bypass will be disabled and this  
indicator will flash, indicating that the bypass is  
unavailable.  
Bypass voltage is present,  
but is disabled for use  
because the voltage or  
frequency is outside  
acceptable limits.  
Bypass indicator is flashing.  
41  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Using the configuration program, the user may specify the number of GXT2-288VBATT external bat-  
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.  
Table 6 shows estimated run times at different loads.  
Table 6  
Battery run times  
Battery/External  
Cabinets  
10000VA Run Time  
in Minutes  
Battery/External  
Cabinets  
10000VA Run Time  
in Minutes  
Load%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
Load%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
107  
52  
31  
22  
16  
13  
10  
9
7
548  
284  
217  
151  
107  
86  
66  
55  
47  
40  
Internal Battery  
+ 1 LRT Battery  
Pack  
Internal Battery  
6
251  
118  
74  
52  
39  
32  
26  
22  
19  
1030  
538  
332  
269  
231  
195  
158  
125  
109  
96  
1473  
821  
520  
382  
289  
264  
238  
215  
189  
165  
1973  
1053  
672  
515  
406  
304  
280  
263  
243  
224  
Internal Battery  
+ 1 External Battery  
Cabinet  
Internal Battery  
+ 2 LRT Battery  
Pack  
17  
333  
216  
118  
85  
66  
53  
44  
38  
32  
28  
494  
265  
191  
119  
92  
75  
62  
54  
47  
Internal Battery  
+ 2 External Battery  
Cabinets  
Internal Battery  
+ 3 LRT Battery  
Pack  
Internal Battery  
+ 3 External Battery  
Cabinets  
Internal Battery  
+ 4 LRT  
41  
590  
295  
236  
178  
119  
98  
82  
71  
61  
54  
Internal Battery  
+ 4 External Battery  
Cabinets  
42  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
13.1 Auto-Learning Battery Run Times  
As batteries age, the estimated run times may become less accurate. The Liebert GXT2-10000RT208  
is programmed to “learn” from a full battery discharge and modify the estimated run time for the  
measured battery capacity. This can improve accuracy and compensate for aging batteries or batter-  
ies that operate at different ambient temperatures.  
The UPS will update the anticipated run time calculation only under certain conditions.  
• The UPS must have a steady load that is greater than 20%.  
• The UPS must be at 100% charge at the start of a battery discharge.  
• The battery discharge must continue uninterrupted until the batteries reach their end-of-dis-  
charge voltage.  
If all conditions are not met, the run time calculation will not be modified.  
If the configuration program is used to change the number of battery cabinets, then the values in  
Table 6 will be restored. This will override any value that is automatically learned.  
43  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
14.0 SPECIFICATIONS  
Table 7  
UPS specifications  
Model Number  
Liebert GXT2-10000RT208  
8000W/8660VA at 127/220 (120 or 240 degrees only)  
8000W/8660VA at 120/208 (120 or 240 degrees)  
8000W/10000VA at 120/240 (180 degrees)  
8000W/10000VA at 115/230 (180 degrees only)  
7200W/9000VA at 110/220 (180 degrees only)  
6400W/8000VA at 100/200 (180 degrees only)  
Model Rating  
DIMENSIONS, RACK MOUNT, W x D x H  
Unit, in. (mm)  
16.93 x 25.98 x 10.5 (430 x 660 x 267); 6U  
22.44 x 33.86 x 15.75 (570 x 860 x 400)  
Shipping, in. (mm)  
WEIGHT lb (kg)  
Unit  
109 (49.3)  
118 (53.6)  
Shipping  
INPUT AC PARAMETERS  
Nominal Operating Frequency  
Factory Default VAC  
50 or 60 Hz (Factory Default = 60)  
120/208 VAC at 120 degrees  
L1-L2 Factory Default Input Phase  
Angle  
120 degrees  
120, 180, 240 degrees, Auto-sensing on application of AC  
(Restrictions for L-N voltages other than 120 VAC)  
Allowable Input Phase Angle  
Factory Default L1-N, L2-N VAC  
User Configurable L1-N, L2-N VAC  
120 VAC nominal  
100/110/115/120/127 VAC (May be modified using configuration program)  
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)  
100% - 91% loading  
90% - 71% loading  
70% - 51% loading  
50% - 31% loading  
30% - 0% loading  
100 VAC - 140 VAC  
90 VAC - 140 VAC  
80 VAC - 140 VAC  
70 VAC - 140 VAC  
60 VAC - 140 VAC  
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)  
100% - 91% loading  
90% - 71% loading  
90 VAC - 140 VAC  
80 VAC - 140 VAC  
70 VAC - 140 VAC  
60 VAC - 140 VAC  
150 VAC  
70% - 51% loading  
50% - 0% loading  
L1-N, L2-N Max. Allowable VAC  
Input Frequency w/o Battery  
Operation  
40 - 70 Hz  
Input Power Connection  
OUTPUT AC PARAMETERS  
Factory Default VAC  
Hardwire Terminal Block 3W + G (L-L-N-G)  
120/208 VAC @ 120 degrees  
120 degrees  
L1-L2 Factory Default  
Output Phase Angle  
Allowable Output Phase Angle  
Factory Default L1-N, L2-N VAC  
User Configurable L1-N, L2-N VAC  
120, 180, 240 degrees Auto-sensing on initial application of input AC  
120 VAC nominal  
100/110/115/120/127 VAC, ±2%  
Hardwire Terminal Block 3W + G (L-L-N-G);  
also see 7.2 - Output Receptacle Distribution Options  
Output Connections  
Frequency  
Waveform  
50 Hz or 60 Hz, Nominal  
Sinewave  
Main Mode Overload  
130% for 60 seconds; 200% for 5 seconds with transfer to bypass.  
44  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table 7  
UPS specifications (continued)  
Model Number  
Liebert GXT2-10000RT208  
Bypass Protection Limits  
Disable Bypass Operation  
If input voltage exceeds ±15% of the nominal voltage  
Re-enable Bypass Operation  
Disable Bypass Operation  
If input voltage returns to within ±10% of nominal output voltage  
When the input frequency prevents synchronous operation  
ENVIRONMENTAL  
Operating Temp  
Storage Temp  
+32°F to +104°F (0°C to +40°C)  
+5°F to +122°F (-15°C to +50°C)  
0% to 95%, non-condensing  
Relative Humidity  
Operating Elevation  
Storage Elevation  
Audible Noise  
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating  
50,000 ft. (15,000 m) maximum  
<55 dBA, at 1 meter  
AGENCY  
Safety  
RFI/EMI  
UL 1778, c-UL Listed (Suitable for computer room applications)  
FCC Part 15, Subpart B, Class A  
Surge Immunity  
Transportation  
IEEE/ANSI C62.41 Category A & B  
ISTA Procedure 1A  
Table 8  
Battery specifications  
Model Number  
GXT2-288RTBKIT—Two Required  
DIMENSIONS, W x D x H  
Shipping, in. (mm)  
WEIGHT lb (kg)  
Unit  
11.02 x 24.02 x 15.35 (280 x 610 x 390)  
78.1 (35.5)  
83.6 (38)  
Shipping  
Type  
Valve-regulated, non-spillable, flame retardant, lead acid  
(2) x 12 x 12V x 9.0 AH  
Quantity x V x Rating  
Battery Manufacturer / Part #  
Back-Up Time  
Yuasa / REW 45-12 FR  
See Table 6 - Battery run times  
6 Hours to 90% capacity after full discharge into 100% load  
Recharge Time  
Table 9  
Optional output distribution specifications—PD-101  
Model Number  
PD-101  
DIMENSIONS, W x D x H  
Shipping, in. (mm)  
WEIGHT lb (kg)  
Unit  
8.86 x 10.43 x 7.87 (225 x 265 x 200)  
3.8 (1.7)  
5.1 (2.3)  
Shipping  
ELECTRICAL SPECIFICATIONS  
Amp Rating  
60 Amps  
Input Power Connections  
Output Power Connection  
L1-L2-G  
Internal Anderson connectors  
(2) L6-30R on a 300mm cord  
L1-N-G  
(4) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers  
(4) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers  
L2-N-G  
45  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table 10 Optional output distribution specifications—PD-102  
Model Number  
DIMENSIONS, W x D x H  
Shipping, in. (mm)  
WEIGHT lb (kg)  
Unit  
PD-102  
8.86 x 10.43 x 7.87 (225 x 265 x 200)  
4.6 (2.1)  
6.0 (2.7)  
Shipping  
ELECTRICAL SPECIFICATIONS  
Amp Rating  
60 Amps  
Input Power Connections  
Output Power Connection  
L1-L2-G  
Internal Anderson connectors  
(4) L6-20R on a 300mm cord  
L1-N-G  
L2-N-G  
(2) 5-15/20R, T-type receptacles with (1) 20A circuit breaker  
(2) 5-15/20R, T-type receptacles with (1) 20A circuit breaker  
Table 11  
Optional output distribution specifications—PD-103  
Model Number  
PD-103  
DIMENSIONS, W x D x H  
Shipping, in. (mm)  
WEIGHT lb (kg)  
Unit  
8.86 x 10.43 x 7.87 (225 x 265 x 200)  
5.5 (2.5)  
6.7 (3.0)  
Shipping  
ELECTRICAL SPECIFICATIONS  
Amp Rating  
60 Amps  
Input Power Connections  
Output Power Connection  
L1-L2-G  
Internal Anderson connectors  
(4) L6-30R on a 300mm cord  
L1-N-G  
L2-N-G  
(2) 5-15/20R, T-type receptacles with (1) 20A circuit breaker  
(2) 5-15/20R, T-type receptacles with (1) 20A circuit breaker  
Table 12 Replacement 10kVA power module specifications  
Model Number  
GXT2-10KPWR208  
DIMENSIONS in (mm)  
Shipping W x D x H 22.04 x 28.14 x 9.88 (560 x 715 x 251)  
WEIGHT lb (kg)  
Shipping 59.5 (27)  
ENVIRONMENTAL  
Storage Temp -5°F to +122°F (-15°C to +50°C)  
Relative Humidity 0% to 95%, non-condensing  
Storage Elevation 50,000 ft. (15,000m) maximum  
46  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table 13 External battery cabinet specifications  
Model Number  
Used w/ UPS Model  
DIMENSIONS, Rack Mount, W x D x H  
Unit (with bezel), in (mm)  
Shipping, in (mm)  
GXT2-288RTVBATT  
Liebert GXT2-10000RT208  
16.93 x 25.98 x 7 (430 x 660 x 178); 4U  
22.64 x 33.46 x 12.40 (575 x 850 x 315)  
WEIGHT lb (kg)  
Unit  
41.6 (18.9)  
50.6 (23)  
Shipping  
BATTERY PARAMETERS  
Type  
Qty x V x Rating  
Valve-regulated, non-spillable, flame retardant, lead acid  
(2) x 12 x 12V x 9.0 AH  
Battery Manufacturer / Part #  
Backup Time  
Yuasa / REW 45-12 FR  
See Table 6 - Battery run times  
ENVIRONMENTAL  
Operating Temp  
+32°F to +104°F (0°C to +40°C)  
+5°F to +122°F (-15°C to +50°C)  
Storage Temp  
Relative Humidity  
Operating Elevation  
Storage Elevation  
AGENCY  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating  
50,000 ft. (15,000m) maximum  
Safety UL 1778, c-UL Listed (suitable for computer room applications)  
RFI/EMI  
FCC Part 15, Subpart B, Class A  
ISTA Procedure 1A  
Transportation  
14.1 Product Warranty Registration  
To register for warranty protection:  
• Visit the Quick Links section of our Website at:  
• Click on Product Warranty Registration and fill in the form.  
If you have any questions, please contact us at:  
US: 800-222-5877  
Outside the US: 614-841-6755  
Contact Liebert Global Services at:  
US: 800-LIEBERT (800-543-2378)  
47  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
48  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISCONTINUED  
PRODUCT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2007 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-23444_REV03_03-08  
Emerson Network Power.  
EmersonNetworkPower.com  
The global leader in enabling Business-Critical Continuity.  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Precision Cooling  
Services  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2007 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KTI Networks Switch KPOE 800 1P User Manual
Kuppersbusch USA Oven EEB 65008 User Manual
LG Electronics Double Oven LDG3011ST User Manual
Mace Security Camera CAM 77 User Manual
Magnavox Flat Panel Television 19ME601B User Manual
Magnavox Portable CD Player AZ 8140 User Manual
Meade Telescope StarNavigator User Manual
Memorex CD Player MD6126CP User Manual
Mercury Marine Outboard Motor 90 850416009 User Manual
MGE UPS Systems Personal Computer Network Shutdown Module V3 User Manual