Precision Cooling
For Business-Critical Continuity™
Liebert Mini-Mate2™ 1 To 8 Tons
Overhead Precision Cooling And Humidity Control
Download from Www.Somanuals.com. All Manuals Search And Download.
Liebert Monitoring Solutions:
When You Need To Know
You will find a full-range of monitoring and control systems,
communications modules designed to interface Liebert equipment with
a variety of building management systems, plus stand-alone monitoring,
control and leak detection devices.
Low Total Cost Of Ownership:
High-Efficiency Compressor. The rotary or scroll
compressors are both energy-efficient and rugged,
to ensure continuous operation.
Local And Remote
Advanced Monitoring
Liebert SiteScan® Web offers
comprehensive, centralized
monitoring, control, data analysis
and reporting for a full-range
of computer support systems. It
provides web-based site monitoring,
alarm management and
Monitoring Panels
Free-Cooling Option. A second cooling coil allows
the system to take advantage of colder outdoor
temperatures and bypass compressor operation.
These units provide basic monitoring
and control for a single unit or small
groups of equipment either at the
equipment location or to a remote site.
Building
Cooling
Tower
Products include:
Liebert Universal Monitor
Liebert Controllers
trending/analysis for critical sites.
Free-Cooling Option
Products include:
Liebert SiteScan Web Software
Free
Cooling
Coil
Leak Detection
Liebert Liqui-tect® leak detection
systems alert facility personnel to
the presence of leaking fluids before
serious damage results. They provide
quick sensing and accurate reporting
of leaks below the floor, above the
ceiling or at the perimeter of a room.
Water Temperature Sensor
Water/
Glycol
Condenser
Field-supplied piping
Products include:
When water temperature goes below 45˚F, cooling switches over to
Free-Cooling operation. A separate chilled water source can also be
used with Air-Cooled system. Note: Special cupro-nickel free-cooling
coil must be specified when applied to open cooling tower.
Liebert Liqui-tect Panel
Two Channel Direct Read
Leak Detection
Liebert Zone Leak Detection Kits
Liebert Point Leak Detection Sensor
For further information,
Third Party Monitoring
System Connectivity
The use of open protocols allows
you to interface Liebert units and
monitoring systems with other types
and brands of control equipment
including BMS, NMS, SCADA and fire
alarm systems.
Fundamental Monitoring
Liebert Nform™ is
a centralized monitoring and
communications software package
that combines full-scale monitoring
with cost-effective deployment
through the use of the existing
network infrastructure.
Protocols supported:
Products include:
Modbus
Liebert Nform Software
BACnet
Liebert IntelliSlot Web/485
Card ADPT
SNMP
Download from Www.Somanuals.com. All Manuals Search And Download.
3
The Right Size To Fit Your Space And Application
With more than 10,000 possible configurations, there is a LiebertMini-Mate2 system
available to fit the needs of many room cooling or spot cooling requirements.
Liebert Mini-Mate2™ Product
Features Include:
A Variety Of Options Help You Meet
Numerous Applications:
Available in 1,1.5, 2, 3, 5 & 8 ton capacities
(3-stage cooling on 8-ton)
Grille (1-1.5 tons) or Plenum (2-3 tons) that fits 2’x4’
ceiling grid for direct supply & return air distribution
Fan speed and/or blower options to handle supply air
ductwork with higher external static pressures
Filter box or duct kits to connect to ducted sites
Hot water reheat to utilize building hot water
for energy savings
Self-contained or split systems allow for fitting
systems with a variety of architectures
Reliable refrigeration components featuring rotary
or scroll compressors with copper tube aluminum
fin coils provide high-efficiency
Units are fully charged with refrigerant and come
standard with quick-connect fittings to reduce
installation time.
Stainless steel electric reheat and/or canister
humidifier for humidity control
High-pressure chilled water systems
Available in air-cooled, water-cooled, glycol-cooled
or chilled-water configurations
Easy-to-use menu-driven microprocessor control
Optional room sensors available
Single-point power connection kit to facilitate close
coupled evaporator & condensing unit wiring
Multiple air-cooled heat rejection solutions: indoor
ducted, outdoor, (standard ambient, high ambient
and Quiet-Line)
Hot gas bypass for low load applications
2-way or 3-way water regulating valves rated for
standard or high-pressure applications
Unit disconnect, smoke sensor, and/or high-temp
sensor options
3-Stage Cooling (8 ton system only)
100%
Improved Load Tracking
Site monitoring and communication devices
to meet monitoring needs
R407C refrigerant
72%
48%
Stage 1
Stage 2
Stage 3
A unique compressor staging system utilizes independent 3-ton and
5-ton circuits to provide better control of room conditions. The unit
microprocessor continuously monitors recent cooling operation,
and selects the most economical cooling stage to satisfy demand.
1-1.5 Ton with grille
Microprocessor Control Features:
User-friendly wall-mount display
Provides precise control of all unit functions
Temperature Control
Humidity Control
Alarm Indication
Programming
Auto Restart
Download from Www.Somanuals.com. All Manuals Search And Download.
4
5-Ton Ducted
Liebert Mini-Mate2
Capacity (Tons)
Product Option Availability
1
1.5
2
3
5
•
•
8
Chilled Water (rated @ 300 psi static pressure)
Chilled Water (rated @ 400 psi static pressure)
Self-Contained Air-Cooled
Self-Contained Water/Glycol-Cooled
Split System Air-Cooled w/Centrifugal Indoor Condensing Unit
Split System Air-Cooled w/Outdoor High Ambient Prop Fan Condensing Unit
Split System Air-Cooled w/Outdoor Prop Fan Condensing Unit
Split System Air-Cooled w/Outdoor Quiet-Line Prop Fan Condensing Unit
Split System Water/Glycol-Cooled (2- or 3-way Valve, 150 or 350 psi)
50 & 60 Hz voltages
Canister Humidifier
Chilled Water w/High Close-Off Pressure Valve
Direct-Drive Motor/Two-Speed
Filter Clog Alarm
High Temp Sensor (Firestat)
Free-Cooling Coil (Cu or CuNi Versions)
Hot Gas Reheat (self-contained systems only)
Hot Water Reheat
Internal Disconnect Switch
SCR Reheat
Smoke Sensor
Stainless Steel Electric Reheat
R407C
High External Static Option
15’ or 30’ Refrigerant Line Sets (R22 only)
Condensate Pump Kit
Duct Kit
Filter Box
Remote Sensors
Single Point Power Kit
Supply & Return Grille/Plenum
Liebert Controller
Liebert Liqui-tect 410 Point Detection Leak Detection Sensor
Liebert LT460-K Zone Leak Detection Kits
Liebert IntelliSlot Web/485 Card ADPT
Liebert ENV-DO Environmental Interface Card
Liebert AC8 Controller
Liebert RCM4 Four-Point Dry Contact Monitor
Liebert Universal Monitor Remote Dry Contact Monitor
Liebert Site Scan Monitoring
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1 Some option/accessory
combinations are not available.
Single-Point Power Kit
High Static Pressure Option
8-ton Configuration Shown
2-3 Ton Shown
2 For further information,
Blower
Evaporator
Motor
(or chilled water)
HEPA Filter Box
High Static
Blower Box
Evaporator
Evaporator Supply
¬
¬
¬
¬
Evaporator Return
Condenser Return
Condenser Supply
Condensing Unit
Field installed single-point power kit
simplifies connection and installation.
Download from Www.Somanuals.com. All Manuals Search And Download.
5
1 And 1-1/2 Ton Systems
Air-Cooled
Water/Glycol
Chilled-Water
Expansion Tank
Drycooler
Pump
Self-Contained Air-Cooled with Grille
Self-Contained Glycol System with Grille
Chilled-Water with Grille
Expansion Tank
Drycooler
Pump
Self-Contained Glycol System Ducted
Chilled-Water Ducted
Self-Contained Air-Cooled Ducted
Optional Filter Box, Duct Connection Available
Optional Filter Box, Duct Connection Available
Optional Filter Box, Duct Connection Available
Cooling Tower
Prop Fan
Condensing
Unit
Evaporator
Split System with Grille
Self-Contained Water-Cooled with Grille
Evaporator Supply
Evaporator Return
Condenser Return
Condenser Supply
¬
Cooling Tower
Prop Fan
Condensing
Unit
¬
Evaporator
¬
¬
Split System Ducted
Self-Contained Water-Cooled Ducted
Optional Filter Box, Duct Connection Available
Optional Filter Box, Duct Connection Available
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Specifications
1 And 1-1/2 Ton Systems
60 HZ
50 HZ
AIR COOLED SYSTEM
with Outdoor Condensing Unit
Split System
with Centrifugal Condensing Unit
with Outdoor Condensing Unit
with Centrifugal Condensing Unit
Self-Contained
Self-Contained
Split System
1 Ton
MMD12E
PFH014A
1.5 Tons
MMD18E
PFH020A
1 Ton
MMD12A
MM2CF
1.5 Tons
MMD18A
MM2CF
1 Ton
MMD11E
PFH013A
1.5 Tons
MMD17E
PFH019A
1 Ton
MMD11A
MM2CF
1.5 Tons
MMD17A
MM2CF
Evaporator
Condensing Unit
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (27.7) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 11,600 (3.4) 15,500 (4.5) 11,300 (3.3) 15,300 (4.5) 11,700 (3.4) 16,000 (4.7) 11,300 (3.3) 15,900 (4.7)
Total 13,000 (3.8) 18,400 (5.4) 12,300 (3.6) 18,000 (5.3) 13,300 (3.9) 19,800 (5.8) 12,400 (3.6) 19,500 (5.7)
Sensible 11,200 (3.3) 15,000 (4.4) 10,900 (3.2) 14,900 (4.4) 11,300 (3.3) 15,600 (4.6) 10,900 (3.2) 15,500 (4.5)
Total 12,400 (3.6) 17,700 (5.2) 11,800 (3.5) 17,300 (5.1) 12,700 (3.7) 19,000 (5.6) 11,900 (3.5) 18,700 (5.5)
Sensible 10,900 (3.2) 14,800 (4.3) 10,600 (3.1) 14,600 (4.3) 11,000 (3.2) 15,300 (4.5) 10,700 (3.1) 15,200 (4.5)
14,100 (4.1) 19,800 (5.8) 13,300 (3.9) 19,300 (5.7) 14,400 (4.2) 21,200 (4.2) 13,400 (3.9) 20,800 (6.1)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7) DB
50% RH
75 F (23.9 C) DB
50% RH
Total
Sensible 10,500 (3.1) 13,800 (4.0) 10,200 (3.0) 13,700 (4.0) 10,600 (3.1) 14,400 (4.2) 10,200 (3.0) 14,200 (4.2)
Total 12,900 (3.8) 18,000 (5.3) 12,300 (3.6) 17,700 (5.2) 13,200 (3.9) 19,200 (5.6) 12,400 (3.6) 18,900 (5.5)
Sensible 10,100 (3.0) 13,500 (4.0) 9,900 (2.9) 13,400 (3.9) 10,200 (3.0) 14,000 (4.1) 9,900 (2.9) 13,900 (4.1)
14,000 (4.1) 19,300 (5.7) 13,300 (3.9) 18,800 (5.5) 14,300 (4.2) 20,600 (6.0) 13,400 (3.9) 20,300 (5.9)
72 F (22.2) DB
50% RH
Total
Sensible
12,300 (3.6) 17,200 (5.0) 11,800 (3.5) 16,900 (5.0) 12,600 (3.7) 18,400 (5.4) 11,900 (3.5) 18,200 (5.3)
9,900 (2.9) 13,300 (3.9) 9,700 (2.8) 13,100 (3.8) 10,000 (2.9) 13,800 (4.0) 9,700 (2.8) 14,200 (4.2)
60 HZ
50 HZ
WATER COOLED
GLYCOL COOLED
WATER COOLED
GLYCOL COOLED
Self-Contained
Self-Contained
Self-Contained
Self-Contained
1 Ton
MMD14W
1.5 Tons
MMD20W
1 Ton
MMD14W
1.5 Tons
MMD20W
1 Ton
MMD13W
1.5 Tons
MMD19W
1 Ton
MMD13W
1.5 Tons
MMD19W
Evaporator
Net Capacity Data*BTUH (kW) High Fan Speed
80F (26.7) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 12,500 (3.7) 16,600 (4.9) 12,000 (3.5) 15,800 (4.6) 12,400 (3.6) 15,500 (4.5) 12,000 (3.5) 16,400 (4.8)
Total 13,900 (4.1) 20,500 (6.0) 12,800 (3.8) 18,600 (5.4) 13,900 (4.1) 21,300 (6.2) 12,900 (3.8) 20,000 (5.9)
Sensible 12,000 (3.5) 16,100 (4.7) 11,600 (3.4) 15,400 (4.5) 12,000 (3.5) 15,100 (4.4) 11,600 (3.4) 15,900 (4.7)
Total 13,300 (3.9) 19,600 (5.7) 12,300 (3.6) 17,900 (5.2) 13,300 (3.9) 20,400 (5.6) 12,400 (3.6) 19,200 (5.6)
Sensible 11,800 (3.5) 15,800 (4.6) 11,400 (3.3) 15,100 (4.4) 11,800 (3.5) 14,900 (4.4) 11,400 (3.3) 15,700 (4.6)
15,000 (4.4) 22,000 (6.4) 13,700 (4.0) 19,900 (5.8) 15,000 (4.4) 23,000 (6.7) 13,900 (4.1) 21,300 (6.2)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 11,000 (3.2) 14,800 (4.3) 10,500 (3.1) 13,900 (4.1) 11,000 (3.2) 17,300 (5.1) 10,600 (3.1) 14,600 (4.3)
Total 13,500 (4.0) 19,700 (5.8) 12,500 (3.7) 17,800 (5.2) 13,500 (4.0) 22,200 (6.5) 12,600 (3.7) 19,300 (5.7)
Sensible 10,700 (3.1) 14,400 (4.2) 10,200 (3.0) 13,600 (4.0) 10,600 (3.1) 16,900 (5.0) 10,300 (3.0) 14,300 (4.2)
Total 12,900 (3.8) 18,900 (5.5) 12,000 (3.5) 17,100 (5.0) 12,900 (3.8) 21,200 (6.2) 12,100 (3.5) 18,600 (5.4)
Sensible 10,400 (3.0) 14,200 (4.2) 10,000 (2.9) 13,400 (3.9) 10,400 (3.0) 16,500 (4.8) 10,100 (3.0) 14,000 (4.1)
14,600 (4.3) 21,100 (6.2) 13,400 (3.9) 18,900 (5.5) 14,500 (4.2) 23,900 (7.0) 13,500 (4.0) 20,700 (6.1)
60 HZ
50 HZ
CHILLED WATER
Self-Contained
1.5 Tons
Self-Contained
1.5 Tons
Evaporator
MMD23C
MMD22C
Capacity Data BTUH (kW) High Fan Speed
80 F (26.7) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
21,800 (6.4)
16,000 (4.7)
14,300 (4.2)
13,100 (3.8)
11,000 (3.2)
11,000 (3.2)
21,800 (6.4)
16,000 (4.7)
14,300 (4.2)
13,100 (3.8)
11,000 (3.2)
11,000 (3.2)
Sensible
Capacity Data BTUH (kW) Low Fan Speed
80 F (26.7) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
17,100 (5.2)
12,800 (3.7)
11,300 (3.1)
10,300 (3.0)
8,500 (2.5)
8,500 (2.5)
17,100 (5.2)
12,800 (3.7)
11,300 (3.1)
10,300 (3.0)
8,500 (2.5)
8,500 (2.5)
Sensible
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001
Download from Www.Somanuals.com. All Manuals Search And Download.
7
2 And 3 Ton Systems
Air-Cooled
Water/Glycol
Chilled-Water
Utilizes Split System Evaporator
Utilizes Split System Evaporator
Centrifugal Fan
Condensing Unit
Expansion Tank
Water/Glycol
Condensing Unit
Evaporator
Evaporator
Drycooler
Pump
Remote Water/Glycol-Condensing Unit
Supply & Return Air Plenum
Chilled-Water
Remote Air-Cooled Condensing Unit
Supply & Return Air Plenum
Supply & Return Plenum
Centrifugal Fan
Condensing Unit
Expansion Tank
Water/Glycol
Evaporator
Condensing Unit
Evaporator
Drycooler
Pump
Remote Water/Glycol-Condensing Unit
Supply & Return Air Ducted
Optional Filter Box, Duct Connection Available
Chilled-Water
Supply & Return Air Ducted
Optional Filter Box, Duct Connection Available
Remote Air-Cooled Condensing Unit
Supply & Return Air Ducted
Optional Filter Box, Duct Connection Available
Cooling Tower
Water/Glycol
Note: All split systems may be
close-coupled or configured with
condensing unit located remotely
from the evaporator.
Prop Fan
Condensing Unit
Evaporator
Condensing Unit
Evaporator
Pump
Outdoor Prop Fan Condensing Unit
Supply & Return Air Plenum
Remote Water/Glycol-Condensing Unit
Supply & Return Air Plenum
Cooling Tower
Prop Fan
Evaporator Supply
Evaporator Return
Condenser Return
Condenser Supply
Condensing Unit
¬
Water/Glycol
Condensing Unit
Evaporator
Evaporator
¬
¬
¬
Pump
Outdoor Prop Fan Condensing Unit
Supply & Return Air Ducted
Optional Filter Box, Duct Connection Available
Remote Water/Glycol-Condensing Unit
Supply & Return Air Ducted
Optional Filter Box, Duct Connection Available
Download from Www.Somanuals.com. All Manuals Search And Download.
8
Specifications
2 And 3 Ton Split Systems
60 HZ
50 HZ
AIR COOLED SYSTEM
with Outdoor Condensing Unit
with Centrifugal Condensing Unit
with Outdoor Condensing Unit
with Centrifugal Condensing Unit
2 Tons
MMD24E
PFH027A
3 Tons
MMD36E
PFH037A
2 Tons
MMD24E
MCD24A
3 Tons
MMD36E
MCD36A
2 Tons
MMD23E
PFH026A
3 Tons
MMD35E
PFH036A
2 Tons
MMD23E
MCD23A
3 Tons
MMD35E
MCD35A
Evaporator
Condensing Unit
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 20,900 (6.1) 26,600 (7.8) 20,300 (5.9) 28,300 (8.3) 20,200 (5.9) 28,400 (8.3) 19,800 (5.8) 27,400 (8.0)
Total 23,800 (7.0) 34,200 (10.0) 22,400 (6.6) 31,700 (9.3) 22,100 (6.5) 32,100 (9.4) 21,000 (6.2) 29,600 (8.7)
Sensible 20,100 (5.9) 25,700 (7.5) 19,500 (5.7) 27,200 (8.0) 19,400 (5.7) 27,400 (8.0) 19,000 (5.6) 26,400 (7.7)
Total 22,900 (6.7) 32,900 (9.6) 21,400 (6.3) 30,400 (8.9) 21,200 (6.2) 30,800 (9.0) 20,100 (5.9) 28,300 (8.3)
Sensible 19,700 (5.8) 25,200 (7.4) 19,100 (5.6) 26,500 (7.8) 19,000 (5.6) 26,700 (7.8) 18,500 (5.4) 25,700 (7.5)
25,600 (7.5) 36,900 (10.8) 24,200 (7.1) 34,100 (10.0) 23,800 (7.0) 34,500 (10.1) 22,700 (6.7) 31,800 (9.3)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 19,800 (5.8) 26,600 (7.8) 19,300 (5.7) 25,300 (7.4) 19,100 (5.6) 25,400 (7.4) 18,700 (5.5) 24,400 (7.1)
Total 23,800 (7.0) 34,200 (10.0) 22,300 (6.5) 31,300 (9.2) 22,000 (6.4) 31,700 (9.3) 20,900 (6.1) 29,300 (8.6)
Sensible 19,200 (5.6) 25,700 (7.5) 18,500 (5.4) 24,300 (7.1) 18,400 (5.4) 24,600 (7.2) 18,000 (5.3) 23,600 (6.9)
Total 22,700 (6.7) 32,900 (9.6) 21,300 (6.2) 29,900 (8.8) 21,100 (6.2) 30,400 (8.9) 20,000 (5.9) 28,000 (8.2)
Sensible 18,700 (5.5) 25,200 (7.4) 18,100 (5.3) 23,900 (7.0) 18,000 (5.3) 24,100 (7.1) 17,500 (5.1) 23,100 (6.8)
25,500 (7.5) 36,900 (10.8) 24,000 (7.0) 33,600 (9.8) 23,700 (6.9) 34,000 (10.0) 22,600 (6.6) 31,500 (9.2)
60 HZ
50 HZ
WATER COOLED
GLYCOL COOLED
WATER COOLED
GLYCOL COOLED
2 Tons
MMD24E
MCD26W
3 Tons
MMD36E
MCD38W
2 Tons
MMD24E
MCD26W
3 Tons
MMD36E
MCD38W
2 Tons
MMD23E
MCD25W
3 Tons
MMD35E
MCD37W
2 Tons
MMD23E
MCD25W
3 Tons
MMD35E
MCD37W
Evaporator
Condensing Unit
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 21,300 (6.2) 29,900 (8.8) 19,900 (5.8) 28,700 (8.4) 20,600 (6.0) 28,900 (8.5) 19,300 (5.7) 27,700 (8.1)
Total 24,600 (7.2) 35,600 (10.4) 21,400 (6.3) 32,700 (9.6) 22,800 (6.7) 33,000 (9.7) 19,800 (5.8) 30,400 (8.9)
Sensible 20,400 (6.0) 28,800 (8.4) 19,100 (5.6) 27,600 (8.1) 19,700 (5.8) 27,700 (8.1) 18,500 (5.4) 26,700 (7.8)
Total 23,400 (6.9) 33,900 (9.9) 20,500 (6.0) 31,300 (9.2) 21,800 (6.4) 31,500 (9.2) 18,700 (5.5) 29,100 (8.5)
Sensible 19,900 (5.8) 28,100 (8.2) 18,700 (5.5) 27,000 (7.9) 19,200 (5.6) 27,100 (7.9) 18,700 (5.5) 26,000 (7.6)
26,600 (7.8) 38,400 (11.3) 23,000 (6.7) 35,200 (10.3) 24,900 (7.3) 35,700 (10.5) 21,300 (6.2) 32,600 (9.6)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible 20,100 (5.9) 26,700 (7.8) 18,800 (5.5) 25,500 (7.5) 19,500 (5.7) 25,700 (7.5) 18,200 (5.3) 24,600 (7.2)
Total 24,200 (7.1) 34,400 (10.1) 21,100 (6.2) 31,800 (9.3) 22,600 (6.6) 32,000 (9.4) 19,600 (5.7) 29,600 (8.7)
Sensible 19,400 (5.7) 25,800 (7.6) 18,100 (5.3) 24,700 (7.2) 18,700 (5.5) 24,800 (7.3) 17,500 (5.1) 23,700 (6.9)
Total 23,000 (6.7) 32,900 (9.6) 20,300 (5.9) 30,500 (8.9) 21,500 (6.3) 30,600 (9.0) 18,800 (5.5) 28,300 (8.3)
Sensible 18,900 (5.5) 25,200 (7.4) 17,700 (5.2) 24,100 (7.1) 18,200 (5.3) 24,200 (7.1) 17,000 (5.0) 23,200 (6.8)
26,200 (7.7) 37,400 (11.0) 22,700 (6.7) 34,200 (10.0) 24,500 (7.2) 34,600 (10.1) 21,100 (6.2) 31,800 (9.3)
60 HZ
50 HZ
CHILLED WATER
3 Tons
3 Tons
Evaporator
MMD40C
MMD39C
Capacity Data BTUH (kW) High Fan Speed
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
49,200 (14.4)
33,100 (9.7)
33,900 (9.9)
27,800 (8.1)
27,100 (7.9)
24,900 (7.3)
49,200 (14.4)
33,100 (9.7)
33,900 (9.9)
27,800 (8.1)
27,100 (7.9)
24,900 (7.3)
Sensible
Capacity Data BTUH (kW) Low Fan Speed
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
40,700 (11.9)
26,900 (7.9)
27,700 (8.1)
22,300 (6.5)
21,700 (6.4)
19,800 (5.8)
40,700 (11.9)
26,900 (7.9)
27,700 (8.1)
22,300 (6.5)
21,700 (6.4)
19,800 (5.8)
Sensible
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001
Download from Www.Somanuals.com. All Manuals Search And Download.
9
5 And 8 Ton Systems
Air-Cooled
Water/Glycol
Chilled-Water
Utilizes Split System Evaporator
Utilizes Split System Evaporator
Cooling Tower
Evaporator
Evaporator
Evaporator
Centrifugal Fan
Condensing Unit
Water/Glycol-
Condensing Unit
Indoor Air-Cooled Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Remote Water/Glycol-Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Chilled-Water Coil
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Drycooler
Expansion
Tank
Evaporator
Evaporator
Prop Fan
Condensing Unit
Pump
Water/Glycol-
Condensing Unit
Outdoor Prop Fan Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Remote Water/Glycol Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Cooling Tower
Evaporator
Evaporator
Evaporator
Centrifugal Fan
Condensing Unit
Water/Glycol-
Condensing Unit
Indoor Air-Cooled Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Remote Water/Glycol-Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Chilled Water-Coil
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Drycooler
Evaporator Supply
Evaporator Return
Condenser Return
Condenser Supply
¬
¬
¬
Expansion Tank
¬
Pump
Evaporator
Evaporator
Prop Fan
Condensing Unit
Water/Glycol-
Condensing Unit
Outdoor Prop Fan Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Remote Water/Glycol-Condensing Unit
Supply & Return Air Ducted
Optional Filter Box/Duct Connection Available
Download from Www.Somanuals.com. All Manuals Search And Download.
10
Specifications
5 And 8 Ton Split Systems
60 Hz
50 Hz
AIR COOLED SYSTEM
w/Outdoor Condensing Unit
5 Tons
w/Centrifugal Condensing Unit
w/Outdoor Condensing Unit
5 Tons
w/Centrifugal Condensing Unit
5 Tons
5 Tons
MMD60E
MCD65A
Evaporator
Condensing Unit
MMD60E
PFH067A
MMD59E
PFH066A
MMD59E
MCD64A
Net Capacity Data*-BTUH (kW)
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
65,000 (19.0)
54,400 (15.9)
60,500 (17.7)
52,600 (15.4)
58,100 (17.0)
51,500 (15.1)
66,200 (19.4)
54,800 (16.1)
61,800 (18.1)
53,100 (15.6)
59,400 (17.4)
52,100 (15.3)
65,400 (19.2)
54,800 (16.1)
60,000 (17.6)
52,600 (15.4)
57,200 (16.8)
51,300 (15.0)
65,500 (19.2)
54,800 (16.1)
61,000 (17.9)
53,000 (15.5)
58,600 (17.2)
51,900 (15.2)
Sensible
WATER COOLED
GLYCOL COOLED
CHILLED WATER
WATER COOLED
GLYCOL COOLED
CHILLED WATER
5 Tons
5 Tons
5 Tons
5 Tons
5 Tons
5 Tons
Evaporator
Condensing Unit
MMD60E
MCD69W
MMD60E
MCD69W
MMD92C
MMD59E
MCD68W
MMD59E
MCD68W
MMD91C
Net Capacity Data*-BTUH (kW)
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
70,800 (20.7)
56,900 (16.7)
66,100 (19.4)
55,200 (16.2)
63,300 (18.5)
54,100 (15.9)
63,400 (18.6)
54,200 (15.9)
59,300 (17.4)
52,500 (15.4)
57,000 (16.7)
51,400 (15.1)
94,000 (27.5)
64,000 (18.8)
62,900 (18.4)
53,300 (15.6)
51,300 (15.0)
48,300 (14.2)
70,000 (20.5)
56,600 (16.6)
65,100 (19.1)
54,800 (16.1)
62,200 (18.2)
53,600 (15.7)
62,000 (18.2)
53,700 (15.7)
57,900 (17.0)
51,900 (15.2)
55,700 (16.3)
50,900 (14.9)
94,000 (27.5)
64,000 (18.8)
62,900 (18.4)
53,300 (15.6)
51,300 (15.0)
48,300 (14.2)
Sensible
60 Hz
50 Hz
AIR COOLED SYSTEM
w/Outdoor Condensing Unit
8 Tons
w/Centrifugal Condensing Unit
8 Tons
w/Outdoor Condensing Unit
8 Tons
w/Centrifugal Condensing Unit
8 Tons
Evaporator
Condensing Unit
MMD96E
PFH096A
MMD96E
MCD96A
MMD95E
PFH095A
MMD95E
MCD95A
Net Capacity Data*-BTUH (kW)
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
100,200 (29.4)
80,500 (23.6)
93,100 (27.3)
78,600 (23.0)
89,200 (26.1)
77,200 (22.6)
95,900 (28.1)
79,400 (23.3)
89,500 (26.2)
77,000 (22.6)
86,800 (25.4)
76,500 (22.4)
96,700 (28.3)
79,300 (23.2)
90,200 (26.4)
77,400 (22.7)
86,200 (25.3)
75,900 (22.2)
93,800 (27.5)
78,300 (22.9)
87,400 (25.6)
76,200 (22.3)
83,600 (24.5)
74,900 (21.9)
Sensible
WATER COOLED
GLYCOL COOLED
CHILLED WATER
WATER COOLED
GLYCOL COOLED
CHILLED WATER
8 Tons
8 Tons
8 Tons
8 Tons
8 Tons
8 Tons
Evaporator
Condensing Unit
MMD96E
MCD98W
MMD96E
MCD98W
MMD8TC
MMD95E
MCD97W
MMD95E
MCD97W
MMD8TC
Net Capacity Data*-BTUH (kW)
80 F (26.7 C) DB
50% RH
75 F (23.9 C) DB
50% RH
72 F (22.2 C) DB
50% RH
Total
Sensible
Total
Sensible
Total
105,000 (30.8)
83,300 (24.4)
97,400 (28.5)
81,300 (23.8)
93,200 (27.3)
79,000 (23.1)
93,000 (27.2)
77,500 (22.7)
86,400 (25.3)
75,000 (22.0)
84,100 (24.6)
75,300 (22.1)
145,600 (42.7)
98,300 (28.8)
96,900 (28.4)
81,400 (23.8)
80,200 (23.5)
74,300 (21.8)
101,100 (29.6)
81,000 (23.7)
93,600 (27.4)
78,700 (23.1)
89,400 (26.2)
77,100 (22.6)
89,600 (26.3)
76,500 (22.4)
84,500 (24.8)
75,600 (22.2)
81,100 (23.8)
73,900 (21.7)
145,600 (42.7)
98,300 (28.8)
96,900 (28.4)
81,400 (23.8)
80,200 (23.5)
74,300 (21.8)
Sensible
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Ensuring The High Availability Of
Mission-Critical Data And Applications.
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
Emerson Network Power, the global leader in enabling business-critical continuity,
ensures network resiliency and adaptability through a family of technologies —
including Liebert power and cooling technologies — that protect and support
business-critical systems. Liebert solutions employ an adaptive architecture that
responds to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility, and reduced capital
equipment and operating costs.
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2007 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
SL-10500 (R12/07)
Printed in USA
Emerson Network Power.
EmersonNetworkPower.com
The global leader in enabling Business-Critical Continuity™.
AC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Racks & Integrated Cabinets
Services
Connectivity
DC Power
Power Switching & Controls
Precision Cooling
Surge Protection