Liebert Network Card Mini Mate2 User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert Mini-Mate21 To 8 Tons  
Overhead Precision Cooling And Humidity Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Liebert Monitoring Solutions:  
When You Need To Know  
You will find a full-range of monitoring and control systems,  
communications modules designed to interface Liebert equipment with  
a variety of building management systems, plus stand-alone monitoring,  
control and leak detection devices.  
Low Total Cost Of Ownership:  
High-Efficiency Compressor. The rotary or scroll  
compressors are both energy-efficient and rugged,  
to ensure continuous operation.  
Local And Remote  
Advanced Monitoring  
Liebert SiteScan® Web offers  
comprehensive, centralized  
monitoring, control, data analysis  
and reporting for a full-range  
of computer support systems. It  
provides web-based site monitoring,  
alarm management and  
Monitoring Panels  
Free-Cooling Option. A second cooling coil allows  
the system to take advantage of colder outdoor  
temperatures and bypass compressor operation.  
These units provide basic monitoring  
and control for a single unit or small  
groups of equipment either at the  
equipment location or to a remote site.  
Building  
Cooling  
Tower  
Products include:  
Liebert Universal Monitor  
Liebert Controllers  
trending/analysis for critical sites.  
Free-Cooling Option  
Products include:  
Liebert SiteScan Web Software  
Free  
Cooling  
Coil  
Leak Detection  
Liebert Liqui-tect® leak detection  
systems alert facility personnel to  
the presence of leaking fluids before  
serious damage results. They provide  
quick sensing and accurate reporting  
of leaks below the floor, above the  
ceiling or at the perimeter of a room.  
Water Temperature Sensor  
Water/  
Glycol  
Condenser  
Field-supplied piping  
Products include:  
When water temperature goes below 45˚F, cooling switches over to  
Free-Cooling operation. A separate chilled water source can also be  
used with Air-Cooled system. Note: Special cupro-nickel free-cooling  
coil must be specified when applied to open cooling tower.  
Liebert Liqui-tect Panel  
Two Channel Direct Read  
Leak Detection  
Liebert Zone Leak Detection Kits  
Liebert Point Leak Detection Sensor  
For further information,  
Third Party Monitoring  
System Connectivity  
The use of open protocols allows  
you to interface Liebert units and  
monitoring systems with other types  
and brands of control equipment  
including BMS, NMS, SCADA and fire  
alarm systems.  
Fundamental Monitoring  
Liebert Nformis  
a centralized monitoring and  
communications software package  
that combines full-scale monitoring  
with cost-effective deployment  
through the use of the existing  
network infrastructure.  
Protocols supported:  
Products include:  
Modbus  
Liebert Nform Software  
BACnet  
Liebert IntelliSlot Web/485  
Card ADPT  
SNMP  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
The Right Size To Fit Your Space And Application  
With more than 10,000 possible configurations, there is a LiebertMini-Mate2 system  
available to fit the needs of many room cooling or spot cooling requirements.  
Liebert Mini-Mate2™ Product  
Features Include:  
A Variety Of Options Help You Meet  
Numerous Applications:  
Available in 1,1.5, 2, 3, 5 & 8 ton capacities  
(3-stage cooling on 8-ton)  
Grille (1-1.5 tons) or Plenum (2-3 tons) that fits 2’x4’  
ceiling grid for direct supply & return air distribution  
Fan speed and/or blower options to handle supply air  
ductwork with higher external static pressures  
Filter box or duct kits to connect to ducted sites  
Hot water reheat to utilize building hot water  
for energy savings  
Self-contained or split systems allow for fitting  
systems with a variety of architectures  
Reliable refrigeration components featuring rotary  
or scroll compressors with copper tube aluminum  
fin coils provide high-efficiency  
Units are fully charged with refrigerant and come  
standard with quick-connect fittings to reduce  
installation time.  
Stainless steel electric reheat and/or canister  
humidifier for humidity control  
High-pressure chilled water systems  
Available in air-cooled, water-cooled, glycol-cooled  
or chilled-water configurations  
Easy-to-use menu-driven microprocessor control  
Optional room sensors available  
Single-point power connection kit to facilitate close  
coupled evaporator & condensing unit wiring  
Multiple air-cooled heat rejection solutions: indoor  
ducted, outdoor, (standard ambient, high ambient  
and Quiet-Line)  
Hot gas bypass for low load applications  
2-way or 3-way water regulating valves rated for  
standard or high-pressure applications  
Unit disconnect, smoke sensor, and/or high-temp  
sensor options  
3-Stage Cooling (8 ton system only)  
100%  
Improved Load Tracking  
Site monitoring and communication devices  
to meet monitoring needs  
R407C refrigerant  
72%  
48%  
Stage 1  
Stage 2  
Stage 3  
A unique compressor staging system utilizes independent 3-ton and  
5-ton circuits to provide better control of room conditions. The unit  
microprocessor continuously monitors recent cooling operation,  
and selects the most economical cooling stage to satisfy demand.  
1-1.5 Ton with grille  
Microprocessor Control Features:  
User-friendly wall-mount display  
Provides precise control of all unit functions  
Temperature Control  
Humidity Control  
Alarm Indication  
Programming  
Auto Restart  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
5-Ton Ducted  
Liebert Mini-Mate2  
Capacity (Tons)  
Product Option Availability  
1
1.5  
2
3
5
8
Chilled Water (rated @ 300 psi static pressure)  
Chilled Water (rated @ 400 psi static pressure)  
Self-Contained Air-Cooled  
Self-Contained Water/Glycol-Cooled  
Split System Air-Cooled w/Centrifugal Indoor Condensing Unit  
Split System Air-Cooled w/Outdoor High Ambient Prop Fan Condensing Unit  
Split System Air-Cooled w/Outdoor Prop Fan Condensing Unit  
Split System Air-Cooled w/Outdoor Quiet-Line Prop Fan Condensing Unit  
Split System Water/Glycol-Cooled (2- or 3-way Valve, 150 or 350 psi)  
50 & 60 Hz voltages  
Canister Humidifier  
Chilled Water w/High Close-Off Pressure Valve  
Direct-Drive Motor/Two-Speed  
Filter Clog Alarm  
High Temp Sensor (Firestat)  
Free-Cooling Coil (Cu or CuNi Versions)  
Hot Gas Reheat (self-contained systems only)  
Hot Water Reheat  
Internal Disconnect Switch  
SCR Reheat  
Smoke Sensor  
Stainless Steel Electric Reheat  
R407C  
High External Static Option  
15’ or 30’ Refrigerant Line Sets (R22 only)  
Condensate Pump Kit  
Duct Kit  
Filter Box  
Remote Sensors  
Single Point Power Kit  
Supply & Return Grille/Plenum  
Liebert Controller  
Liebert Liqui-tect 410 Point Detection Leak Detection Sensor  
Liebert LT460-K Zone Leak Detection Kits  
Liebert IntelliSlot Web/485 Card ADPT  
Liebert ENV-DO Environmental Interface Card  
Liebert AC8 Controller  
Liebert RCM4 Four-Point Dry Contact Monitor  
Liebert Universal Monitor Remote Dry Contact Monitor  
Liebert Site Scan Monitoring  
1 Some option/accessory  
combinations are not available.  
Single-Point Power Kit  
High Static Pressure Option  
8-ton Configuration Shown  
2-3 Ton Shown  
2 For further information,  
Blower  
Evaporator  
Motor  
(or chilled water)  
HEPA Filter Box  
High Static  
Blower Box  
Evaporator  
Evaporator Supply  
¬
¬
¬
¬
Evaporator Return  
Condenser Return  
Condenser Supply  
Condensing Unit  
Field installed single-point power kit  
simplifies connection and installation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
1 And 1-1/2 Ton Systems  
Air-Cooled  
Water/Glycol  
Chilled-Water  
Expansion Tank  
Drycooler  
Pump  
Self-Contained Air-Cooled with Grille  
Self-Contained Glycol System with Grille  
Chilled-Water with Grille  
Expansion Tank  
Drycooler  
Pump  
Self-Contained Glycol System Ducted  
Chilled-Water Ducted  
Self-Contained Air-Cooled Ducted  
Optional Filter Box, Duct Connection Available  
Optional Filter Box, Duct Connection Available  
Optional Filter Box, Duct Connection Available  
Cooling Tower  
Prop Fan  
Condensing  
Unit  
Evaporator  
Split System with Grille  
Self-Contained Water-Cooled with Grille  
Evaporator Supply  
Evaporator Return  
Condenser Return  
Condenser Supply  
¬
Cooling Tower  
Prop Fan  
Condensing  
Unit  
¬
Evaporator  
¬
¬
Split System Ducted  
Self-Contained Water-Cooled Ducted  
Optional Filter Box, Duct Connection Available  
Optional Filter Box, Duct Connection Available  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
Specifications  
1 And 1-1/2 Ton Systems  
60 HZ  
50 HZ  
AIR COOLED SYSTEM  
with Outdoor Condensing Unit  
Split System  
with Centrifugal Condensing Unit  
with Outdoor Condensing Unit  
with Centrifugal Condensing Unit  
Self-Contained  
Self-Contained  
Split System  
1 Ton  
MMD12E  
PFH014A  
1.5 Tons  
MMD18E  
PFH020A  
1 Ton  
MMD12A  
MM2CF  
1.5 Tons  
MMD18A  
MM2CF  
1 Ton  
MMD11E  
PFH013A  
1.5 Tons  
MMD17E  
PFH019A  
1 Ton  
MMD11A  
MM2CF  
1.5 Tons  
MMD17A  
MM2CF  
Evaporator  
Condensing Unit  
Net Capacity Data*BTUH (kW) High Fan Speed  
80 F (27.7) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 11,600 (3.4) 15,500 (4.5) 11,300 (3.3) 15,300 (4.5) 11,700 (3.4) 16,000 (4.7) 11,300 (3.3) 15,900 (4.7)  
Total 13,000 (3.8) 18,400 (5.4) 12,300 (3.6) 18,000 (5.3) 13,300 (3.9) 19,800 (5.8) 12,400 (3.6) 19,500 (5.7)  
Sensible 11,200 (3.3) 15,000 (4.4) 10,900 (3.2) 14,900 (4.4) 11,300 (3.3) 15,600 (4.6) 10,900 (3.2) 15,500 (4.5)  
Total 12,400 (3.6) 17,700 (5.2) 11,800 (3.5) 17,300 (5.1) 12,700 (3.7) 19,000 (5.6) 11,900 (3.5) 18,700 (5.5)  
Sensible 10,900 (3.2) 14,800 (4.3) 10,600 (3.1) 14,600 (4.3) 11,000 (3.2) 15,300 (4.5) 10,700 (3.1) 15,200 (4.5)  
14,100 (4.1) 19,800 (5.8) 13,300 (3.9) 19,300 (5.7) 14,400 (4.2) 21,200 (4.2) 13,400 (3.9) 20,800 (6.1)  
Net Capacity Data*BTUH (kW) Low Fan Speed  
80 F (26.7) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
Total  
Sensible 10,500 (3.1) 13,800 (4.0) 10,200 (3.0) 13,700 (4.0) 10,600 (3.1) 14,400 (4.2) 10,200 (3.0) 14,200 (4.2)  
Total 12,900 (3.8) 18,000 (5.3) 12,300 (3.6) 17,700 (5.2) 13,200 (3.9) 19,200 (5.6) 12,400 (3.6) 18,900 (5.5)  
Sensible 10,100 (3.0) 13,500 (4.0) 9,900 (2.9) 13,400 (3.9) 10,200 (3.0) 14,000 (4.1) 9,900 (2.9) 13,900 (4.1)  
14,000 (4.1) 19,300 (5.7) 13,300 (3.9) 18,800 (5.5) 14,300 (4.2) 20,600 (6.0) 13,400 (3.9) 20,300 (5.9)  
72 F (22.2) DB  
50% RH  
Total  
Sensible  
12,300 (3.6) 17,200 (5.0) 11,800 (3.5) 16,900 (5.0) 12,600 (3.7) 18,400 (5.4) 11,900 (3.5) 18,200 (5.3)  
9,900 (2.9) 13,300 (3.9) 9,700 (2.8) 13,100 (3.8) 10,000 (2.9) 13,800 (4.0) 9,700 (2.8) 14,200 (4.2)  
60 HZ  
50 HZ  
WATER COOLED  
GLYCOL COOLED  
WATER COOLED  
GLYCOL COOLED  
Self-Contained  
Self-Contained  
Self-Contained  
Self-Contained  
1 Ton  
MMD14W  
1.5 Tons  
MMD20W  
1 Ton  
MMD14W  
1.5 Tons  
MMD20W  
1 Ton  
MMD13W  
1.5 Tons  
MMD19W  
1 Ton  
MMD13W  
1.5 Tons  
MMD19W  
Evaporator  
Net Capacity Data*BTUH (kW) High Fan Speed  
80F (26.7) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 12,500 (3.7) 16,600 (4.9) 12,000 (3.5) 15,800 (4.6) 12,400 (3.6) 15,500 (4.5) 12,000 (3.5) 16,400 (4.8)  
Total 13,900 (4.1) 20,500 (6.0) 12,800 (3.8) 18,600 (5.4) 13,900 (4.1) 21,300 (6.2) 12,900 (3.8) 20,000 (5.9)  
Sensible 12,000 (3.5) 16,100 (4.7) 11,600 (3.4) 15,400 (4.5) 12,000 (3.5) 15,100 (4.4) 11,600 (3.4) 15,900 (4.7)  
Total 13,300 (3.9) 19,600 (5.7) 12,300 (3.6) 17,900 (5.2) 13,300 (3.9) 20,400 (5.6) 12,400 (3.6) 19,200 (5.6)  
Sensible 11,800 (3.5) 15,800 (4.6) 11,400 (3.3) 15,100 (4.4) 11,800 (3.5) 14,900 (4.4) 11,400 (3.3) 15,700 (4.6)  
15,000 (4.4) 22,000 (6.4) 13,700 (4.0) 19,900 (5.8) 15,000 (4.4) 23,000 (6.7) 13,900 (4.1) 21,300 (6.2)  
Net Capacity Data*BTUH (kW) Low Fan Speed  
80 F (26.7) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 11,000 (3.2) 14,800 (4.3) 10,500 (3.1) 13,900 (4.1) 11,000 (3.2) 17,300 (5.1) 10,600 (3.1) 14,600 (4.3)  
Total 13,500 (4.0) 19,700 (5.8) 12,500 (3.7) 17,800 (5.2) 13,500 (4.0) 22,200 (6.5) 12,600 (3.7) 19,300 (5.7)  
Sensible 10,700 (3.1) 14,400 (4.2) 10,200 (3.0) 13,600 (4.0) 10,600 (3.1) 16,900 (5.0) 10,300 (3.0) 14,300 (4.2)  
Total 12,900 (3.8) 18,900 (5.5) 12,000 (3.5) 17,100 (5.0) 12,900 (3.8) 21,200 (6.2) 12,100 (3.5) 18,600 (5.4)  
Sensible 10,400 (3.0) 14,200 (4.2) 10,000 (2.9) 13,400 (3.9) 10,400 (3.0) 16,500 (4.8) 10,100 (3.0) 14,000 (4.1)  
14,600 (4.3) 21,100 (6.2) 13,400 (3.9) 18,900 (5.5) 14,500 (4.2) 23,900 (7.0) 13,500 (4.0) 20,700 (6.1)  
60 HZ  
50 HZ  
CHILLED WATER  
Self-Contained  
1.5 Tons  
Self-Contained  
1.5 Tons  
Evaporator  
MMD23C  
MMD22C  
Capacity Data BTUH (kW) High Fan Speed  
80 F (26.7) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
21,800 (6.4)  
16,000 (4.7)  
14,300 (4.2)  
13,100 (3.8)  
11,000 (3.2)  
11,000 (3.2)  
21,800 (6.4)  
16,000 (4.7)  
14,300 (4.2)  
13,100 (3.8)  
11,000 (3.2)  
11,000 (3.2)  
Sensible  
Capacity Data BTUH (kW) Low Fan Speed  
80 F (26.7) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
17,100 (5.2)  
12,800 (3.7)  
11,300 (3.1)  
10,300 (3.0)  
8,500 (2.5)  
8,500 (2.5)  
17,100 (5.2)  
12,800 (3.7)  
11,300 (3.1)  
10,300 (3.0)  
8,500 (2.5)  
8,500 (2.5)  
Sensible  
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
2 And 3 Ton Systems  
Air-Cooled  
Water/Glycol  
Chilled-Water  
Utilizes Split System Evaporator  
Utilizes Split System Evaporator  
Centrifugal Fan  
Condensing Unit  
Expansion Tank  
Water/Glycol  
Condensing Unit  
Evaporator  
Evaporator  
Drycooler  
Pump  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Plenum  
Chilled-Water  
Remote Air-Cooled Condensing Unit  
Supply & Return Air Plenum  
Supply & Return Plenum  
Centrifugal Fan  
Condensing Unit  
Expansion Tank  
Water/Glycol  
Evaporator  
Condensing Unit  
Evaporator  
Drycooler  
Pump  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box, Duct Connection Available  
Chilled-Water  
Supply & Return Air Ducted  
Optional Filter Box, Duct Connection Available  
Remote Air-Cooled Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box, Duct Connection Available  
Cooling Tower  
Water/Glycol  
Note: All split systems may be  
close-coupled or configured with  
condensing unit located remotely  
from the evaporator.  
Prop Fan  
Condensing Unit  
Evaporator  
Condensing Unit  
Evaporator  
Pump  
Outdoor Prop Fan Condensing Unit  
Supply & Return Air Plenum  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Plenum  
Cooling Tower  
Prop Fan  
Evaporator Supply  
Evaporator Return  
Condenser Return  
Condenser Supply  
Condensing Unit  
¬
Water/Glycol  
Condensing Unit  
Evaporator  
Evaporator  
¬
¬
¬
Pump  
Outdoor Prop Fan Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box, Duct Connection Available  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box, Duct Connection Available  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
Specifications  
2 And 3 Ton Split Systems  
60 HZ  
50 HZ  
AIR COOLED SYSTEM  
with Outdoor Condensing Unit  
with Centrifugal Condensing Unit  
with Outdoor Condensing Unit  
with Centrifugal Condensing Unit  
2 Tons  
MMD24E  
PFH027A  
3 Tons  
MMD36E  
PFH037A  
2 Tons  
MMD24E  
MCD24A  
3 Tons  
MMD36E  
MCD36A  
2 Tons  
MMD23E  
PFH026A  
3 Tons  
MMD35E  
PFH036A  
2 Tons  
MMD23E  
MCD23A  
3 Tons  
MMD35E  
MCD35A  
Evaporator  
Condensing Unit  
Net Capacity Data*BTUH (kW) High Fan Speed  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 20,900 (6.1) 26,600 (7.8) 20,300 (5.9) 28,300 (8.3) 20,200 (5.9) 28,400 (8.3) 19,800 (5.8) 27,400 (8.0)  
Total 23,800 (7.0) 34,200 (10.0) 22,400 (6.6) 31,700 (9.3) 22,100 (6.5) 32,100 (9.4) 21,000 (6.2) 29,600 (8.7)  
Sensible 20,100 (5.9) 25,700 (7.5) 19,500 (5.7) 27,200 (8.0) 19,400 (5.7) 27,400 (8.0) 19,000 (5.6) 26,400 (7.7)  
Total 22,900 (6.7) 32,900 (9.6) 21,400 (6.3) 30,400 (8.9) 21,200 (6.2) 30,800 (9.0) 20,100 (5.9) 28,300 (8.3)  
Sensible 19,700 (5.8) 25,200 (7.4) 19,100 (5.6) 26,500 (7.8) 19,000 (5.6) 26,700 (7.8) 18,500 (5.4) 25,700 (7.5)  
25,600 (7.5) 36,900 (10.8) 24,200 (7.1) 34,100 (10.0) 23,800 (7.0) 34,500 (10.1) 22,700 (6.7) 31,800 (9.3)  
Net Capacity Data*BTUH (kW) Low Fan Speed  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 19,800 (5.8) 26,600 (7.8) 19,300 (5.7) 25,300 (7.4) 19,100 (5.6) 25,400 (7.4) 18,700 (5.5) 24,400 (7.1)  
Total 23,800 (7.0) 34,200 (10.0) 22,300 (6.5) 31,300 (9.2) 22,000 (6.4) 31,700 (9.3) 20,900 (6.1) 29,300 (8.6)  
Sensible 19,200 (5.6) 25,700 (7.5) 18,500 (5.4) 24,300 (7.1) 18,400 (5.4) 24,600 (7.2) 18,000 (5.3) 23,600 (6.9)  
Total 22,700 (6.7) 32,900 (9.6) 21,300 (6.2) 29,900 (8.8) 21,100 (6.2) 30,400 (8.9) 20,000 (5.9) 28,000 (8.2)  
Sensible 18,700 (5.5) 25,200 (7.4) 18,100 (5.3) 23,900 (7.0) 18,000 (5.3) 24,100 (7.1) 17,500 (5.1) 23,100 (6.8)  
25,500 (7.5) 36,900 (10.8) 24,000 (7.0) 33,600 (9.8) 23,700 (6.9) 34,000 (10.0) 22,600 (6.6) 31,500 (9.2)  
60 HZ  
50 HZ  
WATER COOLED  
GLYCOL COOLED  
WATER COOLED  
GLYCOL COOLED  
2 Tons  
MMD24E  
MCD26W  
3 Tons  
MMD36E  
MCD38W  
2 Tons  
MMD24E  
MCD26W  
3 Tons  
MMD36E  
MCD38W  
2 Tons  
MMD23E  
MCD25W  
3 Tons  
MMD35E  
MCD37W  
2 Tons  
MMD23E  
MCD25W  
3 Tons  
MMD35E  
MCD37W  
Evaporator  
Condensing Unit  
Net Capacity Data*BTUH (kW) High Fan Speed  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 21,300 (6.2) 29,900 (8.8) 19,900 (5.8) 28,700 (8.4) 20,600 (6.0) 28,900 (8.5) 19,300 (5.7) 27,700 (8.1)  
Total 24,600 (7.2) 35,600 (10.4) 21,400 (6.3) 32,700 (9.6) 22,800 (6.7) 33,000 (9.7) 19,800 (5.8) 30,400 (8.9)  
Sensible 20,400 (6.0) 28,800 (8.4) 19,100 (5.6) 27,600 (8.1) 19,700 (5.8) 27,700 (8.1) 18,500 (5.4) 26,700 (7.8)  
Total 23,400 (6.9) 33,900 (9.9) 20,500 (6.0) 31,300 (9.2) 21,800 (6.4) 31,500 (9.2) 18,700 (5.5) 29,100 (8.5)  
Sensible 19,900 (5.8) 28,100 (8.2) 18,700 (5.5) 27,000 (7.9) 19,200 (5.6) 27,100 (7.9) 18,700 (5.5) 26,000 (7.6)  
26,600 (7.8) 38,400 (11.3) 23,000 (6.7) 35,200 (10.3) 24,900 (7.3) 35,700 (10.5) 21,300 (6.2) 32,600 (9.6)  
Net Capacity Data*BTUH (kW) Low Fan Speed  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible 20,100 (5.9) 26,700 (7.8) 18,800 (5.5) 25,500 (7.5) 19,500 (5.7) 25,700 (7.5) 18,200 (5.3) 24,600 (7.2)  
Total 24,200 (7.1) 34,400 (10.1) 21,100 (6.2) 31,800 (9.3) 22,600 (6.6) 32,000 (9.4) 19,600 (5.7) 29,600 (8.7)  
Sensible 19,400 (5.7) 25,800 (7.6) 18,100 (5.3) 24,700 (7.2) 18,700 (5.5) 24,800 (7.3) 17,500 (5.1) 23,700 (6.9)  
Total 23,000 (6.7) 32,900 (9.6) 20,300 (5.9) 30,500 (8.9) 21,500 (6.3) 30,600 (9.0) 18,800 (5.5) 28,300 (8.3)  
Sensible 18,900 (5.5) 25,200 (7.4) 17,700 (5.2) 24,100 (7.1) 18,200 (5.3) 24,200 (7.1) 17,000 (5.0) 23,200 (6.8)  
26,200 (7.7) 37,400 (11.0) 22,700 (6.7) 34,200 (10.0) 24,500 (7.2) 34,600 (10.1) 21,100 (6.2) 31,800 (9.3)  
60 HZ  
50 HZ  
CHILLED WATER  
3 Tons  
3 Tons  
Evaporator  
MMD40C  
MMD39C  
Capacity Data BTUH (kW) High Fan Speed  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
49,200 (14.4)  
33,100 (9.7)  
33,900 (9.9)  
27,800 (8.1)  
27,100 (7.9)  
24,900 (7.3)  
49,200 (14.4)  
33,100 (9.7)  
33,900 (9.9)  
27,800 (8.1)  
27,100 (7.9)  
24,900 (7.3)  
Sensible  
Capacity Data BTUH (kW) Low Fan Speed  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
40,700 (11.9)  
26,900 (7.9)  
27,700 (8.1)  
22,300 (6.5)  
21,700 (6.4)  
19,800 (5.8)  
40,700 (11.9)  
26,900 (7.9)  
27,700 (8.1)  
22,300 (6.5)  
21,700 (6.4)  
19,800 (5.8)  
Sensible  
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
5 And 8 Ton Systems  
Air-Cooled  
Water/Glycol  
Chilled-Water  
Utilizes Split System Evaporator  
Utilizes Split System Evaporator  
Cooling Tower  
Evaporator  
Evaporator  
Evaporator  
Centrifugal Fan  
Condensing Unit  
Water/Glycol-  
Condensing Unit  
Indoor Air-Cooled Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Chilled-Water Coil  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Drycooler  
Expansion  
Tank  
Evaporator  
Evaporator  
Prop Fan  
Condensing Unit  
Pump  
Water/Glycol-  
Condensing Unit  
Outdoor Prop Fan Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Remote Water/Glycol Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Cooling Tower  
Evaporator  
Evaporator  
Evaporator  
Centrifugal Fan  
Condensing Unit  
Water/Glycol-  
Condensing Unit  
Indoor Air-Cooled Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Chilled Water-Coil  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Drycooler  
Evaporator Supply  
Evaporator Return  
Condenser Return  
Condenser Supply  
¬
¬
¬
Expansion Tank  
¬
Pump  
Evaporator  
Evaporator  
Prop Fan  
Condensing Unit  
Water/Glycol-  
Condensing Unit  
Outdoor Prop Fan Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Remote Water/Glycol-Condensing Unit  
Supply & Return Air Ducted  
Optional Filter Box/Duct Connection Available  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Specifications  
5 And 8 Ton Split Systems  
60 Hz  
50 Hz  
AIR COOLED SYSTEM  
w/Outdoor Condensing Unit  
5 Tons  
w/Centrifugal Condensing Unit  
w/Outdoor Condensing Unit  
5 Tons  
w/Centrifugal Condensing Unit  
5 Tons  
5 Tons  
MMD60E  
MCD65A  
Evaporator  
Condensing Unit  
MMD60E  
PFH067A  
MMD59E  
PFH066A  
MMD59E  
MCD64A  
Net Capacity Data*-BTUH (kW)  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
65,000 (19.0)  
54,400 (15.9)  
60,500 (17.7)  
52,600 (15.4)  
58,100 (17.0)  
51,500 (15.1)  
66,200 (19.4)  
54,800 (16.1)  
61,800 (18.1)  
53,100 (15.6)  
59,400 (17.4)  
52,100 (15.3)  
65,400 (19.2)  
54,800 (16.1)  
60,000 (17.6)  
52,600 (15.4)  
57,200 (16.8)  
51,300 (15.0)  
65,500 (19.2)  
54,800 (16.1)  
61,000 (17.9)  
53,000 (15.5)  
58,600 (17.2)  
51,900 (15.2)  
Sensible  
WATER COOLED  
GLYCOL COOLED  
CHILLED WATER  
WATER COOLED  
GLYCOL COOLED  
CHILLED WATER  
5 Tons  
5 Tons  
5 Tons  
5 Tons  
5 Tons  
5 Tons  
Evaporator  
Condensing Unit  
MMD60E  
MCD69W  
MMD60E  
MCD69W  
MMD92C  
MMD59E  
MCD68W  
MMD59E  
MCD68W  
MMD91C  
Net Capacity Data*-BTUH (kW)  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
70,800 (20.7)  
56,900 (16.7)  
66,100 (19.4)  
55,200 (16.2)  
63,300 (18.5)  
54,100 (15.9)  
63,400 (18.6)  
54,200 (15.9)  
59,300 (17.4)  
52,500 (15.4)  
57,000 (16.7)  
51,400 (15.1)  
94,000 (27.5)  
64,000 (18.8)  
62,900 (18.4)  
53,300 (15.6)  
51,300 (15.0)  
48,300 (14.2)  
70,000 (20.5)  
56,600 (16.6)  
65,100 (19.1)  
54,800 (16.1)  
62,200 (18.2)  
53,600 (15.7)  
62,000 (18.2)  
53,700 (15.7)  
57,900 (17.0)  
51,900 (15.2)  
55,700 (16.3)  
50,900 (14.9)  
94,000 (27.5)  
64,000 (18.8)  
62,900 (18.4)  
53,300 (15.6)  
51,300 (15.0)  
48,300 (14.2)  
Sensible  
60 Hz  
50 Hz  
AIR COOLED SYSTEM  
w/Outdoor Condensing Unit  
8 Tons  
w/Centrifugal Condensing Unit  
8 Tons  
w/Outdoor Condensing Unit  
8 Tons  
w/Centrifugal Condensing Unit  
8 Tons  
Evaporator  
Condensing Unit  
MMD96E  
PFH096A  
MMD96E  
MCD96A  
MMD95E  
PFH095A  
MMD95E  
MCD95A  
Net Capacity Data*-BTUH (kW)  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
100,200 (29.4)  
80,500 (23.6)  
93,100 (27.3)  
78,600 (23.0)  
89,200 (26.1)  
77,200 (22.6)  
95,900 (28.1)  
79,400 (23.3)  
89,500 (26.2)  
77,000 (22.6)  
86,800 (25.4)  
76,500 (22.4)  
96,700 (28.3)  
79,300 (23.2)  
90,200 (26.4)  
77,400 (22.7)  
86,200 (25.3)  
75,900 (22.2)  
93,800 (27.5)  
78,300 (22.9)  
87,400 (25.6)  
76,200 (22.3)  
83,600 (24.5)  
74,900 (21.9)  
Sensible  
WATER COOLED  
GLYCOL COOLED  
CHILLED WATER  
WATER COOLED  
GLYCOL COOLED  
CHILLED WATER  
8 Tons  
8 Tons  
8 Tons  
8 Tons  
8 Tons  
8 Tons  
Evaporator  
Condensing Unit  
MMD96E  
MCD98W  
MMD96E  
MCD98W  
MMD8TC  
MMD95E  
MCD97W  
MMD95E  
MCD97W  
MMD8TC  
Net Capacity Data*-BTUH (kW)  
80 F (26.7 C) DB  
50% RH  
75 F (23.9 C) DB  
50% RH  
72 F (22.2 C) DB  
50% RH  
Total  
Sensible  
Total  
Sensible  
Total  
105,000 (30.8)  
83,300 (24.4)  
97,400 (28.5)  
81,300 (23.8)  
93,200 (27.3)  
79,000 (23.1)  
93,000 (27.2)  
77,500 (22.7)  
86,400 (25.3)  
75,000 (22.0)  
84,100 (24.6)  
75,300 (22.1)  
145,600 (42.7)  
98,300 (28.8)  
96,900 (28.4)  
81,400 (23.8)  
80,200 (23.5)  
74,300 (21.8)  
101,100 (29.6)  
81,000 (23.7)  
93,600 (27.4)  
78,700 (23.1)  
89,400 (26.2)  
77,100 (22.6)  
89,600 (26.3)  
76,500 (22.4)  
84,500 (24.8)  
75,600 (22.2)  
81,100 (23.8)  
73,900 (21.7)  
145,600 (42.7)  
98,300 (28.8)  
96,900 (28.4)  
81,400 (23.8)  
80,200 (23.5)  
74,300 (21.8)  
Sensible  
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Ensuring The High Availability Of  
Mission-Critical Data And Applications.  
Liebert Corporation  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, Ohio 43229  
800 877 9222 Phone (U.S. &  
Canada Only)  
Emerson Network Power, the global leader in enabling business-critical continuity,  
ensures network resiliency and adaptability through a family of technologies —  
including Liebert power and cooling technologies — that protect and support  
business-critical systems. Liebert solutions employ an adaptive architecture that  
responds to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility, and reduced capital  
equipment and operating costs.  
614 888 0246 Phone (Outside U.S.)  
614 841 6022 FAX  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
Italy  
39 049 9719 111 Phone  
39 049 5841 257 FAX  
Emerson Network Power Asia Pacific  
7/F., Dah Sing Financial Centre  
108 Gloucester Rd, Wanchai  
Hong Kong  
852 25722201 Phone  
852 28029250 FAX  
liebert.com  
24 x 7 Tech Support  
800 222 5877 Phone  
614 841 6755 (outside U.S.)  
While every precaution has been taken to ensure accuracy and  
completeness in this literature, Liebert Corporation assumes no  
responsibility, and disclaims all liability for damages resulting  
from use of this information or for any errors or omissions.  
© 2007 Liebert Corporation. All rights reserved throughout  
the world. Specifications subject to change without notice.  
All names referred to are trademarks or registered trademarks  
of their respective owners.  
® Liebert and the Liebert logo are registered trademarks  
of the Liebert Corporation.  
SL-10500 (R12/07)  
Printed in USA  
Emerson Network Power.  
EmersonNetworkPower.com  
The global leader in enabling Business-Critical Continuity.  
AC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Services  
Connectivity  
DC Power  
Power Switching & Controls  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2007 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Krown Manufacturing Smoke Alarm KA300 User Manual
Lennox Hearth Stove 290M User Manual
Lexmark All in One Printer X644E User Manual
Lincoln Electric Welder 455 M User Manual
Logitech Headphones Wireless Headset H800 User Manual
Makita Drill MODEL 6019D User Manual
Marantz Stereo Amplifier MM9000 User Manual
Memorex DVD Player MMP8568 HIT User Manual
Memorex Stereo System MX5510 User Manual
Michelin Automobile Parts LIGHT TRUCK TIRE User Manual